Sie sind auf Seite 1von 55

Introduction to Improving Energy

Efficiency in Chiller Systems


Riyaz Papar, PE, CEM
Director, Global Energy Services
Hudson Technologies Company
rpapar@hudsontech.com
November 2013

Hudson Technologies

Acknowledgments

Texas Industries of the Future (TXIOF)


Texas State Energy Conservation Office (SECO)

Energy Industries in Ohio

Joe Longo & Derrick Shoemake, Hudson


Technologies

Hudson Technologies

Webinar Agenda

The Systems Approach

Fundamentals of Refrigeration

Chiller Plant Actual Operating Performance

Predictive and Preventive Maintenance


BestPractices

Energy Conservation Measures (ECMs)

Conclusions

Hudson Technologies

Chiller System Energy Cost?

1,000 Refrigeration Tons chiller plant load


Chiller System performance = 0.75 kW/ton
Bundled power cost = $0.085/kWh
600,000
500,000
Operating Cost ($)

400,000
300,000
200,000
100,000
4 months

6-8 months

All year round

Operating hours
4

Hudson Technologies

The Systems Approach

Hudson Technologies

The Systems Approach

Establish current system conditions,


operating parameters, and system energy use

Investigate how the total system presently


operates

Identify potential areas where system


operation can be improved

Analyze the impacts of potential


improvements to the plant system

Implement system improvements that meet


plant operational and financial criteria

Continue to monitor overall system


performance
6

Hudson Technologies

A Chilled Water Plant Systems Approach

Hudson Technologies

Main Driving Force for Change

Energy
Reliability
Maintenance
Productivity
Quality
Cost avoidance
Emissions reductions

Hudson Technologies

Fundamentals of
Refrigeration

Hudson Technologies

The Refrigeration Cycle

P [psia]

10

R134a

Condensation / SubCooling

10

105F

2
Expansion

Compression

40F
Ev aporation (Boiling)

0.2

10

0.6

0.4

0.8

25

50

75

100

125

150

h [Btu/lbm]
State Point
10

Hudson Technologies

Single Stage Chiller System


HGBP (Hot Gas ByPass)

Compressor
Condenser

Cooling Water

Evaporator

Chilled Water

HGBP

11

Hudson Technologies

A Centrifugal
A Water-Cooled
Chiller Chiller System

Condenser

Compressor

Evaporator (Chiller Barrel)

12

Hudson Technologies

Two Stage Chiller System


HGBP

Compressor
Condenser

Cooling Water

Evaporator

Economizer

13

Chilled Water

HGBP
(Hot Gas ByPass)

Hudson Technologies

LiBr-Water Absorption Chillers

14

Hudson Technologies

The Air, Water and Refrigerant Cycle

The Systems Approach


15

Hudson Technologies

Chiller Plant - Actual


Operating Performance

16

Hudson Technologies

Chiller Capacity

Definition of Refrigeration Ton (RT)


The

amount of thermal energy to be


removed from 1 Ton (2,000 lbs) of
water at 32F to make it into ice at 32F
in one day (24 hr) is known as 1 RT

1 RT = 12,000 Btu/hr = 3.517 kW


Chiller capacity (size or tonnage) is the
amount of full load cooling capacity
provided by the chiller at certain design
conditions
17

Hudson Technologies

Chiller Performance Metrics

Most standard rating in the US - kW/RT


(hp/RT)

Amount of compressor power (kW or


hp) required to produce 1 RT of cooling
or refrigeration

Compressor Power (kW )


kW / RT
Cooling Load ( RT )

18

Hudson Technologies

Chiller Full Load Design Specifications

Obtained from the Chiller Manufacturer

Chiller ID: Chiller #6

Chiller Manufacturer: ZZZZZZZ

Year Commissioned: 1990

Chiller Type: Constant Speed Centrifugal

Model Number: XXXXXXXXXX

Serial Number: AAAAAAAA

Refrigerant Type: R-134a

Capacity (Tonnage): 2,000

Efficiency (kW/Ton): 0.625

IPLV / NPLV: .541

Full Load Amps (FLA): 198

Volts: 4160

Evaporator Entering Water Temperature: 54.37F

Evaporator Leaving Water Temperature: 44F

Condenser Entering Water Temperature: 85F

Condenser Leaving Water Temperature: 94.4F

Evaporator Delta Temperature: 10.37F

Condenser Delta Temperature: 9.4F

Evaporator GPM: 4,627

Condenser GPM: 6,000

Evaporator Pressure Drop (psig): 9.9

Condenser Pressure Drop (psig): 8.1

19

Hudson Technologies

Overall Chiller Plant Performance

Information required

Total tonnage
Total kW

Compressor Power
Pumping Power
Cooling Tower Fan Power
Other (as defined in the scope)

Plant Performance

20

kW
n
Chiller Tons
m
Hudson Technologies

Overall Chiller Plant Performance

21

Hudson Technologies

Chiller Plant Efficiency Metrics

Overall chiller plant performance

Individual chiller efficiency

Lift is defined as the difference between the refrigerant


saturated condensing and evaporating temperatures

Individual compressor isentropic efficiency

Chiller tonnage
Compressor kW

Individual Chiller Lift

Total tonnage
Total kW (including chillers and auxiliaries)

Suction and discharge temperatures


Suction and discharge pressures

Individual heat exchanger effectiveness

Approach temperatures
T on chilled water and cooling tower water
22

Hudson Technologies

Predictive & Preventive


Maintenance
BestPractices

23

Hudson Technologies

First Things First Fluid Management

Understanding Cause and Effect is very


important for Root Cause Analysis
This enhances system reliability and reduces
unplanned shutdown
Significant savings in Maintenance costs
Most Maintenance BestPractices are testingbased

Refrigerant, Oil and Water Testing


Rotating equipment monitoring

Vibration analysis

Eddy-current testing

In chiller systems, contaminants affect


efficiency & capacity

Chemistry Based Solutions


24

Hudson Technologies

Blood Chemistry

25

Hudson Technologies

Chiller Chemistry

26

Hudson Technologies

Refrigerant Analysis Criteria

Moisture
Oil
Particulate
Chlorides
Acid
Purity
Non-Condensables
Other Contaminants

27

Hudson Technologies

Nonferrous cutting wear

Severe sliding wear

Copper alloy
sliding wear

Ferrography
Oil Analysis

28

Hudson Technologies

Water Testing and Analysis


Cooling Tower Water testing and analysis

Open loop evaporation of water


Control of corrosion, scale and biological activity
Material of construction plays a very important role
Testing conducted for pH, TDS, Conductivity, Hardness,
Alkalinity, Chlorides, Silica, Bacteria, etc.

Chilled Water testing and analysis


Closed loop generally less issues
Lower temperatures

Working with a water chemist / treatment


company
Periodic testing program
29

Hudson Technologies

Energy Conservation
Measures (ECMs)

30

Hudson Technologies

3 Methods of Maximizing Chiller Plant Efficiency

Preventive

Restorative

Identify problems before they become expensive


(cost avoidance)
Maintain optimum chiller plant efficiency
Identify heat transfer problems, i.e., off-design
water flow, fouling or scaling, etc.
Remove non-condensable gases
Maintain proper refrigerant levels

Opportunity

Identify optimal chilled water set points


Proper chiller sequencing and load balancing
Proper tower basin water management
Peak demand management
Condition-based maintenance versus scheduled
preventive maintenance
31

Hudson Technologies

Implement ECWT management


Optimize settings for ChWST
Eliminate all refrigerant leaks
Maintain design water flow rates
in evaporator / condenser
Eliminate refrigerant stacking
Remove non-condensable gases
and moisture
Reclaim refrigerant
32

No Cost / Low Cost


ECMs

List of ECMs

Hudson Technologies

Clean fouled and scaled heat


exchangers
Sequence multiple chillers to optimize
efficiency
Maintain compressor isentropic
efficiency
Improve drive efficiency
Investigate application of variable
frequency drives
Undertake peak load management
strategy
Install water-side economizers
33

Higher Cost
ECMs

Medium Cost
ECMs

List of ECMs (continued)

Hudson Technologies

Implement ECWT Management

ECWT Entering Cooling Water Temperature

Approach

The approach is the difference in temperature between


the cooled-water temperature and the entering-air wet
bulb temperature
Since the cooling towers are based on the principles of
evaporative cooling, the maximum cooling tower
efficiency depends on the wet bulb temperature of air

Wet Bulb

Wet bulb temperature is the lowest temperature that


can be reached by the evaporation of water only
It is determined by the atmospheric pressure, ambient
temperature and the relative humidity
34

Hudson Technologies

Concept of Lift

35

Hudson Technologies

Implement ECWT Management

80F ECWT drops to 70F ECWT


kW/ton drops from 0.7 to 0.47 (33% improvement)

36

Hudson Technologies

Optimize Settings for ChWST

ChWST Chilled Water Supply Temperature

Approach / RAT

The approach (RAT) is the difference in temperature


between the chilled-water supply temperature and the
refrigerant saturated temperature in the evaporator
It provides the driving force to transfer the heat from
the water to the refrigerant

Load control

Cooling required is controlled by bypassing chilled


water flow
Alternate methodology variable pumping

Primary
Secondary
37

Hudson Technologies

Optimize Settings for ChWST

Chiller Performance (kW/RT)

0.475
0.45
0.425
0.4
0.375
0.35
0.325
0.3
41

42

43

44

45

46

47

CWST (F)

38

Hudson Technologies

Clean Fouled and Scaled Evaporator

Fouling in the evaporator / cooler

Refrigerant-side
Water-side

Refrigerant-side fouling Excess Oil

Refrigerant-side fouling Water

Water-side fouling

High makeup (leaks) in the closed loop system


Iron fouling from corrosion, microbiological growth and
scale due to insufficient chemical protection

39

Hudson Technologies

Fouled/Scaled Evaporator

Iron Oxide Scaled


Condition
After tube brushing

40

Hudson Technologies

Fouled/Scaled Condenser
March

July

Sept

41

Hudson Technologies

Reclaim Refrigerant

Over time and operations, the refrigerant in the


chiller gets contaminated and results in

Fouling of heat exchangers


Reductions in heat transfer coefficients

The process of recovering the refrigerant and


bringing it back to AHRI-700 specification
standard is known as Reclamation
Reclaiming a refrigerant improves overall
operating performance and in most cases
increases chiller tonnage (capacity)
Periodic sampling and testing of refrigerants in
chiller systems is key to ensuring that the chiller
chemistry is well maintained

Analogous to maintaining water chemistry in boilers

42

Hudson Technologies

Reclaim Refrigerant

Moisture in
refrigerant
Presence of Oil
in refrigerant
Particulate in
refrigerant
43

Hudson Technologies

Impact on Capacity

Reclaim Refrigerant
SUMMARY of RESULTS & COST SAVINGS
Total System

Design P/L

Design F/L

Refrigerant

Tons = 1,502 [RT]

1,502 [RT]

2,002 [RT]

Design: R134a

com pHP = 1,219 [HP]

1,503 [HP]

2,360 [HP]

Currently Used:

HPTon = 0.81 [BHP/RT]

1.001 [HP/Ton]

1.18 [BHP/RT]

Steam Rate = 12.02 [lb/hr-HP]

R134a

12.03 [lb/hr-HP]

Superheat Capacity Penalties

NC% = 0.0 [% ]
Balance Syste m = 0.0 [% ]

Com ponent Balances

Capacity Loss (RT)

2.8

0.1

Evaporator

Balance Evap = 0.0 [% ]


Balance SubCoole r = ???? [% ]

Potential Savings Opportunities


Pressure Ratio (current):

Annual Energy Costs


Steam Cost = 14.48 [$/1000lb]

2.6

Evaporator

Condenser

System

New Ratio

2.3

2.6

2.3

Savings (% )

13.1

0.0

13.1

Hours = 4,000 [Hr]


LFC = 0.80 [kW/ton]
Cost ($)

NC Penalty ($)

678,871

44

Impact of Oil, Particulate


& Moisture in refrigerant
on energy efficiency &
Hudson Technologies
costs

Eliminate Refrigerant Stacking

Refrigerant stacking impacts heat transfer efficiency


in both the evaporator and condenser - higher
kW/Ton and energy costs

Leads to reduced compressor capacity

Chiller surging or stalling

Shut down on low refrigerant temperature


(pressure)

45

Hudson Technologies

Refrigerant Stacking

Raise
ECWT
46

Hudson Technologies

Sequence Multiple Chillers to Optimize Efficiency

All chillers will have an optimal operation range


(best efficiency point)

When multiple chillers are operating, the overall


plants composite operating curve maybe very
different from the individual chillers curve

It is important to know how each of the chillers


operate under different load conditions

Pick the best chiller operating combination for


the current operating conditions Dynamic
Optimization problem (NOT Easy)
47

Hudson Technologies

Investigate Application of Variable


Frequency Drives (VFD)

Replacing old chillers with newer energy efficient systems


most new packaged chillers will come with a VFD option

VFDs take advantage of lower ambient temperatures (lower


lift) and correspondingly lower cooling loads (lower
refrigerant flow rates)

VFD pumps and fans can play a very important role in


reducing total system energy consumption

VFD efficiency is extremely high (99%) and more


importantly, it offers a benefit on the drive side by providing

Soft start capability


Power factor correction
48

Hudson Technologies

Comparison of Constant Speed & VFD


Chiller Performance

Chiller Performance (kW/RT)

0.75
0.7
Constant Speed

0.65

Variable Frequency

0.6
0.55
0.5
0.45
0.4
0.35
0.3
20

30

40

50

60

70

80

90

100

Cooling Load (% )

49

Hudson Technologies

Install Water-side Economizers

This ECM is applicable only in certain


geographical areas but can have a huge
impact on energy savings

Installing a water-side economizer allows for


free cooling during times of the year when
the outdoor ambient conditions allow for
very low wet-bulb temperatures

The cooling tower water provides all (or


some portion) of the chilled water plant load
and reduces the amount of chillers required
50

Hudson Technologies

Undertake a Peak Load Management Strategy

Peak demand charges can become excessive


depending on chiller plant management and
operational strategy

There are 3 ways to manage peak demand


regarding chillers
Thermal energy storage
Optimize chiller efficiency to lower kW usage of running
chillers
Take a chiller off-line

51

Hudson Technologies

Conclusions

52

Hudson Technologies

Next Steps

Develop a simple schematic of your Chiller Plant /


Refrigeration system and define the boundaries

Use a systems approach to complete an initial assessment to


understand operations and load profile

Undertake a simple gap analysis to identify any potential


improvement opportunities

Evaluate each ECM and prioritize based on quantified savings


opportunities

Put a program in place to ensure that there is proper


Predictive and Preventive Maintenance BestPractices

Implement an effective Chiller Plant Performance Monitoring,


Diagnostics and Optimization system
53

Hudson Technologies

1-Day Training Workshop


Introduction to Energy Efficiency in
Chiller Plant Systems
December 17, 2013
8 am 4 pm
Houston Business RoundTable
5213 Center Street
Pasadena, TX 77505
Facilitator: Riyaz Papar, PE, CEM
Hudson Technologies Co.
Registration Information:
Kathey Ferland
Texas Industries of Future
kferland@mail.utexas.edu
http://TexasIOF.ceer.utexas.edu

54

Hudson Technologies

Contact Information
Technical Information
Riyaz Papar, PE, CEM
Hudson Technologies Co.
rpapar@hudsontech.com
http://www.hudsontech.com

Program Information
Kathey Ferland
Texas Industries of Future
kferland@mail.utexas.edu
http://TexasIOF.ceer.utexas.edu

55

Hudson Technologies

Das könnte Ihnen auch gefallen