PACiS Technical Training Level 2
CS&P Support Team

PCL

Content
 Circuit Breaker
 Disconnector Switch
 Transformer
 Generic Module

Schneider Electric - CS&P Basic Modules Configuration E01

Content
 Circuit Breaker
 Disconnector Switch
 Transformer
 Generic Module

Schneider Electric - CS&P Basic Modules Configuration E01

Add / Configure a CB
1) Circuit Breaker can be added at Bay level in Electric hierarchy.
CB 3 phases (1 DPS for global position) / CB 1 phase (single phase acq.)
2) CB attributes
Short Name :
SCE Key + appears in viewers + printers

CB Type :
3-ph, 1-ph, other

Nodes definition :
AVR

Schneider Electric - CS&P Basic Modules Configuration E01

CB-1ph Configuration (1)


1) CB 1 phase basic configuration
1.1) Type 1
Typed CB Computed Position DPS :
- Global CB Position, computed by C264
- is feedback of DPC command
- is animated on PACiS OI / C264 LCD

Typed Switchgear ph A,B,C DPS :


CB single phase position, acquired by C264
(DI/CCU or IED)

Typed Switch Ctrl DPC :


1.2) Type 2

DPC Open/Close

Position can be computed by :


- typed Switch ph A DPS
- typed Phases Not Together SPS
Note : Positions can be SPS
Schneider Electric - CS&P Basic Modules Configuration E01

CB-1ph Configuration (2)


2) CB enhanced configuration => possible sons
Typed Lock Control SPC :
Operator lock

Typed Selection SPC :


when SBO, activated at selection

Typed Sync CB Close :


Synchrocheck

Typed Lock SPS :


Lock status

Typed Phase Not Together SPS :


- Indicates if all phases are in same position
- holds a timer for CB trip

Typed withdrawn SPS :


brushable devices

Schneider Electric - CS&P Basic Modules Configuration E01

CB-3ph Configuration
1) CB 3 phases basic configuration
1.1) Type 1
Typed Switch Ctrl DPC :
DPC Open/Close

Typed CB Computed Position DPS :


- Global CB Position, computed by C264
- is feedback of DPC command
- is animated on PACiS OI / C264 LCD

Typed Switchgear position DPS :


CB Position, acquired by C264 (DI/CCU or IED)

1.2) Type 2
Typed Switch Ctrl DPC can be replaced by :
- typed Switch Ctrl SPC for CLOSE
- typed Switch ph A SPC for OPEN
Note : Positions can be SPS
Schneider Electric - CS&P Basic Modules Configuration E01

Content
 Circuit Breaker
 Disconnector Switch
 Transformer
 Generic Module

Schneider Electric - CS&P Basic Modules Configuration E01

Add / Configure a Disconnector Switch


1) Disconnector switch is a Switchgear, it can be added at Bay level in
Electric hierarchy.
2) DS attributes
Short Name :
SCE Key + appears in viewers + printers

Nodes definition :
AVR

Schneider Electric - CS&P Basic Modules Configuration E01

Switchgear Configuration (1)


1) Switchgear basic configuration
Typed Switch Ctrl DPC :
DPC Open/Close

Typed Switchgear position DPS :


Switchgear Position, acquired by C264 (DI/CCU
or IED)

Note : Position can be SPS


Schneider Electric - CS&P Basic Modules Configuration E01

10

Switchgear Configuration (2)


2) Switchgear enhanced configuration => possible sons
Typed Lock Control SPC :
Operator lock

Typed Selection SPC :


when SBO, activated at selection

Typed Lock SPS :


Lock status

Typed withdrawn SPS :


brushable devices

Schneider Electric - CS&P Basic Modules Configuration E01

11

Content
 Circuit Breaker
 Disconnector Switch
 Transformer
 Generic Module

Schneider Electric - CS&P Basic Modules Configuration E01

12

Add / Configure a Transformer


1) Transformer module can be added at Transformer or Generic Bay level in
Electric hierarchy.
2) Transformer attributes
Short Name :
SCE Key + appears in viewers + printers

Transformer Type :
- Auto wound : no galvanic isolation between HV
and LV sides, tap changer acts simultaneously in
primary and secondary : TAP RAISE = LV LOWER
- Double wound : galvanic isolation between HV
and LV sides, tap changer acts in primary : TAP
RAISE = LV RAISE

Power value / impedance :


AVR

Nodes definition :
AVR
Schneider Electric - CS&P Basic Modules Configuration E01

13

Transformer Configuration (1)


1) Transformer basic configuration
Tap Changer built-in function:
cf. DATAPOINTS CONFIGURATION course

Typed Raise/Lower DPC :


Tap Change control

Typed TPI MV :
cf. DATAPOINTS CONFIGURATION course

Schneider Electric - CS&P Basic Modules Configuration E01

14

Transformer Configuration (2)


2) Transformer enhanced configuration => possible sons
Typed MCB Open SPC :
- AVR
- In case of invalid tap changing, it will stop
supplying tap changer (power cutting)

Typed TAP Select SPC :


when SBO, activated at selection

Typed Higher Position / Lower Position SPS :


- SET when max tap and min tap are reached

Typed Tap in progress SPS :


- physically acquired by C264
- impact on control sequence

Typed Goto min/max DPC :


DPC doing raise until max tap / lower until min
tap

Schneider Electric - CS&P Basic Modules Configuration E01

15

Content
 Circuit Breaker
 Disconnector Switch
 Transformer
 Generic Module

Schneider Electric - CS&P Basic Modules Configuration E01

16

Features
1) Generic Modules are :
- non typed modules
- contains generic datapoints
- huge range of use => non particular context

- ADVISE : DONT USE GENERIC MODULES for CB and disconnector if you


have :
- Built-in automation (AVR, Synchrocheck, Autorecloser)
- lock, hardware selection, withdrawn

Example for switching device

Schneider Electric - CS&P Basic Modules Configuration E01