Air-Cooled Liquid Chillers

30XA 252-1702
Nominal cooling capacity 270-1700 kW

The Aquaforce liquid chillers are the premium solution for


industrial and commercial applications where installers,
consultants and building owners require optimal
performances and maximum quality.
The Aquaforce liquid chillers are designed to meet current
and future requirements in terms of energy efficiency and
operating sound levels. They use the best technologies
available today:
- Twin-rotor screw compressors with a variable capacity
valve.
- Single refrigerant R134a.
- Low-noise generation IV Flying Bird fans made of
composite material.
- Aluminium micro-channel heat exchangers (MCHX).
- Touch-screen Pro-Dialog control system.
To meet to all environmental and economic requirements, the
Aquaforce is available in two versions:
One offers an extremely low noise level while at the same
time boasting superior energy efficiency.
The other offers unequalled energy efficiency to satisfy the
most stringent demands of building owners wanting to reduce
operating costs to the minimum. This version is also
recommended for applications in geographical zones where
the air temperature is very high.

Features and advantages


Very economical operation
Extremely high full load and part load energy efficiency:
- Eurovent energy efficiency class A, average EER above
3.20 kW/kW (high-efficiency option)
- Average ESEER above 4 kW/kW
- New twin-rotor screw compressor equipped with a highefficiency motor and a variable capacity valve that permits
exact matching of the cooling capacity to the load.
- All aluminium condenser with micro-channels that is more
efficient than a copper/aluminium coil.
- Flooded multi-pipe evaporator to increase the heat
exchange efficiency.
- Electronic expansion device permitting operation at a lower
condensing pressure and improved utilisation of the
evaporator heat exchange surface (superheat control).
- Economizer system with electronic expansion device for
increased cooling capacity.

Low operating sound levels


Compressors
- Discharge dampers integrated in the oil separator (Carrier
patent).
- Silencer on the economiser return line.
- Acoustic compressor and oil separator enclosure reducing
radiated noise.
Condenser section
- Condenser coils in V-shape with an open angle, allowing
quieter air flow across the coil
- Low-noise 4th generation Flying Bird fans, made of a
composite material (Carrier patent) are now even quieter
and do not generate intrusive low-frequency noise
- Rigid fan mounting preventing start-up noise (Carrier
patent)
Easy and fast installation
Integrated hydronic module (option)
- Centrifugal low or high-pressure water pump (as required),
based on the pressure loss of the hydronic installation
- Single or dual pump (as required) with operating time
balancing and automatic changeover to the back-up pump if
a fault develops
- Water filter protecting the water pump against circulating
debris
- High-capacity membrane expansion tank ensures
pressurisation of the water circuit
- Thermal insulation and aluminium protection
- Pressure sensor to check filter pollution and for direct
numerical display of the water flow rate with an estimate of
the instantaneous cooling capacity at the control interface
- Water flow control valve
Simplified electrical connections
- Main disconnect switch with high trip capacity
- Transformer to supply the integrated control circuit
(400/24 V)
Fast commissioning
- Systematic factory operation test before shipment
- Quick-test function for step-by-step verification of the
instruments, expansion devices, fans and compressors

Environmental care
R134a refrigerant
- Refrigerant of the HFC group with zero ozone depletion
potential
- 30% reduction in the refrigerant charge through the use of
micro-channel heat exchangers
Leak-tight refrigerant circuit
- Reduction of leaks as no capillary tubes and flare
connections are used
- Verification of pressure transducers and temperature
sensors without transferring refrigerant charge
- Liquid line service valve for simplified maintenance.

Absolute reliability
Screw compressors
- Industrial-type screw compressors with oversized bearings
and motor cooled by suction gas.
- All compressor components are easily accessible on site
minimising down-time.
- Protection increased by an electronic board.
Air condenser
- All aluminium micro-channel heat exchanger (MCHX)
with a corrosion resistance that is 3.5 times higher than for
a traditional coil. The all aluminium design eliminates the
formation of galvanic currents between aluminium and
copper that cause coil corrosion in saline or corrosive
environments.
Evaporator
- Thermal insulation with aluminium sheet finish for perfect
resistance to external aggression (mechanical and UV
protection).

Auto-adaptive control
- Control algorithm prevents excessive compressor cycling
(Carrier patent)
- Automatic compressor unloading in case of abnormally
high condensing pressure. If condenser coil fouling or fan
failure occurs, the Aquaforce continues to operate, but at
reduced capacity.
Exceptional endurance tests
- Partnerships with specialised laboratories and use of limit
simulation tools (finite element calculation) for the design
of critical components.
- Transport simulation test in the laboratory on a vibrating
table. The test is based on a military standard and
equivalent to 4000 km by truck.
- Salt mist corrosion resistance test in the laboratory for
increased corrosion resistance.

Pro-Dialog control
Pro-Dialog combines intelligence with operating simplicity.
The control constantly monitors all machine parameters and
precisely manages the operation of compressors, electronic
expansion devices, fans and of the evaporator water pump for
optimum energy efficiency.

Energy management
- Internal time schedule clock: controls chiller on/off times
and operation at a second set-point
- Set-point reset based on the outside air temperature or the
return water temperature
- Master/slave control of two chillers operating in parallel
with operating time equalisation and automatic change-over
in case of a unit fault.
Ease-of-use
- User interface with large touch screen (120 x 99 mm) for
intuitive access to the operating parameters. The
information is in clear text and can be displayed in local
language (please contact your distributor).

Remote management (standard)


Aquaforce is equipped with an RS485 serial port that offers
multiple remote control, monitoring and diagnostic
possibilities. Carrier offers a vast choice of control products,
specially designed to control, manage and supervise the
operation of an air conditioning system. Please consult your
Carrier representative for more information.
Aquaforce also communicates with other building
management systems via optional communication gateways.
A connection terminal allows remote control of the
Aquaforce by wired cable:
- Start/stop: opening of this contact will shut down the unit
- Dual set-point: closing of this contact activates a second
set-point (example: unoccupied mode)
- Demand limit: closing of this contact limits the maximum
chiller capacity to a predefined value
- Heat reclaim (option): closing of this contact allows heat
reclaim mode operation
- Water pump 1 and 2 control*: these outputs control the
contactors of one or two evaporator water pumps
- Water pump on reversal*: these contacts are used to detect
a water pump operation fault and automatically change over
to the other pump
- Operation indication: this volt-free contact indicates that
the chiller is operating (cooling load) or that it is ready to
operate (no cooling load)
- Alert indication: this volt-free contact indicates the
necessity to carry out a maintenance operation or the
presence of a minor fault
- Alarm indication: this volt-free contact indicates the
presence of a major fault that has led to the shut-down of
one or several refrigerant circuits
* not available for units with the hydronic module option

Remote management (EMM option)


The Energy Management Module offers extended remote
control possibilities:
- Room temperature: permits set-point reset based on the
building indoor air temperature (with Carrier thermostat)
- Set point reset: ensures reset of the cooling set-point based
on a 4-20 mA or 0-5 V signal
- Demand limit: permits limitation of the maximum chiller
power or current based on a 0-10 V signal
- Demand limit 1 and 2: closing of these contacts limits the
maximum chiller power or current to two predefined values

- User safety: this contact can be used for any customer


safety loop; opening of the contact generates a specific
alarm
- Ice storage end: when ice storage has finished, this input
permits return to the second set-point (unoccupied mode)
- Time schedule override: closing of this contact cancels the
time schedule effects
- Out of service: this signal indicates that the chiller is
completely out of service
- Chiller capacity: this analogue output (0-10 V) gives an
immediate indication of the chiller capacity

New generation 06T screw compressor

The new generation of the Carrier 06T screw compressors


benefits from Carriers long experience in the development of
twin-rotor screw compressors. The compressor is equipped
with bearings with oversized rollers, oil pressure lubricated
for reliable and durable operation, even at maximum load.
A variable control valve controlled by the oil pressure
permits infinitely variable cooling capacity. This system
allows optimal adjustment of the compressor cooling
capacity and ensures exceptionally high stability of the
chilled water leaving temperature.

Among the other advantages: if a fault occurs e.g. if the


condenser is fouled or at very high outside temperature, the
compressor does not switch off, but continues operation with
a reduced capacity (unloaded mode).
The compressor is equipped with a separate oil separator that
minimises the amount of oil in circulation in the refrigerant
circuit and with its integrated silencer considerably reduces
discharge gas pulsations for much quieter operation.

All aluminium micro-channel heat exchanger (MCHX)

Already utilised in the automobile and aeronautical industries


for many years, the MCHX used in the Aquaforce is entirely
made of aluminium. This one-piece concept significantly
increases its corrosion resistance by eliminating the galvanic
currents that are created when two different metals (copper
and aluminium) come into contact in traditional heat
exchangers. Unlike traditional heat exchangers the MCHX
heat exchanger can be used in moderate marine and urban
environments.

From an energy efficiency point-of-view the MCHX heat


exchanger is approximately 10% more efficient than a
traditional coil and allows a 30% reduction in the amount of
refrigerant used in the chiller. The low thickness of the
MCHX reduces air pressure losses by 50% and makes it less
susceptible to fouling (e.g. by sand) than a traditional coil.
Cleaning of the MCHX heat exchanger is very fast using a
high-pressure washer.

Pro-Dialog operator interface with touch-screen

The Aquaforce operator interface is very user-friendly. It is a


large-format touch-screen, and the information is easily
accessible: clear text in the selected language allows

consultation of all operating parameters. Up to eight screens


can be personalised.

Options and accessories


Options
Corrosion protection,
traditional coils
Corrosion protection,
traditional coils
Low-temperature glycol
solution

No.
2B

Very low-temperature
glycol solution

IP 54 control box
Tropical applications

20A
22

Description
Factory application of Blygold Polual treatment
on the copper/aluminium coils
Fins made of pre-treated aluminium
(polyurethane and epoxy)
Low-temperature chilled-water production down to
-6C with ethylene glycol and -3C with propylene
glycol
Low-temperature chilled-water production down to
-12C with ethylene glycol (limited to -10C for
certain sizes) and -8C with propylene glycol
(limited to -6C for certain sizes)
Increased leak tightness of control boxes
Unit control box suitable for tropical applications

Grilles

23

Metallic grilles on the unit front, rear and sides

Winter operation

28

Fan speed control via frequency converter

Evaporator frost protection

41A

Resistance heater on the evaporator

Evaporator and hydronic


module frost protection
Heat reclaim

41B

3A
5

Advantages
Improved corrosion resistance, recommended
for industrial, rural and severe marine environments
Improved corrosion resistance, recommended for
moderate marine and urban environments
Covers specific applications such as ice storage
and industrial processes

Use
30XA 252-1702

Covers specific applications such as ice storage


and industrial processes

30XA 252-1702

Increased control box protection


Reduced relative humidity in the control box for
operation in tropical environments (hot and humid)
Enhanced aesthetics, protection against intrusion
to the unit interior
Stable unit operation when the air temperature
is between -10C and -20C
Evaporator frost protection down to -20C
outside temperature
Evaporator and hydronic module frost
protection down to -20C outside temperature
Free hot-water production, linked to cold-water
production
Quick and easy installation

30XA 252-1702
30XA 252-1702

30XA 252-1502

Simplified maintenance

30XA 252-1702
30XA 252-602

30XA 252-1702
30XA 252-502

30XA 252-1702
30XA 252-1702

30XA 252-1702
30XA 252-1702
30XA 252-1702

Suction valve

92

Three-pass evaporator

100A

Resistance heater on the evaporator and


the hydronic module
Complete recovery of the heat rejected by the
condenser
Power connection of the machine via one main
supply connection
Shut-off valves on the compressor suction piping,
the economiser line and the compressor discharge
piping
Evaporator with three passes water-side

One-pass evaporator

100C

Evaporator with one pass water-side

21 bar evaporator

104

Reversed water connections


High-pressure single-pump
hydronic module
High-pressure dual-pump
hydronic module
Low-pressure single-pump
hydronic module
Low-pressure dual-pump
hydronic module
Direct-expansion free-cooling
system

107
116B

Reinforced evaporator for expansion of the maximum


water-side service pressure range to 21 bar
Evaporator with reversed water inlet/outlet
See hydronic module chapter

Increased water inlet and outlet pressure losses


on opposite sides
Reduced water inlet and outlet pressure
losses on opposite sides
Covers applications with a high water column
(high buildings)
Simplification of the water piping
Easy and fast installation

116C

See hydronic module chapter

Easy and fast installation, operating safety

30XA 252-502

116F

See hydronic module chapter

Easy and fast installation

30XA 252-502

116G

See hydronic module chapter

Easy and fast installation, operating safety

30XA 252-502

118A

Very economical chilled-water production at low


outdoor temperatures

30XA 252-1002

High energy efficiency

119

Chilled water production without the use of the


compressors, using direct-expansion heat exchange
on the condensers
Improved condenser performance

30XA 252-1702

JBus gateway

148B

BacNet gateway

148C

LON gateway

148D

Energy Management
Module EMM
Unit without enclosure
Traditional coils (Cu/Al)
Traditional coils (Cu/Al)
without slots
Suction piping insulation

156
253
254
255

Energy cost reduction, full load operation


at higher air temperatures
Easy connection by communication bus
to a building management system
Easy connection by communication bus
to a building management system
Easy connection by communication bus
to a building management system
Easy connection by wired connection
to a building management system
More economical
Possibility to add specialised condenser treatment
Recommended for the Middle East, sand storms.
Possibility to add specialised condenser treatment.
Prevents condensation on the suction piping

30XA 252-1702

Low sound level

257

Unit sound power level reduction of -3 dB(A)

30XA 252-1702

Advantages
See option 148B
See option 148C
See option 148D
Ease-of-installation
Easy connection by wired connection to
a building management system
Optimised operation of two chillers connected
in parallel with operating time balancing.

Use
See option 148B
See option 148C
See option 148D
30XA 252-1702

Absorption of vibrations, linked to the unit


operation (essentially compressor)

30XA 252-1702

50

Single power connection point 81

256

Two-directional communications board,


complies with JBus protocol
Two-directional communications board,
complies with BacNet protocol
Two-directional communications board,
complies with LON protocol
See chapter Energy Management Module
Compressors not equipped with acoustic enclosure
Coils made of copper tubes with aluminium fins
Coils made of copper tubes with aluminium fins
without slots
Thermal insulation of the suction piping with flexible,
anti-UV insulant
Acoustical insulation of certain unit refrigerant circuit
components (suction, evaporator and economiser
piping)

Accessories
CCN JBus gateway
CCN BacNet gateway
CCN LON Talk gateway
Connection sleeve
Energy Management Module EMM

Description
See option 148B
See option 148C
See option 148D
Piping to be welded with Victaulic connection
See controls manual

Lead-lag kit

Supplementary water outlet temperature sensor kit,


field-installed, allows master/slave operation of two
chillers connected in parallel
Elastomeric anti-vibration mountings for each unit
weight distribution point

Anti-vibration mountings

30XA 252-502
30XA 252-1002

30XA 252-1002
30XA 252-1702

30XA 252-1702
30XA 252-1702
30XA 252-1702
30XA 252-1702
30XA 252-1702
30XA 252-1702
30XA 252-1702

30XA 252-1702
30XA 252-1502

Hydronic module (option)


2
9

C
15

16

17

13

9
7

10

12

16

17

11

9
14

18
Typical hydronic circuit diagram
Legend

A
B
C
D
1
2
3
4
5
6
7
8
9

Components of unit and hydronic module


Pressure sensor (A-B = p evaporator)
Pressure sensor
Pressure sensor (C-D = p water filter)
Pressure sensor
Victaulic screen filter
Expansion tank
Safety valve
Available pressure pump
Drain valve
Water flow control valve
Evaporator
Evaporator defrost heater (option)
Hydronic module defrost heater

10
11
12
13
14

Air vent (evaporator)


Water purge (evaporator)
Expansion compensator (flexible connections)
Flow switch
Water temperature sensor

15
16
17
18

System components
Air vent
Flexible connection
Shut-down valves
Charge valve

--- Hydronic module (option)

Low-pressure pump (hydronic module option)

High-pressure pump (hydronic module option)

Available static pressure, kPa

Available static pressure, kPa

Available static system pressure

Water flow rate, l/s

Water flow rate, l/s

Total heat reclaim (option)


Suitable for heating, domestic hot water preparation,
agriculture and food industry, industrial processes and other
hot-water requirements.
With the total heat reclaim option it is possible to reduce the
energy consumption bill considerably compared to
conventional heating equipment such as fossil fuel boilers or
electric water tanks.

Operating principle
If hot water production is required, the compressor discharge
gases are directed towards the heat reclaim condenser. The
refrigerant releases its heat to the hot water that leaves the
condenser at a temperature of up to 60C. In this way 100%
of the heat rejected by the liquid chiller can be used to
produce hot water. When the demand for heat is satisfied, the
hot gas is again directed towards the air condenser where the
heat is rejected to the outside air by the fans. Hot water
temperature control is ensured by the chiller Pro-Dialog
control that independently controls the reclaim operation of
each refrigerant circuit.
Note: Heat reclaim is only possible, if the unit produces cold
water at the same time.

Physical data
These are the same as for the standard unit except:
30XA heat reclaim mode

252

302

352

402

452

502

602

702

752

802

852

902

1002

Cooling capacity*
Heating capacity in heat reclaim mode*
Total power input (unit)*

kW
kW
kW

261
336
82

291
373
90

311
401
99

379
481
113

438
554
128

493
620
140

603
760
172

665
832
183

707
894
206

775
974
219

814
1027
234

875
1105
253

971
1229
283

Total energy efficiency ratio (EER/COP)

kW/kW

3.16/
4.07

3.22/
4.13

3.15/
4.06

3.36/
4.27

3.40/
4.31

3.53/
4.46

3.52/
4.44

3.63/
4.55

3.43/
4.35

3.53/
4.45

3.48/
4.40

3.45/
4.38

3.42/
4.35

Operating weight**

kg

4230

4270

4280

5260

5380

5880

7000

7100

7470

7680

8320

8670

9280

Refrigerant charge
Circuit A
Circuit B

kg
kg

36
38

37
38

37
39

53
37

54.5
39

62
39

62
62

62
66

70
62

74
69

77
68

74
77

96
94

68

68

55+55 55+55 55+68 55+68 55+68 68+68 68+68

4
106

4
106

4
106

Heat reclaim condenser


Water volume
Water connections
Diameter
Outside diameter

l
in
mm

Flooded multi-pipe condenser


38
38
38
55
Victaulic
3 1/2 3 1/2 3 1/2 4
93
93
93
106

4
106

4
106

4
106

4
106

4
106

4
106

* Entering and leaving water temperature: evaporator 12C/7C; heat reclaim condenser: 40C/45C
** Weights are for guidance only

DX free cooling system (option)


The DX free cooling option permits significant energy
savings for all applications that require cooling in winter.
In the free cooling mode the compressors are stopped and
only the fan and cooling micro-pump are running.
The changeover from compressor cooling mode to free
cooling mode is automatically controlled by the Pro-Dialog
control, based on the chiller heat load and the temperature
difference between chilled water and ambient air.
Important: In order to optimise chiller performances, it is
recommended to use the leaving water set point reset
function.
Operating principle
When the chilled water-air temperature difference exceeds a
threshold value, the Pro-Dialog control carries out a
comparison between the instantaneous chiller cooling
capacity and the available free cooling capacity. If the
operating conditions allow free cooling operation, the
compressors are stopped, a set of valves on the suction piping
connects the evaporator with the condenser, allowing the
migration of the refrigerant vapours to the condenser.
The refrigerant condenses in the condenser coils, and the
cooling micro-pump transports the liquid to the evaporator.
The cooling capacity in free cooling mode is controlled by
the opening of the electronic expansion valve (EXV).
Operation in combined FC (free-cooling) and MC (mechanical cooling) mode is possible in the two independent
refrigerant circuits. This can optimise the free-cooling
operations and at the same time ensures that the cooling
requirements of the system are met.

Advantages of the DX free cooling system


Operation without glycol
Unlike traditional hydronic free-cooling systems that require
the use of a glycol solution, the Aquaforce DX free cooling
chiller works with pure water. The evaporator is protected
against frost down to -20C by an electric resistance heater
(option).
Low water pressure losses
The Aquaforce DX free cooling chiller does not include a
three-way valve nor free cooling coils connected in series
with the evaporator. The Aquaforce free cooling chiller has
the same water pressure losses as a standard chiller.
Weight and dimensions gain
- The DX free cooling option has practically no impact on
the weight of the liquid chiller.
- The Aquaforce free cooling chiller has the same
dimensions as a standard chiller.
Increased energy efficiency
- In free cooling mode only the fans and the cooling micropump run. At an air-water temperature difference of 10 K
for example the average chiller energy efficiency (EER) is
23 (kW/kW).
- In the mechanical cooling mode chiller thermal and energy
performances are not reduced by the use of a water-glycol
solution.
- As the pressure losses of the water circuit are low, the water
pumps use less energy.

Cooling capacities
30XA 252-1002 in free-cooling mode
LWT

Condenser entering air temperature, C


EER

Cap
(C) kW
FC mode:
Circuit 1: FC
Circuit 2: FC
Combined mode:
Circuit 1: MC
Circuit 2: FC
MC mode:
Circuit 1: MC
Circuit 2: MC

Delta T (K)
Legend:
MC
Mechanical cooling (compressors)
FC
Free cooling
Delta T Difference between the leaving water temperature and the entering air temperaure (K)

252 10
302
352
402
452
502
602
702
752
802
852
902
1002

146
146
146
188
191
214
260
280
282
282
326
330
370

Legend
LWT
Cap kW
Unit kW
EER kW/kW

-5

-10

Unit
kW

EER
Cap
kW/kW kW

Unit
kW

EER
Cap
kW/kW kW

Unit
kW

EER
kW/kW

6
6
6
8
8
9
11
12
12
12
14
14
15

24.3
24.5
24.6
23.1
24
24
24
23.4
24.1
23.6
23.4
23.9
24.1

6
6
6
8
8
9
11
12
12
12
14
14
15

30.8
31
31
31.9
33.2
33.2
34.3
34.1
35.1
34.3
34.1
34.7
35

6
6
6
8
8
9
11
12
12
12
14
14
16

31
31.3
31.3
33.9
35.4
35.5
37.8
37.6
38.7
37.8
37.6
38.3
38.6

186
186
186
261
266
299
382
412
414
412
480
485
544

189
190
189
281
286
323
425
459
461
459
534
540
605

Leaving water temperature


Cooling capacity
Unit power input (compressors, fans, control)
Energy efficiency ratio

Operating limits
Freecooling mode

Mechanical
cooling mode
(compressors)

Minimum leaving water temperature

3.3

3.3

Maximum leaving water temperature

25

15.6

Minimum entering air temperature

-20

-20*

Maximum entering air temperature

20

55

Evaporator water temperature, C

Condenser air temperature, C

* For operation at an air temperature below -10C option 28 (winter operation) is required.

Physical data
30XA

252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702

Nominal cooling capacity*


Standard unit
kW 268
Option 119***
kW 274

293
300

320
326

382
393

437
451

492
508

605
616

653
677

706
726

764
792

802
838

869
899

952
1000

Operating weight**
Standard unit and
option 119***
kg

3840 3880 3920 4780 4850 5330 6260 6410 6710 7010 7560 7860 8440

Option 254***

4160 4190 4710 5190 5260 5830 6870 7030 7820 8140 8260 9010 9260

kg

1116
1147

1216
1247

1297
1354

1382
1442

1426
1468

1478
1523

1605
1675

10440 10880 11260 11620 4250/


8380
11470 11890 12250 12640 4650/
9180

4250/
8530
4650/
9340

7560/
7560
8270/
8270

Refrigerant
R134a
Standard unit and option 119***
Circuit A
kg
36
37
Circuit B
kg
38
38
Circuit C
kg
Circuit D
kg
-

37
39
-

53
37
-

55
39
-

62
39
-

62
62
-

62
66
-

70
62
-

70
57
-

77
66
-

70
75
-

80
84
-

69
66
100
-

85
66
100
-

87
68
100
-

87
80
96
-

100
85
100
-

92
95
100
-

77
66
77
66

Option 254***
Circuit A
Circuit B
Circuit C
Circuit D

70
56
-

85
56
-

85
56
-

102
56
-

102
88
-

100
95
-

129
88
-

112
95
-

130
95
-

129
103
-

140
129
-

102
92
135
-

112
92
135
-

112
92
135
-

112
98
122
-

140
103
135
-

140
129
135
-

130
95
130
95

06T semi-hermetic screw compressors, 50 r/s


1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-

1
1
-

1
1
-

1
1
-

1
1
-

1
1
-

1
1
1
-

1
1
1
-

1
1
1
-

1
1
1
-

1
1
1
-

1
1
1
-

1
1
1
1

15

15

15

15

15

15

10

10

10

10

10

10

12
12
13

12
12
13

14
14
14

14
14
15

16
16
16

19
19
19

20
20
20

20
20
20

20
20
20

24
24
24

24
24
24

28
28
28

kg
kg
kg
kg

Compressors
Circuit A
Circuit B
Circuit C
Circuit D
Minimum capacity

60
64
-

64
64
-

15

15

15

15

15

15

15

Control

PRO-DIALOG, electronic expansion valve (EXV)

Condensers

Aluminium micro-channel heat exchanger

Fans
Quantity
Standard unit
Option 119***
Option 254***
Standard total air flow l/s
Standard speed
r/s

Axial Flying Bird 4 with rotating shroud

Evaporator
Water content
l
Maximum pressure**** kPa

6
6
6

6
6
6

6
6
7

8
8
8

8
8
8

9
9
9

11
11
11

12
12
12

20500 20500 20500 27333 27333 30750 37583 41000 41000 41000 47833 47833 54667

64917

68333

68333

68333

82000

82000

95667

11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7

11.7

11.7

11.7

11.7

11.7

11.7

11.7

Flooded multi-pipe type


58
61
61
66
70
77
79
94
98
119 119 130 140
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

168
1000

182
1000

203
1000

224
1000

230
1000

240
1000

240
1000

Water connections
Victaulic
Without hydronic module, inlet/outlet
in
5
5
5
5
5
5
5
6
6
6
6
6
8
6
6
6
6/8
6/8
6/8
6
Diameter
Outside diameter
mm 141.3 141.3 141.3 141.3 141.3 141.3 141.3 168.3 168.3 168.3 168.3 168.3 219.1 168.3 168.3 168.3 168.3/ 168.3/ 168.3/ 168.3
219.3 219.3 219.3
With hydronic module (option), inlet/outlet
Diameter
in
4
4
4
5
5
Outside diameter
mm 114.3 114.3 114.3 139.7 139.7
Expansion tank
volume
l
50
50
50
50
50
Max. water-side operating pressure with hydronic module
kPa 400 400 400 400 400

5
139.7 -

80

400

Legend:
* Nominal conditions: evaporator entering/leaving water temperature = 12C/7C. Outdoor air temperature = 35C, evaporator fouling factor = 0.000018 m2 K/W
** Weights are guidelines only. The refrigerant charge is also given on the unit nameplate.
*** Options: 119 = high energy efficiency; 254 = traditional Cu/Al coils.
**** Max. water-side operating pressure without hydronic module
Weight and diameters of connection modules 1 and 2 for sizes 1402 to 1702.
Note:
Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
Option 119 (high energy efficiency can be used together with options 254 and 255.
Contact your Carrier representative to obtain the performances

Electrical data
30XA
Power circuit
Nominal power
supply
Voltage range

252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702

V-ph-Hz
V

400-3-50
360-440

Maximum supply cable section


2x240 2x240 2x240 2x240 2x240 2x240 4x240 4x240 4x240 4x240 4x240 6x240 6x240 4x240 4x240 4x240 6x240 6x240 6x240 4x240
Circuits A + B
mm2
Circuits C + D
mm2
2x240 2x240 2x240 2x240 2x240 2x240 4x240
2
Option 81
mm
8x240 8x240 8x240 8x240 8x240 8x240 Short circuit holding current (TN system)*
Circuits A + B
kA
38
38
38
Circuits C + D
kA
Option 81
kA
Control circuit

38
-

38
-

38
-

50
-

50
-

50
-

50
-

50
-

50
-

50
-

50
50
50

50
50
50

50
50
50

50
50
50

50
50
50

50
50
50

50
50
-

24 V via internal transformer

Standard unit
Maximum start-up current**
Circuits A + B
A
269
Circuits C + D
A
Option 81
A
Nominal start-up current***
Circuits A + B
A
245
Circuits C + D
A
Option 81
A
-

269
-

287
-

402
-

505
-

505
-

574
-

606
-

773
-

803
-

805
-

893
-

941
-

574
587
991

773
587
1079

803
587
1155

891
587
1242

893
587
1248

941
587
1294

805
805
-

245
-

262
-

378
-

480
-

480
-

536
-

562
-

735
-

759
-

761
-

845
-

865
-

536
587
909

735
587
993

759
587
1036

859
587
1156

845
587
1125

865
587
1143

761
761
-

Cosine Phi (maximum)**** 0.88 0.88 0.87 0.88 0.88 0.88 0.88 0.88 0.86 0.86 0.87 0.85 0.86
Cosine Phi (nominal)
0.85 0.85 0.84 0.84 0.86 0.86 0.87 0.87 0.84 0.85 0.85 0.83 0.84

0.88
0.85

0.86
0.84

0.87
0.85

0.85
0.83

0.85
0.83

0.86
0.84

0.87
0.85

Maximum power input


Circuits A + B
kW
Circuits C + D
kW
Option 81
kW

121
-

131
-

141
-

165
-

185
-

204
-

247
-

267
-

293
-

312
-

343
-

359
-

420
-

247
210
457

293
210
503

342
210
552

388
209
597

390
210
600

420
210
630

343
343
-

Nominal unit current draw


Circuits A + B
A
151
Circuits C + D
A
Option 81
A
-

167
-

184
-

210
-

240
-

266
-

322
-

349
-

406
-

431
-

452
-

516
-

556
-

322
278
600

406
278
684

449
278
727

569
292
861

538
278
816

556
278
834

452
452
-

Maximum unit current draw (Un)


Circuits A + B
A
198 215
Circuits C + D
A
Option 81
A
-

233
-

270
-

303
-

335
-

404
-

436
-

492
-

522
-

572
-

611
-

707
-

404
354
758

492
354
845

568
354
922

655
352
1007

661
354
1015

707
354
1061

572
572
-

Maximum unit current draw (Un 10%)****


Circuits A + B
A
208 232 251
Circuits C + D
A
Option 81
A
-

290
-

326
-

360
-

435
-

469
-

529
-

561
-

615
-

657
-

760
-

435
380
815

529
380
909

611
380
991

705
378
1083

711
380
1091

760
380
1141

615
615
-

High energy efficiency version (option 119)


Maximum start-up current**
Circuits A + B
A
274
Circuits C + D
A
Option 81
A
Nominal start-up current***
Circuits A + B
A
246
Circuits C + D
A
Option 81
A
-

274
-

292
-

407
-

510
-

510
-

583
-

616
-

782
-

812
-

815
-

905
-

954
-

583
587
1010

782
587
1099

812
587
1175

901
587
1265

905
587
1275

954
587
1321

815
815
-

246
-

261
-

379
-

479
-

479
-

535
-

561
-

734
-

757
-

760
-

845
-

860
-

535
587
907

734
587
991

757
587
1026

846
587
1124

845
587
1122

860
587
1133

760
760
-

Cosine Phi (maximum)****


Cosine Phi (nominal)

0.88 0.87 0.87 0.88 0.88 0.88 0.88 0.88 0.86 0.86 0.86 0.85 0.86
0.84 0.84 0.83 0.83 0.85 0.85 0.86 0.86 0.84 0.84 0.84 0.82 0.82

0.88
0.84

0.86
0.83

0.87
0.83

0.85
0.83

0.85
0.82

0.86
0.82

0.86
0.84

Maximum power input


Circuits A + B
kW
Circuits C + D
kW
Option 81
kW

126
-

136
-

147
-

172
-

192
-

212
-

257
-

278
-

304
-

323
-

356
-

372
-

435
-

257
217
475

304
217
522

353
217
570

400
216
615

405
217
622

435
217
652

356
356
712

Nominal unit current draw


Circuits A + B
A
151
Circuits C + D
A
Option 81
A
-

167
-

182
-

210
-

237
-

264
-

320
-

346
-

404
-

427
-

446
-

516
-

546
-

320
273
593

404
273
678

439
273
712

537
275
812

535
273
808

546
273
820

446
446
893

Maximum unit current draw (Un)


Circuits A + B
A
208 226
Circuits C + D
A
Option 81
A
-

243
-

284
-

316
-

350
-

423
-

457
-

512
-

542
-

596
-

635
-

734
-

423
367
790

512
367
879

588
367
956

678
364
1041

688
367
1056

734
367
1102

596
596
1191

Maximum unit current draw (Un 10%)****


Circuits A + B
A
219 243 262
Circuits C + D
A
Option 81
A
-

305
-

340
-

376
-

455
-

491
-

551
-

583
-

640
-

683
-

790
-

455
395
850

551
395
946

633
395
1028

729
391
1120

740
395
1135

790
395
1185

640
640
1281

* kA eff: efficiency value: rms for English version


** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at operation with
maximum unit power input.
*** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at standard
Eurovent unit operating conditions: air 35C, water 12/7C
**** Values obtained at operation with maximum unit power input.
Circuit D for size 1702 only
Values obtained at standard Eurovent unit operating conditions: air 35C, water 12/7C
Values obtained at operation with maximum unit power input. Values given on the unit name plate
Notes:
Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50C): 1.9 A for standard unit; 3.6 A for unit with option 119
Start-up current: 8.4 A for standard unit; 20 A for unit with option 119
Power input: 760 W for standard unit; 1650 W for unit with option 119
Unit sizes 30XA 1102 to 1702 have two power connection points (circuits A + B and circuits C + D).

10

Electrical data
Hydronic module (option)*
30XA

252 302 352 402 452 502

Single or dual low-pressure pump


Motor power
kW
2.2 2.2
Power input
kW
2.8 2.8
Maximum current draw A
4.7 4.7

3
3.9
6.4

4
5.1
8.2

5.5 5.5
7.2 7.2
11.7 11.7

Single or dual high-pressure pump


Motor power
kW
4
5.5 5.5 7.5
Power input
kW
5.1 7.2 7.2 9.2
Maximum current draw A
8.2 11.7 11.7 15

11
11
13.2 13.2
21.2 21.2

* Additional power and current

Electrical data notes


30XA 252-1002 units have a single power connection point located
immediately upstream of the two main disconnect switches.
30XA 1102-1702 units have two power connection points located upstream
of the main disconnect switches.
The control box includes:
- One main disconnect switch per circuit
- Starter and motor protection devices for each compressor, the fans and
the pump
- Control devices
Field connections:
All connections to the system and the electrical installations must be in full
accordance with all applicable local codes.
The Carrier 30XA units are designed and built to ensure conformance with
these codes. The recommendations of European standard EN 60 204-1
(corresponds to IEC 60204-1) (machine safety - electrical machine
components - part 1: general regulations) are specifically taken into
account, when designing the electrical equipment.
Notes:
Generally the recommendations of IEC 60364 are accepted as compliance
with the requirements of the installation directives. Conformance with EN
60204 is the best means of ensuring compliance with the Machines
Directive 1.5.1.
Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines.

1. The operating environment for the 30XA units is specified below:


Environment* - Environment as classified in EN 60721 (corresponds to
IEC 60721) :
- outdoor installation*
- ambient temperature range: minimum temperature -20C to +55C,
class 4K4H*
- altitude: lower than or equal to 2000 m
- presence of hard solids, class 4S2 (no significant dust present)
- presence of corrosive and polluting substances, class 4C2 (negligible)
2. Power supply frequency variation: 2 Hz.
3. The neutral (N) line must not be connected directly to the unit (if necessary
use a transformer).
4. Overcurrent protection of the power supply conductors is not provided with
the unit.
5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type
suitable for power interruption in accordance with EN 60947-3 (corresponds
to IEC 60947-3).
6. The units are designed for simplified connection on TN(s) networks
(IEC 60364). For IT networks derived currents may interfere with network
monitoring elements, and it is recommended to create an IT type divider for
the system units that require this and/or a TN type divider for Carrier units.
Please consult the appropriate local organisations to define the monitoring
and protection elements and carry out the electrical installation.
NOTE: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should
be considered, always contact your local Carrier representative.
* The required protection level for this class is IP43B (according to reference
document IEC 60529). All 30XA units are protected to IP44CW and fulfil this
protection condition.

11

Sound levels
30XA

252 302 352 402 452 502 602 702 752 802 852 902 1002 1102 1202 1302 1352 1402 1502 1702

Standard unit
Sound power level*
Sound pressure level at 10 m**

dB(A)
dB(A)

89
57

89
57

89
57

92
60

93
61

93
61

94
62

93
61

95
63

95
63

94
62

96
63

95
63

96
63

96
63

96
63

97
64

97
64

97
64

97
64

Standard unit + option 257


Sound power level*
Sound pressure level at 10 m**

dB(A)
dB(A)

86
54

86
54

86
54

89
57

90
58

90
58

91
59

90
57

92
60

92
59

91
58

93
60

92
59

93
60

93
60

93
60

94
61

94
61

94
61

94
61

High energy efficiency version (option 119)


Sound power level*
dB(A)
94
Sound pressure level at 10 m**
dB(A)
62

94
62

94
62

95
62

95
62

95
62

96
63

96
64

98
65

98
66

98
65

99
66

98
65

99
66

100
67

99
66

100
67

101
68

100
67

101
67

Unit with options 119 + 257


Sound power level*
Sound pressure level at 10 m**

92
60

92
60

94
62

94
62

94
62

95
62

95
62

96
63

96
63

96
63

97
64

97
64

98
65

98
65

98
65

98
62

99
66

99
66

99
65

dB(A)
dB(A)

92
60

* 10-12 W - In accordance with ISO 9614-1 and certified by Eurovent


** Average sound pressure level, unit in a free field on a reflective surface

Part load performances


With the rapid increase in energy costs and the care about
environmental impacts of electricity production, power
consumption of air conditioning equipment has become an
important topic. The energy efficiency of a liquid chiller at
full load is rarely representative of the actual performance of
the units, as on average a chiller works less than 5% of the
time at full load.

The heat load of a building depends on many factors, such


as the outside air temperature, the exposure to the sun and
its occupation.
Consequently it is preferable to use the average energy
efficiency, calculated at several operating points that are
representative for the unit utilisation.

IPLV (in accordance with ARI 550/590-98)


The IPLV (integrated part load value) allows evaluation of
the average energy efficiency based on four operating
conditions defined by the ARI (American Refrigeration
Institute). The IPLV is the average weighted value of the
energy efficiency ratios (EER) at different operating
conditions, weighted by the operating time.

ESEER (in accordance with EUROVENT)


The ESEER (European seasonal energy efficiency ratio)
permits evaluation of the average energy efficiency at part
load, based on four operating conditions defined by Eurovent.
The ESEER is the average value of energy efficiency ratios
(EER) at different operating conditions, weighted by the
operating time.

IPLV (Integrated Part Load Value)

ESEER (European seasonal energy efficiency ratio)

Load
(%)
100
75
50
25

Air temperature
(C)
35
26.7
18.3
12.8

Energy
efficiency
EER1
EER2
EER3
EER4

Operating
time, %
1
42
45
12

Load
(%)
100
75
50
25

IPLV = EER1 x 1% + EER2 x 42% + EER3 x 45% + EER4 x 12%

Air temperature
(C)
35
30
25
20

Energy
efficiency
EER1
EER2
EER3
EER4

Operating
time, %
3
33
41
23

ESEER = EER1 x 3% + EER2 x 33% + EER3 x 41% + EER4 x 23%

Part load performances


30XA (standard) 252
IPLV

12

302

352

402

452

502

602

702

752

802

852

902

1002 1102 1202 1302 1352 1402 1502 1702

kW/kW

4.53

4.63

4.81

4.50

4.58

4.75

4.61

4.67

4.48

4.42

4.46

4.35

4.39

4.64

4.53

4.56

4.35

4.61

4.58

4.31

ESEER kW/kW

4.11

4.20

4.31

4.05

4.07

4.20

4.13

4.21

4.00

3.95

3.93

3.91

3.91

4.11

4.02

4.03

3.83

4.10

4.11

3.86

Operating limits
Evaporator water temperature

Evaporator water flow rate, l/s


C

Water entering temperature at start-up


Water entering temperature during operation
Water leaving temperature during operation

Minimum Maximum

30XA

Minimum

Maximum*

6.8
3.3

252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

3.6
4
4.3
5.3
6
6.7
8.1
8.9
9.6
10.4
11
11.8
13.1
15.1
16.4
17.5
18.8
19.3
19.9
22

37.5
40.5
40.5
34.1
36.9
42
45
56.1
59.1
67.1
67.1
73.9
83.9
87.8
92.9
96.1
107.4
107.4
109.4
107.4

45
21
15

Note
If the leaving water temperature is below 4C, a glycol/water solution or the frost protection
option must be used.

Condenser air temperature


C

Minimum Maximum

Storage

-20

68

Operation
Standard unit
With winter operation option (option 28)
With high energy efficiency option (option 119)**

-10
-20
-10

55*
55*
55*

Note
If the air temperature is below 0C, a glycol/water solution or the frost protection option
must be used.
* Part-load operation
** Recommended for operation above 46C

* The maximum water flow rate corresponds to a pressure drop of 100 kPa.

Operating range

Entering air temperature, C

Legend

Part load from 46C for standard unit, and 50C with option 119.

Operating range, standard unit.

Below 0C air temperature the unit must either be equipped with the
evaporator frost protection option (41A or 41B), or the water loop must be
protected against frost by using a frost protection solution (by the installer).

Operating range, unit equipped with option 28 (winter operation).

Evaporator leaving water temperature, C

13

Dimensions/clearances
30XA 252-352 - MCHX heat exchanger (standard)
30XA 252-302 - Cu/Al heat exchanger (option 254/255)

Legend:
All dimensions are given in mm.

Required clearances for maintenance


and air flow
Recommended space for evaporator
tube removal
Water inlet

Water outlet

Air outlet do not obstruct

30XA 402-452 - MCHX heat exchanger (standard)


30XA 352-452 - Cu/Al heat exchanger (option 254/255)

Power supply connection

Control circuit connection

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

14

Dimensions/clearances
30XA 502 - MCHX heat exchanger (standard)
30XA 502 - Cu/Al heat exchanger (option 254/255)

30XA 602-802 - MCHX heat exchanger (standard)


30XA 602-702 - Cu/Al heat exchanger (option 254/255)

Legend:
All dimensions are given in mm.

Required clearances for maintenance


and air flow
Recommended space for evaporator
tube removal
Water inlet

Water outlet

Air outlet do not obstruct

Power supply connection

Control circuit connection

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

15

Dimensions/clearances
30XA 852-902 - MCHX heat exchanger (standard)
30XA 752-852 - Cu/Al heat exchanger (option 254/255)

Legend:
All dimensions are given in mm.

Required clearances for maintenance


and air flow
Recommended space for evaporator
tube removal
Water inlet

Water outlet

Air outlet do not obstruct

Power supply connection

Control circuit connection

30XA 1002 - MCHX heat exchanger (standard)


30XA 902-1002 - Cu/Al heat exchanger (option 254/255)

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

16

Dimensions/clearances
30XA 1102-1352 - MCHX heat exchanger (standard)
30XA 1102-1352 - Cu/Al heat exchanger (option 254/255)

Legend:
All dimensions are given in mm.
Required clearances for maintenance and air flow
Recommended space for evaporator tube
removal
Water inlet

Water outlet

Air outlet do not obstruct

Power supply connection

Control circuit connection

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.

17

Dimensions/clearances
30XA 1402-1502, module 1/2 - MCHX heat exchanger (standard)
30XA 1402-1502, module 1/2 - Cu/Al heat exchanger (option 254/255)

Module 2

Legend:
All dimensions are given in mm.
Required clearances for maintenance
and air flow
Recommended space for evaporator
tube removal

30XA 1402-1502, module 2/2 - MCHX heat exchanger (standard)


30XA 1402-1502, module 2/2 - Cu/Al heat exchanger (option 254/255)

Water inlet
Water outlet (to be connected to the
water inlet of module 2)
Air outlet do not obstruct

Power supply connection

Control circuit connection

Module 1

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.
Unit sizes 1402-1502 are supplied in two field-assembled modules (connection pipe completion to be done by the installer).

18

Water inlet (to be connected to the


water outlet of module 1)

Dimensions/clearances
30XA 1702, module 1/2 - MCHX heat exchanger (standard)
30XA 1702, module 1/2 - Cu/Al heat exchanger (option 254/255)

Legend:
All dimensions are given in mm.
Required clearances for maintenance
and air flow

Module 2

Recommended space for evaporator


tube removal
Water inlet
Water outlet (to be connected to the
water inlet of module 2)
Air outlet do not obstruct

Power supply connection

Control circuit connection

30XA 1702, module 2/2 - MCHX heat exchanger (standard)


30XA 1702, module 2/2 - Cu/Al heat exchanger (option 254/255)

Water inlet (to be connected to the


water outlet of module 1)

Module 1

NOTE: Drawings are not contractually binding. Before designing an installation, consult the certified dimensional drawings, available on request.
Unit size 1702 is supplied in two field-assembled modules (connection pipe completion to be done by the installer).

19

20

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

CAP
kW
270
297
325
385
442
497
610
659
714
773
810
879
962
1127
1229
1313
1401
1443
1495
1621

COOL
kPa
14
15
18
34
36
36
46
36
37
35
38
36
35
42
44
46
43
46
47
56

30

COOL
l/s
13
15
16
19
22
25
30
33
35
38
40
43
48
56
61
65
69
71
74
80

CAP
kW
280
309
338
398
457
514
632
683
739
802
840
911
998
1167
1273
1362
1454
1496
1550
1678

COMP UNIT
kW
kW
67
72
77
81
83
87
96
102
115
121
127
133
156
164
164
173
186
195
205
214
209
220
235
246
253
265
286
300
320
335
353
368
400
415
373
391
390
408
415
437

25

Air temperature, C

Standard unit - LWT = 6C

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

CAP
kW
262
289
316
373
429
482
591
640
693
751
787
854
935
1094
1194
1276
1362
1401
1452
1575

COOL
kPa
14
14
17
32
35
34
43
34
35
33
36
34
33
40
41
44
41
44
45
53

30

COOL
l/s
13
14
16
18
21
24
29
32
34
37
39
42
46
54
59
63
67
69
72
78

CAP
kW
272
300
329
386
444
499
613
662
717
779
815
885
968
1133
1236
1323
1413
1452
1505
1631

COMP UNIT
kW
kW
66
71
75
80
81
85
95
101
113
119
124
131
153
161
161
170
182
191
201
210
205
216
230
241
248
260
280
295
314
329
345
360
392
407
366
384
382
400
408
429

25

Air temperature, C

Standard unit - LWT = 5C

COMP UNIT
kW
kW
74
78
84
88
91
95
105
112
126
132
139
145
171
179
179
188
203
212
224
233
228
239
257
267
277
289
312
327
350
365
385
400
438
453
408
426
426
444
454
475

COMP UNIT
kW
kW
73
77
82
87
89
93
104
110
124
130
136
143
167
175
176
185
199
208
220
229
224
235
252
262
271
283
307
321
343
358
378
393
429
444
400
418
417
436
446
467

COOL
l/s
13
14
15
18
21
24
29
31
34
37
39
42
46
54
59
63
67
69
71
77

COOL
l/s
12
14
15
18
20
23
28
30
33
36
37
41
45
52
57
61
65
67
69
75

COOL
kPa
14
14
16
32
34
34
43
34
35
32
35
34
33
39
41
43
40
43
44
52

COOL
kPa
13
13
16
30
33
32
41
32
33
31
34
32
31
37
39
41
38
41
42
50

CAP
kW
260
285
311
371
425
478
587
634
687
743
780
845
925
1084
1182
1261
1345
1387
1437
1560

35

CAP
kW
252
277
302
360
413
464
569
616
667
722
757
821
899
1053
1149
1226
1308
1348
1397
1516

35

COMP UNIT
kW
kW
81
86
92
96
100
104
115
121
138
144
152
159
187
195
196
205
222
231
245
254
250
261
281
291
303
315
342
356
383
398
422
437
480
494
446
464
466
484
497
518

COMP UNIT
kW
kW
80
84
90
95
98
102
113
120
136
142
149
156
183
191
192
201
218
227
240
249
245
256
276
286
297
309
335
350
375
390
414
429
470
485
438
455
457
475
488
509

COOL
l/s
12
14
15
18
20
23
28
30
33
35
37
40
44
52
56
60
64
66
68
74

COOL
l/s
12
13
14
17
20
22
27
29
32
34
36
39
43
50
55
58
62
64
67
72

COOL
kPa
13
13
15
30
32
31
40
31
33
30
33
31
31
36
38
40
37
40
41
49

COOL
kPa
12
12
14
28
30
30
38
30
31
29
31
30
29
35
36
38
36
38
39
46

CAP
kW
248
272
295
356
407
457
563
608
658
711
747
810
887
1039
1134
1207
1286
1329
1377
1495

40

CAP
kW
241
263
287
346
396
444
546
590
639
691
726
787
862
1009
1102
1173
1251
1291
1339
1453

40

COMP UNIT
kW
kW
89
93
101
105
109
113
126
132
151
157
167
173
204
212
214
223
243
252
268
277
274
284
308
318
332
344
374
388
419
434
463
478
526
541
489
506
511
529
545
566

COMP UNIT
kW
kW
87
92
99
103
107
111
124
130
149
154
164
170
200
208
211
219
239
248
263
272
269
279
302
312
326
338
367
381
411
426
454
469
516
530
480
497
501
519
535
556

COOL
l/s
12
13
14
17
19
22
27
29
31
34
36
39
42
50
54
57
61
63
66
71

COOL
l/s
11
13
14
16
19
21
26
28
30
33
35
37
41
48
52
56
60
61
64
69

COOL
kPa
12
12
14
28
30
29
37
29
30
28
31
29
28
34
35
37
34
37
38
45

COOL
kPa
11
11
13
26
28
27
35
28
29
27
29
28
27
32
33
35
33
35
36
43

CAP
kW
234
255
276
338
385
431
531
573
615
655
705
735
831
981
1057
1039
956
1200
1258
1401

46

CAP
kW
227
247
268
328
374
419
515
557
605
644
686
737
814
953
1035
1017
922
1191
1252
1367

46

COMP UNIT
kW
kW
99
103
113
117
122
126
140
146
169
175
187
193
228
236
240
248
267
275
290
299
307
317
324
335
368
379
418
432
458
473
453
467
427
441
511
528
544
561
602
622

COMP UNIT
kW
kW
97
102
111
115
120
124
138
144
166
172
183
190
224
231
235
244
267
275
290
298
301
311
333
343
365
377
410
424
455
470
451
466
420
434
518
535
553
571
595
616

COOL
l/s
11
12
13
16
18
21
25
27
29
31
34
35
40
47
50
50
46
57
60
67

COOL
l/s
11
12
13
16
18
20
25
27
29
31
33
35
39
45
49
48
44
57
60
65

COOL
kPa
10
10
12
25
27
26
33
26
27
24
28
24
25
30
31
28
20
31
32
40

COOL
kPa
10
10
12
24
25
25
31
25
26
23
26
25
24
29
30
27
19
30
32
38

Standard unit

Cooling capacities

Legend
LWT
CAP kW
COMP kW
UNIT kW
COOL l/s
COOL kPa

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

COMP UNIT
kW
kW
79
83
90
94
98
102
113
119
136
142
149
156
184
192
193
202
219
228
242
251
247
258
278
288
300
312
338
352
378
393
418
433
477
492
442
460
461
480
491
512

COMP UNIT
kW
kW
75
80
86
90
93
97
107
113
129
134
141
148
174
182
182
191
207
216
228
237
233
243
262
272
282
294
319
333
357
372
393
408
447
462
416
434
434
452
463
484

Leaving water temperature


Cooling capacity
Compressor power input
Unit power input (compressors, fans and control circuit)
Evaporator water flow rate
Evaporator pressure drop

CAP
kW
304
335
366
433
495
557
686
739
799
864
908
983
1077
1261
1374
1466
1561
1612
1672
1815

COOL
kPa
18
18
22
41
44
43
55
43
45
42
46
44
42
50
53
56
52
55
57
68

30

COOL
l/s
15
17
18
21
24
28
34
37
40
43
45
49
53
62
68
73
77
80
83
90

CAP
kW
316
348
381
447
513
578
710
766
829
897
941
1020
1118
1308
1425
1522
1622
1674
1736
1881

COMP UNIT
kW
kW
72
77
82
87
89
94
103
109
124
130
137
143
169
177
177
186
201
210
222
231
226
237
255
265
275
287
310
324
347
362
384
399
437
452
405
423
423
441
450
471

25

Air temperature, C

Standard unit - LWT = 10C

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

CAP
kW
279
306
335
397
455
511
629
679
734
795
834
904
990
1160
1265
1350
1440
1484
1538
1668

COOL
kPa
15
16
19
35
38
38
48
38
39
36
40
38
37
44
46
49
45
48
49
59

30

COOL
l/s
14
15
17
20
22
25
31
34
36
39
41
45
49
57
62
67
71
73
76
82

CAP
kW
289
318
349
410
471
530
651
703
761
825
864
938
1027
1202
1311
1401
1496
1539
1596
1728

COMP UNIT
kW
kW
68
73
78
82
85
89
98
104
117
123
129
136
159
167
167
176
190
198
209
218
213
224
240
250
258
270
292
306
327
342
360
375
409
424
381
399
398
416
424
445

25

Air temperature, C

Standard unit - LWT = 7C

COOL
kPa
16
17
20
38
41
40
52
41
42
39
43
41
39
47
49
52
48
52
53
63

COOL
kPa
14
15
17
33
36
35
45
35
37
34
37
35
34
41
43
45
42
45
46
55

CAP
kW
292
320
348
417
476
535
659
711
768
829
872
943
1034
1213
1321
1406
1496
1548
1606
1745

35

CAP
kW
268
293
320
382
437
492
605
653
706
764
802
869
952
1116
1216
1297
1382
1426
1478
1605

35

COMP UNIT
kW
kW
86
91
99
103
107
111
123
129
148
154
163
170
201
209
211
220
239
248
265
273
270
280
303
314
327
339
369
383
413
428
457
472
521
536
482
500
504
522
536
557

COMP UNIT
kW
kW
82
87
94
98
102
106
117
123
141
147
155
161
190
198
200
208
226
235
250
258
255
265
286
297
309
321
348
363
390
405
430
445
490
504
455
473
475
493
507
528

COOL
l/s
14
15
17
20
23
26
31
34
37
40
42
45
49
58
63
67
71
74
77
83

COOL
l/s
13
14
15
18
21
23
29
31
34
36
38
41
45
53
58
62
66
68
70
77

COOL
kPa
15
16
18
36
38
38
48
38
39
36
40
38
37
44
46
48
44
48
49
59

COOL
kPa
13
13
16
31
33
33
42
33
34
32
35
33
32
38
40
42
39
42
43
51

Performances in accordance with EN 14511.

Application data:
Standard units, refrigerant: R134a
Evaporator temperature rise: 5 K
Evaporator fluid: chilled water
Fouling factor: 0.18 x 10-4 (m2 K)/W

COOL
l/s
15
16
17
21
24
27
33
35
38
41
43
47
51
60
66
70
75
77
80
87

COOL
l/s
13
15
16
19
22
24
30
32
35
38
40
43
47
55
60
64
69
71
73
80

CAP
kW
280
305
331
400
456
512
632
681
736
793
835
903
989
1162
1265
1331
1374
1481
1536
1671

40

CAP
kW
256
279
304
367
419
470
580
626
677
731
769
832
912
1069
1166
1240
1320
1366
1416
1539

40

COMP UNIT
kW
kW
94
99
108
112
118
122
134
140
162
168
179
186
219
227
231
239
261
270
289
298
295
306
331
341
358
370
403
417
451
466
492
507
534
549
527
545
551
569
587
608

COMP UNIT
kW
kW
90
94
103
107
111
115
128
134
154
160
170
176
208
216
218
227
248
256
273
282
279
289
313
324
338
350
381
395
427
441
472
487
537
551
498
516
520
538
555
576

COOL
l/s
13
15
16
19
22
24
30
33
35
38
40
43
47
55
60
64
66
71
73
80

COOL
l/s
12
13
14
17
20
22
28
30
32
35
37
40
43
51
56
59
63
65
68
73

COOL
kPa
14
14
17
33
35
35
45
35
36
33
37
35
34
40
42
43
38
44
45
54

COOL
kPa
12
12
14
29
31
30
39
30
32
29
32
30
30
35
37
39
36
39
39
47

CAP
kW
263
285
309
378
422
483
588
642
599
631
702
674
760
969
990
1023
1047
1135
1186
1455

46

CAP
kW
241
262
284
347
396
444
547
590
625
658
719
741
830
989
1057
1055
990
1174
1222
1429

46

COMP UNIT
kW
kW
104
109
121
125
132
136
149
155
176
182
201
207
239
247
257
266
233
242
248
257
279
289
261
272
299
310
374
388
381
395
404
418
434
448
431
449
459
476
578
598

COMP UNIT
kW
kW
100
105
115
119
125
129
142
148
172
178
190
197
232
240
244
253
267
275
284
293
308
318
321
331
359
370
412
426
448
462
451
465
434
448
485
502
513
530
605
625

COOL
l/s
13
14
15
18
20
23
28
31
29
30
33
32
36
46
47
49
50
54
57
69

COOL
l/s
11
12
14
17
19
21
26
28
30
31
34
35
40
47
50
50
47
56
58
68

COOL
kPa
13
13
15
30
31
31
39
31
25
22
27
20
21
29
27
27
23
27
28
42

COOL
kPa
11
11
13
26
28
27
35
27
27
24
28
25
25
30
31
29
21
29
30
41

Standard unit

Cooling capacities

21

22

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

CAP
kW
276
303
330
395
454
512
619
681
730
797
843
906
1007
1153
1254
1363
1454
1478
1535
1685

COOL
kPa
15
15
18
35
38
38
47
38
39
36
41
38
38
43
45
49
46
48
49
60

30

COOL
l/s
14
15
16
19
22
25
30
34
36
39
42
45
50
57
62
67
72
73
76
83

CAP
kW
286
315
344
407
469
529
640
704
755
824
872
937
1041
1192
1296
1409
1505
1529
1587
1742

COMP UNIT
kW
kW
64
74
71
80
78
87
90
102
105
117
115
129
143
160
151
171
177
196
188
209
192
216
217
241
232
261
261
292
293
326
322
356
355
386
339
379
354
395
384
431

25

Air temperature, C

Unit with option 119 - LWT = 6C

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

CAP
kW
268
294
321
382
440
497
600
660
708
773
818
879
976
1119
1216
1322
1411
1434
1489
1636

COOL
kPa
14
15
17
33
36
36
44
36
37
35
39
36
36
41
43
47
44
45
47
57

30

COOL
l/s
13
15
16
19
22
24
29
32
35
38
40
43
48
55
60
65
70
71
73
80

CAP
kW
277
305
333
395
455
513
620
682
732
799
846
908
1009
1156
1257
1367
1460
1482
1540
1691

COMP UNIT
kW
kW
63
73
70
79
77
86
88
101
103
115
113
127
141
158
148
168
173
193
185
206
189
212
213
237
228
257
257
288
287
320
317
350
348
379
333
373
347
388
377
424

25

Air temperature, C

Unit with option 119 - LWT = 5C

COMP UNIT
kW
kW
71
80
78
87
86
95
98
110
115
127
126
140
157
174
165
185
193
212
206
226
210
233
237
260
253
282
286
316
319
352
352
386
388
419
370
410
386
427
420
466

COMP UNIT
kW
kW
70
79
77
86
84
93
97
109
113
125
124
138
154
171
163
182
190
209
202
223
206
230
232
256
249
278
281
312
314
347
346
379
380
411
363
404
379
420
413
459

COOL
l/s
13
14
16
19
22
24
29
32
35
38
40
43
48
55
60
65
69
70
73
80

COOL
l/s
13
14
15
18
21
24
29
31
34
37
39
42
46
53
58
63
67
68
71
78

COOL
kPa
14
14
17
33
36
35
44
36
36
34
38
36
36
41
42
46
43
45
46
56

COOL
kPa
13
14
16
31
34
34
42
34
35
33
36
34
34
39
40
44
41
43
44
53

CAP
kW
276
303
330
395
454
512
619
681
730
797
843
906
1007
1153
1254
1363
1454
1478
1535
1685

35

CAP
kW
257
282
307
369
425
479
579
637
684
746
789
848
942
1080
1174
1275
1360
1383
1436
1578

35

COMP UNIT
kW
kW
71
80
78
87
86
95
98
110
115
127
126
140
157
174
165
185
193
212
206
226
210
233
237
260
253
282
286
316
319
352
352
386
388
419
370
410
386
427
420
466

COMP UNIT
kW
kW
76
85
84
93
93
102
106
118
125
136
136
150
169
186
178
197
208
226
222
242
226
249
254
278
272
301
307
338
344
376
379
412
417
448
397
437
415
455
452
498

COOL
l/s
13
14
16
19
22
24
29
32
35
38
40
43
48
55
60
65
69
70
73
80

COOL
l/s
12
13
15
18
20
23
28
30
33
36
38
40
45
51
56
61
65
66
68
75

COOL
kPa
14
14
17
33
36
35
44
36
36
34
38
36
36
41
42
46
43
45
46
56

COOL
kPa
12
13
15
30
32
32
39
32
32
31
34
32
32
36
38
41
38
40
41
50

CAP
kW
255
278
301
367
421
474
575
632
678
740
782
839
933
1070
1164
1263
1346
1371
1421
1563

40

CAP
kW
247
269
292
356
408
460
556
613
658
718
759
815
905
1039
1130
1226
1306
1330
1380
1518

40

COMP UNIT
kW
kW
85
94
94
103
103
112
118
130
139
150
151
165
188
205
198
217
231
250
247
267
252
275
283
306
304
332
342
372
383
415
423
456
466
496
443
483
463
503
503
549

COMP UNIT
kW
kW
84
93
93
102
101
110
116
128
137
148
149
163
185
202
195
214
228
246
243
263
248
271
279
302
299
327
336
367
377
409
416
449
457
488
436
475
455
495
495
541

COOL
l/s
12
13
14
17
20
23
27
30
32
35
37
40
44
51
55
60
64
65
68
74

COOL
l/s
12
13
14
17
19
22
26
29
31
34
36
39
43
49
54
58
62
63
66
72

COOL
kPa
12
12
14
29
31
31
38
31
32
30
33
31
31
35
37
40
37
39
40
49

COOL
kPa
12
12
14
28
30
29
36
30
30
28
32
30
30
34
35
38
35
37
38
46

CAP
kW
240
261
282
349
399
448
545
599
644
702
742
797
885
1016
1105
1198
1275
1301
1348
1483

46

CAP
kW
233
253
273
338
387
435
528
581
625
681
720
774
859
985
1073
1163
1238
1263
1309
1440

46

COMP UNIT
kW
kW
95
104
105
114
116
124
131
143
155
167
169
183
210
226
221
240
258
277
276
295
281
304
316
339
340
367
382
412
427
459
473
505
521
551
495
534
517
557
562
607

COMP UNIT
kW
kW
93
102
104
112
114
123
130
141
153
164
167
180
206
223
218
237
254
273
272
291
277
299
312
334
334
362
376
405
421
452
466
498
512
542
487
526
509
548
554
599

COOL
l/s
11
12
13
17
19
21
26
29
31
33
35
38
42
48
53
57
61
62
64
71

COOL
l/s
11
12
13
16
18
21
25
28
30
32
34
37
41
47
51
55
59
60
62
69

COOL
kPa
11
11
13
26
28
28
35
28
29
27
30
28
28
32
33
36
34
36
36
44

COOL
kPa
10
10
12
25
27
26
33
27
28
26
29
27
27
31
32
35
32
34
35
42

Unit with option 119 (high energy efficiency)

Cooling capacities

Legend
LWT
CAP kW
COMP kW
UNIT kW
COOL l/s
COOL kPa

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

COMP UNIT
kW
kW
75
84
83
93
92
101
104
116
124
136
135
149
168
185
177
197
207
226
220
241
225
249
254
277
272
301
307
337
343
376
379
412
419
450
397
438
415
456
450
497

COMP UNIT
kW
kW
72
81
79
89
87
96
99
112
117
129
128
142
159
177
168
188
196
215
209
230
214
237
241
264
258
286
291
322
325
358
359
392
395
426
376
417
393
434
427
474

Leaving water temperature


Cooling capacity
Compressor power input
Unit power input (compressors, fans and control circuit)
Evaporator water flow rate
Evaporator pressure drop

CAP
kW
312
342
372
446
510
575
699
767
823
898
948
1019
1133
1297
1410
1532
1632
1663
1724
1894

COOL
kPa
18
19
22
43
46
46
57
46
47
44
49
46
46
53
55
60
56
58
60
73

30

COOL
l/s
15
17
19
22
25
28
34
38
41
44
47
50
56
64
70
76
81
82
85
94

CAP
kW
323
355
387
460
527
595
722
793
851
929
981
1055
1173
1341
1458
1586
1691
1721
1786
1959

COMP UNIT
kW
kW
68
78
76
85
84
93
95
107
113
125
123
138
154
171
162
182
190
209
202
223
207
230
233
257
250
279
281
312
315
348
347
381
384
415
365
405
381
422
413
460

25

Air temperature, C

Unit with option 119, LWT = 10C

30XA
252
302
352
402
452
502
602
702
752
802
852
902
1002
1102
1202
1302
1352
1402
1502
1702

CAP
kW
285
313
341
407
468
527
638
702
753
821
869
933
1037
1189
1292
1404
1497
1523
1581
1736

COOL
kPa
16
16
19
37
40
39
49
40
41
38
43
40
40
46
47
52
48
50
52
63

30

COOL
l/s
14
15
17
20
23
26
31
35
37
40
43
46
51
59
64
69
74
75
78
86

CAP
kW
295
325
354
420
483
545
660
726
778
849
899
965
1073
1229
1336
1452
1550
1575
1636
1795

COMP UNIT
kW
kW
65
75
72
82
79
89
91
103
107
119
117
131
146
163
154
173
180
199
192
212
196
219
221
244
236
265
266
297
298
331
328
362
362
393
345
386
360
401
391
438

25

Air temperature, C

Unit with option 119, LWT = 7C

COOL
l/s
15
16
18
21
24
27
33
37
39
43
45
49
54
62
67
73
78
79
82
90

COOL
l/s
14
15
16
19
22
25
30
33
36
39
41
44
49
57
62
67
71
73
75
83

COOL
kPa
17
18
21
41
44
43
54
43
44
42
46
43
43
50
52
56
52
55
56
69

COOL
kPa
15
15
18
35
38
37
46
37
38
36
40
38
37
43
45
49
45
47
48
59

CAP
kW
300
328
356
430
492
554
674
740
793
865
914
981
1091
1251
1359
1476
1571
1602
1660
1826

35

CAP
kW
274
300
326
393
451
508
616
677
726
792
838
899
1000
1147
1247
1354
1442
1468
1523
1675

35

COOL
l/s
14
16
17
21
23
26
32
35
38
41
44
47
52
60
65
70
75
76
79
87

COOL
l/s
13
14
16
19
22
24
29
32
35
38
40
43
48
55
59
65
69
70
73
80

COOL
kPa
16
16
19
38
41
40
50
41
41
39
43
41
40
46
48
53
49
51
52
64

COOL
kPa
14
14
16
33
35
35
43
35
36
34
37
35
35
40
42
46
42
44
45
55

CAP
kW
287
313
339
414
472
532
648
711
762
832
878
942
1048
1202
1306
1418
1506
1538
1594
1754

40

CAP
kW
263
286
310
378
433
488
593
651
698
762
805
864
961
1103
1199
1301
1385
1411
1463
1610

40

COMP UNIT
kW
kW
90
99
100
109
110
119
124
136
148
160
162
176
200
217
211
231
247
266
263
283
269
292
303
326
325
353
365
396
409
441
453
486
501
531
474
513
496
536
538
584

COMP UNIT
kW
kW
86
95
95
104
105
114
119
131
141
153
154
168
191
208
201
221
235
254
251
271
256
279
288
311
309
337
348
378
389
421
430
463
474
504
450
490
471
511
512
557

Performances in accordance with EN 14511.

Application data:
Standard units, refrigerant: R134a
Evaporator temperature rise: 5 K
Evaporator fluid: chilled water
Fouling factor: 0.18 x 10-4 (m2 K)/W

COMP UNIT
kW
kW
82
91
91
100
101
110
113
126
135
147
147
162
183
200
193
213
226
245
241
261
246
269
277
300
297
326
335
365
374
407
414
447
458
489
434
474
453
494
492
538

COMP UNIT
kW
kW
78
88
87
96
96
105
109
121
129
141
140
154
174
191
184
203
215
233
229
249
234
257
263
286
282
310
318
348
355
388
393
425
433
463
411
451
430
470
467
513

COOL
l/s
14
15
16
20
23
25
31
34
36
40
42
45
50
57
62
68
72
73
76
84

COOL
l/s
13
14
15
18
21
23
28
31
33
36
38
41
46
53
57
62
66
67
70
77

COOL
kPa
15
15
17
35
38
37
47
38
39
36
40
38
38
43
45
49
45
47
48
59

COOL
kPa
13
13
15
31
33
32
40
33
33
31
35
33
33
37
39
42
39
41
42
51

CAP
kW
271
294
318
393
448
504
614
673
723
789
832
893
993
1140
1239
1322
1351
1458
1509
1663

46

CAP
kW
248
269
291
359
411
462
562
617
663
723
764
820
911
1046
1138
1233
1311
1339
1387
1527

46

COMP UNIT
kW
kW
100
109
112
121
124
133
138
150
165
177
181
194
223
240
236
255
275
293
293
313
300
323
337
360
363
390
407
437
456
487
494
525
517
547
528
567
553
592
600
645

COMP UNIT
kW
kW
96
105
107
116
118
126
133
145
157
169
172
186
213
229
225
244
262
281
280
300
286
308
321
344
345
373
388
418
434
466
481
513
530
560
503
542
526
565
572
616

COOL
l/s
13
14
15
19
21
24
29
32
35
38
40
43
47
54
59
63
65
70
72
79

COOL
l/s
12
13
14
17
20
22
27
29
32
34
36
39
43
50
54
59
62
64
66
73

COOL
kPa
13
13
15
32
34
34
42
34
35
33
36
34
34
39
41
43
37
43
44
54

COOL
kPa
11
12
13
28
30
29
37
30
30
28
32
30
30
34
35
38
35
37
38
46

Unit with option 119 (high energy efficiency)

Cooling capacities

23

Order No. 13450-20, 10.2007. Supersedes order 13450-20, 10.2006.


Manufacturer reserves the right to change any product specifications without notice.
The cover photo is solely for illustration purposes and not contractually binding.

Manufactured by: Carrier SCS, Montluel, France.


Printed on Totally Chlorine Free Paper.
Printed in the Netherlands.