Enercon Systems Pvt Ltd

EM6400v02.01.02 Register Map EMS Version 01.01.02

Last Updated on Mon, Oct 21, 02

Configuring EM6400 with eLAN


1. EM 6000 operates in two modes. One is in EM3000 compatible mode and second is in
Enhanced mode. Enhanced mode details will be given separately. Presently EM6000 is
configured in EM3000 compatible mode. The scaling of data (tags) is not needed unless
otherwise specified. To access any parameter, the parameters block starting address and
parameters block ending address should be configured as a parameter and then the required
parameter should be configured. The default settings in EM6400 is as follows.
1.1. EM6400 Default Settings
Communication Protocol: Modbus (RTU)
Baud Rate: 9600 bps
Data bits: 8
Stop bits: 1
Parity: Even
1.2. Data type: Float for all parameters unless otherwise specified.
1.2.1. Except for parameter:
1.2.1.1. Intr (number of interrupts in instantaneous parameter block) - unsigned integer
data type.
1.2.1.2. RunSecs (Run seconds in Integrated blocks) unsigned integer data type
1.3. Data format: Count, direct value no scaling is required unless otherwise specified.
Parameters: Read Only. Write to parameters is not yet supported.
2. EM 6400 was tested successfully for communication using Wonderware InTouch 7.1. Details
regarding the settings made in InTouch is given below.
2.1. Wonderware InTouch 7.1 Settings to establish communication with EM6400
Modbus Protocol Settings
COM Port Setting in Wonderware Modicon Modbus
Protocol: RTU
Baud Rate: 9600
Data bits: 8
Stop bits: 1
Parity: Even
Topic Definition in Wonderware Modicon Modbus
Slave Device Type: 584/984 PLC
Register Type: BINARY
Block I/O Sizes:
Coil Read: 32
Coil Write: 32

Register Read: 20
Register Write: 20

Access Name in InTouch


Application Name: Modbus
Topic Name: The topic name should be the exact same name configured for topic in the
Modbus Topic definition.
Protocol to use: DDE

EM6400v02.01.02_EMSRegisterMap_v01.01.02.sdw

1 of 4

Enercon Systems Pvt Ltd

EM6400v02.01.02 Register Map EMS Version 01.01.02

Last Updated on Mon, Oct 21, 02

3. New in v02.01.02
3.1. The Rows highlighted in Pale Blue New parameters in Forward Integrate block 3120
VARh (inductive) and VARh (capacitive) available in display and communication.
3.2. The Rows highlighted in Pale Yellow VAR, VARr, VARy, VARb are now available in
meter display and communication (Version 01.01.02 provided these parameters thru'
communication )
4. Total / Average Instantaneous Parameter Block: 3000 to 3019. Block size: 20.
Slno

Paramet
ers

Intouch Data
type

Format1

Min.
EU & RAW

Max.
EU & RAW

1.

VA

I/O Real

Count

-9999E+09

9999E+09

43001 F

2.

I/O Real

Count

-9999E+09

9999E+09

43003 F

3.

VAR

I/O Real

Count

-9999E+09

9999E+09

43005 F

4.

PF

I/O Real

Count

-9999E+09

9999E+09

43007 F

5.

VLL

I/O Real

Count

-9999E+09

9999E+09

43009 F

6.

VLN

I/O Real

Count

-9999E+09

9999E+09

43011 F

7.

I/O Real

Count

-9999E+09

9999E+09

43013 F

8.

Hz

I/O Real

Count

9999E+09

43015 F

9.

Intr

I/O Real

Count

4295E+06

43019 L

Intouch Address

5. R-Phase Instantaneous Parameter Block: 3030 to 3049. Block size: 20.

Slno

Paramet
ers

Intouch Data
type

Format

Min.
EU & RAW

Max.
EU & RAW

Intouch Address

1.

VAr

I/O Real

Count

-9999E+09

9999E+09

43031 F

2.

Wr

I/O Real

Count

-9999E+09

9999E+09

43033 F

3.

VARr

I/O Real

Count

-9999E+09

9999E+09

43035 F

4.

PFr

I/O Real

Count

-9999E+09

9999E+09

43037 F

5.

VLLry

I/O Real

Count

-9999E+09

9999E+09

43039 F

6.

VLNr

I/O Real

Count

-9999E+09

9999E+09

43041 F

7.

Ar

I/O Real

Count

-9999E+09

9999E+09

43043 F

8.

Hz

I/O Real

Count

9999E+09

43045 F

9.

Intr

I/O Real

Count

4295E+06

43049 L

Count means direct value no scaling is required.

EM6400v02.01.02_EMSRegisterMap_v01.01.02.sdw

2 of 4

Enercon Systems Pvt Ltd

EM6400v02.01.02 Register Map EMS Version 01.01.02

Last Updated on Mon, Oct 21, 02

6. Y-Phase Instantaneous Parameter Block: 3060 to 3079. Block size: 20.


Slno

Paramet
ers

Intouch Data
type

Format

Min.
EU & RAW

Max.
EU & RAW

Intouch Address

1.

VAy

I/O Real

Count

-9999E+09

9999E+09

43061 F

2.

Wy

I/O Real

Count

-9999E+09

9999E+09

43063 F

3.

VARy

I/O Real

Count

-9999E+09

9999E+09

43065 F

4.

PFy

I/O Real

Count

-9999E+09

9999E+09

43067 F

5.

VLLyb

I/O Real

Count

-9999E+09

9999E+09

43069 F

6.

VLNy

I/O Real

Count

-9999E+09

9999E+09

43071 F

7.

Ay

I/O Real

Count

-9999E+09

9999E+09

43073 F

8.

Hz

I/O Real

Count

9999E+09

43075 F

9.

Intr

I/O Real

Count

4295E+06

43079 L

7. B-Phase Instantaneous Parameter Block: 3090 to 3109. Block size: 20.


Slno

Paramet
ers

Intouch Data
type

Format

Min.
EU & RAW

Max.
EU & RAW

Intouch Address

1.

VAb

I/O Real

Count

-9999E+09

9999E+09

43091 F

2.

Wb

I/O Real

Count

-9999E+09

9999E+09

43093 F

3.

VARb

I/O Real

Count

-9999E+09

9999E+09

43095 F

4.

PFb

I/O Real

Count

-9999E+09

9999E+09

43097 F

5.

VLLbr

I/O Real

Count

-9999E+09

9999E+09

43099 F

6.

VLNb

I/O Real

Count

-9999E+09

9999E+09

43101 F

7.

Ab

I/O Real

Count

-9999E+09

9999E+09

43103 F

8.

Hz

I/O Real

Count

9999E+09

43105 F

9.

Intr

I/O Real

Count

4295E+06

43109 L

8. Forward Integrated parameter Block: 3120 to 3139. Block size: 20.


Slno

Paramet
ers

Intouch Data
type

Format

Min.
EU & RAW

Max.
EU & RAW

1.

VAh

I/O Real

Count

-9999E+09

9999E+09

43121 F

2.

Wh

I/O Real

Count

-9999E+09

9999E+09

43123 F

VARh

I/O Real

Count

-9999E+09

9999E+09

43125 F

3.

Intouch Address

Inductive

4.

PF Avg

43127 F

5.

VLL Avg

43129 F

6.

VARh

I/O Real

Count

-9999E+09

9999E+09

43131 F

Capacitive

7.

Ah

EM6400v02.01.02_EMSRegisterMap_v01.01.02.sdw

43133 F

3 of 4

Enercon Systems Pvt Ltd

EM6400v02.01.02 Register Map EMS Version 01.01.02

Intouch Data
type

Slno

Paramet
ers

8.

Hz avg

43135 F

9.

Start
time

43137 L

10.

Runsecs

I/O Real

Format

Count

Min.
EU & RAW

Last Updated on Mon, Oct 21, 02

Max.
EU & RAW

4295E+06

Intouch Address

43139 L

Note:
1 The Min. EU & RAW and MAX EU & RAW is 1:1. The values shown are Minimum limit and
Maximum limits that can be set. Depending on your requirement change the Minimum and
Maximum limits.
1.1 For e.g. If VLN parameter minimum is 50v and maximum 240v then MIN EU & RAW
should have 50 and MAX EU & RAW should have 240.
2 The rows highlighted in 20% gray Forward Integrate block 3120 PFAvg, VLL Avg, Ah,
HzAvg and Start time are not available in this version and will always have values as zero.
3 All Number are in Decimal Number System.
4 The following parameters are available in the Meter display but not available in the meter
communication port
4.1 On Hours
4.2 Current Phase Angle r-Phase
4.3 Current Phase Angle y-Phase
4.4 Current Phase Angle b-Phase

EM6400v02.01.02_EMSRegisterMap_v01.01.02.sdw

4 of 4