Beruflich Dokumente
Kultur Dokumente
The effects of back-pressures on safety valves is a potentially serious problem, but one only now being recognised by
the valve industry. Research has been performed by the University of Milan, as reported in the June 2002 issue of
Valve World. This report is also printed in full below. In addition, please note that RWTH's Hans-Dieter Werker has
presented a paper entitled "Influence of back pressure on function and flow rate of a direct loaded safety valve" at the
Valve World 2002 Conference in Maastricht.
10 barg
Overpressure
10%
Blowdown
< 7%
0.2barg
3.5 barg
4.5 barg
Atmospheric back-pressure
Set pressure measurement : the pressure in the supply tank is slowly increased: The set pressure value is
detected through hearing.
Discharge coefficient measurement: the discharge coefficient is measured at 10% overpressure of the set
pressure stated at point 1.1
Re-seating pressure measurement: the re-seating pressure is evaluated by slowly decreasing the supply tank
pressure until the disc returns to the initial position.
Built-up back pressure: the range of stable operation under built-up back-pressure condition is investigated. The
valve is operated starting from the same condition as at point 1.2; subsequently, the back pressure is slowly
increased by shuttering the exhaust of the back-pressure tank, whilst the relieving pressure is kept constant. The
upper limit of the operational built-up back-pressure range is detected by the appearance of instability in the
valve lift. The trend of valve lift and discharge coefficient as functions of the back-pressure ratio are recorded by
the data acquisition system.
3. Superimposed back pressure : the back-pressure tank is operated at constant pressure. Under this condition
tests described at point 1.1, 1.2 and 1.3 are repeated at almost three different back-pressure values within the
range specified in Table 1.
Blow down %
(1-Pre seating/Pset)*100
37 %
7.3 %
6.7 %
5.6 %
5.33
K/Knom
At 10% over pressure.
1.02
1.0
0.95
1.01
0.95
Figure 1 : Reduction of the discharge coefficient referred to the one declared at atmospheric back
pressure: experimental results and manufacturer declared values.
Results show that the expected de-rating of the flow rate of valves B and C and E is strongly under estimated.
Moreover a very surprising result is found for valve E: in particular the valve shows a dramatic flow capacity decrease
when back-pressure reaches the 18%. No further tests were performed on this device, because when the valve was
operated during the first test at super-imposed back pressure, the bellows broke. In the author's opinion the bellows
was operating correctly when the built-up back-pressure test was performed, but this hypothesis cannot be
confirmed. However this accident underlines the importance of the reliability of the bellows, and supports the
requirement highlighted in [1], paragraph 5.1.8: " In the case of failure of a balanced bellows, if any, the safety valve
shall discharge its certified capacity at no more than 1.1. times the maximum allowable pressure of the equipment
being protected".
Referring to valve A, the de-rating trend is clearly foreseen by the manufacturer and the flow capacity reduction is
quite low. Note that at a back-pressure ratio of 68% the discharge coefficient has undergone a reduction of only 20%;
on the other hand the valve shows great difficulty in the re-seating process, as already shown by the high value of
blowdown measured in the atmospheric back-pressure tests. This will also be noticed in the superimposed backpressure tests.
The manufacturer of valve B declares that the discharge coefficient is not sensitive to the back-pressure ratio until it
reaches 50%, where a 3% de-rating of K is expected. On the contrary, experimental results show that the discharge
coefficient experiences a progressive linear reduction starting from a back-pressure ratio of 20 % up to the 48%,
where the discharge coefficient rate is about 2/3 of that of the atmospheric back pressure. Moreover at the same
built-up back-pressure ratio, the valve shows clear instability and the disc tends to re seat.
As for valve C, the manufacturer declares that the built-up back pressure does not affect the discharge capacity; the
plot clearly shows that this feature is not representative of the actual valve behaviour: the measurements show a
dramatic reduction of the flow capacity, already at back-pressure ratios of less then 30% (K/Knom = 0.63); raising the
back pressure the discharge coefficient is reduced to a minimum value of 43% of the nominal one.
Also the manufacturer of valve D states that no reduction in the discharge coefficient is expected for back-pressure
ratio within 25% while measurements show a reduction of K/Knom to 0.95; the flow capacity reduces to 80 % of the
nominal rate for a back-pressure ratio of 34%, beyond which the disc rapidly re-seats.
Results of superimposed back-pressure tests
Tests under superimposed back-pressure aim to verify the functional and flow capacity characteristics of safety
valves within the limiting overpressure of 10%, evaluated on the basis of the set pressure measured in the
atmospheric back-pressure tests.
Valve A has been tested at three different values of back pressure up to a back-pressure ratio of 65%. All tests show
the same features: the valve pops before the 10% overpressure and the discharge coefficient reaches the same
value measured in the built-up back-pressure tests for the same back-pressure ratio. As already mentioned, this
clearly predicted behaviour is followed by quite a high blowdown; in particular the blowdown is reduced with respect
to the atmospheric tests (37% in tab. 1) and keeps reducing with the increasing back pressure: moving (increasing)
from a back-pressure ratio of 40% to 65% the blowdown reduces from 16.5% to 12%, in any case exceeding the limit
of 7% declared by the manufacturer.
Valve B experiences the pop-up before the 10% overpressure is reached only for back-pressure ratio of less than
33%; for higher back-pressure ratios the pop up requires overpressures rising up to 13% at 37% back pressure,
which corresponds to the limit indicated in the technical specification. Once the valve has opened, the discharge
coefficient reaches the same values measured in the built-up back-pressure tests; clearly when the sample does not
open, the flow capacity is very low. The blowdown is always within the declared limits.
Valve C opens within the 10% overpressure and closes within the declared limit; the discharge coefficient always
reaches the same values measured in the built-up back-pressure tests, but it is necessary to remember that the flow
rates are very small if compared to the declared values (see valve C in fig. 1)
Finally, valve D opens within 10% overpressure only for a back-pressure ratio of less than 25%, as specified by the
manufacturer. Over this limit the opening of the valve requires an overpressure of 16% for a back-pressure ratio of
30%. The blowdown corresponds to the manufacturer's declaration and, once again, the discharge coefficient
reaches the same value recorded in the built-up back-pressure tests.
Conclusions
The results of a wide campaign of operating and flow tests performed on five commercial safety valves, supplied
according to the same technical specifications have been presented and discussed. Valve performance has been
compared to that declared by the manufacturer highlighting the following main features:
Atmospheric back-pressure tests show fairly good agreement to manufacturer's declaration for four of the
five samples, whilst only one sample shows a blowdown of 37% instead of the declared 10%.
Superimposed and built-up back-pressure tests show several differences with the manufacturer's
declarations both in terms of operating and flow performance.
One of the five balancing bellows failed at the beginning of the back-pressure tests.
Therefore it is quite possible that, during on-site applications, when the valve is required to open under back-pressure
conditions, the protected equipment may be exposed to pressure higher than 1.1 times the maximum allowable
pressure. This can be due to the valve's inability to pop-up within the overpressure limit and/or to the reduction of the
flow capacity caused by a poor disk lift and/or to the establishment of a subsonic regime, also when the backpressure ratio is below the critical level (0.528).
This data highlights the need for future standards which clearly require a well defined test procedure for the
evaluation of the behaviour of safety valves operating under back pressure. Things can be further complicated when
a full valve size range has to be characterised by testing only a few samples which comply with the test rig limits; in
fact laboratory tests performed on safety valve models show that body size and outlet to nozzle area ratio strongly
influence the flow capacity within the same size range. [2].
Only extensive laboratory tests will allow us to reasonably foresee the performance of a full size range when the
valve is operated under back pressure and will improve the safety conditions of plants and pressure equipment.
[1 ] prEN ISO 4126-1: January 2000 :"Safety Valves for protection against excessive pressure- Part 1: Safety Valves
(and ISO/DIS 4126-1.2: 2001-11-29, same title)
[2] V. Dossena et al, "On The Influence Of Back Pressure And Size On The Performance Of Safety Valves", to be
presented at 2002 Pressure Vessels and Piping Conference (ASME), Vancouver, August 2002.