MEDIA TENSIN
media tensin
ndice
NDICE
INTRODUCCIN TCNICA ....................................................................................................................................................................
A) Generalidades ..................................................................................................................................................................................
8
8
9
9
10
10
11
16
16
16
17
18
19
19
19
D) Nuevos cables de MT con propiedades frente al fuego mejoradas, versiones S (seguridad) y AS (alta seguridad) ...................
23
E) Ensayos .............................................................................................................................................................................................
Pruebas sobre cables terminados ..............................................................................................................................................
25
25
26
49
51
52
55
57
58
61
63
65
67
69
71
72
78
87
89
Cables tipo VOLTALENE ............................................................................................................................................................. 91
Dimetros bajo aislamiento de Cables VOLTALENE .................................................................................................................... 93
Dimetros exteriores y pesos de Cables VOLTALENE ................................................................................................................. 94
Tablas de datos tcnicos de Cables VOLTALENE .......................................................................................................................... 101
Grficos de intensidades de cortocircuito en el conductor para los Cables tipo VOLTALENE ........................................................ 110
media tensin
ndice
114
116
118
120
122
124
126
129
132
133
136
139
142
145
148
151
155
157
159
161
163
164
166
169
172
174
175
176
177
182
183
184
186
188
200
201
206
207
208
209
210
211
212
213
214
215
INTRODUCCIN TCNICA
media tensin
introduccin tcnica
A) GENERALIDADES
En esta publicacin se hace frecuentemente referencia, cuando proceda, al Reglamento de Lneas para Alta Tensin (R.D. 223/2008), a las Normas
UNE, a los Documentos del CENELEC o a los Documentos de la IEC y, cuando no estn disponibles documentos oficiales, a datos e informacin
interna propia.
Para definir el empleo de los cables tratados en este catlogo, se transcribe parte del contenido del RLAT (artculo 3 y tabla 1 de la ITC-LAT 06)
donde se establecen diferentes categoras para las lneas en funcin de su tensin nominal:
REDES TRIFSICAS DE CORRIENTE ALTERNA CON TENSIN NOMINAL SUPERIOR A 1 kV Y SIN EXCEDER DE 30 kV (TERCERA CATEGORA)
Tensin mxima (Um)
kV
3,6
7,2
12
17,5
24
30
36
REDES TRIFSICAS DE CORRIENTE ALTERNA CON TENSIN NOMINAL SUPERIOR A 30 kV Y SIN EXCEDER DE 220 kV (SEGUNDA Y
PRIMERA CATEGORA)
Tensin mxima (Um)
kV
52 (2 CAT)
72,5 (2 CAT)
145 (1 CAT)
245 (1 CAT)
NOTA: En esta publicacin no se incluyen los datos correspondientes a los cables de tensin nominal superior a los 30 kV, salvo el anexo final sobre
cables y accesorios para 26/45 kV y 36/66 kV.
media tensin
introduccin tcnica
Seccin (mm2)
70
95
120
150
185
240
300
400
180
170
215
205
245
235
275
260
315
295
365
345
410
390
470
445
* Instalacin directamente enterrada a un metro de profundidad, temperatura mxima del suelo 25 C, resistividad trmica del terreno 1,5 K m/W
para tensiones de 12/20 a 18/30 kV. Cable de aluminio unipolar no armado.
Menor dimetro exterior del cable, por incremento del gradiente de trabajo, reduccin del espesor de aislamiento y por su posible reduccin
de su seccin del conductor.
Mayor facilidad de instalacin, por su mayor flexibilidad y menor radio de curvatura.
Menor coste de la lnea elctrica.
media tensin
introduccin tcnica
CARACTERSTICAS GENERALES
Los parmetros para elegir un cable de media tensin son:
Empleo, con indicacin del tiempo de permanencia previsto para la instalacin.
Condiciones de instalacin: fija o mvil, en este caso se prestar atencin a si se trata de un servicio mvil continuo o espordico con descripcin
detallada del tipo de trabajo que efectuar el cable.
Tensin de servicio efectiva en voltios (corriente continua, alterna monofsica, trifsica, etc.).
Nmero y seccin de los conductores, corriente en amperios o datos para su determinacin (potencia en kVA, o en kW y cos ), servicio continuo
o intermitente y, en su caso, caractersticas de esta intermitencia.
Normas o especificaciones a que el cable debe responder.
Longitud total necesaria del cable y metraje de cada pieza.
Dimetro exterior mximo del cable.
CARACTERSTICAS PARTICULARES
1) Cables terrestres para instalacin fija:
Cable enterrado directamente en terreno normal (verificando la posibilidad de entrar en contacto con aceites o hidrocarburos).
En canales o en conductos tubulares en el terreno.
Tendido al aire libre y a la sombra.
Tendido al aire libre al sol.
Tendido al aire bajo tubo.
Enrollado en un tambor.
Tendido en galera
Otras condiciones de instalacin:
- alta montaa.
- zonas de caza.
- riesgos de nieblas o vapores cidos, teniendo en cuenta en este caso, concentracin y naturaleza de stos, etc.
2) Caractersticas particulares del sistema trifsico:
Es un sistema trifsico con neutro aislado o con neutro a tierra?
Si es neutro aislado, cunto tiempo se prev que puede funcionar con una fase a tierra?, breves instantes, ms de una hora o ms de ocho horas?
Valor previsible de la corriente de cortocircuito.
Duracin del cortocircuito.
3) Cables para minas:
Galeras horizontales, inclinadas o verticales?
Se trata de instalaciones semimviles que avanzarn con el trabajo?
Las bobinas deben tener unas dimensiones mximas?
4) Cables subacuticos:
Para ros, lagos, canales, etc., se precisa una breve descripcin del fondo (rocoso, fangoso, pedregoso), indicacin de su profundidad,
velocidad del agua, eventuales peligros derivados del paso de barcos, anclas, elementos de pesca, buceadores, etc.
media tensin
introduccin tcnica
3.6
7.2
10
12
15
17.5
20
24
25
30
30
36
Categora de la red
Cable a utilizar
Tensin nominal del cable
Uo/U (kV)
A-B
C
A-B
C
A-B
C
A-B
C
A-B
C
A-B
C
A-B
C
1.8/3
3.6/6
6/10
8.7/15
12/20
15/25
18/30
26/45
10
media tensin
introduccin tcnica
10
1,21
1,27
Temperatura ambiente, a, en C
15
1,18
1,23
20
25
30
35
40
45
50
55
60
1,14
1,18
1,11
1,14
1,07
1,10
1,04
1,05
1
1
0,96
0,95
0,92
0,89
0,88
0,84
0,83
0,78
11
media tensin
introduccin tcnica
Instalacin
0,95
0,90
0,88
0,85
0,84
0,90
0,85
0,83
0,81
0,80
0,88
0,83
0,81
0,79
0,78
0,86
0,81
0,79
0,77
0,76
0,98
0,96
0,93
0,92
0,95
0,93
0,90
0,89
0,94
0,92
0,89
0,88
0,93
0,90
0,87
0,86
0,93
0,90
0,87
0,86
0,84
0,80
0,75
0,73
0,80
0,76
0,71
0,69
0,78
0,74
0,70
0,68
0,76
0,72
0,68
0,66
0,95
0,78
0,73
0,68
0,66
>3
1,00
0,93
0,87
0,83
0,89
0,83
0,79
0,75
0,80
0,76
0,72
0,69
>3
0,75
0,70
0,66
0,64
30 cm
d
2 cm
30 cm
Bandejas
2 cm
30 cm
30 cm
2 cm
2 cm
12
media tensin
introduccin tcnica
Montaje
Instalacin
Bandejas
30 cm
1
Cables unipolares, tendidos sobre bandejas
continuas (la circulacin de aire es
restringida) con separacin entre cables
igual a un dimetro d.
d d
2 cm
30 cm
0,92
0,89
0,88
0,87
0,84
0,83
0,84
0,82
0,81
0,82
0,80
0,79
0,97
0,96
0,97
0,94
0,93
0,96
0,93
0,92
0,94
0,91
0,90
d d
2 cm
Nmero
de ternos
Factor de
correccin
0,91
0,89
2 cm
Nmero
de ternos
2
0,86
0,84
13
Factor de
correccin
media tensin
introduccin tcnica
INSTALACIN ENTERRADA
1 Cables enterrados en terrenos con temperatura del mismo distinta de 25 C:
COEFICIENTES DE CORRECCIN
Temperatura del terreno, t, en C
Temperatura
de servicio,
s, en C
10
15
20
25
30
35
40
45
50
1,09
1,11
1,06
1,07
1,03
1,04
1,00
1,00
0,97
0,96
0,94
0,92
0,90
0,88
0,87
0,83
0,83
0,78
2 - Cables enterrados directamente o en conducciones en terrenos de resistencia trmica diferente a 1,5 K.m/W.
COEFICIENTES DE CORRECCIN
Tipo de
instalacin
Cables
directamente
enterrados
Cables
en interior
de tubos
enterrados
Seccin del
conductor
mm2
0,8
0,9
1,0
1,5
2,0
2,5
25
35
50
70
95
120
150
185
240
300
400
25
35
50
70
95
120
150
185
240
300
400
1,25
1,25
1,26
1,27
1,28
1,28
1,28
1,29
1,29
1,30
1,30
1,12
1,13
1,13
1,13
1,14
1,14
1,14
1,14
1,15
1,15
1,16
1,20
1,21
1,21
1,22
1,22
1,22
1,23
1,23
1,23
1,24
1,24
1,10
1,11
1,11
1,11
1,12
1,12
1,12
1,12
1,12
1,13
1,13
1,16
1,16
1,16
1,17
1,18
1,18
1,18
1,18
1,18
1,19
1,19
1,08
1,09
1,09
1,09
1,09
1,10
1,10
1,10
1,10
1,10
1,10
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
0,89
0,89
0,89
0,89
0,89
0,88
0,88
0,88
0,88
0,88
0,88
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,92
0,92
0,92
0,81
0,81
0,81
0,81
0,80
0,80
0,80
0,80
0,80
0,80
0,79
0,88
0,88
0,87
0,87
0,87
0,87
0,87
0,87
0,86
0,86
0,86
0,75
0,75
0,74
0,74
0,74
0,74
0,74
0,74
0,73
0,73
0,73
0,83
0,83
0,83
0,82
0,82
0,82
0,82
0,82
0,81
0,81
0,81
14
media tensin
introduccin tcnica
Cables
directamente
enterrados
Cables
bajo tubo
Separacin
de los ternos
10
0,76
0,65
0,58
0,53
0,50
0,47
0,45
0,43
0,42
0,82
0,86
0,88
0,90
0,73
0,78
0,82
0,85
0,68
0,75
0,79
0,83
0,64
0,72
0,77
0,81
0,61
0,70
0,76
0,80
0,59
0,68
0,74
0,79
0,57
0,67
0,74
0,56
0,66
0,73
0,55
0,65
En contacto
(d = 0 cm)
0,80
0,70
0,64
0,60
0,57
0,54
0,52
0,50
0,49
d = 0,2 m
d = 0,4 m
d = 0,6 m
d = 0,8 m
0,83
0,87
0,89
0,90
0,75
0,80
0,83
0,86
0,70
0,77
0,81
0,84
0,67
0,74
0,79
0,82
0,64
0,72
0,78
0,81
0,62
0,71
0,77
0,60
0,70
0,76
0,59
0,69
0,75
0,58
0,68
En contacto
(d = 0 cm)
d = 0,2 m
d = 0,4 m
d = 0,6 m
d = 0,8 m
Profundidad
de instalacin
COEFICIENTES DE CORRECCIN
Profundidad
(m)
0,50
0,60
0,80
1,00
1,25
1,50
1,75
2,00
2,50
3,00
185 mm2
185 mm2
1,06
1,04
1,02
1,00
0,98
0,97
0,96
0,95
0,93
0,92
1,09
1,07
1,03
1,00
0,98
0,96
0,94
0,93
0,91
0,89
1,06
1,04
1,02
1,00
0,98
0,97
0,96
0,95
0,93
0,92
1,08
1,06
1,03
1,00
0,98
0,96
0,95
0,94
0,92
0,91
15
media tensin
introduccin tcnica
K es un coeficiente que depende de la naturaleza del conductor y de sus temperaturas al principio y al final del cortocircuito.
S es la seccin del conductor en mm2.
En la hiptesis de que los conductores se hallaran inicialmente a la temperatura mxima de rgimen y alcancen al final del cortocircuito la admisible
en tal caso, el valor de K es de 142 y 94, segn se trate de cables con conductores de cobre o de aluminio respectivamente. En el supuesto de
que las condiciones de servicio permitieran considerar una temperatura de rgimen ms reducida, aumenta el salto de temperatura y la corriente
de cortocircuito admisible sera por lo tanto ms elevada.
- Las corrientes mximas de cortocircuito admisibles en los conductores vienen dadas en los grficos I y II.
- Las corrientes de cortocircuito mximas tolerables en las pantallas se reflejan en las tablas XI y XII. (Ver ejemplo de clculo n4).
ACCESORIOS
La confeccin de los accesorios (empalmes, terminales, conectadores, pasatapas...) de los cables EPROTENAX COMPACT y VOLTALENE se simplifica
notablemente con el empleo de accesorios normalizados y kits preparados con tal propsito. (Ver apartado accesorios)
Como un empalme o un terminal deben tratar de conservar todo lo posible las caractersticas fsicas del cable al que se aplican, los empalmes o
terminales de los cables EPROTENAX COMPACT y VOLTALENE se realizan con la mxima simplicidad y fiabilidad, empleando materiales suministrados
por PRYSMIAN CABLES Y SISTEMAS, S.A. elaborados con materiales similares a los utilizados en la fabricacin de los cables.
Para los cables apantallados es necesario mantener la continuidad de la pantalla en los empalmes y elaborar deflectores de campo adecuados en
los terminales, a fin de evitar solicitaciones elctricas excesivas localizadas.
Durante el montaje de estos accesorios es de fundamental importancia eliminar la capa semiconductora aplicada sobre el aislamiento sin afectar
lo ms mnimo a este ltimo con las herramientas de corte y/o extraccin.
En los cables clsicos, de capa conductora extrusionada, para facilitar su retiro se puede calentar suave y cuidadosamente con una llama. Despus
deber lijarse la superficie del aislante hasta eliminar completamente la capa de sustancia semiconductora que queda. En nuestros cables de hasta
30 kV, al ser fabricados en triple extrusin separable en fro, no es necesario emplear calor para retirar la capa extrusionada conductora, ya
que esta se retira con facilidad. En todos los casos se limpiar cuidadosamente la superficie del aislamiento hasta asegurarse que se ha eliminado
toda traza de material semiconductor.
16
media tensin
introduccin tcnica
Estos lmites no se aplican a las curvaturas a que el cable pueda estar sometido durante su tendido, cuyos radios deben tener un valor superior
(20D para cables hasta 36/66 kV).
Los esfuerzos de traccin pueden aplicarse a los revestimientos de proteccin (manga de tiro), o a los conductores de cobre o de aluminio, recomendndose
que las solicitaciones no superen los 6 kg/(mm2 de seccin del conductor) para cables unipolares y de 5 kg/mm2 para cables tripolares de cobre.
Para conductores de aluminio se aplicar un esfuerzo de 3 kg/mm2 tanto para conductores unipolares como tripolares. Cuando el esfuerzo
previsto exceda de los valores admisibles mencionados, se deber recurrir al empleo de cables armados con alambres (tipo M o MA); en este caso
se aplicar el esfuerzo a la armadura, sin superar del 25 al 30 % de la carga de rotura terica de la misma.
Los valores de tensin de traccin expuestos son de aplicacin para tendidos per no para la posicin final esttica del cable (recorridos verticales)
en cuyo caso los valores mximos son muy inferiores.
Durante el tendido es conveniente detener el tiro del cable lo menos posible, es mejor llevar una baja velocidad de tiro que tener que arrancar de
parado porque los rozamientos estticos son superiores a los dinmicos.
Cuando la intensidad a transportar sea superior a la admisible por un solo conductor se podr instalar ms de un conductor por fase, segn los
siguientes criterios:
Emplear conductores del mismo material, seccin y longitud.
Los cables se agruparn al tresbolillo, en ternas dispuestas en uno o varios niveles, por ejemplo:
S
S
S
S
Ternas en un nivel:
T
...
S
Ternas apiladas en diferentes niveles:
T
R
S
T
S
...
La temperatura del cable durante la operacin de tendido, en una instalacin fija, en toda su longitud y durante todo el tiempo de la instalacin,
en que est sometido a curvaturas y enderezamientos, no debe ser inferior a 0 C. Esta temperatura se refiere a la del propio cable, no a la
temperatura ambiente. Si el cable ha estado almacenado a baja temperatura durante cierto tiempo, antes del tendido deber llevarse a una
17
media tensin
introduccin tcnica
TRENZADOS AREOS
INTERIOR AEROGENERADORES
(Ver Anexo A)
(Ver Anexo A)
Aeropuertos
Tneles
Minas
TUNELADORAS Y ROZADORAS
OFF-SHORE
INFRAESTRUCTURAS FERROVIARIAS
18
media tensin
introduccin tcnica
C) CARACTERSTICAS ESTRUCTURALES
NORMATIVA
Tal como se ha indicado, los cables relacionados en el presente Catlogo satisfacen la Norma IEC 60502 para "Cables de transporte de energa
aislados con dielctricos secos extrudos para tensiones nominales de 1 kV a 30 kV", lo que incluye cualidades de los materiales que configuran
cada uno de los componentes del cable, criterios de diseo, caractersticas dimensionales, as como los requisitos elctricos que se les exige.
Adems, PRYSMIAN CABLES Y SISTEMAS, tiene concedida la homologacin de AENOR, correspondiente a cables unipolares con conductores de
aluminio y aislamiento seco, para redes de media tensin hasta 30 kV. Esta especificacin, adoptada por las Compaas Elctricas, recoge las
caractersticas constructivas y de ensayo exigibles al material a incorporar en sus redes de distribucin. Estos cables estn tambin recogidos en
la norma UNE HD 620.
Los tipos de cables considerados son, como se ha dicho, con conductor de aluminio en las tensiones y secciones siguientes:
Seccin del conductor mm2
Tensin nominal
50
6/10
95
8,7/15
150
12/20
240
18/30
400
Estos cables se construyen mediante el proceso denominado de triple extrusin, con la capa semiconductora externa separable en fro, tipo
TESF. Incorporan una pantalla metlica de alambres de cobre de seccin total 16 mm2 y la cubierta exterior es de un material de poliolefina especial
con el espesor incrementado para mejorar la resistencia mecnica del cable y dificultar la penetracin de humedad.
A continuacin se indican las caractersticas generales de los diversos constituyentes que pueden conformar un cable EPROTENAX COMPACT o
VOLTALENE, as como los ensayos finales a que se someten los cables terminados.
DEFINICIONES Y DESCRIPCIONES
1 - CONDUCTOR
Los conductores de los cables estn constituidos por cuerdas redondas compactas de cobre recocido o de aluminio. La compactacin se efecta
por un mtodo patentado que permite obtener superficies ms lisas y dimetros de cuerdas menores que los de las cuerdas normales de igual
seccin.
(1) Si eventualmente entra agua en el interior del cable durante su instalacin, o por causa accidental, y se desea evitar su propagacin a lo largo
de los huecos existentes entre los alambres que forman el conductor, estos alambres pueden fabricarse rellenos con un material obturador que
impide dicha propagacin. Los conductores satisfacen las especificaciones de las normas, tanto nacionales (UNE EN 60228), como internacionales
(IEC 60228). En la tabla III se dan los valores de las resistencias elctricas para las distintas secciones de los conductores, as como sus dimetros
aproximados.
Conductor, cuerda
redonda compacta
Conductor, cuerda
redonda normal
19
media tensin
introduccin tcnica
3 - AISLAMIENTO:
El aislamiento de los cables EPROTENAX COMPACT es una mezcla a base del polmero sinttico "etileno-propileno de alto mdulo" (designado con
HEPR).
Sus caractersticas mecnicas, fsicas, elctricas, etc. son iguales o superan a las de las mejores gomas aislantes para cables empleadas hasta el
momento, pero lo que la distingue particularmente es su mayor resistencia al envejecimiento trmico y su elevadsima resistencia al fenmeno de
las "descargas parciales", especialmente crtico en terrenos hmedos en ambientes contaminados, cuando se emplean otros aislamientos "secos".
Esta extraordinaria resistencia al efecto corona o a las descargas parciales, unida a sus excelentes caractersticas elctricas, permite elevar el lmite
de seguridad del dielctrico y elaborar, por tanto, con plena seguridad, cables aislados con goma, no slo para las tensiones citadas en este Catlogo
de hasta 30 kV, sino tambin hasta 150 kV, sin tener que recurrir a protecciones especiales contra la penetracin de humedad en el cable.
Las caractersticas y prescripciones de prueba de la mezcla de etileno-propileno utilizada, responden a las mayores exigencias que se especifican
en las principales Normas en uso, tanto nacionales como extranjeras. En la tabla I figura un resumen de tales caractersticas.
El aislamiento de los cables VOLTALENE est constituido por polietileno qumicamente reticulado. Dicho aislamiento es un material termoestable
que presenta buena rigidez dielctrica, bajo factor de prdidas y una excelente resistencia de aislamiento.
La excelente estabilidad trmica del polietileno reticulado le capacita para admitir en rgimen permanente temperaturas de trabajo en el conductor
de hasta 90 C, tolerando temperaturas de cortocircuito de 250 C. La marcada estabilidad al envejecimiento, la elevada resistencia a los agentes
qumicos y la tenacidad mecnica y elctrica, son las propiedades ms destacadas que hacen del polietileno qumicamente reticulado un material
apropiado para el aislamiento de cables.
El polietileno reticulado empleado por PRYSMIAN, responde a todas las exigencias que se especifican en las principales Normas de uso, en particular,
la Norma Internacional IEC 60502. En la tabla I figura un resumen de sus caractersticas.
4 PANTALLA SOBRE EL AISLAMIENTO:
CAPA SEMICONDUCTORA EXTERNA:
Los cables EPROTENAX COMPACT de tensin superior a 3.6/6 kV deben ir apantallados y los cables VOLTALENE a partir de 1,8/3 kV. En los cables
trifsicos se aplica una pantalla sobre cada uno de los conductores aislados.
Los cables EPROTENAX COMPACT de tensin 1,8/3 kV y 3,6/6 kV y VOLTALENE de tensin 1,8/3 kV pueden fabricarse en las dos versiones:
apantallados o sin apantallar.
La pantalla est normalmente constituida por una envolvente metlica (cintas de cobre , hilos de cobre, etc.) aplicada sobre una capa semiconductora
externa, la cual , a su vez, se ha colocado previamente sobre el aislamiento con el mismo propsito con que se coloca la capa semiconductora
interna sobre el conductor.
La capa semiconductora externa est formada por una mezcla extrusionada y reticulada de caractersticas qumicas semejantes a la del aislamiento,
pero de baja resistencia elctrica.
Como quiera que la ntima unin que debe existir entre el aislamiento y la capa semiconductora externa comporta en ocasiones serias dificultades
de despegue en el momento de cofeccionar empalmes o terminales, adems de la mezcla semiconductora normal, PRYSMIAN ha ensayado y puesto
a punto un tipo de mezcla semiconductora que, conservando las caractersticas que le son propias, se separa fcilmente del aislamiento sin tener
que recurrir a ningn til especial, dejando el aislamiento completamente limpio. Esta mezcla semiconductora externa separable en fro, denominada
tambin como "easy stripping", se emplea en los cables de hasta 30 kV.
TRIPLE EXTRUSIN:
Respecto al proceso de fabricacin, cabe indicar que la aplicacin de la capa semiconductora sobre el conductor, el aislamiento y la capa
semiconductora sobre el aislamiento, se realiza en una sola operacin. Dicho proceso de fabricacin se denomina Triple Extrusin. Este procedimiento
es el ms adecuado ya que impide la incrustacin de cuerpos extraos entre el aislamiento y capas conductoras, y dadas las caractersticas de
los materiales utilizados en la confeccin de dichas mezclas, se suprime el riesgo de ionizacin en la interfase.
20
media tensin
introduccin tcnica
PANTALLA METLICA:
Consideraciones:
Las pantallas desempean distintas misiones, entre las que destacan:
Confinar el campo elctrico en el interior del cable.
Lograr una distribucin simtrica y radial del esfuerzo elctrico en el seno del aislamiento.
Limitar la influencia mutua entre cables elctricos.
Evitar, o al menos reducir, el peligro de electrocuciones.
Las corrientes de cortocircuito que pueden soportar las partes metlicas de las pantallas, vienen dadas en la tabla XI, para las pantallas de cintas
de cobre, en funcin del dimetro medio de la pantalla, y en la tabla XII, para las pantallas constituidas por hilos de cobre, en funcin de la seccin
total de los hilos. Si estas intensidades no son suficientes para las que se esperan en la instalacin particular de que se trate, bajo demanda se
pueden fabricar cables con pantallas de mayor seccin.
Protecciones contra la humedad (solo cables tipo VOLTALENE):
En cables donde se desee evitar la penetracin de humedad en el aislamiento, puede sustituirse la pantalla de cintas en hlice o hilos de cobre
por una cubierta extrusionada de plomo, que adems de impermeabilizar el cable, realiza las funciones elctricas propias de las pantallas metlicas.
Otra posibilidad para impedir la penetracin del agua consiste en aplicar una cinta de cobre longitudinalmente, solapada y sellada. Esta cinta se
adhiere fuertemente a la cubierta exterior. Si la seccin de cobre que proporciona esta cinta no es suficiente para transportar la intensidad de
cortocircuito requerida, la cinta se coloca sobre una corona de hilos de cobre de seccin adecuada.
Tanto las cubiertas de plomo como las protecciones de cinta de cobre longitudinal sellada, que configuran la proteccin radial del cable a la
penetracin del agua, se complementan, generalmente con cintas hinchantes de material higroscpico, que colocadas bajo las mismas en caso
de rotura y consecuente penetracin de agua, se hincharan taponando el espacio entre semiconductora externa y plomo o cinta de cobre, impidiendo
la propagacin longitudinal del agua a lo largo del cable.
5 - IDENTIFICACIN DE LAS ALMAS:
El etileno-propileno de alto mdulo empleado en el aislamiento de los cables EPROTENAX COMPACT el polietileno qumicamente reticulado
empleado en el aislamiento de los cables VOLTALENE es de un solo color. Para la identificacin de las almas en los cables tripolares se utilizan
tiras de distinto color (amarillo, verde y marrn) aplicadas en sentido longitudinal entre la capa conductora externa y la pantalla metlica.
6 - RELLENOS:
En los cables tripolares, los conductores aislados y apantallados se cablean. Para dar forma cilndrica al conjunto se aplica un relleno, y eventualmente
una capa, extrudos, de un material apropiado que pueda ser fcilmente eliminado cuando hay que confeccionar empalmes o terminales.
7 - PROTECCIONES EXTERNAS:
CUBIERTA DE SEPARACIN:
De acuerdo con las prescripciones de la Norma IEC 60502, cuando la pantalla y la armadura estn constituidas por materiales diferentes, debern
estar separadas por una cubierta estanca extruda. La calidad del material debe ser adecuada para la temperatura de trabajo del cable y sus
caractersticas quedan definidas en la Norma citada.
ARMADURA:
Las armaduras de los cables EPROTENAX COMPACT y VOLTALENE han sido estudiadas de forma que se conserve la ligereza y manejabilidad que
caracteriza a este tipo de cables. Estn constituidas por flejes o alambres metlicos dispuestos sobre un asiento apropiado y bajo la cubierta exterior,
con lo que la armadura queda protegida de las corrosiones qumicas o electrolticas. Generalmente las armaduras de alambres se sujetan mediante
una contraespira.
La armadura asume diversas funciones entre las que cabe distinguir:
Refuerzo mecnico, aconsejable segn la forma de instalacin y utilizacin.
Pantalla elctrica antiaccidentstica.
Barrera de proteccin contra roedores, insectos o larvas.
21
media tensin
introduccin tcnica
Los tipos de armadura utilizados en los cables de las series EPROTENAX COMPACT y VOLTALENE son los siguientes:
Para cables tripolares:
dos flejes de hierro (tipo F).
una corona de alambres de acero (tipo M).
Para cables unipolares:
dos flejes de aluminio y sus aleaciones (tipo FA).
una corona de alambres de aluminio y sus aleaciones (tipo MA).
CUBIERTA EXTERIOR:
Al ser las cubiertas una mezcla termoplstica, tienden a endurecerse a temperaturas inferiores a los 0 C, an cuando conservan cierta flexibilidad
a temperaturas entre -10 C y -15 C las de PVC y hasta -30 C la VEMEX y las AFUMEX. La nica precaucin a considerar es que las operaciones
de tendido de los cables no deben realizarse a temperaturas inferiores a los 0 C. Si un cable est fijo y no est sometido a golpes y vibraciones,
puede soportar sin dao temperaturas de -50 C.
A) Cubierta Vemex:
Para cables unipolares no armados sin mayor proteccin mecnica que la cubierta exterior se utiliza la cubierta especial termoplstica VEMEX, desarrollada
por PRYSMIAN. Este tipo de material conjuga una gran resistencia y flexibilidad en fro, con una elevada resistencia al desgarro a temperatura ambiente,
a la vez que una muy alta resistencia a la deformacin en caliente. En el caso de los cables VOLTALENE debe aadirse una muy baja permeabilidad al
agua. El equilibrio conseguido con una adecuada formulacin y las propiedades intrnsecas del polmero utilizado, se traducen en que el nuevo compuesto
termoplstico tiene unas caracterticas mecnicas y una resistencia al medio ambiente activo excepcionales, permitiendo un mayor abanico de
aplicaciones. Los cables EPROTENAX COMPACT y VOLTALENE con cubierta VEMEX presentan, respecto a los cables convencionales:
Mayor resistencia a la absorcin del agua.
Mayor resistencia al rozamiento y a la abrasin.
Mayor resistencia a los golpes.
Mayor resistencia al desgarro.
Mayor facilidad de instalacin en tramos tubulares.
Mayor seguridad en el montaje.
Todo ello hace que sea un cable idneo para el tendido mecanizado.
La tabla II indica las propiedades mnimas exigibles a la cubierta.
B) Cubierta PVC:
Las cubiertas de PVC corresponden a la norma IEC 60502, al tipo ST2, y sus caractersticas se indican en la tabla II, permitiendo mantener en los
cables armados la flexibilidad necesaria para su instalacin.
Cabe destacar que con formulaciones adecuadas se obtienen mezclas de PVC de gran resistencia a los aceites y a los hidrocarburos a condicin
de que su accin no sea permanente. En casos muy particulares de utilizacin en industrias petroqumicas o donde pueda darse la circunstancia
de una posible inmersin del cable en hidrocarburos, es aconsejable la utilizacin de una cubierta especial resistente a estos agentes.
Se recomienda muy especialmente que en las instalaciones en refineras e industrias petroqumicas en general se utilicen estos cables con funda
de plomo (proteccin P), bajo la cubierta, o bajo la armadura, en los casos en que el cable precise tambin de esta proteccin mecnica. La
versatilidad de instalacin de estos cables ofrece una solucin satisfactoria a mltiples problemas al proyectista y al instalador.
El empleo de una cubierta de PVC ignifugado permite conferir la caracterstica de no propagador del incendio al cable, propiedad aconsejable cuando
deban prevenirse las graves consecuencias de un posible incendio.
C) Cubiertas AFUMEX:
Cuando por razones del emplazamiento del cable, instalacin en edificios, galeras, etc... se precise disponer de cables con nula emisin de
halgenos y reducida opacidad deben emplearse cubiertas tipo Afumex que confieren a los cables las propiedades necesarias para superar los
siguientes ensayos de fuego:
No propagadores de la llama, segn UNE EN 60332-2-1.
No propagadores del incendio, segn UNE EN 60332-3.
Baja emisin de humos opacos, segn UNE EN 61034-2.
Baja emisin de gases txicos, segn NES 713 y NFC 20454.
Libre de halgenos, segn UNE EN 50267-2-1.
Baja corrosividad de los humos, segn UNE EN 50267-2-3.
22
media tensin
introduccin tcnica
Semiconductora
EXTERNA
Semiconductora
INTERNA
Conductor de Al
(taponado o no)
Cubierta
DMZ 2
(FLAMEX)
Pantalla de
hilos de Cu
Aislamiento
HEPR o XLPE
2.- Con la cubierta FLAMEX y una capa retardante del fuego bajo la misma, conseguimos superar el ensayo de no propagacin de la llama y el de
no propagacin del incendio (categora B. Ensayo de fuego de varias muestras de cable durante 40 minutos). sta es la versin del cable de
alta seguridad (AS).
Se trata de un cable de idnticas caractersticas a los Afumex (AS) frente al fuego, pero con mejores propiedades mecnicas de la cubierta y superando
en ensayo de categora B de no propagacin del incendio (ms exigente que la categora C). Se distinguen con dos franjas longitudinales de color verde.
NOTA: en zonas donde la propagacin del fuego no sea despreciable (galeras, instalaciones interiores) las exigencias de algunas compaas
elctricas son cable tipo AS exigiendo que supere la categora B del ensayo de no propagacin del incendio (UNE EN 60332-3-23) y manteniendo
unas buenas caractersticas de resistencia a la abrasin y penetracin del agua. El cable MT AS de Prysmian con franjas verdes supera el
ensayo de no propagacin del incendio categora B.
La categora B (UNE EN 60332-3-23) del ensayo de no propagacin del incendio es ms exigente que la categora C (UNE EN 60332-3-24). Para
superar el ensayo de categora B el cable es sometido 40 minutos a la accin de las llamas y el volumen de material combustible del cable a
ensayar es de 3,5 litros por metro de cable, para la categora C el tiempo es de 20 minutos y 1,5 litros de material no metlico por metro de muestra.
Recomendamos tener en cuenta este importante detalle a la hora de seleccionar el cable.
Para aunar unas buenas caractersticas de resistencia a la abrasin, resistencia a la penetracin del agua y cumplir la categora B (UNE
EN 60332-3-23) del ensayo de no propagacin del incendio se dota al cable de una doble cubierta (ver dibujo).
23
media tensin
introduccin tcnica
Obturacin
longitudinal cinta
higroscpica
(en cables de XLPE)
Capa adicional
retardante al
fuego
Semiconductora
EXTERNA
Semiconductora
INTERNA
Conductor de Al
(taponado o no)
Pantalla de
hilos de Cu
Cubierta
DMZ 2
(FLAMEX)
Aislamiento
HEPR o XLPE
Cables cubierta
VEMEX (DMZ1)
Cables (AS)
capa retardante + cubierta
FLAMEX (DMZ2)
SIN FRANJA
FRANJA GRIS
FRANJA VERDE
No propagacin de la llama
UNE-EN 60332-1-2
No
No
No
Opacidad de humos
UNE-EN 61034-2 (Transmitancia > 60%)
24
media tensin
introduccin tcnica
E) ENSAYOS
PRUEBAS SOBRE CABLES TERMINADOS
Una vez finalizado el proceso de fabricacin, durante el cual el producto ha sido sometido a controles intermedios, se realizan sobre los cables
una serie de ensayos destinados a comprobar el buen funcionamiento del cable y la calidad de sus componentes.
Los ensayos a realizar estn definidos en la Norma IEC 60502 para los cables desde 1 a 30 kV, y en la Norma UNE HD 632 e IEC 840 para los cables
de tensin superior a 30 kV.
Estas normas dividen los ensayos a realizar en tres grupos denominndolos ensayos individuales, especiales y tipo.
Los ensayos individuales se efectan sobre todas las piezas de cable terminado. Tienen por finalidad comprobar que el conductor y el
aislamiento estn en buen estado.
Los ensayos especiales se realizan sobre un nmero determinado de muestras extradas de las piezas de cable fabricadas. Su finalidad es
la de comprobar que el cable responde a las especificaciones de su diseo.
Los ensayos tipo se realizan sobre el cable antes de su comercializacin con el fin de comprobar que las caractersticas de servicio sean
satisfactorias para la utilizacin prevista. Una vez realizados, no es necesario repetirlos a menos que se introduzcan modificaciones en los
materiales o en la construccin del cable.
ENSAYOS INDIVIDUALES:
Los ensayos individuales para cables de tensin nominal desde 1 kV hasta 30 kV son los siguientes:
Medida de la resistencia elctrica del conductor. Se admiten como valores mximos los indicados en la tabla III (ver hojas de datos de los cables).
Ensayo de tensin. Se aplica el valor eficaz que corresponda de acuerdo con la tabla V, durante 5 minutos. La tensin se aplica entre conductor
y pantalla.
Ensayo de descargas parciales. Este ensayo debe realizarse, para cables aislados con polietileno reticulado, cuya tensin nominal sea superior
a 1,8/3 kV y para cables aislados con goma de etileno-propileno, cuya tensin nominal sea superior a 3,6/6 kV. La magnitud de las descargas
parciales a la tensin indicada en la tabla V (la tensin se aplica entre conductor y pantalla) no debe ser superior a 10 pC.
Para cables de tensin nominal superior a 30 kV, los ensayos individuales a realizar son los siguientes:
Ensayo de tensin.
Ensayo de descargas parciales.
Ensayo elctrico de la cubierta exterior.
ENSAYOS ESPECIALES:
Los ensayos especiales para cables de hasta 30 kV son los siguientes:
Examen del conductor. Se verifica que el conductor cumple lo indicado en la Norma UNE EN 60228.
Verificaciones dimensionales. Se comprueban las medidas de los espesores de aislamiento, cubiertas, alambres, flejes, etc. de los distintos
constituyentes del cable.
Ensayo elctrico. Para cables de tensin nominal superior a 3,6/6 kV consiste en un ensayo de tensin de 4 horas de duracin.
Los ensayos especiales para cables de ms de 30 kV son:
Examen del conductor.
Medida de la resistencia elctrica del conductor.
Medida de los espesores de aislamiento y cubiertas.
Ensayo de alargamiento en caliente del aislamiento.
Medida de la capacidad.
ENSAYOS TIPO:
Estos ensayos se dividen en dos grupos segn sean elctricos, o no.
Los ensayos tipo elctricos, para cables de media tensin o alta tensin, consisten en una serie de pruebas a realizar consecutivamente sobre una
muestra de cable, entre las que destacan el ensayo de doblado, la medida de la tg en funcin de la temperatura y de la tensin, el ensayo de
ciclos de calentamiento y el ensayo de tensin a impulsos.
Respecto a los ensayos tipo no elctricos, estos tratan principalmente de poner a prueba las caractersticas mecnicas, fsicas y qumicas de todos
los elementos del cable para asegurar su correspondencia con las especificadas en la Norma.
25
media tensin
introduccin tcnica
F) EJEMPLOS DE CLCULO
EJEMPLO DE CLCULO DE SECCIN EN MT (utilizacin de datos iniciales catlogo)
S
=
8,5 MVA Potencia aparente
U
=
20 kV Tensin entre fases
(Tensin nominal del cable 12/20 kV)
cos
=
0,8
L
=
200 m Longitud de la lnea
Una terna de cables AL EPROTENAX COMPACT soterrados bajo tubo en condiciones estndar (profundidad 1 m,
temperatura de terreno 25 C y resistividad trmica del terreno, 1,5 Km/W).
Intensidad de corriente:
S = 3 U I
I = S/ (3 U)
I = 8500 x 103 / (3 x 20000) 245 A
Seccin nominal
mm2
(1)
120
150
185
(3)
(2)
320
360
415
(4)
280
315
360
245
275
315
(5)
230
255
290
(6)
235
265
295
215
240
275
Cada de tensin:
U = L I 3 ((R cos ) + (X sen ))
L: Longitud de la lnea en km
= 0,2 km
I: Intensidad en A
= 245 A
R: Resistencia de la lnea en /km = 0,277 /km
cos = 0,8
sen = 0,6
Pgina 82
Resistencia mxima en c.a. y a 105 C en /km
Seccin nominal
mm2
120
150
185
Cables Unipolares
Cables Tripolares
Cu
Al
Cu
0.206
0.168
0.134
0.340
0.277
0.221
0.209
0.170
0.137
26
Al
0.343
0.281
0.224
media tensin
introduccin tcnica
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
12/25 kV
18/30 kV
0.095
0.093
0.089
0.098
0.096
0.093
0.106
0.102
0.100
0.111
0.108
0.104
0.112
0.110
0.106
0.118
0.115
0.110
0.123
0.118
0.113
Por tanto...
U = 0,2 x 245 x 3 x ((0,277 x 0,8) + (0,110 x 0,6))
U = 24,41 V
0,1
0,2
0,3
0,5
1,5
2,5
10
16
25
5300
8320
12700
3880
6080
9230
3250
5090
7700
2620
4110
6160
1990
3130
4630
1720
2700
3960
1560
2440
3560
1450
2270
3290
Icc = 3130 A en 1s
27
3
1370
2150
3100
media tensin
introduccin tcnica
SECCIONES en mm2
INTENSIDADES en kiloamperios
kA
TIEMPO en segundos
Pgina 75
Pgina 71
Seccin
nominal
mm2
ext.
mm
1 x 120
1 x 150
1 x 185
30
32
33,2
Peso
kg/km
Seccin
mm2
d
Cuerda
mm
d
Semic. int.
mm
120
150
185
12,7
14
16,1
13,7
15
17,1
15D
28
media tensin
introduccin tcnica
Cable Al Voltalene
20 C
1,25 m
RT = 1,5 Km/W
Circuitos en contacto
Nuevo circuito
El RLAT fija como estndares para tendidos subterrneos de media tensin bajo tubo las siguientes condiciones:
- Terno de cables unipolares enterrados bajo tubo
- Temperatura del terreno: 25 C
- Resistividad trmica del terreno: 1,5 Km/W
- Circuito nico (sin influencia trmica de otros cables en el entorno)
- Profundidad de instalacin: 1 m
Por tanto, ests son las condiciones para las que se han calculado las intensidades mximas admisibles para cables hasta 18/30 kV en instalaciones
enterradas bajo tubo (tabla 12 de la ITC-LAT 06 o tabla IX de los cables tipo Voltalene).
29
media tensin
introduccin tcnica
Tensin nominal
90 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
92
120
145
170
210
255
295
335
385
455
520
610
715
830
80
110
130
155
195
235
270
305
345
405
465
-
78
100
120
140
170
205
235
260
295
345
390
445
505
575
74
94
110
130
160
190
215
245
280
320
365
415
480
545
76
95
115
135
165
200
225
255
285
330
375
-
70
90
105
125
155
180
205
230
260
305
345
-
Cualquier desviacin de las condiciones estndares, como es el caso que nos ocupa, debe ser afectada de los coeficientes de correccin que figuran
en las tablas 7, 8, 10 y 11 de la citada ITC-LAT 06 (o tablas 1 y 2 de la pgina 14 y 3 y 4 de la pgina 15 de este catlogo).
De la tabla 7 del RLAT (o tabla 1, pg 14 del catlogo) obtenemos el coeficiente de correccin por temperatura distinta del estndar de 25 C. Al ser
de 20 C la temperatura del terreno en nuestro ejemplo, como vemos el coeficiente de correccin por temperatura ser de 1,04. Al tratarse de una
temperatura inferior a 25 C el coeficiente es superior a 1 pues el cable disipar mejor a temperatura ms baja el calor generado por efecto Joule.
Temperatura del terreno, t, en C
Temperatura
de servicio,
s, en C
10
15
20
25
30
35
40
45
50
1,09
1,11
1,06
1,07
1,03
1,04
1,00
1,00
0,97
0,96
0,94
0,92
0,90
0,88
0,87
0,83
0,83
0,78
KT = 1,04
En la tabla 8 (o tabla 2, pg, 14 del catlogo) tenemos los factores de correccin para resistividad trmica. Como la resistividad de nuestro caso
coincide con el estndar, el coeficiente ser lgicamente 1.
30
media tensin
Tipo de
instalacin
Cables
directamente
enterrados
Cables
en interior
de tubos
enterrados
introduccin tcnica
Seccin del
conductor
mm2
0,8
0,9
1,0
1,5
2,0
2,5
25
35
50
70
95
120
150
185
240
300
400
25
35
50
70
95
120
150
185
240
300
400
1,25
1,25
1,26
1,27
1,28
1,28
1,28
1,29
1,29
1,30
1,30
1,12
1,13
1,13
1,13
1,14
1,14
1,14
1,14
1,15
1,15
1,16
1,20
1,21
1,21
1,22
1,22
1,22
1,23
1,23
1,23
1,24
1,24
1,10
1,11
1,11
1,11
1,12
1,12
1,12
1,12
1,12
1,13
1,13
1,16
1,16
1,16
1,17
1,18
1,18
1,18
1,18
1,18
1,19
1,19
1,08
1,09
1,09
1,09
1,09
1,10
1,10
1,10
1,10
1,10
1,10
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
1,00
0,89
0,89
0,89
0,89
0,89
0,88
0,88
0,88
0,88
0,88
0,88
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,93
0,92
0,92
0,92
0,81
0,81
0,81
0,81
0,80
0,80
0,80
0,80
0,80
0,80
0,79
0,88
0,88
0,87
0,87
0,87
0,87
0,87
0,87
0,86
0,86
0,86
0,75
0,75
0,74
0,74
0,74
0,74
0,74
0,74
0,73
0,73
0,73
0,83
0,83
0,83
0,82
0,82
0,82
0,82
0,82
0,81
0,81
0,81
KR = 1
Al estar influido nuestro circuito por otros 2 en contacto, deberemos aplicar el correspondiente coeficiente por agrupamiento de la tabla 10 del RLAT
(o tabla 3 de la pgina 15 del catlogo). Y vemos la importancia de esta proximidad de circuitos (fuentes de calor), el coeficiente a aplicar es 0,7.
Factor de correccin
Tipo de
instalacin
Cables
directamente
enterrados
Cables
bajo tubo
Separacin
de los ternos
10
0,76
0,65
0,58
0,53
0,50
0,47
0,45
0,43
0,42
0,82
0,86
0,88
0,90
0,73
0,78
0,82
0,85
0,68
0,75
0,79
0,83
0,64
0,72
0,77
0,81
0,61
0,70
0,76
0,80
0,59
0,68
0,74
0,79
0,57
0,67
0,74
0,56
0,66
0,73
0,55
0,65
En contacto
(d = 0 cm)
0,80
0,70
0,64
0,60
0,57
0,54
0,52
0,50
0,49
d = 0,2 m
d = 0,4 m
d = 0,6 m
d = 0,8 m
0,83
0,87
0,89
0,90
0,75
0,80
0,83
0,86
0,70
0,77
0,81
0,84
0,67
0,74
0,79
0,82
0,64
0,72
0,78
0,81
0,62
0,71
0,77
0,60
0,70
0,76
0,59
0,69
0,75
0,58
0,68
En contacto
(d = 0 cm)
d = 0,2 m
d = 0,4 m
d = 0,6 m
d = 0,8 m
KA = 0,70
Y por ltimo la profundidad tambin debe ser considerada al ser distinta al valor de referencia de 1 m. 1,25 m de profundidad nos aportan un
coeficiente de 0,98 en la tabla 11 del RLAT (o tabla 4 de la pgina 15) suponiendo de inicio que la seccin resultado ser superior a 185 mm2, algo
previsible pues partimos de una intensidad de 280 A.
31
media tensin
introduccin tcnica
Profundidad
(m)
185 mm2
185 mm2
1,06
1,04
1,02
1,00
0,98
0,97
0,96
0,95
0,93
0,92
1,09
1,07
1,03
1,00
0,98
0,96
0,94
0,93
0,91
0,89
1,06
1,04
1,02
1,00
0,98
0,97
0,96
0,95
0,93
0,92
1,08
1,06
1,03
1,00
0,98
0,96
0,95
0,94
0,92
0,91
0,50
0,60
0,80
1,00
1,25
1,50
1,75
2,00
2,50
3,00
KP = 0,98
Resumiendo:
KT = 1,04 (temperatura)
KR = 1,00 (resistividad trmica)
KA = 0,70 (agrupamiento)
KP = 0,98 (profundidad)
I = Itabla 12 KT KR KA KP
I
280 A
La seccin cuya intensidad corregida I' sea mayor que I = 280 A (dato inicial) ser la adecuada.
Probamos con el cable de 300 mm2 para ver si cumple la condicin. Tomamos el valor de intensidad de la tabla 12 y aplicamos los coeficientes.
Se corresponde con la tabla IX de los cables Voltalene de este catlogo.
Tensin nominal
90 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
92
120
145
170
210
255
295
335
385
455
520
610
715
830
80
110
130
155
195
235
270
305
345
405
465
-
78
100
120
140
170
205
235
260
295
345
390
445
505
575
32
74
94
110
130
160
190
215
245
280
320
365
415
480
545
76
95
115
135
165
200
225
255
285
330
375
-
70
90
105
125
155
180
205
230
260
305
345
-
media tensin
introduccin tcnica
I = 365 x KT KR KA KP = 365 X 1,04 x 1,00 x 0,70 x 0,98 = 260,4 A < 280 A y por tanto la seccin de 300 mm2 no satisface la intensidad admisible
que necesitamos.
Probamos con la siguiente seccin, 400 mm2:
Tensin nominal
90 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
92
120
145
170
210
255
295
335
385
455
520
610
715
830
80
110
130
155
195
235
270
305
345
405
465
-
78
100
120
140
170
205
235
260
295
345
390
445
505
575
74
94
110
130
160
190
215
245
280
320
365
415
480
545
76
95
115
135
165
200
225
255
285
330
375
-
70
90
105
125
155
180
205
230
260
305
345
-
I = 415 x KT KR KA KP = 415 X 1,04 x 1,00 x 0,70 x 0,98 = 296,1 A > 280 A y por tanto la seccin de 400 mm2 sera la seccin a instalar.
Ahora procedera comprobar si se cumple el criterio de la cada de tensin y del cortocircuito mximo admisible para saber si la seccin de 400 mm2
es la mnima que cumple los requisitos tcnicos.
Recomendamos, que una vez se sepa el valor de la seccin mnima admisible tcnicamente se haga el clculo de la seccin econmica y se tengan
en cuenta las reducciones de emisiones de CO2 que puede conseguir con secciones superiores por reduccin de las prdidas resistivas. Con secciones
superiores conseguir adems: prolongar la vida til de la lnea al ir ms descargada, mejorar la respuesta a fenmenos transitorios y tener la
posibilidad de aumentar la potencia en un futuro sin cambiar de cable.
33
media tensin
introduccin tcnica
20 C
Cable Al Voltalene
1,25 m
RT = 1,5 Km/W
Circuitos en contacto
Nuevo circuito
En estas condiciones recordemos que la seccin por el criterio de la intensidad admisible es de 400 mm2 dado que al aplicar los coeficientes de
correccin (ya que las condiciones de la lnea se desvan del estndar) al valor de la intensidad tabulada para cable con aislamiento de XLPE de
aluminio nos satisfaca la condicin siguiente (ver ejemplo anterior):
I' = 415 x KT KR KA KP = 415 x 1,04 x 1,00 x 0,70 x 0,98 = 296,1 A > 280 A (ver ejemplo anterior)
Siendo 415 A la intensidad mxima admisible para cable de 400 mm2 en condiciones estndares (ver tabla 12, ITC-LAT 06) y KT, KR, KA y KP los
coeficientes de correccin por temperatura, resistividad trmica del terreno, agrupamiento y profundidad de nuestra instalacin respectivamente.
Con un simple clculo podemos saber la cada de tensin mxima en la lnea. Toda vez que sabemos que el valor aproximado de la cada de tensin
en un sistema trifsico se obtiene con la frmula:
U = 3LI(Rcos+Xsen)
Donde:
U: es la cada de tensin en V
L: longitud de la lnea en km
I: intensidad de corriente que recorre la lnea en A
R: resistencia del conductor en /km (valores reflejados en este catlogo)
X: reactancia de la lnea en /km (valores reflejados en este catlogo)
34
media tensin
introduccin tcnica
Tomando los valores de R y X que, para cable Al Voltalene de 1x400 de 12/20 kV, figuran en las pginas 105 y 106
U = 3 x 0,8 x 280 x (0,105 x 0,9 + 0,101 x 0,436) = 53,75 V
Expresado porcentualmente, sabiendo que la tensin de lnea es de 20 kV:
U = 51,66/20000 x 100 0,27 %
Los valores calculados parten de la suposicin de tener el cable a mxima solicitacin trmica, pues la resistencia introducida en la frmula
(0,105 /km) est clculada a 90 C (mxima temperatura en cables con aislamiento de XLPE) tal y como dice la tabla del catlogo.
Si queremos saber la cada de tensin a la temperatura real del conductor, debemos calcular la resistencia a esa temperatura real y por tanto conocer
su valor.
Para ello recurrimos a la frmula de clculo de la temperatura del conductor:
T = Tamb + (Tmax - Tamb) (I/Imax)2
Donde:
Tamb: temperatura ambiente de la instalacin (20 C en nuestro caso)
Tmx: temperatura mxima que puede soportar el conductor (90 C para el cable Al Voltalene de nuestro ejemplo)
I: intensidad que recorre el conductor (280 A)
Imx: intensidad mxima que puede recorrer el conductor en las condiciones de la instalacin (296,1 A). Este es el valor mximo de corriente que
podra circular por el conductor en las condiciones de instalacin en las que se encuentra. (Ver clculo realizado anteriormente con los coeficientes
de correccin)
Por tanto:
T = 20 + (90 - 20) (280/296,1)2 = 82,6 C
Y la resistencia de un conductor a una temperatura X determinada se obtiene con la siguiente expresin:
RT = R20 (1 + (T - 20))
Donde:
RT: valor de la resistencia del conductor en /km a la temperatura T
R20: valor de la resistencia del conductor a 20 C (valor tpicamente tabulado). Al cable de 400 mm2 de aluminio corresponde una resistencia de
0,0778 /km a 20 C (pgina 104).
: coeficiente de variacin de resistencia especfica por temperatura del conductor en C-1 (0,00392 para Cu y 0,00403 para Al)
T: temperatura real del conductor (C)
Sustituyendo:
R82,6 C = 0,0778 x (1 + 0,00403 x (82,6 - 20)) = 0,097 /km
Con lo que la cada de tensin a la temperatura a la que realmente est el conductor ser de:
U = 3 x 0,8 x 280 x (0,097 x 0,9 + 0,101 x 0,436) = 50,95 V
Y en tanto por ciento:
U = 50,95/20000 x 100 = 0,25475 %
Como vemos el valor es inferior que anteriormente porque en el caso anterior se supuso el cable a 90 C.
No han salido valores muy dispares por estar el cable sometido a una intensidad cercana al mximo admisible (280 A est cercano a 296,1 A), si
fuera ms distante por dominar, por ejemplo, el criterio de cortocircuito frente al de la intensidad admisible el valor calculado segn este ltimo
mtodo reflejara una diferencia mayor.
35
media tensin
introduccin tcnica
25 C
1,5 m
RT = 1,5 Km/W
Circuito en contacto
Nuevo circuito
Primeramente calculamos la seccin por el criterio de la intensidad admisible.
S = 3 . U . I
I=
3 . U
I=
2500 x 103
3 x 18000
= 80,2A
Como las condiciones de la lnea difieren de las estndares para las que se han calculado las intensidades admisibles de la tabla 6 de la ITCLAT 06 del RLAT (intensidades para cables directamente enterrados) o tabla IX de cables tipo Eprotenax Compact debemos utilizar coeficientes
de correccin.
Profundidad de instalacin 1,5 m
Agrupacin con otro circuito
KP = 0,97 (tabla 11, ITC-LAT 06 o tabla del punto 4 de la pgina 15 de este catlogo)
KA = 0,76 (tabla 10, ITC-LAT 06 o tabla del punto 3 de la pgina 15 de este catlogo)
36
media tensin
introduccin tcnica
Tensin nominal
105 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
92
125
150
180
225
275
320
360
415
495
565
660
775
905
80
110
135
160
200
240
280
315
360
425
485
-
82
105
125
145
180
215
245
275
315
365
410
470
540
615
76
95
115
135
170
200
230
255
290
345
390
450
515
590
78
100
120
145
170
205
235
265
295
345
390
-
72
95
110
130
160
190
215
240
275
325
365
-
Este clculo se puede realizar con igual resultado tomando los valores de la tabla, multiplicndolos por los coeficientes y comparando con la
intensidad de la lnea pero suele ser un poco ms laborioso:
Para 25 mm2
Itabla25 Kp KA
Para 35 mm2
Itabla25 Kp KA
Como punto de partida para el clculo de la seccin por cortocircuito tenemos la seccin de 35 mm2 (mnimo valor aceptable por calentamiento)
de Al Eprotenax Compact (aislamiento HEPR). Vamos a comprobar inicialmente si esta seccin nos soportar el cortocircuito mximo previsto. Para
ello recurrimos a la tabla 26 de la ITC-LAT 06 del RLAT en la que tenemos los valores mximos de densidad de corriente en A/mm2 en funcin del
tiempo de duracin del cortocircuito para conductores de aluminio.
Tipo de
aislamiento
PVC:
seccin 300 mm2
seccin > 300 mm2
XLPE, EPR y HEPR
HEPR Uo/U 18/30 kV
(K)
0,1
0,2
0,3
0,5
0,6
1,0
1,5
2,0
2,5
3,0
90
70
160
145
240
215
298
281
170
152
211
199
138
124
172
162
107
96
133
126
98
87
122
115
76
68
94
89
62
55
77
73
53
48
66
63
48
43
59
56
43
49
54
51
Esta tabla recoge los resultados de aplicacin de la siguiente frmula para el cortocircuito:
Icc =
K.S
tcc
37
media tensin
introduccin tcnica
Donde:
Icc : corriente de cortocircuito (A)
S: seccin del conductor, en mm2
K: coeficiente que depende de la naturaleza del conductor y de las temperaturas al inicio y final del cortocircuito. Coincide lgicamente con el valor
de la densidad de corriente para cortocircuito de duracin 1s.
tcc : duracin del cortocircuito, en segundos (0,1 s tcc 5 s)
Para comprobar si la seccin de 35 mm2 soporta el cortocircuito, primero calculemos la Icc mxima a soportar por la lnea a partir de la potencia
de cortocircuito de los datos iniciales:
Scc = 3 U Icc Icc = Scc / ( 3 U) Icc = 400 x 106 / ( 3 x 18000) = 12830 A
Ahora tomando el valor de la tabla 26 (162 A/mm2) no tenemos ms que multiplicarlo por la seccin del conductor y sabremos que cortocircuito
mximo soporta el cable en el tiempo de disparo de las protecciones (0,3 s).
Icc35 = 162 A/mm2 x 35 mm2 = 5670 A < 12830 A
Como el valor obtenido es menor que los 12860 A tendremos que emplear una seccin mayor. Probamos por tanto con las secciones superiores:
Icc50 = 162 A/mm2 x 50 mm2 = 8100 A < 12830 A
Icc70 = 162 A/mm2 x 70 mm2 = 11340 A < 12830 A
Icc95 = 162 A/mm2 x 95 mm2 = 15390 A > 12830 A
Como vemos la seccin de 95 mm2 es la primera que soportara el cortocircuito y por ello es la seccin solucin. Pero podemos hacer los clculos
teniendo en cuenta la temperatura inicial real a la que est el conductor realmente lo que nos lleva a obtener intensidades de cortocircuito mayores
en los cables, ya que la tabla 26 est realizada en base al caso ms desfavorable, que sera cuando el cable est en rgimen permanente a mxima
solicitacin, es decir, en nuestro caso cuando el cable llevara la mxima intensidad admisible en rgimen permanente y por tanto su temperatura
sera de 105 C al tratarse de aislamiento de HEPR.
Ya sabemos que la seccin de 95 mm2 soportara el cortocircuito, ahora nos interesa saber si podemos utilizar una seccin inferior que nos garantice
igualmente una respuesta adecuada, por tanto procedemos a hacer nmeros ms afinados con la seccin de 70 mm2.
En el apartado 6.2 de la ITC-LAT 06 del RLAT encontramos que si queremos calcular el cortocircuito mximo teniendo en cuenta la temperatura
inicial del conductor no tendramos ms que utilizar la frmula empleada anteriormente afectando el segundo trmino de un factor que depende
de la temperatura inicial y final del conductor y de la naturaleza del conductor y su aislamiento.
Icc =
KS
tcc
ln
Tcc +
Ti +
ln
Tcc +
Ts +
Donde:
Tcc: mxima temperatura de cortocircuito admisible (250 C para cables de HEPR y XLPE)
Ti: temperatura del conductor en rgimen permanente. Es la temperatura a la que se inicia el cortocircuito
Ts: temperatura mxima del conductor en rgimen permanente (105 C para cables con aislamiento de HEPR y 90 C para cables con aislamiento
de XLPE)
: 235 para cobre y 228 para aluminio
Tenemos todos los valores excepto la temperatura inicial del conductor (Ti). Por lo que debemos calcularla con la siguiente expresin:
Ti = Tamb + (Ts Tamb) (I/Imax)2
Donde:
Ti: temperatura del conductor en rgimen permanente (cuando circulan 80,2 A)
Tamb: temperatura ambiente de la instalacin (25 C en nuestro caso)
Ts: temperatura mxima que puede soportar el conductor (105 C para el cable Al Eprotenax Compact de nuestro ejemplo, aislamiento de HEPR)
I: intensidad que recorre el conductor (80,2 A)
Imx: intensidad mxima que puede recorrer el conductor en las condiciones de la instalacin (Imx70 = Itabla70 Kp Ka = 180 x 0,97 x 0,76 = 132,7 A)
(ver tabla de intensidades admisibles de la que se ha tomado el valor para 70 mm2, 180 A)
38
media tensin
introduccin tcnica
Sustituyendo
Ti70 = 25 + (105-25) x (80,2/132,7)2 = 54,22 C
Por lo que la intensidad de cortocircuito ser:
Icc70 =
89 70
0,3
ln
250 + 228
54,22 + 228
250 + 228
ln
105 + 228
= 13733 A > 12830 A, por tanto la seccin de 70 mm2 soportara la intensidad de cortocircuito de 12830 A
durante los 0,3 s de tiempo hasta el disparo de las protecciones.
Icc50 =
89 50
0,3
ln
250 + 228
70 + 228
250 + 228
ln
105 + 228
El conductor de 50 mm2 no soporta la intensidad de cortocircuito como vemos. La solucin es por lo tanto 70 mm2.
No obstante tendramos ahora que plantear el concepto de seccin comercial como aquella seccin que es ms fcil encontrar en stock y sobre
todo es ms econmica al no tener que acogernos a plazos de suministro ni a mnimos de fabricacin. Hay una serie de secciones de gran consumo
y por tanto de frecuente fabricacin que el proyectista debe tener en cuenta y as facilitar el suministro en obra. En el ejemplo desarrollado convendra
que finalmente la seccin a utilizar fuera de 95 mm2 12/20 kV Al Eprotenax Compact, al ser un tipo de cable y una seccin de consumo frecuente
as como 150, 240 y 400.
Prysmian fabrica y provee las secciones que usted necesite, se trate de cables unipolares o multipolares, de cobre o aluminio, con XLPE o HEPR,
armados o sin armar, de una u otra tensin... pero, si no se trata de las secciones de ms comn suministro, normalmente es necesario encargar
un mnimo metraje o consultar existencias.
39
media tensin
introduccin tcnica
Intensidad (A)
255 A
216 A
40 A
Hora del da
0
17
24
Procedemos a calcular las prdidas resistivas que tenemos en el cable considerando la temperatura del conductor para obtener la resistencia del
cable cuando es recorrido por 216 A o por 40 A.
Clculo de la resistencia a la temperatura real del conductor para el caso del cable de 150 mm2 de aluminio cuando es recorrido por 216 A.
Sabemos que la temperatura de un conductor recorrido por una corriente I se puede obtener con la siguiente expresin:
T = Tamb + (Tmx - Tamb) (I/Imx)2
Siendo:
Tamb: temperatura ambiente de la instalacin (25 C en nuestro caso)
Tmx: temperatura mxima que puede soportar el conductor (105 C para el cable Al Eprotenax Compact de nuestro ejemplo)
I: intensidad que recorre el conductor (216 A de 8 a 17 horas y 40 A el resto del tiempo)
Imx: intensidad mxima que puede recorrer el conductor en las condiciones de la instalacin (255 A)
T150 a 216 A = 25 + (105 - 25) (216/255)2 = 82,4 C
Una vez que hemos calculado la temperatura, podemos obtener la resistencia del cable
RT = R20 (1 + (T - 20))
40
media tensin
introduccin tcnica
Donde:
RT: valor de la resistencia del conductor en /km
R20: valor de la resistencia del conductor a 20 C (valor tpicamente tabulado). Al cable de 150 mm2 de aluminio corresponde una resistencia de
0,206 /km (ver pgina 80)
: coeficiente de variacin de resistencia especfica por temperatura del conductor en C-1 (0,00392 para Cu y 0,00403 para Al)
T: temperatura real del conductor (C)
R150 a 82,4 C = 0,206 x (1 + 0,00403 x (82,4 - 20)) = 0,258 /km
Y anlogamente cuando la intensidad es de 40 A, la temperatura del conductor es de 26,97 C y la resistencia toma el valor de 0,212 /km.
La energa perdida en la lnea por efecto Joule con cable de 150 mm2 durante un ao ser
EP = 3 x R . I2 . L . t/1000 (kWh)
R: resistencia en /km
I: intensidad en A
L: longitud de la lnea en km
t = tiempo en h
Durante el tiempo que por la lnea circulan 40 A tendremos para un periodo de un ao:
EP1-150 = 3 x 0,212 x 402 x 1 x 15 x 365/1000 = 5571 kW.h
Y el resto del tiempo, 9 horas diarias, circulan 216 A:
EP2-150 = 3 x 0,258 x 2162 x 1 x 9 x 365/1000 = 118627 kW.h
EP-150 = 5.571 + 118627 = 124198 kW.h
Y el coste de estas prdidas suponiendo una tarifa media de 0,09 /kW.h sera de:
CP-150 = 124198 kW.h x 0,09 /kW.h = 11178 (en un ao)
Si aumentamos la seccin hasta cable de 240, vamos a ver cuanto nos incrementa el precio el cable y cuanta energa ahorramos, y por tanto dinero,
al tener menos prdidas resistivas (efecto Joule). Y as sabremos si compensa poner una seccin mayor.
Resistencia del cable Al Eprotenax Compact 1x240:
-Cuando circulan 40 A la temperatura del conductor es de 26,07 C y su resistencia aproximada es de 0,126 /km
-Cuando la intensidad es de 216 A la temperatura del conductor es de unos 56,36 C y su resistencia es de 0,143 /km
Siguiendo el mismo procedimiento que con el cable de 150:
Durante el tiempo que por la lnea circulan 40 A tendremos para un periodo de un ao:
EP1-240 = 3 x 0,126 x 402 x 1 x 15 x 365/1000 = 3311 kW.h
Y el resto del tiempo (circulan 216 A)
EP1-240 = 3 x 0,143 x 2162 x 1 x 9 x 365/1000 = 65751 kW.h
EP-240 = 3311 + 65751 = 69062 kW.h
Y el coste de estas prdidas suponiendo una tarifa media de 0,09 /kW.h sera de:
CP-240 = 69062 kW.h x 0,09 /kW.h = 6216 (en un ao)
Por tanto el ahorro de energa (no consumida en la lnea) en un ao con la nueva seccin ser la diferencia entre lo gastado con la seccin
de 150 mm2 (11.178 ) y lo gastado con la seccin de 240 mm2 (6.216 ):
41
media tensin
introduccin tcnica
1335 kg/km
1786 kg/km
CO2
42
CO2
media tensin
introduccin tcnica
Si quisiramos simplificar los clculos, podemos tomar los valores tabulados de resistencia del cable a 20 C. Los resultados sern algo ms pesimistas
pero podremos valorar ms rpidamente el ahorro porque estaremos bajo un supuesto ms desfavorable que el real.
Por tanto la seccin de 1x240 mm2 se demuestra no slo como econmicamente mucho ms interesante sino tambin ecolgicamente.
Hemos considerado poco relevantes los incrementos de costes asociados al aumento de seccin ms all del mayor coste del cable. Sean, si
procediera, costes de tendido, tubera, protecciones (si se quieren considerar se pueden sumar a los 4000 estimados y fcilmente se puede
estimar como en el ejemplo la diferencia de coste sigue siendo abismal). Igualmente no se ha actualizado en valor de los ahorros anuales en
energa dado que igualmente la tarifa elctrica es susceptible de incrementarse en el tiempo.
ECOLGICOS
ECONMICOS
150 mm2
Resistencia con I = 40 A
(/km)
(/km)
0,258
(kW h)
124198
()
11178
()
335340
Peso
(kg/km)
1335
(kg CO2)
(kg CO2)
(kg CO2)
240 mm2
0,212
0,128
Diferencia
Diferencia (%)
0,084
-40
0,143
0,115
-45
69092
55136
-44
6216
4962
-44
186480
148860
-44
1786
-451
34
56647
75784
-19137
34
48437
26934
21503
-44
1453110
808020
645090
-44
Haga nmeros para cuantificar los beneficios que le comportar la seccin econmica y ver como los resultados le recompensan y adems obtendr
otras importantsimas ventajas colaterales como:
- Mayor vida til de la lnea al ir ms descargada
- Mejor respuesta a fenmenos transitorios
- Posibilidad de ampliacin de potencia sin cambiar el cable
- Ahorro de emisiones de CO2
43
media tensin
introduccin tcnica
Seccin nominal
mm2
10
15
25
35
50
70
95
125
160
200
250
300
400
500
600
Densidad de corriente
A/mm2
Cobre
8,75
7,60
6,35
5,75
5,10
4,50
4,05
3,70
3,40
3,20
2,90
2,75
2,50
2,30
2,10
Aluminio
6,00
5,00
4,55
4,00
3,55
3,20
2,90
2,70
2,50
2,30
2,15
1,95
1,80
1,65
44
Aleacin de aluminio
5,60
4,65
4,25
3,70
3,30
3,00
2,70
2,50
2,30
2,15
2,00
1,80
1,70
1,55
media tensin
introduccin tcnica
50 .................. 4,00
54,6 ...............
70 .................. 3,55
20 .................... 0,45
4,6 ................... x
Cdigo
LA-56
Cdigo antiguo
94-AL1/22-ST1A
LA-110
Norma
LA-180
LA-280
HAWK
LA-380
GULL
LA-455
CONDOR
7x2,82 +
54x2,82
2,82
8,46
2,82
25,38
43,7
337,3
381
342
933
1275
109
0,0857
7x3,08 +
54x3,08
3,08
9,24
3,08
27,72
52,2
402,3
454,6
408,9
1112
1521
124
0,0718
UNE EN 50182
mm
mm
mm
mm
mm2
mm2
mm2
kg/km
kg/km
kg/km
kN
/km
1x3,15 +
6x3,15
3,15
3,15
3,15
9,45
7,8
46,8
54,6
60,8
128,3
189,1
16,4
0,6136
7x2,00 +
30x2,0
2
6
2
14
22
94,2
116,2
172,4
260,2
433
43,1
0,3066
Tabla de caractersticas tcnicas de los conductores desnudos para lneas areas (pgina 192)
45
7x2,5 +
30x2,5
2,5
7,5
2,5
17,5
34,3
147,3
181,6
269,4
407
676
63,9
0,1962
7x2,68 +
26x3,44
2,68
8,04
3,44
21,8
39,5
241,7
281,2
310
666,7
977
84,5
0,1194
media tensin
introduccin tcnica
P(R + Xtg)
x100
U2
Sabemos que...
P = Scos = 2520 x 0,8 = 2016 kW
tg = 0,75
U = 25 kV
Ahora necesitamos calcular R y X.
Para el valor de la temperatura mxima considerada (70 C) podemos obtener el valor de R aplicando la frmula de variacin de la resistencia con
la temperatura:
R70 C LA-56 = R20 C LA-56 (1+ (70-20))L = 0,6136 x (1+0,00403 x (70-20)) x 20 = 14,74
R20 C se obtiene de la tabla de datos de los conductores desnudos y el valor de variacin de la resistencia especfica por temperatura del conductor
es igualmente un dato conocido.
Para obtener la reactancia aplicamos la siguiente frmula:
X = L = 2 x x 50 x (0,5+4,6 x log(DMG/r)) x 10-4 x L
Donde DMG es la distancia media geomtrica en mm, r el radio del conductor en mm y L es la longitud de la lnea en km.
DMG = (a12a13a23)1/3
1
a12
2
a13
a23
En nuestro caso las 3 distancias son iguales y por tanto DMG = 1,2 m.
El radio del conductor r es 9,45/2 mm (ver tabla).
Y la longitud de la lnea L es de 20 km.
XLA-56 = L = 2 x x 50 x (0,5+4,6 x log(3000/90)) x 10-4 x 20 = 7,26
Ahora ya podemos obtener la cada de tensin:
U (%)LA 56 =
P(R + Xtg )
2016000x (14,74 + 7,26 x 0,75)
x 100 =
x 100 = 6,51 %
2
U
250002
P(R + Xtg)
U2
x 100 =
46
x 100 = 4,01%
media tensin
introduccin tcnica
3RI
3RI
100 =
100 =
3 U I cos
3 U I cos
3R
P
3 U I cos
3 U I cos
14,74x2016000
RP
100 =
x 100 = 7,43 %
U2 cos2
250002
Y para el LA-110...
Pp LA-110 =
RP
U2 cos2
100 =
7,36x2016000
250002 x 0,82
x 100 = 3,71 %
47
100 =
RP
U2 cos2
100
48
CARACTERSTICAS
CONSTRUCTIVAS DE CABLES
HABITUALES PARA MT
49
50
media tensin
caractersticas constructivas
Por incremento del gradiente de trabajo, reduccin del espesor del aislamiento
y por su posible reduccin de una seccin del conductor.
Ms facilidad de instalacin.
51
media tensin
caractersticas constructivas
Composicin:
Conductor: cuerda redonda compacta de hilos de aluminio, clase 2, segn UNE EN 60228.
52
media tensin
caractersticas constructivas
12/20 kV
1x50/16
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
1x630/16
Cdigo
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
20996806
20994668
20995788
20995789
20996809
20034725
18,1
20,9
23,8
28
33,2
41,5
4,5
4,3
4,3
4,3
4,3
4,5
25,8
28,6
32
36
41,3
49,5
2,5
2,7
3
3
3
2,7
780
960
1200
1600
2130
3130
387
429
480
540
620
743
516
572
640
720
826
990
20020826
20996810
20996811
20996808
20993046
25,7
27,6
31,8
37
45,3
6,7
6,2
6,2
6,2
6,4
34,4
36,3
40,4
45,7
53,4
3
3
3
3
3
1330
1500
1900
2550
3600
516
545
606
686
801
688
726
808
914
1068
18/30 kV
1x95/25 (1)
1x150/25 (1)
1x240/25 (1)
1x400/25 (1)
1x630/25 (1)
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
1x50/16
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
1x630/16 (2)
12/20 kV
18/30 kV
12
20
24
125
18
30
36
170
105
250
Intensidad
Intensidad
Intensidad
Intensidad
Intensidad mxima de cortocircuito
mxima admisible mxima admisible mxima admisible
mxima de
en la pantalla durante 1 s*** (A)
bajo tubo y
directamente
al aire** (A)
cortocircuito en el
enterrado* (A)
enterrado* (A)
conductor durante
1 s (A)
12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV
135
145
180
4700
200
215
275
8930
255
275
360
14100
345
365
495
22560
450
470
660
37600
590
615
905
59220
12/20 kV
(pant, 16 mm2)
3130
3130
3130
3130
3130
3130
18/30 kV
(pant, 25 mm2)
4630
4630
4630
4630
4630
4630
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x50/16
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
1x630/16 (2)
Resistencia del
conductor a
20 C (/km)
Resistencia del
conductor a T
mx (105 C)
(/km)
Reactancia inductiva
(/km)
12/20 kV
0,132
0,118
0,110
0,102
0,096
0,090
53
18/30 kV
0,217
0,129
0,118
0,109
0,102
0,095
Capacidad
(F/km)
12/20 kV
0,147
0,283
0,333
0,435
0,501
0,614
18/30 kV
0,147
0,204
0,250
0,301
0,367
0,095
media tensin
caractersticas constructivas
12/20 kV
1x50/16
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
1x630/16
Cdigo
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
20996806
20994668
20995788
20995789
20996809
20034725
18,1
20,9
23,8
28
33,2
41,5
4,5
4,3
4,3
4,3
4,3
4,5
25,8
28,6
32
36
41,3
49,5
2,5
2,7
3
3
3
3
780
960
1200
1600
2130
3130
387
429
480
540
620
743
516
572
640
720
826
990
20010818
20015523
20015524
20015525
20082534
25,7
27,5
31,8
37
45,3
6,7
6,2
6,2
6,2
6,4
33,7
35,5
39,6
45,0
53,4
3
3
3
3
2,7
1200
1420
1780
2430
3470
506
533
594
675
801
674
710
792
900
1068
18/30 kV
1x95/16 (1)
1x150/16
1x240/16 (1)
1x400/16 (1)
1x630/16 (1)
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
1x50/16
1x95/16 (1)
1x150/16
1x240/16 (1)
1x400/16 (1)
1x630/16 (1)
12/20 kV
18/30 kV
12
20
24
125
18
30
36
170
105
250
Intensidad
Intensidad
Intensidad
mxima admisible mxima admisible
Intensidad
mxima de
Intensidad mxima de cortocircuito
bajo tubo y
directamente
mxima admisible cortocircuito en el
en la pantalla durante 1 s*** (A)
enterrado* (A)
enterrado* (A)
al aire** (A)
conductor durante
1 s (A)
12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV
4700
180
145
135
8930
275
215
200
14100
360
275
255
22560
495
365
345
37600
660
470
450
59220
905
615
590
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x50/16
1x95/16 (1)
1x150/16
1x240/16 (1)
1x400/16 (1)
1x630/16 (1)
Resistencia del
conductor a
20 C (/km)
Resistencia del
conductor a T
mx (105 C)
(/km)
Reactancia inductiva
(/km)
12/20 kV
0,132
0,118
0,110
0,102
0,096
0,090
54
18/30 kV
0,148
0,128
0,117
0,108
0,102
0,095
Capacidad
(F/km)
12/20 kV
0,147
0,283
0,333
0,345
0,501
0,614
18/30 kV
0,147
0,204
0,250
0,301
0,361
0,452
media tensin
caractersticas constructivas
NUEVO
AL RH5Z1
12/20 kV, 18/30 kV
IEC 60502-2, G3 DND003 (en lo aplicable)
Composicin:
NOTA: Ver herramientas y accesorios especficos para conexionado de pantalla (pginas 182 -185)
55
media tensin
caractersticas constructivas
DATOS TCNICOS DEL CABLE AL VOLTALENE H COMPACT (NORMALIZADO POR ENDESA, NUEVO DISEO)
AL RH5Z1
CARACTERSTICAS DIMENSIONALES
1 x seccin
conductor (Al)
(mm2)
12/20 kV
1x95 (1)
1x150 (1)
1x240 (1)
1x400 (1)
18/30 kV
1x95
1x150 (1)
1x240 (1)
1x400 (1)
Cdigo
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
20090757
20090758
20090759
20090760
21,3
24,1
28,2
33,6
4,3
4,3
4,3
4,3
29,4
32,1
36,0
41,5
2,0
2,0
2,0
2,0
860
1070
1430
2020
441
482
540
623
588
642
720
830
20090761
20090762
20090763
20090764
25,7
28,5
32,6
38,0
6,4
6,4
6,4
6,4
33,6
36,4
40,5
46,0
2,0
2,0
2,0
2,0
1060
1300
1690
2320
504
546
608
690
672
728
810
920
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(Al) (mm2)
1x95 (1)
1x150 (2)
1x240 (2)
1x400 (2)
12/20 kV
18/30 kV
12
20
24
125
18
30
36
170
90
250
Intensidad
Intensidad
Intensidad
mxima admisible mxima admisible
Intensidad
mxima de
Intensidad mxima de cortocircuito
bajo tubo y
directamente
mxima admisible cortocircuito en el
en la pantalla durante 1 s*** (A)
enterrado* (A)
enterrado* (A)
al aire** (A)
conductor durante
1 s (A)
12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV
190
205
255
8930
245
260
335
14100
320
345
455
22560
415
445
610
37600
12/20 kV
2240
2540
2990
3440
18/30 kV
2690
2990
3440
3890
(1) Seccin homologada por las compaas del Grupo Endesa en 12/20 kV
(2) Secciones homologadas por las compaas del Grupo Endesa en 12/20 kV y 18/30 kV
*Condiciones de instalacin: una terna de cables enterrado a 1 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1,5 Km/W
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C
1 x seccin
conductor
(Al) (mm2)
1x95 (1)
1x150 (2)
1x240 (2)
1x400 (2)
Resistencia del
conductor a
20 C (/km)
Resistencia del
conductor a T
mx (90 C)
(/km)
Reactancia inductiva
(/km)
12/20 kV
0,123
0,114
0,106
0,099
(1) Seccin homologada por las compaas del Grupo Endesa en 12/20 kV
(2) Secciones homologadas por las compaas del Grupo Endesa en 12/20 kV y 18/30 kV
NOTA: valores obtenidos para una terna de cables al tresbolillo y con los cables en contacto.
56
18/30 kV
0,132
0,123
0,114
0,106
Capacidad
(F/km)
12/20 kV
0,217
0,254
0,306
0,376
18/30 kV
0,167
0,192
0,229
0,277
media tensin
caractersticas constructivas
57
media tensin
caractersticas constructivas
AL RHZ1-OL
12/20 kV, 18/30 kV
UNE HD 620-5E
Composicin:
Pantalla metlica: hilos de cobre en hlice con cinta de cobre a contraespina. Seccin total 16 mm2.
58
media tensin
caractersticas constructivas
DATOS TCNICOS DEL CABLE AL VOLTALENE (NORMALIZADO POR ENDESA. DISEO TRADICIONAL)
AL RHZ1-OL
CARACTERSTICAS DIMENSIONALES
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
18/30 kV
1x95/16
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
Cdigo
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
20986136
20981089
20981091
20981092
23,3
26,2
30,4
35,6
5,5
5,5
5,5
5,5
31
34
38
43,3
2,5
2,5
2,5
2,5
1020
1250
1620
2200
465
510
570
650
620
680
760
866
20045773
20031318
20025636
20012187
28,3
31,2
35,4
40,6
8
8
8
8
36
39
43
48,3
2,5
2,5
2,5
2,5
1270
1500
1910
2510
540
585
645
725
720
780
860
966
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
1x95/16 (1)
1x150/16 (2)
1x240/16 (2)
1x400/16 (2)
12/20 kV
18/30 kV
12
20
24
125
18
30
36
170
90
250
Intensidad
Intensidad
Intensidad
mxima admisible mxima admisible
Intensidad
mxima de
Intensidad mxima de cortocircuito
bajo tubo y
directamente
mxima admisible cortocircuito en el
en la pantalla durante 1 s*** (A)
enterrado* (A)
enterrado* (A)
al aire** (A)
conductor durante
1 s (A)
12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV 12/20 kV y 18/30 kV
190
205
255
8930
245
260
335
14100
320
345
455
22560
415
445
610
37600
(1) Seccin homologada por las compaas del Grupo Endesa en 12/20 kV
(2) Secciones homologadas por las compaas del Grupo Endesa en 12/20 kV y 18/30 kV
*Condiciones de instalacin: una terna de cables enterrado a 1 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1,5 Km/W
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C
***Calculado de acuerdo con la norma IEC 60949
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
1x95/16 (1)
1x150/16 (2)
1x240/16 (2)
1x400/16 (2)
Resistencia del
conductor a
20 C (/km)
Resistencia del
conductor a T
mx (90 C)
(/km)
Reactancia inductiva
(/km)
12/20 kV
0,123
0,114
0,106
0,099
(1) Seccin homologada por las compaas del Grupo Endesa en 12/20 kV
(2) Secciones homologadas por las compaas del Grupo Endesa en 12/20 kV y 18/30 kV
NOTA: valores obtenidos para una terna de cables al tresbolillo y con los cables en contacto.
59
18/30 kV
0,132
0,123
0,114
0,106
Capacidad
(F/km)
12/20 kV
0,217
0,254
0,306
0,376
18/30 kV
0,167
0,192
0,229
0,277
media tensin
caractersticas constructivas
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
Cdigo
20986136
20981089
20981091
20981092
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
23,3
26,2
30,4
35,6
5,5
5,5
5,5
5,5
31
34
38
43,3
2,5
2,5
2,5
2,5
1020
1250
1620
2200
465
510
570
650
Radio de
curvatura
dinmico
(durante tendido)
(mm)
620
680
760
866
CARACTERSTICAS ELCTRICAS
12/20 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(AI)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
12
20
24
125
90
250
Intensidad
Intensidad
Intensidad
mxima admisible mxima admisible
Intensidad
mxima de
Intensidad mxima de cortocircuito
bajo tubo y
directamente
mxima admisible cortocircuito en el
en la pantalla durante 1 s*** (A)
enterrado* (A)
enterrado* (A)
al aire** (A)
conductor durante
1 s (A)
190
245
320
415
205
260
345
445
255
335
455
610
8930
14100
22560
37600
3130
3130
3130
3130
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
Resistencia del
conductor a
20 C (/km)
0,320
0,206
0,125
0,078
Resistencia del
conductor a T
mx (90 C)
(/km)
Reactancia inductiva
(/km)
Capacidad
(F/km)
0,123
0,114
0,106
0,099
0,217
0,254
0,306
0,376
0,410
0,264
0,161
0,100
60
media tensin
caractersticas constructivas
Composicin:
61
media tensin
caractersticas constructivas
DATOS TCNICOS DEL CABLE AL VOLTALENE H (NORMALIZADO POR GAS NATURAL FENOSA)
AL RHZ1-2OL
CARACTERSTICAS DIMENSIONALES
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
Cdigo
37012063
37012064
37012065
20082438
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
23,3
26,1
30,2
36,7
5,5
5,5
5,5
5,5
31,7
34,4
40
44,7
2,5
2,7
2,7
2,7
1020
1260
1640
2300
476
516
600
671
Radio de
curvatura
dinmico
(durante tendido)
(mm)
634
688
800
894
CARACTERSTICAS ELCTRICAS
12/20 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(AI)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
12
20
24
125
90
250
Intensidad
Intensidad
Intensidad
mxima admisible mxima admisible
Intensidad
mxima de
Intensidad mxima de cortocircuito
bajo tubo y
directamente
mxima admisible cortocircuito en el
en la pantalla durante 1 s*** (A)
enterrado* (A)
enterrado* (A)
al aire** (A)
conductor durante
1 s (A)
190
245
320
415
205
260
345
445
255
335
455
610
8930
14100
22560
37600
3130
3130
3130
3130
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
12/20 kV
1x95/16 (1)
1x150/16 (1)
1x240/16 (1)
1x400/16 (1)
Resistencia del
conductor a
20 C (/km)
0,320
0,206
0,125
0,078
Resistencia del
conductor a T
mx (90 C)
(/km)
Reactancia inductiva
(/km)
0,430
0,277
0,168
0,105
0,125
0,117
0,104
0,100
62
Capacidad
(F/km)
0,217
0,254
0,306
0,387
media tensin
caractersticas constructivas
CABLE AL VOLTALENE H LXHIOZ1 6/10 kV, 8,7/15 kV, 12/20 kV, 18/30 kV
CABLE NORMALIZADO POR: EDP
Tipo:
LXHIOZ1 (be), LXHIOZ1 (be, frt), XHIOZ1 (be), XHIOZ1 (be, frt)
Tensin:
6/10 kV, 8,7/15 kV, 18/30 kV
Norma de diseo: DMA-C33-251/E, HD 620-1, IEC 60502-2
Composicin:
Pantalla metlica: corona de hilos de cobre en hlice con cinta de cobre a contraespira.
Seccin 16 mm2.
Proteccin contra el agua: cintas hinchantes (be).
63
media tensin
caractersticas constructivas
6/10 kV
1x120/16 (1)
1x240/16 (1)
8,7/15 kV
1x120/16 (1)
1x240/16 (1)
18/30 kV
1x120/16 (1)
1x240/16 (1)
Cdigo
nominal
aislamiento*
(mm)
Espesor
aislamiento
(mm)
nominal
exterior* (mm)
Espesor cubierta
(mm)
Peso
aproximado*
(kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
20083470
20083471
20,8
26,4
3,4
3,4
28,8
34,2
1,9
2,1
950
1430
432
513
576
684
20083472
20083473
23,0
28,6
4,5
4,5
31,0
36,6
2,0
2,2
1060
1550
465
549
620
732
20083474
20083475
30,0
35,6
8,0
8,0
38,3
44,0
2,2
2,4
1430
1980
575
660
766
880
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
1x120/16 (1)
1x240/16 (1)
6/10 kV
7/15 kV
18/30 kV
6
10
12
75
8,7
15
17,5
95
90
250
18
30
36
170
Intensidad
Intensidad
Intensidad
mxima admisible mxima admisible
Intensidad
mxima de
Intensidad mxima de cortocircuito
bajo tubo y
directamente
mxima admisible cortocircuito en el
en la pantalla durante 1 s*** (A)
enterrado* (A)
enterrado* (A)
al aire** (A)
conductor durante
1 s (A)
6/10 kV, 8,7/15 kV
y 18/30 kV
215
320
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
1x120/16 (1)
1x240/16 (1)
Resistencia del
conductor a
20 C (/km)
Resistencia del
conductor a T
mx (90 C)
(/km)
Reactancia inductiva
(/km)
Capacidad
(F/km)
6/10 kV
8,7/15 kV
18/30 kV
6/10 kV
8,7/15 kV
18/30 kV
0,110
0,099
0,115
0,103
0,129
0,115
0,351
0,465
0,280
0,364
0,182
0,231
64
media tensin
caractersticas constructivas
*Para distribucin trifsica es un cable de 6/10 kV pero al utilizarse como primario de balizamiento los receptores se conectan en serie y no tiene
sentido hablar de tensin entre fases (10 kV). La revisin vigente de la norma UNE 21161 establece como tensin asignada 5 kV, ya que es la
tensin ms alta que suele utilizarse en los circuitos serie de ayudas visuales de aeropuertos.
Composicin:
1
Pantalla metlica: cinta de cobre en hlice aplicada con sobreposicin. Espesor nominal = 0,1 mm.
Cubierta exterior: tipo AFUMEX en versin AFUMEX H y tipo PVC Flam para versin VOLTALENE H.
Espesor nominal = 2 mm.
Dimetro exterior del cable = 18 0,5 mm.
Color rojo.
R (90 C,c.a.) = 3,93 /km.m
C = 0,132 F/km.
X L (un cable solo)=0,842 /km.
X L (dos cables juntos)=0,172 /km.
La versin AFUMEX comporta las mejores propiedades frente al fuego. Supera los siguientes ensayos:
No propagacin de la llama. UNE EN 60332-1-2*.
No propagacion del incendio. UNE EN 60332-3-24*.
Baja emisin de humos opacos. UNE EN 61034-2.
Reducida emisin de gases txicos. NES-713, NFC-20454. It =1,5.
Libre de halgenos. UNE EN 50267-2-1.
Baja corrosividad de los humos. UNE EN 50267-2-3, pH 4,3, Conductividad < 10 S/mm.
* Ensayos que tambin cumple la versin Voltalene (RHV).
Seccin conductor (mm2)
1x6
65
66
CABLES TIPO
EPROTENAX COMPACT
(aislamiento de HEPR)
67
68
media tensin
EPROTENAX
COMPACT
1 x 240/16
Las siglas AL
denotan que el
conductor es de
aluminio, si no se
indica nada, se
entiende que el
conductor es de
cobre.
Es el nombre
comercial del
cable, e indica
que el cable est
aislado con goma
etileno-propileno.
Cable apantallado
COMPACT indica
que el aislamiento
es etilenopropileno de alto
gradiente (HEPR).
La cubierta es tipo
VEMEX, (o PVC en
el caso de cables
armados).
La cifra 1 3
denota que el
cable es unipolar
o tripolar.
240 indica la
seccin del
conductor en
mm2.
16 indica la
seccin de la
pantalla en mm2.
mm2
12/20
kV
Tensin nominal
12 kV entre
conductor (fase)
y pantalla y 20 kV
entre conductores
(fases).
La tensin ms
elevada entre fases
puede ser superior
(ver tabla de la
pgina 7).
Otros ejemplos:
- Cable EPROTENAX H COMPACT 1 x 150/16 mm2 12/20 kV.
Cable unipolar, con conductor de cobre de 150 mm2 de seccin, aislado con HEPR, apantallado, con alambres de cobre de seccin total 16
mm2, no armado, para una tensin nominal de 12/20 kV y con cubierta exterior VEMEX.
- Cable AL EPROTENAX HFA COMPACT 1 x 300/16 mm2 6/10 kV.
Cable unipolar, con un conductor de aluminio de 300 mm2 de seccin, aislado con HEPR, apantallado con una corona de hilos de cobre con
una seccin total de 16 mm2, armado con flejes de aluminio, para una tensin nominal de 6/10 kV y con cubierta exterior de PVC (propia
de cables armados).
- Cable AL EPROTENAX FA COMPACT 1 x 150 mm2 1,8/3 kV.
Cable unipolar, con un conductor de aluminio de 150 mm2 de seccin, aislado con HEPR, sin pantalla, armado con flejes de aluminio, para
una tensin nominal de 1,8/3 kV y con cubierta exterior de PVC (propia de cables armados).
69
media tensin
EQUIVALENCIAS ENTRE DESIGNACIONES PRYSMIAN PARA CABLES EPROTENAX COMPACT Y DESIGNACIONES UNE
EPROTENAX
COMPACT
DENOMINACIN UNE
FORMACIN
PANTALLA
ARMADURA
Unipolar
No
Tripolar
Individual sobre
cada fase
No
No
Flejes aluminio
F1
Unipolar
Tripolar
No
Flejes acero
HFA
Unipolar
Flejes aluminio
HF
Tripolar
Flejes acero
MA 1
Unipolar
No
Alambres de
aluminio 2
M1
Tripolar
No
Alambres de
acero
HMA
Unipolar
Alambres de
aluminio 2
HM
Tripolar
Alambres de
acero
FA 1
P1
HP 3
O1
CAMPO RADIAL
HEPRZ1
Todos los cables deben disponer de una proteccin metlica que los envuelva, bien sea al menos una pantalla o una armadura. Requisito exigido
en la Norma IEC 60502 para los cables de tensin nominal superior a 1000 V.
Las secciones mnimas que figuran en el presente catlogo son las normalizadas por IEC.
Conviene tener presente que los valores que se indican en las referidas tablas no deben entenderse como exactos, sino solamente a ttulo informativo.
Son susceptibles de variacin sin previo aviso.
70
media tensin
d
Cuerda
mm
d
Semic. int.
mm
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
18/30 kV
Conductor de Cu
35
50
70
95
120
150
185
240
300
400
500
7
8,3
9,9
11,6
13,1
14,3
16
18,7
20,6
23,1
26,4
8
9,3
10,9
12,6
14,1
15,3
17
20,1
22
24,5
28,4
11
12,3
13,9
15,6
17,1
18,3
20
22,7
24,6
27,1
30,8
13
14,3
15,9
17,6
19,1
20,3
22
25,3
27,6
30,5
34,8
14,8
16,1
17,7
19,4
20,9
22,1
23,8
26,9
28,8
31,3
35,2
13,8
15,1
16,9
18,6
26,9
21,5
23,2
26,5
28,4
30,9
35
17
17,9
19,5
21,2
22,7
23,9
25,6
28,7
30,6
33,1
37,2
21,1
21,9
23
24,5
25,5
27
30,3
32,4
35,1
39,2
25,3
25,5
26
26,9
27,7
29
32,5
35,2
36,9
41
13,8
14,9
16,8
18,2
26,5
21,2
23,3
25,7
28,4
30,9
34,9
17
17,7
19,4
20,9
22,3
23,8
25,7
28
30,6
33,2
37,1
20,9
21,8
22,6
24,1
25,2
27,1
29,5
32,4
35,1
39,1
25,1
25,4
25,7
26,5
27,6
29,1
31,8
34,2
37
40,9
Conductor de Al
35
50
70
95
120
150
185
240
300
400
500
7
8,1
9,8
11,2
12,7
14
16,1
17,9
20,6
23,1
26,3
8
9,1
10,8
12,2
13,7
15
17,1
19,3
22
24,5
28,3
11
12,1
13,8
15,2
16,7
18
20,1
21,9
24,6
27,1
30,7
13
14,1
15,8
17,2
18,7
20
22,1
24,5
27,6
30,5
34,7
14,8
15,9
17,6
19
20,5
21,8
23,9
26,1
28,8
31,3
35,1
Nota: los valores de d, d y D son iguales para cables unipolares y tripolares siempre que se trate del mismo material de conductor (Cu o Al), el
mismo material de aislamiento (XLPE o HEPR) y la misma seccin y tensin. Es decir, por ejemplo un cable de 1x240, 12/20 kV, Al Eprotenax Compact
presenta iguales valores de d, d y D que un cable 3x240, 12/20 kV, Al Eprotenax Compact.
71
media tensin
ext. mm Peso kg/km ext. mm Peso kg/km ext. mm Peso kg/km ext. mm Peso kg/km ext. mm Peso kg/km
Tipo H
(no armado)
Tipo FA
(armado flejes Al)
1 x 10
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
14,8
15,7
16,9
18,0
19,3
20,9
22,6
24,1
25,3
27,2
30,3
32,4
35,1
39,6
345
420
530
650
795
1020
1295
1560
1810
2190
2825
3410
4180
5400
19,8
20,7
21,9
23,0
24,3
25,9
27,6
29,1
30,3
32,2
35,5
37,4
40,3
44,8
1 x 10
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
15,1
16,0
17,0
18,0
19,1
20,8
22,2
23,7
25,0
27,3
29,6
32,4
35,6
40,0
295
335
385
440
495
590
690
795
890
1075
1275
1540
1875
2280
20,1
21,0
22,0
23,0
24,1
25,8
27,2
28,7
30,0
32,3
34,8
37,4
40,8
45,2
H (no armado)
28,7
31,1
33,9
36,4
39,4
43,1
47,3
50,8
53,6
57,4
64,5
69,2
1385
1700
2140
2610
3175
4030
5115
6105
7035
8410
10825
12975
30,9
33,2
36,0
38,6
43,6
47,4
51,7
55,5
58,8
62,4
69,6
74,5
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
29,4
31,7
34,1
36,4
39,0
42,9
46,5
49,9
52,9
57,6
63,0
69,2
1250
1465
1705
1965
2250
2710
3235
3755
4230
5045
6050
7325
31,5
33,9
36,2
38,6
43,1
47,2
50,4
54,7
57,9
62,6
68,1
74,5
Tipo HFA
(armado flejes Al)
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
Tipo MA
(armado alambres Al)
72
20,2
21,1
22,3
23,4
24,7
26,3
28,2
29,7
31,1
32,8
36,1
38,2
40,9
45,6
560
645
770
905
1065
1310
1620
1900
2180
2570
3260
3875
4675
5975
21,2
22,1
23,3
24,4
25,7
27,5
29,2
30,9
33,1
34,8
38,1
40,2
42,9
48,5
645
735
870
1010
1175
1445
1750
2050
2425
2830
3540
4180
5010
6455
20,5
21,4
22,4
23,4
24,5
26,2
27,8
29,3
30,8
32,9
35,4
38,2
41,4
46,0
515
565
625
690
760
875
1005
1130
1255
1455
1700
2005
2380
2900
21,5
22,4
23,4
24,4
25,5
27,4
28,8
30,5
32,8
34,8
37,4
40,2
43,4
48,9
605
655
725
795
875
1010
1130
1280
1495
1705
1980
2310
2710
3400
Tipo HMA
(armado alambres AI)
34,5
36,9
39,7
42,2
45,4
49,1
53,5
57,2
60,0
64,2
71,3
76,4
2080
2390
2940
3465
4110
5045
6245
7340
8325
9845
12420
14750
36,1
38,5
42,5
45,0
48,2
51,9
56,3
60,0
63,0
67,0
75,6
80,7
2685
3115
4020
4625
5345
6385
7720
8960
10055
11645
15295
17810
35,2
37,3
39,9
42,2
45,0
48,9
52,7
56,3
59,3
64,4
69,8
76,4
1960
2205
2515
2815
3180
3715
4345
4965
5505
6485
7605
9100
36,8
39,1
42,7
45,0
47,8
51,7
55,5
59,1
62,3
67,2
74,1
80,7
2605
2910
3590
3980
4425
5060
5835
6560
7205
8320
10440
12155
media tensin
ext.
mm
Peso
kg/km
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
18,7
19,8
20,9
22,2
23,8
25,5
27,0
28,2
30,1
33,4
35,3
38,0
41,5
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
18,9
19,9
20,9
22,0
23,7
25,1
26,6
27,9
30,2
32,6
35,3
38,5
41,9
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
975
1105
1235
1400
1670
1980
2280
2650
3075
3790
4415
5255
6620
25,0
26,0
27,0
28,1
30,0
31,4
33,1
35,4
37,9
40,0
42,8
46,0
50,6
885
950
1020
1100
1235
1360
1515
1730
1950
2210
2545
2910
3525
35,2
37,7
40,3
43,3
47,4
51,2
54,7
57,4
61,3
68,8
73,3
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
35,6
38,0
40,3
42,9
47,1
50,4
53,8
56,8
62,4
66,9
73,3
2080
41,0
2850
2520
43,5
3400
3015
46,1
3950
3605
49,3
4625
4555
53,8
5680
5640
57,6
6835
6660
61,3
7960
7605
64,0
8975
9050
69,0
10600
11610
75,8
13270
13760
80,5
15555
Tripolares - 6/10 kV (Conductores de aluminio)
1830
41,4
2640
2090
43,8
2970
2370
46,1
3300
2685
48,9
3690
3245
53,5
4355
3745
56,8
4925
4300
60,4
5580
4800
63,4
6145
5690
69,2
7280
6715
73,9
8345
8125
80,5
9905
73
42,5
46,4
48,8
52,0
56,5
60,3
64,0
66,7
71,7
79,8
84,5
3610
4620
5210
5995
7195
8445
9680
10775
12700
16330
18765
42,9
46,7
48,8
51,6
56,2
59,5
63,1
66,1
71,9
77,9
84,5
3410
4185
4560
5030
5830
6510
7275
7955
9230
11310
13115
media tensin
ext.
mm
Peso
kg/km
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
18,8
19,9
21,2
22,8
24,5
26,2
27,4
29,7
32,4
34,5
37,2
40,7
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
18,9
19,9
21
22,7
24,1
25,8
27,1
29,8
31,7
34,5
37,7
41,1
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
1144
1283
1446
1688
2074
2362
2623
3036
3715
4297
5259
6403
25
26,2
27,3
29
31,4
33,1
34,4
37,1
39,2
41,8
46,4
49,8
1000
1083
1156
1279
1488
1637
1758
1990
2255
2557
3078
3520
39,7
42,1
45,5
49,3
53,2
56,6
59,4
64,1
70,7
75
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
39,9
42,1
45
49,1
52,3
55,7
58,7
64,7
69,2
75
2836
45,7
3739
3297
48,3
4273
3934
51,9
4999
4836
55,5
5971
5887
59,8
711
6863
63,4
8198
7784
66,2
9174
9174
71,1
10695
11634
77,9
13299
13643
84,1
16228
Tripolares - 8,7/15 kV (Conductores de aluminio)
2441
2702
3078
3613
4115
4669
5171
6050
7142
8407
45,9
48,3
51,4
55,3
58,9
62,5
65,5
71,7
76,4
84,1
74
3343
3669
4125
4734
5324
5975
6533
7719
8788
10969
48,4
51
54,6
58,2
62,5
66,1
70,2
75,1
81,9
86,6
4985
5599
6422
7524
8761
9946
11723
13671
16331
18684
48,6
51
54,1
58
61,6
65,2
69,5
75,7
80,4
86,6
4622
4994
5557
6254
6952
7700
9091
10462
11727
13429
media tensin
ext.
mm
Peso
kg/km
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
22,7
24
25,6
27,5
29
30,4
32,5
35,4
37,5
40,2
43,7
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
23,7
24,8
26,5
28,6
30
32
33,2
36
38,5
41,3
44,1
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
1400
1576
1902
2227
2506
2790
3190
3883
4631
5445
6636
29
30,3
32,8
34,4
35,9
37,4
39,9
42
46
49,2
52,8
1200
1297
1497
1641
1781
1925
2148
2418
2892
3264
3739
48
51
54,6
58,5
61,9
64,7
69,8
76
80,5
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
48
50,5
54,4
57,6
61
64
70
74,5
80,5
3873
54,4
4966
4492
57,6
5664
5403
61,2
6645
6491
65,3
7826
7500
68,9
8947
8454
71,7
9951
9960
77,2
11625
12411
85,1
14982
14508
89,6
17205
Tripolares - 12/20 kV (Conductores de aluminio)
3283
54,4
4362
3636
57,1
4785
4180
61
5403
4715
64,4
6031
5306
68
6715
5840
71
7305
6840
77,4
8509
7910
83,6
10444
9277
89,6
11950
75
57,1
60,3
63,9
68
73,1
75,9
81,2
87,6
92,1
6440
7245
8323
9598
11616
12704
14926
17433
19790
57,1
59,8
63,7
67,1
72,2
75,2
81,4
86,1
92,1
5840
6338
7087
8709
9342
10067
11485
12871
14536
media tensin
ext.
mm
Peso
kg/km
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
27,4
29
30,9
32,4
33,8
35,9
38,8
40,9
43,6
47,1
34,7
36,3
38,2
39,7
41,1
43,2
47,5
49,4
52,3
55,8
1841
2102
2437
2725
3016
3422
4306
4915
5761
6938
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
27,2
28,9
30,5
32
33,5
36
38,1
40,9
44,1
47,5
915
1020
1135
1240
1360
1535
1750
2025
2360
2725
34,5
36,2
37,8
39,3
40,8
43,3
46,8
49,4
52,8
56,2
1553
1697
1855
1999
2148
2381
2831
3176
3580
4055
ext.
mm
Peso
kg/km
32,8
34,7
36,1
37,8
39,1
41,8
44,1
46,7
50,1
53,5
1353
1502
1632
1786
1911
2148
2432
2739
3125
3562
ext.
mm
Peso
kg/km
57,6
61,2
65,1
68,9
71,7
76,4
82,6
87,1
2483
6236
7375
8505
9495
10974
13522
15675
64,4
68
72,1
76,1
80,6
85,5
91,9
96,4
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
57,1
61
64,2
68
71,1
76,6
81,1
87,1
76
6575
7635
8835
10095
11885
13950
16284
18567
67,1
72
76,3
80,3
83,1
88
94,4
98,9
8333
10267
11592
13029
14159
16135
18893
21357
66,6
71,8
75,4
79,7
82,5
88,2
92,9
98,9
7417
9030
9742
10741
11509
12834
14313
16103
media tensin
ext.
mm
Peso
kg/km
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
28,4
30,2
32,1
33,6
34,8
37,1
40
42,1
44,8
48,1
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
31
32,8
34,4
35
36,3
38
40,4
42,5
45,7
48,7
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
2027
2302
2641
2934
3376
3822
4534
5203
6040
7259
35,7
37,4
39
40,5
43,2
45,9
47,8
50,8
54
57,6
1748
1888
2055
2218
2516
2795
3060
3464
3864
4376
61,7
65,8
69,7
73,1
75,9
80,6
86,8
91,1
5999
7152
8342
9440
10463
11992
14624
16782
68,7
72,8
76,9
82,2
85
89,9
96,3
100,8
7496
8691
9937
11932
13029
14927
17577
19907
72,7
76,8
81,1
84,7
87,5
92,4
98,8
103,3
10128
11499
12969
14317
15471
17438
20404
22873
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
61,3
65,6
68,8
72,2
75,2
80,8
85,3
91,1
72,3
76,6
80,2
83,8
86,8
92,6
97,3
103,3
9244
10258
11109
12016
12820
14229
15750
17619
Nota:
En los cables de tensiones nominales 1,8/3 y 3,6/6 kV la pantalla metlica est formada por cintas de cobre, solapadas, arrolladas en hlice.
En los cables de tensiones nominales comprendidas entre 6/10 y 18/30 kV la pantalla metlica est constituida por una corona de hilos de cobre.
En los cables tripolares, la pantalla metlica est formada por cintas de cobre, solapadas, arrolladas en hlice sobre la capa semiconductora externa
de cada fase.
77
media tensin
Unidad
HEPR
Mecnicas
Valores en estado inicial:
- Carga rotura mnima
- Alargamiento mnimo
- Mdulo elstico mnimo al 150% de alargamiento
N/cm2
%
N/cm2
850
200
450
C
h
150
168
%
%
30
30
C
h
mg/cm2
100
24
3
%
h
0,025 a 0,030
30
C
mn.
N/cm2
%
%
200
15
20
175
15
Fsicas
a) Absorcin de agua:
- Mtodo ponderal:
Temperatura
Duracin
- Variacin de masa admitida
b) Ensayo de resistencia al ozono:
-Concentracin de ozono, en volumen
-Duracin del ensayo sin aparicin de grietas
Qumicas
Comprobacin de la reticulacin:
- Tratamiento:
Temperatura
Tiempo bajo carga
Esfuerzo mecnico
- Alargamiento mximo bajo carga
- Alargamiento permanente mximo despus del enfriamiento
Los ensayos para la comprobacin de estas caractersticas se realizan segn la Norma UNE EN 60811.
78
media tensin
TABLA II
Caractersticas de las cubiertas PVC y de poliolefinas (VEMEX DMZ1) de los cables EPROTENAX COMPACT.
Caractersticas
Unidades
Cubierta PVC
Cubierta VEMEX
(DMZ1) (habitual)
Mecnicas
a) Sin envejecimiento
- Resistencia mnima a la traccin
- Alargamiento mnimo a la rotura
N/mm2
%
12.50
150
15
500
b) Despus de envejecimiento
Tratamiento:
Temperatura
Duracin
- Resistencia mnima a la traccin
- Variacin
- Alargamiento mnimo a la rotura
- Variacin
C
h
N/mm2
%
%
%
100
168
25
25
110 2
336
300
-
C
h
N/mm2
%
%
%
100 2
168
25
25
100 2
168
300
-
C
h
mg/cm2
100
168
1.5
100 2
168
0.5
C
h
%
90
6
0.7
50
115 2
6
0.7
50
C
%
-15
20
-30 2
20
C
N/mm2
20 5
10
20 5
24
Fsico-Qumicas
a) Prdida de masa
Tratamiento:
Temperatura
Duracin
- Prdida mxima:
C
h
%
79
80 2
5x5
7
media tensin
TABLA II (CONTINUACIN)
Caractersticas de las cubiertas PVC y de poliolefinas (VEMEX DMZ1) de los cables EPROTENAX COMPACT.
Caractersticas
Unidades
Cubierta PVC
Cubierta VEMEX
(DMZ1) (habitual)
Fsico-Qumicas
f) Resistencia a la abrasin
Tratamiento:
Temperatura
Masa aplicada
Velocidad
- Mnimo nmero de desplazamientos
C
kg
m/s
-
C
h
mg/cm2
85 2
336
5
85 2
336
0.5
>1
<0.5 (*)
pH
S/mm
3
100
4,3
10
%
%
25
25
15
15
20 5
36
0.3 15%
8
Las caractersticas de la cubierta normal corresponden al tipo de mezcla ST2 (PVC) especificado en la Norma IEC 60502.
Las caracterticas de la cubierta VEMEX corresponden al tipo de mezcla de poliolefina especificado en la UNE HD 620. Los ensayos para la
comprobacin de estas caractersticas se realizan segn la Norma UNE 60811.
(*) El compuesto utilizado para la cubierta Z1 (VEMEX), no contiene hidrocarburos voltiles ni halgenos, ni metales pesados (excepto una mnima
cantidad de Pb en caso de cubiertas con coloracin roja).
TABLA III
Resistencia elctrica mxima en corriente continua a 20C en /km.
Seccin nominal
mm2
10
16
25
35
50
70
95
R mx /km
Cobre desnudo
Aluminio
1.830
1.150
0.727
0.524
0.387
0.268
0.193
1.910
1.200
0.868
0.641
0.443
0.320
Los valores que figuran en la presente tabla estn de acuerdo a la norma UNE EN 60228. Los dimetros de las cuerdas son aproximados.
80
media tensin
TABLA IV
Capacidad en F/km
Seccin nominal
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
18/30 kV
0.248
0.282
0.327
0.368
0.416
0.475
0.499
0.550
0.590
0.648
0.752
0.816
0.853
0.907
0.199
0.224
0.257
0.288
0.324
0.367
0.414
0.454
0.487
0.533
0.617
0.668
0.735
0.793
0.208
0.234
0.262
0.293
0.332
0.374
0.409
0.438
0.488
0.553
0.599
0.658
0.737
0.275
0.309
0.342
0.385
0.423
0.441
0.482
0.543
0.587
0.646
0.718
0.199
0.229
0.258
0.283
0.315
0.333
0.366
0.435
0.455
0.501
0.556
0.183
0.215
0.249
0.271
0.294
0.324
0.365
0.387
0.417
0.465
0.150
0.176
0.204
0.232
0.250
0.281
0.301
0.340
0.367
0.409
Valores informativos calculados en base a los datos dimensionales de los cables que figuran en este catlogo.
TABLA V
Tensiones de ensayo en fbrica
Tensin nominal
Uo/U (kV)
Ensayo de tensin.
Tensin aplicada en c.a. durante
5 min para U 30 kV
(kV)
Ensayo de descargas
parciales.
Tensin de ensayo
(kV)
1,8/3
3,6/6
6/10
8,7/15
12/20
15/25
18/30
6.5
12.5
21
30.5
42
52.5
63
6.3
10.5
15.2
21
26.2
31.5
81
Nivel de aislamiento
a impulsos, Up
(kV)
60
75
95
125
145
170
media tensin
TABLA VI
Resistencia a la frecuencia de 50 Hz (90 C)
Resistencia mxima en c.a. y a 90 C en /km
Seccin nominal
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cables Unipolares
Cables Tripolares
Cu
Al
Cu
Al
2.310
1.455
0.918
0.663
0.490
0.339
0.245
0.195
0.159
0.127
0.098
0.078
0.062
0.051
2.392
1.513
1.093
0.800
0.558
0.403
0.321
0.262
0.209
0.161
0.128
0.102
0.084
2.346
1.479
0.936
0.675
0.499
0.345
0.249
0.197
0.161
0.129
0.099
-
2.431
1.542
1.112
0.822
0.568
0.410
0.324
0.265
0.212
0.163
-
TABLA VII
Resistencia a la frecuencia de 50 Hz (105 C)
Resistencia mxima en c.a. y a 105 C en /km
Seccin nominal
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cables Unipolares
Cables Tripolares
Cu
Al
Cu
Al
2.446
1.540
0.972
0.702
0.519
0.359
0.259
0.206
0.168
0.134
0.104
0.083
0.066
0.054
2.533
1.602
1.157
0.847
0.591
0.430
0.340
0.277
0.221
0.168
0.136
0.105
0.089
2.484
1.566
0.991
0.715
0.528
0.365
0.264
0.209
0.170
0.137
0.105
-
2.574
1.633
1.176
0.087
0.601
0.434
0.343
0.281
0.224
0.173
-
Nota: La cada de tensin de la lnea para el caso de corriente alterna trifsica, se calcula con la frmula aproximada: U = 3 . L . I . (R . cos + X .
sen ). Donde L, en km, es la longitud de la lnea. I, en A, es la intensidad de corriente a transportar. (Se recomienda ver ejemplo de clculo en la
pgina 34).
82
media tensin
TABLA VIII
Reactancia la frecuencia de 50 Hz
Seccin nominal
mm2
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
18/30 kV
0.140
0.130
0.122
0.118
0.112
0.110
0.106
0.102
0.099
0.096
0.093
0.140
0.130
0.121
0.118
0.115
0.110
0.106
0.103
0.100
0.096
0.148
0.137
0.129
0.123
0.118
0.113
0.109
0.105
0.102
0.099
0.121
0.113
0.106
0.101
0.097
0.095
0.093
0.090
0.124
0.115
0.108
0.103
0.100
0.097
0.093
0.135
0.125
0.115
0.110
0.105
0.101
0.097
10
16
25
35
50
70
95
120
150
185
240
300
400
500
0.135
0.126
0.118
0.113
0.108
0.101
0.099
0.095
0.093
0.089
0.088
0.086
0.085
0.084
0.125
0.118
0.113
0.106
0.102
0.098
0.096
0.093
0.090
0.088
0.086
0.084
0.134
0.128
0.122
0.115
0.110
0.106
0.102
0.100
0.097
0.093
0.091
0.089
0.141
0.135
0.128
0.120
0.115
0.111
0.108
0.104
0.101
0.097
0.095
0.092
Un cable tripolar
10
16
25
35
50
70
95
120
150
185
240
0.115
0.107
0.100
0.095
0.091
0.086
0.083
0.081
0.079
0.079
0.076
0.105
0.100
0.095
0.090
0.087
0.084
0.082
0.081
0.079
0.118
0.112
0.106
0.100
0.096
0.093
0.090
0.089
0.085
0.127
0.120
0.114
0.107
0.102
0.098
0.096
0.094
0.090
Nota: La cada de tensin de la lnea para el caso de corriente alterna trifsica, se calcula con la frmula aproximada: U = 3 . L . I . (R . cos + X .
sen ). Donde L, en km, es la longitud de la lnea. I, en A, es la intensidad de corriente a transportar. (Se recomienda ver ejemplo de clculo en la
pgina 34).
83
media tensin
TABLA IX
Intensidad mxima admisible (A), en servicio permanente, para cables aislados con HEPR (Eprotenax Compact) sin armadura.
Tensin nominal
105 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Cu
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
120
160
195
230
295
355
410
465
535
630
725
840
975
1125
110
145
180
215
265
320
365
415
475
555
635
-
105
135
160
190
235
280
320
360
405
470
530
600
680
765
98
125
150
180
220
260
295
330
375
440
500
565
650
730
102
130
155
185
225
265
305
340
385
445
-
94
120
145
170
210
250
285
315
355
420
-
78
100
120
145
170
205
235
265
295
345
390
-
72
95
110
130
160
190
215
240
275
325
365
-
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
96
125
150
180
225
275
320
360
415
495
565
660
775
905
85
110
135
160
200
240
280
315
360
425
485
-
82
105
125
145
180
215
245
275
315
365
410
470
540
615
25
40
1,5
105
84
76
95
115
135
170
200
230
255
290
345
390
450
515
590
media tensin
TABLA IX bis
Intensidad mxima admisible (A), en servicio permanente, para cables aislados con HEPR (Eprotenax Compact) con armadura.
Tensin nominal
105 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Cu
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
120
155
190
225
280
335
385
435
495
575
650
745
855
975
105
140
170
205
255
305
350
395
450
530
605
-
105
135
160
190
235
275
310
345
385
435
480
530
585
635
98
125
145
175
215
250
285
315
355
400
445
490
545
595
100
130
155
185
225
265
300
335
380
440
495
-
94
120
145
170
210
245
280
310
350
415
465
-
78
100
120
140
170
205
230
260
290
335
385
-
72
90
110
130
160
190
215
240
270
315
360
-
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
90
115
140
170
210
255
295
330
380
445
505
585
675
775
80
110
130
160
195
235
270
305
345
405
470
-
80
100
125
150
180
215
245
270
305
350
390
440
490
545
25
40
1,5
105
85
76
95
115
135
165
195
220
250
280
325
360
405
460
510
media tensin
TABLA X
Dimetros medios aproximados (en mm) de las pantallas constituidas por cintas de cobre.
Seccin nominal
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
3,6/6 kV
11.0
11.9
13.1
14.2
15.5
17.1
18.8
20.3
21.5
23.2
26.3
28.2
30.7
35.0
6/10 kV
12.8
13.9
15.0
16.3
17.9
19.6
21.1
22.3
24.4
27.1
29.0
31.5
34.8
8,7/15 kV
16.1
17.2
18.5
20.1
21.8
23.3
24.5
26.6
29.3
31.2
33.7
37.0
12/20 kV
16.8
18.1
19.7
21.4
22.9
24.1
26.2
28.9
30.8
33.3
37.6
15/25 kV
19.5
21.1
22.8
24.3
25.5
27.6
30.3
32.2
34.7
38
18/30 kV
21.9
23.5
25.9
26.7
27.9
30
32.7
34.6
37.3
41,2
TABLA XI
Intensidad de cortocircuito admisible, en amperios, en pantallas constituidas por cintas de cobre de 0,1 mm de espesor.
Dimetro medio
de pantalla
mm
0,1
0,2
0,3
0,5
1,5
2,5
<13,5
13,5 a 27
>27,0
2030
2540
3555
1550
1935
2710
1330
1665
2330
1110
1390
1945
880
1100
1545
775
970
1355
710
885
1240
660
830
1160
Los datos relacionados en esta tabla se han calculado de acuerdo con la norma IEC 60949. Si el cable considerado es trifsico, con las pantallas
metlicas en contacto, la intensidad de retorno en un cortocircuito monofsico circulara por las pantallas de los tres conductores. Por ello, la pantalla
metlica de cada fase debe ser capaz de soportar un tercio de la intensidad de cortocircuito requerida.
TABLA XII
Intensidad de cortocircuito admisible, en amperios, en pantallas constituidas por una corona de alambres de cobre de dimetro inferior
a 1 mm.
Seccin
de pantalla
mm2
0,1
0,2
0,3
0,5
1,5
2,5
10
16
25
5300
8320
12700
3880
6080
9230
3250
5090
7700
2620
4110
6160
1990
3130
4630
1720
2700
3960
1560
2440
3560
1450
2270
3290
Los datos relacionados en esta tabla han sido calculados de acuerdo con la norma IEC 60949.
86
3
1370
2150
3100
media tensin
GRFICOS DE INTENSIDADES DE CORTOCIRCUITO EN EL CONDUCTOR PARA LOS CABLES TIPO EPROTENAX COMPACT
GRFICO I
Intensidades trmicamente admisibles en cortocircuito para conductores de cobre.
(Segn Normas IEC 60949 y UNE 21192).
kA
SECCIONES en mm2
INTENSIDADES en kiloamperios
TIEMPO en segundos
Temperatura mxima en servicio permanente 105 C.
Temperatura mxima en cortocircuito 250 C.
87
media tensin
GRFICOS DE INTENSIDADES DE CORTOCIRCUITO EN EL CONDUCTOR PARA LOS CABLES TIPO EPROTENAX COMPACT
GRFICO II
Intensidades trmicamente admisibles en cortocircuito para conductores de aluminio.
(Segn Normas IEC 60949 y UNE 21192).
kA
SECCIONES en mm2
INTENSIDADES en kiloamperios
TIEMPO en segundos
Temperatura mxima en servicio permanente 105 C.
Temperatura mxima en cortocircuito 250 C.
88
89
90
media tensin
VOLTALENE
VEMEX
1 x 240/16
Las siglas AL
denotan que el
conductor es de
aluminio, si no se
indica nada, se
entiende que el
conductor es de
cobre.
Es el nombre
comercial del
cable, e indica
que el cable est
aislado con
polietileno
reticulado (XLPE)
Cable apantallado.
La presencia de la
palabra VEMEX
indica que la
cubierta exterior
es de dicho
material.
La cifra 1 3
denota que el
cable es unipolar
o tripolar.
240 indica la
seccin del
conductor en
mm2.
16 indica la
seccin de la
pantalla en mm2.
mm2
12/20
kV
Tensin nominal
12 kV entre
conductor (fase)
y pantalla y 20 kV
entre conductores
(fases).
La tensin ms
elevada entre fases
puede ser superior
(ver tabla de la
pgina 7).
Otros ejemplos:
- Cable VOLTALENE H VEMEX 1 x 240/25 mm2 18/30 kV.
Cable unipolar, con conductor de cobre de 240 mm2 de seccin, aislado con XLPE, apantallado, con alambres de cobre de seccin total 25
mm2, no armado, para una tensin nominal de 18/30 kV y con cubierta exterior VEMEX.
- Cable AL VOLTALENE HMA 1 x 300/16 mm2 6/10 kV.
Cable unipolar, con un conductor de aluminio de 300 mm2 de seccin, aislado con XLPE, apantallado con una corona de hilos de cobre con
una seccin total de 16 mm2, armado con hilos de aluminio, para una tensin nominal de 6/10 kV y con cubierta exterior de PVC (propia
de cables armados).
- Cable AL VOLTALENE HF 3 x 150 mm2 1,8/3 kV.
Cable tripolar, con conductores de aluminio de 150 mm2 de seccin, aislados con XLPE, sin pantalla, armado con flejes de acero, para una
tensin nominal de 1,8/3 kV y con cubierta exterior de PVC (propia de cables armados).
91
media tensin
FORMACIN
PANTALLA
ARMADURA
Unipolar
No
Tripolar
Individual sobre
cada fase
No
CAMPO RADIAL
RHZ1
Flejes aluminio
RFAV
Flejes acero
RFV
Flejes aluminio
RHVFAV
FA
Unipolar
Tripolar
HFA
Unipolar
HF
Tripolar
Flejes acero
RHVFV
MA
Unipolar
Alambres de
aluminio 2
RMAV
No
S
No
M
Tripolar
Alambres de
acero
RMV
HMA
Unipolar
Alambres de
aluminio 2
RHVMAV
HM
Tripolar
Alambres de
acero
RHVMV
P
HP 3
O
RPV
RHVPV
ROZ1
92
media tensin
d
Cuerda
mm
d
Semic. int.
mm
D sobre aislamiento
1,8/3 kV
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
18/30 kV
17
18,3
19,9
21,6
23,1
24,3
26
29,1
31
33,5
37,4
19
20,3
21,9
23,6
25,1
26,3
28
31,1
33
35,5
39,4
22,9
24,5
26,2
27,7
28,9
30,6
33,7
35,6
38,1
42
25,3
26,9
28,6
30,1
31,3
33
36,1
38
40,5
44,4
17
18,1
19,8
21,2
22,7
24
26,1
28,3
31
33,5
37,3
19
20,1
21,8
23,3
24,7
26,1
28,1
30,2
33
35,5
39,3
22,7
24,4
25,8
27,3
28,6
30,7
32,9
35,6
38,1
41,9
25,1
26,8
28,3
29,7
31,2
33,1
34,5
38
40,6
44,3
Conductor de Cu
35
50
70
95
120
150
185
240
300
400
500
7
8,3
9,9
11,6
13,1
14,3
16
18,7
20,6
23,1
26,4
8
9,3
10,9
12,6
14,1
15,3
17
20,1
22
24,5
28,4
11
12,3
13,9
15,6
17,1
18,3
20
22,7
24,6
27,1
30,8
13
14,3
15,9
17,6
19,1
20,3
22
25,3
27,6
30,5
34,8
14,8
16,1
17,7
19,4
20,9
22,1
23,8
26,9
28,8
31,3
35,2
Conductor de Al
35
50
70
95
120
150
185
240
300
400
500
7
8,1
9,8
11,2
12,7
14
16,1
17,9
20,6
23,1
26,3
8
9,1
10,8
12,2
13,7
15
17,1
19,3
22
24,5
28,3
11
12,1
13,8
15,2
16,7
18
20,1
21,9
24,6
27,1
30,7
13
14,1
15,8
17,2
18,7
20
22,1
24,5
27,6
30,5
34,7
14,8
15,9
17,6
19
20,5
21,8
23,9
26,1
28,8
31,3
35,1
Nota: los valores de d, d y D son iguales para cables unipolares y tripolares siempre que se trate del mismo material de conductor (Cu o Al), el
mismo material de aislamiento (XLPE o HEPR) y la misma seccin y tensin. Es decir, por ejemplo un cable de 1x240, 12/20 kV, Al Eprotenax Compact
presenta iguales valores de d, d y D que un cable 3x240, 12/20 kV, Al Eprotenax Compact.
93
media tensin
ext. mm Peso kg/km ext. mm Peso kg/km ext. mm Peso kg/km ext. mm Peso kg/km ext. mm Peso kg/km
Tipo H
(no armado)
Tipo FA
(armado flejes Al)
1 x 10
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
12.8
13.8
14.9
16.0
17.3
18.9
20.6
22.1
23.3
25.4
28.3
30.2
32.9
36.8
275
350
455
565
705
925
1195
1445
1690
2085
2690
3250
4015
5145
17.8
18.8
19.9
21.0
22.3
23.9
25.6
27.1
28.3
30.4
33.3
35.4
38.1
42.0
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
14.0
15.0
16.0
17.1
18.8
20.2
21.7
23.0
25.5
27.6
30.2
33.4
37.2
260
305
355
405
490
580
685
770
955
1140
1380
1695
2075
19.0
20.0
21.0
22.1
23.8
25.2
26.7
28.0
30.5
32.6
35.4
38.6
42.4
Tipo H
(no armado)
24.0
26.4
29.0
31.7
34.7
38.4
42.2
45.7
48.9
53.6
59.8
64.1
1035
1330
1715
2170
2690
3505
4495
5425
6380
7850
10055
12065
26.6
28.7
31.3
33.9
36.9
42.7
46.8
50.2
53.6
58.7
64.7
69.4
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
26.8
29.2
31.7
34.3
38.2
41.4
44.8
48.2
53.8
58.3
64.1
1060
1270
1515
1770
2175
2605
3075
3565
4450
5270
6390
29.2
31.5
33.9
36.4
42.5
45.9
49.3
52.9
58.9
63.2
69.4
Tipo HFA
(armado flejes Al)
Tipo F
(armado flejes acero)
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
Tipo MA
(armado alambres acero)
Tipo M
(armado alambres acero)
94
18.2
19.2
20.3
21.4
22.7
24.3
26.0
27.5
28.9
31.0
33.9
36.0
38.7
42.8
470
555
670
795
950
1190
1480
1745
2020
2440
3080
3685
4485
5682
18.9
19.9
21.0
22.1
23.4
25.0
26.7
28.4
29.6
31.9
35.6
37.7
40.4
45.5
525
615
735
865
1020
1265
1570
1855
2125
2565
3300
3920
4745
6100
19.4
20.4
21.4
22.5
24.2
25.6
27.1
28.6
31.1
33.2
36
39.2
43.2
465
525
585
650
750
860
980
1100
1315
1525
1810
2170
2620
20.1
21.1
22.1
23.2
24.9
26.3
28
29.3
32
34.9
37.7
40.9
45.9
525
585
650
720
830
950
1090
1200
1442
1735
2050
2435
3035 5
Tipo HF
(armado flejes acero)
Tipo HMA
(armado alambres acero)
Tipo HM
(armado alambres acero)
27.6
30.0
34.6
37.3
40.5
44.2
48.4
52.1
55.3
60.2
66.6
71.1
1335
1655
2400
2905
3510
4400
5520
6545
7570
9180
11550
13695
31.5
33.7
36.3
39.0
43.2
46.9
51.1
54.8
58.0
62.9
69.3
75.3
2155
2525
3025
3590
4595
5585
6845
7974
9070
10840
13400
16530
30.4
34.8
37.3
40.1
44.0
47.6
51.2
54.6
60.4
65.1
71.1
1395
1960
2260
2590
3070
3620
4190
4755
5795
6745
8035
34.1
36.5
39.0
42.8
46.7
50.3
53.9
57.3
63.1
67.8
75.3
2285
2585
2945
3640
4265
4915
5595
6270
7455
8535
10875
media tensin
ext.
mm
Peso
kg/km
1 x 10
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
13.8
14.8
15.9
17.0
18.3
19.9
21.6
23.1
24.3
26.4
29.5
32.0
35.1
39.0
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
15.0
16.0
17.0
18.1
19.8
21.2
22.7
24.0
26.5
28.8
32.0
35.6
39.4
26.4
28.7
31.5
33.9
36.9
40.5
44.6
48.4
51.2
55.9
62.6
68.3
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
29.2
31.7
33.9
36.4
40.3
43.7
47.6
50.6
56.1
61.1
68.3
Peso
kg/km
ext.
mm
95
ext.
mm
Peso
kg/km
565
660
780
915
1070
1320
1635
1910
2190
2705
3385
4035
4895
6290
21.1
22.1
23.1
24.2
25.9
27.5
29.0
30.5
33.8
36.1
39.3
42.9
48.1
570
635
700
770
885
1015
1140
1270
1585
1820
2160
2590
3240
2380
2767
3305
3865
4925
5960
7150
8430
9505
11230
13920
17370
36.5
39.0
41.4
45.1
49.2
52.4
56.7
59.9
65.4
70.6
79.3
2535
2890
3220
3965
4635
5215
6035
6655
7885
9050
11715
media tensin
ext.
mm
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
18.7
19.8
20.9
22.2
23.8
25.5
27.0
28.2
30.5
33.4
35.3
38.0
41.5
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
18.9
19.9
20.9
22.0
23.7
25.1
26.6
27.9
30.6
32.7
35.3
38.5
41.9
Peso
kg/km
35.2
37.7
40.3
43.3
47.4
51.2
54.7
57.4
62.2
68.8
73.3
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
35.6
38.0
40.3
42.9
47.1
50.4
53.8
56.8
62.4
66.9
73.3
Peso
kg/km
ext.
mm
96
ext.
mm
Peso
kg/km
940
1065
1200
1360
1625
1930
2225
2590
3040
3715
4335
5165
6525
25.0
26.0
27.0
28.1
30.0
31.4
33.1
35.4
37.9
40.0
42.8
46.0
50.6
855
920
985
1060
1190
1315
1460
1670
1915
2150
2465
2862
3470
3565
4535
5085
5864
7075
8330
9535
10620
12485
16127
18585
42.9
46.7
48.8
51.6
56.2
59.5
63.1
66.1
71.9
77.9
84.5
3310
4095
4440
4895
5710
6380
7130
7802
9105
11100
12930
media tensin
ext.
mm
Peso
kg/km
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
22.0
23.1
24.4
26.0
27.7
29.4
30.6
32.9
35.6
37.7
40.4
43.9
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
22.1
23.1
24.2
25.9
27.3
29.0
30.3
33.0
34.9
37.7
40.9
44.3
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
1175
1325
1495
1750
2155
2460
2740
3210
3895
4510
5535
6750
28.2
29.4
30.5
32.2
34.6
36.3
37.6
40.3
42.4
45
49.6
53
1030
1110
1190
1310
1535
1685
1810
2085
2330
2640
3235
3685
42.9
45.3
48.7
52.5
56.4
59.8
62.6
67.3
73.9
78.2
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
43.1
45.3
48.2
52.3
55.5
58.9
61.9
67.9
72.4
78.2
2915
48.9
3930
3400
51.5
4495
4070
55.1
5260
5025
58.7
6265
6135
63.0
7520
7170
66.6
8660
8150
69.4
9705
9760
74.3
11455
12240
81.1
14120
14375
87.3
17255
Tripolares - 8,7/15 kV (Conductores de aluminio)
2480
49.1
3500
2750
51.5
3845
3140
54.6
4325
3695
58.5
4935
4220
62.1
5590
4800
65.7
6270
5325
68.7
6865
6460
74.9
8170
7420
79.6
9265
8720
87.3
11595
97
51.6
54.2
57.8
61.4
65.7
69.3
73.4
78.3
85.1
89.8
5245
5890
6765
7870
9265
10510
12405
14400
17340
19850
51.8
54.2
57.3
61.2
64.8
68.4
72.7
78.9
83.6
89.8
4850
5240
5830
6540
7305
8095
9580
11105
12385
14190
media tensin
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
1440
1620
1965
2305
2595
2900
3355
4045
4845
5705
6970
31.4
32.7
35.2
36.8
38.3
39.8
42.3
44.4
48.4
51.6
55.2
1225
1320
1530
1680
1820
1970
2230
2480
2975
3410
3905
50.4
53.4
57.0
60.9
64.3
67.1
72.2
78.4
82.9
3980
4625
5580
6730
7795
8805
10545
12995
15225
56.8
60.0
63.6
67.7
71.3
74.1
79.6
87.5
92.0
3 x 35
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
50.4
52.9
56.8
60.0
63.4
66.4
72.4
76.9
82.9
98
5205
5945
6985
8250
9425
10495
12430
15880
18251
59.5
62.7
66.3
70.4
75.5
78.3
83.6
90.0
94.5
6760
7610
8754
10120
12260
13415
15550
18470
20985
59.5
62.2
66.1
69.5
74.6
77.6
83.8
88.5
94.5
6115
6635
7425
8150
9815
10580
12170
13565
15325
media tensin
ext.
mm
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
29.2
30.8
32.7
34.2
35.6
37.7
40.6
42.7
45.4
48.9
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
29.0
30.7
32.3
33.8
35.3
37.8
39.9
42.7
45.9
49.3
Peso
kg/km
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
36.5
38.1
40.0
41.5
42.9
45.0
49.3
51.2
54.1
57.6
1880
2150
2500
2800
3105
3575
4460
5105
6000
7245
36.3
38.0
39.6
41.1
42.6
45.1
48.6
51.2
54.6
58.0
1570
1715
1875
2025
2175
2450
2885
3235
3695
4185
59.4
63.0
66.9
70.7
73.5
78.2
84.4
88.9
3 x 50
3 x 70
3 x 95
3 x 120
3 x 150
3 x 185
3 x 240
3 x 300
58.9
62.8
66.0
69.8
72.9
78.4
82.9
88.9
5390
66.2
6875
6400
69.8
7965
7595
73.9
9280
8785
77.9
10600
9835
82.4
12510
11550
87.3
14430
14085
93.7
17210
16370
98.2
19640
Tripolares - 15/25 kV (Conductores de aluminio)
4455
65.7
5925
5065
69.6
6625
5665
73.0
7330
6400
77.0
8190
6995
81.8
9645
8175
87.5
11060
9235
92.2
12305
10715
98.2
13985
99
68.9
73.8
78.1
82.1
84.9
89.8
96.2
100.7
8730
10720
12205
13714
14910
17025
19965
22535
68.4
73.6
77.2
81.5
84.3
90
94.7
100.7
7745
9325
10205
11260
12065
13650
15040
16880
media tensin
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
ext.
mm
Peso
kg/km
31.6
33.4
35.3
36.8
38.0
40.3
43.2
45.3
48.0
51.3
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
31.4
33.3
36
37.2
39
41.5
43
45.3
48.3
51.7
1405
37.4
1810
1675
39.0
2080
1995
40.9
2420
2275
42.6
2735
2545
44.0
3035
3000
46.3
3520
3670
49.0
4190
4295
51.3
4865
5125
54.0
5720
6280
57.7
6970
Unipolares - 18/30 kV (Conductores de aluminio)
1050
1160
1270
1425
1500
1790
1910
2350
2510
3000
37.2
38.9
40.5
42.2
43.7
46.4
48.3
51.3
54.5
58.1
1510
1645
1795
1960
2110
2400
2625
2995
3420
3910
39.1
40.7
42.6
44.1
46.7
49.0
51.7
54.0
56.7
60.4
2055
2340
2690
2995
3460
3975
4675
5375
6260
7545
28.9
40.6
42.2
43.7
46.4
49.1
51.0
54.0
57.2
60.8
1755
1895
2065
2225
2540
2855
3095
3505
3955
4485
64.9
69.0
72.9
76.3
79.1
83.8
90.0
94.3
6175
7305
8550
9705
10785
12560
15165
17450
71.9
76.0
80.1
85.4
88.2
93.1
99.5
104.0
7815
9040
10405
12515
13680
15660
18520
21000
75.9
80.0
84.3
87.9
90.7
95.6
102.0
106.5
10606
12020
13620
15035
16260
18435
21515
24140
64.5
68.8
72.0
75.4
78.4
84.0
88.5
94.3
75.5
79.8
83.4
87.0
90.0
95.8
100.5
106.5
9660
10685
11615
12565
13410
15060
16505
18480
Nota:
En los cables de tensiones nominales 1,8/3 y 3,6/6 kV la pantalla metlica est formada por cintas de cobre, solapadas, arrolladas en hlice.
En los cables de tensiones nominales comprendidas entre 6/10 y 18/30 kV la pantalla metlica est constituida por una corona de hilos de cobre.
En los cables tripolares, la pantalla metlica est formada por cintas de cobre, solapadas, arrolladas en hlice sobre la capa semiconductora externa
de cada fase.
100
media tensin
Unidad
XLPE
Mecnicas
Valores en estado inicial:
- Carga rotura mnima
- Alargamiento mnimo
N/cm2
%
1250
200
C
h
135
168
%
%
25
25
C
h
mg/cm2
85
336
1
b) Ensayo de contraccin:
Temperatura
Duracin
- Contraccin mxima admitida
C
h
%
130
1
4
c) Ensayo de resistencia:
-Concentracin de ozono, en volumen
-Duracin del ensayo sin aparicin de grietas
%
h
Fsicas
a) Absorcin de agua:
- Mtodo ponderal:
Temperatura
Duracin
- Variacin de masa admitida
Qumicas
Comprobacin de la reticulacin:
- Tratamiento:
Temperatura
Tiempo bajo carga
Esfuerzo mecnico
- Alargamiento mximo bajo carga
- Alargamiento permanente mximo despus del enfriamiento
C
mn.
N/cm2
%
%
Los ensayos para la comprobacin de estas caractersticas se realizan segn la norma UNE EN 60811.
101
200
15
20
175
15
media tensin
TABLA II
Caractersticas de las cubiertas PVC y de poliolefinas (VEMEX DMZ1) de los cables VOLTALENE.
Caractersticas
Unidades
Cubierta PVC
Cubierta VEMEX
(DMZ1) (habitual)
Mecnicas
a) Sin envejecimiento
- Resistencia mnima a la traccin
- Alargamiento mnimo a la rotura
N/mm2
%
12.50
150
15
500
b) Despus de envejecimiento
Tratamiento:
Temperatura
Duracin
- Resistencia mnima a la traccin
- Variacin
- Alargamiento mnimo a la rotura
- Variacin
C
h
N/mm2
%
%
%
100
168
25
25
110 2
336
300
-
C
h
N/mm2
%
%
%
100 2
168
25
25
100 2
168
300
-
C
h
mg/cm2
100
168
1.5
100 2
168
0.5
C
h
%
90
6
0.7
50
115 2
6
0.7
50
C
%
-15
20
-30 2
20
C
N/mm2
20 5
10
20 5
24
Fsico-Qumicas
a) Prdida de masa
Tratamiento:
Temperatura
Duracin
- Prdida mxima:
C
h
%
102
80 2
5x5
7
media tensin
TABLA II (CONTINUACIN)
Caractersticas de las cubiertas PVC y de poliolefinas (VEMEX DMZ1) de los cables VOLTALENE.
Caractersticas
Unidades
Cubierta PVC
Cubierta VEMEX
(DMZ1) (habitual)
Fsico-Qumicas
f) Resistencia a la abrasin
Tratamiento:
Temperatura
Masa aplicada
Velocidad
- Mnimo nmero de desplazamientos
C
Kg
m/s
-
C
h
mg/cm2
85 2
336
5
85 2
336
0.5
>1
<0.5 (*)
pH
S/mm
3
100
4,3
10
%
%
25
25
15
15
20 5
36
0.3 15%
8
Las caractersticas de la cubierta normal corresponden al tipo de mezcla ST2 especificado en la Norma IEC 60502.
Las caracterticas de la cubierta VEMEX corresponden al tipo de mezcla de poliolefina especificado en UNE HD 620. Los ensayos para la comprobacin
de estas caractersticas se realizan segn la Norma UNE 60811.
(*) El compuesto utilizado para la cubierta Z1 (VEMEX), no contiene hidrocarburos voltiles ni halgenos, ni metales pesados (excepto una mnima
cantidad de Pb en caso de cubiertas con coloracin roja).
103
media tensin
TABLA III
Resistencia elctrica mxima en corriente continua a 20C en /km
Seccin nominal
mm2
10
16
25
35
50
70
95
R mx /km
Cobre desnudo
Aluminio
1.830
1.150
0.727
0.524
0.387
0.268
0.193
Seccin nominal
mm2
1.910
1.200
0.868
0.641
0.443
0.320
R mx /km
Cobre desnudo
Aluminio
120
150
185
240
300
400
500
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.253
0.206
0.164
0.125
0.100
0.078
0.0605
Los valores que figuran en la presente tabla estn de acuerdo con la Norma UNE EN 60228. Los dimetros de las cuerdas son aproximados.
TABLA IV
Capacidad en F/km
Cables unipolares y tripolares apantallados
Seccin nominal
mm2
1,8/3 kV
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
10
16
25
35
50
70
95
120
150
185
240
300
400
500
0.229
0.265
0.304
0.343
0.388
0.444
0.504
0.556
0.598
0.671
0.765
0.831
0.918
0.939
0.195
0.223
0.255
0.286
0.323
0.368
0.416
0.458
0.491
0.550
0.604
0.612
0.634
0.670
0.179
0.202
0.226
0.253
0.286
0.322
0.353
0.378
0.421
0.477
0.516
0.567
0.635
0.166
0.184
0.205
0.231
0.258
0.281
0.300
0.333
0.375
0.405
0.444
0.495
0.161
0.178
0.199
0.217
0.241
0.254
0.283
0.306
0.343
0.389
0.417
0.154
0.171
0.190
0.206
0.218
0.240
0.269
0.289
0.315
0.349
Valores informativos calculados en base a los datos dimensionales de los cables que figuran en este catlogo.
104
18/30 kV
0.139
0.154
0.167
0.183
0.192
0.213
0.229
0.254
0.277
0.306
media tensin
TABLA V
Tensiones de ensayo en fbrica
Tensin nominal
Uo/U
(kV)
Ensayo de tensin.
Tensin aplicada en c.a. durante
5 min para Uo 30 kV
(kV)
Ensayo de descargas
parciales.
Tensin de ensayo
(kV)
1,8/3
3,6/6
6/10
8,7/15
12/20
15/25
18/30
6.5
12.5
21
30.5
42
52.5
63
6.3
10.5
15.2
21
26.2
31.5
Nivel de aislamiento
a impulsos, Up
(kV)
60
75
95
125
145
170
TABLA VI
Resistencia a la frecuencia de 50 Hz
Resistencia mxima en c.a. y a 90C en /km
Seccin nominal
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
Cables Unipolares
Cables Tripolares
Cu
Al
Cu
2.310
1.455
0.918
0.663
0.490
0.339
0.245
0.195
0.159
0.127
0.098
0.078
0.062
0.051
2.392
1.513
1093
0.800
0.558
0.430
0.321
0.277
0.209
0.168
0.128
0.105
0.084
2.346
1.479
0.936
0.675
0.499
0.345
0.249
0.197
0.161
0.129
0.099
-
Al
2.431
1.542
1.112
0.0822
0.568
0.410
0.324
0.265
0.212
0.163
-
Nota: La cada de tensin de la lnea para el caso de corriente alterna trifsica, se calcula con la frmula aproximada: U = 3 . L . I . (R . cos + X .
sen ). Donde L, en km, es la longitud de la lnea. I, en A, es la intensidad de corriente a transportar. (Se recomienda ver ejemplo de clculo en la
pgina 34).
105
media tensin
TABLA VII
Reactancia la frecuencia de 50 Hz
Seccin nominal
mm2
3,6/6 kV
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
18/30 kV
10
16
25
35
50
70
95
120
150
185
240
300
400
500
0.136
0.126
0.117
0.111
0.106
0.100
0.095
0.092
0.090
0.088
0.085
0.083
0.081
0.080
0.141
0.130
0.121
0.115
0.109
0.103
0.098
0.095
0.092
0.091
0.088
0.087
0.085
0.084
0.143
0.134
0.128
0.122
0.115
0.110
0.106
0.102
0.100
0.097
0.093
0.091
0.089
10
16
25
35
50
70
95
120
150
185
240
0.115
0.107
0.100
0.095
0.091
0.086
0.083
0.081
0.079
0.079
0.076
0.122
0.113
0.105
0.100
0.095
0.090
0.087
0.084
0.082
0.081
0.079
0.127
0.118
0.112
0.106
0.100
0.096
0.093
0.090
0.089
0.085
0.141
0.135
0.128
0.120
0.115
0.111
0.108
0.104
0.101
0.097
0.095
0.092
0.146
0.138
0.130
0.125
0.120
0.117
0.112
0.119
0.104
0.101
0.098
0.144
0.136
0.129
0.123
0.120
0.118
0.116
0.108
0.104
0.100
0.149
0.141
0.132
0.127
0.123
0.120
0.114
0.111
0.106
0.102
0.126
0.120
0.113
0.107
0.103
0.101
0.098
0.094
0.127
0.119
0.114
0.109
0.106
0.103
0.099
0.133
0.125
0.119
0.114
0.111
0.108
0.103
Un cable tripolar
0.127
0.120
0.114
0.107
0.102
0.098
0.096
0.094
0.090
Nota: La cada de tensin de la lnea para el caso de corriente alterna trifsica, se calcula con la frmula aproximada: U = 3 . L . I . (R . cos + X .
sen ). Donde L, en km, es la longitud de la lnea. I, en A, es la intensidad de corriente a transportar. (Se recomienda ver ejemplo de clculo en la
pgina 34).
106
media tensin
TABLA IX
Intensidad mxima admisible (A), en servicio permanente, para cables aislados con XLPE (Voltalene) sin armadura.
Tensin nominal
90 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Cu
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
115
155
185
220
275
335
385
435
500
590
680
790
930
1095
105
140
170
205
255
305
345
395
445
525
600
-
100
130
155
180
225
265
300
340
380
440
490
560
635
715
91
120
145
170
205
245
280
315
355
415
460
520
605
675
98
125
150
175
220
260
290
325
370
425
475
-
90
115
140
160
200
235
265
300
335
395
445
-
76
95
115
135
165
200
225
255
285
330
375
-
70
90
105
125
155
180
205
230
260
305
345
-
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
92
120
145
170
210
255
295
335
385
455
520
610
715
830
80
110
130
155
195
235
270
305
345
405
465
-
78
100
120
140
170
205
235
260
295
345
390
445
505
575
25
40
1,5
90
107
74
94
110
130
160
190
215
245
280
320
365
415
480
545
media tensin
TABLA IX bis
Intensidad mxima admisible (A), en servicio permanente, para cables aislados con XLPE (Voltalene) con armadura.
Tensin nominal
90 C
1,8/3 kV a 18/30 kV
Seccin nominal
mm2
(1)
(3)
(2)
(4)
(5)
(6)
Conductores de Cu
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
115
150
180
210
265
315
360
405
460
530
600
680
775
885
105
140
165
200
250
300
340
385
440
510
580
-
100
130
155
180
225
260
295
325
360
410
450
495
540
585
94
120
140
165
200
235
265
295
330
375
410
450
505
545
100
125
150
180
220
260
295
330
370
425
480
-
92
115
140
165
200
235
270
300
340
395
445
-
76
95
115
140
170
200
225
250
285
325
375
-
70
90
105
125
150
180
205
230
255
295
345
-
Conductores de Al
16
25
35
50
70
95
120
150
185
240
300
400
500
630
88
110
135
160
200
240
275
310
355
415
470
540
620
710
80
105
130
155
190
225
260
295
335
390
455
-
80
100
120
140
175
205
230
255
290
330
365
410
455
505
25
40
1,5
90
108
72
92
110
130
155
185
210
235
265
300
335
375
425
470
media tensin
TABLA X
Dimetros medios aproximados (en mm) de las pantallas constituidas por cintas de cobre.
Seccin nominal
mm2
10
16
25
35
50
70
95
120
150
185
240
300
400
500
3,6/6 kV
10.0
11.0
12.1
13.2
14.5
16.1
17.8
19.3
20.5
22.6
25.5
27.8
30.7
34.9
6/10 kV
12.8
13.9
15.0
16.3
17.9
19.6
21.1
22.3
24.4
27.1
29.0
31.5
35.3
8,7/15 kV
16.1
17.2
18.5
20.1
21.8
23.3
24.5
26.6
29.3
31.2
33.7
37.5
12/20 kV
19.2
20.5
22.1
23.8
25.3
26.5
28.6
31.3
33.2
35.7
39.6
15/25 kV
23.1
24.7
26.4
27.9
29.1
31.2
33.9
35.8
38.3
42.1
18/30 kV
25.5
27.1
28.8
30.3
31.5
33.6
35.1
38.2
40.8
44.5
TABLA XI
Intensidad de cortocircuito admisible, en amperios, en pantallas constituidas por cintas de cobre de 0,1 mm de espesor.
Dimetro medio
de pantalla
mm
0,1
0,2
0,3
0,5
1,5
2,5
<13,5
13,5 a 27
>27
2350
2930
4110
1790
2240
3130
1540
1920
2690
1280
1600
2250
1020
1270
1780
890
1120
1570
820
1020
1430
760
960
1340
Los datos relacionados en esta tabla se han calculado de acuerdo con la Norma IEC 949. Si el cable considerado es trifsico, con las pantallas
metlicas en contacto, la intensidad de retorno en un cortocircuito monofsico circulara por las pantallas de los tres conductores. Por ello, la pantalla
metlica de cada fase debe ser capaz de soportar un tercio de la intensidad de cortocircuito requerida.
TABLA XII
Intensidad de cortocircuito admisible, en amperios, en pantallas constituidas por una corona de alambres de cobre de dimetro inferior
a 1 mm.
Seccin
de pantalla
mm2
10
16
25
0,2
3880
6080
9230
0,3
3250
5090
7700
0,5
2620
4110
6160
1
1990
3130
4630
Los datos relacionados en esta tabla han sido calculados de acuerdo con la Norma IEC 60949.
109
1,5
1720
2700
3960
2
1560
2440
3560
2,5
1450
2270
3290
3
1370
2150
3100
media tensin
SECCIONES en mm2
INTENSIDADES en kiloamperios
TIEMPO en segundos
Temperatura mxima en servicio permanente 90 C.
Temperatura mxima en cortocircuito 250 C.
110
media tensin
SECCIONES en mm2
INTENSIDADES en kiloamperios
TIEMPO en segundos
Temperatura mxima en servicio permanente 90 C.
Temperatura mxima en cortocircuito 250 C.
111
112
113
TMF-E
(Pg. 120)
PCT Exterior
(Pg. 124)
TMF-I
(Pg. 118)
PCT Interior
(Pg. 122)
MSCE-250A
(Pg. 136)
MSCS-400A
(Pg. 139)
MSCS-250A
(Pg. 133)
MSCE-400A
(Pg. 142)
MSCT-630A
(Pg. 145)
MSCEA-630A
(Pg. 148)
ELASPEED
(Pg. 126)
ECOSPEED
(Pg. 129)
TPE-250
(Pg. 155)
Abrazaderas plsticas
(Pg. 169)
Fichas de sujecin
(Pg. 172)
10
TMF-E
(Pg. 120)
PCT Exterior
(Pg. 124)
TMF-I
(Pg. 118)
PCT Interior
(Pg. 122)
MSCE-250A
(Pg. 136)
MSCS-250A
(Pg. 133)
MSCT-630A
(Pg. 145)
ELASPEED
(Pg. 126)
Abrazaderas plsticas
(Pg. 169)
Fichas de sujecin
(Pg. 172)
10
TMF-R
(Pg. 116)
18/30 kV
TMF-R
(Pg. 116)
ECOSPEED
(Pg. 129)
114
1 x 150 mm2
1 x 240 mm2
AL HEPRZ1
1 x 400 mm2
1 x 240 mm2
EXTERIOR
COTRCTIL FRO
ELASPEED 1E 00/24
1 x 150 mm2
EXTERIOR
ENFILABLE
1 x 300 mm2
1 x 95 mm2
INTERIOR
ENFILABLE
TMF-2 00/24 I
AL RHZ1
1 x 400 mm2
630 A,
EN T ROSCADA
MSCE-250A-95/24-T3
MSCEA-630A-95-240/24-T3 MSCT-630A-95-240/24-T3
PCT-25 J2 00/24
HEPR
MSCEA-630A-300-400/24- MSCT-630A-300-400/24-T3
T3
PCT-25 J4 00/24
HEPR
MSCE-250A-95/24-T3
TMF-2 00/24 E
MSCEA-630A-95-240/24-T3 MSCT-630A-95-240/24-T3
PCT-25 J2 00/24
1 x 300 mm2
630 A, EN T
ASIMTRICA ROSCADA
250 A
TMF-3 00/24 E
TMF-3 00/24 I
TMF-3 00/24 E
MSCEA-630A-300-400/24- MSCT-630A-300-400/24-T3
T3
PCT-25 J4 00/24
1 x 150 mm2
1 x 240 mm2
AL HEPRZ1
1 x 300 mm2
EXTERIOR
COTRCTIL FRO
400 A, ACODADA
AL RHZ1
PCT-35 J2 00/36
MSCE-400A-95-240/24-T3
PCT-35 J4 00/36
MSCE-400A-300-400/24-T3
ELASPEED 1I 00/36
TMF-2 00/36 I
TMF-2 00/36 E
TMF-3 00/36 I
TMF-3 00/36 E
MSCT-630A-300-400/24-T3
-
TMF-4 00/36 I
TMF-4 00/36 I
PCT-35 J2 00/36
MSCE-400A-95-240/24-T3
TMF-4 00/36 E
PCT-35 J4 00/36
MSCE-400A-300-400/24-T3
TMF-4 00/36 E
PCT-35 J4 00/36
8
2
Celda compacta
Transformador
8
3
4
3
5
10
115
MSCT-630A-95-240/24-T3
MSCT-630A-300-400/24-T3
Transformador
Celda convencional
10
MSCT-630A-95-240/24-T3
630 A,
EN T ROSCADA
ELASPEED 1H 00/36
1 x 150 mm2
1 x 400 mm2
EXTERIOR
ENFILABLE
HEPR
1 x 95 mm2
1 x 300 mm2
INTERIOR
ENFILABLE
PCT-35 J4 00/36
ELASPEED 1 I 00/36 HEPR TMF-4 00/36 I HEPR TMF-4 00/36 E HEPR
1 x 400 mm2
1 x 240 mm2
media tensin
accesorios
COMPONENTES
1
2
3
1 - CONTACTO METLICO:
Contacto metlico de Cu, Al-Cu o Al estaado.
2 - CAPUCHN DE PROTECCIN:
Moldeado en elastmero antitracking.
Impide la penetracin de agua.
Se posiciona sobre el final del cuerpo externo (4) y el contacto (1).
3 - REPARTIDOR LINEAL DE TENSIN:
Incorporado en el mismo cuerpo externo (4).
Controla y distribuye el campo elctrico en el corte de pantalla del cable.
4 - CUERPO PREMOLDEADO EXTERNO:
Moldeado en elastmero anti-tracking.
Diseado para estancar totalmente el cable y la toma de tierra.
5 - TOMA DE TIERRA:
Utilizando los propios hilos de la pantalla del cable.
CARACTERSTICAS
- PARA CABLES DE AISLAMIENTO SECO Y PAPEL IMPREGNADO.
- FACILIDAD DE MONTAJE: La concepcin misma de una terminacin Monobloc, lubricada internamente en el proceso de fabricacin, permite un
montaje fcil. La terminacin se desliza a mano, sin ninguna herramienta especial como ayuda; a continuacin se conecta el terminal metlico
de conexin y se desliza un capuchn de elastmero para asegurar el sellado perfecto de la terminacin.
La unidad Monobloc admite todo tipo de contactos metlicos.
APLICACIN (Orientativa)
Para dimetros sobre aislamiento del cable (*Tensin servicio 15/25kV). Vlido para cables RHZ1 y HEPRZ1.
Seccin conductor mm2
6/10 kV
8,7/15 kV
12/20 kV
15/25 kV
*18/30 kV
35
50
70
95
120
150
185
240
TMF2-R
TMF2-R
TMF2-R
TMF2-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF2-R
TMF2-R
TMF2-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF2-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
TMF3-R
116
media tensin
accesorios
Mn.
Mx.
L
(mm)
TMF2-R
TMF3-R
15.5
19.9
26
32
340
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene
respectivamente.
117
media tensin
accesorios
COMPONENTES
1
2
1 - CONTACTO METLICO:
Contacto metlico de Cu o Al-Cu.
2 - ALETAS AISLANTES:
Aletas modulares deslizantes fabricadas en elastmero anti-tracking.
3 - REPARTIDOR LINEAL DE TENSIN:
Moldeado elastico, distribuye las lineas de campo elctrico.
4 - PROTECTOR TOMA TIERRA:
Protector de goma elastomrica que impide la penetracin de agua
y protege la toma de tierra.
5 - TOMA DE TIERRA:
Utilizando los propios hilos de la pantalla del cable.
4
5
CARACTERSTICAS
- PARA CABLES DE AISLAMIENTO SECO Y PAPEL IMPREGNADO.
- Posiciones: vertical, angular o invertida.
- No precisa herramientas especiales, calentamiento ni rellenos.
- Se puede poner en servicio inmediatamente.
- Piezas modulares introducidas sobre el cable con la ayuda de un lubricante especial.
CARACTERSTICAS DIMENSIONALES
Tensin kV
L (mm) aprox.
N de aletas
6/10
8,7/15
12/20
18/30
435
435
435
450
2
2
2
4
118
media tensin
accesorios
RHZ1
3,6/6 kV
RHZ1
6/10 kV
RHZ1
8,7/15 kV
RHZ1
12/20 kV
HEPRZ1
12/20 kV
RHZ1
15/25 kV
RHZ1
18/30 kV
HEPRZ1
18/30 kV
TMF0-I
TMF0-I
TMF0-I
TMF0-I
TMF0-I
TMF1-I
TMF1-I
TMF1-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF0-I
TMF0-I
TMF1-I
TMF1-I
TMF1-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF1-I
TMF1-I
TMF1-I
TMF1-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF4-I
TMF1-I
TMF1-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF4-I
TMF5-I
TMF1-I
TMF1-I
TMF1-I
TMF1-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF4-I
TMF5-I
TMF1-I
TMF1-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF4-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF4-I
TMF4-I
TMF4-I
TMF5-I
TMF2-I
TMF2-I
TMF2-I
TMF3-I
TMF3-I
TMF3-I
TMF3-I
TMF3-I
TMF4-I
TMF4-I
TMF4-I
TMF4-I
TMF5-I
CRITERIOS DE DISEO
Modelo de utilizacin recomendado
Dimetro sobre aislamiento cable (mm)
Modelo TMF
TMF0-I
TMF1-I
TMF2-I
TMF3-I
TMF4-I
TMF5-I
Mn.
Mx.
Modelo
ELTI
13
15,5
20
26
36
49,5
22
26
33
43
61
80
A
B
C
D
E
F
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene
respectivamente.
IMPORTANTE: Estos terminales son aptos para ser utilizados en cables aislados en papel impregnado, utilizando el kit de adaptacin CPI-400.
EJEMPLOS DE PEDIDO: Cable con aislamiento de papel 1x150, Al,18/30 kV, para interior, le corresponde el tipo TMF-3 - 150/36 l Al CPl.
119
media tensin
accesorios
COMPONENTES
1
1 - CONTACTO METLICO:
Contacto metlico de Cu o Al-Cu.
2 - ALETAS AISLANTES:
Aletas modulares deslizantes fabricadas en elastmero anti-tracking.
3 - REPARTIDOR LINEAL DE TENSIN:
Moldeado elastico, distribuye las lineas de campo elctrico.
4 - PROTECTOR TOMA TIERRA:
Protector de goma elastomrica que impide la penetracin de agua y protege
la toma de tierra.
5 - TOMA DE TIERRA:
Utilizando los propios hilos de la pantalla del cable.
4
5
CARACTERSTICAS
- PARA CABLES DE AISLAMIENTO SECO Y PAPEL IMPREGNADO.
- Posiciones: vertical, angular o invertida.
- No precisan herramientas especiales, calentamiento ni rellenos.
- Se pueden poner en servicio inmediatamente.
- Piezas modulares introducidas sobre el cable con la ayuda de un lubricante especial.
CARACTERSTICAS DIMENSIONALES
Tensin kV
L (mm) aprox.
N de aletas
6/10
8,7/15
12/20
18/30
450
450
450
500
4
4
4
5
120
media tensin
accesorios
RHZ1
3,6/6 kV
RHZ1
6/10 kV
RHZ1
8,7/15 kV
TMF0-E
TMF0-E
TMF0-E
TMF0-E
TMF0-E
TMF1-E
TMF1-E
TMF1-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF0-E
TMF0-E
TMF1-E
TMF1-E
TMF1-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF1-E
TMF1-E
TMF1-E
TMF1-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF4-E
RHZ1
12/20 kV
TMF1-E
TMF1-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF4-E
TMF5-E
HEPRZ1
12/20 kV
RHZ1
15/25 kV
TMF1-E
TMF1-E
TMF1-E
TMF1-E
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF4-E
TMF5-E
TMF1-E
TMF1-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF4-E
RHZ1
18/30 kV
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF4-E
TMF4-E
TMF4-E
TMF5-E
HEPRZ1
18/30 kV
TMF2-E
TMF2-E
TMF2-E
TMF3-E
TMF3-E
TMF3-E
TMF3-E
TMF3-E
TMF4-E
TMF4-E
TMF4-E
TMF4-E
TMF5-E
IMPORTANTE: Estos Terminales son aptos para ser utilizados en cables aislados en papel impregnado, utilizando el kit de adaptacin CPI-400.
EJEMPLO DE PEDIDO:Cable aislamiento seco 1x150 Al, 12/20 kV, para exterior, le corresponde el tipo TMF-2 - 150/24 E Al.
CRITERIOS DE DISEO
Modelo de utilizacin recomendado
Dimetro sobre aislamiento cable (mm)
Modelo TMF
Mn.
Mx.
Modelo
ELTO
TMF0-E
TMF1-E
TMF2-E
TMF3-E
TMF4-E
TMF5-E
13
15,5
20
26
36
49,5
22
26
33
43
61
80
A
B
C
D
E
F
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene
respectivamente.
121
media tensin
accesorios
COMPONENTES
1
1- CONTACTO METLICO:
Contacto metlico de Cu o Al-Sn, compresin o tornillera fusible.
2- CUERPO AISLANTE:
Fabricado con una formulacin de goma de silicona de gran memoria elstica que ofrece
una alta estanqueidad y ptimas caractersticas elctricas.
3- REPARTIDOR LINEAL DE TENSIN INTEGRADO:
Tubo flexible de alta permitividad integrado en el cuerpo aislante del terminal que efecta
el control del campo elctrico en la zona prxima al corte de la semiconductora externa
del cable. Mientras se va extrayendo el soporte, el conjunto RLT+cuerpo aislante se
contrae uniformemente sobre el cable y en la posicin correcta. No son necesarias
operaciones adicionales durante la instalacin.
4- TOMA DE TIERRA:
Utilizando los propios hilos de la pantalla del cable.
CARACTERSTICAS
- Cubre una amplia gama de aplicaciones con un reducido nmero de modelos.
- Adaptable a cables de papel impregnado y a cables unipolares de aislamiento seco (PE, XLPE, EPR),
con conductor de Cu o Al de hasta 18/30 kV.
- Mxima facilidad de instalacin.
- No necesita herramientas especiales, aportacin de calor, encintados o rellenos.
- Instalacin vertical o inclinada.
- Se puede energizar inmediatamente despus de su conexin a la lnea.
L
(mm)
381
578
762
295
368
427
122
media tensin
accesorios
18/30 kV
Seccin
mm2
6/10 kV
RHZ1
8,7/15 kV
RHZ1
RHZ1
HEPRZ1
RHZ1
HEPRZ1
50
70
95
120
150
185
240
300
400
500
630
800
1000
PCT 15-J1
PCT 15-J1
PCT 15-J1
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J1
PCT 15-J1
PCT 15-J1
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J1
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J1
PCT 15-J1
PCT 15-J1
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT15-J1
PCT15-J2
PCT15-J4
Mximo
16,3
21,3
33
28,5
35,1
53,3
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene
respectivamente.
123
media tensin
accesorios
COMPONENTES
1
1- CONTACTO METLICO:
Contacto metlico de Cu o Al-Sn, compresin o tornillera fusible.
2- CUERPO AISLANTE:
Fabricado con una formulacin de goma de silicona de gran memoria elstica que ofrece
una alta estanqueidad y ptimas caractersticas elctricas.
3- REPARTIDOR LINEAL DE TENSIN INTEGRADO:
Tubo flexible de alta permitividad integrado en el cuerpo aislante del terminal que efecta
el control del campo elctrico en la zona prxima al corte de la semiconductora externa
del cable. Mientras se va extrayendo el soporte, el conjunto RLT+cuerpo aislante se
contrae uniformemente sobre l y en la posicin correcta. No son necesarias operaciones
adicionales durante la instalacin.
4- TOMA DE TIERRA:
Utilizando los propios hilos de la pantalla del cable.
CARACTERSTICAS
- Cubre una amplia gama de aplicaciones con un reducido nmero de modelos.
- Adaptable a cables de papel impregnado y a cables unipolares de aislamiento seco (PE, XLPE, EPR),
con conductor de Cu o Al de hasta 18/30 kV.
- Mxima facilidad de instalacin.
- No necesita herramientas especiales, aportacin de calor, encintados o rellenos.
- Instalacin vertical o inclinada.
- Se puede energizar inmediatamente despus de su conexin a la lnea.
124
Longitud L (mm)
295
368
427
media tensin
accesorios
18/30 kV
Seccin
mm2
6/10 kV
RHZ1
8,7/15 kV
RHZ1
RHZ1
HEPRZ1
RHZ1
HEPRZ1
50
70
95
120
150
185
240
300
400
500
630
800
1000
PCT 15-J1
PCT 15-J1
PCT 15-J1
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J1
PCT 15-J1
PCT 15-J1
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J2
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 15-J4
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J4
PCT 25-J4
PCT 25-J4
PCT 25-J4
PCT 25-J4
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J2
PCT 25-J4
PCT 25-J4
PCT 25-J4
PCT 25-J4
PCT 25-J4
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J2
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
PCT 35-J4
Mnimo
Hasta 8,7 / 15 kV
16,3
21,3
33
Hasta 12 / 20 kV
21,3
33
Hasta 18 / 30 kV
21,3
33
Mximo
28,5
35,1
53,3
35,1
53,3
35,1
53,3
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene
respectivamente.
125
media tensin
accesorios
COMPONENTES
1- MUELLE DE PRESIN CTE.:
Conecta la malla con la pantalla del cable.
2- SEMICONDUCTORA DEL CABLE:
Envuelve y protege de descargas elctricas.
3- CINTA DE SELLADO
4- AISLAMIENTO DEL CABLE:
Aislamiento del cable.
5- ENVOLVENTE:
Proteccin externa del empalme.
6- PANTALLA:
Malla de cobre que da continuidad a la pantalla del cable.
7- CAPA SEMICONDUCTORA:
Continuidad semiconductoras externa cables.
8- CAPA AISLANTE:
Aislante.
9- CAPA DIELCTRICA:
De alta constante dielctrica.
10- ELECTRODO:
Integrado en los empalmes para 12/20 kV.
2
3
6
4
7
8
9
10
CARACTERSTICAS
EMPALME CONTRCTIL EN FRO:
- Completamente integrado.
- Alta fiabilidad.
- Para todo tipo de cables.
Versin unipolar y tripolar.
Desde 6/10 kV hasta 18/30 kV.
Para cables con aislamiento polimrico y papel impregnado.
Con posibilidad de refuerzos mecnicos.
Fcil y rpido de instalar.
Nuevo soporte autoextrable, para un ahorro de tiempo, una disminucin de errores de extraccin del soporte y una instalacin ms limpia.
Nuevas placas de sellado que minimizan la posiblidad de error tanto en la cantidad como en el dimensionado e incorpora un film que facilita el
deslizamiento de la cubierta.
Nuevo aceite lubricante, que facilita el desdoblamiento de la cubierta.
126
media tensin
accesorios
Tensin
(kV)
D
E
F
H
IP
I
12/20
12/20
12/20
18/30
18/30
18/30
17.2
19.0
23.1
24.4
27.8
31.9
32.0
34.0
44.0
46.0
52.0
62.0
Este empalme puede emplearse para unir cables trifsicos con igual o diferente naturaleza de aislante y campo elctrico (empalmes mixtos), lo
que le permite ampliar el carcter de aplicacin universal que tena hasta ahora empalmando cables unipolares de aislamiento seco y papel. En
los empalmes tripolares para cables de aislamiento de papel impregnado y mixtos est incluida la caja de proteccin de polister y microesferas.
Para cables con papel impregnado, aadir el kit de adaptacin CPI-E.
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene,
respectivamente.
APLICACIN
Empalme Universal Contrctil en fro EPJMe-1C (24 kV) y EPJMe-1C (36 kV).
Seccin
(mm2)
6/10 kV
RHZ1
8.7/15 kV
RHZ1
50
70
95
120
150
185
240
300
400
500
630
800
D
D
E-D
E-D
F-E
F-H
H-IP
H-IP
H-IP-I
H-IP-I
I
D
E-D
E-D
E
F-E
F-H
F-H-IP
H-IP
H-IP-I
H-IP-I
H-IP-I
I
12/20 kV
RHZ1
HEPRZ1
D
E-D
F-D-E
F-D-E-H
F-E-H
F-H
F-H-IP
IP-H-I
IP-H-I
I-IP
I-IP
I
D
D-E
E-D
E-D
E-F
F-E-H
F-H-IP
H-IP
H-I-IP
I-IP
I-IP
I
127
15/25 kV
RHZ1
E-D
H
H
H
IP-H
IP-H
I-H-IP
I-H-IP
I-IP
I-IP
I
I
18/30 kV
RHZ1
HEPRZ1
H
H
H-IP
H-IP
H-IP
H-IP-I
IP-H-I
IP-H-I
I-IP
I-IP
I
I
H
H
H
H
H
H-IP
IP-H
IP-H-I
I-IP
I-IP
I
I
media tensin
accesorios
128
media tensin
accesorios
Empalme ECOSPEED
DESCRIPCIN
EMPAME UNIVERSAL CONTRCTIL EN FRO, (hasta 18/30 kV)
Nuevo empalme Gama ECOSPEED 24 kV y 36kV.
Ref. Norma: HD 628; HD 629.
Correspondencia con las normas: IEC 60502-4; IEC 60055
Nivel de tensin hasta 18/30 KV
COMPONENTES
1- CAPA DIELCTRICA:
De alta constante dielctrica.
2- SEMICONDUCTORA DEL CABLE:
Envuelve y protege de descargas elctricas.
3- CINTA DE SELLADO
4- AISLAMIENTO DEL CABLE:
Aislamiento del cable.
5- ENVOLVENTE:
Proteccin externa del empalme.
6- PANTALLA:
Malla de cobre que da continuidad a la pantalla del cable.
7- CAPA SEMICONDUCTORA:
Continuidad semiconductoras externa cables.
8- CAPA AISLANTE:
Aislante.
2
3
6
4
7
8
9
10
129
media tensin
Empalme ECOSPEED
CARACTERSTICAS
EMPALME CONTRCTIL EN FRO:
- Completamente integrado, todos los componentes estn incluidos en el cuerpo del empalme, permitiendo el centraje y la fcil extraccin del
soporte. Consta en los extremos de un sistema que permite la sujecin de la pantalla sin necesidad de otros componentes
- Alta fiabilidad.
- Para todo tipo de cables.
Versin unipolar y tripolar.
Hasta 18/30 KV.
Para cables con aislamiento polimrico y papel impregnado.
Con posibilidad de refuerzos mecnicos.
Fcil y rpido de instalar.
Nuevo soporte autoextrable, para un ahorro de tiempo, una disminucin de errores de extraccin del soporte y una instalacin ms limpia.
Nuevas placas de sellado que minimizan la posiblidad de error tanto en la cantidad como en el dimensionado e incorpora un film que facilita el
deslizamiento de la cubierta.
Nuevo aceite lubricante, que facilita el desdoblamiento de la cubierta.
CARACTERSTICAS DIMENSIONALES
Modelo
Empalme
Referencia
Tensin
(kV)
Dimetro mnimo
sobre aislamiento
0
0
0
1
3
4
151556
162662
151656
202070-1
202070-3
252580-4
12/20
12/20
18/30
18/30
18/30
18/30
19
23
19
28
34
36
Dimetro mximo
cubierta exterior
40
44
40
55
55
62
Este empalme puede emplearse para unir cables tripolares con igual o diferente naturaleza de aislante y campo elctrico (empalmes mixtos), lo
que le permite ampliar el carcter de aplicacin universal que tena hasta ahora empalmando cables unipolares de aislamiento seco y papel.
En los empalmes tripolares para cables de aislamiento de papel impregnado y mixtos est incluida la caja de proteccin de polister y microesferas.
Para cables con papel impregnado, aadir el kit de adaptacin CPI-E.
Para consulta de los dimetros sobre aislamiento en funcin de la seccin y tensin, consultar pginas 71 y 93 para cables Eprotenax y Voltalene,
respectivamente.
APLICACIN
Seccin
(mm2)
6/10 kV
RHZ1
95
120
150
185
240
300
400
0
0
0
0
0
1
1
8.7/15 kV
RHZ1
0
0
0
0
0
1
1
12/20 kV
18/30 kV
RHZ1
HEPRZ1
RHZ1
HEPRZ1
0
0
0
0
0-1
1
1
0
0
0
0
0-1
1
1
0
1
1
1
1
3
3
0
1
1
1
1
3
3
130
media tensin
accesorios
Empalme ECOSPEED
PROCESO DE MONTAJE
Fijacin del extremo del cable y empalme.
131
media tensin
accesorios
250 A
400 A
12/20 kV
12/20 kV
Interfase
Tipo de contacto
Conector
acodado
Conector
recto
DESLIZANTE
MSCE-250A
(pg. 136)
MSCS-250A
(pg. 133)
DESLIZANTE
ROSCADO
ROSCADO
ROSCADO
630 A
18/30 kV
Conector
acodado
Conector
recto
Conector
acodado
Conector
recto
MSCE-400A
(pg. 142)
MSCS-400A
(pg. 139)
MSCE-400A
(pg. 142)
MSCS-400A
(pg. 139)
12/20 kV 18/30 kV
Conector
en T
roscado
Conector
acodado
roscado
Conector
en T
roscado
Tipo
D1
7,9 mm
Profundidad: 32 mm
14 mm
Profundidad: 40 mm
M16
Longitud: 29 mm
M16
Longitud: 29 mm
M16
Longitud: 29 mm
D2
31 mm
46 mm
46 mm
39,9 mm
39,9 mm
D3
32,5 mm
56 mm
56 mm
52,1 mm
61,5 mm
D4
48,5 mm
70 mm
70 mm
76,2 mm
76,2 mm
L1
48 mm
90 mm
90 mm
81 mm
103,7 mm
250 A
Contacto deslizante
Hasta 12/20 kV
400 A
Contacto deslizante
Hasta 18/30 kV
Mismas dimensiones
que Interfase C
630 A
Contacto roscado
Hasta 18/30 kV
Mismas dimensiones
que Interfase B
1250 A
Contacto roscado
Hasta 12/20kV
1250 A
Contacto roscado
Hasta 18/30kV
132
media tensin
accesorios
INTERFASE
A
CABLES
- Ncleo aislante unipolar de polmeros (XLPE, HEPR, EPR, PE...).
- Conductores de cobre o aluminio, rgido o flexible.
- Pantalla semiconductora extrada o encintada.
- Pantalla metlica de cintas, hilos o tipo polylam (RH5Z1).
- Tensin de aislamiento hasta 24 KV (Um).
- Secciones del conductor: de 25 mm2 a 95 mm2.
NORMATIVAS
- Cumple con los requisitos de la VDE 0278 - NF C 33-051 - NF C 33-001 - CENELEC HD 629.1 S2 - IEC 60502-4.
- Interfaces: CENELEC EN 50180 - EN 50181.
- Contacto metlico: IEC 61238-1 A, HN 68-S-91.
CALIDAD ASEGURADA
- La empresa ha sido evaluada por terceros, asegurando su conformidad con los requisitos de la norma ISO 9001-EN 29001, versin 2000.
PACKING
- Se suministra como un kit de 3 conectores unipolares, conteniendo todos los componentes necesarios.
- Peso y volumen de envo (aprox.) del kit: 3 kg / 0,006 m3.
CARACTERISTICAS DE INSTALACIN
- Slo una referencia de producto por clase de tensin permite cubrir las secciones desde 25 mm2 a 95 mm2 tanto en cobre como en aluminio.
- No necesita herramientas especiales, calentar, encintar, o rellenar.
- Posicin Vertical, inclinada o invertida.
- Sin distancia mnima entre fases.
- La tres fases pueden tambin ser bloqueadas juntas y al equipo mediante el uso de un anillo metlico (suministrado separadamente).
- Puesta en marcha inmediatamente despus de conectar el conectador al pasatapas un conector desenchufado no debe ser activado.
OTROS PRODUCTOS
- Productos asociados, tales como pasatapas FMBOm-250, FMBOh-250, FMBOcm, FMBA-250 y accesorios.
- Conector Recto separable MSCE-250A.
133
media tensin
accesorios
INTERFASE
A
2. Semiconductora interior.
Semiconductora EPDM que envuelve el contacto metlico a fin de ionizar el aire
que queda atrapado.
7
4
335
5. Punto de prueba.
Elctricamente protegido por un tapn semiconductor EPDM. Un divisor capacitivo
permite la verificacin de la ausencia de tensin antes de quitar el conector.
1
235
6. Abrazaderas de anclaje.
Abrazaderas de fijacin de acero para el anclaje al pasatapas.
7. Ojal de Puesta a tierra.
Para la puesta a tierra del conector unindola a la pantalla del cable.
8. Hendidura de fijacin.
Resaltes para la fijacin del anillo metlico suministrado cuando es requerido para
las tres fases.
9. Protector de toma a tierra.
Adapta el cuerpo del conector al dimetro sobre aislamiento de los diferentes
cables. Garantiza la estanqueidad de la puesta a tierra y permite la prueba de
pantalla del cable.
134
2
5
8
3
105
media tensin
accesorios
Tensin
12 kV
17 kV
24 kV
Seccin
Conductor
mm2
Referencia
Mn.
Mx.
11,8
17,2
13,7
17,2
17,2
25
17,2
25
25
70
25
70
50
95
35
95
MSCS-250A-25-50/24
MSCS-250A-70-95/24
MSCA-250A-25-35/24
MSCS-250A-50-95/24
17,2
25
25
95
MSCS-250A-25-95/24
T1
T2
T3
Polylam (RH5Z1)
Cintas de cobre
Hilos de cobre
INSTALACIN
Dimensiones (instalado en el pasatapas) en mm.
(*) Dimensin mnima necesaria para la desconexin.
390*
335
32
62
EJEMPLO DE PEDIDO
Cable Polimrico Unipolar 12/20 KV de 50 mm2 en Aluminio, dimetro sobre aislamiento 21,5 mm, con pantalla de hilos de cobre:
MSCE-250A-25-95/24-T3
135
media tensin
accesorios
CABLES
- Ncleo aislante unipolar de polmeros (XLPE, HEPR, EPR, PE...).
- Conductores de cobre o aluminio, rgido o flexible.
- Pantalla semiconductora extrada o encintada.
- Pantalla metlica de cintas, hilos o tipo polylam (RH5Z1).
- Tensin de aislamiento hasta 24 KV (Um).
- Secciones del conductor: de 25 mm2 a 950 mm2.
NORMATIVAS
- Cumple con los requisitos de la VDE 0278 - NF C 33-051 - NF C 33-001 - CENELEC HD 629.1 S2 - IEC 60502-4.
- Interfaces: CENELEC EN 50180 - EN 50181
- Contacto metlico: IEC 61238-1 A, HN 68-S-91.
CALIDAD ASEGURADA
- La empresa ha sido evaluada por terceros, asegurando su conformidad con los requisitos de la norma ISO 9001-EN 29001, versin 2000.
PACKING
- Se suministra como un kit de 3 conectores unipolares, conteniendo todos los componentes necesarios.
- Peso y volumen de envo (aprox.) del kit: 3kg. / 0,006 m3.
CARACTERISTICAS DE INSTALACIN
- Slo una referencia de producto por clase de tensin permite cubrir las secciones desde 25 mm2 a 95 mm2 tanto en cobre como en aluminio.
- No necesita herramientas especiales, calentar, encintar, o rellenar.
- Posicin Vertical, inclinada o invertida.
- Sin distancia mnima entre fases.
- Puesta en marcha inmediatamente despus de conectar el conectador al pasatapas un conector desenchufado no debe ser activado.
OTROS PRODUCTOS
- Productos asociados, tales como pasatapas FMBOm-250, FMBOh-250, FMBOcm, FMBA-250 y accesorios.
- Conector Recto separable MSCS-250A.
136
media tensin
accesorios
160
6
7
2. Tornillo de fijacin.
Compuesto de cobre roscado en contacto del conductor.
3. Semiconductora interior.
Semiconductora EPDM que envuelve el contacto metlico a fin de ionizar el aire
que queda atrapado.
210
5
3
8
4
5. Cuerpo aislante.
Realizado con aislante EPDM, para la reconstitucin del aislamiento. Se mantiene
una presin sobre el aislamiento del cable y sobre el pasatapas, proporcionando
un excelente sellado ante la humedad.
6. Punto de prueba.
Elctricamente protegido por un tapn semiconductor EPDM. Un divisor capacitivo
permite la verificacin de la ausencia de tensin antes de quitar el conector.
10
7. Abrazaderas
Abrazaderas de fijacin de acero para el anclaje al pasatapas.
8. Ojal de Puesta a tierra.
Para la puesta a tierra del conector unindola a la pantalla del cable.
9. Hendidura de fijacin
Resaltes para la fijacin del anillo metlico suministrado cuando es requerido para
las tres fases.
10. Protector de toma a tierra.
Adapta el cuerpo del conector al dimetro sobre aislamiento de los diferentes
cables. Garantiza la estanqueidad de la puesta a tierra y permite la prueba de
pantalla del cable.
137
300
INTERFASE
A
media tensin
accesorios
Tensin
12 kV
17 kV
24 kV
Dimetro sobre
aislamiento (mm)
Seccin
Conductor
mm2
Referencia
Mn.
Mx.
11,8
17,2
13,7
17,2
17,2
25
17,2
25
25
70
25
70
50
95
35
95
MSCE-250A-25-50/24
MSCE-250A-70-95/24
MSCE-250A-25-35/24
MSCE-250A-50-95/24
17,2
25
25
95
MSCE-250A-25-95/24
T1
T2
T3v
Polylam (RH5Z1)
Cintas de cobre
Hilos de cobre
INSTALACIN
Dimensiones (instalado en el pasatapas) en mm.
(*) Dimensin mnima necesaria para la desconexin.
32
62
90
160
220*
110 mx.
70
270
EJEMPLO DE PEDIDO
Cable Polimrico Unipolar 12/20 KV de 50 mm2 en Aluminio, dimetro sobre aislamiento 21,5 mm, con pantalla de hilos de cobre:
MSCE-250A-50/24-T3
138
media tensin
accesorios
CABLES
- Ncleo aislante unipolar de polmeros (XLPE, EPR, PE...).
- Conductores de cobre o aluminio, rgido o flexible.
- Pantalla semiconductora extrada o encintada.
- Pantalla metlica de cintas, hilos o tipo polylam (RH5Z1).
- Tensin de aislamiento hasta 18/30 KV.
- Secciones del conductor: hasta 24 kV de 35 mm2 a 400 mm2.
36 kV de 35 mm2 a 400 mm2.
NORMATIVAS
- Cumple con los requisitos de la CENELEC HD 629.1 S2 - IEC 60502-4 - NF C 33-051 - NF C 33-001.
- Interfaces: CENELEC EN 50180 - EN 50181.
- Contacto metlico: IEC 61238-1 A, HN 68-S-91.
CALIDAD ASEGURADA
- La empresa ha sido evaluada por terceros, asegurando su conformidad con los requisitos de la norma ISO 9001-EN 29001, versin 2000.
PACKING
- Se suministra como un kit de 3 conectores unipolares, conteniendo todos los componentes necesarios.
- Peso y volumen de envo (aprox.) del kit: 4,5 kg / 0,01 m3.
CARACTERISTICAS DE INSTALACIN
- No necesita herramientas especiales, calentar, encintar, o rellenar.
- Posicin Vertical, inclinada o invertida.
- Sin distancia mnima entre fases.
- Puesta en marcha inmediatamente despus de conectar el conectador al pasatapas
- Un conector desenchufado no debe ser activado.
OTROS PRODUCTOS
- Productos asociados, tales como pasatapas FMBOs-400 y accesorios.
139
media tensin
accesorios
75
2. Semiconductora interior.
Semiconductora EPDM que envuelve el contacto metlico a fin de ionizar el aire
que queda atrapado.
325
5. Punto de prueba.
Elctricamente protegido por un tapn semiconductor EPDM. Un divisor capacitivo
permite la verificacin de la ausencia de tensin antes de quitar el conector.
7. Abrazaderas de anclaje.
Abrazaderas de fijacin de acero para el anclaje al pasatapas.
8. Ojal de Puesta a tierra.
Para la conexin del conector unindola a la pantalla metlica del cable.
140
6. Tapn.
Premoldeado de semiconductora EPDM. Protege el divisor capacitivo durante su
uso normal.
410
4. Cuerpo aislante.
Realizado con aislante EPDM, para la reconstitucin del aislamiento. Se mantiene
una presin sobre el aislamiento del cable y sobre el pasatapas, proporcionando
un excelente sellado ante la humedad.
INTERFASE
B
media tensin
accesorios
Tensin
24 kV
36 kV
Reductor
Mn.
Mx.
rB
rC
rD
rF
rC
rD
rE
rF
16,1
20,2
22,7
30,8
20,2
22,7
25,6
30,8
26,3
30,8
33,1
40,6
30,8
33,1
35,3
40,6
Seccin
Conductor
mm2
Referencia
25 - 95
120
150 - 240
300 - 400
25 - 95
120
150 - 240
300 - 400
MSCS-400A-25-95/24-T3-P1
MSCS-400A-120/24-T3-P1
MSCS-400A-150-240/24-T3-P1
MSCS-400A-300-400/24-T3-P1
MSCS-400A-25-95/36-T3-P1
MSCS-400A-120/36-T3-P1
MSCS-400A-150-240/36-T3-P1
MSCS-400A-300-400/36-T3-P1
T1
T2
T3
Polylam (RH5Z1)
Cintas de cobre
Hilos de cobre
INSTALACIN
Dimensiones (instalado en el pasatapas) en mm.
(*) Dimensin mnima necesaria para la desconexin.
540*
440
71
EJEMPLO DE PEDIDO
Cable Polimrico Unipolar 20 kV de 1x50 mm2, dimetro sobre aislamiento 21,5 mm, con pantalla de hilos de cobre, conductor de aluminio:
MSCS-400A-25-95/24-T3
o
MSCS-400A-150-240/24-T3
141
media tensin
accesorios
CABLES
- Ncleo aislante unipolar de polmeros (XLPE, EPR, PE...).
- Conductores de cobre o aluminio, rgido o flexible.
- Pantalla semiconductora extrada o encintada.
- Pantalla metlica de cintas, hilos o tipo polylam (RH5Z1).
- Tensin de aislamiento hasta 18/30 (36) KV.
- Secciones del conductor: hasta 24 kV de 35 mm2 a 400 mm2.
36 kV de 35 mm2 a 400 mm2.
NORMATIVAS
- Cumple con los requisitos de la CENELEC HD 629.1 S2 - IEC 60502-4 - NF C 33-051 - NF C 33-001.
- Interfaces: CENELEC EN 50180 - EN 50181
- Contacto metlico: IEC 61238-1 A, HN 68-S-91.
CALIDAD ASEGURADA
- La empresa ha sido evaluada por terceros, asegurando su conformidad con los requisitos de la norma ISO 9001-EN 29001, versin 2000.
PACKING
- Se suministra como un kit de 3 conectores unipolares, conteniendo todos los componentes necesarios.
- Peso y volumen de envo (aprox.) del kit: 6kg. / 0,013 m3.
CARACTERISTICAS DE INSTALACIN
- No necesita herramientas especiales, calentar, encintar, o rellenar.
- Posicin Vertical, inclinada o invertida.
- Sin distancia mnima entre fases.
- Voltage del aislante hasta 18/30 (36) kV.
- Puesta en marcha inmediatamente despus de conectar el conectador al pasatapas
- Un conector desenchufado no debe ser activado.
OTROS PRODUCTOS
- Productos asociados, tales como pasatapas FMBOm-400 y accesorios.
- Conector Recto separable MSCS/EC-400B.
142
media tensin
accesorios
3 270
220
75
2. Tornillo de fijacin.
Compuesto de cobre roscado en contacto del conductor.
3. Semiconductora interior.
Semiconductora EPDM que envuelve el contacto metlico a fin de ionizar el aire
que queda atrapado.
275
6
360
5. Cuerpo aislante.
Realizado con aislante EPDM, para la reconstitucin del aislamiento. Se mantiene
una presin sobre el aislamiento del cable y sobre el pasatapas, proporcionando
un excelente sellado ante la humedad.
6. Punto de prueba.
Elctricamente protegido por un tapn semiconductor EPDM. Un divisor capacitivo
permite la verificacin de la ausencia de tensin antes de quitar el conector.
7. Abrazaderas
Abrazaderas de fijacin de acero para el anclaje al pasatapas o a otros accesorios.
8. Ojal de Puesta a tierra.
Para la puesta a tierra del conector unindola a la pantalla metlica del cable.
9. Protector de toma a tierra.
Adapta el cuerpo del conector al dimetro sobre aislamiento de los diferentes
cables. Garantiza la estanqueidad de la puesta a tierra y permite la prueba de
pantalla del cable.
143
INTERFASE
B
media tensin
accesorios
Mn.
Mx.
Seccin
Conductor
mm2
rB
rC
rD
rF
rC
rD
rE
rF
16,1
20,2
22,7
30,8
20,2
22,7
25,6
30,8
26,3
30,8
33,1
40,6
30,8
35,4
35,3
40,6
35 - 95
120
150 - 240
300 - 400
35 - 95
120
150 - 240
300 - 400
Tensin
24 kV
36 kV
Referencia
MSCE-400A-35-95/24-T3-P1
MSCE-400A-120/24-T3-P1
MSCE-400A-150-240/24-T3-P1
MSCE-400A-300-400/24-T3-P1
MSCE-400A-35-95/36-T3-P1
MSCE-400A-120/36-T3-P1
MSCE-400A-150-240/36-T3-P1
MSCE-400A-300-400/36-T3-P1
T1
T2
T3
Polylam (RH5Z1)
Cintas de cobre
Hilos de cobre
INSTALACIN
Dimensiones (instalado en el pasatapas) en mm.
(*) Dimensin mnima necesaria para la desconexin.
90
158
250
355*
78
300
98 mx.
320
EJEMPLO DE PEDIDO
Cable Polimrico Unipolar 20 kV de 1x50 mm2 en Aluminio, dimetro sobre aislamiento 21,5 mm, con pantalla de hilos de cobre:
MSCE-400A-25-95/24-T3
o
MSCE-400A-150-240/24-T3
144
media tensin
accesorios
CABLES
- Ncleo aislante unipolar de polmeros (XLPE, HEPR, EPR, PE...).
- Conductores de cobre o aluminio, rgido o flexible.
- Pantalla semiconductora extruda o encintada.
- Pantalla metlica de cintas, hilos o tipo polylam (RH5Z1).
- Tensin de aislamiento hasta 36 KV (Um).
- Secciones del conductor: de 35 mm2 a 400 mm2.
NORMATIVAS
- Cumple con los requisitos de la VDE 0278 - NF C 33-051 - NF C 33-001 - CENELEC HD 629.1 S2 - IEC 60502-4.
- Interfaces: CENELEC EN 50180 - EN 50181.
- Contacto metlico: IEC 61238-1 A, HN 68-S-91.
CALIDAD ASEGURADA
- La empresa ha sido evaluada por terceros, asegurando su conformidad con los requisitos de la norma ISO 9001-EN 29001, versin 2000.
PACKING
- Se suministra como un kit de 3 conectores unipolares, conteniendo todos los componentes necesarios.
- Peso y volumen de envo (aprox.) del kit: 6 kg / 0,013 m3.
CARACTERISTICAS DE INSTALACIN
- Slo tres referencias de producto por clase de tensin permite cubrir las secciones desde 35 mm2 a 240 mm2 tanto en cobre como en aluminio.
- No necesita herramientas especiales, calentar, encintar, o rellenar.
- Posicin Vertical, inclinada o invertida,
- Sin distancia mnima entre fases.
- Puesta en marcha inmediatamente despus de conectar el conectador al pasatapas un conector desenchufado no debe ser activado.
OTROS PRODUCTOS
- Productos asociados, tales como pasatapas FMBOs-400 y accesorios.
145
media tensin
accesorios
220
2
3. Semiconductora interior.
Semiconductora EPDM que envuelve el contacto metlico a fin de ionizar el aire
que queda atrapado.
285
9
3
5. Cuerpo aislante.
Realizado con aislante EPDM, para la reconstitucin del aislamiento. Se mantiene
una presin sobre el aislamiento del cable y sobre el pasatapas, proporcionando
un excelente sellado ante la humedad.
6. Punto de prueba.
Elctricamente protegido por un tapn semiconductor EPDM. Un divisor capacitivo
permite la verificacin de la ausencia de tensin antes de quitar el conector.
10
7. Aislante.
Realizado con Epoxy y una rosca para la sujecin del tornillo.
8. Tapn.
Premoldeado de semiconductora EPDM. Protege el divisor capacitivo durante su
uso normal.
9. Ojal de Puesta a tierra.
Para la puesta a tierra del conector unindola a la pantalla del cable.
10. Reductor de alta permitividad.
Adapta el cuerpo del conector al dimetro sobre aislamiento de los diferentes
cables. Garantiza la estanqueidad de la puesta a tierra y permite la prueba de
pantalla del cable.
146
8
1
370
75
2. Tornillo de fijacin.
Compuesto de acero con plata chapada, roscado en ambos extremos para la fijacin
de los elementos. Una presin uniforme mantiene el contacto.
INTERFASE
C
media tensin
accesorios
Mn.
Mx.
Seccin
Conductor
mm2
rB
rC
rD
rF
rC
rD
rE
rF
16,1
20,2
22,7
30,8
20,2
22,7
25,6
30,8
26,3
30,8
33,1
40,6
30,8
33,1
35,3
40,6
25 - 95
120
150 - 240
300 - 400
25 - 95
120
150 - 240
300 - 400
Tensin
24 kV
36 kV
Referencia
MSCT-400A-25-95/24-T3-P1
MSCT-400A-120/24-T3-P1
MSCT-400A-150-240/24-T3-P1
MSCT-400A-300-400/24-T3-P1
MSCT-400A-25-95/36-T3-P1
MSCT-400A-120/36-T3-P1
MSCT-400A-150-240/36-T3-P1
MSCT-400A-300-400/36-T3-P1
T1
T2
T3
Polylam (RH5Z1)
Cintas de cobre
Hilos de cobre
INSTALACIN
Dimensiones (instalado en el pasatapas) en mm.
(*) Dimensin mnima necesaria para la desconexin.
145
250
75
350 *
85
330
EJEMPLO DE PEDIDO
Cable Polimrico Unipolar 12/20 KV de 50 mm2 en Aluminio, dimetro sobre aislamiento 21,5 mm, con pantalla de hilos de cobre:
MSCT-630 A-35-95/24-T3
147
media tensin
accesorios
CABLES
- Ncleo aislante unipolar de polmeros (XLPE, HEPR, EPR, PE...).
- Conductores de cobre o aluminio, rgido o flexible
- Pantalla semiconductora extrada o encintada.
- Pantalla metlica de cintas, hilos o tipo polylam (RH5Z1).
- Tensin de aislamiento hasta 36 KV (Um).
- Secciones del conductor: de 35 mm2 a 400 mm2.
NORMATIVAS
- Cumple con los requisitos de la VDE 0278 - NF C 33-051 - NF C 33-001 - CENELEC HD 629.1 S2 - IEC 60502-4.
- Interfaces: CENELEC EN 50180 - EN 50181
- Contacto metlico: IEC 61238-1 A, HN 68-S-91.
CALIDAD ASEGURADA
- La empresa ha sido evaluada por terceros, asegurando su conformidad con los requisitos de la norma ISO 9001-EN 29001, versin 2000.
PACKING
- Se suministra como un kit de 3 conectores unipolares, conteniendo todos los componentes necesarios.
- Peso y volumen de envo (aprox.) del kit: 6 kg / 0,013 m3.
CARACTERISTICAS DE INSTALACIN
- Slo tres referencias de producto por clase de tensin permite cubrir las secciones desde 35 mm2 a 240 mm2 tanto en cobre como en aluminio.
- No necesita herramientas especiales, calentar, encintar, o rellenar.
- Posicin Vertical, inclinada o invertida.
- Sin distancia mnima entre fases.
- Puesta en marcha inmediatamente despus de conectar el conectador al pasatapas un conector desenchufado no debe ser activado.
OTROS PRODUCTOS
- Productos asociados, tales como pasatapas FMBOs-400 y accesorios.
148
media tensin
accesorios
175
2
3. Semiconductora interior.
Semiconductora EPDM que envuelve el contacto metlico a fin de ionizar el aire
que queda atrapado.
285
8
3
10
7. Aislante.
Realizado con Epoxy y una rosca para la sujecin del tornillo.
8. Tapn.
Premoldeado de semiconductora EPDM. Protege el divisor capacitivo durante su
uso normal.
9. Ojal de Puesta a tierra.
Para la puesta a tierra del conector unindola a la pantalla del cable.
10. Reductor de alta permitividad.
Adapta el cuerpo del conector al dimetro sobre aislamiento de los diferentes
cables. Garantiza la estanqueidad de la puesta a tierra y permite la prueba de
pantalla del cable.
149
1
5
5. Cuerpo aislante.
Realizado con aislante EPDM, para la reconstitucin del aislamiento. Se mantiene
una presin sobre el aislamiento del cable y sobre el pasatapas, proporcionando
un excelente sellado ante la humedad.
6. Punto de prueba.
Elctricamente protegido por un tapn semiconductor EPDM. Un divisor capacitivo
permite la verificacin de la ausencia de tensin antes de quitar el conector.
365
75
2. Tornillo de fijacin.
Compuesto de acero con plata chapada, roscado en ambos extremos para la fijacin
de los elementos. Una presin uniforme mantiene el contacto.
INTERFACE
C
media tensin
accesorios
Mn.
Mx.
Seccin
Conductor
mm2
rB
rC
rD
rF
rC
rD
rE
rF
16,1
20,2
22,7
30,8
20,2
22,7
25,6
30,8
26,3
30,8
33,1
40,6
30,8
33,1
35,3
40,6
25 - 95
120
150 - 240
300 - 400
25 - 95
120
150 - 240
300 - 400
Tensin
24 kV
36 kV
Referencia
MSCEA-400A-25-95/24-T3-P1
MSCEA-400A-120/24-T3-P1
MSCEA-400A-150-240/24-T3-P1
MSCEA-400A-300-400/24-T3-P1
MSCEA-400A-25-95/36-T3-P1
MSCEA-400A-120/36-T3-P1
MSCEA-400A-150-240/36-T3-P1
MSCEA-400A-300-400/36-T3-P1
T1
T2
T3
Polylam (RH5Z1)
Cintas de cobre
Hilos de cobre
INSTALACIN
Dimensiones (instalado en el pasatapas) en mm.
(*) Dimensin mnima necesaria para la desconexin.
310*
82
145
210
75
330
EJEMPLO DE PEDIDO
Cable Polimrico Unipolar 12/20 KV de 50 mm2 en Aluminio, dimetro sobre aislamiento 21,5 mm, con pantalla de hilos de cobre:
MSCEA-630A-35-95/24-T3
150
media tensin
accesorios
INTERFASE
C
INTERFASE
C
CARACTERSTICAS
- No precisa de herramientas especiales, encintados ni rellenos.
- Se puede instalar en cualquier posicin.
- No es necesario conservar las distancias mnimas entre fases.
- Se puede dar tensin inmediatamente despus de su conexionado.
- Conectable a Pasatapas tipo C (1250 A) segn EN-50181.
- Para conexin a transformadores, celdas compactas, motores interruptores, ect. Diversas posibilidades de conexionado.
- Utilizables en instalaciones de interior e intemperie.
- El conector est completamente apantallado por una envolvente semiconductora.
- Apto para 1250 A. En sobrecarga 1800 A (8 horas cada 24 horas) (interfase C).
- Maniobrables sin tensin.
- Para cables de aislamiento seco unipolares (PE, XLPE, EPR, etc.) y de papel impregnado, con conductores de aluminio y cobre.
- Pantallas de cable: semiconductora extrusionada o encintada y metlica de hilos o cintas.
- Secciones del conductor 50 a 630 mm2 Cu o Al.
DESCRIPCIN
1- CONTACTO ROSCADO:
Vstago de cobre, roscado en ambos extremos para sujecin de los contactos. Mantiene una presin
uniforme con el pasatapas y el contacto engastado al conductor.
2- TAPN AISLANTE:
Componente epoxy que dispone de un inserto metlico hembra que conecta al contacto roscado.
3- DIVISOR CAPACITIVO:
Elemento metlico de cabeza hexagonal, ubicado en el tapn aislante. Permite comprobar la ausencia
de tensin.
4- CAPUCHN:
Parte premoldeada semiconductora (EPDM) que pone a tierra el divisor capacitivo durante el servicio.
5- OJAL DE TOMA-TIERRA:
Permite conectar la semiconductora externa del conector a la pantalla del cable.
6- CONTACTO DEL CONDUCTOR:
Terminal metlico de dimensiones adecuadas para la seccin del conductor que permite su conexin
al equipo.
7- CAPA SEMICONDUCTORA INTERNA:
Proteccin semiconductora EPDM que acta como jaula de Faraday evitando la ionizacin del aire
ocluido en su interior.
8- CAPA SEMICONDUCTORA EXTERNA:
Capa semiconductora premoldeada (EPDM) diseada para dar continuidad a la pantalla del cable. Su
conexin a la misma asegura que el conjunto se mantiene al potencial de tierra.
9- CUERPO AISLANTE:
Premoldeado aislante (EPDM) para la reconstitucin integral del aislamiento. Mantiene una
presin de contacto uniforme entre el reductor y el aislamiento del cable.
10- REDUCTOR:
Premoldeado (EPDM) que permite la total adaptacin del accesorio a las diferentes secciones y tensiones
de los cables.
11- PROTECTOR DE LA TOMA DE TIERRA:
Componente (EPDM) que asegura la estanquidad y protege la toma de tierra.
151
6
9
7
10
5
11
media tensin
accesorios
Tamao
del reductor
Mx.
28,5
32,6
35,8
38,8
41,8
45,8
24,3
A
B
C
D
E
F
Z
EJEMPLO DE PEDIDO: Cable 20 kV, 1 x 95 mm2, dimetro sobre aislamiento 23,2 mm, conductor aluminio. Contacto roscado. FMCTXs-95/24 AI.
Seccin
mm2
8,7/15 kV
50
70
95
120
150
185
240
300
400
500
630
FMCTXs-70/17,5
FMCTXs-95/17,5
FMCTXs-120/17,5
FMCTXs-150/17,5
FMCTXs-185/17,5
FMCTXs-240/17,5
FMCTXs-300/17,5
FMCTXs-400/17,5
FMCTXs-500/17,5
FMCTXs-630/17,5
12/20 kV
FMCTXs-50/24
FMCTXs-70/24
FMCTXs-95/24
FMCTXs-120/24
FMCTXs-150/24
FMCTXs-185/24
FMCTXs-240/24
FMCTXs-300/24
FMCTXs-400/24
FMCTXs-500/24
FMCTXs-630/24
15/25 kV
FMCTXs-50/30
FMCTXs-70/30
FMCTXs-95/30
FMCTXs-120/30
FMCTXs-150/30
FMCTXs-185/30
FMCTXs-240/30
FMCTXs-300/30
FMCTXs-400/30
FMCTXs-500/30
FMCTXs-630/30
NOTAS:
1. Para instalacin en cable HEPR, especificar la denominacin HEPR al final IMP. Ejemplo: FMCTXs-500/36 AL HEPR.
2. Especificar tipo de conductor de Al o Cu. Ejemplo: FMCTXs-500/36 Al.
INSTALACIN
290
140
190
295
355*
420
152
18/30 kV
FMCTXs-50/36
FMCTXs-70/36
FMCTXs-95/36
FMCTXs-120/36
FMCTXs-150/36
FMCTXs-185/36
FMCTXs-240/36
FMCTXs-300/36
FMCTXs-400/36
FMCTXs-500/36
FMCTXs-630/36
media tensin
accesorios
FMCTXs
Terminal.
TAPN AISLANTE
Proteccin del pasatapas.
FMCTXs
Conexin a pasatapas.
153
media tensin
accesorios
154
media tensin
accesorios
COMPONENTES
1- AISLADOR (Monobloc):
Fabricado en goma de silicona anti-tracking.
2- CUERPO AISLANTE:
Fabricado con aislante EPDM, mantiene una presin de contacto uniforme en la interfase
realizando una excelente barrera contra la humedad.
3- PANTALLA SEMICONDUCTORA INTERNA:
Proteccin semiconductora EPDM que acta como jaula de Faraday evitando la
ionizacin del aire en su interior.
4- PANTALLA SEMICONDUCTORA EXTERNA:
Proteccin semiconductora EPDM que acta como deflector de campo.
5- OJAL:
Para puesta a tierra.
6- DISPOSITIVO DE FIJACIN:
Dispositivo de acero inoxidable que fija el aislador.
7- VARILLA DE CONTACTO:
Varilla de cobre acabado en punta para la conexin al equipo correspondiente.
CARACTERSTICAS
- PARA CABLES DE AISLAMIENTO SECO Y PAPEL IMPREGNADO.
- Utilizacin en instalaciones de interior.
- Para alimentacin de transformadores equipados con pasatapas enchufables y conexin directa a conductores no aislados (hilos, barras).
- Para realizar ensayos dielctricos del transformador (no ensayos de serie).
- Intensidad nominal 250 A.
- Intensidad admisible en sobrecarga: 300 A (8 horas por periodo de 24 horas).
- Slo maniobrable sin tensin.
155
2
3
4
5
6
7
media tensin
accesorios
90
318
40
M12
95
156
media tensin
accesorios
COMPONENTES
1- CAPUCHN:
Protege mecnicamente y evita la humedad en la superficie de acoplamiento
(2) durante el transporte y el almacenaje. No puede ser usado como proteccin
elctrica.
2- SUPERFICIE DE ACOPLAMIENTO:
Interfase que conecta al terminal enchufable, sellndolo con presin, para
proteccin contra la humedad.
3- PATILLAS DE ENGANCHE:
Patillas que permiten el enganche de los herrajes de fijacin del conector.
4- CONTACTO ELSTICO:
Contacto enchufable roscado o liso que permite la conexin del producto adjunto.
5- PLACA DE PUESTA A TIERRA:
Electrodo conectado por el plato de acero o el cobre electroltico unido a la
instalacin de tierra.
6- CUERPO MOLDEADO EN RESINA EPOXY:
Preparado para la inmersin en el aceite del transformador. (Si el dielctrico es
aire, el pasatapas posee unas aletas en resina epoxy).
7- CONEXIN:
Varilla de cobre con la superficie exterior roscada para permitir la conexin al
equipo correspondiente.
1
2
3
4
5
6
7
CARACTERSTICAS
PARA CABLES DE AISLAMIENTO SECO Y PAPEL IMPREGNADO EN TRANSFORMADORES CON ACEITE O AIRE COMO AISLANTE
- Para instalaciones de interior y de exterior.
- Intercambiable con pasatapas de porcelana de 250A.
- Intensidad nominal 250A.
- Intensidad admisible en sobrecarga: 300A (8 horas por periodo de 24 horas).
- Slo maniobrable sin tensin.
Nivel
aceite
Tensin
H mm
12 kV
24 kV
40
50
157
media tensin
accesorios
8 28
A
PF1 - L = 178
PF1 - C = 115
PF1 - L = 283
PF1 - C = 220
85
COTAS
20
16
M 10
PF1C 250
PF1L 250
A
B
PF1-L
PF1-C
72
709
75
110
158
media tensin
accesorios
COMPONENTES
1- CAPUCHN:
Protege mecnicamente y evita la humedad en la superficie de acoplamiento (2) durante el
transporte y el almacenaje. No puede ser usado como proteccin elctrica.
2- SUPERFICIE DE ACOPLAMIENTO:
Interfase que conecta al terminal enchufable, sellndolo con presin, para proteccin contra
humedad.
3- CONTACTO ENCHUFABLE:
Contacto enchufable liso o roscado que permite la conexin del conector.
4- PATILLAS DE ENGANCHE:
Patillas que permiten el enganche de los herrajes de fijacin del conector.
5-PLACA DE PUESTA A TIERRA:
Electrodo conectado por el plato de acero o el cobre electroltico unido a la instalacin de tierra.
6- CUERPO MOLDEADO EN RESINA EPOXY:
Preparado para inmersin en el aceite del transformador. (Si el dielctrico es aire, el pasatapas
posee unas aletas en resina epoxy).
7- CONEXIN:
Varilla de cobre con la superficie exterior roscada para permitir la conexin al equipo
correspondiente.
2
3
4
5
PF2 - 400
PF3 - 400
CARACTERSTICAS
- PARA CABLES DE AISLAMIENTO SECO Y PAPEL IMPREGNADO. SLO EN TRANSFORMADORES CON ACEITE COMO AISLANTE.
- Para instalacin de interior y de exterior.
- Intercambiable con pasatapas de porcelana de 1000 A.
- Intensidad nominal 400 A.
- Intensidad admisible en sobrecarga: 600 A (8 horas por periodo de 24 horas).
- Tensin de aislamiento de hasta 36 kV (Umax).
- Solo maniobrable sin tensin.
Nivel
aceite
H mm
6/10
12/20
18/30
40
50
70
159
media tensin
accesorios
10
36
138
COTAS
330
100
152
150
40
30
M 16
PF2 - 400
PF3 - 400
160
media tensin
accesorios
FMPCd-250
Derivacin en T, hembra para dos terminales
enchufables y pasatapas.
FMPCs-250
Pieza para dos terminales enchufables.
FMPE-250
Tapn con conexin tierra.
FMR-250
Tapn aislante hembra
(Para aislamiento pasatapas).
161
media tensin
accesorios
FMPCt-250
Derivacin en T, macho para tres terminales
enchufables.
FMPD-250
Tapn aislante macho.
FMPS-250
Tapn aislante macho con soporte.
162
media tensin
accesorios
FMPE-400
Tapn de conexin a tierra.
FMPCs-400
Pieza empalme terminales enchufables.
FMR-400
Tapn aislante hembra para aislamiento
pasatapas.
163
media tensin
accesorios
Resistencia a los
agentes qumicos
Resistencia a los
rayos ultravioleta
Resistencia a la
absorcin del agua
De acuerdo con: Pasatapas Norma DIN 47637. Ensayos tipo de acuerdo con HD 629.1
Resistente a rayos ultra violeta
Resistencia a la absorcin del agua
Resistencia a los agentes qumicos
No inflamable, auto extinguible y resistente a los golpes
Temperatura de servicio: -50 C a +180 C Con junta de neopreno
Elevada elasticidad
Vida ilimitada de almacenamiento
Materiales respetuosos con el medio ambiente
CARACTERSTICAS
TIPO 0
Tensin mxima de servicio
Intensidad Nominal
Tensin soportada a frecuencia industrial
Tensin soportada onda de choque
Descargas Parciales
Ensayo de Tensin DC
Impulsos
Um (kV)
In (A)
1 min. (kV)
(BIL) (kV)
2 x Uo (pC)
15 min. 6 x Uo (kV)
(kA)
24
250
50
125
5
72
4
Um (kV)
In (A)
1 min. (kV)
(BIL) (kV)
2 x Uo (pC)
15 min. 6 x Uo (kV)
(kA)
36
630
70
170
5
108
125
Um (kV)
In (A)
1 min. (kV)
(BIL) (kV)
2 x Uo (pC)
15 min. 6 x Uo (kV)
(kA)
36
1.250
95
200
5
125
150
164
media tensin
accesorios
Um (kV)
In (A)
1 min. (kV)
(BIL) (kV)
2 x Uo (pC)
15 min. 6 x Uo (kV)
(kA)
52
1.250
117
250
5
156
150
TABLAS DE REDUCTORES
Ejemplo de pedido: INNEX IC1250Y seccin (H C P) tipo conector (CD SD)
Tipo
Reductor
TIPO 3
Tipo
Reductor
A
B
C
D
E
F
G
H
I
J
K
L
M
N
A
B
C
D
E
F
G
H
I
J
K
INNEX IC250
sobre aislamiento
MIN
12,3
14,3
16,3
17,8
18,8
20,3
MAX
15,5
17,5
19,5
21,0
22,0
23,5
Cod
0/02
0/03
0/04
0/05
0/06
0/07
MAX
20,0
26,3
28,4
31,4
34,5
36,9
37,9
39,0
41,6
42,0
43,0
45,1
47,2
49,6
51,0
INNEX IC630
sobre aislamiento
MIN
14,8
16,3
17,3
18,3
20,3
22
23,3
24,8
26,8
28,8
31,8
TIPO 3Y
INNEX IC I250
sobre aislamiento
MIN
19,0
23,1
25,2
28,2
31,3
33,7
34,7
35,8
38,4
38,8
39,8
41,9
44,0
46,4
47,8
TIPO 1
Tipo
Reductor
Cod
3/15
3/12
3/09
3/08
3/01
3/02
3/03
3/04
3/05
3/11
3/06
3/14
3/07
3/13
3/10
A
B
C
D
E
F
G
H
I
J
K
L
M
N
165
MAX
18,0
19,5
20,5
21,5
23,5
25,2
26,5
28,0
30,0
32,0
35,0
Cod
1/03
1/04
1/05
1/06
1/08
1/09
1/10
1/11
1/12
1/13
1/14
INNEX IC I250Y
sobre aislamiento
MIN
23,1
25,2
28,2
31,3
33,7
34,7
35,8
38,4
38,8
39,8
41,9
44,0
46,4
47,8
MAX
26,3
28,4
31,4
34,5
36,9
37,9
39,0
41,6
42,0
43,0
45,1
47,2
49,6
51,0
Cod
3/12
3/09
3/08
3/01
3/02
3/03
3/04
3/05
3/11
3/06
3/14
3/07
3/13
3/10
media tensin
accesorios
Resistencia a la
absorcin de agua
No propagacin
de la llama
Libre
de halgenos
Reconocido
por UL
DESCRIPCIN
AISLAMIENTO
Material: Tubo de poliolefina reticulada de pared media.
Color: Rojo.
APLICACIONES
Tubo termorretrctil anti-track de pared media para embarrado, especialmente diseado para el aislamiento de barras elctricas de hasta media
tensin (tensiones de servicio hasta 36 kV en embarrados elctricos).
166
media tensin
accesorios
19,0
33,0
52,0
69,8
88,9
119,3
Contrado
Rangos aplicaciones
5,5
10,1
19,0
25,4
29,9
39,9
2,70
3,00
2,80
2,90
3,10
3,20
Barras rectangulares
Barras redondas
(Mn.)
mm
(Mx.)
mm
(Mn.)
mm
(Mx.)
mm
6,4
12,7
31,5
44,4
57,1
73
6,4
28,5
50,8
76,2
101,6
142,8
6,8
12,4
22,3
29,7
35,8
47,7
15,2
27,9
43,1
58,4
73,6
101,6
15 kV
25 kV
36 kV
BIL
kV
PTPE
Tubo de pared media
p a p (mm)
p a g (mm)
86,0
114,0
165,0
106,0
152,0
203,0
95
125
150
167
media tensin
accesorios
Mtodo de prueba
Rendimiento tipo
FSICOS
ASTM-D 412, ISO 37
ASTM-D 412, ISO 37
8,3 MPa
200%
ASTM-D 2671
ASTM-D 2671
ASTM-D 2671
10 MPa
200%
No agrieta, no prdidas
ASTM-D 2671
No agrieta
Aprobado
ELCTRICOS
ASTM-D 149
ASTM-D 257
ASTM-D 257
ASTM-D 150
ANSI C37,20, ASTM-D 2303
20 Kv/mm
510e9
1,9e16 cm
3,4
sin seguimiento
ASTM-G 53
sin seguimiento
tras 6000 horas
QUMICOS
Accin corrosiva
Resistencia a fluidos
Absorcin de agua
ASTM-D 2671
MIL-DTL-23053/15
ASTM-D570
168
No corrosivo
Buena a excelente
0,25%
media tensin
accesorios
ABRAZADERAS PLSTICAS
DESCRIPCIN
ABRAZADERAS PLASTICAS PARA CUALQUIER TIPO DE CABLE Y TENSIN
Libre
de halgenos
Resistencia al fro
Resistencia a los
rayos ultravioleta
Resistencia a los
agentes qumicos
TIPOS:
Abrazadera cable ST
Aplicacin en cables tanto unipolares como tetrapolares. Est compuesta por dos partes amovibles,
donde la parte inferior se fija sobre la estructura y la parte superior ejerce la presin sobre los cables.
Abrazadera cables TR
Sujecin de tres cables en tresbolillo. Est compuesta por dos partes amovibles, donde la parte inferior
se fija sobre la estructura y la parte superior ejerce la presin sobre los cables.
Abrazadera en bloque UN
Sujecin de tres o cuatro cables en posicin horizontal separadamente y sin cruzamientos.
De acuerdo con:
ISO 9002
Norma NEN-EN 60204 - 1
Resistencia a los rayos UV
Instalacin tanto en interior como en exterior
Amplio rango de aplicacin: 18 - 130 mm
Libre de halgenos
Resistente a productos qumicos y a cambios de temperatura
Resistente al fuego. VDE 0304, parte 3, clase IIA
Temperatura de servicio: -40 C a +135 C
APLICACIN
Valido para todo tipo de cables y tensiones. Para cables de AT se recomienda la utilizacin de una almohadilla libre de halgenos.
Descripcin
Abrazadera cable unipolar ST 18-26
Abrazadera cable unipolar ST 26-38
Abrazadera cable unipolar ST 36-52
Abrazadera cable unipolar ST 18-26
Abrazadera cable unipolar ST 75-100
Abrazadera cable unipolar ST 100-130
Abrazadera cable tripolar TR 25-40
Abrazadera cable tripolar TR 38-53
Abrazadera cable tripolar TR 53-66
Abrazadera cable tripolar TR 67-82
Abrazadera cable tripolar TR 82-98
Abrazadera cable tripolar TR 99-120
Abrazadera cable tripolar TR 121-145
Abrazadera en bloque UN 4 x 13-32
Abrazadera en bloque UN 4 x 30-47
Abrazadera en bloque UN 3 x 13-32
169
Rango mm
Mtrica
18-26
26-38
36-52
50-75
75-100
100-130
25-40
38-53
53-66
67-82
82-98
99-120
121-145
13-32
30-47
13-32
M10
M12
M12
M12
M14
M14
M10
M14
M14
M16
M16
M16
M16
M10
M12
M10
media tensin
accesorios
ABRAZADERAS PLSTICAS
COTAS
ABRAZADERA CABLE UNIPOLAR ST (RESISTENCIA MECNICA: 20 kN A 40 kN)
L
D
h
a
B
ST
18 - 26
26 - 38
36 - 52
50 - 75
75 - 100
100 - 130
Peso/Grs
18-26
26-38
36-52
50-75
75-100
100-130
77
92
108
128
169
200
45
60
60
60
80
80
49
60
75
95
127
158
10
12
12
12
14
14
36-44
48-60
58-74
76-101
110-135
141-170
13
21
26
35
51
65
6
10
11
14
19
20
90
170
225
310
815
1.000
TR
25 - 40
38 - 53
53 - 66
67 - 82
82 - 98
99 - 120
121 - 145
Peso/Grs
25-40
38-53
53-66
67-82
82-98
99-120
121-145
172
190
205
252
284
342
392
80
80
80
100
100
115
115
125
145
169
202
234
288
338
14,5
14,5
14,5
16,5
16,5
19,0
19,0
80-108
85-115
137-168
140-175
168-205
155-203
180-238
46
54
61
70
78
88
100
30
30
30
33
33
33
33
16
25
32
44
52
55
67
800
865
1.300
1.985
2.515
3.065
3.607
170
media tensin
accesorios
ABRAZADERAS PLSTICAS
COTAS
ABRAZADERA EN BLOQUE UN (RESISTENCIA MECNICA: 15 kN A 25 kN)
UN
Peso/Grs
3 x 13 - 32
4 x 13 - 32
4 x 30 - 47
186-50
246.50
345.00
32,25
32,25
44,50
60,50
60,50
85,00
62,75
62,75
87,50
60,50
60,50
85,00
10,50
10,50
13,00
43,00
43,00
65,00
45,00
45,00
50,00
61,00
61,00
66,00
145
205
375
171
media tensin
accesorios
FICHAS DE SUJECIN
DESCRIPCIN
FICHAS DE SUJECIN PARA CUALQUIER TIPO DE CABLE
Libre
de halgenos
Resistencia al fro
Resistencia a los
rayos ultravioleta
APLICACIN
Descripcin
Rango mm
Uso en gua
8-36
14-48
14-48
24-72
24-72
20/10 - 27/18
27/18 - 28/30
35/18
27/18 - 28/30
35/18
172
media tensin
accesorios
FICHAS DE SUJECIN
COTAS DE LA GUA
Modelo 20/10
20
10
6,4
15
25
10,5
Modelo 27/18
27
20
12
35
18
1,2
15
Modelo 28/30
28
20
30
1,8
12
35
18
Modelo 35/18
35
18
1,5
16,5
173
media tensin
accesorios
CINTA P1000
DESCRIPCIN
CINTA AISLANTE DE POLICLORURO DE VINILO PLASTIFICADO ADHESIVA DE COLORES
CARACTERSTICAS
Excelentes caractersticas mecnicas.
- Resistente al aceite, sustancias qumicas y agentes atmosfricos.
APLICACIN
Se emplea como aislamiento en empalmes y derivaciones en baja tensin (usos domsticos) y para realizaciones de fases.
ESPECIFICACIONES TCNICAS
Caractersticas
Unidad
FSICAS
-
Valor
Condicin
Espesor
Longitud
Ancho
Adherencia
Alargamiento
Temperatura trabajo
Carga rotura
mm
m
mm
g/cm
%
C
kg/cm2
Resistencia:
Ozono
cidos y alcals
Aceite
Humedad
Excelente
Buena
Buena
Excelente
Rigidez dielctrica
Rigidez dielctrica
Constante aislamiento
Constante dielctrica 50 Hz
Factor de prdidas 50 Hz
kV/espesor
kV/mm
M/km
tg
7
45
900
3.50
0.550
Color
REFERENCIA A NORMA
ASTMD-119-67 / ASTMD-1373-67 / ASTMD-100-70a / VDE 0340-1/8,70 / VDE 0303-3/3,67 Y 6/3,68
174
media tensin
accesorios
Cinta BUPRYS
DESCRIPCIN
CINTA SEMICONDUCTORA AUTOVULCANIZABLE PARA RECONSTRUCCIN DE LA PANTALLA
SEMICONDUCTORA
CARACTERSTICAS
- Autovulcanizable.
- Semiconductora.
- Excelente resistencia al ozono.
- Excelente resistencia a la humedad.
- Adaptable a cualquier tipo de superficies.
APLICACIN
Se emplea para la reconstitucin de la pantalla semiconductora en los empalmes y terminales para cable con aislamiento seco de campo
radial y empalmes mixtos entre cables con aislamiento de papel impregnado y aislamiento seco de campo radial.
ESPECIFICACIONES TCNICAS
Caractersticas
Unidad
Valor
Color
Condicin
Espesor
Longitud
Ancho
Adherencia
Alargamiento
Temperatura trabajo
Carga rotura
FSICAS
mm
m.
mm
g/cm
%
C
kg/cm2
Negro
Autovulcanizable
0,5
4,5
19
180
-10 a 100
10,5
Resistencia:
Ozono
cidos y alcals
Aceite
Humedad
Excelente
Buena
Poca
Excelente
Rigidez dielctrica
Rigidez dielctrica
Constante aislamiento
Constante dielctrica 50 Hz
Factor de prdidas 50 Hz
kV/espesor
kV/mm
M/km
tg
Semiconductora
-
Roja
Rojo
REFERENCIA A NORMA
ASTMD-119-67 / ASTMD-1373-67 / ASTMD-1000-70a / VDE 0340-1 / 8,70 / VDE 0303-3 / 3,67 Y 6 / 3,68 / UNE 21356 pl y pll
175
media tensin
accesorios
Cinta PBA-1
DESCRIPCIN
CINTA AISLANTE AUTOVULCANIZABLE PARA LA RECONTRUCCIN DEL AISLAMIENTO
EN EMPALMES Y TERMINALES
CARACTERSTICAS
- Resistente a las descargas parciales y ozono.
- Autovulcanizable.
- Excelente resistencia a la humedad.
- Elevada rigidez dielctrica.
- Excelente en aplicaciones a baja temperatura (-40 C).
- Adaptable a cualquier tipo de superficies.
APLICACIN
Se emplea para la reconstitucin del aislamiento de los empalmes en cables con aislamiento seco y empalmes mixtos entre cables con aislamiento
de papel impregnado y cables con aislamiento seco a campo radial hasta una tensin mxima de 66 kV.
Tambin es utilizada para la confeccin de los deflectores de campo en los terminales a partir de 30 kV y terminaciones hasta 25 kV para los cables
con aislamiento seco.
ESPECIFICACIONES TCNICAS
Caractersticas
Color
Condicin
Espesor
Longitud
Ancho
Adherencia
Alargamiento
Temperatura trabajo
Carga rotura
Fusin
Exposicin al calor a 110C
Resistencia a la tracccin
Remocin de liner
Resistencia:
Ozono
cidos y alcals
Aceite
Humedad
Unidad
FSICAS
mm
m
mm
g/cm
%
C
kg/cm2
mm
MPa
Valor
Negro
Autovulcanizable
0,76
6
25
1.700
-48 a 80
12,5
0,2
Cumple
3,80
OK
Excelente
Buena
Poca
Excelente
Rigidez dielctrica
Rigidez dielctrica
Constante aislamiento
Constante dielctrica 50 Hz
Factor de prdidas 50 Hz
kV/espesor
kV/mm
M/km
tg
48
48
>72.000
2.30
0.00035
Roja
Rojo
176
media tensin
accesorios
APLICACIN
Esta herramienta ejecuta un chafln de entrada para permitir una mejor penetracin de los empalmes
unipolares pre-fabricados en los aislantes de los cables de media tensin.
CAPACIDAD
Dimetro sobre el semi-conductor
mm.
Seccin mm2
12/20 kV
Referencia
19 a 38
25 a 240
CH
177
media tensin
accesorios
APLICACIN
Estas pinzas permiten pelar las cubiertas de PVC, PRC, VEMEX, caucho y hojas finas de cobre y aluminio.
CAPACIDAD
Exterior del cable
(mm.)
Seccin mm2
12/20 kV
Referencia
5 a 17
8 a 23
20 a 35
26 a 52
45 a 75
55 a 95
25 a 240
50 a 630
-
PG 0
PG 1
PG 2
PG 3
PG 4
PG 5
MODO DE EMPLEO
1. Colocar la pinza en el final del corte longitudinal.
2. Apretar la pinza sobre el cable hasta la penetracin de los cuchillos.
3. Girar la pinza 1/4 de vuelta hacia delante y hacia atrs.
Con la ayuda de los cuchillos, situados en la extremidad de la pinza, separar la cubierta del cable.
(*) Los cuchillos de las pinzas son intercambiables y elegidos en funcin del espesor de la cubierta.
178
media tensin
accesorios
APLICACIN
Esta herramienta quita el aislante de los cables unipolares de alta y media tensin y los tripolares de baja
tensin, sin riesgo de daar el conductor.
CAPACIDAD
Dimetro sobre el aislante
mm.
Seccin mm2
12/20 kV
Referencia
14 a 38
38 a 60
55 a 80
80 a 110
80 a 130
25 a 240
300 a 800
(*)
(*)
(*)
LH 1
LH 2
LH 3
LH 4
LH 5
179
media tensin
accesorios
APLICACIN
Estas pinzas cortan la capa semiconductora externa en la longitud deseada permitiendo separarla del aislamiento sin daarla.
CAPACIDAD
Dimetro sobre el semi-conductor
mm.
Seccin mm2
12/20 kV
Referencia
18 a 38
38 a 60
25 a 240
240 a 630
LHM-P 1
LHM-P 2
180
media tensin
accesorios
APLICACIN
Permite un corte regular y helicoidal de la cubierta exterior del cable y un corte de mismas caractersticas en la capa semiconductora y aislamiento.
CAPACIDAD
Dimetro exterior del cable
mm.
Seccin mm2
12/20 kV
Referencia
16 a 40
16 a 58
25 a 240
25 a 630
MF3/40E
MF3/60E
MODO DE EMPLEO
Realizacin de un corte helicoidal de la cubierta del cable.
181
media tensin
accesorios
ABRAZADERAS METLICAS
- Abrazadera metlica para la unin de los sectores abiertos de la cubierta
- Se aprieta mediante til adaptado, garantizando un apriete ptimo
Nota: Ver proceso de conexionando y utilizacin de estas herramientas en pginas 184 y 185.
182
media tensin
accesorios
DESCRIPCIN
Las herramientas incluidas en el maletn multifuncional AL-MT permiten extraer
la cubierta, semiconductora externa pelable en fro, aislamiento y la realizacin de
los cortes sobre la cubierta. Diseadas especficamente para su aplicacin en cables
con pantalla de aluminio.
Modelo maletn
Capacidad
(mm)
Secciones
(mm2)
Peso
(kg)
Multifuncin AL-MT1
Multifuncin AL-MT2
16-40
16-58
25-240
50-630
3,840
4,150
ESPECIFICACIONES
11
2
10
4
7
Referencia
1
2
3
4
5
6
7
8
9
10
11
desglose material
Funcin
extraccin de cubierta
incisin semiconductora pelable
extraccin aislamiento
realizacin de cortes en cubierta
cierre de la cubierta
elevacin cubierta
fijador
cuchilla repuesto para MF3/40 - MF3/60
cuchilla repuesto fentecran 40 y 60
tope regulable
stylet regulable MF3/40 y MF3/60
empuadura para MF3/40 - MF3/60
accesorio cierre cubierta fentecran
maletn plstico
MF3/40
MF3/60
FENTECRAN/40
FENTECRAN/60
EV/NPT
LIGAREX
LMF2
LFE
BR
SR
PCR
GFE
CPM-1MA
Advertencia: las herramientas tienen que ser utlizadas en cables sin tensin por personal cualificado.
183
CPM-2MA
media tensin
accesorios
PROCEDIMIENTO
1 . CORTAR LA CUBIERTA DEL CABLE SEGN
INSTRUCCIONES DE LOS ACCESORIOS
Una vez que sabemos la longitud de la
cubierta a retirar, se procede a su
extraccin con el procedimiento habitual.
Longitud extraccin cubierta
Ajustar la herramienta
al corte de cubierta
Pinza
contra-cubiertas
Cortes de cubierta
184
media tensin
accesorios
5 . INTRODUCIR EL PUENTE-PANTALLA
CON RELIEVE
Abrazaderas metlicas
Cinta PVC
185
media tensin
accesorios
Limpia sin dejar ningn residuo para evitar prdidas a la tierra y puntos calientes.
Homologado para alta tensin hasta 440 kV.
La perfecta adhesin de las resinas en los empalmes previene la penetracin de la humedad.
La reduccin de los defectos de instalacin asegura una duracin mxima de los cables.
Diseado segn las recomendaciones de la IEEE.
No inflamable. Se eliminan los riesgos vinculados con los disolventes lquidos inflamables.
Reduce las emisiones de COV a la atmsfera.
Reduce los riesgos para la salud y la seguridad.
Elimina el riesgo de derrame de lquido y riesgos relacionados.
Elimina la logstica, transporte y almacenaje de las mercancas peligrosas.
HIGIENE Y SEGURIDAD
Se han diseado para su fcil manejo y altas prestaciones en limpieza, adems de sustituir a los disolventes tradicionales tales como el tricloroetano,
alcohol isoproplico y dems disolventes inflamables. Siendo clasificado combustible, se eliminan los riesgos de fuego explosivo y no est sometido
a la logstica de los productos inflamables. El envasado de toallitas pre-impregnadas de disolventes elimina el riesgo de contaminacin por derrame
y dems riesgos relacionados con el manipulado de lquidos.
Respeta el medioambiente, no daa la capa de ozono, no contiene contaminantes peligrosos para la atmsfera o los operadores. No contiene ningn
componente de disolvente halogenado ni ingrediente cancergeno, teratgeno o mutgeno. No est clasificado como mercanca peligrosa. Como
medida de precaucin, se recomienda llevar los EPI. Se recomiendan las gafas de seguridad en caso de riesgo de proyeccin a los ojos. Una
exposicin prolongada puede secar la piel, por tanto llevar guantes.
COMPATIBILIDAD
Disolvente sometido a numerosas pruebas de compatibilidad con la mayora de los materiales encontrados en las redes elctricas, especialmente
las cubiertas de cables, aislantes, metales, composites, resinas, barnizados, esmaltes y cermicas.
INSTRUCCIONES
La baja tensin superficial de nuestro disolvente asegura un excelente mojado incluso sobre los plsticos ms difciles.
1.- Aplicar una fina capa de lquido con la botella o bien mediante una toallita preimpregnada.
2.- Dejar un momento en remojo, hasta 2 minutos en manchas difciles.
3.- Limpiar con la misma toallita pre-impregnada, o bien con un trapo limpio y seco que no suelta fibras.
No es preciso esperar la evaporacin completa del disolvente antes de reanudar el trabajo en el sistema elctrico.
186
media tensin
accesorios
CDIGOS DE PRODUCTO
Descripcin
Envasado
botella 1 litro
spray 1 litro
paquete 24 toallitas
Nota: Para cualquier duda o consulta contactar con nuestra red comercial.
187
media tensin
accesorios
LUBRICANTES LUTEC
CARACTERSTICAS
Todos los productos lubricantes Prysmian comparten los mismos ingredientes y las mismas caractersticas principales. Tienen una consistencia
pegajosa y viscosa, asegurando una perfecta adherencia al cable y a los tubos, as como una gran reduccin de la friccin.
Se pueden aclarar los residuos en la obra sin ningn riesgo de contaminacin. Sin embargo, no se quita fcilmente del cable, asegurando una
lubricacin ptima incluso en tuberas llenas de agua. Adems se seca despacio, dejando una fina capa, menos de 6% del peso tras evaporacin
completa a temperatura ambiente. No inflamable, conserva sus propiedades lubricantes durante meses.
HIGIENE Y SEGURIDAD
Estos lubricantes estn compuestos con base de agua, no txico y biodegradable. Olor agradable. No irrita la piel. No es preciso llevar los EPI.
No causa contaminacin medioambiental, por que no es preciso recoger sus derramas, slo basta con aclararlos con agua.
COMPATIBILIDAD
No contienen parafina, silicona, detergente, sal que puedan daar las cubiertas de cables y causar puntos calientes. Estos lubricantes se sometieron
a varias pruebas de compatibilidad con los materiales de cubierta, de accesorios de cables elctricos y de tubos: poliolefinas, polietileno alta
densidad, polietileno lineal baja densidad, caucho natural, polietileno clorurado, etileno propileno, polietileno de enlace cruzado, PVC, neopreno,
polipropileno, silicona, etc.
INSTRUCCIONES
Nuestros productos son de uso cmodo segn varios mtodos:
Aplicar con la mano o verter desde el cubo encima del cable.
Tambin se puede utilizar una bomba, bien sea manual o elctrica, un embudo o un aplicador.
Puede emplearse para pre-lubicar los tubos con los sacos de pre-lubricacin o introduciendo lubricante delante de la esponja..
188
media tensin
accesorios
LUBRICANTES LUTEC
APLICACIONES
Lubricantes para el tendido subterrneo de cables elctricos y de telecomunicaciones.
Prelubricacin de los tubos para reducir los riesgos en los tendidos difciles.
Contiene un sistema de consistencia pegajosa y viscosa que facilita la perfecta adherencia al cable incluso en tuberas llenas de agua (el lubricante
no se disuelve al entrar en contacto con el agua).
Compatible con todo tipo de cables y accesorios.
Conserva su poder de lubricacin durante meses, facilitando la instalacin posterior de cables en la misma tubera.
Producto no inflamable.
Biodegradable.
No txico para los operadores ni el medioambiente.
Gama completa de lubricantes para cubrir cualquier tipo de tendido.
CDIGOS DE PRODUCTO
Lubricante
LUTEC P1
Viscosidad
cSt
Descripcin
5400-7400
LUTEC P2
4500-6400
LUTEC P3
1800-3500
LUTEC F01
1800-3500
Descripcin
Envasado
Cubo 20 litros
Bolsa 2 kg
Cubo 20 litros
Cubo 20 litros
Botella 1 litro
Nota: Para cualquier duda o consulta contactar con nuestra red comercial.
189
190
ANEXO A:
CONDUCTORES DESNUDOS,
CONDUCTORES RECUBIERTOS
Y CABLES UNIPOLARES AISLADOS
REUNIDOS EN HAZ
191
media tensin
anexo a
CARACTERSTICAS TCNICAS
47-AL1/8-ST1A
Cdigo
LA-56
Cdigo antiguo
94-AL1/22-ST1A
LA-110
Norma
LA-180
LA-280
HAWK
LA-380
GULL
LA-455
CONDOR
7x2,82 +
54x2,82
2,82
8,46
2,82
25,38
43,7
337,3
381
342
933
1275
109
0,0857
7x3,08 +
54x3,08
3,08
9,24
3,08
27,72
52,2
402,3
454,6
408,9
1112
1521
124
0,0718
UNE EN 50182
mm
mm
mm
mm
mm2
mm2
mm2
kg/km
kg/km
kg/km
kN
/km
1x3,15 +
6x3,15
3,15
3,15
3,15
9,45
7,8
46,8
54,6
60,8
128,3
189,1
16,4
0,6136
7x2,00 +
30x2,0
2
6
2
14
22
94,2
116,2
172,4
260,2
433
43,1
0,3066
7x2,5 +
30x2,5
2,5
7,5
2,5
17,5
34,3
147,3
181,6
269,4
407
676
63,9
0,1962
Hilos de acero
Hilos de aluminio
LA 56
(1x3,15 + 6x3,15)
LA 180
(7x2,5 + 30x2,5)
Valores aproximados.
Para otras secciones, consultar.
192
7x2,68 +
26x3,44
2,68
8,04
3,44
21,8
39,5
241,7
281,2
310
666,7
977
84,5
0,1194
media tensin
anexo a
DESCRIPCIN
Norma:
Tipos:
UNE-EN 50397-1
CCX 47-AL1/8-ST1A 20 kV, CCX 47-AL1/8-ST1A 30 kV
CCX 94-AL1/22-ST1A 20 kV, CCX 94-AL1/22-ST1A 30 kV
Conductor:
Cuerda de alambres de aluminio AL1 y alma de alambres de acero galvanizado ST1A. UNE-EN 50182.
Posibilidad de conductor taponado longitudinalmente al agua.
Cubierta aislante:
Polietileno reticulado, XLPE, color negro.
CARACTERSTICAS TCNICAS
CCX 47-AL1/8-ST1A
20 kV
Seccin, mm2
30 kV
CCX 94-AL1/22-ST1A
20 kV
54,6
7
0,6129
81000
1,9210-5
9,45
Nmero de alambres
Resistencia elctrica 20 C /km
Mdulo de elasticidad, N/mm2
Coeficiente de dilatacin, 1/K
Dimetro del conductor, mm
Espesor cubierta XLPE, mm
Dimetro cable, mm
Peso cable, kg/km
Intensidad de servicio, A
Intensidad de ctocto en 1 s, kA
2,3
14,1
274
Valores aproximados.
Otras secciones, consultar.
193
116,2
37
0,3067
77000
1,8910-5
14
3,3
14,8
321
180
4,5
30 kV
2,3
18,6
551
3,3
20,6
612
315
9
media tensin
anexo a
DESCRIPCIN
Norma:
Tipos:
UNE-EN 50397-1
CCX 55-AL2 20 kV, CCX 55-AL2 30 kV
CCX 117-AL2 20 kV, CCX 117-AL2 30 kV
Conductor:
Cuerda de alambres de aleacin de aluminio AL2. UNE-EN 50182.
Posibilidad de conductor taponado longitudinalmente al agua.
Cubierta aislante:
Polietileno reticulado, XLPE, color negro.
CARACTERSTICAS TCNICAS
CCX 55-AL2
20 kV
Seccin, mm2
Nmero de alambres
Resistencia elctrica 20 C /km
Resistencia a la traccin, kN
Mdulo de elasticidad, N/mm2
Coeficiente de dilatacin, 1/K
Dimetro del conductor, mm
Espesor cubierta XLPE, mm
Dimetro cable, mm
Peso cable, kg/km
Intensidad de servicio, A
Intensidad de ctocto en 1 s, kA
CCX 117-AL2
30 kV
20 kV
54,6
7
0,6087
17,73
60000
2,310-5
9,45
2,3
14,1
234
Valores aproximados.
Otras secciones, consultar.
194
117
19
0,2854
38,02
57000
2,310-5
14
3,3
14,8
281
191
4,5
30 kV
2,3
18,6
439
3,3
20,6
501
360
9,3
media tensin
anexo a
AL EPRORRET HACES
Tipo:
Norma:
DHVS
RU 3309, IEC 60502-2
Composicin:
Fiador
1 Cuerda: Acero galvanizado de seccin 50 mm2.
2
nom. (mm)
9,0
11,4
Fases
3 Conductor: Cuerda redonda compacta de hilos de aluminio clase 2, conforme a norma IEC 60228.
4
Cubierta exterior: Doble capa de PVC resistente a la intemperie (rayos UVA, radiacin solar, humedad...)
Color: Negro.
6400
15000
1110-6
195
media tensin
anexo a
18/30 kV
exterior
envolvente
(mm)
Peso
(kg/km)
Seccin
(mm2)
exterior
envolvente
(mm)
Peso
(kg/km)
69,2
71,9
78,1
85,2
3340
3600
4300
5210
3x(1x35/16)+50
3x(1x50/16)+50
3x(1x95/16)+50
3x(1x150/16)+50
79,7
81,9
89,4
95,2
4150
4440
5400
6230
Valores aproximados.
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
Intensidad mxima de cortocircuito en la pantalla durante 1 seg (kA)
Formacin
(mm2)
3(1x35/16)+50
3(1x50/16)+50
3(1x95/16)+50
3(1x150/16)+50
Intensidad admisible
Intensidad de
(temperatura
cortocircuito en el
ambiente 40 C)*
conductor durante 1 s
(A)
(A)
12/20 kV y 18/30 kV
120
150
235
305
12/20 kV y 18/30 kV
3290
4700
8930
14100
Resistencia del
conductor a 20 C
(/km)
12/20 kV y 18/30 kV
0,868
0,641
0,32
0,206
196
12/20 kV
18/30 kV
12
20
24
125
18
30
36
170
90
250
2,9
Reactancia inductiva
(/km)
12/20 kV
0,158
0,151
0,135
0,125
18/30 kV
0,142
0,133
0,120
0,111
Capacidad
(F/km)
12/20 kV
0,187
0,203
0,251
0,293
18/30 kV
0,135
0,149
0,180
0,209
media tensin
anexo a
AL VOLTARRET HACES
Tipo:
Norma:
RHVS
RU 3309, IEC 60502-2
Composicin:
Fiador
1 Cuerda: Acero galvanizado de seccin 50 mm2.
2
nom. (mm)
9,0
11,4
Fases
3 Conductor: Cuerda redonda compacta de hilos de aluminio clase 2, conforme a norma IEC 60228.
4
Cubierta exterior: Doble capa de PVC resistente a la intemperie (rayos UVA, radiacin solar, humedad...)
Color: Negro.
6400
15000
1110-6
197
media tensin
anexo a
18/30 kV
exterior
envolvente
(mm)
Peso
(kg/km)
Seccin
(mm2)
exterior
envolvente
(mm)
Peso
(kg/km)
69,2
71,9
78,1
85,2
3220
3470
4140
5030
3x(1x35/16)+50
3x(1x50/16)+50
3x(1x95/16)+50
3x(1x150/16)+50
79,7
81,9
89,4
95,2
3950
4230
5145
5940
Valores aproximados.
CARACTERSTICAS ELCTRICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
Intensidad mxima de cortocircuito en la pantalla durante 1 seg (kA)
Formacin
(mm2)
3(1x35/16)+50
3(1x50/16)+50
3(1x95/16)+50
3(1x150/16)+50
Intensidad admisible
Intensidad de
(temperatura
cortocircuito en el
ambiente 40 C)*
conductor durante 1 s
(A)
(A)
12/20 kV y 18/30 kV
135
160
245
320
12/20 kV y 18/30 kV
3290
4700
8930
14100
Resistencia del
conductor a 20 C
(/km)
12/20 kV y 18/30 kV
0,868
0,641
0,32
0,206
198
12/20 kV
18/30 kV
12
20
24
125
18
30
36
170
90
250
2,9
Reactancia inductiva
(/km)
12/20 kV
0,158
0,151
0,135
0,125
18/30 kV
0,142
0,133
0,120
0,111
Capacidad
(F/km)
12/20 kV
0,161
0,177
0,217
0,254
18/30 kV
0,125
0,138
0,167
0,193
ANEXO B:
CABLES Y ACCESORIOS
HABITUALES
PARA 26/45 kV Y 36/66 kV
199
media tensin
anexo b
Tipo:
DHZ1, HEPRZ1 (con conductor de cobre), AL DHZ1, AL HEPRZ1 (con conductor de aluminio)
Tensin nominal: 26/45 kV, 36/66 kV
Norma:
UNE HD 632-6A
Composicin:
1
2
Aislamiento: etileno-propileno (EPR) para cables DHZ1 o etileno-propileno de alto gradiente (HEPR)
para cables HEPRZ1.
CARACTERSTICAS TCNICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
200
26/45 kV
36/66 kV
26
45
52
250
90
250
36
66
72,5
325
90
250
media tensin
anexo b
Tipo:
RHZ1 (con conductor de cobre); AL RHZ1 (con conductor de aluminio)
Tensin nominal: 26/45 kV, 36/66 kV
Norma:
UNE HD 632-3A
Composicin:
1
2
CARACTERSTICAS TCNICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
201
26/45 kV
36/66 kV
26
45
52
250
90
250
36
66
72,5
325
90
250
media tensin
anexo b
26/45 kV
1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/16
1x185/16
1x240/16
1x300/16
1x400/16
1x500/16
1x630/16
1x800/16
1x1000/16
Cdigo
conductor
(mm)
6,8
8
9,8
11,2
12,6
14
15,6
18
20,3
22,9
26,3
30,2
34
38,4
20117961
20117962
20117963
20070279
20117964
37011355
20117965
20993429
20994805
20117966
20117967
20117968
20117969
20117970
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
24,7
25,8
27,8
29,1
30,4
30,8
32,3
34,7
37,6
39
42,4
46,3
50,1
53,5
28,1
29,2
31,2
32,5
33,8
34,2
35,7
38,1
41
42,4
45,8
49,7
53,5
56,9
34,2
35,3
37,3
38,6
39,9
40,3
41,9
44,2
47,1
48,5
51,9
55,8
59,6
63,7
1090
1170
1320
1420
1540
1610
1770
2020
2320
2550
3000
3500
4150
4910
547
565
597
618
638
645
670
707
754
776
830
893
954
1019
Radio de
curvatura
dinmico
(durante tendido)
(mm)
684
706
746
772
798
806
838
884
942
970
1038
1116
1192
1274
CARACTERSTICAS ELCTRICAS
26/45 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
26
45
52
250
90
250
(Valores aproximados)
1 x seccin conductor Intensidad mxima
(Al)/seccin pantalla admisible enterrado*
(Cu) (mm2)
(A)
26/45 kV
1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/16
1x185/16
1x240/16
1x300/16
1x400/16
1x500/16
1x630/16
1x800/16
1x1000/16
132
157
193
226
262
295
334
389
440
505
579
663
749
836
Intensidad mxima
admisible
al aire** (A)
Resistencia del
conductor a 20 C
(/km)
Reactancia inductiva
(/km)
Capacidad
(F/km)
134
160
201
236
280
318
365
432
498
582
681
798
920
1052
0,868
0,641
0,443
0,32
0,253
0,206
0,164
0,125
0,1
0,0778
0,0605
0,0469
0,0367
0,0291
0,161
0,153
0,143
0,137
0,132
0,126
0,121
0,116
0,112
0,106
0,102
0,098
0,094
0,091
0,133
0,143
0,162
0,174
0,186
0,208
0,223
0,246
0,273
0,343
0,379
0,422
0,463
0,547
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la
frmula de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
202
media tensin
anexo b
26/45 kV
1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/16
1x185/16
1x240/16
1x300/16
1x400/16
1x500/16
1x630/16
1x800/16
1x1000/16
Cdigo
20117861
20117862
20117863
37011335
20052424
20992340
20013787
20084553
20001742
20117864
37011342
20106569
20117865
20117866
conductor
(mm)
7
8
9,7
11,4
12,6
14,1
15,9
18,3
20,5
23,1
26,3
29,6
34,1
38,7
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
24,9
25,8
27,6
29,2
30,5
30,9
32,7
35,1
37,8
38,9
42
45,4
49,9
53,5
26,9
29,2
31
32,6
33,9
34,3
36,1
38,5
41,2
42,3
45,4
48,8
53,3
56,9
34,4
35,4
37,2
38,7
40
40,4
42,2
44,6
47,3
48,4
51,5
54,9
60
63,6
1320
1460
1720
2010
2290
2520
2910
3500
4180
4910
6020
7410
9490
11550
550
566
595
619
640
646
675
714
757
774
824
878
960
1018
Radio de
curvatura
dinmico
(durante tendido)
(mm)
688
708
744
774
800
808
844
892
946
968
1030
1098
1200
1272
CARACTERSTICAS ELCTRICAS
26/45 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
26
45
52
250
90
250
(Valores aproximados)
1 x seccin conductor Intensidad mxima
(Cu)/seccin pantalla admisible enterrado*
(Cu) (mm2)
(A)
26/45 kV
1x35/16
1x50/16
1x70/16
1x95/16
1x120/16
1x150/16
1x185/16
1x240/16
1x300/16
1x400/16
1x500/16
1x630/16
1x800/16
1x1000/16
171
202
248
297
338
381
431
501
565
644
731
824
921
1007
Intensidad mxima
admisible
al aire** (A)
Resistencia del
conductor a 20 C
(/km)
Reactancia inductiva
(/km)
Capacidad
(F/km)
174
207
258
314
361
411
472
558
640
743
860
984
1132
1269
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
0,0601
0,047
0,0366
0,0283
0,0221
0,0176
0,159
0,152
0,144
0,136
0,132
0,125
0,121
0,115
0,112
0,106
0,102
0,098
0,095
0,090
0,135
0,144
0,161
0,175
0,186
0,209
0,226
0,249
0,275
0,341
0,375
0,411
0,460
0,546
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
203
media tensin
anexo b
36/66 kV
1x35/25
1x50/25
1x70/25
1x95/25
1x120/25
1x150/25
1x185/25
1x240/25
1x300/25
1x400/25
1x500/25
1x630/25
1x800/25
1x1000/25
Cdigo
conductor
(mm)
6,8
8
9,8
11,2
12,6
14
15,6
18
20,3
22,9
26,3
30,2
34
38,4
20117867
20117868
20117869
20104573
20094047
20000781
20980166
37019644
20001498
20000768
20997040
20990024
20000769
20117870
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
34,7
35,8
37,8
39,1
39,4
39,8
40,3
40,7
42,6
46
48,4
52,3
55,1
59,5
39,2
40,4
42,3
43,6
44
44,3
44,9
45,3
46,6
49,8
52,2
56,1
58,9
63,3
45,4
46,5
48,5
49,8
50,1
50,5
51
51,4
52,7
55,9
58,3
62,2
65
70
1900
2000
2180
2310
2380
2460
2560
2690
2940
3330
3730
4280
4930
5830
726
744
776
797
802
808
816
822
843
894
933
995
1040
1120
Radio de
curvatura
dinmico
(durante tendido)
(mm)
908
930
970
996
1002
1010
1020
1028
1054
1118
1166
1244
1300
1400
CARACTERSTICAS ELCTRICAS
36/66 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
36
66
72,5
325
90
250
(Valores aproximados)
1 x seccin conductor Intensidad mxima
(Al)/seccin pantalla admisible enterrado*
(Cu) (mm2)
(A)
36/66 kV
1x35/25
1x50/25
1x70/25
1x95/25
1x120/25
1x150/25
1x185/25
1x240/25
1x300/25
1x400/25
1x500/25
1x630/25
1x800/25
1x1000/25
130
154
190
227
259
291
330
385
437
501
575
659
746
835
Intensidad mxima
admisible
al aire** (A)
Resistencia del
conductor a 20 C
(/km)
Reactancia inductiva
(/km)
Capacidad
(F/km)
134
160
200
241
278
316
363
430
494
575
673
788
911
1040
0,868
0,641
0,443
0,32
0,253
0,206
0,164
0,125
0,1
0,0778
0,0605
0,0469
0,0367
0,0291
0,179
0,170
0,159
0,153
0,146
0,140
0,134
0,125
0,119
0,115
0,109
0,105
0,100
0,097
0,100
0,107
0,117
0,127
0,138
0,150
0,164
0,192
0,219
0,244
0,278
0,308
0,351
0,386
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
204
media tensin
anexo b
36/66 kV
1x50/25
1x70/25
1x95/25
1x120/25
1x150/25
1x185/25
1x240/25
1x300/25
1x400/25
1x500/25
1x630/25
1x800/25
1x1000/25
Cdigo
20117872
20117873
20117874
20117875
20994808
20980450
20098532
20001496
20001052
20117876
20000500
20117877
20117878
conductor
(mm)
8
9,7
11,4
12,6
14,1
15,9
18,3
20,5
23,1
26,3
29,6
34,1
38,7
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
35,8
37,6
39,2
39,5
39,9
40,7
41,1
42,8
45,9
48
51,4
54,9
59,5
40,4
42,2
43,8
44
44,4
45,2
45,6
46,8
49,7
51,8
55,2
58,7
63,3
46,5
48,3
49,9
50,1
50,6
51,3
51,7
52,9
55,8
57,9
61,3
65,3
69,9
2290
2580
2900
3130
3360
3700
4180
4800
5680
6740
8170
10260
12460
744
773
798
802
810
821
827
846
893
926
981
1045
1118
Radio de
curvatura
dinmico
(durante tendido)
(mm)
930
966
998
1002
1012
1026
1034
1058
1116
1158
1226
1306
1398
CARACTERSTICAS ELCTRICAS
36/66 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
36
66
72,5
325
90
250
(Valores aproximados)
1 x seccin conductor Intensidad mxima
(Cu)/seccin pantalla admisible enterrado*
(Cu) (mm2)
(A)
36/66 kV
1x50/25
1x70/25
1x95/25
1x120/25
1x150/25
1x185/25
1x240/25
1x300/25
1x400/25
1x500/25
1x630/25
1x800/25
1x1000/25
199
244
293
334
376
426
497
561
639
727
823
920
1010
Intensidad mxima
admisible
al aire** (A)
Resistencia del
conductor a 20 C
(/km)
Reactancia inductiva
(/km)
207
257
312
359
408
468
555
635
735
852
981
1124
1260
0,641
0,443
0,32
0,253
0,206
0,164
0,125
0,1
0,0778
0,0605
0,0469
0,0367
0,0291
0,170
0,160
0,152
0,146
0,139
0,133
0,124
0,119
0,115
0,109
0,105
0,100
0,096
Capacidad
(F/km)
0,107
0,118
0,128
0,138
0,151
0,167
0,194
0,221
0,242
0,276
0,301
0,349
0,385
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
205
media tensin
anexo b
Tipo:
RHZ1 (con conductor de cobre); AL RHZ1 (con conductor de aluminio)
Tensin nominal: 26/45 kV, 36/66 kV
Norma:
UNE HD 632-4A
Composicin:
1
2
Proteccin radial contra el agua: cinta longitudinal de aluminio adherida a la cubierta exterior.
CARACTERSTICAS TCNICAS
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
206
26/45 kV
36/66 kV
26
45
52
250
90
250
36
66
72,5
325
90
250
media tensin
anexo b
AL HEPRZ1
Composicin:
Conductor: Cuerda de hilos de aluminio de seccin circular compactados clase 2K segn IEC 60228.
Cubierta: Poliolefina tipo ST7 no propagadora de la llama de color rojo con dos bandas grises.
26/45 kV
1x300/75
1x500/75
conductor
(mm)
Cdigo
20103515
20103514
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
34,6
41,4
39,3
46,1
45,4
52,2
2900
3700
726
835
20,3
26,3
Radio de
curvatura
dinmico
(durante tendido)
(mm)
908
1044
CARACTERSTICAS ELCTRICAS
26/45 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
26
45
52
250
90
250
(Valores aproximados)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
26/45 kV
1x300/75
1x500/75
Intensidad
mxima
admisible
enterrado* (A)
440
579
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
Resistencia
del conductor
a 20 C
(/km)
Capacidad
(F/km)
498
681
25500 (1,2 s)
65800 (0,5 s)
11700 (1,2 s)
17200 (0,5 s)
0,1
0,0605
0,352
0,438
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
207
media tensin
anexo b
DATOS TCNICOS DEL CABLE AL VOLTALENE H COMPOSITE 2OL 26/45 kV (conductor de aluminio)
NORMALIZADO POR LAS COMPAAS DEL GRUPO ENDESA
AL RHZ1-2OL
Composicin:
6 5 6
Conductor: Cuerda taponada de hilos de aluminio de seccin circular compactados clase 2K segn IEC 60228.
26/45 kV
1x400/50
1x1000/50
conductor
(mm)
Cdigo
20044043
20080046
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
40,7
56,8
45,8
61,9
53,1
70,2
3300
6000
850
1123
22,9
38,4
Radio de
curvatura
dinmico
(durante tendido)
(mm)
1062
1404
CARACTERSTICAS ELCTRICAS
26/45 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
26
45
52
250
90
250
(Valores aproximados)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
26/45 kV
1x400/50
1x1000/50
Intensidad
mxima
admisible
enterrado* (A)
505
836
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
Resistencia
del conductor
a 20 C
(/km)
Capacidad
(F/km)
582
1052
53000 (0,5 s)
133000 (0,5 s)
11900 (0,5 s)
11900 (0,5 s)
0,0778
0,029
0,329
0,491
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
208
media tensin
anexo b
DATOS TCNICOS DEL CABLE AL VOLTALENE H COMPOSITE 2OL 26/45 kV (conductor de aluminio) y VOLTALENE H COMPOSITE
2OL 26/45 kV (conductor de cobre)
NORMALIZADO POR GAS NATURAL FENOSA
AL RHZ1-2OL
Composicin:
6 5 6
Conductor: Cuerda taponada de hilos de aluminio o de cobre de seccin circular compactados clase 2K segn IEC 60228.
8 Cubierta: Poliolefina AFUMEX tipo DMZ2, libre de halgenos, no propagadora de la llama con capa exterior semiconductora extruda
conjuntamente con la cubierta.
CARACTERSTICAS DIMENSIONALES (Valores aproximados)
1 x seccin
conductor/
seccin pantalla
(Cu) (mm2)
26/45 kV
1x630(Al)/165
1x800(Al)/165
1x400(Cu)/165
1x500(Cu)/165
conductor
(mm)
Cdigo
aislamiento
(mm)
pantalla (mm)
cable (mm)
45
49
37,5
40,8
51,6
55,6
44,1
47,5
59,9
63,9
52,4
55,8
30,2
34
23,1
26,3
20118618
20118619
20118616
20118617
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
5300
6000
6600
7700
958
1022
838
893
1198
1278
1048
1116
CARACTERSTICAS ELCTRICAS
26/45 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
26
45
52
250
90
250
(Valores aproximados)
1 x seccin
conductor
seccin
pantalla (Cu)
(mm2)
26/45 kV
1x630(Al)/165
1x800(Al)/165
1x400(Cu)/165
1x500(Cu)/165
Intensidad
mxima
admisible
enterrado* (A)
663
748
644
731
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
Resistencia
del conductor
a 20 C
(/km)
Capacidad
(F/km)
798
920
743
860
82900 (0,5 s)
105200 (0,5 s)
80900 (0,5 s)
101100 (0,5 s)
36900 (0,5 s)
36900 (0,5 s)
36900 (0,5 s)
36900 (0,5 s)
0,0469
0,0367
0,0470
0,0366
0,475
0,514
0,400
0,433
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
209
media tensin
anexo b
AL HEPRZ1
Composicin:
Conductor: Cuerda de hilos de aluminio de seccin circular compactados clase 2K segn IEC 60228.
Cubierta: Mezcla termoplstica a base de poliolefina Z1, tipo DMZ2 no propagadora de la llama de color rojo con dos bandas grises.
36/66 kV
1x300/75
1x500/75
conductor
(mm)
Cdigo
20080274
20080046
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
39,6
46,4
44,9
51,7
51
57,4
3500
4500
816
918
20,3
26,3
Radio de
curvatura
dinmico
(durante tendido)
(mm)
1020
1148
CARACTERSTICAS ELCTRICAS
36/66 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
36
66
72,5
325
90
250
(Valores aproximados)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
36/66 kV
1x300/75
1x500/75
Intensidad
mxima
admisible
enterrado* (A)
440
579
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
Resistencia
del conductor
a 20 C
(/km)
Capacidad
(F/km)
498
681
27900 (1 s)
65800 (0,5 s)
12800 (1 s)
17200 (0,5 s)
0,1
0,0605
0,268
0,328
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
210
media tensin
anexo b
DATOS TCNICOS DEL CABLE AL VOLTALENE H COMPOSITE 2OL 36/66 kV (conductor de aluminio)
NORMALIZADO POR LAS COMPAAS DEL GRUPO ENDESA
AL RHZ1-2OL
Composicin:
6 5 6
2 1
Conductor: Cuerda taponada de hilos de aluminio de seccin circular compactados clase 2K segn IEC 60228.
36/66 kV
1x630/95
1x1000/95
conductor
(mm)
Cdigo
20044044
20044054
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
52
60,8
58,5
67,3
65,7
75,5
5300
7000
1051
1208
30,2
38,4
Radio de
curvatura
dinmico
(durante tendido)
(mm)
1314
1510
CARACTERSTICAS ELCTRICAS
36/66 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
36
66
72,5
325
90
250
(Valores aproximados)
1 x seccin
conductor
(Al)/seccin
pantalla (Cu)
(mm2)
36/66 kV
1x630/95
1x1000/95
Intensidad
mxima
admisible
enterrado* (A)
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
659
835
788
1040
84000 (0,5 s)
133000 (0,5 s)
21700 (0,5 s)
21700 (0,5 s)
Resistencia
del conductor
a 20 C
(/km)
0,0469
0,0291
Capacidad
(F/km)
0,327
0,395
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
211
media tensin
anexo b
DATOS TCNICOS DEL CABLE AL VOLTALENE H COMPOSITE 2OL 26/45 kV (conductor de aluminio) y VOLTALENE H COMPOSITE
2OL 26/45 kV (conductor de cobre)
NORMALIZADO POR GAS NATURAL FENOSA
AL RHZ1-2OL
Composicin:
6 5 6
2 1
Conductor: Cuerda taponada de hilos de aluminio o de cobre Ade seccin circular compactados clase 2K segn IEC 60228.
8 Cubierta: Poliolefina AFUMEX tipo DMZ2, libre de halgenos, no propagadora de la llama con capa exterior semiconductora extruda
conjuntamente con la cubierta.
CARACTERSTICAS DIMENSIONALES (Valores aproximados)
1 x seccin
conductor/
seccin pantalla
(Cu) (mm2)
36/66 kV
1x630(Al)/75
1x1200(Al)/75
1x800(Cu)/75
conductor
(mm)
Cdigo
20118620
20118622
20118621
aislamiento
(mm)
pantalla (mm)
cable (mm)
48,8
60
52,9
55,4
67,2
60,1
63,7
75,9
68,4
30,2
41
34,1
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
Radio de
curvatura
dinmico
(durante tendido)
(mm)
5600
8000
11700
1019
1214
1094
1274
1518
1368
CARACTERSTICAS ELCTRICAS
36/66 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
36
66
72,5
325
90
250
(Valores aproximados)
1 x seccin
conductor/
seccin
pantalla(Cu)
(mm2)
36/66 kV
1x630(Al)/75
1x1200(Al)/75
1x800(Cu)/75
Intensidad
mxima
admisible
enterrado* (A)
663
920
921
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
Resistencia
del conductor
a 20 C
(/km)
Capacidad
(F/km)
798
1215
1132
82900 (0,5 s)
157800 (0,5 s)
161800 (0,5 s)
36900 (0,5 s)
36900 (0,5 s)
36900 (0,5 s)
0,0469
0,025
0,022
0,372
0,461
0,403
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
212
media tensin
anexo b
DATOS TCNICOS DEL CABLE AL VOLTALENE H COMPOSITE 2OL 36/66 kV (conductor de aluminio)
NORMALIZADO POR RED ELCTRICA DE ESPAA
AL RHZ1-2OL
Composicin:
6 5 6
2 1
Conductor: Cuerda taponada de hilos de aluminio de seccin circular compactados clase 2K segn IEC 60228.
Cubierta: polietileno de alta densidad tipo DMZ2 con capa exterior semiconductora. Color negro.
36/66 kV
1x1200/200
conductor
(mm)
Cdigo
20111383
aislamiento
(mm)
pantalla (mm)
cable (mm)
Peso (kg/km)
Radio de
curvatura
esttico
(posicin final)
(mm)
63,4
71,6
83,2
9100
1331
41
Radio de
curvatura
dinmico
(durante tendido)
(mm)
1664
CARACTERSTICAS ELCTRICAS
36/66 kV
Tensin nominal simple, Uo (kV)
Tensin nominal entre fases, U (kV)
Tensin mxima entre fases, Um (kV)
Tensin a impulsos, Up (kV)
Temperatura mxima admisible en el conductor en servicio permanente (C)
Temperatura mxima admisible en el conductor en rgimen de cortocircuito (C)
36
66
72,5
325
90
250
(Valores aproximados)
1 x seccin
conductor (Al)/
seccin
pantalla (Cu)
(mm2)
36/66 kV
1x1200/200
Intensidad
mxima
admisible
enterrado* (A)
920
Intensidad
mxima
admisible
al aire** (A)
Intensidad
mxima de
cortocircuito
trifsica (A)
Intensidad
mxima de
cortocircuito
monofsica (fasepantalla) (A)
Resistencia
del conductor
a 20 C
(/km)
Capacidad
(F/km)
1215
160460 (0,5 s)
40000 (0,5 s)
0,0247
0,420
*Condiciones de instalacin: una terna de cables directamente enterrada o bajo tubo a 1,2 m de profundidad, temperatura de terreno 25 C y resisitividad trmica 1 Km/W.
**Condiciones de instalacin: una terna de cables al aire (a la sombra) a 40 C.
NOTA: valores obtenidos para una terna de cables al tresbolillo y en contacto. Para el clculo de la reactancia inductiva con los conductores en cualquier disposicin aplicar la frmula
de la pgina 214.
IMPORTANTE: Para los valores concretos de intensidades mximas segn los conexionados de pantalla se ruega contactar con Prysmian.
213
media tensin
anexo b
Frmula para clcular la reactancia inductiva con los conductores en cualquier disposicin:
XL = L (/km)
Donde
=2f
f : frecuencia (HZ)
2DMG . -3
) 10 (H/km)
c
DMG: distancia media geomtrica entre conductores (mm)
L = (0,05 + 0,2 ln
DMG = 3 a1a2a3
a3
a1
a2
a1
a2
a3
c: dimetro del conductor* (mm)
* No confundir con el dimetro del cable.
214
media tensin
anexo b
SIXTY-SPEED
DESCRIPCIN
EMPALME UNIVERSAL CONTRCTIL EN FRO, (hasta 36/66 kV)
Ref. norma: IEC-60840.
Nivel mximo de tensin: 36/66 kV.
COMPONENTES
1
Modelo
SIXTY-SPEED-1-00/72.5-T3-P1
SIXTY-SPEED-2-00/72.5-T3-P1
SIXTY-SPEED-3-00/72.5-T3-P1
Conductor
Mn.
13,50
30,80
40,00
Mn.
35,00
46,70
60,00
Mx.
49,00
61,90
64,00
CARACTERSTICAS
EMPALME CONTRCTIL EN FRO
- 100% ensayado elctricamente en fbrica.
- El sistema de instalacin est basado en los conceptos de la media tensin.
- Ligero.
- Se suministra expandido sobre un tubo soporte polimrico para tensiones de 66 kV
- Fcil de instalar, tubo soporte auto-extrable.
- Rapidez de montaje
- Aplicable a todos los tipos de cable, (XLPE y EPR).
- Proteccin final del empalme segn el tipo de instalacin: tubo termorretrctil, tubo contrctil en fro o con
capas de proteccin de polister reforzado.
215
Mn.
36,30
54,30
90,00
Mx.
62,00
80,00
103,00
media tensin
anexo b
SIXTY-SPEED
APLICACIN
Modelos
Sixty Speed-1-00/72,5-T3-P1
Sixty Speed-2-00/72,5-T3-P1
Sixty Speed-3-00/72,5-T3-P1
35,00
46,7
60,0
216
Prysmian Cables y Sistemas se reserva el derecho de modificar el contenido de este catlogo sin previo aviso.
217
218