It is a pump motor used to circulate transformer oil through the radiator. A relay QPH is provided
to ensure the proper functioning of MPH. Whenever the MPH or PH is not functioning properly
this relay QPH will deenergise and trips DJ. A switch HPH is provided to isolated the motor
MPH it has four positions.
HPH position:
0 Both MPH and QPH isolated
1 Both MPH and QPH in service
2 MPH isolated and QPH in service
3 MPH in service and QPH isolated.
QPH is provided in HT2 compartment and HPH is located in switch panel.
Silicon Rectifier Blower Motors: MVSI 1 & 2
Each rectifier block is provided with one blower which is driven by the motors MVSI 1
& 2. These motors are three phase induction motors of 2.2 KW each. These motors of rectifier
blocks are switched on and off by means of HVSI 1.& 2. The cooling of the rectifiers is
monitored by the airflow relay QVSI 1.& 2, the contact of QVSI 1.& 2 are connected in series
and lie in the energizing circuit of Q44. During normal operation this contact are closed. On
failure of blower the air flow relay QVSI 1 & 2 operates (contacts opens) will cause to open DJ.
These motors are starting along with ARNO.
HVSI positions:0 motor and relay not in service
1 motor and relay in service
2 motor isolated and relay in service
3 motor working and relay isolated
BLPV
HPV
1 Position
2 Position
3 Position
PV1 isolated
4 Position
PV2 isolated
MPV1 & MPV2 are located behind CAB1. ZPV is located in switch panel. Two types of
exhausters are provided. They are of SLM TYPE & NORTHEY TYPE. SLM type exhauster
is having an oil sump at the bottom with a dipstick for checking oil level. The oil level
should be between minimum and maximum marks. A gear driven lubricating oil pump is
provided to transfer the oil from the sump to the bearings. 4 sight glasses are provided on the
exhausters. To check the oil drops for lubricating the gears and bearings. Minimum 9-12
drop/min should pass thorough the sight glasses. A manual operating handle is also provided
on lubricating pump to check the efficiency of the pump.
In NORTHEY type exhauster there are two oil sumps. One at the bottom and other the
top for lubricating the gears & bearings. The lower sump lubricates the gears by splashing oil and
the upper lubricates the gears by splashing oil and the upper sump lubricates the bearings by
section. Both sumps are provided with dipsticks for checking the oil levels. It should between
min & max marks.
MVRH: Radiator Blower Motor
It is provided to operate the blower VRH for cooling the transformer oil in the radiator and RPS.
It is provided in HT2 compartment. C107 contactor is provided to start and stop the motor.
BLVMT is provided to start and stop the motor. When BLVMT is switched on contactor C107
closes and MVRH starts working. The working of MVRH can be checked from corridor No2. To
monitor the working of VRH, a relay QVRH is provided. A switch HVRH is provided to isolate
QVRH or MVRH whenever MVRH or QVRH is defective. It has four positions.
HVRH switch positions:
0
QVRH & MVRH not in service
1
QVRH & MVRH both in service
2
QVRH in service & MVRH not in service
3
QVRH out of service & MVRH in service
MVMT1 & MVMT2 (TRACTION MOTORS BLOWER MOTORS 1 & 2)
MVMT1 is provided to operate VMT1, which cools TM1, 2&3. MVMT2 is provided to
operate VMT2, which cools TM4, 5 and 6. MVMT1 is provided behind CAB1 & MVMT2 is
behind CAB2. Electro magnetic contactor C105 is for MVMT1, and C 106 is for MVMT2.
These contactors are remote controlled by the switch BLVMT. Relays QVMT1 & QVMT2 are
provided to check the proper functioning of MVMT1 &2. In any case if one of the MVMTs
becomes defective or sluggish in operation, these relays will de-energise and trip DJ. MVMT1 is
having an isolating switch HVMT1 and MVMT2 is having an isolating switch HVMT2. They
are located in switch panel and have 4 positions (0, 1, 2 and 3).
HVMT1 positions
0 MVMT1 and QVMT1 are isolated
1 Both MVMT1 and QVMT1 in service
2 MVMT1 is isolated and QVMT1 is in service
3 MVMT1 is in service and QVMT1 is isolated
HVMT2 positions
0 MVMT2 and QVMT2 are isolated
1 Both MVMT2 and QVMT2 in service
2 MVMT2 is isolated and QVMT2 is in service
3 MVMT2 is in service and QVMT2 is isolated
Sl
No
Auxiliary
Name
Remote
Control
Switch
Contacto
Relay
r
ARNO
BLDJ
BLRDJ
C118
Sl
No
Auxiliary
Name
Remote
Control
Switch
Conta
ctor
QCVAR
Relay
Isolating
Switch
HQCVAR
Switch
Positio
ns
Purpose
0,1
It is a single-phase
induction
motor
while starting and
after picking up
speed it works as
on 3 Induction
Generator.
It
converts
single
phase into 3 phase
and supplies 3 to
all 13 auxiliary
motors.
Switch
Isolating
Position
Switch
s
MPH
Direct
QPH
HPH
0,1,2&3
MVSL1
Direct
QVSL1
HVSL1
0,1,2&3
MVSL2
Direct
QVSL2
HVSL2
0,1,2&3
MVSI1
Direct
QVSI1
HVSI1
0,1,2&3
0,1,2&3
MVSI2
Direct
QVSI2
HVSI2
Purpose
It is a motor for
circulating oil in the
transformer through the
pump PH.
It is a motor for
smoothening
reactor
blower (VSL1) which
supplies air to cool SL
It is a motor for
smoothening
reactor
blower (VSL2) which
supplies air to cool SL2.
It is a motor for rectifier
block Cooling blower
(VSI1) which supplies
air to cool RSI1
It is a motor for Rectifier
block cooling blower
(VSI2) Which supplies
air to cool RSI block 2.
7
8
MCP1
MCP2
MCP3
10
MPV1
11
MPV2
12
MVRH
13
14
C101
C102
BLCP /
BLCPD
BLPV/
HPV
BLVMT
RGCP
HCP
C103
C121
0,1,2,3,
(1-2) (23) (1-3)
& (1,2,3)
1,2,3,4
ZPV
C111
C107
QVRH
HVRH
0,1,2&3
MVMT1
C105
QVMT1
HVMT1
0,1,2 &3
MVMT2
C 106
QVMT2
HVMT2
0,1,2&3
To Build up compressed
air pressure and to store
in main Reservoirs
MR1, MR2, MR3&4 for
pneumatic operations
and brake system.
To create vacuum & to
maintain
for
train
braking operation.
It is a motor for radiator
cooling blower (VRH)
which supplies air to
cool the Tr. oil as well as
RPS1 to RPS6
It is a motor for TM
blower to cool the
traction motors 1,2 & 3
It is a motor for TM
blower to cool TM4 ,
5&6