DOCUMENT NO.
TYPICAL CALCULATION SHEET FOR LIGHTING SYSTEM BELOW 2O MTR HEIGHT OF BUILDING/STRUCTURE
= Fill or Select the yellow colour result will get automatically
Bellari
22
LxWXH
43.5
14
Ac
( L X W ) + 2 ( L X H ) + 2 ( W X H ) +( H2)
609
1044
12
336
10
452.45
0.4
Ac
Ng
1.9
(Ac X Ng ) X 10
2441.45
-6
2441.45 X
0.00464
1.9
-6
1.06 Over all Assesment of Risk & Weighing Factor (Refer Table-1A to 1E from IS : 2309:1989 )
A
0.4
1.3
0.4
1.2
1
AXBXCXDXE
1.2
0.2496
=
=
=
0.4
1.3
X 0.2496
0.00116
0.00
1.09 If Overall risk factor exceeds 0.00001 then Lightning protection is required
Conclusion :-
Overall risk factor is excessed than 0.00001 hence Lightning Protection is Required
12
Doc. No.EL00012,Rev05
(( W + L ) X 2) / 20
((43.5+14) X 2 ) / 20