Shutdown SIS
Previous Screen
Product: GENERATOR SET
Model: 3516B GENERATOR SET ZAR00703
Configuration: 3516B Generator Set ZAR00001-UP

Operation and Maintenance Manual


3500 Generator Sets
Media Number -SEBU7789-06

Publication Date -01/08/2011

Date Updated -08/08/2011

i04500469

Maintenance Interval Schedule - Standby


SMCS - 1000; 4450; 7500
Ensure that all safety information, warnings and instructions are read and understood before any
operation or any maintenance procedures are performed.
An authorized operator may perform the maintenance items with daily intervals. An authorized
operator may perform the maintenance items with intervals of every week. The maintenance that is
recommended for all other maintenance intervals must be performed by an authorized service
technician or by your Caterpillar dealer.
The user is responsible for the performance of all maintenance which includes the following items:
performing all adjustments, using proper lubricants, fluids, and filters and replacing old components
with new components due to normal wear and aging .
Failure to adhere to proper maintenance intervals and procedures may result in diminished
performance of the product and/or accelerated wear of components.
Before each consecutive interval is performed, all maintenance from the previous intervals must be
performed.
Choose the interval that occurs first in order to determine the correct maintenance interval: fuel
consumption, service hours and calendar time . Products that operate in severe operating conditions
may require more frequent maintenance.
All of the following will affect the oil change interval: operating conditions, fuel type, oil type and
size of the oil sump . Scheduled oil sampling analyzes used oil in order to determine if the oil change
interval is suitable for your specific engine.
Refer to this Operation and Maintenance Manual, "Engine Oil and Filter - Change" in order to
determine the oil change interval that is suitable for your specific engine.
To determine the maintenance intervals for the overhauls, refer to this Operation and Maintenance
Manual, "Maintenance Recommendations" .

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 05/10/2011

3516B Generator Set ZAR00001-UP(SEBP4058 - 09) - Documentation

Page 2 of 4

Unless other instructions are provided, perform maintenance and perform repairs under the following
conditions:
The starting system is disabled.
The engine is stopped.
The generator does not pose an electrical shock hazard.
The generator is disconnected from the load.

When Required
Battery - Recycle
Battery or Battery Cable - Disconnect
Fuel System - Prime
Fuel System Primary Filter/Water Separator - Drain
Generator - Dry
Generator Bearing - Lubricate
Generator Set - Test
Generator Set Alignment - Check
Generator Winding - Test
Varistor - Test
Zinc Rods - Inspect/Replace

Every Week
Air Inlet Filter - Check
Air Starting Motor Lubricator Oil Level - Check
Air Tank Moisture and Sediment - Drain
Annunciator Panel - Inspect
Automatic Start/Stop - Inspect
Battery Charger - Check
Battery Electrolyte Level - Check
Cooling System Coolant Level - Check
Electrical Connections - Check
Engine Air Cleaner Service Indicator - Inspect
Engine Air Precleaner - Clean
Engine Oil Level - Check
Fuel Tank Water and Sediment - Drain
Generator - Inspect
Generator Bearing Temperature - Test/Record
Generator Lead - Check
Generator Load - Check
Jacket Water Heater - Check
Power Factor - Check
Space Heater - Check
Standby Generator Set Maintenance Recommendations
Stator Winding Temperature - Test
Voltage and Frequency - Check
Walk-Around Inspection

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 05/10/2011

3516B Generator Set ZAR00001-UP(SEBP4058 - 09) - Documentation

Page 3 of 4

Every 50 Service Hours


Zinc Rods - Inspect/Replace

Every 6 Months
Cooling System Coolant Sample (Level 1) - Obtain

Every Year
Air Shutoff - Test
Air Starting Motor Lubricator Bowl - Clean
Alternator - Inspect
Belts - Inspect/Adjust/Replace
Cooling System Coolant Sample (Level 2) - Obtain
Cooling System Supplemental Coolant Additive (SCA) - Test/Add
Crankshaft Vibration Damper - Inspect
Engine - Clean
Engine Air Cleaner Element (Dual Element) - Clean/Replace
Engine Air Cleaner Element (Single Element) - Clean/Replace
Engine Crankcase Breather - Clean
Engine Mounts - Check
Engine Oil Sample - Obtain
Engine Oil and Filter - Change
Engine Protective Devices - Check
Engine Valve Lash - Inspect/Adjust
Fan Drive Bearing - Lubricate
Fuel Injector - Inspect/Adjust
Fuel System Primary Filter (Water Separator) Element - Replace
Fuel System Secondary Filter - Replace
Generator Set Vibration - Test/Record
Generator Winding Insulation - Test
Hoses and Clamps - Inspect/Replace
Prelube Pump - Inspect
Radiator - Clean
Rotating Rectifier - Check
Rotating Rectifier - Inspect/Test
Speed Sensor - Clean/Inspect
Starting Motor - Inspect
Stator Lead - Check
Varistor - Inspect
Water Pump - Inspect

Every 3 Years
Air Shutoff Damper - Remove/Check
Batteries - Replace
Cooling System Coolant (DEAC) - Change
Cooling System Coolant Extender (ELC) - Add

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 05/10/2011

3516B Generator Set ZAR00001-UP(SEBP4058 - 09) - Documentation

Page 4 of 4

Cooling System Water Temperature Regulator - Replace


Turbocharger - Inspect

Every 6 Years
Cooling System Coolant (ELC) - Change

Commissioning
Generator Set Alignment - Check
Generator Set Vibration - Test/Record