Shutdown SIS
Previous Screen
Product: GENERATOR SET
Model: 3516B GENERATOR SET ZAR00703
Configuration: 3516B Generator Set ZAR00001-UP
i04500469
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 05/10/2011
Page 2 of 4
Unless other instructions are provided, perform maintenance and perform repairs under the following
conditions:
The starting system is disabled.
The engine is stopped.
The generator does not pose an electrical shock hazard.
The generator is disconnected from the load.
When Required
Battery - Recycle
Battery or Battery Cable - Disconnect
Fuel System - Prime
Fuel System Primary Filter/Water Separator - Drain
Generator - Dry
Generator Bearing - Lubricate
Generator Set - Test
Generator Set Alignment - Check
Generator Winding - Test
Varistor - Test
Zinc Rods - Inspect/Replace
Every Week
Air Inlet Filter - Check
Air Starting Motor Lubricator Oil Level - Check
Air Tank Moisture and Sediment - Drain
Annunciator Panel - Inspect
Automatic Start/Stop - Inspect
Battery Charger - Check
Battery Electrolyte Level - Check
Cooling System Coolant Level - Check
Electrical Connections - Check
Engine Air Cleaner Service Indicator - Inspect
Engine Air Precleaner - Clean
Engine Oil Level - Check
Fuel Tank Water and Sediment - Drain
Generator - Inspect
Generator Bearing Temperature - Test/Record
Generator Lead - Check
Generator Load - Check
Jacket Water Heater - Check
Power Factor - Check
Space Heater - Check
Standby Generator Set Maintenance Recommendations
Stator Winding Temperature - Test
Voltage and Frequency - Check
Walk-Around Inspection
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 05/10/2011
Page 3 of 4
Every 6 Months
Cooling System Coolant Sample (Level 1) - Obtain
Every Year
Air Shutoff - Test
Air Starting Motor Lubricator Bowl - Clean
Alternator - Inspect
Belts - Inspect/Adjust/Replace
Cooling System Coolant Sample (Level 2) - Obtain
Cooling System Supplemental Coolant Additive (SCA) - Test/Add
Crankshaft Vibration Damper - Inspect
Engine - Clean
Engine Air Cleaner Element (Dual Element) - Clean/Replace
Engine Air Cleaner Element (Single Element) - Clean/Replace
Engine Crankcase Breather - Clean
Engine Mounts - Check
Engine Oil Sample - Obtain
Engine Oil and Filter - Change
Engine Protective Devices - Check
Engine Valve Lash - Inspect/Adjust
Fan Drive Bearing - Lubricate
Fuel Injector - Inspect/Adjust
Fuel System Primary Filter (Water Separator) Element - Replace
Fuel System Secondary Filter - Replace
Generator Set Vibration - Test/Record
Generator Winding Insulation - Test
Hoses and Clamps - Inspect/Replace
Prelube Pump - Inspect
Radiator - Clean
Rotating Rectifier - Check
Rotating Rectifier - Inspect/Test
Speed Sensor - Clean/Inspect
Starting Motor - Inspect
Stator Lead - Check
Varistor - Inspect
Water Pump - Inspect
Every 3 Years
Air Shutoff Damper - Remove/Check
Batteries - Replace
Cooling System Coolant (DEAC) - Change
Cooling System Coolant Extender (ELC) - Add
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 05/10/2011
Page 4 of 4
Every 6 Years
Cooling System Coolant (ELC) - Change
Commissioning
Generator Set Alignment - Check
Generator Set Vibration - Test/Record
Copyright 1993 - 2011 Caterpillar Inc.