Bill of Quantities

ROYAL AUDIT AUTHORITY TRAINING CENTRE, TSIRANG


Royal Audit Authority
Name of work: Electrification & Allied Works
Sub Title: Main Building
S.No.

1
1a
1b
1c

2
2a
2b

DESCRIPTION

BSR Ref

QTY.

UNIT

175
154
168

Point
Point
Point

6
12

Point
Point

WIRING
Providing Wiring for the light point with 2x1.5sq. mmPVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for light point . Including providing accessories,
Platinum brand switches 6A 1-gang / 2gang White colour Code CQ000501/02 for front cover. 6A 1 gang
switch Code CQAT0006, Outer Plate for 1 module Code CQAT0501 for 2 module Code CQAT0502. Inner
Plate for 1 module Code CQAT1501 for 2 module Code CQAT1502. Platinum brand switches 6A 4-gang
White colour Code CQ000504 for front cover. 6A 1 gang switch Code CQAT0006, Outer Plate for 4 module
Code CQAT0504. Inner Plate for 4 module Code CQAT1504 Havells/equivalent make. Use maximum 3 CFL
fixture by 1 switch. Maximum 2single tube light fitting by 1 switch and double tube light fitting by 1 switch.

WC0300 Short Point


WC0301 Medium Point
WC0302 Long Point
Providing Wiring for the 2-way light point with 2x1.5sq. mm PVC insulated multistrand copper conductor
cable in recessed 25mm dia HDPE pipe I/c all accessories as required for twin control light point.
WC0371 Medium point
WC0372 Long point

Page 1 of 22

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

DESCRIPTION

QTY.

WC0381

Providing Wiring for the light point with 2x2.5sq. mm PVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for light circuit wiring .

1350

WC0381

Providing Wiring for points in excess length above long points with 2x1.5sq. mm PVC insulated multistrand
copper conductor cable in recessed 25mm dia HDPE pipe I/c all accessories as required.

238

WC0381

Providing Wiring for Computer point with 2x2.5sq. mm PVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for Computer circuit wiring .

1150

WC0400

Providing Wiring for the power point with 2x4sq. mm PVC insulated multistrand copper conductor cable in
recessed 25mm dia HDPE pipe I/c all accessories as required for power wiring .

1890

Providing Wiring for Split Type Air Conditioner with 1.1kV grade 2x6sq. mm PVC insulated multistrand
WC0410 copper conductor cable in recessed HDPE Pipe including connections, and I/c all accessories as required from
SDB to AC Point as per drawing.

165

UNIT

SUB-TOTAL FOR WIRING


B
1

FITTING & ACCESSORIES


Supplying of Tubelight fitting surface mounted 1x36w/40w fluorscent. Code No.LHIF 71104011 White Havells/Equivalent.

15

IL0201

Supplying of Tubelight fitting recess mounted 1x36w/40w fluorscent. Code No.LHCF 1136811 White Havells/Equivalent.

209

M/R

Supplying of Surface mounted ceiling fitting square decorative downlighter with HF electronic ballast and
translucent diffuser, pre-fitted with flat profile, for 1x25W CFL lamp LONON SQUARE White Code
No.LHDC70125670 - Havells/Equivalent.

IL0170

Page 2 of 22

Each

Each

Each
53

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

DESCRIPTION

QTY.

M/R

Supplying of Recess mounted ceiling fitting square decorative downlighter with HF electronic ballast and
translucent diffuser, pre-fitted with flat profile, for 1x25W CFL lamp LONON SQUARE White Code
No.LHOC68125370 - Havells/Equivalent.

41

M/R

Supplying of decorative wall light fixture foe 1x15W CFL White Code No.LHDL 06160099
Havells/Equivalent

101

M/R

Supplying of Recessed modular downlighter with drop glass for 1x70W MH DE-White Code
No.LHOM74170399 Havells/Equivalent.

6
7

10

11

12

13

14

Each

SS0221 Supplying of PVC Batten holder for 1 x 15W CFL lamp


FN0002

Supplying of ceiling fan 240volt AC 1200rpm with all accessories such as down rod, sweep 3nos. Canopy
2nos. Condenser, fan body & regulator etc. complete as required. - 1200mm sweep-SQCA appd.

77

AC0016

Providing & fixing 1.5tonne, Split Type Air Conditioner complete with all accessories including drilling holes
for pipes, testing and commissioning etc. whatever is required at site to complete this job. SQCA appd.

SS0076

Supplying and fixing of RJ-11 Telephone Socket 1 gang shutter jack type Code No.CQAT 0355 white Havells / Crabtree/Equivalent

57

SS0177

Supplying and fixing of


Havells/Crabtree/Equivalent

113

SS0205

Supplying and fixing 6 Amp 6pin Switch Socket Combined shuttered having rectangle edge (Crabtree/
equivalent).

SS0220

Supplying and fixing 16 Amp 6pin Switch Socket Combined shuttered having rectangle edge (Crabtree/
equivalent).

146

MR

Supplying and fixing 25A Starter, 25A Socket, 25A plug white for 1x2500W Split Type Air Conditioner
(Crabtree/ equivalent).

RJ-45

Code

No.ACPKMCW451

Computer

Page 3 of 22

Socket

white

UNIT

Each

Each
Each
Each

Each

Each

Each

Each

Each

Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

15

16

BSR Ref

DESCRIPTION

QTY.

SS0220

Supplying and fixing 16 Amp 6pin Switch Socket Combined having both Flat & Round Pin White for
Computer points (Crabtree/ equivalent).

65

SS0220

Supplying and fixing 3Pin 16 Amp Modular Recepticle Switch Socket Combined to be flush mounted on floor
for Computer points (Crabtree/ equivalent).

16

UNIT

Each

Each

17

PO0015 Providing & laying 25mm dia HDPE pipe for Telephone.

480

18

PO0015 Providing & laying 25mm dia HDPE pipe for LAN.

1150

19

LS0126 TLF lamp 36/40W

224

Each

20

MR

CFL Lamp 15W

104

Each

21

MR

CFL Lamp 25W

94

Each

SUB-TOTAL FOR FITTING & ACCESSORIES


C
1

ERECTION OF FITTING & ACCESS.


Installation, testing & commissioning of prewired fluorscent fittings of all types complete with all accessories
and tubes etc. directly on wall / ceiling surface /recess mounted etc. as required.

224

EI0002

Erection of compact fluorscent fitting/wall brackets /ceiling fitting/ outdoor fittings/ Batten holder /musical
call bell etc. I/c fixing of lamp connection, testing etc. as required.

198

EI0096

Installation, testing and commissioning of all size ceiling fan and regulator including wiring the down rod of
standard length upto 300mm with 1.5sq.mm PVC insulated copper conductor

77

EI0110

Supplying extra down rod of G.I pipe (heavy duty) 15mm dia, 100mm long with 2x1.5sq.mm PVC insulated
single core copper conductor cable, painting, cutting and threading etc. as required.

77

EI0041

Page 4 of 22

Each

Each

Each

Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

DESCRIPTION

QTY.

SUB-TOTAL FOR ERECTION of FITT & ACCE


D
1

SUBMAIN & CONTROL GEAR


Supplying of following sizes of 1.1 KV grade aluminium conductor PVC insulated and PVC sheathed
armoured power cable.

Page 5 of 22

UNIT

RATE (Nu.)

AMOUNT (Nu.)

S.No.

1a

1b

1c

BSR Ref

DESCRIPTION

QTY.

PC0150

3-1/2Cx25mm2 PVC Insulated UG cable Armoured AYFY from MCPB (Main control panel board) to SDB
(Sub distribution board). Actual length will be as per site condition.

195

PC0179

4Cx16mm2 PVC Insulated UG cable Armoured AYFY from MCPB (Main control panel board) to SDB (Sub
distribution board). Actual length will be as per site condition.

500

PC0123

2Cx10mm2 AYFY Computer points service connection at the SDB-5. Actual length will be as per site
condition.

48

2b

SDB's under Normal Supply


4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-1 (Ground
GB0539
Floor) (SQCA Appd)
GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)
GB0270 6Amp SPMCB
GB0272 16Amp SPMCB
GB0542

12way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-2 (Ground
Floor) (SQCA Appd)

GB0196 100Amp TP&N MCCB, 415volt. 25kA breaking capacity A.C complete (SQCA Appd)
GB0272 16Amp SPMCB

2c

GB0541

8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-3 (Ground
Floor) (SQCA Appd)

GB0196 100Amp TP&N MCCB, 415volt. 25kA breaking capacity A.C complete (SQCA Appd)
GB0272 16Amp SPMCB
GB0274 25Amp SPMCB

2d

Supplying of the following items including all accessories whether specifically mentioned or not but required
to make the Installation complete in all respect.

2a

UNIT

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-4 (First Floor)
(SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


Page 6 of 22

1
1
4
8

1
1
36

1
1
23
1

1
1

Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

GB0270 6Amp SPMCB


GB0272 16Amp SPMCB

2e

GB0542

12way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-5 (First Floor)
(SQCA Appd)

GB0196 100Amp TP&N MCCB, 415volt. 25kA breaking capacity A.C complete (SQCA Appd)
GB0272 16Amp SPMCB
GB0274 25Amp SPMCB

2f

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-6 (First Floor)
(SQCA Appd)

GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd)


GB0272 16Amp SPMCB

2g

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-7 (Second
Floor) (SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0270 6Amp SPMCB
GB0272 16Amp SPMCB

2h

GB0542

12way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-8 (Second
Floor) (SQCA Appd)

GB0196 100Amp TP&N MCCB, 415volt. 25kA breaking capacity A.C complete (SQCA Appd)
GB0272 16Amp SPMCB
GB0274 25Amp SPMCB

2i

2j

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-9 (Second
Floor) (SQCA Appd)

QTY.

UNIT

4
8

Each
Each

1
1
34
2

1
1
12

1
1
3
9

1
1
30
6

GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd)


GB0272 16Amp SPMCB

1
1
12

GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd)

1
Page 7 of 22

Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

QTY.

UNIT

for 9m Compound light.

2k

SDB's under Generator Supply


12way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-2 (Ground
GB0542
Floor) (SQCA Appd)
GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd)
GB0271 10Amp SPMCB

2l

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-2 (Ground
Floor) (SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB

2m

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-3 (Ground
Floor) (SQCA Appd)

GB0368 63Amp TP&N MCB, 415volt. (SQCA Appd)


GB0271 10Amp SPMCB

2n

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-5 (First Floor)
(SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB

2o

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-5 (First Floor)
(SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB

2p

GB0541

8way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-5 (First Floor)
(SQCA Appd)

GB0355 63Amp TP&N MCB, 415volt. (SQCA Appd)


Page 8 of 22

1
1
36

1
1
12

1
1
18

1
1
12

1
1
12

1
1

Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

GB0271 10Amp SPMCB

2q

GB0527

4way DP&N Distribution board (DIN type) with metal door, 230 volts AC SDB-5 (First Floor) (SQCA
Appd)

GB0315 32Amp DP&N MCB, 230volt. (SQCA Appd)


GB0271 10Amp SPMCB

2r

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-6 (First Floor)
(SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB

2s

GB0539
GB0368

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-8 (Second
Floor) (SQCA Appd)

GB0539

GB0539

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-8 (Second
Floor) (SQCA Appd)

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-9 (Second
Floor) (SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB

2v

GB0539

24

Each

1
1
4

1
1
12

1
1
12

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB

2u

UNIT

40Amp TP&N MCB, 415volt.(SQCA Appd)

GB0271 10Amp SPMCB

2t

QTY.

4way TP&N Distribution board (DIN type) with metal door, 415 volts AC complete for SDB-9 (Second
Floor) (SQCA Appd)

GB0368 40Amp TP&N MCB, 415volt.(SQCA Appd)


GB0271 10Amp SPMCB
Page 9 of 22

1
1
12

1
1
12

1
1
12

Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each
Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

DESCRIPTION

QTY.

GB0225

Supplying of 160A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 36kA,
4pole 415volt, A.C complete with all accessories etc. as required at the Generator Panel.

MR

Supplying of 200A TPN Changeover 4pole 415volt, A.C complete with all accessories etc. as required at the
Generator Panel.

GB0241

Supplying of 400A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 70kA,
4pole 415volt, A.C complete with all accessories etc. as required.

UNIT

Each

Each

Each

GB0009 Copper busbar chamber of size 300Amp 4x600mm including all accessories etc. at the Generator MCPB.

Set

GB0027 Copper busbar chamber of size 600Amp 4x650mm including all accessories etc. at the Normal MCPB.

Set

M/R

Providing and fixing electrical measuring instruments at the Main control panel board as per contract
document specification
- Voltmeter 0-500V - 1no.

Set

- Ammeter 0- 400A - 1no.


- Ammeter selector switch - 1no.
- Voltmeter selector switch - 1no.
- CT's and PT's
- Indicating lamps - 4no.
- HRC fuse 2A rating for avove-4no.

M/R

Providing and fixing 400A 3-Phase 4 wire system Energy Meter at the apprppriate location in consultation
with BPCL.

Set

SUB-TOTAL FOR SUBMAIN & CONTRL GEAR


E
1
1a

ROUTE MARKER
Providing and making route marker of size 600mmx600mm at bottom and 500mmx500mm at top with a
thickness of 100mm including inscription as required.
12

CL0070 With cement concrete 1:2:4, 20mm stone aggregate / Steel plate.
Page 10 of 22

each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

QTY.

UNIT

34
16

each
each

1
11
6
3
2
2

each
each
each
each
each
each

1
13
1

each
each
each

SUB-TOTAL FOR ROUTE MARKER


F
1
1a
1b

CABLE TERMINATION WITH COMPRESSION GLAND


Installation, testing and commissioning of end termination with single/double compresion gland for PVC
insulated and sheathed aluminium conductor cable of 1.1kV grade including connections etc. as required.
CL0110 6/10/16/25mm dia
CL0115 82/85mm dia
SUB-TOTAL FOR CABLE TERMINATION WITH COMPRESSION GLAND

1
1a
1b
1c
1d
1e
1f

INSTALLATION of SWITCH GEARS


Installation, testing and commissioning of TP switch fuse unit front drive four/miniature circuit breaker (DIN
type) / Moulded case circuit breaker (MCCB) complete with all accessories to accommodate on/in
prefabricated MS surface/Cubical control panel board including drilling holes, connections etc. as required.
EI0390
EI0338
EI0340
EI0425
EI0426
EI0460

25/32/40A DP MCB, 230V


40A TP&N MCB,415V
63A TP&N MCB,415V
100A TP&N MCCB,415V
125A TP&N MCCB,415V
400A TP&N MCCB,415V
SUB-TOTAL FOR INSTALN. of SWITCH GEARS

1
1a
1b
1c

INSTALLATION of DISTRIBUTION BOARD


Installation, testing and commissioning of TPN DB (DIN type) single/double door complete with all
accessories to accommodate incoming MCB/MCCB/RCCB 4pole 32/40/63A sensitivity 30/100/300mA and
outgoing SPMCB 6A/16A in prefabricated MS surface /MS cubical panel board including drilling holes,
connections etc. as required.
EI0495
EI0525
EI0535

4way DP DB
4way TPN DB
6way TPN DB
Page 11 of 22

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

1d
1e

EI0545
EI0555

DESCRIPTION

8way TPN DB
12way TPN DB

QTY.

UNIT

2
4

each
each

1.2

cu.m

each

SUB-TOTAL FOR INSTALN. of DISTRIBUTION BOARD


I

1
1a

2
2a

METAL PANEL BOARD


Providing and fixing of prefabricated panel board with minimum 50x50x6mm angle iron framework with
horizontal and vertical intermediate members of flat iron 40x6mm and 24swg sheet cover for mounting of
switchgears incoming/outgoing busbar chambers including driling holes, insulator, painting, denting, grouting
etc. as required. for MCPB.
EI0600

Floor mounted cubical control panel board of welded construction


Providing and fixing medium volt danger notice plate made of mild steel and painted with viterous enamelled
white paint on both sides, and with inscription in signal red colour written as 440V/1100V in
Dzongkha/English on front side as required on prefabricated MS surface/MS cubical control panel board on
surface including drilling holes etc. as required.

EI0610

200mmx150mmx2mm
SUB-TOTAL FOR METAL PANEL BOARD

J
1

EARTHING & LIGHTNING PROTEC.


P/F of G.I. earth conductor of size 25mmx4mm for loop earthing as required. Including horizontal and four
ET0075
vertical drops for Lightning arrestor Loop connection for earthings etc.

325

ET0121 Supplying & drawing 14SWG copper wire for loop earthing / earthing for electrical equipments.

1580

LG0002

P/F of lightning arrestor final made of 25mm dia 900mm long GI tube having five prong at top with 85mm dia
6mm thick copper plate I/c holes and spring washer etc. as required.

Page 12 of 22

M
M
M

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

QTY.

Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure with
cover plate having locking arrangement & watering pipe. (For Lightning Arrestor) NOTE: This earthing shall
ET0001 be independently looped to each other and not to be interconnected with the electrical earthing.
4

UNIT

Each
4

ET0001

Earthing with G.I earth plate 600mmx600mm x6mm thick I/c accessories & providing masonry enclosure with
cover plate having locking arrangement & watering pipe. (For General electrical earthing)

Each

SUB-TOTAL FOR EARTNG & LIGHTNING PROTEC.


K
1
1a
1b
1c

HDPE PIPE
Providing and Laying HDPE Pipe including trenching and refilling.
PO0018 50mm dia for service cable, incoming main telephone cable.
PO0022 110mm dia for service cable connection to shaft.
PO0025 225mm dia for service cable connection and incoming main BPC cable

35
100
30

M
M
M

18.00

Each

SUBTOTAL FOR HDPE PIPE


L

1
1a

COMPOUND LIGHT
Supplying of street light poles 50/60mm dia outer dia having base plate 250x250x5.4mm thick, entry hole of
40mm dia 1.1m from bottom and strude bolt as earth terminal, including providing 32mm dia MS/GI pipe for
incoming and outgoing cable connection to junction box, complete as required.
PA0003 5.5m 5.4mm thick as per drawing
OL0070

Supplying and fixing of Post Top Lantern Globe 480mm diameter HPC 16 with 1xHPL-N 80W, lamp holders,
copper wound ballast, condenser, terminal block etc. (Philips/Equivalent/SQCA appd).

Supplying and fixing of floodlight optal-1 New IP 66 suitable for 1x150W MH Code No.LHRM32115C36
OL0161 Ordering Code No.LHRM32115C99 with 1x150W Metal Halide lamp with holder, copper wound ballast,
condenser, terminal block etc. (Havells/Equivalent/SQCA appd).

Page 13 of 22

18.00

Each

Each
8.00

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

QTY.

Supplying and fixing of floodlight JETA 3 New suitable for 1x70W HPL-N Code No.LHFM04170D36
OL0146 Ordering Code No.LHFM04170D99 with 1x70W HPL-N lamp with holder, copper wound ballast, condenser,
terminal block etc. (Havells/Equivalent/SQCA appd).

UNIT

Each
6.00

Erection of street light pole 5.5m and 9m length with 40mm dia MS sleeve as inlet of power cable in cement
concrete 1:3:6, 40mm stone aggregate foundation with cement concrete base 0.47mx0.47mx75mm thick 1:4:8
including excavation, centering & shuttering and filling providing props for pole etc. complete as required.
5
5a
5b
5c

6
6a

7
7a

8
8a

9
9a

PA0020 At dead end


PA0021 At middle
PA0022 Junction of three way

4.00
24.00
4.00

Each
Each
Each

14.00

Each

32.00

Each

32.00

Each

160.00

Supplying of street light poles 50/60mm dia outer dia having base plate 250x250x5.4mm thick, entry hole of
40mm dia 1.1m from bottom and strude bolt as earth terminal, including providing 32mm dia MS/GI pipe for
incoming and outgoing cable connection to junction box, complete as required.
MR

9m pole as per drawing


Supplying of junction box fabricated with 14swg MS sheet, removal cover plate with gasket for dust and
vermin proof, 2 earthing terminals with nut, bolts and spring washer, 2 entry holes 16mm dia at bottom, 32mm
dia hole for cable entry at back, including 4 way terminal block & HRC fuse unit with fuse of 6A with locking
arrangement and finish coat painting complete with all accessories as required as per standard drawing/ /
method.

PA0105 MS junction box outdoor duty


Erection of junction box and pole light fixture including wiring with PVC insulated copper conductor cable
1.1kV grade 2x2.5sq.mm through the existing pole from junction box including erection of street light
fixtures, lamps, connection, testing etc. complete as required.
PA0050 Junction box to lamp
Supplying of following sizes of 1.1 KV grade aluminium conductor PVC insulated and PVC sheathed
armoured power cable.
PC0179 4Cx16mm2 AYFY (Procure as per site actual site measurement).
Page 14 of 22

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

9b
9c

PC0178 4Cx10mm2 AYFY (Procure as per actual site measurement).


PC0177 4Cx6mm2 AYFY (Procure as per actual site measurement).

10

GB0355 63Amp TP&N MCB, 415volt. 25k A breaking capacity A.C complete (SQCA Appd)

QTY.

UNIT

235.00
535.00

M
M

1.00

Each

11

MR

Providing & fixing Auto Timer for the compound lights Maxi Rex 4QT (Legrand).

2.00

Each

12

MR

Providing & fixing 3 power poles contactor for the compound lights PC 37 K3N (Havells).

2.00

Each

SUBTOTAL FOR COMPOUND LIGHT


M
1

FEEDER PILLAR - I
Supplying of 500A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 50kA,
GB0241
4pole 415volt, A.C complete with all accessories etc. as required.

Each

BPC STANDARD Feeder Pillar consisting of following components to be made

2
2a

Providing and fixing of prefabricated panel board with minimum 50x50x6mm angle iron framework with
horizontal and vertical intermediate members of flat iron 40x6mm and 24swg sheet cover for mounting of
switchgears incoming/outgoing busbar chambers including driling holes, insulator, painting, denting, grouting
etc. as required.
EI0600

Floor mounted cubical control panel board of welded construction

1.50

GB0029

Aluminium alloy/wrought aluminium/copper busbar chamber of size 600Amp 4x900mm including all
accessories etc. for feeder pillar.

1.00

Set

Supplying of following sizes of 1.1 KV grade aluminium conductor PVC insulated and PVC sheathed
armoured power cable.

4a

cu.m

PC0060

3-1/2Cx400mm2 PVC insulated & sheathed UG cable armoured AYFY from BPC Sub-station to Clients
Feeder Pillar. Actual length will be as per site condition.

Page 15 of 22

120

RATE (Nu.)

AMOUNT (Nu.)

S.No.

4b

4d

5
5a
5b
5c

BSR Ref

DESCRIPTION

QTY.

PC0059

3-1/2Cx300mm2 PVC insulated & sheathed UG cable armoured AYFY from Feeder Pillar to Main Control
Panel Board. Actual length will be as per site condition.

75

PC0150

3-1/2Cx25mm2 PVC Insulated UG cable Armoured AYFY from Feeder Pillar to Ex. Hostel No.2. Actual
length will be as per site condition.

65

Laying of one number PVC insulated and sheathed power cable aluminium armoured 3-1/2 core to 4 core
direct in the ground including excavation, sand cushing, protective covering and refilling the trenches etc. as
required. However actual cable length may be determined at site before procurement.
CL0002 Above 6sq.mm to 25sq.mm
CL0005 Above 150sq.mm to 300sq.mm
CL0006 Above 300sq.mm to 630sq.mm

45
70
90

m
m
m

15.00

each

Providing and making route marker of size 600mmx600mm at bottom and 500mmx500mm at top with a
thickness of 100mm including inscription as required.

6
6a

UNIT

CL0070 With cement concrete 1:2:4, 20mm stone aggregate / Steel plate.
M/R

Providing and fixing electrical measuring instruments at the Main control panel board as per contract
document specification
- Voltmeter 0-500V - 1no.

1.00

Set

Ammeter 0- 500A - 1no.


Ammeter selector switch - 1no.
Voltmeter selector switch - 1no.
CT's and PT's
Indicating lamps - 4no.
HRC fuse 2A rating for avove-4no.
SUBTOTAL FOR FEEDER PILLAR-I
N
1

FEEDER PILLAR - II
Supplying of 500A Moulded case circuit breaker (MCCB) with electronic release, breaking capacity 50kA,
GB0241
4pole 415volt, A.C complete with all accessories etc. as required.
Page 16 of 22

Each

RATE (Nu.)

AMOUNT (Nu.)

S.No.

DESCRIPTION

BSR Ref

QTY.

UNIT

cu.m

BPC STANDARD Feeder Pillar consisting of following components to be made

2
2a

Providing and fixing of prefabricated panel board with minimum 50x50x6mm angle iron framework with
horizontal and vertical intermediate members of flat iron 40x6mm and 24swg sheet cover for mounting of
switchgears incoming/outgoing busbar chambers including driling holes, insulator, painting, denting, grouting
etc. as required.
EI0600

Floor mounted cubical control panel board of welded construction

1.50

GB0029

Aluminium alloy/wrought aluminium/copper busbar chamber of size 600Amp 4x900mm including all
accessories etc. for feeder pillar.

1.00

Supplying of following sizes of 1.1 KV grade aluminium conductor PVC insulated and PVC sheathed
armoured power cable.

4
4a

4b

4c

4d

4e

5
5a
5b

Set

PC0060

3-1/2Cx400mm2 PVC insulated & sheathed UG cable armoured AYFY from BPC Sub-station to Clients
Feeder Pillar. Actual length will be as per site condition.

90

PC0055

3-1/2Cx120mm2 PVC insulated & sheathed UG cable armoured AYFY from Feeder Pillar to Hostel No.1.
Actual length will be as per site condition.

65

PC0055

3-1/2Cx120mm2 PVC insulated & sheathed UG cable armoured AYFY from Feeder Pillar to Hostel No.2.
Actual length will be as per site condition.

90

PC0053

3-1/2Cx70mm2 PVC insulated & sheathed UG cable armoured AYFY from Feeder Pillar to self Catering
Bldng. No.1. Actual length will be as per site condition.

40

PC0053

3-1/2Cx70mm2 PVC insulated & sheathed UG cable armoured AYFY from Feeder Pillar to self Catering
Bldng. No.2. Actual length will be as per site condition.

65

Laying of one number PVC insulated and sheathed power cable aluminium armoured 3-1/2 core to 4 core
direct in the ground including excavation, sand cushing, protective covering and refilling the trenches etc. as
required. However actual cable length may be determined at site before procurement.
85
135

CL0003 Above 25sq.mm to 70sq.mm


CL0004 Above 70sq.mm to 150sq.mm
Page 17 of 22

m
m

RATE (Nu.)

AMOUNT (Nu.)

S.No.

5c

6
6a

DESCRIPTION

BSR Ref

CL0006 Above 300sq.mm to 630sq.mm

QTY.

UNIT

76

15.00

each

Providing and making route marker of size 600mmx600mm at bottom and 500mmx500mm at top with a
thickness of 100mm including inscription as required.
CL0070 With cement concrete 1:2:4, 20mm stone aggregate / Steel plate.
M/R

Providing and fixing electrical measuring instruments at the Main control panel board as per contract
document specification
- Voltmeter 0-500V - 1no.

1.00

Set

Ammeter 0- 400A - 1no.


Ammeter selector switch - 1no.
Voltmeter selector switch - 1no.
CT's and PT's
Indicating lamps - 4no.
HRC fuse 2A rating for avove-4no.
SUBTOTAL FOR FEEDER PILLAR-II
O
1

FIRE DETECTION & ALARM SYSTEM


Providing Wiring for fire detection and alarm system with 2x1.5sq. mm PVC insulated multistrand copper
WC0381
conductor fire retardent cable in recessed 25mm dia HDPE pipe I/c all accessories as required.
WC0381

Adressable Fire Alarm Control ,198-Point on One Signaling Line Circuit (SLC) Loop, 24 VDC , UL Listed /
International brand- Honeywell, Edward.

MR

Addressable Low-Profile Photoelectric Smoke Detector- UL listed / International brand - Honeywell, Edward.

MR

Addresable Manual Pull Station , Dual -Action ,Lexan , Key Lock - UL listed / International brand Honeywell, Edward.

MR

Addressable Control Module with Conventional Hooter - UL listed / International brand - Honeywell, Edward.

Page 18 of 22

675

75

14

Each

Each

Each

Each

RATE (Nu.)

AMOUNT (Nu.)

QTY.

UNIT

5kg DCP Fire Extinguisher (ISI certified)

15

Each

MR

4.5kg CO2 Extinguisher (ISI certified)

15

Each

MR

Installation, testing and commissioning including maintenance manual and first hand training at site.

Lot

1.00

set

S.No.

BSR Ref

MR

7
8

DESCRIPTION

SUBTOTAL FOR FIRE DETECTION & ALARM SYSTEM


P
1

MR

MR

Providing & fixing of auto load transfer


control panel with motorized switch.
FG Wilson / equivalent

1.00

set

MR

Clearing charge, load-unloading


Transportation cost to the site.

1.00

LS

MR

BST & other taxes as applicable

1.00

LS

D/G SET
Providing, Installation, testing and
commissioning of UK make P150-2
kVA DG set in sound attenuated
and weather proof canopy.
The DG set consists of engine, sound
attenuated and weather proof canopy
power wizard control panel 2.1, Antivibration mounting pads, base frame,
battery, battery leads, battery charger,
50% Auto freeze, Anti condensation
heater, coolant heater, lubricant oil.
FG Wilson / Equivalent.

Page 19 of 22

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

MR

MR

DESCRIPTION

QTY.

UNIT

Other related civil & electrical works


with fuel provision for testing the
D/G set.

1.00

LS

Installation, testing & commissioning

1.00

LS

SUB-TOTAL FOR D/G SET


Q
1

COMPUTER NETWORK
MR

CAT6 Data cable

15.00

box

4.00
1.00

Each
Each

2a
2b

MR

Switch: 24 PORT GIGA ETHERNET SWITCH


Switch: 16 PORT GIGA ETHERNET SWITCH

3a
3b

MR

CAT6: Surface Mount Box with Information Outlet; Simplex


CAT6: Factory Crimped Mounting Cord; 7 ft

113.00
113.00

Each
Each

4a
4b

MR

CAT6: Factory Crimped Mounting Cord; 7 ft


CAT6: 24Port patch Panel

113.00
5.00

Each
Each

MR

Wall Mount Rack with Glass Cover; 6U

5.00

Each

6a
6b

MR

Miscellaneous Items:
PVC Cassing Capping & Accessories, if required.

LS
LS

Installation & Configuration and Commissioning Charges: Installation & Configuration of Wireless System;
termination/testing of all extensions

LS

MR

SUB-TOTAL FOR COMPUTER NETWORK


R

EPABX SYSTEM
EPABX Systems: Equipped with 08 CO (Trunk-Telecom) + 64 Extensions (Internal).
Page 20 of 22

1.00

set

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

MR

DESCRIPTION

QTY.

Digital Key Telephone Instrument:


(Operator Phone): Make: Panasonic

UNIT

Each

MR

Voltage Stabiliser

1.00

Each

MR

Battery Backup

1.00

set

MR

Telehone

57.00

Each

MR

Main Distribution Frame (50 Pairs) (MDF) with KRONE Block Connectors and GD Tube Lightning Protectors for CO
Lines

5.00

MR

Telephone cable Cat-5

LS

MR

LS

MR

Miscellaneous Items
Installation & Configuration and Commissioning Charges: Installation & Configuration of EPABX System;
termination/ testing of all extensions

MR

PVC Pipes, Casing capping and other cable management accessories if required.

Lot

Installation & commissioning of above system

LS

8
9
10

SUB-TOTAL FOR EPABX


TOTAL FOR ELECTRICAL, FIRE DETECTION & ALARM SYSTEM, EPABX & LAN NETWORK
(Nu.)
In Words:

Page 21 of 22

set

LS

RATE (Nu.)

AMOUNT (Nu.)

S.No.

BSR Ref

DESCRIPTION

QTY.

Page 22 of 22

UNIT

RATE (Nu.)

AMOUNT (Nu.)