Beruflich Dokumente
Kultur Dokumente
CONTROLLERS
SELECTION GUIDE
1769-L31
1769-L32C, 1769-L35CR
1769-L32E, 1769-L35E
1756
GuardLogix
Controller tasks:
Continuous
Periodic
Event
100 tasks
100 tasks
Event tasks: all event Event tasks: all
triggers
event triggers
User memory
1756-L55M12: 750 KB
1756-L55M13: 1.5 MB
1756-L55M14: 3.5 MB
1756-L55M16: 7.5 MB
1756-L55M22: 750 KB
1756-L55M23: 1. 5 MB
1756-L55M24: 3.5 MB
1756-L60M03SE: 750 KB
1756-L61: 2 MB
1756-L62: 4 MB
1756-L63: 8 MB
1756-L64: 16 MB
Nonvolatile user
memory
1768
CompactLogix
1769-L35x: 8 tasks
16 tasks
1769-L32x: 6 tasks
Event tasks:
1769-L31: 4 tasks
consumed tag, EVENT Event tasks:
instruction, axis, and consumed tag and
motion event triggers EVENT instruction
triggers
PowerFlex
700S2 with
DriveLogix
1789
SoftLogix5800
1794 FlexLogix
100 tasks
Event tasks: all
event triggers, plus
outbound and
Windows events
8 tasks
Event tasks:
consumed tag and
EVENT instruction
triggers
8 tasks
Event tasks: axis
and motion event
triggers
1794-L34:
256 KB
768 KB with memory
expansion
1789-L10:
2 MB; 3 slots; No
motion
1756-L61S:
2 MB Standard
1 MB Safety
1768-L43:
2 MB
1756-L61S:
4 MB Standard
1 MB Safety
1756-L55M12: none
1756-L55M13: none
1756-L55M14: none
1756-L55M16: none
CompactFlash
1756-L55M22: yes
1756-L55M23: yes
1756-L55M24: yes
1756-L6x: CompactFlash
1769
CompactLogix
1769-L31:
1769-L32x:
1769-L35x:
512 KB
750 KB
1.5 MB
1789-L30:
64 MB; 5 slots
512 KB
1789-L60:
64 MB; 16 slots
None
Yes
Yes (expansion
memory)
CompactFlash
CompactFlash
1769-L31: 2 RS-232
ports
1769-L32C, -L35CR:
1 ControlNet port and Depends on personal
1 RS-232 serial port
computer
1769-L32E, -L35E: 1
EtherNet/IP port and 1
RS-232 serial port
Built-in communication
1 port RS- 232 serial
ports
Communication
options
(these options have
specific products and
profiles for their
platform - other
options are available
via third party products
and generic profiles)
EtherNet/IP
ControlNet
DeviceNet
Data Highway Plus
Remote I/O
SynchLink
EtherNet/IP
(standard and safety)
ControlNet
(standard and safety) EtheNet/IP
DeviceNet (standard ControlNet
and safety)
DeviceNet
Data Highway Plus
Remote I/O
SynchLink
EtherNet/IP
ControlNet
DeviceNet
EtherNet/IP
ControlNet
DeviceNet
EtherNet/IP
ControlNet
DeviceNet
EtherNet/IP
ControlNet
DeviceNet
Serial port
communications
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
ASCII
DF1 full/half duplex
DF1 radio modem
DH-485
Modbus
Connections
100 ControlNet
128 EtherNet/IP
64 TCP/IP
48 ControlNet
128 EtherNet/IP
64 TCP/IP
48 ControlNet
64 EtherNet/IP
32 TCP/IP
32 ControlNet
32 EtherNet/IP
32 TCP/IP
48 ControlNet
EtherNet/IP limited
by type/number cards
32 ControlNet
32 EtherNet/IP
64 TCP/IP
32 ControlNet
32 EtherNet/IP
64 TCP/IP
Controller redundancy
Full support
None
NA
NA
NA
NA
Simple motion
Stepper
Servo via DeviceNet
Analog ac drive
Stepper
Stepper
Stepper
Stepper
Stepper
Stepper
Servo via
Servo via DeviceNet Servo via DeviceNet Servo via DeviceNet Servo via DeviceNet Servo via DeviceNet
DeviceNet
Analog ac drive
Analog ac drive
Analog ac drive
Analog ac drive
Analog ac drive
Analog ac drive
Integrated motion
SERCOS interface
Analog options:
Encoder input
LDT input
SSI input
SERCOS interface
Analog options:
Encoder input
LDT input
SSI input
SERCOS interface
Programming
languages
Relay ladder
Structured text
Function block
SFC
Relay ladder
Structured text
Function block
SFC
Relay ladder
Structured text
Function block
SFC
NA
SERCOS interface
Analog options:
Encoder input
LDT input
SSI input
NA
1 full servo
1 feedback axis
Relay ladder
Structured text
Function block
SFC
Relay ladder
Structured text
Function block
SFC
External routines
(developed in C/C++)
Relay ladder
Structured text
Function block
SFC
Relay ladder
Structured text
Function block
SFC
Logix Platforms
Section
1769 CompactLogix System
Layout the System
Select 1769 I/O Modules
Select Network Communications
Select Controllers
Select Power Supplies
Mount the System
Select Visualization Products
Select Software
Summary
Page
2
3
5
15
23
33
35
37
39
47
CompactLogix System
Overview
What's New in Version 16:
A simple system can consist of only a standalone controller in a single bank of I/O
modules and simple communication.
y Add-on instructions
y Alarms and events
y DF1 radio modem
As you lay out a system configuration, determine the network configuration and the
placement of components in each location. Decide at this time whether each location
will have its own controller.
Use the CompactLogix system to distribute control among different locations. You can
remotely control I/O and field devices from a central CompactLogix controller over
EtherNet/IP, ControlNet, or DeviceNet networks.
For example, this system layout defines Location A and Location B, which each require a
unique CompactLogix controller. Location A and Location B each have their own I/O
modules. Location A also has some remote DeviceNet I/O devices, so that location will
need a DeviceNet scanner, such as a 1769-SDN. Either EtherNet/IP or ControlNet can
serve as the supervisory network to interlock Location A and Location B.
Specify a System
9
Step
1
page 5
page 10
page 11
page 13
page 14
Network overview
EtherNet/IP specifications
ControlNet specifications
DeviceNet specifications
Serial specifications
DH-485 specifications
page 15
page 17
page 19
page 20
page 21
page 22
Controller specifications
Determine memory requirements
Control devices
Communicate with other devices
PhaseManager applications
FactoryTalk alarms and events
Logix system connections
page 23
page 24
page 25
page 26
page 27
page 27
page 28
page 33
page 35
RSView software
PanelView Plus terminals
VersaView industrial computers
VersaView CE industrial computers
Available software products
Programming software
Communication software
Network configuration software
Emulation software
page 37
page 38
page 38
page 38
page 39
page 40
page 42
page 44
page 46
Select controllers.
Select software.
Step 1 - Select:
y I/O modules
y 1492 wiring system (if you want to use a
wiring system instead of the terminal
block that comes with module)
y PanelConnect modules and cables if
connecting input modules to sensors
y 1769-CRLx expansion cables for multiple
banks of I/O modules
The 1769 Compact I/O modules can be used as local I/O for a CompactLogix controller.
Install the I/O modules on a panel with two mounting screws or on a DIN rail. The
modules mechanically lock together by means of a tongue-and-grove design and have an
integrated communication bus that is connected from module to module by a moveable
bus connector.
Each I/O module includes a built-in removable terminal block with finger-safe cover for
connections to I/O sensors and actuators. The terminal block is behind a door at the front
of the module. I/O wiring can be routed from beneath the module to the I/O terminals.
When planning I/O communications, consider:
y which Compact I/O modules to use.
y where to place Compact I/O modules.
y how Compact I/O modules operate.
input module
output module
Description
An input module responds to an input signal in the following manner:
y Input filtering limits the effect of voltage transients caused by contact bounce and/or electrical noise. If
not filtered, voltage transients could produce false data. All input modules use input filtering.
y Optical isolation shields logic circuits from possible damage due to electrical transients.
y Logic circuits process the signal.
y An input LED turns on or off indicating the status of the corresponding input device.
An output module controls the output signal in the following manner:
y Logic circuits determine the output status.
y An output LED indicates the status of the output signal.
y Optical isolation separates module logic and bus circuits from field power.
y The output driver turns the corresponding output on or off.
Most output modules have built-in surge suppression to reduce the effects of highvoltage transients. Use an additional suppression device if an output is being used to
control inductive devices, such as relays, motor starters, solenoids, or motors. Additional
suppression is especially important if your inductive device is in series with or parallel to
hard contacts, such as push buttons or selector switches.
Add a suppression device directly across the coil of an inductive device to reduce the
effects of voltage transients caused by interrupting the current to that device and to
prolong the life of the switch contacts.
Number of
Inputs
1769-IA8I
8 individually
isolated
Input Delay
Voltage
Time, ON to
Category/Type,
Input
Voltage Range OFF
Backplane
Current (mA)
at 5V
Power Supply
Distance
Rating
100 or 120V ac
79...132V ac @
47...63Hz
20 ms
5 mA @ 79V ac
2.5 mA
90 mA
8 modules
1769-IA16 16
100 or 120V ac
79...132V ac @
47...63Hz
20 ms
5 mA @ 79V ac
2.5 mA
115 mA
8 modules
1769-IM12 12
200 or 240V ac
159...265V ac @
47...60Hz
20 ms
5 mA @ 159V ac
2.5 mA
100 mA
8 modules
Cat.
No.
Number of
Outputs
Leakage
Current, OffVoltage
State Output,
Category/Type,
Output
Voltage Range Max.
1769-OA8
100240V ac
85...265 ac @
47...63Hz
100...240V ac
85...265 ac @
47...63Hz
1769-OA16 16
Power Supply
Backplane
Current (mA) Distance
at 5V
Rating
Current per
Output, Max.
Current per
Module, Max.
2.0 mA at 132V ac
2.5 mA at 265V ac
0.25 A @ 60 C (140 F)
0.50 A @ 30 C (86 F)
2.0 A @ 60 C (140 F)
145 mA
4.0 A @ 30 C (86 F)
8 modules
2.0 mA at 132V ac
2.5 mA at 265V ac
0.25 A @ 60 C (140 F)
0.50 A @ 30 C (86 F)
4.0 A @ 60 C (140 F)
225 mA
8.0 A @ 30 C (86 F)
8 modules
Backplane
Current (mA)
at 5V
Power Supply
Distance
Rating
4.5...5.5V dc
1.5 mA off-state
0.6 mA on-state
120 mA
8 modules
1769-IQ6XOW4 6
10...30V dc @ 30 C
(86 F)
8 ms
10...26.4V dc @ 60
C (140 F)
2 mA
1.5 mA
105 mA
8 modules
1769-IQ16
16
10...30V dc @ 30 C
(86 F)
8 ms
10...26.4V dc @ 60
C (140 F)
2 mA
1.5 mA
115 mA
8 modules
1769-IQ16F
16 high-speed
10...30V dc @ 30 C
(86 F)
1 ms
10...26.4V dc @ 60
C (140 F)
2 mA
1.5 mA
110 mA
8 modules
1769-IQ32
32
10...30V dc @ 30 C
(86 F)
8 ms
10...26.4V dc @ 60
C (140 F)
2 mA
1.5 mA
170 mA
8 modules
1769-IQ32T
32 terminated
20.4...26.4V dc
3 mA
1.7 mA
170 mA
8 modules
Cat. No.
Number of
Inputs
Voltage
Category/Type,
Input
1769-IG16
16
0.5 ms
8 ms
TTL inputs are inverted (0.20.8V dc = logic low voltage = ON-state; 2.05.5V dc = logic high voltage = OFF-state).
Number of
Cat. No. Outputs
Leakage
Current, OffVoltage
State Output,
Category/Type,
Output
Voltage Range Max
Current per
Output, Max.
Current per
Module, Max.
Power Supply
Backplane
Current (mA) Distance
at 5V
Rating
1769-OB8
20.4...26.4V dc
1.0 mA @ 26.4V dc
2.0 A @ 60 C (140 F)
8.0 A @ 60 C (140 F)
145 mA
8 modules
1769-OB16
16
20.4...26.4V dc
1.0 mA @ 26.4V dc
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
4.0 A @ 60 C (140 F)
8.0 A @ 30 C (86 F)
200 mA
8 modules
1769-OB16P 16 protected
20.4...26.4V dc
1.0 mA @ 26.4V dc
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
4.0 A @ 60 C (140 F)
8.0 A @ 30 C (86 F)
160 mA7
8 modules
1769-OB32
20.4...26.4V dc
1.0 mA @ 26.4V dc
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
8.0 A @ 60 C (140 F)
16.0 A @ 30 C (86 F)
300 mA
6 modules
1769-OB32T 32 terminated
10.2...26.4V dc
0.1 mA @ 26.4V dc
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
4.0 A @ 60 C (140 F)
8.0 A @ 30 C (86 F)
220 mA
8 modules
1769-OG16 16
4.5...5.5V dc
8 modules
1769-OV16
20.4...26.4V dc
1.0 mA @ 26.4V dc
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
4.0 A @ 60 C (140 F)
8.0 A @ 30 C (86 F)
200 mA
8 modules
10.2...26.4V dc
1.0 mA @ 26.4V dc
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
4.0 A @ 60 C (140 F)
8.0 A @ 30 C (86 F)
220 mA
8 modules
32
16
1769-OV32T 32 terminated
Cat. No.
Number of
Outputs
Voltage
Category/Ty Voltage
pe, Output
Range
Leakage
Current, OffState
Current per
Output, Max. Output, Max.
Current per
Module,
Max.
Power
Backplane Backplane Supply
Current (mA) Current (mA) Distance
at 5V
Rating
at 24V
1769-IQ6XOW4 4
24V dc
5...265V ac
5...125V dc
0 mA
2.5 A
8.0 A
105 mA
50 mA
8 modules
1769-OW8
24V dc
5...265V ac
5...125V dc
0 mA
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
16 A
125 mA
100 mA
8 modules
1769-OW8I
8 individually
isolated
24V dc
5...265V ac
5...125V dc
0 mA
0.5 A @ 60 C (140 F)
1.0 A @ 30 C (86 F)
16 A
125 mA
100 mA
8 modules
1769-OW16
16
24V dc
5...265V ac
5...125V dc
0 mA
2.5 A
20 A
205 mA
180 mA
8 modules
Break
240V ac
7.5 A
0.75 A
15 A
1.5 A
120V ac
2.5 A
Voltamperes
Make
Break
IEC 947
1800 VA
180 VA
AC15=
C300
125V dc 1.0 A
0.22 A
28 VA
DC13=
R150
24V dc
1.2 A
28 VA
2.0 A
Cat. No.
Number of
Inputs
Number of
Outputs
Resolution,
Bits
Signal Range
Sensors
Supported
Backplane
Current (mA)
at 5V
Backplane
Current (mA)
at 24V
Power Supply
Distance
Rating
105 mA
60 mA7
8 modules
1769-IF4
14 bits (unipolar)
020 mA
420 mA
010V dc
10V dc
05V dc
15V dc
1769-IF4I
4 individually
isolated
16 bits (unipolar)
10.5V dc
-0.510.5V dc
-0.5...5.25V dc
0.55.25V dc
145 mA
95 mA
8 modules
120 mA
70 mA
8 modules
1769-IF8
16 bits (unipolar)
020 mA
420 mA
010V dc
10V dc
05V dc
15V dc
1769-OF2
14 bits
120 mA
120 mA7
8 modules
1769-OF4CI
4 current,
individually isolated
16 bits (unipolar)
420 mA
020V mA
145 mA
140 mA
8 modules
1769-OF4VI
4 voltage,
individually isolated
16 bits (unipolar)
-1010V dc
05V dc
0...10V dc
15V dc
145 mA
75 mA
8 modules
145 mA
160 mA
8 modules
1769-OF8C
8 current
16 bits (unipolar)
020 mA
420 mA
010V dc
10V dc
05V dc
15V dc
1769-OF8V
8 voltage
16 bits (unipolar)
020 mA
420 mA
145 mA
125 mA
8 modules
2 individually
isolated
010V dc
10V dc
05V dc
15V dc
120 mA
160 mA
8 modules
45 mA
8 modules
Thermocouple types: J,
K, T, E, R, S, B, N, C
50mV
100mV
40 mA
8 modules
1769-IF4XOF2 4
1769-IR6
1769-IT6
6, plus 2 cold
junction sensors
100 mA
Number of Inputs
Number of Outputs
1769-ARM
60 mA
8 modules
Channel Configuration
1769-ASCII
200 characters
500 mA
4 modules
Number of Inputs
Number of Outputs
1769-BOOLEAN
8 real
8 virtual
220 mA
8 modules
Number of Inputs
1769-HSC 2
Number of Outputs
425 mA
19.2...31.2V dc
100 mA @ 24V dc
10
Description
Communication Rate
280 mA
6 modules
350 mA
0 mA
4 modules
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring
system of:
y interface modules (IFMs) that provide the output terminal blocks for digital I/O
modules. Use the pre-wired cables that match the I/O module to the IFM.
y analog interface modules (AIFMs) that provide the output terminal blocks for analog
I/O modules. Use the pre-wired cables that match the I/O module to the AIFM.
y I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the
front of the I/O module. The other end has individually color-coded conductors that
connect to a standard terminal block.
1492 PanelConnect
Modules for Connecting
Sensors
A PanelConnect module and its sensor connection systems let you connect sensors
directly to I/O modules using convenient pre-built cables and connectors.
The PanelConnect module mounts on the enclosure and creates the correct seal for the
entry of the sensor connections. You do not need to seal the opening where the sensor
cables enter the enclosure, create custom connectors, or wire to those custom
connectors.
11
You can DIN-rail or panel-mount the controller and I/O modules. The number of local
I/O modules supported depends on the controller.
This Controller
1769-L35CR
1769-L35E
1769-L32C
1769-L32E
1769-L31
Supports
That Can Be In
30 local modules
3 separate banks
16 local modules
3 separate banks
12
Order
1769-ECR
1769-ECL
13
Type of Module
Specialty
Considerations
y 1-4 modules can be scanned in 1.0 ms
y 5-16 modules can be scanned in 1.5 ms
y 17-30 modules can be scanned in 2.0 ms
y some input modules have a fixed 8.0 ms filter, so selecting a faster RPI has no affect
y full-sized 1769-SDN modules add 1.5 ms per module
y 1769-HSC modules add 0.5 ms per module
You can always select an RPI that is slower than listed above. These considerations show
how fast modules can be scanned - not how fast an application can use the data. The RPI
is asynchronous to the program scan. Other factors, such as program execution duration,
affect I/O throughput.
14
Select Controller
Ownership
Relationship
Owner controller
Listen-only connection
In a Logix system, modules multicast data. This means that multiple devices can
receive the same data at the same time from a single device. When you choose a
communication format for an I/O module, you have to choose whether to establish an
owner or listen-only relationship with the module.
Description
The controller that creates the primary configuration and communication connection to a
module. The owner controller writes configuration data and can establish a connection to
the module.
An owner provides the configuration data for the I/O module. A controller using a listenonly connection only monitors the module. It does not write configuration data and can
only maintain a connection to the I/O module while the owner controller is actively
controlling the I/O module.
Because of the distributed nature of a CompactLogix system, the CompactLogix controller
must own its local I/O modules. No other Logix controller can listen to or own the local
Compact I/O. The CompactLogix controller must produce its local I/O data for any other
controller to consume. The listen-only format only works for remote I/O.
Step 2 - Select:
y Networks
15
y Communication interfaces
y Associated cables and network
equipment
16
Select a Network
You can configure your system for information exchange between a range of devices and
computing platforms and operating systems. Select a CompactLogix controller with
integrated communications or the appropriate communication device for the networks that
meet your needs.
If your application requires
y Plant management
y Configuration, data collection, and control
on a single, high-speed network
y Time-critical applications with no
established schedule
y Data sent regularly
y Internet/Intranet connection
y High-speed transfer of time-critical data
between controllers and I/O devices
y Deterministic and repeatable data delivery
y Media redundancy
y Intrinsic safety
y redundant controller systems
Select
EtherNet/IP network
ControlNet network
1769-SDN scanner
1761-NET-DNI interface
1769-ADN adapter
EtherNet/IP Network
17
If Your Application
y Controls I/O over EtherNet/IP
y Produces and consumes data
over EtherNet/IP
y Accesses both EtherNet/IP
and serial devices
y Requires high performance
over EtherNet/IP
y Sends and receives messages
over EtherNet/IP
y Transfers small amounts of
data over EtherNet/IP
Select
Description
1769-L32E or 1769-L35E
CompactLogix controller with
integrated EtherNet/IP port
Cat. No.
1769-L32E
10/100 Mbps
1769-L35E
10/100 Mbps
6 TCP/IP connections
Connector
RJ-45
Power
Dissipation
Backplane
Current (mA) at
5V
Backplane
Current (mA) at
24V
Power Supply
Distance Rating
4.74 W
660 mA
90 mA
4 modules
4.74 W
660 mA
90 mA
4 modules
0 mA
50 mA
18
ControlNet Network
19
The ControlNet network is an open, state-of-the-art control network that meets the
demands of real-time, high-throughput applications. The ControlNet network uses the
proven Common Industrial Protocol (CIP) to combine the functionality of an I/O network
and a peer-to-peer network providing high-speed performance for both functions.
The ControlNet network gives you deterministic, repeatable transfers of all missioncritical control data in addition to supporting transfers of non-time-critical data. I/O
updates and controller-to-controller interlocking always take precedence over program
uploads and downloads and messaging.
Cat. No.
1769-L32C
(single media)
Communication Connections
Rate
Supported, Max. Connector
Power
Dissipation
5 Mbps
Standalone system
Backplane
Backplane
Current (mA) at Current (mA) at Power Supply
24V
Distance Rating
5V
680 mA
40 mA
4 modules
680 mA
40 mA
4 modules
1769-L35CR
5 Mbps
(redundant media) Redundant media
Choose taps:
y 1786-TPR (T-tap right
angle)
y 1786-TPS (T-tap straight)
y 1786-TPYR (Y-tap right
angle)
y 1786-TPYS (T-tap straight)
y 1786-TCT2BD1 (IP67 tap)
4.36 W
20
DeviceNet Network
The DeviceNet network is an open, low-level network that provides connections between
simple industrial devices (such as sensors and actuators) and higher-level devices (such as
PLC controllers and computers). The DeviceNet network uses the proven Common
Industrial Protocol (CIP) to provide the control, configure, and data collection capabilities
for industrial devices.
If Your Application
Select
Communicates with other DeviceNet devices (I/O and
messages)
Requires explicit messaging
Uses the controller as a master or slave
1769-SDN DeviceNet
scanner
Uses the controller serial port for other
communications
Requires higher performance than the 1769-NET-DNI
interface
Communicates with other DeviceNet devices
(messaging only)
Uses the controller only as a slave
Does not use the controller serial port for other
communications
Trades lower cost for lower performance than the
1769-SDN scanner
Supports upload/download of controller project
Description
The scanner acts as an interface between
DeviceNet devices and the CompactLogix
controller. The scanner lets the controller:
read inputs from slave devices.
write outputs to slave devices.
send and receive messages.
1761-NET-DNI interface
The adapter:
Interfaces with as many as 30 Compact I/O
modules.
Communicates to other network system
components (typically a controller or scanner).
Cat. No.
Communication
Rate
Cable
1769-SDN
1761-NET-DNI
1769-ADN/B
125 Kbps
250 Kbps
500 Kbps
Power
Requirements,
Max.
Power
Power
Backplane Backplane Power Supply
Consumption Consumption Current (mA) Current (mA) Distance
Rating
at 24V
(W) at 5V
at 5V
(W) at 24V
90 mA @ 11V dc
110 mA @ 25V dc
(N.E.C. Class 2)
2.2
440 mA
mA
4 modules
1125V dc
4.8
0 mA
200 mA
na
Allen-Bradley part
number 1485C-P1-Cxxx 90 mA @ 24V dc (+4%) 2.5
(N.E.C. Class 2)
450 mA
mA
5 modules
90 mA @ 24V dc (+4%)
2.5
(N.E.C. Class 2)
450 mA
mA
4 modules
1769-ADN/A 7
CONTROLNET
L32C
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
Serial Network
Use this DF1 mode
Point to point
DF1 radio modem
DF1 master
DF1 slave
User mode (ASCII)
21
The serial port is compatible with RS-232 serial communication. The serial port supports
the DF1 protocol to communicate with other devices on the serial link.
For
Communication between a controller and other DF1-compatible devices using DF1 full-duplex protocol.
SCADA applications where controllers exchange data via radio transmission.
Control of polling and message transmission between the master and each slave using DF1 halfduplex polled protocol.
Using the controller as a slave station in a master/slave serial network using DF1 half-duplex protocol.
Communication between a controller and an ASCII device, such as a bar code reader.
The CompactLogix controller you choose determines the number of serial ports that
are available.
If You Need
Identified as
1769-L31
Channel Configuration
1769-ASCII
200 characters
500 mA
4 modules
22
Modbus Support
To use Logix5000 controllers on Modbus, you connect through the serial port and execute
a specific ladder logic routine. The controller project is available with RSLogix 5000
Enterprise programming software. For more information, see Using Logix5000 Controllers
as Masters or Slaves on Modbus Application Solution, publication CIG-AP129.
DH-485 Network
On the DH-485 network, the controller can send and receive messages to and from other
controllers on the network. The DH-485 connection does support remote programming
and monitoring via RSLogix 5000 software. However, excessive traffic over a DH-485
connection can adversely affect overall performance and can lead to timeouts and loss
in RSLogix 5000 configuration performance.
Important: Use Logix5000 controllers on DH-485 networks only when you want to add
controllers to an existing DH-485 network. For new applications with Logix5000
controllers, networks in the NetLinx architecture are the recommended networks.
You need a 1761-NET-AIC converter for each controller you want to put on the DH-485
network. You can have two controllers per one 1761-NET-AIC converter, but you need a
different cable for each controller. Connect one controller to port 1 (9-pin connector) and
one controller to port 2 (mini-DIN connector).
If you connect to this port
Port 1
DB-9 RS-232, DTE connection
Port 2
Mini-DIN 8 RS-232 connection
Step 3 - Select:
y A controller with the correct network
port
23
Select Controllers
CompactLogix controllers can monitor and control I/O across the 1769 CompactBus, as
well as over remote I/O links. CompactLogix controllers can communicate with computers
or other processors across RS-232-C (DF1/DH-485 protocol), DeviceNet, ControlNet, and
EtherNet/IP networks. To provide communication for a CompactLogix controller, install the
appropriate interface module or select a controller with integrated communications.
The multi-tasking operating system supports configurable tasks that can be prioritized.
One task can be continuous. The others must be periodic or event tasks. Each task can
have as many as 32 programs, each with its own local data and logic, allowing virtual
machines to operate independently within the same controller.
Specification
Description
4 modules
Power supply
1769-PA2
1769-PB2
1769-PA4
1769-PB4
Battery
1769-BA
Relay ladder
Function block diagram
Structured text
Sequential function chart
Programming cable
24
CompactLogix Controllers
Available
User
Memory
Cat. No. (Kbytes)
Power
I/O Banks Supply
Backplane Backplane
I/O
Number of
Nonvolatile Concurrent Communication Current
Module Supported, Distance
Current
Power
Memory 7 Tasks
(mA) at 5V (mA) at 24V Dissipation Capacity Max.
Ports
Rating
1769-L35E
1536 K bytes
64 Mbytes
CompactFlash
64 Mbytes
CompactFlash
1769-L32E
1769-L32C
1769-L31
90 mA
4.74 W
30
4 modules
RS-232, NAP,
ControlNet channels A 680 mA
and B
40 mA
4.36 W
30
4 modules
768 K bytes
64 Mbytes
CompactFlash
90 mA
4.74 W
16
4 modules
768 K bytes
64 Mbytes
CompactFlash
RS-232, NAP,
ControlNet channel A
680 mA
40 mA
4.36 W
16
4 modules
330 mA
40 mA
2.61 W
16
4 modules
512 K bytes
64 Mbytes
CompactFlash
CH0 - RS-232
DF1, DH-485, ASCII
fully isolated
38.4 kbps max
4
CH1 - RS-232
DF1, DH-485, ASCII
non-isolated
38.4 kbps max
_____ * 4000
_____ * 400
_____ * 2600
_____ * 8000
=
=
=
_____ bytes
(minimum 1 task)
_____ bytes
_____ bytes
_____ bytes
Non-volatile Memory
The 1784-CF64 card offers nonvolatile memory (flash) to permanently store a user
program and tag data on a controller. You can
y manually trigger the controller to save to or load from nonvolatile memory.
y configure the controller to load from nonvolatile memory on power up.
Controller Battery
The CompactLogix controller comes with one 1769-BA lithium battery.
1769-SG001F-EN-P -- November 2006
1769 Controller
Compatibility
I/O Modules
1732 ArmorBlock
1734 POINT
1734D POINTBlock
1738 ArmorPoint
1746 SLC
1756 ControlLogix
1769 Compact I/O
1771 PLC-5
1790 Compact Block LDX
1791D CompactBlock
1792D ArmorBlock MaXum
1794 FLEX I/O
1797 FLEX Ex
1798 FLEX Armor
1799 Embedded
25
The 1769 CompactLogix controller can control these distributed I/O modules.
1769-L32E, 1769-L35E
EtherNet/IP
Yes
Yes
Yes
Yes
No
Yes
No
No
No
No
no
Yes
Yes
No
No
1769-L32C, 1769-L35CR
ControlNet
No
Yes
Yes
Yes
No
Yes
No
No
No
No
no
Yes
Yes
No
No
DeviceNet 7
Yes
Yes
Yes
Yes
No
Yes
Yes
No
Yes
Yes
yes
Yes
No
Yes
Yes
A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge.
7To control I/O, use a 1769-SDN scanner to connect the controller to the DeviceNet network.
Insert a 1797-BIC and 1797-CEC module pair to isolate the FLEX Ex I/O modules from the non-intrinsically safe portion of the system.
EtherNet/IP
ControlNet
DeviceNet 7
RS-232 (DF1)
DH-485
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Yes
No
No
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
No
No
No
No
Yes
No
No
No
Yes
Yes
Yes
A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge.
7For DeviceNet access, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge).
Use PLC/SLC mapping.
26
EtherNet/IP
ControlNet
DeviceNet 7
RS-232 (DF1)
DH-485
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
NA
NA
No
Yes
Yes
No
No
No
No
NA
NA
No
Yes
Yes
Yes
Yes
Yes
Yes
NA
NA
NA
Yes
Yes
Yes
Yes
Yes
Yes
Yesa
Yes
Yes
NA
Yes
Yes
Yes
Yes
Yes
NA
NA
NA
A non-EtherNet/IP controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge.
7In the CompactLogix system, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge).
The Ethernet PLC-5 processor must be series C, firmware revision N.1 or later; series D, firmware revision E.1 or later; or series E, firmware revision D.1 or later.
The 1785-ENET Ethernet communication interface module must be series A, firmware revision D or later.
The PLC-5, SLC, and MicroLogix processors appear as I/O points to the Logix controller. Use the appropriate DeviceNet interface for the controller.
Use a 1747-L55x controller with firmware revision OS501 or later.
aThe PLC-2 controller requires a 1771-KG module for serial (DF1) communications.
The PLC-3 controller requires a 1775-KA module for serial (DF1) communications.
Communication Device
9355 RSLinx software
1770-KFD
1784-KTC, 1784-KTCx,
1784-KTCx15,
1784-PCIC(S), 1784-PCC
1784-PCIDS, 1784-PCD
1788-CN2DN
1788-EN2DN
1788-CN2FF
1203-CN1 ControlNet
module
1203-FM1/FB1
SCANport
EtherNet/IP
Yes
NA
ControlNet
Yes
NA
DeviceNet 7
Yes
Yes
RS-232 (DF1)
Yes
NA
DH-485
Yes
NA
NA
Yes
NA
NA
NA
NA
NA
Yes
NA
NA
Yes
NA
Yes
Yes
Yes
Yes
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
YES
NA
NA
NA
NA
NA
NA
NA
NA
A non-EtherNet/IP CompactLogix controller requires a 1761-NET-ENI interface to connect to an EtherNet/IP network. This interface is only a messaging bridge.
7For DeviceNet access, use either a 1769-SDN scanner (control I/O and send/receive messages) or a 1761-NET-DNI interface (messaging bridge).
Use the generic module configuration to configure the 1203-CN1 module and a CIP generic MSG instruction to communicate with the module.
Use a CIP generic MSG instruction to communicate with the 1203-FM1 SCANport module on a DIN rail that is remote to the controller. The remote DIN rail also requires a 1794-ACN(R)15 ControlNet adapter module.
Program Equipment
Phases
27
The PhaseManager option of RSLogix 5000 software gives you a state model for your
equipment. It includes the following components:
y Phase to run the state model
y Equipment phase instructions for programming the phase
y PHASE data type to link the phase to other equipment and higher-level systems
The PhaseManager option uses the following states.
The integrated FactoryTalk Alarms solution provides a single point of entry for alarm
configuration. You configure an alarm in RSLogix 5000 software (such as does the alarm
latch, does the alarm require an acknowledge, and when does the alarm trigger). The
alarm engine running in the controller pushes alarm information to the HMI via an alarm
server running in RSLinx Enterprise software. With FactoryTalk Alarms, you get:
y New communications method for alarms that pushes alarm status to the HMI rather
than polling. This improves network efficiency and reduces the controller overhead by
sending only those tags that are needed for an alarm.
y One common data base (the Logix controller) stores all tag and status information about
the alarm. You no longer duplicate alarming tags in the HMI. The tags automatically
show up in the HMI when RSLinx Enterprise software subscribes to the controller.
y Accurate status information about the alarm is stored in the controller. All HMI displays
in the system get the same alarm information from the controller.
y Improved time stamp accuracy. The controller generates the time stamps. This
eliminates inaccuracies because the time stamp is the actual time the alarm triggered
and not the time the HMI got around to reading a tag.
y Common historical database stores all alarm events for view by a Log viewer.
For integrated FactoryTalk Alarms, you need a:
y Logix5000 controller, firmware revision 16.0 or later.
y RSLogix 5000 software, version 16.0 or later.
y RSView SE software, CPR 9 or later.
1769-SG001F-EN-P -- November 2006
28
Method
Scheduled connection
Level of determinism
Unique to the ControlNet network
Description
A scheduled connection is unique to ControlNet communication. A scheduled connection
lets you send and receive data repeatedly at a predetermined interval, which is the
requested packet interval (RPI). For example, a connection to an I/O module is a scheduled
connection because you repeatedly receive data from the module at a specified interval.
Other scheduled connections include connections to:
y communication devices.
y produced/consumed tags.
On a ControlNet network, you must use RSNetWorx for ControlNet software to enable all
scheduled connections and establish a network update time (NUT).
Unscheduled connection
Deterministic
Used by both ControlNet and EtherNet/IP
networks
Unconnected message
Least deterministic
This controller
Supports
1769-L32C
1769-L35CR
1769-L32E
1769-L35E
Determine Connections
for I/O Modules
Connection
Rack-optimized
Determine Connections
for Produced and
Consumed Tags
Produced
Consumed
A Logix system uses connections to transmit I/O data. These connections can be direct
connections or rack-optimized connections.
Description
A direct connection is a real-time, data transfer link between the controller and an I/O
module. The controller maintains and monitors the connection between the controller and
the I/O module. Any break in the connection, such as a module fault or the removal of a
module while under power, causes the controller to set fault status bits in the data area
associated with the module.
Typically, analog I/O modules and specialty modules require direct connections.
For digital I/O modules, you can select rack-optimized communication. A rack-optimized
connection consolidates connection usage between the controller and all the digital I/O
modules on a rack (or DIN rail). Rather than having individual, direct connections for each
I/O module, there is one connection for the entire rack (or DIN rail).
Direct
29
The controller supports the ability to produce (broadcast) and consume (receive) systemshared tags over ControlNet or EtherNet/IP networks. Produced and consumed tags each
require connections. Over ControlNet, produced and consumed tags are scheduled
connections.
30
Determine Connections
for Messages
Uses a Connection
9
9
Your option=
9
=You can connect CIP generic messages, but for most applications we recommend you leave CIP generic messages unconnected.
Connections Example
31
Module Quantity
Total Connections
1
1
1
2
1
2
1
6
The controller uses 2 connections for a 1769-SDN module - one for communications to the controller and one for data.
32
Determine Total
Connection
Requirements
Connection Type
Remote EtherNet/IP
communication module
Configured as direct (none)
Configured as rack-optimized
The total connection requirements for a CompactLogix system include both local and
remote connections. The controller supports 100 connections.
Device Quantity
0 or
1
0
1
1
1
Total Connections
Step 4 - Select:
y If power consumption exceeds the
maximum for a single power supply,
install additional banks and power
supplies
33
Cat.
No.
Description
Operating
Voltage
Range
Power
Consumption, Current
Max.
Capacity
85265V ac
Compact 124/240V (wide range; no
1769-PA2 ac Expansion
jumper or DIP
Power Supply
switch required),
4763 Hz
100 VA @ 120V ac
130 VA @ 240V ac
Compact 24V dc
1769-PB2 Expansion Power
Supply
50 VA @ 24V dc
Inrush
Current,
Max.
Line Loss
Overvoltage
Ride Through Protection
250 mA
25 A @ 132V ac
10 source
impedance
40 A @ 265V ac
10 source
impedance
10 ms10 s
30 A @ 31.2V dc
10 ms10 s
25 A @ 132V ac
10 source
impedance
40 A @ 265V ac
10 source
impedance
5 ms10 s
30 A @ 31.2V dc
5 ms10 s
2.0 A @ 5V
0.8 A7 @ 24 V
2.0 A @ 5V
19.231.2V dc
24V dc User
Power
Capacity (0
to 55C)
0.8 A7 @ 24 V
85132V ac or
Compact 124/240V 170265V ac
1769-PA4 ac Expansion
(switch
Power Supply
selectable),
4763 Hz
200 VA @ 120V ac
240 VA @ 240V ac
Compact 24V dc
1769-PB4 Expansion Power
Supply
100 VA @ 24V dc
4.0 A @ 5V
2.0 A @ 24 V
4.0 Aa @ 5V
19.232V dc
Power
Supply
Distance
Rating
8 modules
2.0 A @ 24 V
34
35
If you decide to use a DIN rail, use steel, 35 x 7.55mm DIN rails (A-B part number 199DR1; 46277-3; EN 50022). The DIN rails for all CompactLogix system components must
be mounted on a common, conductive surface to ensure proper electromagnetic
interference (EMI) performance.
36
1769-L32 x, 1769-L35 x
CompactLogix Controller
Dimensions
1769-L31 CompactLogix
Controller Dimensions
37
Visualization Products
Visualization products, together with Logix for control and NetLinx architecture for
communication, make up Rockwell Automations Integrated Architecture strategy. The
visualization strategy combines Rockwell Automations expertise in Allen-Bradley
electronic operator interface and industrialized personal computer hardware with
Rockwell Softwares supervisory control software. Current visualization products include:
y RSView Enterprise Series software.
y PanelView Plus operator interface.
y VersaView industrial computers and monitors.
y VersaView CE industrial computer.
RSView Enterprise Series software from Rockwell Software is a line of HMI software
products designed with a common look, feel, and navigation to help speed HMI
application development and training time. With RSView Enterprise Series 3.0, you can
reference existing Logix data tags. Any changes made to these referenced tags are
automatically inherited by RSView software.
y RSView Studio software lets you create applications in a single design environment. It
configures RSView Supervisory Edition, RSView Machine Edition, VersaView CE, and
PanelView Plus applications. It supports editing and reusing projects for improved
portability between embedded machine and supervisory HMI systems.
y RSView Machine Edition (ME) software is a machine-level HMI product that supports
both open and dedicated operator interface solutions. It provides a consistent operator
interface across multiple platforms (including Microsoft Windows CE, Windows 2000/XP,
and PanelView Plus solutions), and is ideal for monitoring and controlling individual
machines or small processes.
y RSView Supervisory Edition (SE) software is an HMI software for supervisory-level
monitoring and control applications. It has a distributed and scalable architecture that
supports distributed-server/multi-user applications. This highly scalable architecture can
be applied to a standalone, one-server/one-user application or to multiple users
interfacing with multiple servers.
RSView Enterprise
Series Products
Cat. No.
RSView Studio
Description
9701-VWSTENE
9701-VWSTMENE
9701-VWMR015AENE
9701-VWMR030AENE
9701-VWMR075AENE
9701-VWSCWAENE
RSView SE client
9701-VWSCRAENE
9701-VWSS025AENE
9701-VWSS100AENE
9701-VWSS250AENE
9701-VWSS000AENE
9701-VWB025AENE
9701-VWB100AENE
9701-VWB250AENE
9701-VWSB000AENE
38
The PanelView Plus terminal is ideal for applications that need to monitor, control, and
display information graphically, allowing operators to quickly understand the status of
their application. PanelView Plus terminals come with RSView Studio software and have
embedded RSView Machine Edition software functionality. PanelView Plus terminals
combine the best features from the popular Allen-Bradley PanelView Standard and
PanelView e operator-interface products and adds new functionality.
y Multi-vendor communications
y Trending
y Expressions
y Data logging
y Animation
y RSView Studio software direct browsing of RSLogix 5000 addresses
VersaView Industrial
Computers and Monitors
VersaView products are a family of industrial computer and monitor solutions, comprised
of integrated display computers, workstations, non-display computers, and flat panel
monitors. VersaView products offer effortless management of changing technology, a
rugged but cost-effective design, and easier product configuration. All VersaView products
provide the latest industrial solution available, optimized for visualization, control,
information processing, and maintenance application.
VersaView CE Industrial
Computers
Step 7 - Select:
y The appropriate package of RSLogix
5000 Enterprise Series software and any
options
y Other software packages for your
application
y An appropriate operator interface
If you have
EtherNet/IP interface
(set the IP address)
ControlNet interface
DeviceNet interface
39
Order
9324 series
(RSLogix 5000 Enterprise Series software)
Use Lite Edition or higher to support motion.
If no motion, you can use the Service Edition
or Mini Edition.
RSLinx software
or
BOOTP/DHCP server utility to set IP
addresses
(RSLinx Lite and BOOTP server come with
RSLogix 5000 Enterprise Series software)
9324 series
(RSLogix 5000 Enterprise Series software)
or
9324-RLD300NXENE (RSLogix 5000
Enterprise Series software plus RSNetWorx
option)
40
Programming Software
Value
Personal computer
Software requirements
RAM
100 MB of free hard disk space (or more based on application requirements)
Video requirements
41
Mini Edition
Standard/ NetWorx
Concurrent
Professional
Lite Edition
Standard Edition
Edition 9324-
License
Edition 9324-
9324-RLD250 xxE
9324-RLD300 xx E
RLD300NX xxE
9324-RLD600 xx F RLD700NXxxE
Available Features
9324-RLD000xxE
9324-RLD200 xx E
All
CompactLogix
FlexLogix
CompactLogix
FlexLogix
All
All
All
All
Upload/download
and view
Full support
Full support
Full support
Full support
Full support
Full support
Upload/download
and view
Upload/download
Full support
Available separately
Upload/download
Upload/download
Available separately Available separately
Full support
Full support
Upload/download
and view
Upload/download
Full support
Available separately
Upload/download
Upload/download
Available separately Available separately
Full support
Full support
Upload/download
and view
Upload/download
Full support
Available separately
Upload/download
Upload/download
Available separately Available separately
Full support
Full support
PhaseManager
9324-RLDPME
Upload/download
Upload/download
Upload/download
Upload/download
Upload/download
Available separately Available separately Available separately Available separately
Included
Included
GuardLogix Safety
9324-RLDGLXE
Upload/download
and view
NA
NA
Upload/download
Upload/download
Available separately Available separately
Included
Included
Upload/download
and view
Upload/download
Full support
Full support
Full support
Full support
Full support
Graphical trending
Full support
Full support
Full support
Full support
Full support
Full support
Full support
DriveExecutive Lite
9303-4DTE01ENE
Available separately
Included
Included
Included
PIDE autotune
9323-ATUNEENE
Available separately
Included
Included
Included
Included
Included
Included
Available
separately
Available
separately
Available separately
NA
NA
Available
separately
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
FuzzyDesigner
9324-RLDFZYENE
NA
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Lite included
Lite included
Lite included
Lite included
Lite included
Lite included
OEM included
Available
separately
Included
RSLogix Architect
9326-LGXARCHENE
Available separately
Available
separately
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Included
Available
separately
Included
Available separately
Upgrades
To Standard: 9324RLD0U3xxE
To Full: 9324RLD0U6xxE
To Professional:
9324-RLD0U7xxE
To Standard: 9324RLD2U3xxE
To Professional:
9324-RLD2U7xxE
To Full: 9324RLD25U6xxE
To Professional:
9324-RLD25U7xxE
NA
Node Locked to
Concurrent License:
9324-RLD6U6FxxU NA
To Professional:
9324-RLD6U7xxE
Replace xx in the catalog number with the appropriate language designation: ZH=Chinese, EN=English, FR=French, DE=German, IT=Italian, JP=Japanese, KO=Korean, PT=Portuguese, and ES=Spanish.
Service Edition supports controllers running firmware revision 12 and later.
Full Edition supports controllers running firmware revision 10 and later.
A multiple language editor package is available as 9324-RLDMLPE. It contains the function block, sequential function chart, and structured text editors at a reduced price.
7RSNetWorx for ControlNet software is 9357-CNETL3. RSNetWorx for DeviceNet software is 9357-DNETL3. RSNetWorx for EtherNet/IP software is 9357-ENETL3. They are available together as 9357-ANETL3.
aThe multiple language editor package (9324-RLDMLPE) is not the same as an upgrade, but it extends the programming languages to match those in a Full package.
As of RSLogix 5000 programming software, version 15.
As of RSLogix 5000 programming software, version 16.
42
RSLinx Software
Description
Personal computer
Operating system
RAM
32 MB of RAM min
64 MB or more of RAM recommended
Video requirements
In most cases, RSLinx Lite software comes bundled with controller programming software
packages.
You can also download RSLinx Lite for free from the Software Updates link on the Get
Support Now website at http://support.rockwellautomation.com
43
RSLinx Products
RSLinx Lite
RSLinx Single Node
RSLinx OEM
RSLinx Professional
RSLinx Gateway
RSLinx SDK
RSLinx Enterprise
44
Network Configuration
Software
RSNetWorx software is the configuration tool for your control network. With RSNetWorx
software you can create a graphical representation of your network configuration and
configure the parameters that define your network.
Use RSNetWorx software for:
y ControlNet software to schedule network components. The software automatically
calculates network bandwidth for the entire network, as well as the bandwidth used by
each network component. You must have RSNetWorx software to configure and
schedule ControlNet networks.
y DeviceNet software to configure DeviceNet I/O devices and create a scan list. The
DeviceNet scanner stores the configuration information and scan list.
y EtherNet/IP software to configure EtherNet/IP devices using IP addresses or host
names.
45
EtherNet/IP
ControlNet
DeviceNet
Operating system
RAM
32 MB of RAM min
More memory is required for large networks
Minimum: 108 MB (includes program and hardware files) Minimum: 115 MB (includes program and hardware files) Minimum: 190 MB (includes program and hardware files)
Full support: 115...125 MB (includes program, online
Full support: 168...193 MB (includes program, online
Full support: 230...565 MB (includes program, online
help, tutorial, and hardware files)
help, tutorial, and hardware files)
help, tutorial, and hardware files)
Description
RSNetWorx Software for ControlNet
RSNetWorx Software for DeviceNet
RSNetWorx Software for Ethernet/IP
RSNetWorx Software for ControlNet, Ethernet/IP and
DeviceNet
9357-CNETMD3E
9357-DNETMD3E
9357-ENETMD3E
9357-ANETMD3E
46
RSLogix Emulate 5000 software (9310-WED200ENE) is the emulation package for the
Logix5000 controllers. RSLogix Emulate 5000 software, used in conjunction with RSLogix
5000 software, lets you run and debug your application code while at your computer. In
addition, RSLogix Emulate 5000 software lets you test HMI screens, developed in RSView
software for example, without the need to connect to a real controller.
You can set tracepoint and breakpoint instructions (ladder diagram only) in your
application code, use traces, and also vary the execution speed of the emulator. RSLogix
Emulate 5000 software supports all the programming languages (ladder diagram, function
block diagram, structured text, and sequential function chart). RSLogix Emulate 5000
software does not allow for control of real I/O.
Use RSLogix Emulate software for:
y troubleshooting.
Stop the process whenever a selected rung goes true, effectively freezing the process at
the instant that any error occurs.
y ladder logic scanning options.
Scan your ladder logic continuously, one program scan at a time, rung-by-rung, or select
a specific block of rungs to emulate. Selecting a block of rungs lets you isolate a
particular section of the program for testing purposes. You can also set trace points to
trace application program tags and set break points to halt program execution at
predetermined locations.
Description
Personal computer
Operating system
RAM
Video requirements
RSLogix Emulate 5000 software includes RSTestStand Lite software. RSTestStand Lite
software lets you create virtual operator consoles that can help test your application code.
RSTestStand Lite software can be upgraded to the standard version by ordering catalog
number 9310-TSTNDENE.
RSLogix Emulate 5000 and RSTestStand Lite software are included with RSLogix 5000
Professional software.
1769-SG001F-EN-P -- November 2006
47
Summary
Use a spreadsheet to record the amount and type of devices your CompactLogix system
needs. For example, this sample system...
Number of Modules
12
3
1769-IA816
1769-IF4XOF2
16
4
1769-IF4XOF2
DeviceNet scanner
DeviceNet adapter
remote 24V dc digital
outputs
remote contact outputs
NA
NA
1769-SDN
1769-ADN
NA
NA
1
1
1
(part of same module from
analog input
requirements)
1
1
30
1769-OB16
16
1769-OW6
1
2 local 1769 I/O modules
1 1769-SDN scanner
1 remote 1769-ADN
adapter
3 remote 1769 I/O
modules
Controller 1 subtotal
Controller 2 - 1769-L31
Device
Number of Modules
28
NA
1769-OB16
1769-HSC
16
NA
2
1
NA
1761-NET-ENI
NA
Controller 2 subtotal
3 I/O modules
1 1761-NET-ENI interface
1769-SG001F-EN-P -- November 2006
48
As you select devices for your CompactLogix system, keep these guidelines in mind.
9
Step
Remember to Select
y I/O modules
y Wiring system (if you want to use a wiring system instead of
the terminal block that comes with module)
y PanelConnect modules and cables if connecting input
modules to sensors
y Expansion cables if planning multiple banks of I/O modules
y Networks
y Communication interfaces
y Associated cable(s) and network equipment
Select controllers.
Select software.
As you determine placement of the modules you selected, use the worksheets on the next
pages to calculate power requirements and to record placement of modules. Make a copy
of this worksheet for each controller.
49
Cat. No.
Number of Modules
1769-ARM
60
1769-ASCII
420
1769-BOOLEAN
220
1769-HSC
425
1769-IA8I
90
1769-IA16
115
1769-IF4
120
60
1769-IF4I
145
95
1769-IF4XOF2
120
160
1769-IF8
120
70
1769-IG16
120
1769-IM12
100
1769-IQ16
115
1769-IQ16F
110
1769-IQ32
170
1769-IQ32T
170
1769-IQ6XOW4
105
50
1769-IR6
100
45
1769-IT6
100
40
1769-OA8
145
1769-OA16
225
1769-OB8
145
1769-OB16
200
1769-OB16P
160
1769-OB32
300
1769-OB32T
220
1769-OF2
120
120
1769-OF4CI
145
140
1769-OF4VI
145
75
1769-OF8C
145
160
1769-OF8V
145
125
1769-OG16
200
1769-OV16
200
1769-OV32T
200
1769-OW8
125
100
1769-OW8I
125
100
1769-OW16
205
180
1769-ADN
500
1769-SDN
440
1769-ECL
1769-ECR
1769-PA2
1769-PB2
1769-PA4
1769-PB4
2A @ 5V dc
0.8A @ 24V dc
2A @ 5V dc
0.8A @ 24V dc
4A @ 5V dc
2A @ 24V dc
4A @ 5V dc
2A @ 24V dc
250mA
na
na
na
50
1769-______ controller
left
left
left
left
1769-______ power supply
right
right
right
right
right
right
right
right
right
Totals
You only need an end cap if this is the last bank in the system.
mA
mA
51
Bank 2
Placement (left or right of power
supply)
Module
left or right
left
left
left
left
left
left
left
left
right
right
right
right
right
right
right
right
Totals
mA
mA
You only need an end cap if this is the last bank in the system. Place an end cap on the end opposite of the expansion cable.
Bank 3
Placement (left or right of power
supply)
Module
left or right
left
left
left
left
left
left
left
left
right
right
right
right
right
right
right
right
Totals
mA
mA
52
Notes
53
Notes
ControlLogix, GuardLogix, CompactLogix, FlexLogix, PowerFlex 700S with DriveLogix, SoftLogix5800, MicroLogix, PLC-5, PLC-3, PLC-2, SLC, DH+, Allen-Bradley,
FLEX Ex, PanelView, RSLogix, RSLogix 5000 Enterprise Series, RSNetWorx, RSView, Rockwell Software, SERCOS interface, Ultraware, VersaView are trademarks of
Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Copyright 2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.