Beruflich Dokumente
Kultur Dokumente
Group Members:
Dustin Harbottle
Taylor Choy
Kevin Ko
Shane McMonagle
Agaton Pasion
University of Hawaii at Manoa
Department of Civil and Environmental Engineering
CEE 320L Fluid Mechanics
Lab Date: October 27, 2011
Report Submitted Date: November 3, 2011
Abstract
The objective of this lab was to determine the calibration rate for a Venturi
flow meter. In this experiment, the flow rate through the pipe and the pressure
difference through the Venturi pipe were measured many times for different flow
rates and pressures to help find a calibration factor for the Venturi flow meter.
The experimental result for the calibration factor was .101 cfs, which came out
to be close to the theoretical prediction of .101 cfs. This means that even with
possibilities for error, the experiment closely reflected the theoretical use of
using a flow meter in the field.
II Introduction
i.
Background
The Venturi meter creates a restricted flow in a pipe, the velocity of the fluid
increases as the cross sectional area decreases, with the static pressure
correspondingly decreasing. A Venturi meter helps to measure flow rate by
measuring a pressure difference between a converging-diverging flow passage. The
main advantage of the Venturi meter is that it has a lower head loss then an orifice
meter. An equation for the Venturi effect may be derived from a combination of
Bernoulli's principle and the continuity equation.
ii.
iii.
Theory
According to the laws governing fluid dynamics, a fluid's velocity must increase
as it passes through a constriction to satisfy the principle of continuity, while its
pressure must decrease to satisfy the principle of conservation of mechanical
energy. Thus any gain in kinetic energy a fluid may gain due to its increased velocity
through a constriction is negated by a drop in pressure.
iv.
Objective
The objective of this lab was to calibrate a Venturi meter by measuring flow rate
along with pressure drop in the Venturi meter. Measuring the two different
quantities allows for the calculation of the calibration factor, which will make the
calculations for the Venturi meter accurate.
IV Procedures
A Venturi meter is installed in a length of pipe from a sump pump to a weighing
tank with a dump valve. The Venturi meter is, in turn, connected to a pressure
gauge. The pump was turned on and a gate valve just downstream of the pump
was opened. Water flowed through the piping system from the sump pump,
through the Venturi meter and to the weighing tank. The initial pressure gauge
reading, in psi, was recorded. The dump valve on the tank was closed and, as water
collected in the tank, the initial and final weight of the water in the tank was
recorded, along with the time interval, using the stopwatches. The water in the
tank was then released via the dump valve, and the gate valve was then closed a
certain amount to cause a pressure difference, p. This new pressure reading was
recorded and the dump valve on the tank was again closed, allowing water to
collect in the tank. The initial and final weight, along with the time interval, was
again recorded for the new pressure reading. The procedure was repeated for a
total of ten trials.
V Equations/Theory
Q=
Q=CK p
K= A 2
Venturi Constant:
[ ( )]
C=
Error Propagation:
C=C
Derivation of C:
2g
D2
1
D1
Q
K p
Correction Factor:
Relative Error:
w
t
W t ( p )
+ +
W
t
2 p
C
C
Q=CK P C=f ( W , t , P ) =
W
tK P
C=
|(
C=
W
W
W +
t +
)
|
(
)
|
|
tK P
K P t
( 2 tK ( P ) )( P)
[(
C
W
=
C
tK P
3
2
C=C
W t ( P)
+ +
W
t
2 P
VI Experimental Results
Trial
t1 (s)
t2 (s)
tavg (s)
1
2
10.41
11.88
10.75
12.41
3
4
5
13.1
14.26
15.13
13.22
14.28
15.34
17.44
17.69
18.04
18.81
20.5
20.57
9
10
22.15
28.23
22.69
29.81
10.58
12.14
5
13.16
14.27
15.23
5
17.56
5
18.42
5
20.53
5
22.42
29.02
W
(lbs)
100
100
P
(psi)
5.5
4.3
100
100
100
3.4
3
2.5
100
1.9
100
1.65
100
1.3
100
100
1.05
0.5
Trial
No.
1
Re
0.94
0.93
0.95
0.94
0.97
0.96
0.99
8
9
1.00
1.02
231430.7
7
201608.6
9
186059.0
9
171586.3
8
160717.9
2
139398.6
7
132892.1
3
119237.28
109212.2
10
Averag
e
1.14
0.98
0
84374.14
C vs Re
1.2
1
0.8
C
f(x) = - 0x + 1.15
R = 0.68
0.6
0.4
0.2
0
50000
100000
150000
200000
250000
Re
Q vs p
0.10
1.000
1.00
f(x)0.100
= 0.02x + 0.05
R = 0.98
0.010
p
10.00
Q= ( p)
=10 yintercept
( 5.5 ) (12 )2
=slope of graph
.425
1
=
.147
100
Q=0 .008614
v.
Human error must be taken into account mainly with the individuals collecting
the time data. Discrepancies in the times may have occurred due the each
individuals reaction time, having to watch the scale until 100 lbs. of water was
obtained and then stop the watch. Assuming the water flow was constant
throughout the experiment, human error could also be caused due to each person
taking times at different weights with a possibility that the water flow could have
been different at those weights. One or both persons could have taken the time to
early and not allow the flow to become steady enough.
discussion for error. The experimental value Q of .101 cfs was then compared to the
Q value from the log-log plot, which was .147 cfs, which was relatively close to the
theoretical value calculated.
If this experiment were to be considered more critically, more trials should be
made so there is a decrease in the impact of errors. Another way to achieve more
accurate results would be to use a more accurate way of recording the time at
which the weight started to increase, such as video recording which would allow
frame by frame viewing, and use the same weight difference throughout the entire
experiment.
10
IX References
Crowe, C.T., Elger, D.F., Williams, B.C., & Roberson, J.A. 2009. Engineering Fluid
Mechanics, 9th Edition. Hoboken, New Jersey: John Wiley & Sons, Inc.
X Appendices
Appendix I Equations and Sample Calculations
Q=
W
100
ft 3
=
=0.151
t ( 62.4 ) (10.58)
s
Q=C K p
K= A 2
C=
= (0.94) (0.00572)
[ ( )]
2g
D
1 2
D1
1
4 12
( )
(5.50 ) (12)2
2(32.2)
[ ( )]
1
(62.4) 1
2
= 0.151
=0.00572
Q
0.151
=
=0.9 4
K p 0.00572 5.50 ( 12 )2
C=C
] [
W t ( p )
1
0.01
14.4
+ +
=.941
+
+
=.018 9
W
t
2 p
100 10.58 2(792)
11
ft
s