Beruflich Dokumente
Kultur Dokumente
Design Considerations
Factors Many factors influence the proper
selection of the type of substation for a
given application. Factors such as voltage
levels, load capacity, environmental
considerations, site space limitations, and transmission-line right-of-way
requirements are imperative.
Sites for substations are generally selected so that the stations will be as near as
possible to the load center of the distribution areas which they are intended to
serve. Availability of land, cost, local zoning laws, future load growth and taxes
are just a few of the many factors which must be considered before a site is
ultimately chosen.
In addition, design criteria such as (1) Bus layout, (2) Choice of Insulation Level
(3) High level of service continuity (4) Expansion (5) flexibility of operations, and
(6) Low initial and ultimate cost. Selection of optimum voltage levels depend on
the load requirements and transmission-line distances involved. The substations
used in distribution systems operate at voltage class from 13.8 to 69kV.
Transmission substations serving bulk power sources operate at voltages from 69
to 765kV. The choice of insulation levels and coordination practices affects cost
considerably. A drop of one level in BIL can reduce the equipment cost by the
thousand. A substation must be reliable, economical, safe and as simple in design
as possible. Means should be provided for maintaining lines, breaker, and
switches with no service interruptions or hazard to personnel. The physical
orientation of the transmission-line routes often dictates the substations location
and bus arrangement. For reliability, the substation design should prevent total
substation shutdown caused by breaker failure or bus faults and should be such
as to permit rapid restoration of service after a fault occurs. The layout must
permit future additions and extensions without interrupting service.
Types of Substations
Classifications and Types Substations have step-down transformers, high voltage
switches and oil circuit breakers and lightning arresters located just outside the
substation building within which are located the distribution and street lighting
facilities. Substations can be classified in a number of ways.
Classification of Substations:
Service
Alternating Current
AC to DC
Function Tap
Distributing
Industrial
Control
Sectionalizing
Transmission-Line
Power-Factor Correction
Frequency Changer
Portable/Unit
Manual
Semiautomatic
Automatic
Supervisory
enough for general distribution and utilization. In many cases, all high-tension
equipment is placed outdoors, while low-tension equipment is placed indoors.
Industrial Substation are used when fairly large blocks of power are required by
industrial plants. Its simplest form would comprise only of switching equipment,
there being no voltage transformation. If the latter is needed, transformer
equipment is included. Sectionalizing Substations are used in very long highvoltage large-capacity lines, particularly when several circuits are run in parallel,
thus it is necessary to split the lines into sections, in order that proper protection
to the line and service be obtained. It will generally comprise only of switching
equipment. In long lines, it may also serve to supply power-factor-correction.
Transmission-Line Supply Substation steps up the generator voltage for highvoltage transmission lines. Power-Factor Correction Substations controls the
voltage and the power factor of the line through the use of synchronous
condensers. It will include switching equipment, transformers, and all equipment
necessary for the operation of the condensers. Frequency Changer Substations
used to interconnect two systems of different frequencies, such as 25 hz and 60
hz.
Control of Substations
Manual Control is applicable only to small-capacity substations. All the
disconnecting switches, circuit breakers, and other equipment are manually
controlled.
Semiautomatic Control Majority of stations fall under this class. Control is
obtained from a switchboard through mechanically or electrically remote
methods, but all control is dependent upon the operator in charge at the
substation.
Automatic Control substations are entirely unattended, started up and shut down
automatically.
Supervisory Control The operation of the substation is under direct control of an
operator located at a considerable distance away.
Switching Schemes
Main Bus Connections The substation scheme selected determines the electrical
ad physical arrangement of the switching equipment. Different bus schemes are
dependent on the factors of reliability, economy, safety, and simplicity as
warranted by the function and importance of the substation. The bus scheme
more often used as (a) Single Bus, (b) Double bus, double breaker (c) Main and
transfer bus (d) Double bus, single breaker (e) Ring bus, and (f) Breaker and a
half. Some of these schemes maybe modified by the addition of bus-tie breakers,
bus sectionalizing devices, breaker bypass facilities and extra transfer buses.
Single Bus is not normally used for major substations. Dependence on one main
bus can cause serious outage in the event of breaker or bus failure. The station
must be deenergized in order to carry out bus maintenance or add bus
normal operating conditions all breakers are closed and both buses are energized.
A circuit is tripped by opening the two associated circuit breakers. Tie breaker
failure will trip one additional circuit, but no additional circuit is lost if a line trip
involves failure of line breaker. Either bus maybe taken out of service at any time
with no loss of service. With sources connected opposite loads, it is possible to
operate both buses out of service. Breaker maintenance can be done with no loss
of service, no relay changes, and simple operation of the breaker disconnects. It
is more expensive than the other schemes, except the double-breaker-double-bus
scheme. It is, however, superior in flexibility, reliability, and safety. Protective
relaying and automatic reclosing are more complex than other schemes.
Physical Arrangements
Once the switching scheme is determined, it is necessary to consider the station
arrangement, as follows: (a) Conventional outdoor open-type bus-and-switch, (b)
Inverted-bus substation and (c) Sulfur hexaflouride gas mini-type metal-clad
substation.
Outdoor open-type bus-and-switch
arrangements consist essentially of openbus construction using either rigid- or
strain-bus design or combination of rigid
and strain bus. The buses are arranged to
run the length of the station and are located
toward the outside of the station.
Transmission-line exits cross over the main
bus and are dead-ended on takeoff tower
structures. The line drops into the bay in the
station and connects to the the
disconnecting switches and circuit breakers.
It requires three distinct levels of bus to
make the necessary crossovers and
connections to each substation bay. Typical
dimensions of these levels at 230kV, for
example, are 16 ft for the first level above
ground, 30 ft high for the main bus location
and 57 ft for the highest level of bus. It
required a minimum land area per bay and
relative ease of maintenance, and is ideally
suited to a transmission-line through
connection where a substation must be cut
into a line right-of-way.
Inverted Bus uses the breaker-and-a-half scheme, usually used for EHV
substations. All outgoing circuit takeoff towers are located in the outer perimeter
of the substation, eliminating the crossover of line and exit facilities. Main buses
are located in the middle of the substation, with all disconnecting switches,circuit
breakers, and all bay equipment located outboard of the main buses. It offers
advantages such as beauty due to very low profile and aesthetic qualities.
Distribution: Substation Design: Components
Substation Components
1. Switching Equipment and Devices include circuit breakers, disconnecting
switches, and grounding switches.
2. Transformers include metering transformers [current transformers, potential
transformers] or capacitor voltage transformers, and power transformers.
3. Line Traps are discussed fully on Plant Operation and Maintenance. They are
used to make the transmission line appear as a simple two-terminal line used in
telephone circuits.
4. Capacitors and Reactors include coupling capacitors, series and shunt
capacitors; shunt and current-limiting reactors.
5. Station Buses and Insulators carry high amounts of energy in a confined space.
Design factors involve utilization of electric energy adequately and economically
and provide sufficient structural strength to withstand the maximum stresses that
maybe imposed on the conductors. Two designs are: the (1) strain-bus design,
used primarily on high-voltage, is similar to a transmission line and consists of a
conductor usually ACSR, copper, or high-strength aluminum strung between
substation structures; and (2) rigid-bus design used for extra-high-voltages. The
design of station buses depends on the following: (a) Current-carrying capacity,
(b) Short-circuit stresses, and (c) minimum electrical clearances. The currentcarrying capacity of a bus is limited by the heating effects produced by the
current. The permissible temperature rise for plain copper and aluminum buses is
limited to 30 degrees Centigrade above an ambient temperature of 40. Many
factors enter into the heating of a bus, such as the type of material used, the size
and shape of the conductor, the surface are of the conductor and its condition,
skin effect, proximity effect, conductor clearance, ventilation, and inductive
heating caused by the proximity of magnetic materials. Bus Materials, aside from
the two previously mentioned, with hard-drawn aluminum in tubular shape are
most widely used in HV and EHV open-type outdoor stations. Skin Effect in a
conductor carrying an alternating current is the tendency toward crowding if the
current into the outer layer, or "skin" of the conductor due to the self-inductance
of the conductor increasing the effective resistance and lower current rating for a
given temperature rise. Proximity effect is the distortion of the current distribution
caused by the induction between the out and return conductors causing a
concentration of current in the parts of the buses nearest each other, thus
increasing their effective resistance. Thermal expansion and contraction of bus
conductors is limited through the use of expansion joints and clamps permitting
the tubing to slide. Bus Spacing is standardized for respective BILs. Clearances
should be adequate for both line-to-ground and phase-to-phase values.
Coordinate kV class and BIL when choosing minimum values but maybe decrease
in line with good practice, depending on local conditions, procedures. etc.
6. Lightning Arresters and/or Gaps are discussed fully on Plant Operation and
Maintenance: Protection Systems.
7. Grounding Systems provides (a) the ground connection for the grounded
neutral for transformers, reactors and capacitors, (b) the discharge paths for
lightning rods, arresters, gaps and similar devices, (c) safety to operating
personnel by limiting potential differences, (d) means of discharging and
deenergizing equipment for maintenance practices, and (e) a sufficiently low
resistance path to ground to minimize rise in ground potential with respect to
remote ground. The basic substation ground system takes the form of a grid of
horizontally buried conductors, usually AWG 4/0 bare stranded copper cable
buried 12 to 18 in below grade and spaced in a grid pattern of about 10 to 20 feet.
Methods of testing ground resistance fall into three general groups; (a)
Triangulation or three-point methods, in which two auxiliary test grounds and the
point to be measured .
8. Support Structures are usually made of steel, aluminum, or wood, and concrete
foundations. The typical open-type substation requires strain structures to
support the transmission line conductors and other substation components.
When the structures are made of steel or aluminum they require concrete
foundation, however, when they are made of wood, concrete foundations are not
required. Fabricated aluminum or steel equipment support structures may consist
of single wide-flange or tubular-type columns. Rigid-frame structures are
composed of wide flanges or tubular sections. Lattice Structures are made of
angle members. The design of supporting structures is affected by phase
spacings and ground clearances required, by the type of insulators, by the length
and weight of buses and other equipment, and by the wind and ice loading. Other
structural and concrete work required includes site selection and preparation,
roads, control houses, manholes, conduits, ducts, drainage facilities, catch basin
and fences. Site Selection includes the study of the topography and drainage
patterns of the area together with a subsurface soil investigation.
Distribution: Substation Design: Protection
Substation Components
Protective Relaying is a system aimed to protect the equipment associated with
the station, the most important of which are:
a. Transmission line emanating from the station
include circuit breakers, disconnecting switches, and grounding switches.
2. Transformers include metering transformers [current transformers, potential
transformers] or capacitor voltage transformers, and power transformers.
3. Line Traps are discussed fully on Plant Operation and Maintenance. They are
used to make the transmission line appear as a simple two-terminal line used in
telephone circuits.
8. Support Structures are usually made of steel, aluminum, or wood, and concrete
foundations. The typical open-type substation requires strain structures to
support the transmission line conductors and other substation components.
When the structures are made of steel or aluminum they require concrete
foundation, however, when they are made of wood, concrete foundations are not
required. Fabricated aluminum or steel equipment support structures may consist
of single wide-flange or tubular-type columns. Rigid-frame structures are
composed of wide flanges or tubular sections. Lattice Structures are made of
angle members. The design of supporting structures is affected by phase
spacings and ground clearances required, by the type of insulators, by the length
and weight of buses and other equipment, and by the wind and ice loading. Other
structural and concrete work required includes site selection and preparation,
roads, control houses, manholes, conduits, ducts, drainage facilities, catch basin
and fences. Site Selection includes the study of the topography and drainage
patterns of the area together with a subsurface soil investigation.
Distribution: Substation Design: Protection