Beruflich Dokumente
Kultur Dokumente
Current Shunt
Resistors
Tokens Shunt Resistors (FL)
for high-current applications aid precision measurement.
Preview
Current shunt resistors are low resistance precision
resistors used to measure AC or DC electrical
currents by the voltage drop those currents create
across the resistance. Sometimes called an
ammeter shunt, it is a type of current sensor.
A wide range of precision shunts, designed for
use with kilowatt-hour meters and other
high-current applications where a high level
of accuracy is required, is now available from
Token Electronics.
The interchangeable shunts (FL) are used to
multiply the measuring range of measuring
instrument and designed for PCB and busbar mounting, are manufactured from electron beam welded copper and
manganin, and have low temperature coefficients. Featuring low inductance values, shunts FL series can handle
permanent currents of up to 10000A at voltage 75 mV.
FLQ-54 type shunt is made of precision alloy board. Its copper terminals spot welded by silver alloy ensure
extremely high electric capability. The construction provides a kind of excellent stability and high overloaded
ability non-inductive resistor, applied widely as current limited, current balance or sampling sense in
communication system, electric equipment and auto-controlling electrical circuit.
The FL Series is available in bulk packaging and is RoHS compliant and lead free. For non-standard technical
requirements and special applications, please contact us with your specific needs.
Power Rating : Watts (W) = Current (I2) x Resistance Value (R)
- The heat produced is power measured in Watts (W).
- In practice current shunts are often rated to be used continuously at only 2/3 of their rated current.
- Because current shunts are resistors and dissipate heat from the current flowing through them, they get hot.
- Since that heat can change their resistance and even permanently damage the shunt, current shunts are often
given a power rating or a derating factor.
Calculate Current : Current (I) = Voltage (V) / Resistance Value (R)
- Then knowing the resistance of the current shunt you can calculate the current using Ohms law.
- By inserting a current shunt into a circuit whose current you want to measure your can find the current by
measuring the voltage drop across the shunt.
Version 2010
http://www.token.com.tw/
rfq token.com.tw
01 of 03
TOKEN
d1
d
S
d2
d
2-5
b
d1
c
5A ~ 50A
75A ~ 100A
Dimensions (Unit: mm)
Rating
Current (A)
5
10
15
20
30
50
75
100
120
120
120
120
120
120
104
104
100
100
100
100
100
100
85
85
20
20
20
20
20
20
22
22
02 of 03
c1
c2
d1
d2
15
15
15
15
15
15
22
22
5
5
5
5
5
5
10
10
30
30
30
30
30
30
40
40
42
42
42
42
42
42
53
53
60
60
60
60
60
60
http://www.token.com.tw/
High Current
Bolt (mm)-PC
(Option)
M5x6-2
M5x6-2
M5x6-2
M5x6-2
M5x6-2
M5x6-2
M8x35-2
M8x35-2
rfq token.com.tw
Shunt Voltage
Bolt (mm)-PC
(Option)
M5x6-2
Version 2010
TOKEN
d1
d1
S H
S H
d2
d2
c1
c
a
150A ~ 600A
750A ~ 1000A
Dimensions (Unit: mm)
Rating
Current (A)
150
200
250
300
400
500
600
750
1000
116
116
126
126
126
126
126
126
126
85
85
100
100
100
100
100
100
100
22
22
26
26
38
45
62
76
95
Version 2010
c1
50
50
c2
d1
d2
22
22
22
22
22
22
22
22
22
6
6
6
6
6
6
6
6
6
30
30
40
40
40
40
40
40
40
39
39
49
49
49
49
49
49
49
54
54
64
64
64
64
64
64
64
http://www.token.com.tw/
High Current
Bolt (mm)-PC
(Option)
M8x35-2
M8x35-2
M10x35-2
M10x35-2
M10x35-2
M10x35-2
M10x35-2
M10x35-4
M10x35-4
rfq token.com.tw
Shunt Voltage
Bolt (mm)-PC
(Option)
M5x6-2
03 of 03
TOKEN
S H
d2
c1
c1
b
c2
c1
c1
c
1500A ~ 3000A
Rating
Current (A)
1500
2000
2500
3000
4000
5000
6000
7500
10000
02 of 03
4000A ~ 10000A
c
160
160
160
160
160
220
220
220
220
b
95
95
110
145
195
195
210
320
400
c1
50
50
50
2-50
2-50
2-50
2-50
3-50
3-50
c2
55
55
80
2-60
2-90
H
22
22
100
100
100
150
150
150
150
S
6
6
13
13
13
18
18
18
18
http://www.token.com.tw/
d
40
40
40
40
40
40
40
40
40
d1
52
52
52
52
52
52
52
52
52
d2
64
64
84
84
84
88
88
88
88
High Current
Bolt (mm)-PC
(Option)
Shunt Voltage
Bolt (mm)-PC
(Option)
M12x60-4
M12x60-4
M12x60-4
M12x60-6
M16x80-8
M16x80-8
M16x80-8
M16x80-12
M16x80-12
M5x6-2
rfq token.com.tw
Version 2010
TOKEN
2-5
10
B
C
L
30A ~ 75A
Voltage (mV)
75mV
75mV
75mV
30A
50A
75A
H
21
30
30
FL-13-A TYPE
H
C1
Bolts (Option)
C
L
Voltage
(mV)
Rating
Current (A)
75mV
75mV
75mV
75mV
75mV
75mV
75mV
75mV
100A
200A
300A
400A
500A
600A
750A
1000A
Version 2010
L
130
130
130
130
130
130
130
130
http://www.token.com.tw/
H
30
30
30
30
30
30
30
30
C
85
85
100
100
100
100
100
100
rfq token.com.tw
03 of 03
TOKEN
H max.
L1
L1
1.4
L
FLQ54-C
Type
FLQ54-A
FLQ54-B
FLQ54-C
1.5
5.8
B
7.7
FLQ54-A
FLQ54-B
H max.
37
60
32
L1
3
5
3
Style of terminal
6
6
2
FLQ54-A
FLQ54-A
FLQ54-A
FLQ54-B
FLQ54-B
FLQ54-B
FLQ54-C
FLQ54-C
30
50
60
60
75
100
30
60
02 of 03
http://www.token.com.tw/
1.6667
1.0000
0.8333
0.8333
0.6667
0.5000
1.5000
0.7500
0.5
rfq token.com.tw
-55 ~ +85
Temperature
Coefficient
(ppm/C)
25
Version 2010
TOKEN
Test Items
Voltage Drop
Accuracy Class
Over Rating Capacity
Ambient Conditions
Specification
50mV, 60mV, 75mV, 100mV.
0.5% for 5 ~ 4000 A; 1% for 5000 ~ 6000 A
120% of rated current for 2 hours.
Temperature: -40~+60C; relative humidity: 95% 35C
How to Order
FL-2
5A
50mV
F
D
1%
0.5%
Package-Code
Code
Package-Code
Bulk
http://www.token.com.tw/
rfq token.com.tw
03 of 03