Beruflich Dokumente
Kultur Dokumente
General
The Maxigas controller is capable of supporting direct Modbus communication via its integral RS485 connection. This industry standard
connection allows multiple generators to communicate with a remote Modbus master on a network up to 1000m in length. The Maxigas
generator can be programmed with its own unique address, to allow multiple generators to be connected to an existing network.
The remote Modbus master can request all of the information available on the Maxigas controller as well as remotely starting and stopping
the generator.
PC
Modbus
Master
Junction
box
Maxigas
NODE 1
Maxigas
NODE 2
Maxigas
NODE 3
Press [
The generator will complete the current cycle and then exhaust both beds. This may take several
minutes particularly on ppm generators.
Once the generator is in Standby mode disconnect it from the electrical supply.
Generator connection
Open the lower access door and, using a 4mm Allen key, remove the two cap head fixing screws from the underside of the upper panel. Lift the
upper panel and offset it to the right to retain it.
All connections should be made to the three way terminal block marked RS 485 MODBUS as shown below.
In order to maintain the IP rating of the generator, the cable entering the electrical enclosure must do so through the dedicated cable gland
located on the side of the generator. The cable should be of circular cross section and have a diameter between 3 and 6.5mm.
Parker domnick hunter recommends the use of a twisted pair screened cable of at least 0.5mm2 to connect the generators to the Modbus
master. Cable lengths should not exceed 500m [1650 ft] for 0.5mm2 - 0.75mm2 (1000m [3300 ft] for 0.75mm2 - 1.0mm2 ). The cable screen
should be terminated at the terminal marked GND. It is suggested that only the controller end of the screen is connected to earth.
If more than one Maxigas generator is to be connected on to the network it will be necessary to allocate a unique address to each generator.
Refer to section 4 of the user guide supplied with the generator for details on changing the generator address.
To start and stop the generator remotely, the remote control setting in menu 3.11 must be altered. Refer to section 4 of the user guide supplied
with the generator for details on how to change this parameter.
Note. When the generator is configured for remote operation, the start button on the controller will no longer function. For safety reasons the
stop button will continue to operate.
- +
+ + - + + - -
13
14
24 VDC / 2.1A
L1
L1
L1
L1
L1
PIN
1
4 5
4-20mA
INPUT
RS-485
MODBUS
GND
24V
A B
SIGNAL
JP19
INPUT
4
TxD
INPUT
3
RxD
INPUT
2
GND
2
INPUT
1
1
2
3
NAME
- +
02
SENSOR
GND
24VDC
INPUT
FUNCTION
RS485 L1+
RS485 L1-
GND
Screen
- +
Communication rate - the required baud rate for MODBUS communication with the Maxigas is 9600 baud, 8 data bits, no parity, 1 stop bit.
NOTE: the generator uses the MODBUS RTU variant. This system is not compatible with the ASCII variant.
The MODBUS address to access each dryer is the same as the network address of the Maxigas controller. This can be found in menu
3.10 of the control system. The default setting for the Maxigas generator is 1.
Data
Address
(hex)
Description
Data Type
Notes
This is a discrete ON/OFF value:
0x0000
Modbus Control
0x0001
Relay
0x0002
Relay
0x0003
Relay
0x0004
Relay
0x0005
Relay
0x0006
Relay
0x0007
Relay
0x0008
Relay
10
0x0009
Relay
11
0x000A
Relay
12
0x000B
Relay
13
0x000C
Relay
14
0x000D
Fault Code S1
Fault
15
0x000E
Fault Code C1
Fault
16
0x000F
Fault Code P1
Fault
17
0x0010
Fault Code P2
Fault
18
0x0011
Fault Code Y1
Fault
19
0x0012
Fault Code Y2
Fault
20
0x0013
Fault Code Y3
Fault
21
0x0014
Fault Code Y4
Fault
22
0x0015
Fault Code Y5
Fault
Note 1: Modbus control is used to tell the generator to start and stop. This does not indicate the run status of the generator.
0 Stop
1 Start
Data
Address
(hex)
10001
10002
Description
Data Type
0x0000
Input Switch
0x0001
Input Switch
10003
0x0002
Input Switch
10004
0x0003
Input Switch
10005
0x0004
Input Switch
10006
0x0005
Input Switch
Notes
Data
Address
(hex)
40001
Description
Data Type
Notes
0x0000
Run Status
40002
0x0001
Remote Setting
40003
0x0002
Hours
(High 16-bits)
40004
0x0003
Hours
(Low 16-bits)
40005
0x0004
Hours
(High 16-bits)
40006
0x0005
Hours
(Low 16-bits)
40007
0x0006
Hours
(High 16-bits)
40008
0x0007
Hours
(Low 16-bits)
40009
0x0008
Hours
(High 16-bits)
40010
0x0009
Hours
(Low 16-bits)
40011
0x000A
O2 Reading
(High 16-bits)
40012
0x000B
O2 Reading
(Low 16-bits)
The conversion from 32-bit IEEE floating point values to Decimal falls outside of the scope of this manual. For more information on the
conversion try using the following website: http://babbage.cs.qc.edu/IEEE-754/32bit.html.
Value (hex)
Value (hex)
Description
Description
0x0000
Start Delay
0x0001
0x0001
Stand-by
0x0002
0x0002
Economy Stand-by
0x0003
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
Data
Address
(hex)
0x0000
Description
Data Type
Notes
Modbus Control
0 Stop
1 Start