1 Input data
Anchor type and diameter:
Material:
B500B
ETA 12/0084
Issued I Valid:
8/8/2012 | 12/23/2016
Proof:
Design method Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation:
eb = 0 mm (no stand-off); t = 25 mm
Anchor plate:
Profile:
Base material:
cracked concrete, C30/37, fc = 37.00 N/mm2; h = 10000 mm, Temp. short/long: 30/40 C
Installation:
Reinforcement:
no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
with longitudinal edge reinforcement d >= 12 + close mesh (stirrups, hangers) s <=
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
11/2/2015
2
Shear force y
5.000
5.000
5.000
5.000
x
Tension
3
Capacity [kN]
79.286
Utilization bN [%]
17
Status
OK
33.911
49.711
69
OK
33.911
37.087
92
OK
33.911
92.741
37
OK
Steel Strength*
Splitting failure**
* anchor having the highest loading
gM,s
1.400
NRd,s [kN]
79.286
NSd [kN]
13.196
A0p,N [mm2]
136533
2
tRk,ucr,25 [N/mm ]
10.00
scr,Np [mm]
370
ccr,Np [mm]
185
yc
1.000
2
tRk,cr [N/mm ]
5.50
k
2.300
yg,Np
1.749
yg,Np
1.251
ec1,N [mm]
0
yec1,Np
1.000
ec2,N [mm]
85
yec2,Np
0.686
ys,Np
0.883
N0Rk,p [kN]
69.115
NRk,p [kN]
74.567
gM,p
1.500
NRd,p [kN]
49.711
NSd [kN]
33.911
cmin [mm]
113
yre,Np
1.000
A0c,N [mm2]
562500
ccr,N [mm]
375
scr,N [mm]
750
ec1,N [mm]
0
yec1,N
1.000
ec2,N [mm]
85
yec2,N
0.816
N0Rk,c [kN]
173.118
gM,c
1.500
NRd,c [kN]
37.087
NSd [kN]
33.911
Ac,N [mm2]
223740
A0c,N [mm2]
250000
ccr,sp [mm]
250
scr,sp [mm]
500
yh,sp
1.438
ec1,N [mm]
0
yec1,N
1.000
ec2,N [mm]
85
yec2,N
0.747
ys,N
0.836
N0Rk,c [kN]
173.118
gM,sp
1.500
NRd,sp [kN]
92.741
NSd [kN]
33.911
ys,N
0.790
yre,N
1.000
k1
7.200
yre,N
1.000
k1
7.200
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
3
11/2/2015
Capacity [kN]
36.667
Utilization bV [%]
14
Status
OK
N/A
N/A
N/A
N/A
Pryout Strength**
20.224
90.894
23
OK
20.224
147.252
14
OK
VRd,s [kN]
36.667
gM,s
1.500
VSd [kN]
5.056
A0c,N [mm2]
562500
ccr,N [mm]
375
scr,N [mm]
750
k-factor
2.000
ec1,V [mm]
0
yec1,N
1.000
ec2,V [mm]
0
yec2,N
1.000
ys,N
0.790
N0Rk,c [kN]
173.118
gM,c,p
1.500
VRd,c1 [kN]
90.894
VSd [kN]
20.224
a
0.149
b
0.068
yec,V
1.000
yre,N
1.000
dnom [mm]
16.0
k1
1.700
c1 [mm]
113
Ac,V [mm2]
140516
A0c,V [mm2]
57461
ys,V
1.000
yh,V
1.000
ya,V
2.367
ec,V [mm]
0
V0Rk,c [kN]
27.256
gM,c
1.500
VRd,c [kN]
147.252
VSd [kN]
20.224
yre,V
1.400
bV
0.222
a
1.000
Status
OK
9.775 [kN]
dN
0.117 [mm]
VSk
3.745 [kN]
dV
0.150 [mm]
dNV
0.190 [mm]
9.775 [kN]
dN
0.171 [mm]
VSk
3.745 [kN]
dV
0.225 [mm]
dNV
0.282 [mm]
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
4
11/2/2015
7 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
The design method ETAG (filled holes) assumes that no hole clearance between the anchors and the fixture is present. This can
be
achieved by filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Bore hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
Characteristic bond resistances depend on short- and long-term temperatures.
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means.
The compliance with current standards (e.g. EC3) is the responsibility of the user
An SLS-check is not performed for SOFA and has to be provided by the user!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
5
11/2/2015
8 Installation data
Anchor type and diameter: HIT-HY 200-R + Rebar 16mm
Installation torque: 0.000 kNm
Hole diameter in the base material: 20 mm
Hole depth in the base material: 250 mm
Minimum thickness of the base material: 290 mm
Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush
Setting
Dispenser including cassette and mixer
For deep installations, a piston plug is
necessary
Dynamic set
Torque wrench
100
55
100
300
125
240
125
300
55
100
100
x
0
0
0
0
y
245
120
-120
-245
c-x
113
113
113
113
c+x
113
113
113
113
c-y
-
c+y
-
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
6
11/2/2015
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan