Beruflich Dokumente
Kultur Dokumente
TOC - 1
Section 00 00 10
Table of Contents
DIVISION 03 - CONCRETE
03 01 00
CONCRETE SURFACE REPAIR SYSTEMS
03 11 00
CONCRETE FORMWORK
03 15 00
CONCRETE ACCESSORIES
03 15 14
STRIP-TYPE WATERSTOPS
03 20 00
CONCRETE REINFORCEMENT
03 30 00
CAST-IN-PLACE CONCRETE
03 60 00
GROUT
03 64 00
CONCRETE REPAIR CRACK INJECTION
DIVISION 05 - METALS
05 12 00
STRUCTURAL STEEL
05 50 00
METAL FABRICATIONS
05 51 00
METAL STAIRS
05 52 13
PIPE AND TUBE RAILINGS
05 53 00
METAL GRATINGS AND PLANK
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 21 01
METAL BUILDING INSULATION
07 72 33
ALUMINUM HATCHES
07 92 00
JOINT SEALANTS
DIVISION 08 OPENINGS
08 11 13
STEEL DOORS AND FRAMES
08 71 00
DOOR HARDWARE
08 90 00
LOUVERS AND VENTS
DIVISION 09 - FINISHES
09 90 00
PAINTING AND PROTECTIVE COATINGS
DIVISION 10 SPECIALTIES
10 44 16
FIRE EXTINGUISHERS
DIVISION 13 SPECIAL CONSTRUCTION
13 34 19
METAL BUILDING SYSTEMS
DIVISION 23 HVAC
23 05 00
COMMON WORK RESULTS FOR MECHANICAL
23 05 17
SLEEVES AND SLEEVE SEALS FOR HVAC PIPING AND EQUIPMENT
23 05 29
HANGERS AND SUPPORTS FOR MECHANICAL PIPING AND EQUIPMENT
23 05 53
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
23 05 93
TESTING, ADJUSTING, AND BALANCING
23 07 00
DUCTWRAP INSULATION
23 07 13
MECHANICAL INSULATION
23 09 00
INSTRUMENTATION AND CONTROL FOR HVAC
23 23 00
REFRIGERANT PIPING
23 31 13
METAL DUCTS
23 33 00
AIR DUCT ACCESSORIES
Project No. 12078390
Durant State Fish Hatchery Phase 1
TOC - 2
Section 00 00 10
Table of Contents
23 37 13
23 81 26
23 83 33
DIVISION 26 - ELECTRICAL
26 05 00
COMMON WORK RESULTS FOR ELECTRICAL
26 05 14
WIRING DEVICES
26 05 15
ELECTRIC MOTORS
26 05 19
LOW VOLTAGE ELECTRICAL POWER CONDUCTORS & CABLES
26 05 26
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 29
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
26 05 33
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
26 05 43
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
26 05 53
IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 72
OVERCURRENT PROTECTIVE DEVICE SHORT-CIRCUIT STUDY
26 05 73
OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY
26 05 74
OVERCURRENT PROTECTIVE DEVICE ARC-FLAS STUDY
26 09 43
FIBER OPTIC NETWORK
26 22 00
LOW-VOLTAGE TRANSFORMERS
26 24 13
SWITCHBOARDS
26 24 16
PANELBOARDS
26 28 13
FUSES
26 28 16
ENCLOSED SWITCHES AND CIRCUIT BREAKERS
26 29 33
SOLID STATE REDUCED VOLTAGE STARTERS
26 41 13
LIGHTNING PROTECTION FOR STRUCTURES
26 43 13
SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
26 51 00
INTERIOR LIGHTING
26 56 00
EXTERIOR LIGHTING
26 67 05
COMMUNICATION CABLE AND EQUIPMENT
26 90 00
GENERAL INSTRUMENTATION AND CONTROLS
26 90 10
PROCESS AND ANALYTICAL INSTRUMENTS
26 90 20
PROGRAMMABLE LOGIC CONTROLLERS
DIVISION 31 - EARTHWORK
31 05 19
GEOTEXTILE FILTER FABRIC
31 11 00
SITE PREPARATION
31 22 13
SUBGRADE PREPARATION
31 22 19
GRADING
31 23 16
EXCAVATION
31 23 19
DEWATERING
31 23 23.13 FILL AND BACKFILL
31 23 23.16 TRENCH BACKFILL
31 23 23.33 FLOWABLE FILL
31 32 00
SOIL EROSION STABILIZATION
31 50 00
EXCAVATION SUPPORT SYSTEMS
31 51 00
TEMPORARY DAMMING SYSTEMS
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 00
BASE COURSE
Project No. 12078390
Durant State Fish Hatchery Phase 1
TOC - 3
Section 00 00 10
Table of Contents
32 13 13
32 31 13
32 92 19
DIVISION 33 - UTILITIES
33 11 11
PIPING LEAKAGE TESTING
33 31 16
POLYETHYLENE ENCASEMENT FOR DUCTILE IRON PIPE
33 47 23
WASTEWATER LAGOON
DIVISION 40 - PROCESS INTEGRATION
40 05 13
COMMON WORK RESULTS FOR PROCESS PIPING
40 23 39
PROCESS PIPING GENERAL
DATA SHEETS:
40 23 39.1
PROCESS PIPING SCHEDULE
40 23 39.13
CM LINED KIP AND FITTINGS
40 23 39.36
SS PIPE AND FITTINGS
40 23 39.40
C900 AND C905 PVC PIPE AND FITTINGS
40 23 39.43
POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS
40 23 39.56
(HDPE) PIPE AND FITTINGS
40 23 39.62
(MDPE) PIPE AND FITTINS FOR GAS/LP SERVICE
40 23 43
PROCESS VALVES
40 23 46
FABRICATED SLIDE AND SLUICE GATES
DATA SHEETS:
40 23 46.1
GATE SCHEDULE
40 24 00
PROCES PIPING SPECIALTIES
40 41 13
HEAT TRACING
40 92 16
VALVE AND GATE OPERATORS
DIVISION 44 - POLLUTION AND WASTE CONTROL EQUIPMENT
44 42 56.23 VERTICAL TURBINE PUMPS
DATA SHEET:
44 42 56.23.1
VERTICAL TURBINE PUMPS
44 42 69
HOT WATER PRESSURE WASHER SYSTEM
44 43 33.13 INTAKE SCREEN
VOLUME 2 OF 3
STANDARD DETAILS
VOLUME 3 OF 3
DRAWINGS
TOC - 4
Section 00 00 10
Table of Contents
I hereby certify that the applicable portions of this project plans and specifications were
prepared by me or under my direct supervision and that I am a duly Licensed Engineer
under the laws of the State of Oklahoma.
SEAL AND SIGNATURE
APPLICABLE DIVISION
Division 01
Division 02
Division 31
Division 32
Division 33
Division 40
Division 44
Division 03
Division 05
Division 07
Division 08
Division 09
Division 10
Division 13
Section 000001
Certifications
APPLICABLE DIVISION
Division 23
Division 26
Section 000001
Certifications
1. CONTRACT TIME
The time allowed for the completion of the work will be as specified in the contract as Calendar Day.
It is understood and agreed by and between the Owner and the Contractor that the time of completion
herein set out is a reasonable time. The Contractor shall perform fully, entirely, and in an acceptable
manner, the work contracted for within the contract time stated in the Contract. The contract time
shall be counted from ten days after the effective date of the Notice to Proceed, or the date work
commences, whichever occurs first.
CALENDAR DAY: Calendar day contract time includes delays for all holidays, weekends including
Saturday and Sunday, and normal weather-related events, such as rain, snow, and freezing
temperatures that may affect the progress of the construction on a per-month basis as hereinafter set
out. Only weather-related delays in excess of these amounts will be considered for time extensions if
requested by the Contractor. Time extensions due to weather delays will only be considered if the
work was impeded by those conditions. Days Included in Contract Times for Normal WeatherRelated Events are included in Section 4.3.8.2 of the General Conditions. Days Included in Contract
Times for holidays are:
Saturdays and holidays which may be declared in writing by the Owner for certain special or
unusual circumstances will be optional to the Contractor as working days and time will not be
assessed unless work is performed that requires observation. Sunday work shall not be
permitted.
Holidays that shall be observed are the following: New Years Day (January 1); Dr. Martin Luther
King Jr.s Birthday (3rd Monday in January); Presidents Day (3rd Monday in February); Memorial
Day (last Monday in May); Independence Day (July 4); Labor Day (1st Monday in September);
Columbus Day (2nd Monday in October); Thanksgiving Day (4th Thursday in November); Day
after Thanksgiving (Friday following Thanksgiving); Christmas Eve (December 24); and
Christmas Day (December 25). If a holiday falls on a Saturday or Sunday, the observed day
shall be the Friday preceding the Saturday or the Monday following the Sunday.
Section 00 14 00
Special Provisions
Personnel
Hourly Rate
Engineer (E-1)
$92.00
Engineer (E-2)
$106.00
Engineer (E-3)
$129.00
$80.00
$103.00
$126.00
$163.00
Management/Administration (X-1)
$52.00
Management/Administration (X-1)
$71.00
Management/Administration (X-1)
$99.00
Management/Administration (X-1)
$135.00
All rates indicated above in the Schedule of Charges shall be increased by an additional 4% annually,
with the first increase on May 1, 2014.
Should the amount otherwise due the Contractor be less than the amount of such ascertained and
liquidated damages, the Contractor and his Surety shall be liable to the Owner for such deficiency.
3. TESTING
Materials testing including concrete testing, soil density testing, and lagoon soil permeability testing
will be performed by testing agency hired and compensated by the Owner. Retesting of failed tests
will be the responsibility of the Contractor. The Contractor shall use the same testing agency for
retesting. Contractor shall give the Owner 24 hour notice, prior to placing any materials to be tested,
to schedule materials testing.
All other testing including but not limited to pipe leakage testing, water containing structure leakage,
electrical testing, equipment testing, and any other testing required by the Contract Documents will be
paid for and performed by the Contractor in the presence of the Owner and/or the Engineer. No
additional costs will be granted for this testing.
4. PERMITS
All permits shall be acquired and paid for by the Contractor as outlined in Section 3.7 of the General
Conditions. This includes acquiring all permits associated with working in a water body and storm
water pollution prevention permits.
The Owner will only be responsible for permit from Oklahoma Department of Environmental Quality
associated with the lagoon construction and the Oklahoma Water Resources Board permit for
construction within the flood plain.
Section 00 14 00
Special Provisions
The Contractor, prior to beginning any excavation, shall notify the State Department of Labor
(Safety Division) that work is commencing on a project with excavations greater than five feet.
The Contractor shall notify all Utility Companies and Owners in accordance with OSHA
Administration 29 CFR 1926.651(b) (2) for the purpose of locating utilities and underground
installations.
Where the trench or excavation endangers the stability of a building, wall, street, highway,
utilities, or other installation, the Contractor shall provide support systems such as shoring,
bracing, or underpinning to ensure the stability of such structure or utility.
The Contractor may elect to remove and replace or relocate such structures or utilities with the written
approval of the Owner of the structure or utility and the Project Owner.
The cost for work required by this item shall be included in the Lump Sum bid price for the
project. After award of the contract, the Contractor shall submit to the Engineer a breakdown of
cost for work involved in the price bid for "Trench and Excavation Safety Systems" and shall, with
each periodic payment request, submit a certification by the Contractors "competent person" as
defined in Subpart "P" 1926.650(b) that the Contractor has complied with the provisions of
"Occupational Safety and Health Administration Standard for Excavation and Trenches Safety
System", 29 CFR 1926 Subpart P for work for which payment is requested
A copy of the "Occupational Safety and Health Administration Standard for Excavation and
Trenches Safety System, 29 CFR 1926, Subpart P has been attached for reference.
6. CONTRACTORS INSURANCE
Contractor shall obtain insurance of the types and in the amounts described below. The insurance
shall be written by insurance companies and on forms acceptable to Owner.
Owner and Garver, LLC shall be included as an insured under the CGL, (using ISO Additional
Insured Endorsement CG 20 10 11 85 or a substitute providing equivalent coverage), and
under the commercial automobile liability (using ISO Additional Insured Endorsement CA 2048
or a substitute providing equivalent coverage), and commercial umbrella, if any. This
insurance, including insurance provided under the commercial umbrella, if any, shall apply as
primary and non-contributory insurance with respect to any other insurance or self-insurance
programs afforded to, or maintained by, Owner.
6.1 Commercial General and Umbrella Liability Insurance
Contractor shall maintain commercial general liability (CGL) and, if necessary, commercial
umbrella insurance, with a limit of not less than $5,000,000 each occurrence. If such CGL
insurance contains a general aggregate limit, it shall apply separately to the Project.
CGL insurance shall be written on ISO occurrence form CG 20 10 (11-85) (or a substitute
combination of the following forms CG 20 10 (10-01) and CG 20 37 (10-01) providing equivalent
coverage) and shall cover liability arising from premises, operations, independent contractors,
products-completed operations, personal injury and advertising injury and liability assumed under
an insured contract.
There shall be no endorsement or modification of the CGL limiting the scope of coverage for
liability arising from pollution, explosion, collapse, underground property damage, or amending
the contractual coverage in the ISO occurrence form.
Section 00 14 00
Special Provisions
Section 00 14 00
Special Provisions
comfort, contentment, and improvement of armed forces personnel, are instead compensated
with funds generated from earnings of their facility.
Where applicable, Outer Continental Shelf Lands Act Endorsement shall be attached to the
policy.
Where applicable, the Maritime Coverage Endorsement shall be attached to the policy.
If project is located in a state where workers compensation is secured via monopolistic state funds,
include evidence of the Stop Gap endorsement to the general liability policy.
6.7 Property Insurance
If applicable, Contractor shall purchase and maintain property insurance for the Work. Such
insurance shall be written in an amount at least equal to the initial contract sum as well as
subsequent modifications of that sum. The insurance shall apply on a replacement cost basis. If
the insurance obtained in compliance with this paragraph is builders risk insurance, coverage
shall be written on a completed value form.
The property insurance as required above shall name as insureds the Owner, Contractor, and all
subcontractors and sub-subcontractors on the Project.
6.8 Primary and Non-contributory
Contractor agrees that the insurance listed above, including insurance provided under the
commercial umbrella, if any, shall apply as primary and non-contributory insurance with respect to
any other insurance or self-insurance programs afforded to, or maintained by, Owner.
6.9 Waiver of Subrogation
Contractor waives all rights against the Owner and Garver, LLC and its agents, officers, directors
and employees for recovery of damages to the extent these damages are covered by the
commercial general liability, commercial umbrella liability insurance, automobile liability insurance
and workers compensation insurance maintained pursuant to paragraph GC.8 of this agreement.
6.10 No Implied Waiver
Contractor shall furnish certifications matching the coverage requirements. Failure of Owner or
Engineer to demand such certificate or other evidence of full compliance with these insurance
requirements or failure of Owner or Engineer to identify a deficiency from evidence that is provided
shall not be construed as a waiver of the contractors obligations to furnish and maintain such
insurance, or as a waiver to the enforcement of any of the provisions at a later date.
Any waiver of the contractors obligation to furnish such certificate or maintain such evidence must
be by written change order and signed by a Managing Member (Officer) of the Engineer and the
Owner.
6.11 Cancellation, Non-Renewal, and/or Impairment Notification
The Contractor shall not cause any insurance policy to be cancelled or permit it to lapse and all
insurance policies shall include an endorsement to the effect that the insurance policy or certificate
shall not be subject to cancellation or to a reduction in the required limits of liability or amounts of
insurance until notice has been mailed to the Owner and Engineer, stating the date when such
cancellation or reduction shall be effective, which date shall not be less than (60) days after such
notice.
Section 00 14 00
Special Provisions
Notice shall be sent via email and regular mail to the following persons and addresses:
Garver:
Attention: Lance Klement
1016 24th Avenue NW
Norman, OK 73069
LPKlement@GarverUSA.com
Owner:
Attention: Steve Spade
Byron State Fish Hatchery
Route 1 Box 535
Byron, OK 73722-9525
Section 00 14 00
Special Provisions
Section 00 14 00
Special Provisions
1926.606 Definitions
this subpart.
applicable
to
(a) ApronThe area along the waterfront edge of the pier or wharf.
(b) BulwarkThe side of a ship above
the upper deck.
(c) CoamingThe raised frame, as
around a hatchway in the deck, to keep
out water.
(d) Jacobs ladderA marine ladder of
rope or chain with wooden or metal
rungs.
(e) Rail, for the purpose of 1926.605,
means a light structure serving as a
guard at the outer edge of a ships
deck.
Subpart PExcavations
AUTHORITY: Sec. 107, Contract Worker
Hours and Safety Standards Act (Construction Safety Act) (40 U.S.C. 333); Secs. 4, 6, 8,
Occupational Safety and Hea1th Act of 1970
(29 U.S.C. 653, 655, 657); Secretary of Labors
Order No. 1271 (36 FR 8754), 876 (41 FR
1926.650
369
00 75 00-1
1926.650
370
00 75 00-2
1926.651
(4) While the excavation is open, underground installations shall be protected, supported or removed as necessary to safeguard employees.
(c) Access and egress(1) Structural
ramps. (i) Structural ramps that are
used solely by employees as a means of
access or egress from excavations shall
be designed by a competent person.
Structural ramps used for access or
egress of equipment shall be designed
by a competent person qualified in
structural design, and shall be constructed in accordance with the design.
(ii) Ramps and runways constructed
of two or more structural members
shall have the structural members connected together to prevent displacement.
(iii) Structural members used for
ramps and runways shall be of uniform
thickness.
(iv) Cleats or other appropriate
means used to connect runway structural members shall be attached to the
bottom of the runway or shall be attached in a manner to prevent tripping.
(v) Structural ramps used in lieu of
steps shall be provided with cleats or
other surface treatments on the top
surface to prevent slipping.
(2) Means of egress from trench excavations. A stairway, ladder, ramp or
other safe means of egress shall be located in trench excavations that are 4
feet (1.22 m) or more in depth so as to
require no more than 25 feet (7.62 m) of
lateral travel for employees.
(d) Exposure to vehicular traffic. Employees exposed to public vehicular
traffic shall be provided with, and shall
wear, warning vests or other suitable
garments marked with or made of
reflectorized or high-visibility material.
(e) Exposure to falling loads. No employee shall be permitted underneath
loads handled by lifting or digging
equipment. Employees shall be required to stand away from any vehicle
being loaded or unloaded to avoid being
struck by any spillage or falling materials. Operators may remain in the
cabs of vehicles being loaded or unloaded when the vehicles are equipped,
in accordance with 1926.601(b)(6), to
provide adequate protection for the operator during loading and unloading
operations.
371
00 75 00-3
1926.651
(f) Warning system for mobile equipment. When mobile equipment is operated adjacent to an excavation, or
when such equipment is required to approach the edge of an excavation, and
the operator does not have a clear and
direct view of the edge of the excavation, a warning system shall be utilized such as barricades, hand or mechanical signals, or stop logs. If possible, the grade should be away from
the excavation.
(g) Hazardous atmospheres(1) Testing
and controls. In addition to the requirements set forth in subparts D and E of
this part (29 CFR 1926.501926.107) to
prevent exposure to harmful levels of
atmospheric contaminants and to assure acceptable atmospheric conditions, the following requirements shall
apply:
(i)
Where
oxygen
deficiency
(atmospheres containing less than 19.5
percent oxygen) or a hazardous atmosphere exists or could reasonably be expected to exist, such as in excavations
in landfill areas or excavations in areas
where hazardous substances are stored
nearby, the atmospheres in the excavation shall be tested before employees
enter excavations greater than 4 feet
(1.22 m) in depth.
(ii) Adequate precautions shall be
taken to prevent employee exposure to
atmospheres containing less than 19.5
percent oxygen and other hazardous
atmospheres. These precautions include providing proper respiratory protection or ventilation in accordance
with subparts D and E of this part respectively.
(iii) Adequate precaution shall be
taken such as providing ventilation, to
prevent employee exposure to an atmosphere containing a concentration
of a flammable gas in excess of 20 percent of the lower flammable limit of
the gas.
(iv) When controls are used that are
intended to reduce the level of atmospheric contaminants to acceptable levels, testing shall be conducted as often
as necessary to ensure that the atmosphere remains safe.
(2) Emergency rescue equipment. (i)
Emergency rescue equipment, such as
breathing apparatus, a safety harness
and line, or a basket stretcher, shall be
readily available where hazardous at-
372
00 75 00-4
1926.652
373
00 75 00-5
1926.652
(34 degrees measured from the horizontal), unless the employer uses one
of the other options listed below.
(ii) Slopes specified in paragraph
(b)(1)(i) of this section, shall be excavated to form configurations that are
in accordance with the slopes shown
for Type C soil in Appendix B to this
subpart.
(2) Option (2)Determination of slopes
and configurations using Appendices A
and B. Maximum allowable slopes, and
allowable configurations for sloping
and benching systems, shall be determined in accordance with the conditions and requirements set forth in appendices A and B to this subpart.
(3) Option (3)Designs using other tabulated data. (i) Designs of sloping or
benching systems shall be selected
from and be in accordance with tabulated data, such as tables and charts.
(ii) The tabulated data shall be in
written form and shall include all of
the following:
(A) Identification of the parameters
that affect the selection of a sloping or
benching system drawn from such data;
(B) Identification of the limits of use
of the data, to include the magnitude
and configuration of slopes determined
to be safe;
(C) Explanatory information as may
be necessary to aid the user in making
a correct selection of a protective system from the data.
(iii) At least one copy of the tabulated data which identifies the registered professional engineer who approved the data, shall be maintained at
the jobsite during construction of the
protective system. After that time the
data may be stored off the jobsite, but
a copy of the data shall be made available to the Secretary upon request.
(4) Option (4)Design by a registered
professional engineer. (i) Sloping and
benching systems not utilizing Option
(1) or Option (2) or Option (3) under
paragraph (b) of this section shall be
approved by a registered professional
engineer.
(ii) Designs shall be in written form
and shall include at least the following:
(A) The magnitude of the slopes that
were determined to be safe for the particular project;
(B) The configurations that were determined to be safe for the particular
project; and
(C) The identity of the registered professional engineer approving the design.
(iii) At least one copy of the design
shall be maintained at the jobsite
while the slope is being constructed.
After that time the design need not be
at the jobsite, but a copy shall be made
available to the Secretary upon request.
(c) Design of support systems, shield
systems, and other protective systems. Designs of support systems shield systems, and other protective systems
shall be selected and constructed by
the employer or his designee and shall
be in accordance with the requirements
of paragraph (c)(1); or, in the alternative, paragraph (c)(2); or, in the alternative, paragraph (c)(3); or, in the
alternative, paragraph (c)(4) as follows:
(1) Option (1)Designs using appendices A, C and D. Designs for timber
shoring in trenches shall be determined
in accordance with the conditions and
requirements set forth in appendices A
and C to this subpart. Designs for aluminum hydraulic shoring shall be in
accordance with paragraph (c)(2) of this
section, but if manufacturers tabulated data cannot be utilized, designs
shall be in accordance with appendix D.
(2) Option (2)Designs Using Manufacturers Tabulated Data. (i) Design of support systems, shield systems, or other
protective systems that are drawn
from manufacturers tabulated data
shall be in accordance with all specifications, recommendations, and limitations issued or made by the manufacturer.
(ii) Deviation from the specifications,
recommendations,
and
limitations
issued or made by the manufacturer
shall only be allowed after the manufacturer issues specific written approval.
(iii) Manufacturers specifications,
recommendations, and limitations, and
manufacturers approval to deviate
from the specifications, recommendations, and limitations shall be in written form at the jobsite during construction of the protective system.
After that time this data may be
stored off the jobsite, but a copy shall
374
00 75 00-6
1926.652
375
00 75 00-7
to subpart P of part 1926, and when aluminum hydraulic shoring is designed in accordance with appendix D. This Appendix
also applies if other protective systems are
designed and selected for use from data prepared in accordance with the requirements
set forth in 1926.652(c), and the use of the
data is predicated on the use of the soil classification system set forth in this appendix.
(b) Definitions. The definitions and examples given below are based on, in whole or in
part, the following: American Society for
Testing Materials (ASTM) Standards D65385
and D2488; The Unified Soils Classification
System, The U.S. Department of Agriculture
(USDA) Textural Classification Scheme; and
The National Bureau of Standards Report
BSS121.
Cemented soil means a soil in which the particles are held together by a chemical agent,
such as calcium carbonate, such that a handsize sample cannot be crushed into powder or
individual soil particles by finger pressure.
Cohesive soil means clay (fine grained soil),
or soil with a high clay content, which has
cohesive strength. Cohesive soil does not
crumble, can be excavated with vertical
sideslopes, and is plastic when moist. Cohesive soil is hard to break up when dry, and
exhibits significant cohesion when submerged. Cohesive soils include clayey silt,
sandy clay, silty clay, clay and organic clay.
Dry soil means soil that does not exhibit
visible signs of moisture content.
Fissured means a soil material that has a
tendency to break along definite planes of
fracture with little resistance, or a material
that exhibits open cracks, such as tension
cracks, in an exposed surface.
Granular soil means gravel, sand, or silt,
(coarse grained soil) with little or no clay
content. Granular soil has no cohesive
strength. Some moist granular soils exhibit
apparent cohesion. Granular soil cannot be
molded when moist and crumbles easily
when dry.
Layered system means two or more distinctly different soil or rock types arranged
in layers. Micaceous seams or weakened
planes in rock or shale are considered layered.
Moist soil means a condition in which a soil
looks and feels damp. Moist cohesive soil can
easily be shaped into a ball and rolled into
small diameter threads before crumbling.
Moist granular soil that contains some cohesive material will exhibit signs of cohesion
between particles.
Plastic means a property of a soil which allows the soil to be deformed or molded without cracking, or appreciable volume change.
Saturated soil means a soil in which the
voids are filled with water. Saturation does
not require flow. Saturation, or near saturation, is necessary for the proper use of instruments such as a pocket penetrometer or
sheer vane.
376
00 75 00-8
377
00 75 00-9
378
00 75 00-10
379
00 75 00-11
1. All simple slope excavation 20 feet or less in depth shall have a maximum allowable slope
of 34:1.
SIMPLE SLOPEGENERAL
Exception: Simple slope excavations which are open 24 hours or less (short term) and which
are 12 feet or less in depth shall have a maximum allowable slope of 12:1.
380
00 75 00-12
SIMPLE BENCH
MULTIPLE BENCH
3. All excavations 8 feet or less in depth which have unsupported vertically sided lower portions shall have a maximum vertical side of 312 feet.
381
00 75 00-13
SIMPLE SLOPE
2. All benched excavations 20 feet or less in depth shall have a maximum allowable slope
of 1:1 and maximum bench dimensions as follows:
382
00 75 00-14
SINGLE BENCH
MULTIPLE BENCH
3. All excavations 20 feet or less in depth which have vertically sided lower portions shall
be shielded or supported to a height at least 18 inches above the top of the vertical side. All
such excavations shall have a maximum allowable slope of 1:1.
383
00 75 00-15
SIMPLE SLOPE
2. All excavations 20 feet or less in depth which have vertically sided lower portions shall
be shielded or supported to a height at least 18 inches above the top of the vertical side. All
such excavations shall have a maximum allowable slope of 112:1.
384
00 75 00-16
385
00 75 00-17
2. All other sloped excavations shall be in accordance with the other options permitted in
1926.652(b).
386
00 75 00-18
387
00 75 00-19
uprights
at
four
hori-
Arrangement #B3
Space 66 crossbraces at 10 feet horizontally and four feet vertically.
Space 810 wales at four feet vertically.
Space 26 uprights at five feet horizontally.
Arrangement #B4
Space 66 crossbraces at 12 feet horizontally and four feet vertically.
Space 1010 wales at four feet vertically.
Spaces 38 uprights at six feet horizontally.
(2) Example 2.
A trench dug in Type B soil in 13 feet deep
and five feet wide. From Table C1.2 three
acceptable arrangements of members are
listed.
Arrangement #B1
Space 66 crossbraces at six feet horizontally and five feet vertically.
Space 88 wales at five feet vertically.
Space 26 uprights at two feet horizontally.
Arrangement #B2
Space 68 crossbraces at eight feet horizontally and five feet vertically.
Space 1010 wales at five feet vertically.
Space 26 uprights at two feet horizontally.
Arrangement #B3
Space 88 crossbraces at 10 feet horizontally and five feet vertically.
Space 1012 wales at five feet vertically.
Space 26 uprights at two feet vertically.
(3) Example 3.
A trench dug in Type C soil is 13 feet deep
and five feet wide.
From Table C1.3 two acceptable arrangements of members can be used.
Arrangement #B1
Space 88 crossbraces at six feet horizontally and five feet vertically.
Space 1012 wales at five feet vertically.
Position 26 uprights as closely together as
possible.
If water must be retained use special
tongue and groove uprights to form tight
sheeting.
Arrangement #B2
Space 810 crossbraces at eight feet horizontally and five feet vertically.
388
00 75 00-20
389
00 75 00-21
390
00 75 00-22
391
00 75 00-23
392
00 75 00-24
393
00 75 00-25
do not exceed 20 feet (6.1m) in depth. This appendix must be used when design of the aluminum hydraulic protective system cannot
be
performed
in
accordance
with
1926.652(c)(2).
(b) Soil Classification. In order to use data
presented in this appendix, the soi1 type or
types in which the excavation is made must
394
00 75 00-26
395
00 75 00-27
396
00 75 00-28
397
00 75 00-29
398
00 75 00-30
399
00 75 00-31
400
00 75 00-32
401
00 75 00-33
402
00 75 00-34
403
00 75 00-35
404
00 75 00-36
405
00 75 00-37
406
00 75 00-38
DIVISION 01
GENERAL REQUIREMENTS
SUMMARY
A.
B.
Work covered by Contract Documents: The completed Work will provide Owner with various
hatchery improvements. More specifically, the Project includes, but is not limited to, construction
of the following:
1.
New 7,500 gpm intake structure and screen.
2.
New 7,500 gpm raw water pumping station and electrical building.
3.
24 raw water pumping force main replacement.
4.
New disinfection station building and wash bay.
5.
New waste disposal system for disinfection station.
6.
Decommissioning existing intake pump station.
7.
Dam bypass gate replacement.
C.
D.
Secure and pay for all permits including all ODEQ Storm Water Pollution Prevention Plan,
OSHA excavation permits, Department of Transportation permits, government fees and
licenses.
E.
Comply with codes, ordinances, regulations, orders, and other legal requirements of public
authorities having bearing on the performance of the Work.
1.2
ACTIVITIES BY OTHERS
A.
OWNER, utilities, and others may perform activities within Project area while the Work is in
progress.
1.
Schedule the Work with OWNER, utilities, and others to minimize mutual interference.
B.
1.3
COORDINATION OF WORK
A.
B.
Obtain construction schedules from each subcontractor, and require each subcontractor to
maintain schedules and coordinate modifications.
Section 01 11 00
Summary of Work
C.
1.4
Alternates: Alternates, if included, are specified in detail in the Bid Form/Proposal and only
those alternates that were selected by the Owner, as evidenced in the Agreement, are made a
part of this Contract.
PROVISIONS FOR FUTURE WORK
A.
1.5
None.
LOCATION OF WORK
A.
1.6
The Project is located generally at the Durant State Fish Hatchery facilities located at 2021
Caddo Highway, Caddo, OK 74729.
OWNER FURNISHED EQUIPMENT
A.
1.7
For this projects delivery, the Owner shall not be providing and/or delivering any associated
equipment.
EARLY OCCUPANCY OF PORTIONS OF WORK
A.
Certificates of Substantial Completion will be executed for each designated portion of Work prior
to OWNER occupancy.
1.
Such certificate of Substantial Completion will describe the portion of the Work to be
occupied by OWNER, items that may be incomplete or defective, date of occupancy by
OWNER, and other information required by OWNER and CONTRACTOR.
B.
After OWNER occupancy, allow access for OWNERs personnel, access for others authorized
by OWNER, and OWNER operation of equipment and systems.
C.
END OF SECTION
Section 01 11 00
Summary of Work
SUMMARY
A.
1.2
Section includes: Identification and description of coordination work of the Deductive Bid
Alternates which may be incorporated into the Work.
THE WORK
A.
In addition to the Base Bid Project, the OWNER may elect to construct a combination of any of
the following Deductive Bid Alternates:
Deductive Item Identifier
Alternate A
Alternate B
Alternate C
Alternate D
Item Description
Alternate A: Automatic Pump Control and Reservoir
Level Detection
This alternative will omit the following:
1. Control panel PLC01, including hardware, software, and programming called for in specification
section 26 90 20,
2. Conduit and wire connecting PLC01 to
DSSSS01, DSSSS02, and flow meter FIT01
3. Control panel LCP02, ultrasonic level transmitter
LIT01, and associated wiring.
4. Fiber optic cable from pump station to the reservoir.
5. On-Off-Auto switches in pump starter panels
DSSSS01 and DSSSS02; replace these switches
with On-Off selector switches.
Alternate B: Pump station canopy and framing will be
omitted. This alternative will omit the roof deck and
roof framing, the ridged framing along gridline 5, the
roof hatch over the pumps, lighting and electrical
items associated with pump canopy lighting and any
other work or materials required to provide the canopy
over the proposed pump deck.
Alternate C: Copper-Nickel intake screen for zebra
mussel control will be omitted and a standard 304
stainless intake screen meeting the design requirement Section 44 43 33.13 will provided.
Alternate D: 24 discharge line replacement as shown
on the Drawings will be omitted and the new pump
station discharge will connect at an alternate location
as shown on the Drawings.
With this bid, the CONTRACTOR agrees that the CONTRACTOR has carefully examined the
plans and other contractual documents and has coordinated the scopes between the Base Bid
Documents and the Bid Alternate Documents. Through submittal of a bid, the CONTRACTOR
agrees and understands that the documents have been prepared with the highest level of care
in the effort to coordinate the scopes of the Base Bid Project documents and the Bid Alternate
documents. The CONTRACTOR agrees and accepts the responsibilities to coordinate and
construct all required interconnections and coordination facilities between the Base Bid Project
and any of, any combination of, and/or a total combination of the Bid Alternates to develop
Section 01 11 20
Deductive Bid Alternates Coordination
complete and operational facilities that meet the regulatory requirements for the facilities and
the requirements set forth by these contract documents.
B.
C.
Secure and pay for all permits including ODEQ Storm Water Pollution Prevention Plans, OSHA
excavation permits, government fees and licenses.
D.
Comply with codes, ordinances, regulations, orders, and other legal requirements of public
authorities having bearing on the performance of the Work.
E.
When the Work depends for proper execution or results upon work performed by others, inspect
and promptly report apparent discrepancies or defects in work performed by others.
1.
Assume responsibility for work performed by others, except for defects reported as
specified in this paragraph and defects which may become apparent in work performed
by others after execution of the Work.
1.3
COORDINATION OF WORK
A.
B.
Coordinate the scopes of the Base Bid Project documents and the scopes of the Bid Alternate
documents.
C.
With his bid, CONTRACTOR acknowledges and understands that the scope of the
DEDUCTIVE BID ALTERNATIVES is documented via several methods within the Contract
Documents.
Section 01 11 20
Deductive Bid Alternates Coordination
SUMMARY
A.
B.
1.2
REFERENCES
A.
1.3
A.
Document and Section numbers used in Project Manual, and Project Manual arrangement are
in accordance with CSI MasterFormat, except where departures have been deemed
necessary.
B.
Sections are written in accordance with CSI SectionFormat, Three-Part Section Format,
except where departures have been deemed necessary.
C.
Page format for Sections in the Project Manual is in accordance with CSI Page Format, except
where departures have been deemed necessary.
1.4
B.
Phrase "by ENGINEER" modifies words such as "accepted," "directed," "selected," "inspected,"
and "permitted," when they are unmodified.
C.
Phrase "to ENGINEER" modifies words such as "submit," "report," and "satisfactory," when they
are unmodified.
D.
Section 01 11 60
Project Manual Language
1.
When used as an appositive after designation of product, colons are used in place of
words "shall be."
E.
Word "provide" means to manufacture, fabricate, deliver, furnish, install, complete, assemble,
erect in place, test, render ready for use or operation, including necessary related material,
labor, appurtenances, services, and incidentals.
F.
Words "CONTRACTOR shall" are implied when direction is stated in imperative mood.
G.
1.5
REFERENCE STANDARDS
A.
B.
C.
Notify ENGINEER when referenced standard, code, or specification conflicts with Contract
Documents.
END OF SECTION
Section 01 11 60
Project Manual Language
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 11 00 - Summary of Work.
b.
Section 01 35 20 Alteration Project Procedures.
c.
Section 01 50 00 - Temporary Facilities and Controls.
1.2
1.3
A.
Execute the Work while the existing facility is in operation as specified in Section 01 35 20.
B.
C.
Submit notification of required shutdowns of existing facilities at least 14 days prior to the
planned date of shutdown.
D.
The ENGINEER and the Hatchery Personnel will evaluate the request based on the hatcherys
ability to reliably meet capacity demands.
Section 01 14 00
Work Restrictions
E.
Do not begin alterations until ENGINEERs written permission has been received.
F.
Minimize shutdown times by thorough advanced planning. Have required equipment, materials,
and labor on hand at time of shutdown.
G.
Where required to minimize treatment process interruptions while complying with specified
sequencing constraints, provide temporary pumping, power, lighting, controls, instrumentation,
and safety devices.
1.4
Facilities or conditions required to keep the existing hatchery operational include, but are not
limited to, the following:
1.
Electrical power, including transformers, distribution wiring, and motor control centers.
2.
Hatchery Water: Existing hatchery water supply.
3.
Fencing and gates.
4.
Lighting.
5.
Heating, ventilation, and air conditioning equipment.
6.
Instrumentation, meters, controls, and telemetry equipment.
7.
Safety equipment and features.
8.
Parking for hatchery staff and vehicles required for operation and maintenance of the
existing hatchery.
9.
Telephone system.
10.
Storm drainage.
11.
Roadways to provide access route for deliveries.
12.
Other incidentals necessary to continually operate the facilities.
B.
Conduct the Work and provide temporary facilities required to keep the existing hatchery
continuously operational.
C.
Do not remove or demolish existing facilities required to keep the existing hatchery operational
at the capacities specified until the existing facilities are replaced by temporary or new facilities
equipment. The replacement facilities shall have been tested and demonstrated to be
operational prior to removing or demolishing existing facilities.
1.5
1.6
Provide safe, continuous access to process control equipment for hatchery operations
personnel.
SHUTDOWN CONSTRAINTS
A.
1.7
A.
Provide advance notice to and utilize services of Oklahoma One-Call System for location and
marking of underground utilities operated by utility agencies other than the OWNER. Contact
information: Oklahoma One Call System, Inc., 2831 NW 59, Oklahoma City, OK 73112, phone
number 800-522-OKIE or 405-840-9955, website: www.callokie.com. .
B.
Maintain electrical, telephone, water, gas, sanitary facilities, and other utilities within existing
facilities in service. Provide temporary utilities when necessary.
Section 01 14 00
Work Restrictions
1.8
WORK BY OTHERS
A.
1.9
Where proper execution of the Work depends upon work by others, inspect and promptly report
discrepancies and defects.
TEMPORARY SERVICES, MATERIALS, AND EQUIPMENT
A.
Locate temporary facilities in a manner that minimizes interference to OWNERs operation and
maintenance personnel.
B.
Unless otherwise specified, install temporary pipelines of the same size as its connection to the
existing facility at the downstream end of the pipeline.
C.
D.
E.
Dimensions for all existing structures, piping, paving, and other nonstructural items are
approximate. The CONTRACTOR shall field verify all dimensions and conditions and report any
discrepancies to the ENGINEER a minimum of 14 days in advance of any construction in the
area.
F.
Discrepancies between coordinates, bearings and lengths, and stationing shall be resolved in
the following order of precedence:
1.
Coordinates.
2.
Bearings and lengths.
3.
Stationing.
Section 01 14 00
Work Restrictions
SUMMARY
A.
1.2
A.
1.3
Informational:
1.
Statement of Qualification (SOQ) for land surveyor or civil engineer.
2.
Photographs and other records of examination.
3.
Video Recordings: Submit one copy, including updated copy of project video log, within 5
days of being taken.
UTILITY NOTIFICATION AND COORDINATION
A.
Coordinate the Work with various utilities within Project limits. Notify applicable utilities prior to
commencing Work, if damage occurs, or if conflicts or emergencies arise during Work.
1.
Electric Company: Oklahoma Gas and Electric, ph 1-800-522-6870
2.
Telephone Company: AT&T, ph 877-629-7541
3.
Natural Gas Company: Oklahoma Natural Gas, ph 1-800-458-4251
B.
Before excavation, contact Oklahoma One Call System, Inc., ph 811, to arrange for field
location of known utilities.
1.4
WORK SEQUENCING/CONSTRAINTS
A.
Include the following work sequences in the Progress Schedule required under Section 01 32
00.
B.
This Section identifies several construction constraints that must be reflected in the Contractor
project coordination. An overall outline is presented in this Section for the Construction
coordination, demolition, and seasonal/process constraints that shall be considered during
construction. The sequence of Work for this Project must reflect the constraints identified
herein.
C.
Definitions:
1.
Minor Shutdown: Any shutdown requiring less than 8 hours.
2.
Major Shutdown: Any shutdown other than a minor shutdown.
D.
Section 01 31 00
Project Management and Coordination
2.
3.
4.
5.
1.5
Provide 30 days advance notice to Engineer and Owner of need for a major shutdown.
Contractor shall schedule a shutdown coordination meeting with Owner and Engineer
one week prior to each shutdown.
Do not proceed with work affecting a facilitys operation without obtaining Owner and
Engineer advance approval of the need for, and duration of, such work. The Owner will
endeavor to grant Contractor requests where possible.
Any and all facility shutdowns shall require a shutdown plan, including detailed schedule,
backup tools and equipment, personnel involved, contingency plan, and any procedures
involved in restarting the process or facility. Owners approval of the Shutdown Plan is
required prior to any shutdowns.
FACILITY OPERATIONS
A.
B.
Perform Work continuously during critical connections and changeovers, as required, to prevent
interruption of Owners operations.
C.
Conduct Work outside regular working hours on prior written consent of Owner to meet Project
schedule and avoid undesirable conditions.
D.
Be responsible for planning, designing, and providing various temporary services, utilities,
connections, temporary piping, bypass facilities and temporary connections, and similar items to
maintain continuous operations of Owners facility. Sequences other than those specified will
be considered upon written request to Owner and Engineer, provided they afford equivalent
continuity of operations.
E.
Do not close lines, open or close valves, or take other action which would affect the operation of
existing systems, except as specifically required by the Contract Documents and after
authorization by Owner and Engineer. Such authorization will be considered within 48 hours
after receipt of Contractors written request.
F.
Any tanks or pipelines requiring drainage prior to construction will be drained by the Owners
staff to the maximum extent possible utilizing existing piping and drains where they exist.
Contractor shall provide temporary pumping and effort to complete drainage of tank or pipeline
as required. Provide minimum 7 days notice to Engineer and Owner of need to drain a facility,
unless otherwise specified.
G.
Power outages will be considered upon 48 hours written request to Owner and Engineer.
Describe the reason, anticipated length of time, and areas affected by the outage in the written
request. Provide temporary provisions for continuous power supply to critical existing facility
components, is requested by Owner.
H.
Coordinate proposed work with Engineer and Owner before implementing unit shutdowns.
Under no circumstances shall Work end if such actions may inadvertently cause a cessation of
any facility operation. In such cases, remain onsite until necessary repairs are complete and
facility is brought back online.
I.
Section 01 31 00
Project Management and Coordination
3.
4.
5.
1.6
Use only new materials for relocated facility. Match materials of existing facility, unless
otherwise shown or specified.
Perform relocations to minimize downtime of existing facilities.
Install new portions of existing facilities in their relocated position prior to removal of
existing facilities, unless otherwise accepted by Engineer.
Examination:
1.
After Effective Date of the Agreement and before Work at Site is started, Contractor,
Engineer, and affected property owners and utility owners shall make a thorough
examination of pre-existing conditions including existing buildings, structures, and other
improvements in vicinity of Work, as applicable, which could be damaged by construction
operations.
2.
Periodic reexamination shall be jointly performed to include, but not limited to, cracks in
structures, settlement, leakage, and similar conditions.
B.
Documentation:
1.
Record and submit documentation of observations made on examination inspections for
signature of Engineer and Contractor and in accordance with paragraphs Construction
Photographs and Audio-Video Recordings.
2.
Upon receipt, Engineer will review, sign, and return one record copy of documentation to
Contractor to be kept on file in field office. Such documentation shall be used as
indisputable evidence in ascertaining whether and to what extent damage occurred as a
result of Contractors operations, and is for the protection of adjacent property owners,
Contractor, and Owner.
1.7
OWNERS OCCUPANCY
A.
1.8
Owner will occupy the premises during the period of construction for the conduct of its normal
operations. Cooperate with Owner in all construction operations to minimize conflict and to
facilitate Owner usage.
PARTIAL UTILIZATION BY THE OWNER
A.
Schedule operations for completion of portions of the Work, as designated under Work
Sequence/Constraints, herein, for Owners occupancy or separate operation prior to Substantial
Completion of the entire Work.
B.
Unless agreed in writing prior to Owners use, the following conditions shall apply:
1.
Contractors Responsibilities:
a.
Allow access for Owners personnel.
b.
Allow operation of ventilation and electrical systems.
c.
All other responsibilities as specified in the General Conditions.
2.
Owners Responsibilities:
a.
Operate ventilating systems and pay cost of same.
b.
Assume responsibility of power requirements.
c.
Assume responsibility for security and fire protection in utilized areas, but not
extending to Contractors materials and equipment in utilized areas.
d.
Assume responsibility for property insurance of utilized areas.
3.
Other Conditions of Owners Use: The correction period for the occupied or separately
operated portion of Work shall commence at the date of Substantial Completion for that
separate part.
Section 01 31 00
Project Management and Coordination
1.9
PHYSICAL CONDITIONS
A.
Exercise reasonable care to verify locations of existing subsurface facilities and utilities.
B.
Areas immediate and adjacent to planned excavations shall be thoroughly checked by means of
visual examination and with electronic metal and pipe detection equipment for indications of
underground utilities and facilities.
C.
Make exploratory excavation where existing underground facilities or utilities may potentially
conflict with proposed excavations and facilities or where there is reasonable cause to verify the
presence or absence of, or to obtain physical information regarding underground facilities or
utilities. Conduct exploratory excavations as acceptable to and in the presence of Engineer prior
to proceeding with major excavation in the area and sufficiently in advance of construction to
avoid possible delays to Contractors Work. Promptly take measurements, photographs, and
obtain survey data.
1.10
CONSTRUCTION PHOTOGRAPHS
A.
B.
Engineer shall have the right to select the subject matter and vantage point from which
photographs are to be taken.
C.
D.
E.
1.11
AUDIO-VIDEO RECORDINGS
A.
Prior to beginning Work on Construction Site or of a particular area of the Work, and again
within 10 days following date of Substantial Completion, video-graph Construction Site and
property adjacent to Construction Site.
B.
In the case of preconstruction recording, no Work shall begin in the area prior to Engineers
review and approval of content and quality of video for that area.
C.
Particular emphasis shall be directed to physical condition of existing vegetation, structures, and
pavements within Construction Site and areas adjacent to and within the right-of-way or
easement, and on Contractor storage and staging areas.
D.
Engineer shall have right to select subject matter and vantage point from which videos are to be
taken.
E.
Section 01 31 00
Project Management and Coordination
1.
2.
3.
4.
5.
6.
1.12
A.
B.
Dimensions for lines and elevations for grades of structures, appurtenances, and utilities are
indicated on the Drawings, together with the other pertinent information required for laying out
Work. If conditions vary from those indicated, immediately notify Engineer.
C.
Any existing survey points or other control markers destroyed without proper authorization will
be replaced by Owner of the survey points or control markers at the Contractors expense.
D.
Contractors Responsibilities:
1.
Provide additional survey and layout required to layout the Work.
2.
Locate and protect reference points prior to stating site preparation.
3.
Check and establish exact location of existing facilities prior to construction of new
facilities and any connections thereto.
4.
In event of discrepancy in data or staking provided by Owner, request clarification before
proceeding with Work.
5.
Retain professional land surveyor or civil engineer registered in state of Project who shall
perform or supervise engineering surveying necessary for additional construction staking
and layout.
6.
Maintain complete accurate log of survey Work as it progresses as a Record Document.
7.
On request of Engineer, submit documentation.
8.
Provide competent employee(s), tools, stakes, and other equipment and materials as
Engineer may require to:
a.
Establish control points, lines, and easement boundaries.
b.
Check layout, survey, and measurement Work performed by others.
Section 01 31 00
Project Management and Coordination
Cut, fit, adjust, or patch Work and work of others, including excavation and backfill as required,
to make Work complete.
B.
Obtain prior written authorization of Engineer and Owner before commencing work to cut or
otherwise alter:
1.
Structural or reinforcing steel, structural column or beam, elevated slab, trusses, or other
structural member.
2.
Weather- or moisture-resistant elements.
3.
Efficiency, maintenance, or safety of element.
4.
Work of others.
C.
D.
Restore existing work, Underground Facilities, and surfaces that are to remain in completed
Work including concrete-embedded piping, conduit, and other utilities as specified and as
shown.
E.
Make restorations with new materials and appropriate methods as specified for new Work of
similar nature; if not specified, use recommended practice of manufacturer or appropriate trade
association.
F.
Fit Work airtight to pipes, sleeves, ducts, conduit, and other penetrations through surfaces and
fill voids.
G.
END OF SECTION
Section 01 31 00
Project Management and Coordination
SUMMARY
A.
1.2
Section includes: Requirements for conducting conferences and meetings for the purposes of
addressing issues related to the Work, reviewing and coordinating progress of the Work and
other matters of common interest, and includes the following:
1.
General Requirements.
2.
Qualifications of Meeting Participants.
3.
Preconstruction Conference.
4.
Progress Meetings.
5.
Pre-Installation Meetings.
6.
Post Construction Meeting.
GENERAL REQUIREMENTS
A.
1.3
Contractor will schedule physical arrangements for meetings throughout progress of Work,
prepare meeting agenda with regular participant input and distribute with written notice of each
meeting, preside at meetings, record minutes to include significant proceedings and decisions,
and reproduce and distribute copies of minutes within 5 days after each meeting to participants
and parties affected by meeting decisions.
QUALIFICATIONS OF MEETING PARTICIPANTS
A.
1.4
A.
B.
C.
Upon issuance of Notice to Proceed, or earlier when mutually agreeable, ENGINEER will
arrange preconstruction conference in convenient place for most persons invited, in accordance
with the General Conditions.
Section 01 31 19
Project Meetings
D.
E.
F.
G.
H.
CONTRACTOR will record minutes of meeting and distribute copies of minutes within 5 days of
meeting to participants and interested parties.
1.5
PROGRESS MEETINGS
A.
CONTRACTOR will schedule regular progress meetings at site, conducted monthly, to review
the Work progress, progress schedule, Shop Drawing and Sample submissions schedule,
Application for Payment, contract modifications, and other matters needing discussion and
resolution.
B.
C.
Conduct progress meetings at least once every month in CONTRACTORs field office,
ENGINEERs field office, or other mutually agreed upon place.
Section 01 31 19
Project Meetings
D.
Distribute to each anticipated participant written notice and agenda of each meeting at least 2
days before meeting.
E.
F.
Invite OWNER, ENGINEER, utility companies when the Work affects their interests, and others
necessary to agenda.
G.
Complete and bring Application for Payment and Progress Schedule to progress meeting.
H.
I.
Preside at meetings.
J.
K.
Review progress of the Work, Progress Schedule, narrative report, Application for Payment,
record documents, and additional items of current interest that are pertinent to execution of the
Work.
L.
Verify:
1.
Actual start and finish dates of completed activities since last progress meeting.
2.
Durations and progress of activities not completed.
3.
Reason, time, and cost data for Change Order Work that will be incorporated into
Progress Schedule and application for payment.
4.
Percentage completion of items on Application for Payment.
5.
Reasons for required revisions to Progress Schedule and their effect on Contract Time
and Contract Price.
M.
Discuss potential problems which may impede scheduled progress and corrective measures.
N.
CONTRACTOR will record minutes of meeting and distribute copies of minutes within 7 days of
meeting to participants and interested parties.
Section 01 31 19
Project Meetings
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
01 31 00 Project Management and Coordination.
1.2
DEFINITIONS
A.
Action Submittal: Written and graphic information submitted by Contractor that requires
Engineers approval.
B.
Informational Submittal: Information submitted by Contractor that does not require Engineers
approval.
1.3
PROCEDURES
A.
B.
Transmittal of Submittal:
1.
Contractor shall:
a.
Review each submittal and check for compliance with Contract Documents.
b.
Stamp each submittal with uniform approval stamp before submitting to Engineer.
1). Stamp to include Project name, submittal number, Specification number, Contractors reviewer name, date of Contractors approval and statement certifying
that submittal has been reviewed, checked, and approved for compliance with
Contract Documents.
2). Engineer will not review submittals that do not bear Contractors approval
stamp and will return them without action.
2.
Complete, sign, and transmit with each submittal package, one Transmittal of
Contractors Submittal form. A blank Transmittal of Contractors Submittal form shall be
provided by Engineer.
3.
Identify Each Submittal with the Following:
a.
Numbering and Tracking System:
b.
Sequentially number each submittal.
c.
Resubmission of submittal shall have original number with sequential alphabetic
suffix.
Section 01 33 00
Submittal Procedures
1).
2).
3).
4).
4.
C.
Format:
1.
Do not base Shop Drawings on reproductions of Contract Documents.
2.
Package submittal information by individual Specification section. Do not combine
different Specification sections together in submittal package, unless otherwise directed
in Specification.
3.
Present in a clear and thorough manner and in sufficient detail to show kind, size,
arrangement, and function of components, materials, and devices, and compliance with
Contract Documents.
4.
Index with labeled tab dividers in orderly manner.
D.
E.
Processing Time:
1.
Time for review shall commence on Engineers receipt of submittal.
2.
Engineer will act upon Contractors submittal and transmit response to Contractor not
later than 30 days after receipt, unless otherwise specified.
3.
Re-submittals will be subject to same review time.
4.
No adjustment of Contract Times or Price will be allowed due to delays in progress of
Work caused by rejection and subsequent re-submittals.
F.
G.
Incomplete Submittals:
1.
Engineer will return entire submittal for Contractors revision if preliminary review deems
it incomplete.
2.
When any of the following are missing, submittal will be deemed incomplete:
a.
Contractors review stamp completed and signed.
b.
Transmittal of Contractors Submittal completed and signed.
c.
Insufficient number of copies.
3.
Submittals not required by Contract Documents:
4.
Will not be reviewed and will be returned stamped Not Subject to Review.
5.
Engineer will keep one copy and return all remaining copies to Contractor.
1.4
ACTION SUBMITTALS
A.
B.
Shop Drawings:
1.
Copies: Six.
2.
Identify and Indicate:
a.
Applicable Contract Drawing and Detail number, products, units and assemblies,
and system or equipment identification or tag numbers.
b.
Equipment and Component Title: Identical to title shown on Drawings.
c.
Critical field dimensions and relationships to other critical features of Work. Note
dimensions established by field measurement.
d.
Project-specific information drawn accurately to scale.
3.
Manufacturers standard schematic drawings and diagrams as follows:
a.
Modify to delete information that is not applicable to the Work.
Section 01 33 00
Submittal Procedures
b.
4.
5.
C.
Samples:
1.
Copies: One, unless otherwise specified in individual Specifications.
2.
Preparation: Mount, display, or package Samples in manner specified to facilitate review
of quality. Attach label on unexposed side that includes the following:
a.
Manufacturer name.
b.
Model number.
c.
Material.
d.
Sample source.
3.
Manufacturers Color Chart: Units or sections of units showing full range of colors,
textures, and patterns available.
4.
Full-size Samples:
a.
Size as indicated in individual Specification section.
b.
Prepared from same materials to be used for the Work.
c.
Cured and finished in manner specified.
d.
Physically identical with product proposed for use.
D.
Action Submittal Dispositions: Engineer will review, mark, and stamp as appropriate, and
distribute marked-up copies as noted:
1.
Furnish as Submitted:
a.
Contractor may incorporate product(s) or implement Work covered by submittal.
b.
Distribution
1). One copy furnished to Resident Project Representative.
2). Two copies retained in Engineers file.
3). Remaining copies returned to Contractor appropriately annotated.
2.
Furnish as Corrected:
a.
Contractor may incorporate product(s) or implement Work covered by submittal, in
accordance with Engineers notations.
b.
Distribution:
1). One copy furnished to Resident Project Representative.
2). Two copies retained in Engineers file.
3). Remaining copies returned to Contractor appropriately annotated.
3.
Revise and Resubmit:
a.
Make corrections or obtain missing portions, and resubmit.
b.
Except for portions indicated, Contractor may begin to incorporate product(s) or
implement Work covered by submittal, in accordance with Engineers notations.
c.
Distribution:
1). One copy furnished to Resident Project Representative.
2). Two copies retained in Engineers file.
3). Remaining copies returned to Contractor appropriately annotated.
4.
Rejected:
a.
Contractor may not incorporate product(s) or implement Work covered by
submittal.
b.
Distribution:
Section 01 33 00
Submittal Procedures
INFORMATIONAL SUBMITTALS
A.
General:
1.
Copies: Submit four copies, unless otherwise indicated in individual Specification section.
2.
Refer to individual Specification sections for specific submittal requirements.
3.
Engineer will review each submittal. If submittal meets conditions of the Contract,
Engineer will forward copies to appropriate parties. If Engineer determines submittal
does not meet conditions of the Contract and is therefore considered unacceptable,
Engineer will retain one copy and return remaining copies with review comments to
Contractor, and require that submittal be corrected and resubmitted.
4.
Certificates:
a.
General:
1). Provide notarized statement that includes signature of entity responsible for
preparing certification.
2). Signed by officer or other individual authorized to sign documents on behalf of
that entity.
5.
Welding: In accordance with individual Specification sections.
6.
Installer: Prepare written statements on Manufacturers letterhead certifying that installer
complies with requirements as specified in individual Specification sections.
7.
Material Test: Prepared by qualified testing agency, on testing agencys standard form,
indicating and interpreting test results of material for compliance with requirements.
8.
Certificates of Successful Testing or Inspection: Submit when testing or inspection is
required by Laws and Regulations or governing agency or specified in individual
Specification sections.
9.
Manufacturers Certificate of Compliance: In accordance with Section 01 79 00,
DEMONSTRATION AND TRAINING.
10.
Manufacturers Certificate of Proper Installation: In accordance with Section 01 79 00,
DEMONSTRATION AND TRAINING.
B.
C.
D.
Contractor-Design Data:
1.
Written and graphic information.
2.
List of assumptions.
3.
List of performance and design criteria.
4.
Summary of loads or load diagram, if applicable.
5.
Calculations.
6.
List of applicable codes and regulations.
7.
Name and version of software.
8.
Information requested in individual Specification section.
E.
F.
Section 01 33 00
Submittal Procedures
G.
Schedules:
1.
Schedule of Submittals: Prepare separately or in combination with Progress Schedule as
specified in Section 01 32 00, CONSTRUCTION PROGRESS DOCUMENTATION.
a.
Show for Each, at a Minimum, the Following:
1). Specification section number.
2). Identification by numbering and tracking system as specified under Paragraph
Transmittal of Submittal.
3). Estimated date of submission to Engineer, including reviewing and processing
time.
b.
On a monthly basis, submit updated schedule to Engineer if changes have
occurred or re-submittals are required.
2.
Schedule of Values: In accordance with Section 01 29 00, PAYMENT PROCEDURES.
3.
Schedule of Estimated Progress Payments: In accordance with Section 01 32 00,
CONSTRUCTION PROGRESS DOCUMENTATION.
4.
Progress Schedules: In accordance with Section 01 32 00, CONSTRUCTION
PROGRESS DOCUMENTATION.
H.
I.
J.
K.
Section 01 33 00
Submittal Procedures
4.
5.
Testing and Startup Data: In accordance with Section 01 79 00, DEMONSTRATION AND
TRAINING.
Training Data: In accordance with Section 01 79 00, DEMONSTRATION AND
TRAINING.
Section 01 33 00
Submittal Procedures
SUMMARY
A.
1.2
Section Includes: Special procedures for locating and verifying concealed existing facilities.
CONCEALED EXISTING FACILITIES
A.
Verify locations of utilities and facilities which may exist by consulting with the OWNER, utility
companies, and Call Okie (Oklahoma One-Call System) or other service available in area of
Project (see dig/call information on the Drawings):
1.
Abide by easement and right-of-way restrictions.
B.
Notify the OWNER, owners of facilities when the Work will be in progress. Make arrangements
for potential emergency repairs in accordance with requirements of owners of utility facilities,
including individual or residential facilities.
C.
D.
Expose sanitary and storm sewers, water, gas, electric, telephone utility lines, and other
underground facilities indicated to permit survey location prior to commencement of Work in
affected area:
1.
Expose in ample time to permit relocation of interfering utilities with minimum delaying
effect on contract time.
E.
Work required for raising, lowering, or relocating utilities not indicated will be performed by
affected utility owners or as part of the Work at option of affected owners of utilities:
1.
When part of the Work, perform work in accordance with standards of affected utility
owner, and adjustment to Contract Price and Contract Times will be made as stipulated
in conditions of contract.
END OF SECTION
Section 01 35 00
Special Procedures
SUMMARY
A.
Section Includes: Requirements and procedures for performing alterations to existing facilities.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 14 00 Work Restrictions.
b.
Section 01 50 00 Temporary Facilities and Controls.
c.
Section 01 73 20 Cutting and Patching.
D.
Section 01 73 80 Selective Demolition.
e.
Section 01 77 00 Closeout Procedures.
1.2
SUBMITTALS
A.
1.3
A.
B.
Submit separate detailed sub-schedule for alterations, coordinated with construction schedules.
Indicate:
1.
Each stage of Work and dates of occupancy of areas.
2.
Date of Substantial Completion for each area of alterations as appropriate.
3.
Trades and Subcontractors employed in each stage.
1.4
B.
C.
D.
Operational functions of the facility that are required to be performed to facilitate the Work will
be performed by facility personnel only.
Section 01 35 20
Alteration Project Procedures
E.
Plant Superintendent will cooperate in every way practicable to assist in expediting the Work.
F.
When necessary for the proper operation or maintenance of portions of the facility, reschedule
Work operations so that the Work will not conflict with necessary operations or maintenance of
the facility.
1.5
Assign relocation, removal, cutting, and patching to trades qualified to perform in manner which
causes least damage and provide means of returning surfaces to appearance of new
construction.
B.
Provide weather protection, waterproofing, heat and humidity control as needed to prevent
damage to remaining existing and new construction.
C.
1.6
SALVAGE MATERIALS
A.
B.
C.
D.
Pay costs associated with salvaging materials, including handling, transporting, and storage.
1.7
PREPARATION
A.
B.
C.
Cut and remove minimum amount of existing construction in manner which avoids damage to
adjacent work.
D.
Cut finish surfaces such as masonry, tile, plaster, and metals by methods which terminate
surfaces in straight line at natural points of division.
Section 01 35 20
Alteration Project Procedures
E.
1.8
A.
B.
C.
Clean spillage, overspray and heavy collection of dust in OWNER-occupied areas immediately.
D.
At completion of each portion of Work, clean area and make surfaces ready for successive
portions of Work.
E.
At completion of alterations in each area, provide final cleaning and return space to condition
suitable for use by OWNER.
END OF SECTION
Section 01 35 20
Alteration Project Procedures
SUMMARY
A.
1.2
A.
B.
C.
1.3
SYSTEM DESCRIPTION
A.
Design Requirements:
1.
Building code:
a.
International Building Code. As amended by the State of Oklahoma International
Existing Building Code. As amended by the State of Oklahoma
2.
Electrical code:
a.
NFPA 70: National Electric Code. As amended by the State of Oklahoma
Oklahoma Electrical Code.
3.
Energy conservation code:
a.
International Energy Conservation Code. As amended by the State of Oklahoma.
4.
Fire code:
a.
International Fire Code. As amended by the State of
5.
Mechanical codes:
a.
International Mechanical Code. As amended by the State of Oklahoma
6.
Plumbing code:
a.
International Plumbing Code. As amended by the State of Oklahoma
Section 01 41 00
Regulatory Requirements
SECTION 01 42 00 - REFERENCES
PART 1 - GENERAL
1.1
SUMMARY
A.
1.2
A.
Reference to standards and specifications of technical societies and reporting and resolving
discrepancies associated therewith shall be as provided in the General Conditions, and as may
otherwise be required herein and in the individual Specification sections.
B.
C.
Where so specified, products or workmanship shall also meet or exceed additional prescriptive
or performance requirements included within Contract Documents to establish a higher or more
stringent standard of quality than required by referenced standard.
D.
Where two or more standards are specified to establish quality, product and workmanship shall
meet or exceed requirements of most stringent.
E.
Where both a standard and a brand name are specified for a product in Contract Documents,
proprietary product named shall meet or exceed requirements of specified reference standard.
F.
1.3
ABBREVIATIONS
A.
Section 01 42 00
References
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
AITC
ALS
AMCA
ANSI
APA
API
APWA
ARI
ASAE
ASCE
ASHRAE
Inc.
ASME
ASNT
ASTM
AWI
AWPA
AWPI
AWS
AWWA
BHMA
CBM
CDA
CGA
CIS PI
CMAA
CRSI
CS
CSA
CSI
DIN
DIPRA
EIA
EJCDC
ETL
FAA
FCC
FDA
FEMA
FIPS
PM
Fed. Spec.
FS
GA
GANA
ID
HMI
IBC
ICBO
ICC
ICEA
IFC
IEEE
IESNA
IFI
IGMA
Section 01 42 00
References
68.
69.
70.
71.
72.
73.
74.
75.
76.
77.
78.
79.
80.
81.
82.
83.
84.
85.
86.
87.
88.
89.
90.
91.
92.
93.
94.
95.
96.
97.
98.
99.
100.
101.
102.
103.
104.
105.
106.
107.
108.
109.
110.
111.
112.
113.
114.
115.
116.
117.
118.
119.
120.
IMC
INDA
IPC
ISA
ISO
ITL
JIC
MIA
Mil.
MMA
NAAMM
NACE
NEBB
NEC
NECA
NEMA
NESC
NETA
NFPA
NHLA
NICET
NIST
NRCA
NRTL
NSF
NSPE
NTMA
NWWDA
OSHA
PCI
PEI
PPI
PS
RMA
RUS
SAE
SDI
SDI
SJI
SMACNA
SPI
SSPC
SWI
TEMA
TCA
TIA
UBC
UFC
UL
UMC
USBR
WCLIB
WWPA
Section 01 42 00
References
END OF SECTION
Section 01 42 00
References
SECTION 01 42 40 ABBREVIATIONS
PART 1 - GENERAL
1.1
SUMMARY
A.
1.2
A.
1.3
A.
Section 01 42 40
Abbreviations
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
71.
72.
73.
74.
75.
76.
77.
78.
79.
80.
81.
82.
83.
84.
85.
86.
87.
88.
89.
90.
91.
92.
93.
94.
CLFMI
CPSC
CRA
CRI
CRSI
CS
CSI
CTI
DHI
EIFS
EJCDC
FGMA
FIA
FM
FS
FTI
GA
IAPMO
IBC
ICBO
ICC
IEEE
MAG
MIA
ML/SFA
MS
NAAMM
NAPA
NBHA
NCMA
NEC
NECA
NETA
NEMA
NFPA
NFPA
NIST
NMWIA
NPCA
NRCA
NTMA
NWMA
PCA
PCI
PDCA
PDI
PEI
PS
RTI
SAE
SCPA
SDI
SIGMA
SJI
SMACNA
SSPC
Section 01 42 40
Abbreviations
95.
96.
97.
98.
99.
100.
101.
102.
103.
104.
105.
106.
107.
B.
TCA
UBC
UL
UNS
USDA
VA
WCLA
WCLIB
WPA
WPOA
WRC
WSCPA
WWPA
Section 01 42 40
Abbreviations
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
71.
72.
73.
74.
75.
76.
77.
78.
79.
80.
81.
82.
83.
84.
85.
86.
87.
88.
89.
90.
91.
92.
93.
94.
95.
96.
97.
db
DB
dc
diam
DO
DS
emf
fpm
F
ft
fc
ft/day
ft/hr
ft/min
ft/sec
g
G
gal
gal/day
gal/min
gal/sec
gfd
g/L
gpd
gpd/ac
gpd/cap
gpd/sq ft
gph
gpm
gps
h
ha
hp
hp
hp-hr
hr
Hz
ID
ihp
Inc.
inch
inches
inches/sec
J
JTU
k
K
K
kcal
kcmil
kg
km
kN
kPa
ksi
kV
decibels
dry bulb (temperature)
direct current
diameter
dissolved oxygen
dissolved solids
electromotive force
feet per minute
degrees Fahrenheit
feet or foot
foot-candle or foot candles
feet per day
feet per hour
feet per minute
feet per second
gram or grams
gravitational force
gallon or gallons
gallons per day
gallons per minutes
gallons per second
gallons per square foot per day
grams per liter
gallons per day
gallons per day per acre
gallons per day per capita
gallons per day per square foot
gallons per hour
gallons per minute
gallons per second
hour or hours (metric units)
hectare or hectares
high point
horsepower
horsepower-hour or horsepower-hours
hour or hours (English units)
hertz
inside diameter
indicated horsepower
Incorporated
inch
inches
inches per second
joule or joules
Jackson turbidity unit or units
kips
kelvin
thermal conductivity
kilocalorie or kilocalories
thousand circular mils
kilogram or kilograms
kilometer or kilometers
kilonewton or kilonewtons
kilopascal or kilopascals
kips per square inch
kilovolt or kilovolts
4
Section 01 42 40
Abbreviations
98.
99.
100.
101.
102.
103.
104.
105.
106.
107.
108.
109.
110.
111.
112.
113.
114.
115.
116.
117.
118.
119.
120.
121.
122.
123.
124.
125.
126.
127.
128.
129.
130.
131.
132.
133.
134.
135.
136.
137.
138.
139.
140.
141.
142.
143.
144.
145.
146.
147.
148.
149.
150.
151.
152.
153.
kVA
kW
kWh
L
lb/1000 cu ft
lb/acre-ft
lb/ac
lb/cu ft
lb/day/cu ft
lb/day/acre
lb/sq ft
lin
lin ft
lm
log
ln
lx
m
M
mA
max
mCi
meq
F
MFBM
mfr
mg
mgd/ac
mgd
mg/L
g/L
m
mile
mil. gal
miles
min
min
MLSS
MLVSS
mm
mol wt
mol
Mpa
mph
MPN
mR
Mrad
mV
MW
N
N
No.
Nos
NRC
NTU or ntu
oc
kilovolt-ampere or kilovolt-amperes
kilowatt or kilowatts
kilowatt hour
liter or liters
pounds per thousand cubic foot
pounds per acre-foot
pounds per acre
pounds per cubic foot
pounds per day per cubic foot
pounds per day per acre
pounds per square foot
linear, lineal
linear foot or feet
lumen or lumens
logarithm (common)
logarithm (natural)
lux
meter or meters
molar (concentration)
milliampere or milliamperes
maximum
millicurie or millicuries
milliequivalent
microfarad or microfarads
thousand feet board measure
manufacturer
milligram or milligrams
million gallons per day per acre
million gallons per day
milligrams per liter
micrograms per liter
micrometer or micrometers
mile
million gallons
miles
minimum
minute or minutes
mixed liquor suspended solids
miixed liquor volatile suspended solids
millimeter or millimeters
molecular weight
mole
megapascal or megapascals
miles per hour
most probable number
milliroentgen or milliroentgens
megarad or megarads
millivolt or millivolts
megawatt or megawatts
newton or newtons
normal (concentration)
number
numbers
noise reduction coefficient
nephelometric turbidity unit
on center
5
Section 01 42 40
Abbreviations
154.
155.
156.
157.
158.
159.
160.
161.
162.
163.
164.
165.
166.
167.
168.
169.
170.
171.
172.
173.
174.
175.
176.
177.
178.
179.
180.
181.
182.
183.
184.
185.
186.
187.
188.
189.
190.
191.
192.
193.
194.
195.
196.
197.
198.
199.
200.
201.
202.
203.
204.
205.
206.
207.
208.
OD
ORP
OT
OTA
oz
oz/sq ft
Pa
pl
pm
ppb
ppm
ppt
pr
psf/hr
psf
psi
psia
psig
PVC
qt
R
R
rad
RH
rpm
rps
S
S
SDI
sec
SI
sp
sp gr
sp ht
sq
2
cm or sq cm
sq ft
sq inch
sq inches
2
km or sq km
2
m or sq m
2
mm or sq mm
sq yd
SS
STC
SVI
TDS
TKN
TLM
TOC
TOD
TOW
TS
TSS
TVS
outside diameter
oxidation-reduction potential
ortho-tolidine
ortha-tolidine-arsenite
ounce or ounces
ounces per square foot
pascal or pascals
plate or property line
post meridiem (afternoon)
parts per billion
parts per million
parts per thousand
pair
pounds per square foot per hour
pounds per square foot
pounds per square inch
pounds per square inch absolute
pounds per square inch gauge
polyvinyl chloride
quart or quarts
radius
roentgen or roentgens
radiation absorbed dose
relative humidity
revolutions per minute
revolutions per second
second (metric units)
Siemens (mho)
sludge density index or silt density index
second (English units)
International System of Units
static pressure
specific gravity
specific heat
square
square centimeter or centimeters
square feet or foot
square inch
square inches
square kilometer or kilometers
square meter or meters
square millimeter or millimeters
square yard or yards
suspended solids
Sound Transmission Class
sludge volume index
total dissolved solids
total Kjeldahl nitrogen
median tolerance limit
total organic carbon
total oxygen demand
top of weir
total solids
total suspended solids
total volatile solids
6
Section 01 42 40
Abbreviations
209.
210.
211.
212.
213.
214.
215.
216.
217.
218.
219.
220.
221.
222.
C.
U
U
U
UNS
US
V
VA
W
WB
wg
wk
wt
yd
yr
U Factor/U Value
Coefficient of Heat Transfer
heat transfer coefficient
Uniform Numbering System
United States
volt or volts
volt-ampere or volt-amperes
watt or watts
wet bulb
water gauge
week or weeks
weight
yard or yards
year or years (English unit)
END OF SECTION
Section 01 42 40
Abbreviations
SUMMARY
A.
Section includes:
1.
Quality control and control of installation.
2.
Tolerances.
3.
References.
4.
Mock-up requirements.
5.
Authority and duties of Owners representative or inspector.
6.
Sampling and testing.
7.
Testing and inspection services.
8.
Contractors responsibilities.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the Contractors responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
Contractors Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the Contractor to see that the completed Work complies
accurately with the Contract Documents.
a.
Section 01 45 24 - Special Tests and Inspections.
1.2
Monitor quality control over suppliers, manufacturers, products, services, site conditions, and
workmanship, to produce Work of specified quality.
B.
C.
When manufacturers instructions conflict with Contract Documents, request clarification from
Engineer before proceeding.
D.
Comply with specified standards as minimum quality for the Work except where more stringent
tolerances, codes, or specified requirements indicate higher standards or more precise
workmanship.
E.
F.
G.
Secure products in place with positive anchorage devices designed and sized to withstand
stresses, vibration, physical distortion, or disfigurement.
H.
When specified, products will be tested and inspected either at point of origin or at Work site:
1.
Notify Engineer in writing well in advance of when products will be ready for testing and
inspection at point of origin.
2.
Do not construe that satisfactory tests and inspections at point of origin is final
acceptance of products. Satisfactory tests or inspections at point of origin do not preclude
retesting or re-inspection at Work site.
Section 01 45 00
Quality Control
I.
1.3
Do not ship products which require testing and inspection at point of origin prior to testing and
inspection.
TOLERANCES
A.
Monitor fabrication and installation tolerance control of products to produce acceptable Work.
Do not permit tolerances to accumulate.
B.
Comply with manufacturers tolerances. When Manufacturers tolerances conflict with Contract
Documents, request clarification from Engineer before proceeding.
C.
1.4
REFERENCES
A.
American Society for Testing and Materials (ASTM): E 329 - Standard for Agencies Engaged in
the Testing and/or Inspection of Materials Used in Construction.
B.
C.
Conform to reference standard by date of issue current on date of Contract Documents, except
where specific date is established by code.
D.
E.
When specified reference standards conflict with Contract Documents, request clarification from
Engineer before proceeding.
1.5
MOCK-UP REQUIREMENTS
A.
Tests will be performed under provisions identified in this Section and identified in respective
product specification sections.
B.
Assemble and erect specified items with specified attachment and anchorage devices,
flashings, seals, and finishes.
C.
D.
Where mock-up has been accepted by Engineer and is specified in product specification
sections to be removed; remove mock-up and clear area when directed to do so by Engineer.
1.6
B.
Inspections may extend to entire or part of the Work and to preparation, fabrication, and
manufacture of products for the Work.
C.
Deficiencies or defects in the Work which have been observed will be called to Contractors
attention.
D.
Section 01 45 00
Quality Control
1.
2.
3.
4.
E.
1.7
Inspector will:
1.
Conduct on-site observations of the Work in progress to assist Engineer in determining
when the Work is, in general, proceeding in accordance with Contract Documents.
2.
Report to Engineer whenever Inspector believes that Work is faulty, defective, does not
conform to Contract Documents, or has been damaged; or whenever there is defective
material or equipment; or whenever Inspector believes the Work should be uncovered for
observation or requires special procedures.
SAMPLING AND TESTING
A.
General:
1.
Prior to delivery and incorporation in the Work, submit listing of sources of materials,
when specified in sections where materials are specified.
2.
When specified in sections where products are specified:
a.
Submit sufficient quantities of representative samples of character and quality
required of materials to be used in the Work for testing or examination.
b.
Test materials in accordance with standards of national technical organizations.
B.
Sampling:
1.
Furnish specimens of materials when requested.
2.
Do not use materials which are required to be tested until testing indicates satisfactory
compliance with specified requirements.
3.
Specimens of materials will be taken for testing whenever necessary to determine quality
of material.
4.
Assist Engineer in preparation of test specimens at site of work, such as soil samples and
concrete test cylinders.
C.
Testing:
1.
Owner will employ and pay for services of independent testing laboratory to perform
routine tests of materials to confirm compliance with requirements of Contract
Documents:
a.
Mill tests, soil compaction test, and other specified tests shall be paid for by
Contractor.
2.
D.
When protesting failed tests of material in place or to be used, take additional specimens
and have specimens tested:
a.
When original test proves to have been in error, file claim for reimbursement of
direct costs for sampling and testing.
Test standards:
1.
Perform sampling, specimen preparation, and testing of materials in accordance with
specified standards, and when no standard is specified, in accordance with standard of
nationally recognized technical organization.
2.
Physical characteristics of materials not particularly specified shall conform to standards
published by ASTM, where applicable.
3.
Standards and publication references in Contract Documents shall be edition or revision
in effect on date stipulated in the Contract Documents.
Section 01 45 00
Quality Control
1.8
Contractor will employ and pay for specified services of an independent firm; known as
Contractors independent testing firm, to perform Contractor quality control testing as required in
the technical specifications for various work and materials.
B.
Owner will employ and pay for specified services of an Owners independent testing firm to
perform testing and inspection as required in the technical specifications for various work and
materials or stipulated in Section 01 45 24 to confirm Contractors compliance with Contract
Documents. If Engineer or Owners independent testing firm is not properly certified to perform
specialty inspections required by the building department, Owner will employ and pay for a
quality specialty inspection firm to perform required testing and inspection.
C.
The Contractors independent testing firm will perform tests, inspections and other services
specified in individual specification sections and as required by Owner and requested by the
Engineer.
D.
The qualifications of laboratory that will perform the testing, contracted by the Owner or by the
Contractor, shall be as follows:
1.
Has authorization to operate in the state where the project is located.
2.
Meets Recommended Requirements for Independent Laboratory Qualification,
published by American Council of Independent Laboratories.
3.
Meets requirements of ASTM E 329.
4.
Laboratory Staff: Maintain full time specialist on staff to review services.
5.
Testing Equipment: Calibrated at reasonable intervals with devices of accuracy traceable
to National Bureau of Standards (NBS) or accepted values of natural physical constants.
6.
Will submit copy of report of inspection of facilities made by Materials Reference
Laboratory of NBS during most recent tour of inspection, with memorandum of remedies
of deficiencies reported by inspection.
E.
Testing, inspections and source quality control may occur on or off project site. Perform off-site
testing inspections and source quality control as required by Engineer or Owner.
F.
Reports will be submitted by Contractors independent testing firm and by Owners independent
testing firm to Engineer, Contractor, and Owner in triplicate, indicating observations and results
of tests and indicating compliance or non-compliance with Contract Documents. Each report
shall include:
1.
Date issued.
2.
Project title and number.
3.
Testing laboratory name, address, and telephone number.
4.
Name and signature of laboratory inspector.
5.
Date and time of sampling or inspection.
6.
Record of temperature and weather conditions.
7.
Date of test.
8.
Identification of product and specification section.
9.
Location of sample or test in Project.
10.
Type of inspection or test.
11.
Results of tests and compliance with Contract Documents.
12.
Interpretation of test results, when requested by Engineer.
G.
Contractor shall cooperate with Owners independent testing firm, furnish samples of materials,
design mix, equipment, tools, storage, safe access, and assistance by incidental labor as
requested.
1.
Notify Engineer and Owners independent testing firm 48 hours prior to expected time for
operations requiring testing.
Section 01 45 00
Quality Control
2.
Make arrangements with Owners independent testing firm and pay for additional
samples and tests required for Contractors use.
H.
I.
Testing and employment of an Owners independent testing firm or laboratory shall not relieve
Contractor of obligation to perform Work in accordance with requirements of Contract
Documents.
J.
K.
L.
Owners independent testing firm individual test reports: After each test, Owners independent
testing firm will promptly submit electronically and three hard copies of report to Engineer and to
Contractor. When requested by Engineer, the Owners independent testing firm will provide
interpretation of test results. Include the following:
1.
Date issued.
2.
Project title and number.
3.
Name of inspector.
4.
Date and time of sampling or inspection.
5.
Identification of product and specifications section.
6.
Location in Project.
7.
Type of inspection or test.
8.
Date of test.
9.
Certified test results stamped and signed by a registered Engineer in the State of
Oklahoma.
10.
Summary of conformance with Contract Documents.
M.
Owners independent testing firm will provide monthly report of certification to identify all work
performed for special inspections and other contract requirements on this project. The following
certified monthly report at a minimum will include but not limited to:
1.
Results of testing.
2.
Testing logs.
3.
Outstanding deficiencies.
4.
Various statistical data.
5.
Testing curves (up to 4 types) as required by the Engineer.
Section 01 45 00
Quality Control
1.9
CONTRACTORS RESPONSIBILITIES
A.
Cooperate with Owners independent testing firm or laboratory personnel and provide access to
construction and manufacturing operations.
B.
Secure and deliver to Owners independent testing firm or laboratory adequate quantities of
representative samples of materials proposed to be used and which require testing.
C.
Provide to Owners independent testing firm or laboratory and Engineer preliminary mix design
proposed to be used for concrete, and other materials mixes which require control by testing
laboratory.
D.
E.
F.
Section 01 45 00
Quality Control
SUMMARY
A.
Section includes: This Section describes the requirements for providing special tests and
inspections.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 45 00 - Quality Control.
1.2
REFERENCES
A.
B.
1.3
DESCRIPTION
A.
This Section describes special tests and inspections of structural assemblies and components
to be performed in compliance with IBC with State of Oklahoma amendments.
B.
These special tests and inspections are in addition to the requirements specified in Section 01
45 00, and by the individual Sections.
C.
The OWNER will employ one or more inspectors who will provide special inspections during
construction.
1.4
INSPECTION
A.
1.5
A.
Selection of the material required to be tested shall be by the OWNERs Testing Laboratory and
not the CONTRACTOR.
Section 01 45 24
Special Tests and Inspections
1.6
Testing laboratory: Special tests will be performed by the OWNERs testing laboratory as
specified in Section 01 45 00.
B.
C.
The following types of work require special inspection as described in IBC with State of
Oklahoma amendments, Refer to the following verification, testing and inspection schedules.
1.
Appendix A, Cast-In-Place Concrete Special Inspection Schedule.
2.
Appendix B, Essential Architectural, Mechanical and Electrical Inspection Schedule.
3.
Appendix C, Essential Masonry Special Inspection Schedule.
4.
Appendix D, Soils Verification And Inspection Schedule.
5.
Appendix E, Structural Steel Special Inspection Schedule.
6.
Appendix F. Other Special Inspection.
1.7
Masonry shall be tested in accordance with IBC with State of Oklahoma amendments.
1.
Minimum strength of units shall be tested in accordance with ASTM C140.
2.
Minimum strength of grout shall be tested in accordance with ASTM C1019.
3.
Prior to construction, obtain samples of the aggregates, additives, and water; mix and
test in laboratory in accordance with ASTM C270.
4.
During construction, sample and test masonry for consistency prior to use on each
structure in accordance with ASTM C780.
5.
When approved by the building official, if installed masonry does not meet requirements,
conduct prism tests in accordance with ASTM C1314.
SCHEDULE
A.
The CONTRACTOR shall allow time necessary for Special Inspections as listed above.
B.
Sufficient notice shall be given so that the Special Inspections can be performed. This includes
time for off-site Special Inspectors to plan the inspection and travel to site.
3.2
PROCEDURE
A.
The Special Inspector will immediately notify the ENGINEER of any corrections required and
follow notification with appropriate documentation.
B.
The CONTRACTOR shall not proceed until the work is satisfactory to the ENGINEER.
END OF SECTION
Section 01 45 24
Special Tests and Inspections
APPENDIX A
CAST-IN-PLACE CONCRETE SPECIAL INSPECTION SCHEDULE
Verification and Inspection
Reference
Standard
Frequency of Inspection
Periodic
Continuous
During
During Task
Task
Listed
Listed
X
X
Section 01 45 24
Special Tests and Inspections
APPENDIX B
ESSENTIAL ARCHITECTURAL, MECHANICAL AND ELECTRICAL
INSPECTION SCHEDULE
Verification and Inspection
Reference
Standard
Frequency of Inspection
Periodic
During
Continuous
Task
During Task
Listed
Listed
X
X
X
X
Section 01 45 24
Special Tests and Inspections
APPENDIX C
ESSENTIAL MASONRY SPECIAL INSPECTION SCHEDULE
Verification and Inspection
1.
2.
Reference
Standard
Frequency of Inspection
Continuous
During Task
Listed
Periodic
During
Task
Listed
e. Placement of grout.
3.
4.
Section 01 45 24
Special Tests and Inspections
APPENDIX D
SOILS VERIFICATION AND INSPECTION SCHEDULE
Verification and Inspection
Reference
Standard
Frequency of Inspection
Periodic
Continuous
During
During Task
Task
Listed
Listed
Section 01 45 24
Special Tests and Inspections
APPENDIX E
STRUCTURAL STEEL SPECIAL INSPECTION SCHEDULE
Verification and Inspection
Reference
Standard
Frequency of Inspection
Continuous
Periodic
During Task
During
Listed
Task Listed
X
X
X
X
X
X
X
X
X
X
X
X
X
Section 01 45 24
Special Tests and Inspections
APPENDIX F
OTHER SPECIAL INSPECTION SCHEDULE
Verification and Inspection
1.
2.
3.
4.
5.
6.
7.
Reference
Standard
Shoring of Excavations.
Reinforced gypsum concrete.
Shotcrete.
Smoke control system.
Special grading, excavating, and filling.
Spray applied fire resistive material.
Special seismic resistance details.
Frequency of Inspection
Periodic
Continuous
During
During Task
Task
Listed
Listed
Section 01 45 24
Special Tests and Inspections
SUMMARY
A.
Section Includes:
1.
Furnishing, maintaining, and removing construction facilities and temporary controls,
including temporary utilities, construction aids, barriers and enclosures, security, access
roads, temporary controls, project sign, field offices and sheds, and removal after
construction.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 14 00 Work Restrictions.
b.
Section 01 33 00 Submittal Procedures
c.
Section 01 60 00 Product Requirements
1.2
REFERENCES
A.
1.3
A.
Informational Submittals:
1.
General: For products specified to be furnished under this Section, submit product data in
accordance with Section 01 33 00.
2.
For Temporary Piping Systems:
a.
Submit layout drawings showing proposed routing of piping, including proposed
pipe support and pipe restraint locations.
b.
Submit product data for piping, fittings, appurtenances, restraints, supports, and all
other components of the temporary piping system.
c.
Submit all information at least 28 days prior to when each temporary piping system
is scheduled to be installed and allow 14 days for review and comment by
ENGINEER and OWNER.
3.
Copies of permits and approvals for construction as required by Laws and Regulations
and governing agencies.
4.
Temporary Utility Submittals:
a.
Electric power supply and distribution plans.
Section 01 50 00
Temporary Facilities and Controls
5.
6.
1.4
b.
Water supply and distribution plans.
c.
Drainage plans.
d.
Sanitary sewer.
Temporary Construction Submittals:
a.
Access Roads: Routes, cross-sections, and drainage facilities.
b.
Parking area plans.
c.
Contractors field office, storage yard, and storage building plans, including gravel
surfaced area.
d.
Fencing and protective barrier locations and details.
e.
Engineers field office plans.
f.
Staging area location plan.
g.
Traffic and Pedestrian Control and Routing Plans: As specified herein, and
proposed revisions thereto.
Temporary Control Submittals:
a.
Noise control plan.
b.
Plan for disposal of waste materials and intended haul routes.
MOBILIZATION
A.
Mobilization shall Include, but Not be Limited to, these Principal Items:
1.
Obtaining required permits.
2.
Moving Contractors field office and equipment required for first month operations onto
Site.
3.
Installing temporary construction power, wiring, and lighting facilities.
4.
Providing onsite communication facilities, including telephones.
5.
Providing onsite sanitary facilities and potable water facilities as specified and as required
by Laws and Regulations, and governing agencies.
6.
Arrange for and erection of Contractors work and storage yard.
7.
Posting OSHA required notices and establishing safety programs and procedures.
8.
Have Contractors superintendent at Site full time.
B.
1.5
B.
C.
1.6
VEHICULAR TRAFFIC
A.
1.7
Traffic Routing Plan: Show sequences of construction affecting use of roadways, time required
for each phase of the Work, provisions for decking over excavations and phasing of operations
to provide necessary access, and plans for signing, barricading, and striping to provide
passages for pedestrians and vehicles.
TEMPORARY UTILITIES
A.
Section 01 50 00
Temporary Facilities and Controls
3.
Provide, maintain, and pay for electric power for performance of the Work except for
power required for the final 7-day operational test:
a.
When using permanent facilities, provide separate meter and reimburse OWNER
for power used in connection with performance of the Work.
B.
C.
D.
Temporary Water:
1.
Pay for and construct facilities necessary to furnish potable water for human consumption
and non-potable water for use during construction.
2.
Remove temporary piping and connections and restore affected portions of the facility to
original condition before Substantial Completion.
3.
Pay for water used for construction prior to Substantial Completion. OWNER will provide
water for 7-day final test.
4.
Development of Non-Potable Water Supply:
a.
Non-potable water is available from hydrants or hose valves within plant without
cost. When combined demand of the Work and plant exceeds plant supply
capacity, provide additional temporary supply capacity.
b.
Post ample signs throughout the work area warning that plant water is not potable.
E.
F.
Temporary Fire Protection: Provide sufficient number of fire extinguishers of type and capacity
required to protect the Work and ancillary facilities.
G.
First Aid: Post first aid facilities and information posters conforming to requirements of OSHA
and other applicable Laws and Regulations in readily accessible locations.
H.
1.8
CONSTRUCTION AIDS
A.
Provide railings, kick plates, enclosures, safety devices, and controls required by Laws and
Regulations and as required for adequate protection of life and property.
B.
Use construction hoists, elevators, scaffolds, stages, shoring, and similar temporary facilities of
ample size and capacity to adequately support and move loads.
Section 01 50 00
Temporary Facilities and Controls
C.
Design temporary supports with adequate safety factor to assure adequate load bearing
capability:
1.
When requested, submit design calculations by professional registered engineer prior to
application of loads.
2.
Submitted design calculations are for information and record purposes only.
D.
Accident Prevention:
1.
Exercise precautions throughout construction for protection of persons and property.
2.
Observe safety provisions of applicable Laws and Regulations.
3.
Guard machinery and equipment, and eliminate other hazards.
4.
Make reports required by authorities having jurisdiction, and permit safety inspections of
the Work.
5.
Before commencing construction work, take necessary action to comply with provisions
for safety and accident prevention.
E.
Barricades:
1.
Place barriers at ends of excavations and along excavations to warn pedestrian and
vehicular traffic of excavations.
2.
Provide barriers with flashing lights after dark.
3.
Keep barriers in place until excavations are entirely backfilled and compacted.
4.
Barricade excavations to prevent persons from entering excavated areas in streets,
roadways, parking lots, treatment plants, or other public or private areas.
F.
Warning Devices and Barricades: Adequately identify and guard hazardous areas and
conditions by visual warning devices and, where necessary, physical barriers:
1.
Devices shall conform to minimum requirements of OSHA and State agency which
administers OSHA regulations where Project is located.
G.
H.
Hazards in Protected Areas: Mark or guard excavations in areas from which public is excluded,
in manner appropriate for hazard.
I.
Above Grade Protection: On multi-level structures, provide safety protection that meets
requirements of OSHA and State agency which administers OSHA regulations where Project is
located.
J.
Protect existing structures, trees, shrubs, and other items to be preserved on Project site from
injury, damage or destruction by vehicles, equipment, worker or other agents with substantial
barricades or other devices commensurate with hazards.
K.
Fences:
1.
Enclose site of the Work with fence adequate to protect the Work against acts of theft,
violence and vandalism.
2.
Enclose temporary offices and storage areas with fence adequate to protect temporary
facilities against acts of theft, violence and vandalism.
Section 01 50 00
Temporary Facilities and Controls
3.
4.
5.
6.
1.9
When entire or part of site is to be permanently fenced, permanent fence may be built to
serve for both permanent and temporary protection of the work site, provided that
damaged or defaced fencing is replaced prior to Substantial Completion.
Protect temporary and permanent openings and close openings in existing fences to
prevent intrusion by unauthorized persons. Bear responsibility for protection of plant and
material on site of the Work when openings in existing fences are not closed.
During night hours, weekends, holidays, and other times when no work is performed at
site, provide temporary closures or enlist services of security guards to protect temporary
openings.
Fence temporary openings when openings are no longer necessary.
SECURITY
A.
1.10
Make adequate provision for protection of the work area against fire, theft, and vandalism, and
for protection of public against exposure to injury.
ACCESS ROADS
A.
General:
1.
Build and maintain access roads to and on site of the Work to provide for delivery of
material and for access to existing and operating plant facilities on site.
2.
Build and maintain dust free roads which are suitable for travel at 20 miles per hour.
B.
C.
1.11
TEMPORARY CONTROLS
A.
Dust Control:
1.
Prevent dust nuisance caused by operations, unpaved roads, excavation, backfilling,
demolition, or other activities.
2.
Control dust by sprinkling with water, use of dust palliatives, modification of operations, or
other means acceptable to agencies having jurisdiction.
B.
Noise Control:
1.
In inhabited areas, particularly residential, perform operations in manner to minimize
noise.
2.
In residential areas, take special measures to suppress noise during night hours.
C.
Mud Control:
1.
Prevent mud nuisance caused by construction operations, unpaved roads, excavation,
backfilling, demolition, or other activities.
Section 01 50 00
Temporary Facilities and Controls
1.12
PROJECT SIGN
A.
Provide and maintain Project identification sign consisting of painted 8 foot wide by 4 foot high
exterior grade plywood and minimum 10 foot long 4 by 4 lumber posts, set in ground at least 3
feet, with exhibit lettering by professional sign painter using no more than 5 sign colors:
1.
List at least the title of the Project, and names of the OWNER, ENGINEER, and
CONTRACTOR.
B.
1.13
REMOVAL
A.
Remove temporary buildings and furnishings before inspection for Substantial Completion or
when directed.
B.
C.
D.
PART 2 - PRODUCTS
2.1
PART 3 - EXECUTION
3.1
TEMPORARY UTILITIES
A.
Power:
1.
Electric power will be available at or near Site. Determine type and amount available and
make arrangements for obtaining temporary electric power service, metering equipment,
and pay all costs for electric power used during contract period, except for portions of the
Work designated in writing by Engineer as substantially complete.
2.
Cost of electric power will be borne by Contractor.
B.
Lighting: Provide temporary lighting to meet applicable safety requirements to allow erection,
application, or installation of materials and equipment, and observation or inspection of the
Work.
C.
Section 01 50 00
Temporary Facilities and Controls
3.
4.
Pay all costs of installation, maintenance, operation, removal, and fuel consumed.
Provide portable unit heaters, complete with controls, oil- or gas-fired, and suitably
vented to outside as required for protection of health and property.
D.
Water:
1.
Potable water is available at the site. Secure written permission for connection and use
from Owner and meet requirements for use. Contractor shall pay cost to connect water
during construction. Owner shall pay cost to for water used during construction.
2.
Include costs to connect and transport water to construction areas in Contract Price.
3.
Provide a means to prevent water used for testing from flowing back into source pipeline.
E.
F.
Telephone Service:
1.
Contractor: Arrange and provide onsite telephone service for use during construction by
Contractor. Pay costs of installation and monthly bills.
2.
Engineer: Arrange and provide onsite telephone system for use during construction. Pay
for all installation and basic monthly billing charges.
3.
No incoming calls allowed to Owners plant telephone system.
G.
Fire Protection: Furnish and maintain on Site adequate firefighting equipment capable of
extinguishing incipient fires. Comply with applicable parts of National Fire Prevention Standard
for Safeguarding Building Construction Operations (NFPA No. 241).
3.2
General:
1.
Perform Work within right-of-way and easements in a systematic manner that minimizes
inconvenience to property owners and the public.
2.
Schedule the Work so construction will not interfere with irrigation of cultivated lands or
pasturelands. Construction may proceed during irrigation season, provided Contractor
constructs temporary irrigation ditches, turnouts, and miscellaneous structures
acceptable to property owners.
3.
Provide continuous access for livestock through farm areas. Do not cut off ready access
to portions of farmlands in which livestock are pastured. Maintain existing fences required
to restrain livestock. Keep gates closed and secure.
4.
Maintain in continuous service all existing oil and gas pipelines, underground power,
telephone or communication cable, water mains, irrigation lines, sewers, poles and
overhead power, and all other utilities encountered along line of the Work, unless other
arrangements satisfactory to owners of said utilities have been made.
5.
Where completion of the Work requires temporary or permanent removal or relocation of
existing utility, coordinate all activities with owner of said utility and perform all work to
their satisfaction.
6.
Protect, shore, brace, support, and maintain underground pipes, conduits, drains, and
other underground utility construction uncovered or otherwise affected by construction
operations.
7.
In areas where Contractors operations are adjacent to or near a utility, such as gas,
telephone, television, electric power, water, sewer, or irrigation system, and such
operations may cause damage or inconvenience, suspend operations until arrangements
necessary for protection have been made by Contractor.
8.
Notify property owners and utility offices that may be affected by construction operation at
least 2 days in advance: Before exposing a utility, obtain utility owners permission.
Should service of a utility become interrupted due to Contractors operation, notify proper
Section 01 50 00
Temporary Facilities and Controls
9.
10.
B.
Site Security:
1.
Erect a temporary security fence for protection of existing facilities. Maintain fence
throughout construction period. Obtain Engineers written permission before removal of
temporary security fencing.
2.
Provide and maintain additional temporary security fences as necessary to protect the
Work and Contractor-furnished products not yet installed.
C.
D.
E.
Existing Structures:
1.
Where Contractor contemplates removal of small structures such as mailboxes,
signposts, and culverts that interfere with Contractors operations, obtain approval of
property owner and Engineer.
2.
Move mailboxes to temporary locations accessible to postal service.
3.
Replace items removed in their original location and a condition equal to or better than
original.
F.
Finished Construction: Protect finished floors and concrete floors exposed as well as those
covered with composition tile or other applied surfacing.
G.
Waterways: Keep ditches, culverts, and natural drainages continuously free of construction
materials and debris.
H.
Dewatering: Construct, maintain, and operate cofferdams, channels, flume drains, sumps,
pumps, or other temporary diversion and protection works. Furnish materials required, install,
maintain, and operate necessary pumping and other equipment for the environmentally safe
removal and disposal of water from the various parts of the Work. Maintain foundations and
parts of the Work free from water.
Section 01 50 00
Temporary Facilities and Controls
3.3
TEMPORARY CONTROLS
A.
B.
Noise Control:
1.
Noise Control Plan: Propose plan to mitigate construction noise and to comply with noise
control ordinances, including method of construction, equipment to be used, and
acoustical treatments.
C.
D.
Erosion, Sediment, and Flood Control: Provide, maintain, and operate temporary facilities to
control erosion and sediment releases, and to protect the Work and existing facilities from
flooding during construction period.
3.4
B.
Temporary Storage Yards: Construct temporary storage yards for storage of products that are
not subject to damage by weather conditions.
C.
Section 01 50 00
Temporary Facilities and Controls
4.
3.5
ACCESS ROADS
A.
Construct access roads as required and within easements, rights-of-way, or Project limits.
Obtain Engineers approval of access roads.
B.
Maintain drainage ways. Install and maintain culverts to allow water to flow beneath access
roads. Provide corrosion-resistant culvert pipe of adequate strength to resist construction loads.
C.
Provide gravel, crushed rock, or other stabilization material to permit access by all motor
vehicles at all times.
D.
Maintain road grade and crown to eliminate potholes, rutting, and other irregularities that restrict
access.
E.
Coordinate with Engineer detours and other operations affecting traffic and access. Provide at
least 72 hours notice to Engineer of operations that will alter access to the Site.
F.
Where access road crosses existing fences, install and maintain gates.
G.
Upon completion of construction, restore ground surface disturbed by access road construction
to original grade. Replace damaged or broken culverts with new culvert pipe of same diameter
and material.
3.6
PARKING AREAS
A.
Control vehicular parking to preclude interference with public traffic or parking, access by
emergency vehicles, Owners operations, or construction operations.
B.
Provide parking facilities for personnel working on the Project. No employee or equipment
parking will be permitted on Owners existing parking areas, except as specifically designated
for Contractors use.
3.7
VEHICULAR TRAFFIC
A.
Comply with Laws and Regulations regarding closing or restricting use of public streets or
highways. No public or private road shall be closed, except by written permission of proper
authority. Assure the least possible obstruction to traffic and normal commercial pursuits.
B.
Conduct the Work to interfere as little as possible with public travel, whether vehicular or
pedestrian.
C.
Whenever it is necessary to cross, close, or obstruct roads, driveways, and walks, whether
public or private, provide and maintain suitable and safe bridges, detours, or other temporary
expedients for accommodation of public and private travel.
D.
Coordinate traffic routing with that of others working in same or adjacent areas.
E.
10
Section 01 50 00
Temporary Facilities and Controls
F.
Wet down exterior surfaces prior to sweeping to prevent blowing of dust and debris. At least
weekly, sweep all floors (basins, tunnels, platforms, walkways, roof surfaces), and pick up all
debris and dispose.
G.
Provide approved containers for collection and disposal of waste materials, debris, and rubbish.
At least at weekly intervals, dispose of such waste materials, debris, and rubbish offsite.
H.
At least weekly, brush sweep entry drive and roadways, and all other streets and walkways
affected by the Work and where adjacent to the Work.
END OF SECTION
11
Section 01 50 00
Temporary Facilities and Controls
SUMMARY
A.
Section includes description and requirements of the required new products for the project:
1.
Providing and delivering.
2.
Design and environmental requirements.
3.
Shipment.
4.
Delivery and Inspection.
5.
Handling, Storage and Protection.
6.
Inspection and Installation.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
01 50 00 Temporary Facilities and Controls.
b.
09 90 00 Painting and Protective Coatings.
1.2
DEFINITIONS
A.
1.3
Products:
1.
New items for incorporation in the Work whether purchased by Contractor or Owner for
the Project, or taken from previously purchased stock and may also include existing
materials or components required for reuse.
2.
Includes the terms material, equipment, machinery, components, subsystem, system,
hardware, software, and terms of similar intent and is not intended to change meaning of
such other terms used in Contract Documents, as those terms are self-explanatory and
have well recognized meanings in construction industry.
3.
Items identified by Manufacturers product name, including make or model designation,
indicated in Manufacturers published product literature, that is current as of the date of
the Contract Documents.
DESIGN REQUIREMENTS
A.
1.4
A.
Altitude: Provide materials and equipment suitable for installation and operation under rated
conditions at elevations shown on Drawings.
B.
Section 01 60 00
Product Requirements
1.5
When practical, have the factory assemble products, mark or tag separate parts and assemblies
to facilitate field assembly. Cover machined and unpainted parts that may be damaged by the
elements with strippable protective coating.
B.
Package products to facilitate handling and protect from damage during shipping, handling, and
storage. Mark or tag outside of each package or crate to indicate its purchase order number,
bill of lading number, contents by name, name of Project and Contractor, equipment number,
and approximate weight. Include complete packing list and bill of materials with each shipment.
C.
D.
Request a minimum 7-day advance notice of shipment from manufacturer. Upon receipt of
Manufacturers advance notice of shipment, promptly notify Engineer of anticipated date of
equipment arrival.
E.
Factory Test Results: Reviewed and accepted by Engineer before product shipment as
required in individual Specification sections.
1.6
Deliver products in accordance with accepted current Progress Schedule and coordinate to
avoid conflict with the Work and conditions at Site. Deliver anchor bolts and templates
sufficiently early to permit setting prior to placement of structural concrete.
B.
C.
Section 01 60 00
Product Requirements
D.
1.7
Remove damaged products from Site, and expedite delivery of identical new undamaged
products, and remedy incomplete or lost products to provide that specified, so as not to delay
progress of the Work.
HANDLING, STORAGE, AND PROTECTION
A.
Handle and store products in accordance with Manufacturers written instructions and in a
manner to prevent damage. Store in approved storage yards or sheds provided in accordance
with Section 01 50 00, TEMPORARY FACILITIES AND CONTROLS. Provide Manufacturers
recommended maintenance during storage, installation, and until products are accepted for use
by Owner.
B.
Arrange storage in a manner to provide easy access for inspection. Make periodic inspections
of stored products to assure that products are maintained under specified conditions, and free
from damage or deterioration. Keep running account of products in. storage to facilitate
inspection and to estimate progress payments for products delivered, but not installed in the
Work.
C.
Store electrical, instrumentation, and control products, and equipment with bearings in weathertight structures maintained above 60 F. Protect electrical, instrumentation, and control
products, and insulation against moisture, water, and dust damage. Connect and operate
continuously all space heaters furnished in electrical equipment.
D.
Store fabricated products above ground on blocking or skids, prevent soiling or staining, and
store loose granular materials in well-drained area on solid surface to prevent mixing with
foreign matter. Cover products that are subject to deterioration with impervious sheet coverings;
provide adequate ventilation to avoid condensation.
E.
Store finished products that are ready for installation in dry and well-ventilated areas. Do not
subject to extreme changes in temperature or humidity.
F.
After installation, provide coverings to protect products from damage due to traffic and
construction operations. Remove coverings when no longer needed.
G.
Hazardous Materials: Prevent contamination of personnel, storage building, and Site. Meet
requirements of product specification, codes, and manufacturers instructions.
PART 2 - PRODUCTS
2.1
GENERAL
A.
Provide the Manufacturers standard materials suitable for service conditions unless otherwise
specified in the individual Specifications.
B.
Where product specifications include a named Manufacturer, with or without model number, and
also include performance requirements, named Manufacturers products must meet the
performance specifications.
C.
Like items of products furnished and installed in the Work shall be end products of one
Manufacturer and of the same series or family of models to achieve standardization for
appearance, operation and maintenance, spare parts and replacement, Manufacturers
services, and implement same or similar process instrumentation and control functions in same
or similar manner.
Section 01 60 00
Product Requirements
D.
Do not use materials and equipment removed from existing premises, except as specifically
permitted by Contract Documents.
E.
Provide interchangeable components of the same Manufacturer, for similar components, unless
otherwise specified.
F.
Equipment, components, systems, sub-systems: Design and manufacture with due regard for
health and safety of operation, maintenance, and accessibility, durability of parts, and shall
comply with applicable OSHA, State, and local health and safety regulations.
G.
Regulatory Requirement: Coating materials shall meet Federal, State, and local requirements
limiting the emission of volatile organic compounds and for worker exposure.
H.
Safety Guards: Provide for all belt or chain drives, fan blades, couplings, or other moving or
rotary parts. Cover rotating part on all sides. Design for easy installation and removal. Use 16gauge or heavier; galvanized steel, aluminum coated steel, or galvanized or aluminum coated
mesh expanded steel. Provide galvanized steel accessories and supports, including bolts.
For outdoors application, prevent entrance of rain and dripping water.
I.
J.
Equipment Finish:
1.
Provide Manufacturers standard finish and color, except where specific color is indicated.
2.
If Manufacturer has no standard color, provide equipment with gray finish as approved by
Engineer.
K.
Special Tools and Accessories: Furnish to Owner, upon acceptance of equipment, all
accessories required to place each item of equipment in full operation. These accessory items
include, but are not limited to, adequate oil and grease (as required for first lubrication of
equipment after field testing), light bulbs, fuses, hydrant wrenches, valve keys, hand wheels,
chain operators, special tools, and other spare parts as required for maintenance.
L.
2.2
General:
1.
Manufacture parts to U.S.A. standard sizes and gauges.
2.
Two or more items of the same type shall be identical, by the same Manufacturer, and
interchangeable.
3.
Design structural members for anticipated shock and vibratory loads.
4.
Use 1/4 minimum thickness for steel that will be submerged, wholly or partially, during
normal operation.
5.
Modify standard products as necessary to meet performance Specifications.
Section 01 60 00
Product Requirements
B.
2.3
Lubrication System:
1.
Require no more than weekly attention during continuous operation.
2.
Convenient and accessible. Oil drains with bronze or stainless steel valves and fill-plugs
easily accessible from the normal operating area or platform.
3.
Locate drains to allow convenient collection of oil during oil changes without removing
equipment from its installed position.
4.
Provide constant-level oilers or oil level indicators for oil lubrication systems.
5.
For grease type bearings, which are not easily accessible, provide and install stainless
steel tubing; protect and extend tubing to convenient location with suitable grease fitting.
SOURCE QUALITY CONTROL
A.
Where Specifications call for factory testing to be witnessed by Engineer, notify Engineer not
less than 14 days prior to scheduled test date, unless otherwise specified.
B.
Calibration Instruments: Bear the seal of a reputable laboratory certifying instrument has been
calibrated within the previous 12 months to a standard endorsed by the National Institute of
Standards and Technology (NIST).
C.
Factory Tests: Perform in accordance with accepted test procedures and document successful
completion.
PART 3 - EXECUTION
3.1
INSPECTION
A.
3.2
Inspect materials and equipment for signs of pitting, rust decay, or other deleterious effects of
storage. Do not install material or equipment showing such effects. Remove damaged material
or equipment from the Site and expedite delivery of identical new material or equipment. Delays
to the Work resulting from material or equipment damage that necessitates procurement of new
products will be considered delays within Contractors control.
INSTALLATION
A.
Equipment Drawings show general locations of equipment, devices, and raceway, unless
specifically dimensioned.
B.
C.
Install the Work in accordance with NECA Standard of Installation, unless otherwise specified.
D.
E.
Do not cut or notch any structural member or building surface without specific approval of
Engineer.
F.
Handle, install, connect, clean, condition, and adjust products in accordance with
Manufacturers instructions, and as may be specified. Retain a copy of Manufacturers
instruction at Site, available for review at all times.
G.
For material and equipment specifically indicated or specified to be reused in the Work:
1.
Use special care in removal, handling, storage, and reinstallation to assure proper
function in the completed Work.
2.
Arrange for transportation, storage, and handling of products that require offsite storage,
restoration, or renovation. Include costs for such Work in the Contract Price.
Section 01 60 00
Product Requirements
3.3
FIELD FINISHING
A.
3.4
In accordance with Section 09 90 00, PAINTING AND PROTECTIVE COATINGS and individual
Specification sections.
ADJUSTMENT AND CLEANING
A.
3.5
Perform required adjustments, tests, operation checks, and other startup activities.
LUBRICANTS
A.
Fill lubricant reservoirs and replace consumption during testing, startup, and operation prior to
acceptance of equipment by Owner.
END OF SECTION
Section 01 60 00
Product Requirements
SUMMARY
A.
Section includes description and requirements of the required closeout procedures for the
project:
1.
Providing and delivering informational submittals.
2.
Preparing, maintaining, providing and delivering Record Documents.
3.
Furnishing Releases from Agreements.
4.
Furnishing Evidence of Compliance with Requirements of Governing Authorities.
5.
Providing Warranties and Bonds.
6.
Providing Certificate of Final Completion.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 77 00 Closeout Procedures.
1.2
QUALITY ASSURANCE
A.
Qualifications of Surveyor or Engineer: Registered civil engineer or land surveyor in state where
Project is located.
B.
1.3
Execute the Work in accordance with the lines and grades indicated.
B.
Make distances and measurements on horizontal planes, except elevations and structural
dimensions.
1.4
Basic reference line, a beginning point on basic reference line, and a benchmark will be
provided, by OWNER.
B.
From these reference points, establish other control and reference points as required to
properly lay out the Work.
Section 01 72 20
Field Engineering
C.
Locate and protect control points prior to starting site work, and preserve permanent reference
points during construction:
1.
Make no changes or relocations without prior written notice.
2.
Replace Project control point, when lost or destroyed, in accordance with original survey
control.
D.
Set monuments for principal control points and protect them from being disturbed and
displaced;
1.
Re-establish disturbed monuments.
2.
When disturbed, postpone parts of the Work that are governed by disturbed monuments
until such monuments are re-established.
1.5
B.
Record permanent benchmark locations with horizontal and vertical data on Project Record
Documents.
C.
1.6
RECORD DOCUMENTS
A.
B.
C.
Affix civil engineers or land surveyors signature and registration number to Record Drawing to
certify accuracy of information shown.
END OF SECTION
Section 01 72 20
Field Engineering
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 01 60 00 Product Requirements.
1.2
SUBMITTALS
A.
B.
PART 2 - PRODUCTS
2.1
MATERIALS
A.
PART 3 - EXECUTION
3.1
PREPARATION
A.
B.
Provide devices and methods to protect other portions of Project from damage and persons
from injury.
Section 01 73 20
Cutting and Patching
C.
3.2
Provide protection from elements for that portion of Project which may be exposed by cutting
and patching, and maintain excavations free from water.
CUTTING AND PATCHING
A.
B.
Execute cutting and demolition by methods which will prevent damage and will provide proper
surfaces to receive installation of repairs.
C.
D.
E.
F.
G.
Rehabilitate all areas affected by removal of existing equipment, equipment pads and bases,
piping, supports, electrical panels, electric devices, and conduits such that little or no evidence
of the previous installation remains:
1.
Fill areas in existing floors, walls, and ceilings from removed piping, conduit and
fasteners with non-shrink grout and finish smooth.
2.
Remove Concrete Bases for Equipment and Supports by:
a.
Saw cutting clean, straight lines with a depth equal to the concrete cover over
reinforcement minus 1/2 inch below finished surface. Do not cut existing
reinforcement on floors.
b.
Chip concrete within scored lines and cut exposed reinforcing steel and anchor
bolts.
c.
Patch with non-shrink grout to match adjacent grade and finish.
3.
Terminate abandoned piping and conduits with blind flanges, caps, or plugs.
Section 01 73 20
Cutting and Patching
H.
END OF SECTION
Section 01 73 20
Cutting and Patching
SUMMARY
A.
1.2
A.
B.
C.
Project Record Documents: Include locations of service lines and capped utilities.
1.3
REGULATORY REQUIREMENTS
A.
B.
C.
Obtain permits for building demolition, transportation of debris to disposal site and dust control.
1.4
PREPARATION
A.
1.5
Obtain permission from adjacent property OWNERs when outriggers, swinging cranes, and
other equipment may have to traverse adjacent property.
ENVIRONMENTAL REQUIREMENTS
A.
Do not interfere with use of adjacent buildings. Maintain free and safe passage to and from all
areas.
B.
C.
Cease operations and notify ENGINEER immediately when safety of structure appears to be
endangered. Take precautions to properly support structure. Do not resume operations until
safety is restored.
D.
Provide erect and maintain barricades, lighting, guardrails, and protective devices as required to
protect building occupants, general public, workers, and adjoining property.
Section 01 73 80
Selective Demolition
1.6
EXISTING SERVICES
A.
Arrange and pay for capping and plugging utility services. Disconnect and stub off. Notify
affected utility company in advance and obtain approval before starting demolition.
B.
1.7
MAINTAINING TRAFFIC
A.
B.
1.8
MATERIALS
A.
cornerstones,
cornerstone
contents,
B.
C.
CONTRACTOR shall furnish all materials, tools. Equipment, devices, appurtenances, facilities,
and services required for performing selective demolition work on:
1.
Existing Surge Tower.
2.
Existing Intake Pump Station.
D.
E.
Erect and maintain dustproof partitions as required to prevent spread of dust, fumes and smoke
to other parts of building. On completion, remove partitions and repair damaged surfaces to
match adjacent surfaces.
F.
G.
Provide and maintain protective devices to prevent injury from falling objects.
H.
Locate guardrails in stairwells and around open shafts to protect workers. Post clearly visible
warning signs.
I.
Cause as little inconvenience to ongoing plant operations and to adjacent occupied building
areas as possible.
J.
K.
1.9
DEMOLITION
A.
Demolish designated portions of structures and appurtenances in orderly and careful manner.
Section 01 73 80
Selective Demolition
B.
C.
Prevent airborne dust. Use water or dust palliative when necessary. Provide and maintain
hoses and connections to water main or hydrant.
D.
E.
F.
G.
Remove trees and shrubs within marked areas, clear undergrowth and dead plant material as
specified in Division 02.
H.
Backfill open pits and holes caused by demolition as specified in Division 02.
I.
J.
1.10
A.
REPAIR
Repair damage caused by demolition. The contractor shall take appropriate precautions to
protect existing treatment facilities, structures, piping, mechanical equipment, and electrical
equipment, which are to remain in service during the course of construction. In the event of
damage, the contractor shall make the necessary repairs to place the facilities back in service at
no increase in the contract price. Such repairs shall be made to the satisfaction of the OWNER.
END OF SECTION
Section 01 73 80
Selective Demolition
SUMMARY
A.
Section Includes: Requirements for equipment and system testing and facility start up, including
the following:
1.
Start-Up Plan.
2.
Performance Testing.
3.
General Start-Up and Testing Procedures.
4.
Functional Testing.
5.
Operational Testing.
6.
Certificate of Proper Installation.
7.
Services of manufacturers representatives.
8.
Training of OWNERs personnel.
9.
Final testing requirements for the complete facility.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 23 05 93 HVAC Systems Testing, Adjusting and Balancing.
b.
Section 26 05 00 Common Work Results For Electrical.
1.2
Contract Requirements: Testing, training, and start-up are requisite to the satisfactory
completion of the Contract.
B.
C.
Allow realistic durations in the Progress Schedule for testing, training, and start-up activities.
D.
Furnish labor, power, chemicals, tools, equipment, instruments, and services required for and
incidental to completing functional testing, performance testing, and operational testing.
E.
1.3
START-UP PLAN
A.
Submit start-up plan for each piece of equipment and each system not less than 3 weeks prior
to planned initial start-up of equipment or system.
B.
Provide detailed sub-network of Progress Schedule with the following activities identified:
1.
Manufacturers services.
2.
Installation certifications.
3.
Operator training.
Section 01 75 60
Testing, Training, and Facility Start-Up
4.
5.
6.
7.
C.
Provide testing plan with test logs for each item of equipment and each system when specified.
Include testing of alarms, control circuits, capacities, speeds, flows, pressures, vibrations, sound
levels, and other parameters.
D.
Provide summary of shutdown requirements for existing systems which are necessary to
complete start-up of new equipment and systems.
E.
Revise and update start-up plan based upon review comments, actual progress, or to
accommodate changes in the sequence of activities.
1.4
PERFORMANCE TESTING
A.
Test equipment for proper performance at point of manufacture or assembly when specified.
B.
1.5
B.
Section 01 75 60
Testing, Training, and Facility Start-Up
4.
5.
C.
1.6
Perform direct current high potential tests on all cables that will operate at more than
2,000 volts. Obtain services of independent testing lab to perform tests.
Check motors for actual full load amperage draw. Compare to nameplate value.
A.
Perform checkout and performance testing as specified in the individual equipment specification
sections.
B.
Functionally test mechanical and electrical equipment, and instrumentation and controls
systems for proper operation after general start-up and testing tasks have been completed.
C.
Demonstrate proper rotation, alignment, speed, flow, pressure, vibration, sound level,
adjustments, and calibration. Perform initial checks in the presence of and with the assistance
of the manufacturers representative.
D.
Demonstrate proper operation of each instrument loop function including alarms, local and
remote controls, instrumentation and other equipment functions. Generate signals with test
equipment to simulate operating conditions in each control mode.
E.
Conduct continuous 8-hour test under full load conditions. Replace parts which operate
improperly.
1.7
OPERATIONAL TESTING
A.
After completion of operator training, conduct operational test of the entire facility. Demonstrate
satisfactory operation of equipment and systems in actual operation.
B.
C.
OWNER will provide operations personnel, power, fuel, and other consumables for duration of
each specified test.
D.
E.
Repeat operational test when malfunctions or deficiencies cause shutdown or partial operation
of the facility or results in performance that is less than specified.
1.8
Section 01 75 60
Testing, Training, and Facility Start-Up
5.
6.
B.
1.9
Controls, protective devices, instrumentation, and control panels furnished as part of the
equipment package are properly installed, calibrated, and functioning.
Control logic for start-up, shutdown, sequencing, interlocks, and emergency shutdown
have been tested and are properly functioning.
Furnish written report prepared and signed by the electrical and/or instrumentation
subcontractor certifying:
1.
Motor control logic that resides in motor control centers, control panels, and circuit boards
furnished by the electrical and/or instrumentation subcontractor has been calibrated and
tested and is properly operating.
2.
Control logic for equipment start-up, shutdown, sequencing, interlocks and emergency
shutdown has been tested and is properly operating.
3.
Co-sign the reports along with the manufacturers representative and subcontractors.
TRAINING OF OWNERS PERSONNEL
A.
Provide operations and maintenance training for items of mechanical, electrical and
instrumentation equipment. Utilize manufacturers representatives to conduct training sessions.
B.
C.
Provide Operation and Maintenance Manual for specific pieces of equipment or systems 1
month prior to training session for that piece of equipment or system.
D.
E.
Training Sessions: Provide training sessions for equipment as specified in the individual
equipment specification sections.
F.
The CONTRACTOR shall videotape all training sessions and provide a copy for the OWNER.
G.
The CONTRACTOR shall designate and provide one or more persons to be responsible for
coordinating and expediting his/her training duties. The person or persons so designated shall
be present at all training coordination meetings with the OWNER.
H.
The CONTRACTORs coordinator shall coordinate the training periods with OWNER personnel
and manufacturers representatives, and shall submit a training schedule for each piece of
equipment or system for which training is to be provided. Such training schedule shall be
submitted not less than 21 calendar days prior to the time that the associated training is to be
provided and shall be based on the current plan of operation.
1.10
A.
RECORD KEEPING
Maintain and submit following records generated during start-up and testing phase of Project:
1.
Daily logs of equipment testing identifying all tests conducted and outcome.
2.
Logs of time spent by manufacturers representatives performing services on the job site.
3.
Equipment lubrication records.
4.
Electrical phase, voltage, and amperage measurements.
5.
Insulation resistance measurements.
6.
Data sheets of control loop testing including testing and calibration of instrumentation
devices and setpoints.
Section 01 75 60
Testing, Training, and Facility Start-Up
END OF SECTION
Section 01 75 60
Testing, Training, and Facility Start-Up
SUMMARY
A.
Section includes description and requirements of the required closeout procedures for the
project:
1.
Providing and delivering informational submittals.
2.
Preparing, maintaining, providing and delivering Record Documents.
3.
Furnishing Releases from Agreements.
4.
Furnishing Evidence of Compliance with Requirements of Governing Authorities.
5.
Providing Warranties and Bonds.
6.
Providing Certificate of Final Completion.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
01 72 20 Field Engineering.
b.
01 78 23 Operation and Maintenance Data.
c.
01 79 00 Demonstration and Training.
1.2
SUBMITTALS
A.
Informational Submittals:
1.
Submit Prior to Application for Final Payment.
a.
Record Documents: As required in General Conditions.
b.
Approved Shop Drawings and Samples: As required in the General Conditions.
c.
Operations and Maintenance Manuals: In accordance with Section 01 78 23, and
as required in individual Specification sections.
d.
Certificates of Testing and Inspection: As required in the General Conditions, these
General Requirements sections, and the individual Specifications sections.
e.
Training Sessions: In accordance with Section 01 79 00, and individual
Specifications sections.
f.
Certificate of Substantial Completion.
g.
Special bonds, Special Guarantees, and Service Agreements.
2.
Form of Submittal:
a.
Bind in commercial quality 8-1/2 by 11 three ring, side binders with hardback,
cleanable, plastic covers.
Section 01 77 00
Closeout Procedures
3.
4.
1.3
1). Label cover of each binder with typed or printed title Warranties and Bonds,
with title of Project; name; address, and telephone number of Contractor and
equipment Supplier, and name of responsible principal.
2). Table of Contents: Neatly typed, in the sequence of the of the Project Manual,
with each item identified with the number and title of the Specification section
in which specified, and the name of the product or Work item.
3). Separate each warranty or Bond with index tab sheets keyed to the Table of
Contents. Provide full information, using separate typed sheets as necessary.
List Subcontractor, Supplier, and Manufacturer, with name, address, and telephone number of responsible contact for service and warranty issues.
Preparation of Submittal:
a.
Obtain notarized warranties and Bonds, executed in duplicate by responsible
Subcontractor, Supplier, and Manufacturer, within 10 days after completion of the
applicable item or Work, except for items put into use with Owners permission,
leave date of beginning of time warranty until date of Substantial Completion is
determined.
Time of Submission: Submit within 10 days after the date of Date of Substantial
Completion and prior to submission of Final Application of Payment.
a.
Spare parts and special tools as required by individual Specification sections.
b.
Consent of Surety to Final Payment: As required in General Conditions.
c.
Releases or Waivers of Liens and Claims: As required in General Conditions.
d.
Releases from Agreements.
e.
Final Application for Payment: Submit in accordance with procedures and
requirements stated in Section 01 29 00.
f.
Extra Materials: As required by individual Specification sections.
RECORD DOCUMENTS
A.
1.4
Quality Assurance:
1.
Furnish qualified and experienced person, whose duty and responsibility shall be to
maintain record documents.
2.
Accuracy of Records:
3.
Coordinate changes within record documents, making legible and accurate entries on
each sheet of Drawings and other documents where such entry is required to show
change.
4.
Purpose of Project record documents is to document factual information regarding
aspects of the Work, both concealed and visible, to enable future modification of the
Work to proceed without lengthy and expensive Site measurement, investigation, and
examination.
5.
Make entries within 24 hours after receipt of information that a change in the Work has
occurred.
6.
Prior to submitting each request for progress payment, request Engineers review and
approval of current status of record documents. Failure to properly maintain, update, and
submit record documents may result in a deferral by Engineer to recommend whole or
any part of Contractors Application for Payment, either partial or final.
7.
Maintain at Project site, available to OWNER and ENGINEER, 1 copy of the Contract
Documents, shop drawings and other submittals, in good order.
RELEASES FROM AGREEMENTS
A.
Furnish Owner written releases from property owners or public agencies where side
agreements or special easements have been made, or where Contractors operations have not
been kept within the Owners construction right-of-way.
B.
Section 01 77 00
Closeout Procedures
2.
3.
4.
5.
6.
1.5
Owner or its representatives will examine the Site, and Owner will direct Contractor to
complete the Work that may be necessary to satisfy terms of the side agreement or
special easement.
Should Contractor refuse to perform this Work, Owner reserves right to have it done by
separate contract and deduct cost of same from Contract Price, or require Contractor to
furnish a satisfactory bond in a sum to cover legal Claims for damages.
When Owner is satisfied that the Work has been completed in agreement with Contract
Documents and terms of side agreement or special easement, right is reserved to waive
requirement for written release if:
Contractors failure to obtain such statement is due to grantors refusal to sign, and this
refusal is not based upon any legitimate Claims that Contractor has failed to fulfill terms
of side agreement or special easement, or
Contractor is unable to contact or has had undue hardship in contacting grantor.
1.6
A.
B.
Provide specified additional warranties, guarantees, and bonds from manufacturers and
suppliers.
1.7
When 7-day operational test has been successfully completed, ENGINEER will certify that new
facilities are operationally complete. ENGINEER will submit a list of known items (punch list) still
to be completed or corrected prior to contract completion.
B.
C.
When all items have been completed or corrected, submit written certification that the entire
work is complete in accordance with the Contract Documents and request final inspection.
D.
Upon completion of final inspection, ENGINEER will either prepare a written acceptance of the
entire work or advise CONTRACTOR of work not complete. If necessary, inspection procedures
will be repeated.
General:
1.
Promptly following commencement of Contract Times, secure from Engineer at no cost to
Contractor, one complete set of Contract Documents. Drawings will be full size.
Section 01 77 00
Closeout Procedures
2.
3.
Label or stamp each record document with title, RECORD DOCUMENTS, in neat large
printed letters.
Record information concurrently with construction progress and within 24 hours after
receipt of information that change has occurred. Do not cover or conceal Work until
required information is recorded.
B.
Preservation:
1.
Maintain documents in a clean, dry, legible condition and in good order. Do not use
record documents for construction purposes.
2.
Make documents and Samples available at all times for observation by Engineer.
C.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
Additions:
Red
Deletions:
Green
Comments
Blue
Dimensions:
Graphite
Date entries.
Call attention to entry by cloud drawn around area or areas affected.
Legibly mark to record actual changes made during construction, including, but not
limited to:
Depths of various elements of foundation in relation to finished first floor data if not shown
or where depth differs from that shown.
Horizontal and vertical locations of existing and new Underground Facilities and
appurtenances, and other underground structures, equipment, or Work, and Reference to
at least two measurements to permanent surface improvements.
Location of internal utilities and appurtenances concealed in the construction referenced
to visible and accessible features of the structure.
Locate existing facilities, piping, equipment, and items critical to the interface between
existing physical conditions or construction and new construction.
Changes made by Addenda and Field Orders, Work Change Directive, Change Order,
and Engineers written interpretation and clarification using consistent symbols for each
and showing appropriate document tracking number.
Dimensions on Schematic Layouts: Show on record drawings, by dimension, the
centerline of each run of items that are described in previous subparagraph above.
Clearly identify the item by accurate note such as cast iron drain, galv. water, and the
like.
Show, by symbol or note, vertical location of item (under slab, in ceiling plenum,
exposed, and the like).
Make identification so descriptive that it may be related reliably to Specifications.
Mark and record field changes and detailed information contained in submittals and
change orders.
Record actual depths, horizontal and vertical location of underground pipes, duct banks
and other buried utilities. Reference dimensions to permanent surface features.
Identify specific details of pipe connections, location of existing buried features located
during excavation, and the final locations of piping, equipment, electrical conduits,
manholes, and pull boxes.
Identify location of spare conduits including beginning, ending and routing through pull
boxes, and manholes. Record spare conductors, including number and size, within spare
conduits, and filled conduits.
Section 01 77 00
Closeout Procedures
18.
D.
E.
F.
Deliver record documents with transmittal letter containing date, Project title, CONTRACTORs
name and address, list of documents, and signature of CONTRACTOR.
G.
During progress meetings, record documents will be reviewed to ascertain that changes have
been recorded.
H.
3.2
FINAL CLEANING
A.
At completion of the Work or of a part thereof and immediately prior to Contractors request for
certificate of Substantial Completion; or if no certificate is issued, immediately prior to
Contractors notice of completion, clean entire Site or parts thereof, as applicable.
1.
Leave the Work and adjacent areas affected in a cleaned condition satisfactory to Owner.
2.
Remove grease, dirt, dust, paint or plaster splatter, stains, labels, fingerprints, and other
foreign materials from exposed surfaces.
3.
Repair, patch, and touch up marred surfaces to specified finish and match adjacent
surfaces.
4.
Clean all windows.
5.
Clean and wax wood, vinyl, or painted floors.
6.
Broom clean exterior paved driveways and parking areas.
7.
Hose clean sidewalks, loading areas, and others contiguous with principal structures.
8.
Rake and clean all other surfaces.
9.
Remove snow and ice from access to buildings.
10.
Replace air-handling filters and clean ducts, blowers, and coils of ventilation units
operated during construction.
11.
Leave water courses, gutters, and ditches open and clean.
12.
Perform final cleaning prior to inspections for Final Acceptance.
13.
Employ skilled workers who are experienced in cleaning operations.
14.
Use cleaning materials which are recommended by manufacturers of surfaces to be
cleaned.
15.
Prevent scratching, discoloring, and otherwise damaging surfaces being cleaned.
16.
Clean roofs, gutters, downspouts, and drainage systems.
17.
Broom clean exterior paved surfaces and rake clean other surfaces of site work:
a.
Police yards and grounds to keep clean.
18.
Remove dust, cobwebs, and traces of insects and dirt.
19.
Clean grease, mastic, adhesives, dust, dirt, stains, fingerprints, paint, blemishes,
sealants, plaster, concrete, and other foreign materials from sight-exposed surfaces, and
fixtures and equipment.
20.
Remove non-permanent protection and labels.
21.
Polish waxed woodwork and finish hardware.
22.
Wash tile.
23.
Wax and buff hard floors, as applicable.
24.
Wash and polish glass, inside and outside.
25.
Wash and shine mirrors.
26.
Polish glossy surfaces to clear shine.
27.
Vacuum carpeted and soft surfaces.
Section 01 77 00
Closeout Procedures
28.
29.
30.
B.
3.3
Clean permanent filters and replace disposable filters when heating, ventilation, and air
conditioning units were operated during construction.
Clean ducts, blowers and coils when units were operated without filters during
construction.
Clean light fixtures and replace burned-out or dim lamps.
A.
Arrange for and dispose of surplus materials, waste products, and debris off-site:
1.
Prior to making disposal on private property, obtain written permission from OWNER of
such property.
B.
Do not fill ditches, washes, or drainage ways which may create drainage problems.
C.
D.
E.
3.4
Touch-up or repair finished surfaces on structures, equipment, fixtures, and installations that
have been damaged prior to inspection for Final Acceptance.
B.
3.5
Clean channels, pipe, basins, reservoirs, and tanks before running of 7-day test, or before
facility goes on stream when 7-day test is not required.
B.
Wash, wherever practicable, or broom sweep channels, pipe, basins, reservoirs, and tanks.
C.
Disinfect piping intended to carry potable water as follows or in accordance with American
Water Works Association Standards.
D.
E.
Fill pipe with chlorine solution of sufficient strength to retain residual of not less than 10 parts
per million at end of 24 hours.
F.
After disinfection, rinse entire potable water system with potable water sufficient to reduce
chlorine residual to not more than 0.6 parts per million throughout system before system is put
into service.
3.6
B.
When pipe contains dirt that cannot be removed by flushing, swab pipe interiors with solution
containing not less than 500 parts per million of chlorine until clean.
Section 01 77 00
Closeout Procedures
C.
Flush 12 inch in diameter and smaller pipe as thoroughly as available water sources will permit.
D.
Fill pipe with chlorine solution of sufficient strength to provide 10 parts per million chlorine
residual at end of 24 hours.
E.
Flush pipes with potable water until chlorine residual is less than 0.6 parts per million before
pipe are put into service.
3.7
CLOSEOUT DOCUMENTS
A.
Submit following Closeout Submittals upon completion of the Work and at least 7 days prior to
submitting Application for Final Payment:
1.
Evidence of Compliance with Requirements of Governing Authorities.
2.
Project Record Documents.
3.
Operation and Maintenance Manuals.
4.
Warranties and Bonds.
5.
Keys and Keying Schedule.
6.
Evidence of Payment and Release of Stop Payment Notices as outlined in Conditions of
the Contract.
7.
Release of claims as outlined in Conditions of the Contract.
8.
Survey Record Documents as specified in Section 01 72 20.
9.
Certificate of Final Completion.
END OF SECTION
Section 01 77 00
Closeout Procedures
SUMMARY
A.
Section includes:
1.
Detailed information for the preparation, submission, and Engineers review of Operations
and Maintenance (O&M) Data, as required by individual Specification sections.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 77 00 Closeout Procedures.
1.2
DEFINITIONS
A.
B.
C.
1.3
B.
1.4
DATA FORMAT
A.
Prepare preliminary data in the form of an instructional manual. Prepare final data in the form of
an instructional manual and in electronic media format.
B.
Section 01 78 23
Operation and Maintenance Data
1.
2.
3.
4.
5.
6.
7.
8.
9.
C.
1.5
A.
Informational:
1.
Data Outline: Submit four copies of a detailed outline of proposed organization and
contents of Final Data prior to preparation of Preliminary Data.
2.
Preliminary Data:
a.
Submit three copies for Engineers review.
b.
If data meets conditions of the Contract:
1). One copy will be returned to Contractor.
2). One copy will be forwarded to Resident Project Representative.
3). One copy will be retained in Engineers file
c.
If data does not meet conditions of the Contract:
1). Two copies will be returned to Contractor with Engineers comments (on separate document) for revision.
2). Engineers comments will be retained in Engineers file.
3). One copy will be retained in Engineers file.
4). Re-submit three copies revised in accordance with Engineers comments.
3.
Final Data: Submit three copies in each format specified herein.
Section 01 78 23
Operation and Maintenance Data
1.6
B.
Section 01 78 23
Operation and Maintenance Data
1.
2.
3.
4.
5.
6.
7.
8.
9.
C.
1.7
Maintenance Summary:
1.
Compile individual Maintenance Summary for each applicable equipment item, respective
unit or system, and for components or sub-units.
2.
Format: Use only 8-1/2 x 11 size paper.
3.
Include detailed lubrication instructions and diagrams showing points to be greased or
oiled; recommend type, grade, and temperature range of lubricants and frequency of
lubrication.
4.
Recommended Spare Parts:
a.
Data to be consistent with Manufacturers Bill of Materials/Parts List furnished in
O&M manuals.
b.
Unit is the unit of measure for ordering the part.
c.
Quantity is the number of units recommended.
d.
Unit Cost is the current purchase price.
DATA FOR MATERIALS AND FINISHES
A.
Section 01 78 23
Operation and Maintenance Data
5.
END OF SECTION
Section 01 78 23
Operation and Maintenance Data
SUMMARY
A.
Section includes description and requirements of the required demonstration and training for the
project:
1.
Providing and delivering informational submittals.
2.
Submitting required qualifications of Manufacturer Representative.
3.
Preparing, maintaining, providing and delivering Manufacturers Certificate of Compliance
and Manufacturers Certificate of Proper Installation.
4.
Furnishing required Training.
5.
Furnishing required Equipment Testing, Unit Processes and Facility Performance
Demonstration.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 31 19 Project Meetings.
b.
Section 01 78 23 Operation and Maintenance Data.
c.
Section 01 79 00 Demonstration and Training.
1.2
DEFINITIONS
A.
Person-Day: One person for 8 hours within regular Contractor working hours.
B.
C.
Functional Test: Test or tests in presence of Engineer and Owner to demonstrate that installed
equipment meets Manufacturers installation, calibration, and adjustment requirements and
other requirements as specified.
D.
Performance Test: Test or tests performed after any required functional test in presence of
Engineer and Owner to demonstrate and confirm individual equipment meets performance
requirements specified in individual sections.
E.
Unit Process: As used in this Section, a unit process is a portion of the facility that performs a
specific process function, such as, but limited to:
1.
Pump Station
2.
Disinfection Station
F.
Section 01 79 00
Demonstration and Training
a.
b.
1.3
SUBMITTALS
A.
1.4
Informational Submittals:
1.
Training Schedule: Submit not less than 21 days prior to start of equipment installation
and revise as necessary for acceptance.
2.
Lesson Plan: Submit proposed lesson plan not less than 21 days prior to scheduled
training and revise as necessary for acceptance.
3.
Training Session Tapes: Furnish Owner with two complete sets of tapes fully indexed and
cataloged with printed label stating session and date taped.
4.
Facility Startup and Performance Demonstration Plan.
5.
Functional and performance test results.
6.
Completed Unit Process Startup Form for each unit process.
7.
Completed Facility Performance Demonstration/Certification Form.
QUALIFICATION OF MANUFACTURERS REPRESENTATIVE
A.
Authorized representative of the Manufacturer, factory trained, and experienced in the technical
applications, installation, operation, and maintenance of respective equipment, subsystem, or
system, with full authority by the equipment Manufacturer to issue the certifications required of
the Manufacturer. Additional qualifications may be specified elsewhere.
B.
1.5
Develop a written plan, in conjunction with Owners operations personnel; to include the
following:
1.
Step-by-step instructions for startup of each unit process and the complete facility.
2.
Unit Process Startup Form (sample attached), to minimally include the following:
a.
Description of the unit process, including equipment numbers/nomenclature of
each item of equipment and all included devices.
b.
Detailed procedure for startup of the unit process, including valves to be
opened/closed, order of equipment startup, etc.
c.
Startup requirements for each unit process, including water, power, chemicals, etc.
d.
Space for evaluation comments.
3.
Facility Performance Demonstration/Certification Form (sample attached), to minimally
include the following:
a.
Description of unit processes included in the facility startup.
b.
Sequence of unit process startup to achieve facility startup.
c.
Description of computerized operations, if any, included in the facility.
d.
Contractor certification facility is capable of performing its intended function(s),
including fully automatic operation.
e.
Signature spaces for Contractor and Engineer.
Section 01 79 00
Demonstration and Training
GENERAL
A.
B.
Where time is necessary in excess of that stated in the Specifications for Manufacturers
services, or when a minimum time is not specified, the time required to perform the specified
services shall be considered incidental.
C.
Schedule Manufacturers services to avoid conflict with other onsite testing or other
Manufacturers onsite services.
D.
Determine, before scheduling services, that all conditions necessary to allow successful testing
have been met.
E.
Only those days of service approved by Engineer will be credited to fulfill the specified minimum
services.
F.
When specified in individual specification sections, Manufacturers onsite services shall include:
1.
Assistance during product (system, subsystem, or component) installation to include
observation, guidance, instruction of Contractors assembly, erection, installation or
application procedures.
2.
Inspection, checking, and adjustment as required for product (system, subsystem, or
component) to function as warranted by Manufacturer and necessary to furnish
Manufacturers Certificate of Proper Installation.
3.
Providing, on a daily basis, copies of all Manufacturers representatives field notes and
data to Engineer.
4.
Revisiting the Site as required to correct problems and until installation and operation are
acceptable to Engineer.
5.
Resolution of assembly or installation problems attributable to or associated with,
respective Manufacturers products and systems.
6.
Assistance during functional and performance testing, and facility startup and evaluation.
7.
Training of Owners personnel in the operation and maintenance of respective product as
required.
8.
Additional requirements may be specified elsewhere.
G.
H.
I.
Provide temporary valves, gauges, piping, test equipment and other materials and equipment
required for testing and startup.
J.
Provide Subcontractor and equipment Manufacturers with adequate staff to prevent delays.
Schedule ongoing work so as not to interfere with or delay testing and startup.
Section 01 79 00
Demonstration and Training
K.
3.2
Owner will:
1.
Provide water, power, chemicals, and other items as required for startup, unless
otherwise indicated.
2.
Operate process units and facility with support of Contractor.
3.
Provide labor and materials as required for laboratory analyses.
MANUFACTURERS CERTIFICATE OF COMPLIANCE
A.
B.
Engineer may permit use of certain materials or assemblies prior to sampling and testing if
accompanied by accepted certification of compliance.
C.
D.
May reflect recent or previous test results on material or product, if acceptable to Engineer.
3.3
B.
Such form shall certify that the signing party is a duly authorized representative of the
Manufacturer, is empowered by the Manufacturer to inspect, approve, and operate their
equipment and is authorized to make recommendations required to assure that the equipment
is complete and operational.
3.4
TRAINING
A.
General:
1.
Furnish Manufacturers representatives for detailed classroom and hands-on training to
Owners personnel on operation and maintenance of specified product (system,
subsystem, component) and as may be required in applicable Specifications.
2.
Furnish trained, articulate personnel to coordinate and expedite training, to be present
during training coordination meetings with Owner, and familiar with operation and
maintenance manual information specified in Section 01 78 23, OPERATION AND
MAINTENANCE DATA.
3.
Manufacturers representative shall be familiar with facility operation and maintenance
requirements as well as with specified equipment.
4.
Furnish complete training materials, to include operation and maintenance data, to be
retained by each trainee.
B.
Training Schedule:
1.
List specified equipment and systems that require training services and show:
a.
Respective Manufacturer.
b.
Estimated dates for installation completion.
c.
Estimated training dates.
2.
Allow for multiple sessions when several shifts are involved.
3.
Adjust schedule to ensure training of appropriate personnel as deemed necessary by
Owner, and to allow full participation by Manufacturers representatives. Adjust schedule
for interruptions in operability of equipment.
Section 01 79 00
Demonstration and Training
4.
C.
Lesson Plan: When Manufacturer or vendor training of Owner personnel is specified, prepare
for each required course, containing the following minimum information:
1.
Title and objectives.
2.
Recommended types of attendees (e.g., managers, engineers, operators, maintenance).
3.
Course description and outline of course content.
4.
Format (e.g., lecture, self-study, demonstration, hands-on).
5.
Instruction materials and equipment requirements.
6.
Resumes of instructors providing the training.
D.
Pre-startup Training:
1.
Coordinate training sessions with Owners operating personnel and Manufacturers
representatives, and with submission of operation and maintenance manuals in
accordance with Section 01 78 23, OPERATIONS AND MAINTENANCE DATA.
2.
Complete at least 14 days prior to beginning of facility startup.
E.
F.
3.5
EQUIPMENT TESTING
A.
Preparation:
1.
Complete installation before testing.
2.
Furnish qualified Manufacturers representatives, when required by individual
Specification sections.
3.
Obtain and submit from equipment Manufacturers representative Manufacturers
Certificate of Proper Installation Form, in accordance with Section 01 75 60, TESTING,
TRAINING, AND FACILITY START-UP, when required by individual Specification
sections.
4.
Equipment Test Report Form: Provide written test report for each item of equipment to be
tested, to include the minimum information:
a.
Owner/Project Name.
b.
Equipment or item tested.
c.
Date and time of test.
d.
Type of test performed (Functional or Performance).
e.
Test method.
f.
Test conditions.
g.
Test results.
h.
Signature spaces for Contractor and Engineer as witness.
5.
Cleaning and Checking: Prior to beginning functional testing:
a.
Calibrate testing equipment in accordance with Manufacturers instructions.
b.
Inspect and clean equipment, devices, connected piping, and structures to ensure
they are free of foreign material.
c.
Lubricate equipment in accordance with Manufacturers instructions.
d.
Turn rotating equipment by hand when possible to confirm that equipment is not
bound.
Section 01 79 00
Demonstration and Training
e.
6.
Open and close valves by hand and operate other devices to check for binding,
interference, or improper functioning.
f.
Check power supply to electric-powered equipment for correct voltage.
g.
Adjust clearances and torque.
h.
Test piping for leaks.
Ready-to-test determination will be by Engineer-based at least on the following:
a.
Acceptable Operation and Maintenance Data.
b.
Notification by Contractor of equipment readiness for testing.
c.
Receipt of Manufacturers Certificate of Proper Installation, if so specified.
d.
Adequate completion of work adjacent to, or interfacing with, equipment to be
tested.
e.
Availability and acceptability of Manufacturers representative, when specified, to
assist in testing of respective equipment.
f.
Satisfactory fulfillment of other specified Manufacturers responsibilities.
g.
Equipment and electrical tagging complete.
h.
Delivery of all spare parts and special tools.
B.
Functional Testing:
1.
Conduct as specified in individual Specification sections.
2.
Notify Owner and Engineer in writing at least 10 days prior to scheduled date of testing.
3.
Prepare Equipment Test Report summarizing test method and results.
4.
When in Engineers opinion, equipment meets functional requirements specified such
equipment will be accepted for purposes of advancing to performance testing phase, if so
required by individual Specification sections. Such acceptance will be evidenced by
Engineer/Owners signature as witness on Equipment Test Report.
C.
Performance Testing:
1.
Conduct as specified in individual Specification sections.
2.
Notify Engineer and Owner in writing at least 10 days prior to scheduled date of test.
3.
Performance testing shall not commence until equipment has been accepted by Engineer
as having satisfied functional test requirements specified.
4.
Type of fluid, gas, or solid for testing shall be as specified.
5.
Unless otherwise indicated, furnish labor, materials, and supplies for conducting the test
and taking samples and performance measurements.
6.
Prepare Equipment Test Report summarizing test method and results.
7.
When, in Engineers opinion, equipment meets performance requirements specified, such
equipment will be accepted as to conforming to Contract requirements. Such acceptance
will be evidenced by Engineers signature on Equipment Test Report.
3.6
Prior to unit process startup, equipment within unit process shall be accepted by Engineer as
having met functional and performance testing requirements specified.
B.
C.
Make adjustments, repairs, and corrections necessary to complete unit process startup.
D.
Startup shall be considered complete when, in opinion of Engineer, unit process as operated in
manner intended for 5 continuous days without significant interruption. This period is in addition
to functional or performance test periods specified elsewhere.
E.
Section 01 79 00
Demonstration and Training
2.
3.
4.
5.
F.
3.7
Failure to meet specified functional operation for more than 2 consecutive hours.
Failure of any critical equipment or unit process that is not satisfactorily corrected within 5
hours after failure.
Failure of any non-critical equipment or unit process that is not satisfactorily corrected
within 8 hours after failure.
As determined by Engineer.
A significant interruption will require startup then in progress to be stopped. After corrections are
made; start up test period and start from beginning again.
FACILITY PERFORMANCE DEMONSTRATION
A.
When, in the opinion of Engineer, startup of all unit processes has been achieved, sequence
each unit process to the point that facility is operational.
B.
Demonstrate proper operation of required interfaces within and between individual unit
processes.
C.
After facility is operating, complete performance testing of equipment and systems not
previously tested.
D.
E.
3.8
SUPPLEMENTS
A.
Supplements listed below, following End of Section, are a part of this Specification:
1.
Manufacturers Certificate of Proper Installation Form.
2.
Unit Process Startup Form.
3.
Facility Performance Demonstration/Certification Form.
END OF SECTION
Section 01 79 00
Demonstration and Training
EQUIP. SYSTEM:
PROJECT NO:
SPEC. SECTION:
Section 01 79 00 Supplement
Manufacturers Certificate of Proper Installation
Startup Procedure: (Describe procedure for sequential startup and evaluation, including valves to be
opened/closed, order of equipment startup, etc.):
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
Evaluation Comments:
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
Section 01 79 00 Supplement
Unit Process Startup Form
Unit Processes Startup Sequence: (Describe sequence for startup, including computerized operations if
any):
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________
Contractor Certification that Facility is capable of performing its intended function(s), including fully
automatic operation:
Section 01 79 00 Supplement
Facility Performance Demonstration/Certificate Form
SUMMARY
A.
Section includes description and requirements of the required Spare Parts and Maintenance for
the project.
B.
Ninety (90) days after approval of the Shop Drawings of the equipment specified in the
individual Sections, the CONTRACTOR shall furnish spare parts data and maintenance material
for equipment. The data shall include a complete list of parts and supplies, with current unit
prices and source or sources of supply.
C.
Spare parts and materials required to be supplied in the Contract Documents shall be furnished
in manufacturers unopened cartons, boxes, crates, or other protective covering suitable for
preventing corrosion or deterioration for the maximum length of storage which may be normally
anticipated. They shall be clearly marked and identified as to the name of manufacturer or
supplier, applicable equipment, part number, description and location in the equipment. All parts
shall be protected and packaged for a shelf life of at least 10 years.
D.
During construction, store parts in buildings or trailers with floor, roof and closed sides and in
accordance with manufacturers recommendations. Protect from weather, condensation, and
humidity.
E.
Parts and materials shall be delivered to the OWNER upon Substantial Completion of the Work
or start-up. CONTRACTOR shall then place them in permanent storage rooms or areas
approved by the OWNER. The turnover procedures shall be developed by the ENGINEER.
F.
Provide a letter of transmittal and spare parts receiver form including the following:
1.
Date of letter and transfer of parts and material.
2.
Contract title and number.
3.
CONTRACTORs name and address.
4.
Transmittal should list applicable specification sections for each set of spare parts
supplied.
5.
Spare Parts Receiver Form.
G.
CONTRACTOR shall be fully responsible for loss or damage to parts and materials until they
are transmitted to the OWNER.
END OF SECTION
Section 01 79 01
Spare Parts and Maintenance
EQUIPMENT NUMBER:
SPECIFICATION SECTION:
ODWC PERSONNEL FILL IN:
BIN NUMBER:
AIMS NUMBER:
LOCATION IN STORES:
RECEIVED BY:
END OF SECTION
Section 01 79 01
Spare Parts and Maintenance
SUMMARY
A.
1.2
Section includes: Project design criteria such as temperature and site elevation.
PROJECT DESIGN CRITERIA
A.
All equipment and materials for the project are to be suitable for performance in wastewater
treatment plant, water reclamation plant environment and under following conditions:
1.
Design temperatures are:
a.
Outdoor temperatures: -2.0 to 109 degrees Fahrenheit.
b.
Indoor temperatures for the following buildings:
1)
Process areas: 75 to 105 degrees Fahrenheit.
2)
Electrical rooms: 75 to 85 degrees Fahrenheit.
2.
Design groundwater elevation: 1093.00 Ft. El.; this is the sites100 yr flood elevation.
3.
Frost line is assumed 24 inches below grade.
4.
Moisture conditions: Defined in individual equipment sections.
5.
Site elevation: Approximately ranges generally from 1090.00 to 1126.00 feet above mean
sea level.
END OF SECTION
Section 01 81 00
Project Design Criteria
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 41 00 Regulatory Requirements.
1.2
REFERENCES
A.
1.3
A.
Design requirements:
1.
Design in accordance with the requirements of the building code as specified in Section
01 41 00:
a.
Soil Site Class: D
b.
Design spectral acceleration at short period, SDS: 0.348g.
c.
Design spectral acceleration at short period, SD1: 0.121g.
d.
Seismic Design Category: C
e.
Importance Factor, I: 1.25
f.
Component amplification factor, ap: In accordance with ASCE 7-05, Tables 13.5 1
and 13.6-1.
g.
Component response modification factor, Rp: In accordance with ASCE 7 05,
Tables 13.5-1 and 13.6-1.
h.
Component importance factor, Ip: 1.50.
2.
Do not use friction to resist sliding due to seismic forces.
3.
Do not use more than 60 percent of the weight of the mechanical and electrical
equipment for designing anchors for resisting overturning due to seismic forces.
4.
Do not use more than 60 percent of the weight of the tank for resisting overturning due to
seismic forces.
5.
Use anchor bolts, bolts, or welded studs for anchors for resisting seismic forces. Anchor
bolts used to resist seismic forces shall have a standard hex bolt head embedded in the
concrete. Do not use anchor bolts fabricated from rod stock with an L or J shape.
6.
Do not use chemical anchors, concrete anchors, flush shells, powder actuated fasteners,
sleeve anchors, or other types of anchors unless indicated on the Drawings or accepted
in writing by the ENGINEER.
Section 01 81 02
Seismic Design Criteria
7.
1.4
Seismic forces must be resisted by direct bearing on the fasteners used to resist seismic
forces. Do not use connections that use friction to resist seismic forces.
SUBMITTALS
A.
Shop drawings and calculations: Complete shop drawings and seismic calculations.
B.
Calculations shall be signed and stamped by a civil or structural engineer licensed in the state
where the Project is located.
Section 01 81 02
Seismic Design Criteria
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 41 00 Regulatory Requirements.
1.2
SYSTEM DESCRIPTION
A.
1.3
Design requirements:
1.
Building code criteria: Design for wind in accordance with building code as specified in
Section 01 41 00:
a.
Occupancy category: III.
b.
Basic wind speed: 90 miles per hour.
c.
Exposure category: C.
d.
Topographic factor, Kzt: 1.0.
e.
Wind importance factor, Iw: 1.15.
2.
Use anchor bolts, bolts, or welded studs for anchors for resisting wind forces. Anchor
bolts used to resist wind forces shall have a standard hex bolt head embedded in the
concrete. Do not use anchor bolts fabricated from rod stock with an L or J shape:
a.
Do not use concrete anchors, sleeve anchors, flush shells, chemical anchors,
powder actuated fasteners, or other types of anchor unless indicated on the
Drawings or accepted in writing by the ENGINEER.
b.
Wind forces must be resisted by direct bearing on the anchors used to resist wind
forces. Do not use connections which use friction to resist wind forces.
SUBMITTALS
A.
Shop drawings and calculations: Complete shop drawings and seismic calculations.
B.
Calculations shall be signed and stamped by a civil or structural engineer licensed in the state
where the Project is located.
END OF SECTION
Section 01 81 04
Wind Design Criteria
DIVISION 02
EXISTING CONDITIONS
SECTION 02 41 00 - DEMOLITION
PART 1 - GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
Portions of buildings and other areas, equipment and materials selective demolition, and
partial demolition work are as shown on Drawings and specified herein.
2.
Equipment and materials to be removed for construction and reinstalled for reuse or
continued operation are as shown on the drawings and specified herein.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 31 23 23.13 Fill and Backfill
1.2
SUBMITTALS
A.
Shop Drawings: Plans showing all equipment and materials to be removed and reinstalled for
reuse on continued operation including interim storage plans for each item.
B.
PREPARATION
A.
Utilities:
1.
Notify Owner and appropriate utilities 72 hours prior to turning off affected services before
starting demolition or alterations.
2.
Remove utility lines exposed by demolition excavation.
3.
Remove electric, sanitary, and storm drainage adjacent to buildings to be demolished.
4.
Excavate utility lines serving buildings to be demolished and provide a permanent leakproof closure for water and gas lines.
5.
Plug sewer lines at locations shown or at limits of excavation if not shown with min. 2,000
psi compressive strength concrete plug to prevent groundwater infiltrating sewer
systems. Length of plug shall be 5 feet minimum.
B.
Section 02 41 00
Demolition
3.
3.2
DEMOLITION
A.
B.
Provide all demolition, removal, temporary storage, and reinstallation of existing equipment as
required for implementation of the work.
C.
Core drill floor slabs, catch basins, and other concrete improvements to remain in place below
ground, or break holes at structures lowest point to allow water to freely migrate through.
D.
Remove piping from areas to be backfilled. Pipe, valves, and fittings adjacent to those to be
removed may also be removed as salvage.
E.
Remove all materials associated with existing equipment that is to be removed or relocated.
F.
Cut off concealed or embedded conduit, boxes, or other materials a minimum of 3/4 inch below
final finished surface.
G.
Cut off drilled piers a minimum of 6 inches below bottom of new foundations.
H.
3.3
DISPOSAL
A.
3.4
A.
Demolished Areas: Backfill to existing ground level, elevations shown, or foundation level of
new construction.
B.
3.5
SALVAGE
A.
Equipment and materials not reused or reinstalled, including all metals and piping within the
limits of demolition, unless otherwise specified, shall be delivered to the Owner for scrap.
END OF SECTION
Section 02 41 00
Demolition
DIVISION 03
CONCRETE
SUMMARY
A.
Section Includes:
1.
Resurfacing of concrete surfaces in preparation for finish materials.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 Cast-In-Place Concrete.
1.2
REFERENCES
A.
Section 03 01 00
Concrete Surface Repair Systems
p.
q.
r.
1.3
C 1042, Standard Test Method for Bond Strength of Latex Systems used in
Concrete.
C 1202, Standard Test Method for Electrical Induction of Concretes Ability to
Resist Chloride Ion Penetration.
E 699, Criteria for Evaluation of Agencies Involved in Testing, Quality Assurance,
and Evaluating Building Components in Accordance with Test Methods
Promulgated by ASTM Committee.
DEFINITIONS
A.
Low Pressure Spray Mortar: Mortar designated by S before the product number, applied by
low pressure spraying, or in small areas by hand troweling.
B.
Surface Repair Areas: Areas that are deemed to be defective and not meeting the density or
surface specified in Section 03 30 00, CAST-IN-PLACE CONCRETE, regardless of depth of the
defective area.
1.4
SUBMITTAL
A.
1.5
Information Submittals:
1.
Mortar System:
a.
Manufacturers installation bulletin.
b.
Manufacturers recommended fabric size for mesh reinforcement.
2.
Written description of equipment proposed for hydro-demolition surface preparation.
3.
Certificates:
a.
Certificate of Compliance that proposed product systems meet or exceed specified
performance criteria when tested in accordance with Article FIELD QUALITY
CONTROL.
b.
Mortar system Manufacturers Certificate of Proper Installation.
4.
Statements of Qualification:
a.
Independent testing laboratory.
b.
Mortar system Manufacturers representative.
5.
Mortar system Manufacturers proposed modified test procedures for ASTM C 109 and
ASTM C 882 test methods.
6.
Independent testing laboratory test report.
QUALITY ASSURANCE
A.
Qualifications:
1.
Independent Testing Laboratory: Based on evaluation of laboratory submitted criteria in
accordance with ASTM E 699.
2.
Mortar System Applicator: For low pressure spray mortar system in lieu of endorsement,
complete mortar system manufacturers demonstration in accordance with Article
MANUFACTURERS SERVICES.
PART 2 - PRODUCTS
2.1
LOW PRESSURE SPRAY MORTAR SYSTEM (FOR VERTICAL AND OVERHEAD REPAIRS)
A.
Mortar:
1.
One component, rheoplastic, cement based, fiber reinforced, shrinkage compensated,
gray in color, with a minimum 30-minute working time.
2.
Cured materials mixed to a flow of 70%, at five drops shall conform to the following
criteria:
Section 03 01 00
Concrete Surface Repair Systems
a.
b.
c.
d.
e.
f.
g.
h.
Minimum Slant Shear Bond Strength: 3,000 psi in 28 days in accordance with
modified ASTM C 882 test method.
Minimum Compressive Strength: 11,000 psi at 28 days in accordance with ASTM
C 109.
Minimum Direct Shear Bond Strength: 650 psi in 28 days in accordance with
Michigan DOT.
Minimum Tensile Bond Strength (MBT In-House Test): 300 psi. in 28 days.
Minimum Flexural Properties: 1,250 psi in 28 days in accordance with ASTM C
348.
Modulus of Elasticity: 4.1 to 4.5 by 106 psi in accordance with ASTM C 469.
Maximum Permeability: 1,000 coulombs in accordance with AASHTO T 277.
System shall not produce a vapor barrier.
B.
Sprayable, extremely low permeability, sulfate resistant, easy to use and requiring only the
addition of water.
C.
D.
2.2
B.
2.3
WATER
A.
2.4
Clean and free from oil, acid, alkali, organic matter, or other deleterious substances, meeting
federal drinking water standards.
ACCESSORIES
A.
Finishing Aid Manufacturer and Product: Master Builders Inc., Cleveland, OH; CONFILM.
Section 03 01 00
Concrete Surface Repair Systems
B.
Flexible Cementitious Rebar Coating Manufacturer and Product: Master Builders Inc.,
Cleveland, OH; EMACO P22.
PART 3 - EXECUTION
3.1
GENERAL
A.
3.2
Where required because of deficiencies, concrete surface repair system shall be low pressure
spray mortar for structural repairs.
PREPARATION
A.
Remove unsound and deteriorated concrete from Work by high pressure water blasting
machines capable of scoring concrete surfaces to minimum amplitude roughness of 3/16 or as
shown. Remove to provide for maximum thickness specified for mortar.
B.
High pressure water blasting machines with 16,000 to 20,000 psi minimum.
C.
Collect and dispose of water from removal operations in manner and location acceptable to
Owner.
D.
Do not use power-driven jackhammers and chipping hammers, unless water blasting is
prohibited due to potential damage to installed equipment.
E.
Remove concrete minimum of 1 clearance around rebar for application and bonding of new
mortar to entire periphery of exposed rebar if the following surface conditions exist:
1.
50% or more of periphery around rebar is exposed during removal of concrete.
2.
25% or more of periphery around rebar is exposed during removal of concrete and
corrosion has eventuated to the extent that loss of section has occurred.
3.
Bond between existing concrete and reinforcement has deteriorated.
F.
Clean exposed reinforcing bars of rust and concrete, and coat with flexible cementitious rebar
coating.
G.
Maintain surface areas free of slurry where concrete has been removed. Remove slurry from
prepared areas before new mortar is applied.
H.
Clean surface areas to be filled with new mortar of laitance and contamination by high pressure
water blasting not more than 24 hours before applying bonding agent, Saturated Surface Dry
(SSD) existing concrete at time of application of mortar.
3.3
Mix mortar in mortar-concrete mixer attached to pump-spray equipment for spray application.
Mix with a slow speed drill and jiffler type paddle or small mortar type mixer for hand trowel
application.
B.
Apply mortar by low pressure spraying with a machine such as Moynotype, MEYCO DEQUNA
Model 20.
C.
Finish mortar with a hand float application to smooth even surface matching adjacent concrete.
Provide finishing aid at full strength.
D.
Bonding Agent:
Section 03 01 00
Concrete Surface Repair Systems
1.
2.
3.4
Hand apply bonding agent within 20 minutes of troweling on mortar. Prevent bonding
agent from drying by reapplying bonding agent to maintain surface tackiness of coat.
Work mortar firmly and quickly into area and compact with firm trowel stroke. Finish
smooth with finishing aid at full strength.
B.
Hand Troweling: Apply (scrub in) a bond coat slurry of the repair mortar to the SSD prepared
substrate before application of the mortar. Do not apply more of the bond coat than can be
covered with mortar before the bond coat dries. Do not re-temper this bond coat.
C.
Place mortar into prepared area from one side to the other.
D.
Work material firmly into the side and bottom of patch to assure a good bond. Level repair
mortar and screed to elevation of existing concrete.
E.
F.
3.5
CURING
A.
Water fog nozzle all of the mortar systems prior to curing in accordance with mortar system
Manufacturers instructions.
B.
Commence water curing after mortar system application and when curing will not cause erosion
of mortar.
C.
D.
Do not membrane cure, unless method is part of mortar system Manufacturers instructions and
approval has been obtained.
E.
3.6
B.
Construction Testing:
1.
Production Samples:
a.
Obtain mixed mortar material from shotcrete or spray equipment and produce
samples, and cure samples prior to testing.
b.
Provide minimum of three samples each test for each 1,000 square feet or portion
thereof of mortar repair to be installed.
2.
Core Samples of In-Place Repair:
Section 03 01 00
Concrete Surface Repair Systems
a.
b.
c.
d.
e.
C.
3.7
Obtain two core samples and test samples for each 2,000 square feet or portion
thereof for actual repair Work:
Cores shall be either 2-1/2 or 3 in diameter and shall be cored through cured
mortar repair and into base concrete to total depth equal to at least 2.5 times repair
mortar thickness.
Sawcut the cores after removal to trim base concrete thickness to same thickness
as mortar so that bond line is at center of repaired sample.
Samples shall be epoxy bonded to steel plates at each end using a bonding agent
to prevent failure in bond to steel plates.
Sustain bond line without failure or movement with a minimum of 300 psi in direct
tension. The tension test shall use eyebolts or threaded connectors tapped and
threaded into base plate so that tension load is concentric with center of core
sample.
Repair and fill holes where core samples have been removed using same mortar used in repair.
MANUFACTURERS SERVICES
A.
B.
3.8
PROTECTION
A.
3.9
Protect adjacent surfaces, and equipment, from being damaged by overshooting of low
pressure spray mortar.
CLEANING
A.
Remove overshot mortar and deposited rebound materials as Work proceeds. Remove from
Work, waste materials, unsound material from concrete surfaces, material chipped from walls,
water used in preparation of application and finishing.
END OF SECTION
Section 03 01 00
Concrete Surface Repair Systems
SUMMARY
A.
Section Includes:
1.
Concrete formwork.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 Cast-In-Place Concrete.
b.
Section 03 60 00 Grout.
1.2
REFERENCES
A.
1.3
A.
Design, erect, shore, brace, and maintain formwork in accordance with ACI 301, ACI 347, and
ACI 318 to support vertical, lateral, static, and dynamic loads, and construction loads that might
be applied, until structure can support such loads. Provide concrete finishes specified in Section
03 30 00, CAST-IN-PLACE CONCRETE.
1.
Formwork shop drawings shall be prepared by or under the supervision of a qualified
professional engineer licensed in the state of the work.
B.
When high range water reducer (superplasticizer) is used in concrete mix, forms shall be
designed for full hydrostatic pressure per ACI 347.
C.
D.
Limit panel deflection to 1/360th of each component span to achieve tolerances specified.
1.4
SUBMITTALS
A.
Shop Drawings:
1.
Form Ties-Tapered Through-Bolts: Proposed method of sealing form tie hole; coordinate
with details shown.
2.
All formwork erection, shoring and removal are the responsibility of the Contractor and/or
the qualified professional engineer the contractor used for the formwork drawings.
Section 03 11 00
Concrete Formwork
3.
4.
5.
B.
1.5
Indicate proposed schedule and sequence of stripping formwork, shoring removal, and
installing and removing re-shoring.
Manufacturers Data for the Following Product: Form release agent.
Formwork drawings shall be signed and sealed by the professional engineer licensed in
the state of the work and responsible for their preparation.
A.
PART 2 - PRODUCTS
2.1
FORM MATERIALS
A.
B.
Painted Surface Forms: High density overlay plywood for flat concrete surfaces to be painted.
C.
D.
E.
Rustication Grooves and Beveled Edge Corner Strips: Nonabsorbent material, compatible with
form surface, fully sealed on all sides prohibiting loss of paste or water between the two
surfaces.
F.
Form Ties:
1.
Material: Steel
2.
Spreader Inserts:
a.
Conical or spherical type.
b.
Design to maintain positive contact with forming material.
c.
Furnish units that will leave no metal closer than 1 to concrete surface when
forms, inserts, and tie ends are removed.
3.
Wire ties not permitted.
Section 03 11 00
Concrete Formwork
4.
5.
6.
7.
Flat bar ties for panel forms furnish plastic or rubber inserts with minimum 1 depth and
sufficient dimensions to permit patching of tie hole.
Water Stop Ties: For water-holding structures, basements, pipe galleries, and accessible
spaces below finish grade, furnish one of the following:
a.
Integral steel water stop 0.103 thick and 0.625 in diameter tightly and
continuously welded to tie.
b.
Neoprene water stop 3/16 thick and 15/16 diameter whose center hole is 1/2diameter of tie, or molded plastic water stop of comparable size.
c.
Orient water stop perpendicular to tie and symmetrical about center of tie.
d.
Design ties to prevent rotation or disturbance of center portion of tie during
removal of ends and to prevent water leaking along tie.
Through-Bolts: Tapered minimum 1 diameter at smallest end.
Elastic Vinyl Plug:
a.
Design and size of plug to allow insertion with tool to enable plug to elongate and
return to original length, and diameter upon removal forming watertight seal.
b.
Manufacturer and Product: Dayton/Richmond Co., Miamisburg, OH; A58 Sure
Plug.
c.
Recess plug 1 minimum and grout over hole. See Section 03 60 00 GROUT.
PART 3 - EXECUTION
3.1
Thoroughly clean form surfaces that will be in contact with concrete or that have been in contact
with previously cast concrete, dirt, and other surface contaminants prior to coating surface.
B.
Exposed Wood Forms in Contact with Concrete: Apply form release agent as recommended by
the manufacturer.
C.
Steel Forms: Apply form release agent to steel forms as soon as they are cleaned to prevent
discoloration of concrete from rust.
3.2
ERECTION
A.
B.
C.
Wall Forms:
1.
Do not reuse forms with damaged surfaces.
2.
Locate form ties and joints in an uninterrupted uniform pattern.
3.
Inspect form surfaces prior to installation to assure conformance with specified
tolerances.
D.
Section 03 11 00
Concrete Formwork
E.
3.3
Form Tolerances: Provide forms in accordance with ACI 117, 347 and 318 and the following
tolerances for finishes specified:
1.
Wall Tolerances:
a.
Straight Vertical or Horizontal Wall Surface: Flat planes within tolerance specified.
b.
Wall Type W-A:
1). Plumb within 1/4 in 10 or within 1 from top to bottom for walls over 40 feet
high.
2). Depressions in Wall Surface: Maximum 5/16 when 10 straightedge is placed
on high points in all directions.
c.
Wall Type W-B:
1). Plumb within 1/8 in 10 or within 1/2 from top to bottom for walls over 40
high.
2). Depressions in Wall Surface: Maximum 1/8 when 10 straightedge is placed
on high points in all directions.
2.
Thickness: Maximum -1/4 or +1/2 from dimension shown.
3.
Form Offset: Between adjacent pieces of form work, facing material shall not exceed 1/8
where exposed to public view and 1/4 maximum for all other conditions.
ADDITIONAL REQUIREMENTS
A.
B.
Fabricate forms for easy removal without hammering or prying against concrete surfaces.
Provide crush or wrecking plates where stripping may damage cast concrete surfaces. Provide
top forms for inclined surfaces steeper than 1.5 horizontal to 1 vertical.
1.
Install keyways, reglets, recesses and the like for easy removal.
2.
Do not use rust-stained steel form-facing material.
3.
Use only form or form-tying methods which do not cause spalling of the concrete upon
form stripping or tie removal.
C.
Set edge forms, bulkheads and intermediate screed strips for slabs to achieve required
elevations and slopes in finished concrete surfaces. Provide and secure units to support screed
strips; use strike-off templates or compacting-type screeds.
D.
Provide temporary 12 inch wide x 18 inch high openings for cleanouts and inspection ports
every 7 feet at the bottom of each lift form and where interior area of formwork is inaccessible.
Close openings with panels tightly fitted to forms and securely braced to prevent loss of
concrete mortar. Locate temporary openings in forms at inconspicuous locations, where
possible.
E.
Form openings, chases, offsets, sinkages, keyways, reglets, blocking, screeds and bulkheads
required in the Work.
1.
Determine sizes and locations from trades providing such items.
2.
Openings shall be of sufficient size to permit final alignment of pipes or other items
without deflection or offsets of any kind. Allow space for packing where items pass
through the wall to ensure watertightness. Provide openings with continuous keyways
and waterstops. Provide a slight flare to facilitate grouting and the escape of entrained air
during grouting. Provide formed openings with reinforcement as indicated in the typical
structural details. Reinforcing shall be at least 2 inches clear from the opening surfaces
and encased items.
F.
Clean forms and adjacent surfaces to receive concrete. Remove chips, wood, sawdust, dirt and
other debris just before placing concrete.
G.
Retighten forms and bracing before placing concrete, as required, to prevent mortar leaks and
maintain proper alignment.
Section 03 11 00
Concrete Formwork
H.
Coat contact surfaces of forms with form-release agent, according to manufacturers written
instructions before placing reinforcement.
I.
Embedded Items.
1.
Place and secure anchorage devices and other embedded items required for adjoining
work that is attached to or supported by cast-in-place concrete. Use setting drawings,
templates, diagrams, instructions and directions furnished with items to be embedded.
a.
Install anchor bolts/rods, accurately located, to elevations required and complying
with tolerances in Section 7.5 of AISCs Code of Standard Practice for Steel
Buildings and Bridges.
b.
Install reglets to receive waterproofing and to receive through-wall flashings in
outer face of concrete frame at exterior walls, where flashing is shown at lintels,
shelf angles and other conditions.
c.
Check special castings, channels or other metal parts that are to be embedded in
the concrete prior to and again after placing the concrete.
d.
Check nailing blocks, plugs and strips necessary for the attachment of trim, finish
and similar work prior to placing the concrete.
J.
K.
L.
Section 03 11 00
Concrete Formwork
1.
M.
END OF SECTION
Section 03 11 00
Concrete Formwork
SUMMARY
A.
1.2
Section includes:
1.
Waterstops.
2.
Joint fillers.
REFERENCES
A.
B.
C.
1.3
SUBMITTALS
A.
Product Data:
1.
Polyvinyl chloride waterstops: Complete physical characteristics.
2.
Preformed expansion joint material: Sufficient information on each type of material for
review to determine conformance of material to requirements specified.
B.
Samples:
1.
Polyvinyl chloride waterstop.
C.
Laboratory test reports: Indicating that average properties of polyvinyl chloride waterstops
material and finish conform to requirements specified in this Section.
D.
1.4
QUALITY ASSURANCE
A.
Mock-ups:
Section 03 15 00
Concrete Accessories
1.
Welding demonstration:
a.
Demonstrate ability to weld acceptable joints in polyvinyl chloride waterstops
before installing waterstop in forms.
B.
Field joints:
1.
Polyvinyl chloride waterstops field joints: Shall be free of misalignment, bubbles,
inadequate bond, porosity, cracks, offsets, and other defects which would reduce the
potential resistance of the material to water pressure at any point. Replace defective
joints. Remove faulty material from the site and disposed of by the CONTRACTOR at its
own expense.
C.
Inspections:
1.
Quality of welded joints will be subject to acceptance of the ENGINEER.
2.
Polyvinyl chloride waterstop: The following defects that represent a partial list that will be
grounds for rejection:
a.
Offsets at joints greater than 1/16 inch or 15 percent of the material thickness, at
any point, whichever is less.
b.
Exterior crack at joint, due to incomplete bond, which is deeper than 1/16 inch or
15 percent of the material thickness, at any point, whichever is less.
c.
Any combination of offset or crack which will result in a net reduction in the cross
section of the waterstop in excess of 1/16 inch or 15 percent of the material
thickness, at any point, whichever is less.
d.
Misalignment of the joint, which will result in misalignment of the waterstop in
excess of 1/2 inch in 10 feet.
e.
Porosity in the welded joint as evidenced by visual inspection.
f.
Bubbles or inadequate bonding.
PART 2 - PRODUCTS
2.1
WATERSTOPS
A.
Section 03 15 00
Concrete Accessories
Physical Characteristics
Test Method
Required Results
Specific Gravity
ASTM D 792
Hardness
ASTM D 2240
Tensile Strength
ASTM D 638
Ultimate Elongation
ASTM D 638
Alkali Extraction
CRD-C-572
ASTM D 746
Water Absorption
ASTM D 570
Accelerated Extraction
Tensile
CRD-C-572
Stiffness in Flexure
ASTM D 747
Tear Resistance
ASTM D 624
Thickness
3/8 inch
Center Bulb
6 inch Waterstops
9 inch Waterstops
1-inch nominal outside diameter. For expansion joints 1 inch and narrower and 2 inches
for expansion joints wider than 1 inch.
Width
Thickness
Allowable Tolerances
2.2
JOINT FILLERS
A.
B.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Waterstops - General:
Section 03 15 00
Concrete Accessories
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
Waterstops shall be stored so as to permit free circulation of air around the waterstop
material and to prevent direct exposure to sunlight.
Install waterstops in concrete joints where indicated on the Drawings.
Carry waterstops in walls into lower slabs and join to waterstops in slabs with appropriate
types of fittings.
In water-bearing structures: Provide all joints with waterstops, whether indicated on the
Drawings or not.
Provide waterstops that are continuous and in longest lengths practical.
Set waterstops accurately to position and line as indicated on the Drawings.
Hold and securely fix edges in position at intervals of not more than 24 inches so that
they do not move during placing of concrete.
Position the waterstop so that symmetrical halves of the waterstop are equally divided
between the concrete pours. The center axis of the waterstop shall be coincident with the
centerline of the joint.
Do not drive nails, screws, or other fasteners through waterstops in vicinity of
construction joints.
Use wires at not more than 24 inches on centers near outer edge of the waterstop to tie
waterstops into position.
Special clips may be used in lieu of wires, at contractors option.
Terminate waterstops 3 inches from top of finish surfaces of walls and slabs unless
otherwise specified or indicated on the Drawings.
When any waterstop is installed in the concrete on one side of a joint, while the other half
or portion of the waterstop remains exposed to the atmosphere for more than 2 days,
suitable precautions shall be taken to shade and protect the exposed waterstop from
direct rays of sunlight during the entire exposure and until the exposed portion is
embedded in concrete.
When placing concrete at waterstops in slabs, lift the edge of the waterstop while placing
concrete below the waterstop. Manually force the waterstop against and into the
concrete. Then cover the waterstop with fresh concrete.
B.
C.
Joints:
1.
Construct construction, and expansion joints as indicated on the Drawings.
2.
Preformed expansion joint material: Fasten expansion joint strips to concrete, masonry,
or forms with adhesive. No nailing will be permitted, nor shall expansion joint strips be
placed without fastening.
D.
Hardboard:
1.
When indicated on the Drawings, face surface of joint filler with hardboard.
2.
Other facing materials may be used provided they furnish equivalent protection and the
material is acceptable to ENGINEER.
Section 03 15 00
Concrete Accessories
3.
Hold boards in place by nails, waterproof adhesive, or other means acceptable to the
ENGINEER.
END OF SECTION
Section 03 15 00
Concrete Accessories
SUMMARY
A.
1.2
A.
General:
1.
Submit the following items for each type, style and size of hydrophilic waterstop to be
installed.
2.
Product data:
a.
Manufacturers product data sheets.
1). Include complete physical dimensions, expansion characteristics, and laboratory test reports indicating that average material properties conform to the requirements specified.
2). Provide data sheets for all materials to be included in the waterstop system.
3.
Samples:
a.
Minimum 6-inch long samples of each type of waterstop to be used if requested by
the ENGINEER.
4.
Manufacturers installation instructions:
a.
Installation instructions and recommended installation details for the complete
waterstop system, and for each component used in that system.
B.
Where general strip-type waterstop is noted, provide non-expansive mastic strip waterstop.
PART 2 - PRODUCTS
2.1
General:
1.
System composed of flexible hydrophilic urethane polymer with preformed strips,
adhesives, paste, fasteners, and other accessories required for a complete and
watertight installation.
a.
To ensure compatibility of materials, a single manufacturer shall provide all
products and accessories for the hydrophilic waterstop system.
b.
Products incorporating bentonite are not acceptable under this Section.
c.
Provide waterstop and accessories resistant to degradation under cyclic wetting
and drying and to chemicals typically found in wastewater treatment structures.
B.
Section 03 15 14
Strip-Type Waterstops
2.2
A.
General:
1.
System composed of flexible non-expansive hydrocarbon mastic with preformed strips,
primer, and other accessories required for a complete and watertight installation.
2.
To ensure compatibility of materials, a single manufacturer shall provide all products and
accessories for the mastic waterstop system.
3.
Provide waterstop and accessories resistant to degradation under cyclic wetting and
drying and to chemicals typically found in wastewater treatment structures.
B.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
B.
C.
Provide manufacturers recommended lap, splice, and corner details for strip-type waterstops.
1.
Use hydrophilic paste at all corner joints and overlap splices of hydrophilic strips.
D.
Section 03 15 14
Strip-Type Waterstops
E.
3.2
A.
Hydrophilic waterstops.
1.
Use the hydrophilic waterstop given in the table below.
Joint Type
Pipe penetrations
concrete
through
Condition of Use
Joint where hydrophilic strip
waterstop is placed under all of
the following conditions:
1. Slab or wall thickness is
greater than 10 inches, and
2. Water
stop
is
placed between 2 rows of
steel reinforcement.
3. Concrete cover from waterstop to nearest concrete
face is at least 4 inches.
Not allowed.
END OF SECTION
Section 03 15 14
Strip-Type Waterstops
SUMMARY
A.
Section Includes:
1.
Reinforcing steel and related items required for cast-in-place concrete.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 11 00 Concrete Formwork.
b.
Section 03 30 00 Cast-In-Place Concrete.
1.2
SUPERVISION
A.
B.
Codes: Reinforcement placement and detailing shall comply with practice specified in the
"Manual of Standard Practice for Detailing Reinforced Concrete Structures" publication ACI
315- latest edition of the American Concrete Institute or its latest revision, unless otherwise
specified herein.
1.3
SUBMITTALS
A.
Shop drawings: Shop drawings shall be prepared for all reinforcement required by the project.
Shop drawings shall be logically and legibly prepared to permit reasonable ease of sorting,
selecting, placing reinforcement as well as checking drawings. Preparer and fabricator shall be
identified on the drawings.
1.
Reinforcement shall not be fabricated until the shop drawings have been processed,
approved and returned.
2.
Check all shop drawings to verify reinforcement dimensions required by drawings are
satisfied.
3.
Provide bar sizes, bar lengths, bar material, bar grade, bar schedules, stirrup spacing,
bent bar diagrams, bar arrangement, splices and lap lengths, mechanical connections, tie
spacing, hoop spacing, and supports for concrete reinforcement.
B.
C.
Section 03 20 00
Concrete Reinforcement
2.
1.4
Such changes will not be acceptable unless the ENGINEER has accepted such changes
in writing.
PRODUCT HANDLING
A.
Protection:
1.
Use all means necessary to protect reinforcement from dirt and other foreign substances
before and after placing.
2.
Store in a neat manner in logical order, bundled, tagged, off the ground, and in an area
adequately isolated.
3.
Re-bundle to maintain identification when placing is interrupted.
B.
Replacement: All damaged or improperly fabricated bars shall be replaced at the Contractors
expense.
PART 2 - PRODUCTS
2.1
CONCRETE REINFORCEMENT
A.
General: All reinforcement shall be free from rust, loose mill scale, and other contaminants.
B.
Wire bar supports located between reinforcing bars and face of concrete:
1.
Stainless steel. Type 304 stainless steel bar supports.
2.
Support reinforcing for concrete placed on ground using bar support chairs with Type 304
stainless steel plates for resting on ground welded to the chairs.
C.
Concrete bar supports located between reinforcing bars and face of concrete:
1.
Manufactured expressly for supporting reinforcing bars.
2.
Manufactured with two annealed steel wires to securely tie concrete bar support to
reinforcing steel.
3.
Manufactured with minimum fc = 5,000 psi concrete.
2.2
2.3
B.
WWR may not be used in place of reinforcing bars unless accepted in writing by the Engineer.
C.
D.
If WWR is used, provide WWR having cross-sectional area per linear foot of not less than
cross-sectional area per linear foot of reinforcing bars indicated on the Drawings.
ACCESSORIES:
1.
General: Accessories shall be subject to Engineers approval.
2.
Tie wire - 18 gauge annealed steel wire.
3.
Number of chairs shall be adequate to prevent sag during steel and concrete placement.
4.
Wall layer spacers shall be 1/4 inch round "Z" bar.
5.
Horizontal layer spacers shall be wire bar supports or reinforcing bars bent to support top
layer.
6.
Dowel bar splicer:
a.
Dowel bar splicer shall be Richmond or approved equal, manufactured from
standard specified rebar material, with NC threads and shop fabricated to specified
dowel configurations.
Section 03 20 00
Concrete Reinforcement
PART 3 - EXECUTION
3.1
GENERAL
A.
Reinforcing bars and welded wire fabric reinforcement: Verify that reinforcement is new stock
free from rust scale, loose mill scale, excessive rust, dirt, oil, and other coatings which adversely
affect bonding capacity when placed in the work.
B.
Other trades: Coordinate all work of other trades to avoid conflict with reinforcement.
C.
3.2
FABRICATING
A.
B.
Bending: All bending shall be by using bending jigs and mandrels. All bars shall be bent cold.
C.
Cutting: Bars shall be cut by cold shearing. Torch cutting in the field may be permitted in special
situations.
3.3
PREPARATION
A.
3.4
Surface Preparation:
1.
Reinforcing bars: Thin coating of red rust resulting from short exposure will not be
considered objectionable. Thoroughly clean any bars having rust scale, loose mill scale,
or thick rust coat.
2.
Cleaning of reinforcement materials: Remove concrete or other deleterious coatings from
dowels and other projecting bars by wire brushing or sandblasting before bars are
embedded in subsequent concrete placement.
PLACING
A.
General:
1.
Accurately place all bars to meet tolerances as outlined in ACI 318 and tie in place before
placing concrete, include dowels. Tie with 18 gauge steel wire.
2.
Corner bars required for horizontal reinforcing. Unless otherwise noted on plans corner
bars shall be same size and spacing as horizontal bar.
3.
No field bending of bars will be allowed.
B.
Clearance:
1.
Preserve clearance between bars of 1 inch minimum, not less than one bar diameter or
1-1/3 times large aggregate, whichever is larger.
2.
Provide following concrete coverage over reinforcing steel unless otherwise indicated on
plans:
a.
Three inches above subgrade - in excavation.
b.
Two inches above subgrade - slab on fill.
c.
Two inches from form - walls exposed to water or earth and for slab over water.
d.
One and one-half inches from form - normal cover interior walls, beams, columns,
etc.
e.
Three-fourths inch on top steel - interior slabs.
f.
One and one-half inches on top and bottom - exterior slab.
Section 03 20 00
Concrete Reinforcement
3.
4.
5.
Lap all reinforcing bars as required by ACI 318-latest edition Class B as indicated on the
drawings except where otherwise required by ACI.
Stagger splices except where otherwise shown.
Lap welded wire reinforcement a minimum of two spaces.
C.
Dowels:
All dowels shall be placed and securely anchored before placing concrete
D.
Supports:
1.
Provide a sufficient number to prevent sagging, to prevent shifting, and to support loads
during construction; but in no case less than quantities and at locations as indicated in
ACI 315.
2.
Do not use brick, broken concrete masonry units, spalls, rocks, wood or similar materials
for supporting reinforcing steel.
3.
Do not use reinforcing bars that have less cover than required by the Contract
Documents. Do not adjust location of reinforcement required by the Contract Documents
to provide cover to these bars.
4.
Wire chairs will not be accepted to hold reinforcing clearance on walls.
E.
Wall Bar
Spacing
Inches
60
48
96
60
120
96
Bar Size
7.
After tying wire ties, bend ends of wire ties in towards the center of the concrete section.
a.
The cover for wire ties shall be the same as the cover requirements for reinforcing
bars.
F.
G.
Section 03 20 00
Concrete Reinforcement
5.
If lap splice length is not indicated on the Drawings, splice fabric in accordance with
ACI 318 and ACI 350.
H.
I.
Condition: All reinforcement shall be free from loose rust, dirt coating, oil, paint, or any foreign
substance.
END OF SECTION
Section 03 20 00
Concrete Reinforcement
SUMMARY
A.
B.
Related Sections:
1.
2.
3.
1.2
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 01 00 - Concrete Surface Repair
b.
Section 03 11 00 - Concrete Formwork
c.
Section 03 15 00 - Concrete Accessories
d.
Section 03 20 00 - Concrete Reinforcement
e.
Section 03 41 00 - Precast Concrete
f.
Section 03 60 00 - Grout
g.
Section 03 60 01 - Basin Bottom Grout
h.
Section 03 64 00 - Concrete Repair Crack Injection
REFERENCES
A.
B.
Section 03 30 00
Cast-In-Place Concrete
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
ASTM C31 - Standard Practice for Making and Curing Concrete Test Specimens in the
Field.
ASTM C33 - Standard Specification for Concrete Aggregates
ASTM C39 - Standard Test Method for Compressive Strength of Cylindrical Concrete
Specimens
ASTM C40 - Standard Test Method for Organic Impurities in Fine Aggregates for
Concrete
ASTM C42 - Standard Test Method of Obtaining and Testing Drilled Cores and Sawed
Beams of Concrete
ASTM C88 - Standard Test Method of Soundness of Aggregates by Use of Sodium
Sulfate or Magnesium Sulfate
ASTM C94 - Standard Specification for Ready-Mixed Concrete
ASTM C114 - Standard Test Methods for Chemical Analysis of Hydraulic Cement
ASTM C117 - Standard Test Method for Materials Finer that 75-m (No. 200) Sieve in
Mineral Aggregates by Washing
ASTM C123 - Standard Test Method for Lightweight Particles in Aggregate
ASTM C131 - Standard Test Method for Resistance to Degradation of Small-Size Coarse
Aggregate by Abrasion and Impact in the Los Angeles Machine
ASTM C136 - Standard Test Method for Sieve Analysis of Fine and Coarse Aggregates
ASTM C142 - Standard Test Method for Clay Lumps and Friable Particles in Aggregate
ASTM C143 - Standard Test Method for Slump of Hydraulic-Cement Concrete
ASTM C150 - Standard Specification for Portland Cement
ASTM C156 - Standard Test Method for Water Loss [from a Mortar Specimen] Through
Liquid Membrane-Forming Curing Compounds for Concrete
ASTM C157 - Standard Test Method for Length Change of Hardened Hydraulic-Cement
Mortar and Concrete
ASTM C171 - Standard Specifications for Sheet Materials for Curing Concrete
ASTM C172 - Standard Practice for Sampling Freshly Mixed Concrete
ASTM C173 - Standard Test Method for Air Content of Freshly Mixed Concrete by the
Volumetric Method
ASTM C192 Standard Practice for Making and Curing Concrete Test Specimens in the
Laboratory
ASTM C231 Standard Test Method for Air Content of Freshly Mixed Concrete by the
Pressure Method
ASTM C260 Standard Specification for Air-Entraining Admixtures for Concrete
ASTM C295 Standard Guide for Petrographic Examination of Aggregates for Concrete
ASTM C309 Standard Specification for Liquid Membrane-Forming Compounds for
Curing Concrete
ASTM C494 Standard Specification for Chemical Admixtures for Concrete
ASTM C618 Standard Specification for Coal Fly Ash and Raw or Calcined Natural
Pozzolan for Use in Concrete
ASTM C881 Standard Specification for Epoxy-Resin-Base Bonding Systems for
Concrete
ASTM C1064 Standard Test Method for Temperature of Freshly Mixed HydraulicCement Concrete
ASTM C1059 Standard Specification for Latex Agents for Bonding Fresh to Hardened
Concrete
ASTM C1077 Standard Practice for Agencies Testing Concrete and Concrete
Aggregates for Use in Construction and Criteria for Testing Agency Evaluation
ASTM C1116 Standard Specification for Fiber-Reinforced Concrete
ASTM C1315 Standard Specification for Liquid Membrane-Forming Compounds
Having Special Properties for Curing and Sealing Concrete
ASTM D448 Standard Classification for Sizes of Aggregate for Road and Bridge
Construction
ASTM D1751 Standard Specification for Preformed Expansion Joint Filler for Concrete
Paving and Structural Construction (Nonextruding and Resilient Bituminous Types)
Section 03 30 00
Cast-In-Place Concrete
37.
38.
39.
40.
41.
1.3
ASTM D2240 Standard Test Method for Rubber Property Durometer Hardness
ASTM E329 Standard Specification for Agencies Engages in Construction Inspection,
Testing, or Special Inspection
ASTM E1155 Standard Test Method for Determining FF Floor Flatness and FL Floor
Levelness Numbers
ASTM E1643 Standard Practice for Selection, Design, Installation, and Inspection of
Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs
ASTM E1745 Standard Specification for Plastic Water Vapor Retarders Used in
Contact with Soil or Granular Fill under Concrete Slabs
DEFINITIONS
A.
Cementitious Materials: Portland cement alone or in combination with one or more of the
following: blended hydraulic cement, fly ash and other pozzolans, ground granulated blastfurnace slag, and silica fume; subject to compliance with requirements.
B.
Exposed Concrete: Concrete surface that can be seen inside or outside of structures regardless
whether concrete is above water, dry at all times, or can be seen when structure is drained.
C.
D.
Defective Areas: Surface defects that include honeycomb, rock pockets, indentations greater
than 3/16, cracks 0.005 wide and larger as well as any crack that leaks for liquid containing
basins and below grade habitable spaces; cracks 0.010 wide and larger in non-fluid holding
structures, spalls, chips, air bubbles greater than in diameter, pinholes, bug holes,
embedded debris, lift lines, sand lines, bleed lines, leakage from form joints, fins and other
projections, form pop-outs, texture irregularities, and stains and other color variations that
cannot be removed by cleaning.
1.4
SUBMITTALS
A.
B.
C.
Welding certificates.
D.
E.
Section 03 30 00
Cast-In-Place Concrete
9.
Joint-filler strips.
F.
Floor surface flatness and levelness measurements indicating compliance with specified
tolerances.
G.
H.
I.
J.
One copy of each 30 consecutive strength test results and mix design used from a record of
past performance or one copy of the laboratory trial mix design and results and one copy of the
mix design proposed for each mixture and use under this contract. If the 30 consecutive
strength tests are used, the test shall have been made within the 12 month period prior to this
submittal.
K.
Material Test Reports: for the following, from a testing agency acceptable to the ENGINEER,
indicating compliance with requirements:
1.
Aggregates. Include service record data indicating absence of deleterious expansion of
concrete due to alkali aggregate reactivity.
L.
Ready-Mix concrete.
1.
Provide delivery tickets for ready-mix concrete or weigh-masters certificate per ASTM
C94 including weights of cement and each size aggregate and amount of water added at
the plant and record of pours. Record the amount of water added on the job on the
delivery ticket. Water added at the plant shall account for moisture in both coarse and
fine aggregate. If water is added on the job the total water content shall not exceed the
water content of the approved design mix.
2.
Keep record showing time and place of each pour (placement) of concrete, together with
transit-mix delivery slips certifying the contents of the pour (placement).
3.
Furnish records to Engineer upon request.
1.5
QUALITY ASSURANCE
A.
B.
Section 03 30 00
Cast-In-Place Concrete
be granted to base concrete proportions on the water-cement ratio limits set out in
the above referenced code.
1). Past Plant Performance: Proportions may be established on the actual field
performance of the ready-mix producer. Where the concrete production facility
has a record, based on at least 30 consecutive strength tests taken within the
prior 12 months representing similar materials and conditions to those expected, the strength used as the basis for selecting proportions shall exceed
the required fc by at least:
a). 400 psi if the standard deviation is less than 300 psi;
b). 500 psi if the standard deviation is 300 to 400 psi;
c). 700 psi if the standard deviation is 400 to 500 psi;
d). 900 psi if the standard deviation is 500 to 600 psi;
e). 1,200 psi if the standard deviation is above 600 psi or unknown.
2). Strength data for determining standard deviation shall be considered to comply
with the foregoing stipulations if they represent either a group of at least 30
consecutive tests or the statistical average of two groups totaling 30 or more
tests. The tests used to establish standard deviation shall represent concrete
produced to meet a specified strength or strengths within 1,000 psi of that
specified for the proposed work. Changes in materials and proportions within
the population of background tests shall not have been more closely restricted
than they will be for the proposed work.
3). Strength data for determining standard deviation shall be considered to comply
with the foregoing stipulations if they represent either a group of at least 30
consecutive tests or the statistical average of two groups totaling 30 or more
tests. The tests used to establish standard deviation shall represent concrete
produced to meet a specified strength or strengths within 1,000 psi of that
specified for the proposed work. Changes in materials and proportions within
the population of background tests shall not have been more closely restricted
than they will be for the proposed work.
4). Laboratory Trial Batches: When the ready-mix producer does not have a record of past performance, the combination of materials and the proportions selected shall be determined from trial mixes having proportions and consistencies suitable for the work based on ACI 211.1-77.
a)
When laboratory trial batches are used as the basis for selecting concrete proportions, strength tests shall be made in accordance with
Method of Test for Compressive Strength of Molded Concrete Cylinders (ASTM C39) on specimens prepared in accordance with Method of Making and Curing Test Specimens in the Laboratory (ASTM
C192). A curve shall be established showing the relationship between
water-cement ratio (or cement content) and compressive strength.
The curve shall be based on at least three points representing batches which produce strengths above and below that required. Each
point shall represent the average of at least three specimens tested at
28 days or the earlier age designation.
b)
The average strength required shall exceed the specified compressive strength by 1,200 psi.
c)
The maximum permissible water-cement ratio (or minimum cement
content) for the concrete to be used in the structure shall be that
shown by the curve to produce the average strength indicated, but in
no case shall the water-cement ratio exceed 0.42 by weight.
C.
Section 03 30 00
Cast-In-Place Concrete
2.
D.
Source Limitations: Obtain each type or class of cementitious material of the same brand from
the same manufacturers plant, obtain aggregate from single source, and obtain admixtures
from single source from single manufacturer.
E.
ACI Publications: Comply with the following unless modified by requirements in the Contract
Documents:
1.
ACI 301, "Specifications for Structural Concrete."
2.
ACI 117, "Specifications for Tolerances for Concrete Construction and Materials."
3.
ACI 350 Code Requirements for Environmental Engineering Concrete Structures.
4.
ACI 318 Building Code Requirements for Reinforced Concrete.
F.
Concrete Testing Service: Engage a qualified independent testing agency to perform material
evaluation tests and to design concrete mixtures.
G.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1.
Available Products: Subject to compliance with requirements products that may be
incorporated into the work include, but are not limited to products specified.
2.
Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
manufacturers specified.
FORM-FACING MATERIALS
A.
B.
Smooth-Formed Finished Concrete: Form-facing panels that will provide continuous, true, and
smooth concrete surfaces. Furnish in largest practicable sizes to minimize number of joints.
Furnish on exposed surfaces and interior surfaces.
Section 03 30 00
Cast-In-Place Concrete
C.
D.
Forms for Cylindrical Columns, Pedestals, and Supports: Metal, glass-fiber-reinforced plastic,
paper, or fiber tubes that will produce surfaces with gradual or abrupt irregularities not
exceeding specified formwork surface class. Provide units with sufficient wall thickness to resist
plastic concrete loads without detrimental deformation.
E.
F.
Void Forms: Biodegradable paper surface, treated for moisture resistance, structurally sufficient
to support weight of plastic concrete and other superimposed loads.
G.
Chamfer Strips: Wood, metal, PVC, or rubber strips, 3/4 by 3/4 inch, minimum.
H.
Rustication Strips: Wood, metal, PVC, or rubber strips, kerfed for ease of form removal.
I.
2.3
REINFORCEMENT ACCESSORIES
A.
Expansion Joint Dowel Bars: ASTM A615/A615M, Grade 60, plain-steel bars, cut true to length
with ends square and free of burrs.
1.
All dowels shall be placed and securely anchored before placing concrete. All dowels
shall be parallel with each other and perpendicular to the joint.
B.
Bar Supports: Bolsters, chairs, spacers, and other devices for spacing, supporting, and
fastening reinforcing bars and welded wire reinforcement in place. Manufacture bar supports
from steel wire, plastic, or precast concrete according to CRSIs "Manual of Standard Practice,"
of greater compressive strength than concrete and as follows:
1.
For concrete surfaces exposed to view where legs of wire bar supports contact forms,
use CRSI Class 1 plastic-protected steel wire or CRSI Class 2 stainless-steel bar
supports.
2.
Secure all reinforcement in place using steel chairs, supports, A bars and any other ACI
approved product. Supports shall be spaced adequately to support the steel firmly in
place.
3.
Charis will not be accepted to hold reinforcing clearance on walls.
C.
General:
1.
Accessories shall be subject to Engineers approval.
2.
Tie wire- 18 gauge steel wire. Ends of wire shall be bent towards the interior part of the
wall.
3.
Support above forms with fabricated steel chairs. Number of chairs shall be adequate to
prevent sag during steel and concrete placement.
4.
Wall layer spacers shall be 1/4 ROUND Z BAR.
5.
Horizontal layer spacers shall be stand.
6.
Dowel Bar Splicer:
a.
Dowel bar splicer shall be Richmond or approved equal, manufactured from
standard specified rebar material with NC threads and shop fabricated to specified
dowel configurations.
Section 03 30 00
Cast-In-Place Concrete
2.4
CONCRETE MATERIALS
A.
Cementitious Material: Use the following cementitious materials, of the same type, brand, and
source, throughout Project:
1.
Portland Cement (Non-hydraulic Above Grade Structures): ASTM C150, Type I or II, or
combination of Type I with fly ash.
2.
Portland Cement (Hydraulic and/or Below Grade Structures): ASTM C150 type II or
combination of Type I with fly ash.
3.
Fly Ash: ASTM C618, Class C or F fly ash shall not exceed 15 percent of the
cementitious materials, unless written approval is given by the Engineer.
B.
Normal-Weight Aggregates: ASTM C33, Class 3S coarse aggregate or better, graded. Provide
aggregates from a single source with documented service record data of at least 10 years
satisfactory service in similar applications and service conditions using similar aggregates and
cementitious materials.
1.
Maximum Coarse-Aggregate Size: 1 nominal.
2.
Fine Aggregate: Free of materials with deleterious reactivity to alkali in cement.
3.
Fine aggregate:
a.
Provide fine aggregate for concrete or mortar consisting of clean, natural sand or
of sand prepared from crushed stone or crushed gravel.
b.
Do not provide aggregate having deleterious substances in excess of following
percentages by weight of contaminating substances.
c.
In no case shall total exceed percent listed.
Item
Removed by decantation
(dirt, silt, etc.)
Shale or Chert
Test Method
ASTM C117
Percent
3
ASTM C123
1
ASTM C295*
1
Clay Lumps
ASTM C142
1
*
Test Method C123 is used to identify particles in the sample lighter
than 2.40 Specific Gravity. Test Method C295 is used to identify
which of the lightweight particles are shale or chert. If the results of
Test Method C123 are less than 1 percent, Test Method C295 is not
required.
d.
4.
Coarse aggregate:
a.
Provide coarse aggregate consisting of gravel or crushed stone made up of clean,
hard, durable particles free from calcareous coatings, organic matter, or other
foreign substances.
b.
Not exceeding 15 percent by weight, of thin or elongated pieces having length
greater than 5 times average thickness.
c.
Deleterious substances: Not in excess of following percentages by weight, and in
no case having total of all deleterious substances exceeding 2 percent.
d.
Coarse aggregate shall be washed prior to combining in concrete mix.
Section 03 30 00
Cast-In-Place Concrete
Item
Shale or chert
Test Method
ASTM C123
ASTM C295**
Percent
1.25
1
C.
2.5
Grading:
a.
Aggregate for building elements and hydraulic structures: In accordance with
ASTM C33, Size Number 57, except as otherwise specified or authorized in writing
by the ENGINEER.
A.
B.
2.6
VAPOR RETARDERS
A.
Plastic Vapor Retarder: ASTM E1745, Class B. Include manufacturers recommended adhesive
or pressure-sensitive tape.
1.
Products:
a.
Fortifiber Corporation: Moistop Ultra.
b.
Revan Industries Inc.; Vapor Block 10.
c.
Stego Industries, LLC; Stego Wrap, 15 mils.
B.
Granular Fill: Clean mixture of crushed stone or crushed or uncrushed gravel; ASTM D448,
Size 57, with 100 percent passing a 1-1/2-inch sieve and 0 to 5 percent passing a No. 8 sieve.
Section 03 30 00
Cast-In-Place Concrete
2.7
2.8
Penetrating Liquid Floor Treatment: Clear, chemically reactive, waterborne solution of inorganic
silicate or siliconate materials and proprietary components; odorless; that penetrates, hardens,
and densifies concrete surfaces.
1.
Products:
a.
Burke by Edoco; Titan Hard.
b.
ChemMasters; Chemisil Plus.
c.
ChemTec international; ChemTec One.
d.
Conspec Marketing & Manufacturing Co., Inc., a Dayton Superior Company
e.
Curecrete Distribution Inc.; Ashford Formula.
f.
Dayton Superior Corporation; Day-Chem sure Hard.
g.
Euclid Chemical Company (The); Euco Diamond Hard.
h.
Kaufman Products, Inc.; SureHard.
i.
L&M Construction Chemicals, Inc.; Seal Hard.
j.
Meadows, W. R., Inc.; Liqui-Hard.
k.
Metalcrete Industries; Floorsaver.
l.
Nox-Crete Products Group, Kinsman Corporation; Duranox.
m.
Symons Corporation, a Dayton Superior Company; buff Hard.
n.
US Mix Products Company; US Spec Industraseal.
o.
Vexcon Chemicals, Inc.; Vexcon StarSeal PS.
CURING MATERIALS
A.
B.
Absorptive Cover: AASHTO M182, Class 2, burlap cloth made from jute or kenaf, weighing
approximately 9 oz./sq. yd. when dry.
C.
D.
Water: Potable.
E.
10
Section 03 30 00
Cast-In-Place Concrete
1.
F.
2.9
Products
a.
Anti-Hydro International, Inc.; AH Curing Compound #2 DR WB.
b.
Burke by Edoco; Aqua Resin cure.
c.
ChemMasters; Safe-Cure Clear.
d.
Conspec Marketing & Manufacturing co., Inc., a Dayton Superior Company; W.B.
Resin cure.
e.
Dayton Superior Corporation; Day Chem Rez cure (J-11-W).
f.
Euclid Chemical Company (The); Kurez DR VOX.
g.
Kaufman Products, Inc.; Thinfilm 420.
h.
Lambert Corporation; Aqua Kure-Clear.
i.
L&M Construction Chemicals, Inc.; L&M Cure R.
j.
Meadows, W. R., Inc.; 100 Clear.
k.
Nox-Crete Products Group, Kinsman Corporation; Resom Cire E/
l.
Sykkmons Corporation, a Dayton Superior Company; Resi-Chem Clear Cure.
m.
Tamms Industries, Inc., Horncure WB 30.
n.
Unitex; Hydro cure 309.
o.
US Mix Products Company; US Spec Maxcure Resin Clear.
p.
Vexcon Chemicals, Inc.; Certi-Vex Enviocure 100.
Clear, Waterborne, Membrane-Forming Curing and Sealing Compound: ASTM C1315, Type 1,
Class A. Compatible with penetrating liquid floor treatment for surfaces specified to receive
penetrating liquid floor treatment.
1.
Products:
a.
Burke by Edoco; Cureseal 1315 WB.
b.
ChemMasters; Polyseal WB.
c.
Conspec Marketing & Manufacturing Co., Inc., a Dayton Superior Company;
Sealcure 1315 WB
d.
Euclid Chemical Company (The); Super Diamond Clear VOX.
e.
Kaufman Products, Inc.; Sure Cure 25 Emulsion.
f.
Lambert Corporation; UV Safe Seal.
g.
L&M Construction Chemicals, Inc.; Lumiseal WB Plus.
h.
Meadows, W. R., Inc.; Vocomp-30.
i.
Metalcrete Industries; Metcure 30.
j.
Symons Corporation, a Dayton Superior Company; Cure 7 Seal 31 Percent E.
k.
Tamms Industries, Inc.; LusterSeal WB 300.
l.
Unitex; Hydro Seal 25.
m.
US Mix Products Company; US Spec Radiance UV-25.
n.
Vexcon Chemicals, Inc.; Vexcon Starseal 1315.
RELATED MATERIALS
A.
B.
Semi-rigid Joint Filler: Two-component, semi-rigid, 100 percent solids, epoxy resin with a
Type A shore durometer hardness of 80 per ASTM D2240.
C.
Bonding Agent: ASTM C1059, Type II, non-redispersible, acrylic emulsion or styrene butadiene.
D.
Epoxy Bonding Adhesive: ASTM C881, two-component epoxy resin, capable of humid curing
and bonding to damp surfaces, of class suitable for application temperature and of grade to suit
requirements, and as follows:
1.
Types IV and V, load bearing for bonding hardened or freshly mixed concrete to
hardened concrete.
11
Section 03 30 00
Cast-In-Place Concrete
2.10
A.
2.11
REPAIR MATERIALS
See Sections 03 01 00, CONCRETE SURFACE REPAIR SYSTEMS and 03 64 00,
CONCRETE REPAIR CRACK INJECTION.
CONCRETE MIXTURES, GENERAL
A.
Prepare design mixtures for each type and strength of concrete, proportioned on the basis of
laboratory trial mixture or field test data, or both, according to ACI 301.
1.
Use a qualified independent testing agency for preparing and reporting proposed mixture
designs based on laboratory trial mixtures.
B.
C.
D.
2.12
CONCRETE MIXTURES
A.
B.
2.13
A.
CONCRETE MIXING
Ready-Mixed Concrete: Measure, batch, mix, and deliver concrete according to
ASTM C94/C94M and ASTM C1116, and furnish batch ticket information.
1.
When air temperature is between 85 and 90 deg F, reduce mixing and delivery time from
1-1/2 hours to 75 minutes; when air temperature is above 90 deg F, reduce mixing and
delivery time to 60 minutes.
12
Section 03 30 00
Cast-In-Place Concrete
B.
Project-Site Mixing: Measure, batch, and mix concrete materials and concrete according to
ASTM C94/C94M. Mix concrete materials in appropriate drum-type batch machine mixer.
1.
For mixer capacity of 1 cu. yd. or smaller, continue mixing at least 1-1/2 minutes, but not
more than 5 minutes after ingredients are in mixer, before any part of batch is released.
2.
For mixer capacity larger than 1 cu. yd., increase mixing time by 15 seconds for each
additional 1 cu. yd.
3.
Provide batch ticket for each batch discharged and used in the Work, indicating Project
identification name and number, date, mixture type, mixture time, quantity, and amount of
water added. Record approximate location of final deposit in structure.
PART 3 - EXECUTION
3.1
3.2
VAPOR RETARDERS
A.
3.3
Sheet Vapor Retarders: Place, protect, and repair sheet vapor retarder according to
ASTM E1643 and manufacturers written instructions.
1.
Lap joints 6 inches and seal with manufacturers recommended tape.
JOINTS
A.
General: Construct joints true to line with faces perpendicular to surface plane of concrete.
B.
Construction Joints: Install so strength and appearance of concrete are not impaired, at
locations indicated or as approved by Engineer/Owner
1.
Place joints perpendicular to main reinforcement. Continue reinforcement across
construction joints unless otherwise indicated. Do not continue reinforcement through
sides of strip placements of floors and slabs.
2.
Form keyed joints as indicated. Embed keys at least 1-1/2 inches into concrete.
3.
Locate joints for beams, slabs, joists, and girders in the middle third of spans. Offset
joints in girders a minimum distance of twice the beam width from a beam-girder
intersection.
4.
Locate horizontal joints in walls and columns at underside of floors, slabs, beams, and
girders and at the top of footings or floor slabs.
5.
Space vertical joints in walls as indicated. Locate joints beside piers integral with walls,
near corners, and in concealed locations where possible.
6.
Use epoxy-bonding adhesive at locations where fresh concrete is placed against
hardened or partially hardened concrete surfaces.
C.
D.
Isolation Joints in Slabs-on-Grade: After removing formwork, install joint-filler strips at slab
junctions with vertical surfaces, such as column pedestals, foundation walls, grade beams, and
other locations, as indicated.
13
Section 03 30 00
Cast-In-Place Concrete
1.
2.
3.
E.
3.4
Extend joint-filler strips full width and depth of joint, terminating flush with finished
concrete surface unless otherwise indicated.
Terminate full-width joint-filler strips not less than 1/2 inch or more than 1 inch below
finished concrete surface where joint sealants, specified in Division 07 Section "Joint
Sealants," are indicated.
Install joint-filler strips in lengths as long as practicable. Where more than one length is
required, lace or clip sections together.
Doweled Joints: Install dowel bars and support assemblies at joints where indicated. Lubricate
or asphalt coat one-half of dowel length to prevent concrete bonding to one side of joint.
CONCRETE PLACEMENT
A.
Before placing concrete, verify that installation of formwork, reinforcement, and embedded items
is complete and that required inspections have been performed.
B.
Do not add water to concrete during delivery, at Project site, or during placement unless
approved by the Engineer.
C.
Before test sampling and placing concrete, water may be added at Project site, subject to
limitations of ACI 301.
1.
Do not add water to concrete after adding high-range water-reducing admixtures to
mixture.
D.
Deposit concrete continuously in one layer or in horizontal layers of such thickness that no new
concrete will be placed on concrete that has hardened enough to cause seams or planes of
weakness. If a section cannot be placed continuously, provide construction joints as indicated.
Deposit concrete to avoid segregation.
1.
Deposit concrete in horizontal layers of depth to not exceed formwork design pressures
and in a manner to avoid inclined construction joints.
2.
Consolidate placed concrete with mechanical vibrating equipment according to ACI 301.
3.
Do not use vibrators to transport concrete inside forms. Insert and withdraw vibrators
vertically at uniformly spaced locations to rapidly penetrate placed layer and at least 6
inches into preceding layer. Do not insert vibrators into lower layers of concrete that have
begun to lose plasticity. At each insertion, limit duration of vibration to time necessary to
consolidate concrete and complete embedment of reinforcement and other embedded
items without causing mixture constituents to segregate.
E.
Deposit and consolidate concrete for floors and slabs in a continuous operation, within limits of
construction joints, until placement of a panel or section is complete.
1.
Consolidate concrete during placement operations so concrete is thoroughly worked
around reinforcement and other embedded items and into corners.
2.
Maintain reinforcement in position on chairs during concrete placement.
3.
Screed slab surfaces with a straightedge and strike off to correct elevations.
4.
Slope surfaces uniformly to drains where required.
5.
Begin initial floating using bull floats or darbies to form a uniform and open-textured
surface plane, before excess bleedwater appears on the surface. Do not further disturb
slab surfaces before starting finishing operations.
F.
Cold-Weather Placement: Comply with ACI 306.1 and as follows. Protect concrete work from
physical damage or reduced strength that could be caused by frost, freezing actions, or low
temperatures.
1.
When average high and low temperature is expected to fall below 40 deg F for three
successive days, maintain delivered concrete mixture temperature within the temperature
range required by ACI 301.
14
Section 03 30 00
Cast-In-Place Concrete
2.
3.
4.
5.
G.
3.5
All embedded items such as wall pipes, embed frames, steel guide rails, channels, etc.
(not including conduit and reinforcing) shall be considered massive embedments and
are required to be kept above 32 deg F during placement and for the first 48 hours after
placement. Contractor shall take the necessary measures; including insulated blankets,
heated blankets, and heaters; to insure items are kept above 32 deg F. All other methods
shall be submitted to the Engineer for approval.
Do not use frozen materials or materials containing ice or snow.
Do not place concrete on frozen subgrade or on subgrade containing frozen materials.
Top 12-inches of subgrade shall be thawed prior to concrete placement. Contractor is
responsible for verifying that the temperature for the top 12-inches of subgrade is above
32 deg F.
Do not use calcium chloride, salt, or other materials containing antifreeze agents or
chemical accelerators unless otherwise specified and approved in mixture designs.
A.
B.
C.
3.6
General:
1.
Finish slab concrete per the requirements of ACI 302.1R
2.
Use manual screeds, vibrating screeds, or roller compacting screeds to place concrete
level and smooth.
3.
Do not use Jitterbugs or other special tools designed for the purpose of forcing coarse
aggregate away from the surface and allowing a layer of mortar, which will be weak and
cause surface cracks or de-lamination, to accumulate.
4.
Do not dust surface with dry materials.
5.
Use evaporation retardant.
6.
Round off edges of slabs with a steel edging tool, except where a cove finish is shown.
Steel edging tool radius shall be 1/4 for slabs subject to wheeled traffic.
15
Section 03 30 00
Cast-In-Place Concrete
B.
C.
D.
Type S-3 (Underside Elevated Slab Finish): When forming is removed, grind off projections on
underside of slab and patch defective areas, including small shallow air pockets where schedule
of concrete finishes requires painting or protective coating.
E.
F.
G.
Type S-7: The top surfaces of basins in which raking mechanisms are to be installed
1.
Slabs shall be finished by sweeping in cement grout with the mechanism. The cement
grout to be used shall be composed of one part Portland cement and two parts sand.
2.
The sweeping-in process shall be performed under the supervision of a factory
representative of the equipment manufacturer.
3.
The slab upon which the grout is to be applied shall receive a Type S-5 finish except that
after leveling and floating, it shall be raked in such a manner as to provide a good bond
for the grout. Raking shall develop a pattern with a depth of 1/4 every 2. Before grout is
deposited on the slab, it shall be thoroughly cleaned, wet down with clean water and
lightly dusted with neat cement immediately prior to placement of the grout.
16
Section 03 30 00
Cast-In-Place Concrete
3.7
B.
3.8
Type of Finish
Required Form
Tolerances
W-2
W-B
W-1
W-A
W-5
W-A
W-5
W-B
S-5
S-1
S-1
S-5
S-6
S-1
S-7
S-1
S-1
S-3
S-2
Filling In: Fill in holes and openings left in concrete structures after work of other trades is in
place unless otherwise indicated. Mix, place, and cure concrete, as specified, to blend with inplace construction. Provide other miscellaneous concrete filling indicated or required to
complete the Work.
B.
Curbs: Provide monolithic finish to interior curbs by stripping forms while concrete is still green
and by steel-troweling surfaces to a hard, dense finish with corners, intersections, and
terminations slightly rounded.
C.
Equipment Bases and Foundations: Provide machine and equipment bases and foundations as
shown on Drawings. Set anchor bolts for machines and equipment at correct elevations,
complying with diagrams or templates from manufacturer furnishing machines and equipment.
17
Section 03 30 00
Cast-In-Place Concrete
D.
3.9
Steel Pan Stairs: Provide concrete fill for steel pan stair treads, landings, and associated items.
Cast-in inserts and accessories as shown on Drawings. Screed, tamp, and trowel finish
concrete surfaces.
CONCRETE PROTECTING AND CURING
A.
General: Protect freshly placed concrete from premature drying and excessive cold or hot
temperatures. Comply with ACI 306.1 for cold-weather protection and ACI 305.1 for hot-weather
protection during curing.
B.
Evaporation Retarder: Apply evaporation retarder to unformed concrete surfaces if hot, dry, or
windy conditions cause moisture loss approaching 0.2 lb/sq. ft. x h before and during finishing
operations. Apply according to manufacturers written instructions after placing, screeding, and
bull floating or darbying concrete, but before float finishing.
C.
Formed Surfaces: Cure formed concrete surfaces, including underside of beams, supported
slabs, and other similar surfaces. If forms remain during curing period, moist cure after
loosening forms. If removing forms before end of curing period, continue curing for the
remainder of the curing period.
D.
Unformed Surfaces: Begin curing immediately after finishing concrete. Cure unformed surfaces,
including floors and slabs, concrete floor toppings, and other surfaces.
E.
Cure concrete according to ACI 308.1, by one or a combination of the following methods:
1.
Moisture Curing: Keep surfaces continuously moist for not less than seven days with the
following materials:
a.
Water.
b.
Continuous water-fog spray.
c.
Absorptive cover, water saturated, and kept continuously wet. Cover concrete
surfaces and edges with 12-inch lap over adjacent absorptive covers.
2.
Moisture-Retaining-Cover Curing: Cover concrete surfaces with moisture-retaining cover
for curing concrete, placed in widest practicable width, with sides and ends lapped at
least 12 inches, and sealed by waterproof tape or adhesive. Cure for not less than seven
days. Immediately repair any holes or tears during curing period using cover material and
waterproof tape.
a.
Moisture cure or use moisture-retaining covers to cure concrete surfaces to
receive floor coverings.
b.
Moisture cure or use moisture-retaining covers to cure concrete surfaces to
receive penetrating liquid floor treatments.
c.
Cure concrete surfaces to receive floor coverings with either a moisture-retaining
cover or a curing compound that the manufacturer certifies will not interfere with
bonding of floor covering used on Project.
3.
Curing Compound: Apply uniformly in continuous operation by power spray or roller
according to manufacturers written instructions. Recoat areas subjected to heavy rainfall
within three hours after initial application. Maintain continuity of coating and repair
damage during curing period.
a.
Removal: After curing period has elapsed, remove curing compound without
damaging concrete surfaces by method recommended by curing compound
manufacturer unless manufacturer certifies curing compound will not interfere with
bonding of floor covering used on Project.
4.
Curing and Sealing Compound: Apply uniformly to floors and slabs indicated in a
continuous operation by power spray or roller according to manufacturers written
instructions. Recoat areas subjected to heavy rainfall within three hours after initial
application. Repeat process 24 hours later and apply a second coat. Maintain continuity
of coating and repair damage during curing period.
18
Section 03 30 00
Cast-In-Place Concrete
3.10
A.
Penetrating Liquid Floor Treatment: Prepare, apply, and finish penetrating liquid floor treatment
according to manufacturers written instructions.
1.
Remove curing compounds, sealers, oil, dirt, laitance, and other contaminants and
complete surface repairs.
2.
Do not apply to concrete that is less than 28 days old.
3.
Apply liquid until surface is saturated, scrubbing into surface until a gel forms; rewet; and
repeat brooming or scrubbing. Rinse with water; remove excess material until surface is
dry. Apply a second coat in a similar manner if surface is rough or porous.
B.
Sealing Coat: Uniformly apply a continuous sealing coat of curing and sealing compound to
hardened concrete by power spray or roller according to manufacturers written instructions.
3.11
JOINT FILLING
A.
Prepare, clean, and install joint filler according to manufacturers written instructions.
1.
Defer joint filling until concrete has aged at least one month. Do not fill joints until
construction traffic has permanently ceased.
B.
Remove dirt, debris, saw cuttings, curing compounds, and sealers from joints; leave contact
faces of joint clean and dry.
C.
Install semi-rigid joint filler full depth in saw-cut joints and at least 2 inches deep in formed joints.
Overfill joint and trim joint filler flush with top of joint after hardening.
3.12
REPAIRING CONCRETE
A.
General:
1.
Any areas deemed as having excessive defects or considered to have a negative effect
on the structural performance of the structure shall be removed to the extents approved
by the Engineer. The Engineer has the option of calling for the removal of the entire
section if the damage is such that a repair will not be a suitable option. All work required
to correct the defect will be the responsibility of the Contractor and will be paid for by the
Contractor.
2.
Inject cracks as defined in 1.3.D Defective Areas with crack repair epoxy as specified in
Section 03 64 00, CONCRETE REPAIR CRACK INJECTION.
3.
Repair concrete surfaces defects as defined in 1.3.D Defective Areas using one of the
materials specified in Section 03 01 00, CONCRETE SURFACE REPAIR SYSTEMS.
Select system, submit for review, and obtain approval from Engineer prior to use.
4.
Prior to starting the repair work, obtain quantities of color-matched repair material and
manufacturers detailed instructions for use to provide a structural repair with finish to
match adjacent surface.
5.
Develop repair techniques with material manufacturer.
6.
Dress surface of repair that will remain exposed to view to match color and texture of
adjacent surfaces. Repair of concrete shall provide a structurally sound surface finish,
uniform in appearance or upgrade finish by other means until acceptable to Engineer.
B.
Tie Holes:
1.
Fill with nonshrink grout as specified in Section 03 60 00, GROUT.
2.
Match color of adjacent concrete.
3.
Compact grout using steel hammer and steel tool to drive grout to high density. Cure
grout with water.
C.
19
Section 03 30 00
Cast-In-Place Concrete
1.
2.
D.
E.
3.13
A.
Testing and Inspecting: Owner will engage a qualified testing and inspecting agency to perform
field tests and inspections and prepare test reports. Payment of the testing and inspection
agency shall be by the Contractor from the contract allowance for independent testing in
accordance with Section 01 29 00, PAYMENT PROCEDURES.
B.
Inspections:
1.
Steel reinforcement placement.
2.
Headed bolts and studs.
3.
Verification of use of required design mixture.
4.
Concrete placement, including conveying and depositing.
5.
Curing procedures and maintenance of curing temperature.
6.
Verification of concrete strength before removal of shores and forms from beams and
slabs.
C.
20
Section 03 30 00
Cast-In-Place Concrete
a.
6.
7.
8.
9.
10.
11.
12.
13.
Cast and laboratory cure two sets of three standard cylinder specimens for each
composite sample.
b.
Cast and field cure two sets of three standard cylinder specimens for each
composite sample.
Compressive-Strength Tests: ASTM C39/C39M:
a.
Test one set of three laboratory-cured specimens at 7 days and one set of three
laboratory-cured specimens at 28 days.
b.
Test one set of two field-cured specimens at 7 days and one set of two field-cured
specimens at 28 days. The third cylinder will be retained for subsequent testing if
required by the Engineer.
c.
A compressive-strength test shall be the average compressive strength from a set
of two specimens obtained from same composite sample and tested at age
indicated.
When strength of field-cured cylinders is less than 85 percent of companion laboratorycured cylinders, Contractor shall evaluate operations and provide corrective procedures
for protecting and curing in-place concrete.
Strength of each concrete mixture will be satisfactory if every average of any three
consecutive compressive-strength tests equals or exceeds specified compressive
strength and no compressive-strength test value falls below specified compressive
strength by more than 500 psi.
Test results shall be reported in writing to Engineer, Owner, concrete manufacturer, and
Contractor within 48 hours of testing. Reports of compressive-strength tests shall contain
Project identification name and number, date of concrete placement, name of concrete
testing and inspecting agency, location of concrete batch in Work, design compressive
strength at 28 days, concrete mixture proportions and materials, compressive breaking
strength, and type of break for both 7- and 28-day tests.
Nondestructive Testing: Impact hammer, sonoscope, or other nondestructive device may
be permitted by Engineer but will not be used as sole basis for approval or rejection of
concrete.
Additional Tests: Testing and inspecting agency shall make additional tests of concrete
when test results indicate that slump, air entrainment, compressive strengths, or other
requirements have not been met, as directed by the Engineer. Testing and inspecting
agency may conduct tests to determine adequacy of concrete by cored cylinders
complying with ASTM C42/C42M or by other methods as directed by Engineer.
Additional testing and inspecting, at Contractors expense, will be performed to determine
compliance of replaced or additional work with specified requirements.
Correct deficiencies in the Work that test reports and inspections indicate do not comply
with the Contract Documents.
D.
Measure floor and slab flatness and levelness according to ASTM E 1155 48 hours after
finishing. Specified overall values of flatness F(f)=25; and levelness F(L)=20; with minimum
local values, F(f)=17 and F(L)=15.
1.
F(L) value only applies to elevated slabs after shoring has been removed.
E.
Shrinkage Tests
1.
Drying shrinkage tests shall be performed for the trial batch indicated in Paragraph
CONCRETE MIXTURES FOR HYDRAULIC ELEMENTS for the first placement of each
class of concrete for all structures noted in paragraph CONCRETE MIXTURES FOR
HYDRAULIC ELEMENTS, and during construction to insure continued compliance with
these Specifications. Number of field test to be determined by Engineer or Engineers
Field Representative.
2.
Drying shrinkage specimens shall be 4 by 4 by 11 prisms with an effective gauge
length of 10; fabricated, cured, dried, and measured in accordance with ASTM C157
modified as follows: specimens shall be removed from molds at an age of 23 1 hours
after trial batching, shall be placed immediately in water at 70 F 3 F for at least 30
minutes, and shall be measured within 30 minutes thereafter to determine original length
21
Section 03 30 00
Cast-In-Place Concrete
3.
F.
22
Section 03 30 00
Cast-In-Place Concrete
water surface based on the assumption that leakage would occur at the maximum
allowable rate specified or for 72 hours whichever is the lesser time.
G.
Acceptance Criteria:
1.
Volume loss shall not exceed 0.075% of contained liquid volume in a 24-hour period,
correcting for evaporation, precipitation, and settlement.
2.
No damp spots or seepage visible on exterior surfaces. A damp spot is defined as
sufficient moisture to be transferred to a dry hand upon touching.
H.
Repairs When Test Fails: Dewater the structure; fill leaking cracks with crack repair epoxy as
specified in Section 03 64 00 CONCRETE REPAIR CRACK INJECTION. Patch areas of damp
spots previously recorded, and repeat water leakage test in its entirety until the structure
successfully passes the test.
END OF SECTION
23
Section 03 30 00
Cast-In-Place Concrete
SECTION 03 60 00 - GROUT
PART 1 - GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
Non-shrink grout.
2.
Topping grout.
3.
Concrete Fill.
4.
Cement grout for pipe invert fill.
5.
Construction joint mortar.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 11 00 Concrete Formwork.
b.
Section 03 30 00 Cast-In-Place Concrete.
1.2
REFERENCES
A.
B.
1.3
SUBMITTALS
A.
B.
Certified test results verifying compliance with compressive strength, shrinkage and expansion
requirements and manufacturers literature containing instructions and recommendations on the
mixing, handling, placement and appropriate uses for each type of non-shrink and epoxy grout.
C.
D.
One copy of each 30 consecutive strength test results and mix design used from a record of
past performance, or one copy of laboratory trial mix and design and results, and one copy of
the mix design proposed for each cementitious mixture and use under this contract.
E.
Section 03 60 00
Grout
F.
Material test reports: For the following from a qualified testing agency, indicating compliance
with requirements:
1.
Aggregates, Include service record data indicating absence of deleterious expansion of
concrete due to alkali aggregate reactivity.
2.
Non-shrink grout.
3.
Epoxy grout.
G.
H.
I.
J.
Joint Mortar Bed: Provide material analysis and certification for each placement.
K.
Shop Drawings:
1.
Product data of grouts.
2.
Curing method for grout.
3.
Mix design of cement-sand grout mixture for pipe invert/structure fill.
4.
Mix design of Joint Mortar Bed.
L.
Information Submittals:
1.
Manufacturers written instructions for mixing of grout.
2.
Manufacturers Certificate of Compliance: Grout free from chlorides and other corrosioncausing chemicals.
3.
Manufacturers Certificate of Proper Installation.
4.
Statements of Qualification: Non-shrink grout manufacturers representative.
5.
Test Reports: Test report for 24-hour evaluation of non-shrink grout.
1.4
QUALIFICATIONS
A.
Manufacturers qualifications for cement grout and joint mortar bed: A firm experienced in
manufacturing ready-mixed concrete products and a firm that complies with ASTM C 94/C 94M
requirements for production facilities and equipment.
B.
Section 03 60 00
Grout
Source limitations: Obtain each type or class of cementitious material of the same brand from
the same manufacturers plant, obtain aggregate from one source and obtain admixtures
through one source from a single manufacturer.
D.
E.
For grout suppliers not listed herein, provide completed 24-hour Evaluation of Non-shrink Grout
Test Form, attached at the end of this section. Independent testing laboratory to certify that
testing was conducted within last 18 months.
1.5
GUARANTEE
A.
Manufacturers guarantee shall not contain disclaimer on the product data sheet, grout bag, or
container limiting responsibility to only the purchase price of products and materials furnished.
B.
PART 2 - PRODUCTS
2.1
CONCRETE MATERIALS
A.
Cementitious Material: Use the following cementitious materials, of the same type, brand and
source throughout project:
1.
Portland Cement: ASTM C 150, Type I or II or combination of Type I with fly ash.
2.
Fly Ash: ASTM C 618.
B.
Fine aggregates: ASTM C 33, Class 4S or better, graded. Provide aggregates from a single
source with documented service record data of at least 10 years satisfactory service in similar
applications and service conditions using similar aggregates and cementitious materials.
Aggregates shall be free of materials with deleterious reactivity to alkali in cement. Aggregates
for cement grout and/or mortar bed shall be provided from the same source as aggregate for
the cast-in-place concrete.
C.
2.2
ADMIXTURES
A.
2.3
A.
Furnish non-shrink grout for applications in grout category in the following schedule:
Application
Filling tie hole
Machine bases 25 hp or less
Through-bolt openings
Project No. 12078390
Durant State Fish Hatchery Phase 1
Temperature
Range
40 to 100 F
I
II
II
3
II
III
III
II
III
III
II
III
III
II
II
II
NONSHRINK GROUT
A.
Category I:
1.
Nonmetallic and non gas-liberating.
2.
Prepackaged natural aggregate grout requiring only the addition of water.
3.
Test in accordance with ASTM C1107:
a.
Flowable consistency 140%, five drops in 30 seconds, in accordance with ASTM C
230.
b.
Flowable for 15 minutes.
4.
Grout shall not bleed at maximum allowed water.
5.
Minimum strength of flowable grout, 3,000 psi at 3 days, 5,000 psi at 7 days, and 7,000
psi at 28 days.
6.
Manufacturers and Products:
a.
Chemrex, Inc., Shakopee, MN; Set Grout.
b.
Euclid Chemical Co., Cleveland, OH; NS Grout.
c.
Dayton Superior Corp., Miamisburg, OH; 1107 Advantage Grout.
d.
US MIX Products, Denver, CO; US Spec Multi-Purpose Grout.
e.
L & M Construction Chemicals, Inc., Omaha, NE; Duragrout.
f.
Master Builders.
B.
Category II:
1.
Nonmetallic, non gas-liberating.
2.
Prepackaged natural aggregate grout requiring only the addition of water.
3.
Aggregate shall show no segregation or settlement at fluid consistency - at specified
times or temperatures.
4.
Test in accordance with COE CRD-C 621 and ASTM C 1107, Grade B:
a.
Fluid consistency 20 to 30 seconds in accordance with COE CRD-C 611.
b.
Temperatures of 40, 80, and 100 F.
5.
1 hour after mixing, pass fluid grout through flow cone with continuous flow.
6.
Minimum strength of fluid grout, 3,500 psi at 1 day, 4,500 psi at 3 days, and 7,500 psi at
28 days.
7.
Maintain fluid consistency when mixed in 1 to 9 yard loads in ready- mix truck.
8.
Manufacturers and Products:
a.
Chemrex, Inc., Shakopee, MN; Master Flow 928.
b.
Five Star Products Inc., Fairfield, CT; Five Star 100.
c.
Euclid Chemical Co., Cleveland, OH; Hi Flow Grout.
d.
Dayton Superior Corp., Miamisburg, OH; Sure Grip High Performance Grout.
e.
L & M Construction Chemicals, Inc., Omaha, NE; Crystex.
f.
Master Builders.
C.
Category III
1.
Metallic and nongas-liberating flowable fluid.
2.
Prepackaged aggregate grout requiring only the addition of water.
3.
Aggregate shall show no segregation or settlement at fluid consistency at specified times
or temperatures.
4.
Test in accordance with CRD-C 621 and ASTM C 1107, Grade B:
a.
Fluid consistency 20 to 30 seconds in accordance with CRD-C 611.
b.
Temperatures of 40 and 100 F.
5.
1 hour after mixing, pass fluid grout through flow cone with continuous flow.
Section 03 60 00
Grout
6.
7.
8.
2.5
Minimum strength of grout, 4,000 psi at 1 day, 5,000 psi at 3 days, and 9,000 psi at 28
days.
Maintain fluid consistency when mixed in 1 to 9 yard loads in ready-mix truck.
Manufacturers and Products: Chemrex, Inc., Shakopee, MN; EMBECO 885.
Where fill is thicker than 3-inches, structural concrete 03 30 00, CAST-IN-PLACE CONCRETE,
may be used when accepted by the Engineer.
B.
Grout for topping of slabs and concrete/grout fill for built-up surfaces of tank, channel and basin
bottoms shall be composed of cement, fine aggregate, coarse aggregate, water and admixtures
proportioned and be mixed as indicated. Bonding Agent shall be used to enhance adhesion to
basin concrete. Materials and procedures indicated for normal concrete in Section 03 30 00,
CAST-IN-PLACE CONCRETE, shall apply unless indicated otherwise.
C.
Topping grout and concrete/grout fill shall contain a minimum of 564 pounds of cement per
cubic yard with a maximum water cement ratio of 0.45.
D.
E.
Final mix design shall be as determined by trial mix design as indicated in Section 03 30 00,
except that drying shrinkage tests are not required.
F.
Topping grout and concrete grout/fill shall contain air-entraining agent per Section 03 30 00.
G.
Strength: Minimum compressive strength of topping grout and concrete/grout fill at 28 days shall
be 4,000 psi.
H.
Topping grout used in clarifiers shall contain fiber reinforcing. Fiber shall be 100 percent virgin
polypropylene fibrillated fibers specifically manufactured in a blended gradation for use as
concrete secondary reinforcement. Fibers shall be added at a rate of 1.5 pounds per cubic yard
of concrete. Fibers shall conform to ASTM C 1116 Fiber Reinforced Concrete and Shotcrete.
Type III.
2.6
Prepare design mixture proportioned on the basis of laboratory trial mixture or field test data, or
both, according to ACI 301. Submit proposed mixture design to Engineer for review. Comply
with Section 03 30 00 Cast-In-Place Concrete and as follows.
1.
Use a qualified independent testing agency for preparing and reporting proposed mixture
designs based upon laboratory trial mixtures.
B.
Section 03 60 00
Grout
1.
C.
Admixtures: All materials other than Portland cement, water and aggregates that are added to
the concrete or cement grout, shall be subject to the approval of the Engineer. If so approved,
use admixtures according to manufacturers written instructions.
1.
Use water reducing, high-range water-reducing or plasticizing admixture in concrete, as
required, for placement and workability.
2.
Use water-reducing and retarding admixture when required by high temperatures, low
humidity, or other adverse placement conditions.
3.
Use water-reducing admixture in pumped concrete, concrete for heavy-use slabs,
concrete required to be watertight, and concrete with a water-cementitious materials ratio
below 0.50.
D.
E.
Air content: ASTM C 94, 5 percent, plus or minus 1.0 percent at point of delivery.
F.
Aggregate shall be sand, three parts sand to one part cementitious material by volume. The
sand gradation shall be such that 100% shall pass the No. 16 sieve and not more than 30%
shall be retained on a No. 30 sieve.
G.
Water cementitious material ratio. The Contractor shall submit a proposed mix design to the
Engineer for review. The amount of water shall be the minimum amount of water necessary to
make a workable mixture.
H.
2.7
Joint Mortar Bed: Mortar placed on horizontal construction joints shall be a mixture of cement,
sand and water in the same proportions used in the approved 4,500 psi cast-in-place concrete
mix design and/but with the coarse aggregate omitted.
PART 3 - EXECUTION
3.1
NONSHRINK GROUT
A.
General: Mix, place, and cure non-shrink grout in accordance with grout Manufacturers
representatives training instructions.
B.
Form Tie or Through-Bolt Holes: Provide non-shrink grout, Category I and II, fill space with dry
pack dense grout hammered in with steel tool and hammer. Through-bolt holes; coordinate dry
pack dense grout application with vinyl plug in Section 03 11 00, CONCRETE FORMWORK,
and bonding agent in Section 03 30 00, CAST-IN-PLACE CONCRETE.
C.
Section 03 60 00
Grout
3.2
CEMENT GROUT
A.
Place cement grout topping over concrete slabs where indicated on the drawings. Place in
accordance with the procedures of this section and the manufacturers or suppliers of
equipment recommendations. The finish surface of the grout topping shall be similar to a steel
trowel finish and which will facilitate the proper operation of the mechanical equipment. The
finish of the structural slab below the cement grout topping shall be a heavy broom finish.
B.
Where cement grout is to be placed without mechanical equipment, the fresh surface of the
cement grout shall be a smooth trowel finish. Placement procedure of cement grout at areas
with mechanical equipment includes:
1.
Notify Project Representative or Engineer a minimum of 48 hours in advance of
placement.
2.
Make a trial cement grout batch of not less than 1/2 cubic yard to allow time for
adjustment in mix design if required.
3.
Clean the exposed structural slab by sandblasting and washing clean.
4.
Thoroughly broom a neat cement paste containing an epoxy binder into the concrete slab
surface immediately ahead of placing the cement grout topping.
5.
Where applicable, install level and trial operate mechanical screed equipment over the
floor slab to provide a minimum thickness of 2 inches +/- 1/4 inch. In areas where the
distance between the mechanical screed and the structural slab is less than the above
clearances, grind surface as directed by Engineer to provide such clearance. The
mechanical screed shall operate at a speed acceptable to the cement grout topping
placement procedures. Screeding procedures shall account for the effects of differential
temperatures on the mechanical screed equipment.
6.
Place cement grout topping in a continuous operation. If grouting operations are
interrupted, clean the edge of the previously placed topping by water jetting and add a
coat of cement paste to provide a bond to the fresh topping.
7.
Temporarily equip the mechanical screed mechanism on at least two arms with a 2-inch
by 10 inch continuous wood plate with light gauge metal angles and surface plates or
channels. The bottom of the screed plates or steel plates shall be adjustable and set to
elevations which allow the proper operation of equipment and as recommended by the
equipment manufacturer or supplier.
8.
Screed the topping immediately after consolidation with vibrators or tampers and provide
a steel trowel finish.
9.
Cure cement grout topping with water and cover with PVC sheeting to prevent damage
from foot traffic for seven days. When/If the cement grout topping is found not to be
acceptable, remove and replace. Cement grout topping not acceptable shall include, but
is not limited to, poor bonding with the concrete slab, low strength, excessive cracking
and unevenness in finish or elevation.
3.3
3.4
Joint Mortar Bed: Immediately prior to placement of fresh concrete at horizontal joints, or as
indicated, place joint mortar bed to cover horizontal joint and protect water stop as applicable.
Spread uniformly and work into all irregularities of the surface. The water cement ratio of the
joint mortar bed shall not exceed that of the concrete being placed and the consistency of the
mortar shall be suitable for placing and working. The fresh concrete shall then be immediately
placed in a time and manner so that the joint mortar bed and the fresh concrete mix to form a
homogenous concrete meeting all requirements.
NON-SHRINK GROUT
A.
Non-Shrink grout:
1.
Used for repair of holes and defects and at locations indicated where epoxy grout is not
indicated. Execution shall follow manufacturers recommendations.
Section 03 60 00
Grout
2.
3.5
Base plates and equipment where indicated. Execution shall follow manufacturers
recommendations.
EPOXY GROUT
A.
3.6
Epoxy Grout: Used to embed all anchor bolts and reinforcing steel set in grout, specific
machinery base plates as indicated and at other locations where indicated. Execution shall
follow manufacturers recommendations.
FIELD QUALITY CONTROL
A.
3.7
A.
3.8
General: Coordinate demonstrations, training sessions, and applicable site visits with grout
manufacturers representative.
SUPPLEMENTS
A.
The supplement listed below, following END OF SECTION, is part of this Specification.
1.
24-hour Evaluation of Non-shrink Grout Test Form and Grout Testing Procedures.
END OF SECTION
Section 03 60 00
Grout
SUPPLEMENT 1
(Test Lab Name)
(Address)
(Phone No.)
24-HOUR EVALUATION OF NONSHRINK GROUT TEST FORM
OBJECTIVE:
SCOPE:
PRIOR TO TEST:
ANSWER THE FOLLOWING QUESTIONS FOR GROUT BEING TESTED FROM LITERATURE, DATA,
AND PRINTING ON BAG:
A.
Yes_____ No_____
B.
Yes_____ No_____
C.
Yes_____ No_____
D.
E.
Yes_____ No_____
F.
Yes_____ No_____
G.
Yes_____ No_____
*Rejection of a grout will occur if one or more answers are noted NO.
1 of 3
03 60 00 Supplement
Grout
Bagged Material:
1.
2.
3.
ENGINEER will disqualify grout if bag weights have misstated measure plus or minus 2 pounds
by more than one out of five bags. (Accuracy of weights is required to regulate amount of water
used in mixing since this will affect properties.)
B.
2.
Use electric drill with a paddle device to mix grout (jiffy or jiffler type paddle).
3.
Use maximum water allowed per water requirements listed in bag instructions.
4.
5.
In accordance with COE CRD-C611 (flow cone) determine time of mixed grout through
the flow cone. __________ seconds
6.
7.
Record time of grout through cone at new water demand. _______ seconds
8.
9.
C.
When fluid grout is specified and additional water is required beyond grout manufacturers listed
maximum water, COE CRD-C621 will be run at new water per grout ratio to determine whether
grout passes using actual water requirements to be fluid. Use new water per grout ratio on
remaining tests.
D.
Bleed Test:
E.
1.
Fill two gallon cans half full of freshly mixed grout at ambient temperatures for each
category and at required consistency for each.
2.
Place one can of grout in tub of ice water and leave one can at ambient temperature.
3.
Cover top of both cans with glass or plastic plate preventing evaporation.
4.
Maintain 38 to 42 degrees F temperature with grout placed in ice and maintain ambient
temperature for second container for 1 hour.
5.
6.
7.
Extended Flow Time and Segregation Test (for Category II and III):
1.
Divide the remaining grout into two 3 gallon cans. Place the cans into the 40 F and 100
F containers and leave for 20, 40, and 60 minutes. Every 20 minutes remove and check
for segregation or settlement of aggregate. Use a gloved hand to reach to the bottom of
the can, if more than 1/4-inch of aggregate has settled to the bottom or aggregate has
segregated into clumps reject the grout.
2 of 3
03 60 00 Supplement
Grout
2.
Right after the settlement test mix the grout with the drill mixer for 10 seconds.
Take a COE CRD-C611 flow cone test of grout and record flow time. Maintain
this process for 1 hour at ambient temperatures of 40 and 100 degrees F.
a.
b.
c.
d.
e.
f.
All Category II and III grout that will not go through the flow cone with continuous
flow after 60 minutes will be disqualified.
F.
____________
____________
Qualified
Disqualified
Using grout left in mixing cans in accordance with COE CRD-C621 for mixing and
consistency determination test and for extended time flow test, make minimum of nine
cube samples.
2.
3.
Grout will be disqualified if 24-hour compressive strengths are under 2,500 psi for grouts claiming
fluid placement capabilities.
Grouts that have not been disqualified after these tests are qualified for use on the Project for the
application indicated in Nonshrink Grout Schedule.
3 of 3
03 60 00 Supplement
Grout
SUMMARY
A.
Section Includes:
1.
Epoxy injection system.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 Cast-In-Place Concrete.
1.2
REFERENCES
A.
1.3
A.
B.
1.4
SUBMITTALS
A.
Shop Drawings:
1.
Physical and chemical properties for epoxy adhesives.
2.
Technical data for metering, mixing, and injection equipment.
B.
Information Submittals:
1.
Manufacturers recommended surface preparation procedures and application
instructions for epoxy adhesives.
2.
Installation instructions for repairing core holes with epoxy grout.
3.
Manufacturers Certificate of Compliance: Certified test results for each batch of epoxy
adhesive.
4.
Statements of Qualification for Epoxy Adhesive:
a.
Manufacturers site representative.
b.
Injection applicator.
c.
Injection pump operating technician.
Section 03 64 00
Concrete Repair Crack Injection
5.
1.5
Epoxy adhesive two component ratio and injection pressure test records for concrete
crack repair work.
QUALITY ASSURANCE
A.
1.6
A.
Packing and Shipping: Package adhesive material in new sealed containers and
following information:
1.
Manufacturers name.
2.
Product name and lot number.
3.
ANSI Hazard Classification (formerly SPI Classification).
4.
ANSI recommended precautions for handling.
5.
Mix ratio by volume.
label
with
B.
Storage and Protection: Store adhesive containers at ambient temperatures below 120 F and
above 32 F.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
A.
Two-component A and B structural epoxy adhesive for injection into cracks or other voids in
concrete structures for bonding or grouting.
B.
Adhesive Properties: When cured for 7 days at 77, 3 F and conditioned at test temperature 12
hours prior to test, unless otherwise specified.
Test Method
ASTM D638
ASTM D638
Large Cracks
8,000 min.
3.7 max.
Small Cracks
5,000 min.
3.7 max.
ASTM D790
ASTM D790
10,000 min.
5
5.5 x10 min.
10,000 min.
5
4.5 x10 min.
Section 03 64 00
Concrete Repair Crack Injection
2.3
SURFACE SEAL
A.
Sufficient strength and adhesion for holding injection fittings firmly in-place, and to resist
pressures preventing leakage during injection.
B.
PART 3 - EXECUTION
3.1
GENERAL
A.
B.
3.2
PREPARATION
A.
Free cracks from loose matter, dirt, laitance, oil, grease, salt, and other contaminants.
B.
C.
Clean surfaces adjacent to cracks from dirt, dust, grease, oil, efflorescence, and other foreign
matter detrimental to bond of surface seal system.
D.
Do not use acids and corrosives for cleaning, unless neutralized prior to injecting epoxy.
3.3
APPLICATION
A.
Sealing: Apply surface seal in accordance with Manufacturers instructions to designated crack
face prior to injection. Seal surface of crack to prevent escape of injection epoxy.
B.
Entry Ports:
1.
Establish openings for epoxy entry in surface seal along crack.
2.
Determine space between entry ports equal to thickness of concrete member to allow
epoxy to penetrate to the full thickness of the wall.
3.
Provide a means to prevent concrete dusts and fines from contaminating the crack or
ports when drilling.
4.
Space entry ports close together to allow adjustment of injection pressure
to
obtain
minimum loss of epoxy to soil at locations where:
a.
Cracks extend entirely through wall.
Section 03 64 00
Concrete Repair Crack Injection
5.
b.
Backfill of walls on one side.
c.
Difficult to excavate behind wall to seal both crack surfaces.
Core drill to verify epoxy depth where only one side of wall is exposed.
C.
Epoxy Injection:
1.
Store epoxy at minimum of 70 F.
2.
Start injection into each crack at lowest elevation entry port.
3.
Continue injection at first port until adhesive begins to flow out of port at next highest
elevation.
4.
Plug first port and start injection at second port until adhesive flows from next port.
5.
Inject entire crack with same sequence.
D.
Finishing:
1.
Cure epoxy adhesive after cracks have been completely filled to allow surface seal
removal without draining or runback of epoxy material from cracks.
2.
Remove surface seal from cured injection adhesive.
3.
Finish crack face flush with adjacent concrete.
4.
Indentations or protrusions caused by placement of entry ports are not acceptable.
5.
Remove surface seal material and injection adhesive runs and spills from concrete
surfaces.
3.4
EQUIPMENT
A.
Portable, positive displacement type pumps with in-line metering to meter and mix two adhesive
components, and inject mixture into crack.
B.
C.
Automatic Shutoff Control: Provide sensors on both Component A and B reservoirs for stopping
machine automatically when only one component is being pumped to mixing head.
D.
Proportioning Ratio Tolerance: Maintain epoxy adhesive Manufacturers prescribed mix ratio
within a tolerance of 5% by volume at discharge pressure p to 160 psi.
E.
3.5
Section 03 64 00
Concrete Repair Crack Injection
B.
C.
END OF SECTION
Section 03 64 00
Concrete Repair Crack Injection
DIVISION 05
METALS
SUMMARY
A.
Section Includes:
1.
Structural steel.
B.
Related Sections :
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 31 00 Project Management and Coordination.
b.
Section 01 31 19 Project Meetings.
c.
Section 05 50 00 Metal Fabrications, for steel lintels or shelf angles not attached
to structural-steel frame, miscellaneous steel fabrications, and other metal items
not defined as structural steel.
d.
Section 09 90 00 Painting and Protective Coatings, for surface preparation and
priming requirements.
1.2
DEFINITIONS
A.
1.3
A.
B.
C.
Welding certificates.
D.
E.
Mill Test Reports: Signed by Manufacturers certifying that the following products comply with
requirements:
1.
Structural steel including chemical and physical properties.
2.
Bolts, nuts, and washers including mechanical properties and chemical analysis.
3.
Shop primers.
F.
Section 05 12 00
Structural Steel
1.4
QUALITY ASSURANCE
A.
Installer Qualifications: A qualified installer who regularly erects structural steel with scope and
complexity similar to that of this project.
B.
Fabricator Qualifications: A qualified fabricator who regularly fabricates structural steel with
scope and complexity similar to that of this project.
C.
Welding: Qualify procedures and personnel according to AWS D1.1, Structural Welding Code-Steel.
D.
E.
1.5
1.6
Store materials to permit easy access for inspection and identification. Keep steel members off
ground and spaced by using pallets, dunnage, or other supports and spacers. Protect steel
members and packaged materials from erosion and deterioration.
1.
Store fasteners in a protected place. Re-lubricate bolts and nuts that become dry.
2.
Do not store materials on structure in a manner that might cause distortion, damage, or
overload to members or supporting structures. Repair or replace damaged materials or
structures as directed.
3.
Do not clean and use rusty bolts.
COORDINATION
A.
PART 2 - PRODUCTS
2.1
STRUCTURAL-STEEL MATERIALS
A.
B.
C.
D.
E.
Section 05 12 00
Structural Steel
2.
F.
2.2
Welding Electrodes: Comply with AWS requirements. Tensile strength should be the same or
greater than base metal.
BOLTS, CONNECTORS, AND ANCHORS
A.
High-Strength Bolts, Nuts, and Washers: ASTM A 325 Type 1, heavy hex steel structural bolts;
ASTM A 563 heavy hex carbon steel nuts; and ASTM F 436 hardened carbon-steel washers.
1.
Finish: Plain unless noted or indicated otherwise.
B.
Headed and Un-headed Anchor Rods: ASTM F 1554, Grade 36, unless otherwise indicated.
1.
Configuration: as indicated.
2.
Nuts: ASTM A 563, heavy hex carbon steel.
3.
Plate Washers: ASTM A 36 carbon steel.
4.
Washers: ASTM F 436, hardened carbon steel.
5.
Finish: Plain, unless noted or indicated otherwise.
C.
D.
E.
Eye Bolts and Nuts: ASTM A 108, Grade 1030, cold-finished carbon steel.
F.
2.3
PRIMER
A.
Primer: Fabricators standard lead and chromate free non-asphaltic rust inhibiting primer.
B.
2.4
FABRICATION
A.
Structural Steel: Fabricate and assemble in shop to greatest extent possible. Fabricate
according to AISC Code of Standard Practice for Steel Buildings and Bridges and AISC
Specification for Structural Steel Buildings--Allowable Stress Design and Plastic Design.
1.
Camber structural-steel members where indicated.
2.
Identify high-strength structural steel according to ASTM A 6 and maintain markings until
structural steel has been erected.
3.
Mark and match-mark materials for field assembly.
4.
Complete structural-steel assemblies, including welding of units, before starting shoppriming operations.
B.
C.
Bolt Holes: Cut, drill, or punch standard bolt holes perpendicular to metal surfaces.
D.
Finishing: Accurately finish ends of columns and other members transmitting bearing loads.
Section 05 12 00
Structural Steel
E.
Cleaning: Clean and prepare steel surfaces that are to remain unpainted according to SSPC-SP
3, Power Tool Cleaning.
F.
Steel Wall-Opening Framing: Select true and straight members for fabricating steel wall-opening
framing to be attached to structural steel. Straighten as required to provide uniform, square, and
true members in completed wall framing.
G.
Welded Door Frames: Build up welded door frames attached to structural steel. Weld exposed
joints continuously and grind smooth. Plug-weld fixed steel bar stops to frames. Secure
removable stops to frames with countersunk, cross-recessed head machine screws, uniformly
spaced not more than 10 o.c., unless otherwise indicated.
H.
Holes: Provide holes required for securing other work to structural steel and for passage of
other work through steel framing members.
1.
Cut, drill, or punch holes perpendicular to steel surfaces.
2.
Base-Plate Holes: Cut, drill, or punch holes perpendicular to steel surfaces.
3.
Weld threaded nuts to framing and other specialty items indicated to receive other work.
2.5
SHOP CONNECTIONS
A.
High-Strength Bolts: Shop install high-strength bolts according to RCSC Specification for
Structural Joints Using ASTM A 325 or A 490 Bolts for type of bolt and type of joint specified.
1.
Joint Type: Snug tightened.
B.
Weld Connections: Comply with AWS D1.1 for welding procedure specifications, tolerances,
appearance, and quality of welds and for methods used in correcting welding work.
1.
Remove backing bars or runoff tabs, back gouge, and grind steel smooth.
2.
Assemble and weld built-up sections by methods that will maintain true alignment of axes
without exceeding tolerances of AISC Code of Standard Practice for Steel Buildings and
Bridges for mill material.
2.6
SHOP PRIMING
A.
B.
Surface Preparation: Clean the surfaces to be painted. Remove loose rust and mill scale and
spatter, slag, or flux deposits. Prepare surfaces according to the following specifications and
standards:
1.
SSPC-SP 3, Power Tool Cleaning.
C.
Priming: Immediately after surface preparation, apply primer according to Manufacturers written
instructions and at rate recommended by SSPC to provide a dry film thickness of not less than
1.5 mils. Use priming methods that result in full coverage of joints, corners, edges, and exposed
surfaces.
1.
Stripe paint comers, crevices, bolts, welds, and sharp edges.
2.
Apply two coats of shop paint to inaccessible surfaces after assembly or erection.
Change color of second coat to distinguish it from first.
Section 05 12 00
Structural Steel
D.
2.7
Painting: Apply a 1-coat, non-asphaltic primer complying with SSPC-PS Guide 7.00, Painting
System Guide 7.00: Guide for Selecting One-Coat Shop Painting Systems, to provide a dry film
thickness of not less than 1.5 mils.
GALVANIZING
A.
Hot-Dip Galvanized Finish: Apply zinc coating by the hot-dip process to structural steel
according to ASTM A 123.
1.
Fill vent holes and grind smooth after galvanizing.
2.
Galvanize lintels and shelf angles attached to structural-steel frame and located in
exterior walls.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Verify elevations of concrete- and masonry-bearing surfaces and locations of anchor rods,
bearing plates, and other embedment, with steel erector present, for compliance with
requirements.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
PREPARATION
A.
3.3
Provide temporary shores, guys, braces, and other supports during erection to keep structural
steel secure, plumb, and in alignment against temporary construction loads and loads equal in
intensity to design loads. Remove temporary supports when permanent structural steel,
connections, and bracing are in place, unless otherwise indicated.
1.
Do not remove temporary shoring supporting composite deck construction until cast-inplace concrete has attained its design compressive strength.
ERECTION
A.
Set structural steel accurately in locations and to elevations indicated and according to AISC
Code of Standard Practice for Steel Buildings and Bridges and Specification for Structural
Steel Buildings--Allowable Stress Design and Plastic Design.
B.
Base and Bearing Plates: Clean concrete- and masonry-bearing surfaces of bond-reducing
materials, and roughen surfaces prior to setting base and bearing plates. Clean bottom surface
of base and bearing plates.
1.
Set base and bearing plates for structural members on wedges, shims, or setting nuts as
required.
2.
Weld plate washers to top of base plate.
3.
Snug-tighten anchor rods after supported members have been positioned and plumbed.
Do not remove wedges or shims but, if protruding, cut off flush with edge of base or
bearing plate before packing with grout.
4.
Promptly pack grout solidly between bearing surfaces and base or bearing; plates so no
voids remain. Neatly finish exposed surfaces; protect grout and allow it to cure. Comply
with Manufacturers written installation instructions for shrinkage-resistant grouts.
C.
Maintain erection tolerances of structural steel within AISC Code of Standard Practice for Steel
Buildings and Bridges.
D.
Align and adjust various members forming part of complete frame or structure before
permanently fastening. Before assembly clean bearing surfaces and other surfaces that will be
Section 05 12 00
Structural Steel
F.
Do not use thermal cutting during erection unless approved by Engineer. Finish thermally cut
sections within smoothness limits in AWS D1.1.
G.
Do not enlarge unfair holes in members by burning or using drift pins. Ream holes that must be
enlarged to admit bolts.
3.4
FIELD CONNECTIONS
A.
High-Strength Bolts: Install high-strength bolts according to RCSC Specification for Structural
Joints Using ASTM A 325 or A 490 Bolts for type of bolt and type of joint specified.
1.
Joint Type: Snug tightened, unless noted or indicated otherwise.
B.
Weld Connections: Comply with AWS D1.1 for welding procedure specifications, tolerances,
appearance, and quality of welds and for methods used in correcting welding work.
1.
Comply with AISC Code of Standard Practice for Steel Buildings and Bridges and
Specification for Structural Steel Buildings--Allowable Stress Design and Plastic Design,
for bearing, adequacy of temporary connections, alignment, and removal of paint on
surfaces adjacent to field welds.
2.
Remove backing bars or runoff tabs, back gouge, and grind steel smooth.
3.
Assemble and weld built-up sections by methods that will maintain true alignment of axes
without exceeding tolerances of AISC Code of Standard Practice for Steel Buildings and
Bridges for mill material.
3.5
Testing Agency: Owner will engage a qualified independent testing and inspecting agency to
inspect field welds and high-strength bolted connections.
B.
Bolted Connections: Shop-bolted connections will be tested and inspected according to RCSC
Specification for Structural Joints Using ASTM A 325 or A 490 Bolts.
C.
Welded Connections: Field welds will be visually inspected according to AWS D1.1.
D.
Correct deficiencies in Work that test reports and inspections indicate does not comply with the
Contract Documents.
3.6
Repair damaged galvanized coatings on galvanized items with galvanized repair paint
according to ASTM A 780 and Manufacturers written instructions.
B.
Touchup Painting: After installation, promptly clean, prepare, and prime or re-prime field
connections, rust spots, and abraded surfaces of prime-painted joists and accessories, bearing
plates, and abutting structural steel.
1.
Clean and prepare surfaces by SSPC-SP 2 hand-tool cleaning or SSPC-SP 3 power-tool
cleaning.
2.
Apply a compatible primer of same type as shop primer used on adjacent surfaces.
Section 05 12 00
Structural Steel
C.
Touchup Painting: Cleaning and touchup painting are specified in Section 09 90 00, PAINTING
AND PROTECTIVE COATINGS.
END OF SECTION
Section 05 12 00
Structural Steel
SUMMARY
A.
Section Includes:
1.
Steel framing and supports for overhead doors.
2.
Steel framing and supports for mechanical and electrical equipment.
3.
Steel framing and supports for applications where framing and supports are not specified
in other Sections.
4.
Shelf angles.
5.
Loose bearing and leveling plates.
6.
Steel welded plates and angles for casting into concrete not specified in other Sections.
7.
Miscellaneous steel trim including steel angle corner guards and steel edgings.
8.
Metal ladders.
9.
Metal bollards.
10.
Pipe guards.
11.
Metal floor plate and supports.
12.
Abrasive metal nosing, treads, and thresholds.
B.
Products furnished, but not installed, under this Section include the following:
1.
Loose steel lintels.
2.
Anchor bolts, steel pipe sleeves, and wedge-type inserts indicated to be cast into
concrete or built into unit masonry.
C.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 Cast-In-Place Concrete, for installing anchor bolts, steel pipe
sleeves, wedge-type inserts and other items indicated to be cast into concrete.
b.
Section 05 12 00 Structural Steel.
c.
Section 05 51 00 Metal Stairs.
d.
Section 05 52 13 Pipe and Tube Railings.
e.
Section 05 53 00 Metal Gratings and Plank.
f.
Section 07 92 00 Joint Sealants.
g.
Section 09 90 00 Painting and Protective Coatings.
1.2
PERFORMANCE REQUIREMENTS
A.
Structural Performance of Ladders: Provide ladders capable of withstanding the effects of loads
and stresses within limits and under conditions specified in ANSI A14.3.
B.
Thermal Movements: Provide exterior metal fabrications that allow for thermal movements
resulting from the following maximum change (range) in ambient and surface temperatures by
preventing buckling, opening of joints, overstressing of components, failure of connections, and
other detrimental effects. Base engineering calculations on surface temperatures of materials
due to both solar heat gain and nighttime-sky heat loss.
1.
Temperature Change (Range): 120 F, ambient; 180 F, material surfaces.
Section 05 50 00
Metal Fabrications
1.3
SUBMITTALS
A.
B.
Shop Drawings: Show fabrication and installation details for metal fabrications.
1.
Include plans, elevations, sections, and details of metal fabrications and their
connections. Show anchorage and accessory items.
2.
Provide templates for anchors and bolts specified for installation under other Sections.
3.
For installed products indicated to comply with design loads, include structural analysis
data signed and sealed by the qualified professional engineer responsible for their
preparation.
C.
Samples for Verification: For each type and finish of extruded nosing and tread.
D.
E.
Welding certificates.
1.4
QUALITY ASSURANCE
A.
1.5
A.
1.6
Field Measurements: Verify actual locations of walls and other construction contiguous with
metal fabrications by field measurements before fabrication and indicate measurements on
Shop Drawings.
1.
Established Dimensions: Where field measurements cannot be made without delaying
the Work, establish dimensions and proceed with fabricating metal fabrications without
field measurements. Coordinate wall and other contiguous construction to ensure that
actual dimensions correspond to established dimensions.
2.
Provide allowance for trimming and fitting at site.
COORDINATION
A.
B.
Coordinate installation of steel weld plates and angles for casting into concrete that are
specified in this Section but required for work of another Section. Deliver such items to Project
site in time for installation.
Section 05 50 00
Metal Fabrications
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1.
Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, products specified.
2.
Available Manufacturers: Subject to compliance with requirements, Manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
manufacturers specified.
METALS, GENERAL
A.
Metal Surfaces, General: Provide materials with smooth, flat surfaces, unless otherwise
indicated. For metal fabrications exposed to view in the completed Work, provide materials
without seam marks, roller marks, rolled trade names, or blemishes.
B.
Ferrous Metals
1.
Steel Plates, Shapes, and Bars: ASTM A 36.
2.
Stainless-Steel Sheet, Strip, Plate, and Flat Bars: ASTM A 666, Type 304 or 316.
3.
Stainless-Steel Bars and Shapes: ASTM A 276, Type 304 or 316.
4.
Steel Tubing: ASTM A 500, cold-formed steel tubing.
5.
Steel Pipe: ASTM A 53, standard weight (Schedule 40), unless another weight is
indicated or required by structural loads.
6.
Cast Iron: ASTM A 48, Class 30, unless another class is indicated or required by
structural loads.
C.
Nonferrous Metals
1.
Aluminum Plate and Sheet: ASTM B 209, Alloy 6061-T6.
2.
Aluminum Extrusions: ASTM B 221, Alloy 6061-T6.
3.
Aluminum-Alloy Rolled Tread Plate: ASTM B 632, Alloy 6061-T6.
4.
Aluminum Castings: ASTM B 26, Alloy 443.0-F.
2.3
FASTENERS
A.
General: Unless otherwise indicated, provide Type, 304 or 316 stainless-steel fasteners for
exterior use and zinc-plated fasteners with coating complying with ASTM B 633, Class Fe/Zn 5,
at exterior walls. Provide stainless-steel fasteners for fastening aluminum. Select fasteners for
type, grade, and class required.
B.
Steel Bolts and Nuts: Regular hexagon-head bolts, ASTM A 307, Grade A, with hex nuts, ASTM
A 563; and, where indicated, flat washers.
1.
Finish: Plain or Hot Dip Zinc-coated ASTM A153 Class C, as indicated.
C.
Stainless-Steel Bolts and Nuts: Regular hexagon-head annealed stainless-steel bolts, nuts and,
where indicated, flat washers; ASTM F 593, AISI Type 316, Condition CW for bolts and ASTM F
594 for AISI Type 316, Condition CW nuts.
1.
All threads on stainless steel rods/bolts shall be protected with anti-seize lubricant
suitable for submerged stainless bolts and complying with Federal Specification MIL-A907E.
D.
Anchor Bolts: ASTM F 1554, Grade 36 or Grade 55, as required or shown on the drawings.
1.
Provide hot-dip or mechanically deposited, zinc-coated anchor bolts where item being
fastened is indicated to be galvanized.
Section 05 50 00
Metal Fabrications
E.
F.
G.
H.
I.
J.
Cast-in-Place Anchors in Concrete: Anchors capable of sustaining, without failure, a load equal
to four times the load imposed, as determined by testing according to ASTM E 488, conducted
by a qualified independent testing agency.
1.
Threaded or wedge type; galvanized ferrous castings either: ASTM A 47 malleable iron
or ASTM A 27, cast steel. Provide bolts, washers, and shims as needed, hot-dip
galvanized per ASTM A 153.
K.
Expansion Anchors: Anchor bolt and sleeve assembly with capability to sustain, without failure,
a load equal to six times the load imposed when installed in unit masonry and four times the
load imposed when installed in concrete, as determined by testing according to ASTM E 488,
conducted by a qualified independent testing agency.
1.
Material for Anchors in Interior Locations: Carbon-steel components zinc-plated to
comply with ASTM B 633, Class Fe/Zn 5.
2.
Material for Anchors in Exterior Locations: ASTM F 593, AISI Type 316, Condition CW for
bolts and ASTM F 594 for AISI Type 316, Condition CW nuts.
3.
Expansion anchors shall not be substituted for adhesive anchors.
L.
Adhesive Anchors:
1.
Threaded Rod:
a.
ASTM F 593 stainless steel threaded rod, diameter as shown on Drawings.
b.
Length as required to provide minimum depth of embedment.
c.
Clean and fee of grease, oil, or other deleterious material.
d.
For hollow-unit masonry, provide galvanized or stainless steel wire cloth screen
tube to fit threaded rod.
2.
Adhesive:
a.
Two-component, insensitive to moisture, designed to be used in adverse
freeze/thaw environments, with gray color after mixing.
b.
Cure Temperature, Pot Life, and Workability: Compatible for intended use and
environmental conditions.
c.
Nonsag, with selected viscosity based on installation temperature and overhead
application where applicable.
d.
HILTI HIT HY-200 or approved equal.
3.
Packaging:
a.
Disposable, self-contained cartridge system capable of dispensing both
components in the proper mixing ratio and fitting into a manually or pneumatically
operated caulking gun.
b.
Cartridge Marking: Include manufacturers name, product name, material type,
batch serial number, and adhesive expiration date.
4.
Manufacturers and Products:
a.
Hilti, Inc.
1)
HIT-HY 200 for concrete.
2)
HIT-HY 70 for hollow and grout-filled masonry.
b.
Or Approved Equal.
1)
It is the contractors responsibility to provide sufficient documentation so that
the Engineer may determine if the submitted product meets or exceeds the
Section 05 50 00
Metal Fabrications
MISCELLANEOUS MATERIALS
A.
Welding Rods and Bare Electrodes: Select according to AWS specifications for metal alloy
welded.
B.
C.
Universal Shop Primer: Fast-curing, lead- and chromate-free, universal modified-alkyd primer
complying with MPI#79.
1.
Use primer with a VOC content of 420 g/L (3.5 lb/gal.), or less when calculated according
to 40 CFR 59, Subpart D (EPA Method 24).
2.
Use primer containing pigments that make it easily distinguishable from zinc-rich primer.
D.
E.
F.
2.5
FABRICATION, GENERAL
A.
Shop Assembly: Preassemble items in the shop to greatest extent possible. Disassemble units
only as necessary for shipping and handling limitations. Use connections that maintain
structural value of joined pieces. Clearly mark units for reassembly and coordinated installation.
B.
Cut, drill, and punch metals cleanly and accurately. Remove burrs and ease edges to a radius
of approximately 1/32, unless otherwise indicated. Remove sharp or rough areas on exposed
surfaces.
C.
Form bent-metal comers to smallest radius possible without causing grain separation or
otherwise impairing work.
D.
Form exposed work true to line and level with accurate angles and surfaces and straight edges.
E.
Section 05 50 00
Metal Fabrications
4.
At exposed connections, finish exposed welds and surfaces smooth and blended so no
roughness shows after finishing and contour of welded surface matches that of adjacent
surface.
F.
Form exposed connections with hairline joints, flush and smooth, using concealed fasteners
where possible. Where exposed fasteners are required, use Phillips flat-head (countersunk)
screws or bolts, unless otherwise indicated. Locate joints where least conspicuous.
G.
Fabricate seams and other connections that will be exposed to weather in a manner to exclude
water. Provide weep holes where water may accumulate.
H.
Cut, reinforce, drill, and tap metal fabrications as indicated to receive finish hardware, screws,
and similar items.
I.
Provide for anchorage of type indicated; coordinate with supporting structure, and space
anchoring devices to secure metal fabrications rigidly in place and to support indicated loads.
2.6
General: Design and provide steel framing and supports not specified in other Sections as
needed to complete the Work.
B.
Fabricate units from steel shapes, plates, and bars of welded construction, unless otherwise
indicated. Fabricate to sizes, shapes, and profiles indicated and as necessary to receive
adjacent construction retained by framing and supports. Cut, drill, and tap units to receive
hardware, hangers, and similar items.
1.
Fabricate units from slotted channel framing where indicated.
2.
Furnish inserts if units are installed after concrete is placed.
C.
D.
Prime miscellaneous framing and supports with zinc-rich primer where indicated.
2.7
Fabricate loose steel lintels from steel angles and shapes of size indicated for openings and
recesses in masonry walls and partitions at locations indicated. Weld adjoining members
together to form a single unit where indicated.
B.
Size loose lintels to provide bearing length at each side of openings equal to 1/12 of clear span
but not less than 8, unless otherwise indicated.
C.
D.
Prime loose steel lintels located in interior walls with zinc-rich primer.
2.8
Provide loose bearing and leveling plates for steel items bearing on masonry or concrete
construction. Drill plates to receive anchor bolts and for grouting.
B.
C.
Section 05 50 00
Metal Fabrications
2.9
2.10
Provide steel weld plates and angles not specified in other Sections, for items supported from
concrete construction as needed to complete the Work. Provide each unit with not less than two
integrally welded steel strap anchors for embedding in concrete.
MISCELLANEOUS STEEL TRIM
A.
Unless otherwise indicated, fabricate units from steel shapes, plates, and bars of profiles shown
with continuously welded joints and smooth exposed edges. Miter corners and use concealed
field splices where possible.
B.
Provide cutouts, fittings, and anchorages as needed to coordinate assembly and installation
with other work.
1.
Provide with integrally welded steel strap anchors for embedding in concrete or masonry
construction.
C.
D.
2.11
METAL LADDERS
A.
General:
1.
Comply with the more stringent requirements of OSHA and ANSI A14.3, unless indicated
otherwise.
2.
Space side rails 16 clear apart, unless otherwise indicated.
3.
Support each ladder at top and bottom and not more than 60 o.c, with welded or bolted
brackets, made from same metal as ladder.
4.
All ladders including ladders less than 20 feet in height shall be equipped with an integral
fall protection system.
B.
Extension (Pop-up). Every ladder that does not have an exterior hand hold shall be equipped
with a pop-up extension designed by the ladder manufacturer.
1.
Pop-up extension shall be of the same material and finish as the ladder with telescoping
tubular section that locks automatically when fully extended.
2.
Upward and downward movement shall be controlled by stainless steel spring balancing
mechanisms.
3.
Units shall be completely assembled with fasteners for securing to the ladder rungs in
accordance with the manufacturers recommendations.
C.
Section 05 50 00
Metal Fabrications
d.
Available Manufacturers:
1). Sellstorm Manufacturing
2). North Safety Products, Ltd.
3). Or approved equal.
D.
Steel Ladders:
1.
Fit rungs in centerline of side rails; plug-weld and grind smooth on outer rail faces.
2.
Rung spacing shall not exceed 12 inches on center.
3.
Provide non-slip surfaces on top of each rung by coating with abrasive material
metallically bonded to rung by a proprietary process.
4.
Available Products:
a.
IKG Industries, a Harsco company; Mebac.
b.
W. S. Molnar Company; SlipNOT.
5.
Galvanize exterior ladders and interior ladders, unless indicated otherwise, including
brackets and fasteners.
E.
Aluminum Ladders:
1.
Fit rungs in centerline of side rails; fasten by welding or with stainless-steel fasteners or
brackets and aluminum rivets.
2.
Rung spacing shall not exceed 12 inches on center.
3.
4.
2.12
Provide non-slip surfaces on top of each rung by coating with abrasive material
metallically bonded to rung by a proprietary process.
Available Products:
a.
IKG Industries, a Harsco company; Mebac.
b.
W. S. Molnar Company; SlipNOT.
A.
Also referenced as Checkered or Check Plate, with raised lugs on one side and smooth
surface on other side.
B.
Fabricate from roller-aluminum-alloy 6061-T6, ASTM B 632 plate of thickness indicated below
Raised lug pattern shall be on top and start at 45 angle to edge of plate or tread.
C.
Provide stainless steel or aluminum angle stiffeners and/or aluminum beam supports, as
indicated or required.
D.
Provide flush stainless steel bar drop handles for lifting removable sections. Provide one at
each end of each section.
E.
All ends and openings shall be banded and sealed with a 1/4-inch neoprene gasket.
F.
The weight of a floor plate section shall not exceed 150 pounds.
G.
Aluminum surfaces in contact with concrete, grout or dissimilar metals will be protected with a
coat of bituminous paint, Mylar isolators or other protective system, as approved by the
Engineer.
H.
Available Manufacturers
1.
Thompson Fabricating, LLC; Tarrant, AL.
2.
Or approved equal.
Section 05 50 00
Metal Fabrications
2.13
METAL BOLLARDS
A.
Fabricate metal bollards from 6 diameter steel pipe and fill with non-structural concrete. Refer
to drawings and standard details for locations and anchorage details.
B.
2.14
A.
Cast-Metal Units: Cast aluminum, with an integral abrasive finish consisting of aluminum oxide,
silicon carbide, or a combination of both. Fabricate units in sizes and configurations indicated
and in lengths necessary to accurately fit openings or conditions.
1.
Manufacturers:
a.
American Safety Tread Co., Inc.
b.
Baleo Inc.
c.
Barry Pattern & Foundry Co., Inc.
d.
Granite State Casting Co.
e.
Safe-T-Metal Co.
f.
Wooster Products Inc.
2.
Nosing: Cross-hatched units, 4 wide with 1/4 lip, for casting into concrete steps.
3.
Nosing: Cross-hatched units, 1-1/2 x 1-1/2, for casting into concrete curbs.
4.
Treads: Cross-hatched units, full depth of tread with 3/4 x 3/4 nosing, for application
over bent plate treads or existing stairs.
B.
Extruded Units: Aluminum, with abrasive filler consisting of aluminum oxide, silicon carbide, or
a combination of both, in an epoxy-resin binder. Fabricate units in sizes and configurations
indicated and in lengths necessary to accurately fit openings or conditions.
1.
Available Manufacturers:
a.
ACL Industries, Inc.
b.
American Safety Tread Co., Inc.
c.
Amstep Products.
d.
Armstrong Products, Inc.
e.
Baleo Inc.
f.
Granite State Casting Co.
g.
Wooster Products Inc.
2.
Provide ribbed units, with abrasive filler strips projecting 1/16 above aluminum extrusion.
3.
Provide solid-abrasive-type units without ribs.
4.
Nosing: Square-back units, 3 wide, for casting into concrete steps.
5.
Nosing: Beveled-back units, 3 wide with 1-3/8 lip, for surface mounting on existing
stairs.
6.
Nosing: Two-piece units, 3 wide, with sub channel for casting into concrete steps.
7.
Treads: Beveled-back units, full depth of tread with 1-3/8 lip, for application over existing
stairs.
C.
Provide anchors for embedding units in concrete, either integral or applied to units, as standard
with Manufacturer.
D.
Drill for mechanical anchors and countersink. Locate not more than 4 from ends and not more
than 12 o.c., evenly spaced between ends, unless otherwise indicated. Provide closer spacing
if recommended by Manufacturer.
1.
Provide 2 rows of holes for units more than 5 wide, with 2 holes aligned at ends and
intermediate holes staggered.
E.
Apply bituminous paint, Mylar isolators or other protective system as approved by the Engineer
to concealed bottoms, sides, and edges of cast-metal units set into concrete
Section 05 50 00
Metal Fabrications
2.15
FINISHES, GENERAL
A.
Comply with NAAMM Metal Finishes Manual for Architectural and Metal Products for
recommendations for applying and designating finishes.
B.
Finish metal fabrications after assembly according to the paintings and protective coatings
specification.
2.16
A.
Galvanizing: Hot-dip galvanize items as indicated to comply with applicable standard listed
below:
1.
ASTM A 123 for galvanizing steel and iron products.
2.
ASTM A 153 for galvanizing steel and iron hardware.
B.
Preparation for Shop Priming: Prepare uncoated ferrous-metal surfaces to comply with
minimum requirements indicated below for SSPC surface preparation specifications and
environmental exposure conditions of installed metal fabrications:
1.
Exteriors (SSPC Zone 1B) and Items Indicated to Receive Zinc-Rich primer: SP 6/NACE
No.3, Commercial Blast Cleaning.
2.
Interiors (SSPC Zone 1A): SSPC-SP 3, Power Tool Cleaning.
C.
Shop Priming: Apply shop primer to uncoated surfaces of metal fabrications, except those with
galvanized finishes and those to be embedded in concrete, sprayed-on fireproofing, or masonry,
unless otherwise indicated. Comply with SSPC-PA 1, Paint Application Specification No.1:
Shop, Field, and Maintenance Painting of Steel, for shop painting.
1.
Stripe paint corners, crevices, bolts, welds, and sharp edges.
2.17
STAINLESS-STEEL FINISHES
A.
Remove tool and die marks and stretch lines or blend into finish.
B.
Grind and polish surfaces to produce uniform, directionally textured, polished finish indicated,
free of cross scratches. Run grain with long dimension of each piece.
C.
D.
E.
When polishing is completed, passivate and rinse surfaces. Remove embedded foreign matter
and leave surfaces chemically clean.
2.18
ALUMINUM FINISHES
A.
Finish designations prefixed by AA comply with the system established by the Aluminum
Association for designating aluminum finishes.
B.
C.
10
Section 05 50 00
Metal Fabrications
PART 3 - EXECUTION
3.1
INSTALLATION, GENERAL
A.
Cutting, Fitting, and Placement: Perform cutting, drilling, and fitting required for installing metal
fabrications. Set metal fabrications accurately in location, alignment, and elevation; with edges
and surfaces level, plumb, true, and free of rack; and measured from established lines and
levels.
B.
Fit exposed connections accurately together to form hairline joints. Weld connections that are
not to be left as exposed joints but cannot be shop welded because of shipping size limitations.
Do not weld, cut, or abrade surfaces of exterior units that have been hot-dip galvanized after
fabrication and are for bolted or screwed field connections.
C.
D.
Fastening to In-Place Construction: Provide anchorage devices and fasteners where metal
fabrications are required to be fastened to in-place construction. Provide threaded fasteners for
use with concrete and masonry inserts, toggle bolts, through bolts, lag bolts, wood screws, and
other connectors.
E.
Provide temporary bracing or anchors in formwork for items that are to be built into concrete,
masonry, or similar construction.
F.
Protection: Coat concealed surfaces of aluminum that will come into contact with grout,
concrete, masonry, wood, or dissimilar metals with a heavy coat of bituminous paint.
3.2
General: Install framing and supports to comply with requirements of items being supported,
including Manufacturers written instructions and requirements indicated on Shop Drawings.
B.
Install pipe columns on concrete footings with grouted baseplates. Position and grout column
baseplates as specified in Installing Bearing and Leveling Plates Article.
3.3
Clean concrete and masonry bearing surfaces of bond-reducing materials, and roughen to
improve bond to surfaces. Clean bottom surface of plates.
B.
Set bearing and leveling plates on wedges, shims, or leveling nuts. After bearing members have
been positioned and plumbed, tighten anchor bolts. Do not remove wedges or shims but, if
protruding, cut off flush with edge of bearing plate before packing with grout.
1.
Use non-shrink grout, nonmetallic, in concealed locations where not exposed to moisture;
use non shrink, nonmetallic grout in exposed locations, unless otherwise indicated.
2.
Pack grout solidly between bearing surfaces and plates to ensure that no voids remain.
11
Section 05 50 00
Metal Fabrications
3.4
B.
Anchor bollards in place with non-structural concrete, as indicated on the drawings. Place
concrete and vibrate or tamp for consolidation. Support and brace bollards in position until
concrete has cured.
C.
Fill bollards solidly with concrete, mounding top surface to shed water.
1.
Do not fill removable bollards with concrete.
3.5
B.
For nosing embedded in concrete steps or curbs, align nosing flush with riser faces and level
with tread surfaces.
C.
Seal thresholds exposed to exterior with elastomeric sealant complying with Section 07 92 00,
JOINT SEALANTS to provide a watertight installation.
3.6
Touchup Painting: Immediately after erection, clean field welds, bolted connections, and
abraded areas. Paint uncoated and abraded areas with the same material as used for shop
painting to comply with SSPC-PA 1 for touching up shop-painted surfaces.
1.
Apply by brush or spray to provide a minimum 2.0 mil dry film thickness.
B.
Touchup Painting: Cleaning and touchup painting of field welds, bolted connections, and
abraded areas of shop paint are specified in Division 9 painting Sections.
C.
Galvanized Surfaces: Clean field welds, bolted connections, and abraded areas and repair
galvanizing to comply with ASTM A 780.
END OF SECTION
12
Section 05 50 00
Metal Fabrications
SUMMARY
A.
Section Includes:
1.
Pre-engineered industrial-type stairs with galvanized steel grating treads.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 Cast-In-Place Concrete, for concrete fill for stair platforms.
b.
Section 05 50 00 Metal Fabrications, for metal treads and nosings not installed in
metal stairs.
c.
Section 05 52 13 Pipe and Tube Railings, for pipe and tube railings.
1.2
PERFORMANCE REQUIREMENTS
A.
B.
Structural Performance of Stairs: Design and provide metal stairs capable of withstanding the
effects of gravity loads and the following loads and stresses within limits and under conditions
indicated:
1.
Uniform Load: 200 lbf/sq. ft.
2.
Concentrated Load: 300 lbf applied on an area of 4 sq. in.
3.
Uniform and concentrated loads need not be assumed to act concurrently.
4.
Stair tread, 250psf for tread itself.
5.
Platform and landings: Galvanized Steel tread with uniform live load of 200 psf or a
concentrated load of 1000 lbf over one (1) sq. ft. applied at midspan, whichever produces
the greater effect.
6.
Stair Framing: Capable of withstanding stresses resulting from railing loads in addition to
loads specified above.
7.
Limit deflection of treads, platforms, and framing members to L/360 or 1/4 whichever is
less.
C.
D.
Seismic Performance: Provide metal stairs capable of withstanding the effects of earthquake
motions determined according to ASCE 7, Minimum Design Loads for Buildings and Other
Structures; Section 12, Seismic Design Requirements for Building Structures.
1.3
SUBMITTALS
A.
Section 05 51 00
Metal Stairs
B.
Shop Drawings: Include sealed calculations, plans, elevations, sections, details, and
attachments to other work.
1.
Provide templates for anchors and bolts specified for installation under other Sections.
2.
For installed products indicated to comply with design loads, include structural analysis
data signed and sealed by the qualified professional engineer responsible for their
preparation, licensed in the State where the work is located.
C.
Samples for Initial Selection: For products involving selection of color, texture, or design.
D.
Samples for Verification: For the following products, in Manufacturers standard sizes:
1.
Grating treads.
2.
Abrasive nosings.
E.
Welding certificates.
F.
G.
1.4
QUALITY ASSURANCE
A.
B.
NAAMM Stair Standard: Comply with Recommended Voluntary Minimum Standards for Fixed
Metal Stairs in NAAMM AMP 510, Metal Stairs Manual, for class of stair designated, unless
more stringent requirements are indicated.
1.
Industrial-Type Stairs: Industrial class.
C.
D.
1.5
COORDINATION
A.
Coordinate installation of anchorages for metal stairs. Furnish setting drawings, templates, and
directions for installing anchorages, including sleeves, concrete inserts, anchor bolts, and items
with integral anchors, that are to be embedded in concrete or masonry. Deliver such items to
project site in time for installation.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1.
Available Products: Subject to compliance with requirements, products that may be
incorporated into the Work include, but are not limited to, products specified.
2.
Available Manufacturers: Subject to compliance with requirements, Manufacturers
offering products that may be incorporated into the Work include, but are not limited to;
Manufacturers specified.
Section 05 51 00
Metal Stairs
2.2
METALS, GENERAL
A.
Metal Surfaces, General: Provide materials with smooth, flat surfaces, unless otherwise
indicated, for components exposed to view in the completed Work, provide materials without
seam marks, roller marks, rolled trade names, or blemishes.
B.
2.3
ABRASIVE NOSINGS
A.
B.
Provide anchors for embedding units in concrete, either integral or applied to units, as standard
with Manufacturer.
C.
Apply bituminous paint to concealed bottoms, sides, and edges of cast-metal units set into
concrete.
D.
Apply clear lacquer to concealed bottoms, sides, and edges of extruded units set into concrete.
2.4
FASTENERS
A.
2.5
A.
Welding Rods and Bare Electrodes: Select according to AWS specifications for metal alloy
welded.
B.
Bituminous Paint: Cold, applied asphalt emulsion complying with ASTM D 1187.
C.
D.
Concrete Materials and Properties: Comply with requirements in Section 03 30 00, Cast-inPlace Concrete for normal-weight, air-entrained, ready-mix concrete with a minimum 28-day
compressive strength of 3000 psi unless otherwise indicated.
E.
Non slip-Aggregate Concrete Finish: Factory-packaged abrasive aggregate made from fused,
aluminum-oxide grits or crushed emery; rustproof and non-glazing; unaffected by freezing,
moisture, or cleaning materials.
2.6
FABRICATION, GENERAL
A.
Provide complete stair assemblies, including metal framing, hangers, struts, railings, clips,
brackets, bearing plates, and other components necessary to support and anchor stairs and
platforms on supporting structure.
1.
Join components by welding, unless otherwise indicated.
2.
Use connections that maintain structural value of joined pieces.
3.
Fabricate treads and platforms of exterior stairs so finished walking surfaces slope to
drain.
Section 05 51 00
Metal Stairs
B.
Preassembled Stairs: Assemble stairs in shop to greatest extent possible. Disassemble units
only as necessary for shipping and handling limitations. Clearly mark units for reassembly and
coordinated installation.
C.
Cut, drill, and punch metals cleanly and accurately. Remove burrs and ease edges to a radius
of approximately 1/32, unless otherwise indicated. Remove sharp or rough areas on exposed
surfaces.
D.
Form bent-metal comers to smallest radius possible without causing grain separation or
otherwise impairing work.
E.
Form exposed work true to line and level with accurate angles and surfaces and straight edges.
F.
Use materials and methods that minimize distortion and develop strength and corrosion
resistance of base metals.
Obtain fusion without undercut or overlap.
Remove welding flux immediately.
Weld exposed comers and seams continuously, unless otherwise indicated.
At exposed connections, finish exposed welds and surfaces smooth and blended so no
roughness shows after finishing and contour of welded surface matches that of adjacent
surface.
G.
Form exposed connections with hairline joints, flush and smooth, using concealed fasteners
where possible. Where exposed fasteners are required, use Phillips flathead (countersunk)
screws or bolts unless otherwise indicated. Locate joints where least conspicuous.
H.
Fabricate joints that will be exposed to weather in a manner to exclude water. Provide weep
holes where water may accumulate.
2.7
Manufacturers:
1.
Alfab, Inc.
2.
American Stair, Inc.
3.
Sharon Companies Ltd. (The).
4.
Approved Equal.
B.
Stair Framing:
1.
Fabricate stringers of steel channels.
a.
Provide closures for exposed ends of channel stringers.
b.
Minimum stringer size shall be C 10x15.3.
2.
Construct platforms of steel channel headers and miscellaneous framing members as
needed to comply with performance requirements.
3.
Weld or bolt stringers to headers; weld or bolt framing members to stringers and headers.
If using bolts, fabricate and join so bolts are not exposed on finished surfaces.
4.
Columns shall be steel tube as shown on drawings.
5.
Treads shall be galvanized steel tread or galvanized steel grating as indicated. Tread
plate shall have raised lugs on the top surface. Grating for treads shall have integral
corrugated nosing.
a.
Form treads with integral nosing and back edge stiffener. Form risers of same
material as treads.
b.
Weld supporting brackets to stringers and weld treads to brackets.
Section 05 51 00
Metal Stairs
c.
6.
C.
2.8
Fabricate platforms with integral nosings matching treads and weld to platform
framing.
Provide lateral support and bracing as required by design.
Metal Bar-Grating Stairs: Form treads and platforms to configurations shown from metal bar
grating; fabricate to comply with NAAMM MBG 531, Metal Bar Grating Manua1.
1.
Fabricate treads and platforms from welded galvanized steel grating with 1 by 3/16
bearing bars at 19/16 o.c. and crossbars at 4 o.c., NAAMM designation: W-19-4 (1x
3/16) Galvanized Steel.
2.
Surface: Serrated.
3.
Fabricate grating treads with cast abrasive nosing and with steel angle or steel plate
carrier at each end for stringer connections. Secure treads to stringers with bolts.
4.
Fabricate grating platforms with nosing matching that on grating treads. Provide toe
plates at open-sided edges of grating platforms. Weld grating to platform framing.
STAIR RAILINGS
A.
2.9
A.
Comply with NAAMM Metal Finishes Manual for Architectural and Metal Products for
recommendations for applying and designating finishes.
B.
PART 3 - EXECUTION
3.1
INSTALLATION, GENERAL
A.
Fastening to In-Place Construction: Provide anchorage devices and fasteners where necessary
for securing metal stairs to in-place construction. Include threaded fasteners for concrete and
masonry inserts, through-bolts, lag bolts, and other connectors.
B.
Cutting, Fitting, and Placement: Perform cutting, drilling, and fitting required for installing metal
stairs. Set units accurately in location, alignment, and elevation, measured from established
lines and levels and free of rack.
C.
Provide temporary bracing or anchors in formwork for items that are to be built into concrete,
masonry, or similar construction.
D.
Fit exposed connections accurately together to form hairline joints. Weld connections that are
not to be left as exposed joints but cannot be shop welded because of shipping size limitations.
Do not weld, cut, or abrade surfaces of exterior units that have been hot-dip galvanized after
fabrication and are for bolted or screwed field connections.
E.
Section 05 51 00
Metal Stairs
F.
Place and finish concrete till for treads and platforms to comply with Section 03 30 00, CASTIN-PLACE CONCRETE.
1.
Install abrasive nosings with anchors fully embedded in concrete, center nosings on tread
width.
G.
3.2
Clean concrete and masonry bearing surfaces of bond-reducing materials, and roughen to
improve bond to surfaces. Clean bottom surface of baseplates.
B.
Set stair baseplates on wedges, shims, or leveling nuts. After stairs have been positioned and
aligned, tighten anchor bolts. Do not remove wedges or shims but, if protruding, cut off flush
with edge of bearing plate before packing with grout.
1.
Use nonmetallic, non-shrink grout, unless otherwise indicated.
2.
Pack grout solidly between bearing surfaces and plates to ensure that no voids remain.
END OF SECTION
Section 05 51 00
Metal Stairs
SUMMARY
A.
Section Includes:
1.
Aluminum Railings.
2.
Stainless Steel Railings.
3.
Galvanized Steel Railings.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 05 50 00 Metal Fabrications.
b.
Section 09 90 00 Painting and Protective Coatings.
1.2
PERFORMANCE REQUIREMENTS
A.
B.
Structural Performance: Provide railings capable of withstanding the effects of gravity loads
and the following loads and stresses within limits and under conditions indicated:
1.
Handrails:
a.
Uniform load of 50 lbf/ ft. applied in any direction.
b.
Concentrated load of 200 lbf applied in any direction.
c.
Uniform and concentrated loads need not be assumed to act concurrently.
2.
Top Rails of Guards:
a.
Uniform load of 50 lbf/ ft. (0.73 kN/m) applied in any direction.
b.
Concentrated load of 200 lbf applied in any direction.
c.
Uniform and concentrated loads need not be assumed to act concurrently.
3.
Infill of Guards:
2
a.
Concentrated load of 200 lbf (0.89 kN) applied horizontally on an area of 1 ft .
2
b.
Uniform load of 25 lbf / ft applied horizontally.
c.
Infill load and other loads need not be assumed to act concurrently.
C.
Thermal Movements: Provide exterior railings that allow for thermal movements resulting from
the following maximum change (range) in ambient and surface temperatures by preventing
buckling, opening of joints, overstressing of components, failure of connections, and other
detrimental effects. Base the engineering calculation on surface temperatures of materials due
to both solar heat gain and nighttime-sky heat loss.
1.
Temperature Change (Range): 120 F, ambient; 180 F, material surfaces.
Section 05 52 13
Pipe and Tube Railings
D.
1.3
Control of Corrosion: Prevent galvanic action and other forms of corrosion by insulating metals
and other materials from direct contact with incompatible materials.
SUBMITTALS
A.
B.
Shop Drawings:
1.
Include plans, elevations, sections, details, and attachments to other work. Also, provide
locations and details for any post stiffeners, as required by design.
2.
Include structural analysis and design calculations signed and sealed by a qualified
professional engineer licensed in the state of the work.
C.
Samples for Owners Selection: For products involving selection of color, texture, or design.
D.
E.
Mill Certificates:
requirements.
F.
Welding certificates.
G.
H.
1.4
QUALITY ASSURANCE
A.
Source Limitations: Obtain each type of railing through one source from a single Manufacturer.
B.
1.5
PROJECT CONDITIONS
A.
Field Measurements: Verify actual locations of walls and other construction contiguous with
railings by field measurements before fabrication and indicate measurements on Shop
Drawings.
1.
Established Dimensions: Where field measurements cannot be made without delaying
the Work, establish dimensions and proceed with fabricating railings without field
measurements. Coordinate wall and other contiguous construction to ensure that actual
dimensions correspond to established dimensions.
2.
Provide allowance for trimming and fitting at site.
Section 05 52 13
Pipe and Tube Railings
1.6
Coordinate installation of anchorages for railings. Furnish setting drawings, templates, and
directions for installing anchorages, including sleeves, concrete inserts, anchor bolts, and items
with integral anchors, that are to be embedded in concrete or masonry. Deliver such items to
Project site in time for installation.
B.
Schedule installation so wall attachments are made only to completed walls. Do not support
railings temporarily by any means that do not satisfy structural performance requirements.
PART 2 - PRODUCTS
2.1
GENERAL
A.
Metals:
1.
Metal Surfaces, General: Provide materials with smooth surfaces, without seam marks,
roller marks, rolled trade names, stains, discolorations, or blemishes.
2.
Brackets, Flanges, and Anchors: Cast or formed metal of same type of material and finish
as supported rails, unless otherwise indicated.
B.
Finishes:
1.
Comply with NAAMM Metal Finishes Manual for Architectural and Metal Products for
recommendations for applying and designating finishes.
2.
Protect finishes on exposed surfaces from damage by applying a strippable, temporary
protective covering before shipping.
3.
Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces
are acceptable if they are within one-half of the range of approved Samples. Noticeable
variations in the same piece are not acceptable. Variations in appearance of other
components are acceptable if they are within the range of approved Samples and are
assembled or installed to minimize contrast.
4.
Provide exposed fasteners with finish matching appearance, including color and texture,
of railings or posts.
2.2
Aluminum
1.
General: Provide alloy and temper as recommended by manufacturer to meet the type of
use and finish indicated, and with not less than the strength and durability properties
designated below.
2.
Extruded Structural Pipe and Round Tubing: ASTM B 429, Alloy 6063-T6.
3.
Drawn Seamless Tubing: ASTM B 210, Alloy 6063-T832.
4.
Plate and Sheet: ASTM B 209, Alloy 6061-T6.
5.
Die and Hand Forgings: ASTM B 247, Alloy 6061-T6.
6.
Castings: ASTM B 26, Alloy A356.0-T6.
7.
Finish, as follows:
a.
Handrail Pipe and Posts: Anodized finish shall be AA-M32-C22-A41 and shall
meet the requirements of AAMA 607.1
b.
Cast Fittings and Toeboards: Anodized finish shall be AA-M10-C22-A41 and shall
meet the requirements of AAMA 607.1
c.
Pretreat aluminum by cleaning and removing marks before anodizing.
B.
Stainless Steel
1.
General: Provide type as recommended by manufacturer to meet the type of use and
finish indicated, and with not less than the strength and durability properties designated
below.
Section 05 52 13
Pipe and Tube Railings
2.
3.
4.
5.
C.
2.3
Steel
1.
General: Provide type as recommended by manufacturer to meet the type of use and
finish indicated, and with not less than the strength and durability properties designated
below.
2.
Pipe: ASTM A 53
3.
Tubing: ASTM A 500
4.
Plate and Sheet: ASTM A 36
5.
Castings: ASTM A 48
6.
Finish:
a.
Surface Preparation: Remove loose scale, rust, grease, oil, moisture or other
foreign materials to properly prepare the surface for subsequent coating
application.
1)
Remove mill scale, rust and dirt following SSPC SP2 for hand cleaning and
SSPC SP3 for power tool cleaning.
b.
Prime and Paint, as indicated, in accordance with 09 90 00 Painting and Protective
Coatings.
1)
Submit colors to Owner/Engineer for approval.
c.
Galvanizing, as indicated on the drawings, shall be in accordance with ASTM A123
for shapes, plates, and bars and A 525 for sheeting.
RAIL AND POSTS
A.
B.
C.
2.4
FITTINGS
A.
2.5
General
1.
Refer to drawings for fitting, joint, and base details.
2.
Materials and finishes for all fittings, joints, and bases shall match the railing material.
Alloy or material grade shall meet or exceed the alloy or material grade specified.
FASTENERS
A.
B.
C.
Section 05 52 13
Pipe and Tube Railings
2.6
FABRICATION
A.
General: Fabricate railings to comply with requirements indicated for design, dimensions,
member sizes and spacing, details, finish, and anchorage, but not less than that required to
support structural loads.
B.
Assemble railings in the shop to greatest extent possible to minimize field splicing and
assembly. Disassemble units only as necessary for shipping and handling limitations. Clearly
mark units for reassembly and coordinated installation. Use connections that maintain structural
value of joined pieces.
C.
Cut, drill, and punch metals cleanly and accurately. Remove burrs and ease edges to a radius
of approximately 1/32 unless otherwise indicated. Remove sharp or rough areas on exposed
surfaces.
D.
Form work true to line and level with accurate angles and surfaces.
E.
Fabricate connections that will be exposed to weather in a manner to exclude water. Provide
weep holes where water may accumulate.
F.
Cut, reinforce, drill, and tap as indicated to receive finish hardware, screws, and similar items.
G.
Non-welded Connections: Connect members with concealed mechanical fasteners and fittings.
Fabricate members and fittings to produce flush, smooth, rigid, hairline joints.
1.
Fabricate splice joints for field connection using an epoxy structural adhesive if this is
Manufacturers standard splicing method.
H.
I.
Provide wall returns at ends of wall-mounted handrails, unless otherwise indicated. Close ends
of returns unless clearance between end of rail and wall is 1/4 or less.
J.
Provide inserts and other anchorage devices for connecting railings to concrete or masonry
work. Fabricate anchorage devices capable of withstanding loads imposed by railings.
Coordinate anchorage devices with supporting structure.
K.
For railing posts set in concrete, provide steel sleeves not less than 6 long with inside
dimensions not less than 1/2 greater than outside dimensions of post, with steel plate forming
bottom closure.
L.
For removable railing posts, fabricate slip-fit sockets from stainless-steel tube or pipe whose ID
is sized for a close fit with posts; limit movement of post without lateral load, measured at top, to
not more than one-fortieth of post height. Provide socket covers designed and fabricated to
resist being dislodged.
1.
Provide chain with eye, snap hook, and staple across gaps formed by removable railing
sections at locations indicated. Fabricate from same metal as railings.
M.
Toeboards: Where indicated, provide toe boards at railings around openings and at edge of
open-sided floors and platforms. Fabricate to dimensions and details indicated. Dimension
between bottom of toeboard and walking surface not to exceed 1/4-inch.
Section 05 52 13
Pipe and Tube Railings
PART 3 - EXECUTION
3.1
EXAMINATION
A.
3.2
Examine plaster and gypsum board assemblies, where reinforced to receive anchors, to verify
that locations of concealed reinforcements have been clearly marked for Installer. Locate
reinforcements and mark locations if not already done.
INSTALLATION, GENERAL
A.
Fit exposed connections together to form tight, hairline joints and in accordance with
Manufacturers written instructions.
B.
Perform cutting, drilling, and fitting required for installing railings. Set railings accurately in
location, alignment, and elevation; measured from established lines and levels and free of rack.
1.
Do not weld, cut, or abrade surfaces of railing components that have been coated or
finished after fabrication and that are intended for field connection by mechanical or other
means without further cutting or fitting.
2.
Set posts plumb within a tolerance of 1/16 in 3.
3.
Align rails so variations from level for horizontal members and variations from parallel
with rake of steps and ramps for sloping members do not exceed 1/4 in 12.
C.
Corrosion Protection: Prevent galvanic action and other forms of corrosion caused from direct
contact with concrete and dissimilar metals by coating metal surfaces in accordance with
manufacturers recommendations and Section 09 90 00, PAINTING AND PROTECTIVE
COATINGS.
D.
E.
Fastening to In-Place Construction: Use anchorage devices and fasteners where necessary for
securing railings and for properly transferring loads to in-place construction.
F.
Mount handrails only on completed walls. Do not support handrails temporarily by means not
satisfying structural performance requirements.
3.3
RAILING CONNECTIONS
A.
Set rails horizontal or parallel to slope of steps. Install posts and rails in the same plane.
Remove projects or irregularities and provide smooth surface for sliding hand continuously
along top rail. Use offset rail for use on stairs and platforms if post is attached to web of
stringers or structural platform supports.
B.
Expansion Joints: Install expansion joints at locations indicated but not farther apart than
required to accommodate thermal movement, maximum interval of 54 feet on center and at
structural joints. Provide slip-joint internal sleeve extending 2 beyond joint on either side,
fasten internal sleeve securely to 1 side, and locate joint within 6 of post.
3.4
ANCHORING POSTS
A.
Where indicated, use steel pipe sleeves preset and anchored into concrete for installing posts.
After posts have been inserted into sleeves fill annular space between the post and sleeve with
non-shrink, nonmetallic grout, or anchoring cement mixed and placed to comply with anchoring
material manufacturers written instructions.
Section 05 52 13
Pipe and Tube Railings
B.
Form or core-drill holes not less than 5 deep and 3/4 larger than OD of post for installing posts
in concrete. Clean holes of loose material, insert posts, and fill annular space between post and
concrete with non-shrink, nonmetallic grout or anchoring cement, mixed and placed to comply
with anchoring material per Manufacturers written instructions.
C.
Leave anchorage joint exposed; wipe off surplus anchoring material; and leave 1/8 buildup,
sloped away from post.
D.
Where indicated, anchor posts with fittings engineered for anchoring posts to concrete.
E.
Anchor posts to metal surfaces with oval flanges, angle type, or floor type as required by
conditions, connected to posts and to metal supporting members as follows:
1.
For aluminum pipe railings, attach posts using fittings designed and engineered for this
purpose.
F.
Install removable railing sections, where indicated, in slip-fit metal sockets cast in concrete.
G.
3.5
3.6
Anchor railing ends to concrete and masonry with round flanges connected to railing ends and
anchored to wall construction with anchors and bolts.
ATTACHING HANDRAILS TO WALLS
A.
Attach handrails to wall with wall brackets. Provide brackets with 1-1/2 clearance from inside
face of handrail and finished wall surface.
1.
Use type of bracket with predrilled hole for exposed bolt anchorage.
B.
Locate brackets as indicated or, if not indicated, at spacing required to support structural loads.
C.
3.7
3.8
Clean railing by washing thoroughly with clean water and soap and rinsing with clean water.
PROTECTION
A.
Protect finishes of railings from damage during construction period with temporary protective
coverings approved by railing Manufacturer. Remove protective coverings at time of Substantial
Completion.
B.
Restore finishes damaged during installation and construction period so no evidence remains of
correction work. Return items that cannot be refinished in the field to the shop; make required
alterations and refinish entire unit, or provide new units.
END OF SECTION
Section 05 52 13
Pipe and Tube Railings
SUMMARY
A.
Section Includes:
1.
Metal gratings and aluminum plank.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
05 50 00 - Metal Fabrications, for supporting beams and frame work.
b.
05 51 00 - Metal Stairs, for requirements for grating treads.
c.
09 90 00 - Painting and Protective Coatings, for protective coatings and coatings
for dissimilar metals in contact.
1.2
GENERAL REQUIREMENTS
A.
1.3
Contractor, and/or sub-contractor, is responsible for field verifying all grating and plank
locations, dimensions, obstructions, openings, and any other pertinent coordination issues prior
to bidding. For existing items marked to be reused, contractor is responsible for field verifying
existing condition and determining whether replacement is required prior to bidding.
SUBMITTALS
A.
Shop Drawings:
1.
Include plans, elevations, sections, details, supports and attachment to other work.
2.
Grating and Plank: Show dimensions, weight, and location of connections to adjacent
grating, supports, and other Work.
3.
Grating and Plank Supports: Show dimensions, size, location, and anchorage to
supporting structure.
4.
Catalog information and catalog cuts.
5.
Manufacturers specifications, to include coatings.
B.
1.4
REFERENCES
A.
Section 05 53 00
Metal Gratings and Plank
2.
3.
1.5
1989.
American Society for Testing and Materials (ASTM):
a.
A 36, Standard Specification for Structural Steel.
b.
A 123, Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and
Steel Products.
c.
A 153, Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware (R 1987).
d.
A 167, Standard Specification for Stainless and Heat-Resisting Chromium-Nickel
Steel Plate, Sheet, and Strip.
e.
A 193, Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials
for High-Temperature Service.
f.
A 194, Standard Specification for Carbon and Alloy Steel Nuts for Bolts for HighPressure and High-Temperature Service.
g.
A 307, Standard Specification for Carbon Steel Bolts and Studs, 60,000 psi Tensile
Strength.
h.
A 525, Standard Specification for General Requirements for Steel Sheet, ZincCoated (Galvanized) by the Hot-Dip Process.
i.
A 569/A569M, Standard Specification for Steel, Carbon (0.15 Maximum Percent),
Hot-Rolled Sheet and Strip Commercial Quality.
j.
B 221, Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars,
Rods, Wire, Shapes, and Tubes.
k.
F 844, Standard Specification for Washers, Steel, Plain (Flat), Unhardened for
General Use.
National Association of Architectural Metal Manufacturers (NAAMM):
a.
ANSI MBG 531, Metal Bar Grating Manual.
b.
ANSI MBG 532, Heavy-Duty Metal Bar Grating Manual.
Insofar as is practical, factory-assemble items to insure proper fit before shipping to job site.
B.
Package and clearly tag parts and assemblies that are of necessity shipped un-assembled and
protect the materials from damage, and facilitate identification and final assembly in the field.
PART 2 - PRODUCTS
2.1
B.
C.
D.
Section 05 53 00
Metal Gratings and Plank
2.2
B.
C.
D.
2.3
B.
C.
Material:
1.
Galvanized Steel Bar Type:
a.
After Fabrication: ASTM A123, zinc coating.
b.
Manufacturer and Product: IKG/Borden, Clark, NJ; KG/Borden heavy-weld Type
HWF or HWB or press-locked, rectangular crossbar, Type BJ or FJ.
2.4
ALUMINUM PLANK
A.
Acceptable Manufacturers, subject to the requirements, which may have acceptable products
include, but are not limited to the following:
1.
Ohio Gratings Inc.
2.
Grating Pacific, Inc.
3.
Harsco Industrial IKG.
4.
McNichols Co.
5.
Or Approved Equal.
B.
Materials: Planks and banding are Aluminum Alloy 6063-T6, ASTM B-221.
1.
Description: Heavy Duty, Extruded Aluminum Plank.
a.
All ends to be banded.
2.
Type(s): As indicated on the drawings, include:
a.
Interlocking and Unpunched
b.
Unpunched
c.
Diagonally punched with approximately 8% openings.
3.
Top Surface: Manufacturers standard slip-resistant finish.
4.
Finish: Mill Finish.
5.
Fabrication and Tolerances: In accordance with NAAM Metal Bar Grating Manual.
6.
Depth: As indicated on the drawings.
7.
Loading: As indicated on the drawings.
8.
Weight: No section shall weigh more than 150 pounds.
2.5
ACCESSORIES
A.
Section 05 53 00
Metal Gratings and Plank
1.
2.
3.
B.
Flat Washers (Unhardened): ASTM F844; use ASTM A153 for zinc coating.
C.
2.6
FABRICATION
A.
General:
1.
Exposed Surfaces: Smooth finish and sharp, well-defined lines.
2.
Furnish necessary rabbets, lugs, and brackets so work can be assembled in a neat,
substantial manner.
3.
Conceal fastenings where practical.
4.
Drill metalwork and countersink holes as required for attaching hardware or other
materials.
5.
Weld Connections: Not permitted on grating except at banding bars.
B.
Sizing:
1.
Field measure areas to receive grating, verify dimensions of new fabricated supports, and
fabricate to dimension required for specified clearances.
2.
Section Length: Sufficient to prevent falling down through clear opening when oriented in
the span direction when one end is touching either the concrete or the vertical leg of
grating support.
3.
Minimum Bearing: ANSI/NAAMM MBG 531.
4.
Metal Crossbar Spacing: 4 maximum, unless otherwise shown or specified.
5.
Crossbars: Flush with top of main bar and extend downward a minimum of 50% of the
main bar depth.
a.
Swaged Crossbars:
1). Within 1/4 of top of grating with minimum vertical dimension after swaging, and minimum before swaging dimension of 5/16 square.
2). Crossbar Dimension After Swaging: Minimum 1/8 wider than the opening at
minimum of two comers at each side of each square opening in main bar.
3). Crossbars may be a special extruded shape so that after swaging the top will
be flat, 3/16 wide and will be flush with the top surface of the bearing bars
for a minimum of 5/8 at center between bearing bars.
4). Flush crossbar meeting all of the above except that after swaging shall overlap one comer by a minimum of 1/8. A sample of one bearing bar and one
crossbar shall be tested by holding the bearing bar and pulling on the crossbar. The crossbar to bearing bar shall sustain a minimum of 300 pounds
without pullout of the bearing bar.
5). Tightly fit main bars and crossbars allowing no differential movement.
6.
Do not use weld type crossbars.
7.
Banding: All ends to be banded with same material as grating or plank; ANSI/NAAMM
MBG 531 and ANSI/NAAMM MBG 532.
8.
Furnish stainless steel Type 316 threaded anchor studs, as fasteners for grating or plank
attachment to metal supports either not embedded or partially embedded in concrete.
Section 05 53 00
Metal Gratings and Plank
C.
Supports:
1.
Seat angles and beams where shown:
a.
Material: To match grating or plank.
b.
Extruded aluminum frame with slot for recessed grating clips.
2.
Coordinate dimensions and fabrication with grating or plank to be supported.
3.
Welded Frames with Anchors: Continuously welded.
D.
Slip-Resistant Surface:
1.
Rectangular Aluminum Bar Grating: As manufactured by:
a.
IKG/Borden, Clark, NJ; EZ Weldslip-Resistant Coating.
b.
Seidelhuber Metal Products, Inc., Hayward, CA; Safety Grit Non-Slip System.
c.
Ohio Gratings, Inc., Canton, OH with Slip-Not Safety Surface manufactured by
W.S. Molnar Co., Detroit, MI.
2.
I-Bar grating aluminum shall incorporate a striated antiskid walking surface produced
during the extrusion process, as manufactured by:
a.
IKG/Borden, Clark, NJ.
b.
Seidelhuber Metal Products, Inc., Hayward, CA.
c.
Klemp Corp., Chicago, IL.
E.
Aluminum:
1.
ASTM B221 extruded shapes.
2.
Fabricate as shown and in accordance with Manufacturers recommendations.
3.
Grind smooth sheared edges exposed in the finished work.
4.
Swage crossbars, if used, with equipment strong enough to deform crossbars.
5.
Eliminate any loose crossbar intersections on swaged grating.
PART 3 - EXECUTION
3.1
PREPARATION
A.
3.2
Electrolytic Protection:
1.
Aluminum in contact with dissimilar metals, other than stainless steel, or in contact with
masonry, grout, or concrete shall be coated with a bituminous coating as specified in
Section 09 90 00, Painting and Protective Coatings
2.
Allow paint to dry before installation of the material.
INSTALLATION
A.
Install supports such that grating or plank sections have a solid bearing on both ends, and that
rocking or wobbling movement does not occur under designed traffic loading.
B.
C.
D.
Anchor grating or plank securely to supports using minimum of four fastener clips and bolts per
grating or plank section.
E.
F.
G.
Wherever grating or plank is pierced by pipes, ducts, and structural members, cut openings
neatly and accurately to size and weld a rectangular band bar of the same height and material
as bearing bars.
Section 05 53 00
Metal Gratings and Plank
H.
Cutouts for circular openings are to be 2 larger in diameter than the obstruction. Cutouts for all
piping 4 or less shall be made in the field.
I.
All rectangular cutouts are to be made to the next bearing bar beyond the penetration with a
clearance not to exceed bearing bar spacing.
J.
K.
L.
Should coating become marred, prepare and touch up surface in accordance with paint
Manufacturers instructions.
END OF SECTION
Section 05 53 00
Metal Gratings and Plank
DIVISION 07
THERMAL AND MOISTURE PROTECTION
SUMMARY
A.
1.2
Section Includes:
1.
Glass-fiber blanket insulation.
2.
Mineral-wool blanket insulation.
3.
Loose-fill Insulation
SUBMITTALS
A.
B.
C.
1.3
1.4
Protect insulation materials from physical damage and from deterioration due to moisture,
soiling, and other sources. Store inside and in a dry location. Comply with manufacturer's
written instructions for handling, storing, and protecting during installation.
DESIGN CRITERIA
A.
Provide all wall and roof insulation in accordance with the 2009 International Energy Code.
1.
Minimum R-Values shall be as follows, unless noted otherwise:
a.
For walls, R-19 minimum continuous.
b.
For roofs, R-30 minimum continuous with two layers laid perpendicular.
PART 2 - PRODUCTS
2.1
B.
Unfaced, Glass-Fiber Blanket Insulation: ASTM C 665, Type I; with maximum flame-spread and
smoke-developed indexes of 25 and 50, respectively, per ASTM E 84; passing ASTM E 136 for
combustion characteristics.
Section 07 21 00
Metal Building Insulation
2.2
B.
Unfaced, Mineral-Wool Blanket Insulation: ASTM C 665, Type I (blankets without membrane
facing); consisting of fibers; with maximum flame-spread and smoke-developed indexes of 25
and 50, respectively, per ASTM E 84; passing ASTM E 136 for combustion characteristics.
2.3
LOOSE-FILL INSULATION
A.
Glass-Fiber Loose-Fill Insulation: ASTM C 764, Type II for poured application; with maximum
flame-spread and smoke-developed indexes of 5, per ASTM E 84.
B.
2.4
INSULATION FASTENERS
A.
B.
C.
Insulation-Retaining Washers: Self-locking washers formed from 0.016-inch thick galvanizedsteel sheet, with beveled edge for increased stiffness, sized as required to hold insulation
securely in place, but not less than 1-1/2 inches square or in diameter.
1.
Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, the following:
a.
AGM Industries, Inc.; RC150 or SC150.
b.
Gemco; Dome-Cap, R-150, or S-150.
c.
Or Approved Equal.
Section 07 21 00
Metal Building Insulation
2.
D.
Protect ends with capped self-locking washers incorporating a spring steel insert to
ensure permanent retention of cap.
Anchor Adhesive: Product with demonstrated capability to bond insulation anchors securely to
substrates indicated without damaging insulation, fasteners, and substrates.
1.
Products: Subject to compliance with requirements, available products that may be
incorporated into the Work include, but are not limited to, the following:
a.
AGM Industries, Inc.; TACTOO Adhesive.
b.
Gemco; Tuff Bond Hanger Adhesive.
PART 3 - EXECUTION
3.1
PREPARATION
A.
3.2
Clean substrates of substances that are harmful to insulation or vapor retarders, including
removing projections capable of puncturing vapor retarders, or that interfere with insulation
attachment.
INSTALLATION, GENERAL
A.
B.
Install insulation that is undamaged, dry, and unsoiled and that has not been left exposed to ice,
rain, or snow at any time.
C.
Extend insulation to envelop entire area to be insulated. Cut and fit tightly around obstructions
and fill voids with insulation. Remove projections that interfere with placement.
D.
Provide sizes to fit applications indicated and selected from manufacturer's standard
thicknesses, widths, and lengths. Apply single layer of insulation units to produce thickness
indicated unless multiple layers are otherwise shown or required to make up total thickness.
3.3
Apply insulation units to substrates by method indicated, complying with manufacturer's written
instructions. If no specific method is indicated, bond units to substrate with adhesive or use
mechanical anchorage to provide permanent placement and support of units.
B.
C.
Loose-Fill Insulation: Apply according to ASTM C 1015 and manufacturer's written instructions.
Level horizontal applications to uniform thickness as indicated, lightly settle to uniform density,
but do not compact excessively.
Section 07 21 00
Metal Building Insulation
D.
3.4
Miscellaneous Voids: Install insulation in miscellaneous voids and cavity spaces where required
to prevent gaps in insulation.
PROTECTION
A.
Protect installed insulation from damage due to harmful weather exposures, physical abuse,
and other causes. Provide temporary coverings or enclosures where insulation is subject to
abuse and cannot be concealed and protected by permanent construction immediately after
installation.
END OF SECTION
Section 07 21 00
Metal Building Insulation
SUMMARY
A.
B.
Related Sections:
1.
2.
3.
1.2
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
QUALITY ASSURANCE
A.
All aluminum hatches furnished under this Section shall be of a design and manufacture that
has been used in similar applications and it shall be demonstrated to the satisfaction of the
Owner that the quality is equal to equipment made by that manufacturer specifically named
herein.
B.
Unit Responsibility: Aluminum hatches, complete with frame and all other specified accessories
and appurtenances, shall be furnished by the aluminum hatch manufacturer to ensure
compatibility and integrity of the individual components and provide the specified warranty for all
components.
C.
The aluminum hatches specified in this Section, complete with frame and all other specified
accessories and appurtenances, shall be furnished by and be the product of one manufacturer.
1.3
SUBMITTALS
A.
Submit information to establish compliance with the Specifications in accordance with the
provisions of Section 01 33 00 SUBMITTAL PROCEDURES.
B.
C.
Section 07 72 33
Aluminum Hatches
D.
E.
F.
Detailed list of any exceptions taken to these Specifications. Include specification reference and
proposed alternative with reason stated for exception.
1.4
Aluminum hatches specified in this Section shall be designed for a 300 psf live load.
B.
C.
D.
Aluminum hatches shall be designed for easy opening from both inside and outside.
E.
Unless otherwise indicated, hinges shall be located on the longer dimension side.
PART 2 - PRODUCTS
2.1
ACCEPTABLE MANUFACTURERS
A.
2.2
Experience in design and manufacture of aluminum hatches is required for this project. Submit
references for a minimum of ten installations of similar design as specified, having yielded
successful performance for a period of not less than five years. Subject to compliance with
requirements, available manufacturers offering products that may be incorporated into the Work
include the following:
1.
Bilco
2.
Syracuse Castings
3.
Thompson Fabricating
4.
Halliday
MATERIALS
A.
Hatches shall be fabricated from aluminum 6061-T6, unless otherwise indicated. Aluminum
hatch hardware shall be Type 316 stainless steel, unless otherwise indicated.
B.
Cover Leafs: Shall be 1/4 inch 5086 aluminum checkered plate reinforced with structural
aluminum channels capable of withstanding a 300 psf uniform live load with minimal deflection.
C.
Hardware: Cover shall be equipped with the following features: Gas spring assist, heavy-duty
hinges, tamperproof attaching hardware, automatic hold-open arm with latch.
1.
Gas Spring Assist: Type 316 stainless steel.
2.
Hold-Open Arm with Aluminum Release Handle: Type 316 stainless steel. Shall
automatically lock in the open 90 position. Hold-Open arm shall be fastened to the frame
with a 1/2 316 stainless steel bolt.
3.
Heavy-Duty Hinges: Type 316 stainless steel. Each hinge shall have a grade 316
stainless steel 3/8 diameter hinge pin. Hinge shall be fastened to angle and diamond
plate with 316 stainless steel bolts and ny-lock nuts.
Section 07 72 33
Aluminum Hatches
4.
All fasteners which penetrate into the dry area of the hatch shall be sealed with O ring
seals to prevent incidental leakage.
D.
The gutter-type frame shall be 1/4 inch aluminum channel with continuous anchor flange and
shall incorporate a neoprene gasket between the frame and the cover leaf when in the closed
position. The gutter-type frame shall be provided with a 1 inches threaded drainage coupling
located on the Drawings.
E.
The gutterless-type frame shall be 1/4 inch aluminum angle with continuous anchor flange and
shall incorporate a neoprene gasket between the frame and the cover leaf when in the closed
position.
F.
Frame Coating: The portion of the frame in contact with concrete shall receive a protective
bituminous coating.
G.
Locking system: type 316 stainless steel slam lock with one T wrench provided per unit.
H.
Built-in neoprene gasket shall reduce air leakage to less than 1 cfm per linear foot of frame
when the interior of the hatch is subjected to a 2 inch water column vacuum.
I.
All double-leaf hatches shall have two interconnected slam locks which latch at both ends of the
plate and can be unlatched from a single point.
J.
Units shall be supplied with hinged safety grates to provide protection against fall through and to
control access to the confined space.
K.
Each hatch shall be equipped with an aluminum lift handle. The lift handle shall be flush with the
top of the 1/4 diamond plate.
PART 3 - EXECUTION
3.1
INSTALLATION PROCEDURE
A.
B.
C.
All threads on stainless steel rods/bolts shall be protected with an anti-seize lubricant suitable
for submerged stainless bolts and complying with Federal Specification MILl-A-907E.
Section 07 72 33
Aluminum Hatches
3.2
WARRANTY
A.
Warrant all parts to be free from defects in materials and workmanship for a period of five years
after Substantial Completion.
B.
Furnish replacement parts to the Owner for any items found to be defective within the five-year
warranty period.
END OF SECTION
Section 07 72 33
Aluminum Hatches
SUMMARY
A.
Section Includes:
1.
Silicone joint sealants.
2.
Urethane joint sealants.
3.
Preformed joint sealants.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as
if called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any
of CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 04 22 00 - Unit Masonry Assemblies, for masonry control and expansion
joint fillers and gaskets.
1.2
PRECONSTRUCTION TESTING
A.
1.3
A.
B.
Samples for Initial Selection: Manufacturers color charts consisting of strips of cured sealants
showing the full range of colors available for each product exposed to view.
C.
Samples for Verification: For each kind and color of joint sealant required, provide Samples
with joint sealants in 1/2 inch-wide joints formed between two 6 inch- long strips of material
matching the appearance of exposed surfaces adjacent to joint sealants.
D.
Section 07 92 00
Joint Sealants
3.
4.
Joint-sealant formulation.
Joint-sealant color.
E.
F.
Product Certificates: For each kind of joint sealant and accessory, from manufacturer.
G.
H.
I.
1.4
QUALITY ASSURANCE
A.
B.
Source Limitations:
manufacturer.
C.
D.
1.5
Obtain each kind of joint sealant from single source from single
PROJECT CONDITIONS
A.
1.6
Do not proceed with installation of joint sealants under the following conditions:
1.
When ambient and substrate temperature conditions are outside limits permitted by
joint-sealant manufacturer or are below 40 deg F.
2.
When joint substrates are wet.
3.
Where joint widths are less than those allowed by joint-sealant manufacturer for
applications indicated.
4.
Where contaminants capable of interfering with adhesion have not yet been removed
from joint substrates.
WARRANTY
A.
Special Installers Warranty: Manufacturers standard form in which Installer agrees to repair
or replace joint sealants that do not comply with performance and other requirements specified
in this Section within specified warranty period.
1.
Warranty Period: Two years from date of Substantial Completion.
Section 07 92 00
Joint Sealants
B.
C.
Special warranties specified in this article exclude deterioration or failure of joint sealants from
the following:
1.
Movement of the structure caused by structural settlement or errors attributable to
design or construction resulting in stresses on the sealant exceeding sealant
manufacturers written specifications for sealant elongation and compression.
2.
Disintegration of joint substrates from natural causes exceeding design specifications.
3.
Mechanical damage caused by individuals, tools, or other outside agents.
4.
Changes in sealant appearance caused by accumulation of dirt or other atmospheric
contaminants.
PART 1 - PRODUCTS
1.1
MATERIALS, GENERAL
A.
Compatibility: Provide joint sealants, backings, and other related materials that are compatible
with one another and with joint substrates under conditions of service and application, as
demonstrated by joint-sealant manufacturer, based on testing and field experience.
B.
Liquid-Applied Joint Sealants: Comply with ASTM C 920 and other requirements indicated for
each liquid-applied joint sealant specified, including those referencing ASTM C 920
classifications for type, grade, class, and uses related to exposure and joint substrates.
1.
Suitability for Immersion in Liquids. Where sealants are indicated for Use I for joints that
will be continuously immersed in liquids, provide products that have undergone testing
according to ASTM C 1247. Liquid used for testing sealants is de-ionized water, unless
otherwise indicated.
C.
1.2
B.
C.
1.3
Section 07 92 00
Joint Sealants
1.
2.
3.
4.
5.
B.
Two-Part Urethane: Non-Sag, ASTM C920, Type M, Grade NS, Class 25.
1.
Chem-Calk 500, by Bostik.
2.
Vulkem 227, by Mameco.
3.
Dynatrol II, by Pecora Corporation.
4.
Sikaflex-2c NS/SL, by Sika Corporation.
5.
Sonolastic NP 2, by Sonneborn Building Products, ChemRex Inc.
C.
D.
One-Part Urethane: Non-Sag, ASTM C920, Type S, Grade NS, Class 25.
1.
Chem-Calk 900, by Bostik.
2.
Vulkem 116, by Mameco.
3.
Sonolastic NP I, by Sonneborn Building Products, ChemRex Inc.
4.
Sikaflex 1A by Sika.
1.4
1.5
A.
General: Provide sealant backings of material that are non-staining; are compatible with joint
substrates, sealants, primers, and other joint fillers; and are approved for applications indicated
by sealant manufacturer based on field experience and laboratory testing.
B.
Cylindrical Sealant Backings: ASTM C 1330, Type C (closed-cell material with a surface skin)
OR Type O (open-cell material), and of size and density to control sealant depth and otherwise
contribute to producing optimum sealant performance.
1.6
MISCELLANEOUS MATERIALS
A.
B.
Section 07 92 00
Joint Sealants
PART 2 - EXECUTION
2.1
EXAMINATION
A.
Examine joints indicated to receive joint sealants, with Installer present, for compliance with
requirements for joint configuration, installation tolerances, and other conditions affecting jointsealant performance.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
2.2
PREPARATION
A.
Surface Cleaning of Joints: Clean out joints immediately before installing joint sealants to
comply with joint-sealant manufacturers written instructions and the following requirements:
1.
Remove all foreign material from joint substrates that could interfere with adhesion of
joint sealant, including dust, paints (except for permanent, protective coatings tested and
approved for sealant adhesion and compatibility by sealant manufacturer), old joint
sealants, oil, grease, waterproofing, water repellents, water, surface dirt, and frost.
2.
Clean porous joint substrate surfaces by brushing, grinding, mechanical abrading, or a
combination of these methods to produce a clean, sound substrate capable of
developing optimum bond with joint sealants. Remove loose particles remaining after
cleaning operations above by vacuuming or blowing out joints with oil-free compressed
air. Porous joint substrates include the following:
a.
Concrete.
b.
Masonry.
c.
Exterior insulation and finish systems.
3.
Remove laitance and form-release agents from concrete.
4.
Clean nonporous joint substrate surfaces with chemical cleaners or other means that do
not stain, harm substrates, or leave residues capable of interfering with adhesion of joint
sealants. Nonporous joint substrates include the following:
a.
Metal.
B.
2.3
General: Comply with joint-sealant manufacturers written installation instructions for products
and applications indicated, unless more stringent requirements apply.
B.
Sealant Installation Standard: Comply with recommendations in ASTM C 1193 for use of joint
sealants as applicable to materials, applications, and conditions indicated.
C.
Install sealant backings of kind indicated to support sealants during application and at position
required to produce cross-sectional shapes and depths of installed sealants relative to joint
widths that allow optimum sealant movement capability.
1.
Do not leave gaps between ends of sealant backings.
2.
Do not stretch, twist, puncture, or tear sealant backings.
3.
Remove absorbent sealant backings that have become wet before sealant application
and replace them with dry materials.
D.
Install bond-breaker tape behind sealants where sealant backings are not used between
sealants and backs of joints.
Section 07 92 00
Joint Sealants
E.
Install sealants using proven techniques that comply with the following and at the same time
backings are installed:
1.
Place sealants so they directly contact and fully wet joint substrates.
2.
Completely fill recesses in each joint configuration.
3.
Produce uniform, cross-sectional shapes and depths relative to joint widths that allow
optimum sealant movement capability.
F.
Tooling of Nonsag Sealants: Immediately after sealant application and before skinning or
curing begins, tool sealants according to requirements specified in subparagraphs below to
form smooth, uniform beads of configuration indicated; to eliminate air pockets; and to ensure
contact and adhesion of sealant with sides of joint.
1.
Remove excess sealant from surfaces adjacent to joints.
2.
Use tooling agents that are approved in writing by sealant manufacturer and that do not
discolor sealants or adjacent surfaces.
3.
Provide concave joint profile per Figure 8A in ASTM C 1193, unless otherwise indicated.
4.
Provide flush joint profile where indicated per Figure 8B in ASTM C 1193.
5.
Provide recessed joint configuration of recess depth and at locations indicated per
Figure 8C in ASTM C 1193.
G.
2.4
Section 07 92 00
Joint Sealants
5.
B.
2.5
joints were primed, adhesion results and percent elongations, sealant fill, sealant
configuration, and sealant dimensions.
Repair sealants pulled from test area by applying new sealants following same
procedures used originally to seal joints. Ensure that original sealant surfaces are clean
and that new sealant contacts original sealant.
Evaluation of Field-Adhesion Test Results: Sealants not evidencing adhesive failure from
testing or noncompliance with other indicated requirements will be considered satisfactory.
Remove sealants that fail to adhere to joint substrates during testing or to comply with other
requirements. Retest failed applications until test results prove sealants comply with indicated
requirements.
CLEANING
A.
2.6
Clean off excess sealant or sealant smears adjacent to joints as the Work progresses by
methods and with cleaning materials approved in writing by manufacturers of joint sealants and
of products in which joints occur.
PROTECTION
A.
Protect joint sealants during and after curing period from contact with contaminating
substances and from damage resulting from construction operations or other causes so
sealants are without deterioration or damage at time of Substantial Completion. If, despite such
protection, damage or deterioration occurs, cut out and remove damaged or deteriorated joint
sealants immediately so installations with repaired areas are indistinguishable from original
work.
END OF SECTION
Section 07 92 00
Joint Sealants
DIVISION 08
OPENINGS
SUMMARY
A.
Section includes:
1.
Standard hollow metal doors and frames.
2.
Hinged Transom and frames.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 08 71 00 Door Hardware.
1.2
DEFINITIONS
A.
B.
Standard Hollow Metal Work: Hollow metal work fabricated according to ANSI/SDI A250.8.
1.3
SUBMITTALS
A.
B.
C.
Samples for Initial Selection: For units with factory-applied color finishes.
D.
Section 08 11 13
Steel Doors and Frames
a.
b.
E.
1.4
Doors: Show vertical-edge, top, and bottom construction; core construction; and
hinge and other applied hardware reinforcement. Include separate section
showing glazing if applicable.
Frames: Show profile, corner joint, floor and wall anchors, and silencers. Include
separate section showing fixed hollow metal panels and glazing if applicable.
A.
Source Limitations: Obtain hollow metal work from single source from single manufacturer.
B.
1.5
Deliver hollow metal work palletized, wrapped, or crated to provide protection during transit and
Project-site storage. Do not use non vented plastic.
1.
Provide additional protection to prevent damage to finish of factory-finished units.
B.
Deliver welded frames with two removable spreader bars across bottom of frames, tack welded
to jambs and mullions.
C.
Store hollow metal work under cover at Project site. Place in stacks of five units maximum in a
vertical position with heads up, spaced by blocking, on minimum 4-inch- high wood blocking.
Do not store in a manner that traps excess humidity.
1.
Provide minimum 1/4-inch space between each stacked door to permit air circulation.
1.6
PROJECT CONDITIONS
A.
1.7
Field Measurements:
fabrication.
COORDINATION
A.
Coordinate installation of anchorages for hollow metal frames. Furnish setting drawings,
templates, and directions for installing anchorages, including sleeves, concrete inserts, anchor
bolts, and items with integral anchors. Deliver such items to Project site in time for installation.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Section 08 11 13
Steel Doors and Frames
8.
9.
10.
11.
12.
13.
14.
15.
2.2
MATERIALS
A.
Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B; suitable for
exposed applications.
B.
Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, Commercial Steel (CS), Type B; free of scale,
pitting, or surface defects; pickled and oiled.
C.
Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), Type B; with
minimum G60 or A60 metallic coating.
D.
Frame Anchors: ASTM A 591/A 591M, Commercial Steel (CS), 40Z coating designation; mill
phosphatized.
1.
For anchors built into exterior walls, steel sheet complying with ASTM A 1008/A 1008M
or ASTM A 1011/A 1011M, hot-dip galvanized according to ASTM A 153/A 153M,
Class B.
E.
Inserts, Bolts, and Fasteners: Hot-dip galvanized according to ASTM A 153/A 153M.
F.
G.
Grout: ASTM C 476, except with a maximum slump of 4 inches, as measured according to
ASTM C 143/C 143M.
H.
Mineral-Fiber Insulation: ASTM C 665, Type I (blankets without membrane facing); consisting
of fibers manufactured from slag or rock wool with 6- to 12-lb/cu. ft. density; with maximum
flame-spread and smoke-development indexes of 25 and 50, respectively; passing ASTM E 136
for combustion characteristics.
I.
Bituminous Coating: Cold-applied asphalt mastic, SSPC-Paint 12, compounded for 15-mil dry
film thickness per coat. Provide inert-type noncorrosive compound free of asbestos fibers,
sulfur components, and other deleterious impurities.
J.
Glazing:
1.
General: Installed glazing systems shall withstand normal thermal movement and wind
and impact loads (where applicable) without failure, including loss or glass breakage
attributable to the following: defective manufacturer, fabrication or installation; failure of
sealants or gaskets to remain watertight and airtight; deterioration of glazing materials; or
other defects in construction.
2.
Delegated Design: Design glass, including comprehensive engineering analysis
according to ICCs 2006 International Building Code by a qualified professional engineer.
3.
Thermal Movements: Allow for thermal movements from ambient and surface
temperature changes acting on glass framing members and glazing components.
a.
Temperature Change: 120 deg F (67 deg C), ambient; material surfaces.
Section 08 11 13
Steel Doors and Frames
4.
2.3
General: Provide doors and hinged transom of design indicated, not less than thickness
indicated; fabricated with smooth surfaces, without visible joints or seams on exposed faces
unless otherwise indicated. Comply with ANSI/SDI A250.8.
1.
Design: Flush panel.
2.
Core Construction:
Manufacturers standard kraft-paper honeycomb, polystyrene,
polyurethane, polyisocyanurate, mineral-board, or vertical steel-stiffener core.
a.
Thermal-Rated (Insulated) Doors: Where indicated, provide doors fabricated with
thermal-resistance value (R-value) of not less than 12.3 deg F x h x sq. ft./Btu
when tested according to ASTM C 1363.
1). Locations: All doors.
3.
Vertical Edges for Single-Acting Doors: Beveled edge.
a.
Beveled Edge: 1/8 inch in 2 inches.
4.
Vertical Edges for Double-Acting Doors: Round vertical edges with 2-1/8-inch radius.
5.
Top and Bottom Edges: Closed with flush or inverted 0.042-inch- thick, end closures or
channels of same material as face sheets.
6.
Tolerances: Comply with SDI 117, "Manufacturing Tolerances for Standard Steel Doors
and Frames."
B.
All Doors and hinged transom: Face sheets fabricated from metallic-coated steel sheet.
Provide doors complying with requirements indicated below by referencing ANSI/SDI A250.8 for
level and model and ANSI/SDI A250.4 for physical performance level:
C.
Hardware Reinforcement: Fabricate according to ANSI/SDI A250.6 with reinforcing plates from
same material as door face sheets.
D.
Fabricate concealed stiffeners and hardware reinforcement from either cold- or hot-rolled steel
sheet.
2.4
General: Comply with ANSI/SDI A250.8 and with details indicated for type and profile.
B.
C.
2.5
FRAME ANCHORS
A.
Jamb Anchors:
1.
Masonry Type: Adjustable strap-and-stirrup or T-shaped anchors to suit frame size, not
less than 0.042 inch thick, with corrugated or perforated straps not less than 2 inches
wide by 10 inches long; or wire anchors not less than 0.177 inch thick.
2.
Stud-Wall Type: Designed to engage stud, welded to back of frames; not less than 0.042
inch thick.
3.
Compression Type for Drywall Slip-on Frames: Adjustable compression anchors.
B.
Floor Anchors: Formed from same material as frames, not less than 0.042 inch thick, and as
follows:
Section 08 11 13
Steel Doors and Frames
1.
2.
2.6
Monolithic Concrete Slabs: Clip-type anchors, with two holes to receive fasteners.
Separate Topping Concrete Slabs: Adjustable-type anchors with extension clips,
allowing not less than 2-inch height adjustment. Terminate bottom of frames at finish
floor surface.
2.7
Provide hollow metal panels of same materials, construction, and finish as specified for
adjoining hollow metal work.
STOPS AND MOLDINGS
A.
2.8
Fixed Frame Moldings: Formed integral with hollow metal frames, a minimum of 5/8 inch high
unless otherwise indicated.
FABRICATION
A.
Fabricate hollow metal work to be rigid and free of defects, warp, or buckle. Accurately form
metal to required sizes and profiles, with minimum radius for thickness of metal. Where
practical, fit and assemble units in manufacturers plant. To ensure proper assembly at Project
site, clearly identify work that cannot be permanently factory assembled before shipment.
B.
C.
D.
Hollow Metal Frames: Where frames are fabricated in sections due to shipping or handling
limitations, provide alignment plates or angles at each joint, fabricated of same thickness metal
as frames.
1.
Welded Frames: Weld flush face joints continuously; grind, fill, dress, and make smooth,
flush, and invisible.
2.
Provide countersunk, flat- or oval-head exposed screws and bolts for exposed fasteners
unless otherwise indicated.
3.
Grout Guards: Weld guards to frame at back of hardware mortises in frames to be
grouted.
4.
Floor Anchors: Weld anchors to bottom of jambs and mullions with at least four spot
welds per anchor.
5.
Jamb Anchors: Provide number and spacing of anchors as follows:
a.
Masonry Type: Locate anchors not more than 18 inches from top and bottom of
frame. Space anchors not more than 32 inches o.c. and as follows:
1) Two anchors per jamb up to 60 inches high.
2) Three anchors per jamb from 60 to 90 inches high.
3) Four anchors per jamb from 90 to 120 inches high.
b.
Stud-Wall Type: Locate anchors not more than 18 inches from top and bottom of
frame. Space anchors not more than 32 inches o.c. and as follows:
1) Three anchors per jamb up to 60 inches high.
2) Four anchors per jamb from 60 to 90 inches high.
3) Five anchors per jamb from 90 to 96 inches high.
Section 08 11 13
Steel Doors and Frames
c.
d.
E.
Fabricate concealed stiffeners, edge channels, and hardware reinforcement from either cold- or
hot-rolled steel sheet.
F.
Hardware Preparation: Factory prepare hollow metal work to receive templated mortised
hardware; include cutouts, reinforcement, mortising, drilling, and tapping according to the Door
Hardware Schedule and templates furnished as specified in Division 8 Section "Door
Hardware."
1.
Reinforce doors, hinged transom and frames to receive non-templated, mortised and
surface-mounted door hardware.
2.
Comply with applicable requirements in ANSI/SDI A250.6 and ANSI/DHI A115 Series
specifications for preparation of hollow metal work for hardware.
G.
Stops and Moldings: Provide stops and moldings around glazed lites where indicated. Form
corners of stops and moldings with butted or mitered hairline joints.
1.
Provide fixed frame moldings on outside of exterior and on secure side of interior doors
and frames.
2.
Provide loose stops and moldings on inside of hollow metal work.
3.
Coordinate rabbet width between fixed and removable stops with type of glazing and type
of installation indicated.
2.9
STEEL FINISHES
A.
Prime Finish: Apply manufacturers standard primer immediately after cleaning and pretreating.
1.
Shop Primer: Manufacturers standard, fast-curing, lead- and chromate-free primer
complying with ANSI/SDI A250.10 acceptance criteria; recommended by primer
manufacturer for substrate; compatible with substrate and field-applied coatings despite
prolonged exposure.
B.
Factory-Applied Paint Finish: Manufacturers standard, complying with ANSI/SDI A 250.3 for
performance and acceptance criteria.
1.
Color and Gloss: As selected by Owner or Engineer from manufacturers full range.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates, areas, and conditions, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of the Work.
B.
Examine roughing-in for embedded and built-in anchors to verify actual locations before frame
installation.
C.
For the record, prepare written report, endorsed by Installer, listing conditions detrimental to
performance of the Work.
D.
Proceed with installation only after unsatisfactory conditions have been corrected.
Section 08 11 13
Steel Doors and Frames
3.2
PREPARATION
A.
Remove welded-in shipping spreaders installed at factory. Restore exposed finish by grinding,
filling, and dressing, as required to make repaired area smooth, flush, and invisible on exposed
faces.
B.
Prior to installation, adjust and securely brace welded hollow metal frames for squareness,
alignment, twist, and plumbness to the following tolerances:
1.
Squareness: Plus or minus 1/16 inch, measured at door rabbet on a line 90 degrees
from jamb perpendicular to frame head.
2.
Alignment: Plus or minus 1/16 inch, measured at jambs on a horizontal line parallel to
plane of wall.
3.
Twist: Plus or minus 1/16 inch, measured at opposite face corners of jambs on parallel
lines, and perpendicular to plane of wall.
4.
Plumbness: Plus or minus 1/16 inch, measured at jambs on a perpendicular line from
head to floor.
C.
Drill and tap doors and frames to receive nontemplated, mortised, and surface-mounted door
hardware.
3.3
INSTALLATION
A.
General: Install hollow metal work plumb, rigid, properly aligned, and securely fastened in
place; comply with Drawings and manufacturers written instructions.
B.
Hollow Metal Frames: Install hollow metal frames of size and profile indicated. Comply with
ANSI/SDI A 250.11.
1.
Set frames accurately in position, plumbed, aligned, and braced securely until permanent
anchors are set. After wall construction is complete, remove temporary braces, leaving
surfaces smooth and undamaged.
a.
Where frames are fabricated in sections because of shipping or handling
limitations, field splice at approved locations by welding face joint continuously;
grind, fill, dress, and make splice smooth, flush, and invisible on exposed faces.
b.
Install door silencers in frames before grouting.
c.
Remove temporary braces necessary for installation only after frames have been
properly set and secured.
d.
Check plumbness, squareness, and twist of frames as walls are constructed.
Shim as necessary to comply with installation tolerances.
e.
Field apply bituminous coating to backs of frames that are filled with grout
containing anti-freezing agents.
2.
Floor Anchors: Provide floor anchors for each jamb and mullion that extends to floor, and
secure with post-installed expansion anchors.
a.
Floor anchors may be set with powder-actuated fasteners instead of post-installed
expansion anchors if so indicated and approved on Shop Drawings.
3.
Metal-Stud Partitions: Solidly pack mineral-fiber insulation behind frames.
4.
Masonry Walls: Coordinate installation of frames to allow for solidly filling space between
frames and masonry with grout.
5.
In-Place Concrete or Masonry Construction: Secure frames in place with post-installed
expansion anchors. Countersink anchors, and fill and make smooth, flush, and invisible
on exposed faces.
6.
Ceiling Struts: Extend struts vertically from top of frame at each jamb to overhead
structural supports or substrates above frame unless frame is anchored to masonry or to
other structural support at each jamb. Bend top of struts to provide flush contact for
securing to supporting construction. Provide adjustable wedged or bolted anchorage to
frame jamb members.
Section 08 11 13
Steel Doors and Frames
7.
C.
3.4
Hollow Metal Doors and Hinged Transom: Fit hollow metal doors accurately in frames, within
clearances specified below. Shim as necessary.
1.
Non-Fire-Rated Standard Steel Doors:
a.
Jambs and Head: 1/8 inch plus or minus 1/16 inch.
b.
Between Edges of Pairs of Doors: 1/8 inch plus or minus 1/16 inch.
c.
Between Bottom of Door and Top of Threshold: Maximum 3/8 inch.
d.
Between Bottom of Door and Top of Finish Floor (No Threshold): Maximum 3/4
inch.
ADJUSTING AND CLEANING
A.
Final Adjustments: Check and readjust operating hardware items immediately before final
inspection. Leave work in complete and proper operating condition. Remove and replace
defective work, including hollow metal work that is warped, bowed, or otherwise unacceptable.
B.
Remove grout and other bonding material from hollow metal work immediately after installation.
C.
Prime-Coat Touchup: Immediately after erection, sand smooth rusted or damaged areas of
prime coat and apply touchup of compatible air-drying, rust-inhibitive primer.
D.
Metallic-Coated Surfaces: Clean abraded areas and repair with galvanizing repair paint
according to manufacturers written instructions.
3.5
SCHEDULE
A.
Door
Mark
Installation Tolerances: Adjust hollow metal door frames for squareness, alignment, twist,
and plumb to the following tolerances:
a.
Squareness: Plus or minus 1/16 inch, measured at door rabbet on a line 90
degrees from jamb perpendicular to frame head.
b.
Alignment: Plus or minus 1/16 inch, measured at jambs on a horizontal line
parallel to plane of wall.
c.
Twist: Plus or minus 1/16 inch, measured at opposite face corners of jambs on
parallel lines, and perpendicular to plane of wall.
d.
Plumbness: Plus or minus 1/16 inch, measured at jambs at floor.
Nominal Size
Thickness
Remarks
NOTES:
1. Hardware specified in Section 08 71 00 Door Hardware.
2. Finish to be selected by Owner.
END OF SECTION
Section 08 11 13
Steel Doors and Frames
SUMMARY
A.
Section includes:
1.
Commercial door hardware for the following:
a.
Swinging doors.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 08 11 13 Steel Doors and Frames
C.
Products furnished, but not installed, under this Section include the following. Coordinating,
purchasing, delivering, and scheduling remain requirements of this Section.
1.
Thresholds and weather stripping for locks specified in other Sections.
1.2
SUBMITTALS
A.
Product Data: Include construction and installation details, material descriptions, dimensions of
individual components and profiles, and finishes.
B.
Samples for Initial Selection: For each finish, color, and texture required for each type of door
hardware indicated.
C.
Samples for Verification: Submit minimum 2-by-4-inch plate Samples of each type of finish
required, except primed finish.
D.
Maintenance Data: For each type of door hardware to include in maintenance manuals.
Include final hardware and keying schedule.
E.
F.
Section 08 71 00
Door Hardware
2.
1.3
2) Type, style, function, size, quantity, and finish of each door hardware
item. Include description and function of each lockset and exit device.
3) Complete designations of every item required for each door or opening
including name and manufacturer.
4) Fastenings and other pertinent information.
5) Location of each door hardware set, cross-referenced to Drawings, both on
floor plans and in door and frame schedule.
6) Explanation of abbreviations, symbols, and codes contained in schedule.
7) Mounting locations for door hardware.
8) Door and frame sizes and materials.
9) List of related door devices specified in other Sections for each door and frame.
d.
Submittal Sequence: Submit the final door hardware sets at earliest possible date,
particularly where approval of the door hardware sets must precede fabrication of
other work that is critical in Project construction schedule. Include Product Data,
Samples, Shop Drawings of other work affected by door hardware, and other
information essential to the coordinated review of the door hardware sets.
Keying Schedule: Prepared by or under the supervision of Architectural Hardware
Consultant, detailing Owners final keying instructions for locks. Include schematic keying
diagram and index each key set to unique door designations.
QUALITY ASSURANCE
A.
B.
C.
Source Limitations: Obtain each type and variety of door hardware from a single manufacturer,
unless otherwise indicated.
D.
1.4
Inventory door hardware on receipt and provide secure lock-up for door hardware delivered to
Project site.
B.
Tag each item or package separately with identification related to the final door hardware sets,
and include basic installation instructions, templates, and necessary fasteners with each item or
package.
C.
Deliver keys to manufacturer of key control system for subsequent delivery to Owner.
1.5
COORDINATION
A.
Templates: Distribute door hardware templates for doors, frames, and other work specified to
be factory prepared for installing door hardware. Check Shop Drawings of other work to confirm
Section 08 71 00
Door Hardware
that adequate provisions are made for locating and installing door hardware to comply with
indicated requirements.
1.6
WARRANTY
A.
1.7
A.
Maintenance Tools and Instructions: Furnish a complete set of specialized tools and
maintenance instructions as needed for Owners continued adjustment, maintenance, and
removal and replacement of door hardware.
PART 2 - PRODUCTS
2.1
General: Provide door hardware for each door to comply with requirements in this Section and
door hardware sets indicated in Part 3 "Door Hardware Sets" Article.
1.
Door Hardware Sets: Provide quantity, item, size, finish or color indicated, and products
equivalent in function and comparable in quality to named products.
2.
Sequence of Operation: Provide electrified door hardware function, sequence of
operation, and interface with other building control systems indicated.
B.
Designations: Requirements for design, grade, function, finish, size, and other distinctive
qualities of each type of door hardware are indicated in Part 3 "Door Hardware Sets" Article.
Products are identified by using door hardware designations, as follows:
1.
Named Manufacturers Products: Manufacturer and product designation are listed for
each door hardware type required for the purpose of establishing minimum requirements.
Manufacturers names are abbreviated in Part 3 "Door Hardware Sets" Article.
C.
In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1.
Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
manufacturers specified unless noted otherwise in the hardware schedules.
2.2
HINGES, GENERAL
A.
Section 08 71 00
Door Hardware
B.
C.
D.
E.
F.
2.3
HINGES
A.
Butts and Hinges: BHMA A156.1. Listed under Category A in BHMAs Certified Product
Directory.
B.
C.
Available Manufacturers:
1.
Hager Companies (HAG).
2.
Lawrence Brothers, Inc. (LB).
3.
Stanley Commercial Hardware; Div. of The Stanley Works (STH).
2.4
Pivots: BHMA A156.4. Listed under Category C in BHMAs Certified Product Directory.:
B.
Available Manufacturers:
1.
DORMA Architectural Hardware; Member of The DORMA Group North America.
2.
IVES Hardware; an Ingersoll-Rand Company.
3.
Rixson Specialty Door Controls; an ASSA ABLOY Group company.
2.5
Section 08 71 00
Door Hardware
B.
Latches and Locks for Means of Egress Doors: Comply with NFPA 101. Latches shall not
require more than 15 lbf (67 N) to release the latch. Locks shall not require use of a key, tool, or
special knowledge for operation.
C.
Lock Trim
1.
Levers: Cast.
2.
Escutcheons: Forged or Cast.
3.
Dummy Trim: Match lever lock trim and escutcheons.
4.
Lockset Designs: Provide lockset design(s) indicated by hardware sets or, if locksets are
provided by another manufacturer, provide designs that match those designated.
D.
Lock Throw: Comply with testing requirements for lengths of bolts required for labeled fire
doors, and as follows:
1.
Mortise Locks: Minimum 3/4-inch latchbolt throw.
2.
Deadbolts: Minimum 1-inch bolt throw.
a.
Bored Locks: Minimum 1/2-inch latchbolt throw.
E.
F.
Strikes: Manufacturers standard strike with strike box for each latchbolt or lock bolt, with curved
lip extended to protect frame, finished to match door hardware set, and as follows:
2.6
Lock Functions: Function numbers and descriptions indicated in door hardware sets comply
with the following:
1.
Mortise Locks: BHMA A156.13.
2.
Bored (Cylindrical) Locks: BHMA A156.2.
B.
Mortise Locks: Stamped steel case with steel parts; BHMA A156.13, Grade 1; Series 1000.
1.
Available Manufacturers:
a.
Corbin Russwin Architectural Hardware; an ASSA ABLOY Group Company (CR).
b.
Sargent Manufacturing Company; an ASSA ABLOY Group company.
c.
Yale Commercial Locks and Hardware: an ASSA ABLOY Group Company.
2.
Product Reference Standard: CR ML2000 Series with Citation CSB (630) Trim.
C.
2.7
Section 08 71 00
Door Hardware
2.8
DOOR BOLTS
A.
Bolt Throws: Comply with testing requirements for length of bolts required for labeled fire doors,
and as follows:
1.
Mortise Flush Bolts: Minimum 3/4-inch (19 mm) throw.
2.
Surface Bolts: Minimum 7/8-inch (22 mm) throw.
3.
Fire-Rated Surface Bolts: Minimum 1-inch (25 mm) throw.
B.
C.
D.
Manual Flush Bolts: BHMA A156.16, Grade 1, designed for mortising into door edge.
1.
Available Manufacturers:
a.
Ives Hardware; an Ingersoll-Rand Company.
b.
Stanley Commercial Hardware; Div. of The Stanley Works.
c.
Trimco.
2.
Product Reference Standard: Ives No. 457-1/2 x 12 inches with top and bottom plates for
rod retention.
2.9
EXIT DEVICES
A.
B.
Accessibility Requirements: Where handles, pulls, latches, locks, and other operating devices
are indicated to comply with accessibility requirements, comply with the U.S. Architectural &
Transportation Barriers Compliance Boards Americans with Disabilities Act (ADA),
Accessibility Guidelines for Buildings and Facilities (ADAAG) and ANSI A117.1.
1.
Provide operating devices that do not require tight grasping, pinching or twisting of the
wrist and that operate with a force of not more than 5 lbf.
C.
Exit Devices for Means of Egress Doors: Comply with NFPA 101. Exit devices shall not require
more than 15 lbf to release the latch. Locks shall not require use of a key, tool, or special
knowledge for operation.
D.
Panic Exit Devices: Listed and labeled by a testing and inspecting agency acceptable to
authorities having jurisdiction, for panic protection, based on testing according to UL 305.
E.
Fire Exit Devices: Devices complying with NFPA 80 that are listed and labeled by a testing and
inspecting agency acceptable to authorities having jurisdiction, for fire and panic protection,
based on testing according to UL 305 and NFPA 252.
F.
Exit Device Design: Push Bar type equal to Corbin Russwin ED 5000 Series.
1.
Panic-Listed Mortise Exit Devices: Corbin Russwin ED 5600L Series, with Citation C9M
lever trim. Function as indicated on the door and/or hardware schedules.
2.
Rim Exit Devices: Corbin Russwin ED 5200 Series with Citation C9 lever trim. Function
as indicated on the door and/or hardware schedules.
Section 08 71 00
Door Hardware
G.
Outside Trim: Lever with Mortise cylinder and Exit device; material and finish to match locksets,
unless otherwise indicated.
H.
2.10
LOCK CYLINDERS
A.
B.
Cylinders: Manufacturers standard tumbler type, constructed from stainless steel, or nickel
silver, and complying with the following:
1.
Number of Pins: Six.
2.
Mortise Type: Threaded cylinders with rings and straight- or clover-type cam.
3.
Rim Type: Cylinders with back plate, flat-type vertical or horizontal tailpiece, and raised
trim ring.
4.
Bored-Lock Type: Cylinders with tailpieces to suit locks.
C.
Permanent Cores: Manufacturers standard; finish face to match lockset; complying with the
following:
1.
Interchangeable Cores: Core insert, removable by use of a special key; usable with other
manufacturers cylinders.
D.
E.
F.
Available Manufacturers
1.
Corbin Russwin Architectural Hardware; an ASSA ABLOY Group Company.
2.
Or Approved Equal.
2.11
CLOSERS
A.
Accessibility Requirements: Where handles, pulls, latches, locks, and other operating devices
are indicated to comply with accessibility requirements, comply with the U.S. Architectural &
Transportation Barriers Compliance Boards Americans with Disabilities Act (ADA),
Accessibility Guidelines for Buildings and Facilities (ADAAG) and ANSI A117.1.
1.
Comply with the following maximum opening-force requirements:
a.
Interior, Non-Fire-Rated Hinged Doors: 5 lbf (22.2 N) applied perpendicular to
door.
b.
Fire Doors: Minimum opening force allowable by authorities having jurisdiction.
B.
Door Closers for Means of Egress Doors: Comply with NFPA 101. Door closers shall not require
more than 30 lbf (133 N) to set door in motion and not more than 15 lbf (67 N) to open door to
minimum required width.
C.
Overhead Closers: Closers shall have high-strength cast-iron body with rectangular covers,
adjustable spring power and back-check, and full rack and pinion action. All closers shall have
Section 08 71 00
Door Hardware
adjustable back-check intensity valves and separate adjustment screws for closing and latching
speeds.
1.
Closers for doors over 7-feet in height, or more than 3-feet wide, shall have heavy duty
arms.
2.
Closers at exterior doors shall include hold open arms unless otherwise indicated.
3.
Door closer covers and arms shall be primed and painted to match door hardware.
4.
Closers shall be provided with sex bolts for fastening through doors, frames and
transoms.
D.
Size of Units: Unless otherwise indicated, comply with manufacturers written recommendations
for size of door closers depending on size of door, exposure to weather, and anticipated
frequency of use. Provide factory-sized closers, adjustable to meet field conditions and
requirements for opening force.
E.
Surface Closers: BHMA A156.4, Grade 1. Listed under Category C in BHMAs Certified
Product Directory. Provide type of arm required for closer to be located on non-public side of
door, unless otherwise indicated.
F.
2.12
A.
Size: 1-1/2 inches (38 mm) less than door width on push side and 1/2 inch (13 mm) less than
door width on pull side, by height specified below.
B.
C.
Metal Protective Kick Plates: BHMA A156.6; beveled top and 2 sides; fabricated from the
following material:
1.
Material: 0.050-inch- (1.3 mm) thick stainless steel.
2.
Product References Standard: Rockwood No. 1050; 16 inches high.
D.
2.13
A.
B.
Door Stops: Door stops shall be of the type specified in the hardware sets or in this schedule,
and shall be provided with the proper fasteners.
1.
Door Stop Schedule
Floor Stop Floor
Wall Stop
Kick Stop
w/ Keeper Stop
w/ Keeper
(4 Arm)
Wall Stop
Rockwood
472
471
476
406
461L
2.
Section 08 71 00
Door Hardware
C.
Overhead Holders: Overhead type door holders shall be concealed type of correct size for door,
90 degrees openable, unless 120 degree opening shown, and allowing for checkmating. Interior
doors shall be provided with overhead stops if wall type stops cannot be used and floor stops
create a tripping hazard. Finish shall be chrome plated bronze with satin finish, US 26D, unless
otherwise specified.
1.
Holders Design: Door holders shall be Russwin Corbin, DH 5000 Series, Holder No.
DH5400, or equal.
D.
Silencers for Metal Door Frames: BHMA A156.16, Grade 1; neoprene or rubber, minimum
diameter 1/2 inch (13 mm); fabricated for drilled-in application to frame.
2.14
THRESHOLDS
A.
Standard: BHMA A156.21. Listed under Category J in BHMAs Certified Product Directory.
B.
C.
Thresholds for Means of Egress Doors: Comply with NFPA 101. Maximum 1/2-inch (13 mm)
high.
D.
Threshold Design: All exterior doors shall receive a panic style (offset) aluminum threshold
unless otherwise indicated:
1.
Accessible Entry: National Guard No. 896N (neoprene gasket).
2.
Non-Accessible Entry: National Guard No. 884N (neoprene gasket).
3.
Receiving Entry: National Guard No. 513, Saddle/flat style threshold.
2.15
A.
Push Plates and Pulls: 4-inch by 16-inch by 0.050 thick, stainless steel: Rockwood #70 or
equal. Pulls shall be 3/4 diameter thru-bolted with 4-inch x 16-inch stainless steel plate,
Rockwood No. 105 x 70 with 630 finish, or equal.
B.
Astragal: T Astragal No. 158NA, National Guard Products or FRP astragal by door
manufacturer; furnish with neoprene weatherstrip seal.
C.
Coordinator: Frame mounted, non-handed coordinator and filler piece; Rockwood No. 1600
Series with 630 finish.
Provide Rockwood No. 1100 carry bars at openings with astragals.
D.
Drip Strip: National Guard No. 16A x door width plus 2 inches. Mount head to door frame.
E.
F.
Weatherstrip: National Guard No. 135N; install at each jamb and at head.
G.
H.
I.
Section 08 71 00
Door Hardware
J.
K.
Panic Exit Devices: Devices complying with NFPA 80 and as further specified in Section 2.9.
2.16
KEYING
A.
Keying System: Factory registered, complying with guidelines in BHMA A156.28, Appendix A.
1.
Existing System: Master key locks to Owners existing system.
B.
2.17
FABRICATION
A.
Manufacturers Nameplate: Do not provide products that have manufacturers name or trade
name displayed in a visible location.
1.
Manufacturers identification is permitted on rim of lock cylinders only.
B.
Base Metals: Produce door hardware units of base metal, fabricated by forming method
indicated, using manufacturers standard metal alloy, composition, temper, and hardness.
Furnish metals of a quality equal to or greater than that of specified door hardware units and
BHMA A156.18. Do not furnish manufacturers standard materials or forming methods if
different from specified standard.
C.
Fasteners: Provide door hardware manufactured to comply with published templates generally
prepared for machine, wood, and sheet metal screws. Provide screws according to
commercially recognized industry standards for application intended, except aluminum
fasteners are not permitted. Provide Phillips flat-head screws with finished heads to match
surface of door hardware, unless otherwise indicated.
1.
Concealed Fasteners: For door hardware units that are exposed when door is closed,
except for units already specified with concealed fasteners. Do not use through bolts for
installation where bolt head or nut on opposite face is exposed unless it is the only
means of securely attaching the door hardware. Where through bolts are used on hollow
door and frame construction, provide sleeves for each through bolt.
2.
Steel Machine or Wood Screws: For the following fire-rated applications:
a.
Mortise hinges to doors.
b.
Strike plates to frames.
c.
Closers to doors and frames.
3.
Steel Through Bolts: For the following fire-rated applications unless door blocking is
provided:
a.
Surface hinges to doors.
b.
Closers to doors and frames.
c.
Surface-mounted exit devices.
4.
Spacers or Sex Bolts: For through bolting of hollow-metal doors.
5.
Fasteners for Wood Doors: Comply with requirements in DHI WDHS.2, Recommended
Fasteners for Wood Doors.
2.18
FINISHES
A.
B.
10
Section 08 71 00
Door Hardware
C.
2.19
A.
Product numbers listed in the following specifications are taken from catalogs of manufacturers
listed as follows:
1.
ST Stanley Hardware
2.
S
Sargent & Company
3.
NG National Guard Products
4.
R
Russwin
5.
Mc McKinney
6.
N
Norton
7.
H
Hager
8.
RO Rockwood Mfg.
9.
I
Ives
10.
GJ Glynn Johnson
11.
Sch Schlage
12.
VD Von Duprin
13.
C
Cal Royal
14.
D
Dorma
15.
DE Detex
16.
Y
Yale
B.
Products of the following manufacturers will be considered acceptable provided products are of
equivalent weight, function, materials and design:
1.
Hinges: Hager, Mc Kinney
2.
Locks: Russwin, Sargent, Schlage
3.
Closers:
Russwin, Norton, Sargent
4.
Holders and Stops: Sargent
5.
Door Trim: Glynn Johnson, Ives
6.
Thresholds & Weather stripping National Guard, Hager
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine doors and frames, with Installer present, for compliance with requirements for
installation tolerances, wall and floor construction, and other conditions affecting performance.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
PREPARATION
A.
3.3
A.
Mounting Heights: Mount door hardware units at heights indicated as follows unless otherwise
indicated or required to comply with governing regulations.
11
Section 08 71 00
Door Hardware
1.
2.
Standard Steel Doors and Frames: DHIs "Recommended Locations for Architectural
Hardware for Standard Steel Doors and Frames."
Custom Steel Doors and Frames: DHIs "Recommended Locations for Builders
Hardware for Custom Steel Doors and Frames."
B.
Install each door hardware item to comply with manufacturers written instructions. Where
cutting and fitting are required to install door hardware onto or into surfaces that are later to be
painted or finished in another way, coordinate removal, storage, and reinstallation of surface
protective trim units with finishing work specified in Division 9 Sections. Do not install surfacemounted items until finishes have been completed on substrates involved.
1.
Set units level, plumb, and true to line and location. Adjust and reinforce attachment
substrates as necessary for proper installation and operation.
2.
Drill and countersink units that are not factory prepared for anchorage fasteners. Space
fasteners and anchors according to industry standards.
C.
Thresholds: Set thresholds for exterior doors in full bed of sealant complying with requirements
specified in Division 7 Section "Joint Sealants."
3.4
ADJUSTING
A.
3.5
Initial Adjustment: Adjust and check each operating item of door hardware and each door to
ensure proper operation or function of every unit. Replace units that cannot be adjusted to
operate as intended. Adjust door control devices to compensate for final operation of heating
and ventilating equipment and to comply with referenced accessibility requirements.
1.
Door Closers: Unless otherwise required by authorities having jurisdiction, adjust sweep
period so that, from an open position of 70 degrees, the door will take at least 3 seconds
to move to a point 3 inches from the latch, measured to the leading edge of the door.
CLEANING AND PROTECTION
A.
B.
C.
Provide final protection and maintain conditions that ensure that door hardware is without
damage or deterioration at time of Substantial Completion.
3.6
Mfr.
Butt Hinges
Description
Model Number
(3) BB1191 4.5 x 4.5 x US32D
Exit Device
Sch
Cylinder Lock
As Required
Closer
Kickplate
12
Section 08 71 00
Door Hardware
Threshold
412 x DW x AL
Door Sweep
770SV x DW x AL
Seals
Mfr.
Butt Hinges
Description
Model Number
(3) BB1191 4.5 x 4.5 x US32D
Exit Device
Exit Device
Sch
Cylinder Locks
(2) As Required
DE
KR90 x DH
Closer
Kickplates
Threshold
412 x DW x AL
Door Sweeps
(2) 770SV x DW x AL
Interlock Seals
(2) 718S x DW x AL
Brush Seals
(4) 801S x DH x AL
END OF SECTION
13
Section 08 71 00
Door Hardware
SUMMARY
A.
Section Includes:
1.
Combination, Drainable extruded-aluminum louvers.
2.
Stationary, Drainable extruded-aluminum louvers.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 07 92 00 Joint Sealants.
1.2
DEFINITIONS
A.
Louver Terminology: Definitions of terms for metal louvers contained in AMCA 501 apply to this
Section unless otherwise defined in this Section or in referenced standards.
B.
Horizontal Louver: Louver with horizontal blades; i.e., the axes of the blades are horizontal.
C.
Drainable-Blade Louver: Louver with blades having gutters that collect water and drain it to
channels in jambs and mullions, which carry it to bottom of unit and away from opening.
1.3
PERFORMANCE REQUIREMENTS
A.
Structural Performance: Louvers shall withstand the effects of gravity loads and the following
loads and stresses within limits and under conditions indicated without permanent deformation
of louver components, noise or metal fatigue caused by louver blade rattle or flutter, or
permanent damage to fasteners and anchors. Wind pressures shall be considered to act
normal to the face of the building.
1.
Wind Loads: Determine loads based on a uniform pressure of 20 lbf/sq. ft. acting inward
or outward.
B.
1.4
1.5
SUBMITTALS
A.
B.
Shop Drawings: For louvers and accessories. Include plans, elevations, sections, details, and
attachments to other work. Show frame profiles and blade profiles, angles, and spacing.
QUALITY ASSURANCE
Section 08 90 00
Louvers and Vents
A.
Source Limitations: Obtain louvers and vents from single source from a single manufacturer
where indicated to be of same type, design, or factory-applied color finish.
B.
C.
D.
UL and NEMA Compliance: Provide motors and related components for motor-operated
louvers that are listed and labeled by UL and comply with applicable NEMA standards.
1.6
PROJECT CONDITIONS
A.
Field Measurements:
fabrication.
PART 2 - PRODUCTS
2.1
MATERIALS
A.
Aluminum Extrusions: ASTM B 221 (ASTM B 221M), Alloy 6063-T5, T-52, or T6.
B.
C.
D.
2.2
FABRICATION, GENERAL
A.
Assemble louvers in factory to minimize field splicing and assembly. Disassemble units as
necessary for shipping and handling limitations. Clearly mark units for reassembly and
coordinated installation.
B.
Vertical Assemblies: Where height of louver units exceeds fabrication and handling limitations,
fabricate units to permit field-bolted assembly with close-fitting joints in jambs and mullions,
reinforced with splice plates.
1.
Continuous Vertical Assemblies: Fabricate units without interrupting blade-spacing
pattern.
2.
Horizontal Mullions: Provide horizontal mullions at joints.
C.
Section 08 90 00
Louvers and Vents
D.
Fabricate frames, including integral sills, to fit in openings of sizes indicated, with allowances
made for fabrication and installation tolerances, adjoining material tolerances, and perimeter
sealant joints.
E.
F.
Provide vertical mullions of type and at spacings indicated, but not more than recommended by
manufacturer, or 72 inches (1830 mm) o.c., whichever is less.
G.
Provide subsills made of same material as louvers or extended for recessed louvers.
H.
Join frame members to each other and to fixed louver blades with fillet welds, threaded
fasteners, or both, as standard with louver manufacturer unless otherwise indicated or size of
louver assembly makes bolted connections between frame members necessary.
2.3
Louver Construction and Operation: Provide operable louvers with extruded-aluminum frames
and blades not less than 0.080-inch (2.03-mm) nominal thickness, and with operating
mechanisms to suit louver sizes.
1.
Motor operation with 2-position, spring-return application (with power on, motor opens
louver; with power off, spring closes louver); 110-V, 60-Hz motor and limit switch.
B.
Dual-Blade, Drainable-Blade, combination Louver: Fixed drainable blades and adjustable plain
blades combined in single frame.
1.
Louver Depth 6 inches overall.
2.
AMCA Seal: Mark units with AMCA Certified Ratings Seal.
2.4
2.5
Louver Construction: Provide stationary louver with extruded-aluminum frame and blades not
less than 0.080 inch (2.0-mm) nominal thickness. Frame shall be integral flange type.
1.
Hinged frame: Continuous piano hinge
2.
Louver Depth: 4 inches (100 mm)
LOUVER SCREENS
A.
2.6
A.
2.7
A.
2.8
General: Provide manufacturers installation angles and fasteners for each louver.
FINISHES, GENERAL
A.
Comply with NAAMMs "Metal Finishes Manual for Architectural and Metal Products" for
recommendations for applying and designating finishes.
Section 08 90 00
Louvers and Vents
2.9
ALUMINUM FINISHES
A.
B.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates and openings, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
PREPARATION
A.
3.3
3.4
Coordinate setting drawings, diagrams, templates, instructions, and directions for installation of
anchorages that are to be embedded in concrete or masonry construction. Coordinate delivery
of such items to Project site.
INSTALLATION
A.
Locate and place louvers and vents level, plumb, and at indicated alignment with adjacent work.
B.
Use concealed anchorages where possible. Provide brass or lead washers fitted to screws
where required to protect metal surfaces and to make a weathertight connection.
C.
Form closely fitted joints with exposed connections accurately located and secured.
D.
Provide perimeter reveals and openings of uniform width for sealants and joint fillers, as
indicated.
E.
Repair finishes damaged by cutting, welding, soldering, and grinding. Restore finishes so no
evidence remains of corrective work. Return items that cannot be refinished in the field to the
factory, make required alterations, and refinish entire unit or provide new units.
F.
Protect unpainted galvanized and nonferrous-metal surfaces that will be in contact with
concrete, masonry, or dissimilar metals from corrosion and galvanic action by applying a heavy
coating of bituminous paint or by separating surfaces with waterproof gaskets or nonmetallic
flashing.
G.
Install concealed gaskets, flashings, joint fillers, and insulation as louver installation progresses,
where weathertight louver joints are required. Comply with Section 07 92 00, JOINT
SEALANTS for sealants applied during louver installation.
ADJUSTING AND CLEANING
Section 08 90 00
Louvers and Vents
A.
Test operation of adjustable louvers and adjust as needed to produce fully functioning units that
comply with requirements.
B.
Clean exposed surfaces of louvers and vents that are not protected by temporary covering, to
remove fingerprints and soil during construction period. Do not let soil accumulate during
construction period.
C.
Before final inspection, clean exposed surfaces with water and a mild soap or detergent not
harmful to finishes. Thoroughly rinse surfaces and dry.
D.
Restore louvers and vents damaged during installation and construction so no evidence
remains of corrective work. If results of restoration are unsuccessful, as determined by
Architect, remove damaged units and replace with new units.
1.
Touch up minor abrasions in finishes with air-dried coating that matches color and gloss
of, and is compatible with, factory-applied finish coating.
END OF SECTION
Section 08 90 00
Louvers and Vents
DIVISION 09
FINISHES
SUMMARY
A.
1.2
Section includes: Exposed, buried, and submerged metal, exposed PVC and CPVC, exposed
FRP, and aluminum and dissimilar metals, to be protective painted, whether specifically
mentioned or not, except as specified otherwise. Prime coat structural steel surfaces, as
specified herein. Exterior concrete surfaces will not be protective painted except as specified
herein. Interior concrete surfaces will be protective painted as specified herein.
REFERENCES
A.
1.3
A.
Section 09 90 00
Painting and Protective Coatings
11.
1.4
SUBMITTALS
A.
Shop Drawings:
1.
Data Sheets:
a.
For each paint system, furnish a Paint System Data Sheet (PSDS), the
Manufacturers Technical Data Sheets, and paint colors available (where
applicable) for each product used in the paint system. The PSDS form is
appended to the end of this section.
b.
Submit required information on a system-by-system basis.
c.
Furnish copies of paint system submittals to the coating applicator.
d.
Indiscriminate submittal of Manufacturers literature only is not acceptable.
e.
Schedule of proposed coating materials.
f.
Schedule of surfaces to be coated with each coating material.
B.
Samples:
1.
Reference Panel:
a.
Prior to start of surface preparation, furnish a 4 by 4 steel panel for each grade of
sandblast specified herein, prepared to specified requirements.
b.
Provide panel representative of the steel used; prevent deterioration of surface
quality.
c.
Upon approval of Engineer, panel to be reference source for inspection.
d.
Unless otherwise specified, before painting work is started, prepare minimum 8 by
10 samples with type of paint and application specified on similar substrate to
which paint is to be applied.
e.
Furnish additional samples as required until colors, finishes, and textures are
approved.
f.
Approved samples to be the quality standard for final finishes.
C.
D.
1.5
QUALITY ASSURANCE
A.
Qualifications:
1.
Applicator: Minimum 5 years experience in application of specified products.
B.
Regulatory Requirements:
1.
Meet federal, state, and local requirements limiting the emission of volatile organic
compounds.
2.
Perform surface preparation and painting in accordance with recommendations of the
following:
a.
Paint Manufacturers instructions.
b.
SSPC-PA Guide No. 3, Guide to Safety in Paint Applications.
c.
Federal, state, and local agencies having jurisdiction.
Section 09 90 00
Painting and Protective Coatings
C.
1.6
Mockup:
1.
Before proceeding with work under this section, finish one complete space or item of
each color scheme required showing selected colors, finish texture, materials, quality of
work, and special details.
2.
After approval, sample spaces or items shall serve as a standard for similar work
throughout the Project.
DELIVERY, STORAGE AND HANDLING
A.
Store products in a protected area that is heated or cooled to maintain temperatures within the
range recommended by paint Manufacturer.
B.
Shipping:
1.
Where pre-coated items are to be shipped to the site, protect coating from damage.
Batten coated items to prevent abrasion.
2.
Use nonmetallic or padded slings and straps in handling.
1.7
ENVIRONMENTAL REQUIREMENTS
A.
B.
Do not perform abrasive blast cleaning whenever relative humidity exceeds 85%, or whenever
surface temperature is less than 5 F above dew point of ambient air.
1.8
SPECIAL GUARANTEE
A.
B.
Contractor and paint Manufacturer shall jointly and severally furnish guarantee.
PART 2 - PRODUCTS
2.1
Nationally recognized Manufacturers of paints and protective coatings who are regularly
engaged in the production of such materials for essentially identical service conditions.
B.
Manufacturers:
1.
Tnemec Coatings
2.
Sherwin Williams
3.
Quadex, Inc.
4.
Sauereisen
5.
Devoe Coatings, an Akzo Nobel Corporate brand.
6.
Carboline Coatings Company
7.
Or Approved Equal.
2.2
ABRASIVE MATERIALS
A.
Select abrasive type and size to produce surface profile that meets coating Manufacturers
recommendations for specific primer and coating system to be applied.
Section 09 90 00
Painting and Protective Coatings
2.3
PAINT MATERIALS
A.
General:
1.
Manufacturers highest quality products suitable for intended service.
2.
Compatibility: Only compatible materials from a single Manufacturer shall be used in the
work. Particular attention shall be directed to compatibility of primers and finish coats.
3.
Thinners, Cleaners, Driers, and other additives: As recommended by Manufacturer of
coating material.
B.
Products:
Product
Definition
Coating designed to prevent bleeding of black asphaltic varnish through finish paint; Shellac is a
suitable alternate; not applicable for white and pastel colors
Anticorrosive Polyamide
Polyamide, anticorrosive, converted epoxy primer
Epoxy Primer
containing rust-inhibitive pigments
Coal-Tar Epoxy
Amine or phenolic epoxy type: 70% volume solids
minimum, suitable for immersion service
Organic Zinc Rich Primer
Converted epoxy, epoxy/phenolic or urethane type,
minimum 10 pounds metallic zinc content per gallon
Rust Inhibitive Primer
Single Package steel primaers with anticorrosive
pigment loading
Wash Primer
Vinyl butyral acid
Epoxy Nonskid (AggrePolyamide or amine converted epoxies aggregated;
gated)
aggregate may be packaged separately
Epoxy Filler/Surfacer
100% solids epoxy trowel grade filler and nonshrinking,,surfacer, suitable for application to concrete and masonry. Approved for potable water
contact and conforming to NSF 61, where required
High Build Epoxy
Polyamide or polyamidoamine epoxy, minimum
69% volume solids, capability of 4 to 8 MDFT per
coat
1.
High temperature coating 150 to 350 degrees Fahrenheit: As manufactured by one of the
following:
a.
Carboline: Thermaline 4900.
b.
Dampney: Thermalox 245 Silicione Zinc Dust
c.
PPG Amercoat: Amerlock 2/400 GFK.
Tar Stop
2.4
MIXING
A.
Multiple-Component Coatings:
1.
Prepare using the contents of the container for each component as packaged by paint
Manufacturer.
2.
No partial batches will be permitted.
3.
Do not use multiple-component coatings that have been mixed beyond their pot life.
4.
Furnish small quantity kits for touchup painting and for painting other small areas.
5.
Mix only components specified and furnished by paint Manufacturer.
6.
Do not intermix additional components for reasons of color or otherwise, even within the
same generic type of coating.
B.
Colors: Formulate paints with colorants free of lead, lead compounds, or other materials that
might be affected by presence of hydrogen sulfide or other gas likely to be present at the site.
Section 09 90 00
Painting and Protective Coatings
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
Schedule inspection with Engineer in advance for cleaned surfaces and all coats prior to
succeeding coat.
3.2
PREPARATION
A.
B.
Field Abrasive Blasting: Perform blasting for items and equipment where specified and as
required to restore damaged surfaces previously shop or field blasted and primed.
C.
3.3
PREPARATION OF SURFACES
A.
Metal Surfaces:
1.
Where indicated, meet requirements of the following SSPC Specifications:
a.
Solvent Cleaning: SP 1.
b.
Hand Tool Cleaning: SP 2.
c.
Power Tool Cleaning: SP 3.
d.
White Metal Blast Cleaning: SP 5.
e.
Commercial Blast Cleaning: SP 6.
f.
Brush-Off Blast Cleaning: SP 7.
g.
Pickling: SP 8.
h.
Near-White Blast Cleaning: SP 10.
i.
Power Tool Cleaning to Bare Metal: SP 11.
j.
Surface Preparation of Concrete: SP 13.
2.
The words solvent cleaning, hand tool cleaning, wire brushing and blast cleaning,
or similar words of equal intent in these Specifications, or in paint manufacturers
specifications, refer to the applicable SSPC Specifications.
Section 09 90 00
Painting and Protective Coatings
3.
4.
5.
6.
7.
8.
9.
10.
B.
Where OSHA or EPA regulations preclude standard abrasive blast cleaning, wet or vacublast methods may be required. Coating Manufacturers recommendations for wet blast
additives and first coat application shall apply. If not otherwise required, contractor shall
provide abrasive blast cleaning by means of sand blasting or high pressure water.
DeLavaud Process Ductile Iron Pipe:
a.
Use SSPC SP grades as guide only.
b.
For high performance (epoxy) coatings, follow recommendations of pipe and
coating Manufacturers.
c.
The surface preparation and application of the primer and finish coats shall be
performed by the pipe Manufacturer
d.
For conventional (alkyd) coatings, clean asphalt varnish supplied on pipe and
apply one full coat of a tar stop before two full coats of the color coats specified.
Hand tool clean areas that cannot be cleaned by power tool cleaning.
Round or chamfer sharp edges and grind smooth burrs, jagged edges, and surface
defects.
Welds and Adjacent Areas:
a.
Prepare such that there is:
1) No undercutting or reverse ridges on weld bead.
2) No weld spatter on or adjacent to weld or any other area to be painted.
3) No sharp peaks or ridges along weld bead.
b.
Grind embedded pieces of electrode or wire flush with adjacent surface of weld
bead.
Pre-blast Cleaning Requirements:
a.
Remove oil, grease, welding fluxes, and other surface contaminants prior to blast
cleaning.
b.
Cleaning Methods: Steam, hot water, or cold water with appropriate detergent
additives followed with clean water rinsing.
c.
Clean small isolated areas as above or solvent clean with suitable solvents and
clean cloths.
Blast Cleaning Requirements:
a.
Type of Equipment and Speed of Travel: Design to obtain specified degree of
cleanliness. Minimum surface preparation is as specified herein and takes
precedence over coating Manufacturers recommendations.
b.
Select type and size of abrasive to produce a surface profile that meets coating
Manufacturers recommendations for particular primer to be used.
c.
Use only dry blast cleaning methods, unless otherwise directed in writing by
Engineer.
d.
Do not reuse abrasive material, except for designed recyclable systems. Must
meet applicable federal, state, and local air pollution and environmental control
regulations for blast cleaning, confined space entry (if required), and disposition of
spent aggregate and debris.
Post-Blast Cleaning and Other Cleaning Requirements:
a.
Clean surfaces of dust and residual particles from cleaning operations by dry (no
oil or water vapor) air blast cleaning or other method prior to painting. Vacuum
clean enclosed areas and other areas where dust settling is a problem and wipe
with a tack cloth.
b.
Paint surfaces the same day they are blasted. Re-blast surfaces that have started
to rust before they are painted.
Galvanized Surfaces:
1.
Remove soil, cement spatter, and other surface dirt with appropriate hand or power tools.
2.
Remove oil and grease by wiping or scrubbing the surface with a suitable solvent, rags
and brushes. Use clean solvent and clean rags for the final wiping to avoid contaminating
the surface.
3.
Obtain coating Manufacturers recommendations for additional preparation that may be
required.
Section 09 90 00
Painting and Protective Coatings
C.
Concrete Surfaces:
1.
Do not begin until 30 days after concrete has been placed.
2.
Remove grease, oil, dirt, salts or other chemicals, loose materials, or other foreign matter
by solvent, detergent, or other suitable cleaning methods.
3.
Clean to remove loose concrete and provide a surface for binding according to SP-13
Surface Preparation of Concrete. Surface may not be cleaned by acid etching or open
flame methods unless approved in writing by Engineer. Contractor must provide evidence
that method will produce desired profile without causing damage to concrete member.
a.
Mechanical Surface Preparation Methods: (according to section 4 of SP-13)
1)
Dry abrasive blasting (sand blasting)
2)
Wet abrasive blasting
3)
Vacuum-assisted abrasive blasting
b.
Vacuum cleaning, air blast cleaning, and/or water cleaning as described by ASTM
D4258 shall be used after the completion of one or more of the mechanical surface
preparation methods listed above.
c.
Final surface preparation shall be as required by coatings manufacturer to insure
proper adhesion of the coatings, as needed.
4.
Contractor is responsible for coordinating and insuring that manufacturers protective
coatings are compatible with mortar repair or cement lining prior to submitting coatings.
5.
Unless otherwise required for proper adhesion, ensure surfaces are dry prior to painting.
D.
Plastic Surfaces:
1.
Hand sand plastic surfaces to be coated with a medium grit sandpaper to provide tooth
for the coating system.
2.
Large areas may be power sanded or brush-off blasted, provided sufficient controls are
employed so surface is roughened without removing excess material.
3.4
B.
Acid Etching:
1.
After pre-cleaning, spread the following solution by brush or plastic sprinkling can: 1 part
commercial Muriatic acid reduced by 2 parts water by volume. Adding acid to water in
these proportions gives an approximate 10% solution of HCl.
2.
Application:
a.
Application Rate: Approximately 2 gallons per 100 square feet.
b.
Work acid solution into surface by hard-bristled brushes or brooms until complete
wetting and coverage is obtained.
c.
Acid will react vigorously for a few minutes, during which time brushing is
continued.
d.
After bubbling subsides (10 minutes), hose down the remaining slurry with high
pressure clean water.
e.
Rinse immediately to avoid formation on the surface of salts that are difficult to
remove.
Section 09 90 00
Painting and Protective Coatings
f.
3.
4.
C.
3.5
Thoroughly rinse to remove any residual acid surface condition which can impair
adhesion.
Ensure surface is completely dry before application of coating.
Apply acid etching, to obtain a grit sandpaper surface profile. If not, repeat treatment.
Solvent Cleaning:
1.
Consists of removal of foreign matter such as oil, grease, soil, drawing and cutting
compounds, and any other surface contaminants by using solvents, emulsions, cleaning
compounds, steam cleaning, or similar materials and methods which involve a solvent or
cleaning action.
2.
Meets requirements of SSPC-SP 1.
APPLICATION
A.
General:
1.
Extent of Coating (Immersion): Coatings shall be applied to all internal vessel and pipe
surfaces, nozzle bores, flange gasket sealing surfaces, carbon steel internals, and
stainless steel internals, unless otherwise specified.
2.
For coatings subject to immersion, obtain full cure for completed system. Consult
coatings Manufacturers written instructions for these requirements. Do not immerse
coating for any purpose until completion of curing cycle.
3.
Apply coatings in accordance with these Specifications and the paint Manufacturers
printed recommendations and special details. The more stringent requirements shall
apply. Allow sufficient time between coats to assure thorough drying of previously applied
paint.
4.
Apply each coat of paint slightly darker than preceding coat unless otherwise approved.
5.
Sand wood and metal lightly between coats to achieve required finish.
6.
Vacuum clean surfaces free of loose particles. Use tack cloth just prior to applying next
coat.
7.
Fusion Bonded Coatings Method Application: Electrostatic, fluidized bed, or flocking.
8.
Coat units or surfaces to be bolted together or joined closely to structures or to one
another prior to assembly or installation.
9.
Where more than one coat of a material is applied within a given system, alternate color
to provide a visual reference that the required number of coats have been applied.
B.
Galvanized Metal:
1.
Concealed galvanized surfaces (behind building panels or walls) do not required painting
unless specifically indicated herein.
2.
Prepare surface and apply wash primer or coating Manufacturers recommended coating.
This primer will replace the required paint systems indicated primer.
3.
Apply coating system appropriate for the exposure (intermediate/finish coats).
C.
D.
E.
Film Thickness:
Section 09 90 00
Painting and Protective Coatings
1.
2.
3.
4.
5.
6.
Number of Coats: Minimum required without regard to coating thickness. Additional coats
may be required to obtain minimum required paint thickness, depending on method of
application, differences in Manufacturers products, and atmospheric conditions.
Maximum film build per coat shall not exceed coating Manufacturers recommendations.
Film Thickness Measurements and Electrical Inspection of Coated Surfaces:
a.
Perform with properly calibrated instruments.
b.
Recoat and repair as necessary for compliance with the Specifications.
c.
All coats are subject to inspection by Engineer and coating manufacturers
representative.
Visually inspect concrete, nonferrous metal, plastic, and wood surfaces to ensure proper
and complete coverage has been attained.
Give particular attention to edges, angles, flanges, and other similar areas, where
insufficient film thicknesses are likely to be present, and ensure proper millage in these
areas.
Thickness Testing:
a.
After repaired and recoated areas have dried sufficiently, final tests will be
conducted by the Engineer.
b.
Measure coating thickness specified in mils with a magnetic type dry film thickness
gauge.
c.
Test finish coat, except zinc primer, galvanizing, and elastomeric coatings in
excess of 25 mils dry, for holidays and discontinuities with an electrical holiday
detector.
d.
Holiday detect coatings in excess of 25 mils dry with high voltage units
recommended by the coating manufacturer.
e.
Check each coat for correct millage. Do not make measurement before a minimum
of 8 hours after application of coating.
F.
G.
H.
Unsatisfactory Application:
1.
If item has an improper finish color, or insufficient film thickness, clean surface and
topcoat with specified paint material to obtain specified color and coverage. Obtain
specific surface preparation information from coating manufacturer.
2.
Hand or power sand visible areas of chipped, peeled, or abraded paint, and feather the
edges. Follow with primer and finish coat. Depending on extent of repair and appearance,
a finish sanding and topcoat may be required.
3.
Evidence of runs, bridges, shiners, laps, or other imperfections is cause for rejection.
4.
Repair defects in accordance with written recommendations of coating Manufacturer.
5.
Leave staging and lighting up until Engineer has inspected surface or coating. Replace
staging removed prior to approval by Engineer. Provide additional staging and lighting as
requested by Engineer.
3.6
Testing Gauges:
Section 09 90 00
Painting and Protective Coatings
1.
2.
3.
3.7
Provide a magnetic type dry film thickness gauge to test coating thickness specified in
mils, as manufactured by Nordson Corp., Anaheim, CA, Mikrotest.
Provide an electrical holiday detector, low voltage, wet sponge type to test finish coat,
except zinc primer, high-build elastomeric coatings, and galvanizing, for holidays and
discontinuities as manufactured by Tinker and Rasor, San Gabriel, CA, Model M-1.
Provide a high voltage holiday detector for elastomeric coatings in excess of 25 mils dry
film thickness. Unit to be as recommended by the coating Manufacturer.
MANUFACTURERS SERVICES
A.
3.8
A.
Place cloths and waste that might constitute a fire hazard in closed metal containers or destroy
at the end of each day.
B.
Upon completion of the Work, remove staging, scaffolding, and containers from the site or
destroy in a legal manner.
C.
Completely remove paint spots, oil, or stains upon adjacent surfaces and floors and leave entire
job clean.
3.9
All finish coating colors to be submitted for Owner/Engineer selection and/or approval, as
applicable.
B.
Paint Material
Abrasive Blast, or
Polyamide, Anticorrosive
Centrifugal Wheel
Blast (SP 5)
Epoxy Primer
Polyamide High Build
Epoxy
C.
1 coat, 6 MDFT
Paint Material
Abrasive Blast, or
Prime in accordance
Centrifugal Wheel
Blast (SP 5)
with manufacturers
recommendations
Coal Tar Epoxy
10
2 coats minimum,
20 MDFT
Section 09 90 00
Painting and Protective Coatings
D.
Paint Material
Abrasive Blast, or
Polyamide, Anticorrosive
Centrifugal Wheel
Blast (SP 10)
Epoxy Primer
Polyamide High Build
Epoxy
Polyurethane Enamel
E.
Paint Material
Abrasive Blast, or
Polyamide,
Centrifugal Wheel
Blast (SP 10)
Anticorrosive Epoxy
Primer
Polyamide High Build
Epoxy
Polyurethane Enamel
2 coats minimum,
15 MDFT
1 coat, 3 MDFT
1 coat, 5 MDFT
1 coat, 3 MDFT
Paint Material
Centrifugal Wheel
Blast (SP 10)
G.
1 coat, 5 MDFT
F.
instructions
Paint Material
Abrasive Blast or
Centrifugal Wheel.
Blast (SP 10)
Enamel
-ORCoal-Tar Epoxy
-OR-
AWWA C210
AWWA C214
Sec. Al.5
Sec. A1.5
11
Section 09 90 00
Painting and Protective Coatings
Surface Prep.
Paint Material
Tape Coat System
H.
Paint Material
Wash Primer or
Followed by Hand
Tool (SP 2) or Power
Tool (SP 3)
Coating Manufacturers
Recommendation
Remaining coats as
required for exposure
I.
Paint Material
1 coat, 3 MDFT
Followed by Hand
Primer
Paint Material
Epoxy Primer
Epoxy Nonskid
2 coats minimum,
18 MDFT
(Aggregated)
K.
L.
Paint Material
Polyamide High Build
Epoxy
Poly Urethane Enamel
Paint Material
Wash Primer
1 coat, 1 MDFT
1 coat, 10 MDFT
12
Section 09 90 00
Painting and Protective Coatings
M.
N.
Paint Material
Surface Repair Mortar or
Epoxy Filler
SP 13
O.
Paint Material
1 coat, 10 MDFT
Polyurethane Enamel
1 coat, 3 MDFT
Paint Material
Surface Repair Mortar or
Epoxy Filler
SP 13
Q.
Paint Material
System No. 20 New Concrete/CMU- Below Grade (as required by application schedule):
Surface Prep.
SP 13
Paint Material
Surface Repair Mortar or
Epoxy Filler
13
Section 09 90 00
Painting and Protective Coatings
3.10
A.
3.11
Paint Material
APPLICATION SCHEDULE
A.
Unless otherwise shown or specified, paint surfaces in accordance with the following application
schedule. In the event of discrepancies or omissions, request clarification from Engineer before
starting work in question.
B.
C.
System No. 2 Submerged Metal- Domestic Sewage: Use on the following items or areas:
1.
Metal surfaces new and existing below a plane 1 foot above maximum liquid surface,
metal surfaces above maximum liquid surface that are a part of immersed equipment,
concrete embedded surfaces of metallic items, such as wall pipes, pipes, pipe sleeves,
access manholes, gate guides and thimbles, and structural steel.
2.
Pumps, motors, equipment items, and accessories identified in the technical
specifications to be coated with this system.
D.
System No. 3 Exposed Metal- Highly Corrosive: Use on the following items or areas:
1.
All exposed structural steel, metal building structure, bolted connections, and other
exposed metal structures that are part of the following areas:
2.
Pumps, motors, equipment items, and accessories identified in the technical
specifications to be coated with this system.
3.
Pipe, valves, pipe hangers, supports and saddles, conduit, cable tray hangers, and
supports.
4.
Valve and gate operator and stands.
5.
Mechanical equipment supports, drive units, and accessories.
E.
System No. 4 Exposed Metal- Mildly Corrosive: Use on the following items or areas:
1.
Exposed metal surfaces, new and existing located inside or outside of structures and
exposed to weather or in a highly humid atmosphere, such as vaults, chemical rooms,
and other similar areas and as outlined below:
a.
Pump Station Wet Well canopy framing.
b.
Disinfection Station Car Wash boom support column.
14
Section 09 90 00
Painting and Protective Coatings
2.
3.
4.
5.
6.
7.
Interior exposed structural steel, metal building structure, bolted connection and other
exposed metal structures of Pump Station electrical room and Disinfection Station
building.
Pumps, motors, equipment items, and accessories identified in the technical
specifications to be coated with this system.
Pipe, valves, pipe hangers, supports and saddles, conduit, cable tray hangers, and
supports.
Valve and gate operator and stands.
Mechanical equipment supports, drive units, and accessories.
Insulated piping, Polyurethane topcoat not required.
F.
System No. 4A Exposed Metal-High Temperature (150 to 350 degrees Fahrenheit): Use on the
following areas or items:
1.
Metal surfaces subject to temperatures ranging from 150 to 350 degrees Fahrenheit.
2.
Blowers, blower piping, and blower accessories, pumps, motors, equipment items, and
accessories identified in the technical specifications to be coated with this system.
G.
System No. 5 Buried Metal- General: Use on the following items or areas:
1.
Buried, below-grade portions of steel items, except buried stainless steel or ductile iron
pipe.
H.
System No. 10 Galvanized Metal Conditioning: Use on the following items or areas:
1.
Galvanized surfaces requiring painting.
2.
After application of System 10, apply finish coats as required for exposure.
I.
System No. 11 Galvanized Metal Repair: Use on the following items or areas:
1.
New or existing galvanized surfaces that are abraded, chipped, or otherwise damaged.
J.
System No. 12 Skid-Resistant-Aluminum and FRP: Use on the following items or areas:
1.
Checker plate at exterior and interior wet locations.
2.
Aluminum plank at all exterior and interior accessible walking surfaces including, but not
limited to:
a.
AL Hatch at the Pump Station Wet Well.
K.
L.
System No. 15 Aluminum and Dissimilar Metal Insulation: Use on the following items or areas:
1.
Aluminum surfaces embedded or in contact with concrete, masonry, and other metals.
2.
Stainless steel surfaces embedded in concrete.
3.
Dissimilar metals for electrical insulation.
4.
All other miscellaneous aluminum framing members and pipe supports.
M.
N.
15
Section 09 90 00
Painting and Protective Coatings
2.
All exposed exterior surfaces shall receive coatings for moisture protection and
architectural painting as indicated below:
O.
P.
Q.
System No. 20 New Concrete/CMU- Below Grade (as indicated below only):
1.
All surfaces as indicated on the drawings.
2.
All unexposed below grade surfaces shall receive coatings for moisture protection as
indicated below:
a.
Intake Structure Headwall.
b.
Exterior of Pump Station Wet Well.
c.
Exterior of foundations for Pump Station electrical room.
R.
Surfaces Not Requiring Protective Painting: Unless otherwise stated or shown, the following
areas or items will not require protective painting or coating:
1.
Reinforcing steel.
2.
Nonferrous and corrosion-resistant ferrous alloys such as copper, bronze, Monel,
aluminum, chromium plate, atmospherically exposed weathering steel, and stainless
steel, except where:
a.
Required for electrical insulation between dissimilar metals.
b.
Aluminum and stainless steel are embedded in concrete or masonry, or aluminum
is in contact with concrete or masonry.
c.
Color coding of equipment and piping is required.
3.
Nonmetallic materials such as glass, PVC, wood, porcelain, and plastic (FRP) except as
required for exposed-to-view PVC and CPVC, as required for FRP without integral UV
resistant gel coat, and as required for architectural painting or color coding.
4.
Pre-finished electrical items such as motor control centers, switchboards, switchgear,
panelboards, transformers, disconnect switches (if pre-finished in OSHA yellow); except
color coding of equipment is required.
5.
Non-submerged electrical conduits attached to unpainted concrete surfaces.
6.
Cathodic protection anodes.
3.12
COLORS
A.
General: Provide manufacturers full range of color charts to Owner/Owners Representative for
selection and/or approval. Provide colors as indicated in, Door and Hardware Schedule, Interior
Finish Schedule, Exterior Finish Schedule, as shown on the drawings, as selected by Owner,
and as designated herein.
B.
16
Section 09 90 00
Painting and Protective Coatings
C.
Proprietary identification of colors is for identification only. Selected Manufacturer may supply
matches.
D.
Equipment Colors:
1.
Equipment includes the machinery or vessel itself plus the structural supports and
fasteners and attached electrical conduits.
2.
Paint equipment and piping one color as selected.
3.
Paint non submerged portions of equipment the same color as the piping it serves,
except as itemized below:
a.
Dangerous Parts of Equipment and Machinery: OSHA Orange.
b.
Fire Protection Equipment and Apparatus: OSHA Red.
c.
Radiation Hazards: OSHA Purple.
d.
Physical hazards in normal operating area and energy lockout devices, including,
but not limited to, electrical disconnects for equipment and equipment isolation
valves in air and liquid lines under pressure: OSHA Yellow.
4.
Fiberglass reinforced plastic (FRP) equipment with an integral colored gel coat does not
require painting, provided the color is as selected.
END OF SECTION
17
Section 09 90 00
Painting and Protective Coatings
Product Name/Number
(Proprietary)
09 90 00 Supplement
Paint System Data Sheet
DIVISION 10
SPECIALTIES
SUMMARY
A.
1.2
Section includes: portable, hand-carried fire extinguishers and mounting brackets for fire
extinguishers.
1.
Owner-Furnished Material: Hand-carried fire extinguishers.
SUBMITTALS
A.
Product Data: For each type of product indicated. Include rating and classification, material
descriptions, dimensions of individual components and profiles, and finishes for fire
extinguisher and mounting brackets.
B.
Operation and Maintenance Data: For fire extinguishers to include in maintenance manuals.
C.
1.3
QUALITY ASSURANCE
A.
NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10, "Portable
Fire Extinguishers."
B.
Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent
testing agency acceptable to authorities having jurisdiction.
1.
Provide fire extinguishers approved, listed, and labeled by FMG.
1.4
COORDINATION
A.
1.5
Coordinate type and capacity of fire extinguishers with fire protection cabinets to ensure fit and
function.
WARRANTY
A.
PART 2 - PRODUCTS
2.1
Fire Extinguishers: Type, size, and capacity for each mounting bracket indicated.
1.
Manufacturers: Subject to compliance with requirements, available manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
the following:
a.
Amerex Corporation.
b.
Ansul Incorporated; Tyco International Ltd.
c.
Badger Fire Protection; a Kidde company.
d.
Buckeye Fire Equipment Company.
Section 10 44 16
Fire Extinguishers
2.
3.
4.
5.
B.
2.2
e.
Fire End & Croker Corporation.
f.
J. L. Industries, Inc.; a division of Activar Construction Products Group.
g.
Kidde Residential and Commercial Division; Subsidiary of Kidde plc.
h.
Larsen's Manufacturing Company.
i.
Moon-American.
j.
Pem All Fire Extinguisher Corp.; a division of PEM Systems, Inc.
k.
Potter Roemer LLC.
l.
Pyro-Chem; Tyco Safety Products.
Basis-of-Design Product: Subject to compliance with requirements, provide Ansul
Incorporated, Sentry 20, Model AA20 or comparable product by one of the manufacturer
above:
Valves: Manufacturer's standard.
Handles and Levers: Manufacturer's standard.
Instruction Labels:
Include pictorial marking system complying with NFPA 10,
Appendix B and bar coding for documenting fire extinguisher location, inspections,
maintenance, and recharging.
A.
Mounting Brackets:
Manufacturer's standard galvanized steel, designed to secure fire
extinguisher to wall or structure, of sizes required for types and capacities of fire extinguishers
indicated, with plated or black baked-enamel finish.
1.
Manufacturers: Subject to compliance with requirements, available manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
the following:
2.
Basis-of-Design Product: Subject to compliance with requirements, of the manufacturer
of the fire extinguisher or comparable product by one of the following:
a.
Amerex Corporation.
b.
Ansul Incorporated; Tyco International Ltd.
c.
Badger Fire Protection; a Kidde company.
d.
Buckeye Fire Equipment Company.
e.
Fire End & Croker Corporation.
f.
J. L. Industries, Inc.; a division of Activar Construction Products Group.
g.
Larsen's Manufacturing Company.
h.
Potter Roemer LLC.
B.
Identification: Lettering complying with authorities having jurisdiction for letter style, size,
spacing, and location. Locate as indicated by Architect.
1.
Identify bracket-mounted fire extinguishers with the words "FIRE EXTINGUISHER" in red
letter decals applied to mounting surface.
a.
Orientation: Vertical.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
Section 10 44 16
Fire Extinguishers
3.2
INSTALLATION
A.
General: Install fire extinguishers and mounting brackets in locations indicated and in
compliance with requirements of authorities having jurisdiction.
1.
Mounting Brackets: 54 inches above finished floor to top of fire extinguisher.
B.
Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, at locations
indicated.
END OF SECTION
Section 10 44 16
Fire Extinguishers
DIVISION 13
SPECIAL CONSTRUCTION
SUMMARY
A.
Section Includes:
1.
Structural-steel framing.
2.
Metal roof panels.
3.
Metal wall panels.
4.
Metal gutters and downspouts.
5.
Accessories.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 05 50 00 - Metal Fabrications
b.
Section 07 21 01 - Metal Building Insulation
c.
Section 08 11 13 - Steel Doors and Frames
d.
Section 08 71 00 - Door Hardware
e.
Section 08 90 00 - Louvers and Vents
f.
Section 09 90 00 - Painting and Protective Coatings
1.2
DEFINITIONS
A.
1.3
Terminology Standard: See MBMAs "Metal Building Systems Manual" for definitions of terms
for metal building system construction not otherwise defined in this Section or in referenced
standards.
SUBMITTALS
A.
Product Data: For each type of metal building system component. Include construction details,
material descriptions, dimensions of individual components and profiles, and finishes for the
following:
1.
Structural-steel-framing system.
2.
Metal roof panels.
3.
Metal soffit panels.
4.
Metal wall panels.
5.
Metal gutters and downspouts.
6.
Accessories.
B.
Shop Drawings: For the following metal building system components. Include plans,
elevations, sections, details, and attachments to other work.
1.
Anchor-Bolt Plans: Submit anchor-bolt plans and templates before foundation work
begins. Include location, diameter, embedment depth, and projection of anchor bolts
required to attach metal building to foundation. Indicate column reactions at each
location.
Section 13 34 19
Metal Building Systems
2.
3.
4.
C.
Samples for Initial Selection: For units with factory-applied color finish.
D.
Delegated-Design Submittal: For metal building systems indicated to comply with performance
requirements and design criteria, provide signed and sealed shop drawings by a qualified
professional engineer licensed in the state of the work and responsible for their preparation.
E.
Welding certificates.
F.
Metal Building System Certificates: For each type of metal building system, from manufacturer.
1.
Letter of Design Certification: Signed and sealed by a qualified professional engineer.
Include the following:
a.
Name and location of Project.
b.
Order number.
c.
Name of manufacturer.
d.
Name of Contractor.
e.
Building dimensions including width, length, height, and roof slope.
f.
Indicate compliance with AISC standards for hot-rolled steel and AISI standards for
cold-rolled steel, including edition dates of each standard.
g.
Governing building code and year of edition.
h.
Design Loads: Include dead load, roof live load, collateral loads, roof snow load,
deflection, wind loads/speeds and exposure, seismic design category or effective
peak velocity-related acceleration/peak acceleration, and auxiliary loads (cranes).
1). Verify that building frame meets the deflection criteria for supporting a CMU
wall.
i.
Load Combinations: Indicate that loads were applied acting simultaneously with
concentrated loads, according to governing building code.
j.
Building-Use Category: Indicate category of building use and its effect on load
importance factors.
k.
AISC Certification for Category MB: Include statement that metal building system
and components were designed and produced in an AISC-Certified Facility by an
AISC-Certified Manufacturer.
G.
H.
I.
Section 13 34 19
Metal Building Systems
J.
K.
Maintenance Data: For metal panel finishes and door hardware to include in maintenance
manuals.
L.
1.4
QUALITY ASSURANCE
A.
B.
Erector Qualifications: An experienced erector who specializes in erecting and installing work
similar in material, design, and extent to that indicated for this Project and who is acceptable to
manufacturer.
C.
Testing Agency Qualifications: Qualified according to ASTM E 329 for testing indicated.
D.
Source Limitations:
Obtain metal building system components, including primary and
secondary framing and metal panel assemblies, from single source from single manufacturer.
E.
F.
Structural Steel: Comply with AISC 360, "Specification for Structural Steel Buildings," for design
requirements and allowable stresses.
G.
Cold-Formed Steel: Comply with AISIs "North American Specification for the Design of ColdFormed Steel Structural Members" for design requirements and allowable stresses.
H.
Fire-Resistance Ratings: Where indicated, provide metal panel assemblies identical to those of
assemblies tested for fire resistance per ASTM E 119 by a qualified testing agency. Identify
products with appropriate markings of applicable testing agency.
1.
Indicate design designations from ULs "Fire Resistance Directory" or from the listings of
another qualified testing agency.
2.
Combustion Characteristics: ASTM E 136.
I.
Section 13 34 19
Metal Building Systems
c.
3.
1.5
Flashings, special roof details, roof drainage, roof penetrations, equipment curbs,
and condition of other construction that will affect metal roof panels.
d.
Temporary protection requirements for metal roof panel assembly during and after
installation.
e.
Roof observation and repair after metal roof panel installation.
Review methods and procedures related to metal wall panel assemblies including, but
not limited to, the following:
a.
Compliance with requirements for support conditions, including alignment between
and attachment to structural members.
b.
Structural limitations of girts and columns during and after wall panel installation.
c.
Flashings, special siding details, wall penetrations, openings, and condition of
other construction that will affect metal wall panels.
d.
Temporary protection requirements for metal wall panel assembly during and after
installation.
e.
Wall observation and repair after metal wall panel installation.
Deliver components, sheets, panels, and other manufactured items so as not to be damaged or
deformed. Package metal panels for protection during transportation and handling.
B.
Unload, store, and erect metal panels in a manner to prevent bending, warping, twisting, and
surface damage.
C.
Stack metal panels horizontally on platforms or pallets, covered with suitable weather tight and
ventilated covering. Store metal panels to ensure dryness, with positive slope for drainage of
water. Do not store metal panels in contact with other materials that might cause staining,
denting, or other surface damage.
1.6
PROJECT CONDITIONS
A.
Weather Limitations: Proceed with installation only when weather conditions permit metal
panels to be installed according to manufacturers written instructions and warranty
requirements.
B.
Field Measurements:
1.
Established Dimensions for Foundations: Comply with established dimensions on
approved anchor-bolt plans, establishing foundation dimensions and proceeding with
fabricating structural framing without field measurements. Coordinate anchor-bolt
installation to ensure that actual anchorage dimensions correspond to established
dimensions.
2.
Established Dimensions for Metal Panels: Where field measurements cannot be made
without delaying the Work, either establish framing and opening dimensions and proceed
with fabricating metal panels without field measurements, or allow for field trimming metal
panels. Coordinate construction to ensure that actual building dimensions, locations of
structural members, and openings correspond to established dimensions.
1.7
COORDINATION
A.
Coordinate sizes and locations of concrete foundations and anchor bolts with Engineer prior to
fabricating building or forming foundations. Concrete, reinforcement, and formwork
requirements are specified in section 03 30 00 Cast-in-Place Concrete. Anchor bolt
requirements are specified in section 05 50 00 Metal Fabrications.
Section 13 34 19
Metal Building Systems
B.
Coordinate size, location, and framing requirements for all misc. items and openings including
louvers, hatches, piping supports and penetrations, electrical boxes and switches, lighting,
conduit, etc. All items are not necessarily shown on structural plans. See also mechanical,
HVAC, electrical, and civil plans.
C.
Coordinate shop primer with finish coating system, as specified in 09 90 00 Painting and
Protective Coatings, and coatings manufacturer. Primer should be compatible with finish coating
provided by coatings manufacturer.
D.
Coordinate metal panel assemblies with gutters and downspouts, flashing, trim, and
construction of supports and other adjoining work to provide a leak proof, secure, and noncorrosive installation.
1.8
WARRANTY
A.
B.
Special Weather tightness Warranty for Standing-Seam Metal Roof Panels: Manufacturers
standard form in which manufacturer agrees to repair or replace standing-seam metal roof
panel assemblies that leak or otherwise fail to remain weather tight within specified warranty
period.
1.
Warranty Period: 20 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
A.
B.
Primary-Frame Type:
Section 13 34 19
Metal Building Systems
1.
2.
3.
4.
5.
C.
Secondary-Frame Type:
(bypass) girts.
D.
E.
F.
G.
Roof System: Manufacturers standard vertical-rib, standing-seam metal roof panels with fieldinstalled insulation.
2.3
B.
Structural Performance: Metal building systems shall withstand the effects of gravity loads and
the following loads and stresses within limits and under conditions indicated according to
procedures in MBMAs "Metal Building Systems Manual."
1.
Design Loads: As indicated on Drawings.
2.
Design Loads:
As required by MBMAs "Metal Building Systems Manual" and
ASCE/SEI 7.
3.
Deflection Limits: Design metal building system assemblies to withstand design loads
with deflections no greater than the following:
a.
Purlins and Rafters: Vertical deflection of 1/240 of the span.
b.
Girts: Horizontal deflection of 1/240 of the span.
c.
Metal Roof Panels: Vertical deflection of 1/240 of the span.
d.
Design secondary-framing system to accommodate deflection of primary framing
and construction tolerances, and to maintain clearances at openings.
4.
Drift Limits: Engineer building structure to withstand design loads with drift limits no
greater than the following:
a.
Lateral Drift: Maximum of 1/400 of the building height.
5.
Metal panel assemblies shall withstand the effects of gravity loads and loads and
stresses within limits and under conditions indicated according to ASTM E 1592.
C.
Seismic Performance: Metal building systems shall withstand the effects of earthquake motions
determined according to ASCE/SEI 7.
D.
Thermal Movements: Allow for thermal movements resulting from the following maximum
change (range) in ambient and surface temperatures by preventing buckling, opening of joints,
overstressing of components, failure of joint sealants, failure of connections, and other
detrimental effects. Base engineering calculations on surface temperatures of materials due to
both solar heat gain and nighttime-sky heat loss.
1.
Temperature Change (Range): 120 deg F, material surfaces.
Section 13 34 19
Metal Building Systems
E.
Air Infiltration for Metal Roof Panels: Air leakage through assembly of not more than 0.06
cfm/sq. ft. of roof area when tested according to ASTM E 1680 at negative test-pressure
difference of 1.57 lbf/sq. ft.
F.
Water Penetration for Metal Roof Panels: No water penetration when tested according to
ASTM E 1646 at test-pressure difference of 2.86 lbf/sq. ft.
G.
Wind-Uplift Resistance:
Class 60.
H.
Thermal Performance: Provide insulated metal panel assemblies with the following maximum
U-factors and minimum R-values for opaque elements when tested according to ASTM C 1363
or ASTM C 518:
1.
Metal Panel Assemblies:
a.
Wall R-Value: Minimum 19.
b.
Roof R-Value: Minimum 23.
2.4
Provide metal roof panel assemblies that comply with UL 580 for
STRUCTURAL-STEEL FRAMING
A.
B.
Secondary Framing: Manufacturers standard secondary framing, including purlins, girts, eave
struts, flange bracing, base members, gable angles, clips, headers, jambs, and other
miscellaneous structural members. Unless otherwise indicated, fabricate framing from either
cold-formed, structural-steel sheet or roll-formed, metallic-coated steel sheet, pre-painted with
coil coating, to comply with the following:
1.
Purlins: C- or Z-shaped sections; fabricated from built-up steel plates, steel sheet, or
structural-steel shapes; minimum 2-1/2-inch- wide flanges.
a.
Depth: As needed to comply with system performance requirements.
2.
Girts: C- or Z-shaped sections; fabricated from built-up steel plates, steel sheet, or
structural-steel shapes. Form ends of Z-sections with stiffening lips angled 40 to 50
degrees from flange, with minimum 2-1/2-inch- wide flanges.
a.
Depth: As required to comply with system performance requirements
3.
Eave Struts: Unequal-flange, C-shaped sections; fabricated from built-up steel plates,
steel sheet, or structural-steel shapes; to provide adequate backup for metal panels.
4.
Flange Bracing: Minimum 2-by-2-by-1/8-inch structural-steel angles or 1-inch diameter,
cold-formed structural tubing to stiffen primary-frame flanges.
5.
Sag Bracing: Minimum 1-by-1-by-1/8-inch structural-steel angles.
6.
Base or Sill Angles: Minimum 3-by-2-inch zinc-coated (galvanized) steel sheet.
7.
Purlin and Girt Clips: Manufacturers standard clips fabricated from steel sheet. Provide
galvanized clips where clips are connected to galvanized framing members.
8.
Secondary End-Wall Framing: Manufacturers standard sections fabricated from zinccoated (galvanized) steel sheet.
Section 13 34 19
Metal Building Systems
9.
10.
C.
D.
Bolts: Provide plain-finish bolts for structural-framing components that are primed or finish
painted. Provide zinc-plated or hot-dip galvanized bolts for structural-framing components that
are galvanized.
E.
Materials:
1.
W-Shapes: ASTM A 992, ASTM A 572, Grade 50 or 55; or ASTM A 529, Grade 50 or
55.
2.
Channels, Angles, M-Shapes, and S-Shapes: ASTM A 572, Grade 50 or 55; or
ASTM A 529, Grade 50 or 55.
3.
Plate and Bar: ; ASTM A 572, Grade 50 or 55; or ASTM A 529, Grade 50 or 55.
4.
Steel Pipe: ASTM A 53, Type E or S, Grade B.
5.
Cold-Formed Hollow Structural Sections: ASTM A 500, Grade B or C, structural tubing.
6.
Structural-Steel Sheet: Hot-rolled, ASTM A 1011, Structural Steel (SS), Grades 30
through 55, or High-Strength Low-Alloy Steel (HSLAS), Grades 45 through 70; or coldrolled, ASTM A 1008, Structural Steel (SS), Grades 25 through 80, or High-Strength LowAlloy Steel (HSLAS), Grades 45 through 70.
7.
Metallic-Coated Steel Sheet: ASTM A 653, Structural Steel (SS), Grades 33 through 80
or High-Strength Low-Alloy Steel (HSLAS), Grades 50 through 80; with G60 coating
designation; mill phosphatized.
8.
Metallic-Coated Steel Sheet Pre-painted with Coil Coating: Steel sheet, metallic coated
by the hot-dip process and pre-painted by the coil-coating process to comply with
ASTM A 755.
a.
Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653, Structural Steel (SS),
Grades 33 through 80 or High-Strength Low-Alloy Steel (HSLAS), Grades 50
through 80; with G90 coating designation.
b.
Aluminum-Zinc Alloy-Coated Steel Sheet: ASTM A 792, Structural Steel (SS),
Grade 50 or 80; with Class AZ50 coating.
9.
High-Strength Bolts, Nuts, and Washers:
ASTM A 325, Type 1, heavy-hex steel
structural bolts; ASTM A 563 heavy-hex carbon-steel nuts; and ASTM F 436 hardened
carbon-steel washers.
a.
Finish: Plain.
10.
Un-headed Anchor Rods: ASTM F 1554, Grade 36 or ASTM A 572, Grade 50.
a.
Configuration: Straight.
b.
Nuts: ASTM A 563 heavy-hex carbon steel.
c.
Plate Washers: ASTM A 36 carbon steel.
d.
Washers: ASTM F 436 hardened carbon steel.
e.
Finish: Hot-dip zinc coating, ASTM A 153/A 153M, Class C.
F.
Finish: Factory primed. Apply specified primer immediately after cleaning and pre-treating.
1.
Apply primer to primary and secondary framing to a minimum dry film thickness of 1 mil.
a.
Prime secondary framing formed from uncoated steel sheet to a minimum dry film
thickness of 0.5 mil on each side.
2.
Prime galvanized members with specified primer after phosphoric acid pretreatment.
3.
Primer: SSPC-Paint 15, Type I, red oxide.
Section 13 34 19
Metal Building Systems
2.5
Vertical-Rib, Standing-Seam Metal Roof Panels: Formed with vertical ribs at panel edges and
intermediate stiffening ribs symmetrically spaced between ribs; designed for sequential
installation by mechanically attaching panels to supports using concealed clips located under
one side of panels and engaging opposite edge of adjacent panels.
1.
Material: Zinc-coated (galvanized) steel sheet, 0.028-inch nominal thickness.
a.
Exterior Finish: Fluoropolymer.
b.
Color: As selected by Owner or Engineer from manufacturers full range.
2.
Clips: Manufacturers standard, fixed type; fabricated from zinc-coated (galvanized)
steel, aluminum-zinc alloy-coated steel, or stainless-steel sheet.
3.
Joint Type: Panels snapped together.
4.
Joint Type: Mechanically seamed, folded according to manufacturers standard.
5.
Panel Coverage: 24 inches.
6.
Panel Height: 3 inches.
7.
Uplift Rating: UL 60.
B.
Materials:
1.
Metallic-Coated Steel Sheet: Restricted-flatness steel sheet, metallic coated by the hotdip process and pre-painted by the coil-coating process to comply with ASTM A 755.
a.
Zinc-Coated (Galvanized) Steel Sheet: ASTM A 653, G90 coating designation;
structural quality.
b.
Aluminum-Zinc Alloy-Coated Steel Sheet: ASTM A 792, Class AZ50 coating
designation, Grade 40; structural quality.
c.
Surface: Smooth, flat finish.
C.
Finishes:
1.
Exposed Coil-Coated Finish:
a.
Two-Coat Fluoropolymer: AAMA 621. Fluoropolymer finish containing not less
than 70 percent PVDF resin by weight in both color coat and clear topcoat.
Prepare, pretreat, and apply coating to exposed metal surfaces to comply with
coating and resin manufacturers written instructions. Two-coat Fluoropolymer shall
be in addition to the manufacturers prime/adhesive coat.
b.
PVDF finish shall be equal to, or exceed, Kynar 500 or Hylar 500 specifications.
2.
Concealed Finish: Apply pretreatment and manufacturers standard white or light-colored
acrylic or polyester backer finish, consisting of prime coat and wash coat with a minimum
total dry film thickness of 0.5 mil.
2.6
B.
Section 13 34 19
Metal Building Systems
2.
3.
4.
C.
2.7
Materials:
1.
Metallic-Coated Steel Sheet: Restricted-flatness steel sheet, metallic coated by the hotdip process and pre-painted by the coil-coating process to comply with
ASTM A 755/A 755M.
a.
Zinc-Coated (Galvanized) Steel Sheet:
ASTM A 653/A 653M, G90 coating
designation; structural quality.
b.
Aluminum-Zinc Alloy-Coated Steel Sheet: ASTM A 792/A 792M, Class AZ50
coating designation, Grade 40; structural quality.
c.
Surface: Smooth, flat finish.
THERMAL INSULATION
A.
B.
C.
2.8
ACCESSORIES
A.
General: Provide accessories as standard with metal building system manufacturer and as
specified. Fabricate and finish accessories at the factory to greatest extent possible, by
manufacturers standard procedures and processes. Comply with indicated profiles and with
dimensional and structural requirements.
1.
Form exposed sheet metal accessories that are without excessive oil-canning, buckling,
and tool marks and that are true to line and levels indicated, with exposed edges folded
back to form hems.
B.
Roof Panel Accessories: Provide components required for a complete metal roof panel
assembly including copings, fasciae, corner units, ridge closures, clips, sealants, gaskets, fillers,
closure strips, and similar items. Match material and finish of metal roof panels unless
otherwise indicated.
1.
Closures: Provide closures at eaves and ridges, fabricated of same material as metal
roof panels.
2.
Clips: Manufacturers standard, formed from stainless-steel sheet, designed to withstand
negative-load requirements.
3.
Cleats: Manufacturers standard, mechanically seamed cleats formed from stainlesssteel sheet or nylon-coated aluminum sheet.
4.
Backing Plates: Provide metal backing plates at panel end splices, fabricated from
material recommended by manufacturer.
5.
Closure Strips: Closed-cell, expanded, cellular, rubber or cross linked, polyolefin-foam or
closed-cell laminated polyethylene; minimum 1-inch- thick, flexible closure strips; cut or
pre-molded to match metal roof panel profile. Provide closure strips where indicated or
necessary to ensure weather tight construction.
10
Section 13 34 19
Metal Building Systems
6.
Thermal Spacer Blocks: Where metal panels attach directly to purlins, provide thermal
spacer blocks of thickness required to provide 1-inch standoff; fabricated from extruded
polystyrene.
C.
Flashing and Trim: Formed from 0.022-inch nominal-thickness, metallic-coated steel sheet or
aluminum-zinc alloy-coated steel sheet pre-painted with coil coating; finished to match adjacent
metal panels.
1.
Provide flashing and trim as required to seal against weather and to provide finished
appearance. Locations include, but are not limited to, eaves, rakes, corners, bases,
framed openings, ridges, fasciae, and fillers.
2.
Opening Trim: Formed from 0.034-inch nominal-thickness, metallic-coated steel sheet or
aluminum-zinc alloy-coated steel sheet pre-painted with coil coating. Trim head and
jamb of door openings, and head, jamb, and sill of other openings.
D.
Gutters: Formed from 0.022-inch nominal-thickness, metallic-coated steel sheet or aluminumzinc alloy-coated steel sheet pre-painted with coil coating; finished to match roof fascia and rake
trim. Match profile of gable trim, complete with end pieces, outlet tubes, and other special
pieces as required. Fabricate in minimum 96-inch- long sections, sized according to SMACNAs
"Architectural Sheet Metal Manual."
1.
Gutter Supports: Fabricated from same material and finish as gutters.
2.
Strainers: Bronze, copper, or aluminum wire ball type at outlets.
E.
F.
Materials:
1.
Fasteners: Self-tapping screws, bolts, nuts, self-locking rivets and bolts, end-welded
studs, and other suitable fasteners designed to withstand design loads. Provide
fasteners with heads matching color of materials being fastened by means of plastic caps
or factory-applied coating.
a.
Fasteners for Metal Roof Panels: Self-drilling or self-tapping, zinc-plated, hexhead carbon-steel screws, with a stainless-steel cap or zinc-aluminum-alloy head
and EPDM sealing washer.
b.
Fasteners for Metal Roof Panels: Self-drilling, Type 410 stainless-steel or selftapping, Type 304 stainless-steel or zinc-alloy-steel hex washer head, with EPDM
washer under heads of fasteners bearing on weather side of metal panels.
c.
Fasteners for Metal Wall Panels: Self-drilling, Type 410 stainless-steel or selftapping, Type 304 stainless-steel or zinc-alloy-steel hex washer head, with EPDM
sealing washers bearing on weather side of metal panels.
d.
Fasteners for Flashing and Trim: Blind fasteners or self-drilling screws with hex
washer head.
e.
Blind Fasteners: High-strength aluminum or stainless-steel rivets.
2.
Corrosion-Resistant Coating: Cold-applied asphalt mastic, compounded for 15-mil dry
film thickness per coat. Provide inert-type noncorrosive compound free of asbestos
fibers, sulfur components, and other deleterious impurities.
3.
Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic
aggregate grout, noncorrosive, non-staining, mixed with water to consistency suitable for
application and a 30-minute working time.
4.
Metal Panel Sealants:
a.
Sealant Tape: Pressure-sensitive, 100 percent solids, gray polyisobutylenecompound sealant tape with release-paper backing. Provide permanently elastic,
non-sag, nontoxic, non-staining tape of manufacturers standard size.
11
Section 13 34 19
Metal Building Systems
b.
2.9
FABRICATION
A.
General: Design components and field connections required for erection to permit easy
assembly.
1.
Mark each piece and part of the assembly to correspond with previously prepared
erection drawings, diagrams, and instruction manuals.
2.
Fabricate structural framing to produce clean, smooth cuts and bends. Punch holes of
proper size, shape, and location. Members shall be free of cracks, tears, and ruptures.
B.
Tolerances: Comply with MBMAs "Metal Building Systems Manual" for fabrication and erection
tolerances.
C.
Primary Framing: Shop fabricate framing components to indicated size and section, with
baseplates, bearing plates, stiffeners, and other items required for erection welded into place.
Cut, form, punch, drill, and weld framing for bolted field assembly.
1.
Make shop connections by welding or by using high-strength bolts.
2.
Join flanges to webs of built-up members by a continuous, submerged arc-welding
process.
3.
Brace compression flange of primary framing with steel angles or cold-formed structural
tubing between frame web and purlin web or girt web, so flange compressive strength is
within allowable limits for any combination of loadings.
4.
Weld clips to frames for attaching secondary framing.
5.
Shop Priming: Prepare surfaces for shop priming according to SSPC-SP 2. Shop prime
primary framing with specified primer after fabrication.
D.
Secondary Framing: Shop fabricate framing components to indicated size and section by rollforming or break-forming, with baseplates, bearing plates, stiffeners, and other plates required
for erection welded into place. Cut, form, punch, drill, and weld secondary framing for bolted
field connections to primary framing.
1.
Make shop connections by welding or by using non-high-strength bolts.
2.
Shop Priming: Prepare uncoated surfaces for shop priming according to SSPC-SP 2.
Shop prime uncoated secondary framing with specified primer after fabrication.
E.
Metal Panels: Fabricate and finish metal panels at the factory to greatest extent possible, by
manufacturers standard procedures and processes, as necessary to fulfill indicated
performance requirements. Comply with indicated profiles and with dimensional and structural
requirements.
1.
Provide panel profile, including major ribs and intermediate stiffening ribs, if any, for full
length of metal panel.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates, areas, and conditions, with erector present, for compliance with
requirements for installation tolerances and other conditions affecting performance of the Work.
B.
Before erection proceeds, survey elevations and locations of concrete- and masonry-bearing
surfaces and locations of anchor rods, bearing plates, and other embedments to receive
12
Section 13 34 19
Metal Building Systems
structural framing, with erector present, for compliance with requirements and metal building
system manufacturers tolerances.
1.
Engage land surveyor to perform surveying.
C.
3.2
Proceed with erection only after unsatisfactory conditions have been corrected.
PREPARATION
A.
Clean and prepare surfaces to be painted according to manufacturers written instructions for
each particular substrate condition.
B.
Provide temporary shores, guys, braces, and other supports during erection to keep structural
framing secure, plumb, and in alignment against temporary construction loads and loads equal
in intensity to design loads. Remove temporary supports when permanent structural framing,
connections, and bracing are in place unless otherwise indicated.
3.3
Erect metal building system according to manufacturers written erection instructions and
erection drawings.
B.
Do not field cut, drill, or alter structural members without written approval from metal building
system manufacturers professional engineer.
C.
Set structural framing accurately in locations and to elevations indicated, according to AISC
specifications referenced in this Section. Maintain structural stability of frame during erection.
D.
Base and Bearing Plates: Clean concrete- and masonry-bearing surfaces of bond-reducing
materials, and roughen surfaces prior to setting plates. Clean bottom surface of plates.
1.
Set plates for structural members on wedges, shims, or setting nuts as required.
2.
Tighten anchor rods after supported members have been positioned and plumbed. Do
not remove wedges or shims but, if protruding, cut off flush with edge of plate before
packing with grout.
3.
Promptly pack grout solidly between bearing surfaces and plates so no voids remain.
Neatly finish exposed surfaces; protect grout and allow to cure.
Comply with
manufacturers written installation instructions for shrinkage-resistant grouts.
E.
Align and adjust structural framing before permanently fastening. Before assembly, clean
bearing surfaces and other surfaces that will be in permanent contact with framing. Perform
necessary adjustments to compensate for discrepancies in elevations and alignment.
1.
Level and plumb individual members of structure.
2.
Make allowances for difference between temperature at time of erection and mean
temperature when structure will be completed and in service.
F.
Primary Framing and End Walls: Erect framing level, plumb, rigid, secure, and true to line.
Level baseplates to a true even plane with full bearing to supporting structures, set with doublenutted anchor bolts. Use grout to obtain uniform bearing and to maintain a level base-line
elevation. Moist-cure grout for not less than seven days after placement.
1.
Make field connections using high-strength bolts installed according to RCSCs
"Specification for Structural Joints Using ASTM A 325 or A 490 Bolts" for bolt type and
joint type specified.
a.
Joint Type: Snug tightened or pre-tensioned.
G.
Secondary Framing: Erect framing level, plumb, rigid, secure, and true to line. Field bolt
secondary framing to clips attached to primary framing.
13
Section 13 34 19
Metal Building Systems
1.
2.
3.
4.
Provide rake or gable purlins with tight-fitting closure channels and fasciae.
Locate and space wall girts to suit openings such as doors and windows.
Locate canopy framing as indicated.
Provide supplemental framing at entire perimeter of openings, including doors, windows,
louvers, ventilators, and other penetrations of roof and walls.
H.
Bracing: Install bracing in roof and sidewalls where indicated on erection drawings.
1.
Tighten rod and cable bracing to avoid sag.
2.
Locate interior end-bay bracing only where indicated.
I.
Framing for Openings: Provide shapes of proper design and size to reinforce openings and to
carry loads and vibrations imposed, including equipment furnished under mechanical and
electrical work. Securely attach to structural framing.
J.
Erection Tolerances: Maintain erection tolerances of structural framing within AISC 303.
3.4
Examination: Examine primary and secondary framing to verify that structural-panel support
members and anchorages have been installed within alignment tolerances required by
manufacturer.
1.
Examine roughing-in for components and systems penetrating metal panels, to verify
actual locations of penetrations relative to seams before metal panel installation.
B.
General: Anchor metal panels and other components of the Work securely in place, with
provisions for thermal and structural movement.
1.
Field cut metal panels as required for doors, windows, and other openings. Cut openings
as small as possible, neatly to size required, and without damage to adjacent metal panel
finishes.
a.
Field cutting of metal panels by torch is not permitted unless approved in writing by
manufacturer.
2.
Install metal panels perpendicular to structural supports unless otherwise indicated.
3.
Flash and seal metal panels with weather closures at perimeter of openings and similar
elements. Fasten with self-tapping screws.
4.
Locate and space fastenings in uniform vertical and horizontal alignment.
5.
Locate metal panel splices over, but not attached to, structural supports with end laps in
alignment.
6.
Lap metal flashing over metal panels to allow moisture to run over and off the material.
C.
Lap-Seam Metal Panels: Install screw fasteners using power tools with controlled torque
adjusted to compress EPDM washers tightly without damage to washers, screw threads, or
metal panels. Install screws in predrilled holes.
1.
Arrange and nest side-lap joints so prevailing winds blow over, not into, lapped joints.
Lap ribbed or fluted sheets one full rib corrugation. Apply metal panels and associated
items for neat and weather tight enclosure. Avoid "panel creep" or application not true to
line.
D.
Metal Protection: Where dissimilar metals contact each other or corrosive substrates, protect
against galvanic action by painting contact surfaces with corrosion-resistant coating, by applying
rubberized-asphalt underlayment to each contact surface, or by other permanent separation as
recommended by metal roof panel manufacturer.
E.
Joint Sealers: Install gaskets, joint fillers, and sealants where indicated and where required for
weatherproof performance of metal panel assemblies. Provide types of gaskets, fillers, and
14
Section 13 34 19
Metal Building Systems
sealants indicated; or, if not indicated, provide types recommended by metal panel
manufacturer.
1.
Seal metal panel end laps with double beads of tape or sealant the full width of panel.
Seal side joints where recommended by metal panel manufacturer.
2.
Prepare joints and apply sealants to comply with requirements in Division 7 Section "Joint
Sealants."
3.5
General: Provide metal roof panels of full length from eave to ridge unless otherwise indicated
or restricted by shipping limitations.
1.
Install ridge and hip caps as metal roof panel work proceeds.
2.
Flash and seal metal roof panels with weather closures at eaves and rakes. Fasten with
self-tapping screws.
B.
Standing-Seam Metal Roof Panels: Fasten metal roof panels to supports with concealed clips
at each standing-seam joint, at location and spacing and with fasteners recommended by
manufacturer.
1.
Install clips to supports with self-drilling or self-tapping fasteners.
2.
Install pressure plates at locations indicated in manufacturers written installation
instructions.
3.
Snap Joint: Nest standing seams and fasten together by interlocking and completely
engaging factory-applied sealant.
4.
Seamed Joint: Crimp standing seams with manufacturer-approved motorized seamer
tool so that clip, metal roof panel, and factory-applied sealant are completely engaged.
5.
Rigidly fasten eave end of metal roof panels and allow ridge end free movement due to
thermal expansion and contraction. Pre-drill panels for fasteners.
6.
Provide metal closures at peaks each side of ridge and hip caps.
C.
Metal Fascia Panels: Align bottom of metal panels and fasten with blind rivets, bolts, or selfdrilling or self-tapping screws. Flash and seal metal panels with weather closures where
fasciae meet soffits, along lower panel edges, and at perimeter of all openings.
D.
Metal Roof Panel Installation Tolerances: Shim and align metal roof panels within installed
tolerance of 1/4 inch in 20 feet on slope and location lines as indicated and within 1/8-inch offset
of adjoining faces and of alignment of matching profiles.
3.6
General: Install metal wall panels in orientation, sizes, and locations indicated on Drawings.
Install panels perpendicular to girts, extending full height of building, unless otherwise indicated.
Anchor metal wall panels and other components of the Work securely in place, with provisions
for thermal and structural movement.
1.
Unless otherwise indicated, begin metal panel installation at corners with center of rib
lined up with line of framing.
2.
Shim or otherwise plumb substrates receiving metal wall panels.
3.
When two rows of metal panels are required, lap panels 4 inches minimum.
4.
When building height requires two rows of metal panels at gable ends, align lap of gable
panels over metal wall panels at eave height.
5.
Rigidly fasten base end of metal wall panels and allow eave end free movement due to
thermal expansion and contraction. Pre-drill panels.
6.
Flash and seal metal wall panels with weather closures at eaves, rakes, and at perimeter
of all openings. Fasten with self-tapping screws.
7.
Install screw fasteners in predrilled holes.
8.
Install flashing and trim as metal wall panel work proceeds.
15
Section 13 34 19
Metal Building Systems
9.
10.
11.
Apply elastomeric sealant continuously between metal base channel (sill angle) and
concrete, and elsewhere as indicated; or, if not indicated, as necessary for waterproofing.
Align bottom of metal wall panels and fasten with blind rivets, bolts, or self-drilling or selftapping screws.
Provide weatherproof escutcheons for pipe and conduit penetrating exterior walls.
B.
Metal Wall Panels: Install metal wall panels on exterior side of girts. Attach metal wall panels
to supports with fasteners as recommended by manufacturer.
C.
Installation Tolerances: Shim and align metal wall panels within installed tolerance of 1/4 inch
in 20 feet, non-accumulative, on level, plumb, and on location lines as indicated, and within 1/8inch offset of adjoining faces and of alignment of matching profiles.
3.7
General: Install doors and frames plumb, rigid, properly aligned, and securely fastened in place
according to manufacturers written instructions. Coordinate installation with wall flashings and
other components. Seal perimeter of each door frame with elastomeric sealant used for metal
wall panels.
B.
C.
Door Hardware: Mount units at heights indicated in DHIs "Recommended Locations for
Architectural Hardware for Standard Steel Doors and Frames."
1.
Install surface-mounted items after finishes have been completed on substrates involved.
2.
Set units level, plumb, and true to line and location. Adjust and reinforce attachment
substrates as necessary for proper installation and operation.
3.
Drill and countersink units that are not factory prepared for anchorage fasteners. Space
fasteners and anchors according to industry standards.
4.
Set thresholds for exterior doors in full bed of butyl-rubber sealant complying with
requirements specified in Division 7 Section "Joint Sealants."
3.8
ACCESSORY INSTALLATION
A.
General: Install accessories with positive anchorage to building and weather tight mounting,
and provide for thermal expansion.
Coordinate installation with flashings and other
components.
1.
Install components required for a complete metal roof panel assembly, including trim,
copings, ridge closures, seam covers, flashings, sealants, gaskets, fillers, closure strips,
and similar items.
2.
Install components for a complete metal wall panel assembly, including trim, copings,
corners, seam covers, flashings, sealants, gaskets, fillers, closure strips, and similar
items.
3.
Where dissimilar metals contact each other or corrosive substrates, protect against
galvanic action by painting contact surfaces with corrosion-resistant coating, by applying
rubberized-asphalt underlayment to each contact surface, or by other permanent
separation as recommended by manufacturer.
B.
Flashing and Trim: Comply with performance requirements, manufacturers written installation
instructions, and SMACNAs "Architectural Sheet Metal Manual." Provide concealed fasteners
where possible, and set units true to line and level as indicated. Install work with laps, joints,
and seams that will be permanently watertight and weather resistant.
1.
Install exposed flashing and trim that is without excessive oil-canning, buckling, and tool
marks and that is true to line and levels indicated, with exposed edges folded back to
16
Section 13 34 19
Metal Building Systems
2.
form hems. Install sheet metal flashing and trim to fit substrates and to result in
waterproof and weather-resistant performance.
Expansion Provisions: Provide for thermal expansion of exposed flashing and trim.
Space movement joints at a maximum of 10 feet with no joints allowed within 24 inches
of corner or intersection. Where lapped or bayonet-type expansion provisions cannot be
used or would not be sufficiently weather resistant and waterproof, form expansion joints
of intermeshing hooked flanges, not less than 1 inch deep, filled with mastic sealant
(concealed within joints).
C.
D.
Downspouts: Join sections with 1-1/2-inch telescoping joints. Provide fasteners designed to
hold downspouts securely 1 inch away from walls; locate fasteners at top and bottom and at
approximately 60 inches o.c. in between.
1.
Provide elbows at base of downspouts to direct water away from building.
E.
Pipe Flashing: Form flashing around pipe penetration and metal roof panels. Fasten and seal
to panel as recommended by manufacturer.
F.
G.
H.
Product will be considered defective if it does not pass tests and inspections.
I.
3.9
ADJUSTING
A.
Doors: After completing installation, test and adjust doors to operate easily, free of warp, twist,
or distortion.
B.
Door Hardware: Adjust and check each operating item of door hardware and each door to
ensure proper operation and function of every unit. Replace units that cannot be adjusted to
operate as intended.
3.10
17
Section 13 34 19
Metal Building Systems
A.
Repair damaged galvanized coatings on galvanized items with galvanized repair paint
according to ASTM A780 and manufacturers written instructions.
B.
Remove and replace glass that has been broken, chipped, cracked, abraded, or damaged
during construction period.
C.
Touchup Painting: After erection, promptly clean, prepare, and prime or re-prime field
connections, rust spots, and abraded surfaces of prime-painted structural framing, bearing
plates, and accessories.
1.
Clean and prepare surfaces by SSPC-SP 2, "Hand Tool Cleaning," or by SSPC-SP 3,
"Power Tool Cleaning."
2.
Apply a compatible primer of same type as shop primer used on adjacent surfaces.
D.
Touchup Painting: Cleaning and touchup painting are specified in Division 9 painting Sections.
E.
Metal Panels: Remove temporary protective coverings and strippable films, if any, as metal
panels are installed. On completion of metal panel installation, clean finished surfaces as
recommended by metal panel manufacturer. Maintain in a clean condition during construction.
1.
Replace metal panels that have been damaged or have deteriorated beyond successful
repair by finish touchup or similar minor repair procedures.
F.
Doors and Frames: Immediately after installation, sand rusted or damaged areas of prime coat
until smooth and apply touchup of compatible air-drying primer.
1.
Immediately before final inspection, remove protective wrappings from doors and frames.
END OF SECTION
18
Section 13 34 19
Metal Building Systems
DIVISION 23
HVAC
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred
spaces, pipe and duct chases, unheated spaces immediately below roof, spaces above ceilings,
unexcavated spaces, crawlspaces, and tunnels.
B.
Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied
spaces and mechanical equipment rooms.
C.
D.
Concealed, Interior Installations: Concealed from view and protected from physical contact by
building occupants. Examples include above ceilings and chases.
E.
Concealed, Exterior Installations: Concealed from view and protected from weather conditions
and physical contact by building occupants but subject to outdoor ambient temperatures.
Examples include installations within unheated shelters.
F.
G.
1.4
SUBMITTALS
A.
Section 23 05 00
Common Work Results for Mechanical
2.
3.
4.
B.
1.5
Dielectric fittings.
Mechanical sleeve seals.
Escutcheons.
Welding certificates.
QUALITY ASSURANCE
A.
Steel Support Welding: Qualify processes and operators according to AWS D1.1, "Structural
Welding Code--Steel."
B.
1.6
1.7
Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping,
storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and
moisture.
COORDINATION
A.
Arrange for pipe spaces, chases, slots, and openings in building structure during progress of
construction, to allow for mechanical installations.
B.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
In other Part 2 articles where subparagraph titles below introduce lists, the following
requirements apply for product selection:
1.
Manufacturers: Subject to compliance with requirements, provide products by the
manufacturers specified.
PIPE, TUBE, AND FITTINGS
A.
Refer to individual Division 40 piping Sections for pipe, tube, and fitting materials and joining
methods.
B.
Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.
2.3
JOINING MATERIALS
A.
Refer to individual Division 33 piping Sections for special joining materials not listed below.
B.
Pipe-Flange Gasket Materials: Suitable for chemical and thermal conditions of piping system
contents.
1.
ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch maximum thickness unless
thickness or specific material is indicated.
a.
Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze flanges.
Section 23 05 00
Common Work Results for Mechanical
2.
b.
Narrow-Face Type: For raised-face, Class 250, cast-iron and steel flanges.
AWWA C110, rubber, flat face, 1/8 inch thick, unless otherwise indicated; and full-face or
ring type, unless otherwise indicated.
C.
Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless otherwise indicated.
D.
Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux according to
ASTM B 813.
2.4
TRANSITION FITTINGS
A.
B.
Plastic-to-Metal Transition Unions: MSS SP-107, Four-part union. Include brass end, solventcement-joint end, rubber O-ring, and union nut.
2.5
DIELECTRIC FITTINGS
A.
Description: Combination fitting of copper alloy and ferrous materials with threaded, solderjoint, plain, or weld-neck end connections that match piping system materials.
B.
C.
Dielectric Unions: Factory-fabricated, union assembly, for 250-psig minimum working pressure
at 180 deg F.
1.
Manufacturers:
a.
Capitol Manufacturing Co.
b.
Central Plastics Company.
c.
Eclipse, Inc.
d.
Epco Sales, Inc.
e.
Hart Industries, International, Inc.
f.
Watts Industries, Inc.; Water Products Div.
g.
Zurn Industries, Inc.; Wilkins Div.
D.
E.
Dielectric-Flange Kits: Companion-flange assembly for field assembly. Include flanges, fullface- or ring-type neoprene or phenolic gasket, phenolic or polyethylene bolt sleeves, phenolic
washers, and steel backing washers.
1.
Manufacturers:
a.
Advance Products & Systems, Inc.
b.
Calpico, Inc.
c.
Central Plastics Company.
d.
Pipeline Seal and Insulator, Inc.
2.
Separate companion flanges and steel bolts and nuts shall have 150- or 300-psig
minimum working pressure where required to suit system pressures.
Section 23 05 00
Common Work Results for Mechanical
F.
Dielectric Couplings: Galvanized-steel coupling with inert and noncorrosive, thermoplastic lining;
threaded ends; and 300-psig minimum working pressure at 225 deg F.
1.
Manufacturers:
a.
Calpico, Inc.
b.
Lochinvar Corp.
G.
Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic lining;
plain, threaded, or grooved ends; and 300-psig minimum working pressure at 225 deg F.
1.
Manufacturers:
a.
Perfection Corp.
b.
Precision Plumbing Products, Inc.
c.
Sioux Chief Manufacturing Co., Inc.
d.
Victaulic Co. of America.
2.6
2.7
Description: Modular sealing element unit, designed for field assembly, to fill annular space
between pipe and sleeve.
1.
Manufacturers:
a.
PSI Thunderline / Link-Seal
2.
Sealing Elements: EPDM or NBR interlocking links shaped to fit surface of pipe. Provide
silicone (ASTM D 2000 MI GE505) for fire seal applications. Include type and number
required for pipe material and size of pipe.
3.
Pressure Plates: Reinforced nylon polymer. Include two for each sealing element.
4.
Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates
to sealing elements. Include one for each sealing element.
SLEEVES
A.
Galvanized-Steel Sheet:
longitudinal joint.
B.
Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends.
C.
Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile-iron pressure pipe, with plain ends
and integral waterstop, unless otherwise indicated.
D.
Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange. Include
clamping ring and bolts and nuts for membrane flashing.
1.
Underdeck Clamp: Clamping ring with set screws.
2.8
ESCUTCHEONS
A.
Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to closely
fit around pipe, tube, and insulation of insulated piping and an OD that completely covers
opening.
B.
C.
D.
Section 23 05 00
Common Work Results for Mechanical
E.
F.
Split-Casting, Floor-Plate Type: Cast brass with concealed hinge and set screw.
2.9
GROUT
A.
Description: ASTM C 1107, Grade B, nonshrink and nonmetallic, dry hydraulic-cement grout.
1.
Characteristics:
Post-hardening, volume-adjusting, nonstaining, noncorrosive,
nongaseous, and recommended for interior and exterior applications.
2.
Design Mix: 5000-psi, 28-day compressive strength.
3.
Packaging: Premixed and factory packaged.
PART 3 - EXECUTION
3.1
Install piping according to the following requirements and Division 33 Sections specifying piping
systems.
B.
Drawing plans, schematics, and diagrams indicate general location and arrangement of piping
systems. Indicated locations and arrangements were used to size pipe and calculate friction
loss, expansion, pump sizing, and other design considerations. Install piping as indicated
unless deviations to layout are approved on Coordination Drawings.
C.
Install piping in concealed locations, unless otherwise indicated and except in equipment rooms
and service areas.
D.
Install piping indicated to be exposed and piping in equipment rooms and service areas at right
angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated
otherwise.
E.
Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
F.
G.
H.
I.
J.
K.
Select system components with pressure rating equal to or greater than system operating
pressure.
L.
Install escutcheons for penetrations of walls, ceilings, and floors according to the following:
1.
New Piping:
a.
Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type.
b.
Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-plated
finish.
c.
Insulated Piping: One-piece, stamped-steel type with spring clips.
d.
Bare Piping at Wall and Floor Penetrations: One-piece, cast-brass type with
polished chrome-plated finish.
e.
Bare Piping at Wall and Floor Penetrations: One-piece, stamped-steel type.
Section 23 05 00
Common Work Results for Mechanical
f.
g.
h.
M.
Install sleeves for pipes passing through concrete and masonry walls and concrete floor and
roof slabs.
1.
Cut sleeves to length for mounting flush with both surfaces.
a.
Exception: Extend sleeves installed in floors of mechanical equipment areas or
other wet areas 2 inches above finished floor level. Extend cast-iron sleeve fittings
below floor slab as required to secure clamping ring if ring is specified.
2.
Install sleeves in new walls and slabs as new walls and slabs are constructed.
3.
Install sleeves that are large enough to provide 1/4-inch annular clear space between
sleeve and pipe or pipe insulation. Use the following sleeve materials:
a.
Steel Pipe Sleeves: For pipes smaller than NPS 6.
b.
Steel Sheet Sleeves: For pipes NPS 6 and larger, penetrating gypsum-board
partitions.
c.
Stack Sleeve Fittings: For pipes penetrating floors with membrane waterproofing.
Secure flashing between clamping flanges. Install section of cast-iron soil pipe to
extend sleeve to 2 inches above finished floor level. Refer to Division 7 Section
"Sheet Metal Flashing and Trim" for flashing.
1). Seal space outside of sleeve fittings with grout.
4.
Except for underground wall penetrations, seal annular space between sleeve and pipe
or pipe insulation, using joint sealants appropriate for size, depth, and location of joint.
Refer to Division 7 Section "Joint Sealers" for materials and installation.
N.
O.
Underground, Exterior-Wall Pipe Penetrations: Install cast-iron "wall pipes" for sleeves. Seal
pipe penetrations using mechanical sleeve seals. Select sleeve size to allow for 1-inch annular
clear space between pipe and sleeve for installing mechanical sleeve seals.
1.
Mechanical Sleeve Seal Installation: Select type and number of sealing elements
required for pipe material and size. Position pipe in center of sleeve. Assemble
mechanical sleeve seals and install in annular space between pipe and sleeve. Tighten
bolts against pressure plates that cause sealing elements to expand and make watertight
seal.
P.
Q.
3.2
Join pipe and fittings according to the following requirements and Division 33 Sections
specifying piping systems.
B.
Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
Section 23 05 00
Common Work Results for Mechanical
C.
Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
D.
Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube
end. Construct joints according to ASTM B 828 or CDAs "Copper Tube Handbook," using leadfree solder alloy complying with ASTM B 32.
E.
Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut
threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore
full ID. Join pipe fittings and valves as follows:
1.
Apply appropriate tape or thread compound to external pipe threads unless dry seal
threading is specified.
2.
Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or
damaged. Do not use pipe sections that have cracked or open welds.
F.
Flanged Joints: Select appropriate gasket material, size, type, and thickness for service
application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads.
3.3
PIPING CONNECTIONS
A.
3.4
A.
Install equipment to allow maximum possible headroom unless specific mounting heights are
not indicated.
B.
Install equipment level and plumb, parallel and perpendicular to other building systems and
components in exposed interior spaces, unless otherwise indicated.
C.
D.
Install equipment to allow right of way for piping installed at required slope.
3.5
CONCRETE BASES
A.
Section 23 05 00
Common Work Results for Mechanical
4.
5.
6.
7.
3.6
Place and secure anchorage devices. Use supported equipment manufacturers setting
drawings, templates, diagrams, instructions, and directions furnished with items to be
embedded.
Install anchor bolts to elevations required for proper attachment to supported equipment.
Install anchor bolts according to anchor-bolt manufacturers written instructions.
Use 3000-psi 28-day compressive-strength concrete and reinforcement as specified in
Division 3.
GROUTING
A.
Mix and install grout for mechanical equipment base bearing surfaces, pump and other
equipment base plates, and anchors.
B.
C.
D.
E.
F.
Place grout on concrete bases and provide smooth bearing surface for equipment.
G.
H.
END OF SECTION
Section 23 05 00
Common Work Results for Mechanical
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Sleeves.
SUBMITTALS
A.
PART 2 - PRODUCTS
2.1
SLEEVES
A.
Galvanized-Steel-Pipe Sleeves:
coated, with plain ends.
B.
PART 3 - EXECUTION
3.1
SLEEVE INSTALLATION
A.
Install sleeves for piping passing through penetrations in floors, partitions, roofs, and walls.
B.
Install sleeves in concrete floors, concrete roof slabs, and concrete walls as new slabs and
walls are constructed.
1.
Permanent sleeves are not required for holes in slabs formed by molded-PE or -PP
sleeves.
2.
Cut sleeves to length for mounting flush with both surfaces.
a.
Exception: Extend sleeves installed in floors of mechanical equipment areas or
other wet areas 2 inches (50 mm) above finished floor level.
C.
D.
Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at
pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements for
firestopping specified in Division 07 Section "Penetration Firestopping."
Section 23 05 17
Sleeves and Sleeve Seals for HVAC Piping
3.2
Use sleeves and sleeve seals for the following piping-penetration applications:
1.
Exterior Walls above Grade:
a.
Piping smaller than NPS 6 (DN 150): Galvanized-steel-pipe sleeves.
2.
Interior Partitions:
a.
Piping smaller than NPS 6 (DN 150): PVC-pipe sleeves.
END OF SECTION
Section 23 05 17
Sleeves and Sleeve Seals for HVAC Piping
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
This Section includes the following hangers and supports for Mechanical system piping and
equipment:
1.
Steel pipe hangers and supports.
2.
Trapeze pipe hangers.
DEFINITIONS
A.
MSS: Manufacturers Standardization Society for The Valve and Fittings Industry Inc.
B.
Terminology: As defined in MSS SP-90, "Guidelines on Terminology for Pipe Hangers and
Supports."
1.4
SUBMITTALS
A.
1.5
A.
Welding: Qualify procedures and personnel according to AWS D1.1, "Structural Welding Code-Steel."
PART 2 - PRODUCTS
2.1
Description: MSS SP-58, Types 1 through 58, factory-fabricated components. Refer to Part 3
"Hanger and Support Applications" Article for where to use specific hanger and support types.
B.
A.
2.2
2.3
MISCELLANEOUS MATERIALS
A.
Structural Steel: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.
B.
Grout: ASTM C 1107, factory-mixed and packaged, dry, hydraulic-cement, non-shrink and
nonmetallic grout; suitable for interior and exterior applications.
1.
Properties: Non-staining, noncorrosive, and nongaseous.
2.
Design Mix: 5000-psi, 28-day compressive strength.
1
Section 23 05 29
Hangers and Supports for Mechanical Piping and Equipment
PART 3 - EXECUTION
3.1
Specific hanger and support requirements are specified in Sections specifying piping systems
and equipment.
B.
Comply with MSS SP-69 for pipe hanger selections and applications that are not specified in
piping system Sections.
C.
Use hangers and supports with galvanized, metallic coatings for piping and equipment that will
not have field-applied finish.
D.
Use nonmetallic coatings on attachments for electrolytic protection where attachments are in
direct contact with copper tubing.
E.
F.
Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in
piping system Sections, install the following types:
1.
Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of non-insulated or
insulated stationary pipes, NPS 1/2 to NPS 30.
2.
Adjustable, Pipe Saddle Supports (MSS Type 38): For stanchion-type support for pipes,
NPS 2-1/2 to NPS 36, if vertical adjustment is required, with steel pipe base stanchion
support and cast-iron floor flange.
G.
Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system
Sections, install the following types:
1.
Carbon or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers, NPS 3/4
to NPS 20, if longer ends are required for riser clamps.
H.
Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system
Sections, install the following types:
1.
Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads.
I.
Building Attachments: Unless otherwise indicated and except as specified in piping system
Sections, install the following types:
1.
Top-Beam C-Clamps (MSS Type 19): For use under roof installations with bar-joist
construction to attach to top flange of structural shape.
2.
Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams,
channels, or angles.
3.
Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams.
4.
C-Clamps (MSS Type 23): For structural shapes.
J.
Saddles and Shields: Unless otherwise indicated and except as specified in piping system
Sections, install the following types:
1.
Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to
prevent crushing insulation.
K.
Comply with MSS SP-69 for trapeze pipe hanger selections and applications that are not
specified in piping system Sections.
L.
Comply with MFMA-102 for metal framing system selections and applications that are not
specified in piping system Sections.
2
Section 23 05 29
Hangers and Supports for Mechanical Piping and Equipment
M.
3.2
A.
Steel Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install hangers,
supports, clamps, and attachments as required to properly support piping from building
structure.
B.
Trapeze Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Arrange for
grouping of parallel runs of horizontal piping and support together on field-fabricated trapeze
pipe hangers.
1.
Pipes of Various Sizes: Support together and space trapezes for smallest pipe size or
install intermediate supports for smaller diameter pipes as specified above for individual
pipe hangers.
2.
Field fabricate from ASTM A 36/A 36M, steel shapes selected for loads being supported.
Weld steel according to AWS D1.1.
C.
Metal Framing System Installation: Arrange for grouping of parallel runs of piping and support
together on field-assembled metal framing systems.
D.
E.
F.
Install hangers and supports to allow controlled thermal and seismic movement of piping
systems, to permit freedom of movement between pipe anchors, and to facilitate action of
expansion joints, expansion loops, expansion bends, and similar units.
G.
Install lateral bracing with pipe hangers and supports to prevent swaying.
H.
Load Distribution: Install hangers and supports so piping live and dead loads and stresses from
movement will not be transmitted to connected equipment.
I.
Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so maximum
pipe deflections allowed by ASME B31.1 (for power piping) and ASME B31.9 (for building
services piping) are not exceeded.
J.
3
Section 23 05 29
Hangers and Supports for Mechanical Piping and Equipment
5.
3.3
ADJUSTING
A.
Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve
indicated slope of pipe.
B.
Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches.
3.4
PAINTING
A.
Touch Up: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately
after erecting hangers and supports. Use same materials as used for shop painting. Comply
with SSPC-PA 1 requirements for touching up field-painted surfaces.
1.
Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils.
B.
Touch Up: Cleaning and touchup painting of field welds, bolted connections, and abraded
areas of shop paint on miscellaneous metal are specified in Division 09 painting Sections.
C.
Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
END OF SECTION
4
Section 23 05 29
Hangers and Supports for Mechanical Piping and Equipment
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Equipment labels.
2.
Warning signs and labels.
3.
Pipe labels.
4.
Warning tags.
COORDINATION
A.
B.
Coordinate installation of identifying devices with locations of access panels and doors.
C.
PART 2 - PRODUCTS
2.1
EQUIPMENT LABELS
A.
B.
Section 23 05 53
Identification for HVAC Piping & Equipment
7.
8.
C.
2.2
A.
Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16
inch thick, and having predrilled holes for attachment hardware.
B.
C.
D.
E.
Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2
by 3/4 inch.
F.
Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2
inch for viewing distances up to 72 inches, and proportionately larger lettering for greater
viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal
lettering.
G.
H.
Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
I.
Label Content:
instructions.
2.3
PIPE LABELS
A.
General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering
indicating service, and showing flow direction.
B.
Pre-tensioned Pipe Labels: Pre-coiled, semi-rigid plastic formed to cover full circumference of
pipe and to attach to pipe without fasteners or adhesive.
C.
D.
Pipe Label Contents: Include identification of piping service using same designations or
abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.
1.
Flow-Direction Arrows: Integral with piping system service lettering to accommodate both
directions, or as separate unit on each pipe label to indicate flow direction.
2.
Lettering Size: At least 1-1/2 inches high.
2.4
WARNING TAGS
A.
Section 23 05 53
Identification for HVAC Piping & Equipment
3.
4.
PART 3 - EXECUTION
3.1
PREPARATION
A.
3.2
Clean piping and equipment surfaces of substances that could impair bond of identification
devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and
encapsulants.
EQUIPMENT LABEL INSTALLATION
A.
B.
3.3
Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces;
machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and
exterior exposed locations as follows:
1.
Near each valve and control device.
2.
Near each branch connection, excluding short takeoffs for fixtures and terminal units.
Where flow pattern is not obvious, mark each pipe at branch.
3.
Near penetrations through walls, floors, ceilings, and inaccessible enclosures.
4.
At access doors, manholes, and similar access points that permit view of concealed
piping.
5.
Near major equipment items and other points of origination and termination.
6.
Spaced at maximum intervals of 50 feet along each run. Reduce intervals to 25 feet in
areas of congested piping and equipment.
7.
On piping above removable acoustical ceilings. Omit intermediately spaced labels.
B.
3.4
WARNING-TAG INSTALLATION
A.
Write required message on, and attach warning tags to, equipment and other items where
required.
END OF SECTION
Section 23 05 53
Identification for HVAC Piping & Equipment
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Balancing Air Systems:
a.
Ducted heating/cooling HVAC systems.
b.
Exhaust fans.
DEFINITIONS
A.
B.
C.
D.
E.
1.4
SUBMITTALS
A.
1.5
A.
TAB Contractor Qualifications: Engage a TAB entity certified by AABC NEBB or TABB.
B.
TAB Report Forms: Use standard TAB contractor's forms approved by Owner.
C.
1.6
COORDINATION
A.
Perform TAB after leakage and pressure tests on air distribution systems have been
satisfactorily completed.
EXAMINATION
A.
Examine the Contract Documents to become familiar with Project requirements and to discover
conditions in systems' designs that may preclude proper TAB of systems and equipment.
Section 23 05 93
Testing, Adjusting and Balancing
B.
Examine systems for installed balancing devices, such as test ports, gage cocks, thermometer
wells, flow-control devices, balancing valves and fittings, and manual volume dampers. Verify
that locations of these balancing devices are accessible.
C.
D.
Examine design data including HVAC system descriptions, statements of design assumptions
for environmental conditions and systems' output, and statements of philosophies and
assumptions about HVAC system and equipment controls.
E.
F.
Examine system and equipment installations and verify that field quality-control testing,
cleaning, and adjusting specified in individual Sections have been performed.
G.
H.
Examine HVAC equipment and filters and verify that bearings are greased, belts are aligned
and tight, and equipment with functioning controls is ready for operation.
I.
Examine heat-transfer coils for correct piping connections and for clean and straight fins.
J.
K.
Report deficiencies discovered before and during performance of TAB procedures. Observe
and record system reactions to changes in conditions. Record default set points if different from
indicated values.
3.2
PREPARATION
A.
B.
Section 23 05 93
Testing, Adjusting and Balancing
3.3
Perform testing and balancing procedures on each system according to the procedures
contained in NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of
Environmental Systems" and in this Section.
B.
Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the
minimum extent necessary for TAB procedures.
1.
After testing and balancing, patch probe holes in ducts with same material and thickness
as used to construct ducts.
2.
Install and join new insulation that matches removed materials. Restore insulation,
coverings, vapor barrier, and finish according to Division 23 Section "HVAC Insulation."
C.
Mark equipment and balancing devices, including damper-control positions, valve position
indicators, fan-speed-control levers, and similar controls and devices, with paint or other
suitable, permanent identification material to show final settings.
D.
Take and report testing and balancing measurements in inch-pound (IP) units.
3.4
Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and
recommended testing procedures. Crosscheck the summation of required outlet volumes with
required fan volumes.
B.
Determine the best locations in main and branch ducts for accurate duct-airflow measurements.
C.
Check airflow patterns from the outdoor-air louvers and dampers and the return- and exhaustair dampers through the supply-fan discharge and mixing dampers.
D.
Locate start-stop and disconnect switches, electrical interlocks, and motor starters.
E.
Verify that motor starters are equipped with properly sized thermal protection.
F.
G.
H.
I.
J.
Verify that air duct system is sealed as specified in Division 23 Section 23 31 13 "Metal Ducts."
3.5
Adjust fans to deliver total indicated airflows within the maximum allowable fan speed listed by
fan manufacturer.
1.
Measure total airflow.
a.
Where sufficient space in ducts is unavailable for Pilot-tube traverse
measurements, measure airflow at terminal outlets and inlets and calculate the
total airflow.
2.
Measure fan static pressures as follows to determine actual static pressure:
a.
Measure outlet static pressure as far downstream from the fan as practical and
upstream from restrictions in ducts such as elbows and transitions.
Section 23 05 93
Testing, Adjusting and Balancing
b.
c.
3.
4.
5.
6.
7.
Measure static pressure directly at the fan outlet or through the flexible connection.
Measure inlet static pressure of single-inlet fans in the inlet duct as near the fan as
possible, upstream from the flexible connection, and downstream from duct
restrictions.
d.
Measure inlet static pressure of double-inlet fans through the wall of the plenum
that houses the fan.
e.
For non-ducted fans, install temporary duct at fan inlet.
Measure static pressure across each component that makes up an air-handling unit,
rooftop unit, and other air-handling and treating equipment.
a.
Report the cleanliness status of filters and the time static pressures are measured.
Measure static pressures entering and leaving other devices, such as sound traps, heatrecovery equipment, and air washers, under final balanced conditions.
Review Record Documents to determine variations in design static pressures versus
actual static pressures. Calculate actual system-effect factors. Recommend adjustments
to accommodate actual conditions.
Obtain approval from Engineer for adjustment of fan speed higher or lower than indicated
speed. Comply with requirements in Division 23 Sections for air-handling units for
adjustment of fans, belts, and pulley sizes to achieve indicated air-handling-unit
performance.
Do not make fan speed adjustments that result in motor overload. Consult equipment
manufacturers about fan speed safety factors. Modulate dampers and measure fan motor
amperage to ensure that no overload will occur. Measure amperage in full cooling, full
heating, economizer and any other operating mode to determine the maximum required
brake horsepower.
B.
Adjust volume dampers for main duct, submain ducts, and major branch ducts to indicated
airflows within specified tolerances.
1.
Measure airflow of submain and branch ducts.
a.
Where sufficient space in submain and branch ducts is unavailable for Pitot-tube
traverse measurements, measure airflow at terminal outlets and inlets and
calculate the total airflow for that zone.
2.
Measure static pressure at a point downstream from the balancing damper, and adjust
volume dampers until the proper static pressure is achieved.
3.
Re-measure each submain and branch duct after all have been adjusted. Continue to
adjust submain and branch ducts to indicated airflows within specified tolerances.
C.
D.
Adjust air outlets and inlets for each space to indicated airflows within specified tolerances of
indicated values. Make adjustments using branch volume dampers rather than extractors and
the dampers at air terminals.
1.
Adjust each outlet in same room or space to within specified tolerances of indicated
quantities without generating noise levels above the limitations prescribed by the
Contract Documents.
2.
Adjust patterns of adjustable outlets for proper distribution without drafts.
3.6
Motors, 1/2 HP and Larger: Test at final balanced conditions and record the following data:
1.
Manufacturer's name, model number, and serial number.
2.
Motor horsepower rating.
3.
Motor rpm.
4.
Efficiency rating.
5.
Nameplate and measured voltage, each phase.
Section 23 05 93
Testing, Adjusting and Balancing
6.
7.
3.7
B.
C.
3.8
TOLERANCES
A.
3.9
Set HVAC system's air flow rates within the following tolerances:
1.
Supply, Return, and Exhaust Fans and Equipment with Fans: Plus or minus 10 percent.
2.
Air Outlets and Inlets: Plus or minus 10 percent.
FINAL REPORT
A.
General: Prepare a certified written report; tabulate and divide the report into separate sections
for tested systems and balanced systems.
1.
Include a certification sheet at the front of the report's binder, signed and sealed by the
certified testing and balancing engineer.
2.
Include a list of instruments used for procedures, along with proof of calibration.
B.
Final Report Contents: In addition to certified field-report data, include the following:
1.
Fan curves.
2.
Manufacturers' test data.
3.
Field test reports prepared by system and equipment installers.
4.
Other information relative to equipment performance; do not include Shop Drawings and
product data.
C.
General Report Data: In addition to form titles and entries, include the following data:
1.
Title page.
2.
Name and address of the TAB contractor.
3.
Project name.
4.
Project location.
5.
Engineer's name and address.
6.
Contractor's name and address.
7.
Report date.
8.
Signature of TAB supervisor who certifies the report.
9.
Table of Contents with the total number of pages defined for each section of the report.
Number each page in the report.
10.
Summary of contents including the following:
a.
Indicated versus final performance.
b.
Notable characteristics of systems.
c.
Description of system operation sequence if it varies from the Contract
Documents.
11.
Nomenclature sheets for each item of equipment.
12.
Data for terminal units, including manufacturer's name, type, size, and fittings.
13.
Notes to explain why certain final data in the body of reports vary from indicated values.
14.
Test conditions for fans performance forms including the following:
a.
Settings for outdoor, return, and exhaust-air dampers.
b.
Conditions of filters.
c.
Cooling coil, wet and dry bulb conditions.
Section 23 05 93
Testing, Adjusting and Balancing
d.
e.
f.
g.
h.
D.
Air-Handling-Unit Test Reports: For air-handling units with coils, include the following:
1.
Unit Data:
a.
Unit identification.
b.
Location.
c.
Make and type.
d.
Model number and unit size.
e.
Manufacturer's serial number.
f.
Unit arrangement and class.
g.
Discharge arrangement.
h.
Sheave make, size in inches, and bore.
i.
Center-to-center dimensions of sheave, and amount of adjustments in inches.
j.
Number, make, and size of belts.
k.
Number, type, and size of filters.
2.
Motor Data:
a.
Motor make, and frame type and size.
b.
Horsepower and rpm.
c.
Volts, phase, and hertz.
d.
Full-load amperage and service factor.
e.
Sheave make, size in inches, and bore.
f.
Center-to-center dimensions of sheave, and amount of adjustments in inches.
3.
Test Data (Indicated and Actual Values):
a.
Total air flow rate in cfm.
b.
Total system static pressure in inches wg.
c.
Fan rpm.
d.
Discharge static pressure in inches wg.
e.
Filter static-pressure differential in inches wg.
f.
Preheat-coil static-pressure differential in inches wg.
g.
Cooling-coil static-pressure differential in inches wg.
h.
Heating-coil static-pressure differential in inches wg.
i.
Outdoor airflow in cfm.
j.
Return airflow in cfm.
k.
Outdoor-air damper position.
l.
Return-air damper position.
m.
Vortex damper position.
E.
Fan Test Reports: For supply, return, and exhaust fans, include the following:
1.
Fan Data:
a.
System identification.
b.
Location.
c.
Make and type.
d.
Model number and size.
e.
Manufacturer's serial number.
f.
Arrangement and class.
g.
Sheave make, size in inches, and bore.
h.
Center-to-center dimensions of sheave, and amount of adjustments in inches.
2.
Motor Data:
a.
Motor make, and frame type and size.
b.
Horsepower and rpm.
c.
Volts, phase, and hertz.
d.
Full-load amperage and service factor.
Section 23 05 93
Testing, Adjusting and Balancing
3.
F.
3.10
e.
Sheave make, size in inches, and bore.
f.
Center-to-center dimensions of sheave, and amount of adjustments in inches.
g.
Number, make, and size of belts.
Test Data (Indicated and Actual Values):
a.
Total airflow rate in cfm.
b.
Total system static pressure in inches wg.
c.
Fan rpm.
d.
Discharge static pressure in inches wg.
e.
Suction static pressure in inches wg.
A.
Initial Inspection:
1.
After testing and balancing are complete, operate each system and randomly check
measurements to verify that the system is operating according to the final test and
balance readings documented in the final report.
2.
Check the following for each system:
a.
Measure airflow of at least 10 percent of air outlets.
b.
Measure room temperature at each thermostat/temperature sensor. Compare the
reading to the set point.
c.
Verify that balancing devices are marked with final balance position.
d.
Note deviations from the Contract Documents in the final report.
B.
TAB Work will be considered defective if it does not pass inspections. If TAB Work fails,
proceed as follows:
1.
Recheck all measurements and make adjustments. Revise the final report and balancing
device settings to include all changes; resubmit the final report and request a second final
inspection.
2.
If the second final inspection also fails, Owner may contract the services of another TAB
contractor to complete TAB Work according to the Contract Documents and deduct the
cost of the services from the original TAB contractor's final payment.
C.
END OF SECTION
Section 23 05 93
Testing, Adjusting and Balancing
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section consists of furnishing all labor, equipment, materials and accessories, and performing
all operations required, for the correct fabrication and installation of thermal or acoustic
insulation applied to the following systems, piping, equipment, and ductwork.
DEFINITIONS
A.
Exposed piping and ductwork is that which can be seen when the building is complete without
opening or removing access door panels, or ceilings tiles. This also includes all mechanical
equipment rooms and pipe tunnels.
B.
Concealed piping and ductwork are those elements above ceilings, in chases, interstitial space
and pipe spaces. Other piping and ductwork is considered to be exposed.
C.
Exterior piping and ductwork is that which is exposed to the weather and/or outside the building
envelope. Piping and ductwork protected by overhangs, areaways, etc., exterior to the building
envelope are considered exterior.
D.
E.
Air conditioned space: Space directly supplied with heated or cooled air.
F.
G.
H.
I.
Hot: Ductwork handling air at design temperature above 60 degrees F; equipment or piping
handling media above 105 degrees F.
J.
K.
Run-out: Branch pipe connection up to one inch nominal size to a one terminal piece of
equipment (fan coil, terminal box).
L.
Section 23 07 00
Ductwrap Insulation
1.4
QUALITY ASSURANCE
A.
Products of the manufacturers, herein, will be acceptable for use for the specific functions
noted. All materials shall be compatible with the materials to which they are applied, and shall
not corrode, soften or otherwise attack such materials in either the wet or dry state.
B.
Materials shall be applied subject to their temperature limits. Any methods of application of
insulation materials or finishes not specified in detail herein shall be in accordance with the
particular manufacturers published recommendations.
C.
Insulation shall be applied by experienced workers regularly employed for this type work.
1.5
RATING
A.
All insulation shall have composite surface burning characteristic rating as tested by
ASTM E 84, UL 723, or NFPA 255 not exceeding:
Flame Spread
Smoke Developed
B.
1.6
25
50
Composite shall include insulation, jacketing and adhesive used to secure jacketing or facing.
All accessory items such as PVC jacketing and fittings, adhesive, mastic, cement, tape and
cloth shall have the same component rating as specified above.
STANDARDS
A.
B.
Midwest Insulation Contractors Association Commercial and Industrial Insulation Standards Third Edition.
1.7
SUBMITTALS
A.
B.
C.
Submittals shall use pages from Midwest Insulation Contractors Association Commercial and
Industrial Insulation Standards for defining how insulation materials will be applied.
PART 2 - PRODUCTS
2.1
Ductwork (Insulation):
1.
Insulation shall be 250 deg. F rated as manufactured by Owens Corning, Manville, Knauf,
or Certainteed.
Section 23 07 00
Ductwrap Insulation
2.
3.
4.
2.2
Duct Wrap: 2 in. thick, 1.0 PCF with aluminum or FRK facing, having a maximum vapor
transmission of .02 perms. Minimum installed "R" value shall be 5.6 with 25%
compression.
Insulation Board: 2 in. thick 3 PCF with FRK facing. Minimum installed "R" value 6.
Commercial Duct-wrap: 2-1/2 in. thick 3 PCF semi-rigid, flexible board type with FRK
facing. Minimum installed "R" value 6.0.
FINISHES
A.
Metal jacketing, smooth .016 in. thick, type T 3003 aluminum with laminated moisture barrier.
Jacketing shall be Childers, aluminum roll jacketing with Polykraft moisture barrier. Jacketing
shall be embossed "No Asbestos" on a 6 inch spacing.
B.
C.
Foil scrim kraft (FSK) jacket, flame retardant vapor barrier. Jacket shall be Alpha Temp 10651,
all service jackets.
2.3
MISCELLANEOUS
A.
Adhesives:
1.
Glass & Mineral Fiber - Foster 85-20 / Vimasco 795.
2.
Polyurethane - Foster 81-33.
3.
Cellular Glass - Pittcote 300 / Childers CP-30.
4.
Polystyrene - Foster 97-13 / Childers CP-96.
B.
C.
Coatings:
1.
Foster - Monolar Coating / Vimasco
2.
Foster Sealfas 30-36 / Vimasco
3.
Foster Tite-Fit 30-56 / Vimasco
4.
Pittcote 300
D.
E.
F.
Insulpins:
G.
H.
I.
J.
K.
L.
Bands - .020 in., aluminum, 2 in. wide, embossed continuously with the legend "No Asbestos".
Section 23 07 00
Ductwrap Insulation
M.
PART 3 - EXECUTION
3.1
GENERAL
A.
Insulation shall be applied to clean and dry surfaces after tests and approvals required by this
specification have been completed.
B.
On cold surfaces where a vapor barrier must be maintained, insulation shall be applied with a
continuous, unbroken moisture and vapor seal. All hangers, supports, anchors, or other
projections that are secured to cold surfaces shall be insulated and vapor sealed to prevent
condensation.
C.
All surface finishes shall be extended in such a manner as to protect all raw edges, ends and
surfaces of insulation.
D.
All duct insulation shall be continuous through walls, ceiling or floor openings, or sleeves;
except where fire stop or fire safeing materials are required.
E.
Metal shields shall be installed between hangers or supports and the piping insulation. Rigid
insulation inserts shall be installed as required between the pipe and the insulation shields.
Inserts shall be of equal thickness to the adjacent insulation and shall be vapor sealed as
required.
F.
G.
All clevis type pipe supports shall be sized to fit the outside diameter of the insulation.
H.
Insulate valves, fittings, flanges etc. with the same thickness of insulation as specified for piping.
I.
J.
Insulate items mounted in ductwork with the same thickness of insulation as specified for
ductwork: including air measuring stations, smoke dampers, and automatic dampers.
K.
Repair insulation damaged by work under this contract to match existing work or replace
damaged portion with insulation specified for new work.
L.
Standing seams and other projections in ductwork or casings shall have insulation applied so
that at least 2" of insulation will cover such projections.
M.
N.
Where unlined duct and lined duct connect, the insulation shall overlap lined section at least 6".
O.
Piping and ductwork covered with metal or P.V.C. jacketing systems shall have the joints made
to shed water. Laps shall be positioned in the bottom quadrant on horizontal pipe and
ductwork.
3.2
HVAC SYSTEMS
A.
Concealed Ductwork:
Section 23 07 00
Ductwrap Insulation
1.
2.
3.
4.
Apply jacketed duct wrap to all concealed ductwork providing conditioned air, or outside
air. Insulate return ductwork in non-conditioned spaces and in ceiling spaces below a
roof.
Pull insulation snug, but do not compress insulation more than 1/4 inch.
Secure duct wrap insulation to ductwork using adhesive. Secure insulation on bottom on
sides of horizontal ductwork and all sides of vertical ductwork with insulpins welded to
duct on 12 to 18 inch centers and with clips slipped over the pins. Apply clips without
compressing insulation. Make joints by lapping the facing a minimum of 2 inch and
stapling with T-5 flared staples. Vapor - seal with Childers CP-30 Low Odor at all staples,
clip locations and other penetrations. Seal joints with 3 inch wide FSK tape.
Insulation Thickness:
a.
Inside Thermal Envelope:
Supply ductwork - 2 in. thick
Outside air ductwork - 2 in. thick
Return air ductwork - 2 in. thick
b.
Outside Thermal Envelope (Attic/Crawlspace):
Supply ductwork - 4 in. thick - 2 layers
Return air ductwork - 4 in. thick - 2 layers
Exhaust ductwork - 2 in. thick - 1 layer
Outside air - 2 in. thick - 1 layer
B.
C.
D.
Finishes:
1.
Metal Jacketing (Galvanized):
a.
Insulated ductwork installed outdoors, insulated ductwork within 8 ft. of the finished
floor in a mechanical room shall be covered with 30 gauge galvanized steel if
ductwork is to be painted. Covering shall be hemmed, and flanged. Secure with
self tapping screws on eight inch centers. Do not puncture vapor barrier.
Section 23 07 00
Ductwrap Insulation
END OF SECTION
Section 23 07 00
Ductwrap Insulation
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
1.4
Product Data: For each type of product indicated. Include thermal conductivity, water-vapor
permeance thickness, and jackets (both factory- and field-applied if any).
QUALITY ASSURANCE
A.
B.
1.5
1.6
A.
1.7
A.
Schedule insulation application after pressure testing systems and, where required, after
installing and testing heat tracing. Insulation application may begin on segments that have
satisfactory test results.
B.
Complete installation and concealment of plastic materials as rapidly as possible in each area of
construction.
Section 23 07 13
Mechanical Insulation
PART 2 - PRODUCTS
2.1
INSULATION MATERIALS
A.
B.
C.
Products that come in contact with stainless steel shall have a leachable chloride content of less
than 50 ppm when tested according to ASTM C 871.
D.
Insulation materials for use on austenitic stainless steel shall be qualified as acceptable
according to ASTM C 795.
E.
Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing
process.
F.
Mineral-Fiber Blanket Insulation: Mineral or glass fibers bonded with a thermosetting resin.
Comply with ASTM C 553, Type II and ASTM C 1290,. Factory-applied jacket requirements are
specified in "Factory-Applied Jackets" Article.
G.
Mineral-Fiber Board Insulation: Mineral or glass fibers bonded with a thermosetting resin.
Comply with ASTM C 612, Type IA or Type IB. Factory-applied jacket requirements are
specified in "Factory-Applied Jackets" Article.
H.
I.
2.2
ADHESIVES
A.
Materials shall be compatible with insulation materials, jackets, and substrates and for bonding
insulation to itself and to surfaces to be insulated unless otherwise indicated.
B.
C.
Flexible Elastomeric and Polyolefin Adhesive: Comply with MIL-A-24179A, Type II, Class I.
D.
ASJ Adhesive, and FSK Jacket Adhesive: Comply with MIL-A-3316C, Class 2, Grade A for
bonding insulation jacket lap seams and joints.
2.3
SEALANTS
A.
Section 23 07 13
Mechanical Insulation
2.4
FACTORY-APPLIED JACKETS
A.
2.5
A.
Field-applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated.
B.
Metal Jacket:
1.
Aluminum Jacket: Comply with ASTM B 209 (ASTM B 209M), Alloy 3003, 3005, 3105, or
5005, Temper H-14.
a.
Aluminum finish.
b.
Factory-Fabricated Fitting Covers:
1). Same material, finish, and thickness as jacket.
2). Preformed 2-piece or gore, 45- and 90-degree, short- and long-radius elbows.
3). Tee covers.
4). Flange and union covers.
5). End caps.
6). Beveled collars.
7). Valve covers.
8). Field fabricate fitting covers only if factory-fabricated fitting covers are not
available.
2.6
TAPES
A.
FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic adhesive;
complying with ASTM C 1136.
1.
Width: 3 inches (75 mm).
2.
Thickness: 6.5 mils (0.16 mm).
3.
Adhesion: 90 ounces force/inch (1.0 N/mm) in width.
4.
Elongation: 2 percent.
5.
Tensile Strength: 40 lbf/inch (7.2 N/mm) in width.
6.
FSK Tape Disks and Squares: Precut disks or squares of FSK tape.
B.
C.
Staples: Outward-clinching insulation staples, nominal 3/4-inch- (19-mm-) wide, stainless steel
or Monel.
Section 23 07 13
Mechanical Insulation
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine substrates and conditions for compliance with requirements for installation tolerances
and other conditions affecting performance of insulation application.
1.
Verify that systems to be insulated have been tested and are free of defects.
2.
Verify that surfaces to be insulated are clean and dry.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
PREPARATION
A.
3.3
Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will
adversely affect insulation application.
GENERAL INSTALLATION REQUIREMENTS
A.
Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces;
free of voids throughout the length of pipes and fittings.
B.
Install insulation materials, vapor barriers or retarders, jackets, and thicknesses required for
each item of pipe system as specified in insulation system schedules.
C.
Install accessories compatible with insulation materials and suitable for the service. Install
accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or
dry state.
D.
Install insulation with longitudinal seams at top and bottom of horizontal runs.
E.
Install multiple layers of insulation with longitudinal and end seams staggered.
F.
G.
Install insulation with tight longitudinal seams and end joints. Bond seams and joints with
adhesive recommended by insulation material manufacturer.
H.
I.
Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers,
supports, anchors, and other projections with vapor-barrier mastic.
1.
Install insulation continuously through hangers and around anchor attachments.
2.
For insulation application where vapor barriers are indicated, extend insulation on anchor
legs from point of attachment to supported item to point of attachment to structure. Taper
and seal ends at attachment to structure with vapor-barrier mastic.
3.
Install insert materials and install insulation to tightly join the insert. Seal insulation to
insulation inserts with adhesive or sealing compound recommended by insulation
material manufacturer.
J.
Apply adhesives, mastics, and sealants at manufacturers recommended coverage rate and wet
and dry film thicknesses.
K.
Section 23 07 13
Mechanical Insulation
2.
3.
4.
5.
Cover circumferential joints with 3-inch- (75-mm-) wide strips, of same material as
insulation jacket. Secure strips with adhesive and outward clinching staples along both
edges of strip, spaced 4 inches (100 mm) o.c.
Overlap jacket longitudinal seams at least 1-1/2 inches (38 mm). Clean and dry surface
to receive self-sealing lap. Staple laps with outward clinching staples along edge at 2
inches (50 mm) o.c.
a.
For below ambient services, apply vapor-barrier mastic over staples.
Cover joints and seams with tape, according to insulation material manufacturers written
instructions, to maintain vapor seal.
Where vapor barriers are indicated, apply vapor-barrier mastic on seams and joints and
at ends adjacent to pipe flanges and fittings.
L.
Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal
thickness.
M.
Finish installation with systems at operating conditions. Repair joint separations and cracking
due to thermal movement.
N.
Repair damaged insulation facings by applying same facing material over damaged areas.
Extend patches at least 4 inches (100 mm) beyond damaged areas. Adhere, staple, and seal
patches similar to butt joints.
3.4
Requirements in this article generally apply to all insulation materials except where more
specific requirements are specified in various pipe insulation material installation articles.
B.
Section 23 07 13
Mechanical Insulation
7.
8.
9.
Cover segmented insulated surfaces with a layer of finishing cement and coat with a
mastic. Install vapor-barrier mastic for below-ambient services and a breather mastic for
above-ambient services. Reinforce the mastic with fabric-reinforcing mesh. Trowel the
mastic to a smooth and well-shaped contour.
For services not specified to receive a field-applied jacket except for flexible elastomeric
and polyolefin, install fitted PVC cover over elbows, tees, strainers, valves, flanges, and
unions. Terminate ends with PVC end caps. Tape PVC covers to adjoining insulation
facing using PVC tape.
Stencil or label the outside insulation jacket of each union with the word "union." Match
size and color of pipe labels.
C.
Insulate instrument connections for thermometers, pressure gages, pressure temperature taps,
test connections, flow meters, sensors, switches, and transmitters on insulated pipes. Shape
insulation at these connections by tapering it to and around the connection with insulating
cement and finish with finishing cement, mastic, and flashing sealant.
D.
Install removable insulation covers at locations indicated. Installation shall conform to the
following:
1.
Make removable flange and union insulation from sectional pipe insulation of same
thickness as that on adjoining pipe. Install same insulation jacket as adjoining pipe
insulation.
2.
When flange and union covers are made from sectional pipe insulation, extend insulation
from flanges or union long at least two times the insulation thickness over adjacent pipe
insulation on each side of flange or union. Secure flange cover in place with stainlesssteel or aluminum bands. Select band material compatible with insulation and jacket.
3.
Construct removable valve insulation covers in same manner as for flanges, except
divide the two-part section on the vertical center line of valve body.
4.
When covers are made from block insulation, make two halves, each consisting of
mitered blocks wired to stainless-steel fabric. Secure this wire frame, with its attached
insulation, to flanges with tie wire. Extend insulation at least 2 inches (50 mm) over
adjacent pipe insulation on each side of valve. Fill space between flange or union cover
and pipe insulation with insulating cement. Finish cover assembly with insulating cement
applied in two coats. After first coat is dry, apply and trowel second coat to a smooth
finish.
5.
Unless a PVC jacket is indicated in field-applied jacket schedules, finish exposed
surfaces with a metal jacket.
3.5
Seal longitudinal seams and end joints with manufacturers recommended adhesive to eliminate
openings in insulation that allow passage of air to surface being insulated.
B.
C.
Section 23 07 13
Mechanical Insulation
D.
3.6
A.
B.
C.
D.
3.7
Where metal jackets are indicated, install with 2-inch (50-mm) overlap at longitudinal seams and
end joints. Overlap longitudinal seams arranged to shed water. Seal end joints with
weatherproof sealant recommended by insulation manufacturer. Secure jacket with stainlesssteel bands 12 inches (300 mm) o.c. and at end joints.
Section 23 07 13
Mechanical Insulation
3.8
FINISHES
A.
Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of
insulation manufacturers recommended protective coating.
B.
3.9
END OF SECTION
Section 23 07 13
Mechanical Insulation
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
This Section includes control equipment for HVAC systems and components, including control
components for terminal heating and cooling units not supplied with factory-wired controls.
SUBMITTALS
A.
Product Data: Include manufacturer's technical literature for each control device. Indicate
dimensions, capacities, performance characteristics, electrical characteristics, finishes for
materials, and installation and startup instructions for each type of product indicated.
B.
Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of each field
connection.
1.
Bill of materials of equipment indicating quantity, manufacturer, and model number.
2.
Schematic flow diagrams showing fans, pumps, coils, dampers, valves, and control
devices.
3.
Wiring Diagrams: Power, signal, and control wiring.
4.
Details of control panel faces, including controls, instruments, and labeling.
5.
Written description of sequence of operation.
6.
Schedule of dampers including size, leakage, and flow characteristics.
7.
Schedule of valves including flow characteristics.
C.
D.
E.
Operation and Maintenance Data: For HVAC instrumentation and control system to include in
emergency, operation, and maintenance manuals. In addition to items specified in Division 01
Section "Operation and Maintenance Data," include the following:
1.
Maintenance instructions and lists of spare parts for each type of control device and
compressed-air station.
2.
Interconnection wiring diagrams with identified and numbered system components and
devices.
3.
Keyboard illustrations and step-by-step procedures indexed for each operator function.
4.
Inspection period, cleaning methods, cleaning materials recommended, and calibration
tolerances.
5.
Calibration records and list of set points.
1.4
QUALITY ASSURANCE
A.
Section 23 09 00
Instrumentation and Control for HVAC
B.
1.5
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
DELIVERY, STORAGE, AND HANDLING
A.
1.6
Factory-Mounted Components: Where control devices specified in this Section are indicated to
be factory mounted on equipment, arrange for shipping of control devices to equipment
manufacturer.
COORDINATION
A.
Coordinate location of thermostats, humidistats, and other exposed control sensors with plans
and room details before installation.
B.
C.
D.
Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete,
reinforcement, and formwork requirements are specified in Division 03 Section "Cast-in-Place
Concrete."
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
THERMOSTATS
A.
Manufacturers:
1.
Erie Controls.
2.
Danfoss Inc.; Air-Conditioning and Refrigeration Div.
3.
Heat-Timer Corporation.
4.
Sauter Controls Corporation.
5.
tekmar Control Systems, Inc.
6.
Theben AG - Lumilite Control Technology, Inc.
B.
Combination Thermostat and Fan Switches: Line-voltage thermostat with push-button or leveroperated fan switch.
1.
Label switches "FAN ON/OFF/AUTO"
2.
Mount on single electric switch box.
C.
D.
Section 23 09 00
Instrumentation and Control for HVAC
rating; with concealed set-point adjustment, 55 to 85 deg F (13 to 30 deg C) set-point range,
and 2 deg F (1 deg C) maximum differential.
1.
Electric Heating Thermostats: Equip with off position on dial wired to break ungrounded
conductors.
2.
Selector Switch: Integral, manual on-off-auto.
2.3
HUMIDISTATS
A.
Manufacturers:
1.
MAMAC Systems, Inc.
2.
ROTRONIC Instrument Corp.
B.
Humidistats: Electric insertion, 2-position type with adjustable, 2 percent throttling range, 20 to
80 percent operating range, and single- or double-pole contacts.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install software in control units and operator workstation(s). Implement all features of programs
to specified requirements and as appropriate to sequence of operation.
B.
Connect and configure equipment and software to achieve sequence of operation specified.
C.
Verify location of thermostats, humidistats, and other exposed control sensors with Drawings
and room details before installation. Install devices as shown on Drawings.
D.
E.
Install damper motors on outside of duct in warm areas, not in locations exposed to outdoor
temperatures.
F.
Install labels and nameplates to identify control components according to Division 23 Section
"Identification for HVAC Piping and Equipment."
G.
Install duct volume-control dampers according to Division 23 Sections specifying air ducts.
3.2
Install raceways, boxes, and cabinets according to Division 26 Section "Raceway and Boxes for
Electrical Systems."
B.
Install building wire and cable according to Division 26 Section "Low-Voltage Electrical Power
Conductors and Cables."
3.3
B.
Perform the following field tests and inspections and prepare test reports:
1.
Operational Test: After electrical circuitry has been energized, start units to confirm
proper unit operation. Remove and replace malfunctioning units and retest.
2.
Test and adjust controls and safeties.
Section 23 09 00
Instrumentation and Control for HVAC
3.
4.
5.
C.
3.4
Test each point through its full operating range to verify that safety and operating control
set points are as required.
Test each system for compliance with sequence of operation.
Test interlocks.
Replace damaged or malfunctioning controls and equipment and repeat testing procedures.
ADJUSTING
A.
B.
C.
3.5
DEMONSTRATION
A.
END OF SECTION
Section 23 09 00
Instrumentation and Control for HVAC
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
1.4
A.
Refrigerant piping diagram with all pipe sizes and fittings: Based on actual pipe lengths, fittings,
and elevations.
B.
Product Data: For each type of valve and refrigerant piping specialty indicated.
pressure drop, based on manufacturers test data, for the following:
1.
Thermostatic expansion valves.
2.
Pressure-regulating valves.
3.
Replaceable core filters
1.5
Include
QUALITY ASSURANCE
A.
Welding: Qualify procedures and personnel according to ASME Boiler and Pressure Vessel
Code: Section IX, "Welding and Brazing Qualifications."
B.
C.
Comply with ASME B31.5, "Refrigeration Piping and Heat Transfer Components."
1.6
1.7
Store piping in a clean and protected area with end caps in place to ensure that piping interior
and exterior are clean when installed.
COORDINATION
A.
Coordinate size and location of roof curbs, equipment supports, and roof penetrations.
PART 2 - PRODUCTS
2.1
B.
Section 23 23 00
Refrigerant Piping
C.
D.
2.2
Service Valves:
1.
Body: Forged brass with brass cap including key end to remove core.
2.
Core: Removable ball-type check valve with stainless-steel spring.
3.
Seat: Polytetrafluoroethylene.
4.
End Connections: Copper spring.
5.
Working Pressure Rating: 500 psig.
B.
C.
Filters:
1.
Body: Forged brass.
2.
Core: Replaceable
3.
End Connections: Socket or flare.
4.
Working Pressure Rating: 500 psig.
5.
Maximum Operating Temperature: 240 deg F.
D.
Moisture/Liquid Indicators:
1.
Body: Forged brass.
2.
Window: Replaceable, clear, fused glass window with indicating element protected by
filter screen.
3.
Indicator: Color coded to show moisture content in ppm.
4.
Minimum Moisture Indicator Sensitivity: Indicate moisture above 60 ppm.
5.
End Connections: Socket or flare.
6.
Working Pressure Rating: 500 psig.
7.
Maximum Operating Temperature: 240 deg F.
2.3
REFRIGERANTS
A.
PART 3 - EXECUTION
3.1
NPS 1-1/2 and Smaller for Conventional Air-Conditioning Applications: Copper, Type ACR,
annealed-temper tubing and wrought-copper fittings with brazed joints.
B.
NPS 2 to NPS 3-1/2 Insert pipe size range for Conventional Air-Conditioning Applications:
Copper, Type ACR, drawn-temper tubing and wrought-copper fittings with brazed joints.
Section 23 23 00
Refrigerant Piping
3.2
Install service valves for gage taps at inlet and outlet of hot-gas bypass valves and strainers if
they are not an integral part of valves and strainers.
B.
C.
Install moisture/liquid indicators in liquid line at the inlet of the thermostatic expansion valve or
at the inlet of the evaporator coil capillary tube.
3.3
PIPING INSTALLATION
A.
Drawing plans, schematics, and diagrams indicate general location and arrangement of piping
systems; indicated locations and arrangements were used to size pipe and calculate friction
loss, expansion, pump sizing, and other design considerations. Install piping as indicated
unless deviations to layout are approved on Shop Drawings.
B.
C.
D.
Install piping in concealed locations unless otherwise indicated and except in equipment rooms
and service areas.
E.
Install piping indicated to be exposed and piping in equipment rooms and service areas at right
angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated
otherwise.
F.
Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
G.
H.
I.
J.
Select system components with pressure rating equal to or greater than system operating
pressure.
K.
Install piping as short and direct as possible, with a minimum number of joints, elbows, and
fittings.
L.
Arrange piping to allow inspection and service of refrigeration equipment. Install valves and
specialties in accessible locations to allow for service and inspection.
M.
N.
Install refrigerant piping in rigid or flexible conduit in locations where exposed to mechanical
injury.
Section 23 23 00
Refrigerant Piping
O.
P.
When brazing or soldering, remove solenoid-valve coils and sight glasses; also remove valve
stems, seats, and packing, and accessible internal parts of refrigerant specialties. Do not apply
heat near expansion-valve bulb.
Q.
R.
S.
Install piping with adequate clearance between pipe and adjacent walls and hangers or between
pipes for insulation installation.
T.
Install sleeves through floors, walls, or ceilings, sized to permit installation of full-thickness
insulation.
U.
V.
Identify refrigerant piping and valves according to Division 15 Section "Basic Mechanical
Materials and Methods."
3.4
Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
B.
Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before
assembly.
C.
Fill pipe and fittings with an inert gas (nitrogen or carbon dioxide), during brazing or welding, to
prevent scale formation.
D.
Brazed Joints: Construct joints according to AWSs "Brazing Handbook," Chapter "Pipe and
Tube."
1.
Use Type BcuP, copper-phosphorus alloy for joining copper socket fittings with copper
pipe.
2.
Use Type BAg, cadmium-free silver alloy for joining copper with bronze or steel.
3.5
B.
Install hangers for copper tubing with the following maximum spacing and minimum rod sizes:
1.
NPS 1/2: Maximum span, 60 inches; minimum rod size, 1/4 inch.
Section 23 23 00
Refrigerant Piping
2.
3.
4.
5.
6.
7.
8.
9.
C.
NPS 5/8: Maximum span, 60 inches; minimum rod size, 1/4 inch.
NPS 1: Maximum span, 72 inches; minimum rod size, 1/4 inch.
NPS 1-1/4: Maximum span, 96 inches; minimum rod size, 3/8 inch.
NPS 1-1/2: Maximum span, 96 inches; minimum rod size, 3/8 inch.
NPS 2: Maximum span, 96 inches; minimum rod size, 3/8 inch.
NPS 2-1/2: Maximum span, 108 inches; minimum rod size, 3/8 inch.
NPS 3: Maximum span, 10 feet; minimum rod size, 3/8 inch.
NPS 4: Maximum span, 12 feet; minimum rod size, 1/2 inch.
Support multi-floor vertical runs at least at each floor or at every 10 feet; the lesser of the two.
END OF SECTION
Section 23 23 00
Refrigerant Piping
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
Section Includes:
1.
Rectangular ducts and fittings.
2.
Sheet metal materials.
3.
Duct liner.
4.
Sealants and gaskets.
5.
Hangers and supports.
B.
Related Sections:
1.
Division 23 Section 23 05 93 "Testing, Adjusting, and Balancing" for testing, adjusting,
and balancing requirements for metal ducts.
1.3
PERFORMANCE REQUIREMENTS
A.
Delegated Duct Design: Duct construction, including sheet metal thicknesses, seam and joint
construction, reinforcements, and hangers and supports, shall comply with SMACNA's "HVAC
Duct Construction Standards - Metal and Flexible" and performance requirements and design
criteria indicated in "Duct Schedule" Article.
B.
Structural Performance: Duct hangers and supports shall withstand the effects of gravity loads
and stresses within limits and under conditions described in SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible".
C.
Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in
ASHRAE 62.1-2004.
1.4
SUBMITTALS
A.
PART 2 - PRODUCTS
2.1
B.
Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible," Figure 1-4, "Transverse (Girth) Joints," for staticpressure class, applicable sealing requirements, materials involved, duct-support intervals, and
other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
Section 23 31 13
Metal Ducts
C.
Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible," Figure 1-5, "Longitudinal Seams - Rectangular
Ducts," for static-pressure class, applicable sealing requirements, materials involved, ductsupport intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards Metal and Flexible."
D.
Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types
and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and
Flexible," Chapter 2, "Fittings and Other Construction," for static-pressure class, applicable
sealing requirements, materials involved, duct-support intervals, and other provisions in
SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."
2.2
General Material Requirements: Comply with SMACNA's "HVAC Duct Construction Standards
- Metal and Flexible" for acceptable materials, material thicknesses, and duct construction
methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks,
roller marks, stains, discolorations, and other imperfections.
B.
C.
Reinforcement Shapes and Plates: ASTM A 36/A 36M, steel plates, shapes, and bars; black
and galvanized.
1.
Where black- and galvanized-steel shapes and plates are used to reinforce aluminum
ducts, isolate the different metals with butyl rubber, neoprene, or EPDM gasket materials.
D.
Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch
minimum diameter for lengths longer than 36 inches.
2.3
DUCT LINER
A.
Flexible Elastomeric Duct Liner: Preformed, cellular, closed-cell, sheet materials complying with
ASTM C 534, Type II, Grade 1; and with NFPA 90A or NFPA 90B.
1.
Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
a.
Aeroflex USA Inc.
b.
Armacell LLC.
c.
Rubatex International, LLC
2.
Surface-Burning Characteristics: Maximum flame-spread index of 25 and maximum
smoke-developed index of 50 when tested according to UL 723; certified by an NRTL.
3.
Liner Adhesive: As recommended by insulation manufacturer and complying with
NFPA 90A or NFPA 90B.
a.
Use adhesive that has a VOC content of 50 g/L or less when calculated according
to 40 CFR 59, Subpart D (EPA Method 24).
B.
C.
Shop Application of Duct Liner: Comply with SMACNA's "HVAC Duct Construction Standards Metal and Flexible," Figure 2-19, "Flexible Duct Liner Installation."
Section 23 31 13
Metal Ducts
1.
2.
3.
4.
5.
6.
7.
8.
9.
2.4
Adhere a single layer of indicated thickness of duct liner with at least 90 percent adhesive
coverage at liner contact surface area. Attaining indicated thickness with multiple layers
of duct liner is prohibited.
Apply adhesive to transverse edges of liner facing upstream that do not receive metal
nosing.
Butt transverse joints without gaps, and coat joint with adhesive.
Fold and compress liner in corners of rectangular ducts or cut and fit to ensure buttededge overlapping.
Do not apply liner in rectangular ducts with longitudinal joints, except at corners of ducts,
unless duct size and dimensions of standard liner make longitudinal joints necessary.
Apply adhesive coating on longitudinal seams in ducts with air velocity of 2500 fpm.
Secure liner with mechanical fasteners 4 inches from corners and at intervals not
exceeding 12 inches transversely; at 3 inches from transverse joints and at intervals not
exceeding 18 inches longitudinally.
Secure transversely oriented liner edges facing the airstream with metal nosings that
have either channel or "Z" profiles or are integrally formed from duct wall. Fabricate edge
facings at the following locations:
a.
Fan discharges.
b.
Intervals of lined duct preceding unlined duct.
c.
Upstream edges of transverse joints in ducts where air velocities are higher than
2500 fpm or where indicated.
Terminate inner ducts with buildouts attached to fire-damper sleeves, dampers, turning
vane assemblies, or other devices. Fabricated buildouts (metal hat sections) or other
buildout means are optional; when used, secure buildouts to duct walls with bolts,
screws, rivets, or welds.
General Sealant and Gasket Requirements: Surface-burning characteristics for sealants and
gaskets shall be a maximum flame-spread index of 25 and a maximum smoke-developed index
of 50 when tested according to UL 723; certified by an NRTL.
B.
C.
D.
Flange Gaskets: Butyl rubber, neoprene, or EPDM polymer with polyisobutylene plasticizer.
Section 23 31 13
Metal Ducts
2.5
Hanger Rods for Noncorrosive Environments: Cadmium-plated steel rods and nuts.
B.
Hanger Rods for Corrosive Environments: Electrogalvanized, all-thread rods or galvanized rods
with threads painted with zinc-chromate primer after installation.
C.
Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
Flexible," Table 4-1, "Rectangular Duct Hangers Minimum Size," and Table 4-2, "Minimum
Hanger Sizes for Round Duct."
D.
Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible
with duct materials.
E.
PART 3 - EXECUTION
3.1
DUCT INSTALLATION
A.
Drawing plans, schematics, and diagrams indicate general location and arrangement of duct
system. Indicated duct locations, configurations, and arrangements were used to size ducts
and calculate friction loss for air-handling equipment sizing and for other design considerations.
Install duct systems as indicated unless deviations to layout are approved on Shop Drawings
and Coordination Drawings.
B.
Install ducts according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"
unless otherwise indicated.
C.
D.
Install factory- or shop-fabricated fittings for changes in direction, size, and shape and for
branch connections.
E.
Unless otherwise indicated, install ducts vertically and horizontally, and parallel and
perpendicular to building lines.
F.
Install ducts as high as practical, close to walls, overhead construction, columns, and other
structural and permanent enclosure elements of building.
G.
Install ducts with a clearance of 1 inch, plus allowance for insulation thickness.
H.
Route ducts to avoid passing through transformer vaults and electrical equipment rooms and
enclosures.
I.
Where ducts pass through non-fire-rated interior partitions and exterior walls and are exposed
to view, cover the opening between the partition and duct or duct insulation with sheet metal
flanges of same metal thickness as the duct. Overlap openings on four sides by at least 1-1/2
inches.
J.
Where ducts pass through fire-rated interior partitions and exterior walls, install fire dampers.
Comply with requirements of the local code for fire and smoke dampers.
Section 23 31 13
Metal Ducts
K.
3.2
Protect duct interiors from moisture, construction debris and dust, and other foreign
materials. Comply with SMACNA's "Duct Cleanliness for New Construction Guidelines."
INSTALLATION OF EXPOSED DUCTWORK
A.
Protect ducts exposed in finished spaces from being dented, scratched, or damaged; furnish
ductwork free of visual imperfections, ready for field applied painting.
B.
Trim duct sealants flush with metal. Create a smooth and uniform exposed bead. Do not use
tape sealing system.
C.
Grind welds to provide smooth surface free of burrs, sharp edges, and weld splatter. When
welding stainless steel with a No. 3 or 4 finish, grind the welds flush, polish the exposed welds,
and treat the welds to remove discoloration caused by welding.
D.
Maintain consistency, symmetry, and uniformity in the arrangement and fabrication of fittings,
hangers and supports, duct accessories, and air outlets.
E.
Repair or replace damaged sections and finished work that does not comply with these
requirements.
3.3
DUCT SEALING
A.
Seal ducts for duct static-pressure, seal classes, and leakage classes specified in "Duct
Schedule" Article according to SMACNA's "HVAC Duct Construction Standards - Metal and
Flexible."
B.
Seal ducts to the pressure classes according to SMACNA's "HVAC Duct Construction
Standards - Metal and Flexible":
1.
Ductwork in conditioned spaces (including return air plenums):
a.
Supply air ducts: seal traverse joints and duct wall penetrations.
b.
Return air ducts: seal traverse joints and duct wall penetrations.
c.
Exhaust air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
d.
Outside air ducts: seal traverse joints and duct wall penetrations.
2.
Ductwork in unconditioned spaces:
a.
Supply air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
b.
Return air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
c.
Exhaust air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
d.
Outside air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
3.
Ductwork located outdoors:
a.
Supply air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
b.
Return air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
c.
Exhaust air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
d.
Outside air ducts: seal traverse joints, longitudinal seams, and duct wall
penetrations.
Section 23 31 13
Metal Ducts
3.4
Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 4,
"Hangers and Supports."
B.
C.
Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and
Flexible," Table 4-1, "Rectangular Duct Hangers Minimum Size," and Table 4-2, "Minimum
Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports
within 24 inches of each elbow and within 48 inches of each branch intersection.
D.
Hangers Exposed to View: Threaded rod and angle or channel supports. Install swiveling
attachment devices or field fabricated attachments to provide threaded rods vertical installation.
E.
Support vertical ducts with steel angles or channel secured to the sides of the duct with welds,
bolts, sheet metal screws, or blind rivets; support at each floor and at a maximum intervals of 16
feet.
F.
Install upper attachments to structures. Select and size upper attachments with pull-out,
tension, and shear capacities appropriate for supported loads and building materials where
used.
3.5
CONNECTIONS
A.
B.
Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for branch,
outlet and inlet, and terminal unit connections.
3.6
PAINTING
A.
3.7
Prime and paint exterior of metal ducts located outdoors; color to match building color.
DUCT CLEANING
A.
B.
C.
Section 23 31 13
Metal Ducts
4.
5.
6.
7.
D.
3.8
A.
3.9
Air Balance: Comply with requirements in Division 23 Section 23 05 93 "Testing, Adjusting, and
Balancing."
DUCT SCHEDULE
A.
B.
Liner:
1.
Rectangular ducts shall be internally lined with 1-inch thick liner.
C.
Elbow Configuration:
1.
Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
and Flexible," Figure 2-2, "Rectangular Elbows."
a.
Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio.
b.
Radius Type RE 3 with minimum 1.0 radius-to-diameter ratio and two vanes.
c.
Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible," Figure 2-3, "Vanes and Vane
Runners," and Figure 2-4, "Vane Support in Elbows."
D.
Branch Configuration:
1.
Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
and Flexible," Figure 2-6, "Branch Connections."
a.
Rectangular Main to Rectangular Branch: 45-degree entry.
b.
Rectangular Main to Round Branch: 45-degree lead in.
2.
Round and Flat Oval: Comply with SMACNA's "HVAC Duct Construction Standards Metal and Flexible," Figure 3-4, "90 Degree Tees and Laterals," and Figure 3-5, "Conical
Tees." Saddle taps are permitted in existing duct.
a.
45 degree lateral.
Section 23 31 13
Metal Ducts
END OF SECTION
Section 23 31 13
Metal Ducts
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Manual volume dampers.
2.
Flange connectors.
3.
Turning vanes.
4.
Flexible connectors.
5.
Flexible ducts.
6.
Duct accessory hardware.
SUBMITTALS
A.
B.
1.4
QUALITY ASSURANCE
A.
Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with
NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."
B.
PART 2 - PRODUCTS
2.1
MATERIALS
A.
Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for
acceptable materials, material thicknesses, and duct construction methods unless otherwise
indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains,
discolorations, and other imperfections.
B.
C.
Stainless-Steel Sheets: Comply with ASTM A 480/A 480M, Type 304, and having a No. 2 finish
for concealed ducts and exposed ducts.
D.
Aluminum Sheets: Comply with ASTM B 209 (ASTM B 209M), Alloy 3003, Temper H14; with
mill finish for concealed ducts and standard, 1-side bright finish for exposed ducts.
E.
Extruded Aluminum: Comply with ASTM B 221 (ASTM B 221M), Alloy 6063, Temper T6.
Section 23 33 00
Air Duct Accessories
F.
G.
Tie Rods: Galvanized steel, 1/4-inch (6-mm) minimum diameter for lengths 36 inches (900 mm)
or less; 3/8-inch (10-mm) minimum diameter for lengths longer than 36 inches (900 mm).
2.2
2.3
A.
B.
Description:
components.
C.
D.
Section 23 33 00
Air Duct Accessories
2.4
TURNING VANES
A.
General Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal
and Flexible"; Figures 4-3, "Vanes and Vane Runners," and 4-4, "Vane Support in Elbows."
B.
Vane Construction: Single wall for ducts up to [48 inches (1200 mm)] wide and double wall for
larger dimensions.
2.5
2.6
Duct-Mounted Access Doors: Fabricate access panels according to SMACNA's "HVAC Duct
Construction Standards - Metal and Flexible"; Figures 7-2 (7-2M), "Duct Access Doors and
Panels," and 7-3, "Access Doors - Round Duct."
1.
Door:
a.
Double wall, rectangular.
b.
Galvanized sheet metal with insulation fill and thickness as indicated for duct
pressure class.
c.
Vision panel.
d.
Hinges and Latches: 1-by-1-inch (25-by-25-mm) butt or piano hinge and cam
latches.
e.
Fabricate doors airtight and suitable for duct pressure class.
2.
Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets.
3.
Number of Hinges and Locks:
a.
Access Doors Less Than 12 Inches (300 mm) Square: No hinges and two sash
locks.
b.
Access Doors up to 18 Inches (460 mm) Square: Two hinges and two sash locks.
c.
Access Doors up to 24 by 48 Inches (600 by 1200 mm): Three hinges and two
compression latches with outside and inside handles.
d.
Access Doors Larger Than 24 by 48 Inches (600 by 1200 mm): Four hinges and
two compression latches with outside and inside handles.
FLEXIBLE CONNECTORS
A.
B.
C.
D.
Metal-Edged Connectors: Factory fabricated with a fabric strip [3-1/2 inches (89 mm)] [5-3/4
inches (146 mm)] wide attached to 2 strips of 2-3/4-inch- (70-mm-) wide, 0.028-inch- (0.7-mm-)
thick, galvanized sheet steel or 0.032-inch- (0.8-mm-) thick aluminum sheets. Provide metal
compatible with connected ducts.
2.7
FLEXIBLE DUCTS
A.
Section 23 33 00
Air Duct Accessories
3.
B.
Insulated, Flexible Duct: UL 181, Class 1, 2-ply vinyl film supported by helically wound, springsteel wire; fibrous-glass insulation; aluminized vapor-barrier film.
1.
Pressure Rating: 10-inch wg (2500 Pa) positive and 1.0-inch wg (250 Pa) negative.
2.
Maximum Air Velocity: 4000 fpm (20 m/s).
3.
Temperature Range: Minus 10 to plus 160 deg F (Minus 23 to plus 71 deg C).
4.
Insulation R-value: Comply with ASHRAE/IESNA 90.1.
C.
2.8
Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap
and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to
suit duct-insulation thickness.
B.
Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline
and grease.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install duct accessories according to applicable details in SMACNA's "HVAC Duct Construction
Standards - Metal and Flexible" for metal ducts and in NAIMA AH116, "Fibrous Glass Duct
Construction Standards," for fibrous-glass ducts.
B.
Install duct accessories of materials suited to duct materials; use galvanized-steel accessories
in galvanized-steel and fibrous-glass ducts, stainless-steel accessories in stainless-steel ducts,
and aluminum accessories in aluminum ducts.
C.
Install volume dampers at points on supply, return, and exhaust systems where branches
extend from larger ducts. Where dampers are installed in ducts having duct liner, install
dampers with hat channels of same depth as liner, and terminate liner with nosing at hat
channel.
1.
Install steel volume dampers in steel ducts.
D.
Set dampers to fully open position before testing, adjusting, and balancing.
E.
Install test holes at fan inlets and outlets and elsewhere as indicated.
F.
Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining
accessories and equipment at the following locations:
1.
On both sides of duct coils.
2.
Upstream from filters.
3.
At outdoor-air intakes and mixed-air plenums.
4.
Elsewhere as indicated.
G.
H.
Section 23 33 00
Air Duct Accessories
1.
2.
3.
4.
I.
Label access doors according to Division 23 Section "Identification for HVAC Piping and
Equipment" to indicate the purpose of access door.
J.
K.
For fans developing static pressures of 5-inch wg (1250 Pa) and more, cover flexible connectors
with loaded vinyl sheet held in place with metal straps.
L.
Connect flexible ducts to metal ducts with adhesive plus sheet metal screws.
M.
Install duct test holes where required for testing and balancing purposes.
3.2
END OF SECTION
Section 23 33 00
Air Duct Accessories
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
Section includes the air distribution outlets, exhaust and return air devices, and the accessories
required for complete installation.
B.
The work of this section is subject to the requirements of Section 23 05 00 Common Work
Results for Mechanical.
1.3
B.
C.
D.
1.4
SUBMITTALS
A.
Submittals shall include manufacturers technical literature for performance (sound pressure
loss, throw) pictorial literature, and schedule shall be submitted indicating the style and size of
each diffuser or grille, location by room number, CFM of unit, throw, noise level, (NC rating)
method of mounting and finish.
Section 23 37 13
Air Outlets and Inlets
1.5
ACCEPTABLE MANUFACTURERS
A.
PART 2 - PRODUCTS
2.1
GENERAL
A.
Product performance data shall be taken from tests conducted in accordance with ISO Standard
3741, ISO Standard 5135, ISO Standard 5219, ISO Standard 5279, ISO Standard 7244, ISO
Standard 7730-7794, ANSI/ASHRAE 70, and ARI-890.
B.
Exhaust grilles and registers including volume controllers for toilet rooms and janitors' closets,
shall be constructed entirely of aluminum. Except where aluminum is specified, remainder of
diffusers, grilles and registers may be constructed of steel including volume controllers.
C.
Grilles and frames constructed of aluminum shall have a 60 minute anodized aluminum finish.
All other grilles and diffusers shall have a white flo-coat finish suitable as a finish coat or for field
painting.
D.
Refer to architectural drawings for the various types of ceilings, i.e., mineral tile or plaster to
assure that air devices have the correct type of mounting. Refer to drawings of reflected ceiling
plans for location of ceiling diffusers and grilles.
E.
Supplier shall also check all air distribution and return air devices for proper performance, noise
and accessories. Any device exceeding noise level herein specified shall be brought to the
attention of the Engineers.
F.
Contractor shall coordinate openings in hard ceilings, furred walls, masonry walls, and floors.
G.
The nominal or duct connection size of grilles (not overall dimensions) is given on plans.
H.
Device
Supply Grilles
Return Grilles
I.
2.2
Abbreviation used
on the Drawings
S#
R#
A third letter following these abbreviations refers to the type of device which is defined herein.
CEILING DIFFUSER:
A.
Type A Square and Rectangular Louvered Face - 1-4 way, shall be Titus model TDC-Type 1
(surface) or TDC-Type 3 (lay-in). Removable core, square or rectangular neck, with air pattern
shown on the drawings. Diffusers shall be furnished with AG-95 opposed blade damper and
EGS equalizing grids.
Section 23 37 13
Air Outlets and Inlets
2.3
RETURN GRILLES:
A.
2.4
Type A - Titus model 50F, 1/2 inch aluminum grid. Register shall include an AG-35 opposed
blade damper.
SUPPLY GRILLES:
A.
Type A - Titus model 272 - High capacity supply louver. Supply grille shall be a double throw
supply grille with an opposed blade damper.
PART 3 - INSTALLATION
A.
Provide air devices as indicated on the drawings. Mount each device securely to avoid rattling
and vibration.
B.
Devices shall be parallel to the plane of the surfaces they are mounted on.
C.
Continuous linear devices shall be aligned, parallel to walls, with no perceptible distortion.
END OF SECTION
Section 23 37 13
Air Outlets and Inlets
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
Product Data: For each type of product indicated. Include rated capacities, operating
characteristics, and furnished specialties and accessories. Include performance data in terms
of capacities, outlet velocities, static pressures, sound power characteristics, motor
requirements, and electrical characteristics.
B.
C.
1.4
QUALITY ASSURANCE
A.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
B.
ASHRAE Compliance:
1.
Fabricate and label refrigeration system to comply with ASHRAE 15, "Safety Standard for
Refrigeration Systems."
C.
1.5
COORDINATION
A.
1.6
Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchorbolt inserts into bases.
WARRANTY
A.
1.7
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
Section 23 81 26
Split-System Air-Conditioning
1.
2.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
A.
Section 23 81 26
Split-System Air-Conditioning
2.3
3.
4.
5.
6.
7.
Section 23 81 26
Split-System Air-Conditioning
2.1
2.2
A.
Section 23 81 26
Split-System Air-Conditioning
f.
3.
4.
5.
6.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
B.
C.
Install ground-mounted, compressor-condenser units and indoor air handler units on 4-inch(100-mm-) thick, reinforced concrete base that is 4 inches (100 mm) larger, on each side, than
unit. Coordinate anchor installation with concrete base.
D.
E.
Install and connect precharged refrigerant tubing to components quick-connect fittings. Install
tubing to allow access to unit.
F.
Install hard copper condensate drain from air handlers to nearest point of discharge. Trap in
accordance with manufacturers installation instructions.
G.
H.
3.2
CONNECTIONS
A.
Piping installation requirements are specified in other Division 23 Sections. Drawings indicate
general arrangement of piping, fittings, and specialties.
B.
Where piping is installed adjacent to unit, allow space for service and maintenance of unit.
Section 23 81 26
Split-System Air-Conditioning
3.3
DEMONSTRATION
A.
END OF SECTION
Section 23 81 26
Split-System Air-Conditioning
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section includes:
1.
Electric unit heaters.
2.
Electric unit heaters, corrosion resistant.
3.
Gas-fired infrared radiant heaters.
4.
Sill, wall, and floor electric convection heaters.
5.
Electric duct heaters.
6.
Hot water or steam propeller unit heaters.
7.
Hot water or steam fin tube convection heaters.
8.
Electric make-up air furnace.
9.
Thermostats for unit heater.
REFERENCES
A.
B.
C.
D.
E.
F.
G.
H.
1.4
SYSTEM DESCRIPTION
A.
Design requirements:
1.
Provide seismic and wind supports meeting the seismic design criteria as specified in
Section 01 81 02 and wind design criteria for exterior units as specified in Section 01 81
04.
2.
Electrical components: UL listed and meeting the design and installation requirements of
the NEC.
3.
Hot water piping, gas piping, drains, venting, and other appurtenances of unit heaters:
Install in accordance with building code, mechanical code, plumbing code, and the NFPA.
4.
Noise levels for unit heaters installed in offices, hallways, or entry areas: Not to exceed
10 Sones as measured in accordance with AMCA Publication 302.
Section 23 83 33
Heating Units
5.
B.
C.
Design and supply necessary electrical power and control systems, components, and wiring to
make a complete functioning system.
1.5
SUBMITTALS
A.
Product Data: Include rated capacities, operating characteristics, furnished specialties, and
accessories for each product indicated.
B.
Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads,
required clearances, method of field assembly, components, and location and size of each field
connection.
1.
Plans, elevations, sections, and details.
2.
Location and size of each field connection.
3.
Details of anchorages and attachments to structure and to supported equipment.
4.
Equipment schedules to include rated capacities, operating characteristics, furnished
specialties, and accessories.
5.
Wiring Diagrams: Power, signal, and control wiring.
6.
Cut sheets on primary and ancillary equipment.
C.
Operation and Maintenance Data: For cabinet unit heaters to include in emergency, operation,
and maintenance manuals.
D.
Color / Finish.
E.
Warranties.
1.6
QUALITY ASSURANCE
A.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B.
C.
ASHRAE/IESNA 90.1-2004 Compliance: Applicable requirements in ASHRAE/IESNA 90.12004, Section 6 - "Heating, Ventilating, and Air-Conditioning."
D.
1.7
WARRANTY
A.
Extend warranty from the date of Project Acceptance or the date of first beneficial use of the
equipment.
B.
One-year manufacturers warranty on all components, except heating elements and coils.
C.
Section 23 83 33
Heating Units
PART 2 - PRODUCTS
2.1
B.
C.
D.
Features:
1.
Built-in magnetic contactors.
2.
Control transformer for 24-volt, 120-volt, or 240-volt control as indicated in the Heating
Unit Schedules.
3.
Required mounting brackets.
4.
Individually adjustable outlet louvers.
5.
Cabinet formed of minimum thickness 18-gauge steel with steel stiffeners.
6.
Controls:
a.
Provide thermostat as specified in this Section.
b.
Provide control transformer suitable for 24-volt, 120-volt, or 240-volt control as
indicated in the Heating Unit Schedules.
E.
Finishes:
1.
Casing finish backed enamel in manufacturers standard color.
2.2
B.
Section 23 83 33
Heating Units
C.
D.
Features:
1.
Built-in magnetic contactors.
2.
Control transformer for 24 or 120-volt control as indicated in the Heating Unit Schedules.
3.
Required mounting brackets.
4.
Individually adjustable outlet louvers.
5.
Cabinet formed of minimum thickness 20-gauge stainless steel type 304.
6.
Controls:
a.
Provide thermostat as specified in this Section.
b.
Provide control transformer suitable for 24-volt or 120-volt control as indicated in
the Heating Unit Schedules.
2.3
B.
Combustion surface:
1.
Material: Ceramic tile.
2.
Modular perforated construction suitable for sustaining 1,650 degrees Fahrenheit surface
temperature.
C.
D.
Features:
1.
Aluminum housing and reflector.
2.
Control transformer for 24- or 120-volt control as indicated in the Heating Unit Schedules.
3.
Required mounting brackets. Threaded hanger type suitable for wall or ceiling mounting.
4.
Stainless steel hardware.
5.
Design certified by AGA.
6.
Controls:
a.
Provide thermostat as specified in this Section.
b.
Provide control transformer suitable for 24-volt or 120-volt control as indicated in
the Heating Unit Schedules.
c.
Single-stage combination gas value.
d.
Provide control transformer suitable for 24-volt control as indicated in the heating
unit schedules.
2.4
B.
Section 23 83 33
Heating Units
2.
3.
4.
5.
6.
7.
Heating element high quality nickel chromium alloy resistance wire embedded and
completely surrounded by magnesium oxide, enclosed and swaged in aluminum sheath.
Heating element locked to support member for quiet operation.
Aluminum fins mechanically locked to sheath.
Automatic reset thermal cutout extending the full length of the element.
3-phase designed for balanced phases.
Power per unit length as indicated in the Heating Unit Schedules.
C.
Features:
1.
Top air exit.
2.
Designed for mounting as indicated in Heating Unit Schedules on wall or at floor level
with 0 clearance at bottom.
3.
Junction boxes at ends with control and power wiring knockouts, factory mounted and
wired, including specified controls:
4.
Wiring diagram affixed to inside of junction box covers.
5.
Enclosure front and air exit grille fabricated from 16-gauge aluminum extrusions designed
to prevent entrance of small objects.
6.
Enclosure accessories, include adjustable aluminum end caps.
7.
Aluminum, natural anodized.
8.
Controls:
9.
Provide thermostat as specified in this Section.
10.
Provide control transformer suitable for 24-volt or 120-volt control as indicated in the
Heating Unit Schedules.
11.
Built in magnetic contactors.
12.
Required mounting brackets.
D.
Finishes:
1.
Fin tube cabinet finish, baked enamel, color selected by ENGINEER from submitted
samples.
2.5
B.
C.
Features:
1.
Heater terminal boxes, provided with overhang to suit particular case and allow duct
heater installation in accordance with manufacturers recommendations.
2.
Heaters and terminal boxes:
a.
Listed by UL for installation with 0 clearance to combustible surfaces.
3.
Terminal box, control cabinet, and element housing to be made of minimum 18 gauge
aluminized steel.
4.
Terminal box coating to be manufacturers standard.
5.
Built in magnetic contactors.
Section 23 83 33
Heating Units
6.
7.
2.6
Controls:
a.
Provide thermostat as specified in this Section.
b.
Provide control transformer suitable for 24-volt or 120-volt control as indicated in
the Heating Unit Schedules.
c.
Controls supplied and built into heater terminal box.
Required mounting brackets.
B.
C.
Coil characteristics:
1.
Entering hot water temperature: 180 degrees Fahrenheit.
2.
Hot water temperature drop: 20 degrees Fahrenheit.
3.
Rated capacity at entering air temperature of 65 degrees Fahrenheit.
4.
Rectangular draw through for horizontal units or 1 row serpentine for vertical units.
5.
Seamless copper tubing suitable for a minimum of 150 pounds per square inch gauge hot
water or 75 pounds per square inch gauge steam service.
6.
Aluminum fins mechanically bonded to tubing.
D.
Features:
1.
Adjustable horizontal and vertical louvers.
2.
Casing fabricated of minimum 20-gauge, rigid steel.
3.
Controls:
a.
Provide thermostat as specified in this Section.
b.
Provide control transformer suitable for 24-volt or 120-volt control as indicated in
the Heating Unit Schedules.
4.
Required mounting brackets.
E.
Finishes:
1.
Casing finish: Backed enamel in manufacturers standard color.
2.7
B.
Coil characteristics:
1.
Entering hot water temperature: 180 degrees Fahrenheit.
2.
Hot water temperature drop: 20 degrees Fahrenheit.
3.
Rated capacity at entering air temperature of 65 degrees Fahrenheit.
4.
Manufactured of single tier, 3/4-inch copper tubes with aluminum fins.
5.
Integral fin collars to space fins.
Section 23 83 33
Heating Units
6.
7.
C.
Features:
1.
Provide positive temperature control with a modulating damper controller to reduce
heating capacity when closed by as much as 70 percent.
2.
Provide balancing and shutoff cock with access panel.
3.
Dampers, factory mounted on element or unit housing.
4.
Cabinet recessed, floor mounted, or wall mounted as scheduled.
a.
Manufacture with 16-gauge, or thicker, steel sheet reinforced with channel
stiffeners.
1)
Front secured in place with quick opening fasteners.
5.
Required mounting brackets.
6.
Outlet grille linear extruded anodized aluminum.
D.
Finishes:
1.
Fin tube cabinet finish, baked enamel, color selected by ENGINEER from submitted
samples.
2.8
B.
Features:
1.
General: Provide make-up air fan and electric heating unit in a packaged unit suitable for
mounting as scheduled with air inlet and outlet oriented as scheduled.
2.
Power supply:
a.
Design unit for power voltage and phases as scheduled.
b.
Provide disconnect switch at unit; mount in NEMA 3R enclosure; when explosion
proof construction is scheduled, provide disconnect suitable for Group D, Class I,
Division 1 location.
c.
Provide built-in magnetic contactors.
3.
Fan type: Aluminum axial flow or centrifugal as required to meet scheduled cfm and
external static pressure (ESP):
a.
Provide fan guards for fan intake if exposed; provide fan power disconnect switch
on unit access door, fan automatically disconnected when door opened.
b.
Dynamically balance.
c.
Fan designed for quiet operation.
d.
Permanently lubricated ball bearings.
e.
Automatic reset thermal overload protection.
f.
When explosion proof scheduled, provide antistatic, nonsparking materials.
g.
Fan shaft designed so that first critical speed is 25 percent above manufacturers
maximum cataloged fan revolutions per minute.
h.
Provide fan vibration isolators between fan and casing.
4.
Heating element characteristics:
a.
Rated capacity at entering air temperature of 65 degrees Fahrenheit.
b.
Fin type, steel-plated heater elements, with elements brazed to common fins,
designed for maximum strength and maximum heat transfer.
c.
3-phase designed for balanced phases.
d.
Over temperature cutout with automatic reset.
5.
Cabinet:
Section 23 83 33
Heating Units
a.
b.
6.
2.9
Type: Wall mounted, heat only with fan AUTO-ON selector switch when fan part of unit and
separate system ON-OFF selector switch.
B.
Dial or lever temperature setpoint adjustment with 45 to 90 degrees Fahrenheit setpoint range.
C.
D.
E.
Bi-metallic contacts suitable for 1- or 2-stage unit heater control as specified for the heater size
or as scheduled. The use of mercury within the thermostat is not acceptable.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine areas to receive unit heaters for compliance with requirements for installation
tolerances and other conditions affecting performance.
B.
Examine roughing-in for electrical connections to verify actual locations before unit heater
installation.
C.
Proceed with installation only after unsatisfactory conditions have been corrected.
Section 23 83 33
Heating Units
3.2
INSTALLATION
A.
3.3
Install wall-mounting thermostats and switch controls in electrical outlet boxes at heights to
match lighting controls. Verify location of thermostats and other exposed control sensors with
Drawings and room details before installation.
CONNECTIONS
A.
B.
Connect wiring according to Division 26 Section "Low Voltage Electrical Power Conductors and
Cables."
3.4
DEMONSTRATION
A.
END OF SECTION
Section 23 83 33
Heating Units
DIVISION 26
ELECTRICAL
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
DESCRIPTION OF WORK
A.
This Section specifies the basic requirements for electrical installations and includes
requirements common to more than one section of Division 26. It expands and supplements the
requirements specified in the General and Supplementary Conditions.
B.
This project consists of construction of the new building structures, associated facilities, and all
related electrical systems as defined in the plans and in these specifications.
C.
The work includes the installation, connection and testing of new electrical equipment, including
electrical services, power distribution equipment, lighting equipment, underground electrical
work, grounding systems, control systems, conduit and wiring, coordination of traffic flow,
temporary power systems, special electrical systems and all appurtenances to construct and
demonstrate proper operation of the completed electrical systems.
D.
The Contractor shall be responsible for the coordination of power, communication, and controls
for the project.
E.
The electrical plans do not give exact locations, etc., and do not show all the offsets, control
lines, pilot lines, and other installation details. Each contractor shall carefully lay out the work at
the sites to conform to the job conditions, to conform to details of installation supplied by the
manufacturers of the equipment to be installed, and thereby to provide complete operating
systems.
F.
The electrical plans show diagrammatically the locations of the various electrical outlets and
apparatus and the general method of circuiting and controlling. Exact locations of these outlets
and apparatus shall be determined by reference to the general plans and to all detail drawings,
etc., by measurements at the buildings, and in cooperation with other crafts, and in all cases
shall be subject to the approval of the Owner and Engineer. The Engineer reserves the right to
make any reasonable change in location of any outlet or apparatus before installation, without
additional cost to the Owner.
G.
These specifications and the accompanying drawings are intended to cover systems which will
not interfere with the structure of the buildings, which will fit into the several available spaces,
and which will ensure complete and satisfactory systems. Each bidder shall be responsible for
the proper fitting of the material and apparatus into the buildings.
H.
Should the particular equipment which any bidder proposes to install require other space
conditions than those indicated on the Drawings, the Bidder shall arrange for such space with
the Engineer before submitting the bid. Should changes become necessary on account of
failure to comply with this clause, the Contractor shall make such changes at the Contractors
expense.
I.
Where wire sizes, conduit and other items of construction are shown or required for a complete
installation, but are not adequately identified as to size or material requirements, the materials
Section 26 05 00
Common Work Results for Electrical
furnished shall be in accordance with Code requirements as though shown in detail on the
Drawings.
J.
1.3
All equipment shall be leveled and made plumb. Metal junction boxes, equipment enclosures
and metal raceways mounted on water or earth-bearing walls shall be separated from walls not
less than 1/4 inch by corrosion-resistant spacers. All electrical conduits and items of equipment
shall be run or set parallel to walls, floors and other items of construction.
STANDARDS
A.
The Contractor shall perform work specified in Division 26 in accordance with standards listed
below. Where these specifications are more stringent, the most stringent standard shall take
precedence. In case of conflict, obtain a decision from the Engineer.
1.
Applicable National Fire Protection Association (NFPA) codes, including but not limited
to:
a.
NFPA 70 National Electrical Code.
b.
NFPA 70E Standard for Electrical Safety in the Workplace.
c.
NFPA 72 - National Fire Alarm Code.
d.
NFPA 101 Life Safety Code.
e.
NFPA 820 Standard for Fire Protection in Wastewater Treatment and Collection
Facilities.
f.
Internet Website: http://www.nfpa.org
2.
Applicable Code of Federal Regulations (CFR) codes, including but not limited to:
a.
29 CFR 1910 Occupational Safety and Health Standards (OSHA).
b.
29 CFR 1926 Safety and Health Regulations for Construction.
c.
Internet Website: http://www.gpo.gov/fdsys
3.
ANSI/IEEE C2 National Electrical Safety Code.
4.
Applicable Federal, State and Local Fire codes.
5.
Applicable Federal, State and Local Energy Codes.
6.
Applicable Federal, State and Local Building Codes.
7.
Applicable City Electrical Code.
8.
Applicable City Ordinances pertaining to electrical work.
9.
Applicable Federal, State and Local Environmental, Health and Safety Laws and
Regulations.
B.
Contractor shall utilize the most current editions of standards, which are current at time of bid
and as recognized by the Authority Having Jurisdiction for the respective standard.
1.4
SUBMITTALS
A.
Submittals shall comply with the General and Special Provisions and with the General and
Supplementary Conditions.
B.
Submittals shall be furnished by the Contractor for the work involved in sufficient time so that no
delay or changes will be caused. Fax copies are not acceptable; only permanent type prints will
be allowed.
C.
Submittals shall consist of manufacturing information, schematics, wiring diagrams, ladder logic
diagrams, instrument loop diagrams, outline drawings, clearances and related information. Shop
Drawings shall be so marked as to indicate the EXACT items offered.
D.
Submittals shall bear Contractors certification that the item complies in all respects with the
item originally specified. It is the Contractors responsibility to procure the proper sizes,
quantities, rearrangements, structural modifications or other modifications in order for the
substituted item to comply with the established requirements.
Section 26 05 00
Common Work Results for Electrical
E.
The Contractor shall securely bind each submittal set in a separate heavy-duty 3-ring, hard
cover binder. Group materials submitted by their Specification numbers, but do not submit the
entire electrical within one submittal. Provide type written index label tabs and a type written
label for the spine of the binder, which indicate the included equipment types.
F.
The Contractor shall submit complete descriptions, illustrations, specification data, etc., of all
materials, fittings, devices, fixtures, special systems, etc., as required by the individual sections
of this Division.
G.
Submittal of shop drawings, product data and samples will be accepted only when submitted by
the Contractor. Data submitted from subcontractors and material suppliers directly to the
Engineer will not be processed.
H.
I.
Shop Drawings: In addition to the above, submit in reproducible form with six prints made by a
process approved by the Engineer, shop drawings for major materials where called for and
when requested by the Engineer.
1.
Lockout/Tagout Program.
2.
Switchboard, motor control centers, panelboards, surge arresters, and safety switches.
3.
Motor starters and contactors including custom wiring diagrams for all motors.
4.
Lighting fixtures and lamps including light pole foundation requirements.
5.
Wire, cable and conduit.
6.
Dry type transformers including weight and dimensions.
7.
Wiring devices and plates.
8.
Site lighting control components including contactors and lighting control center.
9.
Dimensioned layout of electrical room drawn to scale, with equipment location shown
therein. Clearances shall be in accordance with NEC and local codes.
10.
Dimensioned layout of all below grade conduit installations.
11.
Grounding system and layout.
12.
Emergency power system.
13.
Lightning protection system layout.
14.
Traffic control system layout and schematics.
15.
Seismic protection materials and methods for all electrical equipment.
16.
Mounting brackets, supports and assembly for walkway mounted equipment including
instruments, lighting and control panels
1.5
QUALITY ASSURANCE
A.
1.6
Any electrical equipment provided under this Division shall be turned over to the Owner in
operating condition.
Instruction on further operation and maintenance shall be included in the
operating and maintenance instructions.
PRODUCT LISTING
A.
Prepare listing of major electrical equipment and materials for the project.
B.
C.
Section 26 05 00
Common Work Results for Electrical
D.
When two or more items of same material or equipment are required they shall be of the same
manufacturer when available. Product manufacturer uniformity does not apply to raw materials,
bulk materials, wire, conduit, fittings, sheet metal, steel bar stock, welding rods, solder,
fasteners, motors for dissimilar equipment kits, and similar items used in Work, except as
otherwise indicated.
E.
Provide products that are compatible within systems and other connected items.
1.7
NAMEPLATE DATA
A.
1.8
Provide permanent operational data nameplate on each item of power operated equipment,
indicating manufacturer, product name, model number, serial number, capacity, operating and
power characteristics, labels of tested compliances, and similar essential data. Locate
nameplates in an accessible location.
WORK SUPERVISION
A.
The Contractor shall designate in writing the qualified electrical supervisor who shall provide
supervision to all electrical work on this project. The minimum qualifications for the electrical
supervisor shall be a master electrician as defined by the statutes of the State of the work being
performed. The supervisor or his appointed alternate possessing at least a master electrician
license shall be on site whenever electrical work is being performed. The qualifications of the
electrical supervisor shall be subject to approval of the Owner and the Engineer.
B.
All master and journeyman electricians shall be licensed in accordance with the statutes of the
State of the work being performed. No unlicensed electrical workers shall perform work on this
project. Apprentice electricians in a ratio of not more than one apprentice per journeyman
electrician will be allowed if the apprentices are licensed and actively participating in an
apprentice-ship program recognized and approved by the statutes of the State of the work being
performed.
1.9
The Contractor shall install all primary trenching, conduits, and backfilling for the primary service
in accordance with utility requirements and utility specifications in conjunction with these plans
and specifications. Underground primary conduits shall be PVC schedule 40 conduits with
PVC-coated galvanized rigid metal elbows. All primary conduits shall be 48 minimum deep.
All primary conduits shall include concrete encasement for all crossings, including road and
drive crossings, process lines, or other utility crossings. Concrete encasement shall extend ten
feet minimum horizontally on each side of crossing.
B.
The Contractor shall construct concrete pads for all utility pad mount transformers and
switchgear in accordance with utility requirements and these plans and specifications.
C.
The servicing utility will furnish and install all primary pad-mounted transformers, switchgear and
metering. The Contractor shall coordinate metering requirements with the utility.
D.
Primary sectionalizers may be furnished and installed by the utility. The Contractor shall
coordinate the location and installation of the primary sectionalizers with the utility requirements
and these plans and specifications.
E.
The Contractor shall be responsible for coordinating all electrical work with the servicing utility
prior to construction and providing all equipment, connectors, metering boxes and accessories
to make all final connections.
Section 26 05 00
Common Work Results for Electrical
F.
1.10
The local electric utility contact is: Richard Delano, OG&E, (580)220-2644.
SECONDARY SERVICE
A.
B.
The Contractor shall be responsible for coordinating all electrical work with the servicing utility
prior to construction and providing all equipment, connectors, and accessories to make all final
secondary connections.
C.
The Contractor shall provide temporary service conductors and raceway system as may be
required. The Contractor shall then provide and connect permanent service conductors and
raceway system after the permanent installation. The Contractor shall coordinate temporary
service, installation, metering and all other items as required with the servicing utility. The
Contractor shall be responsible for paying all temporary electric monthly metering charges.
D.
Underground service entrance electrical ducts shall be concrete encased at a depth to provide
30 inches minimum cover over the top of the underground electrical duct, regardless of the soil
conditions or substances encountered. Concrete encasement for service entrance electrical
ducts shall be red in color.
1.11
A.
1.12
TELEPHONE WORK
The Contractor shall be responsible for coordinating all telephone work with the servicing utility,
Owner and Engineer.
LOCKOUT / TAGOUT PROGRAM
A.
The Contractor shall provide a complete copy of and electrical energy source Lockout/Tagout
Program to the Owner, with copy to the Engineer. The document shall clearly identify the on-site
master electricians and their contact information, including office and mobile telephone
numbers.
B.
The Lockout/Tagout Program shall comply with Part 1910 - Occupational Safety and Health
Standards (OSHA) Subpart S Electrical, and meet the requirements of 29 CFR 1910.147, The
Control of Hazardous Energy (Lockout/Tagout), including requirements listed in 1910.331
through 1910.335.
C.
Implementation of the Lockout/Tagout Program and all other related safety requirements are the
sole responsibility of the Contractor.
1.13
SAFETY PROGRAM
A.
The Contractor shall implement an electrical safety program that complies with NFPA 70E and
29 CFR 1926.
B.
Implementation of the Electrical Safety Program, determining and providing proper Personal
Protective Equipment (PPE), training and enforcing personnel to wear the prescribed PPE,
conducting work area safety inspections (including correcting deficiencies), and all other related
safety requirements are the sole responsibility of the Contractor.
1.14
A.
EQUIPMENT CONNECTIONS
General: Provide connections for all equipment installed or modified by this contract, regardless
of who furnished the equipment.
Section 26 05 00
Common Work Results for Electrical
B.
Provide all disconnect switches required by Code whether or not shown on the plans.
C.
1.15
A.
1.16
GENERAL CONDITIONS
The work under this heading is subject to the General and Supplementary Conditions, special
conditions for mechanical and electrical work, and the Contractor or subcontractor will be
responsible for and be governed by all requirements thereunder as though specifically repeated
herein.
COORDINATION
A.
The Contractor shall coordinate arrangement, mounting and support of all electrical equipment:
1.
To allow maximum possible headroom unless specific mounting heights are indicated.
2.
To provide for ease of disconnecting the equipment with minimum interference to other
installations.
3.
To allow right of way for piping and conduit installed at a required slope.
4.
So connecting raceways, cables and wireways will be clear of obstructions and of the
working and access space of other equipment.
B.
1.17
A.
1.18
SPECIAL NOTE
The mechanical, structural and process plans and specifications, including the general
conditions and all supplements issued thereto, information to bidders, and other pertinent
documents issued by the Engineer, are a part of these specifications and the accompanying
electrical plans, and shall be complied with in every respect. All the above is included herewith,
and shall be examined by all bidders. Failure to comply shall not relieve the Contractor of
responsibility or be used as a basis for additional compensation due to omission of mechanical,
process and structural details from the electrical drawings.
CONTINUATION OF SERVICES
A.
The Contractor shall install any temporary lines and connections required to maintain electric
services and safely remove and dispose of them when complete. The Contractor shall supply
emergency power whenever any existing electrical service is without power for a period of more
than three (3) hours due to his work. In general, the existing facility shall remain operational
during construction.
B.
Planned outages shall be coordinated two weeks in advance with duration and time of start
approved by the Owner. Changeover work which may be required after normal hours or
weekends shall not constitute the basis for additional cost to the Owner. When an outage
begins, the Contractor shall proceed directly to completion of the work without unscheduled
interruptions or delays due to lack of manpower, equipment or tools.
C.
The Contractor shall refer to the sequence of construction and shall provide temporary
connections as may be required to complete each phase of construction as may be required.
The Contractor shall submit proposed electrical service plans for each phase of construction to
the Owner and Engineer for consideration.
Section 26 05 00
Common Work Results for Electrical
1.19
A.
1.20
LAYOUT
The Contractor shall coordinate and establish all bench marks and control lines. The Contractor
shall lay out all work. The lay out shall be reviewed by the Engineer and Owner prior to starting
any work.
RELATED WORK SPECIFIED ELSEWHERE
A.
Mechanical Equipment: The Contractor shall rough-in for and make final electrical connections
to all motor, panels, fixtures, and equipment furnished under other sections
of the
specifications, providing all material and equipment required for such final connections, except
hereinbefore described. This includes, but is not limited to, control panels and other
miscellaneous equipment.
B.
The Contractor shall refer to other sections of these specifications for all information relating to
the requirements of all electrical connections to the equipment and shall furnish and install
electrical items required for a complete installation, ready for operation.
C.
D.
Verify final locations for rough-ins with field measurements and with the requirements of the
actual equipment to be connected.
E.
1.21
A.
1.22
A.
1.23
A.
LOCAL CONDITIONS
Inspection of Sites: The bidder shall inspect the site, thoroughly acquaint himself with conditions
to be met and work to be accomplished. Failure to comply with this shall not constitute grounds
for any additional payments.
RECORD DOCUMENTS
Refer to the General and Supplementary Conditions for requirements. The following paragraphs
supplement the requirements of the General and Supplementary Conditions:
1.
Mark Drawings to indicate revisions to conduit size and location both exterior and interior;
actual equipment locations, dimensioned for column lines; concealed equipment,
dimensioned to column lines; distribution and branch electrical circuitry; fuse and circuit
breaker size and arrangements; support and hanger details; Change Orders; concealed
control system devices.
2.
The Contractor shall locate all underground and concealed work, identifying all
equipment, conduit, circuit numbers, motors, feeders, breakers, switches, and starters.
The Contractor will certify accuracy by endorsement. Record drawings shall be correct in
every detail, such that the Owner can properly operate, maintain, and repair exposed and
concealed work.
3.
The Contractor shall store the Record drawings on the site. Drawings shall not be rolled.
Make corrections, additions, etc., with pencil, with date and authorization of change.
4.
Mark specifications to indicate approved substitutions; Change Orders; actual equipment
and materials used.
OPERATION AND MAINTENANCE DATA
Refer to the General and Supplementary Conditions for procedures and requirements for
preparation and submittal of maintenance manuals.
Section 26 05 00
Common Work Results for Electrical
B.
In addition to the information required by the General and Supplementary Conditions, include
the following information:
1.
Installation manual: Description of function, installation and calibration manuals, normal
operating characteristics and limitations, performance curves, engineering data and tests,
and complete nomenclature and commercial numbers of all replaceable parts.
2.
Operations manual: Manufacturers printed operating instructions and procedures to
include start-up, break-in, routine and normal operating instructions; regulation, control,
stopping, shutdown, and emergency instructions; summer and winter operating
instructions; and all programming and equipment settings.
3.
Maintenance manual: Maintenance procedures for routine preventative maintenance and
troubleshooting; disassembly, repair, and reassembly; aligning and adjusting instructions.
4.
Service manual: Servicing instructions and lubrication charts and schedules, including the
names and telephone numbers of personnel to contact for both routine periodic and
warranty service for equipment and materials provided under this Division.
5.
Final approved equipment shop drawings, clearly labeled.
6.
Final test reports, clearly labeled, including motor certification tests.
7.
Final certified calibration sheets for all equipment and instruments.
C.
After approval of the O & M Manuals, the Contractor shall provide three (3) complete electronic
copies of all documentation in Adobe PDF file format using a storage media device of the
Owner and Engineers choosing, along with 6 hard copies.
1.24
GUARANTEE
A.
The Contractor shall guarantee the work and materials for a period of one (1) year from the date
of completion. If there are failures due to faulty material or workmanship, the Contractor shall
correct the failure at no cost to the Owner.
B.
Refer to the General and Supplementary Conditions for procedures and submittal requirements
for warranties. Refer to individual equipment specifications for warranty requirements.
1.
Compile and assemble the warranties specified in Division 26, into a separate set of vinyl
covered, three ring binders, tabulated and indexed for easy reference.
C.
Provide complete warranty information for each item to include product or equipment to include
date of beginning of warranty or bond; duration of warranty or bond; and names, addresses,
and telephone numbers and procedures for filing a claim and obtaining warranty services.
D.
Upon completion of the installation, the Contractor shall adjust the systems to the satisfaction of
the Engineer.
E.
This guarantee shall include the capacity and integrated performance of the component parts of
the various systems in accordance with the intent of the specifications. The Contractor shall
conduct complete tests required by the Engineer to demonstrate the ability of the various
systems.
1.25
CLEANING
A.
Refer to the General and Supplementary Conditions for general requirements for final cleaning.
B.
Clean all light fixtures, lamps and lenses prior to final acceptance. Replace all inoperative
lamps.
C.
The electrical system shall be thoroughly cleaned inside and outside, of all enclosures to
remove all debris, dust, concrete splatter, plaster paint and lint.
Section 26 05 00
Common Work Results for Electrical
PART 2 - PRODUCTS
2.1
2.2
All materials and equipment used in carrying out these specifications shall be new and have UL
listing, or listing by other recognized testing laboratory when such listings are available.
Specifications and drawings indicate name, type, or catalog numbers of materials and
equipment to be used as standards.
HEAT TRACING
A.
Heat trace and insulate all exposed piping, water lines, and valves less than 8 diameter and all
equipment where water may collect as may be indicated in the Drawings.
B.
Furnish and install self-regulating heat tracing with overall metallic braid, rated 120 Volts AC, 3
watts per foot, Chromalox SRL3-1-C or equal. Contractor shall meet all National Electrical code
requirements for heat tracing and particularly to Resistance Heating Elements Article 427-21, 22
and 23.
C.
Securely fasten heat tracing to pipe with tie wraps spaced to less than 12 apart on centers.
D.
Furnish and install heat tracing controller and connection box with solid state thermostat,
Chromalox DL Series, Model RTSS-1A or equal.
E.
Apply fiberglass or phenolic foam insulation to all heat-traced pipe and secure with 0.016
aluminum jacket and bands. Apply two (2) inches minimum thickness to lines larger than 1/2
and one (1) inch minimum thickness to lines 1/2 and smaller.
PART 3 - EXECUTION
3.1
SALVAGE
A.
3.2
All salvage and equipment removed by the work shall remain the property of the Owner unless
directed otherwise by the Owner. Material removed from the project shall be stored on the
project site where and as directed. Debris shall be removed from the job site and disposed of by
the Contractor.
DELIVERY, STORAGE, AND HANDLING
A.
Deliver equipment to project properly identified with names, model numbers, types, grades,
compliance labels, and similar information needed for distinct identifications; adequately
packaged and protected to prevent damage during shipment, storage, and handling.
B.
Store equipment and materials at the site, unless off-site storage is authorized in writing. Protect
stored equipment and materials from damage.
C.
D.
All equipment, including but not limited to equipment containing coils and/or electronics, shall be
stored in a clean, dry, ventilated and heated building. The storage area shall be free from
condensation or other injurious environmental conditions. Freedom from condensation shall be
essential and shall be accomplished by the use of auxiliary heaters as required to raise the
temperature to 5-degree C above the ambient temperature. The equipment shall be protected
from excessive dust.
be
stored
in
accordance
with
the
manufacturers
Section 26 05 00
Common Work Results for Electrical
E.
In addition, certain electronic equipment that requires cooling based upon its specific storage
temperature range shall be stored in an air-conditioned building.
F.
All motors shall be stored in a clean, dry, ventilated and heated building. The storage area shall
be free from condensation or other injurious environmental conditions. Freedom from
condensation shall be essential and shall be accomplished by the use of auxiliary heaters as
required to raise the temperature to 5 degree C above the ambient temperature. The motors
shall be protected from excessive dust.
G.
Cables and wiring shall be kept in a dry location out of the sun.
H.
I.
3.3
INSTALLATION
A.
Coordinate electrical equipment and materials installation with other building components.
B.
C.
Arrange for chases, slots, and openings in other building components to allow for electrical
installations.
D.
The Contractor shall keep ends of conduits, including those extending through roofs, equipment
and fixtures covered or closed with caps or plugs to prevent foreign material from entering
during construction.
E.
Coordinate the installation of required supporting devices and sleeves to be set in concrete and
other structural components as they are constructed.
F.
Sequence, coordinate, and integrate installations of electrical materials and equipment for
maintaining the required operation of the facility. Give particular attention to large equipment
requiring positioning prior to closing-in the building.
G.
Coordinate the cutting and patching of building components to accommodate the installation of
electrical equipment and materials.
H.
Where mounting heights are not detailed or dimensioned, install electrical services and
overhead equipment to provide the maximum headroom possible.
I.
J.
Coordinate the installation of electrical materials and equipment above ceilings with suspension
system, mechanical equipment and systems, and structural components.
K.
Coordinate connection of electrical systems with exterior underground and overhead utilities
and services. Comply with requirements of governing regulations, franchised service
companies, and controlling agencies. Provide required connection for each service.
L.
10
Section 26 05 00
Common Work Results for Electrical
3.4
All materials shall be new, and shall be of the latest standard design of a manufacturer regularly
engaged in the manufacture of that type of equipment. Materials shall be in good condition and
shall be free from dents, scratches or other damage incurred in shipment or installation.
B.
All equipment shall comply with the National Electrical Code, Underwriters Laboratories or other
appropriate agency.
C.
Installation shall be made in a neat and workmanlike manner, and all materials shall be installed
in accordance with the recommendations of the various manufacturers. The installation shall be
subject to the approval of the Owner and Engineer.
D.
3.5
COORDINATION
A.
Carefully examine specification and drawings to be thoroughly familiar with items which require
electrical connections and coordination. (Electrical drawings are diagrammatic and shall not be
scaled for exact sizes.)
B.
Notify other tradesmen of any deviations or special conditions necessary for the installation of
work. Interference between work of various contractors shall be resolved prior to installation.
Work installed not in compliance with specifications and drawings and without properly checking
and coordinating as specified above shall, if necessary, be removed and properly reinstalled
without additional cost to the Owner. Engineer to be mediating authority in all disputes arising
on project.
C.
3.6
Repair or replace routine damage caused by cutting in performance of work under this Division.
B.
Correct unnecessary damage caused due to installation of electrical work, brought about
through carelessness or lack of coordination.
C.
Holes cut through floor slabs to be sleeved or core drilled with drill designed for this purpose. All
openings, sleeves, and holes in slabs to be properly sealed, fire proofed and water proofed.
D.
Repairs to be performed with materials which match existing materials and to be installed in
accordance with appropriate sections of these specifications.
E.
All cutting and patching work shall be coordinated in advance with the Engineer and Owner
prior to any work.
3.7
Provide trenching, excavation, and backfilling necessary for performance of work under this
Division.
11
Section 26 05 00
Common Work Results for Electrical
3.8
Foundations and pads required for equipment shall be provided as indicated. Proper size and
location of foundations, pads and anchor bolts shall be determined under this Division.
B.
Provide anchors and bases for electrical equipment to withstand lateral forces and
accommodate displacements.
3.9
3.10
The electrical system as installed shall be free of objectionable noise or vibration. The
Contractor shall isolate motors, starters, transformers, equipment, ballasts, etc., as directed or
required as to ensure acceptable noise level free from objectionable vibration in all systems.
TESTS
A.
On completion of work, installation shall be completely operational and entirely free from
ground, short circuits, and open circuits. Perform a thorough operational test in presence of the
Owner and Engineer. Furnish all labor, materials and instruments for above tests.
B.
Furnish the Engineer, as part of closing file, a copy of such tests including identification of each
circuit and readings recorded. Test information to be furnished to the Engineer includes ampere
readings of all panels and major circuit breakers, isolation resistance reading of motors and
transformers.
C.
Prior to final observation and acceptance test, all electrical systems and equipment shall be in
satisfactory operating condition. Including, but not limited to the following:
1.
Electrical power and distribution system.
2.
Lighting systems.
3.
Transformers.
4.
Electric motors for all equipment.
5.
Telecommunication system.
6.
Emergency power system.
7.
Special electrical systems and CCTV.
D.
After installation of the electrical system and before operating equipment, functional checking
shall be conducted in accordance with the manufacturers recommendations, with the contract
drawings and as follows:
1.
Functional checking shall include inspection, testing and repair, replacement or
adjustments as necessary to ensure compliance with the requirements of the
specifications. Tests and inspections shall be recorded on appropriate yellow lined
contract and shop drawings, standard test forms and checklists to indicate that wiring and
controls are in place in accordance with requirements and to form the basis of record
drawings.
2.
The functional test procedures shall be signed and dated by the Contractor and
presented to the Owners construction observation personnel prior to operating any
equipment.
a.
Visual Inspection The electrical system shall be examined as outlined below:
1). Parts of components missing
2). Improper assembly
3). Parts or components not functioning properly
4). Finish not as specified
5). Materials not as specified
6). Connections not tight
7). Mounting and supports loose or unsatisfactory
12
Section 26 05 00
Common Work Results for Electrical
b.
c.
d.
3.11
A.
3.12
A.
3.13
A.
Provide a temporary electrical lighting and power distribution system of adequate size to
properly serve the following requirements, including adequate feeder sizes to prevent excessive
voltage drop. Temporary work to be installed in a neat and safe manner in accordance with the
National Electrical Code, Article 590, and as required by OSHA or applicable local safety codes.
B.
Provide one pigtail socket with 150-watt lamp for every 1,000 square feet of floor area, evenly
distributed throughout the building and with minimum of one pigtail socket per room.
13
Section 26 05 00
Common Work Results for Electrical
C.
Provide a minimum of one duplex power outlet for every 1,500 square feet of floor area, evenly
distributed throughout the building. Power outlets shall be 20 amp, single phase located as
directed by the General Contractor.
D.
Coordinate prior to installation to determine if any lighting or power outlets over the minimum
quantity noted above are required.
E.
Provide service and panelboards required for above lighting and power outlets.
F.
G.
END OF SECTION
14
Section 26 05 00
Common Work Results for Electrical
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract including General and Supplementary
conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
B.
C.
D.
E.
1.4
SUBMITTALS
A.
B.
Shop Drawings: List of legends and description of materials and process used for pre-marking
wall plates.
C.
Samples: One for each type of device and wall plate specified in each color specified.
D.
E.
Operation and Maintenance Data: For wiring devices to include in all manufacturers packing
label warnings and instruction manuals that include labeling conditions.
1.5
QUALITY ASSURANCE
A.
Source Limitations: Obtain each type of wiring device and associated wall plate through one
source from a single manufacturer. Insofar as type are available, obtain all wiring devices and
associated wall plates from a single manufacturer and one source.
B.
Electrical Components, Devices and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction and marked for
intended use.
C.
Section 26 05 14
Wiring Devices
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
Available Manufacturers:
1.
Cooper wiring Devices; a division of Cooper Industries, Inc. (Cooper).
2.
Hubbell Incorporated; Wiring Device-Kellems (Hubbell).
3.
Leviton Mfg. Company Inc. (Leviton).
4.
Pass & Seymour/Legrand; Wiring Devices & Accessories (Pass & Seymour).
STRAIGHT BLADE RECEPTACLES
A.
2.3
Convenience Receptacles, 125 V, 20A: Comply with NEMA WD1, NEMA WD 6 configuration 520R, and UL 498.
1.
Available Products: Subject to compliance with requirements, products that may be
incorporated into the work include, but are not limited to the following:
a.
Cooper; 5351 (single), 5352 (duplex).
b.
Hubbell; HBL5351 (single), CR5352 (duplex).
c.
Leviton; 5891 (single), 5352 (duplex).
d.
Pass & Seymour; 5381 (single), 5352 (duplex).
GFCI RECEPTACLES
A.
General Description: Straight blade, feed-through type. Comply with NEMA WD1, NEMA WD6,
UL498 and UL 943, Class A and include indicator light that is lighted when device is tripped.
B.
2.4
MOTION DETECTORS
A.
2.5
A.
B.
Switches, 120/277 V, 20 A:
1.
Available Products: Subject to compliance with requirements, products that may be
incorporated into the work include, but are not limited to the following:
a.
Cooper; 2221 (single pole), 2222 (two pole), 2223 (three way), 2224 (four way).
b.
Hubbell; CSI221 (single pole), CSI222 (two pole), CSI223 (three way), CSI224
(four way).
c.
Leviton; 1221-2 (single pole), 1222-2 (two pole), 1223-2 (three way), 12224-2 (four
way).
d.
Pass & Seymour; 20ACI (single pole), 20AC2 (two pole); 20AC3 (three way),
20AC4 (four way).
Section 26 05 14
Wiring Devices
C.
2.6
A.
2.7
A.
Color:
1.
Wiring Devices: As selected by Owner, unless otherwise indicated or required by NFPA
70 or device listing.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Comply with NECA 1, including the mounting heights listed in that standard, unless otherwise
noted.
B.
C.
Conductors:
1.
Do not strip insulation from conductors until just before they are spliced or terminated on
devices.
2.
Strip insulation evenly around the conductor using tools designed for the purpose. Avoid
scoring or nicking of solid wire or cutting strands from stranded wire.
3.
The length of free conductors at outlets for devices shall meet provisions of NFPA 70,
Article 300, without pigtails.
4.
Existing conductors:
a.
Cut back and pigtail or replace all damaged conductors.
b.
Straighten conductors that remain and remove corrosion and foreign matter.
c.
Pigtailing existing conductors is permitted provided the outlet box is large enough.
D.
Device Installation:
1.
Replace all devices that have been in temporary use during construction or that show
signs that they were installed before building finishing operations were complete.
Section 26 05 14
Wiring Devices
2.
3.
4.
5.
6.
7.
8.
9.
Keep each wiring device in its package or otherwise protected until it is time to connect
conductors.
Do not remove surface protection such as plastic film and smudge covers until the last
possible moment.
Connect devices to branch circuits using pigtails that are not less than 6 inches (152 mm)
in length.
When there is a choice, use side wiring with binding-head screw terminals. Wrap solid
conductor tightly clockwise, 2/3 to 3/4 of the way around terminal screw.
Use a torque screwdriver when a torque is recommended or required by the
manufacturer.
When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice No.
12 AWG pigtails for device connections.
Tighten unused terminal screws on the device.
When mounting into metal boxes, remove the fiber or plastic washers used to hold device
mounting screws in yokes, allowing metal-to-metal contact.
E.
Receptacle Orientation:
1.
Install ground pin of vertically mounted receptacles up, and on horizontally mounted
receptacles to the right.
F.
Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount
outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.
3.2
IDENTIFICATION
A.
3.3
A.
B.
C.
Test straight blade for the retention force of the grounding blade according to NFPA 99.
Retention force shall be not less than 4 oz. (115g).
END OF SECTION
Section 26 05 14
Wiring Devices
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
This section describes materials, installation and testing of induction motors and applies to
motors which are generally provided as part of equipment specified in other sections. The
Contractor shall provide motors, accessories and appurtenances complete and operable in
accordance with the individual driven equipment specifications.
SUBMITTALS
A.
B.
1.4
QUALITY ASSURANCE
A.
Provide routine (short commercial) test data complying with NEMA MG 1-12.51 and MG 123.46.
B.
Test thermally protected motors in accordance with NEMA MG 1 winding temperature and trip
current tests.
C.
Section 26 05 15
Electric Motors
D.
1.5
Motors for applications in hazardous locations shall bear the UL label listing its use in
accordance with the NEC.
COORDINATION
A.
Furnish reviewed shop drawings from motor controller manufacturer for coordination and sizing
of the controller.
B.
Coordinate supplied motor connection box with conduits sizes indicated in the drawings.
C.
Coordinate motor leads and lugs with wire sizes indicated in the drawings.
PART 2 - PRODUCTS
2.1
B.
C.
The maximum motor loading of each motor shall not exceed its nameplate horsepower rating
(exclusive of service factor) under any operating condition.
D.
Motors shall be sized to start and accelerate the design loading and operate the full range of
driven equipment without exceeding any of the specified design requirements. Motors that fail to
meet these requirements shall be replaced at no additional cost to the Owner.
E.
All three phase motors shall be provided with Class F insulation, rated to operate at a maximum
ambient temperature of 40 degrees C and at the altitudes where the motors will be installed and
operated without exceeding Class B temperature rise limits stated in ANSI/NEMA MG1-12, 42.
Single phase motors shall have Class F insulation with temperature rise not to exceed the
insulation class. Motors to be operated with variable frequency drives shall be provided with
insulation systems to withstand 1600 volt spikes, with dV/dt as defined in NEMA MG 1-31.
F.
G.
Motors for use in hazardous locations shall have enclosures suitable for the classification of the
location. Such motors shall be UL listed and stamped.
H.
Motors larger than 50 HP located outdoors or in non-conditioned areas shall have 120-volt AC
space heaters and temperature sensors.
I.
For motors controlled by variable frequency drives, the critical vibration speed of the motor/load
combination shall either not fall within the operating range of the drive or such frequencies shall
be blocked with the drive critical speed avoidance circuit. All motors connected to variable
frequency drives shall be inverter duty rated.
J.
Unless otherwise specified, motors shall have no-load sound power levels not to exceed the
values specified in NEMA MG 1-12.53.3.
Section 26 05 15
Electric Motors
K.
2.2
A.
All motors greater than 2 horsepower shall have bearings designed for 17,500 hours (belted) or
100,000 hours (coupled) L-10 life.
B.
Motors less than 2 horsepower shall be provided with sealed, permanently lubricated ball
bearings.
C.
Horizontal motors over 2 horsepower shall be shielded open-type bearing installed with
labyrinth sealed end bells with pipe plugs. Bearings shall be regreasable and have provisions
for purging old grease.
D.
Vertical motors over 2 horsepower shall be provided with relubricatable ball, spherical, roller or
plate type trust bearings. Lubrication shall be per manufacturers recommendation for smooth
operation and long life of the bearing. Drains shall be provided to prevent over lubrication.
2.3
All single phase motors shall have integral thermal overload protection or shall be current
limited.
B.
Winding thermostats shall be provided in accordance with NEMA MG-1. Thermostats shall be
snap action, bi-metallic, temperature actuated type switches and shall be provided with a
normally closed contact. Thermostats shall be precalibrated by the manufacturer and shall be
series connected.
2.4
ACCESSORIES
A.
All vertical motors and horizontal motors 3 horsepower and larger shall have split-type conduit
boxes with a gasketed moisture seal between the conduit box and motor frame. Motors less
than 3 horsepower shall have the manufacturers standard conduit boxes. Motors other than
open drip-proof shall be gasketed.
B.
All motors weighing 250 pounds or greater shall have suitable lifting eyes for installation and
removal.
C.
Motor grounding lugs shall be provided and shall be suitable for terminating ground wires.
D.
All motors shall be fitted with permanent stainless steel nameplates indelibly stamped or
engraved with NEMA Standard motor data.
E.
Refer to equipment specifications for special requirements such as space heaters or motor
winding thermal protection.
Section 26 05 15
Electric Motors
PART 3 - EXECUTION
3.1
STORAGE
A.
Protect motors from exposure to elements for which they are not designed. Install and energize
temporary electrical service to motors with electrical heaters.
B.
3.2
INSTALLATION
A.
Motor installation shall be performed in accordance with the motor manufacturers written
recommendations and the written requirements of the manufacturer of the driven equipment.
B.
Connections, switches, controls, disconnects and other items shall be provided in accordance
with the plans and specifications for each motor.
C.
The Contractor shall coordinate conduit sizes indicated in the drawings with the supplied motor
connection box. The Contractor shall be responsible for providing larger connection boxes as
may be required.
3.3
FIELD TESTING
A.
Perform insulation resistance tests in accordance with NEMA MG-1. Test voltage shall be 1000
VAC plus twice the rated voltage of motor.
B.
Inspect the physical and mechanical conditions of each motor installation including any
deviations from the nameplate, drawings, specifications and manufacturers written guidelines.
Verify expected rated voltage, phase and frequency for each motor installation. Confirm the
presence of and correct application of lubrications for each motor along with proper securing
and torque settings for bolted installations of each motor.
C.
Check for proper phase and ground connections for each motor are connected. For multivoltage motors, verify that motors are connected properly for the supplied voltage.
D.
E.
Test the motor for proper rotation prior to connection to the driven equipment. Measure and
record running current and evaluate the current relative to the load conditions and nameplate
full-load amps.
F.
Simulate operating conditions for each motor to demonstrate proper operation of interlocks and
control features.
G.
Record operating current in each phase for each motor horsepower and larger. Motors
exceeding motor nameplates values shall be repaired or replaced.
H.
For motors 50 horsepower and larger or when a discernible abnormal vibration is detectible, a
vibration test shall be completed. Vibration shall not exceed 0.25 in./sec. For horizontal motors,
the N-S and E-W vibrations shall be measured at the top and bottom of the front and rear
bearing housing. For vertical motors, the N-S and E-W vibrations shall be measured at the
upper and lower bearing housing.
I.
Section 26 05 15
Electric Motors
1.
2.
3.
3.4
Motor and Motor Protection Tests for motors In addition to other testing start and stop
each motor a minimum of 3 times and perform a run test for vibration, heat, and to
document motor protection. The Contractor shall document the settings of the motor
overcurrent protection, overload relay and similar data on the provided form MOTOR
TEST REPORT.
The Contractor shall develop non-conforming material reports for each failure and repair
or report failures.
The Contractor shall replace defective parts, correct malfunctioning units, make all
repairs and retest to demonstrate compliance. The Contractor shall document action
taken on appropriate non-conforming material report.
The following form is provided for the motor certification specified herein. Master blank forms
are available on request.
END OF SECTION
Section 26 05 15
Electric Motors
2.
Overcurrent Protection:
3.
Overload Protection:
4.
5.
6.
Megger motor from wire in motor control center or control panel and record results:
A-B_______
B-C_______
C-A_______
A-G________
B-G________
C-G________
7.
Ic______
8.
Comments:
Signature Required:
Company:
Date:
Section 26 05 15
Electric Motors
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
B.
1.3
DEFINITIONS
A.
B.
1.4
SUBMITTALS
A.
B.
A.
1.5
QUALITY ASSURANCE
A.
Testing Agency Qualifications: An independent agency, with the experience and capability to
conduct the testing indicated, that is a member company of the InterNational Electrical Testing
Association (NETA) or is a nationally recognized testing laboratory (NRTL) as defined by OSHA
in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.
1.
Testing Agency's Field Supervisor: Person currently certified by the InterNational
Electrical Testing Association or the National Institute for Certification in Engineering
Technologies to supervise on-site testing specified in Part 3.
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C.
1.6
COORDINATION
A.
Set sleeves in cast-in-place concrete, masonry walls, and other structural components as they
are constructed.
Section 26 05 19
Low Voltage Electrical Power Conductors & Cables
PART 2 - PRODUCTS
2.1
B.
C.
Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN, XHHW and RHHRHW-USE.
2.2
B.
Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type,
and class for application and service indicated.
PART 3 - EXECUTION
3.1
Feeders: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
B.
Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and
larger.
3.2
B.
C.
D.
Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type RHH-RHWUSE single conductors in raceway.
E.
Feeders in Cable Tray: Type RHH-RHW-USE, single conductors in raceway for larger than 4/0
AWG; Otherwise Type TC tray cable.
Type RHH-RHW-USE,
Section 26 05 19
Low Voltage Electrical Power Conductors & Cables
F.
G.
H.
I.
Variable Frequency Drive Branch Circuits: Shielded cable, size adjusted for published ampacity
of cable.
J.
Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainlesssteel, wire-mesh, strain relief device at terminations to suit application.
K.
L.
3.3
below
Slabs-on-Grade,
and
Underground:
Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.
B.
C.
Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will
not damage cables or raceway.
D.
Install exposed cables parallel and perpendicular to surfaces of exposed structural members,
and follow surface contours where possible.
E.
Support cables according to Division 26 Section "Hangers and Supports for Electrical Systems."
F.
Identify and color-code conductors and cables according to Division 26 Section "Identification
for Electrical Systems."
3.4
CONNECTIONS
A.
Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in
UL 486A and UL 486B.
B.
Make splices and taps that are compatible with conductor material and that possess equivalent
or better mechanical strength and insulation ratings than unspliced conductors.
C.
Wiring at Outlets: Install conductor at each outlet, with at least 6 inches of slack.
D.
Cable splicing, in general, will not be allowed. Where applicable, all wiring connections to be
made using terminal block type connections. Wire nut use will permitted only where allowed by
the Owner and Engineer.
Section 26 05 19
Low Voltage Electrical Power Conductors & Cables
3.5
B.
C.
D.
END OF SECTION
Section 26 05 19
Low Voltage Electrical Power Conductors & Cables
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
This Section includes methods and materials for grounding systems and equipment.
1.
Underground distribution grounding.
2.
Common ground bonding with lightning protection system.
SUBMITTALS
A.
B.
C.
D.
Operation and Maintenance Data: For grounding to include the following in emergency,
operation and maintenance manuals.
1.
Instructions for periodic testing and inspection of grounding features at test wells ground
rings grounding connections for separately derived systems based on ANSI/NETA MTS.
a.
Test shall be to determine if ground resistance or impedance values remain within
specified maximums and instructions shall recommend corrective action if they do
not.
b.
Include recommended testing intervals.
1.4
QUALITY ASSURANCE
A.
Electrical Components, Devices and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction and marked for
intended use.
B.
Comply with UL 467 for grounding and bonding materials and equipment.
PART 2 - PRODUCTS
2.1
CONDUCTORS
A.
Insulated Conductors: Copper or tinned-copper wire or cable insulated for 600 V unless
otherwise required by applicable Code or authorities having jurisdiction.
B.
Section 26 05 26
Grounding and Bonding for Electrical Systems
3.
4.
2.2
CONNECTORS
A.
Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having
jurisdiction for applications in which used, and for specific types, and combinations of
conductors and other items connected.
B.
Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type, with
at least two bolts.
1.
Pipe connectors: Clamp type, sized for pipe.
C.
2.3
GROUNDING ELECTRODES
A.
PART 3 - EXECUTION
3.1
APPLICATIONS
A.
Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No.
6 AWG and larger, unless otherwise indicated.
B.
Underground Grounding Conductors: Install bare tinned-copper conductor, No. 4/0 AWG
minimum.
1.
Bury at least 30 inches below grade.
C.
3.2
B.
Grounding Manholes and Handholes: Install a driven ground rod through manhole or handhole
floor, close to wall, and set rod depth so 4 inches will extend above finished floor. If necessary,
install ground rod before manhole is placed and provide No. 1/0 AWG bare, tinned-copper
conductor from ground rod into manhole through a waterproof sleeve in manhole wall. Protect
ground rods passing through concrete floor with a double wrapping of pressure-sensitive
insulating tape or heat-shrunk insulating sleeve from 2 inches above to 6 inches below
concrete. Seal floor opening with waterproof, nonshrink grout.
C.
Section 26 05 26
Grounding and Bonding for Electrical Systems
corners and fasten to manhole walls. Connect to cable armor and cable shields as
recommended by manufacturer of splicing and termination kits.
D.
Pad-Mounted Utility Transformers: Install four ground rods and ground ring around the pad.
Ground pad-mounted equipment and noncurrent-carrying metal items associated with utility
transformers by connecting them to underground cable and grounding electrodes. Install tinnedcopper conductor not less than No. 4/0 AWG for ground ring and for taps to equipment
grounding terminals. Bury ground ring not less than 6 inches from the foundation. Comply with
Conway Corporation requirements.
E.
Pad-Mounted Utility Switchgear: Install four ground rods and ground ring around the pad.
Ground pad-mounted equipment and noncurrent-carrying metal items associated with utility
switchgear by connecting them to underground cable and grounding electrodes. Install tinnedcopper conductor not less than No. 4/0 AWG for ground ring and for taps to equipment
grounding terminals. Bury ground ring not less than 6 inches from the foundation.
F.
Pad-Mounted Generator: Install a minimum of four ground rods and ground ring around the
pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with pad
mounted generator by connecting them to underground cable and grounding electrodes. Install
tinned-copper conductor not less than No. 4/0 AWG for ground ring and for taps to equipment
grounding terminals. Bury ground ring not less than 6 inches from the foundation.
3.3
EQUIPMENT GROUNDING
A.
Install insulated equipment grounding conductors with all feeders and branch circuits.
B.
Install insulated equipment grounding conductors with the following items, in addition to those
required by NFPA 70:
1.
Feeders and branch circuits.
2.
Lighting circuits.
3.
Receptacle circuits.
4.
Single-phase motor and appliance branch circuits.
5.
Three-phase motor and appliance branch circuits.
6.
Flexible raceway runs.
C.
D.
Water Heater, Heat-Tracing and Antifrost Heating Cables: Install a separate insulated
equipment grounding conductor to each electric water heater and heat-tracing cable. Bond
conductor to heater units, piping, connected equipment and components.
E.
Metal Poles Supporting Outdoor Lighting fixtures: Install grounding electrode and a separate
insulated equipment grounding conductor in addition to grounding conductor installed with
branch-circuit conductors.
3.4
INSTALLATION
A.
Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise
indicated or required by Code. Avoid obstructing access or placing conductors where they may
be subjected to strain, impact or damage.
Section 26 05 26
Grounding and Bonding for Electrical Systems
B.
Common Ground Bonding with Lightning Protection System: Comply with NFPA 780 and UL 96
when interconnecting with lightning protection system. Bond electrical power system ground
directly to lightning protection system grounding conductor at closest point to electrical service
grounding electrode. Use bonding conductor sized same as system grounding electrode
conductor and install in conduit.
C.
Ground rods: Drive rods until tops are 2 inches below finished floor or final grade, unless
otherwise indicated.
1.
Interconnect ground rods with grounding electrode conductor below grade and as
otherwise indicated. Make connections without exposing steel or damaging coating, if
any.
D.
Test Wells: Ground rod driven through drilled hole in bottom of handhole. Handholes are
specified in Division 26 Section Underground Ducts and Raceways for Electrical Systems, and
shall be at least 12 inches deep, with cover.
1.
Test Wells: Install at least one test well for each service, unless otherwise indicated.
Install at the ground rod electrically closest to service entrance. Set top of test well flush
with finished grade or floor.
E.
Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance,
except where routed through short lengths of conduit.
1.
Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate
any adjacent parts.
2.
Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install so
vibration is not transmitted to rigidly mounted equipment.
3.
Use exothermic-welded connectors for outdoor locations, but if a disconnect-type
connection is required, use a bolted clamp.
F.
G.
Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of
associated fans, blowers, electric heaters and air cleaners. Install bonding jumper to bond
across flexible duct connections to achieve continuity.
H.
Grounding for Steel Building Structure: Install a driven ground rod at base of each corner
column and at intermediate exterior columns at distances not more than 60 feet apart.
I.
Ground Ring: Install a grounding conductor, electrically connected to each building structure
ground rod and to each steel column and indicated item, extending around the perimeter of
building.
1.
Install tinned-copper conductor not less than No. 4/0 AWG for ground ring and for taps to
building steel.
2.
Bury ground ring not less than 24 inches from building foundation at a depth not less than
30 inches below finished grade.
Section 26 05 26
Grounding and Bonding for Electrical Systems
J.
3.5
Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70, using
a minimum of 20 feet of bare copper conductor not smaller than No. 4 AWG.
1.
If concrete foundation is less than 20 feet long, coil excess conductor within base of
foundation.
2.
Bond grounding conductor to reinforcing steel in at least four locations and to anchor
bolts. Extend grounding conductor below grade and connect to building grounding grid or
to grounding electrode external to concrete.
FIELD QUALITY CONTROL
A.
Perform the following tests and inspections and prepare test reports:
1.
After installing grounding system but before permanent electrical circuits have been
energized, test for compliance with requirements.
2.
Test completed grounding system at each location where a maximum ground-resistance
level is specified, at service disconnect enclosure grounding terminal at ground test wells.
Make tests at ground rods before any conductors are connected.
a.
Measure ground resistance not less than two full days after last trace of
precipitation and without soil being moistened by any means other than natural
drainage or seepage and without chemical treatment or other artificial means of
reducing natural ground resistance.
b.
Perform tests by fall-of-potential method according to IEEE 81.
3.
Prepare dimensioned drawings locating each test well, ground rod and ground rod
assembly and other grounding electrodes. Identify each by letter in alphabetical order,
and key to the record of tests and observations. Include the number of rods driven and
their depth at each location, and include observations of weather and other phenomena
that may affect test results. Describe measures taken to improve test results.
B.
C.
Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Engineer
promptly and include recommendations to reduce ground resistance.
END OF SECTION
Section 26 05 26
Grounding and Bonding for Electrical Systems
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
B.
1.4
PERFORMANCE REQUIREMENTS
A.
Design supports for multiple raceways capable of supporting combined weight of supported
systems and its contents.
B.
1.5
SUBMITTALS
A.
B.
Shop Drawings: Show fabrication and installation details and include calculations for the
following:
1.
Trapeze hangers. Include Product Data for components.
2.
Steel slotted channel systems. Include Product Data for components.
3.
Equipment supports.
1.6
QUALITY ASSURANCE
A.
1.7
A.
Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
PART 2 - PRODUCTS
2.1
Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field
assembly.
Section 26 05 29
Hangers and Supports for Electrical System
1.
2.
3.
4.
B.
Raceway and Cable Supports: As described in NECA 1 and NECA 101. NECA publications are
available at www.NECAnet.org.
C.
Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed
for types and sizes of raceway or cable to be supported.
D.
E.
Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates,
shapes and bars.
F.
Mounting, Anchoring and Attachment Components: Items for fastening electrical items or their
supports to building surfaces include the following:
1.
Powder-Actuated Fasteners: Threaded 304 stainless steel stud, for use in hardened
Portland cement concrete, steel or wood, with tension, shear, and pullout capacities
appropriate for supported loads and building materials where used.
a.
Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the work include, but are not limited
to, the following:
1). Hilti Inc.
2). ITW Ramset/Red Head; a division of Illinois tool works, Inc.
3). MKT Fastening, LLC
4). Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.
2.
Mechanical-Expansion Anchors: Insert-wedge-type, stainless steel, for use in hardened
Portland cement concrete with tension, shear and pullout capacities appropriate for
supported loads and building materials in which used.
a.
Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the work include, but are not limited
to, the following:
1). Cooper B-Line, Inc.; a division of Cooper Industries
2). Empire Tool and Manufacturing Co., Inc.
3). Hilti Inc.
4). ITW Ramset/Red head; a division of Illinois tool works, Inc.
5). MKT Fastening, LLC.
3.
Concrete Inserts: Stainless steel, slotted support system units similar to MSS Type 18;
complying with MFMA-4 or MSS SP-58.
4.
Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for
attached structural element.
Section 26 05 29
Hangers and Supports for Electrical System
5.
6.
7.
8.
2.2
Through Bolts: Structural type, hex head, and high strength. Comply with ASTM A 325.
Toggle bolts: All-steel springhead type.
Hanger Rods: Threaded 304 stainless steel.
Nuts: Match threaded rod or bolt; double nut vertical hanger rods.
PART 3 - EXECUTION
3.1
APPLICATION
A.
Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical
equipment and systems except if requirements in this Section are stricter.
B.
Outdoor locations: Supporting material shall be stainless steel or PVC-Coated galvanized steel
or as described within the Drawings.
C.
Indoor locations: Supporting materials shall be galvanized in dry areas and stainless steel or
PVC-Coated galvanized steel in damp areas, or as described within the Drawings.
D.
Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for
RMC as required by NFPA 70. Minimum rod size shall be inch in diameter.
E.
Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support
system, sized so capacity can be increased by at least 25 percent in future without exceeding
specified design load limits.
1.
Secure raceways and cables to these supports with two-bolt conduit clamps.
3.2
SUPPORT INSTALLATION
A.
Comply with NECA 1 and NECA 101 for installation requirements except as specified in this
Article.
B.
C.
Strength of Support Assemblies: Where not indicated, select sizes of components so strength
will be adequate to carry present and future static loads within specified loading limits. Minimum
static design load used for strength determination shall be weight of supported components plus
200 lbs.
D.
Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten
electrical items and their supports to building structural elements by the following methods
unless otherwise indicated by code:
1.
To Wood: Fasten with lag screws or through bolts.
2.
To New Concrete: Bolt to concrete inserts.
3.
To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor
fasteners on solid masonry units.
4.
To Existing Concrete: Expansion anchor fasteners.
5.
Instead of expansion anchors, powder-actuated driven threaded studs provided with lock
washers and nuts may be used in existing standard-weight concrete 4 inches thick or
Section 26 05 29
Hangers and Supports for Electrical System
6.
7.
8.
E.
3.3
greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than
4 inches thick.
To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers
and nuts.
To Light Steel: Stainless steel sheet metal screws.
Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets,
panelboards, disconnect switches, control enclosures, pull and junction boxes,
transformers and other devices on slotted-channel racks attached to substrate.
Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing
bars.
INSTALLATION OF FABRICATED METAL SUPPORTS
A.
3.4
Cut, fit and place miscellaneous metal supports accurately in location, alignment and elevation
to support and anchor electrical materials and equipment.
CONCRETE BASES
A.
Construct concrete bases of dimensions indicated but not less than 4 inches larger in both
directions than supported unit, and so anchors will be a minimum of 10 bolt diameters from
edge of the base.
B.
C.
END OF SECTION
Section 26 05 29
Hangers and Supports for Electrical System
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.
B.
1.3
DEFINITIONS
A.
B.
C.
D.
E.
1.4
SUBMITTALS
A.
Product Data: for surface raceways, wireways and fittings, hinged-cover enclosures and
cabinets.
B.
C.
1.5
QUALITY ASSURANCE
A.
Electrical Components, Devices and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B.
PART 2 - PRODUCTS
2.1
Section 26 05 33
Raceway and Boxes for Electrical Systems
3.
4.
5.
6.
7.
8.
9.
B.
C.
D.
EMT: ANSI C80.3 fittings for conduit (Including all Types and Flexible and Liquidtight), EMT,
and Cable: NEMA FB 1; listed for type and size raceway with which used, and for application
and environment in which installed.
1.
Conduit Fittings for Hazardous (Classified) Locations: comply with UL 886
2.
Coating for Fittings for PVC-Coated Conduit: Minimum Thickness 0.040 inch, with
overlapping sleeves protecting threaded joints.
E.
Joint Compound for Rigid Steel Conduit: Listed for use in cable connector assemblies and
compounded for use to lubricate and protect threaded raceway joints from corrosion and
enhance their conductivity.
2.2
B.
C.
Fittings for RNC: NEMA TC 3; match to conduit or tubing type and material.
2.3
Section 26 05 33
Raceway and Boxes for Electrical Systems
6.
7.
8.
9.
10.
11.
12.
13.
B.
C.
Cast-Metal Outlet and Device boxes: NEMA FB 1, Type FD, with gasketed cover.
D.
E.
F.
Hinged-Cover Enclosures: NEMA 250, Type 1, with continuous-hinge cover with flush latch for
conditioned spaces only, unless otherwise indicated.
G.
Hinged-Cover Enclosures: NEMA 250, Type 4 Stainless steel, with continuous-hinge cover with
latches for outdoor, process buildings, above and below grade structures and damp locations,
unless otherwise indicated.
2.4
Steel Pipe Sleeves: ASTM A 53/A, 53M, Type E, Grade B, Schedule 40, galvanized steel, plain
ends.
B.
Cast-Iron Pipe Sleeves: Cast or fabricated wall pipe, equivalent to ductile-iron pressure pipe,
with plain ends and integral waterstop, unless otherwise indicated.
C.
Sleeves for Rectangular Openings: Galvanized sheet steel with minimum 0.052-or 0.138-inch
thickness as indicated and of length to suit application.
D.
2.5
SLEEVE SEALS
A.
B.
Description: Modular sealing device, designed for field assembly, to fill annular space between
sleeve and cable.
1.
Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit.
Include type and number required for material and size of raceway or cable.
2.
Pressure Plates: Stainless steel. Include two for each sealing element.
3.
Connecting Bolts and Nuts: Stainless steel of length required to secure pressure plates to
sealing elements. Include one for each sealing element.
Section 26 05 33
Raceway and Boxes for Electrical Systems
PART 3 - EXECUTION
3.1
RACEWAY APPLICATION
A.
B.
Indoors:
1.
Exposed: PVC-Coated Rigid Steel or as noted in the Drawings.
2.
Concealed: Galvanized Rigid Steel or as noted in the Drawings.
3.
Connection to Vibrating Equipment (Including Transformers and Hydraulic. Pneumatic,
Electric Solenoid or Motor-Driven Equipment): PVC-Coated LFMC.
4.
Damp or Wet Locations: PVC-coated Rigid Steel or as noted in the Drawings.
5.
Above Drop-in Ceilings: EMT for lighting and receptacle branch circuits or as noted in the
Drawings.
6.
Concealed in New Walls: EMT for lighting and receptacle branch circuits and switch legs
or as noted in the Drawings.
C.
Minimum Raceway Size: -inch trade size; 1-inch trade size for below grade installation.
D.
Raceway Fittings: Compatible with raceways and suitable for use and location.
1.
Rigid Steel Conduit: Use threaded rigid steel conduit fittings, unless otherwise indicated.
2.
PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with that
material.
E.
3.2
INSTALLATION
A.
Comply with NECA 1 for installation requirements applicable to products specified in Part 2
except where requirements on Drawings or in this Article are stricter.
B.
Keep raceways at least 6 inches away from parallel runs of flues and steam or hot-water pipes.
Install horizontal raceway runs above water and steam piping.
C.
D.
Support raceways as specified in Division 26 Section Hangers and Supports for Electrical
Systems.
E.
Arrange stub-ups so curved portions of bends are not visible above the finished slab.
F.
Install no more than the equivalent of four 90-degree bends in any conduit run except for
communications conduits, for which fewer bends are allowed.
G.
Section 26 05 33
Raceway and Boxes for Electrical Systems
2.
3.
4.
5.
Arrange raceways to cross building expansion joints at right angles with expansion
fittings.
Do not install conduits in such a manner as to compromise the structural integrity of
walls, roofs, ceilings or floor. Where necessary, provide additional supporting members to
support conduit runs. Below grade conduits 1 1/2 and larger shall be routed 24 below
the concrete floor slabs.
Comply with Chapter 6 of ACI 318.
Change from nonmetallic conduit to Galvanized Rigid Steel Conduit before rising above
the floor.
H.
Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply
listed compound to threads of raceway and fittings before making up joints. Follow compound
manufacturers written instructions.
I.
J.
Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not
less than 200-lb tensile strength. Leave at least 12 inches of slack at each end of pull wire.
K.
Install raceway sealing fittings at suitable, approved and accessible locations and fill them with
listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a
blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway
sealing fittings at the following points:
1.
Where conduits pass from warm to cold locations, such as boundaries of refrigerated
spaces.
2.
Where otherwise required by NFPA 70.
L.
Expansion-Joint Fittings: Install in each run of aboveground conduit that is located where
environmental temperature change may exceed 30 deg. F, and that has straight-run length that
exceeds 25 feet.
1.
Install expansion-joint fittings for each of the following locations, and provide type and
quantity of fittings that accommodate temperature change listed for location:
a.
Outdoor Locations Not Exposed to Direct Sunlight: 125 deg F temperature change.
b.
Outdoor Locations Exposed to Direct Sunlight: 155 deg F temperature change.
c.
Indoor Spaces: connected with the Outdoors without Physical Separation: 125 deg
F temperature change.
d.
Attics: 135 deg F temperature change.
2.
Install fitting(s) that provide expansion and contraction for at least 0.00041 inch per foot
of length of straight run per deg F of temperature change.
3.
Install each expansion-joint fitting with position, mounting and piston setting selected
according to manufacturers written instructions for conditions at specific location at the
time of installation.
M.
Flexible conduit connections: Use maximum of 36 inches of flexible conduit for equipment
subject to vibration, noise transmission, or movement, and for transformers and motors.
1.
Use LFMC in damp or wet locations subject to severe physical damage.
2.
Use LFMC or LFNC in damp or wet locations not subject to severe physical damage.
N.
Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of cell of masonry block,
and install box flush with surface of wall.
3.3
Section 26 05 33
Raceway and Boxes for Electrical Systems
B.
Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed
openings are used. Install sleeves during erection of slabs and walls.
C.
Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D.
Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies
unless openings compatible with firestop system used are fabricated during construction of floor
or wall.
E.
Cut sleeves to length for mounting flush with both surfaces of walls.
F.
Size pipe sleeves to provide -inch annular clear space between sleeve and raceway unless
sleeve seal is to be installed.
G.
Seal space outside of sleeves with grout for penetrations of concrete and masonry.
H.
Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve
and raceway, using joint sealant appropriate for size, depth, and location of joint.
I.
J.
K.
L.
Underground, Exterior-Wall Penetrations: Install cast-iron wall pipes for sleeves. Size sleeves
to allow for 1-inch annular clear space between raceway and sleeve for installing mechanical
sleeve seals.
3.4
SLEEVE-SEAL INSTALLATION
A.
B.
Use type and number of sealing elements recommended by manufacturer for raceway material
and size. Position raceway in center of sleeve. Assemble mechanical sleeve seals and install in
annular space between raceway and sleeve. Tighten bolts against pressure plates that cause
sealing elements to expand and make watertight seal.
3.5
FIRESTOPPING
A.
3.6
Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore
original fire-resistance rating of assembly.
PROTECTION
A.
Provide final protection and maintain conditions that ensure coatings, finishes and cabinets are
without damage or deterioration at time of Substantial Completion.
END OF SECTION
Section 26 05 33
Raceway and Boxes for Electrical Systems
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
B.
1.4
SUBMITTALS
A.
B.
Shop Drawings for Precast or Factory-Fabricated Underground Utility Structures: Include plans,
elevations, sections, details, attachments to other work, and accessories, including the
following:
1.
Duct entry provisions, including locations and duct sizes.
2.
Reinforcement details/
3.
Step details.
4.
Grounding details.
5.
Dimensioned locations of cable rack inserts, pulling-in and lifting irons, and sumps.
6.
Joint details.
C.
Shop Drawings for Factory-Fabricated Handholes and Boxes Other Than Precast Concrete:
Include dimensioned plans, sections and elevations, and fabrication and installation details,
including the following:
1.
Duct entry provisions, including locations and duct sizes.
2.
Cover design.
3.
Grounding details.
4.
Dimensioned locations of cable rack inserts and pulling-in lifting irons.
D.
Duct-Bank Coordination Drawings: Show duct profiles and coordination with other utilities and
underground structures.
1.
Include plans and sections, drawn to scale, and show bends and locations of expansion
fittings.
E.
Product Certificates: for concrete and steel used in precast concrete handholes, as required by
ASTM C858.
F.
G.
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
1.5
QUALITY ASSURANCE
A.
B.
1.6
Deliver ducts to Project site with ends capped. Store nonmetallic ducts with supports to prevent
bending, warping, and deforming.
B.
Store precast concrete and other factory-fabricated underground utility structures at Project site
as recommended by manufacturer to prevent physical damage. Arrange so identification
markings are visible.
C.
Lift and support precast concrete units only at designated lifting or supporting points.
1.7
COORDINATION
A.
Coordinate layout and installation of ducts, manholes, handholes, and boxes with final
arrangement of other utilities, site grading, and surface features as determined in the field.
B.
Coordinate elevations of ducts and duct-bank entrances into manholes, handholes and boxes
with final arrangement of other utilities, site grading, and surface features as determined in the
field.
C.
Coordinate elevations of ducts and duct-bank entrances into manholes, handholes, and boxes
with final locations and profiles of ducts and duct banks as determined by coordination with
other utilities, underground obstructions and surface features. Revise locations and elevations
from those indicated a required to suit field conditions and to ensure that duct runs drain to
manholes and handholes and as approved by Engineer.
PART 2 - PRODUCTS
2.1
CONDUIT
A.
B.
C.
RNC: NEMA TC2, type EPPC-40-PVC, UL 651 , with matching fittings by same manufacturer
as the conduit, complying with NEMA TC 3 and UL 514B.
2.2
B.
C.
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
2.3
Frame and Cover: Weatherproof cast-iron frame, with cast-iron cover with recessed
cover hook eyes and tamper-resistant, captive, cover-securing bolts.
Frame and Cover: Weatherproof steel frame, with steel cover with recessed cover hook
eyes and tamper-resistant, captive cover-securing bolts.
Frame and Cover: Weatherproof steel frame, with hinged steel access door assembly
with tamper-resistant, captive, cover-securing bolts.
Frame and cover: Weatherproof aluminum frame with hinged aluminum access door
assembly with tamper-resistant, captive, cover-securing bolts.
a.
Cover Hinges: concealed, with hold-open ratchet assembly.
b.
Cover Handle: Recessed.
Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.
Cover Legend: Molded lettering, ELECTRIC.
Configuration: Units shall be designed for flush burial and have integral closed bottom,
unless otherwise indicated.
Extensions and Slabs: Designed to mate with bottom of enclosure. Same material as
enclosure.
a.
Extension shall provide increased depth of 12 inches.
b.
Slab: Same dimensions as bottom of enclosure, and arranged to provide closure.
Windows: Precast openings in walls, arranged to match dimensions and elevations of
approaching ducts and duct banks plus an additional 12 inches vertically and horizontally
to accommodate alignment variations.
a.
Windows shall be located no less than 6 inches from interior surfaces of walls,
floors, or frames and covers of handholes, but close enough to corners to facilitate
racking of cables on walls.
b.
Window opening shall have cast-in-place, welded wire fabric reinforcement for field
cutting and bending to tie in to concrete envelopes of duct banks.
c.
Window openings shall be framed with at least two additional No. 4 steel
reinforcing bars in concrete around each opening.
Duct Entrances in Handhole Walls: Cast end-bell or duct-terminating fitting in wall for
each entering duct.
a.
Type and size shall match fittings to duct or conduit to be terminated.
b.
Fittings shall align with elevations of approaching ducts and be located near
interior corners of handholes to facilitate racking of cable.
Handholes 12 inches wide by 24 inches long and larger shall have inserts for cable racks
and pulling-in irons installed before concrete is poured.
B.
Polymer Concrete Handholes and Boxes with Polymer Concrete Cover: Molded of sand and
aggregate, bound together with a polymer resin and reinforced with steel or fiberglass or a
combination of the two.
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
1.
2.4
B.
Duct-Sealing Compound: Nonhardening, safe for contact with human skin, not deleterious to
cable insulation and workable at temperatures as low as 35 degrees F. Capable of withstanding
temperature of 300 degrees F without slump and adhering to clean surfaces of plastic ducts,
metallic conduits, conduit coatings, concrete, masonry, lead, cable sheaths, cable jackets,
insulation materials, and common metals.
C.
PART 3 - EXECUTION
3.1
3.2
Ducts for Electrical Feeders 600 V and Less: RNC, NEMA Type EPC-40-PVC, in red blended
mix concrete-encased duct bank, unless otherwise indicated. Transition to above ground shall
be PVC-coated steel conduit.
UNDERGROUND ENCLOSURE APPLICATION
A.
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
2.
3.3
EARTHWORK
A.
Restore surface feathers at areas disturbed by excavation and reestablish original grades,
unless otherwise indicated. Replace removed sod immediately after backfilling is completed.
B.
Restore areas disturbed by trenching, storing of dirt, cable laying, and other work. Restore
vegetation and include necessary top soiling, fertilizing, timing, seeding, sodding, sprigging and
mulching.
C.
Cut and patch existing pavement in the path of underground ducts and utility structures.
3.4
DUCT INSTALLATION
A.
Slope: Pitch ducts a minimum slope of 1:300 down toward manholes and handholes and away
from buildings and equipment. Slope ducts from high point in runs between two manholes to
drain in both directions.
B.
Curves and Bends: Use 5-degree angle couplings for small changes in direction. Use
manufactured long sweep bends with a minimum radius of 36 inches, both horizontally and
vertically unless otherwise indicated. All below grade elbows and bends to be galvanized.
C.
Joints: Use solvent-cemented joints in ducts and fittings and make watertight according to
manufacturers written instructions. Stagger couplings so those of adjacent ducts do not lie in
same plane.
D.
Duct Entrances to Manholes and Concrete and Polymer Concrete Handholes: Use end bells,
spaced approximately 10 inches o.c. for 5-inch ducts and vary proportionately for other duct
sizes.
1.
Begin change from regular spacing to end-bell spacing 10- feet from the end bell without
reducing duct line slope and without forming a trap in the line.
2.
Grout end bells into structure walls from both sides to provide watertight entrances.
E.
Building Wall or Floor Penetrations: Make a transition from underground duct to galvanized rigid
steel conduit unless otherwise indicated, at least 3 feet outside the building wall without
reducing duct line slope away from the building and without forming a trap in the line. Use
fittings manufactured for duct-to-conduit transition.
F.
Sealing: Provide temporary closures at terminations of ducts that have cables pulled. Seal
spare ducts at terminations. Use sealing compound and plugs to withstand at least 15-psig
hydrostatic pressure.
G.
3.5
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
3.
Unless otherwise indicated, support units on a level 12 bed of crushed stone or gravel
graded from 1-inch sieve to No. 4 sieve and compacted to same density as adjacent
undisturbed earth.
B.
Elevations:
1.
Install handholes with bottom below the frost line.
2.
Handhole covers: In paved areas and trafficways, set surface flush with finished grade.
Set covers of other handholes 1 inch above finished grade.
3.
Where indicated, cast handhole cover frame integrally with handhole structure.
C.
Hardware: Install removable hardware, including pulling eyes, cable stanchions, and cable arms
as required for installation and support of cables and conductors and as indicated.
D.
Field-Installed Bolting Anchors in Manholes and Concrete Handholes: Do not drill deeper than
3-7/8 inches for manholes and 2 inches for handholes, for anchor bolts installed in the field. Use
a minimum of two anchors for each cable stanchion.
3.6
Install handholes and boxes level and plumb and with orientation and depth coordinated with
connecting ducts to minimize bends and deflections required for proper entrances. Use box
extension if required to match depths of ducts and seal joint between box and extension as
recommended by the manufacturer.
B.
Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from
1/2-inch sieve to No. 4 sieve and compacted to same density as adjacent undisturbed earth.
C.
Elevation: In paved areas and trafficways, set so cover surface will be flush with finished grade.
Set covers of other handholes 1 inch above finished grade.
D.
Install handholes and boxes with bottom below the frost line.
E.
Install removable hardware, including pulling eyes, cable stanchions, cable arms, and
insulators, as required for installation and support of cables and conductors and as indicated.
Select arm lengths to be long enough to provide spare space for future cables, but short enough
to preserve adequate working clearances in the enclosure.
F.
Field-cut openings for ducts and conduits according to enclosure manufacturers written
instructions. Cut wall of enclosure with a tool designed for material to be cut. Size holes for
terminating fittings to be used, and seal around penetrations after fittings are installed.
G.
For enclosures installed in asphalt paving and subject to occasional, nondeliberate, heavyvehicle loading form and pour a concrete ring encircling and in contact with, enclosure and with
top surface screeded to top of box cover frame.
1.
Concrete: 3000 psi, 28-day strength, with a troweled finish.
2.
Dimensions: 12 inches wide by 12 inches deep.
3.7
GROUNDING
A.
3.8
Ground underground ducts and utility structures according to Division 26 Section Grounding
and Bonding for Electrical Systems.
FIELD QUALITY CONTROL
A.
Perform the following tests and inspections and prepare test reports.
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
1.
2.
B.
3.9
A.
Pull leather-washer-type duct cleaner, with graduated washer sizes, through full length of ducts.
Follow with rubber duct swab for final cleaning and to assist in spreading lubricant throughout
ducts.
END OF SECTION
Section 26 05 43
Underground Ducts & Raceways for Electrical Systems
RELATED DOCUMENTS
A.
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B.
C.
1.2
SUMMARY
A.
1.3
A.
B.
1.4
QUALITY ASSURANCE
A.
B.
C.
D.
1.5
COORDINATION
A.
Coordinate identification names, abbreviations, colors and other features with requirements in
the Contract Documents, Shop Drawings, manufacturers wiring diagrams, and the Operation
and Maintenance Manual, and with those required by codes, standards and 29 CFR 1910.145.
Use consistent designations throughout Project.
B.
C.
Coordinate installation of identifying devices with location of access panels and doors.
Section 26 05 53
Identification for Electrical Systems
PART 2 - PRODUCTS
2.1
CONDUCTOR
MATERIALS.
AND
COMMUNICATION
AND
CONTROL-CABLE
IDENTIFICATION
A.
Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils thick by 1
to 2 inches wide.
B.
Marker Tapes: vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification
legend machine printed by thermal transfer or equivalent process.
2.2
B.
C.
Metal-Backed, Butyrate Warning Signs: Weather-resistant, nonfading, preprinted, celluloseacetate butyrate signs with 0.0396-inch galvanized-steel backing; and with colors, legend and
size required for application. inch grommets in corners for mounting. Nominal size, 10 by 14
inches.
D.
Sample warning label and sign shall include, but are not limited to the following legends:
1.
Multiple Power source Warning: DANGER ELECTRICAL SHOCK HAZARD
EQUIPMENT HAS MULTIPLE POWER SOURCES.
2.
Workspace Clearance Warning: WARNING - OSHA REGULATION AREA IN FRONT
OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36 INCHES.
3.
WARNING ARC FLASH AND SHOCK HAZARD APPROPRIATE PPE REQUIRED.
2.3
INSTRUCTION SIGNS
A.
2.4
Engraved, laminated acrylic or melamine plastic, minimum 1/16 inch thick for signs up to 20 sq.
in. and 1/8 inch thick for larger sized.
1.
Engraved legend with black letters on white face.
2.
Punched or drilled for mechanical fasteners.
3.
Framed with mitered acrylic molding and arranged for attachment at applicable
equipment.
EQUIPMENT IDENTIFICATION LABELS
A.
Engraved, Laminated Acrylic or Melamine Label: Punched or drilled for screw mounting. White
letters on a dark gray background. Minimum letter height shall be 3/8 inch.
B.
Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be 1
inch.
2.5
Cable ties: fungus-inert, self-extinguishing, 1-piece, self-locking, type 6/6 nylon cable ties.
1.
Minimum Width: 3/16 inch.
2.
Tensile Strength: 50 lb minimum.
3.
Temperature Range: Minus 40 to plus 185 degrees F.
4.
Color: Black, except where used for color-coding.
Section 26 05 53
Identification for Electrical Systems
B.
Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine
screws with nuts and flat and lock washers.
PART 3 - EXECUTION
3.1
APPLICATION
A.
Outlet Boxes For Receptacles: Identify branch circuit by panel name and circuit number.
B.
Power-Circuit Conductor Identification: of secondary conductors No. 1/0 AWG and larger in
vaults, pull and junction boxes, manholes, and handholes use color-coding conductor tape.
Identify source and circuit number of each set of conductors. For single conductor cables,
identify phase in addition to the above.
C.
Branch-Circuit Conductor Identification: Where there are conductors for more than three branch
circuits in same junction or pull box, use color-coding conductor tape. Identify each ungrounded
conductor according to source and circuit number.
D.
E.
Warning Labels for Indoor Cabinets, Boxes and Enclosures for Power and Lighting: comply with
29 CFR 1910.145 and apply metal-backed, butyrate warning signs. Identify system voltage with
black letters on an orange background. Apply to exterior of door, cover or other access.
1.
Equipment with Multiple Power or Control Sources: Apply to door or cover of equipment
including, but not limited to the following:
a.
Power transfer switches
b.
Controls with external control power connections.
2.
Equipment Requiring Workspace Clearance According to NFPA 70: Unless otherwise
indicated, apply to door or cover of equipment but not on flush panelboards and similar
equipment in finished spaces.
F.
Instruction Signs:
1.
Operating Instructions: Install instruction signs to facilitate proper operation and
maintenance of electrical systems and items to which they connect. Install instruction
signs with approved legend where instructions are needed for system or equipment
operation.
2.
Emergency Operating Instructions: Install instruction signs with white legend on a red
background with minimum 3/8 inch high letters for emergency instructions at equipment
used for power transfer.
G.
Equipment Identification Labels: On each unit of equipment, install unique designation label that
is consistent with wiring diagrams, schedules, and Operation and Maintenance Manual. Apply
labels to disconnect switches and protection equipment, central or master units, control panels,
control stations, terminal cabinets, and racks of each system. Systems include power, lighting,
control, communication, signal, monitoring, and alarm systems unless equipment is provided
with its own identification.
1.
Labeling Instructions:
Section 26 05 53
Identification for Electrical Systems
a.
2.
3.2
INSTALLATION
A.
B.
Location: Install identification materials and devices at locations for most convenient viewing
without interference with operation and maintenance of equipment.
C.
Apply identification devices to surfaces that require finish after completing finish work.
D.
Self-Adhesive Identification Products: Clean surfaces before application, using materials and
methods recommended by manufacturer of identification device.
E.
Attach nonadhesive signs and plastic labels with screws and auxiliary hardware appropriate to
the location and substrate.
F.
Color-Coding for Phase and Voltage Level Identification, 600 V and Less: Use the colors listed
below for ungrounded service, feeder and branch-circuit conductors.
1.
Color shall be factory applied or, for sized larger than No. 6 AWG if authorities having
jurisdiction permit, field applied.
2.
Colors for 480/277-V Circuits:
a.
Phase A: Brown
b.
Phase B: Orange
c.
Phase C: Yellow
3.
Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum
distance of 6 inches from terminal points and in boxes where splices or taps are made.
Apply last two turns of tape with no tension to prevent possible unwinding. Locate bands
to avoid obscuring factory cable markings.
END OF SECTION
Section 26 05 53
Identification for Electrical Systems
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
Existing to Remain: Existing items of construction that are not to be removed and that are not
otherwise indicated to be removed, removed and salvaged, or removed and reinstalled.
B.
One-Line Diagram: A diagram which shows, by means of single lines and graphic symbols, the
course of an electric circuit or system of circuits and the component devices or parts used
therein.
C.
Protective Device: A device that senses when an abnormal current flow exists and then
removes the affected portion from the system.
D.
E.
Service: The conductors and equipment for delivering electric energy from the serving utility to
the wiring system of the premises served.
1.4
ACTION SUBMITTALS
A.
B.
Other Action Submittals: Submit the following after the approval of system protective devices
submittals. Submittals may be in digital form.
1.
Short-circuit study input data, including completed computer program input data sheets.
2.
Short-circuit study and equipment evaluation report; signed, dated, and sealed by a
qualified professional engineer.
a.
Submit study report for action prior to receiving final approval of the distribution
equipment submittals. If formal completion of studies will cause delay in equipment
manufacturing, obtain approval from Engineer for preliminary submittal of sufficient
study data to ensure that the selection of devices and associated characteristics is
satisfactory.
b.
Revised single-line diagram, reflecting field investigation results and results of
short-circuit study.
1.5
INFORMATIONAL SUBMITTALS
A.
B.
Product Certificates: For short-circuit study software, certifying compliance with IEEE 399.
Section 26 05 72
Overcurrent Protective Device Short-Circuit Study
1.6
QUALITY ASSURANCE
A.
Studies shall use computer programs that are distributed nationally and are in wide use.
Software algorithms shall comply with requirements of standards and guides specified in this
Section. Manual calculations are unacceptable.
B.
PART 2 - PRODUCTS
2.1
COMPUTER SOFTWARE
A.
B.
C.
Analytical features of fault-current-study computer software program shall have the capability to
calculate "mandatory," "very desirable," and "desirable" features as listed in IEEE 399.
D.
Computer software program shall be capable of plotting and diagramming time-currentcharacteristic curves as part of its output.
2.2
Executive summary.
B.
Study descriptions, purpose, basis, and scope. Include case descriptions, definition of terms,
and guide for interpretation of the computer printout.
C.
D.
E.
Section 26 05 72
Overcurrent Protective Device Short-Circuit Study
F.
G.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
Gather and tabulate the following input data to support the short-circuit study. Comply with
recommendations in IEEE 551 as to the amount of detail that is required to be acquired in the
field. Field data gathering shall be under the direct supervision and control of the engineer in
charge of performing the study, and shall be by the engineer or its representative who holds
NETA ETT Level III certification or NICET Electrical Power Testing Level III certification.
1.
Product Data for Project's overcurrent protective devices involved in overcurrent
protective device coordination studies. Use equipment designation tags that are
consistent with electrical distribution system diagrams, overcurrent protective device
submittals, input and output data, and recommended device settings.
2.
Obtain electrical power utility impedance at the service.
3.
Power sources and ties.
4.
For transformers, include kVA, primary and secondary voltages, connection type,
impedance, X/R ratio, taps measured in percent, and phase shift.
Section 26 05 72
Overcurrent Protective Device Short-Circuit Study
5.
6.
7.
8.
9.
10.
3.2
For reactors, provide manufacturer and model designation, voltage rating, and
impedance.
For circuit breakers and fuses, provide manufacturer and model designation. List type of
breaker, type of trip, SCCR, current rating, and breaker settings.
Generator short-circuit current contribution data, including short-circuit reactance, rated
kVA, rated voltage, and X/R ratio.
Busway manufacturer and model designation, current rating, impedance, lengths, and
conductor material.
Motor horsepower and NEMA MG 1 code letter designation.
Cable sizes, lengths, number, conductor material and conduit material (magnetic or
nonmagnetic).
SHORT-CIRCUIT STUDY
A.
Perform study following the general study procedures contained in IEEE 399.
B.
C.
D.
Begin short-circuit current analysis at the service, extending down to the system overcurrent
protective devices as follows:
1.
To normal system low-voltage load buses where fault current is 10 kA or less.
2.
Exclude equipment rated 240-V ac or less when supplied by a single transformer rated
less than 125 kVA.
E.
Study electrical distribution system from normal and alternate power sources throughout
electrical distribution system for Project. Study all cases of system-switching configurations and
alternate operations that could result in maximum fault conditions.
F.
The calculations shall include the ac fault-current decay from induction motors, synchronous
motors, and asynchronous generators and shall apply to low- and medium-voltage, three-phase
ac systems. The calculations shall also account for the fault-current dc decrement, to address
the asymmetrical requirements of the interrupting equipment.
1.
For grounded systems, provide a bolted line-to-ground fault-current study for areas as
defined for the three-phase bolted fault short-circuit study.
G.
Calculate short-circuit momentary and interrupting duties for a three-phase bolted fault at each
of the following:
1.
Electric utility's supply termination point.
2.
Incoming switchgear.
3.
Low-voltage switchgear.
4.
Motor-control centers.
5.
Control panels.
6.
Standby generators and automatic transfer switches.
7.
Branch circuit panelboards.
8.
Disconnect switches.
3.3
ADJUSTING
A.
Section 26 05 72
Overcurrent Protective Device Short-Circuit Study
3.4
DEMONSTRATION
A.
Train Owner's operating and maintenance personnel in the use of study results.
END OF SECTION
Section 26 05 72
Overcurrent Protective Device Short-Circuit Study
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
Existing to Remain: Existing items of construction that are not to be removed and that are not
otherwise indicated to be removed, removed and salvaged, or removed and reinstalled.
B.
One-Line Diagram: A diagram which shows, by means of single lines and graphic symbols, the
course of an electric circuit or system of circuits and the component devices or parts used
therein.
C.
Protective Device: A device that senses when an abnormal current flow exists and then
removes the affected portion from the system.
D.
E.
Service: The conductors and equipment for delivering electric energy from the serving utility to
the wiring system of the premises served.
1.4
ACTION SUBMITTALS
A.
B.
Other Action Submittals: Submit the following after the approval of system protective devices
submittals. Submittals may be in digital form.
1.
Coordination-study input data, including completed computer program input data sheets.
2.
Study and equipment evaluation reports.
3.
Overcurrent protective device coordination study report; signed, dated, and sealed by a
qualified professional engineer.
a.
Submit study report for action prior to receiving final approval of the distribution
equipment submittals. If formal completion of studies will cause delay in equipment
manufacturing, obtain approval from Engineer for preliminary submittal of sufficient
study data to ensure that the selection of devices and associated characteristics is
satisfactory.
1.5
INFORMATIONAL SUBMITTALS
A.
B.
Product Certificates: For overcurrent protective device coordination study software, certifying
compliance with IEEE 399.
Section 26 05 73
Overcurrent Protective Device Coordination Study
1.6
CLOSEOUT SUBMITTALS
A.
1.7
Operation and Maintenance Data: For the overcurrent protective devices to include in
emergency, operation, and maintenance manuals.
1.
In addition to items specified in Division 01 "Operation and Maintenance Data," include
the following:
a.
The following parts from the Protective Device Coordination Study Report:
1)
One-line diagram.
2)
Protective device coordination study.
3)
Time-current coordination curves.
b.
Power system data.
QUALITY ASSURANCE
A.
Studies shall use computer programs that are distributed nationally and are in wide use.
Software algorithms shall comply with requirements of standards and guides specified in this
Section. Manual calculations are unacceptable.
B.
PART 2 - PRODUCTS
2.1
COMPUTER SOFTWARE
A.
B.
C.
Analytical features of device coordination study computer software program shall have the
capability to calculate "mandatory," "very desirable," and "desirable" features as listed in
IEEE 399.
D.
Computer software program shall be capable of plotting and diagramming time-currentcharacteristic curves as part of its output. Computer software program shall report device
settings and ratings of all overcurrent protective devices and shall demonstrate selective
coordination by computer-generated, time-current coordination plots.
1.
Optional Features:
a.
Arcing faults.
b.
Simultaneous faults.
c.
Explicit negative sequence.
d.
Mutual coupling in zero sequence.
2.2
Executive summary.
B.
Study descriptions, purpose, basis and scope. Include case descriptions, definition of terms and
guide for interpretation of the computer printout.
C.
Section 26 05 73
Overcurrent Protective Device Coordination Study
2.
3.
4.
5.
D.
E.
Short-Circuit Study:
1.
Low-Voltage Fault Report: Three-phase and unbalanced fault calculations, showing the
following for each overcurrent device location:
a.
Voltage.
b.
Calculated fault-current magnitude and angle.
c.
Fault-point X/R ratio.
d.
Equivalent impedance.
2.
Momentary Duty Report: Three-phase and unbalanced fault calculations, showing the
following for each overcurrent device location:
a.
Voltage.
b.
Calculated symmetrical fault-current magnitude and angle.
c.
Fault-point X/R ratio.
d.
Calculated asymmetrical fault currents:
1)
Based on fault-point X/R ratio.
2)
Based on calculated symmetrical value multiplied by 1.6.
3)
Based on calculated symmetrical value multiplied by 2.7.
3.
Interrupting Duty Report: Three-phase and unbalanced fault calculations, showing the
following for each overcurrent device location:
a.
Voltage.
b.
Calculated symmetrical fault-current magnitude and angle.
c.
Fault-point X/R ratio.
d.
No AC Decrement (NACD) ratio.
e.
Equivalent impedance.
f.
Multiplying factors for 2-, 3-, 5-, and 8-cycle circuit breakers rated on a symmetrical
basis.
g.
Multiplying factors for 2-, 3-, 5-, and 8-cycle circuit breakers rated on a total basis.
F.
G.
Section 26 05 73
Overcurrent Protective Device Coordination Study
1.
2.
3.
4.
5.
6.
7.
Device tag and title, one-line diagram with legend identifying the portion of the system
covered.
Terminate device characteristic curves at a point reflecting maximum symmetrical or
asymmetrical fault current to which the device is exposed.
Identify the device associated with each curve by manufacturer type, function, and, if
applicable, tap, time delay, and instantaneous settings recommended.
Plot the following listed characteristic curves, as applicable:
a.
Power utility's overcurrent protective device.
b.
Medium-voltage equipment overcurrent relays.
c.
Medium- and low-voltage fuses including manufacturer's minimum melt, total
clearing, tolerance, and damage bands.
d.
Low-voltage equipment circuit-breaker trip devices, including manufacturer's
tolerance bands.
e.
Transformer full-load current, magnetizing inrush current, and ANSI through-fault
protection curves.
f.
Cables and conductors damage curves.
g.
Ground-fault protective devices.
h.
Motor-starting characteristics and motor damage points.
i.
Generator short-circuit decrement curve and generator damage point.
j.
The largest feeder circuit breaker in each motor-control center and panelboard.
Series rating on equipment allows the application of two series interrupting devices for a
condition where the available fault current is greater than the interrupting rating of the
downstream equipment. Both devices share in the interruption of the fault and selectivity
is sacrificed at high fault levels. Maintain selectivity for tripping currents caused by
overloads.
Provide adequate time margins between device characteristics such that selective
operation is achieved.
Comments and recommendations for system improvements.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
3.2
Examine Project overcurrent protective device submittals for compliance with electrical
distribution system coordination requirements and other conditions affecting performance.
Devices to be coordinated are indicated on Drawings.
1.
Proceed with coordination study only after relevant equipment submittals have been
assembled. Overcurrent protective devices that have not been submitted and approved
prior to coordination study may not be used in study.
PROTECTIVE DEVICE COORDINATION STUDY
A.
Comply with IEEE 242 for calculating short-circuit currents and determining coordination time
intervals.
B.
C.
The study shall be based on the device characteristics supplied by device manufacturer.
D.
Begin analysis at the service, extending down to the system overcurrent protective devices as
follows:
1.
To normal system low-voltage load buses where fault current is 10 kA or less.
2.
Exclude equipment rated 240-V ac or less when supplied by a single transformer rated
less than 125 kVA.
Section 26 05 73
Overcurrent Protective Device Coordination Study
E.
Study electrical distribution system from normal and alternate power sources throughout
electrical distribution system for Project. Study all cases of system-switching configurations and
alternate operations that could result in maximum fault conditions.
F.
G.
Motor Protection:
1.
Select protection for low-voltage motors according to IEEE 242 and NFPA 70.
2.
Select protection for motors served at voltages more than 600 V according to IEEE 620.
H.
Conductor Protection: Protect cables against damage from fault currents according to ICEA P32-382, ICEA P-45-482, and protection recommendations in IEEE 242. Demonstrate that
equipment withstands the maximum short-circuit current for a time equivalent to the tripping
time of the primary relay protection or total clearing time of the fuse. To determine temperatures
that damage insulation, use curves from cable manufacturers or from listed standards indicating
conductor size and short-circuit current.
I.
J.
The calculations shall include the ac fault-current decay from induction motors, synchronous
motors, and asynchronous generators and shall apply to low- and medium-voltage, three-phase
ac systems. The calculations shall also account for the fault-current dc decrement, to address
the asymmetrical requirements of the interrupting equipment.
1.
For grounded systems, provide a bolted line-to-ground fault-current study for areas as
defined for the three-phase bolted fault short-circuit study.
K.
Calculate short-circuit momentary and interrupting duties for a three-phase bolted fault and
single line-to-ground fault at each of the following:
1.
Electric utility's supply termination point.
2.
Switchgear.
3.
Unit substation primary and secondary terminals.
4.
Low-voltage switchgear.
5.
Motor-control centers.
6.
Standby generators and automatic transfer switches.
7.
Branch circuit panelboards.
L.
3.3
Perform a load-flow and voltage-drop study to determine the steady-state loading profile of the
system. Analyze power system performance two times as follows:
Section 26 05 73
Overcurrent Protective Device Coordination Study
1.
2.
3.4
Determine load-flow and voltage drop based on 80 percent of the design capacity of the
load buses.
Prepare the load-flow and voltage-drop analysis and report to show power system
components that are overloaded, or might become overloaded; show bus voltages that
are less than as prescribed by NFPA 70.
MOTOR-STARTING STUDY
A.
3.5
Perform a motor-starting study to analyze the transient effect of the system's voltage profile
during motor starting. Calculate significant motor-starting voltage profiles and analyze the
effects of the motor starting on the power system stability.
POWER SYSTEM DATA
A.
Obtain all data necessary for the conduct of the overcurrent protective device study.
1.
Verify completeness of data supplied in the one-line diagram on Drawings. Call
discrepancies to the attention of Engineer.
2.
For new equipment, use characteristics submitted under the provisions of action
submittals and information submittals for this Project.
3.
For existing equipment, whether or not relocated obtain required electrical distribution
system data by field investigation and surveys, conducted by qualified technicians and
engineers. The qualifications of technicians and engineers shall be qualified as defined
by NFPA 70E.
B.
Gather and tabulate the following input data to support coordination study. The list below is a
guide. Comply with recommendations in IEEE 241 and IEEE 551 for the amount of detail
required to be acquired in the field. Field data gathering shall be under the direct supervision
and control of the engineer in charge of performing the study, and shall be by the engineer or its
representative who holds NETA ETT Level III certification or NICET Electrical Power Testing
Level III certification.
1.
Product Data for overcurrent protective devices specified in other Sections and involved
in overcurrent protective device coordination studies. Use equipment designation tags
that are consistent with electrical distribution system diagrams, overcurrent protective
device submittals, input and output data, and recommended device settings.
2.
Electrical power utility impedance at the service.
3.
Power sources and ties.
4.
Short-circuit current at each system bus, three phase and line-to-ground.
5.
Full-load current of all loads.
6.
Voltage level at each bus.
7.
For transformers, include kVA, primary and secondary voltages, connection type,
impedance, X/R ratio, taps measured in percent, and phase shift.
8.
For reactors, provide manufacturer and model designation, voltage rating, and
impedance.
9.
For circuit breakers and fuses, provide manufacturer and model designation. List type of
breaker, type of trip and available range of settings, SCCR, current rating, and breaker
settings.
10.
Generator short-circuit current contribution data, including short-circuit reactance, rated
kVA, rated voltage, and X/R ratio.
11.
For relays, provide manufacturer and model designation, current transformer ratios,
potential transformer ratios, and relay settings.
12.
Maximum demands from service meters.
13.
Busway manufacturer and model designation, current rating, impedance, lengths, and
conductor material.
14.
Motor horsepower and NEMA MG 1 code letter designation.
15.
Low-voltage cable sizes, lengths, number, conductor material, and conduit material
(magnetic or nonmagnetic).
Section 26 05 73
Overcurrent Protective Device Coordination Study
16.
17.
3.6
Medium-voltage cable sizes, lengths, conductor material, and cable construction and
metallic shield performance parameters.
Data sheets to supplement electrical distribution system diagram, cross-referenced with
tag numbers on diagram, showing the following:
a.
Special load considerations, including starting inrush currents and frequent starting
and stopping.
b.
Transformer characteristics, including primary protective device, magnetic inrush
current, and overload capability.
c.
Motor full-load current, locked rotor current, service factor, starting time, type of
start, and thermal-damage curve.
d.
Generator thermal-damage curve.
e.
Ratings, types, and settings of utility company's overcurrent protective devices.
f.
Special overcurrent protective device settings or types stipulated by utility
company.
g.
Time-current-characteristic curves of devices indicated to be coordinated.
h.
Manufacturer, frame size, interrupting rating in amperes rms symmetrical, ampere
or current sensor rating, long-time adjustment range, short-time adjustment range,
and instantaneous adjustment range for circuit breakers.
i.
Manufacturer and type, ampere-tap adjustment range, time-delay adjustment
range, instantaneous attachment adjustment range, and current transformer ratio
for overcurrent relays.
j.
Panelboards, switchboards, motor-control center ampacity, and SCCR in amperes
rms symmetrical.
k.
Identify series-rated interrupting devices for a condition where the available fault
current is greater than the interrupting rating of the downstream equipment. Obtain
device data details to allow verification that series application of these devices
complies with NFPA 70 and UL 489 requirements.
FIELD ADJUSTING
A.
Adjust relay and protective device settings according to the recommended settings provided by
the coordination study. Field adjustments shall be completed by the engineering service division
of the equipment manufacturer under the Startup and Acceptance Testing contract portion.
B.
C.
Testing and adjusting shall be by a full-time employee of the Field Adjusting Agency, who holds
NETA ETT Level III certification or NICET Electrical Power Testing Level III certification.
1.
Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters. Perform
NETA tests and inspections for all adjustable overcurrent protective devices.
3.7
DEMONSTRATION
A.
Engage the Coordination Study Specialist to train Owner's maintenance personnel in the
following:
1.
Acquaint personnel in the fundamentals of operating the power system in normal and
emergency modes.
2.
Hand-out and explain the objectives of the coordination study, study descriptions,
purpose, basis, and scope. Include case descriptions, definition of terms, and guide for
interpreting the time-current coordination curves.
3.
Adjust, operate, and maintain overcurrent protective device settings.
END OF SECTION
Project No. 12078390
Durant State Fish Hatchery Phase 1
Section 26 05 73
Overcurrent Protective Device Coordination Study
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section includes a computer-based, arc-flash study to determine the arc-flash hazard distance
and the incident energy to which personnel could be exposed during work on or near electrical
equipment.
DEFINITIONS
A.
Existing to Remain: Existing items of construction that are not to be removed and that are not
otherwise indicated to be removed, removed and salvaged, or removed and reinstalled.
B.
One-Line Diagram: A diagram which shows, by means of single lines and graphic symbols, the
course of an electric circuit or system of circuits and the component devices or parts used
therein.
C.
Protective Device: A device that senses when an abnormal current flow exists and then
removes the affected portion from the system.
D.
E.
Service: The conductors and equipment for delivering electric energy from the serving utility to
the wiring system of the premises served.
1.4
ACTION SUBMITTALS
A.
B.
Other Action Submittals: Submit the following submittals after the approval of system protective
devices submittals. Submittals may be in digital form.
1.
Arc-flash study input data, including completed computer program input data sheets.
2.
Arc-flash study report; signed, dated, and sealed by a qualified professional engineer.
a.
Submit study report for action prior to receiving final approval of the distribution
equipment submittals. If formal completion of studies will cause delay in equipment
manufacturing, obtain approval from Architect for preliminary submittal of sufficient
study data to ensure that the selection of devices and associated characteristics is
satisfactory.
1.5
INFORMATIONAL SUBMITTALS
A.
B.
Product Certificates: For arc-flash hazard analysis software, certifying compliance with
IEEE 1584 and NFPA 70E.
Section 26 05 74
Overcurrent Protective Device Arc-Flash Study
1.6
CLOSEOUT SUBMITTALS
A.
B.
1.7
QUALITY ASSURANCE
A.
Studies shall use computer programs that are distributed nationally and are in wide use.
Software algorithms shall comply with requirements of standards and guides specified in this
Section. Manual calculations are unacceptable.
B.
PART 2 - PRODUCTS
2.1
COMPUTER SOFTWARE
A.
B.
C.
Analytical features of device coordination study computer software program shall have the
capability to calculate "mandatory," "very desirable," and "desirable" features as listed in
IEEE 399.
2.2
Executive summary.
B.
C.
D.
E.
Section 26 05 74
Overcurrent Protective Device Arc-Flash Study
e.
f.
g.
Equivalent impedance.
Multiplying factors for 2-, 3-, 5-, and 8-cycle circuit breakers rated on a symmetrical
basis.
Multiplying factors for 2-, 3-, 5-, and 8-cycle circuit breakers rated on a total basis.
F.
G.
Fault study input data, case descriptions, and fault-current calculations including a definition of
terms and guide for interpretation of the computer printout.
2.3
Comply with requirements in Division 26 "Identification for Electrical Systems." Produce a 3.5by-5-inch (76-by-127-mm) thermal transfer label of high-adhesion polyester for each work
location included in the analysis.
B.
The label shall have an orange header with the wording, "WARNING, ARC-FLASH HAZARD,"
and shall include the following information taken directly from the arc-flash hazard analysis:
1.
Location designation.
2.
Nominal voltage.
3.
Flash protection boundary.
4.
Hazard risk category.
5.
Incident energy.
6.
Working distance.
7.
Engineering report number, revision number, and issue date.
C.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
3.2
Examine Project overcurrent protective device submittals. Proceed with arc-flash study only
after relevant equipment submittals have been assembled. Overcurrent protective devices that
have not been submitted and approved prior to arc-flash study may not be used in study.
SHORT-CIRCUIT STUDY
A.
Perform study following the general study procedures contained in IEEE 399.
B.
C.
D.
Begin analysis at the service, extending down to the system overcurrent protective devices as
follows:
Section 26 05 74
Overcurrent Protective Device Arc-Flash Study
1.
2.
E.
Study electrical distribution system from normal and alternate power sources throughout
electrical distribution system for Project. Include studies of system-switching configurations and
alternate operations that could result in maximum fault conditions.
F.
The calculations shall include the ac fault-current decay from induction motors, synchronous
motors, and asynchronous generators and shall apply to low- and medium-voltage, three-phase
ac systems.
G.
Calculate short-circuit momentary and interrupting duties for a three-phase bolted fault and
single line-to-ground fault at each of the following:
1.
Electric utility's supply termination point.
2.
Switchgear.
3.
Unit substation primary and secondary terminals.
4.
Low-voltage switchgear.
5.
Motor-control centers.
6.
Standby generators and automatic transfer switches.
7.
Branch circuit panelboards.
8.
Control panels.
3.3
Comply with NFPA 70E and its Annex D for hazard analysis study.
B.
Use the short-circuit study output and the field-verified settings of the overcurrent devices.
C.
D.
Calculate the arc-flash protection boundary and incident energy at locations in the electrical
distribution system where personnel could perform work on energized parts.
E.
F.
Safe working distances shall be specified for calculated fault locations based on the calculated
arc-flash boundary, considering incident energy of 1.2 cal/sq.cm.
G.
Incident energy calculations shall consider the accumulation of energy over time when
performing arc-flash calculations on buses with multiple sources. Iterative calculations shall take
into account the changing current contributions, as the sources are interrupted or decremented
with time. Fault contribution from motors and generators shall be decremented as follows:
1.
Fault contribution from induction motors should not be considered beyond three to five
cycles.
2.
Fault contribution from synchronous motors and generators should be decayed to match
the actual decrement of each as closely as possible (e.g., contributions from permanent
magnet generators will typically decay from 10 per unit to three per unit after 10 cycles).
H.
Arc-flash computation shall include both line and load side of a circuit breaker as follows:
1.
When the circuit breaker is in a separate enclosure.
Section 26 05 74
Overcurrent Protective Device Arc-Flash Study
2.
I.
3.4
When the line terminals of the circuit breaker are separate from the work location.
Base arc-flash calculations on actual overcurrent protective device clearing time. Cap maximum
clearing time at two seconds based on IEEE 1584, Section B.1.2.
POWER SYSTEM DATA
A.
Obtain all data necessary for the conduct of the arc-flash hazard analysis.
1.
Verify completeness of data supplied on the one-line diagram on Drawings. Call
discrepancies to the attention of Engineer.
2.
For new equipment, use characteristics submitted under the provisions of action
submittals and information submittals for this Project.
3.
For existing equipment, whether or not relocated, obtain required electrical distribution
system data by field investigation and surveys, conducted by qualified technicians and
engineers.
B.
Gather and tabulate the following input data to support coordination study. Comply with
recommendations in IEEE 1584 and NFPA 70E as to the amount of detail that is required to be
acquired in the field. Field data gathering shall be under the direct supervision and control of the
engineer in charge of performing the study, and shall be by the engineer or its representative
who holds NETA ETT Level III certification or NICET Electrical Power Testing Level III
certification.
1.
Product Data for overcurrent protective devices specified in other Sections and involved
in overcurrent protective device coordination studies. Use equipment designation tags
that are consistent with electrical distribution system diagrams, overcurrent protective
device submittals, input and output data, and recommended device settings.
2.
Obtain electrical power utility impedance at the service.
3.
Power sources and ties.
4.
For transformers, include kVA, primary and secondary voltages, connection type,
impedance, X/R ratio, taps measured in per cent, and phase shift.
5.
For reactors, provide manufacturer and model designation, voltage rating and
impedance.
6.
For circuit breakers and fuses, provide manufacturer and model designation. List type of
breaker, type of trip and available range of settings, SCCR, current rating, and breaker
settings.
7.
Generator short-circuit current contribution data, including short-circuit reactance, rated
kVA, rated voltage, and X/R ratio.
8.
For relays, provide manufacturer and model designation, current transformer ratios,
potential transformer ratios, and relay settings.
9.
Busway manufacturer and model designation, current rating, impedance, lengths, and
conductor material.
10.
Motor horsepower and NEMA MG 1 code letter designation.
11.
Low-voltage cable sizes, lengths, number, conductor material and conduit material
(magnetic or nonmagnetic).
12.
Medium-voltage cable sizes, lengths, conductor material, and cable construction and
metallic shield performance parameters.
3.5
LABELING
A.
Apply one arc-flash label for 911 panelboards and disconnects and for each of the following
locations:
1.
Motor-control center.
2.
Low-voltage switchboard.
3.
Switchgear.
4.
Control panel.
Section 26 05 74
Overcurrent Protective Device Arc-Flash Study
3.6
3.7
Install the arc-fault warning labels under the direct supervision and control of the Arc-Flash
Study Specialist.
DEMONSTRATION
A.
Engage the Arc-Flash Study Specialist to train Owner's maintenance personnel in the potential
arc-flash hazards associated with working on energized equipment and the significance of the
arc-flash warning labels.
END OF SECTION
Section 26 05 74
Overcurrent Protective Device Arc-Flash Study
SUMMARY
A.
Related Sections:
1.
General Instrumentation and Control.
B.
Definitions, Symbols, Definitions, and Abbreviations: All symbols, definitions and engineering
unit abbreviations utilized shall conform to IEEE 100-84, S50.1 and S51.1, where applicable.
C.
System Description
1.2
PATENTS
A.
1.3
If the manufacturer is required or desires to use any design, device, material, or process
covered by letter, patent, or copyright, the manufacturer shall provide for such use by suitable
legal agreement with the patentee or owner, and the prices bid hereunder shall, without
exception, indemnify and save the Owner and Engineer from any and all claims for infringement
by reason of the use of any such patented design, device, material, or process, or any
trademark or copyright used in connection with any equipment to be furnished hereunder.
SUBMITTALS
A.
1.4
A.
Storage and Protection: Delivery, storage, and handling shall be in accordance with
manufacturers recommendation and other sections herein.
PART 2 - PRODUCTS
2.1
All fiber optic connectors shall be type ST. All connectors on equipment and cables shall be fully
compatible.
B.
Number cables and connect each cable to its numbered port on the indicated switch.
Section 26 09 43
Fiber Optic Network
2.2
Fiber optic cable shall be industrial grade, extended performance. The cable shall consist of 12
fibers with 62.5-micron core and 125-micron cladding and shall be suitable for multimode
operation at 850 and 1300 nanometers. Acceptable losses for multimode fiber lengths with
connector pairs at each end shall not be greater than 3.75 dB/km at 850 nm and 1.5dB/kM at
1300nm. Cable shall be rated for installation in harsh environments such as direct burial, aerial
lashing, and conduit and pathways that are subject to wide temperature variations. Cable shall
be plenum rated. Cable shall comply with ANSI/TIA/EIA-568-B including all addendums for fiber
optic cable performance specifications.
B.
The cable shall be suitable for the installation as certified by the fiber optic interface
manufacturer and proven by test results. Fiber optic cable shall be supplied in continuous
lengths between patch panels. Cable shall be as manufactured by Phoenix Digital or Optical
Cable Corporation or Siecor or Lucent or Berk-Tek or equal.
2.3
Patch panel shall be a wall mountable enclosure specifically designed for fiber optic cable
termination and distribution. Cabinet shall be constructed of metal and shall include cable strain
relief and radius limiting, buffer tube fan-out kits, space for a splice tray holder, and capacity for
24 ST connectors.
B.
Install patch panel in control panel. Terminate into ST connectors the two fibers required at
each location. Terminate and jumper each fiber that continues on to another location.
C.
2.4
Fiber optic patch cords shall be duplex ST to ST cords with two tight buffered 62.5/125 multimode strands. Patch cords must comply with ANSI/EIA/TIA standards. Provide Ortronics or
Lucent or Amp or Molex Premise or NORDX/CDT or Panduit or Siemon or equal.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Provide and install fiber optic cable, connectors, transceivers and converters, network cable,
connectors, hubs and network switches to interconnect the PLCs. Fiber optic materials and
equipment shall be installed, tested and terminated by experienced fiber optic system
personnel.
B.
Cable shall be carefully installed and professionally terminated. Submit credentials and a
sample of fiber termination technician. All terminations shall be compatible with the terminal and
communicating equipment. Fiber optic cable shall be installed in underground concrete encased
conduit. Network cable shall be installed in interior locations in conduit.
C.
Fiber Optic splices are not desired or permitted except in unavoidable circumstances. In the
event of fiber optic cable damage exterior splices shall be made in handholes at no additional
cost to the Owner and at the contractors risk. The losses due to the splice shall not exceed
0.2dB per mechanical splice. No more than 1 set of splices shall be allowed in a run. The
Contractor shall protect exposed ends of cable during construction. Network cable shall not be
spliced.
Section 26 09 43
Fiber Optic Network
D.
All required splicing materials shall be included with the fiber optic cable and shall meet the
requirements of the terminal and communicating devices, transceivers and media converters
and the fiber optical cable manufacturers specifications.
E.
Fiber Optic Cable with connectors on each fiber strand shall be coiled in each Control Panel
with 5 feet minimum slack ready for immediate use.
F.
Cable Testing: The fiber optic cable shall be tested at the factory and at the job site before and
after installation. Provide docket of shipment report with attenuation test results to the engineer
prior to installation. These tests shall be signed, dated and immediately transmitted to the
Engineer. Category 5 cable shall be third party verified to TIA/EIA 568-A Category 5.
G.
OTDR Tests: This test shall utilize an OTDR test instrument with signature trace printout
capability and shall document the end-to-end attenuation for fiber, connectors and mechanical
splices (if any).
H.
Site acceptance test: While cable is still on the reel as delivered to the site, prior to installation
submit printed, signed and dated results of on-site, on-reel OTDR attenuation test of each fiber
strand. Verify Category 5 cable performance with 100MHz test set.
I.
Post installation test: Following installation of fiber cable and termination of all strands submit
results of on-site attenuation test of each terminated fiber strand. Tests shall be performed with
an OTDR test instrument with printout capability. Test each terminated Category 5 cable with
100MHz test set.
J.
All cable with attenuation results lower than acceptable limits shall be removed and replaced at
no additional cost to the Owner.
K.
Fiber optic and network devices installation: Modems and connecting cables shall be
preconfigured at the factory for the application. No modem field settings, programming or
adapters shall be required
L.
Fiber Optic Cable Installation: Fiber optic cable installation and termination shall be
accomplished by technicians skilled and experienced in the type work indicated. Experience
shall include 5 years of installation experience with proper training in use of the tools and
equipment recommended by the fiber optic cable manufacturer for installation and termination in
an approved manner. The installer shall have test equipment available to demonstrate that the
completed installation complies with the specified bandwidth and transmission parameters. A
licensed electrical or specialty controls contractor in the State of Oklahoma shall perform this
work.
3.2
DEMONSTRATION
A.
Section 26 09 43
Fiber Optic Network
4.
The Contractor will be allowed two attempts at successfully completing the Final
Acceptance Test. After that time, the Contractor will become responsible to reimburse
the Owner for liquidated damages.
B.
Service: Manufacturers shall provide as part of the equipment cost sufficient days of service by
a factory-trained service engineer specifically trained on the type equipment herein specified to
assist the Contractor during installation and start-up. The service time shall be sufficient to
place the units in satisfactory service and instruct the Owners personnel in proper operation
and maintenance of the equipment.
C.
Maintenance Instruction: Operating and maintenance instructions, along with a separate parts
list, shall be furnished in three (3) copies to the Owner. Operating instructions shall also
incorporate a functional description of the system, including the system schematics which reflect
"as-built" modifications. Maintenance requirements particular to the system shall be clearly
defined, along with calibration and test procedures.
D.
Warranty:
All equipment and workmanship furnished under this contract shall be
guaranteed to be free of defects in materials and workmanship for a period of one (1) year from
and after the date of final acceptance of the work by the Owner, and any such defects which
appear within the stipulated guaranty period shall be repaired, replaced or made good without
charge. This guarantee shall include the capacity and integrated performance of the
components parts.
END OF SECTION
Section 26 09 43
Fiber Optic Network
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
This Section includes the following types of dry-type transformers rated 600 V and less, with
capacities up to 1000 kVA:
1.
Dry-Type distribution transformers.
SUBMITTALS
A.
Product Data: Include rated nameplate data, capacities, weights, dimensions, minimum
clearances, installed devices and features and performance for each type and size of
transformer indicated.
B.
Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required
clearances, method of field assembly, components and location and size of each field
connection.
1.
Wiring Diagrams: Power, signal and control wiring.
C.
D.
E.
F.
Operation and Maintenance Data: For transformers to include in emergency, operation and
maintenance manuals.
1.4
QUALITY ASSURANCE
A.
Testing Agency Qualifications: An independent agency, with the experience and capability to
conduct the testing indicated, that is a nationally recognized testing laboratory (NRTL) as
defined by OSHA in 29 CFR 1910.7.
B.
Source Limitations: Obtain each transformer type through one source from a single
manufacturer.
C.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction and marked for
intended use.
D.
Comply with IEEE C57.12.91, Test Code for Dry-Type Distribution and Power Transformers.
1.5
Section 26 22 00
Low Voltage Transformers
not energized and when transformer is not in a space that is continuously under normal control
of temperature and humidity.
1.6
COORDINATION
A.
Coordinate size and location of concrete bases with actual transformer provided. Cast anchorbolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in
Division 03. Construct housekeeping pad for floor mounted transformers.
B.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
A.
B.
C.
2.3
DISTRIBUTION TRANSFORMERS
A.
Comply with NEMA ST 20, and list and label as complying with UL 1561.
B.
C.
D.
Taps for Transformers 7.5 to 24 kVA: Two 5 percent taps below rated voltage.
E.
Taps for Transformers 25 kVA and Larger: Two 2.5 percent taps above and two 2.5 percent
taps below normal full capacity.
F.
G.
H.
Electrostatic Shielding: Each winding shall have an independent, single full-width copper
electrostatic shield arranged to minimize interwinding capacitance.
Section 26 22 00
Low Voltage Transformers
1.
2.
3.
Arrange coil leads and terminal strips to minimize capacitive coupling between input and
output terminals.
Include special terminal for grounding the shield.
Shield Effectiveness:
a.
Capacitance between Primary and Secondary windings: Not to exceed 33
picofarads over a frequency range of 20 Hz to 1 MHz.
b.
Common-Mode Noise Attenuation: Minimum of minus 120 dBA at 0.5 to 1.5 kHz;
minimum of minus 65 dBA at 1.5 to 100 kHz.
c.
Normal-Mode Noise Attenuation: Minimum of minus 52 dBA at 1.5 to 10 kHz.
I.
J.
2.4
IDENTIFICATION DEVICES
A.
2.5
A.
B.
Factory Sound-Level Tests: Conduct sound-level tests on equipment for this Project.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine conditions for compliance with enclosure and ambient temperature requirements for
each transformer.
B.
Verify that field measurements are as needed to maintain working clearances required by NFPA
70 and manufacturers written instructions.
C.
Examine walls, floors, roofs, and concrete bases for suitable mounting conditions where
transformers will be installed.
D.
Verify that ground connections are in place and requirements in Division 16 Section Grounding
and Bonding for Electrical systems have been met. Maximum ground resistance shall be 5
ohms at location of transformer.
E.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
Install wall-mounting transformers level and plumb with wall brackets fabricated by transformer
manufacturer.
B.
C.
Section 26 22 00
Low Voltage Transformers
3.3
CONNECTIONS
A.
Ground equipment according to Division 26 Section Grounding and Bonding for Electrical
Systems.
B.
Connect wiring according to Division 26 Section Low-Voltage Electrical Power Conductors and
Cables.
3.4
B.
C.
Remove and replace units that do not pass tests or inspections and retest as specified above.
D.
Test Labeling: On completion of satisfactory testing of each unit, attach a dated and signed
Satisfactory Test label to tested component.
3.5
ADJUSTING
A.
Monitor transformer secondary voltage at each unit for at least 2 hours of typical occupancy
period. Adjust transformer taps to provide optimum voltage conditions at secondary terminals.
Optimum is defined as not exceeding nameplate voltage plus 10 percent and not being lower
than nameplate voltage minus 3 percent at maximum load conditions. Submit recording and tap
settings as test results.
B.
Output Settings Report: Prepare a written report recording output voltages and tap settings.
3.6
CLEANING
A.
Vacuum dirt and debris; do not use compressed air to assist in cleaning.
END OF SECTION
Section 26 22 00
Low Voltage Transformers
SECTION 26 24 13 - SWITCHBOARDS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Service and distribution switchboards rated 600 V and less.
PERFORMANCE REQUIREMENTS
A.
1.4
A.
Product Data: For each type of switchboard, overcurrent protective device, transient voltage
suppression device, ground-fault protector, accessory, and component indicated. Include
dimensions and manufacturers technical data on features, performance, electrical
characteristics, ratings, accessories, and finishes.
B.
C.
D.
Section 26 24 13
Switchboards
2.
3.
E.
F.
Operation and Maintenance Data: For switchboards and components to include in emergency,
operation, and maintenance manuals. In addition to items specified in Division 01 Section
"Operation and Maintenance Data," include the following:
1.
Routine maintenance requirements for switchboards and all installed components.
2.
Manufacturers written instructions for testing and adjusting overcurrent protective
devices.
3.
Time-current coordination curves for each type and rating of overcurrent protective
device included in switchboards. Submit on translucent log-log graft paper; include
selectable ranges for each type of overcurrent protective device.
1.5
QUALITY ASSURANCE
A.
B.
C.
D.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
E.
F.
G.
1.6
1.7
Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate
and describe mounting and anchorage provisions.
Detailed description of equipment anchorage devices on which the certification is based
and their installation requirements.
Deliver switchboards in sections or lengths that can be moved past obstructions in delivery
path.
B.
Remove loose packing and flammable materials from inside switchboards and install temporary
electric heating (250W per section) connect factory-installed space heaters to temporary
electrical service to prevent condensation.
C.
Section 26 24 13
Switchboards
A.
Installation Pathway: Remove and replace access fencing, doors, lift-out panels, and structures
to provide pathway for moving switchboards into place.
B.
Environmental Limitations:
1.
Do not deliver or install switchboards until spaces are enclosed and weathertight, wet
work in spaces is complete and dry, work above switchboards is complete, and
temporary HVAC system is operating and maintaining ambient temperature and humidity
conditions at occupancy levels during the remainder of the construction period.
2.
Rate equipment for continuous operation under the following conditions unless otherwise
indicated:
a.
Ambient Temperature: Not exceeding 104 deg F (40 deg C).
b.
Altitude: Not exceeding 6600 feet (2000 m).
C.
D.
Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by
Owner or others unless permitted under the following conditions and then only after arranging to
provide temporary electric service according to requirements indicated:
1.
Notify Owner no fewer than seven days in advance of proposed interruption of electric
service.
2.
Indicate method of providing temporary electric service.
3.
Do not proceed with interruption of electric service without Owners written permission.
4.
Comply with NFPA 70E.
1.8
COORDINATION
A.
Coordinate layout and installation of switchboards and components with other construction that
penetrates walls or is supported by them, including electrical and other types of equipment,
raceways, piping, encumbrances to workspace clearance requirements, and adjacent surfaces.
Maintain required workspace clearances and required clearances for equipment access doors
and panels.
B.
Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchorbolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in
Division 03.
1.9
WARRANTY
A.
PART 2 - PRODUCTS
2.1
MANUFACTURED UNITS
A.
B.
Section 26 24 13
Switchboards
2.
3.
C.
D.
E.
Seismic Requirements: Fabricate and test switchboards according to IEEE 344 to withstand
seismic forces at the project location."
F.
G.
Enclosure Finish for Indoor Units: Factory-applied finish in manufacturers standard gray finish
over a rust-inhibiting primer on treated metal surface.
H.
I.
Insulation and isolation for main bus of main section and main and vertical buses of feeder
sections.
J.
K.
Bus Transition and Incoming Pull Sections: Matched and aligned with basic switchboard.
L.
M.
N.
Buses and Connections: Three phase, four wire unless otherwise indicated.
1.
Phase- and Neutral-Bus Material: Hard-drawn copper of 98 percent conductivity, with tinplated aluminum or copper feeder circuit-breaker line connections.
2.
Load Terminals: Insulated, rigidly braced, runback bus extensions, of same material as
through buses, equipped with compression connectors for outgoing circuit conductors.
Provide load terminals for future circuit-breaker positions at full-ampere rating of circuitbreaker position.
3.
Ground Bus: 1/4-by-1-inch or the minimum-size required by UL 891, hard-drawn copper
of 98 percent conductivity, equipped with compression connectors for feeder and branchcircuit ground conductors. For busway feeders, extend insulated equipment grounding
cable to busway ground connection and support cable at intervals in vertical run.
Section 26 24 13
Switchboards
4.
5.
O.
Main Phase Buses and Equipment Ground Buses: Uniform capacity for entire length of
switchboards main and distribution sections. Provide for future extensions from both
ends.
Neutral Buses: 100 percent of the ampacity of phase buses unless otherwise indicated,
equipped with compression connectors for outgoing circuit neutral cables. Brace bus
extensions for busway feeder neutral bus.
Future Devices: Equip compartments with mounting brackets, supports, bus connections, and
appurtenances at full rating of circuit-breaker compartment.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
Examine switchboards before installation. Reject switchboards that are moisture damaged or
physically damaged.
C.
Examine elements and surfaces to receive switchboards for compliance with installation
tolerances and other conditions affecting performance of the Work.
D.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
B.
Equipment Mounting: Install floor mounted switchboards on concrete base, 4-inch (100-mm)
nominal thickness. Comply with requirements for concrete base specified in Division 03 Section
"Cast-in-Place Concrete or Miscellaneous Cast-in-Place Concrete."
1.
Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 18-inch (450-mm) centers around the full perimeter of
concrete base.
2.
For supported equipment, install epoxy-coated anchor bolts that extend through concrete
base and anchor into structural concrete floor.
3.
Place and secure anchorage devices. Use setting drawings, templates, diagrams,
instructions, and directions furnished with items to be embedded.
4.
Install anchor bolts to elevations required for proper attachment to switchboards.
C.
Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and
temporary blocking of moving parts from switchboard units and components.
D.
Comply with mounting and anchoring requirements specified in Division 26 Section "Vibration
and Seismic Controls for Electrical Systems."
E.
Operating Instructions:
Frame and mount the printed basic operating instructions for
switchboards, including control and key interlocking sequences and emergency procedures.
Fabricate frame of finished wood or metal and cover instructions with clear acrylic plastic.
Mount on front of switchboards.
F.
G.
Install overcurrent
instrumentation.
protective
devices,
transient
voltage
suppression
devices,
and
Section 26 24 13
Switchboards
1.
H.
I.
3.3
CONNECTIONS
A.
Comply with requirements for terminating feeder bus specified in Division 26 Section "Enclosed
Bus Assemblies." Drawings indicate general arrangement of bus, fittings, and specialties.
B.
Comply with requirements for terminating cable trays specified in Division 26 Section "Cable
Trays for Electrical Systems." Drawings indicate general arrangement of cable trays, fittings,
and specialties.
3.4
IDENTIFICATION
A.
B.
C.
Device Nameplates: Label each disconnecting and overcurrent protective device and each
meter and control device mounted in compartment doors with a nameplate complying with
requirements for identification specified in Division 26 Section "Identification for Electrical
Systems."
3.5
B.
C.
Section 26 24 13
Switchboards
1)
4.
D.
Switchboard will be considered defective if it does not pass tests and inspections.
E.
Prepare test and inspection reports, including a certified report that identifies switchboards
included and that describes scanning results. Include notation of deficiencies detected,
remedial action taken, and observations after remedial action.
3.6
ADJUSTING
A.
Adjust moving parts and operable components to function smoothly, and lubricate as
recommended by manufacturer.
B.
3.7
PROTECTION
A.
3.8
Temporary Heating:
Apply temporary heat, to maintain temperature according to
manufacturers written instructions, until switchboard is ready to be energized and placed into
service.
DEMONSTRATION
A.
END OF SECTION
Section 26 24 13
Switchboards
SECTION 26 24 16 - PANELBOARDS
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Distribution panelboards.
2.
Lighting and appliance branch-circuit panelboards.
PERFORMANCE REQUIREMENTS
A.
1.4
A.
Product Data: For each type of panelboard, switching and overcurrent protective device,
transient voltage suppression device, accessory, and component indicated. Include dimensions
and manufacturers' technical data on features, performance, electrical characteristics, ratings,
and finishes.
B.
C.
D.
Section 26 24 16
Panelboards
1.
2.
3.
E.
Panelboard Schedules:
balancing.
F.
Operation and Maintenance Data: For panelboards and components to include in emergency,
operation, and maintenance manuals. In addition to items specified in Division 01 Section
"Operation and Maintenance Data," include the following:
1.
Manufacturer's written instructions for testing and adjusting overcurrent protective
devices.
2.
Time-current curves, including selectable ranges for each type of overcurrent protective
device that allows adjustments.
1.5
QUALITY ASSURANCE
A.
B.
C.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
D.
A.
1.6
Remove loose packing and flammable materials from inside panelboards; install temporary
electric heating (250 W per panelboard) to prevent condensation.
B.
1.7
PROJECT CONDITIONS
A.
Environmental Limitations:
1.
Do not deliver or install panelboards until spaces are enclosed and weathertight, wet
work in spaces is complete and dry, work above panelboards is complete, and temporary
HVAC system is operating and maintaining ambient temperature and humidity conditions
at occupancy levels during the remainder of the construction period.
2.
Rate equipment for continuous operation under the following conditions unless otherwise
indicated:
a.
Ambient Temperature: Not exceeding 23 deg F (minus 5 deg C) to plus 104 deg F
(plus 40 deg C).
b.
Altitude: Not exceeding 6600 feet (2000 m).
B.
Section 26 24 16
Panelboards
C.
1.8
Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by
Owner or others unless permitted under the following conditions and then only after arranging to
provide temporary electric service according to requirements indicated:
1.
Notify Owner no fewer than two days in advance of proposed interruption of electric
service.
2.
Do not proceed with interruption of electric service without Owner's written permission.
3.
Comply with NFPA 70E.
COORDINATION
A.
Coordinate layout and installation of panelboards and components with other construction that
penetrates walls or is supported by them, including electrical and other types of equipment,
raceways, piping, encumbrances to workspace clearance requirements, and adjacent surfaces.
Maintain required workspace clearances and required clearances for equipment access doors
and panels.
B.
Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchorbolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in
Division 03.
1.9
WARRANTY
A.
PART 2 - PRODUCTS
2.1
Fabricate and test panelboards according to IEEE 344 to withstand seismic forces defined in
Division 26 Section "Vibration and Seismic Controls for Electrical Systems."
B.
C.
Section 26 24 16
Panelboards
D.
E.
Conductor Connectors: Suitable for use with conductor material and sizes.
1.
Material: Hard-drawn copper, 98 percent conductivity.
2.
Main and Neutral Lugs: Compression type.
3.
Ground Lugs and Bus-Configured Terminators: Compression type.
4.
Extra-Capacity Neutral Lugs: Rated 200 percent of phase lugs mounted on extracapacity neutral bus.
F.
Service Equipment Label: NRTL labeled for use as service equipment for panelboards or load
centers with one or more main service disconnecting and overcurrent protective devices.
G.
Future Devices:
Mounting brackets, bus connections, filler plates, and necessary
appurtenances required for future installation of devices.
H.
2.2
DISTRIBUTION PANELBOARDS
A.
B.
C.
Doors: Secured with vault-type latch with tumbler lock; keyed alike.
1.
For doors more than 36 inches (914 mm) high, provide two latches, keyed alike.
D.
E.
Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes 125 A and Smaller:
Bolt-on circuit breakers.
F.
Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes Larger Than 125 A:
Bolt-on circuit breakers; plug-in circuit breakers where individual positive-locking device requires
mechanical release for removal.
2.3
B.
C.
D.
Branch Overcurrent Protective Devices: Bolt-on circuit breakers, replaceable without disturbing
adjacent units.
Section 26 24 16
Panelboards
E.
Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike.
F.
Column-Type Panelboards: Narrow gutter extension, with cover, to overhead junction box
equipped with ground and neutral terminal buses.
2.4
B.
Molded-Case Circuit Breaker (MCCB): Comply with UL 489, with interrupting capacity to meet
available fault currents.
1.
Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads,
and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip
setting for circuit-breaker frame sizes 250 A and larger.
2.
GFCI Circuit Breakers: Single- and two-pole configurations with Class A ground-fault
protection (6-mA trip).
3.
Ground-Fault Equipment Protection (GFEP) Circuit Breakers: Class B ground-fault
protection (30-mA trip).
4.
Molded-Case Circuit-Breaker (MCCB) Features and Accessories:
a.
Standard frame sizes, trip ratings, and number of poles.
b.
Lugs: Mechanical style, suitable for number, size, trip ratings, and conductor
materials.
c.
Application Listing:
Appropriate for application; Type SWD for switching
fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity
discharge (HID) lighting circuits.
d.
Application Listing: Appropriate for application; Type HACR for breakers serving
Heating, Air Conditioning and Refrigeration (HACR) loads.
e.
Dual rated SWD and HACR breakers are acceptable.
2.5
Accessory Set: Include tools and miscellaneous items required for overcurrent protective
device test, inspection, maintenance, and operation.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
Examine panelboards before installation. Reject panelboards that are damaged or rusted or
have been subjected to water saturation.
C.
Examine elements and surfaces to receive panelboards for compliance with installation
tolerances and other conditions affecting performance of the Work.
D.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
Section 26 24 16
Panelboards
B.
C.
Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and
temporary blocking of moving parts from panelboards.
D.
Comply with mounting and anchoring requirements specified in Division 26 Section "Vibration
and Seismic Controls for Electrical Systems."
E.
Mount top of trim 90 inches (2286 mm) above finished floor unless otherwise indicated.
F.
Mount panelboard cabinet plumb and rigid without distortion of box. Mount recessed
panelboards with fronts uniformly flush with wall finish and mating with back box.
G.
Install overcurrent protective devices and controllers not already factory installed.
1.
Set field-adjustable, circuit-breaker trip ranges.
H.
I.
Stub four 1-inch (27-GRC) empty conduits from panelboard into accessible ceiling space or
space designated to be ceiling space in the future. Stub four 1-inch (27-GRC) empty conduits
into raised floor space or below slab not on grade.
J.
Arrange conductors in gutters into groups and bundle and wrap with wire ties after completing
load balancing.
K.
3.3
IDENTIFICATION
A.
B.
Create a directory to indicate installed circuit loads; incorporate Owner's final room
designations. Obtain approval before installing. Use a computer or typewriter to create
directory; handwritten directories are not acceptable.
C.
Panelboard Nameplates:
Label each panelboard with a nameplate complying with
requirements for identification specified in Division 26 Section "Identification for Electrical
Systems."
D.
Device Nameplates: Label each branch circuit device in distribution panelboards with a
nameplate complying with requirements for identification specified in Division 26 Section
"Identification for Electrical Systems."
Section 26 24 16
Panelboards
3.4
B.
C.
D.
Panelboards will be considered defective if they do not pass tests and inspections.
E.
Prepare test and inspection reports, including a certified report that identifies panelboards
included and that describes scanning results. Include notation of deficiencies detected,
remedial action taken, and observations after remedial action.
F.
ADJUSTING
G.
Adjust moving parts and operable component to function smoothly, and lubricate as
recommended by manufacturer.
H.
I.
Load Balancing: After Substantial Completion, but not more than 60 days after Final
Acceptance, measure load balancing and make circuit changes if directed by the Engineer.
1.
Measure as directed during period of normal system loading.
2.
Perform load-balancing circuit changes outside normal occupancy/working schedule of
the facility and at time directed. Avoid disrupting critical 24-hour services such as fax
machines and on-line data processing, computing, transmitting, and receiving equipment.
3.
After circuit changes, recheck loads during normal load period. Record all load readings
before and after changes and submit test records.
4.
Tolerance: Difference exceeding 20 percent between phase loads, within a panelboard,
is not acceptable. Rebalance and recheck as necessary to meet this minimum
requirement.
Section 26 24 16
Panelboards
3.5
PROTECTION
A.
END OF SECTION
Section 26 24 16
Panelboards
SECTION 26 28 13 - FUSES
PART 1 - GENERAL
1.1
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Cartridge fuses rated 600-V ac and less for use in control circuits, enclosed switches,
controllers and motor-control centers.
SUBMITTALS
A.
Product Data: For each type of product indicated. Include construction details, material,
dimensions, descriptions of individual components and finishes for spare-fuse cabinets. Include
the following for each fuse type indicated:
1.
Ambient Temperature Adjustment Information: If ratings of fuses have been adjusted to
accommodate ambient temperatures, provide list of fuses with adjusted ratings.
a.
For each fuse having adjusted ratings, include location of fuse, original fuse rating,
local ambient temperature, and adjusted fuse rating.
b.
Provide manufacturers technical data on which ambient temperature adjustment
calculations are based.
2.
Dimensions and manufacturers technical data on features, performance, electrical
characteristics and ratings.
B.
Operation and Maintenance Data: For fuses to include in emergency, operation, and
maintenance manuals. In addition to items specified in Division 01 Section Operation and
Maintenance Data, include the following:
1.
Ambient temperature adjustment information.
2.
Current-limitation curves for fuses with current-limiting characteristics.
1.4
QUALITY ASSURANCE
A.
Source Limitations: Obtain fuses, for use within a specific product or circuit, from single source
from single manufacturer.
B.
Electrical Components, Devices and Accessories: Listed and labeled as defined in NFPA 70, by
a qualified testing agency and marked for intended location and application.
C.
D.
1.5
COORDINATION
A.
Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size
and with system short-circuit current levels.
Section 26 28 13
Fuses
1.6
EXTRA MATERIALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than
two of each size and type.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
A.
Characteristics: NEMA FU 1, nonrenewable cartridge fuses with voltage ratings consistent with
circuit voltages.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine fuses before installation. Reject fuses that are moisture damaged or physically
damaged.
B.
Examine holders to receive fuses for compliance with installation tolerances and other
conditions affecting performance, such as rejection features.
C.
Examine utilization equipment nameplates and installation instructions. Install fuses of sizes and
with characteristics appropriate for each piece of equipment.
D.
Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to
fuse ratings.
E.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
FUSE APPLICATIONS
A.
3.3
Cartridge Fuses:
1.
Feeders: Class L, fast acting Class RK1or fast acting Class RK5.
2.
Motor Branch Circuits: Class RK1, time delay.
3.
Control Circuits: Class CC, fast acting.
INSTALLATION
A.
Install fuses in fusible devices. Arrange fuses so rating information is readable without removing
fuse.
Section 26 28 13
Fuses
3.4
IDENTIFICATION
A.
Install labels complying with requirements for identification specified in Division 26 Section
Identification for Electrical Systems and indicating fuse replacement information on inside door
of each fused switch and adjacent to each fuse block, socket and holder.
END OF SECTION
Section 26 28 13
Fuses
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and other Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Fusible switches.
2.
Nonfusible switches.
3.
Molded-case circuit breakers (MCCBs).
4.
Molded-case switches.
5.
Enclosures.
SUBMITTALS
A.
Product Data: For each type of enclosed switch, circuit breaker, accessory, and component
indicated. Include dimensioned elevations, sections, weights and manufacturers technical data
on features, performance, electrical characteristics, ratings, accessories and finishes.
1.
Enclosure types and details for all types indicated, including NEMA 250, Type 1.
2.
Current and voltage ratings.
3.
Short-circuit current ratings (interrupting and withstand, as appropriate).
4.
Include evidence of Nationally Recognized Testing Laboratory listing for series rating of
installed devices.
5.
Detail features, characteristics, ratings, and factory settings of individual overcurrent
protective devices, accessories, and auxiliary components.
B.
Shop Drawings: For enclosed switches and circuit breakers. Include plans, elevations, sections,
details, and attachments to other work.
1.
Wiring Diagrams: for power, signal, and control wiring.
C.
D.
E.
Operation and Maintenance Data: For enclosed switches and circuit breakers to include in
emergency, operation, and maintenance manuals. In addition to items specified in Division 01
Section Operation and Maintenance Data, include the following:
1.
Manufacturers written instructions for testing and adjusting enclosed switches and circuit
breakers.
1.4
QUALITY ASSURANCE
A.
Source Limitations: Obtain enclosed switches and circuit breakers, overcurrent protective
devices, components, and accessories, within same product category from single manufacturer.
Section 26 28 16
Enclosed Switches and Circuit Breakers
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
C.
1.5
COORDINATION
A.
1.6
Coordinate layout and installation of switches, circuit breakers, and components with equipment
served and adjacent surfaces. Maintain required workspace clearances and required
clearances for equipment access doors and panels.
EXTRA MATERIALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than
three of each size and type.
2.
Fuse Pullers: Two for each size and type.
PART 2 - PRODUCTS
2.1
FUSIBLE SWITCHES
A.
B.
Type HD, Heavy Duty, Single Throw, 600-V ac, 1200 A and Smaller: UL98 and NEMA KS 1,
horsepower rated, with clips or bolt pads to accommodate fuses, lockable handle with capability
to accept three padlocks, and interlocked with cover in closed position.
C.
Accessories:
1.
Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground
conductors.
2.
Neutral Kit: Internally mounted; insulated, capable of being grounded and bonded;
labeled for copper and aluminum neutral conductors.
3.
Class R Fuse Kit: Provides rejection of other fuse types when Class R fuses are
specified.
4.
Lugs: Mechanical type, suitable for number, size and conductor material.
2.2
NONFUSIBLE SWITCHES
A.
B.
Type HD, Heavy Duty, Single Throw, 600-V ac, 1200 A and Smaller: UL 98 and NEMA KS 1,
horsepower rated, lockable handle with capability to accept three padlocks, and interlocked with
cover in closed position.
C.
Accessories:
1.
Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground
conductors.
Section 26 28 16
Enclosed Switches and Circuit Breakers
2.
2.3
Neutral Kit: Internally mounted; insulated, capable of being grounded and bonded;
labeled for copper and aluminum neutral conductors.
B.
General Requirements: Comply with UL 489, NEMA AB 1, and NEMA AB 3, with interrupting
capacity to comply with available fault currents.
C.
Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads and
instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for
circuit-breaker frame sizes 250 A and larger.
D.
2.4
MOLDED-CASE SWITCHES
A.
B.
General Requirements: MCCB with fixed, high-set instantaneous trip only, and short-circuit
withstand rating equal to equivalent breaker frame size interrupting rating.
C.
2.5
ENCLOSURES
A.
Enclosed Switches and Circuit Breakers: NEMA AB 1, NEMA KS 1, NEMA 250, and UL 50, to
comply with environmental conditions at installed location.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Examine elements and surfaces to receive enclosed switches and circuit breakers for
compliance with installation tolerances and other conditions affecting performance of the Work.
B.
Proceed with installation only after unsatisfactory conditions have been corrected.
3.2
INSTALLATION
A.
Install individual wall-mounted switches and circuit breakers with tops at uniform height unless
otherwise indicated.
B.
Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and
temporary blocking of moving parts form enclosures and components.
Section 26 28 16
Enclosed Switches and Circuit Breakers
C.
D.
3.3
IDENTIFICATION
A.
3.4
A.
B.
C.
D.
Enclosed switches and circuit breakers will be considered defective if they do not pass tests and
inspections.
E.
Prepare test and inspection reports, including a certified report that identifies enclosed switches
and circuit breakers. Include notation of deficiencies detected, remedial action taken and
observations after remedial action.
3.5
ADJUSTING
A.
Adjust moving parts and operable components to function smoothly, and lubricate as
recommended by manufacturer.
END OF SECTION
Section 26 28 16
Enclosed Switches and Circuit Breakers
SUMMARY
A.
Section includes
1.
Solid State Reduced Voltage Controller
B.
Related Sections
1.
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2
QUALIFICATIONS
A.
Manufacturer
1.
The manufacturer shall have a minimum of 15 years experience in the manufacturer of
solid state reduced voltage controllers.
B.
Support
1.
The manufacturer shall maintain factory trained and authorized service facilities within
100 miles of the project and shall have a demonstrated record of service for at least the
previous ten years.
2.
Support personnel are to be direct employees of the manufacturer.
3.
The manufacturer shall provide all required start-up and training services.
C.
Certification
1.
To ensure all quality and corrective action procedures are documented and implemented
all manufacturing locations shall be certified to the ISO-9001 Series of Quality Standards.
2.
Third party manufacturers and brand labeling shall not be allowed.
1.3
REFERENCES
A.
B.
EN
1.
2.
3.
4.
5.
6.
C.
1.4
IEC
UL
CSA
NEMA
IEEE
VDE
A.
B.
Maintain area free of dirt and dust during and after installation of products
Section 26 29 33
Solid State Reduced Voltage Starters
1.5
PRE-MANUFACTURE SUBMITTALS
A.
B.
Shop Drawings
1.
Elevation drawings showing dimensional information
2.
Structure Descriptions showing
a.
Enclosure ratings
b.
Fault ratings
c.
Other information as required for approval
3.
Conduit locations
4.
Unit Descriptions including amperage ratings, frame sizes, trip settings, pilot devices, etc.
5.
Nameplate Information
6.
Schematic wiring diagrams
C.
Product Data
1.
Publications on solid state reduced voltage controller.
2.
Data Sheets and Publications on all major components
a.
Contactors
b.
Circuit Breaker and Fuse information including time current characteristics
c.
Control Power Transformers
d.
Pilot devices
e.
Relays
D.
Specification Response
1.
Detailed response to this specification showing where in the literature each requirement
is satisfied.
2.
All clarifications and exceptions must be clearly identified.
E.
1.6
CLOSEOUT SUBMITTALS
A.
B.
Contractor shall provide certification that the solid state reduced voltage controller has been
installed in accordance with the manufacturers instructions.
C.
The Contractor shall provide certification that the Contractor has properly adjusted any timing
devices required in the starting circuitry.
D.
Final Drawings. The manufacturer shall provide final drawings reflecting the As-Shipped
status of the installed equipment. The contractor shall be responsible for making any changes to
the As-Shipped drawings from the manufacturer to reflect any field modifications.
E.
Maintenance Data
1.
Solid state reduced voltage controller installation instructions and User Manual
2.
Installation / Operation instructions for major components such as circuit breakers,
contactors, etc.
3.
Parameter Listing
4.
Field Service report from start-up service
5.
Solid state reduced voltage controller spare parts listing and pricing
Section 26 29 33
Solid State Reduced Voltage Starters
6.
1.7
Include name and phone number for a local distributor for the spare parts.
B.
C.
The contractor shall protect the units from dirt, water, construction debris and traffic.
D.
During storage the contractor shall connect internal space heaters (if specified) with temporary
power.
1.8
FIELD MEASUREMENTS
A.
1.9
The Contractor shall verify all field measurements prior to the fabrication of the solid state
reduced voltage controller.
SPARE MATERIALS
A.
Provide one (1) set of (3) of each size power fuse utilized.
B.
Provide spares equal to 10 percent of the installed quantity for primary and secondary control
power fuses.
C.
Provide one (1) spare control relay for each unique relay utilized on the project.
1.10
WARRANTY
A.
The manufacturer shall provide their standard parts warranty for eighteen (18) months from the
date of shipment or twelve (12) months from the date of being energized, whichever occurs first.
B.
C.
This warranty applies only to stand alone solid state reduced voltage controllers.
PART 2 - PRODUCTS
2.1
MANUFACTURED UNITS
A.
2.2
A.
The solid state reduced voltage controller shall accept an input voltage of 480 VAC, three phase
plus or minus 10 percent
B.
Environmental Ratings
1.
Storage ambient temperature range: -20 to 75 degrees C.
2.
Operating ambient temperature range: 0 to 50 degrees C.
3.
The relative humidity range: 5% to 95% non-condensing.
4.
Operating elevation: up to 2000 Meters.
Section 26 29 33
Solid State Reduced Voltage Starters
C.
2.3
Definitions
1.
The Solid State Reduced Voltage Controller Unit shall refer to the actual controller unit
that will be mounted within the specified enclosure.
2.
The Solid State Reduced Voltage Controller System shall refer to the controller unit and
all items specified under Controller System Options.
SOLID STATE REDUCED VOLTAGE CONTROLLER UNIT DESIGN
A.
The open-type controller device shall be modular, consisting of a power structure and a logic
component.
B.
Power Structure
1.
The power structure shall include an SCR bypass.
2.
The power structure shall include a built-in overload.
3.
For ratings 1 Amps to 1250 Amps, the power structure shall consist of three power poles
with integral heatsinks.
4.
Power poles are to be modular in design that each is easily replaceable.
5.
Back-to-back SCR pairs shall be the only power switching semiconductor means
acceptable.
Diode-SCR (Silicon Controlled Rectifier) combinations shall not be
acceptable.
6.
SCRs shall have the following minimum repetitive peak inverse voltage ratings.
a.
1400V for units rated 200 to 480V
b.
1600V for units rated 200 to 600V
c.
1800V for units rated 230 to 690V
C.
Logic Component
1.
The logic component shall be a self-contained control module, compatible with the full
range of power structures. The control module shall mount directly to the power
structure.
2.
The control module shall provide digital microprocessor control and supervision of all
controller operation, including pulse firing of the SCRs.
3.
The control module shall consist of the following.
a.
Self-tuning power supply accepting control power input from 100 to 240 VAC or
24V AC/DC, 50/60 Hz.
b.
Logic control circuitry incorporating a latch circuit for three-wire control.
c.
SCR firing circuitry that incorporates an RC snubber network to prevent false firing.
d.
Input / output circuitry
e.
Digital programming keypad
f.
Backlit LCD display
g.
DPI communication port.
4.
The control module shall be easily removed from the power structure, without the need to
disassemble associated printed circuit board assemblies.
5.
The control terminals shall be easily accessible and located on the front top of the device.
The terminals shall be UL rated for 300 Volts, 10 Amps maximum and accept a maximum
of two wires rated number 18 to number 14 AWG.
2.4
Starting Modes
1.
The controller shall provide the following starting modes as standard.
a.
Soft Start with Selectable Kickstart
1) Programmable initial torque value of 0 to 90 percent of locked rotor torque
2) Programmable acceleration ramp time from 0 to 30 seconds
3) A selectable kickstart, or boost, shall be provided at the beginning of the voltage ramp. The kickstart shall provide a current pulse of 550 percent of the full
load current. The kickstart time shall be adjustable from 0 to 2 seconds.
Section 26 29 33
Solid State Reduced Voltage Starters
b.
2.
B.
LCD Display
1.
An alphanumeric, backlit LCD display shall be provided for controller set-up, diagnostics,
status and monitoring. The display shall be four-line, 16 characters minimum.
2.
Digital parameter adjustment shall be provided through a keypad. Analog potentiometer
adjustments are not acceptable.
C.
Overload Protection
1.
Shall meet applicable standards as a motor thermal protective device.
Section 26 29 33
Solid State Reduced Voltage Starters
2.
3.
4.
Shall utilize three-phase current sensing. The use of two current transformers shall be
unacceptable.
Selectable trip classes of 10, 15, 20 and 30 shall be provided as standard.
Electronic thermal memory shall provide enhanced motor protection.
D.
Digital I/O
1.
A minimum of four auxiliary contacts shall be provided for customer use.
2.
The contacts shall be rated for 240 Volts AC maximum.
3.
Contact configuration shall be programmable and contain the following configurations:
a.
Normal Operation (N.O. or N.C.)
b.
Up-to-Speed Indication (N.O. or N.C.)
c.
External Bypass
d.
Fault Indication (N.O. or N.C.)
e.
Alarm Indication (N.O. or N.C.)
f.
Network Controlled Output (N.O. or N.C.)
E.
F.
Monitoring
1.
The controller shall provide the following monitoring functions indicated through the LCD
display:
a.
Three-phase current
b.
Three-phase voltage
c.
Power in kW
d.
Power usage in kWh or mWh
e.
Power factor
f.
Motor thermal capacity usage
g.
Elapsed time
G.
Section 26 29 33
Solid State Reduced Voltage Starters
2.5
Enclosure
1.
NEMA 12 enclosure for indoor use to provide a degree of protection against dust, falling
dirt and dripping non-corrosive liquids. They shall be designed to meet drip, dust and
rust resistance tests. No ventilation openings shall be allowed.
2.
Paint: ANSI 49 Gray
3.
Unless indicated differently, provide top entry and bottom exit for power cables
4.
Provide a 6.25 x 2 door mounted white lamacoid nameplate with black letters (message
to be defined during submittal).
5.
UL Label
B.
C.
D.
Bypass Contactor
1.
A bypass contactor with overload shall be provided.
2.
The contactor shall have four N.O. auxiliary contacts.
E.
F.
Selector Switches
1.
Provide selector switches, mounted on the enclosure door, for the following operations:
a.
Local/Off/Remote mode
b.
Vibration Alarm Enable/Disable
c.
Soft Start/Off/Bypass mode
d.
Motor Start Permissive Enable/Disable
2.
The devices shall be Allen-Bradley Bulletin 800E pilot devices (22.5mm, NEMA Type
4/4X/13) mounted on the enclosure door.
G.
Pushbuttons
1.
Provide pushbuttons, mounted on the enclosure door, for the following operations:
a.
Local Start
b.
Local Stop
c.
Vibration Alarm Reset
d.
Soft Starter Fault Reset
2.
The devices shall be Allen-Bradley Bulletin 800E (22.5mm, NEMA Type 4/4X/13) pilot
devices mounted on the enclosure door.
H.
Pilot Lights
1.
Provide pilot lights, mounted on the enclosure door, for indication of:
Section 26 29 33
Solid State Reduced Voltage Starters
2.
3.
a.
Test Run Mode
b.
Motor Space Heater On
c.
Vibration Alarm Disabled
d.
Discharge Valve Closed
e.
MPR Lockout
f.
Motor Stopped
g.
Running on Soft Starter
h.
Running on Bypass
i.
Vibration Alarm
j.
Soft Starter Fault
Pilot lights shall be transformer type.
The devices shall be Allen-Bradley Bulletin 800E (22.5mm, NEMA Type 4/4X/13) pilot
devices mounted on the enclosure door.
I.
J.
PART 3 - EXECUTION
3.1
The service division of the manufacturer shall perform all start-up services. The use of third
party supplier start-up personnel is not allowed.
B.
Start-up personnel shall be direct employees of the manufacturer and shall be degreed
engineers.
C.
Provide a minimum of (2) hours of on-site start-up service for each controller (4 hours
minimum).
D.
Section 26 29 33
Solid State Reduced Voltage Starters
3.2
TRAINING
A.
B.
C.
The instruction shall include the operational and maintenance requirements of the controller.
D.
The basis of the training shall be the installed controller, the engineered drawings and the user
manual. At a minimum, the training shall:
1.
Review of the engineered drawings identifying the components shown on the drawings.
2.
Review starting / stopping options for the controller.
3.
Review operation of the Human Interface for programming and monitoring of the
controller.
4.
Review the maintenance requirements of the controller.
5.
Review safety concerns with operating the controller.
END OF SECTION
Section 26 29 33
Solid State Reduced Voltage Starters
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
A.
B.
C.
Qualification Data: For qualified Installer and manufacturer. Include data on listing or
certification by UL.
D.
E.
F.
1.4
QUALITY ASSURANCE
A.
B.
Electrical components, Devices and Accessories: Listed and labeled as defined in NFPA 780,
Definitions Article.
1.5
COORDINATION
A.
Coordinate installation of lightning protection with installation of other building systems and
components, including electrical wiring, supporting structures and building materials, metal
bodies requiring bonding to lightning protection components, and building finishes.
B.
Coordinate installation of air terminals attached to roof systems with roofing manufacturer and
Installer.
C.
Section 26 41 13
Lightning Protection for Structures
PART 2 - PRODUCTS
2.1
B.
Roof-Mounted Air Terminals: NFPA 780, Class I copper unless otherwise indicated.
1.
Manufacturers: subject to compliance with requirements, available manufacturers offering
products that may be incorporated into the Work include, but are not limited to, the
following:
a.
East Coast Lightning Equipment Inc.
b.
ERICO International Corporation.
c.
Harger.
d.
Heary Bros. Lightning Protection Co., Inc.
e.
Independent Protection Co.
f.
Preferred Lightning Protection.
g.
Robbins Lightning, Inc.
h.
Thompson Lightning Protection, Inc.
2.
Air Terminals More than 24 Inches Long: With brace attached to the terminal at not less
than half the height of the terminal.
3.
Single-membrane, Roof-Mounted, Air Terminals: Designed specifically for singlemembrane roof system materials.
C.
D.
Ground Loop Conductor: The same size and type as the main conductor except tinned.
E.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Install lightning protection components and systems according to UL 96A and NFPA 780.
B.
Install conductors with direct paths from air terminals to ground connections. Avoid sharp
bends.
C.
D.
Cable Connections: Use crimped or bolted connections for all conductor splices and
connections between conductors and other components. Use exothermic-welded connections in
underground portions of the system.
E.
Bond extremities of vertical metal bodies exceeding 60 feet in length of lightning protection
components.
F.
Ground Loop: Install ground-level, potential equalization conductor and extend around the
perimeter of structure.
1.
Bury ground ring not less than 30 inches.
2.
Bond ground terminals to the ground loop.
Section 26 41 13
Lightning Protection for Structures
3.
G.
3.2
Bond grounded building systems to the ground loop conductor within 12 feet of grade
level.
A.
Do not combine materials that can form an electrolytic couple that will accelerate corrosion in
the presence of moisture unless moisture is permanently excluded from junction of such
materials.
B.
Use conductors with protective coatings where conditions cause deterioration or corrosion of
conductors.
3.3
Notify Engineer at least 48 hours in advance of inspection before concealing lightning protection
components.
END OF SECTION
Section 26 41 13
Lightning Protection for Structures
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
Section includes field-mounted SPDs for low-voltage (120 to 600 V) power distribution and
control equipment.
B.
Related Requirements:
1.
Section 262413 "Switchboards" for factory-installed SPDs.
2.
Section 262416 "Panelboards" for factory-installed SPDs.
1.3
DEFINITIONS
A.
B.
C.
Mode(s), also Modes of Protection: The pair of electrical connections where the VPR applies.
D.
MOV: Metal-oxide varistor; an electronic component with a significant non-ohmic currentvoltage characteristic.
E.
F.
G.
H.
1.4
ACTION SUBMITTALS
A.
1.5
A.
B.
1.6
CLOSEOUT SUBMITTALS
A.
Section 26 43 13
Surge Protection for Low-Voltage Elec. Power Circuits
1.7
WARRANTY
A.
Manufacturer's Warranty: Manufacturer agrees to replace or replace SPDs that fail in materials
or workmanship within specified warranty period.
1.
Most manufacturers offer five-year extended warranties on their equipment. Verify
available warranties and warranty periods.
2.
Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1
SPD with Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency,
and marked for intended location and application.
B.
C.
D.
2.2
B.
C.
SPDs: Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying
with UL 1449, Type 1.
1.
SPDs with the following features and accessories:
a.
b.
c.
a.
b.
D.
E.
Peak Surge Current Rating: The minimum single-pulse surge current withstand rating per phase
shall not be less than 200kA. The peak surge current rating shall be the arithmetic sum of the
ratings of the individual MOVs in a given mode.
F.
Protection modes and UL 1449 VPR for grounded wye circuits with 480Y/277 V, three-phase,
four-wire circuits shall not exceed the following:
1.
2.
Section 26 43 13
Surge Protection for Low-Voltage Elec. Power Circuits
3.
G.
Protection modes and UL 1449 VPR for 240/120 V, single-phase, three-wire circuits shall not
exceed the following:
1.
Line to Neutral: 700 V.
2.
Line to Ground: 700 V.
3.
Line to Line: 1000 V.
H.
I.
2.3
ENCLOSURES
A.
B.
2.4
Power Wiring: Same size as SPD leads, complying with Section 260519 "Low-Voltage Electrical
Power Conductors and Cables."
PART 3 - EXECUTION
3.1
INSTALLATION
A.
B.
Install an OCPD or disconnect as required to comply with the UL listing of the SPD.
C.
Install SPDs with conductors between suppressor and points of attachment as short and
straight as possible, and adjust circuit-breaker positions to achieve shortest and straightest
leads. Do not splice and extend SPD leads unless specifically permitted by manufacturer. Do
not exceed manufacturer's recommended lead length. Do not bond neutral and ground.
D.
Use crimped connectors and splices only. Wire nuts are unacceptable.
E.
Wiring:
1.
Power Wiring: Comply with wiring methods in Section 260519 "Low-Voltage Electrical
Power Conductors and Cables."
2.
Controls: Comply with wiring methods in Section 260519 "Low-Voltage Electrical Power
Conductors and Cables."
3.2
Perform the following tests and inspections with the assistance of a factory-authorized service
representative.
1.
Compare equipment nameplate data for compliance with Drawings and Specifications.
2.
Inspect anchorage, alignment, grounding, and clearances.
3.
Verify that electrical wiring installation complies with manufacturer's written installation
requirements.
B.
An SPD will be considered defective if it does not pass tests and inspections.
Section 26 43 13
Surge Protection for Low-Voltage Elec. Power Circuits
C.
3.3
A.
B.
Do not perform insulation-resistance tests of the distribution wiring equipment with SPDs
installed. Disconnect SPDs before conducting insulation-resistance tests, and reconnect them
immediately after the testing is over.
C.
Energize SPDs after power system has been energized, stabilized, and tested.
3.4
DEMONSTRATION
A.
END OF SECTION
Section 26 43 13
Surge Protection for Low-Voltage Elec. Power Circuits
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
1.3
Section Includes:
1.
Interior lighting fixtures, lamps, and ballasts.
2.
Emergency lighting units.
3.
Exit signs.
4.
Lighting fixture supports.
DEFINITIONS
A.
B.
C.
D.
E.
F.
1.4
SUBMITTALS
A.
Product Data: For each type of lighting fixture, arranged in order of fixture designation. Include
data on features, accessories, finishes and the following:
1.
Physical description of lighting fixture including dimensions.
2.
Emergency lighting units including battery and charger.
3.
Ballast, including BF.
4.
Energy-efficiency data.
5.
Life, output (lumens, CCT, and CRI) and energy-efficiency data for lamps.
6.
Photometric data and adjustment factors based on laboratory tests, complying with
IESNA Lighting Measurements Testing & Calculation Guides, of each lighting fixture type.
The adjustment factors shall be for lamps, ballasts and accessories identical to those
indicated for the lighting fixture as applied in this Project.
a.
Manufacturer Certified Data: Photometric data shall be certified by a
manufacturers laboratory with a current accreditation under the National Voluntary
Laboratory Accreditation Program for Energy efficient Lighting Products.
B.
Installation instructions.
C.
Qualification Data: For qualified agencies providing photometric data for lighting fixtures.
D.
Product Certificates: For each type of ballast for bi-level and dimmer-controlled fixtures, from
manufacturer.
Section 26 51 00
Interior Lighting
E.
F.
Operation and Maintenance Data: For lighting equipment and fixtures to include in emergency,
operation and maintenance manuals.
1.
Provide a list of all lamp types used on Project; use ANSI and manufacturers codes.
G.
1.5
QUALITY ASSURANCE
A.
B.
Electric Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by
a qualified testing agency and marked for intended location and application.
C.
1.6
COORDINATION
A.
1.7
Coordinate layout and installation of lighting fixtures and suspension system with other
construction that penetrates ceilings or is supported by them, including HVAC equipment, firesuppression system and partition assemblies.
WARRANTY
A.
1.8
Special Warranty for Emergency Lighting Batteries: Manufacturers standard form in which
manufacturer of battery powered emergency lighting unit agrees to repair or replace
components of rechargeable batteries that fail in materials or workmanship within specified
warranty period.
1.
Warranty Period for Emergency Lighting Unit Batteries: 10 years from date of Substantial
Completion. Full warranty shall apply for first year, and prorated warranty for the
remaining nine years.
2.
Warranty Period for Emergency Fluorescent Ballast and Self-Powered Exit Sign
Batteries: Seven years from date of Substantial Completion. Full warranty shall apply for
first year, and prorated warranty for the remaining six years.
EXTRA MATERIALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
Lamps: 10 for every 100 Insert quantity of each type and rating installed. Furnish at least
one of each type.
2.
Plastic Diffusers and Lenses: One for every 100 of each type and rating installed. Furnish
at least one of each type.
3.
Fluorescent-fixture-mounted, emergency battery pack: One for every 20 emergency
lighting unit.
4.
Ballasts: One for every 100 of each type and rating installed. Furnish at least one of each
type.
5.
Globes and Guards: One for every 20 of each type and rating installed. Furnish at least
one of each type.
Section 26 51 00
Interior Lighting
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
Products: Subject to compliance with requirements, available products that may be incorporated
into the Work include, but are not limited to, product(s) indicated on Drawings.
GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS
A.
B.
Sheet Metal Components: Steel unless otherwise indicated. Form and support to prevent
warping and sagging.
C.
Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under
operating conditions and designed to permit relamping without use of tools. Designed to prevent
doors, frames, lenses, diffusers, and other components from falling accidentally during
relamping and when secured in operating position.
D.
E.
Factory-Applied Labels: Comply with UL 1598. Include recommended lamps and ballasts.
Labels shall be located where they will be readily visible to service personnel, but not seen from
normal viewing angles when lamps are in place.
1.
Label shall include the following lamp and ballast characteristics:
a.
USE ONLY and include specific lamp type.
b.
Lamp diameter code (T-4, T-5, T-8, T-12, etc), tube configuration (twin, quad,
triple, etc.), base type, and nominal wattage for fluorescent and compact
fluorescent luminaires.
c.
Lamp type, wattage, bulb type (ED17, BD56, etc.) and coating (clear or coated) for
HID luminaires.
d.
Start type (preheat, rapid start, instant start, etc.) for fluorescent and compact
fluorescent lunimaires.
e.
ANSI ballast type (M98, M57, etc.) for HID luminaires.
f.
CCT and CRI for all luminaires.
2.3
Section 26 51 00
Interior Lighting
B.
Electronic Programmed Start Ballasts for T5 and T8 Lamps: comply with ANSI C82.11 and the
following:
1.
Lamp end-of-life detection and shutdown circuit for T5 diameter lamps.
2.
Automatic lamp starting after lamp replacement.
C.
Electromagnetic Ballasts: Comply with ANSI C82.1; energy saving, high-power factor, Class P,
and having automatic-reset thermal protection.
1.
Ballast Manufacturer Certification: Indicated by label.
D.
E.
2.4
2.5
Description: Electronic-programmed rapid-start type, complying with UL 935 and with ANSI
C82.11, designed for type and quantity of lamps indicated. Ballast shall be designed for full light
output unless dimmer or bi-level control is indicated:
1.
Lamp end-of-life detection and shutdown circuit.
2.
Automatic lamp starting after lamp replacement.
3.
Sound Rating: Class A.
4.
Total Harmonic Distortion Rating: Less than 20 percent.
5.
Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or better.
6.
Operating Frequency: 20 kHz or higher.
7.
Lamp Current Crest Factor: 1.7 or less.
8.
BF: 0.95 or higher unless otherwise indicated.
9.
Power Factor: 0.95 or higher.
EMERGENCY FLUORESCENT POWER UNIT
A.
2.6
Internal Type: Self-contained, modular, battery-inverter unit, factory mounted within lighting
fixture body and compatible with ballast. Comply with UL 924.
1.
Emergency Connection: Operate one fluorescent lamp(s) continuously at an output of
1100 lumens each. Connect unswitched circuit to battery-inverter unit and switched
circuit to fixture ballast.
2.
Test Push Button and Indicator Light: Visible and accessible without opening fixture or
entering ceiling space.
a.
Push Button: Push-to-test type, in unit housing, simulates loss of normal power
and demonstrates unit operability.
b.
Indicator Light: LED indicates normal power on. Normal glow indicates trickle
charge; bright glow indicates charging at end of discharge cycle.
3.
Battery: Sealed, maintenance-free, nickel-cadmium type.
4.
Charger: Fully automatic, solid-state, constant-current type with sealed power transfer
relay.
BALLASTS FOR HID LAMPS
A.
Electronic Ballast for Metal-Halide Lamps: Include the following features unless otherwise
indicated:
Section 26 51 00
Interior Lighting
1.
2.
3.
4.
5.
6.
7.
8.
9.
2.7
General Requirements for Controllers: Factory installed by lighting fixture manufacturer. Comply
with UL 1598.
B.
Standby (Quartz Restrike): automatically switches quartz lamp on when a HID lamp in the
fixture is initially energized and during the HID lamp restrike period after brief power outages.
C.
D.
Switching Off: automatically switches quartz lamp off when HID lamp strikes.
E.
Switching Off: Automatically switches quartz lamp off when HID lamp reaches approximately 60
percent light output.
2.8
EXIT SIGNS
A.
General Requirements for Exit Signs: comply with UL 924; for sign colors, visibility, luminance
and lettering size, comply with authorities having jurisdiction.
B.
1.
2.
2.9
General Requirements for Emergency Lighting Units: Self-contained units complying with UL
924.
1.
Battery: Sealed, maintenance-free, lead-acid type.
2.
Charger: fully automatic, solid-state type with sealed transfer relay.
Section 26 51 00
Interior Lighting
3.
4.
5.
2.10
Operation: Relay automatically turns lamp on when power-supply circuit voltage drops to
80 percent of nominal voltage or below. Lamp automatically disconnects from battery
when voltage approaches deep-discharge level. When normal voltage is restored, relay
disconnects lamps from battery, and battery is automatically recharged and floated on
charger.
Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and
demonstrates unit operability.
LED Indicator Light: Indicates normal power on. Normal glow indicated trickle charge;
bright glow indicates charging at end of discharge cycle.
FLUORESCENT LAMPS
A.
T8 rapid-start lamps, rated 32 W maximum, nominal length of 48 inches, 28000 initial lumens
(minimum), CRI 75 (minimum), color temperature 3500 K, and average rated life 20,000 hours
unless otherwise indicated.
B.
Compact Fluorescent Lamps: 4-Pin, CRI 80 (minimum), color temperature 3500 K, average
rated life of 10,000 hours at three hours operation per start unless otherwise indicated.
1.
26 W: T4 double or triple tube, rated 1800 initial lumens (minimum).
2.11
A.
2.12
HID LAMPS
Ceramic, Pulse-Start, Metal-Halide Lamps: Minimum CRI 80, and color temperature 4000K.
LIGHTING FIXTURE SUPPORT COMPONENTS
A.
Comply with Division 26 Section Hangers and Supports for Electrical Systems for channeland angle-iron supports and nonmetallic channel and angle supports.
B.
Single-Stem Hangers: 1/2-inch steel tubing with swivel ball fittings and ceiling canopy. Finish
same as fixture.
C.
Twin-Stem Hangers: Two, 1/2-inch steel tubes with single canopy designed to mount a single
fixture. Finish same as fixture.
D.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Lighting fixtures:
1.
Set level, plumb, and square with ceilings and walls unless otherwise indicated.
2.
Install lamps in each luminaire.
B.
C.
Section 26 51 00
Interior Lighting
4.
D.
3.2
Do not use grid as support for pendant luminaires. Connect support wires or rods to
building structure.
Connect wiring according to Division 26 Section Low-Voltage Electrical Power Conductors and
Cables.
IDENTIFICATION
A.
3.3
Install labels with panel and circuit numbers on concealed junction and outlet boxes. Comply
with requirements for identification specified in Division 26 Section Identification for Electrical
Systems.
FIELD QUALITY CONTROL
A.
Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation. Verify
transfer from normal power to battery and retransfer to normal.
B.
Prepare a written report of tests, inspections, observations and verifications indicating and
interpreting results. If adjustments are made to lighting system, retest to demonstrate
compliance with standards.
3.4
STARTUP SERVICE
A.
3.5
Burn-in all lamps that require specific aging period to operate properly, prior to occupancy by
owner. Burn-in fluorescent and compact fluorescent lamps intended to be dimmed, for at least
100 hours at full voltage.
ADJUSTING
A.
END OF SECTION
Section 26 51 00
Interior Lighting
RELATED DOCUMENTS
A.
1.2
Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY
A.
Section Includes:
1.
Exterior luminaires with lamps and ballasts.
2.
Luminarie-mounted photoelectric relays.
3.
Poles and accessories.
B.
Related Sections:
1.
Division 26 Section Interior Lighting for exterior luminaires normally mounted on exterior
surfaces of buildings.
1.3
DEFINITIONS
A.
B.
C.
D.
E.
F.
Pole: Luminaire support structure, including tower used for larger area illumination.
G.
1.4
SUBMITTALS
A.
Product Data: For each luminaire, pole, and support component, arranged in order of lighting
unit designation. Include data on features, accessories, finishes and the following:
1.
Physical description of luminaire, including materials, dimensions, effective projected
area, and verification of indicated parameters.
2.
Details of attaching luminaires and accessories.
3.
Details of installation and construction.
4.
Luminaire materials.
5.
Photometric data based on laboratory tests of each luminaire type, complete with
indicated lamps, ballasts and accessories.
a.
Manufacturer Certified Data: Photometric data shall be certified by manufacturers
laboratory with a current accreditation under the National Voluntary Laboratory
Accreditation Program for Energy Efficient Lighting Products.
6.
Photoelectric relays.
7.
Ballasts, including energy-efficiency data.
8.
Lamps, including life, output, CCT, CRI, lumens and energy-efficiency data.
9.
Materials, dimensions and finishes of poles.
Section 26 56 00
Exterior Lighting
10.
11.
Means of attaching luminaires to supports, and indication that attachment is suitable for
components involved.
Anchor bolts for poles.
B.
Shop Drawings: Include plans, elevations sections, details and attachments to other work.
1.
Detail equipment assemblies and indicate dimensions, weights, loads, required
clearances, method of field assembly, components and location and size of each field
connection.
2.
Anchor-bolt templates keyed to specific poles and certified by manufacturer.
3.
Wiring Diagrams: for power, signal, and control wiring.
C.
Qualification Data: for qualified agencies providing photometric data for lighting fixtures.
D.
E.
Operation and Maintenance Data: For luminaires and poles to include in emergency, operation
and maintenance manuals.
F.
1.5
QUALITY ASSURANCE
A.
B.
Electrical Components, Devices and Accessories: Listed and labeled as defined in NFPA 70, by
a qualified testing agency and marked for intended location and application.
C.
D.
1.6
B.
Store poles on decay-resistant-treated skids at least 12 inches above grade and vegetation.
Support poles to prevent distortion and arrange to provide free air circulation.
C.
Retain factory-applied pole wrappings on metal poles until right before pole installation. For
poles with nonmetallic finishes, handle with web fabric straps.
1.7
WARRANTY
A.
Section 26 56 00
Exterior Lighting
1.8
EXTRA MATERIALS
A.
Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1.
Lamps: One for every 10 of each type and rating installed. Furnish at least one of each
type.
2.
Glass and Plastic Lenses, Covers and Other Optical Parts: One for every 100 of each
type and rating installed. Furnish at least one of each type.
3.
Ballasts: One for every 10 of each type and rating installed. Furnish at least one of each
type.
4.
Gloves and Guards: One for every 20 of each type and rating installed. Furnish at least
one of each type.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
2.2
Products: Subject to compliance with requirements, available products that may be incorporated
into the work include, but are not limited to, product(s) indicated on Drawings.
GENERAL REQUIREMENTS FOR LUMINAIRES
A.
Luminaires shall comply with UL 1598 and be listed and labeled for installation in wet locations
by an NRTL acceptable to authorities having jurisdiction.
B.
Lateral Light Distribution Patterns: Comply with IESNA RP-8 for parameters of lateral light
distribution patterns indicated for luminaires.
C.
D.
Sheet Metal Components: corrosion-resistant aluminum unless otherwise indicated. Form and
support to prevent warping and sagging.
E.
Housings: Rigidly formed, weather- and light-tight enclosures that will not warp, sag or deform in
use. Provide filter/breather for enclosed luminaires.
F.
Doors, Frames, and other Internal Access: Smooth operating, free of light leakage under
operating conditions, and designed to permit relamping without use of tools. Designed to
prevent doors, frames, lenses, diffusers, and other components from falling accidentally during
relamping and when secured in operating position. Doors shall be removable for cleaning or
replacing lenses. Designed to disconnect ballast when door opens.
G.
H.
Plastic Parts: High resistance to yellowing and other changes due to aging, exposure to heat,
and UV radiation.
I.
Reflecting surfaces shall have minimum reflectance as follows unless otherwise indicated:
1.
White Surfaces: 85 percent.
2.
Specular Surfaces: 83 percent
3.
Diffusing specular Surfaces: 75 percent.
J.
Lenses and Refractors Gaskets: Use heat- and aging-resistant resilient gaskets to seal and
cushion lenses and refractors in luminaire doors.
Section 26 56 00
Exterior Lighting
K.
Luminaire Finish: Manufacturers standard paint applied to factory-assembled and test luminaire
before shipping. Where indicated, match finish process and color of pole or support materials.
L.
Factory-Applied Finish for Steel Luminaires: Comply with NAAMMs Metal Finishes Manual for
Architectural and Metal Products for recommendations for applying and designating finishes.
1.
Surface Preparation: Clean surfaces to comply with SSPC-SP 1, Solvent Cleaning, to
remove dirt, oil, grease, and other contaminants that could impair paint bond. Grind welds
and polish surfaces to a smooth, even finish. Remove mill scale and rust, if present, from
uncoated steel, complying with SSPC-SP 5/NACE No. 1, White Metal Blast Cleaning, or
SSPC-SP 8, Pickling.
2.
Exterior Surfaces: Manufacturers standard finish consisting of one or more coats of
primer and two finish coats of high-gloss, high-build polyurethane enamel.
a.
Color: As selected by Engineer from manufacturers full range.
M.
Factory-Applied Finish for aluminum Luninaires: comply with NAAMMs Metal finishes Manual
for Architectural and Metal Products for recommendations for applying and designating
finishes.
1.
Finish designations prefixed by AA comply with the system established by the Aluminum
Association for designating aluminum finishes.
2.
Class 1, Color Anodic Finish: AA-M32C22A42/A44 (Mechanical Finish: medium satin;
Chemical Finish: etched, medium matte; Anodic Coating: Engineerural Class I, integrally
colored or electrolytically deposited color coating 0.018 mm or thicker) complying with
AAMA 611.
N.
Factory-Applied Labels: Comply with UL 1598. Include recommended lamps and ballasts.
Labels shall be located where they will be readily visible to service personnel, but not seen from
normal viewing angles when lamps are in place.
1.
Label shall include the following lamp and ballast characteristics:
a.
USES ONLY and include specific lamp type.
b.
Lamp diameter code (T-4, T-5, T-8, T-12), tube configuration (twin, quad, triple),
base type, and nominal wattage for fluorescent and compact fluorescent
luminaires.
c.
Lamp type, wattage, bulb type (ED17, BD56, etc.) and coating (clear or coated) for
HID luminaires.
d.
Start type (preheat, rapid start, instant start) for fluorescent and compact
fluorescent luminaires.
e.
ANSI ballast type (M98, M57, etc.) for HID luminaires.
f.
CCT and CRI for all luminaires.
2.3
B.
Contact Relays: Factory mounted, single throw, designed to fail in the on position, and factory
set to turn light unit on at 1.5 to 3 fc and off at 4.5 to 10 fc with 15-second minimum time delay.
Relay shall have directional lens in front of photocell to prevent artificial light sources from
causing false turnoff.
1.
Relay with locking-type receptacle shall comply with ANSI C136.10.
2.
Adjustable window slide for adjusting on-off set points.
2.4
Comply with ANSI C82.4 and UL 1029 and capable of open-circuit operation without reduction
of average lamp life. Include the following features unless otherwise indicated:
1.
Ballast Circuit: Constant-wattage autotransformer or regulating high-power-factor type.
2.
Minimum Starting Temperature: Minus 22 deg. F.
Section 26 56 00
Exterior Lighting
3.
4.
2.5
HID LAMPS
A.
2.6
Metal-Halide Lamps: ANSI C78.43, with minimum CRI 65 Insert value, and CCT color
temperature 4000 K.
GENERAL REQUIREMENTS FOR POLES AND SUPPORT COMPONENTS
A.
B.
C.
D.
Handhole: Oval-shaped, with minimum clear opening of 2-1/2 by 5 inches, with cover secured
by stainless-steel captive screws. Provide on all poles.
E.
Concrete Pole Foundations: Cast in place, with anchor bolts to match pole-base flange.
2.7
ALUMINUM POLES
A.
Poles: Seamless, extruded structural tube complying with STM B429/B 429M, alloy 6063-T6
with access handhole in pole wall.
B.
Poles: ASTM B209, 5052-H34 marine sheet alloy with access handhole in pole wall.
1.
Shape: Round, tapered Round, straight Square, tapered Square, straight.
2.
Mounting Provisions: Butt flange for bolted mounting on foundation or breakaway
support.
C.
Pole-Top Tenons: Fabricated to support luminaire or luminaires and brackets indicated, and
securely fastened to pole top.
D.
Grounding and Bonding Lugs: Welded -inch threaded lug, complying with requirements in
Division 26 Section Grounding and Bonding for Electrical Systems, listed for attaching
grounding and bonding conductors of type and size listed in that Section, and accessible
through handhole.
E.
Brackets for Luminaires: Detachable, with pole and adapter fittings of cast aluminum. Adapter
fitting welded to pole and bracket, then bolted together with stainless-steel bolts.
1.
Tapered oval cross section, with straight tubular end section to accommodate luminaire.
2.
Finish: Same as pole and luminaire.
Section 26 56 00
Exterior Lighting
F.
2.8
Aluminum Finish: Comply with NAAMMs Metal Finishes Manual for Architectural and Metal
Products for recommendations for applying and designating finishes.
1.
Finish designations prefixed by AA comply with the system established by the aluminum
Association for designating aluminum finishes.
2.
Class 1, Color Anodic Finish: AA-M32C22A42/A44 (Mechanical Finish: medium satin;
Chemical Finish: etched, medium matte; Anodic Coating: Engineerural Class I, integrally
colored or electrolytically deposited color coating 0.018 mm or thicker) complying with
AAMA 611.
a.
Color: As selected by Engineer from manufacturers full range.
POLE ACCESSORIES
A.
Base Covers: Manufacturers standard metal units, arranged to cover poles mounting bolts and
nuts. Finish same as pole.
PART 3 - EXECUTION
3.1
LUMINAIRE INSTALLATION
A.
B.
C.
Adjust luminaires that require field adjustment or aiming. Include adjustment of photoelectric
device to prevent false operation of relay by artificial light sources, favoring a north orientation.
3.2
POLE INSTALLATION
A.
Alignment: Align pole foundations and poles for optimum directional alignment of luminaires and
their mounting provisions on the pole.
B.
Clearances: Maintain the following minimum horizontal distances of poles from surface and
underground features unless otherwise indicated on Drawings:
1.
Fire Hydrants and Storm Drainage Piping: 60 inches.
2.
Water, Gas, Electric, Communication, and Sewer Lines: 10 feet.
3.
Trees: 15 feet from tree trunk.
C.
Concrete Pole Foundations: Set anchor bolts according to anchor-bolt templates furnished by
pole manufacturer.
D.
Foundation-Mounted Poles: Mount pole with leveling nuts, and tighten top nuts to torque level
recommended by pole manufacturer.
1.
Grout void between pole base and foundation. Use nonshrink or expanding concrete
grout firmly packed to fill space.
2.
Install base covers unless otherwise indicated.
3.
Use a short piece of inch diameter pipe to make a drain hole through grout. Arrange to
drain condensation from interior of pole.
E.
Raise and set poles using web fabric slings (not chain or cable).
3.3
CORROSION PREVENTION
A.
Aluminum: Do not use in contact with earth or concrete. When in direct contact with a dissimilar
metal, protect aluminum by insulating fittings or treatment.
Section 26 56 00
Exterior Lighting
B.
3.4
Steel Conduits: Comply with Division 26 Section Raceway and Boxes for Electrical Systems.
In concrete foundations, wrap conduit with 0.010-inch-thick, pipe-wrapping plastic tape applied
with a 50 percent overlap.
GROUNDING
A.
Ground metal poles and support structures according to Division 26 Section Grounding and
Bonding for Electrical Systems.
1.
Install grounding electrode for each pole unless otherwise indicated.
2.
Install grounding conductor pigtail in the base for connecting luminaire to grounding
system.
B.
Ground nonmetallic poles and support structures according to Division 26 Section Grounding
and Bonding for Electrical Systems.
1.
Install grounding electrode for each pole.
2.
Install grounding conductor and conductor protector.
3.
Ground metallic components of pole accessories and foundations.
3.5
Inspect each installed fixture for damage. Replace damaged fixtures and components.
B.
Illumination Observations: Verify normal operation of lighting units after installing luminaires and
energizing circuits with normal power source.
1.
Verify operation of photoelectric controls.
C.
Prepare a written report of tests, inspections, observations, and verifications indicating and
interpreting results. If adjustments are made to lighting system, retest to demonstrate
compliance with standards.
3.6
DEMONSTRATION
A.
Train Owners maintenance personnel to adjust, operate and maintain luminaire lowering
devices.
END OF SECTION
Section 26 56 00
Exterior Lighting
RELATED DOCUMENTS
A.
1.2
A.
1.3
A.
Ethernet cabling.
B.
Instrumentation cable.
1.4
SUBMITTALS
A.
B.
1.5
QUALITY ASSURANCE
A.
Qualifications:
1.
Manufacturer: Company specializing in manufacturing Products specified with minimum
5 years documented experience.
2.
Installer: Company specializing in the installation of category 6, and fiber optic structured
wiring systems with minimum 5 years documented experience. Contractor shall have a
minimum of one person on job site at all times with documented formal training in the
installation of category 6, and fiber optic cabling systems if fiber optic cabling is required.
Section 26 67 05
Communication Cable & Equipment
B.
Regulatory Requirements:
1.
Conform to requirements of NFPA 70.
2.
Products: Listed and classified by Underwriters Laboratories Incorporated as suitable for
the purpose specified and indicated.
C.
Pre-Installation Meetings:
1.
Convene a pre-installation meeting one week prior to commencing Work of this Section.
2.
Require attendance of parties directly affecting Work of this Section.
3.
Review conditions of operations, procedures and coordination with related work.
4.
Agenda:
a.
Tour, inspect, and discuss conditions relating to communications cable.
b.
Review exact location of each item within building construction, casework, and
fixtures and their requirements.
c.
Review required submittals, both completed and yet to be completed.
d.
Review Drawings and Specifications.
e.
Review and finalize construction schedule and verify availability of materials,
personnel, equipment, and facilities needed to make progress and avoid delays.
f.
Review cable routing and support.
1.6
B.
1.7
REFERENCES
A.
B.
C.
PART 2 - PRODUCTS
2.1
PATCH CORDS
A.
Subject to compliance with project requirements, manufacturers offering products which may
be incorporated in the Work include the following:
1.
AMP Incorporated.
2.
Interlink Technologies.
3.
Lucent Technologies.
4.
NORDX/CDT, Incorporated.
5.
Siemon Company.
6.
Or Equal.
B.
Section 26 67 05
Communication Cable & Equipment
2.
2.2
INSTRUMENTATION CABLE
A.
Subject to compliance with project requirements, manufacturers offering products which may
be incorporated in the work include:
1.
Belden
2.
Approved equal.
B.
Conductors: For all 4-20mA signals, use 20 AWG stranded tinned copper, two pair minimum,
wet location rated.
1.
Individually shielded with shield drain wire.
2.
Insulation to be polyethylene PE or PVC.
3.
Outer jacket to be polyvinyl chloride PVC.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
B.
Report in writing to the Engineer prevailing conditions that will adversely affect satisfactory
execution of the Work of this Section. Do not proceed with Work until unsatisfactory conditions
have been corrected.
C.
By beginning Work, Contractor accepts conditions and assumes responsibility for correcting
unsuitable conditions encountered at no additional cost to the Owner.
3.2
INSTALLATION
A.
B.
C.
D.
3.3
CONSTRUCTION
A.
Section 26 67 05
Communication Cable & Equipment
3.4
B.
C.
END OF SECTION
Section 26 67 05
Communication Cable & Equipment
SUMMARY
A.
The work to be included under this section shall consist of furnishing all materials, labor,
equipment, tools, supplies, and incidentals necessary for the installation and testing of all
instrumentation, control, and SCADA systems.
B.
In general, all instruments, PLC control panels, computers, software, remote telemetry systems
and integration shall be furnished by the contractor with the exception of items furnished as part
of an equipment package. The Contractor shall be responsible for coordinating and sequencing
the required control system installation with subcontractors as required for a complete and
functional system as described herein.
1.
All software shall be purchased, installed and pre-configured by the Contractor.
2.
The Contractor shall be responsible for furnishing, installing and commissioning of the
instrumentation and control systems at the water intake pump station and storage lagoon
sites as further described herein.
3.
The Contractor shall be responsible for the development, installation and startup of the
PLC and HMI operating programs.
4.
The Contractor shall conduct Factory, Site and Final Acceptance Tests as outlined in this
document.
C.
Related Sections:
1.
Process & Analytical Instruments
2.
Programmable Logic Controllers
1.2
REFERENCES
A.
1.3
Definitions: Symbols, Definitions, and Abbreviations: All symbols, definitions, and engineering
unit abbreviations utilized shall conform to IEEE 100-84, S50.1, and S51.1, where applicable.
1.
SCADA Supervisory Control and Data Acquisition
2.
HMI Human Machine Interface
3.
VFD Variable Frequency Drive
4.
PLC Programmable Logic Controller
5.
SSRVS Solid State Reduced Voltage Starter (Soft Starter)
6.
I/O Input/Output
7.
OIT Operator Interface Terminal
8.
RTU Remote Telemetry Unit
9.
MTU Master Telemetry Unit
PATENTS
A.
1.4
If the Manufacturer is required or desires to use any design, device, material, or process
covered by letter, patent, or copyright, the Manufacturer shall provide for such use by suitable
legal agreement with the patentee or owner, and the prices bid hereunder shall, without
exception, indemnify and save the Owner and Engineer from any and all claims for infringement
by reason of the use of any such patented design, device, material, or process, or any
trademark or copyright used in connection with any equipment to be furnished hereunder.
SCOPE
A.
The scope of the instrumentation and control system for this project includes:
Section 26 90 00
General Instrumentation and Controls
1.
1.5
Process Control: Furnishing, installing, and configuring PLC panels and OITs to control
the process equipment as detailed on the Drawings and in the Specifications. PLC
panels in this project, other than those included as part of vendor supplied equipment,
are listed below:
a.
Main PLC01: A new PLC shall be furnished and installed in the pump station
electrical room and indicated in the plans and and as specified herein.
b.
Remote LCP02: A new PLC shall be furnished and installed at the storage lagoon
for transmission of lagoon water level to PLC01 as indicated in the plans and as
specified herein.
SUBMITTALS
A.
Product Data:
1.
Instrument Installation Details.
2.
Instrument Specification Sheets: See Specification 26 90 10 Process and Analytical
Instruments.
3.
Certified Calibration Sheets.
4.
Complete and detailed instruction manuals on each item furnished including but not
limited to all devices and instruments. Information to be contained in the instruction
manuals shall include but not be limited to drawings, dimensions, manufacturers
recommendations, ratings, performance charts, power requirements, schematics,
maintenance requirements and procedures, calibration recommendations and
procedures, repair instructions, complete and recommended spare parts lists and related
information.
5.
Proposed tagging and attachment materials and methods.
B.
C.
Section 26 90 00
General Instrumentation and Controls
1.6
1.7
Storage and Protection: Delivery, storage, and handling shall be in accordance with
Manufacturers recommendation and the requirements of General Conditions and other sections
herein.
PROJECT AND SITE CONDITIONS
A.
-25 C to 80 C
Pressure
650 mm Hg to 800 mm Hg
Relative Humidity
Vibration Frequency:
10 - 2000 Hz.
Vibration Position
1.5 mm peak-to-peak
Vibration Acceleration
10 G.
B.
Where the ratings of individual components cannot meet the requirements, provide suitable
means of physical protection. Suitable physical protection shall consist of an assembly which
meets the requirements listed, while limiting the ambient conditions at the non-conforming
component to 90% of the components rating (Example: A component rated for vibration at only
5 G. acceleration would be required to be combined with vibration isolation to limit the
acceleration of the component to 4.5 G. when subjected to ambient acceleration of 10 G. from
10 - 2000 Hz.).
C.
Operating Environmental Conditions: All instruments and control devices provided shall be
rated for continuous operation in their installed operating environment and shall be capable of
continuous operation at the operating conditions without significant reduction of their operating
life.
D.
All controlling devices shall be NEMA rated.
PART 2 - PRODUCTS (NOT USED)
PART 3 - EXECUTION
3.1
GENERAL
A.
All meters, instruments, control units, and other components shall be the most recent field
proven models marketed by their respective manufacturers at the time of the submittal of the
shop drawings unless otherwise specified to match existing equipment.
Section 26 90 00
General Instrumentation and Controls
B.
Analog measurements and control signals shall be electrical and shall vary in direct linear
proportion to the variable being measured. All analog signals whether inputs or outputs shall be
4-20mA DC unless otherwise noted. The analog input signals shall maintain loop integrity with
the installation of properly sized resistors across the input terminals.
C.
All of the elements, instruments, accessories, and assemblies shall be installed in accordance
with the manufacturers installation instructions, and as detailed on the Drawings. Shielded
instrumentation cables shall be used for all analog signals from the instruments to the
programmable logic controller panels. Separate conduits shall be used for instrument power,
instrument signals, and fiber optic cables.
D.
All instruments and control panels installed outdoors shall include a sun shield.
E.
All digital outputs shall be isolated from the field equipment through an interposing relay. The
relays shall be mounted inside the cabinet housing the associated programmable logic
controller as shown on Drawings.
F.
The Contractor shall make the necessary power connections and signal connections from the
field devices (i.e. instruments, control valves, etc.) to the programmable logic controllers.
G.
The PLCs, OITs, Ethernet switches, surge protection devices, uninterruptible power supplies,
and other incidental equipment shall be configured and installed as shown on the Drawings and
as specified herein.
H.
The Contractor shall configure all networked devices for proper communication via the topology
and protocol shown on the Drawings or specified herein.
I.
The Contractor shall verify that all system devices power up, function and properly
communicate prior to commencing any startup or testing procedures as described herein.
3.2
Testing and Installation Requirements: The Contractor shall be required to coordinate the
following services during construction related to the testing and installation of the
instrumentation and control (I&C) system. The complete system testing shall include all PLCs,
network devices, remote telemetry devices, interconnecting cables, and other peripheral
devices required for a complete and functional system. The testing of the system shall occur in
three stages: A Factory Acceptance Test, a Site Acceptance Test, and a Final Acceptance Test.
B.
Section 26 90 00
General Instrumentation and Controls
4.
5.
terminal numbers will be checked for conformance with the submittal drawings during this
Factory Acceptance Test.
Each control loop shall be checked for proper operation from each field connection point
in the control enclosure and confirmation of each item shall be properly displayed on
each OIT. The contractor shall be prepared to simulate several inputs and outputs in
order to fully confirm the proper operation of each control loop.
After the Owner and Engineer are satisfied that the system is working as intended, the
Contractor will then be authorized to ship the system to the site for installation.
C.
D.
3.3
Training: The Contractor shall provide training for the purpose of familiarizing Owners
personnel with the instrumentation and control system. All training shall be as scheduled by the
Owner. The training shall be scheduled a minimum of thirty (30) days in advance of when they
are to be given. Proposed training materials, including a detailed training agenda itemizing
Section 26 90 00
General Instrumentation and Controls
relative emphasis on various topics of each course, shall be submitted to the Owner and
Engineer at least fourteen (14) days in advance of when the training is to begin.
B.
Startup Assistance
1.
The Contractor shall be responsible for the furnishing of a qualified technical
representative who shall supervise the installation of equipment and/or install equipment,
and who shall test, adjust, field calibrate, and fully commission all flow metering
equipment, instrumentation equipment, control equipment, and accessories specified
herein and required as integral components of the complete systems. The commissioning
will be deemed to be complete only after all systems are found to be performing
satisfactorily following the final balancing of plant operation. The guarantee period, during
which all defective materials shall be replaced and all faulty workmanship will be
corrected at no cost to the Owner, shall begin with the date on which the commissioning
is judged to be complete.
C.
Service:
1.
Manufacturers shall provide as part of the equipment cost sufficient days of service by a
factory-trained service engineer specifically trained on the type equipment herein
specified to assist the Contractor during installation and start-up. The service time shall
be sufficient to place the units in satisfactory service and instruct the Owners personnel
in proper operation and maintenance of the equipment.
D.
Maintenance Instruction:
1.
Operating and maintenance instructions, along with a separate parts list, shall be
furnished in three (3) copies to the Owner. Operating instructions shall also incorporate a
functional description of the system, including the system schematics which reflect "asbuilt" modifications. Maintenance requirements particular to the system shall be clearly
defined, along with calibration and test procedures.
E.
Warranty:
1.
All equipment and workmanship furnished under this contract shall be guaranteed to be
free of defects in materials and workmanship for a period of one (1) year from and after
the date of final acceptance of the work by the Owner, and any such defects which
appear within the stipulated guaranty period shall be repaired, replaced or made good
without charge. This guarantee shall include the capacity and integrated performance of
the components parts.
END OF SECTION
Section 26 90 00
General Instrumentation and Controls
SUMMARY
A.
The work to be included under this section of the Specifications shall consist of furnishing all
materials, labor, equipment, tools, supplies, and incidentals for installation of all instrumentation
equipment. The work shall include every item of construction necessary for a complete and
acceptable installation as shown on the Drawings and as specified herein.
B.
Related Sections:
1.
General Instrumentation and Control
2.
Programmable Logic Controllers
1.2
REFERENCES
A.
ISA S20 - Specification Forms for Process Measurement and Control Instruments, Primary
Elements and Control Valves
B.
ISA S50.1 - Compatibility of Analog Signals for Electronic Industrial Process Instruments
C.
D.
E.
Definitions: Symbols, Definitions, and Abbreviations: All symbols, definitions, and engineering
unit abbreviations utilized shall conform to IEEE 100-84, S50.1, and S51.1, where applicable.
1.
SCADA Supervisory Control and Data Acquisition
2.
HMI Human Machine Interface
3.
VFD Variable Frequency Drive
4.
PLC Programmable Logic Controller
5.
SSRVS Solid State Reduced Voltage Starter (Soft Starter)
6.
I/O Input/Output
7.
OIT Operator Interface Terminal
8.
RTU Remote Telemetry Unit
9.
MTU Master Telemetry Unit
10.
N.O. Normally Open
11.
N.C. Normally Closed
1.3
SCOPE
A.
1.4
This section of the Specifications covers the instrumentation equipment. The major items of
instrumentation equipment to be furnished and installed shall include the following:
1.
Ultrasonic Level Indicating Transmitter
2.
Magnetic Flow Indicating Transmitter
3.
Pressure Indicator
4.
Float Switch
SYSTEM REQUIREMENTS
A.
Design Requirements:
1.
Provide analog field instruments with transmitters which condition the signal to output a
4-20mA signal linear to the measured variable.
2.
Similar instruments shall be by the same Manufacturer to the extent practical.
Section 26 90 10
Process and Analytical Instruments
B.
Performance Requirements:
1.
Accuracy:
a.
Accuracy shall be as defined in ISA S51.1 and ISA S51.1, Sec. 5. Provide a
complete and operating instrument installation with measurement accuracy
determined by adding the accuracy of the element and the transmitter and any
wiring to the field terminal enclosure of 0.75% of calibrated span or better, unless
specified otherwise below, at any environmental condition specified.
2.
Ranges:
a.
The expected range of each instrument shall be as directed by the Owner and
Engineer. Expected ranges shall correspond to actual field conditions.
PART 2 - PRODUCTS
2.1
EQUIPMENT
A.
2.2
Furnish instruments specified in the instrument specification sheets at the end of this section.
Instruments for services not listed shall be equal in quality, performance, and environmental and
functional characteristics as instruments listed and shall be approved in writing by the Owner.
INSTRUMENT ACCESSORIES
A.
Instrument and Control Device Tags: Each field mounted field device shall be identified by its
unique tag number as it appears on the original P&I diagrams and the Instrument Loop
Diagram. The tag number shall be stamped on a 1" x 2" stainless steel tag permanently
attached to the instrument by braided stainless steel wire which has been sealed by an
approved method such that the wire must be cut or the seal broken to remove the tag. The tag
number shall not be stamped on the nameplate of the instrument. This requirement shall be
documented on the Instrumentation Specification Sheet.
B.
Process Tubing:
W.T. minimum.
C.
Pneumatic Supply Tubing: Stainless Steel, ASTM A 269, TP316, seamless, annealed, 1/2" x
0.065" W.T., 3/8" x 0.049" W.T. and 1/4" x 0.035" W.T. minimum.
D.
E.
F.
Enclosures for outdoor locations: Furnish and install NEMA 4X enclosures. All outdoor
enclosures with instrumentation accessible in enclosure door shall have a stainless steel
sunshade.
2.3
CALIBRATION
A.
Order instruments factory calibrated to the range indicated with calibration sheets indicating
certification of traceability to National Institute of Standards and Technology (NIST).
Instruments shall be ranged as directed by Engineer.
Section 26 90 10
Process and Analytical Instruments
2.4
FABRICATION
A.
Materials of Construction:
otherwise specified.
Provide 316 Stainless Steel for wetted and other parts unless
PART 3 - EXECUTION
3.1
APPLICATION
A.
Installation
1.
Install sensing elements at the point of measurement and route sensing line or cable to
the transmitter. Install the transmitters 4-6" above grade or platform in an easily
accessible location adjacent to the sensor location. Mount on pipe stanchion or steel
support designed for the purpose individually or grouped with other transmitters. Route
signal cable in conduit from transmitter to terminal cabinet or control panel for termination
to test terminals. Steel supports shall be in accordance with this Section, and all other
sections and specification requirements. Process connections for instrumentation shall
be in accordance with piping sections and all other specification requirements. Provide
block valves at taps for pressure or sampling sensor lines. Provide plugged tees at taps
suitable for rodding or blowing out taps. Make pipe taps with weld-o-let type fittings or
equal. Install block valves suitable for the service and rated as the pipe at each tap,
generally use NPT threaded ball valves. Use materials rated for the service and transition
to tubing for sensor runs. Use 1/2 OD 316 SS tubing or as shown on the Drawing details.
B.
C.
Pressure Instruments: Make pressure taps in top of pipe for gas service and side of pipe for
liquid or steam service.
D.
Pressure Gauges (Indicators): Use 1/2" NPT pipe and ball or needle valve for pressure gauge
taps. Mount gauges vertically; provide 90 fitting, seal, snubber or siphon tube as required.
Where 90 fitting is required, install a tee-fitting with plug.
E.
Differential pressure and level transmitters: Use 1/2" tubing and ball or needle valves for
pressure taps. Slope tubing runs 1" per foot to drain the sensing line to the pipe where the
transmitter is higher than the tap and to drain the line to the transmitter where the transmitter is
lower than the tap. At the transmitter connection provide a valve manifold that can block, bleed,
vent, purge and provide calibration ports to the transmitter. For gas service transmitters, route
1/2" tubing straight up from the tap for a minimum of 12" to a high point in the line, then with a
minimum slope of 1" per foot to the transmitter connection. Provide an automatic condensate
drain at the transmitter.
F.
Temperature instruments: Generally mount thermocouple assemblies in the side of the pipe at
a minimum angle of 15 up from horizontal and route thermocouple or RTD cable to the
transmitter in conduit. Do not mount thermocouples absolutely horizontal or at angles below
horizontal. Provide adequate clearance for removal of head assembly and extraction of sensor.
G.
Section 26 90 10
Process and Analytical Instruments
H.
I.
J.
Calibration: Calibrate each and every instrument connected to the work of this contract in its
range, whether furnished under this contract, owner-furnished or existing and fill out a signed
and dated five point calibration sheet and install an initialed and dated calibration sticker. Notify
the Owner in writing immediately of any instrument which will not calibrate. Instruments that do
not calibrate will require the on-site services of a factory authorized representative at no cost to
the Owner.
Section 26 90 10
Process and Analytical Instruments
Instrument Tag
Application
LIT01
Measurement
Range
As required
Section 26 90 10
Process and Analytical Instruments
Display
Accuracy:
+/- 0.2% of actual flow rate +/- 1mm/sec at flow rates above 3 fps velocity.
Repeatability shall be +/- 0.15%
Accessories
Suppliers
Instrument Tag
FIT01
Application
Pump Station Flow to Reservoir
Measurement Range
0-7500 gpm
Section 26 90 10
Process and Analytical Instruments
Mounting
Power Supply
Suppliers
120 VAC
Siemens, ABC Chem-Float or equal
Instrument Tag
LS01
Application
Pump well level
Contact
N.O.
Section 26 90 10
Process and Analytical Instruments
Mounting
Suppliers
Instrument Tag
PI
Application
Pump discharge pressure
Range
0-50 psi
END OF SECTION
Section 26 90 10
Process and Analytical Instruments
SUMMARY
A.
The work to be included under this section of the Specifications shall consist of furnishing all
materials, labor, equipment, tools, supplies, and incidentals for installation of all programmable
logic controllers. The work shall include every item of construction necessary for a complete
and acceptable installation as shown on the Drawings and as specified herein.
B.
Related Sections:
1.
General Instrumentation and Control
2.
Process and Analytical Instruments
C.
Manufacturers Support: The PLC system manufacturer shall maintain, as a part of a national
network, engineering service facilities within 100 miles of the project, to provide start-up service,
emergency service calls, repair work, service contracts, maintenance, and training. Emergency
service shall be available within twenty-four hours of notification.
1.2
REFERENCES
A.
1.3
Definitions: Symbols, Definitions, and Abbreviations: All symbols, definitions, and engineering
unit abbreviations utilized shall conform to IEEE 100-84, S50.1, and S51.1, where applicable.
1.
SCADA Supervisory Control and Data Acquisition
2.
PLC Programmable Logic Controller
3.
HMI Human Machine Interface
4.
OIT Operator Interface Terminal
5.
I/O Input/Output
6.
MTU Master Telemetry Unit
7.
RTU Remote Telemetry Unit
8.
VFD Variable Frequency Drive
9.
SSRVS Solid State Reduced Voltage Starter (Soft Starter)
10. Commissioning The process of assuring that all elements and functionality of a process
or system are designed, installed, tested, and operational according to the requirements
of the Owner.
SCOPE
A.
The following lists the PLCs that are part of the control system.
1.
PLC01 (Pump Station)
2.
LCP02 (Storage reservoir level measurement)
B.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
B.
Section 26 90 20
Programmable Logic Controllers
2.2
EQUIPMENT
A.
B.
C.
D.
Each PLC shall have a CompactFlash nonvolatile memory card installed with capacity greater
than or equal to processor internal memory. The controller shall be configured to load a copy of
the program from nonvolatile memory whenever there is no project in the controller and power
is applied.
E.
The PLCs shall be capable of and shall be configured to provide stand-alone operation in the
event of a communications link failure.
F.
The necessary interface cables, communications cables, power cables, bus extension cables,
modular card slot fillers, and other ancillary parts shall be furnished and installed as integral
parts of the control system.
G.
Nameplates shall be provided for each module, device, and other equipment with appropriate
data such as the equipment number, rating, serial number, and manufacturer.
H.
All I/O cards shall be furnished with removable terminal blocks to simplify card wiring and
replacement.
I.
The Contractor shall furnish the Owner the following spare replacement parts:
1.
One (1) Processor Module of each type
2.
One (1) I/O modules of each type
J.
K.
PLC Control Panel Components Each PLC control panel shall contain the following
components:
1.
Current Loop Surge Protection Devices: The 4-20mA signal loop channels on the PLC
analog inputs and outputs shall be protected against static discharge, lightning, and faulty
wiring with three stage surge protection terminal block devices. Devices shall be
Termitrab TT series as manufactured by Phoenix Contact or equal.
2.
Discrete Output Relays: Terminal block syle interposing relays shall be used for all
120VAC PLC outputs. Devices shall be PLC-RSC-120UC/21 as manufactured by
Phoenix Contact or equal.
3.
Current Loop Power Supplies: When required, the instrument transmitter shall be
furnished with a separate power supply to provide the loop power for 2-wire instruments.
The power supplies shall be DIN rail mounted, 120VAC input, 24VDC output, with output
load rated as required for the instrument. Power supplies shall be provided by Phoenix
Contact, Allen-Bradley, or Sola.
Section 26 90 20
Programmable Logic Controllers
4.
5.
6.
7.
8.
9.
Terminal Strips and Accessories: Provide DIN rail mounted terminal strips including
fused terminals with blown fuse indication, ground terminals and terminal groups for each
incoming or outgoing device circuit including group tag identifying the device and
identified terminals for each incoming or outgoing wire. Provide terminal end, partition
and separation plates as required. Provide pre-engraved vinyl marking strips with
terminal and group identification as shown on the submittal drawings. Provide group tags
and terminals or as indicated on the drawings or equals. Do not splice control wires.
Provide DIN rail mounted relay bases with LED coil indicators and arc suppression for
plug-base relays. Identify each terminal with the wire designator from the wire number
i.e. "+", "-", "SH", "NO", "NC", "COM", "L1", "N", etc. Provide 20% spare terminals and
I.D. tags of each designation. Provide 20% spare connectors, fittings, wire ties, labels
and markers of each type provided.
Relays: Provide relays as required to implement indicated control functions. General
purpose, alternating and time delay relays may be used within their ratings for logic,
timing and sequencing but shall not be used to drive loads in excess of 80% of their
contact "make" or "break" ratings. Provide interposing power relays to drive loads such
as starters larger than NEMA size 1 and all other utilization equipment with loads greater
than specified for general purpose and time delay relays. Provide relays rated to drive
the load as required. Relays shall be provided with an LED status indicator.
a.
General Purpose Relays: Provide tube-base relays rated 120VAC, DPDT or
3PDT, 10 Amp contacts rated to break inductive loads of 3 Amperes. Provide
Allen-Bradley 700 Type HA, Potter Brumfield or as indicated on drawings or equal.
Provide additional relays as required to obtain sufficient numbers of contacts.
b.
Time Delay Relays: Provide relays for which the time delay is based on the
presence or absence of control voltage at the relay. Unless indicated otherwise,
provide DIP switch programmable multifunction relays including time delay on
energization, time delay on de-energization or one-shot timing as indicated.
Provide continuous control power to the relay if required, whether indicated or not.
The shop drawings shall reflect the actual proposed connection and timing
diagram for the specific relays to be provided. Provide relays rated 120VAC, DPDT
or 3PDT, 10 Amp contacts rated to break inductive loads of 3 Amperes. Provide
tube-base relays as manufactured by SSAC or equal.
c.
Power Relays: Provide heavy-duty solenoid type relays with contacts rated not
less than 10 amperes continuous at 300 volts AC. Provide a minimum of four
reversible poles or four universal or double-throw poles. Relays shall be type
700N as manufactured by Allen-Bradley or equal.
Grounding: Each panel shall be provided with a copper equipment grounding bar,
ground lugs, and bonding cable and fittings as required.
Nameplates: Each enclosure shall be identified by a nameplate including its designation
and service name as specified. Panel mounted instruments and control devices shall be
identified by a nameplate including the tag number and service name. Control devices
shall be provided with Manufacturers standard legends indicating function (example:
STOP, START, HAND-OFF-AUTO, etc.) Provide engraved, acrylic plastic laminate
nameplates, 1/16 thick, 1" x 6" minimum for junction boxes and panels, sized to fit for
control devices and stations, engraved in black letters on white face and punched for and
fastened with self-tapping 10/32 stainless steel screws and silicone adhesive.
Uninterruptible Power Supply (UPS): Each PLC panel shall contain a UPS to provide
seamless and continuous operation of equipment during power outages. The UPS shall
provide backup power with true sine wave output, fault indicator, overload indicator and a
replace batteries indicator. . Contractor shall furnish and install a bypass toggle switch
that bypasses the UPS in case of failure. UPS shall be manufactured by APC, Eaton,
or equal.
Ethernet Switch: Each PLC cabinet shall be furnished with an N-Tron model 305FX or
equal unmanaged Ethernet switch. The full duplex fiber optic port shall be of type
specified in section 26 09 43, Fiber Optic Network.
Section 26 90 20
Programmable Logic Controllers
10.
Panel Interface Connector (PIC): Each PLC enclosure shall include a PIC mounted on
the outside of the enclosure for providing a Ethernet connection to internal devices. The
PIC shall include a 120 VAC single phase duplex receptacle with 3 Ampere externally
resettable circuit breaker and an RJ45 pass-through connector. A CAT5 cable shall
connect the PIC to an internal Ethernet switch.
PART 3 - EXECUTION
3.1
PROGRAMMING
A.
The Contractor shall furnish all PLC and OIT configuration, application programming,
debugging, and commissioning as required to provide the Owner a complete functional control
system meeting requirements in the plans and specifications herein.
B.
During startup the Contractor shall adjust the system to the satisfaction of the Owner.
C.
Section 26 90 20
Programmable Logic Controllers
h.
i.
D.
The Contractor shall configure numeric displays to display scaled process values
for all analog inputs to the system. This includes pressure, flow, turbidity, pH,
level, streaming current, and other process variables as required.
The Contractor shall program a separate alarm screen that displays the most
recently activated alarms. The screen shall enable the operator to easily
differentiate between active and acknowledged alarms. It shall also allow the
operator to acknowledge or silence any unacknowledged alarm. Each alarm listing
shall display the time of occurrence and acknowledgement time (if any).
FUNCTIONAL DESCRIPTION
1.
The SCADA system shall be setup initially with the basic functionality as described
below. This description shall be used as a guide for controlling various items by location.
Each automatic, manual and operator initiated set point shall be configured with upper
and lower limits to keep the process operating within an expected operating range. The
Contractor shall provide support for the following functions in the PLC programming and
OIT HMI screens.
a.
Pump Station
1)
Display the following information on the OIT:
a)
Pump 1 soft starter fault and alarm.
b)
Pump 1 run status.
c)
Pump 1 vibration warning and alarm.
d)
Pump 1 vibration shutdown and alarm.
e)
Pump 1 vibration detection bypass switch position.
f)
Pump 1 Hand-Off-Auto (HOA) switch position.
g)
Pump 2 soft starter fault.
h)
Pump 1 run status.
i)
Pump 1 vibration warning and alarm.
j)
Pump 1 vibration shutdown and alarm.
k)
Pump 1 vibration detection bypass switch position.
l)
Pump 1 Hand-Off-Auto (HOA) switch position.
m)
Pump station discharge flow rate.
2)
The pump station discharge flow meter shall be calibrated and configured to
display flow rate and totalized flow. Coordinate with the Owner for units of
measure; configure the transmitter to transmit via a 4-20 mA signal the flow
rate to PLC01.
3)
Soft starter control panels DSSSS01 and DSSSS02 control pumps DSP01
and DSP02 respectively. Each panel has an HOA switch. When an HOA
switch is in the Auto position, PLC01 shall control the respective pump run
and stop operation.
a)
The OIT shall support two operator adjustable reservoir level
setpoints: low level for turning pump(s) on and higher level for turning
pump(s) off.
b)
The OIT shall enable the operator to select one-pump or two-pump
operation. In either case, the pumps shall be turned on and off per a)
above.
c)
If one-pump operation is selected, then with each on-off cycle of
operation, the alternate pump shall be operated.
d)
If for any reason a pump controller (soft starter) is disabled, the
system shall operate the other pump.
e)
If the pump well low level switch LS01 should indicate low level,
disable pump operations and generate an alarm on the OIT.
b.
Reservoir
1)
Control panel LCP02 shall be installed at the reservoir as indicated in the
plans. The purpose of LCP02 is to interface with an ultrasonic level
transmitter, LIT01, and transmit the water level in the reservoir over Ethernet
to the pump station control panel, PLC01.
Section 26 90 20
Programmable Logic Controllers
2)
3)
3.2
GENERAL
A.
The Contractor shall utilize personnel who are skilled and experienced in the panel fabrication,
installation, setup, and configuration of the PLCs being furnished under this contract.
B.
The Contractor shall furnish and install all of the I/O listed in the Drawings utilizing the I/O
modules listed in this Specification.
C.
All wiring shall be neatly installed and wire ways shall be used wherever possible. All wiring
shall be identified at all terminating locations by Tag ID as identified in Drawings.
D.
Any PLC furnished as part of a vendor supplied equipment package shall be accessible for
future program monitoring and revisions. If password protection of any kind is implemented, the
vendor or Contractor shall supply all passwords or other security information to the Owner and
the Engineer prior to equipment commissioning.
E.
The Contractor shall furnish and install the conduit, power wiring, signal wiring, communications
wiring, fiber optic cables, and network components that make up the distributed control system
as shown on the Drawings.
F.
The Contractor shall furnish the necessary enclosures, racks, power supplies, surge protection
devices, communications modules, PLC processors, I/O modules, PLC power supplies, loop
power supplies, and Ethernet devices for all of the programmable logic controller units. The
Contractor shall furnish and install the necessary fiber optic cables, Ethernet cables, instrument
signal cables, and control circuits required for monitoring and controlling the equipment within
the treatment facilities.
G.
All accessories and assemblies shall be installed in accordance with the manufacturers
installation instructions.
H.
The Contractor shall furnish the Owner two complete copies of the operations and maintenance
manuals for all PLC components detailed in this Specification.
END OF SECTION
Section 26 90 20
Programmable Logic Controllers
DIVISION 31
EARTHWORK
SUMMARY
A.
Section includes: The installation of a non-woven geotextile fabric below riprap and gravel
pavement.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 31 37 00 Rip Rap.
b.
Section 01 33 00 Submittal Procedures.
1.2
REFERENCE STANDARDS
A.
ASTM D3786 Standard Test Method for Bursting Strength of Textile Fabrics Diaphragm
Bursting Strength Tester Method
B.
ASTM D4355 Standard Test Method for Deterioration of Geotextiles by Exposure to Light,
Moisture and Heat in a Xenon Arc Type Apparatus
C.
ASTM D4491 Standard Test Methods for Water Permeability of Geotextiles by Permittivity
D.
ASTM D4632 Standard Test Method for Grab Breaking Load and Elongation of Geotextiles
E.
ASTM D4833 Standard Test Method for Index Puncture Resistance of Geomembranes and
Related Products
F.
ASTM D4751 Standard Test Method for Determining Apparent Opening Size of a Geotextile
G.
ASTM D4886 Standard Test Method for Abrasion Resistance of Geotextiles (Sand
Paper/Sliding block Method)
H.
ASTM D4533 Standard Test Method for Trapezoid Tearing Strength of Geotextiles
I.
ASTM D6241 Standard Test Method for Static Puncture Strength of Geotextiles and Related
Products Using a 50mm Probe
1.3
QUALITY ASSURANCE
A.
1.4
A.
Section 31 05 19
Geotextile Filter Fabric
B.
PART 2 - PRODUCTS
2.1
MATERIAL
A.
The non-woven geotextile fabric shall be an 8-ounce fabric, US Fabrics US 205NW or equal.
The fabric shall be of non-woven needle punched construction and consist of long-chain
polymeric filaments or fibers composed of polypropylene, polyethylene or polyamide. The
filaments and fibers shall be oriented whereby they retain their relative positions with each other
and allow the passage of water as specified.
B.
The fabric shall be mildew, insect and rodent resistant and shall be inert to chemicals commonly
found in soil. The non-woven fabric shall conform to the physical property requirements below:
Physical Property
Weight
Tensile Strength, wet, lbs
Elongation, wet, %
Permittivity
Puncture Strength, lbs
CBR Puncture
Mullen Burst Strength, psi
Abrasion Resistance, % Strength Retained
Apparent Opening Size (AOS)
Ultraviolet Resistance, % Strength Retention
Trapezoidal Tear
Water Flow Rate
C.
Test Method
ASTM D 5261
ASTM D 4632
ASTM D 4632
ASTM D 4491
ASTM D 4833
ASTM D 6241
ASTM D 3786
ASTM D 4886
ASTM D 4751
ASTM D 4355 (After 500
Xenon Weatherometer hrs.)
ASTM D 4533
ASTM D 4491
Test Results
8 oz/sy
205 lbs
50%
1.35 sec-1
130 lbs
535 lbs
350 psi
90
80 US Sieve
70%
85 lbs
90 gal/min/sf
The non-woven geotextile fabric shall be furnished in a protective wrapping which shall protect
the fabric from ultraviolet radiation and from abrasion due to shipping and handling.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
Fabric Exposure Following Placement - Exposure of the geotextile filter fabric to the elements,
particularly the sun, between lay down and cover shall be a maximum of 7 days.
B.
The non-woven geotextile fabric shall be placed in the manner and at the locations shown on
the drawings or as directed by the Engineer. The surface to receive the fabric shall be prepared
to a smooth condition free of obstructions, depressions and debris. The fabric shall be placed
loosely, not in a stretched condition.
C.
The Contractor shall anchor the geotextile fabric at outer edges of the riprap and gravel
pavement courses by embedding the fabric down, across, and up a 1-foot deep by 1-feet wide
trench. The anchoring trench shall be backfilled with rock material approved by Engineer.
There will be no separate payment for Geotextile Fabric; it shall be subsidiary to other items.
D.
Where necessary, the fabric shall be placed so as to provide a minimum 24-inch overlap. The
fabric shall be placed transverse to the direction of the flow with the upstream panel overlapping
the downstream panel. All installations shall be subject to approval by Engineer.
Section 31 05 19
Geotextile Filter Fabric
E.
Repairs - A geotextile patch, of the same material, shall be placed over any damaged area and
shall extend 12-inches beyond the perimeter of the tear or damaged area. Patch shall be either
glued or sewn to the mother fabric or as approved by Engineer.
END OF SECTION
Section 31 05 19
Geotextile Filter Fabric
SUMMARY
A.
Section includes: Clearing, grubbing, scalping, stripping, and disposal of waste debris.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
1.2
DEFINITIONS
A.
Interfering or Objectionable Material: Trash, rubbish, and junk; vegetation and other organic
matter, whether alive, dead, or decaying; topsoil.
B.
C.
Grubbing: Removal of vegetation and other organic matter including stumps, buried logs, and
roots greater than 2 inches caliper to a depth of 12 inches below subgrade.
D.
Scalping: Removal of sod without removing more than upper 3 inches of topsoil.
E.
F.
1.3
SUBMITTALS
A.
Shop Drawings: Drawings clearly showing clearing, grubbing, and stripping limits.
B.
1.4
QUALITY ASSURANCE
A.
1.5
Obtain Engineers approval of staked clearing, grubbing, and stripping limits, prior to
commencing clearing, grubbing, and stripping.
SCHEDULING AND SEQUENCING
A.
Prepare site only after adequate erosion and sediment controls are in place. Limit areas
exposed uncontrolled to erosion during installation of temporary erosion and sediment controls
to maximum of 5 acres.
Section 31 11 00
Site Preparation
GENERAL
A.
Clear, grub, and strip areas actually needed for waste disposal, borrow, or site improvements
within limits shown or specified.
B.
3.2
LIMITS
A.
B.
Remove rubbish, trash, and junk from entire area within Project limits.
3.3
CLEARING
A.
B.
Fell trees so that they fall away from facilities and vegetation not designated for removal.
C.
Cut stumps not designated for grubbing to within 6 inches of ground surface.
D.
Cut off shrubs, brush, weeds, and grasses to within 2 inches of ground surface.
3.4
GRUBBING
A.
3.5
A.
Do not remove sod until after clearing and grubbing is completed and resulting debris is
removed.
B.
3.6
STRIPPING
A.
B.
Strip areas within limits to minimum depths shown or specified. Do not remove subsoil with
topsoil.
C.
Stockpile strippings, meeting requirements for topsoil, separately from other excavated material.
Section 31 11 00
Site Preparation
3.7
TOPSOIL
A.
3.8
Natural, friable, sandy loam, obtained from well-drained areas, free from objects larger than 11/2 inches maximum dimension, and free of subsoil, roots, grass, other foreign matter,
hazardous or toxic substances, and deleterious material that may be harmful to plant growth or
may hinder grading, planting, or maintenance.
DISPOSAL
A.
B.
C.
Strippings:
1.
Dispose of strippings that are unsuitable for topsoil or that exceed quantity required for
topsoil
2.
Stockpile topsoil in sufficient quantity to meet Project needs. Dispose of excess strippings
as specified for clearing and grubbing.
END OF SECTION
Section 31 11 00
Site Preparation
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 02 41 00 Demolition.
b.
Section 31 11 00 Site Preparation.
c.
Section 31 23 16 Excavation.
d.
Section 31 23 23.13 Fill and Backfill.
1.2
REFERENCE STANDARDS
A.
ASTM D1557 Standard Test Methods for Laboratory Compaction Characteristics of Soil Using
Modified Effort (56,000 ft-lbf/ft3)
B.
ASTM D698 - Standard Test Methods for Laboratory Compaction Characteristics of Soil Using
Standard Effort (12,400 ft-lbf/ft3)
1.3
DEFINITIONS
A.
B.
Prepared Ground Surface: Ground surface after completion of clearing and grubbing, scalping
of sod, stripping of topsoil, excavation to grade, and scarification and compaction of subgrade.
C.
D.
E.
Subgrade: Layer of existing soil after completion of clearing, grubbing, scalping of topsoil prior
to placement of fill, roadway structure or base for floor slab.
F.
Standard Specifications: The latest edition, including supplements of the Oklahoma Department
of Transportation Standard Specifications for Highway Construction.
1.4
Section 31 22 13
Subgrade Preparation
1.5
QUALITY ASSURANCE
A.
1.6
Notify Engineer when subgrade is ready for compaction or whenever compaction is resumed
after a period of extended inactivity.
ENVIRONMENTAL REQUIREMENTS
A.
GENERAL
A.
Keep subgrade free of water, debris, and foreign matter during compaction or proof-rolling.
B.
Bring subgrade to proper grade and cross-section and uniformly compact surface.
C.
Do not use sections of prepared ground surface as haul roads. Protect prepared from traffic.
D.
Maintain prepared ground surface in finished condition until next course is placed.
3.2
MOISTURE CONDITIONING
A.
Dry Subgrade: Add water, then mix to make moisture content uniform throughout.
B.
Wet Subgrade: Aerate material by blading, discing, harrowing, or other methods, to hasten
drying process.
3.3
TESTING
A.
3.4
Test roll subgrade as specified in Standard Specifications to detect soft or loose subgrade or
unsuitable material, as determined by Engineer.
CORRECTION
A.
END OF SECTION
Section 31 22 13
Subgrade Preparation
SECTION 31 22 19 - GRADING
PART 1 - GENERAL
1.1
SUMMARY
A.
Section includes:
1.
Removal and storage of topsoil.
2.
Rough grading the site for site structures, building pads, and drive and parking isles.
3.
Finish grading for planting.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 31 23 16 Excavation.
b.
Section 31 23 23.13 Fill and Backfill.
1.2
SUBMITTALS
A.
1.3
A.
1.4
A.
B.
Protect plants, lawns, rock outcroppings, and other features to remain as a portion of final
landscaping.
C.
Protect bench marks, survey control points, existing structures, fences, sidewalks, paving and
curbs from grading equipment and vehicular traffic.
PART 2 - PRODUCTS
2.1
MATERIALS.
A.
Topsoil: Shall be soil suitable for sustaining grass and vegetation and shall not have any
particles larger than in diameter and shall be free of any trash, debris, or deleterious
material.
B.
Section 31 22 19
Grading
PART 3 - EXECUTIONS
3.1
EXAMINATION
A.
3.2
Verify that survey bench mark and intended elevations for the Work are as indicated.
PREPARATION
A.
B.
C.
D.
3.3
ROUGH GRADING
A.
Remove topsoil from areas to be further excavated, re-landscaped, or re-graded without mixing
with foreign materials.
B.
C.
D.
Do not remove wet subsoil, unless it is subsequently processed to obtain optimum moisture
content.
E.
When excavating through roots, perform work by hand and cut roots with sharp axe.
F.
Stability: Replace damaged or displaced subsoil to same requirements as for specified fill.
3.4
SOIL REMOVAL
A.
B.
C.
Stockpiles: Use areas designated on site; pile depth not to exceed 8 feet; protect from erosion.
3.5
FINISH GRADING
A.
B.
Remove debris, roots, branches, stones, in excess of inch in size. Remove soil contaminated
with petroleum products.
C.
In areas where vehicles or equipment have compacted soil, scarify surface to depth of 3 inches.
D.
E.
Section 31 22 19
Grading
2.
3.
4.
5.
F.
G.
H.
I.
Fine grade topsoil to eliminate uneven areas and low spots. Maintain profiles and contour of
subgrade.
J.
3.6
TOLERANCES
A.
Top Surface of Subgrade: Plus or minus 1/10 foot from required elevation.
B.
3.7
3.8
See Section 31 23 23.13, FILL AND BACKFILL for compaction density testing.
CLEANING AND PROTECTION
A.
Remove unused stockpiled topsoil and subsoil. Grade stockpile area to prevent standing water.
B.
END OF SECTION
Section 31 22 19
Grading
SECTION 31 23 16 - EXCAVATION
PART 1 - GENERAL
1.1
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 50 00 Temporary Facilities and Controls.
b.
Section 02 41 00 Demolition.
c.
Section 31 11 00 Site Preparation.
d.
Section 31 23 19 Dewatering.
e.
Section 31 50 00 Excavation Support Systems.
1.2
SUBMITTALS
A.
1.3
Shop Drawings:
1.
Excavation Plan, Detailing:
a.
Methods and sequencing of excavation.
b.
Proposed locations of stockpiled excavated material.
c.
Proposed and spoil disposal sites.
d.
Numbers, types, and sizes of equipment proposed to perform excavations.
QUALITY ASSURANCE
A.
1.4
A.
Material excavated when frozen or when air temperature is less than 32 degrees F shall not be
used as fill or backfill until material completely thaws.
B.
Material excavated during inclement weather shall not be used as fill or backfill until after
material drains and dries sufficiently for proper compaction.
1.5
B.
Clearing, Grubbing, and Stripping: Complete applicable Work specified in Section 31 11 00,
SITE PREPARATION, prior to excavating.
C.
Section 31 23 16
Excavation
D.
GENERAL
A.
Excavate to lines, grades, and dimensions shown and as necessary to accomplish Work.
Excavate to within tolerance of plus or minus 0.1-foot except where dimensions or grades are
shown or specified as maximum or minimum. Allow for forms, working space, granular base,
topsoil, and similar items, wherever applicable. Trim to neat lines where concrete is to be
deposited against earth.
B.
C.
3.2
UNCLASSIFIED EXCAVATION
A.
3.3
Excavation is unclassified. Complete all excavation regardless of the type, nature, or condition
of the materials encountered.
TRENCH WIDTH
A.
B.
Maximum Trench Width: Unlimited, unless otherwise shown or specified, or unless excess width
will cause damage to existing facilities, adjacent property, or completed Work.
3.4
B.
Excavated or plowed into trench bottom. Forming groove by compaction will not be acceptable.
3.5
Stockpile excavated material that is suitable for use as fill or backfill until material is needed.
Section 31 23 16
Excavation
B.
Post signs indicating proposed use of material stockpiled. Post signs that are readable from all
directions of approach to each stockpile. Signs should be clearly worded and readable by
equipment operators from their normal seated position.
C.
Confine stockpiles to within easements, rights-of-way, and approved work areas. Do not
obstruct roads or streets.
D.
Do not stockpile excavated material adjacent to trenches and other excavations unless
excavation side slopes and excavation support systems are designed, constructed, and
maintained for stockpile loads.
E.
Do not stockpile excavated materials near or over existing facilities, adjacent property, or
completed Work, if weight of stockpiled material could induce excessive settlement.
3.6
DISPOSAL OF SPOIL
A.
Dispose of excavated materials, which are unsuitable or exceed quantity needed for fill or
backfill,
B.
C.
Dispose of debris resulting from removal of organic matter, trash, refuse, and junk as specified
in Section 31 11 00, SITE PREPARATION, for clearing and grubbing debris.
3.7
EXCAVATION SAFETY
A.
3.8
A.
The excavation for all structures and facilities shall be in dewatered, firm, undisturbed earth. If,
in the Engineers opinion, the has been disturbed, corrective measures may include:
1.
Scarification and recompaction to 95 percent relative compaction or,
2.
Overexcavation and replacement with compacted granular fill.
B.
If the source of disturbance is determined to be the result of the actions, or inactions of the
Contractor, (for example, inadequate dewatering, disturbance by excavating or hauling
equipment) the cost of additional subgrade preparation will be at the Contractors expense.
END OF SECTION
Section 31 23 16
Excavation
SECTION 31 23 19 DEWATERING
PART 1 - GENERAL
1.1
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 50 00 Temporary Facilities and Controls.
1.2
As a minimum, include:
1.
Descriptions of proposed groundwater and surface water control facilities including, but
not limited to, equipment; methods; standby equipment and power supply, pollution
control facilities, discharge locations to be utilized, and provisions for immediate
temporary water supply as required by this section.
2.
Drawings showing locations, dimensions, and relationships of elements of dewatering
system.
B.
If system is modified during installation or operation revise or amend and resubmit Water
Control Plan.
GENERAL
A.
3.2
Remove and control surface and subsurface water during periods when necessary to properly
accomplish Work.
SURFACE WATER CONTROL
A.
B.
3.3
DEWATERING SYSTEMS
A.
Provide, operate, and maintain dewatering systems of sufficient size and capacity to permit
excavation and subsequent construction in dry conditions and to lower and maintain
groundwater level a minimum of 2 feet below the lowest point of excavation. Continuously
maintain excavations free of water, regardless of source, and until backfilled to final grade.
Section 31 23 19
Dewatering
B.
C.
Provide sufficient redundancy in each system to keep excavation free of water in event of
component failure.
D.
Provide supplemental ditches and sumps only as necessary to collect water from local seeps.
3.4
DISPOSAL OF WATER
A.
Obtain discharge permit for water disposal from authorities having jurisdiction.
B.
C.
Discharge water as required by discharge permit and in a manner that will not cause erosion or
flooding, or otherwise damage existing facilities, completed Work, or adjacent property.
D.
The discharge of ground water into treatment facilities will not be permitted unless specifically
authorized by the Owner. Remove solids from treatment facilities and perform other
maintenance of treatment facilities as necessary to maintain their efficiency, if Owner allows
groundwater discharge into facilities.
3.5
PROTECTION OF PROPERTY
A.
Make assessment of potential for dewatering induced settlement. Provide and operate devices
or systems, including but not limited to reinjection wells, infiltration trenches and cutoff walls,
necessary to prevent damage to existing facilities, completed Work, and adjacent property.
B.
Securely support existing facilities, completed Work, and adjacent property vulnerable to
settlement due to dewatering operations. Support shall include, but not be limited to, sheeting
bracing, underpinning, or compaction grouting.
3.6
If dewatering reduces quantity or quality of water produced by existing wells, temporarily supply
water to affected well owners from other sources. Furnish water of a quality and quantity equal
to or exceeding the quality and quantity available to the well owner prior to beginning Work or
as satisfactory to each well owner.
END OF SECTION
Section 31 23 19
Dewatering
SUMMARY
A.
Section includes: Work and materials required for fill and backfill for all excavations other than
trench type excavations.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 02 41 00 Demolition.
b.
Section 03 30 00 Cast-In-Place Concrete.
c.
Section 31 11 00 Site Preparation.
d.
Section 31 22 13 Subgrade Preparation.
e.
Section 31 23 16 Excavation.
f.
Section 31 23 23.16 Trench Backfill.
g.
Section 32 11 00 Base Course.
1.2
REFERENCES
A.
1.3
A.
Relative Compaction:
1.
Ratio, in percent, of as-compacted field dry density to laboratory maximum dry density as
determined in accordance with ASTM D698.
2.
Apply corrections for oversize material to either as-compacted field dry density or
maximum dry density, as determined by Engineer.
Section 31 23 23.13
Fill and Backfill
B.
C.
Relative Density: Calculated in accordance with ASTM D4254 based on maximum index density
determined in accordance with ASTM D4253 and minimum index density determined in
accordance with ASTM D4254.
D.
Prepared Ground Surface: Ground surface after completion of required demolition, clearing and
grubbing, scalping of sod, stripping of topsoil, excavation to grade, and preparation.
E.
Completed Course: A course or layer that is ready for next layer or next phase of Work.
F.
G.
H.
Well-Graded:
1.
A mixture of particle sizes with no specific concentration or lack thereof of one or more
sizes.
2.
Does not define numerical value that must be placed on coefficient of uniformity,
coefficient of curvature, or other specific grain size distribution parameters.
3.
Used to define material type that, when compacted, produces a strong and relatively
incompressible soil mass free from detrimental voids.
I.
Influence Area: Area within planes sloped downward and outward at 60-degree angle from
horizontal measured from:
1.
1-foot outside outermost edge at base of foundations or slabs.
2.
1-foot outside outermost edge at surface of roadways or shoulder.
3.
0.5-foot outside exterior at spring line of pipes or culverts.
J.
Borrow Material: Material from required excavations or from designated borrow areas on or near
site.
K.
Selected Backfill Material/Earth fill: Materials available onsite that Engineer determines to be
suitable for specific use.
L.
Imported Material: Materials obtained from sources suitable for specified use.
M.
Structural Fill: Fill materials as required under structures, pavements, and other facilities.
N.
Embankment Material: Fill materials required to raise existing grade in areas other than under
structures.
O.
Standard Specifications: When referenced in this section, shall mean the latest edition of the
Oklahoma Department of Transportation Specifications for highway construction.
1.4
SUBMITTALS
A.
Section 31 23 23.13
Fill and Backfill
1.5
QUALITY ASSURANCE
A.
1.6
A.
B.
Backfill against concrete structures only after concrete has attained compressive strength,
specified in Section 03 30 00, CAST-IN-PLACE CONCRETE. Obtain acceptance of concrete
work and attained strength prior to placing backfill.
C.
Backfill around water-holding structures only after completion of satisfactory leakage tests as
specified in Section 03 30 00, CAST-IN-PLACE CONCRETE.
D.
Do not place granular base, subbase, or surfacing until after subgrade has been prepared as
specified in Section 31 22 13, SUBGRADE PREPARATION.
PART 2 - PRODUCTS
2.1
2.2
A.
Excavated material from required excavations, free from rocks larger than 3 inches, from roots
and other organic matter, ashes, cinders, trash, debris, and other deleterious materials.
B.
Earth fill shall not be used beneath any slab-on-grade or equipment pad. Use granular fill, as
defined below.
2.3
GRANULAR FILL
A.
2.4
Type D aggregate meeting all the requirements of Section 703.01 of the Standard
Specifications.
WATER FOR MOISTURE CONDITIONING
A.
2.5
A.
Section 31 23 23.13
Fill and Backfill
2.6
B.
C.
D.
PART 3 - EXECUTION
3.1
GENERAL
A.
Keep placement surfaces free of water, debris, and foreign material during placement and
compaction of fill and backfill materials.
B.
Place and spread fill and backfill materials in horizontal lifts of uniform thickness, in a manner
that avoids segregation, and compact each lift to specified densities prior to placing succeeding
lifts. Slope lifts only where necessary to conform to final grades or as necessary to keep
placement surfaces drained of water.
C.
During filling and backfilling, keep level of fill and backfill around each structure and buried tank
even.
D.
Do not place fill or backfill, if fill or backfill material is frozen, or if surface upon which fill or
backfill is to be placed is frozen.
E.
F.
Tolerances:
1.
Final Lines and Grades: Within a tolerance of 0.1-foot unless dimensions or grades are
shown or specified otherwise.
2.
Grade to establish and maintain slopes and drainage as shown. Reverse slopes are not
permitted.
G.
Settlement: Correct and repair any subsequent damage to structures, pavements, curbs, slabs,
piping, and other facilities, caused by settlement of fill or backfill material.
H.
Fill and backfill materials shall be conditioned to a water content that is within 2 percentage
points (plus or minus) of the optimum required for compaction as determined by ASTM D698.
3.2
Under Facilities: Within influence area beneath structures, slabs, pavements, curbs, piping,
conduits, duct banks, and other facilities, backfill with granular fill, unless otherwise shown.
Place granular fill in lifts of 6-inch maximum thickness and compact each lift to minimum of 95
percent relative compaction as determined in accordance with ASTM D698, Method C.
Section 31 23 23.13
Fill and Backfill
B.
Subsurface Drainage: Backfill with granular drain material, where shown. Place granular drain
material in lifts of 6-inch maximum thickness and compact each lift to minimum of 90 percent
relative density.
C.
Other Areas: Backfill with earthfill to lines and grades shown, with proper allowance for topsoil
thickness where shown. Place in lifts of 6-inch maximum thickness and compact each lift to
minimum 95 percent relative compaction as determined in accordance with ASTM D698,
Method C.
3.3
FILL
A.
3.4
Outside Influence Areas Beneath Structures, Tanks, Pavements, Curbs, Slabs, Piping, and
Other Facilities: Unless otherwise shown, place earthfill as follows:
1.
Allow for 6-inch thickness of topsoil where required.
2.
Maximum 9-inch thick lifts.
3.
Place and compact fill across full width of embankment.
4.
Compact to minimum 95 percent relative compaction as determined in accordance with
ASTM D698, Method C.
5.
Dress completed embankment with allowance for topsoil, crest surfacing, and slope
protection, where applicable.
SITE TESTING
A.
Gradation:
1.
One sample from each 400 tons of finished product or more often as determined by
Engineer, if variation in gradation is occurring, or if material appears to depart from
Specifications.
2.
If test results indicate material does not meet Specification requirements, terminate
material placement until corrective measures are taken.
3.
Remove material placed in Work that does not meet Specification requirements.
B.
In-Place Density Tests: In accordance with ASTM D6938. During placement of materials, test
as follows:
1.
One test per every other lift per 200 lineal feet of roadway or trench.
2.
A minimum of two tests on granular fill beneath structures.
3.
A minimum of two test per 300 cubic yards during backfilling of walls.
C.
Testing shall be the Contractors responsibility and conducted by persons experienced in such
work.
3.5
3.6
A.
Replace excavation carried below grade lines shown or established by Engineer as follows:
1.
Beneath Footings: Concrete of strength equal to that of respective footing.
2.
Beneath Fill or Backfill: Same material as specified for overlying fill or backfill.
3.
Beneath Slabs-On-Grade: Granular fill.
4.
Trenches:
a.
Unauthorized Overexcavation: Either trench stabilization material or granular pipe
base material, as specified in Section 31 23 23.16, TRENCH BACKFILL.
b.
Authorized Overexcavation: Trench stabilization material, as specified in Section
31 23 23.16, TRENCH BACKFILL.
Section 31 23 23.13
Fill and Backfill
5.
Permanent Cut Slopes (Where Overlying Area is Not to Receive Fill or Backfill):
a.
Flat to Moderate Steep Slopes (3: 1, Horizontal Run: Vertical Rise or Flatter):
Earthfill.
b.
Steep Slopes (Steeper than 3: 1):
1)
Correct overexcavation by transitioning between areas and designed slope
adjoining areas, provided such cutting does not extend offsite or outside
easements and right-of-ways, or adversely impacts existing facilities, adjacent property, or completed Work.
2)
Backfilling overexcavated areas is prohibited unless, in opinion, backfill will
remain stable, and overexcavated material is replaced as compacted earth
fill.
END OF SECTION
Section 31 23 23.13
Fill and Backfill
SUMMARY
A.
Section includes: Bedding, backfill, and other related materials required to install a buried pipe
or conduit.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 Cast-In-Place Concrete.
b.
Section 31 23 19 Dewatering.
c.
Section 31 23 23.13 Fill and Backfill.
d.
Section 32 12 16 Asphalt Concrete Pavement.
1.2
REFERENCES
A.
Section 31 23 23.16
Trench Backfill
o.
p.
q.
r.
s.
1.3
ASTM D4318, Standard Test Methods for Liquid Limit, Plastic Limit, and Plasticity
Index of Soils.
ASTM D4533, Standard Test Method for Trapezoid Tearing Strength of
Geotextiles.
ASTM D4832, Standard Test Method for Preparation and Testing of Controlled
Low Strength Material (CLSM) Test Cylinders.
ASTM D4991, Standard Test Method for Leakage Testing of Empty Rigid
Containers by Vacuum Method.
ASTM D5034, Standard Test Method for Breaking Strength and Elongation of
Textile Fabrics (Grab Test).
DEFINITIONS
A.
Base Rock: Granular material upon which manhole bases and other structures are placed.
B.
Bedding Material: Granular material upon which pipes, conduits, cables, or duct banks are
placed.
C.
D.
E.
Pipe Zone: Backfill zone that includes full trench width and extends from prepared trench
bottom to an upper limit above top outside surface of pipe, conduit, cable or duct bank.
F.
Prepared Trench Bottom: Graded trench bottom after stabilization and installation of bedding
material.
G.
Relative Compaction: The ratio, in percent, of the as-compacted field dry density to the
laboratory maximum dry density as determined by ASTM D698. Corrections for oversize
material may be applied to either the as-compacted field dry density or the maximum dry
density, as determined by the Engineer.
H.
I.
Selected Backfill Material: Material available that the Engineer determines to be suitable for a
specific use.
J.
Well-Graded: A mixture of particle sizes that has no specific concentration or lack thereof of one
or more sizes producing a material type that, when compacted, produces a strong and relatively
incompressible soil mass free from detrimental voids. Well-Graded does not define any
numerical value that must be placed on the coefficient of uniformity, coefficient of curvature, or
other specific grain size distribution parameters.
1.4
SUBMITTALS
A.
B.
Samples:
1.
Trench stabilization material.
2.
Bedding and pipe zone material.
3.
Granular drain.
4.
Granular backfill.
5.
Earth backfill.
6.
Sand(s).
Section 31 23 23.16
Trench Backfill
7.
Geotextile.
C.
Quality Control Submittals: Catalog and manufacturers data sheets for compaction equipment.
D.
Certified Gradation Analysis: Submit not less than 30 days prior to delivery for imported
materials or anticipated use for excavated materials, except for trench stabilization material that
will be submitted prior to material delivery to site.
E.
Controlled Low Strength Material: Certified mix design and test results. Include material types
and weight per cubic yard for each component of mix.
PART 2 - PRODUCTS
2.1
MARKING TAPE
A.
Plastic:
1.
Inert polyethylene, impervious to known alkalis, acids, chemical reagents, and solvents
likely to be encountered in soil.
2.
Thickness: Minimum 4 mils.
3.
Width: 12 inches.
4.
Identifying Lettering: Minimum 1-inch high, permanent black lettering imprinted
continuously over entire length.
5.
Manufacturers and Products:
a.
Reef Industries; Terra Tape.
b.
Allen; Markline.
B.
Metallic:
1.
Solid aluminum foil, visible on unprinted side, encased in a protective high visibility, inert
polyethylene plastic jacket.
2.
Thickness: Minimum 5 mils.
3.
Width: 12 inches.
4.
Identifying Lettering: Minimum 1-inch high, permanent black lettering imprinted
continuously over entire length.
5.
Joining Clips: Tin or nickel-coated, furnished by tape manufacturer.
6.
Manufacturers and Products:
a.
Reef Industries; Terra Tape Sentry Line.
b.
Allen; Detectatape.
C.
Color: In accordance with APWA Uniform Color Code for Temporary Marking of Underground
Facilities.
Section 31 23 23.16
Trench Backfill
Color
Facility
Red
Orange
Yellow
Green
Blue
2.2
Clean, hard, durable 3-inch minus crushed rock gravel, or pit run, free from clay balls, other
organic materials, or debris.
B.
Uniformly graded from coarse to fine, less than 8 percent by weight passing the 1/4-inch sieve.
2.3
B.
Clean or gravelly sand with less than 5 percent passing No. 200 sieve, as determined in
accordance with ASTM D1140, or gravel or crushed rock within maximum particle size and
other requirements as follows unless otherwise specified.
1.
Duct Banks: 3/4-inch maximum particle size.
2.
PVC Irrigation System Piping, and Ductile Iron Pipe with Polyethylene Wrap: 3/8-inch
maximum particle size.
3.
Pipe Under 18 Inches Diameter: 3/4-inch maximum particle size, except 1/4-inch for
stainless steel pipe, copper pipe, tubing, and plastic pipe under 3 inches diameter.
4.
Pipe Greater than 18 Inches Diameter: 1-1/2-inch maximum particle size for ductile iron
pipe, concrete pipe, welded steel pipe, and pretensioned or prestressed concrete cylinder
pipe. 3/4-inch maximum particle size for PVC, FRP, or HDPE Pipe.
5.
Perforated Pipe: Granular drain material.
6.
Conduit and Direct-Buried Cable:
a.
Sand, clean or clean to silty, less than 12 percent passing the No. 200 sieve.
b.
Individual Particles: Free of sharp edges.
c.
Maximum Size Particle: Pass a No. 4 sieve.
d.
If more than 5 percent passes No. 200 sieve, the fraction that passes No. 40 sieve
shall be nonplastic as determined in accordance with ASTM D4318.
2.4
EARTH FILL
A.
2.5
A.
Select and proportion ingredients to obtain compressive strength between 50 and 150 psi at 28
days in accordance with ASTM D4832.
B.
Materials:
Section 31 23 23.16
Trench Backfill
1.
2.
3.
4.
2.6
CONCRETE BACKFILL
A.
2.7
A.
2.8
A.
B.
PART 3 - EXECUTION
3.1
TRENCH PREPARATION
A.
B.
Remove foreign material and backfill contaminated with foreign material that falls into trench.
3.2
TRENCH BOTTOM
A.
Firm Subgrade: Grade with hand tools, remove loose and disturbed material, and trim off high
areas and ridges left by excavating bucket teeth. Allow space for bedding material if shown or
specified.
B.
Soft Subgrade: If it is encountered that it may require removal to prevent pipe settlement, notify
Engineer. Engineer will determine the depth of overexcavation, if any, required.
3.3
B.
Place material over full width of trench in 6-inch lifts to required grade, providing allowance for
bedding thickness.
Section 31 23 23.16
Trench Backfill
C.
3.4
Compact each lift so as to provide a firm, unyielding support for the bedding material prior to
placing succeeding lifts.
BEDDING
A.
Furnish imported bedding material where, in the opinion of the Engineer, excavated material
unsuitable for bedding or insufficient in quantity.
B.
Place over the full width of the prepared trench bottom in two equal lifts when the required depth
exceeds 8 inches.
C.
Hand grade and compact each lift to provide a firm, unyielding surface.
D.
Minimum Thickness:
1.
Pipe, 15-inch and Smaller: 4 inches.
2.
Pipe, 18-inch to 36 inch: 6 inches.
3.
Pipe, 42-inch and Larger: 12 inches.
4.
Conduit: 3 inches.
5.
Direct-Buried Cable: 3 inches.
6.
Duct Banks: 3 inches.
E.
Check grade and correct irregularities in bedding material. Loosen top 1 to 2 inches of
compacted bedding material with a rake or by other means to provide a cushion before laying
each section of pipe, conduit, direct-buried cable, or duct bank.
F.
Install to form continuous and uniform support except at bell holes, if applicable, or minor
disturbances resulting from removal of lifting tackle.
G.
Bell or Coupling Holes: Excavate in bedding at each joint to permit proper assembly and
inspection of joint and to provide uniform bearing along barrel of pipe or conduit.
3.5
B.
Restrain pipe, conduit, cables, and duct banks as necessary to prevent their movement during
backfill operations.
C.
Place material simultaneously in lifts on both sides of pipe and, if applicable, between pipes,
conduit, cables, and duct banks installed in same trench.
1.
Pipes 10 Inches and Smaller Diameter: First lift less than or equal to pipe-diameter.
2.
Pipes Over 10 Inches Diameter: Maximum 6-inch lifts.
D.
Thoroughly tamp each lift, including area under haunches, with handheld tamping bars
supplemented by "walking in" and slicing material under haunches with a shovel to ensure that
voids are completely filled before placing each succeeding lift.
E.
After the full depth of the pipe zone material has been placed as specified, compact the material
by a minimum of three passes with a vibratory plate compactor only over the area between the
sides of the pipe and the trench walls.
Section 31 23 23.16
Trench Backfill
F.
3.6
A.
3.7
Continuously install marking tape along centerline of all buried piping, at depth of 2 feet.
Coordinate with piping installation drawings.
1.
Metallic Marking Tape: Install with nonmetallic piping
2.
Plastic Marking Tape: Install with metallic piping.
BACKFILL ABOVE PIPE ZONE
A.
General:
1.
Process excavated material to meet specified gradation requirements.
2.
Adjust moisture content as necessary to obtain specified compaction.
3.
Do not allow backfill to free fall into the trench or allow heavy, sharp pieces of material to
be placed as backfill until after at least 2 feet of backfill has been provided over the top of
pipe.
4.
Do not use power driven impact type compactors for compaction until at least 4 feet of
backfill is placed over top of pipe.
5.
Backfill to grade with proper allowances for topsoil, crushed rock surfacing, and
pavement thicknesses, wherever applicable.
6.
Backfill around structures with same class backfill as specified for adjacent trench unless
otherwise shown or specified.
B.
C.
Excavated Backfill: Backfill trench above the pipe zone with granular backfill in lifts not
exceeding 8 inches. Compact each lift to a minimum of 95 percent relative compaction prior to
placing succeeding lifts.
D.
Concrete Backfill:
1.
Place above bedding.
2.
Minimum Concrete Thickness: 6 inches on top and sides of pipe.
3.
Do not allow dirt or foreign material to become mixed with concrete during placement.
4.
Allow sufficient time for concrete to reach initial set before additional backfill material is
placed in trench.
5.
Prevent flotation of pipe.
6.
Begin and end concrete backfill within 4 inches of a pipe joint on each end.
7.
Do not encase pipe joints except within the limits of the concrete backfill.
E.
3.8
REPLACEMENT OF TOPSOIL
A.
B.
Maintain the finished grade of topsoil even with adjacent area and grade as necessary to
restore drainage.
Section 31 23 23.16
Trench Backfill
3.9
After each section of trench is backfilled, maintain the surface of the backfilled trench even with
the adjacent ground surface until final surface restoration is completed.
B.
Gravel Surfacing Rock: Add gravel surfacing rock where applicable and as necessary to keep
the surface of the backfilled trench even with the adjacent ground surface, and grade and
compact as necessary to keep the surface of backfilled trenches smooth, free from ruts and
potholes, and suitable for normal traffic flow.
C.
Topsoil: Add topsoil where applicable and as necessary to maintain the surface of the backfilled
trench level with the adjacent ground surface.
D.
Asphaltic Pavement: Replace settled areas or fill with asphalt as specified in Section 32 12 16,
ASPHALT CONCRETE PAVEMENT.
E.
Other Areas: Add excavated material where applicable and keep the surface of the backfilled
trench level with the adjacent ground surface.
3.10
A.
SETTLEMENT OF BACKFILL
Settlement of trench backfill, or of fill or facilities constructed over trench backfill, will be
considered a result of defective compaction of trench backfill.
END OF SECTION
Section 31 23 23.16
Trench Backfill
SUMMARY
A.
B.
C.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 30 00 - Cast-In-Place Concrete.
1.2
DEFINITIONS
A.
1.3
A.
1.4
A.
PART 2 - PRODUCTS
2.1
PRODUCTS
A.
PART 3 - EXECUTION
3.1
EXECUTION
A.
Section 31 23 23.33
Flowable Fill
END OF SECTION
Section 31 23 23.33
Flowable Fill
SUMMARY
A.
1.2
Section includes: Work and materials required to minimize erosion and comply with storm
water pollution prevention plan.
STABILIZATION
A.
B.
Permanent Stabilization:
1.
Permanently stabilize exposed soil surfaces at finished grades.
2.
Permanent stabilization methods include, but are not limited to, seeding (permanent),
mulching, and landscaping.
3.
Immediately perform permanent stabilization at each completed excavation and areas
except for areas that are scheduled to be redisturbed.
4.
Incorporate all permanent erosion control features into the project at the earliest practical
time.
C.
Buffer Zone: Undisturbed area or strip of natural vegetation or an established suitable planting
adjacent to a disturbed area that reduces erosion and runoff.
D.
1.3
SUBMITTALS
A.
B.
1.4
General: Prevent or reduce the discharge of pollutants to stormwater from all material delivery
and storage by minimizing the storage of hazardous materials storing materials in a designated
Section 31 32 00
Soil Erosion Stabilization
area, installing Secondary containment, conducting regular inspection, and training employees
and subcontractors.
B.
Seed:
1.
Furnish in standard containers with seed name, lot number, net weight, percentages of
purity, germination, and hard seed and maximum weed seed content, clearly marked for
each container of seed.
2.
Keep dry during storage.
C.
Hydroseeding Mulch: Mark package of wood fiber mulch to show air dry weight.
1.5
Install erosion and sediment control devices before starting earth disturbance activities and as
drainage facilities get constructed.
B.
Complete Soil Preparation: Seeding, fertilizing, mulching and matting on disturbed areas that
will require stabilization either because the area has reached final grade (permanent
landscaping) or because the area will remain unworked for over 14 days (temporary seeding)
during the wet season.
C.
D.
1.6
MAINTENANCE
A.
Operations:
1.
Seeded Areas: Perform during maintenance period to include:
a.
Watering: Keep seeded surface moist.
b.
Washouts: Repair by filling with topsoil, fertilizing, seeding, and mulching.
c.
Mulch: Replace wherever and whenever washed or blown away.
d.
Reseed unsatisfactory areas or portions thereof immediately at the end of the
maintenance period if a satisfactory stand has not been produced.
e.
Reseed during next planting season if scheduled end of maintenance period falls
after September 15.
f.
Reseed entire area if satisfactory stand does not develop by July 1 of the following
year.
g.
Mowing: Mow to 2 inches after grass height reaches 3 inches, and mow to
maintain grass height from exceeding 3-1/2 inches.
2.
Inspect, repair, and replace as necessary all erosion control measures during the time
period from start of construction to completion of construction.
3.
Inspect a minimum of at least once every 7 days or after a 1/2-inch storm event in a 24hour period.
4.
Furnish and install a rain gauge at the project site to monitor rainfall. At no time shall
more than 1-foot depth of sediment be allowed to accumulate in any erosion control
device.
B.
Sediment Removal:
1.
Remove sediment from erosion control devices and work into the grading plan at least
once a week as required to maintain proper operation of devices. The cleaning operation
shall not dispose of sediment offsite
Section 31 32 00
Soil Erosion Stabilization
2.
3.
Sediment shall be removed and the controls upgraded or repaired as needed as soon as
practicable, but not later than 2 days after the surrounding exposed ground has dried
sufficiently to prevent further damage from equipment needed for repair operations.
In the event of continuous rainfall over a 24 hour period, or other circumstances that
preclude equipment operation in the area, hand carry and install additional sediment
controls as approved by the Engineer.
PART 2 - PRODUCTS
2.1
FERTILIZER
A.
B.
Fertilizer shall have the following minimum percentage of plant food by weight:
1.
Summer Hydroseed Mix:
a.
Nitrogen: 20 percent.
b.
Phosphoric Acid: 10 percent.
c.
Potash: 10 percent.
2.
Winter Hydroseed Mix:
a.
Nitrogen: 16 percent.
b.
Phosphoric Acid: 8 percent.
c.
Potash: 0 percent.
2.2
SEED
A.
2.3
Common bermudagrass meeting the requirements of Section 735 of the Oklahoma Department
of Transportation Standard Specifications for Highway Construction.
MULCH
A.
B.
Straw:
1.
Clean salt hay or threshed straw of oats, wheat, barley, or rye, free from seed of noxious
weeds. Suitable for spreading with mulch blower equipment.
2.
Average Stalk Length: 6 inches.
3.
Seasoned before baling or loading.
2.4
B.
Section 31 32 00
Soil Erosion Stabilization
2.5
Co-extruded, copolymer laminate reinforced with a nonwoven grid of high strength nylon cord
submersed in a permanently flexible adhesive media allowing for equal tear resistance in all
directions.
B.
C.
D.
Manufacturers:
1.
Reef Industries, Inc., Houston, TX.
2.
Griffolyn Co., Houston, TX.
2.6
SILT FENCE
A.
B.
Fasteners: Heavy-duty wire staples at least 1-inch long, tie wires, or hog rings, as
recommended by manufacturer of geotextile.
C.
Filter Fabric: Polyester, polypropylene, or nylon filaments, woven into a uniform pattern, distinct
and measurable openings.
1.
Filaments: Resistant to damage from exposure to ultraviolet rays and heat.
2.
Material Edges: Finish so that, filaments retain their relative positions under stress.
D.
Required Value
ASTM D3776
50-70
160
ASTM D4632
Elongation, % max.
25
ASTM D1682
200
ASTM D3786
70
ASTM D4355
30 to 50
ASTM D4491
Test Method
Manufacturers:
1.
Polyfelt, Evergreen, AL.
2.
Dupont Co., Wilmington, DE.
Section 31 32 00
Soil Erosion Stabilization
3.
2.7
STRAW BALES
A.
2.8
Machine baled clean salt hay or straw of oats, wheat, barley, or rye, free from seed of noxious
weeds, using standard baling wire or string.
POSTS FOR STRAW BALES
A.
2.9
A.
Nontoxic materials that do not have an adverse effect on soil structure or establishment and
growth of vegetation.
PART 3 - EXECUTION
3.1
GENERAL
A.
Erosion control measures are required during all construction and site disturbance activity and
shall remain until permanent site ground covers are in place.
B.
The implementation of the erosion control plan and the construction maintenance, replacement
and upgrading the erosion control devices are the responsibility of the Contractor until all
construction is completed and landscaping established and approved. During the construction
period, the erosion control devices shall be upgraded for unexpected storm events and to
ensure that sediment and sediment laden water do not leave the site.
C.
Maintain existing buffer zones adjacent to project limits. Keep all construction equipment, debris
and soils out of the natural buffer zone.
3.2
Provide a graveled construction access at each access point between the site and any public or
private road or other paved surface.
B.
Place subgrade geotextile, as specified, on the ground prior to erosion control rock placement.
C.
Place erosion control rock over the geotextile to a minimum thickness of 8 inches.
D.
Minimum dimensions for construction entrances are 50-foot in length by 16-foot width.
E.
Contractor shall provide a minimum of 4 inches of erosion control rock for each entrance 3
times during the project at times directed by the Engineer to maintain proper function. More
frequent applications of rock may be required, and if so, shall be considered as incidental work.
3.3
SOIL PREPARATION
A.
Before start of hydroseeding, and after surface has been shaped and graded, and lightly
compacted to uniform grade, scarify soil surface to minimum depth of 1 inch.
Section 31 32 00
Soil Erosion Stabilization
3.4
FERTILIZER
A.
Apply evenly over area in accordance with manufacturers instructions. Mix into top 1-inch of
soil.
B.
Application Rate: 5 pounds per 1,000 square foot over areas to be seeded. Use of approved
hydraulic equipment to sow seed and distribute fertilizer at the same time will be acceptable.
3.5
SEEDING
A.
Prepare 1-inch depth seed bed; obtain Engineers acceptance prior to proceeding.
B.
Apply by hydroseeding method on moist soil, but only after free surface water has drained
away. Prevent drift and displacement of mixture into other areas.
C.
Summer Application:
1.
Prepare and apply slurry as follows:
Item
2.
3.6
Rate
Seed Mix
Fertilizer
As recommended by manufacturer
Water
As necessary
MULCHING
A.
Apply uniformly on disturbed areas that will remain undisturbed for 7 days or more, as
requested by Engineer, and on all seeded areas.
B.
Application: Sufficiently loose to permit penetration of sunlight and air circulation, and
sufficiently dense to shade ground, reduce evaporation rate, and prevent or materially reduce
erosion of underlying soil.
1.
Straw: Apply by hand or mechanical means to minimum depth of 2 inches.
2.
Wood Cellulose Fiber: 1,000 to 1,500 pounds per acre.
3.7
B.
C.
At top of slope, entrench material in a 6-inch by 6-inch trench and staple at 1-foot intervals. At
the bottom of the slope, extend the mat 2 feet beyond the toe of slope, turn material under 4
inches and staple at 1-foot intervals.
D.
Mats shall be stapled in place as they are installed down the slope face. The mat shall have
direct contact with the soil surface.
E.
Overlap:
1.
Lengthwise: 1-foot minimum.
Section 31 32 00
Soil Erosion Stabilization
2.
3.8
Place on areas where hydroseeding and erosion control matting have not controlled erosion
and over all temporary stockpiles.
B.
Install in single thickness, strips parallel to direction of drainage. Anchor plastic in 6-inch by 6inch trench backfilled with compacted native material.
C.
Maintain tightly in place by using sand bags on ropes with a maximum 10-foot grid spacing in all
directions.
D.
E.
3.9
SILT FENCE
A.
B.
One-piece filter fabric or continuously sewn to make one-piece filter fabric for full height of the
fence, including portion buried in the toe trench.
C.
When joints are necessary, splice filter fabric together only at a support post, with a minimum 6inch overlap, and securely fasten both ends to support post.
D.
Filter fabric shall not extend more than 24 inches above the ground surface. Securely fasten to
upslope side of each support post using ties. Filter fabric shall not be stapled to existing trees.
E.
Fasten wire mesh material support fence securely to upslope side of post fasteners. Extend
wire into the trench a minimum of 4 inches, and not more than 36 inches above the ground
surface.
F.
Take precaution not to puncture filter fabric during installation. Repair or replace damaged area.
G.
Remove silt fence after upslope area has been permanently stabilized. Immediately dress
sediment deposits remaining after the silt fence has been removed to conform to existing grade.
Prepare and seed graded area.
3.10
A.
B.
3.11
STRAW BALES
A.
Embed minimum of 4 inches in flat-bottomed trench. Place across swales or ditches to reduce
velocities of concentrated flows. Space bales a minimum of 100-foot spacing.
B.
Place with ends tightly abutting or overlapped. Corner abutment is not acceptable.
Section 31 32 00
Soil Erosion Stabilization
C.
Install so that bale bindings are oriented around the sides and not over the top and bottom of
the bale.
D.
Use two posts for each bale. Drive posts through the bale until top of post is flush with top of
bale.
E.
3.12
DUST CONTROL
A.
Apply appropriate dust control measures on a continuous basis until permanent stabilization
measures are in place.
B.
Apply on construction routes and other disturbed areas subject to surface dust movement and
where off-site damage may occur if dust is not controlled.
C.
3.13
CLEAN-UP
A.
Sediment trapped in erosion control devices shall be regraded into the slopes on the site. Do
not flush sediment-laden water into the drainage system.
B.
After site restoration is complete and when approved by the Engineer, all temporary erosion
control measures shall be completely removed. Immediately shape and permanently stabilize
areas affected by the removal process.
C.
Silt fence, straw bales, reinforced plastic covering, and any other erosion control devices shall
be disposed off site to locations that are approved by federal, state, and local authorities.
END OF SECTION
Section 31 32 00
Soil Erosion Stabilization
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 31 23 16 Excavation.
c.
Section 31 23 23.16 Trench and Backfill.
d.
Section 31 05 19 - Geotextile Filter Fabric.
1.2
REFERENCE STANDARDS
A.
1.3
A.
B.
PART 2 - PRODUCTS
2.1
MATERIALS
A.
The riprap shall be hard, sound, and durable. It shall be reasonably free of fines and shall be
well graded between the maximum and minimum rock sizes so as to produce a minimum of
voids. No riprap shall be placed on the project until it has been accepted by Engineer.
B.
The minimum density of stone shall be 130 pounds per cubic foot and the maximum absorption
shall be 6 percent.
Section 31 37 00
Rip Rap
C.
The shall be well graded with an average diameter of 12 to 18 and the maximum size shall not
be greater than 24-inches in any dimension and approximately 50 percent of the material shall
consist of pieces weighing 20 pounds or more. The stones shall be predominantly angular in
shape with not more than 25 percent having a length more than 2.5 times its breadth or
thickness and none having a length exceeding 3.0 times its breadth or thickness.
D.
E.
Contractor shall obtain and submit certification that the proposed rock meets density and
absorption requirements specified herein. Testing for certification shall be in accordance with
ASTM C97. Certified test results shall be submitted to Engineer prior to the use of the proposed
material as riprap.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
The riprap layer shall be a minimum of 24-inches thick when placed over the geotextile fabric.
B.
When placed on the embankment, the smaller stones shall be well distributed throughout the
mass. Hand placing may be required to obtain the results specified above.
C.
The areas to be protected with riprap shall be dressed to the lines and grades shown on the
Drawings and covered with the geotextile fabric prior to placing the riprap.
D.
Riprap graded so that the smaller stones are uniformly distributed throughout the mass shall
then be placed, starting at the toe of the slope, with a maximum vertical drop onto the geotextile
fabric of 2 feet. In no case shall stones be allowed to roll down the fabric covered slope.
Placement of the riprap over the fabric shall proceed so that the upper boundary of the riprap
layer is at essentially the same level for the entire length of the fabric.
E.
Care shall be taken so that the geotextile fabric is not damaged during riprap installation. Any
rips or tears shall be repaired by Contractor, as specified in Section 31 05 19, GEOTEXTILE
FILTER FABRIC, before proceeding with further riprap installation.
END OF SECTION
Section 31 37 00
Rip Rap
SUMMARY
A.
1.2
Section includes: Work required to install and remove excavation support systems.
SUBMITTALS
A.
Shop Drawings:
1.
Excavation support plan.
2.
Movement monitoring plan.
B.
Quality Control Submittals: Movement measurement and data and reduced results indicating
movement trends.
1.3
QUALITY ASSURANCE
A.
GENERAL
A.
Design, provide, and maintain shoring, sheeting, and bracing as necessary and where shown to
support the sides of excavations and to prevent detrimental settlement and lateral movement of
existing facilities, adjacent property, and completed Work.
B.
Minimum areas for sharing, sheeting and bracing are shown on the Drawings. It will be the
Contractors responsibility to determine if areas will require excavation slope retention to protect
existing structures and facilities from damage resulting from the Contractors excavation or
excavation methods.
C.
The Contractor will also be responsible for providing shoring, sheeting and bracing of
excavations as needed for worker safety and as may be required by federal, state, and local
regulations.
3.2
3.3
A.
Section 31 50 00
Excavation Support Systems
2.
3.
4.
B.
Movement monitoring shall be done on every existing structure that is adjacent to the
Contractors excavations.
C.
Results of movement monitoring will be delivered for the Engineer at least once a week.
3.4
Do not begin to remove excavation support until it can be removed without damage to existing
facilities, completed Work, or adjacent property.
B.
Remove excavation support and protection systems when construction has progressed
sufficiently to support excavation and earth and hydrostatic pressures. Remove in stages to
avoid disturbing underlying soils and rock or damaging structures, pavements, facilities, and
utilities. Maintain soil wall support as excavation is backfilled.
C.
Fill voids immediately with approved backfill compacted to density specified in Section 31 23
23.13, FILL AND BACKFILL.
END OF SECTION
Section 31 50 00
Excavation Support Systems
SUMMARY
A.
Section includes: Work required to install and remove temporary dam systems.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 31 22 19- Grading
b.
Section 31 23 16- Excavation
c.
Section 31 23 19- Dewatering
d.
Section 31 32 00- Soil Erosion Stabilization
1.2
SUBMITTALS
A.
Shop Drawings:
1.
Temporary damming system installation plan.
2.
Temporary damming system removal plan.
3.
Dewatering plan per requirements outlined in section 31 23 19 Dewatering.
4.
Excavation support plan as outlined below.
B.
GENERAL
A.
Design, provide, and maintain shoring, sheeting, and bracing as necessary and where shown to
support the sides and to prevent detrimental settlement and lateral movement of existing
facilities, adjacent property, and completed Work.
B.
Minimum areas for sharing, sheeting and bracing are shown on the Drawings. It will be the
Contractors responsibility to take all necessary precautions to protect other structures and
facilities from damage resulting from the Contractors excavation or damming methods.
C.
The Contractor will be responsible for observing all local, state, and federal regulations
pertaining to protection of the natural environment.
Section 31 51 00
Temporary Damming Systems
D.
3.2
The Contractor will also be responsible for providing shoring, sheeting and bracing of
excavations as needed for worker safety and as may be required by federal, state, and local
regulations.
EXCAVATION SUPPORT PLAN
A.
B.
3.3
Details of shoring, bracing, sloping, or other provisions for worker protection of existing
structures or facilities.
Design assumptions and calculations.
Methods and sequencing of installing excavation support.
Methods and sequencing of removing excavation support.
Proposed locations of stockpiled excavated material.
Minimum lateral distance from the crest of slopes for vehicles and stockpiled excavated
materials.
Do not begin to remove temporary damming system until it can be removed without damage to
existing facilities, completed Work, or adjacent property.
B.
Remove temporary damming and protection systems when construction has progressed
sufficiently to support design loads. Remove in stages, as outlined in the sequencing plans, to
avoid disturbing underlying soils and rock or damaging structures, pavements, facilities, and
utilities.
END OF SECTION
Section 31 51 00
Temporary Damming Systems
DIVISION 32
EXTERIOR IMPROVEMENTS
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 31 22 13 Subgrade Preparation.
1.2
REFERENCES
A.
1.3
A.
Completed Course: Compacted, unyielding, free from irregularities, with smooth, tight, even
surface, true to grade, line, and cross-section.
B.
Completed Lift: Compacted with uniform surface reasonably true to cross- section.
C.
1.4
SUBMITTALS
A.
Section 32 11 00
Base Course
PART 2 - PRODUCTS
2.1
2.2
A.
B.
Final approval of aggregate material will be based on materials test results on installed
materials.
C.
Should separation of course from fine materials occur during processing or stockpiling,
immediately change methods of handling materials to correct uniformity in grading.
PART 3 - EXECUTION
3.1
PREPARATION
A.
B.
C.
3.2
EQUIPMENT
A.
B.
Compaction Equipment: Adequate in design and number to provide compaction and obtain the
specified density for each layer.
3.3
Hauling Materials:
1.
Do not haul over surfacing in process of construction.
2.
Loads: Of uniform capacity.
3.
Measure capacity of truck to determine vehicle load and quantity.
4.
Maintain consistent gradation of material delivered; loads of widely varying gradations will
be cause for rejection.
B.
Spreading Materials:
1.
Distribute material to provide required density, depth, grade and dimensions with
allowance for subsequent lifts.
2.
Produce even distribution of material upon roadway without segregation.
3.
Should segregation of coarse from fine materials occur during placing, immediately
change methods of handling materials to correct uniformity in grading.
3.4
CONSTRUCTION OF COURSES
A.
General: Complete each lift in advance of laying succeeding lift to provide required results and
adequate inspection.
Section 32 11 00
Base Course
B.
3.5
Base Course:
1.
Maximum Completed Lift Thickness: 6 inches.
2.
Completed Course Total Thickness: As shown.
3.
Spread lift on preceding course to required cross-section.
4.
Lightly blade and roll surface until thoroughly compacted.
5.
Add keystone to achieve compaction and as required when aggregate does not compact
readily due to lack of fines or natural cementing properties, as follows:
a.
Use base 1/4-minus crushed aggregate material as keystone.
b.
Spread evenly on top of crushed base course, using spreader boxes or chip
spreaders.
c.
Roll surface until keystone is worked into interstices of crushed base course
without excessive displacement. ,
d.
Continue operation until course has become thoroughly keyed, compacted, and
will not creep or move under roller.
6.
Blade or broom surface to maintain true line, grade, and cross-section.
ROLLING AND COMPACTION
A.
Blade or otherwise work existing surface as necessary to achieve a smooth and thoroughly
compacted surface.
B.
Commence compaction of each layer of base after spreading operations and continue until
density of 100 percent of maximum density has been achieved as determined by AASHTO T
99.
C.
Commence rolling at outer edges of surfacing and continue toward center; do not roll center of
road first.
D.
E.
Place and compact each lift to required density before succeeding lift is placed.
F.
Bind up preceding course before placing leveling course. Remove floating or loose stone from
surface.
G.
Blade or otherwise work surfacing as necessary to maintain grade and cross- section at all
times, and to keep surface smooth and thoroughly compacted.
H.
Surface Defects: Remedy surface defects by loosening and rerolling entire area, including
surrounding surface, until thoroughly compacted.
1.
Finished Surface: True to grade and crown before proceeding with surfacing.
3.6
SURFACE TOLERANCES
A.
Finished Surface of Base Course: Within plus or minus 0.04-foot of grade shown at any
individual point.
B.
Overall Average: Within plus or minus 0.01-foot from crown and grade specified.
3.7
Section 32 11 00
Base Course
3.
4.
B.
Show proof that areas meet specified requirements before identifying density test
locations.
Perform a minimum of 2 tests on completed course per 200 cubic yards of material
placed in accordance with T 191, or T 238 at locations acceptable to Engineer.
Cleaning
1.
Remove excess material; clean stockpile areas of aggregate.
END OF SECTION
Section 32 11 00
Base Course
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 03 30 00 Cast-in-Place Concrete.
c.
Section 07 92 00 Joint Sealants.
d.
Section 32 11 00 Base Course.
1.2
REFERENCES
A.
Section 32 13 13
Portland Cement Concrete Paving
1.3
SUBMITTALS
A.
B.
Product Data: Provide data on joint filler, admixtures, and curing compound.
C.
Design Data: Indicate pavement thickness, designed concrete strength, reinforcement, and
typical details.
1.4
QUALITY ASSURANCE
A.
B.
C.
D.
1.5
ENVIRONMENTAL REQUIRMENTS
A.
Do not place concrete when base surface temperature is less than 40 degrees F, or surface is
wet or frozen.
PART 2 - PRODUCTS
2.1
FORM MATERIALS
A.
B.
Joint Filler: Preformed; non-extruding bituminous type (ASTM D1751) or sponge rubber or cork
(ASTM D1752).
1.
Thickness: 1/2 inch.
2.2
REINFORCEMENT
A.
Reinforcing Steel: ASTM A615 / A615M Grade 60 (420); deformed billet steel bars; unfinished
finish.
B.
Steel Welded Wire Reinforcement: Plain type, ASTM A185; in flat sheets; unfinished.
C.
Dowels: ASTM A615 Grade 60 (420); deformed carbon steel bars; unfinished finish.
2.3
CONCRETE MATERIALS
A.
2.4
A.
2.5
A.
Proportioning Normal Weight Concrete: Comply with ACI 211.1 recommendations. Refer to Civil
Plans and Specifications for site concrete design.
Section 32 13 13
Portland Cement Concrete Paving
B.
Concrete Strength: Establish required average strength for each type of concrete on the basis
of field experience or trial mixtures, as specified in ACI 301.
1.
For trial mixtures method, employ independent testing agency acceptable to Owners
Representative for preparing and reporting proposed mix designs.
C.
D.
Concrete Properties:
1.
Refer to Construction Documents.
2.6
MIXING
A.
On Project Site: Mix in drum type batch mixer, complying with ASTM C685. Mix each batch not
less than 1-1/2 minutes and not more than 5 minutes.
B.
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Verify compacted subgrade is acceptable and ready to support paving and imposed loads.
B.
3.2
SUBBASE
A.
3.3
A.
3.4
A.
Place and secure forms to correct location, dimension, profile, and gradient.
B.
Assemble formwork to permit easy stripping and dismantling without damaging concrete.
C.
Place joint filler vertical in position, in straight lines. Secure to formwork during concrete
placement.
3.5
REINFORCEMENT
A.
B.
3.6
PLACING CONCRETE
A.
B.
Ensure reinforcement, inserts, embedded parts and formed joints are not disturbed during
concrete placement.
Section 32 13 13
Portland Cement Concrete Paving
C.
Place concrete continuously over the full width of the panel and between predetermined
construction joints. Do not break or interrupt successive pours such that cold joints occur.
D.
Apply surface retarder to all exposed surfaces in accordance with manufacturers instructions.
3.7
JOINTS
A.
B.
Place control and expansion joints and edge of new concrete to align with existing joints
beyond.
C.
Evenly space joint patterns not dimensioned on plans. Align joints with corners of masonry
where shown on plans.
D.
Place joint filler between new sidewalks and building or adjacent saw cut paving.
3.8
FINISHING
A.
Sidewalk and Ramp Paving: Light broom, texture perpendicular to pavement direction.
B.
Place during compound on exposed concrete surfaces immediately after finishing. Apply in
accordance with manufacturers instructions.
3.9
JOINT SEALING
A.
3.10
A.
B.
3.11
A.
B.
Compressive Strength Tests: ASTM C39 / C39M. For each test, mold and cure three concrete
test cylinders. Obtain test samples for every 100 cu yd or less of each class of concrete placed.
1.
Take one additional test cylinder during cold weather concreting, cured on job site under
same conditions as concrete it represents.
2.
Perform one slump test for each set of test cylinders taken.
C.
Maintain records of placed concrete items. Record date, location of pour, quantity, air
temperature, and test samples taken.
Section 32 13 13
Portland Cement Concrete Paving
3.12
PROTECTION
A.
Immediately after placement, protect pavement from premature drying, excessive hot or cold
temperatures and mechanical injury.
B.
Do not permit pedestrian traffic over pavement until 75 percent design strength of concrete has
been achieved.
END OF SECTION
Section 32 13 13
Portland Cement Concrete Paving
SUMMARY
A.
Section includes: Work and materials required to install chain link fence and gates.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 02 41 00 Demolition.
b.
Section 03 30 00 Cast-In-Place Concrete.
1.2
REFERENCES
A.
Section 32 31 13
Chain Link Fence and Gates
2.
3.
1.3
Institute of Electrical and Electronic Engineers (IEEE), Inc.: National Electrical Safety
Code.
National Electrical Manufacturers Association (NEMA): 250, Enclosures for Electrical
Equipment (1,000 volts max.).
DEFINITIONS
A.
1.4
A.
Shop Drawings:
1.
Detailed information and specifications for materials, finishes, and dimensions.
2.
Card access system serial communication interface card code message format.
B.
Samples: Approximately 6 inches square, or 6 inches long of posts, rails, braces, fabric, wire,
ties, and fittings.
C.
1.5
Complete necessary site preparation and grading before installing chain link fence and gates.
PART 2 - PRODUCTS
2.1
GENERAL
A.
2.2
Match style, finish, and color of each fence component with that of other fence components.
CHAIN LINK FENCE FABRIC
A.
B.
C.
D.
E.
Diamond Count: Manufacturers standard and consistent for fabric furnished of same height.
F.
Loops of Knuckled Selvages: Closed or nearly closed with space not exceeding diameter of
wire.
G.
2.3
POSTS
A.
General:
Section 32 31 13
Chain Link Fence and Gates
1.
2.
3.
4.
5.
Strength and Stiffness Requirements: ASTM F1043, Light Industrial Fence, except as
modified in this section.
Steel Pipe: ASTM F1083.
Roll-Formed Steel Shapes: from ASTM A1018, Grade 45, Steel.
Lengths: Manufacturers standard with allowance for minimum embedment below finished
grade of 22 inches plus 3 inches for each 1 foot of fence height greater than 4 feet.
Protective Coatings:
a.
Zinc Coating: ASTM F1043, Type A external and internal coating.
B.
Line Posts:
1.
Steel Pipe:
a.
Outside Diameter: 2.375-inch.
b.
Weight: 3.65 pounds per foot.
C.
D.
2.4
2.5
FENCE FITTINGS
A.
B.
Post and Line Caps: Designed to accommodate passage of top rail through cap, where top rail
required.
C.
D.
Tension Bars:
1.
One-piece, no exceptions to ASTM F626.
2.
Equal in length to full height of fabric.
E.
F.
Barb Arms: 45-degree arms for supporting three strands of barbed wire.
2.6
TENSION WIRE
A.
Zinc-coated steel marcelled tension wire conforming to ASTM A824, Type II, Class 2.
Section 32 31 13
Chain Link Fence and Gates
2.7
BARBED WIRE
A.
2.8
A.
General:
1.
Gate Operation: Opened and closed easily by one person.
2.
Welded Steel Joints: Paint with zinc-based paint.
3.
Chain Link Fabric: Attached securely to gate frame at intervals not exceeding 15 inches.
B.
2.9
CONCRETE
A.
2.10
A.
B.
C.
All items noted as salvageable shall not be bent, twisted, dented, or damaged in any way. Any
such items will not be considered for reuse.
Section 32 31 13
Chain Link Fence and Gates
D.
All items not considered for salvage or reuse shall be disposed of offsite at the Contractors
expense. See Section 02 41 00, DEMOLITION.
PART 3 - EXECUTION
3.1
GENERAL
A.
Install chain link fences and gates in accordance with ASTM F567, except as modified in this
section, and in accordance with fence manufacturers recommendations, as approved by
Engineer. Erect fencing in straight lines between angle points.
B.
Provide all necessary hardware for a complete fence and gate installation.
3.2
PREPARATION
A.
3.3
A.
B.
C.
D.
Before concrete sets, crown and finish top of concrete to readily shed water.
3.4
BRACING
A.
3.5
Brace gate and corner posts diagonally to adjacent line posts to ensure stability.
TOP RAILS
A.
3.6
Install top rail sleeves with springs at 105 feet maximum spacing to permit expansion in rail.
CHAIN LINK FABRIC
A.
B.
3.7
BARBED WIRE
A.
3.8
Install three strands of barbed wire on brackets, tighten, and secure at each bracket.
GATES
A.
Hang gates and adjust hardware so gates operate satisfactorily from open or closed position.
B.
Set gate stops in concrete to engage center drop rod or plunger bar.
Section 32 31 13
Chain Link Fence and Gates
3.9
3.10
Gate Tests: Prior to acceptance of installed gates and gate operator systems, demonstrate
proper operation of gates under each possible open and close condition specified.
REUSE OF EXISTING FENCE MATERIAL
A.
Existing fence material shall be installed on new posts using new tension bars, brace bands,
and tension wire.
B.
Existing fence fabric shall not be spliced to new fence fabric at mid-length between posts where
the existing fence fabric ends. A pull post shall be installed with new brace bands, tension
bands, and tension wire. Provide a knuckled selvage at the cut portion of the fence as shown on
the Drawings.
END OF SECTION
Section 32 31 13
Chain Link Fence and Gates
SUMMARY
A.
Section includes:
1.
Fertilizer.
2.
Mulch.
3.
Seed.
4.
Preparation.
5.
Maintenance.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 31 22 19, GRADING.
b.
Section 31 23 16, EXCAVATION.
c.
Section 31 11 00, SITE PREPARATION.
1.2
1.3
Alternate methods from those specified will be considered for use, provided that in the
Engineers opinion the end product will be equal to or exceed that which would result from the
specified methods and products.
DEFINITIONS
A.
1.4
Weeds: Includes Dandelion, Jimsonweed, Quackgrass, Horsetail, Morning Glory, Rush Grass,
Mustard, Lambsquarter, Chickweed, Cress, Crabgrass, Canadian Thistle, Nutgrass, Poison
Oak, Blackberry, Tansy Ragwort, Bermuda Grass, Johnson Grass, Poison Ivy, Nut Sedge,
Nimble Will, Bindweed, Bent Grass, Wold Garlic, Perennial Sorrel, and Brome Grass.
REGULATORY REQUIREMENTS
A.
1.5
A.
1.6
Provide seed mixture in containers showing percentage of seed mix, year of production, net
weight, date of packaging, and location of packaging.
MAINTENANCE DATA
A.
B.
Include maintenance instruction, cutting method, maximum grass height, types, application
frequency, and recommended coverage of fertilizer.
Section 32 92 19
Seeding, Fertilizing and Mulching
1.7
B.
Deliver fertilizer in water proof bags showing weight, chemical analysis, and name of
manufacturer.
PART 2 - PRODUCTS
2.1
AGRICULTURAL LIMESTONE
A.
2.2
Shall be agricultural limestone with not less than 90 percent passing the No. 4 sieve and
containing not less than 40 percent calcium carbonate equivalent. Lime shall be applied at the
rate recommended by soil test.
FERTILIZER
A.
Shall be a standard commercial product which when applied at the proper rate will supply the
equivalent quantity of total nitrogen, available phosphoric acid and soluble potash specified.
Fertilizer shall be delivered to the site in bags or other suitable containers, each fully labeled,
conforming to applicable state fertilizer laws, and bearing the name, trade name or trademark,
and warranty of the producer.
B.
2.3
MULCH
A.
2.4
Shall be vegetive mulch consisting of cereal straw from stalks of oats, rye, wheat or barley.
Straw shall be free of prohibited weed seeds as stated in State Seed Law and shall be relatively
free of all other noxious and undesirable seeds. Straw shall be clean and bright, relatively free
of foreign material and be dry enough to be spread properly.
SEED
A.
Seed shall be a mixture with the specified minimum purity and germination requirements, as
follows:
% Mix
Seed Type
(By Wt.)
Purity %
Germination %
Kentucky K-31 Fescue
52
97
85
Creeping Red Fescue
18
85
80
Rye Grass
8
98
85
Rye Grain
22
Variation in the above mix to suit local conditions or time of year may be required.
B.
C.
Seed shall be sown at a rate of 217 pounds of seed mix per acre for drill seeding. Seed mixture
shall be thoroughly mixed prior to application.
Section 32 92 19
Seeding, Fertilizing and Mulching
PART 3 - EXECUTION
3.1
GENERAL
A.
The application of fertilizer, seed, and mulch shall follow each other in successive sequence as
closely as possible. Seeding shall be accomplished in the first of the following two periods after
completion of earthwork.
February 15 to May 1st
September 1st to October 1st
B.
3.2
Seeding outside the specified seeding periods may be permitted at the Engineers option,
provided the Contractor is willing to make appropriate modifications to his seeding operations,
and will guarantee the crop.
INSPECTION
A.
Contractor must request that Engineer inspect site grading, clean-up and surface preparation to
determine if site is ready for the seeding, fertilizing and mulching operations.
B.
3.3
SURFACE PREPARATION
A.
3.4
A.
Fertilizer and lime shall be dressed evenly over the areas to be seeded using approved
mechanical type spreading equipment.
B.
Fertilizer and lime after spreading shall be immediately incorporated into the soil to a depth of
approximately 2 inches, by chisel, spike tooth harrow, or other approved methods.
3.5
SEEDING METHODS
A.
General methods: The Contractor shall employ a satisfactory method of sowing by use of either
approved mechanical hand seeders or mechanical power-driven drills. When delays in
operation carry the work beyond the specified planting seasons, or when conditions are such
that by reason of drought, high winds, excessive moisture, or other factors, satisfactory results
are not likely to be obtained, seeding shall stop. It will be resumed only where the desired
results are probable or when approved alternate procedures have been adopted.
B.
Broadcast seeding: When broadcast seeding is utilized, the seed shall be uniformly broadcast
by mechanical hand seeder, in two directions at right-angles to each other and at 1/2 of the
specified rate per acre in each direction. After the seed is broadcast it shall be covered by an
approved method to a depth of 1/3 inch to 3/4 inch. Broadcast seeding shall not be done in
windy weather.
Section 32 92 19
Seeding, Fertilizing and Mulching
C.
Drill seeding: When drilling is utilized, it shall be done with approved equipment best suited to
perform the work under prevailing conditions. The seed shall be uniformly drilled to a depth of
one-third (1/3) inch to three-fourths (3/4) inch at the rate per acre specified. Drill seeding may
be required in windy weather.
D.
Prior to start of seeding, the Contractor shall demonstrate that the application of seed is being
made at the specified rate. A final check of the total quantity of seed used shall be made
against the area seeded. If the check shows that the Contractor has not applied seed at the
specified rate, he shall uniformly distribute seed at a rate calculated to meet the shortage.
E.
The Contractor shall maintain the seeded areas until all fertilizing, seeding and mulching is
complete and the work accepted by the Engineer. Areas damaged from the Contractors own
operations shall be repaired at his expense. After acceptance of the work the Contractor will
not be held responsible for erosion due to weather, or conditions not due to the Contractors
own operations or negligence. The Contractor is not required to guarantee a crop, if seeding is
done during the specified seeding periods.
3.6
MULCHING
A.
Immediately after seeding, the Contractor shall apply vegetative mulch at a rate between 1-1/2
and 2-1/2 tons per acre to all seeded areas. Quantity of mulch shall be adjusted within the
above limits, as directed by the Engineer, to the particular area or slope being mulched. Total
application of mulch for the project shall average approximately 2 tons per acre. Mulch shall be
applied by mechanical mulch spreaders equipped to eject by means of a constant air stream
controlled quantities of the vegetative mulch.
B.
Mulch shall be embedded by a disc type roller having flat serrated discs spaced not more than
10 inches apart, with cleaning scrapers for each disc.
C.
Where indicated, or in areas of the project where soil conditions are not suitable for satisfactory
crimping, asphalt emulsion shall be applied with the mulching operation. The normal rate of
application shall be 100 gallons per ton of straw; however, this rate may be varied as directed
by the Engineer to suit the particular area or slope conditions.
D.
All mulch shall be distributed evenly over the areas to be mulched within 24 hours after the
seeding operation. Following the mulching operation, suitable precautions shall be taken to
prohibit traffic over mulched areas. Displaced mulch shall be replaced immediately, including
repair of the underlying seed bed, if damaged as well.
3.7
MAINTENANCE
A.
The Contractor shall maintain all seeded areas until the grass is properly established (not less
than 90 days) until satisfactory development. Maintenance shall be continued until final
acceptance of the work.
B.
Maintenance of seeded areas shall include protecting, watering, mowing, fertilizing, and such
other work as may be necessary to establish a permanent lawn. The Contractor shall reseed
those seeded areas in which a satisfactory growth is not obtained, and shall refill any areas
which become eroded prior to final acceptance of the work.
C.
Paved areas shall be kept clean while maintenance operations are in progress.
Section 32 92 19
Seeding, Fertilizing and Mulching
3.8
REPLACEMENT
A.
The Contractor shall replace all trees, shrubs, and flowers damaged by construction activities in
the areas designated on the construction plans. The replacement trees and shrubs shall be
equal in size to the damaged or removed specimen.
END OF SECTION
Section 32 92 19
Seeding, Fertilizing and Mulching
DIVISION 33
UTILITIES
SUMMARY
A.
Section includes: Work, materials, and procedures required to test installed piping other than
gravity sewer piping.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 40 23 39 Process Piping General.
C.
See Section 40 23 39, PROCESS PIPING GENERAL, which contains information and
requirements that apply to the work specified herein and are mandatory for this project.
1.2
SUBMITTALS
A.
PREPARATION
A.
Notify Engineer in writing 5 days in advance of testing. Perform testing in presence of Engineer.
B.
Pressure Piping:
1.
Install temporary thrust blocking or other restraint as necessary to protect adjacent piping
or equipment and make taps in piping prior to testing.
2.
Wait 5 days minimum after concrete thrust blocking is installed to perform pressure tests.
If high-early strength cement is used for thrust blocking, wait may be reduced to 2 days.
3.
Prior to test, remove or suitably isolate appurtenant instruments or devices that could be
damaged by pressure testing.
Section 33 11 11
Piping Leakage Testing
4.
5.
6.
C.
Test section may be filled with water and allowed to stand under low pressure prior to testing.
D.
Gravity Piping:
1.
Perform test as specified hereinafter.
2.
Perform testing after service connections, manholes, and backfilling have been
completed between stations to be tested.
3.
Determine groundwater level at time of testing by exploratory holes or other method
acceptable to Engineer.
3.2
B.
Fluid: Clean water of such quality to prevent corrosion of materials in piping system.
C.
Exposed Piping:
1.
Perform testing on installed piping prior to application of insulation.
2.
Maximum Filling Velocity: 0.25 feet per second, applied over full area of pipe.
3.
Vent piping during filling: Open vents at high points of piping system or loosen flanges,
using at least four bolts, or use equipment vents to purge air pockets.
4.
Maintain hydrostatic test pressure continuously for 60 minutes, minimum, and for such
additional time as necessary to conduct examinations for leakage.
5.
Examine joints and connections for leakage.
6.
Correct visible leakage and retest as specified.
7.
Empty pipe of water prior to final cleaning.
D.
Buried Piping:
1.
Test after backfilling has been completed.
2.
Expel air from piping system during filling.
3.
Apply and maintain specified test pressure with hydraulic force pump. Valve off piping
system when test pressure is reached.
4.
Maintain hydrostatic test pressure continuously for 2 hours minimum, reopening isolation
valve only as necessary to restore test pressure.
5.
Determine actual leakage by measuring quantity of water necessary to maintain specified
test pressure for duration of test.
6.
Maximum Allowable Leakage:
L= SDP
133,200
Where:
L = Allowable leakage, in gallons per hour.
S = Length of pipe tested, in feet.
D = Nominal diameter of pipe, in inches.
P = Test pressure during leakage test, in pounds per square inch.
7.
Correct leakage greater than allowable, and retest as specified.
Section 33 11 11
Piping Leakage Testing
3.3
B.
C.
D.
Procedure:
1.
Apply preliminary pneumatic test pressure of 25 psig maximum to piping system prior to
final leak testing, to locate visible leaks. Apply soap bubble mixture to joints and
connections, examine for leakage.
2.
Correct visible leaks and repeat preliminary test until visible leaks are corrected.
3.
Gradually increase pressure in system to half of specified test pressure. Thereafter
increase pressure in steps of approximately one-tenth of specified test pressure until
required test pressure is reached.
4.
Maintain pneumatic test pressure continuously for minimum of 10 minutes and for such
additional time as necessary to conduct soap bubble examination for leakage.
5.
Correct visible leakage and retest as specified.
E.
Allowable Leakage: Piping system, exclusive of possible localized instances at pump or valve
packing, shall show no visual evidence of leakage.
F.
After testing and final cleaning, purge with nitrogen those lines that will carry flammable gases
to assure no explosive mixtures will be present in system during filling process.
3.4
Testing Equipment Accuracy: Plus or minus 1/2-gallon of water leakage under specified
conditions.
B.
Maximum Allowable Leakage: 0.16 gallons per hour per inch diameter per 100 feet. Include
service connection footage in test section, subjected to minimum head specified.
C.
Exfiltration Test:
1.
Hydrostatic Head:
a.
At least 6 feet above maximum estimated groundwater level in section being
tested.
b.
No less than 6 feet above inside top of highest section of pipe in test section,
including service connections.
2.
Length of Pipe Tested: Limit length such that pressure on invert of lower end of section
does not exceed 30 feet of water column.
D.
Infiltration Test:
1.
Groundwater Level: At least 6 feet above inside top of highest section of pipe in test
section, including service connections.
E.
Piping with groundwater infiltration rate greater than allowable leakage rate for exfiltration will be
considered defective even if pipe previously passed a leakage test.
F.
Defective Piping Sections: Replace or test and seal individual joints, and retest as specified.
Section 33 11 11
Piping Leakage Testing
3.5
Equipment:
1.
Calibrate gauges with standardized test gauge at start of each testing day.
2.
Install gauges, air piping manifolds, and valves at ground surface.
3.
Provide pressure release device, such as rupture disc or pressure relief valve, to relieve
pressure at 6 psi or less.
4.
Restrain plugs used to close sewer lines to prevent blowoff.
B.
Procedure:
1.
Require that no person enter manhole where pipe is under pressure.
2.
Slowly introduce air into pipe section until internal air pressure reached 4 psi greater than
average back pressure of groundwater submerging pipe.
3.
Allow 2 minutes minimum for air temperature to stabilize.
C.
Allowable Leakage: Test section will be considered defective when time required for pressure to
decrease from 3.5 to 2.5 psi greater than average back pressure of groundwater submerging
pipe is less than that computed utilizing values from following table:
TABLE 1*
A
Time per
Foot up to
Length in
Col C (Seconds)
Test Length
(Feet)
Test Time
for any
Length Between Col C
&E
Length at
Which time
in Col F
Applies
(Feet)
Time per
Foot for
Total
Length
(Seconds)
Pipe Diameter
(Inches)
0.18
636
1:54
1.114
0.10
0.40
424
2:50
743
0.23
0.71
318
3:47
557
0.41
10
1.11
255
4:43
446
0.63
12
1.60
212
5:40
371
0.91
15
2.50
170
7:05
297
1.42
18
3.62
141
8:30
248
2.06
21
4.92
121
9:55
212
2.81
24
6.42
106
11:20
187
3.67
Section 33 11 11
Piping Leakage Testing
D.
Piping with groundwater infiltration rate greater than allowable leakage rate for exfiltration will be
considered defective even if pipe previously passed a leakage test.
E.
Defective Piping Sections: Replace or test and seal individual joints, and retest as specified.
3.6
The Contractor shall develop a numbering system for the pipeline joints so that the test logs can
be tied to the tested joint.
B.
The Contractor shall develop a test system that allows the Engineer reasonable access for
witnessing the joint testing. The contractor shall submit his proposed testing plan to the
Engineer for approval prior to the start of testing.
C.
Pressurize the void at the joint with air to 3.5 psi greater than the pressure exerted by
groundwater above the pipe. Allow the air pressure and temperature to stabilize before shutting
off the air supply, and start of test timing. If pressure holds, or drops less than 1 psi in 5
seconds, the joint is acceptable.
D.
If there is any visible leakage within the pipeline after the joint testing, repairs will be required
before the pipeline is accepted.
3.7
END OF SECTION
Section 33 11 11
Piping Leakage Testing
SUMMARY
A.
Section includes: the Work necessary to completely furnish and install Polyethylene
encasement to be used on all underground ductile iron pipe, fittings, valves, and
appurtenances.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 01 60 00 Product Requirements.
c.
Section 31 23 23.13 Fill and Backfill.
d.
Section 31 23 23.16 Trench Backfill.
1.2
GENERAL
A.
1.3
A.
General: Administrative, shop drawings, samples, quality control, and contract closeout
submittals shall conform to the requirements of Section 01 33 00, SUBMITTAL PROCEDURES.
B.
PART 2 - PRODUCTS
2.1
MATERIALS
A.
Polyethylene Encasement
1.
Polyethylene (PE) shall be in conformance to ANSI/AWWA C105/A21.5 (Polyethylene
Encasement for Ductile-Iron Pipe Systems).
2.
The polyethylene encasement shall be black nominal 2% carbon black UV inhibitor and
printed in accordance with AWWA C105.
3.
Polyethylene film used for encasement shall have a minimum nominal thickness of 0.008
inches (8 mils) and shall be provided in either flat tube or sheet form, at the option of the
Contractor.
4.
Polyethylene film used for encasement shall have minimum tensile strength of 3,600 psi.,
a maximum elongation of 800%, and dielectric strength of 800 V/mil.
1
Section 33 31 19
Polyethylene Encasement for Ductile Iron Pipe and Fittings
5.
The minimum tube size for each pipe diameter shall be as listed in Table 1. For pipe
sizes greater than 24 inches, tube size may be determined by multiplying the nominal
pipe diameter by 2.25 to obtain minimum flat tube width.
TABLE 1
NOMINAL PIPE DIAMETER
(INCHES)
4
6
8
10
12
14
16
18
20
24
B.
Tape
1.
Tape used in field application of polyethylene encasement shall be Polyken #900 as
manufactured by Covalence Adhesives, Scotchrap #50 as manufactured by 3M, or
approved equal. Tape shall be at least two (2) inches wide.
PART 3 - EXECUTION
3.1
GENERAL
A.
Polyethylene encasement shall be installed on all ductile iron pipe and fittings. Although not
intended to be a completely air and water-tight enclosure, the polyethylene shall prevent contact
between the pipe and the surrounding soil.
B.
All ductile iron pipe and fittings shall be installed with 2 layers of polyethylene film double
wrapped.
3.2
PIPE
A.
This standard includes two different methods for the installation of polyethylene encasement.
1.
Method A:
a.
Cut polyethylene tube to a length approximately 2 feet longer than the length of the
pipe section. Slip the tube around the pipe, centering it to provide a 1 foot overlap
on each adjacent pipe section, and bunching it accordion-fashion lengthwise until it
clears the pipe ends.
b.
Lower the pipe into the trench and make up the pipe joint with the preceding
section of pipe. A shallow bell hole must be made at joints to facilitate installation
of the polyethylene tube.
c.
After assembling the pipe joint, make the overlap of the polyethylene tube. Pull the
bunched polyethylene from the preceding length of pipe, slip it over the end of the
new length of pipe, and secure in place with one circumferential turn of adhesive
tape plus enough overlap to assure firm adhesion. Then slip the end of the
polyethylene from the new pipe section over the end of the polyethylene from the
new pipe section over the end of the first wrap until it overlaps the joint at the end
of the preceding length of pipe. Tape it in place. Take up the slack width to make
a snug, but not tight, fit along the barrel of the pipe, securing the fold at quarter
points with adhesive tape.
2
Section 33 31 19
Polyethylene Encasement for Ductile Iron Pipe and Fittings
d.
2.
3.3
Repair any rips, punctures, or other damage to the polyethylene with adhesive
tape or with a short length of polyethylene tube cut open, wrapped around the
pipe, and secured with adhesive tape. Proceed with installation of the next section
of pipe in the same manner.
Method B:
a.
Cut polyethylene tube to a length approximately 1 foot shorter than the length of
the pipe section. Slip the tube around the pipe, centering it to provide 6 inches of
bare pipe at each end. Make polyethylene snug, but not tight. Tape down and
secure ends as described above.
b.
Before making up a joint, slip a 3 foot length of polyethylene tube over the end of
the preceding pipe section, bunching it accordion-fashion lengthwise. After
completing the joint, pull the 3 foot length of polyethylene over the joint,
overlapping the polyethylene previously installed on each adjacent section of pipe
by at least 1 foot. Make snug, tape down, and secure each end as described
above.
c.
Repair any rips, punctures, or other damage to the polyethylene as described
above. Proceed with installation of the next section of pipe in the same manner.
PIPE-SHAPED APPURTENANCES
A.
3.4
Bends, reducers, offsets, and other pipe-shaped appurtenances shall be covered with
polyethylene in the same manner as the pipe.
ODD-SHAPED APPURTENANCES:
A.
3.5
Valves, tees, crosses, and other odd-shaped pieces which cannot practically be wrapped in a
tube shall be wrapped with a flat sheet or split length of polyethylene tube. The sheet shall be
passed under the appurtenance and brought up around the body. Seams shall be made by
bringing the edges together, folding over twice, and taping down. Slack width and overlaps at
joints shall be handled as described above. Tape polyethylene securely in place at valve stem
and other penetrations.
OPENINGS IN ENCASEMENT
A.
3.6
Openings for branches, service taps, blow-offs, air valves, and similar appurtenances shall be
made by making an x-shaped cut in the polyethylene and temporarily folding the film back.
After the appurtenance is installed, tape the slack securely to the appurtenance and repair the
cut as well as any other damaged areas in the polyethylene with tape.
JUNCTIONS BETWEEN WRAPPED AND UNWRAPPED PIPE
A.
3.7
Where polyethylene wrapped pipe joins a pipe which is not wrapped, extend the polyethylene
tube to cover the unwrapped pipe a distance of at least 2 feet. Secure the end with
circumferential turns of tape.
PRODUCT DELIVERY, STORAGE, AND HANDLING
A.
B.
C.
Storage: Products shall be carefully stored in a manner that will prevent damage and in an area
that is protected from the elements.
3
Section 33 31 19
Polyethylene Encasement for Ductile Iron Pipe and Fittings
D.
3.8
The encasement shall be protected from prolonged exposure to sunlight to prevent deterioration
of the PE film.
FIELD QUALITY CONTROL
A.
3.9
Contractor shall visually inspect all pipe and fittings upon delivery and set aside and damaged
or flawed materials and shall not install any damaged or flawed material.
INSTALLATION
A.
Pipe bedding and backfill shall be as specified in Section 31 23 23.13 Fill and Backfill, and
Section 31 23 23.16, TRENCH BACKFILL.
END OF SECTION
4
Section 33 31 19
Polyethylene Encasement for Ductile Iron Pipe and Fittings
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 03 11 00: Concrete Formwork
b.
Section 03 20 00: Concrete Reinforcement
c.
Section 03 30 00: Cast In Place Concrete
d.
Section 31 11 00: Site Preparation
e.
Section 31 22 19: Grading
f.
Section 31 23 16: Excavation
g.
Section 31 32 00: Soil Erosion Stabilization
h.
Section 31 50 00: Excavation Support Systems
i.
Section 32 31 13: Chain Link Fence and Gates
1.2
WASTEWATER LAGOONS
A.
Buffer Zone:
1.
No part of the wastewater treatment facility shall be constructed or extended within 100
feet of the plant site property line. Measurement for lagoons shall be from the centerline
of the nearest dike.
2.
The minimum separation distance from any public water supply well is 300 feet.
B.
C.
Section 33 47 23
Industrial Wastewater Lagoons
5.
6.
7.
8.
D.
1.3
Lagoon Bottom
1.
Soil: Soil used in constructing the lagoon bottom and dike cores shall be relatively
incompressible and tight and compacted at or up to 4 percent above the optimum water
content to at least 90% standard proctor density.
2.
Bentonite Seal: Lagoons shall be sealed so that seepage through the seal is as low as
practically possible. A Geotechnical Engineer shall determine the rate of bentonite to be
-7
mixed with the site clay soil to produce the acceptable permeability rate of 1 X 10 cm/s.
a.
The Bentonite application rate shall be at least 125% of the minimum rate that is
determined to be adequate from the Geotechnical Engineer.
b.
The water content of the soil-bentonite mixture shall be up to 4% above the
optimum for maximum compaction. Bentonite shall be applied to soil that is free of
vegetation, trash, roots, frozen soil, snow, ice, stones over 2 inches in diameter or
other objectionable material.
c.
The soil-bentonite material shall be applied in two 3 inch lifts for a finished
compacted blanket thickness of at least 6 inches.
d.
Compact the soil-bentonite mixture at the proper water content to at least 90%
Standard Proctor Density. The Sheepsfoot roller shall not be used.
e.
Cover the completed seal with at least 4 inches of soil in addition to necessary
erosion control.
f.
Hydrate the lagoon seal with fresh water and keep at or above the optimum water
content until the pond is prefilled.
g.
Written certification to the effect that the seal was provided and applied in
accordance with specifications and that the coefficient of permeability is equal to or
-7
less than 1 X 10 cm/s shall be furnished by the contractor.
3.
Prefilling: Prefilling the pond should be done in order to protect the liner, to prevent weed
growth and to maintain moisture content of the seal. The dikes must be completely
prepared before introduction of water. Prefill the lagoon with water to the optimum level or
above before putting it into service. Water for prefilling may be taken from the municipal
water supply system or a nearby pond or stream. The raw sewage influent alone shall not
be used for prefilling purposes. After successfully prefilling the lagoon, and testing is
completed incoming wastewater can be introduced to the lagoon.
SUBMITTALS
A.
1.4
A.
Install erosion and sediment control devices before starting earth disturbance activities and as
drainage facilities get constructed.
B.
Complete Lagoon Excavation: Excavate lagoon and construct lagoon dikes. Mix bentonite with
existing clay soils as indicated in the soil report. Apply bentonite clay mixture to inner lagoon
Section 33 47 23
Industrial Wastewater Lagoons
bottom and dike as shown on plans in lifts no greater than 3 inches. Seed and sod areas as
shown on the plans.
C.
PART 2 - PRODUCTS
2.1
SOD
A.
2.2
Sodding shall consist of furnishing, and placing sod at all locations shown on the plans, where
directed by the Engineer, and in conformity with these Specifications. Sod shall consist of a live,
dense, well rooted growth of permanent grasses, free of weeds and weedy grasses. All sod
shall be cleanly cut in strips having a reasonably uniform thickness of not less than 12 inches.
Sod shall be a low growing grass such as Kentucky 31 Fescue, Bluegrass, Bermuda or an
approved low growing grass approved by the Engineer. It shall be the obligation of the
contractor to secure satisfactory growth of grass before final acceptance of the project.
BENTONITE
A.
Bentonite used to amend the onsite soil shall be sodium bentonite. The Geotechnical Engineer
shall determine the rate of sodium bentonite to be mixed with the site clay soil to produce the
-7
acceptable permeability rate of 1 X 10 cm/s.
PART 3 - EXECUTION
3.1
GENERAL
A.
Erosion control measures as defined in section 31 32 00 are required during all construction
and site disturbance activity and shall remain until permanent site ground covers are in place.
B.
C.
The lagoon subgrade surface should be dragged to remove large rocks and sharp angles. At
least 2 passes with adequate equipment must be made to ensure a smooth subgrade.
D.
The bentonite shall be ground bentonite with bentonite finer than a No. 30 sieve. Bentonite
containing coarser than a No. 30 sieve shall be well graded and bentonite coarser than a No. 30
sieve be discarded.
E.
The bentonite and clay soil mixture shall be applied in 3 inch lifts.
F.
Contractor shall provide written certification that the soil liner meets the Oklahoma Department
of Environmental Quality specifications for a bentonite clay soil lined lagoon. The contractor
shall provide the type and rate of bentonite being applied. Water content and density tests shall
be taken during application of each lift.
G.
H.
Application should be split so that one half is applied in one direction and the other half in a
perpendicular direction.
I.
The bentonite should be mixed into the soil to a uniform depth not to exceed 3 inches.
J.
The liner shall be compacted at the proper water content to at least 90 percent of Standard
Proctor Density (SPECIFICALLY EXCLUDING USE OF A SHEEPSFOOT ROLLER).
Section 33 47 23
Industrial Wastewater Lagoons
K.
The completed seal should be covered with at least 4 inches of soil in addition to necessary
erosion control.
L.
The completed liner shall be hydrated with fresh water prior to introduction of wastewater and
kept at or above the optimum water content until the pond is prefilled.
M.
Testing for the permeability of the lagoon seal shall be done in accordance with ASTM D 5084.
3.2
B.
3.3
DUST CONTROL
A.
Apply appropriate dust control measures on a continuous basis until permanent stabilization
measures are in place.
B.
Apply on construction routes and other disturbed areas subject to surface dust movement and
where off-site damage may occur if dust is not controlled.
C.
3.4
CLEAN-UP
A.
Sediment trapped in erosion control devices shall be regraded into the slopes on the site. Do
not flush sediment-laden water into the drainage system.
B.
After site restoration is complete and when approved by the Engineer, all temporary erosion
control measures shall be completely removed. Immediately shape and permanently stabilize
areas affected by the removal process.
C.
Silt fence, straw bales, reinforced plastic covering, and any other erosion control devices shall
be disposed off site to locations that are approved by federal, state, and local authorities.
END OF SECTION
Section 33 47 23
Industrial Wastewater Lagoons
DIVISION 40
PROCESS INTEGRATION
SUMMARY
A.
This Section specifies piping materials and installation methods common to more than one
section of Division 40 and includes joining materials, piping specialties, and basic piping
installation instructions.
B.
Related Sections:
1.
Piping materials and installation methods peculiar to individual systems are specified
within their respective system specification sections of Division 40.
2.
Valves are specified in a separate section and in individual piping system sections of
Division 40.
3.
Supports and Anchors are specified in a separate section of Division 22.
4.
Mechanical Identification is specified in a separate section of Division 22.
5.
Fire Barrier Penetration Seals are specified in Division 07.
1.2
SUBMITTALS
A.
Refer to Division 01 and Basic Mechanical Requirements for administrative and procedural
requirements for submittals.
B.
C.
1.3
QUALITY ASSURANCE
A.
Welders Qualifications: All welders shall be qualified in accordance with ASME Boiler and
Pressure Vessel Code, Section IX, Welding and Brazing Qualifications.
B.
Welding procedures and testing shall comply with ANSI Standard B31.1.0 - Standard Code for
Pressure Piping, Power Piping, and The American Welding Society, Welding Handbook.
C.
Soldering and Brazing procedures shall conform to ANSI B9.1 Standard Safety Code for
Mechanical Refrigeration.
1.4
Provide factory-applied plastic end-caps on each length of pipe and tube, except for concrete,
corrugated metal, hub-and-spigot, clay pipe. Maintain end-caps through shipping, storage and
handling to prevent pipe-end damage and prevent entrance of dirt, debris, and moisture.
B.
Protect stored pipes and tubes. Elevate above grade and enclose with durable, waterproof
wrapping. When stored inside, do not exceed structural capacity of the floor.
C.
Protect flanges, fittings, and specialties from moisture and dirt by inside storage and enclosure,
or by packaging with durable, waterproof wrapping.
Section 40 05 13
Common Work Results for Process Piping
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
B.
Pipe Escutcheons:
1.
Chicago Specialty Mfg. Co.
2.
Sanitary-Dash Mfg. Co.
3.
Grinnell
C.
D.
Dielectric Unions:
1.
Eclipse, Inc.
2.
Perfection Corp.
3.
Watts Regulator Co.
E.
2.2
2.3
Refer to the individual piping system specification sections in Division 15 for specifications on
piping and fittings relative to that particular system.
JOINING MATERIALS
A.
Welding Materials: Comply with Section II, Part C, ASME Boiler and Pressure Vessel Code for
welding materials appropriate for the wall thickness and chemical analysis of the pipe being
welded.
B.
Brazing Materials: Comply with SFA-5.8, Section II, ASME Boiler and Pressure Vessel Code
for brazing filler metal materials appropriate for the materials being joined.
C.
Soldering Materials: Refer to individual piping system specifications for solder appropriate for
each respective system.
D.
Gaskets for Flanged Joints: Gasket material shall be full-faced for cast-iron flanges and raisedface for steel flanges. Select materials to suit the service of the piping system in which installed
and which conform to their respective ANSI Standard (A21.11, B16.20, or B16.21). Provide
materials that will not be detrimentally affected by the chemical and thermal conditions of the
fluid being carried.
2.4
PIPING SPECIALTIES
A.
Escutcheons: Chrome-plated, stamped steel, hinged, split-ring escutcheon, with set screw.
Inside diameter shall closely fit pipe outside diameter or outside of pipe insulation where pipe is
insulated. Outside diameter shall completely cover the opening in floors, walls, or ceilings.
Section 40 05 13
Common Work Results for Process Piping
B.
Unions: Malleable-iron, Class 150 for low pressure service and class 250 for high pressure
service; hexagonal stock, with ball-and-socket joints, metal-to-metal bronze seating surfaces;
female threaded ends.
C.
Dielectric Unions: Provide dielectric unions with appropriate end connections for the pipe
materials in which installed (screwed, soldered, or flanged), which effectively isolate dissimilar
metals, prevent galvanic action, and stop corrosion.
D.
E.
Sleeves:
1.
Sheet-Metal Sleeves: 10 gauge, galvanized sheet metal, round tube closed with welded
longitudinal joint.
2.
Steel Sleeves: Schedule 40 galvanized, welded steel pipe, ASTM A53, Grade A.
3.
Mechanical Sleeve Seals: Modular mechanical type, consisting of interlocking synthetic
rubber links shaped to continuously fill annular space between pipe and sleeve,
connected with bolts and pressure plates which cause rubber sealing elements to expand
when tightened, providing watertight seal and electrical insulation.
PART 3 - EXECUTION
3.1
PREPARATION
A.
Ream ends of pipes and tubes, and remove burrs. Bevel plain ends of steel pipe.
B.
Remove scale, slag, dirt, and debris for both inside and outside of piping and fittings before
assembly.
3.2
INSTALLATIONS
A.
General Locations and Arrangements: Drawings (plans, schematics, and diagrams) indicate the
general location and arrangement of the piping systems. Location and arrangement of piping
layout take into consideration pipe sizing and friction loss, expansion, pump sizing, and other
design considerations. So far as practical, install piping as indicated. Refer to individual system
specifications for requirements for coordination drawing submittals.
1.
Conceal all pipe installations in walls, pipe chases, utility spaces, above ceilings, below
grade or floors, unless indicated otherwise.
2.
Install piping free of sags or bends and with ample space between piping to permit proper
insulation applications.
3.
Install exposed piping at right angles or parallel to building walls. Diagonal runs are not
permitted, unless expressly indicated on the Drawings.
4.
Install piping tight to slabs, beams, joists, columns, walls, and other permanent elements
of the building. Provide space to permit insulation applications, with 1" clearance outside
the insulation. Allow sufficient space above removable ceiling panels to allow for panel
removal.
5.
Locate groups of pipes parallel to each other, spaced to permit applying full insulation
and servicing of valves.
6.
Install drains at low points in mains, risers, and branch lines consisting of a tee fitting,
3/4" ball valve, and short 3/4" threaded nipple and cap.
B.
Exterior Wall Penetrations: Seal pipe penetrations through exterior walls using sleeves and
mechanical sleeve seals. Pipe sleeves smaller than 6" shall be steel; pipe sleeves 6" and larger
shall be sheet metal.
Section 40 05 13
Common Work Results for Process Piping
C.
3.3
Fire Barrier Penetrations: Where pipes pass through fire rated walls, partitions, ceilings, or
floors, the fire rated integrity shall be maintained. Refer to Division 07 for special sealers and
materials.
FITTINGS AND SPECIALTIES
A.
Use fittings for all changes in direction and all branch connections.
B.
C.
Install strainers on the supply side of each control valve, pressure reducing or regulating valve,
solenoid valve, and elsewhere as indicated.
D.
Install unions adjacent to each valve and at the final connection to each piece of equipment and
plumbing fixture having 2" and smaller connections, and elsewhere as indicated.
E.
Install Flanges in piping 2-1/2" and larger, where indicated, adjacent to each
the final connection to each piece of equipment.
F.
Install dielectric unions to connect piping materials of dissimilar metals in dry piping systems
(gas, compressed air, vacuum).
G.
Install dielectric fittings to connect piping materials of dissimilar metals in wet piping systems
(water, steam).
3.4
valve,
and
at
JOINTS
A.
B.
C.
Mechanical Joints:
smaller.
D.
Joints for other piping materials are specified within the respective piping system sections.
Flared compression fittings may be used for refrigerant lines 3/4" and
Section 40 05 13
Common Work Results for Process Piping
3.5
END OF SECTION
Section 40 05 13
Common Work Results for Process Piping
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 60 00 Product Requirements.
b.
Section 03 30 00 Cast-In-Place Concrete.
c.
Section 09 90 00 Painting and Protective Coatings.
d.
Section 23 05 29 Hangers and Supports for Mechanical Piping and Equipment.
e.
Section 23 05 53 Identification for HVAC Piping and Equipment.
f.
Section 23 07 13 Mechanical Insulation.
g.
Section 31 23 23.16 Trench Backfill.
h.
Section 33 11 11 Piping Leakage Testing.
i.
Section 33 13 00 Disinfection of Water Systems.
j.
Section 40 41 13 Heat Tracing.
k.
Section 40 24 00 Process Piping Specialties.
1.2
REFERENCES
A.
The following is a list of standards which may be referenced in this Section and any
supplemental Data Sheets:
1.
American Association of State Highway and Transportation Officials (AASHTO):
Standard Specifications for Highway Bridges.
2.
American National Standards Institute (ANSI):
a.
A21.52, Ductile Iron Pipe, Centrifugally Cast, for Gas.
b.
B1.20.1, Pipe Threads, General Purpose (Inch).
c.
B16.1, Cast Iron Pipe Flanges and Flanged Fittings.
d.
B16.3, Malleable Iron Threaded Fittings.
e.
B16.5, Pipe Flanges and Flanged Fittings.
f.
B16.9, Factory-Made Wrought Steel Butt welding Fittings.
g.
B16.11, Forged Fittings, Socket-Welding and Threaded.
h.
B16.15, Cast Bronze Threaded Fittings, Classes 125 and 250.
i.
B16.21, Nonmetallic Flat Gaskets for Pipe Flanges.
j.
B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings.
k.
B16.24, Cast Copper Alloy Pipe Flanges and Flanged Fittings Class
150,300,400,600,900, 1500 and 2500.
l.
B16.25, Butt Welding Ends.
m.
B16.42, Ductile Iron Pipe Flanges and Flanged Fittings, Classes 150 and 300.
3.
American Petroleum Institute (API): 5L, Specification for Line Pipe.
4.
American Society of Mechanical Engineers (ASME):
a.
Boiler and Pressure Vessel Code, Section VITI, Division 1, Pressure Vessels.
b.
Boiler and Pressure Vessel Code, Section IX, Welding and Brazing Qualifications.
c.
B31.1, Power Piping.
Section 40 23 39
Process Piping - General
5.
6.
d.
B31.3, Chemical Plant and Petroleum Refinery Piping.
e.
B31.9, Building Services Piping.
f.
B36.10M, Welded and Seamless Wrought Steel Pipe.
American Society for Nondestructive Testing (ASNT): SNT-TC-1A, Recommended
Practice for Nondestructive Testing Personnel Qualifications.
American Society for Testing and Materials (ASTM):
a.
A47, Standard Specification for Ferritic Malleable Iron Castings.
b.
A53 Rev A, Standard Specification for Pipe, Steel, Black and Hot-Dipped, ZincCoated, Welded and Seamless.
c.
A105/ A105M, Standard Specification for Forgings, Carbon Steel, for Piping
Components.
d.
A106, Standard Specification for Seamless Carbon Steel Pipe for High
Temperature Service.
e.
A126, Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe
Fittings.
f.
A135, Standard Specification for Electric-Resistance-Welded Steel Pipe.
g.
A139 Rev A, Standard Specification for Electric-Fusion (Arc) -Welded Steel Pipe
(NPS 4 and Over).
h.
A153, Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware.
i.
A181/A181M Rev A, Standard Specification for Forgings, Carbon Steel, for
General-Purpose Piping.
j.
A182/A182M Rev C, Standard Specification for Forged or Rolled Alloy-Steel Pipe
Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service.
k.
A183, Standard Specification for Carbon Steel Track Bolts and Nuts.
l.
A193/A193M Rev A, Standard Specification for Alloy-Steel and Stainless Steel
Bolting Materials for High-Temperature Service.
m.
A194/A194M, Standard Specification for Carbon and Alloy Steel Nuts for Bolts for
High-Pressure and High-Temperature Service.
n.
A197, Standard Specification for Cupola Malleable Iron.
o.
A216/A216M, Standard Specification for Steel Castings, Carbon, Suitable for
Fusion Welding, for High Temperature Service.
p.
A234/A234M, Standard Specification for Piping Fittings of Wrought Carbon Steel
and Alloy Steel for Moderate and Elevated Temperatures.
q.
A240, Standard Specification for Heat-Resisting Chromium and Chromium-Nickel
Stainless Steel Plate, Sheet and Strip for Pressure Vessels.
r.
A276, Standard Specification for Stainless and Heat-Resisting Steel Bars and
Shapes.
s.
A283/A283M Rev A, Standard Specification for Low and Intermediate Tensile
Strength Carbon Steel Plates.
t.
A285/ A285M, Standard Specification for Pressure Vessel Plates, Carbon Steel,
Low and Intermediate Tensile Strength.
u.
A307, Standard Specification for Carbon Steel Bolts and Studs, 60,000 psi Tensile
Strength.
v.
A312/A312M, Standard Specification for Seamless and Welded Austenitic
Stainless Steel Pipes.
w.
A320/A320M, Standard Specification for Alloy Steel Bolting Materials for LowTemperature Service.
x.
A395, Standard Specification for Ferritic Ductile Iron Pressure-Retaining Castings
for Use at Elevated Temperatures.
y.
A403/ A403M Rev A, Standard Specification for Wrought Austenitic Stainless Steel
Piping Fittings.
z.
A409/ A409M, Standard Specification for Welded Large Diameter Austenitic Steel
Pipe for Corrosive or High-Temperature Service.
aa.
A536, Standard Specification for Ductile Iron Castings.
bb.
A563, Standard Specification for Carbon and Alloy Steel Nuts.
Section 40 23 39
Process Piping - General
cc.
dd.
ee.
ff.
gg.
hh.
ii.
jj.
kk.
ll.
mm.
nn.
oo.
pp.
qq.
rr.
ss.
tt.
uu.
vv.
ww.
xx.
yy.
zz.
aaa.
bbb.
ccc.
ddd.
eee.
fff.
ggg.
Section 40 23 39
Process Piping - General
7.
8.
9.
10.
1.3
hhh. F493 Rev A, Standard Specification for Solvent Cements for Chlorinated Poly Vinyl
Chloride) (CPVC) Plastic Pipe and Fittings.
iii.
F714, Standard Specification for Polyethylene (PE) Plastic Pipe
(SDR-PR) based on outside diameter.
American Welding Society (AWS):
a.
A5.8, Specification for Filler Metals for Brazing and Braze Welding.
b.
QC 1, Standard for AWS Certification of Welding Inspectors.
American Water Works Association (AWWA):
a.
C104/A21.4, Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water.
b.
C110/A21.10, Ductile-Iron and Gray-Iron Fittings, 3 through 48for Water and
Other Liquids.
c.
C111/A21.11, Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings.
d.
C115/A21.15, Flanged Ductile-Iron Pipe with Threaded Flanges.
e.
C151/A21.51, Ductile-Iron Pipe, Centrifugally Cast, for Water or Other Liquids.
f.
C153/A21.53, Ductile-Iron Compact Fittings 3 through 16, for Water and Other
Liquids.
g.
C200, Steel Water Pipe 6 and Larger.
h.
C205, Cement-Mortar Protective Lining and Coating for Steel Water Pipe-4 and
Larger-Shop Applied.
i.
C207, Steel Pipe Flanges for Water Works Service, Sizes 4 through 144.
j.
C208, Dimensions for Fabricated Steel Water Pipe Fittings.
k.
C214, Fusion Bonded Epoxy Coating for the Interior and Exterior of Steel Water
Pipelines.
l.
C606, Grooved and Shouldered Type Joints.
m.
M11, Steel Pipe - A Guide for Design and Installation.
Manufacturers Standardization Society of the Valve and Fittings Industry, Inc. (MSS): SP
43, Wrought Stainless Steel Butt-Welding Fittings Including Reference to Other Corrosion
Resistant Materials.
National Fire Protection Association (NFPA): 24, Standard for the Installation of Private
Fire Service Mains and Their Appurtenances.
DEFINITIONS
A.
1.4
Submerged or Wetted:
1.
Zone below elevation of:
a.
Top face of channel walls and cover slabs.
b.
Top face of basin walkways.
c.
Top face of clarifier walkways.
d.
Top face of digester walls, including structure piping penetrations.
e.
Liquid surface or within 2 feet above top of liquid surface.
f.
Top of tank wall or under tank cover.
SUBMITTALS
A.
Shop Drawings:
1.
Shop Fabricated Piping:
a.
Detailed pipe fabrication or spool drawings showing special fittings and bends,
dimensions, coatings, and other pertinent information.
b.
Layout drawing showing location of each pipe section and each special length;
number or otherwise designate laying sequence on each piece.
2.
Pipe Wall Thickness: Identify wall thickness and rational method or standard applied to
determine wall thickness for each size of each different service including exposed,
submerged, buried, and concrete-encased installations for Contractor-designed piping.
3.
Hydraulic Thrust Restraint for Restrained Joints: Details including materials, sizes,
assembly ratings, and pipe attachment methods.
4.
Thrust Blocks: Concrete quantity, bearing area on pipe, and fitting joint locations.
Section 40 23 39
Process Piping - General
5.
6.
B.
1.5
A.
B.
Section 40 23 39
Process Piping - General
C.
Certifications:
1.
Coal-Tar Epoxy Applicator: Certified by Piping Manufacturer to be qualified to apply coaltar epoxy coating to submerged or embedded ductile iron or cast iron soil piping.
2.
Weld Testing Agency: Certified in accordance with current American Society for
Nondestructive Testing (4153 Arlingate Plaza, Columbus, OH 43228) recommended
practice SNT-TC-1A, NDT Level II.
D.
1.6
PART 2 - PRODUCTS
2.1
PIPING
A.
As specified on Piping Data Sheet(s) and Piping Schedule located at the end of this section as
Supplement.
B.
Diameters Shown:
1.
Standardized Products: Nominal size.
2.
Fabricated Steel Piping (Except Cement-Lined): Outside diameter, ASME 836.l0M.
3.
Cement-Lined Steel Pipe: Lining inside diameter.
2.2
JOINTS
A.
Section 40 23 39
Process Piping - General
1.
2.
Rigid, except where joints are used to correct misalignment, to provide flexibility, or
where shown, furnish flexible type.
Flanges:
When required, furnish with grooved type flange adapters of same
manufacturer as grooved end couplings.
B.
Flanged Joints:
1.
Flat-faced carbon steel or alloy flanges when mating with flat-faced cast or ductile iron
flanges.
2.
Higher pressure rated flanges as required, to mate with equipment when equipment
flange is of higher pressure rating than required for piping.
C.
Threaded Joints: NPT taper pipe threads in accordance with ANSI B 1.20. 1.
D.
Thrust Tie-Rod Assemblies: NFPA 24; tie-rod attachments relying on clamp friction with pipe
barrel to restrain thrust are unacceptable.
E.
F.
G.
Mechanical connections of the high density polyethylene pipe to auxiliary equipment such as
valves, pumps, tanks, and other piping systems shall be through flanged connections consisting
of the following:
1.
A polyethylene stub end thermally butt-fused to the end of the pipe.
2.
ASTM A240, Type 304 stainless steel backing flange, 125-pound, ANSI B16.1 Standard.
Insulating flanges shall be used where shown.
3.
Bolts and nuts of sufficient length to show a minimum of three complete threads when the
joint is made and tightened to the Manufacturers standard. Re-torque the nuts after 4
hours.
4.
Gaskets as specified on Data Sheet.
2.3
COUPLINGS
A.
B.
Flexible Couplings:
1.
Manufacturers and Products:
a.
Steel Pipe:
1). Dresser; Style 38.
2). Smith-Blair; Style 411.
b.
Ductile Iron Pipe:
1). Dresser; Style 153.
2). Smith-Blair; Style 411.
C.
Transition Couplings:
1.
Manufacturers and Products:
a.
Dresser; Style 162.
Section 40 23 39
Process Piping - General
b.
D.
2.4
A.
2.5
Lubricant shall be supplied by pipe Manufacturer and no substitute or or-equal will be allowed.
DOUBLE WALL CONTAINMENT PIPING SYSTEM
A.
2.6
All system components shall be pre-engineered, factory fabricated, tested, and assembled such
that field assembly is minimized to primarily that of straight joints.
THRUST BLOCKS
A.
2.7
A.
Pipeline 2-1/2 Diameter and Larger: Vent connections shall be 3/4-inch with V300 ball valve.
Drain connection shall be 1-inch with V300 ball valve, unless shown otherwise.
B.
Pipeline 2 Diameter and Smaller: Vent connections shall be 1/2-inch with V300 ball valve.
Drain connection shall be 1-inch with V300 ball valve, unless shown otherwise.
C.
2.8
FABRICATION
A.
B.
C.
Flanged pipe shall be fabricated in the shop, not in the field, and delivered to the site with
flanges in place and properly faced. Threaded flanges shall be individually fitted and machine
tightened on matching threaded pipe by the Manufacturer.
2.9
FINISHES
A.
Factory prepare, prime, and finish coat in accordance with Pipe Data Sheet(s), Piping Schedule,
and Section 09 90 00, PAINTING AND PROTECTIVE COATINGS.
B.
Galvanizing:
1.
Hot-dip applied, meeting requirements of ASTM A153.
2.
Electroplated zinc or cadmium plating is unacceptable.
3.
Stainless steel components may be substituted where galvanizing is specified.
Section 40 23 39
Process Piping - General
PART 3 - EXECUTION
3.1
EXAMINATION
A.
Verify size, material, joint types, elevation, horizontal location, and pipe service of existing
pipelines to be connected to new pipelines or new equipment.
B.
Inspect size and location of structure penetrations to verify adequacy of wall pipes, sleeves, and
other openings.
C.
Welding Electrodes: Verify proper grade and type, free of moisture and dampness, and coating
is undamaged.
3.2
PREPARATION
A.
B.
Inspect pipe and fittings before installation, clean ends thoroughly, and remove foreign matter
and dirt from inside.
C.
Damaged Coatings and Linings: Repair using original coating and lining materials in
accordance with Manufacturers instructions, except for damaged glass-lined pipe or PVDFlined pipe that is to be promptly removed from the site.
3.3
WELDING
A.
Perform in accordance with Section IX, ASME Boiler and Pressure Vessel Code and ASME
B31.1 for Pressure Piping, as may be specified on Piping Data Sheets, and if recommended by
piping or fitting Manufacturer.
B.
C.
D.
Surfaces:
1.
Clean and free of paint, oil, rust, scale, slag, or other material detrimental to welding.
2.
Clean stainless steel joints with stainless steel wire brushes or stainless steel wool prior
to welding.
3.
Thoroughly clean each layer of deposited weld metal, including final pass, prior to
deposition of each additional layer of weld metal with a power-driven wire brush.
E.
F.
Climatic Conditions:
1.
Do not perform welding if there is impingement of any rain, snow, sleet or high wind on
the weld area, or if the ambient temperature is below 32 F.
Section 40 23 39
Process Piping - General
2.
Stainless Steel and Alloy Piping: f the ambient is less than 32 F, local preheating to a
temperature warm to the hand is required.
G.
Tack Welds: Performed by qualified welder using same procedure as for completed weld,
made with electrode similar or equivalent to electrode to be used for first weld pass, and not
defective. Remove those not meeting requirements prior to commencing welding procedures.
H.
I.
J.
Weld Quality: Free of cracks, incomplete penetration, weld undercutting, excessive weld
reinforcement, porosity slag inclusions, and other defects in
excess of limits shown in
applicable piping code.
3.4
INSTALLATION - GENERAL
A.
Join pipe and fittings in accordance with Manufacturers instructions, unless otherwise shown or
specified.
B.
C.
Flanged Joints:
1.
Install perpendicular to pipe centerline.
2.
Bolt Holes: Straddle vertical centerlines, aligned with connecting equipment flanges or as
shown.
3.
Use torque-limiting wrenches to ensure uniform bearing and proper bolt tightness.
4.
Plastic Flanges: Install annular ring filler gasket at joints of raised-face flange.
5.
Raised-Face Flanges: Use flat-face flange when joining with flat-faced ductile or cast
iron flange.
D.
E.
Soldered Joints:
1.
Use only solder specified for particular service.
2.
Cut pipe ends square and remove fins and burrs.
3.
After thoroughly cleaning pipe and fitting of oil and grease using solvent and emery cloth,
apply non-corrosive flux to the male end only.
4.
Wipe excess solder from exterior of joint before hardened.
5.
Before soldering, remove stems and washers from solder joint valves.
F.
Couplings:
1.
General:
a.
Install in accordance with Manufacturers written instructions.
b.
Before coupling, clean pipe holdback area of oil, scale, rust, and dirt.
c.
Remove pipe coating if necessary to present smooth surface.
2.
Application:
10
Section 40 23 39
Process Piping - General
a.
b.
c.
d.
e.
G.
H.
I.
Penetrations:
1.
Watertight Penetrations:
a.
Provide wall pipes with thrust collars, as specified in Section 40 24 00, PROCESS
PIPING SPECIALTIES.
b.
Provide taps for stud bolts in flanges to be set flush with wall face.
2.
Non-watertight Penetrations:
a.
Pipe sleeves with seep ring as specified in Section 40 24 00, PROCESS PIPING
SPECIALTIES.
b.
Pipe sleeves with modular mechanical seal may be provided where fabrication of
seep ring on pipe sleeve is impractical.
3.
Existing Walls:
a.
Pipe sleeve with modular mechanical seal as specified in Section 40 24 00,
PROCESS PIPING SPECIALTIES.
b.
Rotary drilled holes may be provided in lieu of sleeves in concrete walls.
4.
Fire-Rated or Smoke-Rated Walls, Floor, or Ceilings: Insulated and encased pipe sleeves
as specified in Section 40 24 00, PROCESS PIPING SPECIALTIES.
J.
K.
Ductile Iron, Cement-Lined Ductile Iron, and Glass-Lined Ductile Iron Piping:
1.
Cutting Pipe: Cut pipe with milling type cutter, rolling pipe cutter, or abrasive saw cutter.
Do not flame cut.
2.
Dressing Cut Ends:
a.
General: As required for the type of joint to be made.
b.
Rubber Gasketed Joints: Remove sharp edges or projections.
c.
Push-On Joints: Bevel, as recommended by pipe Manufacturer.
d.
Flexible Couplings, Flanged Coupling Adapters, and Grooved End
Pipe Couplings: As recommended by the coupling or adapter Manufacturer.
3.5
INSTALLATION-EXPOSED PIPING
A.
Piping Runs:
1.
Parallel to building or column lines and perpendicular to floor, unless shown otherwise.
2.
Piping upstream and downstream of flow measuring devices shall provide straight
lengths as required for accurate flow measurement.
11
Section 40 23 39
Process Piping - General
B.
C.
Group piping wherever practical at common elevations; installing to conserve building space
and not interfere with use of space and other work.
D.
E.
F.
3.6
INSTALLATION-BURIED PIPE
A.
Joints:
1.
Dissimilar Buried Pipes:
a.
Provide flexible mechanical compression joints for pressure pipe.
b.
Provide concrete closure collar for gravity and low pressure (maximum 10 psi)
piping or as shown.
2.
Concrete Encased or Embedded Pipe: Do not encase joints in concrete unless
specifically shown.
B.
Placement:
1.
Keep trench dry until pipe laying and joining are completed.
2.
Pipe Base and Pipe Zone: As specified in Section 31 23 23.16, TRENCH BACKFILL.
3.
Exercise care when lowering pipe into trench to prevent twisting or damage to pipe.
4.
Measure for grade at pipe invert, not at top of pipe.
5.
Excavate trench bottom and sides of ample dimensions to permit visual inspection and
testing of entire flange, valve, or connection.
6.
Prevent foreign material from entering pipe during placement.
7.
Close and block open end of last pipe section laid when placement operations are not in
progress and at close of days work.
8.
Lay pipe upgrade with bell ends pointing in the direction the pipe is laying.
9.
Install closure sections and adapters for gravity piping at locations where pipe laying
changes direction.
12
Section 40 23 39
Process Piping - General
10.
11.
12.
13.
Deflect pipe at joints for pipelines laid on a curve using unsymmetrical closure of spigot
into bell. If joint deflection of standard pipe lengths will not accommodate horizontal or
vertical curves in alignment, provide:
a.
Shorter pipe lengths.
b.
Special mitered joints.
c.
Standard or special fabricated bends.
After joint has been made, check pipe alignment and grade.
Place sufficient pipe zone material to secure pipe from movement before next joint is
installed.
Prevent uplift and floating of pipe prior to backfilling.
C.
D.
Tolerances:
1.
Deflection from Horizontal Line, Except PVC, CPVC, or HDPE: Maximum 2.
2.
Deflection from Vertical Grade: Maximum 1/4.
3.
Joint Deflection: Maximum of 75% of Manufacturers recommendation.
4.
Horizontal position of pipe centerline on alignment around curves maximum variation of
1.75 from position shown.
5.
Pipe Cover: Minimum 5, unless otherwise shown.
3.7
THRUST RESTRAINT
A.
Location:
1.
Buried Piping: At pipeline tees, plugs, caps, bends, and other locations where
unbalanced forces exist.
2.
Exposed Piping: At all joints in pressure piping.
B.
Thrust Ties:
1.
Install as detailed.
2.
Anchoring retainer glands or thrust ties with setscrews is unacceptable.
C.
Mechanical Joint Valve Restraint in Proprietary Restrained Joint Piping: Install pipe joint
Manufacturers adapter gland follower and pipe end retainer, or thrust tie-rods and socket
clamps.
D.
Thrust Blocking:
1.
Place between undisturbed ground and fitting to be anchored.
2.
Quantity of Concrete: Sufficient to cover bearing area on pipe and provide required soil
bearing area as shown.
3.
Place blocking so that pipe and fitting joints will be accessible for repairs.
4.
Place concrete in accordance with Section 03 30 00, CAST-IN-PLACE CONCRETE.
3.8
WALL PIPES
A.
B.
13
Section 40 23 39
Process Piping - General
1.
2.
3.9
Isolate embedded metallic piping from concrete reinforcement using coated pipe
penetrations as specified in Section 09 90 00, PAINTING AND PROTECTIVE
COATINGS.
Support wall pipes securely by formwork to prevent contact with reinforcing steel and tie
wires.
BRANCH CONNECTIONS
A.
Do not install branch connections smaller than 1/2-inch nominal pipe size, including instrument
connections, unless shown otherwise.
B.
When line of lower pressure connects to a line of higher pressure, requirements of Piping Data
Sheet for higher pressure rating prevails up to and including the first block valve in the line
carrying the lower pressure, unless otherwise shown.
C.
3.10
A.
3.11
A.
Following assembly and testing, and prior to disinfection and final acceptance, flush pipelines
(except as stated below) with water at 2.5 fps minimum flushing velocity until foreign matter is
removed.
B.
Blow clean of loose debris plant process air, natural gas, and instrument air-lines with
compressed air at 4,000 fpm; do not flush with water.
C.
If impractical to flush large diameter pipe at 2.5 fps or blow at 4,000 fpm velocity, clean in-place
from inside by brushing and sweeping, then flush or blow line at lower velocity.
D.
Insert cone strainers in flushing connections to attached equipment and leave in-place until
cleaning is complete.
E.
Remove accumulated debris through drains 2 and larger or by removing spools and valves
from piping.
3.12
FIELD FINISHING
A.
Notify Engineer at least 3 days prior to start of any surface preparation or coating application
work.
B.
14
Section 40 23 39
Process Piping - General
3.13
A.
3.14
A.
3.15
A.
3.16
PIPE IDENTIFICATION
See Section 23 05 53, IDENTIFICATION FOR HVAC PIPING AND EUQIPMENT and 09 90 00
PAINTING AND PROTECTIVE COATINGS.
INSULATION
See Section 23 07 13, MECHANICAL INSULATION.
HEAT TRACING
See Section 40 41 13, HEAT TRACING.
FIELD QUALITY CONTROL
A.
Pressure Leakage Testing: As specified. See Section 33 11 11, PIPING LEAKAGE TESTING.
B.
C.
3.17
A.
SUPPLEMENTS
The supplements listed below, following END OF SECTION, are a part of this Specification.
1.
Piping Schedule.
2.
Data Sheets.
Number
40 23 39.13
40 23 39.36
40 23 39.40
40 23 39.43
40 23 39.56
40 23 39.62
Title
Cement Mortar Lined Ductile Iron Pipe and Fittings
Stainless Steel Pipe and Fittings
C900 & C905 PVC Pipe and Fittings
Polyvinyl Chloride (PVC) Pipe and Fittings
High Density Polyethylene (HDPE) Pipe and Fittings
Medium Density Polyethylene (MDPE) Pipe and Fittings
END OF SECTION
15
Section 40 23 39
Process Piping - General
IW
Industrial Waste
1
2
3
4
5
Remarks:
Notes:
Water, Potable
Water, Potable
Buried
Buried
Exposed-Inside
Buried
Exposed
All
Installation
(Note 1)
ALL
4
>4
ALL
ALL
All
Nominal
Diameter
(Note 2)
NONE
NONE
CTP
EPP
NONE
Coating
(Note 8)
40 23 39.13
40 23 39.40
40 23 39.56
40 23 39.43
40 23 39.56
40 23 39.40
40 23 39.36
40 23 39.13
125
125
Ambient
50
150
Max
Operating
Pressure
(psig)
Ambient
Ambient
300
Max
Operating
Temp (F)
200,H
200,H
150,H
250,P
Test Pressure
(psig) &
Method
(Note 4)
PVC
NONE
40 23 39.43
Ambient
Gravity
4,G
NONE
MDPE
NONE
40 23 39.62
Ambient
80
100,P
Steel
NONE
H - Hydrostatic Test
P - Pneumatic Test
G - Gravity Piping
See Section 33 11 11 for Piping Leakage Testing requirements.
Pipe testing required as specified above.
See Section 09 99 00 for required painting.
For buried piping, no color shall be required; coordinate for proper coatings, as necessary.
Where no color is indicated, color to be selected by Owner.
For exposed piping not coated, provide colored banding and identification.
General - Deviations from this schedule are indicated directly by note on Drawings where
deviation is required.
General - The piping material shall conform to the requirements for the service listed being
drained or vented.
EPP Epoxy and Polyurethane Coating System
HSE High Solids Epoxy
CTP Coal Tar Pitch
HT High Temperature
CLDI,
C900/905 PVC,
or HDPE
PVC
HDPE
C900/905 PVC
SST
CLDI
Material
(Note 3)
Spec /
Data
Sheet No.
Pipe
Color
(Note 5)
Remark
s
1 of 1
40 23 39 Supplement
Process Piping Schedule
Buried
4
Exposed
Encased All buried piping under concrete slabs
4
and/or structures shall be concrete encased per
standard detail D40/2400-009 unless indicated
otherwise on the Drawings.
> Greater Than
< Less Than
5
<= Less Than or Equal To
>= Greater Than or Equal To
CLDI - Cement Lined Ductile Iron
CELDI Ceramic Epoxy Lined Ductile Iron
6
CPVC - Chlorinated Polyvinyl Chloride
CU Copper
7
GALV - Galvanized Pipe
HDPE High Density Polyethylene
8
SST - Stainless Steel
FS Flanged Steel
WS Welded Steel
FL PVC Flanged Polyvinyl Chloride Pipe
PO PVC Push on Joint Polyvinyl Chloride Pipe
SW PVC Solvent Weld Polyvinyl Chloride Pipe
Welded or flanged, flanged where shown.
Buried raw water piping between and pump station and intake shall be CLDI. Drop leg from pump header to buried force main shall be CLDI.
Where buried piping transitions to exposed PVC piping, the buried piping shall be extended at least six (6) inches above the finished floor before transitioning to exposed PVC piping.
Heat trace and insulate all outside exposed piping.
SW PVC or FL PVC, FL PVC where shown
RW
Raw Water
Liquid Propane
ABW
Air, Backwash
Service
Flow
Stream
Identifier
Item
Pipe
Lining
Fittings
SECTION 40 23 39.13
DUCTILE IRON PIPE AND FITTINGS
Description
Buried Liquid Service: Push-On, Mechanical, or Proprietary
Restrained Joints: AWWA C110/A21.10-93, AWWA
C115/A21.15-88, and AWWA C151/A21.51-91, pressure class
conforming to Tables 51.1 and 51.3 for Type 4 trench, 250 psi
minimum working pressure.
Exposed Pipe: Grooved End or Flange Joints:
AWWA C115/A21.15-88, and AWWA C151/A21.51-91, thickness
Class 53 minimum conforming to Table 51.7, 250 psi minimum
working pressure.
Cement-Mortar: AWWA C104/A21.4-90.
Ceramic Epoxy: Protecto 401 or equal.
Joints, Lining and coating same as pipe.
Push-On: AWWA C110/A21.10-93 and C111/A21.11-90, gray or
ductile iron, 250 psi minimum working pressure. American Cast
Iron Pipe Co., Fastite Joints; U.S. Pipe and Foundry, Tyton Joint.
Mechanical: For Buried Service. AWWA C110/A21.10-93,
C111/A21.11-90, and C153/A21.53-88 gray or ductile iron, 250 psi
minimum working pressure. Coating shall Fusion-Bonded Epoxy
meeting AWWA C116. American Cast Iron Pipe Co., Mechanical
Joint; U.S. Pipe and Foundry, Mechanical Joint.
Proprietary Restrained: AWWA C111/A21.11-90 and
C153/A21.53-88, ductile iron, 250 psi minimum working pressure.
Clow Corp., Super-Lock Joint; American Cast Iron Pipe Co., FlexRing or Lok-Ring Joint; U.S. Pipe, TR Flex.
Proprietary Restrained River Crossing: Clow Ball and Socket;
U.S. Pipe Usiflex.
Grooved End: AWWA C606-87 and C110/A21.10-93, ductile iron,
250 psi minimum working pressure. Victaulic; Gustin-Bacon.
Flange: AWWA C110/A21.10-93 and ANSI B16.1-89, ductile or
gray cast iron, faced and drilled, 125-pound flat face or 250-pound
raised face. Gray cast iron will not be allowed.
1 of 3
Item
Joints
SECTION 40 23 39.13
DUCTILE IRON PIPE AND FITTINGS
Description
Push-On: 250 psi minimum working pressure, AWWA
C110/A21.10-93 and C111/A21.11-90. American Cast Iron Pipe
Co., Fastite Joints; U.S. Pipe and Foundry, Tyton Joint.
Mechanical: 250 psi minimum working pressure. American Cast
Iron Pipe Co., Mechanical Joint; U.S. Pipe and Foundry,
Mechanical Joint.
Proprietary Restrained: 150 psi minimum working pressure. Clow
Corp., Super-Lock; American Cast Iron Pipe Co., Flex-Ring or
Lok-Ring; U.S. Pipe, TR Flex.
Grooved End: Rigid type radius cut conforming to AWWA C60687, 250 psi minimum working pressure. Victaulic; Gustin-Bacon.
Couplings
Bolting
2 of 3
Item
Gaskets
SECTION 40 23 39.13
DUCTILE IRON PIPE AND FITTINGS
Description
Mechanical, and Proprietary Restrained Joints, Water and
Sewage: Rubber conforming to ANSI/AWWA C111/A21.11-90
Mechanical and Proprietary Restrained Joints, Air: Viton, Fluorel,
or Manufacturers standard for high temperature air service, rated
to 300 degrees F minimum, conforming to ANSI/AWWA
C111/A21.11-90
Grooved End Joints: Halogenated butyl conforming to ASTM
D2000-90 and AWWA C606-87. Gaskets for air service shall be
pressure-responsive synthetic rubber, rated to 300 degrees F
minimum, conforming to ASTM D2000.
Flanged, Water and Sewage Services: 1/8-inch thick, unless
otherwise specified, homogenous black rubber (EPDM), hardness
60 (Shore A), rated to 212 degrees F., conforming to ANSI B16.21
and ASTM D1330 Steam Grade.
Flanged, Air Service: 1/8-inch thick, unless otherwise specified,
Teflon, PTFE, or compressed inorganic fiber with nitrile binder,
rated to 300 degrees F. minimum, conforming to ANSI B16.21 and
ASTM D1330.
Ring gaskets shall not be permitted. Blind flanges shall be
gasketed covering the entire inside face with the gasket cemented
to the blind flange.
Joint Lubricant
3 of 3
Item
Pipe
SECTION 40 23 39.36
STAINLESS STEEL PIPE AND FITTINGS GENERAL SERVICE
Size
Description
2 & smaller
Schedule 40S: ASTM A312/A312M-93,
Type 316 seamless, pickled and
passivated.
Joints
Fittings
2-1/2 thru 6
Schedule 10S: ASTM A778 Rev A-90 aswelded grade, Type 316L.
8 & larger
Schedule 5S: ASTM A778 Rev A-90 aswelded grade, Type 316L.
2 & smaller
2 & smaller
Branch Connections
2 & smaller
All
Cast Carbon Steel: ASTM A216/A216M93, Grade WCA, drilled, ANSI B16.5-88
Class 150 or Class 300 Van Stone Type
with stainless steel stub ends, ASTM A24094 Type 316L as welded grade,
conforming to MSS-SP43, wall thickness
same as pipe.
Item
Unions
Bolting
Gaskets
SECTION 40 23 39.36
STAINLESS STEEL PIPE AND FITTINGS GENERAL SERVICE
Size
Description
2 & smaller
Threaded Forged: ASTM A182/A182M
Rev C-93 Grade F316, 2,000 pound or
3,000 pound WOG, integral ground seats,
AAR design meeting the requirements of
ANSI B16.11-91, bore to match pipe.
All
Forged Flanges: Type 316 stainless steel,
ASTM A320/A320M-94 Grade B8M hex
head bolts and ASTM A194/A194M-94
Grade 8M hex head nuts.
Van Stone Flanges: Carbon steel ASTM
A307-94 Grade B hex head bolts and
ASTM A563-93 Grade A hex head nuts.
Provide same on mating cast iron flange on
valve or equipment with flat ring gasket.
Flanged, Water, and Wastewater Service:
1/8-inch thick, unless otherwise specified,
homogenous black rubber (EPDM),
hardness 60 (Shore A), rated to 212
degrees F., conforming to ANSI B16.21
and ASTM D1330 Steam Grade.
All Flanges
Thread Lubricant
2 & smaller
END OF SECTION
Item
Pipe
Fittings
Joints
SECTION 40 23 39.40
C900 & C905 PVC Pipe and Fittings
Size/Installation
Description
4 IN. 12 IN.
C900 DR 18: Conforming to ASTM D1784
with a cell classification of 12454.
Conforming to AWWA C900
C905 DR 18: Conforming to AWWA C905
Ductile Iron Mechanical Joint Fittings as
specified in 40 23 39.13 CM LINED
DUCTILE IRON PIPE AND FITTINGS with
restraint gland
Push-on: Meeting ASTM D3139 with
gasket meeting ASTM F477
14 IN 48 IN.
Buried
All
Restrained Joints:
C900: Proprietary Locking Gaskets
C905: Joint Restraint Harness;
EBAA Iron Series 2800 or equal
Flanges
Couplings
None
Dissimilar Pipe Materials
Not allowed
Transition Coupling: Smith-Blair Style 413
or equal
END OF SECTION
1 of 1
Item
Pipe
SECTION 40 23 39.43
POLYVINYL CHLORIDE (PVC) PIPE AND FITTINGS
Size
Description
All
Schedule 80 PVC: Type IV, Grade I or
Class 23447-B conforming to ASTM
D1785-05.
Fittings
All
Joints
All
Flanges
All
Bolting
All
Gaskets
Solvent Cement
Thread Lubricant
All
All
All
END OF SECTION
Item
Pipe
SECTION 40 23 39.56
HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS
Size
Description
Smaller than 4
DR 9 (CTS): conforming to ASTM D2239,
ASTM D2737, D2737 or ASTM 3035. Shall
meet AWWA C901. With pressure rating of
250 psi
4 - 42
Fittings
Smaller than 4
4 - 42
Joints
Thread Lubricant
Smaller than 4
4 - 42 Similar materials
4 - 42 Dissimilar materials
All
END OF SECTION
1 of 1
SECTION 40 23 39.62
MEDIUM DENSITY POLYETHYLENE (MDPE) PIPE AND FITTINGS FOR GAS/LP SERVICE
Item
Size
Description
Pipe
3 and less
Fittings
3 and less
Joints
Thread Lubricant
All
END OF SECTION
1 of 1
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 01 60 00 Product Requirements.
c.
Section 01 78 23 Operation and Maintenance Data.
d.
Section 01 79 00 Demonstration and Training.
e.
Section 09 90 00 Painting and Protective Coatings.
f.
Section 40 23 39 Process Piping - General.
1.2
GENERAL
A.
See Section 40 23 39, PROCESS PIPING - GENERAL, which contains information and
requirements that apply to the work specified herein and are mandatory for this project.
B.
1.3
SUBMITTALS
A.
Section 40 23 43
Process Valves
1.4
O&M Manuals: Content, format, and schedule for providing as specified in Section 01 78 23,
OPERATION AND MAINTENANCE DATA.
B.
PART 2 - PRODUCTS
2.1
GENERAL
A.
Valve to include operator, actuator, hand wheel, chain wheel, extension stern, floor stand, worm
and gear operator, operating nut, chain, wrench, and accessories for a complete operation. For
operator specifications, see section 40 92 16 VALVE AND GATE OPERATORS.
B.
Valve to be suitable for intended service. Renewable parts not to be of a lower quality than
specified.
C.
D.
E.
F.
2.2
SCHEDULE
A.
2.3
Requirements relative to this section for certain type of actuated or process valves are shown
on the Valve Schedules attached as Supplements to the related Sections.
MATERIALS
A.
Brass and bronze valve components and accessories that have surfaces in contact with water
to be alloys containing less than 16% zinc and 2% aluminum.
B.
2.4
FACTORY FINISHING
A.
B.
Exposed Valves:
1.
In accordance with Section 09 90 00, PAINTING AND PROTECTIVE COATINGS. Match
adjacent piping system.
2.
Safety isolation valves and lockout valves with handles, hand wheels, or chain wheels
safety yellow.
Section 40 23 43
Process Valves
2.5
VALVES
A.
Gate Valves:
1.
Type V 142: Resilient Wedge Gate Valve 2 Inches to 12 Inches
a.
UL listed, iron body, bronze mounted, designed for fire protection service, rising
stem, outside screw and yoke, ANSI B16.1 flanged ends, rated 175-pound WOG.
b.
Single disc, resilient seat, parallel seat, gate stem in bronze bushing through stuffing
box.
c.
Furnish with supervisory switch. Valve supervised in OPEN position so closing results
in actuation of alarm.
d.
Manufacturers and Products:
1). Mueller.
2). American.
B.
Ball Valves:
1.
Type V300: Metal Body Ball Valve, Less than 6 Inch Size
a.
General
1)
Type: Non-lubricated and capable of sealing in either flow direction.
3). End Connections:
a)
Threaded or solder ends for sizes 3-inch and smaller.
b)
Class 150 flanged for sizes larger than 3 inch. Flanges shall conform
to ANSI/ASME B16.1 standards.
4). Stem Packing: Manually adjustable while valve is under pressure.
5). Shafts: Rigidly connected to the ball by a positive means. The connection
shall be designed to transmit torque equivalent to at least 75 percent of the
torsional strength of the shaft.
6). Handles: Stainless steel latch lock handle with vinyl grip and stainless steel
nut designed to open and close the valve under operating conditions.
7). Temperature Limits: Suitable for operation between minus 20 and 350 degrees Fahrenheit.
b.
Materials:
1). Valves in Copper Lines: Bronze body
2). Valves in Steel and Ductile Iron Piping: Ductile iron or cast steel bodies.
3). Ball: Type 304 or 316 stainless steel.
4). Seats: PTFE.
5). Stem Seals: TFE or Viton
6). Bearings: Self-lubricated, corrosion resistant material that will not contaminate
potable water.
c.
Manufacturers:
1). Apollo.
2). Nibco.
3). Milwaukee Valve.
2.
Type V302: Metal Body Ball Valve, 6 Inch Size and Larger
a.
General
1). Type: Non-lubricated and capable of sealing in either flow direction.
2). Conform to AWWA C 507.
3). Stem Packing: Manually adjustable while valve is under pressure.
4). ANSI B16.1, Class 125 flanged ends.
b.
Materials
1). Body: ASTM A48 cast iron and integrally cast bronze bushed trunnions.
2). Ball: Type 304 or Type 316 stainless steel.
3). Seats: TFE.
4). Stem Seals: TFE or Viton.
c.
Manually operated ball valves shall have self-locking worm gear type actuator with
position indicator. Gearing shall be permanently lubricated. Provide adjustable
screws to stop travel at both Open and Closed positions.
Section 40 23 43
Process Valves
d.
3.
4.
C.
Manufacturers:
1). Henry Pratt.
2). McANNA/MARPAC
Type V303 Instrumentation Ball Valves
a.
Brass or stainless steel body ball valve, nylon handle.
b.
Manufacturers and Products:
1). Swagelok, 40G Series.
2). Imperial Eastman; Series 200.
Type V330 Plastic Body Ball Valve
a.
General:
1). Type: Non-lubricated and capable of sealing in either flow direction.
2). End Connections: True union; solvent or heat welded to piping.
3). Operator Handle: Lever.
b.
Materials
1). Body: Polyvinyl chloride (PVC).
2). Ball: Polyvinyl chloride (PVC).
3). Seats: Teflon (TFE).
4). O-rings: Viton (FPM).
c.
Manufacturers
1). Asahi/America, Inc.
2). Nibco.
Butterfly Valves:
1.
General: Butterfly valve specified as AWWA C504 to be in compliance with AWWA C504
and following requirements:
a.
Suitable for throttling operations and infrequent operation after periods of inactivity.
b.
Elastomer seats bonded or vulcanized to body shall have adhesive integrity of
bond between seat and body assured by testing with minimum 75-pound pull in
accordance with ASTM D429, Method B.
c.
Bubble-tight with rated pressure, or any pressure lower than rated, applied from
either side with the valve mounted in any orientation.
d.
No travel stops for the disc on interior of the body.
e.
Self-adjusting V-type.
f.
Isolate metal-to-metal thrust bearing surfaces from flow stream.
g.
Valves intended for air service shall meet ANSI B16.104.
2.
Type V500: Butterfly Valve, 4 Inch Size and Larger
a.
Valve Style: Flanged end, short body type.
b.
AWWA C504, Class 150B.
c.
Cast iron body, cast or ductile iron disc with Type 304 stainless steel shaft, Buna N
or NBR rubber seat bonded or molded in body only, and stainless steel seating
surface.
d.
Manufacturers:
1). DeZurik.
2). Henry Pratt.
3). Val-Matic.
3.
Type V504: Butterfly Valve, 4 Inch Size and Larger
a.
Valve Style: Mechanical joint end type AWWA C504.
b.
Class 150B, Valve position indicator at valve box locations. Indicator to be
hermetically sealed and show valve disc position, direction of rotation, and number
of turns from FULLY OPENED to FULLY CLOSED, valve by valve manufacturer.
c.
Cast iron body, cast or ductile iron disc with Type 304 stainless steel shaft, Buna N
or NBR rubber seat, and stainless steel seating surface.
d.
Manufacturers:
1). Henry Pratt.
2). DeZurik.
3). Val-Matic.
Section 40 23 43
Process Valves
D.
Section 40 23 43
Process Valves
3)
4)
5)
6)
7)
8)
9)
E.
Section 40 23 43
Process Valves
1)
2)
3)
5.
6.
7.
8.
Maximum Inlet Pressure: 250 psig (Cast Iron), 300 psig (Steel).
Droop: 10% of outlet pressure setting.
Maximum Differential Pressure: 150 psig or body rating limit, whichever is
lower.
4)
Body: Ductile Iron, Cast Steel, or Bronze.
5)
Disc Retainer and Diaphragm Washer: Cast Iron, Cast Steel, or Bronze.
6)
Stem, Nut and Spring: Stainless Steel
7)
Diaphragm: Nylon Reinforced Buna-N Rubber
b.
Manufacturers:
1)
Cla-Val.
2)
Watts.
3)
Golden Anderson.
Type V730: Pressure Relief Valve, 2 Inch Size and Smaller
a.
Direct diaphragm, spring controlled, Type 316 stainless steel body, spring case,
Type 316 stainless steel diaphragm, stainless steel valve stem.
b.
Capable of opening when upstream-pressure reaches a maximum set point.
c.
Manufacturers:
1)
Fisher.
2)
Or equal.
Type V732: Pressure Relief Valve, Pressure Sustaining Valve, 1 Inch Size and Larger
a.
Hydraulically operated, diaphragm, actuated, pilot controlled globe valve, cast iron
body, ANSI B16.1 flanged ends, rated 175 psi, stainless steel trim, stainless steel
stem, externally mounted strainers with cocks, to open when upstream pressure
reaches a maximum set point.
b.
Manufacturers:
1)
Cla-Val.
2)
Or equal.
Type V750: Well Service Air Valve, 1/2 Inch Size and Larger
a.
Fully automatic float operated valve, suitable for vertical turbine pump discharge
service, designed to exhaust air which is present in pump column on pump start-up
and allow air to re-enter the column on pump shutdown or should a negative
pressure occur.
b.
Valves used in potable water service shall be NSI/ANSI 61 certified.
c.
Valve shall be equipped with a dual post throttling device to provide adjustable
control of the exhaust rate and allow free air to flow into the valve through a
separate inlet port.
d.
Valve body, cover, trim and baffle shall be constructed of either cast iron or ductile
iron with stainless steel float, guide shafts and bushings.
e.
Manufacturers:
1)
Val-Matic.
2)
DeZurik.
Type V755: Clean Water Surge Suppression Combination Air Valve, 1 Inch Size and
Larger
a.
Surge Suppression Air Valves shall be automatic float operated valves designed to
control the exhaust of air during the filling of a piping system and close upon liquid
entry. The valve shall fully open during draining or if a negative pressure occurs.
The valve shall also release accumulated air from a piping system while the
system is in operation and under pressure.
b.
A Regulated Exhaust Device shall be provided to reduce pressure surges due to
column separation or rapid changes in velocity and pressure in the pipeline.
c.
Valve shall perform functions of both air release and Air/Vacuum valves and be
furnished as a single body.
d.
Valves shall be manufactured and tested in accordance with American Water
Works Association (AWWA) Standard C512.
e.
Valves used in potable water shall be NSF/ANSI certified.
Section 40 23 43
Process Valves
f.
9.
F.
2.6
Valve body and structure shall be constructed of cast iron or ductile iron. Float,
guide shafts and bushings shall be stainless steel.
g.
Manufacturers:
1)
Val-Matic.
2)
DeZurik.
Type V780: Safety Relief Valve for Air Service, 1-1/2 Inch Size through 3 Inch Size
a.
Spring loaded, adjustable pressure relief valve for process air service, with
stainless steel trim; seat material suitable for elevated temperatures above 300 F,
test pull ring or lever.
b.
Manufacturers:
1)
Kunkle.
2)
Apollo Valve
Miscellaneous Valves:
1.
Type V940 Solenoid Valve 2 inches and smaller
a.
Two-way internal pilot operated diaphragm type, brass body, resilient seat suitable
for air or water, solenoid coil molded epoxy, NEMA Class A, 120 volts ac, 60-Hz,
unless otherwise indicated. Solenoid enclosure NEMA 250, Type 4 unless
otherwise indicated. Size and normal position (OPEN or CLOSED when deenergized) as indicated.
b.
Minimum operating pressure differential no greater than 5 psig, maximum
operating pressure differential not less than 125 psig.
c.
Manufacturers and Products:
1). ASCO
2). Skinner
TAGGING REQUIREMENTS
A.
2.7
The tags shall be attached to the valves by soldered split key rings so that ring and tag cannot
be removed. The tag shall bear the 1/4 die-stamped equipment identification number as
indicated in the Contract Documents.
ACCESSORIES
A.
B.
Cast Iron Valve Box: Designed for traffic loads, sliding type, with minimum of 6 ID shaft.
1.
Box: Cast iron with minimum depth of 9.
2.
Lid: Cast iron, minimum depth 3, marked for the appropriate service.
3.
Extensions: Cast iron.
PART 3 - EXECUTION
3.1
3.2
A.
Flange Ends:
Section 40 23 43
Process Valves
1.
2.
B.
Screwed Ends:
1.
Clean threads by wire brushing or swabbing.
2.
Apply joint compound.
C.
Valve Orientation:
1.
Install operating stem vertical when valve is installed in horizontal runs of pipe having
centerline elevations 4 6 or less above finished floor, unless otherwise shown.
2.
Install operating stem horizontal in horizontal runs of pipe having centerline elevations
between 4 6 and 6 9 above finish floor, unless otherwise shown.
3.
Orient butterfly valve shaft so that unbalanced flows or eddies are equally divided to each
half of the disc, i.e., shaft is in the plane of rotation of the eddy.
4.
If no plug valve seat position is shown, locate as follows:
a.
Horizontal Flow: The flow shall produce an unseating pressure, and the plug
shall open into the top half of valve.
b.
Vertical Flow: Install seat in the highest portion of the valve.
D.
Install a line size ball valve and union upstream of each solenoid valve, in-line flow switch, or
other in-line electrical device, excluding magnetic flow meters, for isolation during maintenance.
E.
F.
G.
Extension Stem for Operator: Where the depth of the valve is such that its centerline is more
than 3 feet below grade. Furnish an operating extension stem with 2operating nut to bring the
operating nut to a point 6 below the surface of the ground and/or box cover.
H.
Torque Tube: Where operator for quarter-turn valve is located on floor stand. Furnish extension
stem torque tube of a type properly sized for maximum torque capacity of the valve.
I.
Floor Box and Stem: Steel extension stem length shall locate operating nut in floor box.
3.3
B.
Test that valves open and close smoothly with operating pressure on one side and atmospheric
pressure on the other, in both directions for two-way valve and applications.
C.
Inspect air and vacuum valves as pipe is being filled to verify venting and seating is fully
functional.
D.
Count and record number of turns to open and close valve; account for any discrepancies with
Manufacturers data.
E.
Set, verify, and record set pressures for all relief and regulating valves.
F.
Section 40 23 43
Process Valves
G.
3.4
Test hydrostatic relief valve seating; record leakage. Adjust and retest to maximum leakage of
0.1 gpm per foot of seat periphery.
MANUFACTURERS SERVICES
A.
A Manufacturers representative for the equipment specified herein shall be present at the
jobsite for the minimum person-days listed for the services herein under, travel time excluded:
1.
2 person-days for installation assistance, inspection, and certification of the installation.
Provide certificate.
2.
2 person-days for functional and performance testing.
3.
2 person-days for pre-startup classroom or jobsite training of OWNERS personnel.
B.
Training of OWNERS personnel shall be at such times and at such locations as requested by
OWNER.
C.
3.5
MANUFACTURERS CERTIFICATE(S)
A.
END OF SECTION
10
Section 40 23 43
Process Valves
SUMMARY
A.
Section includes: the Work necessary to furnish and completely install, adjust, protect, put in
operation, and test fabricated slide and sluice gates as shown on the Drawings and as specified
herein.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 01 60 00 Product Requirements.
c.
Section 01 78 23 Operation and Maintenance Data.
d.
Section 01 79 00 Demonstration and Training.
e.
Section 05 50 00 Metal Fabrications.
f.
Section 09 90 00 Painting and Protective Coatings.
1.2
GENERAL
A.
B.
Like items of equipment provided hereinafter shall be the end products of one manufacturer to
achieve standardization of appearance, operation, maintenance, spare parts, and
manufacturers services.
C.
Unit Responsibility: The Work requires that slide and sluice gates, complete with all accessories
and appurtenances (including, but not necessarily limited to, thimbles, gates, stems, hand
actuators, and other components), be the end product of one responsible system manufacturer
or responsible system supplier. Unless otherwise indicated, the Contractor shall obtain each
system from the responsible supplier of the equipment, which supplier shall furnish all
components and accessories of the system to enhance compatibility, ease of operation and
maintenance, and as necessary to place the equipment in operation in conformance with the
specified performance, features and functions without altering or modifying the Contractors
responsibilities under the Contract Documents. The Contractor is responsible to the Owner for
providing the equipment systems as specified herein.
D.
E.
Section 40 23 46
Fabricated Slide and Sluice Gates
1.3
DEFINITIONS
A.
Slenderness Ratio: The ratio of the maximum unsupported stem length to the stem crosssection radius of gyration.
B.
Self-Contained: The arrangement of the gate operator, supported by the gate frame, such that
operating thrust loads are not applied external to the assembly.
1.4
SYSTEM COORDINATION
A.
1.5
Coordinate gate dimensional requirements with concrete formwork and reinforcing details where
gates are to be embedded in concrete walls and floor slabs.
SUBMITTALS
A.
B.
Section 40 23 46
Fabricated Slide and Sluice Gates
1.6
O&M Manuals: Content, form, and schedule for providing as specified in Section 01 78 23,
OPERATION AND MAINTENANCE DATA.
B.
1.7
WARRANTY
A.
Provide warranty for a period of 24 months after the final acceptance of the equipment by the
Owner and Engineer. The warranty shall stipulate that the equipment furnished is suitable for
the purpose intended and free from defects of material and workmanship for the duration of the
warranty. In the event the equipment fails to perform as specified, the Manufacturer will
promptly repair or replace the defective equipment without additional cost to the Owner.
B.
Spare parts identified within this specification shall not be used to address warranty repairs.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Where a Manufacturers standard equipment name and/or model number is listed, the
equipment system shall be provided as modified to conform to the performance, functions,
features, and materials of construction as specified herein.
B.
2.2
GATE TYPES
A.
2.3
Rising stem type unless stated otherwise on the Drawings and/or Gate Schedule, with assembly
styles designated as follows:
1.
Style A: Upward acting slide gate type for mounting in channels with concrete embedded
invert.
2.
Style B: Downward acting slide gate type with P-type invert seal for wall surface
mounting on concrete structures.
3.
Style C: Downward acting slide gate weir type with P-type invert seal for wall surface
mounting on concrete structures.
4.
Style D: Upward acting sluice gate type for wall surface mounting on concrete structures.
5.
Style E: Upward acting stop or sluice gate type for mounting in channels with concrete
embedded invert.
PERFORMANCE REQUIREMENTS
A.
2.4
Leakage shall not exceed 0.1 gallon per minute per foot of gate periphery under either seating
or unseating head conditions.
SLIDE GATES
A.
Materials
1.
Aluminum Plate and Shapes: ASTM B209 and B308, Alloy 6061-T6.
2.
Stainless Steel:
Section 40 23 46
Fabricated Slide and Sluice Gates
a.
b.
B.
Construction
1.
Guide Frames:
a.
Stainless steel.
b.
All gate frames shall be self-contained unless explicitly stated otherwise on
drawings and/or on Gate Schedule.
c.
Vertical Guides: Design for maximum rigidity, and extend in one continuous piece
from the gate invert to form posts for support of gate operators. When guides
extended above the operating floor, they shall be sufficiently strong so that no
further reinforcements are required.
1) Weight: Not less than 9 pounds per linear foot for stainless steel.
2) Incorporate a replaceable UHMW polyethylene bearing strip in a retainer slot
on the downstream side (unseating head side) of the gate.
d.
Join vertical guide frames and invert with factory welded comers.
e.
Size guided slot to provide a minimum disc engagement of 1 on each side.
C.
Disc:
1.
Disc Plate (Sliding Member): One-piece aluminum. Reinforce as required so that the
disc will not deflect more than 1/360 of the gate span, when the upstream liquid depth
(seating head side) is as shown on the schedule and the downstream liquid depth is less
than .
2.
Reinforce gate disc with one-piece aluminum angles or channels welded to the disc plate.
Bolted reinforcements will not be permitted.
3.
Where required on the Drawings, furnish V-notch or rectangular weir cutouts in the disc
plate and cutout dimensions and location to match details shown on the Drawings.
D.
E.
Stems:
1.
1 minimum diameter, ASTM A276, Type 304 stainless steel.
2.
Threads: ACME type with RMS surface roughness of 63 micro-inches or less on the
flanks for manually operated gates and 32 micro-inches or less on the flanks for
electrically operated gates. Extend threaded portion of stem 2 above operator when
gate is in CLOSED position.
3.
Slenderness ratio shall not exceed 200.
4.
Stems to withstand in compression, without damage, the thrust equal to at least 250% of
the rated output of the hoisting mechanism, with a 40-pound effort applied to the hand
wheel or crank.
5.
Cast iron bushed stem guides, mounted on cast iron brackets; adjustable in two
directions and spaced so that the slenderness ratio does not exceed 200.
6.
Adjustable stop collar for the CLOSED position.
7.
Connect the stems to the disc plate with a yoke, bolted to the stem and welded to the
disc.
8.
Slide gates having a width greater than twice the height or width greater than 84 shall
have dual stems.
9.
For downward opening weir type gates, locate stems near outside edges of gate.
F.
Stem Covers:
1.
Transparent plastic, vented pipe stem cover and cap.
Section 40 23 46
Fabricated Slide and Sluice Gates
2.
G.
2.5
Gate Operators
1.
Hand wheel-Operated Bench Stands:
a.
Sealed, ball-thrust, roller or needle bearing type and equipped with bronze lift nut,
internally threaded with Acme threads.
b.
Furnish mechanical seals at housing penetrations.
c.
Hand wheel and Baseplate: Cast iron or cast aluminum.
d.
Manual Effort: Not to exceed 40 pounds.
2.
Identification Tagging Requirements:
a.
For each gate operator, l-1/2 minimum diameter heavy brass tag, and bearing the
gate tag number shown in the Gate Schedule.
b.
Attach the tags to the operator by soldered split key rings such that ring and tag
cannot be removed. Use block type numbers and letters with minimum height.
Numbers and letters shall be stamped on and filled with black enamel.
SLUICE GATES
A.
General:
1.
Unless otherwise specified, conform to AWWA C501, rising stem type.
2.
Minimum Acceptable Casting Thickness for Cast Iron Components: 3/4.
3.
Gates shall open to the full dimension of the opening as indicated in the Gate Schedule.
B.
Wall Thimbles:
1.
Cast-iron, one-piece construction, in accordance with ASTM A126, Class B.
2.
Cast center ring or water stop around periphery.
3.
Front Flange: Machined, with tapped holes for sluice gate frame attaching studs.
4.
Stamp vertical center lines of metal with word TOP.
5.
Furnish permanent gasket of uniform thickness or mastic between sluice gate frame and
thimble.
6.
Coordinate with sluice gate manufacturer as necessary for required bolt-hole size and
pattern for connection to sluice gate thimbles.
C.
Frames:
1.
Cast iron one-piece construction, in accordance with ASTM A126, Class B.
2.
Unless specifically noted otherwise, all gates shall be furnished with self-contained
frames.
3.
Machine contact surfaces.
a.
Machine dovetailed grooves on front face, into which seat facings shall be driven
and machined.
b.
Machine back flange to bolt directly to machined-face of wall thimble cast in
concrete.
4.
For frames with top and bottom wedges, furnish integrally cast pads machined with
keyways to receive wedge seats.
5.
Where side clearance is limited, flanged frames may require mounting holes to be drilled
through to front face of frame.
D.
Discs:
1.
Cast iron, one-piece construction with integrally cast vertical and horizontal ribs in
accordance with ASTM A126 Class B.
2.
Machine dovetailed grooves on seating face, into which seat facings shall be driven and
machined.
3.
Wedge Pads: Integrally cast on disc and machined to receive adjustable wedges.
4.
Cast a heavily reinforced nut pocket integrally on vertical centerline above horizontal
centerline to receive thrust nut.
Section 40 23 46
Fabricated Slide and Sluice Gates
E.
Guides:
1.
Cast iron, one-piece, in accordance with ASTM A126 Class B designed to withstand total
thrust from water pressure and wedging action.
2.
Machine contact surfaces.
3.
Length: Sufficient to retain and support disc in fully OPEN position.
4.
Attach to frame with ASTM A167, Type 304 stainless steel studs; dowel to prevent
relative motion between guides and frame or cast guides integrally with frame.
5.
Securely attach wedge seats to machined pads on guides.
6.
Maximum spacing between guides shall be no more than 8 feet.
F.
G.
Stems:
1.
1 minimum diameter, ASTM A276, Type 304 stainless steel.
2.
Threads: Acme type with RMS surface roughness of 63 micro-inches or less on flanks
for manually operated gates and 32 micro-inches or less on flanks for electrically
operated gates. Extend threaded portion of stem 2 above operator when gate is in
CLOSED position.
3.
Couplings:
a.
Use when stems have more than one section.
b.
Same material as stem.
c.
Furnish with internal threads that transmit full thrust of stem.
d.
Hold in place on stem with bolts or keys and keyways.
e.
Same size and interchangeable.
4.
Slenderness ratio shall not exceed 200.
5.
Withstand in compression, without damage, thrust equal to at least 250% of rated output
of hoisting mechanism, with a 40-pound effort applied to hand wheel or crank.
6.
Cast iron, bushed stem guides, mounted on cast iron brackets, adjustable in two
directions and spaced so that slenderness ratio does not exceed 200.
7.
Adjustable stop collar for CLOSED position.
H.
Stem Covers:
1.
Transparent plastic, vented pipe stem cover and cap.
2.
Provide with OPEN/CLOSED designators with 1 graduations on Mylar pressure
sensitive, adhesive tape, suitable for outdoor application.
I.
Section 40 23 46
Fabricated Slide and Sluice Gates
b.
c.
d.
J.
2.6
Securely fastened to bottom cross member of frame on a stop plate, with a retainer
and stainless steel fasteners.
Make top surface of seal flush with invert of gate opening.
Machine full length of bottom edge of disc accurately to make contact with seal
when disc is closed.
Operators
1.
General:
a.
Components: Withstand a minimum of 250% of design torque or thrust at extreme
operator positions without damage.
b.
Sizing: Include hydraulic down-pull load for heads greater than 30 and for nominal
gate widths greater than 5.
c.
Gear train and gate stem sections shall produce a self-locking drive train.
d.
Lift Nuts: Internally threaded with cut or cold-rolled Acme threads corresponding to
stem threading.
e.
Roller Bearings: Ball-thrust or tapered above and below lift nut to support both
opening and closing thrusts.
1) Grease lubrication fittings for bearings.
2) Input pinions with needle or ball bearings.
f.
Lubrication: Furnish rising stem gates with an insert lubricator flange in lift, with
grease fitting for greasing stem threads below stem nut.
2.
Type 1, Manual, Hand wheel-Operated Floor Stands:
a.
Manual Effort: Not to exceed 40 pounds.
b.
Hand wheel: Directly drive a replaceable bronze stem nut for a rising gate stem,
bearing mounted on a cast iron pedestal and base.
3.
Identification Tagging Requirements:
a.
For each gate operator, 1-1/2 minimum diameter heavy brass tag, bearing gate
tag number shown in schedule.
b.
Attach tags to operator by soldered split key rings so that ring and tag cannot be
removed. Use block type numbers and letters with minimum high numbers and
letters stamped on and filled with black enamel.
STOP GATES
A.
Materials
1.
Aluminum Plate and Shapes: ASTM B209 and B308, Alloy 6061-T6.
2.
Stainless Steel:
a.
Plate, Sheet, and Strip: ASTM A240, Type 304L.
b.
Bars and Shapes: ASTM A276, Type 304L.
B.
Construction
1.
Guides:
a.
Stainless steel.
b.
All gate guides shall be embedded in concrete as shown on the Drawings.
c.
Vertical Guides: Design for maximum rigidity, and extend in one continuous piece
from the gate invert to top of wall or operating floor. Guides shall not extend above
the operating floor.
1) Weight: Not less than 9 pounds per linear foot for stainless steel.
2) Incorporate a replaceable UHMW polyethylene bearing strip in a retainer slot
on the downstream side (unseating head side) of the gate.
d.
Join vertical guide frames and invert with factory welded comers.
e.
Size guide slot to provide a minimum disc engagement of 1 on each side.
C.
Disc:
1.
Disc Plate (Sliding Member): One-piece aluminum. Provide hand hole for manual
removal of gate. Reinforce as required so that the disc will not deflect more than 1/360 of
Section 40 23 46
Fabricated Slide and Sluice Gates
2.
3.
2.7
the gate span, when the upstream liquid depth (seating head side) is as shown on the
schedule and the downstream liquid depth is less than .
Reinforce gate disc with one-piece aluminum angles or channels welded to the disc plate.
Bolted reinforcements will not be permitted.
Where required on the Drawings, furnish V-notch or rectangular weir cutouts in the disc
plate and cutout dimensions and location to match details shown on the Drawings.
ACCESSORIES
A.
Lifting Lugs: Equipment weighing over 100 pounds shall be provided with lifting lugs.
B.
Anchor Bolts: ASTM A193, Type 316 stainless steel, sized by equipment Manufacturer at least
1/2 in diameter, or as shown, and as specified in Section 05 50 00, METAL FABRICATIONS.
C.
Staff Gauges: For all downward acting Weir Gates. Graduated in 1/4 and marked every inch
and foot.
D.
Extension Bonnet for Gate Operator: Complete with stem and accessories for gate and
operator.
E.
F.
Painting: Coat all aluminum surfaces in contact with concrete with un-thinned Bitumastic paint
or insulate with suitable protective neoprene gasket material.
2.8
Tools: The work includes furnishing two complete set of special tools recommended by the
manufacturer for maintenance and repair of each separate type of equipment; tools shall be
stored in tool boxes and identified with the equipment number by means of stainless steel or
solid plastic name tags attached to the box.
B.
Spare parts shall be tagged by project equipment number and identified as to part number,
equipment manufacturer and subassembly component (if appropriate). Spare parts subject to
deterioration such as ferrous metal items and electrical components shall be properly protected
by lubricants or desiccants and encapsulated in hermetically sealed plastic wrapping. Spare
parts with individual weights less than 50 pounds and dimensions less than 2 feet wide, or 18
inches high, or 3 feet in length shall be stored in a wooden box with hinged wooden cover and
locking clasp. Hinges shall be strap type. The box shall be painted and identified with stenciled
lettering stating the name of the equipment, equipment numbers, and the words spare parts. A
neatly typed inventory of spare parts shall be taped to the underside of the cover.
C.
Quantity
1 of each different size
1 of each different size
1 complete set
Section 40 23 46
Fabricated Slide and Sluice Gates
2.9
FABRICATION
A.
Shop/Factory Finishing: Shop prime and finish coatings shall be as required in Section 09 90
00, PAINTING AND PROTECTIVE COATINGS, System No. 2. Coordinate color with OWNER.
PART 3 - EXECUTION
3.1
Each drive unit, including motor, shall be completely factory assembled, aligned, and securely
crated for shipment. Accessory equipment which cannot be shipped assembled to the unit, such
as shafts, baseplates, spare parts, and anchorage materials, shall be separately crated, clearly
marked as to the contents, and shipped on the same shipment as the drives.
B.
For shipment, exposed surfaces subject to rust, such as mounting flange faces, etc., shall be
covered with a rust-preventive compound such as Kendall No. 5, or equal.
3.2
B.
C.
Storage: Products shall be carefully stored in a manner that will prevent damage and in an area
that is protected from the elements.
D.
3.3
INSTALLATION
A.
In strict accordance with the Manufacturers written instructions and recommendations in the
locations shown on the Drawings and the Gate Schedule.
B.
C.
D.
E.
Accurately place anchor bolts using templates furnished by the Manufacturer and as specified in
Section 05 50 00, METAL FABRICATIONS.
F.
G.
Extension Stem for Operator: Furnish, as required by the Drawings, an operating extension
stem with 2 operating nut to bring the operating nut to a point 6 below the surface of the
ground and/or box cover.
Section 40 23 46
Fabricated Slide and Sluice Gates
H.
3.4
Floor Box and Stem: Steel extension stem length shall locate operating nut in the floor box.
QUALITY CONTROL
A.
Functional Test:
operators.
B.
Performance Test: Perform under actual or approved simulated operating conditions, and test
for a continuous 3-hour period without malfunction. Adjust, realign, or modify units and retest if
necessary.
3.5
Prior to plant start-up, ensure proper movement of all slide gates and
MANUFACTURERS SERVICES
A.
A manufacturers representative for the equipment specified herein shall be present at the job
site for the minimum person-days listed for the services hereinunder, travel time excluded:
1.
Installation, Startup and Testing Services:
a.
1 person day for installation assistance, inspection and Certificate of Proper
Installation.
b.
1/2 person-day for functional and performance testing.
c.
Provide qualifications of Manufacturers Representative.
2.
Training Services:
a.
1 person-day of prestart classroom or jobsite training of Owners personnel.
b.
Training of Owners personnel shall be at such times and at such locations as
required and approved by the Owner.
B.
3.6
MANUFACTURERS CERTIFICATE(S)
A.
3.7
A.
The supplement listed below, following END OF SECTION, is a part of this Specification.
1.
Fabricated Slide / Sluice Gate Schedule.
END OF SECTION
10
Section 40 23 46
Fabricated Slide and Sluice Gates
New Intake
Pump
Station
Existing
Intake Pump
Station
Location
Assembly
Style
Aluminum
Aluminum
Material
Field Verify
Circular
Opening
Shape
NSC
NSC
STD
STD
Field
Verify
N/A
N/A
Weir
Cutout
Width/
Height
(inches)
F = Flatback; SC = Self-Contained with Operator 3 feet above Walking Surface; NSC = Non Self-Contained.
STD = Standard; FB = Flushbottom.
MO = Motor Operated; refer to Section 40 23 43 for types of Electric Operators; FB = Floorbox.
Opening
Invert
Elevation
(feet)
24/24
Nominal
Gate
Width/
Height
(inches)
1 of 1
Comments:
1.
Contractor to field verify location, dimensions, and selected gate with engineer prior to ordering gate.
Notes:
1.
2.
3.
General Notes:
1.
Refer to Drawing for structure finished floor and top of structure.
2.
Invert elevation is bottom of gate in lowest position.
3.
For weir type gates, invert elevation is top of weir most closed position.
4.
For sluice type gates, nominal pipe diameter shown.
5.
* Denotes value to be confirmed for equipment selected.
DSG02
DSG01
Gate ID
Tag
Type of Type of
Frame Closure
(Note 1) (Note 2)
N/A
N/A
Weir
Max/Min
Invert
Elevation
(feet)
FB
FB
Type of
Operator
(Note 3)
Rising
Rising
Stem
Type
Comments
40 23 46.1 Supplement
Fabricated Slide and Sluice Gate Schedule
25/25
25/25
Design
Operating
Head Seating/
Unseating
Condition (feet)
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 60 00 Product Requirements.
b.
Section 03 30 00 Cast-In-Place Concrete.
c.
Section 09 90 00 Painting and Protective Coatings.
d.
Section 23 05 29 Hangers and Supports for Mechanical Piping and Equipment.
e.
Section 40 23 39 Process Piping General.
1.2
REFERENCES
A.
1.3
A.
PART 2 - PRODUCTS
2.1
GENERAL
A.
Provide required piping specialty items, whether shown or not shown on the Drawings, as
required by applicable codes and standard industry practice.
B.
Rubber ring joints, mechanical joints, flexible couplings, and proprietary restrained ductile iron
pipe joints are considered flexible joints; welded pipe joints are not.
Section 40 24 00
Process Piping Specialties
2.2
CONNECTORS
A.
B.
C.
D.
2.3
EXPANSION JOINTS
A.
Elastomer Bellows:
1.
Type: Reinforced, molded wide-arch.
2.
End Connections: Flanged, drilled 125-pound ANSI B16.1 standard with split galvanized
steel retaining rings.
3.
Washers: Over the retaining rings to help provide a leak proof joint under test pressure.
4.
Thrust Protection: Control rods to protect the bellows from overextension.
5.
Bellows Arch Lining: Buna-N, nitrile, or butyl.
6.
Rated Temperature: 250 F.
7.
Rated Deflection and Pressure:
a.
Lateral Deflection: 3/4 minimum.
b.
Burst Pressure: Four times the working pressure.
c.
Compression deflection and minimum working pressure as follows:
Size
8.
B.
Deflection Pressure
(inch)
(inch)
(psig)
2-1/2 to 12
1.06
150
14
1.65
130
16 to 20
1.65
110
Manufacturers and Products:
a.
General Rubber Corp.; Style 1015 Maxijoint.
b.
Mercer; Flexmore Style 450.
c.
Goodall Rubber Co.; Specification E-711.
Teflon Bellows:
Section 40 24 00
Process Piping Specialties
1.
2.
3.
4.
5.
C.
D.
E.
F.
Section 40 24 00
Process Piping Specialties
d.
2.4
2.5
A.
Double-Strap Iron:
1.
Pressure Rating: Capable of withstanding 150 psi internal pressure without leakage or
over stressing.
2.
Run Diameter: Compatible with the outside diameter of the pipe on which the saddle is
installed.
3.
Taps: Iron pipe threads.
4.
Materials:
a.
Body: Malleable or ductile iron.
b.
Straps: Galvanized steel.
c.
Hex Nuts and Washers: Steel.
d.
Seal: Rubber.
5.
Manufacturers and Products:
a.
Smith-Blair; Series 313 or 366.
b.
Dresser; Style 91.
B.
Nylon-Coated Iron:
1.
Pressure Rating: Capable of withstanding 150 psi internal pressure without leakage or
over stressing.
2.
Run Diameter: Compatible with the outside diameter of the pipe on which the saddle is
installed.
3.
Materials:
a.
Body: Nylon-coated iron.
b.
Seal: Buna-N.
c.
Clamps and Nuts: Stainless steel.
4.
Manufacturer and Product:
a.
Smith-Blair; Style 315 or 317.
2.6
Materials:
1.
In accordance with the applicable piping material specified in the Pipe Data Sheets.
2.
Galvanically compatible with piping.
B.
Union Type:
1.
2 and Smaller: Screwed or solder-joint.
2.
2-1/2 and Larger: Flanged, complete with bolt insulators, dielectric gasket, bolts, and
nuts.
C.
D.
Section 40 24 00
Process Piping Specialties
2.
2.7
b.
Capitol Insulation Unions.
Insulating Couplings:
a.
Dresser; STAB-39.
b.
R. H. Baker; Series 216.
WALL PIPES
A.
B.
2.8
PIPE SLEEVES
A.
B.
C.
Section 40 24 00
Process Piping Specialties
1.
2.
3.
4.
2.9
Type: Interconnected synthetic rubber links shaped and sized to continuously fill annular
space between pipe and wall sleeve opening.
Fabrication: Assemble interconnected rubber links with ASTM A276, Type 316 stainless
steel bolts, nuts, and pressure plates.
Size: According to Manufacturers instructions for the size of pipes shown to provide a
watertight seal between pipe and wall sleeve opening, and to withstand a hydrostatic
head of 40 feet of water.
Manufacturer: Thunderline Link-Seal.
MISCELLANEOUS SPECIALTIES
A.
B.
C.
Spray Nozzles:
1.
Design:
a.
Operating pressure 10 pounds per square inch gauge, at which pressure each
nozzle discharges not less than 3.5 gallons per minute.
1)
Spray: Flat, heavy sheet, fan with uniform distribution.
2)
Fan spray angle: 105 degrees.
3)
Spray deflection with a replaceable deflector insert free to rotate away from
the orifice opening and mechanically locked in place and counterweighted.
b.
Spray nozzles structurally suitable for pressure up to 200 pounds per square inch
gauge.
c.
Nozzles, easy flush type.
d.
Provide split eyelet connectors or weld-0-lets for nozzle connections.
2.
Materials:
a.
Spray Nozzles: Brass.
b.
Nozzles provided with inch national pipe thread, and the orifice diameter not
less than inch.
c.
Replaceable Spray Deflector: Neoprene rubber.
3.
Manufacturers:
a.
Spray Nozzles: Spray System Co, Model 22561, or approved equal.
b.
Split eyelet connectors: Spray Systems Co, Series 8370 and Series 15475, or
approved equal.
D.
Quick Couplings:
1.
Provide female NPT by male quick-connect hose adaptors. All adapters and couplers
shall satisfy dimensional requirements of MIL-C-27487E and shall be cast iron and sized
shown on the Drawings.
2.
Manufacturers and Products: Swagelock; Series QH.
E.
Section 40 24 00
Process Piping Specialties
1.
2.
3.
4.
5.
6.
7.
Type: Twin cam arm actuated, male and female, locking, for chemical loading and
transfer.
Material: Glass-filled polypropylene and PVDF with Teflon gaskets and as recommended
for the service by Manufacturer.
End Connections: NPT threaded or flanged to match piping connections.
Hose shanks for chemical installations.
Plugs and Caps: Female dust cap for each male end, male dust plug for each female
end.
Pressure Rating: 125 psi, minimum at 70 F.
Manufacturers:
a.
OPW; Kamlock
b.
Ryan Herco; 1300 Series
c.
Goodall; Basic Eight
F.
G.
Breakaway Coupling:
1.
Breakaway couplings shall be non-valved coupling.
2.
Pressure Rating: 125 psi, minimum at 70 F.
3.
Couplings shall have flanged ends.
4.
Viton seals shall be provided or seals that are compatible with the chemical service.
5.
Provide one set of spare bolts and seals.
6.
Manufacturers:
a.
Intrico Products, Ltd.
b.
KLAW Products Ltd.
c.
Or equal
PART 3 - EXECUTION
3.1
B.
Install process piping specialties in accordance with manufacturers directions, as shown on the
Drawings, and as specified herein.
3.2
General:
1.
Install thrust protection.
2.
Install flexible couplings to facilitate piping installation, in accordance with approved shop
drawings.
B.
Flexible Joints at Concrete Backfill or Encasement: Install within 18 or one-half pipe diameter,
whichever is less, from the termination of any concrete backfill or concrete encasement.
C.
Section 40 24 00
Process Piping Specialties
3.3
PIPING TRANSITION
A.
Applications:
1.
Provide complete closure assembly where pipes meet other pipes or structures.
2.
Pressure Pipeline Closures: Plain end pieces with double flexible couplings, unless
otherwise shown.
3.
Restrained Joint Pipe Closures: Install with thrust tie-rod assemblies as shown or in
accordance with NFPA 24.
4.
Gravity Pipe Closures: As specified for pressure pipelines, or concrete closures.
5.
Concrete Closures: Use to make connections between dissimilar pipes where standard
rubber gasketed joints or flexible couplings are impractical, as approved.
6.
Elastomer sleeves bonded to pipe ends are not acceptable.
B.
Installation:
1.
Flexible Transition Couplings: Install in accordance with coupling Manufacturers
instructions to connect dissimilar pipe and pipes with a small difference in outside
diameter.
2.
Concrete Closures:
a.
Locate away from structures so that there are at least two flexible joints between
the closure and pipe entering the structure.
b.
Clean pipe surface before closure collars are placed.
c.
Wet non-metallic pipe thoroughly prior to pouring collars.
d.
Prevent concrete from entering pipe.
e.
Extend collar a minimum of 12 on each side of joint with minimum thickness of 6
around outside diameter of pipe.
f.
Make entire collar in one placement.
g.
After concrete has reached initial set, cure by covering with well moistened earth.
3.4
PIPING EXPANSION
A.
Piping Installation: Allow for thermal expansion due to differences between installation and
operating temperatures.
B.
Expansion Joints:
1.
Grooved Joint and Flanged Piping Systems: Elastomer Bellows Expansion Joint.
2.
Nonmetallic Pipe: Teflon Bellows Expansion Joint.
3.
Screwed and Soldered Piping Systems: Copper or Galvanized and Black Steel Pipe
Expansion Compensator, as applicable.
4.
Pipe Run Offset: Flexible Metal Hose.
C.
Section 40 24 00
Process Piping Specialties
D.
3.5
Anchors and Anchor Walls: Install as specified in Section 23 05 29, HANGERS AND
SUPPORTS FOR MECHANICAL PIPING AND EQUIPMENT, to withstand expansion thrust
loads and to direct and control thermal expansion.
SERVICE SADDLES AND THRUST TIES
A.
Service Saddles:
1.
Ferrous Metal Piping (except stainless steel): Double-strap iron.
2.
Plastic Piping: Nylon-coated iron.
B.
Thrust Ties:
1.
Install where shown and where required to restrain the force developed by the specified
test pressure.
2.
Steel Pipe: Attach with fabricated lugs.
3.
Ductile Iron Pipe: Attach with socket clamps against a grooved joint coupling or flange.
4.
Flanged Coupling Adapters: For exposed installations, install Manufacturers anchor
studs through the coupling sleeve.
C.
3.6
3.7
Tie Bolts: Tighten snug prior to applying any pressure to the system.
INSULATING FLANGES, COUPLINGS, AND UNIONS
A.
Applications:
1.
Copper to ferrous metal piping connections.
2.
Cathodically protected piping penetration to buildings and watertight structures.
3.
Submerged to un-submerged metallic piping connections.
4.
Where required for electrically insulated connection.
B.
Installation of Insulating Kits: Drill oversize to accommodate insulating sleeves through the bolt
holes, assuming standard bolt sizes.
C.
Pipe Installation:
1.
Insulating joints connecting immersed piping to non-immersed piping shall be installed
above maximum water surface elevation.
2.
All submerged carbon steel, ductile iron, or galvanized piping in reinforced concrete
basins shall be isolated from the concrete reinforcement steel.
3.8
WALL PIPES
A.
Applications:
1.
As specified in Section 40 23 39, PROCESS PIPING GENERAL
2.
Watertight and Below Ground Penetrations:
a.
Wall pipes with thrust collars.
b.
Provide taps for stud bolts in flanges to be set flush with wall face.
c.
Existing Walls: Rotary drilled holes.
3.
Wall Pipe Installation:
a.
Isolate embedded metallic piping from concrete reinforcement.
b.
Support wall pipes securely by formwork to prevent contact with reinforcing steel
and tie-wires.
Section 40 24 00
Process Piping Specialties
3.9
PIPE SLEEVES
A.
Application:
1.
As specified in Section 40 23 39, PROCESS PIPING GENERAL.
2.
Above Grade in Non-submerged Areas: Hot-dip galvanized after fabrication.
3.
Below Grade or in Submerged or Damp Environments: Shop-lined and coated.
B.
Installation:
1.
Support non-insulating type securely in form work to prevent contact with reinforcing steel
and tie-wires.
2.
Caulk joint with rubber sealant or seal with wall penetration seal.
3.10
A.
MISCELLANEOUS SPECIALTIES
Install in accordance with manufacturers instructions.
END OF SECTION
10
Section 40 24 00
Process Piping Specialties
SUMMARY
A.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 23 07 13 Mechanical Insulation.
1.2
SUBMITTALS
A.
B.
1.3
WARRANTY
A.
Provide warranty as specified in the General Conditions. Warranty shall be valid beginning on
the Substantial Completion date and extending 1 year after the date of final acceptance of
project.
PART 2 - PRODUCTS
2.1
Design Heating Load: Sodium Hydroxide service uses 75. All other services use a 50 column.
Nominal
Pipe Size
(in)
1/4
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2
50 Column Heat
Trace Minimum Capacity (watts/ft)
1.9
2.5
2.9
2.2
2.5
2.8
3.2
3.8
1
75 Column Heat
Trace Minimum Capacity (watts/ft)
2.9
3.9
4.5
3.4
3.9
4.3
5.0
5.8
Section 40 41 13
Heat Tracing
Nominal
Pipe Size
(in)
3
3-1/2
4
6
8
10
12
14
16
18
20
24
2.2
50 Column Heat
Trace Minimum Capacity (watts/ft)
4.4
3.6
3.9
5.3
6.7
8.1
7.3
7.9
8.9
8.2
9.0
10.6
75 Column Heat
Trace Minimum Capacity (watts/ft)
6.8
5.5
6.0
8.2
10.3
12.5
11.3
12.2
13.8
12.6
13.9
16.3
Cable: Self-limiting, parallel circuit construction consisting of continuous inner core of variable
resistance conductive heating material between two parallel copper bus wires. Provide tinned
copper braid for PVC, FRP, and stainless steel applications.
B.
UL Listing: Listed as self-limiting tracing material for freeze protection application in ordinary
conditions.
C.
D.
E.
Service Voltage: As indicated by branch circuits provided for heat tracing on the Drawings.
F.
2.3
CONNECTION SYSTEM
A.
B.
Operating Monitor Light: Furnish with each circuit power connection kit to indicate when heat
tracing is energized.
C.
Section 40 41 13
Heat Tracing
4.
5.
6.
2.4
b.
Thermon; Tee Snap.
c.
Nelson; PLT-BY
End Seal Kit:
a.
Pentair Raychem; E-100-A, E-100-L-A.
b.
Thermon; ET -6C.
c.
Nelson HEC-100 or SLT-E
Pilot Light:
a.
Raychem; Included with power connection kit.
b.
Thermon; VIL-6.
c.
Nelson; LT-L or HEL-100
Pipe Adapter Kit:
a.
Raychem; Included with power connection kit.
b.
Thermon; Included with power connection kit
c.
Nelson; LT-P
SECURING TAPE
A.
B.
2.5
AMBIENT THERMOSTAT
A.
B.
C.
D.
E.
F.
2.6
Type: Fixed, non-adjustable, sodium hydroxide service set at 60 F, all other services set at 40
F.
B.
Section 40 41 13
Heat Tracing
C.
Enclosure: Glass-filled nylon, NEMA 250, Type 4X weatherproof with gasketed lid.
D.
E.
PART 3 - EXECUTION
3.1
INSTALLATION
A.
General:
1.
Install in accordance with the Manufacturers instructions and recommended practices.
2.
Ground metallic structures or materials used for support of heating cable or on which it is
installed in accordance with applicable codes.
3.
Wiring between power-connection points of heat tracing cable branch lines shall be
provided by heat tracing system supplier.
4.
Install and test prior to installation of piping insulation as specified in Section 23 07 13,
MECHANICAL INSULATION.
B.
C.
Heat Tracing Circuits: Limit individual lengths of heat tracing circuits such that maximum single
circuit capacity is 20 amps when starting the circuit at 40 F. Provide multiple 20-amp circuits as
required at individual heat tracing locations.
D.
Thermostats:
1.
Install in accordance with Manufacturers instructions and as approved by Engineer.
2.
For each group of heat traced circuit, install one ambient thermostat.
3.2
Test each circuit with 500-volt insulation tester between circuit and ground with neutrals isolated
from ground.
1.
Insulation Resistance: Minimum 1,000 megohm per 1,000 feet.
END OF SECTION
Section 40 41 13
Heat Tracing
SUMMARY
A.
Section includes:
1.
Valve and Gate Operators.
2.
Handwheel Operators.
3.
Key Operated Valves.
4.
Bench Stands.
5.
Floor Stands.
6.
Accessory Equipment and Floor Boxes
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 01 60 00 Product Requirements.
c.
Section 01 78 23 Operation and Maintenance Data.
1.2
GENERAL
A.
1.3
A.
1.4
A.
1.5
A.
Section 40 92 16
Valve and Gate Operators
e.
2.
1.6
Open/close and throttle actuators sizing calculations including factor of safety used
and final torques used for actuation selection.
f.
Refer to specific valve type for additional submittal requirements.
Quality Control Submittals:
a.
Special shipping, storage and protection, and handling instructions.
b.
Suggested spare parts list to maintain the equipment in service for a period of 5
years. Include a list of special tools required for checking, testing, parts
replacement, and maintenance with current price information.
c.
List special tools, materials, and supplies furnished with equipment for use prior to
and during startup and for future maintenance.
O&M Manuals: Content, format, and schedule for providing as specified in Section 01 78 23,
OPERATION AND MAINTENANCE DATA.
B.
1.7
QUALITY ASSURANCE
A.
Provide valve operators integral with the valve or gate, except for valve operators utilizing Twrenches or keys, and portable operators intended to operate more than 1 valve.
B.
C.
D.
E.
1.8
MAINTENANCE
A.
Extra materials:
1.
Key operated Valve Keys or Wrenches: Furnish a minimum of 4 keys with 4 foot shafts
and 3 foot pipe handles or wrenches with 4 foot shafts and 3 foot handles for operating
key operated valves.
PART 2 - PRODUCTS
2.1
GENERAL
A.
Size operator to operate valve for the full range of pressures and velocities.
B.
C.
2.2
VALVE OPERATORS
A.
Manual Operator:
1.
General:
a.
Operator force not to exceed 40 pounds under any operating condition, including
initial breakaway, and gear reduction operator when force exceeds 40 pounds.
Section 40 92 16
Valve and Gate Operators
b.
c.
d.
2.
3.
2.3
Stem Covers:
1.
Aluminum pipe; threaded cap on top; bolted aluminum flange on bottom; 1 by 12 inch
slots cut at 18 inches on center in front and back of pipe; capable of covering threaded
portion of greased stems that project above operators when gates or valves are opened
or closed.
B.
C.
D.
Position Indicators:
1.
Tail rods on hydraulic cylinders, or dial indicators with clear full-open and closed position
indicators, calibrated in number of turns or percentage of opening.
E.
F.
Operator Size: Capable of supporting weight of suspended shafting unless carried by bottom
thrust bearings; shaft guides with wall mounting brackets.
G.
Provisions for Alternate Operation: Where specified or indicated on the Drawings, position and
equip crank- or handwheel-operated geared valve operators or lifts for alternate operation with
tripod mounted portable gate operators.
Section 40 92 16
Valve and Gate Operators
H.
Operation: Counterclockwise to open with suitable and adequate stops, capable of resisting at
least twice normal operating force to prevent overrun of valve or gate in open or closed position.
I.
Open Direction Indicator: Cast arrow and legend indicating direction to rotate operator on
handwheel, chain wheel rim, crank, or other prominent place.
J.
Buried Operator Housing: Oil and watertight, specifically designed for buried service, factory
packed with suitable grease, completely enclosed space between operator housing and valve
body so that no moving parts are exposed to soil; provide operators with 2 inch square AWWA
operating nut.
K.
Worm Gear Operators: Provide gearing on worm gear operators that is self-locking with gear
ratio such that torque in excess of 160 foot-pounds will not need to be applied to operate valve
at most adverse conditions for which valve is designed.
L.
Traveling Nut Operators: Capable of requiring maximum 100 foot-pounds of torque when
operating valve under most adverse condition; limit stops on input shaft of manual operators for
fully open and closed positions; non-moving vertical axis of operating nut when opening or
closing valve.
2.4
HANDWHEEL OPERATORS
A.
B.
Mounting: Floor stand or bench stand. Unless otherwise indicated on the Drawings position
operator 36 inches (nominal) above top of walkway surface.
C.
Bearings above and below Finished Threaded Bronze Operating Nut: Ball or roller.
D.
E.
Indicator: Counterclockwise opening with arrow, and word OPEN cast on top of handwheel
indicating direction for opening.
F.
G.
Stem Travel Limiting Device: Setscrew locked stop nuts above and below lift nut.
H.
2.5
B.
Mounting: Floor and Bench Stand. Unless otherwise indicated on the Drawings, position the
operator 36-inches (nominal) above the top of the walkway surface.
C.
D.
E.
Teeth on Gears, Spur Pinions, Bevel Gears, and Bevel Pinions: Cut.
Section 40 92 16
Valve and Gate Operators
F.
G.
H.
Bearings above and below Flange on Lift Nuts: Ball or roller; capable of taking thrust developed
by opening and closing of gates under maximum operating head; with bronze sleeve bearings
and sufficient grease fittings for lubrication of moving parts, including bearings and gears.
I.
Crank Rotation Indicator: Cast arrow with word OPEN in prominent, readily visible location
indicating correct rotation of crank to open gate.
J.
Hand Cranks: 15 inch radius; requiring maximum 25 pounds pull to operate gate at maximum
operating head with:
1.
Revolving brass sleeves.
2.
Gears, spur pinions, bevel gears, and bevel pinions with cut teeth.
3.
Cast manganese bronze lift nuts.
4.
Cast iron lift parts with smooth exterior surfaces.
K.
Indicator: Dial position type mounted on gear operator; enclosed in cast-iron or aluminum
housing with clear plastic cover; marked with fully open, 3/4, 1/2, 1/4, and closed positions.
2.6
B.
2.7
B.
Floor Stand Assemblies: Heavy-duty cast iron, suitable for mounting specified operator.
1.
Nonrising, indicating type.
2.
Complete with stem, coupling, hand wheel, stem guide brackets, and yoke attachment.
3.
Stem Guide: Space such that stem UR ratio does not exceed 200.
4.
Anchor Bolts: Type 304 SST.
2.8
BENCH STANDS
A.
Section 40 92 16
Valve and Gate Operators
1.
2.
B.
2.9
Bench Stands: Handwheel operators or hand crank, geared operators conforming to handcranked geared operator requirements, except capacity to be mounted on haunch, wall bracket,
or self-contained gate yoke.
ACCESSORY EQUIPMENT
A.
B.
Extension Bonnet for Valve Operator: Complete with stem and accessories for valve and
operator.
1.
Manufacturers and Products:
a.
Metallic Valves:
1). Pratt.
2). Allis-Chalmers.
b.
Plastic Valves: ASAHI/America.
C.
D.
E.
Stems: Stainless steel; sized to match output of operator; minimum gate or valve operating
stem diameter; maximum 200 slenderness ratio.
F.
Stem Couplings: Stainless steel; internally threaded to match stem; lockable to stem by set
screw.
G.
Stem Guides: Cast iron with silicon bronze bushing; maximum 200 slenderness ratio; capable of
being mounted with a wall bracket; adjustable in 2 directions.
H.
Wall Brackets: Cast iron, capable of withstanding the output of the operator; adjustable in 2
directions.
I.
Stem Stuffing Boxes: Cast iron, with adjustable gland and packing.
J.
Section 40 92 16
Valve and Gate Operators
K.
Geared Valve Operators: Provided with cut gears, either spur or worm; sized to operate valves
at most adverse design condition; with maximum 40 pound pull at handwheel or chain wheel
rim.
L.
Geared Valve Traveling Nut Operators: Acceptable only where specified or indicated on the
Drawings.
M.
Accessory Equipment for Valves and Gates Requiring Remote Operators: Operating stems,
stem couplings, stem guides, wall brackets, and stem stuffing boxes.
PART 3 - EXECUTION
3.1
3.2
A.
Install floor boxes in concrete floor with lid flush with floor.
B.
After installation of gate and stem covers, mark stem covers at point where top of stems are at
full-open position and at closed position.
C.
D.
Install stem stuffing boxes where operating stems pass through intermediate concrete floor
slabs.
3.3
SCHEDULES
A.
B.
Handwheel operators: Provide handwheel operators for valves mounted at 6 feet or less above
floors.
C.
Chain Wheel Operators; Provide chain wheel operators for valves mounted more than 6 feet to
centerline above floors.
END OF SECTION
Section 40 92 16
Valve and Gate Operators
DIVISION 44
POLLUTION CONTROL EQUIPMENT
SUMMARY
A.
Section includes: the Work necessary to furnish and install, complete, the vertical turbine pumps
including all related equipment, material, and appurtenances.
B.
Related Sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures.
b.
Section 01 60 00 Product Requirements.
c.
Section 01 78 23 Operation and Maintenance Data.
d.
Section 01 79 00 Demonstration and Training.
e.
Section 05 50 00 Metal Fabrications.
f.
Section 09 90 00 Painting and Protective Coatings.
g.
Division 26 Electrical.
1.2
GENERAL
A.
B.
Like items of equipment provided hereinafter shall be the end products of one manufacturer to
achieve standardization of appearance, operation, maintenance, spare parts, and
manufacturers services.
C.
Unit Responsibility: The Work requires that the vertical turbine pumps, local control panel,
instruments, and components, complete with all accessories and appurtenances be the end
product of one responsible system manufacturer or responsible system supplier. Unless
otherwise indicated, the Contractor shall obtain each system from the responsible supplier of
the equipment, which supplier shall furnish all components and accessories of the system to
enhance compatibility, ease of operation and maintenance, and as necessary to place the
equipment in operation in conformance with the specified performance, features, and functions
without altering or modifying the Contractors responsibilities under the Contract Documents.
The Contractor is responsible to the Owner for providing the equipment systems as specified
herein.
D.
E.
Section 44 42 56.23
Vertical Turbine Pumps
1.3
REFERENCES
A.
1.4
Terminology pertaining to pumping unit performance and construction shall conform to the
ratings and nomenclature of the Hydraulic Institute Standards.
SUBMITTALS
A.
General: Administrative, shop drawings, samples, quality control, and contract closeout
submittals shall conform to the requirements of Section 01 33 00, SUBMITTAL PROCEDURES.
B.
1.5
QUALITY CONTROL
A.
Factory Inspections: Inspect control panels for required construction, electrical connection, and
intended function.
B.
Factory Tests and Adjustments: Test all equipment and control panels actually furnished.
Section 44 42 56.23
Vertical Turbine Pumps
C.
Factory Test Report: Include test data sheets, curve test results, performance test logs, certified
correct by a registered professional engineer.
D.
Functional Test: Perform manufacturers standard pump test on equipment. Include vibration
test, as follows:
1.
Dynamically balance rotating parts of each pump and its actual driving unit before final
assembly.
2.
Limits:
a.
Driving Unit Alone: Less than 80 percent of NEMA MG 1 limits.
b.
Complete Rotating Assembly Including Coupling, Drive Unit, and Motor: Less than
90 percent of limits established in the Hydraulic Institute Standards at all operating
speeds.
3.
Shop Performance Test:
a.
Conduct on each pump with actual motor furnished.
b.
Perform under simulated operating conditions.
c.
Test for a continuous 3-hour period without malfunction.
d.
Test Log: Record the following for each flow head condition:
1) Total head.
2) Capacity.
3) Horsepower requirements.
4) Flow measured by factory instrumentation and storage volumes.
5) Average distance from suction well water surface to pump discharge centerline
for duration of test.
6) Pump discharge pressure converted to feet of liquid pumped and corrected to
pump discharge centerline.
7) Calculated velocity head at the discharge flange.
8) Field head.
9) Driving motor voltage and amperage measured for each phase.
4.
Adjust, realign, or modify units and retest in accordance with Hydraulic Institute
Standards, if necessary.
5.
Motor Test: Provide NEMA short commercial test. Document guaranteed efficiency by
providing certified test report for test conducted on actual motor furnished.
1.6
O&M Manuals: Content, form, and schedule for providing as specified in Section 01 78 23,
OPERATION AND MAINTENANCE DATA.
B.
1.7
WARRANTY
A.
Provide warranty for a period of 12 months after the final acceptance of the equipment by the
Owner and Engineer. The warranty shall stipulate that the equipment furnished is suitable for
the purpose intended and free from defects of material and workmanship for the duration of the
warranty. In the event the equipment fails to perform as specified, the Manufacturer shall
promptly repair or replace the defective equipment without additional cost to the Owner.
B.
Spare parts identified within this specification shall not be used to address warranty repairs.
Section 44 42 56.23
Vertical Turbine Pumps
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Where a manufacturers standard equipment name and/or model number is listed, the
equipment system shall be provided as modified to conform to the performance, functions,
features, and materials of construction as specified herein.
B.
Materials, equipment, components and accessories specified in this section shall be, products
of:
1.
Fairbanks Morse.
2.
Layne/Vertil-ine.
3.
Goulds.
4.
Patterson.
5.
Peerless.
2.2
GENERAL REQUIREMENTS
A.
2.3
All pump system components shall be supplied by the pump manufacturer and including but not
limited to motor, bowl assembly, column assembly, discharge head, and all necessary
appurtenances for a complete pumping unit.
SUPPLEMENTS
A.
2.4
See supplemental data sheets to this section for additional equipment system product,
component and accessory information and requirements.
PUMPS
A.
Specific requirements for the pumps are attached to this section as supplements.
B.
The structural, mechanical, and electrical designs shown on the drawings are based on
equipment manufactured by Layne/Verti-Line. Any modifications to the mechanical, structural,
electrical, instrumentation and control, and other portions of the work that may be required to
adapt the general layout and detail shown on the Plans and the equipment actually furnished
shall be at no additional cost to the Owner. All necessary design revisions shall be made at the
Contractors sole expense. All redesign information prepared by the Contractor shall be
submitted for review prior to incorporating the redesign into the work.
C.
Rotation
1.
Pump rotation shall be counterclockwise when viewed from the driver end looking at the
pump.
D.
Impeller
1.
The waterways through the pump shall have extremely smooth contours, devoid of sharp
corners, so as to promote maximum efficiency.
2.
The impeller shall be balanced and secured to the shaft by means of stainless steel collet
for bowl shafts 1-15/16 and smaller. For bowl shafts larger than 1-15/16 impeller shall
be secured to the shaft using a combination of thrust washer, key and/or snap rings.
3.
Impeller shall be adjustable by means of top shaft-adjusting nut.
E.
Bowls
1.
Castings shall be free from blowholes, sand holes and shall be accurately machined and
fitted to close dimensions.
Section 44 42 56.23
Vertical Turbine Pumps
2.
3.
4.
Bowls with nominal diameter of 8 and above shall be flanged connected. Bowls smaller
than 8 nominal diameter may use either flanged or threaded connections.
Bowls shall be designed with smooth passages to ensure effienct operation and their
interior shall be coated with Tnemec N140 Pota-Pox Plus, or equal.
The casing shall be hydrostatically tested to 1.5 times the design head or 1.25 times the
shutoff head whichever is greater.
F.
Impeller Shaft
1.
Impeller shaft shall be of stainless steel construction conforming to ASTM A582 (416
stainless steel).
2.
The shaft shall be supported by bronze or neoprene bearings located on both sides of
each impeller.
3.
The impeller shaft coupling shall be of stainless steel construction conforming to ASTM
A582 (416 stainless steel).
G.
Wear Rings
1.
Wear rings shall be provided on both the impellers and bowls on bowls of nominal
diameter of 8 or larger so that the clearances can be maintained throughout the life of
the rings and minimize recirculation. Bowls smaller than 8 shall incorporate bowl wear
rings only.
2.
Impeller wear rings shall be of the radial-type.
3.
Wear rings shall be attached to the impellers and bowls using interface fit and Loctite.
H.
Column
1.
Column pipe in sizes 4 through 12 diameter shall be provided in interchangeable
sections not over 10 feet in length, and shall be connected with threaded, sleeve-type
couplings. Column pipe 14 diameter and larger shall be flanged and provided in
interchangeable sections not over 10 feet in length.
2.
Column joints are to be butted to insure perfect column alignment after assembly.
I.
Lineshafts
1.
Lineshafting shall be of ample size to transmit the torque and operate the pump without
distortion or vibration.
2.
Lineshaft shall be furnished in interchangeable section not over 10 feet in length.
3.
Lineshafting shall be coupled with extra-long threaded steel couplings machined from
solid steel bar.
4.
Lineshafting shall be fitted with stainless steel replaceable sleeves at each bearing and
shall conform AISI 304 material.
J.
2.5
NON-REVERSING RATCHET
A.
Pump assembly shall include a motor-mounted non-reversing ratchet to prevent pump rotation
in the reverse direction when flow is reversed through the pump.
Section 44 42 56.23
Vertical Turbine Pumps
2.6
ACCESSORIES
A.
Equipment Identification Plate: 16-gauge stainless steel with 1/4-inch die-stamped equipment
tag number securely mounted in a readily visible location.
B.
C.
Base Flange Bolts: Sized by equipment manufacturer and as specified in Division 05, METALS.
2.7
FACTORY FINISHING
A.
2.8
Prepare, prime, and finish coating and lining as shown on Drawings and in accordance with
Section 09 90 00, PAINTING AND PROTECTIVE COATINGS, System No. 2.
MOTOR REQUIREMENTS
A.
B.
2.9
General:
1.
Conform with Division 26, ELECTRICAL.
2.
Provide all necessary electrical components and wiring for a complete, functional system.
3.
Where indicated, motor starters for constant-speed, 460-volt motors shall be provided in
a separate motor control center specified in Division 26, ELECTRICAL. Provide all
necessary control functions to properly interface with this motor starter.
B.
Wiring: The Drawings and Specifications indicate the anticipated wiring for the equipment
provided under this section. If additional wiring is required, or if required wiring does not match
what is indicated, the Contractor shall make the necessary modifications to the electrical wiring
and documentation as part of the lump sum price. Wiring shall meet the requirements of
Division 26, ELECTRICAL, and NFPA 70. Insulation shall be rated 600 volts, minimum. Lowvoltage (24V) signals shall be run in twisted, shielded pair cable.
C.
Electrical Raceways: Electrical wiring shall be installed in conduit meeting the requirements of
Division 26, ELECTRICAL. Raceways shall be installed in accordance with Division 26,
ELECTRICAL, and NFPA 70.
2.10
A.
All instrumentation and control components shall be provided in accordance with the
requirements of Division 26, ELECTRICAL.
B.
Section 44 42 56.23
Vertical Turbine Pumps
C.
Soft Start Control Panel Operator Interfaces: At a minimum, provide the following functions on
the face of the panel:
1.
Hand Switches and Other Controls:
a.
(2) Pump ON/OFF/AUTO, label with equipment numbers as appropriate.
b.
(2) Emergency Stop.
c.
(2) Soft starter reset.
d.
(2) Vibration bypass switch.
e.
(2) Vibration reset.
2.
Indicators and Alarms: The following alarms shall be provided on the panel:
a.
(2) Soft starter fault.
b.
(2) Vibration warning.
c.
(2) Vibration shutdown.
d.
(2) Motor over temp.
e.
(2) Remote stop indicator.
f.
LOW wetwell level.
3.
Status: The following status shall be indicated on the face of the panels:
a.
(2) Pump ON/OFF.
b.
(2) Elapsed time meter
D.
Control Scheme:
1.
The vertical turbine pumps shall be controlled to maintain a specified liquid level in the
hatchery reservoir.
2.
Pumps shall automatically cycle on and off as necessary to maintain liquid level, as well
as to minimize the number of starts and stops for any given pump.
3.
The control panel shall accept a signal from the level indicating instrumentation and cycle
pumps on and off to maintain an operator selected level in the reservoir.
4.
SHOULD THE DEDUCTIVE ALTERNATIVE FOR RESEVOIR LEVEL INDICATION BE
SELECTED THE PUMPS WILL BE ON/OFF OPERATION ONLY. AUTOMATIC
OPERATION WILL NOT BE INCLUDED.
2.11
A.
Tools: The work includes furnishing two complete set of special tools recommended by the
manufacturer for maintenance and repair of each separate type of equipment; tools shall be
stored in tool boxes, and identified with the equipment number by means of stainless steel or
solid plastic name tags attached to the box.
B.
Spare Parts:
1.
All equipment shall be furnished with the specified manufacturers spare parts as
indicated in the individual equipment sections.
2.
Spare parts shall be tagged by project equipment number and identified as to part
number, equipment manufacturer and subassembly component (as appropriate). Spare
parts subject to deterioration such as ferrous metal items and electrical components shall
be properly protected by lubricants or desiccants and encapsulated in hermetically sealed
plastic wrapping. Spare parts with individual weights less than 50 pounds and dimensions
less than 2 feet wide, or 18 inches high, or 3 feet in length shall be stored in a wooden
box with hinged wooden cover and locking clasp. Hinges shall be strap type. The box
shall be painted and indentified with stenciled lettering stating the name of the equipment,
equipment numbers and the words spare parts. A neatly typed inventory of spare parts
shall be taped to the underside of the cover.
3.
Provide at a minimum, the following spare parts for the equipment:
a.
Complete set packing.
b.
Complete set pump bearings.
c.
Complete set gaskets and O-ring seals.
d.
Complete set of shaft sleeves.
e.
Complete set keys, dowels, pins, etc.
Section 44 42 56.23
Vertical Turbine Pumps
f.
g.
h.
i.
j.
2.12
Impeller.
Impeller shaft.
Impeller wear ring.
Head shaft.
One complete set of any special tools required to dismantle pump.
FABRICATION
A.
B.
Shop/Factory Finishing: Shop prime coatings shall conform to the requirements of Section 09
90 00, PAINTING AND PROTECTIVE COATINGS; System 1 for Columns and Bowls and
System 3 for discharge heads and motors; coordinate color with Owner.
PART 3 - EXECUTION
3.1
3.2
Coordination shall include space and structural requirements, clearances, utility connections,
signals, outputs and features required by the manufacturer including safety interlocks.
PRODUCT DELIVERY, STORAGE AND HANDLING
A.
B.
C.
Storage: Products shall be carefully stored in a manner that will prevent damage and in an area
that is protected from the elements.
D.
Protection of Equipment: Equipment shall be boxed, crated or otherwise protected from damage
and moisture during shipment, handling, and storage. Equipment shall be protected from
exposure to corrosive fumes and shall be kept thoroughly dry at all times. Pumps, motors,
drives, electrical equipment and other equipment with anti-friction or sleeve bearings shall be
stored in weathertight and heated storage facilities prior to installation. For extended storage
periods, plastic equipment wrappers shall not be used to prevent accumulation of condensate in
gears and bearings.
3.3
INSTALLATION
A.
B.
C.
Adjust pump assemblies such that the driving units are properly aligned, plumb, and level with
the driven units and all interconnecting shafts and couplings. Do not compensate for
misalignment by use of flexible couplings.
D.
E.
Anchor Bolts: Provide templates and specify bolts for furnishing by Contractor.
Section 44 42 56.23
Vertical Turbine Pumps
3.4
B.
3.5
MANUFACTURERS SERVICES
A.
A manufacturers representative for the equipment specified herein shall be present at the job
site for the minimum person-days listed for the services hereinunder, travel time excluded:
1.
Installation, Startup, and Testing Services:
a.
1 person day for installation assistance, inspection, and Certificate of Proper
Installation.
b.
1 person-day for functional and performance testing.
c.
Provide Qualifications of Manufacturers Representative.
2.
Training Services:
a.
1 person-day of prestart classroom or jobsite training of Owners personnel.
b.
Training of Owners personnel shall be at such times and at such locations as
required and approved by the Owner.
B.
3.6
MANUFACTURERS CERTIFICATES
A.
3.7
A.
The supplement listed below, following End of Section, is a part of this Specification.
1.
Vertical Turbine Pump Data Sheet.
END OF SECTION
Section 44 42 56.23
Vertical Turbine Pumps
MANUFACTURERS
SUGGESTED MODEL
Layne Verti-Line
Fairbanks-Morse
Patterson
Goulds
Peerless
16GM (1-STAGE)
16E (1-STAGE)
16 RHC
20EHXC (1-STAGE)
14HH (2-STAGE)
SERVICE CONDITIONS
Liquid Pumped:
Largest solid:
Liquid Temperature:
PERFORMANCE REQUIREMENTS
Raw Water
0.30
40-70 F
EQUIPMENT DESCRIPTION
Pump Type:
Column:
Wear Rings:
Impeller:
Bowl:
Impeller Shaft:
Lineshaft:
Lineshaft
Bearings
Lubrication:
Discharge
Head
Assembly
Vertical Turbine
12 in. dia. Max, Flanged or
Threaded
Bronze ASTM B505, C93200
MOTOR DATA
Type:
Manufacturer:
125 (max)
460
3
60
Hz
Synchronous Speed
1800
rpm
Service Factor:
1.0
Mounting Type
Enclosure Type
Material
Load Class:
Horizontal
Vertical
WP I
Cast Iron A48 Class 35B
Constant Torque
max
1.15
Adjustable Speed Drive: See Division 26, ELECTRIC. Provide Inverter Duty Rated Motors.
Windings:
One
Two
Thermal protection embedded in windings.
Motor nameplate horsepower shall not be exceeded at any operational point.
Provide
Space Heater
Oversize main terminal (conduit) box for motors
Additional Motor Requirements: See Section 26 05 15, ELECTRIC MOTORS
1 of 1
SUMMARY
A.
Section includes: Work necessary to completely furnish and install a hot water pressure washer
including the controls, hoses, boom, fittings, wand and, all related equipment, material, and
appurtenances.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures
b.
Section 01 60 00 Product Requirements
c.
Section 01 78 23 Operation and Maintenance Data
d.
Section 01 79 00 Demonstration and Training
e.
Section 05 50 00 Metal Fabrications
f.
Section 09 90 00 Painting and Protective Coatings
g.
Section 44 42 69 Hot Water Pressure Washer System
h.
Division 26 Electrical Sections
1.2
GENERAL
A.
Like items of equipment provided hereinafter shall be the end products of one manufacturer to
achieve standardization of appearance, operation, maintenance, spare parts and
manufacturers services.
B.
Unit Responsibility: The Work requires that the hot water pressure washer, hoses, remote
operation with time delay shutdown, instruments, wand, draft diverter, hose boom, detergent
metering valve, and components complete with all accessories and appurtenances be the end
product of one responsible system manufacturer or responsible system supplier. Unless
otherwise indicated, the Contractor shall obtain each system from the responsible supplier of
the equipment. The supplier shall furnish all components and accessories of the system to
enhance compatibility, ease of operation and maintenance, and as necessary to place the
equipment in operation in conformance with the specified performance, features, and functions
without altering or modifying the Contractors responsibilities under the Contract Documents.
The Contractor is responsible to the Owner for providing the equipment systems as specified
herein.
C.
D.
Section 44 42 69
Hot Water Pressure Washer System
1.3
SUBMITTALS
A.
General: Administrative, shop drawings, samples, quality control, and contract closeout
submittals shall conform to the requirements of Section 01 33 00, SUBMITTAL PROCEDURES.
B.
1.4
QUALITY CONTROL
A.
1.5
A.
O&M Manuals: Content, format and schedule for providing as specified in Section 01 78 23,
OPERATION AND MAINTENANCE DATA.
B.
1.6
WARRANTY
A.
Provide warranty for a period of 12 months after the final acceptance of the equipment by the
Owner and Engineer. The warranty shall stipulate that the equipment furnished is suitable for
the purpose intended and free from defects of material and workmanship for the duration of the
Section 44 42 69
Hot Water Pressure Washer System
warranty. In the event the equipment fails to perform as specified, the Manufacturer will
promptly repair or replace the defective equipment without additional cost to the Owner.
B.
Spare parts identified within this specification shall not be used to address warranty repairs.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Where a manufacturers standard equipment name and/or model number is listed, the
equipment system shall be provided and modified as required to conform to the performance,
functions, features, and materials of construction as specified herein.
B.
Materials, equipment, components, and accessories specified in this section shall be, products
of:
1.
Landa - Model VHG4-22024A
2.
Hotsy Model 943P
2.2
GENERAL REQUIREMENTS
A.
Safety Devices: The completed work shall include all necessary permanent safety devices, such
as machinery guards, emergency stops and similar items required by OSHA, and other federal,
state, and local health and safety regulations.
1.
Where gear drive input to output shafts connect to couplings or sprockets, the gear drive
manufacturer shall supply matching key.
B.
Anchor bolts shall be specified in Section 05 50 00, METAL FABRICATIONS. Number and size
as recommended by manufacturer.
C.
Stainless Steel: Stainless steel components shall be 304 stainless steel, or higher, as specified.
D.
2.3
SERVICE CONDITIONS
A.
The hot water pressure washer will produce four (4) gallons per minute at 2,200 pounds per
square inch with a 150F temperature rise.
B.
2.4
EQUIPMENT
A.
Pump
1.
Triplex ceramic plunger pump
B.
Water Heater
1.
1/2 - SCH.80 boiler grade coil
2.
Burner with electronic ignition
3.
Adjustable temperature control
Section 44 42 69
Hot Water Pressure Washer System
2.5
ACCESSORIES
A.
Provide stainless steel wall mounted boom capable of reaching full extents of wash bay as
shown on the drawings.
B.
C.
Provide minimum 3/8 inch 5,000 psi high pressure hose and fittings lengths as required to
connect pressure washer to lance wand and trigger gun. See drawings.
D.
2.6
ELECTRICAL COMPONENTS
A.
General:
1.
Conform with Division 26, ELECTRICAL.
2.
Provide all necessary electrical components and wiring for a complete, functional system.
3.
Where indicated, motor starters shall be provided in a separate motor control center
specified in Division 26, ELECTRICAL. Provide all necessary control functions to properly
interface with this motor starter.
B.
Wiring: The Drawings and Specifications indicate the anticipated wiring for the equipment
provided under this section. If additional wiring is required, or if required wiring does not match
what is indicated, the Contractor shall make the necessary modifications to the electrical wiring
and documentation as part of the lump sum price. Wiring shall meet the requirements of
Division 26, ELECTRICAL, and NFPA 70. Insulation shall be rated 600 volts, minimum. Lowvoltage (24V) signals shall be run in twisted, shielded pair cable.
C.
Electrical Raceways: Electrical wiring shall be installed in conduit meeting the requirements of
Division 26, ELECTRICAL. Raceways shall be installed in accordance with Division 26,
ELECTRICAL, and NFPA 70.
D.
Provide breather drain units in the bottom of all electrical enclosures to allow moisture to exit the
enclosure.
E.
Motors:
1.
Provide squirrel-cage AC induction motors meeting the requirements of Division 26,
ELECTRICAL, and as specified herein.
2.
For additional specific requirements on motors, refer to the Motor Data Sheets at the end
of the Section.
2.7
All instrumentation and control components shall be provided in accordance with the
requirements of Division 26.
B.
C.
Other Instrumentation and Controls: Provide all items not specifically called out which are
required to implement the functions described herein.
Section 44 42 69
Hot Water Pressure Washer System
2.8
Tools: The work includes one complete set of special tools recommended by the manufacturer
for maintenance and repair of each separate type of equipment; tools shall be stored in tool
boxes, and identified with the equipment number by means of stainless steel or solid plastic
name tags attached to the box.
B.
Spare Parts:
1.
All equipment shall be furnished with the specified manufacturers spare parts, as
indicated in the individual equipment sections.
2.
Spare parts shall be tagged by project equipment number and identified as to part
number, equipment manufacturer, and subassembly component (if appropriate). Spare
parts subject to deterioration such as ferrous metal items and electrical components shall
be properly protected by lubricants or desiccants and encapsulated in hermetically sealed
plastic wrapping. Spare parts with individual weights less than 50 pounds and dimensions
less than 2 feet wide, or 18 inches high, or 3 feet in length shall be stored in a wooden
box with hinged wooden cover and locking clasp. Hinges shall be strap type. The box
shall be painted and identified with stenciled lettering stating the name of the equipment,
equipment numbers, and the words "spare parts." A neatly typed inventory of spare parts
shall be taped to the underside of the cover.
3.
Provide, at a minimum, the following spare parts for the equipment:
a.
Any parts or special tools required for regular maintenance as recommended by
the manufacturer.
2.9
FABRICATION
A.
B.
Shop/Factory Finishing: Shop prime coatings shall conform to the requirements of Section 09
90 00, PAINTING AND PROTECTIVE COATINGS, System No. 2.
PART 3 - EXECUTION
3.1
GENERAL
A.
3.2
Coordination shall include space and structural requirements, clearances, utility connections,
signals, outputs and features required by the manufacturer including safety interlocks.
ASSEMBLY AND PREPARATION FOR SHIPMENT
A.
Each drive unit, including motor, shall be completely factory assembled, aligned, and securely
crated for shipment. Accessory equipment which cannot be shipped assembled to the unit, such
as shafts, baseplates, impellers, spare parts, and anchorage materials, shall be separately
crated, clearly marked as to the contents, and shipped on the same shipment as the drives.
B.
For shipment, exposed surfaces subject to rust, such as mounting flange faces, etc., shall be
covered with a rust-preventive compound such as Kendall No. 5, or equal.
3.3
B.
Section 44 42 69
Hot Water Pressure Washer System
C.
Storage: Products shall be carefully stored in a manner that will prevent damage and in an area
that is protected from the elements.
D.
3.4
3.5
Functional Testing: Prior to startup, all equipment described herein shall be inspected for proper
alignment, quite operation, proper connection, and satisfactory performance by means of a
functional test. Provide certification of test results. Tests and certification shall be as specified
in Section 01 79 00, DEMONSTRATION AND TRAINING.
INSTALLATION
A.
As shown on the Drawings. All anchors, bolts, and accessories shall be 316 stainless steel.
The manufacturer shall provide templates for anchor bolt locations.
B.
3.6
MANUFACTURERS SERVICES
A.
A manufacturers representative for the equipment specified herein shall be present at the job
site for the minimum person-days listed for the services hereinunder, travel time excluded:
1.
Installation, Startup, and Testing Services:
a.
1/2 person-day for installation assistance, inspection, and Certificate of Proper
Installation.
b.
1/2 person-day for functional and performance testing.
c.
Provide Qualifications of Manufacturers Representative.
2.
Training Services:
a.
1/2 person-day of prestart classroom or jobsite training of Owners personnel.
b.
Training of Owners personnel shall be at such times and at such locations as
required and approved by the Owner.
B.
3.7
MANUFACTURERS CERTIFICATES
A.
END OF SECTION
Section 44 42 69
Hot Water Pressure Washer System
SUMMARY
A.
Section includes: the Work necessary to completely furnish and install the intake screen
including the air backwash system, all related equipment, material, and appurtenances.
B.
Related sections:
1.
The Contract Documents are complementary; what is called for by one is as binding as if
called for by all.
2.
It is the CONTRACTORs responsibility for scheduling and coordinating the Work of
subcontractors, suppliers, and other individuals or entities performing or furnishing any of
CONTRACTORs Work.
3.
The following Sections are related to the Work described in this Section. This list of
Related Sections is provided for convenience only and is not intended to excuse or
otherwise diminish the duty of the CONTRACTOR to see that the completed Work
complies accurately with the Contract Documents.
a.
Section 01 33 00 Submittal Procedures
b.
Section 01 60 00 Product Requirements
c.
Section 01 78 23 Operation and Maintenance Data
d.
Section 01 79 00 Demonstration and Training
e.
Section 05 50 00 Metal Fabrications
f.
Section 09 90 00 Painting and Protective Coatings
g.
Division 26 Electrical Sections
1.2
GENERAL
A.
Like items of equipment provided hereinafter shall be the end products of one manufacturer to
achieve standardization of appearance, operation, maintenance, spare parts and
manufacturers services.
B.
Unit Responsibility: The Work requires that the intake screen, air backwash system, local
control panel, instruments, and components complete with all accessories and appurtenances
be the end product of one responsible system manufacturer or responsible system supplier.
Unless otherwise indicated, the Contractor shall obtain each system from the responsible
supplier of the equipment, which supplier shall furnish all components and accessories of the
system to enhance compatibility, ease of operation and maintenance, and as necessary to
place the equipment in operation in conformance with the specified performance, features, and
functions without altering or modifying the Contractors responsibilities under the Contract
Documents. The Contractor is responsible to the Owner for providing the equipment systems as
specified herein.
C.
D.
The equipment specified herein is included in the List of Proposed Manufacturers Form. Refer
to the Bid Form and the Instructions to Bidders for additional requirements.
1.3
SUBMITTALS
A.
General: Administrative, shop drawings, samples, quality control, and contract closeout
submittals shall conform to the requirements of Section 01 33 00, SUBMITTAL PROCEDURES.
Section 44 43 33.13
Intake Screen
B.
1.4
A.
The equipment manufacturer must maintain an ongoing quality assurance program, including
ISO-9000 certification.
B.
All welders must maintain certification to ASME Section IX. Copies of certifications shall be
provided upon request.
C.
The manufacturer supplying this equipment must be able to furnish proof of over 100
installations and 20 years of manufacturing equipment of similar technology.
OPERATION AND MAINTENANCE DATA
A.
O&M Manuals: Content, form and schedule for providing as specified in Section 01 78 23,
OPERATION AND MAINTENANCE DATA.
B.
1.5
1.6
WARRANTY
A.
Provide warranty for a period of 12 months after the final acceptance of the equipment by the
Owner and Engineer. The warranty shall stipulate that the equipment furnished is suitable for
the purpose intended and free from defects of material and workmanship for the duration of the
warranty. In the event the equipment fails to perform as specified, the Manufacturer will
promptly repair or replace the defective equipment without additional cost to the Owner.
Section 44 43 33.13
Intake Screen
B.
Spare parts identified within this specification shall not be used to address warranty repairs.
PART 2 - PRODUCTS
2.1
MANUFACTURERS
A.
Where a manufacturers standard equipment name and/or model number is listed, the
equipment system shall be provided and modified as required to conform to the performance,
functions, features, and materials of construction as specified herein.
B.
Materials, equipment, components, and accessories specified in this section shall be, products
of:
1.
Johnson Screen, New Brighton, MN
2.
Concord Screen, Newmarket, ON
2.2
GENERAL REQUIREMENTS
A.
Noise Level: When in operation, no piece of equipment shall exceed the OSHA noise level
requirements for a 1 hour exposure, 105 dBA.
B.
Service Factors: Service factors shall be applied in the selection and design of components
where so indicated in individual sections. When not indicated there, minimum service factors
shall be 1.25, except for gears and gear drives as specified herein.
C.
Safety Devices: The completed work shall include all necessary permanent safety devices, such
as machinery guards, emergency stops and similar items required by OSHA, and other federal,
state, and local health and safety regulations.
D.
Flanges and Pipe Threads: Comply with ANSI B 16.1, Class 125; or B 16.5, Class 150, unless
otherwise indicated. Threaded flanges and fittings shall have standard taper pipe threads
complying with ANSI/ASME B 1.20.1.
E.
Bearings:
1.
Conform to the standards of the Anti-Friction Bearing Manufacturers Association, Inc.
(AFBMA).
2.
Except where otherwise indicated, bearings of process equipment shall have a minimum
L-10 life expectancy of 100,000 hours.
F.
Anchor bolts shall be specified in Section 05 50 00, METAL FABRICATIONS. Number and size
as recommended by manufacturer.
G.
Stainless Steel: Stainless steel components shall be 304 stainless steel, or higher, as specified.
H.
2.3
Capacity:
1.
The intake assembly capacity shall be 7,500 gpm at a maximum through-slot velocity, as
a result of water withdrawal, of 0.5 feet per second. The corresponding average throughslot velocity shall be 80% - 90% of the maximum velocity. At this flow rate the pressure
Section 44 43 33.13
Intake Screen
2.
3.
drop through the clean screen surface shall be less than 0.1 psi. Pressure drop through
the entire intake assembly shall be less than 0.6 psi at the rated flow.
The total intake assembly capacity of 7,500 gpm shall be handled by one (1), intake tee
screen assembly.
Evidence of the intake assembly capacity and flow distribution shall be able to be
provided by a Computational Fluid Dynamic (CFD) analysis, supplied by the
manufacturer
B.
Strength:
1.
The intake assembly shall be designed to withstand a differential hydrostatic collapse
pressure of thirty (30) feet of water.
2.
Design stress used for determining strength of the assembly shall be no more than 90%
of the published yield strength of the material used. Strength calculations verifying
compliance with these criteria shall be provided upon request.
C.
Construction:
1.
The intake screen surface wire shall be wedgewire or v-wire mesh.
2.
The surface wire, support beam and stiffener structure shall be an all-welded matrix
designed to provide the specific strength with minimal interference with the through
screen flow pattern.
3.
End closures and tee body shall be a minimum of 0.15 inches thick. All structural butt
welds shall be full penetration fillet welds and shall be the thickness of the thinner
component. Upstream end closure shall be a conical debris deflector.
D.
E.
Materials:
1.
The main outlet flange shall mate with a twenty-four (24) inch flange with a flange pattern
equal to AWWA C-207, Table 2, Class D. Air backwash connection shall be 3 inches.
2.
The intake screen material shall be manufactured of Copper-Nickel alloy to inhibit
attachment of zebra mussels.
3.
If deductive alternate for Copper-Nickel alloy intake screen is selected the screen
shall be constructed of 304 stainless steel.
2.4
The air backwash system shall be designed to remove debris from the screen surface by
delivering a suitable volume of compressed air to the inside of the screen body. The exiting air
shall scour the screen surface to maintain adequate design flow and through slot velocity
characteristics.
B.
The air backwash system shall consist of an integrated system of a 7.5 HP(maximum)
compressor, 200 gallon receiver tank, air filter system, and 3 manual lever operated ball
valves. All components to be mounted on air receiver and completely piped and wired ready to
operate.
1.
The compressor shall be a reciprocating type, lubricated air compressor with food grade
lubricant and shall be sized to recover from each backwash in 15 minutes.
2.
Compressor assembly shall include air cooled aftercooler to reduce discharge air
temperature to a temperature accessible to the air filters. Air shall be filtered through a 3
stage filtering system that includes a filter separator, 1.0 micron coalescing filter and 0.01
Section 44 43 33.13
Intake Screen
3.
4.
5.
6.
2.5
micron coalescing filter. Filters to have auto drains and differential pressure indicators to
indicate when elements need to be changed.
The receiver shall be a 200 gallon receiver, ASME coded for 200 psig, sized for the
system piping and to displace three (3) screen volumes of air at the screen during a
backwash to provide suitable debris removal and cleaning. Two of three volumes shall be
delivered in the first second of the backwash cycle.
The receiver shall be equipped with a 4 inch isolated pressure gauge, safety valve and
automatic drain valve.
The system shall include one 3 butterfly valve rated at 200 psi with standard ANSI class
125/150 flange with a pneumatic actuator with direct mounted solenoid valves, position
indicator and position switches.
Unused discharge ports shall be fitted with a plug.
General:
1.
Conform with Division 26, ELECTRICAL.
2.
Provide all necessary electrical components and wiring for a complete, functional system.
3.
Where indicated, motor starters shall be provided in a separate motor control center
specified in Division 26, ELECTRICAL. Provide all necessary control functions to properly
interface with this motor starter.
B.
Wiring: The Drawings and Specifications indicate the anticipated wiring for the equipment
provided under this section. If additional wiring is required, or if required wiring does not match
what is indicated, the Contractor shall make the necessary modifications to the electrical wiring
and documentation as part of the lump sum price. Wiring shall meet the requirements of
Division 26, ELECTRICAL, and NFPA 70. Insulation shall be rated 600 volts, minimum. Lowvoltage (24V) signals shall be run in twisted, shielded pair cable.
C.
Electrical Raceways: Electrical wiring shall be installed in conduit meeting the requirements of
Division 26, ELECTRICAL. Raceways shall be installed in accordance with Division 26,
ELECTRICAL, and NFPA 70.
D.
Provide breather drain units in the bottom of all electrical enclosures to allow moisture to exit the
enclosure.
E.
Motors:
1.
Provide squirrel-cage AC induction motors meeting the requirements of Division 26,
ELECTRICAL, and as specified herein.
2.6
All instrumentation and control components shall be provided in accordance with the
requirements of Division 26.
B.
C.
The control system included shall allow a full week duration of programmed air backwash
cycles.
Section 44 43 33.13
Intake Screen
D.
Control Panel Operator Interfaces: At a minimum, provide the following controls and indicators
on the face of the panel:
1.
Hand Switches and pushbuttons:
a.
SYSTEM ON/OFF
E.
F.
Other Instrumentation and Controls: Provide all items not specifically called out which are
required to implement the functions described herein.
G.
Control Description
1.
In the ON mode, the compressor system shall operate with automatic start-stop control
accomplished by means of manufacturer supplied pressure switches.
2.7
Tools: The work includes one complete set of special tools recommended by the manufacturer
for maintenance and repair of each separate type of equipment; tools shall be stored in tool
boxes, and identified with the equipment number by means of stainless steel or solid plastic
name tags attached to the box.
B.
Spare Parts:
1.
All equipment shall be furnished with the specified manufacturers spare parts, as
indicated in the individual equipment sections.
2.
Spare parts shall be tagged by project equipment number and identified as to part
number, equipment manufacturer, and subassembly component (if appropriate). Spare
parts subject to deterioration such as ferrous metal items and electrical components shall
be properly protected by lubricants or desiccants and encapsulated in hermetically sealed
plastic wrapping. Spare parts with individual weights less than 50 pounds and dimensions
less than 2 feet wide, or 18 inches high, or 3 feet in length shall be stored in a wooden
box with hinged wooden cover and locking clasp. Hinges shall be strap type. The box
shall be painted and identified with stenciled lettering stating the name of the equipment,
equipment numbers, and the words "spare parts." A neatly typed inventory of spare parts
shall be taped to the underside of the cover.
2.8
FABRICATION
A.
B.
Shop/Factory Finishing: Shop prime coatings shall conform to the requirements of Section 09
90 00, PAINTING AND PROTECTIVE COATINGS, System No. 4.
PART 3 - EXECUTION
3.1
GENERAL
A.
3.2
Coordination shall include space and structural requirements, clearances, utility connections,
signals, outputs and features required by the manufacturer including safety interlocks.
PRODUCT SHIPPING, STORAGE, AND HANDLING
A.
B.
For shipment, exposed surfaces subject to rust, such as mounting flange faces, etc., shall be
covered with a rust-preventive compound such as Kendall No. 5, or equal.
Section 44 43 33.13
Intake Screen
C.
D.
Storage: Products shall be carefully stored in a manner that will prevent damage and in an area
that is protected from the elements.
E.
3.3
3.4
Prior to startup, all equipment described herein shall be inspected for proper alignment, quiet
operation, proper connection, and satisfactory performance by means of a functional test.
Provide certification of test results. Tests and certification shall be as specified in Section 01 79
00 DEMONSTRATION AND TRAINING.
INSTALLATION
A.
B.
3.5
MANUFACTURERS SERVICES
A.
A manufacturers representative for the equipment specified herein shall be present at the job
site for the minimum person-days listed for the services hereinunder, travel time excluded:
1.
Installation, Startup, and Testing Services:
a.
1 person-day for installation assistance, inspection, and Certificate of Proper
Installation.
b.
1/2 person-day for functional and performance testing.
c.
Provide Qualifications of Manufacturers Representative.
2.
Training Services:
a.
1 person-day of prestart classroom or jobsite training of Owners personnel.
b.
Training of Owners personnel shall be at such times and at such locations as
required and approved by the Owner.
B.
3.6
MANUFACTURERS CERTIFICATES
A.
END OF SECTION
Section 44 43 33.13
Intake Screen