Beruflich Dokumente
Kultur Dokumente
E60439A
User manual
Discovering Micrologic H
Identification
Presentation
Setting procedure
Setting Micrologic 5.0 H using the dials
Setting Micrologic 6.0 H using the dials
Setting Micrologic 7.0 H using the dials
Selecting the type of neutral protection
Main menus
Metering
History, maintenance and setup
Protection
4
5
6
8
9
10
11
12
14
18
20
Overview of functions
22
Current protection
Voltage protection
Other protection
Load shedding and reconnection
Measurements
Harmonic measurements
Alarms
Optional M2C and M6C contacts
Event histories
LEDs and display screens
COM communications option
22
28
29
30
31
33
44
45
46
47
49
Setup
50
50
52
55
58
Protection settings
60
64
66
Metering
68
Current measurements
Voltage measurements
Power measurements
Energy measurements
Harmonic measurements
Frequency measurements
68
71
73
75
76
82
Maintenance
84
84
85
86
87
88
Micrologic H
60
61
62
63
Schneider Electric
Technical appendix
90
Tripping curves
Voltage measurements
Zone selective interlocking (ZSI)
Power supply
Changing the long-time rating plug
Thermal memory
Data available via the COM communications option
Threshold and time-delay settings
Other settings
Measurement setting ranges and accuracy
Power-factor sign conventions
90
92
94
95
97
98
99
101
104
105
106
Index
108
Micrologic H
Schneider Electric
Micrologic H
Schneider Electric
Discovering Micrologic H
Identification
Micrologic 5.0 H
E60231A
E71927A
t
Idmtl
4260A
N 1 2 3
100
50
0
long time
Ir
.7
.6
.5
.4
x In
Isd
Ii
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
Ii
(s)
on
I t
setting
4
3
off
6 8 10
12
15
off
2
x In
delay
test
Micrologic 5.0 H
Micrologic 6.0 H
Micrologic 6.0 H
E60233A
E71928A
E60231A
Idmtl
4260A
I t on
N 1 2 3
100
X: type of protection
c 2 for basic protection
c 5 for selective protection
c 6 for selective + ground-fault protection
c 7 for selective + earth-leakage protection
I t off
50
Ir
Isd
Ii
Ig
long time
Ir
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
instantaneous
Y: version number
Identification of the control-unit generation:
"0" signifies the first generation.
tsd
(s)
.3
.2
.1
D
C
B
A
I t
6 8 10
4
12
3
15
off
2
x In
.2
.1
0
off
delay
tg
on
setting
Ig
Ii
.4 .4 .3
(s)
F
G
H
J
Ground-fault protection
Selective protection
+ Idmtl
@ 6 Ir
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
test
.4 .4 .3
.3
.2
.1
on
I t
.2
.1
0
off
ground fault
Z: type of measurement
c A for "ammeter"
c P for "power meter"
c H for "harmonic meter"
c no indication = no measurements
Micrologic 7.0 H
Micrologic 7.0 H
E51452A
E60231A
E71926A
Ir
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
Idmtl
4260A
N 1 2 3
100
50
0
long time
Ir
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
on
setting
(A)
3
2
1
.5
I t
off
delay
(ms)
230
7
10
140
20
30
60
4
3
Isd
Ii
In
Earth-leakage protection
6 8 10
12
15
off
2
x In
test
In
Ii
(s)
Ir
Selective protection
+ Idmtl
350
800
earth leakage
Micrologic H
Schneider Electric
top fastener
terminal block for external connections
housing for battery
screw for long-time rating plug
long-time rating plug
cover opening point
protective cover
lead-seal fixture for protective cover
infrared link with communications interfaces
connection with circuit breaker
bottom fastener
E60236A
1
2
3
4
5
6
7
8
9
10
11
E60235B
Presentation
1
2
Micro
logic
5.0 P
3
9
alarm
Indications
15
16
17
time
tr
(s)
2
1
.5
8 12
16
20
24
Ir
at 6
4
5
10
11
E60238A
14
E71930A
12
13
long
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
Micrologic 5.0 H
12
18
19
20
21
22
23
17
13
14
Navigation
20
21
22
23
100
50
Adjustment dials
35
24
25
26
27
28
29
30
31
32
33
34
N 1 2 3
16
long time
Ir
.7
.6
.5
.4
24
25
x In
27
long time
Ir
24
@ 6 Ir
25
tsd
(s)
Ii
.4 .4 .3
.2
.1
.3
.2
.1
on
I t
setting
4
3
0
off
6 8 10
12
15
off
2
x In
.7
.6
.5
.4
x In
28
26
27
delay
@ 6 Ir
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
instantaneous
35
29
30
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
D
C
B
A
on
I t
off
delay
tg
F
G
H
J
Ii
(s)
setting
Ig
33
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
short time
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
26
33
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
E60240A
18
19
4260A
15
(s)
on
.2
.1
2
I t
6 8 10
12
15
off
2
x In
test
.4 .4 .3
.3
.2
.1
4
3
0
off
28
34
35
ground fault
( )
E60241B
long time
Ir
24
.7
.6
.5
.4
25
x In
@ 6 Ir
instantaneous
short time
26
27
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
(s)
31
32
2
1
.5
Ii
.4 .4 .3
.2
.1
.3
.2
.1
on
setting
I t
0
off
delay
(ms)
230
350
10
140
20
30
60
800
4
3
6 8 10
12
15
off
2
x In
test
In
(A)
33
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
28
34
35
earth leakage
Micrologic H
Schneider Electric
Setting procedure
Dials
c dials are used to set Micrologic H
protection thresholds and tripping delays for
overloads, short-circuits, ground faults and
earth leakage.
c if the set thresholds are overrun, these
protection functions systematically trip the
circuit breaker.
5.0
logic
Micro
5.0
logic
Micro
60252B
E60250B
E60251B
Discovering Micrologic H
Micro
logic
5.0
Micrologic H
Schneider Electric
E60254B
E60253B
5.0
logic
Micro
E60490B
5.0
logic
Micro
Micrologic H
5.0
logic
Micro
c if necessary, install a
lead seal to protect the
settings
c settings may be viewed
at any time using the
keypad.
Caution!
If you notice that the tab on the back of the protective
cover has been broken off, contact the Schneider
after-sales support department to replace the cover.
Schneider Electric
E60445A
E60325A
Discovering Micrologic H
In = 2000 A
long time
Ir
.7
.6
.5
.4
.8
x In
.9
.95
.98
1
Ii = 2 x 2000 = 4000 A
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ii
6 8 10
4
12
3
15
off
2
x In
setting
In = 2000 A
In =
A
2000
long time
tr
(s)
2
1
.5
12
16
20
24
tsd = 0.2 s
@ 6 Ir
short time
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
off
delay
thresholds
Ir
I2t ON curve
Ir
E51375A
curve
E51376A
time delays
I2t OFF curve
E51372A
E51373A
I2t ON
tr
Isd
tr
Isd
tsd
Ii
0
Ir: LT threshold
Isd: ST pickup
Ii: Instantaneous pickup
tsd
Ii
I
0
tr: LT tripping delay
tsd: ST tripping delay
Micrologic H
Schneider Electric
E60445A
E60329A
In = 2000 A
long time
Ir
.7
.6
.5
.4
.8
.9
.95
.98
1
x In
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
6 8 10
4
12
3
15
off
2
x In
Ii = 2 x 2000 = 4000 A
setting
Ig
D
C
B
A
In = 2000 A
In =
Ii
A
2000
Ig = 640 A
F
G
H
J
ground fault
long time
tr
(s)
2
1
.5
12
16
20
24
@ 6 Ir
tsd = 0.2 s
short time
tsd
(s)
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
tg = 0.2 s
delay
tg
(s)
.4 .4 .3
.3
.2
.1
on
.2
.1
2
I t
0
off
ground fault
thresholds
Ir
I2t ON curve
curve
Ir
curve
E51376A
time delays
I2t OFF
E51372A
E51373A
I2t ON
tr
tr
Isd
Isd
tsd
Ig
0
tr: LT tripping delay
tsd: ST tripping delay
E51419A
E51416A
E51415A
E51418A
Ii
0
Ir: LT threshold
Isd: ST pickup
Ii: Instantaneous pickup
tsd
Ii
Ig
tg
tg
0
I
Ig: ground-fault pickup
0
I
tg: ground-fault tripping delay
Micrologic H
Schneider Electric
E60445A
E60333B
Discovering Micrologic H
In = 2000 A
long time
Ir
.7
.6
.5
.4
.8
.9
.95
.98
1
x In
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ii
6 8 10
4
12
3
15
off
2
x In
Ii = 2 x 2000 = 4000 A
setting
In
(A)
2
1
.5
In = 2000 A
In =
A
2000
In = 1 A
7
10
20
30
earth leakage
long time
tr
2
1
.5
12
16
20
24
@ 6 Ir
E60153A
(s)
short time
tsd
tsd = 0.2 s
.4 .4 .3
(s)
.2
.1
.3
.2
.1
on
I t
0
off
t = 140 ms
delay
(ms)
230
350
140
60
800
earth leakage
time delays
thresholds
Ir
I2t ON curve
curve
Ir
curve
E51376A
I2t OFF
E51372A
E51373A
I2t ON
tr
Isd
tr
Isd
tsd
Ii
0
tr: LT tripping delay
tsd: ST tripping delay
E51423A
E51421A
0
Ir: LT threshold
Isd: ST pickup
Ii: Instantaneous pickup
tsd
Ii
I
In
t
0
I
In: earth-leakage pickup
t: earth-leakage tripping
delay
10
Micrologic H
Schneider Electric
E51383A
4P 4D
4P 3D
Caution!
With the 4P 3D setting, the current in the neutral must
not exceed the rated current of the circuit breaker.
11
Micrologic H
Schneider Electric
Main menus
Discovering Micrologic H
The Micrologic H control unit offers access to the main screen and three menus:
c the main screen displaying the continuous measurement of the phase currents
(I1, I2, I3) and the neutral current (IN), if it exists
c the "Metering" menu
c the "History, maintenance and setup" menu
c the "Protection" menu.
E60101A
Main screen
4260A
1 2 3
100
50
E71931B
c "Metering" menu
(A)
(V)
(kW)
(kWh)
v press the
screen
or
v press the
button to return to the previous
screen
v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
few minutes
v the LED goes OFF on exiting the menu.
Harmonic
12
Micrologic H
Schneider Electric
E71711A
v press the
screen
Event
history
Contacts
M2C / M6C
Micrologic
setup
or
v press the
button to return to the previous
screen
v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
few minutes
v the LED goes OFF on exiting the menu.
Metering
setup
Com.
setup
E71712A
c "Protection" menu
v press the
screen
Current
protection
or
v press the
button to return to the previous
screen
v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
few minutes
v the LED goes OFF on exiting the menu.
Voltage
protection
Other
protection
Load
shedding
Load
shedding
E71657A
c saving settings
When a setting is made in any of the three menus, the
screen used to save the modification(s) may be
accessed by pressing one of the three buttons
,
Do you want
to save new
settings?
or
no
yes
13
Micrologic H
Schneider Electric
Discovering Micrologic H
Metering
Press the
E71932B
(A)
(V)
(kW)
(kWh)
Current measurements
(A)
Instant.
Harmonic
Max
Demand
I1, I2, I3, IN
E71933B
Max
(A)
(V)
(kW)
(kWh)
Voltage measurements
Harmonic
(V)
Instant.
Average 3
Unbal 3
Phase sequence.
Phase
rotation
14
Micrologic H
Schneider Electric
E71934B
Power measurements
(A)
(V)
(kW)
(kWh)
(kW)
Instant.
P, Q, S,
Power
factor
Harmonic
Demand
P, Q, S
E71935B
Max
(A)
(V)
(kW)
(kWh)
Energy measurements
Harmonic
(kWh)
E total
E in
E out
Reset
Energy
15
Micrologic H
Schneider Electric
E71936B
Discovering Micrologic H
Harmonic measurements
(A)
(V)
Harmonic
(kW)
(kWh)
Waveform
Harmonic
I1, 2, 3
Waveform capture
for currents I1, I2 and I3
IN
Waveform capture
for the neutral current IN
U12, 23, 31
Fundament.
Measurement of
the fundamental of currents
I1, I2, I3 and IN
(A)
(V)
(W)
(%)
(%)
(%)
(%)
Measurement of
the fundamental of voltages
U12, U23 and U31
and V1N, V2N and V3N
Measurement of
the fundamental of active
power P, reactive power Q
and apparent power S.
THD
Total harmonic distortion
of currents I1, I2, I3 and IN
Total harmonic distortion
of voltages U12, U23 and
U31 and V1N, V2N
and V3N
thd
Total harmonic distortion
of currents I1, I2, I3 and IN
FFT
16
Micrologic H
Schneider Electric
E71937B
Frequency measurement
(V)
(kW)
(kWh)
(Hz)
Harmonic
F
(Hz)
17
Micrologic H
Schneider Electric
Discovering Micrologic H
History, maintenance
and setup
Press the
E71711A
Event
history
Contacts
M2C / M6C
Event history
Event
history
Micrologic
setup
Metering
setup
E71713A
Com.
setup
Trip
history
Alarm
history
Operation
counter
Contact
wear
Event
history
Contacts
M2C / M6C
Contacts
M2C / M6C
Alarm
type
Micrologic
setup
Metering
setup
Setup
Com.
setup
Reset
18
Micrologic H
Schneider Electric
E71714A
Event
history
Contacts
M2C / M6C
Micrologic setup
Micrologic
setup
Micrologic
setup
Language
Metering
setup
Date / time
E71715A
Com.
setup
Event
history
Contacts
M2C / M6C
Power
sign
VT ratio
System
frequency
Metering
setup
Com.
setup
E71716A
Breaker
selection
System
type
Current
demand
Power
demand
Sign
convention
Metering
setup
Contacts
M2C / M6C
Metering setup
Micrologic
setup
Event
history
Com.
setup
Micrologic
setup
Metering
setup
Com.
setup
19
Com.
parameter
Remote
settings
Remote
control
Micrologic H
Schneider Electric
Discovering Micrologic H
Protection
Press the
E71712A
Current protection
Current
protection
Current
protection
Voltage
protection
Other
protection
Load
shedding
Load
shedding
(A)
Idmtl
(A)
(A)
Ineutral (A)
I
Setting of the I
alarm
Alarm
Iunbal
(%)
I1 max
(A)
I2 max
(A)
I3 max
(A)
IN max (A)
20
Micrologic H
Schneider Electric
E71719A
Voltage protection
Current
protection
E71720A
Voltage
protection
Other
protection
E71721A
Umin
(V)
(V)
Load
shedding
Umax
Load
shedding
Uunbal (%)
Other protection
Current
protection
Other
protection
Voltage
protection
Other
protection
rPmax (W)
Load
shedding
Load
shedding
Fmin
(Hz)
Fmax
(Hz)
Phase
rotation
Current
protection
Voltage
protection
Other
protection
E71722A
Voltage
protection
Load
shedding
Load
shedding
Load
shedding
Current
protection
Load
shedding
Voltage
protection
Other
protection
Load
shedding
Load
shedding
21
Micrologic H
Schneider Electric
Overview of functions
Current protection
I2t long-time protection
The long-time protection function protects cables against overloads. This function is
based on true rms measurements.
It is possible to select either I2t long-time protection or Idmtl long-time protection.
current setting
Ir = In (*) x
tripping betweeen 1.05 and 1.20 Ir
time setting
time delay (s)
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
0 to - 30%
0 to - 20%
0 to - 20%
0.4
0.5
0.6
0.7
0.8
0.9
other ranges or disable by changing rating plug
0.95
0.98
0,5
12.5
0.7 (1)
0.7 (2)
16
400
16
11
20
500
20
13.8
24
600
24
16.6
1
25
1
0.69
2
50
2
1.38
4
100
4
2.7
8
200
8
5.5
12
300
12
8.3
22
Micrologic H
Schneider Electric
Idmtl Protection
Long-time current setting Ir and Idmtl tripping delay tr
current setting
Ir = In (*) x
tripping between 1.05 and 1.20 Ir
0.4
0.5
0.6
0.7
0.8
0.9
other ranges or disable by changing rating plug
0.95
0.98
time setting
0,5
12
16
20
24
DT
time delay (s)
SIT
time delay (s)
VIT
time delay (s)
EIT
time delay (s)
HVF
time delay (s)
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir
0 to - 20%
0 to - 20%
0 to - 20%
0 to - 20%
0.53
0.53
0.53
0.53
1
1
1
1
2
2
2
2
4
4
4
4
8
8
8
8
12
12
12
12
16
16
16
16
20
20
20
20
24
24
24
24
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir
0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%
1.9
0.5
0.7 (1)
0.7 (2)
3.8
1
0.88
0.8
7.6
2
1.77
1.43
15.2
4
3.54
2.86
30.4
8
7.08
5.73
45.5
12
10.6
8.59
60.7
16
14.16
11.46
75.8
20
17.7
14.33
91
24
21.2
17.19
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir
0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%
3.6
0.5
0.7 (1)
0.7 (2)
7.2
1
0.81
0.75
14.4
2
1.63
1.14
28.8
4
3.26
2.28
57.7
8
6.52
4.57
86.5
12
9.8
6.86
115.4
16
13.1
9.13
144.2
20
16.34
11.42
173.1
24
19.61
13.70
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir
0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%
12.5
0.7 (1)
0.7 (2)
0.7 (2)
25
1
0.69
0.7 (1)
50
2
1.38
0.7 (1)
100
4
2.7
1.41
200
8
5.5
2.82
300
12
8.3
4.24
400
16
11
5.45
500
20
13.8
7.06
600
24
16.6
8.48
tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir
0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%
164.5
0.7 (1)
0.7 (2)
0.7 (2)
329
1
0.7 (1)
0.7 (2)
658
2
1.1 (1)
0.7 (1)
1316
4
1.42
0.7 (1)
2632
8
3.85
1.02
3950
12
5.78
1.53
5265
16
7.71
2.04
6581
20
9.64
2.56
7900
24
11.57
3.07
23
Micrologic H
Schneider Electric
Overview of functions
Current protection
Short-time and instantaneous
protection
Short-time protection
c the short-time protection function protects the distribution system against
impedant short-circuits
c the short-time tripping delay and the I2t ON and I2t OFF options can be used to
ensure discrimination with a downstream circuit breaker
c this function carries out true rms measurements.
c use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve
v I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 Ir. Above 10 Ir, the time curve is constant.
2
0.1
0.1
80
140
2.5
0.2
0.2
140
200
3
0.3
0.3
230
320
4
0.4
0.4
350
500
10
If the "without long-time protection" plug is used and the long-time protection
function is disabled, the short-time pickup Isd is automatically multiplied by In
instead of Ir as is the standard case.
Instantaneous protection
c the instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping delay
for instantaneous protection is not adjustable. The tripping order is sent to the
circuit breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
c this function carries out true rms measurements.
Instantaneous pickup Ii
10
12
15
OFF
24
Micrologic H
Schneider Electric
Neutral protection
Setting
OFF
Type of neutral
N/2
1.6xN
Description
No neutral protection
Setting
OFF
Type of neutral
No neutral protection
Half neutral protection
25
Micrologic H
N/2
Description
The distribution system does not require protection of the
neutral conductor.
The cross-sectional area of the neutral conductor is half that
of the phase conductors.
c the long-time current setting Ir for the neutral is equal to
half the setting value
c the short-time pickup Isd for the neutral is equal to half
the setting value
c the instantaneous pickup Ii for the neutral is equal to the
setting value
The cross-sectional area of the neutral conductor is equal
to that of the phase conductors.
c the long-time current setting Ir for the neutral is equal to
the setting value
c the short-time pickup Isd for the neutral is equal to the
setting value
c the instantaneous pickup Ii for the neutral is equal to
the setting value.
Schneider Electric
Overview of functions
Current protection
Ground-fault and earth-leakage
protection
Type
Description
Residual
6.0 H
A
0.3
0.2
500 A
0
20
80
B
0.3
0.3
640 A
0.1
0.1
80
140
C
0.4
0.4
720 A
0.2
0.2
140
200
D
0.5
0.5
800 A
0.3
0.3
230
320
E
0.6
0.6
880 A
0.4
0.4
350
500
F
0.7
0.7
960 A
G
0.8
0.8
1040 A
H
0.9
0.9
1120 A
J
1
1
1200 A
7.0 H
In accuracy 0 to - 20 %
0.5
60
140
140
200
230
320
350
500
800
1000
26
Micrologic H
10
20
30
Schneider Electric
3
1
4
I t Alarm, I unbal,
I max
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
c for protection tripped by a maximum value, it is possible to set:
v a pickup threshold (1) that activates an alarm, a contact and/or tripping
v a pickup time delay (2) that steps in when the pickup threshold (1) is reached
v a dropout threshold (3) corresponding to deactivation of the alarm and/or contact
v a dropout time delay (4) that steps in when the dropout threshold (3) is reached
c the dropout threshold is always less than or equal to the pickup threshold.
I t Alarm
c the alarm function is tripped by the rms value of an earth-leakage current
c this alarm signals an earth-leakage current under the pickup value and does not
produce circuit-breaker tripping.
E71749A
I avg
I1
I2
I3
c from:
v I avg is the average value of the rms currents of the
three phases
I1 + I2 + I3
I avg =
3
v E max is the maximum difference between the
current of each phase and I avg
c Micrologic H uses the two values above to calculate
the current unbalance:
E max
I unbal =
I avg
27
Micrologic H
Schneider Electric
Overview of functions
Voltage protection
Minimum voltage, maximum voltage,
voltage unbalance
Operating principle
protection tripped
by a maximum value
E71741A
E60489A
protection tripped
by a minimum value
t
U min 0
U max
U unbal.
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
c for protection tripped by a minimum or maximum value, it is possible to set:
v a pickup threshold (1) that activates an alarm, a contact and/or tripping
v a pickup time delay (2) that steps in when the pickup threshold (1) is reached
v a dropout threshold (3) corresponding to deactivation of the alarm and/or contact
v a dropout time delay (4) that steps in when the dropout threshold (3) is reached
c for protection tripped by a minimum value, the dropout threshold is always greater
than or equal to the pickup threshold
c for protection tripped by a maximum value, the dropout threshold is always less
than or equal to the pickup threshold
c if both the minimum and maximum protection functions are activated at the same
time, the minimum threshold is automatically limited to the value of the maximum
and vice versa.
E71742A
U avg
U12
U23
U31
28
Micrologic H
c from:
v U avg is the average value of the rms voltages of the
three phases
U12 + U23 + U31
U avg =
3
v E max: is the maximum difference between the
voltage of each phase and U avg
c Micrologic H uses the two values above to calculate
the voltage unbalance:
E max
U unbal =
U avg
Schneider Electric
Other protection
Reverse power, min. frequency,
max. frequency, phase rotation
E60487A
protection tripped
by a minimum value
protection tripped
by a maximum value
E60486A
Operating principle
3
3
4
4
F min 0
F max
rP max
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
c for protection tripped by a minimum or maximum value, it is possible to set:
v a pickup threshold (1) that activates an alarm, a contact and/or tripping
v a pickup time delay (2) that steps in when the pickup threshold (1) is reached
v a dropout threshold (3) corresponding to deactivation of the alarm and/or contact
v a dropout time delay (4) that steps in when the dropout threshold (3) is reached
c for protection tripped by a minimum value, the dropout threshold is always greater
than or equal to the pickup threshold
c for protection tripped by a maximum value, the dropout threshold is always less
than or equal to the pickup threshold
c if both the minimum and maximum protection functions are activated at the same
time, the minimum threshold is automatically limited to the value of the maximum
and vice versa.
Phase-rotation alarm
This alarm is activated if two of the three phases are inverted.
Note:
The alarm is activated following a fixed 300-millisecond time delay. If one of the phases is
absent, the alarm will not operate. If the 400 Hz frequency is set, the alarm cannot be
activated.
29
Micrologic H
Schneider Electric
Overview of functions
Load shedding
and reconnection
E71754A
The pickup curve for load shedding and reconnection depending on current is
parallel to the LT I2t and Idmtl curves. If a "without long-time protection" rating plug
is installed, the load shedding/reconnection function based on current cannot be
activated.
c I2t protection: the neutral is taken into account
c Idmtl: the neutral is not taken into account.
This function does not trip the circuit breaker, but can be used to set off an alarm
linked to an M2C or M6C contact (disconnection and reconnection of non-priority
loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
t
Long-time
protection
curve
3
1
4
2
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
E60249B
Load shedding and reconnection depending on power calculates the total active
power on the three phases. This function does not trip the circuit breaker, but can
be used to set off an alarm linked to an M2C or M6C contact (disconnection and
reconnection of non-priority loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
t
3
1
4
2
1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.
30
Micrologic H
Schneider Electric
Measurements
Current and voltage
Instantaneous current
Demand current
c display of the demand current on phases I1, I 2, I 3 and the neutral IN
(depending on the type of distribution system)
c selection of the demand calculation method
c display of the interval over which the value is calculated
c the maximum demand values are displayed and stored in memory
c the stored maximums can be reset at any time.
Note:
The calculation method, the type of calculation window (fixed or sliding) and its duration
may be set in the "Metering setup" menu under "History, maintenance and setup".
Average voltage
Average Uavg of the instantaneous voltages between phases U12, U23 and U31.
Phase rotation
Displays the phase sequence.
Voltage unbalance
Display of the unbalance Uunbal between the three phase-to-phase voltages,
displayed as a percentage.
E71742A
U
E max
U avg
c from:
v U avg is the average value of the rms voltages of the
three phases
U avg =
U12
U23
U31
31
Micrologic H
Schneider Electric
Overview of functions
Measurements
Power, energy and frequency
Demand power
c display of the demand values for the active power P, reactive power Q and
apparent power S
c selection of the demand calculation method
c display of the interval over which the value is calculated
c the maximum demand values are displayed and stored in memory
c the stored maximums can be reset at at any time.
Note:
c the calculation method, the type of calculation window (fixed or sliding) and its duration may
be set in the "Metering setup" menu under "History, maintenance and setup".
c the synchronisation function (Synchro.Com) is available only with the COM communication
option; with this function, the demand power is determined on the basis of a signal
synchronised by the communication module.
c these settings apply to all demand powers (active power P, reactive power Q and apparent
power S). If the settings are modified, the demand values are systematically recalculated.
Energy
Micrologic H offers a number of different measurements:
c total energy:
v total active energy E.P in kWh
v total reactive energy E.Q in kvarh
v total apparent energy E.S in kVAh
c energy consumed (Energy in), positively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
c energy supplied (Energy out), negatively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
c energy values can be reset.
Note:
c the Energy in and Energy out values are incremented according to the power sign set
in the "Metering setup" menu under "History, maintenance and setup".
c as standard, the total calculated energy values are "absolute total values".
They represent the sum of the energy in and out values:
v EP = EP in + EP out
v EQ = EQ in + EQ out
c as an option (access exclusively via the COM communications option), energy can be
calculated algebraically:
v EP = EP in - EP out
v EQ = EQ in - EQ out
These values are called "signed" energies.
Frequency
The frequency of the distribution system is displayed in Hz.
32
Micrologic H
Schneider Electric
Harmonic measurements
Origin and effects
Definition of harmonics
A periodic signal is a combination of:
v the original sinusoidal signal at the fundamental frequency
v other sinusoidal signals (the harmonics) with frequencies that are whole-number
multiples of the fundamental frequency
v a DC component, where applicable.
Any periodic signal can therefore be represented as the sum of a number of terms:
y(t) = Yo + Yn r sin(nt - n)
E89243B
n=1
I peak
Total
I rms
Fundamental
50 Hz
I1
Harmonic
3 (150 Hz)
I3
Harmonic
5 (250 Hz)
I5
Harmonic
7 (350 Hz)
Harmonic
9 (450 Hz)
I7
I9
where:
c Yo is the value of the DC component (generally equal to zero and considered as
such hereinafter)
c Yn is the rms value of the nth harmonic
c is the angular frequency of the fundamental
c n is the phase displacement of the harmonic component at t = 0.
A harmonic of order n, referred to as the nth harmonic, is the sinusoidal
component of a signal with a frequency that is n times higher than the fundamental
frequency.
For example, the current and voltage waveforms distributed on the European
electrical power grid have the following characteristics:
c the fundamental frequency is 50 hertz (Hz)
c the 2nd harmonic has a frequency of 100 Hz
c the 3rd harmonic has a frequency of 150 Hz
c the 4th harmonic has a frequency of 200 Hz
c
A distorted waveform is the result of superimposing the various harmonics on the
fundamental.
The figure opposite shows a current distorted by harmonics.
33
Micrologic H
Schneider Electric
E89247B
Overview of functions
Standby generator
set
Ina
Rectifiers,
Arc furnaces,
Welding machines
Inb
Variable-speed
drives
Ind
Fluorescent or
discharge lamps
Power-factor
correction
HV/LV
Harmonic measurements
Origin and effects
Origin of harmonics
Harmonics are caused by non-linear loads.
A load is said to be non-linear when the current that it draws does not have the
same waveform as the voltage. Typical examples of non-linear loads are those
using power electronics. Such loads are increasingly numerous and their share in
overall electrical consumption is growing.
A
In and
distorted
voltage
Harmonic disturbances
transmitted to distribution
system and other users
Ine
Linear loads
(do not cause
harmonics)
Examples are:
c industrial equipment including welding machines, arc furnaces, induction
furnaces, rectifiers, etc.
c variable speed drives for asynchronous or DC motors
c office equipment including computers, photocopy machines, fax machines, etc.
c household equipment including televisions, microwave ovens, neon lighting,
UPSs, etc.
Non-linear phenomena may also be caused by the saturation of transformers and
other equipment.
Effects of harmonics
The flow of harmonics in distribution systems can cause serious problems:
c increased currents flowing in the system and overloads
c additional losses and premature ageing of equipment
c disturbances to loads due to voltage harmonics
c disturbances in communication networks.
The above effects can also have major financial impact due to:
c the cost of equipment (premature replacement, oversizing)
c increased power losses and the need to subscribe to higher power levels
c losses in productivity (unnecessary tripping of protection devices).
34
Micrologic H
Schneider Electric
LV
6
5
3.5
3
2
1,5
1.5
1.5
MV
6
5
3.5
3
2
1.5
1
1
EHV
2
2
1.5
1.5
1
1
0.7
0.7
LV
5
1.5
0.3
0.2
0.2
MV
2.5
1.5
0.3
0.2
0.2
Even harmonics
EHV
1.5
1
0,3
0.2
0.2
Order n
2
4
6
8
10
12
>12
LV
2
1
0.5
0.5
0.5
0.2
0.2
MV
1.5
1
0.5
0.2
0.2
0.2
0.2
EHV
1.5
1
0.5
0.2
0.2
0.2
0.2
Note:
The individual harmonic content of a harmonic of order n is defined as the percentage of
its rms value with respect to the rms value of the fundamental. This value is displayed on
the graphic screen of the Micrologic H.
35
Micrologic H
Schneider Electric
Overview of functions
Harmonic measurements
Quality indicators
Micrologic H control units can quantify and evaluate the harmonic distortion of
current and voltage waves using the quality indicators listed below:
c measurement of the fundamental signal
c phase displacement of the fundamental signals
c harmonic distortion THD and thd
c cos
c power factor
c K factor
c distortion power
c distortion factor
c crest factor
c amplitude spectrum of even and odd harmonics up to order 31
c displacement spectrum with respect to V1N of even and odd harmonics up to
order 31.
These indicators are the indispensable tools used to determine any required
corrective action.
Quality
indicator
measurement of
the fundamental
phase displacement of
the fundamental
harmonic distortion
THD and thd
cos
power factor
K factor
distortion power
distortion factor
crest factor
amplitude spectrum of
odd harmonics up to order 31
amplitude spectrum of
even harmonics up to order 31
displacement spectrum
with respect to V1N of
even and odd harmonics
up to order 31
36
Micrologic H
On the Micrologic H
screen
Via the
communication
module
c
c
-
c
c
c
c
c
c
c
Schneider Electric
Fundamental
Micrologic H control units can determine the value of the fundamental signals for:
c currents: I1, I2, I3 and IN (in amperes)
c voltages:
v phase-to-neutral V1N, V2N, V3N (in volts)
v phase-to-phase U12, U23, U31 (in volts)
c power:
v active P (kW)
v reactive Q (kVAR)
v apparent S (kVA).
Irms =
n=1 n
c the rms voltage is the square root of the sum of the squares of the rms current
values for each harmonic from the fundamental to an infinite order.
Urms =
n=1
I
THD(I) =
n=2 n
Ifund
THD(I) =
( )Irms
Ifund
Note:
v Ifund is the fundamental current.
v Irms is the rms current.
37
Micrologic H
Schneider Electric
Overview of functions
Harmonic measurements
Quality indicators
n=2
U
THD(U) =
Ufund
Note:
Ufund is the fundamental voltage.
38
Micrologic H
Schneider Electric
I
thd(I) =
n=2 n
Irms
Note:
Irms is the rms current.
c Micrologic H control units measure the thd(I) for currents I1, I2, I3 and IN, taking
into account harmonic orders up to 31.
Defined by standard IEC 61000-2-2, total harmonic distortion thd(I) is a single
value that expresses the distortion of the current flowing at a given point in a
distribution system.
thd(U) =
n=2
Urms
Note:
Urms is the rms voltage.
39
Micrologic H
Schneider Electric
Overview of functions
Harmonic measurements
Quality indicators
Cos
Cos is the ratio between the active power Pfund and the apparent power Sfund of
the fundamental (1).
cos =
Pfund
Sfund
Note:
v Pfund is the active power of the fundamental.
v Sfund is the apparent power of the fundamental.
Power factor PF
The power factor is the ratio between the active power P and the apparent power S.
P
S
PF =
Note:
v P is the active power.
v S is the apparent power.
v the power factor must not be confused with the cos . The power factor is equal to the
cos only when the signal is perfectly sinusoidal (no harmonics).
c if the measured power factor is not equal to the cos (the power factor is lower),
that may be an initial indication of harmonic disturbances in an installation.
c the power factor PF is the means to evaluate the oversizing required for the
power sources in an installation.
c there is a relation between the power factor and the total harmonic distortion of
current THD(I). When the voltage signal is (virtually) sinusoidal, the power factor
may be roughly calculated using the equation below:
cos
PF z
1 + THD(I)
E89246B
When plotted, the above equation produces the graph below showing the PF to
cos ratio, depending on the THD(I)
PF/cos
1,2
1
0,8
0,6
0,4
0,2
40
50
Micrologic H
100
150
THD(I) (%)
Schneider Electric
K factor
The K factor is a quality indicator that indicates high-order harmonics.
n
n=2
K factor =
Irms
Note:
I is the amplitude of the current.
Distortion power
When there are harmonics, the relation S2 = P2 + Q2 is no longer valid.
The distortion power D is defined by the equation below:
D=
S 2 - P 2 - Q2
Distortion factor
The distortion factor is the relation between the power factor and the cos .
Crest factor
The crest factor is the relation between the peak value of the current or voltage and
the corresponding rms value.
Crest factor =
Ipeak
Irms
or crest factor =
Upeak
Urms
Note:
v Irms is the rms current.
v Urms is the rms voltage.
c possible values:
v for a sinusoidal signal, the crest factor is equal to r
v for a non-sinusoidal signal, the crest factor may be less than or greater than r.
c the crest factor is used to characterise the capacity of a source (UPS or
generator) to supply high instantaneous currents. In particular, it draws attention to
the presence of exceptional peak values with respect to the rms value.
Computer equipment, for example, draws highly distorted current with a crest factor
that can reach 3 or even 5.
c typical crest factors for the currents drawn by non-linear loads are much higher
than r. They are often equal to 1.5 or 2 and can reach 5 in critical cases.
c a very high crest factor means that there can be high temporary overcurrents,
which, when detected by the protective devices, may result in nuisance tripping.
41
Micrologic H
Schneider Electric
Overview of functions
Harmonic measurements
Quality indicators
The communication module can be used to FFT amplitude spectrum of odd harmonic
determine for each harmonic order up to 31: orders from 3 up to 31
Each type of distorting device has its own harmonic-current "fingerprint", with
c the amplitude spectrum
c the displacement spectrum with respect to different amplitudes and displacements.
These values, in particular the amplitude for each harmonic order, are essential for
the phase-to-neutral voltage V1N.
E89245A
H%
s(t)
1
100
33
20
0
6 h
c the Micrologic H control unit indicates the FFT amplitude spectrum and the
individual distortion level for harmonic orders from 3 to 31 for:
v each current I1, I2, I3 and IN
v each phase-to-phase voltage U12, U23 and U31.
c the Micrologic H control unit also indicates for each current or voltage the
corresponding level of total harmonic distortion THD (thd for Neutral current).
42
Micrologic H
Schneider Electric
Micrologic H control units can capture and store current and voltage waveforms
using digital sampling techniques similar to those used in oscilloscopes.
Waveform capture is the means to detect weak points in the system and the
equipment. Using the information available in the captured waveform, it is possible
to determine the level of harmonics as well as the direction and amplitude of the
flow of harmonic power.
c users of Micrologic H control units can record manually via the keypad the
following waveforms:
v the four currents I1, I2, I3 and IN
v the three phase-to-neutral voltages V1N, V2N and V3N.
c waveforms may be displayed on the graphic screen of Micrologic H control units.
The recording takes place over one cycle with a measurement range of 0 to 1.5 In
for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.
43
Micrologic H
Schneider Electric
Overview of functions
Alarms
E71744B
T1
Dropout
T2
E71745B
Other alarms
T2
I t Alarm
II unbal
I 1 max
I 2 max
I 3 max
N max
U min
U max
U unbal
Other protection
Trip + Alarm
c delayed alarms are activated when the pickup and dropout thresholds are
overrun and the corresponding time delays have expired.
Voltage protection
T1
Alarm
c
c
c
Current protection
Pickup /
Dropout
Off
Ir
Isd / li
It
rP max
F min
F max
Phase rotation
Shedding/reconnection
current I
power P
Off
Alarm
Trip + Alarm
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
c
Off
Alarm
Trip + Alarm
c
c
c
c
c
c
c
c
c
Off
Alarm
Trip + Alarm
c
c
c
c
c
c
c
c
c
c
c
Off
On
c
c
c
c
c history logging
v Alarm mode: as soon as a given protection threshold is overrun, an alarm is
recorded in the "Alarm history"
v Trip mode: as soon as a given protection threshold is overrun, the circuit breaker
trips and the fault is recorded in the "Trip history".
c the "Protection setup" menu under "History, maintenance and setup" is used to
enable or disable the Trip mode that is displayed in the protection-setting screens.
On leaving the factory, the protection functions are set to Alarm mode.
c the "M2C / M6C contacts" menu under "History, maintenance and setup" is used
to link an M2C or M6C contact to an alarm. M2C and M6C contacts may not be
used together. They require a 24 V external power supply.
c the COM communications module can be used to transmit alarms to a
supervisor.
44
Micrologic H
Schneider Electric
c current protection:
c voltage protection:
c other protection:
v Ir
v U min
v F min
v U max
v F max
v Isd
v Ii
v U unbal.
v rP max
vIt
v phase rotation.
v I t Alarm
v I unbal
v I 1 max
v I 2 max
v I 3 max
v I N max.
c load shedding and reconnection:
v current I
v power P.
c latching settings:
v non-latching contact: the contact remains activated as long as the fault that
caused the alarm has not been cleared
v latching contact: the contact remains activated until it is reset ("Reset menu")
v time-delay contact: the contact remains activated for the duration of an adjustable
time delay or until it is reset ("Reset menu").
v locked to 1: the contact is forced to 1 for an automation test
v locked to 0: the contact is forced to 0 for an automation test.
Caution!
The M2C and M6C contacts require an
auxiliary power supply. See the "Power
supply" section in the technical appendix.
484
474
E60492A
S1 S2
E60494B
471
T1 tr delay
25
23
21
19
17
11
T2 = 1 sec
t
Ir LED
Press
Internal alarm
S1
S2
S3
24V 0V
S4
Non-latching contact
Time-delay
contact
Latching
contact
Com
Q1 Q2 Q3
S5
S6
delay 1 to 360 s
E71914A
Isd, Ii or Ig pickup
tsd or tg delay
Isd, Ii or Ig LED
Press
Internal alarm
Non-latching contact
Time-delay
contact
Latching
contact
delay 1 to 360 s
24
22
20
18
16
14
12
10
E60491C
Pickup
Dropout
Internal alarm
Non-latching contact
Time-delay
contact
Latching
contact
45
Micrologic H
delay 1 to 360 s
Schneider Electric
Overview of functions
Event histories
Trip history
c the trip history is the means to display at any time the parameters measured
during the last ten trips.
c for each trip, the following parameters are recorded:
v tripping cause
v trip threshold
v interrupted currents in amperes (only if an external power supply is present) for Ir,
Isd/Ii, Ig or In trips
v date
v time (hours, minutes and seconds).
Alarm history
c the alarm history is the means to display at any time the parameters measured
during the last ten alarms.
c for each alarm, the following parameters are recorded:
v alarm cause
v alarm threshold
v date
v time (hours, minutes and seconds).
Operation counter
This function is available only via the COM communications option.
c Micrologic H:
v stores and displays the total number of operations (incremented each time the
circuit breaker opens) since the initial installation of the circuit breaker
v stores and displays the total number of operations since the last reset.
46
Micrologic H
Schneider Electric
Overload bargraph on
the main screen
Alarm
E89205A
E60444A
LED indicator
Micrologic 5.0 H
4260A
N 1 2 3
off
100
50
Fault-trip indications
c control-unit status
The circuit breaker has tripped.
The control unit may or may not have an external power supply.
The voltage measurement inputs may be connected upstream or downstream.
Micrologic 5.0 H
Caution!
The battery maintains the trip indications.
If no indications are displayed, check the
battery.
Micrologic 5.0 H
Trip
22/11/1999
02:04:04
Umin
100V
Reset
by test/reset
button
47
Micrologic H
Schneider Electric
Overview of functions
c fault-trip LEDs
c the LEDs indicate the type of fault that tripped the circuit breaker
c the LEDs are located in the upper part of the front panel (red Ir, Isd, Ii, Ig, I2n and
Ap LEDs)
c when activated, a LED remains ON until it is locally reset.
Micrologic 5.0 H
c Ig, In LED
c Ap LED
Micrologic 5.0 H
E89211A
E89210A
Micrologic 5.0 H
c Isd, Ii LED
E89209A
E89208A
c Ir LED
Micrologic 5.0 H
E60485A
48
Micrologic H
Schneider Electric
E89212B
Communication options
Chassis
COM module on
chassis (optional)
Digipact and ModBus are the indispensable elements when integrating Micrologic
H in the Digivision and SMS Powerlogic installation-management systems which
communicate via the BatiBus and ModBus protocols.
External gateways are available for communication over other networks, including
ProfiBus, Ethernet, etc.
The communications option makes possible the following remote functions:
c device identification:
v address
v device type
v control-unit type
v type of long-time rating plug
Circuit breaker
(Infra Red)
c settings:
v reading of the dial settings
v fine adjustments within the range determined by the dial
v protection and alarm settings
v setup of the M2C / M6C contacts.
Micrologic H
control unit
c measurement values:
v currents
v voltages, frequencies, power, etc.
c fault values:
v fault type
v interrupted current.
c histories and logs:
v trip history
v alarm history
v event history.
c indicators:
v contact wear, counters, etc.
v maintenance register.
49
Micrologic H
Schneider Electric
Setup
Select an alarm
S2
S1
S2
then
Ir
then
Select an alarm.
Confirm.
Contacts
M2C / M6C
S1
S2
then
Select a contact.
50
Micrologic H
S2
E71604A
Setup
M2C / M6C
E71603A
Setup
S2
Ir
Select a contact.
E60226A
Alarm
type
E60146A
Note:
An alarm may be selected if the "Alarm" or "Trip + Alarm" mode was selected during setup of
the given protection function, in the "Protection" menu.
E71601A
Contacts
M2C / M6C
Alarm
type
S2
Mode
Mode
latching
contact
latching
contact
then
Select a latching mode:
c non-latching
c latching
c time-delay
c locked to 1
c locked to 0.
Confirm.
Schneider Electric
S2
E71607A
S2
E71606A
E71605A
S2
Mode
Mode
Mode
time delay
time delay
time delay
Delay
Delay
Delay
360s
350s
350s
then
Select the time delay.
Confirm.
M2C / M6C
Reset
E60389A
M2C / M6C
Contacts
Adjust.
M2C / M6C
S1 0
S2 0
S1 1
S2 1
Reset (- / +)
Reset (- / +)
then
51
Micrologic H
Schneider Electric
Setup
Language
E71938B
Language
Micrologic
setup
Language
Deutsch
English UK
English US
Espanol
English UK
Franais
Espanol
Italiano
Franais
Select.
Confirm.
To return to English
1. Return to the main
screen by pressing any
of the three buttons
Micrologic
setup
Date
E71612B
Date
E71611B
c enter the date and time for time-stamping purposes in the trip and alarm
histories.
E71610B
Date / time
Date
01 / 01 / 2000
01 / 01 / 2000
01 / 01 / 2000
Time
Time
Time
18 : 30 : 03
18 : 30 : 03
18 : 30 : 03
then
Select the date.
then
Enter the day.
then
Enter the month.
52
Micrologic H
Schneider Electric
Date
E71614B
E71613B
Date
01 / 01 / 2000
01 / 01 / 2000
Time
Time
18 : 30 : 03
18 : 30 : 03
then
then
E71617C
Breaker
selection
Breaker
selection
Standard
Standard
Standard
UL
Circuit breaker
IEC
Circuit breaker
IEC
Circuit breaker
Masterpact
Masterpact
Masterpact
type
NT08N
type
NT H1
type
NT H1
03E7
03E7
03E7
H Logicxxxxxx
H Logicxxxxxx
H Logicxxxxxx
then
then
Breaker
selection
then
Select the circuit breaker.
E71619C
E71618C
Breaker
selection
E71616C
Circuit-breaker selection
E71615C
Micrologic
setup
Breaker
selection
Breaker
selection
E71620BC
Breaker
selection
Standard
Standard
Standard
IEC
Circuit breaker
IEC
Circuit breaker
IEC
Circuit breaker
Compact NS
Compact NS
Compact NS
type
630b
type
630b
type
800
03E7
03E7
03E7
H Logicxxxxxx
H Logicxxxxxx
H Logicxxxxxx
then
Choose and confirm.
53
Micrologic H
then
Select the type.
then
Choose and confirm.
Schneider Electric
Power
sign
Select.
Power
sign
P+
P-
P+
Confirm.
Choose.
VT ratio
E71625A
Micrologic
setup
VT ratio
Power
sign
Primary
If the supply voltage for the control unit
exceeds 690 V, an external voltage
transformer must be installed.
VT ratio
E71626A
Micrologic
setup
Power
sign
E71644B
E71643B
E71642B
Setup
Primary
VT ratio
Primary
690V
690V
690V
Secondary
Secondary
Secondary
690V
690V
690V
then
Select either the:
c primary voltage
c secondary voltage.
400Hz
Select.
54
System
frequency
50 - 60Hz
Choose.
Micrologic H
E71629A
System
frequency
E71628A
Micrologic
setup
System
frequency
then
System
frequency
50 - 60Hz
Confirm.
Schneider Electric
Metering
setup
System
type
Caution!
The neutral current IN cannot be measured
with the "3-phase, 3-wire, 3-CT" and
"3-phase, 4-wire, 3-CT" types.
For a 3-pole device, the neutral,
if distributed, must be connected to
terminal VN of the Micrologic H control unit.
See the "Overview of functions" section for
information on the available types of
measurements.
3 4w
3CT
3 3w
3CT
Select.
System
type
3 3w
3CT
Confirm.
Choose.
Calculation
method
Current
demand
E89201C
Current
demand
E89200C
Metering
setup
Current
demand
System
type
E71632A
System
type
E71631A
E71630A
Note:
It is advised not to use the "3-phase, 4-wire, 4-CT" type of measurement unless the neutral is
effectively connected to the control unit (four-pole circuit breaker with an external voltagemeasurement input).
Current
demand
Window type
sliding
Calculation
method
block
block
interval
interval
Window type
sliding
Calculation
method
block
interval
Window type
sliding
Interval
Interval
Interval
thermal
15 min
Select.
55
15 min
Adjust.
Micrologic H
15 min
Confirm.
Schneider Electric
Calculation
method
block
interval
Window type
sliding
Calculation
method
block
interval
Window type
sliding
Interval
Interval
Interval
20 min
Select.
Confirm.
Adjust.
Window type
sliding
Calculation
method
block
interval
Window type
sliding
Interval
Interval
Interval
15 min
Select.
Confirm.
Choose between:
c thermal
c block interval
c sync. to comms
Power
demand
E89220C
E89219C
15 min
15 min
Power
demand
E89221C
Sliding window:
power demand is refreshed
every 15 secondes.
Power
demand
Calculation
method
block
interval
Window type
sliding
thermal
Power
demand
E89218C
E89217C
Power
demand
Calculation
method
Fixed window:
power demand is refreshed
at the end of the time interval.
20 min
Metering
setup
Power
demand
Current
demand
Calculation
method
block
interval
Window type
sliding
15 min
Current
demand
E89215C
E89213C
Current
demand
E89214C
Setup
Power
demand
Calculation
method
block
interval
Window type
sliding
Calculation
method
block
interval
Window type
fixed
Calculation
method
block
interval
Window type
fixed
Interval
Interval
Interval
15 min
Select.
56
15 min
Choose between fixed or
sliding.
Micrologic H
15 min
Confirm.
Schneider Electric
Calculation
method
block
interval
Window type
fixed
Calculation
method
block
interval
Window type
fixed
Interval
Interval
Interval
20 min
20 min
Select.
Confirm.
Adjust.
Sign
convention
E89227B
Sign
convention
E89226B
Metering
setup
Sign
convention
Power
demand
Calculation
method
block
interval
Window type
fixed
15 min
Power
demand
E98320A
E89223C
E89222C
Power
demand
Sign
convention
IEEE
Select.
57
IEEE alt.
Micrologic H
IEEE alt.
Confirm.
Schneider Electric
Setup
Com.
setup
Com.
parameter
Modbus
Com
E71725A
Modbus
Com
E71724A
E71723A
Address
Address
47
Address
45
45
Baud-rate
Baud-rate
Baud-rate
9600
9600
9600
Parity
Parity
Parity
None
None
then
Select an existing
parameter.
Modbus
Com
None
Adjust.
Confirm.
Adjust all the other parameters for the communications option in the same manner.
Address
Baud rate
DIGIPACT
MODBUS
(read only)
1 - 255
1 - 47
9 600 bauds
19 200 bauds
Even
None
Parity
Remote
settings
E71728A
Remote
settings
E71727A
Com.
setup
Remote
settings
Remote
settings
Access
permit
Access
permit
Access
permit
No
Yes
Yes
Access
code
Access
code
Access
code
0000
0000
0000
then
Select existing setting.
58
Micrologic H
Choose.
Confirm.
Schneider Electric
Access
permit
Access
permit
Yes
Yes
Yes
Access
code
Access
code
Access
code
1000
1000
Manual
Press enter.
59
Micrologic H
Remote
control
Auto
E71734A
Remote
control
E71733A
Com.
setup
Remote
control
Remote
settings
Access
permit
0000
Remote
settings
E71731A
Remote
settings
E71730A
E71729A
Remote
control
Auto
Confirm.
Schneider Electric
Current
protection
I(A)
Trip
(A)
1000 A
1.0 s
2000 A
0.2 s
I(A)
E60149A
E60275A
4000 A
I(A)
E60276A
E71738A
Protection settings
I(A)
Trip
Trip
Trip
1000 A
998 A
998 A
1.0 s
1.0 s
1.0 s
2000 A
0.2 s
2000 A
0.2 s
2000 A
0.2 s
4000 A
4000 A
4000 A
then
I(A)
Trip
Trip
998 A
998 A
1.0 s
1.0 s
2000 A
0.2 s
2000 A
0.2 s
4000 A
4000 A
Confirm.
E71657A
I(A)
E60277A
E60277A
Select a setting.
Do you want
to save new
settings?
No
Yes
then
Adjust the other settings
and confirm.
60
Micrologic H
Confirm.
Schneider Electric
Current
protection
Idmtl
(A)
Trip
long-time current setting Ir
long-time tripping delay tr
Idmtl protection:
DT, SIT, VIT, EIT, HVF
short-time pickup Isd
short-time tripping delay tsd
instantaneous pickup Ii
1.0 s
EIT
2000 A
0.2 s
Idmtl
(A)
E60278A
E71718A
4000 A
Change I(A)
settings with
Idmtl(A)?
No
Idmtl
(A)
E60151A
(A)
1000 A
Idmtl
(A)
Trip
Trip
1000 A
1000 A
1.0 s
1.0 s
EIT
VIT
2000 A
0.2 s
2000 A
0.2 s
4000 A
4000 A
Yes
then
then
(A)
Idmtl
(A)
Trip
Trip
1000 A
1000 A
1.0 s
1.0 s
VIT
VIT
2000 A
0.2 s
2000 A
0.2 s
4000 A
4000 A
E71657A
Idmtl
Select a setting.
E60280A
Select yes.
E60279A
Idmtl
E71739A
Do you want
to save new
settings?
No
Yes
puis
Confirm.
61
Micrologic H
Confirm.
Schneider Electric
Protection settings
E89231A
Current
protection
E89230A
Trip
(A)
Trip
(A)
1200A
threshold
1200A
0.5s
time delay
0.5s
then
(A)
Trip
(A)
E89234A
E89233A
E89232A
Select a setting.
Trip
(A)
Trip
1198A
1198A
1198A
0.5s
0.5s
0.5s
then
(A)
Trip
(A)
Trip
(A)
Trip
1198A
1198A
1198A
0.4s
0.4s
0.4s
62
Confirm.
E89236A
E89235A
Micrologic H
Confirm.
Schneider Electric
(A)
Caution!
Selection of the CT type determines the
"Ineutral" protection in the "Protection"
menu.
c "none" disables the neutral protection.
c "Internal" for a four-pole circuit breaker
provides access to the N/2, N and OFF
protection functions.
c "External" for a three-pole circuit breaker
provides access to the N/2, N, 1.6xN and
OFF protection functions.
three-pole
E89239B
Ineutral (A)
Neutral CT
Neutral CT
Internal
External
External
Protection
Protection
Protection
OFF
OFF
OFF
then
Ineutral (A)
Confirm.
E89242B
E89241B
Choose between:
c internal
c external
c none.
Ineutral (A)
Ineutral (A)
Neutral CT
Neutral CT
Neutral CT
External
External
External
Protection
Protection
Protection
N/2
N/2
OFF
then
Select.
E89242B
four-pole
Ineutral (A)
Neutral CT
Select.
E89240B
Type of
Possibles choices
circuit breaker
Ineutral (A)
Choose.
Ineutral (A)
Confirm.
E71657A
Ineutral
E89237B
Current
protection
E89238B
Neutral CT
External
Do you want
to save new
settings?
no
Protection
N/2
Quit the setting screen.
yes
Confirm.
Note:
On four-pole circuit breakers, setting of the neutral using the keypad is limited by the dial
setting.
63
Micrologic H
Schneider Electric
Protection settings
E71661B
Current
protection
Alarm
I unbal
type of protection
operating mode
(Off, Alarm or Trip)
Pick up
pickup threshold
(%)
I1 max
(A)
I2 max
(A)
I3 max
(A)
Drop out
dropout threshold
dropout time delay
IN max (A)
Voltage
protection
(V)
Uunbal
(%)
Umax (V)
Off
Pick up
Other
protection
Fmin
(Hz)
Fmax
(Hz)
Alarm
Pick up
Alarm
Pick up
690V
690V
5.00s
5.00s
5.00s
Drop out
690V
0.50s
Drop out
690V
0.50s
690V
0.50s
then
Umax (V)
Off
Pick up
E60292B
Phase
rotation
Umax (V)
690V
Drop out
rPmax (W)
Umax (V)
E60293B
Umax
(V)
E60292B
Umin
Confirm.
Umax (V)
Trip
Pick up
690V
690V
5.00s
5.00s
Drop out
690V
0.50s
then
Select the first setting.
64
Micrologic H
Choose Trip.
Schneider Electric
E89293B
E89295B
Umax (V)
Umax (V)
Trip
Pick up
Do you want
to set the
protection to
Trip mode?
690V
5.00s
no
yes
then
Confirm.
Alarm
Pick up
Alarm
Pick up
Alarm
Pick up
690V
690V
690V
5.00s
5.00s
5.00s
Drop out
690V
Drop out
685V
Drop out
685V
0.50s
0.50s
0.50s
Umax (V)
Adjust.
E71668A
E71668A
then
Select the existing
dropout threshold setting
Umax (V)
Confirm.
Umax (V)
Alarm
Pick up
Alarm
Pick up
690V
690V
5.00s
5.00s
Drop out
Drop out
685V
685V
0.50s
0.50s
E71657A
Umax (V)
E71667A
Umax (V)
E71666A
Do you want
to save new
settings?
No
Yes
then
Set the other parameters.
65
Micrologic H
Confirm
Schneider Electric
Setting load
shedding / reconnection
Load
shedding I
Load
shedding P
E71673B
Protection settings
Load
shedding
type of shedding (I or P)
operating mode (On, Off)
Pick up
pickup threshold
pickup time delay
Drop out
dropout threshold
dropout time delay
66
Micrologic H
Schneider Electric
Load
shedding
E71672A
Load
shedding
E71671A
E71670A
Load
shedding
Off
On
On
Pick up
Pick up
Pick up
1000kW
1000kW
1000kW
3600s
3600s
3600s
Drop out
Drop out
1000kW
10s
Drop out
1000kW
10s
1000kW
10s
then
Load
shedding
E71676A
Load
shedding
Confirm.
Select:
c Off: load shedding
disabled
c On: load shedding
enabled.
E71675A
E71674A
Load
shedding
On
On
On
Pick up
Pick up
Pick up
1000kW
1000kW
1000kW
3600s
3600s
3600s
Drop out
985kW
Drop out
980kW
10s
Drop out
985kW
10s
10s
then
Load
shedding
On
On
Pick up
Pick up
1000kW
1000kW
3600s
3600s
Drop out
E71657A
Load
shedding
Confirm.
Adjust.
E71677A
E71677A
Do you want
to save new
settings?
Drop out
985kW
985kW
10s
10s
No
Yes
then
Set the other parameters.
67
Micrologic H
Confim.
Schneider Electric
Metering
Current measurements
3850A
E60187A
4260A
E60185A
E60184A
The bargraph displays the value in amperes of the most heavily loaded phase.
3410A
1 2 3
1 2 3
1 2 3
100
100
100
50
50
50
The
and
buttons may be used to display the currents on the three
phases. If the operator no longer uses the buttons for a few seconds, the bargraph
returns to the display of the most heavily loaded phase.
I inst.
E60189A
I inst.
I1
I2
= 3410 A
= 4260 A
I3
= 3850 A
IN
200 A
13 A
then
Select.
View.
I inst.
E60191A
Instant.
(A)
E60190A
Imax
instant.
I1
I2
= 5600 A
= 4800 A
I3
= 4700 A
IN
800 A
28 A
Reset ( - / + )
then
View.
Select.
68
Micrologic H
Schneider Electric
Imax
E60191A
E60192A
Imax
instant.
instant.
I1
I2
=
=
0A
0A
I1
I2
= 5600 A
= 4800 A
I3
IN
=
=
0A
0A
I3
= 4700 A
IN
800 A
0A
28 A
Reset ( - / + )
Reset ( - / + )
(A)
Demand
E71679A
Demand.
Demand
13min
I1 =
3950 A
I2 =
4270 A
I3 =
3890 A
IN =
340 A
then
Select.
69
View.
Micrologic H
Schneider Electric
Current measurements
Metering
Demand
E71681A
E71680A
Imax
Demand
15min
Max
I1 =
4020 A
I2 =
4450 A
I3 =
4300 A
IN =
600 A
Reset ( - / +)
then
Select.
View.
Imax
E71683A
E71682A
Imax
Demand
Demand
15min
15min
I1 =
0A
I1 =
4020 A
I2 =
0A
I2 =
4450 A
I3 =
0A
I3 =
4300 A
IN =
0A
IN =
600 A
Reset ( - / +)
70
Micrologic H
Reset ( - / +)
Schneider Electric
Voltage measurements
U (V)
Instant.
Average 3
Unbal 3
Phase
rotation
Uinst.
U12 =
U23 =
U31 =
400 V
404 V
401 V
U1N =
U2N =
U3N =
230 V
229 V
233 V
then
Select.
View.
U (V)
E71687A
E89258B
Uavg.
3
Instant.
Average 3
402 V
Unbal 3
Phase
rotation
then
Select.
View.
E89259B
U (V)
Instant.
E71689A
(V)
E89257B
E60193A
Uunbal
3
Average 3
1%
Unbal 3
Phase
rotation
then
Select.
71
View.
Micrologic H
Schneider Electric
Voltage measurements
Metering
U (V)
Instant.
E89261A
E89260A
Phase
rotation
Average 3
Unbal 3
Phase
rotation
: 1, 2, 3
then
Select.
72
View.
Micrologic H
Schneider Electric
Power measurements
(kW)
E71690A
P
Instant.
Pinst.
E60199B
P, Q, S
Power
factor
Pinst.
P
(kW)
2180
(kvar)
-650
(kVA)
2280
then
Select.
View.
Pinst.
E71692A
E71691A
Power
factor
P, Q, S
Power
factor
1.00
then
Select.
(kW)
Demand
P, Q, S
E71694B
Demand
View.
Demand
P
(kW)
2350
(kvar)
-820
(kVA)
2640
Max
then
Select.
73
View.
Micrologic H
Schneider Electric
Metering
Demand
E71696B
E71695A
Pmax
Demand
P, Q, S
Max
(kW)
2450
(kvar)
-800
(kVA)
2700
Reset (- / +)
then
Select.
View.
Pmax
E71698B
E71697B
Pmax
Demand
Demand
(kW)
0
(kW)
2450
(kvar)
0
(kvar)
-800
(kVA)
0
Reset (- / +)
(kVA)
2700
Reset (- / +)
74
Micrologic H
Schneider Electric
Energy measurements
E (kWh)
E total
E in
E out
Reset
energy
then
E total
E in
E71702B
E71700B
Select.
E71701B
E out
E.P
(kWh)
20168
E.P
(kWh)
+21320
E.P
(kWh)
168
E.Q
(kvarh)
-2733
E.Q
(kvarh)
-2770
E.Q
(kvarh)
33
E.S
(kVAh)
22926
E71703A
E (kWh)
E total
E in
Reset
Energy
Are you
sure ?
E out
Reset
Energy
E71705A
(kWh)
E71704A
E71699A
To reset
energy
press
enter
No
Yes
then
Select.
75
then
Select yes or no.
Micrologic H
If yes, confirm.
Schneider Electric
Waveform
Waveform
I1,2,3
I1,2,3
I1
IN
U12,23,31
I2
I3
then
Select.
View.
Waveform
E89265A
E89264B
IN
I1,2,3
IN
U12,23,31
then
Select.
View.
E89266B
Waveform
E89267A
Harmonic
E89263A
Harmonic measurements
Waveform capture
E89262B
Metering
U12,23,31
I1,2,3
IN
U12,23,31
then
Select.
76
View.
Micrologic H
Schneider Electric
Fundamentals
E89268B
Fundament.
Fundament
(A)
U
P
(V)
I(A)
Fundament
I1
92 A
I2
= 126 A
I3
62 A
IN
1A
(W)
then
Select.
View.
Fundament
E89271B
E89270B
U(V)
Fundament
(A)
U
P
(V)
(W)
U12 =
U21 =
U31 =
281 V
333 V
276 V
V1N =
V2N =
V3N =
139 V
185 V
190 V
then
Select.
View.
E89272B
Fundament
E89273B
Harmonic
E89269B
P,Q,S
Fundament
(A)
U
P
(V)
(kW)
-9
(kvar)
47
(kVA)
52
(W)
then
Select.
77
View.
Micrologic H
Schneider Electric
Harmonic measurements
THD
THD
ITHD(%)
(%)
I1
7.0 %
(%)
I2
5.8 %
I3
6.2 %
IN
2.1 %
then
Select.
View.
E89277B
THD
E89274A
Harmonic
E89275B
Metering
THD
(%)
(%)
UTHD(%)
U12 =
U23 =
U31 =
1.0 %
1.2 %
1.4 %
V1N =
V2N =
V3N =
2.2 %
2.0 %
2.0 %
then
Select.
78
View.
Micrologic H
Schneider Electric
thd
thd
Ithd (%)
(%)
I1
6.8 %
(%)
I2
7.2 %
I3
5.6 %
IN
8.1 %
then
Select.
View.
E89281B
thd
E89278A
Harmonic
E89279B
thd
(%)
(%)
Uthd (%)
U12 =
U23 =
U31 =
1.0 %
1.2 %
1.8 %
V1N =
V2N =
V3N =
2.0 %
2.8 %
2.6 %
then
Select.
79
View.
Micrologic H
Schneider Electric
FFT
FFT
(3,5,7,.,31)
(3,.,31)
U(3,5,7,.,31)
I2
(3,.,31)
I3
(3,.,31)
IN
(3,.,31)
Note :
FFT= Fast Fourier Transform
FFT
I1
I1 FFT
THD=6.3
8.0%
3 5 7 9 11
then
then
E89285B
Select.
Select a current.
I1 FFT
E89286B
Harmonic
E89284B
E89283A
Harmonic measurements
FFT amplitude spectrum
E89282A
Metering
I1 FFT
THD=6.3
5.0%
THD=6.3
1.0%
3 5 7 9 11
23 25 27 29 31
80
Micrologic H
Schneider Electric
E89289B
FFT
E89288A
E89287A
FFT
(3,5,7,.,31)
U12
(3,.,31)
U(3,5,7,.,31)
U23
(3,.,31)
U31
(3,.,31)
U12 FFT
THD=3.2
3.0%
3 5 7 9 11
then
then
Select a voltage.
U12 FFT
E89291B
E89290B
Select.
U12 FFT
THD=3.2
23.0%
THD=3.2
0.0%
3 5 7 9 11
23 25 27 29 31
81
Micrologic H
Schneider Electric
Frequency measurements
E60110A
Metering
F (Hz)
(Hz)
60.0
View.
82
Micrologic H
Schneider Electric
83
Micrologic H
Schneider Electric
Caution!
If the circuit breaker remains closed and
the Ap LED remains ON after the reset,
open the circuit breaker and contact the
after-sales support department.
Maintenance
Micrologic 7.0 H
Fault
22/11/1999
02:04:04
Umin
100V
Reset
by test/reset
button
84
Micrologic H
Schneider Electric
E71706A
Event
history
Trip
history
Trip
history
E71707A
Trip history
Trip
22/11/1999
02:04:04
Umin
160V
U min
27/01/1999
Ir
27/06/1998
Ir
18/02/1998
then
Select a fault.
Alarm
history
I2 max
27/01/1999
E71709A
Alarm
history
Alarm history
E71708A
Event
history
View.
Alarm
27/01/1999
13:06:09
I2 max 3400A
In max
23/03/1998
U max
12/02/1998
then
Select an alarm.
85
Micrologic H
View.
Schneider Electric
Event
history
Operation
counter
Number of
operations
Number of
operations
E71737A
E71736A
E71735A
Maintenance
Number of
operations
Total
Total
Total
17824
17824
17824
Operations
since last
reset
Operations
since last
reset
Operations
since last
reset
6923
6923
Reset ( - / + )
Reset ( - / + )
Reset ( - / + )
then
Reset
Event
history
Contact
wear
Contact
wear
59
86
Micrologic H
Schneider Electric
E89248A
1 2 3
E71751A
Press and hold down the test button on the control unit to check the LEDs and the
battery. The battery information is displayed if the control unit is equipped with an
external power supply or if the circuit breaker is ON.
Battery fully charged
Battery half charged
No battery or must be replaced
E60308A
1. remove
the battery cover
87
E60473A
Micrologic H
Schneider Electric
Tests
Maintenance
E89249A
5.0
logic
Micro
If the circuit breaker does not trip, contact the after-sales support department.
E89251A
E89250A
The test connector is used to connect the mini or the portable test kit to check that
the control unit is operating correctly.
5.0
logic
Micro
Micro
logic
5.0 H
88
Micrologic H
Schneider Electric
89
Micrologic H
Schneider Electric
Tripping curves
Technical appendix
10 000
5 000
Ir = 0.41 x In
2 000
1 000
tr = 0.524 s
500
200
100
50
20
10
5
t(s)
Isd = 1.510 x Ir
2
1
I2t ON
.5
0.4
0.3
.2
0.2
0.1
.1
.05
.02
.01
0.4
0.3
0.2
0.1
I2t OFF
Ii = 215 x In . OFF
.005
.002
.001
.5 .7 1
3 4 5 7 10
x Ir
20
7 10
x In
20 30
100 000
HVF
10 000
5 000
2 000
1 000
EIT
500
t(s)
200
100
VIT
50
SIT
20
10
DT
5
2
1
.5
.5 .7
4 5
10
20
I / Ir
90
Micrologic H
Schneider Electric
E46266A
Ig = AJ x In (1)
1200 A max.
1 000
500
200
100
50
20
10
5
t(s)
I2t ON
2
1
.5
.2
.1
.05
It
0.4
0.4
0.3
0.2
0.1
0.3
0.2
0.1
OFF
.02
.01
.005
.002
.001
.05.07 .1
.2 .3 .4 .5 .7 1
7 10
200 300
I / In
91
Micrologic H
Schneider Electric
Technical appendix
Voltage measurements
Micrologic H is equipped with a three-phase voltage power supply that, with respect
to the distribution system, may be considered a delta load. The three-phase power
supply reinjects voltage on an open phase.
The voltage-protection functions react as indicated below.
Minimum-voltage protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit
reinjects voltage on the failed phase and measures a phase-to-phase voltage
higher than the actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
In diagram 2, the phase-to-neutral voltage is effectively zero and the measurement
indicates zero as well.
By limiting the pickup threshold of the minimum-voltage protection to the 80% 100% range of the rated distribution-system voltage, the differences between the
real voltages and the measured values are not significant and Micrologic will
operate under all circumstances in the expected manner.
Voltage-unbalance protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit
reinjects voltage on the failed phase and measures a phase-to-phase voltage
higher than the actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
In diagram 2, the phase-to-neutral voltage is effectively zero and the measurement
indicates zero as well.
By limiting the pickup threshold of the voltage-unbalance protection to the 0% 20% range, the differences between the real voltages and the measured values are
not significant and Micrologic will operate under all circumstances in the expected
manner.
Phase failure
Detection of phase failure is not possible on the basis of the minimum-voltage and
voltage-unbalance protection functions.
The Micrologic power supply requires at least two phases (between 100 and 690 V).
In diagrams 1, 3 and 4, if two phases have failed, Micrologic H measures for the
three phases the value of the single voltage present (e.g. U12 = U23 = U31 = 410 V).
92
Micrologic H
Schneider Electric
E71916A
c diagram 1
Contactor
Fuses
Motor
Open
E71917A
c diagram 2
Contactor
Fuses
Motor
Open
E71918A
c diagram 3
Contactor
Motor
Open
Fuses
E71919A
c diagram 4
Load
Fuses
Other
measurement
and protection
systems
93
Micrologic H
Schneider Electric
E60450B
Technical appendix
Operating principle
Note:
On device no. 1, the tsd and tg tripping delays must not be set to zero because this
would make discrimination impossible.
2
Caution!
lf the protection function is not used on
circuit breakers equipped for ZSI
protection, a jumper must be installed to
short terminals Z3, Z4 and Z5. If the jumper
is not installed, the short-time and groundfault tripping delays are set to zero,
whatever the position of the adjustment
dial.
Wiring
upstream
circuit-breaker
Z1
Z2
Z3
Z4
Z5
tsd = 0.3
point B
Z1
Z2
Z3
Z4
Z5
tsd = 0. 2
point A
Z1
Z2
Z3
Z4
Z5
downstream
circuit-breaker
Z1
Z2
Z3
Z4
Z5
Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
94
Micrologic H
Schneider Electric
Power supply
Caution!
It is advised to use the AD power-supply
module rather than an off-the-shelf 24 V
power supply to ensure Class II insulation
on the front panel of the Micrologic H
control unit.
AD power-supply module
The AD power-supply module provides auxiliary 24 V DC power for the control-unit
functions listed below:
c graphic display:
v device OFF or not supplied
v the long-time, short-time, instantaneous and ground-fault protection functions
operate under all circumstances on their own power
c activation of an M2C programmable contact
The AD power-supply module is required to assign an M2C programmable contact
to an alarm.
Battery module
Use of a BAT battery module, mounted in series with the AD power-supply module,
ensures a continous supply of 24 V DC power for 12 hours if the AD module fails.
Wiring diagrams
E60449A
L4
L3
AD 22
Input
AC
220V
t
OutpuC
24VD
0V
+
G2
G1
F2
+
F1
-
E60448A
H4
L4
L3
AD 22
H3
Input
AC
220V
0V
t
OutpuC
24VD
InputC
24VD
24
BAT
G2
G1
t
OutpuC
24VD
+
H1
H2
F1
-
F2
+
E60447A
2 Q3
25
21 23
17 19
L4
L3
AD 22
M6C
Input
AC
220V
0V
t
OutpuC
24VD
+
G2
G1
95
Micrologic H
Schneider Electric
Technical appendix
Power supply
circuit breaker
closed
open
open
yes
yes
no
yes
no
no
no
yes
no
no
no
yes
yes
no
no
no
no
yes
c if the 24 V DC external power supply (AD module) is used, the maximum cable
length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed
10 metres.
c the communications bus requires its own 24 V DC power source (E1, E2).
This source is not the same as the 24 V DC external power-supply module (F1-,
F2+).
96
Micrologic H
Schneider Electric
Part number
33542
33543
33544
33545
Caution!
Following any modifications to the longtime rating plug, all control-unit protection
parameters must be checked.
standard
0.4 to 1 x Ir
low setting
0.4 to 0.8 x Ir
high setting
0.8 to 1 x Ir
without long-time protection
c Ir = In for the short-time protection setting
c frequency protection not available
c load shedding / reconnection based on current not available
E89252A
3. completely remove
the long-time rating plug screw
5.0
logic
Micro
Micro
logic
5.0 H
E89254A
Caution!
If no long-time rating plug is installed, the
control unit continues to operate under the
following downgraded conditions:
c the long-time current setting Ir is 0.4
c the long-time tripping delay tr
corresponds to the value indicated by the
adjustment dial
c the earth-leakage protection function is
disabled
c the voltage-measurement inputs are
disconnected.
Micro
logic
5.0 H
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s) 4
2
1
8 12
16
20
24
.5 @ 6 Ir
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
97
Micrologic H
tr
(s) 4
2
1
8 12
16
20
24
.5 @ 6 Ir
Schneider Electric
Technical appendix
Thermal memory
Thermal memory
The thermal memory is the means to take into account temperature rise and
cooling caused by changes in the flow of current in the conductors.
These changes may be caused by:
c repetitive motor starting
c loads fluctuating near the long-time protection settings
c repeated circuit-breaker closing on a fault.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.
98
Micrologic H
Schneider Electric
Measurements
c currents
v instantaneous currents
v maximum and minimum instantaneous currents
v average instantaneous currents
v instantaneous-current unbalance per phase
v maximum and minimum instantaneous-current unbalance per phase
c demand current
v demand current per phase
v maximum and minimum demand current per phase since last reset
v prediction of demand current per phase
v time-stamping of demand-current maximums and minimums
c voltages
v phase-to-neutral and phase-to-phase voltages
v average phase-to-neutral and phase-to-phase voltages
v phase-to-neutral and phase-to-phase voltage unbalance
v maximum and minimum phase-to-neutral and phase-to-phase voltage unbalance
c active, reactive and apparent power per phase
c demand power
v demand power per phase
v maximum and minimum demand power per phase since last reset
v maximum and minimum recommended demand power per phase
v time-stamping of demand-power maximums and minimums
c energy
v total active and reactive energy
v positively incremented energy
v negatively incremented energy
c system frequency
c power factor
c reset date of demand currents, demand power and energy
c power quality indicators:
v instantaneous measurements together with maximums and minimums:
- fundamental apparent currents
- fundamental phase-to-neutral and phase-to-phase voltages
- fundamental rms currents
- fundamental active, reactive and apparent power per phase and total
- distortion power per phase and total
- THD and thd of the phase-to-neutral and phase-to-phase voltages
- THD and thd of the currents
- phase angle between the voltages and the currents
- K factors
- peak voltages
- peak currents
- phase angle between the voltages
- K factors averages
v demand K factors:
- demand K factors per phase
- maximum demand K factor per phase since last reset
- prediction of demand K factors
- time-stamping of demand K factor maximums per phase
v harmonics:
- phase-to-neutral and phase-to-phase voltage harmonic amplitudes
- current harmonic amplitudes
- phase-to-neutral and phase-to-phase voltage harmonic phase angle
- current harmonic phase angle
v monitoring of electrical parameters
v dates of last resets of minimums and maximums
v waveform capture
v event history file in the measurement module
v minimum and maximum file with time-stamping
v maintenance file in the measurement module
- minimum and maximum reset counters with time-stamping
- maximum demand-current reset counters with time-stamping
- maximum demand-power reset counters with time-stamping
- energy reset counters with time-stamping.
99
Micrologic H
Schneider Electric
Technical appendix
Setup / Maintenance
c setting of the control-unit date and time
c password for the measurement module
c control-unit ID code
c control-unit ID name
c selection of the measurement calculation algorithm
c sign convention for the active power
c total-energy measurement mode
c interval for the demand-current calculation window
c power quality indication
c demand-power calculation mode
c interval for the demand-power calculation window
c battery-charge indication
c trip and alarm histories
c operation counter and contact-wear indicator
c assignment and setup of programmable contacts
c event log and maintenance register
c power factor sign conventions
c monitoring parameters
c monitoring priorities levels
c waveform capture.
Protection
c circuit-breaker rated current
c type of neutral protection
c long-time I2t protection settings
c long-time Idmtl protection settings
c short-time protection settings
c instantaneous-protection settings
c ground-fault protection settings
c earth-leakage protection settings
c current-unbalance, It alarm and maximum-current protection settings
c voltage-protection settings
c setting for other protection functions.
100
Micrologic H
Schneider Electric
Range
Factory setting
Step
Accuracy
0.4 to In
0.5 to 24 s
maximum
maximum
1A
0.5 s
1.05 to 1.20 Ir
- 20 %, + 0 %
Short-time protection
Type
Isd pickup
tsd tripping delay
Range
Factory setting
Step
Accuracy
1.5 to 10 Ir
0 - 0.1 - 0.2 - 0.3 - 0.4 s
maximum
maximum
10 A
0.1 s
10 %
Instantaneous protection
Type
Ii pickup
Range
Factory setting
Step
Accuracy
2 to 15 In or off
maximum
10 A
10 %
Range
Factory setting
Step
Accuracy
depends on rating
0 - 0.1 - 0.2 - 0.3 - 0.4 s
maximum
maximum
1A
0.1 s
10 %
In pickup
t tripping delay
Range
Factory setting
Step
Accuracy
0.1 A
1 setting
- 20 %, + 0 %
maximum
maximum
Neutral protection
Type
three-pole device
four-pole device
Range
Factory setting
off.
N/2
101
Micrologic H
Schneider Electric
Technical appendix
Current protection
Type
current unbalance I unbal
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
ground-fault I t alarm
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
earth-leakage I t alarm
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
Range
Factory setting
Step
Accuracy
5% to 60%
5% of pickup threshold
1 s to 40 s
10 s to 360 s
60 %
pickup threshold
40 s
10 s
1%
1%
1s
1s
-10 %, +0 %
-10 %, +0 %
-20 %, +0 %
-20 %, +0 %
20 A to 1200 A
20 A to pickup threshold
1 s to 10 s
1 s to 10 s
120 A
pickup threshold
10 s
1s
1A
1A
0.1 s
0.1 s
+/- 15 %
+/- 15 %
-20 %, +0 %
-20 %, +0 %
30 A
pickup threshold
10 s
1s
0.1 A
0.1 A
0.1 s
0.1 s
-20 %, +0 %
-20 %, +0 %
-20 %, +0 %
-20 %, +0 %
In
pickup threshold
1500 s
15 s
1A
1A
1s
1s
6.6%
6.6%
-20 %, +0 %
-20 %, +0 %
0.5 A to 30 A
0.5 A to pickup threshold
1 s to 10 s
1 s to 10 s
maximum current I 1 max, I 2 max, I 3 max, I N max
Pickup threshold
0.2 In to In
Dropout threshold
0.2 In to pickup threshold
Pickup time delay
15 s to 1500 s
Dropout time delay
15 s to 3000 s
Voltage protection
Type
Range
Factory setting
Step
Accuracy
100 V
pickup threshold
5V
5V
-5 %, +0 %
-5 %, +0 %
5s
1.2 s
0.1 s
0.1 s
-0 %, +20 %
-0 %, +20 %
725 V
pickup threshold
5s
1.2 s
5V
5V
0.1 s
0.1 s
-0 %, +5 %
-0 %, +5 %
-0 %, +20 %
-0 %, +20 %
2% to 30%
2% to pickup threshold
1 s to 40 s
10 s to 360 s
30 %
pickup threshold
40 s
10 s
1%
1%
1s
1s
-20 %, +0 %
-20 %, +0 %
-20 %, +0 %
-20 %, +0 %
102
Micrologic H
Schneider Electric
Other protection
Type
Range
Factory setting
Step
Accuracy
5 to 500 kW
5 kW to pickup threshold
0.2 s to 20 s
1 s to 360 s
500 kW
pickup threshold
20 s
1s
5 kW
5 kW
0.1 s
0.1 s
2.5%
2.5%
-0 %, +20 % (1)
-0 %, +20 %
65 Hz
pickup threshold
5s
1.2 s
0.5 Hz
0.5 Hz
0.1 s
0.1 s
0.5 Hz
0.5 Hz
-0 %, +20 % (2)
-0 %, +20 % (2)
45 Hz
pickup threshold
0.5 Hz
0.5 Hz
0.5 Hz
0.5 Hz
5s
1.2 s
0.1 s
0.1 s
-0 %, +20 % (2)
-0 %, +20 % (2)
phase rotation
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
none
none
none
none
none
none
-0 %, +50 %
-0 %, +50 %
Range
Factory setting
Step
Accuracy
current I
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
50 % to 100% Ir
30 % Ir to shedding threshold
20 % to 80% tr
10 s to 600 s
100 % Ir
shedding threshold
80 % tr
10 s
1%
1%
1%
1s
6%
6%
-20 %, +0 %
-20 %, +0 %
power P
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
200 kW to 10 000 kW
100 kW to shedding threshold
10 s to 3600 s
10 s to 3600 s
10 000 kW
shedding threshold
3600 s
10 s
50 kW
50 kW
10 s
10 s
2.5 %
2.5 %
-20 %, +0 %
-20 %, +0 %
103
Micrologic H
Schneider Electric
Technical appendix
Other settings
Range
Factory setting
Step
1 - 360 s
360 s
1s
Step
Micrologic setup
Type
Range
Factory setting
language
German
English US
English UK
Italian
French
Spanish
Chinese
English UK
date / time
circuit-breaker
selection
neutral TC
VT ratio
primary voltage
secondary voltage
system
frequency
1s
"no def"
no TC
min. 100 V, max. 1150 V
min. 100 V, max. 690 V
50/60 Hz
or
400 Hz
690 V
690 V
50/60 Hz
1V
1V
Range
Factory setting
Step
3 , 3 w, 3 CT
3 , 4 w, 3 CT
3 , 4 w, 4 CT
3 , 4 w, 4 CT
thermal or
block interval
sliding
5 to 60 minutes
block interval
thermal or
block interval or
sync. to comms
fixed or sliding
5 to 60 minutes
P+
P-
block interval
Measurement setup
Type
system type
demand-current
calculation method
type of window
calculation interval
demand-power
calculation method
type of window
calculation interval
power sign
sign convention
IEEE
IEEE alternate
IEC
sliding
15 minutes
1 minute
sliding
15 minutes
P+
(flow from top to
bottom)
IEEE
1 minute
Communication setup
Type
com parameter
address
baud rate
parity
remote settings
access authorisation
access code
remote
control
Range
Factory setting
MODBUS
1-47
9600 to 19 200 bauds
even
none
47
19 200 bauds
even
yes / no
0000 to 9999
manual
automatic
yes
0000
automatic
Protection setup
Type
current protection
voltage protection
other protection
104
Micrologic H
Range
Factory setting
OFF
Schneider Electric
Example:
For a circuit breaker with a 4000 A rating
and a current displayed on Micrologic
of 49 A, the accuracy is:
0.5% x 4000 + 1.5% x 49 = 21 A
Accuracy at 25 C
instantaneous current
I1, I2, I3
IN
I t ground
I t earth leakage
I1 max, I2 max, I3 max
IN max
I t max ground
I t max earth leakage
0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to In
0 to 30 A
0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to In
0 to 30 A
1.5 %
1.5 %
10 %
1.5 %
1.5 %
1.5 %
10 %
1.5 %
demand current
I 1, I 2, I 3
IN
I 1 max, I 2 max, I 3 max
I N max
0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to 20 x In
1.5 %
1.5 %
1.5 %
1.5 %
phase-to-phase voltages
U12
U23
U31
170 to 1150 V
170 to 1150 V
170 to 1150 V
0.5 %
0.5 %
0.5 %
phase-to-neutral voltages
V1N
V2N
V3N
100 to 1150 V
100 to 1150 V
100 to 1150 V
0.5 %
0.5 %
0.5 %
average voltage
U avg
170 to 1150 V
0.5 %
voltage unbalance
U unbal
0 to 100 %
0.5 %
instantaneous power
P
Q
S
0.015 to 184 MW
0.015 to 184 Mvar
0.015 to 184 MVA
2%
2%
2%
power factor
PF
-1 to +1
2%
demand power
P
Q
S
P max
Q max
S max
0.015 to 184 MW
0.015 to 184 Mvar
0.015 to 184 MVA
0.015 to 184 MW
0.015 to 184 Mvar
0.015 to 184 MVA
2%
2%
2%
2%
2%
2%
total energy
E.P
E.Q
E.S
2%
2%
2%
total energy in
E.P
E.Q
2%
2%
2%
2%
frequency
F
45 Hz to 440 Hz
0.1 %
I
U
P, Q, S
0.005 x In to 1.5 x In
30 to 1150 V
0.15 to 13.8 kW
1.5 % (1)
0.5 %
2%
THD, thd
I
U
2 to 1000%
2 to 1000%
5%
5%
FFT
I
U
0 to 1000%
0 to 1000%
5%
5%
Type
fundamentals
105
Micrologic H
Schneider Electric
E71920B
Technical appendix
Q
P to load
Q to load
P from load
Q to load
E71921B
P from load
Q from load
IEC
P to load
Q from load
Q
P=Q=+
pf = -
P=+
Q=+
pf = +
P
E71922B
P=Q=pf = -
IEEE
P=+
Q=pf = +
Q
P=Q=+
pf = + (leading)
P=+
Q=+
pf = - (lagging)
P
E71923B
P=Q=pf = - (lagging)
IEEE Alt
P=+
Q=pf = + (leading)
Q
P=Q=pf = + (leading)
P=+
Q=pf = - (lagging)
P
P=Q=+
pf = - (lagging)
106
Micrologic H
P=+
Q=+
pf = + (leading)
Schneider Electric
107
Micrologic H
Schneider Electric
Index
A
Activation
Active, reactive, apparent energy
Active, reactive, apparent power
AD power-supply module
Address
Alarm
Alarm history
B
Baud rate
Buttons
58
5, 6
C
Circuit-breaker selection
COM communication option
Contact
Contact wear
Control unit identification
Control-unit battery
Cos
Crest factor
Current demand calculation
53
49, 58, 99
45, 50
86
4
5, 87
40
41
31, 55
D
Date and time
Demand current
Demand power
Digipact
Direction of power flow
Distortion factor
Distortion power
Dropout
DT
52
55, 69
32, 56
58
54
41
41
27, 28, 29, 30, 44
23, 61
E
Earth-leakage protection
Earth-leakage protection tripping delay
EIT
26
26
23, 61
F
F max
F min
Fault
Frequency
FTT
Full neutral protection
Fundamental
Graphic display
Ground-fault / Earth-leakage fault protection test
Ground-fault protection
29, 64
29, 64
84
32, 54, 82
42, 80
25, 63
77
5
88
26
H
Half neutral protection
Harmonics
History, setup and maintenance menu
HVF
25, 63
33
13, 18
6, 23
I
It
I t Alarm
I avg
I max
I unbal
In pickup
I2t
Idmtl
Ig pickup
Ii pickup
Infrared link
Instantaneous current
Instantaneous protection
Ir current setting
Isd pickup
62
27, 64
27
27, 64
64
26
22, 60
23, 61
26
24
5
68
24
22, 23
24
K
K factor
41
108
Micrologic H
Schneider Electric
L
Language
Latching
Lead seal for cover
LEDs
Load shedding / reconnection
Long-time I2t protection
Long-time Idmtl protection
Long-time plug
52
45, 50
5
5, 47, 87
30, 66
22
23
5, 97
M
M2C / M6C
Main screen
Maximum demand current
Maximum demand power
Maximum instantaneous current
Metering menu
ModBus
45, 50
12, 68
31, 70
32, 74
31, 68
13, 14
58
N
Negatively incremented energy
Neutral CT
Neutral protection
Neutral protection setting
No neutral protection
32, 75
63
23, 25
11
25, 63
O
Operation counter
Oversized neutral protection
86
25, 63
P
Parity
Phase rotation
Phase sequence
Phase-to-neutral and phase-to-phase voltage
Portable test kit
Positively incremented energy
Power demand calculation
Power factor
Power sign
Power supply
Protection menu
58
29, 31, 64
31, 72
31, 71
88
32, 75
32, 56
40
54
95
13, 20
R
Remote control
Remote settings
Resetting the alarms and fault indications
Resetting the contacts
Resetting the energy values
Resetting the maximum demand current values
Resetting the maximum demand power values
Resetting the maximum instantaneous current values
Resetting the operation counter
RMS current
rms voltage
rP max
59
58
84
45, 50
75
70
74
68
86
37
37
29, 64
S
Self-protection
Setting dials
Short-time protection
Sign convention
SIT
System frequency
System type
5, 48
5, 6
24
106
23, 61
54
55
109
Micrologic H
Schneider Electric
Index
T
Tab
Temperature
Test connector
tg tripping delay
THD
thd
Thermal memory
tr tripping delay
Transformation ratio
Trip
Trip history
Tripping curves
tsd tripping delay
7
22, 48, 98
5, 88
26
37, 78
39, 79
22, 98
22, 23
54
44
46, 85
90
24
U
U max
U min
U unbal
28
28, 92
28, 71, 92
V
VIT
Voltage U avg
23, 61
28, 31
W
Waveform
Waveform capture
43
43, 76
Z
Zone selective interlocking
94
110
Micrologic H
Schneider Electric
As standards, specifications and design change from time to time, always ask for confirmation
of the information given in this publication.
This document has been printed on ecological paper
Layout by: HeadLines
Printed by:
http://www.schneider-electric.com
04443728AA-C
05-02