BITZER Output data

Created on : 2015-10-26 14:43:39

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

2 / 11

Table of content
Project survey............................................................................................................................................................ 3
Compressor Selection: Semi-hermetic Screw Compressors HS............................................................................... 4
Technical Data: HSN7461-70.................................................................................................................................... 5
Semi-hermetic Screw Compressors HS.................................................................................................................... 6
Oil cooler, air cooled.................................................................................................................................................. 7
Technical Data: OL600.............................................................................................................................................. 8
Oil separator.............................................................................................................................................................. 9
Technical Data: OA1954.......................................................................................................................................... 10
Oil separator............................................................................................................................................................ 11

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

3 / 11

Project survey
Selected compressors
Semi-hermetic Screw Compressors HS

1x

HSN7461-70

1x
1x

OL600
OA1954

Chosen accessory
Oil cooler, air cooled
Oil separator

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

4 / 11

Compressor Selection: Semi-hermetic Screw Compressors HS


Input Values
Compressor model
Refrigerant
Reference temperature
Evaporating SST
Condensing SDT
Liq. subc. (in condenser)
Auto. subcooling
Suct. gas superheat
Operating mode
Power supply
Useful superheat
Additional cooling
Max. discharge gas temp.

HSN7461-70
R404A
Dew point temp.
-40,00 C
45,0 C
0K
Auto
10,00 K
Economizer
400V-3-50Hz
100%
Automatic
80,0 C

Result
Compressor
Capacity steps
Cooling capacity
Cooling capacity *
Evaporator capacity
Power input
Current (400V)
Voltage range
Condenser Capacity
COP/EER
COP/EER *
Mass flow LP
Mass flow HP
Operating mode
Liquid temp. (sc)
Mass flow ECO
sub cooler load
sat. ECO Temp.
ECO pressure
Oil volume flow
Cooling method
Oil cooler outlet
Oil cooler load
Discharge gas temp. w/o cooling

HSN7461- 70-40P
100%
48,4 kW
50,0 kW
48,4 kW
55,6 kW
88,9 A
380-415V
84,9 kW
0,87
0,89
1192 kg/h
1919 kg/h
Economizer
3,48 C
727 kg/h
20,9 kW
-6,52 C
4,89 bar(a)
2,10 m/h
External
62,1 C
19,31 kW
109,3 C

Additional cooling/ Limitations (see Limits + T. Data)!


*According to EN12900 (10K suction gas superheat, liquid subcooling in Economiser with 5K temperature difference)

Application Limits ECO


Legend

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

5 / 11

Technical Data: HSN7461- 70


Dimensions and Connections

Technical Data
Technical Data
Displacement (2900 RPM 50 Hz)
Displacement (3500 RPM 60 Hz)
Weight
Max. pressure (LP/HP)
Connection suction line
Connection discharge line
Adapter/shut-off valve for ECO
Oil type R22
Oil type R134a/R404A/R507A
Motor data
Motor voltage (more on request)
Max operating current
Starting current (Rotor locked)
Max. Power input
Extent of delivery (Standard)
Discharge gas temperature sensor
Start unloading
Oil flow control
Motor protection
Suction shut-off valve
Capacity control
Enclosure class
Available Options
Discharge shut-off valve
ECO connection with shut-off valve
Motor protection
Sound measurement
Sound power level (-35C / 40C)
Sound pressure level @ 1m (-35C / 40C)

220 m/h
266 m/h
310 kg
19 / 28 bar
76 mm - 3 1/8''
54 mm - 2 1/8''
22 mm - 7/8'' (Option)
B150SH, B100 (Option)
BSE170 (Option)
380-415V PW-3-50Hz
124.0 A
290.0 A D / 485.0 A DD
75,0 kW
Standard
Standard
SE-B2 (Standard)
SE-E1 (Standard), INT69VSY-II(Standard for 660-690V)
Standard
100-75-50% (Standard)
IP54
Option
Option
SE-C1 (Option)
88,5 dB(A)
80,5 dB(A)

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

6 / 11

Semi-hermetic Screw Compressors HS


HSK = Application for air-conditioning and medium temperature cooling
HSN = Application for low temperature cooling
Notes regarding application limits (see Limits):
- Ranges are valid for standard operation and at full-load conditions.
- With high pressure conditions, part-load operation is partly limited
(see application limits in applications manual SH-100)
- With Economizer operation the maximum admissible evaporation temperature
is shifted by 10 K downward (otherwise there is a danger of excessive
compression and overload of the motor because of a higher mass flow).
At pull-down conditions from higher evaporation temperatures, the ECO injection
must remain closed until the evaporation temperature is below the maximum
admissible value and a stable operation is achieved (e.g. control of the ECO
solenoid valve by means of a low pressure cut-out). The use of the ECO-system
with higher evaporation temperatures requires individual consultation with Bitzer.
HS 64/74:
- Capacity control with ECO operation at the same time is limited to one single
regulating step (CR 75 %). At CR 50 % the ECO injection should be closed.
- Combined operation (ECO + CR 50 %) is possible under certain conditions,
control and system design, however, require individual consultation with Bitzer.
Data for sound emission:
Data are based on 50Hz application (IP-units 60Hz) and R404A.
Sound pressure level: values are based on open air test sites with semi-spherical sound emissions at 1 meter distance.
For further information see Technical Information "Sound Data".
Legend of connection positions according to "Dimensions":
1 High pressure connection (HP)
2 Low pressure connection (LP)
3 Discharge gas temperature sensor
4 Economiser / liquid injection
5 Oil injection
6 Oil pressure connection
7 Oil drain plug (motor housing)
8 Threaded hole for foot fixation
9 Threaded hole for pipe support (ECO and LI line)

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

Oil cooler, air cooled


Input Values
Common
Ambient temp.
Operating point

Yes
32C
Auto

Operating Points
to [C]
tc [C]

-40
45

Result
Compressor:
Recommendation:
Selection
Recommended operating point:
Selected operating point:
Number
Oil cooler capacity
Oil cooler load
Max. oil volume flow
Oil volume flow load

(all)
OL600
OL600
A
A
1
27,8 kW
69,4 %
7,4 m/h
28,5 %

7 / 11

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

Technical Data: OL600


Dimensions and Connections

Technical Data
Technical Data
Weight
Total width
Total depth
Total height
Receiver volume refrigerant
Fans: Number
Voltage (more on request)
Current / Power consumption of each fan
Air flow condenser 50Hz
Oil inlet
Oil outlet
*According PED 97/23/EC

84,0 kg
1393mm
590mm
727mm
14,0 dm
2
230V/400V-3-50Hz (Standard)
2,4 A 1,38 A / 660 W
13000 m/h
28 mm - 1 1/8''
28 mm - 1 1/8''
Standard

8 / 11

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

Oil separator
Input Values
Common
Operating point

Yes
Auto

Operating Points
to [C]
tc [C]

-40
45

Result
Compressor:
Recommendation:
Selection
Recommended operating point:
Selected operating point:
Number
Max. HP mass flow
Mass flow load
Max. oil volume flow
Oil volume flow load

(all)
OA1954
OA1954
A
A
1
2230 kg/h
86,05 %
3,10 m/h
67,74 %

#1: Selection for direct expansion systems. Flooded systems require individual selection.

9 / 11

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

Technical Data: OA1954


Dimensions and Connections

Technical Data
Technical Data
Weight
Total width
Total depth
Total height
Oil charge
Receiver volume refrigerant
Max. no. of compressor
Refrigerant inlet
Refrigerant outlet
Oil outlet
Max. pressure
Max. Operating Temperature
Crankcase heater
Oil level switch
Connection for pressure relief valve
*According PED 97/23/EC

45 kg
376 mm
450 mm
764 mm
18 l
40 l
2
54 mm - 2 1/8''
42 mm - 1 5/8''
22 mm - 7/8''
28 bar
120C
1x140 W
Standard
1 1/4'' - 12 UNF
Standard

10 / 11

HSN7461-70

BITZER Software v6.4.1 rev1210

2015-10-26 / All data subject to change.

Oil separator
Connection positions
1 Refrigerant inlet
2 Refrigerant outlet
3 Oil outlet
4 Oil fill connection
5 Service connection
6 Oil thermostat connection
7 Oil heater connection
8 Oil level switch connection
9 Connection for pressure relief valve
10 Oil outlet (secondary stage)
11 Service flange for filter cartridges (filter of the secondary stage)
Dimensions can show tolerances
according to EN ISO 13920-B.