R J Meadows
Group Technical Officer
11kV
415V
Load
FAULT!
11kV
415V
I
0
Load
Earth path
impedance
The loop impedance can be lowered by
including more conductors in the earth path e.g. cross bonding.
Broken neutral
A serious problem:
415V
415V 415V
240V
240V
240V
368V
11kV
Although the line voltages remain correct,
the phase voltages (ph-n) vary widely.
240V
138V
240V
276V
Load a
Load b
ZL
Displaced
neutral R
139V
138 above true
neutral
2ZL
415
368
121.5
240
276
Phase current
Earth path current
CT current
e/f
Load
Protection is by simple current sensing relay and will respond to any current
flowing in the earth path.
Phase current
Neutral current
Earth path current
CT current
e/f
EFFECT OF LEAVING
ALTERNATOR NEUTRAL
EARTH LINK IN PLACE.
Load
ZL
Nuisance tripping
Neutral current has an
alternative route, through
the earth path, resulting in
protection operation on load
imbalance.
Phase current
Neutral current
Gen. 1
Gen. 2
e/f
Phase current
Gen. 1
Gen 1 earth path current
Gen 2 earth path current
25 mA
CT current
e/f
25 mA
e/f
Phase current
Gen. 1
Gen 1 Earth path current
Gen 2 Earth path current
50 mA
CT current
e/f
Gen. 2
ADVANTAGES
Simple to apply
Provides protection for all earth faults on the generator, switchgear and system
Can give good level of personnel protection throughout the system
DISADVANTAGES
MAIN USE
Back-up high-set protection for main, submain and distribution board faults
Phase current
Neutral current
CT current
e/f
Load
NORMAL OPERATION
PROTECTION
ZONE
Phase current
Neutral current
Earth path current
CT current
e/f
Load
PROTECTION
ZONE
Phase current
Earth path current
CT current
e/f
Load
PROTECTION
ZONE
Phase current
Gen. 1
e/f
Load
FAULT OUTSIDE OF ZONE
Although multiple earthing exists,
protection is stable due to positioning of
the neutral earth links.
Gen. 2
e/f
Phase current
Gen. 1
Gen 1 Earth path current
Gen 2 Earth path current
CT current
e/f
Load
FAULT ON ONE SET
Gen. 2
e/f
ADVANTAGES
DISADVANTAGES
MAIN USE
Differential protection - 1
Phase current
Neutral current
CT current
diff diff
diff
SINGLE PHASE
LOAD
PROTECTION
ZONE
Differential protection - 2
Phase currents
CT current
i
diff diff
diff
THREE PHASE LOAD
PROTECTION
ZONE
CT accuracy and correct wiring connections are
of paramount importance. Class X CTs should
be used and pilot resistors may be needed to
balance the pilot impedances if, as is usual,
the relay is mounted closer to one set of CTs
than the other.
Differential protection - 3
Phase current
Earth path current
CT current
i
diff diff
diff
LOA
D
PROTECTION
ZONE
Differential protection - 4
Phase current
Earth path current
CT current
diff diff
diff
LOA
D
PROTECTION
ZONE
For high voltage sets, the effects of an earth fault in the
stator pack or terminal box may be severe. Differential
protection, correctly installed will prevent the fault
building up and will localise the damage.
Differential protection - 5
Phase currents
Earth path current
CT current
diff diff
diff
LOA
D
PROTECTION
ZONE
ADVANTAGES
Sensitive
Senses both line-line and line earth faults
Zone protection eliminates discrimination problems
DISADVANTAGES
Relatively expensive
MAIN USES
Earth and interturn fault protection of high voltage or large low voltage
alternators and transformers
NER
BACKUP EARTH
FAULT
Single generator
Parallel generators
Red H1
20
Red H3
Yellow H3
-20
Blue H3
-40
Neutral
-60
R
Y
B
11kV
415V
Generator should be
connected to a delta wound
step up transformer LV
winding
HV step down transformer
should have delta HV
winding + star LV
Summary