OP2100.1.1.5.R1ENG
ALIAMAG
Electromagnetic Flowmeter
Model AMC2100 Series
Operation Manual
URL: http://www.alia-inc.com
E-mail: alia@alia-inc.com
OP2100.1.1.5.R1ENG
OP2100.1.1.5.R1ENG
Index
1. Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
2.Installation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
3.1 Power and signal output connected line (Compact and separate mode) - - - - - - - - - - - - - -
3.5 Example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
OP2100.1.1.5.R1ENG
1. Sensor
EM Flowmeter composed by sensor and Converter, be compact version or separate version, there are several
specification of sensor as follow:
98
60
48
Size
Standard
Pressure
(mm)
Kg/cm2
Liner Material
FEP / PFA
Neoprene
Polyurethane
Dimensions (mm)
PTFE
6
10
15
90
145
95
155
105
160
115
166
140
180
40
150
190
50
165
201
185
220
200
235
220
254
250
284
150
20
25
32
40
200
65
80
100
125
250
16
150
300
285
314
200
350
340
369
250
400
395
430
445
480
505
540
500
565
600
550
615
640
670
700
780
800
300
450
350
400
450
500
10
600
600
700
700
895
910
800
800
1015
1020
900
900
1115
1120
1000
1000
1230
1230
1200
1200
1405
1450
1400
1400
1630
1560
1600
1830
1770
1800
1800
2045
2040
2000
2000
2265
2250
1600
OP2100.1.1.5.R1ENG
Size
Dimensions (mm)
mm
Inch
25
1"
90
67
142
32
1-1/4"
76
152
40
1-1/2"
87
160
50
2"
110
100
175
65
2-1/2"
120
120
195
80
3"
130
135
210
100
4"
145
155
230
125
5"
160
185
260
150
6"
175
210
285
200
8"
200
265
340
100
Tie-rod
Nut
Packing
Flange
OP2100.1.1.5.R1ENG
2. Installation
When you design the tube, please consider following items:
T - Tube
ELBOW 90
> 5D
> 5D
> /2
Grove Valve
> 10D
Generally tube installation, the flowmeter Upstream could try to stay 5D-10D ,Downstream 2D-5D.
c. Pipe design should make sure no air bubble in the flowmeter position.
F:
123 . 4 m3 /H
F:
5 6. 7 m/ S
T: 123 4 .56 7 8 m3
A MC 30 00 S e ri es
SET
F:
123 . 4 m 3/H
F:
5 6. 7 m/ S
T: 123 4. 56 78 m 3
A M C 30 00 S e ri es
SET
ESC
F: 123.4 m3 /H
F: 56.7 m/S
T: 12 34.5678 m3
AMC 3000 Seri es
SET
F: 123. 4 m3 /H
F: 56.7 m/S
T: 12 34.5 678 m3
AMC 3000 Seri es
ESC
SE T
ESC
ESC
Exhaust valve
>3m
Horizontal install, the electrode position A.B should on the right and left side.
e. Transportation
When you moving, please remember DO NOT use rope through the flowmeter tube, it may cause Liner inside
broken.
Please DO NOT use your hand or rope to hang on Converter or wiring box, if Flowmeter size is bigger than 80mm,
because the material of converter and wiring box is tender aluminum, it cant stand huge weight.
f. Grounding measure
Grounding
Ring
OP2100.1.1.5.R1ENG
F
U
S
E
I+
I-
P+ R+
P- RP-
L N
1 .4 ~ 20mA output +
2.4~ 20mA output -
3. Pulse output +
4. Pulse output 5 . RS485 output +
6. RS485 output -
Power supply
90 ~ 260V AC
50/60Hz
or
24VDC
1
+
3
-
mA
Load
4~20mA Output
( Hart protocol)
Load
Modbus protocol
Pulse (Frequency)
Output
RS485 Output
OP2100.1.1.5.R1ENG
Coil
Electrode
Sensor
AM F500
AM F900
series
70 mm
123.456 m3
Key
Name
Setting
Up
Right
Button
Sign
ENT
150 mm
150 mm
+0.000 m3/h
Move
OP2100.1.1.5.R1ENG
Display
Unit sign
Unit
Totalizer
L, M3, G , kg, T
Totalizer+
+
Totalizer
Velocity
m/s
Flowrate
m3/h
% of Full Scale
FS%
Line 1
Line 2
mA output
value
Frequency
Description
= + ()
mA
Hz
3.5 Example
If you need Line 1 display from m3/h turn to %
123.456 m3
+0.0000m3/h
V
123.456 m3
+0.0000m3/h
123.456 m3
+0.0000 %FS
Press
ENT
123.456 m3
+0.0000m3/h
or
V
ENT
1
2
123.456 m3
123.450 m3
123.400 m3
EXIT
HELP
Zero window.
.current totalizer value
1.last totalizer value
2.the time before last time totalizer value
Please selected CLR and press enter,doing the zero operation
CLR
ENT
Clear
NO
Total
YES
ENT
to confirm
OP2100.1.1.5.R1ENG
123.456 m3
ENT
+0.1234m3/h
V
ENT
OPERATIONS
SET
ZERO
or
ENT
ENT
to confirm
ESC
ENT
ZERO
NO
to confirm .
YES
ENT
Condition OK ?
NO
YES
ENT
HELP
ENT
Zero Adjustment.
Zero
Triming
ENT
Esc
ENT
OPERATIONS
SET
ZERO
ENT
ESC
ENT
123.456 m3
+0.0000m3/h
V
3.8 Check for power off message
123.456 m3
+0.0000m3/h
button to select
V
ENT
ON
OFF
2008/04/23
13:30:55
Q:
:
1.0234 m3/h
4.321 m3
10
Q:
OP2100.1.1.5.R1ENG
123.456 m3
+0.0000m3/h
V
ENT
OPERATIONS
SET
ZERO
ESC
ENT
Password
ENT
0000
Empty Detect
Language
ENT
ENT
PV Units
Empty Limit(%)
ENT
Communication
ENT
ENT
URV
MODBUS Type
ENT
ENT
ENT
Switch Func
Baudrate
ENT
Liter/Pulse
ENT
ENT
Parity
ENT
Pulse Width
ENT
Alarm
Select
ENT
Modbus Address
ENT
Low Cutoff(%fs)
UPPER-Alarm
ENT
DATE (yy-mm-dd)
ENT
ENT
Damping(s)
TIME (hh-mm-ss)
ENT
Hydro-State
ENT
ENT
Direction
ENT
11
HART Address
OP2100.1.1.5.R1ENG
ENT
Password
Password
****
1111
Sensor NO.
Sensor NO.
ENT
ENT
Diameter (mm)
Diameter (mm)
ENT
ENT
Sensor Factor
Sensor Factor
ENT
ENT
Output Check
Output Check
ENT
ENT
Loop
Restore Shipping
ENT
Restore Shipping
Test
ENT
ENT
Pulse
Convertor NO.
Test
ENT
ENT
Coil
Test
Convertor Factor
ENT
Zero Factor
ENT
4mA
Trim
ENT
20mA Trim
12
OP2100.1.1.5.R1ENG
123.456 m3
+0.0000m3/h
ENT
V
ENT
OPERATIONS
SET
ZERO
or
ESC
ENT
Password
0000
ENT
Language
Language
CHINESE ENGLISH
Press
or
ENT
PV Units
m3/h L/h GPH
Kg/h t/h GPM
L/min m3/min
4: t/h
5: GPM
ENT
URV
m3/h
70.0000
Flow Range
Setting Flow Range, thats mean 4-20mA and Pulse, frequency output max. Value
Press
button to move, Press to change the Value
ENT
Switch
Contact output
Func
Default
Freq
Pulse
Alarm
Press
or
1. Default
4. Alarm
ENT
Liter/Pulse
(L/P)
0.1000
Pulse output
Each pulse match the Liter value (Liter/Pulse)
Press button to move, Press to changed the Value
ENT
Pulse width
Pulse Width
1ms
10ms
100ms 1s
20ms
50%
Press
or
ENT
Low
Cutoff (%fs)
0.0
ENT
13
OP2100.1.1.5.R1ENG
Damping (s)
01
ENT
Hydro-State
Hydro State
Normal
Waved
Press
or
button to selected the Hydro-State
Normal: for general application
Waved: For fluid in wave states
ENT
ENT
Response time
Press
button to move, Press
to change the value
Response time range: 00~99, Adjust flowmeter response time.
ENT
Direction
Direction
Fwd.
Press or
1. Forward
Bid.
ENT
Empty Detect
NO
Press
YES
or
ENT
Press
50
ENT
Communication
OFF
ON
Communication
Press
or
HART
Address
ENT
MODBUS
Type
RTU
ASCII
MODBUS Mode
Press
or
ENT
14
Baudrate
1200
4800
19200
2400
9600
38400
OP2100.1.1.5.R1ENG
RS485 Speed
Press
or
ENT
Parity
Parity Type
Press or
button to select the parity type
1. None 2. Odd 3. Even
ENT
MODBUS Address
001
MODBUS address
Press
ENT
DATE (yy-mm-dd)
Date Setting
Press
08-01-10
ENT
TIME (hh:mm:ss)
Time Setting
Press
button to move, Press
button to change the digit.
button for 5 seconds, then it will go back to the normal display.
Pls press
ENT
17:09:49
HART Address
Address
00
Press
or
ENT
DATE (yy-mm-dd)
Date Setting
Press
08-01-10
ENT
TIME (hh:mm:ss)
Time Setting
Press
button to move, Press
button to change the digit.
button for 5 seconds, then it will go back to the normal display.
Pls press
ENT
17:09:49
15
OP2100.1.1.5.R1ENG
ZERO
ESC
ENT
Password
1111
ENT
Sensor No.
Sensor NO.
Press
A7082106
ENT
Diameter
Diameter (mm)
Press
0065
ENT
Sensor Factor KS
Sensor Factor
00.94100
KS is the original factory rectified factor, please dont change it unless professional or technical staff
button to change the value
Press button to move, Press
ENT
Output Calibration
Output Check
NO
Press
or
button to choose YES select if needs calibration
Choose NO jump to Restore Shipping
YES
ENT
Loop
Test
16
Press
or
button to select the simulated output value
4 . 8 . 12 . 16 . 20
100
20
ENT
Pulse Test
1
1000
10
2000
5000
ENT
Coil
Test
ON
XJY
ENT
Restore
NO
Shipping
YES
16
OP2100.1.1.5.R1ENG
ZERO
ESC
ENT
Password
****
ENT
Sensor No.
Sensor NO.
Press
A7082106
ENT
Diameter (mm)
Diameter
Press
0065
ENT
Sensor Factor KS
Sensor Factor
00.94100
KS is the original factory rectified factor, please dont change it unless professional or technical staff
button to change the value
Press button to move, Press
ENT
Output Calibration
Output Check
NO
Press
or
button to choose YES select if needs calibration
Choose NO jump to Restore Shipping
YES
ENT
Loop
Test
16
20
Press
or
button to select the calibration type
4 . 8 . 12 . 16 . 20
ENT
Pulse Test
1
10
1000 2000
100
5000
Press
or
button to select the calibration type
1 . 10 . 100 . 1000 . 2000 . 5000
ENT
Coil
Test
ON
XJY
ENT
17
Restore
Shipping
NO
OP2100.1.1.5.R1ENG
YES
or
ENT
Converter No.
Converter NO.
Press
B0000000
ENT
Converter
Factor
01.05988
Converter Factor KC
Press
ENT
Coil
Current (A)
0.1654
Ic is the tested current of the converter when out of factory, please dont change it unless agent or
professional technical staff.
button to move, Press button to change the value
Press
ENT
Coil
3.125
Freq (Hz)
6.25
33
Press
or
button to select the coil frequency
Original setting Value: 6.25
ENT
Zero
Factor
Press
- 9.9
ENT
4mA
Trim
Press
4.000
ENT
20mA
Trim
Press
button to move, Press
to change the value
button for 5 seconds, then it will go back to the normal display.
Pls press
ENT
20.000
18