Spaces to Be Pressurised
5.1.1
5.1.2
5.1.3
5.1.4
5.1.5
Stair 3
Stair 3 is constructed from Ground Floor to fifth floor. There is a single leaf door (1mx2.1m (H))
separating the staircase and accommodation areas.
5.2
Code of Design
5.2.1
5.2.2
BS EN 12101-6:2005.
Uniform Building By Law
5.3
5.3.1
Design condition: In the event of fire, all the following doors open between
~Stair/lobby on the fire affected floor;
~Stair/lobby on the floor below fire affected floor;
~Lobby/accomodation area on the fire affected floor (minimum air velocity=2m/s);
~Final exit door.
5.3.1.1.1 Staircase 1 - Leakage Through Closed Doors
There are 34 nos. of 1mx2.1m(H) doors opening into the pressurised staircase and 1 no. of
1mx2.1m(H) door opening outward from pressurised staircase at ground floor.
a) Leakage area for 0.8mx2m(H) single leaf door opening
into pressuried space
Leakage area for 0.8mx2m(H) single leaf door opening
opening outwards from pressuried space
Crack length for 0.8mx2m(H) door
=
=
0.01 m2
0.02 m2
=
=
=
=
=
=
(0.8+2)2
5.6m
(1+2.1)2
6.2m
(6.2/5.6)0.01
0.0111 m2
(6.2/5.6)0.02
0.022 m2
=
=
=
0.06 m2
0.83x((0.06x41)-2+0.1-2)-1/2x45(1/2)
0.556 m3/s
=
=
=
1.110x(1x2.1)/[(1x2.1)+(1x2.1)+(2x0.03)+0.06]
1.11x0.486
0.540 m3/s
0.540+0.521
5.3
1.061 m3/s
=
=
1.061/(0.7x2.1)
0.722 m/s
(but < 2m/s as recommended)
=
=
(2-0.722)x(0.7x2.1)
1.879 m3/s
=
=
1.879x(1/0.486)
3.866 m3/s
= 3.866+1.11
m3/s
= 4.976
(10544 cfm)
=
=
4.976/3
1.659 m3/s
=
=
1.659+0.521
2.180 m3/s
2.180/(1.4x2.1x2)
0.371 m/s
=
=
=
=
(0.75-0.371)x(1.4x2.1x2)
2.229 m3/s
2.229+0.521
2.750 m3/s
(5827 cfm)
5.5
5.3.2
=
=
=
=
(0.011m2x3)+3(1mx2.1m)
6.33 m3/s
6.33 x1.15
7.283 m3/s
(15432 cfm)
5.4
=
=
2x2.1x1.4x0.75
4.410 m3/s
(9344 cfm)
5.6
5.5