Relion 615 series

Transformer Protection and Control


RET615
Product Guide

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Contents
1. Description.....................................................................3

16. Inputs and outputs......................................................21

2. Standard configurations.................................................3

17. Station communication................................................22

3. Protection functions......................................................14

18. Technical data.............................................................27

4. Application...................................................................14

19. Local HMI....................................................................49

5. Supported ABB solutions.............................................18

20. Mounting methods......................................................50

6. Control.........................................................................19

21. IED case and IED plug-in unit......................................50

7. Measurements.............................................................20

22. Selection and ordering data.........................................50

8. Disturbance recorder....................................................20

23. Accessories and ordering data....................................51

9. Event log......................................................................20

24. Tools...........................................................................52

10. Recorded data............................................................20

25. Cyber security.............................................................53

11. Condition monitoring ..................................................20

26. Terminal diagrams.......................................................54

12. Trip-circuit supervision.................................................20

27. Certificates..................................................................56

13. Self-supervision...........................................................21

28. References..................................................................56

14. Fuse failure supervision...............................................21

29. Functions, codes and symbols....................................57

15. Access control............................................................21

30. Document revision history...........................................59

Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
Copyright 2014 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1. Description
RET615 is a dedicated transformer protection and control IED
(intelligent electronic device) for power transformers, unit and
step-up transformers including power generator-transformer
blocks in utility and industry power distribution systems.
RET615 is a member of ABBs Relion product family and
part of its 615 protection and control product series. The 615
series IEDs are characterized by their compactness and
withdrawable-unit design.
Re-engineered from the ground up, the 615 series has been
designed to unleash the full potential of the IEC 61850
standard for communication and interoperability between
substation automation devices. Once the standard
configuration IED has been given the application-specific
settings, it can directly be put into service.
The 615 series IEDs support a range of communication
protocols including IEC 61850 with GOOSE messaging, IEC
61850-9-2 LE (except in RED615), IEC 60870-5-103,
Modbus and DNP3. Profibus DPV1 communication protocol
is supported by using the protocol converter SPA-ZC 302.

ABB

1MRS756891 H
Issued: 2014-01-24
Revision: H
2. Standard configurations
RET615 is available in eight alternative standard
configurations. The standard signal configuration can be
altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED
Manager PCM600. Further, the application configuration
functionality of PCM600 supports the creation of multi-layer
logic functions utilizing various logical elements including
timers and flip-flops. By combining protection functions with
logic function blocks the IED configuration can be adapted to
user specific application requirements.
The IED is delivered from the factory with default connections
described in the functional diagrams for binary inputs, binary
outputs, function-to-function connections and alarm LEDs.
The positive measuring direction of directional protection
functions is towards the outgoing feeder.

Transformer Protection and Control


RET615
Product version: 5.0

RET615

1MRS756891 H

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I>
51P-1

3I>/Io>BF
51BF/51NBF

3I>>
51P-2

ESC

STANDARD
CONFIGURATION

Clear

AND

R
L

OR

Io
CONDITION MONITORING
AND SUPERVISION

Io (HV)
Io>
51N-1
6RTD
2mA

Io>>
51N-2

dIoLo>
87NL

18
MAP
MAP

OPTS
OPTM

1
1
1
1
1
1
1
1
(RJ45),

ARC
50L/50NL

3I>
51P-1

3I>>
51P-2

0 1 0 0
0 1 1 0
1 0 0 1
0 1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

0
0
1
1
0
0
1
1

Interfaces:
Ethernet: TX
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

CONTROL AND INDICATION 1)


Object

3I>>>
50P/51P

Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3

TCS
TCM

Io

3I (LV)

3dI>T
87T

I2>
46

CBCM
CBCM

COMMUNICATION

Ind 3)

CB

DC

ES

2)

3)

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

1
0
1
1
1
0
1
1

MEASUREMENT

Ctrl 2)

1)

1
1
1
1
1
1
1
1

- HV side: I, Io
- LV side: I
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer

1)

Conventional transformer inputs

TPOSM
84M

REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-C90DE25B-AEC6-4542-8FC8-F4604ACDB769 V1 EN

Figure 1.

Functionality overview for standard configuration A

ABB

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0 1 0 0
1 0
0

0
0
0
0
0
0
0
0

Transformer Protection and Control


RET615
Product version: 5.0

RET615

1MRS756891 H

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I>
51P-1

3I>/Io>BF
51BF/51NBF

3I>>
51P-2

ESC

STANDARD
CONFIGURATION

Clear

AND

R
L

OR

Io
CONDITION MONITORING
AND SUPERVISION
6RTD
2mA

0
1 0

18
MAP
MAP

3dI>T
87T

CBCM
CBCM

OPTS
OPTM

COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3

1
1
1
1
1
1
1
1
(RJ45),

TCS
TCM

0
0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1 0

Io (LV)

Io>
51N-1

Io>>
51N-2

0 1 0 0
0 1 1 0
1 0 0 1
0 1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

0
0
1
1
0
0
1
1

Interfaces:
Ethernet: TX
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

dIoLo>
87NL

Io

1
1
1
1
1
1
1
1

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

3
I2>
46

ARC
50L/50NL

CONTROL AND INDICATION 1)


Object

3I (LV)

3I>>>
50P/51P

3I>
51P-1

3I>>
51P-2

MEASUREMENT

Ctrl 2)

Ind 3)

CB

DC

ES

1)

2)

3)

- HV side: I
- LV side: I, Io
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer

1)

Conventional transformer inputs

TPOSM
84M

REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-C948BC5D-9075-4336-86FC-B8C3F7BA5BAB V1 EN

Figure 2.

ABB

Functionality overview for standard configuration B

1
0
1
1
1
0
1
1

0
0
0
0
0
0
0
0

0
1 0

0
0 1 0 1
1 0
0

1
0
1
1
1
0
1
1

Transformer Protection and Control


RET615
Product version: 5.0

RET615

1MRS756891 H

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

Io

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1 0

Io>
51N-1

Io (HV)

IL2 0 A

3I>>
51P-2

ESC

Clear

AND

R
L

OR

CONDITION MONITORING
AND SUPERVISION

Io>>
51N-2

dIoHi>
87NH

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

3I>
51P-1

3I>/Io>BF
51BF/51NBF

CBCM
CBCM

OPTS
OPTM

COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3

1
1
1
1
1
1
1
1
(RJ45),

TCS
TCM

3dI>T
87T

6RTD
2mA

3I (LV)

0
0
1
1
0
0
1
1

1
1
1
1
1
1
1
1

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

1
0
1
1
1
0
1
1

Io

3
I2>
46

3I>>>
50P/51P

0 1 0 0
0 1 1 0
1 0 0 1
0 1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

Interfaces:
Ethernet: TX
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

18
MAP
MAP

STANDARD
CONFIGURATION

ARC
50L/50NL

3I>
51P-1

3I>>
51P-2

CONTROL AND INDICATION 1)


Object

MEASUREMENT

Ctrl 2)

Ind 3)

CB

DC

ES

1)

2)

3)

- HV side: I, Io
- LV side: I
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer

1)

Conventional transformer inputs

TPOSM
84M

REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-F8F3319F-B60D-47EF-A940-0891BC683D6C V1 EN

Figure 3.

Functionality overview for standard configuration C

ABB

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0 1 0 0
1 0
0

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

RET615

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I>
51P-1

3I>/Io>BF
51BF/51NBF

3I>>
51P-2

ESC

STANDARD
CONFIGURATION

Clear

AND

R
L

OR

Io
CONDITION MONITORING
AND SUPERVISION
6RTD
2mA

18
MAP
MAP

CBCM
CBCM

dIoHi>
87NH

3dI>T
87T

Io>
51N-1

Io>>
51N-2

OPTS
OPTM

COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3

1
1
1
1
1
1
1
1
(RJ45),

TCS
TCM

Io

CONTROL AND INDICATION 1)


Object

3
I2>
46

3I>>>
50P/51P

ARC
50L/50NL

3I>
51P-1

0
0
1
1
0
0
1
1

Interfaces:
Ethernet: TX
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

Io (LV)

3I (LV)

0 1 0 0
0 1 1 0
1 0 0 1
0 1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

3I>>
51P-2

Ind 3)

CB

DC

ES

2)

3)

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

MEASUREMENT

Ctrl 2)

1)

1
1
1
1
1
1
1
1

- HV side: I
- LV side: I, Io
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer

1)

Conventional transformer inputs

TPOSM
84M

REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-422AE187-3E2A-4A20-BBE2-2B8A840DC1FA V1 EN

Figure 4.

ABB

Functionality overview for standard configuration D

1
0
1
1
1
0
1
1

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0
1 0
0

UL1UL2UL3

Uo

Transformer Protection and Control


RET615
Product version: 5.0

RET615

1MRS756891 H

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

IL2 0 A

3I>>
51P-2

Io
Io (HV)

3I (HV)
Io>
51N-1

0 1 0 0 0 1 1 0 0 1 1 0 0

Io>>
51N-2

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

3I>
51P-1

3I>/Io>BF
51BF/51NBF

ESC

Clear

AND

R
L

OR

CONDITION MONITORING
AND SUPERVISION

dIoLo>
87NL

FUSEF
60

CBCM
CBCM

COMMUNICATION
Protocols:
IEC 61850-8-1/9-2LE
1 0
Modbus
1 0
IEC 60870-5-103 1 1
1 0
DNP3

OPTS
OPTM

1
1

2xRTD
1xmA

18
MAP
MAP

3dI>T
87T

TCS
TCM

UL1UL2UL3

3I>>>
50P/51P

3U<
27

3I>
51P-1

3U>
59

3I>>
51P-2

UL1UL2UL3

Object

Ind 3)

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

1
0
1
1
1
0
1
1

CB

DC

ES

1)

2)

- HV side: I, Io, U, Uo, P, Q, E, pf


- LV side: I
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer 2)

1)

1
1
1
1
1
1
1
1

MEASUREMENT

Ctrl 2)

3)

Uo

0
0
1
1
0
0
1
1

ARC
50L/50NL
CONTROL AND INDICATION 1)

3I (LV)

1 0 0
1 1 0
0 0 1
1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

Interfaces:
1
1
Ethernet: TX (RJ45),
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

Io

3
I2>
46

STANDARD
CONFIGURATION

2)

Uo>
59G

TPOSM
84M

Conventional transformer inputs


One of the ve inputs is reserved for future
applications

REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-DC590CA4-DF86-499D-8B77-3DE0CB2997F0 V1 EN

Figure 5.

Functionality overview for standard configuration E

ABB

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0 1 0 0
1 0
0

UL1UL2UL3

Uo

Transformer Protection and Control


RET615
Product version: 5.0

RET615

1MRS756891 H

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I>
51P-1

3I>/Io>BF
51BF/51NBF

3I>>
51P-2

ESC

STANDARD
CONFIGURATION

Clear

AND

R
L

OR

Io

2RTD
1mA
0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

1
0
1
1
1
0
1
1

0
0
0
0
0
0
0
0

0
1 0

3I (HV)
18
MAP
MAP

CONDITION MONITORING
AND SUPERVISION

3dI>T
87T

FUSEF
60

CBCM
CBCM

COMMUNICATION
Protocols:
IEC 61850-8-1/9-2LE
1 0
Modbus
1 0
IEC 60870-5-103 1 1
1 0
DNP3

OPTS
OPTM

0
0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1 0
0

1
1

Io (LV)

Io>
51N-1

Io>>
51N-2

dIoLo>
87NL

TCS
TCM

3
3I (LV)

CONTROL AND INDICATION 1)

ARC
50L/50NL

3I>>>
50P/51P

3I>
51P-1

Object

3I>>
51P-2

Ind 3)

CB

DC

ES

2)

3)

UL1UL2UL3
UL1UL2UL3

3U<
27

3U>
59

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

- HV side: I, U, Uo, P, Q, E, pf
- LV side: I, Io
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer 2)

1)
2)

Uo>
59G

1
1
1
1
1
1
1
1

MEASUREMENT

Ctrl 2)

1)

0
0
1
1
0
0
1
1

Interfaces:
1
1
Ethernet: TX (RJ45),
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

Io

I2>
46

1 0 0
1 1 0
0 0 1
1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

TPOSM
84M

Conventional transformer inputs


One of the ve inputs is reserved for future
applications

Uo
REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-7F2F76A7-E9D6-4845-8A56-42144178898C V1 EN

Figure 6.

ABB

Functionality overview for standard configuration F

1
0
1
1
1
0
1
1

0
0
0
0
0
0
0
0

0
1 0

0
0 1 0 1
1 0
0

RET615

UL1UL2UL3

Uo

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

IL2 0 A

3I>>
51P-2

Io
3I (HV)
Io>
51N-1

Io (HV)

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

3I>
51P-1

3I>/Io>BF
51BF/51NBF

ESC

Clear

AND

R
L

OR

CONDITION MONITORING
AND SUPERVISION

Io>>
51N-2

FUSEF
60

CBCM
CBCM

COMMUNICATION
Protocols:
IEC 61850-8-1/9-2LE
1 0
Modbus
1 0
IEC 60870-5-103 1 1
1 0
DNP3

OPTS
OPTM

1
1

dIoHi>
87NH

3dI>T
87T

TCS
TCM

2xRTD
1xmA

I2>
46

3
3I (LV)

CONTROL AND INDICATION 1)

Io
ARC
50L/50NL

3I>>>
50P/51P

3I>
51P-1

Object

3I>>
51P-2

Ind 3)

CB

DC

ES

2)

3)

UL1UL2UL3
2

3U<
27

3U>
59

Uo>
59G

1
1
1
1
1
1
1
1

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

1
0
1
1
1
0
1
1

- HV side: I, Io, U, Uo, P, Q, E, pf


- LV side: I
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer

1)

UL1UL2UL3

0
0
1
1
0
0
1
1

MEASUREMENT

Ctrl 2)

1)

1 0 0
1 1 0
0 0 1
1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

Interfaces:
1
1
Ethernet: TX (RJ45),
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

18
MAP
MAP

STANDARD
CONFIGURATION

Conventional transformer inputs

TPOSM
84M

Uo
REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-D133822F-DB95-4CF6-B971-9D67054A5731 V1 EN

Figure 7.

10

Functionality overview for standard configuration G

ABB

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0 1 0 0
1 0
0

0
0
0
0
0
0
0
0

1MRS756891 H

RET615

UL1UL2UL3

Uo

Transformer Protection and Control


RET615
Product version: 5.0

TRANSFORMER PROTECTION AND CONTROL IED

PROTECTION

LOCAL HMI

ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization

ESC

- Disturbance and fault recorders


- Event log and recorded data
- High-Speed Output module (optional)
- IED self-supervision
- Local/Remote push button on LHMI
- User management
- Web HMI

Clear

I2>
46

3I (HV)

3Ith>T
49T

3I>>>
50P/51P

R
L

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I>
51P-1

3I>/Io>BF
51BF/51NBF

3I>>
51P-2

ESC

STANDARD
CONFIGURATION

Clear

AND

R
L

OR

Io

2RTD
1mA
0
1 0

CONDITION MONITORING
AND SUPERVISION

3I (HV)
18
MAP
MAP

0
0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1 0
0

FUSEF
60

dIoHi>
87NH

3dI>T
87T

Io>
51N-1

Io>>
51N-2

Io (LV)

Io

1
1

ARC
50L/50NL

3I>>>
50P/51P

3I>
51P-1

3I>>
51P-2

TCS
TCM

Ind 3)

CB

DC

ES

2)

UL1UL2UL3

3)

3U<
27

3U>
59

1
1
1
1
1
1
1
1

1
0
0
0
1
0
0
0

0
1
1
1
0
1
1
1

0
1
1
1
0
1
1
1

1
1
0
0
1
1
0
0

- HV side: I, U, Uo, P, Q, E, pf
- LV side: I, Io
- Limit value supervision
- Load prole record
- RTD/mA measurement, optional
- Symmetrical components

Check availability of binary inputs/outputs


from technical documentation
Control and indication function for
primary object
Status indication function for
primary object

Analog interface types

1)

Current transformer

Voltage transformer

1)

UL1UL2UL3

0
0
1
1
0
0
1
1

MEASUREMENT

Ctrl 2)

1)

1 0 0
1 1 0
0 0 1
1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX

Interfaces:
1
1
Ethernet: TX (RJ45),
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP

Object

3I (LV)

Protocols:
IEC 61850-8-1/9-2LE
1 0
Modbus
1 0
IEC 60870-5-103 1 1
1 0
DNP3

OPTS
OPTM

CONTROL AND INDICATION 1)

I2>
46

CBCM
CBCM

COMMUNICATION

Conventional transformer inputs

Uo>
59G

Uo
REMARKS
5

Master trip
Lockout relay
94/86

Optional
function

3 No. of
instances

Calculated
value
Io/Uo

OR Alternative
function to be
dened when
ordering

GUID-8C9FE17B-5399-487C-BE59-7377D23FC744 V1 EN

Figure 8.

ABB

Functionality overview for standard configuration H

11

1
0
1
1
1
0
1
1

0
0
0
0
0
0
0
0

0
1 0
0
0 1 0
1 0
0

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 1. Standard configurations


Description

Std. conf.

Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the
high-voltage (HV) side, optional RTD/mA inputs

Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the
low-voltage (LV) side, optional RTD/mA inputs

Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault
protection for the high-voltage (HV) side, optional RTD/mA inputs

Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault
protection for the low-voltage (LV) side, optional RTD/mA inputs

Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the
high-voltage (HV) side, phase-voltage based protection and measurement functions

Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the
low-voltage (LV) side, phase-voltage based protection and measurement functions

Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault
protection for the high-voltage (HV) side, phase-voltage based protection and measurement functions

Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault
protection for the low-voltage (LV) side, phase-voltage based protection and measurement functions

12

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 2. Supported functions


Function

IEC 61850

Three-phase non-directional overcurrent


protection, low stage

PHLPTOC1

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Three-phase non-directional overcurrent


protection, low stage

PHLPTOC2

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

Three-phase non-directional overcurrent


protection, high stage

PHHPTOC1

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Three-phase non-directional overcurrent


protection, high stage

PHHPTOC2

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

Three-phase non-directional overcurrent


protection, instantaneous stage

PHIPTOC1

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Three-phase non-directional overcurrent


protection, instantaneous stage

PHIPTOC2

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

Protection1)

2)

3)

2)

3)

Non-directional earth-fault protection, low stage

EFLPTOC1

Non-directional earth-fault protection, low stage

EFLPTOC2

Non-directional earth-fault protection, high


stage

EFHPTOC1

Non-directional earth-fault protection, high


stage

EFHPTOC2

Negative-sequence overcurrent protection

NSPTOC1

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Negative-sequence overcurrent protection

NSPTOC2

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

Residual overvoltage protection

ROVPTOV

2 HV 6)

2 HV 6)

2 HV 6)

2 HV 6)

Three-phase undervoltage protection

PHPTUV

2 HV

2 HV

2 HV

2 HV

Three-phase overvoltage protection

PHPTOV

2 HV

2 HV

2 HV

2 HV

Three-phase thermal overload protection for


power transformers, two time constants

T2PTTR

Stabilized and instantaneous differential


protection for 2W-transformers

TR2PTDF

Numerical stabilized low impedance restricted


earth-fault protection

LREFPNDF

High impedance-based restricted earth-fault


protection

HREFPDIF

Circuit breaker failure protection 3)

CCBRBRF

1 HV

Master trip 9)

TRPPTRC

2 (5)

Arc protection 10)

ARCSARC

Multi-purpose protection 11)12)

MAPGAPC

1 HV

1 HV
1 LV 4)

1 HV 2)

1 HV
1 LV 5)

1 HV 3)
1 LV 4)

1 HV
1 LV 4)

1 HV 2)
1 LV 5)

1 LV 5)
1 HV 3)

1 LV 4)

1 LV 5)
1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 LV 7)

1 HV

1 LV 7)
1 HV

1 LV 8)
1 HV

1 HV

1 LV 8)

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

2 (5)

2 (5)

2 (5)

2 (5)

2 (5)

2 (5)

2 (5)

(3) LV

(3) LV

(3) LV

(3) LV

(3) LV

(3) LV

(3) LV

(3) LV

18

18

18

18

18

18

18

18

CBXCBR

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

DCXSWI

Control
Circuit-breaker control
Disconnector control

12)
12)

ESXSWI

Disconnector position indication 12)

DCSXSWI

Earthing switch indication 12)

ESSXSWI

Tap changer position indication

TPOSSLTC

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Earthing switch control

Condition monitoring
Circuit-breaker condition monitoring

SSCBR

Trip circuit supervision

TCSSCBR

Fuse failure supervision

SEQRFUF

Runtime counter for machines and devices

MDSOPT

Disturbance recorder

RDRE

Load profile record

LDPMSTA

Three-phase current measurement

CMMXU1

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Three-phase current measurement

CMMXU2

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

1 LV

Sequence current measurement

CSMSQI

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

Residual current measurement

RESCMMXU1

1 HV

Residual current measurement

RESCMMXU2

Three-phase voltage measurement

VMMXU

1 HV

1 HV

1 HV

1 HV

Residual voltage measurement

RESVMMXU

1 HV

1 HV

1 HV

1 HV

Measurement

ABB

1 HV
1 LV

1 HV
1 LV

1 HV
1 LV

1 LV

13

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 2. Supported functions, continued


Function

IEC 61850

Sequence voltage measurement

VSMSQI

Three-phase power and energy measurement

PEMMXU

RTD/mA measurement

XRGGIO130

IEC 61850-9-2 LE (Voltage sharing) 13)

SMVSENDER

(1)

(1)

(1)

(1)

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

1 HV

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

HV = The function block is to be used on the high-voltage side in the application.


LV = The function block is to be used on the low-voltage side in the application.
1, 2, ... = number of included instances
() = optional
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)

The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
Io selectable by parameter, "Io measured" as default
"Io calculated" is always used.
IoB selectable by parameter, "IoB measured" as default
"IoB calculated" is always used.
Uo selectable by parameter, "Uo measured" as default
IoB measured and 3IB are always used.
IoB measured is always used.
Master trip included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If the ARC option is selected additionally, ARCSARC is
connected to the corresponding master trip input in the configuration.
IoB calculated and 3IB are always used.
Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
Must be added with Application Configuration to be available in Signal Matrix and in IED.
Only available with COM0031-COM0034

3. Protection functions
The IED features, three-phase, multi-slope stabilized (biased)
stage transformer differential protection and an instantaneous
stage to provide fast and selective protection for phase-tophase short-circuit, winding interturn fault and bushing flashover protection. Besides second harmonic restraint an
advanced waveform-based blocking algorithm ensures
stability at transformer energization and a fifth harmonic
restraint function ensures good protection stability at
moderate overexcitation of power transformers. Sensitive
restricted earth-fault protection completes the overall
differential protection providing detection of even single
phase-to-earth faults close to the neutral earthing point of the
transformer. Either the conventional high-impedance scheme
or a numerical low-impedance scheme can be selected for
protection of the transformer windings. When low-impedance
restricted earth-fault protection is used neither stabilizing
resistors nor varistors are needed and as a further benefit the
transforming ratio of the neutral earthing CTs can differ from
those of the phase current transformers. Due to its unit
protection character and absolute selectivity restricted earthfault does not need to be time-graded with other protection
schemes, and therefore high speed fault clearance can be
achieved.

features three-phase overvoltage protection, three-phase


undervoltage protection and residual overvoltage protection.
Further, the IED also offers circuit breaker failure protection.

The IED also incorporates a thermal overload protection


function, which supervises the thermal stress of the
transformer windings to prevent premature aging of the
insulation of the windings. Multiple stages of short-circuit,
phase-overcurrent, negative-phase-sequence and earth-fault
back-up protection are separately available for both sides of
the power transformer. Earth-fault protection based on the
measured or calculated residual voltage is also available.
Depending on the chosen standard configuration the IED also

The standard configurations A, C, E and G are intended for


power transformers with earthed HV-side neutrals. The A and
E configuration features low impedance REF protection while
the C and G configuration offers high impedance REF
protection. The B, D, F and H configurations fit transformers
with solidly-earthed LV-side neutral or the LV side with a
neutral earthing resistor. The B, D, F and H configurations
also fit applications including a separate earthing transformer
located within the area of protection. The A, B , E, and F

14

Enhanced with optional hardware and software, the IED also


features three light detection channels for arc fault protection
of the circuit breaker, busbar and cable compartment of
metal-enclosed indoor switchgear.
The arc-fault protection sensor interface is available on the
optional communication module. Fast tripping increases staff
safety and security and limits material damage in an arc fault
situation. A binary input and output module can be selected
as an option - having three high speed binary outputs (HSO) it
further decreases the total operate time with typically 4...6 ms
compared to the normal power outputs.
4. Application
RET615 provides main protection for two-winding power
transformers and power generator-transformer blocks. As of
now, there are eight standard configurations offering
comprehensive protection functions for detection and
elimination of operational disturbance conditions and power
transformer faults.

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

configurations also suit applications, where the turns ratio of


the CT of the neutral earthing circuit differs from the turns
ratio of the line CTs. The C, D, G and H configurations require
that the turns ratios of the CTs are equal.
Standard configurations E, F, G and H include phase-voltage
protection and measurement functions which provide twostage power transformer overvoltage and undervoltage
protection and/or supervision.
Two optional RTD/mA modules are available.
The optional RTD/mA module offered for the standard
configurations A-D allows up to eight analog signals to be
measured via the six RTD inputs and the two mA inputs using
transducers. The RTD and mA inputs can be used for
measuring the oil temperature at the bottom and top of the
transformer. Furthermore, the RTD/mA inputs can be used for
measuring the ambient air temperature. The RTD inputs also
offer thermal protection of dry-type power transformers fitted
with Pt-100 temperature sensors. Temperature measurement

over the RTD/mA inputs extends the function of the threephase thermal overload protection of the IED. Further, one of
the RTD inputs can also be used as a direct resistance
measuring input for position information of the on-load tap
changer. Alternatively, the tap changer position indication can
be obtained via a mA-transducer.
The optional RTD/mA module offered for the standard
configurations E-H allows up to three analog signals to be
measured via the two RTD inputs and the one mA input using
transducers. The RTD inputs can be used for measuring the
oil temperature and the ambient air temperature. Temperature
measurement over the RTD inputs extends the function of the
three-phase thermal overload protection of the IED. For onload tap changer the tap changer position indication can be
obtained via a mA-transducer. The analog temperature or tap
changer position values can, if required, be sent using analog
horizontal GOOSE messaging to other IEDs. Analog values
can also, vice versa, be received from other IEDs over the
station bus, thus improving the extent of relevant information.

3I (HV)

RET615

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

I
O

Io (HV)

RTD

ESC

Clear

R
L

Std. conf.
ANSI

IEC

49T

3Ith>T

50L/50NL

ARC

50P/51P

3I>>>

51P/51N

3I/Io

87NL

dIoLo>

87T

3dI>T

3I (LV)

GUID-6657E450-7FB8-4154-954D-E896064D04A3 V1 EN

Figure 9.

Protection of two winding power transformer with RET615 standard configuration A

Protection of two winding power transformer with RET615


standard configuration A. Main protection used in this
application example is transformer differential protection.

ABB

Additionally restricted E/F with numerical low impedance


principle is applied on the transformer HV side.

15

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

3I (HV)

RET615

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

ESC

Clear

R
L

RTD

Io (LV)

Std. conf.
ANSI

IEC

49T

3Ith>T

50L/50NL

ARC

50P/51P

3I>>>

51P/51N

3I/Io

87NH

dIoHi>

87T

3dI>T

3I (LV)

GUID-46A1FCF8-F2EC-4737-9EA8-636E4AEF84FC V1 EN

Figure 10.

Protection of two winding power transformer with RET615 standard configuration D

Protection of two winding power transformer with RET615


standard configuration D. Main protection used in this
application example is transformer differential protection.

3U

Additionally restricted E/F with high impedance principle is


applied on the transformer LV side.

Uo
A

3I (HV)

Io (HV)

RTD

RET615

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

ESC

Clear

R
L

Std. conf.
ANSI

IEC

27/59

3U</3U>

49T

3Ith>T

50L/50NL

ARC

50P/51P

3I>>>

51P/51N

3I/Io

59G

Uo>

87NL

dIoLo>

87T

3dI>T

3I (LV)

GUID-3C760FFC-6D6B-4860-A198-4BA4273B32D9 V1 EN

Figure 11.

Protection of two winding power transformer with RET615 standard configuration E

Protection of two winding power transformer with RET615


standard configuration E. Main protection used in this
application example is transformer differential protection.

16

Additionally restricted E/F with numerical low impedance


principle is applied on the transformer HV side and also
voltage based protection.

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

3U

Uo
RET615
A

3I (HV)

IL2 0 A

I
O

ESC

Std. conf.

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr

Clear

R
L

Io (HV)

RTD

ANSI

IEC

27/59

3U</3U>

49T

3Ith>T

50L/50NL

ARC

50P/51P

3I>>>

51P/51N

3I/Io

87NL

dIoLo>

87T

3dI>T

3U
A

REU615

U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A

3I (LV)

I
O

ESC

Clear

R
L

Std. conf.
ANSI

IEC

27/59

3U</3U>

50P/51P

3I>>>

51P/51N

3I/Io

84M

TPOSM

90V

COLTC

GUID-AB31C909-F38E-4885-AFEE-E2EEE3675263 V4 EN

Figure 12.

Protection of a two winding power transformer with RET615 standard configuration E

Protection of a two winding power transformer with RET615


standard configuration. Main protection used in this
application example is transformer differential protection.
Restricted E/F protection with numerical low impedance
principle is applied on the transformer HV-side. The RTD

ABB

inputs of are utilized for monitoring the oil temperature and oil
level of the transformer. Additionally a REU615 with the
standard configuration B is used as automatic voltage
regulator for the on-load tap changer of the transformer.

17

Transformer Protection and Control


RET615
Product version: 5.0

5. Supported ABB solutions


ABBs 615 series protection and control IEDs together with
the grid automation controller COM600 constitute a genuine
IEC 61850 solution for reliable power distribution in utility and
industrial power systems. To facilitate and streamline the
system engineering, ABB's IEDs are supplied with
connectivity packages. The connectivity packages include a
compilation of software and IED-specific information,
including single-line diagram templates and a full IED data
model. The data model also includes event and parameter
lists. With the connectivity packages, the IEDs can be readily
configured using PCM600 and integrated with the grid
automation controller COM600 or the network control and
management system MicroSCADA Pro.
The 615 series IEDs offer native support for the IEC 61850
standard also including binary and analog horizontal GOOSE
messaging. In addition, process bus with sampled values of
analog phase voltages is supported. Process bus with
sampled values of analog phase voltages is also supported.
Compared to traditional hard-wired, inter-device signaling,
peer-to-peer communication over a switched Ethernet LAN
offers an advanced and versatile platform for power system
protection. Among the distinctive features of the protection
system approach, enabled by the full implementation of the
IEC 61850 substation automation standard, are fast
communication capability, continuous supervision of the
integrity of the protection and communication system, and an
inherent flexibility regarding reconfiguration and upgrades.
At substation level, COM600 uses the data content of the baylevel IEDs to enhance substation level functionality. COM600
features a Web browser-based HMI, which provides a

1MRS756891 H

customizable graphical display for visualizing single-line mimic


diagrams for switchgear bay solutions. The SLD feature is
especially useful when 615 series IEDs without the optional
single-line diagram feature are used. The Web HMI of
COM600 also provides an overview of the whole substation,
including IED-specific single-line diagrams, which makes
information easily accessible. Substation devices and
processes can also be remotely accessed through the Web
HMI, which improves personnel safety.
In addition, COM600 can be used as a local data warehouse
for the substation's technical documentation and for the
network data collected by the IEDs. The collected network
data facilitates extensive reporting and analyzing of network
fault situations, by using the data historian and event handling
features of COM600. The history data can be used for
accurate monitoring of process and equipment performance,
using calculations based on both real-time and history values.
A better understanding of the process dynamics is achieved
by combining time-based process measurements with
production and maintenance events.
COM600 can also function as a gateway and provides
seamless connectivity between the substation IEDs and
network-level control and management systems, such as
MicroSCADA Pro and System 800xA.
GOOSE Analyzer interface in COM600 enables the following
and analyzing the horizontal IEC 61850 application during
commissioning and operation at station level. It logs all
GOOSE events during substation operation to enable
improved system supervision.

Table 3. Supported ABB solutions


Product

Version

Grid automation controller COM600

4.0 SP1 or later

MicroSCADA Pro SYS 600

9.3 FP2 or later

System 800xA

5.1 or later

18

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

ABB
MicroSCADA Pro/
System 800xA

Utility: IEC 60870-5-104


Industry: OPC

COM600
Web HMI

Ethernet switch

Analog and binary horizontal


GOOSE communication

PCM600

IEC 61850

COM600
Web HMI

Ethernet switch

Analog and binary horizontal


GOOSE communication

PCM600

IEC 61850

GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V1 EN

Figure 13.

ABB power system example using Relion IEDs, Grid Automation controller COM600 and MicroSCADA Pro/System 800xA

6. Control
RET615 integrates functionality for the control of a circuit
breaker via the front panel HMI or by means of remote
controls. In addition to the circuit-breaker control the IED
features two control blocks which are intended for motoroperated control of disconnectors or circuit breaker truck and
for their position indications. Further, the IED offers one
control block which is intended for motor-operated control of
one earthing switch control and its position indication.
Two physical binary inputs and two physical binary outputs
are needed in the IED for each controllable primary device
taken into use. Depending on the chosen standard
configuration of the IED the number of unused binary inputs
and binary outputs varies. Further, some standard
configurations also offer optional hardware modules that
increase the number of available binary inputs and outputs.
In case the amount of available binary inputs and/or outputs
of the chosen standard configuration is not sufficient, the
following alternatives are recommended:

ABB

To modify the chosen standard configuration of the IED in


order to release some binary inputs or binary outputs which
have originally been configured for other purposes, when
applicable.
To integrate an external input or output module for
example, RIO600 to the IED. The binary inputs and outputs
of the external I/O module can be used for the less time
critical binary signals of the application. The integration
enables releasing of some initially reserved binary inputs
and outputs of the IED in the standard configuration.
The suitability of the binary outputs of the IED which have
been selected for controlling of primary devices should be
carefully verified, for example the make and carry as well as
the breaking capacity. In case the requirements for the
control-circuit of the primary device are not met, the use of
external auxiliary relays should to be considered.
The optional large graphical LCD of the IED's HMI includes a
single-line diagram (SLD) with position indication for the
relevant primary devices. Interlocking schemes required by
19

Transformer Protection and Control


RET615
Product version: 5.0

the application are configured using the signal matrix or the


application configuration functionality of PCM600.
7. Measurements
The IED continuously measures the high voltage (HV) side and
the low-voltage (LV) side phase currents and the neutral
current of the protected transformer. In addition, the IED
calculates the symmetrical components of the currents and
voltages, maximum current demand value over a userselectable pre-set time frame, the active and reactive power,
the power factor, and the active and reactive energy values.
Calculated values are also obtained from the protection and
condition monitoring functions of the IED. Depending on the
standard configuration, the IED also measures the phase
voltages, the residual voltage and the voltage sequence
components.
For standard configuration A, B, C and D RTD/mA inputs are
offered as an option. By means of the optional RTD/mA
module the IED can measure up to eight analog signals such
as temperature, pressure and tap changer position values via
the six RTD inputs or the two mA inputs using transducers.
For standard configuration E, F, G and H RTD/mA inputs are
offered as an option. By means of these inputs the IED can
measure up to three analog signals such as temperature,
pressure and tap changer position values via the two RTD
inputs or the one mA inputs using transducers.
The values measured can be accessed locally via the user
interface on the IED front panel or remotely via the
communication interface of the IED. The values can also be
accessed locally or remotely using the Web browser-based
user interface.
The IED has a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time
interval (demand interval). The records are in COMTRADE
format.
8. Disturbance recorder
The IED is provided with a disturbance recorder with up to 12
analog and 64 binary signal channels. The analog channels
can be set to record either the waveform or the trend of the
currents and voltages measured.

1MRS756891 H

trigger the recording. The recorded information is stored in a


non-volatile memory and can be uploaded for subsequent
fault analysis.
9. Event log
To collect sequence-of-events information, the IED has a nonvolatile memory with a capacity of storing 1024 events with
associated time stamps. The non-volatile memory retains its
data also in case the IED temporarily loses its auxiliary supply.
The event log facilitates detailed pre- and post-fault analyses
of feeder faults and disturbances. The increased capacity to
process and store data and events in the IED offers
prerequisites to support the growing information demand of
future network configurations.
The sequence-of-events information can be accessed either
locally via the user interface on the IED front panel, or
remotely via the communication interface of the IED. The
information can also be accessed using the Web browserbased user interface, either locally or remotely.
10. Recorded data
The IED has the capacity to store the records of the 128
latest fault events. The records enable the user to analyze the
power system events. Each record includes current, voltage
and angle values, time stamp and so on. The fault recording
can be triggered by the start signal or the trip signal of a
protection block, or by both. The available measurement
modes include DFT, RMS and peak-to-peak. Fault records
store IED measurement values at the moment when any
protection function starts. In addition, the maximum demand
current with time stamp is separately recorded. By default,
the records are stored in the nonvolatile memory.
11. Condition monitoring
The condition monitoring functions of the IED constantly
monitors the performance and the condition of the circuit
breaker. The monitoring comprises the spring charging time,
SF6 gas pressure, the travel time and the inactivity time of the
circuit breaker.
The monitoring functions provide operational circuit breaker
history data, which can be used for scheduling preventive
circuit breaker maintenance.

The analog channels can be set to trigger the recording


function when the measured value falls below, or exceeds,
the set values. The binary signal channels can be set to start
a recording either on the rising or the falling edge of the
binary signal or on both.

In addition, the IED includes a runtime counter for monitoring


of how many hours a protected device has been in operation
thus enabling scheduling of time-based preventive
maintenance of the device.

By default, the binary channels are set to record external or


internal IED signals, for example, the start or trip signals of
the IED stages, or external blocking or control signals. Binary
IED signals, such as protection start and trip signals, or an
external IED control signal via a binary input, can be set to

12. Trip-circuit supervision


The trip-circuit supervision continuously monitors the
availability and operability of the trip circuit. It provides opencircuit monitoring both when the circuit breaker is in its

20

ABB

Transformer Protection and Control


RET615
Product version: 5.0

closed and in its open position. It also detects loss of circuitbreaker control voltage.
13. Self-supervision
The IEDs built-in self-supervision system continuously
monitors the state of the IED hardware and the operation of
the IED software. Any fault or malfunction detected is used
for alerting the operator.
A permanent IED fault blocks the protection functions to
prevent incorrect operation.
14. Fuse failure supervision
Depending on the chosen standard configuration, the IED
includes fuse failure supervision functionality. The fuse failure
supervision detects failures between the voltage
measurement circuit and the IED. The failures are detected
either by the negative sequence-based algorithm or by the
delta voltage and delta current algorithm. Upon the detection
of a failure, the fuse failure supervision function activates an
alarm and blocks voltage-dependent protection functions
from unintended operation.
15. Access control
To protect the IED from unauthorized access and to maintain
information integrity, the IED is provided with a four-level, rolebased authentication system with administratorprogrammable individual passwords for the viewer, operator,
engineer and administrator level. The access control applies
to the front-panel user interface, the Web browser-based
user interface and PCM600.

1MRS756891 H

current input, three phase-voltage inputs and one residual


voltage input. The rated level of the current inputs is 1/5 A
and selectable in the IED software. The three phase-voltage
inputs and the residual-voltage input covers the rated
voltages 60-210 V. Both phase-to-phase voltages and phaseto-earth voltages can be connected. In addition, the binary
input thresholds 16176 V DC are selected by adjusting the
IEDs parameter settings.
All binary inputs and outputs contacts are freely configurable
with the signal matrix or application configuration functionality
of PCM600.
As an option for standard configurations A, B, C and D, the
IED offers six RTD inputs and two mA inputs. By means of the
optional RTD/mA module the IED can measure up to eight
analog signals such as temperature, pressure and tap
changer position values via the six RTD inputs or the two mA
inputs using transducers. The values can, apart from
measuring and monitoring purposes, be used for tripping and
alarm purposes using the offered optional multipurpose
protection functions.
As an option for standard configurations E, F, G and H, the
IED offers two RTD inputs and one mA input.
As an option a binary input and output module can be
selected, having three high speed binary outputs (HSO),
decreasing further the total operate time with typically 4-6 ms
compared to the normal power outputs.
Please refer to the Input/output overview table and the
terminal diagrams for more detailed information about the
inputs and outputs.

16. Inputs and outputs


The IED is equipped with six phase-current inputs and one
neutral-current input or six phase-current inputs, one neutral-

ABB

21

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 4. Input/output overview


Std. conf.

A
B
C
D

Order code digit

Analog channels

Binary channels

5-6

7-8

CT

VT

BI

BO

RTD

mA

BB

14

4 PO + 9 SO

14

4 PO + 5 SO
+ 3 HSO

4 PO + 6 SO

4 PO + 2 SO
+ 3 HSO

12

4 PO + 6 SO

12

4 PO + 2 SO
+ 3 HSO

4 PO + 6 SO

4 PO + 2 SO
+ 3 HSO

BA

FF
BA

BG

FD
AD

E
F
G
H

BC

FE
BA

BE

FD

17. Station communication


The IED supports a range of communication protocols
including IEC 61850, IEC 61850-9-2 LE, Modbus and
DNP3. Profibus DPV1 communication protocol is supported
with using the protocol converter SPA-ZC 302. Operational
information and controls are available through these
protocols. However, some communication functionality, for
example, horizontal communication between the IEDs, is only
enabled by the IEC 61850 communication protocol.
The IEC 61850 communication implementation supports
monitoring and control functions. Additionally, parameter
settings, disturbance recordings and fault records can be
accessed using the IEC 61850 protocol. Disturbance
recordings are available to any Ethernet-based application in
the standard COMTRADE file format. The IED supports
simultaneous event reporting to five different clients on the
station bus. The IED can exchange signals with other IEDs
using the IEC 61860 protocol.
The IED can send binary and analog signals to other IEDs (so
called horizontal communication) using the IEC 61850-8-1
GOOSE (Generic Object Oriented Substation Event) profile.
Binary GOOSE messaging can, for example, be employed for
protection and interlocking-based protection schemes. The
IED meets the GOOSE performance requirements for tripping
applications in distribution substations, as defined by the IEC
61850 standard. The IED also supports the sending and
receiving of analog values using GOOSE messaging. Analog
GOOSE messaging enables easy transfer of analog
measurement values over the station bus, thus facilitating for
example sharing of RTD input values, such as surrounding
temperature values, to other IED applications.
22

The IED also supports IEC 61850 process bus with sampled
values of analog phase voltages. With this functionality the
galvanic interpanel wiring can be replaced with Ethernet
communication. The measured values are transferred as
sampled values using IEC 61850-9-2 LE protocol. The
intended application for sampled values shares the phase
voltages to other 615 series IEDs, having phase voltage
based functions and 9-2 support. 615 IEDs with process bus
based applications use IEEE 1588 for high accuracy time
synchronization.
For redundant Ethernet communication, the IED offers either
two optical or two galvanic Ethernet network interfaces. A
third port with galvanic Ethernet network interface is also
available. The third Ethernet interface provides connectivity
for any other Ethernet device to an IEC 61850 station bus
inside a switchgear bay, for example connection of a Remote
I/O. The high accuracy time synchronization method IEEE
1588 support is included in all variants that have a redundant
Ethernet communication module.
Ethernet network redundancy can be achieved using the highavailability seamless redundancy (HSR) protocol or the
parallel redundancy protocol (PRP) or a with self-healing ring
using RSTP in managed switches. Ethernet redundancy can
be applied to Ethernet-based IEC 61850, Modbus and DNP3
protocols.
The IEC 61850 standard specifies network redundancy which
improves the system availability for the substation
communication. The network redundancy is based on two
complementary protocols defined in the IEC 62439-3
standard: PRP and HSR protocols. Both the protocols are
able to overcome a failure of a link or switch with a zero
ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

switch-over time. In both the protocols, each network node


has two identical Ethernet ports dedicated for one network
connection. The protocols rely on the duplication of all
transmitted information and provide a zero switch-over time if
the links or switches fail, thus fulfilling all the stringent realtime requirements of substation automation.

In PRP, each network node is attached to two independent


networks operated in parallel. The networks are completely
separated to ensure failure independence and can have
different topologies. The networks operate in parallel, thus
providing zero-time recovery and continuous checking of
redundancy to avoid failures.

COM600

Ethernet switch

REF615

REF620

SCADA

IEC 61850 PRP

RET620

Ethernet switch

REM620

REF615

GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V1 EN

Figure 14.

Parallel redundancy protocol (PRP) solution

HSR applies the PRP principle of parallel operation to a single


ring. For each message sent, the node sends two frames,
one through each port. Both the frames circulate in opposite
directions over the ring. Every node forwards the frames it
receives from one port to another to reach the next node.
When the originating sender node receives the frame it sent,

ABB

the sender node discards the frame to avoid loops. The HSR
ring with 615 series IEDs supports the connection of up to
thirty IEDs. If more than 30 IEDs are to be connected, it is
recommended to split the network into several rings to
guarantee the performance for real-time applications.

23

Transformer Protection and Control


RET615
Product version: 5.0

COM600

1MRS756891 H

Devices not supporting HSR

SCADA

Ethernet switch

Redundancy
Box

Redundancy
Box

Redundancy
Box

IEC 61850 HSR

REF615

REF620

RET620

REM620

REF615

GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN

Figure 15.

High availability seamless redundancy (HSR) solution

The choice between the HSR and PRP redundancy protocols


depends on the required functionality, cost and complexity.
The self-healing Ethernet ring solution enables a cost-efficient
communication ring controlled by a managed switch with
standard Rapid Spanning Tree Protocol (RSTP) support. The
managed switch controls the consistency of the loop, routes
the data and corrects the data flow in case of a

24

communication switch-over. The IEDs in the ring topology act


as unmanaged switches forwarding unrelated data traffic. The
Ethernet ring solution supports the connection of up to thirty
615 series IEDs. If more than 30 IEDs are to be connected, it
is recommended to split the network into several rings. The
self-healing Ethernet ring solution avoids single point of failure
concerns and improves the reliability of the communication.

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Client A

Client B

Network A
Network B

Managed Ethernet switch


with RSTP support

Managed Ethernet switch


with RSTP support

GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN

Figure 16.

Self-healing Ethernet ring solution

All communication connectors, except for the front port


connector, are placed on integrated optional communication
modules. The IED can be connected to Ethernet-based
communication systems via the RJ-45 connector (100BaseTX) or the fibre-optic LC connector (100Base-FX). If
connection to a serial bus is required, the 10-pin RS-485
screw-terminal or the fibre-optic ST connector can be used.
Modbus implementation supports RTU, ASCII and TCP
modes. Besides standard Modbus functionality, the IED
supports retrieval of time-stamped events, changing the
active setting group and uploading of the latest fault records.
If a Modbus TCP connection is used, five clients can be
connected to the IED simultaneously. Further, Modbus serial
and Modbus TCP can be used in parallel, and if required both
IEC 61850 and Modbus protocols can be run simultaneously.
The IEC 60870-5-103 implementation supports two parallel
serial bus connections to two different masters. Besides
basic standard functionality, the IED supports changing of the
active setting group and uploading of disturbance recordings
in IEC 60870-5-103 format. Further, IEC 60870-5-103 can
be used at the same time with the IEC 61850 protocol.
DNP3 supports both serial and TCP modes for connection up
to five masters. Changing of the active setting and reading
fault records are supported. DNP serial and DNP TCP can be
ABB

used in parallel. If required, both IEC 61850 and DNP


protocols can be run simultaneously.
615 series supports Profibus DPV1 with support of SPA-ZC
302 Profibus adapter. If Profibus is required the IED must be
ordered with Modbus serial options. Modbus implementation
includes SPA-protocol emulation functionality. This
functionality enables connection to SPA-ZC 302.
When the IED uses the RS-485 bus for the serial
communication, both two- and four wire connections are
supported. Termination and pull-up/down resistors can be
configured with jumpers on the communication card so
external resistors are not needed.
The IED supports the following time synchronization methods
with a time-stamping resolution of 1 ms.
Ethernet-based
SNTP (Simple Network Time Protocol)
With special time synchronization wiring
IRIG-B (Inter-Range Instrumentation Group - Time Code
Format B)

25

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

The IED supports the following high accuracy time


synchronization method with a time-stamping resolution of 4
s required especially in process bus applications.
PTP (IEEE 1588) v2 with Power Profile

Required accuracy of grandmaster clock is +/-1 s. IED can


work as master clock per BMC algorithm if external
grandmaster clock is not available for short term.
The IEEE 1588 support is included in all variants having a
redundant Ethernet communication module.

The IEEE 1588 support is included in all variants having a


redundant Ethernet communication module.

In addition, the IED supports time synchronization via the


following serial communication protocols.
Modbus
DNP3
IEC 60870-5-103

IEEE 1588 v2 features


Ordinary Clock with Best Master Clock algorithm
One-step Transparent Clock for Ethernet ring topology
1588 v2 Power Profile
Receive (slave): 1-step/2-step
Transmit (master): 1-step
Layer 2 mapping
Peer to peer delay calculation
Multicast operation
Table 5. Supported station communication interfaces and protocols
Interfaces/Protocols

Ethernet

Serial

100BASE-TX RJ-45

100BASE-FX LC

RS-232/RS-485

Fibre-optic ST

IEC 61850-8-1

IEC 61850-9-2 LE

MODBUS RTU/ASCII

MODBUS TCP/IP

DNP3 (serial)

DNP3 TCP/IP

IEC 60870-5-103

= Supported

26

ABB

1MRS756891 H

Transformer Protection and Control


RET615
Product version: 5.0

18. Technical data


Table 6. Dimensions
Description

Value

Width

frame

177 mm

case

164 mm

frame

177 mm (4U)

case

160 mm

Height

Depth

201 mm (153 + 48 mm)

Weight

complete IED

4.1 kg

plug-in unit only

2.1 kg

Table 7. Power supply


Description

Type 1

Type 2

Nominal auxiliary voltage Un

100, 110, 120, 220, 240 V AC, 50 and 60 Hz

24, 30, 48, 60 V DC

48, 60, 110, 125, 220, 250 V DC


Maximum interruption time in the auxiliary
DC voltage without resetting the IED

50 ms at Un

Auxiliary voltage variation

38...110% of Un (38...264 V AC)

50...120% of Un (12...72 V DC)

80...120% of Un (38.4...300 V DC)


Start-up threshold

19.2 V DC (24 V DC * 80%)

Burden of auxiliary voltage supply under


quiescent (Pq)/operating condition

DC < 12.0 W (nominal)/< 18.0 W (max)


AC< 16.0 W (nominal)/< 21.0W (max)

Ripple in the DC auxiliary voltage

Max 15% of the DC value (at frequency of 100 Hz)

Fuse type

T4A/250 V

DC < 12.0 W (nominal)/< 18.0 W (max)

Table 8. Energizing inputs


Description

Value

Rated frequency

50/60 Hz 5 Hz

Current inputs

Rated current, In

1/5 A1)

Thermal withstand capability:


Continuously

20 A

For 1 s

500 A

Dynamic current withstand:

Voltage inputs

Half-wave value

1250 A

Input impedance

<20 m

Rated voltage

60...210 V AC

Voltage withstand:

1)

ABB

Continuous

240 V AC

For 10 s

360 V AC

Burden at rated voltage

<0.05 VA

Residual current and/or phase current

27

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 9. Binary inputs


Description

Value

Operating range

20% of the rated voltage

Rated voltage

24...250 V DC

Current drain

1.6...1.9 mA

Power consumption

31.0...570.0 mW

Threshold voltage

16...176 V DC

Reaction time

<3 ms

Table 10. RTD/mA measurement (XRGGIO130)


Description
RTD inputs

mA inputs

Value
Supported RTD sensors

100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper

Supported resistance range

0...2 k

Maximum lead resistance (threewire measurement)

25 per lead

Isolation

2 kV (inputs to protective earth)

Response time

<4 s

RTD/resistance sensing current

Maximum 0.33 mA rms

Operation accuracy

Resistance

Temperature

2.0% or 1

1C
10 copper: 2C

Supported current range

020 mA

Current input impedance

44 0.1%

Operation accuracy

0.5% or 0.01 mA

TCR 0.00385 (DIN 43760)


TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427

Table 11. Signal output X100: SO1


Description

Value

Rated voltage

250 V AC/DC

Continuous contact carry

5A

Make and carry for 3.0 s

15 A

Make and carry for 0.5 s

30 A

Breaking capacity when the control-circuit time constant L/R<40 ms

1 A/0.25 A/0.15 A

Minimum contact load

100 mA at 24 V AC/DC

28

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 12. Signal outputs and IRF output


Description

Value

Rated voltage

250 V AC/DC

Continuous contact carry

5A

Make and carry for 3.0 s

10 A

Make and carry 0.5 s

15 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at


48/110/220 V DC

1 A/0.25 A/0.15 A

Minimum contact load

10 mA at 5 V AC/DC

Table 13. Double-pole power output relays with TCS function


Description

Value

Rated voltage

250 V AC/DC

Continuous contact carry

8A

Make and carry for 3.0 s

15 A

Make and carry for 0.5 s

30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at


48/110/220 V DC (two contacts connected in series)

5 A/3 A/1 A

Minimum contact load

100 mA at 24 V AC/DC

Trip-circuit supervision (TCS):


Control voltage range

20...250 V AC/DC

Current drain through the supervision circuit

~1.5 mA

Minimum voltage over the TCS contact

20 V AC/DC (15...20 V)

Table 14. Single-pole power output relays


Description

Value

Rated voltage

250 V AC/DC

Continuous contact carry

8A

Make and carry for 3.0 s

15 A

Make and carry for 0.5 s

30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at


48/110/220 V DC

5 A/3 A/1 A

Minimum contact load

100 mA at 24 V AC/DC

ABB

29

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 15. High-speed output HSO with BIO0007


Description

Value

Rated voltage

250 V AC/DC

Continuous contact carry

6A

Make and carry for 3.0 s

15 A

Make and carry for 0.5 s

30 A

Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC

5 A/3 A/1 A

Start

1 ms

Reset

20 ms, resistive load

Table 16. Front port Ethernet interfaces


Ethernet interface

Protocol

Cable

Data transfer rate

Front

TCP/IP protocol

Standard Ethernet CAT 5 cable with RJ-45 connector

10 MBits/s

Table 17. Station communication link, fibre-optic


Connector

Fibre type1)

Wave length

Max. distance

Permitted path attenuation2)

LC

MM 62.5/125 or 50/125 m
glass fibre core

1300 nm

2 km

<8 dB

ST

MM 62.5/125 or 50/125 m
glass fibre core

820-900 nm

1 km

<11 dB

1)
2)

(MM) multi-mode fibre, (SM) single-mode fibre


Maximum allowed attenuation caused by connectors and cable together

Table 18. IRIG-B


Description

Value

IRIG time code format

B004, B0051)

Isolation

500V 1 min

Modulation

Unmodulated

Logic level

5 V TTL

Current consumption

<4 mA

Power consumption

<20 mW

1)

According to the 200-04 IRIG standard

Table 19. Lens sensor and optical fibre for arc protection
Description

Value

Fibre-optic cable including lens

1.5 m, 3.0 m or 5.0 m

Normal service temperature range of the lens

-40...+100C

Maximum service temperature range of the lens, max 1 h

+140C

Minimum permissible bending radius of the connection fibre

100 mm

30

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 20. Degree of protection of flush-mounted IED


Description

Value

Front side

IP 54

Rear side, connection terminals

IP 20

Table 21. Environmental conditions


Description

Value

Operating temperature range

-25...+55C (continuous)

Short-time service temperature range

-40...+85C (<16h)1)2)

Relative humidity

<93%, non-condensing

Atmospheric pressure

86...106 kPa

Altitude

Up to 2000 m

Transport and storage temperature range

-40...+85C

1)
2)

ABB

Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C
For IEDs with an LC communication interface the maximum operating temperature is +70 C

31

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 22. Electromagnetic compatibility tests


Description

Type test value

1 MHz/100 kHz burst disturbance test

IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002

Common mode

2.5 kV

Differential mode

2.5 kV

3 MHz, 10 MHz and 30 MHz burst disturbance


test
Common mode

Reference

IEC 61000-4-18
IEC 60255-22-1, class III
2.5 kV

Electrostatic discharge test

IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001

Contact discharge

8 kV

Air discharge

15 kV

Radio frequency interference test


10 V (rms)
f = 150 kHz...80 MHz

IEC 61000-4-6
IEC 60255-22-6, class III

10 V/m (rms)
f = 80...2700 MHz

IEC 61000-4-3
IEC 60255-22-3, class III

10 V/m
f = 900 MHz

ENV 50204
IEC 60255-22-3, class III

20 V/m (rms)
f = 80...1000 MHz

IEEE C37.90.2-2004

Fast transient disturbance test

All ports

IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
4 kV

Surge immunity test

IEC 61000-4-5
IEC 60255-22-5

Communication

1 kV, line-to-earth

Other ports

4 kV, line-to-earth
2 kV, line-to-line

Power frequency (50 Hz) magnetic field


immunity test

IEC 61000-4-8

Continuous
1...3 s

300 A/m
1000 A/m

Pulse magnetic field immunity test

1000 A/m
6.4/16 s

Damped oscillatory magnetic field immunity test

IEC 61000-4-10

2s

100 A/m

1 MHz

400 transients/s

Voltage dips and short interruptions

30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms

32

IEC 61000-4-9

IEC 61000-4-11

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 22. Electromagnetic compatibility tests, continued


Description

Type test value

Reference

Power frequency immunity test

Binary inputs only

IEC 61000-4-16
IEC 60255-22-7, class A

Common mode

300 V rms

Differential mode

150 V rms

Conducted common mode disturbances

15 Hz...150 kHz
Test level 3 (10/1/10 V rms)

Emission tests

IEC 61000-4-16
EN 55011, class A
IEC 60255-25

Conducted
0.15...0.50 MHz

<79 dB (V) quasi peak


<66 dB (V) average

0.5...30 MHz

<73 dB (V) quasi peak


<60 dB (V) average

Radiated
30...230 MHz

<40 dB (V/m) quasi peak, measured at 10 m


distance

230...1000 MHz

<47 dB (V/m) quasi peak, measured at 10 m


distance

Table 23. Insulation tests


Description

Type test value

Reference

Dielectric tests

2 kV, 50 Hz, 1 min


500 V, 50 Hz, 1 min, communication

IEC 60255-5 and


IEC 60255-27

Impulse voltage test

5 kV, 1.2/50 s, 0.5 J


1 kV, 1.2/50 s, 0.5 J, communication

IEC 60255-5 and


IEC 60255-27

Insulation resistance measurements

>100 M, 500 V DC

IEC 60255-5 and


IEC 60255-27

Protective bonding resistance

<0.1 , 4 A, 60 s

IEC 60255-27

Description

Reference

Requirement

Vibration tests (sinusoidal)

IEC 60068-2-6 (test Fc)


IEC 60255-21-1

Class 2

Shock and bump test

IEC 60068-2-27 (test Ea shock)


IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2

Class 2

Seismic test

IEC 60255-21-3

Class 2

Table 24. Mechanical tests

ABB

33

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 25. Environmental tests


Description

Type test value

Reference

Dry heat test

96 h at +55C
16 h at +85C1)

IEC 60068-2-2

Dry cold test

96 h at -25C
16 h at -40C

IEC 60068-2-1

Damp heat test

6 cycles (12 h + 12 h) at +25C+55C,


humidity >93%

IEC 60068-2-30

Change of temperature test

5 cycles (3 h + 3 h)
at -25C...+55C

IEC60068-2-14

Storage test

96 h at -40C
96 h at +85C

IEC 60068-2-1
IEC 60068-2-2

1)

For IEDs with an LC communication interface the maximum operating temperature is +70 o C

Table 26. Product safety


Description

Reference

LV directive

2006/95/EC

Standard

EN 60255-27 (2005)
EN 60255-1 (2009)

Table 27. EMC compliance


Description

Reference

EMC directive

2004/108/EC

Standard

EN 50263 (2000)
EN 60255-26 (2007)

Table 28. RoHS compliance


Description
Complies with RoHS directive 2002/95/EC

34

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Protection functions
Table 29. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


PHLPTOC

1.5% of the set value or 0.002 In

PHHPTOC
and
PHIPTOC

1.5% of set value or 0.002 In

Start time 1)2)


PHIPTOC:
IFault = 2 set Start value
IFault = 10 set Start value
PHHPTOC and PHLPTOC:
IFault = 2 x set Start value

(at currents in the range of 0.110 In)


5.0% of the set value
(at currents in the range of 1040 In)
Minimum

Typical

Maximum

16 ms

19 ms

23 ms

11 ms

12 ms

14 ms

23 ms

26 ms

29 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<30 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Operate time accuracy in inverse time mode

5.0% of the theoretical value or 20 ms 3)


5.0% of the theoretical value or 40 ms 3)4)

Suppression of harmonics

RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression

1)
2)
3)
4)

ABB

Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Includes the delay of the heavy-duty output contact
Valid for FPHLPTOC

35

1MRS756891 H

Transformer Protection and Control


RET615
Product version: 5.0

Table 30. Three-phase non-directional overcurrent protection (PHxPTOC) main settings


Parameter

Function

Value (Range)

Step

Start Value

PHLPTOC

0.05...5.00 In

0.01

PHHPTOC

0.10...40.00 In

0.01

PHIPTOC

1.00...40.00 In

0.01

PHLPTOC

0.05...15.00

0.01

PHHPTOC

0.05...15.00

0.01

PHLPTOC

40...200000 ms

10

PHHPTOC

40...200000 ms

10

PHIPTOC

20...200000 ms

10

PHLPTOC

Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

PHHPTOC

Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC

Definite time

Time multiplier

Operate delay time

Operating curve type1)

1)

For further reference, see Operation characteristics table

Table 31. Non-directional earth-fault protection (EFxPTOC)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


EFLPTOC

1.5% of the set value or 0.002 In

EFHPTOC
and
EFIPTOC

1.5% of set value or 0.002 In


(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Minimum

Typical

Maximum

IFault = 10 set Start value

16 ms
11 ms

19 ms
12 ms

23 ms
14 ms

EFHPTOC and EFLPTOC:


IFault = 2 set Start value

23 ms

26 ms

29 ms

Start time 1)2)


EFIPTOC:
IFault = 2 set Start value

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<30 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Operate time accuracy in inverse time mode

5.0% of the theoretical value or 20 ms 3)

Suppression of harmonics

RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression

1)
2)
3)

36

Measurement mode = default (depends on stage), current before fault = 0.0 I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 I n , Start value multiples in range of 1.5...20

ABB

1MRS756891 H

Transformer Protection and Control


RET615
Product version: 5.0

Table 32. Non-directional earth-fault protection (EFxPTOC) main settings


Parameter

Function

Value (Range)

Step

Start value

EFLPTOC

0.010...5.000 In

0.005

EFHPTOC

0.10...40.00 In

0.01

EFIPTOC

1.00...40.00 In

0.01

EFLPTOC

0.05...15.00

0.01

EFHPTOC

0.05...15.00

0.01

EFLPTOC

40...200000 ms

10

EFHPTOC

40...200000 ms

10

EFIPTOC

20...200000 ms

10

EFLPTOC

Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

EFHPTOC

Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

EFIPTOC

Definite time

Time multiplier

Operate delay time

Operating curve type1)

1)

For further reference, see Operation characteristics table

Table 33. Negative phase-sequence overcurrent protection (NSPTOC)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


1.5% of the set value or 0.002 In

Start time 1)2)


IFault = 2 set Start value
IFault = 10 set Start value

Minimum

Typical

Maximum

23 ms
15 ms

26 ms
18 ms

28 ms
20ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Operate time accuracy in inverse time mode

5.0% of the theoretical value or 20 ms 3)

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

1)

Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements

2)
3)

Includes the delay of the signal output contact


Maximum Start value = 2.5 I n, Start value multiples in range of 1.5...20

Table 34. Negative phase-sequence overcurrent protection (NSPTOC) main settings


Parameter

Function

Value (Range)

Step

Start value

NSPTOC

0.01...5.00 In

0.01

Time multiplier

NSPTOC

0.05...15.00

0.01

Operate delay time

NSPTOC

40...200000 ms

10

Operating curve type1)

NSPTOC

Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

1)

ABB

For further reference, see Operation characteristics table

37

1MRS756891 H

Transformer Protection and Control


RET615
Product version: 5.0

Table 35. Residual overvoltage protection (ROVPTOV)


Characteristic

Value

Operation accuracy

Depending on the frequency of the voltage measured: fn 2 Hz


1.5% of the set value or 0.002 Un

Start time1)2)
UFault = 1.1 set Start value

Minimum

Typical

Maximum

48 ms

51 ms

54 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

1)

Residual voltage before fault = 0.0 U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000

2)

measurements
Includes the delay of the signal output contact

Table 36. Residual overvoltage protection (ROVPTOV) main settings


Parameter

Function

Value (Range)

Step

Start value

ROVPTOV

0.010...1.000 Un

0.001

Operate delay time

ROVPTOV

40...300000 ms

Table 37. Three phase undervoltage protection (PHPTUV)


Characteristic

Value

Operation accuracy

Depending on the frequency of the voltage measured: fn 2 Hz


1.5% of the set value or 0.002 Un

Start time1)2)
UFault = 0.9 set Start value

Minimum

Typical

Maximum

62 ms

66 ms

70 ms

Reset time

Typically 40 ms

Reset ratio

Depends on the set Relative hysteresis

Retardation time

<35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Operate time accuracy in inverse time mode

5.0% of the theoretical value or 20 ms3)

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

1)
2)
3)

38

Start value = 1.0 Un, Voltage before fault = 1.1 U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20

ABB

1MRS756891 H

Transformer Protection and Control


RET615
Product version: 5.0

Table 38. Three-phase undervoltage protection (PHPTUV) main settings


Parameter

Function

Value (Range)

Step

Start value

PHPTUV

0.05...1.20 Un

0.01

Time multiplier

PHPTUV

0.05...15.00

0.01

Operate delay time

PHPTUV

60...300000 ms

10

Operating curve type1)

PHPTUV

Definite or inverse time


Curve type: 5, 15, 21, 22, 23

1)

For further reference, see Operation characteristics table

Table 39. Three-phase overvoltage protection (PHPTOV)


Characteristic

Value

Operation accuracy

Depending on the frequency of the voltage measured: fn 2 Hz


1.5% of the set value or 0.002 Un

Start time1)2)
UFault = 1.1 set Start value

Minimum

Typical

Maximum

23 ms

27 ms

31 ms

Reset time

Typically 40 ms

Reset ratio

Depends of the set Relative hysteresis

Retardation time

<35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Operate time accuracy in inverse time mode

5.0% of the theoretical value or 20 ms3)

Suppression of harmonics

DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,

1)
2)
3)

Start value = 1.0 Un, Voltage before fault = 0.9 U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 1.20 U n, Start value multiples in range of 1.10... 2.00

Table 40. Three-phase overvoltage protection (PHPTOV) main settings


Parameter

Function

Value (Range)

Step

Start value

PHPTOV

0.05...1.60 Un

0.01

Time multiplier

PHPTOV

0.05...15.00

0.01

Operate delay time

PHPTOV

40...300000 ms

10

Operating curve type1)

PHPTOV

Definite or inverse time


Curve type: 5, 15, 17, 18, 19, 20

1)

For further reference, see Operation characteristics table

Table 41. Thermal overload protection, two time constants (T2PTTR)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


Current measurement: 1.5% of the set value or 0.002 x In (at
currents in the range of 0.01...4.00 x In)

Operate time accuracy1)


1)

ABB

2.0% of the theoretical value or 0.50 s

Overload current > 1.2 x Operate level temperature

39

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 42. Thermal overload for protection, two time constants (T2PTTR) main settings
Parameter

Function

Value (Range)

Step

Temperature rise

T2PTTR

0.0...200.0oC

0.1

Max temperature

T2PTTR

0.0...200.0oC

0.1

Operate temperature

T2PTTR

80.0...120.0 %

0.1

Weighting factor p

T2PTTR

0.00...1.00

0.01

Short time constant

T2PTTR

6...60000 s

Current reference

T2PTTR

0.05...4.00 x In

0.01

Operation

T2PTTR

Off
On

Table 43. Transformer differential protection of two-winding transformers (TR2PTDF)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


3.0% of the set value or 0.002 In

Start time1)2)

Minimum

Typical

Maximum

36 ms
21 ms

41 ms
22 ms

46 ms
24 ms

Low stage
High stage
Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

1)

Current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements

2)

Includes the delay of the output contact. When differential current = 2 set operate value and f n = 50 Hz.

40

ABB

1MRS756891 H

Transformer Protection and Control


RET615
Product version: 5.0

Table 44. Stabilized differential protection for two-winding transformers (TR2PTDF) main settings
Parameter

Function

Value (Range)

Step

Restraint mode

TR2PTDF

2.h & 5.h & wav


Waveform
2.h & waveform
5.h & waveform

High operate value

TR2PTDF

500...3000 %

10

Low operate value

TR2PTDF

5...50 %

Slope section 2

TR2PTDF

10...50 %

End section 2

TR2PTDF

100...500 %

Start value 2.H

TR2PTDF

7...20 %

Start value 5.H

TR2PTDF

10...50 %

Operation

TR2PTDF

Off
On

Winding 1 type

TR2PTDF

Y
YN
D
Z
ZN

Winding 2 type

TR2PTDF

Y
YN
D
Z
ZN

Zro A elimination

TR2PTDF

Not eliminated
Winding 1
Winding 2
Winding 1 and 2

Table 45. Numerical stabilized low impedance restricted earth-fault protection (LREFPNDF)
Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


2.5% of the set value or 0.002 x In

Start time1)2)
IFault = 2.0 set Operate value

Minimum

Typical

Maximum

37 ms

41 ms

45 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

Retardation time

<35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

1)

Current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements

2)

Includes the delay of the signal output contact

ABB

41

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 46. Stabilized restricted earth-fault protection (LREFPNDF) main settings


Parameter

Function

Value (Range)

Step

Operate value

LREFPNDF

5...50 %

Restraint mode

LREFPNDF

None
2nd harmonic

Start value 2.H

LREFPNDF

10...50 %

Minimum operate time

LREFPNDF

40...300000 ms

Operation

LREFPNDF

Off
On

Table 47. High-impedance based restricted earth-fault protection (HREFPDIF)


Characteristic

Value

Operation accuracy

At the frequency f = fn
1.5% of the set value or 0.002 In

Start time1)2)

IFault = 2.0 set Operate value


IFault = 10.0 set Operate value

Typical 22 ms (5 ms)
Typical 15 ms (5 ms)

Reset time

< 60 ms

Reset ratio

Typical 0.96

Retardation time

< 60 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

1)

Current before fault = 0.0 I n , f n = 50 Hz

2)

Includes the delay of the signal output contact

Table 48. High-impedance based restricted earth-fault protection (HREFPDIF) main settings
Parameter

Function

Value (Range)

Step

Operate value

HREFPDIF

1.0...50.0 %

0.1

Minimum operate time

HREFPDIF

40...300000 ms

Operation

HREFPDIF

Off
On

Table 49. Circuit breaker failure protection (CCBRBRF)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


1.5% of the set value or 0.002 In

Operate time accuracy

1.0% of the set value or 20 ms

Retardation time

<20 ms

42

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 50. Circuit breaker failure protection (CCBRBRF) main settings


Parameter

Function

Value (Range)

Step

Current value (Operating phase


current)

CCBRBRF

0.05...1.00 In

0.05

Current value Res (Operating


residual current)

CCBRBRF

0.05...1.00 In

0.05

CB failure mode (Operating mode


of function)

CCBRBRF

1 = Current
2 = Breaker status
3 = Both

CB fail trip mode

CCBRBRF

1 = Off
2 = Without check
3 = Current check

Retrip time

CCBRBRF

0...60000 ms

10

CB failure delay

CCBRBRF

0...60000 ms

10

CB fault delay

CCBRBRF

0...60000 ms

10

Table 51. Arc protection (ARCSARC)


Characteristic

Value

Operation accuracy

3% of the set value or 0.01 In

Operate time

Minimum

Typical

Maximum

Operation mode = "Light


+current"1)2)

9 ms

12 ms

15 ms

Operation mode = "Light only"2)

9 ms

10 ms

12 ms

Reset time

Typically 40 ms

Reset ratio

Typically 0.96

1)

Phase start value = 1.0 I n, current before fault = 2.0 set Phase start value , f n = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements

2)

Includes the delay of the heavy-duty output contact

Table 52. Arc protection (ARCSARC) main settings


Parameter

Function

Value (Range)

Step

Phase start value (Operating


phase current)

ARCSARC

0.50...40.00 x In

0.01

Ground start value (Operating


residual current)

ARCSARC

0.05...8.00 x In

0.01

Operation mode

ARCSARC

1=Light+current
2=Light only
3=BI controlled

Table 53. Multipurpose protection (MAPGAPC)


Characteristic

Value

Operation accuracy

1.0% of the set value or 20 ms

ABB

43

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 54. Multipurpose analog protection (MAPGAPC) main settings


Parameter

Function

Value (Range)

Step

Start value

MAPGAPC

-10000.0...10000.0

0.1

Operate delay time

MAPGAPC

0...200000 ms

100

Operation mode

MAPGAPC

Over
Under

Table 55. Operation characteristics


Parameter

Value (Range)

Operating curve type

1 = ANSI Ext. inv.


2 = ANSI Very. inv.
3 = ANSI Norm. inv.
4 = ANSI Mod inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv
15 = IEC Def. Time
17 = Programmable
18 = RI type
19 = RD type

Operating curve type (voltage protection)

5 = ANSI Def. Time


15 = IEC Def. Time
17 = Inv. Curve A
18 = Inv. Curve B
19 = Inv. Curve C
20 = Programmable
21 = Inv. Curve A
22 = Inv. Curve B
23 = Programmable

44

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Control functions
Table 56. Tap position indication (TPOSSLTC)
Descrpition

Value

Response time for binary inputs

Typical 100 ms

ABB

45

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Supervision functions
Table 57. Fuse failure supervision (SEQRFUF)
Characteristic
Operate time1)

Value
NPS function

UFault = 1.1 set Neg Seq voltage

<33 ms

Lev

Delta function

1)

UFault = 5.0 set Neg Seq voltage


Lev

<18 ms

U = 1.1 set Voltage change rate

<30 ms

U = 2.0 set Voltage change rate

<24 ms

Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements

Table 58. Motor run time counter (MDSOPT)


Description

Value

Motor run-time measurement accuracy1)

0.5%

1)

46

Of the reading, for a stand-alone IED, without time synchronization.

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Measurement functions
Table 59. Three-phase current measurement (CMMXU)
Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: fn 2 Hz


0.5% or 0.002 In
(at currents in the range of 0.01...4.00 In)

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,


RMS: No suppression

Table 60. Current sequence components (CSMSQI)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: f/fn = 2 Hz


1.0% or 0.002 In
at currents in the range of 0.01...4.00 In

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

Table 61. Residual current measurement (RESCMMXU)


Characteristic

Value

Operation accuracy

Depending on the frequency of the current measured: f/fn = 2 Hz


0.5% or 0.002 In
at currents in the range of 0.01...4.00 In

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,


RMS: No suppression

Table 62. Three-phase voltage measurement (VMMXU)


Characteristic

Value

Operation accuracy

Depending on the frequency of the voltage measured: fn 2 Hz


At voltages in range 0.011.15 Un
0.5% or 0.002 Un

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,


RMS: No suppression

Table 63. Residual voltage measurement (RESVMMXU)


Characteristic

Value

Operation accuracy

Depending on the frequency of the measured current: f/fn = 2 Hz


0.5% or 0.002 Un

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,


RMS: No suppression

ABB

47

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 64. Voltage sequence components (VSMSQI)


Characteristic

Value

Operation accuracy

Depending on the frequency of the voltage measured: fn 2 Hz


At voltages in range 0.011.15 Un
1.0% or 0.002 Un

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

Table 65. Three-phase power and energy (PEMMXU)


Characteristic

Value

Operation accuracy

At all three currents in range 0.101.20 In


At all three voltages in range 0.501.15 Un
At the frequency fn 1 Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71
1.5% for power (S, P and Q)
0.015 for power factor
1.5% for energy

Suppression of harmonics

DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,

Table 66. RTD/mA measurement (XRGGIO130)


Value

Description
RTD inputs

mA inputs

48

Supported RTD sensors

100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper

Supported resistance range

0...2 k

Maximum lead resistance (threewire measurement)

25 per lead

Isolation

2 kV (inputs to protective earth)

Response time

<4 s

RTD/resistance sensing current

Maximum 0.33 mA rms

Operation accuracy

Resistance

Temperature

2.0% or 1

1C
10 copper: 2C

Supported current range

020 mA

Current input impedance

44 0.1%

Operation accuracy

0.5% or 0.01 mA

TCR 0.00385 (DIN 43760)


TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

19. Local HMI


The IED is available with two optional displays, a large one
and a small one. The large display is suited for IED
installations where the front panel user interface is frequently
used and a single line diagram is required. The small display
is suited for remotely controlled substations where the IED is
only occasionally accessed locally via the front panel user
interface.
Both LCD displays offer front-panel user interface
functionality with menu navigation and menu views. However,
the large display offers increased front-panel usability with
less menu scrolling and improved information overview. In
addition, the large display includes a user-configurable single
line diagram (SLD) with position indication for the associated
primary equipment. Depending on the chosen standard
configuration, the IED displays the related measuring values,

IECA070904 V3 EN

Figure 17.

apart from the default single line diagram. The SLD view can
also be accessed using the Web browser-based user
interface. The default SLD can be modified according to user
requirements by using the Graphical Display Editor in
PCM600. The user can create up to 10 SLD pages.
The local HMI includes a push button (L/R) for local/remote
operation of the IED. When the IED is in the local mode, the
IED can be operated only by using the local front panel user
interface. When the IED is in the remote mode, the IED can
execute commands sent from a remote location. The IED
supports the remote selection of local/remote mode via a
binary input. This feature facilitates, for example, the use of
an external switch at the substation to ensure that all IEDs are
in the local mode during maintenance work and that the
circuit breakers cannot be operated remotely from the
network control center.

IECA070901 V3 EN

Small display

Figure 18.

Large display

Table 67. Small display


Character size1)

Rows in the view

Characters per row

Small, mono-spaced (6x12 pixels)

20

Large, variable width (13x14 pixels)

8 or more

1)

Depending on the selected language

Table 68. Large display


Character size1)

Rows in the view

Characters per row

Small, mono-spaced (6x12 pixels)

10

20

Large, variable width (13x14 pixels)

8 or more

1)

ABB

Depending on the selected language

49

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Mounting methods:

20. Mounting methods


By means of appropriate mounting accessories the standard
IED case for the 615 series IED can be flush mounted, semiflush mounted or wall mounted. The flush mounted and wall
mounted IED cases can also be mounted in a tilted position
(25) using special accessories.

Further, the IEDs can be mounted in any standard 19


instrument cabinet by means of 19 mounting panels available
with cut-outs for one or two IEDs.Alternatively, the IED can be
mounted in 19 instrument cabinets by means of 4U
Combiflex equipment frames.

Flush mounting
Semi-flush mounting
Semi-flush mounting in a 25 tilt
Rack mounting
Wall mounting
Mounting to a 19" equipment frame
Mounting with a RTXP 18 test switch to a 19" rack

Panel cut-out for flush mounting:


Height: 161.5 1 mm
Width: 165.5 1 mm

For the routine testing purposes, the IED cases can be


equipped with test switches, type RTXP 18, which can be
mounted side by side with the IED cases.

190

6
18
164

177

230

177

177

160

160

25

1 53

48

IECA070900 V4 EN

Figure 19.

98

IECA070903 V4 EN

Flush mounting

Figure 20.

133

IECA070902 V4 EN

Semi-flush mounting

21. IED case and IED plug-in unit


For safety reasons, the IED cases for current measuring IEDs
are provided with automatically operating contacts for shortcircuiting the CT secondary circuits when a IED unit is
withdrawn from its case. The IED case is further provided with
a mechanical coding system preventing current measuring
IED units from being inserted into a IED case for a voltage

50

107

103

Figure 21.

Semi-flush with a 25 tilt

measuring IED unit and vice versa, i.e. the IED cases are
assigned to a certain type of IED plug-in unit.
22. Selection and ordering data
Use the ABB Library to access the selection and ordering
information and to generate the order number.

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

23. Accessories and ordering data


Table 69. Cables
Item

Order number

Cable for optical sensors for arc protection 1.5 m

1MRS120534-1.5

Cable for optical sensors for arc protection 3.0 m

1MRS120534-3.0

Cable for optical sensors for arc protection 5.0 m

1MRS120534-5.0

Table 70. Mounting accessories


Item

Order number

Semi-flush mounting kit

1MRS050696

Wall mounting kit

1MRS050697

Inclined semi-flush mounting kit

1MRS050831

19 rack mounting kit with cut-out for one IED

1MRS050694

19 rack mounting kit with cut-out for two IEDs

1MRS050695

Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19 variant C)

2RCA022642P0001

Mounting bracket for one IED in 4U Combiflex (RHGT 19 variant C)

2RCA022643P0001

19 rack mounting kit for one IED and one RTXP18 test switch (the test switch is not included in the delivery)

2RCA021952A0003

19 rack mounting kit for one IED and one RTXP24 test switch (the test switch is not included in the delivery)

2RCA022561A0003

Replacement kit for a Strmberg SP_J40 series relay (cut-out in the center of the installation plate)

2RCA027871A0001

Replacement kit for a Strmberg SP_J40 series relay (cut-out on the left or the right of the installation plate)

2RCA027874A0001

Replacement kit for two Strmberg SP_J3 series relays

2RCA027880A0001

19 rack replacement kit for Strmberg SP_J3/J6 series relays (one cut-out)

2RCA027894A0001

19 rack replacement kit for Strmberg SP_J3/J6 series relays (two cut-outs)

2RCA027897A0001

Replacement kit for a Strmberg SP_J6 series relay

2RCA027881A0001

Replacement kit for three BBC S_ series relays

2RCA027882A0001

Replacement kit for a SPA 300 series relay

2RCA027885A0001

ABB

51

Transformer Protection and Control


RET615
Product version: 5.0

24. Tools
The IED is delivered as a pre-configured unit. The default
parameter setting values can be changed from the front-panel
user interface, the Web browser-based user interface (Web
HMI) or the PCM600 tool in combination with the IED-specific
connectivity package.
The Protection and Control IED Manager PCM600 offers
extensive IED configuration functions such as IED signal
configuration, application configuration, graphical display
configuration including single line diagram configuration, and
IEC 61850 communication configuration including horizontal
GOOSE communication.
When the Web browser-based user interface is used, the IED
can be accessed either locally or remotely, using a Web
browser (Internet Explorer). For security reasons, the Web

1MRS756891 H

browser-based user interface is disabled by default. The


interface can be enabled with PCM600 or via the front panel
user interface. The functionality of the interface can be limited
to read-only access through PCM600.
The IED connectivity package is a collection of software and
specific IED information, which enable system products and
tools to connect and interact with the IED. The connectivity
packages reduce the risk of errors in system integration,
minimizing device configuration and set-up times. Further, the
connectivity packages for this product series IEDs include a
flexible update tool for adding one additional local HMI
language to the IED. The update tool is activated using
PCM600, and it enables multiple updates of the additional
HMI language, thus offering flexible means for possible future
language updates.

Table 71. Tools


Configuration and setting tools

Version

PCM600

2.6 or later

Web-browser based user interface

IE 8.0, IE 9.0 or IE 10.0

RE_615 Connectivity Package

5.0

52

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 72. Supported functions


Function

Web HMI

PCM600

IED parameter setting

Saving of IED parameter settings in the IED

Signal monitoring

Disturbance recorder handling

Alarm LED viewing

Access control management

IED signal configuration (signal matrix)

Modbus communication configuration (communication


management)

DNP3 communication configuration (communication


management)

IEC 60870-5-103 communication configuration


(communication management)

Saving of IED parameter settings in the tool

Disturbance record analysis

XRIO parameter export/import

Graphical display configuration

Application configuration

IEC 61850 communication configuration, GOOSE


(communication configuration)

Phasor diagram viewing

Event viewing

Saving of event data on the user's PC

Online monitoring

= Supported

25. Cyber security

IED supports role based user authentication and


authorization. It can store 2048 audit trail events to nonvolatile memory. FTP used for, for example, configuration

ABB

download and Web HMI uses TLS encryption with 128 bit
key length protecting data in transit according FTPS and
HTTPS standards.

53

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

26. Terminal diagrams

GUID-3CB989EB-6ECA-471F-8692-DB15C1DE5EFB V2 EN

Figure 22.

54

Terminal diagram of standard configurations A-D

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

GUID-3655E0AF-034F-4D63-B098-5B5321A13662 V1 EN

Figure 23.

ABB

Terminal diagram of standard configurations E-H

55

Transformer Protection and Control


RET615
Product version: 5.0

27. Certificates
KEMA has issued an IEC 61850 Certificate Level A1 for
Relion 615 series. Certificate number: 74102147-MOC/INC
13-4263.
Det Norske Veritas (DNV) has issued a Type Approval
Certificate for RET615. Certificate number: E-11189.

1MRS756891 H

The download area to the right contains the latest product


documentation, such as the technical manual, installation
manual and operation manual.
The Features and Application tabs contain product-related
information in a compact format.

28. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
products and services.
You will find the latest relevant information on the RET615
protection IED on the product page.

56

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

29. Functions, codes and symbols


Table 73. Functions included in the IED
Function

IEC 61850

IEC 60617

IEC-ANSI

PHLPTOC1

3I> (1)

51P-1 (1)

PHLPTOC2

3I> (2)

51P-1 (2)

PHHPTOC1

3I>> (1)

51P-2 (1)

PHHPTOC2

3I>> (2)

51P-2 (2)

Three-phase non-directional overcurrent protection, instantaneous


stage

PHIPTOC1

3I>>> (1)

50P/51P (1)

PHIPTOC2

3I>>> (2)

50P/51P (2)

Non-directional earth-fault protection, low stage

EFLPTOC1

Io> (1)

51N-1 (1)

EFLPTOC2

Io> (2)

51N-1 (2)

EFHPTOC1

Io>> (1)

51N-2 (1)

EFHPTOC2

Io>> (2)

51N-2 (2)

NSPTOC1

I2> (1)

46 (1)

NSPTOC2

I2> (2)

46 (2)

ROVPTOV1

Uo> (1)

59G (1)

ROVPTOV2

Uo> (2)

59G (2)

PHPTUV1

3U< (1)

27 (1)

PHPTUV2

3U< (2)

27 (2)

PHPTOV1

3U> (1)

59 (1)

PHPTOV2

3U> (2)

59 (2)

Three-phase thermal overload protection for power transformers,


two time constants

T2PTTR1

3Ith>T (1)

49T (1)

Stabilized and instantaneous differential protection for 2Wtransformers

TR2PTDF1

3dI>T (1)

87T (1)

Numerical stabilized low impedance restricted earth-fault protection

LREFPNDF1

dIoLo> (1)

87NL (1)

High impedance based restricted earth-fault protection

HREFPDIF1

dIoHi> (1)

87NH (1)

Circuit breaker failure protection

CCBRBRF1

3I>/Io>BF (1)

51BF/51NBF (1)

Master trip

TRPPTRC1

Master Trip (1)

94/86 (1)

TRPPTRC2

Master Trip (2)

94/86 (2)

TRPPTRC3

Master Trip (3)

94/86 (3)

TRPPTRC4

Master Trip (4)

94/86 (4)

TRPPTRC5

Master Trip (5)

94/86 (5)

ARCSARC1

ARC (1)

50L/50NL (1)

ARCSARC2

ARC (2)

50L/50NL (2)

ARCSARC3

ARC (3)

50L/50NL (3)

Protection
Three-phase non-directional overcurrent protection, low stage

Three-phase non-directional overcurrent protection, high stage

Non-directional earth-fault protection, high stage

Negative-sequence overcurrent protection

Residual overvoltage protection

Three-phase undervoltage protection

Three-phase overvoltage protection

Arc protection

ABB

57

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 73. Functions included in the IED, continued


Function

IEC 61850

IEC 60617

IEC-ANSI

Multi-purpose protection1)

MAPGAPC1

MAP (1)

MAP (1)

MAPGAPC2

MAP (2)

MAP (2)

MAPGAPC3

MAP (3)

MAP (3)

MAPGAPC4

MAP (4)

MAP (4)

MAPGAPC5

MAP (5)

MAP (5)

MAPGAPC6

MAP (6)

MAP (6)

MAPGAPC7

MAP (7)

MAP (7)

MAPGAPC8

MAP (8)

MAP (8)

MAPGAPC9

MAP (9)

MAP (9)

MAPGAPC10

MAP (10)

MAP (10)

MAPGAPC11

MAP (11)

MAP (11)

MAPGAPC12

MAP (12)

MAP (12)

MAPGAPC13

MAP (13)

MAP (13)

MAPGAPC14

MAP (14)

MAP (14)

MAPGAPC15

MAP (15)

MAP (15)

MAPGAPC16

MAP (16)

MAP (16)

MAPGAPC17

MAP (17)

MAP (17)

MAPGAPC18

MAP (18)

MAP (18)

Circuit-breaker control

CBXCBR1

I <-> O CB (1)

I <-> O CB (1)

Disconnector control

DCXSWI1

I <-> O DCC (1)

I <-> O DCC (1)

DCXSWI2

I <-> O DCC (2)

I <-> O DCC (2)

Earthing switch control

ESXSWI1

I <-> O ESC (1)

I <-> O ESC (1)

Disconnector position indication

DCSXSWI1

I <-> O DC (1)

I <-> O DC (1)

DCSXSWI2

I <-> O DC (2)

I <-> O DC (2)

DCSXSWI3

I <-> O DC (3)

I <-> O DC (3)

ESSXSWI1

I <-> O ES (1)

I <-> O ES (1)

ESSXSWI2

I <-> O ES (2)

I <-> O ES (2)

TPOSSLTC1

TPOSM (1)

84M (1)

Circuit-breaker condition monitoring

SSCBR1

CBCM (1)

CBCM (1)

Trip circuit supervision

TCSSCBR1

TCS (1)

TCM (1)

TCSSCBR2

TCS (2)

TCM (2)

Fuse failure supervision

SEQRFUF1

FUSEF (1)

60 (1)

Runtime counter for machines and devices

MDSOPT1

OPTS (1)

OPTM (1)

Disturbance recorder

RDRE1

DR (1)

DFR (1)

Load profile record

LDPMSTA1

LOADPROF (1)

LOADPROF (1)

Control

Earthing switch indication

Tap changer position indication


Condition monitoring

Measurement

58

ABB

Transformer Protection and Control


RET615
Product version: 5.0

1MRS756891 H

Table 73. Functions included in the IED, continued


Function

IEC 61850

IEC 60617

IEC-ANSI

Three-phase current measurement

CMMXU1

3I (1)

3I (1)

CMMXU2

3I (2)

3I (2)

Sequence current measurement

CSMSQI1

I1, I2, I0 (1)

I1, I2, I0 (1)

Residual current measurement

RESCMMXU1

Io (1)

In (1)

RESCMMXU2

Io (2)

In (2)

Three-phase voltage measurement

VMMXU1

3U (1)

3V (1)

Residual voltage measurement

RESVMMXU1

Uo (1)

Vn (1)

Sequence voltage measurement

VSMSQI1

U1, U2, U0 (1)

V1, V2, V0 (1)

Three-phase power and energy measurement

PEMMXU1

P, E (1)

P, E (1)

RTD/mA measurement

XRGGIO130

X130 (RTD) (1)

X130 (RTD) (1)

IEC 61850-9-2 LE (Voltage sharing)2)

SMVSENDER

SMVSENDER

SMVSENDER

1)
2)

For example, used for RTD/mA based protection or analog GOOSE


Only available with redundant Ethernet communication modules

30. Document revision history


Document revision/date

Product version

History

A/2009-07-03

2.0

First release

B/2009-10-01

2.0

Content updated

C/2010-06-11

3.0

Content updated to correspond to the product version

D/2010-06-29

3.0

Terminology updated

E/2010-09-07

3.0

Content updated

F/2012-05-11

4.0

Content updated to correspond to the product version

G/2013-02-21

4.0 FP1

Content updated to correspond to the product version

H/2014-01-24

5.0

Content updated to correspond to the product version

ABB

59

60

ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094

ABB Limited
Distribution Automation
Maneja
Vadodara 390013, India
Phone
+91 265 2604032
Fax
+91 265 2638922
www.abb.com/substationautomation

1MRS756891 H Copyright 2014 ABB. All rights reserved.

Contact us

Das könnte Ihnen auch gefallen