1.0 CT sizing calculation for 33kV Definite Time Ground O/C Protection (51NS)
1.1 Basic Data:
Ratio
= 900
Accuracy class
= 5P10
Burden ( VA )
= 15
VA
= 0.1
VA
Cable Length ( m )
= 150
= 4
Sqmm
= 5.41
/km
= 1.62
()
Loop Burden ( VA )
= 1.62
VA
= 0.1
VA
Total Burden on CT ( VA )
= 1.72
VA
/ 1 A
HENCE SAFE.
Core II :
1.0 CT sizing calculation for 33kV Restricted Earth Fault Protection (64R)
1.1 Basic Data:
Ratio
900 / 1 A
Primary Voltage ( kV )
33
kV
Secondar Voltage ( kV )
6.6
kV
Accuracy Class
PS
Transformer rating
Impedence of transformer
8.35
= (8 x 100 ) /8.35
=
95.81
MVA
%
MVA
= ( 95.81 x 1000 ) / (3 x 33 )
If
1676.29 A
1 of 18
1.863
DOC NO :
TRANSFORMER SECONDARY SIDE NEUTRAL CT
1.2 Burdens of Relays connected :
Restricted Earth Fault Relay
= 1.00
VA
Cable Length ( m )
= 150
= 4
Sqmm
= 5.41
/km
= 1.6230
= 1.6230
VA
= 2
Loop Burden ( VA )
RL
(2 x Ifs(Rct+2RL)) volt
2 x1.87 x (2+ 2 x 1.623)
Vk
19.55
500