SC1
SC2.5
SC4
@ 16 mJ/cm2
@ 40 mJ/cm2
GPM
L/Min
GPM
L/Min
2.0
4.2
7.5
7.5
15.9
28.4
0.5
1.9
2.8
2
7.2
10.6
Lamp
Watts
Power
Consumption
10W
14W
17W
12W
16W
19W
Dimensions, Inches
Length
Cell Dia.
Shipping
Weight
Lbs.
13.5
16.5
18.2
2.5
2.5
2.5
4
5
6
Replacement Parts
Model No.
SC1
SC2.5
SC4
Ballast:
Lamp
Quartz Sleeve
S212RL
QS-212D
S287RL
QS-287D
S330RL
QS-330D
BA-C1 (100-130V/ 50-60 Hz)
BA-C2 (200-250V/ 50-60 Hz)
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-1
@ 16 mJ/cm2
@ 40 mJ/cm2
GPM
L/Min
GPM
L/Min
3.2
4.0
11.0
20.0
29.1
12.3
15.0
41.6
75.7
110
1.5
2.0
4.5
7.7
11.1
5.5
7.5
17.0
29.3
42.0
S1Q-PA
S2Q-PA
S5Q-PA
S8Q-PA
S12Q-PA
Lamp
Watts
Inlet/Outlet
Connection
(Inches)
Cell
(Dia. L)
Dimensions, Inches
Controller
(L W H)
Shipping
Weight
Lbs.
14
17
24
37
39
MNPT
MNPT
MNPT
MNPT
F/1M
2.5 15
2.5 17
2.5 21
2.5 35
3.5 37
19 8.1 2.5
19 8.1 2.5
19 8.1 2.5
19 8.1 2.5
19 8.1 2.5
6
6
6
10
13
Models listed above are 100-130v/50-60Hz. For 200-250v/50-60Hz, add /2 to the end of the part number, example: S2Q-PA/2.
For 12v DC, add /12 to the end of the part number, example: S2Q-PA/12 (Available for S1Q-PA, S2Q-PA, S5Q-PA only)
*Flow Rates listed are dose dependent. 40 mJ/cm2 = NSF/EPA Standard. 16 mJ/cm2 = US Public Health Standard.
Replacement Parts
For System
S1Q-PA
S2Q-PA
S5Q-PA
S8Q-PA
S12Q-PA
UV Lamp
Quartz Sleeve
Model No.
Description
S287RL
S330RL
S463RL
S810RL
S36RL
QS-001
QS-330
QS-463
QS-810
QS-012
OR-212
BA-ICE-S
RN-001
RN-001/2
Technical Information
Note: Microorganisms require varying UV dose levels for destruction. Some of
the common organisms and their corresponding dosage level are shown
below.
Microorganism
Dose
Microorganism
Dose
mJ/cm2
mJ/cm2
E. Coli2
6.6
Influenza Virus1
6.6
1
Cryptosporidium parvum
<10
Shigella dysenteria2
4.2
Giardia lamblia1
<10
Legionella pnuemophila2
3.8
Hepatitis Virus1
8
Salmonella paratyphi2
6.1
1. 2-log reduction
2. 4-log reduction
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-2
SSM-17
SSM-24
SSM-37
SSM-39
Flow Rate*
@ 16 mJ/cm2
GPM
L/Min
4
11
20
29
15.0
41.6
75.7
110.0
@ 40 mJ/cm2
GPM
L/Min
2.0
4.5
7.7
11
7.5
17
29.3
42
Lamp
Watts
Inlet/Outlet
Connection (In.)
17
25
37
39
MNTP
MNTP
MNTP
FNPT/1MNPT
Dimensions
Reactor
(L Dia.)
17.1
22.1
35.6
37.5
2.6
2.6
2.6
2.6
Controller
(LHD)
Shipping
Weight
(Lbs.)
8
8
11
13
Models listed above are 100-130v/50-60Hz. For 200-250v/50-60Hz, add /2 to the end of the part number, example: SSM-17/2
*Flow Rates listed are dose dependent and are stated @ 95% UVT FOL. 40 mJ/cm2 = NSF/EPA Standard. 16 mJ/cm2 = US
Public Health Standard
SSM-17
SSM-24
SSM-37
SSM-39
Part No.
BA-ICE-SM
254NM-S1
254NM-S2
UV Lamp
Quartz Sleeve
S330RL
S463RL
S810RL
S36RL
QS-330
QS-463
QS-810
QS-012
Description
Monitored controller
(100-240v/50-60Hz)
UV Sensor for SSM-17, 24, 37
UV Sensor for SSM-39
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-3
No Monitor
Plus Series
Model
Basic Series
Model
SCM-200
SCM-320
SCM-600
SCM-740
SC-200
SC-320
SC-600
SC-740
Flow Rate*
@ 16
mJ/cm2
@40
mJ/cm2
GPM
L/Min
GPM
L/Min
15
25
60
60
57
95
227
227
6
10
24
30
23
38
91
114
Reactor
Dimensions
(Dia. L)
3.5
3.5
3.5
3.5
17.8
22.8
30.7
39.4
Controller Dimensions
(LWH)
Inlet/Outlet
Connection Size
Lamp
Watts
Shipping
Weight
Lbs.
FNPT/1MNPT
30W
36W
65W
80W
13
17
21
25
1 MNPT
1 MNPT
1.5 MNPT
*Flow Rates listed are dose dependent and are stated @ 95% UVT FOL. 40 mJ/cm2 = NSF/EPA Standard. 16 mJ/cm2 = US Public Health Standard
Note: System Models above are for 110v, USA. To order a different style power cord, add the appropriate number to the end of the model number when
ordering. (Example: SCM-200/2)
European Style: "/2" - European systems are shipped with 2-prong continental European (cee-7/7), 2 pin with ground schuko power cord.
Australian Style (as 3112): "/2A"
UK (bs 1363): "/2B"
Bare Leads: "/2C"
Replacement Parts
For System
SCM-200/SC-200
SCM-320/SC-320
SCM-600/SC-600
SCM-740/SC-740
UV Lamp
S200RL-HO
S320RL-HO
S600RL-HO
S740RL-HO
Quartz Sleeve
QS-200
QS-320
QS-600
QS-740
Model No.
Description
OR-212
RN-001
BA-ICE-C
BA-ICE-CM
254NM-C1
As these systems incorporate Sterilume-HO "high output" UV lamps providing more power and without the incorporation of
Flow-Pace technology as in the Platinum systems, one may experience high ambient water temperatures in extended
periods of no-flow. To solve this issue, a separate temperature management valve 440179 is offered.
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-4
SPV-200
SPV-410
SPV-600
SPV-740
SPV-950
Flow Rate*
GPM
L/Min
2.6
6.0
8.0
12.0
15.0
9.8
22.7
30.3
45.4
56.8
Lamp
Watts
Inlet/Outlet Connection
30
36
45
65
80
MNPT
FNPT, 1 MNPT
FNPT, 1 MNPT
FNPT, 1 MNPT
FNPT, 1 MNPT
Dimensions, Inches
Chamber (L D)
Controller
(L W H)
17.8 3.5
26.0 3.5
30.7 3.5
39.4 3.5
44.5 3.5
10.75 4.5 2
10.75 4.5 2
10.75 4.5 2
10.75 4.5 2
10.75 4.5 2
Shipping
Weight Lbs.
13
19
21
25
30
Note: Models listed above are 90-265v/50-60Hz w/ STD North American 3 Prong Grounded Power Cord. For other power cord type, use
appropriate suffix below:
Continental European 2-pin power = /2,
UK 3 Prong Grounded= /2B
Australian 3 prong grounded = /2A
No Connector Bare Leads = /NC
Example: SPV1.5/2B = British Power Cord
*Flow rates stated as determined by NSF Standard 55 testing. (40 mJ/cm @ UVT >75% @ fail-safe point)
Please note that the NSF/ANSI Certified systems above contain a flow restrictor to limit the flow at the certified level.
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-5
SP320-HO
SP410-HO
SP600-HO
SP740-HO
SP950-HO
@ 16
GPM
mJ/cm2
34
45
60
60
60
L/Min
@ 40
GPM
128.7
170.3
227.1
227.1
227.1
13
18
26
31
39
mJ/cm2
L/Min
49.2
68.1
98.4
117.3
147.6
Lamp
Watts
36
45
65
80
100
Inlet/Outlet
Connection, (Inches)
MNPT, 1 FNPT
1 MNPT
1 MNPT
1.5 MNPT
1.5 MNPT
Dimensions, Inches
Chamber
(L D)
Controller
(L W H)
22.8 3.5
26.0 3.5
30.7 3.5
39.4 3.5
44.5 3.5
11 4.5 2
11 4.5 2
11 4.5 2
11 4.5 2
11 4.5 2
Shipping
Weight
Lbs.
15
17
19
24
29
Note: Models listed above are 90-265v/50-60Hz with Standard North American 3 Prong Grounded Power Cord. For other power cord type,
use appropriate suffix: Continental European 2-pin power = /2, UK 3 Prong Grounded= /2B Australian 3 prong grounded = /2A No
Connector Bare Leads = NC. Example: SP100-HO/2B = British Power Cord.
*Flow rates and dose stated at 95% UVT10
Replacement Parts
For System
UV Lamp, Sterilume
Quartz Sleeve
SP320-HO
SP410-HO & SPV-410
SP600-HO & SPV-600
SP740-HO & SPV-740
SP950-HO & SPV-950
S320RL-HO
S410RL-HO
S600RL-HO
S740RL-HO
S950RL-HO
QS-320
QS-410
QS-600
QS-740
QS-950
Part Number
For System
SPC-ICE-HO
254NM-FP2
254NM-FP1
OR-12N
RN-001
OR-212
SP008
410076
ALL
ALL SPV
ALL HO
ALL
ALL
ALL
ALL
ALL
Description
Controller, Platinum Ice
UV Sensor Assembly, Flow-Pace 254nm for NSF Certified Systems, w/3 Sensor Cable
UV Sensor Assembly, Flow-Pace 254nm for Non-Validated Systems, w/3 Sensor Cable
O-Ring for Sensor Assembly
Aluminum Retaining Nut
O-Ring for Quartz Sleeve/Aluminum Nuts
Quartz Sleeve Spring
3 Clamp
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-6
Controls
Operating Parameters
Model
No.
Description
SV50
S80
SM80
Flow Rate*
@ 30mJ/cm2
GPM
L/Min
N/A
80
80
303
303
@ 40 mJ/cm2
GPM
L/Min
50
50
50
189
189
189
Lamp
Watts
Inlet/Outlet
Connection
(Inches)
200
200
200
2 MNPT
2 MNPT
2 MNPT
Dimensions, Inches
Cell
(Dia. L)
Controller
(L W H)
4 41
4 41
4 41
13 6.5
13 6.5
13 6.5
Shipping
Weight
Lbs.
15
15
15
*Flow Rates listed are dose dependent. 40 mJ/cm2 = NSF/EPA Standard. 30 mJ/cm2 = UV Industry Standard.
Flow for SV50 stated at 85% UVT and End of Lamp Life; Flow for S80 & SM80 shown at 95% UVT and End of Lamp Life.
Description
S37RL-AM
QS-37
602988
440256-R
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-7
Visual Power-On
Audible/Visual Alarm
Visual Lamp Life Remaining
Total Running Time Display
Model No.
SHF-140
SHF-180
SHFM-140
SHFM-180
254nm UV Sensor
Solenoid Valve Output
40-20mA Signal Output
Description
Flow Rate*
Basic HF UV System
HF System with UV
Monitor & Alarm Output
@ 16mJ/cm2
GPM
m3/hr
@ 40 mJ/cm2
GPM
m3/hr
268
343
268
343
107
137
107
137
61
78
61
78
24
31
24
31
Power
Consumption
350W
440W
350W
440W
Dimensions, Inches
Chamber
Controller
34614
42.3614
34614
42.3614
18208
18208
18208
18208
# of
Lamps
4
4
4
4
*Flow Rates listed are dose dependent. 40 mJ/cm2 = NSF/EPA Standard. 16 mJ/cm2 = US Public Health Standard.
SHF-140, SHFM-140
SHF-180, SHFM-180
Qty. Per
System
UV Lamp
Quartz
Sleeve
4
4
SHO740/4C-RL
SHO950/4C-RL
QS-012
QS-950
Part Number
For System(s)
Description
RN-001
440238
410867
BA-ICE-HF
BA-ICE-M-HF
260192-R
260198-R
260193-R
254NM-HF
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-8
S1Q-DWS
S2Q-DWS
S5Q-DWS
Flow Rate*
@ 16 mJ/cm2
@ 40 mJ/cm2
GPM
L/Min
GPM
L/Min
3.2
4.0
11.0
12.3
15.0
41.6
1.5
2.0
4.5
Lamp Watts
Length
14
17
24
16.5
15.5
20.5
5.5
7.5
17.0
Dimension, Inches
Width
Height
5.9
5.9
5.9
13.8
15.0
28.0
Cell Dia.
Weight
(Lbs.)
2.5
2.5
2.5
15
17
21
*Flow Rates listed are dose dependent. 40 mJ/cm2 = NSF/EPA Standard. 16 mJ/cm2 = US Public Health Standard.
Models listed above are 100-130v/50-60Hz. For 200-250v/50-60Hz with European (CEE 7/7) cord, add /2 to the end of the part number, example: S2Q-DWS/2.
*Models S5Q-DWS and S5Q-DWS/2 come with two (2) 20 slimline filter housings.
**For systems with the addition of a flow control meter including automatic shut-off, add -M to the end of the part no. Example: S1Q-DWS-M. Available for
S1Q-DWS and S2Q-DWS only.
Replacement Parts
For Systems
UV Lamp
Quartz Sleeve
Ballast Model
Sediment Cartridge
Carbon Cartridge
S1Q-DWS
S2Q-DWS
S5Q-DWS
S287RL
S330RL
S463RL
QS-001
QS-330
QS-463
BA-ICE-1F
BA-ICE-1F
BA-ICE-1F
H-F1005CF
H-F1005CF
H-F2005STR
H-F2510AC
H-F2510AC
H-F2520AC
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-9
Commercial UV Systems
NeoTech 2 Chamber Series 35 to 65 GPM
Industry Applications
Pharmaceutical
Micro-electronics
Medical Sciences
Water Remediation
Hospitality
Applications Include
Disinfection
TOC Reduction
Chlorine and Chloramines Removal
Ozone Destruction
Ultrapure Water Disinfection
Our patented flow chamber design brings unparalleled performance in a compact size. This highly efficient
reaction chamber saves thousands of dollars in capital and operation costs with superior disinfection capabilities
and outstanding TOC reduction performance. Our products are made from the highest quality materials,
exceeding the rigorous demands required for industrial grade equipment.
D222
D228
D238
1
35
50
65
8
11
15
9.7
14.9
18.1
Operating
Power Watts
2.2
3.2
4.2
2
85
100
125
Pressure Drop2
PSI
NPM
Length
Height
Depth
4
10
20
27.6k
68.9k
137.9k
23.6
29.6
39.6
8.2
8.2
8.2
6.3
6.3
6.3
Weight3
(Lbs)
30
33
42
Replacement Parts
Replacement Lamps, Quartz Sleeves & Light Traps
For System
Light Kit
Part No.
Description
D222
D228
D238
LK-22
LK-28
LK-38
QSK-22
QSK-28
QSK-38
UVLTK-2-S
UVLTK-2-S
UVLTK-2-S
UVIM-3
CK2-1
CU-4-1
UV Intensity Monitor
Cleaning Kit for UVS2 Systems
Controller, 1 UV unit control (can be
expanded to control up to 4 systems)
Ballast, Electronic, 120 VAC, 50-60 Hz
Ballast, Electronic, 240 VAC, 50-60 Hz
Ballast, Electronic, 240 VAC, 50-60 Hz, 4-wire
BK-120
BK-240
BK-240-ENT
4 Up
Page 10-10
Commercial UV Systems
NeoTech 3 Chamber Series 100 to 225 GPM
Industry Applications
Pharmaceutical
Beverage
Municipal Drinking Water
Food Processing
Water Remediation
Waste Water
Hospitality
Applications Include
Disinfection
Chlorine and Chloramines Removal
Ozone Destruction
Our patented flow chamber design brings unparalleled performance in a compact size. This highly efficient
reaction chamber saves thousands of dollars in capital and operation costs with superior disinfection
performance capabilities using just a single HOLP Amalgam lamp. Our products are made from the highest
quality materials, exceeding the rigorous demands required for industrial grade equipment.
D322
D328
D338
100
150
225
23
34
50
Operating
Power Watts
PSI
85
100
125
1
2
9.3
Pressure Drop2
NPM
6.9k
13.8k
64.1k
24.1
30.1
40.1
9.0
9.0
9.0
7.3
7.3
7.3
Weight3
(Lbs)
39
43
51
Replacement Parts
Replacement Lamps, Quartz Sleeves & Light Traps
For System
Light Kit
Part No.
Description
D322
D328
D338
LK-22
LK-28
LK-38
QSK-22
QSK-28
QSK-38
UVLTK-3-S
UVLTK-3-S
UVLTK-3-S
UVIM-3
CK3-1
CU-4-1
UV Intensity Monitor
Cleaning Kit for UVS3 Systems
Controller, 1 UV unit control (can be
expanded to control up to 4 systems)
Ballast, Electronic, 120 VAC, 50-60 Hz
Ballast, Electronic, 240 VAC, 50-60 Hz
Ballast, Electronic, 240 VAC, 50-60 Hz, 4-wire
BK-120
BK-240
BK-240-ENT
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-11
Commercial UV Systems
NeoTech 4 Chamber Series 300 to 500 GPM
Industry Applications
Beverage
Food Processing
Municipal Drinking Water
Water Remediation
Waste Water
Hospitality
Applications Include
Disinfection
Chlorine and Chloramines Removal
Ozone Destruction
Our patented flow chamber design brings unparalleled performance in a compact size. This highly efficient
reaction chamber saves thousands of dollars in capital and operation costs, with superior disinfection
performance capabilities using just two HOLP Amalgam lamps. Our products are made from the highest quality
materials, exceeding the rigorous demands required for industrial grade equipment.
D428
D438
300
500
Operating
Power Watts
68
112
160
200
Pressure Drop2
PSI
NPM
8.2
10.9
19.3k
75.2k
30.5
40.5
11.39
11.39
8
8
Weight3
(Lbs)
55
63
Replacement Parts
Replacement Lamps, Quartz Sleeves & Light Traps
For System
D428
D438
Light Kit
LK-28
LK-38
QSK-28
QSK-38
Part No.
Description
UVLTK-4-S
UVLTK-4-S
UVIM-3
CK4-1
CU-4-1
UV Intensity Monitor
Cleaning Kit for UVS3 Systems
Controller, 1 UV unit control (can be
expanded to control up to 4 systems)
Ballast, Electronic, 120 VAC, 50-60 Hz
Ballast, Electronic, 240 VAC, 50-60 Hz
Ballast, Electronic, 240 VAC, 50-60 Hz, 4-wire
BK-120
BK-240
BK-240-ENT
4 Up
Page 10-12
Dose
Bacteria
Agrobacterium tumefaciens
Bacillus anthracis
Bacillus megatherium (vegetative)
Bacillus megatherium (spores)
Bacillus subtilis (vegetative)
Bacillus subtilis (spores)
Clostridium tetani
Corynebacterium diphtheria
Dysentery bacilli (diarrhea)
Escherichia coli (diarrhea)
Legionella bozemanii
Legionella dumoffii
Legionella gormanii
Legionella micdadei
Legionella longbeachae
Legionella pneumophila (legionnaires disease)
Leptospira interrogans (infectious jaundice)
Mycobacterium tuberculosis
Neisseria catarrahalis
Proteus vulgaris
Pseudomonas aeruginosa (laboratory)
Pseudomonas aeruginosa (environmental)
Rhodospirillum rubrum
Salmonella (food poisoning)
Salmonella enteritidis
Name
Dose
Bacteria
8.5
8.7
2.5
2.5
11
58
22
6.5
4.2
6.6
3.5
5.5
4.9
3.1
2.9
3.8
6
10
8.5
6.6
3.9
10.5
6.2
10
7.6
Name
Dose
Algae
6.1
15.2
7
26.4
6.2
4.2
3.4
7
5.8
7
10
5.5
8.8
3.8
6.5
Mold Spores
Aspergillus flavus (yellowish green)
Aspergillus glaucus (bluish green)
Aspergillus nigar (yellowish green)
Mucor ramosissimus (white-grey)
Penicillium digitatum (olive)
Penicillium expansum (olive)
Penicillium roqueforti (green)
Rhizopus nigricans (cheese mold)
99
88
330
35.2
88
22
26.4
220
Chlorella vulgaris
22
Protozoa
Nematode eggs
Paramecium
Giardia lamblia (3-log)
Cryptosporidium (3-log)
92
200
6-10
<10
Viruses
Influenza
Poliovirus (poliomyelitis)
Rotavirus
Tobacco mosaic virus
Bacteriophage (E. Coli)
Hepatitis
6.6
7
24
440
6.6
8
Yeast
Bakers yeast
Brewers yeast
Common yeast cake
Saccharomyces ellipsoideus
Saccharomyces sp
8.8
6.6
13.2
13.2
17.6
Typical Installations
Visit us on the web for our complete product line and in-depth technical information. www.appliedmembranes.com
(760) 727-3711 FX: (760) 727-4427
sales@appliedmembranes.com
ARE TRADEMARKS OF APPLIED MEMBRANES, INC. 2012
Page 10-13