Beruflich Dokumente
Kultur Dokumente
Introduction
Capacitors provide tremendous benefits to distribution
system performance.
performance Most noticeably,
noticeably capacitors
reduce losses, free up capacity, and reduce voltage
drop:
L
Losses; Capacity:
C
i
B providing
By
d
the
h reactive power to motors andd
other loads with low power factor, capacitors decrease the line
current. Reduced current frees up capacity; the same circuit can serve
more load. Reduced current also significantly
g f
y lowers the I2R
line.
Voltage drop: Capacitors provide a voltage boost, which cancels part
of the drop caused by system loads. Switched capacitors can regulate
voltage on a circuit.
Introduction
If applied properly and controlled, capacitors can
significantly improve the performance of distribution
circuits.
But if not properly applied or controlled, the reactive
power from capacitor banks can create losses and high
voltages The greatest danger of over-voltages occurs
voltages.
under light load.
Capacitor Construction
Capacitor Construction
Capacitor Connection
Capacitors are either fixed or switched banks.
The fixed capacitors exist all time but the switched
capacitors are switched on based on the system need.
A typical switched capacitor bank is shown in the figure
below:
Capacitor Ratings
Capacitors should not be applied when any of the following
limits are exceeded:
135% of nameplate kvar.
110% off rated
t d RMS voltage.
lt
135% of nominal RMS current based on rated kvar and
rated voltage
voltage.
Capacitors are designed to withstand over-voltages for
short periods of time.
Capacitor Losses
Capacitor losses are typically on the order of 0.07
Capacitor Connection
a) Delta-connection
F
For ddelta
lt connection,
ti the
th single
i l phase
h
capacitor
it is
i a two
t
bushing capacitor unit.
11
a) Delta-connection
Example-1
Determine the appropriate voltage and kVAR ratings for
the capacitor units used to make a 2400 kVAR delta
connected capacitor bank to be installed on 13.8 kV
feeder.
feeder
12
a) Delta-connection
Example-1-solution
kVAR / phase
2400
800 kVAR / phase
3
13
Capacitor Connection
b) Y-connection
For Y connection,
connection the single phase capacitor is a single
bushing capacitor unit.
Capacitor Connection
b) Y-connection
The voltage rating of the capacitor unit must be
equal or more than the nominal line-ground
voltage of the feeder.
Additional units may be added in parallel to
increase the rating of the bank.
Group fusing is typically provided by fused
cutouts. However, individual fusing is provided
for larger capacitor banks.
15
b) Y-connection
Example-2
A 4800 kVAR, 12.47 kV, solidly grounded Y-connected
capacitor bank is made of eight 200 kVAR, 7200 V
capacitor
it units
it per phase.
h
A blown
bl
fuse
f
detection
d t ti scheme
h
is to be used to determine the presence of a blown fuse.
Assume that one fuse of phase A is blown, calculate the
current flowing from the neutral of the bank to the
ground.
16
b) Y-connection
Example-2-solution
7200 2
Z B ZC j
j 32.4
8 200,000
7200 2
ZA j
j 37.0
7 200,000
IC
72000
194.690 A
37 90
7200120
222.2210 A
32.4 90
IB
VCN 7200120
7200 120
222.2 30 A
32.4 90
I N I A I B I C 27.690 A
17
18
19
20
Example-3
If a 700 kVA load has a 65%
%p
power factor connected
to 4160VGrdY/2400V system, it is required to
improve the power factor to 92%. Using the following
Table determine the following:
Table,
a) The correction factor required.
b) The capacitor size required
c) If the capacitor size calculated in (b) is not the
standard size, use the list standard of capacitors sizes
previous Table to calculate the new p
possible
in the p
improved power factor.
21
22
Solution:
From the previous Table, the correction factor
required
i d is
i 0.74.
0 74
The real power of the 700 kVA load at 0.65 power
factor
= 700 x 0.65
= 455 kW
The capacitor size necessary to improve the power
factor from 65% to 92% can de found as
C
Capacitor
it size
i = P x (correction
(
ti factor)
f t )
= 455 (0.74)
= 336.7 kVAR
23
24
25
(0.879 0.878)
0.96025 0.96
(0.918 0.878)
26
b) Voltage Support
As mentioned earlier, capacitors are used to
improve the voltage profile for the feeders.
The best location for voltage support depends
on where the voltage
g support
pp is needed.
U
Unlikee a regulator,
egu o , a capacitor
c p c o changes
c ges thee
voltage profile upstream of the bank.
27
b) Voltage Support
28
Vrise ZI cap
K rise
kvar . mile
29
Example 4
Example-4
Calculate the Krise
i factor for a feeder
with an impedance of Z=0.25+j0.6 and a
length of 3 miles.
miles
Assuming a load of 7000 kVA and
power factor of 0.9
0 9 lagging and a
nominal line to line voltage = 11 kV
determine the rating of a three phase
capacitor bank to limit the voltage drop
to 1.5%.
1 5%
30
Example-44 Solution
Example
I cap
1kVAR
90 0.052590
3kVL L
I load
0.034
0.000537% rise / kVAR.mile
11000 / 3
7000
31
Example-44 Solution
Example
%Vdropp
238.6
3.76%
11000 / 3
Vrise
2.26
kVAR
1403 kVAR
K rise mile 0.000537 3
32
IL I
1/ 2
Where:
-Ip = magnitude of in-phase component of
line current
- Iq = magnitude of quadrature component of
line current
34
IL I
I q I c
2 1/ 2
Where:
-IIc = magnitude
i d off the
h capacitor
i current
35
36
Losses 3 I 2 R
I L1
I L2
455
97 A
3 4.16 .65
455
38.2 A
3 4.16 .96
L
Losses
14.16 kW
L
Losses
2.19 kW
38
39
kI1 I1
. x I1
i ( x)
L
The active power loss per phase
due to reactive component of load
current is:
PLoss
L
kI1 I1
.x I1 .R.dx
L
0
L
41
L 2 2
PLoss .I1 . K K 1 .R
3
If the load has only lumped
load, so K = 1 and:
PLoss L.I12 .R
If the load has only distributed
load, so K = 0 and:
L 2
PLoss
.I1 .R
L
3
42
for 0 x x '
for x ' x L
2
x'
So:
PLoss
kI I
1 1 .x I1 I C .R.dx
L
0
2
kI I
1 1 .x I1 .R.dx
L
x'
L
43
L
PLoss ( I1 I C (1 K ) x' ( I C2 2 I1 I C ) I12 ( K 2 K 1) .R
3
L
For
F a given
i
lloadd profile,
fil line
li length,
l th
and resistance, the quantities K, I1, R and
L are constant.
The only two variables are IC and xx.
To determine the optimum capacitor
size and location to minimize losses, the
partial derivatives are taken for these
two variables, IC and x.
PLoss
2 x'
I1I C (1 K ) ( I C2 2 I1I C )
0
x'
L
PLoss
x'
0 I1 (1 K ) 2 I C 2 I1
I C
L
(1)
(2)
44
( I C2 2 I1 I C ) L
x'
I1 I C (1 K ) 2
It is convenient to express the capacitor
current IC as a function of the reactive
current I1
L 2
I C I1 x '
2 1 K
(3)
2
3
0 1
3
2
45
2 1
x' L
3 1 K
So it can be seen from this equation that
the 2/3 capacitor size is only true for K
value is up to 1/3. If K is more than 1/3
th x will
then
ill be
b more than
th L which
hi h is
i nott
logic.
If K exceeds 1/3, the optimum location
is x=L
x =L and the capacitor size will be:
K 1
2
46
47
48
49
Example 7:
A section of a 12.47 kV distribution line has a length of 3
miles. The reactive power loading was measured as 2000
kVAR at the distribution substation line exit. The reactive
power loading at the end of the line section was estimated as
600 kVAR. Determine the optimum
p
capacitor
p
ratingg and
location to minimize line loss of this section.
50
Example 7-solution:
The ratio of reactive power at the end of the line section to the
reactive power at the beginning of the line is:
600
K
0.3
2000
Since K is less than 1/3, the optimum capacitor rating is twothirds time the reactive loading at the beginning of the line
section i.e.
section,
i e kVARCAP = (2/3)*2000=1333.3
(2/3)*2000=1333 3 kVAR
The optimum
p
capacitor
p
location is ggiven by:
y
2 1
x' (3)
2.86 miles
3 1 0.3
51
d) Released Capacity
In addition to reducing losses and improving voltage,
capacitors release capacity.
Improving the power factor increases the amount of realpower load the circuit can supply.
52
d) Released Capacity
53
Example 8:
IIn the
th following
f ll i Figure
Fi
a primary
i
line
li with
ith uniformly
if
l di
distributed
t ib t d load.
l d
The voltage at the distribution substation low-voltage bus is held at 1.03
pu V with bus voltage regulation. When there is no capacitor bank
installed on the feeder,
feeder the per unit voltage at the end of the line at annual
peak load is 0.97. Use the nominal operating voltage of 13.8 KV of the
three-phase as the base voltage. Assume that the off peak load of the
system is about 25% of the on peak load. Also, assume that the line
reactance is 0.80 /(phase.mi) but the line resistance is neglected and
determine the following:
aa- When the shunt capacitor bank is not used,
used find the Vx,
Vx voltages at the
times of peak load and off-peak load.
b- Apply an un-switched capacitor bank and locate it at the point of X = 4
mi on the line, and size the capacitor bank to yield a voltage of 1.05 per
unit at point X=0 at the time of zero load. Find the size of the capacitor in
three phase kilovars.
54
Example 8, solution
The current flowing through any segment along a feeder with
uniformly distributed load can be calculated from the
following equation (no installed capacitors exist):
I x I S 1
dVD x I x z dx
55
Example 8, solution
The total voltage drop from the source point to point x along
the feeder is given by:
x
VDx dVDx I x z dx
VDx I S 1
0
x
x
z dx
l
x
x2
VDx I S z x I S z x 1
2l
2l
56
Example 8, solution
The total voltage drop from the source point to the feeder
end-point is given by:
l2
l
VDl I S z l I S z
2
2l
x 1
2l x
VD x % VD x
2
l
VDl
% VDl
l
2
57
Example 8, solution
The total voltage drop from the source point to the feeder
end-point (no installed capacitors exist) at the peak load is
given by:
2 2 0.888
VDl
l
l 3
3 9
VD x 0.888 x 0.06 0.0533 pu
Example 8, solution
The total voltage drop from the source point to the feeder
end-point (no installed capacitors exist) at the no loading
condition is given by:
% VD
D
l , off
% VDl , peak
off
D peak
1
4
VDl , offff
l
l 3
3 9
VD x , off 0.888 x 0.015 0.0133 pu
59
Example 8, solution
The voltage at point X with no capacitor is 1.03 pu (because
there is no load and the voltage at the bus will equal the
voltage at X), after installing the capacitor bank the voltage at
point X becomes 1.05 pu. Therefore, the per unit voltage rise
att point
i t X is
i 0.02
0 02 pu or 2 %.
%
I cap
1kVAR
90 0.04290
3 *13.8
0.0336
0.000422%rise/kvar.
rise/kvar mile
13.8 / 3
%Vrise
i K rise
i * kVAR * mile
2
KVAR
1185.7
0.000422 * 4
60
Capacitor banks
b) More complicated control: these techniques
require different electrical measurements like:
Voltage:
The capacitor switches on and off, based on voltage
magnitude.
Vo
Voltage
tage co
control
t o iss most
ost app
appropriate
op ate w
when
e tthee pprimary
a y role
oe
of a capacitor is voltage support and regulation.
Voltage-controlled capacitor banks have bandwidths
which should be at least 3 or 4 V ((on a 120-V scale).
)
62
Capacitor banks
Vars:
The capacitor uses var measurements to
determine switching.
This is the most accurate method of ensuring
that the capacitor is on at the appropriate times
for maximum reduction of losses.
losses
Like the voltage control technique, there is a
bandwidth for switching of each capacitor bank
to prevent excessive switching operations in
most cases.
63
Distribution Substation
Banks
Percent
Voltage
16.6
30.8
Current
4.9
2.4
Time
59.8
16.3
Voltage-Current
7.2
12.6
Voltage-Time
5.1
6.3
Manual*
6.2
28.4
Others
0.2
3.2
Total
100.0
100.0
64
2 .V LL
3
MVAR rated
2 . . f rated .( kV LL _ rated ) 2
Th capacitor
The
i switching
i hi current is:
i
Vo / s
I (s)
sL s (1 / sC )
68
s2
Vo / Ls
(1 / L s C )
1/2
2 o 2
s o
Where:
o
1
L sC
C
i(t ) V o
L
1/ 2
sin(( o t )
I max
C
Vo
L
1/ 2
69
Example 9:
A 1200-kVAR, 4.16-kV capacitor bank is installed
on a pplant bus. The plant
p
bus is supplied
pp
from a
5000-kVA, 69kV-4.16/2.4 kV transformer having
an impedance of 7%. Neglecting the impedance of
the source and resistance determine the maximum
instantaneous value and the frequency of the
inr sh ccurrent.
inrush
rrent Also
Also, determine the ind
inductance
ctance of
the inductors that must be added to reduce the
inrush current
current.
70
Example 9-solution:
The transformer inductive reactance is:
2
4.16kV
X 0.07.
5MVA
0.242
0.242
L
6.43 10 4 H
2 .60
1.2 MVAR
4
1
.
84
10
F
2 .60.(4.16kV ) 2
Vo
2 .4160
3396V
3
1/ 2
I max
1.84 10 4
3396
4
6.43 10
1817 A
71
Example 9-solution:
The frequency of the transient inrush current is
o
1.84 10
1
4
.6.43 10
4 1/ 2
2909rad 463Hz