The purpose of this White Paper is to offer the necessary The “Double G” is able to distinguish between each type of
guidelines for the correct implementation of the “Double G” fault, restricted and unrestricted, thanks to a chrono-ampero-
function of ABB SACE low voltage circuit-breakers. With this metric discrimination and to the MV/LV integration.
function it is possible to ensure protection against:
− − earth faults downstream the circuit-breaker on the secon-
dary side of the Medium/Low voltage (MV/LV) transformer It is always available on New Emax circuit-breakers equipped
(unrestricted earth faults or downstream earth faults); with PR123/P LSIG trip units and on X1 circuit-breakers
− − earth faults between the transformer secondary windings equipped with PR333/P LSIG trip units. The “Double G” func-
and its cables connected to the circuit-breaker terminals tion is easy to install and doesn’t require special wiring.
(restricted earth faults or upstream earth faults).
MV CB ACB
MV side LV side
Homopolar
toroid
Time-Current curve only the case in which the trip unit is programmed to allow
the opening is taken into consideration.
1Es
This possible trip cannot guarantee the complete plant pro-
tection because the fault occurs between the secondary of
100s
the transformer and the circuit-breaker terminals.
0.1s Once the fault has been detected, the trip unit can made
Internal G: I4=0.2xIn, t4=0.25s available an output signal to the MV circuit-breaker. The MV
circuit-breaker detects the signal and commands the opening
0.1kA 1kA 10kA of the breaker ensuring the complete protection of the plant.
Figure 3 – Possible curves of the External and Internal G protections.
Let’s suppose that an unrestricted fault - downstream fault -
occurs in the plant:
The settings of G and Gext protections must guarantee the
discrimination: the Gext curve has always to be set at a higher
Transformer
value than G curve. secondary winding
L1
Circuit-breaker
Internal CTs
Now, let’s suppose that a restricted fault - upstream fault -
occurs in the plant. L2
Transformer
secondary winding L3
L1
N
Circuit-breaker External
Internal CTs toroid
PE
L2
Figure 5
L3
Both G, external and internal, are activated and go into the
N
External “timing” phase. By apposite current and time settings of
toroid
PE both protections (Internal G and External G), the low voltage
circuit-breaker trips thanks to the internal G protection, assur-
ing fault extinction and avoiding unnecessary opening of MV
circuit breaker.
Figure 4
Firstly the Gext protection is activated and, after the Gext Therefore, thanks to the time-current discrimination between
protection timing, the low voltage circuit-breaker can open: in the two G protection functions, before the MV breaker re-
fact, in the trip unit, it is possible to select if the breaker must ceives the opening command, the low voltage breaker is able
open or remain closed after Gext protection timing; hence to trip and eliminate the unrestricted earth fault.
MV CB
Electrical distribution plant
Homopolar toroid
MV-LV
E2N 1600 4p
PR123/P LSIG
MCCB MCCB
LSIG LSIG
M
MCCB MCCB
LSIG LSIG
L L
A4
X K9 K10 K8 K6 K4 K10 K8 K6 K4
XV K9 K10 K8 K6 K4 K10 K8 K6 K4
K10
K10
K9
K8
K6
K4
K8
K6
K4
XK6 9 XK6 7 XK6 5 XK6 3 XK6 1 XK6 9 XK6 7 XK6 5 XK6 5 XK6 1
module PR120/K
module PR120/K
Signalling
Signalling
A1 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51
K51 K51
IN1 p1 p2 p3 p4 IN1 p1 p2 p3 p4
PR123/P PR123/P
XK6 10 XK6 8 XK6 6 XK6 4 XK6 2 XK6 10 XK6 8 XK6 6 XK6 4 XK6 2
K7
K5
K3
K9
K7
K5
K3
XV K7 K5 K3 K9 K7 K5 K3
X K7 K5 K3 K9 K7 K5 K3
A4
Figure 7 – PR120/K (4 Outputs + 1 Input with common terminal) Figure 8 – PR120/K (4 Outputs with independent terminals)
W3
W4
W3
W4
K1
K2
K1
K2
XV K1 K2 W3 W4 XV K1 K2 W3 W4
X K1 K2 W3 W4 X13 K1 K2 W3 W4
+ +
– 24 V – 24 V
A4 A4 A13
11 13 15 17 19 21 23 25 1 2 7 8 11 13 15 17 19 21 23 25 1 2 7 8
K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51 K51
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
12 14 14 18 20 22 24 26 10 PR021/K 12 14 14 18 20 22 24 26 10 PR021/K
PR123/P
k51
PR333/P
PR330/D-M module only
module or PR333/P with
For PR123/P with PR120/D-M
XV W1 X2 XV K2 K1 W3 W4
X W1 X2 X K2 K1 W3 W4
W2
(A) (B)
W1 +
– 24 V
W2
12 10 7 6 14 16 13 20 1 2 23 24
(A) (B)
D01 D02 D03 D04 D05 D06 D07 D07
A31
11 9 8 5 13 15 17 19 3 LD030 DO
Figure 10 – LD030 DO
PR120/K – PR021/K contact Monostable STDP −− and finally, to make the interlocking cabling between the
Maximum switching power (resistive load) 100W / 1250 VA signalling unit and the shunt opening release of the medium
Maximum switching voltage 130 V DC / 250 V AC voltage circuit-breaker. For example, when the K51/P1
Maximum switching current 5A
contact (PR120K) closes, the medium voltage shunt open-
Breaking capacity (resistive load) @ 30V DC 3.3 A
ing release receive the signal and command the opening of
@ 250V AC 5 A
Contact/coil insulation 2000V r.m.s. (1min@50Hz) the MV circuit-breaker (Figure 11).
It follows that:
XK6 7 − − the MV CB opens, since it is activated by the contact;
−− the LV CB opens. As already described above, the trip unit
X21/d10
-AR
is enabled to open the LV circuit-breaker because of Gext
K51
p1 (803) X21/d12 protection. In the most common plants, the LV circuit-
breaker must to open when the MV circuit breaker trips
XK6 8 due to the Gext protection.
K9
K9
K9
-XX 11
Caption -TR1 ˜ +
-XB11 2 K10
AR: REF 542 protection unit Transformer K10
BB1, BB3: auxiliary contacts -MO1 secondary winding
˜
K10
TR1: AC/DC converters L1
MO1: opening coil
-XB 8 Emax XK6 7
K51/p1: contact of PR120/K module internal CTs
Figure 11
Transformer K10
secondary winding K9
K10
L1 K9
Emax
internal CTs XK6 7
Figure 13 – Unrestricted fault
L2
Unrestricted fault is detected by both the homopolar toroid
and by the internal G, but, because of the settings, internal
K51
p1 G protection is faster than external G protection (Gext). The
L3 contact remains open because the protection “Gext” goes
into protection timing but the fault is extinguished before the
N
External protection timing phase ends.
toroid
PE XK6 8
It follows that:
K9
K10
Transformer K10
secondary winding
K10
L1
XK6 7
ACB internal MCCB internal
current sensors current sensors
L2
K51
p1
L3
N
External
toroid XK6 8
PE
K9
K9
K9
4.1 Shopping list section 1. External homopolar toroid installation and settings
Homopolar Terminal
In range
4.2 Testing field section Toroid clamp Box on CB
1 T7
In this section it is shown how to set each device in order to 2 T8 100 / 250A
make available the “Double G” function. The customer has to 3 T8 400 / 800 A
SD-TestBus2
Figure – 17
1
In SD-TestBus2, in order to set the LD030 DO, use the PR021/K page con-
figuration.
4. select “Gext alarm (blocked trip)” Connect the PR010/T to the trip unit:
5. set this contact to “NO” (normally open)
6. press "Submit" 1. select “Operation mode” and press “Enter”
2. select DUT “PR123” for New Emax CB or “PR333” for X1
and press “Enter”
It is also possible to choose:
3. select “4. Config/Param” and press “Enter”
− − contact “Latched” or “Not latched”. Contact “latched” is
activated when the associated event happens; they are 4. choose “1. Configurations” and press “Enter”
reset only by the reset of the circuit-breaker or of trip unit; 5. select “9. Modules” and press “Enter”
− − it is possible to set a delay time, i.e. a time shift respect to 6. select “3. Signalling” and press “Enter”
the event that changes the normal status of the contact.
7. select “1. Relay 1” and press “Enter”
8. select “1. Signal source” and press “Enter”
SD-Pocket 9. insert Password (if required) and then press “Enter”
10. select, by , the signal source “Custom” and press
1. Start SD-pocket tool “Enter”
2. Log-in as Administrator 11. move, by , to “Alarm 2 1…3”
3. Select the device PR123/P or PR333/P (on the trip unit a
device type PR120/D-BT or BT030 must be installed) 12. set the blinking cursor to “Gext alarm”, scroll and
4. Press “Connect”, press “Enter”
5. In the toolbar, select “Menu” select “PR120/K configu- select “Gext alarm” , press and press “Enter”.
ration” (or PR021/K or LD030 DO configuration”) 13. enter in “Configuration”, select NO (Normally Open).
6. In Function, select “Custom” 14. press “Esc” until you have the possibility to save the con-
7. Move to “Byte Offset #8” figuration
8. Select “Gext alarm (blocked trip)” 15. save Configuration.
9. Set this contact to “NO” (normally open)
10. In order to accept the configuration, press “SET”
11. “Yes” to save.
B) Instruction to set PR021/K and LD030 DO signalling 3. Trip unit protection settings
modules.
The parameters of internal G protection and external G pro-
tection (Gext) have to be set in order to guarantee a chrono-
amperometric discrimination between the two curves: protec-
tion Gext settings must have both trip thresholds and trip time
parameters higher than those set for protection G.
Please note:
G protection Trip threshold I4 = 0.2 xIn = 160A Trip Time t = 0.25s t=k
Gext protection Trip threshold I4 = 0.5 xIn = 400A Trip Time t = 0.5s t=k
The signalling unit must be connected to the trip unit. Con-
nect PR010/T to the trip unit and repeat the steps from 1 to 4
of the PR120/K setting, and afterwards:
In order to avoid the opening of the low voltage circuit-breaker
1. select “10. Local Bus Unit” and press “Enter” after the Gext protection trip, in case of restricted earth fault,
2. select “2. Relay 1” and press “Enter” follow these instructions:
Follow the instructions of PR120/K from the 8th step.
1. select “Protection” in the Main Menu of the trip unit
2. select “Gext Protection”
It is also possible to choose: 3. press “Enable” and enter the password
− − contact “Latched” or “Not latched”. 4. select “On”
− − it is possible to set a delay time, i.e. a time delay with 5. select “Trip Enable”
respect to the event that changes the normal status of the 6. select “OFF”
contact. 7. press “Esc” and confirm the changes.
ABB SACE The data and illustrations are not binding. We reserve
1SDC007403G0201 - 03/2009
the right to modify the contents of this document on
A division of ABB S.p.A. the basis of technical development of the products,
L.V. Breakers without prior notice.
Via Baioni, 35 Copyright 2009 ABB. All rights reserved.
24123 Bergamo - Italy
Tel.: +39 035 395 111
Fax: +39 035 395306-433
www.abb.com