Beruflich Dokumente
Kultur Dokumente
Emergency Model:P350E
3P4W
Rating Range
Standby:
kW
k VA
1500RPM 50Hz
280
350
Prime:
kW
k VA
240
300
ALTERNATOR RATINGS
Alternator Model
HCI444ES(STAMFORD)
50Hz
1500rpm
50Hz
1500rpm
Cont.H -125K/40
Cont.H -125K/40
380
400
415
440
380
400
415
190
200
208
220
190
200
208
220
220
230
240
254
220
230
240
N/A
Rating capacity(kVA)
350
350
350
350
333
357
372
381
Rating power(kW)
280
280
280
280
266
286
298
305
Power efficiency(%)
93.2
93.5
93.6
93.8
93.9
93.9
93.9
93.9
Input power(kW)
300
299
299
299
283
305
317
325
440
Standby.H -125K/40
Standby.H -150K/40
380
400
415
440
380
400
415
190
200
208
220
190
200
208
220
220
230
240
254
220
230
240
N/A
440
Rating capacity(kVA)
370
370
370
370
359
383
397
412
Rating power(kW)
296
296
296
296
287
306
318
330
Power efficiency(%)
92.9
93.2
93.4
93.6
93.0
93.0
93.0
93.0
Input power(kW)
319
318
317
316
308
329
342
355
RATINGS: All three-phase units are rated at 0.8 power factor. Standby ratings : Standby
ratings apply to installations served by a reliable utility source. The standby rating is for
this rating. Ratings are in according with ISO-3046/1,BS 5514 ,AS 2789 , and DIN 6271.
Prime Power Ratings: Prime power ratings apply to installations where utility power is
unavailable or unreliable. At varying load, the number of generator set operating hours
is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with IS0-8528/1, overload capacity in accordance with ISO-3046/1,BS 5514,
AS 2789, and DIN 6271. For limited running time and base load ratings, consult the
factory. The generator set manufacturer reserves the right to change the design or
specifications without notice and without any obligation or liability whatsoever.
GENERAL GUIDELINES FOR DERATION: Altitude: Derate 2.0% per 300m(984 ft.)
elevation above 1000m(3279 ft.) up to a maximum elevation of 2450m(8000 ft.).More than
2450m(8000ft), please contacts with us or our dealer seek the help.
Temperature: Derate 6.0% per 11
(20
) temperature above 40 (104
).
ALTERNATOR
1500RPM 50Hz
Specification
Stator winding
Winding pitch
Winding leads
Maximum overspeed
Altitude
1.5%
Class H
IP23
The 2/3 pitch design avoids excessive neutral currents. With the
2/3 pitch and carefully selected pole and tooth designs,
ensuresvery low waveform distortion.
0.8
Double layer concentric
Two thirds
12
2250 Rev/min
Self excited machines do not
sustain a short circuit current
Type
Exciter type
Voltage regulator
Voltage regulation
Insulation
Protection
Rated power factor
DIESEL ENGINE
2206C-E13TAG2 diesel engines are manufactured by Perkins
Engines Company Limited(UK).
Engine Electrical
Engine Electrical System
Battery charging alternator:
Ground(negative/positive)
Volts(DC)
Ampere rating
Application Data
1500RPM 50Hz
EngineSpecifications
PERKINS
Manufacturer
Number of cylinders
Cylinder arrangement
Cycle
Induction system
Turbocharged
Compression ratio
Bore
16.3:1
130mm (5.39in)
Stroke
Cubic capacity
Direction of rotation
6
Vertical in-line
1, 5, 3, 6, 2, 4
349KW
1478kg (3725 lb)
0.25%
Fixed
8.28m/s
32 m3 /min
Exhaust
Exhaust System
400
(752
Lubrication
Total system
Sump minimum
Relief valve opens
Normal oil temperature
7.65KW
120 rev/min
Battery voltage
12V
Fuel System
1500RPM 50Hz
MEUI
Fuel injector
Fuel injector pressure
MEUI
2000bar
1500RPM 50Hz
Gear driven
413litres/hr
600kPa
4m
Fuel consumption
1500RPM 50Hz
Standby power
75 litre/hr
71litre/hr
Prime Power
65litre/hr
60litre/hr
Baseload Power
55litre/hr
50litre/hr
35litre/hr
Electronic governor
1500RPM 50Hz
Lubrication system
Negative
24V
70A
24V
Fuel
Firing order
1500RPM 50Hz
1500RPM 50Hz
68litres
45litres
610 kPa
95 (203 )
Application Data
Cooling System
Radiator
1500RPM 50Hz
Face area
Rows and materials
0.996 m 2
2 Aluminium
15 Aluminium
Width of matrix
1048.4 mm
Height of matrix
950mm
0.7bar
Fan
1500RPM 50Hz
Diameter
Drive ratio
Number of blades
Material
Type
813 mm
1.055 : 1
9
Plastic
Pusher
Coolant
1500RPM 50Hz
47 litres
12.8 litres
7.0 litres
103
(217.4 )
0.3bar
88 - 98 (190.4 - 208.4 )
Recommended coolant:
50% ethylene glycol with a corrosion inhibitor
(BS 6580 :1992 or ASTM D3306-89 or AS2108)
and 50% clean fresh water.
CONTROLLERS
DSE 702 MANUAL CONTROLLER
DC Supply: 8 to 35 V Continuous.
Paralleling System
Controller System
Accessories
Enclosed Unit
Miscellaneous Accessories
Sound Enclosure
Weather Enclosure (with enclosed critical silencer)
Weather Housing (with roof-mounted critical silencer)
Trailer(Causes the genset easily to move)
Open Unit
Exhaust Silencer, Critical kit
Open Style
Cooling System
Block Heater
(recommended for ambient temperatures below 0
Overall Size, L W H
)
mm
3601 1110
Weight(radiator model),net,Kg
2070
3100
Fuel System
Auxiliary Fuel Pump
Soundproof Style
Overall Size, L W H
Weight(radiator model),net,Kg
mm
4300 1350
2200
3750
Electrical System
Battery Charger, Equalize/Float Type
NOTE : This drawing is provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
DISTRIBUTED BY: