Beruflich Dokumente
Kultur Dokumente
Established in 1993
The leading independent repairer of servo motors and drives in North America.
2094-BC01-MP5-S, -BC01-M01-S,
-BC02-M02-S, -BC04-M03-S, -BC07-M05-S
2094-PRF
2094-AL09, -AL75S
2094-BL02, -BL75S
2094-XL75S-C1
2094-XL75S-C2
2094-BSP2)
Integration Manual
Important User Information Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
Allen-Bradley, A-B, ControlLogix, and Kinetix are registered trademarks of Rockwell Automation.
DriveExplorer, RSLogix, RSLogix 5000, SoftLogix, and SCANport are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . P-1
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Contents of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Product Receiving and Storage Responsibility . . . . . . . . . . . P-2
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . P-3
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . P-4
Chapter 1
Commission Your Kinetix 6000 Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
General Startup Precautions . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Understand IAM/AM Connectors . . . . . . . . . . . . . . . . . . . . 1-2
Integrated Axis Module/Axis Module Connectors . . . . . . 1-2
Locate IAM Connectors and Indicators . . . . . . . . . . . . . . . . 1-3
Locate AM Connectors and Indicators . . . . . . . . . . . . . . . . . 1-4
Understand SM Connectors . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Locate Shunt Module Connectors . . . . . . . . . . . . . . . . . 1-5
Understand LIM Connectors and Indicators . . . . . . . . . . . . . 1-6
Line Interface Module Connectors . . . . . . . . . . . . . . . . . 1-6
Locate SERCOS Interface Fiber-Optic Connectors . . . . . . . . 1-9
Configure Your Kinetix 6000 . . . . . . . . . . . . . . . . . . . . . . . 1-9
Configure Your Integrated Axis Module. . . . . . . . . . . . 1-10
Configure Your Axis Module(s) . . . . . . . . . . . . . . . . . . 1-15
Configure Your Logix SERCOS interface Module . . . . . . . . 1-16
Configure Your Logix Controller . . . . . . . . . . . . . . . . . 1-16
Configure Your Logix Module . . . . . . . . . . . . . . . . . . . 1-17
Configure Your Kinetix 6000 Modules . . . . . . . . . . . . . 1-19
Configure the Motion Group . . . . . . . . . . . . . . . . . . . . 1-23
Configure Axis Properties . . . . . . . . . . . . . . . . . . . . . . 1-24
Download Your Program . . . . . . . . . . . . . . . . . . . . . . 1-25
Apply Power to Your Kinetix 6000 . . . . . . . . . . . . . . . . . . 1-26
Apply Power to Your Kinetix 6000 (with LIM) . . . . . . . 1-26
Apply Power to Your Kinetix 6000 (without LIM). . . . . 1-30
Test and Tune Your Axes. . . . . . . . . . . . . . . . . . . . . . . . . 1-33
Test Your Axes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33
Tune Your Axes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36
Chapter 2
Troubleshoot Your Kinetix 6000 Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
General Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Troubleshoot IAM/AM Status LEDs . . . . . . . . . . . . . . . . . . . 2-8
Drive Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Comm Status LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Appendix A
Interconnect Diagrams Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Kinetix 6000 Interconnect Diagram Notes . . . . . . . . . . . . . . A-1
Power Interconnect Diagrams. . . . . . . . . . . . . . . . . . . . . . . A-3
DC Common Bus Interconnect Diagrams . . . . . . . . . . . . . . A-8
Shunt Module Interconnect Diagrams . . . . . . . . . . . . . . . . A-13
1336 Active Shunt Input Fuse Specifications . . . . . . . . . A-14
1336 Active Shunt Fault Relay Specifications . . . . . . . . A-14
AM/Motor Interconnect Diagrams . . . . . . . . . . . . . . . . . . . A-16
Controlling a Brake Example . . . . . . . . . . . . . . . . . . . . . . A-24
System Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . A-26
IAM/AM Inverter Block Diagram . . . . . . . . . . . . . . . . . A-26
IAM Converter Block Diagram . . . . . . . . . . . . . . . . . . . A-27
Safe-Off Feature Block Diagram. . . . . . . . . . . . . . . . . . A-28
SM Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . A-28
LIM Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . A-29
RBM Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . A-34
Appendix B
Upgrade Your Kinetix 6000 Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Firmware Upgrade Drive Firmware Using DriveExplorer . . . . . . . . . . B-1
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Select Axis Modules to Upgrade . . . . . . . . . . . . . . . . . . B-1
HyperTerminal Configuration . . . . . . . . . . . . . . . . . . . . B-4
Flash Your Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . B-5
Appendix C
Integrate Resistive Brake Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
Modules Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
with Kinetix 6000 Drives Understand Safety Precautions . . . . . . . . . . . . . . . . . . . . . . C-2
Safety Standards for Reference . . . . . . . . . . . . . . . . . . . C-2
Background on Safety Design . . . . . . . . . . . . . . . . . . . . C-3
Stop Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
Risk Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
Control Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
Resistive Brake Module Interconnect Diagram Notes . . . . . . C-5
Resistive Brake Module Interconnect Diagrams . . . . . . . . . . C-6
Set the RBM Delay Time Using DriveExplorer . . . . . . . . . . C-14
Remove SERCOS Communication . . . . . . . . . . . . . . . . C-14
Set the RBM Delay Time Parameter . . . . . . . . . . . . . . . C-15
Save the Delay Time Parameter to Non-Volatile
Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-16
Reconnect SERCOS Communication . . . . . . . . . . . . . . C-17
Appendix D
DC Common Bus Applications Chapter Objectives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Calculate Total Bus Capacitance . . . . . . . . . . . . . . . . . . D-2
Calculate Additional Bus Capacitance . . . . . . . . . . . . . . D-3
Kinetix 6000 Capacitance Values . . . . . . . . . . . . . . . . . . D-3
Common Bus Capacitance Example . . . . . . . . . . . . . . . D-4
Set the Additional Bus Capacitance Parameter. . . . . . . . . . . D-5
Remove SERCOS Communication . . . . . . . . . . . . . . . . . D-5
Set the Additional Bus Capacitance Parameter . . . . . . . . D-6
Save the Add Bus Cap Parameter to Non-Volatile
Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-7
Reconnect SERCOS Communication . . . . . . . . . . . . . . . D-8
Introduction Read this preface to familiarize yourself with the rest of the manual.
This preface contains the following topics:
Who Should Use this This manual is intended for engineers or programmers directly
involved in the operation, field maintenance, and integration of the
Manual Kinetix 6000 multi-axis servo drive with the SERCOS interface module.
Purpose of this Manual This manual provides the startup, configuration, and troubleshooting
procedures for the Kinetix 6000. The purpose of this manual is to
assist you in the integration of your Kinetix 6000 servo drive with the
ControlLogix 1756-MxxSE SERCOS interface module or SoftLogix
1784-PM16SE SERCOS PCI card.
Contents of this Manual Refer to the following listing for the descriptive contents of this
installation manual.
Product Receiving and You, the customer, are responsible for thoroughly inspecting the
equipment before accepting the shipment from the freight company.
Storage Responsibility Check the item(s) you receive against your purchase order. If any
items are obviously damaged, it is your responsibility to refuse
delivery until the freight agent has noted the damage on the freight
bill. Should you discover any concealed damage during unpacking,
you are responsible for notifying the freight agent. Leave the shipping
container intact and request that the freight agent make a visual
inspection of the equipment.
Installation instructions for the LIM and removal/replacement Kinetix 6000 Line Interface Module Installation 2094-IN005
procedures for selected internal LIM components Instructions
Information on wiring and troubleshooting your Kinetix 6000 safety Kinetix Safe-Off Feature Safety Reference Manual GMC-RM002
drive
A description and specifications for the 2094 family including motors
and motor accessories Kinetix Motion Control Selection Guide GMC-SG001
Drive and motor sizing with application analysis software Motion Analyzer CD PST-SG003
(v4.1 or above)
Kinetix 6000 user documentation and CAD files Kinetix 6000 User Documentation and CAD Files CD 2094-CL001
More detailed information on the use of ControlLogix motion features
and application examples ControlLogix Motion Module Programming Manual 1756-RM086
ControlLogix SERCOS interface module installation instructions SERCOS interface Module Installation Instructions 1756-IN572
SoftLogix SERCOS interface PCI card installation instructions 16 Axis PCI SERCOS interface Card Installation 1784-IN041
Instructions
Logix5000 Controllers Motion Instructions
The instructions needed to program a motion application Reference Manual 1756-RM007
Information on configuring and troubleshooting your ControlLogix Logix5000 Motion Modules User Manual 1756-UM006
SERCOS and analog motion modules
Information on configuring and troubleshooting your SoftLogix PCI SoftLogix Motion Card Setup and Configuration
card Manual 1784-UM003
Information on proper handling, installing, testing, and Fiber-Optic Cable Installation and Handling 2090-IN010
troubleshooting fiber-optic cables Instructions
Information, examples, and techniques designed to minimize system
failures caused by electrical noise System Design for Control of Electrical Noise GMC-RM001
Conventions Used in this The following conventions are used throughout this manual.
Manual • Bulleted lists such as this one provide information, not procedural
steps
• Numbered lists provide sequential steps or hierarchical
information
• Words that you type or select appear in bold
• When we refer you to another location, the section or chapter
name appears in italics
• Acronyms for the Kinetix 6000 components, shown in the table
below, are used throughout this manual.
Chapter Objectives This chapter provides you with information to apply power and
configure your Kinetix 6000. This chapter includes:
General Startup The following precautions pertain to all of the procedures in this
chapter. Be sure to read and thoroughly understand them before
Precautions proceeding.
ATTENTION
This product contains stored energy devices. To
avoid hazard of electrical shock, verify that all
voltages on the system bus network have been
discharged before attempting to service, repair or
remove this unit. Only qualified personnel familiar
with solid state control equipment and safety
procedures in publication NFPA 70E or applicable
local codes should attempt this procedure.
Understand IAM/AM The following table provides a brief description of the Kinetix 6000
IAM/AM connectors.
Connectors
Locate IAM Connectors and Use the figure below to locate the Integrated Axis Module connectors
and indicators. Although the physical size of the 2094-BCxx-Mxx
Indicators (460V) IAM is larger than the 2094-ACxx-Mxx (230V) IAM, the location
of the connectors and indicators is identical.
Figure 1.1
Kinetix 6000 Integrated Axis Modules (2094-ACxx-Mxx and -BCxx-Mxx)
1 2
(CPD) Connector CTRL 1
1 2 3 4
DC- Motor Power
1 2 3 4 5 6
W
DC+ (MP) Connector
V
DC Bus / AC Input Power
U
(IPD) Connector L3
1 2 3 4 5 6 7 8 9
MBRK -
L2
1 2 3 4 5 6
MBRK +
L1 COM
Motor/Resistive Brake
PWR (BC) Connector
Contactor Enable CONT EN- DBRK -
1 2
Safe-Off RX TX BAUD
(SO) Connector DPI RATE
Seven Segment
Fault Status LED
Mounting Screw
Note: Power, feedback, and I/O connectors are shown, however for
wiring information, refer to the Kinetix 6000 Multi-Axis Servo
Drive Installation Manual (publication 2094-IN001).
Locate AM Connectors and Use the figure below to locate the Axis Module connectors and
indicators. Although the physical size of the 2094-BMxx (460V) AM is
Indicators larger than the 2094-AMxx (230V) AM, the location of the connectors
and indicators is identical.
Figure 1.2
Kinetix 6000 Axis Modules (2094-AMxx and -BMxx)
1 2 3 4
W Motor Power
V (MP) Connector
U
1 2 3 4 5 6 7 8 9
MBRK - 1 2 3 4 5 6
MBRK +
Safe-Off COM Motor/Resistive Brake
(SO) Connector PWR (BC) Connector
DBRK -
(present only on the 2094-BMxx-S) DBRK +
RX TX
BAUD
RATE
Seven Segment
Fault Status LED
Mounting Screw
Note: Power, feedback, and I/O connectors are shown, however for
wiring information, refer to the Kinetix 6000 Multi-Axis Servo
Drive Installation Manual (publication 2094-IN001).
Understand SM Connectors Use the table below and Figure 1.3 to locate the Shunt Module
connectors and indicators.
Figure 1.3
Kinetix 6000 Shunt Modules (2094-BSP2)
COL
1 2 3
INT
External Shunt Resistor
DC+ (RC) Connector
TS2 External Thermal Switch
1 2
Mounting Screw
Understand LIM Connectors Use the tables below and figures 1.4 and 1.5 to locate the Line
Interface Module connectors.
and Indicators
Use the figure below to locate the Line Interface Module connectors
and indicators.
Figure 1.4
Kinetix 6000 Line Interface Modules (2094-AL09 and -BL02)
1 2
L2/N (CPL) Connector
1
PE PE
1 2 3 4
1 2 3 4
VAC Line
50/60 Hz
50/60 Hz
L3 MBRK PWR L3
VAC Load
4321
(IPL) Connector L2 MBRK COM
MBRK PWR
L2 1
(OPL) Connector
L1 MBRK COM L1 1
Use the figure below to locate the Line Interface Module connectors
and indicators.
Figure 1.5
Kinetix 6000 Line Interface Modules (2094-AL75S, -BL75S, and -XL75S-Cx)
CONTROL VAC
CTRL2
Control Power Output (CPL) Connector
1 2
CTRL1
195-265 VAC LINE, 50/60 Hz
VAC Line
1 2 3 4
AUX2
L3
(IPL) Connector L2
AUX2
230V ac Auxiliary Power Output (P2L) Connector
3
AUX1
AUX1
L1
4
12 3 4 5 6
I/O_COM
195-265 VAC LOAD, 50/60 Hz
24 VDC SUPPLY
I/O_PWR
1
I/O_COM
I/O_PWR 24V dc Brake Power Output (P1L) Connector
VAC Load
2
L3' I/O_COM
L1'
4
I/O Power
Status LED
Main VAC
OFF
CB1
ON
MAIN VAC
CB3 CB2
1 Auxiliary Power Input (APL) connector is only present on the 2094-XL75S-Cx model.
Locate SERCOS Interface Use the figure below to locate the SERCOS interface fiber-optic
connectors. The fiber-optic ring is connected using the SERCOS
Fiber-Optic Connectors Receive and Transmit connectors.
Figure 1.6
ControlLogix and SoftLogix SERCOS Connector Locations
SERCOS interfaceTM
ControlLogix
1756-MxxSE SERCOS
CP OK
interface Module 0
F 1
ABCDE
23 6 7
45
RSLogix 5000 89
SoftLogix
OK 1784-PM16SE SERCOS interface PCI Card
(as viewed from the back of your PC)
CP
TX
SERCOS Transmit Connector, Tx
Tx (rear)
Configure Your Kinetix 6000 These procedures assume you have completed mounting, wiring, and
connecting your SERCOS interface module and Kinetix 6000 drive as
described in the Kinetix 6000 Multi-Axis Servo Drive Installation
Manual (publication 2094-IN001).
These procedures assume you have connected the fiber optic cables
between your IAM (2094-xCxx-Mxx, inverter section), axis modules
(2094-xMxx), and the ControlLogix chassis with 1756-MxxSE interface
module or personal computer with 1784-PM16SE PCI card.
1. Verify that there is no power applied to the IAM and that the
SERCOS fiber-optic cables are plugged into the Tx and Rx
connectors. To verify your fiber-optic cable connections, refer to
the Kinetix 6000 Multi-Axis Servo Drive Installation Manual
(publication 2094-IN001).
2. Set the base node address for the IAM by setting the SERCOS
Node Address switch. Valid node addresses are 01-99. The left
hand switch sets the most significant digit (MSD) and the right
hand switch sets the least significant digit (LSD). Refer to the table
below for switch operation. Refer to for switch location.
To Press
Increment the (MSD/LSD) node address The plus (+) switch.
Decrement the (MSD/LSD) node address The minus (-) switch.
Figure 1.7
Setting the Base Address Switches
MSD LSD
Setting the base node address on the IAM determines the node
address for the IAM inverter. Node addressing for all slot locations
on the same power rail increment (from the IAM inverter) left to
right.
Figure 1.8
Fiber-Optic Ring Connection
0 SoftLogix
ABCDE
3456 72
89 F 1
OK
1784-PM16SE SERCOS
TX
CP
Figure 1.9
Node Addressing Example 1
1756-MxxSE SERCOS
interface Module
SERCOS interfaceTM
CP OK
ControlLogix Chassis
Tx (rear)
Rx (front)
Transmit Receive
Receive Transmit
Kinetix 6000
Receive System 2
Transmit
(2-axis power rail)
Kinetix 6000
System 1
(6-axis power rail)
17 = AM (axis 2) node address
16 = IAM (axis 1) base node address
15 = Slot Filler node address
14 = Shunt Module node address
13 = AM (axis 4) node address
12 = AM (axis 3) node address
11 = AM (axis 2) node address
10 = IAM (axis 1) base node address
Kinetix 6000 (2-axis) System 2 power rail contains one IAM and
one AM. The base node address of the IAM (system 2) must be set
for an address of ≥16 or ≤8.
Figure 1.10
Node Addressing Example 2
1756-MxxSE SERCOS 1756-MxxSE SERCOS
interface Module 1 interface Module 2
SERCOS interfaceTM SERCOS interfaceTM
CP OK CP OK
Transmit Receive
Receive Transmit
Kinetix 6000
(8-axis power rail)
Note: You can mount the two SERCOS interface modules in two
separate ControlLogix chassis (as shown above) or you can
mount them in the same chassis.
Figure 1.11
Node Addressing Example 3
1756-MxxSE SERCOS
interface Module
SERCOS interfaceTM
CP OK
ControlLogix Chassis
Tx (rear)
Rx (front)
Transmit Receive
Receive Transmit
Kinetix 6000
(8-axis power rail)
3. Set the SERCOS baud rate using DIP switches 2 and 3, as shown in
Figure 1.12. Refer to the table below for baud rate switch settings.
4. Set the SERCOS optical power level to High using DIP switch 1, as
shown in Figure 1.12. Refer to the table below for optical power
level switch setting.
Figure 1.12
SERCOS Baud Rate and Optical Power DIP Switches
This procedure assumes you have configured your IAM. Use the
following procedure to configure your axis module(s). In this
procedure you will set the baud rate and optical power level switches
for your IAM and each AM.
1. Verify that there is no power applied to the IAM and that the
SERCOS fiber-optic cables are plugged into the Tx and Rx
connectors. To verify your fiber-optic cable connections, refer to
the Kinetix 6000 Multi-Axis Servo Drive Installation Manual
(publication 2094-IN001).
2. Set the SERCOS baud rate using DIP switches 2 and 3, as shown in
Figure 1.12 (page 1-14). Refer to the table below for the baud rate
switch settings.
3. Set the optical power level to High using DIP switch 1, as shown
in Figure 1.12. Refer to the table below for optical power level
switch setting.
Configure Your Logix This procedure assumes that you have wired your Kinetix 6000 system
and have configured the Kinetix 6000 baud rate and optical power
SERCOS interface Module switches.
Detailed information on configuring and SoftLogix Motion Card Setup and 1784-UM003
troubleshooting your SoftLogix PCI card Configuration Manual
If you have already configured your Logix module using one of the
setup and configuration manuals listed above, go directly to Apply
Power to Your Kinetix 6000 (page 1-26). If not, go to Configure Your
Logix Controller beginning below.
2. Select New in the File menu. The New Controller window opens.
3. Select OK.
7. Select OK.
3. Select OK. The New Module window opens. Your new module
appears under the I/O Configuration folder in the explorer
window.
5. Select the SERCOS Interface tab and reference the table below.
7. Select OK.
1. Right-click on the new Logix module you just created and select
New Module. The Select Module window opens.
4. Select OK.
6. Select the New Axis button. The New Tag window opens.
7. Select OK. The axis appears under the Ungrouped Axes folder in
the explorer window.
8. Assign your axis to the node address (as shown in the window
below).
With drive firmware version 1.80 (or above) and RSLogix 5000
software version 13 (or above), it is possible to configure the
auxiliary axis feedback port as a Feedback Only axis. With this
feature, each IAM (inverter) or AM can be configured to appear as
two axes/nodes on the SERCOS ring. The base node is the servo
axis utilizing the motor feedback, and the base node (plus 128) is
a feedback only axis utilizing the auxiliary feedback port (as
shown below).
9. Select OK.
13. Repeat steps 1-9 for each 2094-xMxx Axis Module (AM).
3. Select OK. New group appears under the Motion Groups folder.
5. Select the Axis Assignment tab and move your axes (created
earlier) from Unassigned to Assigned.
6. Select the Attribute tab and edit the default values as appropriate
for your application.
7. Select OK.
3. Select the Motor Feedback tab and verify the Feedback Type
shown is appropriate for your actual hardware configuration.
4. Select the Units tab and edit default values as appropriate for your
application.
6. Select the Fault Actions tab and click on the Set Custom Stop
Action... tab. The Custom Stop Action Attributes window opens.
7. Select OK.
Apply Power to Your Use the table below to determine where to begin applying power to
your Kinetix 6000.
Kinetix 6000
If your Kinetix 6000 system Then
Go to Apply Power to Your Kinetix 6000 (with
Includes a (2094-xLxx or -xLxxS-xx) LIM LIM)
Does not include a (2094-xLxx or -xLxxS-xx) LIM Go to Apply Power to Your Kinetix 6000 (without
LIM)
This procedure assumes that you have wired and configured your
Kinetix 6000 (including the LIM) and your SERCOS interface module.
1. Ensure CB1, CB2, and CB3 on the LIM are in the OFF position
(refer to figures 1.4 and 1.5 for the location of the CB1, CB2, and
CB3).
ATTENTION
To avoid personal injury or damage to
equipment, disconnect the load to the motor(s).
Ensure each motor is free of all linkages when
initially applying power to the system.
5. Observe the Brake Power Status LED on the LIM (2094-xLxx only).
Refer to Figure 1.4 for the location of the Brake Power Status LED.
6. Observe the I/O Power Status LED on the LIM. Refer to Figure 1.4
(2094-xLxx) or Figure 1.5 (2094-xLxxS-xx) for the location of the
I/O Power Status LED.
9. Verify the Hardware Enable Input signal (IOD pin 2) for each axis
is at 0 volts.
10. Observe the IAM/AM front panel logic power LED as shown in the
figure below.
Figure 1.13
Logic Power and Status LED Display
11. Observe the IAM/AM front panel seven segment status LED
display as shown in Figure 1.13.
Note: The seven segment LED will first flash the SERCOS node
address, then cycle through phases until final configuration
(phase 4) is reached.
If Is Status Do This
The drive is looking for a closed SERCOS
Actively cycling Check fiber-optic
ring. Wait for phase 1 or take corrective
(phase 0) connections.
action until you reach phase 1.
Displaying a fixed 1 The drive is looking for active nodes. Check node
Wait for phase 2 or take corrective action
(phase 1) addressing.
until you reach phase 2.
Check program
The seven segment Displaying a fixed 2 The drive is configuring nodes for motor and drive
status LED on your (phase 2) communication. Wait for phase 3 or take configuration
2094-xCxx-Mxx IAM corrective action until you reach phase 3. against installed
or hardware.
2094-xMxx AM
Displaying a fixed 3 The drive is configuring device specific Check motor
parameters. Wait for phase 4 or take catalog number
(phase 3)
corrective action until you reach phase 4. against selection.1
Displaying a fixed 4
The drive is configured and active. Go to step 12.
(phase 4)
Flashing an E Go to Error Codes
followed by two Drive is faulted.
on page 2-3.
numbers
1 You can get diagnostic information from the module by highlighting the module name in RSLogix 5000. A Pseudo
Key Failure often indicates that the motor selection does not match the motor installed.
This procedure assumes that you have wired and configured your
Kinetix 6000 and SERCOS interface module.
Figure 1.14
Logic Power and Status LED Display
Note: The seven segment LED will first flash the SERCOS node
address, then cycle through phases until final configuration
(phase 4) is reached.
If Is Status Do This
The drive is looking for a closed SERCOS
Actively cycling Check fiber-optic
ring. Wait for phase 1 or take corrective
(phase 0) action until you reach phase 1. connections.
Flashing an E
Go to Error Codes
followed by two Drive is faulted
on page 2-3.
numbers
1
You can get diagnostic information from the module by highlighting the module name in RSLogix 5000. A Pseudo
Key Failure often indicates that the motor selection does not match the motor installed.
Test and Tune Your Axes This procedure assumes that you have configured your Kinetix 6000,
your SERCOS interface module, and applied power to the system.
Detailed information on configuring and SoftLogix Motion Card Setup and 1784-UM003
troubleshooting your SoftLogix PCI card Configuration Manual
If you have already tested and tuned your Logix module using one of
the setup and configuration manuals listed above, you are finished
commissioning your Kinetix 6000 system. If not, go to Test Your Axes
beginning below.
4. Select 2.0 as the number of revolutions for the test (or another
number more appropriate for your application).
5. Apply Hardware Enable Input signal (IOD-2) for the axis you are
testing.
7. Select OK.
9. Select OK.
If Then
Your test completes successfully, this window 1. Select OK.
appears:
2. Remove Hardware Enable Input
signal (IOD-2).
3. Go to Tune Your Axes.
1. Select OK.
Your test failed, this widow appears: 2. Verify the Bus Status LED turned
solid green during the test.
3. Verify that the Hardware Enable
Input signal (IOD-2) is applied to
the axis you are testing.
4. Verify conversion constant entered
in the Conversion tab.
5. Return to step 6 and run the test
again.
1. Verify the load is still removed from the axis being tuned.
ATTENTION
To reduce the possibility of unpredictable motor
response, tune your motor with the load
removed first, then re-attach the load and
perform the tuning procedure again to provide
an accurate operational response.
3. Enter values for Travel Limit and Speed. In this example, Travel
Limit = 5 and Speed = 10.
Note: Actual value of programmed units depend on your
application.
6. Apply Hardware Enable Input signal (IOD-2) for the axis you are
tuning.
ATTENTION
To avoid personal injury or damage to
equipment, apply 24V ENABLE signal (IOD-2)
only to the axis you are tuning.
7. Select the Start Tuning button to auto-tune your axis. The Online
Command - Tune Servo window opens. When the test completes,
the Command Status changes from Executing to Command
Complete.
9. Select OK.
10. The Online Command - Apply Tune window opens. When the test
completes, the Command Status changes from Executing to
Command Complete.
If Then
Your test completes successfully, this window 1. Select OK.
appears:
2. Remove the Hardware Enable
Input signal (IOD-2) applied
earlier.
3. Go to step 12.
1. Select OK.
Your test failed, this widow appears:
2. Make an adjustment to motor
velocity.
3. Refer to appropriate Logix motion
module setup and configuration
manual for more information.
4. Return to step 7 and run the test
again.
12. Repeat Test and Tune Your Axes for each axis.
• Safety Precautions
• General Troubleshooting
• Troubleshoot IAM/AM Status LEDs
• Troubleshoot SM Status LEDs
• Troubleshoot LIM Status LEDs
• Troubleshoot RBM Status LEDs
• Troubleshoot General System Problems
• Understand Logix/Drive Fault Behavior
• Supplemental Troubleshooting Information
• Replace Kinetix 6000 System Components
Safety Precautions Observe the following safety precautions when troubleshooting your
Kinetix 6000 drive.
ATTENTION
DC bus capacitors may retain hazardous voltages
after input power has been removed, but will
normally discharge in several seconds. Before
working on the drive, measure the DC bus voltage to
verify it has reached a safe level or wait the full time
interval listed on the warning on the front of the
drive. Failure to observe this precaution could result
in severe bodily injury or loss of life.
Do not attempt to defeat or override the drive fault
circuits. You must determine the cause of a fault and
correct it before you attempt to operate the system. If
you do not correct a drive or system malfunction, it
could result in personal injury and/or damage to
equipment as a result of uncontrolled machine
system operation.
If you use an oscilloscope (or chart recorder) for
troubleshooting, you must properly ground it. The
oscilloscope chassis can be at a potentially fatal
voltage if you do not properly ground it. Always
connect the oscilloscope chassis to an earth ground.
General Troubleshooting Refer to the Error Codes section to identify problems, potential causes,
and appropriate actions to resolve the problems. If problems persist
after attempting to troubleshoot the system, please contact your
Allen-Bradley representative for further assistance. To determine if
your Kinetix 6000 drive has an error, refer to the table below.
Error Codes
OverSpeedFault Motor speed has exceeded 150% of maximum rated speed. The 100% • Check cables for noise.
E18 trip point is dictated by the lesser of the user velocity limits or the
(Overspeed Fault) motor rated base speed. • Check tuning.
SERCOSFault The SERCOS ring is not Check that fiber-optic cable is present and
E38 active after being active Cable disconnected. connected properly.
(SERCOS Ring Flt) and operational.
• Verify that there are no impediments to
motion at startup, such as hard limits.
E39
DriveHardFault Self-sensing Commutation Motion required for self-sensing startup • Increase self-sensing current if high
(Self Sense Flt) Startup Error commutation was obstructed. friction or load conditions exist.
• Check motor or encoder wiring using
wiring diagnostics.
• An attempt was made to enable the • Disable the Drive Enable Input fault.
axis through software while the Drive
DriveEnableInput Enable hardware input was inactive. • Verify that Drive Enable hardware input
E43 Fault Missing Drive Enable Input is active whenever the drive is enabled
Signal • The Drive Enable input transitioned through software.
(Drive Enable Flt)
from active to inactive while the axis
was enabled.
DriveHardFault For symptom, cause, and resolution of this error code, refer to the Kinetix Safe-Off Feature Safety Reference Manual
E49 (publication GMC-RM002). Applies to IAM (2094-xCxx-Mxx-S) and AM (2094-xMxx-S) with Safe-Off feature.
(Safe-Off HW Flt)
SERCOSFault Verify that each SERCOS drive is assigned
E50 Duplicate node address detected on SERCOS ring.
(SERCOS Same ADDR) a unique node address.
DriveHardFault
E54 Current feedback hardware fault detected. Replace the module
(Ifbk HW Fault)
DriveHardFault
E60 Illegal ID bits detected Replace the module
(Unknown Axis)
• Use shielded cables with twisted pair
wires.
AuxFeedbackFault Auxiliary Encoder State The auxiliary encoder encountered an • Route the feedback away from
E61 potential noise sources.
(Aux Fdbk AQB) Error illegal transition.
• Check the system grounds.
• Replace the motor/encoder.
The airflow access to the Kinetix 6000 is Check airflow and re-route cables away
limited or blocked. from the Kinetix 6000.
Power rail CAN communications failed. Check module for proper mount.
Communicate
E73 Check power rail and module for foreign
(Backplane Comm) Power rail connection shorted or open. objects.
• Check for proper motor sizing.
Steady Red Drive faulted Seven-segment LED displays error code Refer to the section Error Codes and continue
troubleshooting.
Use the table below for troubleshooting the Bus Status LED on your
Kinetix 6000 IAM (2094-xCxx-Mxx) or AM (2094-xMxx).
Troubleshoot SM Status Each of the shunt module LEDs provide specific troubleshooting
information, as described in Bus Status LED, Temperature Fault LED,
LEDs and Shunt Fault LED.
The following table applies when all three SM LEDs are flashing.
Use the table below for troubleshooting the Bus Status LED on your
Kinetix 6000 SM (2094-BSP2).
Flashing Normal condition when control power is applied and bus voltage is less than N/A
60V dc.
Normal condition when control power is applied and bus voltage is greater
Steady Green than 60V dc. N/A
Off Control power is not present Internal power supply failure Replace shunt module.
Use the table below for troubleshooting the Temperature Fault LED on
your Kinetix 6000 SM (2094-BSP2).
Use the table below for troubleshooting the Shunt Fault LED on your
Kinetix 6000 SM (2094-BSP2).
Troubleshoot LIM Status The following troubleshooting table applies to the following Line
Interface Module status LEDs:
LEDs
• 24V Power status LED (2094-AL75S, -BL75S, and -XL75S-Cx)
• Brake Power status LED (2094-AL09 and -BL02)
• I/O Power status LED (2094-AL09 and -BL02)
Troubleshoot RBM Status The Resistive Brake Module (RBM) contactor status LED is visible from
the front of the RBM. Use the table below for troubleshooting the
LEDs RBM status LEDs.
If the Status LED is RBM Contactor Status is Potential Cause is Possible Resolution is
Contactor engaged
(direct connection between drive and No faults or failures N/A
motor)
Steady Green
Contactor disengaged • Monitor CONSTAT_41/42 status to verify lack of
(no connection between drive and Contactor failure drive/motor power (output is NC).
motor) • Contact A-B representative.
• Verify ground wiring.
Recommended grounding • Route wires away from noise sources.
not followed
Blinking Green Contactor rapidly engaging/ • Refer to System Design for Control of Electrical Noise
(audible clicking) disengaging Reference Manual (publication GMC-RM001).
Control circuit improperly Verify control wiring and programming.
wired
Off No faults or failures N/A
(intended)
• +24V supply is off.
Contactor disengaged
(connection open between drive and +24V not applied between • Verify wiring.
Off motor) COIL_A1 and COIL_A2 • Drive not enabled.
(unintended)
• Contact A-B representative.
T1 (Fault) thermostat open Duty cycle exceeded, allow RBM to cool.
Troubleshoot General Use the tables below for troubleshooting general system faults. For a
list of Bulletin 1756 product manuals, refer to Related Documentation
System Problems in the Preface.
Motor Select limit is incorrectly set (servo motor is not matched • Check setups.
to axis module). • Run Tune in RSLogix 5000.
Notch filter or output filter may be required
Mechanical resonance (refer to Axis Properties window, Output tab
in RSLogix 5000).
Torque Limit limits are set too low. Verify that current limits are set properly.
Select the correct motor and run Tune in
Incorrect motor selected in configuration. RSLogix 5000 again.
• Check motor size vs. application need.
The system inertia is excessive.
• Review servo system sizing.
You cannot obtain the motor
acceleration/deceleration The system friction torque is excessive. Check motor size vs. application need.
that you want • Check motor size vs. application need.
Available current is insufficient to supply the correct accel/decel
rate. • Review servo system sizing.
Verify limit settings and correct them, as
Acceleration limit is incorrect. necessary.
Verify limit settings and correct them, as
Velocity Limit limits are incorrect. necessary.
The axis cannot be enabled for 1.5 seconds after disabling. Disable the axis, wait for 1.5 seconds, and
enable the axis.
Enable signal has not been applied or the enable wiring is • Check the controller.
incorrect. • Check the wiring.
The motor wiring is open. Check the wiring.
The motor connections are loose or open. Check motor wiring and connections.
Foreign matter is lodged in the motor. Remove foreign matter.
The motor load is excessive. Verify the servo system sizing.
No Rotation The bearings are worn. Return the motor for repair.
• Check brake wiring and function.
The motor brake is engaged (if supplied).
• Return the motor for repair.
The motor is not connect to the load. Check coupling.
Change the command profile to reduce accel/
The duty cycle is excessive. decel or increase time.
Motor Overheating
The rotor is partially demagnetized causing excessive motor Return the motor for repair.
current.
Motor tuning limits are set too high. Run Tune in RSLogix 5000 again.
• Remove the loose parts.
Loose parts are present in the motor. • Return motor for repair.
• Replace motor.
Abnormal Noise
Through bolts or coupling is loose. Tighten bolts.
The bearings are worn. Return motor for repair.
Notch filter may be required (refer to Axis
Mechanical resonance Properties window, Output tab in RSLogix
5000).
Motor power phases U and V, U and W, or V and W reversed. Check and correct motor power wiring.
Erratic Operation - Motor
locks into position, runs Sine, Cosine or Rotor leads are reversed in the feedback cable
without control or with connector. Check and correct motor feedback wiring.
reduced torque
Sine, Cosine, Rotor lead sets of resolver feedback are reversed. Check and correct motor feedback wiring.
Understand Logix/Drive This section provides the drive fault actions and indicates whether the
fault action is programmable.
Fault Behavior
The following drive fault action definitions apply:
Shutdown The drive disables and the contactor enable relay opens. Uncontrolled
stop, motor coasts to a stop.
Disable Drive The drive is disabled. Uncontrolled Stop, motor coasts to a stop.
Logix configuration for velocity loop Kp/Ki is followed. When zero speed is
reached or stopping time is exceeded, the drive is disabled.
Stop Motion
Note: Stopping time and stopping torque are configurable parameters in
RSLogix 5000.
Status Only Drive continues to operate. Status is provided by 7-Segment Fault Status
LED, Drive Status LED, and DPI (if used).
RSLogix
Fault Message RSLogix Error Description Drive Fault Programmable
(HIM) Code Action Fault Action?
BusUndervoltageFault
E00 A blown fuse was detected in the inverter pcb. SHUTDOWN N
(Blown fuse)
The motor thermal switch was tripped.
MotorOvertempFault Note: Firmware I2t protection does not generate a fault, rather it
E04 dynamically folds back current when 110% of motor rating is STOP Y
(Motor Overtemp)
reached. Setting the Motor Thermal fault action to Status Only
will bypass this function.
DriveOvercurrentFault An instantaneous over-current was detected in the inverter power
E05 section. SHUTDOWN N
(Power Fault)
HardOvertravelFault Axis moved beyond the physical travel limits in the positive/negative
E06 direction. This fault can be configured for status only. STOP Y
(+/- Hard Overtravel)
MotFeedbackFault
E07 The feedback wiring is open, shorted or missing. DISABLE N
(Motor Feedback Loss)
With 3 phase present, the DC bus voltage is below limits. The trip
BusUndervoltageFault point is 275V and 137V DC for 460V/230V drives respectively.
E09 SHUTDOWN N
(Bus Under Voltage) DC bus voltage is below limits when any axis on common bus
follower power rail was enabled.
DriveOvervoltageFault The DC bus voltage is above limits. The trip point is 820V and 410V
E10 DC for 460V/230V drives respectively. SHUTDOWN N
(Bus Overvoltage)
MotFeedbackFault
E11 State of Hall feedback inputs in incorrect. DISABLE N
(Illegal Hall State)
SoftovertravelFault Axis position exceeded maximum software setting in the positive/
E16 negative direction. This fault can be configured for status only. STOP Y
(+/- Software Overtravel)
OverSpeedFault Axis speed has reached 150% of the maximum rated setting. The
E18 100% trip point is dictated by the lesser of the user velocity limits or DISABLE N
(Overspeed Fault) the motor rated base speed.
PositionErrorFault Axis position error limit has been exceeded. This fault can be
E19 configured for status only. STOP Y
(Follow Error)
RSLogix
Fault Message RSLogix Error Description Drive Fault Programmable
(HIM) Code Action Fault Action?
MotFeedbackFault
E20 Motor encoder has encountered an illegal state transition. DISABLE N
(Mtr Fdbk AQB)
AuxFeedbackFault Communication was not established with an intelligent (i.e.
E21 STOP N
(Aux Feedback Comm) Stegmann) encoder on the Auxiliary feedback port.
GroundShortFault
E34 Excessive ground current in the converter was detected. SHUTDOWN N
(Ground Fault)
DriveUndervoltageFault
E35 The converter pre-charge cycle has failed. SHUTDOWN N
(Precharge Fault)
DriveOvertempFault
E36 Converter internal temperature limit exceeded. SHUTDOWN N
(System Overtemperature)
• One or more phases of the input AC power is missing.
PowerPhaseLossFault • Axis was enabled when main (3-phase) power was removed.
E37 SHUTDOWN/ STOP N
(Phase Loss Flt) • Common bus follower axis was enabled when DC bus power was
removed.
SERCOSFault
E38 The SERCOS ring is not active after being active and operational. STOP N
(SERCOS Ring Flt)
DriveHardFault
E39 Self-sensing commutation fault detected DISABLE N
(Self Sense Flt)
DriveEnableInputFault
E43 Generated when Enable input switches off when drive is enabled. STOP Y
(Drive Enable Flt)
Safe-off function mismatch. Drive will not allow motion. Refer to the
DriveHardFault Kinetix Safe-Off Feature Safety Reference Manual (publication
E49 GMC-RM002) for more information. Applies to IAM SHUTDOWN N
(Safe-Off HW Flt)
(2094-xCxx-Mxx-S) and AM (2094-xMxx-S) with Safe-Off feature.
SERCOSFault
E50 Duplicate node address detected on SERCOS ring. STOP N
(SERCOS Same ADDR)
DriveHardFault
E54 Current feedback hardware fault detected. SHUTDOWN N
(Ifbk HW Fault)
DriveHardFault
E60 Invalid module type identified by firmware during power on SHUTDOWN N
(Unknown Axis)
AuxFeedbackFault
E61 Auxiliary encoder has encountered an illegal state transition. DISABLE N
(Aux Fdbk AQB)
AuxFeedbackFault
E62 The feedback wiring is open, shorted or missing. DISABLE N
(Aux Fdbk Loss)
AuxFeedbackNoise
E63 Presence of noise on auxiliary feedback cable.
(Aux Fdbk Noise)
DISABLE Y
MotorFeedbackNoise
E64 Presence of noise on motor feedback cable.
(Mtr Fdbk Noise)
No Fault Message
(condition indicated by
on-screen message) E65 Hookup procedure failed DISABLE N
(Hookup Fault)
RSLogix
Fault Message RSLogix Error Description Drive Fault Programmable
(HIM) Code Action Fault Action?
No Fault Message
(condition indicated by
on-screen message) E66 Autotune procedure failed DISABLE N
(Atune Flt)
DriveHardFault
E67 Operating System Failed SHUTDOWN N
(Task init)
DriveHardFault
E68 DPI Communication Failed STOP N
(SCANport Comm)
DriveHardFault
E69 Non-Volatile Memory attribute out of range SHUTDOWN N
(Objects Init)
DriveHardFault
E70 Non-Volatile Memory Corrupted SHUTDOWN N
(NV Mem Init)
DriveHardFault
E71 RAM or Flash memory validation failure. SHUTDOWN N
(Memory Init)
Inverter temperature limit exceeded.
DriveOvertempFault
E72 Note: Firmware I2t protection does not generate a fault, rather it SHUTDOWN Y
(Drive Overtemp) dynamically folds back current when 110% of drive rating is
reached.
Communicate
E73 Power Rail Backplane CAN communications failed STOP N
(Backplane Comm)
DriveOvercurrentFault
E74 The converter has exceeded its converter rating. SHUTDOWN N
(Bus OverCurrent)
The IAM, AM, or SM has exceeded its shunt resistor continuous
DriveOvervoltageFault rating.
E75 SHUTDOWN N
(Shunt Time Out) Note: SHUTDOWN for IAM, DISABLE for AM. IAM also provides
fault handling for Shunt Module.
DriveHardFault
E76 Either DPI or Backplane CAN initialization failure SHUTDOWN N
(Can Init)
DriveHardFault Generated by IAM if the power rating of one of the AM’s on the
E77 power rail does not match with IAM input power rating SHUTDOWN N
(Module Mismatch)
DriveHardFault
E78 Control hardware fault detected SHUTDOWN N
SERCOS Init
DriveOvervoltageFault Power Rail mounted Shunt Module Fault. Displayed on IAM
E79 7-segment fault status LED. SHUTDOWN N
(Shunt Module Flt)
HardwareFault
E80 Control hardware fault detected SHUTDOWN N
(CPLD FLT)
HardwareFault
E81 Common Bus Follower IAM detected AC input power being applied. SHUTDOWN N
(Common Bus FLT)
HardwareFault
E90 Pre-charge resistor power exceeds the resistor rating. SHUTDOWN N
(Pre-charge Timeout FLT)
All
RESERVED Others
Figure 2.1
DriveExplorer Example
When using the HIM to monitor or change parameters, use the up and
down arrows (∧ and ∨ ) to arrive at selections. Refer to the
instructions that came with your HIM for more information.
4. Press Sel.
There are two analog output test points accessible from the IOD
26-pin connector on each IAM and AM (refer to figures and 1.2 for
connector locations).
Figure 2.2
Pin Orientation for 26-pin I/O (IOD) Connector
26-pin IAM/AM
I/O Connector
Pin 18
Pin 9
Pin 26
Pin 19 Pin 1
Pin 10
Use the two analog output test points to monitor system variables, as
shown in the table below.
The value entered in Scale Parameter will scale the analog output so
that you can get a full scale reading of the specific parameter for the
dynamic range or values you are testing.
ATTENTION
This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. You are required to
follow static control precautions when you install,
test, service, or repair this assembly. If you do not
follow ESD control procedures, components can be
damaged. If you are not familiar with static control
procedures, refer to Allen-Bradley publication
8000-4.5.2, Guarding Against Electrostatic Damage
or any other applicable ESD Protection Handbook.
Remove Modules from the To remove module(s) from the power rail:
Power Rail 1. Verify that all control and input power has been removed from the
system.
ATTENTION
This product contains stored energy devices. To
avoid hazard of electrical shock, verify that all
voltage on capacitors has been discharged before
attempting to service, repair, or remove this unit.
You should only attempt the procedures in this
document if you are qualified to do so and are
familiar with solid-state control equipment and
the safety procedures in publication NFPA 70E.
3. Label and remove all connectors from the module (IAM, AM, or
SM) you are removing. To identify each connector, refer to
Commission Your Kinetix 6000 (pages 1-3 to 1-5).
Note: The Slot Filler module has no connectors aside from the
connections to the power rail.
4. Remove the motor cable from the cable shield clamp, as shown in
the figure below.
Figure 2.3
Depressing the Spring Clamp
Cable Clamp
Cable Clamp
6. Grasp top and bottom of the module with both hands and gently
pull the module away from the connectors enough to clear the
guide pin(s) (module will pivot on top bracket). Lift the bracket
out of the power rail slot and remove module from the power rail.
Figure 2.4
Removing Module from Power Rail
Guide Pin(s)
3. Hang the mounting bracket from the slot on the power rail.
4. Align the guide pin(s) on the power rail with the guide pin hole(s)
in the back of the module (refer to Figure 2.4).
Note: The IAM can have two or three power rail connectors and
guide pins, the AM can have one or two, all other modules
have only one connector and one guide pin.
5. Use 2.26 N-m (20 lb-in.) torque to tighten the mounting screw.
Remove the Power Rail This procedure assumes you have disconnected all power from the
power rail modules and removed all modules from the power rail.
Figure 2.5
Removing Ground Strap (2094-PRx)
Braided Ground Strap
100 mm (3.9 in.)
Bonded Cabinet Ground
Figure 2.6
Removing Ground Strap (2094-PRSx)
Replace the Power Rail This procedure assumes you do not need to change the location of
the power rail on the panel and you intend to reuse the mounting
bolts of the power rail you just removed.
1. Align the replacement power rail over the existing mounting bolts.
Remove the Line Interface To remove the Line Interface Module (LIM):
Module 1. Verify that all input power has been removed from the LIM.
ATTENTION
To avoid shock hazard or personal injury, assure
that all power has been removed before
proceeding. This system may have multiple
sources of power. More than one disconnect
switch may be required to de-energize the
system.
3. Label and remove all connectors and wires from the LIM. To
identify each connector, refer to page 1-6.
Replace the Line Interface This procedure assumes you do not need to change the location of
the LIM on the panel and you intend to reuse the mounting bolts of
Module the LIM you just removed.
Interconnect Diagrams
Kinetix 6000 Interconnect This section provides interconnect diagram notes to assist you in
wiring the Kinetix 6000 system. The notes apply to the interconnect
Diagram Notes diagrams on the pages that follow.
ATTENTION
The National Electrical Code and local electrical
codes take precedence over the values and methods
provided. Implementation of these codes is the
responsibility of the machine builder.
Note Information
1 For power wiring specifications, refer to Kinetix 6000 Installation Manual (publication 2094-IN001).
2 For input fuse and circuit breaker sizes, refer to Kinetix 6000 Installation Manual (publication 2094-IN001).
3 For AC line filter specifications, refer to Kinetix 6000 Installation Manual (publication 2094-IN001).
4 Terminal block is required to make connections.
5 2094-BCxx-Mxx (460V) IAM requires step down transformer for single-phase control power input. Source 2094-ACxx-Mxx (230V) IAM control
power from the three-phase input power (line-to-line). Supplying 230V control power from any other source requires an isolation transformer. If
used, do not ground either leg of the isolation transformer output.
6 LIM models 2094-AL75S and -BL75S can supply a maximum of eight axes. LIM models 2094-XL75S-Cx can supply a maximum of sixteen axes. For
common bus systems with more than sixteen axes, multiple LIMs (or control power transformers) are required.
7 Contactor coil (M1) needs integrated surge suppressors for AC coil operation.
8 Drive Enable input must be opened when main power is removed, or a drive fault will occur. A delay of at least 1.0 second must be observed
before attempting to enable the drive after main power is restored.
9 Cable shield clamp must be used in order to meet CE requirements. No external connection to ground required.
10 Jumper is factory set, indicating grounded system at user site. Ungrounded sites must jumper the bleeder resistor to prevent high electrostatic
buildup. Refer to Kinetix 6000 Installation Manual (publication 2094-IN001) for more information.
11 Implementation of safety circuits and risk assessment is the responsibility of the
ATTENTION
machine builder. Please reference international standards EN 1050 and EN 954
estimation and safety performance categories. For more information refer to
Understanding the Machinery Directive (publication SHB-900).
12 Wiring the Contactor Enable relay is required. To avoid injury or damage to the
ATTENTION
drive, wire the Contactor Enable relay into your safety control string. The
recommended minimum wire size for wiring the safety circuit to the contactor
enable connector is 1.5 mm2 (16 AWG).
13 The Kinetix 6000 axis module referenced is either an individual axis module (2094-xMxx) or the same axis module that resides within an
integrated axis module (2094-xCxx-Mxx).
14 For motor cable specifications, refer to the Kinetix Motion Control Selection Guide (publication GMC-SG001).
15 Wire colors are for flying lead cable (2090-XXNFxx-Sxx) and may vary from the premolded connector cable (2090-UXNFBxx-Sxx).
16 Y-Series feedback cables have a drain wire that must be folded back under the Low Profile connector clamp.
17 Only the MPG-Bxxx encoder uses the +5V dc supply. MPL-Bxxx encoders use the +9V dc supply.
18 Brake wires on MPF/MPS-A/B5xx motors are labeled plus (+) and minus (-). All other MP-Series Food Grade and Stainless Steel motor brake
wires are labeled F and G.
19 Refer to Kinetix 6000 Installation Manual (publication 2094-IN001) for input fuse specifications. Current requirements are for master only shunt
applications. For master/slave applications you must multiply the current requirement by the number of shunt units.
20 Refer to Kinetix 6000 Installation Manual (publication 2094-IN001) for fault relay specifications. This normally closed contact (TTL compatible) is
closed when 115V ac is applied and opens when a shunt fault or loss of power occurs.
Power Interconnect The interconnect wiring for an IAM is shown beginning below.
Diagrams In the configuration below the IAM has input power, brake power,
and the start/stop string wired from a LIM (2094-AL09 or -BL02). The
2094-xLxx LIM contains an AC line filter, so an external filter is not
required.
Figure A.1
IAM Power Interconnect Diagram (IAM with LIM)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
Power Rail
Bonded Cabinet Ground Stud
Ground Bus*
Note 9
1
MBRK_PWR
2
24V dc Output MBRK_COM
3
(PSL) Connector MBRK_PWR
4 6
MBRK_COM BR-
MBRK - Motor Brake
5 BR+ Connections
MBRK +
4
COM
24-26 Motor/Resistive 3
IO_PWR Brake (BC) Connector PWR
2 BR-
I/O (IOL) STOP * DBRK - Resistive Brake
Connector 1 BR+
13 DBRK + Connections
Note 11, 12 COIL_A1
20-22 1
IO_COM CONT EN- Contactor Enable
4 2 (CED) Connector
COIL_A2 CONT EN+
Note 12
* INDICATES USER SUPPLIED COMPONENT
In the configuration below two IAMs have input power, brake power,
and the start/stop string wired from the same LIM (2094-AL75S,
-BL75S, or -XL75S-Cx). The 2094-xL75S-xx LIM does not contain an AC
line filter, so an external filter is added between the LIM and IAM.
Figure A.2
IAM Power Interconnect Diagram (IAM with LIM)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
(IAM_1)
Kinetix 6000 4
LINE INTERFACE MODULE 3 Three-Phase
Motor Power W Motor Power
2094-AL75S, -BL75S, or -XL75S-Cx (MP) Connector 2 Connections
V
1 Note 14
Note 4 1 U
Control Power CTRL 2 1 CTRL 2 Control Power
Single-Phase (CPL) Output 2 2 (CPD) Connector
195-264V ac RMS CTRL 1 CTRL 1
Note 1
To CPD connector,
IAM_2
Note 6
1
DC-
2 DC Bus
DC+ and
1 1 Note 4 3
VAC LOAD 3-Phase
VAC LINE 2 3-Phase (OPL) Output 2 Three-Phase 4 Input (IPD)
L3 L3' L3
3-Phase (IPL) Input 3 195-264V ac RMS 3 AC Line Filter 5 Connector
195-264V ac RMS L2 or 324-528V ac RMS L2' Note 3 L2
4 4 6
or 324-528V ac RMS L1 Note 1 L1' L1
Note 1
To IPD connector,
IAM_2
Auxiliary Power 1
L1
Single-Phase (APL) Input 2
93-121V ac RMS L2/N 1
IO_PWR2
or 196-253V ac RMS 2 To BC connector, IAM_2
(This connector is present IO_COM2
only on the 2094-XL75S-Cx) 3
24V dc (P1L) Output IO_PWR2
Note 1 4
IO_COM2
5
IO_PWR2
6
IO_COM2 Motor Brake
Connections
6 BR-
MBRK -
5 BR+
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2 BR-
1, 3, 5 DBRK -
IO_PWR1
1 BR+
DBRK +
I/O (IOL) STOP *
Connector Resistive Brake
7 Connections
Note 11, 12 COIL_E1
2, 4, 6 1
IO_COM1 CONT EN- Contactor Enable
8 2 (CED) Connector
COIL_E2 CONT EN+
Note 12
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
(IAM_2)
4
Three-Phase
3 Motor Power
Motor Power W
(MP) Connector 2 Connections
V Note 14
1
1 U
CTRL 2 Control Power
From CPL connector, LIM 2 (CPD) Connector
CTRL 1
1
DC-
2 DC Bus
DC+ and
3
3-Phase
Three-Phase 4 Input (IPD)
L3
From OPL connector, LIM AC Line Filter 5 Connector
Note 3 L2
6
L1
6 BR-
MBRK - Motor Brake
5 BR+ Connections
MBRK +
4
COM
Motor/Resistive 3 From P1L connector, LIM
Brake (BC) Connector PWR
2 BR-
DBRK - Resistive Brake
1 BR+
DBRK + Connections
1
From IOL connector, LIM CONT EN- Contactor Enable
2 (CED) Connector
and CED connector, IAM_1 CONT EN+
Note 12
The configuration on this page does not include a LIM. You must
supply input power components. The diagram below is preferred
because one three-phase line filter is utilized by both control power
and main input power connections. The three-phase line filter is wired
upstream of fusing and the M1 contactor.
Figure A.3
IAM Power Interconnect Diagram (IAM without LIM - Preferred)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
The configuration on this page does not include a LIM. You must
supply input power components. The diagram below is not preferred
because two line filters are required. The single-phase and
three-phase line filters are wired downstream of fusing and the M1
contactor.
Figure A.4
IAM Power Interconnect Diagram (IAM without LIM - Alternate)
Kinetix 6000
INTEGRATED AXIS MODULE
2094-ACxx-Mxx or -BCxx-Mxx
1 Note 9
Single-Phase CTRL 2 Control Power
Single-Phase Input
AC Line Filter 2 Cable Shield
95-264V ac RMS CTRL 1 (CPD) Connector
Note 3 Clamp
Notes 1, 2
Input Fusing *
Isolation 4
Transformer * Three-Phase
3
Note 5 Motor Power W Motor Power
(MP) Connector 2 Connections
V
1 1 Note 14
DC- U
2 DC Bus
DC+
Note 4 3 and
3-Phase
Three-Phase Input Three-Phase 4 Input (IPD)
L3
195-264V ac RMS AC Line Filter 5 Connector 6
L2 BR-
or 324-528V ac RMS Note 3 MBRK - Motor Brake
6 5
Notes 1, 2 L1 BR+ Connections
MBRK +
Input Fusing * M1 * 4
Motor/Resistive COM User Supplied
Notes 7, 8 3
Brake (BC) Connector 24V dc (1.2A maximum)
PWR
2 BR-
DBRK - Resistive Brake
1 BR+ Connections
Notes 7, 12 1 DBRK +
CONT EN- Contactor Enable
2 (CED) Connector
CONT EN+
STOP * START * Note 12
24V ac/dc CR1 *
or
120V ac
50/60 Hz M1 * CR1 * Ground Jumper
Note 10
CR1 *
* INDICATES USER SUPPLIED COMPONENT
Refer to Attention statement (Note 11)
Kinetix 6000
COMMON BUS FOLLOWER IAM
Bonded Cabinet 2094-ACxx-Mxx or -BCxx-Mxx
Ground Bus*
DC Common Bus
Ground Bus*
Power Rail 1
Interconnect Diagrams
1
CONT EN- Contactor Enable * INDICATES USER SUPPLIED COMPONENT
2 (CED) Connector
CONT EN+
Note 12
CR1*
Kinetix 6000 (460V) Follower IAM are shown.
IMPORTANT Use a push-button circuit (instead of a SPST toggle switch) in series with the contactor enable string
(between the 8720MC-RPS and Kinetix 6000) to allow a drive fault to remove the DC bus power, and
Non-Kinetix 6000 Leader Drive with Single Follower IAM Power Diagram
to prevent the drive from applying DC bus power without the user’s input after clearing a drive fault.
In the figure below, the 8720MC-RPS regenerative power supply and
Figure A.7
Leader IAM with Multiple Follower IAM Diagram
To Follower
DC Bus Connections
To Follower
Control Power
Connections
Kinetix 6000
COMMON BUS LEADER IAM
2094-ACxx-Mxx or -BCxx-Mxx
Bonded Cabinet
Ground Bus *
Power Rail
Ground Stud Note 9
Cable Shield
Clamp
Single-Phase Input 1
CTRL 2 Control Power
95-264V ac RMS 2 (CPD) Connector
Notes 1, 2 CTRL 1 4
Note 4 Three-Phase
3
1 Motor Power W Motor Power
DC- 2
2 (MP) Connector V Connections
DC+ DC Bus 1 Note 14
3 and U
4 3-Phase
Three-Phase Input from LIM L3 Input (IPD)
or input power contactor (M1) 5 Connector
195-264V ac RMS L2
6 6
or 324-528V ac RMS L1 MBRK -
Notes 1, 2, 7, 8 5
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2
DBRK -
1
DBRK +
1
CONT EN- Contactor Enable
2 (CED) Connector
CONT EN+
Note 12
To Follower
Control Circuit
Connections
Wire the Leader and Follower IAM
contactor enable terminals in series
with the safety control string or LIM I/O.
Kinetix 6000
COMMON BUS FOLLOWER IAM
2094-ACxx-Mxx or -BCxx-Mxx
Bonded Cabinet
Ground Bus *
Power Rail
Ground Stud Note 9
Cable Shield
Clamp
Note 4
From Leader 1
CTRL 2 Control Power
Control Power 2 (CPD) Connector
Connections CTRL 1 4
Note 4 Three-Phase
3
From Leader 1 Motor Power W Motor Power
DC- (MP) Connector 2 Connections
DC Bus Connections 2 DC Bus V
DC+ 1 Note 14
3 and U
DC Bus Fusing * 4 3-Phase
Note 2 N.C. L3 Input (IPD)
5 Connector
N.C. L2
6 6
N.C. L1 MBRK -
5
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2
DBRK -
1
DBRK +
1 Contactor Enable
CONT EN-
2 (CED) Connector
CONT EN+
Note 12
Kinetix 6000
COMMON BUS FOLLOWER IAM
2094-ACxx-Mxx or -BCxx-Mxx
Bonded Cabinet
Ground Bus *
Power Rail
Ground Stud Note 9
Cable Shield
Clamp
1
CTRL 2 Control Power
2 (CPD) Connector
CTRL 1 4
3 Three-Phase
1 Motor Power W Motor Power
DC- 2
2 (MP) Connector V Connections
DC+ DC Bus 1 Note 14
3 and U
DC Bus Fusing * 4 3-Phase
Note 2 N.C. L3 Input (IPD)
5 Connector
N.C. L2
6 6
N.C. L1 MBRK -
5
MBRK +
4
COM
Motor/Resistive 3
Brake (BC) Connector PWR
2
DBRK -
1
DBRK +
From Leader
Control Circuit 1
CONT EN- Contactor Enable
Connections 2 (CED) Connector
CONT EN+
Note 12
In the figure below, a non-Kinetix 6000 leader drive and Kinetix 6000
Follower IAM are shown.
Figure A.8
Non-Kinetix 6000 Leader Drive with Single Follower IAM Power Diagram
Kinetix 6000
COMMON BUS FOLLOWER IAM
Bonded Cabinet 2094-ACxx-Mxx or -BCxx-Mxx
Ground Bus*
Power Rail
Non-Kinetix 6000 Ground Stud Note 9
COMMON BUS LEADER Cable Shield
Bonded Cabinet Clamp
Ground Bus*
Ground Stud Single-Phase Input 1
CTRL 2 Control Power
95-264V ac RMS 2
CTRL 1 (CPD) Connector
Notes 1, 2 4
Three-Phase
3
1 Motor Power W Motor Power
DC Bus DC- Pre-charge DC- DC Bus (MP) Connector 2 Connections
Circuitry* 2 Connections V
Connections DC+ DC+ 1 Note 14
3 U
DC Bus Fusing* 4 Ground
N.C. L3 3-Phase
5
N.C. L2 Input (IPD)
6 Connector 6
N.C. L1 MBRK -
5
MBRK +
Three-Phase Input L3 4
COM
from LIM or input L2 Motor/Resistive 3
power contactor (M1) Brake (BC) Connector PWR
Notes 1, 2, 7, 8 L1 2
DBRK -
1
DBRK +
1
CONT EN- Contactor Enable
2 (CED) Connector
CONT EN+
Note 12
DRIVE OK-
Contactor Enable * INDICATES USER -SUPPLIED COMPONENT
DRIVE OK+
Shunt Module Interconnect In the figure below, the Kinetix 6000 Shunt Module is shown wired for
internal shunt operation. This is the factory default jumper setting.
Diagrams
Figure A.9
Internal Shunt Module Interconnect Diagram
Kinetix 6000
SHUNT MODULE
2094-BSP2
3
External Shunt Resistor COL
2
(RC) Connector INT
1
DC+
2
External Thermal Switch TS2 1
(TS) Connector TS1
In the figure below, the Kinetix 6000 shunt module is shown wired
with an external passive shunt resistor.
Figure A.10
External Passive Shunt Module Interconnect Diagram
3
External Shunt Resistor COL COL
2
(RC) Connector INT Resistor
1 DC+
DC+
In the figure below, the Kinetix 6000 IAM (without the LIM) is shown
wired with a Bulletin 1336 external active shunt.
Figure A.11
External Active Shunt Module Interconnect Diagram
Contactor Enable 1
CONT EN- Refer to Attention statement (Note 11)
(CED) Connector 2
CONT EN+ CR1*
Note 12
CR1*
M1* 24V ac/dc
or
CR1* 120V ac
50/60 Hz
* INDICATES USER SUPPLIED COMPONENT START* STOP*
Notes 7, 12
Kx005 or Kx010 Input current requirement to power logic for fault 0.05A
contact operation.
Input current requirement to power fan and logic for
KB050 fault contact operation. 0.65A
In the figure below, the Kinetix 6000 IAM is shown (without a LIM)
wired with a Bulletin 1336 external active shunt (master) and two
slave units.
Figure A.12
External Active Shunt Module Interconnect Diagram
1
Contactor Enable CONT EN- EXTERNAL ACTIVE SHUNT
(CED) Connector 2
CONT EN+ RESISTOR (1336-MOD-Kxxxx)
Note 12
1
(+) Slave In
Notes 7, 12 2
(–) Slave In
3
STOP* START* (–) Master Out
24V ac/dc CR1* 4
or (+) Master Out
120V ac 5
M1* (–) DC Bus
50/60 Hz CR1* TB1
CR1* 6
(+) DC Bus
Note 4
Refer to Attention statement (Note 11)
1
TB3
2
3
Fault Relay Note 20
4
Shunt chassis 1336 Slave
ground screw
Single-Phase Input 1
115V ac RMS TB3
2
50/60 Hz
Note 4 3
Input Fusing* Fault Relay Note 20
Note 19 4
Shunt chassis 1336 Slave
ground screw
* INDICATES USER SUPPLIED COMPONENT
AM/Motor Interconnect This section contains the motor power, brake, and feedback signal
interconnect diagrams between an Axis Module and MP-Series,
Diagrams 1326AB, or F-, H-, N-, and Y-Series servo motors.
In the figure below, the Kinetix 6000 axis module (460V) is shown
connected to MP-Series Low Inertia and Integrated Gear (460V)
motors.
Figure A.13
Axis Module to MP-Series (460V) Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1
4 Green/Yellow D Motor Feedback
2
3 1/Blue C W (MF) Connector
3 Motor Power W GND
(IAM/AM)
4 (MP) Connector 2 2/Black B V
V Three-Phase
5 1 3/Brown A U Motor Power A BLACK SIN+ 1
6 Motor Feedback U WHT/BLACK SIN- 2
2090-XXNPMP-xxSxx
B
7 (MF) Connector COS+
Motor Power Cable C RED 3
8 Note 14
D WHT/RED COS- 4
9
10 Motor Feedback E GREEN DATA+ 5
11 Motor/Resistive 2090-UXNBMP-18Sxx Brake Cable F WHT/GREEN DATA- 10
12 Brake (BC) Connector Note 14
14
K GRAY +5VDC
13 6 Black C BR- L WHT/GRAY ECOM 6
MBRK -
14 5 White A Motor Brake N +9VDC 7
MBRK + BR+ ORANGE
15 R WHT/ORANGE TS+ 11
4
COM User Supplied Thermostat
3 24V dc (1.2A max.) S Refer to Low Profile Connector
PWR illustration (lower left)
2 BR- for proper grounding technique.
DBRK - Resistive Brake P
1 BR+ Connections
DBRK +
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Notes 14, 15, 17
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to MP-Series Low Inertia (MPL) and Integrated Gear (MPG)
230V servo motors.
Figure A.14
Axis Module to MP-Series (230V) Motor Interconnect Diagram
Cable Shield
Clamp
0 Note 9
1
4 Green/Yellow D
2
3 1/Blue C W Motor Feedback
3 Motor Power W GND
(MF) Connector
4 (MP) Connector 2 2/Black B V
V Three-Phase (IAM/AM)
5 1 3/Brown A U Motor Power
6 U SIN+ 1
A BLACK
7 2090-XXNPMP-xxSxx
Motor Feedback Motor Power Cable B WHT/BLACK SIN- 2
8 (MF) Connector Note 14 COS+
C RED 3
9
D WHT/RED COS- 4
10
11 Motor/Resistive 2090-UXNBMP-18Sxx Brake Cable E GREEN DATA+ 5
Brake (BC) Connector Motor Feedback
12 Note 14 F WHT/GREEN DATA- 10
13 6 Black C BR- K GRAY +5VDC 14
MBRK -
14 5 White A Motor Brake L WHT/GRAY ECOM 6
MBRK + BR+
15 N ORANGE – 7
4
COM User Supplied R WHT/ORANGE TS+ 11
3 24V dc (1.2A max.)
PWR Thermostat
2 BR- S Refer to Low Profile Connector
DBRK - Resistive Brake illustration (lower left)
1 BR+ for proper grounding technique.
DBRK + Connections P
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Notes 14, 15
Motor Feedback
MPL-A (230V) SERVO MOTORS (MF) Connector
WITH INCREMENTAL FEEDBACK (IAM/AM)
D A BLACK AM+ 1
B WHT/BLACK AM- 2
Grounding Technique for C W GND
Feedback Cable Shield B V C RED BM+ 3
Low Profile Connector Three-Phase D WHT/RED BM- 4
(2090-K6CK-D15M shown) A U Motor Power
E GREEN IM+ 5
F WHT/GREEN IM- 10
Motor Feedback K GRAY +5VDC 14
L WHT/GRAY ECOM 6
Clamp N ORANGE – 7
Exposed shield secured R WHT/ORANGE TS+ 11
under clamp.
Thermostat
Clamp screws (2) S BLUE –
Turn clamp over to hold C BR- T WHT/BLUE S1 12
small cables secure.
Motor Brake U YELLOW S2 13
A BR+ V WHT/YELLOW S3 8
P
Refer to Low Profile Connector
illustration (lower left)
for proper grounding technique.
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Notes 14, 15
In the figure below, the Kinetix 6000 axis module is shown connected
to MP-Series Food Grade (MPF) and MP-Series Stainless Steel (MPS)
servo motors.
Figure A.15
Axis Module to MP-Series Food Grade and Stainless Steel Motors
2090-XXNFMF-Sxx
(flying-lead) Feedback Cable
Notes 14, 15
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to TL-Series (230V) servo motors.
Figure A.16
Axis Module to TL-Series (230V) Motor Interconnect Diagram
In the figure below, the Kinetix 6000 axis module (460V) is shown
connected to 1326AB-Bxxxx (460V) servo motors.
Figure A.17
Axis Module to 1326AB Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1
4 Green/Yellow D Motor Feedback
2
3 1/Blue W (MF) Connector
3 Motor Power W C GND (IAM/AM)
4 (MP) Connector 2 2/Black B V
V Three-Phase
5 1 3/Brown A U A BLACK SIN+ 1
6 U Motor Power WHT/BLACK 2
B SIN-
2090-XXNPMP-xxSxx
7 Motor Feedback COS+ 3
Motor Power Cable C RED
8 (MF) Connector Note 14 WHT/RED COS-
D 4
9
10 Motor Feedback E GREEN DATA+ 5
11 Motor/Resistive 2090-UXNBMP-18Sxx Brake Cable F WHT/GREEN DATA- 10
12 Brake (BC) Connector Note 14
K – 14
GRAY
13 6 Black C BR- L WHT/GRAY ECOM 6
MBRK -
14 5 White A BR+ Motor Brake N ORANGE +9VDC– 7
15 MBRK +
4 R WHT/ORANGE TS+ 11
COM User Supplied Thermostat
3 24V dc (1.2A max.) S
PWR
2 BR- Refer to the
DBRK - Resistive Brake P Kinetix 6000 Installation Manual
1 BR+ Connections (publication 2094-IN001) for proper
DBRK +
2090-XXNFMP-Sxx
(flying-lead) Feedback Cable
Note 14, 15
1
Wiring the thermal switch on 1326AB (resolver-based) motors requires the use of the Low Profile connector kit
(2090-K6CK-D15MF) and wire extension to the power connector. Pins 16, 17, and S are filtered to prevent noise
transmission back to the drive. Refer to the Kinetix 6000 Installation Manual (publication 2094-IN001) for wiring
instructions and a diagram.
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to H- and F-Series (230V) servo motors.
Figure A.18
Axis Module to H/F-Series Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1
4 Green/Yellow D
2
3 1/Blue C W Motor Feedback
3 Motor Power W GND
(MF) Connector
4 (MP) Connector 2 2/Black B V
V Three-Phase (IAM/AM)
5 1 3/Brown A U Motor Power
6 U A BLACK AM+ 1
2090-XXNPH/HF-xxSxx
7 Motor Power Cable B WHT/BLACK AM- 2
8 Motor Feedback Note 14
C RED BM+ 3
9 (MF) Connector
D WHT/RED BM- 4
10
11 9101-0330 Brake Cable Connector Kit E GREEN IM+ 5
Motor Feedback
12 Note 14 F WHT/GREEN IM- 10
13 6 Black B BR- R WHT/BROWN TS+ 11
MBRK -
14 5 White A Motor Brake P BROWN S3 8
BR+
15 MBRK +
K
4 GRAY +5VDC 14
COM User Supplied J
3 24V dc (1.2A max.) L
PWR WHT/GRAY ECOM 6
2 BR- M
DBRK - Resistive Brake
1 BR+ N BLUE S2 13
DBRK + Connections
T WHT/BLUE S1 12
Motor/Resistive H VIOLET –
Brake (BC) Connector Thermostat
S WHT/VIOLET TS- 6
Refer to Low Profile Connector
illustration (below)
for proper grounding technique.
2090-XXNFHF-Sxx
(flying-lead) Feedback Cable
Note 14, 15
Clamp
Exposed shield secured
under clamp.
Clamp screws (2)
Turn clamp over to hold
small cables secure.
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to N-Series (230V) servo motors.
Figure A.19
Axis Module to N-Series Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9 E N/C
1
4 Green/Yellow D
2
3 1/Blue C W Motor Feedback
3 Motor Power W GND
(MF) Connector
4 (MP) Connector 2 2/Black B V
V Three-Phase (IAM/AM)
5 1 3/Brown A U Motor Power
6 U A BLACK AM+ 1
2090-XXNPN-xxSxx
7 Motor Power Cable B WHT/BLACK AM- 2
8 Motor Feedback Note 14
C RED BM+ 3
9 (MF) Connector
D WHT/RED BM- 4
10
11 9101-1698 Brake Cable Connector Kit E GREEN IM+ 5
Motor Feedback
12 Note 14 F WHT/GREEN IM- 10
13 6 Black B BR- R WHT/BROWN TS+ 11
MBRK -
14 5 White A Motor Brake V BROWN S3 8
BR+
15 MBRK +
K
4 GRAY +5VDC 14
COM User Supplied C N/C J
3 24V dc (1.2A max.) L
PWR WHT/GRAY ECOM 6
2 BR- M
DBRK - Resistive Brake
1 BR+ U BLUE S2 13
DBRK + Connections
T WHT/BLUE S1 12
Motor/Resistive H VIOLET –
Brake (BC) Connector Thermostat
S WHT/VIOLET TS- 6
Refer to Low Profile Connector
illustration (below)
for proper grounding technique.
2090-XXNFN-Sxx
(flying-lead) Feedback Cable
Note 14, 15
Clamp
Exposed shield secured
under clamp.
Clamp screws (2)
Turn clamp over to hold
small cables secure.
In the figure below, the Kinetix 6000 axis module (230V) is shown
connected to Y-Series (230V) servo motors.
Figure A.20
Axis Module to Y-Series Motor Interconnect Diagram
Cable Shield
0 Clamp
Note 9
1 4 Green/Yellow 4
2 Motor Feedback
3 3/Black 3 W GND
3 Motor Power W (MF) Connector
4 (MP) Connector 2 2/Black 2 V (IAM/AM)
V Three-Phase
5 1 1/Black 1 U Motor Power
6 U 9 BLACK AM+ 1
7 Motor Feedback 10 WHT/BLACK AM- 2
8 (MF) Connector Pigtail
2090-XXNPY-xxSxx 11 RED BM+ 3
9 Motor Power and Brake Cable Motor 12 WHT/RED BM- 4
Note 14
10 Feedback
13 GREEN IM+ 5
11
14 WHT/GREEN IM- 10
12 Pigtail
Black 9 BR- 15 WHT/BLUE S1 12
13 Motor
14 Motor/Resistive 7 17 BLUE S2 13
Black BR+ Brake
15 Brake (BC) Connector 8
19 BROWN S3
6 – WHT/BROWN –
MBRK -
5 22 GRAY +5VDC 14
MBRK +
4 23 WHT/GRAY ECOM 6
COM User Supplied 24 DRAIN
3 24V dc (1.2A max.)
PWR
2 Refer to Low Profile Connector
BR- illustration (below)
DBRK - Resistive Brake
1 for proper grounding technique.
BR+ Connections
DBRK +
2090-XXNFY-Sxx
(flying-lead) Feedback Cable
Notes 14, 15, 16
Clamp
Exposed shield and drain wire
secured under clamp.
Clamp screws (2)
Turn clamp over to hold
small cables secure.
Controlling a Brake The relay output of the Kinetix 6000 (MBRK± BC-5 and -6) is suitable
for directly controlling a motor brake, subject to the relay voltage limit
Example of 30V dc, and the relay current limit as shown in the table below.
The following tables list Allen-Bradley motors and brake coil current
ratings.
Coil Currents Rated at < 1.0A Coil Currents Rated at < 1.0A
Compatible Brake Motors Coil Current Compatible Brake Motors Coil Current
F-4030, -4050, and -4075 0.69A MPL/MPF/MPS-x310, -x320, -x330 1 0.50A
1
H-3007 and -3016 0.60A MPL-x420, -x430, -x4520, -x4530, -x4540
0.64A
H-4030, -4050, and -4075 0.69A MPF-x430, -x4530, -x4540 1
N-2302, and -2304 0.28A MPG-x004 1 0.33A
N-3406, -3412, -4214, and -4220 0.36A MPG-x010 1
0.45A
N-5630, -5637, and -5647 0.71A MPG-x025 1
Y-1002 and -1003 0.26A MPG-x050 1 0.50A
Y-2006 and -2012 0.31A MPG-x110 1 1.0A
Y-3023 0.37A
TL-A110P-H, -A120P-H, and -A130P-H 0.208A
TL-A220P-H and -A230P-H 0.375A 1326AB-B4xxx 0.88A
TL-A2530P-H and -A2540P-H 0.396A
TL-A410P-H 0.746A
1
Applies to 230V and 460V motors.
Coil Currents Rated > 1.0A and ≤1.3A Coil Currents Rated > 1.0A and ≤1.3A
Compatible Brake Motors Coil Current Compatible Brake Motors Coil Current
F-6100, -6200, and -6300 1.30A MPL-x520, -x540, -x560, -x580 1
1.05 to 1.28A
MPF-B540
H-6100, -6200, and -6300 1.13A
1326AB-B5xxx, and -B7xxx 1.20A
1Applies to 230V and 460V motors.
Coil Currents Rated > 1.3A and ≤3.0A Coil Currents Rated > 1.3A and ≤3.0A
Compatible Brake Motors Coil Current Compatible Brake Motors Coil Current
MPL-B640, -B660, -B680, -B860, -B880,
H-8350 and -8500 2.20A 1.91 to 2.19A
-B960, -B980
Figure A.21
Example Configuration Controlling a Motor Brake
Kinetix 6000
IAM (inverter) or AM
Note 13
6
MBRK -
5 CR1
MBRK +
4
COM User Supplied
3 24V dc (3.0A max.)
PWR
2
DBRK -
1 BR-
DBRK +
CR1 BR+ Brake
Motor/Resistive 1 SERVO
Brake (BC) Connector Feedback MOTOR
Power
1
For Motor/Resistive Brake (BC) connector specifications, refer to the Kinetix 6000 Installation Manual (publication
2094-IN001).
PWR U V W
System Block Diagrams
DBRK MBRK
Interconnect Diagrams
Motor Shield
DC+
Common Mode
Choke
(460V only)
Inverter Block Diagram
POWER
RAIL DC-
SYSOK
Inverter Section Shunt Circuit
CONV_ID (5)
CTRL 1 (460V only)
SMPS
GSHUNT (2)
+/-12V (Control)
CTRL 2
IAM/AM Inverter Block Diagram
Vcc
Ground Jumper 4 120K Shunt Circuit 2 Vsns
CONV_OT
Figure A.23
95C POWER
Chassis RAIL
CTRL-
DC+
DC-
Control Power CTRL+
Converter Block Diagram
AC Input
CTRL1
SYS_OK
CTRL2
EMC Filter1 GSHUNT
IAM Converter Block Diagram
Control Power
Loss Detector
DROK/
CONT_EN Rectifier Circuit 2
CONT_EN1
1
CONT_EN2 EMC filter present only on 460V converters.
2
Rectifier and shunt circuits present only on 230V converters.
3
Internal DC link inductor present on 460V converters.
Interconnect Diagrams
The Kinetix 6000 Safe-Off drives ship with the wiring header and
motion allowed jumper installed, as shown in the figure below. With
the motion allowed jumper installed, the safe-off feature is not used.
Figure A.24
Safe-Off Feature Block Diagram
Safe-Off Option
Safe-Off (SO) Gate Control
9-pin Connector Power Supply
K1-C
8 +24V
9 +24V_COM
3 FDBK1+
4 FDBK1-
K1-A
7 ENABLE1+
K1 Gate Control
6 ENABLE- Safety Monitor
K2 uC Circuit (CCP)
5 ENABLE2+
K2-A
1 FDBK2+
2 FDBK2-
SM Block Diagram
Figure A.25
Shunt Module Block Diagram
DC+
Internal
or External
Shunt
Resistor
POWER
RAIL DC-
SYSOK
Shunt Circuit
CTRL 1 SMPS
GSHUNT (2)
+5V (Control)
CTRL 2 +/-15V (IGBT)
24V (Control)
Chassis
OPL
OPL
1 CONSTAT_12
1 Interface PCB
2 L3' CONSTAT_22
2
3 L2' CONSTAT_32
3 24V Status LED
4 L1' CONSTAT_54 IOL: STATUS I/O
4 IOL
COIL_A2 IOL Pin 1 IO_PWR1
OPL: VAC LOAD Pin 2 IO_COM1
1 1
Pin 1 PE N/C 2 2 Pin 3 IO_PWR1
COIL_E2
Pin 2 L3' 2 4 6 12 22 32 42 54 A2 E2 3 Pin 4 IO_COM1
COIL_E1
Pin 3 L2' E1 4 Pin 5 IO_PWR1
Pin 4 L1' CR1 100-JE 5 Pin 6 IO_COM1
CONSTAT_54
6 Pin 7 COIL_E1
1 3 5 11 21 31 41 53 A1 A1 CONSTAT_32
7 Pin 8 COIL_E2
IPL CONSTAT_22
IPL N/C 8
CB1 CONSTAT_12 Pin 9 ALRM_M
1 9
1 ALRM_COM Pin 10 SHIELD
10
2 L1 1 2 ALRM_B Pin 11 ALRM_B
2 11
COIL_E1 Pin 12 ALRM_COM
3 L2 3 4 12
3 CONSTAT_53 CONSTAT_53
13 Pin 13 CONSTAT_11
4 L3 5 6 CONSTAT_31 CONSTAT_31
14 Pin 14 CONSTAT_12
4 CONSTAT_21 CONSTAT_21
15
Figure A.26
4
L1 1 2 Single Phase, 1-Stage 3 Pin 3 AUX1_L1
14
L2 Line Filter (230VAC) 2 3 Pin 2
1 2 AUX2_L2
L2 3 4 1
L1 1 3 L1' 2 Pin 1 AUX2_L1
3 4 CTRL1
L2 2 4 L2'
5 PE CTRL2 1
Interface PCB
OPL
OPL
1 CONSTAT_12
1 Interface PCB
2 L3' CONSTAT_22
2
3 L2' CONSTAT_32 24V Status LED
3
4 L1' CONSTAT_54 IOL IOL: STATUS I/O
4
COIL_A2 IOL Pin 1 IO_PWR1
OPL: VAC LOAD 1 Pin 2 IO_COM1
1
N/C 2 2 Pin 3 IO_PWR1
Pin 1 PE COIL_E2
2 4 6 12 22 32 42 54 A2 E2 3 Pin 4 IO_COM1
Pin 2 L3' COIL_E1
E1 4 Pin 5 IO_PWR1
Pin 3 L2' CR1 100-JE 5 Pin 6 IO_COM1
Interconnect Diagrams
OPL
OPL
1 CONSTAT_12
1 Interface PCB
2 L3' CONSTAT_22
2
3 L2' CONSTAT_32 24V Status LED
3
4 L1' CONSTAT_54 IOL IOL: STATUS I/O
4
COIL_A2 IOL Pin 1 IO_PWR1
OPL: VAC LOAD 1 Pin 2 IO_COM1
1
Pin 1 PE N/C 2 2 Pin 3 IO_PWR1
COIL_E2
Pin 2 L3' 2 4 6 12 22 32 42 54 A2 E2 3 Pin 4 IO_COM1
COIL_E1
E1 4 Pin 5 IO_PWR1
Pin 3 L2'
CR1 100-JE 5 Pin 6 IO_COM1
Pin 4 L1' CONSTAT_54
6 Pin 7 COIL_E1
1 3 5 11 21 31 41 53 A1 A1 CONSTAT_32
7 Pin 8 COIL_E2
IPL CONSTAT_22
IPL N/C 8
CB1 CONSTAT_12 Pin 9 ALRM_M
1 9
1 ALRM_COM Pin 10 SHIELD
10
2 L1 1 2 ALRM_B Pin 11 ALRM_B
11
2 COIL_E1 Pin 12
L2 3 4 12 ALRM_COM
3 CONSTAT_53 CONSTAT_53
3 13 Pin 13 CONSTAT_11
4 L3 5 6 CONSTAT_31 CONSTAT_31
14 Pin 14 CONSTAT_12
4 CONSTAT_21 CONSTAT_21
15
Figure A.28
Pin 4 PE
CONSTAT_22
Pin 3 L3'
OPL Pin 2 L2' CONSTAT_32 24V Status LEDs
Pin 1 L1'
4
CONSTAT_42
L3_OUT
3
L2_OUT COIL_A2
2
L1_OUT
1
2 4 6 12 22 32 42 A2
IOL: STATUS I/O
D1 Pin 1 N/C
CR1
IPL: VAC LINE INPUT Pin 2 N/C
Pin 1 PE Pin 3 N/C
5 31 Pin 4 COIL_A2
Pin 2 L3 1 3 11 21 41 A1
Interconnect Diagrams
Pin 5 N/C
Pin 3 L2
IOL Pin 6 CONSTAT_12
Pin 4 L1 COIL_A1
Pin 7 CONSTAT_22
COIL_A1
19
10
Pin 25 IO_PWR
Pin 26 IO_PWR
Single-Phase, 1-Stage
Line Filter (230VAC)
1 2
IO_PWR
L1 L1' L1 24+
3 4 6A Power Supply IO_COM
L2 L2' L2 24-
PE PSL
PE
CB3 1 PSL: I/O 24V DC OUTPUT
PS2
LF2
2 Pin 1 MBRK_PWR
MBRK_PWR Pin 2 MBRK_COM
L1 24+ 3 Pin 3 MBRK_PWR
2A Power Supply MBRK_COM Pin 4 MBRK_COM
L2 24- 4
PE
PS1
CPL
CPL: CONTROL POWER
1 2 L2/N
1 Pin 1 L2/N
3 4 L1 Pin 2 L1
2
CB2
OPL: VAC LOAD OUTPUT CONSTAT_12
Pin 1 PE
CONSTAT_22
Pin 2 L3'
OPL Pin 3 L2' CONSTAT_32 24V Status LEDs
Pin 4 L1'
1
CONSTAT_42
L3_OUT
2
L2_OUT COIL_A2
3
L1_OUT
4
2 4 6 12 22 32 42 A2
IOL: STATUS I/O
CR1 D1 Pin 1 N/C
IPL: VAC LINE INPUT 100S-C85 Pin 2 N/C
Pin 4 PE Pin 3 N/C
5 31 Pin 4 COIL_A2
Pin 3 L3 1 3 11 21 41 A1
Pin 5 N/C
Pin 2 L2
IOL Pin 6 CONSTAT_12
Pin 1 L1 COIL_A1
Pin 7 CONSTAT_22
CONSTAT_42 Pin 8
CONSTAT_41 CONSTAT_32
Three Phase, 1-Stage CONSTAT_41
Pin 9 CONSTAT_42
IPL Line Filter (460VAC) CONSTAT_32
9
18
1 2 Pin 10 N/C
26
COIL_A1
19
10
Pin 25 IO_PWR
Pin 26 IO_PWR
Single-Phase, 1-Stage
Line Filter (230VAC)
1 2
IO_PWR
L1 L1' L1 24+
3 4 6A Power Supply IO_COM
L2 L2' L2 24-
460V to 230V PE PSL
750VA XFMR PE
CB3 1 PSL: I/O 24V DC OUTPUT
PS2
TX1 LF2
2 Pin 1 MBRK_PWR
MBRK_PWR Pin 2 MBRK_COM
L1 24+ 3 Pin 3 MBRK_PWR
2A Power Supply MBRK_COM Pin 4 MBRK_COM
L2 24- 4
PE
PS1
Interconnect Diagrams
CPL
CPL: CONTROL POWER
1 2 L2/N
1 Pin 1 L2/N
3 4 L1 Pin 2 L1
2
CB2
GROUND 4 4 GROUND
3 1 2
W DRIVE 3 W MTR
3 4
I/O Connections
D1 (TB3) Connector
RBM Block Diagrams
R1 R2 R3 1 TS_21
2 TS_22
T1 (fault) 3 CONSTAT_41
RBM Block Diagram (2090-XB33-xx)
4 CONSTAT_42
5 SHIELD
T2 (warning)
6 COIL_A1
7 COIL_A2
8 SHIELD
Drive Connections RBM Enclosure Motor Connections
(TB1) Connector (TB2) Connector
CR1
GROUND 4 4 GROUND
W DRIVE 3 1 2
3 W MTR
V DRIVE 2 3 4
2 V MTR
U DRIVE 1 5 6
1 U MTR
W BRAKE 11 12
V BRAKE 21 22
Figure A.32
CONSTAT_42
T2 (warning)
5 SHIELD
6 COIL_A1
7 COIL_A2
8 SHIELD
Interface PCB
Interconnect Diagrams
Chapter Objectives This appendix provides a procedure for upgrading the Kinetix 6000
firmware using DriveExplorer.
Upgrade Drive Firmware Upgrading axis module firmware using DriveExplorer (via the DPI
port) involves setting the Axes to Flash parameter, configuring a
Using DriveExplorer HyperTerminal session, and flashing the firmware.
Before you begin this procedure, make sure you have the following:
Minimum Firmware
Description Catalog Numbers Revision
In this procedure you will use DriveExplorer software to set the Axes
to Flash parameter (x708) and allow selective axis module upgrading.
Note: You will save time by selecting only the axis module(s) that
require a firmware upgrade.
ATTENTION
To avoid injury or damage to equipment due to
unpredictable motor activity, do not apply AC
input (three-phase) power or establish
communications with the 1756-MxxSE SERCOS
interface module.
4. Verify that the 1203-SSS has power by observing the LED indicated
in Figure B.1.
Figure B.1
1203-SSS DPI Adapter
DPI communication
10. Check each axis to flash (example above shows two axes to flash).
HyperTerminal Configuration
5. Go to the Transfer menu and select Send File. The Send File
window opens. Browse for your firmware upgrade file.
ATTENTION
To avoid unrecoverable fault to modules, do not
interrupt control power to IAM, power to the
1203-SSS DPI adapter, or power to your PC while
the flash upgrade operation is in progress.
10. Verify that parameter 30 for each axis module is now upgraded to
the new firmware revision. Return to DriveExplorer (refer to Select
Axis Modules to Upgrade, step 6) to see the linear list of
parameters.
Chapter Objectives This appendix provides Bulletin 2090 Resistive Brake Module (RBM)
integration procedures specific to the Allen-Bradley Kinetix 6000
multi-axis servo drive systems using drive firmware v1.071 (or above).
The procedure involves setting the time delay parameter using
RSLogix 5000.
Before You Begin These procedures assume you have mounted and wired your RBM
with your Kinetix 6000 drive system. The following publications are
available to assist you with RBM installation:
Understand Safety The following precautions apply to resistive brake module installation
as shown in the interconnect diagrams. Be sure to read and
Precautions thoroughly understand them before proceeding.
ATTENTION
The interconnection diagrams should be used as a
general recommendation on how the safety control
circuit may be implemented. Actual applications may
vary due to requirements based on the machine
builders risk assessment. The machine builder must
perform a risk assessment and determine a category
level of safety that must be applied to the machine.
Stop Categories
One of the most basic safety functions is stopping the machine. The
stopping function of a machine must fall into one of three categories
(EN60204-1 and NFPA79). The categories are as follows:
Risk Assessment
The European safety standard (EN 1050) and U.S. technical report
(ANSI B11.TR3) explain the process of risk assessment, which must be
conducted by the machine builder. This is done by analyzing the tasks
that people perform on and around the machine. This includes
functions such as operation, set up, and maintenance. For the purpose
of this appendix, the light curtain or gate interlock is intended to focus
on the operation and perhaps loading/unloading of a machine.
Additional protective measures must be identified by the risk
assessment.
Control Reliability
In the United States the AMT has promoted a concept called Control
Reliability as part of the ANSI B11.TR3 standard. This standard has
similar requirements to those in the Machinery Directive EN954-1
Category 3 risk standard.
Resistive Brake Module This section provides interconnect diagrams to assist you in wiring a
Kinetix 6000 system which includes an RBM. The notes in the table
Interconnect Diagram below apply to the following example RBM interconnect diagrams.
Notes
ATTENTION The National Electrical Code and local electrical
codes take precedence over the values and
methods provided. Implementation of these
codes is the responsibility of the machine
builder.
Note Information
1 Cable shield clamp must be used in order to meet CE requirements. No external connection to ground required.
2 For motor cable specifications, refer to the Kinetix Motion Control Selection Guide (publication GMC-SG001).
3 The BRKTMP0 signal can be wired to a ControlLogix input as overtemp warning in user program.
4 Firmware version 1.071 (or higher) is required to use the DBRK outputs on the Kinetix 6000 IAM or AM.
5 The safety relay time delay should be set beyond the time required to stop and disable the axis when running at full speed.
6 Drive Enable Input Checking must be selected in Axis Properties.
-XL75S-C2 4 4 4 D
Resistive Brake Module
Motor Power 3 3 L1 3 C
Single-Phase Output 1 1 Control Power W W_DRIVE W_MTR W GND
CTRL 2 CTRL 2 (MP) Connector 2 2 L2 2 B
(CPL) Connector 2 2 (CPD) Connector V V_DRIVE V_MTR V
CTRL 1 CTRL 1 1 1 L3 1 A
3 3 5 Connector
L2 L2' L2 Note 2
4 4 6
L1 L1' L1
IO_COM2 2
3 L2
24V dc Output IO_PWR2 B
4 1
(P1L) Connector 6 L1
IO_COM2 MBRK -
5 5
IO_PWR2
6 A MBRK + I/O Connections
IO_COM2 4 (TB3) Connector
COM
Motor/Resistive 3
1 PWR 8
AUX1_L1 Brake (BC) Connector SHIELD
B 2 7 T1
230V ac Output 2 DBRK - COIL_A2
AUX1_L2
(P2L) Connector 3 1 Note 4 6
AUX2_L1 DBRK + COIL_A1 K
C 5
AUX2_L2 4 SHIELD
BRKSTAT0 4 AUX4
CONSTAT_42
3
I/O (IOL) 2, 4, 6 1 Contactor Enable Note 3 CONSTAT_41
IO_COM1 CONT EN- BRKTMP0 2
Connector 8 2 (CED) Connector
COIL_E2 CONT EN+ TS_22
K IO_PWR1 1
1, 3, 5 TS_21
IO_PWR1
7 T2
COIL_E1
230V ac Auxiliary 1
L1
Input Power 2
L2/N IO_PWR1
(APL) Connector
* INDICATES USER SUPPLIED COMPONENT
D
Example RBM Interconnection Diagram (Category 2 Configuration per EN954-1)
The example diagram below shows Kinetix 6000 IAM, AM, and LIM
(2094-AL75S, -BL75S, and -XL75S) wired with the Bulletin 2090 RBM.
D
T2
5 Connector Note 2
L2 L2' L2
6
L1 L1' L1
(PSL) Connector 3 2
MBRK_PWR L2
4 A 1
MBRK_COM 6 L1
MBRK -
5
MBRK + I/O Connections
4
COM (TB3) Connector
Motor/Resistive 3
PWR 8
Brake (BC) Connector SHIELD
2 7 T1
DBRK - COIL_A2
1 Note 4 6
DBRK + COIL_A1 K
5
SHIELD
BRKSTAT0 4 AUX4
CONSTAT_42
3
I/O (IOL) 24-26 1 Contactor Enable Note 3 CONSTAT_41
IO_PWR CONT EN- BRKTMP0 2
Connector 20-22 2 (CED) Connector
IO_COM CONT EN+ TS_22
K IO_PWR 1
13 TS_21
COIL_A1
4 T2
COIL_A2
IO_PWR
B
Example RBM Interconnection Diagram (Category 2 Configuration per EN954-1)
The example diagram below shows Kinetix 6000 IAM, AM, and LIM
B
T2
Note 2 R1 AUX1
(OPL) Connector Three-Phase 2094-IN001) for motor power
2 2 4 Input (IPD)
L3 L3' L3 cable catalog numbers.
3 3 5 Connector Note 2
L2 L2' L2
4 4 6
L1 L1' L1
Auxiliary 230V ac
1 Input (TB4) Connector
Three-Phase Input IO_PWR2
(IPL) Connector 2 (2090-XB120-xx only)
Integrate Resistive Brake Modules with Kinetix 6000 Drives
IO_COM2
3 2
24V dc Output IO_PWR2 L2
(P1L) Connector 4 6 A 1
IO_COM2 L1
5 MBRK -
IO_PWR2 Motor/Resistive 5
6 Brake (BC) Connector MBRK + I/O Connections
IO_COM2 4 (TB3) Connector
COM
3 8
1 PWR SHIELD
AUX1_L1 2
2 A 7 T1
230V ac Output AUX1_L2 DBRK - COIL_A2
(P2L) Connector 3 1 Note 4 6
AUX2_L1 DBRK + COIL_A1 K
5
AUX2_L2 4 BRKSTAT0 SHIELD
4 AUX4
1
+24V_PWR E CONSTANT_42
IO_PWR1 I/O (IOD) 2 3
Connector ENABLE CONSTANT_41
BRKTMP0 2
Note 6 3 TS_22
+24V_COM
1, 3, 5 1 Note 3 IO_PWR1 1
I/O (IOL) IO_PWR1 CONT EN- TS_21
Connector 2, 4, 6 2 T2
IO_COM1 CONT EN+
7
K COIL_E1 Contactor Enable
8 (CED) Connector
COIL_E2
230V ac Auxiliary 1 * INDICATES USER SUPPLIED COMPONENT
L1
Input Power 2
(APL) Connector L2/N
B C D
The example diagram below shows Kinetix 6000 IAM and LIM
A2 X1 X2 X3 X4 Y39 Y40 Y2 Y1 14 24 38 48 58
ENABLE0
* INDICATES USER SUPPLIED COMPONENT
COIL0
COM
BRKSTAT0
STOPSTAT
Integrate Resistive Brake Modules with Kinetix 6000 Drives
2 DC Bus RBM to Drive Interface Cable R2 AUX2 Refer to the Kinetix 6000
DC+
Three-Phase Output 3 and Note 2 AUX1 Installation Manual (publication
R1
(OPL) Connector Three-Phase 2094-IN001) for motor power
4
L3 L3' L3 Input (IPD) cable catalog numbers.
5 Connector Note 2
L2 L2' L2
6
L1 L1' L1
Auxiliary 230V ac
Integrate Resistive Brake Modules with Kinetix 6000 Drives
A2 X1 X2 X3 X4 Y39 Y40 Y2 Y1 14 24 38 48 58
ENABLE0
* INDICATES USER SUPPLIED COMPONENT
COIL0
COM
BRKSTAT0
STOPSTAT
Integrate Resistive Brake Modules with Kinetix 6000 Drives
Set the RBM Delay Time In this procedure you will break SERCOS ring communications, set the
delay time parameter using DriveExplorer software, and re-establish
Using DriveExplorer SERCOS communication.
1
Refer to DriveExplorer Getting Results Manual (publication 9306-GR001) for instructions.
2
Refer to 1203-SSS (Series B) FRN 3.xxx User Manual (publication 20COMM-UM001) for instructions.
3
Additional information regarding these communication and software tools is available at www.ab.com/
support/abdrives.
ATTENTION
To avoid personal injury or equipment damage,
at least one end of a SERCOS fiber-optic cable
must be disconnected from the drive. This
ensures that motion will not occur while
changes are made to the time delay parameter.
6. Click on the Value Edit tab and enter the delay time Value (ms).
The recommended RBM delay time is 71 ms.
7. Select OK. The RBM delay time is changed, but not saved in
non-volatile memory.
4. Click OK.
5.
If you Then
Have another RBM in the Go to Set the RBM Delay Time
Kinetix 6000 system Parameter (step 4).
1. Close DriveExplorer.
Do not have another RBM
in the Kinetix 6000 system 2. Go to Reconnect SERCOS
Communication.
Chapter Objectives This appendix provides integration procedures specific to the Kinetix
6000 multi-axis servo drive systems configured for DC common bus
and using drive firmware v1.85 (or above). The procedure involves
calculating capacitance values and setting the Add Bus Cap parameter
using DriveExplorer software.
Before You Begin These procedures assume you have mounted and wired your Kinetix
6000 DC common bus system. Refer to the Kinetix 6000 Installation
Manual (publication 2094-IN001) for mounting and wiring
information.
Before you set the Additional Bus Capacitance (Add Bus Cap)
parameter in DriveExplorer, you need to calculate the following
values using the tables provided:
Total bus capacitance is the sum of all capacitance values for your
Kinetix 6000 common bus modules. Specifically, this includes the
capacitance values for the following modules:
Use the tables below when calculating total bus capacitance and
additional bus capacitance for your Kinetix 6000 common bus
application.
SM (230/460V) Module
SM (230-460V) Capacitance
2094- µF
BSP2 470
In the figure below, the sum of the Leader IAM power rail modules
capacitance (6530 µF) and the Follower IAM power rail modules
capacitance (5280 µF) equals 11810 µF Total Bus Capacitance.
The sum of the Follower IAM power rail modules equal 5280 µF
Additional Bus Capacitance.
Figure D.1
Calculating Common Bus Capacitance
AC Line
Filter
Three-Phase
Input Power
Set the Additional Bus In this procedure you will set the Add Bus Cap parameter using
DriveExplorer software.
Capacitance Parameter
The following hardware and software tools are required to provide
the necessary communication link between your PC and the Kinetix
6000 drive system running DriveExplorer.
1
Refer to DriveExplorer Getting Results Manual (publication 9306-GR001) for instructions.
2
Refer to 1203-SSS (Series B) FRN 3.xxx User Manual (publication 20COMM-UM001) for instructions.
3
Additional information regarding these communication and software tools is available at www.ab.com/
support/abdrives.
ATTENTION
To avoid personal injury or equipment damage, at
least one end of a SERCOS fiber-optic cable must be
disconnected from the drive. This ensures that
motion will not occur while changes are made to the
Add Bus Cap parameter.
6. Click on the Value Edit tab and enter the Add Bus Cap Value (µF).
7. Select OK. The Add Bus Cap parameter is changed, but not saved
in non-volatile memory.
Numerics A-33
1203-SSS serial cable B-2, B-4 RBM A-34, A-35
16 axis SERCOS interface PCI safe-off feature A-28
card installation instructions shunt module A-28
P-3 blown fuse 2-3
1756 module properties 1-18 brake A-24
1756-MxxSE interface module brake power LED 1-27, 2-12
1-9, 1-16 bus
1784-PM16SE PCI card 1-9 overvoltage 2-4
24V power LED 2-12 undervoltage 2-4
26-pin I/O connector 2-20 bus overcurrent 2-7
bus regulator 1-22
bus status LED 1-29, 1-32, 2-9,
A 2-11
acronyms P-4
additional bus capacitance
calculating D-3
C
example D-4 cables
analog test points fiber optic cable length 1-9
DAC0 2-20 CAD files P-3
DAC1 2-20 can init 2-7
applying power 1-26 CB1, CB2, CB3 1-26
with LIM 1-26 certifications
without LIM 1-30 Rockwell Automation Product
atune fault 2-6 Certification P-3
aux fdbk noise fault 2-6 changing parameters
aux feedback AQB 2-6 DriveExplorer 2-19
aux feedback loss 2-6 HIM 2-20
auxiliary encoder error, circuit breakers 1-26
see troubleshooting comm status LED 1-29, 1-31, 2-8
axis module commissioning your Kinetix 6000
connector designators 1-2 1-1
connector locations 1-4 common bus (see DC common
axis properties 1-24 bus)
axis unstable 2-14 Common Bus FLT 2-7
component removal and
replacement 2-22
B configuring
backplane comm 2-7 AM 1-15
bandwidth 1-37 base node address 1-10
base node address 1-10 baud rate, AM 1-15
example with two baud rate, IAM 1-14
ControlLogix chassis 1-12, feedback only axis 1-21
1-13 IAM 1-10
example with two power rails Kinetix 6000 1-9
1-11 optical power level 1-14, 1-15
baud rate 1-14, 1-15 SERCOS module 1-16
block diagrams connector designators
converter A-27 axis module 1-2
inverter A-26 integrated axis module 1-2
LIM A-29, A-30, A-31, A-32, line interface module 1-6
D G
DAC0 2-20 ground fault 2-5
DAC1 2-20
data rate 1-19 H
data type 1-20 hardware overtravel 2-4
date and time tab 1-17 HIM 2-19
DC common bus hookup fault 2-6
configuring 1-22 hookup tab 1-34
interconnect diagram A-8, A-9, human interface module (HIM)
A-10, A-12 2-19
setting the add bus cap hyperterminal B-4
parameter D-5
digital I/O not working correctly
2-3 I
dip switches 1-19 I/O connector 2-20
disable drive 2-16 I/O power LED 1-27, 2-12
documentation files P-3 Ifbk HW Fault 2-6
download program 1-25 illegal hall state 2-4
drive enable fault 2-5 integrated axis module
drive overcurrent 2-3 configuring 1-10
drive overtemp 2-5, 2-7 connector designators 1-2
drive status LED 1-29, 1-31, 2-8 connector locations 1-3
drive tab 1-24 interconnect diagram A-3, A-4,
drive undervoltage 2-5 A-6, A-7, A-8, A-9, A-10,
DriveExplorer 2-19, B-1, C-14, A-12
D-5 interconnect diagrams
2094 with H-Series motor A-21
2094 with MPG-A motor A-17,
E A-18, A-19
encoder communication fault 2-5
Installation Assistance
Rockwell tests all of its products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is
not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case
number (see phone number above to obtain one) to your distributor in
order to complete the return process.
Outside United Please contact your local Rockwell Automation representative for
States return procedure.