Sie sind auf Seite 1von 6

SSP Pendant Glass Bulb Sprinkler

SSP-15 Glass Bulb Sprinkler

I. Introduction:
SSP Pendant glass bulb sprinkler is the key part of the automatic sprinkler system. It is used for
detecting fire and controlling or extinguishing fire by spraying water automatically. It is widely used for
protecting restaurant, hotel, shop, commercial building, warehouse, underground garage, garment
factory and other buildings or mild, middle and serious danger level.

II. Characteristics:
SSP Pendant Glass Bulb Sprinkler is composed of glass bulb, copper alloy frame and sealed
element, etc. with compact structure and exquisite appearance.
1. The frame of sprinkler adopts copper alloy precision forging with high strength and corrosion
resistance. The surface treatment has two kinds for users to choose: natural color deactivation
and polishing chromate treatment.
2. Both temperature sensitive element (glass bulb) and washer are imported from Germany. The
glass bulb has high strength with reliable operation and quick reaction and washer with high ageing and
corrosion resistance.

III. Technical Characteristics


1.
2.
3.
4.

Nominal diameter 15mmConnecting ScrewR"


Rated working pressure1.2MPaTesting Pressure when leaving factory3.0MPa
CoefficientK=804
Diameter of Glass Bulb 3mm 5mm

5. Rated temperature and color index


Rated Operating
Type
Temperature ()
SSP15/57
57
SSP15/68
68
SSP15/79
79
SSP15/93
93
SSP15/141
141
SSP15/182
182

Max Ambient
Temperature ()
27
38
49
63
111
152

Color of Glass Bulb


Orange
Red
Yellow
Green
Blue
Purple

6. Performance Curve:

Flow Rate of SprinklerL/min


Curve between pressure and flow rate
0.5

Protection Radiusm
Jet Curve of SSP Pendant Glass Bulb
0.5

7. RTI: 3mm50 (MS) ; 5mm80 (MS) .

IV. Others:
1. This product can only be installed pendant with the deflector downwards.
2. When used in the buildings with ceiling, our company can supply relative decorative tray or
protection cover.
Notes: When installing, it should adopt relative special wrench. Screw moment is within 1020Nm
(it should not surpass 29Nm).

SSU Vertical Glass Bulb Sprinkler

SSU Vertical Glass Bulb Sprinkler

I. Introduction:
SSU Vertical glass bulb sprinkler is the key part of the automatic sprinkler system. It is used for
detecting fire and controlling or extinguishing fire by spraying water automatically. It is widely used fro
protecting restaurant, hotel, shop, commercial building, warehouse, underground garage, garment
factory and other buildings or mild, middle and serious danger level.

II. Characteristics:
SSUVertical Glass Bulb Sprinkler is composed of glass bulb, copper alloy frame and sealed
element, etc. with compact structure and exquisite appearance.
1. The frame of sprinkler adopts copper alloy precision forging with high strength and corrosion
resistance. The surface treatment has two kinds for users to choose: natural color deactivation
and polishing chromate treatment.
2. Both temperature sensitive element (glass bulb) and washer are imported from Germany. The
glass bulb has high strength with reliable operation and quick reaction and washer with high ageing and
corrosion resistance.

III. Technical Characteristics


1.
2.
3.
4.

Nominal diameter 15mmConnecting ScrewR".


Rated working pressure1.2MPaTesting Pressure when leaving factory3.0MPa
CoefficientK=804
Diameter of Glass Bulb 3mm 5mm

5. Rated temperature and color index


Rated Operating
Type
Temperature ()
SSU15/57
57
SSU15/68
68
SSU15/79
79
SSU15/93
93
SSU15/141
141
SSU15/182
182

Max Ambient
Temperature ()
27
38
49
63
111
152

Color of Glass Bulb


Orange
Red
Yellow
Green
Blue
Purple

6. Performance Curve:

Flow Rate of SprinklerL/min


Curve between pressure and flow rate
0.5

Protection Radiusm
Jet Curve of SSU Vertical Glass Bulb
0.5

7. RTI: 3mm50 (MS) ; 5mm80 (MS) .

IV. Others:
1. This product can only be installed on the concealed or exposed water network vertically with
the deflector upwards.
2. When used in the buildings with ceiling, our company can supply relative decorative tray or
protection cover.
Notes: When installing, it should adopt relative special wrench. Screw moment is within 1020Nm
(it should not surpass 29Nm).

SSB Sidewall Glass Bulb Sprinkler

SSB-15 Vertical Sidewall


Glass Bulb Sprinkler

SSB-15 Horizontal Sidewall


Glass Bulb Sprinkler

I. Introduction:
SSB Sidewall glass bulb sprinkler is the key part of the automatic sprinkler system. It is used for
detecting fire and controlling or extinguishing fire by spraying water automatically. It is widely used for
protecting restaurant, hotel, shop, commercial building, warehouse, underground garage, garment
factory and other buildings or mild, middle and serious danger level.

II. Characteristics:
SSB Sidewall Glass Bulb Sprinkler is composed of glass bulb, copper alloy frame and sealed
element, etc. with compact structure and exquisite appearance.
1. The frame of sprinkler adopts copper alloy precision forging with high strength and corrosion
resistance. The surface treatment has two kinds for users to choose: natural color deactivation
and polishing chromate treatment.
2. Both temperature sensitive element (glass bulb) and washer are imported from Germany. The
glass bulb has high strength with reliable operation and quick reaction and washer with high ageing and
corrosion resistance.
3. This product is installed on the concealed or exposed water pipeline. When it is installed on the
sidewall of the guest room, it has good concealed performance, long range and large protection area.

III. Technical Characteristics


1.
2.
3.
4.

Nominal diameter 15mmConnecting ScrewR".


Rated working pressure1.2MPaTesting Pressure when leaving factory3.0MPa
CoefficientK=804
Diameter of Glass Bulb 3mm 5mm

5. Rated temperature and color index


Sprinkler Pressure0.1MPa

SSB15/57

Rated
Operating
Temperature
()
57

SSB15/68

68

38

Red

SSB15/79

79

49

Yellow

SSB15/93

93

63

Green

SSB15/141

141

111

Blue

SSB15/182

182

152

Purple

Type

Max
Ambient
Temperature
()
27

Color of
Glass Bulb
Orange

Flow
Rate
of
Sprinkler (L/min)

Curve between Pressure and Flow Rate

6. Performance Curve:
Jet Point

Jet Point

Protection Radius (m)

Radius (m)

Front View of SSB Sidewall Jet Curve

Side View of SSB Sidewall Jet Curve

Jet Curve of SSB Sidewall Sprinkler


0.5

0.5

7. RTI: 3mm50 (MS) ; 5mm80 (MS) .

IV. Others:
1. This product can only be installed pendantly with the deflector downwards.
2. When used in the buildings with ceiling, our company can supply relative decorative tray or
protection cover.
Notes: When installing, it should adopt relative special wrench. Screw moment is within 1020Nm
(it should not surpass 29Nm).

Das könnte Ihnen auch gefallen