Sie sind auf Seite 1von 163

Two nos. WTI for HV (on extreme phases), one no.

WTI
for IV ( on middle phase) & one no.WTI for LV ( tertiary)
winding : These shall be indicating type, with repeater
responsible to the combination of top oil temperature and
winding current, calibrated to follow the hottest spot
temperature of the transformer winding. The winding
temperature indicator shall operate a remote alarm before the
hottest spot temperature approaches a dangerous value and it
shall automatically actuate the cooling fan Motors.
iii RWTI : These shall be as per cl. 11.10 of section I. A
precision potentiometer mounted inside the case shall function
as a transmitter to operate a repeater for RWTI. For two
windings ( i.e. HV and IV) the transmitter shall be directly
connected to the repeater. For the third winding (i.e. LV)
the transmitter shall be connected to a Resistance Transducer,
which will supply DC for operating repeater.
iv One magnetic type oil level gauge with low level alarm
contacts and dial showing minimum, maximum and normal oil
levels.
v One plain oil level gauge of over lapped type on either side of
the conservator shall also be provided.
vi Valves (As Per Annexure V) In the Annexure-V of valve
schedule, 4 nos. valves are required to be provided in each
Thermosyphon filter. Out of 4 nos., 2 nos. shall be provided
for the purpose of disconnecting the oil flow between the
main tank and Thermosyphon filter and 2 nos. are to be
provided for the purpose of filtration of charge of the
Thermosyphon without disconnecting the Thermosyphon from
body .
vii Minimum 3 nos. pressure relief valves . The quantity of
these valves should commensurate with the quantity of oil in
the transformer and also location of valves should be
properly designed to adequately release the excessive
pressure.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 80 of 115

viii A set of air release valves on the top and on the radiators and
also at appropriate places.
ix One thermometer pocket for mercury in glass type
thermometer.
x One double float gas detector relay(Buchholz relay) with alarm
and tripping contacts to detect accumulation of gas and
sudden changes of oil pressure, complete with shutoff valves
and flanges couplings to permit easy removal without lowering
oil level in the main tank, a blend valve for gas venting, and
test valve. Make of buchholz relay shall be as per our
discretion.
xi Heat exchangers or radiators complete with shut of valves and
with facility for oil draining arrangement.
xii a. Two oil conservator, with required accessories, one for
main tank and other for OLTC. Two nos Silica gel
Breathers with main Conservator & OLTC Conservator.
b. Air cell type breathing arrangement with oil preserving
equipment complete in all respects of PRONOL make

only.
xiii Eye bolts and lugs on all parts for easy handling.
xiv Two grounding earthing terminals at diagonally opposite
corner of tank.
xv One rating and diagram plate.
xvi A set of minimum 4 nos. flanged bi-directional wheels for rail
mounting (for 1676 mm rail gauge.)
xvii Set of fans required for ONAF cooling of the transformer with
following information
a. Number of Radiator Banks.
b. Required no of cooling fans (Industrial duty of
adequate voltage & rpm) be provided in each bank to
ensure 100% ONAF rating of the transformer. As per
our specification, for each bank 20% additional cooling
fan is to be included which will be duly wired-up.
xviii Suitable jacking lugs and haulage holes.
xix Inspection window & main holes with bolted cover as per
Annexure-IV
xx Adequate no of Thermosyphon filter assembly (minimum 4
nos) with suitable supports, valves and pumps for forced but
slow circulation of Transformer oil .
xxi Lifting arrangement for the complete transformer, core coil
assembly and also tank.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 81 of 115

xxii One detachable bolted type MS ladder each on main tank and
conservator tank.
xxiii For the purpose of taking earthing connection from the
neutral bushing, adequate number of brackets with small
support insulators shall be provided on the body of the tank
so that earthing could be arranged by Purchaser near the
earthing pit of transformer itself.
xxiv A separate weather proof FCC (Fan/Cooler control) cubicle
containing dial type thermometer and winding temperature
indicator and terminals of dial, type thermometer, winding
temperature indicator, buchholz relay, MOG, control of fans
etc.
Please note provision of separate Fan Control Cubicle (FCC)
is a must. FCC shall be suitably dimensioned to accommodate
the following :a The wiring from RTCC shall be brought to marshalling box
and for terminating the same adequate numbers of
suitably rated terminal connectors shell be provided.
b Necessary cable glands shall be included in the scope of
supply. The cable gland and the hole on gland plate for
cable entry shall be provided.
c Arrangement for terminating the connecting leads of
OTI, WTI, buchholz, magnetic oil level gauge etc. shall be
made in the marshalling box. It should be possible to
read OTI and WTI readings without opening the box
through suitable glass window. All trip alarm and
repeater signals will be transferred to control room for
which arrangement will have to be made.
d Starters for cooling fans shall be housed in marshalling box

and necessary switches for local operation of fans shall be


provided.
e Local remote control switch for OLTC shall be provided.
f Space heater with switch, cubicle illumination lamp, fuses,
links overload protection arrangement for motors and
other accessories shall be included in the scope of supply.
xxv One set of indoor RTCC (Remote tap changer control) cubicle
complete with provision for remote operation of OLTC, as
independent or master/follower scheme, with oil and
winding temperature repeater, tap position indicator with
annunciation for fan group ON/OFF and cooler supply fail
indication and Tap changer in progress including OTI repeater
& WTI remote indicator operated by remote sensors.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 82 of 115

xxvi One set of erection manual/relevant drawing/leaflets should be


secured permanently inside the RTCC cubicle as a guide line for
site erection and commissioning.
xxvii Three separate connection i.e. connection from core,
connection from end frame and connection from tank shall
be brought out on to a terminal box with cover. Arrangement
for inter connecting these terminals in the terminal box shall also
be provided. This arrangement shall facilitate verification of
core, end frame and tank insulation.
xxviii Mounting of radiators on the 33KV side of 72.5 KV
bushing should be avoided. In no case, the radiators
should be projected above the main tank height.
xxix All transformers shall be supplied with a full outfit of tools,
spanners, jacks, special tools as per annexure IX for
assembly and all spanners shall be double ended and of very
good quality of " Gedore " or "Taparia " or equivalent make.
2. The equipments and accessories furnished with the transformer
shall be suitably mounted on the transformer for ease of operation, inspection
and maintenance and the mounting details shall be subject to the approval
of the purchaser. All valves shall be provided either with blind companion
flanges or with pipe plugs for protection.
3. Indication, alarm and relay equipment shall have contacts suitable for
operation with 110V/220V DC supply. Any other accessories or appliances
recommended by the manufacturer for the satisfactory operation of the
transformer shall also have 110V/220V DC as input.
4. a. OLTC and its controls shall be as per clause 14.
b. All cabinets & panels shall be conforming to
stipulations under Clause-16.
c. All 220KV, 132KV, 33KV and neutral bushings shall be of OIP
condenser type and as per Clause 11.13.
5. Nitrogen injection type fire prevention & extinguishing system with flow
sensitive conservator isolation valve shall be provided for all the transformers
as per clause no. 20.9.
6. On Line Monitoring Device shall be provided for all the transformers as
per clause no. 20.10.
7. Provision for Measurement of Degree of Polymerisation of
Insulation of Winding of Transformer :- To assess the life of paper
insulation of winding , a provision is to be made inside the transformer . For
this purpose, a container of insulating material of good electrical, mechanical

& chemical properties having free circulation of oil through it shall be provided
at suitable location where maximum oil temperature is expected. In the
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 83 of 115

container, atleast 10-12 spools of paper having size not more than one cm be
placed . The container shall be closed and there should not be any possibility
of spools coming out from the container due to natural circulation as well
turbulence of oil during fault etc.
Location of the container shall be selected such that spools may be
removed from the container as and when required by the purchaser during
service of transformer for the purpose of testing of insulating material for
Degree of Polymerisation (DP test).
8. Accessories, which are not included in the above annexure
but details of which are given in Bid specification and which are
necessary for satisfactory operation of Transformer shall be deemed
to have been included in the accepted price without any extra cost
to the Purchaser.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 84 of 115

ANNEXURE -III
LIST OF TRANSFORMER ACCESSORIES AND THEIR TESTCERTIFICATES
TO BE SUBMITTED BY MANUFACTURERS/APPROVED VENDORS
S.
No.
Accessory Ref. Std. Test-certificates required
1 Condenser
Bushing
IS 2099
IEC 60137
1. Appearance, construction and
dimensional check
2. Test for leakage of
internal filling at a pressure
of 1.0 kg/cm2 for 12hours.
3. Insulation resistance IS
2099 measurement with
2000V megger.
4. Dry/wet power frequency
voltage withstand test.
5. Dry/wet power frequency
voltage withstand test for
test tap insulation
6. Partial discharge
measurement up to 1.5
UN/_/3 KV.
7. Measurement of tangent
delta and capacitance.
2. Pronol IEC 1. Dimensional check,
inflation/Deflation at 10
inflation/Deflation at 10 KPa
2. Pressure test at 10 KPa for
24 Hr.
3. OLTC IS 2026 Part I
IEC 60214

1. Oil tightness test for the 8468


diverter switch oil chamber
at an oil pressure of 0.5
kg/cm2 at 100 degree
centigrade for 1 hour.
2. Mechanical operation test.
3. Operation sequence
measurement
4. Insulation resistance
measurement using 2000V
megger
5. Power frequency voltage
withstand test on diverter
switch to earth and between
even and odd contacts.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 85 of 115

S.
No.
Accessory Ref. Std. Test-certificates required
6. Power frequency voltage
withstand test on tap
selector-between stationary
contacts, between max. and
min. taps, between phases
and supporting frames,
between phases.
7. Operation test of complete
OLTC.
8. Operation & dielectric test
4. Winding & Oil
Temp Indicator
IS 1. Calibration test
2. Dielectric test at 2 kV for one
minute.
3. Accuracy test for indication
and switch setting scales.
4. Test for adjustability of
switch setting
5. Test for switch rating
6. Measurement of temperature
rise with respect to the
heater coil current.
5. Pressure Relief
valve
IS 13947 1. Functional test with
Compressed air to check
bursting pressure, indicating
flag operation and switch
operation.
2. Dielectric test at 2 KV for one
minute.
3. Switch contact testing at 5A,
240 Volt AC.

4. Leakage test at 75%


operating pressure for 1Hr.
6. Cooling Fan and
motor assembly
IS 2312 1. Appearance, construction and
dimensional check.
2. Insulation resistance
measurement
3. Dielectric test at 1.5 KV
between winding and body
for one minute
4. Operation check.
5. Power consumption, RPM,
Current.
7. Buchholz Relay IS:3407 1. Leak test with transformer oil
at a pressure of 3 kg/cm2
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 86 of 115

S.
No.
Accessory Ref. Std. Test-certificates required
for 30 minutes at ambient
temperature for relay casing.
2. Insulation resistance
measurement with 500V
megger.
3. Dielectric test at 2 kV for 1
minute
4. Elements test at 1.75 kg/cm2
for 15 minutes using
transformer oil at ambient
temperature.
5. Loss of oil and surge test.
6. Gas volume test
7. Mechanical strength test
8. Velocity calibration test
9. Appearance construction and
dimensional check.
8. Oil Level gauge
including MOG
IS 1. Appearance, construction and
dimensional check
2. Dielectric test at 2 KV for 1
minute
3. Switch contact test at 5A 240V
AC
4. Switch operation for low level
alarm
5. Test for oil levels
9. Pressed Steel
Radiators
IS 513 1. Appearance, construction &
dimensional check.
2. Air pressure test at 2

kg/cm2 under water for 15


minutes
10. OLTC Control
cubical/Cooler
Control cubicle
IS 1. Appearance, construction &
dimensional check.
2. Electric operation
3. Insulation resistance
measurement using 500 V
meggar at ambient
temperature
4. Dielectric test at 2kV for 1
minute
11. Bushing Current
Transformers
IS 2705 1. Appearance, construction &
dimensional check. Polarity
Check, Measurement of
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 87 of 115

S.
No.
Accessory Ref. Std. Test-certificates required
insulation resistance.
2. H V power frequency test.
3. Determination of ratio error
and phase angle of measuring
and protection BCTs
4. Interturn insulation test
5. Exciting current characteristic
test, Secondary winding
resistance measurement
12. Terminal
connector
IS 5561 1. Dimensional check construction
2. Tensile test, resistance test,
3. Test as per IS-5561
13 Silica Gel
Breather
1.Pressure tests
2. Visual & dimension tests
3. Operation test
4. silica gel test
5. Oil compatibility test
14 NIFPS TAC/NEPA
norms
1. Lamp test
2. Out of Service
3. Transformer Conservator
Insulator Valve (TCIV) open
4. Transformer Conservator
Insulator Valve (TCIV)
closed

5. Fire Detector trip


6. Buchholz Relay trip
7. Differential Relay trip
8. PRV trip
9. RPRR trip
10.Transformer trip
11.D.C. fail etc..
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 88 of 115

ANNEXURE-IV
SCHEDULE OF INSPECTION COVER/ACCESS WINDOWS
S.No. Particulars
Size
(Length x
Width)
(mm x mm)
Qty.
(Nos.)
1 Inspection cover (man hole) 450x900 1
2
Inspection cover/ Access Window
for OLTC
400x500 3
3
Inspection cover/ Access Window
for HV Bushing
500x500 3
4
Inspection cover/ Access Window
for IV Bushing
500x500
3
5
Inspection cover/ Access Window
for LV (Tertiary) Bushing
500x500
3
6
Inspection cover/ Access Window
for Common Neutral Bushing
(Auto Xmer)
500x500
1
7
Inspection cover/ Access Window
for inspection of active parts /
connections etc. as per
manufacturers design
As per design requirement
8
Inspection cover/ Access Window
for visual inspection internal
parts
As per design requirement

Volume-II, Part-4

MPPTCL/TECH/PROC/04/July13 Page 89 of 115

ANNEXURE-V
SCHEDULE OF VALVES
Item Description of Valves Size Qty Type (Design)
1 Oil inlet valve for Radiator
header
250NB 2 Gate valve
2 Oil outlet valve for Radiator
header
250NB 2 Gate valve
3 Top Oil filter valve 50NB 2 Gate valve
4 Bottom Oil filter valve 50NB 4 Gate valve
5 Top oil sampling valve 25NB 1 Globe valve
6 Bottom oil sampling valve 25NB 1 Globe valve
7 Drain plug bottom tank 50NB 2
8 Drain valve (Tank) 100NB 1 Butterfly valve
9 Drain valve (Tank) 100NB 1 Gate valve
10 Quick Oil discharge valve 125NB 1 Gate valve
11 N2 Injection valve 25NB 6 Gate valve
12 Radiator Isolating valve 100NB As per
design
Butterfly valve
13 Drain plug on radiators Bsp
14 Air release plug on radiators Bsp
15 Drain cum filter valve on
header
50NB 4 Globe valve
16 Drain plug on header Bsp 4 -17 Air release plug on header Bsp 4
18 Drain plug on inlet pipe Bsp 2
19 Drain plug on outlet pipe Bsp 2
20 Air release valve on tank
cover
15NB 2 Gate valve
21 Pressure release valve (Main
tank)
150NB 3 Gate valve
22 Valve for DGA 25NB 2 Gate valve
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 90 of 115

23 Thermosyphon drain valve 25NB 4 Globe valve


24 Thermosyphon filter valve 50NB 8 Gate valve
25 Drain plug on Thermosyphon
filter
Bsp 4
26 Air release plug on
Thermosyphon filter
Bsp 4
27 Thermosyphon pump isolating
valve
100NB 4 Gate valve
28 Thermosyphon pump bypass
valve

100NB As per
design
Gate valve
29 Thermosyphon isolating valve 100NB 8 Butterfly valve
30 Oil surge relay isolating valve 25NB 3 Globe valve
31 OLTC equalizing valve 25NB 3 Gate valve
32 OLTC suction valve 25NB 3 Globe valve
33 OLTC Conservator drain valve 25NB 1 Globe valve
34 Buccholz relay isolating valve 80NB 2 Gate valve
35 Pre Stressed Non return valve 80NB 1 Gate valve
36 Gas Sampling valve Bsp 2 Gate valve
37 Main conservator Drain valve 50NB 1 Gate valve
38 Main conservator Air release
valve
25NB 1 Gate valve
39 Main Breather isolating valve 25NB 1 Gate valve
40 Valve for Vacuum breaking
during oil filling
25NB 1 Gate valve
41 Valve for inlet/outlet for OLMD 25NB 2 Gate valve
* NOTE: 1. All valves shall have position indicators to indicate the status i.e.
valves are in open or shut position.
2. All valves shall be made of gun metal (GM); cast iron valves are
not acceptable.
3. All plugs shall be made of cast iron (CI)/GM
NB- Normal Bore mm.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 91 of 115

ANNEXURE VI (A)
DRAWINGS AND DATA TO BE FURNISHED BY THE BIDDER.
The following drawings and data for each items are to be submitted
with the Bid
(a) Outline dimensional drawings of transformer and its accessories
including conservator complete with Bill of material and details of
all parts, their quantity, rating & name of Vendors indicating
clearances of transformer body from live terminals i.e. HV,IV,LV.
(b) Drawing of transformer tank with location of inspection windows,
thickness of side/bottom/top of tank, details of stiffener.
(c) Drawing indicating limbed core construction with complete details of
no., width and wt. of core laminations with size of steps; thickness of
core laminations ; dimension of window; size of limbs; Gross and net
core ; wt. of complete core.
(d) Drawing indicating core belting arrangement with details of belting,
belting material etc.
(e) Large scale dimensioned drawings for HV,IV & LV windings of the
transformer; size and no. of parallel of HV,IV, LV and of, cooling
ducts, coil clamping arrangement, no./size & location of pressure
screws, clamping ring; top yoke arrangement etc. The details should
commensurate with the short circuit calculations submitted by you for
each rating of transformer
(f) Detailed drawing of transformer tank with complete core and winding
indicating clearances inside transformer tank as also passage and
space for free movement of at least two persons for inspection of
active parts etc .

(g) Schematic diagram showing the flow of oil in the cooling system as
well as each limb and winding. Longitudinal and cross-sectional views
showing the duct sizes, cooling pipes etc. for the
transformers/radiators drawn to scale .
(h) Drawings giving the weights for foundations.
(i) Combined Rating and diagram plate including tap changing, which
should also include details of guaranteed and measured no load and
load losses as also winding resistances and percentage impedances at
all taps.
(j) Schematic control and wiring diagram for all auxiliary equipment
and control cubicle.
(k) Drawing showing constructional details, dimensions, mechanical
& technical particulars of bushings. Arrangement of terminals and
details of connection of bushing shall also be indicated in drawing with
their technical particulars.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 92 of 115

(l) Transportation drawing of transformer.


(m) Details of fittings and cable box.
(n) Drawing showing arrangement and details of tap changing gear
including selector switch, diverter switch and drive mechanism.
(o) Valve Schedule plate.
(p) Oil filling instruction plate for conservator fitted with Air cell breather
arrangement including equalizing arrangement if any required at
the time of taking full Vacuum at site.
(q) Drawing and instruction for fitting of Air Cell.
(r) Drawing of conservator indicating internal details of air cell MOG, oil
level gauge and silica gel breather pipe fitting arrangement.
(s) Drawings of all HV, IV & LV bushings with complete details meeting TS
requirement.
(t) Drawings of HV,IV,LV & neutral terminal connectors indicating plate
thickness, no. of nut bolts with size and other details.
(u) Drawing of foldable & detachable ladder with its complete details and
fitting arrangement on transformer/ conservator tank.
(v) Drawing for HV/IV neutral earthing arrangement indicating voltage
rating of insulators and its fitting arrangements, size of copper strips,
terminal connectors etc.
(w) Detailed drawing indicating two views of all valves provided in the
transformer tank.
(x) Drawing of Thermosyphon filter with fixing arrangement with
transformer tank.
(y) Detailed internal drawing of transformer indicating transportation
locking arrangement provided to avoid shifting of core assembly.
(z) Drawing showing weights of transformers, cooling fan structures, FCC
structures with distance from central line of transformer for casting of
civil foundation for transformer and associated equipments.
(aa) Drawing of Earthing terminal box showing earthing arrangement for
core, end frame, tank giving details of voltage class and current rating
of terminal bushings.
(ab) Drawing indicating insulation thickness details and other arrangement
provided between core assembly and bottom yoke and base of bottom
of tank.
(ac) Drawing indicating details of O ring gasketting arrangement provided
in transformer tank covers.

(ad) Detailed Drawing of jacks.


(ae) Drawing of stiffeners provided on top, each faces/sides of tank with
their number and size.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 93 of 115

(af) Drawing indicating number, location, size of shields/ magnetic shunts


and its material provided inside the tank as per clause 11.1 (g).
(ag) Drawing indicating internal details of transformer giving complete
details of clearances from live parts.
(ah) Drawing of internal LV winding termination arrangement indicating
minimum clearance between core and LV take off lead.
(ai) Drawing of Neutral Current Transformer with details of its mounting
arrangement.
(aj) Drawing for Lead termination to bottom of HV & LV bushings.
(ak) Drawing of On Line Monitoring Device with details of mounting
arrangement.
(al) Drawing for Lead termination to bottom of HV & LV bushings.
(am) Internal drawing & design of Core & Winding indicating all attachment
with identification numbers, description including take-off arrangement
of lead connection for Core & End frame and related Bill of Material
(an) Locking arrangement drawing for tank top cover, core & winding with
complete dimension & details.
(ao) Plan view of the bottom of Bell Tank for complete details of core coil
resting arrangement, indicating clearly dimensional details, material of
insulation, clamping arrangement with details of nuts/ bolts, clearance
from all sides provided at bottom.
(ap) Drawing indicating complete details, dimension & mounting
arrangement of OLTC inside the tank with respect to End frame.
(aq) Drawing indicating complete details, dimensions & fixing arrangement
of static end rings if used.
(ar) Other relevant drawings.
As soon as possible after the award of the contract the manufacturer shall
supply four (4) copies of the drawings as listed out above, which will
describe the equipment in details for approval and shall subsequently
provide ten complete sets of final drawings, one of which shall be autopositive
suitable for taking blue prints. Ten sets of instruction books,
operation and maintenance manuals and spare part bulletin, shall be
supplied. In addition to above two sets of manuals and drawings with test
certificates for each unit to be despatched as per despatch instructions.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 94 of 115

ANNEXURE VI (B)
LIST OF DRAWINGS TO BE FURNISHED ALONGWITH BID
S.No. Particulars
1 OGA drawing of transformer
2 List of fittings & accessories for OGA
3 Drawing for HV,IV,LV , OIP Condenser bushings
4 Makes of various accessories and source of raw material
5 Universal type bimetallic terminal connector for HV,IV,LV, Neutral
6 Conservator with air cell breathing arrangement
7 Thermosyphon filter assembly with pump & without pump
8 Internal clearances detailed drawing
9 Dimensional details for transportation of transformer.
10 Radiator arrangement

11 Core earthing arrangement box


12 Yoke binding details
13 Neutral earthing arrangement
14 Foundation details
15 List of tools & tackles
16 Bottom locking & insulating arrangement
17 Core insulation details
18 MS Ladder
19 Sealing arrangement between top & bottom shell.
20 OLTC Conservator with breather arrangement
21 Drawings for various types of valves.
22 Core shunt fixing arrangement
23 Rating & diagram plate
24 Valve schedule plate
25 Oil filling instruction plate for conservator with air cell.
26 Roller assembly with anit-earthquake arrangement
27 Coil clamping arrangement
28 Oil flow diagram
29 Winding details arrangement with dimension
30 Core details with design data
31 Over fluxing curve
32 Drawing for tank stiffener & magnetic shunt inside transformer with
calculation.
33 NIFPS with complete catalogue, manuals & drawings.
34 Schematic drawings for OLTC, FCC & RTCC .
35 Cooler control cubicle cum marshalling box with schematic
36 RTCC panel drawing
37 Drawing for static end ring
38 Complete dimensioned details of bottom tank
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 95 of 115

ANNEXURE VII
DESIGN CALCULATIONS & DESIGN DATA REQUIRED TO BE ENCLOSED
WITH THE BID FOR POWER TRANSFORMER
It should be specifically noted by the Bidders that submission of
following Design Calculations & Design Data with the offer is
necessary and bids wherein these calculations are not found enclosed
shall run risk of rejection.
(1) SHORT CIRCUIT WITHSTAND CAPABILITIES : The calculations to
prove dynamic and thermal short circuit withstand capability of transformer
as per clause 31.1.1 shall be submitted for the fault level indicated as
under:
220KV & 132 KV - 40 KA for 3 secs.
33KV - 31.5KA for 3 secs.
Results of calculations shall be submitted with the Bid. The design of winding
assembly , which is to be furnished in the drawing as per Sr. No. (e) of
Annexure VI(A) should be commensurating with these calculations. The
details of clamping ring shall be indicated in the drawing .
It may be noted by the Bidders that calculations for short circuit withstand
capability for two winding transformer is not acceptable under any
circumstances and these calculations shall be submitted for 3 winding auto
transformer. The computer output for calculations of short circuit forces with
minimum of 7 iterations with limiting values shall be submitted during Design
Review as per Cigre Guidelines.

(2) DESIGN DATA OF CORE & WINDING : On the basis of offered flux
density and current density, the Bidders shall furnish following design
calculations & data. Calculations regarding wt. of core & copper and also
calculations for losses will be brought out to justify the offered transformer
losses. :
(A) Core Data: Details of core material i.e Name of Manufacturer,
Manufacturers type designation for core , thickness of core, curve for
Loss Vs Flux density, no. of steps of Core & no. of limbs, gross core area
, stacking factor , Net core area ,height & width of core window, center
to center distance of limb, voltage per turn, wt. of core material,
working flux density , core loss in watts per kg marked on graph for
grade of core material & selected flux density, building factor and
calculated no load loss in watts, guaranteed no load loss. Design data for
core as per clause 31.2.1 shall be submitted with the Bid. A drawing
indicating details of core i.e. limbed construction, step width & thickness
, core belting, top & bottom yoke plate etc shall be submitted with the
Bid .
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 96 of 115

(B) Winding Data: wt. of copper for windings ie. for HV(series), IV(common)
,tap, LV(tertiary), cross sectional area , current density, type of coil,
ID/OD/mean dia of coils, size of winding conductor including parallels,
no. of turns per phase, no of spacers, length of mean turn, weight of
copper without paper covering, resistance per phase of winding at 75 deg
C, I2R loss at 75 deg C at normal tap, eddy current & stray loss at 75 deg
C , total copper loss at 75 deg C , guaranteed transformer losses at 75
deg C.
Complete details of Insulation components i.e. Top & Bottom clamping
rings, washers , Pressboard blocks & cylinders, Pressboard spacers &
Phase barriers, Pressboard segments etc shall be submitted indicating
qty , thickness in mm, width & height , wt. Design data for winding as
per clause 31.2.2 shall be submitted with the Bid.
Dimensioned drawings indicating details of winding , ducts, insulation ,
take off arrangement, clamping ring , pressure points etc shall be
submitted with the Bid .
(3) DESIGN OF TANK : Complete mechanical design of transformer tank
including details of stiffeners as per clause 31.1.2 shall be submitted . The
tank shall be designed to withstand the following without permanent
distortion.
(i) Mechanical shocks during transportation.
(ii) Vacuum filling of oil at 10 milli torr in transformer with all fittings.
(iii) Continuous internal pressure of 35 kN/m2 over normal hydrostatic
pressure of oil.
(iv) Short circuit forces &
(v) Under seismic condition /events both horizontal/vertical .
The calculations for tank stiffeners shall be submitted with the Bid to prove
no. & size of stiffeners are adequate to withstand full vacuum & pressure .
Drawing of tank shall be submitted indicating stiffeners .
(4) DESIGN OF STATIC END RINGS (SER) AND MAGNETIC SHUNTS :
Details of Static End Rings (SER) and magnetic shunts , if provided , with
calculations as per clause 31.1.3 shall be submitted with the Bid. A drawing
indicating locations , size ,material of SER and magnetic shunts shall be
submitted with the Bid .
(5) QUANTITY OF OIL : Complete calculations of oil quantity to be utilized

in transformer for first filling shall be submitted with the Bid. The calculations
shall indicate
(i) Volume of tank including turrets, conservator main & OLTC ,volume
of headers & Radiators, oil quantity in OLTC & thermosyphon filter.
(ii) Oil displacement by Active parts i.e. core - coil assembly,
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 97 of 115

(6) CAPACITY OF CONSERVATOR & SIZE OF AIR CELL : While furnishing


details of conservator & air cell type sealing arrangement, the Bidder shall
submit details & calculations for adequacy of size and capacity of Pronal
make air cell for the rating of the power transformer and also for the
quantity of oil required. Catalogue of Pronal should be enclosed with the Bid
clearly marking type designation of selected size of Air cell. A drawing
indicating complete details of conservator with Air cell shall be submitted .
(7) CAPACITY OF PRESSURE RELIEF DEVICE : Bidders must submit
calculation to prove that the capacity/rating of pressure relief device and
locations of the same for the transformer will adequately meet our
requirement. Constructional and design details of pressure relief device must
be furnished and it should be proved by calculation that the size and
setting of pressure relief device is adequate considering the rating of the
transformer and quantity of oil in the transformer. A drawing indicating
complete details of PRDs & their locations on tank shall be submitted .
(8) CALCULATIONS FOR TEMPERATURE RISE & HOT SPOT WINDING
TEMPERATURE : The limits of temperature rise for windings, oil and hot spot
have been specified in Volume II . Temperature rise calculations at rated full
load, 110% load and 125% load considering 100% cooler banks, 50% cooler
banks and without coolers shall be furnished as indicated below :
(a) 100 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(b) 110 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(c) 125 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
The calculations shall indicate temperature gradient (for all windings i.e.
HV,IV,LV,tap), load losses at lowest tap for all windings , Eddy current & stray
losses, thermal Constant Value & calculations with parameters affecting the
values for above conditions for top oil temperature & winding hot spot
temperature .The Calculations for Hot Spot winding Temperature and
Calculations for Temperature Rise shall be submitted with the Bid.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 98 of 115

(9) COOLING CALCULATIONS : Calculations of tank surface for heat

dissipation, details of radiators , fans for ONAN & ONAF cooling shall be
provided with the Bid.
(10) OVERFLUXING CAPABILITY: A curve to prove suitability of
transformer to withstand various Overfluxing conditions for the duration
indicated in clause 4.4.1 to 4.4.3 without core saturation shall be furnished
with the Bid .
(11) CAPACITY OF FILTER & BREATHER :
(A) Number and Capacity of each Thermosyphon Filter : The
Bidder shall submit details & calculations for adequacy of size and
capacity of thermosyphon filter for the oil quantity in the power
transformer . While furnishing details of thermosyphon filter
arrangements, the Bidder must confirm clearly the number of
thermosyphon filter, its size and capacity is adequate for the rating of
power transformer. The Bidder shall submit details & calculation to
prove for adequacy of size and capacity of thermosyphon filter.
(B) Capacity of Silica Gel Breather : The Bidder shall submit details &
calculations for adequacy of size and capacity of silica gel breather
for the oil quantity in the power transformer with the Bid.
(12) RATING OF ON LOAD TAP CHANGER (OLTC) : To verify the
adequacy and suitability of the OLTC components, it is necessary to furnish
the calculations for selecting the proper rating of transition resistance as
well as the normal current rating of OLTC. The calculations shall include the
temperature rise of the OLTC diverter switch and also the short circuit
current considered for calculation of temperature rise.
Calculations shall be submitted to prove that the current rating of OLTC is
adequate for the rating of the transformer winding taking in to account the
over loading capability as per IS 6600 . The basis for selection of transition
resistance and its current carrying capacity shall also be submitted. In this
regard the circulating current in tap winding during tap change operation
through transition resistance shall be taken in to consideration. Adequacy of
insulation provided in the OLTC between various parts needs to be established
with specific reference to the voltage between two taps. Confirmation shall be
given that the OLTC is suitable for bidirectional flow of current. The through
current capacity shall be adequate to handle on continuous basis the winding
current including over loading as per IS 6600. The through current rating and
the rating of transition resistance shall take in to account the short time
current rating of the winding. Capability to handle short circuit current to be
established by calculations and also by test reports.
The above Calculations for OLTC shall be submitted with the Bid.
(13) Capacity of Nitrogen Cylinder, pressure in Nitrogen Cylinder to be used
during transportation shall be submitted with the Bid.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 99 of 115

(14) Size & capacity of Oil sump/ pit for Nitrogen Injection Fire Protection
System shall be submitted with the Bid.
(15) DESIGN REVIEW : The Design Review of the 160 MVA, 220 KV
transformer shall be carried out in accordance with the Guidelines
for consulting Design Reviews for transformers 100 MVA & above of
Cigre working group 12.22 (SC12 WG 12.22). The Bidder shall carry out
optimization of Dielectric design of insulation including electromagnetic
design, overload & short circuit withstand capabilities. During design ,
transformer modeling shall be done & finite element software (FEM) may be
used.
Note : Bidders may please note that submission of above

calculations & design data as mentioned in clause 31 and in this


Annexure with technical bid is an essential requirement of the Bid.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 100 of 115

ANNEXURE VIII
DETAILS OF INSPECTION PROGRAMME
1 . INSPECTION PROGRAMME :
1.1 Manufacturer shall chalk out a detailed inspection and testing
programme for various manufacturing activities for the different
components, fittings & accessories. The MPPTCL also reserves the right to
carryout any tests by a third party at its sole discretion. All Costs of
inspection/ tests shall be borne by Manufacturer.
2.2 STAGE INSPECTIONS :
2.2.1 Manufacturer shall indicate the inspections and checks carried out at
various stages of the manufacture of the transformer. A complete record of
stage inspection shall be kept by Manufacturer and this record shall be made
available for inspection by the representative of the MPPTCL. Manufacturer
shall indicate the manufacturing programme and the MPPTCL will have a right
to depute its inspecting officers during the manufacture. The inspecting stages
shall be Fabrication of Tank & Conservator, core building, coil winding ,
assembly of coil on core, the condition of the coil and core after the
treatment in vacuum chamber, assembly within the transformer tank
together with application of tap changer etc .
2.2.2 It may be noted that stage inspections for all the units shall be done
by us at the following stages as per the different formats enclosed :
(i) STAGE I : Stage Inspection of Transformer Tank and Conservator
after fabrication. After fabrication, tank & conservator shall be inspected for
measurement of its dimensions, thickness of sheets used and leakage test by
applying requisite pressure.
In this stage following shall be measured ,recorded & checked in Format I
(A,B,C) .
(A) Format I (A) : Inspection of Tank & Conservator
a) Certification of chemical composition and mechanical properties
of plates.
b) Welder's and weld procedure qualification.
c) Testing of electrodes for quality of base materials as per ASME.
d) Dimensional check and visual Inspection of weld .
e) Crack detection, of major strength weld seams by dye
penetration test.
f) Measurement of film thickness of inside and outside of X'mer tank
and conservator
i) Oil insoluble varnish
ii) Zinc chromate paint
iii) Light grey paint
g) Check correct dimensions between wheels, rotation of wheels
through 90 deg.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 101 of 115

h) Check for physical properties of materials for lifting lugs, jacking


pads, etc. All load bearing welds including lifting lug and jacking
parts shall be subjected to DP test.
i) Leakage test of conservator and tank.
j) Pressure and vacuum test of tank.
k) Surface cleaning by sand or shot blasting.

l) Certification of all test results.


(B) Format I (B) : Inspection of Valves as per Schedule of Valves
(C) Format I (C) : Inspection of Tank for Inspection Windows.
(ii) STAGE II : Stage Inspection of Transformer Core during Core
Building : After the core is built but before its clamping,
MPPTCL representative shall inspect the core to take complete
weight of the core and also to measure approximate core loss. If
necessary, a small strip of core shall also be taken for testing at CPRI,
Bangalore at our discretion or at any other testing lab. of repute for
measurement of specific loss .
During this stage, following documents shall be verified by our
inspector as a proof towards use of prime core material material for
manufacturer of transformer ordered by us .
i) Invoice of the supplier
ii) Mills test certificate
iii) Packing list
iv) Bill of lading
v) Bill of entry certificate by custom's.
The core material shall be directly procured either from the
manufacturer or through their accredited reputed marketing
organisation but not through any agent. A copy of all above
documents shall be sent with joint inspection report for MPPTCL
records.
In this stage, following shall be measured, recorded & checked in
Format II (A,B,C).
(A) Format II (A) : Report in respect of Raw material viz core,
copper, insulating material ,tank steel etc.: Details of various raw
material shall be recorded viz. Name of Supplier/Sub supplier, Test
Certificate, QAP Report , Invoices, Bill of Lading ,bill of entry etc.
(B) Format II (B) : Report in respect of Accessories: Details of
accessories Viz Buchholz relay, Pressure Relief device, Axles and
wheels, Winding and oil temperature indicators , Cooling fan and
radiator, Condenser Bushing & Bushing Current Transformer, OLTC,
Oil level gauge ,OLTC Cubicle and fan control cubicle, RTCC , Valves,
Clamps, Air Cell Breather, Pronol Bag etc. shall be recorded i.e. Make,
Rating, Factory Test Certificate, QAP Report , Invoices etc.
(C) Format II (C) : Inspection of Core .
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 102 of 115

a) Checking of in house or vendor core cutting facilities. Sample


testing of core steel for checking specific total loss, ductility and
bend properties, resistivity, ageing , magnetisation characteristics
and thickness.
b) Check on the quality of surface insulation & surface finish;
Measurement of thickness and hardness of varnish on stampings;
Solvent resistance test to check that varnish does not react in hot
oil; Check over quality of varnish on stamping, to ensure uniform
shining colour, no hot spots, no over burnt varnish layer and no
bubbles on varnished surface.
c) Check on the amount of burrs i.e. cutting & edge; Bow Check on
stampings.
d) During core building dimension, leaning or waviness of core,
tightening torque, dia of resiglass tap to be checked.
e) Check for the over laping stampings. Corners of the sheets are to

be apart.
f) Visual and dimensional check during assembly stage.
g) Check for interlaminar insulation between core sections after
pressing.
h) Visual and dimensional check for straightness and roundness of
core.
i) High voltage test on fully built core 2 kV for one minute
between core & yoke bolts, core & core clamps, core clamps & yoke
bolts, core loss measurement.
j) Certification of all test results.
(iii) STAGE III : Stage Inspection of Winding after their preparation
: Once the coils are prepared but before the same are fitted on to
the core, stage inspection shall be done to take various measurements
and also for weighment of total weight of coil of each voltage class.
Measurement of winding resistance shall be also done. A small piece of
conductor for each type of winding shall be made available by the
manufacturer to our representative.
During this stage, following documents shall be verified by MPPTCL
inspector as a proof towards use of prime copper and insulating material
for manufacturer of transformer ordered by us :
i) Invoice of the supplier
ii) Mills test certificate
iii) Packing list
iv) Bill of lading
v) Bill of entry certificate by custom's.
The winding and insulating material shall be directly procured either
from the manufacturer or through their accredited reputed marketing
organisation but not through any agent. A copy of all above documents
shall be sent with joint inspection report for our records.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 103 of 115

In this stage, following shall be measured, recorded & checked in Format


III.
(A) Winding:
a) Sample check on winding conductor for mechanical
properties and electrical conductivity.
b) Visual dimensional checks on conductor for scratches,
dent marks etc.
c) Sample check on insulating paper for PH value, electric
strength.
d) Check for the reaction of hot oil on insulating paper.
e) Check for the bonding of the insulating paper on conductor.
f) Check and ensure that physical condition of all materials taken
for
winding is satisfactory and free of dust.
g) Check for absence of short circuit between parallel strands.
h) Check for brazed joints wherever applicable.
i) Measurement of voltage to be carried out when core/yoke is
completely restacked and all connections ready.
j) Conductor-enamel test for checking of cracks, leakage and pin
holes.
k) Conductor-flexibility test.
l) Heat shrink test for enamelled wire.
m) Measurement of no. of turns, cross sectional area of each

winding , winding resistance and weighment of windings.


n) Certification of all test results.
(B) Insulating Material:
a) Sample check for physical & chemical properties of material.
b) Check for dielectric strength.
c) Visual and dimensional checks.
d) Check for the reaction of hot oil on insulating materials.
e) Dimensional stability test at high temperature for insulating
material.
f) Tracking resistance test on insulating material.
g) Certification of all test results.
(iv) STAGE IV : Stage Inspection of Core Coil Assembly before
Vapour Phase Drying/Dryout : In this stage , following shall be
measured, recorded & checked in Format IV.
a) Check Clamping Ring with approved drawing. Check Core Belting,
Check condition of insulation on the conductor & between the
windings.
b) Check insulation distance between high voltage & low voltage
connections with respect to earth and other parts.
c) Insulation test of core earthing .
d) Check for proper cleanliness and absence of dust etc.
e) Certification of all test results.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 104 of 115

(v) STAGE V : Stage Inspection of Core Coil Assembly after Vapour


Phase Drying/Dryout : In this stage , following shall be measured,
recorded & checked in Format V.
a) Measurement and recording of temperature and drying time during
vacuum treatment.
b) Check for completeness of drying by measuring IR values & Tan
Delta.
c) Measure minimum clearance from all sides/bottom/top.
c) Certification of all test results.
(vi) STAGE VI : Inspection of Final Assembly of Transformer after
boxing in of active material : Complete details of all bought accessories ,
their test certificates shall be appended. Minutes of meeting shall record
overall workmanship and other pertinent details.
a) Check completed transformer against approved out line
drawing, provision for all fittings, finish level etc.
b) Jacking test on all the assembled Transformers.
Pre-shipment Checks at Manufacturer's Works:
a) Check for interchangeability of components of similar
Transformers for mounting dimensions.
b) Check for proper packing and preservation of accessories like
radiators, bushings, explosion vent, dehydrating breather, rollers,
buchholz relay, control cubicle, connecting pipes, conservator etc.
c) Check for proper provision of bracings to arrest the movement
of core and winding assembly inside the tank.
d) Gas tightness test to conform tightness.
e) Derivation of leakage rate and ensure adequate reserve gas
capacity.
Installation & pre-commissioning test of Nitrogen Injection Fire
Protection System : After installation the system pre-commissioning
tests shall be carried out jointly before the system is put in service.

2.2.3 Details of Procurement : Manufacturer shall provide us complete


details of procurement of raw materials i.e. core, insulation and copper .
Manufacturer shall also record a certificate .
2.2.4 The MPPTCL also reserves the right to carry out stage
inspections at other stages also, for which advance intimation shall
be given and all necessary cooperation shall be rendered by the
manufacturer.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 105 of 115

ANNEXURE IX
LIST OF HAND TOOLS FOR SUPPLY
ALONG WITH TRANSFORMER
(A) One tool box consisting of the following 41 Hand tools of
GEDORE make or equivalent with better quality shall be
supplied
1. Spanners of different sizes
a) Open Jaw Double Ended - 8 Nos.
b) Cranked ring double ended - 3 Nos.
c) Tubular Box Double Ended - 1 No.
2. Tommy Bar - 1 No.
(For Tabular Box Spanner)
3. Adjustable Wrenches - 2 Nos.
4. Pipe Wrench - 1 No.
5. Screw Drivers Of Different Sizes - 5 Nos.
6. Flat Nose, Round Nose, Side Cutting - 3 Nos.
Pliers
7. Gasket Punches - 10 Nos.
8. Files With Handles - 2 Nos.
9. Hammers With Handles - 2 Nos.
10. Knife With Handles - 1 No.
11. Adjustable Hacksaw - 1 No.
12. Cold Chisel - 1 No.
Total 41 Nos.
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 106 of 115

ANNEXURE - X

DESCRIPTION OF EQUIPMENT FOR SCHEDULE OF RATES & PRICES


For this Bid which includes 220KV 160MVA transformers, description of main
equipments and other items should be brought out exactly as per details
furnished herein and accordingly schedule I should be enclosed with the Bid.
Item
Nos.
Description Quantity
(Nos)
1. Supply of 160MVA 220/132/33KV, Three phase ONAN/ ONAF cooled
auto transformer fitted with Pronol air-cell, Nitrogen Injection Fire
Protection System (NIFPS) as described in cl 20.9, on line
monitoring device (OLMD) as described in cl.20.10 and all
accessories/ fittings as described under annexure II , duly passed
all routine additional routine and acceptance tests as per IS-2026
with one set of tools as per annexure IX complete with first filling
of oil including wastage & 10% extra of that quantity & meeting
all technical requirement as per Part-1 of Volume II &
annexure I. The offered cost includes cost of all tests as per clause
24.5 and conforming to all requirements as described in bid
document. The transformers shall be supplied fitted with Impact

Recorder (on returnable basis) during transportation of


Transformers and Vehicle tracking system (GPRS/ GPS/ GSM
based) to track the exact position of the vehicle during
transportation of Transformers as per clause no. 36.0.
As per
price
Schedule
2 Against Item no.1 above, composite total cost of power

transformer alongwith various accessories, equipments, tool,


oil etc as well as cost of testing as described in details above,
will be furnished by the bidder. However, bidders are
requested to indicate the following unit price of items
included in composite cost mentioned under Item no. 1
above for the purpose of computation price variation after
award of contact:(a) On Line Monitoring Device
(b) Complete System of Nitrogen Injection Drain and Stir
Method type fire prevention and extinguishing system
(NIFPS) including required Nitrogen cylinders dully filled, all
piping works, Civil works with material etc.
c) Charges for fitting Impact Recorder (on returnable basis)
during transportation of Transformers and Vehicle tracking
system (GPRS/ GPS/ GSM based) to track the exact position
of the vehicle during transportation of Transformers as per
clause no. 37.0
SIGNATURE
WITH SEAL OF BIDDER
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 107 of 115

ANNEXURE XI
LIST OF VENDORS FOR MAJOR ITEMS OF TRANSFORMER
The vendors of various major items from whom procurement was made by
various suppliers of transformers and quality of which was found acceptable
are listed below. However, Major items/inputs in transformers have to
conform to highest quality standards and these items/inputs procured from
any vendors meeting the required specification would be acceptable.
No. Name of Item Supplier
1. CRGO M/s Nippon steel corporation, Japan
M/s JFE Steel corp., Japan ( Erstwhile M/s
Kawasaki Corp. Japan)
M/s AK Steel,USA
M/s Armco, USA,
M/s Posco,Korea
M/s Covefi, France
M/s Salzgittar, Germany
M/s Usinor, France
M/s Transfer, France
M/s Mitsubishi, Japan.
M/s AST Terni, Italy
M/s EBG India Pvt Limited, (Indian Agent) for M/s
GELSE NKIRCHEN, Germany
M/s British Steel Corporation , UK
M/s Thyseen Krupp Group of Companies
2.
(a)

Winding copper &


conductor
M/s Invex Filli Isolati Speciali s.p.a. Italy
M/s Sam Dong Korea
M/s Asta, Austria
M/s Smit Draad, Holland
M/s Incab Industries, Jamshedpur
M/s Sterlite Industries, Mumbai
M/s Hindalco Industries
M/s Bhandary Powerlines Private Limited (BPPL),
Manipal.
M/s BCPL Conductors Private Limited, Manideep,
Bhopal.
M/s Bhandary Powerlines Private Limited
(BPPL),Vadodara.
M/s Shakti Insulated Wires,Mumbai
M/s KSH International Pvt Limited, Taloja
M/s Delta-Trans Conductor, Mumbai
M/s Vijay Electricals, Hyderabad
M/s RIMA Transfomers & Conductors Pvt. Limited,
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 108 of 115

No. Name of Item Supplier


Bangalore.
M/s Lacroix and Kress (GMBH) germany
M/s Pirellicavi Italy
M/s Shree Cable & Conductors
M/s Chandra Metals,allahabad
(b) CTC Conductor M/s Sam Dong Korea
M/s Invex Filli Isolati Speciali s.p.a. Italy
M/s Loc Roix AND KRESS Germany
M/s Chandra Portico ltd silvassa
M/s KSH International Pvt Ltd, Chakan
3. Precompressed
press Board & press
Board components
M/s H. Weidmann, Switzerland
M/s Fige Holms Brruk, Swedan
M/s Senapathy Whiteley, Banglore
M/s Raman Board, Mysore
4. Insulating Material M/s Dupont, USA
M/s Senapathy Whiteley, Banglore
M/s H. Weidmann, Switzerland
M/s Munksio
M/s Amotfors, Sweden
M/s Krammerer
5. Air Cell M/s PRONAL, France
M/s PRONAL, Asia manufacturing SDN BHD
Malaysia
6. Gaskets M/s Talbros, Faridabad
M/s Cortica, Chennai
M/s Packing & Jointing, Chennai
M/s Indian Rubber Products, Haridwar
M/s Bombay Oil Seal Mfg. Mumbai

M/s MGM Rubber Kolkata


M/s Bharat Corrub Industries, Vadodara.
M/s Indian Cork Industries,Bahadarpur
M/s Nucork, Gurgaon
7. OIP Condensor
bushing
M/s BHEL
M/s CGL
M/s TELK
M/s ASEA-MICAFIL
M/s Passonivilla
8. Terminal Connector M/s Best & Crompton, Chennai
M/s PeeVee Engg., Bangalore
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 109 of 115

No. Name of Item Supplier


M/s Milind Engg., Mumbai
M/s Nootan, Baroda
M/s Utsav, Baroda
M/s Vinayak and Co., Mumbai
M/s Megha Engg. Enterprises, Chennai
M/s Klemmen Engg. Corporation , Chennai
9. OTI/WTI with
repeater
M/s Accurate Control,UK
M/s AKM, Swedan
M/s Perfect Control, Chennai, India
M/s Preci Measure, Banglore
M/s Radix Electrosystems Pvt. Ltd/ Radix Pyrotech
India
10. Magnetic oil gauge M/s Sukrut Udyog, Pune
M/s Yogya, Jhansi
11. Buchholz Relay &
Oil surge relays
M/s Fukuda Instrument, Japan
M/s Atvus,Calcutta
M/s English Electric, Chennai
M/s Prayog; M/s BHEL
M/s Instrument and Control, Vadodara
12. Pressure Relief
Device
M/s Qualtrol, USA
M/s GE, USA;
M/s Sukrut Udyog, Pune
M/s ATVUS Industries, Kolkatta
13. Fan & Motor M/s Marathon Electric Motors (India) Ltd, Kolkata
(Erstwhile M/s Areva, (Alstom), Kolkata)
M/s CGL, Mumbai
M/s Khaitan,Calcutta.
M/s EPC, Calcutta
14. Un-impregnated
Densified laminated
wood
M/s Permali Wallace Bhopal

M/s Kit ply Assam


M/s Mysore Polymers Banglore
M/s Narmada Forest Ind. Pvt. Ltd. Bhopal.
M/s Western India Plywood , Kerala
15. Valves M/s Leader
M/s Bombay Metal & Alloys
M/s Audco
M/s Petson
M/s Manixon
M/s Creseant
M/s Precision Engg. Kottayam,
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 110 of 115

No. Name of Item Supplier


M/s Eapen Joseph, Kottayam
M/s Apex Piping Systems, Jalandhar
M/s Liberty Engg., Mumbai
M/s Niton Valves, Mumbai
M/s Eapen Joseph & co., Coimbatore
M/s GG Valves ,Udaipur
16. MCB Ms Siemans
M/s MDS
M/s S&S
M/s Havell's
17. Fuse M/s Siemens/ S&S / Areva / Havell's
18. Tank Steel M/s SAIL
M/s Essar
19. OLTC Complete M/s BHEL
M/s TELK
M/s Easun, Madras
20. Terminal Blocks M/S ELMEX
M/S Technoplast,
M/S Tosha
21. Silica gel Breather M/S Yogya Enterprises, Jhansi.
M/S Anusen Industries, Pune.
M/s Instruments & Controls , Vadodara, India
22. Transformer oil M/s Apar Limited, Mumbai
M/s Savita Chemicals Ltd, New Mumbai
23. Radiator M/s CTR Manufacturing Industries, Pune
M/s Thermal Transformer Product, Bangalore
M/s Exotherm, Bangalore.
M/s P.E. Engg. Hyderanad.
M/s Hitech Switchgear, Mumbai
24. On Line Monitoring
Device
M/s Kelman, UK
25 NIFPS M/s CTR , Pune
26. Oil flow indicator M/s Sukrut Udyog, Pune
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 111 of 115

APPENDIX I
Calculation for Hot Spot winding temperature for EHV transformers
Overloading capability of the transformer and also the loading
capability of transformer with and without cooling fans (coolers) for a

short period of 10/20 minutes with out exceeding temperature rise of


winding beyond specified limits have been indicated in the technical
specification. In this regard following calculation based on maximum
ambient air temperature as 50 degree centigrade and maximum
yearly average weighted air temperature as 32 degree centigrade
using the under mentioned formulae or any other authentic formulae
shall be furnished.
-t/ 2y
c = a + b0 + ( b- bo) ( 1- e ) + ( c - b ) k
2x

( 1+dk )
b = br ------------- ( 1+d) x
Where
a = Weighted ambient temperature (cooling medium)
c = Winding hot-spot temperature at K load = a +
c
cr = Winding hot-spot temperature at rated load
c = Winding hot-spot temperature rise at K load
cr = Winding hot-spot temperature rise at rated load
bo = Original oil temperature
b = Top oil temperature at K load = a + b
br = Top oil temperature at rated load
b = Top oil temperature rise at load K
br = Top oil temperature rise at rated power
t = Time duration in hours of any load power
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 112 of 115

= Oil air thermal time constant of transformer at rated


load, in hours
K = Ratio of any load/rated load = S /Sr
K1 = Ratio of initial load/rated load = S1 /Sr
K1 = Ratio of permissible load/rated load = S2 /Sr
K2 = Ratio of permissible load/rated load
x = Exponent for oil rise
y = Exponent for winding rise
d = Ratio of load loss at rated load/no load loss.
a = Subscript representing ambient (cooling medium)
b = Subscript representing top oil
c = Subscript representing hot-spot of winding
r = Subscript representing rated value.
SIGNATURE
WITH SEAL OF BIDDER
Volume-II, Part-4
MPPTCL/TECH/PROC/04/July13 Page 113 of 115

APPENDIX II
TECHNICAL PARTICULARS TO BE FILLED-IN BY BIDDER
S. No. Particulars Values
1 Maximum flux density (Tesla)
2 Maximum current density (Amp/sq.cm)
3 Magnetising current (mA)
4 Short time current rating (Amp.)
5 Losses
a. No load Losses (KW)
b. Load Losses including stray losses

(KW)
c. Auxiliary losses (KW)
6 Impedance voltage (Percentage)
7 Weight of copper (Kg)
8 Weight of core (Kg)
9 Weight of core + winding (Kg)
10 Quantity of oil
a. For first filling including wastage
(KL/Kg)
b. 10% extra of a (KL/Kg)
11 Total weight of Transformer. (Kg)
12 Transport weight of main tank
a. with oil (Kg)
b. without oil (Kg)
SIGNATURE
WITH SEAL OF BIDDER
Volume-II, Part-4

MPPTCL/TECH/PROC/04/July13 Page 114 of 115

List of Abbreviation used in technical specification


1. OLTC - On load tap changer
2. OIP - Oil impregnated paper
3. DL type - Draw lead type
4. COPS - Conservator oil preservation system
5. RTCC - Remote tap changer cubicle
6. Cl - Clause
7. IEEMA - Indian Electrical & Electronics Manufacturing
Association
8. KV - Kilo voltage
9. KW - Kilo Watt
10. IV - Intermediate voltage
11. LV - Low voltage
12. VPD - Vapour phase drying
13. ONAN - Oil natural air natural
14. ONAF - Oil natural air forced
15. OFAF - Oil forced air forced
16. CBIP - Central Board of Irrigation and Power
17. OTI - Oil temperature indicator
18. WTI - Winding temperature indicator
19. KA - Kilo Ampere
20. TC - Terminal connector or test certificates as
applicable
21. V - Voltage
22. f - Frequency
23. VN - Normal voltage
24. FN - Normal frequency
25. CT - Current Transformer
26. PT - Potential Transformer
27. Xmer - Transformer.
28. PRD - Pressure Relief Device
29. PRV - Pressure Relief valve
30. MOLG - Magnetic Oil Level Gauge

31.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.

OSR - Oil Surge Relay


Isc - RMS value of symmetrical short ckt current,KA
V - rated voltage of system ,KV
Zt - short ckt impedance of transformer ,Ohms
Zs - short ckt impedance of system ,Ohms
1 - final temperature in degree centigrade
0 - Initial temperature in degree centigrade
J - short ckt current density ,amp/mm sq.
t - duration of short ckt in secs
Iph - rated phase current in amps
Zpu - per unit impedance

Volume-II, Part-4

MPPTCL/TECH/PROC/04/July13 Page 115 of 115

47. Rdc - DC resistance of the per phase of winding at 75


degree centigrade
48. Hw - height of winding in cm
49. N - no of turns per phase of winding
50. Dmi - mean diameter of inside winding ,cm
51. Bi - thickness of inside winding conductor ,cm
52. E - modulus of elasticity of conductor, cm
53. Sn - rated KVA
54. Pu - per unit impedance
55. Fa - axial imbalance force, Kg
56. Ai - (no of spacers x length x width ) for inner
winding
57. Ao - (no of spacers x length x width ) for outer
winding
58. m - no of conductors in the radial direction= no of
turns x no of parallel conductor
59. bo - thickness of outer winding conductor, cm
60. Dmo - mean diameter of outer winding, cm
61. Ao - supported area of outer radial spacers
62. F - total axial force in MT
63. D - mean diameter of clamping ring ,cm
64. b - width of clamping ring ,cm
65. t - thickness of clamping ring ,cm
66. n - no of jacking or clamping points
67. mA - milli ampere
68. kg - kilogram
69. kl - kilolitre
70. temp. - temperature
71. max. - maximum
72. min. - minimum
73. vol. - volume

MADHYA PRADESH POWER TRANSMISSION CO. LTD.

SHAKTI BHAWAN RAMPUR: JABALPUR

VOLUME II
PART-5
Technical Book Serial No.
MPPTCL/TECH/PROC/05/June13

TECHNICAL SPECIFICATION FOR SUPPLY


OF EHV EQUIPMENTS AND MATERIAL FOR
SUB-STATIONS AND FEEDER BAYS

O/o CHIEF ENGINEER (PROCUREMENT)


MPPTCL, JABALPUR
Volume-II contains eight booklets as under:Section Description Technical Book
Serial No.
Part-1 TECHNICAL SPECIFICATION FOR
SUPPLY OF 400KV/220KV, 315MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/01/JULY13
Part-2 TECHNICAL SPECIFICATION FOR
SUPPLY OF 400KV/132KV, 100MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/02/JULY13
Part-3 TECHNICAL SPECIFICATION FOR
SUPPLY OF 400KV, 125MVAR REACTOR
MPPTCL/TECH/
PROC/03/JULY13
Part-4 TECHNICAL SPECIFICATION FOR
SUPPLY OF 220KV/132KV, 160MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/04/JULY13
Part-5 TECHNICAL SPECIFICATION FOR
SUPPLY OF 220KV/33KV, 50MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/05/JULY13
Part-6 TECHNICAL SPECIFICATION FOR
SUPPLY OF 132KV/33KV, 63MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/06/JULY13
Part-7 TECHNICAL SPECIFICATION FOR
SUPPLY OF 132KV/33KV, 40MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/07/JULY13

Part-8 TECHNICAL SPECIFICATION FOR


400/220/132/33KV EQUIPMENTS
( 3 BOOKLETS)
MPPTCL/TECH/
PROC/08/JULY13
MPPTCL/TECH/
PROC/09/JULY13
MPPTCL/TECH/
PROC/10/JULY13

All the above eight booklets are in the form of separate


books. This book refers to:-

PART-4
TECHNICAL SPECIFICATION FOR 220/33 KV, 50 MVA
POWER TRANSFORMERS
Please note that the modifications in technical specifications
are indicated in Appendix-1, enclosed in Volume-I of the
Tender document.
Contents
Description of document Page No.
Technical specification for transformer 1-72
Annexures and appendix for 220KV, 50MVA Power Transformer
Annexure I - Principal Technical particulars 72-75
Annexure II - List of Fittings and Accessories 76-80
Annexure III - Test certificates to be furnished for
accessories 81-84
Annexure IV - Schedule of Inspection Windows 85
Annexure V - Schedule of Valves 86-87
Annexure VI(A)- Drawings & Data to be furnished 88-90
Annexure VI(B)- List of drawings to be furnished
alongwith bid
91
Annexure VII - Calculations required to be furnished 92-95
Annexure VIII - Details of Inspection Program 96-100
Annexure IX - List of Hand Tools and Jacks 101
Annexure X - Description of equipment for schedule of
rates & prices
102
Annexure XI - List of vendors for major items of
transformer
103-106
Appendix I - Calculation for Hot Spot winding
temperature for EHV transformers
107-108
Appendix II - Technical particulars to be filled-in by
bidder
109
List of abbreviations used in technical specification 110-111

MPPTCL/TECH/PROC/05/JUNE13 Page 1 of 111

VOLUME II, PART-5

TECHNICAL SPECIFICATION FOR 50 MVA ,


220/33 KV POWER TRANSFORMERS
1.0 SCOPE
1.1 This specification covers design, engineering, manufacture,
assembly, stage inspections and testing before supply and delivery
including unloading on plinth at our substation sites located anywhere in
the state of Madhya Pradesh. The 220/33KV, 50 MVA three phase transformers
complete with all fittings, accessories, associated equipment including oil for
first filling including wastage & 10% extra of that quantity specified herein
which are required for efficient and trouble free operation as specified
hereunder.
1.2 It is not the intent to specify completely herein all the details of the
design and construction of equipment. However, the equipment shall conform
in all respects to high standards of engineering, design and workmanship
and shall be capable of performing the duties specified herein. The offered
transformers shall be complete with all components necessary for their
effective and trouble free operation. Such components shall be deemed to be
within the scope of Bidders supply irrespective of whether those are specifically
brought out in this specification or not. The transformers should be free
from Polychlorinated Biphenyls (PVB/PCB).
1.3 The Purchaser will interpret the meanings of drawings and
specification and shall have the power to reject any work or material
which, in his judgment is not in accordance therewith. The offered
transformers shall be complete with all components necessary for their
effective and trouble free operation. Such, components shall be deemed to be
within the scope of Bidders supply irrespective of whether those are specifically
brought out in this specification and/or the commercial order or not.
2.0 STANDARDS
2.1 The transformers and associated accessories shall conform to the
latest issues/amendments of standards as given below, and report of the
committee for standardization of the parameters and specification of class 220
KV equipment, except to the extent explicitly modified in this specification.
Transformers conforming to any other authoritative standards meeting better
quality and ensuring better performance are also acceptable. Bidder shall
specifically indicate deviations if any from the INDIAN STANDARDS.
MPPTCL/TECH/PROC/05/JUNE13 Page 2 of 111

THE APPLICABLE INDIAN/INTERNATIONAL STANDARDS FOR POWER


TRANSFORMERS AND ASSOCIATED ACCESSORIES ETC.
INDIAN
STANDARD
NUMBER
TITLE
INTERNATIONAL
AND
INTERNATIONALLY
RECOGNISIED
STANDARD
IS-2026 (Part 1
to 5 )
Power Transformers IEC-60076(Part I to 5)
CBIP Publi-cation
No.295

Manual on Power Transformers


IS-335 Insulating oil for transformers IEC-296,BS-148.
IS1866-2000 Electrical maintenance and Supervision
of mineral insulating oil in equipment.
IS-2099 Bushings for alternating Voltage above
1000V.
IEC-60137(2008)
IS-2312 Fans (Cooler fans)
IS-2705. Current Transformers. IEC 60044
IS-325. Three phase Induction motors. IEC-34.
IS-375 & IS996
Marking & arrangements for switch
gear, bus bars, main connections &
auxiliary wiring.
IS-3637. Gas & oil operated relays.
IS-10028 (Part
1to3)
Code of practice for installation and
maintenance of transformers.
IS-2147. Degree of protection provided by
enclosures for low voltage switch gear
and control.
IEC 60529,IEC60947
IS-5. Colors for ready mix paints.
IS-6272 Industrial cooling fans.
DOC.ETD16
(3703)
Draft standard by BIS for revision of IS6600 for Guide for loading of oil
immersed transformers.
IEC 60354
OLTC IEC 60214
IS 8478 Application Guide for OLTC IEC 60542
IS 10561 Application Guide for Power
Transformer.
IEC 60076-8
IS 13964 Method of measurement of Transformer
Sound levels.
NEMA-TR1
IS 2071 (Part 1
to 3)
Methods of High Voltage Testing IEC 60060
IS 6209 Methods for Partial Discharge
Measurements
IEC 60270
IS 2165 Insulation Coordination IEC 60071
MPPTCL/TECH/PROC/05/JUNE13 Page 3 of 111

INDIAN
STANDARD
NUMBER
TITLE
INTERNATIONAL
AND

INTERNATIONALLY
RECOGNISIED
STANDARD
IS 5561 Terminal connectors
Short Circuit Current calculation of
effects
IEC 865(part I & II)
IS-5553 Shunt Reactors, Neutral/Earthing
Reactor and Arc Suppression Coil
IEC 60289
IS:335 Insulating oils for transformers and
switchgears
IEC:60296, BS:223
IS -1886 Code of practice for installation and
maintenance of transformers.
Supervision and Maintenance guide for
Mineral Insulating Oil in Electrical
Equipment
IEC 60422
Method of Sampling of Liquid dielectrics IEC 60475
Guide for the Sampling of Gases and of
Oil from Oil-filled Electrical Equipment
for the Analysis of Free and Dissolved
Gases
IEC 60567
Digital Recorders and Software for High
Voltage Impulse testing
IEC 61083
Specification for radio disturbance and
immunity measuring apparatus
CISPR 16
Guidelines for conducting design reviews
for transformers 100 MVA and 123 kV
and above.
Cigre Publication 202
Metal oxide surge arrestors without
gaps
IEC 99-4
Selection and application
recommendation
IEC 99-5
Indian Electricity Rule 1956
2.2 In case equipment conforms to other International standards which
ensure equivalent or better performance than specified under cl 2.1 then
the English version of such standards or the relevant extracts of same shall
be forwarded with the bid and the salient features of comparison shall be
brought out separately.
2.3 The electrical installation shall meet requirements of Indian
Electricity Rules, 1956 and IS-1886,"Code of practice for installation &
maintenance of Transformers" as amended till date.
2.4 It has been experienced that the weight of core lamination, weight of
copper, weight of steel, weight of Transformer Tank along with Fittings and
MPPTCL/TECH/PROC/05/JUNE13 Page 4 of 111

Accessories and quantity of oil for first filling including wastage & 10% extra

of that quantity, total weight of core + winding after assembly and total
weight of transformer are indicated in the technical bid by the manufacturers
on tentative basis and at the time of submission of drawing, wide
variations in these quantities take place. This is not in order and it will
be obligatory on the part of the Bidder to ensure that all these details are
worked out carefully and only correct figures after proper design are offered in
the technical bid. It may be noted that at the time of submission of final
drawings, variation in these weights beyond the limits of (+) 5% shall not be
permitted.
2.5 It will also be obligatory on the part of the Bidders to furnish details
of calculations for quantity (weight & size) of core material, quantity (weight
& size) of copper material, calculations for thermal and dynamic short circuit
withstand capability of transformer, calculations for pressure relief valve,
adequacy of size of AIRCELL Bag, volume of oil for adequate cooling with
calculations of size of conservator and other details as called for in the
specification. Furnishing of these calculations along-with technical bid is a
must. All the data should be supported with calculation details. In addition,
calculations for no. of thermosyphon filter and their adequacy be furnished.
2.6 Interconnection : The transformers are meant for service as
interconnecting transformers and shall be capable of being energized either
from 220 KV side or 33 KV side. The power transformer shall be capable of
being loaded at rated power on the 220 KV and 33 KV sides. On Load Tap
Changer shall be suitable for such operation. The OLTC shall be suitable for
bidirectional flow of power.
3.0 SERVICE CONDITIONS
3.1 Climatic Conditions : The transformers and its accessories to be
supplied against this specification shall be suitable for satisfactory continuous
operation under the following tropical conditions.
1. Location At various substations within
the State of Madhya Pradesh
2. Max. Ambient air temp. (oC) 50
3. Min ambient air temp (oC) -5
4. Maximum daily average ambient air
temperature(oC)
40
5. Maximum yearly weighted average
temperature (oC)
32
6. Maximum Relative humidity (%) 95 (sometimes reaches
saturation.)
7. Average annual rainfall (cm) 125
8. Max. Wind pressure (Kg/sq.m.) 150
9. Max. Altitude above mean sea level
(Metres)
1000
MPPTCL/TECH/PROC/05/JUNE13 Page 5 of 111

10. Isoceraunic level (Average number of


thunderstorm days per year)
50
11. Seismic level (horizontal acceleration) 0.3g
Moderately hot and humid tropical climate, conducive to rust and
fungus growth. Tropical Protection Shall conform to IS:3202 titled climate
proofing of electrical equipments and BS: 1014 : titled protection of electrical
power equipments against the climatic condition. The transformer tank

fittings and radiators including all accessories shall be designed to withstand


seismic acceleration equivalent to 0.3 g. Special precautions shall be taken to
prevent mal-operation of Buchholz relay under such condition.
3.2 Auxiliary Power Supply : Auxiliary electrical equipment shall be
suitable for operation on the following supply system.
a. Power Devices
(like drive motors)
0.4 KV, 3phase, 4wire 50Hz. neutral grounded AC
supply.
b. DC Alarm,
control &
protective
devices
220V or 110volts DC, ungrounded 2wire
(Substation wise exact details shall be furnished to
the successful Bidder).
c. Lighting. 230V, single phase, 50Hz. AC supply.
Bidders scope include supply of interconnecting cables, terminal
boxes etc. The above supply voltage may vary as indicated below and all
devices shall be suitable for continuous operation over the entire range of
voltages.
i) AC supply : Voltage Variation of 25% to +10%; Frequency
+/- 4%
ii) DC supply : Voltage Variation of -20% to + 10%.
All accessories requiring AC or DC supply shall perform
satisfactorily for voltage variation as above.
4.0 GENERAL TECHNICAL REQUIREMENTS
4.1 Duty Requirements
a) The transformers and all its accessories like CTs etc., shall
be designed to withstand without injury, the thermal and
mechanical effects of any external short circuit to earth and of
short circuits at the terminals considering infinite bus
arrangement of values specified as under :
220KV - 40KA for 3 secs.
33KV - 31.5KA for 3 secs.
MPPTCL/TECH/PROC/05/JUNE13 Page 6 of 111

b) Over Loading : The transformer shall be capable of being


loaded in accordance with IS:6600. There shall be no limitation
imposed by windings, bushings, tap changer etc. of
transformer. Transformer & all its accessories shall be liberally
rated to allow 10% over loading at all taps on continuous basis
without exceeding the temperature limits specified in clause
6.0.
The transformer shall be capable of being operated without
danger on each tapping at the rated KVA with specified voltage
variation corresponding to the voltage of that tapping with
normal temperature rise. The design adopted to achieve this
shall be indicated in detail in the Bid.
Transformer shall be capable of operating under the natural
cooled condition up to the specified load i.e. as ONAN rating.
The forced air cooling equipment shall come into operation
by pre-set contacts of winding temperature indicator and the
transformer shall operate as a forced air cooled unit i.e. as
ONAF. Cooling shall be so designed that during total failure of

power supply to cooling fans, the transformer shall be able to


operate at full load for Ten(10) minutes without the calculated
winding hot spot temperature exceeding 140 deg.C. Also
stopping of two cooling fans should not have any effect on the
cooling system. Transformers fitted with two coolers (cooling
banks) each capable of dissipating 50 per cent of the loss at
continuous maximum rating shall be capable of operating for
20 minutes in the event of failure of the blowers associated
with one cooler, without the calculated winding hot spot
temperature exceeding 140oC at continuous maximum rating.
c) Over Voltage : The transformers shall be capable of being
operated on continuous basis at 10% excess voltage than
the rated voltage specified at each tap.
4.2 Radio Interference & Noise Level
4.2.1 The transformers shall be designed with particular attention for
suppression of maximum harmonic voltage especially the third and fifth so
as to eliminate wave form distortion and minimize interference with
communication circuits.
4.2.2 The noise level, when energized at normal voltage and frequency
with fans running shall not exceed, when measured under standard conditions,
the values specified in NEMA,TR-I.
4.3 Stresses : Transformer shall be capable of withstanding Electrical,
thermal and mechanical stresses on any winding caused by forces due to
symmetrical or asymmetrical external fault.
MPPTCL/TECH/PROC/05/JUNE13 Page 7 of 111

4.4 Frequency & Magnetic Induction


4.4.1 The transformers shall be suitable for continuous operation for a
frequency variation of (+) plus (-) minus 4% from normal 50Hz without
exceeding the specified temperature rise. For considerations of over fluxing,
the transformer shall be suitable for continuous operation for values of over
fluxing factor up to 1.1.
V FN
The over fluxing factor being { -- x -- }
VN F
4.4.2 The working flux density shall not exceed 1.65 Tesla for offered no
load losses and the maximum flux density in any part of core and yoke at
110% rated voltage combined with (-) 4% frequency variation shall
preferably not exceed the value of 1.90 Tesla as per CBIP manual no 295.
For manufacturing of Power transformer, core laminations of various
specifications are available and therefore while selecting the working flux
density, the Bidders will have to comply with the requirements of cl.4.4.1 &
4.4.3.
4.4.3 For the selected flux density, the transformer shall have
minimum of following over fluxing capabilities , such that while meeting
the above requirement saturation of transformer core shall not take place
under any circumstances. Transformer shall accept, without injurious
heating, combined voltage & frequency fluctuation, which produces the
following over fluxing conditions :
Over Fluxing
Factor
Period
1.50 Less than 2 seconds
1.40 5.0 seconds
1.25 60 seconds

1.10 Continuous
The Bidder shall also indicate 160% & 170% over voltage/over
fluxing withstand capability period. Over fluxing withstand characteristics up to
170% shall be submitted along with the bid.
4.4.4 Detailed calculations for maximum flux density and magnetizing
current for core material shall be furnished to substantiate the above
requirement. The Bidder shall enclose details of Core Material with thickness
of lamination, type designation and source of raw material and its
characteristic curves. All characteristic curves of material including Voltage Vs
Flux Density and Loss per Kg Vs Flux Density are to be enclosed with Bid
clearly indicating Flux Density selected for calculation of core losses (No load
loss). On the basis of these data, for the Flux Density and core material
chosen verification of Saturation Flux Density shall be done by the purchaser,
to know the margin considered in operating Flux Density .
MPPTCL/TECH/PROC/05/JUNE13 Page 8 of 111

4.4.5 The maximum current density for design of power transformers


within specified limits of transformer losses shall not exceed the limits of 300
amps per sq.cm.
4.4.6 All other requirement of magnetic circuit shall be as per latest issue
of CBIP Manual no 295.
4.4.7 The transformers shall be either core type or shell type
construction, oil immersed, ONAN/ONAF with external heat exchangers
and shall be suitable for outdoor service as inter connecting and/or stepdown
transformers suitable for parallel operation with the existing
transformer having tertiary winding already in service at the EHV substation
where these transformers are to be commissioned. The rating and electrical
characteristics of the transformers shall be strictly as specified in this
specification. For matching the parameters required for parallel operation with
existing unit, details shall be intimated to successful Bidder.
4.5 All the transformers shall be suitable for continuous operation with
frequency variation of +/- 4% from normal 50 Hz . Combined voltage &
frequency variation should not exceed the rated V/f ratio by 10 %.
5. INSULATION
5.1 Impulse & Power Frequency Voltage Withstand Values : For
rated system voltage of 33KV & 220KV following minimum power frequency
and impulse withstand voltage should be offered for the windings.
System
Voltage
Highest
System
Voltage
Power Frequency
Withstand
Voltages
Impulse
Withstand
Voltage
33KV 36KV 95KV rms 250KVp
220KV 245KV 395KV rms 950KVp
5.2 The HV/LV winding of the transformers shall have graded
insulation. The insulation class of the neutral end of the winding shall be
graded to 95 KV. The 33KV winding shall have full insulation for 33KV i.e.
250 KVp impulse and 95KVrms power frequency.
6.0 TEMPERATURE RISE : Each transformer shall be capable of

operating continuously at its normal rating & 10% over load condition
without exceeding temperature limits as specified below. The maximum
ambient temperature shall be taken as 50 degree C and type of cooling be
suitably adopted to limit the temperature rise within the safe limit of operation.
Type Of Cooling Temperature-Rise
Windings Oil
MPPTCL/TECH/PROC/05/JUNE13 Page 9 of 111

ONAN (Air natural). 50oC 45oC


ONAF (Air blast/forced) 50oC 45oC.
7.0 FREQUENCY : All the transformers shall be suitable for continuous
operation with a frequency variation of + 4% to -4% from normal 50 Hz
without exceeding the specified temperature rise.
8.0 IMPEDANCE : The percentage impedance of the power transformer
shall be 10% on 50 MVA base. Tenderers shall indicate the guaranteed
impedance, tolerances and also the impedance on all taps for the offered
transformers. Impedance shall include positive and zero sequence and shall
be expressed in terms of the branches of the star connected equivalent
diagrams on all the specified MVA base and the range shall be given for each
branch of the equivalent circuit turn. It may be noted that if required the
percentage impedance should be designed identical to the existing
transformer of any make in case parallel operation is desired. The IS
tolerance on all matching taps are acceptable. Confirmation regarding
requirement of parallel operation should be given in the Tender.
It may be noted by the Tenderers that for the purpose of
matching impedance of transformer included in scope of this Tender
between 220KV & 33KV windings, the Tenderers are not permitted to use
reactor or reactor/capacitor assembly. The design of the main winding should
take care of the requirement of impedances as specified in this Tender
document and for this purpose, no reactor or reactor/capacitor should be
used.
9.0 GUARANTEED LOSSES AND PENALTY
9.1 Maximum Losses : While the Bidders may offer their own design, it
may be noted that the transformer losses at 75 deg. C. at rated output, rated
Voltage and rated frequency should not exceed the following maximum limits
which include tolerances as per IS :
a) No load losses (Iron losses). : 27 KW
b) Load(Copper losses) + Auxiliary losses. : 150 KW
including stray loss in KW
9.2 The no load losses in kilowatts ( including BIS tolerance ) at rated
voltage and rated frequency and the total load losses in kilowatts at rated
output, rated voltage and rated frequency at 75oC shall be guaranteed by
the bidder. It may be noted that the losses of the Transformer shall not
exceed during final testing of the transformer, if the same exceeds from the
maximum ceiling limit of Transformer losses as detailed in 9.1 above then the
Transformer shall not be accepted.
9.3 Heat run Test:
MPPTCL/TECH/PROC/05/JUNE13 Page 10 of 111

One 50 MVA 220KV power transformer of each manufacturer (if there


are more than one manufacturer) shall be subject to heat run test
(Temperature rise test).
10.0 COOLING : The Bidder may offer ONAN / ONAF type of cooling
for these transformers. The ONAF rating for each transformer winding of
220/33 KV transformers shall be 125% of ONAN rating achieved by cooling.
The ONAF cooling shall be in two groups each of 50% capacity. Adequate
no. of standby cooling fans shall be provided for 20% additional cooling per

bank, in line with requirement indicated in clause 15.1 ( C ).


11.0 CONSTRUCTION DETAILS : The features and construction details
of power transformer shall be in accordance with the requirements stated
hereunder
11.1 Tank
(A) As required in CBIP specification, the tank shall be of Bell type
construction for 50 MVA transformers covered under this
specification. Top cover of Bell type construction shall be welded
to the tank body .
(B) Tank shall be of welded construction and fabricated from
tested quality low carbon steel suitable for welding & of
following minimum sheet thickness.
Tank cover - 20 mm, sides including inspection covers - 10
mm, Base-20 mm.
(C) All seams and those joints not required to be opened at site
shall be factory welded and wherever possible they shall be
double welded. After completion of tank construction and
before painting, 'Dye Penetration Test' shall be carried out on
welded parts of jacking bosses, lifting lugs and all load
bearing members.
(D) Tank stiffeners shall be provided for general rigidity and these
shall be designed to prevent retention of water.
(E) The tanks shall be designed to withstand the following without
permanent distortion.
(i) Mechanical shocks during transportation.
(ii) Vacuum filling of oil at 10 milli torr in transformer with
all fittings.
(iii) Continuous internal pressure of 35 kN/m2 over normal
hydrostatic pressure of oil.
(iv) Short circuit forces &
(v) Under seismic condition /events both horizontal/vertical .
(F) Where ever possible, the transformer tank and its accessories
shall be designed without pockets wherein gas may collect.
MPPTCL/TECH/PROC/05/JUNE13 Page 11 of 111

Where pockets can not be avoided, pipes shall be provided to


vent the gas into the main expansion pipes if any.
(G) The shields shall be such that no magnetic fields shall exist
outside the tank. They shall be of magnetically permeable
material. If required impermeable shields shall be provided at
the coil ends. Tank shield shall not resonate when excited at the
natural frequency of the equipment.
(H) The tank shall be provided with :
(i) Lifting lugs suitable for lifting the equipment complete
with oil.
(ii) A minimum of four jacking pads in accessible position at
500mm height to enable the transformer complete with oil
to be raised or lowered using hydraulic or screw jacks.
The location of jacking pads shall be such that there should
not be any interference with the civil foundation of rails in
either direction i.e. longitudinal or transverse.
(iii) Suitable haulage holes shall be provided.
(I) (i) Inspection cover/access windows & Manholes:
Suitable man-hole with a welded flange and a properly
gasketted bolted cover having of minimum thickness of 10

mm shall be provided on the tank cover. The man- hole


shall be of sufficient size to offer easy access to the
lower ends of the bushings, terminal etc. The
requirement of inspection windows and manholes have
been stipulated in Annexure-IV & Bidders have to
confirm compliance of the same in their Bid.
(ii) Space for free movement in Transformer Tank for
inspection:
Details of passage & free space provided inside the main
tank should be indicated in concerned drawing to allow
free movement of at-least two persons for inspection of
active parts etc. To be more specific it may please be
noted that minimum clearance from outer most
winding/connection leads/supports to tank shall
not be less than 300 mm. on all 4 sides with suitable
platform on bottom of the tank to facilitate free
movement of person all around inside the tank.
(J) All bolted connections to the tank shall be fitted with
suitable oil tight neoprene/nitrile gaskets which shall give
satisfactory service under all operating conditions. Special
attention shall be given to the methods of making the hot oil
tight joints between the tank and the cover as also between
the cover and the bushings and all other outlets to ensure that
the joints can be remade satisfactorily and easily with the
help of semi skilled labour. Where compressible gaskets are
MPPTCL/TECH/PROC/05/JUNE13 Page 12 of 111

used, stoppers/ runners shall be provided to prevent over


compression.
(K) Suitable guides shall be provided for positioning the various
parts during assembly or dismantling. Adequate space shall
be provided between the cores and windings assembly and the
bottom of the tank for collection of any sediment.
(L) The design of the tank, lifting lugs shall be such that the
complete transformer assembly filled with oil can be lifted with
the use of these lugs without any damage or distortions.
(M) For the complete transformer we have clearly brought out our
requirement of various types of valves in Annexure V
enclosed brings out details of type, size and quantity of valves
which are to be provided at various locations. This requirement
has to be confirmed by the Bidders without any deviation.
(N) It may be noted that all gasketted joints shall be grooved one
using O rings of nitrile rubber or better, such as the joints
between bushing turret and bushing flange, inspection covers
of inspection windows and all other openings provided for the
purpose of inspection of internal parts of the transformer etc.
The main bell tank gasket between upper tank and bottom tank
shall be single piece O ring cord/gasket of nitrile rubber or
material of better quality. The gasketting arrangement shall be
grooved one with proper stopper to avoid over compression. It
is to be noted that one additional set of gaskets shall be
delivered by the tenderer alongwith transformer to replace the
used gaskets at the time of erection of the unit.
(O) One detachable bolted type mild steel (MS) ladder with anticlimbing
arrangement shall be provided. Ladder for climbing up

to & over top cover of power transformers shall be mechanically


sturdy enough to bear the load of healthy maintenance staff
without any shake/jerks. The arrangement shall not be
detached after erection and commissioning of the unit, hence
shall be provided with padlock locking arrangement for anticlimbing
device. On the upper top of the ladder, provision for
support shall be made. However, the arrangement of the
ladder shall be to purchasers approval. Collapsible ladder shall
not be acceptable to us.
(P) Suitable earthing bridge between upper and lower tank shall be
provided at least on two places each on HV & LV side and one
place on other both sides.
11.2 Tank Cover
(a) The tank cover shall be sloped to prevent retention of rain
water and shall not distort when lifted.
MPPTCL/TECH/PROC/05/JUNE13 Page 13 of 111

(b) Inspection cover/man holes shall be provided as per


Annexure-IV.
(c) The tank covers shall be fitted with pockets at the position
of maximum oil temperature of MCR (Maximum Continuous
Rating) for inserting bulbs of oil and winding temperature
indicators. It shall be possible to remove these bulbs
without lowering the oil in the tank. The thermometer shall be
fitted with a captive sensor to prevent the ingress of water.
(d) Bushings, turrets, covers of inspection openings,
thermometer, pockets etc., shall be designed to prevent
ingress of water into or leakages of oil from the tank.
(e) All bolted connections shall be fitted with weather-proof, hot
oil resistant gasket in between, for complete oil tightness.
If gasket is compressible, metallic stoppers shall be provided to
prevent over-compression.
(f) A minimum of three nos. PRD shall be provided above each
phase winding.
11.3 Undercarriage
(a) The transformer tank shall be supported on a structural steel
base equipped with forged steel or cast steel single flanged
wheels suitable for moving the transformer completely filled
with oil.
(b) Jacking pads/steps shall be provided. It shall be possible to
change the direction of the wheels through 90 deg. when the
transformer is lifted on jacks to permit movement of the
transformer both in longitudinal and transverse direction.
(c) The track/rail gauge shall be 1676 mm along the longer side,
as well as along the shorter axis. However Rails shall be placed
perpendicular to the bushing line.
(d) Pulling eyes shall be provided to facilitate movement/pulling of
the transformers and these shall be suitably braced in a
vertical direction so that bending does not occur when the pull
has a vertical component.
11.4 Axles And Wheels
(a) The transformers are to be provided with flanged bidirectional
wheels and axles. These shall be so designed as not
to deflect excessively to interfere with the movement of the
transformer. Wheels shall be provided with suitable bearings

which shall be rust and corrosion resistant. Fittings for


lubrication shall also be provided.
(b) Suitable locking arrangement along-with foundation bolts
shall be provided for the wheels to prevent accidental
MPPTCL/TECH/PROC/05/JUNE13 Page 14 of 111

movement of transformer. The locking arrangement shall be


such that it can be locked with plinth of transformer. The length
of the arrangement should be adequate to cover height of the
rail. No floating type locking arrangement shall be accepted
(c) The wheels are required to swivel and they shall be arranged
so that they can be turned through an angle of 90 degrees
when the tank is jacked up to clear of rails. Means shall be
provided for locking the swivel movements in positions
parallel to and at right angles to the longitudinal axis of the
tank (i.e. longitudinal & transverse directions).
(d) To facilitate uniform distribution of transformer weight two nos.
props each on front & rear side along longer axis to be
provided.
11.5 Anti Earthquake/Transport Clamping Device
(a) To prevent transformer movement during earthquake,
clamping device shall be provided for fixing transformer to the
foundation. The Bidder shall supply necessary bolts for
embedding in the concrete foundation. The arrangements
shall be such that the transformer can be fixed to or
unfastened from these bolts as desired. The fixing of the
transformers to the foundations shall be designed to
withstand seismic events to the extent that a static co-efficient
of 0.3g. applied in the direction of least resistance to that
loading will not cause the transformer or clamping devices as
well as bolts to be over stressed.
(b) Locking arrangement to eliminate relative movement between
top yoke/active parts with the transformer tank shall be sturdy
enough to bear transport hazards taking in to account the poor
road conditions and also considering that road transportation of
transformer will not be on hydraulic trailers
11.6 Conservator Tank
(a) The conservator tank shall be of minimum thickness of 8 mm
and it shall have adequate capacity between highest and
lowest visible levels to meet the requirement of expansion
of the total cold oil volume in the transformer and cooling
equipment from minimum ambient temperature to 100 oC.
(b) The conservator tank shall be bolted into position so that it
can be removed for cleaning purposes.
(c) Magnetic oil gauge (MOG) & prismatic oil level gauge having
three overlapped windows on one side of conservator and
on opposite side of conservator, plain oil gauge with three
overlapped windows shall be provided to indicate oil level
inside the conservator at each location. Proper arrangement
to ensure visibility of oil level from ground be also ensured .
MPPTCL/TECH/PROC/05/JUNE13 Page 15 of 111

(d) Conservator shall be provided in such a position as not to


obstruct the electrical connections to the transformer.
(e) In order to avoid congestion and to facilitate operation and
maintenance activities, the main conservator and OLTC
conservator shall be provided on opposite sides of the main

tank. Further, there shall be adequate space for manual


operation of OLTC.
(f) Separate conservator tank shall be provided for OLTC.
(g) The size of the conservator shall be so designed as to
accommodate approximately 10% volume of total quantity of
oil in the transformer.
(h) Suitable arrangement shall be made for providing a foot rest
with easy & access arrangement to facilitate
maintenance/operation at top of the conservator, on magnetic
oil level gauge and buchholz relay.
(i) The design of conservator shall be such that the air is not
trapped between air cell and main conservator.
11.7 Tank Earthing Arrangement : Two earthing pads complete with
two number tapped holes M10 bolts plain and spring washer suitable for
connection to 50X8 mm GI flat shall be provided each at position close to two
diagonally opposite bottom corners of tank. Earthing strips up to the ground
level and its connection with station earth pit shall be provided by the Bidder.
11.8 Pressure Relief Device : A minimum of 3 (three) number of
pressure relief devices of reputed make and reliable quality shall be provided
on each transformer and these shall be mounted preferably on the tank
cover above each phase winding. Bidders must submit calculations to prove
that the no and capacity of pressure relief device with location of each PRV
provided on the transformer will adequately meet our requirement. The
quantity of three numbers is on the basis that two numbers will be required as
per design calculation and one number additional PRD shall be provided from
the point of view of additional safety.
Constructional and design details of pressure relief device must be furnished
and it should be proved by calculation that the size and operating pressure
setting of pressure relief device is adequate, considering the rating of the
transformer and quantity of oil in the transformer. Furnishing of this
information is a must. These PRD's shall be of sufficient size for rapid
release of any pressure that may be generated in the tank and which may
result in damage to the equipment. The device shall operate at a static
pressure of less than the hydraulic test pressure of transformer tank. It shall
be mounted directly on the tank. One set of electrically insulated contacts
shall be provided for alarm & tripping along-with the recommendations.
MPPTCL/TECH/PROC/05/JUNE13 Page 16 of 111

11.9 Relays
11.9.1 Buchholz Relay : A double float type Buchholz relay along with
suitable moulded type cover to avoid ingress of moisture/ rain water shall be
provided. All the gases evolved in the transformer shall collect in this relay.
The relay shall be provided with a test cock suitable for a flexible pipe
connection for checking its operation and for taking gas sample. A copper
or stainless steel tube, shall be connected from the gas collector to a
valve located about 1200mm above ground level to facilitate sampling of gas
while the transformer is in service. The device shall be provided with two
electrically independent ungrounded contacts, one for alarm on gas
accumulation and the other for tripping on sudden rise of pressure. The
contacts of relay shall be properly housed, sealed and gasketted to make the
arrangement water proof. Entry of moisture/water in the contact chamber
needs to be eliminated. Cable entry to terminal box of buchholz relay should
be made through bottom of relay.
11.9.2 Oil Surge Relay (OSR) : From our past experience, it is found
that undesired tripping of Power Transformers is occurring on oil surge relay

(OSR)and Buchholz relay operation actuating due to accumulation of water


inside relay pockets. The water accumulation takes place through entry
point of cable gland. In view of above, the design and placement of Alarm &
trip contact assembly of OSR and Buchholz Relay should be improved to
take care of the following requirements:
(a) The cable entry to terminal box of OSR should be made through
bottom of relay. Also the OSR relay should be protected from rain water
by providing proper cover on it.
(b) In order to ensure exit/drainage of accumulated water from inside the
relay, a fine hole should be made in terminal box of relay.
11.9.3 Rapid Pressure Rise Relay (RPRR) : The provision for the
same be made on the main tank to operate on rate of rise of pressure. An
electrically insulated trip contact shall be provided in RPRR relay as per
requirement of NIFPS.
Note : The Bidders shall ensure that the compartments housing relay
contacts of Pressure Relief Valve , Buchholz Relay and Oil Surge Relay are
made absolutely water and vermin proof. The compartment housing
contacts of OSR,PRV and Buchholz Relay shall be tested for water proof at
the time of inspection and effectiveness of water proofing shall be
demonstrated at the time of inspection. This should be noted carefully by
the Bidder and specifically confirmed in their bid.
11.10 Temperature Indicator
11.10.1 Oil Temperature Indicator (OTI) :Transformers shall be
provided with a 150mm dial type thermometer with maximum pointer for top
oil temperature indication. The thermometer shall have adjustable two
electrically isolated heavy duty alarm and trip contacts, maximum reading
MPPTCL/TECH/PROC/05/JUNE13 Page 17 of 111

pointer and resetting device mounted in the Fan control cubicle (FCC). A
temperature sensing element suitably located in a pocket on top oil shall be
provided. This shall be connected to the OTI by means of capillary tubing.
Accuracy class of OTI shall be plus or minus 1.0% or better. The OTI shall be
provided with anti vibration mounting .
11.10.2 Winding Temperature Indicator (WTI)
(a) WTI for measuring the winding temperature of each of the
windings (HV, LV) shall be provided. It shall comprise of the
following
(i) Temperature sensing element.
(ii) Image coil.
(iii) Auxiliary CTs, if required, to match the image coil, shall
be provided.
(iv) 150mm dia local indicating instrument with maximum
reading pointer mounted in FCC/marshalling box and with
four adjustable electrically isolated heavy duty contacts
(two for control of cooling equipment, one for high
winding temperature alarm and other for trip) shall be
provided. The WTI shall be provided with anti vibration
mounting.
(v) Calibration device.
(b) In addition to the (a) above, repeater dial of WTI for each
winding shall be provided for Remote winding temperature
indication. It shall be suitable for flush mounting on RTCC
panel. A precision potentiometer mounted inside the case
shall function as a transmitter to operate a repeater for
RWTI. For HV winding, the transmitter shall be connected

directly to the repeater. For LV winding , the transmitter shall


be connected to a resistance Transducer, which will supply
DC for operating repeater.
(c) Auxiliary supply, if required in RTCC panel for RWTI, shall be
220V or 110V DC only.
(d) Accuracy class of WTI as well as RWTI shall be plus or minus
1.0% or better.
(e) Any special cables required for shielding purpose for
connection between cooler control cabinet and remote winding
temperature indicator control circuit shall be in Bidders
scope of work.
(f) WTI CT ratio shall be embossed on secondary winding terminal
box.
Note Some of the manufacturers have a practice to directly install winding
temperature indicator (WTI) and oil temperature indicator (OTI) on
the body of the transformer in open. This is not acceptable & it is
MPPTCL/TECH/PROC/05/JUNE13 Page 18 of 111

obligatory on the part of the Bidders to enclose OTI & WTI and all
such accessories in a separate Fan Control Cubicle (FCC) cum
Marshalling Box .
11.11 Core
a) The core shall be constructed from high grade, non- ageing,
low loss, Cold Rolled Super Grain oriented (CRGO) silicon steel
laminations of HI-B grade steel or better. All stipulations under
clause 4.4 should be considered while selecting material of
core. Interlamination resistance shall be as per BS601
Part 5 method of July 1973. The Bidder shall furnish the
details of steel laminations i.e. type alongwith hysterisis
loss curve (B-H curve) etc.
(b) After being sheared, the laminations shall be treated to
remove all burrs and shall be re-annealed to remove all
residual stresses.
(c) The design of the magnetic circuit shall be such as to avoid
static discharges, development of short circuit paths within itself
or to the earthed clamping structure and production of flux
component at right angles to the plane of laminations which
may cause local heating.
(d) The core shall be provided with lugs suitable for lifting complete
core & coil assembly of transformer.
(e) Core Belting : The core shall be rigidly clamped by belting to
ensure adequate mechanical strength. Core and winding shall
be capable of withstanding the vibrations & shock during
transport, installation, service and adequate provision shall
be made to prevent movement of core & winding relative to
tank during these conditions. The location, size and material
of belting shall be clearly indicated in drawing which shall
be submitted with Bid. Bolted type core construction
shall not be acceptable.
(f) All steel sections used for supporting the core shall be
thoroughly sand blasted after cutting, drilling and welding.
(g) Each core lamination shall be insulated with a material that will
not deteriorate due to pressure and hot oil.
(h) The insulation of core to bolts and core to clamps
plates shall be able to withstand a voltage of 2KV RMS

for one minute.


(i) The maximum flux density in any part of the core and yoke at
rated MVA, 110% voltage and (-) 4% frequency at any tap
shall not exceed 1.90 Tesla. The Bidder shall provide
saturation curve of the core material proposed to be used
and calculations to demonstrate that the core is not over fluxed
under stringent condition of transformer operation.
MPPTCL/TECH/PROC/05/JUNE13 Page 19 of 111

(j) Bidder will offer the core for inspection & approval by
the purchaser during the manufacturing stage.
Bidder's call notice for this purpose should be
accompanied with the following documents, as
applicable, as a proof towards use of prime core
material.
i) Invoice of the supplier
ii) Mill's Test Certificate
iii) Packing List
iv) Bill of lading
v) Bill of entry certificate by customs.
(k) Core material shall be directly procured either from the
manufacturer or through their accredited marketing
organization of repute and not through any agent.
(l) Bidder should have in-house Core Cutting facility for proper
monitoring & control on quality and also to avoid any possibility
of mixing of prime material with defective/second grade
material.
(m) Oil ducts shall be provided wherever necessary to ensure
adequate cooling. The winding structure and major insulation
shall not obstruct the free flow of oil through such ducts.
Where the magnetic circuit is divided into pockets by cooling
ducts parallel to the plane of laminations or by insulating
material above 0.254 mm. Thick, tinned copper strip bridging
pieces shall be inserted to maintain electrical continuity
between pockets. The design of the magnetic circuit shall be
such as to avoid static discharge development of short circuit
path within itself or to the earthed clamping structure and
production of flux components at right angles to the plane of
the laminations which may cause local heating.
(n) Core shall not directly rest on the bottom metal sheet of
transformer tank. Around 3 mm or more free space for oil
insulation shall be made between the core and bottom sheet of
transformer tank. A 5 mm FRP Insulating sheet shall be
provided to take care of core earthing due to accidental
slippage of stampings. Also in addition to this extra
insulation thickness of 5 mm or more FRP sheet be
provided at the bottom of resting shoes of end frame
with proper fixing arrangement to avoid accidental
slippage, damages etc.
11.12 Windings
(a) The Bidder shall ensure that windings of all transformers are
made in dust proof, conditioned atmosphere. The Bidder shall
furnish the facilities available at their works alongwith the
bid.
MPPTCL/TECH/PROC/05/JUNE13 Page 20 of 111

(b) The conductors shall be of electrolytic grade copper as per

relevant IS. The maximum current density for design of


transformers within specified limits of transformer losses shall
not exceed the limits of 300 amps per sq.cm.
(c) The insulation of transformer windings and connections shall be
free from insulating compounds which are liable to soften,
ooze out, shrink or collapse or be catalytic and chemically
active in transformer oil during service.
(d) Coil assembly and insulating spacers shall be so arranged as
to ensure free circulation of oil and to reduce the hot spot of
the winding. The conductor shall be transposed at sufficient
intervals in order to minimize eddy currents and equalize the
distribution of currents and temperature along the winding.
(e) The LV winding should withstand short circuit faults/forces of
the transformer upto the prescribed fault levels on HV & LV
sides against mechanical and thermal stresses.
(f) Best insulating material shall be used and compression of
the windings after drying out shall be carried out at a
pressure exceeding one and a half to twice the force which can
occur in the transformer; to impart greater mechanical
strength to the windings against heavy short circuit
stresses.
(g) The windings shall be so designed that all coil assemblies of
identical voltage ratings shall be interchangeable and field
repairs to the windings can be made readily without special
equipment. The coils shall be supported between adjacent
sections by insulating spacers, and the bracings and other
insulation used in the assembly of the winding shall be
arranged to ensure free circulation of the oil to reduce hot
spots in the windings.
(h) The coil insulation shall be treated with suitable insulating
varnish or equivalent compound wherever necessary to develop
the full electrical strength of the winding. All materials used in
the insulation and assembly of the winding shall be insoluble,
non-catalytic and chemically inactive in the hot transformer oil
and shall not soften or otherwise be adversely affected under
the operating conditions.
(i) All threaded connections shall be provided with locking
facilities. All leads from the winding to the terminal
connectors and bushings shall be rigidly supported to prevent
injury from vibration. Guide tubes shall be used where
practicable.
(j) Windings shall be subjected to a shrinkage treatment before
final assembly so that no further shrinkage occurs during
service. Adjustable device shall be provided for taking up any
possible shrinkage of coils in service. After shrinkage process,
MPPTCL/TECH/PROC/05/JUNE13 Page 21 of 111

the windings shall be clamped securely in place so that they will


not be displaced or deformed during short circuits. The
assembled core and windings shall be vacuum-dried and
suitably impregnated before removal from the treating tank.
The copper conductors used in the coil structure shall be best
suited to the requirements and all permanent current carrying
joints in the windings and the leads shall be crimped or
brazed preferably by high frequency brazing system.

It is observed that many manufacturers are using sectored


clamping arrangement at top as well as bottom for clamping of
the windings. This type of arrangement is considered to be not
suitable for EHV grade power transformers. In this regard, it
may be noted that both top & bottom clamping rings to be
provided for clamping of windings shall be of one piece single
ring. The top & bottom clamping rings should be of
minimum thickness 60 mm with proper safety margins
based on design and shall be in one piece to make the
clamping arrangement sturdy. Sectored
pressure/clamping rings are not acceptable. The single
pressing/clamping ring shall be provided with adequate
number of pressure/jacking points as per design. Since
sectored ring arrangement shall not be accepted hence
bidder should ensure and confirm this specific
requirement in the technical questionnaire.
(k) Bidder will offer the Copper and insulating material for
windings for inspection & approval by the purchaser during
the manufacturing stage. Bidder's call notice for the
purpose should be accompanied with the following documents,
as applicable, as a proof towards use of prime Copper and
insulating material for windings .
i) Invoice of the supplier
ii) Mill's Test Certificate
iii) Packing List
iv) Bill of lading
v) Bill of entry certificate by customs.
(l) Core, Copper and insulating material for windings shall be
directly procured either from the manufacturer or through their
accredited marketing organisation of repute and not through
any agent.
(m) Certificate : Supplier shall provide purchaser details of
procurement of raw materials i.e., core, insulation & copper.
Supplier shall also record a certificate as under :
" CERTIFICATE "
It is certified that the Transformer shall be
manufactured by --------- (Name of manufacturer) out of
the core, insulating and winding material procured as per
details indicated in specification. We are agreeable to
MPPTCL/TECH/PROC/05/JUNE13 Page 22 of 111

undertake third party inspection of Transformer during its


manufacture or of raw materials, at the sole discretion of
MPPTCL without any extra cost.
If at any stage it is found that the transformer is not
manufactured out of the raw material indicated in
specification, the transformer shall be liable for rejection by
MPPTCL and transformer shall be replaced by (name of
manufacturer) at no extra cost to MPPTCL.
Signature of Authorised
Signatory with Seal of manufacturer
(n) The Purchaser also reserves the right to carry out stage
inspections at other stages also, for which advance
intimation shall be given and all necessary cooperation
shall be rendered by the supplier.

11.13 Bushings
(a) The electrical & mechanical characteristics of bushings shall
be in accordance with IS-3347 & IS-2099 ( latest version ) &
IEC 60137(2008 or latest version).
(b) The bushings shall have high factor of safety against
leakage to ground and shall be so located as to provide
adequate electrical clearances between bushings and also
between the bushings and grounded parts. Bushings of
identical voltage rating shall be of similar BCT and inter
changeable. All bushings shall be equipped with suitable
terminals of approved type and size and all external current
carrying contact surfaces shall be adequately silver plated.
The insulation class of the high voltage neutral bushing shall
be properly coordinated with the insulation class of the
neutral of the high voltage winding.
(c) All main winding and neutral leads shall be brought out
through outdoor type bushings which shall be so located that
the full flashover strength will be utilized and the
adequate phase clearance shall be realized.
(d) Each bushing shall be so coordinated with the transformer
insulation that all flashovers will occur outside the tank.
(e) All porcelain used in bushings shall be of the wet process,
homogeneous and free from cavities or other flaws. The
glazing shall be uniform in color and free from blisters, burns
and other defects.
(f) (i) For 33KV winding & neutral, the bushing shall be of OIP
condenser of 72.5KV class of draw rod type/solid stem
type.
MPPTCL/TECH/PROC/05/JUNE13 Page 23 of 111

(ii) The bushings of 245 KV class shall be of OIP condenser of


draw rod type (DR) only.
(iii) Tan-delta of all bushings shall be 0.005 (max.)during
testing at manufacturers works
(g) All bushings shall have puncture strength greater than the dry
flashover value.
(h) Main winding terminals shall be solder-less terminals and
shall be of the type and size specified .
(i) The spacing between the bushings must be adequate to prevent
flashover between phases under all conditions of operation.
The clearances shall be as follows :
S.
N
o
Nomin
al
Syste
m
Voltag
e
Voltage
Class
Of
Bushin
g

Curre
nt
Rating
Impulse
Withsta
nd
Voltage
(Kvp)
1min.Po
wer
Frequenc
y
Withstan
d Voltage
Kv(rms)
Creepage
Distance
in mm
Clearance
in mm
Ph to
Ph.
Ph to
E
1 220KV 245KV 1250A 1050 460 6125 2700 2400
2 33KV 72.5KV 1250A 325 140 1813 700 660
The Bidders are required to confirm clearances and no change
/reduction in clearances shall be acceptable. The clearances
shall be clear distances in air after accounting for
clamps/connectors dimensions to be mounted on the stud of
bushings.
(j) Special adjustable arcing horns shall be provided for the HV
bushings. For 72.5KV class bushings, arcing horns are not
required.
(k) The Bidder is requested to furnish the guaranteed withstand
voltage for the above and also furnish a calibration curve with
different settings of the coordination gap to the purchaser
to decide the actual gap setting. Bidder's recommendations
are also invited in this respect.
(l) The bushings shall be capable of withstanding without injury the
electrical, thermal and mechanical effects of external short
circuits. 245 KV bushings shall be rated for short time
thermal current rating of 40 KA for 3 seconds and 72.5 KV
Bushings, 31.5KA for 3 seconds.
(m) All the transformers covered under this specification shall be
utilized in heavily polluted atmosphere. In view of this the
Bidders while offering prices for the transformers against
this contract may please note that the offer should be made
out based on the creepage for the bushings @ 25mm per KV
based on the voltage of 72.5KV/ 245KV. Thus in the quoted
MPPTCL/TECH/PROC/05/JUNE13 Page 24 of 111

prices of transformer cost of bushings should be included


based on a creepage distance of 25mm per KV.
(n) All O.I.P. Condenser bushings shall be provided with :

(i) Oil level gauge.


(ii) Oil filling plug and drain valve, if not hermetically sealed.
(iii) Tap for capacitance/tan delta test.
(o) The bushings with current transformers are specified, hence
the bushings shall be removable without disturbing the current
transformers.
(p) Porcelain used in bushing manufacture shall be homogenous,
free from laminations, cavities and other flaws or
imperfections that might affect the mechanical or dielectric
quality and shall be thoroughly vitrified tough and
impervious to moisture. Glazing of porcelain and bushing
shall be of uniform brown color free from blisters and burrs.
(q) Bushing turrets shall be provided with suitable vent pipes
which shall be connected to route any air/gas collection
through the Buchholz relay.
(r) For Bushings of all voltage class, the arrangement for
connection of winding/neutral terminal shall be indicated .
(s) From the end point of the condenser of the bushing which
will protrude inside the transformer OR the bottom
termination point of bushing, sufficient clearance should be
available so that in case any other make bushing is
installed problem in this regard may not arise. Maximum
length of condenser portion, which can be easily
accommodated, should be clearly indicated by the Bidder.
(t) The LV take off arrangement within the transformer is of utmost
importance hence due care shall be taken while providing this
arrangement inside the transformer tank. The connecting lug of
LV winding with the bushing bottom terminal pad should match
with the current rating of the bushing. The size of the LV
winding lug shall be of suitable rating to match with the
maximum load current of the transformer to be fed through
extreme tap of OLTC meeting requirements of IS-6600. In this
regard, the clamping arrangement of LV winding with
two lugs having two holes with two hole terminals on
counter part of the bushing pad are not acceptable. In
case of such arrangement, it will have to be ensured that
the counter part of winding lead/lug i.e. bushing
terminal is with four holes or vice versa. Similar
arrangement shall be ensured for termination of neutral
lead on neutral bushing pad.
MPPTCL/TECH/PROC/05/JUNE13 Page 25 of 111

11.14 Bushing Current Transformers


(a) Current transformers shall comply with IS:2705.
(b) One no. bushing CT of Ratio 800/1 on each phase of HV i.e 3
nos for HV & one no. bushing CT of Ratio 1200/1 on each phase
of LV winding i.e. 3 nos. for LV. One no. bushing CT of Ratio
800/1 for HV neutral & one no. bushing CT of Ratio 1200/1 for
LV neutral shall be provided for each Transformer.
(c) It shall be possible to remove turret mounted CTs from the
transformer tank without removing the tank cover. Necessary
precaution shall be taken to minimize the eddy currents and
local heat generated in the turret.
(d) All secondary leads shall be brought to a terminal box near
each bushing. These terminals shall be wired out to cooler

control cabinet using separate cables for each core.


(e) For the thermal image coil of winding temperature indicator,
CT with suitable ratio and class may be used.
11.15 Terminal Marking : The terminal marking and their physical
position shall be in accordance with IS:2026.
11.16 The positioning of HV & LV bushings shall be such that skew
jumpering is avoided. The middle phase primary & secondary bushing center
line shall be parallel to side axis of the transformer body.
12.0 EARTHING ARRANGEMENT
12.1 NEUTRAL EARTHING ARRANGEMENT : The neutral terminal of
the star connected HV/ LV winding shall be brought up to the ground level
through two tinned copper flat strips of size 50x6mm which shall be supported
on transformer tank horizontal/ vertical by porcelain insulators of adequate
voltage class. The number of insulators shall be sufficient to provide a
mechanically sturdy arrangement. Necessary mechanical supports on the tank
for mounting of the insulators shall be made. The KV class rating of insulators
shall commensurate with the rating/ KV class of neutral design. It may be
ensured that connection of the neutral strips to neutral bushings at one end
shall be made using a terminal connector suitable for connection to the neutral
bushing terminal and to receive 2x50x6 mm tinned copper strips on the other
side. The connection between the bushing and transformers earth pit shall be
through 2x50x6 mm tinned copper strips single run without any joint
connection/brazing/ welding etc. In case of problem in availability of single run
tinned copper strips, it may be accepted with single joint. However, joint to be
provided shall be subject to approval of purchaser. The other end of the earth
connection to the earth pit shall also be through terminal connector suitable to
receive 2x50x6 mm copper strips at one end and to receive MS flat and / or
twin ACSR zebra conductor on the other end. The length of the copper strips
shall be suitable for providing a joint less connection between transformer
neutral and earth pit and details in this regard shall be intimated to the
MPPTCL/TECH/PROC/05/JUNE13 Page 26 of 111

successful Tenderer based on transformer/substation layout design. A typical


arrangement is shown in drg. No MPPTCL/50MVA/02 of this specification for
neutral earthing.
12.2 CORE EARTHING ARRANGEMENT
The Tenderer should note our requirement in this regard very
clearly. It is required to bring out leads from core, end frame and tank to
the top of the transformer through only three insulated bushings. The
arrangement shall be housed in a box at the top cover of transformer tank with
provision for interconnection between the studs of bushings. The bushing
housing shall have a suitable cover with gasket to make the arrangement
waterproof. A clear marking (engraved/punched) shall be made to indicate
that the housing contains core/end frame/ tank earthing arrangement. Please
note that stickers/flags/tags/painted marking for identification shall not be
accepted. A typical sketch of general arrangement needed by purchaser is
shown in drawing no. MPPTCL/50MVA/03 of this specification. Arrangement
shall be such that even after removal of connections, oil shall not leak.
Removable shorting strips between the three bushing shall be provided. It
may be noted that internal earthing of any nature between core and End
frame should not be provided. Earthing at site shall be done by
interconnecting the three bushings through shorting strips. This arrangement
is to facilitate checking of multiple core earthing in the transformer.
It may be noted that :
a) any alternative arrangement is not acceptable and therefore

Tenderer must confirm provision of three bushings as desired


above.
b) Once transformer reaches site, before unloading from the
trailor, the position of core earthing shall be checked and in
case any problem of multiple core earthing is observed, delivery
of Transformer will not be taken.
The insulated cable to be used for core to Bushing connection & end
frame to Bushing connection should be of good quality with proper
grounding arrangement. The size and number of strands of cable shall
be subject to purchasers approval.
13.0 AUXILIARY POWER SUPPLY FOR OLTC, COOLER CONTROL
AND POWER CIRCUIT
13.1 Duplicate(Two) auxiliary power supplies of 0.4 KV, three phase,
four(4) wire shall be provided by the purchaser at cooler control cabinet and
for OLTC drive.
13.2 All loads shall be fed by one of the two feeders through an
electrically interlocked automatic transfer switch housed in the cooler control
cabinet , for tap changer control and cooler control circuits.
MPPTCL/TECH/PROC/05/JUNE13 Page 27 of 111

13.3 Design features of the transfer switch shall include the following :
i) Provision for the selection of one of the feeders as normal
source and other as standby.
ii) Upon failure of the normal source, the loads shall be
automatically transferred after an adjustable time delay to the
standby source.
iii) Indication to be provided at cooler control cabinet & RTCC for
failure of normal source and for transfer to standby source and
also for failure to transfer.
iv) Automatic re-transfers to normal source without any
intentional time delay following re-energisation on the
normal source.
v) Both the transfer & re-transfer shall be dead transfers and AC
feeders shall not be paralleled at any time.
13.4 AC feeder shall be brought to the OLTC cabinet (Cooler Control Cabinet)
by the Bidder, after suitable selection at cooler control cabinet. The Bidder
shall derive AC power for control circuit from the AC feeder as mentioned
above by using appropriately rated dry type transformers. If the control
circuit is operated by DC supply then suitable converters to be provided by
the Bidder to be operated from AC Power source.
13.5 Necessary isolating switches and HRC fuses shall be provided at
suitable points as per approved scheme of purchaser.
14.0 TAP CHANGING EQUIPMENT
14.1 General Requirement
(a) OLTC gear shall be motor operated for local as well as
remote operation. An external hand wheel/handle shall be
provided for local manual operation. This hand wheel/handle
shall be easily operable by a man standing at ground level.
(b) Arrangement shall be made for securing and padlocking the
tap changer wheel in any of the working positions and it shall
not be possible for setting or padlocking the wheel in any
intermediate position. The arrangement shall be such that no
padlock key can be inserted unless all contacts are correctly
engaged and switch set in a position where no open or short
circuit is possible. An indicating device shall be provided to

show the tap in use.


(c) The current & voltage rating of OLTC for the transformers
shall be as under. The through current rating of OLTC shall
be based on Clause 2.3.2 of IS 8478 and following OLTC rating
specified are the minimum requirements. Bidder, however
MPPTCL/TECH/PROC/05/JUNE13 Page 28 of 111

must offer OLTC with higher current rating, as mentioned


below:Transformer
Rating
OLTC on
Winding
HV
Neutral
end
Rating of OLTC
Voltage
Rating
Minimum
Current
Rating
Tap
Range
(In steps
of 1.25%)
220KV,
50MVA
HV
Neutral
end
170KV 500Amp. (+)5% to
(-)15% of
220 kV
e) The OLTC motor should be capable of smooth and trouble free
operation with supply voltage variation of 0.4 KV -25% &
+10%.
14.2 On Load Tap Changing Gear(OLTC)
(a) The details of the method of diversion of the load current
during tap changing, the mechanical construction of the gear
and the control features for OLTC gear alongwith detailed
drawings on the inner view and the arrangement of
connections shall be submitted with the Bid. Information
regarding the service experience on the gear and a list of
important users shall also be furnished. The tap changer shall
change the effective transformation ratio without producing
phase displacement.
(b) The current diverting contacts shall be housed in a separate oil
chamber not communicating with the oil in main tank of the
transformer.
(c) The contacts shall be accessible for inspection without
lowering oil level in the main tank and the contact tips shall
be replaceable.
(d) The Bidder shall indicate the safeguards employed to take care
of harmful arcing at the current diverting contacts in the

event of operation of the OLTC gear under overload


conditions ( overloading capability as per IS 6600 ) of the
transformer. Necessary tools and tackles shall be provided
alongwith main supply for maintenance of OLTC gear.
(e) The OLTC oil chamber shall have oil filling and drain valves, oil
sampling valve, relief vent and oil level gauge/glass. It shall
also be fitted with an oil surge relay. For accommodating oil
expansion of OLTC a separate conservator tank shall be
provided.
(f) The diverter switch or arcing switch shall be designed so as
to ensure that its operation once commenced shall be
completed independently of the control relays or switches,
MPPTCL/TECH/PROC/05/JUNE13 Page 29 of 111

failure of auxiliary supplies etc. To meet any contingency


which may result in incomplete operation of the diverter
switch, adequate means shall be provided to safeguard the
transformer and its ancillary equipments.
(g) Drive mechanism chamber shall be mounted on the tank in
accessible position. It should be adequately ventilated and
provided with anti condensation metal clad heaters. All
contactors, relay coils and other parts shall be protected against
corrosion, deterioration due to condensation, fungi etc.
(h) The control feature shall provide the following :
i) LOCAL-REMOTE selector switch mounted in the local
control cubicle shall switch control of OLTC for lower/ raise
functions in local or remote mode as selected.
ii) The LOCAL-REMOTE selector switch shall have at-least
two spare contacts per position which are closed in that
position but open in the other position.
iii) A RAISE-LOWER CONTROL SWITCH shall be
provided in the local control cubicle. The switch shall be
spring loaded to return to the Centre "OFF" position and
shall require movement to the RIGHT to raise the
voltage of the transformer. Movement to the left shall
lower the voltage. Alternatively push button type
arrangement of standard design may be provided.
iv) An OFF-ON tap changer control switch shall be provided
in the OLTC local control cabinet of transformer. The tap
changer shall be inoperative in the OFF position. Also the
OFF-ON switch shall have atleast one spare contact per
position which is closed in that position but open in the
other position.
v) Operating mechanism for on load tap changer shall be
designed to go through one step or tap change per
command. Subsequent tap changes shall be initiated only
by a new or a repeat command.
vi) On load tap changer shall be equipped with a time delay
in complete STEP alarm consisting of a normally open
contact which closes, if the tap changer fails to make a
complete tap change. The alarm shall not operate for
momentary loss of auxiliary power.
vii) The selsyn units or approved equivalents shall be
installed in the local OLTC control cabinet to provide tap
position indication for the transformer. Complete

mounting details shall be included with approved


diagram.
viii) Transformer load tap changer shall be equipped with a
fixed resistor network capable of providing discrete
MPPTCL/TECH/PROC/05/JUNE13 Page 30 of 111

voltage steps for input to the supervisory system. Any


other approved / established design for remote indication
of tap position shall also be acceptable.
(i) Limit switches shall be provided to prevent over-running of the
mechanism and in addition, a mechanical stop shall be
provided to prevent over-running of the mechanism under any
condition.
(j) Limit switches may be connected in the control circuit of the
operating motor provided that a mechanical-de-clutching
mechanism is incorporated.
(k) Thermal device or other means shall be provided to protect
the motor and control circuit. All relays, switches, fuses etc.
shall be mounted in the drive mechanism chamber and shall
be clearly marked for the purpose of identification.
(l) A permanently legible lubrication chart shall be fitted within
the driving mechanism chamber.
(m) Any "DROP DOWN" tank associated with the tap changing
apparatus shall be fitted with guide rod to control the
movements during lifting or lowering.
(n) A five digit counter shall be fitted to the tap changing
equipment to indicate the number of operations performed.
(o) All relays and operating devices shall operate correctly at any
voltage between the limits specified.
(p) It shall not be possible to operate the electric drive when the
manual operating gear is in use.
(q) It shall not be possible for any two controls to be in
operation at the same time.
(r) The equipment shall be suitable for supervisory control and
indication with make before break multi-way switch, having
one potential free contact for each tap position. This switch
shall be provided in addition to any other switch/switches
which may be required for remote tap position.
(s) Operation from the local or remote control switch shall cause
one tap movement only until the control switch is returned to
the off position between successive operations.
(t) All electrical control switches and the local operating gear shall
be clearly labeled in a suitable manner to indicate the direction
of tap changing.
(u) Transfer of source failure of one AC supply shall not affect tap
changing operation.
(v) For the purpose of operation of OLTC, based on design of
manufacturer, transition resistor could be used. However, no
component of OLTC including transition resistor shall be
MPPTCL/TECH/PROC/05/JUNE13 Page 31 of 111

housed inside main transformer tank. The design of the


transition resisters should be liberal to ensure suitability during
tap change operation at rated current including over loading
capability and system short circuits.
(w) The location and design of OLTC shall be such that in the event
of any repair / maintenance , it should be possible to take out

various parts from the OLTC and other accessories and fittings
mounted on the transformer particularly equalising pipes etc do
not infringe / obstruct .
14.3 Manual Control
The cranking device for manual operation of the OLTC gear shall be
removable and suitable for operation by a man standing on ground level. The
mechanism shall be complete with the following :
i) Mechanical tap position indicator which shall be clearly
visible to the person operating tap changer manually at the
transformer.
ii) A mechanical operation counter.
iii) Mechanical stoppers to prevent over-cranking of the mechanism
beyond the extreme tap positions.
iv) The manual control considered as back up to the motor
operated load tap changer control shall be interlocked with the
motor to block motor start-up during manual operation. The
manual operating mechanism shall be labeled to show the
direction of operation for raising the voltage and vice-versa.
14.4 Electrical Control : This includes Local Electrical control and
Electrical remote control from remote control panel. The control circuits shall
have the following features:
i. An interlock to cut off electrical control automatically upon
recourse being taken to the manual control in emergency.
ii. Reinforcement of the initiating impulse for a tap change,
ensuring a positive completion once initiated to the next
(higher or lower) tap.
iii. Step-by-step operation ensuring only one tap change from
each tap changing impulse and lock-out of the mechanism if
the control switch (or push button) remains in the "Operate
Position".
iv. An interlock to cut-out electrical control when it tends to
operate the gear beyond either of the extreme tap positions.
v. An electrical interlock to cut-off a counter impulse for reverse
step change being initiated during a progressing tap change
and until the mechanism comes to rest and resets circuits for
a fresh position. Suitable interlocks shall be provided to
MPPTCL/TECH/PROC/05/JUNE13 Page 32 of 111

prevent operation of OLTC beyond extreme tap with a


mechanical/electrical lockable switch.
vi. Protection apparatus, considered essential by the Bidder
according to specification.
14.5 Remote Electrical Group Control : The OLTC control scheme
offered shall have provision of remote electrical group control during parallel
operation of transformers. This is in addition to independent control of OLTC.
i. A four position selector switch having MASTER, FOLLOWER,
INDEPENDENT and OFF position shall be provided in the
remote OLTC control panel for each transformers. This shall
be wired to enable operator to select operation of OLTC in
either Master, Follower or Independent mode.
ii. Out of step relays with timer contacts shall also be
provided to give alarm and indication in case of tap
positions in all the transformers under group control being not
in same position.
iii. Master Position : If the selector switch is in MASTER

position, it shall be possible to control the OLTC units in the


FOLLOWER mode by operating the controls of the MASTER unit
Independent operation of the units under FOLLOWER mode
shall have to be prevented. However, the units under
independent mode will be controlled independently.
iv. Follower Position : If the selector switch is in FOLLOWER
mode, control of OLTC shall be possible only from MASTER
panel.
v. Independent Position : In this position of Selector Switch,
Control of OLTC of individual unit only shall be possible.
14.6 Local OLTC Control Cubicle : The Auxiliary devices for
electrical control of the OLTC shall be housed in a weather proof cubicle . It
shall be complete with the following :
i) A circuit breaker/contactor with thermal overload devices for
controlling the AC auxiliary supply to the OLTC motor.
ii) Cubicle light with door switch.
iii) Space heaters to prevent condensation of moisture.
iv) Padlocking arrangement for hinged door of cabinet.
v) Cable terminal glands for power and control cables to the
OLTC gear.
14.7 Remote Tap Changer Control Panel (RTCC) : Remote tap
changer control panel to be supplied by the Bidder shall consist of :
i) Actuating switch for electrical raise/lower control.
MPPTCL/TECH/PROC/05/JUNE13 Page 33 of 111

ii) Remote tap position indicator.(preferred digital type)


iii) Signal lamps for Tap changer in progress and Tap changer out
of step.
iv) Auxiliary devices for remote electric group control of OLTC.
v) Annunciation scheme with the following :
- Fan fail (for all fans individual windows).
- AC supply fail.
- Stand by fan fail.
- Stand by fan on.
- OLTC motor over loaded.
- OLTC control supply fail.
- OLTC at extreme position i.e. lowest & highest voltage tap.
- Two spare windows.
vi) Indicating Devices : Following lamp indications shall be
provided in Remote tap changer control cubicle / panel- Fan "ON", Fan "OFF"
- Cooling system "On Automatic Control".
- Cooling system "On Manual".
- Selector switch in auto or manual.
- 0.4 KV cooler supply auto changeover.
- Control supply failure main and standby.
- one potential free initiating contact for all the above
indications shall be wired independently to the
terminal blocks of cooler control cabinet exclusively for
owner's use.
vii) Remote OTI with repeater unit.
viii) Separate WTI 2 nos. for HV and one no. for LV winding
operated by signal transmitter.
ix) Voltmeter for indicating HV & LV voltage.
x) Schedule of equipments for RTCC panel shall be as under:

Name plate remote OLTC and cooler control cubicle


Indicating lamp-OLTC control supply on ( red)
Indicating lamp-tap change in progress ( yellow)
Indicating lamp-OLTC out of step ( red)
Indicating lamp-OLTC motor trip ( red)
Cooler mode selector (auto-off-on)

MPPTCL/TECH/PROC/05/JUNE13 Page 34 of 111

- OLTC sequence selector switch (OFF-INT-FOLL-MAST.)


- Emergency stop push button for tap change operation. (red)
- Auxiliary contactor for OLTC out of step monitoring.
- Out of step timer.
- Voltmeter for HV. ( 0 ~ 250kv )
- Voltmeter for LV. ( 0 ~ 40kv )
- Terminal blocks.
- Cubicle lamp.
- Door switch.
- HRC cartridge fuse holder with link for cubicle illumination
circuit.
- Neutral link.
- Earth bus.
- HRC cartridge fuse holder with link for HV volt meter.
- HRC cartridge fuse holder with link for LV volt meter..
- HRC cartridge fuse holder with link for RWTI and ROTI circuit.
- Selector switch for HV volt meter.
- Selector switch for LV volt meter.
- Remote winding temperature indicator. ( for HV & LV )
- Selector switch for winding temperature indicator.
- OLTC control switch
- Tap position indicator (digital).
- Remote oil temperature indicator.
xi. a. HV digital Voltmeter of accuracy class 0.5 provided for
indicating HV voltage shall be scaled for voltage range 0250 KV (phase to phase) and shall be suitable for use with
PT ratio 220KV/110 volt. The HV digital voltmeter shall be
precisely calibrated so as to indicate 220KV Voltage on
voltmeter scale corresponding to input voltage of 110 Volt
(phase to phase).
b. LV digital Voltmeter of accuracy class 0.5 provided for
indicating LV voltage shall be scaled for voltage range 040 KV (phase to phase) and shall be suitable for use with
PT ratio 33KV/110 volt. The LV digital voltmeter shall be
precisely calibrated so as to indicate 33KV Voltage on
voltmeter scale corresponding to input voltage of 110 Volt
(phase to phase).
15.0 COOLING EQUIPMENT
15.1 The design shall take into account the following requirements
a) The oil cooling system of transformer shall be designed using
2x50% radiator banks. The radiator banks shall be mounted
on two different sides of transformer tank. The arrangement
MPPTCL/TECH/PROC/05/JUNE13 Page 35 of 111

shall be subject to approval by the purchaser based on


substation layout and positioning of other neighboring switch
yard equipments. Coolers/radiators shall with stand pressure /
vacuum conditions specified for the tank. All coolers/ radiators
shall be attached on the transformer tank through header

having suitable expansion joints (flexible coupling) to


ensure adequate mechanical strength against vibration
etc. subject to specific approval from the purchaser. Radiators
directly mounted on transformer tank are not acceptable.
b) Each radiator bank / block shall have its own set of cooling
fans, shut off valves, lifting lugs, top and bottom oil filling
valves, air release plugs, drain valves and if considered
necessary based on design thermometer pocket fitted with
captive screw cap on the inlet and outlet, in line with valve
schedule as per Annexure-V.
c) Each radiator bank shall be provided with at least 20% standby
(spare)cooling fans. These spare fans shall be duly mounted
and shall also be wired up complete with required protective
devices and be identified with each radiator bank. While
working out number of spare fan for 20% additional cooling per
bank, if 20% quantity works out in fraction , the spare fans to
be provided shall be next whole number.
d) Cooling fans shall be designed to meet overloading
requirements as per clause 4.1 (b)
e) The exhaust air flow from cooling fan shall not be directed
towards the main tank in any case.
f) Cooling fans for each radiator bank shall be located so as to
prevent ingress of rain water. Each fan shall be suitably
protected by galvanised wire guard.
g) The cooler and its accessories shall preferably be hot dipped
galvanised or corrosion resistant paint shall be applied to it.
h) Each cooling fan shall be provided with starter thermal
overload and short circuit protection and also single phase
preventor.
i) Each radiator shall be provided with suitable lifting lugs and
shut off/air release/sampling valves as per Annexure-V
j) Expansion joints, one each on top and bottom cooler pipe
connections as per a above.
k) Air release device/plug and oil drain plug on oil pipe
connections.
l) The cooling Fans shall be mounted on separate foundation.
Mounting of Cooling fans directly on Radiators or on
transformer tank is not acceptable . The radiators mounting
arrangement is to be indicated by the Bidder in his Bid.
MPPTCL/TECH/PROC/05/JUNE13 Page 36 of 111

m) Cooling fan support shall be of adequate strength to avoid


bending etc.
n) The mounting arrangement of cooling fans shall be subject to
drawing approval from MPPTCL.
15.2 Cooling Equipment Control (ONAN/ONAF Cooling)
a) Automatic operation control (switching in and out) of fans shall
be provided (with temperature change) from contacts of
winding temperature indicator. The Bidder shall recommend
the setting of WTI for automatic change over of cooler
control from ONAN to ONAF. The setting shall be such that
hunting i.e. frequent start stop operations for small
temperature difference do not occur.
b) Suitable manual control facility for cooler fans shall be
provided.

c) Selector switches and push buttons, shall also be provided in


the cooler control to disconnect the automatic control and
start/stop the fans manually.
15.3 Indicating devices
- Fan ON , Fan OFF
- Cooling system on automatic control.
- Cooling system on manual.
- Selector switch in auto or manual for cooler.
- A.C. auxiliary cooler supply auto change over.
- Cooler supply failure for main /standby.
- Cooling fan failure for each fan.
- Control supply failure for main and standby.
One potential free initiating contact for all the above indications shall be
wired independently to the terminal block of cooler control cabinet exclusively
for purchasers use.
16.0 LOCAL OLTC CONTROL CABINET, COOLER CONTROL CABINET
& REMOTE TAP CHANGER CONTROL PANEL
a) Each three phase transformer unit shall be provided with local
OLTC control cabinet, cooler control cabinet OR fan control
cubicle (FCC) and RTCC panel. The total height of RTCC panel
shall be 2250mm to match with the height of other control &
relay panels. Local OLTC control cabinet shall be mounted on
the transformer. The thickness of front panel, door frame
etc. shall be 3mm (10 SWG),while doors & side panels may
be 2 mm (14 SWG) and gland plate shall be of minimum
thickness 4 mm.
MPPTCL/TECH/PROC/05/JUNE13 Page 37 of 111

b) The cooler control cabinet or FCC shall not be


mounted directly on transformer tank .Please note that FCC
shall be grouted away from the main tank thus the length of
capillary tubes of all oil and winding temperature indicating
meter shall be sufficient to connect OTI and WTI meters in
the FCC. The cooler cabinet shall have all necessary devices
meant for cooler control and local temp. indicators. All the
contacts of various protective devices mounted on the
transformer shall also be wired up to the terminal Board in
the cooler control cabinet. All the secondary terminals of the
bushing CT's shall also be wired upto the terminal Board at the
cooler control cabinet.
c) The cooler control cabinet shall have two(2) sections. One
section shall have the control equipment exclusively meant for
cooler control. The other section shall house the
temperature indicators, aux. CT's and the terminal Boards
meant for termination of various alarm and trip contacts.
Alternatively the two sections may be provided as two
separate panels depending on the standard practices of the
Bidder.
d) The cooler control cabinet, Local OLTC cabinet and RTCC
Panel shall be provided with non disconnecting stud type
terminal blocks. Each of the terminal blocks in the above
panels should have 20% spare terminals exclusively for
purchasers use. All the necessary terminals for remote
connection to purchasers panel shall be wired upto the cooler
control cabinet. Necessary shorting of terminals shall be done

at the cooler control cabinet, local OLTC cabinet and remote


OLTC panel. All the CT secondary terminals in the cooler
control cabinet shall have provision for short circuiting to
avoid CT open circuit while it is not in use.
e) The local OLTC control cabinet shall house all necessary
devices meant for OLTC control and indication.
f) Following cabling are specifically excluded from the scope of
the Bidder. However, interconnection drawings for the same
are to be submitted by the Bidder.
i) Cabling between Remote OLTC Panel to Cooler Control
Cabinet.
ii) Cabling between Remote OLTC panel to Local OLTC
Cabinet.
iii) Cabling between Remote OLTC to Purchaser's Panel.
iv) Cabling between Cooler Control Cabinet to Purchaser's
Panel.
v) Cabling between Local OLTC Cabinet to Purchaser's Panel.
16.1 The degree of protection shall be IP-55 in accordance with IS-2147.
MPPTCL/TECH/PROC/05/JUNE13 Page 38 of 111

16.2 The temperature indicators shall be so mounted that the dials are
not above 1600mm from ground level. Glazed door of suitable size
shall be provided for convenience of reading.
16.3 A space heater and cubicle lighting with ON-OFF switch shall be
provided.
16.4 Terminal Blocks
a) The terminal blocks to be provided shall be fully enclosed with
removable covers and made of moulded, non inflammable
plastic material with block and barriers moulded integrally .Such
block shall have washer and binding screws for external circuit
wire connections, a white marking strip for circuit identification
and moulded plastic cover. All terminals shall be clearly
marked with identification numbers or letters to facilitate
connection to external wiring.
b) All internal wiring to be connected to the external equipment
shall terminate on terminal blocks, preferably vertically
mounted on the side of each panel. The terminal blocks shall
be 1100 V grade and have 10 amps continuous rating,
moulded piece, complete with insulated barriers, nondisconnecting
stud type terminals, washers, nuts and lock nuts.
Terminal block design shall include a white fiber marking strip
with clear plastic, slip-on/clip-on terminal cover. Markings on
the terminal strips shall correspond to wire number and
terminal numbers on the wiring diagrams.
c) Terminal blocks for current transformer secondary leads
shall be provided with test links and isolating facilities. Also
current transformer secondary leads shall be provided with
short circuiting and earthing facilities.
d) Unless otherwise specified, terminal blocks shall be
suitable for connecting the following conductors on each side.
For all circuits except current transformer circuits minimum of
two nos. 2.5 mm2 copper.
For all CT circuits minimum of four nos. 4.0 mm2 copper.
e) There shall be a minimum edge to edge clearance of 250 mm
between the first row of terminal blocks and the associated

cable gland plate. Also the clearance between two rows of


terminal blocks shall be a minimum of 150 mm.
f) Arrangement of the terminal block assemblies and the wiring
channel within the enclosure shall be such that a row of
terminal blocks is run parallel and in close proximity along each
side of the wiring duct to provide for convenient attachment
of internal panel wiring. The side of the terminal block
opposite the wiring duct shall be reserved for the owner's
MPPTCL/TECH/PROC/05/JUNE13 Page 39 of 111

external cable connection. All adjacent terminal blocks shall


also share this field wiring corridor. A steel strip shall be
connected between adjacent terminal block rows at 450mm
intervals for support of incoming cables.
g) The number and sizes of the owner's multi core incoming
cable will be furnished to the successful Bidder.
16.5 One Cooler Control Cabinet and OLTC local control cabinet shall be
tested for IP-55 protection in accordance with IS-2147.
16.6 The gaskets shall be of neoprene rubber.
17.0 PAINTING
17.1 It has been observed that certain units received in the past by
us are not having good quality painting on inside & out side and with
passage of time peeling of flakes of paint takes place. In view of this
the Bidders are requested to furnish in a separate sheet painting
procedure adopted by them for internal & external surfaces of the
tank. This is an essential requirement and details should be confirmed
by the Bidders in their offer. The internal and external surfaces including
oil filled chambers and structural steel work to be painted shall be shot or
sand blasted to remove all rust and scale of foreign adhering matter or
grease. All steel surfaces in contact with insulating oil shall be painted with
two coats of heat resistant, oil insulating varnish.
17.2 All steel surfaces exposed to weather shall be given a primary
coat of zinc chromate, second coat of oil and weather resistant varnish of a
colour distinct from primary and final two coats of glossy oil and Epoxy light
gray paint in accordance with shade no.631 of IS-5.For each transformer oil
paints should be obtained from same source to ensure compatibility & proper
finish.
17.3 All paints shall be carefully selected to withstand extremes of
weather. The paint shall not scale off or crinkle or be removed by abrasion due
to normal handling. The process of painting should be clearly described.
17.4 The minimum thickness of each coat of outside painting of tank
shall be 20 microns and the total thickness shall be minimum 80 microns.
17.5 Bolts & Nuts :All bolts and nuts exposed to weather shall be hot
dipped galvanised/cadmium plated.
18.0 WIRING & CABLING
(a) All external cabling will be carried out by the purchaser based
on wiring diagram & interconnection schedule to be supplied
by the Bidder . Cable box/sealing end shall be suitable for
following types of cables :MPPTCL/TECH/PROC/05/JUNE13 Page 40 of 111

i) POWER SUPPLY 0.4 KV : 1100volts grade PVC insulated


armoured aluminum cable .
ii) CONTROL CABLE : 1100volts grade PVC insulated
7/0.737mm stranded
armoured copper cable .
Size of the Purchasers cable will be intimated to the

successful Bidder after detailed engineering.


(b) Compression type cable glands shall be provided for
termination of power and control cables.
(c) All controls, alarms, indicating and relaying devices
provided with the transformer shall be wired upto the
terminal blocks inside the Cooler Control Cabinet.
(d) All devices and terminal blocks with the Cooler Control
Cabinet shall be clearly identified by symbols corresponding to
those used on applicable schematic or wiring diagrams.
(e) Not more than 2 wires shall be connected to one terminal.
Each terminal shall be suitable for connecting two 7/0.737mm
stranded copper conductors from each side.
(f) All internal wiring shall be securely supported, neatly
arranged, readily accessible and connected to equipment
terminals and terminal blocks.
(g) Engraved code identification plastic ferrules marked to
correspond with schematic diagrams shall be fitted at both
ends of wires. Ferrules shall fit tightly on wires and shall not
fall off when the wire is disconnected from terminal block.
(h) The schematic diagrams of circuitry shall be available in the
respective cabinets (local OLTC control cabinet , local fan
control cubicle and RTCC panel). The diagrams shall be
mounted on the inner side of door of cubicle/cabinets. The
arrangements shall be such that it is not be possible to remove
the diagram from its place and diagrams are long lasting
(engraved type).
19.0 TERMINAL CONNECTORS:
19.1 Terminal connectors for HV side bushings shall be suitable for single
Zebra ACSR (28.62mm) conductor and suitable for horizontal and /or
vertical take off arrangement i.e. universal type. However, for LV side
bushings clamps shall be either suitable for double zebra ACSR conductor for
horizontal & vertical take off arrangement or for connection to 33KV single
core cable of current rating of 100 amps. Precise particulars in this regard shall
be intimated to the successful bidders.
MPPTCL/TECH/PROC/05/JUNE13 Page 41 of 111

19.2 Bushing terminals shall be provided with terminal connectors of


approved type and size for connection to external parts. Terminal connectors
offered must have been successfully type tested as per IS-5561.
19.3 All terminal connectors shall be manufactured out of gravity dye
casting process only and shall be free from blow holes, surface blisters,
cracks and cavities. All sharp edges and corners shall be blurred and
rounded off. The aluminum alloy castings, if used, shall conform to
relevant IS.
19.4 No part of the clamp shall be less than 12mm thickness.
19.5 All bolts, nuts and washers shall be of Hot Dip Galvanised.
19.6 For bimetallic clamps , bimetallic strip of not less than 2 mm
thickness shall be provided.
19.7 Flexible connectors, if provided shall be made from tinned copper
sheets.
19.8 Size of terminal (bushing stud)/conductor ( ACSR Zebra ) for which
the clamp is designed and also rated current under site conditions shall be
embossed/ punched on each part of the clamp, except hardware.
19.9 All current carrying parts shall be designed and manufactured to
have minimum contact resistance.

19.10 Clamps shall be designed corona controlled.


19.11 The nominal current rating and short time current rating of terminal
connectors shall match the corresponding rating of respective bushings.
20.0 INSULATING OIL REQUIRED FOR TRANSFORMERS
20.1 Transformer oil shall be supplied by the Bidder. The offered Price
of transformers therefore, should include first filling of oil( including wastage)
& 10% extra of that quantity. The quantity of oil for first filling including
wastage and 10% extra of that quantity should be indicated by the Bidder in
kilo-liters and in kg. The design of the transformer shall be based on the
characteristic of EHV transformer oil as per relevant IS.
20.2 Although oil for the transformer is included in the scope of supply,
but it may be noted that the transformer shall be supplied duly N2 gas filled
with suitable arrangement to ensure that the pressure of gas is regularly
maintained during transit and upto the date of filling of oil. For this
purpose, necessary gas cylinders with regulator shall be supplied on non
returnable basis. Additional gas cylinders required for recouping and
maintaining of positive Nitrogen pressure upto filling of oil should be
supplied by the manufacturer of Transformers and the offered price
should take into account this requirement.
MPPTCL/TECH/PROC/05/JUNE13 Page 42 of 111

20.3 The quality of the oil supplied with transformer shall conform to the
oil parameters specified in this clause. No inhibitors shall be used in the oil.
The oil samples of transformer will be drawn for the oil used at factory & site
as follows.
i. Prior to filling
ii. Before and after heat run test / pre-commissioning test
iii. Before energizing.
All tests as per IS:335 (latest revision) shall be conducted on oil
samples.
20.4 Sufficient quantity of oil necessary for first filling of main tank,
coolers, radiators and conservators etc. upto the proper level plus anticipated
quantity of wastage of oil during first filling shall be supplied in tankers. Please
note, wastage means quantity of oil absorbed during initial filling at works for
testing. In addition to the oil needed for first filling, 10% extra quantity of oil
for topping up in future, shall be supplied in non-returnable containers suitable
for outdoor storage. Therefore, total quantity of oil required for first filling shall
be measured at works at the time of testing on unit subjected to heat run test.
20.5 The supplier shall dispatch the transformer in an atmosphere of
pressurised Nitrogen. In this case, necessary arrangement shall be ensured by
the supplier to take care of pressure drop of nitrogen during transit and
storage till completion of oil filling during erection. A gas pressure testing
valve with necessary pressure gauge and adapter valve shall be provided.
20.6 The supplier shall warrant and confirm that oil to be used for the
transformer testing at Works & oil to be supplied for the transformer is free
from Polychlorinated Biphenyls (PVB/PCB). The transformer oil to be used
and supplied by the bidder for first filling at site shall be new oil of EHV Grade-I
having technical specification mentioned hereunder . Hence Oil to be used
by the manufacturers at factory for the purpose of testing at their
works shall be of similar or better quality having parameters matching
with the parameters specified in the specification. Specific approval of
oil test results of oil proposed to be used for testing of transformer in
factory shall be obtained by the manufacturer from the purchaser
before first filling in the unit. MPPTCL shall not accept any other oil for
testing purposes having lower parameters than those specified in the

Bid. Bidders should specifically confirm this requirement in their offer.


Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
MPPTCL/TECH/PROC/05/JUNE13 Page 43 of 111

Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
1. Appearance The oil shall be clear
and transparent and
free from suspended
matter or sediment
A representative
sample of oil shall be
examined in a 100
mm thick layer at
ambient
temperature.
2. Density at 29.5oC
(maximum)
0.89 gm/cm3
IS:1448
3. Kinematics viscosity at
27oC (minimum).
27 CST IS:1448
4. Interfacial tension at
27oC (minimum).
0.04 N/m
IS:6104
5. Flashpoint Pensky
Marten (closed)
(minimum).
140oC IS:1448
6. Pour point. (maximum) -6 oC IS:1448
7. Neutralization value
(Total acidity maximum)
0.01 mg KOH/g
IS:335 Appendix `A
8. Corrosive Sulphur Non-corrosive IS:335 Appendix `B
9. Electric strength
(breakdown voltage)
Minimum.
a. New unfiltered oil (as
received condition).
b. After filtration
40 KV (rms)
60 KV (rms)
IS:6792
10. Dielectric dissipation
factor (tan delta) at
90oc Maximum.
0.002 IS:6262

11. Specific resistance


(resistivity)
a. at 90oC Minimum.
b. at 27oC Minimum.
100x1012 ohm.cm
1500X1012 ohm.cm
IS:6103
12. Oxidation stability
a. Neutralisation value
after oxidation,
maximum.
b. Total sludge, after
oxidation Maximum
0.20 mg KOH/g
0.02 percent by
weight
MPPTCL/TECH/PROC/05/JUNE13 Page 44 of 111

Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
13. Presence of oxidation
inhibitor
The oil shall not
contain antioxidant
inhibitors .
IS:335
Appendix `D
14. SK value 6% maximum IS:335
15. Water content,
maximum.
10 ppm IS:2362
16. Ageing characteristics
after accelerated ageing
(open Breaker method
with copper catalyst)
a) Resistivity
i. 27oc
ii. 90oc
b) Tan delta at 90oc
c) Total acidity
d) Sludge content
by weight
2.5x1012 ohm.cm
(min.)
0.2x1012 ohm.cm
(min.)
0.15 (max.)
0.05 mg
KOH/gm(max.)
0.05% (max)
As per ASTM-D
1934/ IS 12177
17. Oil sample taken from

the transformer after


the completion of site
processing and tested in
approved manner shall
have the following
values before
commissioning of the
transformer.
i. Break down
strength
ii. Moisture content
iii. Resistivity at 90oc
minimum
iv. Interfacial Tension
at 27oc
v. Dielectric
dissipation factor at
90 oC
Minimum 70 KV
withstand
Maximum of 10 ppm
35x1012 ohm.cm
(min)
0.04 N/M (min)
0.002 (max.)
Tested in accordance
with IS :335
MPPTCL/TECH/PROC/05/JUNE13 Page 45 of 111

Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
18 N-dm analysis
CA%
CN%
CP%
4 6%
40-43%
51-54%
20.7 AIR CELL : Our technical specification calls for supply of power
transformers with air cell type oil preservation system of PRONOL, make only.
It is obligatory on the part of the Bidders to clearly submit complete
constructional and technical details of sealing arrangement, duly supported
with technical details, pamphlets and dimensional drawings. While
furnishing details for the above sealing arrangement the Bidders must
confirm clearly that the size and capacity of sealing arrangement is
adequate for the transformer and for the quantity of oil required for the
transformers. Necessary calculation/documentary proof shall be furnished.
20.8 Air cell type oil preservation system included with each transformer
shall ensure as under:
(a) The air inlet of COPS (Conservator Oil preservation System)
shall be properly fitted on the conservator for leak proof
arrangement to ensure that the air does not come in contact
with oil under any circumstances.

(b) The size and capacity of the COPS (Conservator Oil


preservation System) shall be selected to suit the design of
Conservator and to ensure proper operation for the quantity of
oil in the unit with the proper allowances. The COPS shall be of
reputed make, proven design and of established performance.
Details in this regard are to be submitted with the offer by the
Bidder for verification . The Bidder is required to submit
calculation with bid to prove adequacy of air cell & its size.
(c) The Bidder shall clearly indicate in the manual the
procedure for installation of COPS and precautions to be
taken at the time of first oil filling under vacuum in the
transformer.
20. 9 SPECIFICATION OF FIRE PROTECTION SYSTEM : Nitrogen
injection type fire prevention & extinguishing system with flow sensitive
conservator isolation valve shall be provided for all the transformers.
20.9.1 Nitrogen Injection Fire Protection System (NIFPS) shall be
designed to prevent explosion of transformer tank and the fire during internal
faults resulting from arc and also to extinguish the external oil fires on
transformer/ reactor due to tank explosion and/or external failures like bushing
fires, OLTC fires and fire from surrounding equipments, etc. The system shall
work on the principle of Drain & stir. On activation, it shall drain a pre MPPTCL/
TECH/PROC/05/JUNE13 Page 46 of 111

determined quantity of oil from the tank top through drain valve to reduce the
tank pressure, isolate conservator tank oil and inject nitrogen gas at high
pressure from the bottom side of the tank through inlet valves to create
stirring action and reduce the temperature of oil below flash point to extinguish
the fire. The quantity of oil removed from the tank shall be such that adequate
amount of oil shall remain to cover active part, i.e. core coil assembly even
after stoppage of oil drain. Electrical isolation of transformer shall be an
essential pre-condition for activating the system.
20.9..2 OPERATIONAL CONTROLS: The system operation shall be fully
automatic and activate from the required fire and other trip signals. In addition
to automatic operation, remote operation from control room/ remote centre
and local manual control in the fire extinguishing cubicle shall also be provided.
System shall operate on following situations.
20.9.3 PREVENTION OF TRANSFORMER EXPLOSION AND FIRE: To
prevent transformer explosion and fire in case of an internal fault, signals
given by operation of Electrical protection relays and tripping of circuit breaker
of transformer and operation of either Buchholtz relay, or pressure relief valve
(PRV) alongwith Rapid Pressure Rise Relay (RPRR) shall be used to
activate the system and logic for RPRR for system activation should
include for operation of Electrical protection relays and tripping of
circuit breaker of transformer. The exact logic for system activation shall be
finalized during detailed engineering.
20.9..4 FIRE PROTECTION: In case of fire, sensed by fire detectors, the
system shall be activated only after electrical isolation of the transformer,
confirmed by breaker trip. If the fire detection is not associated with any other
fault, the system activation shall be only manual. Manual operation switch shall
be provided in the control room/ remote control centre with a cover to avoid
accidental operation of it.
20.9.5 OPERATION OF SYSTEM: On receiving activation signal, the
following shall take place:
i. Open the quick opening drain valve to drain the top layer oil
ii. Shut off the conservator isolation valve to prevent flow of oil from the

Conservator tank to the main tank.


iii. Open the Nitrogen regulator valve to inject Nitrogen into the transformer
tank to create stirring of oil.
There shall be interlock to prevent activation of the system if the transformer
is not electrically isolated. There shall also be provision for isolating the system
during maintenance and/or testing of the transformer.
20.9.6 TECHNICAL PARTICULARS: The supplier shall be responsible for
the design of the complete system and shall submit the drawings and design
calculations for the number of fire detectors, pipe sizing of drain pipe and
MPPTCL/TECH/PROC/05/JUNE13 Page 47 of 111

Nitrogen injection pipe, Nitrogen cylinder capacity, number of injection points,


etc. and get approval from. Facility shall be provided to test the system when
the transformer is in service, without actually draining the oil and injecting
Nitrogen. The Nitrogen regulator valve shall be designed in such a way that the
Nitrogen shall not enter the transformer tank even in case of passing/ leakage
of valve. The system shall work on station DC supply. MPPTCL shall give two
distinct DC feeders in control. The control box of fire protection system shall
have facility to receive these feeders for auto change over of supply. It shall be
the contractors responsibility to further distribute power to the required
locations.
Following indications and alarms shall be provided in the cubicle as well as the
control box: Nitrogen cylinder pressure indication.
Nitrogen cylinder pressure low.
Fire in Transformer/ Reactor.
Oil drain started.
Conservator oil isolation valve closed.
Nitrogen injection started.
20.9.7 DETAILS OF SUPPLY & WORK FOR SYSTEM EQUIPMENTS AND
OTHER RELATED ACTIVITIES: The scope of supply shall include the
following items, any other items required for safe & trouble free operation of
the system and the scope of works include complete earthwork (i.e.
excavation, backfilling etc.), scope of supply also includes services to be
availed by the purchaser for erection and commissioning of NIFPS at EHV
substations
of MPPTCL in MP. , civil work with civil material for the entire open/
buried piping for the fire protection system, construction of safety wall,
construction of oil pits with provision of oil storage tank of MS and pipe
supports for open/ buried, entrenched and over ground piping. The system
design shall also conform to TAC/NFPA norms.
(i) Fire extinguishing cubicle with base frame and containing at least the
following:
Nitrogen gas cylinder of sufficient capacity with pressure regulator and
manometer with sufficient number of adjustable NO contacts.
Oil Drain Assembly including oil drain pipe extension of suitable size for
connecting pipes to oil pit.
Mechanical release device for oil drain and nitrogen release.
Limit switches for monitoring of the systems.
Panel lighting.
Flanges on top of the panel for connecting oil drain and nitrogen injection
pipes for transformer.
Limit switch for pressure switch/sensor.
Pressure indicators for Nitrogen pressure in the cylinder and after
Nitrogen regulator.

(ii) Control box to be installed in the control room of the station for monitoring
system operation, automatic control and remote operation, with alarms,
indication light, switches, push buttons, audio signal, suitable for tripping and
signaling.
MPPTCL/TECH/PROC/05/JUNE13 Page 48 of 111

(iii) Conservator isolation valve which shall be flow sensitive and shut off when
the flow in the pipe is more than the flow expected in the permissible normal
operating conditions. It shall be provided with position indicator remote alarm
indication.
(iv) Required number of fire detectors to be located in strategic locations to be
finalized during detailed engineering.
(v) Flow Sensitive Conservator Isolation Valve
(vi) All controls, alarms, panels, cables, cable trays (if required), junction
boxes etc.
20.9.8 INSTALLATION AND PRE-COMMISSIONING TEST: After
installation the system pre-commissioning tests shall be carried out jointly with
the MPPTCL representative before the system is put in service.
20.9.9 In order to restrict the supply of oil in case of a fire in transformer,
provision shall be made to isolate the conservator oil from the main tank.
20.9.10 A valve which shall be flow sensitive and shut off when the flow in the
pipe is more than the flow expected in the permissible normal operating
conditions. This valve shall be located in the piping between the conservator
and the buchholz relay and shall not affect the flow of oil from and to the
conservator in normal conditions.
20.9.11 When the flow from conservator to main tank is more than the normal
operating conditions, the valve shall shut off by itself and will have to be reset
manually. It shall be provided with valve open/close position indicator along
with alarm indication in control room during closing operation of valve.
20.9.12 The necessary switches shall be provided in cooler control cabinet /
common marshalling box for manual open / close operation of the valve.
Bidders shall offer Transformers completely fitted with Nitrogen
Injection Fire Protection Systems and also indicate cost of complete
system, separately in their offer in Schedule of prices.
20.10 ON LINE MONITORING DEVICE FOR TRANSFORMER
20.10.1 The Bidder should offer for a suitable on line monitoring device
for regular monitoring of 3 key gases and moisture for condition assessment
and fault detection of the 220 KV transformer . The device should measure 3
key dissolved gases viz. Hydrogen, Acetylene, Carbon mono oxide with
accuracy of 10%. The minimum range of measurement of dissolved gases
shall be Hydrogen :5 to 500, Acetylene : 3 to 5000, Carbon mono oxide : 10
to 5000 . The moisture content shall be measured from 0 to 100 % RS (in
ppm). The device shall have non volatile memory storage to prevent loss of
data. The device shall be provided with user configurable at least six alarm
contacts & two front panel LED arrays. The alarm setting screen shall be
available for setting alarms based on level of 3 Key gases or moisture and
rates of change for Key gases. For configuring the six alarm settings, suitable
PC software shall be provided with the device. The device shall be supplied
with two separate channels for remote communication plus local USB and
MPPTCL/TECH/PROC/05/JUNE13 Page 49 of 111

Ethernet connections. The device should support communication Protocol viz.


MODBUS, DNP 3.0 and IEC-61850. It shall be possible to configure sampling
rates to hourly/ daily. The alarm & Caution thresholds shall be user
configurable. The device should support Load monitoring by analyzing results
with loading of Transformer and device shall be provided with suitable
software for graphical trending & diagnostic analysis of results. The device shall

have minimum maintenance requirements.


On line monitoring unit shall not be mounted on the body of the
transformer. A separate mounting arrangement near the transformer body with
proper protective sheds & covers for protection against sun and rains be
provided. The mounting cubical shall have provision for ventilation/cooling and
also provision for reading of parameters by operators without opening the
box. On line monitoring unit shall be complete with provision for remote
monitoring alarm and indication in RTCC panel in control room. Complete
details of offered device shall be submitted by the Bidder and explained by
suitable manual/pamphlets.
External temperature range : 0 to 55 o C
Operating Humidity : 10 to 95% RH non condensing
Enclosure : IP55
Input Power requirement : Voltage 120 to 260 V AC, Frequency 47 to 60
Hz; The power supply should be able to withstand
electrical surges & disturbances prevalent in EHV
substation.
20.10.2 Bidders shall offer Transformers completely fitted with On Line
Monitoring Device for Transformer of Kelman & equivalent make,
suitable for monitoring of 3 Key gases.
20.11 THERMOSYPHON FILTER: Atleast four Nos. of Thermosyphon filter
arrangement each of capacity 1/5th of the total oil flow in the cooler shall be
provided with rigid support (i.e., slotted one not acceptable) on the
transformer along with connecting piping, isolating valves at either end, drain
plug shall be mounted on the transformer. It will have Alumina trap and will
be designed in such a way that 1/5th of the forced oil circulation passes
through it. The quantity of absorbent will be 0.25% of the total weight of total
oil in the transformer, cooler, conservator etc. Spare alumina for one time
replacement shall be also supplied by the supplier. The location of
Thermosyphon filter should be in such a way that same do not interfere with
any of the existing equipments. The Thermosyphon filter shall be located at
diagonally opposite points of transformer and out of four filters, two filters shall
be with pumps .The connecting pipes of Thermosyphon filter to tank shall be
provided with flexible couplings. It may be noted that rigid supports shall be
provided for thermosyphon filter i.e., slotted type of fixing arrangement is not
acceptable.
20.12 SILICAGEL BREATHER : Minimum 2 nos. dehydrating filter Silica Gel
Breathers each of 100% breathing capacity are required and the same shall be
MPPTCL/TECH/PROC/05/JUNE13 Page 50 of 111

provided. Size of breather and its pipe connection is to be indicated. However,


each breather of minimum capacity of 8 Kg having its pipe connection of
minimum size of one inch dia shall be preferable. Suitable arrangement for
parallel mounting of breathers shall be made for connecting both the Silica Gel
Breather to the main conservator.The passage of air should be through dual
filter & Silica Gel. Silica Gel shall be isolated from atmosphere by an oil seal.
Adequate supports are required to be provided for pipe connection to avoid any
swing in air.
The capacity of silicagel breather shall be adequate to ensure supply of dry air
only for the volumetric expansion/contraction of oil keeping in view the total
quantity of oil in the unit. The container of the breather shall be made of
metal with glass enclosure along its periphery to ensure that the transparency
(to verify the colour of dehydrating agent) is maintained during operation
directly under sunlight (ultra violet rays) for long life. The quantity of the
dehydrating agent shall be sufficient keeping in view the climatic condition

specified and that the breather will be maintained generally two times in a
year. This applies to all the breathers provided with the transformer.
21.0 FITTINGS & ACCESSORIES FOR THE POWER TRANSFORMERS
21.1 The transformers will be supplied complete with all fittings and
accessories exactly in line with various requirements indicated in Annexure II
in this technical specification. The basic offered cost must take into
consideration cost of all fittings and accessories as under and indicated
elsewhere in this specification .
21.2 The equipments and accessories furnished with the
transformer shall be suitably mounted on the transformer for ease of
operation, inspection and maintenance and the mounting details shall be
subject to the approval of the purchaser. All valves shall be provided either
with blind companion flanges or with pipe plugs for protection.
21.3 Indication, alarm and relay equipment shall have contacts suitable
for operation with 110V/220V DC supply. Any other accessories or appliances
recommended by the manufacturer for the satisfactory operation of the
transformer shall also have 110V/220V DC as input.
a) OLTC and its controls shall be as per clause 14.
b) All cabinets & panels shall be conforming to
stipulations under Clause-16 .
c) All 245KV & 72.5KV phase and 72.5 KV neutral bushings shall
be of OIP condenser type and as per Clause 11.13 .
21.4. Equalizing pipes for maintaining equal pressure between main tank
and OLTC and at various other locations as per design shall be provided. These
equalizing pipes shall be routed such as not to create any obstruction.
MPPTCL/TECH/PROC/05/JUNE13 Page 51 of 111

21.5 Accessories, which are necessary for satisfactory operation of


Transformer shall be deemed to have been included in the accepted price
without any extra cost to the Purchaser.
21.6 It may be noted that all the name plates/rating plates/diagram
plates on transformer shall be engraved type/anodized type and shall be fixed
using rivets/spot welding method. The method of printing of letters on the R&D
plate shall be such that inscriptions shall not fade by ultra violet rays and other
adverse weather conditions under which the same is subject to during service
life of transformers.
(a) Rating & Diagram Plate: In the R&D plate following additional
information over & above as specified in the IS/CBIP specification shall
be provided.
- Weight of the copper for windings
- Weight of the core laminations for core
- Weight of insulation
- Transport weight
- Weight of steel
- Untanking weight (Core & Coil)
- Total weight of Transformer Tank along with Fittings &
Accessories and oil.
- Percentage Impedance at all taps
- HV winding resistance of all phases at all taps
- LV winding resistance of all phases
- Weight of the oil for first filling in Kg/Liters
- Total quantity of oil (including wastage) and 10% extra
quantity in Kg/Liters
- If required two separate R& D plates may be used.

(b) Valve Schedule Plate: In the valve schedule plate, at least two views
should be inscribed so that location of all the valves provided on the
transformer could be indicated/visualised. In the table of valve schedule
plate, details of valves viz. type of valve, material of valve, size of valve
& position of valve during transportation and after commissioning shall
be clearly indicated. The size of the letter shall be such that the same
be visible clearly to a person standing away at a distance of one meter
from the respective vertical face of the transformer.
(c) Instruction Plate For Oil Filling in the Conservator with Air Cell:
An instruction plate shall be provided for oil filling in the conservator
having air cell type breathing arrangement. In addition to the
instructions for oil filling on this plate, a diagram indicating mounting
details of MOLG, oil level gauges, air cell inside the conservator with a
pictorial view of conservator including make, type & size of air cell shall
also be inscribed. The location of plate should be such that same is
visible to operating personal from a distance as mentioned in (b) above.
22.0 CENTRE OF GRAVITY : The centre of gravity of the assembled
transformer shall be low and as near to the vertical centre line as possible.
The transformer shall be stable with or without oil. If the centre of gravity is
MPPTCL/TECH/PROC/05/JUNE13 Page 52 of 111

eccentric relative to track gauge either with or without oil, its location shall
be shown on the outline drawing.
23.0 PACKING
23.1 The packing may be in accordance with the Bidder's standard
practice but Bidder should give full particulars of packing for the approval of
the purchaser. Special arrangements should be made to facilitate handling
and to protect the projecting connections for damage in transit.
23.2 The transformer shall be transported filled with inert gas preferably
Nitrogen gas. The Bidder shall ensure that adequate pressure of gas is
maintained inside the tank throughout during transportation by sending
escorts and required apparatus and equipment with the transformers.
23.3 All parts shall be adequately marked to facilitate field erection.
Boxes and crates shall be marked with the contract number and shall have
a packing list enclosed showing the parts contained therein. however the
verification of accessories shall be done in presence of suppliers
representative.
24.0 TESTS
24.1 The manufacturer shall carryout routine test ,additional routine
tests and type tests on the transformers as per the relevant Indian Standard
IS-2026 with latest amendments , IEC 60076,CBIP Publication No 295,IEEE or
any equivalent International Standard .The details of tests are specified
hereunder. It should be specifically noted by the Bidder that testing of each &
every transformer included in this Bid specification shall be carried out at the
manufacturers works in fully assembled condition complete with all fittings &
accessories.
24.2 ROUTINE TESTS AND ADDITIONAL ROUTINE TESTS:
All routine tests and additional routine Tests detailed under clauses
24.2.1 & 24.2.2 herein under will be carried out on each transformer on "free
of cost" basis, in accordance with IS:2026 part-I.
24.2.1 ROUTINE TESTS
a) Measurement of winding resistance as per cl.16.2 of IS 2026
Part I. The winding resistance shall be measured on all taps and
of all the three phases and values be recorded in respective test
certificates.

b) Measurement of voltage ratio at all taps and checking of


voltage vector relationship as per cl.16.3 of IS 2026 Part I.
c) Measurement of Impedance voltage/ short circuit impedance
(at all taps) & load loss (at principal tap & extreme taps) as per
cl.16.4 of IS 2026 Part I, IEC 60076.
MPPTCL/TECH/PROC/05/JUNE13 Page 53 of 111

d) Measurement of no load loss at 90%,100%,110% of rated


voltage & no load current as per cl.16.5 of IS 2026 Part I.
e) Measurement of insulation resistance as per cl. 16.6 of IS
2026 Part I.
f) Dielectric tests as per cl.16.7 of IS 2026 Part I , IEC 60076 as
per latest version.
g) Tests on OLTC as per cl.16.9 of IS 2026 Part I.
h) Measurement of Tan-Delta, Capacitance & IR values of HV, LV &
Neutral bushings before after tests on transformer.
i) Low voltage AC, magnetic balance and magnetizing current
three phase & single phase at normal tap for field reference.
The test shall be carried out only after ensuring proper demagnetization
of the core so as to achieve proper results.
Note : DGA test of oil of main tank of transformer before (initial)& after
completion of all testing shall be done and test results shall be submitted to
the purchaser .
24.2.2 ADDITIONAL ROUTINE TESTS
(A) Insulation Resistance : Insulation Resistance
measurement shall be done for 15 Secs. , 60 secs. and 600
secs. Duration. Polarization Index (PI) shall be clearly
recorded on test report for 600 sec /60 sec values and D.A.R.
for 60 sec/15 sec values.
PI value : PI value (i.e. ratio of IR Values for 600 sec /
IR Values for 60 sec) for winding should be greater than
2.0. This requirement is to be confirmed specifically by
the Bidders in their offer.
(B) Magnetic Circuit Test :After assembly, core shall be tested
for 1 minute at 2000 volts AC between all bolts, side plates &
structural steel work. Immediately prior to the despatch of the
transformer from works of manufacturer, the magnetic
circuit shall be tested for one minute at 2 KV AC between the
Core & Earth and leakage current shall also be recorded.
(C) Oil Leakage Test on Tank : All Transformer tank with its
active part as assembled for type test (i.e. including pipe work
and cooling equipment and excluding PRV and conservator
when air cell is provided) shall be subjected to a pressure
corresponding to twice the normal head of oil or to normal
pressure plus 35 kN/ m.sq. whichever is lower measured at
the base of the tank and will be maintained for 12 hours
during which time no leakage shall occur. Before conducting
the pressure test, the following are to be taken care of :
(i) Pressure relief valve are to be removed and the opening
blanked .
MPPTCL/TECH/PROC/05/JUNE13 Page 54 of 111

(ii) Transformer and tap changer conservators are to be


disconnected.
(iii) Diverter switch compartment of tap changer to be
connected with transformer tank for equalising the
pressure on both sides.

(iv) Oil should be completely filled and all trapped air


released.
(D) Capacitance & Tan-delta Test on winding : The
measurement of capacitance and tan delta to determine
capacitance between winding & earth shall be carried out before
and after series of dielectric tests by Ampere turn method. For
temperature correction factors IEEE C.57.90 shall be referred.
The measured Tan delta values of winding shall not
exceed 0.45% at 200C (degree Centigrade) temperature.
In case Tan delta of transformers during testing at works
of manufacturer is measured above maximum ceiling of
0.45% at 200C (degree Centigrade) temperature, then
MPPTCL reserves right not to accept such of the
transformer. This requirement is to be confirmed
specifically by the Bidders in their offer.
(E) Test Results of calibration & measurement reports of
WTI CT & ratio test for bushing CT.
(F) Checking & recording of following:
a. IR values
i. Between Core and End frame
ii. Between Core and Tank
iii. Between End frame and main Tank.
The measured IR values should be more than 1000 M
Ohms. This requirement is to be confirmed specifically by
the Bidders in their offer.
b. Measurement and recording of currents with
application of 400 volts, 3phase, AC supply on HV side
with LV side shorted, as under
i. Between Core and Tank.
ii. Between Core and End frame
iii. Between End frame and Tank
iv. Between neutral and short circuited links with neutral
grounded and ungrounded conditions.
NOTE: The details of arrangements provided outside the main tank
for connecting core, end frame and main tank body shall be indicated
on a diagram , to be attached with the test reports.
(G) Magnetising current measured with LT supply.
MPPTCL/TECH/PROC/05/JUNE13 Page 55 of 111

With Single phase


supply
With Three phase
supply
Volts. Amps. Volts. Amps.
a On HV
side
b On LV
side
(H) Magnetic balance test on HV and LV side
(I) Pressure Relief Device Test :All pressure relief devices
provided in each transformer shall be subject to test for its
successful operation. It shall operate before reaching the test
pressure specified in clause 24.3 (C) of this specification. The
device shall seal off after the excess pressure has been
relieved.

(J) Frequency Response Analysis (SFRA) Test on Transformer


: The SFRA test shall be conducted by the manufacturer
at manufacturers works using his own SFRA test set and
also SFRA test shall be conducted by the manufacturer
at site using same SFRA test set at the time of erection &
commissioning of unit.
(K) Measurement of Dew point prior to despatch of the unit,
filled with N2 gas: Dew point is the temperature at which
water vapours present in the gas filled in the transformer
begins to condense. The transportation of transformer
from the factory of manufacturers works upto the
purchasers site is done with dry Nitrogen gas filled
condition, due to weight limitation. Positive gas pressure
say 0.25 kg/cm2 is normally maintained during
transportation as well as during storage. In case positive
pressure is not maintained then due to hygroscopic
properties of insulation used in transformer possibility of
absorption of moisture in insulation can not be overruled.
Therefore to check the dryness of insulation,
measurement of dew point at factory prior to despatch
and at site prior to oil filling is necessary and to be
carried out. It may be noted that dew point shall be
measured at factory prior to despatch. Temperature,
pressure and dew point at the time of gas filling (reading
taken after stabilisation) shall be taken and painted on
the transformer tank. The minimum permissible value of
dew point shall be ()25oC at normal temperature and
pressure.
(L) Functional tests on auxiliary equipments i.e. OTI,WTI,
valves etc as per CBIP publication no 295.
MPPTCL/TECH/PROC/05/JUNE13 Page 56 of 111

24.3 TYPE TESTS : Following Type Tests shall be conducted on one


transformer of each manufacturer (if there are more than one manufacturer)
as per IS:2026 Part I.
(A) Temperature Rise Test : This test as per cl. 16.8 of IS:2026 (PartII) shall be conducted at the lowest voltage tap having maximum
current with 10% over load condition. The supplier before carrying
out such tests, shall submit detailed calculations showing the
alternatives possible, on various taps and for different ratings
(ONAN/ONAF), of the transformer and shall recommend the
combination that results in highest temperature rise, for the test.
Gas chromatographic analysis of oil shall be conducted before and
after heat run test and the values shall be recorded in the test
report. The sampling shall be in accordance with IEC-567. For the
evaluation of the gas analysis in temperature rise test, a method
will be proposed which is based on the rate of increase of
particular gases and the permissible limits of minimum detectable
value of gases and the maximum limit will be mutually discussed
and agreed upon between the Purchaser and Supplier. This shall be
treated as reference during maintenance of transformer in future.
The calibration of OTI and WTI shall be done by
Transformer Manufacturer and these calibrated OTI,WTI shall be
used during testing of transformer. The Sr.No. of WTI,OTI shall be
recorded during testing of transformer and these indicators only

shall be supplied with the transformer. During test the


manufacturer selects suitable tap from CT based on gradient
between the reading of WTI & OTI . This tap position is to be
clearly recorded on test report so that selection of correct tap could
be done at site to avoid discrepancy in temperature gradient
recorded during factory test and the value recorded at site.
(B) Impulse Test on line terminals as per IS 2026 part III, on one
transformer of Bid
(C) Tank tests : Following Vacuum and Pressure tests shall be carried
out on one transformer tank.
(a) Vacuum Test (Fabrication stage) : One transformer tank
of each design shall be subjected to the vacuum of 760 mm of
Hg. The tanks designed for full vacuum (760 mm of mercury at
sea level or the barometric reading at the location of test) shall
be tested at a maximum internal pressure of 3.33 kN/m.sq.
(25 mm of Hg) for one hour i.e. 760-25=735 mm of Hg at sea
level and (Barometric reading -25mm Hg) at other location.
The permanent deflection of flat plates after vacuum has been
released shall not exceed the values specified below:
MPPTCL/TECH/PROC/05/JUNE13 Page 57 of 111

Horizontal Length of flat


plate (in mm)
Permanent Deflection
(in mm)
Up to and including 750 5
751 to 1250 6.5
1251 to 1750 8
1751 to 2000 9
2001 to 2250 11
2251 to 2500 12.5
2501 to 3000 16
Above 3000 19
(b) Pressure Test (Fabrication stage) : One transformer tank of
each design, its radiator, conservator vessel ,and other fittings
together or separately shall be subjected to a pressure
corresponding to twice the normal head of oil or to normal
pressure plus 35 kN/m2, whichever is lower, measured at the
base of the tank and will be maintained for 1 hour during
which time no leakage shall occur. The permanent deflection of
the flat plate after the excess pressure has been released shall
not exceed the figures specified above for vacuum test as per
clause 24.3(C)(a).
24.4 SPECIAL TESTS : Following special tests other than type and
routine tests shall also be carried out as per IS:2026 Part-I on one
transformer of each manufacturer (if there are more than one manufacturer)
a) Measurement of zero seq. impedance as per CL.16.10 of IS:2026 Part-I.
b) Measurement of acoustic noise level as per CL.16.12 of IS:2026
Part-I,NEMA TR1 & IEC 60076-10. Detailed calculations & conditions
outlined in the IEEE standard C 57.12.12.90 shall be followed.
c) Measurement of power taken by fans as per cl.16.14 of IS:2026
Part-I.
d) Measurement of harmonic level of no load current and total harmonic
distortion of voltage & current as per CL.16.13 of IS:2026 Part-I. Details
of rms voltage applied & print out of Harmonic Analyser shall be

enclosed with report.


e) One Cooler Control Cabinet and OLTC cabinet of each type of
transformer shall be tested for IP:55 protection in accordance with
IS:2147.
f) Test to prove over fluxing capability of transformer.
24.5 To summarize the requirement of tests for 220KV 50MVA
power transformers covered in this Bid specification, are as under :
MPPTCL/TECH/PROC/05/JUNE13 Page 58 of 111

Clause
No.
Nature of tests
Number of
transformers to
be tested
Test charges
1234
24.2.1
&
24.2.2.
Routine tests &
additional routine
tests
On each unit While offering for the Bid, cost
of all these tests for specified
no. of units as per column 3
should be included in the total
Bid price. Thus no additional
charges shall be payable for
any of the tests and
therefore, offered Bid price
should account for all the
costs to be incurred for this
purpose
24.3 Type test:
(A)Temperature
rise test
On one unit
included in Bid
(B)Impulse test On One Unit of
Bid
(C)Vacuum and
pressure test
On One unit of
Bid
24.4 Special tests On One unit of
Bid
24.7 Tests at site On each unit
included in Bid
Note : It is to be noted that after complete final testing of the unit , it
should be kept charge at rated voltage for adequate time to ensure
proper demagnetization of core i.e. demagnetization of core shall be
ensured prior to dispatch of the unit.
24.6 Oil to be used by manufacturers at factory for the purpose of
testing at their works shall be of similar or better quality having

parameters matching with the parameters specified in the


specification. Specific approval of oil test results of oil proposed to be
used for testing of transformer in factory shall be obtained by the
manufacturer from the purchaser before first filling in the unit. MPPTCL
shall not accept any other oil for testing purposes having lower
parameters than those specified in the Bid. Bidders should specifically
confirm this requirement in their offer.
25.0 TESTS AT SITE :On delivery /receipt, after erection at site, the
transformer shall be subject to the following tests, in presence of
supplier's engineer.
(i) Immediately upon receipt of transformer at site and before
unloading of transformer from trailer, core earthing , end frame
earthing & tank earthing shall be checked . Only after
satisfactory verification that there is no multiple core
earthing in transformer, unloading of transformer shall be
undertaken.
ii) Insulation resistance test and polarisation index.
iii) Ratio and polarity test.
MPPTCL/TECH/PROC/05/JUNE13 Page 59 of 111

iv) DGA of oil and Dielectric, Tan-Delta, resistivity & moisture


content test of oil .
v) OLTC operational test at each tap for lower and raise operation
of tap changer.
vi) Magnetic balance test and measurement of magnetizing
current.
vii) Vector group test.
viii) Percentage Impedance test at all taps.
ix) Short circuit current measurement at low voltage and at all
taps.
x) Measurement of winding resistance at all taps.
xi) Tangent Delta, capacitance and insulations resistance tests of
bushings.
xii) Leakage current between core & tank, core & end frame , end
frame & tank and between short circuited links & neutral in
grounded and un grounded conditions.
xiii) Dew point measurement & recording of pressure of Nitrogen
gas.
xiv) SFRA test
xv) After receipt of transformer at site physical inspection shall be
done for checking any physical damage to transformer tank &
accessories. Further data of Impact recorder shall be analysed
for any changes before unloading of transformer.
26.0 CHECKS & TESTS : Following checks & tests shall be carried out by
Manufacturer at different stages of manufacture & supply of transformer and
these reports shall be sent to the purchaser for records :
(i) Assembled Transformer:
a) Check completed transformer against approved out line drawing,
provision for all fittings, finish level etc.
b) Jacking test on the assembled Transformer.
c) Measurement and recording of temperature and drying time during
vacuum treatment.
d) Check for completeness of drying by measuring IR values & Tan
Delta.
e) Certification of all test results.

(ii) Preshipment Checks at Manufacturer's Works:


a) Check for interchangeability of components of similar Transformers for
mounting dimensions.
b) Check for proper packing and preservation of accessories like radiators,
bushings, explosion vent, dehydrating breather, rollers, buchholz relay,
control cubicle, connecting pipes, conservator etc.
MPPTCL/TECH/PROC/05/JUNE13 Page 60 of 111

c) Check for proper provision of bracings to arrest the movement of core


and winding assembly inside the tank.
d) Gas tightness test to conform tightness.
e) Derivation of leakage rate and ensure adequate reserve gas capacity.
(iii) Commissioning Checks at site :
a) Check the colour of silicagel breather.
b) Check the oil level in the breather housing, conservator tank, cooling
system, condenser housing etc.
c) Check the bushings for conformity of connection to the line etc.
d) Check for correct operation of all protection and alarms.
i) Buchholz relay
ii) Excessive winding temperature
iii) Excessive oil temperature
iv) Low oil flow
v) Low oil level indication
e) Check for adequate protection on electric circuit supplying the
accessories.
f) Insulation resistance measurement for:
i) Control wiring
ii) Main winding
g) Check for cleanliness of the Transformer and the surroundings.
27.0 TEST REPORTS : After all tests have been completed seven
certified copies of each test report shall be furnished. Each report shall
supply the following information :i) Complete identification data including serial number of the
transformer.
ii) Method of application, where applied, duration and
interpretation of results for each test. Complete diagram of test
circuits and details of test equipments including auxiliary
transformer, Instrument transformer shall be furnished.
iii) Where ever applicable parameters to be corrected to 75 C
temperature.
iv) Test certificates of all the accessories and stage
inspections.
28.0 TOOLS : The transformer shall be supplied with a full outfit of
tools, spanners, special tools for assembling and dismantling transformers
MPPTCL/TECH/PROC/05/JUNE13 Page 61 of 111

with a rack for holding them as per Annexure X. All spanners shall be double
ended & case hardened. The quantity of each item of tools shall be indicated
by the Bidder in Bid.
29.0 DRAWINGS & INSTRUCTION MANUALS
29.1 SPECIFIC REQUIREMENT FOR GENERAL ARRANGEMENT
DRAWING: For our 220KV switch yard, the bay width adopted is 15 metres.
Following points shall be kept in view while finalizing General Arrangement
drawing of the transformer.
i. Along transverse direction (i.e. the parallel to the Bushing line)
spread of the transformer from one extreme end to the other
extreme end shall be limited to 15 meters. This spread shall be

distributed symmetrically with respect to the centre line of the


transformer ( i.e. 7.5 meters on either sides) This is an essential
requirement to avoid encroachment of the transformer body in the
adjoining bay.
ii. Along the longitudinal direction the 220KV lightning arrestor are
located at a distance of 7.5 meters from centre line of the
transformers. While deciding arrangement of location of the
accessories, this requirement needs to be kept in view from
consideration of clearances.
29.2 The drawings for each items of transformer and its accessories are
to be submitted to MPPTCL at the time of obtaining approval of
manufacturer.
29.3 As soon as possible after the award of the contract the
manufacturer shall supply Instruction Manual. This Instruction Manual
shall be hard bound manual shall contain set of all approved drawings,
instruction books, manufacturers catalogue of all bought items & fittings,
operation & maintenance manuals , spare part bulletin.
(a) Two copies of each drawing mentioned above and Instruction
Manual shall be sent along with the transformer & its accessories to
site. Further a CD containing soft copy of all drawings in AutoCAD ,
instructions manuals and other relevant details in acrobat or MS word
shall be sent with transformer to site . This CD shall contain AutoCAD
software and acrobat reader software also.
(b) Ten (10) sets of hard bound folders containing copies of approved
drawings, instruction manuals shall be sent to order placing authority
within a fortnight of approval of drawings. Further, Six (6) CDs
containing soft copy of all drawings in AutoCAD , instructions manuals
and other relevant details in Acrobat or MS word shall be sent to order
placing authority. These CDs shall contain AutoCAD software and
acrobat reader software also.
MPPTCL/TECH/PROC/05/JUNE13 Page 62 of 111

30.0 The offered price shall include cost of drawing / manuals as


detailed out in Annexure VII.
31.0 DESIGN CALCULATIONS & DESIGN DATA TO BE ENCLOSED
WITH BID : All the important data of the transformer i.e. Net weight of bare
copper in each winding , Weight of core without clamping fixtures , Weight of
core and windings, Cross section of the core, Flux density calculations ,
Calculations for short circuit current and its duration , Current density during
short circuit , Calculations showing withstand capability of windings for thermal
& mechanical stresses during short circuit conditions , Mechanical Design of
transformer tank etc should be invariably submitted by the Bidder . After
placement of detailed contract the final design calculations shall be submitted
for our verification and records .
Submission of design calculations and data with technical bid is a
necessary requirement and those Bids will be rejected wherein
these data & calculations is not found . It may be noted by the Bidders
that no correspondence with the bidder in this regard shall be made
after opening of technical & commercial offer. All responsibility for
Submission of design calculations and data with the Bid is therefore
of the Bidder & non furnishing of same may run the risk of rejection
/non responsiveness of the Bid.
31.1 DESIGN CALCULATIONS & DRAWINGS
31.1.1 Short Circuit Withstand Capabilities : The calculations to prove
dynamic and thermal short circuit withstand capability of transformer shall be

submitted by the Bidder for the fault level indicated as under


220KV - 40 KA for 3 secs.
33KV - 31.5KA for 3 secs.
It may be noted by the Bidders that calculations for short circuit withstand
capability for two winding transformer shall be submitted. Results of
calculations shall be submitted with the bid. The design of winding assembly,
which is to be furnished in the drawing as per Sr. No. (e) of Annexure VI(A)
should be commensurating with these calculations. The details of clamping ring
shall be indicated in the drawing .
31.1.2 Design of Tank : Complete mechanical design of transformer tank
including details of stiffeners shall be submitted . The tank shall be designed to
withstand the following without permanent distortion.
(i) Mechanical shocks during transportation.
(ii) Vacuum filling of oil at 10 milli torr in transformer with all fittings.
(iii) Continuous internal pressure of 35 kN/m2 over normal hydrostatic
pressure of oil.
MPPTCL/TECH/PROC/05/JUNE13 Page 63 of 111

(iv) Short circuit forces &


(v) Under seismic condition /events both horizontal/vertical .
The calculations for tank stiffeners shall be submitted with the Bid to prove
no. & size of stiffeners are adequate to withstand full vacuum & pressure.
Drawing of tank shall be submitted indicating stiffners .
31.1.3 Design of Static End Rings (SER) and Magnetic Shunts : Details
of Static End Rings (SER) and magnetic shunts , if provided , shall be
submitted with the Bid with calculations . A drawing indicating locations , size
,material of SER and magnetic shunts shall be submitted with the Bid .
31.1.4 Overfluxing Capability: A curve to prove suitability of transformer to
withstand various Overfluxing conditions for the duration indicated in clause
4.4.1 to 4.4.3 without core saturation shall be furnished with the Bid .
31.1.5 Cooling Calculations : Calculations of tank surface for heat
dissipation, details of radiators , fans for ONAN & ONAF cooling shall be
provided with the Bid.
31.2 DESIGN DATA : On the basis of offered flux density and current
density, the Bidder shall furnish following design calculations & data.
Calculations regarding wt. of core & copper and also calculations for losses
will be brought out to justify the offered transformer losses. :
31.2.1 Core Data: Details of core material i.e Name of Manufacturer,
Manufacturers type designation for core , thickness of core, curve for Loss Vs
Flux density, no. of steps of Core & no. of limbs, gross core area , stacking
factor , Net core area ,height & width of core window, center to center distance
of limb, voltage per turn, wt. of core material, working flux density , core loss
in watts per kg marked on graph for grade of core material & selected flux
density, building factor and calculated no load loss in watts, guaranteed no
load loss.
Design data for core shall be submitted with the Bid. A drawing indicating
details of core i.e. limbed construction, step width & thickness , core belting,
top & bottom yoke plate etc shall be submitted with the Bid .
31.2.2 Winding Data: wt. of copper for windings ie. for HV, tap, LV, cross
sectional area, current density, type of coil, ID/OD/mean dia of coils, size of
winding conductor including parallels, no. of turns per phase, no of spacers,
length of mean turn, weight of copper without paper covering, resistance per
phase of winding at 75 deg C, I2R loss at 75 deg C at normal tap, eddy current
& stray loss at 75 deg C , total copper loss at 75 deg C , guaranteed
transformer losses at 75 deg C.

Complete details of Insulation components i.e. Top & Bottom clamping rings,
washers , Pressboard blocks & cylinders, Pressboard spacers & Phase barriers,
MPPTCL/TECH/PROC/05/JUNE13 Page 64 of 111

Pressboard segments etc shall be submitted indicating qty , thickness in mm,


width & height , wt. Design data for winding shall be submitted with the Bid.
Dimensioned drawings indicating details of winding , ducts, insulation , take off
arrangement, clamping ring , pressure points etc shall be submitted with the
Bid .
31.3 QUANTITY OF OIL : Complete calculations of oil quantity to be utilized
in transformer for first filling shall be submitted with the Bid. The calculations
shall indicate
(i) Volume of tank including turrets, conservator main & OLTC ,volume of
headers & Radiators, oil quantity in OLTC & thermosyphon filter.
(ii) Oil displacement by Active parts i.e. core - coil assembly.
31.4 CAPACITY OF CONSERVATOR & SIZE OF AIR CELL : While furnishing
details of conservator & air cell type sealing arrangement, the Bidder shall
submit details & calculations for adequacy of size and capacity of Pronal make
air cell for the rating of the power transformer and also for the quantity of oil
required with the Bid. Catalogue of Pronal should be enclosed with the Bid
clearly marking type designation of selected size of Air cell. A drawing
indicating complete details of conservator with Air cell shall be submitted .
31.5 CAPACITY OF PRESSURE RELIEF DEVICE : Our specification calls
for supply of pressure relief device for all power transformers. Bidders
must submit calculation with the Bid to prove that the capacity/rating of
pressure relief device and locations of the same for the transformer will
adequately meet our requirement. Constructional and design details of
pressure relief device must be furnished and it should be proved by
calculation that the size and setting of pressure relief device is
adequate considering the rating of the transformer and quantity of oil in the
transformer.
A drawing indicating complete details of PRDs & their locations on tank shall
be submitted.
31.6 LIMITS OF TEMPERATURE RISE & HOT SPOT WINDING
TEMPERATURE : The limits of temperature rise for windings, oil and hot spot
have been specified. Temperature rise calculations at rated full load, 110% load
and 125% load considering 100% cooler banks, 50% cooler banks and without
coolers shall be furnished as indicated below :
(a) 100 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(b) 110 % Loading : (i) 20 minutes duration - 100 % cooler bank
MPPTCL/TECH/PROC/05/JUNE13 Page 65 of 111

- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(c) 125 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank

- without cooler bank


The calculations shall indicate temperature gradient (for all windings i.e. HV,LV
& tap), load losses at lowest tap for all windings , Eddy current & stray losses,
thermal Constant Value & calculations with parameters affecting the values for
above conditions for top oil temperature & winding hot spot temperature .
The Calculations for Hot Spot winding Temperature and Calculations for
Temperature Rise shall be submitted with the Bid.
31.7 CAPACITY OF FILTER & BREATHER :
31.7.1 NUMBER OF THERMOSYPHON FILTER AND CAPACITY OF EACH
THERMOSYPHON FILTER : The Bidder shall submit details & calculations for
adequacy of size and capacity of thermosyphon filter for the oil quantity in
the power transformer . While furnishing details of thermosyphon filter
arrangements, the Bidder must confirm clearly the number of thermosyphon
filter, its size and capacity is adequate for the rating of power transformer. The
Bidder shall submit details & calculation to prove for adequacy of size and
capacity of thermosyphon filter in with the Bid.
.
31.7.2 CAPACITY OF SILICA GEL BREATHER : The Bidder shall submit
details & calculations for adequacy of size and capacity of silica gel breather
for the oil quantity in the power transformer with the Bid.
31.8 RATING OF ON LOAD TAP CHANGER (OLTC) : It has been our
experience that due to inadequate rating of OLTC elements, the failure of
OLTC components or pitting of contacts have been observed before the claimed
period for maintenance. To verify the adequacy and suitability of the OLTC
components, it is necessary to furnish the calculations for selecting the
proper rating of transition resistance as well as the normal current rating
of OLTC. The calculations shall include the temperature rise of the OLTC
diverter switch and also the short circuit current considered for calculation of
temperature rise.
Calculations shall be submitted to prove that the current rating of OLTC is
adequate for the rating of the transformer winding taking in to account the
over loading capability as per IS 6600 . The basis for selection of transition
resistance and its current carrying capacity shall also be submitted. In this
regard the circulating current in tap winding during tap change operation
MPPTCL/TECH/PROC/05/JUNE13 Page 66 of 111

through transition resistance shall be taken in to consideration. Adequacy of


insulation provided in the OLTC between various parts needs to be established
with specific reference to the voltage between two taps. Confirmation shall be
given that the OLTC is suitable for bidirectional flow of current. The through
current capacity shall be adequate to handle on continuous basis the winding
current including over loading as per IS 6600. The through current rating and
the rating of transition resistance shall take in to account the short time
current rating of the winding. Capability to handle short circuit current to be
established by calculations and also by test reports. The above Calculations for
OLTC shall be submitted with the Bid.
31.9 Capacity of Nitrogen Cylinder, pressure in Nitrogen Cylinder to be used
during transportation of transformer shall be submitted with the Bid.
31.10 Size & capacity of Oil sump/ pit for Nitrogen Injection Fire Protection
System shall be submitted with the Bid.
31.11 The Bidder shall carry out optimization of Dielectric design of insulation
including electromagnetic design, overload & short circuit withstand
capabilities. During design , transformer modeling shall be done & finite
element software (FEM) may be used.
31.12 Please note that submission of above calculations with

technical bid is a must and in absence of the above, the Bid will
be treated as non responsive and rejected. It is assured that these data
will be kept strictly confidential by MPPTCL.
32.0 QUALITY ASSURANCE PROGRAMME : The Bidders must establish
that a proper quality assurance program is being followed by them for
manufacture of power transformers. In order to ensure this, suitable QAP
should form a part of the technical bid, which will be submitted against
this Bid specification. The quality Assurance Program must have a
structure as detailed in the following paragraphs.
32.1 Customers Specifications And Contract Review : The quality
assurance and failure prevention starts with careful study and scrutiny of our
technical specifications and requirements. The supplier shall carefully study
all the technical parameters and other particulars & the supplier shall
categorically give his confirmation that these requirements shall be met
in a satisfactory manner.
32.2 Design Control : The supplier shall furnish the checks exercised in
design calculations particularly in respect of short circuit forces and method
of clamping end coil to show the healthiness of the design. The salient
features of design together with the certificates of design engineers will have
to be made available to the Purchaser.
32.3 Engineering Documents :The supplier shall give complete information
regarding copper conductor, insulating paper, core materials, tap changer,
gaskets etc. bringing out the detailed description and specification of these
MPPTCL/TECH/PROC/05/JUNE13 Page 67 of 111

items with explanation as to how our requirements are being met in this
respect.
32.4 Procurement Document Control & Purchased Material &
Services :
The supplier shall indicate the various sources of the items namely
copper conductor, insulating paper, core material, tap changer and other
items such as gaskets etc. are being procured. The type of checks,
quantum of checks and acceptance norms shall be intimated and random
test and check results should be made available for inspection whenever
so desired. The vendor list for various bought out items shall be submitted with
the Bid and the same shall be subject to purchasers approval. However, no
change in vendor list shall be acceptable after placement of order and list of
vendors shall be freezed at the time of placement of order. Furnishing of
following certificates is essential ;
i) Certificate and proof in the form of bill of lading for purchase
of core material either directly from abroad manufacturers
or their accredited selling agent.
ii) Certificate and proof in the form of bill of lading for purchase
of EC grade copper from National & International reputed
manufacturers or from their accredited selling agents.
It will however be obligatory on the part of Bidder to allow third
party inspection of all important material e.g. copper, core material, Insulating
cylinder etc . Bidder shall furnish certificate that the transformer shall be
manufactured with the input material approved by the Purchaser and in
case during independent third party inspection any of the above material is
found different than from approved list of vendors, in that case Purchaser
reserves the right to summarily reject complete transformer and the
manufacturer has to replace complete unit made out from all input material
from the vendors approved by the Purchaser.
32.5 Programme Chart : Based on above QAP and offered delivery

schedule a tentative program chart indicating period for various


manufacturing/testing activities shall be submitted along with QAP . The
program chart should specify periods for various activities i.e. design,
ordering of new materials, assembly, testing etc.
It should be noted by the Bidders that submission of QAP with the Bid
is an essential requirement and such of the Bids wherein QAP is not
found shall be rejected by the Purchaser.
33.0 INSPECTION AND TESTING
33.1 Inspection
MPPTCL/TECH/PROC/05/JUNE13 Page 68 of 111

33.1.1 The Purchaser shall have access at all times to the works and all
other places of manufacture where the transformers are being manufactured
and the Bidder shall provide all facilities for unrestricted inspection of the
Bidders works, raw materials, manufacture of all the accessories and for
conducting necessary tests as detailed herein.
33.1.2 The successful Bidder shall keep the Purchaser informed in advance
of the time of starting and of the progress of manufacture of
equipment at its various stages of manufacturing, so that arrangements
could be made for inspection.
33.1.3 No material shall be dispatched from its point of manufacture
unless the material has been satisfactorily inspected and tested.
33.1.4 The acceptance of any quantity of Transformer & its accessories
shall in no way relieve the successful Bidder of his responsibility for
meeting all the requirement of this specification and shall not prevent
subsequent rejection if such equipments are later found to be defective.
Acceptance of condition regarding stage inspection at various stages which will
be intimated to successful Bidders shall be the essence of the contract to be
placed against this Bid.
33.2. Inspection Programme :The Bidder shall chalk out a detailed
inspection and testing program for manufacturing activities for the various
components. An indicative program of inspection as envisaged by the
Purchaser is given in Annexure-VIII. The Purchaser reserves the right to get
carried out any tests by a third party. All Cost of inspection/tests shall be
borne by the Bidder.
33.3 Stage Inspections
33.3.1 The supplier shall indicate the inspections and checks carried out
at various stages of the manufacture of the transformers. A complete
record of stage inspection would be kept by the supplier and this record should
be made available for inspection by the representative of the Purchaser. The
supplier should indicate the manufacturing program and the Purchaser will
have a right to depute its inspecting officers during the manufacture.
Some of the inspecting stages are tank during fabrication, coil winding , core
building, assembly of coil on core, the condition of the coil and core after the
treatment in vacuum chamber, assembly within the transformer tank
together with application of tap changer.
33.3.2 It may be noted that stage inspection for first unit or all the units
,at our discretion , shall be done by us at the following stages.
(a) Fabrication stage of tank: After fabrication, tank shall be inspected for
measurement of its dimensions, thickness of sheets used and leakage test by
applying requisite pressure/vacuum.
MPPTCL/TECH/PROC/05/JUNE13 Page 69 of 111

(b) Building up of Core : After the core is built but before its clamping,
our representative will inspect the core to take complete weight of the
core and also to measure approximate core loss. If necessary, a small strip
of core shall also be taken for testing at CPRI, Bangalore or at any other

testing lab. of repute


(c) Preparation of Winding : Once the coils are prepared but before
the same are fitted on to the core, stage inspection shall be done to take
various measurements and also for weighment of total weight of coil of each
voltage class. Measurement of resistance shall be taken and for this purpose,
a small piece of conductor for each type of winding shall be made available
by the manufacture.
(d) Core Coil Assembly before & After VPD or Drying out
The Bidder has to submit with the Bid complete details of Drying out
process of transformer adopted in its works. The details should include
cycle, description , termination rate , process diagram , size of oven ,
measurement method of moisture extracted etc . Failure of the Bidder
to comply with this requirement shall result in rejection of the Bid.
(e) Final Assembly of Transformer after boxing in of active material
Apart from the above, the Purchaser also reserves the right to carry out stage
inspections at other stages also, for which advance intimation shall be given
and all necessary cooperation shall be rendered by the manufacturer.
33.4 Final Inspection and Testing
33.4.1 At the time of final inspection, the supplier shall identify each
and every item/accessories/fittings of the particular transformer under
testing. Unless all the items are identified, the manufacture will not be treated
as complete. Serial number of bushings, serial number of tap changer and
other accessories shall be entered into the test report to ensure that the same
are supplied with the transformer. Various tests stipulated in IS shall be
performed in the presence of purchasers engineers or when the inspection
waiver has been given, in such a case, the testing shall be done at the
manufacturer's works as per IS stipulations and same should be confirmed
by documentary evidence by way of Test Certificate which shall be got
approved by the purchaser.
33.4.2 The WTI & OTI shall be calibrated during testing of transformer
and Serial Nos. of these instruments shall be recorded in test reports. The
WTI & OTI used during testing shall be dispatched with the transformer so
that installation of same OTI & WTI on transformer is done which are
utilized during testing of transformer at suppliers works. The Bushings and
Radiators on Transformer (if heat run test is conducted ) during testing of
transformer at manufacturers works are required to be supplied with the
same transformer to avoid any mismatch / misalignment etc. during
assembly of transformer. This should be noted for strict compliance and
confirmed specifically.
MPPTCL/TECH/PROC/05/JUNE13 Page 70 of 111

33.4.3 Whenever inspection call for a particular transformer is given, the


letter of inspection call will accompany the following:
a. List of various fittings and accessories which are ready at the
works and will be offered for inspection. The Inspecting Officer
will carry the list and check the items declared to have been
offered for inspection
b. It is expected that before a transformer is finally offered for
inspection, internal testing of the transformer for various
important parameters like winding resistance, transformer
losses, IR values etc are already done. Routine test report for
such tests shall also accompany the letter of inspection call so
that the Inspecting Officer at the time of inspection may verify
the parameters brought out in the preliminary report. Details
of all tests should be clearly brought out.

c. In case for any reasons inspection is not completed or


equipment is not found to be complete with all accessories as
per confirmation given with the letter of inspection call, the
Purchaser will reserve the right to recover the complete cost of
deputation of inspecting team to the works of the
manufacturer.
34.0 STORAGE, HANDLING & SHIPPING : When the transformer is
declared ready, the manufacturer has to identify each and every item
associated with this unit and a `Complete Packing List shall be prepared in
advance. The equipments shall be stored and handled properly in shipping
depot, while the same is under process of dispatch. The manufacturer
should ensure dispatch of all the related items and accessories with a
particular unit of transformer along with tank.
Tap changer, bushing, radiators and other accessories of the
transformer should not be withheld for use subsequently on units for testing
purposes. If there are any items procured from sub-contractors which are to
be directly installed like instrumentation, panels, control gear etc. test and
inspection report for the same shall be kept separately and made available to
purchasers inspecting officers.
It may be noted that NO CHANGE in any accessory or
associated equipments after passing all the test successfully shall be allowed
and if this is subsequently detected it shall be binding on the Bidder to replace
with the same item with which the initial test were conducted at his part
failing which the entire test shall become null and void. The Purchaser at
his discretion may consider for rejection of the units thus supplied. The entire
cost, for replacement of such rejected units thus supplied and for repeating
acceptance test, shall be borne by the Bidder.
35.0 COMPLETENESS OF EQUIPMENT AND BOUGHT OUT ITEMS
The Bidders must furnish the following information along with
technical bid.
MPPTCL/TECH/PROC/05/JUNE13 Page 71 of 111

35.1 A list of all the accessories which will be supplied with the
transformer should be furnished. This should be as per Annexure II & III.
While furnishing the list of accessories , items which will be manufactured by
the Bidder and balance items, which will be procured from sub-suppliers
should be clearly identified and stipulated in the bid.
35.2 It is obligatory on the part of Bidder to ensure that supply of all
accessories as per Annexure-II are made alongwith Main Tank or prior to
delivery of Main Tank so that erection and commissioning work of
Transformer can be completed properly and uninterruptedly .The date of
supply of last accessory will be treated as date of delivery of transformer and
penalty shall be imposed upto a maximum of 10 % for delay in supply and
supply bills will be processed accordingly.
35.3 The responsibility for obtaining timely supplies of bought out items
will rest on the Bidder and only on this basis, delivery period will be offered
in the Bid.
35.4 It may be noted that in case of damages/shortages due to
improper packing or any other negligence ,replenishment shall be arranged
within 45 days of being noticed by the Purchaser. If this is not done, date of
delivery of such accessory will be treated as date of delivery of main
equipment and full penalty shall be recoverable from the Bidder on total
cost of the equipment. This should be confirmed.
35.5 For bought out items, responsibility for guarantee and obtaining
immediate replacement in case any defects are noticed and in case defective

supply of any item is reported will rest on the Bidder.


35.6 In case for attending to defect in any accessory or inspection/
replacement of the accessory, which may be bought out item for the Bidder;
services of engineer of original manufacturer is required, the same will be
organized on immediate basis by the Bidder at his cost.
35.7 The bidders are required to furnish in their bid, the following details
of packages for supply of complete quantity of materials/one complete
equipment:
i. Total number of packages
ii. Dimensional details of each package.
iii. Weight of each package.
iv. Nature of content (i.e. fragile or non-fragile)
In addition, the bidder from outside India offering CIF prices shall
also indicate the port of entry in India.
36.0 For all power transformer included in the Bid specification ,
provisions and stipulations as per CBIP Manual on Transformers in regard to
the following except as modified in this document should be strictly adopted
a) Design and standardisation.
b) Galvanising.
MPPTCL/TECH/PROC/05/JUNE13 Page 72 of 111

c) Labels.
d) Nuts & bolts.
e) Cleaning & Painting.
f) Prevention of acidity.
g) Continuous maximum rating & over loads.
h) Duty under faults conditions for stabilizing windings.
i) Flux density and magnetizing current.
j) Vibration & noise.
k) Suppressions of harmonics.
l) Magnetic circuit and mechanical construction of cores.
m) Constructional arrangements for winding.
n) Earthing arrangements.
o) Cooling plant for the transformers.
p) Temperature indicating device and alarm.
q) Gas actuated relays.
r) Marshalling box/control cubicle, panel drives & Mechanism Box
s) Control connection and instrument wiring.
t) Drying out, transport and erection.
u) Valves and air release plugs.
37.0 REQUIREMENT FOR TRANSPORTATION OF TRANSFORMERS: The
Bidders shall include charges for fitting atleast one Electronic impact recorder
(on returnable basis) during transportation of Transformers to measure the
magnitude and duration of the impact in all three directions. The acceptance
criteria and limits of impact in all three directions which can be withstood by
the equipment during transportation and handling shall be submitted by the
supplier during detailed engineering. The recording shall commence in the
factory before despatch and must continue till the unit is installed on its
foundation. The data of electronic impact recorder(s) shall be down-loaded at
site and a soft copy of it shall be handed over to Engineer-incharge. Further,
within three weeks the supplier shall communicate the interpretation of the
data. In the unlikely event of impact recorder output not available at site, the
equipment shall be thoroughly internally inspected by the manufacturers
representative before erection at site to ensure healthiness of the equipment.
Further the supplier shall mount Vehicle tracking system (GPRS/ GPS/

GSM based) to track the exact position of the vehicle on which the power
transformer is being loaded for transportation and during detailed engineering
take approval for the equipment installed.
38.0 Please ensure the bid document containing number of pages
have been properly page numbered and each page is signed by the
Bidder. All bid documents including Annexures should be indexed
properly and Index of the document should be enclosed/placed at the
beginning of the bid document.
MPPTCL/TECH/PROC/05/JUNE13 Page 73 of 111

ANNEXURE I
PRINCIPAL PARAMETERS FOR 220/33KV 50MVA
POWER TRANSFORMER
The transformers shall conform to the following specific parameters described
here under:1 Type of power transformer/
installation
220 KV 50MVA Two winding, Three
phase Suitable for out door
installation
2 Type of mounting Mounted on rails Center to center
distance 1676 mm+ Rail width,
longitudinal and transverse both
3 Suitable for system frequency 50 Hz
4. a. MVA Rating HV/LV 50 MVA
b. Rated voltage ratio: HV/LV 220/33 KV
5 No. of phases Three
6 No. of windings two winding, three phase
7 Type of cooling ONAN/ONAF
8 MVA Rating corresponding to
a. ONAN Cooling (80%)
b. ONAF Cooling (100%)
40 MVA
50 MVA
9 Method of connection HV - Star
LV - Star
10 Connection Symbol (Vector
group)
YNyn0
11 System earthing Solidly/Effectively earthed
12 Percentage Impedances, Voltage
on normal tap and MVA base
corresponding to HV/LV
rating and
applicable tolerances
10%
13 Ohmic value of HV/LV short
circuit Impedance as viewed
from HV side
a. Max. Voltage Tapping
b. Minimum Voltage
Tapping
c. Normal Voltage Tapping
Supplier to furnish
14 Anticipated continuous loading

HV and LV
a) Not to exceed 110% of its rated
capacity
15 Tap Changing gear
MPPTCL/TECH/PROC/05/JUNE13 Page 74 of 111

i) Type
ii) Rated Voltage
iii) Rated Current
iv) Provided On
v) Tap range
vi) Tap step
ON LOAD
170 KV (Min)
500 Amp (Min)
Taps at neutral end of HV winding
(-)15 % to (+)5%.
1.25%
16 Over voltage operating capability
and Duration
110% rated voltage continuous,
125% rated voltage for 60 seconds,
140% rated voltage for 5 seconds.
17 Minimum Air core reactance of
HV Windings
20%
18 Minimum knee point voltage 110% rated voltage
19 Working Flux density in any part
of core and yoke at rated MVA
frequency and normal voltage
(Tesla)
1.65 ( as specified in clause 4.4.2 the
maximum flux density shall be 1.90
Tesla)
20 Insulation levels For windings
a. 1.2/50 micro second wave
shape lightening impulse
withstand (KVp)
b. Power frequency voltage
withstand (KV rms)
HV/LV / Neutral
950/250 /250
395/95/95
21 Type of winding insulation
a. HV/IV winding
b. LV winding
Graded
Full
22 System short circuit level and
duration for which the
transformer shall be able to
withstand thermal and dynamic
stresses (kA rms/sec)
220 KV - 40KA for 3 secs.
33 KV - 31.5 KA for 3 secs

23 Noise level when energized at


rated voltage and frequency but
without load.
81 dB
24 Permissible temperature rise
Over ambient temp of 50C.
i) of top oil measured by
thermometer
ii)of winding measured by
resistance
45C
50C
25 Minimum clearance in air (mm)
a. HV (220)
b. LV ( 33)
Ph-Ph Ph-G
2700 2400
700 660
MPPTCL/TECH/PROC/05/JUNE13 Page 75 of 111

26 Terminals : (Bushings)
a. HV winding line end
b. LV winding & HV/LV
Neutral end
245 KV OIP condenser
72.5 KV OIP condenser
27 Max. Radio Interference voltage
level at 1 MHz. & 266 kV rms
phase to ground voltage for HV
winding
1000 micro volt
28 Cooling Equipments :
a. Number of banks
b. Number of Fans
Two 50% banks
Adequate number of Fans for ONAF
cooling and standby Fans for 20%
additional cooling, in each bank
29 Bushings :
a. Voltage Rating (KV rms)
b. Current Rating (Amps)
c. Insulation level
i. Lightning impulse
withstand(KVp)
ii. 1 Minute power
frequency voltage (KV
rms)
iii. Creepage distance (mm)
HV/LV/HV-N/LV-N
245/72.5/72.5/72.5
1250/1250/1250/1250
1050/325/325/325
460/140/140/.140
6125/1813 /1813/1813
30 a) Bushing Current

Transformer for purchasers


use
i. Type
ii. Current Ratio HV:LV(A/A)
iii. Quantity
iv. Knee point voltage (V)
v. Accuracy class
vi. Secondary resistance
(Ohms)
vii. No. of cores
b) Neutral side C.T. for
Purchasers use (for
restricted E/F protection):
i. Type
ii. Quantity
iii. No. of cores
iv. Current Ratio (A/A)
v. Class of accuracy
vi. Max. secondary winding
resistance
HV LV
Single phase ring type turret mounted
800/1 1200/1
3 nos 3 nos
1000V 1000V
PS PS
As per requirement or < one ohm
One One
HVN LVN
Single phase ring type turret
mounted
1 no 1 no
One One
800/1 1200/1
PS PS
As per requirement or < 1.0 ohm
MPPTCL/TECH/PROC/05/JUNE13 Page 76 of 111

ANNEXURE - II
LIST OF FITTINGS AND ACCESSORIES TO BE PROVIDED WITH EACH
POWER TRANSFORMERS.
1. Each transformer shall be provided with the following accessories.
i One no. Dial type Thermometers for oil : A dial type
indicating thermometer with repeater of robust pattern
mounted inside FCC at a convenient height to read the
temperature in the hottest part of the oil and fitted with alarm
and trip contacts. ROTI shall also be mounted on RTCC panel.
ii Two nos. WTI for HV (on extreme phases), one no. WTI
for LV ( on middle phase) winding : These shall be
indicating type, with repeater responsible to the combination of
top oil temperature and winding current, calibrated to follow
the hottest spot temperature of the transformer winding.
The winding temperature indicator shall operate a remote alarm
before the hottest spot temperature approaches a dangerous
value and it shall automatically actuate the cooling fan Motors.

iii RWTI : These shall be as per cl. 11.10 of section I. A


precision potentiometer mounted inside the case shall function
as a transmitter to operate a repeater for RWTI. For HV
windings the transmitter shall be directly connected to the
repeater. For LV winding the transmitter shall be connected to
a Resistance Transducer, which will supply DC for operating
repeater.
iv One magnetic type oil level gauge with low level alarm
contacts and dial showing minimum, maximum and normal oil
levels.
v One plain oil level gauge of over lapped type on either side of
the conservator shall also be provided.
vi Valves (As Per Annexure V) In the Annexure-V of valve
schedule, 4 nos. valves are required to be provided in each
Thermosyphon filter. Out of 4 nos., 2 nos. shall be provided for
the purpose of disconnecting the oil flow between the main
tank and Thermosyphon filter and 2 nos. are to be provided for
the purpose of filtration of charge of the Thermosyphon without
disconnecting the Thermosyphon from body .
vii Minimum 3 nos. pressure relief valves . The quantity of these
valves should commensurate with the quantity of oil in the
transformer and also location of valves should be properly
designed to adequately release the excessive pressure.
viii A set of air release valves on the top and on the radiators and
also at appropriate places.
MPPTCL/TECH/PROC/05/JUNE13 Page 77 of 111

ix One thermometer pocket for mercury in glass type


thermometer.
x One double float gas detector relay(Buchholz relay) with alarm
and tripping contacts to detect accumulation of gas and
sudden changes of oil pressure, complete with shutoff valves
and flanges couplings to permit easy removal without lowering
oil level in the main tank, a blend valve for gas venting, and
test valve. Make of buchholz relay shall be as per our discretion.
xi Heat exchangers or radiators complete with shut of valves and
with facility for oil draining arrangement.
xii a. Two oil conservator, with required accessories, one for
main tank and other for OLTC. Two nos Silica gel Breathers
with main Conservator & one no. with OLTC Conservator.
b. Air cell type breathing arrangement with oil preserving
equipment complete in all respects of PRONOL make only.
xiii Eye bolts and lugs on all parts for easy handling.
xiv Two grounding earthing terminals at diagonally opposite
corner of tank.
xv One rating and diagram plate.
xvi A set of minimum 4 nos. flanged bi-directional wheels for rail
mounting (for 1676 mm rail gauge.)
xvii Set of fans required for ONAF cooling of the transformer with
following information
a. Number of Radiator Banks.
b. Required no of cooling fans (Industrial duty of adequate
voltage & rpm) be provided in each bank to ensure 100%
ONAF rating of the transformer. As per our specification,
for each bank 20% additional cooling fan is to be included

which will be duly wired-up.


xviii Suitable jacking lugs and haulage holes.
xix Inspection window & main holes with bolted cover as per
Annexure-IV
xx Adequate no of Thermosyphon filter assembly (minimum 4
nos) with suitable supports, valves and pumps for forced but
slow circulation of Transformer oil .
xxi Lifting arrangement for the complete transformer, core coil
assembly and also tank.
xxii One detachable bolted type MS ladder each on main tank and
conservator tank.
xxiii For the purpose of taking earthing connection from the
neutral bushing, adequate number of brackets with small
support insulators shall be provided on the body of the tank
MPPTCL/TECH/PROC/05/JUNE13 Page 78 of 111

so that earthing could be arranged by Purchaser near the


earthing pit of transformer itself.
xxiv A separate weather proof FCC (Fan/Cooler control) cubicle
containing dial type thermometer and winding temperature
indicator and terminals of dial, type thermometer, winding
temperature indicator, buchholz relay, MOG, control of fans
etc.
Please note provision of separate Fan Control Cubicle (FCC) is
a must. FCC shall be suitably dimensioned to accommodate the
following :a The wiring from RTCC shall be brought to marshalling box
and for terminating the same adequate numbers of
suitably rated terminal connectors shell be provided.
b Necessary cable glands shall be included in the scope of
supply. The cable gland and the hole on gland plate for cable
entry shall be provided.
c Arrangement for terminating the connecting leads of
OTI, WTI, buchholz, magnetic oil level gauge etc. shall be
made in the marshalling box. It should be possible to
read OTI and WTI readings without opening the box
through suitable glass window. All trip alarm and
repeater signals will be transferred to control room for which
arrangement will have to be made.
d Starters for cooling fans shall be housed in marshalling box
and necessary switches for local operation of fans shall be
provided.
e Local remote control switch for OLTC shall be provided.
f Space heater with switch, cubicle illumination lamp, fuses,
links overload protection arrangement for motors and other
accessories shall be included in the scope of supply.
xxv One set of indoor RTCC (Remote tap changer control) cubicle
complete with provision for remote operation of OLTC, as
independent or master/follower scheme, with oil and winding
temperature repeater, tap position indicator with annunciation
for fan group ON/OFF and cooler supply fail indication and Tap
changer in progress including OTI repeater & WTI remote
indicator operated by remote sensors.
xxvi One set of erection manual/relevant drawing/leaflets should be
secured permanently inside the RTCC cubicle as a guide line for

site erection and commissioning.


xxvii Three separate connection i.e. connection from core,
connection from end frame and connection from tank shall be
brought out on to a terminal box with cover. Arrangement for
inter connecting these terminals in the terminal box shall also be
MPPTCL/TECH/PROC/05/JUNE13 Page 79 of 111

provided. This arrangement shall facilitate verification of


core, end frame and tank insulation.
xxviii Mounting of radiators on the 33KV side of 72.5 KV
bushing should be avoided. In no case, the radiators
should be projected above the main tank height.
xxix All transformers shall be supplied with a full outfit of tools,
spanners, special tools as per annexure X for assembly and
all spanners shall be double ended and of very good quality of
" Gedore " or "Taparia " or equivalent make.
2. The equipments and accessories furnished with the transformer
shall be suitably mounted on the transformer for ease of operation, inspection
and maintenance and the mounting details shall be subject to the approval of
the purchaser. All valves shall be provided either with blind companion
flanges or with pipe plugs for protection.
3. Indication, alarm and relay equipment shall have contacts suitable for
operation with 110V/220V DC supply. Any other accessories or appliances
recommended by the manufacturer for the satisfactory operation of the
transformer shall also have 110V/220V DC as input.
4. a. OLTC and its controls shall be as per clause 14 Section-I
of specification.
b. All cabinets & panels shall be conforming to
stipulations under Clause-16 of Section -I of specifications.
c. All 245KV, 72.5KV and neutral bushings shall be of OIP
condenser type and as per Clause 11.13 of Section I of
specification.
5. Nitrogen injection type fire prevention & extinguishing system with flow
sensitive conservator isolation valve shall be provided for all the transformers
as per clause no. 20.9.
6. On Line Monitoring Device shall be provided for all the transformers as per
clause no. 20.10.
7. Provision for Measurement of Degree of Polymerisation of
Insulation of Winding of Transformer :- To assess the life of paper
insulation of winding , a provision is to be made inside the transformer . For
this purpose, a container of insulating material of good electrical, mechanical &
chemical properties having free circulation of oil through it shall be provided at
suitable location where maximum oil temperature is expected. In the
container, atleast 10-12 spools of paper having size not more than one cm be
placed . The container shall be closed and there should not be any possibility
of spools coming out from the container due to natural circulation as well
turbulence of oil during fault etc.
MPPTCL/TECH/PROC/05/JUNE13 Page 80 of 111

Location of the container shall be selected such that spools may be


removed from the container as and when required by the purchaser during
service of transformer for the purpose of testing of insulating material for
Degree of Polymerisation (DP test).
8. Accessories, which are not included in the above Annexure
but details of which are given in Bid specification and which are
necessary for satisfactory operation of Transformer shall be deemed
to have been included in the accepted price without any extra cost to

the Purchaser.
MPPTCL/TECH/PROC/05/JUNE13 Page 81 of 111

ANNEXURE -III
LIST OF TRANSFORMER ACCESSORIES AND THEIR TESTCERTIFICATES
TO BE SUBMITTED BY MANUFACTURERS/APPROVED VENDORS
S.
No.
Accessory Ref. Std. Test-certificates required
1 Condenser
Bushing
IS 2099
IEC 60137
1. Appearance, construction and
dimensional check
2. Test for leakage of
internal filling at a pressure
of 1.0 kg/cm2 for 12hours.
3. Insulation resistance IS
2099 measurement with
2000V megger.
4. Dry/wet power frequency
voltage withstand test.
5. Dry/wet power frequency
voltage withstand test for
test tap insulation
6. Partial discharge
measurement up to 1.5
UN/_/3 KV.
7. Measurement of tangent
delta and capacitance.
2. Pronol france IEC 1. Dimensional check,
inflation/Deflation at 10
inflation/Deflation at 10 KPa
2. Pressure test at 10 KPa for
24 Hr.
3. OLTC IS 2026 Part I
IEC 60214
1. Oil tightness test for the 8468
diverter switch oil chamber
at an oil pressure of 0.5
kg/cm2 at 100 degree
centigrade for 1 hour.
2. Mechanical operation test.
3. Operation sequence
measurement
4. Insulation resistance
measurement using 2000V
megger
5. Power frequency voltage
withstand test on diverter
switch to earth and between
even and odd contacts.
MPPTCL/TECH/PROC/05/JUNE13 Page 82 of 111

S.
No.

Accessory Ref. Std. Test-certificates required


6. Power frequency voltage
withstand test on tap
selector-between stationary
contacts, between max. and
min. taps, between phases
and supporting frames,
between phases.
7. Operation test of complete
OLTC.
8. Operation & dielectric test
4. Winding & Oil
Temp Indicator
IS 1. Calibration test
2. Dielectric test at 2 kV for one
minute.
3. Accuracy test for indication
and switch setting scales.
4. Test for adjustability of
switch setting
5. Test for switch rating
6. Measurement of temperature
rise with respect to the
heater coil current.
5. Pressure Relief
valve
IS 13947 1. Functional test with
Compressed air to check
bursting pressure, indicating
flag operation and switch
operation.
2. Dielectric test at 2 KV for one
minute.
3. Switch contact testing at 5A,
240 Volt AC.
4. Leakage test at 75%
operating pressure for 1Hr.
6. Cooling Fan and
motor assembly
IS 2312 1. Appearance, construction and
dimensional check.
2. Insulation resistance
measurement
3. Dielectric test at 1.5 KV
between winding and body
for one minute
4. Operation check.
5. Power consumption, RPM,
Current.
7. Buchholz Relay IS:3407 1. Leak test with transformer oil
at a pressure of 3 kg/cm2
MPPTCL/TECH/PROC/05/JUNE13 Page 83 of 111

S.
No.

Accessory Ref. Std. Test-certificates required


for 30 minutes at ambient
temperature for relay casing.
2. Insulation resistance
measurement with 500V
megger.
3. Dielectric test at 2 kV for 1
minute
4. Elements test at 1.75 kg/cm2
for 15 minutes using
transformer oil at ambient
temperature.
5. Loss of oil and surge test.
6. Gas volume test
7. Mechanical strength test
8. Velocity calibration test
9. Appearance construction and
dimensional check.
8. Oil Level gauge
including MOG
IS 1. Appearance, construction and
dimensional check
2. Dielectric test at 2 KV for 1
minute
3. Switch contact test at 5A 240V
AC
4. Switch operation for low level
alarm
5. Test for oil levels
9. Pressed Steel
Radiators
IS 513 1. Appearance, construction &
dimensional check.
2. Air pressure test at 2
kg/cm2 under water for 15
minutes
10. OLTC Control
cubical/Cooler
Control cubicle
IS 1. Appearance, construction &
dimensional check.
2. Electric operation
3. Insulation resistance
measurement using 500 V
meggar at ambient
temperature
4. Dielectric test at 2kV for 1
minute
11. Bushing Current
Transformers
IS 2705 1. Appearance, construction &
dimensional check. Polarity
Check, Measurement of
MPPTCL/TECH/PROC/05/JUNE13 Page 84 of 111

S.
No.
Accessory Ref. Std. Test-certificates required
insulation resistance.
2. H V power frequency test.
3. Determination of ratio error
and phase angle of measuring
and protection BCTs
4. Interturn insulation test
5. Exciting current characteristic
test, Secondary winding
resistance measurement
12. Terminal
connector
IS 5561 1. Dimensional check construction
2. Tensile test, resistance test,
3. Test as per IS-5561
13 Silica Gel
Breather
1.Pressure tests
2. Visual & dimension tests
3. Operation test
4. silica gel test
5. Oil compatibility test
14 NIFPS TAC/NEPA
norms
1. Lamp test
2. Out of Service
3. Transformer Conservator
Insulator Valve (TCIV) open
4. Transformer Conservator
Insulator Valve (TCIV)
closed
5. Fire Detector trip
6. Buchholz Relay trip
7. Differential Relay trip
8. PRV trip
9. RPRR trip
10.Transformer trip
11.D.C. fail etc..
MPPTCL/TECH/PROC/05/JUNE13 Page 85 of 111

ANNEXURE-IV
SCHEDULE OF INSPECTION COVER/ACCESS WINDOWS
S.No. Particulars
Size
(Length x
Width)
(mm x mm)
Qty.
(Nos.)
1 Inspection cover (man hole) 450x900 1
2
Inspection cover/ Access Window
for OLTC

400x500 3
3
Inspection cover/ Access Window
for HV Bushing
500x500 3
4
Inspection cover/ Access Window
for LV Bushing
500x500 3
5
Inspection cover/ Access Window
for Neutral Bushing (Power
Xmer)
500x500 2
6
Inspection cover/ Access Window
for inspection of active parts /
connections etc. as per
manufacturers design
As per design requirement
7
Inspection cover/ Access Window
for visual inspection internal
parts
As per design requirement
Note: The Schedule is tentative and is subject to review based on
design. This Schedule shall be finalized at the drawing approval stage.
MPPTCL/TECH/PROC/05/JUNE13 Page 86 of 111

ANNEXURE-V
SCHEDULE OF VALVES
Item Description of Valves Size Qty Type (Design)
1 Oil inlet valve for Radiator
header
200NB 2 Gate valve
2 Oil outlet valve for Radiator
header
200NB 2 Gate valve
3 Top Oil filter valve 50NB 2 Gate valve
4 Bottom Oil filter valve 50NB 4 Gate valve
5 Top oil sampling valve 25NB 1 Globe valve
6 Bottom oil sampling valve 25NB 1 Globe valve
7 Drain plug bottom tank 50NB 2
8 Drain valve (Tank) 100NB 1 Butterfly valve
9 Drain valve (Tank) 100NB 1 Gate valve
10 Quick Oil discharge valve 125NB 1 Gate valve
11 N2 Injection valve 25NB 6 Gate valve
12 Radiator Isolating valve 100NB As per
design
Butterfly valve
13 Drain plug on radiators Bsp
14 Air release plug on radiators Bsp
15 Drain cum filter valve on
header
50NB 4 Globe valve

16 Drain plug on header Bsp 4 -17 Air release plug on header Bsp 4
18 Drain plug on inlet pipe Bsp 2
19 Drain plug on outlet pipe Bsp 2
20 Air release valve on tank
cover
15NB 2 Gate valve
21 Pressure release valve (Main 150NB 3
MPPTCL/TECH/PROC/05/JUNE13 Page 87 of 111

tank)
22 Valve for DGA 25NB 2 Gate valve
23 Thermosyphon drain valve 25NB 4 Globe valve
24 Thermosyphon filter valve 50NB 8 Gate valve
25 Drain plug on Thermosyphon
filter
Bsp 4
26 Air release plug on
Thermosyphon filter
Bsp 4
27 Thermosyphon pump isolating
valve
100NB 4 Gate valve
28 Thermosyphon pump bypass
valve
100NB As per
design
Gate valve
29 Thermosyphon isolating valve 100NB 8 Butterfly valve
30 Oil surge relay isolating valve 25NB 2 Globe valve
31 OLTC equalizing valve 25NB 1 Gate valve
32 OLTC suction valve 25NB 1 Globe valve
33 OLTC Conservator drain valve 25NB 1 Globe valve
34 Buccholz relay isolating valve 80NB 2 Gate valve
35 Pre Stressed Non return valve 80NB 1 Gate valve
36 Gas Sampling valve Bsp 2
37 Main conservator Drain valve 50NB 1 Gate valve
38 Main conservator Air release
valve
25NB 1 Gate valve
39 Main Breather isolating valve 25NB 1 Gate valve
40 Valve for Vacuum breaking
during oil filling
25NB 1 Gate valve
* NOTE: 1. All valves shall have position indicators to indicate the status i.e.
valves are in open or shut position.
2. All valves shall be made of gun metal (GM); cast iron valves are not
acceptable.
3. All plugs shall be made of cast iron (CI)/GM,NB- Normal Bore mm.
MPPTCL/TECH/PROC/05/JUNE13 Page 88 of 111

ANNEXURE VI(A)
DRAWINGS AND DATA TO BE FURNISHED BY THE BIDDER.
The following drawings and data for each items are to be submitted
with the Bid
(a) Outline dimensional drawings of transformer and its accessories
including conservator complete with Bill of material and details of

all parts, their quantity, rating & name of Vendors indicating clearances
of transformer body from live terminals i.e. HV & LV.
(b) Drawing of transformer tank with location of inspection windows,
thickness of side/bottom/top of tank, details of stiffener.
(c) Drawing indicating limbed core construction with complete details of
no., width and wt. of core laminations with size of steps; thickness of
core laminations ; dimension of window; size of limbs; Gross and net
core ; wt. of complete core.
(d) Drawing indicating core belting arrangement with details of belting,
belting material etc.
(e) Large scale dimensioned drawings for HV & LV windings of the
transformer; size and no. of parallel of HV, LV and of cooling ducts,
coil clamping arrangement, no./size & location of pressure screws,
clamping ring; top yoke arrangement etc. The details should
commensurate with the short circuit calculations submitted by you for
each rating of transformer
(f) Detailed drawing of transformer tank with complete core and winding
indicating clearances inside transformer tank as also passage and
space for free movement of at least two persons for inspection of
active parts etc .
(g) Schematic diagram showing the flow of oil in the cooling system as
well as each limb and winding. Longitudinal and cross-sectional views
showing the duct sizes, cooling pipes etc. for the
transformers/radiators drawn to scale .
(h) Drawings giving the weights for foundations.
(i) Combined Rating and diagram plate including tap changing, which
should also include details of guaranteed and measured no load and load
losses as also winding resistances and percentage impedances at all
taps.
(j) Schematic control and wiring diagram for all auxiliary equipment
and control cubicle.
(k) Drawing showing constructional details, dimensions, mechanical
& technical particulars of bushings. Arrangement of terminals and details
of connection of bushing shall also be indicated in drawing with their
technical particulars.
(l) Transportation drawing of transformer.
(m) Details of fittings and cable box.
(n) Drawing showing arrangement and details of tap changing gear
including selector switch, diverter switch and drive mechanism.
(o) Valve Schedule plate.
MPPTCL/TECH/PROC/05/JUNE13 Page 89 of 111

(p) Oil filling instruction plate for conservator fitted with Air cell breather
arrangement including equalizing arrangement if any required at
the time of taking full Vacuum at site.
(q) Drawing and instruction for fitting of Air Cell.
(r) Drawing of conservator indicating internal details of air cell MOG, oil
level gauge and silica gel breather pipe fitting arrangement.
(s) Drawings of all HV, LV & Neutral bushings with complete details meeting
TS requirement.
(t) Drawings of HV, LV & neutral terminal connectors indicating plate
thickness, no. of nut bolts with size and other details.
(u) Drawing of detachable bolted type MSladder with its complete details
and fitting arrangement on transformer/ conservator tank.
(v) Drawing for HV/LV neutral earthing arrangement indicating voltage

rating of insulators and its fitting arrangements, size of copper strips,


terminal connectors etc.
(w) Detailed drawing indicating two views of all valves provided in the
transformer tank.
(x) Drawing of Thermosyphon filter with fixing arrangement with
transformer tank.
(y) Detailed internal drawing of transformer indicating transportation locking
arrangement provided to avoid shifting of core assembly.
(z) Drawing showing weights of transformers, cooling fan structures, FCC
structures with distance from central line of transformer for casting of
civil foundation for transformer and associated equipments.
(aa) Drawing of Earthing terminal box showing earthing arrangement for
core, end frame, tank giving details of voltage class and current rating
of terminal bushings.
(ab) Drawing indicating insulation thickness details and other arrangement
provided between core assembly and bottom yoke and base of bottom
of tank.
(ac) Drawing indicating details of O ring gasketting arrangement provided
in transformer tank covers.
(ad) Drawing of stiffeners provided on top, each faces/sides of tank with their
number and size.
(ae) Drawing indicating number, location, size of shields/ magnetic shunts
and its material provided inside the tank.
(af) Drawing indicating internal details of transformer giving complete details
of clearances from live parts.
(ag) Drawing of internal LV winding termination arrangement indicating
minimum clearance between core and LV take off lead.
(ah) Drawing for Lead termination to bottom of HV & LV bushings.
(ai) Drawing of On Line Monitoring Device with details of mounting
arrangement.
(aj) Internal drawing & design of Core & Winding indicating all attachment
with identification numbers, description including take-off arrangement
of lead connection for Core & End frame and related Bill of Material
(ak) Locking arrangement drawing for tank top cover, core & winding with
complete dimension & details.
MPPTCL/TECH/PROC/05/JUNE13 Page 90 of 111

(al) Plan view of the bottom of Bell Tank for complete details of core coil
resting arrangement, indicating clearly dimensional details, material of
insulation, clamping arrangement with details of nuts/ bolts, clearance
from all sides provided at bottom.
(am) Drawing indicating complete details, dimension & mounting arrangement
of OLTC inside the tank with respect to End frame.
(an) Drawing indicating complete details, dimensions & fixing arrangement of
static end rings if used.
(ao) Other relevant drawings.
As soon as possible after the award of the contract the manufacturer shall
supply four (4) copies of the drawings as listed out above, which will
describe the equipment in details for approval and shall subsequently
provide ten complete sets of final drawings, one of which shall be autopositive
suitable for taking blue prints. Ten sets of instruction books,
operation and maintenance manuals and spare part bulletin, shall be
supplied. In addition to above two sets of manuals and drawings with test
certificates for each unit to be despatched as per despatch instructions.
MPPTCL/TECH/PROC/05/JUNE13 Page 91 of 111

ANNEXURE VI (B)

LIST OF DRAWINGS TO BE FURNISHED ALONGWITH BID


S.No. Particulars
1 OGA drawing of transformer
2 List of fittings & accessories for OGA
3 Drawing for HV,LV & N OIP Condenser bushings
4 Makes of various accessories and source of raw material
5 Universal type bimetallic terminal connector for HV,LV, Neutral
6 Conservator with air cell breathing arrangement
7 Thermosyphon filter assembly with pump & without pump
8 Internal clearances detailed drawing
9 Dimensional details for transportation of transformer.
10 Radiator arrangement
11 Core earthing arrangement box
12 Yoke binding details
13 Neutral earthing arrangement
14 Foundation details
15 List of tools & tackles
16 Bottom locking & insulating arrangement
17 Core insulation details
18 MS Ladder
19 Sealing arrangement between top & bottom shell.
20 OLTC Conservator with breather arrangement
21 Drawings for various types of valves.
22 Core shunt fixing arrangement
23 Rating & diagram plate
24 Valve schedule plate
25 Oil filling instruction plate for conservator with air cell.
26 Roller assembly with anit-earthquake arrangement
27 Coil clamping arrangement
28 Oil flow diagram
29 Winding details arrangement with dimension
30 Core details with design data
31 Over fluxing curve
32 Drawing for tank stiffener & magnetic shunt inside transformer with
calculation.
33 NIFPS with complete catalogue, manuals & drawings.
34 Schematic drawings for OLTC, FCC & RTCC .
35 Cooler control cubicle cum marshalling box with schematic
36 RTCC panel drawing
37 Drawing for static end ring
38 Complete dimensioned details of bottom tank
MPPTCL/TECH/PROC/05/JUNE13 Page 92 of 111

ANNEXURE VII
DESIGN CALCULATIONS & DESIGN DATA REQUIRED TO BE ENCLOSED
WITH THE BID FOR POWER TRANSFORMER
It should be specifically noted by the Bidders that submission of
following Design Calculations & Design Data with the offer is
necessary and bids wherein these calculations are not found enclosed
shall run risk of rejection.
(1) SHORT CIRCUIT WITHSTAND CAPABILITIES : The calculations to
prove dynamic and thermal short circuit withstand capability of transformer
as per clause 31.1.1 shall be submitted for the fault level indicated as under:
220KV - 40 KA for 3 secs.
33KV - 31.5 KA for 3 secs.

Results of calculations shall be submitted with the Bid. The design of winding
assembly , which is to be furnished in the drawing as per Sr. No. (e) of
Annexure VI(A) should be commensurating with these calculations. The
details of clamping ring shall be indicated in the drawing .
(2) DESIGN DATA OF CORE & WINDING : On the basis of offered flux
density and current density, the Bidders shall furnish following design
calculations & data. Calculations regarding wt. of core & copper and also
calculations for losses will be brought out to justify the offered transformer
losses. :
(A) Core Data: Details of core material i.e Name of Manufacturer,
Manufacturers type designation for core , thickness of core, curve for
Loss Vs Flux density, no. of steps of Core & no. of limbs, gross core area
, stacking factor , Net core area ,height & width of core window, center to
center distance of limb, voltage per turn, wt. of core material, working
flux density , core loss in watts per kg marked on graph for grade of core
material & selected flux density, building factor and calculated no load
loss in watts, guaranteed no load loss. Design data for core as per clause
31.2.1 shall be submitted with the Bid. A drawing indicating details of
core i.e. limbed construction, step width & thickness , core belting, top &
bottom yoke plate etc shall be submitted with the Bid .
(B) Winding Data: wt. of copper for windings ie. for HV, tap, LV, cross
sectional area , current density, type of coil, ID/OD/mean dia of coils, size
of winding conductor including parallels, no. of turns per phase, no of
spacers, length of mean turn, weight of copper without paper covering,
resistance per phase of winding at 75 deg C, I2R loss at 75 deg C at
normal tap, eddy current & stray loss at 75 deg C , total copper loss at 75
deg C , guaranteed transformer losses at 75 deg C.
Complete details of Insulation components i.e. Top & Bottom clamping
rings, washers , Pressboard blocks & cylinders, Pressboard spacers &
MPPTCL/TECH/PROC/05/JUNE13 Page 93 of 111

Phase barriers, Pressboard segments etc shall be submitted indicating qty


, thickness in mm, width & height , wt. Design data for winding as per
clause 31.2.2 shall be submitted with the Bid.
Dimensioned drawings indicating details of winding , ducts, insulation ,
take off arrangement, clamping ring , pressure points etc shall be
submitted with the Bid .
(3) DESIGN OF TANK : Complete mechanical design of transformer tank
including details of stiffeners as per clause 31.1.2 shall be submitted . The tank
shall be designed to withstand the following without permanent distortion.
(i) Mechanical shocks during transportation.
(ii) Vacuum filling of oil at 10 milli torr in transformer with all fittings.
(iii) Continuous internal pressure of 35 kN/m2 over normal hydrostatic
pressure of oil.
(iv) Short circuit forces &
(v) Under seismic condition /events both horizontal/vertical .
The calculations for tank stiffeners shall be submitted with the Bid to prove
no. & size of stiffeners are adequate to withstand full vacuum & pressure .
Drawing of tank shall be submitted indicating stiffeners .
(4) DESIGN OF STATIC END RINGS (SER) AND MAGNETIC SHUNTS :
Details of Static End Rings (SER) and magnetic shunts , if provided , with
calculations as per clause 31.1.3 shall be submitted with the Bid . A drawing
indicating locations , size ,material of SER and magnetic shunts shall be
submitted with the Bid .
(5) QUANTITY OF OIL : Complete calculations of oil quantity to be utilized in

transformer for first filling shall be submitted with the Bid. The calculations
shall indicate
(i) Volume of tank including turrets, conservator main & OLTC ,volume of
headers & Radiators, oil quantity in OLTC & thermosyphon filter.
(ii) Oil displacement by Active parts i.e. core - coil assembly,
(6) CAPACITY OF CONSERVATOR & SIZE OF AIR CELL : While furnishing
details of conservator & air cell type sealing arrangement, the Bidder shall
submit details & calculations for adequacy of size and capacity of Pronal make
air cell for the rating of the power transformer and also for the quantity of oil
required with the Bid. Catalogue of Pronal should be enclosed with the Bid
clearly marking type designation of selected size of Air cell. A drawing
indicating complete details of conservator with Air cell shall be submitted .
(7) CAPACITY OF PRESSURE RELIEF DEVICE : Bidders must submit
calculation with the Bid to prove that the capacity/rating of pressure relief
device and locations of the same for the transformer will adequately meet our
requirement. Constructional and design details of pressure relief device must
MPPTCL/TECH/PROC/05/JUNE13 Page 94 of 111

be furnished and it should be proved by calculation that the size and


setting of pressure relief device is adequate considering the rating of the
transformer and quantity of oil in the transformer. A drawing indicating
complete details of PRDs & their locations on tank shall be submitted .
(8) CALCULATIONS FOR TEMPERATURE RISE & HOT SPOT WINDING
TEMPERATURE : The limits of temperature rise for windings, oil and hot spot
have been specified in Volume II . Temperature rise calculations at rated full
load, 110% load and 125% load considering 100% cooler banks, 50% cooler
banks and without coolers shall be furnished as indicated below :
(a) 100 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(b) 110 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(c) 125 % Loading : (i) 20 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
(ii) 10 minutes duration - 100 % cooler bank
- 50 % cooler bank
- without cooler bank
The calculations shall indicate temperature gradient (for all windings i.e. HV &
LV), load losses at lowest tap for all windings , Eddy current & stray losses,
thermal Constant Value & calculations with parameters affecting the values for
above conditions for top oil temperature & winding hot spot temperature .The
Calculations for Hot Spot winding Temperature and Calculations for
Temperature Rise shall be submitted with the Bid.
(9) COOLING CALCULATIONS : Calculations of tank surface for heat
dissipation, details of radiators , fans for ONAN & ONAF cooling shall be
provided with the Bid.
(10) OVERFLUXING CAPABILITY: A curve to prove suitability of

transformer to withstand various Overfluxing conditions for the duration


indicated in clause 4.4.1 to 4.4.3 without core saturation shall be furnished with
the Bid .
(11) CAPACITY OF FILTER & BREATHER :
(A) Number and Capacity of each Thermosyphon Filter : The Bidder
shall submit details & calculations for adequacy of size and capacity of
thermosyphon filter for the oil quantity in the power transformer . While
MPPTCL/TECH/PROC/05/JUNE13 Page 95 of 111

furnishing details of thermosyphon filter arrangements, the Bidder must


confirm clearly the number of thermosyphon filter, its size and capacity
is adequate for the rating of power transformer. The Bidder shall submit
details & calculation to prove for adequacy of size and capacity of
thermosyphon filter with the Bid.
(B) Capacity of Silica Gel Breather : The Bidder shall submit details &
calculations for adequacy of size and capacity of silica gel breather for
the oil quantity in the power transformer with the Bid .
(12) RATING OF ON LOAD TAP CHANGER (OLTC) : To verify the
adequacy and suitability of the OLTC components, it is necessary to furnish
the calculations for selecting the proper rating of transition resistance as well
as the normal current rating of OLTC. The calculations shall include the
temperature rise of the OLTC diverter switch and also the short circuit
current considered for calculation of temperature rise.
Calculations shall be submitted to prove that the current rating of OLTC is
adequate for the rating of the transformer winding taking in to account the
over loading capability as per IS 6600 . The basis for selection of transition
resistance and its current carrying capacity shall also be submitted. In this
regard the circulating current in tap winding during tap change operation
through transition resistance shall be taken in to consideration. Adequacy of
insulation provided in the OLTC between various parts needs to be established
with specific reference to the voltage between two taps. Confirmation shall be
given that the OLTC is suitable for bidirectional flow of current. The through
current capacity shall be adequate to handle on continuous basis the winding
current including over loading as per IS 6600. The through current rating and
the rating of transition resistance shall take in to account the short time
current rating of the winding. Capability to handle short circuit current to be
established by calculations and also by test reports.The above Calculations for
OLTC shall be submitted with the Bid
(13) Capacity of Nitrogen Cylinder, pressure in Nitrogen Cylinder to be used
during transportation shall be submitted with the Bid.
(14) Size & capacity of Oil sump/ pit for Nitrogen Injection Fire Protection
System shall be submitted with the Bid.
Note : Bidders may please note that submission of above
calculations & design data as mentioned in clause 31 and in this
Annexure with technical bid is an essential requirement of the Bid.
MPPTCL/TECH/PROC/05/JUNE13 Page 96 of 111

ANNEXURE VIII
DETAILS OF INSPECTION PROGRAMME
1 . INSPECTION PROGRAMME :
1.1 Manufacturer shall chalk out a detailed inspection and testing
programme for various manufacturing activities for the different
components, fittings & accessories. The MPPTCL also reserves the right to
carryout any tests by a third party at its sole discretion. All Costs of inspection/
tests shall be borne by Manufacturer.
2.2 STAGE INSPECTIONS :
2.2.1 Manufacturer shall indicate the inspections and checks carried out at

various stages of the manufacture of the transformer. A complete record of


stage inspection shall be kept by Manufacturer and this record shall be made
available for inspection by the representative of the MPPTCL. Manufacturer
shall indicate the manufacturing programme and the MPPTCL will have a right
to depute its inspecting officers during the manufacture. The inspecting stages
shall be Fabrication of Tank & Conservator, core building, coil winding ,
assembly of coil on core, the condition of the coil and core after the
treatment in vacuum chamber, assembly within the transformer tank
together with application of tap changer etc .
2.2.2 It may be noted that stage inspections for all the units shall be done
by us at the following stages as per the different formats enclosed :
(i) STAGE I : Stage Inspection of Transformer Tank and Conservator
after fabrication. After fabrication, tank & conservator shall be inspected for
measurement of its dimensions, thickness of sheets used and leakage test by
applying requisite pressure.
In this stage following shall be measured ,recorded & checked in Format I
(A,B,C) .
(A) Format I (A) : Inspection of Tank & Conservator
a) Certification of chemical composition and mechanical properties of
plates.
b) Welder's and weld procedure qualification.
c) Testing of electrodes for quality of base materials as per ASME.
d) Dimensional check and visual Inspection of weld .
e) Crack detection, of major strength weld seams by dye penetration
test.
f) Measurement of film thickness of inside and outside of X'mer tank
and conservator
i) Oil insoluble varnish
ii) Zinc chromate paint
iii) Light grey paint
MPPTCL/TECH/PROC/05/JUNE13 Page 97 of 111

g) Check correct dimensions between wheels, rotation of wheels through


90 deg.
h) Check for physical properties of materials for lifting lugs, jacking
pads, etc. All load bearing welds including lifting lug and jacking parts
shall be subjected to DP test.
i) Leakage test of conservator and tank.
j) Pressure and vacuum test of tank.
k) Surface cleaning by sand or shot blasting.
l) Certification of all test results.
(B) Format I (B) : Inspection of Valves as per Schedule of Valves
(C) Format I (C) : Inspection of Tank for Inspection Windows.
(ii) STAGE II : Stage Inspection of Transformer Core during Core
Building : After the core is built but before its clamping,
MPPTCL representative shall inspect the core to take complete weight
of the core and also to measure approximate core loss. If
necessary, a small strip of core shall also be taken for testing at CPRI,
Bangalore at our discretion or at any other testing lab. of repute for
measurement of specific loss .
During this stage, following documents shall be verified by our
inspector as a proof towards use of prime core material material for
manufacturer of transformer ordered by us .
i) Invoice of the supplier
ii) Mills test certificate

iii) Packing list


iv) Bill of lading
v) Bill of entry certificate by custom's.
The core material shall be directly procured either from the
manufacturer or through their accredited reputed marketing
organisation but not through any agent. A copy of all above
documents shall be sent with joint inspection report for MPPTCL
records.
In this stage, following shall be measured, recorded & checked in Format
II (A,B,C).
(A) Format II (A) : Report in respect of Raw material viz core,
copper, insulating material ,tank steel etc.: Details of various raw
material shall be recorded viz. Name of Supplier/Sub supplier, Test
Certificate, QAP Report , Invoices, Bill of Lading ,bill of entry etc.
(B) Format II (B) : Report in respect of Accessories: Details of
accessories Viz Buchholz relay, Pressure Relief device, Axles and
wheels, Winding and oil temperature indicators , Cooling fan and
radiator, Condenser Bushing & Bushing Current Transformer, OLTC,
MPPTCL/TECH/PROC/05/JUNE13 Page 98 of 111

Oil level gauge ,OLTC Cubicle and fan control cubicle, RTCC , Valves,
Clamps, Air Cell Breather, Pronol Bag etc. shall be recorded i.e. Make,
Rating, Factory Test Certificate, QAP Report , Invoices etc.
(C) Format II (C) : Inspection of Core .
a) Checking of in house or vendor core cutting facilities. Sample testing
of core steel for checking specific total loss, ductility and bend
properties, resistivity, ageing , magnetisation characteristics and
thickness.
b) Check on the quality of surface insulation & surface finish;
Measurement of thickness and hardness of varnish on stampings;
Solvent resistance test to check that varnish does not react in hot
oil; Check over quality of varnish on stamping, to ensure uniform
shining colour, no hot spots, no over burnt varnish layer and no
bubbles on varnished surface.
c) Check on the amount of burrs i.e. cutting & edge; Bow Check on
stampings.
d) During core building dimension, leaning or waviness of core,
tightening torque, dia of resiglass tap to be checked.
e) Check for the over laping stampings. Corners of the sheets are to be
apart.
f) Visual and dimensional check during assembly stage.
g) Check for interlaminar insulation between core sections after
pressing.
h) Visual and dimensional check for straightness and roundness of
core.
i) High voltage test on fully built core 2 kV for one minute
between core & yoke bolts, core & core clamps, core clamps & yoke
bolts, core loss measurement.
j) Certification of all test results.
(iii) STAGE III : Stage Inspection of Winding after their preparation
: Once the coils are prepared but before the same are fitted on to
the core, stage inspection shall be done to take various measurements
and also for weighment of total weight of coil of each voltage class.
Measurement of winding resistance shall be also done. A small piece of
conductor for each type of winding shall be made available by the

manufacturer to our representative.


During this stage, following documents shall be verified by MPPTCL
inspector as a proof towards use of prime copper and insulating material for
manufacturer of transformer ordered by us :
i) Invoice of the supplier
ii) Mills test certificate
iii) Packing list
iv) Bill of lading
v) Bill of entry certificate by custom's.
MPPTCL/TECH/PROC/05/JUNE13 Page 99 of 111

The winding and insulating material shall be directly procured either


from the manufacturer or through their accredited reputed marketing
organisation but not through any agent. A copy of all above documents shall
be sent with joint inspection report for our records.
In this stage, following shall be measured, recorded & checked in Format III.
(A) Winding:
a) Sample check on winding conductor for mechanical properties
and electrical conductivity.
b) Visual dimensional checks on conductor for scratches,
dent marks etc.
c) Sample check on insulating paper for PH value, electric
strength.
d) Check for the reaction of hot oil on insulating paper.
e) Check for the bonding of the insulating paper on conductor.
f) Check and ensure that physical condition of all materials taken for
winding is satisfactory and free of dust.
g) Check for absence of short circuit between parallel strands.
h) Check for brazed joints wherever applicable.
i) Measurement of voltage to be carried out when core/yoke is
completely restacked and all connections ready.
j) Conductor-enamel test for checking of cracks, leakage and pin
holes.
k) Conductor-flexibility test.
l) Heat shrink test for enamelled wire.
m) Measurement of no. of turns, cross sectional area of each
winding , winding resistance and weighment of windings.
n) Certification of all test results.
(B) Insulating Material:
a) Sample check for physical & chemical properties of material.
b) Check for dielectric strength.
c) Visual and dimensional checks.
d) Check for the reaction of hot oil on insulating materials.
e) Dimensional stability test at high temperature for insulating
material.
f) Tracking resistance test on insulating material.
g) Certification of all test results.
(iv) STAGE IV : Stage Inspection of Core Coil Assembly before
Vapour Phase Drying/Dryout : In this stage , following shall be
measured, recorded & checked in Format IV.
a) Check Clamping Ring with approved drawing. Check Core Belting,
Check condition of insulation on the conductor & between the
windings.
MPPTCL/TECH/PROC/05/JUNE13 Page 100 of 111

b) Check insulation distance between high voltage & low voltage


connections with respect to earth and other parts.

c) Insulation test of core earthing .


d) Check for proper cleanliness and absence of dust etc.
e) Certification of all test results.
(v) STAGE V : Stage Inspection of Core Coil Assembly after Vapour
Phase Drying/Dryout : In this stage , following shall be measured,
recorded & checked in Format V.
a) Measurement and recording of temperature and drying time during
vacuum treatment.
b) Check for completeness of drying by measuring IR values & Tan
Delta.
c) Measure minimum clearance from all sides/bottom/top.
d) Certification of all test results.
(vi) STAGE VI : Inspection of Final Assembly of Transformer after
boxing in of active material : Complete details of all bought accessories ,
their test certificates shall be appended. Minutes of meeting shall record overall
workmanship and other pertinent details.
a) Check completed transformer against approved out line
drawing, provision for all fittings, finish level etc.
b) Jacking test on all the assembled Transformers.
Pre-shipment Checks at Manufacturer's Works:
a) Check for interchangeability of components of similar
Transformers for mounting dimensions.
b) Check for proper packing and preservation of accessories like
radiators, bushings, explosion vent, dehydrating breather, rollers,
buchholz relay, control cubicle, connecting pipes, conservator etc.
c) Check for proper provision of bracings to arrest the movement of
core and winding assembly inside the tank.
d) Gas tightness test to conform tightness.
e) Derivation of leakage rate and ensure adequate reserve gas
capacity.
Installation & pre-commissioning test of Nitrogen Injection Fire
Protection System & OLMD : After installation the system precommissioning
tests shall be carried out jointly before the system is put in
service.
2.2.3 Details of Procurement : Manufacturer shall provide us complete
details of procurement of raw materials i.e. core, insulation and copper .
Manufacturer shall also record a certificate .
2.2.4 The MPPTCL also reserves the right to carry out stage
inspections at other stages also, for which advance intimation shall
be given and all necessary cooperation shall be rendered by the
manufacturer.
MPPTCL/TECH/PROC/05/JUNE13 Page 101 of 111

ANNEXURE IX
LIST OF HAND TOOLS FOR SUPPLY
ALONG WITH TRANSFORMER
(A) One tool box consisting of the following 41 Hand tools of
GEDORE make or equivalent with better quality shall be supplied
1. Spanners of different sizes
a) Open Jaw Double Ended - 8 Nos.
b) Cranked ring double ended - 3 Nos.
c) Tubular Box Double Ended - 1 No.
2. Tommy Bar - 1 No.
(For Tabular Box Spanner)
3. Adjustable Wrenches - 2 Nos.

4. Pipe Wrench - 1 No.


5. Screw Drivers Of Different Sizes - 5 Nos.
6. Flat Nose, Round Nose, Side Cutting - 3 Nos.
Pliers
7. Gasket Punches - 10 Nos.
8. Files With Handles - 2 Nos.
9. Hammers With Handles - 2 Nos.
10. Knife With Handles - 1 No.
11. Adjustable Hacksaw - 1 No.
12. Cold Chisel - 1 No.
Total 41 Nos.
MPPTCL/TECH/PROC/05/JUNE13 Page 102 of 111

ANNEXURE X
DESCRIPTION OF EQUIPMENT FOR SCHEDULE OF RATES & PRICES
For this Bid which includes 220KV 50MVA transformers, description of main
equipments and other items should be brought out exactly as per details
furnished herein and accordingly schedule I of price should be enclosed with
the Bid.
Item
Nos.
Description Quantity
(Nos)
1. Supply of 50MVA 220/33KV, Three phase ONAN/ ONAF
cooled power transformer fitted with Pronol air-cell, Nitrogen
Injection Fire Protection System (NIFPS) as described in cl
20.9, on line monitoring device (OLMD) as described in
cl.20.10 and all accessories/ fittings as described under
annexure II , duly passed all routine additional routine and
acceptance tests as per IS-2026 with one set of tools as per
annexure IX complete with first filling of oil including
wastage & 10% extra of that quantity & meeting all
technical requirement as per Part 1 of Volume II &
annexure I. The offered cost includes cost of all tests as per
clause 24.5 conforming to all requirements as described in
bid document. The transformers shall be supplied fitted with
Impact Recorder (on returnable basis) during transportation
of Transformers and Vehicle tracking system (GPRS/ GPS/
GSM based) to track the exact position of the vehicle during
transportation of Transformers as per clause no. 37.0.
As per
price
schedule
2 Against Item no.1 above, composite total cost of power
transformer alongwith various accessories, equipments, tool,
oil etc as well as cost of testing as described in details above,
will be furnished by the bidder. However, bidders are
requested to indicate the following unit price of items
included in composite cost mentioned under Item no. 1
above for the purpose of computation price variation after
award of contact:(a) On Line Monitoring Device
(b) Complete System of Nitrogen Injection Drain and Stir
Method type fire prevention and extinguishing system
(NIFPS) including required Nitrogen cylinders dully filled, all

piping works, Civil works with material etc.


(c) Charges for fitting Impact Recorder (on returnable basis)
during transportation of Transformers and Vehicle tracking
system (GPRS/ GPS/ GSM based) to track the exact position
of the vehicle during transportation of Transformers as per
clause no. 37.0
SIGNATURE
WITH SEAL OF BIDDER
ANNEXURE XI
MPPTCL/TECH/PROC/05/JUNE13 Page 103 of 111

LIST OF VENDORS FOR MAJOR ITEMS OF TRANSFORMER


The vendors of various major items from whom procurement was made by
various suppliers of transformers and quality of which was found acceptable
are listed below. However, Major items/inputs in transformers have to conform
to highest quality standards and these items/inputs procured from any
vendors meeting the required specification would be acceptable.
No. Name of Item Supplier
1. CRGO M/s Nippon steel corporation, Japan
M/s JFE Steel corp., Japan ( Erstwhile M/s
Kawasaki Corp. Japan)
M/s AK Steel,USA
M/s Armco, USA,
M/s Posco,Korea
M/s Covefi, France
M/s Salzgittar, Germany
M/s Usinor, France
M/s Transfer, France
M/s Mitsubishi, Japan.
M/s AST Terni, Italy
M/s EBG India Pvt Limited, (Indian Agent) for M/s
GELSE NKIRCHEN, Germany
M/s British Steel Corporation , UK
M/s Thyseen Krupp Group of Companies
2.
(a)
Winding copper &
conductor
M/s Invex Filli Isolati Speciali s.p.a. Italy
M/s Sam Dong Korea
M/s Asta, Austria
M/s Smit Draad, Holland
M/s Incab Industries, Jamshedpur
M/s Sterlite Industries, Mumbai
M/s Hindalco Industries
M/s Bhandary Powerlines Private Limited (BPPL),
Manipal.
M/s BCPL Conductors Private Limited, Manideep,
Bhopal.
M/s Bhandary Powerlines Private Limited
(BPPL),Vadodara.
M/s Shakti Insulated Wires,Mumbai
M/s KSH International Pvt Limited, Taloja
M/s Delta-Trans Conductor, Mumbai
M/s Vijay Electricals, Hyderabad

M/s RIMA Transfomers & Conductors Pvt. Limited,


MPPTCL/TECH/PROC/05/JUNE13 Page 104 of 111

No. Name of Item Supplier


Bangalore.
M/s Lacroix and Kress (GMBH) germany
M/s Pirellicavi Italy
M/s Shree Cable & Conductors
M/s Chandra Metals,allahabad
(b) CTC Conductor M/s Sam Dong Korea
M/s Invex Filli Isolati Speciali s.p.a. Italy
M/s Loc Roix AND KRESS Germany
M/s Chandra Portico ltd silvassa
M/s KSH International Pvt Ltd, Chakan
3. Precompressed
press Board & press
Board components
M/s H. Weidmann, Switzerland
M/s Fige Holms Brruk, Swedan
M/s Senapathy Whiteley, Banglore
M/s Raman Board, Mysore
4. Insulating Material M/s Dupont, USA
M/s Senapathy Whiteley, Banglore
M/s H. Weidmann, Switzerland
M/s Munksio
M/s Amotfors, Sweden
M/s Krammerer
5. Air Cell M/s PRONAL, France
M/s PRONAL, Asia manufacturing SDN BHD
Malaysia
6. Gaskets M/s Talbros, Faridabad
M/s Cortica, Chennai
M/s Packing & Jointing, Chennai
M/s Indian Rubber Products, Haridwar
M/s Bombay Oil Seal Mfg. Mumbai
M/s MGM Rubber Kolkata
M/s Bharat Corrub Industries, Vadodara.
M/s Indian Cork Industries,Bahadarpur
M/s Nucork, Gurgaon
7. OIP Condensor
bushing
M/s BHEL
M/s CGL
M/s TELK
M/s ASEA-MICAFIL
M/s Passonivilla
8. Terminal Connector M/s Best & Crompton, Chennai
M/s PeeVee Engg., Bangalore
MPPTCL/TECH/PROC/05/JUNE13 Page 105 of 111

No. Name of Item Supplier


M/s Milind Engg., Mumbai
M/s Nootan, Baroda
M/s Utsav, Baroda
M/s Vinayak and Co., Mumbai
M/s Megha Engg. Enterprises, Chennai
M/s Klemmen Engg. Corporation , Chennai

9. OTI/WTI with
repeater
M/s Accurate Control,UK
M/s AKM, Swedan
M/s Perfect Control, Chennai, India
M/s Preci Measure, Banglore
M/s Radix Electrosystems Pvt. Ltd/ Radix Pyrotech
India
10. Magnetic oil gauge M/s Sukrut Udyog, Pune
M/s Yogya, Jhansi
11. Buchholz Relay &
Oil surge relays
M/s Fukuda Instrument, Japan
M/s Atvus,Calcutta
M/s English Electric, Chennai
M/s Prayog; M/s BHEL
M/s Instrument and Control, Vadodara
12. Pressure Relief
Device
M/s Qualtrol, USA
M/s GE, USA;
M/s Sukrut Udyog, Pune
M/s ATVUS Industries, Kolkatta
13. Fan & Motor M/s Marathon Electric Motors (India) Ltd, Kolkata
(Erstwhile M/s Areva, (Alstom), Kolkata)
M/s CGL, Mumbai
M/s Khaitan,Calcutta.
M/s EPC, Calcutta
14. Un-impregnated
Densified laminated
wood
M/s Permali Wallace Bhopal
M/s Kit ply Assam
M/s Mysore Polymers Banglore
M/s Narmada Forest Ind. Pvt. Ltd. Bhopal.
M/s Western India Plywood , Kerala
15. Valves M/s Leader
M/s Bombay Metal & Alloys
M/s Audco
M/s Petson
M/s Manixon
M/s Creseant
M/s Precision Engg. Kottayam,
MPPTCL/TECH/PROC/05/JUNE13 Page 106 of 111

No. Name of Item Supplier


M/s Eapen Joseph, Kottayam
M/s Apex Piping Systems, Jalandhar
M/s Liberty Engg., Mumbai
M/s Niton Valves, Mumbai
M/s Eapen Joseph & co., Coimbatore
M/s GG Valves ,Udaipur
16. MCB Ms Siemans
M/s MDS
M/s S&S

M/s Havell's
17. Fuse M/s Siemens/ S&S / Areva / Havell's
18. Tank Steel M/s SAIL
M/s Essar
19. OLTC Complete M/s BHEL
M/s TELK
M/s Easun, Madras
20. Terminal Blocks M/S ELMEX
M/S Technoplast,
M/S Tosha
21. Silica gel Breather M/S Yogya Enterprises, Jhansi.
M/S Anusen Industries, Pune.
M/s Instruments & Controls , Vadodara, India
22. Transformer oil M/s Apar Limited, Mumbai
M/s Savita Chemicals Ltd, New Mumbai
23. Radiator M/s CTR Manufacturing Industries, Pune
M/s Thermal Transformer Product, Bangalore
M/s Exotherm, Bangalore.
M/s P.E. Engg. Hyderanad.
M/s Hitech Switchgear, Mumbai
24. On Line Monitoring
Device
M/s Kelman, UK
25 NIFPS M/s CTR , Pune
MPPTCL/TECH/PROC/05/JUNE13 Page 107 of 111

APPENDIX I
Calculation for Hot Spot winding temperature for EHV transformers
Overloading capability of the transformer and also the loading
capability of transformer with and without cooling fans (coolers) for a
short period of 10/20 minutes with out exceeding temperature rise of
winding beyond specified limits have been indicated in the technical
specification. In this regard following calculation based on maximum
ambient air temperature as 50 degree centigrade and maximum
yearly average weighted air temperature as 32 degree centigrade
using the under mentioned formulae or any other authentic formulae
shall be furnished.
-t/ 2y
c = a + b0 + ( b- bo) ( 1- e ) + ( c - b ) k
2x

( 1+dk )
b = br ------------- ( 1+d) x
Where
a = Weighted ambient temperature (cooling medium)
c = Winding hot-spot temperature at K load = a + c
cr = Winding hot-spot temperature at rated load
c = Winding hot-spot temperature rise at K load
cr = Winding hot-spot temperature rise at rated load
bo = Original oil temperature
b = Top oil temperature at K load = a + b
br = Top oil temperature at rated load
b = Top oil temperature rise at load K
br = Top oil temperature rise at rated power
t = Time duration in hours of any load power
= Oil air thermal time constant of transformer at rated

load, in hours
MPPTCL/TECH/PROC/05/JUNE13 Page 108 of 111

K = Ratio of any load/rated load = S /Sr


K1 = Ratio of initial load/rated load = S1 /Sr
K1 = Ratio of permissible load/rated load = S2 /Sr
K2 = Ratio of permissible load/rated load
x = Exponent for oil rise
y = Exponent for winding rise
d = Ratio of load loss at rated load/no load loss.
a = Subscript representing ambient (cooling medium)
b = Subscript representing top oil
c = Subscript representing hot-spot of winding
r = Subscript representing rated value.
SIGNATURE
WITH SEAL OF
BIDDER
MPPTCL/TECH/PROC/05/JUNE13 Page 109 of 111

APPENDIX II
TECHNICAL PARTICULARS TO BE FILLED-IN BY BIDDER
S. No. Particulars Values
1 Maximum flux density (Tesla)
2 Maximum current density (Amp/sq.cm)
3 Magnetising current (mA)
4 Short time current rating (Amp.)
5 Losses
a. No load Losses (KW)
b. Load Losses including stray losses
(KW)
c. Auxiliary losses (KW)
6 Impedance voltage (Percentage)
7 Weight of copper (Kg)
8 Weight of core (Kg)
9 Weight of core + winding (Kg)
10 Quantity of oil
a. For first filling including wastage
(KL/Kg)
b. 10% extra of a (KL/Kg)
11 Total weight of Transformer. (Kg)
12 Transport weight of main tank
a. with oil (Kg)
b. without oil (Kg)
SIGNATURE
WITH SEAL OF BIDDER
MPPTCL/TECH/PROC/05/JUNE13 Page 110 of 111

List of Abbreviation used in technical specification


1. OLTC - On load tap changer
2. OIP - Oil impregnated paper
3. DL type - Draw lead type
4. COPS - Conservator oil preservation system
5. RTCC - Remote tap changer cubicle
6. Cl - Clause
7. IEEMA - Indian Electrical & Electronics Manufacturing
Association
8. KV - Kilo voltage

9. KW - Kilo Watt
10. IV - Intermediate voltage
11. LV - Low voltage
12. VPD - Vapour phase drying
13. ONAN - Oil natural air natural
14. ONAF - Oil natural air forced
15. OFAF - Oil forced air forced
16. CBIP - Central Board of Irrigation and Power
17. OTI - Oil temperature indicator
18. WTI - Winding temperature indicator
19. KA - Kilo Ampere
20. TC - Terminal connector or test certificates as applicable
21. V - Voltage
22. f - Frequency
23. VN - Normal voltage
24. FN - Normal frequency
25. CT - Current Transformer
26. PT - Potential Transformer
27. Xmer - Transformer.
28. PRD - Pressure Relief Device
29. PRV - Pressure Relief valve
30. MOLG - Magnetic Oil Level Gauge
31. OSR - Oil Surge Relay
37. Isc - RMS value of symmetrical short ckt current,KA
38. V - rated voltage of system ,KV
39. Zt - short ckt impedance of transformer ,Ohms
40. Zs - short ckt impedance of system ,Ohms
41. 1 - final temperature in degree centigrade
42. 0 - Initial temperature in degree centigrade
43. J - short ckt current density ,amp/mm sq.
44. t - duration of short ckt in secs
45. Iph - rated phase current in amps
MPPTCL/TECH/PROC/05/JUNE13 Page 111 of 111

46. Zpu - per unit impedance


47. Rdc - DC resistance of the per phase of winding at 75
degree centigrade
48. Hw - height of winding in cm
49. N - no of turns per phase of winding
50. Dmi - mean diameter of inside winding ,cm
51. Bi - thickness of inside winding conductor ,cm
52. E - modulus of elasticity of conductor, cm
53. Sn - rated KVA
54. Pu - per unit impedance
55. Fa - axial imbalance force, Kg
56. Ai - (no of spacers x length x width ) for inner
winding
57. Ao - (no of spacers x length x width ) for outer
winding
58. m - no of conductors in the radial direction= no of
turns x no of parallel conductor

59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
71.
72.
73.

bo - thickness of outer winding conductor, cm


Dmo - mean diameter of outer winding, cm
Ao - supported area of outer radial spacers
F - total axial force in MT
D - mean diameter of clamping ring ,cm
b - width of clamping ring ,cm
t - thickness of clamping ring ,cm
n - no of jacking or clamping points
mA - milli ampere
kg - kilogram
kl - kilolitre
temp. - temperature
max. - maximum
min. - minimum
vol. - volume

MADHYA PRADESH POWER TRANSMISSION CO. LTD.


SHAKTI BHAWAN RAMPUR: JABALPUR

VOLUME II
PART-6
Technical Book Serial No.
MPPTCL/TECH/PROC/06/July13

TECHNICAL SPECIFICATION FOR SUPPLY


OF EHV EQUIPMENTS AND MATERIAL FOR
SUB-STATIONS AND FEEDER BAYS

O/o CHIEF ENGINEER (PROCUREMENT)


MPPTCL, JABALPUR
Volume-II contains eight booklets as under:Section Description Technical Book
Serial No.
Part-1 TECHNICAL SPECIFICATION FOR
SUPPLY OF 400KV/220KV, 315MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/01/JULY13
Part-2 TECHNICAL SPECIFICATION FOR
SUPPLY OF 400KV/132KV, 100MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/02/JULY13
Part-3 TECHNICAL SPECIFICATION FOR
SUPPLY OF 400KV, 125MVAR REACTOR
MPPTCL/TECH/
PROC/03/JULY13
Part-4 TECHNICAL SPECIFICATION FOR

SUPPLY OF 220KV/132KV, 160MVA


POWER TRANSFORMERS
MPPTCL/TECH/
PROC/04/JULY13
Part-5 TECHNICAL SPECIFICATION FOR
SUPPLY OF 220KV/33KV, 50MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/05/JULY13
Part-6 TECHNICAL SPECIFICATION FOR
SUPPLY OF 132KV/33KV, 63MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/06/JULY13
Part-7 TECHNICAL SPECIFICATION FOR
SUPPLY OF 132KV/33KV, 40MVA
POWER TRANSFORMERS
MPPTCL/TECH/
PROC/07/JULY13
Part-8 TECHNICAL SPECIFICATION FOR
400/220/132/33KV EQUIPMENTS
( 3 BOOKLETS)
MPPTCL/TECH/
PROC/08/JULY13
MPPTCL/TECH/
PROC/09/JULY13
MPPTCL/TECH/
PROC/10/JULY13

All the above eight booklets are in the form of separate


books. This book refers to:-

PART-6
TECHNICAL SPECIFICATION FOR 132/33 KV, 63 MVA
POWER TRANSFORMERS
Please note that the modifications in technical specifications
are indicated in Appendix-1, enclosed in Volume-I of the
Tender document.
Contents
Description of document Page No.
Technical specification for transformer 1-67
Annexures and appendix for 132KV, 63MVA Power Transformer
Annexure I - Principal Technical particulars 68-70
Annexure II - List of Fittings and
Accessories
71-75
Annexure III - Test certificates to be furnished
for accessories 76-78
Annexure IV - Schedule of Inspection
Windows
79

Annexure V - Schedule of Valves 80-81


Annexure VI(A)- Drawings & Data to be
furnished
82-84
Annexure VI(B)- List of drawings to be
furnished alongwith bid
85
Annexure VII - Calculations required to be
furnished
86-89
Annexure VIII - Details of Inspection Program 90-94
Annexure IX - List of Hand Tools and Jacks 95
Annexure X - Description of equipment for
schedule of rates & prices
96
Annexure XI - List of vendors for major items of
transformer 97-100
Appendix I - Calculation for Hot Spot
winding temperature for EHV
transformers
101-102
Appendix II - Technical particulars to be
filled-in by bidder
103
List of abbreviations used in technical
specification
104-105
MPPTCL/TECH/PROC/06/JULY13 Page 1 of 105

VOLUME II, PART-6


TECHNICAL SPECIFICATION FOR 63 MVA , 132/33 KV
POWER TRANSFORMERS
1.0 SCOPE
1.1 This specification covers design, engineering, manufacture,
assembly, stage inspections and testing before supply and delivery
including unloading on plinth at our substation sites located anywhere in
the state of Madhya Pradesh, of the 132/33KV, 63 MVA three phase
transformers complete with all fittings, accessories, associated equipment
including oil for first filling including wastage & 10% extra of that quantity
specified herein which are required for efficient and trouble free operation
as specified hereunder.
1.2 It is not the intent to specify completely herein all the details of
the design and construction of equipment. However, the equipment shall
conform in all respects to high standards of engineering, design and
workmanship and shall be capable of performing the duties specified
herein. The offered transformers shall be complete with all components
necessary for their effective and trouble free operation. Such components
shall be deemed to be within the scope of Bidders supply irrespective of
whether those are specifically brought out in this specification or not. The
transformers should be free from Polychlorinated Biphenyls
(PVB/PCB).

1.3 The Purchaser will interpret the meanings of drawings and


specification and shall have the power to reject any work or material
which, in his judgment is not in accordance therewith. The offered
transformers shall be complete with all components necessary for their
effective and trouble free operation. Such, components shall be deemed to
be within the scope of Bidders supply irrespective of whether those are
specifically brought out in this specification and/or the commercial order or
not.
2.0 STANDARDS
2.1 The transformers and associated accessories shall conform to
the latest issues/amendments of standards as given below, and report of
the committee for standardization of the parameters and specification of class
132 KV equipment, except to the extent explicitly modified in this
specification. Transformers conforming to any other authoritative standards
meeting better quality and ensuring better performance are also acceptable.
Bidder shall specifically indicate deviations if any from the INDIAN
STANDARDS.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 2 of 105

THE APPLICABLE INDIAN/INTERNATIONAL STANDARDS FOR POWER


TRANSFORMERS AND ASSOCIATED ACCESSORIES ETC.
INDIAN
STANDARD
NUMBER
TITLE
INTERNATIONAL
AND
INTERNATIONALLY
RECOGNISIED
STANDARD
IS-2026
(Part 1 to 5 )
Power Transformers IEC-60076(Part I to
5)
CBIP Publication
No.295
Manual on Power Transformers
IS-335 Insulating oil for transformers IEC-296,BS-148.
IS18662000
Electrical maintenance and Supervision
of mineral insulating oil in equipment.
IS-2099 Bushings for alternating Voltage above
1000V.
IEC-60137(2008)
IS-2312 Fans (Cooler fans)
IS-2705. Current Transformers. IEC 60044
IS-325. Three phase Induction motors. IEC-34.
IS-375 &
IS-996
Marking & arrangements for switch
gear, bus bars, main connections &
auxiliary wiring.
IS-3637. Gas & oil operated relays.

IS-10028
(Part 1to3)
Code of practice for installation and
maintenance of transformers.
IS-2147. Degree of protection provided by
enclosures for low voltage switch gear
and control.
IEC 60529,IEC60947
IS-5. Colours for ready mix paints.
IS-6272 Industrial cooling fans.
DOC.ETD16
(3703)
Draft standard by BIS for revision of IS6600 for Guide for loading of oil
immersed transformers.
IEC 60354
OLTC IEC 60214
IS 8478 Application Guide for OLTC IEC 60542
IS 10561 Application Guide for Power
Transformer.
IEC 60076-8
IS 13964 Method of measurement of Transformer
Sound levels.
NEMA-TR1
IS 2071
(Part 1 to 3)
Methods of High Voltage Testing IEC 60060
IS 6209 Methods for Partial Discharge
Measurements
IEC 60270
IS 2165 Insulation Coordination IEC 60071
IS 5561 Terminal connectors
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 3 of 105

INDIAN
STANDARD
NUMBER
TITLE
INTERNATIONAL
AND
INTERNATIONALLY
RECOGNISIED
STANDARD
Short Circuit Current calculation of
effects
IEC 865(part I & II)
IS-5553 Shunt Reactors, Neutral/Earthing
Reactor and Arc Suppression Coil
IEC 60289
IS:335 Insulating oils for transformers and
switchgears
IEC:60296, BS:223
IS -1886 Code of practice for installation and
maintenance of transformers.

Supervision and Maintenance guide for


Mineral Insulating Oil in Electrical
Equipment
IEC 60422
Method of Sampling of Liquid dielectrics IEC 60475
Guide for the Sampling of Gases and of
Oil from Oil-filled Electrical Equipment
for the Analysis of Free and Dissolved
Gases
IEC 60567
Digital Recorders and Software for High
Voltage Impulse testing
IEC 61083
Specification for radio disturbance and
immunity measuring apparatus
CISPR 16
Guidelines for conducting design reviews
for transformers 100 MVA and 123 kV
and above.
Cigre Publication 202
Metal oxide surge arrestors without
gaps
IEC 99-4
Selection and application
recommendation
IEC 99-5
Indian Electricity Rule 1956
2.2 In case equipment conforms to other International standards which
ensure equivalent or better performance than specified under cl 2.1 then
the English version of such standards or the relevant extracts of same shall
be forwarded with the bid and the salient features of comparison shall be
brought out separately.
2.3 The electrical installation shall meet requirements of Indian
Electricity Rules, 1956 and IS-1886,"Code of practice for installation &
maintenance of Transformers" as amended till date.
2.4 It has been experienced that the weight of core lamination, weight of
copper, weight of steel, weight of Transformer Tank along with Fittings and
Accessories and quantity of oil for first filling including wastage & 10% extra
of that quantity, total weight of core + winding after assembly and total
weight of transformer are indicated in the technical bid by the manufacturers
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 4 of 105

on tentative basis and at the time of submission of drawing, wide


variations in these quantities take place. This is not in order and it will
be obligatory on the part of the Manufacturer to ensure that all these
details are worked out carefully and only correct figures after proper design
are offered in the technical bid. It may be noted that at the time of
submission of final drawings, variation in these weights beyond the limits of
(+) 5% shall not be permitted.
2.5 It will also be obligatory on the part of the manufacturer to furnish
details of calculations for quantity (weight & size) of core material, quantity
(weight & size) of copper material, calculations for thermal and dynamic
short circuit withstand capability of transformer, calculations for pressure
relief valve, adequacy of size of AIRCELL Bag, volume of oil for adequate

cooling with calculations of size of conservator and other details as called


for in the specification. Furnishing of these calculations along-with technical
bid is a must. All the data should be supported with calculation details. In
addition, calculations for no. of thermosyphon filter and their adequacy be
furnished.
2.6 Interconnection : The transformers are meant for service as
interconnecting transformers and shall be capable of being energized either
from 132 KV side or 33 KV side. The power transformer shall be capable of
being loaded at rated power on the 132 KV and 33 KV sides at its full rating
(lagging or leading or mixed load). On Load Tap Changer shall be suitable for
such operation. The OLTC shall be suitable for bidirectional flow of power.
3.0 SERVICE CONDITIONS
3.1 Climatic Conditions : The transformers and its accessories to be
supplied against this specification shall be suitable for satisfactory
continuous operation under the following tropical conditions.
1. Location At various substations within
the State of Madhya Pradesh
2. Max. Ambient air temp. (oC) 50
3. Min ambient air temp (oC) -5
4. Maximum daily average ambient air
temperature(oC)
40
5. Maximum yearly weighted average
temperature (oC)
32
6. Maximum Relative humidity (%) 95 (sometimes reaches
saturation.)
7. Average annual rainfall (cm) 125
8. Max. Wind pressure (Kg/sq.m.) 150
9. Max. Altitude above mean sea level
(Metres)
1000
10. Isoceraunic level (Average number of
thunderstorm days per year)
50
11. Seismic level (horizontal acceleration) 0.3g
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 5 of 105

Moderately hot and humid tropical climate, conducive to rust and


fungus growth. Tropical Protection Shall conform to IS:3202 titled climate
proofing of electrical equipments and BS: 1014 : titled protection of
electrical power equipments against the climatic condition. The
transformer tank fittings and radiators including all accessories shall be
designed to withstand seismic acceleration equivalent to 0.3 g. Special
precautions shall be taken to prevent mal-operation of Buchholz relay under
such condition.
3.2 Auxiliary Power Supply : Auxiliary electrical equipment shall be
suitable for operation on the following supply system.
a. Power Devices
(like drive motors)
0.4 KV, 3phase, 4wire 50Hz. neutral grounded AC
supply.
b. DC Alarm,
control &

protective
devices
110volts DC, ungrounded 2wire .
c. Lighting. 230V, single phase, 50Hz. AC supply.
Bidders scope include supply of interconnecting cables, terminal
boxes etc. The above supply voltage may vary as indicated below and all
devices shall be suitable for continuous operation over the entire range of
voltages.
i) AC supply : Voltage Variation of 25% to +10%;Frequency
+/- 4%
ii) DC supply : Voltage Variation of -20% to + 10%.
All accessories requiring AC or DC supply shall perform
satisfactorily for voltage variation as above.
4.0 GENERAL TECHNICAL REQUIREMENTS
4.1 Duty Requirements
a) The transformers and all its accessories like CTs etc., shall
be designed to withstand without injury, the thermal and
mechanical effects of any external short circuit to earth and of
short circuits at the terminals considering infinite bus
arrangement of values specified as under :
132KV - 40KA for 3 secs.
33KV - 31.5KA for 3 secs.
b) Over Loading : The transformer shall be capable of being
loaded in accordance with IS:6600. There shall be no limitation
imposed by windings, bushings, tap changer etc. of
transformer. Transformer & all its accessories shall be liberally
rated to allow 10% over loading at all taps on continuous
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 6 of 105

basis without exceeding the temperature limits specified in


clause 6.0.
The transformer shall be capable of being operated without
danger on each tapping at the rated KVA with specified
voltage variation corresponding to the voltage of that
tapping with normal temperature rise. The design adopted to
achieve this shall be indicated in detail in the Bid.
Transformer shall be capable of operating under the
natural cooled condition up to the specified load i.e. as ONAN
rating. The forced air cooling equipment shall come into
operation by pre-set contacts of winding temperature
indicator and the transformer shall operate as a forced air
cooled unit i.e. as ONAF. Cooling shall be so designed that
during total failure of power supply to cooling fans the
transformer shall be able to operate at full load for Ten(10)
minutes without the calculated winding hot spot temperature
exceeding 140 deg.C. Also stopping of two cooling fans should
not have any effect on the cooling system. Transformers fitted
with two coolers (cooling banks) each capable of dissipating
50 per cent of the loss at continuous maximum rating shall be
capable of operating for 20 minutes in the event of failure of
the blowers associated with one cooler, without the
calculated winding hot spot temperature exceeding 140 oC at
continuous maximum rating.
c) Over Voltage : The transformers shall be capable of being

operated on continuous basis at 10% excess voltage than


the rated voltage specified at each tap.
4.2 Radio Interference & Noise Level
4.2.1 The transformers shall be designed with particular attention for
suppression of maximum harmonic voltage especially the third and fifth so
as to eliminate wave form distortion and minimize interference with
communication circuits.
4.2.2 The noise level, when energized at normal voltage and
frequency with fans running shall not exceed, when measured under standard
conditions, the values specified in NEMA,TR-I.
4.3 Stresses : Transformer shall be capable of withstanding Electrical,
thermal and mechanical stresses on any winding caused by forces due to
symmetrical or asymmetrical external fault on any winding .
4.4 Frequency & Magnetic Induction
4.4.1 The transformers shall be suitable for continuous operation for a
frequency variation of (+) plus (-) minus 4% from normal 50Hz without
exceeding the specified temperature rise. For considerations of over
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 7 of 105

fluxing, the transformer shall be suitable for continuous operation for


values of over fluxing factor up to 1.1.
V FN
The over fluxing factor being { -- x -- }
VN F
4.4.2 The working flux density shall not exceed 1.65 Tesla for offered no
load losses and the maximum flux density in any part of core and yoke at
110% rated voltage combined with (-) 4% frequency variation shall
preferably not exceed the value of 1.90 Tesla as per CBIP manual no 295.
For manufacturing of Power transformer, core laminations of various
specifications are available and therefore while selecting the working flux
density, the Bidders will have to comply with the requirements of cl.4.4.1 &
4.4.3.
4.4.3 For the selected flux density, the transformer shall have
minimum of following over fluxing capabilities , such that while meeting
the above requirement saturation of transformer core shall not take place
under any circumstances. Transformer shall accept, without injurious
heating, combined voltage & frequency fluctuation, which produces the
following over fluxing conditions :
Over Fluxing
Factor
Period
1.50 Less than 2 seconds
1.40 5.0 seconds
1.25 60 seconds
1.10 Continuous
The Bidder shall also indicate 160% & 170% over voltage/over
fluxing withstand capability period. Over fluxing withstand characteristics up
to 170% shall be submitted along with the bid.
4.4.4 Detailed calculations for maximum flux density and magnetizing
current for core material shall be furnished to substantiate the
above requirement. The Bidder shall enclose details of Core Material with
thickness of lamination, type designation and source of raw material and its
characteristic curves. All characteristic curves of material including Voltage Vs
Flux Density and Loss per Kg Vs Flux Density are to be enclosed with Bid

clearly indicating Flux Density selected for calculation of core losses (No load
loss). On the basis of these data, for the Flux Density and core material
chosen verification of Saturation Flux Density shall be done by the
purchaser, to know the margin considered in operating Flux Density .
4.4.5 The maximum current density for design of power transformers
within specified limits of transformer losses shall not exceed the limits of 300
amps per sq.cm.
4.4.6 All other requirement of magnetic circuit shall be as per latest issue
of CBIP Manual no 295.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 8 of 105

4.4.7 The transformers shall be either core type or shell type


construction, oil immersed, ONAN/ONAF with external heat exchangers
and shall be suitable for outdoor service as inter connecting and/or stepdown
transformers suitable for parallel operation with the existing
transformer having tertiary winding already in service at the EHV substation
where these transformers are to be commissioned. The rating and electrical
characteristics of the transformers shall be strictly as specified in this
specification. For matching the parameters required for parallel operation with
existing unit, details shall be intimated to successful Bidder.
4.5 All the transformers shall be suitable for continuous operation with
frequency variation of +/- 4% from normal 50 Hz . Combined voltage &
frequency variation should not exceed the rated V/f ratio by 10 %.
5. INSULATION
5.1 Impulse & Power Frequency Voltage Withstand Values : For
rated system voltage of 33KV & 132KV following minimum power frequency
and impulse withstand voltage should be offered for the windings.
System
Voltage
Highest
System
Voltage
Power Frequency
Withstand
Voltages
Impulse
Withstand
Voltage
33KV 36KV 95KV rms 250KVp
132KV 145KV 230KV rms 550KVp
5.2 The HV winding of the transformers shall have graded
insulation. The insulation class of the neutral end of the winding
shall be graded to 95 KV. The 33KV winding shall have full insulation
for 33KV i.e. 250 KVp impulse and 95KVrms power frequency.
6.0 TEMPERATURE RISE : Each transformer shall be capable of
operating continuously at its normal rating & 10% over load condition
without exceeding temperature limits as specified below. The maximum
ambient temperature shall be taken as 50 degree C and type of cooling be
suitably adopted to limit the temperature rise within the safe limit of
operation.
Type Of Cooling Temperature-Rise
Windings Oil
ONAN (Air natural). 50oC 45oC
ONAF (Air blast/forced) 50oC 45oC.

7.0 FREQUENCY : All the transformers shall be suitable for continuous


operation with a frequency variation of + 4% to -4% from normal 50 Hz
without exceeding the specified temperature rise.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 9 of 105

8.0 IMPEDANCE : The percentage impedance of the power transformer


shall be 10% on 63 MVA base. Bidders shall indicate the guaranteed
impedance, tolerances and also the impedance on all taps for the offered
transformers. Impedance shall include positive and zero sequence and shall
be expressed in terms of the branches of the star connected equivalent
diagrams on all the specified MVA base and the range shall be given for each
branch of the equivalent circuit turn. It may be noted that if required the
percentage impedance should be designed identical to the existing
transformer of any make in case parallel operation is desired. The IS
tolerance on all matching taps are acceptable. Confirmation regarding
requirement of parallel operation should be given in the Bid.
It may be noted by the Bidders that for the purpose of matching
impedance of transformer, included in scope of this Bid, between 132KV &
33KV windings, the Bidders are not permitted to use reactor or
reactor/capacitor assembly. The design of the main winding should take care
of the requirement of impedances as specified in this Bid document and for
this purpose, no reactor or reactor/capacitor should be used.
9.0 MAXIMUM LOSSES:
9.1 Maximum Losses : While the Bidders may offer their own design, it
may be noted that the transformer losses at 75 deg. C. at rated output,
rated Voltage and rated frequency should not exceed the following maximum
limits which include tolerances as per IS :
a) No load losses (Iron losses). : 25 KW
b) Load(Copper losses) + Auxiliary losses. : 145 KW
including stray loss in KW
9.2 The No load losses in kilowatts ( including BIS tolerance ) at rated
voltage and rated frequency and the total load losses in kilowatts at rated
output, rated voltage and rated frequency at 75oC shall be guaranteed by
the bidder. It may be noted that the losses of the Transformer shall not
exceed during final testing of the transformer, if the same exceeds from the
maximum ceiling limit of Transformer losses as detailed in 9.1 above then the
Transformer shall not be accepted.
9.3 Heat Run Test:
One 63 MVA 132 KV power transformer of each manufacturer (if
there are more than one manufacturer) shall be subject to heat run test
(Temperature rise test).
10.0 COOLING : The Bidder may offer ONAN / ONAF type of cooling
for these transformers. The ONAF rating for each transformer winding shall
be 125% of ONAN rating achieved by cooling. The ONAF cooling shall be in
two groups each of 50% capacity. Adequate no. of standby cooling fans
shall be provided for 20% additional cooling per bank, in line with requirement
indicated in clause 15.1 ( C ).
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 10 of 105

11.0 CONSTRUCTION DETAILS : The features and construction details


of power transformer shall be in accordance with the requirements stated
hereunder
11.1 Tank
(A) As required in CBIP specification, the tank shall be of Bell type
construction for 63 MVA transformers covered under this

specification. Top cover of Bell type construction shall be


welded to the tank body
(B) Tank shall be of welded construction and fabricated from
tested quality low carbon steel suitable for welding & of
following minimum sheet thickness.
Tank cover - 20 mm, sides including inspection covers - 10
mm , Base - 20 mm.
(C) All seams and those joints not required to be opened at site
shall be factory welded and wherever possible they shall
be double welded. After completion of tank construction and
before painting, 'Dye Penetration Test' shall be carried out on
welded parts of jacking bosses, lifting lugs and all load
bearing members.
(D) Tank stiffeners shall be provided for general rigidity and these
shall be designed to prevent retention of water.
(E) The tanks shall be designed to withstand the following
without permanent distortion.
(i) Mechanical shocks during transportation.
(ii) Vacuum filling of oil at 10 milli torr in transformer
with all fittings.
(iii) Continuous internal pressure of 35 kN/m2 over normal
hydrostatic pressure of oil.
(iv) Short circuit forces .
(v) Under seismic condition /events both horizontal/vertical .
(F) Where ever possible the transformer tank and its accessories
shall be designed without pockets wherein gas may collect.
Where pockets can not be avoided, pipes shall be provided to
vent the gas into the main expansion pipes if any.
(G) The shields shall be such that no magnetic fields shall exist
outside the tank. They shall be of magnetically permeable
material. If required impermeable shields shall be provided
at the coil ends. Tank shield shall not resonate when excited at
the natural frequency of the equipment.
(H) The tank shall be provided with :
(i) Lifting lugs suitable for lifting the equipment complete
with oil.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 11 of 105

(ii) A minimum of four jacking pads in accessible position


at 500mm height to enable the transformer complete
with oil to be raised or lowered using hydraulic or
screw jacks. The location of jacking pads shall be such
that there should not be any interference with the civil
foundation of rails in either direction i.e. longitudinal or
transverse. A typical drawing no. MPPTCL/ 63MVA/01 for
providing jacking pad is enclosed with the Bid
specification.
(iii) Suitable haulage holes shall be provided.
(I) (i) Inspection cover/access windows & Manholes:
Suitable man-hole with a welded flange and a properly
gasketted bolted cover having of minimum thickness of
10 mm shall be provided on the tank cover. The manhole
shall be of sufficient size to offer easy access to
the lower ends of the bushings, terminal etc. The

requirement of inspection windows and manholes have


been stipulated in Annexure-IV & Bidders have to
confirm compliance of the same in their Bid.
(ii) Space for free movement in Transformer Tank for
inspection:
Details of passage & free space provided inside the
main tank should be indicated in concerned drawing to
allow free movement of at-least two persons for
inspection of active parts etc. To be more specific it
may please be noted that minimum clearance from
outer most winding/connection leads/supports to
tank shall not be less than 300 mm. on all 4 sides
with suitable platform on bottom of the tank to
facilitate free movement of person all around inside
the tank.
(J) All bolted connections to the tank shall be fitted with
suitable oil tight gaskets which shall give satisfactory
service under all operating conditions. Special attention
shall be given to the methods of making the hot oil tight
joints between the tank and the cover as also between
the cover and the bushings and all other outlets to
ensure that the joints can be remade satisfactorily and
easily with the help of semi skilled labour. Where
compressible gaskets are used, stoppers/ runners shall be
provided to prevent over compression.
(K) Suitable guides shall be provided for positioning the various
parts during assembly or dismantling. Adequate space shall be
provided between the cores and windings assembly and the
bottom of the tank for collection of any sediment.
(L) The design of the tank, lifting lugs shall be such that the
complete transformer assembly filled with oil can be lifted with
the use of these lugs without any damage or distortions.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 12 of 105

(M) For the complete transformer we have clearly brought out our
requirement of various types of valves in Annexure V
enclosed brings out details of type, size and quantity of valves
which are to be provided at various locations. This
requirement has to be confirmed by the Bidders without any
deviation.
(N) It may be noted that all gasketted joints shall be grooved one
using O rings of nitrile rubber or better, such as the joints
between bushing turret and bushing flange, inspection covers
of inspection windows and all other openings provided for the
purpose of inspection of internal parts of the transformer etc.
The main bell tank gasket between upper tank and bottom
tank shall be single piece O ring cord/gasket of nitrile rubber
or material of better quality. The gasketting arrangement shall
be grooved one with proper stopper to avoid over
compression. It is to be noted that one additional set of
gaskets shall be delivered by the tenderer alongwith
transformer to replace the used gaskets at the time of
erection of the unit.
(O) One detachable bolted type mild steel (MS) ladder with anticlimbing

arrangement shall be provided. Ladder for climbing


up to & over top cover of power transformers shall be
mechanically sturdy enough to bear the load of healthy
maintenance staff without any shake/jerks. The arrangement
shall not be detached after erection and commissioning of the
unit, hence shall be provided with padlock locking arrangement
for anti-climbing device. On the upper top of the ladder,
provision for support shall be made. However, the
arrangement of the ladder shall be to purchasers approval.
Collapsible ladder shall not be acceptable to us.
(P) Suitable earthing bridge between upper and lower tank shall be
provided at least on two places each on HV & LV side and one
place on other both sides.
11.2 Tank Cover
(a) The tank cover shall be sloped to prevent retention of rain
water and shall not distort when lifted.
(b) Inspection cover/man holes shall be provided as per
Annexure-IV.
(c) The tank covers shall be fitted with pockets at the position of
maximum oil temperature of MCR (Maximum Continuous
Rating) for inserting bulbs of oil and winding temperature
indicators. It shall be possible to remove these bulbs
without lowering the oil in the tank. The thermometer shall be
fitted with a captive sensor to prevent the ingress of water.
(d) Bushings, turrets, covers of inspection openings,
thermometer, pockets etc., shall be designed to prevent
ingress of water into or leakages of oil from the tank.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 13 of 105

(e) All bolted connections shall be fitted with weather-proof, hot


oil resistant gasket in between, for complete oil tightness.
If gasket is compressible, metallic stoppers shall be provided
to prevent over-compression.
(f) A minimum of three nos. PRD shall be provided above
each phase winding.
11.3 Undercarriage
(a) The transformer tank shall be supported on a structural steel
base equipped with forged steel or cast steel single flanged
wheels suitable for moving the transformer completely filled
with oil.
(b) Jacking pads/steps shall be provided. It shall be possible to
change the direction of the wheels through 90 deg. when the
transformer is lifted on jacks to permit movement of the
transformer both in longitudinal and transverse direction.
(c) The track/rail gauge shall be 1676 mm along the longer side,
as well as along the shorter axis. However Rails shall be placed
perpendicular to the bushing line.
(d) Pulling eyes shall be provided to facilitate movement/pulling of
the transformers and these shall be suitably braced in a
vertical direction so that bending does not occur when the
pull has a vertical component.
11.4 Axles And Wheels
(a) The transformers are to be provided with flanged bidirectional
wheels and axles. These shall be so designed as

not to deflect excessively to interfere with the movement of


the transformer. Wheels shall be provided with suitable
bearings which shall be rust and corrosion resistant.
Fittings for lubrication shall also be provided.
(b) Suitable locking arrangement along-with foundation bolts
shall be provided for the wheels to prevent accidental
movement of transformer. The locking arrangement shall be
such that it can be locked with plinth of transformer. The
length of the arrangement should be adequate to cover height
of the rail. No floating type locking arrangement shall be
accepted
(c) The wheels are required to swivel and they shall be arranged
so that they can be turned through an angle of 90 degrees
when the tank is jacked up to clear of rails. Means shall be
provided for locking the swivel movements in positions
parallel to and at right angles to the longitudinal axis of the
tank (i.e. longitudinal & transverse directions).
(d) To facilitate uniform distribution of transformer weight two
nos. props each on front & rear side along longer axis to be
provided.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 14 of 105

11.5 Anti Earthquake/Transport Clamping Device


(a) To prevent transformer movement during earthquake,
clamping device shall be provided for fixing transformer to the
foundation. The Bidder shall supply necessary bolts for
embedding in the concrete foundation. The arrangements
shall be such that the transformer can be fixed to or
unfastened from these bolts as desired. The fixing of the
transformers to the foundations shall be designed to
withstand seismic events to the extent that a static co-efficient
of 0.3g. applied in the direction of least resistance to that
loading will not cause the transformer or clamping devices as
well as bolts to be over stressed.
(b) Locking arrangement to eliminate relative movement between
top yoke/active parts with the transformer tank shall be sturdy
enough to bear transport hazards taking in to account the poor
road conditions and also considering that road transportation
of transformer will not be on hydraulic trailers
11.6 Conservator Tank
(a) The conservator tank shall be of minimum thickness of 8 mm
and it shall have adequate capacity between highest and
lowest visible levels to meet the requirement of expansion
of the total cold oil volume in the transformer and cooling
equipment from minimum ambient temperature to 100 oC.
(b) The conservator tank shall be bolted into position so that it
can be removed for cleaning purposes.
(c) Magnetic oil gauge (MOG) & prismatic oil level gauge
having three overlapped windows on one side of
conservator and on opposite side of conservator, plain
oil gauge with three overlapped windows shall be
provided to indicate oil level inside the conservator
at each location. Proper arrangement to ensure visibility of
oil level from ground be also ensured .

(d) Conservator shall be provided in such a position as not to


obstruct the electrical connections to the transformer.
(e) In order to avoid congestion and to facilitate operation and
maintenance activities, the main conservator and OLTC
conservator shall be provided on opposite sides of the main
tank. Further, there shall be adequate space for manual
operation of OLTC.
(f) Separate conservator tank shall be provided for OLTC.
(g) The size of the conservator shall be so designed as to
accommodate approximately 10% volume of total quantity of
oil in the transformer.
(h) Suitable arrangement shall be made for providing a foot rest
with easy & access arrangement to facilitate
maintenance/operation at top of the conservator, on magnetic
oil level gauge and buchholz relay.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 15 of 105

(i) The design of conservator shall be such that the air is not
trapped between air cell and main conservator.
11.7 Tank Earthing Arrangement : Two earthing pads complete with
two number tapped holes M10 bolts plain and spring washer suitable for
connection to 50X8 mm GI flat shall be provided each at position close to
two diagonally opposite bottom corners of tank. Earthing strips up to the
ground level and its connection with station earth pit shall be provided by the
Bidder.
11.8 Pressure Relief Device : A minimum of 3 (three) number
of pressure relief devices of reputed make and reliable quality shall
be provided on each transformer and these shall be mounted
preferably on the tank cover above each phase winding. Bidders must
submit calculations to prove that the no and capacity of pressure relief device
with location of each PRV provided on the transformer will adequately meet
our requirement. The quantity of three numbers is on the basis that two
numbers will be required as per design calculation and one number additional
PRD shall be provided from the point of view of additional safety.
Constructional and design details of pressure relief device must be furnished
and it should be proved by calculation that the size and operating pressure
setting of pressure relief device is adequate, considering the rating of the
transformer and quantity of oil in the transformer. Furnishing of this
information is a must. These PRD's shall be of sufficient size for rapid
release of any pressure that may be generated in the tank and which may
result in damage to the equipment. The device shall operate at a static
pressure of less than the hydraulic test pressure of transformer tank. It
shall be mounted directly on the tank. One set of electrically insulated
contacts shall be provided for alarm & tripping along-with the
recommendations.
11.9 Relays
11.9.1 Buchholz Relay : A double float type Buchholz relay along with
suitable moulded type cover to avoid ingress of moisture/ rain water shall be
provided. All the gases evolved in the transformer shall collect in this relay.
The relay shall be provided with a test cock suitable for a flexible pipe
connection for checking its operation and for taking gas sample. A copper
or stainless steel tube, shall be connected from the gas collector to a
valve located about 1200mm above ground level to facilitate sampling of
gas while the transformer is in service. The device shall be provided with

two electrically independent ungrounded contacts, one for alarm on gas


accumulation and the other for tripping on sudden rise of pressure. The
contacts of relay shall be properly housed, sealed and gasketted to make the
arrangement water proof. Entry of moisture/water in the contact chamber
needs to be eliminated. Cable entry to terminal box of buchholz relay should
be made through bottom of relay.
11.9.2 Oil Surge Relay (OSR) : From our past experience, it is found
that undesired tripping of Power Transformers is occurring on oil surge relay
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 16 of 105

(OSR)and Buchholz relay operation actuating due to accumulation of water


inside relay pockets. The water accumulation takes place through entry
point of cable gland. In view of above, the design and placement of Alarm &
trip contact assembly of OSR and Buchholz Relay should be improved to
take care of the following requirements:
(a) The cable entry to terminal box of OSR should be made through
bottom of relay. Also the OSR relay should be protected from rain
water by providing proper cover on it.
(b) In order to ensure exit/drainage of accumulated water from inside the
relay, a fine hole should be made in terminal box of relay.
Note : The Bidders shall ensure that the compartments housing relay
contacts of Pressure Relief Valve , Buchholz Relay and Oil Surge Relay are
made absolutely water and vermin proof. The compartment housing
contacts of OSR,PRV and Buchholz Relay shall be tested for water proof at
the time of inspection and effectiveness of water proofing shall be
demonstrated at the time of inspection. This should be noted carefully by
the Bidder and specifically confirmed in their bid.
11.10 Temperature Indicator
11.10.1 Oil Temperature Indicator (OTI) :Transformers shall be
provided with a 150mm dial type thermometer with maximum pointer for
top oil temperature indication. The thermometer shall have adjustable two
electrically isolated heavy duty alarm and trip contacts, maximum reading
pointer and resetting device mounted in the Fan control cubicle (FCC). A
temperature sensing element suitably located in a pocket on top oil shall be
provided. This shall be connected to the OTI by means of capillary
tubing. Accuracy class of OTI shall be plus or minus 1.0% or better. The OTI
shall be provided with anti vibration mounting .
11.10.2 Winding Temperature Indicator (WTI)
(a) WTI for measuring the winding temperature of the windings
shall be provided. It shall comprise of the following
(i) Temperature sensing element.
(ii) Image coil.
(iii) Auxiliary CTs, if required, to match the image coil, shall
be provided.
(iv) 150mm dia local indicating instrument with maximum
reading pointer mounted in FCC/marshalling box and with
four adjustable electrically isolated heavy duty contacts
(two for control of cooling equipment, one for high
winding temperature alarm and other for trip) shall be
provided. The WTI shall be provided with anti vibration
mounting.
(v) Calibration device.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 17 of 105

(b) In addition to the (a) above, repeater dial of WTI for each

winding shall be provided for Remote winding temperature


indication. It shall be suitable for flush mounting on RTCC
panel. A precision potentiometer mounted inside the case
shall function as a transmitter to operate a repeater for
RWTI. The transmitter shall be directly connected to the
repeater.
(c) Auxiliary supply, if required in RTCC panel for RWTI, shall be
110V DC only.
(d) Accuracy class of WTI as well as RWTI shall be plus or minus
1.0% or better.
(e) Any special cables required for shielding purpose for
connection between cooler control cabinet and remote winding
temperature indicator control circuit shall be in Bidders
scope of work.
(f) WTI CT ratio shall be embossed on secondary winding terminal
box.
Note Some of the manufacturers have a practice to directly install
winding temperature indicator (WTI) and oil temperature indicator
(OTI) on the body of the transformer in open. This is not acceptable
& it is obligatory on the part of the Bidders to enclose OTI & WTI
and all such accessories in a separate Fan Control Cubicle (FCC)
cum Marshalling Box .
11.11 Core
a) The core shall be constructed from high grade, non- ageing,
low loss, Cold Rolled Super Grain oriented (CRGO) silicon
steel laminations of HI-B grade steel or better. All stipulations
under clause 4.4 should be considered while selecting material
of core. Interlamination resistance shall be as per BS601
Part 5 method of July 1973. The Bidder shall furnish the
details of steel laminations i.e. type alongwith hysterisis
loss curve (B-H curve) etc.
(b) After being sheared, the laminations shall be treated to
remove all burrs and shall be re-annealed to remove all
residual stresses.
(c) The design of the magnetic circuit shall be such as to avoid
static discharges, development of short circuit paths within
itself or to the earthed clamping structure and production of
flux component at right angles to the plane of laminations
which may cause local heating.
(d) The core shall be provided with lugs suitable for lifting complete
core & coil assembly of transformer.
(e) Core Belting : The core shall be rigidly clamped by belting to
ensure adequate mechanical strength. Core and winding
shall be capable of withstanding the vibrations & shock
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 18 of 105

during transport, installation, service and adequate


provision shall be made to prevent movement of core &
winding relative to tank during these conditions. The
location, size and material of belting shall be clearly
indicated in drawing which shall be submitted with Bid.
Bolted type core construction shall not be acceptable.
(f) All steel sections used for supporting the core shall be
thoroughly sand blasted after cutting, drilling and welding.

(g) Each core lamination shall be insulated with a material that will
not deteriorate due to pressure and hot oil.
(h) The insulation of core to bolts and core to clamps
plates shall be able to withstand a voltage of 2KV RMS
for one minute.
(i) The maximum flux density in any part of the core and yoke at
rated MVA, 110% voltage and (-) 4% frequency at any tap
shall not exceed 1.90 Tesla. The Bidder shall provide
saturation curve of the core material proposed to be used
and calculations to demonstrate that the core is not over
fluxed under stringent condition of transformer operation.
(j) Bidder will offer the core for inspection & approval by
the purchaser during the manufacturing stage.
Bidder's call notice for this purpose should be
accompanied with the following documents, as
applicable, as a proof towards use of prime core
material.
i) Invoice of the supplier
ii) Mill's Test Certificate
iii) Packing List
iv) Bill of lading
v) Bill of entry certificate by customs.
(k) Core material shall be directly procured either from the
manufacturer or through their accredited marketing
organization of repute and not through any agent.
(l) Bidder should have in-house Core Cutting facility for proper
monitoring & control on quality and also to avoid any
possibility of mixing of prime material with defective/second
grade material.
(m) Oil ducts shall be provided wherever necessary to ensure
adequate cooling. The winding structure and major insulation
shall not obstruct the free flow of oil through such ducts.
Where the magnetic circuit is divided into pockets by cooling
ducts parallel to the plane of laminations or by insulating
material above 0.254 mm. Thick, tinned copper strip bridging
pieces shall be inserted to maintain electrical continuity
between pockets. The design of the magnetic circuit shall be
such as to avoid static discharge development of short circuit
path within itself or to the earthed clamping structure and
production of flux components at right angles to the plane of
the laminations which may cause local heating.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 19 of 105

(n) Core shall not directly rest on the bottom metal sheet of
transformer tank. Around 3 mm or more free space for oil
insulation shall be made between the core and bottom sheet of
transformer tank. A 5 mm FRP Insulating sheet shall be
provided to take care of core earthing due to accidental
slippage of stampings. Also in addition to this extra
insulation thickness of 5 mm or more FRP sheet be
provided at the bottom of resting shoes of end frame
with proper fixing arrangement to avoid accidental
slippage, damages etc.
11.12 Windings

(a) The Bidder shall ensure that windings of all transformers are
made in dust proof, conditioned atmosphere. The Bidder shall
furnish the facilities available at their works alongwith the
bid.
(b) The conductors shall be of electrolytic grade copper as per
relevant IS. The maximum current density for design of
transformers within specified limits of transformer losses shall
not exceed the limits of 300 amps per sq.cm.
(c) The insulation of transformer windings and connections shall
be free from insulating compounds which are liable to
soften, ooze out, shrink or collapse or be catalytic and
chemically active in transformer oil during service.
(d) Coil assembly and insulating spacers shall be so arranged as
to ensure free circulation of oil and to reduce the hot spot of
the winding. The conductor shall be transposed at sufficient
intervals in order to minimize eddy currents and equalize the
distribution of currents and temperature along the winding.
(e) The LV winding should withstand short circuit faults/forces of
the transformer upto the prescribed fault levels on HV & LV
sides against mechanical and thermal stresses.
(f) Best insulating material shall be used and compression of
the windings after drying out shall be carried out at a
pressure exceeding one and a half to twice the force which
can occur in the transformer; to impart greater mechanical
strength to the windings against heavy short circuit
stresses.
(g) The windings shall be so designed that all coil assemblies of
identical voltage ratings shall be interchangeable and field
repairs to the windings can be made readily without special
equipment. The coils shall be supported between adjacent
sections by insulating spacers, and the bracings and other
insulation used in the assembly of the winding shall be
arranged to ensure free circulation of the oil to reduce hot
spots in the windings.
(h) The coil insulation shall be treated with suitable insulating
varnish or equivalent compound wherever necessary to
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 20 of 105

develop the full electrical strength of the winding. All materials


used in the insulation and assembly of the winding shall be
insoluble, non-catalytic and chemically inactive in the hot
transformer oil and shall not soften or otherwise be adversely
affected under the operating conditions.
(i) All threaded connections shall be provided with locking
facilities. All leads from the winding to the terminal
connectors and bushings shall be rigidly supported to prevent
injury from vibration. Guide tubes shall be used where
practicable.
(j) Windings shall be subjected to a shrinkage treatment before
final assembly so that no further shrinkage occurs during
service. Adjustable device shall be provided for taking up any
possible shrinkage of coils in service. After shrinkage process,
the windings shall be clamped securely in place so that they
will not be displaced or deformed during short circuits. The

assembled core and windings shall be vacuum-dried and


suitably impregnated before removal from the treating tank.
The copper conductors used in the coil structure shall be
best suited to the requirements and all permanent current
carrying joints in the windings and the leads shall be
crimped or brazed preferably by high frequency brazing
system.
It is observed that many manufacturers are using sectored
clamping arrangement at top as well as bottom for clamping of
the windings. This type of arrangement is considered to be not
suitable for EHV grade power transformers. In this regard, it
may be noted that both top & bottom clamping rings to be
provided for clamping of windings shall be of one piece single
ring. The top & bottom clamping rings should be of
minimum thickness 60 mm thk with proper safety
margins based on design and shall be in one piece to
make the clamping arrangement sturdy. Sectored
pressure/clamping rings are not acceptable. The single
pressing/clamping ring shall be provided with adequate
number of pressure/jacking points as per design. Since
sectored ring arrangement shall not be accepted hence
bidder should ensure and confirm this specific
requirement in the technical questionnaire.
(k) Bidder will offer the Copper and insulating material for
windings for inspection & approval by the purchaser during
the manufacturing stage. Bidder's call notice for the
purpose should be accompanied with the following documents,
as applicable, as a proof towards use of prime Copper and
insulating material for windings .
i) Invoice of the supplier
ii) Mill's Test Certificate
iii) Packing List
iv) Bill of lading
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 21 of 105

v) Bill of entry certificate by customs.


(l) Core, Copper and insulating material for windings shall be
directly procured either from the manufacturer or through their
accredited marketing organisation of repute and not through
any agent.
(m) Certificate : Supplier shall provide purchaser details
of procurement of raw materials i.e., core, insulation &
copper. Supplier shall also record a certificate as under :
" CERTIFICATE "
It is certified that the Transformer shall be
manufactured by --------- (Name of manufacturer) out of
the core, insulating and winding material procured as per
details indicated in specification. We are agreeable to
undertake third party inspection of Transformer during its
manufacture or of raw materials, at the sole discretion of
MPPTCL without any extra cost.
If at any stage it is found that the transformer is not
manufactured out of the raw material indicated in
specification, the transformer shall be liable for rejection by

MPPTCL and transformer shall be replaced by (name of


manufacturer) at no extra cost to MPPTCL.
Signature of Authorised
Signatory with Seal of manufacturer
(o) The Purchaser also reserves the right to carry out stage
inspections at other stages also, for which advance
intimation shall be given and all necessary cooperation
shall be rendered by the supplier.
11.13 Bushings
(a) The electrical & mechanical characteristics of bushings shall
be in accordance with IS-3347 & IS-2099 ( latest version ) &
IEC 60137(2008 or latest version).
(b) The bushings shall have high factor of safety against
leakage to ground and shall be so located as to provide
adequate electrical clearances between bushings and also
between the bushings and grounded parts. Bushings of
identical voltage rating shall be of similar BCT and
inter changeable. All bushings shall be equipped with
suitable terminals of approved type and size and all external
current carrying contact surfaces shall be adequately silver
plated. The insulation class of the high voltage neutral
bushing shall be properly coordinated with the insulation
class of the neutral of the high voltage winding.
(c) All main winding and neutral leads shall be brought out
through outdoor type bushings which shall be so located that
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 22 of 105

the full flashover strength will be utilized and the


adequate phase clearance shall be realized.
(d) Each bushing shall be so coordinated with the transformer
insulation that all flashovers will occur outside the tank.
(e) All porcelain used in bushings shall be of the wet process,
homogeneous and free from cavities or other flaws. The
glazing shall be uniform in color and free from blisters, burns
and other defects.
(f) (i) For 33KV winding & neutral , the bushing shall be of
OIP condenser of 72.5KV class of draw rod type/solid
stem type.
(ii) The bushings of 145 KV class shall be of OIP condenser of
draw rod type (DR) only.
(iii) Tan-delta of all bushings shall be 0.005 (max.)during
testing at manufacturers works.
(g) All bushings shall have puncture strength greater than the dry
flashover value.
(h) Main winding terminals shall be solder-less terminals and
shall be of the type and size specified in the schedule of
requirement of drawings.
(i) The spacing between the bushings must be adequate to
prevent flashover between phases under all conditions of
operation. The clearances shall be as follows :
S.
N
o
Nomin

al
Syste
m
Voltag
e
Voltage
Class
Of
Bushing
Curre
nt
Rating
Impulse
Withsta
nd
Voltage
(Kvp)
1min.Po
wer Frequency
Withstan
d Voltage
Kv(rms)
Creepa
ge
Distanc
e
in mm
Clearance
in mm
Ph to
Ph.
Ph to
E
1 132KV 145KV 1250A 650 275 3625 1430 1270
2 33KV 72.5KV 2000A 325 140 1813 700 660
The Bidders are required to confirm clearances and no change
/reduction in clearances shall be acceptable. The clearances
shall be clear distances in air after accounting for
clamps/connectors dimensions to be mounted on the stud of
bushings.
(j) Special adjustable arcing horns shall be provided for the HV
bushings. For 72.5KV class bushings, arcing horns are not
required.
(k) The Bidder is requested to furnish the guaranteed withstand
voltage for the above and also furnish a calibration curve with
different settings of the coordination gap to the purchaser
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 23 of 105

to decide the actual gap setting. Bidder's


recommendations are also invited in this respect.
(l) The bushings shall be capable of withstanding without injury
the electrical, thermal and mechanical effects of external
short circuits. The 145 KV bushings shall be rated for short
time thermal current rating of 40 KA for 3 seconds and 72.5

KV Bushings, for 31.5KA for 3 seconds.


(m) All the transformers covered under this specification shall be
utilized in heavily polluted atmosphere. In view of this the
Bidders while offering prices for the transformers against
this contract may please note that the offer should be made
out based on the creepage for the bushings @ 25mm per KV
based on the voltage of 72.5KV/145KV. Thus in the quoted
prices of transformer cost of bushings should be included
based on a creepage distance of 25mm per KV.
(n) All O.I.P. Condenser bushings shall be provided with :
(i) Oil level gauge.
(ii) Oil filling plug and drain valve, if not hermetically sealed.
(iii) Tap for capacitance/tan delta test.
(o) The bushings with current transformers are specified,
hence the bushings shall be removable without disturbing the
current transformers.
(p) Porcelain used in bushing manufacture shall be homogenous,
free from laminations, cavities and other flaws or
imperfections that might affect the mechanical or dielectric
quality and shall be thoroughly vitrified tough and
impervious to moisture. Glazing of porcelain and bushing
shall be of uniform brown color free from blisters and burrs.
(q) Bushing turrets shall be provided with suitable vent pipes
which shall be connected to route any air/gas collection
through the Buchholz relay.
(r) For Bushings of all voltage class, the arrangement for
connection of winding/neutral terminal shall be indicated .
(s) From the end point of the condenser of the bushing which
will protrude inside the transformer OR the bottom
termination point of bushing, sufficient clearance should be
available so that in case any other make bushing is
installed problem in this regard may not arise. Maximum
length of condenser portion, which can be easily
accommodated, should be clearly indicated by the Bidder.
(t) The LV take off arrangement within the transformer is of
utmost importance hence due care shall be taken while
providing this arrangement inside the transformer tank. The
connecting lug of LV winding with the bushing bottom terminal
pad should match with the current rating of the bushing. The
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 24 of 105

size of the LV winding lug shall be of suitable rating to match


with the maximum load current of the transformer to be fed
through extreme tap of OLTC meeting requirements of IS6600. In this regard, the clamping arrangement of LV
winding with two lugs having two holes with two hole
terminals on counter part of the bushing pad are not
acceptable. In case of such arrangement, it will have to
be ensured that the counter part of winding lead/lug i.e.
bushing terminal is with four holes or vice versa.
11.14 Bushing Current Transformers
(a) Current transformers shall comply with IS:2705.
(b) One no. bushing CT of Ratio 400/1 on each phase of HV & One
no. bushing CT of Ratio 1200/1 on each phase of LV winding

i.e 3 nos for HV & 3 nos for LV winding, one no. bushing CT of
Ratio 400/1 for HV neutral and one no. bushing CT of Ratio
1200/1 for LV neutral shall be provided for each outdoor
Transformer.
(c) It shall be possible to remove turret mounted CTs from the
transformer tank without removing the tank cover. Necessary
precaution shall be taken to minimize the eddy currents and
local heat generated in the turret.
(d) All secondary leads shall be brought to a terminal box near
each bushing. These terminals shall be wired out to cooler
control cabinet using separate cables for each core.
(e) For the thermal image coil of winding temperature indicator,
CT with suitable ratio and class may be used.
11.15 Terminal Marking : The terminal marking and their physical
position shall be in accordance with IS:2026.
11.16 The positioning of HV & LV bushings shall be such that skew
jumpering is avoided. The middle phase primary & secondary bushing center
line shall be parallel to side axis of the transformer body.
12.0 EARTHING ARRANGEMENT
12.1 NEUTRAL EARTHING ARRANGEMENT : The neutral terminal
of the star connected HV / LV winding shall be brought up to the ground
level through two tinned copper flat strips of size 50x6mm which shall be
supported on transformer tank horizontal/vertical by porcelain insulators of
adequate voltage class. The number of insulators shall be sufficient to
provide a mechanically sturdy arrangement. Necessary mechanical supports
on the tank for mounting of the insulators shall be made. The KV class rating
of insulators shall commensurate with the rating /KV class of neutral design.
It may be ensured that connection of the neutral strips to neutral bushings at
one end shall be made using a terminal connector suitable for connection to
the neutral bushing terminal and to receive 2x50x6 mm tinned copper strips
on the other side. The connection between the bushing and transformers
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 25 of 105

earth pit shall be through 2x50x6 mm tinned copper strips single run without
any joint connection/brazing/ welding etc. In case of problem in availability of
single run tinned copper strips, it may be accepted with single joint. However,
joint to be provided shall be subject to approval of purchaser. The other end
of the earth connection to the earth pit shall also be through terminal
connector suitable to receive 2x50x6 mm copper strips at one end and to
receive MS flat and /or twin ACSR zebra conductor on the other end. The
length of the copper strips shall be suitable for providing a joint less
connection between transformer neutral and earth pit and details in this
regard shall be intimated to the successful bidder based on
transformer/substation layout design. A typical arrangement is shown in drg.
No: MPPTCL/63MVA/02 of this specification for neutral earthing.
12.2 CORE EARTHING ARRANGEMENT : The bidder should note our
requirement in this regard very clearly. It is required to bring out leads from
core, end frame and tank to the top of the transformer through only
three insulated bushings. The arrangement shall be housed in a box at the top
cover of transformer tank with provision for interconnection between the studs
of bushings. The bushing housing shall have a suitable cover with gasket to
make the arrangement waterproof. A clear marking (engraved/punched)
shall be made to indicate that the housing contains core/end frame/ tank
earthing arrangement. Please note that stickers/flags/tags/painted marking for

identification shall not be accepted. A typical sketch of general arrangement


needed by purchaser is shown in drawing no. MPPTCL/63MVA/03 of this
specification. Arrangement shall be such that even after removal of
connections, oil shall not leak. Removable shorting strips between the three
bushing shall be provided. It may be noted that internal earthing of any
nature between core and End frame should not be provided. Earthing at
site shall be done by interconnecting the three bushings through shorting
strips. This arrangement is to facilitate checking of multiple core earthing
in the transformer.
It may be noted that :
a) Any alternative arrangement is not acceptable and therefore
bidder must confirm provision of three bushings as desired
above.
b) Once transformer reaches site, before unloading from the
trailor the position of core earthing shall be checked and in
case any problem of multiple core earthing is observed,
delivery of Transformer will not be taken.
The insulated cable to be used for core to Bushing connection & end
frame to Bushing connection should be of good quality with proper
grounding arrangement. The size & no. of strands of cable shall be
subject to Purchasers approval.
13.0 AUXILIARY POWER SUPPLY FOR OLTC, COOLER CONTROL
AND POWER CIRCUIT
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 26 of 105

13.1 Duplicate (Two) auxiliary power supplies of 0.4 KV, three phase,
four(4) wire shall be provided by the purchaser at cooler control cabinet and
for OLTC drive.
13.2 All loads shall be fed by one of the two feeders through an
electrically interlocked automatic transfer switch housed in the cooler control
cabinet , for tap changer control and cooler control circuits.
13.3 Design features of the transfer switch shall include the following :
i) Provision for the selection of one of the feeders as normal
source and other as standby.
ii) Upon failure of the normal source, the loads shall be
automatically transferred after an adjustable time delay to the
standby source.
iii) Indication to be provided at cooler control cabinet & RTCC
for failure of normal source and for transfer to standby source
and also for failure to transfer.
iv) Automatic re-transfers to normal source without any
intentional time delay following re-energisation on the
normal source.
v) Both the transfer & re-transfer shall be dead transfers and AC
feeders shall not be paralleled at any time.
13.4 AC feeder shall be brought to the OLTC cabinet (Cooler Control Cabinet)
by the Bidder, after suitable selection at cooler control cabinet. The Bidder
shall derive AC power for control circuit from the AC feeder as mentioned
above by using appropriately rated dry type transformers. If the control
circuit is operated by DC supply then suitable converters to be provided by
the Bidder to be operated from AC Power source.
13.5 Necessary isolating switches and HRC fuses shall be provided at suitable
points as per approved scheme of purchaser.
14.0 TAP CHANGING EQUIPMENT

14.1: GENERAL REQUIREMENT


a) OLTC gear shall be motor operated for local as well as remote
operation. An external hand wheel/handle shall be provided for local
manual operation. This hand wheel/handle shall be easily operable by a
man standing at ground level.
(b) Arrangement shall be made for securing and padlocking the tap changer
wheel in any of the working positions and it shall not be possible for
setting or padlocking the wheel in any intermediate position. The
arrangement shall be such that no padlock key can be inserted unless
all contacts are correctly engaged and switch set in a position where no
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 27 of 105

open or short circuit is possible. An indicating device shall be provided to


show the tap in use.
(c) The design of OLTC shall be on the principle of Constant Flux Design
(CFVV) wherein HV (132KV ) voltage would be varied in the range of (+)5
% to (-)15 % in steps of 1.25 % so as to provide constant voltage of 33
KV on LV side. While through current rating of OLTC shall be based on
cl.2.3.2 of IS 8478,the purchaser desires to obtain OLTC with higher
voltage and current rating from the point of view of better performance. In
view of this, the bidder shall offer OLTC for 63 MVA transformer suitable
for rated voltage and rated current as mentioned in the following table :
Transformer
Rating
OLTC on
Winding
(HV)
Rating of OLTC
Voltage
Rating
Minimum
Current
Rating
Tap Range
(In steps of
1.25%)
132 KV, 63
MVA
132KV 66KV/132KV* 500 Amp. (+)5% to (-)15%
*Suitable for 132KV neutral end
d) The OLTC motor should be capable of smooth and trouble free operation
with supply voltage variation of 0.4 KV +10% & -25%.
14.2 ON LOAD TAP CHANGING GEAR (OLTC)
(a) The details of the method of diversion of the load current during tap
changing, the mechanical construction of the gear and the control
features for OLTC gear alongwith detailed drawings on the inner view and
the arrangement of connections shall be submitted with the Bid.
Information regarding the service experience on the gear and a list of
important users shall also be furnished. The tap changer shall change the
effective transformation ratio without producing phase displacement.
(b) The current diverting contacts shall be housed in a separate oil chamber
not communicating with the oil in main tank of the transformer.
(c) The contacts shall be accessible for inspection without lowering oil level in
the main tank and the contact tips shall be replaceable.

(d) The Bidder shall indicate the safeguards employed to take care of harmful
arcing at the current diverting contacts in the event of operation of the
OLTC gear under overload conditions (overloading capability as per IS
6600) of the transformer. Necessary tools and tackles shall be provided
alongwith main supply for maintenance of OLTC gear.
(e) The OLTC oil chamber shall have oil filling and drain valves, oil sampling
valve, relief vent and oil level gauge/glass. It shall also be fitted with
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 28 of 105

an oil surge relay. For accommodating oil expansion of OLTC a separate


conservator tank shall be provided.
(f) The diverter switch or arcing switch shall be designed so as to ensure that
its operation once commenced shall be completed independently of the
control relays or switches, failure of auxiliary supplies etc. To meet any
contingency which may result in incomplete operation of the diverter
switch, adequate means shall be provided to safeguard the transformer
and its ancillary equipments.
(g) Drive mechanism chamber shall be mounted on the tank in accessible
position. It should be adequately ventilated and provided with anti
condensation metal clad heaters. All contactors, relay coils and other
parts shall be protected against corrosion, deterioration due to
condensation, fungi etc.
(h) The control feature shall provide the following :
i) LOCAL-REMOTE selector switch mounted in the local control
cubicle shall switch control of OLTC for lower/ raise functions in
local or remote mode as selected.
ii) The LOCAL-REMOTE selector switch shall have at-least two spare
contacts per position which are closed in that position but open in
the other position.
iii) A RAISE-LOWER CONTROL SWITCH shall be provided in the local
control cubicle. The switch shall be spring loaded to return to the
Centre "OFF" position and shall require movement to the RIGHT to
raise the voltage of the transformer. Movement to the left shall
lower the voltage. Alternatively push button type arrangement of
standard design may be provided.
iv) An OFF-ON tap changer control switch shall be provided in the OLTC
local control cabinet of transformer. The tap changer shall be
inoperative in the OFF position. Also the OFF-ON switch shall have
atleast one spare contact per position which is closed in that
position but open in the other position.
v) Operating mechanism for on load tap changer shall be designed to
go through one step or tap change per command. Subsequent tap
changes shall be initiated only by a new or a repeat command.
vi) On load tap changer shall be equipped with a time delay in complete
STEP alarm consisting of a normally open contact which closes, if
the tap changer fails to make a complete tap change. The alarm
shall not operate for momentary loss of auxiliary power.
vii) The selsyn units or approved equivalents shall be installed in the
local OLTC control cabinet to provide tap position indication for the
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 29 of 105

transformer. Complete mounting details shall be included with


approved diagram.
viii) Transformer load tap changer shall be equipped with a fixed resistor
network capable of providing discrete voltage steps for input to the

supervisory system. Any other approved / established design for


remote indication of tap position shall also be acceptable.
(i) Limit switches shall be provided to prevent overrunning of the
mechanism and in addition, a mechanical stop shall be provided to
prevent over-running of the mechanism under any condition.
(j) Limit switches may be connected in the control circuit of the operating
motor provided that a mechanical-de-clutching mechanism is
incorporated.
(k) Thermal device or other means shall be provided to protect the motor
and control circuit. All relays, switches, fuses etc. shall be mounted in the
drive mechanism chamber and shall be clearly marked for the purpose
of identification.
(l) A permanently legible lubrication chart shall be fitted within the driving
mechanism chamber.
(m) Any "DROP DOWN" tank associated with the tap changing apparatus
shall be fitted with guide rod to control the movements during lifting or
lowering.
(n) A five digit counter shall be fitted to the tap changing equipment to
indicate the number of operations performed.
(o) All relays and operating devices shall operate correctly at any voltage
between the limits specified.
(p) It shall not be possible to operate the electric drive when the manual
operating gear is in use.
(q) It shall not be possible for any two controls to be in operation at the
same time.
(r) The equipment shall be suitable for supervisory control and indication
with make before break multi-way switch, having one potential free
contact for each tap position. This switch shall be provided in addition
to any other switch/switches which may be required for remote tap
position.
(s) Operation from the local or remote control switch shall cause one tap
movement only until the control switch is returned to the off position
between successive operations.
(t) All electrical control switches and the local operating gear shall be clearly
labeled in a suitable manner to indicate the direction of tap changing.
(u) Transfer of source failure of one AC supply shall not affect tap changing
operation.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 30 of 105

(v) For the purpose of operation of OLTC, based on design of


manufacturer, transition resistor could be used. However, no component
of OLTC including transition resistor shall be housed inside main
transformer tank. The design of the transition resisters should be liberal
to ensure suitability during tap change operation at rated current
including over loading capability and system short circuits.
(w) The location and design of OLTC shall be such that in the event of any
repair / maintenance , it should be possible to take out various parts
from the OLTC and other accessories and fittings mounted on the
transformer particularly equalizing pipes etc do not infringe /obstruct.
14.3 MANUAL CONTROL : The cranking device for manual operation of
the OLTC gear shall be removable and suitable for operation by a man
standing on ground level. The mechanism shall be complete with the
following :
i) Mechanical tap position indicator which shall be clearly visible to the

person operating tap changer manually at the transformer.


ii) A mechanical operation counter.
iii) Mechanical stoppers to prevent over-cranking of the mechanism beyond
the extreme tap positions.
iv) The manual control considered as back up to the motor operated load
tap changer control shall be interlocked with the motor to block motor
start-up during manual operation. The manual operating mechanism
shall be labeled to show the direction of operation for raising the
voltage and vice-versa.
14.4 ELECTRICAL CONTROL This includes Local Electrical control and
Electrical remote control from remote control panel. The control circuits shall
have the following features:
(i) An interlock to cut off electrical control automatically upon recourse
being taken to the manual control in emergency.
(ii) Reinforcement of the initiating impulse for a tap change, ensuring a
positive completion once initiated to the next (higher or lower) tap.
(iii) Step-by-step operation ensuring only one tap change from each tap
changing impulse and lock-out of the mechanism if the control switch (or
push button) remains in the "Operate Position".
(iv) An interlock to cut-out electrical control when it tends to operate the
gear beyond either of the extreme tap positions.
(v) An electrical interlock to cut-off a counter impulse for reverse step
change being initiated during a progressing tap change and until the
mechanism comes to rest and resets circuits for a fresh position.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 31 of 105

Suitable interlocks shall be provided to prevent operation of OLTC


beyond extreme tap with a mechanical/electrical lockable switch.
(vi) Protection apparatus, considered essential by the Bidder according to
specification.
14.5 REMOTE ELECTRICAL GROUP CONTROL The OLTC control scheme
offered shall have provision of remote electrical group control during parallel
operation of transformers. This is in addition to independent control of OLTC.
(i) A four position selector switch having MASTER, FOLLOWER,
INDEPENDENT and OFF position shall be provided in the remote OLTC
control panel for each transformer. This shall be wired to enable
operator to select operation of OLTC in either Master, Follower or
Independent mode.
(ii) Out of step relays with timer contacts shall also be provided to
give alarm and indication in case of tap positions in all the
transformers under group control being not in same position.
(iii) Master Position : If the selector switch is in MASTER position, it shall
be possible to control the OLTC units in the FOLLOWER mode by
operating the controls of the MASTER unit Independent operation of the
units under FOLLOWER mode shall have to be prevented. However, the
units under independent mode will be controlled independently.
(iv) Follower Position : If the selector switch is in FOLLOWER mode,
control of OLTC shall be possible only from MASTER panel.
(v) Independent Position : In this position of Selector Switch, Control of
OLTC of individual unit only shall be possible.
14.6 LOCAL OLTC CONTROL CUBICLE The Auxiliary devices for electrical
control of the OLTC shall be housed in a weather proof cubicle. It shall be
complete with the following :
i) A circuit breaker/contactor with thermal overload devices for

controlling the AC auxiliary supply to the OLTC motor.


ii) Cubicle light with door switch.
iii) Space heaters to prevent condensation of moisture.
iv) Padlocking arrangement for hinged door of cabinet.
v) Cable terminal glands for power and control cables to the OLTC
gear.
14.7 REMOTE TAP CHANGER CONTROL PANEL (RTCC)
Remote tap changer control panel to be supplied by the Bidder shall
consist of :
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 32 of 105

i) Actuating switch for electrical raise/lower control.


ii) Remote tap position indicator.(preferred digital type)
iii) Signal lamps for Tap changer in progress and Tap changer out of
step.
iv) Auxiliary devices for remote electric group control of OLTC.
v) Annunciation scheme with the following :
(a) Fan fail (for all fans individual windows).
(b) AC supply fail.
(c) Stand by fan fail.
(d) Stand by fan on.
(e) OLTC motor over loaded.
(f) OLTC control supply fail.
(g) OLTC at extreme position i.e. lowest & highest voltage tap.
(h) Two spare windows.
vi) Indicating Devices : Following lamp indications shall be provided in
Remote tap changer control cubicle /panel
- Fan "ON", Fan "OFF"
- Cooling system "On Automatic Control".
- Cooling system "On Manual".
- Selector switch in auto or manual.
- 433volts cooler supply auto changeover.
- Control supply failure main and standby.
- one potential free initiating contact for all the above indications
shall be wired independently to the terminal blocks of cooler
control cabinet exclusively for owner's use.
vii) Remote OTI with repeater unit.
viii) WTI repeater unit.
ix) Voltmeter for indicating HV & LV voltage.
x) Schedule of equipments for RTCC panel shall be as under:
1. Name plate remote OLTC and cooler control cubicle
2. Indicating lamp-OLTC control supply on ( red)
3. Indicating lamp-tap change in progress ( yellow)
4. Indicating lamp-OLTC out of step ( red)
5. Indicating lamp-OLTC motor trip ( red)
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 33 of 105

6. Cooler mode selector (auto-off-on)


7. OLTC sequence selector switch.(OFF-INT-FOLL-MAST.)
8. Emergency stop push button for tap change operation. (red)
9. Auxiliary contactor for OLTC out of step monitoring.
10. Out of step timer.
11. Voltmeter for HV. (0-150 KV)
12. Remote oil temperature indicator.
13. Voltmeter for LV. (0-40 KV)

14. Terminal blocks.


15. Cubicle lamp.
16. Door switch.
17. HRC cartridge fuse holder with link for cubicle illumination circuit.
18. Neutral link.
19. Earth bus.
20. HRC cartridge fuse holder with link for HV volt meter.
21. HRC cartridge fuse holder with link for LV volt meter..
22. HRC cartridge fuse holder with link for RWTI and ROTI circuit.
23. Selector switch for HV volt meter.
24. Selector switch for LV volt meter.
25. Remote winding temperature indicator.
28. OLTC control switch
29. Tap position indicator (digital).
xi. a. HV digital Voltmeter of accuracy class 0.5 provided for indicating HV
voltage shall be scaled for voltage range 0-150 KV (phase to phase)
and shall be suitable for use with PT ratio 132KV/110 volt. The HV
digital voltmeter shall be precisely calibrated so as to indicate 132KV
Voltage on voltmeter scale corresponding to input voltage of 110 Volt
(phase to phase).
b. LV digital Voltmeter of accuracy class 0.5 provided for indicating LV
voltage shall be scaled for voltage range 0-40 KV (phase to phase)
and shall be suitable for use with PT ratio 33KV/110 volt. The LV
digital voltmeter shall be precisely calibrated so as to indicate 33KV
Voltage on voltmeter scale corresponding to input voltage of 110 Volt
(phase to phase).
15.0 COOLING EQUIPMENT
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 34 of 105

15.1 The design shall take into account the following requirements
a) The oil cooling system of transformer shall be designed using
2x50% radiator banks. The radiator banks shall be mounted
on two different sides of transformer tank. The arrangement
shall be subject to approval by the purchaser based on
substation layout and positioning of other neighboring switch
yard equipments. Coolers/radiators shall with stand pressure /
vacuum conditions specified for the tank. All coolers/ radiators
shall be attached on the transformer tank through header
having suitable expansion joints (flexible coupling) to
ensure adequate mechanical strength against vibration
etc. subject to specific approval from the purchaser. Radiators
directly mounted on transformer tank are not
acceptable.
b) Each radiator bank / block shall have its own set of cooling
fans, shut off valves, lifting lugs, top and bottom oil filling
valves, air release plugs, drain valves and if considered
necessary based on design thermometer pocket fitted with
captive screw cap on the inlet and outlet, in line with valve
schedule as per Annexure-V.
c) Each radiator bank shall be provided with at least 20%
standby (spare)cooling fans. These spare fans shall be duly
mounted and shall also be wired up complete with required
protective devices and be identified with each radiator bank.
While working out number of spare fan for 20% additional

cooling per bank, if 20% quantity works out in fraction , the


spare fans to be provided shall be next whole number.
d) Cooling fans shall be designed to meet overloading
requirements as per clause 4.1 (b).
e) The exhaust air flow from cooling fan shall not be directed
towards the main tank in any case.
f) Cooling fans for each radiator bank shall be located so as to
prevent ingress of rain water. Each fan shall be suitably
protected by galvanised wire guard.
g) The cooler and its accessories shall preferably be hot dipped
galvanised or corrosion resistant paint shall be applied to it.
h) Each cooling fan shall be provided with starter thermal
overload and short circuit protection and also single phase
preventor.
i) Each radiator shall be provided with suitable lifting lugs and
shut off/air release/sampling valves as per Annexure-V.
j) Expansion joints, one each on top and bottom cooler pipe
connections as per a above.
k) Air release device/plug and oil drain plug on oil pipe
connections.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 35 of 105

l) The cooling Fans shall be mounted on separate


foundation at bottom of externally mounted radiator
Banks. Mounting of Cooling fans directly on Radiators or on
transformer tank is not acceptable . The radiators mounting
arrangement is to be indicated by the Bidder in his Bid.
m) Cooling fan support shall be of adequate strength to avoid
bending etc.
n) The mounting arrangement of cooling fans shall be subject to
drawing approval from MPPTCL.
15.2 Cooling Equipment Control (ONAN/ONAF Cooling)
a) Automatic operation control (switching in and out) of fans
shall be provided (with temperature change) from contacts of
winding temperature indicator. The Bidder shall recommend
the setting of WTI for automatic change over of cooler
control from ONAN to ONAF. The setting shall be such that
hunting i.e. frequent start stop operations for small
temperature difference do not occur.
b) Suitable manual control facility for cooler fans shall be
provided.
c) Selector switches and push buttons, shall also be provided in
the cooler control to disconnect the automatic control and
start/stop the fans manually.
15.3 Indicating devices
- Fan ON , Fan OFF
- Cooling system on automatic control.
- Cooling system on manual.
- Selector switch in auto or manual for cooler.
- A.C. auxiliary cooler supply auto change over.
- Cooler supply failure for main /standby.
- Cooling fan failure for each fan.
- Control supply failure for main and standby.
One potential free initiating contact for all the above indications shall be

wired independently to the terminal block of cooler control cabinet exclusively


for purchasers use.
16.0 LOCAL OLTC CONTROL CABINET, COOLER CONTROL CABINET
& REMOTE TAP CHANGER CONTROL PANEL
a) Each three phase transformer unit shall be provided with local
OLTC control cabinet, cooler control cabinet OR fan control
cubicle (FCC) and RTCC panel. The total height of RTCC
panel shall be 2250mm to match with the height of other
control & relay panels. Local OLTC control cabinet shall be
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 36 of 105

mounted on the transformer. The thickness of front panel,


door frame etc. shall be 3mm (10 SWG),while doors &
side panels may be 2 mm (14 SWG) and gland plate shall be of
minimum thickness 4 mm.
b) The cooler control cabinet or FCC shall not be mounted
directly on transformer tank .Please note that FCC shall be
grouted away from the main tank thus the length of capillary
tubes of all oil and winding temperature indicating meter
shall be sufficient to connect OTI and WTI meters in the
FCC. The cooler cabinet shall have all necessary devices
meant for cooler control and local temp. indicators. All the
contacts of various protective devices mounted on the
transformer shall also be wired up to the terminal Board in
the cooler control cabinet. All the secondary terminals of the
bushing CT's shall also be wired upto the terminal Board at
the cooler control cabinet.
(c) The cooler control cabinet shall have two(2) sections. One
section shall have the control equipment exclusively meant
for cooler control. The other section shall house the
temperature indicators, aux. CT's and the terminal Boards
meant for termination of various alarm and trip contacts.
Alternatively the two sections may be provided as two
separate panels depending on the standard practices of the
Bidder.
d) The cooler control cabinet, Local OLTC cabinet and RTCC
Panel shall be provided with non disconnecting stud type
terminal blocks. Each of the terminal blocks in the above
panels should have 20% spare terminals exclusively for
purchasers use. All the necessary terminals for remote
connection to purchasers panel shall be wired upto the cooler
control cabinet. Necessary shorting of terminals shall be
done at the cooler control cabinet, local OLTC cabinet and
remote OLTC panel. All the CT secondary terminals in the
cooler control cabinet shall have provision for short
circuiting to avoid CT open circuit while it is not in use.
e) The local OLTC control cabinet shall house all necessary
devices meant for OLTC control and indication.
f) Following cabling are specifically excluded from the scope of
the Bidder. However, interconnection drawings for the same
are to be submitted by the Bidder.
i) Cabling between Remote OLTC Panel to Cooler Control
Cabinet.
ii) Cabling between Remote OLTC panel to Local OLTC

Cabinet.
iii) Cabling between Remote OLTC to Purchaser's Panel.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 37 of 105

iv) Cabling between Cooler Control Cabinet to Purchaser's


Panel.
v) Cabling between Local OLTC Cabinet to Purchaser's Panel.
16.1 The degree of protection shall be IP-55 in accordance with IS2147.
16.2 The temperature indicators shall be so mounted that the
dials are not above 1600mm from ground level. Glazed door of suitable
size shall be provided for convenience of reading.
16.3 A space heater and cubicle lighting with ON-OFF switch shall be
provided.
16.4 Terminal Blocks
a) The terminal blocks to be provided shall be fully enclosed
with removable covers and made of moulded, non
inflammable plastic material with block and barriers moulded
integrally .Such block shall have washer and binding screws for
external circuit wire connections, a white marking strip for
circuit identification and moulded plastic cover. All
terminals shall be clearly marked with identification
numbers or letters to facilitate connection to external wiring.
b) All internal wiring to be connected to the external equipment
shall terminate on terminal blocks, preferably vertically
mounted on the side of each panel. The terminal blocks shall
be 1100 V grade and have 10 amps continuous rating,
moulded piece, complete with insulated barriers, nondisconnecting
stud type terminals, washers, nuts and lock
nuts. Terminal block design shall include a white fiber marking
strip with clear plastic, slip-on/clip-on terminal cover.
Markings on the terminal strips shall correspond to wire
number and terminal numbers on the wiring diagrams.
c) Terminal blocks for current transformer secondary leads
shall be provided with test links and isolating facilities. Also
current transformer secondary leads shall be provided with
short circuiting and earthing facilities.
d) Unless otherwise specified, terminal blocks shall be
suitable for connecting the following conductors on each
side.
For all circuits except current transformer circuits minimum of
two nos. 2.5 mm2 copper.
For all CT circuits minimum of four nos. 4.0 mm2 copper.
e) There shall be a minimum edge to edge clearance of 250
mm between the first row of terminal blocks and the
associated cable gland plate. Also the clearance between two
rows of terminal blocks shall be a minimum of 150 mm.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 38 of 105

f) Arrangement of the terminal block assemblies and the wiring


channel within the enclosure shall be such that a row of
terminal blocks is run parallel and in close proximity along
each side of the wiring duct to provide for convenient
attachment of internal panel wiring. The side of the
terminal block opposite the wiring duct shall be reserved for

the owner's external cable connection. All adjacent terminal


blocks shall also share this field wiring corridor. A steel strip
shall be connected between adjacent terminal block rows at
450mm intervals for support of incoming cables.
g) The number and sizes of the owner's multi core incoming
cable will be furnished to the successful Bidder.
16.5 One Cooler Control Cabinet and OLTC local control cabinet shall be
tested for IP-55 protection in accordance with IS-2147.
16.6 The gaskets shall be of neoprene rubber.
17.0 PAINTING
17.1 It has been observed that certain units received in the past
by us are not having good quality painting on inside & out side and
with passage of time peeling of flakes of paint takes place. In view of
this the Bidders are requested to furnish in a separate sheet painting
procedure adopted by them for internal & external surfaces of the
tank. This is an essential requirement and details should be confirmed
by the Bidders in their offer. The internal and external surfaces including
oil filled chambers and structural steel work to be painted shall be shot or
sand blasted to remove all rust and scale of foreign adhering matter or
grease. All steel surfaces in contact with insulating oil shall be painted with
two coats of heat resistant, oil insulating varnish.
17.2 All steel surfaces exposed to weather shall be given a primary
coat of zinc chromate, second coat of oil and weather resistant varnish of
a colour distinct from primary and final two coats of glossy oil and Epoxy light
gray paint in accordance with shade no.631 of IS-5.For each transformer oil
paints should be obtained from same source to ensure compatibility & proper
finish.
17.3 All paints shall be carefully selected to withstand extremes of
weather. The paint shall not scale off or crinkle or be removed by abrasion
due to normal handling. The process of painting should be clearly described.
17.4 The minimum thickness of each coat of outside painting of tank
shall be 20 microns and the total thickness shall be minimum 80 microns.
17.5 Bolts & Nuts :All bolts and nuts exposed to weather shall be hot
dipped galvanised/cadmium plated.
18.0 WIRING & CABLING
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 39 of 105

(a) All external cabling will be carried out by the purchaser based
on wiring diagram & interconnection schedule to be supplied
by the Bidder . Cable box/sealing end shall be suitable for
following types of cables :i) POWER SUPPLY 0.4 KV : 1100volts grade PVC
insulated armoured
aluminum cable .
ii) CONTROL CABLE : 1100volts grade PVC
insulated 7/0.737mm
stranded armoured copper
cable .
Size of the Purchasers cable will be intimated to the
successful Bidder after detailed engineering.
(b) Compression type cable glands shall be provided for
termination of power and control cables.
(c) All controls, alarms, indicating and relaying devices
provided with the transformer shall be wired upto the

terminal blocks inside the Cooler Control Cabinet.


(d) All devices and terminal blocks with the Cooler Control
Cabinet shall be clearly identified by symbols corresponding to
those used on applicable schematic or wiring diagrams.
(e) Not more than 2 wires shall be connected to one terminal.
Each terminal shall be suitable for connecting two 7/0.737mm
stranded copper conductors from each side.
(f) All internal wiring shall be securely supported, neatly
arranged, readily accessible and connected to equipment
terminals and terminal blocks.
(g) Engraved code identification plastic ferrules marked to
correspond with schematic diagrams shall be fitted at both
ends of wires. Ferrules shall fit tightly on wires and shall not
fall off when the wire is disconnected from terminal block.
(h) The schematic diagrams of circuitry shall be available in the
respective cabinets (local OLTC control cabinet , local fan
control cubicle and RTCC panel). The diagrams shall be
mounted on the inner side of door of cubicle/cabinets. The
arrangements shall be such that it is not be possible to remove
the diagram from its place and diagrams are long lasting
(engraved type).
19.0 TERMINAL CONNECTORS:
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 40 of 105

19.1 Terminal connectors for HV & LV side bushings shall be suitable


for single/double Zebra ACSR (28.62mm) conductor and suitable for
horizontal and /or vertical take off arrangement i.e. universal type.
19.2 Bushing terminals shall be provided with terminal connectors of
approved type and size for connection to external parts. Terminal connectors
offered must have been successfully type tested as per IS-5561.
19.3 All terminal connectors shall be manufactured out of gravity dye
casting process only and shall be free from blow holes, surface blisters,
cracks and cavities. All sharp edges and corners shall be blurred and
rounded off. The aluminum alloy castings, if used, shall conform to
relevant IS.
19.4 No part of the clamp shall be less than 12mm thickness.
19.5 All bolts, nuts and washers shall be of Hot Dip Galvanised.
19.6 For bimetallic clamps , bimetallic strip of not less than 2 mm
thickness shall be provided.
19.7 Flexible connectors, if provided shall be made from tinned copper
sheets.
19.8 Size of terminal (bushing stud)/conductor ( ACSR Zebra ) for which
the clamp is designed and also rated current under site conditions shall be
embossed/ punched on each part of the clamp, except hardware.
19.9 All current carrying parts shall be designed and manufactured to
have minimum contact resistance.
19.10 Clamps shall be designed corona controlled.
19.11 The nominal current rating and short time current rating of terminal
connectors shall match the corresponding rating of respective bushings.
20.0 INSULATING OIL REQUIRED FOR TRANSFORMERS
20.1 Transformer oil shall be supplied by the Bidder. The offered Price
of transformers therefore, should include first filling of oil( including
wastage) & 10% extra of that quantity. The quantity of oil for first filling
including wastage and 10% extra of that quantity should be indicated by the

Bidder in kilo-liters and in kg. The design of the transformer shall be based
on the characteristic of EHV transformer oil as per relevant IS.
20.2 Although oil for the transformer is included in the scope of supply,
but it may be noted that the transformer shall be supplied duly N2 gas filled
with suitable arrangement to ensure that the pressure of gas is regularly
maintained during transit and upto the date of filling of oil. For this
purpose, necessary gas cylinders with regulator shall be supplied on non
returnable basis. Additional gas cylinders required recouping and
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 41 of 105

maintaining of positive Nitrogen pressure upto filling of oil should be


supplied by the manufacturer of Transformers and the offered price
should take into account this requirement.
20.3 The quality of the oil supplied with transformer shall conform to the
oil parameters specified in this clause. No inhibitors shall be used in the oil.
The oil samples of transformer will be drawn for the oil used at factory &
site as follows.
i. Prior to filling
ii. Before and after heat run test / pre-commissioning test.
iii. Before energizing.
All tests as per IS:335 (latest revision) shall be conducted on oil
samples.
20.4 Sufficient quantity of oil necessary for first filling of main tank,
coolers, radiators and conservators etc. upto the proper level plus anticipated
quantity of wastage of oil during first filling shall be supplied in tankers. Please
note, wastage means quantity of oil absorbed during initial filling at works for
testing. In addition to the oil needed for first filling, 10% extra quantity of oil
for topping up in future, shall be supplied in non-returnable containers
suitable for outdoor storage. Therefore, total quantity of oil required for first
filling shall be measured at works at the time of testing on unit subjected to
heat run test.
20.5 The supplier shall dispatch the transformer in an atmosphere of
pressurised Nitrogen. In this case, necessary arrangement shall be ensured
by the supplier to take care of pressure drop of nitrogen during transit and
storage till completion of oil filling during erection. A gas pressure testing
valve with necessary pressure gauge and adapter valve shall be provided.
20.6 The supplier shall warrant and confirm that oil to be used for the
transformer testing at Works & oil to be supplied for the transformer is free
from Polychlorinated Biphenyls (PVB/PCB). The transformer oil to be used
and supplied by the bidder for first filling at site shall be new oil of EHV GradeI having technical specification mentioned hereunder . Hence Oil to be used
by the manufacturers at factory for the purpose of testing at their
works shall be of similar or better quality having parameters matching
with the parameters specified in the specification. Specific approval of
oil test results of oil proposed to be used for testing of transformer in
factory shall be obtained by the manufacturer from the purchaser
before first filling in the unit. MPPTCL shall not accept any other oil for
testing purposes having lower parameters than those specified in the
Bid. Bidders should specifically confirm this requirement in their offer.
Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 42 of 105

Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
1. Appearance The oil shall be clear
and transparent and
free from suspended
matter or sediment
A representative
sample of oil shall be
examined in a 100
mm thick layer at
ambient
temperature.
2. Density at 29.5oC
(maximum)
0.89 gm/cm3
IS:1448
3. Kinematics viscosity at
27oC (miximum).
27 CST IS:1448
4. Interfacial tension at
27oC (minimum).
0.04 N/m
IS:6104
5. Flashpoint Pensky
Marten (closed)
(minimum).
140oC IS:1448
6. Pour point. (maximum) -6 oC IS:1448
7. Neutralization value
(Total acidity maximum)
0.01 mg KOH/g
IS:335 Appendix `A
8. Corrosive Sulphur Non-corrosive IS:335 Appendix `B
9. Electric strength
(breakdown voltage)
Minimum.
a. New unfiltered oil (as
received condition).
b. After filtration
40 KV (rms)
60 KV (rms)
IS:6792
10. Dielectric dissipation
factor (tan delta) at
90oc Maximum.
0.002 IS:6262
11. Specific resistance
(resistivity)
a. at 90oC Minimum.
b. at 27oC Minimum.
100x1012 ohm.cm
1500X1012 ohm.cm

IS:6103
12. Oxidation stability
a. Neutralisation value
after oxidation,
maximum.
b. Total sludge, after
oxidation Maximum
0.20 mg KOH/g
0.02 percent by
weight
13. Presence of oxidation
inhibitor
The oil shall not
contain antioxidant
inhibitors .
IS:335
Appendix `D
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 43 of 105

Sl.
No
Characteristics Requirement Method of Test
1. 2. 3. 4.
14. SK value 6% maximum IS:335
15. Water content,
maximum.
10 ppm IS:2362
16. Ageing characteristics
after accelerated ageing
(open Breaker method
with copper catalyst)
a) Resistivity
i. 27oc
ii. 90oc
b) Tan delta at 90oc
c) Total acidity
d) Sludge content
by weight
2.5x1012 ohm.cm
(min.)
0.2x1012 ohm.cm
(min.)
0.15 (max.)
0.05 mg
KOH/gm(max.)
0.05% (max)
As per ASTM-D
1934/ IS 12177
17. Oil sample taken from
the transformer after
the completion of site
processing and tested in
approved manner shall
have the following

values before
commissioning of the
transformer.
i. Break down
strength
ii. Moisture content
iii. Resistivity at 90oc
minimum
iv. Interfacial Tension
at 27oc
v. Dielectric
dissipation factor at
90 oC
Minimum 70 KV
withstand
Maximum of 10 ppm
35x1012 ohm.cm
(min)
0.04 N/M (min)
0.002 (max.)
Tested in accordance
with IS :335
18 N-dm analysis
CA%
CN%
CP%
4 6%
40-43%
51-54%
20.7 AIR CELL : Our technical specification calls for supply of power
transformers with air cell type oil preservation system of PRONOL, make
only. It is obligatory on the part of the Bidders to clearly submit complete
constructional and technical details of sealing arrangement, duly supported
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 44 of 105

with technical details, pamphlets and dimensional drawings. While


furnishing details for the above sealing arrangement the Bidders must
confirm clearly that the size and capacity of sealing arrangement is
adequate for the transformer and for the quantity of oil required for the
transformers. Necessary calculation/documentary proof shall be furnished.
20.8 Air cell type oil preservation system included with each transformer
shall ensure as under:
(a) The air inlet of COPS (Conservator Oil preservation System)
shall be properly fitted on the conservator for leak proof
arrangement to ensure that the air does not come in contact
with oil under any circumstances.
(b) The size and capacity of the COPS (Conservator Oil
preservation System) shall be selected to suit the design of
Conservator and to ensure proper operation for the quantity of
oil in the unit with the proper allowances. The COPS shall be of
reputed make, proven design and of established performance.
Details in this regard are to be submitted with the offer by the
Bidder for verification . The Bidder is required to submit
calculation with bid to prove adequacy of air cell & its size.

(c) The Bidder shall clearly indicate in the manual the


procedure for installation of COPS and precautions to be
taken at the time of first oil filling under vacuum in the
transformer.
20.9 THERMOSYPHON FILTER : Atleast two Nos. of Thermosyphon filter
arrangement each of capacity 1/5th of the total oil flow in the cooler shall be
provided with rigid support (i.e., slotted one not acceptable) on the
transformer along with connecting piping, isolating valves at either end, drain
plug shall be mounted on the transformer. It will have Alumina trap and will
be designed in such a way that 1/5th of the forced oil circulation passes
through it. The quantity of absorbent will be 0.25% of the total weight of total
oil in the transformer, cooler, conservator etc. Spare alumina for one time
replacement shall be also supplied by the supplier. The location of
Thermosyphon filter should be in such a way that same do not interfere with
any of the existing equipments. The Thermosyphon filter shall be located at
diagonally opposite points of transformer. The connecting pipes of
Thermosyphon filter to tank shall be provided with flexible couplings. It may
be noted that rigid supports shall be provided for thermosyphon filter i.e.,
slotted type of fixing arrangement is not acceptable.
20.10 Silicagel breather : Minimum 2 nos. dehydrating filter Silica Gel
Breathers each of 100% breathing capacity are required and the same shall
be provided. Size of breather and its pipe connection is to be indicated.
However, each breather of minimum capacity of 8 Kg having its pipe
connection of minimum size of one inch dia shall be preferable. Suitable
arrangement for parallel mounting of breathers shall be made for connecting
both the Silica Gel Breather to the main conservator.The passage of air should
be through dual filter & Silica Gel. Silica Gel shall be isolated from atmosphere
Volume-II, Part-4
MPPTCL/TECH/PROC/06/JULY13 Page 45 of 105

by an oil seal. Adequate supports are required to be provided for pipe


connection to avoid any swing in air.
The capacity of silicagel breather shall be adequate to ensure supply of dry air
only for the volumetric expansion/contraction of oil keeping in view the total
quantity of oil in the unit. The container of the breather shall be made of
metal with glass enclosure along its periphery to ensure that the transparency
(to verify the colour of dehydrating agent) is maintained during operation
directly under sunlight (ultra violet rays) for long life. The quantity of the
dehydrating agent shall be sufficient keeping in view the climatic condition
specified and that the breather will be maintained generally two times in a
year. This applies to all the breathers provided with the transformer.
20.11 TRANSPORTATION CONFIGURATION OF POWER
TRANSFORMER : In order to conduct low voltage field testing on power
transformers before unloading/commissioning at site to determine the
internal condition, the transformer shall be transported with :
a) Small bushing (12 KV) may be installed on the bushing cover plate to
represent the actual bushing.
b) Winding leads may be routed, secured and electrically isolated from the
tank walls and active part.
c) Temporarily tests leads may be used to connect the winding leads by
the small bushings (which will be removed before erection of the main
bushings).
The details of arrangement for transport configuration of Power Transformer (
which shall be adopted by Manufacturer) shall be submitted by the
Manufacturer to the Purchaser for approval. The price quoted by the Bidder

should take into account this requirement.

Das könnte Ihnen auch gefallen