Sie sind auf Seite 1von 112

Micrologic control units

5.0 H, 6.0 H and 7.0 H


Low Voltage Products

Firmware version H Logic-2002 AA

E60439A

User manual

We do more with electricity.

Micrologic control units


5.0 H, 6.0 H and 7.0 H

Discovering Micrologic H

Identification
Presentation
Setting procedure
Setting Micrologic 5.0 H using the dials
Setting Micrologic 6.0 H using the dials
Setting Micrologic 7.0 H using the dials
Selecting the type of neutral protection
Main menus
Metering
History, maintenance and setup
Protection

4
5
6
8
9
10
11
12
14
18
20

Overview of functions

22

Current protection
Voltage protection
Other protection
Load shedding and reconnection
Measurements
Harmonic measurements
Alarms
Optional M2C and M6C contacts
Event histories
LEDs and display screens
COM communications option

22
28
29
30
31
33
44
45
46
47
49

Setup

50

Setting up the optional M2C / M6C contacts


Setting up the Micrologic control unit
Setting up the metering functions
Setting up the COM communications option

50
52
55
58

Protection settings

60

Fine adjustment of the long-time I2t, short-time and


instantaneous settings using the keypad
Fine adjustment of the long-time Idmtl, short-time and
instantaneous settings using the keypad
Fine adjustment of the ground-fault and earth-leakage
protection setting using the keypad
Setting the neutral protection
Setting the It, I unbal, I max, U min, U max, U unbal, rP max,
F min, F max and phase-rotation protection functions
using the keypad
Setting load shedding / reconnection

64
66

Metering

68

Current measurements
Voltage measurements
Power measurements
Energy measurements
Harmonic measurements
Frequency measurements

68
71
73
75
76
82

Maintenance

84

Resetting fault indications


Viewing the event histories
Operation counter and contact-wear indicator
Checking/replacing the battery
Tests

84
85
86
87
88

Micrologic H

60
61
62
63

Schneider Electric

Technical appendix

90

Tripping curves
Voltage measurements
Zone selective interlocking (ZSI)
Power supply
Changing the long-time rating plug
Thermal memory
Data available via the COM communications option
Threshold and time-delay settings
Other settings
Measurement setting ranges and accuracy
Power-factor sign conventions

90
92
94
95
97
98
99
101
104
105
106

Index

108

Micrologic H

Schneider Electric

Micrologic H

Schneider Electric

Discovering Micrologic H

Identification

All Masterpact NT and NW circuit breakers


are equipped with a Micrologic control unit
that can be changed on site.
Control units are designed to protect
power circuits and connected loads.
They offer current, voltage, frequency,
power and energy measurements.
The functions provided by Micrologic 5.0 H,
6.0 H and 7.0 H control units optimise
continuity of service and power
management in your installation.

Micrologic 5.0 H

E60231A

E71927A

Selective protection + Idmtl,


power measurements and additional protection
Micrologic 5.0 H

t
Idmtl

4260A
N 1 2 3
100

50

0
long time

Ir
.7
.6
.5
.4

x In

Isd

Ii

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

Ii

(s)

on

I t

setting

4
3

off

6 8 10
12
15
off
2
x In

delay

test

Micrologic 5.0 H
Micrologic 6.0 H

Micrologic 6.0 H

E60233A

E71928A

E60231A

Selective protection + Idmtl + ground-fault protection,


power measurements and additional protection
t

Idmtl

4260A

I t on

N 1 2 3
100

X: type of protection
c 2 for basic protection
c 5 for selective protection
c 6 for selective + ground-fault protection
c 7 for selective + earth-leakage protection

I t off

50

Ir

Isd

Ii

Ig

long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

instantaneous

Y: version number
Identification of the control-unit generation:
"0" signifies the first generation.

tsd
(s)

.3
.2
.1

D
C
B
A

I t

6 8 10
4
12
3
15
off
2
x In

.2
.1
0
off

delay

tg

on

setting

Ig

Ii

.4 .4 .3

(s)

F
G
H
J

Ground-fault protection

Selective protection
+ Idmtl

@ 6 Ir

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

test

.4 .4 .3

.3
.2
.1
on

I t

.2
.1
0
off

ground fault

Z: type of measurement
c A for "ammeter"
c P for "power meter"
c H for "harmonic meter"
c no indication = no measurements

Micrologic 7.0 H

Micrologic 7.0 H

E51452A

E60231A

Selective protection + Idmtl + earth-leakage protection,


power measurements and additional protection
E71929A

E71926A

Ir

Selective protection + Idmtl

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

Idmtl

4260A
N 1 2 3
100

50

0
long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

on

setting
(A)

3
2
1
.5

I t

off

delay

(ms)

230
7
10
140
20
30
60

4
3

Isd

Ii

In

Earth-leakage protection

6 8 10
12
15
off
2
x In
test

In

Ii

(s)

Ir

Selective protection
+ Idmtl

350
800

earth leakage

Micrologic H

Schneider Electric

top fastener
terminal block for external connections
housing for battery
screw for long-time rating plug
long-time rating plug
cover opening point
protective cover
lead-seal fixture for protective cover
infrared link with communications interfaces
connection with circuit breaker
bottom fastener

E60236A

1
2
3
4
5
6
7
8
9
10
11

E60235B

Presentation

1
2
Micro

logic

5.0 P

3
9

alarm

Indications

15
16
17

time

tr
(s)

2
1
.5

8 12
16
20
24
Ir
at 6

4
5

10

11

E60238A

14

LED indicating long-time tripping


LED indicating short-time or
instantaneous tripping
LED indicating ground-fault or
earth-leakage tripping
LED indicating additional-protection or
auto-protection tripping
graphics display
button for reset of fault-trip LED reset
and battery test

E71930A

12
13

long

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

Micrologic 5.0 H

12

18

19

20

21

22

23

17

13
14

Navigation

20
21
22
23

access button to the "Metering" menu (*)


access button to the "History, maintenance
and setup" menu (*)
access button to the "Protection" menu (*)
button used to scroll down or reduce
the displayed value
button used to scroll up or increase
the displayed value
button used to select or confirm a choice

100

50

Adjustment dials

35

long-time current setting Ir


long-time tripping delay tr
short-time pickup Isd
short-time tripping delay tsd
instantaneous pickup Ii
ground-fault pickup Ig
ground-fault tripping delay tg
earth-leakage pickup In
earth-leakage tripping delay t
LED indicating an overload
test button for ground-fault and
earth-leakage protection
test connector

Micrologic 5.0 H control unit


E60239A

24
25
26
27
28
29
30
31
32
33
34

N 1 2 3

16

Micrologic 6.0 H control unit

long time

Ir
.7
.6
.5
.4

24
25

x In

27

long time

Ir

24

@ 6 Ir

25

tsd
(s)

Ii

.4 .4 .3
.2
.1

.3
.2
.1

on

I t

setting

4
3

0
off

6 8 10
12
15
off
2
x In

.7
.6
.5
.4

x In

28

26
27

delay

@ 6 Ir

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

instantaneous

35

29
30

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

D
C
B
A

on

I t

off

delay

tg
F
G
H
J

Ii

(s)

setting

Ig

33

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

short time

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

26

33

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

E60240A

18
19

4260A

15

(s)

on

.2
.1
2

I t

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1

4
3

0
off

28
34
35

ground fault

Micrologic 7.0 H control unit

( )

E60241B

* These buttons include a LED indicating the active menu.

long time

Ir

24

.7
.6
.5
.4

25

x In

@ 6 Ir

instantaneous

short time

26
27

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd
(s)

31
32

2
1
.5

Ii

.4 .4 .3
.2
.1

.3
.2
.1

on

setting

I t

0
off

delay

(ms)

230

350

10
140
20
30
60

800

4
3

6 8 10
12
15
off
2
x In
test

In
(A)

33

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

28
34
35

earth leakage

Micrologic H

Schneider Electric

Setting procedure

Dials
c dials are used to set Micrologic H
protection thresholds and tripping delays for
overloads, short-circuits, ground faults and
earth leakage.
c if the set thresholds are overrun, these
protection functions systematically trip the
circuit breaker.

Settings using the dials

5.0
logic
Micro

c open the protective


cover.

5.0
logic
Micro

c make the necessary settings using the dials


c the screen automatically displays the relevant curve
c check the set value on the screen, in absolute value
in amperes (A) and in seconds (s).

Settings using the keypad


Buttons
c buttons on the keypad are used for fine
and
buttons under the screen may be
adjustments of the protection thresholds and c the
used for fine adjustments of the settings made using
tripping delays for overloads, short-circuits, the dials.
ground faults and earth leakage. The value
c all the settings not available via the dials are made
in the same manner, using the keypad.
previously set using a dial automatically
becomes the maximum value for the keypad Caution!
settings.
A new overload (long-time) or short-circuit
(short-time and instantaneous) protection setting
c they may also be used to activate other
made using one of the dials:
factory-disabled protection functions
c deletes all the fine adjustments previously
available on Micrologic H. These other
made using the keypad for the overload
protection functions are not accessible via
(long-time) and short-circuit (short-time and
instantaneous) protection
the dials.

With the protective cover open, make all the


necessary settings for your control unit.
All fine adjustments are permanently stored
in memory, unless the setting is modified
using the adjustment dial.
For remote settings using the
communications option,
see the "Remote settings" section in the
"Com setup" menu under "History,
maintenance and setup".

60252B

E60250B

E60251B

Discovering Micrologic H

Micro

logic

5.0

c does not affect the fine adjustments made


using the keypad for ground-fault and
earth-leakage protection
c does not affect any other settings made using
the keypad.
Similarly, a new ground-fault or earth-leakage
protection setting made using one of the dials:
c deletes all the fine adjustments previously
made using the keypad for the ground-fault and
earth-leakage protection
c does not affect the fine adjustments made
using the keypad for the overload (long-time) and
short-circuit (short-time and instantaneous)
protection
c does not affect any other settings made using
the keypad.

Micrologic H

Schneider Electric

E60254B

E60253B

View the settings and measurements

5.0
logic
Micro

c close the protective


cover for the dials
c access to the dials is
blocked and it is no
longer possible to make
fine adjustments using
the keypad

E60490B

With the protective cover closed,


it is not possible to set the protection
functions. However, it is possible to set
metering functions and alarms, as well as
view all measurements, settings and
histories.

5.0
logic
Micro

Micrologic H

5.0
logic
Micro

c if necessary, install a
lead seal to protect the
settings
c settings may be viewed
at any time using the
keypad.

Caution!
If you notice that the tab on the back of the protective
cover has been broken off, contact the Schneider
after-sales support department to replace the cover.

Schneider Electric

Setting Micrologic 5.0 H


using the dials

Consider a 2000 A circuit breaker.

Set the thresholds

E60445A

E60325A

Discovering Micrologic H

In = 2000 A

long time

Ir
.7
.6
.5
.4

.8

x In

.9
.95
.98
1

Ir = 0.5 x 2000 = 1000 A


Isd = 2 x 1000 = 2000 A

Ii = 2 x 2000 = 4000 A

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ii

6 8 10
4
12
3
15
off
2
x In

setting

In = 2000 A
In =

A
2000

See pages 22 and 24 for selection of the


setting ranges.
E60326A

Set the time delays


tr = 1 s

long time

tr
(s)

2
1
.5

12
16
20
24

tsd = 0.2 s

@ 6 Ir

short time

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

off

delay

thresholds

Ir

I2t OFF curve

I2t ON curve

Ir

E51375A

curve

E51376A

time delays
I2t OFF curve
E51372A

E51373A

I2t ON

tr
Isd

tr

Isd
tsd
Ii

0
Ir: LT threshold
Isd: ST pickup
Ii: Instantaneous pickup

tsd

Ii
I

0
tr: LT tripping delay
tsd: ST tripping delay

Micrologic H

Schneider Electric

Setting Micrologic 6.0 H


using the dials

Set the thresholds

E60445A

E60329A

Consider a 2000 A circuit breaker.

In = 2000 A

long time

Ir
.7
.6
.5
.4

.8

.9
.95
.98
1

x In

Ir = 0.5 x 2000 = 1000 A


instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

6 8 10
4
12
3
15
off
2
x In

Ii = 2 x 2000 = 4000 A

setting

Ig
D
C
B
A

In = 2000 A
In =

Isd = 2 x 1000 = 2000 A

Ii

A
2000

Ig = 640 A

F
G
H
J

ground fault

See pages 22 to 26 for selection


of the setting ranges.
E60330A

Set the time delays


tr = 1 s

long time

tr
(s)

2
1
.5

12
16
20
24

@ 6 Ir

tsd = 0.2 s

short time

tsd
(s)

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

tg = 0.2 s

delay

tg
(s)

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

thresholds

Ir

I2t ON curve

curve

Ir

I2t OFF curve


E51375A

curve

E51376A

time delays
I2t OFF
E51372A

E51373A

I2t ON

tr

tr

Isd

Isd

tsd

Ig

0
tr: LT tripping delay
tsd: ST tripping delay

E51419A

E51416A

E51415A

E51418A

Ii
0
Ir: LT threshold
Isd: ST pickup
Ii: Instantaneous pickup

tsd

Ii

Ig

tg

tg

0
I
Ig: ground-fault pickup

0
I
tg: ground-fault tripping delay

Micrologic H

Schneider Electric

Setting Micrologic 7.0 H


using the dials

Consider a 2000 A circuit breaker.

Set the thresholds

E60445A

E60333B

Discovering Micrologic H

In = 2000 A

long time

Ir
.7
.6
.5
.4

.8

.9
.95
.98
1

x In

Ir = 0.5 x 2000 = 1000 A


instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Isd = 2 x 1000 = 2000 A

Ii

6 8 10
4
12
3
15
off
2
x In

Ii = 2 x 2000 = 4000 A

setting

In
(A)

2
1
.5

In = 2000 A
In =

A
2000

In = 1 A
7
10
20
30

earth leakage

See pages 22 to 26 for selection of


the setting ranges.
E60334B

Set the time delays


tr = 1 s

long time

tr

2
1
.5

12
16
20
24

@ 6 Ir

E60153A

(s)

short time

tsd

tsd = 0.2 s

.4 .4 .3

(s)

.2
.1

.3
.2
.1

on

I t

0
off

t = 140 ms

delay

(ms)

230

350

140
60

800

earth leakage

time delays

thresholds

Ir

I2t ON curve

curve

Ir

I2t OFF curve


E51375A

curve

E51376A

I2t OFF
E51372A

E51373A

I2t ON

tr
Isd

tr

Isd
tsd
Ii

0
tr: LT tripping delay
tsd: ST tripping delay

E51423A

E51421A

0
Ir: LT threshold
Isd: ST pickup
Ii: Instantaneous pickup

tsd

Ii
I

In
t

0
I
In: earth-leakage pickup

t: earth-leakage tripping
delay

10

Micrologic H

Schneider Electric

E51383A

Selecting the type of neutral


protection

Selection dial on four-pole circuit breakers


/2
3D+N

4P 4D

4P 3D

On four-pole circuit breakers, it is possible to select the type of neutral protection


for the fourth pole using the three-position dial on the circuit breaker:
c no neutral protection 4P 3D
c half neutral protection 3D + N/2
c full neutral protection 4P 4D
The factory default setting is 3D + N/ 2.

Caution!
With the 4P 3D setting, the current in the neutral must
not exceed the rated current of the circuit breaker.

11

Micrologic H

Schneider Electric

Main menus

Discovering Micrologic H

The Micrologic H control unit offers access to the main screen and three menus:
c the main screen displaying the continuous measurement of the phase currents
(I1, I2, I3) and the neutral current (IN), if it exists
c the "Metering" menu
c the "History, maintenance and setup" menu
c the "Protection" menu.

E60101A

Main screen

4260A
1 2 3
100

As long as no functions are activated, Micrologic H


control units display in real time the current on the
most heavily loaded phase.
The number for that phase is presented in a square.
The current in the neutral is displayed if the neutral CT
is set as internal or external (see "Ineutral (A)"
settings in the "Current protection" menu).

50

When a menu button is pressed, a


presentation screen is displayed and the
green LED on the button goes ON.

"Metering", "History, maintenance and setup" and


"Protection" menus

E71931B

c "Metering" menu

(A)

(V)

(kW)

(kWh)

v press the
screen

or

button to return to the main

v press the
button to return to the previous
screen
v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
few minutes
v the LED goes OFF on exiting the menu.

Harmonic

12

Micrologic H

Schneider Electric

E71711A

c "History, maintenance and setup" menu

v press the
screen

Event
history
Contacts
M2C / M6C
Micrologic
setup

or

button to return to the main

v press the
button to return to the previous
screen
v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
few minutes
v the LED goes OFF on exiting the menu.

Metering
setup
Com.
setup

E71712A

c "Protection" menu

v press the
screen

Current
protection

or

button to return to the main

v press the
button to return to the previous
screen
v whatever the screen displayed, if no further action is
taken, the system returns to the main screen after a
few minutes
v the LED goes OFF on exiting the menu.

Voltage
protection
Other
protection
Load
shedding

Load
shedding

E71657A

c saving settings
When a setting is made in any of the three menus, the
screen used to save the modification(s) may be
accessed by pressing one of the three buttons
,

Do you want
to save new
settings?

or

v select yes to save the modifications


v select no to cancel and maintain the previous
settings
v this screen remains displayed until yes or no are
selected.

no
yes

13

Micrologic H

Schneider Electric

Discovering Micrologic H

Metering

Press the

button to select the "Metering" menu.

move the cursor down the screen or decrement a value.


move the cursor up the screen or increment a value.
select an option in a list, confirm a selection or the value of a setting.
indicates that the operator is in the "Metering" menu and returns
to the previous screen.

E71932B

return to the main screen.

(A)

(V)

(kW)

(kWh)

Current measurements

access to the following sections:

(A)
Instant.

Harmonic

I1, I2, I3, IN

I1, I2, I3, IN currents


(depending on the type of
system)

Max

Storing and reset of the


maximum instantaneous
currents

Demand
I1, I2, I3, IN

E71933B

Max

(A)

(V)

(kW)

(kWh)

Demand current on the


phases I1, I 2, I3 and on IN
(depending on the type of
system)
Storing and reset of
the maximum demand
currents.

Voltage measurements

Harmonic

(V)

access to the following sections:

Instant.

Instantaneous phase-to-phase U12, U23, U31 and


phase-to-neutral V1N, V2N, V3N voltages
(depending on the type of system)

Average 3

Average voltage U average of the phase-to-phase


voltages.

Unbal 3

Unbalance voltage U unbal. of the phase-to-phase


voltages.

Phase sequence.

Phase
rotation

14

Micrologic H

Schneider Electric

E71934B

Power measurements

(A)

(V)

(kW)

(kWh)

(kW)

access to the following sections:

Instant.
P, Q, S,
Power
factor

Harmonic

Total active power P


Total reactive power Q
Total apparent power S
Power factor PF

Demand
P, Q, S

E71935B

Max

(A)

(V)

(kW)

(kWh)

Demand values for the:


c total active power P
c total reactive power Q
c total apparent power S
Storing and reset of
the maximum demand power
values

Energy measurements

Harmonic

(kWh)
E total

Total active energy E.P


Total reactive energy E.Q
Total apparent energy E.S

E in

Positive component of:


c the total active energy E.P
c the total reactive energy E.Q

E out

Negative component of:


c the total active energy E.P
c the total reactive energy E.Q

Reset
Energy

15

access to the following sections:

Micrologic H

Reset all the energy values to zero

Schneider Electric

E71936B

Discovering Micrologic H

Harmonic measurements

(A)

(V)

Harmonic

(kW)

(kWh)

access to the following sections:

Waveform

Harmonic

I1, 2, 3

Waveform capture
for currents I1, I2 and I3

IN

Waveform capture
for the neutral current IN

U12, 23, 31

Waveform capture for


voltages U12, U23 and U31

Fundament.
Measurement of
the fundamental of currents
I1, I2, I3 and IN

(A)

(V)

(W)

(%)

(%)

(%)

(%)

Total harmonic distortion of


voltages U12, U23 and U31
and V1N, V2N and V3N

I (3, 5, 7,..., 31)

Amplitude spectrum of odd


current harmonics
up to H31

U (3, 5, 7,..., 31)

Amplitude spectrum of odd


voltage harmonics
up to H31

Measurement of
the fundamental of voltages
U12, U23 and U31
and V1N, V2N and V3N
Measurement of
the fundamental of active
power P, reactive power Q
and apparent power S.

THD
Total harmonic distortion
of currents I1, I2, I3 and IN
Total harmonic distortion
of voltages U12, U23 and
U31 and V1N, V2N
and V3N

thd
Total harmonic distortion
of currents I1, I2, I3 and IN

FFT

16

Micrologic H

Schneider Electric

E71937B

Frequency measurement

(V)

(kW)

(kWh)

(Hz)

access to the frequency measurement

Harmonic
F

(Hz)

17

Micrologic H

Schneider Electric

Discovering Micrologic H

History, maintenance
and setup

Press the

button to select the "History, maintenance and setup" menu.

move the cursor down the screen or decrement a value.


move the cursor up the screen or increment a value.
select an option in a list, confirm a selection or the value of a setting.
indicates that the operator is in the "History, maintenance and setup" menu
and returns to the previous screen.

E71711A

return to the main screen.

Event
history
Contacts
M2C / M6C

Event history

Event
history

Micrologic
setup
Metering
setup

E71713A

Com.
setup

access to the following sections:

Trip
history

The last ten faults recorded

Alarm
history

The last ten alarms recorded

Operation
counter

Number of operations (opening or closing)

Contact
wear

Wear of the circuit-breaker main contacts

M2C / M6C Contacts

Event
history
Contacts
M2C / M6C

Contacts
M2C / M6C
Alarm
type

Micrologic
setup

access to the following sections:

Assignment of a protection alarm to an M2C or an


M6C contact

Latching mode for each M2C or M6C contact

Metering
setup

Setup

Com.
setup

Reset

Reset of the M2C or M6C contacts

18

Micrologic H

Schneider Electric

E71714A

Event
history
Contacts
M2C / M6C

Micrologic setup

Micrologic
setup

Micrologic
setup

Language

Metering
setup

Date / time

E71715A

Com.
setup

Event
history
Contacts
M2C / M6C

Indication of the circuit-breaker type

Power
sign

Setting the power sign

VT ratio

Select of the primary and secondary voltages on


the instrument transformer

System
frequency

Indication of the rated system frequency

Metering
setup

Com.
setup

E71716A

Setting of the date and time

Breaker
selection

access to the following sections:

System
type

c 3 phases, 3 wires, 3 CTs: method using two


wattmeters
c 3 phases, 4 wires, 3 CTs: method using three
wattmeters
c 3 phases, 4 wires, 4 CTs: method using three
wattmeters with measurement of the neutral
current.

Current
demand

Selection of the calculation method and setting of


the time interval for the calculation

Power
demand

Selection of the calculation method and setting of


the parameters for the calculation

Sign
convention

Setting of the sign convention for the power factor


and reactive power, i.e. IEEE, IEEE alternate or IEC
(see page 106 to determine the sign convention)

Metering
setup

Contacts
M2C / M6C

Selection of the display language

Metering setup

Micrologic
setup

Event
history

access to the following sections:

COM communications-option setup

Com.
setup

Micrologic
setup
Metering
setup
Com.
setup

19

access to the following sections:

Com.
parameter

Setting of parameters for the COM communications


option (address, baud rate, parity)

Remote
settings

Authorisation of access to settings via


the COM communications option.

Remote
control

Authorisation of access to the circuit-breaker ON


and OFF commands via the COM communications
option.

Micrologic H

Schneider Electric

Discovering Micrologic H

Protection

Press the

button to select the "Protection" menu.

move the cursor down the screen or decrement a value


move the cursor up the screen or increment a value
select an option in a list, confirm a selection or the value of a setting
indicates that the operator is in the "Protection" menu and returns
to the previous screen

E71712A

return to the main screen

Current protection

Current
protection

access to the following sections:

Current
protection

Voltage
protection
Other
protection
Load
shedding

Load
shedding

(A)

Fine settings of the long-time I2t, short-time and


instantaneous protection functions

Idmtl

(A)

Fine settings of the long-time Idmtl,


short-time and instantaneous protection functions

(A)

Fine settings of the:


c ground-fault (Micrologic 6.0 H)
c earth-leakage (Micrologic 7.0 H) protection functions

Ineutral (A)
I

Setting of the I

alarm

Alarm

Iunbal

Setting of the current-unbalance protection I unbal

(%)

I1 max

(A)

I2 max

(A)

I3 max

(A)

IN max (A)

20

Selection of the type of neutral


sensor and type of neutral protection

Micrologic H

Setting of the maximum-current protection I1 max

Setting of the maximum-current protection I 2 max

Setting of the maximum-current protection I 3 max

Setting of the maximum-current protection I N max

Schneider Electric

E71719A

Voltage protection

Current
protection

E71720A

Voltage
protection
Other
protection

E71721A

Umin

(V)
(V)

Load
shedding

Umax

Load
shedding

Uunbal (%)

Setting of the minimum-voltage protection U min.

Setting of the maximum-voltage protection U max.

Setting of the voltage-unbalance protection U unbal.

Other protection

Current
protection

access to the following sections:

Other
protection

Voltage
protection
Other
protection

rPmax (W)

Load
shedding

Load
shedding

Fmin

(Hz)

Fmax

(Hz)

Phase
rotation

Current
protection
Voltage
protection
Other
protection

E71722A

access to the following sections:

Voltage
protection

Setting of the reverse-power protection rP max

Setting of the minimum-frequency protection F min

Setting of the maximum-frequency protection F max

Setting of the phase-rotation protection

Load shedding depending on current

Load
shedding

Load
shedding

Load
shedding

Access to load shedding and reconnection


depending on current

Load shedding depending on power

Current
protection

Load
shedding

Voltage
protection
Other
protection
Load
shedding

Load
shedding

21

Micrologic H

Access to load shedding and reconnection


depending on power

Schneider Electric

Overview of functions

Current protection
I2t long-time protection

For the default values, the setting ranges,


increment steps and setting accuracies,
see the technical appendix.

The long-time protection function protects cables against overloads. This function is
based on true rms measurements.
It is possible to select either I2t long-time protection or Idmtl long-time protection.

I2t long-time protection


Long-time current setting Ir and standard tripping delay tr

Micrologic control unit

Accuracy 5.0 H, 6.0 H and 7.0 H

current setting
Ir = In (*) x
tripping betweeen 1.05 and 1.20 Ir

time setting
time delay (s)

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir

0 to - 30%
0 to - 20%
0 to - 20%

0.4
0.5
0.6
0.7
0.8
0.9
other ranges or disable by changing rating plug

0.95

0.98

0,5
12.5
0.7 (1)
0.7 (2)

16
400
16
11

20
500
20
13.8

24
600
24
16.6

1
25
1
0.69

2
50
2
1.38

4
100
4
2.7

8
200
8
5.5

12
300
12
8.3

(*) In: circuit breaker rating


(1) 0 to - 40%
(2) 0 to - 60%

c it is possible to enhance the Ir setting accuracy (reduced range) or disable the


long-time protection function by using a different long-time rating plug.
See the technical appendix "Changing the long-time rating plug".
Thermal memory
c the thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function of
the circuit breaker by taking into account the temperature rise in the cables.
c the thermal memory assumes a cable cooling time of approximately 15 minutes.

22

Micrologic H

Schneider Electric

Idmtl long-time protection

Idmtl Protection
Long-time current setting Ir and Idmtl tripping delay tr

Micrologic control unit

Accuracy 5.0 H, 6.0 H and 7.0 H

current setting
Ir = In (*) x
tripping between 1.05 and 1.20 Ir

0.4
0.5
0.6
0.7
0.8
0.9
other ranges or disable by changing rating plug

0.95

0.98

time setting

0,5

12

16

20

24

DT
time delay (s)

SIT
time delay (s)

VIT
time delay (s)

EIT
time delay (s)

HVF
time delay (s)

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir

0 to - 20%
0 to - 20%
0 to - 20%
0 to - 20%

0.53
0.53
0.53
0.53

1
1
1
1

2
2
2
2

4
4
4
4

8
8
8
8

12
12
12
12

16
16
16
16

20
20
20
20

24
24
24
24

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir

0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%

1.9
0.5
0.7 (1)
0.7 (2)

3.8
1
0.88
0.8

7.6
2
1.77
1.43

15.2
4
3.54
2.86

30.4
8
7.08
5.73

45.5
12
10.6
8.59

60.7
16
14.16
11.46

75.8
20
17.7
14.33

91
24
21.2
17.19

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir

0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%

3.6
0.5
0.7 (1)
0.7 (2)

7.2
1
0.81
0.75

14.4
2
1.63
1.14

28.8
4
3.26
2.28

57.7
8
6.52
4.57

86.5
12
9.8
6.86

115.4
16
13.1
9.13

144.2
20
16.34
11.42

173.1
24
19.61
13.70

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir

0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%

12.5
0.7 (1)
0.7 (2)
0.7 (2)

25
1
0.69
0.7 (1)

50
2
1.38
0.7 (1)

100
4
2.7
1.41

200
8
5.5
2.82

300
12
8.3
4.24

400
16
11
5.45

500
20
13.8
7.06

600
24
16.6
8.48

tr at 1.5 x Ir
tr at 6 x Ir
tr at 7.2 x Ir
tr at 10 x Ir

0 to - 30%
0 to - 20%
0 to - 20%
0 to - 20%

164.5
0.7 (1)
0.7 (2)
0.7 (2)

329
1
0.7 (1)
0.7 (2)

658
2
1.1 (1)
0.7 (1)

1316
4
1.42
0.7 (1)

2632
8
3.85
1.02

3950
12
5.78
1.53

5265
16
7.71
2.04

6581
20
9.64
2.56

7900
24
11.57
3.07

(*) In: circuit breaker rating


(1) 0 to - 40%
(2) 0 to - 60%

c these curves with different slopes are used to improve:


v discrimination with fuses positioned upstream (HV) and/or downstream
v protection for certain types of loads
c five types of curves are available:
v DT: definite time curve
v SIT: standard inverse time curve (I0.5t)
v VIT: very inverse time curve (It)
v EIT: extremely inverse time curve (I2t)
v HVF: compatible with high-voltage fuses (I4t).
c neutral protection
Overload protection (long time) for the neutral is disabled if the Idmtl protection
function is selected. However, the short-circuit protection (short time and
instantaneous) remains operational.
c intermittent overloads
As long as the Micrologic H control unit remains supplied with power, the effects of
intermittent overloads on cables are calculated. If power is cut, temperature rise in
cables is not calculated.
c circuit-breaker thermal limit
For certain settings, the Idmtl curves may be limited by the I2t curve when the
tripping delay tr is set to 24 seconds or by its thermal memory. The maximum I2t
curve remains active for the phases and the neutral even when the Idmtl curves are
activated.

23

Micrologic H

Schneider Electric

Overview of functions

Current protection
Short-time and instantaneous
protection

For the default values, the setting ranges,


increment steps and setting accuracies,
see the technical appendix.

Short-time protection
c the short-time protection function protects the distribution system against
impedant short-circuits
c the short-time tripping delay and the I2t ON and I2t OFF options can be used to
ensure discrimination with a downstream circuit breaker
c this function carries out true rms measurements.
c use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve
v I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 Ir. Above 10 Ir, the time curve is constant.

For the characteristics and external wiring


of the zone selective interlocking function,
see the technical appendix on "Zone
selective interlocking".

c zone selective interlocking (ZSI)


The short-time and ground-fault protection functions enable time discrimination by
delaying the upstream devices to provide the downstream devices the time
required to clear the fault. Zone selective interlocking can be used to obtain total
discrimination between circuit breakers using external wiring.
c intermittent faults are taken into account by Micrologic H and may lead to shorter
tripping times than those set.
Short-time pickup Isd and tripping delay tsd

Micrologic control unit


pickup
time delay (ms)
at 10 Ir
I2t On or
I2t Off

Isd = Ir x ... accuracy 10 %


setting
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)

5.0 H, 6.0 H and 7.0 H


1.5
0
20
80

2
0.1
0.1
80
140

2.5
0.2
0.2
140
200

3
0.3
0.3
230
320

4
0.4
0.4
350
500

10

If the "without long-time protection" plug is used and the long-time protection
function is disabled, the short-time pickup Isd is automatically multiplied by In
instead of Ir as is the standard case.

Instantaneous protection
c the instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping delay
for instantaneous protection is not adjustable. The tripping order is sent to the
circuit breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
c this function carries out true rms measurements.
Instantaneous pickup Ii

Micrologic control unit


pickup

Ii = In (*) x ... accuracy 10 %

5.0 H, 6.0 H and 7.0 H


2

10

12

15

OFF

(*) In: circuit-breaker rating

c circuit breakers have two types of instantaneous protection:


v adjustable instantaneous protection Ii
v self-protection.
Depending on the circuit breaker, the OFF position corresponds to
the self-protection pickup.

24

Micrologic H

Schneider Electric

Neutral protection

For the default values, the setting ranges,


increment steps and setting accuracies,
see the technical appendix.

Three-pole circuit breakers


Protection of the neutral is possible on a three-pole circuit breaker by connecting
an external sensor.
Settings are made using the
and
buttons on the control unit.

Micrologic control unit

5.0 H, 6.0 H and 7.0 H

Setting

OFF

Type of neutral

N/2

1.6xN

Description

No neutral protection

The distribution system does not require protection


of the neutral conductor.
Half neutral protection
The cross-sectional area of the neutral conductor is half that
of the phase conductors.
c the long-time current setting Ir for the neutral is equal to
half the setting value
c the short-time pickup Isd for the neutral is equal to half
the setting value
c the instantaneous pickup Ii for the neutral is equal to
the setting value
c for ground-fault protection (Micrologic 6.0 H), pickup Ig for
the neutral is equal to the setting value.
Full neutral protection
The cross-sectional area of the neutral conductor is equal to
that of the phase conductors.
c the long-time current setting Ir for the neutral is equal to
the setting value
c the short-time pickup Isd for the neutral is equal to the
setting value
c the instantaneous pickup Ii for the neutral is equal to the
setting value
c for ground-fault protection (Micrologic 6.0 H), pickup Ig for
the neutral is equal to the setting value.
Oversized neutral protection In installations with a high level of third-order harmonic
currents (or multiples thereof), the current in the neutral
conductor may exceed that of the phase currents under
steady-state conditions
c the long-time current setting Ir for the neutral is 1.6 times
that of the setting value
c the short-time pickup Isd for the neutral is 1.6 times that of
the setting value, but may not exceed 10 In to limit
transients and self-protect the installation
c the instantaneous pickup Ii for the neutral is equal to
the setting value
c for ground-fault protection (Micrologic 6.0 H), pickup Ig for
the neutral is equal to the setting value.

Four-pole circuit breakers


The initial protection setting is made using the dial on the neutral pole of the circuit
breaker.
and
buttons on the control unit may then be used for a more precise
The
setting. The dial setting constitutes the upper limit for adjustments using the keypad.

Micrologic control unit

5.0 H, 6.0 H and 7.0 H

Setting

OFF

Type of neutral
No neutral protection
Half neutral protection

Full neutral protection

25

Micrologic H

N/2

Description
The distribution system does not require protection of the
neutral conductor.
The cross-sectional area of the neutral conductor is half that
of the phase conductors.
c the long-time current setting Ir for the neutral is equal to
half the setting value
c the short-time pickup Isd for the neutral is equal to half
the setting value
c the instantaneous pickup Ii for the neutral is equal to the
setting value
The cross-sectional area of the neutral conductor is equal
to that of the phase conductors.
c the long-time current setting Ir for the neutral is equal to
the setting value
c the short-time pickup Isd for the neutral is equal to the
setting value
c the instantaneous pickup Ii for the neutral is equal to
the setting value.
Schneider Electric

Overview of functions

Current protection
Ground-fault and earth-leakage
protection

For the default values, the setting ranges,


increment steps and setting accuracies,
see the technical appendix.

Ground-fault protection on Micrologic 6.0 H


c an ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
function is to eliminate this type of fault.
c there are two types of ground-fault protection.

Type

Description

Residual

Source Ground Return

c the function determines the zero-phase sequence


current, i.e. the vector sum of the phase and neutral
currents (depending on the type of installation).
c using a special external sensor, this function directly
measures the fault current returning to the transformer
via the earth cable
c it detects faults both upstream and downstream of
the circuit breaker
c the maximum distance between the sensor and the
circuit breaker is ten metres.

c ground-fault and neutral protection are independent and can therefore be


combined.
Ground-fault pickup Ig and tripping delay tg
The pickup and tripping-delay values can be set independently and are identical for
both the residual and "source ground return" ground-fault protection functions.

Micrologic control unit


pickup

time delay (ms)


at In or 1200 A
I2t On or
I2t Off

Ig = In (*) x ... accuracy 10 %


In 400 A
400 A < In 1200 A
In > 1200 A
settings
I2t Off
I2t On
tg (max resettable time)
tg (max. break time)

6.0 H
A
0.3
0.2
500 A
0
20
80

B
0.3
0.3
640 A
0.1
0.1
80
140

C
0.4
0.4
720 A
0.2
0.2
140
200

D
0.5
0.5
800 A
0.3
0.3
230
320

E
0.6
0.6
880 A
0.4
0.4
350
500

F
0.7
0.7
960 A

G
0.8
0.8
1040 A

H
0.9
0.9
1120 A

J
1
1
1200 A

(*) In: circuit-breaker rating

Earth-leakage protection on sur Micrologic 7.0 H


c the earth-leakage protection function primarily protects people against indirect
contact because an earth-leakage current can provoke an increase in the potential
of the exposed conductive parts. The earth-leakage pickup value In is displayed
directly in amperes and the tripping delay follows a constant-time curve.
c an external rectangular sensor is required for this function
c this function is inoperative if the long-time rating plug is not installed
v d Protected against nuisance tripping
v k DC-component withstand class A up to 10 A.
c if the optional external voltage-measurement input is used, a 24 V DC external
power supply must be connected to Micrologic H (terminals F1-, F2+).
Pickup value In and tripping delay t

Micrologic control unit


pickup (A)
time delay (ms)
settings

7.0 H

In accuracy 0 to - 20 %

0.5

t (max resettable time)


t (max. break time)

60
140

140
200

230
320

350
500

800
1000

26

Micrologic H

10

20

30

Schneider Electric

I t Alarm, current unbalance,


maximum current
Operating principle

For the pickup and dropout thresholds and


time delays, see the technical appendix.
E71740A

protection tripped by a maximum value


t

3
1
4

I t Alarm, I unbal,
I max

1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
c for protection tripped by a maximum value, it is possible to set:
v a pickup threshold (1) that activates an alarm, a contact and/or tripping
v a pickup time delay (2) that steps in when the pickup threshold (1) is reached
v a dropout threshold (3) corresponding to deactivation of the alarm and/or contact
v a dropout time delay (4) that steps in when the dropout threshold (3) is reached
c the dropout threshold is always less than or equal to the pickup threshold.

I t Alarm
c the alarm function is tripped by the rms value of an earth-leakage current
c this alarm signals an earth-leakage current under the pickup value and does not
produce circuit-breaker tripping.

Current-unbalance protection I unbal

E71749A

c this protection is activated by an adjustable level of unbalance between the RMS


values of the three phase currents.
I
E max

I avg

I1

I2

I3

c from:
v I avg is the average value of the rms currents of the
three phases
I1 + I2 + I3
I avg =
3
v E max is the maximum difference between the
current of each phase and I avg
c Micrologic H uses the two values above to calculate
the current unbalance:
E max
I unbal =
I avg

Maximum-current protection per phase I max


c protection values may be set for each of the following currents:
v I 1 max: maximum current on phase 1
v I 2 max: maximum current on phase 2
v I 3 max: maximum current on phase 3
v I N max: maximum current in the neutral
c this function calculates the rms demand value of the current for the given phase
( I1, I 2, I 3) or the neutral ( IN), over a sliding time interval.
The time interval is the same as that for the calculation of the demand currents in
the "Metering" menu.
Settings are made in the "Metering setup" menu.
Note:
IN max protection does not take into account the neutral-protection setting (N, N/2, 1.6xN, OFF).

27

Micrologic H

Schneider Electric

Overview of functions

Voltage protection
Minimum voltage, maximum voltage,
voltage unbalance

For the pickup and dropout thresholds and


time delays, see the technical appendix.

Operating principle
protection tripped
by a maximum value
E71741A

E60489A

protection tripped
by a minimum value
t

U min 0

U max
U unbal.

1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
c for protection tripped by a minimum or maximum value, it is possible to set:
v a pickup threshold (1) that activates an alarm, a contact and/or tripping
v a pickup time delay (2) that steps in when the pickup threshold (1) is reached
v a dropout threshold (3) corresponding to deactivation of the alarm and/or contact
v a dropout time delay (4) that steps in when the dropout threshold (3) is reached
c for protection tripped by a minimum value, the dropout threshold is always greater
than or equal to the pickup threshold
c for protection tripped by a maximum value, the dropout threshold is always less
than or equal to the pickup threshold
c if both the minimum and maximum protection functions are activated at the same
time, the minimum threshold is automatically limited to the value of the maximum
and vice versa.

If the voltage protection functions are


activated and the voltage measurement
inputs are still energised, it is impossible to
reset and close the circuit breaker.

Minimum-voltage protection U min


c this function calculates the minimum rms value of the three phase-to-phase
voltages
c protection is activated when at least one of the three phase-to-phase voltages
(U12, U23, U31) is below the threshold set by the user
c this protection function does not detect phase failure.

Maximum-voltage protection U max


c this function calculates the maximum rms value of the three phase-to-phase
voltages
c protection is activated when the three phase-to-phase voltages (U12, U23, U31)
are simultaneously above the threshold set by the user.

Voltage-unbalance protection U unbal

E71742A

This protection is activated by an adjustable level of unbalance between the rms


values of the three phase-to-phase voltages.
This function calculates the rms value of the unbalance between the three phaseto-phase voltages.
U
E max

U avg

U12

U23

U31

28

Micrologic H

c from:
v U avg is the average value of the rms voltages of the
three phases
U12 + U23 + U31
U avg =
3
v E max: is the maximum difference between the
voltage of each phase and U avg
c Micrologic H uses the two values above to calculate
the voltage unbalance:
E max
U unbal =
U avg

Schneider Electric

Other protection
Reverse power, min. frequency,
max. frequency, phase rotation

E60487A

protection tripped
by a minimum value

protection tripped
by a maximum value

E60486A

Operating principle

For the pickup and dropout thresholds and


time delays, see the technical appendix.

3
3

4
4

F min 0

F max
rP max

1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
c for protection tripped by a minimum or maximum value, it is possible to set:
v a pickup threshold (1) that activates an alarm, a contact and/or tripping
v a pickup time delay (2) that steps in when the pickup threshold (1) is reached
v a dropout threshold (3) corresponding to deactivation of the alarm and/or contact
v a dropout time delay (4) that steps in when the dropout threshold (3) is reached
c for protection tripped by a minimum value, the dropout threshold is always greater
than or equal to the pickup threshold
c for protection tripped by a maximum value, the dropout threshold is always less
than or equal to the pickup threshold
c if both the minimum and maximum protection functions are activated at the same
time, the minimum threshold is automatically limited to the value of the maximum
and vice versa.

Reverse-power protection rP max


c this function calculates the value of the total active power on the three phases
c the function is activated when the total active power of the three phases flows in
the direction opposite that set by the user is greater than the pickup threshold (1)
for a time greater than the time delay (2).
Note:
The direction of flow is set by the user in the "Power sign" section of the "Micrologic setup"
menu under "History, maintenance and settings".
c + corresponds to the normal direction of flow, i.e. from the top terminals on the circuit breaker
to the bottom terminals
c - is the opposite.

If the voltage protection functions are


activated and the voltage measurement
inputs are still energised, it is impossible to
reset and close the circuit breaker.

Minimum and maximum-frequency protection F min.


and F max
These functions monitor the value of the frequency on the distribution system.

Phase-rotation alarm
This alarm is activated if two of the three phases are inverted.
Note:
The alarm is activated following a fixed 300-millisecond time delay. If one of the phases is
absent, the alarm will not operate. If the 400 Hz frequency is set, the alarm cannot be
activated.

29

Micrologic H

Schneider Electric

Overview of functions

Load shedding
and reconnection

For the pickup and dropout thresholds and


time delays, see the technical appendix.

Load shedding and reconnection depending on current

E71754A

The pickup curve for load shedding and reconnection depending on current is
parallel to the LT I2t and Idmtl curves. If a "without long-time protection" rating plug
is installed, the load shedding/reconnection function based on current cannot be
activated.
c I2t protection: the neutral is taken into account
c Idmtl: the neutral is not taken into account.
This function does not trip the circuit breaker, but can be used to set off an alarm
linked to an M2C or M6C contact (disconnection and reconnection of non-priority
loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
t
Long-time
protection
curve

3
1
4
2

1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.

Load shedding and reconnection depending on power

E60249B

Load shedding and reconnection depending on power calculates the total active
power on the three phases. This function does not trip the circuit breaker, but can
be used to set off an alarm linked to an M2C or M6C contact (disconnection and
reconnection of non-priority loads).
The load-shedding and reconnection function is determined by thresholds and time
delays.
t

3
1
4
2

1: pickup threshold
2: pickup time delay
3: dropout threshold
4: dropout time delay
The pickup threshold is always greater than or equal to the dropout threshold.

30

Micrologic H

Schneider Electric

Measurements
Current and voltage

Instantaneous current

For the setting ranges and measurement


accuracies, see the technical appendix.

Micrologic H control units offer two, non-exclusive measurement possibilities.


c on the bargraph display on the main screen
The instantaneous current of the most heavily loaded phase is automatically
displayed in amperes for phases 1, 2, 3 and the neutral (depending on the neutral
protection settings). The bargraph indicates the percent load of the
three phases.
c in the I inst. section of the instantaneous currents
v display in amperes of the instantaneous currents I (rms) on phases I1, I2 and I3
and the neutral current IN, the ground-fault current Ig (Micrologic 6.0 H), the
earth-leakage current In (Micrologic 7.0 H)
v the maximum instantaneous currents are displayed and stored in memory
v the stored maximums can be reset at any time.

Demand current
c display of the demand current on phases I1, I 2, I 3 and the neutral IN
(depending on the type of distribution system)
c selection of the demand calculation method
c display of the interval over which the value is calculated
c the maximum demand values are displayed and stored in memory
c the stored maximums can be reset at any time.
Note:
The calculation method, the type of calculation window (fixed or sliding) and its duration
may be set in the "Metering setup" menu under "History, maintenance and setup".

Phase-to-neutral and phase-to-phase voltages


Micrologic H offers different voltage measurements:
c phase-to-phase voltages (rms) between phases U12, U23 and U31,
displayed in volts
c phase-to-neutral voltages (rms) between the phases and the neutral V1N, V2N
and V3N, displayed in volts.

Average voltage
Average Uavg of the instantaneous voltages between phases U12, U23 and U31.

Phase rotation
Displays the phase sequence.

Voltage unbalance
Display of the unbalance Uunbal between the three phase-to-phase voltages,
displayed as a percentage.
E71742A

To display the phase-to-neutral voltages,


select the "3 4w 4CT" option in "System
type" in the "Metering setup" menu under
"History, maintenance and setup".

U
E max

U avg

c from:
v U avg is the average value of the rms voltages of the
three phases
U avg =

U12

U23

U31

U12 + U23 + U31


3

31

Micrologic H

v E max is the maximum difference between the


voltage of each phase and U avg
c Micrologic H uses the two values above to calculate
the voltage unbalance
E max
U unbal =
U avg

Schneider Electric

Overview of functions

Measurements
Power, energy and frequency

For the setting ranges and measurement


accuracies, see the technical appendix.

Instantaneous power and power factor


Micrologic H offers a number of different measurements.
c total power measurements:
v instantaneous active power P in kW
v instantaneous reactive power Q in kvar
v instantaneous apparent power S in kVA
c measurement of the power factor PF.

Demand power
c display of the demand values for the active power P, reactive power Q and
apparent power S
c selection of the demand calculation method
c display of the interval over which the value is calculated
c the maximum demand values are displayed and stored in memory
c the stored maximums can be reset at at any time.
Note:
c the calculation method, the type of calculation window (fixed or sliding) and its duration may
be set in the "Metering setup" menu under "History, maintenance and setup".
c the synchronisation function (Synchro.Com) is available only with the COM communication
option; with this function, the demand power is determined on the basis of a signal
synchronised by the communication module.
c these settings apply to all demand powers (active power P, reactive power Q and apparent
power S). If the settings are modified, the demand values are systematically recalculated.

Energy
Micrologic H offers a number of different measurements:
c total energy:
v total active energy E.P in kWh
v total reactive energy E.Q in kvarh
v total apparent energy E.S in kVAh
c energy consumed (Energy in), positively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
c energy supplied (Energy out), negatively incremented:
v active energy E.P in kWh
v reactive energy E.Q in kvarh
c energy values can be reset.
Note:

c the Energy in and Energy out values are incremented according to the power sign set
in the "Metering setup" menu under "History, maintenance and setup".
c as standard, the total calculated energy values are "absolute total values".
They represent the sum of the energy in and out values:
v EP = EP in + EP out
v EQ = EQ in + EQ out
c as an option (access exclusively via the COM communications option), energy can be
calculated algebraically:
v EP = EP in - EP out
v EQ = EQ in - EQ out
These values are called "signed" energies.

Frequency
The frequency of the distribution system is displayed in Hz.

32

Micrologic H

Schneider Electric

Harmonic measurements
Origin and effects

Harmonics represent the most common power problem encountered in todays


electrical installations.
When harmonics are present, the current or voltage waveform is distorted, i.e. it is
no longer perfectly sinusoidal.
A distorted current or voltage waveform disturbs the distribution of electrical power
and power quality is not optimum.

Definition of harmonics
A periodic signal is a combination of:
v the original sinusoidal signal at the fundamental frequency
v other sinusoidal signals (the harmonics) with frequencies that are whole-number
multiples of the fundamental frequency
v a DC component, where applicable.
Any periodic signal can therefore be represented as the sum of a number of terms:

y(t) = Yo + Yn r sin(nt - n)
E89243B

n=1

I peak
Total

I rms

Fundamental
50 Hz

I1

Harmonic
3 (150 Hz)

I3

Harmonic
5 (250 Hz)

I5

Harmonic
7 (350 Hz)
Harmonic
9 (450 Hz)

I7
I9

where:
c Yo is the value of the DC component (generally equal to zero and considered as
such hereinafter)
c Yn is the rms value of the nth harmonic
c is the angular frequency of the fundamental
c n is the phase displacement of the harmonic component at t = 0.
A harmonic of order n, referred to as the nth harmonic, is the sinusoidal
component of a signal with a frequency that is n times higher than the fundamental
frequency.
For example, the current and voltage waveforms distributed on the European
electrical power grid have the following characteristics:
c the fundamental frequency is 50 hertz (Hz)
c the 2nd harmonic has a frequency of 100 Hz
c the 3rd harmonic has a frequency of 150 Hz
c the 4th harmonic has a frequency of 200 Hz
c
A distorted waveform is the result of superimposing the various harmonics on the
fundamental.
The figure opposite shows a current distorted by harmonics.

33

Micrologic H

Schneider Electric

E89247B

Overview of functions

Standby generator
set

Ina

Rectifiers,
Arc furnaces,
Welding machines

Inb

Variable-speed
drives

Ind

Fluorescent or
discharge lamps

Power-factor
correction

HV/LV

Harmonic measurements
Origin and effects

Origin of harmonics
Harmonics are caused by non-linear loads.
A load is said to be non-linear when the current that it draws does not have the
same waveform as the voltage. Typical examples of non-linear loads are those
using power electronics. Such loads are increasingly numerous and their share in
overall electrical consumption is growing.

A
In and
distorted
voltage
Harmonic disturbances
transmitted to distribution
system and other users

Ine

Devices using rectified


current (televisions,
computers, etc.)

Linear loads
(do not cause
harmonics)

Examples are:
c industrial equipment including welding machines, arc furnaces, induction
furnaces, rectifiers, etc.
c variable speed drives for asynchronous or DC motors
c office equipment including computers, photocopy machines, fax machines, etc.
c household equipment including televisions, microwave ovens, neon lighting,
UPSs, etc.
Non-linear phenomena may also be caused by the saturation of transformers and
other equipment.

Effects of harmonics
The flow of harmonics in distribution systems can cause serious problems:
c increased currents flowing in the system and overloads
c additional losses and premature ageing of equipment
c disturbances to loads due to voltage harmonics
c disturbances in communication networks.
The above effects can also have major financial impact due to:
c the cost of equipment (premature replacement, oversizing)
c increased power losses and the need to subscribe to higher power levels
c losses in productivity (unnecessary tripping of protection devices).

34

Micrologic H

Schneider Electric

What is an acceptable level of harmonics?


The presence of harmonics in a distribution system should be assessed:
c as a preventive measure, to gain information on the system and detect any drift
c as a corrective measure, to diagnose a disturbance or check the effectiveness of
a solution.
Harmonic disturbances are subject to a number of standards and regulations:
c compatibility standards designed for public utilities:
v low voltage: IEC 61000-2-2
v medium voltage: IEC 61000-2-4
c electromagnetic compatibility (EMC) standards:
v for loads drawing less than 16 A: IEC 61000-3-2
v for loads drawing more than 16 A: IEC 61000-3-4
c utility recommendations for installations.
A number of international studies have produced data used to estimate the typical
harmonic values encountered in utility distribution systems. Below is a table
presenting the levels of harmonics that, in the opinion of many utility companies,
should not be exceeded.
Voltage individual harmonics of even and odd orders for:
c low-voltage (LV) systems
c medium-voltage (MV) systems
c extra high voltage (EHV) systems.

Odd harmonics (not multiples of 3)


Order n
5
7
11
13
17
19
23
25

LV
6
5
3.5
3
2
1,5
1.5
1.5

MV
6
5
3.5
3
2
1.5
1
1

EHV
2
2
1.5
1.5
1
1
0.7
0.7

Odd harmonics (multiples of 3)


Order n
3
9
15
21
>21

LV
5
1.5
0.3
0.2
0.2

MV
2.5
1.5
0.3
0.2
0.2

Even harmonics
EHV
1.5
1
0,3
0.2
0.2

Order n
2
4
6
8
10
12
>12

LV
2
1
0.5
0.5
0.5
0.2
0.2

MV
1.5
1
0.5
0.2
0.2
0.2
0.2

EHV
1.5
1
0.5
0.2
0.2
0.2
0.2

Note:
The individual harmonic content of a harmonic of order n is defined as the percentage of
its rms value with respect to the rms value of the fundamental. This value is displayed on
the graphic screen of the Micrologic H.

Which harmonics are we concerned with?


c individual harmonics of odd orders at low frequency
c mainly order 3, 5, 7, 11 and 13.

35

Micrologic H

Schneider Electric

Overview of functions

Harmonic measurements
Quality indicators

Micrologic H control units can quantify and evaluate the harmonic distortion of
current and voltage waves using the quality indicators listed below:
c measurement of the fundamental signal
c phase displacement of the fundamental signals
c harmonic distortion THD and thd
c cos
c power factor
c K factor
c distortion power
c distortion factor
c crest factor
c amplitude spectrum of even and odd harmonics up to order 31
c displacement spectrum with respect to V1N of even and odd harmonics up to
order 31.
These indicators are the indispensable tools used to determine any required
corrective action.

Access to quality indicators


The quality indicators may be accessed on the Micrologic H screen and/or via the
communication module.

Quality
indicator
measurement of
the fundamental
phase displacement of
the fundamental
harmonic distortion
THD and thd
cos
power factor
K factor
distortion power
distortion factor
crest factor
amplitude spectrum of
odd harmonics up to order 31
amplitude spectrum of
even harmonics up to order 31
displacement spectrum
with respect to V1N of
even and odd harmonics
up to order 31

36

Micrologic H

On the Micrologic H
screen

Via the
communication
module

c
c
-

c
c
c
c
c
c
c

Schneider Electric

Fundamental
Micrologic H control units can determine the value of the fundamental signals for:
c currents: I1, I2, I3 and IN (in amperes)
c voltages:
v phase-to-neutral V1N, V2N, V3N (in volts)
v phase-to-phase U12, U23, U31 (in volts)
c power:
v active P (kW)
v reactive Q (kVAR)
v apparent S (kVA).

Current and voltage rms values


c the rms current is the square root of the sum of the squares of the rms voltage
values for each harmonic from the fundamental to an infinite order.

Irms =

n=1 n

c the rms voltage is the square root of the sum of the squares of the rms current
values for each harmonic from the fundamental to an infinite order.

Urms =

n=1

Total harmonic distortion of current THD(I)


The total harmonic distortion of current is the ratio of the square root of the sum of
the squares of the harmonic currents from the 2nd to an infinite order to the
fundamental current.

I
THD(I) =

n=2 n

Ifund

THD(I) =

( )Irms

Ifund

Note:
v Ifund is the fundamental current.
v Irms is the rms current.

Distortion is expressed as a percentage and may exceed 100%.


Defined by standard IEC 61000-2-2, total harmonic distortion THD(I) is a single
value that expresses the distortion of the current flowing at a given point in a
distribution system.
c Micrologic H control units measure the THD for currents I1, I2, I3 and IN
(in amperes), taking into account harmonic orders up to 31.
c The total harmonic distortion of current characterises the distortion of the current
waveform.
c Loads causing distortion are identified by measuring the THD(I) on the incoming
and outgoing circuits.
c THD(I) values measured and the corresponding phenomena in an installation.
v THD(I) under 10% is considered normal. There is no particular risk of
malfunctions.
v THD(I) between 10 and 50% signals a significant level of harmonic disturbance.
There is a risk of temperature rise, which means that cables and sources must be
oversized.
v THD(I) greater than 50% signals major harmonic distortion. Malfunctions are
probable. An in-depth analysis and the installation of compensation equipment is
required.

37

Micrologic H

Schneider Electric

Overview of functions

Harmonic measurements
Quality indicators

Total harmonic distortion of voltage THD(U)


The total harmonic distortion of voltage is the ratio of the square root of the sum of
the squares of the harmonic voltages from the 2nd to an infinite order to the
fundamental voltage.

n=2

U
THD(U) =

Ufund

Note:
Ufund is the fundamental voltage.

Distortion is expressed as a percentage and may exceed 100%.


Defined by standard IEC 61000-2-2, total harmonic distortion THD(U) is a single
value that expresses the distortion of the voltage at a given point in a distribution
system.
c Micrologic H control units measure the THD for:
v phase-to-neutral voltages V1N, V2N, V3N (in volts)
v phase-to-phase voltages U12, U23, U31 (in volts)
taking into account harmonic orders up to 31.
c Total harmonic distortion of voltage characterises the distortion of the voltage
waveform.
c THD(U) values measured and the corresponding phenomena in an installation:
v THD(U) under 5% is considered normal.
There is no particular risk of malfunctions.
v THD(U) between 5 and 8% signals a significant level of harmonic disturbance.
Malfunctions may occur.
v THD(U) greater than 8% signals major harmonic distortion. Malfunctions are
probable. An in-depth analysis and the installation of compensation equipment is
required.

38

Micrologic H

Schneider Electric

Total harmonic distortion of current thd(I)


The total harmonic distortion of current is the ratio of the square root of the sum of
the squares of the harmonic currents from the 2nd to an infinite order to the rms
current.

I
thd(I) =

n=2 n

Irms

Note:
Irms is the rms current.

c Micrologic H control units measure the thd(I) for currents I1, I2, I3 and IN, taking
into account harmonic orders up to 31.
Defined by standard IEC 61000-2-2, total harmonic distortion thd(I) is a single
value that expresses the distortion of the current flowing at a given point in a
distribution system.

Total harmonic distortion of voltage thd(U)


The total harmonic distortion of voltage is the ratio of the square root of the sum of
the squares of the harmonic voltages from the 2nd to an infinite order to the rms
voltage.
2

thd(U) =

n=2

Urms

Note:
Urms is the rms voltage.

c Micrologic H control units measure the thd(U) for:


v phase-to-neutral voltages V1N, V2N, V3N (in volts)
v phase-to-phase voltages U12, U23, U31 (in volts) taking into account harmonic
orders up to H31.

39

Micrologic H

Schneider Electric

Overview of functions

Harmonic measurements
Quality indicators

Cos
Cos is the ratio between the active power Pfund and the apparent power Sfund of
the fundamental (1).

cos =

Pfund
Sfund

Note:
v Pfund is the active power of the fundamental.
v Sfund is the apparent power of the fundamental.

Cos pertains exclusively to the fundamental frequency. Consequently, if there are


harmonics, the value of the cos is not the same as that of the power factor.

Power factor PF
The power factor is the ratio between the active power P and the apparent power S.

P
S

PF =

Note:
v P is the active power.
v S is the apparent power.
v the power factor must not be confused with the cos . The power factor is equal to the
cos only when the signal is perfectly sinusoidal (no harmonics).

c if the measured power factor is not equal to the cos (the power factor is lower),
that may be an initial indication of harmonic disturbances in an installation.
c the power factor PF is the means to evaluate the oversizing required for the
power sources in an installation.
c there is a relation between the power factor and the total harmonic distortion of
current THD(I). When the voltage signal is (virtually) sinusoidal, the power factor
may be roughly calculated using the equation below:

cos

PF z

1 + THD(I)

E89246B

When plotted, the above equation produces the graph below showing the PF to
cos ratio, depending on the THD(I)
PF/cos
1,2
1
0,8
0,6
0,4
0,2

40

50

Micrologic H

100

150

THD(I) (%)

Schneider Electric

K factor
The K factor is a quality indicator that indicates high-order harmonics.

n
n=2

K factor =

Irms

Note:
I is the amplitude of the current.

The K factor is used to:


c calculate temperature rise in the busbars
c size the transformers for non-linear loads.

Distortion power
When there are harmonics, the relation S2 = P2 + Q2 is no longer valid.
The distortion power D is defined by the equation below:

D=

S 2 - P 2 - Q2

Distortion factor
The distortion factor is the relation between the power factor and the cos .

Crest factor
The crest factor is the relation between the peak value of the current or voltage and
the corresponding rms value.

Crest factor =

Ipeak
Irms

or crest factor =

Upeak
Urms

Note:
v Irms is the rms current.
v Urms is the rms voltage.

c possible values:
v for a sinusoidal signal, the crest factor is equal to r
v for a non-sinusoidal signal, the crest factor may be less than or greater than r.
c the crest factor is used to characterise the capacity of a source (UPS or
generator) to supply high instantaneous currents. In particular, it draws attention to
the presence of exceptional peak values with respect to the rms value.
Computer equipment, for example, draws highly distorted current with a crest factor
that can reach 3 or even 5.
c typical crest factors for the currents drawn by non-linear loads are much higher
than r. They are often equal to 1.5 or 2 and can reach 5 in critical cases.
c a very high crest factor means that there can be high temporary overcurrents,
which, when detected by the protective devices, may result in nuisance tripping.

41

Micrologic H

Schneider Electric

Overview of functions

Harmonic measurements
Quality indicators

The communication module can be used to FFT amplitude spectrum of odd harmonic
determine for each harmonic order up to 31: orders from 3 up to 31
Each type of distorting device has its own harmonic-current "fingerprint", with
c the amplitude spectrum
c the displacement spectrum with respect to different amplitudes and displacements.
These values, in particular the amplitude for each harmonic order, are essential for
the phase-to-neutral voltage V1N.

E89245A

the analysis of power quality.


c FFT (Fast Fourier Transform) frequency spectrum
The Micrologic H control unit can display the FFT amplitude spectrum of odd
harmonics from the 3rd up to 31st.
The Micrologic H control unit presents the amplitude of each harmonic order with
respect to its frequency in the form of a histogram, called a spectral analysis.

H%

s(t)
1

100

33
20
0

6 h

Above is an example of the spectral analysis of a square-wave signal.


c harmonic content of the nth harmonic for the phases I1, I2, I3
The individual harmonic content of a harmonic of order n is defined as the
percentage of its rms value with respect to the rms value of the fundamental:

in (%) = 100 In or un (%) = 100 Un


Ufund
Ifund
Note:
v Ifund is the fundamental current.
v Ufund is the fundamental voltage

c harmonic content of the nth harmonic for neutral current.


The individual harmonic content of a harmonic of order n is defined as the
percentage of its rms value with respect to the rms value of the Neutral:

in (%) = 100 In or un (%) = 100 Un


IN rms
UN rms
Note:
v IN rms is the Neutral rms current.
v UN rms is the Neutral rms voltage.

c the Micrologic H control unit indicates the FFT amplitude spectrum and the
individual distortion level for harmonic orders from 3 to 31 for:
v each current I1, I2, I3 and IN
v each phase-to-phase voltage U12, U23 and U31.
c the Micrologic H control unit also indicates for each current or voltage the
corresponding level of total harmonic distortion THD (thd for Neutral current).

42

Micrologic H

Schneider Electric

Waveform and waveform capture

The communication module may be used to:


c set up "Measurement" or "Protection"
alarms
c capture and analyse waveforms; capture
may be tripped by the alarms
c captured waveforms are recorded over 4
cycles (resolution of 64 points per cycle).

Micrologic H control units can capture and store current and voltage waveforms
using digital sampling techniques similar to those used in oscilloscopes.
Waveform capture is the means to detect weak points in the system and the
equipment. Using the information available in the captured waveform, it is possible
to determine the level of harmonics as well as the direction and amplitude of the
flow of harmonic power.
c users of Micrologic H control units can record manually via the keypad the
following waveforms:
v the four currents I1, I2, I3 and IN
v the three phase-to-neutral voltages V1N, V2N and V3N.
c waveforms may be displayed on the graphic screen of Micrologic H control units.
The recording takes place over one cycle with a measurement range of 0 to 1.5 In
for current and 0 to 690 volts for voltage. The resolution is 64 points per cycle.

43

Micrologic H

Schneider Electric

Overview of functions

Alarms

For information on the communications


option and the portable test kit, see the
respective user guides.

c an alarm may be viewed using:


v the "Alarm history" menu
v the COM communications option
v the portable test kit.
c the commands in the "Protection" menu are used to attribute a specific operating
mode to each of the protection functions:
v OFF: protection disabled
v Alarm: the function issues an alarm, but does not trip the circuit breaker
v Trip + Alarm: the function issues an alarm and trips the circuit breaker.
c the protection functions against overloads (long time), short circuits (short time
and instantaneous) and ground faults (ground-fault and earth-leakage currents)
automatically result in tripping and cannot be deactivated (Trip mode only).
c the "I t Alarm" and phase rotation alarms can be set exclusively to OFF or Alarm
mode.
c the other protection functions for current, voltage, power and frequency may be
set to any of the three modes, OFF, Alarm or Trip + Alarm.
c the load shedding and reconnection function may be set to ON or OFF.
c the resettable alarms linked to device tripping are activated when the Ir, Isd/Ii
or I t thresholds are overrun.
The Ir alarm is reset one second after tripping. The Isd/Ii and t alarms are reset by
pressing the
button.

E71744B

Different pickup and dropout thresholds


Current protection
Pickup

T1

Dropout

T2

E71745B

Other alarms

Identical pickup and dropout thresholds

T2

I t Alarm
II unbal
I 1 max
I 2 max
I 3 max
N max
U min
U max
U unbal

Other protection

Ir, Isd, Ii, I alarms


Other alarms

Trip + Alarm

c delayed alarms are activated when the pickup and dropout thresholds are
overrun and the corresponding time delays have expired.

Voltage protection
T1

Alarm

c
c
c

Current protection

Ir, Isd, Ii, I alarms

Pickup /
Dropout

Off

Ir
Isd / li
It

rP max
F min
F max
Phase rotation

Shedding/reconnection
current I
power P

Off

Alarm

Trip + Alarm

c
c
c
c
c
c

c
c
c
c
c
c

c
c
c
c
c

Off

Alarm

Trip + Alarm

c
c
c

c
c
c

c
c
c

Off

Alarm

Trip + Alarm

c
c
c
c

c
c
c
c

c
c
c

Off

On

c
c

c
c

c history logging
v Alarm mode: as soon as a given protection threshold is overrun, an alarm is
recorded in the "Alarm history"
v Trip mode: as soon as a given protection threshold is overrun, the circuit breaker
trips and the fault is recorded in the "Trip history".
c the "Protection setup" menu under "History, maintenance and setup" is used to
enable or disable the Trip mode that is displayed in the protection-setting screens.
On leaving the factory, the protection functions are set to Alarm mode.
c the "M2C / M6C contacts" menu under "History, maintenance and setup" is used
to link an M2C or M6C contact to an alarm. M2C and M6C contacts may not be
used together. They require a 24 V external power supply.
c the COM communications module can be used to transmit alarms to a
supervisor.

44

Micrologic H

Schneider Electric

Optional M2C and M6C contacts

c available types of contacts:


v M2C: up to two contacts maximum, S1 and S2
v M6C: up to six contacts maximum, S1 to S6.

An alarm is issued if the Alarm or the


Trip + Alarm mode was set for the given
protection function.

c current protection:
c voltage protection:
c other protection:
v Ir
v U min
v F min
v U max
v F max
v Isd
v Ii
v U unbal.
v rP max
vIt
v phase rotation.
v I t Alarm
v I unbal
v I 1 max
v I 2 max
v I 3 max
v I N max.
c load shedding and reconnection:
v current I
v power P.
c latching settings:
v non-latching contact: the contact remains activated as long as the fault that
caused the alarm has not been cleared
v latching contact: the contact remains activated until it is reset ("Reset menu")
v time-delay contact: the contact remains activated for the duration of an adjustable
time delay or until it is reset ("Reset menu").
v locked to 1: the contact is forced to 1 for an automation test
v locked to 0: the contact is forced to 0 for an automation test.

Caution!
The M2C and M6C contacts require an
auxiliary power supply. See the "Power
supply" section in the technical appendix.

484

474

E60492A

Wiring diagram for M2C contacts.

S1 S2

E60494B

471

c contact operating diagram for long-time protection


Ir threshold

T1 tr delay

25

23

21

19

17

11

T2 = 1 sec
t
Ir LED

Press

Internal alarm
S1

S2

S3

24V 0V

S4

Non-latching contact
Time-delay
contact
Latching
contact

Com
Q1 Q2 Q3

S5

S6

delay 1 to 360 s

Reset possible before


end of delay
Reset possible
only after T2 = 1 s

E71914A

Isd, Ii or Ig pickup

tsd or tg delay

Isd, Ii or Ig LED

Press

Internal alarm
Non-latching contact
Time-delay
contact
Latching
contact

delay 1 to 360 s

Reset possible before


end of delay
Reset possible
only after pressing

c contact operating diagram for the other protection functions


E60493B

24

22

20

18

16

14

12

10

c contact operating diagram for short-time, instantaneous and ground-fault


protection

E60491C

Wiring diagram for M6C contacts

Pickup

Dropout

Internal alarm
Non-latching contact
Time-delay
contact
Latching
contact

45

Micrologic H

delay 1 to 360 s

Reset possible before


end of delay
Reset possible
only after T2

Schneider Electric

Overview of functions

Event histories

The interrupted currents are indicated in


terms of their peak values.

Trip history
c the trip history is the means to display at any time the parameters measured
during the last ten trips.
c for each trip, the following parameters are recorded:
v tripping cause
v trip threshold
v interrupted currents in amperes (only if an external power supply is present) for Ir,
Isd/Ii, Ig or In trips
v date
v time (hours, minutes and seconds).

Alarm history
c the alarm history is the means to display at any time the parameters measured
during the last ten alarms.
c for each alarm, the following parameters are recorded:
v alarm cause
v alarm threshold
v date
v time (hours, minutes and seconds).

Operation counter
This function is available only via the COM communications option.
c Micrologic H:
v stores and displays the total number of operations (incremented each time the
circuit breaker opens) since the initial installation of the circuit breaker
v stores and displays the total number of operations since the last reset.

Contact wear indication


This function can be used to:
c determine the condition of the most worn contact in the circuit breaker. A counter
is displayed on the screen. The contacts must be inspected each time the counter
reaches a hundred mark. The message "Not available or circuit breaker type not
defined" is displayed if the type of circuit breaker has not been defined. In this case,
see "Breaker selection" in the "Micrologic setup" menu under "History, maintenance
and setup".
c reset the indicator after changing the main contacts. Reset is also carried out via
"Breaker selection" in the "Micrologic setup" menu.
Note:
If the control unit is changed, the circuit breaker must be defined again. In this case, see
"Breaker selection" in the "Micrologic setup" menu under "History, maintenance and
setup".

46

Micrologic H

Schneider Electric

LEDs and display screens

Overload bargraph on
the main screen

Alarm

E89205A

E60444A

LED indicator

Micrologic 5.0 H

4260A
N 1 2 3

off

100

50

Signals overrun of the


long-time current setting
(1.125 x Ir).

The procedure required to reclose the


circuit-breaker following a fault trip is
presented in the circuit-breaker user guide.

Fault-trip indications
c control-unit status
The circuit breaker has tripped.
The control unit may or may not have an external power supply.
The voltage measurement inputs may be connected upstream or downstream.

Concerning the presence or absence of an


external power supply, see the "Power
supply" section in the technical appendix.

Micrologic 5.0 H

v control unit with an


external power supply
and with voltage
measurement input
connected upstream
E89207B

v control unit without an


external power supply
and with voltage
measurement input
connected downstream
E89206A

Caution!
The battery maintains the trip indications.
If no indications are displayed, check the
battery.

Signals the load level on


each phase as a
percentage of Ir.

Micrologic 5.0 H

Trip
22/11/1999
02:04:04
Umin
100V

Reset
by test/reset
button

A LED signals the type of


fault (Ir, Isd, Ii, Ig, In or
Ap).

47

Micrologic H

The type of fault is


signalled by a LED and
on the graphic display.

Schneider Electric

LEDs and display screens

Overview of functions

c fault-trip LEDs
c the LEDs indicate the type of fault that tripped the circuit breaker
c the LEDs are located in the upper part of the front panel (red Ir, Isd, Ii, Ig, I2n and
Ap LEDs)
c when activated, a LED remains ON until it is locally reset.

A number of simultaneous causes may


result in tripping. For example, a shortcircuit and a distribution-system voltage
under a set value.
The LED signalling the last fault
chronologically is the only one to remain
ON. E.g., the Ap LED may signal a voltage
drop under a set value where the voltage
drop was caused by a short-circuit.

Micrologic 5.0 H

Signals tripping following


overrun of the short-time
pickup Isd or the
instantaneous pickup Ii.

c Ig, In LED

c Ap LED

Micrologic 5.0 H

Signals tripping following


overrun of the groundfault pickup Ig or the
earth-leakage pickup In.

E89211A

Signals tripping following


overrun of the long-time
current setting Ir.

E89210A

The self-protection function (excessive


temperature, fault detected in ASIC power
supply or instantaneous self-protection built
into the device) trips the circuit breaker and
turns the Ap LED on.

Micrologic 5.0 H

c Isd, Ii LED
E89209A

E89208A

c Ir LED

Micrologic 5.0 H

Signals tripping due to:


c self-protection function:
v temperature
v ASIC power supply
v instantaneous pickup for circuit-breaker self
protection
c protection functions:
v current unbalance I unbal
v maximum current I 1 max, I 2 max, I 3 max, I N max;
v voltage unbalance U unbal
v maximum voltage U max
v minimum voltage U min
v reverse power rP max
v maximum frequency F max
v minimum frequency F min.

E60485A

c LEDs on buttons to access the menus


The activated LED indicates the menu for which the screen is displayed:
v "Metering"
v "History, maintenance and setup"
v "Protection".

48

Micrologic H

Schneider Electric

E89212B

COM communications option

Communication options
Chassis

COM module on
chassis (optional)

Digipact and ModBus are the indispensable elements when integrating Micrologic
H in the Digivision and SMS Powerlogic installation-management systems which
communicate via the BatiBus and ModBus protocols.
External gateways are available for communication over other networks, including
ProfiBus, Ethernet, etc.
The communications option makes possible the following remote functions:
c device identification:
v address
v device type
v control-unit type
v type of long-time rating plug

Circuit breaker

COM module on circuit breaker

(Infra Red)

c settings:
v reading of the dial settings
v fine adjustments within the range determined by the dial
v protection and alarm settings
v setup of the M2C / M6C contacts.

Operating and maintenance aids


c protection and alarm values:
v standard
v set.

Micrologic H
control unit

c measurement values:
v currents
v voltages, frequencies, power, etc.
c fault values:
v fault type
v interrupted current.
c histories and logs:
v trip history
v alarm history
v event history.
c indicators:
v contact wear, counters, etc.
v maintenance register.

49

Micrologic H

Schneider Electric

Setup

Setting up the optional


M2C / M6C contacts

Select the command

Select an alarm

S2

S1
S2

then

Ir

then
Select an alarm.

Confirm.

Set up each contact

Contacts
M2C / M6C

S1
S2

then
Select a contact.

50

Micrologic H

S2

E71604A

Setup
M2C / M6C

E71603A

c select the latching mode


E71602A

Setup

S2

Ir

Select a contact.

Select the command

E60226A

Alarm
type

E60146A

Note:
An alarm may be selected if the "Alarm" or "Trip + Alarm" mode was selected during setup of
the given protection function, in the "Protection" menu.
E71601A

Contacts
M2C / M6C
Alarm
type

S2

Mode

Mode

latching
contact

latching
contact

then
Select a latching mode:
c non-latching
c latching
c time-delay
c locked to 1
c locked to 0.

Confirm.

Schneider Electric

S2

E71607A

S2

E71606A

E71605A

c set the time delay for time-delay latching

S2

Mode

Mode

Mode

time delay

time delay

time delay

Delay

Delay

Delay

360s

350s

350s

then
Select the time delay.

Select the command

Confirm.

M2C / M6C

Reset

E60389A

Reset the contacts to 0


E60442A

M2C / M6C
Contacts

Adjust.

M2C / M6C

S1 0
S2 0

S1 1
S2 1

Reset (- / +)

Reset (- / +)
then

Reset the contacts to 0

51

Micrologic H

or cancel the reset,


then confirm.

Schneider Electric

Setting up the Micrologic


control unit

Setup

Prior to setting up the protection functions or carrying out measurements,


the following operations are required:
c selection of the display language
c entry of the date and time
c entry of the circuit-breaker type
c entry the power sign
c selection of the transformation ratio between the primary and secondary
windings if an auxiliary voltage transformer is installed
c entry of the rated frequency.

Select the command

Language

E71938B

Language

Select the display language


E71608A

Micrologic
setup

Language

Deutsch

English UK

English US

Espanol

English UK

Franais

Espanol

Italiano

Franais

Select.

Confirm.

To return to English
1. Return to the main
screen by pressing any
of the three buttons

2. Select the "History,


maintenance and setup"
menu by pressing

or press the button

3. Select the "Micrologic


setup" menu by moving
the cursor up on the first
menu. Move the cursor
down on the third menu
and confirm
by pressing

followed by any of the


three buttons

Select the command

Set the date and time

Micrologic
setup

Date

E71612B

Date

E71611B

c enter the date and time for time-stamping purposes in the trip and alarm
histories.
E71610B

Date / time

4. Select the "Language"


menu by moving the
cursor up on the first
menu.
Confirm by pressing

Date

01 / 01 / 2000

01 / 01 / 2000

01 / 01 / 2000

Time

Time

Time

18 : 30 : 03

18 : 30 : 03

18 : 30 : 03

If the time is set via a communications


module, any previous manual setting is
automatically erased.

then
Select the date.

then
Enter the day.

then
Enter the month.

c the resolution of the time setting is 20 ms.

52

Micrologic H

Schneider Electric

If time is not synchronised by


the supervisor via the communication
module, a drift of up to one hour per year
may be observed.

Date

E71614B

E71613B

Date

01 / 01 / 2000

01 / 01 / 2000

Time

Time

18 : 30 : 03

18 : 30 : 03

then

then

Enter the year.

Select the command

The circuit-breaker code is required to


identify the device and activate the contactwear counter.

Enter this code when setting up a new


control unit on the circuit breaker.
For a new device, the code is set to zero.

E71617C

Breaker
selection

Breaker
selection

Standard

Standard

Standard

UL
Circuit breaker

IEC
Circuit breaker

IEC
Circuit breaker

Masterpact

Masterpact

Masterpact

type
NT08N

Note this code if the control unit


must be changed (example 03E7).

type
NT H1

type
NT H1

03E7

03E7

03E7

H Logicxxxxxx

H Logicxxxxxx

H Logicxxxxxx

then

then

Select the standard.

Breaker
selection

then
Select the circuit breaker.

Choose and confirm.

E71619C

E71618C

When the main circuit-breaker contacts are


replaced, this code must be reset to zero.

Breaker
selection

E71616C

Circuit-breaker selection
E71615C

Micrologic
setup
Breaker
selection

Set the time in the same


manner.

Breaker
selection

E71620BC

Date and time are backed up by battery.

Breaker
selection

Standard

Standard

Standard

IEC
Circuit breaker

IEC
Circuit breaker

IEC
Circuit breaker

Compact NS

Compact NS

Compact NS

type
630b

type
630b

type
800

03E7

03E7

03E7

H Logicxxxxxx

H Logicxxxxxx

H Logicxxxxxx

then
Choose and confirm.

53

Micrologic H

then
Select the type.

then
Choose and confirm.

Schneider Electric

Select the sign of the power

Power
sign

Select.

Select the command

Power
sign

P+

P-

By default, Micrologic H uses P+ for the


power flowing from top to bottom terminals.
The selected direction of flow is valid for:
c measurement of power and the power
factor
c measurement of energy
c load shedding and reconnection
depending on power.

P+

Confirm.

Choose.

VT ratio

E71625A

Enter the voltage-transformation ratio


E71624A

Micrologic
setup
VT ratio

Power
sign

Primary
If the supply voltage for the control unit
exceeds 690 V, an external voltage
transformer must be installed.

VT ratio

E71626A

Micrologic
setup
Power
sign

E71644B

Select the command

E71643B

Setting up the Micrologic


control unit

E71642B

Setup

Primary

VT ratio
Primary

690V

690V

690V

Secondary

Secondary

Secondary

690V

690V

690V

To display the true voltage values, enter the


transformation ratio between the primary
and secondary voltages of the transformer.
Note that if Digipact display modules are
used, the rated distribution-system voltage
must be entered.

then
Select either the:
c primary voltage
c secondary voltage.

Select the command

Go on to the next setting.

Enter the voltage.

400Hz

If the phase-rotation protection function is


activated, the 400 Hz frequency may not be
selected. If the 400 Hz frequency is
selected, the phase-rotation protection
function is disabled.

Select.

54

System
frequency
50 - 60Hz

Choose.

Micrologic H

E71629A

System
frequency

E71628A

Enter the rated frequency


E71627A

Micrologic
setup
System
frequency

then

System
frequency
50 - 60Hz

Confirm.

Schneider Electric

Setting up the metering functions

Prior to setting up the protection functions or carrying out measurements,


the following operations are required:
c entry of the system type
c selection of the calculation mode for the demand current
c selection of the calculation mode for the demand power
c select the power sign
c select the sign convention for the power factor measurement.

Select the command

Select the system type

Metering
setup
System
type

The Micrologic H control unit offers three measurement options:


c 3 phases, 3 wires, 3 CTs (method using two wattmeters)
The currents on phases I1, I2 and I3 are displayed.
The current on the neutral IN is not displayed.
The phase-to-phase voltages U12, U23 and U31 are displayed.
The phase-to-neutral voltages V1N, V2N and V3N are not displayed.
c 3 phases, 4 wires, 3 CTs (method using three wattmeters)
The currents on phases I1, I2 and I3 are displayed.
The current on the neutral IN is not displayed.
The phase-to-phase voltages U12, U23 and U31 are displayed.
The phase-to-neutral voltages V1N, V2N and V3N are displayed.
c 3 phases, 4 wires, 4 CTs (method using three wattmeters)
The currents on phases I1, I2 and I3 are displayed.
The current on the neutral IN is displayed.
The phase-to-phase voltages U12, U23 and U31 are displayed.
The phase-to-neutral voltages V1N, V2N and V3N are displayed.

Caution!
The neutral current IN cannot be measured
with the "3-phase, 3-wire, 3-CT" and
"3-phase, 4-wire, 3-CT" types.
For a 3-pole device, the neutral,
if distributed, must be connected to
terminal VN of the Micrologic H control unit.
See the "Overview of functions" section for
information on the available types of
measurements.

3 4w
3CT

3 3w
3CT

Select.

Select the command

Thermal method based in I2t calculation.

System
type
3 3w
3CT

Confirm.

Choose.

Calculation
method

Current
demand

E89201C

Current
demand

E89200C

Select the calculation method for demand current


E71945C

Metering
setup
Current
demand

System
type

E71632A

System
type

E71631A

E71630A

Note:
It is advised not to use the "3-phase, 4-wire, 4-CT" type of measurement unless the neutral is
effectively connected to the control unit (four-pole circuit breaker with an external voltagemeasurement input).

Current
demand

Window type
sliding

Calculation
method
block
block
interval
interval
Window type
sliding

Calculation
method
block
interval
Window type
sliding

Interval

Interval

Interval

thermal

15 min
Select.

55

15 min
Adjust.

Micrologic H

15 min
Confirm.
Schneider Electric

Calculation
method
block
interval
Window type
sliding

Calculation
method
block
interval
Window type
sliding

Interval

Interval

Interval

20 min

Select.

Confirm.

Adjust.

Window type
sliding

Calculation
method
block
interval
Window type
sliding

Interval

Interval

Interval

15 min
Select.

Confirm.

Choose between:
c thermal
c block interval
c sync. to comms

Power
demand

E89220C

E89219C

15 min

15 min

Power
demand

E89221C

Sliding window:
power demand is refreshed
every 15 secondes.

Power
demand

Calculation
method
block
interval
Window type
sliding

thermal

Thermal method based on I2t calculation.

Power
demand

E89218C

E89217C

Power
demand
Calculation
method

The synchronisation function


"Synchro.Com" is available only with the
COM communication option. With this
function, the demand power is determined
on the basis of a signal synchronised by
the communication module.

Fixed window:
power demand is refreshed
at the end of the time interval.

20 min

Select the calculation method for demand power


E89216C

Metering
setup
Power
demand

Current
demand

Calculation
method
block
interval
Window type
sliding

15 min

Select the command

Current
demand

E89215C

E89213C

Current
demand

E89214C

Setting up the metering functions

Setup

Power
demand

Calculation
method
block
interval
Window type
sliding

Calculation
method
block
interval
Window type
fixed

Calculation
method
block
interval
Window type
fixed

Interval

Interval

Interval

15 min
Select.

56

15 min
Choose between fixed or
sliding.

Micrologic H

15 min
Confirm.

Schneider Electric

Calculation
method
block
interval
Window type
fixed

Calculation
method
block
interval
Window type
fixed

Interval

Interval

Interval

20 min

20 min

Select.

Confirm.

Adjust.

Sign
convention

E89227B

Sign
convention

E89226B

Set up the power-factor calculation


E89225B

Metering
setup
Sign
convention

Power
demand

Calculation
method
block
interval
Window type
fixed

15 min

Select the command

Power
demand

E98320A

E89223C

E89222C

Power
demand

Sign
convention

See page 106 for the description of power


factor sign conventions.

IEEE

Select.

57

IEEE alt.

Choose between IEEE,


IEEE alternate and IEC.

Micrologic H

IEEE alt.

Confirm.

Schneider Electric

Setup

Setting up the COM


communications option

Select the command

When a COM communications option is used, it is necessary to:


c set up the COM communications option
c authorise remote setting of the Micrologic control unit
c authorise remote control of the circuit breaker.

Com.
setup
Com.
parameter

Modbus
Com

E71725A

Modbus
Com

E71724A

E71723A

As soon as the Digipact or ModBus


communications option is connected, the
control unit recognises it and displays the
type of module on the graphic screen.
Automatic time updates are possible only
with the ModBus system.

View and set up the communications option

Address

Address

47

Address

45

45

Baud-rate

Baud-rate

Baud-rate

9600

9600

9600

Parity

Parity

Parity

None

None
then
Select an existing
parameter.

Modbus
Com

None

Adjust.

Confirm.

Adjust all the other parameters for the communications option in the same manner.

Address
Baud rate

DIGIPACT

MODBUS

(read only)

(read and set up)

1 - 255

1 - 47
9 600 bauds
19 200 bauds
Even
None

Parity

Select the command

The access code is a password that must


be provided by the supervisor prior to
accessing the Micrologic settings.

Remote
settings

E71728A

Remote
settings

E71727A

Authorise remote setup of Micrologic


E71726A

Com.
setup
Remote
settings

Remote
settings

Access
permit

Access
permit

Access
permit

No

Yes

Yes

Access
code

Access
code

Access
code

0000

0000

0000

then
Select existing setting.

58

Micrologic H

Choose.

Confirm.

Schneider Electric

Access
permit

Access
permit

Yes

Yes

Yes

Access
code

Access
code

Access
code

1000

Select the existing


access code setting.

1000

Confirm and proceed in


the same manner for the
other digits.

Enter the first digit.

Manual

It is possible to set circuit-breaker control to


local only ("Manual") or to local and remote
("Auto").

Press enter.

59

Micrologic H

Remote
control
Auto

Select Auto or Manual.

E71734A

Remote
control

E71733A

Authorise remote control of the circuit breaker


E71732A

Com.
setup
Remote
control

Remote
settings

Access
permit

0000

Select the command

Remote
settings

E71731A

Remote
settings

E71730A

E71729A

If the operator does not enter a specific


access code, the default access code is
0000 and is requested by the supervisor.

Remote
control
Auto

Confirm.

Schneider Electric

Fine adjustment of the long-time


I2t, short-time and instantaneous
settings using the keypad

Select the command.

Current
protection

I(A)
Trip

(A)

1000 A

long-time current setting Ir

1.0 s

long-time tripping delay tr

2000 A
0.2 s

short-time pickup Isd


short-time tripping delay tsd
instantaneous pickup Ii

I(A)

E60149A

E60275A

4000 A

I(A)

E60276A

E71738A

Protection settings

I(A)

Trip

Trip

Trip

1000 A

998 A

998 A

1.0 s

1.0 s

1.0 s

2000 A
0.2 s

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

4000 A

then

I(A)

Trip

Trip

998 A

998 A

1.0 s

1.0 s

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

Confirm.

E71657A

I(A)

Adjust the value.

E60277A

When all the settings have been adjusted,


quit the screen by pressing one of the
menu-access buttons. This saves the new
values.

E60277A

Select a setting.

Do you want
to save new
settings?
No
Yes

then
Adjust the other settings
and confirm.

60

Micrologic H

Quit the setting screen.

Confirm.

Schneider Electric

Select the command

Current
protection

Idmtl

(A)

Trip
long-time current setting Ir
long-time tripping delay tr
Idmtl protection:
DT, SIT, VIT, EIT, HVF
short-time pickup Isd
short-time tripping delay tsd
instantaneous pickup Ii

1.0 s

EIT
2000 A
0.2 s

Idmtl

(A)

E60278A

E71718A

4000 A

Change I(A)
settings with
Idmtl(A)?
No

Idmtl

(A)

E60151A

(A)

1000 A

Idmtl

(A)

Trip

Trip

1000 A

1000 A

1.0 s

1.0 s

EIT

VIT

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

Yes
then

then

(A)

Idmtl

Change the setting.

(A)

Trip

Trip

1000 A

1000 A

1.0 s

1.0 s

VIT

VIT

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

E71657A

Idmtl

Select a setting.

E60280A

Select yes.

E60279A

Idmtl

E71739A

Fine adjustment of the long-time


Idmtl, short-time and
instantaneous settings using
the keypad

Do you want
to save new
settings?
No
Yes

puis
Confirm.

61

Micrologic H

Adjust the other settings.

Confirm.

Schneider Electric

Protection settings

E89231A

Current
protection

E89230A

Select the command

Fine adjustment of the groundfault and earth-leakage protection


setting using the keypad
(A)

Trip

(A)
Trip

(A)
1200A

threshold

1200A

0.5s

time delay

0.5s

then

(A)

Trip

(A)

E89234A

E89233A

E89232A

Select a setting.

Trip

(A)
Trip

1198A

1198A

1198A

0.5s

0.5s

0.5s

then

(A)

Trip

(A)
Trip

(A)
Trip

1198A

1198A

1198A

0.4s

0.4s

0.4s

Adjust the value.

62

Go to the next setting.


E89236A

Confirm.
E89236A

When all the settings have been adjusted,


quit the screen by pressing one of the
menu-access buttons. This saves the new
values.

E89235A

Adjust the value.

Micrologic H

Confirm.

Quit the setting screen.

Schneider Electric

Setting the neutral protection

(A)

Caution!
Selection of the CT type determines the
"Ineutral" protection in the "Protection"
menu.
c "none" disables the neutral protection.
c "Internal" for a four-pole circuit breaker
provides access to the N/2, N and OFF
protection functions.
c "External" for a three-pole circuit breaker
provides access to the N/2, N, 1.6xN and
OFF protection functions.

three-pole

E89239B

Ineutral (A)

Neutral CT

Neutral CT

Internal

External

External

Protection

Protection

Protection

OFF

OFF

OFF

then

OFF: no neutral protection


N / 2: half neutral protection
N: full neutral protection

Ineutral (A)

Confirm.

E89242B

E89241B

Choose between:
c internal
c external
c none.

Ineutral (A)

Ineutral (A)

Neutral CT

Neutral CT

Neutral CT

External

External

External

OFF: no neutral protection


N / 2: half neutral protection
N: full neutral protection
1.6 x N: oversized neutral protection

Protection

Protection

Protection

N/2

N/2

OFF
then
Select.
E89242B

four-pole

Ineutral (A)

Neutral CT

Select.

E89240B

Type of
Possibles choices
circuit breaker

Ineutral (A)

Choose.

Ineutral (A)

Confirm.

E71657A

Ineutral

E89237B

Current
protection

E89238B

Using the keypad on the control unit

Select the command

Neutral CT
External

Do you want
to save new
settings?
no

Protection

N/2
Quit the setting screen.

yes

Confirm.

Note:
On four-pole circuit breakers, setting of the neutral using the keypad is limited by the dial
setting.

63

Micrologic H

Schneider Electric

Protection settings

E71661B

Setting the I , I unbal, I max, U min,


U max, U unbal, rP max, F min,
F max, and phase-rotation protection
functions using the keypad

Select the corresponding menu

Current
protection

Alarm

I unbal

type of protection
operating mode
(Off, Alarm or Trip)

Pick up

pickup threshold

(%)

I1 max

(A)

I2 max

(A)

I3 max

(A)

pickup time delay

Drop out
dropout threshold
dropout time delay

Specific case for It alarm


c only the following choices are available:
v On: activation of the alarm without fault tripping by the circuit breaker
v Off: alarm disabled.

IN max (A)
Voltage
protection

Example: Maximum voltage setting (U max)

(V)

Uunbal

(%)

Umax (V)
Off
Pick up

Other
protection

Fmin

(Hz)

Fmax

(Hz)

Alarm
Pick up

In trip mode, the dropout threshold is equal


to the pickup threshold.
The dropout time delay is fixed and equal
to 1 second.

Alarm
Pick up

690V

690V

5.00s

5.00s

5.00s

Drop out

690V
0.50s

Drop out

690V
0.50s

690V
0.50s

then

Umax (V)
Off
Pick up

Choose Off or Alarm.


E89294B

E60292B

Select the first setting.

Phase
rotation

Umax (V)

690V

Drop out

rPmax (W)

Umax (V)

E60293B

Umax

c select Alarm mode


E60171B

(V)
E60292B

Umin

Confirm.

Umax (V)
Trip
Pick up

690V

690V

5.00s

5.00s

Drop out
690V
0.50s

then
Select the first setting.

64

Micrologic H

Choose Trip.

Schneider Electric

E89293B

E89295B

Umax (V)

Umax (V)
Trip
Pick up

Do you want
to set the
protection to
Trip mode?

690V
5.00s

no
yes
then
Confirm.

If both the minimum and maximum


protection values are activated, the
minimum threshold is automatically limited
to the value of the maximum and vice
versa.

Alarm
Pick up

Alarm
Pick up

Alarm
Pick up

690V

690V

690V

5.00s

5.00s

5.00s

Drop out
690V

Drop out
685V

Drop out
685V

0.50s

0.50s

0.50s

Umax (V)

Adjust.

E71668A

E71668A

then
Select the existing
dropout threshold setting

When all the settings have been made,


quit the screen by pressing one of the
menu-access buttons.
This saves the new values.

Umax (V)

Confirm.

Umax (V)

Alarm
Pick up

Alarm
Pick up

690V

690V

5.00s

5.00s

Drop out

Drop out

685V

685V

0.50s

0.50s

E71657A

For protection tripped by a minimum value,


the dropout threshold is always greater
than or equal to the pickup threshold.

Umax (V)

E71667A

Umax (V)

E71666A

c set the pickup and dropout thresholds and time delays


E71665A

For protection tripped by a maximum value,


the dropout threshold is always less than or
equal to the pickup threshold.

Do you want
to save new
settings?
No
Yes

then
Set the other parameters.

65

Micrologic H

Quit the setting screen.

Confirm

Schneider Electric

Setting load
shedding / reconnection

Select the command

Load
shedding I
Load
shedding P

E71673B

Protection settings

Load
shedding

type of shedding (I or P)
operating mode (On, Off)

Pick up
pickup threshold
pickup time delay

Drop out
dropout threshold
dropout time delay

66

Micrologic H

Schneider Electric

Load
shedding

E71672A

Load
shedding

E71671A

E71670A

Example: Take load shedding / reconnection depending on power.

Load
shedding

Off

On

On

Pick up

Pick up

Pick up

1000kW

1000kW

1000kW

3600s

3600s

3600s

Drop out

Drop out
1000kW
10s

Drop out

1000kW
10s

1000kW
10s

then

Load
shedding

E71676A

Load
shedding

Confirm.

Select:
c Off: load shedding
disabled
c On: load shedding
enabled.
E71675A

E71674A

Select the first setting.

Load
shedding

On

On

On

Pick up

Pick up

Pick up

1000kW

1000kW

1000kW

3600s

3600s

3600s

Drop out
985kW

Drop out
980kW
10s

Drop out
985kW

10s

10s

then

Load
shedding

On

On

Pick up

Pick up

1000kW

1000kW

3600s

3600s

Drop out

E71657A

Load
shedding

Confirm.

Adjust.

E71677A

When all the settings have been made,


quit the screen by pressing one of the
menu-access buttons.
This saves the new values.

E71677A

Select the existing


dropout threshold.

Do you want
to save new
settings?

Drop out

985kW

985kW

10s

10s

No
Yes

then
Set the other parameters.

67

Micrologic H

Quit the setting screen.

Confim.

Schneider Electric

Metering

Current measurements

Only the measurements for the phase


(1, 2, 3) and neutral currents are displayed
on the main screen.

Continuous current measurement

3850A

E60187A

4260A

E60185A

E60184A

The neutral current is displayed if the


neutral CT is set to internal or external
(see "Ineutral (A)" settings in the "Current
protection" menu).

The bargraph displays the value in amperes of the most heavily loaded phase.

3410A

1 2 3

1 2 3

1 2 3

100

100

100

50

50

50

The
and
buttons may be used to display the currents on the three
phases. If the operator no longer uses the buttons for a few seconds, the bargraph
returns to the display of the most heavily loaded phase.

Select the command

I inst.

E60189A

c measure the instantaneous currents


E60188A

I inst.

I1, I2, I3, IN


Max

I1
I2

= 3410 A
= 4260 A

I3

= 3850 A

IN

200 A

13 A

then
Select.

View.

c check the instantaneous-current maximeter

I inst.

E60191A

Instant.

(A)

E60190A

Measure an instantaneous-current value

Imax

instant.

I1, I2, I3, IN


Max

I1
I2

= 5600 A
= 4800 A

I3

= 4700 A

IN

800 A

28 A

Reset ( - / + )
then
View.

Select.

68

Micrologic H

Schneider Electric

Imax

E60191A

E60192A

c reset the maximeter

Imax

instant.

instant.
I1
I2

=
=

0A
0A

I1
I2

= 5600 A
= 4800 A

I3
IN

=
=

0A
0A

I3

= 4700 A

IN

800 A

0A

28 A

Reset ( - / + )

Reset ( - / + )

Reset the maximeter or...

Select the command

(A)

c measure the demand currents

Demand

E71679A

Demand.

Measure a demand-current value


E71678A

cancel the reset.

Demand

I1, I2, I3, IN


Max

13min
I1 =

3950 A

I2 =

4270 A

I3 =

3890 A

IN =

340 A

then
Select.

69

View.

Micrologic H

Schneider Electric

Current measurements

Metering

Demand

E71681A

E71680A

c check the demand-current maximeter

Imax

Demand

I1, I2, I3, IN

15min

Max

I1 =

4020 A

I2 =

4450 A

I3 =

4300 A

IN =

600 A

Reset ( - / +)
then
Select.

View.

Imax

E71683A

E71682A

c reset the maximeter

Imax

Demand

Demand

15min

15min

I1 =

0A

I1 =

4020 A

I2 =

0A

I2 =

4450 A

I3 =

0A

I3 =

4300 A

IN =

0A

IN =

600 A

Reset ( - / +)

Reset the maximeter or...

70

Micrologic H

Reset ( - / +)

cancel the reset.

Schneider Electric

Voltage measurements

U (V)
Instant.

The phase-to-neutral voltages are


displayed if the selected system type is
3-phase, 4-wire (see page 55).

Average 3
Unbal 3
Phase
rotation

Uinst.
U12 =
U23 =
U31 =

400 V
404 V
401 V

U1N =
U2N =
U3N =

230 V
229 V
233 V

then
Select.

View.

U (V)

E71687A

E89258B

Measure the average voltage U avg

Uavg.
3

Instant.
Average 3

402 V

Unbal 3
Phase
rotation

then
Select.

View.

E89259B

Measure the voltage unbalance U unbal

U (V)
Instant.

E71689A

(V)

E89257B

E60193A

Measure an instantaneous-voltage value (U or V)

Select the command

Uunbal
3

Average 3

1%

Unbal 3
Phase
rotation

then
Select.

71

View.

Micrologic H

Schneider Electric

Voltage measurements

Metering

U (V)
Instant.

E89261A

E89260A

Determine the phase sequence

Phase
rotation

Average 3
Unbal 3
Phase
rotation

: 1, 2, 3

then
Select.

72

View.

Micrologic H

Schneider Electric

Power measurements

(kW)

E71690A

P
Instant.

Pinst.

E60199B

Measure an instantaneous-power value

Select the command

P, Q, S
Power
factor

To ensure reliable power and power-factor


measurements, the "Power sign" and "Sign
convention" parameters must be set.

Pinst.
P

(kW)
2180

(kvar)
-650

(kVA)
2280

then
Select.

View.

Pinst.

E71692A

E71691A

Measure the power factor

Power
factor

P, Q, S
Power
factor

1.00

then
Select.

Select the command

Measure a demand-power value

(kW)

Demand
P, Q, S

E71694B

Demand

c display the demand power


E71693A

View.

Demand
P

(kW)
2350

(kvar)
-820

(kVA)
2640

Max

then
Select.

73

View.

Micrologic H

Schneider Electric

Metering

Demand

E71696B

E71695A

c check the demand-power maximeter

Pmax

Demand

P, Q, S
Max

(kW)
2450

(kvar)
-800

(kVA)
2700
Reset (- / +)

then
Select.

View.

Pmax

E71698B

E71697B

c reset the maximeter

Pmax

Demand

Demand

(kW)
0

(kW)
2450

(kvar)
0

(kvar)
-800

(kVA)
0
Reset (- / +)

(kVA)
2700
Reset (- / +)

Reset the maximeter or...

74

Micrologic H

cancel the reset.

Schneider Electric

Energy measurements

Measure the energy values

To ensure reliable energy measurements,


the "Power sign" and "Sign convention"
parameters must be set.

Select the energy value to be measured:


c total energy
c energy in (positive component in the total energy)
c energy out (negative component in the total energy).

E (kWh)
E total
E in
E out
Reset
energy

then

E total

E in

E71702B

E71700B

Select.
E71701B

E out

E.P

(kWh)
20168

E.P

(kWh)
+21320

E.P

(kWh)
168

E.Q

(kvarh)
-2733

E.Q

(kvarh)
-2770

E.Q

(kvarh)
33

E.S

(kVAh)
22926

View the total energy


values.

View the energy


in values.

View the energy


out values.

E71703A

Reset the energy values

E (kWh)
E total
E in

Reset
Energy
Are you
sure ?

E out
Reset
Energy

E71705A

(kWh)

E71704A

E71699A

Select the command

To reset
energy
press
enter

No
Yes

then
Select.

75

then
Select yes or no.

Micrologic H

If yes, confirm.

Schneider Electric

Select the command

Waveform capture for currents I1, I2 and I3

Waveform

Waveform

I1,2,3

I1,2,3

I1

IN
U12,23,31

I2

I3

then
Select.

View.

Waveform

E89265A

E89264B

Waveform capture for neutral current IN

IN

I1,2,3
IN
U12,23,31

then
Select.

View.

E89266B

Waveform capture for voltages U12, U23 and U31

Waveform

E89267A

Harmonic

E89263A

Harmonic measurements
Waveform capture

E89262B

Metering

U12,23,31

I1,2,3
IN
U12,23,31

then
Select.

76

View.

Micrologic H

Schneider Electric

Fundamentals

E89268B

Fundament.

Fundament

(A)

U
P

(V)

I(A)
Fundament
I1

92 A

I2

= 126 A

I3

62 A

IN

1A

(W)

then
Select.

View.

Fundament

E89271B

E89270B

Measure the fundamental voltages

U(V)
Fundament

(A)

U
P

(V)
(W)

U12 =
U21 =
U31 =

281 V
333 V
276 V

V1N =
V2N =
V3N =

139 V
185 V
190 V

then
Select.

View.

E89272B

Measure the fundamental power values

Fundament

E89273B

Harmonic

E89269B

Measure the fundamental currents

Select the command

P,Q,S
Fundament

(A)

U
P

(V)

(kW)
-9

(kvar)
47

(kVA)
52

(W)

then
Select.

77

View.

Micrologic H

Schneider Electric

Harmonic measurements
THD

Select the command

Measure the total harmonic distortion (THD) of the current


(with respect to fundamental)

THD

ITHD(%)

(%)

I1

7.0 %

(%)

I2

5.8 %

I3

6.2 %

IN

2.1 %

then
Select.

View.

E89277B

Measure the total harmonic distortion (THD) of the voltage


(with respect to fundamental)
E89276A

THD

E89274A

Harmonic

E89275B

Metering

THD

(%)

(%)

UTHD(%)
U12 =
U23 =
U31 =

1.0 %
1.2 %
1.4 %

V1N =
V2N =
V3N =

2.2 %
2.0 %
2.0 %

then
Select.

78

View.

Micrologic H

Schneider Electric

thd

thd

Ithd (%)

(%)

I1

6.8 %

(%)

I2

7.2 %

I3

5.6 %

IN

8.1 %

then
Select.

View.

E89281B

Measure the total harmonic distortion (thd) of the voltage


(with respect to rms value)
E89280A

thd

E89278A

Harmonic

E89279B

Measure the total harmonic distortion (thd) of the current


(with respect to rms value)

Select the command

thd

(%)

(%)

Uthd (%)
U12 =
U23 =
U31 =

1.0 %
1.2 %
1.8 %

V1N =
V2N =
V3N =

2.0 %
2.8 %
2.6 %

then
Select.

79

View.

Micrologic H

Schneider Electric

Measure the amplitude spectrum of the current harmonics

FFT

FFT
(3,5,7,.,31)

(3,.,31)

U(3,5,7,.,31)

I2

(3,.,31)

I3

(3,.,31)

IN

(3,.,31)

Note :
FFT= Fast Fourier Transform

FFT

I1

I1 FFT
THD=6.3
8.0%

3 5 7 9 11
then

then

E89285B

Select.

Select a current.

I1 FFT

E89286B

Harmonic

E89284B

Select the command

E89283A

Harmonic measurements
FFT amplitude spectrum

E89282A

Metering

I1 FFT

THD=6.3
5.0%

THD=6.3
1.0%

3 5 7 9 11

23 25 27 29 31

View the 5th harmonic...

... and the other odd


harmonics up to the 31st.

80

Micrologic H

View the individual


distortion of the 3rd
harmonic

Schneider Electric

E89289B

FFT

E89288A

E89287A

Measure the amplitude spectrum of the voltage harmonics

FFT

(3,5,7,.,31)

U12

(3,.,31)

U(3,5,7,.,31)

U23

(3,.,31)

U31

(3,.,31)

U12 FFT
THD=3.2
3.0%

3 5 7 9 11
then

then
Select a voltage.

U12 FFT

E89291B

E89290B

Select.

U12 FFT

THD=3.2
23.0%

THD=3.2
0.0%

3 5 7 9 11

23 25 27 29 31

View the 5th harmonic...

81

Micrologic H

View the individual


distortion of the 3rd
harmonic

... and the other odd


harmonics up to the 31st.

Schneider Electric

Frequency measurements

Select the command

E60110A

Metering

F (Hz)

(Hz)

60.0

View.

82

Micrologic H

Schneider Electric

83

Micrologic H

Schneider Electric

Resetting fault indications

Caution!
If the circuit breaker remains closed and
the Ap LED remains ON after the reset,
open the circuit breaker and contact the
after-sales support department.

The fault indication is maintained until it is reset on the control panel.


Press the reset button.
E89292B

Maintenance

Micrologic 7.0 H

Fault
22/11/1999
02:04:04
Umin
100V

Reset
by test/reset
button

84

Micrologic H

Schneider Electric

Viewing the event histories

E71706A

Event
history
Trip
history

Trip
history

E71707A

Trip history

Select the command

Trip
22/11/1999
02:04:04
Umin
160V

U min
27/01/1999

Ir
27/06/1998

Ir
18/02/1998
then
Select a fault.

Select the command

Alarm
history
I2 max
27/01/1999

E71709A

Alarm
history

Alarm history
E71708A

Event
history

View.

Alarm
27/01/1999
13:06:09
I2 max 3400A

In max
23/03/1998
U max
12/02/1998
then
Select an alarm.

85

Micrologic H

View.

Schneider Electric

View and/or reset the operation counter

Event
history
Operation
counter

Number of
operations

Number of
operations

E71737A

Select the command

E71736A

Operation counter and


contact-wear indicator

E71735A

Maintenance

Number of
operations

Total

Total

Total

17824

17824

17824

Operations
since last
reset

Operations
since last
reset

Operations
since last
reset

6923

6923

Reset ( - / + )

Reset ( - / + )

Reset ( - / + )
then

Reset

Select the command

Check the wear of the contacts


E71710C

Event
history
Contact
wear

or cancel the reset,


then confirm.

Contact
wear

Contact wear is indicated from 0 to 900.


The contacts should be inspected every
time the counter reaches a multiple of 100.

59

86

Micrologic H

Schneider Electric

Checking/replacing the battery

E89248A

Check the control-unit battery


Micrologic 7.0 H

1 2 3

E71751A

Press and hold down the test button on the control unit to check the LEDs and the
battery. The battery information is displayed if the control unit is equipped with an
external power supply or if the circuit breaker is ON.
Battery fully charged
Battery half charged
No battery or must be replaced

Replacing the control-unit battery


2. remove the battery
E51443A

E60308A

1. remove
the battery cover

87

4. put the cover back


in place. Press the
battery-test button to
check the new battery.
E60481A

3. insert a new battery.


Check the polarity.

E60473A

If the battery must be replaced, use a new


battery with the Schneider part number
33593 (technical characteristics available
on the battery-slot cover).
Check its condition regularly by pressing
and holding down the test button on the
control unit for several seconds.

Micrologic H

Schneider Electric

Tests

Maintenance

Test the ground-fault (Micrologic 6.0 H) and earth-leakage


(Micrologic 7.0 H) protection functions
The circuit breaker must be supplied with power and closed for the test.

E89249A

Press the TEST button. The circuit breaker should trip.

5.0
logic
Micro

If the circuit breaker does not trip, contact the after-sales support department.

Mini test kit and portable test kit

Refer to the manual that comes with the


test kits.

E89251A

E89250A

The test connector is used to connect the mini or the portable test kit to check that
the control unit is operating correctly.

5.0
logic
Micro

Micro

logic

5.0 H

88

Micrologic H

Schneider Electric

89

Micrologic H

Schneider Electric

Tripping curves

Technical appendix

Long-time I2t, short-time and instantaneous protection


Micrologic 5.0 H, 6.0 H, 7.0 H
E71753A

10 000
5 000

Ir = 0.41 x In

2 000
1 000
tr = 0.524 s

500
200
100
50
20
10
5
t(s)

Isd = 1.510 x Ir

2
1

I2t ON

.5

0.4
0.3

.2

0.2
0.1

.1
.05
.02
.01

0.4
0.3
0.2
0.1

I2t OFF

Ii = 215 x In . OFF

.005
.002
.001
.5 .7 1

3 4 5 7 10
x Ir

20

7 10
x In

20 30

Long-time Idmtl, short-time and instantaneous protection


Micrologic 5.0 H, 6.0 H, 7.0 H
E47587A

100 000

HVF

10 000
5 000
2 000
1 000
EIT

500
t(s)

200
100

VIT

50
SIT

20
10

DT

5
2
1
.5

.5 .7

4 5

10

20

I / Ir

90

Micrologic H

Schneider Electric

E46266A

Ground-fault protection - Micrologic 6.0 H


10 000
5 000
2 000

Ig = AJ x In (1)
1200 A max.

1 000
500
200
100
50
20
10
5
t(s)

I2t ON

2
1
.5
.2
.1
.05

It

0.4

0.4

0.3
0.2
0.1

0.3
0.2
0.1

OFF

.02
.01
.005
.002
.001
.05.07 .1

.2 .3 .4 .5 .7 1

7 10

200 300

I / In

91

Micrologic H

Schneider Electric

Technical appendix

Voltage measurements

Micrologic H is equipped with a three-phase voltage power supply that, with respect
to the distribution system, may be considered a delta load. The three-phase power
supply reinjects voltage on an open phase.
The voltage-protection functions react as indicated below.

Minimum-voltage protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit
reinjects voltage on the failed phase and measures a phase-to-phase voltage
higher than the actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
In diagram 2, the phase-to-neutral voltage is effectively zero and the measurement
indicates zero as well.
By limiting the pickup threshold of the minimum-voltage protection to the 80% 100% range of the rated distribution-system voltage, the differences between the
real voltages and the measured values are not significant and Micrologic will
operate under all circumstances in the expected manner.

Voltage-unbalance protection
This function is based on the measurement of the phase-to-phase voltages.
In diagrams 1, 3 and 4 on the next page, a fuse has blown. The control unit
reinjects voltage on the failed phase and measures a phase-to-phase voltage
higher than the actual voltage.
The phase-to-neutral voltage should be zero, but the value measured is not zero.
In diagram 2, the phase-to-neutral voltage is effectively zero and the measurement
indicates zero as well.
By limiting the pickup threshold of the voltage-unbalance protection to the 0% 20% range, the differences between the real voltages and the measured values are
not significant and Micrologic will operate under all circumstances in the expected
manner.

Phase failure
Detection of phase failure is not possible on the basis of the minimum-voltage and
voltage-unbalance protection functions.
The Micrologic power supply requires at least two phases (between 100 and 690 V).
In diagrams 1, 3 and 4, if two phases have failed, Micrologic H measures for the
three phases the value of the single voltage present (e.g. U12 = U23 = U31 = 410 V).

92

Micrologic H

Schneider Electric

E71916A

c diagram 1

Contactor
Fuses

Motor

Open

E71917A

c diagram 2
Contactor
Fuses

Motor

Open

E71918A

c diagram 3
Contactor

Motor

Open
Fuses

E71919A

c diagram 4

Load

Fuses

Other
measurement
and protection
systems

93

Micrologic H

Schneider Electric

Zone selective interlocking (ZSI)

E60450B

Technical appendix

Operating principle

c a fault occurs at point A


Downstream device no. 2 clears the fault and sends a signal to upstream device no.
1, which maintains the short-time tripping delay tsd or the ground-fault tripping
delay tg to which it is set.
c a fault occurs at point B
Upstream device no. 1 detects the fault. In the absence of a signal from a
downstream device, the set time delay is not taken into account and the device
trips according to the zero setting. If it is connected to a device further upstream, it
sends a signal to that device, which delays tripping according to its tsd or tg setting.

Note:
On device no. 1, the tsd and tg tripping delays must not be set to zero because this
would make discrimination impossible.
2

Connections between control units


A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
c Micrologic 5.0 A, 6.0 A, 7.0 A
c Micrologic 5.0 P, 6.0 P, 7.0 P
c Micrologic 5.0 H, 6.0 H, 7.0 H.
An interface is available for connection to previous generations of trip units.

Caution!
lf the protection function is not used on
circuit breakers equipped for ZSI
protection, a jumper must be installed to
short terminals Z3, Z4 and Z5. If the jumper
is not installed, the short-time and groundfault tripping delays are set to zero,
whatever the position of the adjustment
dial.

c maximum impedance: 2.7 / 300 metres


c capacity of connectors: 0.4 to 2.5 mm2
c wires: single or multicore
c maximum length: 3000 metres
c limits to device interconnection:
v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to
a maximum of ten inputs
v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and
to an input ZSI - IN CR (Z4) or GF (Z5).
E71912A

Terminals Z1 to Z5 correspond to the


identical indications on the circuit-breaker
terminal blocks.

Wiring

upstream
circuit-breaker

Z1
Z2
Z3
Z4
Z5

tsd = 0.3

point B

Z1
Z2
Z3
Z4
Z5

tsd = 0. 2

point A

Z1
Z2
Z3
Z4
Z5

downstream
circuit-breaker

Z1
Z2
Z3
Z4
Z5

Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.

94

Micrologic H

Schneider Electric

Power supply

Caution!
It is advised to use the AD power-supply
module rather than an off-the-shelf 24 V
power supply to ensure Class II insulation
on the front panel of the Micrologic H
control unit.

AD power-supply module
The AD power-supply module provides auxiliary 24 V DC power for the control-unit
functions listed below:
c graphic display:
v device OFF or not supplied
v the long-time, short-time, instantaneous and ground-fault protection functions
operate under all circumstances on their own power
c activation of an M2C programmable contact
The AD power-supply module is required to assign an M2C programmable contact
to an alarm.

The power supply must have the following


characteristics:
c output voltage 24 V DC
c DC ripple less than 5%
c power rating 5 W / 5 VA
c Dielectric withstand (input/output):
3 kV rms

The AD power-supply module can supply the following voltages:


c 110 V AC
c 220 V AC
c 380 V AC
c 24 / 30 V DC
c 48 / 60 V DC
c 125 V DC.

Battery module
Use of a BAT battery module, mounted in series with the AD power-supply module,
ensures a continous supply of 24 V DC power for 12 hours if the AD module fails.

Wiring diagrams
E60449A

v reliable or backed-up auxiliary system

L4
L3

AD 22

Input
AC
220V
t
OutpuC
24VD

0V

+
G2

G1

F2
+

F1
-

E60448A

v auxiliary system without back-up

H4

L4
L3

AD 22

H3

Input
AC
220V

0V

t
OutpuC
24VD

InputC
24VD

24
BAT

G2

G1

t
OutpuC
24VD

+
H1

H2

F1
-

F2
+

E60447A

c supply with the MC6 module


Q1 Q

2 Q3

25
21 23
17 19

L4
L3

AD 22

M6C

Input
AC
220V

0V

t
OutpuC
24VD

+
G2

G1

95

Micrologic H

Schneider Electric

Technical appendix

Power supply

Using the AD power-supply module


The 24 V DC external power-supply (AD module) is required for certain operating
configurations as indicated in the table below:
c yes means the power supply is required
c no means it is not required.

circuit breaker

closed

open

open

AC power present for Micrologic H

yes

yes

no

yes
no
no
no

yes
no
no
no

yes
yes
no
no

no

no

yes

M2C, M6C programmable-contacts option


display function
time-stamping function
circuit-breaker status indications and control
via communications bus
identification, settings, operation and maintenance aids
via communications bus

c if the 24 V DC external power supply (AD module) is used, the maximum cable
length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed
10 metres.
c the communications bus requires its own 24 V DC power source (E1, E2).
This source is not the same as the 24 V DC external power-supply module (F1-,
F2+).

Selection of the voltage-measurement inputs


The voltage-measurement inputs are standard equipment on the downstream
connectors of the circuit breaker.
It is possible to measure distribution-system voltage externally using the PTE
external voltage-measurement input option.
With this option, the internal voltage-measurement inputs are disconnected. The
PTE option is required for voltages greater than 690 V (in which case a voltage
transformer is required).
When the PTE option is implemented, the supply circuit of the voltagemeasurement input must be protected against short-circuits. Installed as close as
possible to the busbars, this protection function is ensured by a P25M circuit
breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
The supply circuit of the voltage-measurement input is reserved exclusively for the
control unit and must never be used to supply other circuits.

96

Micrologic H

Schneider Electric

Changing the long-time


rating plug

Select the long-time rating plug


A number of long-time rating plugs are available for Micrologic H control units.

Part number

Setting range for the Ir value

33542
33543
33544
33545

Caution!
Following any modifications to the longtime rating plug, all control-unit protection
parameters must be checked.

standard
0.4 to 1 x Ir
low setting
0.4 to 0.8 x Ir
high setting
0.8 to 1 x Ir
without long-time protection
c Ir = In for the short-time protection setting
c frequency protection not available
c load shedding / reconnection based on current not available

Change the long-time rating plug


Proceed in the following manner.
1. open the circuit breaker
2. open the protective
cover of the control unit
E89253A

E89252A

3. completely remove
the long-time rating plug screw

5.0
logic
Micro

Micro

4. snap out the rating


plug

logic

5.0 H

5. clip in the new rating plug

E89254A

6. refit the screw for the


long-time rating plug
5.0
logic
Micro

7. check and/or modify the


control-unit settings
E89255A

Caution!
If no long-time rating plug is installed, the
control unit continues to operate under the
following downgraded conditions:
c the long-time current setting Ir is 0.4
c the long-time tripping delay tr
corresponds to the value indicated by the
adjustment dial
c the earth-leakage protection function is
disabled
c the voltage-measurement inputs are
disconnected.

Micro

logic

5.0 H

alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr

(s) 4

2
1

8 12
16
20
24

.5 @ 6 Ir

alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

97

Micrologic H

tr

(s) 4

2
1

8 12
16
20
24

.5 @ 6 Ir

Schneider Electric

Technical appendix

Thermal memory

Thermal memory
The thermal memory is the means to take into account temperature rise and
cooling caused by changes in the flow of current in the conductors.
These changes may be caused by:
c repetitive motor starting
c loads fluctuating near the long-time protection settings
c repeated circuit-breaker closing on a fault.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.

Micrologic control units and thermal memory


All Micrologic control units are equipped as standard with a thermal memory.
c for all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend depend on the tr tripping delay:
v if the tripping delay is short, the time constant is low
v if the tripping delay is long, the time constant is high.
c for long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping
curves.

Short-time protection and intermittent faults


For the short-time protection function, intermittent currents that do no provoke
tripping are stored in the Micrologic H memory.
This information is equivalent to the long-time thermal memory and reduces the
tripping delay for the short-time protection.
Following a trip, the short-time tsd tripping delay is reduced to the value of the
minimum setting for 20 seconds.

Ground-fault protection and intermittent faults


The ground-fault protection implements the same function as the short-time
protection (see above).

98

Micrologic H

Schneider Electric

Data available via the COM


communications option

The COM communications option can be


used to remotely access the Micrologic H
measurement, setting, maintenance and
protection values.

Measurements
c currents
v instantaneous currents
v maximum and minimum instantaneous currents
v average instantaneous currents
v instantaneous-current unbalance per phase
v maximum and minimum instantaneous-current unbalance per phase
c demand current
v demand current per phase
v maximum and minimum demand current per phase since last reset
v prediction of demand current per phase
v time-stamping of demand-current maximums and minimums
c voltages
v phase-to-neutral and phase-to-phase voltages
v average phase-to-neutral and phase-to-phase voltages
v phase-to-neutral and phase-to-phase voltage unbalance
v maximum and minimum phase-to-neutral and phase-to-phase voltage unbalance
c active, reactive and apparent power per phase
c demand power
v demand power per phase
v maximum and minimum demand power per phase since last reset
v maximum and minimum recommended demand power per phase
v time-stamping of demand-power maximums and minimums
c energy
v total active and reactive energy
v positively incremented energy
v negatively incremented energy
c system frequency
c power factor
c reset date of demand currents, demand power and energy
c power quality indicators:
v instantaneous measurements together with maximums and minimums:
- fundamental apparent currents
- fundamental phase-to-neutral and phase-to-phase voltages
- fundamental rms currents
- fundamental active, reactive and apparent power per phase and total
- distortion power per phase and total
- THD and thd of the phase-to-neutral and phase-to-phase voltages
- THD and thd of the currents
- phase angle between the voltages and the currents
- K factors
- peak voltages
- peak currents
- phase angle between the voltages
- K factors averages
v demand K factors:
- demand K factors per phase
- maximum demand K factor per phase since last reset
- prediction of demand K factors
- time-stamping of demand K factor maximums per phase
v harmonics:
- phase-to-neutral and phase-to-phase voltage harmonic amplitudes
- current harmonic amplitudes
- phase-to-neutral and phase-to-phase voltage harmonic phase angle
- current harmonic phase angle
v monitoring of electrical parameters
v dates of last resets of minimums and maximums
v waveform capture
v event history file in the measurement module
v minimum and maximum file with time-stamping
v maintenance file in the measurement module
- minimum and maximum reset counters with time-stamping
- maximum demand-current reset counters with time-stamping
- maximum demand-power reset counters with time-stamping
- energy reset counters with time-stamping.

99

Micrologic H

Schneider Electric

Technical appendix

Data available via the COM


communications option

Setup / Maintenance
c setting of the control-unit date and time
c password for the measurement module
c control-unit ID code
c control-unit ID name
c selection of the measurement calculation algorithm
c sign convention for the active power
c total-energy measurement mode
c interval for the demand-current calculation window
c power quality indication
c demand-power calculation mode
c interval for the demand-power calculation window
c battery-charge indication
c trip and alarm histories
c operation counter and contact-wear indicator
c assignment and setup of programmable contacts
c event log and maintenance register
c power factor sign conventions
c monitoring parameters
c monitoring priorities levels
c waveform capture.

Protection
c circuit-breaker rated current
c type of neutral protection
c long-time I2t protection settings
c long-time Idmtl protection settings
c short-time protection settings
c instantaneous-protection settings
c ground-fault protection settings
c earth-leakage protection settings
c current-unbalance, It alarm and maximum-current protection settings
c voltage-protection settings
c setting for other protection functions.

100

Micrologic H

Schneider Electric

Threshold and time-delay settings

Long-time I2t and Idmtl protection


Type
Ir current setting
tr tripping delay

Range

Factory setting

Step

Accuracy

0.4 to In
0.5 to 24 s

maximum
maximum

1A
0.5 s

1.05 to 1.20 Ir
- 20 %, + 0 %

Short-time protection
Type
Isd pickup
tsd tripping delay

Range

Factory setting

Step

Accuracy

1.5 to 10 Ir
0 - 0.1 - 0.2 - 0.3 - 0.4 s

maximum
maximum

10 A
0.1 s

10 %

Instantaneous protection
Type
Ii pickup

Range

Factory setting

Step

Accuracy

2 to 15 In or off

maximum

10 A

10 %

Ground-fault protection on Micrologic 6.0 H


Type
Ig pickup
tg tripping delay

Range

Factory setting

Step

Accuracy

depends on rating
0 - 0.1 - 0.2 - 0.3 - 0.4 s

maximum
maximum

1A
0.1 s

10 %

Earth-leakage protection on Micrologic 7.0 H


Type

In pickup
t tripping delay

Range

Factory setting

Step

Accuracy

0.1 A
1 setting

- 20 %, + 0 %

60 -140 - 230 - 350 - 800 ms

maximum
maximum

Neutral protection
Type
three-pole device
four-pole device

Range

Factory setting

Off, N/2, N, 1.6xN


Off, N/2, N

off.
N/2

101

Micrologic H

Schneider Electric

Technical appendix

Threshold and time-delay settings

Current protection
Type
current unbalance I unbal
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
ground-fault I t alarm
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay
earth-leakage I t alarm
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

Range

Factory setting

Step

Accuracy

5% to 60%
5% of pickup threshold
1 s to 40 s
10 s to 360 s

60 %
pickup threshold
40 s
10 s

1%
1%
1s
1s

-10 %, +0 %
-10 %, +0 %
-20 %, +0 %
-20 %, +0 %

20 A to 1200 A
20 A to pickup threshold
1 s to 10 s
1 s to 10 s

120 A
pickup threshold
10 s
1s

1A
1A
0.1 s
0.1 s

+/- 15 %
+/- 15 %
-20 %, +0 %
-20 %, +0 %

30 A
pickup threshold
10 s
1s

0.1 A
0.1 A
0.1 s
0.1 s

-20 %, +0 %
-20 %, +0 %
-20 %, +0 %
-20 %, +0 %

In
pickup threshold
1500 s
15 s

1A
1A
1s
1s

6.6%
6.6%
-20 %, +0 %
-20 %, +0 %

0.5 A to 30 A
0.5 A to pickup threshold
1 s to 10 s
1 s to 10 s
maximum current I 1 max, I 2 max, I 3 max, I N max
Pickup threshold
0.2 In to In
Dropout threshold
0.2 In to pickup threshold
Pickup time delay
15 s to 1500 s
Dropout time delay
15 s to 3000 s

Voltage protection
Type

Range

Factory setting

Step

Accuracy

100 V
pickup threshold

5V
5V

-5 %, +0 %
-5 %, +0 %

Pickup time delay


Dropout time delay

100 V to U max pickup threshold


pickup threshold to U max
pickup threshold
1.2 s to 5 s
1.2 s to 36 s

5s
1.2 s

0.1 s
0.1 s

-0 %, +20 %
-0 %, +20 %

maximum voltage U max


Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

U min pickup threshold to 1200 V


100 V to pickup threshold
1.2 s to 5 s
1.2 s to 36 s

725 V
pickup threshold
5s
1.2 s

5V
5V
0.1 s
0.1 s

-0 %, +5 %
-0 %, +5 %
-0 %, +20 %
-0 %, +20 %

voltage unbalance U unbal


Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

2% to 30%
2% to pickup threshold
1 s to 40 s
10 s to 360 s

30 %
pickup threshold
40 s
10 s

1%
1%
1s
1s

-20 %, +0 %
-20 %, +0 %
-20 %, +0 %
-20 %, +0 %

minimum voltage U min


Pickup threshold
Dropout threshold

102

Micrologic H

Schneider Electric

Other protection
Type

Range

Factory setting

Step

Accuracy

reverse power rP max


Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

5 to 500 kW
5 kW to pickup threshold
0.2 s to 20 s
1 s to 360 s

500 kW
pickup threshold
20 s
1s

5 kW
5 kW
0.1 s
0.1 s

2.5%
2.5%
-0 %, +20 % (1)
-0 %, +20 %

maximum frequency F max


Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

F min pickup threshold to 440 Hz


45 Hz to pickup threshold
1.2 s to 5 s
1.2 s to 36 s

65 Hz
pickup threshold
5s
1.2 s

0.5 Hz
0.5 Hz
0.1 s
0.1 s

0.5 Hz
0.5 Hz
-0 %, +20 % (2)
-0 %, +20 % (2)

45 Hz
pickup threshold

0.5 Hz
0.5 Hz

0.5 Hz
0.5 Hz

Pickup time delay


Dropout time delay

45 Hz to F max pickup threshold


pickup threshold to F max
pickup threshold
1.2 s to 5 s
1.2 s to 36 s

5s
1.2 s

0.1 s
0.1 s

-0 %, +20 % (2)
-0 %, +20 % (2)

phase rotation
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

Ph1, Ph2, Ph3 or Ph1, Ph3, Ph2


pickup threshold
0.3 s
0.3 s

Ph1, Ph2, Ph3


pickup threshold
0.3 s
0.3 s

none
none
none
none

none
none
-0 %, +50 %
-0 %, +50 %

minimum frequency F min


Pickup threshold
Dropout threshold

(1) + 30 % on dial 0.2 s


(2) + 30 % up to 1.5 s

Load shedding and reconnection


Type

Range

Factory setting

Step

Accuracy

current I
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

50 % to 100% Ir
30 % Ir to shedding threshold
20 % to 80% tr
10 s to 600 s

100 % Ir
shedding threshold
80 % tr
10 s

1%
1%
1%
1s

6%
6%
-20 %, +0 %
-20 %, +0 %

power P
Pickup threshold
Dropout threshold
Pickup time delay
Dropout time delay

200 kW to 10 000 kW
100 kW to shedding threshold
10 s to 3600 s
10 s to 3600 s

10 000 kW
shedding threshold
3600 s
10 s

50 kW
50 kW
10 s
10 s

2.5 %
2.5 %
-20 %, +0 %
-20 %, +0 %

103

Micrologic H

Schneider Electric

Technical appendix

Other settings

M2C / M6C contacts


Type
time-delay
latching
time delay

Range

Factory setting

Step

1 - 360 s

360 s

1s

Step

Micrologic setup
Type

Range

Factory setting

language

German
English US
English UK
Italian
French
Spanish
Chinese

English UK

date / time
circuit-breaker
selection
neutral TC
VT ratio
primary voltage
secondary voltage
system
frequency

1s
"no def"
no TC
min. 100 V, max. 1150 V
min. 100 V, max. 690 V
50/60 Hz
or
400 Hz

690 V
690 V
50/60 Hz

1V
1V

Range

Factory setting

Step

3 , 3 w, 3 CT
3 , 4 w, 3 CT
3 , 4 w, 4 CT

3 , 4 w, 4 CT

thermal or
block interval
sliding
5 to 60 minutes

block interval

thermal or
block interval or
sync. to comms
fixed or sliding
5 to 60 minutes
P+
P-

block interval

Measurement setup
Type
system type

demand-current
calculation method
type of window
calculation interval
demand-power
calculation method

type of window
calculation interval
power sign

sign convention

IEEE
IEEE alternate
IEC

sliding
15 minutes

1 minute

sliding
15 minutes
P+
(flow from top to
bottom)
IEEE

1 minute

Communication setup
Type
com parameter
address
baud rate
parity
remote settings
access authorisation
access code
remote
control

Range

Factory setting

MODBUS
1-47
9600 to 19 200 bauds
even
none

47
19 200 bauds
even

yes / no
0000 to 9999
manual
automatic

yes
0000
automatic

Protection setup
Type
current protection
voltage protection
other protection

104

Micrologic H

Range

Factory setting

alarm / trip / OFF

OFF

Schneider Electric

Measurement setting ranges


and accuracy

c The accuracy of the current


measurements depends on both the value
displayed (or transmitted) and the circuitbreaker rating, where:
Accuracy = 0.5% In + 1.5% reading

Example:
For a circuit breaker with a 4000 A rating
and a current displayed on Micrologic
of 49 A, the accuracy is:
0.5% x 4000 + 1.5% x 49 = 21 A

Measurement setting ranges and accuracy


Range

Accuracy at 25 C

instantaneous current
I1, I2, I3
IN
I t ground
I t earth leakage
I1 max, I2 max, I3 max
IN max
I t max ground
I t max earth leakage

0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to In
0 to 30 A
0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to In
0 to 30 A

1.5 %
1.5 %
10 %
1.5 %
1.5 %
1.5 %
10 %
1.5 %

demand current
I 1, I 2, I 3
IN
I 1 max, I 2 max, I 3 max
I N max

0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to 20 x In
0.005 x In to 20 x In

1.5 %
1.5 %
1.5 %
1.5 %

phase-to-phase voltages
U12
U23
U31

170 to 1150 V
170 to 1150 V
170 to 1150 V

0.5 %
0.5 %
0.5 %

phase-to-neutral voltages
V1N
V2N
V3N

100 to 1150 V
100 to 1150 V
100 to 1150 V

0.5 %
0.5 %
0.5 %

average voltage
U avg

170 to 1150 V

0.5 %

voltage unbalance
U unbal

0 to 100 %

0.5 %

instantaneous power
P
Q
S

0.015 to 184 MW
0.015 to 184 Mvar
0.015 to 184 MVA

2%
2%
2%

power factor
PF

-1 to +1

2%

demand power
P
Q
S
P max
Q max
S max

0.015 to 184 MW
0.015 to 184 Mvar
0.015 to 184 MVA
0.015 to 184 MW
0.015 to 184 Mvar
0.015 to 184 MVA

2%
2%
2%
2%
2%
2%

total energy
E.P
E.Q
E.S

-1010 GWh to +1010 GWh


-1010 Gvarh to +1010 Gvarh
-1010 GVAh to +1010 GVAh

2%
2%
2%

total energy in
E.P
E.Q

-1010 GWh to +1010 GWh


-1010 Gvarh to +1010 Gvarh

2%
2%

total energy out


E.P
E.Q

-1010 GWh to +1010 GWh


-1010 Gvarh to +1010 Gvarh

2%
2%

frequency
F

45 Hz to 440 Hz

0.1 %

I
U
P, Q, S

0.005 x In to 1.5 x In
30 to 1150 V
0.15 to 13.8 kW

1.5 % (1)
0.5 %
2%

THD, thd
I
U

2 to 1000%
2 to 1000%

5%
5%

FFT
I
U

0 to 1000%
0 to 1000%

5%
5%

Type

fundamentals

(1) Over the range 0.7 x In to 1.5 x In

105

Micrologic H

Schneider Electric

Power factor sign conventions

E71920B

Technical appendix

Flow of active and


reactive power

Q
P to load
Q to load

P from load
Q to load

E71921B

P from load
Q from load

IEC

P to load
Q from load

Q
P=Q=+
pf = -

P=+
Q=+
pf = +
P

E71922B

P=Q=pf = -

IEEE

P=+
Q=pf = +

Q
P=Q=+
pf = + (leading)

P=+
Q=+
pf = - (lagging)
P

E71923B

P=Q=pf = - (lagging)

IEEE Alt

P=+
Q=pf = + (leading)

Q
P=Q=pf = + (leading)

P=+
Q=pf = - (lagging)
P

P=Q=+
pf = - (lagging)

106

Micrologic H

P=+
Q=+
pf = + (leading)

Schneider Electric

107

Micrologic H

Schneider Electric

Index

A
Activation
Active, reactive, apparent energy
Active, reactive, apparent power
AD power-supply module
Address
Alarm
Alarm history

27, 28, 29, 30, 44


32, 75
73
95
58
44, 47
46, 85

B
Baud rate
Buttons

58
5, 6

C
Circuit-breaker selection
COM communication option
Contact
Contact wear
Control unit identification
Control-unit battery
Cos
Crest factor
Current demand calculation

53
49, 58, 99
45, 50
86
4
5, 87
40
41
31, 55

D
Date and time
Demand current
Demand power
Digipact
Direction of power flow
Distortion factor
Distortion power
Dropout
DT

52
55, 69
32, 56
58
54
41
41
27, 28, 29, 30, 44
23, 61

E
Earth-leakage protection
Earth-leakage protection tripping delay
EIT

26
26
23, 61

F
F max
F min
Fault
Frequency
FTT
Full neutral protection
Fundamental
Graphic display
Ground-fault / Earth-leakage fault protection test
Ground-fault protection

29, 64
29, 64
84
32, 54, 82
42, 80
25, 63
77
5
88
26

H
Half neutral protection
Harmonics
History, setup and maintenance menu
HVF

25, 63
33
13, 18
6, 23

I
It
I t Alarm
I avg
I max
I unbal
In pickup
I2t
Idmtl
Ig pickup
Ii pickup
Infrared link
Instantaneous current
Instantaneous protection
Ir current setting
Isd pickup

62
27, 64
27
27, 64
64
26
22, 60
23, 61
26
24
5
68
24
22, 23
24

K
K factor

41

108

Micrologic H

Schneider Electric

L
Language
Latching
Lead seal for cover
LEDs
Load shedding / reconnection
Long-time I2t protection
Long-time Idmtl protection
Long-time plug

52
45, 50
5
5, 47, 87
30, 66
22
23
5, 97

M
M2C / M6C
Main screen
Maximum demand current
Maximum demand power
Maximum instantaneous current
Metering menu
ModBus

45, 50
12, 68
31, 70
32, 74
31, 68
13, 14
58

N
Negatively incremented energy
Neutral CT
Neutral protection
Neutral protection setting
No neutral protection

32, 75
63
23, 25
11
25, 63

O
Operation counter
Oversized neutral protection

86
25, 63

P
Parity
Phase rotation
Phase sequence
Phase-to-neutral and phase-to-phase voltage
Portable test kit
Positively incremented energy
Power demand calculation
Power factor
Power sign
Power supply
Protection menu

58
29, 31, 64
31, 72
31, 71
88
32, 75
32, 56
40
54
95
13, 20

R
Remote control
Remote settings
Resetting the alarms and fault indications
Resetting the contacts
Resetting the energy values
Resetting the maximum demand current values
Resetting the maximum demand power values
Resetting the maximum instantaneous current values
Resetting the operation counter
RMS current
rms voltage
rP max

59
58
84
45, 50
75
70
74
68
86
37
37
29, 64

S
Self-protection
Setting dials
Short-time protection
Sign convention
SIT
System frequency
System type

5, 48
5, 6
24
106
23, 61
54
55

109

Micrologic H

Schneider Electric

Index

T
Tab
Temperature
Test connector
tg tripping delay
THD
thd
Thermal memory
tr tripping delay
Transformation ratio
Trip
Trip history
Tripping curves
tsd tripping delay

7
22, 48, 98
5, 88
26
37, 78
39, 79
22, 98
22, 23
54
44
46, 85
90
24

U
U max
U min
U unbal

28
28, 92
28, 71, 92

V
VIT
Voltage U avg

23, 61
28, 31

W
Waveform
Waveform capture

43
43, 76

Z
Zone selective interlocking

94

110

Micrologic H

Schneider Electric

Schneider Electric Industries SA


Postal address
5, rue Nadar
92506 Rueil-Malmaison Cedex
France
Tel: +33 (0)1 41 29 82 00
Fax:+33 (0)1 47 51 80 20

As standards, specifications and design change from time to time, always ask for confirmation
of the information given in this publication.
This document has been printed on ecological paper
Layout by: HeadLines
Printed by:

http://www.schneider-electric.com

04443728AA-C

05-02

Das könnte Ihnen auch gefallen