Project Name:
TECHNICAL PROPOSAL
REF NO.:
PACKAGE:
E-0971
HV Switchgear, Distribution Transformer, MCC, EMCC
and Distribution Panels
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
TABLE OF CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Page | 2/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
GENERAL
1.2
STANDARD
Electrical equipment and system which provided will conform to the relevant standards as below:
1.3
Installed equipment
IEC standard
System study
IEC standard
Installation &implementation
IEC standard
Site safety
All offered equipments are designed and selected base on relevant standards (IEC) but in normal condition and
non- hazardous. Offered electrical panel will be suitable for installation in condition specified in project datasheet.
Assume site conditions (indoor) are listed below:
Maximum 40 C
1.3.3 Altitude
Less than or equal to 1000m
1.3.4 Atmosphere
Ambient air not significantly polluted by dust, smoke, corrosive or inflammable gas and vapour, or salt.
1.3.5 Humidity
Average relative humidity over 24-hour period 95%
Average relative humidity over a month period 95%
Page | 3/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
2. SCOPE OF SUPPLY
This Technical Specification contain the proposed design, engineering, procurement, manufacture, inspection,
testing, packaging for shipment and delivery of the equipments of Electrical equipment which comprise of :
MV Switchgear (tag name HVS-RMU)
Distribution Transformer (tag name MP-T)
Low Voltage Motor Control Center - (tag name MCC)
Low Voltage Emergency Motor Control Center (tag name EMCC)
Distribution Boards (tag name MP-SDB-1, ML-SDB-1 & ML-SDB-2, EP-SDB-1, HT-SDB-1, EL-SDB-1)
Page | 4/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
3. SPARE PARTS
3.1
No
MV Switchboard
1
VPIS 24kV
LV Switchboards
1
FUSE 10*38-SP-GI- 10A
Distribution Boards
Not Applicable
Dry Transformer
Not Applicable
3.2
Description
Unit
Qty.
pcs
set
10
Unit
Qty.
pcs
No
Description
MV Switchboard
Charging motor 230VAC, 50Hz for
1
2
Pressure switch
set
VPIS 24kV
set
set
LV Switchboards
MCB 2P 4A C
1
2
set
set
BLOC LAD-N22
set
set
CONTACTOR LC1D80P7
set
set
20
set
set
set
1
1
Distribution Boards
Not Applicable
Dry Transformer
1
PT100
2
Digital Thermometer
Page | 5/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
4. PROPOSED MAKE OF
Item
Description
Model
Brand
Country of origin
24kV switchboard
RM6
Schneider Electric
France
1.1
Circuit Breaker
SF6
Schneider Electric
France
1.2
CT,VT
Schneider Electric
France
1.3
Relay
Sepam
Schneider Electric
France
24kV switchboard
(Option)
FBX
Schneider Electric
France
2.1
Circuit Breaker
Vacuum
Schneider Electric
France
2.2
CT,VT
Schneider Electric
France
2.3
Relay
Sepam
Schneider Electric
France
Dry Transformer
Trihal
Schneider Electric
France
LV switchboard
Okken
Schneider Electric
Indonesia
3.1
Masterpact
Schneider Electric
France
3.2
MCCB
Compact
Schneider Electric
France
3.3
Main contactor
Tesys
Schneider Electric
Czech Republic
3.4
Main relay
Sepam
Schneider Electric
France
3.4
VFD panel
ATV
Schneider Electric
Austria
Distribution Boards
Wall mounting
Schneider Electric
Indonesia
Page | 6/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
PROJECT MANAGEMENT
The management of projects requires knowledge of modern management. This project has a specific set of
objectives and constraints such as a required time frame for completion. While the relevant technology,
institutional arrangements or processes will differ, the management of such projects has much in common with the
management of similar types of projects in other specialty or technology domains.
5.2
PROJECT MANAGER
The project manager is the most important person for the success or failure of a project. Schneiders skilled
project manager will receives authority from the management of the organization to mobilize the necessary
resources to complete a project.
Our project manager will be able to exert interpersonal influence in order to lead the project team and has long
experiences for electrical in this type of project.
The project manager will be given the responsibility and authority to resolve various conflicts such that the
established project policy and quality standards will not be jeopardized. When contending issues of a more
fundamental nature are developed, they must be brought to the attention of a high level in the management and
be resolved expeditiously.
The purpose of this role is to ensure the management of projects to meet contractual obligations, project
milestones and deadlines.
As a Project Manager he will be responsible for:
Construct, develop & implement plans of action to meet clients needs.
Identify assumptions made in the contract scope & assess the risk associated with these assumptions,
inform the client accordingly & take action to minimize these risks.
Coordinate between construction, engineering & procurement throughout the project cycle & ensure that
project activities are in-line with the overall project schedule.
Liaison with technical, environmental, procurement and legal departments; who are all involved with the
project life cycle
Decision making on project
Assist the Project Teams when requested in the execution of their responsibilities and duties.
To manage all phases of the project from the award of the contract through to eventual client acceptance. The
Project Manager will be responsible for all aspects of design, procurement, and construction, supervision and
hands on commissioning of all electrical, instruments and control systems
5.3
Schneider will delegate Electrical engineer to take the leading role in ensuring the scope of work are identified,
studied, recommendations made and documented for the selected options, including:
Responsibilities:
Manage Electrical equipment specification and selection.
Generate/Lead/Implement execution strategies for scope of work.
Provide/facilitate resolution of issues arising from issues.
To provide progress and other reports as required.
Reviews and approves Studies, conceptual designs, detailed design, material/equipment specifications
and drawings.
To attend Factory Acceptance Tests (FAT).
Supervises all electrical work during the design, construction and commissioning of the Project.
Full co-operation with every aspect of the Health and Safety Management System.
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM
Page | 7/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
To ensure that tests and inspection of works are carried out as stated in the specifications.
Page | 8/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
FAT for Transformer shall be scheduled in our site Schneider Electric / Regional Equipment Factory,
Metz, France
FAT for LV switchgear shall be scheduled in our site Schneider Electric / Regional Equipment Factory,
Cikarang, Indonesia
Page | 9/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Project Manager
Purchasing/ Delivery
Project Engineer
Finance
Schneider
MV Switchgear Factory
(France)
Schneider
LV switchboard, DB Factory
(Indonesia)
Schneider
Dry Transformer Factory
(France)
Page | 10/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 11/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 12/42
Our ref.
Project name
Date
9.1
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
GENERAL CONDITIONS
9.2
STANDARDS
In order to be accepted, the switchgear shall comply with the requirements stated in the latest editions of the
following recommendations, standard and specifications:
IEC 60694 common clauses for MV switchgear standards,
IEC 62271-200 MV metal-enclosed switchgear, (replacing IEC 60298)
IEC 60265-1 MV switches,
IEC 62271-102 AC disconnectors and earthing switches, (replacing IEC 60129)
IEC 62271-100 MV AC circuit breakers, (replacing IEC 60056)
IEC 60529 degrees of protection procured by enclosures (IP code).
9.3
SERVICE CONDITIONS
The RMU shall be suitable for operations at a height of less than 1000 meters above sea level.
The RMU shall be capable of operating normally within the following temperature range:
Maximum air temperature : + 40 C
Minimum air temperature : - 25 C
Manufacturer shall declare whether RMU is able to operate in air temperature higher than + 40 C and if
current derating is necessary.
The RMU shall be capable of being operated in electrically exposed locations.
The RMU shall be capable of being exposed to high relative humidity and ambient air pollution.
The RMU shall be capable of being installed in either concrete indoor substations or in compact metal substations
and kiosks with an IP54 rating. Manufacturer shall give all details regarding its solution for free-standing outdoor
installations when requested.
9.4
The RMU shall meet the criteria for compact, metal-enclosed indoor switchgear in accordance with IEC 62271200:
Switchgear classification : PM class
Loss of service continuity class : LSC2A
It shall include, within the same metal enclosure, the number of MV functional units required for connection, power
supply and protection of transformers
9.4.1 Switchboards
The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.2 bar (200 hPa)
relative pressure to ensure the insulation and breaking functions. Sealed for life, the enclosure shall meet the
Package: HV Switchgear, Distribution Transformer, MCC, EMCC and Distribution Panels
BKT WELLHEAD PLATFORM
Page | 13/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
"sealed pressure system" criterion in accordance with the IEC 60694 standard ( 3.6.5.4) : "a volume for which no
further gas processing is required during its entire expected life3. In addition, manufacturer shall confirm that
maximum leakage rate is lower than 0,1 % / year.
It shall provide full insulation, making the switchgear insensitive to the environment (temporary flooding, high
humidity...), IPX7 degrees of protection in accordance with recommendation IEC 60529 14.2.7.
Thus assembled, the active parts of the switchgear shall be maintenance-free and the switchboard shall be lowmaintenance.
The switchboards shall have an IP3X protection index.
The tank shall be made of at least 2 mm AISI 304 unpainted stainless steel and be able to withstand an accidental
internal overpressure of at least 3 bars (3000 hPA)
The colour shall be RAL 9002 for the enclosure and RAL9005 for the mimic panel.
The switchboards shall be suitable for mounting on a trench, utilities space or base.
Each switchboard shall be identified by an appropriately sized label which clearly indicates the functional units and
their electrical characteristics.
The switchgear and switchboards shall be designed so that the position of the different devices is visible to the
operator on the front of the switchboard and operations are visible as well.
In accordance with the standards in effect, the switchboards shall be designed so as to prevent access to all live
parts during operation without the use of tools.
Page | 14/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
9.4.12 Finishing
The device shall be fully designed for use in a hot, humid atmosphere and shall be low-maintenance.
Manufacturer shall provide type test report to prove salt fog withstand for at least 200 hours on operating
mechanism according to IEC 68-2-2 standard.
All metallic parts shall have rust protection.
Two lifting rings shall be installed on the top of the switchboards for handling.
9.5
TEST
The routine tests carried out by the manufacturer shall be backed by test reports signed by the factory's quality
control department. They shall include the following:
Conformity with drawings and diagrams,
Measurement of closing and opening speeds,
Measurement of operating torque,
Checking of filling pressure,
Checking of gas-tightness,
Checking of partial discharges on individual components,
Dielectric testing and main circuit resistance measurement.
Page | 15/42
Our ref.
Project name
Date
9.6
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
22kV
DE-B
22kV
DE-Mt
22kV
DE-BB
Page | 16/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
General characteristics:
SELF- CONTAINED UNIT
Degree of protection
-RM6 Tank
IP67
IP3X (std)
Paint
-RM6 Tank
unpainted
- Enclosure
RAL 9002
- Front plate
RAL 7016
Electrical characteristics:
ELECTRICAL CHARACTERISTICS
Rated voltage
kV rms
24
Service voltage
kV rms
22
Hz
50
kV rms
50
kV peak
125
630
kA rms /1 sec
20
kA rms /1 sec
20
kA peak
50
Frequency
Rated current
Yes
no
the RM6s plinth has got 4 anchoring points which permit
direct fixing to the ground
Page | 17/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
DE-B
(Incoming)
C = plug in 630A (Disconnectable M16)
Bolted
703 mm (std)
standard
three cores, dry type
Yes
Voltage indicator
VPIS
Motorisation
Yes
Auxiliary contacts
Protection relay
CRa
Voltage transformer
/
/
Yes
(1 A.C.)
Trip coil
Included
Undervoltage coil
Interlocking
/
Yes
DE-Mt
(for RC6)
3 Phase to Earth VTs
VT protection
Without MV fuses
VTs position
Fitted left of CT
CTs number
3 Current Transformers
VT ratio
22kV:3 / 110V:3
30VA cl0.5
CT ratio
100-200/5-5A
5VA cl0.5
5VA 5P20
Key locking
LV Box
Yes
Others
Page | 18/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
B unit (Spare)
C = plug in 630A
(Disconnectable M16)
C = plug in 630A
(Disconnectable M16)
Bolted
Bolted
703 mm (std)
703 mm (std)
standard
standard
Yes
Yes
Voltage indicator
VPIS
VPIS
Motorisation
Yes
Yes
Protection relay
SEPAM series 10
SEPAM series 10
CRa
CRa
CSH200
CSH200
Yes
Yes
Included
Included
Undervoltage coil
Interlocking
Bushing type
Interlocking of the access to the bushing
compartment
Height of the cable connectors
Cable box
Type of cables
Auxiliary contacts
Page | 19/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 20/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Withdrawable
Disconnectable
Fixed
Electrical distribution
4000 6300A (Masterpact NW)
800 4000A (Masterpact NW)
800 1600A (Masterpact NT)
800 1600A (Compact NS)
400 630A (Compact NS)
100 250A (Compact NS)
< 100A (C60)
Withdrawable
(device)
(device)
(device)
(device)
Disconnectable
Withdrawable
Disconnectable
Fixed
Fixed
Multi-purpose:
Distribution and motor control feeders
Feeders with different installation modes
Page | 21/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Front side
With all types of connection:
Powering by busbar trunking (Canalis) and/or cables
Cable incoming from the top and/or bottom
Several cable compartment widths and depths for front and rear connection
Rear connection
Page | 22/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Auxiliary circuit:
withdrawable
Withdrawability level:
WWW
Service rating:
332
Auxiliary circuit:
fixed
Withdrawability level:
FFF
Service rating:
211
Auxiliary circuit:
fixed
Withdrawability level:
FFF
Service rating:
211
Auxiliary circuit:
withdrawable
Withdrawability level:
WWW
Service rating:
232
Page | 23/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Disconnectable Polyfast
Solution recommended for:
Economical adaptation by qualified personnel. with operation on
downstream connections
Front connection. by cables
Technical data
Power circuit:
Auxiliary circuit:
withdrawable
Withdrawability level:
WFW
Service rating
223
Plug-in Polyfast
Solution recommended for:
Easy. quick replacements
All types of connection. front or rear. by cables
Technical data
Power circuit:
Auxiliary circuit:
withdrawable
Withdrawability level:
WWW
Service rating:
233
Polyfast drawer
Solution recommended for:
Extremely short replacement times
Auxiliary circuit testing. disconnected from power (TEST position
of the drawer)
All types of connection. front or rear. by cables
Security position: withdrawn / padlocked
Technical data
Power circuit:
Auxiliary circuit:
withdrawable
Withdrawability level:
WWW
Service rating:
333
Page | 24/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Auxiliary circuit:
fixed
Withdrawability level:
WFF
Service rating:
223
Auxiliary circuit:
disconnectab
disconnectable
Withdrawability level:
WFD
Service rating:
223
Auxiliary circuit:
withdrawable
Withdrawability level:
WWW
Service rating:
333
Page | 25/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Easy to connect
Movable framework girders and cross-members
cross
Wide choice of connection compartments
Quick-mounting
mounting junction block for busbar trunking
Page | 26/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
For Okken. all tests were carried out in the most unfavorable conditions.
Partitions
Okken switchboards. respect protection of persons by the choice of functional unit partitions required by the IEC
60439-1 standard:
incomers:
forms 3b. 4b
feeders:
Standard
OKKEN meets the main national and international standards for TTA equipment (Type Tested Assemblies):
IEC 60439-1
IEC 60529
IEC 60068-2-11
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-1
IEC 61641
NBN C 63439
IBC 2003
BS 5486
IEC 60721-2-6
CEI 542
IEC 68-3-3
GOST
Page | 27/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
<= 2000 M
Ambient atmosphere :
STANDARD
40 C
Climate :
STANDARD
400 V
Rated frequency :
50 Hz
15 kA
Neutral system :
TNS
Neutral section :
= PHASE
Auxiliary circuit
Control voltage :
230 V AC Internal
Degree of protection :
54
3B
Painting
RAL 7032
WWW
Plain
Cable connection
Connexion access :
Front
BOTTOM
TOP
Busbar
Rating of main busbar :
800 A - CONSTANT
Coating :
TINNED+EPOXY
Page | 28/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
<= 2000 M
Ambient atmosphere :
STANDARD
40 C
Climate :
STANDARD
400 V
Rated frequency :
50 Hz
15 kA
Neutral system :
TNS
Neutral section :
= PHASE
Auxiliary circuit
Control voltage :
230 V AC Internal
54
31 (VSD Panel)
3B
Painting
RAL 7032
WWW
Plain
Degree of protection :
Cable connection
Connexion access :
Front
BOTTOM
TOP
Busbar
Rating of main busbar :
800 A - CONSTANT
Coating :
TINNED+EPOXY
Page | 29/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 30/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 31/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
18A
Page | 32/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 33/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
32A
Page | 34/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
SECTION
MODULE
>
OKKEN
18/72
>
OKKEN
18/72
>
OKKEN
18/72
>
OKKEN
8/72
>
OKKEN
8/72
>
OKKEN
8/72
>
OKKEN
4/72
>
OKKEN
12/72
Page | 35/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
SWITCHBOARD : EMCC
As per limited space Emergency Room, the EMCC Switchboard will be separated into 2 parallel switchboards:
SIDE A and SIDE B
FRONT FACE LABEL
SECTION
MODULE
SIDE A
INCOMER ACB GENERATOR/1 - 630 A
>
OKKEN
18/72
>
OKKEN
18/72
>
OKKEN
4/72
>
OKKEN
8/72
14
>
OKKEN
8/72
>
OKKEN
8/72
>
OKKEN
20/72
>
OKKEN
4/72
>
OKKEN
72/72
SIDE B
VSD/1 - 90 kW
Page | 36/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Design System
Wall mounted
Type Panel
Indoor
Altitude
Up to 2000 m
Relative Humidity
o
Less than 50 %
Less than 90 %
Anti Arc
No
Environment
Colour
RAL 7032
Electrical Characteristic
Rated Insulation Voltage
1000 VAC
AC 400V, 3P 4W
6kA 1s
Rated Current :
- Main Bus bars
Frequency
50Hz
Communication Facilities
NO
Mechanical Characteristic
Withdrawabily
Fix
Form
Degrees of Protection
IP32
Cable Connection
Top/Bottom
Access
Front
Material
Enclosures
Stainless Steel
Control Cable
Painting
Mimic Diagram
NO
Name Plate
Gravoply
:YES
:YES
:YES
:NO
NO
Page | 37/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Remark
1
1
1
1
3
3
13
8
1
1
1
1
3
3
8
3
NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA
NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA
ML-SDB-2
1
1
1
1
3
3
19
NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
EP-SDB-1
1
1
1
1
3
3
18
1
6
6
NSX100F 4P
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA
MX coil MCB
Aux relay
HT-SDB-1
1
1
1
1
3
3
12
12
NSX100F 4P Toggle
OF+SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 75/5A, Cl1
Pilot Lamps
MCB Acti9 2P
Vigi C60H 30mA
ML-SDB-1
Page | 38/42
Our ref.
Project name
Date
EL-SDB-1
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
1
1
1
1
3
3
21
1
NSX100F 4P Toggle
OF +SD
Voltmeter + Selector Switch
Ammeter + Selector Switch
CT 50/5A, Cl1
Pilot Lamps
MCB Active9 2P
Vigi C60 30mA
Page | 39/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Page | 40/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Frequency : ........................................................50 Hz
Vector group : ...................................................D yn11
Windings HV/LV : ............................. Copper imposed
Rated low voltage 1 : .............. 420 V (At no-load)
Rated high voltage insulation level : .....................24kV Rated low voltage insulation level : ................... 1.1 kV
Applied voltage to industrial frequency : ..............50 kV Applied voltage to industrial frequency : ............ 10 kV
B.I.L. (1,2 / 50s) : .............................................125 kV B.I.L. (1,2 / 50s) : ................................................. N/A
HV tapping (off-circuit) : ..... +-2,5 +-5,0 % (Connecting
links)
High voltage connections
Low voltage connections
Connections type : ....... Fixed plug-in bush. HN 52S61 Connections type : ............. LV upward pointing risers
Cables incoming : ...................................................Top Cables incoming : .................................................. Top
Connections location : .............................................Top Connections location : ................... Top LV connection
Current rated of the plug in bushings : ................ 250 A Secondary arrival : .............................................Cable
Connections marking : ............................................ IEC Number of connections : ........................................... 4
Number of connections : .............................................. 3
Plug in bushings location : ...................... On the cover
Locking device on plug in bushings : .... Stainless steel
without lock
Electrical characteristics
Site conditions
No load losses : ................................................ 1375 W
Load losses (AN) at 120C : ............................ 4862 W
Impedance voltage (AN) at 120C : .....................6.6 %
Tolerances : ............................ IEC 60076-1 Tolerance
Thermal characteristics
Page | 41/42
Our ref.
Project name
Date
: E-0971
: BKT WELLHEAD PLATFORM
: October 06, 2014
Packing characteristics
Packing type : ........................................ Packing SEI4c
Wood quality : .................................................... normal
Page | 42/42