Beruflich Dokumente
Kultur Dokumente
Si34-803
RXYQ5P(A) ............................................................................................78
RXYQ8P(A) ............................................................................................80
RXYQ10P(A), 12P(A).............................................................................82
RXYQ14P(A), 16P(A), 18P(A)................................................................84
Outdoor Air Processing Unit FXMQ125MFV1~250MFV1 ......................86
RXYQ5P(A) ............................................................................................87
RXYQ8P(A) ............................................................................................88
RXYQ10P(A) ..........................................................................................89
RXYQ12P(A) ..........................................................................................90
RXYQ14P(A), 16P(A), 18P(A)................................................................91
2. Basic Control.......................................................................................112
2.1
2.2
2.3
2.4
2.5
Table of Contents
Si34-803
3. Special Control....................................................................................143
3.1
3.2
3.3
3.4
3.5
3.6
3.7
5. Other Control.......................................................................................157
5.1
5.2
5.3
5.4
Table of Contents
Si34-803
Table of Contents
Si34-803
3.37
3.38
3.39
3.40
3.41
3.42
3.43
3.44
3.45
3.46
3.47
3.48
3.49
3.50
3.51
3.52
3.53
3.54
3.55
3.56
3.57
Table of Contents
Si34-803
6.
7.
8.
9.
Index
............................................................................................. i
Table of Contents
Introduction
Si34-803
1. Introduction
1.1
Safety Cautions
Cautions and
Warnings
Be sure to read the following safety cautions before conducting repair work.
The caution items are classified into
Warning and
Caution. The
Warning
items are especially important since they can lead to death or serious injury if they are not
followed closely. The
Caution items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
vi
Si34-803
Introduction
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
vii
Introduction
Si34-803
Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly.
For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
viii
Si34-803
Introduction
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
Type of
Information
Note
Description
A note provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Note:
Caution
Warning
Reference
Caution
Warning
ix
Introduction
1.2
Si34-803
PREFACE
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2008 VRVIII series Heat Pump System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVIII series R-410A Heat
Pump System.
June, 2008
After Sales Service Division
Si34-803
Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................2
2. External Appearance...............................................................................3
2.1 Indoor Units ..............................................................................................3
2.2 Outdoor Units ...........................................................................................4
General Information
Si34-803
Model Name
Power Supply
FXFQ
25P
32P
40P
50P
63P
80P
100P
125P
FXCQ
20M
25M
32M
40M
50M
63M
80M
125M
Ceiling Mounted
Cassette Corner Type
FXKQ
63MA
20PB
25PB
32PB
FXDQPBVE
FXDQPBVET
FXDQNBVE
FXDQNBVET
20PB
25PB
32PB
40NB
50NB
63NB
40NB
50NB
63NB
VE
Ceiling Mounted
Built-In Type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M
125M
Ceiling Mounted
Duct Type (Middle and
high static pressure)
FXMQ
40P
50P
63P
80P
100P
125P
Ceiling Mounted
Duct Type
FXMQ
Ceiling Suspended
Type
FXHQ
32MA
63MA
100MA
FXAQ
FXLQ
Concealed Floor
Standing Type
FXNQ
FXMQMF
Ceiling Suspended
Cassette Type
FXUQ
Connection Unit
BEVQMA
VE
200MA 250MA
VE
Outdoor Units
Normal Series
Series
Heat Pump
RXYQ
Model Name
Power Supply
5P(A) 8P(A) 10P(A) 12P(A) 14P(A) 16P(A) 18P(A) 20P(A) 22P(A)
Y1(E)
24P(A) 26P(A) 28P(A) 30P(A) 32P(A) 34P(A) 36P(A) 38P(A) 40P(A)
YL(E)
TL(E)
42P(A) 44P(A) 46P(A) 48P(A) 50P(A) 52P(A) 54P(A)
Model Name
Power Supply
16P(A)H 18P(A)H 24P(A)H 26P(A)H 28P(A)H 30P(A)H 32P(A)H 34P(A)H 36P(A)H
Y1(E)
YL(E)
38P(A)H 40P(A)H 42P(A)H 44P(A)H 46P(A)H 48P(A)H 50P(A)H
TL(E)
Heat Pump
RXYQ
Power Supply
General Information
Si34-803
External Appearance
2. External Appearance
2.1
Indoor Units
FXMQ200MA
FXMQ250MA
FXDQ40NB
FXDQ50NB
FXDQ63NB
General Information
BEVQ71MA
BEVQ100MA
BEVQ125MA
Connection Unit
External Appearance
2.2
Si34-803
Outdoor Units
RXYQ5P(A)
RXYQ8P(A), 10P(A)
5HP
8, 10HP
General Information
Si34-803
External Appearance
RXYQ24P(A)H, 26P(A)H
16, 18HP
24, 26HP
RXYQ28P(A)H, 30P(A)H
RXYQ32P(A)H, 34P(A)H
28, 30HP
32, 34HP
General Information
Si34-803
System Number
Capacity of units
5HP
1
8HP
1
10HP
1
12HP
1
14HP
1
16HP
1
18HP
1
20HP
2
22HP
2
24HP
2
26HP
2
28HP
2
30HP
2
32HP
2
34HP
2
36HP
2
38HP
3
40HP
3
42HP
3
44HP
3
46HP
3
48HP
3
50HP
3
52HP
3
54HP
3
Note:
10
Module
12
14
16
18
For multiple connection of 18HP system or more, an optional Daikin Outdoor Unit Multi
Connection Piping Kit is required.
General Information
Si34-803
System Number
Capacity of units
16HP
2
18HP
2
24HP
3
26HP
3
28HP
3
30HP
3
32HP
3
34HP
3
36HP
3
38HP
3
40HP
3
42HP
3
44HP
3
46HP
3
48HP
3
50HP
3
Note:
General Information
10
Module
12
14
16
18
For multiple connection of 16HP system or more, an optional Daikin Outdoor Unit Multi
Connection Piping Kit is required.
Model Selection
Si34-803
4. Model Selection
VRV III Heat Pump Series
Outdoor Units
Normal Type (Space Saving Type)
Total capacity index of
connectable indoor units*
RXYQ5P(A)
Maximum number of
connectable indoor units*
8 (12)
RXYQ8P(A)
13 (20)
RXYQ10P(A)
RXYQ10P(A)
16 (25)
12 HP
RXYQ12P(A)
RXYQ12P(A)
19 (30)
14 HP
RXYQ14P(A)
RXYQ14P(A)
23 (35)
16 HP
RXYQ16P(A)
RXYQ16P(A)
26 (40)
18 HP
RXYQ18P(A)
RXYQ18P(A)
29 (45)
20 HP
RXYQ20P(A)
RXYQ8P(A) + RXYQ12P(A)
32 (40)
22 HP
RXYQ22P(A)
RXYQ10P(A) + RXYQ12P(A)
35 (44)
24 HP
RXYQ24P(A)
RXYQ8P(A) + RXYQ16P(A)
39 (48)
26 HP
RXYQ26P(A)
RXYQ8P(A) + RXYQ18P(A)
42 (52)
28 HP
RXYQ28P(A)
RXYQ10P(A) + RXYQ18P(A)
45 (56)
30 HP
RXYQ30P(A)
RXYQ12P(A) + RXYQ18P(A)
48 (60)
32 HP
RXYQ32P(A)
RXYQ16P(A) x 2
52 (64)
34 HP
RXYQ34P(A)
RXYQ16P(A) + RXYQ18P(A)
55 (64)
36 HP
RXYQ36P(A)
RXYQ18P(A) x 2
58 (64)
38 HP
RXYQ38P(A)
61 (61)
40 HP
RXYQ40P(A)
RXYQ8P(A) + RXYQ16P(A) x 2
42 HP
RXYQ42P(A)
44 HP
RXYQ44P(A)
RXYQ8P(A) + RXYQ18P(A) x 2
46 HP
RXYQ46P(A)
RXYQ10P(A) + RXYQ18P(A) x 2
48 HP
RXYQ48P(A)
RXYQ12P(A) + RXYQ18P(A) x 2
50 HP
RXYQ50P(A)
RXYQ14P(A) + RXYQ18P(A) x 2
52 HP
RXYQ52P(A)
RXYQ16P(A) + RXYQ18P(A) x 2
54 HP
RXYQ54P(A)
RXYQ18P(A) x 3
HP
Model name
Combination
5 HP
RXYQ5P(A)
8 HP
RXYQ8P(A)
10 HP
BHFP22P100
64 (64)
Note: For multiple connection of 20 HP systems and above, the above Daikin optional kit (separately sold) is required.
*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160%
for double outdoor units, and 130% for triple outdoor units.
Model name
Combination
16 HP
RXYQ16P(A)H
RXYQ8P(A) x 2
18 HP
RXYQ18P(A)H
RXYQ8P(A) + RXYQ10P(A)
24 HP
RXYQ24P(A)H
26 HP
28 HP
26 (32)
29 (36)
RXYQ8P(A) x 3
39 (39)
RXYQ26P(A)H
RXYQ8P(A) x 2 + RXYQ10P(A)
42 (42)
RXYQ28P(A)H
RXYQ8P(A) x 2 + RXYQ12P(A)
45 (45)
30 HP
RXYQ30P(A)H
48 (48)
32 HP
RXYQ32P(A)H
RXYQ8P(A) + RXYQ12P(A) x 2
52 (52)
34 HP
RXYQ34P(A)H
RXYQ10P(A) + RXYQ12P(A) x 2
55 (55)
36 HP
RXYQ36P(A)H
RXYQ12P(A) x 3
58 (58)
38 HP
RXYQ38P(A)H
RXYQ12P(A) x 2 + RXYQ14P(A)
61 (61)
40 HP
RXYQ40P(A)H
RXYQ12P(A) x 2 + RXYQ16P(A)
42 HP
RXYQ42P(A)H
RXYQ12P(A) x 2 + RXYQ18P(A)
44 HP
RXYQ44P(A)H
RXYQ12P(A) + RXYQ16P(A) x 2
46 HP
RXYQ46P(A)H
48 HP
RXYQ48P(A)H
RXYQ16P(A) x 3
50 HP
RXYQ50P(A)H
RXYQ16P(A) x 2 + RXYQ18P(A)
BHFP22P100
BHFP22P151
64 (64)
Note: For multiple connection of 16 HP systems and above, the above Daikin optional kit (separately sold) is required.
*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160%
for double outdoor units, and 130% for triple outdoor units.
General Information
Si34-803
Model Selection
Model Name
Power Supply
Ceiling Mounted
Cassette Type
(Multi Flow)
FXFQ
25P
32P
40P
50P
63P
80P
100P
125P
Ceiling Mounted
Cassette Type
(Double Flow)
FXCQ
20M
25M
32M
40M
50M
63M
80M
125M
Ceiling Mounted
Cassette Corner Type
FXKQ
63MA
FXDQPBVE
20PB
25PB
32PB
FXDQPBVET
20PB
25PB
32PB
FXDQNBVE
40NB
50NB
63NB
FXDQNBVET
40NB
50NB
63NB
Ceiling Mounted
Built-In Type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M
125M
Ceiling Mounted
Duct Type (Middle and
high static pressure)
FXMQ
40P
50P
63P
80P
100P
125P
Ceiling Mounted
Duct Type
FXMQ
Ceiling Suspended
Type
FXHQ
32MA
63MA
100MA
FXAQ
FXLQ
Concealed Floor
Standing Type
FXNQ
FXMQMF
Ceiling Suspended
Cassette Type
FXUQ
Connection Unit
BEVQ-MA
VE
200MA 250MA
VE
P20
type
2.2
kW
0.8HP
P25
type
2.8
kW
1HP
P32
type
3.5
kW
1.25HP
P40
type
4.5
kW
1.6HP
P50
type
5.6
kW
2.0HP
P63
type
7.0
kW
2.5HP
P80
type
9.0
kW
3.2HP
P100
type
11.2
kW
4HP
P125
type
14.0
kW
5HP
P200
type
22.4
kW
8HP
P250
type
28.0
kW
10HP
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
General Information
Model Selection
Si34-803
Object
Connection of equalizer oil pipe
Equalizer oil pipe for multioutdoor-unit system
Workability
Refrigerant charge
10
Differences
New model (P(A) Model)
z NONE
(No particular changes in
terms of service)
z NONE
z NONE
General Information
Si34-803
Part 2
Specifications
1. Specifications ........................................................................................12
1.1 Outdoor Units .........................................................................................12
1.2 Indoor Units ............................................................................................54
Specifications
11
Specifications
Si34-803
1. Specifications
1.1
Outdoor Units
RXYQ5PAY1(E)
RXYQ8PAY1(E)
kcal / h
12,100
19,400
Btu / h
48,100
76,800
kW
14.1
22.5
kW
14.0
22.4
kcal / h
13,800
21,500
Btu / h
54,600
85,300
3 Heating Capacity
Casing Color
kW
16.0
25.0
Without(E)
With(E)
mm
1680635765
1680930765
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
Piston Displacement
m/h
13.34
Number of Revolutions
r.p.m
6300
7980
Motor OutputNumber
of Units
kW
2.81
4.51
Starting Method
Type
Fan
0.751
kW
0.351
m/min
95
180
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
160
205
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Soft Start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Soft Start
Propeller Fan
Charge
kg
Control
Refrigerator Oil
Deicer
Deicer
28~100
20~100
R-410A
R-410A
6.2
7.2
Standard Accessories
Drawing No.
C: 4D061005
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
12
Specifications
Si34-803
Specifications
Model Name
RXYQ10PAY1(E)
RXYQ12PAY1(E)
kcal / h
24,300
29,000
Btu / h
96,200
115,000
kW
28.2
33.7
kW
28.0
33.5
3 Heating Capacity
Casing Color
kcal / h
27,100
32,300
Btu / h
107,000
128,000
kW
31.5
37.5
Without(E)
With(E)
mm
1680930765
16801240765
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
13.34+10.53
m/h
13.34+10.53
r.p.m
6300, 2900
6300, 2900
Motor OutputNumber
of Units
kW
(1.4+4.5)1
(2.5+4.5)1
Soft Start
Soft Start
Propeller Fan
Propeller Fan
0.352
Motor Output
kW
0.751
m/min
185
233
Direct Drive
Direct Drive
Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Number of Revolutions
Type
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
249
285
Deicer
Deicer
14~100
14~100
R-410A
R-410A
7.9
9.5
Standard Accessories
Drawing No.
C: 4D061007
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
13
Specifications
Si34-803
Model Name
RXYQ14PAY1(E)
RXYQ16PAY1(E)
kcal / h
34,600
39,000
Btu / h
137,000
155,000
kW
40.2
45.3
kW
40.0
45.0
3 Heating Capacity
Casing Color
kcal / h
38,700
43,000
Btu / h
154,000
171,000
kW
45.0
50.0
Without(E)
With(E)
mm
16801240765
16801240765
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
13.34+10.53+10.53
m/h
13.34+10.53+10.53
r.p.m
6300, 29002
6300, 29002
Motor OutputNumber
of Units
kW
(1.6+4.5+4.5)1
(2.7+4.5+4.5)1
Soft Start
Soft Start
Propeller Fan
Propeller Fan
0.352
Motor Output
kW
0.352
m/min
233
233
Direct Drive
Direct Drive
Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Number of Revolutions
Type
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
329
329
Deicer
Deicer
10~100
10~100
R-410A
R-410A
11.3
11.5
Standard Accessories
Drawing No.
C: 4D061009
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
14
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
RXYQ18PAY1(E)
RXYQ20PAY1(E)
RXYQ8PAY1(E)+RXYQ12PAY1(E)
kcal / h
42,000
48,300
Btu / h
168,000
192,000
kW
49.3
56.2
kW
49.0
55.9
3 Heating Capacity
Casing Color
kcal / h
48,600
53,800
Btu / h
193,000
213,000
kW
56.5
62.5
Without(E)
With(E)
mm
16801240765
(1680930765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
16.90+10.53+10.53
(16.90)+(13.34+10.53)
Number of Revolutions
r.p.m
(7980)+(6300, 2900)
Motor OutputNumber
of Units
kW
(4.3+4.5+4.5)1
(4.51)+((2.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
(0.751)+(0.352)
kW
0.752
m/min
239
180+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
341
205+285
Deicer
Deicer
9~100
8~100
R-410A
R-410A
11.7
7.2+9.5
Standard Accessories
Drawing No.
C: 4D061011
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
15
Specifications
Si34-803
RXYQ22PAY1(E)
RXYQ24PAY1(E)
RXYQ10PAY1(E)+RXYQ12PAY1(E)
RXYQ8PAY1(E)+RXYQ16PAY1(E)
kcal / h
53,200
58,300
Btu / h
211,000
231,000
kW
61.9
67.8
kW
61.5
67.4
3 Heating Capacity
Casing Color
kcal / h
59,300
64,500
Btu / h
235,000
256,000
kW
69.0
75.0
Without(E)
With(E)
mm
(1680930765)+(16801240765)
(1680930765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53)+(13.34+10.53)
16.90+(13.34+10.53+10.53)
Number of Revolutions
r.p.m
7980+(6300, 29002)
Motor OutputNumber
of Units
kW
((1.4+4.5)1)+((2.5+4.5)1)
(4.51)+((2.7+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
(0.751)+(0.352)
kW
(0.751)+(0.352)
m/min
185+233
180+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
249+285
205+329
Deicer
Deicer
7~100
6~100
R-410A
R-410A
7.9+9.5
7.2+11.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
16
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
RXYQ26PAY1(E)
RXYQ28PAY1(E)
RXYQ8PAY1(E)+RXYQ18PAY1(E)
RXYQ10PAY1(E)+RXYQ18PAY1(E)
kcal / h
61,700
66,700
Btu / h
250,000
26,400
kW
71.8
77.5
kW
71.4
77.0
Casing Color
kcal / h
70,100
75,700
Btu / h
278,000
300,000
kW
81.5
88.0
Without(E)
With(E)
mm
(1680930765)+(16801240765)
(1680930765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(16.90)+(16.90+10.53+10.53)
(13.34+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
(4.51)+((4.3+4.5+4.5)1)
((1.4+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
(0.751)+(0.752)
kW
(0.751)+(0.752)
m/min
180+239
185+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
205+341
249+341
Deicer
Deicer
6~100
5~100
R-410A
R-410A
7.2+11.7
7.9+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
17
Specifications
Si34-803
RXYQ30PAY1(E)
RXYQ32PAY1(E)
RXYQ12PAY1(E)+RXYQ18PAY1(E)
RXYQ16PAY1(E)+RXYQ16PAY1(E)
kcal / h
71,400
77,800
Btu / h
283,000
309,000
kW
83
90.5
kW
82.5
90.0
3 Heating Capacity
Casing Color
kcal / h
80,800
86,000
Btu / h
321,000
341,000
kW
94.0
100
Without(E)
With(E)
mm
(16801240765)+(16801240765)
(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53)+(16.90+10.53+10.53)
(13.34+10.53+10.53)+(13.34+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
((2.5+4.5)1)+((4.3+4.5+4.5)1)
((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
(0.352)+(0.352)
kW
(0.352)+(0.752)
m/min
233+239
233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
285+341
329+329
Deicer
Deicer
5~100
5~100
R-410A
R-410A
9.5+11.7
11.5+11.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
18
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
RXYQ34PAY1(E)
RXYQ36PAY1(E)
RXYQ16PAY1(E)+RXYQ18PAY1(E)
RXYQ18PAY1(E)+RXYQ18PAY1(E)
kcal / h
81,400
85,100
Btu / h
323,000
338,000
kW
94.6
99.0
kW
94.0
98.0
3 Heating Capacity
Casing Color
kcal / h
92,000
97,200
Btu / h
365,000
386,000
kW
107
113
Without(E)
With(E)
mm
(16801240765)+(16801240765)
(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53+10.53)+(16.90+10.53+10.53)
(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
(0.752)+(0.752)
kW
(0.352)+(0.752)
m/min
233+239
239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
329+341
341+341
Deicer
Deicer
5~100
4~100
R-410A
R-410A
11.5+11.7
11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
19
Specifications
Si34-803
RXYQ38PAY1(E)
RXYQ40PAY1(E)
RXYQ8PAY1(E)+RXYQ12PAY1(E)+RXYQ18PAY1(E)
RXYQ8PAY1(E)+RXYQ16PAY1(E)+RXYQ16PAY1(E)
kcal / h
91,200
97,200
Btu / h
362,000
386,000
kW
106
113
kW
105
112
kcal / h
102,000
108,000
Btu / h
406,000
427,000
kW
119
125
Without(E)
3 Heating Capacity
Casing Color
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(1680930765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(16.90)+(13.34+10.53)+(16.90+10.53+10.53)
(16.90)+(13.34+10.53+10.53)+(13.34+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
(4.51)+((2.5+4.5)1)+((4.3+4.5+4.5)1)
(4.51)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.352)+(0.752)
(0.751)+(0.352)+(0.352)
m/min
180+233+239
180+233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+285+341
205+329+329
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
4~100
4~100
R-410A
R-410A
7.2+9.5+11.7
7.2+11.5+11.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
20
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
RXYQ42PAY1(E)
RXYQ44PAY1(E)
RXYQ8PAY1(E)+RXYQ16PAY1(E)+RXYQ18PAY1(E)
RXYQ8PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
kcal / h
101,000
104,000
Btu / h
399,000
413,000
kW
117
121
kW
116
120
kcal / h
114,000
119,000
Btu / h
450,000
471,000
kW
132
138
Without(E)
Casing Color
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(1680930765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(16.90)+(13.34+10.53+10.53)+(16.90+10.53+10.53)
(16.90)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
(4.51)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
(4.51)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.352)+(0.752)
(0.751)+(0.752)+(0.752)
m/min
180+233+239
180+239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+329+341
205+341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
4~100
4~100
R-410A
R-410A
7.2+11.5+11.7
7.2+11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
21
Specifications
Si34-803
RXYQ46PAY1(E)
RXYQ48PAY1(E)
RXYQ10PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
RXYQ12PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
kcal / h
109,000
114,000
Btu / h
433,000
454,000
kW
127
133
kW
126
132
kcal / h
124,000
130,000
Btu / h
495,000
515,000
kW
145
151
Without(E)
Casing Color
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
(13.34+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
((1.4+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
((2.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.752)+(0.752)
(0.352)+(0.752)+(0.752)
m/min
185+239+239
233+239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
249+341+341
285+341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
3~100
3~100
R-410A
R-410A
7.9+11.7+11.7
9.5+11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
22
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
RXYQ50PAY1(E)
RXYQ52PAY1(E)
RXYQ14PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
RXYQ16PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
kcal / h
120,000
124,000
Btu / h
474,000
491,000
kW
139
144
kW
138
143
kcal / h
136,000
140,000
Btu / h
539,000
556,000
kW
158
163
Without(E)
Casing Color
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
Piston Displacement
m/h
(13.34+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
(13.34+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
r.p.m
Motor OutputNumber
of Units
kW
((1.6+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft Start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.752)+(0.752)
(0.352)+(0.752)+(0.752)
m/min
233+239+239
233+239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
329+341+341
329+341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
Number of Revolutions
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
3~100
3~100
R-410A
R-410A
11.3+11.7+11.7
11.5+11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
23
Specifications
Si34-803
RXYQ54PAY1(E)
RXYQ18PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
kcal / h
127,000
Btu / h
505,000
kW
148
kW
147
kcal / h
146,000
Btu / h
580,000
Casing Color
kW
170
Without(E)
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
Piston Displacement
m/h
(16.90+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
Motor OutputNumber
of Units
kW
((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Starting Method
Soft Start
Type
Fan
Propeller Fan
Motor Output
kW
(0.752)+(0.752)+(0.752)
m/min
239+239+239
Liquid Pipe
mm
Gas Pipe
mm
Drive
Connecting
Pipes
Direct Drive
kg
Safety Devices
Defrost Method
Deicer
Capacity Control
Refrigerant Name
Refrigerant
341+341+341
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Charge
kg
Control
3~100
R-410A
11.7+11.7+11.7
Electronic Expansion Valve
Refrigerator Oil
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
24
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
RXYQ16PAHY1(E)
RXYQ18PAHY1(E)
RXYQ8PAY1(E)+RXYQ8PAY1(E)
RXYQ8PAY1(E)+RXYQ10PAY1(E)
kcal / h
38,800
43,600
Btu / h
154,000
173,000
kW
45.1
50.7
kW
44.8
50.4
3 Heating Capacity
Casing Color
kcal / h
43,000
48,600
Btu / h
171,000
193,000
kW
50.0
56.5
Without(E)
With(E)
mm
(1680930765)+(1680930765)
(1680930765)+(1680930765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
(16.90)+(16.90)
r.p.m
(7980)+(7980)
(7980)+(6300,2900)
Motor OutputNumber
of Units
kW
(4.51)+(4.51)
(4.51)+((1.4+4.5)1)
Soft start
Soft start
Propeller Fan
Propeller Fan
(0.751)+(0.751)
Motor Output
kW
(0.751)+(0.751)
m/min
180+180
180+185
Direct Drive
Direct Drive
Drive
Liquid Pipe
mm
12.7(Brazing Connection)
15.9(Brazing Connection)
Gas Pipe
mm
28.6(Brazing Connection)
28.6(Brazing Connection)
kg
205+205
205+249
Deicer
Deicer
Refrigerant Name
Refrigerant
(16.90)+(13.34+10.53)
m/h
Number of Revolutions
Type
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
10~100
8~100
R-410A
R-410A
7.2+7.2
7.2+7.9
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
25
Specifications
Si34-803
Model Name
Model Name (Independent Unit)
RXYQ24PAHY1(E)
RXYQ26PAHY1(E)
RXYQ8PAY1(E)+RXYQ8PAY1(E)+RXYQ8PAY1(E)
RXYQ8PAY1(E)+RXYQ8PAY1(E)+RXYQ10PAY1(E)
kcal / h
58,100
63,000
Btu / h
231,000
250,000
kW
67.6
73.2
kW
67.2
72.8
3 Heating Capacity
Casing Color
kcal / h
64,500
70,100
Btu / h
260,000
278,000
kW
75.0
81.5
Without(E)
With(E)
mm
(1680930765)+(1680930765)+(1680930765)
(1680930765)+(1680930765)+(1680930765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(16.90)+(16.90)+(16.90)
(16.90)+(16.90)+(13.34+10.53)
Number of Revolutions
r.p.m
(7980)+(7980)+(7980)
(7980)+(7980)+(6300,2900)
Motor OutputNumber
of Units
kW
(4.51)+(4.51)+(4.51)
(4.51)+(4.51)+((1.4+4.5)1)
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.751)+(0.751)
(0.751)+(0.751)+(0.751)
m/min
180+180+180
180+180+185
Direct Drive
Direct Drive
Liquid Pipe
mm
15.9(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
34.9(Brazing Connection)
34.9(Brazing Connection)
kg
205+205+205
205+205+249
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
7~100
6~100
R-410A
R-410A
7.2+7.2+7.2
7.2+7.2+7.9
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
26
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
Model Name
Model Name (Independent Unit)
RXYQ28PAHY1(E)
RXYQ30PAHY1(E)
RXYQ8PAY1(E)+RXYQ8PAY1(E)+RXYQ12PAY1(E)
RXYQ8PAY1(E)+RXYQ10PAY1(E)+RXYQ12PAY1(E)
kcal / h
67,800
72,600
Btu / h
269,000
288,000
kW
78.8
84.4
kW
78.3
83.9
3 Heating Capacity
Casing Color
kcal / h
75,300
80,800
Btu / h
299,000
321,000
kW
87.5
94.0
Without(E)
With(E)
mm
(1680930765)+(1680930765)+(16801240765)
(1680930765)+(1680930765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(16.90)+(16.90)+(13.34+10.53)
(16.90)+(13.34+10.53)+(13.34+10.53)
Number of Revolutions
r.p.m
(7980)+(7980)+(6300,2900)
(7980)+(6300,2900)+(6300,2900)
Motor OutputNumber
of Units
kW
(4.51)+(4.51)+((2.5+4.5)1)
(4.51)+((1.4+4.5)1)+((2.5+4.5)1)
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.751)+(0.352)
(0.751)+(0.751)+(0.352)
m/min
180+180+233
180+185+233
Direct Drive
Direct Drive
Liquid Pipe
mm
19.1(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
34.9(Brazing Connection)
34.9(Brazing Connection)
kg
205+205+285
205+249+285
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
6~100
5~100
R-410A
R-410A
7.2+7.2+9.5
7.2+7.9+9.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
27
Specifications
Si34-803
Model Name
Model Name (Independent Unit)
RXYQ32PAHY1(E)
RXYQ34PAHY1(E)
RXYQ8PAY1(E)+RXYQ12PAY1(E)+RXYQ12PAY1(E)
RXYQ10PAY1(E)+RXYQ12PAY1(E)+RXYQ12PAY1(E)
kcal / h
77,300
82,200
Btu / h
307,000
326,000
kW
89.9
95.6
kW
89.4
95.0
3 Heating Capacity
Casing Color
kcal / h
86,000
92,000
Btu / h
341,000
365,000
kW
100
107
Without(E)
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(1680930765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(16.90)+(13.34+10.53)+(13.34+10.53)
(13.34+10.53)+(13.34+10.53)+(13.34+10.53)
Number of Revolutions
r.p.m
(7980)+(6300,2900)+(6300,2900)
(6300,2900)+(6300,2900)+(6300,2900)
Motor OutputNumber
of Units
kW
(4.51)+((2.5+4.5)1)+((2.5+4.5)1)
((1.4+4.5)1)+((2.5+4.5)1)+((2.5+4.5)1)
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.352)+(0.352)
(0.751)+(0.352)+(0.352)
m/min
180+233+233
185+233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
19.1(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
34.9(Brazing Connection)
34.9(Brazing Connection)
kg
205+285+285
249+285+285
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
5~100
5~100
R-410A
R-410A
7.2+9.5+9.5
7.9+9.5+9.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
28
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
Model Name
Model Name (Independent Unit)
RXYQ36PAHY1(E)
RXYQ38PAHY1(E)
RXYQ12PAY1(E)+RXYQ12PAY1(E)+RXYQ12PAY1(E)
RXYQ12PAY1(E)+RXYQ12PAY1(E)+RXYQ14PAY1(E)
kcal / h
87,700
92,900
Btu / h
348,000
368,000
kW
102
108
kW
101
107
kcal / h
97,200
103,000
Btu / h
386,000
409,000
kW
113
120
Without(E)
3 Heating Capacity
Casing Color
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53)+(13.34+10.53)+(13.34+10.53)
(13.34+10.53)+(13.34+10.53)+(13.34+10.53+10.53)
Number of Revolutions
r.p.m
(6300,2900)+(6300,2900)+(6300,2900)
(6300,2900)+(6300,2900)+(6300,2900,2900)
Motor OutputNumber
of Units
kW
((2.5+4.5)1)+((2.5+4.5)1)+((2.5+4.5)1)
((2.5+4.5)1)+((2.5+4.5)1)+((1.6+4.5+4.5)1)
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.352)
m/min
233+233+233
233+233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
19.1(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
41.3(Brazing Connection)
41.3(Brazing Connection)
kg
285+285+285
285+285+329
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
5~100
4~100
R-410A
R-410A
9.5+9.5+9.5
9.5+9.5+11.3
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
29
Specifications
Si34-803
Model Name
RXYQ40PAHY1(E)
RXYQ42PAHY1(E)
RXYQ12PAY1(E)+RXYQ12PAY1(E)+RXYQ16PAY1(E)
RXYQ12PAY1(E)+RXYQ12PAY1(E)+RXYQ18PAY1(E)
kcal / h
97,200
101,000
Btu / h
386,000
399,000
kW
113
117
kW
112
116
kcal / h
108,000
114,000
Btu / h
427,000
450,000
kW
125
132
Without(E)
Casing Color
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53)+(13.34+10.53)+(13.72+10.53+10.53)
(13.34+10.53)+(13.34+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
(6300,2900)+(6300,2900)+(6300,2900,2900)
(6300,2900)+(6300,2900)+(7980,2900,2900)
Motor OutputNumber
of Units
kW
((2.5+4.5)1)+((2.5+4.5)1)+((2.7+4.5+4.5)1)
((2.5+4.5)1)+((2.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.752)
m/min
233+233+233
233+233+239
Direct Drive
Direct Drive
Liquid Pipe
mm
19.1(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
41.3(Brazing Connection)
41.3(Brazing Connection)
kg
285+285+329
285+285+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
4~100
4~100
R-410A
R-410A
9.5+9.5+11.5
9.5+9.5+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
30
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
Model Name
RXYQ44PAHY1(E)
RXYQ46PAHY1(E)
RXYQ12PAY1(E)+RXYQ16PAY1(E)+RXYQ16PAY1(E)
RXYQ12PAY1(E)+RXYQ16PAY1(E)+RXYQ18PAY1(E)
kcal / h
108,000
111,000
Btu / h
427,000
440,000
kW
125
129
kW
124
128
kcal / h
119,000
124,000
Btu / h
471,000
491,000
kW
138
144
Without(E)
Casing Color
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53)+(13.34+10.53+10.53)+(13.34+10.53+10.53)
(13.34+10.53)+(13.34+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions
r.p.m
(6300,2900)+(6300,2900,2900)+(6300,2900,2900)
(6300,2900)+(6300,2900,2900)+(7980,2900,2900)
Motor OutputNumber
of Units
kW
((2.5+4.5)1)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
((2.5+4.5)1)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.752)
m/min
233+233+233
233+233+239
Direct Drive
Direct Drive
Liquid Pipe
mm
19.1(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
41.3(Brazing Connection)
41.3(Brazing Connection)
kg
285+329+329
285+329+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
4~100
3~100
R-410A
R-410A
9.5+11.5+11.5
9.5+11.5+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
31
Specifications
Si34-803
Model Name
RXYQ48PAHY1(E)
RXYQ50PAHY1(E)
RXYQ16PAY1(E)+RXYQ16PAY1(E)+RXYQ16PAY1(E)
RXYQ16PAY1(E)+RXYQ16PAY1(E)+RXYQ18PAY1(E)
kcal / h
117,000
120,000
Btu / h
464,000
478,000
kW
136
140
kW
135
139
kcal / h
129,000
134,000
Btu / h
512,000
532,000
kW
150
156
Without(E)
Casing Color
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
m/h
(13.34+10.53+10.53)+(13.34+10.53+10.53)+(13.34+10.53
+10.53)
(13.34+10.53+10.53)+(13.34+10.53+10.53)+(16.90+10.53
+10.53)
Number of Revolutions
r.p.m
(6300,2900,2900)+(6300,2900,2900)+(6300,2900,2900)
(6300,2900,2900)+(6300,2900,2900)+(7980,2900,2900)
Motor OutputNumber
of Units
kW
((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft start
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.752)
m/min
233+233+233
233+233+239
Direct Drive
Direct Drive
Liquid Pipe
mm
19.1(Brazing Connection)
19.1(Brazing Connection)
Gas Pipe
mm
41.3(Brazing Connection)
41.3(Brazing Connection)
kg
329+329+329
329+329+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Piston Displacement
Starting Method
Fan
Charge
kg
Control
Refrigerator Oil
3~100
3~100
R-410A
R-410A
11.5+11.5+11.5
11.5+11.5+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
32
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
Model Name
Casing Color
Dimensions: (HWD)
YL(E)
RXYQ5PAYL(E)
RXYQ8PAYL(E)
TL(E)
RXYQ5PTL(E)
RXYQ8PTL(E)
kcal / h
12,100
19,400
Btu / h
48,100
76,800
kW
14.1
22.5
kW
14.0
22.4
kcal / h
13,800
21,500
Btu / h
54,600
85,300
kW
16.0
25.0
Without(E)
With(E)
mm
1680635765
1680930765
Heat Exchanger
YL(E)
13.34
16.90
TL(E)
13.34
16.90
YL(E)
6300
7980
TL(E)
6300
7980
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
kW
Starting Method
Type
Fan
Propeller Fan
Propeller Fan
kW
0.351
0.751
m/min
95
180
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
Safety Devices
160
205
Defrost Method
Capacity Control
Refrigerant Name
Refrigerant
4.51
Soft Start
Motor Output
Drive
Connecting
Pipes
2.81
Soft Start
Charge
kg
Control
Refrigerator Oil
Deicer
20~100
R-410A
R-410A
6.2
7.2
Standard Accessories
Drawing No.
Deicer
28~100
YL(E)
4D061025
4D061026
TL(E)
4D060845A
4D060846A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
33
Specifications
Si34-803
60Hz
Model Name
YL(E)
RXYQ10PAYL(E)
RXYQ12PAYL(E)
TL(E)
RXYQ10PTL(E)
RXYQ12PTL(E)
kcal / h
24,300
29,000
Btu / h
96,200
115,000
kW
28.2
33.7
kW
28.0
33.5
kcal / h
27,100
32,300
Btu / h
107,000
128,000
kW
31.5
37.5
Without(E)
With(E)
mm
1680930765
16801240765
Casing Color
Dimensions: (HWD)
Heat Exchanger
YL(E)
13.34+12.52
13.34+12.52
TL(E)
13.34+12.52
13.34+12.52
YL(E)
6300, 3450
6300, 3450
TL(E)
6300, 3450
6300, 3450
kW
(1.4+4.5)1
(2.5+4.5)1
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
0.352
kW
0.751
m/min
185
233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
249
285
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Charge
kg
Control
Refrigerator Oil
Deicer
Deicer
14~100
14~100
R-410A
R-410A
7.9
9.5
Standard Accessories
Drawing No.
Propeller Fan
Refrigerant
Soft Start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Soft Start
60Hz
YL(E)
4D061027
4D061028
TL(E)
4D060847A
4D060848A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
34
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
60Hz
Model Name
YL(E)
RXYQ14PAYL(E)
RXYQ16PAYL(E)
TL(E)
RXYQ14PTL(E)
RXYQ16PTL(E)
kcal / h
34,600
39,000
Btu / h
137,000
155,000
kW
40.2
45.3
kW
40.0
45.0
kcal / h
38,700
43,000
Btu / h
154,000
171,000
kW
45.0
50.0
Without(E)
With(E)
mm
16801240765
16801240765
Casing Color
Dimensions: (HWD)
Heat Exchanger
YL(E)
12.84+12.52+12.52
12.84+12.52+12.52
TL(E)
12.84+12.52+12.52
12.84+12.52+12.52
YL(E)
TL(E)
kW
(1.6+4.5+4.5)1
(2.7+4.5+4.5)1
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Propeller Fan
0.352
kW
0.352
m/min
233
233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
329
329
Refrigerant Name
Refrigerant
Soft Start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Soft Start
Charge
kg
Control
Refrigerator Oil
Deicer
10~100
R-410A
R-410A
11.3
11.5
Standard Accessories
Drawing No.
Deicer
10~100
60Hz
YL(E)
4D061029
4D061030
TL(E)
4D060849A
4D060850A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
35
Specifications
Si34-803
YL(E)
TL(E)
Casing Color
Comp.
r.p.m
48,300
kW
49.3
56.2
kW
49.0
55.9
kcal / h
48,600
53,800
Btu / h
193,000
213,000
kW
56.5
62.5
Without(E)
With(E)
mm
16801240765
(1680930765)+(16801240765)
YL(E)
12.84+12.52+12.52
(16.90)+(13.34+12.52)
TL(E)
12.84+12.52+12.52
(16.90)+(13.34+12.52)
YL(E)
(7980)+(6300, 3450)
TL(E)
(7980)+(6300, 3450)
kW
(4.3+4.5+4.5)1
(4.51)+((2.5+4.5)1)
Starting Method
Type
Propeller Fan
(0.751)+(0.352)
kW
0.752
m/min
239
180+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
341
205+285
Deicer
Deicer
Safety Devices
Defrost Method
Capacity Control
Refrigerant Name
Charge
kg
Control
Refrigerator Oil
9~100
8~100
R-410A
R-410A
11.7
7.2+9.5
Standard Accessories
Drawing No.
Soft Start
Propeller Fan
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ8PTL(E)+RXYQ12PTL(E)
192,000
Motor OutputNumber
of Units
Fan
RXYQ20PTL(E)
42,400
Type
Number of
Revolutions
RXYQ18PTL(E)
168,000
Heat Exchanger
m/h
RXYQ8PAYL(E)+RXYQ12PAYL(E)
Btu / h
Dimensions: (HWD)
Piston
Displacement
RXYQ20PAYL(E)
kcal / h
RXYQ18PAYL(E)
60Hz
YL(E)
4D061031
TL(E)
4D060851A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
36
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
TL(E)
Casing Color
53,200
58,300
231,000
kW
61.9
67.8
kW
61.5
67.4
kcal / h
59,300
64,500
Btu / h
235,000
256,000
kW
69.0
75.0
Without(E)
With(E)
mm
(1680930765)+(16801240765)
(1680930765)+(16801240765)
YL(E)
(13.34+12.52)+(13.34+12.52)
(16.90)+(12.84+12.52+12.52)
TL(E)
(13.34+12.52)+(13.34+12.52)
(16.90)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((1.4+4.5)1)+((2.5+4.5)1)
(4.51)+((2.7+4.5+4.5)1)
Type
Comp.
Number of
Revolutions
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft Start
Propeller Fan
Propeller Fan
(0.751)+(0.352)
kW
(0.751)+(0.352)
m/min
185+233
180+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
249+285
205+329
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ24PTL(E)
RXYQ8PTL(E)+RXYQ16PTL(E)
211,000
Heat Exchanger
m/h
RXYQ22PTL(E)
RXYQ10PTL(E)+RXYQ12PTL(E)
Btu / h
Dimensions: (HWD)
Piston
Displacement
RXYQ24PAYL(E)
RXYQ8PAYL(E)+RXYQ16PAYL(E)
kcal / h
RXYQ22PAYL(E)
RXYQ10PAYL(E)+RXYQ12PAYL(E)
Charge
kg
Control
Refrigerator Oil
7~100
6~100
R-410A
R-410A
7.9+9.5
7.2+11.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
37
Specifications
Si34-803
YL(E)
TL(E)
Casing Color
61,700
66,700
264,000
kW
71.8
77.5
kW
71.4
77.0
kcal / h
70,100
75,700
Btu / h
278,000
300,000
kW
81.5
88.0
Without(E)
With(E)
mm
(1680930765)+(16801240765)
(1680930765)+(16801240765)
YL(E)
(16.90)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)
TL(E)
(16.90)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
(4.51)+((4.3+4.5+4.5)1)
((1.4+4.5)1)+((4.3+4.5+4.5)1)
Type
Comp.
Number of
Revolutions
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft Start
Propeller Fan
Propeller Fan
(0.751)+(0.752)
kW
(0.751)+(0.752)
m/min
180+239
185+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+341
249+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ28PTL(E)
RXYQ10PTL(E)+RXYQ18PTL(E)
250,000
Heat Exchanger
m/h
RXYQ26PTL(E)
RXYQ8PTL(E)+RXYQ18PTL(E)
Btu / h
Dimensions: (HWD)
Piston
Displacement
RXYQ28PAYL(E)
RXYQ10PAYL(E)+RXYQ18PAYL(E)
kcal / h
RXYQ26PAYL(E)
RXYQ8PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
6~100
5~100
R-410A
R-410A
7.2+11.7
7.9+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
38
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
TL(E)
Casing Color
71,400
77,800
309,000
kW
83.0
90.5
kW
82.5
90.0
kcal / h
80,800
86,000
Btu / h
321,000
341,000
kW
94.0
100
Without(E)
With(E)
mm
(16801240765)+(16801240765)
(16801240765)+(16801240765)
Type
Comp.
Number of
Revolutions
r.p.m
(13.34+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((2.5+4.5)1)+((4.3+4.5+4.5)1)
((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Type
Soft Start
Soft Start
Propeller Fan
Propeller Fan
(0.352)+(0.352)
Motor Output
kW
(0.352)+(0.752)
m/min
233+239
233+233
Direct Drive
Direct Drive
Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
285+341
329+329
Deicer
Deicer
Refrigerant Name
Refrigerant
TL(E)
Starting Method
Connecting
Pipes
Motor OutputNumber
of Units
Fan
RXYQ32PTL(E)
RXYQ16PTL(E)+RXYQ16PTL(E)
283,000
Heat Exchanger
m/h
RXYQ30PTL(E)
RXYQ12PTL(E)+RXYQ18PTL(E)
Btu / h
Dimensions: (HWD)
Piston
Displacement
RXYQ32PAYL(E)
RXYQ16PAYL(E)+RXYQ16PAYL(E)
kcal / h
RXYQ30PAYL(E)
RXYQ12PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
5~100
5~100
R-410A
R-410A
9.5+11.7
11.5+11.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
39
Specifications
Si34-803
YL(E)
TL(E)
Casing Color
81,400
85,100
338,000
kW
94.6
99.0
kW
94.0
98.0
kcal / h
92,000
97,200
Btu / h
365,000
386,000
kW
107
113
Without(E)
With(E)
mm
(16801240765)+(16801240765)
(16801240765)+(16801240765)
Type
Comp.
Number of
Revolutions
r.p.m
(12.84+12.52+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Soft Start
Soft Start
Propeller Fan
Propeller Fan
(0.752)+(0.752)
Motor Output
kW
(0.352)+(0.752)
m/min
233+239
239+239
Direct Drive
Direct Drive
Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
329+341
341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
TL(E)
Starting Method
Connecting
Pipes
Motor OutputNumber
of Units
Fan
RXYQ36PTL(E)
RXYQ18PTL(E)+RXYQ18PTL(E)
323,000
Heat Exchanger
m/h
RXYQ34PTL(E)
RXYQ16PTL(E)+RXYQ18PTL(E)
Btu / h
Dimensions: (HWD)
Piston
Displacement
RXYQ36PAYL(E)
RXYQ18PAYL(E)+RXYQ18PAYL(E)
kcal / h
RXYQ34PAYL(E)
RXYQ16PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
5~100
4~100
R-410A
R-410A
11.5+11.7
11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
40
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
TL(E)
Casing Color
91,200
97,200
386,000
kW
106
113
kW
105
112
kcal / h
102,000
108,000
Btu / h
406,000
427,000
kW
119
125
Without(E)
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(1680930765)+(16801240765)+(16801240765)
YL(E)
(16.90)+(13.34+12.52)+(12.84+12.52+12.52)
(16.90)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
TL(E)
(16.90)+(13.34+12.52)+(12.84+12.52+12.52)
(16.90)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
(4.51)+((2.5+4.5)1)+((4.3+4.5+4.5)1)
(4.51)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Type
Comp.
Number of
Revolutions
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft Start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.352)+(0.752)
(0.751)+(0.352)+(0.352)
m/min
180+233+239
180+233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+285+341
205+329+329
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ40PTL(E)
RXYQ8PTL(E)+RXYQ16PTL(E)+RXYQ16PTL(E)
362,000
Heat Exchanger
m/h
RXYQ38PTL(E)
RXYQ8PTL(E)+RXYQ12PTL(E)+RXYQ18PTL(E)
Btu / h
Dimensions: (HWD)
Piston
Displacement
RXYQ40PAYL(E)
RXYQ8PAYL(E)+RXYQ16PAYL(E)+RXYQ16PAYL(E)
kcal / h
RXYQ38PAYL(E)
RXYQ8PAYL(E)+RXYQ12PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
4~100
4~100
R-410A
R-410A
7.2+9.5+11.7
7.2+11.5+11.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
41
Specifications
Si34-803
YL(E)
Casing Color
RXYQ42PTL(E)
RXYQ44PTL(E)
RXYQ8PTL(E)+RXYQ18PTL(E)+RXYQ18PTL(E)
kcal / h
101,000
104,000
Btu / h
399,000
413,000
kW
117
121
kW
116
120
kcal / h
114,000
119,000
Btu / h
450,000
471,000
kW
132
138
Without(E)
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(1680930765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(16.90)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(16.90)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
TL(E)
(16.90)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(16.90)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
(4.51)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
(4.51)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft Start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.352)+(0.752)
(0.751)+(0.752)+(0.752)
m/min
180+233+239
180+239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+329+341
205+341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ44PAYL(E)
RXYQ8PAYL(E)+RXYQ18PAYL(E)+RXYQ18PAYL(E)
RXYQ8PTL(E)+RXYQ16PTL(E)+RXYQ18PTL(E)
TL(E)
RXYQ42PAYL(E)
RXYQ8PAYL(E)+RXYQ16PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
4~100
4~100
R-410A
R-410A
7.2+11.5+11.7
7.2+11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
42
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
Casing Color
RXYQ46PTL(E)
RXYQ48PTL(E)
RXYQ12PTL(E)+RXYQ18PTL(E)+RXYQ18PTL(E)
kcal / h
109,000
114,000
Btu / h
433,000
454,000
kW
127
133
kW
126
132
kcal / h
125,000
130,000
Btu / h
495,000
515,000
kW
145
151
Without(E)
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
TL(E)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((1.4+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
((2.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft Start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.752)+(0.752)
(0.352)+(0.752)+(0.752)
m/min
185+239+239
233+239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
249+341+341
285+341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ48PAYL(E)
RXYQ12PAYL(E)+RXYQ18PAYL(E)+RXYQ18PAYL(E)
RXYQ10PTL(E)+RXYQ18PTL(E)+RXYQ18PTL(E)
TL(E)
RXYQ46PAYL(E)
RXYQ10PAYL(E)+RXYQ18PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
3~100
3~100
R-410A
R-410A
7.9+11.7+11.7
9.5+11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
43
Specifications
Si34-803
YL(E)
Casing Color
RXYQ50PTL(E)
RXYQ52PTL(E)
RXYQ16PTL(E)+RXYQ18PTL(E)+RXYQ18PTL(E)
kcal / h
120,000
124,000
Btu / h
474,000
491,000
kW
139
144
kW
138
143
kcal / h
136,000
140,000
Btu / h
539,000
556,000
kW
158
163
Without(E)
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
TL(E)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((1.6+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft Start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.752)+(0.752)
(0.352)+(0.752)+(0.752)
m/min
233+239+239
233+239+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
329+341+341
329+341+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft Start
Motor Output
Drive
Connecting
Pipes
RXYQ52PAYL(E)
RXYQ16PAYL(E)+RXYQ18PAYL(E)+RXYQ18PAYL(E)
RXYQ14PTL(E)+RXYQ18PTL(E)+RXYQ18PTL(E)
TL(E)
RXYQ50PAYL(E)
RXYQ14PAYL(E)+RXYQ18PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
Refrigerator Oil
3~100
3~100
R-410A
R-410A
11.3+11.7+11.7
11.5+11.7+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
44
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
TL(E)
Casing Color
127,000
Btu / h
505,000
kW
148
kW
147
kcal / h
146,000
Btu / h
580,000
kW
170
Without(E)
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Piston
Displacement
Comp.
Number of
Revolutions
YL(E)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
TL(E)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Motor OutputNumber
of Units
Starting Method
Soft Start
Type
Fan
Propeller Fan
Motor Output
kW
(0.752)+(0.752)+(0.752)
m/min
239+239+239
Liquid Pipe
mm
Gas Pipe
mm
Drive
Connecting
Pipes
Direct Drive
kg
Safety Devices
341+341+341
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method
Deicer
Capacity Control
Refrigerant Name
Refrigerant
RXYQ54PTL(E)
RXYQ18PTL(E)+RXYQ18PTL(E)+RXYQ18PTL(E)
kcal / h
RXYQ54PAYL(E)
RXYQ18PAYL(E)+RXYQ18PAYL(E)+RXYQ18PAYL(E)
Charge
kg
Control
3~100
R-410A
11.7+11.7+11.7
Electronic Expansion Valve
Refrigerator Oil
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
45
Specifications
Si34-803
Heat Pump 60Hz High COP Series (Energy Saving Series) <RXYQ-P(A)H>
Model Name (Combination Unit)
Model Name (Independent Unit)
Model Name (Combination Unit)
Model Name (Independent Unit)
YL(E)
TL(E)
RXYQ16PAHYL(E)
RXYQ18PAHYL(E)
RXYQ8PAYL(E)+RXYQ8PAYL(E)
RXYQ8PAYL(E)+RXYQ10PAYL(E)
RXYQ16PHTL(E)
RXYQ18PHTL(E)
RXYQ8PTL(E)+RXYQ8PTL(E)
RXYQ8PTL(E)+RXYQ10PTL(E)
kcal / h
38,800
43,600
Btu / h
154,000
173,000
kW
45.1
50.7
kW
44.8
50.4
3 Heating Capacity
Casing Color
kcal / h
43,000
48,600
Btu / h
171,000
193,000
kW
50.0
56.5
Without(E)
With(E)
mm
(1680930765)+(1680930765)
(1680930765)+(1680930765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
Piston
Displacement
m/h
Number of
Revolutions
r.p.m
(16.90)+(16.90)
(16.90)+(13.34+12.52)
TL(E)
(16.90)+(16.90)
(16.90)+(13.34+12.52)
YL(E)
(7980)+(7980)
(7980)+(6300, 3450)
TL(E)
(7980)+(7980)
(7980)+(6300, 3450)
kW
(4.51)+(4.51)
(4.51)+((1.4+4.5)1)
Starting Method
Type
Soft start
Propeller Fan
Propeller Fan
(0.751)+(0.751)
kW
(0.751)+(0.751)
m/min
180+180
180+185
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+205
205+249
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
YL(E)
Motor OutputNumber
of Units
Fan
Charge
kg
Control
Refrigerator Oil
10~100
8~100
R-410A
R-410A
7.2+7.2
7.2+7.9
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
46
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
TL(E)
RXYQ24PAHYL(E)
RXYQ26PAHYL(E)
RXYQ8PAYL(E)+RXYQ8PAYL(E)+RXYQ8PAYL(E)
RXYQ8PAYL(E)+RXYQ8PAYL(E)+RXYQ10PAYL(E)
RXYQ24PHTL(E)
RXYQ26PHTL(E)
RXYQ8PTL(E)+RXYQ8PTL(E)+RXYQ8PTL(E)
RXYQ8PTL(E)+RXYQ8PTL(E)+RXYQ10PTL(E)
kcal / h
58,100
63,000
Btu / h
231,000
250,000
kW
67.6
73.2
kW
67.2
72.8
3 Heating Capacity
Casing Color
kcal / h
64,500
70,100
Btu / h
260,000
278,000
kW
75.0
81.5
Without(E)
With(E)
mm
(1680930765)+(1680930765)+(1680930765)
(1680930765)+(1680930765)+(1680930765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(16.90)+(16.90)+(16.90)
(16.90)+(16.90)+(13.34+12.52)
TL(E)
(16.90)+(16.90)+(16.90)
(16.90)+(16.90)+(13.34+12.52)
YL(E)
(7980)+(7980)+(7980)
(7980)+(7980)+(6300, 3450)
TL(E)
(7980)+(7980)+(7980)
(7980)+(7980)+(6300, 3450)
kW
(4.51)+(4.51)+(4.51)
(4.51)+(4.51)+((1.4+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Propeller Fan
kW
(0.751)+(0.751)+(0.751)
(0.751)+(0.751)+(0.751)
m/min
180+180+180
180+180+185
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+205+205
205+205+249
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Soft start
Charge
kg
Control
Refrigerator Oil
7~100
6~100
R-410A
R-410A
7.2+7.2+7.2
7.2+7.2+7.9
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
47
Specifications
Si34-803
YL(E)
TL(E)
RXYQ28PAHYL(E)
RXYQ30PAHYL(E)
RXYQ8PAYL(E)+RXYQ8PAYL(E)+RXYQ12PAYL(E)
RXYQ8PAYL(E)+RXYQ10PAYL(E)+RXYQ12PAYL(E)
RXYQ28PHTL(E)
RXYQ30PHTL(E)
RXYQ8PTL(E)+RXYQ8PTL(E)+RXYQ12PTL(E)
RXYQ8PTL(E)+RXYQ10PTL(E)+RXYQ12PTL(E)
kcal / h
67,800
72,600
Btu / h
269,000
288,000
kW
78.8
84.4
kW
78.3
83.9
3 Heating Capacity
Casing Color
kcal / h
75,300
80,800
Btu / h
299,000
321,000
kW
87.5
94.0
Without(E)
With(E)
mm
(1680930765)+(1680930765)+(16801240765)
(1680930765)+(1680930765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
Type
Comp.
Piston
Displacement
m/h
Number of
Revolutions
r.p.m
(16.90)+(16.90)+(13.34+12.52)
(16.90)+(13.34+12.52)+(13.34+12.52)
TL(E)
(16.90)+(16.90)+(13.34+12.52)
(16.90)+(13.34+12.52)+(13.34+12.52)
YL(E)
(7980)+(7980)+(6300, 3450)
TL(E)
(7980)+(7980)+(6300, 3450)
kW
(4.51)+(4.51)+((2.5+4.5)1)
(4.51)+((1.4+4.5)1)+((2.5+4.5)1)
Starting Method
Type
Soft start
Propeller Fan
Propeller Fan
kW
(0.751)+(0.751)+(0.352)
(0.751)+(0.751)+(0.352)
m/min
180+180+233
180+185+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+205+285
205+249+285
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
YL(E)
Motor OutputNumber
of Units
Fan
Charge
kg
Control
Refrigerator Oil
6~100
5~100
R-410A
R-410A
7.2+7.2+9.5
7.2+7.9+9.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
48
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
TL(E)
RXYQ32PAHYL(E)
RXYQ34PAHYL(E)
RXYQ8PAYL(E)+RXYQ12PAYL(E)+RXYQ12PAYL(E)
RXYQ10PAYL(E)+RXYQ12PAYL(E)+RXYQ12PAYL(E)
RXYQ32PHTL(E)
RXYQ34PHTL(E)
RXYQ8PTL(E)+RXYQ12PTL(E)+RXYQ12PTL(E)
RXYQ10PTL(E)+RXYQ12PTL(E)+RXYQ12PTL(E)
kcal / h
77,300
82,200
Btu / h
307,000
326,000
kW
89.9
95.6
kW
89.4
95.0
3 Heating Capacity
Casing Color
kcal / h
86,000
92,000
Btu / h
341,000
365,000
kW
100
107
Without(E)
With(E)
mm
(1680930765)+(16801240765)+(16801240765)
(1680930765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(16.90)+(13.34+12.52)+(13.34+12.52)
(13.34+12.52)+(13.34+12.52)+(13.34+12.52)
TL(E)
(16.90)+(13.34+12.52)+(13.34+12.52)
(13.34+12.52)+(13.34+12.52)+(13.34+12.52)
YL(E)
TL(E)
kW
(4.51)+((2.5+4.5)1)+((2.5+4.5)1)
((1.4+4.5)1)+((2.5+4.5)1)+((2.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Propeller Fan
kW
(0.751)+(0.352)+(0.352)
(0.751)+(0.352)+(0.352)
m/min
180+233+233
185+233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
205+285+285
249+285+285
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Soft start
Charge
kg
Control
Refrigerator Oil
5~100
5~100
R-410A
R-410A
7.2+9.5+9.5
7.9+9.5+9.5
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
49
Specifications
Si34-803
YL(E)
TL(E)
RXYQ36PAHYL(E)
RXYQ38PAHYL(E)
RXYQ12PAYL(E)+RXYQ12PAYL(E)+RXYQ12PAYL(E)
RXYQ12PAYL(E)+RXYQ12PAYL(E)+RXYQ14PAYL(E)
RXYQ36PHTL(E)
RXYQ38PHTL(E)
RXYQ12PTL(E)+RXYQ12PTL(E)+RXYQ12PTL(E)
RXYQ12PTL(E)+RXYQ12PTL(E)+RXYQ14PTL(E)
kcal / h
87,700
92,900
Btu / h
348,000
368,000
kW
102
108
kW
101
107
kcal / h
97,200
103,000
Btu / h
386,000
409,000
kW
113
120
Without(E)
3 Heating Capacity
Casing Color
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(13.34+12.52)+(13.34+12.52)+(13.34+12.52)
(13.34+12.52)+(13.34+12.52)+(12.84+12.52+12.52)
TL(E)
(13.34+12.52)+(13.34+12.52)+(13.34+12.52)
(13.34+12.52)+(13.34+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((2.5+4.5)1)+((2.5+4.5)1)+((2.5+4.5)1)
((2.5+4.5)1)+((2.5+4.5)1)+((1.6+4.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.352)
m/min
233+233+233
233+233+233
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
285+285+285
285+285+329
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Propeller Fan
Motor Output
Drive
Connecting
Pipes
Soft start
Charge
kg
Control
Refrigerator Oil
5~100
4~100
R-410A
R-410A
9.5+9.5+9.5
9.5+9.5+11.3
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
50
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
Casing Color
RXYQ40PHTL(E)
RXYQ42PHTL(E)
RXYQ12PTL(E)+RXYQ12PTL(E)+RXYQ18PTL(E)
kcal / h
97,200
101,000
Btu / h
386,000
399,000
kW
113
117
kW
112
116
kcal / h
108,000
114,000
Btu / h
427,000
450,000
kW
125
132
Without(E)
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(13.34+12.52)+(13.34+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(13.34+12.52)+(12.84+12.52+12.52)
TL(E)
(13.34+12.52)+(13.34+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(13.34+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((2.5+4.5)1)+((2.5+4.5)1)+((2.7+4.5+4.5)1)
((2.5+4.5)1)+((2.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.752)
m/min
233+233+233
233+233+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
285+285+329
285+285+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
RXYQ42PAHYL(E)
RXYQ12PAYL(E)+RXYQ12PAYL(E)+RXYQ18PAYL(E)
RXYQ12PTL(E)+RXYQ12PTL(E)+RXYQ16PTL(E)
TL(E)
RXYQ40PAHYL(E)
RXYQ12PAYL(E)+RXYQ12PAYL(E)+RXYQ16PAYL(E)
Charge
kg
Control
Refrigerator Oil
4~100
4~100
R-410A
R-410A
9.5+9.5+11.5
9.5+9.5+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
51
Specifications
Si34-803
YL(E)
Casing Color
RXYQ44PHTL(E)
RXYQ46PHTL(E)
RXYQ12PTL(E)+RXYQ16PTL(E)+RXYQ18PTL(E)
kcal / h
108,000
111,000
Btu / h
427,000
440,000
kW
125
129
kW
124
128
kcal / h
119,000
124,000
Btu / h
471,000
491,000
kW
138
144
Without(E)
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
TL(E)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
(13.34+12.52)+(12.84+12.52+12.52)+(12.84+12.52+12.52)
YL(E)
TL(E)
kW
((2.5+4.5)1)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
((2.5+4.5)1)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
Type
Piston
Displacement
Comp.
Number of
Revolutions
m/h
r.p.m
Motor OutputNumber
of Units
Starting Method
Type
Fan
Soft start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.752)
m/min
233+233+233
233+233+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
285+329+329
285+329+341
Deicer
Deicer
Refrigerant Name
Refrigerant
Soft start
Motor Output
Drive
Connecting
Pipes
RXYQ46PAHYL(E)
RXYQ12PAYL(E)+RXYQ16PAYL(E)+RXYQ18PAYL(E)
RXYQ12PTL(E)+RXYQ16PTL(E)+RXYQ16PTL(E)
TL(E)
RXYQ44PAHYL(E)
RXYQ12PAYL(E)+RXYQ16PAYL(E)+RXYQ16PAYL(E)
Charge
kg
Control
Refrigerator Oil
4~100
3~100
R-410A
R-410A
9.5+11.5+11.5
9.5+11.5+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
52
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
YL(E)
Casing Color
RXYQ48PHTL(E)
RXYQ50PHTL(E)
RXYQ16PTL(E)+RXYQ16PTL(E)+RXYQ18PTL(E)
kcal / h
117,000
120,000
Btu / h
464,000
478,000
kW
136
140
kW
135
139
kcal / h
129,000
134,000
Btu / h
512,000
532,000
kW
150
156
Without(E)
With(E)
mm
(16801240765)+(16801240765)+(16801240765)
(16801240765)+(16801240765)+(16801240765)
Dimensions: (HWD)
Heat Exchanger
YL(E)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52
+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52
+12.52)
TL(E)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52
+12.52)
(12.84+12.52+12.52)+(12.84+12.52+12.52)+(12.84+12.52
+12.52)
YL(E)
(6060, 3450, 3450)+(6060, 3450, 3450)+(6060, 3450, 3450) (6060, 3450, 3450)+(6060, 3450, 3450)+(6060, 3450, 3450)
TL(E)
(6060, 3450, 3450)+(6060, 3450, 3450)+(6060, 3450, 3450) (6060, 3450, 3450)+(6060, 3450, 3450)+(6060, 3450, 3450)
Type
Comp.
Piston
Displacement
m/h
Number of
Revolutions
r.p.m
Motor OutputNumber
of Units
kW
Starting Method
Type
Fan
((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)
Soft start
Soft start
Propeller Fan
Propeller Fan
kW
(0.352)+(0.352)+(0.352)
(0.352)+(0.352)+(0.752)
m/min
233+233+233
233+233+239
Direct Drive
Direct Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
329+329+329
329+329+341
Deicer
Deicer
Refrigerant Name
Refrigerant
((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Motor Output
Drive
Connecting
Pipes
RXYQ50PAHYL(E)
RXYQ16PAYL(E)+RXYQ16PAYL(E)+RXYQ18PAYL(E)
RXYQ16PTL(E)+RXYQ16PTL(E)+RXYQ16PTL(E)
TL(E)
RXYQ48PAHYL(E)
RXYQ16PAYL(E)+RXYQ16PAYL(E)+RXYQ16PAYL(E)
Charge
kg
Control
Refrigerator Oil
3~100
3~100
R-410A
R-410A
11.5+11.5+11.5
11.5+11.5+11.7
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ16PAHYLE.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
53
Specifications
1.2
Si34-803
Indoor Units
FXFQ25PVE
FXFQ32PVE
FXFQ40PVE
kcal/h
2,500
3,200
4,000
5,000
Btu/h
9,900
12,600
16,000
19,800
kW
2.9
3.7
4.7
5.8
kW
2.8
3.6
4.5
5.6
3 Heating Capacity
kcal/h
2,800
3,400
4,300
5,400
Btu/h
10,900
13,600
17,100
21,500
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
5.0
6.3
mm
246840840
246840840
246840840
246840840
RowsStagesFin Pitch
mm
261.2
261.2
261.2
261.2
Face Area
0.267
0.267
0.267
0.267
QTS48C15M
QTS48C15M
QTS48C15M
QTS48C15M
Turbo Fan
Model
Type
Fan
Turbo Fan
Turbo Fan
Turbo Fan
561
561
561
561
m/min
13/11.5/10
13/11.5/10
15/13/11
16/13.5/11
cfm
459/406/353
459/406/353
530/459/388
565/477/388
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
Polyurethane Form
Polyurethane Form
Polyurethane Form
Polyurethane Form
Liquid Pipes
mm
Gas Pipes
mm
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Drain Pipe
Mass (Weight)
5 Sound Level (HH/H/L) (220-240V)
VP25
19.5
19.5
19.5
30/28.5/27
31/29/27
32/29.5/27
Panel Color
mm
Air Filter
kg
Drawing No.
19.5
Model
Standard Accessories
30/28.5/27
Weight
kg
Refrigerant Control
Dimensions: (HWD)
dBA
Safety Devices
Decoration
Panels
(Option)
FXFQ50PVE
Fuse
Fuse
Fuse
Fuse
BYCP125K-W1
BYCP125K-W1
BYCP125K-W1
BYCP125K-W1
Fresh White
Fresh White
Fresh White
Fresh White
50950950
50950950
50950950
50950950
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
5.5
5.5
5.5
5.5
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
C : 3D060255
Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
54
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXFQ63PVE
FXFQ80PVE
FXFQ100PVE
FXFQ125PVE
kcal/h
6,300
8,000
10,000
12,500
Btu/h
24,900
31,700
39,600
49,500
kW
7.3
9.3
11.6
14.5
kW
7.1
9.0
11.2
14.0
kcal/h
6,900
8,600
10,800
13,800
Btu/h
27,300
34,100
42,700
54,600
kW
8.0
10.0
12.5
16.0
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
mm
246840840
246840840
288840840
288840840
RowsStagesFin Pitch
mm
2101.2
2101.2
2121.2
2121.2
Face Area
0.446
0.446
0.535
0.535
QTS48C15M
QTS48C15M
QTS48C15M
QTS48C15M
Turbo Fan
Model
Type
Fan
Turbo Fan
Turbo Fan
Turbo Fan
561
561
1201
1201
m/min
19/16.5/13.5
21/18/15
32/26/20
33/28/22.5
cfm
671/583/477
742/636/530
1,130/918/706
1,165/989/794
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
Polyurethane Form
Polyurethane Form
Polyurethane Form
Polyurethane Form
Liquid Pipes
mm
Gas Pipes
mm
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Drain Pipe
Mass (Weight)
5 Sound Level (HH/H/L) (220-240V)
VP25
22
25
25
36/33.5/31
43/37.5/32
44/39/34
Panel Color
mm
Air Filter
kg
Drawing No.
22
Model
Standard Accessories
34/31/28
Weight
kg
Refrigerant Control
Dimensions: (HWD)
dBA
Safety Devices
Decoration
Panels
(Option)
Fuse
Fuse
Fuse
Fuse
BYCP125K-W1
BYCP125K-W1
BYCP125K-W1
BYCP125K-W1
Fresh White
Fresh White
Fresh White
Fresh White
50950950
50950950
50950950
50950950
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
5.5
5.5
5.5
5.5
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
Operation Manual.
Installation Manual.
Paper Pattern for
Installation.
Drain Hose. Clamp Metal.
Washer Fixing Plate.
Sealing Pads. Clamps.
Screws. Washer for
Hanging Bracket. Insulation
for Fitting.
Installation Guide.
C : 3D060255
Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
55
Specifications
Si34-803
FXCQ20MVE
FXCQ25MVE
FXCQ32MVE
kcal/h
2,000
2,500
3,200
4,000
Btu/h
7,800
9,900
12,600
16,000
kW
2.3
2.9
3.7
4.7
kW
2.2
2.8
3.6
4.5
kcal/h
2,200
2,800
3,400
4,300
Btu/h
8,500
10,900
13,600
17,100
3 Heating Capacity
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
5.0
mm
305775600
305775600
305775600
305990600
mm
2101.5
2101.5
2101.5
2101.5
Face Area
20.100
20.100
20.100
20.145
D17K2AA1
D17K2AB1
D17K2AB1
2D17K1AA1
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
101
151
151
201
m/min
7/5
9/6.5
9/6.5
12/9
cfm
247/177
318/230
318/230
424/318
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
2.5
Galvanized Steel Plate
RowsStagesFin Pitch
Model
Fan
FXCQ40MVE
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
Liquid Pipes
mm
Gas Pipes
mm
VP25
VP25
VP25
VP25
Drain Pipe
mm
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
kg
26
26
26
31
dBA
32/27
34/28
34/28
34/29
Safety Devices
Refrigerant Control
Model
BYBC32G-W1
BYBC32G-W1
BYBC32G-W1
BYBC50G-W1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
531,030680
531,030680
531,030680
531,245680
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Decoration
Panels
(Option)
Dimensions: (HWD)
mm
Air Filter
Weight
kg
8
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Standard Accessories
Drawing No.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
3D039413
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.
56
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXCQ50MVE
FXCQ63MVE
FXCQ80MVE
FXCQ125MVE
kcal/h
5,000
6,300
8,000
12,500
Btu/h
19,800
24,900
31,700
49,500
kW
5.8
7.3
9.3
14.5
kW
5.6
7.1
9.0
14.0
kcal/h
5,400
6,900
8,600
13,800
Btu/h
21,500
27,300
34,100
54,600
kW
6.3
8.0
10.0
16.0
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
mm
305990600
3051,175600
3051,665600
3051,665600
RowsStagesFin Pitch
mm
2101.5
2101.5
2101.5
2101.5
Face Area
20.145
20.184
20.287
20.287
2D17K1AA1
2D17K2AA1VE
3D17K2AA1
3D17K2AB1
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
201
301
501
851
m/min
12/9
16.5/13
26/21
33/25
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
424/318
582/459
918/741
1,165/883
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Glass Wool/Urethane Foam
Liquid Pipes
mm
Gas Pipes
mm
VP25
VP25
VP25
VP25
Drain Pipe
mm
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
Dia. 32
( External
Internal Dia. 25 )
kg
32
35
47
48
dBA
34/29
37/32
39/34
44/38
Safety Devices
Refrigerant Control
Model
BYBC50G-W1
BYBC63G-W1
BYBC125G-W1
BYBC125G-W1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
531,245680
531,430680
531,920680
531,920680
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Decoration
Panels
(Option)
Dimensions: (HWD)
mm
Air Filter
Weight
kg
8.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Standard Accessories
Drawing No.
9.5
12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
12
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Washer for Hanging
Brackets, Clamp Metal,
Drain Hose, Insulation for
Fitting, Washer Fixing
Plates, Sealing Pads,
Clamps, Screws, Washers.
3D039413
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
57
Specifications
Si34-803
FXKQ25MAVE
FXKQ32MAVE
FXKQ40MAVE
kcal/h
2,500
3,200
4,000
6,300
Btu/h
9,900
12,600
16,000
24,900
kW
2.9
3.7
4.7
7.3
kW
2.8
3.6
4.5
7.1
3 Heating Capacity
kcal/h
2,800
3,400
4,300
6,900
Btu/h
10,900
13,600
17,100
27,300
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
5.0
8.0
mm
2151,110710
2151,110710
2151,110710
2151,310710
RowsStagesFin Pitch
mm
2111.75
2111.75
2111.75
3111.75
Face Area
0.180
0.180
0.180
0.226
3D12H1AN1V1
3D12H1AN1V1
3D12H1AP1V1
4D12H1AJ1V1
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
151
151
201
451
m/min
11/9
11/9
13/10
18/15
cfm
388/318
388/318
459/353
635/530
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
FXKQ63MAVE
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
Polyethylene Foam
Liquid Pipes
mm
Gas Pipes
mm
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Drain Pipe
Machine Weight (Mass)
VP25
kg
31
31
31
34
dBA
38/33
38/33
40/34
42/37
Safety Devices
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Fuse,
Thermal Fuse for Fan Motor
Refrigerant Control
BYK45FJW1
BYK45FJW1
BYK45FJW1
BYK71FJW1
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
701,240800
701,240800
701,240800
701,440800
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Dimensions: (HWD)
mm
Air Filter
Weight
kg
Standard Accessories
Drawing No.
8.5
8.5
8.5
9.5
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
Operation Manual,
Installation Manual, Paper
Pattern for Installation, Drain
Hose, Clamp Metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers, Positioning Jig for
Installation, Insulation for
Hanger Bracket, Air Outlet
Blocking Pad.
3D038813A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
58
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
Slim Ceiling Mounted Duct Type (VE: with Drain Pump, VET: without Drain Pump)
Model
FXDQ20PBVE (T)
FXDQ25PBVE (T)
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
3 Heating Capacity
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
Fan
2.5
3.2
4.0
mm
200700620
200700620
200700620
RowsStagesFin Pitch
mm
2121.5
2121.5
3121.5
Face Area
0.126
0.126
0.126
Model
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
621
621
621
m/min
8.0/7.2/6.4
8.0/7.2/6.4
8.0/7.2/6.4
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXDQ32PBVE (T)
30-10
30-10
30-10
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
kg
23
23
23
dBA
33/31/29
33/31/29
33/31/29
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Standard Accessories
Drawing No.
3D060921A
Note:
1 Indoor temp.: 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp.: 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller. This pressure means High static
pressure - Standard static pressure. (Factory setting is 10 Pa.)
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
7 FXDQ20 / 25 / 32PBVE only.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
59
Specifications
Si34-803
Slim Ceiling Mounted Duct Type (VE: with Drain Pump, VET: without Drain Pump)
Model
FXDQ40NBVE(T)
FXDQ50NBVE(T)
kcal/h
4,000
5,000
6,300
Btu/h
16,000
19,800
24,900
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
3 Heating Capacity
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
Fan
5.0
6.3
8.0
mm
200900620
200900620
2001100620
RowsStagesFin Pitch
mm
3121.5
3121.5
3121.5
Face Area
0.176
0.176
0.227
Model
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
621
1301
1301
m/min
10.5/9.5/8.5
12.5/11.0/10.0
16.5/14.5/13.0
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
FXDQ63NBVE(T)
44-15
44-15
44-15
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
kg
27
28
31
dBA
34/32/30
35/33/31
36/34/32
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Standard Accessories
Drawing No.
3D060921A
Note:
1 Indoor temp.: 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp.: 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m.
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller. This pressure means High static
pressure - Standard static pressure. (Factory setting is 15 Pa.)
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx. 5dBA.
7 FXDQ40 / 50 / 63NBVE only.
60
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXSQ20MVE
FXSQ25MVE
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
3 Heating Capacity
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
mm
300550800
300550800
300550800
mm
3141.75
3141.75
3141.75
Face Area
0.088
0.088
0.088
D18H3A
D18H3A
D18H3A
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
501
501
501
m/min
9/6.5
9/6.5
9.5/7
4 External static
pressure
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
88-39-20
88-39-20
64-39-15
Direct Drive
Direct Drive
Direct Drive
Glass Fiber
Glass Fiber
Glass Fiber
mm
mm
mm
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
kg
30
30
30
dBA
37/32
37/32
38/32
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Model
BYBS32DJW1
BYBS32DJW1
BYBS32DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
mm
55650500
55650500
55650500
kg
2.5
Galvanized Steel Plate
RowsStagesFin Pitch
Model
Fan
FXSQ32MVE
Dimensions: (HWD)
Weight
Standard Accessories
Drawing No.
3D039431
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means High static pressure-Standard -Low static pressure.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
61
Specifications
Si34-803
FXSQ40MVE
FXSQ50MVE
kcal/h
4,000
5,000
6,300
Btu/h
16,000
19,800
24,900
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
3 Heating Capacity
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
6.3
8.0
mm
300700800
300700800
3001,000800
mm
3141.75
3141.75
3141.75
Face Area
0.132
0.132
0.221
D18H2A
D18H2A
2D18H2A
Sirocco Fan
Type
Sirocco Fan
Sirocco Fan
651
851
1251
m/min
11.5/9
15/11
21/15.5
4 External static
pressure
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
88-49-20
88-59-29
88-49-20
Direct Drive
Direct Drive
Direct Drive
Glass Fiber
Glass Fiber
Glass Fiber
mm
mm
mm
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
kg
30
31
41
dBA
38/32
41/36
42/35
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Model
BYBS45DJW1
BYBS45DJW1
BYBS71DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
mm
55800500
55800500
551,100500
kg
3.5
3.5
4.5
5.0
Galvanized Steel Plate
RowsStagesFin Pitch
Model
Fan
FXSQ63MVE
Dimensions: (HWD)
Weight
Standard Accessories
Drawing No.
3D039431
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means High static pressure-Standard -Low static pressure.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
62
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXSQ80MVE
FXSQ100MVE
FXSQ125MVE
kcal/h
8,000
10,000
12,500
Btu/h
31,700
39,600
49,500
kW
9.3
11.6
14.5
kW
9.0
11.2
14.0
kcal/h
8,600
10,800
13,800
Btu/h
34,100
42,700
54,600
kW
10.0
12.5
16.0
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
mm
3001,400800
3001,400800
3001,400800
RowsStagesFin Pitch
mm
3141.75
3141.75
3141.75
Face Area
0.338
0.338
0.338
3D18H2A
3D18H2A
3D18H2A
Model
Type
Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
2251
2251
2251
m/min
27/21.5
28/22
38/28
4 External static
pressure
Pa
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
107-75
78-39
Direct Drive
Direct Drive
Glass Fiber
Glass Fiber
Glass Fiber
mm
mm
mm
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
VP25
(External Dia. 32 Internal Dia. 25)
kg
51
51
52
dBA
43/37
43/37
46/41
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Model
BYBS125DJW1
BYBS125DJW1
BYBS125DJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
mm
551,500500
551,500500
551,500500
kg
6.5
6.5
6.5
113-82
Direct Drive
Dimensions: (HWD)
Weight
Standard Accessories
Drawing No.
3D039431
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means High static pressure-Standard.
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
63
Specifications
Si34-803
FXMQ200MAVE
FXMQ250MAVE
kcal/h
19,800
24,800
Btu/h
78,500
98,300
kW
23.0
28.8
kW
22.4
28.0
kcal/h
21,500
27,100
Btu/h
85,300
107,500
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
31.5
Galvanized Steel Plate
mm
4701,3801,100
4701,3801,100
RowsStagesFin Pitch
mm
3262.0
3262.0
Face Area
0.68
0.68
D13/4G2DA12
D13/4G2DA12
Model
Type
Motor Output Number
of Units
Fan
25.0
Galvanized Steel Plate
Sirocco Fan
Sirocco Fan
3802
3802
m/min
58/50
72/62
cfm
2,047/1,765
2,542/2,189
Pa
221/270-132 4
270/191-147 4
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections Gas Pipes
Drain Pipe
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Glass Fiber
Glass Fiber
mm
Air Filter
Liquid Pipes
Direct Drive
Microprocessor Thermostat for Cooling and Heating
mm
19.1(Brazing Connection)
mm
PS1B
PS1B
kg
137
137
dBA
48/45
48/45
Safety Devices
Fuse.
Thermal Protector for Fan Motor.
Fuse.
Thermal Protector for Fan Motor.
Refrigerant Control
Standard Accessories
Drawing No.
C : 3D038814A
Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
means "High static pressure-Standard".
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
64
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXMQ40PVE
FXMQ50PVE
FXMQ63PVE
kcal/h
4,000
5,000
6,300
8,000
Btu/h
16,000
19,800
24,900
31,700
kW
4.7
5.8
7.3
9.3
kW
4.5
5.6
7.1
9.0
3 Heating Capacity
kcal/h
4,300
5,400
6,900
8,600
Btu/h
17,100
21,500
27,300
34,100
kW
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
5.0
6.3
8.0
10.0
mm
300700700
3001,000700
3001,000700
3001,000700
RowsStagesFin Pitch
mm
3161.75
3161.75
3161.75
3161.75
Face Area
0.148
0.249
0.249
0.249
Model
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Sirocco Fan
1401
3501
3501
3501
m/min
16/13/11
18/16.5/15
19.5/17.5/16
25/22.5/20
cfm
565/459/388
635/582/530
688/618/565
883/794/706
Pa
Drive
Temperature Control
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Liquid Pipes
mm
Gas Pipes
mm
mm
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Air Filter
Piping
Connections
FXMQ80PVE
Drain Pipe
Mass (Weight)
7 Sound Level (HH/H/L)
dBA
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
VP25
kg
28
36
36
36
220V
39/37/35
41/39/37
42/40/38
43/41/39
240V
39/37/35
41/39/37
42/40/38
43/41/39
Fuse.
Fan Driver Overload
Protector.
Fuse.
Fan Driver Overload
Protector.
Fuse.
Fan Driver Overload
Protector.
Fuse.
Fan Driver Overload
Protector.
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Washers.
Screws. Air Discharge
Flange. Air Suction Flange.
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Washers.
Screws. Air Discharge
Flange. Air Suction Flange.
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Washers.
Screws. Air Discharge
Flange. Air Suction Flange.
Operation Manual.
Installation Manual. Drain
Hose. Clamp Metal.
Insulation for Fitting. Sealing
Pads. Clamps. Washers.
Screws. Air Discharge
Flange. Air Suction Flange.
C : 3D060388A
Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
4 External static pressure is changeable in 13 or 14 stages within the ( ) range by remote controller.
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
65
Specifications
Si34-803
FXMQ100PVE
FXMQ125PVE
kcal/h
10,000
12,500
Btu/h
39,600
49,500
kW
11.6
14.5
kW
11.2
14.0
kcal/h
10,800
13,800
Btu/h
42,700
54,600
kW
12.5
16.0
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
mm
3001,400700
3001,400700
RowsStagesFin Pitch
mm
3161.75
3161.75
Face Area
0.383
0.383
Model
Type
Sirocco Fan
Sirocco Fan
3501
3501
m/min
32/27/23
39/33/28
cfm
1,130/953/812
1,377/1,165/988
Pa
Drive
Temperature Control
Direct Drive
Direct Drive
Liquid Pipes
mm
Gas Pipes
mm
mm
VP25
External Dia. 32
Internal Dia. 25
Dia. 32
( External
Internal Dia. 25 )
Air Filter
Piping
Connections
Drain Pipe
Mass (Weight)
7 Sound Level (HH/H/L)
dBA
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
VP25
kg
46
46
220V
43/41/39
44/42/40
240V
43/41/39
44/42/40
Fuse.
Fan Driver Overload Protector.
Fuse.
Fan Driver Overload Protector.
C : 3D060388A
Note:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5 m, level
difference : 0 m.
3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5 m, level difference :
0 m.
4 External static pressure is changeable in 13 or 14 stages within the ( ) range by remote controller.
5 Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its
colorimetric method (gravity method) 50% or more.
6 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
7 Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
66
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXHQ32MAVE
FXHQ63MAVE
FXHQ100MAVE
kcal/h
3,200
6,300
10,000
Btu/h
12,600
24,900
39,600
kW
3.7
7.3
11.6
kW
3.6
7.1
11.2
kcal/h
3,400
6,900
10,800
Btu/h
13,600
27,300
42,700
kW
4.0
8.0
12.5
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
mm
195960680
1951,160680
1951,400680
RowsStagesFin Pitch
mm
2121.75
3121.75
3121.75
Face Area
0.182
0.233
0.293
3D12K1AA1
4D12K1AA1
3D12K2AA1
Sirocco Fan
Model
Type
Fan
Sirocco Fan
Sirocco Fan
621
621
1301
m/min
12/10
17.5/14
25/19.5
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
424/353
618/494
883/688
Direct Drive
Direct Drive
Direct Drive
Glass Wool
Glass Wool
Glass Wool
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
kg
24
28
33
dBA
36/31
39/34
45/37
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
3D038815A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
67
Specifications
Si34-803
FXAQ20MAVE
FXAQ25MAVE
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
3 Heating Capacity
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
White (3.0Y8.5/10.5)
White (3.0Y8.5/10.5)
mm
290795230
290795230
290795230
mm
2141.4
2141.4
2141.4
Face Area
0.161
0.161
0.161
QCL9661M
QCL9661M
QCL9661M
Type
401
401
401
m/min
7.5/4.5
8/5
9/5.5
cfm
265/159
282/177
318/194
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Direct Drive
Direct Drive
Direct Drive
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
mm
Gas Pipes
mm
Drain Pipe
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Liquid Pipes
Piping
Connections
2.5
White (3.0Y8.5/10.5)
RowsStagesFin Pitch
Model
Fan
FXAQ32MAVE
kg
11
11
11
dBA
35/29
36/29
37/29
Fuse
Fuse
Fuse
Standard Accessories
Drawing No.
3D039370B
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length:7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
68
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXAQ40MAVE
FXAQ50MAVE
kcal/h
4,000
5,000
6,300
Btu/h
16,000
19,800
24,900
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
3 Heating Capacity
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
6.3
8.0
White (3.0Y8.5/10.5)
White (3.0Y8.5/10.5)
mm
2901,050230
2901,050230
2901,050230
mm
2141.4
2141.4
2141.4
Face Area
0.213
0.213
0.213
QCL9686M
QCL9686M
QCL9686M
Cross Flow Fan
Type
431
431
431
m/min
12/9
15/12
19/14
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
424/318
530/424
671/494
Direct Drive
Direct Drive
Direct Drive
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
mm
Gas Pipes
mm
Drain Pipe
mm
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
VP13
(External Dia. 18 Internal Dia. 13)
Liquid Pipes
Piping
Connections
5.0
White (3.0Y8.5/10.5)
RowsStagesFin Pitch
Model
Fan
FXAQ63MAVE
kg
14
14
14
dBA
39/34
42/36
46/39
Fuse
Fuse
Fuse
Standard Accessories
Drawing No.
3D039370B
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp; 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
69
Specifications
Si34-803
FXLQ20MAVE
FXLQ25MAVE
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
3 Heating Capacity
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
mm
6001,000222
6001,000222
6001,140222
mm
3141.5
3141.5
3141.5
Face Area
0.159
0.159
0.200
D14B20
D14B20
2D14B13
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
151
151
251
m/min
7/6
7/6
8/6
cfm
247/212
247/212
282/212
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
2.5
Ivory White (5Y7.5/1)
RowsStagesFin Pitch
Model
Fan
FXLQ32MAVE
Direct Drive
Direct Drive
Direct Drive
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
kg
25
25
30
dBA
35/32
35/32
35/32
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Standard Accessories
Drawing No.
3D038816A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
70
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXLQ40MAVE
FXLQ50MAVE
kcal/h
4,000
5,000
6,300
Btu/h
16,000
19,800
24,900
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
3 Heating Capacity
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
6.3
8.0
mm
6001,140222
6001,420222
6001,420222
mm
3141.5
3141.5
3141.5
Face Area
0.200
0.282
0.282
2D14B13
2D14B20
2D14B20
Sirocco Fan
Type
Sirocco Fan
Sirocco Fan
251
351
351
m/min
11/8.5
14/11
16/12
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
5.0
Ivory White (5Y7.5/1)
RowsStagesFin Pitch
Model
Fan
FXLQ63MAVE
388/300
494/388
565/424
Direct Drive
Direct Drive
Direct Drive
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
kg
30
36
36
dBA
38/33
39/34
40/35
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Standard Accessories
Drawing No.
3D038816A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
71
Specifications
Si34-803
FXNQ20MAVE
FXNQ25MAVE
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
kW
2.2
2.8
3.6
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
3 Heating Capacity
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
3.2
4.0
mm
610930220
610930220
6101,070220
mm
3141.5
3141.5
3141.5
Face Area
0.159
0.159
0.200
D14B20
D14B20
2D14B13
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
151
151
251
m/min
7/6
7/6
8/6
cfm
247/212
247/212
282/212
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
2.5
Galvanized Steel Plate
RowsStagesFin Pitch
Model
Fan
FXNQ32MAVE
Direct Drive
Direct Drive
Direct Drive
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
kg
19
19
23
dBA
35/32
35/32
35/32
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Standard Accessories
Drawing No.
3D038817A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
72
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
Specifications
Si34-803
Specifications
FXNQ40MAVE
FXNQ50MAVE
kcal/h
4,000
5,000
6,300
Btu/h
16,000
19,800
24,900
kW
4.7
5.8
7.3
kW
4.5
5.6
7.1
3 Heating Capacity
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
kW
Casing Color
Dimensions: (HWD)
Coil (Cross
Fin Coil)
6.3
8.0
mm
6101,070220
6101,350220
6101,350220
mm
3141.5
3141.5
3141.5
Face Area
0.200
0.282
0.282
2D14B13
2D14B20
2D14B20
Sirocco Fan
Type
Sirocco Fan
Sirocco Fan
251
351
351
m/min
11/8.5
14/11
16/12
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
5.0
Galvanized Steel Plate
RowsStagesFin Pitch
Model
Fan
FXNQ63MAVE
388/300
494/388
565/424
Direct Drive
Direct Drive
Direct Drive
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
kg
23
27
27
dBA
38/33
39/34
40/35
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Standard Accessories
Drawing No.
3D038817A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
73
Specifications
Si34-803
Indoor Unit
FXUQ71MAV1
FXUQ100MAV1
FXUQ125MAV1
Connection Unit
BEVQ71MAVE
BEVQ100MAVE
BEVQ125MAVE
kcal/h
7,100
10,000
12,500
Btu/h
28,300
39,600
49,500
kW
8.3
11.6
14.5
kW
8.0
11.2
14.0
kcal/h
7,700
10,800
12,000
Btu/h
30,700
42,700
47,800
kW
9.0
12.5
14.0
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Fan
mm
165895895
230895895
230895895
RowsStagesFin Pitch
mm
361.5
381.5
381.5
Face Area
0.265
0.353
0.353
Model
QTS48A10M
QTS50B15M
QTS50B15M
Type
Turbo Fan
Turbo Fan
Turbo Fan
451
901
901
m/min
19/14
29/21
32/23
cfm
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Piping
Connections
671/494
1,024/741
1,130/812
Direct Drive
Direct Drive
Direct Drive
Liquid Pipes
mm
Gas Pipes
mm
Drain Pipe
mm
I.D20O.D26
I.D20O.D26
I.D20O.D26
kg
25
31
31
dBA
40/35
43/38
44/39
Standard Accessories
Drawing No.
C:4D045395A
Notes:
1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5m, level
difference: 0m.
3 Indoor temp. : 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference:
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
values are normally somewhat higher during actual operation as a result of ambient conditions.
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
BEV Units
Model
Power Supply
Casing
Dimensions: (HWD)
mm
Piping
Connection
BEVQ125MAVE
1 Phase 50Hz 220~240V
100350225
100350225
100350225
Liquid Pipes
Gas Pipes
Outdoor
Unit
Liquid Pipes
Standard Accessories
74
BEVQ100MAVE
1 Phase 50Hz 220~240V
Indoor
Unit
Drawing No.
BEVQ71MAVE
1 Phase 50Hz 220~240V
kg
3.0
3.0
3.5
4D045387A
4D045387A
4D045388A
Specifications
Si34-803
Specifications
1 Heating Capacity
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
kcal/h
12,000
19,300
24,100
Btu/h
47,800
76,400
95,500
kW
14.0
22.4
28.0
kcal/h
7,700
12,000
15,000
Btu/h
30,400
47,400
59,400
kW
8.9
13.9
17.4
Casing
Dimensions: (HWD)
Coil (Cross
Fin Coil)
mm
4707441,100
4701,3801,100
4701,3801,100
RowsStagesFin
Pitch
mm
3262.0
3262.0
3262.0
Face Area
Model
Type
Motor Output
Number of Units
Fan
0.65
0.65
D13/4G2DA1
D13/4G2DA1
Sirocco Fan
Sirocco Fan
Sirocco Fan
3801
3801
3801
m/min
18
28
35
cfm
635
988
1,236
External Static
Pressure 4
Pa
185
225
205
Direct Drive
Direct Drive
Direct Drive
Glass Fiber
Glass Fiber
Glass Fiber
Liquid Pipes
9.5mm
(Flare Connection)
9.5mm
(Flare Connection)
9.5mm
(Flare Connection)
Gas Pipes
15.9mm
(Flare Connection)
19.1mm
(Brazing Connection)
22.2mm
(Brazing Connection)
(mm)
kg
86
123
123
dBA
42
47
47
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Fuse
Thermal Protector
for Fan Motor
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Piping
Connections
0.28
D13/4G2DA1
Drain Pipe
Machine Weight (Mass)
Sound Level (220V) 3,4
Safety Devices
Refrigerant Control
Standard Accessories
Connectable Outdoor Units 5,6
Drawing No.
RXYQ8~54PAY1
RXYQ8~54PAY1
RXYQ10~54PAY1
C:3D046147A
C:3D046147A
C:3D046147A
Notes:
1. Specifications are based on the following conditions:
Cooling: Outdoor temp. of 33CDB, 28CWB (68% RH). and discharge temp. of 18CDB
Heating: Outdoor temp. of 0CDB, -2.9CWB (50% RH). and discharge temp. of 25CDB
Equivalent reference piping length: 7.5m (0m Horizontal)
At 220V
2. Air intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
Please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
3. Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center.
These values (measured at 220V) are normally somewhat higher during actual operation as a result of
ambient conditions.
4. Valves measured at 220 V.
5. Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the
outdoor unit.
6. It is not possible to connect to the 5 HP outdoor unit. Not available for Heat Recovery type and VRV II-S
series.
This equipment cannot be incorporated into the refrigerant piping system or remote group control of the
VRV II system.
Specifications
Conversion Formulae
kcal/h=kW860
Btu/h=kW3412
cfm=m/min35.3
75
Specifications
76
Si34-803
Specifications
Si34-803
Part 3
Refrigerant Circuit
1. Refrigerant Circuit .................................................................................78
1.1
1.2
1.3
1.4
1.5
RXYQ5P(A) ............................................................................................78
RXYQ8P(A) ............................................................................................80
RXYQ10P(A), 12P(A).............................................................................82
RXYQ14P(A), 16P(A), 18P(A)................................................................84
Outdoor Air Processing Unit FXMQ125MFV1~250MFV1 ......................86
RXYQ5P(A) ............................................................................................87
RXYQ8P(A) ............................................................................................88
RXYQ10P(A) ..........................................................................................89
RXYQ12P(A) ..........................................................................................90
RXYQ14P(A), 16P(A), 18P(A)................................................................91
Refirgerant Circuit
77
Refrigerant Circuit
Si34-803
1. Refrigerant Circuit
1.1
RXYQ5P(A)
No. in
refrigerant
Symbol
system
diagram
Major Function
M1C
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
Y2S
Y4S
Solenoid valve (Injection) SVT Used to cool the compressor by injecting refrigerant when the compressor discharge
temperature is high.
Y3S
4-way valve
S1PH
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the
compressor.
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
R2T
R3T
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
R4T
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
R6T
R7T
Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
superheated degree constant in heating operation, and others.
78
Name
Refirgerant Circuit
Si34-803
Refrigerant Circuit
RXYQ5P(A)
5
4
K
E
6
D
M
3
A
W
G
3D055764D
Refirgerant Circuit
79
Refrigerant Circuit
1.2
Si34-803
RXYQ8P(A)
No. in
refrigerant
Symbol
system
diagram
80
Name
Major Function
M1C
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y2E
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
Y2S
Y3S
4-way valve
S1PH
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to subcool liquid refrigerant from the electronic expansion valve (cooling) or
indoor units (heating).
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
R2T
R3T
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
R4T
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
R5T
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant, and others.
R6T
R7T
Thermistor (Accumulator inlet) Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
superheated degree constant in heating operation, and others.
Refirgerant Circuit
Si34-803
Refrigerant Circuit
RXYQ8P(A)
V
F
T
5
4
7
D
M
6
N
3
W
A
O
J
3D055765D
Refirgerant Circuit
81
Refrigerant Circuit
1.3
Si34-803
RXYQ10P(A), 12P(A)
No. in
refrigerant
Symbol
system
diagram
82
Name
Major Function
M1C
M2C
Standard compressor 1
(STD1)
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y2E
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
Y2S
Y3S
4-way valve
S1PH
S2PH
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to subcool liquid refrigerant from the electronic expansion valve (cooling) or
indoor units (heating).
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
R2T
R31T
R32T
R4T
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
R5T
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant, and others.
R6T
R7T
Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
Thermistor (Accumulator inlet) superheated degree constant in heating operation, and others.
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
Refirgerant Circuit
Si34-803
Refrigerant Circuit
RXYQ10P(A), 12P(A)
F
U
5
6
8
M
7
N
1
G
Q
P
O
2
3D055766E
Refirgerant Circuit
83
Refrigerant Circuit
1.4
Si34-803
No. in
refrigerant
Symbol
system
diagram
84
Name
Major Function
M1C
M2C
Standard compressor 1
(STD1)
M3C
Standard compressor 1
(STD2)
M1F
Inverter fan
Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
speed by using the inverter.
Y1E
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
Y2E
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
Y2S
Y3S
4-way valve
S1PH
S2PH
S3PH
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to subcool liquid refrigerant from the electronic expansion valve (cooling) or
indoor units (heating).
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the STD2
compressor.
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.
R1T
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
R2T
R31T
R32T
R33T
R4T
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
R5T
Used to detect gas pipe temperature on the evaporation side of subcooling heat
exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant, and others.
R6T
R7T
Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
Thermistor (Accumulator inlet) superheated degree constant in heating operation, and others.
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
Refirgerant Circuit
Si34-803
Refrigerant Circuit
7
E
F
6
9
U
D
N
8
G
1
P
J
O
2
3D050785C
Refirgerant Circuit
85
Refrigerant Circuit
1.5
Si34-803
Th3
Th2
C
Th1
4D018650B
Symbol
Name
Y1E
Motorized valve
Y1S
Solenoid valve
Capillary tube
Main function
Used to control the flow rate of refrigerant, and
make the SH control while in cooling or the SC
control while in heating.
Used to bypass hot gas while in heating with
thermostat OFF.
Used to reduce pressure from high to low in
bypassing hot gas.
Thermistor
86
Code
Symbol
Th1
R1T
Th2
R2T
Th3
R3T
Name
Suction air temperature
thermistor
Liquid pipe temperature
thermistor
Gas pipe temperature
thermistor
Th4
R4T
Discharge air
temperature thermistor
Main function
Used to turn ON or OFF the thermostat and select
cooling or heating operation.
Used to control the opening degree of EV (Y1F)
under the SC control.
Used to control the opening degree of EV (Y1E)
under the SH control.
Used to control the electric expansion valve
opening and thermostat ON/OFF so as to keep the
discharge air temperature at the set temperature.
Refirgerant Circuit
Si34-803
RXYQ5P(A)
Plan
Accumulator ass'y
Heat exchanger
ACCUMULATOR
THERMISTOR
Front View
THERMISTOR
R7T
4 way valve
(Y3S)
THERMISTOR
THERMISTOR
THERMISTOR
Solenoid valve (Accumulator oil return)
(Y2S)
THERMISTOR
(R6T)
Refirgerant Circuit
87
2.2
Si34-803
RXYQ8P(A)
Plan
Heat exchanger
Accumulator
THERMISTOR
Front View
THERMISTOR
THERMISTOR
ELECTRONIC
ELECTRONIC
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
88
Refirgerant Circuit
Si34-803
2.3
RXYQ10P(A)
Plan
Accumulator
Heat exchanger
THERMISTOR
THERMISTOR
Front View
THERMISTOR
THERMISTOR
ELECTRONIC
ELECTRONIC
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
Refirgerant Circuit
89
2.4
Si34-803
RXYQ12P(A)
Plan
Heat exchanger
Accumulator
Front View
FAN MOTOR
(M2F)
FAN MOTOR
(M1F)
THERMISTOR
(R5T)
THERMISTOR
(R7T)
(S1NPH)
ELECTRONIC
(Y2E)
ELECTRONIC
(Y1E)
THERMISTOR
(Y3S)
(R1T)
(Y1S)
THERMISTOR
(R4T)
THERMISTOR
(R6T)
(M1C)
(S1NPL)
(Y2S)
(E2HC)
(E1HC)
(M2C)
THERMISTOR
(R2T)
90
(M1C)
(M2C)
Refirgerant Circuit
Si34-803
2.5
Plan
Heat exchanger
Accumulator
THERMISTOR
THERMISTOR
THERMISTOR
Front View
THERMISTOR
THERMISTOR
ELECTRONIC
ELECTRONIC
THERMISTOR
THERMISTOR
THERMISTOR
THERMISTOR
Refirgerant Circuit
91
Si34-803
Fan ON
" ON "
Fan OFF
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
EV:Nomal
control
Filter
Filter
92
Filter
EV:0pls
Filter
Filter
EV:0pls
Filter
Refirgerant Circuit
Si34-803
Fan OFF
Fan ON
" OFF "
" ON "
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
Filter
Refirgerant Circuit
" ON "
Heat exchanger
Filter
EV:224pls
Filter
Filter
EV:Nomal
Filter
93
Si34-803
Fan OFF
" ON "
Fan OFF
Fan OFF
" ON "
Heat exchanger
Heat exchanger
Fan
Fan
Fan
EV:416pls
Filter
EV:256pls
Filter
Filter
EV:416pls
Filter
Indoor unit
Indoor unit
Thermostat "ON"
94
Heat exchanger
Filter
Filter
Refirgerant Circuit
Si34-803
Heating Operation
Indoor unit operation
FanLL
Fan ON
" ON "
Fan OFF
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
EV:Nomal
control
Filter
EV:200pls
Filter
Refirgerant Circuit
Filter
EV:200pls
Filter
Filter
Filter
95
Si34-803
RXYQ8P(A)
Cooling Operation
Indoor unit operation
Fan ON
Fan ON
" ON "
Fan OFF
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
Filter
Filter
EV:0pls
Filter
Filter
EV:0pls
Filter
Thermostat "ON"
COMPRESSOR
96
Refirgerant Circuit
Si34-803
Fan ON
Fan ON
" OFF "
" ON "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
EV:224pls
Filter
Filter
EV:Nomal
Filter
Filter
Filter
COMPRESSOR
Refirgerant Circuit
97
Si34-803
" ON "
Fan OFF
Heat exchanger
" ON "
Fan OFF
Heat exchanger
Fan
Fan
Fan
EV:416pls
Filter
EV:256pls
Filter
Filter
EV:416pls
Filter
Filter
Filter
COMPRESSOR
98
Refirgerant Circuit
Si34-803
Heating Operation
Indoor unit operation
Fan ON
Fan LL
" ON "
Fan OFF
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
EV:200pls
Filter
Filter
EV:200pls
Filter
Thermostat "ON"
Filter
Filter
COMPRESSOR
Refirgerant Circuit
99
Si34-803
RXYQ10P(A), 12P(A)
Cooling Operation
Indoor unit operation
Fan ON
Fan ON
" ON "
" ON "
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
Filter
100
Fan OFF
Heat exchanger
Filter
EV:0pls
Filter
Filter
EV:0pls
Filter
Refirgerant Circuit
Si34-803
Fan ON
Fan ON
" OFF "
" ON "
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
EV:224pls
Filter
Refirgerant Circuit
" ON "
Heat exchanger
Filter
EV:Nomal
Filter
Filter
Filter
101
Si34-803
" ON "
Fan OFF
Heat exchanger
" ON "
Fan OFF
Heat exchanger
Fan
Fan
Fan
EV:416pls
Filter
EV:256pls
Filter
102
Filter
EV:416pls
Filter
Filter
Filter
Refirgerant Circuit
Si34-803
Heating Operation
Indoor unit operation
Fan ON
Fan LL
" ON "
" ON "
Heat exchanger
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
EV:200pls
Filter
Refirgerant Circuit
Fan OFF
Filter
EV:200pls
Filter
Filter
Filter
103
Si34-803
Fan ON
" ON "
" ON "
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
EV:Nomal
control
Filter
104
Fan OFF
Heat exchanger
Filter
EV:0pls
Filter
Filter
EV:0pls
Filter
Refirgerant Circuit
Si34-803
Fan OFF
Fan ON
" ON "
Heat exchanger
Fan
Fan
Fan
EV:Nomal
control
Filter
EV:224pls
Filter
Filter
EV:Nomal
Filter
Indoor unit
Indoor unit
Thermostat "ON"
Refirgerant Circuit
" ON "
Heat exchanger
Filter
Filter
105
Si34-803
" ON "
Fan OFF
Heat exchanger
" ON "
Fan OFF
Heat exchanger
Fan
Fan
Fan
EV:416pls
Filter
106
EV:256pls
Filter
Filter
EV:416pls
Filter
Indoor unit
Thermostat "ON"
Indoor unit
Filter
Filter
Refirgerant Circuit
Si34-803
Heating Operation
Indoor unit operation
Fan ON
Heat exchanger
Heat exchanger
Fan
Fan
Fan
Filter
Refirgerant Circuit
Fan LL
" OFF "
Fan OFF
Heat exchanger
EV:control
Nomal
" ON "
EV:200pls
Filter
Filter
EV:200pls
Filter
Indoor unit
Thermostat "ON"
Indoor unit
Filter
Filter
107
108
Si34-803
Refirgerant Circuit
Si34-803
Part 4
Function
1. Function general .................................................................................110
1.1 Symbol .................................................................................................110
1.2 Operation Mode....................................................................................111
2. Basic Control.......................................................................................112
2.1
2.2
2.3
2.4
2.5
3. Special Control....................................................................................143
3.1
3.2
3.3
3.4
3.5
3.6
3.7
5. Other Control.......................................................................................157
5.1
5.2
5.3
5.4
Function
Function general
Si34-803
1. Function general
1.1
Symbol
Symbol
Electric symbol
Description or function
20S1
Y3S
DSH
DSHi
DSHs
EV
EV1
Y1E
EV2
Y2E
HTDi
HTDs
Pc
S1NPH
Pe
S1NPL
SH
SHS
SVO
Y2S
SVP
Y1S
SVT
Y4S
Ta
R1T (A1P)
Tb
R4T
Ts2
R2T
Suction pipe temperature detected with the suction pipe thermistor (R2T)
Tsh
R5T ()
Temperature detected with the subcooling heat exchanger outlet thermistor (R5T)
Tc
TcS
Target temperature of Tc
Te
TeS
Target temperature of Te
Tfin
R1T
Tl
R6T
Liquid pipe temperature detected with the liquid pipe thermistor (R6T)
Tp
Ts1
R7T
110
Function
Si34-803
1.2
Function general
Operation Mode
Operation in
stop mode
Indoor unit stop or
thermostat OFF
Pressure
equalization
prior to startup
Startup control
Operation mode
changeover
(After completion of
startup control)
Normal operation
Compressor PI control
Motorized valve PI control
Protection control
Cooling
After completion of
startup control
Malfunction/
Standby
(Retry)
Pump-down
residual
operation
Malfunction/
Standby (Retry)
in operation
Malfunction/
Standby (Retry)
Oil return IN
conditions are met.
Yes
No
Outdoor unit
rotation
Defrost IN
conditions are met.
Yes
Defrosting operation
No
Operation mode changeover
(after completion of oil return
or defrost control)
*)
In the event indoor unit stops or
the thermostat turns OFF while in
oil return operation or defrosting
operation, pump-down residual
operation is performed on
completion of the oil return
operation or defrosting operation.
Function
111
Basic Control
Si34-803
2. Basic Control
2.1
Normal Operation
Compressor
20S1
EV1
EV2
(Y2E)
PI control
PI control
SVP
(Y1S)
OFF
(Y2S)
ON
Part Name
Symbol
(Electric
Symbol)
Normal cooling
Remote controller setting
OFF
Remote controller setting
Normal opening *1
0 pls
0 pls
Normal heating
Remote controller setting
OFF
LL
Normal opening *2
200 pls
200 pls
112
Function
Si34-803
2.2
Basic Control
Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te set value (Make this setting while in Setting
mode 2.)
Te setting
L
M (Normal)
H
(factory
setting)
3
6
9
[Heating operation]
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Te set value (Make this setting while in Setting
mode 2.)
Tc setting
L
M (Normal)
H
(factory
setting)
43
46
49
Function
113
Basic Control
Si34-803
Operating Priority and Rotation of Compressors (For multi standard connection system)
Each compressor operates in the following order of priority.
In the case of multi-outdoor-unit system, each compressor operates in any of Pattern 1
through Pattern 3 according to the rotation of outdoor units.
Pattern 1
Pattern 2
RXYQ8P(A)
RXYQ5P(A)
No. 1
No. 1
INV
INV
Pattern 3
RXYQ10P(A)
RXYQ12P(A)
No. 1 No. 2
No. 1 No. 2
INV
INV
INV
STD1
RXYQ22P(A)
RXYQ20P(A)
STD1
STD1 STD2
RXYQ24P(A), 26P(A)
No. 1
No. 2 No. 3
No. 1 No. 3
No. 2 No. 4
No. 1
No. 2
No. 1 No. 3
No. 2 No. 4
No. 1 No. 3
No. 2
INV
INV
INV
INV
INV
STD1
STD1
STD1
INV
No. 1 No. 3
No. 2 No. 4
INV
STD1
INV
STD1 STD2
STD1 STD2
INV
STD1 STD2
INV
STD1 STD2
RXYQ38P(A)
No. 1
No. 2
No. 4
No. 3
No. 1
No. 4
No. 2
No. 3
No. 5
INV
114
INV
STD1
INV
STD1 STD2
Function
Si34-803
Basic Control
No. 1
No. 3
No. 2
INV
INV
STD1 STD2
INV
STD1 STD2
No. 1 No. 4
No. 3 No. 6
No. 2 No. 5
INV
INV
INV
STD1
STD1 STD2
STD1 STD2
INV
INV
INV
STD1 STD2
STD1 STD2
STD1 STD2
*
In the case of combination of 3 outdoor units, the above diagram shows master unit, slave unit 1, and slave unit 2
from left to right.
Compressors may operate in any pattern other than those mentioned above according to the operating status.
Function
115
Basic Control
Si34-803
Compressor Step Control (Multi outdoor unit connection is available on the standard connection system)
Compressor operations vary with the following steps according to information in "2.2 Compressor PI Control".
Furthermore, the operating priority of compressors is subject to information in " Operating Priority and Rotation of
Compressors".
50Hz
Stand-alone installation
RXYQ5PAY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
RXYQ8PAY1
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
RXYQ18PAY1
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
INV
STD1
STD2
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
INV
STD1
STD2
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Notes:
1. INV : Inverter compressor
STD1 : Standard compressor 1
STD2 : Standard compressor 2
2. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
116
Function
Si34-803
Basic Control
RXYQ22PAY1 (10+12HP)
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STD
STEP
No.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STEP
No.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
117
Basic Control
Si34-803
RXYQ26PAY1 (8+18HP)
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
118
Function
Si34-803
Basic Control
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
119
Basic Control
Si34-803
RXYQ36PAY1 (18+18HP)
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
120
Function
Si34-803
Basic Control
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
121
Basic Control
Si34-803
RXYQ44PAY1 (8+18+18HP)
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
122
Function
Si34-803
Basic Control
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
123
Basic Control
Si34-803
RXYQ54PAY1 (18+18+18HP)
(To increase Step No.)
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
124
Function
Si34-803
Basic Control
60Hz
Stand-alone installation
RXYQ5PAYL, PTL
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
RXYQ8PAYL, PTL
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
RXYQ18PAYL, PTL
INV
STD1
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
INV
STD1
STD2
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
INV
STD1
STD2
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Notes:
1. INV : Inverter compressor
STD1 : Standard compressor 1
STD2 : Standard compressor 2
2. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
125
Basic Control
Si34-803
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
126
Function
Si34-803
Basic Control
RXYQ26PAYL,PTL (8+18HP)
(To decrease Step No.)
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
ON 2
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
127
Basic Control
Si34-803
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
ON 3
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
128
Function
Si34-803
Basic Control
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
144 Hz
158 Hz
166 Hz
176 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
80 Hz
88 Hz
92 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
132 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
129
Basic Control
Si34-803
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
210 Hz
210 Hz
210 Hz
210 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
202 Hz
202 Hz
202 Hz
202 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
202 Hz
202 Hz
202 Hz
202 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
130
Function
Si34-803
Basic Control
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
218 Hz
232 Hz
248 Hz
266 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
ON 4
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
131
Basic Control
Si34-803
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
210 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
202 Hz
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
132
Function
Si34-803
Basic Control
Master
unit
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit1
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit2
INV
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
110 Hz
116 Hz
124 Hz
80 Hz
88 Hz
96 Hz
104 Hz
116 Hz
124 Hz
132 Hz
88 Hz
96 Hz
104 Hz
124 Hz
144 Hz
92 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
STEP
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
Master
unit
INV
52 Hz
56 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit1
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
70 Hz
74 Hz
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
Slave
unit2
INV
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
52 Hz
56 Hz
62 Hz
66 Hz
68 Hz
70 Hz
74 Hz
80 Hz
88 Hz
96 Hz
52 Hz
62 Hz
68 Hz
74 Hz
80 Hz
88 Hz
96 Hz
104 Hz
52 Hz
62 Hz
74 Hz
88 Hz
96 Hz
52 Hz
62 Hz
74 Hz
92 Hz
104 Hz
52 Hz
62 Hz
74 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
52 Hz
68 Hz
80 Hz
96 Hz
104 Hz
116 Hz
124 Hz
144 Hz
158 Hz
166 Hz
176 Hz
188 Hz
202 Hz
STD
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 1
ON 2
ON 2
ON 2
ON 2
ON 2
ON 3
ON 3
ON 3
ON 3
ON 3
ON 4
ON 4
ON 4
ON 4
ON 4
ON 5
ON 5
ON 5
ON 5
ON 5
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
ON 6
Notes:
1. INV : Inverter compressor
STD : Standard compressor
Figures after ON represent the number of STD compressors in operation.
2. Master unit, and slave unit in this section are the names for control, and they will be transferred according to the
priority of rotation system.
3. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Function
133
Basic Control
Si34-803
134
Function
Si34-803
Basic Control
Function
135
Basic Control
Si34-803
136
Function
Si34-803
Basic Control
Function
137
Basic Control
Si34-803
138
Function
Si34-803
Basic Control
Function
139
Basic Control
Si34-803
140
Function
Si34-803
2.3
Basic Control
The optimum initial value of the evaporator outlet superheated degree is 5C, but varies
depending on the discharge pipe superheated degree of inverter compressor.
2.4
Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
Fan revolutions (rpm)
STEP
No.
0
1
2
3
4
5
6
7
8
RXYQ5P(A)
RXYQ8P(A)
RXYQ10P(A)
0
285
315
360
450
570
710
Cooling: 951
Heating: 941
Cooling: 951
Heating: 941
0
350
370
400
450
540
670
0
350
370
400
460
560
680
Cooling: 821
Heating: 800
Cooling: 821
Heating: 800
760
Cooling: 796
Heating: 780
RXYQ12P(A)
RXYQ14P(A)
FAN1 FAN2
0
0
230
0
380
0
290
260
375
345
570
540
720
690
RXYQ16P(A)
RXYQ18P(A)
FAN1
0
230
380
290
375
570
720
FAN2
0
0
0
260
345
540
690
FAN1
0
395
460
570
385
550
800
FAN2
0
0
0
0
355
520
770
1091
1061
1091
1061
1136
1106
1136
1106
1136
1106
1166
1136
* Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
Function
141
Basic Control
2.5
Si34-803
Pc<2.75MPa
Pc>3.24MPa
PI control
Lapse of 20 sec.
PI control
Hold the
-1 step on
+1 step on
current step on
outdoor unit fan
outdoor unit fan
outdoor unit fan
PI control
Lapse of 20 sec.
142
Function
Si34-803
Special Control
3. Special Control
3.1
Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
Pressure equalization
control prior to startup
STEP1
STEP2
Compressor
0 Hz
52 Hz
+ OFF + OFF
STEP4
Ta<20C: OFF
Ta20C: STEP4
Holds
OFF
OFF
0 pls
480 pls
480 pls
0 pls
0 pls
0 pls
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Ending conditions
A lapse of 10 sec.
OR
Pressure equalization
control prior to startup
STEP1
STEP2
Compressor
0 Hz
52 Hz
+ OFF + OFF
STEP4
STEP8
STEP8
Holds
ON
ON
0 pls
0 pls
0 pls
0 pls
0 pls
0 pls
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Ending conditions
A lapse of 10 sec.
OR
Function
143
Special Control
3.2
Si34-803
For startup, oil return operation, or setup after defrosting, start up multiple compressors at a high speed according to the
conditions of indoor units with thermostat ON, thus maximizing the equipment capacity.
INV
STD
25
20
Pc
9
15
Pressure
8
7
10
Number of
compressors
6
5
Pe
5
4
3
Time
144
Function
Si34-803
3.3
Special Control
In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil flown out
from the compressor to the system side.
Post-oil-return operation
Compressor
5 HP: 52 Hz
( Low pressure constant
control)
Other model:
52 Hz + ON + ON
Take the current step as the
( Low pressure
upper limit.
constant control)
Maintain number of
compressors in oil
return preparation
operation ON
Fan control (Normal cooling) Fan control (Normal cooling) Fan control (Normal cooling)
OFF
OFF
OFF
480 pls
480 pls
480 pls
SH control
0 pls
0 pls
OFF
OFF
OFF
ON
ON
ON
Ending conditions
20 sec.
or
3 min.
Ts - Te<5C
or
3 min.
Pe<0.6MPa
HTdi>110C
Fan
Function
Thermostat ON unit
Stopping unit
OFF
Thermostat ON unit
Normal opening
Stopping unit
224 pls
145
Special Control
Si34-803
Post-oil-return operation
Compressor
176 Hz + ON + ON
STEP7
or
STEP8
OFF
STEP8
ON
OFF
ON
480 pls
55 pls
SH control
0 pls
0 pls
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
Ending conditions
170 sec.
or
4 min.
Ts - Te<5C
or
10 sec.
Pc - Pe>0.4MPa
Fan
146
Thermostat ON unit
OFF
Stopping unit
OFF
OFF
Thermostat ON unit
Stopping unit
256 pls
Function
Si34-803
3.4
Special Control
Defrosting Operation
To defrost the outdoor unit heat exchanger while in Evaporator, the defrost operation is conducted to recover the
heating capacity.
[Start conditions]
Referring to the set conditions for the following items, start the defrosting operation.
Heat transfer coefficient of the outdoor unit heat exchanger
Heat exchange temperature (Tb)
Timer (Set to two hours at minimum.)
Furthermore, the heat transfer coefficient of the outdoor unit Evaporator is computed from Tc, Te, and compressor
loads.
Defrost preparation
operation
Defrost operation
Compressor
176 Hz + ON + ON
STEP7
or
STEP8
OFF
STEP8
ON
OFF
ON
480 pls
55 pls
0 pls
0 pls
0 pls
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
Ending conditions
170 sec.
or
10 min.
Tb>11C
or
10 sec.
Pc - Pe>0.4MPa
Fan
Function
During defrost
Thermostat ON unit
OFF
Stopping unit
OFF
OFF
Thermostat ON unit
Stopping unit
256 pls
147
Special Control
3.5
Si34-803
Compressor
OFF
Fan control
OFF
OFF
OFF
480 pls
0 pls
0 pls
0 pls
OFF
OFF
ON
ON
Ending conditions
or
5 min.
Master Unit Pe<0.49 MPa
Master Unit Td>110C
Master Unit Pc>2.94 MPa
Compressor
OFF
STEP7
STEP4
ON
ON
0 pls
0 pls
0 pls
0 pls
OFF
OFF
ON
ON
Ending conditions
or
3 min.
Master Unit Pe<0.25 MPa
Master Unit Td>110C
Master Unit Pc>2.94 MPa
148
Function
Si34-803
3.6
Special Control
Standby
Operation
Compressor
OFF
Ta>30C: STEP4
Ta30C: OFF
Holds
0 pls
0 pls
OFF
OFF
OFF
Ending conditions
2 min.
Function
Discharge pipe
temperature > 75C
Crankcase heater
ON
149
Special Control
3.7
Si34-803
Stopping Operation
Operation
Compressor
OFF
OFF
Holds
0 pls
0 pls
OFF
OFF
OFF
Ending conditions
Judgment Criteria
Malfunction Code
0.07MPa
E4
4.0MPa
E3
135C
F3
U1
L8
93C
L4
150
Function
Si34-803
Special Control
Operation
Compressor
OFF
OFF
ON
0 pls
0 pls
OFF
OFF
OFF
Ending conditions
Function
151
Protection Control
Si34-803
4. Protection Control
4.1
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
High pressure not limited
Pc: HP pressure sensor detection
value for each outdoor unit
Pc>3.43MPa
INV upper limit frequency:
3-step down from current
compressor rps
(Slave unit: 3-step down as well)
After 10 sec.
Pc>3.43MPa
Pc<3.24MPa
Current step maintained
Pc>3.55MPa
After 15 sec.
After 10 sec.
Pc>3.64MPa
STD compressor
standby
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
High pressure not limited
Pc>3.10MPa
Pc<2.9MPa
System load down 1 steps
After 10 sec.
Pc>3.10MPa
Pc<3.0MPa
After 60 sec.
Pc<2.52MPa
Pc>3.64MPa
152
Function
Si34-803
4.2
Protection Control
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
Low pressure not limited
Pe<0.34MPa
Pe>0.39MPa
Pe<0.15MPa
Pe>0.30MPa
Pe<0.25MPa
Hot gas SVP = ON
Master unit:52 Hz + OFF + OFF
Slave unit:Stop
Pe<0.07MPa
When occurring 4 times within 30 min.,
the malfunction code E4 is output.
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
Pe: LP pressure sensor detection
value for each outdoor unit
Pe<0.17 MPa
INV upper limit frequency:
3-step down from current
compressor frequency
&
Pe >0.23 MPa
INV upper limit Hz = MAX
Pe<0.12MPa
Pe>0.17MPa
After 10 sec.
Pe<0.17 MPa
Low pressure limited
Pe<0.13 MPa
Pe >0.20 MPa
After 15 sec.
After 10 sec.
52 Hz + OFF + OFF
Pe<0.07 MPa
Function
153
Protection Control
4.3
Si34-803
Each compressor performs the discharge pipe temperature protection control individually
in the following sequence.
[INV compressor]
Normal operation
or
HTdi>115C
Tp>135C
INV upper limit frequency:
1-step down from current
compressor rps
&
HTdi<100C
Tp<110C
After 30 sec.
or
HTdi>115C
Tp>135C
&
HTdi>130C
HTdi>120C
or
for 90 sec.
or more.
Tp>130C
HTdi<110C
Tp<125C
RXYQ5P(A)Y1: 52 Hz
Other models:
INV62 Hz + OFF + OFF
or
HTdi>135C
HTdi>120C for 10 min. or more.
Discharge pipe
temperature standby (for
a period of 10 minutes)
[STD compressor]
HTds : Value of STD compressor discharge
pipe temperature ( Tds) compensated
with outdoor air temperature
Tp : Value of compressor port temperature
calculated by Tc and Te , and suction
superheated degree.
or
Applicable STD
compressor stops.
After 10 min.
154
Function
Si34-803
4.4
Protection Control
In the case of multi-outdoor-unit system, each INV compressor performs these controls in
the following sequence.
&
Tfin>84C
INV upper limit frequency: 1-step /
1 min down from current compressor
rps
&
Tfin>84C
Under fin temperature
protection control
Tfin<81C
INV upper limit rps = max
Tfin>93C
Function
155
Protection Control
4.5
Si34-803
STD compressor ON
Demand to operate.
4.6
SVT = OFF
HTdi: Correction value of the discharge pipe
HTdi>112C
HTdi<107C
SVT = ON
156
Function
Si34-803
Other Control
5. Other Control
5.1
or
Example) The following diagram shows outdoor unit rotation in combination of 3 outdoor units.
(in heating) (in cooling)
Starting
control
Normal operation
Normal operation
<In Heating>
Priority
1
Priority
2
Priority
3
Any of outdoor
unit stops for a
period of 20
Normal operation minutes or more.
Priority
3
Function
Priority
1
Priority
2
Priority
2
Normal operation
Priority
1
Priority
2
Priority
3
Priority
1
157
Other Control
Si34-803
<In Cooling>
Normal operation
Normal operation
Priority
3
Priority
1
Priority
1
Priority
2
Priority
3
* Master unit, slave unit 1 and slave unit 2 in this section are the names for installation.
They are determined in installation work, and not changed thereafter. (These names are
different from master unit and slave unit for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be
designated as main unit.
Consequently, The LED display on the main PC board for master unit, slave unit 1 and
slave unit 2 do not change. (Refer to the page 161.)
5.2
Emergency Operation
If the compressor cannot operate, this control inhibits any applicable compressor or outdoor unit
from operating to perform emergency operation only with the operative compressor or outdoor
unit.
Caution
In order to disable the compressor operation due to a failure or else, be sure to do so
in emergency operation mode.
NEVER attempt to disconnect power supply wires from magnetic contactors or else.
(Doing so will operate compressors in combination that disables oil equalization
between the compressors, thus resulting in malfunctions of other normal
compressors.)
158
Function
Si34-803
Other Control
7777777
777777
777
777
777
7
77777
77777
79 (Factory set)
77777
777797
7777777
777777
7777777
77
7777
LED display (7:ON 7:OFF 9:Blink)
H1P----H7P
7777777
777777
77
7777
7777
777777
777777
7 (Factory set)
77777
77777
79
7777777
777777
7777777
77
7777
LED display (7:ON 7:OFF 9:Blink)
H1P----H7P
7777777
777777
77
7777
7777
777777
777777
7 (Factory set)
77777
777797
7777777
777777
7777777
77
7777
For RXYQ14P(A), 16P(A) and 18P(A), if the INV compressor is set to operation prohibition
mode, only a single STD compressor will operate for the convenience of oil equalization.
For RXYQ14P(A), 16P(A) and 18P(A), only the STD1 compressor cannot be put into operation
prohibition mode for the convenience of oil equalization.
For the system with a single outdoor unit (RXYQ8P(A) to 18P(A)), automatic backup operation
is not functional.
Function
159
Other Control
Note :
160
Si34-803
In order to forcedly clear the automatic backup operation, reset the power
supply with the outdoor unit in the stopped state.
Function
Si34-803
Other Control
7777777
7777 7
Master: 77
Slave 1: 7777777 9
Slave 2: 7777777 7
(Factory set)
In order to set the master unit to operation
prohibition mode, set No. 38 of Setting mode 2 to
"MASTER OPERATION PROHIBITION".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
7777777
777777
7777
77777
7
77777
77777
79 (Factory set)
7777
7777
797
7777777
777777
7777777
77
7777
7777777
777777
7777
77777
77777
77777
79 (Factory set)
7777
7777
797
7777777
777777
7777777
77
7777
7777777
777777
777
77777
777
77777
77777
79 (Factory set)
77777
777797
7777777
777777
7777777
77
7777
In the case of multi-outdoor-unit system, Inhibition of operation is not set with each
compressor individually.
In the case of multi-outdoor-unit system, when the above Inhibition of operation is set,
outdoor unit rotation is not functional.
Function
161
Other Control
Si34-803
162
7777777
777777
777
777
777
7
7777
7777
797
77777
77777
79 (Factory set)
7777777
777777
7777777
77
7777
LED display (7:ON 7:OFF 9:Blink)
H1P----H7P
7777777
777777
77
7777
7777
77777
77777
79
77777
777777
77 (Factory set)
7777777
777777
7777777
77
7777
LED display (7:ON 7:OFF 9:Blink)
H1P----H7P
7777777
777777
77
7777
7777
7777
7777
797
77777
777777
77 (Factory set)
7777777
777777
7777777
77
7777
Function
Si34-803
Other Control
<RXYQ20P(A) to 54P(A)>
Cancel to set the master unit from operation
prohibition mode, set No. 38 of Setting mode 2 to
"OFF".
(Procedure)
(1) Press and hold the MODE button (BS1) for a period
of 5 seconds or more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
Function
7777777
777777
7777
77777
7
7777
7777
797
7777
7777
779 (Factory set)
7777777
777777
7777777
77
7777
7777777
777777
7777
77777
7777
7777
797
7777
77777
779 (Factory set)
7777777
777777
7777777
77
7777
7777777
777777
777
77777
777
7777
7777
797
77777
77777
79 (Factory set)
7777777
777777
7777777
77
7777
163
Other Control
5.3
Si34-803
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using Demand 1 Setting or Demand 2 Setting.
To operate the unit with this mode, additional setting of Continuous Demand Setting or
external input by external control adapter is required.
Set item
Demand 1
Demand 2
5.4
Condition
Mode 1
Mode 2
Mode 3
Content
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
The compressor operates at approx. 40% or less of rating.
164
Function
Si34-803
6.1.1 When the Float Switch is Tripped While the Cooling Thermostat is
ON:
1. The objective of residual operation is to completely drain any moisture adhering to the fin of
the indoor unit heat exchanger when the thermostat goes off during cooling operation.
6.1.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF :
Function
165
Si34-803
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
Note:
166
If the float switch is tripped five times in succession, a drain malfunction is determined to have
occurred. AF is then displayed as operation continues.
Function
Si34-803
6.2
P0
P1
P2
P3
P4
Standard Setting
position
P0
P0
P1
P1
P3
P4
P4
P4'
P0
P1
P2
P2
P0'
P1'
P2'
P2
Draft
prevention
position
P0
P4
P3'
P3
P4
P0''
P1''
P2''
P4'' P3''
Prohibited
P0'
P1'
P2'
P3'
P4'
Prohibited
P0''
P1''
P2''
P3''
P4''
Function
167
6.3
Si34-803
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
168
Function
Si34-803
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesnt become cold by widening the range in which thermostat sensor in remote
controller can be used so that suction temperature is higher than the preset temperature.
Ex: When heating Assuming the preset temperature in the figure above is 24C, and
the suction temperature has changed from 18C to 28C (A D):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18C to 25C (A C).
Remote controller thermostat sensor is used for temperatures from 25C to 28C (C D).
And, assuming suction temperature has changed from 28C to 18C (D A):
Remote controller thermostat sensor is used for temperatures from 28C to 23C (D B).
Body thermostat sensor is used for temperatures from 23C to 18C (B A).
Function
169
6.4
Si34-803
Cooling operation:
Heating operation:
While in a single remote controller group control, the body thermostat is only used fro this
control.
Furthermore, while in heating operation, cassette-mounted indoor units conduct the thermostat
control by a value compensated by -2C for the value detected with the body thermostat.
(Through field settings, the thermostat differential setting can be changed from 1C to 0.5C.
For details on the changing procedure, refer to information on page onward.)
6.5
In dry operation
Thermostat OFF
In dry operation
Thermostat OFF
Furthermore, while in dry operation mode, fans operate at L flow rate, stops for a period of six
minutes while the thermostat is OFF, and then return to operation at L flow rate. (This control is
used to prevent a rise in indoor humidity while in thermostat OFF mode.)
170
Function
Si34-803
6.6
(Heating SC=TC-TH1)
Furthermore, the default value of the optimal evaporator outlet superheated degree (condenser
outlet subcooled degree) is 5 deg. However, this default value varies with the operating
performance.
6.7
Fan
H/L remote
controller setting
LL
Louver
OFF
Remote controller
setting
Normal control
Po (Horizontal)
Function
171
6.8
Si34-803
Freeze Prevention
Freeze
Prevention by Off
Cycle (Indoor
Unit)
When the temperature detected by liquid pipe temperature thermistor (R2T) of the indoor unit
heat exchanger drops too low, the unit enters freeze prevention operation in accordance with
the following conditions, and is also set in accordance with the conditions given below.
Conditions for starting freeze prevention: Temperature is -1C or less for total of 40 min., or
temperature is -5C or less for total of 10 min.
Conditions for stopping freeze prevention: Temperature is +7C or more for 10 min.
continuously
Ex: Case where temperature is -5C or less for total of 10 min.
6.9
Heater Control
The heater control is conducted in the following manner.
[Normal control]
While in heating operation, the heater
ON
control (ON/OFF) is conducted as
shown on the right.
172
OFF
2C
[Overload control]
When the system is overloaded
in heating operation, the heater
will be turned OFF in the
following two manners.
(1) The heater control (ON/OFF)
is conducted through the
liquid pipe temperature (R2T)
of the indoor unit.
Set temperature
ON
43C
2C
OFF
Function
Si34-803
60C
Condensing pressure
equivalent saturated
temperature
OFF
FXFQ
FXAQ
OFF
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Swing
OFF
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Swing
LL
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
LL
Hot start from thermostat Swing
OFF mode (for prevention
of cold air)
Wind direction set LL
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
Horizontal
OFF
Horizontal
Horizontal
Totally closed
Horizontal
Horizontal
Totally closed
Swing
Flap
FXCQ
FXHQ
FXKQ
Defrosting operation
Swing
Stop
Thermostat ON in dry
operation using micro
computer
Thermostat OFF in dry
operation using micro
computer
Cooling Thermostat OFF in
cooling
Swing
L*1
Swing
Swing
Swing
L*1
Set
Set
Set
Swing
Swing
Swing
Swing
OFF or L
Wind direction set
Set
Swing
Swing
Swing
Set
Set
Set
Swing
OFF
Horizontal
Horizontal
Totally closed
Horizontal
Horizontal
Totally closed
Swing
Swing
Swing
Swing
Set
Set
Set
Swing
Set
Stop
Micro computer control
(including cooling
operation)
Function
173
Si34-803
To select cooling, heating, or fan operation mode according to the suction air (outdoor air)
temperature.
Details
Cooling mode
15
19
Cooling
Cooling
Fan operation
Fan stop
Heating mode
43
18
Heating
Heating
16
Automatic mode
Heating
Fan operation
(Fixed speed)
(Thermostat
OFF)
Heating
Cooling
Cooling
18
16
174
Function
Si34-803
T3
Refrigerant
Discharge
air
CPU
Ts
T1
T4
T2
Temp.
Setting
EV
Refrigerant
T1: Temperature detected by suction air thermistor Th1
T2: Temperature detected by liquid pipe temp. thermistor Th2
T3: Temperature detected by gas pipe temp. thermistor Th3
T4: Temperature detected by discharge air thermistor Th4
EV: Electronic expansion valve opening
SH=T3T2
Yes
No
T4 > Ts?
Is EV possible
to open?
Yes
No
Is
EV possible to
close?
Yes
If yes,
EV is opened.
EV=EV+EV
Function
If yes,
EV is closed.
No
EV=EVEV
175
Si34-803
Refrigerant
Discharge
air
Tc
CPU
Ts
T1
T4
T2
Temp.
Setting
EV
Refrigerant
T1: Temperature detected by suction air thermistor Th1
T2: Temperature detected by liquid pipe temp. thermistor Th2
T3: Temperature detected by gas pipe temp. thermistor Th3
T4: Temperature detected by discharge air thermistor Th4
Tc : Outdoor unit condensing temperature
EV: Electronic expansion valve opening
SC=TcT2
Yes
No
T4 < Ts?
Is EV possible
to open?
Yes
No
Is
EV possible to
close?
Yes
If yes,
EV is opened
EV=EV+EV
176
If yes,
EV is closed.
No
EV=EVEV
Function
Si34-803
In cooling (or fan operation) or heating, if outdoor air is low in temperature, stop the fan forcibly.
Details
Function
177
Si34-803
178
Function
Si34-803
Part 5
Test Operation
1. Test Operation ....................................................................................180
1.1 Installation Process ..............................................................................180
1.2 Procedure and Outline .........................................................................181
1.3 Operation When Power is Turned On ..................................................195
Test Operation
179
Test Operation
Si34-803
1. Test Operation
1.1
Installation Process
Below figure shows the installation process. Install in the order of the steps shown.
3. Selection of Location
7. Field Wiring
6. Refrigerant Piping
9. Pipe Insulation
180
Test Operation
Si34-803
1.2
Test Operation
Have the airtight test and the vacuum drying been conducted
according to the procedure in the Installation Manual?
Test Operation
181
Test Operation
Si34-803
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
(*) The master unit is the outdoor unit to which the transmission wiring for
the indoor units is conncted.
The other outdoor units are slave units.
Make field settings with outdoor
unit PC board.
182
Test Operation
Si34-803
Test Operation
1.2.3.1
Preparations
<Needed tools>
Gauge manifold
Charge hose valve
Vacuum pump
Nitrogen
Gouge manifold
Measuring device
Gas side
shutoff valve
Charge
hose
Outdoor
unit
Shutoff valve
service port
Outdoor
unit
Valve B
Valve C
To indoor unit
R-410A cylinder Vacuum pump
(with siphon)
Valve A
Interunit pipings
Gas flow
fig. 28
Valve
A
shutoff valve
C
Liquid side
Gas side
Close
Close
Note:
The airtightness test and vacuum drying should be done using the liquid
side and gas side shutoff valve service ports.
See the [R-410A] Label attached to the front plate of the outdoor unit for
details on the location of the service port (see figure at right).
See [Shutoff valve operation procedure] for details on handling the
shutoff valve. (Refer to page 185)
The refrigerant charge port is connected to unit pipe.
When shipped, the unit contains refrigerant, so use caution when
attaching the charge hose.
Test Operation
[Caution] Label
183
Test Operation
1.2.3.2
Si34-803
Before Working
[About the refrigerant cylinder]
Check whether the cylinder has a siphon pipe before charging and place the cylinder so that the
refrigerant is charged in liquid form. (See the figure below.)
With siphon pipe
Stand the cylinder upright and charge.
(The siphon pipe goes all the way inside,
so the cylinder does not need be put
upside-down charge in liquid form.)
Other tanks
Stand the cylinder upside-down and charge.
Caution
184
Always use the proper refrigerant (R-410A). If charged with the refrigerant containing an
improper material, it may cause an explosion or accident.
R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition
to change, which may prevent normal operation.
Test Operation
Si34-803
Test Operation
8HP type
10HP type 12HP type 14HP type 16HP type 18HP type
12.7
9.5
Liquid side The 12HP type corresponds
The
18HP
type
corresponds to the
to the 12.7-diameter 15.9-diameter onsite
shutoff valve onsite piping using the included
piping using the
piping.
accessory pipe.
Gas side
shutoff valve
15.9
19.1
25.4
The 10HP type corresponds to the
22.2-diameter onsite piping using the accessory pipe.
The 12 ~ 18HP type corresponds to the 28.6-diameter onsite
piping using the accessory pipe.
<Tightening torque>
Tightening torque Nm (Turn clockwise to close)
Shutoff valve size
Cap
(valve lid)
9.5
5.4 - 6.6
12.7
8.1 - 9.9
15.9
13.5 - 16.5
Hexagonal wrench
6 mm
27.0 - 33.0
Hexagonal wrench
8 mm
19.1
25.4
Hexagonal wrench
4 mm
Service port
13.5 - 16.5
18.0 - 22.0
11.5 - 13.9
22.5 - 27.5
Service port
Cap
Seal section
Hex holes
Shaft (valve body)
fig 34
[To open]
1. Remove the cap and turn the shaft counterclockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
[To close]
1. Remove the cap and turn the shaft clockwise with the hexagon wrench (JISB4648).
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
Test Operation
185
Test Operation
Si34-803
1. Press the MODE button (BS1) once, and set the MONITOR MODE
(H1P: Blinking).
2.
H H H H H H H
1 2 3 4 5 6 7
P P P P P P P
5333333
5334333
5333434
3. Press the RETURN button (BS3) and read the number of units from the
5353553
32 0 + 16 1 + 8 0 + 4 1 + 2 1 + 1 0 = 22 units
Note: 000000 indicates 64 units.
4. Press the MODE button (BS1) once. This returns to Setting Mode 1
(default).
3343333
Note:
Press the MODE button (BS1) if you get confused while operating.
This returns to Setting Mode 1 (default).
186
Test Operation
Si34-803
1.2.4.2
Test Operation
Caution
Make sure to use the protect tool (protective groves and goggles) when charging the
refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be charged over the allowable
maximum amount when charging the refrigerant.
Do not perform the refrigerant charging operation under working for the indoor unit.
When opening the front panel, make sure to take caution to the fan rotation during the
working.
After the outdoor unit stops operating, the fan may keep rotation for a while.
Note:
If operation is performed within 12 minutes after the indoor and outdoor units are turned on,
H2P will be lit on and the compressor will not operate.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starting operating. This is not a malfunction.
<About refrigerant charging>
The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the units internal piping is already charged with
refrigerant, so be careful when connecting the charge hose.
After adding the refrigerant, make sure to close the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 Nm.
See [Shutoff valve operation procedure] in 1.2.4.1 for details on how to handle shutoff
valves.
When done or when pausing the refrigerant charging operation, close the valve of the
refrigerant tank immediately. If the tank is left with the valve open, the amount of refrigerant
which is properly charged may be off the point. More refrigerant may be charged by any
remaining pressure after the machine is stopped.
<About check operation>
Make sure to perform the check operation after installation. Otherwise, the malfunction code
U3 will be displayed and normal operation cannot be performed.
And the failure of Check of miswiring may also cause abnormal operation. Performance
may drop due to the failure of Judgment of piping length.
Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.
The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is completed. (See page
194)
The check operation cannot be performed in recovery or other service modes.
1. Make sure the following works are complete in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Installation work for indoor unit
2. Calculate the additional charging amount using How to calculate the additional refrigerant
to be charged in 6 Example of connection on Part7. Appendix in page 425.
Test Operation
187
Test Operation
Si34-803
3. Open the valve C (See the figure 31. The valve A, B and the liquid and gas side shutout
valve must be left closed), and charge the refrigerant of the additional charging amount
from the liquid side shutout valve service port.
If the additional charging amount was charged fully, close the valve C and go to step 5.
If the additional charging amount was not charged fully, go to step 4.
Liquid side
shutoff valve
Gus side
shutoff valve
shutoff valve
service port
Valve B
Charge hose
Measuring device
Outdoor unit
Outdoor unit
Refrigerant
charg port
Valve C
To indoor unit
Field pipings
Refrigerant flow
Valve A
R-410A cylinder
(with siphon)
fig 31
Inspection door
Pipe intake
fig 32
Charge hose
Measuring
device
R-410A cylinder
(with siphon)
Refrigerant
charge port
Liquid side
shutoff valve
Gas side
shutoff valve
Shutoff valve
service port
Outdoor
unit
Outdoor
unit
valve B
valve C
valve A
valve A
To indoor unit
: Field piping
: Refrigerant flow
fig 33
188
Test Operation
Si34-803
Test Operation
IND
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
Master unit
Sub unit 1
Sub unit 2
Single system
Multi
system
(*)
C/H SELECTOR
(2) If necessary, set the field setting by using the dip switch on the outdoor unit PC board(A1P).
(For how to set, see 1.2.5.1 Onsite Settings With the Power Off)
(3) Close the EL. COMPO. BOX lid and all front panel except on the side of the EL. COMPO.
BOX (*1) and turn the power to the outdoor unit and all connected indoor units. (*2)
After H2P stop blinking (about 12 minutes after turning on the power), check LED displays
as shown in the table [Display of normal system] and the system is normal state.
If H2P is blinking, check the malfunction code in the remote controller, and correct the
malfunction in accordance with [Remote controller display malfunction code] in page 191.
(*1) Lead the refrigerant charge hose etc from the pipe intake. All front panels must be closed at
the procedure (9).
(*2) If you perform the refrigerant charging operation within the refrigerant system that have the
power off unit, the operation cannot finish properly.
For confirming the number of the outdoor and indoor units with the power on, see [How to
check how many units are connected] in chapter 1.2.4.1. In case of a multi system, turn on
the power to all outdoor units in the refrigerant system.
To energize the crankcase heater, make sure to turn on for 6 hours before starting
operation.
(4) Start the additional refrigerant charge operation.
(About the system settings for additional refrigerant charge operation, refer to the [Service
Precaution] label attached on the EL. COMPO. BOX lid in the outdoor unit.)
Open valve A immediately after starting the compressor.
(5) Close the valve A if the additional charging amount of refrigerant was charged, and push
the RETURN button (BS3) once.
(6) Record the charging amount on the accessory REQUEST FOR THE INDICATION label
and attach it to the back side of the front panel.
5. After completing the additional refrigerant charging perform the check operation following
below
Test Operation
189
Test Operation
Si34-803
NOTE:
For check operation, the following work will be performed.
Check of shutoff valve opening
Check of miswiring
Judgment of piping length
Check of refrigerant overcharge
It takes about 40 minutes to complete the check operation.
IND
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
Master unit
Sub unit 1
Sub unit 2
Single system
Multi
system
(*)
C/H SELECTOR
(*)How to distinguish the master unit, sub unit 1, and sub unit 2 in the multi system.
Method 1: By the H8P (MULTI) LED display
(4) Make the onsite settings as needed using the push button (BS1-BS5) on the outdoor unit
PC board (A1P) with the power on. (See 1.2.5.2 Onsite Settings With the Power On)
(5) Perform the check operation following the Check Operation Method of the [Service
Precautions] label on the EL. COMPO. BOX lid. The system operation for about 40 minutes
and automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after the system stop, check
operation is completed. Normal operation will be possible after 5 minutes. If the malfunction
code is displayed in the remote controller, correct the malfunction following [Remote
controller displays malfunction code] and perform the check operation again.
190
Test Operation
Si34-803
Test Operation
Refrigerant overcharge.
E4
F3
Insufficient refrigerant.
U7, U4
UF, UH
Remedial action
Open the shutoff valve.
Exchange two of the three phases (L1, L2, L3) to
make a proper connection.
Make sure the power source wire is properly
connected to the outdoor unit and revise if
necessary.
Check if the refrigerant piping line and the
transmission wiring are consistent with each other.
Recalculate the additional amount refrigerant from
the piping length and correct the refrigerant charge
level by recovering any excessive refrigerant with
a refrigerant recovery machine.
Check if the additional refrigerant charge has
been finished correctly.
Recalculate the additional amount refrigerant
from the piping length and add the adequate
amount.
Remove the line from the outdoor multi terminals
(Q1 and Q2).
If any malfunction codes other than the above are displayed, check the service manual for how
to respond.
Test Operation
191
Test Operation
Si34-803
1.2.5.1
Warning
Inspection
door
EL.COMPO.
BOX lid
[Service Precautions]
label
1.2.5.2
Warning
192
Test Operation
Si34-803
Test Operation
1.2.6.2
Test Run
After check operation is completed, operate the unit normally and check the following.
(1) Make sure the indoor and outdoor units are operating normally.
(2) Operate each indoor unit one by one and make sure the corresponding outdoor unit is also
operating.
(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller to see if they operate
properly.
NOTE:
Heating is not possible if the outdoor temperature is 24C or higher. Refer to the Operation
manual.
If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button of
the remote controller is pushed.
When the system operation is stopped by the remote controller, the outdoor units may
continue operating for further 5 minutes at maximum.
The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not a malfunction.
Test Operation
193
Test Operation
1.2.6.3
Si34-803
194
Test Operation
Si34-803
1.3
Test Operation
Indoor unit
Indoor unit
1.3.3 When an Indoor Unit or Outdoor unit Has Been Added, or Indoor or
Outdoor Unit PC Board Has Been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit
Indoor unit
Service cover
[Service Precautions] label
Switch box cover
Switch box
(the upper right)
Caution When the 400 volt power supply is applyed to "N" phase by mistake,
replace Inverter PC board (A2P) and control transformer (T1R, T2R) in
switch box together.
Test Operation
195
Si34-803
HAP
(3) Mode setting switch
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
RESET
1 2 3 4 1 2 3 4
DS1
DS2
F1 F2 F1 F2 Q1 Q2
Indoor
Outdoor
Outdoor
Outdoor
Multi outdoor
196
Test Operation
Si34-803
Field Setting
3. Field Setting
3.1
MODE NO.
SECOND
CODE NO.
FIRST
CODE NO.
FIELD
SET
MODE
UNIT NO.
SETTING
.
1 7
TEST
Test Operation
197
Field Setting
Si34-803
198
Test Operation
Si34-803
Field Setting
Test Operation
199
Field Setting
Si34-803
0
10
(20)
11
(21)
VRV
system
indoor
unit
settings
12
(22)
13
(23)
15
(25)
Filter contamination
heavy/light (Setting for
display time to clean air
filter)
(Sets display time to clean
air filter to half when there
is heavy filter
contamination.)
01
Super
long life
filter
Long life
filter
02
Approx.
10,000
hrs.
Approx.
2,500
hrs.
Light
Standard
filter
03
04
Details
No.
(1)
Approx.
5,000
hrs.
Approx.
1,250
hrs.
Heavy
Approx.
200 hrs.
Approx.
100 hrs.
(2)
Use
No use
(3)
Display
No display
(4)
OFF
Completion of
airflow
adjustment
Start of airflow
adjustment
(5)
Operation
output
Malfunction
output
(6)
Forced OFF
ON/OFF control
External protection
device input
(7)
1C
0.5C
(8)
LL
(9)
01:0
Not equipped
Equipped
(11)
LL air flow
(12)
(13)
F (4 directions)
T (3 directions)
W (2 directions)
(14)
Equipped
Not equipped
(15)
Draft prevention
Standard
Ceiling Soiling
prevention
(16)
Standard
High static
pressure
(17)
Not equipped
Equipped
(19)
Not equipped
Equipped
(20)
Not equipped
Equipped
(21)
Not equipped
Equipped
(22)
Airflow adjustment
Notes :
200
01:30
02:1
02:50
03:2
03:60
04:3
04:70
05:4
06:5
05:80
06:90
07:6
08:7
07:100 08:110
*7
(10)
(18)
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked
are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. 88 may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to Equipped, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
7. The FXMQ506380100125PVE cannot be set to 30Pa.
The FXMQ40PVE cannot be set to 180 or 200Pa.
Test Operation
Si34-803
Field Setting
Slim
Ceiling
mounted
Round Double Corner duct
flow
flow
type
type
Ceiling
mounted
built-in
type
Ceiling
Mounted
duct type
(Middle
and high
static
pressure)
FXMQ- FXMQFXHQ
P
MA
Concealed
Floor
standing
type
New
Ceiling
suspended
cassette
type
Outdoor Details
air
No.
processing
unit
FXAQ
FXLQ
FXNQ
FXUQ
FXMQMF
(1)
(2)
(3)
(9) (12)
(5)
(13)
(14)
(15)
(16)
{1
{1
(17)
(18)
3.1.72
3.1.72
FXFQ
FXCQ
FXKQ
FXDQ
FXSQ
Filter sign
Remote controller
thermostat sensor
Test Operation
201
Field Setting
Si34-803
Standard
Long Life
200 hrs.
100 hrs.
2,500 hrs.
1,250 hrs.
10,000 hrs.
5,000 hrs.
10 (20)
Setting
Long-Life Filter
Ultra-Long-Life Filter (1)
10 (20)
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and remote controller thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the remote
controller thermistor.
202
Mode No.
10 (20)
Test Operation
Si34-803
Field Setting
11 (21)
12 (22)
03
04
Remarks
Indoor unit thermostat ON/OFF signal is
provided.
Output linked with "Start/Stop" of remote
controller is provided.
In case of "Malfunction Display" appears
on the remote controller, output is
provided.
Setting Table
Mode No.
Setting
Switch No.
Setting
Position No.
01
12 (22)
02
03
Test Operation
203
Field Setting
Si34-803
12(22)
Differential value
1C
0.5C
12 (22)
Contents
LL air flow
Preset air flow
12 (22)
01
0C
02
1C
07
6C
08
7C
The automatic operation mode setting is made by the use of the "Operation Mode Selector"
button.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
204
Mode No.
12 (22)
Contents
LL air flow
Preset air flow
Test Operation
Si34-803
Field Setting
Setting Switch
No.
13(23)
Setting Position
Setting
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
13(23)
Second code
No.
01
02
First Second
code
code
No.
No.
01
13 (23)
02
03
Setting
Standard All
round outlet
High Ceiling (1)
Higher Ceiling (2)
2.7
2.7-3
3-3.5
First Second
code
code
No.
No.
01
13 (23)
02
03
Setting
Standard All
round outlet
High Ceiling (1)
Higher Ceiling (2)
3.2
3.2-3.6
3.6-4.2
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 3.1 m Lower than 3.0 m Lower than 3.5 m
0
02
High Ceiling (H) Lower than 3.4 m Lower than 3.3 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 4.0 m Lower than 3.5 m
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 3.4 m Lower than 3.6 m Lower than 4.2 m
0
02
High Ceiling (H) Lower than 3.9 m Lower than 4.0 m Lower than 4.2 m
03
Higher Ceiling (S) Lower than 4.5 m Lower than 4.2 m
*1 Mode No. setting is done in a batch for the group. To make or confirm settings for an
individual unit, set the internal mode number in parentheses.
*2 The figure of the ceiling height is for the all round outlet. For the settings for four-direction
(part of corner closed off), three-direction and two-direction outlets, see the installation
manual and technical guide supplied with the separately sold closure material kit.
Test Operation
205
Field Setting
Si34-803
13 (23)
First Second
Ceiling height
code
code
Setting
4-way Outlets
3-way Outlets
2-way Outlets
No.
No.
01
Standard (N)
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
0
02
High Ceiling (H) Lower than 3.0 m Lower than 3.5 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.8 m
13 (23)
Second Code
No.
01
02
03
Setting
F : 4-direction air flow
T : 3-direction air flow
W : 2-direction air flow
13 (23)
Setting
Down-flow operation: Yes
Down-flow operation: No
Setting Table
Mode No.
13 (23)
02
03
Setting
Upward (Draft
prevention)
Standard
Downward (Ceiling
soiling prevention)
Some indoor unit models are not equipped with draft prevention (upward) function.
206
Model No.
13 (23)
Test Operation
Si34-803
Field Setting
13 (23)
06
The SECOND CODE NO. is set to 07 (an external static pressure of 100 Pa) at factory set.
*1 The FXMQ50 63 80 100 125PVE cannot be set to 30 Pa.
*2 The FXMQ40PVE cannot be set to 180 or 200 Pa.
15 (25)
Setting
Setting of humidifier
15 (25)
2
02
Contents
Without direct duct
connection
With direct duct
connection equipped
with fan
15 (25)
3
02
Test Operation
Contents
Individual operation of
humidifier
Interlocked operation
between humidifier and
drain pump
207
Field Setting
Si34-803
208
Mode No.
15 (25)
Contents
Individual operation of
ventilation
Test Operation
Si34-803
Field Setting
1
12
(22)
5
3
14
(24)
4
Setting
contents
Stain of filter
Filtering
time
cumulation
External
ON/OFF
input
Power
failure
automatic
reset
Discharge
temperature
(cooling)
Discharge
temperature
(heating)
02
03
04
05
2500hr
1250hr
10
11
12
13
14
15
Display
No
display
Forced
stop
ON-OFF
control
Not
Equipped
equipped
13C
14
15
16
17
18
19
20
21
22
23
24
25
25
25
18C
19
20
21
22
23
24
25
26
27
28
29
30
30
30
Test Operation
01
209
Field Setting
Si34-803
In order to conduct the central remote control using the central remote controller and the unified
ON/OFF controller, Group No. settings should be made by group using the operating remote
controller.
Make Group No. settings for central remote control using the operating remote controller.
1. Turn ON the power of the indoor unit and unified ON/OFF controller. (Unless the power is
ON, no setting can be made.)
Check that the installation and electrical wiring are correct before turning the power supply
ON.
When the power supply is turned ON, all LCD appear once and the unit may not accept the
operation for about one minute with the display of
flashing (an interval of ON,
ON, and OFF).
2. While in normal mode, press and hold the
switch for a period of four seconds or
more to set the system to "Field Setting Mode".
3. Select the MODE No. 00 with the
button.
4. Use the
button to select the group No. for each group.
(Group numbers increase in the order of 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
5. Press
to set the selected group No.
6. Press
to return to the NORMAL MODE.
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
MODE
SETTING
TEST
2,6
Note:
For wireless remote controller, see the following.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
210
Test Operation
Si34-803
Field Setting
button (advance/backward).
BRC7C Type
BRC7E Type
BRC4C Type
Indoor/Outdoor Outdoor/Outdoor
Centoral Remote
Controller
Indoor/Outdoor Outdoor/Outdoor
F1 F2
F1 F2
F1 F2
F1 F2 P1 P2
RC
1-00
F1 F2 P1 P2
No Remote Controller
1-03
Caution
Test Operation
F1 F2
F1 F2 P1 P2
Main RC
RC Sub
1-01
F1 F2 P1 P2
F1 F2
F1 F2 P1 P2
RC
1-02
F1 F2 P1 P2
F1 F2 P1 P2
F1 F2 P1 P2
RC
1-04
When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
211
Field Setting
Si34-803
212
Test Operation
Si34-803
How to Select
Operation Mode
Example
ON by remote
controller
(Unified ON by
central remote
controller)
Rejection
Field Setting
Whether operation by remote controller will be possible or not for turning on/off, controlling
temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
OFF by remote
controller
(Unified OFF by
central remote
controller)
OFF by
remote
controller
Rejection
Rejection
Temperature
control by
remote controller
Operation mode
setting by
remote controller
Acceptance
Acceptance
Control
mode is "1."
Unified operation,
individual operation
by central remote
controller, or
operation controlled
by timer
Unified OFF,
individual stop by
central remote
controller, or timer
stop
OFF
Temperature
Operation Control mode
control
mode setting
Rejection
ON/OFF control
impossible by
remote controller
Rejection
(Example)
Acceptance
(Example)
Rejection (Example)
Rejection
Rejection (Example)
Acceptance
Rejection
Centralized
Acceptance
Acceptance
Acceptance
Rejection
Individual
Acceptance
Acceptance
Timer operation
possible by
remote controller
Acceptance
(During timer at ON
position only)
Acceptance
(During timer at ON
position only)
Rejection
Acceptance
Acceptance
Rejection
10
Acceptance
(Example)
1(Example)
Rejection
11
Acceptance
Rejection
12
Acceptance
Rejection
13
Acceptance
Rejection
14
Acceptance
Rejection
15
Acceptance
Rejection
16
Acceptance
Rejection
7 1
17
Acceptance
Rejection
18
Acceptance
Rejection
19
Do not select timer operation possible by remote controller if not using a remote controller.
Operation by timer is impossible in this case.
1. Factory setting
Test Operation
213
Field Setting
3.2
Si34-803
Function setting
4
5
214
Setting of AirNet
address
Test Operation
Si34-803
Field Setting
Setting item
Content and objective of setting
Overview of setting procedure
Indoor unit fan
to operate the indoor unit in the
Set No. 5 of "Setting mode 2" to indoor unit
1 forced H operation Used
stopped state in forced H operation mode.
forced fan H.
2
Service setting
10
11
12
13
Setting of
sequential startup
For setting items of (*1), refer to detailed information provided on page 226 onward.
Test Operation
215
Field Setting
Si34-803
Setting item
Description
Setting
ON
to set cool / heat select by Cool/Heat selector
Cool / Heat select Used
equipped with outdoor unit.
OFF (Factory set)
DS1-2
~DS1-4
ON
OFF (Factory set)
Not used
DS2-1
~4
ON
OFF (Factory set)
Not used
Caution
DIP switch Setting after changing the main PC board(A1P) to spare parts PC board
After the replacement by the spare PC board, be sure to make settings shown below.
When you change the main PC board(A1P) to spare parts PC board, please carry out the
following setting.
ON
OFF
ON
OFF
1 2 3 4
DS1
1 2 3 4
DS2
Contents
COOL/HEAT
setting is made with the use of a
ON
Cool/Heat selector mounted to the outdoor unit.
OFF (Factory COOL/HEAT setting is not made with the use of a
setting of spare Cool/Heat selector mounted to the outdoor unit.
PC board)
ON
200V class (220V)
DS1-4
DS2-1
Domestic
Japan
Overseas
General
OFF
OFF
ON
OFF
ON
OFF
Europe
If the DS1-1~1-4, DS2-2~2-4 setting has not been carried out, error code UA are displayed
and unit can not be operated.
216
Test Operation
Si34-803
Field Setting
Test Operation
Setting method (
HEAT PUMP(5HP)
RXYQ5PAY1
RXYQ5PAYL, PTL
HEAT PUMP(8HP)
RXYQ8PAY1
RXYQ8PAYL, PTL
HEAT PUMP(10HP)
RXYQ10PAY1
RXYQ10PAYL, PTL
HEAT PUMP(12HP)
RXYQ12PAY1
RXYQ12PAYL, PTL
HEAT PUMP(14HP)
RXYQ14PAY1
RXYQ14PAYL, PTL
HEAT PUMP(16HP)
RXYQ16PAY1
RXYQ16PAYL, PTL
HEAT PUMP(18HP)
RXYQ18PAY1
RXYQ18PAYL, PTL
217
Field Setting
Si34-803
Single-outdoor-unit
system
Outdoormulti
system
Master
Slave 1
Slave 2
MODE
H1P
TEST
H2P
7
7
7
7
7
7
7
7
COOL/HEAT select
Multi;
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
IND
H3P
H7P
H8P
8
8
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
(Factory setting)
BS1
BS2
BS3
BS4
BS5
MODE
SET
RETURN
TEST
RESET
(V2760)
Setting mode 2
(Normal)
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 1
MODE
MODE
Off
On
H1P
Blinking
H1P
H1P
(V2761)
Setting mode 1
(Initial condition)
Setting mode 2
Monitor mode
Press BS3
(RETURN button).
Setting condition
selection (SET button)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS1
(MODE button).
Press BS1
(MODE button).
(V2762)
218
Test Operation
Si34-803
Field Setting
a. Setting mode 1
This mode is used to set and check the following items.
1. Set items In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
COOL/HEAT selection (IND) Used to select COOL or HEAT by individual outdoor
unit (factory set).
COOL/HEAT selection (MASTER) Used to select COOL or HEAT by outdoor unit group
with the master unit.
COOL/HEAT selection (SLAVE)Used to select COOL or HEAT by outdoor unit group
with the slave unit.
2. Check items The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Normally, Setting mode 1 is set. In
case of other status, push MODE
(BS1) button one time and set to
Setting mode 1.
8 ON
7 OFF
9 Blink
Push the SET (BS2) button to set
the blinking of LED to any of
conditions shown on the right.
MODE TEST
H2P
H1P
7
7
7
7
7
7
COOL/HEAT select
Low
Demand
IND MASTER SLAVE noise
H7P
H6P
H4P
H5P
H3P
9
7
7
7
9
7
7
7
9
7
7
7
7
7
7
Pushing the RETURN (BS3) button will return the system to the initial condition of
"Setting mode 1".
COOL/HEAT select
MODE TEST
H1P
H2P
Low
Demand
IND MASTER SLAVE noise
H7P
H6P
H3P
H4P
H5P
7
Current operating conditions
7Normal 8Abnormal
9In preparation or in
check operation
Test Operation
219
Field Setting
b. Setting mode 2
Push and hold the MODE (BS1)
button for 5 seconds and set to
Setting mode 2.
Si34-803
No.
Digital pressure
gauge kit display
Cool/heat unified
address
Low noise/demand
address
Test operation
settings
6
8
9
10
12
13
16
18
19
20
Push the RETURN (BS3) button and
set to the initial status of Setting
mode 2.
21
22
If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
24
Sets low noise level when the low noise signal is input
from outside.
29
Capacity
precedence setting
30
Demand setting 1
32
Normal demand
setting
25
26
27
28
220
Description
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)
11
Setting item
Test Operation
Si34-803
Field Setting
No.
35
38
39
40
42
Test Operation
Setting item
Setting of difference
in elevation for the
outdoor unit
Emergency
operation
(Setting for the
master unit
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 1
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(Setting for the
slave unit 2
operation
prohibition in multioutdoor-unit
system)
Emergency
operation
(prohibition of INV
compressor
operation)
Description
Make the setting when the outdoor unit is installed 40 m
or more below the indoor unit.
221
Field Setting
Si34-803
Setting item
Digital pressure
gauge kit display
MODE
H1P
TEST
H2P
IND
H3P
C/H selection
Master Slave
H4P
H5P
Low
noise
H6P
Demand
H7P
Address
Binary number
(4 digits)
~
15
Cool / Heat
Unified address
Address
Binary number
(6 digits)
Low noise/demand
address
Address
Binary number
(6 digits)
Test operation
8788888
8777778
8777787
8777778
8777787
8777778
8777787
8777778
8777787
8777788
8777877
8777878
8777887
8777888
8777778
8777787
8777877
8777778
8777787
8777877
8777778
8777787
8777778
8777787
Te setting
High
High
(Level H)
High
High
Low
9
Tc setting
changeover
10 Defrost
setting
Sequential operation
11 setting
low noise/
12 External
demand setting
13 Airnet address
OFF
ON
Address
Binary number
(6 digits)
static pressure
18 High
setting
Emergency
operation
19 (STD compressor is
inhibited to operate.)
Additional refrigerant
20 charging operation
setting
Refrigerant
21 recovery/vacuuming
mode setting
222
8777777
8777778
~
63
of hot water
16 Setting
heater
8788888
8777777
8777778
~
31
3
8778888
8777777
8777778
~
31
Factory set
8777777
8777778
8888888
8777778
8777787
8777778
8777787
OFF
ON
OFF
STD 1, 2 operation: Inhibited
STD 2 operation: Inhibited
Refrigerant charging: OFF
Refrigerant charging: ON
Refrigerant recovery / vacuuming: OFF
Refrigerant recovery / vacuuming: ON
8777777
8777778
8777787
8777778
8777787
8777778
8777787
Test Operation
Si34-803
Field Setting
Setting item
MODE
H1P
TEST
H2P
IND
H3P
C/H selection
Master
Slave
H4P
H5P
Low
noise
H6P
Demand
H7P
OFF
ENECUT test
24 operation (Domestic
Japan only)
About 7:00
About 8:00 (factory setting)
28 Power transistor
check mode
Capacity
29 precedence setting
OFF
ON
OFF
ON
60 % demand
30 Demand setting 1
70 % demand
80 % demand
Normal demand
32 setting
OFF
ON
Normal
Setting of difference
35 in elevation for the
outdoor unit
65 m or less
90 m or less
Emergency
operation
(Master unit with
38 multi-outdoor-unit
system is inhibited to
operate.)
Emergency
operation
(Slave unit 1 with
39 multi-outdoor-unit
system is inhibited to
operate.)
Emergency
operation
(Slave unit 2 with
40 multi-outdoor-unit
system is inhibited to
operate.)
Emergency
operation
42 (prohibition of INV
compressor
operation)
Test Operation
OFF
Factory set
8777777
8777778
8777787
8777788
8777778
8777787
8777778
8777787
8777877
8777778
8777787
8777877
8777778
8777787
8777877
8777778
8777787
8777778
8777787
8777778
8777787
8777877
8777778
8777787
8777777
8777887
8777888
8777778
7
Master unit operation: Inhibited
8777787
OFF
8777778
8777787
OFF
8777778
8777787
Normal operation
8777778
Emergency operation
(prohibition of INV compressor
operation)
8777787
223
Field Setting
c. Monitor mode
To enter the monitor mode, push the
MODE (BS1) button when in
Setting mode 1.
Si34-803
No.
Setting item
H3P
H4P
H5P
H6P
H7P
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
7
7
8
8
7
7
8
7
8
7
Not used
Airnet address
9
9
9
9
9
9 7 7 7 8 7 8
9 7 7 7 8 8 7
9 7 7 7 8 8 8
Number of BS units *4
9 7 7 8 7 7 7
9 7 7 8 7 7 8
10
Number of BS units *4
11
Data display
Lower 4 digits
Lower 6 digits
Lower 4 digits:
upper
Lower 4 digits:
lower
9 7 7 8 7 8 7
9 7 7 8 7 8 8
12
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
9 7 7 8 8 7 8
Lower 4 digits:
lower
14
9 7 7 8 8 8 7
Malfunction
code table
Contents of malfunction
9 7 7 8 8 8 8
Refer page
256.
(1 cycle before)
Contents of malfunction
20
21
22
9
9
9
9
25
9 7 8 8 7 7 8
16
H2P
Various settings
15
H1P
LED display
(2 cycle before)
7
7
7
7
8
8
8
8
7
7
7
7
7
8
8
8
7
7
7
8
Lower 6 digits
7
7
8
7
Lower 6 digits
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
224
Test Operation
Si34-803
Field Setting
ON
OFF
Short
Medium
Long
Te setting
L
M
H ~
Tc setting
L
M
H
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
8
7
7
7
7
7
7
7
7
7
7
7
7
8
9
7
7
7
7
7
7
7
7
7
7
7
7
7
9
8
7
7
7
7
7
7
7
7
7
7
7
7
9
8
Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
9 797997
16
32
4
8
1
2
977 7979
64 16
No.12 128 32
977 7997
4
No.13
1
2
See the preceding page for a list of data, etc. for No. 0 - 25.
Test Operation
225
Field Setting
Si34-803
c Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to IN (factory set).
Set cool/heat switching to IND (individual) for Setting mode 1 (factory set).
Set the master unit (= indoor unit having the right to select the cooling/heating operation
mode).
226
Test Operation
Si34-803
Field Setting
d Set Cool / Heat Separately for Each Outdoor Unit System by Cool / Heat Selector
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to OUT (factory set).
Set cool/heat switching to IND (individual) for Setting mode 1 (factory set).
Test Operation
227
Field Setting
Si34-803
e Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Indoor Unit Remote Controller
Install the external control adapter for outdoor unit on either the outdoor-outdoor, indooroutdoor transmission line.
Set outdoor unit PC board DS1-1 to IN (factory set).
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as
the group master, and set the other outdoor units as group slave units.
Set the outdoor unit external control adapter SS1 to BOTH (factory set) or C/H, and SS2 to
OFF (factory set).
228
Test Operation
Si34-803
Field Setting
f Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Cool / Heat Selector
Install the external control adapter for outdoor unit on either the outdoor-outdoor, indooroutdoor transmission line.
Mount the COOL/HEAT selector to the master outdoor unit for the unified control.
Set the DS1-1 on the PC board of master outdoor unit to OUT.
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as
the group master, and set the other outdoor units as group slave units.
Set the outdoor unit external control adapter SS1 to BOTH (factory set) or C/H, and SS2 to
OFF (factory set).
229
Field Setting
Si34-803
Supplementation on e and f.
When switching cool/heat for each adapter PC board with the use of more than one adapter PC
board, set the address of the external control adaptor for outdoor unit PC board DS1 and DS2
so that it matches the unified cool/heat address of outdoor unit main PC board.
Address setting for e and f (Set lower 5 digits with binary number.) [No.0 to No.31]
Address
No.
No 0
87
DS2
DS1
77777
0
No 1
87
77778
1
No 2
87
77787
2
No 3
87
77788
3
No 4
87
No 31
77877
~
No 30
87
88887
87
88888
8ON
7OFF
30
30
31
31
230
Test Operation
Si34-803
Field Setting
Content
Set the outdoor unit fan to Step 6 or lower.
Set the outdoor unit fan to Step 5 or lower.
Set the outdoor unit fan to Step 4 or lower.
A. When the low noise operation is carried out by external instructions (with the use
of the external control adapter for outdoor unit)
1. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2",
or "Mode 3") for set item No. 25 (Setting of external low noise level).
3. If necessary, while in "Setting mode 2", set the setting condition for the set item No. 29
(Setting of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the low
noise operation command will be ignored to put the system into normal operation mode.)
B. When the low noise operation is carried out automatically at night (The external
control adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
Test Operation
231
Field Setting
Si34-803
232
Test Operation
Si34-803
Field Setting
Demand 2
Condition
Mode 1
Mode 2
Mode 3
Content
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
The compressor operates at approx. 40% or less of rating.
A. When the demand operation is carried out by external instructions (with the use of the
external control adapter for outdoor unit).
1. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
2. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the normal demand operation is carried out. (Use of the external control
adapter for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Test Operation
233
Field Setting
Si34-803
The power
consumption during
the demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power consumption"
has been set at
factory.)
(V3081)
(V3082)
Power consumption
234
Test Operation
Si34-803
Field Setting
Test Operation
235
Field Setting
Si34-803
{: ON
d
c
Setting
No.
Setting
contents
22
External
low noise /
Demand
setting
Night-time
low noise
setting
Setting
contents
YES
OFF
(Factory
setting)
{
{
{
{
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
9
9
z
9
z
9
9
{
{
z
z
z
z
z
z
9
z
z
z
z
9
{
{
{
z
z
z
z
z
z
z
z
z
9
z
z
z
z
9
z
9
z
AM 8:00
(Factory
setting)
Low noise
precedence
(Factory
setting)
Capacity
precedence
60 % of
rated power
consumption
70 % of
rated power
consumption
(Factory
setting)
80 % of
rated power
consumption
OFF
(Factory
setting)
ON
Mode 2
Mode 3
External
low noise
setting
Mode 1
Mode 2
(Factory
setting)
Mode 3
26
Night-time
low noise
start setting
PM 8:00
PM 10:00
(Factory
setting)
PM 0:00
27
29
30
32
Night-time
low noise
end setting
AM 6:00
AM 7:00
Capacity
precedence
setting
Demand
setting 1
Normal
demand
setting
236
NO
(Factory
setting)
Mode 1
25
9: Blink
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12
z: OFF
Test Operation
Si34-803
Field Setting
Test Operation
237
Field Setting
Si34-803
Unit stopping
3:OFF 9:BLINK)
3383333
Press the TEST button for 5 seconds.
Step 1
Pressure equalizing
3933338
10 sec to 10 minutes
Step 2
Step 3
3933383
20 sec to 2 minutes
3933388
10 minutes
Step4~8
Judgement function
3933833
3933838
3933883
3933888
3938333
Step 9
3938338
5 minutes
Step 10
3938383
5 minutes
Completion
238
Test Operation
Si34-803
Part 6
Troubleshooting
1. Symptom-based Troubleshooting .......................................................242
2. Troubleshooting by Remote Controller ...............................................245
2.1
2.2
2.3
2.4
Troubleshooting
239
Si34-803
Troubleshooting
Si34-803
Troubleshooting
241
Symptom-based Troubleshooting
Si34-803
1. Symptom-based Troubleshooting
1
Symptom
The system does not start operation at all.
Supposed Cause
Blowout of fuse(s)
Cutout of breaker(s)
Countermeasure
Turn Off the power supply and
then replace the fuse(s).
If the knob of any breaker is in
its OFF position, turn ON the
power supply.
If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
ON
Knob
Tripped
OFF
Circuit breaker
Power failure
2
242
Troubleshooting
Si34-803
Symptom-based Troubleshooting
Symptom
The system
This symptom occurs
conducts fan
immediately after turning ON
operation but not the power supply.
cooling or
heating
operation.
The airflow rate Even pressing the AIRFLOW
is not
RATE SET button makes no
reproduced
changes in the airflow rate.
according to the
setting.
The airflow
direction is not
reproduced
according to the
setting.
10 A white mist
comes out from
the system.
11 The system
produces
sounds.
<Outdoor unit>
Pitch of operating sounds
changes.
Troubleshooting
Supposed Cause
The system is in preparation
mode of operation.
Countermeasure
Wait for a period of approximately
10 minutes.
Normal operation.
Normal operation.
Normal operation.
This sound becomes low after a
lapse of approximately one
minute.
These sounds are produced from Normal operation.
gas (refrigerant) flowing
respectively through the indoor
and outdoor units.
These sounds are produced
Normal operation.
when the gas (refrigerant) stops
or changes flowing.
243
Symptom-based Troubleshooting
Symptom
12 Dust comes out Dust comes out from the
from the system. system when it restarts after
the stop for an extended period
of time.
13 Odors come out In operation
from the system.
14 Outdoor unit fan
does not rotate.
In operation
Supposed Cause
Countermeasure
Dust, which has deposited on the Normal operation.
inside of indoor unit, is blown out
from the system.
Odors of room, cigarettes or else
adsorbed to the inside of indoor
unit are blown out.
The reason is that fan revolutions
are controlled to put the operation
to the optimum state.
The reason is that the system is
checking to be sure the remote
controller is normal.
It stops in order to prevent oil or
refrigerant from dwelling.
244
Si34-803
Normal operation.
This code is displayed for a period
of approximately one minute at
maximum.
Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.
Normal operation.
Normal operation.
Troubleshooting
Si34-803
Local
setting
mode
Service
mode
Normal
mode
Press Inspection/Test Operation button once.
Or after 30 minutes
Test
operation
mode
Troubleshooting
(V0815)
245
2.2
Si34-803
Explanation
If operation stops due to malfunction, the remote controllers operation LED blinks, and
malfunction code is displayed. (Even if stop operation is carried out, malfunction contents are
displayed when the inspection mode is entered.) The malfunction code enables you to tell what
kind of malfunction caused operation to stop. See page 254 for malfunction code and
malfunction contents.
Operation LED
ON/OFF button
Inspection display
Malfunction code
Inspection/Test button
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or
more will clear the failure history indication shown above. In this case, on the codes display,
the malfunction code will blink twice and then change to 00 (=Normal), the Unit No. will
change to 0, and the operation mode will automatically switch from check mode to normal
mode (displaying the set temperature).
246
Troubleshooting
Si34-803
2.3
In the Case of
BRC7C Type
BRC7E Type
BRC4C Type
If equipment stops due to a malfunction, the operation indicating LED on the light reception
section flashes.
The malfunction code can be determined by following the procedure described below. (The
malfunction code is displayed when an operation error has occurred. In normal condition, the
malfunction code of the last problem is displayed.)
1. Press the INSPECTION/TEST button to select Inspection.
The equipment enters the inspection mode. The Unit indication lights and the Unit No.
display shows flashing 0 indication.
2. Set the Unit No.
Press the UP or DOWN button and change the Unit No. display until the buzzer (*1) is
generated from the indoor unit.
*1 Number of beeps
3 short beeps : Conduct all of the following operations.
1 short beep : Conduct steps 3 and 4.
Continue the operation in step 4 until a buzzer remains ON. The continuous buzzer indicates
that the malfunction code is confirmed.
Continuous beep : No abnormality.
3. Press the MODE selector button.
The left 0 (upper digit) indication of the malfunction code flashes.
4. Malfunction code upper digit diagnosis
Press the UP or DOWN button and change the malfunction code upper digit until the
malfunction code matching buzzer (*2) is generated.
The upper digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
*2 Number of beeps
Continuous beep : Both upper and lower digits matched. (Malfunction code confirmed)
2 short beeps : Upper digit matched.
1 short beep : Lower digit matched.
5. Press the MODE selector button.
The right 0 (lower digit) indication of the malfunction code flashes.
6. Malfunction code lower digit diagnosis
Press the UP or DOWN button and change the malfunction code lower digit until the
continuous malfunction code matching buzzer (*2) is generated.
Troubleshooting
247
Si34-803
The lower digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
248
Troubleshooting
Si34-803
Troubleshooting
249
2.4
Si34-803
Inspection/test
operation
0
Unit
L0
Malfunction code
Inspection
Inspection mode
Inspection/test
operation
Display
Example model
FXCQ25
028
FXFQ63
071
System classification
VRV system
VRV system
VRV system
VRV system
Display
071
FCJ
Indoor unit model code display
Display
AA1
Outdoor unit model code display
Inspection/test
operation
Test operation
Test operation mode
Wall mounted
FXAQ
Double flow
FXCQ
Corner
FXKQ
Multi flow
FXFQ
Ceiling suspended
FXHQ
Built-in
FXSQ
Floor standing
FXLQ
FXMQ
FXNQ
FXZQ
FXDQ
FXUQ
Inspection/test
operation
250
Model
Type
Type
Model
AA1
RSXYP
AA3
RXYP
A92
RSEYP
AA5
RSXYP-L
AAA
VRV II
RXYQ-M
AAC
VRV II M/C
RXYQ-MA
AAE
VRV III
RXYQ-P(A)
Troubleshooting
Si34-803
2.5
Service Mode
Operation
Method
Troubleshooting
251
Mode
No
40
Function
Malfunction
hysteresis display
Si34-803
Unit 1
Malfunction code
2-U4
40
Malfunction code
Hystory No: 1 - 9
1: Latest
(VE007)
41
Display of sensor
and address data
Sensor type
1 1
41
27
Address data
4: Indoor unit address
5: Outdoor unit address
6: BS unit address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
Temperature C
Address display
Unit No.
Address type
1 8
41
Address
(VE008)
43
Forced fan ON
Unit 1
43
(VE009)
44
Individual setting
Unit 1
Code
44
1 3
Fan speed 1: Low
3: High
(VE010)
45
1
Code
0 2
45
46
47
252
This function is not used by VRV lll R-410A Heat Pump 50Hz / 60Hz.
Troubleshooting
Si34-803
2.6
ON/OFF button
Inspection display
Malfunction code
(VL050)
Troubleshooting
253
Si34-803
8: ON
Indoor Unit
Outdoor Unit
254
7: OFF
Malfunction Operation
Malfunction contents
code
lamp
A0
9
Error of external protection device
A1
9
PC board defect, E2 PROM defect
A3
A6
9
9
A7
A8
A9
AF
AH
AJ
C1
C4
8
9
9
8
8
9
9
9
C5
C6
C9
9
9
CC
CJ
E1
E3
E4
E5
E6
E7
E9
F3
F6
H7
H9
8
9
9
9
9
9
9
9
9
9
9
9
J2
J3
9
9
J5
J6
J7
J9
JA
JC
L0
L4
L5
L8
9
9
9
9
9
9
9
9
9: Blink
Page
Referred
260
261
262
264,
265
268
270
271
273
274
275
277
278
279
280
281
282
283
284
286
288
290
291
294
296
297
298
299
300
301
302
303
304
305
306
307
308
310
312
Troubleshooting
Si34-803
8: ON
Malfunction Operation
code
lamp
Outdoor Unit
System
Central
Remote
Controller
and
Schedule
Timer
Heat
Reclaim
Ventilation
7: OFF
Malfunction contents
9: Blink
Page
Referred
L9
314
LA
LC
P1
P4
PJ
9
9
9
9
9
316
319
320
322
U0
U1
U2
U3
U4
U5
U5
9
9
9
9
9
7
U7
U8
9
9
U9
UA
UC
UE
UF
UH
M1
M8
8
9
9
9
8 or 7
8 or 7
MA
MC
64
65
6A
6A
6F
6H
94
8 or 7
8 or 7
8
8
8
9
8
8
9
323
324
325
328
329
331
331
332
334
335
336
338
339
342
343
345
346
348
350
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting
255
Si34-803
PC board malfunction
Malfunction
code
PC board malfunction
E1
Faulty PC board
HPS activated
E3
Abnormal Pe
E4
Compressor lock
E5
Activation of OC
E6
E7
EV1
EV3
H7
H9
F3
F6
J2
E9
EV2
Detail
description
on next
page.
J3
J5
J6
JA
JC
(L2)
Inverter radiation fin temperature rising Over heating of inverter radiation fin temperature
L4
L5
IGBT malfunction
L5
L8
Electronic thermal
L9
256
LC
Troubleshooting
Si34-803
8: ON
7: OFF
9:Blink
Confirmation of malfunction 1
Confirmation of malfunction 2
Confirmation of malfunction 3
Confirmation of malfunction 4
Malfunction
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
E1
E6
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
9
9
9
7
7
9
7
7
9
9
9
9
7
9
7
E7
E9
9
9
9
7
7
7
7
9
7
9
9
9
9
7
7
J3
J5
E3
E4
E5
H7
H9
F3
F6
J2
J6
J7
J9
JA
JC
9
9
7
7
9
9
7
7
7
9
(L2)
L4
L5
L5
L8
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
7
7
7
7
9
7
9
7
7
7
7
7
7
7
9
9
9
7
9
7
9
7
9
7
9
7
9
7
9
7
9
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
9
7
7
7
7
7
7
7
7
7
7
9
7
7
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
7
7
7
7
9
7
9
7
9
7
9
7
7
7
7
7
7
7
7
9
7
9
7
7
9
7
7
7
9
9
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
7
7
7
7
7
7
7
9
7
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
7
7
7
7
9
9
9
9
9
9
9
7
7
7
9
7
7
7
7
9
7
9
9
9
9
9
L9
LC
Display of contents of
malfunction (first digit)
Display of contents of
malfunction (second digit)
Display 1 of
malfunction in detail
Display 2 of
malfunction in detail
1
Troubleshooting
7
7
9
9
7
9
7
9
Master
Slave1
Slave2
System
257
Si34-803
<Monitor mode>
Contents of malfunction
P1
P3
P4
PJ
Malfunction
code
Gas shortage
U0
Reverse phase
U1
U2
U4
U7
U7
U3
No implementation of test-run
Detail
description
on next
page.
U9
UA
Refrigerant abnormal
Multi-ID abnormal
Alarm of TSS field setting
UA
UJ
UJ
UF
UH
258
Troubleshooting
Si34-803
8: ON
7: OFF
9:Blink
Confirmation of malfunction 1
Confirmation of malfunction 2
Confirmation of malfunction 3
Confirmation of malfunction 4
Malfunction
code
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
P1
9
9 7 7 7 9
7 7 7 9 9
7 7 7 7 9
7 7
P3
P4
PJ
7
7
7
7
7
7
7
7
9
7
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
9
9
7
7
9
7
7
7
7
7
9
7
7
7
7
9
U2
9
9
9
9
9
9
9
9
9
9
U3
U4
U7
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
9
9
9
7
7
7
7
7
7
9
7
9
7
9
9
7
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
7
9
9
9
9
9
7
7
9
9
7
7
9
7
9
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
9
9
9
9
7
7
7
7
9
9
9
9
9
9
9
9
9
9
9
7
7
9
7
7
9
9
7
7
7
7
7
9
7
7
9
7
9
7
7
9
7
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
U0
U1
U7
U9
UA
9
9
9
9
7
9
9
7
9
9
UA
UH
UJ
UJ
UF
Display of contents of
malfunction (first digit)
Display of contents of
malfunction (second digit)
Display 1 of
malfunction in detail
Display 2 of
malfunction in detail
1
Troubleshooting
7
7
9
9
7
9
7
9
Master
Slave1
Slave2
System
259
Si34-803
Remote
Controller
Display
A0
Applicable
Models
Method of
Malfunction
Detection
Detect open or short circuit between external input terminals in indoor unit.
Malfunction
Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal".
Supposed
Causes
Troubleshooting
Caution
External
protection device is
connected to terminals T1
and T2 of the indoor
unit terminal
block.
YES
NO
ON/OFF
input from
outside (mode No. 12,
first code No. 1) has been
set to external protection
device input (second
code No. 03)
by remote
controller.
NO
260
YES
Troubleshooting
Si34-803
3.2
Remote
Controller
Display
A1
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
NO
Troubleshooting
YES
261
3.3
Si34-803
Remote
Controller
Display
A3
Applicable
Models
FXCQ, FXFQ, FXSQ, FXKQ, FXDQ, FXMQ, FXUQ, FXHQ (Option), FXMQ200,250M (Option),
FXAQ (Option), FXMQ-MF (Option)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed
Causes
262
Troubleshooting
Si34-803
Troubleshooting
Caution
Is power supply
220~240V provided?
NO
Provide 220~240V power
supply.
YES
The float
switch is connected to
X8A of the indoor unit
PC board.
NO
YES
The float
switch contact is
forming a short circuit
(continuity check
with X8A or X15A
disconnected)
A short
circuit connector is
connected to
X8A.
NO
Connect either a short circuit
connector or float switch and
turn on again.
YES
YES
Becomes
normal when X8A of
the indoor unit PC board
is short circuited
NO
Defect of indoor unit PC board.
YES
NO
Water builds up
in the drain pan.
NO
YES
YES
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoorunit PC
board.
NO
Replace float switch.
Modify the float switch's
connection and turn on again.
NO
Connect the drain pump and
turn on again.
YES
The drain
pump works when
the power supply is reset
for the indoor
unit.
YES
Check the drain piping for
clogging or upward slope, etc.
NO
The voltage
of terminals Y1
and Y2 or X25A is
220~240 V (within
5minutes of resetting
the power
supply).
YES
Troubleshooting
NO
Replace indoor unit PC board.
263
3.4
Si34-803
Remote
Controller
Display
A6
Applicable
Models
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When number of turns cant be detected even when output voltage to the fan is maximum
Supposed
Causes
Troubleshooting
Caution
Is the
wiring from the fan
motor securely connected
to connectors on the
indoor unit PC
board?
NO
YES
Wiring
between the
indoor unit PC board and
fan motor is
disconnected.
YES
NO
Does the fan motor run?
NO
264
YES
Troubleshooting
Si34-803
Remote
Controller
Display
A6
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
An overcurrent flows.
The RPM is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.
An overcurrent flows.
265
Si34-803
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
There is a
foreign matter around
the fan.
YES
NO
The fan
motor connectors (X1A
and X2A) of the fan PC board (A2P)
are disconnected.
YES
Connect correctly.
NO
The connectors
between the indoor
PC board (A1P) and the fan
PC board (A2P) are
disconnected.
YES
Connect correctly.
NO
The fuse
(F3U, white) on the fan
PC board (A2P) is not in a
conduction state.
NO
YES
NO
YES
The resistance
between the power wire
terminals of the fan motor and
motor frame (meal part) is
1 M or below.
YES
NO
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases (*1).
A
266
Troubleshooting
Si34-803
NO
YES
Remove the signal connector
from the fan motor and check
the resistance (*2).
YES
NO
Turn on the power.
The HAP
lamp of the indoor PC
YES
board (A1P) blinks and the HAP
lamp of the fan PC board
(A2P) is off.
NO
Replace the fan motor.
*1. Measurement of power wire connector.
Remove the X1A connector from the fan PC board (A2P) and
measure the resistance between the U and V, V and W, and W
and U phases of the motor connector (with five conductors) and
check that each phase are balanced (within a permissible
dispersion range of 20%).
*2. Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between
GND and VCC, HW, HV, or HU terminals of the motor connector
(with five conductors).
Connector power wire use (X1A)
5 Red
4
3 White
2
1 Black
Troubleshooting
GND
4 Pink
Vcc
3 Orange
Hw
2 Blue
HV
1 Yellow
HU
267
3.5
Si34-803
Remote
Controller
Display
A7
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
268
Troubleshooting
Si34-803
Troubleshooting
Caution
Is power supply
220~240V provided?
NO
Provide 220~240V power
supply.
YES
Indoor unit
is a model equipped
with a swing flap
function
NO
YES
The swing
motor works when
the power supply is turned
off and then back
on.
YES
NO
The connector
is connected to X9A of
the indoor unit PC
board.
NO
YES
The limit switch
functions normally.
NO
YES
After
turning
the swing-flap
ON and then
stopping with the
remote controller, the
voltage of X6A of the indoor
unit PC board is 220 ~ 240
VAC (60 Hz) / 220 VAC
(50 Hz) when turned on
again (within 30
seconds of
turning on
again).
The connecting
cable is short-circuited
or disconnected.
YES
NO
NO
YES
The connecting cable
has no continuity.
YES
NO
When
the air flow
direction flap's cam
mechanism is disconnected
from the swing motor,
operation is normal
when turned
on again.
YES
Troubleshooting
NO
269
3.6
Si34-803
Remote
Controller
Display
A8
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the input voltage of fan motor is 150V and below, or 386V and above.
Supposed
Causes
Troubleshooting
Caution
There
are problems on
the condition of power
source described
above.
YES
NO
"A8"
Reoccurrence
of malfunction.
YES
NO
It is possible to have external
factor, such as brownout and
instantaneous blackout.
270
Troubleshooting
Si34-803
3.7
Remote
Controller
Display
A9
Applicable
Models
Method of
Malfunction
Detection
Use a microcomputer to check the electronic expansion valve for coil conditions.
Malfunction
Decision
Conditions
When the pin input of the electronic expansion valve is not normal while in the initialization of
the microcomputer.
Supposed
Causes
Troubleshooting
Caution
The
electronic
expansion valve is
connected to X7A of the
indoor unit PC
board.
YES
Normal
when coil check
(1) of the moving part of
the electronic expansion
valve is
checked.
NO
NO
YES
The connecting
cable is short-circuited or
disconnected.
NO
Troubleshooting
YES
271
Si34-803
1: Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
1. White
2. Yellow
3. Orange
{
Approx.
300
4. Blue
{
Approx.
300
5. Red
{
Approx.
150
{
Approx.
150
6. Brown
{
Approx.
150
{
Approx.
150
6. Brown
{: Continuity
: No continuity
272
Troubleshooting
Si34-803
3.8
Remote
Controller
Display
AF
Applicable
Models
Method of
Malfunction
Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is in
non-operation.
Malfunction
Decision
Conditions
When the float switch changes from ON to OFF while the compressor is in non-operation.
Supposed
Causes
Troubleshooting
Caution
Field drain
piping has a defect such as
upward sloping.
YES
NO
A humidifier
unit (optional accessory)
is installed on the
indoor unit.
YES
NO
Defect of indoor unit PC board.
Troubleshooting
273
3.9
Si34-803
Remote
controller display
AJ
Applicable
Models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
is determined.
Malfunction
Decision
Conditions
Operation and:
When the capacity code is not contained in the PC boards memory, and the capacity setting
adaptor is not connected.
Supposed
Causes
Troubleshooting
Caution
The indoor
unit PC board was replaced
with a replacement
PC board.
NO
Replace the indoor unit PC board.
YES
Was the
capacity setting
adapter mounted when
replacing the
PC board?
NO
274
YES
Troubleshooting
Si34-803
C1
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detecion
Check the condition of transmission between indoor PC board (A1P) and PC board for fan
(A2P) using computer.
Malfunction
Decision
Conditions
Supposed
Causes
Connection defect of the connecter between indoor PC board (A1P) and PC board for fan
(A2P).
Malfunction of indoor PC board (A1P).
Malfunction of PC board for fan (A2P).
External factor, such as instantaneous blackout.
Troubleshooting
275
Si34-803
Troubleshooting
Caution
Is the connector
between indoor PC board (A1P) and
PC board for fan (A2P) accurately
connected? (*1)
NO
YES
Confirm the condition
of transmission on
indoor PC board
using local installation
mode. (*2)
NO
YES
Connect the
connecter X70A and
turn on the power
again.
"C1"
Malfunction
breaks out
again.
YES
NO
Connect it and operate (It is
possible to have a cause, such
as instantaneous blackout)
1. Pull out and insert the connecter once and check it is absolutely connected.
2. Method to check transmission part of indoor PC board.
Turn off the power and remove the connecter X70A of indoor PC board (A1P).
Short-circuit X70A.
After turning on the power, check below numbers under local setting remote control.
(Confirmation: Setting position NO. at the condition of setting switch No. 21 on mode No.
41)
Determination
01: Normal
Other than 01: Transmission defect on indoor PC board
After confirmation, turn off the power, take off the short-circuit and connect X70A back to
original condition.
276
Troubleshooting
Si34-803
C4
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Troubleshooting
Caution
Is the
thermistor normal?
YES
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
5 k to 90 k
YES
NO
Troubleshooting
277
Si34-803
C5
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Troubleshooting
Caution
Is the
thermistor normal?
YES
NO
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
5 k to 90 k
YES
NO
278
Troubleshooting
Si34-803
C6
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detection
Conduct open line detection with PC board for fan (A2P) using indoor PC board (A1P).
Malfunction
Decision
Conditions
When the communication data of PC board for fan (A2P) is determined as incorrect.
Supposed
Causes
Troubleshooting
Caution
Is the
type of PC
board for fan (A2P)
correct?
NO
YES
NO
Was
indoor PC board
(A1P) replaced with
supplementary PC
board?
YES
Was
correct capacity setting
adapter installed when replacing it
with supplementary PC
board?
NO
YES
After establishing transmission
for indoor and outdoor,
diagnose the operation again.
Troubleshooting
279
Si34-803
C9
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Supposed
Causes
Troubleshooting
Caution
Is the
thermistor normal?
NO
YES
5 k to 90 k
YES
NO
280
Troubleshooting
Si34-803
CC
Applicable
Models
FXFQ
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Faulty sensor
Disconnection
Troubleshooting
Caution
Does it
function normally?
YES
It is normal.
(Poor connector contact)
NO
Delete the malfunction code
record from the remote
controller. (*1)
Is "CC"
displayed on
the remote
controller? (*2)
YES
NO
It is believed that external factors
(noise or else) other than failure
caused the malfunction.
*1: To delete the record, the ON/OFF button of the remote controller must be pushed and
held for 5 seconds in the check mode.
*2: To display the code, the Inspection/Test Operation button of the remote controller must be
pushed and held in the normal mode.
*3: If "CC" is displayed even after replacing the humidity sensor PC board ASS'Y (A2P) and
taking the steps *1 and 2, replace the indoor PC board ASS'Y (A1P).
Troubleshooting
281
Si34-803
CJ
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the remote controller air temperature thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
Troubleshooting
Caution
Note:
YES
In case of remote controller thermistor malfunction, unit is still operable by suction air thermistor
on indoor unit.
Refer to Thermistor Resistance / Temperature Characteristics table on P.427.
282
Troubleshooting
Si34-803
E1
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Return to normal?
NO
YES
Troubleshooting
283
Si34-803
E3
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure:
2.85MPa
Supposed
Causes
284
Troubleshooting
Si34-803
Troubleshooting
Caution
Are the
three points above
OK?
NO
YES
Mount a pressure gauge on the high-pressure service port.
Connect the Service Checker.
Reset the operation using the remote controller,
and then restart the operation.
YES
Is the HPS
operating value normal
(i.e., 4.0MPa)?
YES
NO
Are the
characteristics of the high
pressure sensor normal?
(See *1.)
NO
NO
YES
Is the
pressure detected with
the PC board normal?
(See *2.)
NO
YES
The high pressure sensor is normal, and the pressure detected with the PC board is also normal.
The high pressure has really become high.
Referring to information on page 360, remove the causes by
CHECK 3 which the high pressure has become high.
*1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on page 429.)
*2: Make a comparison between the high pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
+5V
Red
(3)
Black
(2)
Micro controller
A/D input
(1)
High
pressure
sensor
White
Make measurement of DC
voltage between these wires.
Troubleshooting
285
Si34-803
E4
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under specific pressure.
Operating pressure:0.07MPa
Supposed
Causes
286
Troubleshooting
Si34-803
Troubleshooting
Caution
NO
Is the stop
valve open?
YES
Mount a pressure gauge on the low-pressure service port.
Connect the Service Checker.
Reset the operation using the remote controller, and then
restart the operation.
Are the
characteristics of the
low pressure sensor
normal?
(See *1.)
NO
YES
Is the
pressure detected
with the PC board
normal?
(See *2.)
NO
YES
The low pressure sensor is normal, and the pressure
detected with the PC board is also normal.
The low pressure has really become low.
*1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on page 429.)
*2: Make a comparison between the low pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
+5V
Connector for low pressure sensor
(Blue)
Micro controller
A/D input
(4)
Red
(3)
Black
(2)
White
Low
pressure
sensor
(1)
Troubleshooting
287
Si34-803
E5
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phasecurrent waveform.
Malfunction
Decision
Conditions
This malfunction will be output when the inverter compressor motor does not start up even in
forced startup mode.
Supposed
Causes
288
Troubleshooting
Si34-803
Troubleshooting
Caution
NO
On-site causes.
Open the stop valve.
YES
Check the compressor cable
for disconnection and flaws.
YES
NO
Are wire
connections made to
phases U, V, and W in the
proper order and
manner?
NO
YES
Are wire
connections properly
made (according to the
Wiring Diagram)?
U
V
NO
Are the wire connections
mixed up with those for
non-inverter compressor?
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
The insulation
resistance is low (i.e., not
more than
100k.)
YES
Replace the
compressor.
NO
Check the compressor motor
coil for any broken wire.
YES
NO
Restart the
compressor, and then
check whetehr or not
the malfunction
recurs.
Power ON
YES
Has the
compressor started
up at high differential
pressure (not less
than 0.5MPa)?
NO
Troubleshooting
NO
YES
End of work
Faulty pressure
equalization or else
may have occurred.
Check the refrigerant
system.
Faulty pressure
equalization:
Check the refrigerant
system.
Replace the
compressor.
Conduct checks and
diagnosis of the
compressor.
289
Si34-803
E6
Remote
Controller
Display
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
400 V class unit : 15.0 A
200 V class unit : 28.8 A
Supposed
Causes
Troubleshooting
Caution
NO
YES
NO
Is the power
supply voltage
normal?
YES
Is the
magnetic switch
(K2M, K3M)
normal?
YES
NO
NO
Check the wiring from power supply ~ current sensor (A6P, A7P) ~
MgS (K2M, K3M) ~ compressor
Is
above wiring
correct?
NO
Correct wiring.
YES
Is
current sensor
correct? 1
YES
NO
Note:
290
1 Abnormal case
The current sensor value is 0 during STD compressor operation.
The current sensor value is more than 15.0A during STD compressor stop.
Troubleshooting
Si34-803
E7
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction of fan motor system is detected according to the fan speed detected by hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
When the fan runs with speed less than a specified one for 6 seconds or more when the fan
motor running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
Troubleshooting
291
Si34-803
Troubleshooting
Caution
YES
NO
Any of
the fan motor
connectors X1A and
X3A or the relay harness
connectors Z5C, Z9C,
and X1A is
disconnected.
YES
NO
Different
power supply
cable connector and
signal cable connector
have been connected to the
relay harness. (Power supply
and signal cable connectors
of different colors are
connected for one
and the same
motor.)
YES
NO
Connectors
of harness between
the compressor inverter
PC board and the fan
inverter PC board (A4P
and A8P) are
disconnected.
YES
NO
The fuse
(white tubular fuse)
on the fan inverter PC board has
a broken wire (has no
continuity).
YES
NO
With
the connector
disconnected from the
fan motor, the fan
cannot be rotated
by hand.
YES
NO
Resitance
between the fan motor
power supply cable terminal
and the motor frame
(metal part) is not
more than
1M.
NO
A
292
YES
Troubleshooting
Si34-803
Troubleshooting
A
Check 1
Check for the fan motor
connector (Power supply cable)
Resistance
of the U, V, and W
phases of the fan motor
has got imbalanced or short
circuits have been established
amoung the U, V,
and W
phases.
YES
NO
Check 2
Check for the fan motor
connector (Signal cable)
Has a
short circuit been
established between
the fan motor signal cables
Vcc and GND, and UVW
and GND,
respectively?
YES
NO
Turn ON the power supply.
The LED
(HAP) on the
compressor inverter PC
board is blinking, but the LED
(HAP) on the fan inverter
PC board is not
blinking.
YES
NO
Note:
Troubleshooting
293
Si34-803
E9
Applicable
Models
RXYQ5P(A)~54P(A)Y1
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
294
Troubleshooting
Si34-803
Troubleshooting
Caution
YES
NO
Electronic
expansion valve is
connected to X21A and
X23A of outdoor unit
PC board
(A1P).
NO
* X26A only for RXYQ5M
YES
Normal
when coil
check (1) of the moving
part of the electronic
expansion valve is
checked.
NO
YES
The connecting
cable is short-circuited or
disconnected.
YES
NO
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
Measuring points
1-6
2-6
3-6
4-6
(Gray) 6
Troubleshooting
295
Si34-803
F3
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Discharge
pipetemperature is 115C
or higher when the unit stop
by malfunction.
YES
NO
Pull out the discharge pipe
thermistor from the outdoor PC
board, and then make
measurement of resistance
using a multiple meter.
Are
the characteristics
of the discharge pipe
thermistor normal?
(3.5~400K)
YES
NO
296
Troubleshooting
Si34-803
F6
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Excessive charging of refrigerant is detected by using the outside air temperature, heat
exchanging deicer temperature and liquid pipe temperature during a check run.
Malfunction
Decision
Conditions
When the amount of refrigerant, which is calculated by using the outside air temperature, heat
exchanging deicer temperature and liquid pipe temperature during a check run, exceeds the
standard.
Supposed
Causes
Refrigerant overcharge
Misalignment of the outside air thermistor
Misalignment of the heat exchanging deicer thermistor
Misalignment of the liquid pipe thermistor
Troubleshooting
Caution
Are the
above thermistor
installed on pipes
correctly?
NO
YES
Remove the outside air thermistor,
heat exchanging deicer thermister
and the liquid pipe thermistor from
the outdoor PC board and measure
resistance with a tester.
Is the
characteristic of the
above thermistor
normal?
YES
NO
Replace thermistor.
Refrigerant overcharged.
Troubleshooting
297
Si34-803
H7
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Is the fan
motor connector
X2A connected to PC board
for Fan inverter
correctly?
NO
Connect correctly.
YES
Check of fan motor connector.
(+1)
The
resistance of
fan motor read wire
connector pins between
Vcc-UVW and
GND-UVW
balanced?
NO
YES
298
5 Gray
GND
4 Pink
Vcc
3 Orange
2 Blue
1 Yellow
Measure the
resistance
between VccUVW and
GND-UVW.
Troubleshooting
Si34-803
H9
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Troubleshooting
Caution
Connector is
connected to X18A of
outdoor PC board
(A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PC board.
(1.8k to
800k)
YES
NO
Troubleshooting
299
Si34-803
J2
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
Troubleshooting
Caution
Is the
connector for
current sensor
connected to X25A, X26A
on outdoor unit
PC board
(A1P)?
NO
YES
Are the
current sensors inversely
connected to two STD
compressors?
YES
NO
Is the
current sensor
mounted on the T-phase
(A6P) and R-phase
(A7P) wire?
YES
300
NO
Troubleshooting
Si34-803
J3
Remote
Controller
Display
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R31T, R32T or R33T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Defect of thermistor connection
Troubleshooting
Caution
Connector
is connected to X29A
of outdoor unit
PC board
(A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R31, 32T or R33T from the
outdoor unit PC board.
(2.5k to
1.3k)
NO
YES
The alarm indicator is displayed when the fan is being used also.
Note:
5 HP class R3T
8~12 HP class R31T, R32T
14, 16Hp class R31T, R32T and R33T
Troubleshooting
301
Si34-803
J5
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the suction pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Supposed
Causes
Troubleshooting
Caution
Connector
is connected to
X30A, of outdoor unit
PC board.
(A1P)
NO
YES
Resistance
is normal when
measured after disconnecting the thermistor
(R2T), (R7T) from the
outdoor unit PC
board. (1.8k
to 800k)
YES
NO
302
Troubleshooting
Si34-803
J6
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Troubleshooting
Caution
Connector
is connected to X30A
of outdoor unit PC
board (A1P).
NO
YES
Resistance
is normal when
measured after
disconnecting the thermistor
R4T from the indoor
unit PC board.
(1.8k to
800k)
YES
NO
Troubleshooting
303
Si34-803
J7
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Is
the connector
for liquid pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?
NO
YES
Is the
resistance
measured after
removing the thermistor
(R6T) from outdoor unit PC
board normal?
(1.8k to
800k)
YES
NO
304
Troubleshooting
Si34-803
J9
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Supposed
Causes
Troubleshooting
Caution
Is
the connector
for subcooling heat
exchanger gas pipe
thermistor connected to
X30A on outdoor
unit PC board
(A1P)?
NO
YES
Is the
resistance
measured after
removing the thermistor
(R5T) from outdoor unit PC
board normal?
(1.8k to
800k)
YES
NO
Troubleshooting
305
Si34-803
JA
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
The high
pressure sensor is
connected to X32A of
outdoor unit PC
board (A1P).
NO
YES
The
relationship
between the 1
VH and high pressure
is normal (see 2) when
YES
voltage is measured between
X32A pins (1) and (3) of
outdoor unit PC
board (A1P)
(see 1).
NO
306
Troubleshooting
Si34-803
JC
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
The low
pressure sensor is
connected to X31A of
outdoor unit PC
board (A1P).
NO
YES
The
relationship
between the 1
VL and low pressure is
normal (see 2) when voltage
is measured between X31A pins
(2) and (3) of outdoor unit
PC board (A1P)
(see 1).
YES
NO
Troubleshooting
307
Si34-803
L4
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 93C.
Supposed
Causes
Troubleshooting
Caution
Power OFF
Fin temperature
of the compressor
inverter is high.
YES
NO
Remove and insert the fin
thermistor connector "X111A".
Power ON
Turn ON
the power supply,
YES
and then check whether or
not the malfunction
recurs.
NO
308
End of measures
It is supposed that
radiation fin
temperature has risen
due to on-site causes.
Conduct the checks
shown below.
Radiation fin for stains
Airflow for interference
Fan propeller for
damage
Whether or not
outdoor temperature
is too high
Troubleshooting
Si34-803
Troubleshooting
309
Si34-803
L5
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Compressor inspection
Caution
NO
On-site causes.
Open the stop valve.
YES
Power OFF
The
compressor cable has
a defect.
NO
YES
310
Troubleshooting
Si34-803
Troubleshooting
A
Power OFF
The insulation
resistance is low (i.e.,
not more than
100k.)
YES
NO
Check the compressor motor
coil for any broken wire.
YES
NO
Check the power transistor on
the inverter PC board using a
multiple tester. [For details,
refer to information in the
"Check for power transistor"
on Page 430.
The power
transistor has an
abnormality.
YES
NO
Make wire connections
according to the Wiring Diagram.
Power ON
Restart the
compressor, and then
check whether or not
the malfunction
recurs.
NO
YES
Power OFF
Power ON
Troubleshooting
Restart the
compressor, and then
check whether or not
the malfunction
recurs.
YES
NO
Normal
On-site causes such as
instantaneous power
failure or open phase
Conduct checks and
diagnosis of the
compressor.
End of work
311
Si34-803
L8
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When overload in the compressor is detected. (Inverter secondary current 16.1A (Y1, YL) and
27.6A (TL))
Supposed
Causes
Troubleshooting
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
Faulty compressor
Caution
Power ON
YES
NO
Is the stop valve
open?
NO
Overcurrent:
Check the compressor
and refrigerant system
(in the same manner as
that for E3).
Open the stop valve.
YES
Are wire
connections properly
made (according to the
Wiring Diagram)?
NO
Check the compressor cable for
any disconnection or flaws.
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Power OFF
The insulation
resistance is low, i.e.,
not more than
100k.)
YES
Replace the
compressor.
NO
Check the power transistor on
the inverter PC board using a
multiple tester.
Does the
power transistor have any
abnormalities?
NO
Connect the compressor cable,
and then restart the operation.
A
312
YES
Troubleshooting
Si34-803
Troubleshooting
A
Is a difference
between high pressure
and low pressure prior
to startup
0.2MPa?
NO
Faulty pressure
equalization:
Check the refrigerant
system.
YES
Power ON
NO
It can take a maximum of 60 minutes
to determine the malfunction.
End of measures:
Check the refrigerant
system.
YES
Check of compressor:
Check the compressor
for abnormal sounds,
vibration, operating
conditions, and others
according to the
Compressor Diagnosis
Procedure.
Troubleshooting
313
Si34-803
L9
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
This malfunction code will be output if overcurrent occurs at the time of startup.
Malfunction
Decision
Conditions
Supposed
Causes
Defect of compressor
Pressure differential start
Defect of inverter PC board
Troubleshooting
Caution
NO
YES
Are wire
connections properly
made (according to the
Wiring Diagram)?
NO
Check the compressor cable for
any disconnection or flaws.
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Power OFF
The insulation
resistance is low (i.e.,
not more than
100k.)
YES
Replace the
compressor.
NO
Check the power transistor on
the inverter PC board using a
multiple tester.
Does the
power transistor have any
abnormalities?
NO
Connect the compressor cable,
and then restart the operation.
A
314
YES
Troubleshooting
Si34-803
Troubleshooting
A
Is a difference
between high pressure
and low pressure prior
to startup
0.2MPa?
NO
Faulty pressure
equalization:
Check the refrigerant
system.
YES
Power ON
NO
It can take a maximum of 60 minutes
to determine the malfunction.
End of measures:
Check the refrigerant
system.
YES
Check of compressor:
Check the compressor
for abnormal sounds,
vibration, operating
conditions, and others
according to the
Compressor Diagnosis
Procedure.
Troubleshooting
315
Si34-803
LC
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Check the communication state between inverter PC board and control PC board by microcomputer.
Malfunction
Decision
Conditions
Supposed
Causes
316
Malfunction of connection between the inverter PC board and outdoor control PC board
Defect of outdoor control PC board (transmission section)
Defect of inverter PC board
Defect of noise filter
Faulty fan inverter
Incorrect type of fan inverter
Faulty compressor
Faulty fan motor
Troubleshooting
Si34-803
Troubleshooting
Caution
NO
YES
Power ON
Check
whether or not
the power supply voltage
between L2 and N falls in
the range of 220 to
240VAC?
NO
On-site cause.
Correct the wiring.
YES
Is the type
(PC No.) of the fan
inverter correct?
NO
YES
Power OFF
RXYQ5PA
RXYQ8PA
RXYQ10PA
RXYQ12PA
RXYQ16PA
RXYQ18PA
The insulation
resistance is low (i.e., not
more than
100k.)
FAN1
PC0511-3
PC0511-1
PC0511-1
PC0511-3
PC0511-3
PC0511-1
FAN2
PC0511-4
PC0511-4
PC0511-2
YES
RXYQ5PTL
RXYQ8PTL
RXYQ10PTL
RXYQ12PTL
RXYQ14PTL
RXYQ16PTL
RXYQ18PTL
FAN1
PC0615-1
PC0615-2
PC0615-2
PC0615-1
PC0615-1
PC0615-1
PC0615-2
FAN2
PC0715-1
PC0715-1
PC0715-1
PC0715-2
Replace the
compressor.
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
The insulation
resistance is low (i.e., not
more than
1M.)
YES
NO
Check for connector connections: Remove and insert the
connectors shown below.
RXYQ-PA
RXYQ-PTL
[Fan 1]
[Fan 2]
[Fan 1] : A2P
A1P X28A X6A A3P
A4P X51A X5A A8P
[Fan 2] : A5P
A1P X20A X4A A3P
A4P X4A X3A A8P
A3P X61A X402A A2P
A8P X4A Short connector
A3P X1A X403A A2P
A3P X5A X5A A4P
Note) X3A: black
A3P X41A X3A A4P
X4A: yellow
A4P X4A Short connector
F400U of the
A2P has been
molten.
YES
NO
A
Troubleshooting
F400U
RXYQ-PA
317
Si34-803
Troubleshooting
A
NO
NO
YES
NO
The LC malfunction recurs.
YES
NO
End of measures:
The malfunction may
temporarily result from
on-site causes.
Causes:
Instantaneous power
failure (open phase),
noises, or else.
318
Troubleshooting
Si34-803
P1
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
minutes.
Supposed
Causes
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PC board
Defect of K2 relay in inverter PC board
Improper main circuit wiring
Troubleshooting
Caution
Imbalance
in supplied voltage is
in excess of 14 V
(Y1). 1
YES
Open phase?
NO
NO
Is
the voltage
imbalance applied to the
inverter in excess of
14 V (Y1)?
2
YES
No abnormalities are
observed in the power
supply, but the imbalance
in voltage recurs.
YES
Open phase
Normalize field cause.
Fix power supply voltage
imbalance.
Part or wiring defect
After turning the power supply
OFF, check and repair the
main circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K2 contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
Explanation for users In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results"and leave Be sure to explain to the user that
there is a "power supply imbalance"
it up to him to improve the imbalance.
for which DAIKIN is not responsible.
Troubleshooting
319
Si34-803
P4
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed
Causes
Troubleshooting
Caution
Power OFF
YES
Replace the
compressor.
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
The insulation
resistance is low (i.e., not more than
1M.)
YES
NO
Remove and insert the fin
thermistor connector [X111A].
Power ON
Turn ON the
power supply, and then check
whether or not the malfunction
recurs.
YES
NO
End
320
Troubleshooting
Si34-803
Troubleshooting
321
Si34-803
PJ
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
The faulty (or no) field setting after replacing PC board or faulty PC board combination is
detected through communications with the inverter.
Malfunction
Decision
Conditions
Whether or not the field setting or the type of the PC board is correct through the communication
date is judged.
Supposed
Causes
Troubleshooting
Caution
Has the PC
board been replaced?
NO
YES
When
replacing the
main PC board, were field
setting properly
made?
NO
YES
Is the type of
PC board correct?
YES
NO
322
Troubleshooting
Si34-803
U0
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Cooling
YES
NO
The suction
pipe temperature minus
coil temperature is 20 C
or higher.
Low pressure
is 0.1 MPa
or less.
NO
The
voltage
of X31A pins (2)
and (3) on main
outdoor unit PC board
(A1P) is 0.8 VDC or less.
(Low pressure
sensor output
voltage)
2
NO
YES
YES
YES
NO
Resistance
is normal when
measured with the
suction pipe thermistor
(R7T) and coil thermistor
(R4T) disconnected
from the outdoor
unit PC
board.
1
YES
NO
Troubleshooting
323
Si34-803
U1
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
There
is an open phase
at the power supply
terminal section (X1M)
of the outdoor
unit.
YES
NO
Operation
is normal if one
place of power supply
line phase is
replaced.
NO
324
YES
Reverse phase
Counter measure of the problem is
completed by phase replacement.
Replace outdoor unit PC board
(A1P).
Troubleshooting
Si34-803
U2
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
When the voltage aforementioned is not less than 780V or not more than 320V, or when the
current-limiting voltage does not reach 200V or more or exceeds 740V.
Supposed
Causes
Troubleshooting
325
Si34-803
Troubleshooting
Caution
On-site causes.
Make proper wire connections
without open phase, erroneous
connections, or erroneous order of
phases.
YES
Power ON
Unbalanced
power supply? (Not more
than 2%: Phase voltage of
not more than
approx. 5V)
Power OFF
NO
NO
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
The
YES
insulation resistance is
low (i.e., not more than
100k.)
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
The
insulation resistance is
low (i.e., not more than
1M.)
NO
YES
On-site causes
Correct the unbalanced loads to
eliminate the unbalanced state.
Unbalanced voltage will cause
extremely unbalanced current,
thus impairing the service life of or
resulting in the malfunction of the
equipment.
YES
NO
YES
326
Troubleshooting
Si34-803
Troubleshooting
A
Power OFF
YES
A3P: Replace the inverter PC board.
If the PC board replaced is badly
damaged, the compressor is
likely to get faulty. To make sure,
recheck the compressor.
NO
Has the
fan driver caused
damage?
YES
NO
YES
NO
Power ON
Stop (standby)
when the compressor
starts up.
YES
NO
The U2
malfunction recurs.
YES
NO
End of measures:
The malfunction may temporarily
result from on-site causes.
Causes: Instantaneous power
failure (open phase), noises, or
else.
Troubleshooting
327
Si34-803
U3
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Troubleshooting
Caution
Has the
check operation
performed on Outdoor
unit PC board?
YES
NO
328
Troubleshooting
Si34-803
U4
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address doesnt match
Defect of indoor unit PC board
Defect of outdoor unit PC board
Troubleshooting
329
Si34-803
Troubleshooting
Caution
Has
the indoor
or outdoor unit PC
board been replaced,
or has the indoor - outdoor
or outdoor - outdoor unit
transmission wiring
been
modified?
YES
NO
All
indoor unit
remote controllers of the
same refrigerant system
display
"U4."
NO
Is indoor
- outdoor and outdoor outdoor unit transmission
wiring normal?
YES
NO
YES
Outdoor
unit PC board
microcomputer monitor
(HAP) blinks.
NO
YES
The
voltage between
terminals L1 and N of the
outdoor unit PC board
is 220~240 V
10%.
NO
Supply 220~240 V.
YES
The fuse on
the outdoor unit's PC
board is burnt.
NO
NO
YES
Operation
ready lamp (H2P) is
blinking.
YES
Lamp does
not go off for 12 minutes
or more.
YES
NO
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
NO
YES
Disconnect
the outdoor-outdoor
unit transmission wiring, and
then check with a single
system whether or
not it
is normal.
YES
330
NO
Troubleshooting
Si34-803
U5
Applicable
Models
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer is signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Using
2-remote controllers
control.
YES
NO
All indoor
PC board microcomputer
monitors blink.
YES
NO
NO
YES
Operation
returns to normal when
the power is turned off
momentarily.
YES
Normal
SS1 of
both remote controllers
is set to "MAIN."
YES
NO
NO
Replace the indoor unit PC
board.
Normal
NO
Troubleshooting
YES
Normal
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
331
Si34-803
U7
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Improper connection of transmission wiring between outdoor unit and external control
adaptor for outdoor unit
Improper connection of transmission wiring between outdoor units.
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defect of outdoor unit PC board (A1P)
Defect of external control adaptor for outdoor unit
332
Troubleshooting
Si34-803
Troubleshooting
Caution
Is there any
broken wire or erroneous
wire connection in the
communication wiring of
multi outdoor unit
system?
NO
YES
C/H SELECT is set to "IND".
YES
NO
Cool / heat selection is
unified.
NO
YES
C/H SELECT
is set to
"MASTER."
YES
NO
C/H SELECT
is set to
"SLAVE."
YES
NO
External control adaptor for outdoor unit
Is this PC board energized?
Does the cool/heat unified address match?
Outdoor unit (unified master unit)
Is this energized?
Does the cool/heat unified address match?
YES
Does a
malfunction occur when
the cool / heat selector is
set to "IND?"
NO
YES
Replace the outdoor unit PC
board (A1P).
Troubleshooting
333
Si34-803
U8
Applicable
Models
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
Using 2-remote
controllers control.
NO
YES
SS1
of both remote controllers is
setto "SUB."
YES
334
SS1
of remote controller PC boards
is set to "MAIN."
NO
YES
NO
Troubleshooting
Si34-803
U9
Applicable
Models
Method of
Malfunction
Detection
Detect the malfunction signal of any other indoor unit within the system concerned.
Malfunction
Decision
Conditions
When the malfunction decision is made on any other indoor unit within the system concerned.
Supposed
Causes
Troubleshooting
Caution
"U9"
has been displayed for 2
minutes or more.
YES
Troubleshooting
NO
335
Si34-803
UA
Applicable
Models
Method of
Malfunction
Detection
A difference occurs in data by the type of refrigerant between indoor and outdoor units.
The number of indoor units is out of the allowable range.
Malfunction
Decision
Conditions
Supposed
Causes
336
Troubleshooting
Si34-803
Troubleshooting
Caution
Is the
malfunction code "UA"
displayed?
NO
Normal
(It is assumed that the code is
displayed due to temporary
external cause (e.g. noises).
YES
Is the
malfunction code
"UA" displayed for all
indoor units connected to
one and the same
system?
YES
Is the outdoor
PC board replaced
to spare parts PC
board ?
NO
Is
the type of
refrigerant for the
indoor units with "UA"
displayed corresponding
to that for the
outdoor
units?
YES
NO
YES
NO
The total
of indoor units
displaying "UA" and
indoor units connected to the NO
same refrigerant system is
within connectable
number of
unit
YES
Replace the indoor unit PC board.
Does the
refrigerant type of indoor
and outdoor unit
match?
NO
YES
Is it a multi
outdoor unit connection
system?
NO
YES
Is the
combination of master
unit and slave unit
correct?
NO
YES
Replace the outdoor unit main PC
board.
The number of indoor units that can be connected to a single outdoor unit system depends on
the model of outdoor unit.
Troubleshooting
337
Si34-803
UC
Applicable
Models
Method of
Malfunction
Detection
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Caution
338
Troubleshooting
Si34-803
UE
Applicable
Models
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Failure of PC board for central remote controller
Defect of indoor unit PC board
Troubleshooting
339
Si34-803
Troubleshooting
Caution
Check
the indoor
unit for which
UE is displayed.
Is the the transmission
malfunction (UE)
caused on
all indoor
units?
YES
Continued to A
(on the following
page)
NO
Is the
power supply of
the indoor unit, on which
the UE occurred,
turned ON?
NO
YES
Has
the setting of
central control group No.
been made with the
indoor unit on which
the UE
occurred?
NO
YES
340
YES
NO
YES
Was
the central
control group No.
for indoor unit
changed?
Can
the setting of
central control group
No be made?
For VRV
systems, can the
setting of central controlgroup
No. be made in one and
the same refrigerant
system?
NO
YES
NO
Troubleshooting
Si34-803
Troubleshooting
A
Check the
transmission
wiring between central
equipment for any broken
wire. For details, refer to
information in the Procedure
for checking broken
wires section.
(Refer P.352)
Abnormal
Normal
Check the
transmission
wiring with the master
unit central equipment for
any broken wire. For details,
refer to information in the
Procedure for checking
broken wires
section.
(Refer P.352)
Abnormal
Normal
Has the
master unit central
setting connector been
connected?
NO
YES
Disconnect the transmission
wiring of the master unit
central equipment, and then
check the voltage between the
transmission terminals (F1 and
F2) of the master unit
transmission equipment using
a multiple meter.
Is the
voltage between
the terminals F1 (+)
and F2 (-) in the range of
15.2 to 17.6
VDC?
YES
NO
Troubleshooting
341
Si34-803
UF
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to
that of indoor units that have made changes in temperature.
Malfunction
Decision
Conditions
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdooroutdoor units
Failure to execute check operation
Defect of indoor unit PC board
Stop valve is left in closed
Troubleshooting
Caution
NO
YES
Is the
check operation
carried out?
NO
YES
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
YES
Is indoor
-outdoor and outdooroutdoor unit transmission
wiring normal?
YES
Replace indoor unit PC board.
NO
NO
Note:
342
Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
Troubleshooting
Si34-803
UH
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdooroutdoor units
Defect of indoor unit PC board
Defect of outdoor unit PC board (A1P)
Troubleshooting
343
Si34-803
Troubleshooting
Caution
Is
electricity
being introduce for
the first time after
YES
installation or after an indoor
or outdoor unit PC
board has been
replaced?
NO
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
NO
Normal
YES
NO
YES
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outdoor
units?
NO
Normal
YES
Disconnect
the outdoor-outdoor
unit transmission
wiring to create the onesystem status, and then
check whether or not
the system is
normal.
YES
NO
Does
a "UH" malfunction occur
for all indoor units in
the system?
YES
344
NO
Troubleshooting
Si34-803
M1 PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
With M1 displayed
Without M1 displayed
Troubleshooting
345
4.2
Si34-803
Remote
Controller
Display
M8
Applicable
Models
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data. (The system will be
automatically reset.)
Malfunction
Decision
Conditions
When no master controller is present at the time of the startup of slave controller.
When the centralized controller, which was connected once, shows no response.
Supposed
Causes
346
Troubleshooting
Si34-803
Troubleshooting
Caution
Were
any changes
made to the number
of units of central
equipment? (The central
equipment was connected once,
and then disconnected, or
additional central
equipment was
installed.)
YES
NO
NO
Have power
supplies to every central
equipment been
turned ON?
YES
Is the display of LCD OK?
Is the
Intelligent Touch
Controller used?
NO
NO
YES
Normal
Troubleshooting
Abnormal
347
4.3
Si34-803
Remote
Controller
Display
MA
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
When the remote control adapter is present.
Supposed
Causes
348
Troubleshooting
Si34-803
Troubleshooting
Caution
Has the
remote control adapter
(KRP2A series) been
connected?
YES
NO
Has the
schedule timer been
connected?
YES
NO
Has
the Interface for
BaCnet been
connected?
YES
NO
Has the
DMF-IF been
connected?
YES
NO
Has the parallel
interface been
connected?
YES
NO
NO
Are there
two or more units
of central equipment
with master unit setting
connectors (CN1/X1A)
connected?
YES
Has the
Independent/
YES
Combined use
connector(CN1/X1A) of the
schedule timer been
connected?
NO
Reset the
power supplies of every
central equipment.
Troubleshooting
349
4.4
Si34-803
Remote
Controller
Display
MC
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Two or more units of central remote controllers and Intelligent Touch Controllers are
connected, and all of them are set to master unit central setting or slave unit central setting.
Two units of schedule timers are connected.
Supposed
Causes
Troubleshooting
Caution
Did the
malfunction
occur while in the first test
run using the intelligent
Touch controller?
NO
YES
Is the
Master/Slave setting of the
central equipment
correct?
NO
Is the
NO
Master/Slave setting of the
central equipment
correct?
Be sure to
refer to the
Master/
Slave
setting
table.
(Refer
page 351.) Correct the setting of the
combination of master and
slave units, and then reset
the power supplies of every
Was the
central equipment.
central equipment connected
YES
once, and then disconnected,
Reset the power supplies of
or was additional central
every central equipment.
equipment
installed?
YES
YES
NO
Turn ON the power supply of
the central equipment with
"MC" displayed once again.
If the intelligent Touch
controller is used, correct the
setting of the combination of
master and slave units again
while in DIII-NET test run
mode, referring to the
Master/Slave setting table.
(Refer page 351.)
With "MC"
displayed
Is the "MC"
displayed again?
Without "MC"
displayed
Reset the power supplies of
every central equipment.
350
Troubleshooting
Si34-803
Master-Slave Unit
Setting Table
#1
Slave
#2
#3
#1
Pattern
#4
#2
1-00~4-15
Master/
Slave
CRC
CRC
Intelligent
Touch
controller
Master
CRC
#3
5-00~8-15
Master/
Slave
Master
CRC
Master
#4
1-00~4-15
Master/
Slave
5-00~8-15
Master/
Slave
Master
CRC
Slave
CRC
Slave
CRC
Slave
Intelligent
Touch
controller
Slave
Master
Intelligent
Touch
controller
Slave
Intelligent
Touch
controller
Master
CRC
Slave
CRC
Master
Intelligent
Touch
controller
Master
Master Unit
Central
Connector
Setting Table
The master unit central setting connector (CN1/X1A) is mounted at the factory.
To independently use a single unit of the intelligent Touch controller or a single unit of the
central remote controller, do not dismount the master unit central setting connector (i.e., use
the connector with the factory setting unchanged).
To independently use the schedule timer, insert an independent-use setting connector.
No independent-use setting connector has been mounted at the factory. Insert the
connector, which is attached to the casing of the main unit, in the PC board (CN1/X1A).
(Independent-use connector=Master unit central setting connector)
To use two or more central equipment in combination, make settings according to the table
shown below.
Central equipment connection pattern
Pattern Intelligent Central
remote
Touch
controller controller
Unified
ON/OFF Schedule
timer
controller
1 to 2
units
(*1)
1 unit
(*1)
1 to 8
units
1 to 2
units
1 to 4
units
1 to 16
units
(*1)
1 unit
1 unit
Central
remote
controller
Provided
Not provided
Unified
ON/OFF
controller
Schedule
timer
(*1)
1 unit
1 to 16
units
1 unit
1 unit
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Not provided
Not provided
Only a
single unit:
"Provided",
Others: "Not
provided"
Not provided
Provided
(*1) The intelligent Touch controller and the schedule timer are not available for combined use.
(*2) The intelligent Touch controller, central remote controller, and the unified ON/OFF controller have been set to "Provided with the master
unit central setting connector" at the factory. The schedule timer has been set to "Not provided with the master unit central setting
connector" at the factory, which is attached to the casing of the main unit.
Troubleshooting
351
Procedures for
Detecting Broken
Wires in
Transmission
Wiring for Control
Si34-803
1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short-circuit
between the outdoor-outdoor unit terminal parts F1 and F2 in the "Outdoor Unit A" that is
farthest from the central remote controller, and then conduct continuity checks between the
transmission wiring terminal blocks F1 and F2 of the central remote controller using a
multiple meter. If there is continuity between the said terminal blocks, the outdoor-outdoor
unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the outdooroutdoor unit terminal parts of the "Outdoor Unit A" short-circuited, conduct continuity checks
between the transmission wiring terminal blocks F1 and F2 of the unified ON/OFF controller.
If there is no continuity as well, conduct continuity checks between the outdoor-outdoor unit
terminal parts of the "Outdoor Unit E", between the outdoor-outdoor unit terminal parts of the
"Outdoor Unit D", between the outdoor-outdoor unit terminal parts of the "Outdoor Unit C",
in the order described, thus identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places before the
said place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for
checking the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for broken
wires)
Turn OFF the power supply to all equipment, short-circuit between the indoor-outdoor unit
terminal parts F1 and F2 in the "Outdoor Unit C, and then conduct continuity checks
between the transmission wirings F1 and F2 of the "Indoor Unit a" that is farthest from the
"Outdoor Unit C" using a multiple meter. If there is continuity between the said transmission
wirings, the indoor-outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indooroutdoor unit terminal parts of the "Outdoor Unit C" short-circuited, identify the place with
continuity in the transmission wiring of the "Indoor Unit b", transmission wiring of the "Indoor
Unit c", and transmission wiring of the "Indoor Unit d" in the order described.
If the place with continuity can be identified, there may be broken wires in places before the
said place with continuity.
Short-circuit
between the
outdoor-outdoor
unit terminal
parts.
Indoor-outdoor Unit
Transmission Wiring
Short-circuit between
the indoor-outdoor unit
terminal parts.
Outdoor-outdoor Unit
Transmission Wiring
352
Troubleshooting
Si34-803
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
353
Si34-803
Troubleshooting
Caution
Is a
malfunction
code displayed on the
remote controller?
YES
NO
Has a
once connected
indoor unit been removed
or its address
changed?
YES
NO
Is the
power supply for
the indoor unit displaying
a malfunction
turned
on?
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Is
transmission
with all indoor units
malfunctioning?
NO
YES
NO
YES
Is the
transmission
wiring with the master
controller disconnected or
wired incorrectly?
Is
the group
No. of malfunctioning
indoor units
set?
YES
NO
YES
Is the
master
controller's connector for
setting master controller
disconnected.
YES
NO
Replace the central PC board.
354
Troubleshooting
Si34-803
5.2
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When the centralized controller, which was connected once, shows no response.
The control ranges are overlapped.
When multiple master central controller are present.
When the schedule timer is set to individual use mode, other central controller is present.
When the wiring adaptor for electrical appendices is present.
Supposed
Causes
Troubleshooting
355
Si34-803
Troubleshooting
Caution
Has a once
connected optional
controller for centralized
control been disconnected
or itsaddress
changed?
YES
NO
Is the
power supply
turned on for all
optional controllers for
centralized
control?
YES
Is the
reset switch
of all optional controllers
for centralized
control set to
"normal"?
NO
NO
YES
Is
transmission wiring
disconnected or wired
incorrectly?
YES
NO
Is
a central remote
controller or schedule timer
connected?
YES
NO
Are
two or more unified
ON / OFF controllers
connected?
NO
Is the
central remote
controller or schedule
timer displaying a
malfunction?
YES
Refer to failure diagnosis for
central remote controller or
schedule timer.
NO
YES
Is the setting
of the unified
ON / OFF controller's
switch for setting
each address
duplicated?
YES
NO
356
Troubleshooting
Si34-803
A
Is the
wiring adaptor for
electrical appendices
connected?
YES
Cannot be used in
combination with a wiring
adaptor for electrical
appendices. Remove the
wiring adaptor for electrical
appendices and reset the
power supply for all optional
controllers for centralized
control simultaneously.
NO
Is a schedule timer
connected?
YES
NO
Is a parallel interface
connected?
YES
NO
Is the
schedule timer's
individual/combined
connector
connected?
NO
Are
there two or
more optional
controllers for centralized
control connected with the
connector for setting
master
controller?
YES
NO
Reset the power supply
for all optional controllers
for centralized control
simultaneously.
If the malfunction is still not cleared:
Troubleshooting
YES
357
5.3
Si34-803
Remote
Controller
Display
Applicable
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Central control address (group No.) is not set for indoor unit.
Improper control range setting switch
Improper wiring of transmission wiring
Troubleshooting
Caution
Is the central
control address (group No.) NO
set for the
indoor unit?
YES
Is the control
range setting switch
set correctly?
NO
YES
Is
the transmission
wiring disconnected or
wired incorrectly?
YES
NO
Replace the unified ON/OFF
controller.
358
Troubleshooting
Si34-803
[Check No. 1]
[Check No. 2]
Troubleshooting
Red
White
Black
5 Gray
GND
4 Pink
Vcc
3 Orange
2 Blue
1 Yellow
359
Si34-803
Local
pressure
rise
[In cooling]
If the outdoor unit electronic
expansion valve is throttled:
(See *1.)
Rise in high
pressure
Faulty high
pressure
control
High pipe
resistance
Clogging of foreign
particles
Faulty outdoor
Faulty valve coil
unit motorized
valve
Faulty valve body
A temperature difference in excess of 10C
between the inlet and the outlet is deemed to be abnormal.
Faulty high pressure sensor
Faulty
control
Faulty control PC board
Faulty valve coil
Faulty indoor
unit motorized
valve
[In heating]
If the indoor unit electronic
expansion valve excessively
throttled:
(See *2.)
[In cooling]
High suction
air
temperature
of the
condenser
Faulty
control
Short circuit
High suction
air temperature
of indoor unit
Short circuit
[In heating]
Degradation
in condensing
capacity
Dirty condenser
Decreased
fan airflow
rate
Decreased
fan
output
High air
passage
resistance
Excessive refrigerant charging
Improper model selection [In heating]
Faulty fan
motor
Faulty control
PC board
(Including
capacity setting)
Dirty filter
Obstacle
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
*2: In heating, the indoor unit electronic expansion valve is used for subcooled degree control.
(For details, refer to Electronic Expansion Valve Control on page 171.)
SDK04009
360
Troubleshooting
Si34-803
Abnormally low
low-pressure
(Low evaporating
temperature)
Faulty
compressor
capacity
control
Faulty low
pressure
protection
control
Faulty indoor
unit electronic
expansion valve
Low suction
air temperature
of the
evaporator
Faulty
control
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled:
(See *4.)
[In cooling]
Faulty
control
Short circuit
[In heating]
High pipe
resistance
Degradation
in condensing
capacity
Moisture choke
Dirty
evaporator
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Dirty filter
Obstacle
*1: For details of the compressor capacity control while in cooling, refer to Compressor PI Control on page 113.
*2: The low pressure protection control includes low pressure protection control and hot gas bypass control. For details, refer to page 153.
*3: In cooling, the indoor unit electronic expansion valve is used for superheated degree control. (For details, refer to page 171.)
*4: In heating, the outdoor unit electronic expansion valve (EV1) is used for superheated degree control of outdoor unit heat exchanger.
(For details, refer to page 141.)
Troubleshooting
SDK04009
361
362
Si34-803
Troubleshooting
Si34-803
Part 7
Appendix
1. Piping Diagrams..................................................................................364
1.1 Outdoor Unit .........................................................................................364
1.2 Indoor Unit............................................................................................371
6.
7.
8.
9.
Appendix
363
Piping Diagrams
Si34-803
1. Piping Diagrams
1.1
Outdoor Unit
RXYQ5PAY1
3D050782B
364
Appendix
Si34-803
Piping Diagrams
RXYQ5PTL
RXYQ5PAYL
3D055764D
Appendix
365
Piping Diagrams
Si34-803
RXYQ8PAY1
COMPRESSOR
3D050783C
366
Appendix
Si34-803
Piping Diagrams
RXYQ8PTL
RXYQ8PAYL
3D055765D
Appendix
367
Piping Diagrams
Si34-803
RXYQ10PA / 12PAY1
3D050784C
368
Appendix
Si34-803
Piping Diagrams
RXYQ10P / 12PTL
RXYQ10PA / 12PAYL
3D055766E
Appendix
369
Piping Diagrams
Si34-803
3D050785C
370
Appendix
Si34-803
1.2
Piping Diagrams
Indoor Unit
Heat exchanger
(4)
Fan
(2)
(3)
Liquid piping connection port
(Flare connection)
Filter
(1)
Electronic
Filter
expansion valve
DU220-602J
Code
Appendix
Name
Code
(1)
Y1E
(2)
R1T
(3)
Liquid pipe
R2T
(4)
Gas pipe
R3T
Capacity
GAS
20 / 25 / 32 / 40 / 50M(A)
63 / 80 / 100 / 125M(A)
200M(A)
250M(A)
12.7
15.9
19.1
22.2
Main function
Used for gas superheated degree control while in
cooling operation or subcooled degree control while
in heating operation.
Used for thermostat control.
Used for gas superheated degree control while in
cooling operation or subcooled degree control while
in heating operation.
Used for gas superheated degree control while in
cooling operation.
(mm)
Liquid
6.4
9.5
9.5
9.5
371
Piping Diagrams
Si34-803
FXDQ
Gas side
Liquid side
Filter
Fan
Gas
(mm)
Liquid
12.7
6.4
15.9
9.5
4D034245C
372
Gas
12.7
15.9
(mm)
Liquid
6.4
9.5
Appendix
Si34-803
Piping Diagrams
4D018650B
Appendix
Gas
15.9
19.1
22.2
(mm)
Liquid
9.5
9.5
9.5
373
Piping Diagrams
Si34-803
FXUQ + BEVQ
Indoor unit
4D037995H
Connection Unit
4D034127B
374
Appendix
RED
WHT
BLK
X1M L1 L2 L3 N
BLU
Z1C
A2P
POWER SUPPLY
Y1 : 3N~380-415V 50Hz
YL : 3N~380V 60Hz
K4M
RED
Z3C
N=5
+
P1
WHT
L1R
WHT
P2
A3P
R50 R59
C66 C63
+ +
RED
WHT
BLK
X400A
X111A
X41A
X5A
5
X2A
P<
X4A
X3A
X2A
A1P
A2P
A3P
A4P
A5P
BS1~5
K3R
K4R
X66A
HEAT
COOL
HEAT
FAN
S1S
COOL/HEAT SELECTOR
(OPTIONAL ACCESSORY)
S2S
COOL
X30A
R5T R6T
t
t
E1HC
X11A
PS
C/H SELECTOR
B
C
A
X1A X1M
A5P
Y4S
X15A
Y3S
X9A
K5R
R2T R4T
t
t
X29A
Y2S
X8A
K11R
R3T
t
Y1S
X7A
K7R
NOTE) 5
X1M
TO IN/D UNIT TO OUT/D UNIT
F1 F2 F1 F2
X21A
X32A
X31A
X18A
S1NPH
S1NPL
Y1E
M
t R1T
L1R
A4P
(BACK)
A2P
A3P
K4M
K3R
K4R
K5R
K7R
K11R
L1R
M1C
M1F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
S1NPL
S1PH
V1CP
V1R
V2R
X1A, X2A
X1M
X1M
X1M
Y1E
Y1S
Y2S
Y3S
Y4S
Z1C~5C
Z1F
A5P
A1P
X1M
(FRONT)
X1M
X1A
X2A
OUTER SHELL
V
LAYOUT OF M1C, M1F
EL. COMPO. BOX
M1F
M1C
TERMINAL OF M1C
3D060907A
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR TRANSMISSION
F1 F2, REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
V1CP
S1PH
F2U Q1RP
F1U
MS
3~
M1F
MS
3~
X1A
Z5C
F1U R10
- X4A
X3A +
V1R
X2A
X1A
X5A
X20A
X28A
P1 N1
X61A Z2C
X6A
X4A
A1P
RED X1A
BLU
BLK
N3 Z4CBLK
RED
P3
A4P
X1A
PS
t
R1T
X11A
V1R
R95
K1R
V2R
X10A
K2M
F400U
K3R
X402A
X401A X403A
Z1F
C1
M1C
U V W
RED
WHT
BLK
Appendix
GRN
WHT
BLU
BLK
2.1
RED
WHT
BLK
L1 L2 L3 N
Si34-803
Wiring Diagrams for Reference
RXYQ5PAY1
RXYQ5PAYL
375
RED
WHT
BLU
X1M L1 L2 L3
+C1
U V W
Z1C
N=4
P2
L1R
WHT
Z1F
K1M
P1 +
K84R
R1
P3
N3
X4A
X6A
MS
3~
M1F
M1C
X1A
Z2C
X501A
R112
F1U
+
V2R
V1R
-
PS
X7A
MS
3~
U V W
BLU
K2M
A2P
L1A L2A L3A E1
GRN
X20A
X28A
X2A
R502
V3R
X502A
X504A
Z3C
N=3
t R1T
A1P
RED X1A
WHT
BLU
X4A
X3A
X2A
K3R
X66A
R3T
t
Y1S
X7A
K4R
K5R
Y4S
X15A
R2T R4T
t
t
Y3S
X9A
K11R
X30A
R5T R6T
t
t
E1HC
X11A
COOL
HEAT
S1S
FAN
outdoor (F1) (F2)
indoor (F1) (F2)
OUT-OUT
F1 F2
X21A
X32A
X31A
X18A
HAP
NOTE) 4.
X37A
ON DS1
OFF
1234
PS
X1M
IN-OUT
F1 F2
S2S
COOL HEAT
X1A X1M
COOL/HEAT SELECTOR
C
A
B
A3P
X29A
Y2S
X8A
K7R
S1NPH
S1NPL
Y1E
M
t R1T
K84R
L1R
M1C
M1F
PS
Q1RP
R1
R112
R502
R1T
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
S1NPL
S1PH
V1CP
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
V1R
V2R, V3R
X1A, X2A
X1M
X1M
X1M
Y1E
Y1S
Y2S
Y3S
Y4S
Z1C~3C
Z1F
L1R
(BACK)
A2P
A3P
A1P
X1M
(FRONT)
X1M
X1A
X2A
OUTER SHELL
V
LAYOUT OF M1C, M1F
EL. COMPO. BOX
M1F
M1C
TERMINAL OF M1C
3D060626B
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR
TRANSMISSION F1 F2, REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
V1CP
S1PH
P<
F2U Q1RP
F1U
L1-RED
L2-WHT
L3-BLU
PRINTED CIRCUIT BOARD (MAIN)
A1P
PRINTED CIRCUIT BOARD (INV)
A2P
PRINTED CIRCUIT BOARD (ABC I/P)
A3P
PUSH BUTTON SWITCH
BS1~5
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
C1
DIP SWITCH
DS1
CRANKCASE HEATER
E1HC
FUSE (16A, DC450V) (A2P)
F1U
F1U, F2U FUSE (T, 3.15A, 250V) (A1P)
H1P~8P PILOTLAMP (SERVICE MONITOR-ORANGE)
[H2P] PREPARE, TEST-------------------FLICKERING
MALFUNCTION DETECTION---LIGHT UP
PILOTLAMP (SERVICE MONITOR-GREEN)
HAP
K1M, K2M MAGNETIC CONTACTOR (M1C) (A2P)
MAGNETIC RELAY (Y1S)
K3R
MAGNETIC RELAY (Y2S)
K4R
MAGNETIC RELAY (Y3S)
K5R
MAGNETIC RELAY (E1HC)
K7R
MAGNETIC RELAY (Y4S)
K11R
POWER SUPPLY
220V 3~60Hz
RED
BLK BLK
RED
WHT
BLK
376
RED
WHT
BLK
L1 L2 L3
RXYQ5PTL
Appendix
X1M L1 L2 L3 N
RED
WHT
BLK
BLU
K4M
Z3C
N=5
P1
WHT
L1R
WHT
P2
A3P
R50 R59
+ +
C66 C63
X111A
X41A
X5A
P1 N1
X20A
X28A
MS
3~
M1F
MS
3~
X1A
Z5C
P<
V1CP
S1PH
F2U Q1RP
F1U
X4A
X3A
X2A
K3R
X66A
R3T
t
Y1S
X7A
K4R
E1HC
X11A
PS
FAN
S1S
COOL/HEAT SELECTOR
(OPTIONAL ACCESSORY)
S2S
COOL HEAT
COOL
HEAT
C/H SELECTOR
A
C
B
X30A
Y3S
X9A
K5R
X1A X1M
A5P
X29A
Y2S
X8A
K7R
NOTE) 5
X1M
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT X23A BLU
F1 F2 F1 F2 Q1 Q2
X21A
X32A
X31A
X18A
NOTE) 4
OFF 1234
HAP
X37A
ON DS1
WHT BLU
Y2E
M
Y1E
5 M
S1NPH
S1NPL
t R1T
L1R
A4P
(BACK)
A2P
A3P
A5P
A1P
X1M
(FRONT)
X1M
X1A
X2A
OUTER SHELL
V
LAYOUT OF M1C, M1F
EL. COMPO. BOX
M1F
M1C
TERMINAL OF M1C
K4M
K3R
K4R
K5R
K7R
L1R
M1C
M1F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH
V1CP
V1R
V2R
X1A, X2A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~5C
Z1F
3D060908A
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR TRANSMISSION
X2A
F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2 (ONLY FOR RXYQ), REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
F1U R10
X3A +
- X4A
V1R
X2A
X1A
X5A
Z4C
N3
BLK
RED
P3
A4P
X4A
X61A Z2C
X6A
X1A
A1P
RED X1A
BLU
BLK
M1C
U V W
X400A
X402A
X403A
PS
t
R1T
X11A
V1R
K1R
R95
V2R
X10A
K2M
F400U
K3R
X401A
Z1F
C1
A1P
A2P
A3P
A4P
A5P
BS1~5
Z1C
A2P
POWER SUPPLY
Y1 : 3N~380-415V 50Hz
YL : 3N~380V 60Hz
YC : 3N~380V 50Hz
RED
RED
WHT
BLK
RED
WHT
BLK
GRN
WHT
BLU
BLK
Appendix
RED
WHT
BLK
L1 L2 L3 N
Si34-803
Wiring Diagrams for Reference
RXYQ8PAY1
RXYQ8PAYL
377
RED
WHT
BLU
X1M L1 L2 L3
+C1
U V W
Z1C
N=4
P2
L1R
Z1F
K1M
P1 +
K84R
R1
X7A
P3
N3
X4A
X6A
X20A
X28A
X2A
R502
V3R
X502A
X504A
Z3C
N=3
t R1T
A1P
RED X1A
WHT
BLU
X4A
X3A
X2A
K3R
X66A
R3T
t
Y1S
X7A
K4R
E1HC
X11A
X30A
Y3S
X9A
K5R
COOL
HEAT
S1S
FAN
COOL/HEAT SELECTOR
(OPTIONAL ACCESSORY)
S2S
COOL HEAT
X1A X1M
COOL/HEAT SELECTOR
C
A
B
A3P
X29A
Y2S
X8A
K7R
HAP
NOTE) 5.
X1M
IN-OUT
F1 F2
X21A
WHT BLU
5
Y2E
M
Y1E
M
S1NPL
S1NPH
t R1T
X18A
* : * IS CONNECTOR COLOR FOR
X31A
PRINTED CIRCUIT BOARD.
* : * IS CONNECTOR COLOR FOR COMPONENT.
X32A
* : * IS DISCRIMINATION COLOR FOR
COMPONENT LEAD WIRE.
NOTE) 4.
X37A
ON DS1
OFF
1234
PS
L1R
(BACK)
A2P
A3P
A1P
X1M
(FRONT)
X1M
X1A
X2A
OUTER SHELL
V
LAYOUT OF M1C, M1F
EL. COMPO. BOX
M1F
M1C
TERMINAL OF M1C
L1R
M1C
M1F
PS
Q1RP
R1
R112
R502
R1T
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH
V1CP
REACTOR
MOTOR (COMPRESSOR)
MOTOR (FAN)
SWITCHING POWER SUPPLY (A1P,A2P)
PHASE REVERSAL DETECT CIRCUIT
RESISTOR (CURRENT LIMITING)
RESISTOR (CURRENT SENSOR) (A2P)
RESISTOR (CURRENT SENSOR) (A2P)
THERMISTOR (AIR) (A1P)
THERMISTOR (FIN) (A2P)
THERMISTOR (SUCTION)
THERMISTOR (M1C DISCHARGE)
THERMISTOR (HEAT EXC. DEICER)
THERMISTOR (HEAT EXC. OUTLET)
THERMISTOR (LIQ. PIPE)
THERMISTOR (ACCUMULATOR)
PRESSURE SENSOR (HIGH)
PRESSURE SENSOR (LOW)
PRESSURE SWITCH (HIGH)
SAFETY DEVICES INPUT
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
V1R
V2R, V3R
X1A, X2A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~3C
Z1F
3D060627B
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR
TRANSMISSION F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2, REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
V1CP
S1PH P<
F2U Q1RP
F1U
L1-RED
L2-WHT
L3-BLU
PRINTED CIRCUIT BOARD (MAIN)
A1P
PRINTED CIRCUIT BOARD (INV)
A2P
PRINTED CIRCUIT BOARD (ABC I/P)
A3P
PUSH BUTTON SWITCH
BS1~5
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
C1
DIP SWITCH
DS1
CRANKCASE HEATER
E1HC
FUSE (16A, DC450V) (A2P)
F1U
F1U, F2U FUSE (T, 3.15A, 250V) (A1P)
PILOTLAMP (SERVICE MONITOR-ORANGE)
H1P~8P
[H2P] PREPARE,TEST------------FLICKERING
MALFUNCTION DETECTION---LIGHT UP
PILOTLAMP (SERVICE MONITOR-GREEN)
HAP
K1M, K2M MAGNETIC CONTACTOR (M1C) (A2P)
MAGNETIC RELAY (Y1S)
K3R
MAGNETIC RELAY (Y2S)
K4R
MAGNETIC RELAY (Y3S)
K5R
MAGNETIC RELAY (E1HC)
K7R
MAGNETIC RELAY (CURRENT LIMITING)
K84R
MS
3~
M1F
MS
3~
X1A
Z2C
X501A
R112
F1U
+
V2R
V1R
-
PS
GRN
M1C
U V W
BLU
K2M
A2P
L1A L2A L3A E1
RED
BLK BLK
POWER SUPPLY
220V 3~60Hz
WHT
RED
WHT
BLK
378
RED
WHT
BLK
L1 L2 L3
RXYQ8PTL
Appendix
X1M L1 L2 L3 N
U V W
Z7C
N=5
K2M
R S T
Z6C
M2C
M
3~
U V W
X1A
T1A
A6P
RED
WHT
BLK
BLU
RED
WHT
BLK
K4M
R50 R59
+ +
C66 C63
X5A
X111A
X41A
P1 N1
X20A
X28A
X26A
F1U
P<
P<
K1R
X4A
X3A
X2A
A1 RED
V1CP
S2PH
S1PH
F2U Q1RP
K3R
Y2S
X8A
K4R
X66A
E1HC
X11A
K7R
E2HC
X12A
PS
NOTE) 4
OFF 1234
X18A
HAP
X37A
ON DS1
FAN
S1S
COOL/HEAT SELECTOR
(OPTIONAL ACCESSORY)
S2S
COOL HEAT
COOL
HEAT
C/H SELECTOR
A
B
C
X30A
NOTE) 5
X1M
TO IN/D UNIT TO OUT/D UNIT TO OUT/M UNIT X23A BLU
F1 F2 F1 F2 Q1 Q2
X21A
Y3S
X9A
K5R
X1A X1M
A5P
X29A
R31T R32T
t
t
Y1S
X7A
K8R
WHT BLU
Y2E
M
Y1E
5 M
S1NPH
S1NPL
t R1T
MS
3~
M1F
MS
3~
X1A
Z5C
5
X2A
A6P
K2M
L1R
A4P
(BACK)
A2P
A3P
K2M
K1R
K3R
K4R
K5R
K7R
K8R
L1R
M1C, M2C
M1F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R31T, R32T
R4T
R5T
R6T
R7T
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
S1NPH
S1NPL
S1PH, S2PH
T1A
V1CP
V1R
V2R
X1A, X2A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~7C
Z1F
A5P
A1P
X1M
(FRONT)
X1M
X1A
X2A
EL.COMPO.BOX
OUTER SHELL
V
LAYOUT OF M1C, M2C, M1F
EL. COMPO. BOX
M1F
M1C
M2C
3D060909A
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR TRANSMISSION
F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2 (ONLY FOR RXYQ), REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH, S2PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
F1U R10
NOTES)
X3A +
- X4A
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
V1R
2.
: FIELD WIRING.
X2A
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
X1A
X5A
Z4C
N3
BLK
RED
P3
A4P
X4A
X61A Z2C
X6A
X1A
PS
t
R1T
X11A
V1R
R95
K1R
V2R
X10A
K2M
X402A
X403A
X400A
M1C
U V W
Z3C
N=5
P1
WHT
L1R
WHT
P2
A3P
F400U
K3R
X401A
Z1F
C1
A1P
RED X1A
BLU
BLK
A1P
A2P
A3P
A4P
A5P
A6P
BS1~5
Z1C
A2P
POWER SUPPLY
Y1 : 3N~380-415V 50Hz
YL : 3N~380V 60Hz
YC : 3N~380V 50Hz
RED
RED
WHT
BLK
RED
WHT
BLK
GRN
WHT
BLU
BLK
Appendix
RED
WHT
BLK
L1 L2 L3 N
Si34-803
Wiring Diagrams for Reference
RXYQ10PAY1
RXYQ10PAYL
379
U V W
Z4C
N=4
K2M
R S T
M2C
M
3~
U V W
+C1
WHT
X7A
MS
3~
M1F
M1C
X1A
Z2C
X501A
R112
F1U
+
V2R
P3
N3
X4A
X6A
PS
V1R
-
K2M
BLU
MS
3~
U V W
U V W
Z1C
N=4
P2
L1R
Z1F
K1M
P1 +
K84R
R1
A2P
L1A L2A L3A E1
GRN
A1P
X28A
X20A
X2A
R502
V3R
X502A
X504A
Z3C
N=3
t R1T
X26A
RED X1A
WHT
BLU
K3R
Y1S
X7A
Y2S
X8A
K4R
X5A
X66A
K5R
E1HC
X11A
E2HC
X12A
1
X30A
Y3S
X9A
K7R
COOL
HEAT
S1S
FAN
NOTE) 5.
X1M
IN-OUT
F1 F2
X21A
X32A
X31A
X18A
HAP
NOTE) 4.
X37A
ON DS1
OFF
1234
PS
S2S
COOL HEAT
X1A X1M
COOL/HEAT SELECTOR
C
A
B
A3P
X29A
X3A
X2A
K8R
WHT BLU
S1NPH
S1NPL
Y2E
M
Y1E
M
t R1T
A4P A3P
K2M
A1P
X1M
K8R
K84R
L1R
M1C, M2C
M1F
PS
Q1RP
R1
R112
R502
R1T
R1T
R2T
R31T, R32T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH, S2PH
T1A
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
V1CP
V1R
V2R, V3R
X1A, X2A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~4C
Z1F
L1R
(BACK)
A2P
(FRONT)
X1M
X1A
X2A
OUTER SHELL
TERMINAL OF M1C
W
U
V
LAYOUT OF M1C, M1F
EL. COMPO. BOX
M1F
M1C
M2C
3D060629B
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR
TRANSMISSION F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2, REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
K2M WHT
A2
A1RED K1R
V1CP
S2PH P<
S1PH P<
F2U Q1RP
F1U
L1-RED
L2-WHT
L3-BLU
PRINTED CIRCUIT BOARD (MAIN)
A1P
PRINTED CIRCUIT BOARD (INV)
A2P
PRINTED CIRCUIT BOARD (ABC I/P)
A3P
PRINTED CIRCUIT BOARD (CURRENT SENSOR)
A4P
PUSH BUTTON SWITCH
BS1~5
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
C1
DIP SWITCH
DS1
E1HC, E2HC CRANKCASE HEATER
FUSE (16A, DC450V) (A2P)
F1U
FUSE (T, 3.15A, 250V) (A1P)
F1U, F2U
PILOTLAMP (SERVICE MONITOR-ORANGE)
H1P~8P
[H2P] PREPARE,TEST------------FLICKERING
MALFUNCTION DETECTION---LIGHT UP
PILOTLAMP (SERVICE MONITOR-GREEN)
HAP
MAGNETIC CONTACTOR (M1C) (A2P)
K1M, K2M
MAGNETIC CONTACTOR (M2C)
K2M
MAGNETIC RELAY (K2M)
K1R
MAGNETIC RELAY (Y1S)
K3R
MAGNETIC RELAY (Y2S)
K4R
MAGNETIC RELAY (Y3S)
K5R
MAGNETIC RELAY (E1HC)
K7R
POWER SUPPLY
220V 3~60Hz
X1A
T1A
A4P
X1M L1 L2 L3
RED
WHT
BLU
RED
WHT
BLK
RED
BLK BLK
RED
WHT
BLK
380
RED
WHT
BLK
L1 L2 L3
RXYQ10PTL
Appendix
X1M L1 L2 L3 N
U V W
Z7C
N=5
K2M
R S T
Z6C
M2C
M
3~
U V W
X1A
T1A
A6P
RED
WHT
BLK
BLU
RED
WHT
BLK
Z1C
A2P
K4M
RED
R50 R59
+ +
C66 C63
X400A
X111A
M1F
M1C
A1 RED
A1P
A2P
A3P
A4P, A8P
A5P
A6P
BS1~5
K3R
Y1S
X7A
Y2S
X8A
K4R
N1
X66A
E1HC
X11A
K7R
E2HC
X12A
S2S
COOL HEAT
COOL
HEAT
FAN
S1S
C/H SELECTOR
A
B
C
X30A
Y3S
X9A
K5R
X1A X1M
A5P
X29A
X3A
X2A
K8R
X18A
NOTE) 5
X1M
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT X23A BLU
F1 F2 F1 F2 Q1 Q2
X21A
NOTE) 4
OFF 1234
HAP
X37A
ON DS1
WHT BLU
S1NPH
S1NPL
Y2E
M
Y1E
M
t R1T
RED
Z9C
K2M
K1R
K3R
K4R
K5R
K7R
K8R
L1R
M1C, M2C
M1F, M2F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R31T, R32T
R4T
R5T
R6T
R7T
M2F
RED MS
3~
WHT
A6P
K2M
L1R
A8P
A4P
RED
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
S1NPH
S1NPL
S1PH, S2PH
T1A
V1CP
V1R
V2R
X1A~4A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~7C, Z9C
Z1F
3D060910A
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR TRANSMISSION
X4A
F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2, REFER TO THE INSTALLATION MANUAL.
WHT
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH, S2PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
(BACK)
A2P
A3P
A5P
A1P
X1M
(FRONT)
X1M
X1A X3A
X2A X4A
OUTER SHELL
V
LAYOUT OF M1C, M2C, M1F, M2F
EL. COMPO. BOX
M2F M1F M1C
M2C
A8P
P1
X5A
BLK
RED
K2M WHT
A2
X2A X3A
N2
X51A
R10
- X4A
V1R
X2A
X20A
P<
P<
V1CP
S2PH
S1PH
F2U Q1RP
F1U
MS
3~
X1A
Z5C
X1A
Z4C
N3
BLK
RED
P3
A4P
P1 P2 N1
X5A
X5A
F1U
X3A +
X41A
X4A
X28A
X26A
A1P
RED X1A
BLU
BLK
X61A Z2C
X6A
X1A
X402A
X403A
PS
t
R1T
X11A
V1R
K1R
R95
V2R
X10A
K2M
F400U
K3R
X401A
Z1F
C1
MS
3~
U V W
Z3C
N=5
P1
WHT
L1R
WHT
P2
A3P
RED
WHT
BLK
RED
WHT
BLK
GRN
WHT
BLU
BLK
POWER SUPPLY
Y1 : 3N~380-415V 50Hz
YL : 3N~380V 60Hz
YC : 3N~380V 50Hz
RED
WHT
BLK
Appendix
RED
WHT
BLK
L1 L2 L3 N
Si34-803
Wiring Diagrams for Reference
RXYQ12PAY1
RXYQ12PAYL
381
U V W
R S T
Z4C
N=4
K2M
M2C
M
3~
U V W
X1A
T1A
A4P
X1M L1 L2 L3
K1M
U V W
Z1C
N=4
P2 + C1
L1R
P1 +
K84R
R1
Z1F
X7A
P3
M1F
M1C
5
RED
Z6C
X1A
X5A +
M2F
RED MS
3~
WHT
X2A X3A
R502
- X5A
V3R
X502A
X504A
RED
Y1S
Y2S
X8A
X66A
E1HC
E2HC
X12A
X30A
Y3S
X11A
K7R
COOL
HEAT
S1S
FAN
X1M
IN-OUT
F1 F2
X21A
X32A
X31A
NOTE) 5.
X18A
HAP
NOTE) 4.
X37A
ON DS1
OFF
1234
PS
S2S
COOL HEAT
X1A X1M
COOL/HEAT SELECTOR
A
C
B
A3P
X29A
K5R
X9A
K8R
WHT BLU
S1NPH
S1NPL
Y2E
M
Y1E
M
t R1T
A4P
K2M
A5P
L1R
(BACK)
A2P
A3P
A1P
X1M
(FRONT)
X1M
X1A X3A
X2A X4A
EL.COMPO.BOX
OUTER SHELL
V
LAYOUT OF M1C, M1F
EL. COMPO. BOX
M2F M1F M1C
M2C
TERMINAL OF M1C
W
U
K8R
K84R
L1R
M1C, M2C
M1F, M2F
PS
Q1RP
R1
R2
R112
R502
R1T
R1T
R2T
R31T, R32T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH, S2PH
T1A
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
V1CP
V1R
V1R
V2R, V3R
X1A~4A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~6C
Z1F
3D060630B
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
RED
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR
X4A
TRANSMISSION F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2, REFER TO THE INSTALLATION MANUAL.
WHT
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
NOTES)
R2
- X4A
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
V1R
2.
: FIELD WIRING.
X2A
A5P
N1
P1
X3A F1U
X20A
X28A
K3R
X7A
K4R
X3A
X2A
A1RED K1R
V1CP
S2PH P<
S1PH P<
F2U Q1RP
F1U
L2-WHT
L1-RED
L3-BLU
PRINTED CIRCUIT BOARD (MAIN)
A1P
PRINTED CIRCUIT BOARD (INV)
A2P
PRINTED CIRCUIT BOARD (ABC I/P)
A3P
PRINTED CIRCUIT BOARD (CURRENT SENSOR)
A4P
PRINTED CIRCUIT BOARD (INV)
A5P
PUSH BUTTON SWITCH
BS1~5
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
C1
DIP SWITCH
DS1
E1HC, E2HC CRANKCASE HEATER
FUSE (16A, DC450V) (A2P, A5P)
F1U
FUSE (T, 3.15A, 250V) (A1P)
F1U, F2U
PILOTLAMP (SERVICE MONITOR-ORANGE)
H1P~8P
[H2P] PREPARE, TEST------------------FLICKERING
MALFUNCTION DETECTION---LIGHT UP
PILOTLAMP (SERVICE MONITOR-GREEN)
HAP
MAGNETIC CONTACTOR (M1C) (A2P)
K1M, K2M
MAGNETIC CONTACTOR (M2C)
K2M
MAGNETIC RELAY (K2M)
K1R
MAGNETIC RELAY (Y1S)
K3R
MAGNETIC RELAY (Y2S)
K4R
MAGNETIC RELAY (Y3S)
K5R
MAGNETIC RELAY (E1HC)
K7R
MS
3~
X1A
X501A
Z2C
Z3C
N=3
t R1T
X26A
A1P
RED X1A
WHT
BLU
Z5C
N3 N=2 BLU
X4A
X6A
R112
F1U
+
V2R
V1R
-
PS
GRN
MS
3~
U V W
BLU
K2M
A2P
L1A L2A L3A E1
RED
BLK BLK
RED
WHT
BLU
RED
WHT
BLK
WHT
RED
WHT
BLK
POWER SUPPLY
220V 3~60Hz
RED
WHT
BLK
382
RED
WHT
BLK
L1 L2 L3
RXYQ12PTL
Appendix
A3P
X10A
K2M
Z3C
N=5
HAP
K1R
K3R
K2M
K4M
R50 R59
V1R
X111A
X4A
X61A Z2C
X6A
N1
K3R
K4R
Y2S
X8A
K5R
Y3S
X9A
K7R
E1HC
X11A
E2HC
X12A
K8R
E3HC
X13A
X18A
PS
X66A
1
1
COOL HEAT
S2S
X30A
COOL
HEAT
C/H SELECTOR
A
B
C
X1A X1M
A5P
X29A
FAN
S1S
outdoor (Q1) (Q2)
outdoor (F1) (F2)
indoor (F1) (F2)
NOTE) 5
X1M
TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT X23A BLU
F1 F2 F1 F2 Q1 Q2
X21A
Y1S
X7A
K9R
WHT BLU
S1NPH
S1NPL
Y2E
M
Y1E
M
t R1T
RED
Z9C
M2F
RED MS
3~
WHT
5
WHT
A8P
A4P
L1R
(BACK)
A2P
A3P
THERMISTOR (ACCUMULATOR)
PRESSURE SENSOR (HIGH)
PRESSURE SENSOR (LOW)
PRESSURE SWITCH (HIGH)
CURRENT SENSOR (A6P, A7P)
SAFETY DEVICES INPUT
POWER MODULE (A3P, A4P, A8P)
DIODE BRIDGE (A3P)
CONNECTOR (M1F, M2F)
TERMINAL STRIP (POWER SUPPLY)
TERMINAL STRIP (CONTROL) (A1P)
TERMINAL STRIP (ABC I/P) (A5P)
ELECTRONIC EXPANSION VALVE (MAIN)
ELECTRONIC EXPANSION VALVE (SUBCOOL)
SOLENOID VALVE (HOT GAS)
SOLENOID VALVE (OIL)
SOLENOID VALVE (4 WAY VALVE)
NOISE FILTER (FERRITE CORE)
NOISE FILTER (WITH SURGE ABSORBER)
COOL/HEAT SELECTOR
SELECTOR SWITCH (FAN/COOL HEAT)
S1S
SELECTOR SWITCH (COOL/HEAT)
S2S
R7T
S1NPH
S1NPL
S1PH~3PH
T1A
V1CP
V1R
V2R
X1A~4A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~9C
Z1F
3D060911A
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR
TRANSMISSION F1 F2 OUTDOOR-MULI TRANSMISSION Q1 Q2, REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH~S3PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
X4A
RED
X1M
A1P
(FRONT)
X1M
X1A X3A
X2A X4A
OUTER SHELL
COOL/HEAT SELECTOR
NOTES) (OPTIONAL ACCESSORY)
F1U R10
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
- X4A
X3A +
V1R
2.
: FIELD WIRING.
X2A
3.
: TERMINAL STRIP
: CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
X1A
X5A
A8P
K2R
X6A
P1
WHT
A2
K3M
A2
A1RED
WHT
X2A X3A
N2
X51A
R10
- X4A
V1R
X2A
V1CP
X4A
X3A
X2A
A1RED K1R
K2M
X5A
BLK
RED
X20A
X28A
X25A
X26A
P<
<
S3PH P
S2PH
<
S1PH P
F2U Q1RP
F1U
M1F
M1C
X1A
Z5C
X1A
MS
3~
t
R1T
X11A
PS
X1A
X402A
X403A
X400A
RED X1A
BLU
BLK
A1P
MS
3~
U V W
A1P
A2P
A3P
A4P, A8P
A5P
A6P, A7P
BS1~5
C1
C63, C66
DS1
E1HC~3HC
F1U
F1U, F2U
F400U
H1P~8P
U V W
M
3~
M3C
RED
WHT
BLK
C1
N3 Z4CBLK
RED
P3
A4P
P1 P2 N1
X5A
X5A
F1U
X3A +
X41A
F400U
K3R
X401A
Z1F
V2R
+
P1
R S T WHT
K1R
L1R
K3M
R95
U V W WHT
P2
Z8C
C66 C63
N=5
+ +
X1A
T1A
A7P
RED
WHT
BLK
U V W
M
3~
M2C
K2M
U V W
Z7C
N=5
R S T
X1A
T1A
A6P
RED
WHT
BLK
BLU
Z6C
K4M
RED
WHT
BLK
X1M L1 L2 L3 N
Z1C
A2P
RED
RED
WHT
BLK
GRN
WHT
BLU
BLK
POWER SUPPLY
Y1 : 3N~380-415V 50Hz
YL : 3N~380V 60Hz
YC : 3N~380V 50Hz
RED
WHT
BLK
Appendix
RED
WHT
BLK
L1 L2 L3 N
Si34-803
Wiring Diagrams for Reference
383
RED
V W
Z7C
N=4
K3M
U
A6P
A4P
V W
U V W
M
3~
M3C
Z1F
K1M
U
Z1C
N=4
P2
L1R
P1
K84R
R1
V W
+ C1
V1R
F1U
A1P
Z3C
N=3
t R1T
P3
X2A
K8R
K9R
K84R
L1R
M1C~3C
M1F,M2F
PS
Q1RP
R1
R2
R112
R502
R1T
R1T
R2T
R31T~33T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH~3PH
M1F
V3R
X502A
WHT
MS
3~
M2F
WHT
X4A
X3A
X2A
Y2S
Y3S
X9A
X66A
R4T
E1HC
X30A
R5T
E2HC
X12A
R6T
S2S
COOL
HEAT
COOL
HEAT
S1S
FAN
R7T
E3HC
X13A
X1A X1M
COOL/HEAT SELECTOR
A
B
C
A3P
K7R
X11A
K8R
*
*
1234
NOTE) 4.
X18A
HAP
NOTE) 5.
X21A
OFF
X37A
ON DS1
PS
X1M
IN-OUT
F1
F2
X29A
Y1S
X8A
X7A
K9R
WHT BLU
S1NPH
S1NPL
t R1T
Y2E
M
Y1E
M
OUTER SHELL
EL.COMPO.BOX
M1C
M2C
M3C
K2M K3M
A1P
X1M
(BACK)
A5P
L1R
(FRONT)
A2P
X1M
X1A X3A
X2A X4A
EL.COMPO.BOX
M2F M1F
TERMINAL OF M1C
COOL/HEAT SELECTOR
S1S
SELECTOR SWITCH (FAN/COOL HEAT)
S2S
SELECTOR SWITCH (COOL/HEAT)
T1A
V1CP
V1R
V1R
V2R,V3R
X1A~4A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~7C
Z1F
3D060632B
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2.
: FIELD WIRING.
3.
: TERMINAL STRIP
: CONNECTOR
: TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 F2, OUTDOOR-OUTDOOR TRANSMISSION
RED
F1 F2, OUTDOOR-MULTI TRANSMISSION Q1 Q2, REFER TO THE INSTALLATION MANUAL.
X4A
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
WHT
7. WHEN OPERATING, DON'T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN GRY : GRAY
GRN : GREEN ORG : ORANGE.
X6A
K2R
X5A
R2
X4A
V1R
X2A
N1
A2
K3M
A1 RED
A2
K2M
A1 RED K1R
F1U
+
P<
P<
P<
V1CP
S3PH
S2PH
S1PH
F2U Q1RP
F1U
K5R
RED
WHT
X3A
RED
Z6C
X1A
X3A
X5A
X504A
A5P
P1
R502
X5A
-
RED
X20A
X28A
X25A
X26A
RED X1A
WHT
BLU
Z5C
N3 N=2 BLU
M1C
X1A
Z2C
X501A
V2R
X6A
X4A
MS
3~
R112
K2M
PS
X7A
MS
3~
U V W
BLU
E1
GRN
L1-RED
L2-WHT
L3-BLU
PRINTED CIRCUIT BOARD (MAIN)
A1P
A2P
PRINTED CIRCUIT BOARD (INV)
A3P
PRINTED CIRCUIT BOARD (ABC I/P)
A4P, A6P PRINTED CIRCUIT BOARD (CURRENT SENSOR)
A5P
PRINTED CIRCUIT BOARD (INV)
BS1~5 PUSH BUTTON SWITCH
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
C1
DIP SWITCH
DS1
E1HC~3HC CRANKCASE HEATER
FUSE (16A, DC450V) (A2P, A5P)
F1U
F1U,F2U FUSE (T, 3.15A, 250V) (A1P)
H1P~8P PILOTLAMP (SERVICE MONITOR-ORANGE)
[H2P] PREPARE, TEST ------------------- FLICKERING
MALFUNCTION DETECTION --- LIGHT UP
PILOTLAMP (SERVICE MONITOR-GREEN)
HAP
K1M,K2M MAGNETIC CONTACTOR (M1C) (A2P)
K2M,K3M MAGNETIC CONTACTOR (M2C, M3C)
K1R,K2R MAGNETIC RELAY (K2M, K3M)
MAGNETIC RELAY (Y1S)
K3R
K4R
MAGNETIC RELAY (Y2S)
K5R
MAGNETIC RELAY (Y3S)
K7R
MAGNETIC RELAY (E1HC)
V W
M
3~
M2C
RED
Z4C
N=4
K2M
U
WHT
WHT
X1A
T1A
RED
BLU
BLK
X1A
T1A
RED
WHT
A2P
L1A L2A L3A
WHT
BLK
RED
BLK BLK
WHT
BLK
X1M L1 L2 L3
RED
WHT
BLK
POWER SUPPLY
220V 3~60Hz
RED
WHT
BLK
K3R
384
K4R
L1 L2 L3
Appendix
Appendix
MAIN
SWITCH
L1 L2 L3 N
FUSE
2 WIRES CABLE
(POWER LINE)
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
FUSE
SWITCH
2 WIRES CABLE
(POWER LINE)
POWER SUPPLY
LN
MAIN SWITCH
SWITCH
INDOOR UNITS
FUSE
2 WIRES CABLE
(POWER LINE)
L
FUSE
SWITCH
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
FUSE
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(POWER LINE)
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
OUTDOOR UNITS
3D051452F
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10) If there exists the possibility of reversed phase, lose phase, momentary blackout or the
power goes on and off while the product is operating, attach a reversed phase protection
circuit locally.
Running the product in reversed phase may break the compressor and other parts.
2.2
POWER SUPPLY
L1 L2 L3 N
Notes 1) All wiring, components and materials to be procured on the site must comply with the
applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
Si34-803
Wiring Diagrams for Reference
Field Wiring
385
386
MAIN
SWITCH
L1 L2 L3
FUSE
2 WIRES CABLE
(POWER LINE)
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
FUSE
SWITCH
2 WIRES CABLE
(POWER LINE)
POWER SUPPLY
LN
MAIN SWITCH
POWER SUPPLY
L1 L2 L3
FUSE
2 WIRES CABLE
(POWER LINE)
SWITCH
SWITCH
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
FUSE
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
FUSE
2 WIRES CABLE
(POWER LINE)
INDOOR UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
OUTDOOR UNITS
3D060852
Notes 1) All wiring, components and materials to be procured on the site must comply with the
applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner
because this system consists of the equipment utilizing the multiple power sources.
10) If there exists the possibility of reversed phase, lose phase, momentary blackout or the
power goes on and off while the product is operating, attach a reversed phase protection
circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Appendix
Appendix
FUSE
2 WIRES CABLE
(POWER LINE)
SWITCH
FUSE
L
SWITCH
2 WIRES CABLE
(POWER LINE)
INDOOR UNITS
2 WIRES CABLE
(POWER LINE)
L
SWITCH
2 WIRES CABLE
(POWER LINE)
N
FUSE
L
SWITCH
SWITCH
L1 L2 L3 N
POWER SUPPLY
L1L2L3 N
MAIN
SWITCH
2 WIRES CABLE
(POWER LINE)
FUSE
SWITCH
SWITCH
INDOOR UNITS
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
FUSE
SWITCH
FUSE
FUSE
SWITCH
2 WIRES CABLE
(POWER LINE)
3D052261D
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
OUTDOOR UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
[UNIT 1]
[UNIT 2]
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
10) The capacity of UNIT1 must be larger than UNIT2 when the power source is connected in
series between the units.
11) If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
FUSE
POWER SUPPLY
LN
MAIN
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
(TRANSMISSION LINE)
(POWER LINE)
FUSE
[UNIT 1]
2 WIRES CABLE
(TRANSMISSION LINE)
L1 L2 L3 N
2 WIRES CABLE
(TRANSMISSION LINE)
[UNIT 2]
OUTDOOR UNITS
SWITCH
FUSE
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(POWER LINE)
POWER SUPPLY
LN
MAIN
SWITCH
FUSE
SWITCH
L1 L2 L3 N
POWER SUPPLY
L1L2L3 N
MAIN
SWITCH
Notes 1) All wiring, components and materials to be procured on the site must comply with the
applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
Si34-803
Wiring Diagrams for Reference
387
388
L1 L2 L3
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
L
SWITCH
FUSE
L
SWITCH
FUSE
INDOOR UNITS
SWITCH
FUSE
L1 L2 L3
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
N
N
L
SWITCH
FUSE
2 WIRES CABLE 2 WIRES CABLE
(POWER LINE) (POWER LINE)
L
SWITCH
FUSE
L
SWITCH
FUSE
INDOOR UNITS
2 WIRES CABLE
(POWER LINE)
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
3D060853
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
OUTDOOR UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
[UNIT 1]
[UNIT 2]
POWER SUPPLY
LN
MAIN
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE)
(TRANSMISSION LINE) (TRANSMISSION LINE) (TRANSMISSION LINE) (POWER LINE)
L1 L2 L3
POWER SUPPLY
L1L2 L3
MAIN
SWITCH
7) Wiring shown are general points-of-connection guides only and are not intended for or to include all
details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
10) The capacity of UNIT1 must be larger than UNIT2 when the power source is connected in series
between the units.
11) If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes
on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
OUTDOOR UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
[UNIT 1]
[UNIT 2]
SWITCH
FUSE
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(POWER LINE)
POWER SUPPLY
LN
MAIN
SWITCH
SWITCH
FUSE
POWER SUPPLY
L1L2 L3
MAIN
SWITCH
Notes 1) All wiring, components and materials to be procured on the site must comply with
the applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
Appendix
Appendix
L1 L2 L3 N
SWITCH
FUSE
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
SWITCH
FUSE
L1 L2 L3 N
[UNIT 1]
L
SWITCH
FUSE
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
L
SWITCH
FUSE
L
SWITCH
FUSE
L
SWITCH
FUSE
INDOOR UNITS
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
L
SWITCH
FUSE
POWER SUPPLY
LN
MAIN
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
(TRANSMISSION LINE)
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
INDOOR UNITS
L
SWITCH
FUSE
2 WIRES CABLE
(TRANSMISSION LINE)
L1 L2 L3 N
2 WIRES CABLE
(POWER LINE)
SWITCH
FUSE
[UNIT 1]
OUTDOOR UNITS
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
[UNIT 2]
[UNIT 3]
3D052262D
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
10) The capacity of UNIT1 must be larger than UNIT2 when the power source is connected in
series between the units.
11) If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit
locally.
Running the product in reversed phase may break the compressor and other parts.
POWER SUPPLY
L1L2 L3N
MAIN
OUTDOOR UNITS
2 WIRES CABLE
2 WIRES CABLE SWITCH
(TRANSMISSION LINE) (TRANSMISSION LINE)
[UNIT 2]
[UNIT 3]
L1 L2 L3 N
2 WIRES CABLE
(TRANSMISSION LINE)
POWER SUPPLY
LN
MAIN
SWITCH
SWITCH
FUSE
POWER SUPPLY
L1L2 L3N
MAIN
SWITCH
Notes 1) All wiring, components and materials to be procured on the site must comply with
the applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
Si34-803
Wiring Diagrams for Reference
RXYQ34PA / 36PA / 38PA / 40PA / 42PA / 44PA / 46PA / 48PA / 50PA / 52PA / 54PAY1
RXYQ34PA / 36PA / 38PA / 40PA / 42PA / 44PA / 46PA / 48PA / 50PA / 52PA / 54PAYL
389
390
L1 L2 L3
SWITCH
FUSE
L1 L2 L3
L
2 WIRES CABLE
SWITCH
(POWER LINE)
FUSE
2 WIRES CABLE
(POWER LINE)
L1 L2 L3
SWITCH
FUSE
L1 L2 L3
[UNIT 1]
L
SWITCH
FUSE
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
L
SWITCH
FUSE
L
SWITCH
FUSE
INDOOR UNITS
L
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
L
SWITCH
FUSE
POWER SUPPLY
LN
MAIN
SWITCH
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
(TRANSMISSION LINE)
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
INDOOR UNITS
L
SWITCH
FUSE
2 WIRES CABLE
(TRANSMISSION LINE)
SWITCH
FUSE
[UNIT 1]
OUTDOOR UNITS
2 WIRES CABLE
2 WIRES CABLE
(TRANSMISSION LINE) (TRANSMISSION LINE)
[UNIT 2]
[UNIT 3]
3D060854
7) Wiring shown are general points-of-connection guides only and are not intended for or to include all
details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner because this
system consists of the equipment utilizing the multiple power sources.
10) The capacity of UNIT1 must be larger than UNIT2 when the power source is connected in series
between the units.
11) If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes
on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
POWER SUPPLY
L1L2 L3
MAIN
OUTDOOR UNITS
2 WIRES CABLE
2 WIRES CABLE SWITCH
(TRANSMISSION LINE) (TRANSMISSION LINE)
[UNIT 2]
[UNIT 3]
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
POWER SUPPLY
LN
MAIN
SWITCH
SWITCH
FUSE
POWER SUPPLY
L1L2 L3
MAIN
SWITCH
Notes 1) All wiring, components and materials to be procured on the site must comply with
the applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
RXYQ34P / 36P / 38P / 40P / 42P / 44P / 46P / 48P / 50P / 52P / 54PTL
Appendix
X33A
A1P
X2M
A2P
CN1
KPR
R1T
X16A
X27A
F1U
X25A
Y1E
X7A
YLW
YLW
Z1F
C1
+
PS
X18A
MS
3~
100, 125-CLASS
M1F
Z1C
X20A
V1R +
M1P
M
~
K1R
R4T
N=1
X35A
NOTE) 3
HAP
X17A
R3T
M1S
MSW
X36A
X33A
NOTE) 3
X30A
X24A
NOTE) 3
X15A
S1L
BLK
BLU
ORG
YLW
WHT
PNK
X2A
A3P
X1A
X1A
A4P
H1P
H2P BS1
H3P
H4P
H5P
H6P
P1
X1M
P2
F1
MS
3~
25~80-CLASS
M1F
WHT
Z1C
N=1
TRANSMISSION WIRING
CENTRAL REMOTE CONTROLLER
NOTE) 2
P2
WIRED REMOTE
P1 R1T
CONTROLLER
SS1
F2
X20A
INPUT FROM
NOTE) 4
OUTSIDE
T1
T2
RECEIVER/DISPLAY UNIT
SS2
SS1
3D059890
: TERMINAL
,
: CONNECTOR
4. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR
: FIELD WIRING
ON/OFF CONTROL OPERATION CAN BE SELECTED BY THE REMOTE
2. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO
CONTROLLER. SEE INSTALLATION MANUAL FOR MORE DETAILS.
THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION
5. CONFIRM THE METHOD OF SETTING THE SELECTOR SWITCH (SS1, SS2) BY
MANUAL.
INSTALLATION MANUAL AND ENGINEERING DATA, ETC.
3. X24A, X33A AND X35A ARE CONNECTED WHEN THE OPTIONAL
6. SYMBOLS SHOWS AS FOLLOWS:
ACCESSORIES ARE BEING USED.
RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW GRN : GREEN
ORG : ORANGE BRN : BROWN PNK : PINK GRY : GRAY BLU : BLUE
CONTROL BOX
X35A
A2P
WHT
GRN/YLW
RED
X2M
WHT
ORG
BRN
BLU
POWER SUPPLY
~220-240V ~220V
50Hz
60Hz
A1P
R2T
RED
GRN
WHT
ORG
BRN
BLU
Appendix
RED
2.3
NOTES)
1.
INDOOR UNIT
H1P LIGHT EMITTING DIODE
(ON-RED)
A1P PRINTED CIRCUIT BOARD
A2P PRINTED CIRCUIT BOARD H2P LIGHT EMITTING DIODE
C1 CAPACITOR
(TIMER-GREEN)
F1U FUSE (F, 5A, 250V) H3P LIGHT EMITTING DIODE
(FILTER SIGN-RED)
HAP LIGHT EMITTING DIODE
(SERVICE MONITOR GREEN) H4P LIGHT EMITTING DIODE
(DEFROST-ORANGE)
K1R MAGNETIC RELAY
KPR MAGNETIC RELAY (M1P) SS1 SELECTOR SWITCH
(MAIN/SUB)
M1F MOTOR (INDOOR FAN)
M1P MOTOR (DRAIN PUMP) SS2 SELECTOR SWITCH
(WIRELESS ADDRESS SET)
M1S MOTOR (SWING FLAP)
R1T THERMISTOR (AIR) CONNECTOR FOR OPTIONAL PARTS
R2T THERMISTOR (COIL LIQUID) X24A CONNECTOR (WIRELESS
REMOTE CONTROLLER)
R3T THERMISTOR (COIL GAS)
R4T THERMISTOR PTC X33A CONNECTOR
(ADAPTOR FOR WIRING)
S1L FLOAT SWITCH
V1R DIODE BRIDGE
X35A CONNECTOR (GROUP
CONTROL ADAPTOR)
X1M TERMINAL STRIP
WIRED REMOTE CONTROLLER
X2M TERMINAL STRIP
R1T THERMISTOR (AIR)
Y1E ELECTRONIC
EXPANSION VALVE SS1 SELECTOR SWITCH (MAIN/SUB)
Z1C FERRITE CORE
Z1F NOISE FILTER
PS POWER SUPPLY CIRCUIT
RECEIVER/DISPLAY UNIT
(ATTACHED TO WIRELESS
X24A
REMOTE CONTROLLER)
A3P PRINTED CIRCUIT BOARD
X1M
A4P PRINTED CIRCUIT BOARD
BS1 PUSH BUTTON (ON/OFF)
Si34-803
Wiring Diagrams for Reference
Indoor Unit
391
Si34-803
3D039556A
392
Appendix
Si34-803
3D039557A
Appendix
393
Si34-803
3D039564C
394
Appendix
TRANSFORMER (220V/22V)
TERMINAL BLOCK
TERMINAL BLOCK
T1R
V1TR
X1M
X2M
Y1E
SS1
: CONNECTOR
: TERMINAL
Z2C
Z1C
X2M
X16A
CONTROL BOX
T1R
C1
A1P
X18A
~220-240V~220V
50Hz
60Hz
POWER
SUPPLY
Y1E
GRN
/YLW
BLU
RED
S1L
X2M
X8A
X7A
X31A
F1U
X13A
R1T
X25A
KPR
X1A
X12A
R2T
M
~
M1P
T1R
X11A
R3T
HAP
X3A
X4A
X27A
X18A
X30A
V1TR
X16A
A1P
BLK
RED
GRY
PRP
BLU
Z2C
N=3
Z1C
N=3
C1
X1M
PNK T2
WHT T1
YLW F2
ORG F1
BLU P2
BLK P1
M1F
M
~
Q1M
3D060547
NOTE) 5
INPUT FROM
OUTSIDE
TRANSMISSION
WIRING CENTRAL
REMOTE CONTROLLER
NOTE) 3
P2 R1T
P1
SS1
WIRED REMOTE
CONTROLLER
2.
: FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN
NOTES)
1.
X18A
X1M
X16A
THERMISTOR (AIR)
R1T
THERMISTOR (COIL-2)
FLOAT SWITCH
S1L
THERMISTOR (COIL-1)
R2T
R3T
THERMISTOR (AIR)
R1T
M1F
KPR
HAP
Q1M
FUSE (F5A/250V)
F1U
M1P
CAPACITOR (M1F)
C1
YLW
Appendix
WHT
A1P
Si34-803
Wiring Diagrams for Reference
395
CAPACITOR (M1F)
FUSE (F5A/250V)
THERMISTOR (AIR)
THERMISTOR (COIL-1)
THERMISTOR (COIL-2)
TRANSFORMER (220V/22V)
TERMINAL BLOCK
TERMINAL BLOCK
F1U
HAP
M1F
Q1M
R1T
R2T
R3T
T1R
V1TR
X1M
X2M
Y1E
SS1
: CONNECTOR
: TERMINAL
Z2C
Z1C
X2M
X16A
CONTROL BOX
T1R
C1
A1P
X18A
~220-240V~220V
50Hz
60Hz
POWER
SUPPLY
Y1E
X2M
GRN
/YLW
BLU
RED
X7A
X31A
F1U
X13A
R1T
X1A
X12A
R2T
T1R
t
X11A
R3T
X3A
HAP
X4A
X27A
X18A
X30A
V1TR
X16A
A1P
BLK
RED
GRY
PRP
BLU
Z2C
N=3
Z1C
N=3
C1
X1M
PNK T2
WHT T1
YLW F2
ORG F1
BLU P2
BLK P1
M1F
M
~
Q1M
3D060548
NOTE) 5
INPUT FROM
OUTSIDE
TRANSMISSION
WIRING CENTRAL
REMOTE CONTROLLER
NOTE) 3
P2 R1T
P1
SS1
WIRED REMOTE
CONTROLLER
2.
: FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN
NOTES)
1.
X18A
X1M
X16A
THERMISTOR (AIR)
R1T
YLW
C1
WHT
396
A1P
Appendix
Appendix
INDOOR UNIT
POWER SUPPLY
NOTE-6
COMPRESSOR ADAPTOR FOR WIRING
PRINTED CIRCUIT BOARD
220-240V 220V
OPERATION (OPTIONAL ACCESSORY)
TERMINAL BOARD
LOW E.S.P OPERATION NOTE-5 SEPARATE POWER SUPPLY
~
~
50Hz 60Hz
X1
CAPACITOR (M1F)
220-240V 220V
KCR
~
~
FUSE ( B , 5A, 250V)
X4A
X2
60Hz
50Hz
LIGHT EMITTING DIODE (SERVICE MONITOR GREEN)
X3
KFR
A2P
MAGNETIC RELAY (M1F)
S1H
X4
X3A X4A X5A
MAGNETIC RELAY (M1P)
L
N X3M
FAN
L N X3M
Hu
KHuR
HIGH E.S.P OPERATION
%H2O
MOTOR (INDOOR FAN)
OPERATION
R1T R2T R3T S1L
Y2
K1M
X1M L N
K1M
MOTOR (DRAIN PUMP)
KHR
F1U
Y1
K1M
X4A
THERMO SWITCH (135C) OR
BLK
t
t
t
F1U
RED BLU GRN/YLW
YC
(145C NOTE9) (M1F EMBEDDED)
F2U
WHT
F3U A1P
A2P
L N
R1T
THERMISTOR (AIR)
E1H
E1H
X3A X4A X5A
X13A X12A X11A
X8A
R2T R3T THERMISTOR (COIL)
(20 25 32 40 50 63 TYPE)
F1U
HAP
S1L
FLOAT SWITCH
X16A
40 50 63 80
(20 25 32 TYPE)
X3A
X18A
100 125 TYPE
T1R
TRANSFORMER (220-240V/22V)
HIGH E.S.P OPERATION
X30A
X1M
TERMINAL BLOCK (POWER)
PNK
FC FH FL FLL T1R
X2M
TERMINAL BLOCK (CONTROL)
T2
T2
NOTE-4
X4A
X4A
WHT
t
Y1E
ELECTRONIC EXPANSION VALVE
INPUT FROM OUTSIDE
KPR T1
T1
BLK
BRN
ORG
RED
X1A
YLW
OPTIONAL PARTS
A2P
NOTE-3
F2
F2
BLU
X3A X4A
E1H
ELECTRIC HEATER
ORG
TRANSMISSION WIRING
A2P
F1
F1
L
LL
C
K1R K2R K3R
F1U-F3U FUSE ( B , 15A, 250V)
(80 100 125 TYPE)
CENTRAL REMOTE CONTROLLER
BLU
X3A X4A
P2
P2
Hu
HUMIDIFIER
X7A
ELECTRIC PARTS BOX
BLK
P1
K1M
MAGNETIC RELAY (E1H)
P1
RED GRY BLK ORG BRN
X16A
X18A
FC FH FL FLL
X7A
S1H
HUMIDISTAT
Y2
Y1
WHT
M
X2M
X4A
~
Q1M
X3M
TERMINAL BLOCK (E1H)
C1
BLK
ORG BRN
A2P
A1P
RED
M1F (80 100 125 TYPE)
YLW
WIRED REMOTE CONTROLLER
BLU
A2P C
R1T
THERMISTOR (AIR)
L LL
X1M
WHT
WHT
T1R C1
SS1
SELECTOR SWITCH (MAIN/SUB)
X3A X4A X5A X6A
R1T
M
M
X2M
X7A
ADAPTOR FOR WIRING
P1 P2
~
RED GRY BLK BLU
F1U F2U FUSE ( B , 5A, 250V)
SS1
M1P
Y1E
ORG BRN
KCR
MAGNETIC RELAY
M
WHT
~
WIRED REMOTE CONTROLLER
KFR
MAGNETIC RELAY
C1
(OPTIONAL ACCESSORY)
Q1M
KHR
MAGNETIC RELAY(E1H)
YLW
M1F (20 25 32 40 50 63 TYPE)
KHuR MAGNETIC RELAY(Hu)
CONNECTOR FOR OPTIONAL PARTS
X16A CONNECTOR (ADAPTOR FOR WIRING)
X18A CONNECTOR (WIRING ADAPTOR
FOR ELECTORICAL APPENDICES)
F1U
F2U
X1A
TERMINALS FOR
OPERATION
INDICATOR
3D039561B
NOTES)
1.
: TERMINAL BLOCK,
,
: CONNECTOR,
: TERMINAL
2.
: FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTRUCTION MANUAL.
4. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE. FDRCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER. IN DETAILS, REFER TO THE
INSTALLATION MANUAL ATTACHED THE UNIT.
5. IN CASE INSTALLING THE ELECTRIC HEATER, EXECUTE THE ADDITIONAL WIRING FOR HEATER CIRCUIT (K1M, E1H). IN THIS CASE, THE MAIN POWER SUPPLY HAS TO BE SUPPLIED
INDEPENDENTLY.
6. IN CASE HIGH OR LOW E.S.P. OPERATION, CHANGE OVER THE WIRING CONNECTION FROM X4A (OF A2P) TO X3A OR X5A.
7. SYMBOLS SHOW AS FOLLOWS. (PNK : PINK WHT : WHITE YLW : YELLOW GRY : GRAY ORG : ORANGE BLU : BLUE BLK : BLACK RED : RED BRN : BROWN GRN : GREEN)
8. USE COPPER CONDUCTORS ONLY.
9. ONLY 80. 100. 125 TYPE.
X2A
A1P
A2P
C1
F1U
HAP
K1R-K3R
KPR
M1F
M1P
Q1M
Si34-803
Wiring Diagrams for Reference
397
398
X10A
F3U
K1R
HAP
Z1F
R1
X3A
A2P
TO X70A (A1P)
R2
X2A
V2R
X1A
X9A
YLW
BLU
ORG
PNK
GRY
RED
WHT
BLK
GRN
/YLW
MS
3~
M1F
R4
Z1C
N=1
GRN
BLU
RED
BLU
RED
F1U
X10A
F4U
BLK
PS
KPR
X25A
K1R
R1
A2P
HAP
Z1F
X3A
PS
R2
F2U
X8A
BLU
BRN
ORG
WHT
RED
X16A
R1T
t
R3T
X7A
MS
3~
M1F
Y1E
X35A
HAP
X18A X17A
R2T
INPUT FROM
OUTSIDE NOTE) 3
X1M X2M
A
3
P
*
Z2C
A
1
P
X33A
X35A
X28A
WIRED REMOTE
CONTROLLER
(OPTIONAL ACCESSORY)
SS1
P2
P1 R1T
CENTRAL REMOTE
CONTROLLER
NOTE) 2
TRANSMISSION
WIRING
Z
1
C
BLK
A2P
L1P
T2
T1
F2
F1
P2
P1
X2M
PNK
WHT
YLW
ORG
S1L
X15A
X30A
X33A
X28A
X13A
R4T
3D058783
NOTES) 1.
: TERMINAL
: CONNECTOR
: FIELD WIRING
2. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO
THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION
MANUAL.
3. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED
OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY
REMOTE CONTROLLER. IN DETAILS, REFER TO THE INSTALLATION
MANUAL ATTACHED THE UNIT.
4. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE
PNK : PINK YLW : YELLOW BRN : BROWN GRY : GRAY GRN : GREEN
ORG : ORANGE.
V1R
+ C1
X6A
GRN
L1R
Z2C
YLW YLW
BLK
X70A
X27A
A1P
ELECTRONIC
EXPANSION VALVE
Z1C, Z2C NOISE FILTER
(FERRITE CORE)
Z1F NOISE FILTER
CONNECTOR OPTIONAL
ACCESSORY
X28A CONNECTOR
(POWER SUPPLY FOR WIRING)
X33A CONNECTOR
(FOR WIRING)
X35A CONNECTOR (ADAPTER)
WIRED REMOTE CONTROLLER
R1T THERMISTOR (AIR)
SS1 SELECTOR SWITCH
(MAIN/SUB)
Y1E
R3
X1M
+ C2 + C3
~220V
60Hz
SWITCHING POWER
SUPPLY (A1P, A2P)
RESISTOR
(CURRENT LIMITING)
CURRENT SENSING
DEVICE
RESISTOR
(ELECTRIC DISCHARGE)
THERMISTOR (SUCTION AIR)
THERMISTOR (LIQUID)
THERMISTOR (GAS)
THERMISTOR
(DISCHARGE AIR)
FLOAT SWITCH
DIODE BRIDGE
POWER MODULE
TERMINAL STRIP
(POWER SUPPLY)
TERMINAL STRIP
(CONTROL)
PS
A3P
+ C1
X6A
V1R
L1R
INDOOR UNIT
PS
PRINTED CIRCUIT
BOARD
R1
A2P PRINTED CIRCUIT
BOARD (FAN)
R2
A3P PRINTED CIRCUIT
BOARD (CAPACITOR) R3, R4
C1, C2, C3 CAPACITOR
F1U FUSE (T, 3.15A, 250V) R1T
R2T
F2U FUSE (T, 5A, 250V)
R3T
F3U FUSE (T, 6.3A, 250V)
F4U FUSE (T, 6.3A, 250V)
R4T
HAP LIGHT EMITTING DIODE
S1L
(SERVICE MONITOR-GREEN)
V1R
(A1P, A2P)
KPR MAGNETIC RELAY
V2R
K1R MAGNETIC RELAY
X1M
L1R REACTOR
M1F MOTOR (FAN)
X2M
M1P MOTOR (DRAIN PUMP)
A1P
BLU
RED
TO X1M
~220-240V
50Hz
POWER
SUPPLY
M
~
BLU
M1P
Appendix
Si34-803
3D039621B
FXMQ200MA / 250MAVE
Appendix
399
Si34-803
3D039801D
400
Appendix
POWER CIRCUIT
(DEFROST-ORANGE)
(FILTER SIGN-RED)
(TIMER-GREEN)
PC
SIDE
FRONT
X1M
X2M
X27A
X20A
F1U
: CONNECTOR
: CONNECTOR
: FIELD WIRING
M1F
MS
3~
PC
: TERMINAL
A1P
HAP
N WHT
L RED
A1P
X2M GRN/YLW
PC
M1S
MSW
X36A
NE
GRN
HAP
Y1E
X7A
X35A
X19A
X18A
X14A
WHT
X15A
X35A
X15A
4.
X1A
A3P
H1P
BS1
H2P
H3P
H4P
CONNECTING.
3D034206D
PNK : PINK YLW : YELLOW BLK : BLACK ORG : ORANGE BRN : BROWN BLU : BLUE 7. CONFIRM THE METHOD OF SETTING THE SELECTOR
PNK
WHT
YLW
ORG
BLU
BLK
X1A
SS2
SS1
RECEIVER/DISPLAY UNIT
X2A
A2P
X24A
NOTE) 8
A1P
X30A
NOTE) 8
X24A
R1T
R2T
R3T
1.
X1M
X2M
CONTROL BOX
(INDOOR UNIT)
HAP
A1P
NOTES)
L
N
220V
~
60Hz
POWER SUPPLY
WHT
ORG
BRN
BLU
INDOOR UNIT
RED
Appendix
Si34-803
Wiring Diagrams for Reference
401
Si34-803
3D039826D
402
Appendix
Si34-803
3D044973A
Appendix
403
Si34-803
3D044996C
404
Appendix
Si34-803
3D044901B
Appendix
405
Si34-803
Outdoor Unit
3.1.1 RXYQ5PAY1~8PAY1
Item
Name
Type
Inverter
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Pressure
protection
Temperature
protection
Others
406
Symbol
Model
RXYQ5PAY1
RXYQ8PAY1
JT1GCVDKYR@SB
M1C
14.7A
M2C
M3C
M1F
Y1E
Y2E
1.15A
3A
+0
For M1C
S1PH
High pressure
For M2C
switch
S2PH
S3PH
SLNPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
A1P
A2P
250V, 15A
250V, 3A
F1U
250V AC 5A Class B
For M3C
Low pressure sensor
Discharge gas temperature
protection
(Discharge pipe thermistor)
Inverter fin temperature
protection
(Radiator fin thermistor)
Fuse
ON: 3.00.15MPa
Appendix
Si34-803
3.1.2 RXYQ10PAY1~12PAY1
Item
Name
Type
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Inverter
Pressure
protection
Others
Appendix
Model
RXYQ10PAY1
RXYQ12PAY1
JT1GCVDKYR@SB
M1C
14.7A
JT170G-KYE@T
M2C
15.0A
M3C
M1F
3A
1.15A
Y1E
Y2E
For M1C
S1PH
High pressure
For M2C
switch
S2PH
For M3C
Temperature
protection
Symbol
+0
+0
ON: 3.00.15MPa
ON: 3.00.15MPa
S3PH
SLNPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
A1P
A2P
250V, 15A
250V, 3A
F1U
250V AC 5A Class B
Fuse
407
Item
Name
Type
Inverter
OC protection
device
Type
Compressor
STD 1
OC protection
device
Type
STD 2
OC protection
device
OC
protection
Fan motor
device
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Temperature
protection
Others
408
Symbol
RXYQ14PAY1
Model
RXYQ16PAY1
JT1GCVDKYR@SB
M1C
RXYQ18PAY1
14.7A
JT170G-KYE@T
M2C
15.0A
JT170G-KYE@T
M3C
15.0A
M1F
1.15A
Y1E
Y2E
S1PH
ON: 3.00.15MPa
S2PH
+0
OFF: 4.0 0.12 MPa
ON: 3.00.15MPa
For M3C
S3PH
+0
OFF: 4.0 0.12 MPa
SLNPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
A1P
A2P
250V, 15A
250V, 3A
F1U
250V AC 5A Class B
For M1C
Pressure
protection
Si34-803
Fuse
3A
+0
ON: 3.00.15MPa
Appendix
Si34-803
3.2
Name
Inverter
Compressor
STD 1
STD 2
Fan motor
Item
Name
Inverter
Compressor
Type
OC protection
device
Type
OC protection
device
Type
OC protection
device
OC protection
device
Type
OC protection
device
Type
Model
RXYQ5PAYL
RXYQ8PAYL
JT1GCVDKYR@SB
M1C
14.7A
M2C
M3C
M1F
Symbol
1.15A
3A
Model
RXYQ5PTL
RXYQ8PTL
JT100GCVDK@SB
M1C
26.5A
OC protection
device
Type
STD 2
OC protection
device
OC protection
Fan motor
device
Electronic expansion valve (Main)
M2C
M3C
Y2E
Pressure
protection
Temperature
protection
Others
Appendix
STD 1
Symbol
M1F
Y1E
2.3A
5.5A
+0
For M1C
S1PH
High pressure
For M2C
switch
S2PH
S3PH
SLNPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
A1P
A2P
F1U
250V, 15A
250V, 3A (PTL : 250V, 15A)
250V AC 6.3A Class B
(No fuse for TL model)
For M3C
Low pressure sensor
Discharge gas temperature
protection
(Discharge pipe thermistor)
Inverter fin temperature
protection
(Radiator fin thermistor)
Fuse
ON: 3.00.15MPa
409
Si34-803
Name
Inverter
Compressor
STD 1
STD 2
OC protection
device
Fan motor
Item
Name
Inverter
Compressor
Type
OC protection
device
Type
OC protection
device
Type
OC protection
device
STD 1
STD 2
Type
OC protection
device
Type
OC protection
device
Type
OC protection
device
Others
410
M1C
14.7A
JT170G-KYH@T
M2C
15.0A
M3C
M1F
M2F
Symbol
3A
1.15A
1.15A
Model
RXYQ10PTL
RXYQ12PTL
JT100GCVDK@SB
M1C
26.5A
JT170G-K
M2C
28.8A
M3C
5.5A
For M1C
S1PH
High pressure
For M2C
switch
S2PH
Temperature
protection
Model
RXYQ10PAYL
RXYQ12PAYL
JT1GCVDKYR@SB
M1F
M2F
Y1E
Y2E
OC protection
device
Fan motor
Pressure
protection
Symbol
For M3C
Low pressure sensor
Discharge gas temperature
protection
(Discharge pipe thermistor)
Inverter fin temperature
protection
(Radiator fin thermistor)
Fuse
+0
+0
2.3A
2.3A
Fully open: 480pls
Fully open: 480pls
ON: 3.00.15MPa
ON: 3.00.15MPa
S3PH
SLNPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
A1P
A2P
F1U
250V, 15A
250V, 3A (PTL : 250V, 15A)
250V AC 6.3A Class B
(No fuse for TL model)
Appendix
Si34-803
Name
Inverter
Compressor
STD 1
STD 2
Fan motor
Item
Compressor
Type
OC protection
device
Type
OC protection
device
Type
OC protection
device
M2C
OC protection
device
M1F
M2F
Name
Inverter
STD 1
STD 2
Type
OC protection
device
Type
OC protection
device
Type
OC protection
device
Others
Appendix
Model
RXYQ16PAYL
JT1GCVDKYR@SB
M1C
RXYQ18PAYL
14.7A
JT170G-KYH@T
15.0A
JT170G-KYH@T
M3C
Symbol
15.0A
1.15A
1.15A
RXYQ14PTL
3A
3A
Model
RXYQ16PTL
JT100GCVDK@SB
M1C
RXYQ18PTL
26.5A
JT170G-K
M2C
28.8A
JT170G-K
M3C
28.8A
2.3A
2.3A
Fully closed: 0pls
Fully closed: 0pls
For M1C
S1PH
S2PH
For M3C
S3PH
SLNPL
OFF: 0.07MPa
R3T
OFF: 135C
R1T
OFF: 93C
For main PC
board
A1P
A2P
F1U
250V, 15A
250V, 3A (PTL : 250V, 15A)
250V AC 6.3A Class B
(No fuse for TL model)
Temperature
protection
RXYQ14PAYL
M1F
M2F
Y1E
Y2E
OC protection
device
Fan motor
Pressure
protection
Symbol
Fuse
5.5A
5.5A
Fully open: 480pls
Fully open: 480pls
+0
ON: 3.00.15MPa
+0
ON: 3.00.15MPa
+0
411
3.3
Si34-803
Indoor Side
Remote
Controller
Symbol
FXFQ25
PVE
FXFQ32
PVE
FXFQ40
PVE
FXFQ50
PVE
Wired Remote
Controller
FXFQ80
PVE
BRC1C62
Option
Wireless Remote
Controller
Fan Motor
FXFQ63
PVE
BRC7F634F
M1F
DC280V 56W 8P
DC 320V 120W 8P
Drain Pump
M1P
Swing Motor
M1S
MP35HCA[3P080801-1]
Stepping Motor DC12V
R1T
R3T
ST8605-14 8 L1000
20k (25C)
R2T
ST8602A-15 6 L1000
20k (25C)
Motors
Thermistor (Heat
Exchanger)
Others
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Thermal Fuse
TFu
Transformer
T1R
Model
Parts Name
Remote
Controller
Symbol
FXCQ
20MVE
FXCQ
25MVE
FXCQ
32MVE
FXCQ
40MVE
FXCQ
50MVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC7C62
FXCQ
63MVE
FXCQ
80MVE
FXCQ Remark
125MVE
Option
AC 220~240V 50Hz
Fan Motor
M1F
110W
115W
Thermal Fuse 152C
Motors
120W
130W
Drain Pump
M1P
Swing Motor
M1S
MT8-L[3PA07509-1]
AC200~240V
R1T
ST8601-6 4 L1250
20k (25C)
R3T
ST8605-6 8 L1250
20k (25C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-5 6 L1000
20k (25C)
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Others
412
150W
185W
87C : ON
Appendix
Si34-803
Model
Parts Name
Remote
Controller
Symbol
FXKQ
25MAVE
FXKQ
32MAVE
FXKQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C61
FXKQ
63MAVE
Remark
Option
AC 220~240V 50Hz
Fan Motor
115W 4P
M1F
120W 4P
M1P
AC 220-240V (50Hz)
PLD-12200DM
Thermal Fuse 145C
Swing Motor
M1S
MP35HCA [3P080801-1]
AC200~240V
R1T
ST8601-13 4 L630
20k (25C)
R3T
ST8605-7 8 L1600
20k (25C)
R2T
ST8602A-7 6 L1600
20k (25C)
Thermistor (Heat
Exchanger)
Others
145W 4P
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
105C :
Model
Parts Name
Remote
Controller
Symbol
FXDQ
20PBVE(T)
FXDQ
25PBVE(T)
FXDQ
32PBVE(T)
FXDQ
40NBVE(T)
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C65
FXDQ
50NBVE(T)
FXDQ
63NBVE(T)
Remark
Option
AC 220~240V 50Hz
Fan Motor
M1F
162W
1130W
Thermal protector
130C: OFF, 83C: ON
Motors
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145C
R1T
ST8601-1 4 L=250
20k (25C)
R3T
ST8605-4 8 L=800
20k (25C)
R2T
ST8602A-4 6 L=800
20k (25C)
Thermistor (Heat
Exchanger)
Others
Float Switch
S1L
FS-0211E
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Appendix
413
Parts Name
Remote
Controller
Symbol
Si34-803
Model
Remark
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
FXSQ
20MVE 25MVE 32MVE 40MVE 50MVE 63MVE 80MVE 100MVE 125MVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
Option
AC 220~240V 50Hz
Fan Motor
150W
M1F
165W
185W 1125W
Motors
Drain Pump
M1P
AC220-240V (50Hz)
PLD-12230DM
Thermal Fuse 145C
R1T
ST8601-4 4 L800
20k (25C)
R3T
ST8605-7 8 L1600
20k (25C)
R2T
ST8602A-6 6 L1250
20k (25C)
Thermistor (Heat
Exchanger)
Others
1225W
Thermal protector
135C : OFF 87C : ON
Float Switch
S1L
FS-0211B
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Model
Parts Name
Remote
Controller
Symbol
FXMQ
40PVE
FXMQ
50PVE
FXMQ
63PVE
FXMQ
80PVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C65
Fan Motor
M1F
DC280V 140W 8P
Drain Pump
M1P
R1T
ST8601-3 L630
20k (25C)
R3T
ST8605-14 8 L1000
20k (25C)
R2T
ST8602A-6 8 L1250
20k (25C)
Others
414
Float Switch
S1L
FS-0211B
Fuse (A1P)
F1U
250V 3.15A
F3U
F4U
250V 6.3A
Fuse (A2P)
F2U
250V 5A
FXMQ
125PVE
Remark
DC373V 350W 8P
AC220-240V (50/60Hz)
PLD-12230DM
Thermal protector 145C
Motors
FXMQ
100PVE
Appendix
Si34-803
Parts Name
Remote
Controller
Motors
Symbol
Model
FXMQ200MAVE
FXMQ250MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
Option
Fan Motor
M1F
C1R
AC 220~240V 50Hz
1380W2
10 F 400V
12 F 400V
R1T
ST8601A-13
4 L630
R3T
ST8605A-5
8 L1000
Thermistor (Heat
Exchanger)
R2T
ST8602A-6
6 L1250
Float switch
S1L
FS-0211
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Others
Remark
Model
Parts Name
Remote
Controller
Symbol
FXHQ
32MAVE
FXHQ
63MAVE
Wired Remote
Controller
FXHQ
100MAVE
BRC1C62
Wireless Controller
Remark
Option
BRC7E63W
AC 220~240V/220V 50Hz/60Hz
Fan Motor
M1F
163W
1130W
Motors
Capacitor for Fan Motor
C1R
9.0F-400V
3.0F-400V
Swing Motor
M1S
MT8-L[3P058751-1]
AC200~240V
R1T
ST8601A-1 4 L250
20k (25C)
R3T
ST8605-6 8 L = 1250
20k (25C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-6 6 L = 1250
20k (25C)
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
Others
Appendix
80C : ON
ST8605-6 8 L = 1250
20k (25C)
ST8602A-6 6 L = 1250
20k (25C)
415
Si34-803
Model
Parts Name
Remote
Controller
Symbol
FXAQ
20MAVE
FXAQ
25MAVE
FXAQ
32MAVE
FXAQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC7E618
FXAQ
50MAVE
Remark
FXAQ
63MAVE
Option
AC 220~240V 50Hz
Fan Motor
M1F
140W
Motors
143W
MSFBC20C21 [3SB40550-1]
AC200~240V
Swing Motor
M1S
R1T
ST8601-2 4 L400
20k (25C)
R3T
ST8605-2 8 L400
20k (25C)
R2T
ST8602-2 6 L400
20k (25C)
Float Switch
S1L
OPTION
Fuse
F1U
250V 5A 5.2
Others
80C : ON
Model
Parts Name
Remote
Controller
Symbol
FXLQ
20MAVE
FXLQ
25MAVE
FXLQ
32MAVE
FXLQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
FXLQ
50MAVE
Remark
FXLQ
63MAVE
Option
AC 220~240V 50Hz
Motors
Fan Motor
M1F
115W
125W
Thermal protector 135C : OFF
C1R
1.0F-400V
0.5F-400V
1.0F-400V
R1T
ST8601-6 4 L1250
20k (25C)
R3T
ST8605-9 8 L2500
20k (25C)
R2T
ST8602A-9 6 L2500
20k (25C)
Fuse
F1U
AC250V 5A
Transformer
T1R
TR22H21R8
Others
416
135W
120C : ON
1.5F-400V
2.0F-400V
Appendix
Si34-803
Model
Parts Name
Remote
Controller
Symbol
FXNQ
20MAVE
FXNQ
25MAVE
FXNQ
32MAVE
FXNQ
40MAVE
Wired Remote
Controller
BRC1C62
Wireless Remote
Controller
BRC4C62
FXNQ
50MAVE
FXNQ
63MAVE
Remark
Option
AC 220~240V 50Hz
Motors
Fan Motor
M1F
115W
125W
Thermal protector 135C : OFF
C1R
1.0F-400V
0.5F-400V
1.0F-400V
R1T
ST8601-6 4 L1250
20k (25C)
R3T
ST8605-9 8 L2500
20k (25C)
R2T
ST8602A-9 6 L2500
20k (25C)
Fuse
F1U
AC250V 5A
Transformer
T1R
TR22H21R8
Others
Parts Name
Remote
Controller
Symbol
135W
120C : ON
1.5F-400V
2.0F-400V
Model
FXUQ71MAV1
FXUQ100MAV1
Wired Remote
Controller
FXUQ125MAV1
Remark
BRC1C62
Option
Wireless Remote
Controller
BRC7C528W
AC 220~240V 50Hz
Fan Motor
M1F
145W
190W
Thermistors
Others
Appendix
Drain Pump
M1P
Swing Motor
M1S
MT8-L[3PA07572-1]
AC200~240V
R1T
ST8601-1 4 L=250
20k (25C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-4 6 L=800
20k (25C)
Float Switch
S1L
FS-0211B
83C : ON
417
Parts Name
Remote
Controller
Symbol
Si34-803
Model
FXMQ125MFV1
Wired Remote
Controller
FXMQ200MFV1
FXMQ250MFV1
Remark
BRC1C62
Wireless Remote
Controller
Option
AC200~240V 50Hz
Fan Motor
M1F
1380W
Motors
Solenoid
valve
Thermistors
Others
418
87C : ON
10 F
400V
C1R
Solenoid valve
(Hot gas)
Y1S
Body: VPV-603D
Coil: NEV-MOAJ532C1 AC220-240V
R1T
ST8601-13 4 L=630
20k (25C)
R3T
ST8605-6 8 L=1250
20k (25C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-2 6 L=1250
20k (25C)
Thermistor (for
discharge air)
R4T
ST8605-8 L=2000
20k (25C)
Float switch
S1L
Option
Fuse
F1U
250V 5A 5.2
Transformer
T1R
TR22H21R8
16 F
400V
Appendix
Si34-803
Option List
4. Option List
4.1
Type
Item
Wireless
Wired
Wired remote controller
with weekly schedule timer
Simplified remote
controller
Remote controller for
hotel use
Adaptor for wiring
Wiring adaptor for
electrical appendices (1)
Wiring adaptor for
electrical appendices (2)
Remote sensor
Installation box for
adaptor PC board
Central remote controller
Electrical box with earth
terminal (3 blocks)
Unified on/off controller
Electrical box with earth
terminal (2 blocks)
Noise filter (for
electromagnetic interface
use only)
Schedule timer
External control adaptor
for outdoor unit (Must be
installed on indoor units)
Remote
controller
FXFQ-P
FXCQ-M
FXKQ-MA
FXDQ-NB
FXDQ-PB
FXUQ-M
FXSQ-M
BRC7F634F
BRC7C62
BRC4C61
BRC4C65
BRC7C528W
BRC4C62
BRC1C62
FXMQ-MA
FXMQ-P
BRC4C65
FXLQ-MA
FXHQ-MA FXAQ-MA FXNQ-MA
BRC7E63W
BRC7E618
BRC4C62
BRC1D61
Note 8
BRC2C51
Note 8
BRC2C51
Note 8
BRC2C51
BRC3A61
KRP1C63
KRP1B61
KRP1B61
KRP1B56
KRP1B61
BRC3A61
KRP1C64
KRP1C3
KRP1B61
KRP2A62
KRP2A61
KRP2A61
KRP2A53
KRP2A62
KRP2A61
KRP2A61
KRP2A62
KRP2A61
KRP2A61
KRP4AA53
KRP4A51
KRP4A51
KRP4A54
KRP4A53
KRP4A51
KRP4AA51
KRP4A52
KRP4A51
KRP4A51
KRCS01-4B
Note 2, 3
KRP1H98
KRCS01-1
Note 2, 3
KRP1B96
Note 3
KRP1C93
KRCS01-1
Note 2, 3
KRP4A93
DTA104A61
DTA104A61
KRCS01-1
Note 4, 6
KRP1B101
KRP1B97
Note 5
KRP4A91
DCS302CA61
KRCS01-4B
Note 2, 3
KRP4A96
BRC3A61
KJB311AA
DCS301BA61
KJB212AA
KEK26-1A
DST301BA61
DTA104A62
DTA104A61
DTA104A61
DTA104A53
DTA104A61
Note 7
DTA102A52
DTA104A61 DTA104A62
Note:
1. Installation box (No.8) is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box (No. 8) is necessary for second adaptor.
6. Installation box (No. 8) is necessary for each adaptor.
7. This adaptor is required when connecting with optional controller for centralized control.
8. BRC2A51 is also available.
Various PC Boards
No.
Part name
Appendix
Model No.
KRP1B56
KRP1B57
KRP1B59
KRP1B61
KRP1C3
DTA109A51
Function
PC board when equipped with auxiliary electric heater in the indoor unit.
Up to 1024 units can be centrally controlled in 64 different groups.
Wiring restrictions (max. length: 1000m, total wiring length: 2000m, max. number of
branches: 16) apply to each adaptor.
419
Option List
Si34-803
System Configuration
No.
Item
Model No.
2-1
3
Note *2
DCS303A51
DCS302CA61
KJB311AA
DCS301BA61
3-1
KJB212AA
3-2
KEK26-1A
Schedule timer
For SkyAir,
FD(Y)M-FA,
FDY-KA
FDYB-KA,
FVY(P)J-A
*DTA102A52
Central control
adaptor kit
For UAT(Y)K(A),FD-K
*DTA107A55
*DTA103A51
DTA109A51
8-1
Function
Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD
panel. ON/OFF, temperature settings and scheduling can be controlled individually for
indoor units.
DST301BA61
Mounting plate
KRP4A92
Note:
1. Installation box for * adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralized control equipment.
1-3
1-4
2-1
2-2
3-1
3-2
4
5
6
7
8
Basic
Hardware
128 units
256 units
Number of
512 units
units to be
connected
768 units
1024 units
P.P.D.
Model No.
Function
DCS601C51
DCS601A52
DCS002C51
DCS004A51
Web
DAM004A51
Eco
DAM003A51
DAM101A51
DEC101A51
DEC102A51
Option
Option Software
Contact/analog
signal
2-3
2-4
2-5
2-6
Basic
intelligent
Manager III
1
1-1
1-2
Part name
intelligent Touch
Controller
No.
DMS502B51
DAM411B51
Expansion kit, installed on DMS502B51, to provide 2 more DIIINET communication ports. Not usable independently.
Optional Di board
DAM412B51
DMS504B51
DPF201A51
DPF201A52
DPF201A53
* DCS302A52
Parallel interface
Basic unit
Temperature
measurement units
Temperature
setting units
Unification adaptor for
computerized control
Note:
*1. BACnet is a registered trademark of American Society of Heating, Refrigerating and AirConditioning Engineers (ASHRAE).
*2. LONWORKS is a registered trade mark of Echelon Corporation.
*3. Installation box for * adaptor must be procured on site.
420
Appendix
Si34-803
4.2
Option List
KRC19-26A
Cool/Heat Selector
Distributive Cool/Heat
Piping
Selector
KJB111A
Fixing box
KHRP26M22H
(Max. 4 branch)
Refnet header
Refnet joint
KHRP26A22T
KHRP26M22H,
(Max. 4 branch)
KHRP26M33H
(Max. 8 branch)
KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch)
KHRP26M72H
(Max. 8 branch)
KHRP26A22T,
KHRP26A33T
KHRP26A22T, KHRP26A33T,
KHRP26A72T
KWC26C160
KWC26C280
KWC26C280E
KWC26C450
KWC26C450E
BHGP26A1(E)
C : 3D053052C
Optional accessories
Cool/Heat
Selector
KRC19-26A
Cool/Heat Selector
Distributive
Piping
KJB111A
Fixing box
Refnet header
KHRP26M22H
(Max. 4 branch),
KHRP26M33H
(Max. 8 branch),
KHRP26M72H
(Max. 8 branch)
Refnet joint
KHRP26A22T,
KHRP26A33T,
KHRP26A72T
KWC26C280E
KWC26C450E
KHRP26M73TP, KHRP26M73HP
KWC26C280
KWC26C280E
KWC26C4502
KWC26C450E
KWC26C450
BHGP26A1(E)
KWC26C450E2
C : 3D053052C
Optional accessories
KJB111A
Fixing box
Refnet header
Refnet joint
KHRP26M73TP, KHRP26M73HP
KRC19-26A
Cool/Heat Selector
Distributive Cool/Heat
Piping
Selector
KWC26C280
KWC26C4502
KWC26C280E
KWC26C450E2
KWC26C4503
KWC26C450E3
BHGP26A1(E)
C : 3D053052C
Appendix
421
Option List
Si34-803
Optional accessories
KRC19-26A
Cool/Heat
Selector
Cool/Heat Selector
Distributive
Piping
KJB111A
Fixing box
KHRP26M22H, KHRP26M33H,
(Max. 4 branch) (Max. 8 branch)
KHRP26M72H
(Max. 8 branch)
Refnet header
Refnet joint
KWC26C280E2
KWC26C2802
BHGP26A1(E)
C : 3D053053A
Optional accessories
RXYQ24PAHY1E,
PAHYLE, PHTLE
RXYQ26PAHY1E,
PAHYLE, PHTLE
RXYQ28PAHY1E,
PAHYLE, PHTLE
RXYQ30PAHY1E,
PAHYLE, PHTLE
KRC19-26A
Cool/Heat Selector
Distributive Cool/Heat
Piping
Selector
RXYQ28PAHY1,
PAHYL, PHTL
RXYQ30PAHY1,
PAHYL, PHTL
KJB111A
Fixing box
Refnet header
Refnet joint
KHRP26M73TP, KHRP26M73HP
KWC26C280E2
KWC26C450E
KWC26C2802
KWC26C450
KWC26C280E3
BHGP26A1(E)
C : 3D053053A
Optional accessories
Distributive Cool/Heat
Piping
Selector
Cool/Heat Selector
KJB111A
Fixing box
Refnet header
Refnet joint
KHRP26M73TP, KHRP26M73HP
KWC26C280
KWC26C4502
KWC26C280E
KWC26C450E2
KWC26C4503
KWC26C450E3
BHGP26A1(E)
C : 3D053053A
422
Appendix
Si34-803
5m or less
than 5m
Connection
Kit A
Connection
Kit B
Since there is a possibility that oil may be collected on a stop machine side, install piping
between outdoor units to go to level or go up to an outdoor unit, and to make a slope.
Less than 2m
Vertical
Projection
200mm or
more
Less than 2m
2m or more
Vertical
Projection
Less than 2m
Appendix
Vertical
Projection
Less than 2m
423
5.2
Si34-803
Wrong
Good
Good
Vertical
Projection
Outdoor Unit - Multi Connection Piping Kit Actual piping length 10m or less, equivalent length 13m or less
piping length 165m or less, equivalent length 190m or
Max.allowable Multi Connection Piping Kit - Indoor Unit Actual
less,
the
total extension 1000m or less
Piping Length
Actual
piping
length 40m or less
REFNET Joint - Indoor Unit
(Refer to Page 425, 426 Note 2 in case of up to 90m)
Outdoor Unit - Outdoor Unit
5m or less
90m or less
Allowable
50m or less
(when an outdoor unit is lower than indoor units: 40m or less in
Level
Outdoor Unit - Indoor Unit
case of RXYQ5P(A))
Difference
Indoor Unit - Indoor Unit
15m or less
424
Appendix
Si34-803
Example of connection
(Connection of 8 indoor units)
Single outdoor
system
Outdoor unit
Outdoor unit
(1)
indicate the Outdoor unit multi
connection piping kit
b
A
c
B
d
C
i
1
j
2
k
3
l
4
H1
H1
m
5
d
1
Indoor units ( 1 - 8 )
e
2
First Outdoor
unit multi connection
piping kit
Actual pipe length
Maximum
allowable
length
Allowable
height
length
Equivalent length
Total extension length
Actual pipe length
Equivalent length
Difference in height
Difference in height
Difference in height
Actual pipe length
H3
Appendix
i
1
k
3
f
E
j
2
l
4
H1
m
6
Part C
f
3
h
7 H2
i
8
REFNET header
a
j
g
f
4
H3
e
2
e
3
d
2
Indoor units ( 1 - 8 )
Outdoor unit
REFNET header
7 H2
REFNET joint (A B)
Indoor units ( 1 - 8 )
b
1
H1
k
7
H1
H2
c
1
d
2
e
4
h
7 H2
Indoor units ( 1 - 8 )
Indoor units ( 1 - 8 )
i
8
Outdoor unit
6.4
9.5
12.7
15.9
19.1
22.2
25.4
28.6
31.8
34.9
38.1
41.3
0.80
0.80
0.80
0.99
0.80
0.80
0.88
0.99
1.10
1.21
1.32
1.43
Temper grade
O type
5HP type
8HP type
10HP type
12~16HP type
18~22HP type
24HP type
26~34HP type
36~54HP type
(See Note 1 - Next page)
How to select the Outdoor unit multi connection piping kit (This is required when the system is multi outdoor unit system.)
Choose from the following table in accordance with the number of outdoor units.
Number of outdoor units
2 units
3 units
Liquid pipe
9.5
12.7
15.9
34.9
41.3
1/2H type
Part B
Part A
H2
Indoor units ( 1 - 8 )
Outdoor unit
H1
a
a
A
f
3
H3
Multi outdoor
system
j
7
7 H2
REFNET header
Outdoor unit
a
REFNET header
Outdoor unit
REFNET joint (A B)
i
a
a
Liquid pipe
9.5
28.6
12.7
15.9
34.9
41.3
19.1
19.1
20 25 32 40 50 type
63 80 100 125 type
200 type
250 type
(Unit:mm)
Liquid pipe
6.4
9.5
425
Si34-803
R=
0.37
0.26
0.18
0.12
0.059
0.022
REFRIGERANT
AMOUNT FOR
HEAT PUMP SYSTEM
REFRIGERANT AMOUNT
FOR EXCEEDING CONNECTION
CAPACITY OF INDOOR UNIT
TABLE A
TABLE B
TABLE A
MODEL NAME
RX(Y)Q5P
RX(Y)Q8 ~ 12P
RX(Y)Q14 ~ 22P
RX(Y)Q24 ~ 30P
RX(Y)Q32 ~ 38P
RX(Y)Q40 ~ 48P
RX(Y)Q50 ~ 54P
TABLE B
THE AMOUNT OF
REFRIGERANT
0kg
0.5kg
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg
INDOOR CONNECTION
CAPACITY [X]
X 100%
100% < X 120%
120% < X 130%
130% < X 140%
140% < X 150%
150% < X 160%
160% < X 170%
170% < X 180%
180% < X 190%
190% < X 200%
5P~8P
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : RXYQ34P~
R = ( 30 0.26 + 10 0.18 + 10 0.12 + 40 0.059 + 49 0.022 )+ 2.0 + 0.5
Total capacity of indoor unit : 116%
a
b
i
c+d+e+f
g+h+i+j+k RXYQ34P~ 116%
a : 19.1 30m d : 9.5 10m g : 6.4 10m j : 6.4 10m
= 16.738
16.7kg
b : 15.9 10m e : 9.5 10m h : 6.4 20m k : 6.4 9m
c : 9.5 10m f : 9.5 10m i : 12.7 10m
Round off units of 0.1 kg.
Note 1
When the equivalent pipe length between outdoor and indoor
units is 90m or more, the size of main pipes (both gas-side and
liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but
even in such case it is able to increase the size of main pipes.
The first refrigerant branch kit
Outdoor unit
Main pipes
Indoor unit
Increase
Gas
Liquid
Model
Gas
Liquid
Model
Gas
Liquid
RXYQ5 Type
19.1
Not Increased
RXYQ20 Type
31.8*
19.1
RXYQ34 Type
38.1*
22.2
22.2
RXYQ8 Type
22.2
12.7
RXYQ22 Type
31.8*
19.1
22.2
22.2
RXYQ10 Type
25.4*
12.7
19.1
22.2
22.2
15.9
RXYQ26 Type
38.1*
22.2
22.2
22.2
15.9
RXYQ28 Type
38.1*
22.2
22.2
RXYQ16 Type
31.8*
15.9
RXYQ30 Type
38.1*
22.2
22.2
RXYQ18 Type
31.8*
19.1
RXYQ32 Type
38.1*
22.2
22.2
Note 2
Model
Gas
Liquid
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are satisfied. (In case of Branch with REFNET joint )
Required Conditions
Example Drawings
1. It is necessary to increase the pipe size between the first branch kit and the final
branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must not be increased.
8 b + c + d + e + f + g + p 90 m
increase the pipe size of b, c, d, e, f, g
2. For calculation of Total extension length, the actual length of above pipes must be
doubled. (except main pipe and the pipes that are not increased)
a+b2+c2+d2+e2+f2+g2
+ h + i + j + k + l + m + n + p 1000 m
h, i, j....... p 40 m
h
1
j
2
e
D
l
4
m
5
H1
f
E
k
3
34.9 38.1*
Outdoor unit
22.2 25.4*
28.6 31.8*
n
6
Indoor units ( 1 - 8 )
7
8
Note 3
If the pipe size above the REFNET header is 34.9 or more, KHRP26M73HP is required.
426
Appendix
Si34-803
TC
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
Appendix
0.0
88.0
79.1
71.1
64.1
57.8
52.3
47.3
42.9
38.9
35.3
32.1
29.2
26.6
24.3
22.2
20.3
18.5
17.0
15.6
14.2
13.1
12.0
11.1
10.3
9.5
8.8
8.2
7.6
7.0
6.7
6.0
5.5
5.2
4.79
4.46
4.15
3.87
3.61
3.37
3.15
2.94
2.75
2.51
2.41
2.26
2.12
1.99
1.87
1.76
1.65
1.55
1.46
1.38
R1T
R2T
R3T
R1T
R2T
R4T
R5T
R6T
TC
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
0.0
197.81
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
111.99
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
65.84
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
39.96
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
25.01
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
16.10
0.5
192.08
181.16
170.94
161.36
152.38
143.96
136.05
128.63
121.66
115.12
108.96
103.18
97.73
92.61
87.79
83.25
78.97
74.94
71.14
67.56
64.17
60.96
57.94
55.08
52.38
49.83
47.42
45.14
42.98
40.94
39.01
37.18
35.45
33.81
32.25
30.77
29.37
28.05
26.78
25.59
24.45
23.37
22.35
21.37
20.45
19.56
18.73
17.93
17.17
16.45
15.76
TC
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
0.0
16.10
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
10.63
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
7.18
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
4.96
4.79
4.62
4.46
4.30
4.16
4.01
3.88
3.75
3.62
3.50
3.38
3.27
3.16
3.06
2.96
2.86
2.77
2.68
2.60
2.51
(k)
0.5
15.76
15.10
14.48
13.88
13.31
12.77
12.25
11.76
11.29
10.84
10.41
10.00
9.61
9.24
8.88
8.54
8.21
7.90
7.60
7.31
7.04
6.78
6.53
6.53
6.53
6.53
6.06
5.84
5.43
5.05
4.87
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
3.44
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
2.47
427
Si34-803
Outdoor Unit
Thermistors for
Discharge Pipe
(R3T, R3133T)
TC
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
428
0.0
640.44
609.31
579.96
552.00
525.63
500.66
477.01
454.60
433.37
413.24
394.16
376.05
358.88
342.58
327.10
312.41
298.45
285.18
272.58
260.60
249.00
238.36
228.05
218.24
208.90
200.00
191.53
183.46
175.77
168.44
161.45
154.79
148.43
142.37
136.59
131.06
125.79
120.76
115.95
111.35
106.96
102.76
98.75
94.92
91.25
87.74
84.38
81.16
78.09
75.14
72.32
0.5
624.65
594.43
565.78
538.63
512.97
488.67
465.65
443.84
423.17
403.57
384.98
367.35
350.62
334.74
319.66
305.33
291.73
278.80
266.51
254.72
243.61
233.14
223.08
213.51
204.39
195.71
187.44
179.57
172.06
164.90
158.08
151.57
145.37
139.44
133.79
128.39
123.24
118.32
113.62
109.13
104.84
100.73
96.81
93.06
89.47
86.04
82.75
79.61
76.60
73.71
70.96
TC
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
0.0
72.32
69.64
67.06
64.60
62.24
59.97
57.80
55.72
53.72
51.98
49.96
48.19
46.49
44.86
43.30
41.79
40.35
38.96
37.63
36.34
35.11
33.92
32.78
31.69
30.63
29.61
28.64
27.69
26.79
25.91
25.07
24.26
23.48
22.73
22.01
21.31
20.63
19.98
19.36
18.75
18.17
17.61
17.07
16.54
16.04
15.55
15.08
14.62
14.18
13.76
13.35
0.5
70.96
68.34
65.82
63.41
61.09
58.87
56.75
54.70
52.84
50.96
49.06
47.33
45.67
44.07
42.54
41.06
39.65
38.29
36.98
35.72
34.51
33.35
32.23
31.15
30.12
29.12
28.16
27.24
26.35
25.49
24.66
23.87
23.10
22.36
21.65
20.97
20.31
19.67
19.05
18.46
17.89
17.34
16.80
16.29
15.79
15.31
14.85
14.40
13.97
13.55
13.15
TC
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
0.0
13.35
12.95
12.57
12.20
11.84
11.49
11.15
10.83
10.52
10.21
9.92
9.64
9.36
9.10
8.84
8.59
8.35
8.12
7.89
7.68
7.47
7.26
7.06
6.87
6.69
6.51
6.33
6.16
6.00
5.84
5.69
5.54
5.39
5.25
5.12
4.98
4.86
4.73
4.61
4.49
4.38
4.27
4.16
4.06
3.96
3.86
3.76
3.67
3.58
3.49
3.41
(k)
0.5
13.15
12.76
12.38
12.01
11.66
11.32
10.99
10.67
10.36
10.06
9.78
9.50
9.23
8.97
8.71
8.47
8.23
8.01
7.78
7.57
7.36
7.16
6.97
6.78
6.59
6.42
6.25
6.08
5.92
5.76
5.61
5.46
5.32
5.18
5.05
4.92
4.79
4.67
4.55
4.44
4.32
4.22
4.11
4.01
3.91
3.81
3.72
3.62
3.54
3.45
3.37
Appendix
Si34-803
Pressure Sensor
8. Pressure Sensor
Detected Pressure
PH = 1.38V-0.69
PL = 0.57V-0.28
PH : High pressure (MPa)
VL : Low pressure (MPa)
V : Voltage (V)
Appendix
429
Si34-803
J1
J2
J3
P1
P3
N3 U
Electronic circuit
DM
P1
P2 P3
IGBT
X10A K2
J1
L1
J2
L2
L3
J3
N3
W
X11A
According to the checking aforementioned, it is probed that the malfunction results from the
faulty inverter.The following section describes supposed causes of the faulty inverter.
1 Faulty compressor (ground leakage)
1 Faulty fan motor (ground leakage)
1 Entry of conductive foreign particles
1 Abnormal voltage (e.g. overvoltage, surge (thunder), or unbalanced voltage)
In order to replace the faulty inverter, be sure to check for the points aforementioned.
430
Appendix
Si34-803
Measuring
point
+
P3
U
2
3
4
5
6
7
8
9
10
11
12
P3
P3
U
V
W
N3
N3
N3
U
V
W
No.
V
W
P3
P3
P3
U
V
W
N3
N3
N3
Criterion
Remark
2 to 15k
Not less
than
15k
(including)
It may take
time to
determine the
resistance due
to capacitor
charge or else.
2 to 15k
Measuring
point
+
P1
J1
2
3
4
5
6
7
8
9
10
11
12
P1
P1
J1
J2
J3
N3
N3
N3
J1
J2
J3
No.
Appendix
J2
J3
P1
P1
P1
J1
J2
J3
N3
N3
N3
Criterion
Remark
2 to 15k
Not less
than
15k
(including)
2 to 15k
It may take
time to
determine the
resistance due
to capacitor
charge or else.
Measuring
point
+
-
1
2
3
4
P3
P3
P3
U
U
V
W
P3
5
6
7
8
9
10
11
12
V
W
N3
N3
N3
U
V
W
P3
P3
U
V
W
N3
N3
N3
Criterion
Remark
Not less
than
1.2V
(including)
0.3 to 0.7V
Not less
than
1.2V
(including)
Measuring
point
+
-
1
2
3
4
P1
P1
P1
J1
J1
J2
J3
P1
5
6
7
8
9
10
11
12
J2
J3
N3
N3
N3
J1
J2
J3
P1
P1
J1
J2
J3
N3
N3
N3
Criterion
Remark
Not less
than
1.2V
(including)
0.3 to 0.7V
Not less
than
1.2V
(including)
431
Si34-803
432
Appendix
Si34-803
Part 8
Precautions for New
Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................434
1.1 Outline ..................................................................................................434
1.2 Refrigerant Cylinders............................................................................436
1.3 Service Tools........................................................................................437
433
Si34-803
Outline
Refrigerant name
Composing
substances
Design pressure
Refrigerant oil
Ozone destruction
factor (ODP)
Combustibility
Toxicity
HCFC units
R-22
Single-component
refrigerant
2.75MPa (gauge pressure)
= 28.0 kgf/cm2
0.05
None
None
None
None
None
None
434
Si34-803
Steam pressure
(kPa)
Liquid
Vapor
Density
(kg/m3 )
Liquid
Vapor
Specific enthalpy
(kJ/kg)
Liquid
Vapor
Specific entropy
(kJ/KgK)
Liquid
Vapor
435
1.2
Si34-803
Refrigerant Cylinders
Cylinder specifications
2 The cylinder is painted refrigerant color (pink).
2 The cylinder valve is equipped with a siphon tube.
Siphon tube
Cylinder
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
(2) Handing of vessels
Since R-410A is high-pressure gas, it is contained in high-pressure vessels.
Although those vessels are durable and strong, careless handling can cause damage that
can lead to unexpected accidents. Do not drop vessels, let them fall, apply impact or roll
them on the ground.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same way as any other high-pressure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releases gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
436
Si34-803
1.3
Service Tools
R-410A is used under higher working pressure, compared to previous refrigerants
(R-22,R-407C). Furthermore, the refrigerating machine oil has been changed from Suniso oil to
Ether oil, and if oil mixing is occurred, sludge results in the refrigerants and causes other
problems. Therefore, gauge manifolds and charge hoses that are used with a previous
refrigerant (R-22,R-407C) can not be used for products that use new refrigerants.
Be sure to use dedicated tools and devices.
Tool compatibility
Tool
Compatibility
HFC
HCFC
R-410A
R-407C
R-22
Gauge manifold
Charge hose
Charging cylinder
Gas detector
Vacuum pump
(pump with reverse flow
preventive function)
Weighting instrument
Charge mouthpiece
{
{
{
{
{
Refrigerant recovery
device
Refrigerant piping
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
Copper tube material and thickness
Pipe size
6.4
9.5
12.7
15.9
19.1
22.2
25.4
28.6
31.8
38.1
44.5
Material
O
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Ve-up
R-407C
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.2
1.4
1.6
Material
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
1/2H
Ve-up11
R-410A
Thickness
t (mm)
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.1
1.4
1.6
* O: Soft (Annealed)
H: Hard (Drawn)
437
Si34-803
1. Flaring tool
Flare gauge
Specifications
2 Dimension A
Unit:mm
Nominal size
A +00.4
Tube O.D.
Do
Class-2 (R-410A)
Class-1 (Conventional)
1/4
6.35
9.1
9.0
3/8
9.52
13.2
13.0
1/2
12.70
16.6
16.2
5/8
15.88
19.7
19.4
3/4
19.05
24.0
23.3
Differences
2 Change of dimension A
Dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
438
Si34-803
2. Torque wrench
Specifications
2 Dimension B
Nominal size
1/2
5/8
Unit:mm
Class-1
24
27
Class-2
26
29
Previous
24
27
Dimension B
Specifications
2 Discharge speed
50 l/min (50Hz)
60 l/min (60Hz)
2 Suction port UNF7/16-20(1/4 Flare)
UNF1/2-20(5/16 Flare) with adapter
Differences
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
439
Si34-803
4. Leak tester
Specifications
2 Hydrogen detecting type, etc.
2 Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2 Offers high rust resistance and stability over long period of time.
Differences
2 Can be used for R-410A and R-22 units.
Specifications
2 High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
2 Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
2 1/4" 5/16" (2min 2.5min)
2 No oil is used in pressure test of gauges.
For prevention of contamination
440
Si34-803
2 Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
2 Change in pressure
2 Change in service port diameter
2
2
2
Specifications
Working pressure 5.08 MPa (51.8 kg/cm2)
Rupture pressure 25.4 MPa (259 kg/cm2)
Available with and without hand-operate valve that prevents refrigerant from outflow.
2
2
2
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
2 Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
2 The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
441
Si34-803
Specifications
2 High accuracy
TA101A (for 10-kg cylinder) = 2g
TA101B (for 20-kg cylinder) = 5g
2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2 Measurement is based on weight to prevent change of mixing ratio during charging.
Specifications
2 For R-410A, 1/4" 5/16" (2min 2.5min)
2 Material is changed from CR to H-NBR.
Differences
2 Change of thread specification on hose connection side (For the R-410A use)
2 Change of sealer material for the HFCs use.
442
Si34-803
Index
A
A0 .........................................................................260
A1 .........................................................................261
A3 .........................................................................262
A6 .................................................................264, 265
A7 .........................................................................268
A8 .........................................................................270
A9 .........................................................................271
Abnormal Discharge Pipe Temperature ...............296
Abnormal Outdoor Fan Motor Signal ...................298
Abnormal Power Supply Voltage .........................270
Actuation of High Pressure Switch .......................284
Actuation of Low Pressure Sensor .......................286
Address Duplication of Centralized Controller .....338
Address Duplication, Improper Setting .................350
AF .........................................................................273
AJ .........................................................................274
Applicable range of Field setting ..........................201
F3 ........................................................................ 296
F6 ........................................................................ 297
Failure of Combination (Between Indoor unit PC
Board and Fan PC Board) ............................ 279
Failure of Transmission (Between Indoor unit PC
Board and Fan PC Board) ............................ 275
Fan Motor (M1F) Lock, Overload ........................ 264
Faulty Field Setting after Replacing Main PC Board or
Faulty Combination of PC Board .................. 322
Field Setting ........................................................ 197
Functional Parts Layout ........................................ 87
RXYQ10P(A) .................................................. 89
RXYQ12P(A) .................................................. 90
RXYQ14P(A), 16P(A), 18P(A) ........................ 91
RXYQ5P(A) .................................................... 87
RXYQ8P(A) .................................................... 88
C
C1 .........................................................................275
C4 .........................................................................277
C5 .........................................................................278
C6 .........................................................................279
C9 .........................................................................280
CC ........................................................................281
Check 3 ................................................................360
Check 4 ................................................................361
Check No. 1 .........................................................359
Check No. 2 .........................................................359
Check Operation not Executed ............................328
CJ .........................................................................282
Compressor Motor Overcurrent/Lock ...................290
Cool / Heat Mode Switching .................................226
Current Sensor Malfunction .................................300
H
H7 ........................................................................ 298
H9 ........................................................................ 299
I
Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller ............. 336
Improper Combination of Optional Controllers for
Centralized Control ...................................... 348
Injection Control (only for RXYQ5P(A)) ............... 156
Inverter Compressor Abnormal ........................... 310
Inverter Compressor Motor Lock ......................... 288
Inverter Current Abnormal ................................... 312
Inverter Over-Ripple Protection ........................... 319
Inverter Start up Error ......................................... 314
J2
J3
J5
J6
J7
J9
JA
JC
E1 .........................................................................283
E3 .........................................................................284
E4 .........................................................................286
E5 .........................................................................288
E6 .........................................................................290
E7 .........................................................................291
E9 .........................................................................294
Emergency Operation ..........................................158
Error of External Protection Device ......................260
L4 ........................................................................ 308
L5 ........................................................................ 310
L8 ........................................................................ 312
L9 ........................................................................ 314
LC ........................................................................ 316
List of Electrical and Functional Parts ................. 406
Indoor Unit .................................................... 412
Outdoor Unit ................................................. 406
Outdoor Unit - 60Hz ...................................... 409
Index
........................................................................ 300
........................................................................ 301
........................................................................ 302
........................................................................ 303
........................................................................ 304
........................................................................ 305
........................................................................ 306
........................................................................ 307
Si34-803
M
M1 ........................................................................345
M8 ........................................................................346
MA ........................................................................348
Malfunction code indication by outdoor unit
PC board .......................................................256
Malfunction of Capacity Determination Device ....274
Malfunction of Discharge Pipe Thermistor
(R3, R31~33T) ..............................................301
Malfunction of Drain Level Control System
(S1L) .............................................................262
Malfunction of High Pressure Sensor ...................306
Malfunction of Humidity Sensor System ..............281
Malfunction of Inverter Radiating Fin Temperature
Rise ...............................................................308
Malfunction of Inverter Radiating Fin Temperature
Rise Sensor ..................................................320
Malfunction of Liquid Pipe Thermistor (R6T) ........304
Malfunction of Low Pressure Sensor ...................307
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E) ...................................................271
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E, Y2E) ..........................................294
Malfunction of Outdoor Unit Fan Motor ................291
Malfunction of Subcooling Heat Exchanger Gas Pipe
Thermistor (R5T) ...........................................305
Malfunction of Swing Flap Motor (M1S) ...............268
Malfunction of System, Refrigerant System Address
Undefined ......................................................343
Malfunction of Thermistor (R1T) for Suction Air ...280
Malfunction of Thermistor (R2T) for
Heat Exchanger ............................................277
Malfunction of Thermistor (R2T, R7T) for
Suction Pipe ..................................................302
Malfunction of Thermistor (R3T) for Gas Pipes ....278
Malfunction of Thermistor (R4T) for Outdoor Unit Heat
Exchanger .....................................................303
Malfunction of Thermostat Sensor in Remote
Controller ......................................................282
Malfunction of Transmission Between Centralized
Controller and Indoor Unit .............................339
Malfunction of Transmission Between Indoor and
Outdoor Units in the Same System ...............335
Malfunction of Transmission Between
Indoor Units ...................................................329
Malfunction of Transmission Between Inverter and
Control PC Board ..........................................316
Malfunction of Transmission Between Main and
Sub Remote Controllers ................................334
Malfunction of Transmission Between Optional
Controllers for Centralized Control ................346
Malfunction of Transmission Between
Outdoor Units ................................................332
Malfunction of Transmission Between Remote
Controller and Indoor Unit .............................331
MC ........................................................................350
Monitor Mode .......................................................224
ii
O
Operation Lamp Blinks ........................................ 353
Outdoor Air Processing Unit-Field Setting ........... 209
Outdoor Unit PC Board Layout ........................... 196
P
P1 ........................................................................ 319
P4 ........................................................................ 320
PC Board Defect ................................. 261, 283, 345
Piping Installation Point ....................................... 423
The Example of a Wrong Pattern ................. 424
PJ ........................................................................ 322
Power Supply Insufficient or
Instantaneous Failure ................................... 325
Procedure and Outline ........................................ 181
R
Refrigerant Circuit ................................................. 78
FXMQ125MFV1~250MFV1 ............................ 86
RXYQ10P(A), 12P(A) ..................................... 82
RXYQ14P(A), 16P(A), 18P(A) ........................ 84
RXYQ5P(A) .................................................... 78
RXYQ8P(A) .................................................... 80
Refrigerant Flow for Each Operation Mode ........... 92
RXYQ10P(A), 12P(A) ................................... 100
RXYQ14P(A), 16P(A), 18P(A) ...................... 104
RXYQ5P(A) .................................................... 92
RXYQ8P(A) .................................................... 96
Refrigerant Overcharged ..................................... 297
Reverse Phase, Open Phase .............................. 324
S
Setting by push button switches .......................... 218
Symptom-based Troubleshooting ....................... 242
System is not Set yet .......................................... 342
T
The Example of A Wrong Pattern ....................... 424
Troubleshooting
(OP: Central Remote Controller) .................. 345
Troubleshooting
(OP: Unified ON/OFF Controller) ................. 353
U
U0 ........................................................................ 323
U1 ........................................................................ 324
U2 ........................................................................ 325
U3 ........................................................................ 328
U4 ........................................................................ 329
U5 ........................................................................ 331
U7 ........................................................................ 332
U8 ........................................................................ 334
U9 ........................................................................ 335
UA ....................................................................... 336
UC ....................................................................... 338
UE ....................................................................... 339
UF ....................................................................... 342
UH ....................................................................... 343
Index
Si34-803
C
Centralized Control Group No. Setting .................210
BRC1C Type .................................................210
BRC4C Type .................................................211
BRC7C Type .................................................211
BRC7E Type ..................................................211
Group No. Setting Example ...........................211
Check No. 1 .........................................................359
Check No. 2 .........................................................359
Check Operation not Executed ............................328
Compressor Motor Overcurrent/Lock ...................290
Contents of Control Modes ..................................212
How to Select Operation Mode ......................213
Control of Outdoor Air Processing Unit (Unique
Control for Outdoor Air Processing Unit) ......174
Discharge Air Temperature Control ...............175
Selection of Operation Mode (by suction air
thermostat) .......................................174
Current Sensor Malfunction .................................300
D
Display Under Centralized Control Blinks
(Repeats Double Blink) .................................358
Display Under Centralized Control Blinks
(Repeats Single Blink) ..................................355
Drain Level above Limit .......................................273
Drain Pump Control .............................................165
When the Float Switch is Tripped and AF is
Displayed on the Remote
Controller ..........................................166
When the Float Switch is Tripped During Heating
Operation ..........................................166
When the Float Switch is Tripped while the
Cooling Thermostat is OFF ...............165
When the Float Switch is Tripped While the
Cooling Thermostat is ON ................165
E
Error of External Protection Device ......................260
Example of connection (R-410A Type) ................425
F
Failure of Combination (Between Indoor unit PC
Board and Fan PC Board) ............................279
Failure of Transmission (Between Indoor unit PC
Board and Fan PC Board) ............................275
Drawings & Flow Charts
I
Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller ............ 336
Improper Combination of Optional Controllers for
Centralized Control ...................................... 348
Inverter Compressor Abnormal ........................... 310
Inverter Compressor Motor Lock ......................... 288
Inverter Current Abnormal ................................... 312
Inverter Over-Ripple Protection ........................... 319
Inverter Start up Error ......................................... 314
L
Louver Control for Preventing Ceiling Dirt ........... 167
Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure ............. 323
M
Malfunction of Capacity Determination Device ... 274
Malfunction of Discharge Pipe Thermistor
(R3, R31~33T) ............................................. 301
Malfunction of Drain Level Control System
(S1L) ............................................................ 262
Malfunction of High Pressure Sensor .................. 306
Malfunction of Humidity Sensor System ............. 281
Malfunction of Inverter Radiating Fin Temperature
Rise .............................................................. 308
Malfunction of Inverter Radiating Fin Temperature
Rise Sensor ................................................. 320
Malfunction of Liquid Pipe Thermistor (R6T) ....... 304
Malfunction of Low Pressure Sensor .................. 307
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E) .................................................. 271
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E, Y2E) ......................................... 294
Malfunction of Outdoor Unit Fan Motor ............... 291
Malfunction of Subcooling Heat Exchanger Gas Pipe
Thermistor (R5T) .......................................... 305
Malfunction of Swing Flap Motor (M1S) .............. 268
Malfunction of System, Refrigerant System Address
Undefined ..................................................... 343
iii
Si34-803
O
Operation Lamp Blinks .........................................353
Operation of The Remote Controllers Inspection /
Test Operation Button ...................................250
Outdoor Unit PC Board Layout ............................196
S
Self-diagnosis by Wired Remote Controller ........ 246
Self-diagnosis by Wireless Remote Controller .... 247
Setting of Low Noise Operation and Demand
Operation ..................................................... 231
Image of operation in the case of A ...... 232, 234
Image of operation in the case of
A and B .................................... 232, 234
Image of operation in the case of B ...... 232, 234
Simplified Remote Controller .............................. 199
BRC2A51, BRC2C51 .................................... 199
System is not Set yet .......................................... 342
T
Test Operation .................................................... 180
Thermostat Sensor in Remote Controller ............ 168
Cooling .......................................................... 168
Heating ......................................................... 169
Troubleshooting
(OP: Central Remote Controller) .................. 345
Troubleshooting
(OP: Unified ON/OFF Controller) ................. 353
Troubleshooting by Remote Controller ............... 245
W
Wired Remote Controller ..................................... 197
Wireless Remote Controller - Indoor Unit ........... 198
BRC4C type .................................................. 198
BRC7C type .................................................. 198
BRC7E type .................................................. 198
Wiring Diagrams for Reference ........................... 375
Field Wiring ................................................... 385
Indoor Unit .................................................... 391
Outdoor Unit ................................................. 375
R
Refrigerant Circuit ..................................................78
RXYQ10P(A), 12P(A) ......................................83
RXYQ14P(A), 16P(A), 18P(A) .........................85
RXYQ5P(A) .....................................................78
RXYQ8P(A) .....................................................81
Refrigerant Flow for Each Operation Mode ............92
RXYQ10P(A), 12P(A) ....................................100
RXYQ14P(A), 16P(A), 18P(A) .......................104
RXYQ5P(A) .....................................................92
RXYQ8P(A) .....................................................96
iv
Warning
Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
JMI-0107
JQA-1452
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Specifications, designs and other content appearing in this brochure are current as of June 2008 but subject to change without notice.
Si34-803
Printed in Japan 06/2008 AK