TRANSFORMER, 40/50/60 MVA, 132/34.5KV

Date: 10.12.2014

TECHNICAL DATA SCHEDULE


TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM

DESCRIPTION

UNITS

REQUIRED

1.0

Manufacturer

1.1

Type

Three-phase with
2 windings

1.2

Class

2.0

Rated data and characteristics

2.1

Rated power:

- primary/secondary

Power Xmer

ONAN/ONAF/ONAF

kV
kV

132
34.5

132
34.5

- manufacturer

MR

Huaming

- model
- type
- on-load tap changer location

M III 500
CFVV

2.3

Rated voltage
- HV winding
- LV winding

40/50/60
ONAN/ONAF1/
ONAF2

Tap changer:

HV neutral
132 kV
+4 x 1.25%
-12 x 1.25%

- regulating range
%
- rating

2.5

Frequency

2.6

Connection of the three-phase windings


(group of vectors IEC 76)

2.7

Rated current at ONAF rated power and


rated voltage tap:
- HV winding
- LV winding

Hz

50

YNd11

YNd11

A
A

263
1004.1

262.43@60M
1004.1

Base: rated
voltage and 60
MVA

Page 1 of 6

HV neutral
132 kv
+4x1.25%
-12x1.25%
Rated power
on all taps

Rated power on
all taps

A
A

Short circuit impedance

CM III 500 Y
High speed,
transition resistor

No-load current through:


- HV winding
- LV winding

2.9

Three-phase with
2 windings

40/50/60

Cooling

2.8

T & R (I) LTD

MVA

2.2

2.4

GUARANTEED

50

0.5% of Rated
full load
current
(Approx)

Base: rated
voltage and 60
MVA

TECHNICAL DATA SCHEDULE


TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM

2.9.1

DESCRIPTION

UNITS

REQUIRED

10

Direct impedance at nominal voltage tap:


- HV/LV

2.9.2

%
%

7.5
10

- HV winding

kA RMS
kA (peak)

2.9 (Approx)
7.4(Approx)

- LV winding

kA RMS
kA (peak)

- tertiary winding

kA RMS
kA (peak)

NA

- pre-fault voltage

p.u.

1.05

1.05

Zero sequence impedance at nominal


voltage tap
- HV / LV

2.10

7.5
10

Transformer capacity to withstand external


short circuits:

2.11.1

Short circuit duration

2.11.2

Symmetrical short circuit current withstand


during the indicated period and
asymmetrical short circuit withstand:

2.12

9.0%(Approx)

Tolerance to be applied to the short circuit


impedance, in terms of % of the
guaranteed value on:
- nominal voltage tap
- other taps

2.11

9.25%(Approx)
10.3%(Approx)

Direct impedance at maximum voltage tap:


- HV/LV

2.9.4

10% (Sub. To
Tolerance)@60
MVA

Direct impedance at minimum voltage tap:


- HV/LV

2.9.3

GUARANTEED

6.06(Approx)
15.5(Approx)

Guaranteed losses

2.12.1

No-load losses at rated voltage and


frequency, with rated voltage tap

kW

32.0 (Max)

2.12.2

No-load losses at 110% of the rated


voltage, at rated frequency and rated
voltage tap

kW

45.0 (Approx)

2.12.3

No-load losses capitalized value

US $/kW

3000

2.12.4

Tolerance to be applied to no-load losses


(in % of the guaranteed value)

10

Page 2 of 6

3000
0%, Max Loss
Specified

TECHNICAL DATA SCHEDULE


TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM

2.12.5

DESCRIPTION

UNITS

REQUIRED

kW
kW
kW

On-load losses at rated voltage and


frequency, with rated voltage tap and
ONAN rating:
- HV winding
- LV winding
tertiary winding

GUARANTEED

112 @ 40MVA
247.5@60
MVA
NA

2.12.6

On-load losses capitalized value

2.12.7

2.12.8
2.13

US $/kW

1080

Tolerance to be applied to total losses (in


%of the guaranteed value) for all the
windings

10

Auxiliaries consumption at second stage of


cooling (ONAF/ONAF)

kW

kV
kV

145
36

145
36

2.14.1

kV RMS
kV RMS
kV RMS
kV RMS

230
70
38
2.0

230
70
38
2.0

kV (peak)
kV (peak)
kV (peak)

550
145
95

550
145
95

60
65

60
65

Short time power frequency withstand:

Basic impulse level:


- HV winding - line terminal
- LV winding - line terminal
- neutral point

2.15

Temperature rise limits at maximum power


output at ONAN and ONAF ratings and at
lowest voltage tap and corresponding
voltage:
o

- top oil at ambient temperature


- average copper at ambient temperature
2.16

4 KW

Rated insulation level:

- HV winding - line terminal


- LV winding - line terminal
- neutral
- control wiring
2.14.2

0%, Max Loss


Specified

Highest voltage for equipment:


- HV winding
- LV winding

2.14

1080

C
C

Permissible overload in emergency cases:


- permanent permissible overload based
on highest winding temperature which
o
exceeds by 5 C the guaranteed limit

MVA

- permanent permissible over voltage


based on the maximum top oil
o
temperature which exceeds by 5 C the
guaranteed limit at rated power (in % of
the rated voltage)

Page 3 of 6

As per
60076-7

IEC-

As per
60076-7

IEC-

TECHNICAL DATA SCHEDULE


TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM

2.17

DESCRIPTION

UNITS

Oil:

REQUIRED

PCB prohibited

- manufacturer
- type
- data sheet attached

2.18
2.18.1

As per IEC-296

kV
A
kA RMS

145
-

kV(peak)
kV RMS
mm

650
275
TBA
As per pollution
level of site

650
275

kV
A

36

170

HV bushings:

- short circuit withstand


- basic insulation level
- power frequency withstand for 1 minute
- connectors for
- leakage distance

2.18.3

PCB provided
Apar/Savita or
equi.

Bushings

- class
- manufacturer
- type designation
- rated current

2.18.2

GUARANTEED

145
ABB/ALSTOM/
CGL or equi.
800 A
25 times the
rated current for
2 sec

3625 mm

LV bushings:
- class
- manufacturer
- type designation
- rated current
- short circuit withstand

KA RMS

36
-

- basic insulation level

kV (peak)

170

- power frequency withstand for 1 minute


- connectors for
- leakage distance

kV RMS
mm

70
TBA
As per pollution
level of site

kV
-

24
-

- type designation
- rated current
- short circuit withstand

A
kA RMS

- basic insulation level

kV (peak)

125

125

- power frequency withstand for 1 minute


- connectors for

kV RMS

50

50
-

GENESIS/CJI or

equi.
Porcelain type
2000 A
25 times the
rated current for
2 sec.

70
900 mm

Neutral bushings:
- class
- manufacturer

Page 4 of 6

52
GENESIS/CJI/
or equi.
Porcelain type
1000 A
25 times the
rated current foe
2 sec

TECHNICAL DATA SCHEDULE


TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM

DESCRIPTION

- leakage distance
2.19
2.19.1

2.19.4

2.19.6

mm

tesla
tesla

1.6 T
1.68 T

tesla
tesla

1.6 T
1.68 T

Maximum flux density in the yokes at:

Maximum current density at ONAN rated


power and rated voltage tap:
- HV winding

A/mm

< 3.5 at ONAF2


A/mm2

- LV winding

A/mm2

< 3.5 at ONAF2


2
A/mm

ohms
ohms

- with unity power factor:


. LV side
. TV side

%
%

0.50@ 40 MVA
NA

- with 0.9 power factor (lagging):


. LV side
. TV side

%
%

3.33 @ 40MVA
NA

- with 0.8 power factor (lagging):


. LV side
. TV side

%
%

4.36 @ 40 MVA
NA

kA
kA

0.5 % of rated
current
(Exciting
current)
Core

Winding resistance:
- HV winding
- LV winding

2.19.5

GUARANTEED

1300 mm

Maximum flux density in the columns at:

- rated voltage
- 105% of the rated voltage
2.19.3

REQUIRED

As per pollution
level at site

Design data:

- rated voltage
- 105% of the rated voltage
2.19.2

UNITS

0.61 ohm/ph.
(Approx)
0.095 ohm/ph.
(Approx)

Voltage regulation at ONAN rating and


rated voltage tap (in % of the rated
voltage):

Primary exciting current, LV side:


- at 0.01 second
- at 0.1 second

2.19.7

Core type (core or shell)

2.19.8

Winding conductor

Copper

Copper

2.20

Audible noise level


%
dB(A)
dB(A)

105
75 max
78 max

105
75 max
78 max

2500 max

- Voltage in percent of rated value


- ONAN rating
- ONAF maximum rating
2.21

Radio Interference Voltage at 0.5 MHz

Page 5 of 6

2500 max

TECHNICAL DATA SCHEDULE


TRANSFORMER 40/50/60 MVA, 132/34.5kV

ITEM

DESCRIPTION

UNITS

REQUIRED

GUARANTEED

kg

77000(approx)

kg
kg
kg
kg

17000(approx)
40000(approx)
20000(approx)
8250(approx)

as per IEC 694


3.0

Weights and dimensions

3.1

Total weight of transformer, equipped for


service

3.2

Weight:
- oil
- core and coil assembling
- tank and accessories
- net copper
- net core steel

kg

3.3

Maximum shipping weight (heaviest item)

kg

3.4

Height from foundation to:


mm
mm
mm

mm

- highest point of HV bushing


- highest point of tank
- highest point of conservator tank
- highest point of lifting hook to remove
core and coil assembly
3.5

28000(approx)

Outline dimensions:
- length
- width
o

3.6

Layout drawing n

3.7

Maximum shipping dimensions of tank:


- outside height
- outside width
- outside length

Page 6 of 6

WITH
INSULATION

mm
mm

To be enclosed
with bid

mm
mm
mm

70000(approx)
Oil Filled

As per
Attached
GA Drawing