Beruflich Dokumente
Kultur Dokumente
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc.
1021 Main Campus Drive
Raleigh, NC 27606, USA
Toll Free: 1-800-HELP-365, menu option #8
ABB Inc.
3450 Harvester Road
Burlington, ON L7N 3W5, Canada
Toll Free: 1-800-HELP-365, menu option #8
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure would
create a risk for harm to property or persons (including but not limited to personal
injuries or death) shall be the sole responsibility of the person or entity applying the
equipment, and those so responsible are hereby requested to ensure that all measures
are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standards EN 50263 and EN 60255-26 for the EMC directive, and with the product
standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series and
ANSI C37.90.
Table of contents
Table of contents
Section 1
Introduction..........................................................................23
Introduction to the technical reference manual.......................................23
About the complete set of manuals for an IED..................................23
About the technical reference manual...............................................24
This manual.......................................................................................25
Introduction...................................................................................25
Principle of operation....................................................................25
Input and output signals...............................................................29
Function block..............................................................................29
Setting parameters.......................................................................30
Technical data..............................................................................30
Intended audience.............................................................................30
Revision notes...................................................................................30
Section 2
Analog inputs.......................................................................31
Introduction.............................................................................................31
Operation principle..................................................................................31
Function block.........................................................................................32
Setting parameters.................................................................................33
Section 3
Local HMI............................................................................35
Human machine interface ......................................................................35
Medium size graphic HMI.......................................................................38
Medium..............................................................................................38
Design................................................................................................39
Keypad....................................................................................................41
LED.........................................................................................................42
Introduction........................................................................................42
Status indication LEDs......................................................................42
Indication LEDs.................................................................................43
Local HMI related functions....................................................................44
Introduction........................................................................................44
General setting parameters...............................................................44
Status LEDs.......................................................................................44
Design..........................................................................................44
Function block..............................................................................45
1
Table of contents
Section 4
2
Technical reference manual
Table of contents
Function block...................................................................................83
Input and output signals....................................................................83
Setting parameters............................................................................83
Test mode functionality TEST.................................................................83
Introduction........................................................................................83
Principle of operation.........................................................................84
Function block...................................................................................86
Input and output signals....................................................................86
Setting parameters............................................................................86
IED identifiers.........................................................................................87
Introduction........................................................................................87
Setting parameters............................................................................87
Product information.................................................................................87
Introduction........................................................................................87
Setting parameters............................................................................88
Factory defined settings....................................................................88
Signal matrix for binary inputs SMBI.......................................................88
Introduction........................................................................................88
Principle of operation.........................................................................89
Function block...................................................................................89
Input and output signals....................................................................89
Signal matrix for binary outputs SMBO ..................................................90
Introduction........................................................................................90
Principle of operation.........................................................................90
Function block...................................................................................91
Input and output signals....................................................................91
Signal matrix for mA inputs SMMI..........................................................91
Introduction........................................................................................91
Principle of operation.........................................................................92
Function block...................................................................................92
Input and output signals....................................................................92
Signal matrix for analog inputs SMAI......................................................93
Introduction........................................................................................93
Principle of operation.........................................................................93
Frequency values..............................................................................93
Function block...................................................................................95
Input and output signals....................................................................95
Setting parameters............................................................................96
Summation block 3 phase 3PHSUM......................................................98
Introduction........................................................................................98
3
Technical reference manual
Table of contents
Principle of operation.........................................................................98
Function block...................................................................................99
Input and output signals....................................................................99
Setting parameters............................................................................99
Authority status ATHSTAT....................................................................100
Introduction......................................................................................100
Principle of operation.......................................................................100
Function block.................................................................................101
Output signals..................................................................................101
Setting parameters..........................................................................101
Denial of service DOS..........................................................................101
Introduction......................................................................................101
Principle of operation.......................................................................101
Function blocks................................................................................102
Signals.............................................................................................102
Settings............................................................................................103
Section 5
Differential protection........................................................105
Busbar differential protection ...............................................................105
Introduction......................................................................................107
Available versions.......................................................................107
Principle of operation.......................................................................108
Differential protection.......................................................................108
Differential Zone A or B BZNTPDIF, BZNSPDIF (87)......................108
Open CT detection.....................................................................110
Differential protection supervision..............................................111
Explanation of Zone function block.............................................111
Function block............................................................................117
Input and output signals.............................................................118
Setting parameters.....................................................................120
Calculation principles.......................................................................126
General.......................................................................................126
Open CT detection.....................................................................133
Check zone BCZTPDIF, BCZSPDIF (87B)......................................135
Introduction.................................................................................135
Explanation of Check zone function block..................................136
Function block............................................................................138
Input and output signals.............................................................138
Setting parameters.....................................................................139
Zone selection.................................................................................139
4
Technical reference manual
Table of contents
Section 6
Current protection..............................................................163
Four step phase overcurrent protection OC4PTOC (51/67).................163
Introduction......................................................................................163
Principle of operation.......................................................................163
Second harmonic blocking element.................................................168
Function block.................................................................................170
Input and output signals..................................................................170
Setting parameters..........................................................................172
Technical data.................................................................................178
Four step single phase overcurrent protection PH4SPTOC (51)..........178
Introduction......................................................................................179
Principle of operation.......................................................................179
Function block.................................................................................181
Input and output signals..................................................................181
Setting parameters..........................................................................182
Technical data.................................................................................187
5
Table of contents
Table of contents
Section 7
Voltage protection.............................................................233
Two step undervoltage protection UV2PTUV (27)................................233
Introduction......................................................................................233
Principle of operation.......................................................................233
Measurement principle...............................................................234
Time delay..................................................................................234
Blocking......................................................................................240
Design........................................................................................241
Function block.................................................................................243
Input and output signals..................................................................243
Setting parameters..........................................................................244
Technical data.................................................................................246
Two step overvoltage protection OV2PTOV (59).................................247
Introduction......................................................................................247
Principle of operation.......................................................................247
Measurement principle...............................................................248
Time delay..................................................................................249
Blocking......................................................................................254
Design........................................................................................254
Function block.................................................................................256
Input and output signals..................................................................256
Setting parameters..........................................................................257
Technical data.................................................................................259
Two step residual overvoltage protection ROV2PTOV (59N)...............260
Introduction......................................................................................260
Principle of operation.......................................................................260
7
Table of contents
Measurement principle...............................................................261
Time delay..................................................................................261
Blocking......................................................................................266
Design........................................................................................266
Function block.................................................................................267
Input and output signals..................................................................268
Setting parameters..........................................................................268
Technical data.................................................................................270
Voltage differential protection VDCPTOV (60).....................................271
Introduction......................................................................................271
Principle of operation.......................................................................271
Function block.................................................................................272
Input and output signals..................................................................273
Setting parameters..........................................................................273
Technical data.................................................................................274
Loss of voltage check LOVPTUV (27)..................................................274
Introduction......................................................................................274
Principle of operation.......................................................................275
Function block.................................................................................276
Input and output signals..................................................................277
Setting parameters..........................................................................277
Technical data.................................................................................278
Section 8
Frequency protection.........................................................279
Underfrequency protection SAPTUF (81).............................................279
Principle of operation.......................................................................279
Measurement principle...............................................................279
Time delay..................................................................................280
Voltage dependent time delay....................................................280
Blocking......................................................................................282
Design........................................................................................282
Function block.................................................................................283
Input and output signals..................................................................283
Setting parameters..........................................................................283
Technical data.................................................................................284
Overfrequency protection SAPTOF (81)...............................................285
Introduction......................................................................................285
Principle of operation.......................................................................286
Measurement principle...............................................................286
Time delay..................................................................................286
8
Technical reference manual
Table of contents
Blocking......................................................................................286
Design........................................................................................287
Technical data.................................................................................288
Rate-of-change frequency protection SAPFRC (81)............................288
Introduction......................................................................................288
Principle of operation.......................................................................288
Measurement principle...............................................................289
Time delay..................................................................................289
Blocking......................................................................................290
Design........................................................................................290
Function block.................................................................................291
Input and output signals..................................................................292
Setting parameters..........................................................................292
Technical data.................................................................................293
Section 9
Multipurpose protection.....................................................295
General current and voltage protection CVGAPC................................295
Introduction......................................................................................295
Principle of operation.......................................................................295
Measured quantities within CVGAPC.........................................295
Base quantities for CVGAPC function........................................298
Built-in overcurrent protection steps...........................................298
Built-in undercurrent protection steps.........................................304
Built-in overvoltage protection steps...........................................305
Built-in undervoltage protection steps........................................305
Logic diagram.............................................................................305
Function block.................................................................................311
Input and output signals..................................................................312
Setting parameters..........................................................................313
Technical data.................................................................................321
Table of contents
Setting parameters..........................................................................337
Technical data.................................................................................338
Section 11 Control...............................................................................339
Autorecloser SMBRREC (79)...............................................................339
Introduction......................................................................................339
Principle of operation.......................................................................339
Logic Diagrams...........................................................................339
Auto-reclosing operation Disabled and Enabled........................339
Auto-reclosing mode selection...................................................340
Initiate auto-reclosing and conditions for initiation of a
reclosing cycle............................................................................340
Control of the auto-reclosing open time for shot 1......................342
Long trip signal...........................................................................342
Time sequence diagrams...........................................................349
Function block.................................................................................354
Input and output signals..................................................................354
Setting parameters..........................................................................356
Technical data.................................................................................358
Apparatus control APC.........................................................................358
Introduction......................................................................................358
Principle of operation.......................................................................359
Error handling..................................................................................359
Bay control QCBAY.........................................................................361
Introduction.................................................................................361
Principle of operation..................................................................361
Function block............................................................................363
Input and output signals.............................................................363
Setting parameters.....................................................................364
Local/Remote switch LOCREM, LOCREMCTRL............................364
Introduction.................................................................................364
Principle of operation..................................................................364
Function block............................................................................366
Input and output signals.............................................................366
Setting parameters.....................................................................367
Switch controller SCSWI..................................................................368
Introduction.................................................................................368
Principle of operation..................................................................368
Function block............................................................................373
Input and output signals.............................................................373
10
Technical reference manual
Table of contents
Setting parameters.....................................................................375
Circuit breaker SXCBR....................................................................375
Introduction.................................................................................375
Principle of operation..................................................................376
Function block............................................................................380
Input and output signals.............................................................380
Setting parameters.....................................................................381
Circuit switch SXSWI.......................................................................381
Introduction.................................................................................381
Principle of operation..................................................................382
Function block............................................................................386
Input and output signals.............................................................386
Setting parameters.....................................................................387
Bay reserve QCRSV........................................................................387
Introduction.................................................................................387
Principle of operation..................................................................388
Function block............................................................................390
Input and output signals.............................................................391
Setting parameters.....................................................................392
Reservation input RESIN.................................................................392
Introduction.................................................................................392
Principle of operation..................................................................392
Function block............................................................................394
Input and output signals.............................................................395
Setting parameters.....................................................................396
Interlocking (3)......................................................................................396
Introduction......................................................................................396
Principle of operation.......................................................................397
Logical node for interlocking SCILO (3)...........................................400
Introduction.................................................................................400
Logic diagram.............................................................................401
Function block............................................................................401
Input and output signals.............................................................401
Interlocking for busbar grounding switch BB_ES (3).......................402
Introduction.................................................................................402
Function block............................................................................402
Logic diagram.............................................................................403
Input and output signals.............................................................403
Interlocking for bus-section breaker A1A2_BS (3)...........................403
Introduction.................................................................................403
11
Technical reference manual
Table of contents
Function block............................................................................404
Logic diagram.............................................................................405
Input and output signals.............................................................406
Interlocking for bus-section disconnector A1A2_DC (3)..................408
Introduction.................................................................................408
Function block............................................................................408
Logic diagram.............................................................................409
Input and output signals.............................................................410
Interlocking for bus-coupler bay ABC_BC (3)..................................410
Introduction.................................................................................411
Function block............................................................................412
Logic diagram.............................................................................413
Input and output signals.............................................................415
Interlocking for breaker-and-a-half diameter BH (3)........................418
Introduction.................................................................................418
Function blocks...........................................................................420
Logic diagrams...........................................................................422
Input and output signals.............................................................427
Interlocking for double CB bay DB (3).............................................431
Introduction.................................................................................432
Function block............................................................................433
Logic diagrams...........................................................................435
Input and output signals ............................................................438
Interlocking for line bay ABC_LINE (3)............................................442
Introduction.................................................................................442
Function block............................................................................444
Logic diagram.............................................................................445
Input and output signals.............................................................450
Interlocking for transformer bay AB_TRAFO (3)..............................453
Introduction.................................................................................453
Function block............................................................................454
Logic diagram.............................................................................455
Input and output signals.............................................................457
Position evaluation POS_EVAL.......................................................459
Introduction.................................................................................459
Logic diagram.............................................................................459
Function block............................................................................459
Input and output signals.............................................................459
Logic rotating switch for function selection and LHMI presentation
SLGGIO................................................................................................460
12
Technical reference manual
Table of contents
Introduction......................................................................................460
Principle of operation.......................................................................460
Functionality and behaviour .......................................................462
Graphical display........................................................................462
Function block.................................................................................464
Input and output signals..................................................................464
Setting parameters..........................................................................466
Selector mini switch VSGGIO...............................................................466
Introduction......................................................................................466
Principle of operation.......................................................................466
Function block.................................................................................467
Input and output signals..................................................................468
Setting parameters..........................................................................468
IEC61850 generic communication I/O functions DPGGIO...................468
Introduction......................................................................................469
Principle of operation.......................................................................469
Function block.................................................................................469
Input and output signals..................................................................469
Settings............................................................................................470
Single point generic control 8 signals SPC8GGIO...............................470
Introduction......................................................................................470
Principle of operation.......................................................................470
Function block.................................................................................471
Input and output signals..................................................................471
Setting parameters..........................................................................472
AutomationBits, command function for DNP3.0 AUTOBITS................472
Introduction......................................................................................473
Principle of operation.......................................................................473
Function block.................................................................................474
Input and output signals..................................................................474
Setting parameters..........................................................................475
Single command, 16 signals SINGLECMD..........................................491
Introduction......................................................................................491
Principle of operation.......................................................................491
Function block.................................................................................492
Input and output signals..................................................................492
Setting parameters..........................................................................493
Section 12 Logic..................................................................................495
Configurable logic blocks......................................................................495
13
Technical reference manual
Table of contents
Introduction......................................................................................495
Inverter function block INV..............................................................496
OR function block OR......................................................................496
AND function block AND.................................................................497
Timer function block TIMER............................................................498
Pulse timer function block PULSETIMER........................................498
Exclusive OR function block XOR...................................................499
Loop delay function block LOOPDELAY.........................................499
Set-reset with memory function block SRMEMORY.......................500
Reset-set with memory function block RSMEMORY.......................501
Controllable gate function block GATE............................................502
Settable timer function block TIMERSET........................................503
Technical data.................................................................................503
Fixed signal function block FXDSIGN...................................................504
Setting parameters..........................................................................504
Boolean 16 to Integer conversion B16I.................................................504
Introduction......................................................................................504
Operation principle..........................................................................505
Function block.................................................................................506
Input and output signals..................................................................506
Setting parameters..........................................................................507
Boolean 16 to Integer conversion with logic node representation
B16IFCVI..............................................................................................507
Introduction......................................................................................507
Operation principle..........................................................................507
Function block.................................................................................509
Input and output signals..................................................................509
Setting parameters..........................................................................510
Integer to Boolean 16 conversion IB16.................................................510
Introduction......................................................................................510
Operation principle..........................................................................510
Function block.................................................................................512
Input and output signals..................................................................512
Setting parameters..........................................................................513
Integer to Boolean 16 conversion with logic node representation
IB16FCVB.............................................................................................513
Introduction......................................................................................513
Operation principle..........................................................................513
Function block.................................................................................515
Input and output signals..................................................................515
14
Technical reference manual
Table of contents
Setting parameters..........................................................................516
Section 13 Monitoring..........................................................................517
Measurements......................................................................................517
Introduction......................................................................................518
Principle of operation.......................................................................519
Measurement supervision..........................................................519
Measurements CVMMXN...........................................................523
Phase current measurement CMMXU........................................528
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU....................................................................529
Voltage and current sequence measurements VMSQI,
CMSQI........................................................................................529
Function block.................................................................................529
Input and output signals..................................................................531
Setting parameters..........................................................................535
Technical data.................................................................................548
Event counter CNTGGIO......................................................................550
Identification....................................................................................550
Introduction......................................................................................550
Principle of operation.......................................................................551
Reporting....................................................................................551
Design........................................................................................551
Function block.................................................................................552
Input signals....................................................................................552
Setting parameters..........................................................................553
Technical data.................................................................................553
Event function EVENT..........................................................................553
Introduction......................................................................................553
Principle of operation.......................................................................553
Function block.................................................................................555
Input and output signals..................................................................555
Setting parameters..........................................................................556
Logical signal status report BINSTATREP...........................................558
Introduction......................................................................................558
Principle of operation.......................................................................559
Function block.................................................................................559
Input and output signals..................................................................560
Setting parameters..........................................................................561
Measured value expander block RANGE_XP......................................561
15
Technical reference manual
Table of contents
Introduction......................................................................................561
Principle of operation.......................................................................561
Function block.................................................................................562
Input and output signals..................................................................562
Disturbance report DRPRDRE.............................................................562
Introduction......................................................................................563
Principle of operation.......................................................................564
Function block.................................................................................572
Input and output signals..................................................................573
Setting parameters..........................................................................575
Technical data.................................................................................585
Sequential of events.............................................................................585
Introduction......................................................................................585
Principle of operation.......................................................................585
Function block.................................................................................586
Input signals....................................................................................586
Technical data.................................................................................586
Indications.............................................................................................587
Introduction......................................................................................587
Principle of operation.......................................................................587
Function block.................................................................................588
Input signals....................................................................................588
Technical data.................................................................................588
Event recorder .....................................................................................588
Introduction......................................................................................588
Principle of operation.......................................................................589
Function block.................................................................................589
Input signals....................................................................................589
Technical data.................................................................................590
Trip value recorder................................................................................590
Introduction......................................................................................590
Principle of operation.......................................................................590
Function block.................................................................................591
Input signals....................................................................................591
Technical data.................................................................................591
Disturbance recorder............................................................................591
Introduction......................................................................................591
Principle of operation.......................................................................592
Memory and storage...................................................................593
IEC 60870-5-103........................................................................594
16
Technical reference manual
Table of contents
Function block.................................................................................595
Input and output signals..................................................................595
Setting parameters..........................................................................595
Technical data.................................................................................595
Section 14 Metering............................................................................597
Pulse-counter logic PCGGIO................................................................597
Introduction......................................................................................597
Principle of operation.......................................................................597
Function block.................................................................................600
Input and output signals..................................................................600
Setting parameters..........................................................................601
Technical data.................................................................................601
Function for energy calculation and demand handling ETPMMTR......601
Introduction......................................................................................602
Principle of operation.......................................................................602
Function block.................................................................................603
Input and output signals..................................................................603
Setting parameters..........................................................................604
Table of contents
18
Technical reference manual
Table of contents
Table of contents
Introduction.................................................................................701
Design........................................................................................701
Binary input module (BIM)...............................................................703
Introduction.................................................................................703
Design........................................................................................703
Technical data............................................................................707
Binary output modules (BOM).........................................................708
Introduction.................................................................................708
Design........................................................................................708
Technical data............................................................................709
Static binary output module (SOM).................................................710
Introduction.................................................................................710
Design........................................................................................710
Technical data............................................................................712
Binary input/output module (IOM)....................................................714
Introduction.................................................................................714
Design........................................................................................714
Technical data............................................................................716
mA input module (MIM)...................................................................718
Introduction.................................................................................718
Design........................................................................................719
Technical data............................................................................720
Serial and LON communication module (SLM) ..............................721
Introduction.................................................................................721
Design........................................................................................721
Technical data............................................................................722
Galvanic RS485 communication module.........................................723
Introduction.................................................................................723
Design........................................................................................723
Technical data............................................................................725
Optical ethernet module (OEM).......................................................725
Introduction.................................................................................725
Functionality...............................................................................725
Design........................................................................................725
Technical data............................................................................726
Line data communication module (LDCM)......................................727
Introduction.................................................................................727
Design........................................................................................727
Technical data............................................................................728
GPS time synchronization module (GTM).......................................729
20
Technical reference manual
Table of contents
Introduction.................................................................................729
Design........................................................................................729
Technical data............................................................................730
GPS antenna...................................................................................730
Introduction.................................................................................730
Design........................................................................................731
Technical data............................................................................732
IRIG-B time synchronization module IRIG-B...................................732
Introduction.................................................................................732
Design........................................................................................732
Technical data............................................................................734
Dimensions...........................................................................................735
Flush mounting dimensions.............................................................735
Side-by-side flush mounting dimensions.........................................736
Wall mounting dimensions...............................................................737
External current transformer unit.....................................................738
Mounting alternatives............................................................................738
Flush mounting................................................................................738
Overview.....................................................................................738
Mounting procedure for flush mounting......................................739
19 panel rack mounting..................................................................740
Mounting procedure for 19 panel rack mounting.......................740
Wall mounting..................................................................................741
Overview.....................................................................................741
Mounting procedure for wall mounting.......................................741
How to reach the rear side of the IED........................................742
Side-by-side 19 rack mounting.......................................................743
Overview.....................................................................................743
Mounting procedure for side-by-side rack mounting..................743
IED in the 670 series mounted with a RHGS6 case...................744
Side-by-side flush mounting............................................................744
Overview.....................................................................................744
Mounting procedure for side-by-side flush mounting..................745
Technical data......................................................................................746
Enclosure.........................................................................................746
Connection system..........................................................................746
Influencing factors...........................................................................747
Type tests according to standard....................................................748
Section 18 Labels................................................................................751
21
Technical reference manual
Table of contents
Labels on IED.......................................................................................751
Section 21 Glossary............................................................................807
22
Technical reference manual
Section 1
Introduction
1MRK505208-UUS D
Section 1
Introduction
1.1
1.1.1
Decommissioning
deinstalling & disposal
Maintenance
Operation
Commissioning
Installing
Engineering
Engineeringmanual
Installation and
Commissioning manual
Operators manual
Application manual
Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN
Section 1
Introduction
1MRK505208-UUS D
1.1.2
Local HMI describes the control panel on the IED and explains display
characteristics, control keys and various local HMI features.
Basic IED functions presents functions for all protection types that are included in
all IEDs, for example, time synchronization, self supervision with event list, test
mode and other general functions.
Current protection describes functions, for example, over current protection,
breaker failure protection and pole discordance.
Voltage protection describes functions for under voltage and over voltage
protection and residual over voltage protection.
Frequency protection describes functions for over frequency, under frequency and
rate of change of frequency protection.
Multipurpose protection describes the general protection function for current and
voltage.
Control describes control functions, for example, synchronization and energizing
check and other product specific functions.
Logic describes trip logic and related functions.
24
Technical reference manual
Section 1
Introduction
1MRK505208-UUS D
1.1.3
Monitoring describes measurement related functions that are used to provide data
regarding relevant quantities, events and faults, for example.
Metering describes pulse counter logic.
Station communication describes Ethernet based communication in general,
including the use of IEC 61850 and horizontal communication via GOOSE.
Remote communication describes binary and analog signal transfer, and the
associated hardware.
Hardware describes the IED and its components.
Connection diagrams provides terminal wiring diagrams and information
regarding connections to and from the IED.
Inverse time characteristics describes and explains inverse time delay, inverse
time curves and their effects.
Glossary is a list of terms, acronyms and abbreviations used in ABB technical
documentation.
This manual
The description of each IED related function follows the same structure (where
applicable). The different sections are outlined below.
1.1.3.1
Introduction
Outlines the implementation of a particular protection function.
1.1.3.2
Principle of operation
Describes how the function works, presents a general background to algorithms and
measurement techniques. Logic diagrams are used to illustrate functionality.
Logic diagrams
Logic diagrams describe the signal logic inside the function block and are bordered by
dashed lines.
Signal names
Input and output logic signals consist of two groups of letters separated by two dashes.
The first group consists of up to four letters and presents the abbreviated name for the
corresponding function. The second group presents the functionality of the particular
signal. According to this explanation, the meaning of the signal BLKTR in figure 4 is
as follows:
BLKTR informs the user that the signal will BLOCK the TRIP command from the
under-voltage function, when its value is a logical one (1).
25
Technical reference manual
Section 1
Introduction
1MRK505208-UUS D
Input signals are always on the left hand side, and output signals on the right hand side.
Settings are not displayed.
Input and output signals
In a logic diagram, input and output signal paths are shown as a lines that touch the
outer border of the diagram.
Input and output signals can be configured using the ACT tool. They can be connected
to the inputs and outputs of other functions and to binary inputs and outputs. Examples
of input signals are BLKTR, BLOCK and VTSU. Examples output signals are TRIP,
START, STL1, STL2, STL3.
Setting parameters
Signals in frames with a shaded area on their right hand side represent setting
parameter signals. These parameters can only be set via the PST or LHMI. Their values
are high (1) only when the corresponding setting parameter is set to the symbolic value
specified within the frame. Example is the signal Block TUV=Yes. Their logical
values correspond automatically to the selected setting value.
Internal signals
Internal signals are illustrated graphically and end approximately 2 mm from the frame
edge. If an internal signal path cannot be drawn with a continuous line, the suffix -int is
added to the signal name to indicate where the signal starts and continues, see figure 1.
26
Technical reference manual
Section 1
Introduction
1MRK505208-UUS D
BLKTR
TEST
TEST
AND
Block TUV=Yes
OR
BLOCK-int.
BLOCK
VTSU
BLOCK-int.
PU_V_A
AND
BLOCK-int.
AND
PU_V_B
BLOCK-int.
AND
PU_V_C
OR
AND
0-t
0
TRIP
PICKUP
PU_A
PU_B
PU_C
xx04000375_ansi.vsd
ANSI04000375 V1 EN
Figure 1:
External signals
Signal paths that extend beyond the logic diagram and continue in another diagram
have the suffix -cont., see figure 2 and figure 3.
27
Technical reference manual
Section 1
Introduction
1MRK505208-UUS D
AB
BC
CA
AG
BG
CG
STZMPP-cont.
OR
PHSEL
PUND_AB-cont.
AND
PUND_BC-cont.
AND
PUND_CA-cont.
AND
PUND_AG-cont.
AND
PUND_BG-cont.
AND
PUND_CG-cont.
AND
PUND_GND-cont.
OR
OR
LOVBZ
1--BLOCK
PU_ND
AND
OR
BLK-cont.
xx04000376_ansi.vsd
ANSI04000376 V1 EN
Figure 2:
STND_AG-cont.
or
STND_BG-cont.
AND
STND_CG-cont.
STND_AB-cont.
or
AND
STND_BC-cont.
STND_CA-cont.
AND
or
or
AND
PU_A
15 ms
PU_B
15 ms
PU_C
15 ms
PICKUP
15 ms
BLK-cont.
Xx04000377_ansi.vsd
ANSI04000377 V1 EN
Figure 3:
28
Technical reference manual
Section 1
Introduction
1MRK505208-UUS D
1.1.3.3
1.1.3.4
Function block
Each function block is illustrated graphically.
Input signals are always on the left hand side and output signals on the right hand side.
Settings are not displayed. Special kinds of settings are sometimes available. These are
supposed to be connected to constants in the configuration scheme and are therefore
depicted as inputs. Such signals will be found in the signal list but described in the
settings table.
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set a signal name of their
own in PCM600.
The * character after an input or output signal name in the function block symbol
given for a function, indicates that the signal must be connected to another
function block in the application configuration to achieve a valid application
configuration.
IEC 61850 - 8 -1
Logical Node
Mandatory
signal (*)
Inputs
Outputs
PCGGIO
BLOCK
READ_VAL
BI_PULSE*
RS_CNT
User defined
name (^)
INVALID
RESTART
BLOCKED
NEW_VAL
^SCAL_VAL
en05000511-1-en.vsd
Diagram
Number
IEC05000511 V2 EN
Figure 4:
29
Technical reference manual
Section 1
Introduction
1.1.3.5
1MRK505208-UUS D
Setting parameters
These are presented in tables and include all parameters associated with the function in
question.
1.1.3.6
Technical data
The technical data section provides specific technical information about the function or
hardware described.
1.1.4
Intended audience
General
This manual addresses system engineers, installation and commissioning personnel,
who use technical data during engineering, installation and commissioning, and in
normal service.
Requirements
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logics in the
protective devices. The installation and commissioning personnel must have a basic
knowledge in the handling electronic equipment.
1.1.5
Revision notes
Revision
Description
30
Technical reference manual
Section 2
Analog inputs
1MRK505208-UUS D
Section 2
Analog inputs
2.1
Introduction
Analog input channels must be configured and set properly to get correct measurement
results and correct protection operations. For power measuring and all directional and
differential functions the directions of the input currents must be defined properly.
Measuring and protection algorithms in the IED use primary system quantities. Setting
values are in primary quantities as well and it is important to set the data about the
connected current and voltage transformers properly.
A reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channels phase angle will always be fixed to zero degrees and all other angle
information will be shown in relation to this analog input. During testing and
commissioning of the IED the reference channel can be changed to facilitate testing
and service values reading.
The availability of VT inputs depends on the ordered transformer input
module (TRM) type.
2.2
Operation principle
The direction of a current depends on the connection of the CT. The main CTs are
typically star (WYE) connected and can be connected with the Star (WYE) point to the
object or from the object. This information must be set in the IED.
The convention of the directionality is defined as follows:
Positive value of current or power means that the quantity has the direction into
the object.
Negative value of current or power means that the quantity has the direction out
from the object.
For directional functions the directional conventions are defined as follows (see figure
5)
31
Technical reference manual
Section 2
Analog inputs
1MRK505208-UUS D
Definition of direction
for directional functions
Reverse
Forward
Forward
Reverse
Protected Object
Line, transformer, etc
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CT_WyePoint
Correct Setting is
"ToObject"
Set parameter
CT_WyePoint
Correct Setting is
"FromObject"
en05000456_ansi.vsd
ANSI05000456 V1 EN
Figure 5:
2.3
Function block
The function blocks are not represented in the configuration tool. The
signals appear only in the SMT tool when a TRM is included in the
configuration with the function selector tool. In the SMT tool they can
be mapped to the desired virtual input (SMAI) of the IED and used
internally in the configuration.
32
Technical reference manual
Section 2
Analog inputs
1MRK505208-UUS D
2.4
Setting parameters
Dependent on ordered IED type.
Table 1:
Name
PhaseAngleRef
Values (Range)
TRM40-Ch1
TRM40-Ch2
TRM40-Ch3
TRM40-Ch4
TRM40-Ch5
TRM40-Ch6
TRM40-Ch7
TRM40-Ch8
TRM40-Ch9
TRM40-Ch10
TRM40-Ch11
TRM40-Ch12
TRM41-Ch1
TRM41-Ch2
TRM41-Ch3
TRM41-Ch4
TRM41-Ch5
TRM41-Ch6
TRM41-Ch7
TRM41-Ch8
TRM41-Ch9
TRM41-Ch10
TRM41-Ch11
TRM41-Ch12
MU1-IA
MU1-IB
MU1-IC
MU1-I0
MU1- VA
MU1- VB
MU1-VC
MU1-V0
MU2-IA
MU2-IB
MU2-IC
MU2-I0
MU2-VA
MU2-VB
MU2-VC
MU2-V0
MU3-IA
MU3-IB
MU3-IC
MU3-I0
MU3-VB
MU2-VB
MU3-VC
MU3-V0
Unit
-
Step
-
Default
TRM40-Ch1
Description
Reference channel for phase angle
presentation
33
Technical reference manual
34
Section 3
Local HMI
1MRK505208-UUS D
Section 3
Local HMI
3.1
Connection of each bay, respecting the two differential protection zones and the
check zone. In the Parameter Setting Tool the user sets individual bay names to
facilitate the identification of each primary bay for station personnel.
Status of each individual primary switchgear device, for example, open, closed, 00
as intermediate state and 11 as bad state. In PCM600 the user sets the individual
primary switchgear object names to facilitate the identification of each switchgear
device for the station personnel.
35
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
IEC06000530 V1 EN
Figure 6:
36
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
IEC06000191 V1 EN
Figure 7:
37
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
IEC06000192 V1 EN
Figure 8:
3.2
3.2.1
Medium
The following case sizes can be equipped with the medium size LCD:
1/2 x 19
3/4 x 19
1/1 x 19
38
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
This is a fully graphical monochrome LCD which measures 4.7 x 3.5 inches. It has 28
lines with up to 40 characters per line. To display the single line diagram, this LCD is
required. To display the station matrix, this LCD is required.
3.2.2
Design
The different parts of the medium size local HMI are shown in figure 9. The local HMI
exists in an IEC version and in an ANSI version. The difference is on the keypad
operation buttons and the yellow LED designation.
39
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
IEC06000530-CALLOUT V1 EN
Figure 9:
40
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
3.3
Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look and
feel in all IEDs. LCD screens and other details may differ but the way the keys
function is identical.
IEC06000531 V1 EN
Figure 10:
Table 2 describes the HMI keys that are used to operate the IED.
Table 2:
Key
IEC06000532 V1 EN
Press to open two sub menus: Key operation and IED information.
IEC05000103 V1 EN
Press to open the main menu and to move to the default screen.
IEC05000105 V1 EN
41
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Key
Function
Press to set the IED in local or remote control mode.
IEC05000106 V1 EN
Press to start the editing mode and confirm setting changes, when in editing mode.
IEC05000108 V1 EN
Press to navigate forward between screens and move right in editing mode.
IEC05000109 V1 EN
Press to navigate backwards between screens and move left in editing mode.
IEC05000110 V1 EN
Press to move up in the single line diagram and in the menu tree.
IEC05000111 V1 EN
Press to move down in the single line diagram and in the menu tree.
IEC05000112 V1 EN
3.4
LED
3.4.1
Introduction
The LED module is a unidirectional means of communicating. This means that events
may occur that activate a LED in order to draw the operators attention to something
that has occurred and needs some sort of action.
3.4.2
Information
Green:
Steady
In service
Flashing
Internal failure
Dark
No power supply
Yellow:
Steady
42
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
LED Indication
Flashing
Information
Terminal in test mode
Red:
Steady
3.4.3
Indication LEDs
The LED indication module comprising 15 LEDs is standard in 670 series. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.
Alarm indication LEDs and hardware associated LEDs are located on the right hand
side of the front panel. Alarm LEDs are located on the right of the LCD screen and
show steady or flashing light.
Alarm LEDs can be configured in PCM600 and depend on the binary logic. Therefore
they can not be configured on the local HMI.
Typical examples of alarm LEDs
The RJ45 port has a yellow LED indicating that communication has been established
between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
43
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
3.5
3.5.1
Introduction
The local HMI can be adapted to the application configuration and to user preferences.
3.5.2
Table 3:
Name
Unit
Step
Default
Description
Language
English
OptionalLanguage
English
DisplayTimeout
10 - 120
Min
10
60
AutoRepeat
Disabled
Enabled
Enabled
ContrastLevel
-10 - 20
DefaultScreen
0-0
Default screen
EvListSrtOrder
Latest on top
Oldest on top
Latest on top
SymbolFont
IEC
ANSI
IEC
3.5.3
Status LEDs
3.5.3.1
Design
The function block LocalHMI controls and supplies information about the status of the
status indication LEDs. The input and output signals of local HMI are configured with
PCM600.
The function block can be used if any of the signals are required in a configuration logic.
See section "Status indication LEDs" for information about the LEDs.
44
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
3.5.3.2
Function block
LocalHMI
RSTLEDS
HMI-ON
RED-S
YELLOW-S
YELLOW-F
RSTPULSE
LEDSRST
ANSI05000773-2-en.vsd
ANSI05000773 V2 EN
Figure 11:
3.5.3.3
Table 5:
Name
Default
0
Description
Input to reset the LCD-HMI LEDs
Description
HMI-ON
BOOLEAN
RED-S
BOOLEAN
YELLOW-S
BOOLEAN
YELLOW-F
BOOLEAN
RSTPULSE
BOOLEAN
A reset pulse is provided when the LEDs on the LCDHMI are cleared
LEDSRST
BOOLEAN
3.5.4
Indication LEDs
3.5.4.1
Introduction
The function block LEDGEN controls and supplies information about the status of the
indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.
45
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Each indication LED on the local HMI can be set individually to operate in six
different sequences
The light from the LEDs can be steady (-S) or flashing (-F). See the technical reference
manual for more information.
3.5.4.2
Design
The information on the LEDs is stored at loss of the auxiliary power to the IED in
some of the modes of LEDGEN. The latest LED picture appears immediately after the
IED is successfully restarted.
Operating modes
Collecting mode
Re-starting mode
In the re-starting mode of operation each new pickup resets all previous
active LEDs and activates only those which appear during one disturbance.
Only LEDs defined for re-starting mode with the latched sequence type 6
(LatchedReset-S) will initiate a reset and a restart at a new disturbance. A
disturbance is defined to end a settable time after the reset of the activated
input signals or when the maximum time limit has elapsed.
Acknowledgment/reset
46
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
via the reset button and menus on the local HMI. See the operator's manual
for more information.
Automatic reset
Automatic reset can only be performed for indications defined for re-starting
mode with the latched sequence type 6 (LatchedReset-S). When automatic
reset of the LEDs has been performed, still persisting indications will be
indicated with a steady light.
Operating sequences
For the Follow type the LED follows the input signal completely.
For the Latched type each LED latches to the corresponding input signal until it is
reset.
Figure 12 show the function of available sequences that are selectable for each LED
separately.
The letters S and F in the sequence names have the meaning S = Steady and F = Flashing.
At the activation of the input signal, the indication operates according to the selected
sequence diagrams.
In the sequence diagrams the LEDs have the characteristics as shown in figure 12.
47
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
= No indication
= Steady light
= Flash
en05000506.vsd
IEC05000506 V1 EN
Figure 12:
Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input signals.
It does not react on acknowledgment or reset. Every LED is independent of the other
LEDs in its operation.
Activating
signal
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN
Figure 13:
Sequence 2 (Follow-F)
This sequence is the same as sequence 1, Follow-S, but the LEDs are flashing instead
of showing steady light.
Sequence 3 (LatchedAck-F-S)
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal, the
indication starts flashing. After acknowledgment the indication disappears if the signal
is not present any more. If the signal is still present after acknowledgment it gets a
steady light.
Activating
signal
LED
Acknow.
en01000231.vsd
IEC01000231 V1 EN
Figure 14:
48
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing light
have been alternated.
Sequence 5 (LatchedColl-S)
This sequence has a latched function and works in collecting mode. At the activation of
the input signal, the indication will light up with a steady light. The difference to
sequence 3 and 4 is that indications that are still activated will not be affected by the
reset that is, immediately after the positive edge of the reset has been executed a new
reading and storing of active signals is performed. Every LED is independent of the
other LEDs in its operation.
Activating
signal
LED
Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN
Figure 15:
Sequence 6 (LatchedReset-S)
In this mode all activated LEDs, which are set to sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to sequence 6 (LatchedReset-S). Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the positive
edge of that the manual reset has been executed a new reading and storing of active
signals is performed. LEDs set for sequence 6 are completely independent in its
operation of LEDs set for other sequences.
Definition of a disturbance
A disturbance is defined to last from the first LED set as LatchedReset-S is activated
until a settable time, tRestart, has elapsed after that all activating signals for the LEDs
set as LatchedReset-S have reset. However if all activating signals have reset and some
signal again becomes active before tRestart has elapsed, the tRestart timer does not
restart the timing sequence. A new disturbance start will be issued first when all signals
have reset after tRestart has elapsed. A diagram of this functionality is shown in figure
16.
49
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
From
disturbance
length control
per LED
set to
sequence 6
OR
OR
AND
OR
New
disturbance
tRestart
0
0-100s
AND
OR
AND
en01000237_ansi.vsd
ANSI01000237 V1 EN
Figure 16:
In order not to have a lock-up of the indications in the case of a persisting signal each
LED is provided with a timer, tMax, after which time the influence on the definition of
a disturbance of that specific LED is inhibited. This functionality is shown i diagram in
figure 17.
Activating signal
To LED
AND
0-tMax
0
To disturbance
length control
en05000507_ansi.vsd
ANSI05000507 V1 EN
Figure 17:
50
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN
Figure 18:
Figure 19 shows the timing diagram for a new indication after tRestart time has elapsed.
51
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Disturbance
tRestart
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN
Figure 19:
Figure 20 shows the timing diagram when a new indication appears after the first one
has reset but before tRestart has elapsed.
52
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN
Figure 20:
53
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Disturbance
tRestart
Activating
signal 1
Activating
signal 2
LED 1
LED 2
Automatic
reset
Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN
Figure 21:
3.5.4.3
Function block
LEDGEN
BLOCK
RESET
LEDTEST
NEWIND
ACK
IEC05000508_2_en.vsd
IEC05000508 V2 EN
Figure 22:
3.5.4.4
Default
Description
BLOCK
BOOLEAN
RESET
BOOLEAN
LEDTEST
BOOLEAN
54
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Table 7:
Name
3.5.4.5
Table 8:
Type
Description
NEWIND
BOOLEAN
ACK
BOOLEAN
Setting parameters
LEDGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
tRestart
0.0 - 100.0
0.1
0.0
tMax
0.0 - 100.0
0.1
0.0
SeqTypeLED1
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED2
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED3
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED4
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED5
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
55
Technical reference manual
Section 3
Local HMI
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
SeqTypeLED6
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED7
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED8
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED9
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED10
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED11
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED12
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
56
Technical reference manual
Section 3
Local HMI
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
SeqTypeLED13
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED14
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
SeqTypeLED15
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Follow-S
57
Technical reference manual
58
Section 4
Basic IED functions
1MRK505208-UUS D
Section 4
4.1
Authorization
To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The authorization
handling of the IED and the PCM600 is implemented at both access points to the IED:
4.1.1
Principle of operation
There are different levels (or types) of users that can access or operate different areas
of the IED and tools functionality. The pre-defined user types are given in Table 9.
Be sure that the user logged on to the IED has the access required when
writing particular data to the IED from PCM600.
The meaning of the legends used in the table:
R= Read
W= Write
- = No access rights
59
Technical reference manual
Section 4
Basic IED functions
Table 9:
1MRK505208-UUS D
Access rights
Guest
Super User
SPA Guest
System
Operator
Protection
Engineer
Design
Engineer
User
Administrator
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
The IED users can be created, deleted and edited only with the IED User Management
within PCM600. The user can only LogOn or LogOff on the local HMI on the IED,
there are no users, groups or functions that can be defined on local HMI.
Only characters A - Z, a - z and 0 - 9 should be used in user names and
passwords.
The maximum of characters in a password is 18.
60
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.1.1.1
61
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.2
4.2.1
Introduction
Self supervision with internal event list function listens and reacts to internal system
events, generated by the different built-in self-supervision elements. The internal
events are saved in an internal event list.
4.2.2
Principle of operation
The self-supervision operates continuously and includes:
The self-supervision function status can be monitored from the local HMI, from the
Event Viewer in PCM600 or from a SMS/SCS system.
Under the Diagnostics menu in the local HMI the present information from the selfsupervision function can be reviewed. The information can be found under Main
menu/Diagnostics/Internal events or Main menu/Diagnostics/IED status/General.
The information from the self-supervision function is also available in the Event
Viewer in PCM600.
A self-supervision summary can be obtained by means of the potential free alarm
contact (INTERNAL FAIL) located on the power supply module. The function of this
output relay is an OR-function between the INT-FAIL signal see figure 24 and a
couple of more severe faults that can occur in the IED, see figure 23
62
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Watchdog
TX overflow
Master resp.
Supply fault
Power supply
module
Fault
I/O nodes
Fault
AND
ReBoot I/O
INTERNAL
FAIL
Internal Fail (CPU)
Fault
CEM
Figure 23:
IO fail
OR
IO stopped
Set
Reset
IO started
OR
Internal
FAIL
OR
LON ERROR
FTF fatal error
OR
Watchdog
NUMFAIL
OR
Reset
Internal
WARN
Set
OR
RTCERROR
Set
RTC OK
Reset
TIMESYNCHERROR
Time reset
OR
Set
Reset
SYNCH OK
Settings changed
NUMWARNING
TIMESYNCHERROR
SETCHGD
1 second pulse
en04000519-1.vsd
IEC04000519 V2 EN
Figure 24:
63
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Some signals are available from the INTERRSIG function block. The signals from this
function block are sent as events to the station level of the control system. The signals
from the INTERRSIG function block can also be connected to binary outputs for
signalization via output relays or they can be used as conditions for other functions if
required/desired.
Individual error signals from I/O modules can be obtained from respective module in
the Signal Matrix tool. Error signals from time synchronization can be obtained from
the time synchronization block TIMEINTERRSIG.
4.2.2.1
Internal signals
Self supervision provides several status signals, that tells about the condition of the
IED. As they provide information about the internal status of the IED, they are also
called internal signals. The internal signals can be divided into two groups.
Standard signals are always presented in the IED, see Table 10.
Hardware dependent internal signals are collected depending on the hardware
configuration, see Table 11.
Name of signal
Description
FAIL
WARNING
NUMFAIL
NUMWARNING
RTCERROR
TIMESYNCHERROR
RTEERROR
IEC61850ERROR
WATCHDOG
LMDERROR
APPERROR
SETCHGD
Settings changed
SETGRPCHGD
FTFERROR
64
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 11:
Card
Name of signal
Description
PSM
PSM-Error
ADOne
ADOne-Error
BIM
BIM-Error
BOM
BOM-Error
IOM
IOM-Error
MIM
MIM-Error
LDCM
LDCM-Error
Table 12:
Name of signal
FAIL
WARNING
NUMFAIL
NUMWARNING
RTCERROR
This signal will be active when there is a hardware error with the real
time clock.
TIMESYNCHERROR
This signal will be active when the source of the time synchronization
is lost, or when the time system has to make a time reset.
RTEERROR
IEC61850ERROR
This signal will be active if the IEC 61850 stack did not succeed in
some actions like reading IEC 61850 configuration, startup, for
example
WATCHDOG
This signal will be activated when the terminal has been under too
heavy load for at least 5 minutes. The operating systems background
task is used for the measurements.
LMDERROR
APPERROR
This signal will be active if one or more of the application threads are
not in the state that Runtime Engine expects. The states can be
CREATED, INITIALIZED, RUNNING, for example
65
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Name of signal
4.2.2.2
SETCHGD
This signal will generate an Internal Event to the Internal Event list if
any settings are changed.
SETGRPCHGD
This signal will generate an Internal Event to the Internal Event list if
any setting groups are changed.
FTFERROR
This signal will be active if both the working file and the backup file
are corrupted and can not be recovered.
Run-time model
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification, see Figure 25.
ADx
ADx_Low
x1
u1
x2
ADx_High
ADx
Controller
x1
u1
x2
IEC05000296-3-en.vsd
IEC05000296 V3 EN
Figure 25:
The technique to split the analog input signal into two A/D converter(s) with different
amplification makes it possible to supervise the A/D converters under normal
conditions where the signals from the two A/D converters should be identical. An
alarm is given if the signals are out of the boundaries. Another benefit is that it
improves the dynamic performance of the A/D conversion.
The self-supervision of the A/D conversion is controlled by the ADx_Controller
function. One of the tasks for the controller is to perform a validation of the input
signals. This is done in a validation filter which has mainly two objects: First is the
validation part that checks that the A/D conversion seems to work as expected.
Secondly, the filter chooses which of the two signals that shall be sent to the CPU, that
is the signal that has the most suitable signal level, the ADx_LO or the 16 times higher
ADx_HI.
66
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
When the signal is within measurable limits on both channels, a direct comparison of
the two A/D converter channels can be performed. If the validation fails, the CPU will
be informed and an alarm will be given for A/D converter failure.
The ADx_Controller also supervise other parts of the A/D converter.
4.2.3
Function block
IEC09000787 V1 EN
Figure 26:
4.2.4
Output signals
Table 13:
Name
4.2.5
Type
Description
FAIL
BOOLEAN
Internal fail
WARNING
BOOLEAN
Internal warning
CPUFAIL
BOOLEAN
CPU fail
CPUWARN
BOOLEAN
CPU warning
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
4.2.6
Technical data
Table 14:
Data
Value
Recording manner
List size
67
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.3
Time synchronization
4.3.1
Introduction
The time synchronization source selector is used to select a common source of absolute
time for the IED when it is a part of a protection system. This makes it possible to
compare event and disturbance data between all IEDs in a station automation system.
Micro SCADA OPC server should not be used as a time
synchronization source.
4.3.2
Principle of operation
4.3.2.1
General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time
the clock is intended to have. Clock accuracy indicates the increase in error, that is, the
time gained or lost by the clock. A disciplined clock knows its own faults and tries to
compensate for them.
The time system is based on a software clock, which can be adjusted from external
time sources and a hardware clock. The protection and control modules will be timed
from a hardware clock, which runs independently from the software clock. See figure 27
68
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
External
Synchronization
sources
Off
LON
SPA
Min. pulse
GPS
SNTP
DNP
Communication
TimeRegulator
(Setting,
see
technical
reference
manual)
Events
Protection
and control
functions
SW-time
Connected when GPS-time is
used for differential protection
IRIG-B
PPS
Off
GPS
IRIG-B
PPS
TimeRegulator
(fast or slow)
A/D
converter
Diff.communication
Transducers*
*IEC 61850-9-2
IEC08000287-2-en.vsd
IEC08000287 V2 EN
Figure 27:
All time tagging is performed by the software clock. When for example a status signal
is changed in the protection system with the function based on free running hardware
clock, the event is time tagged by the software clock when it reaches the event
recorder. Thus the hardware clock can run independently.
The echo mode for the differential protection is based on the hardware clock. Thus,
there is no need to synchronize the hardware clock and the software clock.
The synchronization of the hardware clock and the software clock is necessary only
when GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differential
protection. The two clock systems are synchronized by a special clock synchronization
unit with two modes, fast and slow. A special feature, an automatic fast clock time
regulator is used. The automatic fast mode makes the synchronization time as short as
possible during start up or at interruptions/disturbances in the GPS timing. The setting
fast or slow is also available on the local HMI.
If a GPS clock is used for 670 series IEDs other than line differential RED670, the
hardware and software clocks are not synchronized
69
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Synchronization principle
Synchronization from
a higher level
Function
Optional synchronization of
modules at a lower level
IEC09000342-1-en.vsd
IEC09000342 V1 EN
Figure 28:
Synchronization principle
70
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
to choose the source with the best quality, and to adjust its internal clock after this
source. The maximum error of a clock can be defined as:
4.3.2.2
During power off, the system time in the IED is kept by a capacitor-backed real-time
clock that will provide 35 ppm accuracy for 5 days. This means that if the power is off,
the time in the IED may drift with 3 seconds per day, during 5 days, and after this time
the time will be lost completely.
The first message that contains the full time (as for instance LON, SNTP and GPS)
gives an accurate time to the IED. After the initial setting of the clock, one of three
things happens with each of the coming synchronization messages configured as fine:
Synchronization messages configured as coarse are only used for initial setting of the
time. After this has been done, the messages are checked against the internal time and
only an offset of more than 10 seconds resets the time.
71
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Rate accuracy
In the IED, the rate accuracy at cold start is 100 ppm but if the IED is synchronized for
a while, the rate accuracy is approximately 1 ppm if the surrounding temperature is
constant. Normally, it takes 20 minutes to reach full accuracy.
All synchronization interfaces has a time-out and a configured interface must receive
time-messages regularly in order not to give an error signal (TSYNCERR). Normally,
the time-out is set so that one message can be lost without getting a TSYNCERR, but if
more than one message is lost, a TSYNCERR is given.
4.3.2.3
Synchronization alternatives
Three main alternatives of external time synchronization are available. The
synchronization message is applied:
via any of the communication ports of the IED as a telegram message including
date and time
as a minute pulse connected to a binary input
via GPS
The minute pulse is used to fine tune already existing time in the IEDs.
On the serial buses (both LON and SPA) two types of synchronization messages are sent.
72
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Coarse message is sent every minute and comprises complete date and time, that
is, year, month, day, hours, minutes, seconds and milliseconds.
Fine message is sent every second and comprises only seconds and milliseconds.
The built in GPS clock modules receives and decodes time information from the global
positioning system. The modules are located on the GPS time synchronization Module
(GTM).
The IED accepts minute pulses to a binary input. These minute pulses can be generated
from, for example station master clock. If the station master clock is not synchronized
from a world wide source, time will be a relative time valid for the substation. Both
positive and negative edge on the signal can be accepted. This signal is also considered
as a fine time synchronization signal.
The minute pulse is connected to any channel on any Binary Input Module in the IED.
The electrical characteristic is thereby the same as for any other binary input.
If the objective of synchronization is to achieve a relative time within the substation
and if no station master clock with minute pulse output is available, a simple minute
pulse generator can be designed and used for synchronization of the IEDs. The minute
pulse generator can be created using the logical elements and timers available in the IED.
The definition of a minute pulse is that it occurs one minute after the last pulse. As
only the flanks are detected, the flank of the minute pulse shall occur one minute after
the last flank.
Binary minute pulses are checked with reference to frequency.
Pulse data:
73
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
a
b
c
en05000251.vsd
IEC05000251 V1 EN
Figure 29:
The default time-out-time for a minute pulse is two minutes, and if no valid minute
pulse is received within two minutes a SYNCERR will be given.
If contact bounce occurs, only the first pulse will be detected as a minute pulse. The
next minute pulse will be registered first 60 s - 50 ms after the last contact bounce.
If the minute pulses are perfect, for example, it is exactly 60 seconds between the
pulses, contact bounces might occur 49 ms after the actual minute pulse without
effecting the system. If contact bounce occurs more than 50 ms, for example, it is less
than 59950 ms between the two most adjacent positive (or negative) flanks, the minute
pulse will not be accepted.
Binary synchronization example
An IED is configured to use only binary input, and a valid binary input is applied to a
binary input card. The HMI is used to tell the IED the approximate time and the minute
pulse is used to synchronize the IED thereafter. The definition of a minute pulse is that
it occurs one minute after the previous minute pulse, so the first minute pulse is not
used at all. The second minute pulse will probably be rejected due to the spike filter.
The third pulse will give the IED a good time and will reset the time so that the fourth
minute pulse will occur on a minute border. After the first three minutes, the time in
the IED will be good if the coarse time is set properly via the HMI or the RTC backup
still keeps the time since last up-time. If the minute pulse is removed for instance for
an hour, the internal time will drift by maximum the error rate in the internal clock. If
the minute pulse is returned, the first pulse automatically is rejected. The second pulse
will possibly be rejected due to the spike filter. The third pulse will either synchronize
the time, if the time offset is more than 100 ms, or adjust the time, if the time offset is
small enough. If the time is set, the application will be brought to a safe state before the
time is set. If the time is adjusted, the time will reach its destination within 1.7 minutes.
74
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.3.3
Function block
TIMEERR
TSYNCERR
RTCERR
IEC05000425-2-en.vsd
IEC05000425 V2 EN
Figure 30:
4.3.4
Output signals
Table 15:
Name
Description
TSYNCERR
BOOLEAN
RTCERR
BOOLEAN
75
Technical reference manual
Section 4
Basic IED functions
4.3.5
1MRK505208-UUS D
Setting parameters
Path in the local HMI is located under Main menu/Setting/Time
Path in PCM600 is located under Main menu/Settings/Time/Synchronization
Table 16:
Name
Unit
Step
Default
Description
CoarseSyncSrc
Disabled
SPA
LON
SNTP
DNP
Disabled
FineSyncSource
Disabled
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
Disabled
SyncMaster
Disabled
SNTP-Server
Disabled
TimeAdjustRate
Slow
Fast
Fast
HWSyncSrc
Disabled
GPS
IRIG-B
PPS
Disabled
AppSynch
NoSynch
Synch
NoSynch
SyncAccLevel
Class T5 (1us)
Class T4 (4us)
Unspecified
Unspecified
Table 17:
Name
Unit
Step
Default
Description
ModulePosition
3 - 16
BinaryInput
1 - 16
BinDetection
PositiveEdge
NegativeEdge
PositiveEdge
76
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 18:
Name
Values (Range)
Unit
Step
Default
Description
ServerIP-Add
0 - 18
IP
Address
0.0.0.0
Server IP-address
RedServIP-Add
0 - 18
IP
Address
0.0.0.0
Table 19:
Name
Values (Range)
Unit
Step
Default
Description
MonthInYear
January
February
March
April
May
June
July
August
September
October
November
December
March
DayInWeek
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
WeekInMonth
Last
First
Second
Third
Fourth
Last
UTCTimeOfDay
0 - 172800
3600
77
Technical reference manual
Section 4
Basic IED functions
Table 20:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
MonthInYear
January
February
March
April
May
June
July
August
September
October
November
December
October
DayInWeek
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
WeekInMonth
Last
First
Second
Third
Fourth
Last
UTCTimeOfDay
0 - 172800
3600
Table 21:
Name
NoHalfHourUTC
Table 22:
Name
Unit
-
Step
1
Default
0
Description
Number of half-hours from UTC
Unit
Step
Default
Description
SynchType
BNC
Opto
Opto
Type of synchronization
TimeDomain
LocalTime
UTC
LocalTime
Time domain
Encoding
IRIG-B
1344
1344TZ
IRIG-B
Type of encoding
TimeZoneAs1344
MinusTZ
PlusTZ
PlusTZ
78
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.3.6
Technical data
Table 23:
Function
Value
1 ms
1.0 ms typically
1.0 ms typically
4.4
4.4.1
Introduction
Use the six different groups of settings to optimize the IED operation for different
power system conditions. Creating and switching between fine-tuned setting sets,
either from the local HMI or configurable binary inputs, results in a highly adaptable
IED that can cope with a variety of power system scenarios.
4.4.2
Principle of operation
Parameter setting groups ActiveGroup function has six functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of these
inputs changes the active setting group. Seven functional output signals are available
for configuration purposes, so that up to date information on the active setting group is
always available.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ActiveGroup function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
More than one input may be activated at the same time. In such cases the lower order
setting group has priority. This means that if for example both group four and group
two are set to activate, group two will be the one activated.
Every time the active group is changed, the output signal GRP_CHGD is sending a pulse.
79
Section 4
Basic IED functions
1MRK505208-UUS D
The parameter MAXSETGR defines the maximum number of setting groups in use to
switch between.
ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
+RL2
IOx-Bly1
IOx-Bly2
IOx-Bly3
IOx-Bly4
ActiveGroup
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
IOx-Bly5
ACTGRP5
GRP5
IOx-Bly6
ACTGRP6
GRP6
GRP_CHGD
ANSI05000119-2-en.vsd
ANSI05000119 V2 EN
Figure 31:
The above example also includes seven output signals, for confirmation of which
group that is active.
SETGRPS function block has an input where the number of setting groups used is
defined. Switching can only be done within that number of groups. The number of
setting groups selected to be used will be filtered so only the setting groups used will
be shown on the Parameter Setting Tool.
4.4.3
Function block
ActiveGroup
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
ACTGRP5
GRP5
ACTGRP6
GRP6
GRP_CHGD
ANSI05000433-2-en.vsd
ANSI05000433 V2 EN
Figure 32:
80
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
SETGRPS
MAXSETGR
IEC05000716_2_en.vsd
IEC05000716 V2 EN
Figure 33:
4.4.4
Name
Type
BOOLEAN
ACTGRP2
BOOLEAN
ACTGRP3
BOOLEAN
ACTGRP4
BOOLEAN
ACTGRP5
BOOLEAN
ACTGRP6
BOOLEAN
Name
Table 26:
Description
ACTGRP1
Table 25:
4.4.5
Default
Type
Description
GRP1
BOOLEAN
GRP2
BOOLEAN
GRP3
BOOLEAN
GRP4
BOOLEAN
GRP5
BOOLEAN
GRP6
BOOLEAN
GRP_CHGD
BOOLEAN
Setting parameters
ActiveGroup Non group settings (basic)
Name
t
Values (Range)
0.0 - 10.0
Unit
Step
0.1
Default
1.0
Description
Pulse length of pulse when setting changed
81
Technical reference manual
Section 4
Basic IED functions
Table 27:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
ActiveSetGrp
SettingGroup1
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6
SettingGroup1
ActiveSettingGroup
MAXSETGR
1-6
No
4.5
4.5.1
Introduction
Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.
4.5.2
Principle of operation
The Change lock function (CHNGLCK) is configured using ACT.
The function, when activated, will still allow the following changes of the IED state
that does not involve reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input signal LOCK controlling the function is defined in ACT or SMT:
82
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Binary input
4.5.3
Function
Activated
Deactivated
Function block
CHNGLCK
LOCK
IEC09000946-1-en.vsd
IEC09000946 V1 EN
Figure 34:
4.5.4
Name
Type
LOCK
4.5.5
Table 29:
BOOLEAN
Default
0
Description
Parameter change lock
Setting parameters
CHNGLCK Non group settings (basic)
Name
Operation
Values (Range)
LockHMI and Com
LockHMI,
EnableCom
EnableHMI,
LockCom
Unit
-
Step
-
Default
LockHMI and Com
4.6
4.6.1
Introduction
Description
Operation mode of change lock
When the Test mode functionality TESTMODE is activated, all the functions in the
IED are automatically blocked. It is then possible to unblock every function(s)
individually from the local HMI to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes normal
operation. However, if during TESTMODE operation, power is removed and later
83
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
restored, the IED will remain in TESTMODE with the same protection functions
blocked or unblocked as before the power was removed. All testing will be done with
actually set and configured values within the IED. No settings will be changed, thus
mistakes are avoided.
4.6.2
Principle of operation
Put the IED into test mode to test functions in the IED. Set the IED in test mode by
While the IED is in test mode, the ACTIVE of the function block TESTMODE is
activated. The other outputs of the function block TESTMODE shows the cause of the
"Test mode: Enabled" state input from configuration (OUTPUT output is activated)
or setting from local HMI (SETTING output is activated).
While the IED is in test mode, the yellow PICKUP LED will flash and all functions are
blocked. Any function can be unblocked individually regarding functionality and event
signalling.
Most of the functions in the IED can individually be blocked by means of settings from
the local HMI. To enable these blockings the IED must be set in test mode (output
ACTIVE is activated), see example in figure 35. When leaving the test mode, that is
entering normal mode, these blockings are disabled and everything is set to normal
operation. All testing will be done with actually set and configured values within the
IED. No settings will be changed, thus no mistakes are possible.
The blocked functions will still be blocked next time entering the test mode, if the
blockings were not reset.
The blocking of a function concerns all output signals from the actual function, so no
outputs will be activated.
When a binary input is used to set the IED in test mode and a
parameter, that requires restart of the application, is changed, the IED
will re-enter test mode and all functions will be blocked, also functions
that were unblocked before the change. During the re-entering to test
mode, all functions will be temporarily unblocked for a short time,
which might lead to unwanted operations. This is only valid if the IED
is put in TEST mode by a binary input, not by local HMI.
The TESTMODE function block might be used to automatically block functions when
a test handle is inserted in a test switch. A contact in the test switch (RTXP24 contact
84
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
29-30) or an FT switch finger can supply a binary input which in turn is configured to
the TESTMODE function block.
Each of the functions includes the blocking from the TESTMODE function block. A
typical example from the undervoltage function is shown in figure 35.
The functions can also be blocked from sending events over IEC 61850 station bus to
prevent filling station and SCADA databases with test events, for example during a
maintenance test.
Disconnection
Normal voltage
Pickup1
Pickup2
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466_ansi.vsd
ANSI05000466 V1 EN
Figure 35:
85
Technical reference manual
Section 4
Basic IED functions
4.6.3
1MRK505208-UUS D
Function block
TESTMODE
INPUT
ACTIVE
OUTPUT
SETTING
NOEVENT
IEC09000219-1.vsd
IEC09000219 V1 EN
Figure 36:
4.6.4
Name
Type
INPUT
BOOLEAN
Table 31:
Table 32:
Name
Description
Sets terminal in test mode when active
Name
4.6.5
Default
Type
Description
ACTIVE
BOOLEAN
OUTPUT
BOOLEAN
SETTING
BOOLEAN
NOEVENT
BOOLEAN
Setting parameters
TESTMODE Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
TestMode
Disabled
Enabled
Disabled
EventDisable
Disabled
Enabled
Disabled
CmdTestBit
Disabled
Enabled
Disabled
86
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.7
IED identifiers
4.7.1
Introduction
IED identifiers (TERMINALID) function allows the user to identify the individual IED
in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
4.7.2
Table 33:
Setting parameters
TERMINALID Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
StationName
0 - 18
Station name
Station name
StationNumber
0 - 99999
Station number
ObjectName
0 - 18
Object name
Object name
ObjectNumber
0 - 99999
Object number
UnitName
0 - 18
Unit name
Unit name
UnitNumber
0 - 99999
Unit number
4.8
Product information
4.8.1
Introduction
The Product identifiers function identifies the IED. The function has seven pre-set,
settings that are unchangeable but nevertheless very important:
IEDProdType
ProductDef
FirmwareVer
SerialNo
OrderingNo
ProductionDate
The settings are visible on the local HMI , under Main menu/Diagnostics/IED status/
Product identifiers
87
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
They are very helpful in case of support process (such as repair or maintenance).
4.8.2
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
4.8.3
IEDProdType
FirmwareVer
IEDMainFunType
Describes the type of the IED (like REL, REC or RET). Example: REL670
SerialNo
OrderingNo
ProductionDate
4.9
4.9.1
Introduction
The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see
88
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
the application manual to get information about how binary inputs are brought in for
one IED configuration.
4.9.2
Principle of operation
The Signal matrix for binary inputs (SMBI) function , see figure 37, receives its inputs
from the real (hardware) binary inputs via the Signal Matrix Tool (SMT), and makes
them available to the rest of the configuration via its outputs, BI1 to BI10. The inputs
and outputs, as well as the whole block, can be given a user defined name. These
names will be represented in SMT as information which signals shall be connected
between physical IO and SMBI function. The input/output user defined name will also
appear on the respective output/input signal.
4.9.3
Function block
SMBI
^VIN1
^VIN2
^VIN3
^VIN4
^VIN5
^VIN6
^VIN7
^VIN8
^VIN9
^VIN10
^BI1
^BI2
^BI3
^BI4
^BI5
^BI6
^BI7
^BI8
^BI9
^BI10
IEC05000434-2-en.vsd
IEC05000434 V2 EN
Figure 37:
4.9.4
Default
Description
VIn1
BOOLEAN
VIn2
BOOLEAN
VIn3
BOOLEAN
VIn4
BOOLEAN
VIn5
BOOLEAN
VIn6
BOOLEAN
VIn7
BOOLEAN
VIn8
BOOLEAN
VIn9
BOOLEAN
VIn10
BOOLEAN
89
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 35:
Name
Type
Description
BI1
BOOLEAN
Binary input 1
BI2
BOOLEAN
Binary input 2
BI3
BOOLEAN
Binary input 3
BI4
BOOLEAN
Binary input 4
BI5
BOOLEAN
Binary input 5
BI6
BOOLEAN
Binary input 6
BI7
BOOLEAN
Binary input 7
BI8
BOOLEAN
Binary input 8
BI9
BOOLEAN
Binary input 9
BI10
BOOLEAN
Binary input 10
4.10
4.10.1
Introduction
The Signal matrix for binary outputs (SMBO) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see
the application manual to get information about how binary inputs are sent from one
IED configuration.
4.10.2
Principle of operation
The Signal matrix for binary outputs (SMBO) function , see figure 38, receives logical
signal from the IED configuration, which is transferring to the real (hardware) outputs,
via the Signal Matrix Tool (SMT). The inputs in SMBO are BO1 to BO10 and they, as
well as the whole function block, can be tag-named. The name tags will appear in SMT
as information which signals shall be connected between physical IO and the SMBO.
It is important that SMBO inputs are connected when SMBOs are
connected to physical outputs through the Signal Matrix Tool. If
SMBOs are connected (in SMT) but their inputs not, all the
physical outputs will be set by default. This might cause
malfunction of primary equipment and/or injury to personnel.
90
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.10.3
Function block
SMBO
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
^BO1
^BO2
^BO3
^BO4
^BO5
^BO6
^BO7
^BO8
^BO9
^BO10
IEC05000439-2-en.vsd
IEC05000439 V2 EN
Figure 38:
4.10.4
Name
Type
Default
Description
BO1
BOOLEAN
BO2
BOOLEAN
BO3
BOOLEAN
BO4
BOOLEAN
BO5
BOOLEAN
BO6
BOOLEAN
BO7
BOOLEAN
BO8
BOOLEAN
BO9
BOOLEAN
BO10
BOOLEAN
4.11
4.11.1
Introduction
The Signal matrix for mA inputs (SMMI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see
the application manual to get information about how milliamp (mA) inputs are brought
in for one IED configuration.
91
Technical reference manual
Section 4
Basic IED functions
4.11.2
1MRK505208-UUS D
Principle of operation
The Signal matrix for mA inputs (SMMI) function, see figure 39, receives its inputs
from the real (hardware) mA inputs via the Signal Matrix Tool (SMT), and makes
them available to the rest of the configuration via its analog outputs, named AI1 to
AI6. The inputs, as well as the whole block, can be tag-named. These tags will be
represented in SMT.
The outputs on SMMI are normally connected to the IEC61850 generic
communication I/O functions (MVGGIO) function for further use of the mA signals.
4.11.3
Function block
SMMI
^VIN1
^VIN2
^VIN3
^VIN4
^VIN5
^VIN6
AI1
AI2
AI3
AI4
AI5
AI6
IEC05000440-2-en.vsd
IEC05000440 V2 EN
Figure 39:
4.11.4
Default
Description
VIn1
REAL
VIn2
REAL
VIn3
REAL
VIn4
REAL
VIn5
REAL
VIn6
REAL
Table 38:
Name
Description
AI1
REAL
AI2
REAL
AI3
REAL
92
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Name
Type
Description
AI4
REAL
AI5
REAL
AI6
REAL
4.12
4.12.1
Introduction
Signal matrix for analog inputs function (SMAI), also known as the preprocessor
function, processes the analog signals connected to it and gives information about all
aspects of the analog signals connected, like the RMS value, phase angle, frequency,
harmonic content, sequence components and so on. This information is then used by
the respective functions in ACT (for example protection, measurement or monitoring).
The SMAI function is used within PCM600 in direct relation with the Signal Matrix
tool or the Application Configuration tool.
4.12.2
Principle of operation
Every Signal matrix for analog inputs function (SMAI) can receive four analog signals
(three phases and one neutral value), either voltage or current, see figure 41 and
figure 42. SMAI outputs give information about every aspect of the 3ph analog signals
acquired (phase angle, RMS value, frequency and frequency derivates etc. 244 values
in total). The BLOCK input will reset all outputs to 0.
The output signal AI1 to AI4 are direct output of the, in SMT, connected input to
GRPx_A, GRPxB, GRPxC and GRPx_N, x=1-12. AIN is always the neutral current,
calculated residual sum or the signal connected to GRPx_N. Note that function block
will always calculate the residual sum of current/voltage if the input is not connected in
SMT. Applications with a few exceptions shall always be connected to AI3P.
4.12.3
Frequency values
The frequency functions includes a functionality based on level of positive sequence
voltage, IntBlockLevel, to validate if the frequency measurement is valid or not. If
positive sequence voltage is lower than IntBlockLevel the function is blocked.
IntBlockLevel, is set in % of VBase/3
93
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
If SMAI setting ConnectionType is Ph-Ph at least two of the inputs GRPx_A, GRPx_B
and GRPx_C must be connected in order to calculate positive sequence voltage. If
SMAI setting ConnectionType is Ph-N, all three inputs GRPx_A, GRPx_B and
GRPx_C must be connected in order to calculate positive sequence voltage.
If only one phase-phase voltage is available and SMAI setting ConnectionType is PhPh the user is advised to connect two (not three) of the inputs GRPx_A, GRPx_B and
GRPx_C to the same voltage input as shown in figure 40 to make SMAI calculating a
positive sequence voltage (that is input voltage/3).
IEC10000060-1-en.vsd
IEC10000060 V1 EN
Figure 40:
Connection example
The outputs from the above configured SMAI block shall only be used
for Overfrequency protection (SAPTOF, 81), Underfrequency
protection (SAPTUF, 81) and Rate-of-change frequency protection
(SAPFRC, 81) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.
94
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.12.4
Function block
SMAI1
BLOCK
DFTSPFC
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
TYPE
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
ANSI05000705-1-en.vsd
ANSI05000705 V1 EN
Figure 41:
BLOCK
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2_N
TYPE
AI3P
AI1
AI2
AI3
AI4
AIN
ANSI07000130-1-en.vsd
ANSI07000130 V1 EN
Figure 42:
4.12.5
Default
Description
BLOCK
BOOLEAN
Block group 1
DFTSPFC
REAL
20.0
GRP1_A
STRING
GRP1_B
STRING
GRP1_C
STRING
GRP1_N
STRING
95
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 40:
Name
Type
Description
SPFCOUT
REAL
AI3P
GROUP SIGNAL
AI1
GROUP SIGNAL
AI2
GROUP SIGNAL
AI3
GROUP SIGNAL
AI4
GROUP SIGNAL
AIN
GROUP SIGNAL
Table 41:
Name
Default
Description
BLOCK
BOOLEAN
Block group 2
GRP2_A
STRING
GRP2_B
STRING
GRP2_C
STRING
GRP2_N
STRING
Table 42:
Name
4.12.6
Description
AI3P
GROUP SIGNAL
AI1
GROUP SIGNAL
AI2
GROUP SIGNAL
AI3
GROUP SIGNAL
AI4
GROUP SIGNAL
AIN
GROUP SIGNAL
Setting parameters
Settings DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available. Internal nominal
frequency DFT reference is then the reference.
96
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 43:
Name
Values (Range)
Unit
Step
Default
Description
DFTRefExtOut
InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
InternalDFTRef
DFTReference
InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
Ph-N
TYPE
1-2
Ch
1=Voltage, 2=Current
Table 44:
Name
Values (Range)
Unit
Step
Default
Description
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
Disabled
Negation
MinValFreqMeas
5 - 200
10
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
97
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 45:
Name
Values (Range)
Unit
Step
Default
Description
DFTReference
InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
Ph-N
TYPE
1-2
Ch
1=Voltage, 2=Current
Table 46:
Name
Unit
Step
Default
Description
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
Disabled
Negation
MinValFreqMeas
5 - 200
10
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
4.13
4.13.1
Introduction
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of threephase analog signals (of the same type) for those IED functions that might need it.
4.13.2
Principle of operation
Summation block 3 phase 3PHSUM receives the three-phase signals from Signal
matrix for analog inputs function (SMAI). In the same way, the BLOCK input will
reset all the outputs of the function to 0.
98
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.13.3
Function block
3PHSUM
BLOCK
DFTSPFC
G1AI3P*
G2AI3P*
AI3P
AI1
AI2
AI3
AI4
IEC05000441-2-en.vsd
IEC05000441 V2 EN
Figure 43:
4.13.4
Default
Description
BLOCK
BOOLEAN
Block
DFTSPFC
REAL
G1AI3P
GROUP
SIGNAL
G2AI3P
GROUP
SIGNAL
Table 48:
Name
4.13.5
Description
AI3P
GROUP SIGNAL
AI1
GROUP SIGNAL
AI2
GROUP SIGNAL
AI3
GROUP SIGNAL
AI4
GROUP SIGNAL
Setting parameters
Settings DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available.
99
Technical reference manual
Section 4
Basic IED functions
Table 49:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
SummationType
Group1+Group2
Group1-Group2
Group2-Group1
-(Group1+Group2)
Group1+Group2
Summation type
DFTReference
InternalDFTRef
AdDFTRefCh1
External DFT ref
InternalDFTRef
DFT reference
Table 50:
Name
Unit
Step
Default
Description
FreqMeasMinVal
5 - 200
10
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
4.14
4.14.1
Introduction
Authority status (ATHSTAT) function is an indication function block for user log-on
activity.
4.14.2
Principle of operation
Authority status (ATHSTAT) function informs about two events related to the IED and
the user authorization:
the fact that at least one user has tried to log on wrongly into the IED and it was
blocked (the output USRBLKED)
the fact that at least one user is logged on (the output LOGGEDON)
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC 61850
station bus.
100
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.14.3
Function block
ATHSTAT
USRBLKED
LOGGEDON
IEC06000503-2-en.vsd
IEC06000503 V2 EN
Figure 44:
4.14.4
Output signals
Table 51:
Name
4.14.5
Type
Description
USRBLKED
BOOLEAN
LOGGEDON
BOOLEAN
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
4.15
4.15.1
Introduction
The Denial of service functions (DOSFRNT, DOSOEMAB and DOSOEMCD) are
designed to limit overload on the IED produced by heavy Ethernet network traffic. The
communication facilities must not be allowed to compromise the primary functionality
of the device. All inbound network traffic will be quota controlled so that too heavy
network loads can be controlled. Heavy network load might for instance be the result
of malfunctioning equipment connected to the network.
4.15.2
Principle of operation
The Denial of service functions (DOSFRNT, DOSOEMAB and DOSOEMCD)
measures the IED load from communication and, if necessary, limit it for not
jeopardizing the IEDs control and protection functionality due to high CPU load. The
function has the following outputs:
101
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
4.15.3
Function blocks
DOSFRNT
LINKUP
WARNING
ALARM
IEC09000749-1-en.vsd
IEC09000749 V1 EN
Figure 45:
DOSOEMAB
LINKUP
WARNING
ALARM
IEC09000750-1-en.vsd
IEC09000750 V1 EN
Figure 46:
DOSOEMCD
LINKUP
WARNING
ALARM
IEC09000751-1-en.vsd
IEC09000751 V1 EN
Figure 47:
4.15.4
Signals
Table 52:
Name
Description
LINKUP
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
102
Technical reference manual
Section 4
Basic IED functions
1MRK505208-UUS D
Table 53:
Name
Type
Description
LINKUP
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
Table 54:
Name
4.15.5
Description
LINKUP
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
Settings
The function does not have any parameters available in the local HMI or PCM600.
103
Technical reference manual
104
Section 5
Differential protection
1MRK505208-UUS D
Section 5
Differential protection
5.1
IEC 61850
identification
BUTPTRC
IEC 60617
identification
3Id/I
ANSI/IEEE C37.2
device number
87B
SYMBOL-JJ V1 EN
BTCZPDIF
3Id/I
87B
SYMBOL-JJ V1 EN
BTZNPDIF
3Id/I
87B
SYMBOL-JJ V1 EN
BTZNPDIF
3Id/I
87B
SYMBOL-JJ V1 EN
BZITGGIO
3Id/I
87B
SYMBOL-JJ V1 EN
105
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
IEC 61850
identification
BUSPTRC
IEC 60617
identification
3Id/I
ANSI/IEEE C37.2
device number
87B
SYMBOL-JJ V1 EN
BCZSPDIF
3Id/I
87B
SYMBOL-JJ V1 EN
BZNSPDIF
3Id/I
87B
SYMBOL-JJ V1 EN
BZNSPDIF
3Id/I
87B
SYMBOL-JJ V1 EN
BZISGGIO
3Id/I
87B
SYMBOL-JJ V1 EN
IEC 61850
identification
SWSGGIO
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
106
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
5.1.1
Introduction
IED is designed for the selective, reliable and fast differential protection of busbars, Tconnections and meshed corners. IED can be used for different switchgear layouts,
including single and double busbar with or without transfer bus, double circuit breaker
or breaker-and-a-half stations. The IED is applicable for the protection of medium
voltage (MV), high voltage (HV) and extra high voltage (EHV) installations at a power
system frequency of 50Hz or 60Hz. The IED can detect all types of internal phase-tophase and phase-to-ground faults in solidly earthed or low impedance grounded power
systems, as well as all internal multi-phase faults in isolated or high-impedance
grounded power systems.
5.1.1.1
Available versions
The following versions of the IED are available:
1.
2.
3.
4.
This version is available in full 19 case. The IED is intended for busbar
protection applications in big substation where dynamic Zone Selection,
107
Section 5
Differential protection
1MRK505208-UUS D
5.1.2
quite large number of binary inputs and outputs and many CT inputs are
needed. The IED includes two differential zones and twenty-four CT inputs.
This version can be optionally used with external auxiliary summation
transformers.
Principle of operation
Busbar differential protection detects internal faults within the station. In order to do
that selectively it often incorporates more than one differential protection-measuring
element. These differential protection-measuring elements are often called protection
zones in relay protection literature. On the other hand, the protection function is quite
specific, because typically all CTs in the station are connected to it. It is, therefore, of
outmost importance that individually connected CT inputs are appropriately routed to
the relevant protection zone. Sometimes these connections need to be dynamically
changed in accordance with the actual connections within the station. Therefore, the
busbar differential protection has two essential parts:
1.
2.
It is also important to understand that all function blocks described in the next sections,
except the Switch Status function block, are not independent from each other. Hidden
connections are pre-made in the software in order to simplify the required engineering
work in PCM600 for the end user.
5.1.3
Differential protection
This part of busbar protection consists of differential protection algorithm, sensitive
differential protection algorithm, check zone algorithm, open CT algorithm and two
supervision algorithms. It is presented to the end user as three function blocks:
1.
2.
3.
5.1.4
Zone A
Zone B (functionality wise completely identical to the Zone A)
Check Zone
108
Technical reference manual
1MRK505208-UUS D
Section 5
Differential protection
provided with a restraint feature. The minimum pick-up value for the differential
current is set to give a suitable sensitivity for all internal faults. For busbar protection
applications typical setting value for the minimum differential operating current is
from 50% to 150% of the biggest CT. This setting is made directly in primary amperes.
The operating slope for the differential operating characteristic is fixed to 53% in the
algorithm. The fast tripping time of the low-impedance differential protection function
is especially advantages for power system networks with high fault levels or where fast
fault clearance is required for power system stability. The advanced open CT detection
algorithm detects instantly the open CT secondary circuits and prevents differential
protection operation without any need for additional check zone.
Differential protection zones include a sensitive operational level. This sensitive
operational level is designed to be able to detect internal busbar ground faults in low
impedance grounded power systems (that is, power systems where the ground-fault
current is limited to a certain level, typically between 300A and 2000A primary by a
neutral point reactor or resistor). Alternatively, this sensitive level can be used when
high sensitivity is required from busbar differential protection (that is, energizing of the
bus via long line).
Overall operating characteristic of Busbar differential protection is shown in figure 48.
109
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Id [Primary Amps]
Sensitive
differential
protection
I in
I d=
Operate
region
Differential protection
operation characteristic
Diff Oper Level
Sensitive Oper Level
Figure 48:
Operating characteristic
Where:
Iin
Iin represents the RMS value of the incoming current to the differential protection zone
Id
Id represents the RMS value of the differential current of the differential protection zone
s = 0.53 the operating slope for the differential function is fixed to 0.53 in the algorithm and can not be
changed by the user
5.1.4.1
Open CT detection
The innovative measuring algorithm provides stability for open or short-circuited main
CT secondary circuits, which means that no separate check zone is actually necessary.
Pick-up current for open CT detection can usually be set to detect the open circuit
condition for the smallest CT. This built-in feature allows the protection terminal to be
set very sensitive, even to a lower value than the maximum CT primary rating in the
station. At detection of problems in CT secondary circuits, the differential protection
can be instantly blocked and an alarm is given. Alternatively, the differential protection
can be automatically desensitized in order to ensure busbar differential protection
stability during normal through-load condition. When problems in CT secondary
circuits have been found and associated error has been corrected a manual reset must
be given to the IED. This can be done locally from the local HMI, or remotely via
binary input or communication link.
110
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
However, it is to be noted that this feature can only be partly utilized when the
summation principle is in use.
5.1.4.2
5.1.4.3
BLOCK, when this binary input has logical value one all trip commands from the
zone are prevented
BLKST, when this binary input has logical value one the differential protection
within the zone is blocked (that is, can not operate)
TRZONE, when this binary input has logical value one forced external trip will be
given from the zone
RSTTRIP, when this binary input has logical value one latched trip from the zone
will be re-set back to zero. Whether zone trip is in Latched or SelfReset mode is
defined by a parameter setting DiffTripOut
RSTOCT, when this binary input has logical value one OCT latched signals and
possible blocking will be re-set. It is to be noted that it is possible to do this only if
the zone differential current has lower value then defined by a parameter
DiffOperLevel
ENSENS, when this binary input has logical value one the sensitive differential
protection feature within the zone is allowed to operate in accordance with its
settings (for example, connect here the pickup signal from open delta overvoltage
relay in impedance grounded system)
Check zone
supervision
TRIP
TRIPLX
TREXTBA
Y
TREXTZ
TRSENS
I>DiffOperLevel
Off
Yes
Yes
BFP BU Trip
Off
Yes
Yes
Yes
111
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
TRZONE Input
activated
Off
Yes
Yes
Yes
I>SensOperLevel +
ENSENS activated
Off
Yes
Yes
Yes
I>DiffOperLevel
without CheckZone
operation
On
Yes
I>DiffOperLevel with
CheckZone
operation
On
Yes
Yes
BFP BU Trip
On
Yes
Yes
Yes
TRZONE Input
activated
On
Yes
Yes
Yes
I>SensOperLevel +
ENSENS activated
On
Yes
Yes
Yes
TRIP, this binary output is used as general trip command from the zone. It is
activated when either differential protection operates or sensitive differential
protection operates or for any external trip signal (that is, either from the
individual bays connected to the zone or via TRZONE input).
TRIP_X, this binary output has logical value one whenever zone TRIP output
signal is initiated (only available in 1Ph-version)
TRIP_A, TRIP_B, TRIP_C, these binary outputs has logical value one whenever
zone TRIP output signal is initiated (only available in 3Ph-version)
TREXTBAY, this binary output has logical value one whenever zone TRIP output
signal is initiated by operation of the external trip signal from one of the connected
bays. In most cases this will in practice mean operation of back-up trip command
from the breaker failure protection in that bay
TREXTZ, this binary output has logical value one whenever zone TRIP output
signal is initiated externally via input TRZONE
TRSENS, this binary output has logical value one whenever zone TRIP output
signal is initiated by operation of the sensitive differential protection algorithm
(only available in 1Ph-version)
TRSENS_A(B,C), this binary output has logical value one whenever zone TRIP
output signal is initiated by operation of the sensitive differential protection
algorithm in the corresponding phase (only available in 3Ph-version)
OCT, this binary output is used as general Open CT detection signal from the
zone. It is activated when either fast or slow OCT algorithm operates.
SOCT, this binary output has logical value one whenever zone OCT output signal
is initiated by operation of the slow OCT algorithm (only available in 1Ph-version)
SOCT_A(B,C), this binary output has logical value one whenever zone OCT
output signal is initiated by operation of the slow OCT algorithm in the
corresponding phase (only available in 3Ph-version)
112
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
FOCT, this binary output has logical value one whenever zone OCT output signal
is initiated by operation of the fast OCT algorithm (only available in 1Ph-version)
FOCT_A(B,C), this binary output has logical value one whenever zone OCT
output signal is initiated by operation of the fast OCT algorithm in the
corresponding phase (only available in 3Ph-version)
ALDIFF, this binary output has logical value one whenever differential current
supervision algorithm operates (only available in 1Ph-version)
ALDIFF_A(B,C), this binary output has logical value one whenever differential
current supervision algorithm operates in the corresponding phase (only available
in 3Ph-version)
ALIIN, this binary output has logical value one whenever incoming current
supervision algorithm operates (only available in 1Ph-version)
ALIIN_A(B,C), this binary output has logical value one whenever incoming
current supervision algorithm operates in the corresponding phase (only available
in 3Ph-version)
IIN, this output represents internally calculated instantaneous (sample based)
incoming current. It can be connected to the disturbance recorder function in order
to record it during external and internal faults (only available in 1Ph-version)
IIN_A(B,C), this output represents phase wise internally calculated instantaneous
(sample based) incoming current. It can be connected to the disturbance recorder
function in order to record it during external and internal faults (only available in
3Ph-version)
ID, this output represents internally calculated instantaneous (sample based)
differential current. It can be connected to the disturbance recorder function in
order to record it during external and internal faults (only available in 1Ph-version)
IID_A(B,C), this output represents phase wise internally calculated instantaneous
(sample based) differential current. It can be connected to the disturbance recorder
function in order to record it during external and internal faults (only available in
3Ph-version)
IIN_ZA, this output represents internally calculated RMS value of the incoming
current. It can be connected to the disturbance recorder function in order to record
it during external and internal faults (only available in 1Ph-version)
IIN_ZA_A(B,C), this output represents phase wise internally calculated RMS
value of the incoming current. It can be connected to the disturbance recorder
function in order to record it during external and internal faults (only available in
3Ph-version)
IINRANGE, this output represents internally calculated RMS value of the
incoming current. It can be connected to the measurement expander block for
value reporting via IEC 61850 (only available in 1Ph-version)
IINRNG_A(B,C), this output represents phase wise internally calculated RMS
value of the incoming current. It can be connected to the measurement expander
block for value reporting via IEC 61850 (only available in 3Ph-version)
ID_ZA, this output represents internally calculated RMS value of the differential
current. It can be connected to the disturbance recorder function in order to record
it during external and internal faults (only available in 1Ph-version)
113
Section 5
Differential protection
1MRK505208-UUS D
ID_ZA_A(B,C), this output represents phase wise internally calculated RMS value
of the differential current. It can be connected to the disturbance recorder function
in order to record it during external and internal faults (only available in 3Ph-version)
IDRANGE, this output represents internally calculated RMS value of the
differential current. It can be connected to the measurement expander block for
value reporting via IEC 61850 (only available in 1Ph-version)
IDRNG_A(B,C), this output represents phase wise internally calculated RMS
value of the differential current. It can be connected to the measurement expander
block for value reporting via IEC 61850 (only available in 3Ph-version)
IDFRMS, this output represents internally calculated fundamental frequency RMS
value of the differential current. It can be connected to the disturbance recorder
function in order to record it during external and internal faults (only available in
1Ph-version)
IDFRMS_A(B,C), this output represents phase wise internally calculated
fundamental frequency RMS value of the differential current. It can be connected
to the disturbance recorder function in order to record it during external and
internal faults (only available in 3Ph-version)
DiffOperLevel: this setting determines the minimum pickup level for the
differential feature. It shall be entered directly in primary amperes. Default value
1000A
DiffTripOut: this setting determines how the trip output from the zone shall
behave. One of the following two alternatives shall be selected for every function
block:
1.
2.
SelfReset: when this mode is selected the zone TRIP output will reset to
logical value zero after the pre-set time determined by the setting parameter
tTripHold.
Latched: when this mode is selected the zone TRIP output will latched and it
will require manual re-set command. This reset command can be given from
local HMI or via communication link
tTripHold: defines the drop-off time for the TRIP signal in the SelfReset mode of
operation. Time delay can be set from 0.000s to 60.000s in step of 0.001s. Default
value is 0.200s
CheckZoneSup: this setting determines whether the busbar protection zone
differential algorithm is supervised by the operation of the built-in Check Zone or
not. One of the following two alternatives shall be selected for every function block:
114
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
1.
2.
SlowOCTOper: this setting determines operation of the slow OCT algorithm. One
of the following three alternatives shall be selected for every function block:
1.
2.
3.
3.
Off: when this mode is selected the slow OCT feature is completely disabled
Block: when this mode is selected the operation of the slow OCT feature
completely blocks the operation of the differential protection. It shall be
noted that this blocking is selective (that is, zone and phase wise)
Supervise: when this mode is selected the operation of the slow OCT feature
only supervises the operation of the differential protection. As soon as
differential current is bigger than the pre-set level determined by the setting
parameter OCTReleaseLev the differential function will be again allowed to
operate.
FastOCTOper: this setting determines operation of the fast OCT algorithm. One of
the following three alternatives shall be selected for every function block:
1.
2.
On: when this mode is selected the zone differential trip is supervised by the
operation of the built-in Check Zone
Off: when this mode is selected the zone differential trip is not supervised by
the operation of the built-in Check Zone
Off: when this mode is selected the fast OCT feature is completely disabled
Block: when this mode is selected the operation of the fast OCT feature
completely blocks the operation of the differential protection. It shall be
noted that this blocking is selective (that is, zone and phase wise)
Supervise: when this mode is selected the operation of the fast OCT feature
only supervises the operation of the differential protection. As soon as
differential current is bigger than the pre-set level determined by the setting
parameter OCTReleaseLev the differential function will be again allowed to
operate
OCTOperLevel: this setting determines the minimum pickup level for the slow and
fast OCT feature. It shall be entered directly in primary amperes. Default value 200A.
tSlowOCT: this delay on pickup timer is used in order to delay the action of the
slow OCT algorithm. Time delay can be set from 0.00s to 6000.00s in step of
0.01s. Default value is 20.00s. Minimum setting should always be above 1 s
OCTReleaseLev: this setting determines the differential current level above which
the OCT feature will again allow the differential protection operation, when OCT
feature is used in the Supervise mode of the operation. It is to be entered directly in
primary amperes. Default value 2500A
IdAlarmLev: this setting determines the differential current level above which the
alarm is given after the pre-set time determined by the parameter setting tIdAlarm.
It shall be entered directly in primary amperes. Default value 200A.
tIdAlarm: this delay on pickup timer is used in order to delay the action of the
differential alarm feature. Time delay can be set from 0.00s to 6000.00s in step of
0.01s. Default value is 30.00s
IinAlarmLev: this setting determines the incoming current level (bus throughgoing current level) above which the alarm is given instantaneously. It is to be
entered directly in primary amperes. Default value 3000A
115
Section 5
Differential protection
1MRK505208-UUS D
SensOperLevel: this setting determines the minimum pickup level for the sensitive
differential algorithm. It shall be entered directly in primary amperes. Default
value 200A.
SensIinBlock: this setting determines the incoming current level (bus throughgoing current level) above which the sensitive differential algorithm is
automatically blocked. It shall be entered directly in primary amperes. Default
value 1000A
tSensDiff: this delay on pickup timer is used in order to delay the action of the
sensitive differential algorithm. Time delay can be set from 0.000s to 60.000s in
step of 0.001s. Default value is 0.400s
116
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
5.1.4.4
Function block
BTZABZNTPDIF_87B
BLOCK
BLKST
TRZONE
RSTTRIP
RSTOCT
ENSENS
TRIP
TRIP_A
TRIP_B
TRIP_C
TREXTBAY
TREXTZ
TRSENS_A
TRSENS_B
TRSENS_C
OCT
SOCT_A
SOCT_B
SOCT_C
FOCT_A
FOCT_B
FOCT_C
ALDIFF_A
ALDIFF_B
ALDIFF_C
ALIIN_A
ALIIN_B
ALIIN_C
IIN_ZA_A
IINRNG_A
IIN_ZA_B
IINRNG_B
IIN_ZA_C
IINRNG_C
ID_ZA_A
IDRNG_A
ID_ZA_B
IDRNG_B
ID_ZA_C
IDRNG_C
IDFRMS_A
IDFRMS_B
IDFRMS_C
en06000159_ansi.vsd
ANSI06000159 V1 EN
Figure 49:
117
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
BSZABZNSPDIF_87B
BLOCK
BLKST
TRZONE
RSTTRIP
RSTOCT
ENSENS
TRIP
TRIP_X
TREXTBAY
TREXTZ
TRSENS
OCT
SOCT
FOCT
ALDIFF
ALIIN
IIN_ZA
IINRANGE
ID_ZA
IDRANGE
IDFRMS
en06000160_ansi.vsd
ANSI06000160 V1 EN
Figure 50:
5.1.4.5
Default
Description
BLOCK
BOOLEAN
BLKST
BOOLEAN
TRZONE
BOOLEAN
RSTTRIP
BOOLEAN
RSTOCT
BOOLEAN
ENSENS
BOOLEAN
Table 56:
Name
Description
TRIP
BOOLEAN
TRIP_A
BOOLEAN
TRIP_B
BOOLEAN
TRIP_C
BOOLEAN
TREXTBAY
BOOLEAN
TREXTZ
BOOLEAN
TRSENS_A
BOOLEAN
TRSENS_B
BOOLEAN
TRSENS_C
BOOLEAN
Section 5
Differential protection
1MRK505208-UUS D
Name
Type
Description
OCT
BOOLEAN
SOCT_A
BOOLEAN
SOCT_B
BOOLEAN
SOCT_C
BOOLEAN
FOCT_A
BOOLEAN
FOCT_B
BOOLEAN
FOCT_C
BOOLEAN
ALDIFF_A
BOOLEAN
ALDIFF_B
BOOLEAN
ALDIFF_C
BOOLEAN
ALIIN_A
BOOLEAN
ALIIN_B
BOOLEAN
ALIIN_C
BOOLEAN
IIN_ZA_A
REAL
IINRNG_A
INTEGER
IIN_ZA_B
REAL
IINRNG_B
INTEGER
IIN_ZA_C
REAL
IINRNG_C
INTEGER
ID_ZA_A
REAL
IDRNG_A
INTEGER
ID_ZA_B
REAL
IDRNG_B
INTEGER
ID_ZA_C
REAL
IDRNG_C
INTEGER
IDFRMS_A
REAL
IDFRMS_B
REAL
IDFRMS_C
REAL
Table 57:
Name
Default
Description
BLOCK
BOOLEAN
BLKST
BOOLEAN
TRZONE
BOOLEAN
RSTTRIP
BOOLEAN
RSTOCT
BOOLEAN
ENSENS
BOOLEAN
Section 5
Differential protection
1MRK505208-UUS D
Table 58:
Name
5.1.4.6
Type
Description
TRIP
BOOLEAN
TRIP_X
BOOLEAN
TREXTBAY
BOOLEAN
TREXTZ
BOOLEAN
TRSENS
BOOLEAN
OCT
BOOLEAN
SOCT
BOOLEAN
FOCT
BOOLEAN
ALDIFF
BOOLEAN
ALIIN
BOOLEAN
IIN_ZA
REAL
IINRANGE
INTEGER
ID_ZA
REAL
IDRANGE
INTEGER
IDFRMS
REAL
Setting parameters
All general settings for Busbar differential protection are only relevant for proper event
reporting via IEC 61850-8-1. They are not important for proper operation of Busbar
differential protection.
Note that all settings for busbar protection under relevant parameter setting group are
directly related to proper operation of the Busbar differential protection.
Table 59:
Name
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
DiffOperLev
1 - 99999
1000
DiffTripOut
SelfReset
Latched
SelfReset
tTripHold
0.000 - 60.000
0.001
0.200
CheckZoneSup
Disabled
Enabled
Disabled
Section 5
Differential protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
SlowOCTOper
Disabled
Block
Supervise
Block
FastOCTOper
Disabled
Block
Supervise
Block
OCTOperLev
1 - 99999
200
tSlowOCT
0.00 - 6000.00
0.01
20.00
OCTReleaseLev
1 - 99999
2500
IdAlarmLev
1 - 99999
200
tIdAlarm
0.00 - 6000.00
0.01
30.00
IinAlarmLev
1 - 99999
3000
SensDiffOper
Disabled
Enabled
Disabled
SensOperLev
1 - 99999
200
SensIinBlock
1 - 99999
1000
tSensDiff
0.000 - 60.000
0.001
0.400
Table 60:
Name
Values (Range)
Unit
Step
Default
Description
IIN_A db
0 - 300
s,%,%s
10
IIN_A zeroDb
0 - 100000
500
IIN_A hhLim
0.000 10000000000.000
0.001
5000.000
IIN_A hLim
0.000 10000000000.000
0.001
3000.000
High limit
IIN_A lLim
0.000 10000000000.000
0.001
100.000
Low limit
IIN_A llLim
0.000 10000000000.000
0.001
50.000
IIN_A min
0.000 10000000000.000
0.001
25.000
Minimum value
IIN_A max
0.000 10000000000.000
0.001
6000.000
Maximum value
121
Technical reference manual
Section 5
Differential protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
IIN_A dbType
Cyclic
Dead band
Int deadband
Dead band
IIN_A limHys
0.000 - 100.000
0.001
5.000
IIN_B db
0 - 300
s,%,%s
10
IIN_B zeroDb
0 - 100000
500
IIN_B hhLim
0.000 10000000000.000
0.001
5000.000
IIN_B hLim
0.000 10000000000.000
0.001
3000.000
High limit
IIN_B lLim
0.000 10000000000.000
0.001
100.000
Low limit
IIN_B llLim
0.000 10000000000.000
0.001
50.000
IIN_B min
0.000 10000000000.000
0.001
25.000
Minimum value
IIN_B max
0.000 10000000000.000
0.001
6000.000
Maximum value
IIN_B dbType
Cyclic
Dead band
Int deadband
Dead band
IIN_B limHys
0.000 - 100.000
0.001
5.000
IIN_C db
0 - 300
s,%,%s
10
IIN_C zeroDb
0 - 100000
500
IIN_C hhLim
0.000 10000000000.000
0.001
5000.000
IIN_C hLim
0.000 10000000000.000
0.001
3000.000
High limit
IIN_C iLim
0.000 10000000000.000
0.001
100.00
Low limit
IIN_C llLim
0.000 10000000000.000
0.001
50.000
IIN_C min
0.000 10000000000.000
0.001
25.000
Minimum value
IIN_C max
0.000 10000000000.000
0.001
6000.000
Maximum value
IIN_C dbType
Cyclic
Dead band
Int deadband
Dead band
122
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
IIN_C limHys
0.000 - 100.000
0.001
5.000
ID_A db
0 - 300
s,%,%s
10
ID_A zeroDb
0 - 100000
500
ID_A hhLim
0.000 10000000000.000
0.001
5000.000
ID_A hLim
0.000 10000000000.000
0.001
3000.000
High limit
ID_A lLim
0.000 10000000000.000
0.001
100.000
Low limit
ID_A llLim
0.000 10000000000.000
0.001
50.000
ID_A min
0.000 10000000000.000
0.001
25.000
Minimum value
ID_A max
0.000 10000000000.000
0.001
6000.000
Maximum value
ID_A dbType
Cyclic
Dead band
Int deadband
Dead band
ID_A limHys
0.000 - 100.000
0.001
5.000
ID_B db
0 - 300
s,%,%s
10
ID_B zeroDb
0 - 100000
500
ID_B hhLim
0.000 10000000000.000
0.001
5000.000
ID_B hLim
0.000 10000000000.000
0.001
3000.000
High limit
ID_B lLim
0.000 10000000000.000
0.001
100.000
Low limit
ID_B llLim
0.000 10000000000.000
0.001
50.000
ID_B min
0.000 10000000000.000
0.001
25.000
Minimum value
ID_B max
0.000 10000000000.000
0.001
6000.000
Maximum value
ID_B dbType
Cyclic
Dead band
Int deadband
Dead band
ID_B limHys
0.000 - 100.000
0.001
5.000
ID_C db
0 - 300
s,%,%s
10
Section 5
Differential protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
ID_C zeroDb
0 - 100000
500
ID_C hhLim
0.000 10000000000.000
0.001
5000.000
ID_C hLim
0.000 10000000000.000
0.001
3000.000
High limit
ID_C lLim
0.000 10000000000.000
0.001
100.000
Low limit
ID_C llLim
0.000 10000000000.000
0.001
50.000
ID_C min
0.000 10000000000.000
0.001
25.000
Minimum value
ID_C max
0.000 10000000000.000
0.001
6000.000
Maximum value
ID_C dbType
Cyclic
Dead band
Int deadband
Dead band
ID_C limHys
0.000 - 100.000
0.001
5.000
Table 61:
Name
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
DiffOperLev
1 - 99999
1000
DiffTripOut
SelfReset
Latched
SelfReset
tTripHold
0.000 - 60.000
0.001
0.200
CheckZoneSup
Disabled
Enabled
Disabled
SlowOCTOper
Disabled
Block
Supervise
Block
FastOCTOper
Disabled
Block
Supervise
Block
OCTOperLev
1 - 99999
200
tSlowOCT
0.00 - 6000.00
0.01
20.000
OCTReleaseLev
1 - 99999
2500
IdAlarmLev
1 - 99999
200
Section 5
Differential protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
tIdAlarm
0.00 - 6000.00
0.01
30.000
IinAlarmLev
1 - 99999
3000
SensDiffOper
Disabled
Enabled
Disabled
SensOperLev
1 - 99999
200
SensIinBlock
1 - 99999
1000
tSensDiff
0.000 - 60.000
0.001
0.400
Table 62:
Description
Name
Values (Range)
Unit
Step
Default
Description
IIN db
0 - 300
s,%,%s
10
IIN zeroDb
0 - 100000
500
IIN hhLim
0.000 10000000000.000
0.001
5000.000
IIN hLim
0.000 10000000000.000
0.001
3000.000
High limit
IIN lLim
0.000 10000000000.000
0.001
100.000
Low limit
IIN llLim
0.000 10000000000.000
0.001
50.000
IIN min
0.000 10000000000.000
0.001
25.000
Minimum value
IIN max
0.000 10000000000.000
0.001
6000.000
Maximum value
IIN dbType
Cyclic
Dead band
Int deadband
Dead band
IIN limHys
0.000 - 100.000
0.001
5.000
ID db
0 - 300
s,%,%s
10
ID zeroDb
0 - 100000
500
ID hhLim
0.000 10000000000.000
0.001
5000.000
ID hLim
0.000 10000000000.000
0.001
3000.000
High limit
Section 5
Differential protection
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
ID lLim
0.000 10000000000.000
0.001
100.000
Low limit
ID llLim
0.000 10000000000.000
0.001
50.000
ID min
0.000 10000000000.000
0.001
25.000
Minimum value
ID max
0.000 10000000000.000
0.001
6000.000
Maximum value
ID dbType
Cyclic
Dead band
Int deadband
Dead band
ID limHys
0.000 - 100.000
0.001
5.000
5.1.5
Calculation principles
5.1.5.1
General
The calculation of relevant quantities from the CT input values are performed by the
IED and passed to the Busbar differential protection and open CT algorithm for further
processing.
These calculations are completely phase-segregated. Therefore, they can be explained
for one phase only. Calculations for other two phases are done in exactly the same way.
The prerequisites for correct calculations are:
The instantaneous differential current is calculated as absolute value of the sum of all
currents connected to the protection zone:
126
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
ij
id =
j=1
EQUATION1141 V1 EN
(Equation 1)
Where:
id
ij
instantaneous current value (that is, latest sample value) for bay j
The sum of all latest current samples with positive value is made:
M
ij
SP =
j= 1
EQUATION1143 V1 EN
(Equation 2)
Where:
M
number of bays with positive value of the latest current sample (M<N)
as well as the absolute value of the sum of all latest negative current samples:
N
SN =
ij
j = M+1
EQUATION1142 V1 EN
(Equation 3)
Now the instantaneous incoming and outgoing currents are calculated as follows:
iin = max {SP,SN}
iout = min {SP, SN}
All these quantities are calculated for every set of samples (that is, 20 times in one
power system cycle in the IED). It is to be noted that all three quantities (that is, iin, iout
& id) will be of a DC nature in time (that is, these quantities can only be positive).
This means that the instantaneous incoming current during normal load condition looks
like as the output of the full wave rectifier. Note that iin is always bigger than or equal
to iout.
127
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Figure 51 shows the comparison between above calculated quantities and REB103 (or
RADSS) design:
N
IR1
SR
RZ2
Z1
TMD
TMZ
RD3
AR
Vd3
IL io u t
Z1
D2
DR
Id 1 id
RD11
IT 3 i in
VS
IR2
en06000134_ansi.vsd
ANSI06000134 V1 EN
Figure 51:
Where:
iout
instantaneous outgoing current from the zone of protection (calculated from raw samples)
id
iin
instantaneous incoming current into the zone of protection (calculated from raw samples)
This means that any differential protection zone in the IED can be represented as
shown in figure 52, regardless the number of the connected feeders.
iin
Differential
Protection Zone
iout
id
en04000229.vsd
IEC04000229 V1 EN
Figure 52:
The instantaneous quantities are constantly changing in time, therefore, RMS values of
the incoming, outgoing and differential currents (that is, Iin, Iout and Id respectively)
are used in the algorithm. These quantities are calculated over last power system cycle
(that is, 16.66ms long, moving window for 60Hz system). The only requirement for
128
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
this type of calculation is that the last twenty samples of the instantaneous quantity
must be stored in the IED internal memory. The calculated values of Iin and Id are
available as service values on local HMI.
When all six values (that is, iin, iout, id, Iin, Iout and Id) are calculated, they are passed
further to the general differential protection function and open CT algorithm for further
processing to the differential and open CT algorithms.
CT saturation
Differential relays do not measure directly the primary currents in the high voltage
conductors, but the secondary currents of magnetic core current transformers, which
are installed in all high-voltage bays. Because the current transformer is a non-linear
measuring device, under high current conditions in the primary CT circuit, the
secondary CT current can be drastically different from the original primary current.
This is caused by CT saturation, a phenomenon that is well known to protection
engineers. This phenomenon is especially relevant for bus differential protection
applications, because it has the tendency to cause unwanted operation of the
differential relay.
Another difficulty is the large number of main CTs (that is, up to 24x3 for REB670
single phase and up to 8x3 CTs for REB670 three phase version) which can be
connected to the differential IED. If the CT saturation has to be checked and preventive
measures taken for every HV CT connected to the protection zone on one-by-one basis,
the differential relay algorithm would be slow and quite complex. Therefore, only the
properties of incoming, outgoing and differential currents are used in order to cope
with CT saturation of any main CT connected to the IED as shown in figure 53.
129
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
id
iin
iout
CT saturation compensation logic
Id
Id_mod
Iin
Iout
en01000148.vsd
IEC01000148 V1 EN
Figure 53:
Tripping criteria
130
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
These tripping conditions are then arranged in an AND gate in order to provide final
trip signal to the binary output contacts of the terminal.
The trip from differential zone can be either latched or self rest in accordance with end
user settings. Figure 54 shows the simplified internal trip logic for the busbar protection.
131
Technical reference manual
Section 5
Differential protection
TRZONE
tripZoneA from Bay01
tripZoneA from Bay02
1MRK505208-UUS D
TREXTZ
TREXTBAY
OR
...
tripZoneA from Baynn
OR
SensDiffOper = On
ENSENS
Iin
a
a>b
b
Id
SensIinBlock
SensOperLevel
0
3s
TRSENS
AND 0-tSensDiff
0
a>b
b
BLKST
ZA Diff Algorithm
Id
AND
TRIP_X
OR
OR
Iin
OCTBlock
CheckZoneSup = Off
CZTrip
OR
AND
OR
BLOCK
AND
Operation = On
0
0-tTripHold
AND
RSTTRIP
AND
AND
OR
TRIP
R
ZATrip-cont.
DiffTripOper = Latched
en06000072_ansi.vsd
ANSI06000072 V1 EN
Figure 54:
Section 5
Differential protection
1MRK505208-UUS D
user settable level. This feature can for example be used to design automatic reset logic
for previously described open CT detection feature. The second monitoring feature
operates immediately when the busbar through-going current is bigger than the user
settable level. Both of these monitoring features are phase segregated and they give out
binary signals, which can be either used to trigger disturbance recorder or for alarming
purposes.
Id
IdAlarmLev
Iin
IinAlarmLev
a
b
a>b
ALDIFF
0-tIdAlarm
0
ALIIN
a>b
en06000071_ansi.vsd
ANSI06000071 V1 EN
Figure 55:
5.1.5.2
Open CT detection
The three input quantities into the open CT detection algorithm are:
It is to be noted that the open CT detection algorithm does not know the number of
connected CT inputs into the IED.
The open CT detection algorithm is completely phase-segregated. Therefore, it is
explained for one phase only.
Fast operating open CT detection logic instantly detects the moment when a healthy
CT secondary circuit carrying the load current is accidently opened (that is, current
interrupted to the differential relay). The logic is based on the perception that the total
busbar through-load current is the same before and after that CT is open circuited.
In order to prevent false operation of this logic in case of a fault or disturbance in the
power system, the total through-load current must not have big changes three seconds
before the open CT condition is detected.
When one CT secondary circuit is open circuited during normal through-load condition
one measuring point is lost and, therefore, the following should hold true:
133
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
When all above conditions are simultaneously detected open CT condition is declared,
the trip output of the affected phase is blocked and alarm output is set
It is to be noted that this logic can only detect an instant of time when an already
connected CT with the secondary load current is open circuited. This logic do not
detect, for example, the situation when a new bay is connected to the differential zone,
but its CT secondary circuits are short circuited or open circuited.
Slow operating open CT detection logic will detect most abnormalities in the CT
secondary circuits or in the Zone Selection logic, but with the time delay determined
by setting parameter tSlowOCT. The logic is based on the perception that the values of
Iin and Iout shall be equal during normal through-load situation.
This logic will operate when:
there was not any big through-load current change during last five seconds
value of Iin is much bigger than value of Iout (0.9Iin > Iout)
Id > OCTOperLevel
When these conditions are fulfilled for longer than time defined by the tSlowOCT
parameter, the open CT condition is declared.
Note that the setting of tSlowOCT should always be longer than 1 s.
134
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
SlowOCTOper=Off
Slow OCT Algorithm
Id
a
b
OCTOperLevel
0-tSlowOCT
0
AND
a>b
AND
SOCT
S
R
FastOCTOper=Off
Fast OCT Algorithm
Id
a
b
OCTOperLevel
AND
a>b
AND
FOCT
S
R
100ms
RSTOCT
AND
Id
a
b
DiffOperLevel
a>b
OR
SlowOCTOper=
Supervise
AND
Id
a
b
OCTReleaseLev
a>b
FastOCTOper=
Supervise
AND
Id
a
b
OCTReleaseLev
OR
OCT
AND
OCTBlock-cont.
a>b
en06000074_ansi.vsd
ANSI06000074 V1 EN
Figure 56:
5.1.6
5.1.6.1
Introduction
For busbar protection in double busbar stations when dynamic zone selection is
needed, it is sometimes required to include the overall differential zone (that is, check
zone). Hence, the built-in, overall check zone is available in the IED. Because the builtin check zone current measurement is not dependent on the disconnector status, this
135
Section 5
Differential protection
1MRK505208-UUS D
feature ensures stability of Busbar differential protection even for completely wrong
status indication from the busbar disconnectors. It is to be noted that the overall check
zone, only supervise the usual differential protection operation. The external trip
commands, breaker failure backup-trip commands and sensitive differential protection
operation are not supervised by the overall check zone.
The overall check zone has simple current operating algorithm, which ensures check
zone operation for all internal faults regardless the fault current distribution. To
achieve this, the outgoing current from the overall check zone is used as restraint
quantity. If required, the check zone operation can be activated externally by a binary
signal.
Id [Primary Amps]
Oper Level
Operate
region
s=0.0-0.90 (settable)
Figure 57:
5.1.6.2
When EXTTRIP binary input has logical value one, operation of the check zone is
forced (that is, TRIP output signal set to one). Therefore, this signal can be used to
connect other release criteria (for example, pickup signal from external undervoltage
IED) .
136
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
TRIP, this binary output is used as general trip command from the check zone. It is
activated when either differential protection in check zone operates or when
external signal EXTTRIP is set one.
TR_x, this binary output has logical value one whenever check zone TRIP output
signal is initiated by operation of the differential protection in the corresponding
phase (only available in 3Ph-version)
IIN, this is output which represents internally calculated instantaneous (sample
based) incoming current. It can be connected to the disturbance recorder function
in order to record it during external and internal faults (only available in 1Ph-version)
IIN_x, this is output which represents phase wise internally calculated
instantaneous (sample based) incoming current. It can be connected to the
disturbance recorder function in order to record it during external and internal
faults (only available in 3Ph-version)
ID, this is output which represents internally calculated instantaneous (sample
based) differential current. It can be connected to the disturbance recorder function
in order to record it during external and internal faults (only available in 1Ph-version)
ID_x, this is output which represents phase wise internally calculated
instantaneous (sample based) differential current. It can be connected to the
disturbance recorder function in order to record it during external and internal
faults (only available in 3Ph-version)
OperLevel, this setting determines the minimum pickup level for the check zone. It
shall be entered directly in primary amperes. Default value 1000A.
Slope, this setting determines the slope of the check zone operating characteristic.
It can be set from 0.00 to 0.90 in step of 0.01. Default value 0.15.
Check zone uses simple differential algorithm. Outgoing current is used for restraining
in order to insure check zone operation for all internal faults.
137
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
EXTTRIP
CZ Diff Algorithm
Id
OR
OR
TRIP
AND
OR
Iout
CZTrip-cont.
Operation = On
Operation = Off
en06000073_ansi.vsd
ANSI06000073 V1 EN
Figure 58:
5.1.6.3
Function block
BTCZBCZTPDIF_87B
EXTTRIP
TRIP
TR_A
TR_B
TR_C
en06000161_ansi.vsd
ANSI06000161 V1 EN
Figure 59:
BCZSPDIF
EXTTRIP
TRIP
IEC06000162-2-en.vsd
IEC06000162 V2 EN
Figure 60:
5.1.6.4
Default
0
Description
External check zone trip
138
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Table 64:
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
Table 65:
Name
Type
EXTTRIP
BOOLEAN
Table 66:
Type
TRIP
Table 67:
Default
Description
External check zone trip
Name
5.1.6.5
Description
Description
BOOLEAN
Setting parameters
BCZTPDIF (87B) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
OperLevel
1 - 99999
1000
Slope
0.00 - 0.90
0.01
0.15
Step
Default
Table 68:
Name
Values (Range)
Unit
Description
Operation
Disabled
Enabled
Disabled
OperLevel
0 - 99999
1000
Slope
0.00 - 0.90
0.01
0.15
5.1.7
Zone selection
Typically CT secondary circuits from every bay in the station are connected to the
busbar protection. The built-in software feature called Zone Selection gives a simple
but efficient control over the connected CTs to busbar protection IED in order to
139
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
5.1.8
5.1.8.1
Introduction
For stations with complex primary layout (that is, double busbar single breaker station
with or without transfer bus) the information about busbar disconnector position in
every bay is crucial information for busbar protection. The positions of these
disconnectors then actually determine which CT input (that is, bay) is connected to
which differential protection zone. For some more advanced features like end-fault or
140
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
blind-spot protection the actual status of the circuit breaker in some or even all bays
can be vital information for busbar protection as well. The switch function block is
used to take the status of two auxiliary contacts from the primary device, evaluate them
and then to deliver the device primary contact position to the rest of the zone selection
logic.
For such applications typically two auxiliary contacts (that is, normally open and
normally closed auxiliary contacts) from each relevant primary switching object shall
be connected to the IED. Then the status for every individual primary switching object
will be determined. The dedicated function block for each primary switching object is
available in order to determine the status of the object primary contacts. By a
parameter setting one of the following two logical schemes can be selected for each
primary object individually by the end user:
Open or closed only when clearly indicated by aux contact status (that is, as in
INX schemes)
141
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Table 69:
Primary equipment
Normally Open Normally Closed
auxiliary contact auxiliary contact
status
status
(that is, closed (that is, open
or a contact)
or b contact)
5.1.8.2
Alarm facility
Alarm after
settable time
delay
Information
visible on local
HMI
open
open
closed
Last position
saved
yes
intermediate_00
open
closed
open
open
no
open
closed
open
closed
closed
no
closed
closed
closed
closed
closed
yes
badState_11
DISABLE, when this binary input has logical value zero function works in
accordance with the selected scheme (see setting OperMode). When this binary
input has logical value one, OPEN and CLOSED outputs from the function are
unconditionally set to logical value zero. All other outputs work as usual.
NO, to this binary input normally open (that is, closed or a contact) of the
primary switching object shall be connected
NC, to this binary input normally closed (that is, OPEN or b contact) of the
primary switching object shall be connected.
Outputs
CLOSED, this binary output has logical value one when the internal logic
determines that the primary object is closed (for more information about available
logical schemes, refer to table 69)
OPEN, this binary output has logical value one when the internal logic determines
that the primary object is open (for more info about available logical schemes,
refer to table 69)
ALARM, this binary output has logical value one when pre-set timer set under
setting tAlarm expires and the auxiliary contacts still have illegal status (that is, 00
or 11)
FORCED, this binary output has logical value zero when the object status is
forced via parameter setting OperMode
142
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Settings
SwitchName, this setting is only a string with user definable free, descriptive text
to designate particular primary switching object in the station in order to make
easier identification of the relevant primary object in the SwitchgearStatus matrix
on the local HMI. The string can be up to thirteen characters long.
OperMode, this setting determines the operating logic used within the function
block. One of the following five alternatives shall be selected for every function
block
1.
Off, when this mode is selected the entire function block is switched off (that
is, de-activated)
Scheme1_RADSS, when this mode is selected the internal logic behaves as
described in table 69/row 3. Note that this logical scheme has the minimal
requirements regarding the auxiliary contacts timing. It is recommended
scheme to be used, especially to determine the circuit breaker status
Scheme2_INX, when this mode is selected the internal logic behaves as
described in table 69/row 4. Note that this logical scheme has increased
requirements regarding the auxiliary contacts timing, especially for normally
open (that is, a contact), as explained intable 69.
ForceOpen, when this mode is selected the internal logic consider the
primary object as open regardless the status of the auxiliary contacts.
However, note that ALARM output will still work as usual and that
FORCED binary output will be unconditionally set to one
ForceClosed, when this mode is selected the internal logic consider the
primary object as closed regardless the actual status of the auxiliary contacts.
However, note that ALARM output will still work as usual and that
FORCED binary output will be unconditionally set to one
2.
3.
4.
5.
5.1.8.3
tAlarm, this delay on pickup timer is used in order to give an alarm output when
illegal status of auxiliary input contacts (that is, 00 or 11) is given to the function.
Timer can be set from 0.00s to 6000.00s in step of 0.01s. Default value is 15.00s.
Function block
SWSGGIO (87B)
DISABLE
CLOSED
NO
OPEN
NC
ALARM
FORCED
ANSI06000163-1-en.vsd
ANSI06000163 V1 EN
Figure 61:
143
Technical reference manual
Section 5
Differential protection
5.1.8.4
1MRK505208-UUS D
Name
Type
NO
BOOLEAN
NC
BOOLEAN
Name
Table 72:
Name
Description
BOOLEAN
Table 71:
5.1.8.5
Default
DISABLE
Type
Description
CLOSED
BOOLEAN
OPEN
BOOLEAN
ALARM
BOOLEAN
FORCED
BOOLEAN
Setting parameters
SWSGGIO (87B) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
OperMode
Disabled
Scheme1_RADSS
Scheme2_INX
ForceOpen
ForceClosed
Disabled
tAlarm
0.00 - 6000.00
0.01
15.00
Step
Default
Table 73:
Name
SwitchName
Unit
-
Switch#
Description
User defined name for switch
144
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
5.1.9
5.1.9.1
Introduction
Each CT input is allocated to one dedicated bay function block. This function block is
used to provide complete user interface for all signals from and towards this bay. It is
also used to influence bay measured current.
In order to guarantee proper operation of the IED, the first instance of
Bay function block must always be used in the configuration.
It is possible by a parameter setting CTConnection to connect or disconnect the CT
input to the bay function block. Once the CT input is connected to the bay function
block this associated current input can be included to or excluded from the two
internally available differential functions in software. This can be done by a parameter
setting for simple station layouts (that is, breaker-and-a-half stations) or alternatively
via dedicated logical scheme (that is, double busbar stations). For each bay the end user
have to select one of the following five alternatives:
At the same time, an additional feature for instantaneous or time delayed disconnection
or even inversion of the connected bay current via separate logical signals is also
available. This feature is provided in order to facilitate for bus-section or bus-coupler
CT disconnection for tie-breakers with a CT only on one side of the circuit breaker.
This ensures correct and fast fault clearance of faults between the CT and the circuit
breaker within these bays. The same feature can be individually used in any feeder bay
to optimize Busbar differential protection performance, when feeder circuit breaker is
open. Thus, the end-fault protection for faults between circuit breaker and the CT is
145
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
available. However, to use this feature circuit breaker auxiliary contacts and closing
command to the circuit breaker shall be wired to the binary inputs of the IED.
Therefore, he IED offers best possible coverage for these special faults between CT
and circuit breaker in feeder and bus-section/bus-coupler bays.
Within the Bay function block it is decided by a parameter setting how this bay should
behave during zone interconnection (that is, load transfer). For each bay individually
one of the following three options can be selected:
Bay current is forced out from both zones during zone interconnection (used for buscoupler bays)
Bay current is unconditionally forced into both zones during zone interconnection
(used in special applications)
Bay current is connected to both zones during zone interconnection if the bay was
previously connected to one of the two zones (typically used for feeder bays)
The third option ensures that the feeder, which is out of service, is not connected to any
of the two zones during zone interconnection.
Within the Bay function block it is decided by a parameter setting whether this bay
should be connected to the check zone or not. In this way the end user has simple
control over the bays, which shall be connected to the overall check zone.
By appropriate configuration logic it is possible to take any bay (that is, CT input) out
of service. This can be done from the local HMI or externally via binary signal. In that
case all internal current measuring functions (that is, differential protection, sensitive
differential protection, check zone, breaker failure protection and overcurrent
protection) are disabled. At the same time, any trip command to this bay circuit breaker
can be inhibited.
Via two dedicated binary input signals it is possible to:
Trip only the bay circuit breaker (used for integrated OC protection tripping)
Trip the whole differential zone to which this bay is presently connected (used for
backup-trip command from either integrated or external bay circuit breaker failure
protection)
Finally dedicated trip binary output from the Bay function block is available in order to
provide common trip signal to the bay circuit breaker from busbar differential
protection, breaker failure protection, backup overcurrent protection and so on.
In this way the interface to the user is kept as simple as possible and IED engineering
work is quite straight forward.
146
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
5.1.9.2
CTRLZB, this binary input is used to control the bay CT connection to the
differential zone B. Note that the status of this binary input is considered ONLY if
the value of setting parameter ZoneSel is either
CtrlIncludes when logical value one of this input will include current to zone
A, or
CtrlExcludes when logical value zero of this input will include current to
zone A
CtrlIncludes when logical value one of this input will include current to zone
B, or
CtrlExcludes when logical value zero of this input will include current to
zone B
ZEROCUR, when this binary input has logical value one the bay CT current is
unconditionally forced to zero (that is, internally multiplied with zero) after the
internal delay on pickup timer has expired. The time delay is determined by setting
parameter tZeroCurrent. Note that the zero current value will be given to all
differential zones, including the check zone, to which this bay is currently connected
INVCUR, when this binary input has logical value one the bay CT current will be
inverted (that is, internally multiplied with 1) after the internal delay on pickup
timer has expired. The time delay is determined by setting parameter
tInvertCurrent. Note that the inverted current value will be given to all differential
zones, including the check zone, to which this bay is currently connected.
However, it shall be noted that the INVCUR input has lower priority than the
ZEROCUR input. This means that, when both of them simultaneously have
logical value one, and both timers have expired, the bay CT current will be forced
to zero.
TRZONE, when this binary input has logical value one the trip signal will be sent
to the differential zone to which this bay is currently connected. As a consequence
all bays connected to that zone will receive the trip signal. To this input the
breaker failure protection backup trip command for this bay is typically connected.
This will insure that all breakers connected to the same zone with the failed
147
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
breaker will be tripped. Note that this tripping is not supervised by the Check Zone
operation, in application where Check Zone is enabled.
TRBAY, when this binary input has logical value one the output TRIP signal from
the same function block will be activated. In this way only the bay circuit breaker
is tripped. No any other breaker in the station will receive this trip command. This
input is used to give backup overcurrent trip command to the bay CB.
Outputs
TRIP, this binary output shall be used as dedicated three-pole trip command to the
bay circuit breaker. It will be activated when the differential zone, to which this
bay is currently connected, operates for internal fault, or in case of breaker failure
in some other bay connected to the same zone (see description for input
TRZONE). It operates when external trip signal is given to this bay (see
description for input TRBAY).
CONNZA, this binary output has logical value one whenever this bay CT is
connected to zone A
CONNZB, this binary output has logical value one whenever this bay CT is
connected to zone B
CONNBAY, this is not a binary output. It has integer value between 1 and 9 and is
used in order to display actual BayConnections information on the local HMI.
Settings
BAYnn, this setting is only a string with user definable free, descriptive text to
designate particular primary bay in the station in order to make easier bay
identification on the BayConnections matrix on the local HMI. The string can be
up to thirteen characters long.
CTConnection, this setting determines how the hardware CT input is connected to
bay function block in software. One of the following three alternatives shall be
selected for every function block:
1.
2.
3.
ZoneSel, this setting determines how the bay CT input connection to the
differential zones is controlled within the IED internal logic. One of the five
148
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
alternatives listed below shall be selected for every function block. CtrlIncludes
and CtrlExcludes are typically used for feeder bays in double busbar-single
breaker stations where dynamic connections between CT and differential zones are
required. It shall be noted that when one of the last two modes are selected and in
the same time the operation of the Zone Interconnection function block is set to
"On" the zone interconnection (that is, merging between ZA & ZB) will be
automatically started as soon as the bay is connected to both zones simultaneously
(that is, zone interconnection on a feeder bay).
1.
2.
3.
4.
5.
ZoneSwitching, this setting determines how the bay CT shall behave when zone
interconnection is active (that is, merging between ZA & ZB). One of the
following three alternatives shall be selected for every function block:
1.
2.
3.
Section 5
Differential protection
1MRK505208-UUS D
for feeder bays in double busbar-single breaker stations, and for all spare/
future bays.
CheckZoneSel, this setting determines the bay CT input connection towards the
check zone. One of the following two alternatives shall be selected for every
function block:
1.
2.
5.1.9.3
NotConnected, when this mode is selected the bay CT input is not connected
to the overall check zone. This setting is typically used for bus-coupler bay
in double busbar-single breaker stations.
Connected, when this mode is selected the bay CT input is connected to the
overall check zone. This setting is typically used for feeder bays in double
busbar-single breaker stations.
tTripPulse, this pulse timer is used in order to guaranty minimum trip pulse
duration from the bay function block. Pulse time can be set from 0.000s to 60.000s
in step of 0.001s. Default value is 0.200s.
tZeroCurrent, this delay on pickup timer is used in order to unconditionally force
bay current to zero when ZEROCUR input into the function block has logical
value one. Time delay can be set from 0.000s to 60.000s in step of 0.001s. Default
value is 0.200s.
tInvertCurrent, this delay on pickup timer is used in order to invert bay current
when INVCUR input into the function block has logical value one. Time delay can
be set from 0.000s to 60.000s in step of 0.001s. Default value is 0.200s.
The setting parameter for bay connection called ZoneSel can be individually set for
every CT. ZoneSel can be set to only one of the following five alternatives:
150
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
When the last two options are used the CT input can be dynamically included or
excluded from the differential zone by simply controlling the dedicated inputs of the
Bay function block.
CTRLZA
AND
OR
5 ms
0
OR
5 ms
0
OR
AND
CTtoZoneA-cont.
CTRLZB
AND
ZoneSel=
CtrlIncludes
OR
CTtoZoneB-cont.
AND
AND
ZoneSel=
CtrlExcludes
StrtLoadTransfBayxx-cont.
ZoneSel=
FixedToZA
InvertCTtoZoneB-cont.
ZoneSel=
FixedToZB
ZoneSel=
FixedToZA&-ZB
en06000066_ansi.vsd
ANSI06000066 V1 EN
Figure 62:
This logic is intended for binary input signals that give possibility to force current to
zero or invert the current. Two settable delays on timer tZeroCurrent and
tInvertCurrent are also implemented making sure that the right decision is taken, see
figure 63.
151
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
ZEROCUR
INV
CU
R
0-tZeroCurrent
0
0.0
0-tInvertCurrent
0
T
F
-1.0
1.0
T
F
CurrentBayxx-cont.
CTConnection
Connected= 1
NotConnected= 0
ConnInverted= -1
A/D Conversion,
Multiplication with CT Ratio,
Taking in account setting
CTWyePoint for TRM
Bayxx Current in
Primary Amperes
REB 670
CT Input
en06000068_ansi.vsd
ANSI06000068 V1 EN
Figure 63:
Overall CT status
152
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
ANSI07000187 V1 EN
Figure 64:
Check zone selection and zone interconnection operation influence on zone selection.
If there is an internal fault, differential function will operate, that is, a tripZoneA/
TripZoneB will be given to all bays. All the bays that are connected to that zone will be
tripped if they are not blocked by input BLKTR.
A pulse timer tTripPulse will ensure the minimal duration of the trip signal.
153
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
BayxxInZA
ZATrip
AND
AND
BayxxInZB
ZBTrip
OR
OR
AND
TRBAY
BLKTR
AND
tTripPulse
t
OR
TRIP
en06000070_ansi.vsd
ANSI06000070 V1 EN
Figure 65:
5.1.9.4
Function block
BUSPTRC_B1 (87B)
ISI1*
TRIP
BLKTR
CONNZA
CTRLZA
CONNZB
CTRLZB
CONNBAY
ZEROCUR
INVCUR
TRZONE
TRBAY
ANSI06000165-1-en.vsd
ANSI06000165 V1 EN
Figure 66:
BUTPTRC_B1 (87B)
I3PB1*
TRIP
BLKTR
CONNZA
CTRLZA
CONNZB
CTRLZB
CONNBAY
ZEROCUR
INVCUR
TRZONE
TRBAY
ANSI06000164-1-en.vsd
ANSI06000164 V1 EN
Figure 67:
154
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
5.1.9.5
Default
Description
I3PB1
GROUP
SIGNAL
BLKTR
BOOLEAN
CTRLZA
BOOLEAN
CTRLZB
BOOLEAN
ZEROCUR
BOOLEAN
INVCUR
BOOLEAN
TRZONE
BOOLEAN
TRBAY
BOOLEAN
Table 75:
Name
Description
TRIP
BOOLEAN
CONNZA
BOOLEAN
CONNZB
BOOLEAN
CONNBAY
INTEGER
Table 76:
Name
Default
Description
ISI1
GROUP
SIGNAL
BLKTR
BOOLEAN
CTRLZA
BOOLEAN
CTRLZB
BOOLEAN
ZEROCUR
BOOLEAN
INVCUR
BOOLEAN
TRZONE
BOOLEAN
TRBAY
BOOLEAN
155
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Table 77:
Name
5.1.9.6
Table 78:
Name
Type
Description
TRIP
BOOLEAN
CONNZA
BOOLEAN
CONNZB
BOOLEAN
CONNBAY
INTEGER
Setting parameters
BUTPTRC_B1 (87B) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
CTConnection
Conn Inverted
NotConnected
Connected
Connected
ZoneSel
FixedToZA
FixedToZB
FixedToZA&-ZB
CtrlIncludes
CtrlExcludes
CtrlIncludes
ZoneSwitching
ForceOut
ForceIn
Conditionally
ForceIn
CheckZoneSel
NotConnected
Connected
NotConnected
tTripPulse
0.000 - 60.000
0.001
0.200
tZeroCurrent
0.000 - 60.000
0.001
0.200
tInvertCurrent
0.000 - 60.000
0.001
0.200
Table 79:
Name
BAY01
Unit
-
Step
1
Default
BayName01
Description
User defined name for bay
156
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Table 80:
Name
Values (Range)
Unit
Step
Default
Description
CTConnection
Conn Inverted
NotConnected
Connected
Connected
ZoneSel
FixedToZA
FixedToZB
FixedToZA&-ZB
CtrlIncludes
CtrlExcludes
CtrlIncludes
ZoneSwitching
ForceOut
ForceIn
Conditionally
ForceIn
CheckZoneSel
NotConnected
Connected
NotConnected
tTripPulse
0.000 - 60.000
0.001
0.200
tZeroCurrent
0.000 - 60.000
0.001
0.200
tInvertCurrent
0.000 - 60.000
0.001
0.200
Table 81:
Name
BAY01
Values (Range)
0 - 13
Unit
-
Step
1
Default
BayName01
Description
User defined name for bay
5.1.10
5.1.10.1
Introduction
When this feature is activated the two integrated differential protection zones are
merged into one common, overall differential zone. This feature is required in double
busbar stations when in any of the feeder bays both busbar disconnectors are closed at
the same time (that is, load transfer). As explained in above section Bay each CT input
will then behave in the pre-set way in order to ensure proper current balancing during
this special condition. This feature can be started automatically (when Zone Selection
logic determines that both busbar disconnectors in one feeder bay are closed at the
same time) or externally via dedicated binary signal. If this feature is active for longer
time than the pre-set vale the alarm signal is given.
157
Technical reference manual
Section 5
Differential protection
5.1.10.2
1MRK505208-UUS D
EXTSTART, when this binary input has logical value one the zone
interconnection feature will be activated if it is enabled by the setting parameter
Operation
SUMB1B2, this binary input is used for quite special feature which enables the
user to internally sum Bay 01 and Bay 02 currents while the zone interconnection
is active
SUMB3B4, this binary input is used for quite special feature which enables the
user to internally sum Bay 03 and Bay 04 currents while the zone interconnection
is active
SUMB5B6, this binary input is used for quite special feature which enables the
user to internally sum Bay 05 and Bay 06 currents while the zone interconnection
is active. It shall be noted that this input is only available in 1-phase version of
REB670.
Outputs
ACTIVE, this binary output has logical value one while zone interconnection
feature is active in the IED
ALARM, this binary output has logical value one, if the zone interconnection
feature is active longer than the time set under setting parameter tAlarm
Settings
5.1.10.3
158
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
EXTSTART
1
OR
0
50 ms
StrtLoadTransfBay01
ACTIVE
AND
&
ZoneIntercActive-cont.
StrtLoadTransfBay02
...
OR
0-tAlarm
0
ALARM
StrtLoadTransfBaynn
Operation = On
en06000069_ansi.vsd
ANSI06000069 V1 EN
Figure 68:
5.1.10.4
ForceOut, the particular bay will be excluded during the zone interconnection.
ForceIn, the particular bay will be included during the zone interconnection.
Conditionally, the particular bay will be included if it was in operation two ms
before, otherwise the bay will be excluded during the zone interconnection.
Function block
BZITGGIO (87B)
EXTSTART
ACTIVE
SUMB1B2
ALARM
SUMB3B4
ANSI06000166-2-en.vsd
ANSI06000166 V2 EN
Figure 69:
BZISGGIO (87B)
EXTSTART
ACTIVE
SUMB1B2
ALARM
SUMB3B4
SUMB5B6
ANSI06000167-2-en.vsd
ANSI06000167 V2 EN
Figure 70:
159
Technical reference manual
Section 5
Differential protection
5.1.10.5
1MRK505208-UUS D
Name
Type
SUMB1B2
BOOLEAN
SUMB3B4
BOOLEAN
Name
Type
BOOLEAN
ALARM
BOOLEAN
Name
Type
Default
Description
EXTSTART
BOOLEAN
SUMB1B2
BOOLEAN
SUMB3B4
BOOLEAN
SUMB5B6
BOOLEAN
Table 85:
Name
Name
Description
ACTIVE
Table 84:
Table 86:
Description
BOOLEAN
Table 83:
5.1.10.6
Default
EXTSTART
Type
Description
ACTIVE
BOOLEAN
ALARM
BOOLEAN
Setting parameters
BZITGGIO (87B) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
tAlarm
0.00 - 6000.00
0.01
300.00
160
Technical reference manual
Section 5
Differential protection
1MRK505208-UUS D
Table 87:
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
tAlarm
0.00 - 6000.00
0.01
300.00
5.1.11
Technical data
Table 88:
Function
Range or value
Accuracy
Operating characteristic
S=0.53 fixed
Reset ratio
> 95%
(1-100000) A
(1-100000) A
(0-100000) A
(0.0-0.9)
Timers
(0.000-60.000) s
0.5% 10 ms
Timers
(0.00-6000.00) s
0.5% 10 ms
Operate time
19 ms typically at 0 to 2 x Id
12 ms typically at 0 to 10 x Id
Reset time
21 ms typically at 2 to 0 x Id
29 ms typically at 10 to 0 x Id
8 ms typically at 0 to 2 x Id
161
Technical reference manual
162
Section 6
Current protection
1MRK505208-UUS D
Section 6
Current protection
6.1
IEC 61850
identification
IEC 60617
identification
OC4PTOC
3I>
4
4
ANSI/IEEE C37.2
device number
51/67
alt
TOC-REVA V1 EN
6.1.1
Introduction
The four step phase overcurrent protection function OC4PTOC (51/67) has
independent inverse time delay settings for step 1 and 4. Step 2 and 3 are always
definite time delayed.
All IEC and ANSI inverse time characteristics are available together with an optional
user defined time characteristic.
The directional function is voltage polarized with memory. The function can be set to
be directional or non-directional independently for each of the steps.
Second harmonic blocking level can be set for the function and can be used to block
each step individually
6.1.2
Principle of operation
The Four step phase overcurrent protection OC4PTOC (51/67) is divided into four
different sub-functions, one for each step. For each step x , where x is step 1, 2, 3 and
163
Section 6
Current protection
1MRK505208-UUS D
faultState
Direction
Element
I3P
dirPhAFlt
dirPhBFlt
dirPhCFlt
faultState
PICKUP
V3P
TRIP
I3P
Harmonic
Restraint
Element
harmRestrBlock
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
en05000740_ansi.vsd
ANSI05000740 V1 EN
Figure 71:
164
Technical reference manual
1MRK505208-UUS D
Section 6
Current protection
A common setting for all steps, NumPhSel, is used to specify the number of phase
currents to be high to enable operation. The settings can be chosen: 1 out of 3, 2 out of
3 or 3 out of 3.
The sampled analog phase currents are processed in a pre-processing function block.
Using a parameter setting MeasType within the general settings for the four step phase
overcurrent protection 3-phase output function OC4PTOC (51/67), it is possible to
select the type of the measurement used for all overcurrent stages. It is possible to
select either discrete Fourier filter (DFT) or true RMS filter (RMS).
If DFT option is selected then only the RMS value of the fundamental frequency
components of each phase current is derived. Influence of DC current component and
higher harmonic current components are almost completely suppressed. If RMS option
is selected then the true RMS values is used. The true RMS value in addition to the
fundamental frequency component includes the contribution from the current DC
component as well as from higher current harmonic. The selected current values are
fed to OC4PTOC (51/67).
In a comparator, for each phase current, the DFT or RMS values are compared to the
set operation current value of the function (Pickup1, Pickup2, Pickup3, Pickup4). If a
phase current is larger than the set operation current, outputs PICKUP, PU_STx,
PU_A, PU_B and PU_C are, without delay, activated. Output signals PU_A, PU_B
and PU_C are common for all steps. This means that the lowest set step will initiate the
activation. The PICKUP signal is common for all three phases and all steps. It shall be
noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC (51/67) .
Service value for individually measured phase currents are also available on the local
HMI for OC4PTOC (51/67) function, which simplifies testing, commissioning and in
service operational checking of the function.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from the
pre-processing of the phase currents and the relation is compared to a set restrain
current level.
The function can be directional. The direction of the fault current is given as current
angle in relation to the voltage angle. The fault current and fault voltage for the
directional function is dependent of the fault type. To enable directional measurement
at close in faults, causing low measured voltage, the polarization voltage is a
combination of the apparent voltage (85%) and a memory voltage (15%). The
following combinations are used.
165
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Vref _ AB = VA - VB
I dir _ AB = I A - I B
(Equation 4)
GUID-4F361BC7-6D91-47B5-8119-A27009C0AD6A V1 EN
Vref _ BC = VB - VC
I dir _ BC = I B - I C
(Equation 5)
ANSIEQUATION1450 V1 EN
Vref _ CA = VC - VA
I dir _ CA = IC - I A
(Equation 6)
ANSIEQUATION1451 V1 EN
Vref _ A = VA
I dir _ A = I A
(Equation 7)
ANSIEQUATION1452 V1 EN
Vref _ B = VB
I dir _ B = I B
(Equation 8)
ANSIEQUATION1453 V1 EN
Vref _ C = VC
I dir _ C = I C
ANSIEQUATION1454 V1 EN
(Equation 9)
If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition seals in.
If the current decreases below the minimum operating value, the memory resets
until the positive sequence voltage exceeds 10% of its rated value.
166
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
The directional setting is given as a characteristic angle AngleRCA for the function and
an angle window AngleROA.
Reverse
Vref
RCA
ROA
ROA
Forward
Idir
en05000745_ansi.vsd
ANSI05000745 V1 EN
Figure 72:
The default value of AngleRCA is 65. The parameters AngleROA gives the angle
sector from AngleRCA for directional borders.
A minimum current for directional phase pickup current signal can be set:
PUMinOpPhSel.
If no blockings are given the pickup signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or inverse time
characteristic. A wide range of standardized inverse time characteristics is available. It
is also possible to create a tailor made time characteristic. The possibilities for inverse
time characteristics are described in section "Inverse characteristics".
167
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
All four steps in OC4PTOC (51/67) can be blocked from the binary input BLOCK.
The binary input BLKx (x=1, 2, 3 or 4) blocks the operation of respective step.
Characteristx=DefTime
|IOP|
Pickupx
AND
OR
a>b
0-tx
0
TRx
STx
AND
0-txMin
0
BLKSTx
AND
BLOCK
Inverse
Characteristx=Inverse
OR
DirModeSelx=Disabled
STAGEx_DIR_Int
DirModeSelx=Non-directional
DirModeSelx=Forward
DirModeSelx=Reverse
FORWARD_Int
REVERSE_Int
AND
OR
AND
ANSI12000008-1-en.vsd
ANSI12000008-1-en.vsd
ANSI12000008 V1 EN
Figure 73:
6.1.3
168
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
BLOCK
a
0.07*IBase
IOP
a>b
Extract second
harmonic current
component
Extract
fundamental
current component
a>b
2NDHARMD
AND
a>b
2ndH_BLOCK_Int
2ndHarmStab
IEC13000014-1-en.vsd
IEC13000014 V1 EN
Figure 74:
169
Technical reference manual
Section 6
Current protection
6.1.4
1MRK505208-UUS D
Function block
OC4PTOC (51_67)
I3P*
TRIP
V3P*
TRST1
BLOCK
TRST2
BLKTR
TRST3
BLK1
TRST4
BLK2
TR_A
BLK3
TR_B
BLK4
TR_C
MULTPU1
TRST1_A
MULTPU2
TRST1_B
MULTPU3
TRST1_C
MULTPU4
TRST2_A
TRST2_B
TRST2_C
TRST3_A
TRST3_B
TRST3_C
TRST4_A
TRST4_B
TRST4_C
PICKUP
PU_ST1
PU_ST2
PU_ST3
PU_ST4
PU_A
PU_B
PU_C
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2_A
PU_ST2_B
PU_ST2_C
PU_ST3_A
PU_ST3_B
PU_ST3_C
PU_ST4_A
PU_ST4_B
PU_ST4_C
2NDHARM
DIR_A
DIR_B
DIR_C
ANSI06000187-2-en.vsd
ANSI06000187 V2 EN
Figure 75:
6.1.5
Default
Description
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
Section 6
Current protection
1MRK505208-UUS D
Name
Type
Default
Description
BLKTR
BOOLEAN
Block of trip
BLK1
BOOLEAN
Block of Step1
BLK2
BOOLEAN
Block of Step2
BLK3
BOOLEAN
Block of Step3
BLK4
BOOLEAN
Block of Step4
MULTPU1
BOOLEAN
MULTPU2
BOOLEAN
MULTPU3
BOOLEAN
MULTPU4
BOOLEAN
Table 90:
Name
Description
TRIP
BOOLEAN
Trip
TRST1
BOOLEAN
TRST2
BOOLEAN
TRST3
BOOLEAN
TRST4
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TRST1_A
BOOLEAN
TRST1_B
BOOLEAN
TRST1_C
BOOLEAN
TRST2_A
BOOLEAN
TRST2_B
BOOLEAN
TRST2_C
BOOLEAN
TRST3_A
BOOLEAN
TRST3_B
BOOLEAN
TRST3_C
BOOLEAN
TRST4_A
BOOLEAN
TRST4_B
BOOLEAN
TRST4_C
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
PU_ST3
BOOLEAN
Section 6
Current protection
1MRK505208-UUS D
Name
6.1.6
Table 91:
Name
Type
Description
PU_ST4
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2_A
BOOLEAN
PU_ST2_B
BOOLEAN
PU_ST2_C
BOOLEAN
PU_ST3_A
BOOLEAN
PU_ST3_B
BOOLEAN
PU_ST3_C
BOOLEAN
PU_ST4_A
BOOLEAN
PU_ST4_B
BOOLEAN
PU_ST4_C
BOOLEAN
2NDHARM
BOOLEAN
DIR_A
INTEGER
DIR_B
INTEGER
DIR_C
INTEGER
Setting parameters
OC4PTOC (51_67) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IBase
1 - 99999
3000
Base current
Vbase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
AngleRCA
40 - 65
Deg
55
AngleROA
40 - 89
Deg
80
NumPhSel
1 out of 3
2 out of 3
3 out of 3
1 out of 3
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Non-directional
172
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Characterist1
Pickup1
1 - 2500
%IB
1000
t1
0.000 - 60.000
0.001
0.000
TD1
0.05 - 999.00
0.01
0.05
IMin1
1 - 10000
%IB
100
t1Min
0.000 - 60.000
0.001
0.000
MultPU1
1.0 - 10.0
0.1
2.0
DirModeSel2
Disabled
Non-directional
Forward
Reverse
Non-directional
Characterist2
Pickup2
1 - 2500
%IB
500
Section 6
Current protection
Name
1MRK505208-UUS D
Values (Range)
Unit
t2
0.000 - 60.000
Step
0.001
Default
0.400
Description
Definitive time delay of step 2
TD2
0.05 - 999.00
0.01
0.05
IMin2
1 - 10000
%IB
50
t2Min
0.000 - 60.000
0.001
0.000
MultPU2
1.0 - 10.0
0.1
2.0
DirModeSel3
Disabled
Non-directional
Forward
Reverse
Non-directional
Characterist3
Pickup3
1 - 2500
%IB
250
t3
0.000 - 60.000
0.001
0.800
TD3
0.05 - 999.00
0.01
0.05
IMin3
1 - 10000
%IB
33
t3Min
0.000 - 60.000
0.001
0.000
MultPU3
1.0 - 10.0
0.1
2.0
DirModeSel4
Disabled
Non-directional
Forward
Reverse
Non-directional
174
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Characterist4
Pickup4
1 - 2500
%IB
175
t4
0.000 - 60.000
0.001
2.000
TD4
0.05 - 999.00
0.01
0.05
IMin4
1 - 10000
%IB
17
t4Min
0.000 - 60.000
0.001
0.000
MultPU4
1.0 - 10.0
0.1
2.0
Table 92:
Name
Values (Range)
Unit
Step
Default
Description
PUMinOpPhSel
1 - 100
%IB
2ndHarmStab
5 - 100
%IB
20
ResetTypeCrv1
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset1
0.000 - 60.000
0.001
0.020
tPCrv1
0.005 - 3.000
0.001
1.000
tACrv1
0.005 - 200.000
0.001
13.500
tBCrv1
0.00 - 20.00
0.01
0.00
175
Technical reference manual
Section 6
Current protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
tCCrv1
0.1 - 10.0
0.1
1.0
tPRCrv1
0.005 - 3.000
0.001
0.500
tTRCrv1
0.005 - 100.000
0.001
13.500
tCRCrv1
0.1 - 10.0
0.1
1.0
HarmRestrain1
Disabled
Enabled
Disabled
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset2
0.000 - 60.000
0.001
0.020
tPCrv2
0.005 - 3.000
0.001
1.000
tACrv2
0.005 - 200.000
0.001
13.500
tBCrv2
0.00 - 20.00
0.01
0.00
tCCrv2
0.1 - 10.0
0.1
1.0
tPRCrv2
0.005 - 3.000
0.001
0.500
tTRCrv2
0.005 - 100.000
0.001
13.500
tCRCrv2
0.1 - 10.0
0.1
1.0
HarmRestrain2
Disabled
Enabled
Disabled
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset3
0.000 - 60.000
0.001
0.020
tPCrv3
0.005 - 3.000
0.001
1.000
tACrv3
0.005 - 200.000
0.001
13.500
tBCrv3
0.00 - 20.00
0.01
0.00
tCCrv3
0.1 - 10.0
0.1
1.0
tPRCrv3
0.005 - 3.000
0.001
0.500
Section 6
Current protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
tTRCrv3
0.005 - 100.000
0.001
13.500
tCRCrv3
0.1 - 10.0
0.1
1.0
HarmRestrain3
Disabled
Enabled
Disabled
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset4
0.000 - 60.000
0.001
0.020
tPCrv4
0.005 - 3.000
0.001
1.000
tACrv4
0.005 - 200.000
0.001
13.500
tBCrv4
0.00 - 20.00
0.01
0.00
tCCrv4
0.1 - 10.0
0.1
1.0
tPRCrv4
0.005 - 3.000
0.001
0.500
tTRCrv4
0.005 - 100.000
0.001
13.500
tCRCrv4
0.1 - 10.0
0.1
1.0
HarmRestrain4
Disabled
Enabled
Disabled
Table 93:
Name
MeasType
Values (Range)
DFT
RMS
Unit
-
Step
-
Default
DFT
Description
Selection between DFT and RMS
measurement
177
Technical reference manual
Section 6
Current protection
6.1.7
1MRK505208-UUS D
Technical data
Table 94:
OC4PTOC (51/67)
Function
6.2
Setting range
Accuracy
Trip current
(5-2500)% of lBase
1.0% of In at I In
1.0% of I at I > In
Reset ratio
(1-10000)% of lBase
1.0% of In at I In
1.0% of I at I > In
(40.065.0) degrees
2.0 degrees
(40.089.0) degrees
2.0 degrees
(5100)% of fundamental
2.0% of In
(0.000-60.000) s
0.2 % or 35 ms whichever is
greater
(0.000-60.000) s
2.0 % or 40 ms whichever is
greater
16 curve types
Min. = 15 ms
Min. = 15 ms
10 ms typically at 0 to 2 x Iset
15 ms typically
lBase
Max. = 30 ms
Max. = 30 ms
IEC 61850
identification
IEC 60617
identification
PH4SPTOC
I>
4
4
ANSI/IEEE C37.2
device number
51
alt
OC V1 EN
178
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.2.1
Introduction
Four step single phase overcurrent protection (PH4SPTOC, 51)has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time delayed characteristics are available together with an optional
user defined time characteristic.
The function is normally used as end fault protection to clear faults between current
transformer and circuit breaker.
6.2.2
Principle of operation
The function is divided into four different sub-functions, one for each step.
The function consists of two major parts:
179
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
4 step overcurrent
element
One element for each
step
ISI
PICKUP
TRIP
I3P
Harmonic
Restraint
Element
harmRestrBlock
en06000141_ansi.vsd
ANSI06000141 V1 EN
Figure 76:
The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT)
block. The RMS value of the phase current is derived. The phase current value is fed to
the PH4SPTOC (51) function. In a comparator the RMS value is compared to the set
operation current value of the function (Pickup1, Pickup2, Pickup3, Pickup4). If the
phase current is larger than the set operation current a signal from the comparator is set
to true. This signal will, without delay, activate the output signal Pickup for this step
and a common Pickup signal.
A harmonic restrain of the function can be chosen. A set 2nd harmonic current in
relation to the fundamental current is used. The 2nd harmonic current is taken from the
pre-processing of the phase current and compared to a set restrain current level.
If no blockings are given the pickup signals will start the timers of the step. The time
characteristic for each step can be chosen as definite time delay or some type of inverse
time characteristic. A wide range of standardized inverse time characteristics is
available. It is also possible to create a tailor made time characteristic. The possibilities
for inverse time characteristics are described in chapter "Inverse time characteristics".
180
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Different types of reset time can be selected as described in chapter "Inverse time
characteristics".
There is also a possibility to activate a preset change (MultPUx, x= 1, 2, 3 or 4) of the
set operation current via a binary input (enable multiplier). In some applications the
operation value needs to be changed, for example due to changed network switching
state. The function can be blocked from the binary input BLOCK. The pickup signals
from the function can be blocked from the binary input BLK. The trip signals from the
function can be blocked from the binary input BLKTR.
6.2.3
Function block
PH4SPTOC (51)
ISI*
TRIP
BLOCK
TRST1
BLK1
TRST2
BLK2
TRST3
BLK3
TRST4
BLK4
PICKUP
BLKTR
PU_ST1
MULTPU1
PU_ST2
MULTPU2
PU_ST3
MULTPU3
PU_ST4
MULTPU4
2NDHARM
ANSI10000015-1-en.vsd
ANSI10000015 V1 EN
Figure 77:
6.2.4
Default
Description
ISI
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLK1
BOOLEAN
Block of Step1
BLK2
BOOLEAN
Block of Step2
BLK3
BOOLEAN
Block of Step3
BLK4
BOOLEAN
Block of Step4
BLKTR
BOOLEAN
Block of trip
MULTPU1
BOOLEAN
MULTPU2
BOOLEAN
MULTPU3
BOOLEAN
MULTPU4
BOOLEAN
181
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Table 96:
Name
6.2.5
Table 97:
Name
Type
Description
TRIP
BOOLEAN
Trip
TRST1
BOOLEAN
TRST2
BOOLEAN
TRST3
BOOLEAN
TRST4
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
PU_ST3
BOOLEAN
PU_ST4
BOOLEAN
2NDHARM
BOOLEAN
Setting parameters
PH4SPTOC (51) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IBase
1 - 99999
3000
OpStep1
Disabled
Enabled
Enabled
Characterist1
Pickup1
1 - 2500
%IB
1000
t1
0.000 - 60.000
0.001
0.000
TD1
0.05 - 999.00
0.01
0.05
Section 6
Current protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
MultPU1
1.0 - 10.0
0.1
2.0
t1Min
0.000 - 60.000
0.001
0.000
OpStep2
Disabled
Enabled
Enabled
Characterist2
Pickup2
1 - 2500
%IB
500
t2
0.000 - 60.000
0.001
0.400
TD2
0.05 - 999.00
0.01
0.05
MultPU2
1.0 - 10.0
0.1
2.0
t2Min
0.000 - 60.000
0.001
0.000
OpStep3
Disabled
Enabled
Enabled
183
Technical reference manual
Section 6
Current protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
Characterist3
Pickup3
1 - 2500
%IB
250
t3
0.000 - 60.000
0.001
0.800
TD3
0.05 - 999.00
0.01
0.05
MultPU3
1.0 - 10.0
0.1
2.0
t3Min
0.000 - 60.000
0.001
0.000
OpStep4
Disabled
Enabled
Enabled
Characterist4
Pickup4
1 - 2500
%IB
175
t4
0.000 - 60.000
0.001
2.000
184
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Name
Values (Range)
Step
Default
TD4
0.05 - 999.00
0.01
0.05
MultPU4
1.0 - 10.0
0.1
2.0
t4Min
0.000 - 60.000
0.001
0.000
Table 98:
Unit
Description
Name
Values (Range)
Unit
Step
Default
Description
2ndHarmStab
5 - 100
%IB
20
ResetTypeCrv1
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset1
0.000 - 60.000
0.001
0.020
tPCrv1
0.005 - 3.000
0.001
1.000
tACrv1
0.005 - 200.000
0.001
13.500
tBCrv1
0.00 - 20.00
0.01
0.00
tCCrv1
0.1 - 10.0
0.1
1.0
tPRCrv1
0.005 - 3.000
0.001
0.500
tTRCrv1
0.005 - 100.000
0.001
13.500
tCRCrv1
0.1 - 10.0
0.1
1.0
HarmRestrain1
Disabled
Enabled
Enabled
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset2
0.000 - 60.000
0.001
0.020
tPCrv2
0.005 - 3.000
0.001
1.000
tACrv2
0.005 - 200.000
0.001
13.500
tBCrv2
0.00 - 20.00
0.01
0.00
185
Technical reference manual
Section 6
Current protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
tCCrv2
0.1 - 10.0
0.1
1.0
tPRCrv2
0.005 - 3.000
0.001
0.500
tTRCrv2
0.005 - 100.000
0.001
13.500
tCRCrv2
0.1 - 10.0
0.1
1.0
HarmRestrain2
Disabled
Enabled
Enabled
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset3
0.000 - 60.000
0.001
0.020
tPCrv3
0.005 - 3.000
0.001
1.000
tACrv3
0.005 - 200.000
0.001
13.500
tBCrv3
0.00 - 20.00
0.01
0.00
tCCrv3
0.1 - 10.0
0.1
1.0
tPRCrv3
0.005 - 3.000
0.001
0.500
tTRCrv3
0.005 - 100.000
0.001
13.500
tCRCrv3
0.1 - 10.0
0.1
1.0
HarmRestrain3
Disabled
Enabled
Enabled
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tReset4
0.000 - 60.000
0.001
0.020
tPCrv4
0.005 - 3.000
0.001
1.000
tACrv4
0.005 - 200.000
0.001
13.500
tBCrv4
0.00 - 20.00
0.01
0.00
tCCrv4
0.1 - 10.0
0.1
1.0
tPRCrv4
0.005 - 3.000
0.001
0.500
Section 6
Current protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
tTRCrv4
0.005 - 100.000
0.001
13.500
tCRCrv4
0.1 - 10.0
0.1
1.0
HarmRestrain4
Disabled
Enabled
Enabled
6.2.6
Technical data
Table 99:
Function
6.3
Setting range
Accuracy
Operate current
(1-2500)% of lbase
1.0% of In at I In
1.0% of I at I > In
Reset ratio
> 95%
(5100)% of fundamental
2.0% of In
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
19 curve types
25 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
10 ms typically at 0 to 2 x Iset
15 ms typically
IEC 61850
identification
IEC 60617
identification
TRPTTR
ANSI/IEEE C37.2
device number
49
SYMBOL-A V1 EN
187
Technical reference manual
Section 6
Current protection
6.3.1
1MRK505208-UUS D
Introduction
If a power transformer or generator reaches very high temperatures the equipment
might be damaged. The insulation within the transformer/generator will have forced
ageing. As a consequence of this the risk of internal phase-to-phase or phase-to-ground
faults will increase. High temperature will degrade the quality of the transformer/
generator insulation.
The thermal overload protection estimates the internal heat content of the transformer/
generator (temperature) continuously. This estimation is made by using a thermal
model of the transformer/generator with two time constants, which is based on current
measurement.
Two warning pickup levels are available. This enables actions in the power system to
be done before dangerous temperatures are reached. If the temperature continues to
increase to the trip value, the protection initiates a trip of the protected transformer/
generator.
6.3.2
Principle of operation
The sampled analog phase currents are pre-processed and for each phase current the
true RMS value of each phase current is derived. These phase current values are fed to
the Thermal overload protection, two time constants (TRPTTR, 49).
From the largest of the three phase currents a relative final temperature (heat content)
is calculated according to the expression:
Q final
I
=
I ref
(Equation 10)
EQUATION1171 V1 EN
where:
I
Iref
If this calculated relative temperature is larger than the relative temperature level
corresponding to the set operate (trip) current a pickup output signal PICKUP is activated.
The actual temperature at the actual execution cycle is calculated as:
188
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
If
Q final > Q n
(Equation 11)
EQUATION1172 V1 EN
Dt
Qn = Qn -1 + ( Q final - Q n-1 ) 1 - e t
(Equation 12)
EQUATION1173 V1 EN
If
Q final < Qn
(Equation 13)
EQUATION1174 V1 EN
Qn = Q final - ( Q final - Q n -1 ) e
Dt
(Equation 14)
EQUATION1175 V1 EN
where:
Qn
Qn-1
Qfinal
is the calculated final (steady state) temperature with the actual current
Dt
is the time step between calculation of the actual and final temperature
is the set thermal time constant Tau1 or Tau2 for the protected transformer
Q
- Qoperate
toperate = -t ln final
Q final - Q n
EQUATION1176 V1 EN
(Equation 15)
The calculated time to trip can be monitored as it is exported from the function as a
real figure TTRIP.
189
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated when
the temperature of the object is above the set lockout release temperature setting ResLo.
The time to lockout release is calculated, That is, a calculation of the cooling time to a
set value.
Q
- Qlockout _ release
tlockout _ release = -t ln final
Q
Q
final
n
EQUATION1177 V1 EN
(Equation 16)
In the above equation, the final temperature is calculated according to equation 10.
Since the transformer normally is disconnected, the current I is zero and thereby the
final is also zero. The calculated component temperature can be monitored as it is
exported from the function as a real figure, TRESLO.
When the current is so high that it has given a pickup signal PICKUP, the estimated
time to trip is continuously calculated and given as analog output TTRIP. If this
calculated time get less than the setting time Warning, set in minutes, the output
WARNING is activated.
In case of trip a pulse with a set duration tPulse is activated.
190
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
PICKUP
Final Temp
> TripTemp
Calculation
of heat
content
I3P
Calculation
of final
temperature
ALARM1
ALARM2
Management of
setting
parameters: Tau,
IBase
S
R
Tau used
LOCKOUT
Actual Temp
< Recl
Temp
Calculation
of time to
trip
Calculation
of time to
reset of
lockout
time to trip
warning if time to trip < set value
en05000833_ansi.vsd
ANSI05000833 V1 EN
Figure 78:
191
Technical reference manual
Section 6
Current protection
6.3.3
1MRK505208-UUS D
Function block
TRPTTR (49)
I3P*
TRIP
BLOCK
PICKUP
COOLING
ALARM1
MULTPU
ALARM2
RESET
LOCKOUT
WARNING
ANSI06000272-2-en.vsd
ANSI06000272 V2 EN
Figure 79:
6.3.4
Default
Description
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
COOLING
BOOLEAN
MULTPU
BOOLEAN
RESET
BOOLEAN
Reset of function
Table 101:
Name
Description
TRIP
BOOLEAN
Trip Signal
PICKUP
BOOLEAN
Pickup signal
ALARM1
BOOLEAN
ALARM2
BOOLEAN
LOCKOUT
BOOLEAN
Lockout signal
WARNING
BOOLEAN
192
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.3.5
Table 102:
Setting parameters
TRPTTR (49) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IBase
1 - 99999
3000
Base current in A
IRef
10.0 - 1000.0
%IB
1.0
100.0
IRefMult
0.01 - 10.00
0.01
1.00
IBase1
30.0 - 250.0
%IB
1.0
100.0
IBase2
30.0 - 250.0
%IB
1.0
100.0
Tau1
1.0 - 500.0
Min
1.0
60.0
Tau2
1.0 - 500.0
Min
1.0
60.0
IHighTau1
30.0 - 250.0
%IB1
1.0
100.0
Tau1High
5 - 2000
%tC1
100
ILowTau1
30.0 - 250.0
%IB1
1.0
100.0
Tau1Low
5 - 2000
%tC1
100
IHighTau2
30.0 - 250.0
%IB2
1.0
100.0
Tau2High
5 - 2000
%tC2
100
ILowTau2
30.0 - 250.0
%IB2
1.0
100.0
Tau2Low
5 - 2000
%tC2
100
ITrip
50.0 - 250.0
%IBx
1.0
110.0
Alarm1
50.0 - 99.0
%Itr
1.0
80.0
Alarm2
50.0 - 99.0
%Itr
1.0
90.0
LockoutReset
10.0 - 95.0
%Itr
1.0
60.0
193
Technical reference manual
Section 6
Current protection
Name
1MRK505208-UUS D
Unit
Step
Default
ThetaInit
0.0 - 95.0
1.0
50.0
Warning
1.0 - 500.0
Min
0.1
30.0
tPulse
0.01 - 0.30
0.01
0.10
6.3.6
Values (Range)
Description
Technical data
Table 103:
Function
Range or value
Accuracy
(30250)% of IBase
1.0% of In
Operate time:
Operate current
(50250)% of IBase
1.0% of In
I 2 - I p2
t = t ln 2
I - Ib 2
EQUATION1356 V1 EN
(Equation 17)
I = Imeasured
6.4
IEC 61850
identification
IEC 60617
identification
CCRBRF
ANSI/IEEE C37.2
device number
50BF
3I>BF
SYMBOL-U V1 EN
6.4.1
Introduction
Breaker failure protection (CCRBRF) ensures fast back-up tripping of surrounding
breakers in case the own breaker fails to open. CCRBRF (50BF) can be current based,
contact based, or an adaptive combination of these two conditions.
194
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Current check with extremely short reset time is used as check criterion to achieve high
security against inadvertent operation.
Contact check criteria can be used where the fault current through the breaker is small.
CCRBRF (50BF) can be single- or three-phase initiated to allow use with single pole
tripping applications. For the three-phase version of CCRBRF (50BF) the current
criteria can be set to operate only if two out of four for example, two phases or one
phase plus the residual current pickups. This gives a higher security to the back-up trip
command.
CCRBRF (50BF) function can be programmed to give a single- or three-phase re-trip
of the own breaker to avoid unnecessary tripping of surrounding breakers at an
incorrect initiation due to mistakes during testing.
6.4.2
Operation principle
Breaker failure protection CCRBRF (50BF) is initiated from protection trip command,
either from protection functions within the IED or from external protection devices.
The initiate signal can be phase selective or general (for all three phases). Phase
selective initiate signals enable single pole re-trip function. This means that a second
attempt to open the breaker is done. The re-trip attempt can be made after a set time
delay. For transmission lines single pole trip and autoreclosing is often used. The retrip function can be phase selective if it is initiated from phase selective line protection.
The re-trip function can be done with or without current check. With the current check
the re-trip is only performed if the current through the circuit breaker is larger than the
operate current level.
The initiate signal can be an internal or external protection trip signal. This signal will
initiate the back-up trip timer. If the opening of the breaker is successful this is
detected by the function, by detection of either low current through RMS evaluation
and a special adapted current algorithm or by open contact indication. The special
algorithm enables a very fast detection of successful breaker opening, that is, fast
resetting of the current measurement. If the current and/or contact detection has not
detected breaker opening before the back-up timer has run its time a back-up trip is
initiated.
Further the following possibilities are available:
The minimum length of the re-trip pulse, the back-up trip pulse and the back-up
trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-up
trip pulse 2 will however sustain as long as there is an indication of closed breaker.
In the current detection it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out of 4
where it is sufficient to detect failure to open (high current) in one pole or high
195
Section 6
Current protection
1MRK505208-UUS D
residual current and 2 out of 4 where at least two current (phase current and/or
residual current) shall be high for breaker failure detection.
The current detection level for the residual current can be set different from the
setting of phase current detection.
It is possible to have different back-up time delays for single-phase faults and for
multi-phase faults.
The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
It is possible to have instantaneous back-up trip function if a signal is high if the
circuit breaker is insufficient to clear faults, for example at low gas pressure.
30 ms
BFI_3P
BFI_A
BFP Started A
OR
AND
S
R
BLOCK
SR
150ms
Time out A
AND
OR
Reset A
OR
ANSI09000976-2-en.vsd
ANSI09000976 V2 EN
Figure 80:
Pickup_PH
a
b
FunctionMode
a>b
Current
OR
AND
OR
Time out A
OR
I_A
AND
Current High A
CB Closed A
AND
OR
BFP Started A
a
Pickup_BlkCont
52a_A
Reset A
Contact
a>b
AND
OR
AND
AND
AND
Contact Closed A
ANSI09000977-1-en.vsd
ANSI09000977 V1 EN
Figure 81:
196
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
BFP Started A
RetripMode
OR
TRRET
OR
TRRET_A
OR
OR
AND
CB Pos Check
CB Closed A
52FAIL
TRRET_B
tPulse
AND
No CBPos Check
1
TRRET_C
From other
phases
t1
0
AND
ANSI09000978-4-en.vsd
ANSI09000978 V4 EN
Figure 82:
BFP Started A
BFP Started B
AND
BFP Started C
AND
IN
Pickup_N
BUTripMode
1
From other
phases
a>b
Contact Closed A
2 out of 4
1 out of 4
1 out of 3
Current High B
Current High C
OR
OR
Current High A
52FAIL
AND
AND
BFP Started A
t2
OR
0
AND
OR
From other
phases
BFP Started B
AND
AND
Backup Trip A
t2MPh
0
OR
tPulse
OR
2 of 3
OR
TRBU
tPulse
BFP Started C
S
AND
SR
t3
OR
TRBU2
ANSI09000979-4-en.vsd
ANSI09000979 V4 EN
Figure 83:
Internal logical signals PU_A, PU_B, PU_C have logical value 1 when current in
respective phase has magnitude larger than setting parameter Pickup_PH.
197
Technical reference manual
Section 6
Current protection
6.4.3
1MRK505208-UUS D
Function block
CCRBRF (50BF)
I3P*
BLOCK
BFI_3P
BFI_A
BFI_B
BFI_C
52A_A
52A_B
52A_C
52FAIL
TRBU
TRBU2
TRRET
TRRET_A
TRRET_B
TRRET_C
CBALARM
ANSI06000188-2-en.vsd
ANSI06000188 V2 EN
Figure 84:
6.4.4
Default
Description
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BFI_3P
BOOLEAN
BFI_A
BOOLEAN
BFI_B
BOOLEAN
BFI_C
BOOLEAN
52a_A
BOOLEAN
52a_B
BOOLEAN
52a_C
BOOLEAN
52FAIL
BOOLEAN
Table 105:
Name
Description
TRBU
BOOLEAN
TRBU2
BOOLEAN
TRRET
BOOLEAN
TRRET_A
BOOLEAN
TRRET_B
BOOLEAN
TRRET_C
BOOLEAN
CBALARM
BOOLEAN
198
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.4.5
Table 106:
Setting parameters
CCRBRF (50BF) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IBase
1 - 99999
3000
Base current
FunctionMode
Current
Contact
Current&Contact
Current
BuTripMode
2 out of 4
1 out of 3
1 out of 4
1 out of 3
RetripMode
Retrip Off
CB Pos Check
No CBPos Check
Retrip Off
Pickup_PH
5 - 200
%IB
10
Pickup_N
2 - 200
%IB
10
t1
0.000 - 60.000
0.001
0.000
t2
0.000 - 60.000
0.001
0.150
t2MPh
0.000 - 60.000
0.001
0.150
tPulse
0.000 - 60.000
0.001
0.200
Table 107:
Name
Values (Range)
Unit
Step
Default
Description
Pickup_BlkCont
5 - 200
%IB
20
t3
0.000 - 60.000
0.001
0.030
tCBAlarm
0.000 - 60.000
0.001
5.000
6.4.6
Technical data
Table 108:
Function
Range or value
Accuracy
(5-200)% of lBase
1.0% of In at I In
1.0% of I at I > In
> 95%
(2-200)% of lBase
1.0% of In at I In
1.0% of I at I > In
Section 6
Current protection
1MRK505208-UUS D
Function
6.5
Range or value
Accuracy
> 95%
(5-200)% of lBase
1.0% of In at I In
1.0% of I at I > In
Reset ratio
> 95%
Timers
(0.000-60.000) s
0.5% 10 ms
10 ms typically
15 ms maximum
IEC 61850
identification
IEC 60617
identification
CCSRBRF
ANSI/IEEE C37.2
device number
50BF
I>BF
SYMBOL-II V1 EN
6.5.1
Introduction
Breaker failure protection, single phase version (CCSRBRF, 50BF) function ensures
fast back-up tripping of surrounding breakers.
A current check with extremely short reset time is used as check criteria to achieve a
high security against unnecessary operation.
CCSRBRF (50BF) can be programmed to give a re-trip of the own breaker to avoid
unnecessary tripping of surrounding breakers at an incorrect initiation due to mistakes
during testing.
6.5.2
Principle of operation
Breaker failure protection, single phase version CCSRBRF (50BF) is initiated from
protection trip command, either from protection functions within the protection IED or
from external protection devices.
200
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
The initiate signal enables the re-trip function. This means that a second attempt to
open the breaker is done. The re-trip attempt can be made after a set time delay. The retrip function can be done with or without current check. With the current check the retrip is only performed if the current through the circuit breaker is larger than the
operate current level.
The initiate signal can be an internal or external protection trip signal. If this initiate
signal gets high at the same time as current is detected through the circuit breaker, the
back-up trip timer is started. If the opening of the breaker is successful this is detected
by the function, both by detection of low RMS current and by a special adapted
algorithm. The special algorithm enables a very fast detection of successful breaker
opening, that is, fast resetting of the current measurement. If the current detection has
not detected breaker opening before the set back-up time has elapsed, a back-up trip is
initiated. There is also a possibility to have a second back-up trip output activated a
settable time after the first back-up trip.
Further the following possibilities are available:
The minimum length of the re-trip pulse, the back-up trip pulse and the back-up
trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the back-up
trip pulse 2 will however sustain as long as there is an indication of closed breaker.
The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
It is possible to have instantaneous back-up trip function if a signal (52FAIL) is
high due to that circuit breaker is unable to clear faults, for example at low gas
pressure.
Current
AND
BLOCK
BFI_A
AND
tp
Current &
Contact
AND
OR
BFI_A
0-t1
0
TRRET
OR
52a
AND
AND
Contact
en06000150_ansi.vsd
ANSI06000150 V1 EN
Figure 85:
Internal logical signalBFI_A has logical value 1 when current in that phase has
magnitude larger than setting parameter Pickup_PH.
201
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Current
AND
tp
TRBU
Current &
Contact
pickup
AND
AND
OR
0-t2
0
OR
BFI
tp
0-t3
0
TRBU2
OR
52a
AND
Contact
AND
52FAIL
CBALARM
0-CBAlarm
0
en06000156_ansi.vsd
ANSI06000156 V1 EN
Figure 86:
6.5.3
Function block
CCSRBRF (50BF)
ISI*
BLOCK
BFI
52A
52FAIL
TRBU
TRBU2
TRRET
CBALARM
ANSI06000158-2-en.vsd
ANSI06000158 V2 EN
Figure 87:
6.5.4
Default
Description
ISI
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BFI
BOOLEAN
52a
BOOLEAN
52FAIL
BOOLEAN
202
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Table 110:
Name
6.5.5
Table 111:
Type
Description
TRBU
BOOLEAN
TRBU2
BOOLEAN
TRRET
BOOLEAN
CBALARM
BOOLEAN
Setting parameters
CCSRBRF (50BF) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IBase
1 - 99999
3000
FunctionMode
Current
Contact
Current&Contact
Current
RetripMode
Retrip Off
Current_Check
No_Current_Check
Retrip Off
Pickup_PH
5 - 200
%IB
10
Pickup_BlkCont
5 - 200
%IB
20
t1
0.000 - 60.000
0.001
0.000
t2
0.000 - 60.000
0.001
0.150
t3
0.000 - 60.000
0.001
0.030
tCBAlarm
0.000 - 60.000
0.001
5.000
tPulse
0.000 - 60.000
0.001
0.200
6.5.6
Technical data
Table 112:
Function
Range or value
Accuracy
(5-200)% of lBase
1.0% of In at I In
1.0% of I at I > In
> 95%
(5-200)% of lBase
1.0% of In at I In
1.0% of I at I > In
Reset ratio
> 95%
Section 6
Current protection
1MRK505208-UUS D
Function
6.6
Range or value
Accuracy
Timers
(0.000-60.000) s
0.5% 10 ms
10 ms typically
15 ms maximum
IEC 61850
identification
GUPPDUP
IEC 60617
identification
P<
ANSI/IEEE C37.2
device number
37
SYMBOL-LL V1 EN
6.6.1
Introduction
The task of a generator in a power plant is to convert mechanical energy available as a
torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it
does not cover bearing losses and ventilation losses. Then, the synchronous generator
becomes a synchronous motor and starts to take electric power from the rest of the
power system. This operating state, where individual synchronous machines operate as
motors, implies no risk for the machine itself. If the generator under consideration is
very large and if it consumes lots of electric power, it may be desirable to disconnect it
to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state.
The task of the reverse power protection is to protect the turbine and not to protect the
generator itself.
Figure 88 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a higher
margin and should provide better dependability. On the other hand, the risk for
unwanted operation immediately after synchronization may be higher. One should set
the underpower IED to trip if the active power from the generator is less than about
2%. One should set the overpower IED to trip if the power flow from the network to
the generator is higher than 1% depending on the type of turbine.
204
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
When IED with a metering class input CTs is used pickup can be set to more sensitive
value (e.g.0,5% or even to 0,2%).
Underpower IED
Operate
Line
Overpower IED
Operate
Line
Margin
Margin
Operating point
without
turbine torque
Operating point
without
turbine torque
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Figure 88:
6.6.2
Principle of operation
A simplified scheme showing the principle of the power protection function is shown
in figure 89. The function has two stages with individual settings.
Chosen current
phasors
Chosen voltage
phasors
P
Complex
power
calculation
Derivation of
S( composant)
in Char angle
S( angle)
S( angle) <
Power1
t
0
TRIP1
PICKUP1
S( angle) <
Power2
t
0
TRIP2
PICKUP2
P = POWRE
Q = POWIM
ANSI06000438-2-en.vsd
ANSI06000438 V2 EN
Figure 89:
205
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 113.
Table 113:
Set value: Mode
A, B, C
S = V A I A* + VB I B* + VC I C *
(Equation 18)
EQUATION2055-ANSI V1 EN
Arone
S = V AB I A* - VBC IC *
(Equation 19)
EQUATION2056-ANSI V1 EN
PosSeq
S = 3 VPosSeq I PosSeq*
(Equation 20)
EQUATION2057-ANSI V1 EN
AB
S = VAB ( I A* - I B* )
(Equation 21)
EQUATION2058-ANSI V1 EN
BC
S = VBC ( I B* - IC * )
(Equation 22)
EQUATION2059-ANSI V1 EN
CA
S = VCA ( I C * - I A* )
EQUATION2060-ANSI V1 EN
S = 3 VA I A*
EQUATION2061-ANSI V1 EN
(Equation 24)
S = 3 VB I B*
EQUATION2062-ANSI V1 EN
(Equation 23)
(Equation 25)
S = 3 VC I C *
EQUATION2063-ANSI V1 EN
(Equation 26)
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is
calculated. If this angle is 0 the active power component P is calculated. If this angle
is 90 the reactive power component Q is calculated.
206
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
The calculated power component is compared to the power pick up setting Power1(2).
For directional underpower protection, a pickup signal PICKUP1(2) is activated if the
calculated power component is smaller than the pick up value. For directional
overpower protection, a pickup signal PICKUP1(2) is activated if the calculated power
component is larger than the pick up value. After a set time delay TripDelay1(2) a trip
TRIP1(2) signal is activated if the pickup signal is still active. At activation of any of
the two stages a common signal PICKUP will be activated. At trip from any of the two
stages also a common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) + drop-power1(2)). For
generator low forward power protection the power setting is very low, normally down
to 0.02 p.u. of rated generator power. The hysteresis should therefore be set to a
smaller value. The drop-power value of stage1 can be calculated with the Power1(2),
Hysteresis1(2): drop-power1(2) = Power1(2) + Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the droppower1(2) would be too small. In such cases, the hysteresis1 greater than (0.5
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value, the function will reset
after a set time DropDelay1(2). The reset means that the pickup signal will drop out
and that the timer of the stage will reset.
6.6.2.1
S = TD SOld + (1 TD ) SCalculated
EQUATION1959-ANSI V1 EN
(Equation 27)
Where
S
Sold
is the measured value given from the function in previous execution cycle
is settable parameter by the end user which influence the filter properties
Default value for parameter TD is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
207
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
When TD is set to value bigger than 0, the filtering is enabled. A typical value for
TD=0.92 in case of slow operating functions.
6.6.2.2
Magnitude
compensation
+10
IMagComp5
Measured
current
IMagComp30
IMagComp100
30
-10
Degrees
100
% of In
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
Angle
compensation
+10
Measured
current
IAngComp30
IAngComp5
IAngComp100
30
100
% of In
-10
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN
Figure 90:
Calibration curves
The first current and voltage phase in the group signals will be used as reference and
the amplitude and angle compensation will be used for related input signals.
Analog outputs (Monitored data) from the function can be used for service values or in
the disturbance report. The active power is provided as MW value: P, or in percent of
base power: PPERCENT. The reactive power is provided as Mvar value: Q, or in
percent of base power: QPERCENT.
208
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.6.3
Function block
GUPPDUP (37)
I3P*
V3P*
BLOCK
BLOCK1
BLOCK2
TRIP
TRIP1
TRIP2
PICKUP
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI07000027-2-en.vsd
ANSI07000027 V2 EN
Figure 91:
6.6.4
Default
Description
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLOCK1
BOOLEAN
Block of stage 1
BLOCK2
BOOLEAN
Block of stage 2
Table 115:
Name
Description
TRIP
BOOLEAN
TRIP1
BOOLEAN
Trip of stage 1
TRIP2
BOOLEAN
Trip of stage 2
PICKUP
BOOLEAN
Common pickup
PICKUP1
BOOLEAN
Pickup of stage 1
PICKUP2
BOOLEAN
Pickup of stage 2
REAL
Active Power in MW
PPERCENT
REAL
REAL
QPERCENT
REAL
209
Technical reference manual
Section 6
Current protection
6.6.5
Table 116:
Name
1MRK505208-UUS D
Setting parameters
GUPPDUP (37) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
OpMode1
Disabled
UnderPower
UnderPower
Operation mode 1
Power1
0.0 - 500.0
%SB
0.1
1.0
Angle1
-180.0 - 180.0
Deg
0.1
0.0
TripDelay1
0.010 - 6000.000
0.001
1.000
DropDelay1
0.010 - 6000.000
0.001
0.060
OpMode2
Disabled
UnderPower
UnderPower
Operation mode 2
Power2
0.0 - 500.0
%SB
0.1
1.0
Angle2
-180.0 - 180.0
Deg
0.1
0.0
TripDelay2
0.010 - 6000.000
0.001
1.000
DropDelay2
0.010 - 6000.000
0.001
0.060
Table 117:
Name
Unit
Step
Default
Description
TD
0.000 - 0.999
0.001
0.000
Hysteresis1
0.2 - 5.0
pu
0.1
0.5
Hysteresis2
0.2 - 5.0
pu
0.1
0.5
IMagComp5
-10.000 - 10.000
0.001
0.000
IMagComp30
-10.000 - 10.000
0.001
0.000
IMagComp100
-10.000 - 10.000
0.001
0.000
VMagComp5
-10.000 - 10.000
0.001
0.000
VMagComp30
-10.000 - 10.000
0.001
0.000
VMagComp100
-10.000 - 10.000
0.001
0.000
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
210
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Table 118:
Name
Values (Range)
Unit
Step
Default
Description
IBase
1 - 99999
3000
VBase
0.05 - 2000.00
kV
0.05
400.00
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
Pos Seq
6.6.6
Technical data
Table 119:
Function
Power level
Range or value
(0.0500.0)% of SBase
At low setting:
(0.5-2.0)% of SBase
(2.0-10)% of SBase
6.7
Accuracy
1.0% of Sr at S < Sr
1.0% of S at S > Sr
< 50% of set value
< 20% of set value
Characteristic angle
(-180.0180.0) degrees
2 degrees
Timers
(0.00-6000.00) s
0.5% 10 ms
IEC 61850
identification
GOPPDOP
IEC 60617
identification
P>
ANSI/IEEE C37.2
device number
32
DOCUMENT172362-IMG158942
V1 EN
6.7.1
Introduction
The task of a generator in a power plant is to convert mechanical energy available as a
torque on a rotating shaft to electric energy.
211
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Sometimes, the mechanical power from a prime mover may decrease so much that it
does not cover bearing losses and ventilation losses. Then, the synchronous generator
becomes a synchronous motor and starts to take electric power from the rest of the
power system. This operating state, where individual synchronous machines operate as
motors, implies no risk for the machine itself. If the generator under consideration is
very large and if it consumes lots of electric power, it may be desirable to disconnect it
to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous state.
The task of the reverse power protection is to protect the turbine and not to protect the
generator itself.
Figure 92 illustrates the low forward power and reverse power protection with
underpower and overpower functions respectively. The underpower IED gives a higher
margin and should provide better dependability. On the other hand, the risk for
unwanted operation immediately after synchronization may be higher. One should set
the underpower IED to trip if the active power from the generator is less than about
2%. One should set the overpower IED to trip if the power flow from the network to
the generator is higher than 1%.
When IED with a metering class input CTs is used pickup can be set to more sensitive
value (e.g.0,5% or even to 0,2%).
Underpower IED
Operate
Line
Overpower IED
Operate
Line
Margin
Margin
Operating point
without
turbine torque
Operating point
without
turbine torque
IEC06000315-2-en.vsd
IEC06000315 V2 EN
Figure 92:
6.7.2
Principle of operation
A simplified scheme showing the principle of the power protection function is shown
in figure 93. The function has two stages with individual settings.
212
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Chosen current
phasors
Chosen voltage
phasors
P
Complex
power
calculation
Derivation of
S(composant)
in Char angle
S(angle)
S(angle) >
Power1
TRIP1
PICKUP1
S(angle) >
Power2
TRIP2
PICKUP2
P = POWRE
Q = POWIM
ANSI06000567-2-en.vsd
ANSI06000567 V2 EN
Figure 93:
The function will use voltage and current phasors calculated in the pre-processing
blocks. The apparent complex power is calculated according to chosen formula as
shown in table 120.
Table 120:
S = V A I A + V B I B + V C IC
(Equation 28)
EQUATION2038 V1 EN
Arone
S = V AB I A - V BC I C
S = 3 V PosSeq I PosSeq
(Equation 30)
EQUATION2040 V1 EN
A,B
S = V AB (I A - I B )
(Equation 31)
EQUATION2041 V1 EN
B,C
(Equation 29)
EQUATION2039 V1 EN
PosSeq
S = V BC (I B - I C )
EQUATION2042 V1 EN
(Equation 32)
213
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
S = V CA (I C - I A )
(Equation 33)
EQUATION2043 V1 EN
S = 3 V A IA
(Equation 34)
EQUATION2044 V1 EN
S = 3 V B IB
(Equation 35)
EQUATION2045 V1 EN
S = 3 V C IC
EQUATION2046 V1 EN
(Equation 36)
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction Angle1(2) is
calculated. If this angle is 0 the active power component P is calculated. If this angle
is 90 the reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting Power1(2).
A pickup signal PICKUP1(2) is activated if the calculated power component is larger
than the pick up value. After a set time delay TripDelay1(2) a trip TRIP1(2) signal is
activated if the pickup signal is still active. At activation of any of the two stages a
common signal PICKUP will be activated. At trip from any of the two stages also a
common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is Hysteresis1(2) = abs (Power1(2) drop-power1(2)). For
generator reverse power protection the power setting is very low, normally down to
0.02 p.u. of rated generator power. The hysteresis should therefore be set to a smaller
value. The drop-power value of stage1 can be calculated with the Power1(2),
Hysteresis1(2): drop-power1(2) = Power1(2) Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the droppower1(2) would be too small. In such cases, the hysteresis1 greater than (0.5
Power1(2)) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset
after a set time DropDelay1(2). The reset means that the pickup signal will drop out ant
that the timer of the stage will reset.
214
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.7.2.1
EQUATION1959 V1 EN
Where
S
Sold
is the measured value given from the function in previous execution cycle
is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for k =
0.92 in case of slow operating functions.
6.7.2.2
215
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
% of In
Magnitude
compensation
+10
IMagComp5
Measured
current
IMagComp30
IMagComp100
30
-10
Degrees
100
% of In
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
Angle
compensation
+10
Measured
current
IAngComp30
IAngComp5
IAngComp100
30
100
% of In
-10
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN
Figure 94:
Calibration curves
The first current and voltage phase in the group signals will be used as reference and
the amplitude and angle compensation will be used for related input signals.
Analog outputs from the function can be used for service values or in the disturbance
report. The active power is provided as MW value: P, or in percent of base power:
PPERCENT. The reactive power is provided as Mvar value: Q, or in percent of base
power: QPERCENT.
216
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.7.3
Function block
GOPPDOP (32)
I3P*
V3P*
BLOCK
BLOCK1
BLOCK2
TRIP
TRIP1
TRIP2
PICKUP
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI07000028-2-en.vsd
ANSI07000028 V2 EN
Figure 95:
6.7.4
Default
Description
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLOCK1
BOOLEAN
Block of stage 1
BLOCK2
BOOLEAN
Block of stage 2
Table 122:
Name
Description
TRIP
BOOLEAN
TRIP1
BOOLEAN
Trip of stage 1
TRIP2
BOOLEAN
Trip of stage 2
PICKUP
BOOLEAN
Common pickup
PICKUP1
BOOLEAN
Pickup of stage 1
PICKUP2
BOOLEAN
Pickup of stage 2
REAL
Active Power in MW
PPERCENT
REAL
REAL
QPERCENT
REAL
217
Technical reference manual
Section 6
Current protection
6.7.5
Table 123:
Name
1MRK505208-UUS D
Setting parameters
GOPPDOP (32) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
OpMode1
Disabled
OverPower
OverPower
Operation mode 1
Power1
0.0 - 500.0
%SB
0.1
120.0
Angle1
-180.0 - 180.0
Deg
0.1
0.0
TripDelay1
0.010 - 6000.000
0.001
1.000
DropDelay1
0.010 - 6000.000
0.001
0.060
OpMode2
Disabled
OverPower
OverPower
Operation mode 2
Power2
0.0 - 500.0
%SB
0.1
120.0
Angle2
-180.0 - 180.0
Deg
0.1
0.0
TripDelay2
0.010 - 6000.000
0.001
1.000
DropDelay2
0.010 - 6000.000
0.001
0.060
Table 124:
Name
Unit
Step
Default
Description
0.000 - 0.999
0.001
0.000
Hysteresis1
0.2 - 5.0
pu
0.1
0.5
Hysteresis2
0.2 - 5.0
pu
0.1
0.5
IMagComp5
-10.000 - 10.000
0.001
0.000
IMagComp30
-10.000 - 10.000
0.001
0.000
IMagComp100
-10.000 - 10.000
0.001
0.000
VMagComp5
-10.000 - 10.000
0.001
0.000
VMagComp30
-10.000 - 10.000
0.001
0.000
VMagComp100
-10.000 - 10.000
0.001
0.000
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
218
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Table 125:
Name
Values (Range)
Unit
Step
Default
Description
IBase
1 - 99999
3000
VBase
0.05 - 2000.00
kV
0.05
400.00
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
Pos Seq
6.7.6
Technical data
Table 126:
Function
Range or value
Power level
Accuracy
(0.0500.0)% of Sbase
1.0% of Sr at S < Sr
1.0% of S at S > Sr
At low setting:
(0.5-2.0)% of Sbase
(2.0-10)% of Sbase
6.8
6.8.1
Characteristic angle
(-180.0180.0) degrees
2 degrees
Timers
(0.00-6000.00) s
0.5% 10 ms
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
CBPGAPC
Introduction
Shunt Capacitor Banks (SCB) are used in a power system to provide reactive power
compensation and power factor correction. They are as well used as integral parts of
Static Var Compensators (SVC) or Harmonic Filters installations. Capacitor bank
protection (CBPGAPC) function is specially designed to provide protection and
supervision features for SCBs.
219
Technical reference manual
Section 6
Current protection
6.8.2
1MRK505208-UUS D
Principle of operation
Capacitor bank protection (CBPGAPC) function measures the SCB three-phase
current. CBPGAPC function has the following built-in features:
6.8.2.1
Overcurrent stage
Undercurrent stage
Reconnection inhibit
Harmonic overload
Reactive power overload
Measured quantities
Three-phase input current from the SCB is connected via the preprocessing block to
CBPGAPC function. From this preprocessing block CBPGAPC function obtains the
following quantities for every phase:
Current sample values with sampling rate of 1 kHz in 50 Hz power system and 1.2
kHz in 60 Hz power system (that is, 20 samples in fundamental power system
cycle). These samples correspond to the instantaneous current waveform of the
protected SCB and in further text will be marked with symbol i~
Equivalent RMS current value based on Peak Current measurement. This value is
obtained as maximum absolute current sample value over last power system cycle
divided by 2 and in further text will be marked with symbol IpeakRMS
Equivalent true RMS current value based on the following formula:
~m
TRMS
EQUATION2232 V1 EN
m =1
N
(Equation 38)
where N is used number of samples in one power system cycle (that is, 20) and i~m are
last N samples of the current waveform. In further text this equivalent true rms current
quantity will be marked with symbol ITRMS.
Note that the measured IpeakRMS value is available as a service value in primary
amperes for every phase from the function.
From the measured SCB currents, voltage value across every SCB phase is calculated.
This is done by continuous integration of the measured current waveform by using the
following principal equation:
220
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
v ( t) =
1
i (t) t
C
(Equation 39)
EQUATION2233-ANSI V1 EN
Where:
v(t)
i(t)
is capacitance in Farads
By using this integration procedure and subsequent filtering the following quantities
for every phase are calculated within the function:
Voltage sample values with rate of 1 kHz in 50 Hz power system and 1.2 kHz in
60 Hz power system (that is, 20 samples in fundamental power system cycle).
These samples correspond to the instantaneous voltage waveform across the
protected SCB and in further text will be marked with symbol v~
Equivalent rms voltage value based on Peak Voltage measurement. This value is
obtained as maximum absolute voltage sample value over last power system cycle
divided by 2 and in further text will be marked with symbol VpeakRMS
Equivalent true RMS voltage value based on the following formula:
v =
TRMS
~m
m =1
EQUATION2234-ANSI V1 EN
(Equation 40)
Where:
N
is used number of samples in one power system cycle (for example, 20)
v~m
In further text this equivalent true RMS voltage quantity will be marked with symbol
VTRMS
Some additional filtering of the calculated voltage quantities is additionally performed
within the function in order to avoid equivalent RMS voltage values overshooting
during capacitor switching.
In order to avoid dependence of the current integration on exact value of the protected
capacitor bank capacitance the whole integration process is done in per unit system. In
order to convert measured current in primary amperes into per unit value the base
current for the protected capacitor bank shall be known. This value is set as parameter
221
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
IBase and it represents the rated SCB current in primary amperes at fundamental
frequency. This value is calculated for a three-phase SCB as follows:
IBase =
1000 Q [MVAr]
3 V [kV ]
EQUATION2235-ANSI V1 EN
(Equation 41)
Where:
IBase
Q[MVAr]
V[kV]
Once the base current is known the internal voltage calculations can be performed.
Note that the calculated VpeakRMS value is available as a service value in percent for
every phase from the function.
Generated reactive power (Q) by the capacitor bank is calculated within the function
for every phase as given by the following equation:
Q=V
TRMS
TRMS
EQUATION2236-ANSI V1 EN
(Equation 42)
Where:
Q
VTRMS
ITRMS
222
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
I3P
I PeakRMS [A]
Overcurrent
Undercurrent
I TRMS[A]
i~ [A]
IBase
v~ [ pu]
Reconnection Inhibit
TRMS
FILTER
V TRMS[ pu]
PEAK
FILTER
VPeakRMS[pu]
Harmonic Overload
Figure 96:
6.8.2.2
Simplified logic diagram about used analog quantities within one phase
a
b
0.02 s
a>b
CapBank
NOT
Energised
CAPDISC
Phx
ANSI08000345-1-en.vsd
ANSI08000345 V1 EN
Figure 97:
Capacitor bank energization check for one phase. Similar for all three
phases
When SCB is disconnected in all three phases, the reconnection inhibit signal will be
given. This signal will be active until the preset time elapsed and is used to inhibit the
reconnection of charged capacitor bank to live network. The internal logic diagram for
the inhibit feature is shown in figure 98.
223
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
CAPDISC
_ Ph1
CAPDISC
CAPDISC Ph2
tReconnInhibit
AND
RECNINH
AND
CAPDISC Ph3
AND
Z-2
Z-2
en08000346.vsd
IEC08000346 V1 EN
Figure 98:
6.8.2.3
Overcurrent feature
The overcurrent protection feature protects the capacitor bank from excessive current
conditions. The sub function takes the current peakRMS value from the preprocessing
block in the IED as input. The peakRMS value of the current is compared with the
setting of parameter PU 51. Whenever the peakRMS value of the current crosses the
set level the function sends a Pickup signal as output. The signal is passed through the
definite timer for giving the TRIP signal. Each phase will have its own Pickup and
TRIP signals for overcurrent. The internal logic for the overcurrent feature is shown in
fig 99.
IPeakRMS
PU 51
a
b
tOC
a>b
AND
OperationOC=Enabled
AND
TROC
PU_OC
BLKTR
BLKOC
BLOCK
OR
ANSI08000350-1-en.vsd
ANSI08000350 V1 EN
Figure 99:
6.8.2.4
Undercurrent feature
Undercurrent protection feature is used to disconnect the capacitor bank from the rest
of the power system when the voltage at the capacitor bank terminals is too low for too
long period of time. This sub function uses the current peakRMS value from the
224
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
preprocessing block in the IED as input. The peakRMS value of the current is
compared to the set value of the parameter PU_37. Whenever the peakRMS value of
the current falls below the set undercurrent level, the function will send a Pickup signal
as output. The function can be blocked when the current falls below the cut off level.
The capacitor bank disconnected signals are used for this blocking. This feature will
help to prevent trip operation when the capacitor bank is disconnected from the power
system. The TRIP output signal is delayed by a definite timer. Each phase will have its
own Pickup and TRIP signals for undercurrent. The internal logic for the undercurrent
feature is shown in fig 100.
IPeakRMS
a
b
PU_37
b>a
tUC
AND
Operation37=Enabled
BLUC
BLOCK
AND
TRUC
PU_UC
OR
CAPDISC
BLKTR
ANSI08000351-1-en.vsd
ANSI08000351 V1 EN
Figure 100:
6.8.2.5
225
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
2.3
2.1
1.9
1.7
1.5
1.3
1.1
0.1
10
100
1000
10000
Figure 101:
Main seven operating points for this IDMT curve are defined by IEC/ANSI standards
and they are shown in above figure and summarized in the following table:
Table 127:
VpeakRMS
[pu]
1.15
1.2
1.3
1.4
1.7
2.0
2.2
Time [s]
1800
300
60
15
1.0
0.3
0.12
When parameter K_HOL_IDMT has different value from 1.0 operating time is
proportionally changed (for example, when K_HOL_IDMT =0.9 operating times
will be 90% of the values shown in above figure 101 and table 127)
Between the seven main points in table 127, the operate time is calculate by using
linear interpolation in the logarithmic scale
Integration process is used to calculate the operate time for varying voltage condition
By setting parameter tmin_HOL_IDMT =0.1s standard requirements for minimum
operating time of 100ms for harmonic overload IDMT curve can be fluffed
By setting parameter tMax_HOL_IDMT =2000s operation for small harmonics
overload condition when VpeakRMS is in-between 1.1pu and 1.2pu is assured
Harmonic overload definite time curve has settings facilities for independent pickup
and time delay. It can be used as separate tripping stage or as an alarm stage.
Both of these two harmonic overload stages are active during capacitor bank
energizing and are capable to properly measure and operate up to and including 9th
harmonic.
226
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
The internal logic for harmonic overload feature is shown in figure 102:
PU_HOL_DT_X
UPeakRMS [pu]
HOL_DT_V
a>b
tHOL_DT
AND
OperationHOL=Enabled
OR
AND
TRHOL
BLKHOL
OR
BLOCK
OR
PU_HOL
BLKTR
AND
OperationHOL=Enabled
UPeakRMS [pu]
TR
a
a>b
PU_HOL_DT_V
k_HOL_IDMT
IDMT
b
tMax_HOL_IDMT
tmin_HOL_IDMT
ST
PU_HOL_IDMT_X
UPeakRMS [pu]
ANSI09000752-1-en.vsd
ANSI09000752 V1 EN
Figure 102:
6.8.2.6
227
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Q [pu]
a
a>b
b
UP_QOL
tQOL
AND
Operation QOL=Enabled
AND
TRQOL
BLKTR
BLKQOL
PU_QOL_X
OR
BLOCK
ANSI08000353-1-en.vsd
ANSI08000353 V1 EN
Figure 103:
6.8.3
Function block
CBPGAPC
I3P*
BLOCK
BLKTR
BLKOC
BLUC
BLKUCCUT
BLKQOL
BLKHOL
TRIP
TROC
TRUC
TRQOL
TRHOL
BFI_3P
PU_OC
PU_UC
PU_QOL
PU_HOL
PU_51_A
PU_51_B
PU_51_C
PU_37_A
PU_37_B
PU_37_C
PU_QOL_A
PU_QOL_B
PU_QOL_C
PU_HOL_DT_A
PU_HOL_DT_B
PU_HOL_DT_C
PU_HOL_IDMT_A
PU_HOL_IDMT_B
PU_HOL_IDMT_C
RECNINH
ANSI08000500-1-en.vsd
ANSI08000500 V1 EN
Figure 104:
228
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
6.8.4
Default
Description
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLKOC
BOOLEAN
BLUC
BOOLEAN
BLKUCCUT
BOOLEAN
BLKQOL
BOOLEAN
BLKHOL
BOOLEAN
Table 129:
Name
Description
TRIP
BOOLEAN
TROC
BOOLEAN
TRUC
BOOLEAN
TRQOL
BOOLEAN
TRHOL
BOOLEAN
BFI_3P
BOOLEAN
PU_OC
BOOLEAN
PU_UC
BOOLEAN
PU_QOL
BOOLEAN
PU_HOL
BOOLEAN
PU_51_A
BOOLEAN
PU_51_B
BOOLEAN
PU_51_C
BOOLEAN
PU_37_A
BOOLEAN
PU_37_B
BOOLEAN
PU_37_C
BOOLEAN
PU_QOL_A
BOOLEAN
PU_QOL_B
BOOLEAN
PU_HOL_C
BOOLEAN
PU_HOL_DT_A
BOOLEAN
PU_HOL_DT_B
BOOLEAN
229
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Name
6.8.5
Table 130:
Name
Type
Description
PU_HOL_DT_C
BOOLEAN
PU_HOL_IDMT_A
BOOLEAN
PU_HOL_IDMT_B
BOOLEAN
PU_HOL_IDMT_C
BOOLEAN
RECNINH
BOOLEAN
Setting parameters
CBPGAPC Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
IBase
1 - 99999
3000
OperationRecIn
Disabled
Enabled
Enabled
IRecInhibit
4 - 1000
%IB
10
tReconnInhibit
1.00 - 6000.00
0.01
300.00
OperationOC
Disabled
Enabled
Enabled
overcurrent enable/disable
PU 51
0 - 900
%IB
135
tOC
0.00 - 6000.00
0.01
30.00
Operation37
Disabled
Enabled
Disabled
PU_37
5 - 100
%IB
70
tUC
0.00 - 6000.00
0.01
5.00
Operation QOL
Disabled
Enabled
Enabled
UP _QOL
5 - 900
130
tQOL
1.00 - 6000.00
0.01
60.00
OperationHOL
Disabled
Enabled
Enabled
HOL_DT_V
5 - 500
200
tHOL_DT
0.00 - 6000.00
0.01
10.00
PU_HOL_DT_V
80 - 200
110
230
Technical reference manual
Section 6
Current protection
1MRK505208-UUS D
Name
Step
Default
k_HOL_IDMT
0.50 - 1.50
0.01
1.00
tMax_HOL_IDMT
0.05 - 6000.00
0.01
2000.00
tmin_HOL_IDMT
0.05 - 60.00
0.01
0.10
6.8.6
Values (Range)
Unit
Description
Technical data
Table 131:
Function
Range or value
Accuracy
(0-900)% of lBase
1.0% of In at I < In
1.0% of I at I > In
>95%
10 ms typically
30 ms typically
15 ms typically
(5-100)% of IBase
1.0% of In at I < In
1.0% of I at I > In
<105%
(4-1000)% of IBase
1.0% of In at I < In
1.0% of I at I > In
(5-900)%
1.0% of Sr at S < Sn
1.0% of S at S > Sn
(5-500)%
0.5% of Vn at V<Vn
0.5% of V at V>Vn
(80-200)%
0.5% of Vn at V<Vn
0.5% of V at V>Vn
10% + 50 ms
(0.05-6000.00) s
0.5% 10 ms
(0.05-60.00) s
0.5% 10 ms
Timers
(0.00-6000.00) s
0.5% 10 ms
231
Technical reference manual
232
Section 7
Voltage protection
1MRK505208-UUS D
Section 7
Voltage protection
7.1
IEC 61850
identification
IEC 60617
identification
UV2PTUV
ANSI/IEEE C37.2
device number
27
3U<
SYMBOL-R-2U-GREATER-THAN
V2 EN
7.1.1
Introduction
Undervoltages can occur in the power system during faults or abnormal conditions.
Two step undervoltage protection (UV2PTUV, 27) function can be used to open circuit
breakers to prepare for system restoration at power outages or as long-time delayed backup to primary protection.
UV2PTUV (27) has two voltage steps, each with inverse or definite time delay.
7.1.2
Principle of operation
Two-step undervoltage protection (UV2PTUV ,27) is used to detect low power system
voltage. UV2PTUV (27) has two voltage measuring steps with separate time delays. If
one, two or three phase voltages decrease below the set value, a corresponding
PICKUP signal is generated. UV2PTUV (27) can be set to PICKUP/TRIP based on 1
out of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being below the set point. If
the voltage remains below the set value for a time period corresponding to the chosen
time delay, the corresponding trip signal is issued. To avoid an unwanted trip due to
disconnection of the related high voltage equipment, a voltage controlled blocking of
the function is available, that is, if the voltage is lower than the set blocking level the
233
Section 7
Voltage protection
1MRK505208-UUS D
EQUATION1606 V1 EN
EQUATION1991-ANSI V1 EN
7.1.2.1
Measurement principle
Depending on the set ConnType value, UV2PTUV (27) measures phase-to-ground or
phase-to-phase voltages and compare against set values, Pickup1 and Pickup2. The
parameters OpMode1 and OpMode2 influence the requirements to activate the
PICKUP outputs. Either 1 out of 3, 2 out of 3, or 3 out of 3 measured voltages have to
be lower than the corresponding set point to issue the corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
7.1.2.2
Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse time
undervoltage (TUV). For the inverse time delay three different modes are available:
inverse curve A
inverse curve B
customer programmable inverse curve
234
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
TD
Vpickup < -V
Vpickup <
(Equation 45)
ANSIEQUATION1431 V1 EN
where:
Vpickup
<
Measured voltage
TD 480
Vpickup < -V
- 0.5
32
Vpickup <
2.0
+ 0.055
EQUATION1608 V1 EN
(Equation 46)
TD A
+D
t=
P
Vpickup < -V
-C
B
Vpickup
EQUATION1609 V1 EN
(Equation 47)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval Vpickup< down to
Vpickup< (1.0 CrvSatn/100) the used voltage will be: Vpickup< (1.0 CrvSatn/
100). If the programmable curve is used this parameter must be calculated so that:
CrvSatn
-C > 0
100
EQUATION1435 V1 EN
(Equation 48)
235
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
The lowest voltage is always used for the inverse time delay integration. The details of
the different inverse time characteristics are shown in section 20.3 "Inverse
characteristics".
Figure 105:
Voltage
VL1
VL2
VL3
IDMT Voltage
Time
ANSI12000186-1-en.vsd
Trip signal issuing requires that the undervoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time
mode (DT) and by some special voltage level dependent time curves for the inverse
time mode (TUV). If the pickup condition, with respect to the measured voltage ceases
during the delay time, and is not fulfilled again within a user defined reset time
(tReset1 and tReset2 for the definite time and tIReset1 and tIReset2pickup for the
inverse time) the corresponding pickup output is reset. Here it should be noted that
after leaving the hysteresis area, the pickup condition must be fulfilled again and it is
not sufficient for the signal to only return back to the hysteresis area. Note that for the
undervoltage function the TUV reset time is constant and does not depend on the
voltage fluctuations during the drop-off period. However, there are three ways to reset
the timer, either the timer is reset instantaneously, or the timer value is frozen during
the reset time, or the timer value is linearly decreased during the reset time. See
figure 106 and figure 107.
236
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
tIReset1
Voltage
tIReset1
PICKUP
HystAbs1
Measured
Voltage
TRIP
PICKUP1
Time
t
PICKUP
TRIP
Time
Integrator
Frozen Timer
Instantaneous
Linearly
decreased
Time
ANSI05000010-3-en.vsd
ANSI05000010 V3 EN
Figure 106:
Voltage profile not causing a reset of the pickup signal for step 1, and inverse time delay at different
reset types
237
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
tIReset1
Voltage
PICKUP
PICKUP
tIReset1
HystAbs1
Measured Voltage
TRIP
PICKUP 1
Time
t
PICKUP
TRIP
Time
Integrator
Frozen Timer
Time
Instantaneous
Linearly
decreased
ANSI05000011-2-en.vsd
ANSI05000011 V2 EN
Figure 107:
Voltage profile causing a reset of the pickup signal for step 1, and inverse time delay at different
reset types
238
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
When definite time delay is selected the function will operate as shown in figure 108.
Detailed information about individual stage reset/operation behavior is shown in figure
109 and figure 110 respectively. Note that by setting tResetn = 0.0s, instantaneous reset
of the definite time delayed stage is ensured.
PU_ST1
V
Pickup1
a
a<b
R tReset1
TRST1
t1
0
AND
ANSI09000785-3-en.vsd
ANSI09000785 V3 EN
Figure 108:
Pickup1
PU_ST1
TRST1
tReset1
t1
ANSI10000039-3-en.vsd
ANSI10000039 V3 EN
Figure 109:
239
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Pickup1
PU_ST1
TRST1
tReset1
t1
ANSI10000040-3-en.vsd
ANSI10000040 V3 EN
Figure 110:
7.1.2.3
Blocking
It is possible to block Two step undervoltage protection UV2PTUV (27) partially or
completely, by binary input signals or by parameter settings, where:
BLOCK:
BLKTR1:
BLK1:
BLKTR2:
BLK2:
If the measured voltage level decreases below the setting of IntBlkStVal1, either the
trip output of step 1, or both the trip and the PICKUP outputs of step 1, are blocked.
The characteristic of the blocking is set by the IntBlkSel1 parameter. This internal
blocking can also be set to Disabled resulting in no voltage based blocking.
Corresponding settings and functionality are valid also for step 2.
In case of disconnection of the high voltage component the measured voltage will get
very low. The event will PICKUP both the under voltage function and the blocking
function, as seen in figure 111. The delay of the blocking function must be set less than
the time delay of under voltage function.
240
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Disconnection
Normal voltage
Pickup1
Pickup2
tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2
Time
Block step 1
Block step 2
en05000466_ansi.vsd
ANSI05000466 V1 EN
Figure 111:
Blocking function
7.1.2.4
Design
The voltage measuring elements continuously measure the three phase-to-neutral
voltages or the three phase-to-phase voltages. Recursive fourier filters or true RMS
filters of input voltage signals are used. The voltages are individually compared to the
set value, and the lowest voltage is used for the inverse time characteristic integration.
A special logic is included to achieve the 1 out of 3, 2 out of 3 and 3 out of 3 criteria to
fulfill the PICKUP condition. The design of Two step undervoltage protection
UV2PTUV (27) is schematically shown in Figure 112.
241
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
VL1
VL2
VL3
Comparator
VL1 < V1<
Comparator
VL2 < V1<
Comparator
VL3 < V1<
Voltage Phase
Selector
OpMode1
1 out of 3
2 out of 3
3 out of 3
ST1L1
Phase 1
ST1L2
Phase 2
Phase 3
IntBlkStVal1
PICKUP
Time integrator
MinVoltSelector
tIReset1
ResetTypeCrv1
Pickup
t1
t1Reset
&
Trip
Output
Logic
ST1L3
ST1
OR
TR1L1
Step 1
TR1L2
TRIP
TR1L3
TR1
OR
Comparator
VL1 < V2<
Comparator
VL2 < V2<
Comparator
VL3 < V2<
Voltage Phase
Selector
OpMode2
1 out of 3
2 out of 3
3 out of 3
IntBlkStVal2
PICKUP
ST2L1
Phase 1
ST2L2
Phase 2
Pickup
t2
Phase 3 t2Reset
&
Trip
Output
Logic
ST2L3
ST2
OR
TR2L1
Step 2
MinVoltSelector
Time integrator
tIReset2
ResetTypeCrv2
TR2L2
TRIP
TR2L3
TR2
OR
OR
OR
PICKUP
TRIP
ANSI05000012-2-en.vsd
ANSI05000012 V2 EN
Figure 112:
242
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.1.3
Function block
UV2PTUV (27)
V3P*
BLOCK
BLKTR1
BLK1
BLKTR2
BLK2
TRIP
TRST1
TRST1_A
TRST1_B
TRST1_C
TRST2
TRST2_A
TRST2_B
TRST2_C
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
PU_ST2_A
PU_ST2_B
PU_ST2_C
ANSI06000276-2-en.vsd
ANSI06000276 V2 EN
Figure 113:
7.1.4
Default
Description
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLKTR1
BOOLEAN
BLK1
BOOLEAN
Block of step 1
BLKTR2
BOOLEAN
BLK2
BOOLEAN
Block of step 2
Table 133:
Name
Description
TRIP
BOOLEAN
Trip
TRST1
BOOLEAN
TRST1_A
BOOLEAN
TRST1_B
BOOLEAN
TRST1_C
BOOLEAN
TRST2
BOOLEAN
TRST2_A
BOOLEAN
243
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Name
7.1.5
Table 134:
Name
Type
Description
TRST2_B
BOOLEAN
TRST2_C
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2
BOOLEAN
PU_ST2_A
BOOLEAN
PU_ST2_B
BOOLEAN
PU_ST2_C
BOOLEAN
Setting parameters
UV2PTUV (27) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
OperationStep1
Disabled
Enabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
Definite time
OpMode1
1 out of 3
2 out of 3
3 out of 3
1 out of 3
Pickup1
1 - 100
%VB
70
t1
0.00 - 6000.00
0.01
5.00
t1Min
0.000 - 60.000
0.001
5.000
TD1
0.05 - 1.10
0.01
0.05
IntBlkSel1
Disabled
Block of trip
Block all
Disabled
IntBlkStVal1
1 - 100
%VB
20
244
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Name
Values (Range)
Unit
tBlkUV1
0.000 - 60.000
0.001
0.000
HystAbs1
0.0 - 100.0
%VB
0.1
0.5
OperationStep2
Disabled
Enabled
Enabled
Characterist2
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
Definite time
OpMode2
1 out of 3
2 out of 3
3 out of 3
1 out of 3
Pickup2
1 - 100
%VB
50
t2
0.000 - 60.000
0.001
5.000
t2Min
0.000 - 60.000
0.001
5.000
TD2
0.05 - 1.10
0.01
0.05
IntBlkSel2
Disabled
Block of trip
Block all
Disabled
IntBlkStVal2
1 - 100
%VB
20
tBlkUV2
0.000 - 60.000
0.001
0.000
HystAbs2
0.0 - 100.0
%VB
0.1
0.5
Table 135:
Step
Default
Description
Name
Values (Range)
Unit
tReset1
0.000 - 60.000
Step
0.001
Default
0.025
Description
Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tIReset1
0.000 - 60.000
0.001
0.025
ACrv1
0.005 - 200.000
0.001
1.000
BCrv1
0.50 - 100.00
0.01
1.00
CCrv1
0.0 - 1.0
0.1
0.0
DCrv1
0.000 - 60.000
0.001
0.000
Section 7
Voltage protection
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
PCrv1
0.000 - 3.000
0.001
1.000
CrvSat1
0 - 100
tReset2
0.000 - 60.000
0.001
0.025
ResetTypeCrv2
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tIReset2
0.000 - 60.000
0.001
0.025
ACrv2
0.005 - 200.000
0.001
1.000
BCrv2
0.50 - 100.00
0.01
1.00
CCrv2
0.0 - 1.0
0.1
0.0
DCrv2
0.000 - 60.000
0.001
0.000
PCrv2
0.000 - 3.000
0.001
1.000
CrvSat2
0 - 100
Table 136:
Name
ConnType
7.1.6
Unit
Step
Default
PhN DFT
Description
Group selector for connection type
Technical data
Table 137:
Function
Range or value
Accuracy
(1100)% of VBase
0.5% of Vn
Absolute hysteresis
(0100)% of VBase
0.5% of Vn
(1100)% of VBase
0.5% of Vn
Inverse time
characteristics for step 1
and step 2, see table 494
246
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Function
Range or value
Accuracy
(0.00 - 6000.00) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
(0.00060.000) s
0.5% 10 ms
25 ms typically at 2 x Vset to 0 0
7.2
10 ms typically at 2 x Vset to 0
15 ms typically
IEC 61850
identification
IEC 60617
identification
OV2PTOV
ANSI/IEEE C37.2
device number
59
3U>
SYMBOL-C-2U-SMALLER-THAN
V2 EN
7.2.1
Introduction
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, open line ends on long lines etc.
Two step overvoltage protection (OV2PTOV, 59) function can be used to detect open
line ends, normally then combined with a directional reactive over-power function to
supervise the system voltage. When triggered, the function will cause an alarm, switch
in reactors, or switch out capacitor banks.
OV2PTOV (59) has two voltage steps, each of them with inverse or definite time delayed.
OV2PTOV (59) has an extremely high reset ratio to allow settings close to system
service voltage.
7.2.2
Principle of operation
Two step overvoltage protection OV2PTOV (59) is used to detect high power system
voltage. OV2PTOV (59) has two steps with separate time delays. If one-, two- or three247
Section 7
Voltage protection
1MRK505208-UUS D
phase voltages increase above the set value, a corresponding PICKUP signal is issued.
OV2PTOV (59) can be set to PICKUP/TRIP, based on 1 out of 3, 2 out of 3 or 3 out of
3 of the measured voltages, being above the set point. If the voltage remains above the
set value for a time period corresponding to the chosen time delay, the corresponding
trip signal is issued.
The time delay characteristic is individually chosen for the two steps and can be either,
definite time delay or inverse time delay.
The voltage related settings are made in percent of the global set base voltage VBase,
which is set in kV, phase-to-phase.
OV2PTOV (59) can be set to measure phase-to-ground fundamental value, phase-tophase fundamental value, phase-to-ground RMS value or phase-to-phase RMS value.
The choice of measuring is done by the parameter ConnType.
The setting of the analog inputs are given as primary phase-to-ground or phase-tophase voltage. OV2PTOV (59) will operate if the voltage gets higher than the set
percentage of the set base voltage VBase. This means operation for phase-to-ground
voltage over:
Vpickup > (%) VBase(kV ) / 3
(Equation 49)
EQUATION1610 V2 EN
EQUATION1992 V1 EN
7.2.2.1
Measurement principle
All the three voltages are measured continuously, and compared with the set values,
Pickup1 and Pickup2. The parameters OpMode1 and OpMode2 influence the
requirements to activate the PICKUP outputs. Either 1 out of 3, 2 out of 3 or 3 out of 3
measured voltages have to be higher than the corresponding set point to issue the
corresponding PICKUP signal.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
248
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.2.2.2
Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (TOV). For the inverse time delay four different modes are available:
inverse curve A
inverse curve B
inverse curve C
customer programmable inverse curve
t=
(Equation 51)
EQUATION1625 V2 EN
TD 480
0.035
V Vpickup >
32
0.5
Vpickup >
(Equation 52)
ANSIEQUATION2287 V2 EN
TD 480
+ 0.035
V Vpickup >
32
0.5
Vpickup >
(Equation 53)
ANSIEQUATION2288 V2 EN
TD A
V - Vpickup
-C
B
Vpickup
EQUATION1616 V1 EN
+D
(Equation 54)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval Vpickup down to Vpickup
(1.0 CrvSatn/100) the used voltage will be: Vpickup (1.0 CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:
249
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
CrvSatn
-C > 0
100
EQUATION1435 V1 EN
(Equation 55)
The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
integration, see figure 114. The details of the different inverse time characteristics are
shown in section "Inverse characteristics"
Voltage
IDMT Voltage
VA
VB
VC
Time
ANSI05000016-2-en.vsd
ANSI05000016 V2 EN
Figure 114:
Trip signal issuing requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time
mode (DT) and by selected voltage level dependent time curves for the inverse time
mode (TOV). If the PICKUP condition, with respect to the measured voltage ceases
during the delay time, and is not fulfilled again within a user defined reset time
(tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for the inverse
time) the corresponding PICKUP output is reset, after that the defined reset time has
elapsed. Here it should be noted that after leaving the hysteresis area, the PICKUP
condition must be fulfilled again and it is not sufficient for the signal to only return
back to the hysteresis area. The hysteresis value for each step is settable (HystAbs2) to
allow an high and accurate reset of the function. It should be noted that for Two step
overvoltage protection OV2PTOV (59) the TOV reset time is constant and does not
depend on the voltage fluctuations during the drop-off period. However, there are three
250
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
ways to reset the timer, either the timer is reset instantaneously, or the timer value is
frozen during the reset time, or the timer value is linearly decreased during the reset time..
tIReset1
tIReset1
Voltage
PICKUP
TRIP
PU_Overvolt1
HystAbs1
Measured
Voltage
Time
PICKUP
TRIP
Time
Integrator
Frozen Timer
Linearly
decreased
Time
Instantaneous
ANSI05000019-3-en.vsd
ANSI05000019 V3 EN
Figure 115:
Voltage profile not causing a reset of the PICKUP signal for step 1, and inverse time delay
251
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
tIReset1
Voltage
PICKUP
PICKUP
tIReset1
HystAbs1
TRIP
Pickup1
Measured Voltage
Time
t
PICKUP
TRIP
Time
Integrator
Frozen Timer
Time
Instantaneous
Linearly decreased
ANSI05000020-2-en.vsd
ANSI05000020 V2 EN
Figure 116:
Voltage profile causing a reset of the PICKUP signal for step 1, and inverse time delay
252
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
PU_ST1
tReset1
a
a>b
Vpickup>
t1
t
TRST1
AND
OFF
Delay
ON
Delay
ANSI10000100-2-en.vsd
ANSI10000100 V2 EN
Figure 117:
Pickup1
PICKUP
TRIP
tReset1
t1
ANSI10000037-2-en.vsd
ANSI10000037 V2 EN
Figure 118:
253
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Pickup1
PICKUP
TRIP
tReset1
t1
ANSI10000038-2-en.vsd
ANSI10000038 V2 EN
Figure 119:
7.2.2.3
Blocking
It is possible to block Two step overvoltage protection OV2PTOV, (59) partially or
completely, by binary input signals where:
7.2.2.4
BLOCK:
BLKTR1:
BLK1:
BLKTR2:
BLK2:
Design
The voltage measuring elements continuously measure the three phase-to-ground
voltages or the three phase-to-phase voltages. Recursive Fourier filters filter the input
voltage signals. The phase voltages are individually compared to the set value, and the
highest voltage is used for the inverse time characteristic integration. A special logic is
included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria to fulfill the PICKUP
condition. The design of Two step overvoltage protection (OV2PTOV, 59) is
schematically described in figure 120.
254
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
VA
VB
VC
Comparator
VA >
Pickup 1
Comparator
VB >
Pickup 1
Comparator
VC >
Pickup 1
Voltage Phase
Selector
OpMode1
1 out of 3
2 out of 3
3 out of 3
PU_ST1_A
Phase A
PU_ST1_B
Phase B
Phase C
Phase C
PICKUP
Pickup
t1
t1Reset
&
Trip
Output
Logic
PU_ ST1_C
PU_ST1
OR
TRST1-A
Step1
MaxVoltSelect
Time integrator
tIReset1
ResetTypeCrv1
TRST1_B
TRIP
TRST1_C
TRST1
OR
Comparator
VA >
Pickup 2
Comparator
VB >
Pickup 2
Comparator
VC >
Pickup 2
Voltage Phase
Selector
Phase A
OpMode2
1 out of 3
2 out of 3
3 out of 3
Phase B
Phase C
PICKUP
MaxVoltSelect
Time integrator
tIReset2
ResetTypeCrv2
TRIP
PU_ST2_A
PU_ST2_B
Pickup
t2
t2Reset
&
Trip
Output
Logic
PU_ST2_C
PU_ST2
OR
TRST2-A
Step 2
TRST2-B
TRST2-C
TRST2
OR
OR PICKUP
OR
TRIP
ANSI05000013-2-en.vsd
_
.
ANSI05000013 V2 EN
Figure 120:
255
Technical reference manual
Section 7
Voltage protection
7.2.3
1MRK505208-UUS D
Function block
OV2PTOV (59)
V3P*
BLOCK
BLKTR1
BLK1
BLKTR2
BLK2
TRIP
TRST1
TRST1_A
TRST1_B
TRST1_C
TRST2
TRST2_A
TRST2_B
TRST2_C
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
PU_ST2_A
PU_ST2_B
PU_ST2_C
ANSI06000277-2-en.vsd
ANSI06000277 V2 EN
Figure 121:
7.2.4
Default
Description
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLKTR1
BOOLEAN
BLK1
BOOLEAN
Block of step 1
BLKTR2
BOOLEAN
BLK2
BOOLEAN
Block of step 2
Table 139:
Name
Description
TRIP
BOOLEAN
Trip
TRST1
BOOLEAN
TRST1_A
BOOLEAN
TRST1_B
BOOLEAN
TRST1_C
BOOLEAN
TRST2
BOOLEAN
TRST2_A
BOOLEAN
256
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Name
7.2.5
Table 140:
Type
Description
TRST2_B
BOOLEAN
TRST2_C
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2
BOOLEAN
PU_ST2_A
BOOLEAN
PU_ST2_B
BOOLEAN
PU_ST2_C
BOOLEAN
Setting parameters
OV2PTOV (59) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
OperationStep1
Disabled
Enabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time
OpMode1
1 out of 3
2 out of 3
3 out of 3
1 out of 3
Pickup1
1 - 200
%VB
120
t1
0.00 - 6000.00
0.01
5.00
t1Min
0.000 - 60.000
0.001
5.000
TD1
0.05 - 1.10
0.01
0.05
HystAbs1
0.0 - 100.0
%VB
0.1
0.5
OperationStep2
Disabled
Enabled
Enabled
257
Technical reference manual
Section 7
Voltage protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
Characterist2
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time
OpMode2
1 out of 3
2 out of 3
3 out of 3
1 out of 3
Pickup2
1 - 200
%VB
150
t2
0.000 - 60.000
0.001
5.000
t2Min
0.000 - 60.000
0.001
5.000
TD2
0.05 - 1.10
0.01
0.05
HystAbs2
0.0 - 100.0
%VB
0.1
0.5
Table 141:
Name
Unit
tReset1
0.000 - 60.000
Step
0.001
Default
0.025
Description
Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tIReset1
0.000 - 60.000
0.001
0.025
ACrv1
0.005 - 200.000
0.001
1.000
BCrv1
0.50 - 100.00
0.01
1.00
CCrv1
0.0 - 1.0
0.1
0.0
DCrv1
0.000 - 60.000
0.001
0.000
PCrv1
0.000 - 3.000
0.001
1.000
CrvSat1
0 - 100
tReset2
0.000 - 60.000
0.001
0.025
ResetTypeCrv2
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tIReset2
0.000 - 60.000
0.001
0.025
258
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
ACrv2
0.005 - 200.000
0.001
1.000
BCrv2
0.50 - 100.00
0.01
1.00
CCrv2
0.0 - 1.0
0.1
0.0
DCrv2
0.000 - 60.000
0.001
0.000
PCrv2
0.000 - 3.000
0.001
1.000
CrvSat2
0 - 100
Table 142:
Name
ConnType
7.2.6
Values (Range)
PhN DFT
PhPh DFT
PhN RMS
PhPh RMS
Unit
Step
Default
PhN DFT
Description
Group selector for connection type
Technical data
Table 143:
Function
Range or value
Accuracy
(1-200)% of VBase
0.5% of Vn at V < Vn
0.5% of V at V > Vn
Absolute hysteresis
(0100)% of VBase
0.5% of Vn at V < Vn
0.5% of V at V > Vn
Inverse time
characteristics for steps 1
and 2, see table 493
(0.00 - 6000.00) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
25 ms typically at 0 to 2 x Vset
25 ms typically at 2 to 0 x Vset
10 ms typically at 0 to 2 x Vset
15 ms typically
259
Technical reference manual
Section 7
Voltage protection
7.3
1MRK505208-UUS D
IEC 61850
identification
IEC 60617
identification
ROV2PTOV
ANSI/IEEE C37.2
device number
59N
3U0
TRV V1 EN
7.3.1
Introduction
Residual voltages may occur in the power system during ground faults.
Two step residual overvoltage protection ROV2PTOV (59N) function calculates the
residual voltage from the three-phase voltage input transformers or measures it from a
single voltage input transformer fed from a broken delta or neutral point voltage
transformer.
ROV2PTOV (59N) has two voltage steps, each with inverse or definite time delay.
Reset delay ensures operation for intermittent ground faults.
7.3.2
Principle of operation
Two step residual overvoltage protection ROV2PTOV (59N) is used to detect high singlephase voltage, such as high residual voltage, also called 3V0. The residual voltage can
be measured directly from a voltage transformer in the neutral of a power transformer
or from a three-phase voltage transformer, where the secondary windings are
connected in an open delta. Another possibility is to measure the three-phase voltages
and internally in the IED calculate the corresponding residual voltage and connect this
calculated residual voltage to ROV2PTOV (59N). ROV2PTOV (59N) has two steps
with separate time delays. If the single-phase (residual) voltage remains above the set
value for a time period corresponding to the chosen time delay, the corresponding
TRIP signal is issued.
The time delay characteristic is individually chosen for the two steps and can be either,
definite time delay or inverse time delay.
The voltage related settings are made in percent of the base voltage, which is set in kV,
phase-phase.
260
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.3.2.1
Measurement principle
The residual voltage is measured continuously, and compared with the set values,
Pickup1 and Pickup2.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
7.3.2.2
Time delay
The time delay for the two steps can be either definite time delay (DT) or inverse time
delay (TOV). For the inverse time delay four different modes are available:
inverse curve A
inverse curve B
inverse curve C
customer programmable inverse curve
TD
V - Vpickup >
Vpickup >
(Equation 56)
ANSIEQUATION2422 V1 EN
where:
Un>
Measured voltage
TD 480
V - Vpickup >
- 0.5
32
Vpickup
>
2.0
- 0.035
(Equation 57)
ANSIEQUATION2423 V1 EN
TD 480
V - Vpickup >
- 0.5
32
Vpickup >
3.0
+ 0.035
ANSIEQUATION2421 V1 EN
(Equation 58)
261
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
t=
TD A
V - Vpickup
-C
B
Vpickup
EQUATION1616 V1 EN
+D
(Equation 59)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval Vpickup up to Vpickup
(1.0 + CrvSatn/100) the used voltage will be: Vpickup (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:
CrvSatn
-C > 0
100
EQUATION1440 V1 EN
(Equation 60)
The details of the different inverse time characteristics are shown in section "Inverse
characteristics".
TRIP signal issuing requires that the residual overvoltage condition continues for at
least the user set time delay. This time delay is set by the parameter t1 and t2 for
definite time mode (DT) and by some special voltage level dependent time curves for
the inverse time mode (TOV).
If the PICKUP condition, with respect to the measured voltage ceases during the delay
time, and is not fulfilled again within a user defined reset time (tReset1 and tReset2 for
the definite time and tIReset1 and tIReset2 for the inverse time) the corresponding
PICKUP output is reset, after that the defined reset time has elapsed.
Here it should be noted that after leaving the hysteresis area, the PICKUP condition
must be fulfilled again and it is not sufficient for the signal to only return back to the
hysteresis area. Also notice that for the overvoltage function TOV reset time is
constant and does not depend on the voltage fluctuations during the drop-off period.
However, there are three ways to reset the timer, either the timer is reset
instantaneously, or the timer value is frozen during the reset time, or the timer value is
linearly decreased during the reset time. See figure 115 and figure 116.
262
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
tIReset1
tIReset1
Voltage
PICKUP
TRIP
PU_Overvolt1
HystAbs1
Measured
Voltage
Time
PICKUP
TRIP
Time
Integrator
Frozen Timer
Linearly
decreased
Time
Instantaneous
ANSI05000019-3-en.vsd
ANSI05000019 V3 EN
Figure 122:
Voltage profile not causing a reset of the PICKUP signal for step 1, and inverse time delay
263
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
tIReset1
Voltage
PICKUP
PICKUP
tIReset1
HystAbs1
TRIP
Pickup1
Measured Voltage
Time
t
PICKUP
TRIP
Time
Integrator
Frozen Timer
Time
Instantaneous
Linearly decreased
ANSI05000020-2-en.vsd
ANSI05000020 V2 EN
Figure 123:
Voltage profile causing a reset of the PICKUP signal for step 1, and inverse time delay
264
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
PU_ST1
tReset1
a
a>b
Vpickup>
t1
t
TRST1
AND
OFF
Delay
ON
Delay
ANSI10000100-2-en.vsd
ANSI10000100 V2 EN
Figure 124:
Pickup1
PICKUP
TRIP
tReset1
t1
ANSI10000037-2-en.vsd
ANSI10000037 V2 EN
Figure 125:
265
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Pickup1
PICKUP
TRIP
tReset1
t1
ANSI10000038-2-en.vsd
ANSI10000038 V2 EN
Figure 126:
7.3.2.3
Blocking
It is possible to block Two step residual overvoltage protection ROV2PTOV (59N)
partially or completely, by binary input signals where:
7.3.2.4
BLOCK:
BLKTR1:
BLK1:
BLKTR2:
BLK2:
Design
The voltage measuring elements continuously measure the residual voltage. Recursive
Fourier filters filter the input voltage signal. The single input voltage is compared to
the set value, and is also used for the inverse time characteristic integration. The design
of Two step residual overvoltage protection (ROV2PTOV, 59N) is schematically
described in figure 127.
266
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
Comparator
VN >
Pickup 1
VN
Phase 1
PICKUP
Time integrator
tIReset1
ResetTypeCrv1
Comparator
VN >
Pickup2
TRIP
TRST1
Pickup
t1
tReset1
&
Trip
Output
Logic
Step 1
PU_ST2
Phase 1
PICKUP
Time integrator
tIReset2
ResetTypeCrv2
PU_ ST1
TRIP
TRST2
Pickup
t2
tReset2
&
Trip
Output
Logic
Step 2
OR
OR
PICKUP
TRIP
ANSI05000748-2-en.vsd
ANSI05000748 V2 EN
Figure 127:
7.3.3
Function block
ROV2PTOV (59N)
V3P*
TRIP
BLOCK
TRST1
BLKTR1
TRST2
BLK1
PICKUP
BLKTR2
PU_ST1
BLK2
PU_ST2
ANSI06000278-2-en.vsd
ANSI06000278 V2 EN
Figure 128:
267
Technical reference manual
Section 7
Voltage protection
7.3.4
1MRK505208-UUS D
Name
Type
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLKTR1
BOOLEAN
BLK1
BOOLEAN
Block of step 1
BLKTR2
BOOLEAN
BLK2
BOOLEAN
Block of step 2
Name
Table 146:
Name
Description
V3P
Table 145:
7.3.5
Default
Type
Description
TRIP
BOOLEAN
Trip
TRST1
BOOLEAN
TRST2
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
Setting parameters
ROV2PTOV (59N) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
OperationStep1
Disabled
Enabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time
Pickup1
1 - 200
%VB
30
t1
0.00 - 6000.00
0.01
5.00
t1Min
0.000 - 60.000
0.001
5.000
Section 7
Voltage protection
1MRK505208-UUS D
Name
Step
Default
TD1
0.05 - 1.10
0.01
0.05
HystAbs1
0.0 - 100.0
%VB
0.1
0.5
OperationStep2
Disabled
Enabled
Enabled
Characterist2
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time
Pickup2
1 - 100
%VB
45
t2
0.000 - 60.000
0.001
5.000
t2Min
0.000 - 60.000
0.001
5.000
TD2
0.05 - 1.10
0.01
0.05
HystAbs2
0.0 - 100.0
%VB
0.1
0.5
Table 147:
Values (Range)
Unit
Description
Name
Values (Range)
Unit
tReset1
0.000 - 60.000
Step
0.001
Default
0.025
Description
Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tIReset1
0.000 - 60.000
0.001
0.025
ACrv1
0.005 - 200.000
0.001
1.000
BCrv1
0.50 - 100.00
0.01
1.00
CCrv1
0.0 - 1.0
0.1
0.0
DCrv1
0.000 - 60.000
0.001
0.000
PCrv1
0.000 - 3.000
0.001
1.000
CrvSat1
0 - 100
tReset2
0.000 - 60.000
0.001
0.025
ResetTypeCrv2
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
269
Technical reference manual
Section 7
Voltage protection
Name
1MRK505208-UUS D
Values (Range)
Unit
tIReset2
0.000 - 60.000
0.001
0.025
ACrv2
0.005 - 200.000
0.001
1.000
BCrv2
0.50 - 100.00
0.01
1.00
CCrv2
0.0 - 1.0
0.1
0.0
DCrv2
0.000 - 60.000
0.001
0.000
PCrv2
0.000 - 3.000
0.001
1.000
CrvSat2
0 - 100
7.3.6
Step
Default
Description
Technical data
Table 148:
Function
Range or value
Accuracy
(1-200)% of VBase
0.5% of Vn at V < Vn
1.0% of V at V > Vn
Absolute hysteresis
(0100)% of VBase
0.5% of Vn at V < Vn
1.0% of V at V > Vn
Inverse time
characteristics for low
and high step, see
table 495
(0.006000.00) s
0.5% 10 ms
(0.00060.000) s
0.5% 10 ms
(0.000-60.000) s
0.5% 10 ms
25 ms typically at 0 to 2 x Vset
25 ms typically at 2 to 0 x Vset
10 ms typically at 0 to 2 x Vset
15 ms typically
270
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.4
7.4.1
IEC 61850
identification
IEC 60617
identification
VDCPTOV
ANSI/IEEE C37.2
device number
60
Introduction
A voltage differential monitoring function is available. It compares the voltages from
two three phase sets of voltage transformers and has one sensitive alarm step and one
trip step.
7.4.2
Principle of operation
The Voltage differential protection function VDCPTOV (60) is based on comparison
of the magnitudes of the two voltages connected in each phase. Possible differences
between the ratios of the two Voltage/Capacitive voltage transformers can be
compensated for with a ratio correction factors RF_X. The voltage difference is
evaluated and if it exceeds the alarm level VDAlarm or trip level VDTrip signals for
alarm (ALARM output) or trip (TRIP output) is given after definite time delay tAlarm
respectively tTrip. The two three phase voltage supplies are also supervised with
undervoltage settings V1Low and V2Low. The outputs for loss of voltage V1LOW resp
V2LOW will be activated. The V1 voltage is supervised for loss of individual phases
whereas the V2 voltage is supervised for loss of all three phases.
Loss of all U1or all U2 voltages will block the differential measurement. This blocking
can be switched off with setting BlkDiffAtULow = No.
VDCPTOV (60) function can be blocked from an external condition with the binary
BLOCK input. It can for example, be activated from Fuse failure supervision function
SDDRFUF.
To allow easy commissioning the measured differential voltage is available as service
value. This allows simple setting of the ratio correction factor to achieve full balance in
normal service.
The principle logic diagram is shown in figure 129.
271
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
VDTrip_A
AND
VDTrip_B
AND
VDTrip_C
O
R
0
0-tReset
0-tTrip
0
AND
AND
AND
VDAlarm_A
TRIP
PICKUP
AND
VDAlarm_B
AND
VDAlarm_C
O
R
0-tAlarm
0
AND
ALARM
AND
V1LOW
AND
V1Low_A
V1Low_B
0-tAlarm
0
AND
V1Low_C
AND
OR
BlkDiffAtULow
V2Low_A
V2Low_B
0-t1
0
AND
AND
V2LOW
V2Low_C
BLOCK
en06000382_2_ansi.vsd
ANSI06000382 V3 EN
Figure 129:
7.4.3
Function block
VDCPTOV (60)
V3P1*
V3P2*
BLOCK
TRIP
PICKUP
ALARM
V1LOW
V2LOW
VDIFF_A
VDIFF_B
VDIFF_C
ANSI06000528-2-en.vsd
ANSI06000528 V2 EN
Figure 130:
272
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.4.4
Name
Type
GROUP
SIGNAL
Bus voltage
V3P2
GROUP
SIGNAL
Capacitor voltage
BLOCK
BOOLEAN
Block of function
Name
Table 151:
Description
V3P1
Table 150:
7.4.5
Default
Type
Description
TRIP
BOOLEAN
PICKUP
BOOLEAN
ALARM
BOOLEAN
V1LOW
BOOLEAN
Loss of V1 voltage
V2LOW
BOOLEAN
Loss of V2 voltage
VDIFF_A
REAL
VDIFF_B
REAL
VDIFF_C
REAL
Setting parameters
VDCPTOV (60) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
VBase
0.50 - 2000.00
kV
0.01
400.00
Base Voltage
BlkDiffAtVLow
No
Yes
Yes
VDTrip
0.0 - 100.0
%VB
0.1
5.0
tTrip
0.000 - 60.000
0.001
1.000
tReset
0.000 - 60.000
0.001
0.000
V1Low
0.0 - 100.0
%VB
0.1
70.0
V2Low
0.0 - 100.0
%VB
0.1
70.0
273
Technical reference manual
Section 7
Voltage protection
Name
1MRK505208-UUS D
Values (Range)
Unit
tBlock
0.000 - 60.000
0.001
0.000
VDAlarm
0.0 - 100.0
%VB
0.1
2.0
tAlarm
0.000 - 60.000
0.001
2.000
Table 152:
Step
Default
Description
Name
Values (Range)
RF_A
0.000 - 3.000
0.001
1.000
RF_B
0.000 - 3.000
0.001
1.000
RF_C
0.000 - 3.000
0.001
1.000
7.4.6
Unit
Step
Function
Range or value
Accuracy
(0.0100.0) % of VBase
0.5 % of Vn
(0.0100.0) % of VBase
0.5% of Vn
Timers
(0.00060.000)s
0.5% 10 ms
7.5.1
Description
Technical data
Table 153:
7.5
Default
IEC 61850
identification
LOVPTUV
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
27
Introduction
Loss of voltage check (LOVPTUV, 27) is suitable for use in networks with an
automatic system restoration function. LOVPTUV (27) issues a three-pole trip
command to the circuit breaker, if all three phase voltages fall below the set value for a
time longer than the set time and the circuit breaker remains closed.
274
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.5.2
Principle of operation
The operation of Loss of voltage check LOVPTUV (27) is based on line voltage
measurement. LOVPTUV (27) is provided with a logic, which automatically
recognizes if the line was restored for at least tRestore before starting the tTrip timer.
All three phases are required to be low before the output TRIP is activated. The
PICKUP output signal indicates pickup.
Additionally, LOVPTUV (27) is automatically blocked if only one or two phase
voltages have been detected low for more than tBlock.
LOVPTUV (27) operates again only if the line has been restored to full voltage for at
least tRestore. Operation of the function is also inhibited by fuse failure and open
circuit breaker information signals, by their connection to dedicated inputs of the
function block.
Due to undervoltage conditions being continuous the trip pulse is limited to a length set
by setting tPulse.
The operation of LOVPTUV (27) is supervised by the fuse-failure function (BLKV
input) and the information about the open position (CBOPEN) of the associated circuit
breaker.
The BLOCK input can be connected to a binary input of the IED in order to receive a
block command from external devices or can be software connected to other internal
functions of the IED itself in order to receive a block command from internal
functions. LOVPTUV (27) is also blocked when the IED is in TEST status and the
function has been blocked from the HMI test menu. (Blocked=Yes).
275
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
TEST
TEST-ACTIVE
AND
Blocked = Yes
PICKUP
BLOCK
OR
Function Enable
tPulse
AND
PU_V_A
PU_V_B
TRIP
0-tTrip
0
AND
only 1 or 2 phases are low for
at least 10 s (not three)
Latched
Enable
PU_V_C
AND
OR
0-tBlock
0
CBOPEN
Reset Enable
OR
AND
VTSU
OR
Set Enable
0-tRestore
OR
ANSI07000089_2_en.vsd
ANSI07000089 V2 EN
Figure 131:
7.5.3
Function block
LOVPTUV (27)
V3P*
BLOCK
CBOPEN
VTSU
TRIP
PICKUP
ANSI07000039-2-en.vsd
ANSI07000039 V2 EN
Figure 132:
276
Technical reference manual
Section 7
Voltage protection
1MRK505208-UUS D
7.5.4
Name
Type
GROUP
SIGNAL
Voltage connection
BLOCK
BOOLEAN
CBOPEN
BOOLEAN
VTSU
BOOLEAN
Name
Table 156:
Description
V3P
Table 155:
7.5.5
Default
Type
Description
TRIP
BOOLEAN
Trip signal
PICKUP
BOOLEAN
Pickup signal
Setting parameters
LOVPTUV (27) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
VBase
0.1 - 9999.9
kV
0.1
400.0
Base voltage
VPG
1 - 100
%VB
70
tTrip
0.000 - 60.000
0.001
7.000
Table 157:
Name
Values (Range)
Unit
tPulse
0.050 - 60.000
Step
0.001
Default
0.150
Description
Duration of TRIP pulse
tBlock
0.000 - 60.000
0.001
5.000
tRestore
0.000 - 60.000
0.001
3.000
277
Technical reference manual
Section 7
Voltage protection
7.5.6
1MRK505208-UUS D
Technical data
Table 158:
Function
Accuracy
Operate voltage
(0100)% of VBase
0.5% of Vn
Pulse timer
(0.05060.000) s
0.5% 10 ms
Timers
(0.00060.000) s
0.5% 10 ms
278
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
Section 8
Frequency protection
8.1
8.1.1
Principle of operation
Underfrequency protection SAPTUF (81) is used to detect low power system
frequency. SAPTUF (81) can either have a definite time delay or a voltage magnitude
dependent time delay. If the voltage magnitude dependent time delay is applied, the
time delay will be longer if the voltage is higher, and the delay will be shorter if the
voltage is lower. If the frequency remains below the set value for a time period
corresponding to the chosen time delay, the corresponding trip signal is issued. To
avoid an unwanted trip due to uncertain frequency measurement at low voltage
magnitude, a voltage controlled blocking of the function is available, that is, if the
voltage is lower than the set blocking voltage IntBlockLevel the function is blocked and
no PICKUP or TRIP signal is issued.
8.1.1.1
Measurement principle
The fundamental frequency of the measured input voltage is measured continuously,
and compared with the set value, PUFrequency. The frequency function is dependent
on the voltage magnitude. If the voltage magnitude decreases the setting IntBlockLevel,
SAPTUF (81) gets blocked, and the output BLKDMAGN is issued. All voltage
settings are made in percent of the setting VBase, which should be set as a phase-phase
voltage in kV.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
279
Technical reference manual
Section 8
Frequency protection
8.1.1.2
1MRK505208-UUS D
Time delay
The time delay for underfrequency protection SAPTUF (81) can be either a settable
definite time delay or a voltage magnitude dependent time delay, where the time delay
depends on the voltage level; a high voltage level gives a longer time delay and a low
voltage level causes a short time delay. For the definite time delay, the setting
TimeDlyOperate sets the time delay.
For the voltage dependent time delay the measured voltage level and the settings VNom,
VMin, Exponent, t_MaxTripDelay and t_MinTripDelay set the time delay according to
figure 133 and equation 61. The setting TimerOperation is used to decide what type of
time delay to apply.
Trip signal issuing requires that the underfrequency condition continues for at least the
user set time delay TimeDlyOperate. If the PICKUP condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
within a user defined reset time, TimeDlyReset, the PICKUP output is reset, after that
the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the PICKUP condition must be fulfilled again and it is not sufficient
for the signal to only return back to the hysteresis area.
On the output of SAPTUF (81) a 100ms pulse is issued, after a time delay
corresponding to the setting of TimeDlyRestore, when the measured frequency returns
to the level corresponding to the setting RestoreFreq.
8.1.1.3
280
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
V - VMin
t=
VNom - VMin
Exponent
(Equation 61)
EQUATION1559 V1 EN
where:
t
Exponent
is a setting,
VMin, VNom
= 90%
= 100%
t_MaxTrip
Delay
= 1.0 s
t_MinTripD
elay
= 0.0 s
Exponent
= 0, 1, 2, 3 and 4
TimeDlyOperate [s]
0
Exponenent
1
2
3
0.5
90
95
100
V [% of VBase]
en05000075_ansi.vsd
ANSI05000075 V1 EN
Figure 133:
281
Technical reference manual
Section 8
Frequency protection
8.1.1.4
1MRK505208-UUS D
Blocking
It is possible to block underfrequency protection SAPTUF (81) partially or completely,
by binary input signals or by parameter settings, where:
BLOCK:
BLKTRIP:
BLKREST:
If the measured voltage level decreases below the setting of IntBlockLevel, both the
PICKUP and the TRIP outputs, are blocked.
8.1.1.5
Design
The frequency measuring element continuously measures the frequency of the positive
sequence voltage and compares it to the setting PUFrequency. The frequency signal is
filtered to avoid transients due to switchings and faults. The time integrator can operate
either due to a definite delay time or to the special voltage dependent delay time. When
the frequency has returned back to the setting of RestoreFreq, the RESTORE output is
issued after the time delay TimeDlyRestore. The design of underfrequency protection
SAPTUF (81) is schematically described in figure 134.
Block
OR
BLKDMAGN
BLOCK
Comparator
V < IntBlockLevel
Voltage
Frequency
Time integrator
Comparator
f < PuFrequency
TimerOperation Mode
Selector
PICKUP
TimeDlyOperate
TRIP
Pickup
&
Trip
Output
Logic
PICKUP
TimeDlyReset
TRIP
100 ms
Comparator
f > RestoreFreq
TimeDlyRestore
RESTORE
en05000726_ansi.vsd
ANSI05000726 V1 EN
Figure 134:
282
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
8.1.2
Function block
SAPTUF (81)
V3P*
BLOCK
BLKTRIP
BLKREST
TRIP
PICKUP
RESTORE
BLKDMAGN
FREQ
ANSI06000279-2-en.vsd
ANSI06000279 V2 EN
Figure 135:
8.1.3
Name
Type
GROUP
SIGNAL
Voltage connection
BLOCK
BOOLEAN
Block of function
BLKTRIP
BOOLEAN
BLKREST
BOOLEAN
Name
Table 161:
Description
V3P
Table 160:
8.1.4
Default
Type
Description
TRIP
BOOLEAN
PICKUP
BOOLEAN
RESTORE
BOOLEAN
BLKDMAGN
BOOLEAN
FREQ
REAL
Measured frequency
Setting parameters
SAPTUF (81) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
Vbase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
PUFrequency
35.00 - 75.00
Hz
0.01
48.80
IntBlockLevel
0 - 100
%VB
50
283
Technical reference manual
Section 8
Frequency protection
Name
1MRK505208-UUS D
Values (Range)
Unit
TimeDlyOperate
0.000 - 60.000
0.001
0.200
TimeDlyReset
0.000 - 60.000
0.001
0.000
TimeDlyRestore
0.000 - 60.000
0.001
0.000
RestoreFreq
45.00 - 65.00
Hz
0.01
50.10
TimerOperation
Definite timer
Volt based timer
Definite timer
VNom
50 - 150
%VB
100
VMin
50 - 150
%VB
90
Exponent
0.0 - 5.0
0.1
1.0
t_MaxTripDelay
0.010 - 60.000
0.001
1.000
t_MinTripDelay
0.010 - 60.000
0.001
1.000
8.1.5
Step
Default
Description
Technical data
Table 162:
Function
Range or value
Accuracy
(35.00-75.00) Hz
2.0 mHz
100 ms typically
100 ms typically
284
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
Function
Range or value
Accuracy
(0.000-60.000)s
0.5% 10 ms
(0.000-60.000)s
0.5% 10 ms
Settings:
VNom=(50-150)% of Vbase
VMin=(50-150)% of Vbase
Exponent=0.0-5.0
t_MaxTripDelay=(0.000-60.000
)s
t_MinTripDelay=(0.000-60.000)
s
5% + 200 ms
V - VMin
t=
VNom - VMin
Exponent
EQUATION1559 V1 EN
(Equation 62)
V=Vmeasured
8.2
8.2.1
Introduction
Overfrequency protection function SAPTOF (81) is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs because of sudden load drops or shunt faults in the power
network. Close to the generating plant, generator governor problems can also cause
over frequency.
SAPTOF (81) is used mainly for generation shedding and remedial action schemes. It
is also used as a frequency stage initiating load restoring.
SAPTOF (81) is provided with an undervoltage blocking.
285
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
The operation is based on positive sequence voltage measurement and requires two phasephase or three phase-neutral voltages to be connected. For information about how to
connect analog inputs, refer to Application manual/IED application/Analog inputs/
Setting guidelines
8.2.2
Principle of operation
Overfrequency protection SAPTOF (81) is used to detect high power system
frequency. SAPTOF (81) has a settable definite time delay. If the frequency remains
above the set value for a time period corresponding to the chosen time delay, the
corresponding TRIP signal is issued. To avoid an unwanted TRIP due to uncertain
frequency measurement at low voltage magnitude, a voltage controlled blocking of the
function is available from the preprocessing function, that is, if the voltage is lower
than the set blocking voltage in the preprocessing function, the function is blocked and
no PICKUP or TRIP signal is issued.
8.2.2.1
Measurement principle
The fundamental frequency of the positive sequence voltage is measured continuously,
and compared with the set value, PUFrequency. Overfrequency protection SAPTOF
(81) is dependent on the voltage magnitude. If the voltage magnitude decreases below
the setting IntBlockLevel, SAPTOF (81) is blocked, and the output BLKDMAGN is
issued. All voltage settings are made in percent of the VBase, which should be set as a
phase-phase voltage in kV. To avoid oscillations of the output PICKUP signal, a
hysteresis has been included.
8.2.2.2
Time delay
The time delay for Overfrequency protection SAPTOF (81) is a settable definite time
delay, specified by the setting TimeDlyOperate.
TRIP signal issuing requires that the overfrequency condition continues for at least the
user set time delay, TimeDlyReset. If the PICKUP condition, with respect to the
measured frequency ceases during this user set delay time, and is not fulfilled again
within a user defined reset time, TimeDlyReset, the PICKUP output is reset, after that
the defined reset time has elapsed. It is to be noted that after leaving the hysteresis area,
the PICKUP condition must be fulfilled again and it is not sufficient for the signal to
only return back to the hysteresis area.
8.2.2.3
Blocking
It is possible to block overfrequency protection SAPTOF (81) partially or completely,
by binary input signals or by parameter settings, where:
286
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
BLOCK:
BLKTRIP:
If the measured voltage level decreases below the setting of IntBlockLevel, both the
PICKUP and the TRIP outputs, are blocked.
8.2.2.4
Design
The frequency measuring element continuously measures the frequency of the positive
sequence voltage and compares it to the setting PUFrequency. The frequency signal is
filtered to avoid transients due to switchings and faults in the power system. The time
integrator operates due to a definite delay time. The design of overfrequency protection
SAPTOF (81) is schematically described in figure 136.
BLOCK
BLKTRIP
BLOCK
Comparator
V < IntBlockLevel
Voltage
Time integrator
Definite Time Delay
Frequency
Comparator
f > PuFrequency
BLKDMAGN
OR
PICKUP
Pickup
&
Trip
Output
Logic
PICKUP
TimeDlyOperate
TRIP
TimeDlyReset
TRIP
en05000735_ansi.vsd
ANSI05000735 V1 EN
Figure 136:
287
Technical reference manual
Section 8
Frequency protection
8.2.3
1MRK505208-UUS D
Technical data
Table 163:
Function
8.3
Range or value
Accuracy
(35.00-75.00) Hz
2.0 mHz at
symmetrical threephase voltage
100 ms typically
(0.000-60.000)s
0.5% 10 ms
(0.000-60.000)s
0.5% 10 ms
IEC 61850
identification
IEC 60617
identification
SAPFRC
ANSI/IEEE C37.2
device number
81
df/dt >
<
SYMBOL-N V1 EN
8.3.1
Introduction
Rate-of-change frequency protection function (SAPFRC,81) gives an early indication
of a main disturbance in the system. SAPFRC (81) can be used for generation
shedding, load shedding and remedial action schemes. SAPFRC (81) can discriminate
between positive or negative change of frequency.
SAPFRC (81) is provided with an undervoltage blocking. The operation is based on
positive sequence voltage measurement and requires two phase-phase or three phaseneutral voltages to be connected. For information about how to connect analog inputs,
refer to Application manual/IED application/Analog inputs/Setting guidelines.
8.3.2
Principle of operation
Rate-of-change frequency protection SAPFRC (81) is used to detect fast power system
frequency changes, increase as well as, decrease at an early stage. SAPFRC (81) has a
settable definite time delay. If the rate-of-change of frequency remains below the set
value, for negative rate-of-change, for a time period equal to the chosen time delay, the
288
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
TRIP signal is issued. If the rate-of-change of frequency remains above the set value,
for positive rate-of-change, for a time period equal to the chosen time delay, the TRIP
signal is issued. To avoid an unwanted TRIP due to uncertain frequency measurement
at low voltage magnitude, a voltage controlled blocking of the function is available,
that is if the voltage is lower than the set blocking voltage IntBlockLevel, the function
is blocked and no PICKUP or TRIP signal is issued. If the frequency recovers, after a
frequency decrease, a restore signal is issued.
8.3.2.1
Measurement principle
The rate-of-change of the fundamental frequency of the selected voltage is measured
continuously, and compared with the set value, PUFreqGrad. Rate-of-change
frequency protection SAPFRC (81) is also dependent on the voltage magnitude. If the
voltage magnitude decreases below the setting IntBlockLevel, SAPFRC (81) is
blocked, and the output BLKDMAGN is issued. The sign of the setting PUFreqGrad,
controls if SAPFRC (81) reacts on a positive or on a negative change in frequency. If
SAPFRC (81) is used for decreasing frequency that is, the setting PUFreqGrad has
been given a negative value, and a trip signal has been issued, then a 100 ms pulse is
issued on the RESTORE output, when the frequency recovers to a value higher than
the setting RestoreFreq. A positive setting of PUFreqGrad, sets SAPFRC (81) to
PICKUP and TRIP for frequency increases.
To avoid oscillations of the output PICKUP signal, a hysteresis has been included.
8.3.2.2
Time delay
Rate-of-change frequency protection SAPFRC (81) has a settable definite time delay,
tTrip. .
Trip signal issuing requires that the rate-of-change of frequency condition continues
for at least the user set time delay, tTrip. If the PICKUP condition, with respect to the
measured frequency ceases during the delay time, and is not fulfilled again within a
user defined reset time, tReset, the PICKUP output is reset, after that the defined reset
time has elapsed. Here it should be noted that after leaving the hysteresis area, the
PICKUP condition must be fulfilled again and it is not sufficient for the signal to only
return back into the hysteresis area.
The RESTORE output of SAPFRC (81) is set, after a time delay equal to the setting of
tRestore, when the measured frequency has returned to the level corresponding to
RestoreFreq, after an issue of the TRIP output signal. If tRestore is set to 0.000 s the
restore functionality is disabled, and no output will be given. The restore functionality
is only active for lowering frequency conditions and the restore sequence is disabled if
a new negative frequency gradient is detected during the restore period, defined by the
settings RestoreFreq and tRestore.
289
Technical reference manual
Section 8
Frequency protection
8.3.2.3
1MRK505208-UUS D
Blocking
Rate-of-change frequency protection (SAPFRC, 81) can be partially or totally blocked,
by binary input signals or by parameter settings, where:
BLOCK:
BLKTRIP:
BLKREST:
If the measured voltage level decreases below the setting of IntBlockLevel, both the
PICKUP and the TRIP outputs, are blocked.
8.3.2.4
Design
Rate-of-change frequency protection (SAPFRC, 81) measuring element continuously
measures the frequency of the selected voltage and compares it to the setting
PUFreqGrad. The frequency signal is filtered to avoid transients due to power system
switchings and faults. The time integrator operates with a definite delay time. When
the frequency has returned back to the setting of RestoreFreq, the RESTORE output is
issued after the time delay tRestore, if the TRIP signal has earlier been issued. The sign
of the setting PUFreqGrad is essential, and controls if the function is used for raising
or lowering frequency conditions. The design of SAPFRC (81) is schematically
described in figure 137.
290
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
BLOCK
BLKTRIP
BLKRESET
Voltage
Rate-of-Change
of Frequency
OR
BLOCK
BLKDMAGN
Comparator
V < IntBlockLevel
Comparator
If
[PickupFreqGrad<0
PICKUP
AND
df/dt < PickupFreqGrad]
OR
[PickupFreqGrad>0
AND
df/dt > PickupFreqGrad]
Then
PICKUP
Time integrator
Definite Time Delay
TimeDlyOperate
Pickup
&
Trip
Output
Logic
PICKUP
TimeDlyReset
TRIP
100 ms
Frequency
Comparator
f > RestoreFreq
TimeDlyRestore
RESTORE
en05000835_ansi.vsd
ANSI05000835 V1 EN
Figure 137:
8.3.3
Function block
SAPFRC (81)
V3P*
TRIP
BLOCK
PICKUP
BLKTRIP
RESTORE
BLKREST
BLKDMAGN
ANSI06000281-2-en.vsd
ANSI06000281 V2 EN
Figure 138:
291
Technical reference manual
Section 8
Frequency protection
8.3.4
1MRK505208-UUS D
Name
Type
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLKTRIP
BOOLEAN
BLKREST
BOOLEAN
Name
Table 166:
Name
Description
V3P
Table 165:
8.3.5
Default
Type
Description
TRIP
BOOLEAN
PICKUP
BOOLEAN
RESTORE
BOOLEAN
BLKDMAGN
BOOLEAN
Setting parameters
SAPFRC (81) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
VBase
0.05 - 2000.00
kV
0.05
400.00
PUFreqGrad
-10.00 - 10.00
Hz/s
0.01
0.50
IntBlockLevel
0 - 100
%VB
50
tTrip
0.000 - 60.000
0.001
0.200
RestoreFreq
45.00 - 65.00
Hz
0.01
49.90
tRestore
0.000 - 60.000
0.001
0.000
tReset
0.000 - 60.000
0.001
0.000
292
Technical reference manual
Section 8
Frequency protection
1MRK505208-UUS D
8.3.6
Technical data
Table 167:
Function
Range or value
Accuracy
(-10.00-10.00) Hz/s
10.0 mHz/s
(0-100)% of VBase
0.5% of Vn
100 ms typically
293
Technical reference manual
294
Section 9
Multipurpose protection
1MRK505208-UUS D
Section 9
Multipurpose protection
9.1
IEC 61850
identification
CVGAPC
9.1.1
Introduction
9.1.2
Principle of operation
9.1.2.1
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
General current and voltage protection (CVGAPC) function is always connected to threephase current and three-phase voltage input in the configuration tool, but it will always
measure only one current and one voltage quantity selected by the end user in the
setting tool.
The user can select to measure one of the current quantities shown in table 168.
Table 168:
CurrentInput
Comment
PhaseA
PhaseB
PhaseC
PosSeq
295
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
CurrentInput
Comment
NegSeq
3ZeroSeq
MaxPh
CVGAPC function will measure current phasor of the phase with maximum
magnitude
MinPh
CVGAPC function will measure current phasor of the phase with minimum
magnitude
UnbalancePh
10
PhaseA-PhaseB
11
PhaseB-PhaseC
12
PhaseC-PhaseA
13
MaxPh-Ph
CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
15
UnbalancePh-Ph
The user can select to measure one of the voltage quantities shown in table 169:
Table 169:
VoltageInput
Comment
PhaseA
PhaseB
PhaseC
PosSeq
296
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
VoltageInput
Comment
-NegSeq
-3ZeroSeq
MaxPh
CVGAPC function will measure voltage phasor of the phase with maximum
magnitude
MinPh
CVGAPC function will measure voltage phasor of the phase with minimum
magnitude
UnbalancePh
10
PhaseA-PhaseB
11
PhaseB-PhaseC
12
PhaseC-PhaseA
13
MaxPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the minimum
magnitude
15
UnbalancePh-Ph
It is important to notice that the voltage selection from table 169 is always applicable
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-ground voltages VA, VB & VC or three phaseto-phase voltages VAB, VBC & VCA). This information about actual VT connection is
entered as a setting parameter for the pre-processing block, which will then take
automatic care about it.
The user can select one of the current quantities shown in table 170 for built-in current
restraint feature:
297
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Table 170:
9.1.2.2
Comment
PosSeq
NegSeq
3ZeroSeq
MaxPh
CVGAPC function will measure current phasor of the phase with maximum
magnitude
rated phase current of the protected object in primary amperes, when the measured
Current Quantity is selected from 1 to 9, as shown in table 168.
rated phase current of the protected object in primary amperes multiplied by 3
(1.732 Iphase), when the measured Current Quantity is selected from 10 to 15, as
shown in table 168.
9.1.2.3
rated phase-to-ground voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table 169.
rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table 169.
298
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Pickup signal will only come if all of the enabled built-in features in the overcurrent
step are fulfilled at the same time.
This feature will simple prevent overcurrent step pickup if the second-to-first harmonic
ratio in the measured current exceeds the set level.
Directional feature
The overcurrent protection step operation can be can be made dependent on the
relevant phase angle between measured current phasor (see table 168) and measured
voltage phasor (see table 169). In protection terminology it means that the General
currrent and voltage protection (CVGAPC) function can be made directional by
enabling this built-in feature. In that case overcurrent protection step will only operate
if the current flow is in accordance with the set direction (Forward, which means
towards the protected object, or Reverse, which means from the protected object). For
this feature it is of the outmost importance to understand that the measured voltage
phasor (see table 169) and measured current phasor (see table 168) will be used for
directional decision. Therefore it is the sole responsibility of the end user to select the
appropriate current and voltage signals in order to get a proper directional decision.
CVGAPC function will NOT do this automatically. It will just simply use the current
and voltage phasors selected by the end user to check for the directional criteria.
Table 171 gives an overview of the typical choices (but not the only possible ones) for
these two quantities for traditional directional relays.
299
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Table 171:
Set value for the
parameter
CurrentInput
VoltageInput
Comment
PosSeq
PosSeq
NegSeq
-NegSeq
3ZeroSeq
-3ZeroSeq
Phase1
Phase2-Phase3
Phase2
Phase3-Phase1
Phase3
Phase1-Phase2
Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.
Two types of directional measurement principles are available, I & V and IcosPhi&V.
The first principle, referred to as "I & V" in the parameter setting tool, checks that:
the magnitude of the measured current is bigger than the set pick-up level
the phasor of the measured current is within the operating region (defined by the
relay operate angle, ROADir parameter setting; see figure 139).
300
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
V=-3V0
RCADir
Ipickup
ROADir
I=3Io
Operate region
mta line
en05000252_anis.vsd
IEC05000252-ANIS V1 EN
Figure 139:
where:
RCADir is -75
ROADir is 50
The second principle, referred to as "IcosPhi&V" in the parameter setting tool, checks
that:
that the product Icos() is bigger than the set pick-up level, where is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined by
the Icos() straight line and the relay operate angle, ROADir parameter setting;
see figure 139).
301
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
V=-3V0
RCADir
Ipickup
ROADir
I=3Io
Operate region
mta line
en05000253_ansi.vsd
ANSI05000253 V1 EN
Figure 140:
where:
RCADir is -75
ROADir is 50
Note that it is possible to decide by a parameter setting how the directional feature
shall behave when the magnitude of the measured voltage phasor falls below the preset value. User can select one of the following three options:
It shall also be noted that the memory duration is limited in the algorithm to 100 ms.
After that time the current direction will be locked to the one determined during
memory time and it will re-set only if the current fails below set pickup level or voltage
goes above set voltage memory limit.
The overcurrent protection step operation can be can be made dependent of a measured
voltage quantity (see table 169). Practically then the pickup level of the overcurrent
step is not constant but instead decreases with the decrease in the magnitude of the
measured voltage quantity. Two different types of dependencies are available:
302
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
PickupCurr_OC1
VDepFact_OC1 * PickupCurr_OC1
VLowLimit_OC1
VHighLimit_OC1
Selected Voltage
Magnitude
en05000324_ansi.vsd
ANSI05000324 V1 EN
Figure 141:
PickupCurr_OC1
VDepFact_OC1 *
PickupCurr_OC1
VHighLimit_OC1
ANSI05000323 V1 EN
Figure 142:
This feature will simply change the set overcurrent pickup level in accordance with
magnitude variations of the measured voltage. It shall be noted that this feature will as
well affect the pickup current value for calculation of operate times for IDMT curves
(overcurrent with IDMT curve will operate faster during low voltage conditions).
303
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
IMeasured
pe
O
te
ra
ea
ar
IsetHigh
ff
oe
trC
s
e
I>R
tr
es
*I r
ain
IsetLow
atan(RestrCoeff)
Restraint
en05000255.vsd
IEC05000255 V1 EN
Figure 143:
This feature will simply prevent overcurrent step to pickup if the magnitude of the
measured current quantity is smaller than the set percentage of the restrain current
magnitude. However this feature will not affect the pickup current value for calculation
of operate times for IDMT curves. This means that the IDMT curve operate time will
not be influenced by the restrain current magnitude.
When set, the pickup signal will start definite time delay or inverse (IDMT) time delay
in accordance with the end user setting. If the pickup signal has value one for longer
time than the set time delay, the overcurrent step will set its trip signal to one. Reset of
the pickup and trip signal can be instantaneous or time delay in accordance with the
end user setting.
9.1.2.4
304
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
time than the set time delay the undercurrent step will set its trip signal to one. Reset of
the pickup and trip signal can be instantaneous or time delay in accordance with the
setting.
9.1.2.5
9.1.2.6
9.1.2.7
Logic diagram
The simplified internal logics, for CVGAPC function are shown in the following figures.
305
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
IED
Phasors &
samples
Phasor calculation of
individual currents
Selected current
Selected voltage
Phasors &
samples
52
CVGAPC function
Phasor calculation of
individual voltages
A/D conversion
scaling with CT ratio
ADM
ANSI05000169_2_en.vsd
ANSI05000169 V2 EN
Figure 144:
Figure 144 shows how internal treatment of measured currents is done for
multipurpose protection function
The following currents and voltages are inputs to the multipurpose protection function.
They must all be expressed in true power system (primary) Amperes and kilovolts.
1.
2.
3.
306
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
1.
2.
3.
Selects one current from the three-phase input system (see table 168) for internally
measured current.
Selects one voltage from the three-phase input system (see table 169) for internally
measured voltage.
Selects one current from the three-phase input system (see table 170) for internally
measured restraint current.
307
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
CURRENT
UC1
2
Selected current
TRUC1
nd
Harmonic
restraint
PU_UC2
UC2
nd
2 Harmonic
restraint
TRUC2
PU_OC1
OC1
2nd Harmonic
restraint
TROC1
OR
Current restraint
BLK2ND
DIROC1
Directionality
Voltage control /
restraint
PU_OC2
TROC2
OC2
2nd Harmonic
restraint
Current restraint
Directionality
OR
VDIRLOW
DIROC2
Voltage control /
restraint
PU_OV1
OV1
TROV1
PU_OV2
OV2
Selected voltage
TROV2
PU_UV1
UV1
TRUV1
PU_UV2
UV2
TRUV2
VOLTAGE
308
en05000170_ansi.vsd
Section 9
Multipurpose protection
1MRK505208-UUS D
ANSI05000170 V1 EN
Figure 145:
The selected currents and voltage are given to built-in protection elements. Each
protection element and step makes independent decision about status of its
PICKUP and TRIP output signals.
More detailed internal logic for every protection element is given in the following
four figures
Common PICKUP and TRIP signals from all built-in protection elements & steps
(internal OR logic) are available from multipurpose function as well.
2.
3.
Enable
second
harmonic
Second
harmonic check
DEF time
selected
a
b
AND
TROC1
OR
a>b
OC1=On
BLKOC1
BLKTROC1
0-DEF
0
Selected current
PickupCurr_OC1
NOT
PU_OC1
AND
Inverse
Voltage
control or
restraint
feature
Selected voltage
Directionality
check
DIR_OK
Inverse
time
selected
Current
Restraint
Feature
Imeasured > k Irestraint
en05000831_ansi.vsd
ANSI05000831 V1 EN
Figure 146:
Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)
309
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Selected current
b>a
AND
PickupCurr_UC1
TRUC1
AND
0-DEF
0
Operation_UC1=On
PU_UC1
en05000750_ansi.vsd
ANSI05000750 V1 EN
Figure 147:
Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has the
same internal logic)
DEF time
selected
0
Selected voltage
a
b
PickupVolt_OV1
BLKTROV1
0-DEF
AND
TROV1
OR
a>b
PU_OV1
AND
Inverse
Operation_OV1=On
BLKOV1
Inverse time
selected
en05000751_ansi.vsd
ANSI05000751 V1 EN
Figure 148:
Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)
310
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
DEF time
selected
0
Selected voltage
BLKTRUV1
0-DEF
AND
TRUV1
OR
b>a
PU_UV1
AND
PickupVolt_UV1
Inverse
Operation_UV1=On
Inverse time
selected
BLKUV1
en05000752_ansi.vsd
ANSI05000752 V1 EN
Figure 149:
Simplified internal logic diagram for built-in first undervoltage step UV1 (step UV2 has the same
internal logic)
9.1.3
Function block
CVGAPC
I3P*
V3P*
BLOCK
BLKOC1
BLKOC1TR
ENMLTOC1
BLKOC2
BLKOC2TR
ENMLTOC2
BLKUC1
BLKUC1TR
BLKUC2
BLKUC2TR
BLKOV1
BLKOV1TR
BLKOV2
BLKOV2TR
BLKUV1
BLKUV1TR
BLKUV2
BLKUV2TR
TRIP
TROC1
TROC2
TRUC1
TRUC2
TROV1
TROV2
TRUV1
TRUV2
PICKUP
PU_OC1
PU_OC2
PU_UC1
PU_UC2
PU_OV1
PU_OV2
PU_UV1
PU_UV2
BLK2ND
DIROC1
DIROC2
VDIRLOW
CURRENT
ICOSFI
VOLTAGE
VIANGLE
ANSI05000372-2-en.vsd
ANSI05000372 V2 EN
Figure 150:
311
Technical reference manual
Section 9
Multipurpose protection
9.1.4
1MRK505208-UUS D
Default
Description
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Block of function
BLKOC1
BOOLEAN
BLKOC1TR
BOOLEAN
ENMLTOC1
BOOLEAN
BLKOC2
BOOLEAN
BLKOC2TR
BOOLEAN
ENMLTOC2
BOOLEAN
BLKUC1
BOOLEAN
BLKUC1TR
BOOLEAN
BLKUC2
BOOLEAN
BLKUC2TR
BOOLEAN
BLKOV1
BOOLEAN
BLKOV1TR
BOOLEAN
BLKOV2
BOOLEAN
BLKOV2TR
BOOLEAN
BLKUV1
BOOLEAN
BLKUV1TR
BOOLEAN
BLKUV2
BOOLEAN
BLKUV2TR
BOOLEAN
Table 173:
Name
Description
TRIP
BOOLEAN
TROC1
BOOLEAN
TROC2
BOOLEAN
TRUC1
BOOLEAN
TRUC2
BOOLEAN
TROV1
BOOLEAN
TROV2
BOOLEAN
312
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Name
9.1.5
Table 174:
Type
Description
TRUV1
BOOLEAN
TRUV2
BOOLEAN
PICKUP
BOOLEAN
PU_OC1
BOOLEAN
PU_OC2
BOOLEAN
PU_UC1
BOOLEAN
PU_UC2
BOOLEAN
PU_OV1
BOOLEAN
PU_OV2
BOOLEAN
PU_UV1
BOOLEAN
PU_UV2
BOOLEAN
BLK2ND
BOOLEAN
DIROC1
INTEGER
DIROC2
INTEGER
VDIRLOW
BOOLEAN
CURRENT
REAL
ICOSFI
REAL
VOLTAGE
REAL
VIANGLE
REAL
Setting parameters
CVGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
CurrentInput
Phase A
Phase B
Phase C
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
MaxPh
IBase
1 - 99999
3000
Base Current
Section 9
Multipurpose protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
VoltageInput
Phase A
Phase B
Phase C
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
MaxPh
VBase
0.05 - 2000.00
kV
0.05
400.00
Base Voltage
OperHarmRestr
Disabled
Enabled
Disabled
l_2nd/l_fund
10.0 - 50.0
1.0
20.0
EnRestrainCurr
Disabled
Enabled
Disabled
RestrCurrInput
PosSeq
NegSeq
3*ZeroSeq
Max
PosSeq
RestrCurrCoeff
0.00 - 5.00
0.01
0.00
RCADir
-180 - 180
Deg
-75
ROADir
1 - 90
Deg
75
LowVolt_VM
0.0 - 5.0
%VB
0.1
0.5
Operation_OC1
Disabled
Enabled
Disabled
PickupCurr_OC1
2.0 - 5000.0
%IB
1.0
120.0
314
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
CurveType_OC1
tDef_OC1
0.00 - 6000.00
0.01
0.50
TD_OC1
0.05 - 999.00
0.01
0.30
IMin1
1 - 10000
%IB
100
tMin_OC1
0.00 - 6000.00
0.01
0.05
VCntrlMode_OC1
Voltage control
Input control
Volt/Input control
Disabled
Disabled
VDepMode_OC1
Step
Slope
Step
VDepFact_OC1
0.02 - 5.00
0.01
1.00
VLowLimit_OC1
1.0 - 200.0
%VB
0.1
50.0
VHighLimit_OC1
1.0 - 200.0
%VB
0.1
100.0
HarmRestr_OC1
Disabled
Enabled
Disabled
DirMode_OC1
Non-directional
Forward
Reverse
Non-directional
DirPrinc_OC1
I&V
IcosPhi&U
I&V
ActLowVolt1_VM
Non-directional
Block
Memory
Non-directional
Operation_OC2
Disabled
Enabled
Disabled
PickupCurr_OC2
2.0 - 5000.0
%IB
1.0
120.0
315
Technical reference manual
Section 9
Multipurpose protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
CurveType_OC2
tDef_OC2
0.00 - 6000.00
0.01
0.50
TD_OC2
0.05 - 999.00
0.01
0.30
IMin2
1 - 10000
%IB
50
tMin_OC2
0.00 - 6000.00
0.01
0.05
VCntrlMode_OC2
Voltage control
Input control
Volt/Input control
Disabled
Disabled
VDepMode_OC2
Step
Slope
Step
VDepFact_OC2
0.02 - 5.00
0.01
1.00
VLowLimit_OC2
1.0 - 200.0
%VB
0.1
50.0
VHighLimit_OC2
1.0 - 200.0
%VB
0.1
100.0
HarmRestr_OC2
Disabled
Enabled
Disabled
DirMode_OC2
Non-directional
Forward
Reverse
Non-directional
DirPrinc_OC2
I&V
IcosPhi&U
I&V
ActLowVolt2_VM
Non-directional
Block
Memory
Non-directional
Operation_UC1
Disabled
Enabled
Disabled
EnBlkLowI_UC1
Disabled
Enabled
Disabled
Section 9
Multipurpose protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
BlkLowCurr_UC1
0 - 150
%IB
20
PickupCurr_UC1
2.0 - 150.0
%IB
1.0
70.0
tDef_UC1
0.00 - 6000.00
0.01
0.50
tResetDef_UC1
0.00 - 6000.00
0.01
0.00
HarmRestr_UC1
Disabled
Enabled
Disabled
Operation_UC2
Disabled
Enabled
Disabled
EnBlkLowI_UC2
Disabled
Enabled
Disabled
BlkLowCurr_UC2
0 - 150
%IB
20
PickupCurr_UC2
2.0 - 150.0
%IB
1.0
70.0
tDef_UC2
0.00 - 6000.00
0.01
0.50
HarmRestr_UC2
Disabled
Enabled
Disabled
Operation_OV1
Disabled
Enabled
Disabled
PickupVolt_OV1
2.0 - 200.0
%VB
0.1
150.0
CurveType_OV1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time
tDef_OV1
0.00 - 6000.00
0.01
1.00
tMin_OV1
0.00 - 6000.00
0.01
0.05
TD_OV1
0.05 - 999.00
0.01
0.30
Operation_OV2
Disabled
Enabled
Disabled
PickupVolt_OV2
2.0 - 200.0
%VB
0.1
150.0
CurveType_OV2
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
Definite time
tDef_OV2
0.00 - 6000.00
0.01
1.00
tMin_OV2
0.00 - 6000.00
0.01
0.05
Section 9
Multipurpose protection
Name
Values (Range)
1MRK505208-UUS D
Step
Default
TD_OV2
0.05 - 999.00
Unit
-
0.01
0.30
Description
Time multiplier for the dependent time delay
for OV2
Operation_UV1
Disabled
Enabled
Disabled
PickupVolt_UV1
2.0 - 150.0
%VB
0.1
50.0
CurveType_UV1
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
Definite time
tDef_UV1
0.00 - 6000.00
0.01
1.00
tMin_UV1
0.00 - 6000.00
0.01
0.05
TD_UV1
0.05 - 999.00
0.01
0.30
EnBlkLowV_UV1
Disabled
Enabled
Enabled
BlkLowVolt_UV1
0.0 - 5.0
%VB
0.1
0.5
Operation_UV2
Disabled
Enabled
Disabled
PickupVolt_UV2
2.0 - 150.0
%VB
0.1
50.0
CurveType_UV2
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
Definite time
tDef_UV2
0.00 - 6000.00
0.01
1.00
tMin_UV2
0.00 - 6000.00
0.01
0.05
TD_UV2
0.05 - 999.00
0.01
0.30
EnBlkLowV_UV2
Disabled
Enabled
Enabled
BlkLowVolt_UV2
0.0 - 5.0
%VB
0.1
0.5
318
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Table 175:
Name
Values (Range)
Unit
Step
Default
Description
MultPU_OC1
1.0 - 10.0
0.1
2.0
ResCrvType_OC1
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tResetDef_OC1
0.00 - 6000.00
0.01
0.00
P_OC1
0.001 - 10.000
0.001
0.020
A_OC1
0.000 - 999.000
0.001
0.140
B_OC1
0.000 - 99.000
0.001
0.000
C_OC1
0.000 - 1.000
0.001
1.000
PR_OC1
0.005 - 3.000
0.001
0.500
TR_OC1
0.005 - 600.000
0.001
13.500
CR_OC1
0.1 - 10.0
0.1
1.0
MultPU_OC2
1.0 - 10.0
0.1
2.0
ResCrvType_OC2
Instantaneous
IEC Reset
ANSI reset
Instantaneous
tResetDef_OC2
0.00 - 6000.00
0.01
0.00
P_OC2
0.001 - 10.000
0.001
0.020
A_OC2
0.000 - 999.000
0.001
0.140
B_OC2
0.000 - 99.000
0.001
0.000
C_OC2
0.000 - 1.000
0.001
1.000
PR_OC2
0.005 - 3.000
0.001
0.500
TR_OC2
0.005 - 600.000
0.001
13.500
CR_OC2
0.1 - 10.0
0.1
1.0
tResetDef_UC2
0.00 - 6000.00
0.01
0.00
Section 9
Multipurpose protection
Name
Values (Range)
1MRK505208-UUS D
Unit
Step
Default
Description
ResCrvType_OV1
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tResetDef_OV1
0.00 - 6000.00
0.01
0.00
tResetIDMT_OV1
0.00 - 6000.00
0.01
0.00
A_OV1
0.005 - 999.000
0.001
0.140
B_OV1
0.500 - 99.000
0.001
1.000
C_OV1
0.000 - 1.000
0.001
1.000
D_OV1
0.000 - 10.000
0.001
0.000
P_OV1
0.001 - 10.000
0.001
0.020
ResCrvType_OV2
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tResetDef_OV2
0.00 - 6000.00
0.01
0.00
tResetIDMT_OV2
0.00 - 6000.00
0.01
0.00
A_OV2
0.005 - 999.000
0.001
0.140
B_OV2
0.500 - 99.000
0.001
1.000
C_OV2
0.000 - 1.000
0.001
1.000
D_OV2
0.000 - 10.000
0.001
0.000
P_OV2
0.001 - 10.000
0.001
0.020
ResCrvType_UV1
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tResetDef_UV1
0.00 - 6000.00
0.01
0.00
tResetIDMT_UV1
0.00 - 6000.00
0.01
0.00
A_UV1
0.005 - 999.000
0.001
0.140
B_UV1
0.500 - 99.000
0.001
1.000
320
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
C_UV1
0.000 - 1.000
0.001
1.000
D_UV1
0.000 - 10.000
0.001
0.000
P_UV1
0.001 - 10.000
0.001
0.020
ResCrvType_UV2
Instantaneous
Frozen timer
Linearly decreased
Instantaneous
tResetDef_UV2
0.00 - 6000.00
0.01
0.00
tResetIDMT_UV2
0.00 - 6000.00
0.01
0.00
A_UV2
0.005 - 999.000
0.001
0.140
B_UV2
0.500 - 99.000
0.001
1.000
C_UV2
0.000 - 1.000
0.001
1.000
D_UV2
0.000 - 10.000
0.001
0.000
P_UV2
0.001 - 10.000
0.001
0.020
9.1.6
Technical data
Table 176:
Function
Range or value
Accuracy
Base current
(1 - 99999) A
Base voltage
(0.05 - 2000.00) kV
(2 - 5000)% of IBase
(2 - 150)% of IBase
Section 9
Multipurpose protection
Function
1MRK505208-UUS D
Range or value
Accuracy
(0.00 - 6000.00) s
0.5% 10 ms
25 ms typically at 0 to 2 x Iset
25 ms typically at 2 to 0 x Iset
25 ms typically at 2 to 0 x Iset
25 ms typically at 0 to 2 x Iset
0.5% of Vn
Pickup undervoltage,
step 1 and 2
25 ms typically at 0 to 2 x Vset
25 ms typically at 2 to 0 x Vset
25 ms typically 2 to 0 x Vset
25 ms typically at 0 to 2 x Vset
Directional function
2.0 degrees
(1 to 90) degrees
2.0 degrees
> 95%
< 105%
> 95%
< 105%
Overcurrent:
Table continues on next page
322
Technical reference manual
Section 9
Multipurpose protection
1MRK505208-UUS D
Function
Range or value
Accuracy
10 ms typically at 0 to 2 x Iset
15 ms typically
10 ms typically at 2 to 0 x Iset
15 ms typically
10 ms typically at 0 to 2 x Vset
15 ms typically
10 ms typically at 2 to 0 x Vset
15 ms typically
Undercurrent:
Overvoltage:
Undervoltage:
323
Technical reference manual
324
Section 10
Secondary system supervision
1MRK505208-UUS D
Section 10
10.1
10.1.1
Introduction
The aim of the fuse failure supervision function (SDDRFUF) is to block voltage
measuring functions at failures in the secondary circuits between the voltage
transformer and the IED in order to avoid unwanted operations that otherwise might
occur.
The fuse failure supervision function basically has three different algorithms, negative
sequence and zero sequence based algorithms and an additional delta voltage and delta
current algorithm.
The negative sequence detection algorithm is recommended for IEDs used in isolated
or high-impedance grounded networks. It is based on the negative-sequence measuring
quantities, a high value of voltage without the presence of the negative-sequence
current 3I2.
The zero sequence detection algorithm is recommended for IEDs used in directly or
low impedance grounded networks. It is based on the zero sequence measuring
quantities, a high value of voltage 3V0 without the presence of the residual current 3I0.
For better adaptation to system requirements, an operation mode setting has been
introduced which makes it possible to select the operating conditions for negative
sequence and zero sequence based function. The selection of different operation modes
makes it possible to choose different interaction possibilities between the negative
sequence and zero sequence based algorithm.
325
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
A criterion based on delta current and delta voltage measurements can be added to the
fuse failure supervision function in order to detect a three phase fuse failure, which in
practice is more associated with voltage transformer switching during station operations.
10.1.2
Principle of operation
10.1.2.1
The measured signals are compared with their respective set values 3V0PU and 3I0PU,
3V2PU and 3I2PU.
The function enable the internal signal FuseFailDetZeroSeq if the measured zerosequence voltage is higher than the set value 3V0PU and the measured zero-sequence
current is below the set value 3I0PU.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value 3V2PU and the measured negative
sequence current is below the set value 3I2PU.
A drop out delay of 100 ms for the measured zero-sequence and negative sequence
current will prevent a false fuse failure detection at un-equal breaker opening at the two
line ends.
326
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
Sequence Detection
3I0PU
IA
CurrZeroSeq
Zero
sequence
filter
IB
3I0
a
b
a>b
Negative
sequence
filter
IC
3I2
AND
a
b
3I2PU
CurrNegSeq
100 ms
0
a>b
100 ms
0
AND
3V0PU
FuseFailDetZeroSeq
FuseFailDetNegSeq
VoltZeroSeq
VA
Zero
sequence
filter
VB
Negative
sequence
filter
VC
a
b
3V0
a>b
VoltNegSeq
a
b
3V2
a>b
3V2PU
ANSI10000036-2-en.vsd
ANSI10000036 V2 EN
Figure 151:
The calculated values 3V0, 3I0, 3I2 and 3V2 are available as service values on local
HMI and monitoring tool in PCM600.
The output signals 3PH, BLKV and BLKZ can be blocked in the following conditions:
The input BLOCK signal is a general purpose blocking signal of the fuse failure
supervision function. It can be connected to a binary input of the IED in order to
receive a block command from external devices or can be software connected to other
internal functions of the IED itself in order to receive a block command from internal
functions. Through OR gate it can be connected to both binary inputs and internal
function outputs.
327
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
The input BLKSP is intended to be connected to the trip output at any of the protection
functions included in the IED. When activated for more than 20 ms, the operation of
the fuse failure is blocked during a fixed time of 100 ms. The aim is to increase the
security against unwanted operations during the opening of the breaker, which might
cause unbalance conditions for which the fuse failure might operate.
The output signal BLKZ will also be blocked if the internal dead line detection is
activated. The block signal has a 200 ms drop-out time delay.
The input signal MCBOP is supposed to be connected via a terminal binary input to the
N.C. auxiliary contact of the miniature circuit breaker protecting the VT secondary
circuit. The MCBOP signal sets the output signals BLKU and BLKZ in order to block
all the voltage related functions when the MCB is open independent of the setting of
OpModeSel selector. The additional drop-out timer of 150 ms prolongs the presence of
MCBOP signal to prevent the unwanted operation of voltage dependent function due to
non simultaneous closing of the main contacts of the miniature circuit breaker.
The input signal 89b is supposed to be connected via a terminal binary input to the
N.C. auxiliary contact of the line disconnector. The 89b signal sets the output signal
BLKU in order to block the voltage related functions when the line disconnector is
open. The impedance protection function is not affected by the position of the line
disconnector since there will be no line currents that can cause malfunction of the
distance protection. If DISCPOS=0 it signifies that the line is connected to the system
and when the DISCPOS=1 it signifies that the line is disconnected from the system and
the block signal BLKU is generated.
The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, synchro-check and so on) except for the impedance protection.
The function output BLKZ shall be used for blocking the impedance protection function.
328
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
AND
BlocFuse = Yes
BLOCK
intBlock
OR
20 ms
t
BLKTRIP
AND
100 ms
t
FusefailStarted
AND
AND
AND
SealIn = On
3PH
AND
Any UL < UsealIn<
FuseFailDetDUDI
AND
OpDUDI = On
OR
5s
t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs
OpMode
CurrZeroSeq
CurrNegSeq
OR
UZsIZs
UZsIZs OR UNsINs
OR
AND
a>b
AND
200 ms
t
DeadLineDet1Ph
AND
150 ms
t
MCBOP
60 s
t
OR
OR
OR
OR
AND
AND
BLKZ
BLKU
AND
5s
t
AllCurrLow
CBCLOSED
DISCPOS
IEC10000033-2-en.vsd
IEC10000033 V2 EN
329
Technical reference manual
Section 10
Secondary system supervision
Figure 152:
10.1.2.2
1MRK505208-UUS D
The magnitude of the phase-ground voltage has been above UPh> for more than
1.5 cycle
The magnitude of DU is higher than the corresponding setting DU>
The magnitude of DI is below the setting DI>
The magnitude of the phase current in the same phase is higher than the setting IPh>
The circuit breaker is closed (CBCLOSED = True)
The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used to
reduce the risk of false fuse failure detection. If the current on the protected line is low,
a voltage drop in the system (not caused by fuse failure) is not by certain followed by
current change and a false fuse failure might occur
The second criterion requires that the delta condition shall be fulfilled in any phase at
the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way only the
first criterion can activate the delta function.
330
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
DUDI Detection
DUDI detection Phase 1
IL1
One cycle
delay
|DI|
a
b
DI<
UL1
a>b
One cycle
delay
|DU|
a
b
DU>
a
b
UPh>
IL2
a>b
20 ms
t
a>b
AND
1.5 cycle
t
UL2
IL3
UL3
UL1
a
b
IL1
IPh>
a
b
a<b
a>b
AND
CBCLOSED
UL2
a
b
IL2
AND
a
b
a
b
IL3
a
b
OR
AND
a<b
a>b
AND
AND
UL3
OR
OR
OR
AND
a<b
a>b
AND
AND
OR
OR
AND
OR
FuseFailDetDUDI
IEC10000034-1-en.vsd
IEC10000034 V1 EN
Figure 153:
331
Technical reference manual
Section 10
Secondary system supervision
10.1.2.3
1MRK505208-UUS D
a
b
IB
a
b
IC
a
b
a<b
AllCurrLow
AND
a<b
a<b
IDLDPU
VA
DeadLineDet1Ph
a
b
VB
a
b
VC
a
b
a<b
a<b
AND
OR
AND
AND
AND
a<b
DLD1PH
AND
AND
DLD3PH
VDLDPU
intBlock
ANSI0000035-1-en.vsd
ANSI0000035 V1 EN
Figure 154:
10.1.2.4
Main logic
A simplified diagram for the functionality is found in figure 155. The fuse failure
supervision function (SDDRFUF) can be switched on or off by the setting parameter
Operation to Enabled or Disabled.
For increased flexibility and adaptation to system requirements an operation mode
selector, OpModeSel, has been introduced to make it possible to select different
operating modes for the negative and zero sequence based algorithms. The different
operation modes are:
332
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
V0I0 OR V2I2; Both negative and zero sequence is activated and working in
parallel in an OR-condition
V0I0 AND V2I2; Both negative and zero sequence is activated and working in
series (AND-condition for operation)
OptimZsNs; Optimum of negative and zero sequence (the function that has the
highest magnitude of measured negative and zero sequence current will be activated)
The delta function can be activated by setting the parameter OpDVDI to Enabled.
When selected it operates in parallel with the sequence based algorithms.
As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,
FuseFailDetNegSeq or FuseFailDetDVDI, and the specific functionality is released,
the function will activate the output signal BLKV. The output signal BLKZ will be
activated as well if not the internal dead phase detection, DeadLineDet1Ph, is not
activated at the same time. The output BLKV can be used for blocking voltage related
measuring functions (under voltage protection, synchro-check, and so on). For
blocking of impedance protection functions output BLKZ shall be used.
If the fuse failure situation is present for more than 5 seconds and the setting parameter
SealIn is set to Enabled it will be sealed in as long as at least one phase voltages is
below the set value VSealInPU. This will keep the BLKV and BLKZ signals activated
as long as any phase voltage is below the set value VSealInPU. If all three phase
voltages drop below the set value VSealInPU and the setting parameter SealIn is set to
Enabled the output signal 3PH will also be activated. The signals 3PH, BLKV and
BLKZ signals will now be active as long as any phase voltage is below the set value
VSealInPU.
If SealIn is set to Enabled the fuse failure condition is stored in the non volatile
memory in the IED. At start-up of the IED (due to auxiliary power interruption or restart due to configuration change) it checks the stored value in its non volatile memory
and re-establishes the conditions that were present before the shut down. All phase
voltages must be greater than VSealInPU before fuse failure is de-activated and
removes the block of different protection functions.
The output signal BLKV will also be active if all phase voltages have been above the
setting VSealInPU for more than 60 seconds, the zero or negative sequence voltage has
been above the set value 3V0PU and 3V2PU for more than 5 seconds, all phase
currents are below the setting IDLDPU (operate level for dead line detection) and the
circuit breaker is closed (input 52a is activated).
If a MCB is used then the input signal MCBOP is to be connected via a terminal binary
input to the N.C. auxiliary contact of the miniature circuit breaker protecting the VT
secondary circuit. The MCBOP signal sets the output signals BLKV and BLKZ in
order to block all the voltage related functions when the MCB is open independent of
the setting of OpModeSel or OpDVDI. An additional drop-out timer of 150 ms
333
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
prolongs the presence of MCBOP signal to prevent the unwanted operation of voltage
dependent function due to non simultaneous closing of the main contacts of the
miniature circuit breaker.
The input signal 89b is supposed to be connected via a terminal binary input to the
N.C. auxiliary contact of the line disconnector. The 89b signal sets the output signal
BLKV in order to block the voltage related functions when the line disconnector is
open. The impedance protection function does not have to be affected since there will
be no line currents that can cause malfunction of the distance protection.
The output signals 3PH, BLKV and BLKZ as well as the signals DLD1PH and
DLD3PH from dead line detections are blocked if any of the following conditions occur:
The input BLOCK is a general purpose blocking signal of the fuse failure supervision
function. It can be connected to a binary input of the IED in order to receive a block
command from external devices or can be software connected to other internal
functions of the IED. Through OR gate it can be connected to both binary inputs and
internal function outputs.
The input BLKTRIP is intended to be connected to the trip output of any of the
protection functions included in the IED and/or trip from external equipments via
binary inputs. When activated for more than 20 ms without any fuse fail detected, the
operation of the fuse failure is blocked during a fixed time of 100 ms. The aim is to
increase the security against unwanted operations during the opening of the breaker,
which might cause unbalance conditions for which the fuse failure might operate.
334
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
AND
BlocFuse = Yes
BLOCK
intBlock
OR
20 ms
t
BLKTRIP
AND
100 ms
t
FusefailStarted
AND
AND
AND
SealIn = Enabled
3PH
AND
Any VL < VSealInPU
FuseFailDetDUDI
AND
OpDVDI = Enabled
OR
5s
t
FuseFailDetZeroSeq
AND
AND
FuseFailDetNegSeq
AND
UNsINs
OpModeSel
CurrZeroSeq
CurrNegSeq
OR
UZsIZs
UZsIZs OR UNsINs
OR
AND
a>b
AND
200 ms
t
DeadLineDet1Ph
AND
150 ms
t
MCBOP
60 s
t
VoltZeroSeq
VoltNegSeq
OR
OR
OR
OR
AND
AND
BLKZ
BLKV
AND
5s
t
AllCurrLow
52a
89b
ANSI10000033-2-en.vsd
ANSI10000033 V2 EN
335
Technical reference manual
Section 10
Secondary system supervision
Figure 155:
10.1.3
1MRK505208-UUS D
Simplified logic diagram for fuse failure supervision function, Main logic
Function block
SDDRFUF
I3P*
V3P*
BLOCK
52A
MCBOP
89B
BLKTRIP
BLKZ
BLKV
3PH
DLD1PH
DLD3PH
ANSI05000700-2-en.vsd
ANSI05000700 V2 EN
Figure 156:
10.1.4
Default
Description
I3P
GROUP
SIGNAL
Current connection
V3P
GROUP
SIGNAL
Voltage connection
BLOCK
BOOLEAN
Block of function
52a
BOOLEAN
MCBOP
BOOLEAN
89b
BOOLEAN
BLKTRIP
BOOLEAN
Table 178:
Name
Description
BLKZ
BOOLEAN
BLKV
BOOLEAN
General pickup
3PH
BOOLEAN
Three-phase pickup
DLD1PH
BOOLEAN
DLD3PH
BOOLEAN
336
Technical reference manual
Section 10
Secondary system supervision
1MRK505208-UUS D
10.1.5
Table 179:
Setting parameters
SDDRFUF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Enabled
Disable/Enable Operation
IBase
1 - 99999
3000
Base current
VBase
0.05 - 2000.00
kV
0.05
400.00
Base voltage
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
V0I0
3V0PU
1 - 100
%VB
30
3I0PU
1 - 100
%IB
10
3V2PU
1 - 100
%VB
30
3I2PU
1 - 100
%IB
10
OpDVDI
Disabled
Enabled
Disabled
DVPU
1 - 100
%VB
60
DIPU
1 - 100
%IB
15
VPPU
1 - 100
%VB
70
IPPU
1 - 100
%IB
10
SealIn
Disabled
Enabled
Enabled
VSealInPU
1 - 100
%VB
70
IDLDPU
1 - 100
%IB
VDLDPU
1 - 100
%VB
60
337
Technical reference manual
Section 10
Secondary system supervision
10.1.6
1MRK505208-UUS D
Technical data
Table 180:
Function
Range or value
Accuracy
(1-100)% of VBase
1.0% of Vn
(1100)% of IBase
1.0% of In
(1100)% of VBase
0.5% of Vn
(1100)% of IBase
1.0% of In
(1100)% of VBase
5.0% of Vn
(1100)% of IBase
5.0% of In
(1-100)% of VBase
0.5% of Vn
(1-100)% of IBase
1.0% of In
(1-100)% of VBase
0.5% of Vn
(1-100)% of IBase
1.0% of In
25 ms typically at 1 to 0 of Vbase
35 ms typically at 0 to 1 of Vbase
338
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Section 11
Control
11.1
IEC 61850
identification
IEC 60617
identification
SMBRREC
ANSI/IEEE C37.2
device number
79
O->I
SYMBOL-L V1 EN
11.1.1
Introduction
The autoreclosing function provides high-speed and/or delayed three pole
autoreclosing. The autoreclosing can be used for delayed busbar restoration. One
Autorecloser (SMBRREC ,79) per zone can be made available.
11.1.2
Principle of operation
11.1.2.1
Logic Diagrams
The logic diagrams below illustrate the principles applicable in the understanding of
the functionality.
11.1.2.2
339
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.1.2.3
11.1.2.4
CBREADY: CB ready for a reclosing cycle, for example, charged operating gear
52a: to ensure that the CB was closed when the line fault occurred and initiation
was applied
No blocking or inhibit signal shall be present.
After the initiate has been accepted, it is latched in and an internal signal Started is
set. It can be interrupted by certain events, like an inhibit signal.
To initiate auto-reclosing by CB position Open instead of from protection trip signals,
one has to configure the CB Open position signal to inputs 52a and RI and set a
parameter StartByCBOpen = Enabled and CBAuxContType = NormClosed (normally
340
Technical reference manual
Section 11
Control
1MRK505208-UUS D
closed, 52b). One also has to configure and connect signals from manual trip
commands to input INHIBIT.
The logic for switching the auto-recloser Enabled/Disabled and the starting of the
reclosing is shown in figure 157. The following should be considered:
Setting Operation can be set to Disabled, External ctrl or Enabled. External ctrl
offers the possibility of switching by external switches to inputs ON and OFF,
communication commands to the same inputs, and so on.
SMBRREC (79) is normally started by tripping. It is either a Zone 1 and
Communication aided trip or a general trip. If the general trip is used the function
must be blocked from all back-up tripping connected to INHIBIT. In both
alternatives the breaker failure function must be connected to inhibit the function.
RI makes a first attempt with synchronism-check, RI_HS makes its first attempt
without synchronism-check. TRSOTF starts shots 2-5.
Circuit breaker checks that the breaker was closed for a certain length of time
before the starting occurred and that the CB has sufficient stored energy to
perform an auto-reclosing sequence and is connected to inputs 52a and CBREADY.
Operation:Enabled
Operation:Disabled
Operation:External Ctrl
ON
AND
OFF
AND
OR
RI
RI_HS
OR
OR
OR
autoInitiate
Additional conditions
TRSOTF
initiate
AND
PICKUP
CBREADY
52a
SETON
AND
AND
0
0-t120
CB Closed
AND
AND
0-tCBClosedMin
0
AND
Blocking conditions
OR
AND
READY
Inhibit conditions
count 0
ANSI05000782_2_en.vsd
ANSI05000782 V2 EN
Figure 157:
341
Technical reference manual
Section 11
Control
11.1.2.5
1MRK505208-UUS D
11.1.2.6
342
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Extended t1
PLCLOST
initiate
pickup
AND
0-tTrip
0
OR
AND
AND
Extend t1
AND
AND
long duration
(block SMBRREC)
ANSI05000783_2_en.vsd
ANSI05000783 V2 EN
Figure 158:
Control of extended auto-reclosing open time and long trip pulse detection
When dead time has elapsed during the auto-reclosing procedure certain conditions
must be fulfilled before the CB closing command is issued. To achieve this, signals are
exchanged between program modules to check that these conditions are met. In threephase reclosing a synchronizing and/or energizing check can be used. It is possible to
use a synchronism check function in the same physical device or an external one. The
release signal is configured by connecting to the auto-reclosing function input SYNC.
If reclosing without checking is preferred the SYNC input can be set to TRUE (set
high). Another possibility is to set the output of the synchronism check function to a
permanently activated state. At confirmation from the synchronism check, or if the
reclosing is of single-phase or two-phase type, the signal passes on. At single-phase, twophase reclosing and at three-phase high-speed reclosing started by RI_HS,
synchronization is not checked, and the state of the SYNC input is disregarded.
By choosing CBReadyType = CO (CB ready for a Close-Open sequence) the readiness
of the circuit breaker is also checked before issuing the CB closing command. If the
CB has a readiness contact of type CBReadyType = OCO (CB ready for an Open-CloseOpen sequence) this condition may not be complied with after the tripping and at the
moment of reclosure. The Open-Close-Open condition was however checked at the
start of the reclosing cycle and it is then likely that the CB is prepared for a CloseOpen sequence.
343
Technical reference manual
Section 11
Control
1MRK505208-UUS D
The synchronism check or energizing check must be fulfilled within a set time interval,
tSync. If it is not, or if other conditions are not met, the reclosing is interrupted and
blocked.
The reset timer defines a time from the issue of the reclosing command, after which the
reclosing function resets. Should a new trip occur during this time, it is treated as a
continuation of the first fault. The reset timer is started when the CB closing command
is given.
A number of outputs for Autoreclosing state control keeps track of the actual state in
the reclosing sequence.
344
Technical reference manual
Section 11
Control
1MRK505208-UUS D
0-t1 1Ph
0
From logic for
reclosing
programs
1P2PTO
3PHSTO
3PT1TO
3PT2TO
3PT3TO
3PT4TO
3PT5TO
OR
0-t1 2Ph
0
AND
OR
OR
0-t1 3Ph HS
0
3PHSTO
0-t1 3Ph
0
3PT1TO
Pulse AR
AND
SYNC
initiate
CBREADY
AND
AND
SMBRREC State
Control
COUNTER
0-tSync
0
AND
Blocking out
OR
CL
Shot 0
Shot 1
0
1
Shot 2
Shot 3
2
3
Pulse SMBRREC (above)
OR
TR2P
LOGIC
reclosing
programs
TR3P
AND
0-tReset
0
Reset Timer On
Shot 4
Shot 5
4
5
1PT1
PICKUP
2PT1
RI
3PHS
Shot 0
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
3PT1
INPROGR
OR
3PT2
3PT3
3PT4
PERMIT1P
3PT5
PREP3P
1
Blocking out
INHIBIT
OR
0
tInhibit
Inhibit (internal)
ANSI05000784_2_en.vsd
ANSI05000784 V2 EN
Figure 159:
345
Technical reference manual
Section 11
Control
1MRK505208-UUS D
tPulse
AND
**)
CLOSECMD
OR
50 ms
1PT1
AND
2PT1
AND
3PT1
AND
3PT2
AND
3PT3
AND
3PT4
AND
3PT5
AND
RSTCOUNT
counter
counter
COUNT1P
COUNT2P
counter
COUNT3P1
counter
COUNT3P2
counter
COUNT3P3
counter
COUNT3P4
counter
COUNT3P5
counter
COUNTAR
Figure 160:
Transient fault
After the reclosing command the reset timer tReset starts running for the set time. If no
tripping occurs within this time, the auto-reclosing will reset.
346
Technical reference manual
Section 11
Control
1MRK505208-UUS D
If a new trip occurs after the CB closing command, and a new input signal RI or
TRSOTF appears, the output UNSUCCL (unsuccessful closing) is set high. The timers
for the first shot can no longer be started. Depending on the setting for the number of
reclosing shots, further shots may be made or the reclosing sequence will be ended.
After the reset time has elapsed, the auto-reclosing function resets but the CB remains
open. The CB closed data at the 52a input will be missing. Because of this, the
reclosing function will not be ready for a new reclosing cycle.
Normally the signal UNSUCCL appears when a new trip and initiate is received after
the last reclosing shot has been made and the auto-reclosing function is blocked. The
signal resets once the reset time has elapsed. The unsuccessful signal can also be
made to depend on CB position input. The parameter UnsucClByCBChk should then be
set to CBCheck, and a timer tUnsucCl should also be set. If the CB does not respond to
the closing command and does not close, but remains open, the output UNSUCCL is
set high after time tUnsucCl.
initiate
block start
AND
OR
shot 0
AND
UNSUCCL
UnsucClByCBchk = CBcheck
Pulse AR (Closing)
52a
OR
CBclosed
AND
0-tUnsucCl
0
AND
en05000786_ansi.vsd
ANSI05000786 V1 EN
Figure 161:
347
Technical reference manual
Section 11
Control
1MRK505208-UUS D
0-tAutoContWait
0
AND
CLOSECMD
AND
S Q
R
AND
52a
CBClosed
OR
RI
OR
initiate
en05000787_ansi.vsd
ANSI05000787 V1 EN
Figure 162:
348
Technical reference manual
Section 11
Control
1MRK505208-UUS D
StartByCBOpen= Enabled
NOT
RI
AND
RI_HS
AND
100 ms
PICKUP
AND
100 ms
AND
ANSI05000788_2_en.vsd
ANSI05000788 V2 EN
Figure 163:
11.1.2.7
349
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Fault
CB POS
Closed
Open
Closed
CB READY
RECL. INT. (Trip)
SYNC
tReset
READY
INPROG
1PT1
ACTIVE
CLOSE CMD
t1 1Ph
tPulse
PREP3P
SUCCL
Time
en04000196-2_ansi.vsd
ANSI04000196 V2 EN
Figure 164:
350
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Fault
CB POS
Closed
Open
Open
CB READY
t1 3Ph
3PT2
t2 3Ph
tReset
ACTIVE
CLOSE CMD
tPulse
tPulse
PREP3P
UNSUCCL
Time
en04000197_ansi.vsd
ANSI04000197 V1 EN
Figure 165:
351
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-RI
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
AR01-CLOSECMD
t1s
AR01-P3P
AR01-UNSUC
tReset
en04000198_ansi.vsd
ANSI04000198 V1 EN
Figure 166:
352
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Fault
AR01-CBCLOSED
AR01-CBREADY(CO)
AR01-RI
AR01-TR3P
AR01-SYNC
AR01-READY
AR01-INPROGR
AR01-1PT1
AR01-T1
AR01-T2
AR01-CLOSECMD
t1s
t2
AR01-P3P
AR01-UNSUC
tReset
en04000199_ansi.vsd
ANSI04000199 V1 EN
Figure 167:
Permanent single-phase fault. Program 1ph + 3ph or 1/2ph + 3ph, twoshot reclosing
353
Technical reference manual
Section 11
Control
11.1.3
1MRK505208-UUS D
Function block
SMBRREC (79)
ON
BLOCKED
OFF
SETON
BLKON
READY
BLKOFF
ACTIVE
RESET
SUCCL
INHIBIT
UNSUCCL
RI
INPROGR
RI_HS
1PT1
TRSOTF
2PT1
SKIPHS
3PT1
ZONESTEP
3PT2
TR2P
3PT3
TR3P
3PT4
THOLHOLD
3PT5
CBREADY
PERMIT1P
52A
PREP3P
PLCLOST
CLOSECMD
SYNC
WFMASTER
WAIT
COUNT1P
RSTCOUNT
COUNT2P
MODEINT
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ANSI06000189-2-en.vsd
ANSI06000189 V2 EN
Figure 168:
11.1.4
Default
Description
ON
BOOLEAN
OFF
BOOLEAN
BLKON
BOOLEAN
BLKOFF
BOOLEAN
RESET
BOOLEAN
INHIBIT
BOOLEAN
RI
BOOLEAN
RI_HS
BOOLEAN
TRSOTF
BOOLEAN
SKIPHS
BOOLEAN
ZONESTEP
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
TR2P
BOOLEAN
TR3P
BOOLEAN
THOLHOLD
BOOLEAN
CBREADY
BOOLEAN
52a
BOOLEAN
PLCLOST
BOOLEAN
SYNC
BOOLEAN
WAIT
BOOLEAN
RSTCOUNT
BOOLEAN
MODEINT
INTEGER
Table 182:
Name
Description
BLOCKED
BOOLEAN
SETON
BOOLEAN
READY
BOOLEAN
ACTIVE
BOOLEAN
SUCCL
BOOLEAN
UNSUCCL
BOOLEAN
INPROGR
BOOLEAN
1PT1
BOOLEAN
2PT1
BOOLEAN
3PT1
BOOLEAN
3PT2
BOOLEAN
3PT3
BOOLEAN
3PT4
BOOLEAN
3PT5
BOOLEAN
PERMIT1P
BOOLEAN
PREP3P
BOOLEAN
CLOSECMD
BOOLEAN
WFMASTER
BOOLEAN
COUNT1P
INTEGER
COUNT2P
INTEGER
Section 11
Control
1MRK505208-UUS D
Name
11.1.5
Table 183:
Name
Type
Description
COUNT3P1
INTEGER
COUNT3P2
INTEGER
COUNT3P3
INTEGER
COUNT3P4
INTEGER
COUNT3P5
INTEGER
COUNTAR
INTEGER
MODE
INTEGER
Setting parameters
SMBRREC (79) Group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
External ctrl
Enabled
External ctrl
Off, ExternalCtrl, On
ARMode
3 phase
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
1/2/3ph
t1 1Ph
0.000 - 60.000
0.001
1.000
t1 3Ph
0.000 - 60.000
0.001
6.000
t1 3PhHS
0.000 - 60.000
0.001
0.400
tReset
0.00 - 6000.00
0.01
60.00
tSync
0.00 - 6000.00
0.01
30.00
tTrip
0.000 - 60.000
0.001
0.200
tPulse
0.000 - 60.000
0.001
0.200
tCBClosedMin
0.00 - 6000.00
0.01
5.00
tUnsucCl
0.00 - 6000.00
0.01
30.00
Priority
None
Low
High
None
tWaitForMaster
0.00 - 6000.00
0.01
60.00
356
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 184:
Name
Values (Range)
Unit
Step
Default
Description
NoOfShots
1
2
3
4
5
StartByCBOpen
Disabled
Enabled
Disabled
To be set ON if AR is to be started by CB
open position
CBAuxContType
NormClosed
NormOpen
NormOpen
CBReadyType
CO
OCO
CO
t1 2Ph
0.000 - 60.000
0.001
1.000
t2 3Ph
0.00 - 6000.00
0.01
30.00
t3 3Ph
0.00 - 6000.00
0.01
30.00
t4 3Ph
0.00 - 6000.00
0.01
30.00
t5 3Ph
0.00 - 6000.00
0.01
30.00
Extended t1
Disabled
Enabled
Disabled
tExtended t1
0.000 - 60.000
0.001
0.500
tInhibit
0.000 - 60.000
0.001
5.000
CutPulse
Disabled
Enabled
Disabled
Follow CB
Disabled
Enabled
Disabled
AutoCont
Disabled
Enabled
Disabled
tAutoContWait
0.000 - 60.000
0.001
2.000
UnsucClByCBChk
NoCBCheck
CB check
NoCBCheck
BlockByUnsucCl
Disabled
Enabled
Disabled
ZoneSeqCoord
Disabled
Enabled
Disabled
357
Technical reference manual
Section 11
Control
11.1.6
1MRK505208-UUS D
Technical data
Table 185:
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
Range or value
1-5
(0.000-60.000) s
0.5% 10 ms
shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
Reset time
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
11.2
11.2.1
Introduction
Accuracy
The apparatus control functions are used for control and supervision of circuit
breakers, disconnectors and grounding switches within a bay. Permission to operate is
given after evaluation of conditions from other functions such as interlocking,
synchronism check, operator place selection and external or internal blockings.
In normal security, the command is processed and the resulting position is not
supervised. However with enhanced security, the command is processed and the
resulting position is supervised.
358
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.2.2
Principle of operation
A bay can handle, for example a power line, a transformer, a reactor, or a capacitor
bank. The different primary apparatuses within the bay can be controlled via the
apparatus control function directly by the operator or indirectly by automatic sequences.
Because a primary apparatus can be allocated to many functions within a Substation
Automation system, the object-oriented approach with a function module that handles
the interaction and status of each process object ensures consistency in the process
information used by higher-level control functions.
Primary apparatuses such as breakers and disconnectors are controlled and supervised
by one software module (SCSWI) each. Because the number and type of signals
connected to a breaker and a disconnector are almost the same, the same software is
used to handle these two types of apparatuses.
The software module is connected to the physical process in the switchyard via an
interface module by means of a number of digital inputs and outputs. One type of
interface module is intended for a circuit breaker (SXCBR) and another type is
intended for a disconnector or grounding switch (SXSWI). Four types of function
blocks are available to cover most of the control and supervision within the bay. These
function blocks are interconnected to form a control function reflecting the switchyard
configuration. The total number used depends on the switchyard configuration. These
four types are:
The three latter functions are logical nodes according to IEC 61850. The functions
Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle the
local/remote switch, and the functions Bay reserve (QCRSV) and Reservation input
(RESIN), for the reservation function, also belong to the apparatus control function.
The principles of operation, function block, input and output signals and setting
parameters for all these functions are described below.
11.2.3
Error handling
Depending on the error that occurs during the command sequence the error signal will
be set with a value. Table 186 describes vendor specific cause values in addition to
these specified in IEC 61850-8-1 standard. The list of values of the cause are in order
of priority. The values are available over the IEC 61850. An output L_CAUSE on the
function block for Switch controller (SCSWI), Circuit breaker (SXCBR) and Circuit
switch (SXSWI) indicates the latest value of the error during the command.
359
Section 11
Control
1MRK505208-UUS D
Table 186:
Description
Supported
no error
serviceError-type
blocked-by-switchinghierarchy
select-failed
invalid-position
position-reached
parameter-change-inexecution
step-limit
blocked-by-mode
blocked-by-process
10
blocked-by-interlocking
11
blocked-by-synchrocheck
12
command-already-inexecution
13
blocked-by-health
14
1-of-n-control
15
abortion-by-cancel
16
time-limit-over
17
abortion-by-trip
18
object-not-selected
19
Not in use
360
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Attribute value
Description
-20
Not in use
-21
Not in use
-23
blocked-for-command
-24
blocked-for-opencommand
-25
blocked-for-closecommand
-26
Not in use
-27
Not in use
-28
Not in use
-29
Not in use
-30
long-operation-time
-31
switch-not-start-moving
-32
persisting-intermediatestate
-33
switch-returned-to-initialposition
-34
switch-in-bad-state
-35
not-expected-final-position
Vendor specific
11.2.4
11.2.4.1
Introduction
Supported
The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the
bay.
11.2.4.2
Principle of operation
The functionality of the Bay control (QCBAY) function is not defined in the IEC 61850
81 standard, which means that the function is a vendor specific logical node.
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay for example, switch control
functions, voltage control functions and measurement functions.
361
Technical reference manual
Section 11
Control
1MRK505208-UUS D
The local panel switch is a switch that defines the operator place selection. The switch
connected to this function can have three positions remote/local/off. The positions are
here defined so that remote means that operation is allowed from station/remote level
and local from the IED level. The local/remote switch is also on the control/protection
IED itself, which means that the position of the switch and its validity information are
connected internally, and not via I/O boards. When the switch is mounted separately
from the IED the signals are connected to the function via I/O boards.
When the local panel switch (or LHMI selection, depending on the set source to select
this) is in Off position, all commands from remote and local level will be ignored. If
the position for the local/remote switch is not valid the PSTO output will always be set
to faulty state (3), which means no possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch, the
function blocks LOCREM and LOCREMCTRL are needed and connected to QCBAY.
The actual state of the operator place is presented by the value of the Permitted Source
To Operate, PSTO signal. The PSTO value is evaluated from the local/remote switch
position according to table 187. In addition, there is one configuration parameter that
affects the value of the PSTO signal. If the parameter AllPSTOValid is set and LRswitch position is in Local or Remote state, the PSTO value is set to 5 (all), that is, it is
permitted to operate from both local and remote level without any priority. When the
external panel switch is in Off position the PSTO value shows the actual state of switch
that is, 0. In this case it is not possible to control anything.
Table 187:
Local panel switch
positions
AllPSTOValid
(configuration
parameter)
0 = Off
--
1 = Local
Priority
Local Panel
1 = Local
No priority
2 = Remote
Priority
Remote level
2 = Remote
No priority
3 = Faulty
--
Blockings
The blocking states for position indications and commands are intended to provide the
possibility for the user to make common blockings for the functions configured within
a complete bay.
362
Technical reference manual
Section 11
Control
1MRK505208-UUS D
The blocking facilities provided by the bay control function are the following:
Blocking of position indications, BL_UPD. This input will block all inputs related
to apparatus positions for all configured functions within the bay.
Blocking of commands, BL_CMD. This input will block all commands for all
configured functions within the bay.
Blocking of function, BLOCK, signal from DO (Data Object) Behavior (IEC 61850
81). If DO Behavior is set to "blocked" it means that the function is active, but no
outputs are generated, no reporting, control commands are rejected and functional
and configuration data is visible.
The switching of the Local/Remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been
defined in the IED. Otherwise the default authority level, SuperUser, can handle the
control without LogOn. The users and passwords are defined in PCM600.
11.2.4.3
Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
IEC10000048-1-en.vsd
IEC10000048 V1 EN
Figure 169:
11.2.4.4
Default
Description
LR_OFF
BOOLEAN
LR_LOC
BOOLEAN
LR_REM
BOOLEAN
LR_VALID
BOOLEAN
BL_UPD
BOOLEAN
BL_CMD
BOOLEAN
363
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 189:
Name
11.2.4.5
Table 190:
Name
AllPSTOValid
Type
Description
PSTO
INTEGER
UPD_BLKD
BOOLEAN
CMD_BLKD
BOOLEAN
LOC
BOOLEAN
REM
BOOLEAN
Setting parameters
QCBAY Non group settings (basic)
Values (Range)
Priority
No priority
Unit
-
Step
-
Default
Priority
Description
Priority of originators
11.2.5
11.2.5.1
Introduction
The signals from the local HMI or from an external local/remote switch are applied via
the function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)
function block. A parameter in function block LOCREM is set to choose if the switch
signals are coming from the local HMI or from an external hardware switch connected
via binary inputs.
11.2.5.2
Principle of operation
The function block Local remote (LOCREM) handles the signals coming from the local/
remote switch. The connections are seen in figure 170, where the inputs on function
block LOCREM are connected to binary inputs if an external switch is used. When the
local HMI is used, the inputs are not used and are set to FALSE in the configuration.
The outputs from the LOCREM function block control the output PSTO (Permitted
Source To Operate) on Bay control (QCBAY).
364
Technical reference manual
Section 11
Control
1MRK505208-UUS D
LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
QCBAY
LR_ OFF
PSTO
LR_ LOC UPD_ BLKD
LR_ REM CMD_ BLKD
LOC
LR_ VALID
REM
BL_ UPD
BL_ CMD
LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
QCBAY
LR_ OFF
PSTO
LR_ LOC UPD_ BLKD
LR_ REM CMD_ BLKD
LOC
LR_ VALID
REM
BL_ UPD
BL_ CMD
LOCREMCTRL
PSTO1
HMICTR1
PSTO2
HMICTR2
PSTO3
HMICTR3
PSTO4
HMICTR4
PSTO5
HMICTR5
PSTO6
HMICTR6
PSTO7
HMICTR7
PSTO8
HMICTR8
PSTO9
HMICTR9
PSTO 10
HMICTR 10
PSTO 11
HMICTR 11
PSTO 12
HMICTR 12
IEC10000052-1-en.vsd
IEC10000052 V1 EN
Figure 170:
Configuration for the local/remote handling for a local HMI with two
bays and two screen pages
If the IED contains control functions for several bays, the local/remote position can be
different for the included bays. When the local HMI is used the position of the local/
remote switch can be different depending on which single line diagram screen page
that is presented on the local HMI. The function block Local remote control
(LOCREMCTRL) controls the presentation of the LEDs for the local/remote position
to applicable bay and screen page.
The switching of the local/remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been
defined in the IED. Otherwise the default authority level, SuperUser, can handle the
control without LogOn. The users and passwords are defined in PCM600.
365
Technical reference manual
Section 11
Control
11.2.5.3
1MRK505208-UUS D
Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL
OFF
LOCAL
REMOTE
VALID
IEC05000360-2-en.vsd
IEC05000360 V2 EN
Figure 171:
PSTO1
PSTO2
PSTO3
PSTO4
PSTO5
PSTO6
PSTO7
PSTO8
PSTO9
PSTO10
PSTO11
PSTO12
LOCREMCTRL
HMICTR1
HMICTR2
HMICTR3
HMICTR4
HMICTR5
HMICTR6
HMICTR7
HMICTR8
HMICTR9
HMICTR10
HMICTR11
HMICTR12
IEC05000361-2-en.vsd
IEC05000361 V2 EN
Figure 172:
11.2.5.4
Default
Description
CTRLOFF
BOOLEAN
Disable control
LOCCTRL
BOOLEAN
Local in control
REMCTRL
BOOLEAN
Remote in control
LHMICTRL
INTEGER
LHMI control
Table 192:
Name
Description
OFF
BOOLEAN
Control is disabled
LOCAL
BOOLEAN
REMOTE
BOOLEAN
VALID
BOOLEAN
366
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 193:
Name
Type
INTEGER
PSTO2
INTEGER
PSTO3
INTEGER
PSTO4
INTEGER
PSTO5
INTEGER
PSTO6
INTEGER
PSTO7
INTEGER
PSTO8
INTEGER
PSTO9
INTEGER
PSTO10
INTEGER
PSTO11
INTEGER
PSTO12
INTEGER
Name
Table 195:
Description
PSTO1
Table 194:
11.2.5.5
Default
Type
Description
HMICTR1
INTEGER
HMICTR2
INTEGER
HMICTR3
INTEGER
HMICTR4
INTEGER
HMICTR5
INTEGER
HMICTR6
INTEGER
HMICTR7
INTEGER
HMICTR8
INTEGER
HMICTR9
INTEGER
HMICTR10
INTEGER
HMICTR11
INTEGER
HMICTR12
INTEGER
Setting parameters
LOCREM Non group settings (basic)
Name
ControlMode
Values (Range)
Internal LR-switch
External LR-switch
Unit
-
Step
-
Default
Internal LR-switch
Description
Control mode for internal/external LR-switch
367
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.2.6
11.2.6.1
Introduction
The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may handle
and operate on one three-phase device.
11.2.6.2
Principle of operation
The Switch controller (SCSWI) is provided with verification checks for the select execute sequence, that is, checks the conditions prior each step of the operation. The
involved functions for these condition verifications are interlocking, reservation,
blockings and synchronism-check.
Control handling
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
parameter CtlModel defines which one of the two control models is used. The control
model "direct with normal security" does not require a select whereas, the "SBO with
enhanced security" command model requires a select before execution.
Normal security means that only the command is evaluated and the resulting position is
not supervised. Enhanced security means that the command sequence is supervised in
three steps, the selection, command evaluation and the supervision of position. Each
step ends up with a pulsed signal to indicate that the respective step in the command
sequence is finished. If an error occurs in one of the steps in the command sequence,
the sequence is terminated and the error is mapped into the enumerated variable
"cause" attribute belonging to the pulsed response signal for the IEC 61850
communication. The last cause L_CAUSE can be read from the function block and
used for example at commissioning.
There is no relation between the command direction and the actual
position. For example, if the switch is in close position it is possible to
execute a close command.
Before an execution command, an evaluation of the position is done. If the parameter
PosDependent is true and the position is in intermediate state or in bad state no
execution command is sent. If the parameter is false the execution command is sent
independent of the position value.
368
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Evaluation of position
In the case when there are three one-phase switches connected to the switch control
function, the switch control will "merge" the position of the three switches to the
resulting three-phase position. In the case when the position differ between the onephase switches, following principles will be applied:
The position output from switch (SXCBR or SXSWI) is connected to SCSWI. With
the group signal connection the SCSWI obtains the position, time stamps and quality
attributes of the position which is used for further evaluation.
All switches in open position:
The time stamp of the output three-phase position from switch control will have the
time stamp of the last changed phase when it goes to end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.
In addition, there is also the possibility that one of the one-phase switches will change
position at any time due to a trip. Such situation is here called pole discrepancy and is
supervised by this function. In case of a pole discrepancy situation, that is, the position
of the one-phase switches are not equal for a time longer than the setting tPoleDiscord,
an error signal POLEDISC will be set.
In the supervision phase, the switch controller function evaluates the "cause" values
from the switch modules Circuit breaker (SXCBR)/ Circuit switch (SXSWI). At error
the "cause" value with highest priority is shown.
Blocking principles
The blocking signals are normally coming from the bay control function (QCBAY)
and via the IEC 61850 communication from the operator place.
The IEC 61850 communication has always priority over binary inputs,
e.g. a block command on binary inputs will not prevent commands over
IEC 61850.
The different blocking possibilities are:
Section 11
Control
1MRK505208-UUS D
The Switch controller (SCSWI) works in conjunction with the synchronism-check and
the synchronizing function (SESRSYN, 25). It is assumed that the synchronism-check
function is continuously in operation and gives the result to SCSWI. The result from
the synchronism-check function is evaluated during the close execution. If the operator
performs an override of the synchronism-check, the evaluation of the synchronismcheck state is omitted. When there is a positive confirmation from the synchronismcheck function, SCSWI will send the close signal EXE_CL to the switch function
Circuit breaker (SXCBR).
When there is no positive confirmation from the synchronism-check function, SCSWI
will send a start signal START_SY to the synchronizing function, which will send the
closing command to SXCBR when the synchronizing conditions are fulfilled, see
figure 173. If no synchronizing function is included, the timer for supervision of the
"synchronizing in progress signal" is set to 0, which means no start of the
synchronizing function. SCSWI will then set the attribute "blocked-by-synchronismcheck" in the "cause" signal. See also the time diagram in figure 177.
370
Technical reference manual
Section 11
Control
1MRK505208-UUS D
SCSWI
EXE_CL
SXCBR
OR
CLOSE
SYNC_OK
START_SY
SY_INPRO
SESRSYN
CLOSECMD
Synchro
check
Synchronizing
function
ANSI09000209-1-en.vsd
ANSI09000209 V1 EN
Figure 173:
Time diagrams
The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.
The timer tSelect is used for supervising the time between the select and the execute
command signal, that is, the time the operator has to perform the command execution
after the selection of the object to operate.
select
execute command
tSelect
timer
t1
IEC05000092 V1 EN
Figure 174:
tSelect
The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback reservation
granted from all bays involved in the reservation function.
371
Technical reference manual
Section 11
Control
1MRK505208-UUS D
select
reservation request RES_RQ
reservation granted RES_GRT
command termination
tResResponse
timer
t1>tResResponse, then
1-of-n-control in 'cause'
is set
t1
en05000093.vsd
IEC05000093 V1 EN
Figure 175:
tResResponse
The timer tExecutionFB supervises the time between the execute command and the
command termination, see figure 176.
execute command
phase A open
close
phase B open
close
phase C open
close
command termination
phase A
command termination
phase B
command termination
phase C
command termination
t1
t1>tExecutionFB, then
long-operation-time in
'cause' is set
Figure 176:
tExecutionFB
The parameter tSynchrocheck is used to define the maximum allowed time between the
execute command and the input SYNC_OK to become true. If SYNC_OK=true at the
time the execute command signal is received, the timer "tSynchrocheck" will not start.
The start signal for the synchronizing is obtained if the synchronism-check conditions
are not fulfilled.
372
Technical reference manual
Section 11
Control
1MRK505208-UUS D
execute command
SYNC_OK
tSynchrocheck
t1
START_SY
SY_INPRO
tSynchronizing
t2
t2>tSynchronizing, then
blocked-by-synchronism
check in 'cause' is set
en05000095_ansi.vsd
ANSI05000095 V1 EN
Figure 177:
11.2.6.3
Function block
SCSWI
BLOCK
PSTO
L_SEL
L_OPEN
L_CLOSE
AU_OPEN
AU_CLOSE
BL_CMD
RES_GRT
RES_EXT
SY_INPRO
SYNC_OK
EN_OPEN
EN_CLOSE
XPOS1
XPOS2
XPOS3
EXE_OP
EXE_CL
SELECTED
RES_RQ
START_SY
POSITION
OPENPOS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUSE
XOUT
POS_INTR
IEC05000337-2-en.vsd
IEC05000337 V2 EN
Figure 178:
11.2.6.4
Default
Description
BLOCK
BOOLEAN
Block of function
PSTO
INTEGER
L_SEL
BOOLEAN
L_OPEN
BOOLEAN
L_CLOSE
BOOLEAN
373
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
BL_CMD
BOOLEAN
RES_GRT
BOOLEAN
RES_EXT
BOOLEAN
SY_INPRO
BOOLEAN
SYNC_OK
BOOLEAN
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN
XPOS1
GROUP
SIGNAL
XPOS2
GROUP
SIGNAL
XPOS3
GROUP
SIGNAL
Table 197:
Name
Description
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
SELECTED
BOOLEAN
RES_RQ
BOOLEAN
START_SY
BOOLEAN
POSITION
INTEGER
Position indication
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
POLEDISC
BOOLEAN
CMD_BLK
BOOLEAN
L_CAUSE
INTEGER
XOUT
BOOLEAN
POS_INTR
BOOLEAN
Section 11
Control
1MRK505208-UUS D
L_SEL, L_OPEN and L_CLOSE are used for local command sequence
connected to binary inputs. In order to have effect, the operator place
selector, PSTO, must be set to local or to remote with no priority. If the
control model used is Select before operate, Also the corresponding
enable input must be set, and no interlocking is active. The L_SEL
input must be set before L_OPEN or L_CLOSE is operated, if the
control model is Select before operate.
11.2.6.5
Table 198:
Setting parameters
SCSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CtlModel
Dir Norm
SBO Enh
SBO Enh
PosDependent
Always permitted
Not perm at 00/11
Always permitted
tSelect
0.00 - 600.00
0.01
30.00
tResResponse
0.000 - 60.000
0.001
5.000
tSynchrocheck
0.00 - 600.00
0.01
10.00
tSynchronizing
0.00 - 600.00
0.01
0.00
tExecutionFB
0.00 - 600.00
0.01
30.00
tPoleDiscord
0.000 - 60.000
0.001
2.000
11.2.7
11.2.7.1
Introduction
The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions
and to perform the control operations, that is, pass all the commands to primary
apparatuses in the form of circuit breakers via binary output boards and to supervise
the switching operation and position.
375
Section 11
Control
11.2.7.2
1MRK505208-UUS D
Principle of operation
The users of the Circuit breaker function (SXCBR) is other functions such as for
example, switch controller, protection functions, autorecloser function or an IEC 61850
client residing in another IED or the operator place. This switch function executes
commands, evaluates block conditions and evaluates different time supervision
conditions. Only if all conditions indicate a switch operation to be allowed, the
function performs the execution command. In case of erroneous conditions, the
function indicates an appropriate "cause" value.
SXCBR has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a binary
input or remotely from the operator place by configuring a signal from the Single Point
Generic Control 8 signals (SPC8GGIO) for example.
Local/Remote switch
One binary input signal LR_SWI is included in SXCBR to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
TRUE it means that change of position is allowed only from switchyard level. If the
signal is set to FALSE it means that command from IED or higher level is permitted.
When the signal is set to TRUE all commands (for change of position) from internal
IED clients are rejected, even trip commands from protection functions are rejected.
The functionality of the local/remote switch is described in figure 179.
UE
TR
From I/O
Local= Operation at
switch yard level
switchLR
FAL
SE
Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN
Figure 179:
Local/Remote switch
Blocking principles
SXCBR includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example, operators
place, protection functions, autoreclosure and so on.
The IEC 61850 communication has always priority over binary inputs,
e.g. a block command on binary inputs will not prevent commands over
IEC 61850.
376
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Substitution
The substitution part in SXCBR is used for manual set of the position for the switch.
The typical use of substitution is that an operator enters a manual value because that
the real process value is erroneous for some reason. SXCBR will then use the manually
entered value instead of the value for positions determined by the process.
It is always possible to make a substitution, independently of the
position indication and the status information of the I/O board. When
substitution is enabled, the position values are blocked for updating and
other signals related to the position are reset. The substituted values are
stored in a non-volatile memory.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 180 explains these two timers during the execute phase.
377
Technical reference manual
Section 11
Control
1MRK505208-UUS D
AdaptivePulse = TRUE
EXE_CL
Close pulse duration
OPENPOS
CLOSEPOS
tStartMove timer
t1
tStartMove
tIntermediate timer
t2
tIntermediate
en05000097.vsd
IEC05000097 V1 EN
Figure 180:
The timers tOpenPulse and tClosePulse are the length of the execute output pulses to
be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be adaptive
with the configuration parameter AdaptivePulse. Figure 181 shows the principle of the
execute output pulse. The AdaptivePulse parameter will have affect on both execute
output pulses.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN
Figure 181:
378
Technical reference manual
Section 11
Control
1MRK505208-UUS D
If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.
The execute output pulses are reset when:
the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in closed
position and a close command is executed. In these cases, with the additional condition
that the configuration parameter AdaptivePulse is true, the execute output pulse is
always activated and resets when tStartMove has elapsed. If the configuration
parameter AdaptivePulse is set to false the execution output remains active until the
pulse duration timer has elapsed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS
=1) when a command is executed the execute output pulse resets only
when timer tOpenPulse or tClosePulse has elapsed.
An example of when a primary device is open and an open command is executed is
shown in figure 182 .
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_OP
tOpenPulse
AdaptivePulse=TRUE
EXE_OP
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
Figure 182:
379
Technical reference manual
Section 11
Control
11.2.7.3
1MRK505208-UUS D
Function block
SXCBR
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
TR_OPEN
TR_CLOSE
RS_CNT
XIN
XPOS
EXE_OP
EXE_CL
SUBSTED
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
TR_POS
CNT_VAL
L_CAUSE
IEC05000338-2-en.vsd
IEC05000338 V2 EN
Figure 183:
11.2.7.4
Default
Description
BLOCK
BOOLEAN
Block of function
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
TR_OPEN
BOOLEAN
TR_CLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Table 200:
Name
Description
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
380
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
11.2.7.5
Table 201:
Type
Description
SUBSTED
BOOLEAN
OP_BLKD
BOOLEAN
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
TR_POS
INTEGER
CNT_VAL
INTEGER
L_CAUSE
INTEGER
Setting parameters
SXCBR Non group settings (basic)
Name
Values (Range)
Unit
tStartMove
0.000 - 60.000
Step
0.001
0.100
tIntermediate
0.000 - 60.000
0.001
0.150
AdaptivePulse
Not adaptive
Adaptive
Not adaptive
tOpenPulse
0.000 - 60.000
0.001
0.200
tClosePulse
0.000 - 60.000
0.001
0.200
SuppressMidPos
Disabled
Enabled
Enabled
11.2.8
11.2.8.1
Introduction
Default
Description
The purpose of Circuit switch (SXSWI) function is to provide the actual status of
positions and to perform the control operations, that is, pass all the commands to
primary apparatuses in the form of disconnectors or grounding switches via binary
output boards and to supervise the switching operation and position.
381
Technical reference manual
Section 11
Control
11.2.8.2
1MRK505208-UUS D
Principle of operation
The users of the Circuit switch (SXSWI) is other functions such as for example, switch
controller, protection functions, autorecloser function, or a 61850 client residing in
another IED or the operator place. SXSWI executes commands, evaluates block
conditions and evaluates different time supervision conditions. Only if all conditions
indicate a switch operation to be allowed, SXSWI performs the execution command. In
case of erroneous conditions, the function indicates an appropriate "cause" value.
SXSWI has an operation counter for closing and opening commands. The counter
value can be read remotely from the operator place. The value is reset from a binary
input or remotely from the operator place by configuring a signal from the Single Point
Generic Control 8 signals (SPC8GGIO) for example.
Local/Remote switch
One binary input signal LR_SWI is included in SXSWI to indicate the local/remote
switch position from switchyard provided via the I/O board. If this signal is set to
TRUE it means that change of position is allowed only from switchyard level. If the
signal is set to FALSE it means that command from IED or higher level is permitted.
When the signal is set to TRUE all commands (for change of position) from internal
IED clients are rejected, even trip commands from protection functions are rejected.
The functionality of the local/remote switch is described in figure 184.
TR
From I/O
UE
Local= Operation at
switch yard level
switchLR
FAL
SE
Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN
Figure 184:
Local/Remote switch
Blocking principles
SXSWI includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example, operators
place, protection functions, autorecloser and so on.
The blocking possibilities are:
382
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Substitution
The substitution part in SXSWI is used for manual set of the position for the switch.
The typical use of substitution is that an operator enters a manual value because the
real process value is erroneous of some reason. SXSWI will then use the manually
entered value instead of the value for positions determined by the process.
It is always possible to make a substitution, independently of the
position indication and the status information of the I/O board. When
substitution is enabled, the position values are blocked for updating and
other signals related to the position are reset. The substituted values are
stored in a non-volatile memory.
Time diagrams
There are two timers for supervising of the execute phase, tStartMove and
tIntermediate. tStartMove supervises that the primary device starts moving after the
execute output pulse is sent. tIntermediate defines the maximum allowed time for
intermediate position. Figure 185 explains these two timers during the execute phase.
383
Technical reference manual
Section 11
Control
1MRK505208-UUS D
AdaptivePulse = TRUE
EXE_CL
Close pulse duration
OPENPOS
CLOSEPOS
tStartMove timer
t1
tStartMove
tIntermediate timer
t2
tIntermediate
en05000097.vsd
IEC05000097 V1 EN
Figure 185:
The timers tOpenPulse and tClosePulse are the length of the execute output pulses to
be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be adaptive
with the configuration parameter AdaptivePulse. Figure 186 shows the principle of the
execute output pulse. The AdaptivePulse parameter will have affect on both execute
output pulses.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_CL
tClosePulse
AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN
Figure 186:
384
Technical reference manual
Section 11
Control
1MRK505208-UUS D
If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.
The execute output pulses are reset when:
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS
=1) when a command is executed the execute output pulse resets only
when timer tOpenPulse or tClosePulse has elapsed.
the new expected final position is reached and the configuration parameter
AdaptivePulse is set to true
the timer tOpenPulse or tClosePulse has elapsed
an error occurs due to the switch does not start moving, that is, tStartMove has
elapsed.
There is one exception from the first item above. If the primary device is in open
position and an open command is executed or if the primary device is in close position
and a close command is executed. In these cases, with the additional condition that the
configuration parameter AdaptivePulse is true, the execute output pulse is always
activated and resets when tStartMove has elapsed. If the configuration parameter
AdaptivePulse is set to false the execution output remains active until the pulse
duration timer has elapsed.
An example when a primary device is open and an open command is executed is
shown in figure 187.
OPENPOS
CLOSEPOS
AdaptivePulse=FALSE
EXE_OP
tOpenPulse
AdaptivePulse=TRUE
EXE_OP
tOpenPulse
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
Figure 187:
385
Technical reference manual
Section 11
Control
11.2.8.3
1MRK505208-UUS D
Function block
SXSWI
BLOCK
LR_SWI
OPEN
CLOSE
BL_OPEN
BL_CLOSE
BL_UPD
POSOPEN
POSCLOSE
RS_CNT
XIN
XPOS
EXE_OP
EXE_CL
SUBSTED
OP_BLKD
CL_BLKD
UPD_BLKD
POSITION
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
IEC05000339-2-en.vsd
IEC05000339 V2 EN
Figure 188:
11.2.8.4
Default
Description
BLOCK
BOOLEAN
Block of function
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Table 203:
Name
Description
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
SUBSTED
BOOLEAN
OP_BLKD
BOOLEAN
386
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
11.2.8.5
Table 204:
Type
Description
CL_BLKD
BOOLEAN
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
CNT_VAL
INTEGER
L_CAUSE
INTEGER
Setting parameters
SXSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
tStartMove
0.000 - 60.000
0.001
3.000
tIntermediate
0.000 - 60.000
0.001
15.000
AdaptivePulse
Not adaptive
Adaptive
Not adaptive
tOpenPulse
0.000 - 60.000
0.001
0.200
tClosePulse
0.000 - 60.000
0.001
0.200
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
Disconnector
1=LoadBreak,2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw
SuppressMidPos
Disabled
Enabled
Enabled
11.2.9
11.2.9.1
Introduction
Default
Description
387
Technical reference manual
Section 11
Control
11.2.9.2
1MRK505208-UUS D
Principle of operation
The Bay reserve (QCRSV) function handles the reservation. QCRSV function starts to
operate in two ways. It starts when there is a request for reservation of the own bay or
if there is a request for reservation from another bay. It is only possible to reserve the
function if it is not currently reserved. The signal that can reserve the own bay is the
input signal RES_RQx (x=1-8) coming from switch controller (SCWI). The signals for
request from another bay are the outputs RE_RQ_B and V_RE_RQ from function
block RESIN. These signals are included in signal EXCH_OUT from RESIN and are
connected to RES_DATA in QCRSV.
The parameters ParamRequestx (x=1-8) are chosen at reservation of the own bay only
(TRUE) or other bays (FALSE). To reserve the own bay only means that no
reservation request RES_BAYS is created.
If the reservation request comes from the own bay, the function QCRSV has to know
which apparatus the request comes from. This information is available with the input
signal RES_RQx and parameter ParamRequestx (where x=1-8 is the number of the
requesting apparatus). In order to decide if a reservation request of the current bay can
be permitted QCRSV has to know whether the own bay already is reserved by itself or
another bay. This information is available in the output signal RESERVED.
If the RESERVED output is not set, the selection is made with the output RES_GRTx
(where x=1-8 is the number of the requesting apparatus), which is connected to switch
controller SCSWI. If the bay already is reserved the command sequence will be reset
and the SCSWI will set the attribute "1-of-n-control" in the "cause" signal.
When the function QCRSV receives a request from an apparatus in the own bay that
requires other bays to be reserved as well, it checks if it already is reserved. If not, it
will send a request to the other bays that are predefined (to be reserved) and wait for
their response (acknowledge). The request of reserving other bays is done by activating
the output RES_BAYS.
When it receives acknowledge from the bays via the input RES_DATA, it sets the
output RES_GRTx (where x=1-8 is the number of the requesting apparatus). If not
acknowledgement from all bays is received within a certain time defined in SCSWI
(tResResponse), the SCSWI will reset the reservation and set the attribute "1-of-ncontrol" in the "cause" signal.
When another bay requests for reservation, the input BAY_RES in corresponding
function block RESIN is activated. The signal for reservation request is grouped into
the output signal EXCH_OUT in RESIN, which is connected to input RES_DATA in
388
Technical reference manual
Section 11
Control
1MRK505208-UUS D
QCRSV. If the bay is not reserved, the bay will be reserved and the acknowledgment
from output ACK_T_B is sent back to the requested bay. If the bay already is reserved
the reservation is kept and no acknowledgment is sent.
If only one instance of QCRSV is used for a bay that is, use of up to eight apparatuses,
the input EXCH_IN must be set to FALSE.
If there are more than eight apparatuses in the bay there has to be one additional
QCRSV. The two QCRSV functions have to communicate and this is done through the
input EXCH_IN and EXCH_OUT according to figure 189. If more then one QCRSV
are used, the execution order is very important. The execution order must be in the way
that the first QCRSV has a lower number than the next one.
389
Technical reference manual
Section 11
Control
1MRK505208-UUS D
QCRSV
EXCH_IN
RES_ GRT1
RES_RQ1 RES_ GRT2
RES_RQ2 RES_ GRT3
RES_RQ3 RES_ GRT4
RES_RQ4 RES_ GRT5
RES_RQ5 RES_ GRT6
RES_RQ6 RES_ GRT7
RES_RQ7 RES_ GRT8
RES_RQ8 RES_ BAYS
BLK_ RES
ACK_TO_B
OVERRIDE RESERVED
RES_ DATA EXCH_ OUT
QCRSV
EXCH_IN
RES_ GRT1
RES_RQ1 RES_ GRT2
RES_RQ2 RES_ GRT3
RES_RQ3 RES_ GRT4
RES_RQ4 RES_ GRT5
RES_RQ5 RES_ GRT6
RES_RQ6 RES_ GRT7
RES_RQ7 RES_ GRT8
RES_RQ8 RES_ BAYS
BLK_ RES
ACK_TO_B
OVERRIDE RESERVED
RES_ DATA EXCH_ OUT
OR
OR
OR
RES_ BAYS
ACK_TO_B
RESERVED
ANSI05000088_2_en.vsd
ANSI05000088 V2 EN
Figure 189:
11.2.9.3
Function block
QCRSV
EXCH_IN
RES_RQ1
RES_RQ2
RES_RQ3
RES_RQ4
RES_RQ5
RES_RQ6
RES_RQ7
RES_RQ8
BLK_RES
OVERRIDE
RES_DATA
RES_GRT1
RES_GRT2
RES_GRT3
RES_GRT4
RES_GRT5
RES_GRT6
RES_GRT7
RES_GRT8
RES_BAYS
ACK_TO_B
RESERVED
EXCH_OUT
IEC05000340-2-en.vsd
IEC05000340 V2 EN
Figure 190:
390
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.2.9.4
Default
Description
EXCH_IN
INTEGER
RES_RQ1
BOOLEAN
RES_RQ2
BOOLEAN
RES_RQ3
BOOLEAN
RES_RQ4
BOOLEAN
RES_RQ5
BOOLEAN
RES_RQ6
BOOLEAN
RES_RQ7
BOOLEAN
RES_RQ8
BOOLEAN
BLK_RES
BOOLEAN
OVERRIDE
BOOLEAN
RES_DATA
INTEGER
Table 206:
Name
Description
RES_GRT1
BOOLEAN
RES_GRT2
BOOLEAN
RES_GRT3
BOOLEAN
RES_GRT4
BOOLEAN
RES_GRT5
BOOLEAN
RES_GRT6
BOOLEAN
RES_GRT7
BOOLEAN
RES_GRT8
BOOLEAN
RES_BAYS
BOOLEAN
ACK_TO_B
BOOLEAN
RESERVED
BOOLEAN
EXCH_OUT
INTEGER
391
Technical reference manual
Section 11
Control
11.2.9.5
Table 207:
Name
1MRK505208-UUS D
Setting parameters
QCRSV Non group settings (basic)
Values (Range)
Unit
tCancelRes
0.000 - 60.000
Step
0.001
Default
10.000
ParamRequest1
ParamRequest2
ParamRequest3
ParamRequest4
ParamRequest5
ParamRequest6
ParamRequest7
ParamRequest8
11.2.10
11.2.10.1
Introduction
Description
The Reservation input (RESIN) function receives the reservation information from
other bays. The number of instances is the same as the number of involved bays (up to
60 instances are available).
11.2.10.2
Principle of operation
The reservation input (RESIN) function is based purely on Boolean logic conditions.
The logic diagram in figure 191 shows how the output signals are created. The inputs
of the function block are connected to a receive function block representing signals
transferred over the station bus from another bay.
392
Technical reference manual
Section 11
Control
1MRK505208-UUS D
EXCH_IN
INT
BIN
ACK_F_B
AND
FutureUse
OR
BAY_ACK
ANY_ACK
OR
VALID_TX
AND
BAY_VAL
OR
RE_RQ_B
OR
BAY_RES
AND
V _RE_RQ
OR
BIN
EXCH_OUT
INT
INT..Integer
BIN..Binary
en05000089_ansi.vsd
ANSI05000089 V1 EN
Figure 191:
Figure 192 describes the principle of the data exchange between all RESIN modules in
the current bay. There is one RESIN function block per "other bay" used in the
reservation mechanism. The output signal EXCH_OUT in the last RESIN functions are
connected to the module bay reserve (QCRSV) that handles the reservation function in
the own bay. The value to the input EXCH_IN on the first RESIN module in the chain
has the integer value 5. This is provided by the use of instance number one of the
function block RESIN, where the input EXCH_IN is set to #5, but is hidden for the user.
393
Technical reference manual
Section 11
Control
1MRK505208-UUS D
RESIN
BAY_ACK ACK_F_B
BAY_VAL ANY_ACK
BAY_RES VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
Bay 1
Bay 2
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
Bay n
RESIN
EXCH_IN ACK_F_B
BAY_ACK ANY_ACK
BAY_VAL VALID_TX
BAY_RES RE_RQ_B
V_RE_RQ
EXCH_OUT
QCRSV
RES_DATA
en05000090.vsd
IEC05000090 V2 EN
Figure 192:
11.2.10.3
Function block
RESIN1
BAY_ACK
BAY_VAL
BAY_RES
ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC05000341-2-en.vsd
IEC05000341 V2 EN
Figure 193:
RESIN2
EXCH_IN
BAY_ACK
BAY_VAL
BAY_RES
ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V_RE_RQ
EXCH_OUT
IEC09000807_1_en.vsd
IEC09000807 V1 EN
Figure 194:
394
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.2.10.4
Default
Description
BAY_ACK
BOOLEAN
BAY_VAL
BOOLEAN
BAY_RES
BOOLEAN
Table 209:
Name
Description
ACK_F_B
BOOLEAN
ANY_ACK
BOOLEAN
VALID_TX
BOOLEAN
RE_RQ_B
BOOLEAN
V_RE_RQ
BOOLEAN
EXCH_OUT
INTEGER
Table 210:
Name
Default
Description
EXCH_IN
INTEGER
BAY_ACK
BOOLEAN
BAY_VAL
BOOLEAN
BAY_RES
BOOLEAN
395
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 211:
Name
11.2.10.5
Table 212:
Name
FutureUse
Table 213:
Name
FutureUse
Type
Description
ACK_F_B
BOOLEAN
ANY_ACK
BOOLEAN
VALID_TX
BOOLEAN
RE_RQ_B
BOOLEAN
V_RE_RQ
BOOLEAN
EXCH_OUT
INTEGER
Setting parameters
RESIN1 Non group settings (basic)
Values (Range)
Bay in use
Bay future use
Unit
-
Step
-
Default
Bay in use
Description
The bay for this ResIn block is for future use
Unit
-
Step
-
11.3
Interlocking (3)
11.3.1
Introduction
Default
Bay in use
Description
The bay for this ResIn block is for future use
Section 11
Control
1MRK505208-UUS D
11.3.2
Principle of operation
The interlocking function consists of software modules located in each control IED.
The function is distributed and not dependent on any central function. Communication
between modules in different bays is performed via the station bus.
The reservation function (see section "Introduction") is used to ensure that HV
apparatuses that might affect the interlock are blocked during the time gap, which
arises between position updates. This can be done by means of the communication
system, reserving all HV apparatuses that might influence the interlocking condition of
the intended operation. The reservation is maintained until the operation is performed.
After the selection and reservation of an apparatus, the function has complete data on
the status of all apparatuses in the switchyard that are affected by the selection. Other
operators cannot interfere with the reserved apparatus or the status of switching devices
that may affect it.
The open or closed positions of the HV apparatuses are inputs to software modules
distributed in the control IEDs. Each module contains the interlocking logic for a bay.
The interlocking logic in a module is different, depending on the bay function and the
switchyard arrangements, that is, double-breaker or breaker-and-a-half bays have
different modules. Specific interlocking conditions and connections between standard
interlocking modules are performed with an engineering tool. Bay-level interlocking
signals can include the following kind of information:
397
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Interlocking
modules in
other bays
Interlocking
module
Apparatus control
modules
SCILO
SCSWI
SXSWI
Apparatus control
modules
SCILO
SCSWI
SXCBR
152
Apparatus control
modules
SCILO
SCSWI
SXSWI
en04000526_ansi.vsd
ANSI04000526 V1 EN
Figure 195:
Bays communicate via the station bus and can convey information regarding the
following:
Ungrounded busbars
Busbars connected together
Other bays connected to a busbar
Received data from other bays is valid
398
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Station bus
Bay 1
Bay n
Bus coupler
...
..
WA1 ungrounded
WA1 ungrounded
WA1 and WA2 interconn
WA1
WA2
189
289
189
289
289
189
189G
289G
152
152
152
989
989
en05000494_ansi.vsd
ANSI05000494 V1 EN
Figure 196:
When invalid data such as intermediate position, loss of a control IED, or input board
error are used as conditions for the interlocking condition in a bay, a release for
execution of the function will not be given.
On the local HMI an override function exists, which can be used to bypass the
interlocking function in cases where not all the data required for the condition is valid.
For all interlocking modules these general rules apply:
399
Technical reference manual
Section 11
Control
1MRK505208-UUS D
The interlocking conditions can be altered, to meet the customer specific requirements,
by adding configurable logic by means of the graphical configuration tool PCM600.
The inputs Qx_EXy on the interlocking modules are used to add these specific conditions.
The input signals EXDU_xx shall be set to true if there is no transmission error at the
transfer of information from other bays. Required signals with designations ending in
TR are intended for transfer to other bays.
11.3.3
11.3.3.1
Introduction
The Logical node for interlocking SCILO(3) function is used to enable a switching
operation if the interlocking conditions permit. SCILO (3) function itself does not
provide any interlocking functionality. The interlocking conditions are generated in
separate function blocks containing the interlocking logic.
400
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.3.2
Logic diagram
The function contains logic to enable the open and close commands respectively if the
interlocking conditions are fulfilled. That means also, if the switch has a defined end
position for example, open, then the appropriate enable signal (in this case EN_OPEN)
is false. The enable signals EN_OPEN and EN_CLOSE can be true at the same time
only in the intermediate and bad position state and if they are enabled by the
interlocking function. The position inputs come from the logical nodes Circuit breaker/
Circuit switch (SXCBR/SXSWI) and the enable signals come from the interlocking
logic. The outputs are connected to the logical node Switch controller (SCSWI). One
instance per switching device is needed.
SCILO
POSOPEN
POSCLOSE
XOR
NOT
EN_OPEN
AND
OR
AND
OPEN_EN
CLOSE_EN
EN_CLOSE
AND
OR
AND
en04000525_ansi.vsd
ANSI04000525 V1 EN
Figure 197:
11.3.3.3
Function block
SCILO (3)
POSOPEN
EN_OPEN
POSCLOSE
EN_CLOSE
OPEN_EN
CLOSE_EN
ANSI05000359-1-en.vsd
ANSI05000359 V1 EN
Figure 198:
11.3.3.4
Default
Description
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
OPEN_EN
BOOLEAN
CLOSE_EN
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Table 215:
Name
Type
Description
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN
11.3.4
11.3.4.1
Introduction
The interlocking for busbar grounding switch (BB_ES, 3) function is used for one
busbar grounding switch on any busbar parts according to figure 199.
89G
en04000504.vsd
ANSI04000504 V1 EN
Figure 199:
11.3.4.2
Function block
BB_ES (3)
89G_OP
89GREL
89G_CL
89GITL
BB_DC_OP
BBGSOPTR
VP_BB_DC
BBGSCLTR
EXDU_BB
ANSI05000347-2-en.vsd
ANSI05000347 V2 EN
Figure 200:
402
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.4.3
Logic diagram
BB_ES
VP_BB_DC
BB_DC_OP
EXDU_BB
AND
NOT
89G_OP
89G_CL
89GREL
89GITL
BBGSOPTR
BBGSCLTR
en04000546_ansi.vsd
ANSI04000546 V1 EN
11.3.4.4
Default
Description
QC_OP
BOOLEAN
QC_CL
BOOLEAN
BB_DC_OP
BOOLEAN
VP_BB_DC
BOOLEAN
EXDU_BB
BOOLEAN
Table 217:
Name
Description
QCREL
BOOLEAN
QCITL
BOOLEAN
BBESOPTR
BOOLEAN
BBESCLTR
BOOLEAN
11.3.5
11.3.5.1
Introduction
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bussection circuit breaker between section 1 and 2 according to figure 201. The function
can be used for different busbars, which includes a bus-section circuit breaker.
403
Technical reference manual
Section 11
Control
1MRK505208-UUS D
WA1 (A1)
WA2 (A2)
289
189
189G
289G
152
489G
389G
A1A2_BS
en04000516_ansi.vsd
ANSI04000516 V1 EN
Figure 201:
11.3.5.2
Function block
A1A2_BS (3)
152_OP
152OPREL
152_CL
152OPITL
189_OP
152CLREL
189_CL
152CLITL
289_OP
189REL
289_CL
189ITL
389G_OP
289REL
389G_CL
289ITL
489G_OP
389GREL
489G_CL
389GITL
S189G_OP
489GREL
S189G_CL
489GITL
S289G_OP
S1S2OPTR
S289G_CL
S1S2CLTR
BBTR_OP
189OPTR
VP_BBTR
189CLTR
EXDU_12
289OPTR
EXDU_89G
289CLTR
152O_EX1
VPS1S2TR
152O_EX2
VP189TR
152O_EX3
VP289TR
189_EX1
189_EX2
289_EX1
289_EX2
ANSI05000348-2-en.vsd
ANSI05000348 V2 EN
Figure 202:
404
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.5.3
Logic diagram
152_OP
152_CL
189_OP
189_CL
289_OP
289_CL
389G_OP
389G_CL
489G_OP
489G_CL
S1189G_OP
S1189G_CL
S2289G_OP
S2289G_CL
VP189
189_OP
152O_EX1
VP289
289_OP
152O_EX2
VP_BBTR
BBTR_OP
EXDU_12
152O_EX3
VP189
VP289
VP152
VP389G
VP489G
VPS1189G
152_OP
389G_OP
489G_OP
S1189G_OP
EXDU_89G
189_EX1
VP389G
VPS1189G
389G_CL
S1189G_CL
EXDU_89G
189_EX2
A1A2_BS
XOR
VP152
XOR
VP189
XOR
VP289
XOR
VP389G
XOR
VP489G
XOR
VPS1189G
XOR
VPS2289G
AND
OR
NOT
152OPREL
152OPITL
AND
AND
AND
AND
NOT
OR
NOT
152CLREL
152CLITL
189REL
189ITL
AND
en04000542_ansi.vsd
ANSI04000542 V1 EN
405
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP389G
VP489G
VPS2289G
152_OP
389G_OP
489G_OP
S2289G_OP
EXDU_89G
289_EX1
VP489G
VPS2289G
489G_CL
S2289G_CL
EXDU_89G
289_EX2
VP189
VP289
189_OP
289_OP
AND
289REL
289ITL
OR
NOT
AND
AND
389GREL
389GITL
489GREL
489GITL
NOT
NOT
189_OP
189_CL
VP189
189OPTR
189CLTR
VP189TR
289_OP
289_CL
VP289
289OPTR
289CLTR
VP289TR
189_OP
289_OP
152_OP
VP189
VP289
VP152
OR
NOT
S1S2OPTR
S1S2CLTR
VPS1S2TR
AND
en04000543_ansi.vsd
ANSI04000543 V1 EN
11.3.5.4
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QC4_OP
BOOLEAN
QC4_CL
BOOLEAN
S1QC1_OP
BOOLEAN
S1QC1_CL
BOOLEAN
S2QC2_OP
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
S2QC2_CL
BOOLEAN
BBTR_OP
BOOLEAN
VP_BBTR
BOOLEAN
EXDU_12
BOOLEAN
EXDU_ES
BOOLEAN
QA1O_EX1
BOOLEAN
QA1O_EX2
BOOLEAN
QA1O_EX3
BOOLEAN
QB1_EX1
BOOLEAN
QB1_EX2
BOOLEAN
QB2_EX1
BOOLEAN
QB2_EX2
BOOLEAN
Table 219:
Name
Description
QA1OPREL
BOOLEAN
QA1OPITL
BOOLEAN
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QC3REL
BOOLEAN
QC3ITL
BOOLEAN
QC4REL
BOOLEAN
QC4ITL
BOOLEAN
S1S2OPTR
BOOLEAN
S1S2CLTR
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Description
VPS1S2TR
BOOLEAN
VPQB1TR
BOOLEAN
VPQB2TR
BOOLEAN
11.3.6
11.3.6.1
Introduction
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one
bus-section disconnector between section 1 and 2 according to figure 203. A1A2_DC (3)
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)
WA2 (A2)
52
289G
189G
A1A2_DC
en04000492_ansi.vsd
ANSI04000492 V1 EN
Figure 203:
11.3.6.2
Function block
A1A2_DC (3)
089_OP
089OPREL
089_CL
089OPITL
S189G_OP
089CLREL
S189G_CL
089CLITL
S289G_OP
DCOPTR
S289G_CL
DCCLTR
S1DC_OP
VPDCTR
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_89G
EXDU_BB
089C_EX1
089C_EX2
089O_EX1
089O_EX2
089O_EX3
ANSI05000349-2-en.vsd
ANSI05000349 V2 EN
Figure 204:
408
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.6.3
Logic diagram
A1A2_DC
89_OP
89_CL
S1189G_OP
S1189G_CL
S2289G_OP
S2289G_CL
VPS1189G
VPS2289G
VPS1_DC
S1189G_OP
S2289G_OP
S1DC_OP
EXDU_89G
XOR
VPQB
VPDCTR
DCOPTR
DCCLTR
VPS1189G
XOR
VPS2289G
XOR
AND
OR
NOT
89OPREL
89OPITL
EXDU_BB
QBOP_EX1
VPS1189
VPS2289G
VPS2_DC
S1189G_OP
S2289G_OP
S2DC_OP
EXDU_89G
AND
EXDU_BB
QBOP_EX2
VPS1189G
VPS2289G
S1189G_CL
S2289G_CL
EXDU_89G
QBOP_EX3
AND
en04000544_ansi.vsd
ANSI04000544 V1 EN
IEC04000545 V1 EN
409
Technical reference manual
Section 11
Control
11.3.6.4
1MRK505208-UUS D
Type
Default
Description
QB_OP
BOOLEAN
QB_CL
BOOLEAN
S1QC1_OP
BOOLEAN
S1QC1_CL
BOOLEAN
S2QC2_OP
BOOLEAN
S2QC2_CL
BOOLEAN
S1DC_OP
BOOLEAN
S2DC_OP
BOOLEAN
VPS1_DC
BOOLEAN
VPS2_DC
BOOLEAN
EXDU_ES
BOOLEAN
EXDU_BB
BOOLEAN
QBCL_EX1
BOOLEAN
QBCL_EX2
BOOLEAN
QBOP_EX1
BOOLEAN
QBOP_EX2
BOOLEAN
QBOP_EX3
BOOLEAN
Table 221:
Name
11.3.7
Description
QBOPREL
BOOLEAN
QBOPITL
BOOLEAN
QBCLREL
BOOLEAN
QBCLITL
BOOLEAN
DCOPTR
BOOLEAN
DCCLTR
BOOLEAN
VPDCTR
BOOLEAN
410
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.7.1
Introduction
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure 205. The function
can also be used for a single busbar arrangement with transfer busbar or double busbar
arrangement without transfer busbar.
WA1 (A)
WA2 (B)
WA7 (C)
189
289
189G
2089
789
152
289G
en04000514_ansi.vsd
ANSI04000514 V1 EN
Figure 205:
411
Technical reference manual
Section 11
Control
11.3.7.2
1MRK505208-UUS D
Function block
ABC_BC (3)
152_OP
152OPREL
152_CL
152OPITL
189_OP
152CLREL
189_CL
152CLITL
289_OP
189REL
289_CL
189ITL
789_OP
289REL
789_CL
289ITL
2089_OP
789REL
2089_CL
789ITL
189G_OP
2089REL
189G_CL
2089ITL
289G_OP
189GREL
289G_CL
189GITL
1189G_OP
289GREL
1189G_CL
289GITL
2189G_OP
189OPTR
2189G_CL
189CLTR
7189G_OP
22089OTR
7189G_CL
22089CTR
BBTR_OP
789OPTR
BC_12_CL
789CLTR
VP_BBTR
1289OPTR
VP_BC_12
1289CLTR
EXDU_89G
BC12OPTR
EXDU_12
BC12CLTR
EXDU_BC
BC17OPTR
152O_EX1
BC17CLTR
152O_EX2
BC27OPTR
152O_EX3
BC27CLTR
189_EX1
VP189TR
189_EX2
V22089TR
189_EX3
VP789TR
289_EX1
VP1289TR
289_EX2
VPBC12TR
289_EX3
VPBC17TR
2089_EX1
VPBC27TR
2089_EX2
789_EX1
789_EX2
ANSI05000350-2-en.vsd
ANSI05000350 V2 EN
Figure 206:
412
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.7.3
Logic diagram
152_OP
152_CL
189_OP
189_CL
2089_OP
2089_CL
789_OP
789_CL
289_OP
289_CL
189G_OP
189G_CL
289G_OP
289G_CL
1189G_OP
1189G_CL
2189G_OP
2189G_CL
7189G_OP
7189G_CL
VP189
189_OP
152O_EX1
VP2089
2089_OP
152O_EX2
VP_BBTR
BBTR_OP
EXDU_12
ABC_BC
VP152
XOR
XOR
VP189
XOR
VP2089
XOR
VP789
XOR
VP289
XOR
VP189G
XOR
VP289G
XOR
VP1189G
XOR
VP2189G
XOR
VP7189G
AND
152OPREL
152OPITL
OR
NOT
AND
AND
152O_EX3
VP189
VP289
VP789
VP2089
AND
NOT
152CLREL
152CLITL
en04000533_ansi.vsd
ANSI04000533 V1 EN
VP152
VP289
VP189G
VP289G
VP1189G
152_OP
289_OP
189G_OP
289G_OP
1189G_OP
EXDU_89G
189_EX1
VP289
VP_BC_12
289_CL
BC_12_CL
EXDU_BC
189_EX2
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
189_EX3
AND
OR
NOT
189REL
189ITL
AND
AND
en04000534_ansi.vsd
ANSI04000534 V1 EN
413
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP189
VP189G
VP289G
VP2189G
152_OP
189_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
289_EX1
VP189
VP_BC_12
189_CL
BC_12_CL
EXDU_BC
289_EX2
VP189G
VP2189G
189G_CL
2189G_CL
EXDU_89G
289_EX3
AND
OR
NOT
289REL
289ITL
AND
AND
en04000535_ansi.vsd
ANSI04000535 V1 EN
VP152
VP2089
VP189G
VP289G
VP7189G
152_OP
2089_OP
189G_OP
289G_OP
7189G_OP
EXDU_89G
789_EX1
VP289G
VP7189G
289G_CL
7189G_CL
EXDU_89G
789_EX2
VP152
VP789
VP189G
VP289G
VP2189G
152_OP
789_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
2089_EX1
VP289G
VP2189G
289G_CL
2189G_CL
EXDU_89G
2089_EX2
AND
789REL
OR
NOT
789ITL
AND
AND
2089REL
OR
NOT
2089ITL
AND
en04000536_ansi.vsd
ANSI04000536 V1 EN
414
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP189
VP2089
VP789
VP289
189_OP
2089_OP
789_OP
289_OP
189_OP
189_CL
VP189
2089_OP
289_OP
VP2089
VP289
789_OP
789_CL
VP789
189_OP
289_OP
VP189
VP289
152_OP
189_OP
2089_OP
VP152
VP189
VP2089
152_OP
189_OP
789_OP
VP152
VP189
VP789
152_OP
289_OP
789_OP
VP152
VP289
VP789
AND
189GREL
189GITL
289GREL
289GITL
NOT
NOT
AND
NOT
AND
OR
NOT
AND
OR
NOT
189OPTR
189CLTR
VP189TR
22089OTR
22089CTR
V22089TR
789OPTR
789CLTR
VP789TR
1289OPTR
1289CLTR
VP1289TR
BC12OPTR
BC12CLTR
VPBC12TR
AND
OR
NOT
BC17OPTR
BC17CLTR
VPBC17TR
AND
OR
NOT
BC27OPTR
BC27CLTR
VPBC27TR
AND
en04000537_ansi.vsd
ANSI04000537 V1 EN
11.3.7.4
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QB7_OP
BOOLEAN
QB7_CL
BOOLEAN
QB20_OP
BOOLEAN
QB20_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QC11_OP
BOOLEAN
QC11_CL
BOOLEAN
QC21_OP
BOOLEAN
QC21_CL
BOOLEAN
QC71_OP
BOOLEAN
QC71_CL
BOOLEAN
BBTR_OP
BOOLEAN
BC_12_CL
BOOLEAN
VP_BBTR
BOOLEAN
VP_BC_12
BOOLEAN
EXDU_ES
BOOLEAN
EXDU_12
BOOLEAN
EXDU_BC
BOOLEAN
QA1O_EX1
BOOLEAN
QA1O_EX2
BOOLEAN
QA1O_EX3
BOOLEAN
QB1_EX1
BOOLEAN
QB1_EX2
BOOLEAN
QB1_EX3
BOOLEAN
QB2_EX1
BOOLEAN
QB2_EX2
BOOLEAN
QB2_EX3
BOOLEAN
QB20_EX1
BOOLEAN
QB20_EX2
BOOLEAN
QB7_EX1
BOOLEAN
QB7_EX2
BOOLEAN
416
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 223:
Name
Description
QA1OPREL
BOOLEAN
QA1OPITL
BOOLEAN
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QB7REL
BOOLEAN
QB7ITL
BOOLEAN
QB20REL
BOOLEAN
QB20ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
QB220OTR
BOOLEAN
QB220CTR
BOOLEAN
QB7OPTR
BOOLEAN
QB7CLTR
BOOLEAN
QB12OPTR
BOOLEAN
QB12CLTR
BOOLEAN
BC12OPTR
BOOLEAN
BC12CLTR
BOOLEAN
BC17OPTR
BOOLEAN
BC17CLTR
BOOLEAN
BC27OPTR
BOOLEAN
BC27CLTR
BOOLEAN
VPQB1TR
BOOLEAN
417
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Type
Description
VQB220TR
BOOLEAN
VPQB7TR
BOOLEAN
VPQB12TR
BOOLEAN
VPBC12TR
BOOLEAN
VPBC17TR
BOOLEAN
VPBC27TR
BOOLEAN
11.3.8
11.3.8.1
Introduction
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half
diameter according to figure 207.
418
Technical reference manual
Section 11
Control
1MRK505208-UUS D
WA1 (A)
WA2 (B)
189
289
189G
189G
152
152
289G
289G
689
689
389G
BH_LINE_A
389G
6189
152
BH_LINE_B
6289
989
989
189G
289G
989G
989G
BH_CONN
en04000513_ansi.vsd
ANSI04000513 V1 EN
Figure 207:
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and
BH_LINE_B (3) are the connections from a line to a busbar. BH_CONN (3) is the
connection between the two lines of the diameter in the breaker-and-a-half switchyard
layout.
419
Technical reference manual
Section 11
Control
11.3.8.2
1MRK505208-UUS D
Function blocks
BH_LINE_A (3)
152_OP
152CLREL
152_CL
152CLITL
689_OP
689REL
689_CL
689ITL
189_OP
189REL
189_CL
189ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389G_OP
389GREL
389G_CL
389GITL
989_OP
989REL
989_CL
989ITL
989G_OP
989GREL
989G_CL
989GITL
C152_OP
189OPTR
C152_CL
189CLTR
C6189_OP
VP189TR
C6189_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
1189G_OP
1189G_CL
VOLT_OFF
VOLT_ON
EXDU_89G
689_EX1
689_EX2
189_EX1
189_EX2
989_EX1
989_EX2
989_EX3
989_EX4
989_EX5
989_EX6
989_EX7
ANSI05000352-2-en.vsd
ANSI05000352 V2 EN
Figure 208:
420
Technical reference manual
Section 11
Control
1MRK505208-UUS D
BH_LINE_B (3)
152_OP
152CLREL
152_CL
152CLITL
689_OP
689REL
689_CL
689ITL
289_OP
289REL
289_CL
289ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389G_OP
389GREL
389G_CL
389GITL
989_OP
989REL
989_CL
989ITL
989G_OP
989GREL
989G_CL
989GITL
C152_OP
289OPTR
C152_CL
289CLTR
C6289_OP
VP289TR
C6289_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
2189G_OP
2189G_CL
VOLT_OFF
VOLT_ON
EXDU_89G
689_EX1
689_EX2
289_EX1
289_EX2
989_EX1
989_EX2
989_EX3
989_EX4
989_EX5
989_EX6
989_EX7
ANSI05000353-2-en.vsd
ANSI05000353 V2 EN
Figure 209:
BH_CONN (3)
152_OP
152CLREL
152_CL
152CLITL
6189_OP
6189REL
6189_CL
6189ITL
6289_OP
6289REL
6289_CL
6289ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
1389G_OP
1389G_CL
2389G_OP
2389G_CL
6189_EX1
6189_EX2
6289_EX1
6289_EX2
ANSI05000351-2-en.vsd
ANSI05000351 V2 EN
Figure 210:
Section 11
Control
11.3.8.3
1MRK505208-UUS D
Logic diagrams
152_OP
152_CL
6189_OP
6189_CL
6289_OP
6289_CL
189G_OP
189G_CL
289G_OP
289G_CL
1389G_OP
1389G_CL
2389G_OP
2389G_CL
VP6189
VP6289
VP152
VP189G
VP289G
VP1389G
152_OP
189G_OP
289G_OP
1389G_OP
6189_EX1
VP189G
VP1389G
189G_CL
1389G_CL
6189_EX2
VP152
VP189G
VP289G
VP2389G
152_OP
189G_OP
289G_OP
2389G_OP
6289_EX1
VP289G
VP2389G
289G_CL
2389G_CL
6289_EX2
VP6189
VP6289
6189_OP
6289_OP
BH_CONN
XOR
VP152
XOR
VP6189
XOR
VP6289
XOR
VP189G
XOR
VP289G
XOR
VP1389G
VP2389G
152CLREL
152CLITL
NOT
XOR
AND
AND
OR
NOT
6189REL
61891ITL
AND
AND
OR
NOT
6289REL
6289ITL
AND
AND
NOT
NOT
189GREL
189GITL
289GREL
289GITL
en04000560_ansi.vsd
ANSI04000560 V1 EN
422
Technical reference manual
Section 11
Control
1MRK505208-UUS D
152_OP
152_CL
189_OP
189_CL
689_OP
689_CL
989G_OP
989G_CL
989_OP
989_CL
189G_OP
189G_CL
289G_OP
289G_CL
389G_OP
389G_CL
C152_OP
C152_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
C6189_OP
C6189_CL
1189G_OP
1189G_CL
VOLT_OFF
VOLT_ON
VP189
VP689
VP989
VP152
VP189G
VP289G
VP389G
152_OP
189G_OP
289G_OP
389G_OP
689_EX1
VP289G
VP389G
289G_CL
389G_CL
689_EX2
BH_LINE_A
XOR
VP152
XOR
VP189
XOR
VP689
XOR
VP989G
XOR
VP989
XOR
VP189G
XOR
VP289G
XOR
VP389G
XOR
VPC152
XOR
VPC189G
XOR
VPC289G
XOR
VPC6189
XOR
VP1189G
XOR
AND
AND
NOT
OR
NOT
VPVOLT
152CLREL
152CLITL
689REL
689ITL
AND
en04000554_ansi.vsd
ANSI04000554 V1 EN
423
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP189G
VP289G
VP1189G
152_OP
189G_OP
289G_OP
1189G_OP
EXDU_89G
189_EX1
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
189_EX2
VP189
VP689
189_OP
689_OP
VP689
VP989
VPC6189
689_OP
989_OP
C6189_OP
VP152
VP689
VP989G
VP189G
VP289G
VP389G
VPC152
VPC6189
VPC189G
VPC289G
989_EX1
689_OP
989_EX2
152_OP
189G_OP
289G_OP
989_EX3
AND
189REL
189ITL
OR
NOT
AND
AND
189GREL
189GITL
289GREL
289GITL
NOT
NOT
389GREL
389GITL
AND
NOT
AND
OR
NOT
989REL
989ITL
OR
AND
en04000555_ansi.vsd
ANSI04000555 V1 EN
C6189_OP
989_EX4
C152_OP
C189G_OP
C289G_OP
989_EX5
989G_OP
389G_OP
989_EX6
VP989G
VP389G
989G_CL
389G_CL
989_EX7
VP989
VPVOLT
989_OP
VOLT_OFF
189_OP
189_CL
VP189
OR
AND
OR
AND
AND
AND
NOT
989GREL
989GITL
189OPTR
189CLTR
VP189TR
en04000556_ansi.vsd
ANSI04000556 V1 EN
424
Technical reference manual
Section 11
Control
1MRK505208-UUS D
152_OP
152_CL
289_OP
289_CL
689_OP
689_CL
989G_OP
989G_CL
989_OP
989_CL
189G_OP
189G_CL
289G_OP
289G_CL
389G_OP
389G_CL
C152_OP
C152_CL
C189G_OP
C189G_CL
C289G_OP
C289G_CL
C6289_OP
C6289_CL
2189G_OP
2189G_CL
VOLT_OFF
VOLT_ON
VP289
VP689
VP989
VP152
VP189G
VP289G
VP389G
152_OP
189G_OP
289G_OP
389G_OP
689_EX1
VP289G
VP389G
289G_CL
389G_CL
689_EX2
BH_LINE_B
XOR
VP152
XOR
VP289
XOR
VP689
XOR
VP989G
XOR
VP989
XOR
VP189G
XOR
VP289G
XOR
VP389G
XOR
VPC152
XOR
VPC189G
XOR
VPC289G
XOR
VPC6289
XOR
VP2189G
XOR
VPVOLT
152CLREL
152CLITL
AND
AND
NOT
OR
NOT
689REL
689ITL
AND
en04000557_ansi.vsd
ANSI04000557 V1 EN
425
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP189G
VP289G
VP2189G
152_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
289_EX1
VP189G
VP2189G
189G_CL
2189G_CL
EXDU_89G
289_EX2
VP289
VP689
289_OP
689_OP
VP689
VP989
VPC6289
689_OP
989_OP
C6289_OP
VP152
VP689
VP989G
VP189G
VP289G
VP389G
VPC152
VPC6289
VPC189G
VPC289G
989_EX1
689_OP
989_EX2
152_OP
189G_OP
289G_OP
989_EX3
289REL
OR
AND
289ITL
NOT
AND
AND
189GREL
189GITL
289GREL
289GITL
NOT
NOT
389GREL
389GITL
AND
NOT
989REL
AND
OR
NOT
989ITL
OR
AND
en04000558_ansi.vsd
ANSI04000558 V1 EN
C6289_OP
989_EX4
C152_OP
C189G_OP
C289G_OP
989_EX5
989G_OP
389G_OP
989_EX6
VP989G
VP389G
989G_CL
389G_CL
989_EX7
VP989
VPVOLT
989_OP
VOLT_OFF
289_OP
289_CL
VP289
OR
AND
OR
AND
AND
AND
NOT
989GREL
989GITL
289OPTR
289CLTR
VP289TR
en04000559_ansi.vsd
ANSI04000559 V1 EN
426
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.8.4
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB6_OP
BOOLEAN
QB6_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QB9_OP
BOOLEAN
QB9_CL
BOOLEAN
QC9_OP
BOOLEAN
QC9_CL
BOOLEAN
CQA1_OP
BOOLEAN
CQA1_CL
BOOLEAN
CQB61_OP
BOOLEAN
CQB61_CL
BOOLEAN
CQC1_OP
BOOLEAN
CQC1_CL
BOOLEAN
CQC2_OP
BOOLEAN
CQC2_CL
BOOLEAN
QC11_OP
BOOLEAN
QC11_CL
BOOLEAN
VOLT_OFF
BOOLEAN
VOLT_ON
BOOLEAN
EXDU_ES
BOOLEAN
QB6_EX1
BOOLEAN
QB6_EX2
BOOLEAN
QB1_EX1
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
QB1_EX2
BOOLEAN
QB9_EX1
BOOLEAN
QB9_EX2
BOOLEAN
QB9_EX3
BOOLEAN
QB9_EX4
BOOLEAN
QB9_EX5
BOOLEAN
QB9_EX6
BOOLEAN
QB9_EX7
BOOLEAN
Table 225:
Name
Description
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB6REL
BOOLEAN
QB6ITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QC3REL
BOOLEAN
QC3ITL
BOOLEAN
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
VPQB1TR
BOOLEAN
428
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 226:
Name
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB6_OP
BOOLEAN
QB6_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QB9_OP
BOOLEAN
QB9_CL
BOOLEAN
QC9_OP
BOOLEAN
QC9_CL
BOOLEAN
CQA1_OP
BOOLEAN
CQA1_CL
BOOLEAN
CQB62_OP
BOOLEAN
CQB62_CL
BOOLEAN
CQC1_OP
BOOLEAN
CQC1_CL
BOOLEAN
CQC2_OP
BOOLEAN
CQC2_CL
BOOLEAN
QC21_OP
BOOLEAN
QC21_CL
BOOLEAN
VOLT_OFF
BOOLEAN
VOLT_ON
BOOLEAN
EXDU_ES
BOOLEAN
QB6_EX1
BOOLEAN
QB6_EX2
BOOLEAN
QB2_EX1
BOOLEAN
QB2_EX2
BOOLEAN
429
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
QB9_EX1
BOOLEAN
QB9_EX2
BOOLEAN
QB9_EX3
BOOLEAN
QB9_EX4
BOOLEAN
QB9_EX5
BOOLEAN
QB9_EX6
BOOLEAN
QB9_EX7
BOOLEAN
Table 227:
Name
Description
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB6REL
BOOLEAN
QB6ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QC3REL
BOOLEAN
QC3ITL
BOOLEAN
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
VPQB2TR
BOOLEAN
Table 228:
Name
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB61_OP
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Default
Description
BOOLEAN
QB62_OP
BOOLEAN
QB62_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
1QC3_OP
BOOLEAN
1QC3_CL
BOOLEAN
2QC3_OP
BOOLEAN
2QC3_CL
BOOLEAN
QB61_EX1
BOOLEAN
QB61_EX2
BOOLEAN
QB62_EX1
BOOLEAN
QB62_EX2
BOOLEAN
Table 229:
Name
11.3.9
Type
QB61_CL
Description
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB61REL
BOOLEAN
QB61ITL
BOOLEAN
QB62REL
BOOLEAN
QB62ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
431
Technical reference manual
Section 11
Control
11.3.9.1
1MRK505208-UUS D
Introduction
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A
(3), DB_BUS_B (3) and DB_LINE (3) functions are used for a line connected to a
double busbar arrangement according to figure 211.
WA1 (A)
WA2 (B)
189
DB_BUS_A
189G
289
489G
DB_BUS_B
252
152
589G
289G
6189
6289
389G
DB_LINE
989
989G
en04000518_ansi.vsd
ANSI04000518 V1 EN
Figure 211:
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE (3) is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A (3) and DB_BUS_B (3) are the connections
from the line to the busbars.
432
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.9.2
Function block
DB_BUS_A (3)
152_OP
152CLREL
152_CL
152CLITL
189_OP
6189REL
189_CL
6189ITL
6189_OP
189REL
6189_CL
189ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389G_OP
189OPTR
389G_CL
189CLTR
1189G_OP
VP189TR
1189G_CL
EXDU_89G
6189_EX1
6189_EX2
189_EX1
189_EX2
ANSI05000354-2-en.vsd
ANSI05000354 V2 EN
Figure 212:
DB_LINE (3)
152_OP
152_CL
252_OP
252_CL
6189_OP
6189_CL
189G_OP
189G_CL
289G_OP
289G_CL
6289_OP
6289_CL
489G_OP
489G_CL
589G_OP
589G_CL
989_OP
989_CL
389G_OP
389G_CL
989G_OP
989G_CL
VOLT_OFF
VOLT_ON
989_EX1
989_EX2
989_EX3
989_EX4
989_EX5
989REL
989ITL
389GREL
389GITL
989GREL
989GITL
ANSI05000356-2-en.vsd
ANSI05000356 V2 EN
Figure 213:
433
Technical reference manual
Section 11
Control
1MRK505208-UUS D
DB_BUS_B (3)
252_OP
252CLREL
252_CL
252CLITL
289_OP
6289REL
289_CL
6289ITL
6289_OP
289REL
6289_CL
289ITL
489G_OP
489GREL
489G_CL
489GITL
589G_OP
589GREL
589G_CL
589GITL
389G_OP
289OPTR
389G_CL
289CLTR
2189G_OP
VP289TR
2189G_CL
EXDU_89G
6289_EX1
6289_EX2
289_EX1
289_EX2
ANSI05000355-2-en.vsd
ANSI05000355 V2 EN
Figure 214:
434
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.9.3
Logic diagrams
152_OP
152_CL
6189_OP
6189_CL
189_OP
189_CL
189G_OP
189G_CL
289G_OP
289G_CL
389G_OP
389G_CL
1189G_OP
1189G_CL
VP6189
VP189
VP152
VP189G
VP289G
VP389G
152_OP
189G_OP
289G_OP
389G_OP
6189_EX1
VP289G
VP389G
289G_CL
389G_CL
6189_EX2
VP152
VP189G
VP289G
VP1189G
152_OP
189G_OP
289G_OP
1189G_OP
EXDU_89G
189_EX1
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
189_EX2
DB_BUS_A
VP152
XOR
XOR
VP6189
XOR
VP189
XOR
VP189G
XOR
VP289G
XOR
VP389G
XOR
NOT
VP1189G
152CLREL
152CLITL
NOT
6189REL
6189ITL
AND
AND
OR
AND
AND
OR
NOT
189REL
189ITL
AND
en04000547_ansi.vsd
ANSI04000547 V1 EN
VP6189
VP189
6189_OP
189_OP
189_OP
189_CL
VP189
AND
NOT
NOT
189GREL
189GITL
289GREL
289GITL
189OPTR
189CLTR
VP189TR
en04000548_ansi.vsd
ANSI04000548 V1 EN
435
Technical reference manual
Section 11
Control
1MRK505208-UUS D
252_OP
252_CL
6289_OP
6289_CL
289_OP
289_CL
489G_OP
489G_CL
589G_OP
589G_CL
389G_OP
389G_CL
2189G_OP
2189G_CL
VP6289
VP289
VP252
VP489G
VP589G
VP389G
252_OP
489G_OP
589G_OP
389G_OP
6289_EX1
VP589G
VP389G
589G_CL
389G_CL
6289_EX2
VP252
VP489G
VP589G
VP2189G
252_OP
489G_OP
589G_OP
2189G_OP
EXDU_89G
289_EX1
VP489G
VP2189G
489G_CL
2189G_CL
EXDU_89G
289_EX2
DB_BUS_B
XOR
VP252
XOR
VP6289
XOR
VP289
XOR
VP489G
XOR
VP589G
VP389G
XOR
XOR
AND
AND
NOT
OR
NOT
VP2189G
252CLREL
252CLITL
6289REL
6289ITL
AND
AND
OR
NOT
289REL
289ITL
AND
en04000552_ansi.vsd
ANSI04000552 V1 EN
VP6289
VP289
6289_OP
289_OP
289_OP
289_CL
VP289
AND
NOT
NOT
489GREL
489GITL
589GREL
589GITL
289OPTR
289CLTR
VP289TR
en04000553_ansi.vsd
ANSI04000553 V1 EN
436
Technical reference manual
Section 11
Control
1MRK505208-UUS D
152_OP
152_CL
252_OP
252_CL
6189_OP
6189_CL
189G_OP
189G_CL
289G_OP
289G_CL
6289_OP
6289_CL
489G_OP
489G_CL
589G_OP
589G_CL
989_OP
989_CL
389G_OP
389G_CL
989G_OP
989G_CL
VOLT_OFF
VOLT_ON
VP152
VP252
VP189G
VP289G
VP389G
VP489G
VP589G
VP989G
152_OP
252_OP
189G_OP
289G_OP
389G_OP
489G_OP
589G_OP
989G_OP
989_EX1
DB_LINE
VP152
XOR
XOR
VP252
XOR
VP6189
XOR
VP189G
XOR
VP289G
XOR
VP6289
XOR
VP489G
XOR
VP589G
XOR
VP989
XOR
VP389G
XOR
VP989G
VPVOLT
XOR
AND
OR
NOT
989REL
989ITL
AND
en04000549_ansi.vsd
ANSI04000549 V1 EN
437
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP189G
VP289G
VP389G
VP989G
VP6289
152_OP
189G_OP
289G_OP
389G_OP
989G_OP
6289_OP
989_EX2
VP252
VP6189
VP389G
VP489G
VP589G
VP989G
252_OP
6189_OP
389G_OP
489G_OP
589G_OP
989G_OP
989_EX3
VP389G
VP989G
VP6189
VP6289
389G_OP
989G_OP
6189_OP
6289_OP
989_EX4
VP389G
VP989G
389G_CL
989G_CL
989_EX5
AND
OR
AND
AND
AND
en04000550_ansi.vsd
ANSI04000550 V1 EN
VP6189
VP6289
VP989
6189_OP
6289_OP
989_OP
VP989
VPVOLT
989_OP
VOLT_OFF
NOT
389GREL
389GITL
NOT
989GREL
989GITL
AND
AND
en04000551_ansi.vsd
ANSI04000551 V1 EN
11.3.9.4
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
QB61_OP
BOOLEAN
QB61_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QC11_OP
BOOLEAN
QC11_CL
BOOLEAN
EXDU_ES
BOOLEAN
QB61_EX1
BOOLEAN
QB61_EX2
BOOLEAN
QB1_EX1
BOOLEAN
QB1_EX2
BOOLEAN
Table 231:
Name
Description
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB61REL
BOOLEAN
QB61ITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
VPQB1TR
BOOLEAN
439
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 232:
Name
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QA2_OP
BOOLEAN
QA2_CL
BOOLEAN
QB61_OP
BOOLEAN
QB61_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QB62_OP
BOOLEAN
QB62_CL
BOOLEAN
QC4_OP
BOOLEAN
QC4_CL
BOOLEAN
QC5_OP
BOOLEAN
QC5_CL
BOOLEAN
QB9_OP
BOOLEAN
QB9_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QC9_OP
BOOLEAN
QC9_CL
BOOLEAN
VOLT_OFF
BOOLEAN
VOLT_ON
BOOLEAN
QB9_EX1
BOOLEAN
QB9_EX2
BOOLEAN
QB9_EX3
BOOLEAN
QB9_EX4
BOOLEAN
QB9_EX5
BOOLEAN
440
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 233:
Name
Description
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QC3REL
BOOLEAN
QC3ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
Table 234:
Name
Default
Description
QA2_OP
BOOLEAN
QA2_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QB62_OP
BOOLEAN
QB62_CL
BOOLEAN
QC4_OP
BOOLEAN
QC4_CL
BOOLEAN
QC5_OP
BOOLEAN
QC5_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QC21_OP
BOOLEAN
QC21_CL
BOOLEAN
EXDU_ES
BOOLEAN
QB62_EX1
BOOLEAN
QB62_EX2
BOOLEAN
QB2_EX1
BOOLEAN
QB2_EX2
BOOLEAN
441
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 235:
Name
Description
QA2CLREL
BOOLEAN
QA2CLITL
BOOLEAN
QB62REL
BOOLEAN
QB62ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QC4REL
BOOLEAN
QC4ITL
BOOLEAN
QC5REL
BOOLEAN
QC5ITL
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
VPQB2TR
BOOLEAN
11.3.10
11.3.10.1
Introduction
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 215. The
function can also be used for a double busbar arrangement without transfer busbar or a
single busbar arrangement with/without transfer busbar.
442
Technical reference manual
Section 11
Control
1MRK505208-UUS D
WA1 (A)
WA2 (B)
WA7 (C)
189
289
189G
789
152
289G
989
989G
en04000478_ansi.vsd
ANSI04000478 V1 EN
Figure 215:
443
Technical reference manual
Section 11
Control
11.3.10.2
1MRK505208-UUS D
Function block
ABC_LINE (3)
152CLREL
152_OP
152_CL
152CLITL
989_OP
989REL
989_CL
989ITL
189_OP
189REL
189_CL
189ITL
289_OP
289REL
289_CL
289ITL
789_OP
789REL
789_CL
789ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
989G_OP
989GREL
989G_CL
989GITL
1189G_OP
189OPTR
1189G_CL
189CLTR
2189G_OP
289OPTR
2189G_CL
289CLTR
7189G_OP
789OPTR
7189G_CL
789CLTR
BB7_D_OP
1289OPTR
BC_12_CL
1289CLTR
BC_17_OP
VP189TR
BC_17_CL
VP289TR
BC_27_OP
VP789TR
BC_27_CL
VP1289TR
VOLT_OFF
VOLT_ON
VP_BB7_D
VP_BC_12
VP_BC_17
VP_BC_27
EXDU_89G
EXDU_BPB
EXDU_BC
989_EX1
989_EX2
189_EX1
189_EX2
189_EX3
289_EX1
289_EX2
289_EX3
789_EX1
789_EX2
789_EX3
789_EX4
ANSI05000357-2-en.vsd
ANSI05000357 V2 EN
Figure 216:
444
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.10.3
Logic diagram
152_OP
152_CL
989_OP
989_CL
189_OP
189_CL
289_OP
289_CL
789_OP
789_CL
189G_OP
189G_CL
289G_OP
289G_CL
989G_OP
989G_CL
1189G_OP
1189G_CL
2189G_OP
2189G_CL
7189G_OP
7189G_CL
VOLT_OFF
VOLT_ON
VP152
VP189G
VP289G
VP989G
152_OP
189G_OP
289G_OP
989G_OP
989_EX1
VP289G
VP989G
289G_CL
989G_CL
989_EX2
ABC_LINE
XOR
VP152
XOR
VP989
XOR
VP189
XOR
VP289
XOR
VP789
XOR
VP189G
XOR
VP289G
XOR
VP989G
XOR
VP1189G
XOR
VP2189G
XOR
VP7189G
XOR
VPVOLT
AND
AND
OR
NOT
NOT
152CLREL
152CLITL
989REL
989ITL
AND
en04000527_ansi.vsd
ANSI04000527 V1 EN
445
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP289
VP189G
VP289G
VP1189G
152_OP
289_OP
189G_OP
289G_OP
1189G_OP
AND
VP289
AND
189REL
OR
NOT
189ITL
EXDU_89G
189_EX1
VP_BC_12
289_CL
BC_12_CL
EXDU_BC
189_EX2
VP189G
VP1189G
189G_CL
1189G_CL
EXDU_89G
AND
189EX3
en04000528_ansi.vsd
ANSI04000528 V1 EN
446
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP189
VP189G
VP289G
VP2189G
152_OP
189_OP
189G_OP
289G_OP
2189G_OP
EXDU_89G
AND
VP189
VP_BC_12
QB1_CL
BC_12_CL
EXDU_BC
AND
289REL
OR
NOT
289ITL
289_EX1
289_EX2
VP189G
VP2189G
189G_CL
2189G_CL
EXDU_89G
AND
289_EX3
en04000529_ansi.vsd
ANSI04000529 V1 EN
447
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP989G
VP7189G
AND
VP_BB7_D
789REL
OR
NOT
VP_BC_17
789ITL
VP_BC_27
989G_OP
7189G_OP
EXDU_89G
BB7_D_OP
EXDU_BPB
BC_17_OP
BC_27_OP
EXDU_BC
789_EX1
VP152
VP189
VP989G
VP989
VP7189G
VP_BB7_D
VP_BC_17
152_CL
189_CL
989G_OP
989_CL
7189G_OP
EXDU_89G
AND
BB7_D_OP
EXDU_BPB
BC_17_CL
EXDU_BC
789_EX2
en04000530_ansi.vsd
ANSI04000530 V1 EN
448
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP289
VP989G
VP989
VP7189G
VP_BB7_D
VP_BC_27
152_CL
289_CL
989G_OP
989_CL
7189G_OP
EXDU_89G
AND
OR
BB7_D_OP
EXDU_BPB
BC_27_CL
EXDU_BC
789_EX3
VP989G
VP7189G
989G_CL
7189G_CL
EXDU_89G
789_EX4
VP189
VP289
VP989
189_OP
289_OP
989_OP
VP789
VP989
VPVOLT
789_OP
989_OP
VOLT_OFF
AND
AND
NOT
NOT
AND
NOT
189GREL
189GITL
289GREL
289GITL
989GREL
989GITL
en04000531_ansi.vsd
ANSI04000531 V1 EN
449
Technical reference manual
Section 11
Control
1MRK505208-UUS D
189_OP
189_CL
VP189
189OPTR
189CLTR
VP189TR
289_OP
289_CL
VP289
289OPTR
289CLTR
VP289TR
789_OP
789_CL
VP789
789OPTR
789CLTR
VP789TR
189_OP
289_OP
VP189
VP289
OR
NOT
AND
1289OPTR
1289CLTR
VP1289TR
en04000532_ansi.vsd
ANSI04000532 V1 EN
11.3.10.4
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB9_OP
BOOLEAN
QB9_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QB7_OP
BOOLEAN
QB7_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QC9_OP
BOOLEAN
QC9_CL
BOOLEAN
450
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
QC11_OP
BOOLEAN
QC11_CL
BOOLEAN
QC21_OP
BOOLEAN
QC21_CL
BOOLEAN
QC71_OP
BOOLEAN
QC71_CL
BOOLEAN
BB7_D_OP
BOOLEAN
BC_12_CL
BOOLEAN
BC_17_OP
BOOLEAN
BC_17_CL
BOOLEAN
BC_27_OP
BOOLEAN
BC_27_CL
BOOLEAN
VOLT_OFF
BOOLEAN
VOLT_ON
BOOLEAN
VP_BB7_D
BOOLEAN
VP_BC_12
BOOLEAN
VP_BC_17
BOOLEAN
VP_BC_27
BOOLEAN
EXDU_ES
BOOLEAN
EXDU_BPB
BOOLEAN
EXDU_BC
BOOLEAN
QB9_EX1
BOOLEAN
QB9_EX2
BOOLEAN
QB1_EX1
BOOLEAN
QB1_EX2
BOOLEAN
451
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
QB1_EX3
BOOLEAN
QB2_EX1
BOOLEAN
QB2_EX2
BOOLEAN
QB2_EX3
BOOLEAN
QB7_EX1
BOOLEAN
QB7_EX2
BOOLEAN
QB7_EX3
BOOLEAN
QB7_EX4
BOOLEAN
Table 237:
Name
Description
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QB7REL
BOOLEAN
QB7ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
QB7OPTR
BOOLEAN
QB7CLTR
BOOLEAN
QB12OPTR
BOOLEAN
QB12CLTR
BOOLEAN
VPQB1TR
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Description
VPQB2TR
BOOLEAN
VPQB7TR
BOOLEAN
VPQB12TR
BOOLEAN
11.3.11
11.3.11.1
Introduction
The interlocking for transformer bay (AB_TRAFO, 3) function is used for a
transformer bay connected to a double busbar arrangement according to figure 217.
The function is used when there is no disconnector between circuit breaker and
transformer. Otherwise, the interlocking for line bay (ABC_LINE, 3) function can be
used. This function can also be used in single busbar arrangements.
WA1 (A)
WA2 (B)
189
289
189G
AB_TRAFO
152
289G
389G
252
489G
389
489
en04000515_ansi.vsd
ANSI04000515 V1 EN
Figure 217:
453
Technical reference manual
Section 11
Control
11.3.11.2
1MRK505208-UUS D
Function block
AB_TRAFO (3)
152_OP
152CLREL
152_CL
152CLITL
189_OP
189REL
189_CL
189ITL
289_OP
289REL
289_CL
289ITL
189G_OP
189GREL
189G_CL
189GITL
289G_OP
289GREL
289G_CL
289GITL
389_OP
189OPTR
389_CL
189CLTR
489_OP
289OPTR
489_CL
289CLTR
389G_OP
1289OPTR
389G_CL
1289CLTR
1189G_OP
VP189TR
1189G_CL
VP289TR
2189G_OP
VP1289TR
2189G_CL
BC_12_CL
VP_BC_12
EXDU_89G
EXDU_BC
152_EX1
152_EX2
152_EX3
189_EX1
189_EX2
189_EX3
289_EX1
289_EX2
289_EX3
ANSI05000358-2-en.vsd
ANSI05000358 V2 EN
Figure 218:
454
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.11.3
Logic diagram
152_OP
152_CL
189_OP
189_CL
289_OP
289_CL
189G_OP
189G_CL
289G_OP
289G_CL
389_OP
389_CL
489_OP
489_CL
389G_OP
389G_CL
1189G_OP
1189G_CL
2189G_OP
2189G_CL
VP189
VP289
VP189G
VP289G
VP389
VP489
VP389G
152_EX2
389G_OP
152_EX3
189G_CL
289G_CL
389G_CL
152_EX1
AB_TRAFO
XOR
VP152
XOR
VP189
XOR
VP289
XOR
VP189G
XOR
VP289G
XOR
VP389
XOR
VP489
XOR
VP389G
XOR
VP1189G
XOR
VP2189G
152CLREL
152CLITL
AND
NOT
OR
AND
en04000538_ansi.vsd
ANSI04000538 V1 EN
455
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP152
VP289
VP189G
VP289G
VP389G
VP1189G
152_OP
289_OP
189G_OP
289G_OP
389G_OP
1189G_OP
EXDU_89G
189_EX1
VP289
VP389G
VP_BC_12
289_CL
389G_OP
BC_12_CL
EXDU_BC
189_EX2
VP189G
VP289G
VP389G
VP1189G
189G_CL
289G_CL
389G_CL
1189G_CL
EXDU_89G
189_EX3
AND
189REL
OR
NOT
189ITL
AND
AND
en04000539_ansi.vsd
ANSI04000539 V1 EN
VP152
VP189
VP189G
VP289G
VP389G
VP2189G
152_OP
189_OP
189G_OP
289G_OP
389G_OP
2189G_OP
EXDU_89G
289_EX1
VP189
VP389G
VP_BC_12
189_CL
389G_OP
BC_12_CL
EXDU_BC
289_EX2
VP189G
VP289G
VP389G
VP2189G
189G_CL
289G_CL
389G_CL
2189G_CL
EXDU_89G
289_EX3
AND
OR
NOT
252REL
252ITL
AND
AND
en04000540_ansi.vsd
ANSI04000540 V1 EN
456
Technical reference manual
Section 11
Control
1MRK505208-UUS D
VP189
VP289
VP389
VP489
189_OP
289_OP
389_OP
489_OP
AND
189GREL
189GITL
289GREL
289GITL
NOT
NOT
189_OP
189_CL
VP189
189OPTR
189CLTR
VP189TR
289_OP
289_CL
VP289
189_OP
289_OP
VP189
VP289
289OPTR
289CLTR
VP289TR
1289OPTR
1289CLTR
VP1289TR
OR
NOT
AND
en04000541_ansi.vsd
ANSI04000541 V1 EN
11.3.11.4
Default
Description
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QB3_OP
BOOLEAN
QB3_CL
BOOLEAN
QB4_OP
BOOLEAN
QB4_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QC11_OP
BOOLEAN
QC11_CL
BOOLEAN
QC21_OP
BOOLEAN
QC21_CL
BOOLEAN
BC_12_CL
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
Type
Default
Description
VP_BC_12
BOOLEAN
EXDU_ES
BOOLEAN
EXDU_BC
BOOLEAN
QA1_EX1
BOOLEAN
QA1_EX2
BOOLEAN
QA1_EX3
BOOLEAN
QB1_EX1
BOOLEAN
QB1_EX2
BOOLEAN
QB1_EX3
BOOLEAN
QB2_EX1
BOOLEAN
QB2_EX2
BOOLEAN
QB2_EX3
BOOLEAN
Table 239:
Name
Description
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
QB12OPTR
BOOLEAN
QB12CLTR
BOOLEAN
VPQB1TR
BOOLEAN
VPQB2TR
BOOLEAN
VPQB12TR
BOOLEAN
458
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.3.12
11.3.12.1
Introduction
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals OPENPOS or
CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
11.3.12.2
Logic diagram
Position including quality
POSITION
POS_EVAL
OPENPOS
CLOSEPOS
Open/close position of
switch device
IEC08000469-1-en.vsd
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is not
used.
Input position (Value)
11.3.12.3
Signal quality
Output OPENPOS
Output CLOSEPOS
0 (Breaker intermediate)
Good
1 (Breaker open)
Good
2 (Breaker closed)
Good
3 (Breaker faulty)
Good
Any
Invalid
Any
Oscillatory
Function block
POSITION
POS_EVAL
OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd
IEC09000079 V1 EN
Figure 219:
11.3.12.4
Default
0
Description
Position status including quality
459
Section 11
Control
1MRK505208-UUS D
Table 241:
Name
11.4
Type
OPENPOS
BOOLEAN
Open position
CLOSEPOS
BOOLEAN
Close position
11.4.1
Description
IEC 61850
identification
SLGGIO
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
The logic rotating switch for function selection and LHMI presentation (SLGGIO) (or
the selector switch function block) is used to get a selector switch functionality similar
to the one provided by a hardware selector switch. Hardware selector switches are used
extensively by utilities, in order to have different functions operating on pre-set values.
Hardware switches are however sources for maintenance issues, lower system
reliability and an extended purchase portfolio. The logic selector switches eliminate all
these problems.
11.4.2
Principle of operation
The logic rotating switch for function selection and LHMI presentation (SLGGIO)
function has two operating inputs UP and DOWN. When a signal is received on the
UP input, the block will activate the output next to the present activated output, in
ascending order (if the present activated output is 3 for example and one operates the
UP input, then the output 4 will be activated). When a signal is received on the DOWN
input, the block will activate the output next to the present activated output, in
descending order (if the present activated output is 3 for example and one operates
the DOWN input, then the output 2 will be activated). Depending on the output
settings the output signals can be steady or pulsed. In case of steady signals, in case of
UP or DOWN operation, the previously active output will be deactivated. Also,
depending on the settings one can have a time delay between the UP or DOWN
activation signal positive front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
460
Technical reference manual
1MRK505208-UUS D
Section 11
Control
461
Technical reference manual
Section 11
Control
11.4.2.1
1MRK505208-UUS D
Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language
Ctrl/Com
Single Command
Selector Switch (GGIO)
3
../Com/Sel Sw/
SLGGIO3
Damage ctrl
../Ctrl/Com/Sel Sw
SLGGIO1
SLGGIO2
..
..
SLGGIO15
../Com/Sel Sw/
SLGGIO3
Damage ctrl
P:Disc All
OK
N: Disc Fe
Cancel
4
5
../Com/Sel Sw/
DmgCtrl
Damage ctrl:
IEC06000420-2-en.vsd
IEC06000420 V2 EN
Figure 220:
Example 1 on handling the switch from the local HMI.
From the local HMI:
1 SLGGIO instances in the ACT application configuration
2 Switch name given by the user (max 13 characters)
3 Position number, up to 32 positions
4 Change position
5 New position
11.4.2.2
Graphical display
There are two possibilities for SLGGIO
462
Technical reference manual
Section 11
Control
1MRK505208-UUS D
if it is used just for the monitoring, the switches will be listed with their actual
position names, as defined by the user (max. 13 characters).
if it is used for control, the switches will be listed with their actual positions, but
only the first three letters of the name will be used.
In both cases, the switch full name will be shown, but the user has to redefine it when
building the Graphical Display Editor, under the "Caption". If used for the control, the
following sequence of commands will ensure:
../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DAL
Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language
Open
Close
E
The pos will not be modified
(outputs will not be activated) until
you press the E-button for O.K.
Control
Single Line Diagram
Commands
../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
P: Disc
OK
N: Disc Fe
Cancel
../Control/SLD/Switch
SMBRREC control
WFM
Pilot setup
OFF
Damage control
DFW
ANSI06000421-2-en.vsd
ANSI06000421 V2 EN
Figure 221:
Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.
463
Technical reference manual
Section 11
Control
11.4.3
1MRK505208-UUS D
Function block
SLGGIO
BLOCK
PSTO
UP
DOWN
^SWPOS01
^SWPOS02
^SWPOS03
^SWPOS04
^SWPOS05
^SWPOS06
^SWPOS07
^SWPOS08
^SWPOS09
^SWPOS10
^SWPOS11
^SWPOS12
^SWPOS13
^SWPOS14
^SWPOS15
^SWPOS16
^SWPOS17
^SWPOS18
^SWPOS19
^SWPOS20
^SWPOS21
^SWPOS22
^SWPOS23
^SWPOS24
^SWPOS25
^SWPOS26
^SWPOS27
^SWPOS28
^SWPOS29
^SWPOS30
^SWPOS31
^SWPOS32
SWPOSN
ANSI05000658-2-en.vsd
ANSI05000658 V2 EN
Figure 222:
11.4.4
Default
Description
BLOCK
BOOLEAN
Block of function
PSTO
INTEGER
UP
BOOLEAN
DOWN
BOOLEAN
464
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 243:
Name
Description
SWPOS01
BOOLEAN
SWPOS02
BOOLEAN
SWPOS03
BOOLEAN
SWPOS04
BOOLEAN
SWPOS05
BOOLEAN
SWPOS06
BOOLEAN
SWPOS07
BOOLEAN
SWPOS08
BOOLEAN
SWPOS09
BOOLEAN
SWPOS10
BOOLEAN
SWPOS11
BOOLEAN
SWPOS12
BOOLEAN
SWPOS13
BOOLEAN
SWPOS14
BOOLEAN
SWPOS15
BOOLEAN
SWPOS16
BOOLEAN
SWPOS17
BOOLEAN
SWPOS18
BOOLEAN
SWPOS19
BOOLEAN
SWPOS20
BOOLEAN
SWPOS21
BOOLEAN
SWPOS22
BOOLEAN
SWPOS23
BOOLEAN
SWPOS24
BOOLEAN
SWPOS25
BOOLEAN
SWPOS26
BOOLEAN
SWPOS27
BOOLEAN
SWPOS28
BOOLEAN
SWPOS29
BOOLEAN
SWPOS30
BOOLEAN
SWPOS31
BOOLEAN
SWPOS32
BOOLEAN
SWPOSN
INTEGER
465
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.4.5
Table 244:
Name
Setting parameters
SLGGIO Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
NrPos
2 - 32
32
OutType
Pulsed
Steady
Steady
tPulse
0.000 - 60.000
0.001
0.200
tDelay
0.000 - 60000.000
0.010
0.000
StopAtExtremes
Disabled
Enabled
Disabled
11.5
11.5.1
IEC 61850
identification
VSGGIO
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
The Selector mini switch VSGGIO function block is a multipurpose function used for a
variety of applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line diagram
(SLD) on the local HMI.
11.5.2
Principle of operation
Selector mini switch (VSGGIO) function can be used for double purpose, in the same
way as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1
and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and distributed in
the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
466
Technical reference manual
Section 11
Control
1MRK505208-UUS D
The output CMDPOS21 is set when the function receives an OPEN command
from the local HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that the a symbol is associated
with a controllable object, otherwise the symbol won't be displayed on
the screen. A symbol is created and configured in GDE tool in PCM600.
The PSTO input is connected to the Local remote switch to have a selection of
operators place, operation from local HMI (Local) or through IEC 61850 (Remote). An
INTONE connection from Fixed signal function block (FXDSIGN) will allow
operation from local HMI.
As it can be seen, both indications and commands are done in double-bit
representation, where a combination of signals on both inputs/outputs generate the
desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the name
of the string that is shown on the SLD. The value of the strings are set in PST.
IPOS1
11.5.3
IPOS2
PosUndefined
P00
Position1
P01
Position2
P10
PosBadState
P11
Function block
VSGGIO
BLOCK
PSTO
IPOS1
IPOS2
BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
IEC06000508-2-en.vsd
IEC06000508 V3 EN
Figure 223:
467
Technical reference manual
Section 11
Control
11.5.4
1MRK505208-UUS D
Name
Type
Table 247:
Name
Description
BLOCK
BOOLEAN
Block of function
PSTO
INTEGER
IPOS1
BOOLEAN
IPOS2
BOOLEAN
Table 246:
Name
11.5.5
Default
Type
Description
BLOCKED
BOOLEAN
POSITION
INTEGER
POS1
BOOLEAN
POS2
BOOLEAN
CMDPOS12
BOOLEAN
CMDPOS21
BOOLEAN
Setting parameters
VSGGIO Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
CtlModel
Dir Norm
SBO Enh
Dir Norm
Mode
Steady
Pulsed
Pulsed
Operation mode
tSelect
0.000 - 60.000
0.001
30.000
tPulse
0.000 - 60.000
0.001
0.200
11.6
468
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Function description
IEC 61850
identification
11.6.1
IEC 60617
identification
DPGGIO
ANSI/IEEE C37.2
device number
-
Introduction
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It is
especially used in the interlocking and reservation station-wide logics.
11.6.2
Principle of operation
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipment
or system that requests these signals. To be able to get the signals, other tools must be
used, as described in the application manual, to PCM600 must be used to define which
function block in which equipment or system should receive this information.
11.6.3
Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC07000200-2-en.vsd
IEC07000200 V2 EN
Figure 224:
11.6.4
Default
Description
OPEN
BOOLEAN
Open indication
CLOSE
BOOLEAN
Close indication
VALID
BOOLEAN
Valid indication
Table 249:
Name
POSITION
Type
INTEGER
Description
Double point indication
469
Technical reference manual
Section 11
Control
11.6.5
1MRK505208-UUS D
Settings
The function does not have any parameters available in the local HMI or PCM600.
11.7
11.7.1
IEC 61850
identification
SPC8GGIO
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
The Single point generic control 8 signals (SPC8GGIO) function block is a collection
of 8 single point commands, designed to bring in commands from REMOTE (SCADA)
to those parts of the logic configuration that do not need extensive command receiving
functionality (for example, SCSWI). In this way, simple commands can be sent
directly to the IED outputs, without confirmation. Confirmation (status) of the result of
the commands is supposed to be achieved by other means, such as binary inputs and
SPGGIO function blocks. The commands can be pulsed or steady.
11.7.2
Principle of operation
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the
eight outputs is activated based on the command sent from the operator place selected.
The settings Latchedx and tPulsex (where x is the respective output) will determine if
the signal will be pulsed (and how long the pulse is) or latched (steady). BLOCK will
block the operation of the function in case a command is sent, no output will be activated.
PSTO is the universal operator place selector for all control functions.
Although, PSTO can be configured to use LOCAL or ALL operator
places only, REMOTE operator place is used in SPC8GGIO function.
470
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.7.3
Function block
SPC8GGIO
BLOCK
PSTO
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
IEC07000143-2-en.vsd
IEC07000143 V2 EN
Figure 225:
11.7.4
Default
Description
BLOCK
BOOLEAN
PSTO
INTEGER
Table 251:
Name
Description
OUT1
BOOLEAN
Output 1
OUT2
BOOLEAN
Output2
OUT3
BOOLEAN
Output3
OUT4
BOOLEAN
Output4
OUT5
BOOLEAN
Output5
OUT6
BOOLEAN
Output6
OUT7
BOOLEAN
Output7
OUT8
BOOLEAN
Output8
471
Technical reference manual
Section 11
Control
11.7.5
Table 252:
Name
1MRK505208-UUS D
Setting parameters
SPC8GGIO Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Disabled/Enabled
Latched1
Pulsed
Latched
Pulsed
tPulse1
0.01 - 6000.00
0.01
0.10
Latched2
Pulsed
Latched
Pulsed
tPulse2
0.01 - 6000.00
0.01
0.10
Latched3
Pulsed
Latched
Pulsed
tPulse3
0.01 - 6000.00
0.01
0.10
Latched4
Pulsed
Latched
Pulsed
tPulse4
0.01 - 6000.00
0.01
0.10
Latched5
Pulsed
Latched
Pulsed
tPulse5
0.01 - 6000.00
0.01
0.10
Latched6
Pulsed
Latched
Pulsed
tPulse6
0.01 - 6000.00
0.01
0.10
Latched7
Pulsed
Latched
Pulsed
tPulse7
0.01 - 6000.00
0.01
0.10
Latched8
Pulsed
Latched
Pulsed
tPulse8
0.01 - 6000.00
0.01
0.10
11.8
IEC 61850
identification
AUTOBITS
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
472
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.8.1
Introduction
AutomationBits function for DNP3 (AUTOBITS) is used within PCM600 to get into
the configuration of the commands coming through the DNP3 protocol. The
AUTOBITS function plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).
11.8.2
Principle of operation
AutomationBits function (AUTOBITS) has 32 individual outputs which each can be
mapped as a Binary Output point in DNP3. The output is operated by a "Object 12" in
DNP3. This object contains parameters for control-code, count, on-time and off-time.
To operate an AUTOBITS output point, send a control-code of latch-On, latch-Off, pulseOn, pulse-Off, Trip or Close. The remaining parameters will be regarded were
appropriate. ex: pulse-On, on-time=100, off-time=300, count=5 would give 5 positive
100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the
same way the setting Operation: Enabled/Disabled does. That means that, upon
activation of the BLOCK input, all 32 CMDBITxx outputs will be set to 0. The
BLOCK acts like an overriding, the function still receives data from the DNP3 master.
Upon deactivation of BLOCK, all the 32 CMDBITxx outputs will be set by the DNP3
master again, momentarily. For AUTOBITS , the PSTO input determines the operator
place. The command can be written to the block while in Remote. If PSTO is in
Local then no change is applied to the outputs.
473
Technical reference manual
Section 11
Control
11.8.3
1MRK505208-UUS D
Function block
AUTOBITS
BLOCK
PSTO
^CMDBIT1
^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32
IEC09000925-1-en.vsd
IEC09000925 V1 EN
Figure 226:
11.8.4
Default
Description
BLOCK
BOOLEAN
Block of function
PSTO
INTEGER
Table 254:
Name
Description
CMDBIT1
BOOLEAN
CMDBIT2
BOOLEAN
CMDBIT3
BOOLEAN
CMDBIT4
BOOLEAN
CMDBIT5
BOOLEAN
Section 11
Control
1MRK505208-UUS D
Name
11.8.5
Table 255:
Type
Description
CMDBIT6
BOOLEAN
CMDBIT7
BOOLEAN
CMDBIT8
BOOLEAN
CMDBIT9
BOOLEAN
CMDBIT10
BOOLEAN
CMDBIT11
BOOLEAN
CMDBIT12
BOOLEAN
CMDBIT13
BOOLEAN
CMDBIT14
BOOLEAN
CMDBIT15
BOOLEAN
CMDBIT16
BOOLEAN
CMDBIT17
BOOLEAN
CMDBIT18
BOOLEAN
CMDBIT19
BOOLEAN
CMDBIT20
BOOLEAN
CMDBIT21
BOOLEAN
CMDBIT22
BOOLEAN
CMDBIT23
BOOLEAN
CMDBIT24
BOOLEAN
CMDBIT25
BOOLEAN
CMDBIT26
BOOLEAN
CMDBIT27
BOOLEAN
CMDBIT28
BOOLEAN
CMDBIT29
BOOLEAN
CMDBIT30
BOOLEAN
CMDBIT31
BOOLEAN
CMDBIT32
BOOLEAN
Setting parameters
AUTOBITS Non group settings (basic)
Name
Operation
Values (Range)
Disabled
Enabled
Unit
-
Step
-
Default
Disabled
Description
Disable/Enable Operation
475
Technical reference manual
Section 11
Control
Table 256:
Name
Operation
Table 257:
Name
1MRK505208-UUS D
Unit
-
Step
-
Default
Disabled
Description
Disable/Enable Operation
Unit
Step
Default
Description
Operation
Disabled
Serial-Mode
Disabled
Operation mode
BaudRate
300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
9600 Bd
WireMode
Four-wire
Two-wire
Two-wire
Table 258:
Name
Unit
Step
Default
Description
DLinkConfirm
Never
Sometimes
Always
Never
Data-link confirm
tDLinkTimeout
0.000 - 60.000
0.001
2.000
DLinkRetries
0 - 255
tRxToTxMinDel
0.000 - 60.000
0.001
0.000
Rx to Tx minimum delay in s
ApLayMaxRxSize
20 - 2048
2048
ApLayMaxTxSize
20 - 2048
2048
StopBits
1-2
Stop bits
Parity
No
Even
Odd
Even
Parity
tRTSWarmUp
0.000 - 60.000
0.001
0.000
RTS warm-up in s
tRTSWarmDown
0.000 - 60.000
0.001
0.000
RTS warm-down in s
tBackOffDelay
0.000 - 60.000
0.001
0.050
tMaxRndDelBkOf
0.000 - 60.000
0.001
0.100
476
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 259:
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
TCP/IP
UDP-Only
Disabled
Operation mode
TCPIPLisPort
1 - 65535
20000
UDPPortAccData
1 - 65535
20000
UDPPortInitNUL
1 - 65535
20000
UDPPortCliMast
0 - 65535
Table 260:
Name
Values (Range)
Unit
Step
Default
Description
ApLayMaxRxSize
20 - 2048
2048
ApLayMaxTxSize
20 - 2048
2048
Table 261:
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
TCP/IP
UDP-Only
Disabled
Operation mode
TCPIPLisPort
1 - 65535
20000
UDPPortAccData
1 - 65535
20000
UDPPortInitNUL
1 - 65535
20000
UDPPortCliMast
0 - 65535
Table 262:
Name
Values (Range)
Unit
Step
Default
Description
ApLayMaxRxSize
20 - 2048
2048
ApLayMaxTxSize
20 - 2048
2048
477
Technical reference manual
Section 11
Control
Table 263:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
Operation
Disabled
TCP/IP
UDP-Only
Disabled
Operation mode
TCPIPLisPort
1 - 65535
20000
UDPPortAccData
1 - 65535
20000
UDPPortInitNUL
1 - 65535
20000
UDPPortCliMast
0 - 65535
Table 264:
Name
Unit
Step
Default
Description
ApLayMaxRxSize
20 - 2048
2048
ApLayMaxTxSize
20 - 2048
2048
Table 265:
Name
Unit
Step
Default
Description
Operation
Disabled
TCP/IP
UDP-Only
Disabled
Operation mode
TCPIPLisPort
1 - 65535
20000
UDPPortAccData
1 - 65535
20000
UDPPortInitNUL
1 - 65535
20000
UDPPortCliMast
0 - 65535
Table 266:
Name
Unit
Step
Default
Description
ApLayMaxRxSize
20 - 2048
2048
ApLayMaxTxSize
20 - 2048
2048
Table 267:
Name
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
SlaveAddress
0 - 65519
Slave address
MasterAddres
0 - 65519
Master address
Section 11
Control
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Obj1DefVar
1:BISingleBit
2:BIWithStatus
1:BISingleBit
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
3:BIChWithRelTim
e
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
3:DIChWithRelTim
e
Obj10DefVar
1:BO
2:BOStatus
2:BOStatus
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
5:BinCnt32WoutF
Obj22DefVar
1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
1:BinCnt32EvWou
tT
Obj30DefVar
1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
3:AI32IntWithoutF
Obj32DefVar
1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
1:AI32IntEvWoutF
Table 268:
Name
Values (Range)
Unit
Step
Default
Description
ValMasterAddr
No
Yes
Yes
AddrQueryEnbl
No
Yes
Yes
tApplConfTout
0.00 - 300.00
0.01
10.00
479
Technical reference manual
Section 11
Control
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
ApplMultFrgRes
No
Yes
Yes
ConfMultFrag
No
Yes
Yes
UREnable
No
Yes
Yes
URSendOnline
No
Yes
No
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
Disabled
UROfflineRetry
0 - 10
tURRetryDelay
0.00 - 60.00
0.01
5.00
tUROfflRtryDel
0.00 - 60.00
0.01
30.00
UREvCntThold1
1 - 100
tUREvBufTout1
0.00 - 60.00
0.01
5.00
UREvCntThold2
1 - 100
tUREvBufTout2
0.00 - 60.00
0.01
5.00
UREvCntThold3
1 - 100
tUREvBufTout3
0.00 - 60.00
0.01
5.00
DelOldBufFull
No
Yes
No
tSynchTimeout
30 - 3600
1800
TSyncReqAfTout
No
Yes
No
DNPToSetTime
No
Yes
Yes
Averag3TimeReq
No
Yes
No
PairedPoint
No
Yes
Yes
tSelectTimeout
1.0 - 60.0
0.1
30.0
Select timeout
480
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Table 269:
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
SlaveAddress
0 - 65519
Slave address
MasterAddres
0 - 65519
Master address
ValMasterAddr
No
Yes
Yes
MasterIP-Addr
0 - 18
IP
Address
0.0.0.0
Master IP-address
MasterIPNetMsk
0 - 18
IP
Address
255.255.255.255
Obj1DefVar
1:BISingleBit
2:BIWithStatus
1:BISingleBit
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
3:BIChWithRelTim
e
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
1:DIWithoutFlag
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
3:DIChWithRelTim
e
Obj10DefVar
1:BO
2:BOStatus
2:BOStatus
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
5:BinCnt32WoutF
481
Technical reference manual
Section 11
Control
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
Obj22DefVar
1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
1:BinCnt32EvWou
tT
Obj30DefVar
1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
3:AI32IntWithoutF
Obj32DefVar
1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
1:AI32IntEvWoutF
Table 270:
Name
Unit
Step
Default
Description
AddrQueryEnbl
No
Yes
Yes
tApplConfTout
0.00 - 300.00
0.01
10.00
ApplMultFrgRes
No
Yes
Yes
ConfMultFrag
No
Yes
Yes
UREnable
No
Yes
Yes
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
Disabled
UROfflineRetry
0 - 10
tURRetryDelay
0.00 - 60.00
0.01
5.00
tUROfflRtryDel
0.00 - 60.00
0.01
30.00
UREvCntThold1
1 - 100
482
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Unit
Step
Default
tUREvBufTout1
0.00 - 60.00
0.01
5.00
UREvCntThold2
1 - 100
tUREvBufTout2
0.00 - 60.00
0.01
5.00
UREvCntThold3
1 - 100
tUREvBufTout3
0.00 - 60.00
0.01
5.00
DelOldBufFull
No
Yes
No
ExtTimeFormat
LocalTime
UTC
UTC
DNPToSetTime
No
Yes
No
tSynchTimeout
30 - 3600
1800
TSyncReqAfTout
No
Yes
No
Averag3TimeReq
No
Yes
No
PairedPoint
No
Yes
Yes
tSelectTimeout
1.0 - 60.0
0.1
30.0
Select timeout
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
10
Keep-Alive timer
Table 271:
Values (Range)
Description
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
SlaveAddress
0 - 65519
Slave address
MasterAddres
0 - 65519
Master address
ValMasterAddr
No
Yes
Yes
MasterIP-Addr
0 - 18
IP
Address
0.0.0.0
Master IP-address
MasterIPNetMsk
0 - 18
IP
Address
255.255.255.255
Obj1DefVar
1:BISingleBit
2:BIWithStatus
1:BISingleBit
483
Technical reference manual
Section 11
Control
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
3:BIChWithRelTim
e
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
1:DIWithoutFlag
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
3:DIChWithRelTim
e
Obj10DefVar
1:BO
2:BOStatus
2:BOStatus
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
5:BinCnt32WoutF
Obj22DefVar
1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
1:BinCnt32EvWou
tT
Obj30DefVar
1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
3:AI32IntWithoutF
Obj32DefVar
1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
1:AI32IntEvWoutF
Table 272:
Name
Unit
Step
Default
Description
AddrQueryEnbl
No
Yes
Yes
tApplConfTout
0.00 - 300.00
0.01
10.00
ApplMultFrgRes
No
Yes
Yes
484
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
ConfMultFrag
No
Yes
Yes
UREnable
No
Yes
Yes
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
Disabled
UROfflineRetry
0 - 10
tURRetryDelay
0.00 - 60.00
0.01
5.00
tUROfflRtryDel
0.00 - 60.00
0.01
30.00
UREvCntThold1
1 - 100
tUREvBufTout1
0.00 - 60.00
0.01
5.00
UREvCntThold2
1 - 100
tUREvBufTout2
0.00 - 60.00
0.01
5.00
UREvCntThold3
1 - 100
tUREvBufTout3
0.00 - 60.00
0.01
5.00
DelOldBufFull
No
Yes
No
ExtTimeFormat
LocalTime
UTC
UTC
DNPToSetTime
No
Yes
No
tSynchTimeout
30 - 3600
1800
TSyncReqAfTout
No
Yes
No
Averag3TimeReq
No
Yes
No
PairedPoint
No
Yes
Yes
tSelectTimeout
1.0 - 60.0
0.1
30.0
Select timeout
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
10
Keep-Alive timer
485
Technical reference manual
Section 11
Control
Table 273:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
SlaveAddress
0 - 65519
Slave address
MasterAddres
0 - 65519
Master address
ValMasterAddr
No
Yes
Yes
MasterIP-Addr
0 - 18
IP
Address
0.0.0.0
Master IP-address
MasterIPNetMsk
0 - 18
IP
Address
255.255.255.255
Obj1DefVar
1:BISingleBit
2:BIWithStatus
1:BISingleBit
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
3:BIChWithRelTim
e
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
1:DIWithoutFlag
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
3:DIChWithRelTim
e
Obj10DefVar
1:BO
2:BOStatus
2:BOStatus
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
5:BinCnt32WoutF
486
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Obj22DefVar
1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
1:BinCnt32EvWou
tT
Obj30DefVar
1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
3:AI32IntWithoutF
Obj32DefVar
1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
1:AI32IntEvWoutF
Table 274:
Name
Values (Range)
Unit
Step
Default
Description
AddrQueryEnbl
No
Yes
Yes
tApplConfTout
0.00 - 300.00
0.01
10.00
ApplMultFrgRes
No
Yes
Yes
ConfMultFrag
No
Yes
Yes
UREnable
No
Yes
Yes
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
Disabled
UROfflineRetry
0 - 10
tURRetryDelay
0.00 - 60.00
0.01
5.00
tUROfflRtryDel
0.00 - 60.00
0.01
30.00
UREvCntThold1
1 - 100
487
Technical reference manual
Section 11
Control
Name
1MRK505208-UUS D
Unit
Step
Default
tUREvBufTout1
0.00 - 60.00
0.01
5.00
UREvCntThold2
1 - 100
tUREvBufTout2
0.00 - 60.00
0.01
5.00
UREvCntThold3
1 - 100
tUREvBufTout3
0.00 - 60.00
0.01
5.00
DelOldBufFull
No
Yes
No
ExtTimeFormat
LocalTime
UTC
UTC
DNPToSetTime
No
Yes
No
tSynchTimeout
30 - 3600
1800
TSyncReqAfTout
No
Yes
No
Averag3TimeReq
No
Yes
No
PairedPoint
No
Yes
Yes
tSelectTimeout
1.0 - 60.0
0.1
30.0
Select timeout
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
10
Keep-Alive timer
Table 275:
Name
Values (Range)
Description
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
SlaveAddress
0 - 65519
Slave address
MasterAddres
0 - 65519
Master address
ValMasterAddr
No
Yes
Yes
MasterIP-Addr
0 - 18
IP
Address
0.0.0.0
Master IP-address
MasterIPNetMsk
0 - 18
IP
Address
255.255.255.255
Obj1DefVar
1:BISingleBit
2:BIWithStatus
1:BISingleBit
488
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Obj2DefVar
1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
3:BIChWithRelTim
e
Obj3DefVar
1:DIWithoutFlag
2:DIWithFlag
1:DIWithoutFlag
Obj4DefVar
1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
3:DIChWithRelTim
e
Obj10DefVar
1:BO
2:BOStatus
2:BOStatus
Obj20DefVar
1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
5:BinCnt32WoutF
Obj22DefVar
1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
1:BinCnt32EvWou
tT
Obj30DefVar
1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
3:AI32IntWithoutF
Obj32DefVar
1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
1:AI32IntEvWoutF
Table 276:
Name
Values (Range)
Unit
Step
Default
Description
AddrQueryEnbl
No
Yes
Yes
tApplConfTout
0.00 - 300.00
0.01
10.00
ApplMultFrgRes
No
Yes
Yes
489
Technical reference manual
Section 11
Control
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
ConfMultFrag
No
Yes
Yes
UREnable
No
Yes
Yes
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
Disabled
UROfflineRetry
0 - 10
tURRetryDelay
0.00 - 60.00
0.01
5.00
tUROfflRtryDel
0.00 - 60.00
0.01
30.00
UREvCntThold1
1 - 100
tUREvBufTout1
0.00 - 60.00
0.01
5.00
UREvCntThold2
1 - 100
tUREvBufTout2
0.00 - 60.00
0.01
5.00
UREvCntThold3
1 - 100
tUREvBufTout3
0.00 - 60.00
0.01
5.00
DelOldBufFull
No
Yes
No
ExtTimeFormat
LocalTime
UTC
UTC
DNPToSetTime
No
Yes
No
tSynchTimeout
30 - 3600
1800
TSyncReqAfTout
No
Yes
No
Averag3TimeReq
No
Yes
No
PairedPoint
No
Yes
Yes
tSelectTimeout
1.0 - 60.0
0.1
30.0
Select timeout
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
10
Keep-Alive timer
490
Technical reference manual
Section 11
Control
1MRK505208-UUS D
11.9
11.9.1
IEC 61850
identification
SINGLECMD
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
The IEDs can receive commands either from a substation automation system or from
the local HMI. The command function block has outputs that can be used, for example,
to control high voltage apparatuses or for other user defined functionality.
11.9.2
Principle of operation
Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of 13
characters in PCM600.
The output signals can be of the types Disabled, Steady, or Pulse. This configuration
setting is done via the local HMI or PCM600 and is common for the whole function
block. The length of the output pulses are 100 ms. In steady mode, SINGLECMD
function has a memory to remember the output values at power interruption of the IED.
Also a BLOCK input is available used to block the updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
491
Technical reference manual
Section 11
Control
11.9.3
1MRK505208-UUS D
Function block
SINGLECMD
BLOCK
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
IEC05000698-2-en.vsd
IEC05000698 V3 EN
Figure 227:
11.9.4
Table 278:
Name
Default
0
Description
Block single command function
Description
OUT1
BOOLEAN
OUT2
BOOLEAN
OUT3
BOOLEAN
OUT4
BOOLEAN
OUT5
BOOLEAN
OUT6
BOOLEAN
OUT7
BOOLEAN
OUT8
BOOLEAN
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
492
Technical reference manual
Section 11
Control
1MRK505208-UUS D
Name
11.9.5
Table 279:
Type
Description
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
Setting parameters
SINGLECMD Non group settings (basic)
Name
Mode
Values (Range)
Disabled
Steady
Pulsed
Unit
-
Step
-
Default
Disabled
Description
Operation mode
493
Technical reference manual
494
Section 12
Logic
1MRK505208-UUS D
Section 12
Logic
12.1
12.1.1
Introduction
A number of logic blocks and timers are available for the user to adapt the
configuration to the specific application needs.
OR function block.
PULSETIMER function block can be used, for example, for pulse extensions or
limiting of operation of outputs, settable pulse time.
GATE function block is used for whether or not a signal should be able to pass
from the input to the output.
LOOPDELAY function block used to delay the output signal one execution cycle.
TIMERSET function has pick-up and drop-out delayed outputs related to the
input signal. The timer has a settable time delay.
SRMEMORY function block is a flip-flop that can set or reset an output from two
inputs respectively. Each block has two outputs where one is inverted. The
495
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
memory setting controls if the block's output should reset or return to the state it
was, after a power interruption.
12.1.2
RSMEMORY function block is a flip-flop that can reset or set an output from two
inputs respectively. Each block has two outputs where one is inverted. The
memory setting controls if the block's output should reset or return to the state it
was, after a power interruption. RESET input has priority.
OUT
IEC04000404_2_en.vsd
IEC04000404 V2 EN
Figure 228:
Table 280:
Name
Type
INPUT
BOOLEAN
Table 281:
Description
Input
Name
Type
OUT
12.1.3
Default
BOOLEAN
Description
Output
OR function block OR
The OR function is used to form general combinatory expressions with boolean
variables. The OR function block has six inputs and two outputs. One of the outputs is
inverted.
OR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
IEC04000405_2_en.vsd
IEC04000405 V2 EN
Figure 229:
OR function block
496
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Table 282:
OR Input signals
Name
Type
Description
INPUT1
BOOLEAN
Input 1 to OR gate
INPUT2
BOOLEAN
Input 2 to OR gate
INPUT3
BOOLEAN
Input 3 to OR gate
INPUT4
BOOLEAN
Input 4 to OR gate
INPUT5
BOOLEAN
Input 5 to OR gate
INPUT6
BOOLEAN
Input 6 to OR gate
Table 283:
OR Output signals
Name
12.1.4
Default
Type
Description
OUT
BOOLEAN
NOUT
BOOLEAN
OUT
NOUT
IEC04000406_2_en.vsd
IEC04000406 V2 EN
Figure 230:
Table 284:
Name
Type
Default
Description
INPUT1
BOOLEAN
Input 1
INPUT2
BOOLEAN
Input 2
INPUT3
BOOLEAN
Input 3
INPUT4N
BOOLEAN
Input 4 inverted
Table 285:
Name
Description
OUT
BOOLEAN
Output
NOUT
BOOLEAN
Output inverted
497
Section 12
Logic
12.1.5
1MRK505208-UUS D
ON
OFF
IEC04000378-3-en.vsd
IEC04000378 V2 EN
Figure 231:
Table 286:
Name
Type
BOOLEAN
Table 287:
Name
Table 288:
Name
T
12.1.6
Default
INPUT
Type
Description
Input to timer
Description
ON
BOOLEAN
OFF
BOOLEAN
Unit
0.000 - 90000.000
Step
0.001
Default
Description
0.000
OUT
IEC04000407-2-en.vsd
IEC04000407 V2 EN
Figure 232:
Table 289:
Name
INPUT
Type
BOOLEAN
Default
0
Description
Input to pulse timer
498
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Table 290:
Name
Type
OUT
Table 291:
Description
BOOLEAN
Name
T
12.1.7
Values (Range)
Unit
0.000 - 90000.000
Step
Default
0.001
Description
0.010
OUT
NOUT
IEC04000409-2-en.vsd
IEC04000409 V2 EN
Figure 233:
Table 292:
Name
Default
Description
BOOLEAN
INPUT2
BOOLEAN
Table 293:
Name
12.1.8
Type
INPUT1
Description
OUT
BOOLEAN
NOUT
BOOLEAN
499
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
LOOPDELAY
INPUT
OUT
IEC09000296-1-en.vsd
IEC09000296 V1 EN
Figure 234:
Table 294:
Name
Type
INPUT
Table 295:
Description
Input signal
Name
Type
OUT
12.1.9
Default
BOOLEAN
Description
BOOLEAN
OUT
NOUT
Last
value
Inverted
last value
SRMEMORY
SET
OUT
RESET
NOUT
IEC04000408_2_en.vsd
IEC04000408 V2 EN
Figure 235:
500
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Table 297:
Name
Type
Description
SET
BOOLEAN
RESET
BOOLEAN
Table 298:
Name
Table 299:
Default
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Name
Memory
12.1.10
Values (Range)
Unit
Disabled
Enabled
Step
Default
Enabled
Description
Operating mode of the memory function
RESET
SET
OUT
NOUT
Last
value
Inverted last
value
RSMEMORY
SET
RESET
OUT
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Figure 236:
501
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Table 301:
Name
Type
BOOLEAN
RESET
BOOLEAN
Name
Name
Memory
12.1.11
Description
SET
Table 302:
Table 303:
Default
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Unit
Disabled
Enabled
Step
-
Default
Enabled
Description
Operating mode of the memory function
OUT
IEC04000410-2-en.vsd
IEC04000410 V2 EN
Figure 237:
Table 304:
Name
Type
INPUT
Table 305:
Type
OUT
Name
Operation
Description
Input to gate
Name
Table 306:
Default
BOOLEAN
Description
BOOLEAN
Unit
-
Step
-
Default
Disabled
Description
Operation Disabled/Enabled
502
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
12.1.12
ON
OFF
IEC04000411-2-en.vsd
IEC04000411 V2 EN
Figure 238:
Table 307:
Name
Type
INPUT
Table 308:
Description
Input to timer
Name
Table 309:
Default
BOOLEAN
Type
Description
ON
BOOLEAN
OFF
BOOLEAN
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Disabled/Enabled
0.000 - 90000.000
0.001
0.000
12.1.13
Technical data
Table 310:
Logic block
Range or value
Accuracy
LogicAND
90
90
100
LogicOR
90
90
100
LogicXOR
15
15
10
LogicInverter
45
45
50
LogicSRMemory
15
15
10
LogicRSMemory
15
15
10
Section 12
Logic
1MRK505208-UUS D
Logic block
12.2
Accuracy
LogicGate
15
15
10
LogicTimer
15
15
10
(0.000
90000.000) s
0.5% 10 ms
LogicPulseTimer
15
15
10
(0.000
90000.000) s
0.5% 10 ms
LogicTimerSet
15
15
10
(0.000
90000.000) s
0.5% 10 ms
LogicLoopDelay
15
15
10
(0.000
90000.000) s
0.5% 10 ms
Boolean 16 to Integer
Boolean 16 to
integer with Logic
Node
Integer to Boolean 16
Integer to Boolean
16 with Logic Node
12.2.1
Range or value
IEC 61850
identification
FXDSIGN
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
12.3
12.3.1
IEC 61850
identification
B16I
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.
504
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
12.3.2
Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up
to 16 binary inputs INx where 1x16 to an integer. Each INx represents a value
according to the table below from 0 to 32768. This follows the general formula: INx =
2x-1 where 1x16. The sum of all the values on the activated INx will be available on
the output OUT as a sum of the values of all the inputs INx that are activated. OUT is
an integer. When all INx where 1x16 are activated that is = Boolean 1 it corresponds
to that integer 65535 is available on the output OUT. B16I function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will
freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1x16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block B16I
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
Input 1
IN2
BOOLEAN
Input 2
IN3
BOOLEAN
Input 3
IN4
BOOLEAN
Input 4
IN5
BOOLEAN
Input 5
16
IN6
BOOLEAN
Input 6
32
IN7
BOOLEAN
Input 7
64
IN8
BOOLEAN
Input 8
128
IN9
BOOLEAN
Input 9
256
IN10
BOOLEAN
Input 10
512
IN11
BOOLEAN
Input 11
1024
IN12
BOOLEAN
Input 12
2048
IN13
BOOLEAN
Input 13
4096
IN14
BOOLEAN
Input 14
8192
IN15
BOOLEAN
Input 15
16384
IN16
BOOLEAN
Input 16
32768
The sum of the numbers in column Value when activated when all INx (where
1x16) are active that is=1; is 65535. 65535 is the highest boolean value that can be
converted to an integer by the B16I function block.
505
Technical reference manual
Section 12
Logic
12.3.3
1MRK505208-UUS D
Function block
B16I
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
OUT
IEC07000128-2-en.vsd
IEC07000128 V2 EN
Figure 239:
12.3.4
Default
Description
BLOCK
BOOLEAN
Block of function
IN1
BOOLEAN
Input 1
IN2
BOOLEAN
Input 2
IN3
BOOLEAN
Input 3
IN4
BOOLEAN
Input 4
IN5
BOOLEAN
Input 5
IN6
BOOLEAN
Input 6
IN7
BOOLEAN
Input 7
IN8
BOOLEAN
Input 8
IN9
BOOLEAN
Input 9
IN10
BOOLEAN
Input 10
IN11
BOOLEAN
Input 11
IN12
BOOLEAN
Input 12
IN13
BOOLEAN
Input 13
IN14
BOOLEAN
Input 14
IN15
BOOLEAN
Input 15
IN16
BOOLEAN
Input 16
506
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Table 312:
Name
OUT
12.3.5
Type
INTEGER
Description
Output value
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
12.4
12.4.1
IEC 61850
identification
B16IFCVI
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
Boolean 16 to integer conversion with logic node representation function (B16IFCVI)
is used to transform a set of 16 binary (logical) signals into an integer.
B16IFCVI can receive remote values via IEC 61850 depending on the operator
position input (PSTO).
12.4.2
Operation principle
The Boolean 16 to integer conversion with logic node representation function
(BTIGAPC) will transfer a combination of up to 16 binary inputs INx where 1x16 to
an integer. Each INx represents a value according to the table below from 0 to 32768.
This follows the general formula: INx = 2x-1 where 1x16. The sum of all the values
on the activated INx will be available on the output OUT as a sum of the values of all
the inputs INx that are activated. OUT is an integer. When all INx where 1x16 are
activated that is = Boolean 1 it corresponds to that integer 65535 is available on the
output OUT. The BTIGAPC function is designed for receiving the integer input from a
station computer - for example, over IEC 61850. If the BLOCK input is activated, it
will freeze the logical outputs at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1x16.
507
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block BTIGAPC.
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
Input 1
IN2
BOOLEAN
Input 2
IN3
BOOLEAN
Input 3
IN4
BOOLEAN
Input 4
IN5
BOOLEAN
Input 5
16
IN6
BOOLEAN
Input 6
32
IN7
BOOLEAN
Input 7
64
IN8
BOOLEAN
Input 8
128
IN9
BOOLEAN
Input 9
256
IN10
BOOLEAN
Input 10
512
IN11
BOOLEAN
Input 11
1024
IN12
BOOLEAN
Input 12
2048
IN13
BOOLEAN
Input 13
4096
IN14
BOOLEAN
Input 14
8192
IN15
BOOLEAN
Input 15
16384
IN16
BOOLEAN
Input 16
32768
The sum of the numbers in column Value when activated when all INx (where
1x16) are active that is=1; is 65535. 65535 is the highest boolean value that can be
converted to an integer by the BTIGAPC function block.
508
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
12.4.3
Function block
B16IFCVI
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
OUT
IEC09000624-1-en.vsd
IEC09000624 V1 EN
Figure 240:
12.4.4
Default
Description
BLOCK
BOOLEAN
Block of function
IN1
BOOLEAN
Input 1
IN2
BOOLEAN
Input 2
IN3
BOOLEAN
Input 3
IN4
BOOLEAN
Input 4
IN5
BOOLEAN
Input 5
IN6
BOOLEAN
Input 6
IN7
BOOLEAN
Input 7
IN8
BOOLEAN
Input 8
IN9
BOOLEAN
Input 9
IN10
BOOLEAN
Input 10
IN11
BOOLEAN
Input 11
IN12
BOOLEAN
Input 12
IN13
BOOLEAN
Input 13
IN14
BOOLEAN
Input 14
IN15
BOOLEAN
Input 15
IN16
BOOLEAN
Input 16
509
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Table 314:
Name
OUT
12.4.5
Type
Description
INTEGER
Output value
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
12.5
12.5.1
IEC 61850
identification
IB16
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
Integer to boolean 16 conversion function (IB16) is used to transform an integer into a
set of 16 binary (logical) signals.
12.5.2
Operation principle
With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the
remaining OUTx = 0 for (5x16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the table IB16_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1,
OUT2 has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of
these OUTx is equal to 1 + 2 + 4 + 8 = 15.
This follows the general formulae: The sum of the values of all OUTx = 2x-1 where
1x16 will be equal to the integer value on the input INP.
The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a
value between 0 to 65535 connected to the input INP to a combination of activated
outputs OUTx where 1x16. The sum of the values of all OUTx will then be equal to
the integer on input INP. The values of the different OUTx are according to the table
below. When an OUTx is not activated, its value is 0.
510
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
When all OUTx where 1x16 are activated that is = Boolean 1 it corresponds to that
integer 65535 is connected to input INP. The IB16 function is designed for receiving
the integer input locally. If the BLOCK input is activated, it will freeze the logical
outputs at the last value.
Values of each of the different OUTx from function block IB16 for 1x16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block IB16.
Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
OUT2
BOOLEAN
Output 2
OUT3
BOOLEAN
Output 3
OUT4
BOOLEAN
Output 4
OUT5
BOOLEAN
Output 5
16
OUT6
BOOLEAN
Output 6
32
OUT7
BOOLEAN
Output 7
64
OUT8
BOOLEAN
Output 8
128
OUT9
BOOLEAN
Output 9
256
OUT10
BOOLEAN
Output 10
512
OUT11
BOOLEAN
Output 11
1024
OUT12
BOOLEAN
Output 12
2048
OUT13
BOOLEAN
Output 13
4096
OUT14
BOOLEAN
Output 14
8192
OUT15
BOOLEAN
Output 15
16384
OUT16
BOOLEAN
Output 16
32768
The sum of the numbers in column Value when activated when all OUTx (where x =
1 to 16) are active that is=1; is 65535. 65535 is the highest integer that can be
converted by the IB16 function block.
511
Technical reference manual
Section 12
Logic
12.5.3
1MRK505208-UUS D
Function block
IB16
BLOCK
INP
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
ANSI06000501-1-en.vsd
ANSI06000501 V1 EN
Figure 241:
12.5.4
Default
Description
BLOCK
BOOLEAN
Block of function
INP
INTEGER
INP
Table 316:
Name
Description
OUT1
BOOLEAN
Output 1
OUT2
BOOLEAN
Output 2
OUT3
BOOLEAN
Output 3
OUT4
BOOLEAN
Output 4
OUT5
BOOLEAN
Output 5
OUT6
BOOLEAN
Output 6
OUT7
BOOLEAN
Output 7
OUT8
BOOLEAN
Output 8
OUT9
BOOLEAN
Output 9
OUT10
BOOLEAN
Output 10
OUT11
BOOLEAN
Output 11
OUT12
BOOLEAN
Output 12
OUT13
BOOLEAN
Output 13
Section 12
Logic
1MRK505208-UUS D
Name
12.5.5
Type
Description
OUT14
BOOLEAN
Output 14
OUT15
BOOLEAN
Output 15
OUT16
BOOLEAN
Output 16
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
12.6
12.6.1
IEC 61850
identification
IB16FCVB
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
Integer to boolean conversion with logic node representation function (IB16FCVB) is
used to transform an integer to 16 binary (logic) signals.
IB16FCVB function can receive remote values over IEC61850 depending on the
operator position input (PSTO).
12.6.2
Operation principle
With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the
remaining OUTx = 0 for (5x16).
OUTx represents a value when activated. The value of each of the OUTx is in
accordance with the table ITBGAPC_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1,
OUT2 has a value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of
these OUTx is equal to 1 + 2 + 4 + 8 = 15.
This follows the general formulae: The sum of the values of all OUTx = 2x-1 where
1x16 will be equal to the integer value on the input INP.
513
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
Output signals
Type
Description
Value when
activated
Value when
deactivated
OUT1
BOOLEAN
Output 1
OUT2
BOOLEAN
Output 2
OUT3
BOOLEAN
Output 3
OUT4
BOOLEAN
Output 4
OUT5
BOOLEAN
Output 5
16
OUT6
BOOLEAN
Output 6
32
OUT7
BOOLEAN
Output 7
64
OUT8
BOOLEAN
Output 8
128
OUT9
BOOLEAN
Output 9
256
OUT10
BOOLEAN
Output 10
512
OUT11
BOOLEAN
Output 11
1024
OUT12
BOOLEAN
Output 12
2048
OUT13
BOOLEAN
Output 13
4096
OUT14
BOOLEAN
Output 14
8192
OUT15
BOOLEAN
Output 15
16384
OUT16
BOOLEAN
Output 16
32768
The sum of the numbers in column Value when activated when all OUTx (where x =
1 to 16) are active that is=1; is 65535. 65535 is the highest integer that can be
converted by the ITBGAPC function block.
514
Technical reference manual
Section 12
Logic
1MRK505208-UUS D
The operator position input (PSTO) determines the operator place. The integer number
can be written to the block while in Remote. If PSTO is in Off or Local, then no
change is applied to the outputs.
12.6.3
Function block
IB16FCVB
BLOCK
PSTO
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC09000399-1-en.vsd
IEC09000399 V1 EN
Figure 242:
12.6.4
Default
Description
BLOCK
BOOLEAN
Block of function
PSTO
INTEGER
Table 319:
Name
Description
OUT1
BOOLEAN
Output 1
OUT2
BOOLEAN
Output 2
OUT3
BOOLEAN
Output 3
OUT4
BOOLEAN
Output 4
OUT5
BOOLEAN
Output 5
OUT6
BOOLEAN
Output 6
OUT7
BOOLEAN
Output 7
OUT8
BOOLEAN
Output 8
Section 12
Logic
1MRK505208-UUS D
Name
12.6.5
Type
Description
OUT9
BOOLEAN
Output 9
OUT10
BOOLEAN
Output 10
OUT11
BOOLEAN
Output 11
OUT12
BOOLEAN
Output 12
OUT13
BOOLEAN
Output 13
OUT14
BOOLEAN
Output 14
OUT15
BOOLEAN
Output 15
OUT16
BOOLEAN
Output 16
Setting parameters
This function does not have any setting parameters.
516
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Section 13
Monitoring
13.1
Measurements
Function description
Measurements
IEC 61850
identification
IEC 60617
identification
CVMMXN
ANSI/IEEE C37.2
device number
-
P, Q, S, I, U, f
SYMBOL-RR V1 EN
CMMXU
I
SYMBOL-SS V1 EN
VMMXU
U
SYMBOL-UU V1 EN
CMSQI
VMSQI
I1, I2, I0
SYMBOL-VV V1 EN
U1, U2, U0
SYMBOL-TT V1 EN
VNMMXU
U
SYMBOL-UU V1 EN
517
Technical reference manual
Section 13
Monitoring
13.1.1
1MRK505208-UUS D
Introduction
Measurement functions is used for power system measurement, supervision and
reporting to the local HMI, monitoring tool within PCM600 or to station level for
example, via IEC 61850. The possibility to continuously monitor measured values of
active power, reactive power, currents, voltages, frequency, power factor etc. is vital
for efficient production, transmission and distribution of electrical energy. It provides
to the system operator fast and easy overview of the present status of the power system.
Additionally, it can be used during testing and commissioning of protection and control
IEDs in order to verify proper operation and connection of instrument transformers
(CTs and VTs). During normal service by periodic comparison of the measured value
from the IED with other independent meters the proper operation of the IED analog
measurement chain can be verified. Finally, it can be used to verify proper direction
orientation for distance or directional overcurrent protection function.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
All measured values can be supervised with four settable limits that is, low-low limit,
low limit, high limit and high-high limit. A zero clamping reduction is also supported,
that is, the measured value below a settable limit is forced to zero which reduces the
impact of noise in the inputs.
Dead-band supervision can be used to report measured signal value to station level
when change in measured value is above set threshold limit or time integral of all
changes since the last time value updating exceeds the threshold limit. Measure value
can also be based on periodic reporting.
The measurement function, CVMMXN, provides the following power system quantities:
518
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and magnitude compensation at 5, 30 and
100% of rated current and at 100% of rated voltage.
The power system quantities provided, depends on the actual hardware,
(TRM) and the logic configuration made in PCM600.
The measuring functions CMSQI and VMSQI provide sequence component quantities:
13.1.2
Principle of operation
13.1.2.1
Measurement supervision
The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks.
The number of processed alternate measuring quantities depends on the type of IED
and built-in options.
The information on measured quantities is available for the user at different locations:
All phase angles are presented in relation to a defined reference channel. The General
setting parameter PhaseAngleRef defines the reference.
Measured value below zero point clamping limit is forced to zero. This allows the
noise in the input signal to be ignored. The zero point clamping limit is a general
setting (XZeroDb where X equals S, P, Q, PF, V, I, F, IA, IB, IC, VA, VB, VC, VAB,
VBC, VCA, I1, I2, 3I0, V1, V2 or 3V0). Observe that this measurement supervision
519
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
zero point clamping might be overridden by the zero point clamping used for the
measurement values within CVMMXU.
Users can continuously monitor the measured quantity available in each function block
by means of four defined operating thresholds, see figure 243. The monitoring has two
different modes of operating:
Overfunction, when the measured current exceeds the High limit (XHiLim) or Highhigh limit (XHiHiLim) pre-set values
Underfunction, when the measured current decreases under the Low limit
(XLowLim) or Low-low limit (XLowLowLim) pre-set values.
High-high limit
X_RANGE= 1
Hysteresis
High limit
X_RANGE=0
X_RANGE=0
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
en05000657.vsd
IEC05000657 V1 EN
Figure 243:
Each analog output has one corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: Highhigh limit exceeded, 2: below Low limit and 4: below Low-low limit). The output may
be connected to a measurement expander block (XP (RANGE_XP)) to get
measurement supervision as binary signals.
The logical value of the functional output signals changes according to figure 243.
The user can set the hysteresis (XLimHyst), which determines the difference between
the operating and reset value at each operating point, in wide range for each measuring
channel separately. The hysteresis is common for all operating values within one channel.
520
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting of
the value to the higher levels depends on the selected reporting mode. The following
basic reporting modes are available:
Cyclic reporting
Value Reported
Value Reported
Value Reported
Value Reported
Y3
Y2
Y4
Y1
Y5
t (*)
Value 5
Value 4
t (*)
Value 3
t (*)
Value 2
Value 1
t (*)
en05000500.vsd
IEC05000500 V1 EN
Figure 244:
Periodic reporting
521
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
If a measuring value is changed, compared to the last reported value, and the change is
larger than the Y pre-defined limits that are set by user (XZeroDb), then the
measuring channel reports the new value to a higher level, if this is detected by a new
measured value. This limits the information flow to a minimum necessary. Figure 245
shows an example with the magnitude dead-band supervision. The picture is
simplified: the process is not continuous but the values are evaluated with a time
interval of one execution cycle from each other.
Value Reported
Y
Value Reported
(1st)
Value Reported
Y3
Y2
Y1
Value Reported
DY
DY
DY
DY
DY
DY
t
99000529.vsd
IEC99000529 V1 EN
Figure 245:
After the new value is reported, the Y limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more than
defined by the Y set limits.
The measured value is reported if the time integral of all changes exceeds the pre-set
limit (XDbRepInt), figure 246, where an example of reporting with integral dead-band
supervision is shown. The picture is simplified: the process is not continuous but the
values are evaluated with a time interval of one execution cycle from each other.
The last value reported, Y1 in figure 246 serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
522
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
absolute values of these integral values are added until the pre-set value is exceeded.
This occurs with the value Y2 that is reported and set as a new base for the following
measurements (as well as for the values Y3, Y4 and Y5).
The integral dead-band supervision is particularly suitable for monitoring signals with
small variations that can last for relatively long periods.
A1 >=
pre-set value
Y
A >=
pre-set value
A2 >=
pre-set value
Y3
Y2
Value Reported
(1st)
A1
Value
Reported
A2
Value
Reported
Y1
Y4
Value
Reported
A3 + A4 + A5 + A6 + A7 >=
pre-set value
A4
A3
A5
A6
A7
Y5
Value
Reported
t
99000530.vsd
IEC99000530 V1 EN
Figure 246:
13.1.2.2
Measurements CVMMXN
Mode of operation
523
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
A, B, C
S = VA I A* + VB I B* + VC I C*
EQUATION1561 V1 EN
(
I =( I
V = VA + VB + VC
+ IB + IC
)/
)/3
Comment
EQUATION1562 V1 EN
Arone
S = VAB I A - VBC I C
*
(Equation 63)
EQUATION1563 V1 EN
(
I =( I
V = VAB + VBC / 2
A
EQUATION1564 V1 EN
PosSeq
V =
(Equation 65)
I = I PosSeq
S = 3 VPosSeq I PosSeq
EQUATION1565 V1 EN
AB
S = VAB I A - I B
*
(Equation 67)
EQUATION1567 V1 EN
BC
S = VBC I B - I C
*
(Equation 69)
EQUATION1569 V1 EN
CA
S = VCA I C - I A
*
(Equation 71)
EQUATION1571 V1 EN
EQUATION1573 V1 EN
(Equation 73)
(Equation 68)
Used when only
VBC phase-tophase voltage is
available
V = VBC
I = I B + IC / 2
(Equation 70)
V = VCA
I = IC + I A / 2
V =
S = 3 VA I A
EQUATION1572 V1 EN
(Equation 66)
I = IA + IB / 2
EQUATION1570 V1 EN
V = VAB
EQUATION1568 V1 EN
(Equation 64)
3 VPosSeq
EQUATION1566 V1 EN
+ IC / 2
(Equation 72)
Used when only
VA phase-toground voltage is
available
3 VA
I = IA
EQUATION1574 V1 EN
(Equation 74)
524
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
V =
S = 3 VB I B
*
(Equation 75)
EQUATION1575 V1 EN
3 VB
I = IB
EQUATION1576 V1 EN
V =
S = 3 VC I C
*
EQUATION1577 V1 EN
(Equation 77)
(Equation 76)
3 VC
I = IC
EQUATION1578 V1 EN
Comment
(Equation 78)
It shall be noted that only in the first two operating modes that is, 1 & 2 the
measurement function calculates exact three-phase power. In other operating modes
that is, from 3 to 9 it calculates the three-phase power under assumption that the power
system is fully symmetrical. Once the complex apparent power is calculated then the P,
Q, S, & PF are calculated in accordance with the following formulas:
P = Re( S )
(Equation 79)
EQUATION1403 V1 EN
Q = Im( S )
(Equation 80)
EQUATION1404 V1 EN
S = S =
P +Q
2
EQUATION1405 V1 EN
(Equation 81)
PF = cosj = P
S
EQUATION1406 V1 EN
(Equation 82)
Additionally to the power factor value the two binary output signals from the function
are provided which indicates the angular relationship between current and voltage
phasors. Binary output signal ILAG is set to one when current phasor is lagging behind
voltage phasor. Binary output signal ILEAD is set to one when current phasor is
leading the voltage phasor.
525
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Each analog output has a corresponding supervision level output (X_RANGE). The
output signal is an integer in the interval 0-4, see section "Measurement supervision".
Measured currents and voltages used in the CVMMXN function can be calibrated to
get class 0.5 measuring accuracy. This is achieved by magnitude and angle
compensation at 5, 30 and 100% of rated current and voltage. The compensation below
5% and above 100% is constant and linear in between, see example in figure 247.
% of In
Magnitude
compensation
+10
IMagComp5
Measured
current
IMagComp30
IMagComp100
30
% of In
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
-10
Degrees
100
Angle
compensation
+10
Measured
current
IAngComp30
IAngComp5
IAngComp100
30
100
% of In
-10
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN
Figure 247:
Calibration curves
The first current and voltage phase in the group signals will be used as reference and
the magnitude and angle compensation will be used for related input signals.
In order to minimize the influence of the noise signal on the measurement it is possible
to introduce the recursive, low pass filtering of the measured values for P, Q, S, V, I
and power factor. This will make slower measurement response to the step changes in
526
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
EQUATION1407 V1 EN
where:
X
is a new measured value (that is P, Q, S, V, I or PF) to be given out from the function
XOld
is the measured value given from the measurement function in previous execution cycle
is settable parameter by the end user which influence the filter properties
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is, without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. Appropriate value of k
shall be determined separately for every application. Some typical value for k =0.14.
In order to avoid erroneous measurements when either current or voltage signal is not
present, it is possible for the end user to set the magnitudeIGenZeroDb level for current
and voltage measurement VGenZeroDb is forced to zero. When either current or
voltage measurement is forced to zero automatically the measured values for power (P,
Q and S) and power factor are forced to zero as well. Since the measurement
supervision functionality, included in CVMMXN, is using these values the zero
clamping will influence the subsequent supervision (observe the possibility to do zero
point clamping within measurement supervision, see section "Measurement
supervision").
Compensation facility
In order to compensate for small magnitude and angular errors in the complete
measurement chain (CT error, VT error, IED input transformer errors and so on.) it is
possible to perform on site calibration of the power measurement. This is achieved by
setting the complex constant which is then internally used within the function to
multiply the calculated complex apparent power S. This constant is set as magnitude
(setting parameter PowMagFact, default value 1.000) and angle (setting parameter
PowAngComp, default value 0.0 degrees). Default values for these two parameters are
done in such way that they do not influence internally calculated value (complex
constant has default value 1). In this way calibration, for specific operating range (for
example, around rated power) can be done at site. However, to perform this calibration
it is necessary to have an external power meter with high accuracy class available.
527
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Directionality
Busbar
52
IED
Q
Protected
Object
ANSI05000373_2_en.vsd
ANSI05000373 V2 EN
Figure 248:
Practically, it means that active and reactive power will have positive values when they
flow from the busbar towards the protected object and they will have negative values
when they flow from the protected object towards the busbar.
In some application, for example, when power is measured on the secondary side of the
power transformer it might be desirable, from the end client point of view, to have
actually opposite directional convention for active and reactive power measurements.
This can be easily achieved by setting parameter PowAngComp to value of 180.0
degrees. With such setting the active and reactive power will have positive values
when they flow from the protected object towards the busbar.
Frequency
13.1.2.3
528
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
outputs and IEC 61850. This is achieved by magnitude and angle compensation at 5,
30 and 100% of rated current. The compensation below 5% and above 100% is
constant and linear in between, see figure 247.
Phase currents (magnitude and angle) are available on the outputs and each magnitude
output has a corresponding supervision level output (Ix_RANGE). The supervision
output signal is an integer in the interval 0-4, see section "Measurement supervision".
13.1.2.4
13.1.2.5
13.1.3
Function block
The available function blocks of an IED are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
529
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
CVMMXN
I3P*
U3P*
S
S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE
IEC10000016-1-en.vsd
IEC10000016 V1 EN
Figure 249:
CMMXU
I3P*
I_A
IA_RANGE
IA_ANGL
I_B
IB_RANGE
IB_ANGL
I_C
IC_RANGE
IC_ANGL
ANSI05000699-2-en.vsd
ANSI05000699 V2 EN
Figure 250:
VNMMXU
V3P*
V_A
VA_RANGE
VA_ANGL
V_B
VB_RANGE
VB_ANGL
V_C
VC_RANGE
VC_ANGL
ANSI09000850-1-en.vsd
ANSI09000850 V1 EN
Figure 251:
530
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
VMMXU
V3P*
V_AB
VAB_RANG
VAB_ANGL
V_BC
VBC_RANG
VBC_ANGL
V_CA
VCA_RANG
VCA_ANGL
ANSI05000701-2-en.vsd
ANSI05000701 V2 EN
Figure 252:
CMSQI
I3P*
3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL
IEC05000703-2-en.vsd
IEC05000703 V2 EN
Figure 253:
VMSQI
V3P*
3V0
3V0RANG
3V0ANGL
V1
V1RANG
V1ANGL
V2
V2RANG
V2ANGL
ANSI05000704-2-en.vsd
ANSI05000704 V2 EN
Figure 254:
13.1.4
Default
Description
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
531
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Table 321:
Name
Description
REAL
S_RANGE
INTEGER
P_INST
REAL
Active Power
REAL
P_RANGE
INTEGER
Q_INST
REAL
Reactive Power
REAL
Q_RANGE
INTEGER
PF
REAL
PF_RANGE
INTEGER
ILAG
BOOLEAN
ILEAD
BOOLEAN
REAL
V_RANGE
INTEGER
REAL
I_RANGE
INTEGER
REAL
F_RANGE
INTEGER
Table 322:
Name
I3P
Table 323:
Name
Default
-
Description
Group connection abstract block 1
Description
I_A
REAL
IA_RANGE
INTEGER
IA_ANGL
REAL
I_B
REAL
IB_RANGE
INTEGER
IB_ANGL
REAL
I_C
REAL
IC_RANGE
INTEGER
IC_ANGL
REAL
532
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Table 324:
Name
V3P
Table 325:
Name
Default
GROUP
SIGNAL
Description
Group connection abstract block 5
Description
V_A
REAL
VA_RANGE
INTEGER
VA_ANGL
REAL
V_B
REAL
VB_RANGE
INTEGER
VB_ANGL
REAL
V_C
REAL
VC_RANGE
INTEGER
VC_ANGL
REAL
Table 326:
Name
V3P
Table 327:
Name
Default
-
Description
Group connection abstract block 2
Description
V_AB
REAL
VAB_RANG
INTEGER
VAB_ANGL
REAL
V_BC
REAL
VBC_RANG
INTEGER
VBC_ANGL
REAL
V_CA
REAL
VCA_RANG
INTEGER
VCA_ANGL
REAL
533
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Table 328:
Name
I3P
Table 329:
Name
Default
-
Description
Group connection abstract block 3
Description
3I0
REAL
3I0RANG
INTEGER
3I0ANGL
REAL
I1
REAL
I1RANG
INTEGER
I1 Magnitude range
I1ANGL
REAL
I2
REAL
I2RANG
INTEGER
I2 Magnitude range
I2ANGL
REAL
Table 330:
Name
V3P
Table 331:
Name
Default
-
Description
Group connection abstract block 4
Description
3V0
REAL
3V0RANG
INTEGER
3V0ANGL
REAL
V1
REAL
V1RANG
INTEGER
V1 Magnitude range
V1ANGL
REAL
V1 Magnitude angle
V2
REAL
V2RANG
INTEGER
V2 Magnitude range
V2ANGL
REAL
V2 Magnitude angle
534
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.1.5
Setting parameters
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM600.
Table 332:
Name
Values (Range)
Unit
Step
Default
Description
SLowLim
0.0 - 2000.0
%SB
0.1
80.0
SLowLowLim
0.0 - 2000.0
%SB
0.1
60.0
SMin
0.0 - 2000.0
%SB
0.1
50.0
SMax
0.0 - 2000.0
%SB
0.1
200.0
SRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
PMin
-2000.0 - 2000.0
%SB
0.1
-200.0
PMax
-2000.0 - 2000.0
%SB
0.1
200.0
PRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
QMin
-2000.0 - 2000.0
%SB
0.1
-200.0
QMax
-2000.0 - 2000.0
%SB
0.1
200.0
QRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
PFMin
-1.000 - 1.000
0.001
-1.000
Minimum value
PFMax
-1.000 - 1.000
0.001
1.000
Maximum value
PFRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VMin
0.0 - 200.0
%VB
0.1
50.0
VMax
0.0 - 200.0
%VB
0.1
200.0
VRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
IMin
0.0 - 500.0
%IB
0.1
50.0
IMax
0.0 - 500.0
%IB
0.1
200.0
IRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
FrMin
0.000 - 100.000
Hz
0.001
0.000
Minimum value
FrMax
0.000 - 100.000
Hz
0.001
70.000
Maximum value
535
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
FrRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IBase
1 - 99999
3000
VBase
0.05 - 2000.00
kV
0.05
400.00
SBase
0.05 - 200000.00
MVA
0.05
2080.00
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
A, B, C
PowMagFact
0.000 - 6.000
0.001
1.000
PowAngComp
-180.0 - 180.0
Deg
0.1
0.0
0.000 - 1.000
0.001
0.000
Table 333:
Name
Unit
Step
Default
Description
SDbRepInt
1 - 300
Type
10
SZeroDb
0 - 100000
m%
500
SHiHiLim
0.0 - 2000.0
%SB
0.1
150.0
SHiLim
0.0 - 2000.0
%SB
0.1
120.0
SLimHyst
0.000 - 100.000
0.001
5.000
PDbRepInt
1 - 300
Type
10
PZeroDb
0 - 100000
m%
500
PHiHiLim
-2000.0 - 2000.0
%SB
0.1
150.0
PHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
PLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
PLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
PLimHyst
0.000 - 100.000
0.001
5.000
QDbRepInt
1 - 300
Type
10
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
QZeroDb
0 - 100000
m%
500
QHiHiLim
-2000.0 - 2000.0
%SB
0.1
150.0
QHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
QLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
QLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
QLimHyst
0.000 - 100.000
0.001
5.000
PFDbRepInt
1 - 300
Type
10
PFZeroDb
0 - 100000
m%
500
PFHiHiLim
-1.000 - 1.000
0.001
1.000
PFHiLim
-1.000 - 1.000
0.001
0.800
PFLowLim
-1.000 - 1.000
0.001
-0.800
PFLowLowLim
-1.000 - 1.000
0.001
-1.000
PFLimHyst
0.000 - 100.000
0.001
5.000
VDbRepInt
1 - 300
Type
10
VZeroDb
0 - 100000
m%
500
VHiHiLim
0.0 - 200.0
%VB
0.1
150.0
VHiLim
0.0 - 200.0
%VB
0.1
120.0
VLowLim
0.0 - 200.0
%VB
0.1
80.0
VLowLowLim
0.0 - 200.0
%VB
0.1
60.0
VLimHyst
0.000 - 100.000
0.001
5.000
IDbRepInt
1 - 300
Type
10
IZeroDb
0 - 100000
m%
500
IHiHiLim
0.0 - 500.0
%IB
0.1
150.0
IHiLim
0.0 - 500.0
%IB
0.1
120.0
ILowLim
0.0 - 500.0
%IB
0.1
80.0
ILowLowLim
0.0 - 500.0
%IB
0.1
60.0
ILimHyst
0.000 - 100.000
0.001
5.000
FrDbRepInt
1 - 300
Type
10
FrZeroDb
0 - 100000
m%
500
FrHiHiLim
0.000 - 100.000
Hz
0.001
65.000
FrHiLim
0.000 - 100.000
Hz
0.001
63.000
537
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
FrLowLim
0.000 - 100.000
Hz
0.001
47.000
FrLowLowLim
0.000 - 100.000
Hz
0.001
45.000
FrLimHyst
0.000 - 100.000
0.001
5.000
VGenZeroDb
1 - 100
%VB
IGenZeroDb
1 - 100
%IB
VMagComp5
-10.000 - 10.000
0.001
0.000
VMagComp30
-10.000 - 10.000
0.001
0.000
VMagComp100
-10.000 - 10.000
0.001
0.000
IMagComp5
-10.000 - 10.000
0.001
0.000
IMagComp30
-10.000 - 10.000
0.001
0.000
IMagComp100
-10.000 - 10.000
0.001
0.000
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Table 334:
Name
Unit
Step
Default
Description
IA_DbRepInt
1 - 300
Type
10
Operation
Disabled
Enabled
Disabled
Disbled/Enabled operation
IBase
1 - 99999
3000
IA_Max
0.000 10000000000.000
0.001
1000.000
Maximum value
IA_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
IA_AngDbRepInt
1 - 300
Type
10
IB_DbRepInt
1 - 300
Type
10
IB_Max
0.000 10000000000.000
0.001
1000.000
Maximum value
538
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
IB_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
IB_AngDbRepInt
1 - 300
Type
10
IC_DbRepInt
1 - 300
Type
10
IC_Max
0.000 10000000000.000
0.001
1000.000
Maximum value
IC_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
IC_AngDbRepInt
1 - 300
Type
10
Table 335:
Name
Values (Range)
Unit
Step
Default
Description
IA_ZeroDb
0 - 100000
m%
IA_HiHiLim
0.000 10000000000.000
0.001
900.000
IA_HiLim
0.000 10000000000.000
0.001
800.000
IMagComp5
-10.000 - 10.000
0.001
0.000
IMagComp30
-10.000 - 10.000
0.001
0.000
IA_LowLim
0.000 10000000000.000
0.001
0.000
IA_LowLowLim
0.000 10000000000.000
0.001
0.000
IMagComp100
-10.000 - 10.000
0.001
0.000
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
IA_Min
0.000 10000000000.000
0.001
0.000
Minimum value
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
IA_LimHys
0.000 - 100.000
0.001
5.000
IB_ZeroDb
0 - 100000
m%
IB_HiHiLim
0.000 10000000000.000
0.001
900.000
539
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
IB_HiLim
0.000 10000000000.000
0.001
800.000
IB_LowLim
0.000 10000000000.000
0.001
0.000
IB_LowLowLim
0.000 10000000000.000
0.001
0.000
IB_Min
0.000 10000000000.000
0.001
0.000
Minimum value
IB_LimHys
0.000 - 100.000
0.001
5.000
IC_ZeroDb
0 - 100000
m%
IC_HiHiLim
0.000 10000000000.000
0.001
900.000
IC_HiLim
0.000 10000000000.000
0.001
800.000
IC_LowLim
0.000 10000000000.000
0.001
0.000
IC_LowLowLim
0.000 10000000000.000
0.001
0.000
IC_Min
0.000 10000000000.000
0.001
0.000
Minimum value
IC_LimHys
0.000 - 100.000
0.001
5.000
Table 336:
Name
Unit
Step
Default
Description
VA_DbRepInt
1 - 300
Type
10
Operation
Disabled
Enabled
Disabled
Disbled/Enabled operation
VBase
0.05 - 2000.00
kV
0.05
400.00
VA_Max
0.000 10000000000.000
0.001
300000.000
Maximum value
VA_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VA_LimHys
0.000 - 100.000
0.001
5.000
VA_AnDbRepInt
1 - 300
Type
10
VB_DbRepInt
1 - 300
Type
10
540
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
VB_Max
0.000 10000000000.000
0.001
300000.000
Maximum value
VB_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VB_LimHys
0.000 - 100.000
0.001
5.000
VB_AnDbRepInt
1 - 300
Type
10
VC_DbRepInt
1 - 300
Type
10
VC_Max
0.000 10000000000.000
0.001
300000.000
Maximum value
VC_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VC_LimHys
0.000 - 100.000
0.001
5.000
VC_AnDbRepInt
1 - 300
Type
10
Table 337:
Name
Values (Range)
Unit
Step
Default
Description
VA_ZeroDb
0 - 100000
m%
VA_HiHiLim
0.000 10000000000.000
0.001
260000.000
VA_HiLim
0.000 10000000000.000
0.001
240000.000
VA_LowLim
0.000 10000000000.000
0.001
220000.000
VA_LowLowLim
0.000 10000000000.000
0.001
200000.000
VMagComp100
-10.000 - 10.000
0.001
0.000
VA_Min
0.000 10000000000.000
0.001
0.000
Minimum value
VB_ZeroDb
0 - 100000
m%
VB_HiHiLim
0.000 10000000000.000
0.001
260000.000
VB_HiLim
0.000 10000000000.000
0.001
240000.000
VB_LowLim
0.000 10000000000.000
0.001
220000.000
541
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
VB_LowLowLim
0.000 10000000000.000
0.001
200000.000
VB_Min
0.000 10000000000.000
0.001
0.000
Minimum value
VC_ZeroDb
0 - 100000
m%
VC_HiHiLim
0.000 10000000000.000
0.001
260000.000
VC_HiLim
0.000 10000000000.000
0.001
240000.000
VC_LowLim
0.000 10000000000.000
0.001
220000.000
VC_LowLowLim
0.000 10000000000.000
0.001
200000.000
VC_Min
0.000 10000000000.000
0.001
0.000
Minimum value
Table 338:
Name
Values (Range)
Unit
Step
Default
Description
VAB_DbRepInt
1 - 300
Type
10
Operation
Disabled
Enabled
Disabled
Disbled/Enabled operation
VBase
0.05 - 2000.00
kV
0.05
400.00
VAB_Max
0.000 10000000000.000
0.001
500000.000
Maximum value
VAB_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VAB_AnDbRepInt
1 - 300
Type
10
VBC_DbRepInt
1 - 300
Type
10
VBC_Max
0.000 10000000000.000
0.001
500000.000
Maximum value
VBC_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VBC_AnDbRepInt
1 - 300
Type
10
VCA_DbRepInt
1 - 300
Type
10
542
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
VCA_Max
0.000 10000000000.000
0.001
500000.000
Maximum value
VCA_RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
VCA_AnDbRepInt
1 - 300
Type
10
Table 339:
Name
Values (Range)
Unit
Step
Default
Description
VAB_ZeroDb
0 - 100000
m%
VAB_HiHiLim
0.000 10000000000.000
0.001
450000.000
VAB_HiLim
0.000 10000000000.000
0.001
420000.000
VAB_LowLim
0.000 10000000000.000
0.001
380000.000
VAB_LowLowLim
0.000 10000000000.000
0.001
350000.000
VMagComp100
-10.000 - 10.000
0.001
0.000
VAB_Min
0.000 10000000000.000
0.001
0.000
Minimum value
VAB_LimHys
0.000 - 100.000
0.001
5.000
VBC_ZeroDb
0 - 100000
m%
VBC_HiHiLim
0.000 10000000000.000
0.001
450000.000
VBC_HiLim
0.000 10000000000.000
0.001
420000.000
VBC_LowLim
0.000 10000000000.000
0.001
380000.000
VBC_LowLowLim
0.000 10000000000.000
0.001
350000.000
VBC_Min
0.000 10000000000.000
0.001
0.000
Minimum value
VBC_LimHys
0.000 - 100.000
0.001
5.000
VCA_ZeroDb
0 - 100000
m%
VCA_HiHiLim
0.000 10000000000.000
0.001
450000.000
VCA_HiLim
0.000 10000000000.000
0.001
420000.000
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
VCA_LowLim
0.000 10000000000.000
0.001
380000.000
VCA_LowLowLim
0.000 10000000000.000
0.001
350000.000
VCA_Min
0.000 10000000000.000
0.001
0.000
Minimum value
VCA_LimHys
0.000 - 100.000
0.001
5.000
Table 340:
Name
Unit
Step
Default
Description
3I0DbRepInt
1 - 300
Type
10
3I0Min
0.000 10000000000.000
0.001
0.000
Minimum value
3I0Max
0.000 10000000000.000
0.001
1000.000
Maximum value
3I0RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
3I0LimHys
0.000 - 100.000
0.001
5.000
3I0AngDbRepInt
1 - 300
Type
10
Operation
Disabled
Enabled
Disabled
Disbled/Enabled operation
3I0AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
3I0AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
3I0AngRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
I1DbRepInt
1 - 300
Type
10
I1Min
0.000 10000000000.000
0.001
0.000
Minimum value
I1Max
0.000 10000000000.000
0.001
1000.000
Maximum value
I1RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
I1AngDbRepInt
1 - 300
Type
10
I1AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
544
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
I1AngRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
I2DbRepInt
1 - 300
Type
10
I2Min
0.000 10000000000.000
0.001
0.000
Minimum value
I2Max
0.000 10000000000.000
0.001
1000.000
Maximum value
I2RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
I2LimHys
0.000 - 100.000
0.001
5.000
I2AngDbRepInt
1 - 300
Type
10
I2AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
I2AngRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
Table 341:
Name
Values (Range)
Unit
Step
Default
Description
3I0ZeroDb
0 - 100000
m%
3I0HiHiLim
0.000 10000000000.000
0.001
900.000
3I0HiLim
0.000 10000000000.000
0.001
800.000
3I0LowLim
0.000 10000000000.000
0.001
0.000
3I0LowLowLim
0.000 10000000000.000
0.001
0.000
3I0AngZeroDb
0 - 100000
m%
I1ZeroDb
0 - 100000
m%
I1HiHiLim
0.000 10000000000.000
0.001
900.000
I1HiLim
0.000 10000000000.000
0.001
800.000
I1LowLim
0.000 10000000000.000
0.001
0.000
I1LowLowLim
0.000 10000000000.000
0.001
0.000
545
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
I1LimHys
0.000 - 100.000
0.001
5.000
I1AngZeroDb
0 - 100000
m%
I1AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
I2ZeroDb
0 - 100000
m%
I2HiHiLim
0.000 10000000000.000
0.001
900.000
I2HiLim
0.000 10000000000.000
0.001
800.000
I2LowLim
0.000 10000000000.000
0.001
0.000
I2LowLowLim
0.000 10000000000.000
0.001
0.000
I2AngZeroDb
0 - 100000
m%
I2AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
Table 342:
Name
Unit
Step
Default
Description
3V0DbRepInt
1 - 300
Type
10
3V0Min
0.000 10000000000.000
0.001
0.000
Minimum value
3V0Max
0.000 10000000000.000
0.001
300000.000
Maximum value
3V0RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
3V0LimHys
0.000 - 100.000
0.001
5.000
3V0AngDbRepInt
1 - 300
Type
10
Operation
Disabled
Enabled
Disabled
Disbled/Enabled operation
3V0AngZeroDb
0 - 100000
m%
3V0AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
3V0AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
3V0AngRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
V1DbRepInt
1 - 300
Type
10
546
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
V1Min
0.000 10000000000.000
0.001
0.000
Minimum value
V1Max
0.000 10000000000.000
0.001
300000.000
Maximum value
V1RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
V1LimHys
0.000 - 100.000
0.001
5.000
V1AngDbRepInt
1 - 300
Type
10
V2DbRepInt
1 - 300
Type
10
V2Min
0.000 10000000000.000
0.001
0.000
Minimum value
V2Max
0.000 10000000000.000
0.001
300000.000
Maximum value
V2RepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
V2LimHys
0.000 - 100.000
0.001
5.000
V2AngDbRepInt
1 - 300
Type
10
V2AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
V2AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
V2AngRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
UAmpPreComp5
-10.000 - 10.000
0.001
0.000
UAmpPreComp30
-10.000 - 10.000
0.001
0.000
UAmpPreComp100
-10.000 - 10.000
0.001
0.000
Table 343:
Name
Values (Range)
Unit
Step
Default
Description
3V0ZeroDb
0 - 100000
m%
3V0HiHiLim
0.000 10000000000.000
0.001
260000.000
3V0HiLim
0.000 10000000000.000
0.001
240000.000
547
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
3V0LowLim
0.000 10000000000.000
0.001
220000.000
3V0LowLowLim
0.000 10000000000.000
0.001
200000.000
V1ZeroDb
0 - 100000
m%
V1HiHiLim
0.000 10000000000.000
0.001
260000.000
V1HiLim
0.000 10000000000.000
0.001
240000.000
V1LowLim
0.000 10000000000.000
0.001
220000.000
V1LowLowLim
0.000 10000000000.000
0.001
200000.000
V1AngZeroDb
0 - 100000
m%
V1AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
V1AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
V1AngRepTyp
Cyclic
Dead band
Int deadband
Cyclic
Reporting type
V2ZeroDb
0 - 100000
m%
V2HiHiLim
0.000 10000000000.000
0.001
260000.000
V2HiLim
0.000 10000000000.000
0.001
240000.000
V2LowLim
0.000 10000000000.000
0.001
220000.000
V2LowLowLim
0.000 10000000000.000
0.001
200000.000
V2AngZeroDb
0 - 100000
m%
13.1.6
Technical data
Table 344:
Function
Range or value
Accuracy
Frequency
(0.95-1.05) fn
2.0 mHz
Voltage
(0.1-1.5) Vn
0.5% of Vn at VVn
0.5% of V at V > Vn
Connected current
(0.2-4.0) In
0.5% of In at I In
0.5% of I at I > In
548
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Function
Range or value
Active power, P
Reactive power, Q
Apparent power, S
Table 345:
Accuracy
1.0% of Sn at S Sn
1.0% of S at S > Sn
Conditions:
0.8 x Vn < V < 1.2 Vn
0.2 x In < I < 1.2 In
0.02
Function
Range or value
Current
(0.1-4.0) In
0.2% of In at I 0.5 In
0.2% of I at I > 0.5 In
Phase angle
(0.14.0) x In
Table 346:
Accuracy
Function
Range or value
Voltage
(10 to 300) V
0.3% of V at V 50 V
0.2% of V at V > 50 V
Phase angle
(10 to 300) V
0.3 at V 50 V
0.2 at V > 50 V
Table 347:
Accuracy
Function
Range or value
Voltage
(10 to 300) V
0.3% of V at V 50 V
0.2% of V at V > 50 V
Phase angle
(10 to 300) V
0.3 at V 50 V
0.2 at V > 50 V
Accuracy
549
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Table 348:
Function
Range or value
Accuracy
(0.14.0) In
0.2% of In at I 0.5 In
0.2% of I at I > 0.5 In
(0.11.0) In
0.2% of In at I 0.5 In
0.2% of I at I > 0.5 In
(0.11.0) In
0.2% of In at I 0.5 In
0.2% of I at I > 0.5 In
Phase angle
(0.14.0) In
Table 349:
Function
Range or value
Accuracy
(10 to 300) V
0.3% of V at V 50 V
0.2% of V at V > 50 V
(10 to 300) V
0.3% of V at V 50 V
0.2% of V at V > 50 V
(10 to 300) V
0.3% of V at V 50 V
0.2% of V at V > 50 V
Phase angle
(10 to 300) V
0.3 at V 50 V
0.2 at V > 50 V
13.2
13.2.1
Identification
Function description
Event counter
IEC 61850
identification
IEC 60617
identification
CNTGGIO
ANSI/IEEE C37.2
device number
-
S00946 V1 EN
13.2.2
Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number of
times each counter input has been activated.
550
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.2.3
Principle of operation
Event counter (CNTGGIO) has six counter inputs. CNTGGIO stores how many times
each of the inputs has been activated. The counter memory for each of the six inputs is
updated, giving the total number of times the input has been activated, as soon as an
input is activated.
To not risk that the flash memory is worn out due to too many writings, a mechanism
for limiting the number of writings per time period is included in the product. This
however gives as a result that it can take long time, up to several minutes, before a new
value is stored in the flash memory. And if a new CNTGGIO value is not stored before
auxiliary power interruption, it will be lost. CNTGGIO stored values in flash memory
will however not be lost at an auxiliary power interruption.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked. The input can for example, be used for blocking the counters at
testing.The function block has an input RESET. At activation of this input all six
counters are set to 0.
All inputs are configured via PCM600.
13.2.3.1
Reporting
The content of the counters can be read in the local HMI.
Reset of counters can be performed in the local HMI and a binary input.
Reading of content can also be performed remotely, for example from a IEC 61850
client. The value can also be presented as a measuring value on the local HMI
graphical display.
13.2.3.2
Design
The function block has six inputs for increasing the counter values for each of the six
counters respectively. The content of the counters are stepped one step for each
positive edge of the input respectively.
The function block also has an input BLOCK. At activation of this input all six
counters are blocked and are not updated. Valid number is held.
The function block has an input RESET. At activation of this input all six counters are
set to 0.
551
Technical reference manual
Section 13
Monitoring
13.2.4
1MRK505208-UUS D
Function block
CNTGGIO
BLOCK
COUNTER1
COUNTER2
COUNTER3
COUNTER4
COUNTER5
COUNTER6
RESET
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6
IEC05000345-2-en.vsd
IEC05000345 V2 EN
Figure 255:
13.2.5
Input signals
Table 350:
Name
Default
Description
BLOCK
BOOLEAN
Block of function
COUNTER1
BOOLEAN
COUNTER2
BOOLEAN
COUNTER3
BOOLEAN
COUNTER4
BOOLEAN
COUNTER5
BOOLEAN
COUNTER6
BOOLEAN
RESET
BOOLEAN
Reset of function
Table 351:
Name
Description
VALUE1
INTEGER
Output of counter1
VALUE2
INTEGER
Output of counter2
VALUE3
INTEGER
Output of counter3
VALUE4
INTEGER
Output of counter4
VALUE5
INTEGER
Output of counter5
VALUE6
INTEGER
Output of counter6
552
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.2.6
Table 352:
Setting parameters
CNTGGIO Group settings (basic)
Name
Operation
13.2.7
Values (Range)
Unit
Disabled
Enabled
Step
Disabled
Description
Disable/Enable Operation
Technical data
Table 353:
Function
13.3
Default
Range or value
Accuracy
Counter value
0-100000
IEC 61850
identification
IEC 60617
identification
EVENT
ANSI/IEEE C37.2
device number
-
S00946 V1 EN
13.3.1
Introduction
When using a Substation Automation system with LON or SPA communication, timetagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT). The event function block is used for remote communication.
Analog and double indication values are also transferred through EVENT function.
13.3.2
Principle of operation
The main purpose of the event function (EVENT) is to generate events when the state
or value of any of the connected input signals is in a state, or is undergoing a state
transition, for which event generation is enabled.
Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a
name from the Application Configuration tool. The inputs are normally used to create
single events, but are also intended for double indication events.
553
Section 13
Monitoring
1MRK505208-UUS D
EVENT function also has an input BLOCK to block the generation of events.
The events that are sent from the IED can originate from both internal logical signals
and binary input channels. The internal signals are time-tagged in the main processing
module, while the binary input channels are time-tagged directly on the input module.
The time-tagging of the events that are originated from internal logical signals have a
resolution corresponding to the execution cyclicity of EVENT function. The timetagging of the events that are originated from binary input signals have a resolution of
1 ms.
The outputs from EVENT function are formed by the reading of status, events and
alarms by the station level on every single input. The user-defined name for each input
is intended to be used by the station level.
All events according to the event mask are stored in a buffer, which contains up to
1000 events. If new events appear before the oldest event in the buffer is read, the
oldest event is overwritten and an overflow alarm appears.
The events are produced according to the set-event masks. The event masks are treated
commonly for both the LON and SPA communication. The EventMask can be set
individually for each input channel. These settings are available:
NoEvents
OnSet
OnReset
OnChange
AutoDetect
It is possible to define which part of EVENT function generates the events. This can be
performed individually for the SPAChannelMask and LONChannelMask respectively.
For each communication type these settings are available:
Disabled
Channel 1-8
Channel 9-16
Channel 1-16
For LON communication the events normally are sent to station level at change. It is
possibly also to set a time for cyclic sending of the events individually for each input
channel.
To protect the SA system from signals with a high change rate that can easily saturate
the event system or the communication subsystems behind it, a quota limiter is
implemented. If an input creates events at a rate that completely consume the granted
quota then further events from the channel will be blocked. This block will be removed
554
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
when the input calms down and the accumulated quota reach 66% of the maximum
burst quota. The maximum burst quota per input channel is 45 events per second.
13.3.3
Function block
EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000697-2-en.vsd
IEC05000697 V2 EN
Figure 256:
13.3.4
Default
Description
BLOCK
BOOLEAN
Block of function
INPUT1
GROUP
SIGNAL
Input 1
INPUT2
GROUP
SIGNAL
Input 2
INPUT3
GROUP
SIGNAL
Input 3
INPUT4
GROUP
SIGNAL
Input 4
INPUT5
GROUP
SIGNAL
Input 5
INPUT6
GROUP
SIGNAL
Input 6
INPUT7
GROUP
SIGNAL
Input 7
INPUT8
GROUP
SIGNAL
Input 8
INPUT9
GROUP
SIGNAL
Input 9
Section 13
Monitoring
1MRK505208-UUS D
Name
13.3.5
Table 355:
Type
Default
Description
INPUT10
GROUP
SIGNAL
Input 10
INPUT11
GROUP
SIGNAL
Input 11
INPUT12
GROUP
SIGNAL
Input 12
INPUT13
GROUP
SIGNAL
Input 13
INPUT14
GROUP
SIGNAL
Input 14
INPUT15
GROUP
SIGNAL
Input 15
INPUT16
GROUP
SIGNAL
Input 16
Setting parameters
EVENT Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SPAChannelMask
Disabled
Channel 1-8
Channel 9-16
Channel 1-16
Disabled
LONChannelMask
Disabled
Channel 1-8
Channel 9-16
Channel 1-16
Disabled
EventMask1
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask2
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask3
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask4
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
556
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
EventMask5
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask6
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask7
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask8
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask9
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask10
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask11
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask12
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask13
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask14
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
557
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
EventMask15
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
EventMask16
NoEvents
OnSet
OnReset
OnChange
AutoDetect
AutoDetect
MinRepIntVal1
0 - 3600
MinRepIntVal2
0 - 3600
MinRepIntVal3
0 - 3600
MinRepIntVal4
0 - 3600
MinRepIntVal5
0 - 3600
MinRepIntVal6
0 - 3600
MinRepIntVal7
0 - 3600
MinRepIntVal8
0 - 3600
MinRepIntVal9
0 - 3600
MinRepIntVal10
0 - 3600
MinRepIntVal11
0 - 3600
MinRepIntVal12
0 - 3600
MinRepIntVal13
0 - 3600
MinRepIntVal14
0 - 3600
MinRepIntVal15
0 - 3600
MinRepIntVal16
0 - 3600
13.4
13.4.1
IEC 61850
identification
BINSTATREP
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
The Logical signal status report (BINSTATREP) function makes it possible for a SPA
master to poll signals from various other functions.
558
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.4.2
Principle of operation
The Logical signal status report (BINSTATREP) function has 16 inputs and 16
outputs. The output status follows the inputs and can be read from the local HMI or via
SPA communication.
When an input is set, the respective output is set for a user defined time. If the input
signal remains set for a longer period, the output will remain set until the input signal
resets.
INPUTn
OUTPUTn
t
t
IEC09000732-1-en.vsd
IEC09000732 V1 EN
Figure 257:
13.4.3
Function block
BINSTATREP
OUTPUT1
BLOCK
^INPUT1
OUTPUT2
^INPUT2
OUTPUT3
^INPUT3
OUTPUT4
^INPUT4
OUTPUT5
^INPUT5
OUTPUT6
^INPUT6
OUTPUT7
^INPUT7
OUTPUT8
^INPUT8
OUTPUT9
^INPUT9
OUTPUT10
^INPUT10
OUTPUT11
^INPUT11
OUTPUT12
^INPUT12
OUTPUT13
^INPUT13
OUTPUT14
^INPUT14
OUTPUT15
^INPUT15
OUTPUT16
^INPUT16
IEC09000730-1-en.vsd
IEC09000730 V1 EN
Figure 258:
559
Technical reference manual
Section 13
Monitoring
13.4.4
1MRK505208-UUS D
Default
Description
BLOCK
BOOLEAN
Block of function
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
INPUT5
BOOLEAN
INPUT6
BOOLEAN
INPUT7
BOOLEAN
INPUT8
BOOLEAN
INPUT9
BOOLEAN
INPUT10
BOOLEAN
INPUT11
BOOLEAN
INPUT12
BOOLEAN
INPUT13
BOOLEAN
INPUT14
BOOLEAN
INPUT15
BOOLEAN
INPUT16
BOOLEAN
Table 357:
Name
Description
OUTPUT1
BOOLEAN
OUTPUT2
BOOLEAN
OUTPUT3
BOOLEAN
OUTPUT4
BOOLEAN
OUTPUT5
BOOLEAN
OUTPUT6
BOOLEAN
OUTPUT7
BOOLEAN
OUTPUT8
BOOLEAN
OUTPUT9
BOOLEAN
OUTPUT10
BOOLEAN
OUTPUT11
BOOLEAN
OUTPUT12
BOOLEAN
OUTPUT13
BOOLEAN
Section 13
Monitoring
1MRK505208-UUS D
Name
13.4.5
Table 358:
Type
Description
OUTPUT14
BOOLEAN
OUTPUT15
BOOLEAN
OUTPUT16
BOOLEAN
Setting parameters
BINSTATREP Non group settings (basic)
Name
t
13.5
Values (Range)
0.000 - 60000.000
Unit
s
Step
0.001
10.000
Description
Time delay of function
13.5.1
Default
IEC 61850
identification
RANGE_XP
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Introduction
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-high
limit. The measure value expander block (RANGE_XP) has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary signals:
below low-low limit, below low limit, normal, above high-high limit or above high
limit. The output signals can be used as conditions in the configurable logic or for
alarming purpose.
13.5.2
Principle of operation
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according
to table 359.
561
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Table 359:
Measured supervised
value is:
Output:
LOWLOW
between low
and high limit
High
LOW
High
NORMAL
High
HIGH
High
HIGHHIGH
13.5.3
High
Function block
RANGE*
RANGE_XP
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346-2-en.vsd
IEC05000346 V2 EN
Figure 259:
13.5.4
Table 361:
Name
13.6
Default
0
Description
Measured value range
Description
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN
562
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Function description
13.6.1
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
A41RADR
Disturbance report
DRPRDRE
Disturbance report
A1RADR
Disturbance report
A4RADR
Disturbance report
B1RBDR
Introduction
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of
all selected analog input and binary signals connected to the function block with a,
maximum of 40 analog and 96 binary signals.
The Disturbance report functionality is a common name for several functions:
Sequential of events
Indications
Event recorder
Trip value recorder
Disturbance recorder
563
Technical reference manual
Section 13
Monitoring
13.6.2
1MRK505208-UUS D
Principle of operation
Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:
Figure 260 shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events (SOE), Event recorder (ER) and Indications
(IND) uses information from the binary input function blocks (BxRBDR). Trip value
recorder (TVR) uses analog information from the analog input function blocks
(AxRADR). Disturbance recorder DRPRDRE acquires information from both
AxRADR and BxRBDR.
A1-4RADR
A4RADR
Disturbance Report
DRPRDRE
Analog signals
Trip value rec
B1-6RBDR
Binary signals
Disturbance
recorder
B6RBDR
Sequential of
events
Event recorder
Indications
ANSI09000337-1-en.vsd
ANSI09000337 V1 EN
Figure 260:
564
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
The whole disturbance report can contain information for a number of recordings, each
with the data coming from all the parts mentioned above. The sequential of events
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary power.
Each report will get an identification number in the interval from 0-999.
Disturbance report
Record no. N
General dist.
information
Indications
Trip
values
Event
recordings
Disturbance
recording
Event list
(SOE)
en05000161_ansi.vsd
ANSI05000161 V1 EN
Figure 261:
565
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Number of recordings
100
3.4s
20 analog
96 binary
3.4s
80
40 analog
96 binary
60
6.3s
6.3s
50 Hz
6.3s
40
60 Hz
300
350
400 s
en05000488_ansi.vsd
ANSI05000488 V1 EN
Figure 262:
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk space.
Disturbance information
Date and time of the disturbance, the indications, events, fault location and the trip
values are available on the local HMI. To acquire a complete disturbance report the
user must use a PC and - either the PCM600 Disturbance handling tool - or a FTP or
MMS (over 61850) client. The PC can be connected to the IED front, rear or remotely
via the station bus (Ethernet ports).
Indications (IND)
Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged), see section "Indications" for more detailed information.
566
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
The event recorder may contain a list of up to 150 time-tagged events, which have
occurred during the disturbance. The information is available via the local HMI or
PCM600, see section "Event recorder" for more detailed information.
The sequetial of events may contain a list of totally 1000 time-tagged events. The list
information is continuously updated when selected binary signals change state. The
oldest data is overwritten. The logged signals may be presented via local HMI or
PCM600, see section "Sequential of events" for more detailed information.
The recorded trip values include phasors of selected analog signals before the fault and
during the fault, see section "Trip value recorder" for more detailed information.
Disturbance recorder records analog and binary signal data before, during and after the
fault, see section "Disturbance recorder" for more detailed information.
Time tagging
The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report
Recording times
567
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Trig point
TimeLimit
PreFaultRecT
PostFaultRecT
3
en05000487.vsd
IEC05000487 V1 EN
Figure 263:
PreFaultRecT, 1
Pre-fault or pre-trigger recording time. The time before the fault including the operate
time of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2
Fault time of the recording. The fault time cannot be set. It continues as long as any
valid trigger condition, binary or analog, persists (unless limited by TimeLimit the limit
time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit
Limit time. The maximum allowed recording time after the disturbance recording was
triggered. The limit time is used to eliminate the consequences of a trigger that does
not reset within a reasonable time interval. It limits the maximum recording time of a
recording and prevents subsequent overwriting of already stored disturbances. Use the
setting TimeLimit to set this time.
Analog signals
Up to 40 analog signals can be selected for recording by the Disturbance recorder and
triggering of the Disturbance report function. Out of these 40, 30 are reserved for
external analog signals from analog input modules (TRM) and line data
communication module (LDCM) via preprocessing function blocks (SMAI) and
summation block (3PHSUM). The last 10 channels may be connected to internally
calculated analog signals available as function block output signals (mA input signals,
phase differential currents, bias currents and so on).
568
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
A1RADR
SMAI
External analog
signals
Block
^GRP2_A
AI3P
AI1
^GRP2_B
^GRP2_C
AI2
AI3
INPUT2
^GRP2_N
Type
AI4
AIN
INPUT4
A2RADR
INPUT1
A3RADR
INPUT3
INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40
ANSI10000029-1-en.vsd
ANSI10000029 V1 EN
Figure 264:
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated according to
the cycle time of the specific function. If a function is running at lower speed than the
base sampling rate, Disturbance recorder will use the latest updated sample until a new
updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration). In
case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used). SMAI makes the
information available as a group signal output, phase outputs and calculated residual
output (AIN-output). In situations where AI4-input is used as an input signal the
corresponding information is available on the non-calculated output (AI4) on the
SMAI function block. Connect the signals to the AxRADR accordingly.
569
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
For each of the analog signals, Operation = Enabled means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of Operation, and
triggers even if operation is set to Disabled. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
If Operation = Disabled, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If Operation = Enabled, waveform (samples) will also be recorded and reported in graph.
The analog signals are presented only in the disturbance recording, but they affect the
entire disturbance report when being used as triggers.
Binary signals
Each of the 96 signals can be selected as a trigger of the disturbance report (Operation
= Operation>TrigDR =Disabled). A binary signal can be selected to activate the red
LED on the local HMI (SetLED = Enabled/Disabled).
The selected signals are presented in the event recorder, sequential of events and the
disturbance recording. But they affect the whole disturbance report when they are used
as triggers. The indications are also selected from these 96 signals with local HMI
IndicationMask=Show/Hide.
Trigger signals
The trigger conditions affect the entire disturbance report, except the sequential of
events, which runs continuously. As soon as at least one trigger condition is fulfilled, a
complete disturbance report is recorded. On the other hand, if no trigger condition is
fulfilled, there is no disturbance report, no indications, and so on. This implies the
importance of choosing the right signals as trigger conditions.
A trigger can be of type:
Manual trigger
Binary-signal trigger
Analog-signal trigger (over/under function)
570
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Manual trigger
A disturbance report can be manually triggered from the local HMI, PCM600 or via
station bus (IEC 61850). When the trigger is activated, the manual trigger signal is
generated. This feature is especially useful for testing. Refer to the operator's manual
for procedure.
Binary-signal trigger
Any binary signal state (logic one or a logic zero) can be selected to generate a trigger
(Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to generate a trigger
from a logic zero, the selected signal will not be listed in the indications list of the
disturbance report.
Analog-signal trigger
All analog signals are available for trigger purposes, no matter if they are recorded in
the disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp,
OverTrigLe and UnderTrigLe.
The check of the trigger condition is based on peak-to-peak values. When this is found,
the absolute average value of these two peak values is calculated. If the average value
is above the threshold level for an overvoltage or overcurrent trigger, this trigger is
indicated with a greater than (>) sign with the user-defined name.
If the average value is below the set threshold level for an undervoltage or undercurrent
trigger, this trigger is indicated with a less than (<) sign with its name. The procedure
is separately performed for each channel.
This method of checking the analog trigger conditions gives a function which is
insensitive to DC offset in the signal. The operate time for this initiation is typically in
the range of one cycle, 16 2/3 ms for a 60 Hz network.
All under/over trig signal information is available on the local HMI and PCM600.
Post Retrigger
Disturbance report function does not automatically respond to any new trig condition
during a recording, after all signals set as trigger signals have been reset. However,
under certain circumstances the fault condition may reoccur during the post-fault
recording, for instance by automatic reclosing to a still faulty power line.
In order to capture the new disturbance it is possible to allow retriggering (PostRetrig
= Enabled) during the post-fault time. In this case a new, complete recording will start
and, during a period, run in parallel with the initial recording.
When the retrig parameter is disabled (PostRetrig = Disabled), a new recording will
not start until the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a
new trig occurs during the post-fault period and lasts longer than the proceeding
recording a new complete recording will be started.
571
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.6.3
Function block
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC05000406-3-en.vsd
IEC05000406 V3 EN
Figure 265:
A1RADR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
IEC05000430-3-en.vsd
IEC05000430 V3 EN
Figure 266:
A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40
IEC05000431-3-en.vsd
IEC05000431 V3 EN
Figure 267:
572
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC05000432-3-en.vsd
IEC05000432 V3 EN
Figure 268:
13.6.4
Description
DRPOFF
BOOLEAN
RECSTART
BOOLEAN
RECMADE
BOOLEAN
CLEARED
BOOLEAN
MEMUSED
BOOLEAN
Table 363:
Name
Default
Description
INPUT1
GROUP
SIGNAL
INPUT2
GROUP
SIGNAL
INPUT3
GROUP
SIGNAL
INPUT4
GROUP
SIGNAL
INPUT5
GROUP
SIGNAL
INPUT6
GROUP
SIGNAL
INPUT7
GROUP
SIGNAL
573
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Type
Default
Description
INPUT8
GROUP
SIGNAL
INPUT9
GROUP
SIGNAL
INPUT10
GROUP
SIGNAL
Table 364:
Name
Default
Description
INPUT31
REAL
Analog channel 31
INPUT32
REAL
Analog channel 32
INPUT33
REAL
Analog channel 33
INPUT34
REAL
Analog channel 34
INPUT35
REAL
Analog channel 35
INPUT36
REAL
Analog channel 36
INPUT37
REAL
Analog channel 37
INPUT38
REAL
Analog channel 38
INPUT39
REAL
Analog channel 39
INPUT40
REAL
Analog channel 40
Table 365:
Name
Default
Description
INPUT1
BOOLEAN
Binary channel 1
INPUT2
BOOLEAN
Binary channel 2
INPUT3
BOOLEAN
Binary channel 3
INPUT4
BOOLEAN
Binary channel 4
INPUT5
BOOLEAN
Binary channel 5
INPUT6
BOOLEAN
Binary channel 6
INPUT7
BOOLEAN
Binary channel 7
INPUT8
BOOLEAN
Binary channel 8
INPUT9
BOOLEAN
Binary channel 9
INPUT10
BOOLEAN
Binary channel 10
INPUT11
BOOLEAN
Binary channel 11
INPUT12
BOOLEAN
Binary channel 12
INPUT13
BOOLEAN
Binary channel 13
574
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
13.6.5
Table 366:
Type
Default
Description
INPUT14
BOOLEAN
Binary channel 14
INPUT15
BOOLEAN
Binary channel 15
INPUT16
BOOLEAN
Binary channel 16
Setting parameters
DRPRDRE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
PreFaultRecT
0.05 - 9.90
0.01
0.10
PostFaultRecT
0.1 - 10.0
0.1
0.5
TimeLimit
0.5 - 10.0
0.1
1.0
PostRetrig
Disabled
Enabled
Disabled
ZeroAngleRef
1 - 30
Ch
OpModeTest
Disabled
Enabled
Disabled
Table 367:
Name
Values (Range)
Unit
Step
Default
Description
Operation01
Disabled
Enabled
Disabled
Operation On/Off
NomValue01
0.0 - 999999.9
0.1
0.0
UnderTrigOp01
Disabled
Enabled
Disabled
UnderTrigLe01
0 - 200
50
OverTrigOp01
Disabled
Enabled
Disabled
OverTrigLe01
0 - 5000
200
Operation02
Disabled
Enabled
Disabled
Operation On/Off
NomValue02
0.0 - 999999.9
0.1
0.0
UnderTrigOp02
Disabled
Enabled
Disabled
UnderTrigLe02
0 - 200
50
575
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
OverTrigOp02
Disabled
Enabled
Disabled
OverTrigLe02
0 - 5000
200
Operation03
Disabled
Enabled
Disabled
Operation On/Off
NomValue03
0.0 - 999999.9
0.1
0.0
UnderTrigOp03
Disabled
Enabled
Disabled
UnderTrigLe03
0 - 200
50
OverTrigOp03
Disabled
Enabled
Disabled
OverTrigLe03
0 - 5000
200
Operation04
Disabled
Enabled
Disabled
Operation On/Off
NomValue04
0.0 - 999999.9
0.1
0.0
UnderTrigOp04
Disabled
Enabled
Disabled
UnderTrigLe04
0 - 200
50
OverTrigOp04
Disabled
Enabled
Disabled
OverTrigLe04
0 - 5000
200
Operation05
Disabled
Enabled
Disabled
Operation On/Off
NomValue05
0.0 - 999999.9
0.1
0.0
UnderTrigOp05
Disabled
Enabled
Disabled
UnderTrigLe05
0 - 200
50
OverTrigOp05
Disabled
Enabled
Disabled
OverTrigLe05
0 - 5000
200
Operation06
Disabled
Enabled
Disabled
Operation On/Off
NomValue06
0.0 - 999999.9
0.1
0.0
UnderTrigOp06
Disabled
Enabled
Disabled
UnderTrigLe06
0 - 200
50
OverTrigOp06
Disabled
Enabled
Disabled
OverTrigLe06
0 - 5000
200
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Operation07
Disabled
Enabled
Disabled
Operation On/Off
NomValue07
0.0 - 999999.9
0.1
0.0
UnderTrigOp07
Disabled
Enabled
Disabled
UnderTrigLe07
0 - 200
50
OverTrigOp07
Disabled
Enabled
Disabled
OverTrigLe07
0 - 5000
200
Operation08
Disabled
Enabled
Disabled
Operation On/Off
NomValue08
0.0 - 999999.9
0.1
0.0
UnderTrigOp08
Disabled
Enabled
Disabled
UnderTrigLe08
0 - 200
50
OverTrigOp08
Disabled
Enabled
Disabled
OverTrigLe08
0 - 5000
200
Operation09
Disabled
Enabled
Disabled
Operation On/Off
NomValue09
0.0 - 999999.9
0.1
0.0
UnderTrigOp09
Disabled
Enabled
Disabled
UnderTrigLe09
0 - 200
50
OverTrigOp09
Disabled
Enabled
Disabled
OverTrigLe09
0 - 5000
200
Operation10
Disabled
Enabled
Disabled
Operation On/Off
NomValue10
0.0 - 999999.9
0.1
0.0
UnderTrigOp10
Disabled
Enabled
Disabled
UnderTrigLe10
0 - 200
50
OverTrigOp10
Disabled
Enabled
Disabled
OverTrigLe10
0 - 5000
200
577
Technical reference manual
Section 13
Monitoring
Table 368:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
Operation31
Disabled
Enabled
Disabled
Operation On/off
NomValue31
0.0 - 999999.9
0.1
0.0
UnderTrigOp31
Disabled
Enabled
Disabled
UnderTrigLe31
0 - 200
50
OverTrigOp31
Disabled
Enabled
Disabled
OverTrigLe31
0 - 5000
200
Operation32
Disabled
Enabled
Disabled
Operation On/off
NomValue32
0.0 - 999999.9
0.1
0.0
UnderTrigOp32
Disabled
Enabled
Disabled
UnderTrigLe32
0 - 200
50
OverTrigOp32
Disabled
Enabled
Disabled
OverTrigLe32
0 - 5000
200
Operation33
Disabled
Enabled
Disabled
Operation On/off
NomValue33
0.0 - 999999.9
0.1
0.0
UnderTrigOp33
Disabled
Enabled
Disabled
UnderTrigLe33
0 - 200
50
OverTrigOp33
Disabled
Enabled
Disabled
OverTrigLe33
0 - 5000
200
Operation34
Disabled
Enabled
Disabled
Operation On/off
NomValue34
0.0 - 999999.9
0.1
0.0
UnderTrigOp34
Disabled
Enabled
Disabled
UnderTrigLe34
0 - 200
50
OverTrigOp34
Disabled
Enabled
Disabled
578
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
OverTrigLe34
0 - 5000
200
Operation35
Disabled
Enabled
Disabled
Operation On/off
NomValue35
0.0 - 999999.9
0.1
0.0
UnderTrigOp35
Disabled
Enabled
Disabled
UnderTrigLe35
0 - 200
50
OverTrigOp35
Disabled
Enabled
Disabled
OverTrigLe35
0 - 5000
200
Operation36
Disabled
Enabled
Disabled
Operation On/off
NomValue36
0.0 - 999999.9
0.1
0.0
UnderTrigOp36
Disabled
Enabled
Disabled
UnderTrigLe36
0 - 200
50
OverTrigOp36
Disabled
Enabled
Disabled
OverTrigLe36
0 - 5000
200
Operation37
Disabled
Enabled
Disabled
Operation On/off
NomValue37
0.0 - 999999.9
0.1
0.0
UnderTrigOp37
Disabled
Enabled
Disabled
UnderTrigLe37
0 - 200
50
OverTrigOp37
Disabled
Enabled
Disabled
OverTrigLe37
0 - 5000
200
Operation38
Disabled
Enabled
Disabled
Operation On/off
NomValue38
0.0 - 999999.9
0.1
0.0
UnderTrigOp38
Disabled
Enabled
Disabled
UnderTrigLe38
0 - 200
50
OverTrigOp38
Disabled
Enabled
Disabled
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
OverTrigLe38
0 - 5000
200
Operation39
Disabled
Enabled
Disabled
Operation On/off
NomValue39
0.0 - 999999.9
0.1
0.0
UnderTrigOp39
Disabled
Enabled
Disabled
UnderTrigLe39
0 - 200
50
OverTrigOp39
Disabled
Enabled
Disabled
OverTrigLe39
0 - 5000
200
Operation40
Disabled
Enabled
Disabled
Operation On/off
NomValue40
0.0 - 999999.9
0.1
0.0
UnderTrigOp40
Disabled
Enabled
Disabled
UnderTrigLe40
0 - 200
50
OverTrigOp40
Disabled
Enabled
Disabled
OverTrigLe40
0 - 5000
200
Table 369:
Name
Unit
Step
Default
Description
Operation01
Disabled
Enabled
Disabled
TrigLevel01
Trig on 0
Trig on 1
Trig on 1
IndicationMa01
Hide
Show
Hide
SetLED01
Disabled
Enabled
Disabled
Operation02
Disabled
Enabled
Disabled
TrigLevel02
Trig on 0
Trig on 1
Trig on 1
IndicationMa02
Hide
Show
Hide
SetLED02
Disabled
Enabled
Disabled
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Operation03
Disabled
Enabled
Disabled
TrigLevel03
Trig on 0
Trig on 1
Trig on 1
IndicationMa03
Hide
Show
Hide
SetLED03
Disabled
Enabled
Disabled
Operation04
Disabled
Enabled
Disabled
TrigLevel04
Trig on 0
Trig on 1
Trig on 1
IndicationMa04
Hide
Show
Hide
SetLED04
Disabled
Enabled
Disabled
Operation05
Disabled
Enabled
Disabled
TrigLevel05
Trig on 0
Trig on 1
Trig on 1
IndicationMa05
Hide
Show
Hide
SetLED05
Disabled
Enabled
Disabled
Operation06
Disabled
Enabled
Disabled
TrigLevel06
Trig on 0
Trig on 1
Trig on 1
IndicationMa06
Hide
Show
Hide
SetLED06
Disabled
Enabled
Disabled
Operation07
Disabled
Enabled
Disabled
TrigLevel07
Trig on 0
Trig on 1
Trig on 1
IndicationMa07
Hide
Show
Hide
SetLED07
Disabled
Enabled
Disabled
Operation08
Disabled
Enabled
Disabled
TrigLevel08
Trig on 0
Trig on 1
Trig on 1
581
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
IndicationMa08
Hide
Show
Hide
SetLED08
Disabled
Enabled
Disabled
Operation09
Disabled
Enabled
Disabled
TrigLevel09
Trig on 0
Trig on 1
Trig on 1
IndicationMa09
Hide
Show
Hide
SetLED09
Disabled
Enabled
Disabled
Operation10
Disabled
Enabled
Disabled
TrigLevel10
Trig on 0
Trig on 1
Trig on 1
IndicationMa10
Hide
Show
Hide
SetLED10
Disabled
Enabled
Disabled
Operation11
Disabled
Enabled
Disabled
TrigLevel11
Trig on 0
Trig on 1
Trig on 1
IndicationMa11
Hide
Show
Hide
SetLED11
Disabled
Enabled
Disabled
Operation12
Disabled
Enabled
Disabled
TrigLevel12
Trig on 0
Trig on 1
Trig on 1
IndicationMa12
Hide
Show
Hide
SetLED12
Disabled
Enabled
Disabled
Operation13
Disabled
Enabled
Disabled
TrigLevel13
Trig on 0
Trig on 1
Trig on 1
IndicationMa13
Hide
Show
Hide
SetLED13
Disabled
Enabled
Disabled
582
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
Operation14
Disabled
Enabled
Disabled
TrigLevel14
Trig on 0
Trig on 1
Trig on 1
IndicationMa14
Hide
Show
Hide
SetLED14
Disabled
Enabled
Disabled
Operation15
Disabled
Enabled
Disabled
TrigLevel15
Trig on 0
Trig on 1
Trig on 1
IndicationMa15
Hide
Show
Hide
SetLED15
Disabled
Enabled
Disabled
Operation16
Disabled
Enabled
Disabled
TrigLevel16
Trig on 0
Trig on 1
Trig on 1
IndicationMa16
Hide
Show
Hide
SetLED16
Disabled
Enabled
Disabled
FUNT1
0 - 255
FunT
FUNT2
0 - 255
FunT
FUNT3
0 - 255
FunT
FUNT4
0 - 255
FunT
FUNT5
0 - 255
FunT
FUNT6
0 - 255
FunT
FUNT7
0 - 255
FunT
FUNT8
0 - 255
FunT
FUNT9
0 - 255
FunT
FUNT10
0 - 255
FunT
583
Technical reference manual
Section 13
Monitoring
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
FUNT11
0 - 255
FunT
FUNT12
0 - 255
FunT
FUNT13
0 - 255
FunT
FUNT14
0 - 255
FunT
FUNT15
0 - 255
FunT
FUNT16
0 - 255
FunT
INFNO1
0 - 255
InfNo
INFNO2
0 - 255
InfNo
INFNO3
0 - 255
InfNo
INFNO4
0 - 255
InfNo
INFNO5
0 - 255
InfNo
INFNO6
0 - 255
InfNo
INFNO7
0 - 255
InfNo
INFNO8
0 - 255
InfNo
INFNO9
0 - 255
InfNo
INFNO10
0 - 255
InfNo
INFNO11
0 - 255
InfNo
INFNO12
0 - 255
InfNo
INFNO13
0 - 255
InfNo
INFNO14
0 - 255
InfNo
INFNO15
0 - 255
InfNo
INFNO16
0 - 255
InfNo
584
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.6.6
Technical data
Table 370:
Function
Range or value
Accuracy
Pre-fault time
(0.059.90) s
Post-fault time
(0.110.0) s
Limit time
(0.510.0) s
1 ms
See table 23
30 + 10 (external + internally
derived)
96
30
96
150
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
Recording bandwidth
(5-300) Hz
13.7
Sequential of events
13.7.1
Introduction
Continuous event-logging is useful for monitoring the system from an overview
perspective and is a complement to specific disturbance recorder functions.
The sequential of events logs all binary input signals connected to the Disturbance
report function. The list may contain up to 1000 time-tagged events stored in a ring-buffer.
13.7.2
Principle of operation
When a binary signal, connected to the disturbance report function, changes status, the
sequential of events function stores input name, status and time in the sequential of
585
Section 13
Monitoring
1MRK505208-UUS D
events in chronological order. The list can contain up to 1000 events from both internal
logic signals and binary input channels. If the list is full, the oldest event is overwritten
when a new event arrives.
The list can be configured to show oldest or newest events first with a setting on the
local HMI.
The sequential of events function runs continuously, in contrast to the event recorder
function, which is only active during a disturbance, and each event record is an integral
part of its associated DR.
The name of the binary signal that appears in the event recording is the user-defined
name assigned when the IED is configured. The same name is used in the disturbance
recorder function (DR), indications (IND) and the event recorder function (ER).
The sequential of events is stored and managed separate from the disturbance report
information(ER, DR, IND, TVR and FL).
13.7.3
Function block
The Sequential of events has no function block of its own.It is included in the
DRPRDRE block and uses information from the BxRBDR block.
13.7.4
Input signals
The Sequential of events logs the same binary input signals as configured for the
Disturbance report function.
13.7.5
Technical data
Table 371:
technical data
Function
Buffer capacity
Value
Maximum number of events in the list
1000
Resolution
1 ms
Accuracy
Depending on time
synchronizing
586
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.8
Indications
13.8.1
Introduction
To get fast, condensed and reliable information about disturbances in the primary and/
or in the secondary system it is important to know, for example binary signals that
have changed status during a disturbance. This information is used in the short
perspective to get information via the local HMI in a straightforward way.
There are three LEDs on the local HMI (green, yellow and red), which will display
status information about the IED and the Disturbance report function (triggered).
The Indication list function shows all selected binary input signals connected to the
Disturbance report function that have changed status during a disturbance.
13.8.2
Principle of operation
The LED indications display this information:
Green LED:
Steady light
In Service
Flashing light
Internal fail
Dark
No power supply
Yellow LED:
Steady light
Flashing light
Red LED:
Steady light
Indication list:
The possible indication signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
587
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
Indications are selected with the indication mask (IndicationMask) when setting the
binary inputs.
The name of the binary signal that appears in the Indication function is the user-defined
name assigned at configuration of the IED. The same name is used in disturbance
recorder function (DR), indications (IND) and event recorder function (ER).
13.8.3
Function block
The Indications function has no function block of its own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.
13.8.4
Input signals
The Indications function logs the same binary input signals as the Disturbance report
function.
13.8.5
Technical data
Table 372:
technical data
Function
Buffer capacity
13.9
Event recorder
13.9.1
Introduction
Value
Maximum number of indications presented
for single disturbance
96
100
Quick, complete and reliable information about disturbances in the primary and/or in
the secondary system is vital, for example, time-tagged events logged during
588
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example functional analysis).
The event recorder logs all selected binary input signals connected to the Disturbance
report function. Each recording can contain up to 150 time-tagged events.
The event recorder information is available for the disturbances locally in the IED.
The event recording information is an integrated part of the disturbance record
(Comtrade file).
13.9.2
Principle of operation
When one of the trig conditions for the disturbance report is activated, the event
recorder logs every status change in the 96 selected binary signals. The events can be
generated by both internal logical signals and binary input channels. The internal
signals are time-tagged in the main processor module, while the binary input channels
are time-tagged directly in each I/O module. The events are collected during the total
recording time (pre-, post-fault and limit time), and are stored in the disturbance report
flash memory at the end of each recording.
In case of overlapping recordings, due to PostRetrig = Enabled and a new trig signal
appears during post-fault time, events will be saved in both recording files.
The name of the binary input signal that appears in the event recording is the userdefined name assigned when configuring the IED. The same name is used in the
disturbance recorder function (DR), indications (IND) and event recorder function(ER).
The event record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and FL) and managed via the local HMI or PCM600.
Events can not be read from the IED if more than one user is accessing
the IED simultaneously.
13.9.3
Function block
The Event recorder has no function block of its own. It is included in the DRPRDRE
block and uses information from the BxRBDR block.
13.9.4
Input signals
The Event recorder function logs the same binary input signals as the Disturbance
report function.
589
Section 13
Monitoring
13.9.5
1MRK505208-UUS D
Technical data
Table 373:
technical data
Function
Buffer capacity
Value
Maximum number of events in disturbance report
150
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
13.10
13.10.1
Introduction
Information about the pre-fault and fault values for currents and voltages are vital for
the disturbance evaluation.
The Trip value recorder calculates the values of all selected analog input signals
connected to the Disturbance report function. The result is magnitude and phase angle
before and during the fault for each analog input signal.
The trip value recorder information is available for the disturbances locally in the IED.
The trip value recorder information is an integrated part of the disturbance record
(Comtrade file).
13.10.2
Principle of operation
Trip value recorder (TVR)calculates and presents both fault and pre-fault magnitudes
as well as the phase angles of all the selected analog input signals. The parameter
ZeroAngleRef points out which input signal is used as the angle reference.
When the disturbance report function is triggered the sample for the fault interception
is searched for, by checking the non-periodic changes in the analog input signals. The
channel search order is consecutive, starting with the analog input with the lowest number.
When a fault interception point is found, the Fourier estimation of the pre-fault values
of the complex values of the analog signals starts 1.5 cycle before the fault sample. The
estimation uses samples during one period. The post-fault values are calculated using
the Recursive Least Squares (RLS) method. The calculation starts a few samples after
the fault sample and uses samples during 1/2 - 2 cycles depending on the shape of the
signals.
590
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
If no starting point is found in the recording, the disturbance report trig sample is used
as the start sample for the Fourier estimation. The estimation uses samples during one
cycle before the trig sample. In this case the calculated values are used both as pre-fault
and fault values.
The name of the analog signal that appears in the Trip value recorder function is the userdefined name assigned when the IED is configured. The same name is used in the
Disturbance recorder function (DR).
The trip value record is stored as a part of the disturbance report information (ER, DR,
IND, TVR and fault locator) and managed in PCM600 or via the local HMI.
13.10.3
Function block
The Trip value recorder has no function block of its own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.
13.10.4
Input signals
The trip value recorder function uses analog input signals connected to A1RADR to
A3RADR (not A4RADR).
13.10.5
Technical data
Table 374:
technical data
Function
Buffer capacity
Value
Maximum number of analog inputs
30
100
13.11
Disturbance recorder
13.11.1
Introduction
The Disturbance recorder function supplies fast, complete and reliable information
about disturbances in the power system. It facilitates understanding system behavior
and related primary and secondary equipment during and after a disturbance. Recorded
information is used for different purposes in the short perspective (for example
corrective actions) and long perspective (for example functional analysis).
The Disturbance recorder acquires sampled data from selected analog- and binary
signals connected to the Disturbance report function (maximum 40 analog and 96
591
Section 13
Monitoring
1MRK505208-UUS D
binary signals). The binary signals available are the same as for the event recorder
function.
The function is characterized by great flexibility and is not dependent on the operation
of protection functions. It can record disturbances not detected by protection functions.
Up to ten seconds of data before the trigger instant can be saved in the disturbance file.
The disturbance recorder information for up to 100 disturbances are saved in the IED
and the local HMI is used to view the list of recordings.
13.11.2
Principle of operation
Disturbance recording (DR) is based on the acquisition of binary and analog signals.
The binary signals can be either true binary input signals or internal logical signals
generated by the functions in the IED. The analog signals to be recorded are input
channels from the Transformer Input Module (TRM), Line Differential communication
Module (LDCM) through the Signal Matrix Analog Input (SMAI) and possible
summation (Sum3Ph) function blocks and some internally derived analog signals.For
details, refer to section "Disturbance report DRPRDRE".
Disturbance recorder collects analog values and binary signals continuously, in a cyclic
buffer. The pre-fault buffer operates according to the FIFO principle; old data will
continuously be overwritten as new data arrives when the buffer is full. The size of this
buffer is determined by the set pre-fault recording time.
Upon detection of a fault condition (triggering), the disturbance is time tagged and the
data storage continues in a post-fault buffer. The storage process continues as long as
the fault condition prevails - plus a certain additional time. This is called the post-fault
time and it can be set in the disturbance report.
The above mentioned two parts form a disturbance recording. The whole memory,
intended for disturbance recordings, acts as a cyclic buffer and when it is full, the
oldest recording is overwritten. Up to the last 100 recordings are stored in the IED.
The time tagging refers to the activation of the trigger that starts the disturbance
recording. A recording can be trigged by, manual start, binary input and/or from analog
inputs (over-/underlevel trig).
A user-defined name for each of the signals can be set. These names are common for
all functions within the disturbance report functionality.
592
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
13.11.2.1
The IED flash disk should NOT be used to store any user files. This
might cause disturbance recordings to be deleted due to lack of disk space.
When a recording is completed, a post recording processing occurs.
This post-recording processing comprises:
Saving the data for analog channels with corresponding data for binary signals
Add relevant data to be used by the Disturbance handling tool (part of PCM 600)
Compression of the data, which is performed without losing any data accuracy
Storing the compressed data in a non-volatile memory (flash memory)
Analog:
Section 13
Monitoring
1MRK505208-UUS D
Binary:
Signal names
Status of binary input signals
13.11.2.2
IEC 60870-5-103
The communication protocol IEC 60870-5-103 may be used to poll disturbance
recordings from the IED to a master (station HSI). The standard describes how to
handle 8 disturbance recordings, 8 analog channels (4 currents and 4 voltages) using
the public range and binary signals.
The last 8 recordings, out of maximum 100, are available for transfer to the master.
When the last one is transferred and acknowledged new recordings in the IED will
appear, in the master points of view (even if they already where stored in the IED).
To be able to report 40 analog channels from the IED using IEC 60870-5-103 the first
8 channels are placed in the public range and the next 32 are placed in the private
range. To comply the standard the first 8 must be configured according to table 375.
Table 375:
Signal
IA
A1RADR
INPUT1
IB
A1RADR
INPUT2
IC
A1RADR
INPUT3
IN
A1RADR
INPUT4
VA
A1RADR
INPUT5
VB
A1RADR
INPUT6
VC
A1RADR
INPUT7
VN
A1RADR
INPUT8
594
Technical reference manual
Section 13
Monitoring
1MRK505208-UUS D
The binary signals connected to BxRBDR are reported by polling. The function blocks
include function type and information number.
13.11.3
Function block
The Disturbance recorder has no function block of its own. It is included in the
DRPRDRE, AxRADR and BxRBDR block.
13.11.4
13.11.5
Setting parameters
For Setting parameters see section "Disturbance report DRPRDRE".
13.11.6
Technical data
Table 376:
technical data
Function
Buffer capacity
Value
Maximum number of analog inputs
40
96
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
595
Technical reference manual
596
Section 14
Metering
1MRK505208-UUS D
Section 14
Metering
14.1
IEC 61850
identification
IEC 60617
identification
PCGGIO
ANSI/IEEE C37.2
device number
-
S00947 V1 EN
14.1.1
Introduction
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then read
by the function. A scaled service value is available over the station bus. The special
Binary input module with enhanced pulse counting capabilities must be ordered to
achieve this functionality.
14.1.2
Principle of operation
The registration of pulses is done for positive transitions (0->1) on one of the 16 binary
input channels located on the Binary Input Module (BIM). Pulse counter values are
sent to the station HMI with predefined cyclicity without reset.
The reporting time period can be set in the range from 1 second to 60 minutes and is
synchronized with absolute system time. Interrogation of additional pulse counter
values can be done with a command (intermediate reading) for a single counter. All
597
Section 14
Metering
1MRK505208-UUS D
active counters can also be read by the LON General Interrogation command (GI) or
IEC 61850.
Pulse counter (PCGGIO) function in the IED supports unidirectional incremental
counters. That means only positive values are possible. The counter uses a 32 bit
format, that is, the reported value is a 32-bit, signed integer with a range
0...+2147483647. The counter is reset at initialization of the IED.
The reported value to station HMI over the station bus contains Identity, Scaled Value
(pulse count x scale), Time, and Pulse Counter Quality. The Pulse Counter Quality
consists of:
The transmission of the counter value by SPA can be done as a service value, that is,
the value frozen in the last integration cycle is read by the station HMI from the
database. PCGGIO updates the value in the database when an integration cycle is
finished and activates the NEW_VAL signal in the function block. This signal can be
connected to an Event function block, be time tagged, and transmitted to the station
HMI. This time corresponds to the time when the value was frozen by the function.
The pulse counter function requires a binary input card, BIMp, that is
specially adapted to the pulse counter function.
Figure 269 shows the pulse counter function block with connections of the inputs and
outputs.
598
Technical reference manual
Section 14
Metering
1MRK505208-UUS D
SingleCmdFunc
OUTx
SingleCmdFunc
OUTx
I/Omodule
Pulse
INPUT OUT
Pulse length >1s
Reset counter
PulseCounter
BLOCK
INVALID
RESTART
READ_VAL
BLOCKED
NEW_VAL
BI_PULSE
RS_CNT
NAME
SCAL_VAL
SMS settings
1.Operation = Off/On
2.tReporting = 0s...60min
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
EVENT
INPUT1
INPUT2
INPUT3
INPUT4
IEC EVENT
Database
Pulse counter value:
0...2147483647
en05000744_ansi.vsd
ANSI05000744 V1 EN
Figure 269:
The BLOCK and READ_VAL inputs can be connected to Single Command blocks,
which are intended to be controlled either from the station HMI or/and the local HMI.
As long as the BLOCK signal is set, the pulse counter is blocked. The signal connected
to READ_VAL performs one additional reading per positive flank. The signal must be
a pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
The RS_CNT input is used for resetting the counter.
Each pulse counter function block has four binary output signals that can be connected
to an Event function block for event recording: INVALID, RESTART, BLOCKED
and NEW_VAL. The SCAL_VAL signal can be connected to the IEC Event function
block.
The INVALID signal is a steady signal and is set if the Binary Input Module, where
the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-up,
in the first message after deblocking, and after the counter has wrapped around during
last integration cycle.
The BLOCKED signal is a steady signal and is set when the counter is blocked. There
are two reasons why the counter is blocked:
599
Technical reference manual
Section 14
Metering
1MRK505208-UUS D
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
Note, the pulse is short, one cycle.
The SCAL_VAL signal consists of scaled value (according to parameter Scale), time
and status information.
14.1.3
Function block
PCGGIO
BLOCK
READ_VAL
BI_PULSE*
RS_CNT
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC05000709-2-en.vsd
IEC05000709 V3 EN
Figure 270:
14.1.4
Default
Description
BLOCK
BOOLEAN
Block of function
READ_VAL
BOOLEAN
BI_PULSE
BOOLEAN
RS_CNT
BOOLEAN
Table 378:
Name
Description
INVALID
BOOLEAN
RESTART
BOOLEAN
BLOCKED
BOOLEAN
NEW_VAL
BOOLEAN
SCAL_VAL
REAL
600
Technical reference manual
Section 14
Metering
1MRK505208-UUS D
14.1.5
Table 379:
Setting parameters
PCGGIO Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
EventMask
NoEvents
ReportEvents
NoEvents
CountCriteria
Disabled
RisingEdge
Falling edge
OnChange
RisingEdge
Scale
1.000 - 90000.000
0.001
1.000
Quantity
Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
Count
tReporting
0 - 3600
60
14.1.6
Technical data
Table 380:
Function
14.2
Setting range
Accuracy
Input frequency
(13600) s
IEC 61850
identification
ETPMMTR
IEC 60617
identification
ANSI/IEEE C37.2
device number
-
601
Technical reference manual
Section 14
Metering
14.2.1
1MRK505208-UUS D
Introduction
Outputs from the Measurements (CVMMXN) function can be used to calculate energy
consumption. Active as well as reactive values are calculated in import and export
direction. Values can be read or generated as pulses. Maximum demand power values
are also calculated by the function.
14.2.2
Principle of operation
The instantaneous output values of active and reactive power from the Measurements
(CVMMXN) function block are used and integrated over a selected time tEnergy to
measure the integrated energy. The energy values (in MWh and MVarh) are available
as output signals and also as pulsed output which can be connected to a pulse counter.
Outputs are available for forward as well as reverse direction. The accumulated energy
values can be reset from the local HMI reset menu or with input signal RSTACC.
The maximum demand values for active and reactive power are calculated for the set
time tEnergy and the maximum value is stored in a register available over
communication and from outputs MAXPAFD, MAXPARD, MAXPRFD, MAXPRRD
for the active and reactive power forward and reverse direction until reset with input
signal RSTDMD or from the local HMI reset menu.
CVMMXN
P_INST
Q_INST
P
Q
TRUE
FALSE
FALSE
ETPMMTR
STACC
RSTACC
RSTDMD
IEC09000106.vsd
IEC09000106 V1 EN
Figure 271:
602
Technical reference manual
Section 14
Metering
1MRK505208-UUS D
14.2.3
Function block
ETPMMTR
P
Q
STACC
RSTACC
RSTDMD
ACCST
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC07000120-2-en.vsd
IEC07000120 V2 EN
Figure 272:
14.2.4
Default
Description
REAL
REAL
STACC
BOOLEAN
RSTACC
BOOLEAN
RSTDMD
BOOLEAN
Table 382:
Name
Description
ACCST
BOOLEAN
EAFPULSE
BOOLEAN
EARPULSE
BOOLEAN
ERFPULSE
BOOLEAN
ERRPULSE
BOOLEAN
EAFALM
BOOLEAN
EARALM
BOOLEAN
603
Technical reference manual
Section 14
Metering
1MRK505208-UUS D
Name
14.2.5
Table 383:
Name
Type
Description
ERFALM
BOOLEAN
ERRALM
BOOLEAN
EAFACC
REAL
EARACC
REAL
ERFACC
REAL
ERRACC
REAL
MAXPAFD
REAL
MAXPARD
REAL
MAXPRFD
REAL
MAXPRRD
REAL
Setting parameters
ETPMMTR Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation Enable/Disable
StartAcc
Disabled
Enabled
Disabled
tEnergy
1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
1 Minute
tEnergyOnPls
0.000 - 60.000
0.001
1.000
tEnergyOffPls
0.000 - 60.000
0.001
0.500
EAFAccPlsQty
0.001 - 10000.000
MWh
0.001
100.000
EARAccPlsQty
0.001 - 10000.000
MWh
0.001
100.000
ERFAccPlsQty
0.001 - 10000.000
MVArh
0.001
100.000
ERVAccPlsQty
0.001 - 10000.000
MVArh
0.001
100.000
604
Technical reference manual
Section 14
Metering
1MRK505208-UUS D
Table 384:
Name
Values (Range)
Unit
Step
Default
Description
EALim
0.001 10000000000.000
MWh
0.001
1000000.000
ERLim
0.001 10000000000.000
MVArh
0.001
1000.000
DirEnergyAct
Forward
Reverse
Forward
DirEnergyReac
Forward
Reverse
Forward
EnZeroClamp
Disabled
Enabled
Enabled
LevZeroClampP
0.001 - 10000.000
MW
0.001
10.000
LevZeroClampQ
0.001 - 10000.000
MVAr
0.001
10.000
EAFPrestVal
0.000 - 10000.000
MWh
0.001
0.000
EARPrestVal
0.000 - 10000.000
MWh
0.001
0.000
ERFPresetVal
0.000 - 10000.000
MVArh
0.001
0.000
ERVPresetVal
0.000 - 10000.000
MVArh
0.001
0.000
605
Technical reference manual
606
Section 15
Station communication
1MRK505208-UUS D
Section 15
Station communication
15.1
Overview
Each IED is provided with a communication interface, enabling it to connect to one or
many substation level systems or equipment, either on the Substation Automation (SA)
bus or Substation Monitoring (SM) bus.
Following communication protocols are available:
15.2
15.2.1
Introduction
The IED is equipped with single or double optical Ethernet rear ports (order
dependent) for IEC 61850-8-1 station bus communication. The IEC 61850-8-1
communication is also possible from the optical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from different vendors to exchange
information and simplifies system engineering. Peer-to-peer communication according
to GOOSE is part of the standard. Disturbance files uploading is provided.
607
Technical reference manual
Section 15
Station communication
15.2.2
Table 385:
Name
1MRK505208-UUS D
Setting parameters
IEC61850-8-1 Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
Off
Operation Off/On
GOOSE
Front
OEM311_AB
OEM311_CD
OEM311_AB
15.2.3
Technical data
Table 386:
Function
Value
Protocol
IEC 61850-8-1
100BASE-FX
Protocol
IEC 6085103
9600 or 19200 Bd
Protocol
DNP3.0
30019200 Bd
Protocol
TCP/IP, Ethernet
100 Mbit/s
15.2.4
15.2.4.1
Function block
SPGGIO
BLOCK
^IN
IEC07000124-2-en.vsd
IEC07000124 V2 EN
Figure 273:
608
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
SP16GGIO
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC07000125-2-en.vsd
IEC07000125 V2 EN
Figure 274:
15.2.4.2
Default
Description
BLOCK
BOOLEAN
Block of function
IN
BOOLEAN
Input status
Table 388:
Name
Default
Description
BLOCK
BOOLEAN
Block of function
IN1
BOOLEAN
Input 1 status
IN2
BOOLEAN
Input 2 status
IN3
BOOLEAN
Input 3 status
IN4
BOOLEAN
Input 4 status
IN5
BOOLEAN
Input 5 status
IN6
BOOLEAN
Input 6 status
IN7
BOOLEAN
Input 7 status
IN8
BOOLEAN
Input 8 status
IN9
BOOLEAN
Input 9 status
IN10
BOOLEAN
Input 10 status
IN11
BOOLEAN
Input 11 status
IN12
BOOLEAN
Input 12 status
IN13
BOOLEAN
Input 13 status
609
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
15.2.4.3
Type
Default
Description
IN14
BOOLEAN
Input 14 status
IN15
BOOLEAN
Input 15 status
IN16
BOOLEAN
Input 16 status
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
15.2.5
15.2.5.1
Principle of operation
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range, as
output values. In the same time, it will send over IEC 61850-8-1 the value, to other
IEC 61850 clients in the substation.
15.2.5.2
Function block
MVGGIO
BLOCK
^IN
^VALUE
RANGE
IEC05000408-2-en.vsd
IEC05000408 V2 EN
Figure 275:
15.2.5.3
Table 389:
Name
Setting parameters
MVGGIO Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
MV db
1 - 300
Type
10
MV zeroDb
0 - 100000
m%
500
MV hhLim
-10000000000.000
- 10000000000.000
0.001
90.000
MV hLim
-10000000000.000
- 10000000000.000
0.001
80.000
High limit
MV lLim
-10000000000.000
- 10000000000.000
0.001
-80.000
Low limit
610
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
MV llLim
-10000000000.000
- 10000000000.000
0.001
-90.000
MV min
-10000000000.000
- 10000000000.000
0.001
-100.000
Minimum value
MV max
-10000000000.000
- 10000000000.000
0.001
100.000
Maximum value
MV dbType
Cyclic
Dead band
Int deadband
Dead band
Reporting type
MV limHys
0.000 - 100.000
0.001
5.000
15.2.6
15.2.6.1
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
PRPSTATUS
DUODRV
Introduction
Redundant station bus communication according to IEC 62439-3 Edition 1 and IEC
62439-3 Edition 2 are available as options in 670 series IEDs. IEC 62439-3 parallel
redundant protocol is an optional quantity and the selection is made at ordering.
Redundant station bus communication according to IEC 62439-3 uses both port AB
and port CD on the OEM module.
Select IEC 62439-3 Edition 1 protocol at the time of ordering when an
existing redundant station bus DuoDriver installation is extended.
Select IEC 62439-3 Edition 2 protocol at the time of ordering for new
installations with redundant station bus.
IEC 62439-3 Edition 1 is NOT compatible with IEC 62439-3 Edition 2.
15.2.6.2
Principle of operation
The redundant station bus communication (DUODRV) is configured using the local
HMI. The settings for DUODRV are also visible in PST in PCM600.
The communication is performed in parallel, that is the same data package is
transmitted on both channels simultaneously. The received package identity from one
611
Section 15
Station communication
1MRK505208-UUS D
channel is compared with data package identity from the other channel, if the same, the
last package is discarded.
PRPSTATUS function block supervise the redundant communication on the two
channels. If no data package has been received on one (or both) channels within the
last 10 s, the output LAN-A-STATUS and/or LAN-B-STATUS is set to indicate error.
612
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Data
Data
Switch A
Switch B
1 2
1 2
Data
Data
AB
Configuration
CD
IED
OEM
DUODRV
PRPSTATUS
IEC09000758-2-en.vsd
IEC09000758 V2 EN
Figure 276:
613
Technical reference manual
Section 15
Station communication
15.2.6.3
1MRK505208-UUS D
Function block
PRPSTATUS
LAN-A-Status
LAN-B-Status
IEC09000757-1-en.vsd
IEC09000757 V1 EN
Figure 277:
15.2.6.4
Output signals
Table 390:
Name
15.2.6.5
Table 391:
Name
Type
Description
LAN-A-Status
BOOLEAN
Channel A status
LAN-B-Status
BOOLEAN
Channel B status
Setting parameters
DUODRV Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Disable/Enable Operation
IPAddress
0 - 18
IP
Address
192.168.7.10
IP-Address
IPMask
0 - 18
IP
Address
255.255.255.0
IP-Mask
15.3
15.3.1
Introduction
An optical network can be used within the substation automation system. This enables
communication with the IED through the LON bus from the operators workplace,
from the control center and also from other terminals.
LON communication protocol is specified in LonTalkProtocol Specification Version 3
from Echelon Corporation and is designed for communication in control networks.
These networks are characterized by high speed for data transfer, short messages (few
bytes), peer-to-peer communication, multiple communication media, low maintenance,
multivendor equipment, and low support costs. LonTalk supports the needs of
614
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
applications that cover a range of requirements. The protocol follows the reference
model for open system interconnection (OSI) designed by the International
Standardization Organization (ISO).
In this document the most common addresses for commands and events are available.
For other addresses, refer to section "".
It is assumed that the reader is familiar with LON communication protocol in general.
15.3.2
Principle of operation
The speed of the network depends on the medium and transceiver design. With
protection and control devices, fibre optic media is used, which enables the use of the
maximum speed of 1.25 Mbits/s. The protocol is a peer-to-peer protocol where all the
devices connected to the network can communicate with each other. The own subnet
and node number are identifying the nodes (max. 255 subnets, 127 nodes per one subnet).
The LON bus links the different parts of the protection and control system. The
measured values, status information, and event information are spontaneously sent to
the higher-level devices. The higher-level devices can read and write memorized
values, setting values, and other parameter data when required. The LON bus also
enables the bay level devices to communicate with each other to deliver, for example,
interlocking information among the terminals without the need of a bus master.
The LonTalk protocol supports two types of application layer objects: network
variables and explicit messages. Network variables are used to deliver short messages,
such as measuring values, status information, and interlocking/blocking signals.
Explicit messages are used to transfer longer pieces of information, such as events and
explicit read and write messages to access device data.
The benefits achieved from using the LON bus in protection and control systems
include direct communication among all terminals in the system and support for multimaster implementations. The LON bus also has an open concept, so that the terminals
can communicate with external devices using the same standard of network variables.
For more information, refer to LON bus, LonWorks Network in Protection and
Control, Users manual and Technical description.
LON protocol
Configuration of LON
Lon Network Tool (LNT 505) is a multi-purpose tool for LonWorks network
configuration. All the functions required for setting up and configuring a LonWorks
network, is easily accessible on a single tool program. For more information, refer to
the operator's manual.
615
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
616
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
EVENT:1
1024
EVENT:2
1040
EVENT:3
1056
EVENT:4
1072
EVENT:5
1088
EVENT:6
1104
EVENT:7
1120
EVENT:8
1136
EVENT:9
1152
EVENT:10
1168
EVENT:11
1184
EVENT:12
1200
EVENT:13
1216
EVENT:14
1232
EVENT:15
1248
EVENT:16
1264
EVENT:17
1280
EVENT:18
1296
EVENT:19
1312
EVENT:20
1328
Event masks
The event mask for each input can be set individually from Parameter Setting Tool
(PST) under: Settings/ General Settings/ Monitoring / EventFunction as follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for
integers has no semantic, prefer to be set by the user)
617
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
The following type of signals from application functions can be connected to the event
function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is always
reported on change, no changed detection is done in the event function block. Other
Boolean signals, for example a start or a trip signal from a protection function is event
masked in the event function block.
Double indications
Double indications can only be reported via switch-control (SCSWI) functions, the
event reporting is based on information from switch-control, no change detection is
done in the event function block.
Directly connected binary IO signal via binary input function block (SMBI) is not
possible to handle as double indication. Double indications can only be reported for the
first 8 inputs on an event function block.
Analog value
All analog values are reported cyclic, the reporting interval is taken from the connected
function if there is a limit supervised signal, otherwise it is taken from the event
function block.
Command handling
Commands are transferred using transparent SPA-bus messages. The transparent SPAbus message is an explicit LON message, which contains an ASCII character message
following the coding rules of the SPA-bus protocol. The message is sent using explicit
messages with message code 41H and using acknowledged transport service.
Both the SPA-bus command messages (R or W) and the reply messages (D, A or N)
are sent using the same message code. It is mandatory that one device sends out only
one SPA-bus message at a time to one node and waits for the reply before sending the
next message.
For commands from the operator workplace to the IED for apparatus control, That is,
the function blocks type SCSWI 1 to 32, SXCBR 1 to 18 and SXSWI 1 to 28; the SPA
addresses are according to table 393.
618
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Horizontal communication
Network variables are used for communication between 500 series and 670 series
IEDs. The supported network variable type is SNVT_state (NV type 83). SNVT_state
is used to communicate the state of a set of 1 to 16 Boolean values.
Multiple command send function block (MULTICMDSND) is used to pack the
information to one value. This value is transmitted to the receiving node and presented
for the application by a multiple command function block (MULTICMDRCV). At
horizontal communication the input BOUND on the event function block
(MULTICMDSND) must be set to 1. There are 10 MULTICMDSND and 60
MULTICMDRCV function blocks available. The MULTICMDSND and
MULTICMDRCV function blocks are connected using Lon Network Tool (LNT 505).
This tool also defines the service and addressing on LON.
This is an overview for configuring the network variables for 670 series IEDs.
Configuration of LON network variables
Configure the Network variables according to the specific application using the LON
network Tool. For more information, refer to LNT 505 in Operation manual. The
following is an example of how to configure network variables concerning, for
example, interlocking between two IEDs.
LON
BAY E1
BAY E3
MULTICMDSND: 7
MULTICMDSND: 9
BAY E4
MULTICMDSND: 9
en05000718.vsd
IEC05000718 V2 EN
Figure 278:
The network variable connections are done from the NV Connection window. From
LNT window select Connections/ NVConnections/ New.
619
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
en05000719.vsd
IEC05000719 V1 EN
Figure 279:
There are two ways of downloading NV connections. Either the users can use the dragand-drop method where they can select all nodes in the device window, drag them to
the Download area in the bottom of the program window and drop them there; or, they
can perform it by selecting the traditional menu, Configuration/ Download.
620
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
en05000720.vsd
IEC05000720 V1 EN
Figure 280:
Communication ports
SPA addresses for commands from the operator workplace to the IED for apparatus control
Name
Function
block
SPA
address
Description
BL_CMD
SCSWI01
1 I 5115
BL_CMD
SCSWI02
1 I 5139
BL_CMD
SCSWI02
1 I 5161
BL_CMD
SCSWI04
1 I 5186
621
Technical reference manual
Section 15
Station communication
Name
1MRK505208-UUS D
Function
block
SPA
address
Description
BL_CMD
SCSWI05
1 I 5210
BL_CMD
SCSWI06
1 I 5234
BL_CMD
SCSWI07
1 I 5258
BL_CMD
SCSWI08
1 I 5283
BL_CMD
SCSWI09
1 I 5307
BL_CMD
SCSWI10
1 I 5331
BL_CMD
SCSWI11
1 I 5355
BL_CMD
SCSWI12
1 I 5379
BL_CMD
SCSWI13
1 I 5403
BL_CMD
SCSWI14
1 I 5427
BL_CMD
SCSWI15
1 I 5451
BL_CMD
SCSWI16
1 I 5475
BL_CMD
SCSWI17
1 I 5499
BL_CMD
SCSWI18
1 I 5523
BL_CMD
SCSWI19
1 I 5545
BL_CMD
SCSWI20
1 I 5571
BL_CMD
SCSWI21
1 I 5594
BL_CMD
SCSWI22
1 I 5619
BL_CMD
SCSWI23
1 I 5643
BL_CMD
SCSWI24
1 I 5667
BL_CMD
SCSWI25
1 I 5691
BL_CMD
SCSWI26
1 I 5715
622
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
Function
block
SPA
address
Description
BL_CMD
SCSWI27
1 I 5739
BL_CMD
SCSWI28
1 I 5763
BL_CMD
SCSWI29
1 I 5787
BL_CMD
SCSWI30
1 I 5811
BL_CMD
SCSWI31
1 I 5835
BL_CMD
SCSWI32
1 I 5859
CANCEL
SCSWI01
1 I 5107
CANCEL
SCSWI02
1 I 5131
CANCEL
SCSWI03
1 I 5153
CANCEL
SCSWI04
1 I 5178
CANCEL
SCSWI05
1 I 5202
CANCEL
SCSWI06
1 I 5226
CANCEL
SCSWI07
1 I 5250
CANCEL
SCSWI08
1 I 5275
CANCEL
SCSWI09
1 I 5299
CANCEL
SCSWI10
1 I 5323
CANCEL
SCSWI11
1 I 5347
CANCEL
SCSWI12
1 I 5371
CANCEL
SCSWI13
1 I 5395
CANCEL
SCSWI14
1 I 5419
CANCEL
SCSWI15
1 I 5443
CANCEL
SCSWI16
1 I 5467
623
Technical reference manual
Section 15
Station communication
Name
1MRK505208-UUS D
Function
block
SPA
address
Description
CANCEL
SCSWI17
1 I 5491
CANCEL
SCSWI18
1 I 5515
CANCEL
SCSWI19
1 I 5537
CANCEL
SCSWI20
1 I 5563
CANCEL
SCSWI21
1 I 5586
CANCEL
SCSWI22
1 I 5611
CANCEL
SCSWI23
1 I 5635
CANCEL
SCSWI24
1 I 5659
CANCEL
SCSWI25
1 I 5683
CANCEL
SCSWI26
1 I 5707
CANCEL
SCSWI27
1 I 5731
CANCEL
SCSWI28
1 I 5755
CANCEL
SCSWI29
1 I 5779
CANCEL
SCSWI30
1 I 5803
CANCEL
SCSWI31
1 I 5827
CANCEL
SCSWI32
1 I 5851
SELECTOpen=00,
SELECTClose=01,
SELOpen+ILO=10,
SELClose+ILO=11,
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31
SCSWI01
1 I 5105
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI02
1 I 5129
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI03
1 I 5151
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI04
1 I 5176
Section 15
Station communication
1MRK505208-UUS D
Name
Function
block
SPA
address
Description
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI05
1 I 5200
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI06
1 I 5224
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI07
1 I 5248
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI08
1 I 5273
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI09
1 I 5297
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI10
1 I 5321
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI11
1 I 5345
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI12
1 I 5369
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI13
1 I 5393
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI14
1 I 5417
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI15
1 I 5441
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI16
1 I 5465
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI17
1 I 5489
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI18
1 I 5513
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI19
1 I 5535
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI20
1 I 5561
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI21
1 I 5584
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI22
1 I 5609
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI23
1 I 5633
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI24
1 I 5657
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI25
1 I 5681
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI26
1 I 5705
625
Technical reference manual
Section 15
Station communication
Name
1MRK505208-UUS D
Function
block
SPA
address
Description
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI27
1 I 5729
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI28
1 I 5753
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI29
1 I 5777
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI30
1 I 5801
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI31
1 I 5825
SELECTOpen=00,
SELECTClose=01, so on.
SCSWI32
1 I 5849
ExcOpen=00,
ExcClose=01,
ExcOpen+ILO=10,
ExcClose+ILO=11,
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31
SCSWI01
1 I 5106
ExcOpen=00,
ExcClose=01, so on.
SCSWI02
1 I 5130
ExcOpen=00,
ExcClose=01, so on.
SCSWI02
1 I 5152
ExcOpen=00,
ExcClose=01, so on.
SCSWI04
1 I 5177
ExcOpen=00,
ExcClose=01, so on.
SCSWI05
1 I 5201
ExcOpen=00,
ExcClose=01, so on.
SCSWI06
1 I 5225
ExcOpen=00,
ExcClose=01, so on.
SCSWI07
1 I 5249
ExcOpen=00,
ExcClose=01, so on.
SCSWI08
1 I 5274
ExcOpen=00,
ExcClose=01, so on.
SCSWI09
1 I 5298
ExcOpen=00,
ExcClose=01, so on.
SCSWI10
1 I 5322
ExcOpen=00,
ExcClose=01, so on.
SCSWI11
1 I 5346
ExcOpen=00,
ExcClose=01, so on.
SCSWI12
1 I 5370
ExcOpen=00,
ExcClose=01, so on.
SCSWI13
1 I 5394
ExcOpen=00,
ExcClose=01, so on.
SCSWI14
1 I 5418
Section 15
Station communication
1MRK505208-UUS D
Name
Function
block
SPA
address
Description
ExcOpen=00,
ExcClose=01, so on.
SCSWI15
1 I 5442
ExcOpen=00,
ExcClose=01, so on.
SCSWI16
1 I 5466
ExcOpen=00,
ExcClose=01, so on.
SCSWI17
1 I 5490
ExcOpen=00,
ExcClose=01, so on.
SCSWI18
1 I 5514
ExcOpen=00,
ExcClose=01, so on.
SCSWI19
1 I 5536
ExcOpen=00,
ExcClose=01, so on.
SCSWI20
1 I 5562
ExcOpen=00,
ExcClose=01, so on.
SCSWI21
1 I 5585
ExcOpen=00,
ExcClose=01, so on.
SCSWI22
1 I 5610
ExcOpen=00,
ExcClose=01, so on.
SCSWI23
1 I 5634
ExcOpen=00,
ExcClose=01, so on.
SCSWI24
1 I 5658
ExcOpen=00,
ExcClose=01, so on.
SCSWI25
1 I 5682
ExcOpen=00,
ExcClose=01, so on.
SCSWI26
1 I 5706
ExcOpen=00,
ExcClose=01, so on.
SCSWI27
1 I 5730
ExcOpen=00,
ExcClose=01, so on.
SCSWI28
1 I 5754
ExcOpen=00,
ExcClose=01, so on.
SCSWI29
1 I 5778
ExcOpen=00,
ExcClose=01, so on.
SCSWI30
1 I 5802
ExcOpen=00,
ExcClose=01, so on.
SCSWI31
1 I 5826
ExcOpen=00,
ExcClose=01, so on.
SCSWI32
1 I 5850
Sub Value
SXCBR01
2 I 7854
Sub Value
SXCBR02
2 I 7866
Sub Value
SXCBR03
2 I 7884
Sub Value
SXCBR04
2 I 7904
Section 15
Station communication
Name
1MRK505208-UUS D
Function
block
SPA
address
Description
Sub Value
SXCBR05
2 I 7923
Sub Value
SXCBR06
2 I 7942
Sub Value
SXCBR07
2 I 7961
Sub Value
SXCBR08
2 I 7980
Sub Value
SXCBR09
3I7
Sub Value
SXCBR10
3 I 26
Sub Value
SXCBR11
3 I 45
Sub Value
SXCBR12
3 I 56
Sub Value
SXCBR13
3 I 74
Sub Value
SXCBR14
3 I 94
Sub Value
SXCBR15
3 I 120
Sub Value
SXCBR16
3 I 133
Sub Value
SXCBR17
3 I 158
Sub Value
SXCBR18
3 I 179
Sub Value
SXSWI01
3 I 196
Sub Value
SXSWI02
3 I 216
Sub Value
SXSWI03
3 I 235
Sub Value
SXSWI04
3 I 254
Sub Value
SXSWI05
3 I 272
Sub Value
SXSWI06
3 I 292
Sub Value
SXSWI07
3 I 310
Sub Value
SXSWI08
3 I 330
628
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
Function
block
SPA
address
Description
Sub Value
SXSWI09
3 I 348
Sub Value
SXSWI10
3 I 359
Sub Value
SXSWI11
3 I 378
Sub Value
SXSWI12
3 I 397
Sub Value
SXSWI13
3 I 416
Sub Value
SXSWI14
3 I 435
Sub Value
SXSWI15
3 I 454
Sub Value
SXSWI16
3 I 473
Sub Value
SXSWI17
3 I 492
Sub Value
SXSWI18
3 I 511
Sub Value
SXSWI19
3 I 530
Sub Value
SXSWI20
3 I 549
Sub Value
SXSWI21
3 I 568
Sub Value
SXSWI22
3 I 587
Sub Value
SXSWI23
3 I 606
Sub Value
SXSWI24
3 I 625
Sub Value
SXSWI25
3 I 644
Sub Value
SXSWI26
3 I 663
Sub Value
SXSWI27
3 I 682
Sub Value
SXSWI28
3 I 701
Sub Enable
SXCBR01
2 I 7855
629
Technical reference manual
Section 15
Station communication
Name
1MRK505208-UUS D
Function
block
SPA
address
Description
Sub Enable
SXCBR02
2 I 7865
Sub Enable
SXCBR03
2 I 7885
Sub Enable
SXCBR04
2 I 7903
Sub Enable
SXCBR05
2 I 7924
Sub Enable
SXCBR06
2 I 7941
Sub Enable
SXCBR07
2 I 7962
Sub Enable
SXCBR08
2 I 7979
Sub Enable
SXCBR09
3I8
Sub Enable
SXCBR10
3 I 25
Sub Enable
SXCBR11
3 I 46
Sub Enable
SXCBR12
3 I 55
Sub Enable
SXCBR13
3 I 75
Sub Enable
SXCBR14
3 I 93
Sub Enable
SXCBR15
3 I 121
Sub Enable
SXCBR16
3 I 132
Sub Enable
SXCBR17
3 I 159
Sub Enable
SXCBR18
3 I 178
Sub Enable
SXSWI01
3 I 197
Sub Enable
SXSWI02
3 I 215
Sub Enable
SXSWI03
3 I 234
Sub Enable
SXSWI04
3 I 252
Sub Enable
SXSWI05
3 I 271
630
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
Function
block
SPA
address
Description
Sub Enable
SXSWI06
3 I 290
Sub Enable
SXSWI07
3 I 309
Sub Enable
SXSWI08
3 I 328
Sub Enable
SXSWI09
3 I 347
Sub Enable
SXSWI10
3 I 360
Sub Enable
SXSWI11
3I 379
Sub Enable
SXSWI12
3 I 398
Sub Enable
SXSWI13
3 I 417
Sub Enable
SXSWI14
3 I 436
Sub Enable
SXSWI15
3 I 455
Sub Enable
SXSWI16
3 I 474
Sub Enable
SXSWI17
3 I 493
Sub Enable
SXSWI18
3 I 512
Sub Enable
SXSWI19
3 I 531
Sub Enable
SXSWI20
3 I 550
Sub Enable
SXSWI21
3 I 569
Sub Enable
SXSWI22
3 I 588
Sub Enable
SXSWI23
3 I 607
Sub Enable
SXSWI24
3 I 626
Sub Enable
SXSWI25
3 I 645
Sub Enable
SXSWI26
3 I 664
Sub Enable
SXSWI27
3 I 683
631
Technical reference manual
Section 15
Station communication
Name
1MRK505208-UUS D
Function
block
SPA
address
Description
Sub Enable
SXSWI28
3 I 702
Update Block
SXCBR01
2 I 7853
Update Block
SXCBR02
2 I 7864
Update Block
SXCBR03
2 I 7883
Update Block
SXCBR04
2 I 7905
Update Block
SXCBR05
2 I 7922
Update Block
SXCBR06
2 I 7943
Update Block
SXCBR07
2 I 7960
Update Block
SXCBR08
2 I 7981
Update Block
SXCBR09
3I6
Update Block
SXCBR10
3 I 27
Update Block
SXCBR11
3 I 44
Update Block
SXCBR12
3 I 57
Update Block
SXCBR13
3 I 73
Update Block
SXCBR14
3 I 92
Update Block
SXCBR15
3 I 122
Update Block
SXCBR16
3 I 131
Update Block
SXCBR17
3 I 160
Update Block
SXCBR18
3 I 177
Update Block
SXSWI01
3 I 198
Update Block
SXSWI02
3 I 214
Update Block
SXSWI03
3 I 236
632
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
Function
block
SPA
address
Description
Update Block
SXSWI04
3 I 253
Update Block
SXSWI05
3 I 273
Update Block
SXSWI06
3 I 291
Update Block
SXSWI07
3 I 311
Update Block
SXSWI08
3 I 329
Update Block
SXSWI09
3 I 349
Update Block
SXSWI10
3 I 358
Update Block
SXSWI11
3 I 377
Update Block
SXSWI12
3 I 396
Update Block
SXSWI13
3 I 415
Update Block
SXSWI14
3 I 434
Update Block
SXSWI15
3 I 453
Update Block
SXSWI16
3 I 472
Update Block
SXSWI17
3 I 491
Update Block
SXSWI18
3 I 510
Update Block
SXSWI19
3 I 529
Update Block
SXSWI20
3 I 548
Update Block
SXSWI21
3 I 567
Update Block
SXSWI22
3 I 586
Update Block
SXSWI23
3 I 605
Update Block
SXSWI24
3 I 624
Update Block
SXSWI25
3 I 643
633
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
15.3.3
Table 394:
Name
Operation
Table 395:
Name
Function
block
SPA
address
Description
Update Block
SXSWI26
3 I 662
Update Block
SXSWI27
3 I 681
Update Block
SXSWI28
3 I 700
Setting parameters
HORZCOMM Non group settings (basic)
Values (Range)
Unit
Disabled
Enabled
Step
Default
Description
Disabled
Operation
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation
TimerClass
Slow
Normal
Fast
Slow
Timer class
15.3.4
Technical data
Table 396:
Function
Value
Protocol
LON
Communication speed
1.25 Mbit/s
15.4
15.4.1
Introduction
In this section the most common addresses for commands and events are available. For
other addresses, refer to section "".
It is assumed that the reader is familiar with the SPA communication protocol in general.
634
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.4.2
Principle of operation
The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7 data
bits + even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more
information on recommended baud rate for each type of IED, refer to Technical
reference manual. Messages on the bus consist of ASCII characters.
The basic construction of the protocol assumes that the slave has no self-initiated need
to talk to the master but the master is aware of the data contained in the slaves and,
consequently, can request required data. In addition, the master can send data to the
slave. Requesting by the master can be performed either by sequenced polling (for
example, for event information) or only on demand.
The master requests slave information using request messages and sends information to
the slave in write messages. Furthermore, the master can send all slaves in common a
broadcast message containing time or other data. The inactive state of bus transmit and
receive lines is a logical "1".
SPA protocol
The tables below specify the SPA addresses for reading data from and writing data to
an IED with the SPA communication protocol implemented.
The SPA addresses for the mA input service values (MIM3 to MIM16) are found in
table 397.
Table 397:
Function block
SPA address
MIM3-CH1
4-O-6508
MIM3-CH2
4-O-6511
MIM3-CH3
4-O-6512
MIM3-CH4
4-O-6515
MIM3-CH5
4-O-6516
MIM3-CH6
4-O-6519
MIM4-CH1
4-O-6527
MIM4-CH2
4-O-6530
MIM4-CH3
4-O-6531
MIM4-CH4
4-O-6534
MIM4-CH5
4-O-6535
MIM4-CH6
4-O-6538
MIM5-CH1
4-O-6546
MIM5-CH2
4-O-6549
Section 15
Station communication
Function block
1MRK505208-UUS D
SPA address
MIM5-CH3
4-O-6550
MIM5-CH4
4-O-6553
MIM5-CH5
4-O-6554
MIM5-CH6
4-O-6557
MIM6-CH1
4-O-6565
MIM6-CH2
4-O-6568
MIM6-CH3
4-O-6569
MIM6-CH4
4-O-6572
MIM6-CH5
4-O-6573
MIM6-CH6
4-O-6576
MIM7-CH1
4-O-6584
MIM7-CH2
4-O-6587
MIM7-CH3
4-O-6588
MIM7-CH4
4-O-6591
MIM7-CH5
4-O-6592
MIM7-CH6
4-O-6595
MIM8-CH1
4-O-6603
MIM8-CH2
4-O-6606
MIM8-CH3
4-O-6607
MIM8-CH4
4-O-6610
MIM8-CH5
4-O-6611
MIM8-CH6
4-O-6614
MIM9-CH1
4-O-6622
MIM9-CH2
4-O-6625
MIM9-CH3
4-O-6626
MIM9-CH4
4-O-6629
MIM9-CH5
4-O-6630
MIM9-CH6
4-O-6633
MIM10-CH1
4-O-6641
MIM10-CH2
4-O-6644
MIM10-CH3
4-O-6645
MIM10-CH4
4-O-6648
MIM10-CH5
4-O-6649
MIM10-CH6
4-O-6652
MIM11-CH1
4-O-6660
MIM11-CH2
4-O-6663
636
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Function block
SPA address
MIM11-CH3
4-O-6664
MIM11-CH4
4-O-6667
MIM11-CH5
4-O-6668
MIM11-CH6
4-O-6671
MIM12-CH1
4-O-6679
MIM12-CH2
4-O-6682
MIM12-CH3
4-O-6683
MIM12-CH4
4-O-6686
MIM12-CH5
4-O-6687
MIM12-CH6
4-O-6690
MIM13-CH1
4-O-6698
MIM13-CH2
4-O-6701
MIM13-CH3
4-O-6702
MIM13-CH4
4-O-6705
MIM13-CH5
4-O-6706
MIM13-CH6
4-O-6709
MIM14-CH1
4-O-6717
MIM14-CH2
4-O-6720
MIM14-CH3
4-O-6721
MIM14-CH4
4-O-6724
MIM14-CH5
4-O-6725
MIM14-CH6
4-O-6728
MIM15-CH1
4-O-6736
MIM15-CH2
4-O-6739
MIM15-CH3
4-O-6740
MIM15-CH4
4-O-6743
MIM15-CH5
4-O-6744
MIM15-CH6
4-O-6747
MIM16-CH1
4-O-6755
MIM16-CH2
4-O-6758
MIM16-CH3
4-O-6759
MIM16-CH4
4-O-6762
MIM16-CH5
4-O-6763
MIM16-CH6
4-O-6766
637
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
The SPA addresses for the pulse counter values PCGGIO:1 to PCGGIO:16 are found
in table 398.
Table 398:
Function block
PCGGIO:1
3-O-5834
3-O-5833
PCGGIO:2
3-O-5840
3-O-5839
PCGGIO:3
3-O-5846
3-O-5845
PCGGIO:4
3-O-5852
3-O-5851
PCGGIO:5
3-O-5858
3-O-5857
PCGGIO:6
3-O-5864
3-O-5863
PCGGIO:7
3-O-5870
3-O-5869
PCGGIO:8
3-O-5876
3-O-5875
PCGGIO:9
3-O-5882
3-O-5881
PCGGIO:10
3-O-5888
3-O-5887
PCGGIO:11
3-O-5894
3-O-5893
PCGGIO:12
3-O-5900
3-O-5899
PCGGIO:13
3-O-5906
3-O-5905
PCGGIO:14
3-O-5912
3-O-5911
PCGGIO:15
3-O-5918
3-O-5917
PCGGIO:16
3-O-5924
3-O-5923
I/O modules
To read binary inputs, the SPA-addresses for the outputs of the I/O-module function
block are used, that is, the addresses for BI1 BI16. For SPA addresses, refer to
section "".
Single command, 16 signals
The IEDs can be provided with a function to receive signals either from a substation
automation system or from the local HMI. That receiving function block has 16
outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used.
Single command, 16 signals function consists of three function blocks; SINGLECMD:
1 to SINGLECMD:3 for 16 binary output signals each.
The signals can be individually controlled from the operator station, remote-control
gateway, or from the local HMI on the IED. For Single command, 16 signals function
block, SINGLECMD:1 to SINGLECMD:3, the address is for the first output. The other
638
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
outputs follow consecutively after the first one. For example, output 7 on the
SINGLECMD:2 function block has the 5O533 address.
The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to
SINGLECMD:3 are found in table 399.
Table 399:
Function block
SINGLECMD1-Cmd1
4-S-4639
5-O-511
SINGLECMD1-Cmd2
4-S-4640
5-O-512
SINGLECMD1-Cmd3
4-S-4641
5-O-513
SINGLECMD1-Cmd4
4-S-4642
5-O-514
SINGLECMD1-Cmd5
4-S-4643
5-O-515
SINGLECMD1-Cmd6
4-S-4644
5-O-516
SINGLECMD1-Cmd7
4-S-4645
5-O-517
SINGLECMD1-Cmd8
4-S-4646
5-O-518
SINGLECMD1-Cmd9
4-S-4647
5-O-519
SINGLECMD1-Cmd10
4-S-4648
5-O-520
SINGLECMD1-Cmd11
4-S-4649
5-O-521
SINGLECMD1-Cmd12
4-S-4650
5-O-522
SINGLECMD1-Cmdt13
4-S-4651
5-O-523
SINGLECMD1-Cmd14
4-S-4652
5-O-524
SINGLECMD1-Cmd15
4-S-4653
5-O-525
SINGLECMD1-Cmd16
4-S-4654
5-O-526
SINGLECMD2-Cmd1
4-S-4672
5-O-527
SINGLECMD2-Cmd2
4-S-4673
5-O-528
SINGLECMD2-Cmdt3
4-S-4674
5-O-529
SINGLECMD2-Cmd4
4-S-4675
5-O-530
SINGLECMD2-Cmd5
4-S-4676
5-O-531
SINGLECMD2-Cmd6
4-S-4677
5-O-532
SINGLECMD2-Cmd7
4-S-4678
5-O-533
SINGLECMD2-Cmd8
4-S-4679
5-O-534
SINGLECMD2-Cmd9
4-S-4680
5-O-535
SINGLECMD2-Cmd10
4-S-4681
5-O-536
SINGLECMD2-Cmd11
4-S-4682
5-O-537
SINGLECMD2-Cmd12
4-S-4683
5-O-538
SINGLECMD2-Cmd13
4-S-4684
5-O-539
SINGLECMD2-Cmd14
4-S-4685
5-O-540
639
Technical reference manual
Section 15
Station communication
Function block
1MRK505208-UUS D
SINGLECMD2-Cmd15
4-S-4686
5-O-541
SINGLECMD2-Cmd16
4-S-4687
5-O-542
SINGLECMD3-Cmd1
4-S-4705
5-O-543
SINGLECMD3-Cmd2
4-S-4706
5-O-544
SINGLECMD3-Cmd3
4-S-4707
5-O-545
SINGLECMD3-Cmd4
4-S-4708
5-O-546
SINGLECMD3-Cmd5
4-S-4709
5-O-547
SINGLECMD3-Cmd6
4-S-4710
5-O-548
SINGLECMD3-Cmd7
4-S-4711
5-O-549
SINGLECMD3-Cmd8
4-S-4712
5-O-550
SINGLECMD3-Cmd9
4-S-4713
5-O-551
SINGLECMD3-Cmd10
4-S-4714
5-O-552
SINGLECMD3-Cmd11
4-S-4715
5-O-553
SINGLECMD3-Cmd12
4-S-4716
5-O-554
SINGLECMD3-Cmd13
4-S-4717
5-O-555
SINGLECMD3-Cmd14
4-S-4718
5-O-556
SINGLECMD3-Cmd15
4-S-4719
5-O-557
SINGLECMD3-Cmd16
4-S-4720
5-O-558
Figure 281 shows an application example of how the user can, in a simplified way,
connect the command function via the configuration logic circuit in a protection IED
for control of a circuit breaker.
A pulse via the binary outputs of the IED normally performs this type of command
control. The SPA addresses to control the outputs OUT1 OUT16 in SINGLECMD:1
are shown in table 399.
640
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
PULSETIMER
SINGLECMD
BLOCK
INPUT
^OUT1
^OUT2
#1.000
OUT
^OUT3
^OUT4
^OUT5
^OUT6
^OUT8
^OUT9
^OUT10
^OUT11
PULSETIMER
AND
^OUT7
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
INPUT
#1.000
OUT
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
SYNCH OK
IEC05000717-2-en.vsd
IEC05000717 V2 EN
Figure 281:
The MODE input defines if the output signals from SINGLECMD:1 is off, steady or
pulsed signals. This is set in Parameter Setting Tool (PST) under: Setting / General
Settings / Control / Commands / Single Command.
Event function
Event function is intended to send time-tagged events to the station level (for example,
operator workplace) over the station bus. The events are there presented in an event
list. The events can be created from both internal logical signals and binary input
channels. All the internal signals are time tagged in the main processing module, while
the binary input channels are time tagged directly on each I/O module. The events are
produced according to the set event masks. The event masks are treated commonly for
both the LON and SPA channels. All events according to the event mask are stored in a
buffer, which contains up to 1000 events. If new events appear before the oldest event
in the buffer is read, the oldest event is overwritten and an overflow alarm appears.
Two special signals for event registration purposes are available in the IED, Terminal
Restarted (0E50) and Event buffer overflow (0E51).
The input parameters can be set individually from the Parameter Setting Tool (PST)
under: Setting / General Setting / Monitoring / Event Function as follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, event system itself make the reporting decision, (reporting criteria for
integers has no semantic, prefer to be set by the user)
641
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
The Status and event codes for the Event functions are found in table 400.
Table 400:
Event block
Single indication1)
Set event
Reset
event
Double indication
Intermedi Closed 10 Open 01 Undefined
ate 00
11
EVENT:1
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
22O1
22O2
22O3
22O4
22O5
22O6
22O7
22O8
22O9
22O10
22O11
22O12
22O13
22O14
22O15
22O16
22E33
22E35
22E37
22E39
22E41
22E43
22E45
22E47
22E49
22E51
22E53
22E55
22E57
22E59
22E61
22E63
22E32
22E34
22E36
22E38
22E40
22E42
22E44
22E46
22E48
22E50
22E52
22E54
22E56
22E58
22E60
22E62
22E0
22E4
22E8
22E12
22E16
22E20
22E24
22E28
-
22E1
22E5
22E9
22E13
22E17
22E21
22E25
22E29
-
22E2
22E6
22E10
22E14
22E18
22E22
22E26
22E30
-
22E3
22E7
22E11
22E15
22E19
22E23
22E27
22E31
-
EVENT:2
EVENT:3
EVENT:20
230..
240..
410..
23E..
24E..
41E..
23E..
24E..
41E..
23E..
24E..
41E..
23E..
23E..
41E..
23E..
24E..
41E..
23E..
24E..
41E..
These values are only applicable if the Event mask is masked OFF.
Connection of signals as events
Signals coming from different protection and control functions and must be sent as
events to the station level over the SPA-bus (or LON-bus) are connected to the Event
function block according to figure 282.
642
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
EVENT
Block
ILRANG
PSTO
UL12RANG
UL23RANG
UL31RANG
3I0RANG
3U0RANG
FALSE
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC07000065-2-en.vsd
IEC07000065 V2 EN
Figure 282:
15.4.2.1
Communication ports
The serial communication module (SLM) is used for SPA /IEC 60870-5-103/DNP and
LON communication. This module is a mezzanine module, and can be placed on the
Analog/Digital conversion module (ADM). The serial communication module can
have connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST,
bayonet) or a combination of plastic and glass fibre. Three different types are available
depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out, pay
special attention to the instructions concerning the handling and connection of the
optical fibres. The module is identified with a number on the label on the module.
The procedure to set the transfer rate and slave number can be found in the Installation
and commissioning manual for respective IEDs.
15.4.3
Design
When communicating locally with a computer (PC) in the station, using the rear SPA
port, the only hardware needed for a station monitoring system is:
Optical fibres
Opto/electrical converter for the PC
PC
When communicating remotely with a PC using the rear SPA port, the same hardware
and telephone modems are needed.
643
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.4.4
Table 401:
Name
Setting parameters
SPA Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
SlaveAddress
1 - 899
30
Slave address
BaudRate
300 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
9600 Bd
Table 402:
Name
Unit
Step
Default
Description
Operation
Disabled
Enabled
Disabled
Operation
SlaveAddress
1 - 899
30
Slave address
15.4.5
Technical data
Table 403:
Function
Value
Protocol
SPA
Communication speed
Slave number
1 to 899
15.5
15.5.1
Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must have
software that can interpret the IEC 60870-5-103 communication messages.
644
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.5.2
Principle of operation
15.5.2.1
General
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data transfer
rate up to 38400 bit/s. In IEC terminology, a primary station is a master and a
secondary station is a slave. The communication is based on a point-to-point principle.
The master must have software that can interpret IEC 60870-5-103 communication
messages.
Event handling
Report of analog service values (measurements)
Fault location
Command handling
Autorecloser ON/OFF
Teleprotection ON/OFF
Protection ON/OFF
LED reset
Characteristics 1 - 4 (Setting groups)
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard part
5: Transmission protocols, and to the section 103: Companion standard for the
informative interface of protection equipment.
The signal and setting tables specify the information types supported by the IEDs with
the communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in the
protection and control IED.
Commands in control direction
Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.
Number of instances: 1
645
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Message
Supported
19
LED Reset
Yes
23
Yes
24
Yes
25
Yes
26
Yes
Message
Supported
16
Auto-recloser on/off
Yes
17
Teleprotection on/off
Yes
18
Protection on/off
Yes
Message
Supported
Output signal 01
Yes
Output signal 02
Yes
Output signal 03
Yes
Output signal 04
Yes
Output signal 05
Yes
646
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Info. no.
Message
Supported
Output signal 06
Yes
Output signal 07
Yes
Output signal 08
Yes
Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each input signals.
Info. no.
Message
Supported
19
LED reset
Yes
20
No
21
TestMode
22
23
Yes
24
Yes
25
Yes
26
Yes
Section 15
Station communication
1MRK505208-UUS D
Message
Supported
48
Ground fault A
No
49
Ground fault B
No
50
Ground fault C
No
51
Yes
52
Yes
Message
Supported
64
Start L1
Yes
65
Start L2
Yes
66
Start L3
Yes
67
Start IN
Yes
84
General start
Yes
69
Trip L1
Yes
70
Trip L2
Yes
71
Trip L3
Yes
68
General trip
Yes
74
Fault forward/line
Yes
75
Fault reverse/busbar
Yes
78
Zone 1
Yes
648
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Info. no.
Message
Supported
79
Zone 2
Yes
80
Zone 3
Yes
81
Zone 4
Yes
82
Zone 5
Yes
76
Signal transmitted
Yes
77
Signal received
Yes
73
Yes
Message
Supported
64
Start L1
Yes
65
Start L2
Yes
66
Start L3
Yes
67
Start IN
Yes
84
General start
Yes
69
Trip L1
Yes
70
Trip L2
Yes
71
Trip L3
Yes
68
General trip
Yes
74
Fault forward/line
Yes
75
Fault reverse/busbar
Yes
85
Breaker failure
Yes
86
Yes
87
Yes
88
Yes
89
Yes
90
Yes
649
Technical reference manual
Section 15
Station communication
Info. no.
1MRK505208-UUS D
Message
Supported
91
Yes
92
Yes
93
Yes
Message
Supported
16
Autorecloser active
Yes
17
Teleprotection active
No
18
Protection active
No
128
CB on by Autorecloser
Yes
129
CB on by long-time AR
No
130
Autorecloser blocked
Yes
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.
Measurands in public range, I103Meas
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no.
Message
Supported
148
I_A
Yes
144, 145,
148
I_B
Yes
148
I_C
Yes
147
Yes
650
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Info. no.
Message
Supported
148
V_A
Yes
148
V_B
Yes
148
V_C
Yes
145, 146
V_A-V_B
Yes
147
Yes
146, 148
P, active power
Yes
146, 148
Q, reactive power
Yes
148
f, frequency
Yes
Message
*1)
Meas1
Supported
Yes
Meas2
Yes
Meas3
Yes
Meas4
Yes
Meas5
Yes
Meas6
Yes
Meas7
Yes
Meas8
Yes
Meas9
Yes
Disturbance recordings
The following elements are used in the ASDUs (Application Service Data Units)
defined in the standard.
Analog signals, 40-channels: the channel number for each channel has to be specified.
Channels used in the public range are 1 to 8 and with:
Section 15
Station communication
1MRK505208-UUS D
Channel number used for the remaining 32 analog signals are numbers in the private
range 64 to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION
TYPE and an INFORMATION NUMBER.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be
reported to the master. The last eight disturbances that are recorded are available for
transfer to the master. A successfully transferred disturbance (acknowledged by the
master) will not be reported to the master again.
When a new disturbance is recorded by the IED a list of available recorded
disturbances will be sent to the master, an updated list of available disturbances can be
sent whenever something has happened to disturbances in this list. For example, when
a disturbance is deteceted (by other client, for example, SPA) or when a new
disturbance has been recorded or when the master has uploaded a disturbance.
Deviations from the standard
Information sent in the disturbance upload is specified by the standard; however, some
of the information are adapted to information available in disturbance recorder in 670
series.
This section describes all data that is not exactly as specified in the standard.
ASDU23
In list of recorded disturbances (ASDU23) an information element named SOF
(status of fault) exists. This information element consists of 4 bits and indicates whether:
Bit TP: the protection equipment has tripped during the fault
Bit TM: the disturbance data are currently being transmitted
Bit TEST: the disturbance data have been recorded during normal operation or test
mode.
Bit OTEV: the disturbance data recording has been initiated by another event than
pick-up
652
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
The only information that is easily available is test-mode status. The other information
is always set (hard coded) to:
TP
TM
OTEV
Another information element in ASDU23 is the FAN (fault number). According to the
standard this is a number that is incremented when a protection function takes action.
In 670 series FAN is equal to disturbance number, which is incremented for each
disturbance.
ASDU26
When a disturbance has been selected by the master; (by sending ASDU24), the
protection equipment answers by sending ASDU26, which contains an information
element named NOF (number of grid faults). This number must indicate fault number
in the power system,that is, a fault in the power system with several trip and autoreclosing has the same NOF (while the FAN must be incremented). NOF is in 670
series, just as FAN, equal to disturbance number.
To get INF and FUN for the recorded binary signals there are parameters on the
disturbance recorder for each input. The user must set these parameters to whatever he
connects to the corresponding input.
No
number of loads
No
Optical interface
glass fibre
Yes
plastic fibre
Transmission speed
9600 bit/s
Yes
19200 bit/s
Yes
Link Layer
DFC-bit used
Yes
Connectors
connector F-SMA
No
connector BFOC/2.5
Yes
653
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Yes
Time-tagged message
Yes
Yes
Measurands I
Yes
Yes
Identification
Yes
Time synchronization
Yes
Yes
Measurands II
Yes
10
Generic data
No
11
Generic identification
No
23
Yes
26
Yes
27
Yes
28
Yes
29
Transmission of tags
Yes
30
Yes
31
End of transmission
Yes
Yes
Time synchronization
Yes
General interrogation
Yes
10
Generic data
No
20
General command
Yes
21
Generic command
No
24
Yes
25
Yes
No
Yes
Disturbance data
Yes
Private data
Yes
Generic services
No
654
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.5.2.2
Communication ports
The serial communication module (SLM) is used for SPA/IEC 60870-5-103/DNP and
LON communication. This module is a mezzanine module, and can be placed on the
Analog/Digital conversion module (ADM). The serial communication module can
have connectors for two plastic fibre cables (snap-in) or two glass fibre cables (ST,
bayonet) or a combination of plastic and glass fibre. Three different types are available
depending on type of fibre.
The incoming optical fibre is connected to the RX receiver input, and the outgoing
optical fibre to the TX transmitter output. When the fibre optic cables are laid out, pay
special attention to the instructions concerning the handling and connection of the
optical fibres. The module is identified with a number on the label on the module.
15.5.3
Function block
BLOCK
FUNTYPE
I103IEDCMD
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC05000689-2-en.vsd
IEC05000689 V2 EN
I103CMD
BLOCK
FUNTYPE
16-AR
17-DIFF
18-PROT
IEC05000684-2-en.vsd
IEC05000684 V2 EN
I103USRCMD
BLOCK
OUTPUT1
PULSEMOD
OUTPUT2
T
OUTPUT3
FUNTYPE
OUTPUT4
INFNO_1
OUTPUT5
INFNO_2
OUTPUT6
INFNO_3
OUTPUT7
INFNO_4
OUTPUT8
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000693-2-en.vsd
IEC05000693 V2 EN
655
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
I103IED
BLOCK
19_LEDRS
23_GRP1
24_GRP2
25_GRP3
26_GRP4
21_TESTM
FUNTYPE
IEC05000688-2-en.vsd
IEC05000688 V2 EN
I103USRDEF
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
FUNTYPE
INFNO_1
INFNO_2
INFNO_3
INFNO_4
INFNO_5
INFNO_6
INFNO_7
INFNO_8
IEC05000694-2-en.vsd
IEC05000694 V2 EN
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
FUNTYPE
IEC05000692-2-en.vsd
IEC05000692 V2 EN
I103EF
BLOCK
51_EFFW
52_EFREV
FUNTYPE
IEC05000685-2-en.vsd
IEC05000685 V2 EN
656
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
I103FLTDIS
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
76_TRANS
77_RECEV
73_SCL
FLTLOC
ARINPROG
FUNTYPE
IEC05000686-2-en.vsd
IEC05000686 V2 EN
I103FLTSTD
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
84_STGEN
69_TRL1
70_TRL2
71_TRL3
68_TRGEN
74_FW
75_REV
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FUNTYPE
IEC05000687-2-en.vsd
IEC05000687 V2 EN
I103AR
BLOCK
16_ARACT
128_CBON
130_UNSU
FUNTYPE
IEC05000683-2-en.vsd
IEC05000683 V2 EN
657
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
I103MEAS
BLOCK
I_A
I_B
I_C
IN
V_A
V_B
V_C
V_AB
V_N
P
Q
F
FUNTYPE
ANSI05000690-2-en.vsd
ANSI05000690 V2 EN
15.5.4
Table 405:
Name
Default
0
Description
Block of commands
Description
19-LEDRS
BOOLEAN
23-GRP1
BOOLEAN
24-GRP2
BOOLEAN
25-GRP3
BOOLEAN
26-GRP4
BOOLEAN
Table 406:
Name
BLOCK
Table 407:
Name
Default
0
Description
Block of commands
Description
16-AR
BOOLEAN
17-DIFF
BOOLEAN
18-PROT
BOOLEAN
658
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Table 408:
Name
BLOCK
Table 409:
Name
Default
BOOLEAN
Description
Block of commands
Description
OUTPUT1
BOOLEAN
Command output 1
OUTPUT2
BOOLEAN
Command output 2
OUTPUT3
BOOLEAN
Command output 3
OUTPUT4
BOOLEAN
Command output 4
OUTPUT5
BOOLEAN
Command output 5
OUTPUT6
BOOLEAN
Command output 6
OUTPUT7
BOOLEAN
Command output 7
OUTPUT8
BOOLEAN
Command output 8
Table 410:
Name
Default
Description
BLOCK
BOOLEAN
19_LEDRS
BOOLEAN
23_GRP1
BOOLEAN
24_GRP2
BOOLEAN
25_GRP3
BOOLEAN
26_GRP4
BOOLEAN
21_TESTM
BOOLEAN
Table 411:
Name
Default
Description
BLOCK
BOOLEAN
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
INPUT5
BOOLEAN
INPUT6
BOOLEAN
INPUT7
BOOLEAN
INPUT8
BOOLEAN
659
Technical reference manual
Section 15
Station communication
Table 412:
Name
1MRK505208-UUS D
Default
Description
BLOCK
BOOLEAN
32_MEASI
BOOLEAN
33_MEASU
BOOLEAN
37_IBKUP
BOOLEAN
38_VTFF
BOOLEAN
46_GRWA
BOOLEAN
47_GRAL
BOOLEAN
Table 413:
Name
Default
Description
BLOCK
BOOLEAN
51_EFFW
BOOLEAN
52_EFREV
BOOLEAN
Table 414:
Name
Default
Description
BLOCK
BOOLEAN
64_PU_A
BOOLEAN
65_PU_B
BOOLEAN
66_PU_C
BOOLEAN
67_STIN
BOOLEAN
84_STGEN
BOOLEAN
69_TR_A
BOOLEAN
70_TR_B
BOOLEAN
71_TR_C
BOOLEAN
68_TRGEN
BOOLEAN
74_FW
BOOLEAN
75_REV
BOOLEAN
78_ZONE1
BOOLEAN
79_ZONE2
BOOLEAN
80_ZONE3
BOOLEAN
81_ZONE4
BOOLEAN
82_ZONE5
BOOLEAN
76_TRANS
BOOLEAN
Section 15
Station communication
1MRK505208-UUS D
Name
Type
Default
Description
77_RECEV
BOOLEAN
73_SCL
REAL
FLTLOC
BOOLEAN
ARINPROG
BOOLEAN
Table 415:
Name
Default
Description
BLOCK
BOOLEAN
64_PU_A
BOOLEAN
65_PU_B
BOOLEAN
66_PU_C
BOOLEAN
67_STIN
BOOLEAN
84_STGEN
BOOLEAN
69_TR_A
BOOLEAN
70_TR_B
BOOLEAN
71_TR_C
BOOLEAN
68_TRGEN
BOOLEAN
74_FW
BOOLEAN
75_REV
BOOLEAN
85_BFP
BOOLEAN
86_MTR_A
BOOLEAN
87_MTR_B
BOOLEAN
88_MTR_C
BOOLEAN
89_MTRN
BOOLEAN
90_IOC
BOOLEAN
91_IOC
BOOLEAN
92_IEF
BOOLEAN
93_IEF
BOOLEAN
ARINPROG
BOOLEAN
661
Technical reference manual
Section 15
Station communication
Table 416:
Name
1MRK505208-UUS D
Default
Description
BLOCK
BOOLEAN
16_ARACT
BOOLEAN
128_CBON
BOOLEAN
130_UNSU
BOOLEAN
Table 417:
Name
Default
Description
BLOCK
BOOLEAN
I_A
REAL
0.0
I_B
REAL
0.0
I_C
REAL
0.0
IN
REAL
0.0
V_A
REAL
0.0
V_B
REAL
0.0
V_C
REAL
0.0
V_AB
REAL
0.0
V_N
REAL
0.0
REAL
0.0
REAL
0.0
REAL
0.0
Table 418:
Name
Default
Description
BLOCK
BOOLEAN
INPUT1
REAL
0.0
INPUT2
REAL
0.0
INPUT3
REAL
0.0
INPUT4
REAL
0.0
INPUT5
REAL
0.0
INPUT6
REAL
0.0
INPUT7
REAL
0.0
INPUT8
REAL
0.0
INPUT9
REAL
0.0
662
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.5.5
Table 419:
Setting parameters
IEC60870-5-103 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SlaveAddress
0 - 255
30
Slave address
BaudRate
9600 Bd
19200 Bd
9600 Bd
RevPolarity
Disabled
Enabled
Enabled
Invert polarity
CycMeasRepTime
1.0 - 3600.0
0.1
5.0
Table 420:
Name
Values (Range)
FUNTYPE
Table 421:
1 - 255
FunT
Step
1
Default
255
Description
Function type (1-255)
Name
Values (Range)
FUNTYPE
Table 422:
Unit
1 - 255
Unit
FunT
Step
1
Default
1
Description
Function type (1-255)
Name
Values (Range)
Unit
Step
Default
Description
PULSEMOD
0-1
Mode
0.200 - 60.000
0.001
0.400
Pulse length
FUNTYPE
1 - 255
FunT
INFNO_1
1 - 255
InfNo
INFNO_2
1 - 255
InfNo
INFNO_3
1 - 255
InfNo
INFNO_4
1 - 255
InfNo
INFNO_5
1 - 255
InfNo
INFNO_6
1 - 255
InfNo
INFNO_7
1 - 255
InfNo
INFNO_8
1 - 255
InfNo
Table 423:
Name
FUNTYPE
Values (Range)
1 - 255
Unit
FunT
Step
1
Default
1
Description
Function type (1-255)
663
Technical reference manual
Section 15
Station communication
Table 424:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
FUNTYPE
1 - 255
FunT
INFNO_1
1 - 255
InfNo
INFNO_2
1 - 255
InfNo
INFNO_3
1 - 255
InfNo
INFNO_4
1 - 255
InfNo
INFNO_5
1 - 255
InfNo
INFNO_6
1 - 255
InfNo
INFNO_7
1 - 255
InfNo
INFNO_8
1 - 255
InfNo
Table 425:
Name
FUNTYPE
Table 426:
Name
FUNTYPE
Table 427:
Name
FUNTYPE
Table 428:
Name
FUNTYPE
Table 429:
Name
FUNTYPE
Unit
FunT
Step
1
Default
1
Description
Function type (1-255)
Unit
FunT
Step
1
Default
160
Description
Function type (1-255)
Unit
FunT
Step
1
Default
128
Description
Function type (1-255)
Unit
FunT
Step
1
Default
1
Description
Function type (1-255)
Unit
FunT
Step
1
Default
1
Description
Function type (1-255)
664
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Table 430:
Name
Values (Range)
Unit
Step
Default
Description
RatedI_A
1 - 99999
3000
RatedI_B
1 - 99999
3000
RatedI_C
1 - 99999
3000
RatedI_N
1 - 99999
3000
RatedV_A
0.05 - 2000.00
kV
0.05
230.00
RatedV_B
0.05 - 2000.00
kV
0.05
230.00
RatedV_C
0.05 - 2000.00
kV
0.05
230.00
RatedV_AB
0.05 - 2000.00
kV
0.05
400.00
RatedV_N
0.05 - 2000.00
kV
0.05
230.00
RatedP
0.00 - 2000.00
MW
0.05
1200.00
RatedQ
0.00 - 2000.00
MVA
0.05
1200.00
RatedF
50.0 - 60.0
Hz
10.0
50.0
FUNTYPE
1 - 255
FunT
Table 431:
Name
Values (Range)
Unit
Step
Default
Description
FUNTYPE
1 - 255
FunT
25
INFNO
1 - 255
InfNo
RatedMeasur1
0.05 10000000000.00
0.05
1000.00
RatedMeasur2
0.05 10000000000.00
0.05
1000.00
RatedMeasur3
0.05 10000000000.00
0.05
1000.00
RatedMeasur4
0.05 10000000000.00
0.05
1000.00
RatedMeasur5
0.05 10000000000.00
0.05
1000.00
RatedMeasur6
0.05 10000000000.00
0.05
1000.00
RatedMeasur7
0.05 10000000000.00
0.05
1000.00
RatedMeasur8
0.05 10000000000.00
0.05
1000.00
RatedMeasur9
0.05 10000000000.00
0.05
1000.00
665
Technical reference manual
Section 15
Station communication
15.5.6
1MRK505208-UUS D
Technical data
Table 432:
Function
Value
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
666
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.6
15.6.1
Function block
GOOSEINTLKRCV
BLOCK
^RESREQ
^RESGRANT
^APP1_OP
^APP1_CL
APP1VAL
^APP2_OP
^APP2_CL
APP2VAL
^APP3_OP
^APP3_CL
APP3VAL
^APP4_OP
^APP4_CL
APP4VAL
^APP5_OP
^APP5_CL
APP5VAL
^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COM_VAL
IEC07000048-2-en.vsd
IEC07000048 V2 EN
Figure 283:
667
Technical reference manual
Section 15
Station communication
15.6.2
1MRK505208-UUS D
Table 434:
Name
Default
0
Description
Block of output signals
Description
RESREQ
BOOLEAN
Reservation request
RESGRANT
BOOLEAN
Reservation granted
APP1_OP
BOOLEAN
APP1_CL
BOOLEAN
APP1VAL
BOOLEAN
APP2_OP
BOOLEAN
APP2_CL
BOOLEAN
APP2VAL
BOOLEAN
APP3_OP
BOOLEAN
APP3_CL
BOOLEAN
APP3VAL
BOOLEAN
APP4_OP
BOOLEAN
APP4_CL
BOOLEAN
APP4VAL
BOOLEAN
APP5_OP
BOOLEAN
APP5_CL
BOOLEAN
APP5VAL
BOOLEAN
APP6_OP
BOOLEAN
APP6_CL
BOOLEAN
APP6VAL
BOOLEAN
APP7_OP
BOOLEAN
APP7_CL
BOOLEAN
APP7VAL
BOOLEAN
APP8_OP
BOOLEAN
APP8_CL
BOOLEAN
APP8VAL
BOOLEAN
APP9_OP
BOOLEAN
APP9_CL
BOOLEAN
APP9VAL
BOOLEAN
Section 15
Station communication
1MRK505208-UUS D
Name
15.6.3
Table 435:
Type
Description
APP10_OP
BOOLEAN
APP10_CL
BOOLEAN
APP10VAL
BOOLEAN
APP11_OP
BOOLEAN
APP11_CL
BOOLEAN
APP11VAL
BOOLEAN
APP12_OP
BOOLEAN
APP12_CL
BOOLEAN
APP12VAL
BOOLEAN
APP13_OP
BOOLEAN
APP13_CL
BOOLEAN
APP13VAL
BOOLEAN
APP14_OP
BOOLEAN
APP14_CL
BOOLEAN
APP14VAL
BOOLEAN
APP15_OP
BOOLEAN
APP15_CL
BOOLEAN
APP15VAL
BOOLEAN
COM_VAL
BOOLEAN
Setting parameters
GOOSEINTLKRCV Non group settings (basic)
Name
Operation
Values (Range)
Disabled
Enabled
Unit
-
Step
-
Default
Disabled
Description
Operation Disabled/Enabled
669
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.7
15.7.1
Function block
GOOSEBINRCV
BLOCK
^OUT1
OUT1VAL
^OUT2
OUT2VAL
^OUT3
OUT3VAL
^OUT4
OUT4VAL
^OUT5
OUT5VAL
^OUT6
OUT6VAL
^OUT7
OUT7VAL
^OUT8
OUT8VAL
^OUT9
OUT9VAL
^OUT10
OUT10VAL
^OUT11
OUT11VAL
^OUT12
OUT12VAL
^OUT13
OUT13VAL
^OUT14
OUT14VAL
^OUT15
OUT15VAL
^OUT16
OUT16VAL
IEC07000047-2-en.vsd
IEC07000047 V2 EN
Figure 284:
15.7.2
Table 437:
Name
Default
0
Description
Block of output signals
Description
OUT1
BOOLEAN
Binary output 1
OUT1VAL
BOOLEAN
OUT2
BOOLEAN
Binary output 2
Section 15
Station communication
1MRK505208-UUS D
Name
15.7.3
Table 438:
Type
Description
OUT2VAL
BOOLEAN
OUT3
BOOLEAN
Binary output 3
OUT3VAL
BOOLEAN
OUT4
BOOLEAN
Binary output 4
OUT4VAL
BOOLEAN
OUT5
BOOLEAN
Binary output 5
OUT5VAL
BOOLEAN
OUT6
BOOLEAN
Binary output 6
OUT6VAL
BOOLEAN
OUT7
BOOLEAN
Binary output 7
OUT7VAL
BOOLEAN
OUT8
BOOLEAN
Binary output 8
OUT8VAL
BOOLEAN
OUT9
BOOLEAN
Binary output 9
OUT9VAL
BOOLEAN
OUT10
BOOLEAN
Binary output 10
OUT10VAL
BOOLEAN
OUT11
BOOLEAN
Binary output 11
OUT11VAL
BOOLEAN
OUT12
BOOLEAN
Binary output 12
OUT12VAL
BOOLEAN
OUT13
BOOLEAN
Binary output 13
OUT13VAL
BOOLEAN
OUT14
BOOLEAN
Binary output 14
OUT14VAL
BOOLEAN
OUT15
BOOLEAN
Binary output 15
OUT15VAL
BOOLEAN
OUT16
BOOLEAN
Binary output 16
OUT16VAL
BOOLEAN
Setting parameters
GOOSEBINRCV Non group settings (basic)
Name
Operation
Values (Range)
Disabled
Enabled
Unit
-
Step
-
Default
Disabled
Description
Operation Disabled/Enabled
671
Technical reference manual
Section 15
Station communication
15.8
1MRK505208-UUS D
15.8.1
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
MULTICMDRCV
MULTICMDSND
Introduction
The IED can be provided with a function to send and receive signals to and from other
IEDs via the interbay bus. The send and receive function blocks has 16 outputs/inputs
that can be used, together with the configuration logic circuits, for control purposes
within the IED or via binary outputs. When it is used to communicate with other IEDs,
these IEDs have a corresponding Multiple transmit function block with 16 outputs to
send the information received by the command block.
15.8.2
Principle of operation
Two multiple transmit function blocks MULTICMDSND:1 and MULTICMDSND:2
and 8 slow multiple transmit function blocks MULTICMDSND:3 to MULTICMDSND:
10 are available in the IED.
Sixteen signals can be connected and they will then be sent to the multiple command
block in the other IED. The connections are set with the LON Network Tool (LNT).
Twelve multiple command function blocks MULTICMDRCV:1 to MULTICMDRCV:
12 with fast execution time and 48 multiple command function blocks MULTICMDRCV:
13 to MULTICMDRCV:60 with slower execution time are available in the IED.
Multiple command function block MULTICMDRCV has 16 outputs combined in one
block, which can be controlled from other IEDs.
The output signals, here OUTPUT1 to OUTPUT16, are then available for
configuration to built-in functions or via the configuration logic circuits to the binary
outputs of the IED.
MULTICMDRCV also has a supervision function, which sets the output VALID to 0
if the block does not receive data within set maximum time.
672
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
15.8.3
Design
15.8.3.1
General
The output signals can be of the types Disabled, Steady, or Pulse. The setting is done
on the MODE settings, common for the whole block, from PCM600.
15.8.4
0 = Disabled sets all outputs to 0, independent of the values sent from the station
level, that is, the operator station or remote-control gateway.
1 = Steady sets the outputs to a steady signal 0 or 1, depending on the values sent
from the station level.
2 = Pulse gives a pulse with one execution cycle duration, if a value sent from the
station level is changed from 0 to 1. That means that the configured logic
connected to the command function blocks may not have a cycle time longer than
the execution cycle time for the command function block.
Function block
MULTICMDRCV
BLOCK
ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID
IEC06000007-2-en.vsd
IEC06000007 V2 EN
Figure 285:
673
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
MULTICMDSND
BLOCK
ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
IEC06000008-2-en.vsd
IEC06000008 V2 EN
Figure 286:
15.8.5
Table 440:
Name
Default
0
Description
Block of function
Default
Description
BLOCK
BOOLEAN
Block of function
INPUT1
BOOLEAN
Input 1
INPUT2
BOOLEAN
Input 2
INPUT3
BOOLEAN
Input 3
INPUT4
BOOLEAN
Input 4
INPUT5
BOOLEAN
Input 5
INPUT6
BOOLEAN
Input 6
INPUT7
BOOLEAN
Input 7
INPUT8
BOOLEAN
Input 8
INPUT9
BOOLEAN
Input 9
INPUT10
BOOLEAN
Input 10
INPUT11
BOOLEAN
Input 11
INPUT12
BOOLEAN
Input 12
INPUT13
BOOLEAN
Input 13
674
Technical reference manual
Section 15
Station communication
1MRK505208-UUS D
Name
Type
Default
Description
INPUT14
BOOLEAN
Input 14
INPUT15
BOOLEAN
Input 15
INPUT16
BOOLEAN
Input 16
Table 441:
Name
Description
ERROR
BOOLEAN
MultiReceive error
NEWDATA
BOOLEAN
OUTPUT1
BOOLEAN
Output 1
OUTPUT2
BOOLEAN
Output 2
OUTPUT3
BOOLEAN
Output 3
OUTPUT4
BOOLEAN
Output 4
OUTPUT5
BOOLEAN
Output 5
OUTPUT6
BOOLEAN
Output 6
OUTPUT7
BOOLEAN
Output 7
OUTPUT8
BOOLEAN
Output 8
OUTPUT9
BOOLEAN
Output 9
OUTPUT10
BOOLEAN
Output 10
OUTPUT11
BOOLEAN
Output 11
OUTPUT12
BOOLEAN
Output 12
OUTPUT13
BOOLEAN
Output 13
OUTPUT14
BOOLEAN
Output 14
OUTPUT15
BOOLEAN
Output 15
OUTPUT16
BOOLEAN
Output 16
VALID
BOOLEAN
Table 442:
Name
ERROR
Description
MultiSend error
675
Technical reference manual
Section 15
Station communication
15.8.6
Table 443:
Name
1MRK505208-UUS D
Setting parameters
MULTICMDRCV Non group settings (basic)
Values (Range)
Unit
Step
Default
Description
tMaxCycleTime
0.050 - 200.000
0.001
11.000
tMinCycleTime
0.000 - 200.000
0.001
0.000
Mode
Steady
Pulsed
Steady
tPulseTime
0.000 - 60.000
0.001
0.200
Table 444:
Name
Unit
Step
Default
Description
tMaxCycleTime
0.000 - 200.000
0.001
5.000
tMinCycleTime
0.000 - 200.000
0.001
0.000
676
Technical reference manual
Section 16
Remote communication
1MRK505208-UUS D
Section 16
Remote communication
16.1
16.1.1
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
BinSignReceive
BinSignTransm
Introduction
The remote end data communication is used either for the transmission of current
values together with maximum 8 binary signals in the line differential protection, or for
transmission of only binary signals, up to 192 signals, in the other 670 series IEDs. The
binary signals are freely configurable and can, thus, be used for any purpose, for
example, communication scheme related signals, transfer trip and/or other binary
signals between IEDs.
Communication between two IEDs requires that each IED is equipped with an LDCM
(Line Data Communication Module). The LDCMs are then interfaces to a 64 kbit/s
communication channel for duplex communication between the IEDs.
The IED can be equipped with up to two short range LDCM.
16.1.2
Principle of operation
The communication is made on standard ITU (CCITT) PCM digital 64 kbit/s channels.
It is a two-way communication where telegrams are sent every 5 ms (same in 50 Hz
and 60 Hz), exchanging information between two IEDs. The format used is C37.94 and
one telegram consists of start and stop flags, address, data to be transmitted, Cyclic
Redundancy Check (CRC) and Yellow bit (which is associated with C37.94).
677
Technical reference manual
Section 16
Remote communication
Start
flag
8 bits
1MRK505208-UUS D
Information
n x 16 bits
CRC
Stop
flag
16 bits
8 bits
en01000134.vsd
IEC01000134 V1 EN
Figure 287:
The start and stop flags are the 0111 1110 sequence (7E hexadecimal), defined in the
HDLC standard. The CRC is designed according to the standard CRC16 definition.
The optional address field in the HDLC frame is not used instead a separate addressing
is included in the data field.
The address field is used for checking that the received message originates from the
correct equipment. There is always a risk that multiplexers occasionally mix the
messages up. Each terminal in the system is given a number. The terminal is then
programmed to accept messages from a specific terminal number. If the CRC function
detects a faulty message, the message is thrown away and not used in the evaluation.
When the communication is used for line differential purpose, the transmitted data
consists of three currents, clock information, trip-, block- and alarm-signals and eight
binary signals which can be used for any purpose. The three currents are represented as
sampled values.
When the communication is used exclusively for binary signals, the full data capacity
of the communication channel is used for the binary signal purpose which gives the
capacity of 192 signals.
678
Technical reference manual
Section 16
Remote communication
1MRK505208-UUS D
16.1.3
Function block
LDCMRecBinStat1
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
REMCOMF
LOWLEVEL
IEC07000043-2-en.vsd
IEC07000043 V2 EN
LDCMRecBinStat2
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC07000044-2-en.vsd
IEC07000044 V2 EN
Figure 288:
LDCMRecBinStat3
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
REMGPSER
SUBSTITU
LOWLEVEL
IEC05000451-2-en.vsd
IEC05000451 V2 EN
Figure 289:
679
Technical reference manual
Section 16
Remote communication
16.1.4
1MRK505208-UUS D
Description
COMFAIL
BOOLEAN
YBIT
BOOLEAN
NOCARR
BOOLEAN
NOMESS
BOOLEAN
ADDRERR
BOOLEAN
LNGTHERR
BOOLEAN
CRCERROR
BOOLEAN
REMCOMF
BOOLEAN
LOWLEVEL
BOOLEAN
Table 446:
Name
Description
COMFAIL
BOOLEAN
YBIT
BOOLEAN
NOCARR
BOOLEAN
NOMESS
BOOLEAN
ADDRERR
BOOLEAN
LNGTHERR
BOOLEAN
CRCERROR
BOOLEAN
TRDELERR
BOOLEAN
SYNCERR
BOOLEAN
REMCOMF
BOOLEAN
REMGPSER
BOOLEAN
SUBSTITU
BOOLEAN
LOWLEVEL
BOOLEAN
680
Technical reference manual
Section 16
Remote communication
1MRK505208-UUS D
Table 447:
Name
16.1.5
Table 448:
Type
Description
COMFAIL
BOOLEAN
YBIT
BOOLEAN
NOCARR
BOOLEAN
NOMESS
BOOLEAN
ADDRERR
BOOLEAN
LNGTHERR
BOOLEAN
CRCERROR
BOOLEAN
TRDELERR
BOOLEAN
SYNCERR
BOOLEAN
REMCOMF
BOOLEAN
REMGPSER
BOOLEAN
SUBSTITU
BOOLEAN
LOWLEVEL
BOOLEAN
Setting parameters
LDCMRecBinStat1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ChannelMode
Disabled
Enabled
OutOfService
Enabled
TerminalNo
0 - 255
RemoteTermNo
0 - 255
CommSync
Slave
Master
Slave
OptoPower
LowPower
HighPower
LowPower
ComFailAlrmDel
5 - 500
ms
100
ComFailResDel
5 - 500
ms
100
InvertPolX21
Disabled
Enabled
Disabled
681
Technical reference manual
Section 16
Remote communication
Table 449:
Name
1MRK505208-UUS D
Unit
Step
Default
Description
ChannelMode
Disabled
Enabled
OutOfService
Enabled
NAMECH1
0 - 13
LDCM#-CH1
TerminalNo
0 - 255
RemoteTermNo
0 - 255
NAMECH2
0 - 13
LDCM#-CH2
DiffSync
Echo
GPS
Echo
GPSSyncErr
Block
Echo
Block
CommSync
Slave
Master
Slave
NAMECH3
0 - 13
LDCM#-CH3
OptoPower
LowPower
HighPower
LowPower
NAMECH4
0 - 13
LDCM#-CH4
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
CT-GRP1
ComFailAlrmDel
5 - 500
ms
100
ComFailResDel
5 - 500
ms
100
RedChSwTime
5 - 500
ms
RedChRturnTime
5 - 500
ms
100
AsymDelay
-20.00 - 20.00
ms
0.01
0.00
AnalogLatency
2 - 20
remAinLatency
2 - 20
MaxTransmDelay
0 - 40
ms
20
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
0-25kA
Compression range
682
Technical reference manual
Section 16
Remote communication
1MRK505208-UUS D
Name
Values (Range)
Unit
Step
Default
Description
MaxtDiffLevel
200 - 2000
us
600
DeadbandtDiff
200 - 1000
us
300
InvertPolX21
Disabled
Enabled
Disabled
Table 450:
Name
Values (Range)
Unit
Step
Default
Description
ChannelMode
Disabled
Enabled
OutOfService
Enabled
NAMECH1
0 - 13
LDCM#-CH1
TerminalNo
0 - 255
RemoteTermNo
0 - 255
NAMECH2
0 - 13
LDCM#-CH2
DiffSync
Echo
GPS
Echo
GPSSyncErr
Block
Echo
Block
CommSync
Slave
Master
Slave
NAMECH3
0 - 13
LDCM#-CH3
OptoPower
LowPower
HighPower
LowPower
NAMECH4
0 - 13
LDCM#-CH4
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel
CT-GRP1
ComFailAlrmDel
5 - 500
ms
100
ComFailResDel
5 - 500
ms
100
RedChSwTime
5 - 500
ms
RedChRturnTime
5 - 500
ms
100
AsymDelay
-20.00 - 20.00
ms
0.01
0.00
AnalogLatency
2 - 20
Section 16
Remote communication
Name
1MRK505208-UUS D
Values (Range)
Unit
Step
Default
Description
remAinLatency
2 - 20
MaxTransmDelay
0 - 40
ms
20
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
0-25kA
Compression range
MaxtDiffLevel
200 - 2000
us
600
DeadbandtDiff
200 - 1000
us
300
InvertPolX21
Disabled
Enabled
Disabled
16.2
16.2.1
Function block
LDCMTRN
^CT1L1
^CT1L2
^CT1L3
^CT1N
^CT2L1
^CT2L2
^CT2L3
^CT2N
IEC10000017-1-en.vsd
IEC10000017 V1 EN
Figure 290:
684
Technical reference manual
Section 16
Remote communication
1MRK505208-UUS D
16.2.2
Default
Description
CT1L1
STRING
CT1L2
STRING
CT1L3
STRING
CT1N
STRING
CT2L1
STRING
CT2L2
STRING
CT2L3
STRING
CT2N
STRING
685
Technical reference manual
686
Section 17
IED hardware
1MRK505208-UUS D
Section 17
IED hardware
17.1
Overview
17.1.1
Close
Open
xx04000460_ansi.e
ANSI04000460 V1 EN
Figure 291:
687
Technical reference manual
Section 17
IED hardware
17.1.2
Table 452:
1MRK505208-UUS D
Module
Rear Positions
PSM
X11
SLM
X301:A, B, C, D
X302
LDCM or RS485
X303
OEM
X311:A, B, C, D
X312, 313
TRM
X401
1MRK002801-AC-2-670-1.2-PG V1 EN
688
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Table 453:
Module
Rear Positions
PSM
X11
SLM
X301:A, B, C, D
X302
LDCM or RS485
X303
OEM
X311:A, B, C, D
X312, X313
TRM
X401
1MRK002801-AC-3-670-1.2-PG V1 EN
689
Technical reference manual
Section 17
IED hardware
Table 454:
1MRK505208-UUS D
Module
Rear Positions
PSM
X11
BIM, BOM,
SOM, IOM or
MIM
SLM
X301:A, B, C, D
LDCM, IRIG-B or
RS485
X302
LDCM or RS485
X303
OEM
X311:A, B, C, D
LDCM, RS485 or
GTM
TRM 1
X401
TRM 2
X411
1MRK002801-AC-6-670-1.2-PG V1 EN
17.2
Hardware modules
17.2.1
Overview
Table 455:
Basic modules
Module
Description
690
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Module
Description
Table 456:
Module
Description
17.2.2
17.2.2.1
Introduction
The combined backplane module (CBM) carries signals between modules in an IED.
691
Technical reference manual
Section 17
IED hardware
17.2.2.2
1MRK505208-UUS D
Functionality
The Compact PCI makes 3.3V or 5V signaling in the backplane possible. The CBM
backplane and connected modules are 5V PCI-compatible.
Some pins on the Compact PCI connector are connected to the CAN bus, to be able to
communicate with CAN based modules.
If a modules self test discovers an error it informs other modules using the Internal Fail
signal IRF.
17.2.2.3
Design
There are two basic versions of the CBM:
Each PCI connector consists of 2 compact PCI receptacles. The euro connectors are
connected to the CAN bus and used for I/O modules and power supply.
2
en05000516.vsd
IEC05000516 V1 EN
Figure 292:
Pos Description
1
CAN slots
CPCI slots
692
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
en05000755.vsd
IEC05000755 V1 EN
Figure 293:
Pos Description
1
CAN slots
CPCI slots
en05000756.vsd
IEC05000756 V1 EN
Figure 294:
Pos Description
1
CBM
693
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.3
17.2.3.1
Introduction
The Universal Backplane Module (UBM) is part of the IED backplane and is mounted
above the CBM. It connects the Transformer input module (TRM) to the Analog
digital conversion module (ADM) and the Numerical module (NUM).
17.2.3.2
Functionality
The Universal Backplane Module connects the CT and VT analog signals from the
transformer input module to the analog digital converter module. The Numerical
processing module (NUM) is also connected to the UBM. The ethernet contact on the
front panel as well as the internal ethernet contacts are connected to the UBM which
provides the signal path to the NUM board.
17.2.3.3
Design
It connects the Transformer input module (TRM) to the Analog digital conversion
module (ADM) and the Numerical module (NUM).
The UBM exists in 2 versions.
for IEDs with two TRM and two ADM. It has four 48 pin euro connectors and one
96 pin euro connector, see figure 296
for IEDs with one TRM and one ADM. It has two 48 pin euro connectors and one
96 pin euro connector, see figure 297.
The 96 pin euro connector is used to connect the NUM board to the backplane. The 48
pin connectors are used to connect the TRM and ADM.
694
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
TRM
ADM
NUM
AD Data
X1
X2
X3
X4
RS485
X10
X10
Ethernet
Front
LHMI connection
port
Ethernet
X5
en05000489.vsd
IEC05000489 V1 EN
Figure 295:
en05000757.vsd
IEC05000757 V1 EN
Figure 296:
en05000758.vsd
IEC05000758 V1 EN
Figure 297:
695
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
en05000759.vsd
IEC05000759 V1 EN
Figure 298:
Pos Description
1
UBM
17.2.4
17.2.4.1
Introduction
The Numeric processing module (NUM), is a CPU-module that handles all protection
functions and logic.
For communication with high speed modules, e.g. analog input modules and high
speed serial interfaces, the NUM is equipped with a Compact PCI bus. The NUM is the
compact PCI system card i.e. it controls bus mastering, clock distribution and receives
interrupts.
696
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.4.2
Functionality
The NUM, Numeric processing module is a high performance, standard off-the-shelf
compact-PCI CPU module. It is 6U high and occupies one slot. Contact with the
backplane is via two compact PCI connectors and an euro connector.
The NUM has one PMC slot (32-bit IEEE P1386.1 compliant) and two PC-MIP slots
onto which mezzanine cards such as SLM or LDCM can be mounted.
To reduce bus loading of the compact PCI bus in the backplane the NUM has one
internal PCI bus for internal resources and the PMC/PC-MIP slots and external PCI
accesses through the backplane are buffered in a PCI/PCI bridge.
The application code and configuration data are stored in flash memory using a flash
file system.
The NUM is equipped with a real time clock. It uses a capacitor for power backup of
the real time clock.
No forced cooling is used on this standard module because of the low power dissipation.
697
Technical reference manual
Section 17
IED hardware
17.2.4.3
1MRK505208-UUS D
Block diagram
Compact
Flash
Logic
PMC
connector
Memory
Ethernet
UBM
connector
PC-MIP
PCI-PCIbridge
Backplane
connector
North
bridge
CPU
en04000473.vsd
IEC04000473 V1 EN
Figure 299:
17.2.5
17.2.5.1
Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the terminal and the battery system. An internal fail alarm output is
available.
698
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.5.2
Design
There are two types of the power supply module. They are designed for different DC
input voltage ranges see table 457. The power supply module contains a built-in, selfregulated DC/DC converter that provides full isolation between the terminal and the
external battery system.
Power
supply
Filter
Backplane connector
Input connector
Block diagram
Supervision
99000516.vsd
IEC99000516 V1 EN
Figure 300:
17.2.5.3
Technical data
Table 457:
Quantity
17.2.6
Rated value
Nominal range
EL = (24 - 60) V
EL = (90 - 250) V
EL 20%
EL 20%
Power consumption
50 W typically
Section 17
IED hardware
1MRK505208-UUS D
17.2.7
17.2.7.1
Introduction
The transformer input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers. The module
has twelve inputs in different combinations of currents and voltage inputs.
Alternative connectors of Ring lug or Compression type can be ordered.
17.2.7.2
Design
The transformer module has 12 input transformers. There are several versions of the
module, each with a different combination of voltage and current input transformers.
Basic versions:
The rated values and channel type, measurement or protection, of the current inputs are
selected at order.
Transformer input module for measuring should not be used with
current transformers intended for protection purposes, due to
limitations in overload characteristics.
The TRM is connected to the ADM and NUM via the UBM.
For configuration of the input and output signals, refer to section "Signal matrix for
analog inputs SMAI".
17.2.7.3
Technical data
Table 458:
TRM - Energizing quantities, rated values and limits for protection transformer modules
Quantity
Rated value
Current
In = 1 or 5 A
Operative range
(0-100) x In
Permissive overload
4 In cont.
100 In for 1 s *)
Nominal range
(0.2-40) In
700
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Quantity
Rated value
Burden
Ac voltage
Vn = 120 V
Operative range
(0340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
Frequency
fn = 60/50 Hz
*)
Nominal range
0.5288 V
5%
17.2.8
17.2.8.1
Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC slot.
The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards according
to table 459. The OEM card should always be mounted on the ADM board. The UBM
connects the ADM to the transformer input module (TRM).
Table 459:
PC-MIP cards
LDCM
SLM
LR-LDCM
OEM 1 ch
MR-LDCM
OEM 2 ch
X21-LDCM
IRIG-B
RS485
17.2.8.2
Design
The Analog digital conversion module input signals are voltage and current from the
transformer module. Shunts are used to adapt the current signals to the electronic
voltage level. To gain dynamic range for the current inputs, two shunts with separate A
\D channels are used for each input current. In this way a 20 bit dynamic range is
obtained with a 16 bit A\D converter.
Input signals are sampled with a sampling freqency of 5 kHz at 50 Hz system
frequency and 6 kHz at 60 Hz system frequency.
701
Section 17
IED hardware
1MRK505208-UUS D
The A\D converted signals goes through a filter with a cut off frequency of 500 Hz and
are reported to the numerical module (NUM) with 1 kHz at 50 Hz system frequency
and 1,2 kHz at 60 Hz system frequency.
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
Channel 11
Channel 12
AD1
AD2
1.2v
AD3
AD4
PMC
level shift
PC-MIP
2.5v
PCI to PCI
PC-MIP
en05000474.vsd
IEC05000474 V1 EN
Figure 301:
702
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.9
17.2.9.1
Introduction
The binary input module has 16 optically isolated inputs and is available in two
versions, one standard and one with enhanced pulse counting capabilities on the inputs
to be used with the pulse counter function. The binary inputs are freely programmable
and can be used for the input of logical signals to any of the functions. They can also
be included in the disturbance recording and event-recording functions. This enables
extensive monitoring and evaluation of operation of the IED and for all associated
electrical circuits.
17.2.9.2
Design
The Binary input module contains 16 optical isolated binary inputs. The voltage level
of the binary input is selected at order.
For configuration of the input signals, refer to section "Signal matrix for binary inputs
SMBI".
A signal discriminator detects and blocks oscillating signals. When blocked, a
hysteresis function may be set to release the input at a chosen frequency, making it
possible to use the input for pulse counting. The blocking frequency may also be set.
Well defined input high and input low voltages ensure normal operation at battery
supply earth faults, see figure 302 The figure shows the typical operating
characteristics of the binary inputs of the four voltage levels.
The standard version of binary inputs gives an improved capability to withstand
disturbances and should generally be used when pulse counting is not required. Inputs
are debounced by software.
I/O events are time stamped locally on each module for minimum time deviance and
stored by the event recorder if present.
703
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
[V]
300
176
144
88
72
38
32
19
17
24/30V
48/60V
110/125V
220/250V
xx99000517-2_ansi.vsd
ANSI99000517 V2 EN
Figure 302:
Operation uncertain
No operation
IEC99000517-ABC V1 EN
This binary input module communicates with the Numerical module (NUM) via the
CAN-bus on the backplane.
The design of all binary inputs enables the burn off of the oxide of the relay contact
connected to the input, despite the low, steady-state power consumption, which is
shown in figure 303 and 304.
704
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
[mA]
50
55
[ms]
en07000104-3.vsd
IEC07000104 V3 EN
Figure 303:
Approximate binary input inrush current for the standard version of BIM.
[mA]
50
5.5
[ms]
en07000105-1.vsd
IEC07000105 V2 EN
Figure 304:
Approximate binary input inrush current for the BIM version with
enhanced pulse counting capabilities.
705
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Process connector
Microcontroller
Backplane connector
CAN
Process connector
99000503-2.vsd
IEC99000503 V2 EN
Figure 305:
706
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.9.3
Technical data
Table 460:
Quantity
Rated value
Nominal range
Binary inputs
16
DC voltage, RL
24/30 V
48/60 V
125 V
220/250 V
RL 20%
RL 20%
RL 20%
RL 20%
Power consumption
24/30 V, 50mA
48/60 V, 50mA
125 V, 50mA
220/250 V, 50mA
220/250 V, 110mA
10 pulses/s max
Debounce filter
Settable 120ms
Table 461:
Quantity
Rated value
Nominal range
Binary inputs
16
DC voltage, RL
24/30 V
48/60 V
125 V
220/250 V
RL 20%
RL 20%
RL 20%
RL 20%
Power consumption
24/30 V
48/60 V
125 V
220/250 V
10 pulses/s max
40 pulses/s max
707
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.10
17.2.10.1
Introduction
The binary output module has 24 independent output relays and is used for trip output
or any signaling purpose.
17.2.10.2
Design
The binary output module (BOM) has 24 software supervised output relays. Each pair
of relays have a common power source input to the contacts, see figure 306. This
should be considered when connecting the wiring to the connection terminal on the
back of the IED.
The high closing and carrying current capability allows connection directly to breaker
trip and closing coils. If breaking capability is required to manage fail of the breaker
auxiliary contacts normally breaking the trip coil current, a parallel reinforcement is
required.
For configuration of the output signals, refer to section "Signal matrix for binary
outputs SMBO".
Output module
3
ANSI_xx00000299.vsd
ANSI00000299 V1 EN
Figure 306:
708
Technical reference manual
Section 17
IED hardware
Relay
Relay
Relay
Relay
Process connector
Relay
Relay
1MRK505208-UUS D
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Microcontroller
Relay
Relay
Backplane connector
Relay
CAN
Process connector
Relay
Relay
99000505-2-en.vsd
IEC99000505 V2 EN
Figure 307:
17.2.10.3
Technical data
Table 462:
BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
24
250 V AC, DC
1000 V rms
8A
10 A
12 A
709
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Function or quantity
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
17.2.11
17.2.11.1
Introduction
The static binary output module has six fast static outputs and six change over output
relays for use in applications with high speed requirements.
17.2.11.2
Design
The Static output module (SOM) have 6 normally open (NO) static outputs and 6
electromechanical relay outputs with change over contacts.
The SOM consists mainly of:
An MCU
A CAN-driver
6 static relays outputs
6 electromechanical relay outputs
A DC/DC converter
Connectors interfacing
710
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Drive &
Read back
Process connector
Drive &
Read back
Drive &
Read back
Drive &
Read back
Codeflash
Drive &
Read back
MCU
Drive &
Read back
CANdriver
Drive &
Read back
DC/DC
Drive &
Read back
Drive &
Read back
Internal_fail_n
AC_fail_n
RCAN_ID
Sync
Drive &
Read back
Backplane connector
Process connector
Drive &
Read back
Reset
Drive &
Read back
en07000115.vsd
IEC07000115 V1 EN
Figure 308:
711
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
IEC09000974-1-en.vsd
IEC09000974 V1 EN
Figure 309:
1MRK002802-AB-13-670-1.2-PG-ANSI V1 EN
Figure 310:
17.2.11.3
Technical data
Table 463:
SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Rated voltage
48 - 60 VDC
Number of outputs
~300 k
~810 k
No galvanic separation
No galvanic separation
Continuous
5A
5A
1.0s
10A
10A
0.2s
30A
30A
1.0s
10A
10A
Section 17
IED hardware
1MRK505208-UUS D
Function of quantity
Breaking capacity for DC with L/R
40ms
110V / 0.4A
60V / 0.75A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Operating time
Table 464:
<1ms
<1ms
SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical
relay outputs
Function of quantity
250V AC/DC
Number of outputs
1000V rms
8A
1.0s
10A
30A
1.0s
10A
48V / 1A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
713
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.12
17.2.12.1
Introduction
The binary input/output module is used when only a few input and output channels are
needed. The ten standard output channels are used for trip output or any signaling
purpose. The two high speed signal output channels are used for applications where
short operating time is essential. Eight optically isolated binary inputs cater for
required binary input information.
17.2.12.2
Design
The binary input/output module is available in two basic versions, one with
unprotected contacts and one with MOV (Metal Oxide Varistor) protected contacts.
Inputs are designed to allow oxide burn-off from connected contacts, and increase the
disturbance immunity during normal protection operate times. This is achieved with a
high peak inrush current while having a low steady-state current, see figure 303. Inputs
are debounced by software.
Well defined input high and input low voltages ensures normal operation at battery
supply ground faults, see figure 302.
The voltage level of the inputs is selected when ordering.
I/O events are time stamped locally on each module for minimum time deviance and
stored by the event recorder if present.
The binary I/O module, IOM, has eight optically isolated inputs and ten output relays.
One of the outputs has a change-over contact. The nine remaining output contacts are
connected in two groups. One group has five contacts with a common and the other
group has four contacts with a common, to be used as single-output channels, see
figure 311.
The binary I/O module also has two high speed output channels where a reed relay is
connected in parallel to the standard output relay.
For configuration of the input and output signals, refer to sections "Signal matrix for
binary inputs SMBI" and "Signal matrix for binary outputs SMBO".
714
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
IEC1MRK002801-AA11-UTAN-RAM V1 EN
IEC1MRK002802-AA-13 V1 EN
Figure 311:
The binary input/output module version with MOV protected contacts can for example
be used in applications where breaking high inductive load would cause excessive wear
of the contacts.
715
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
The test voltage across open contact is lower for this version of the
binary input/output module.
xx04000069.vsd
IEC04000069 V1 EN
Figure 312:
17.2.12.3
Technical data
Table 465:
Quantity
Rated value
Nominal range
Binary inputs
DC voltage, RL
24/30 V
48/60 V
125 V
220/250 V
RL 20%
RL 20%
RL 20%
RL 20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
10 pulses/s max
Debounce filter
Settable 1-20 ms
716
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Table 466:
IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
10
250 V AC, DC
250 V DC
1000 V rms
800 V DC
8A
10 A
12 A
8A
10 A
12 A
30 A
10 A
0.4 A
0.4 A
0.2 s
1.0 s
30 A
10 A
220250 V/0.4 A
110125 V/0.4 A
4860 V/0.2 A
2430 V/0.1 A
250 V/8.0 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
10 nF
IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC
61810-2)
Function or quantity
Binary outputs
IOM: 10
IOM: 2
250 V AC, DC
250 V DC
717
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
250 V rms
250 V rms
8A
10 A
12 A
8A
10 A
12 A
30 A
10 A
0.4 A
0.4 A
0.2 s
1.0 s
30 A
10 A
220250 V/0.4 A
110125 V/0.4 A
4860 V/0.2 A
2430 V/0.1 A
250 V/8.0 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
48 V/1 A
110 V/0.4 A
220 V/0.2 A
250 V/0.15 A
10 nF
17.2.13
17.2.13.1
Introduction
The milli-ampere input module is used to interface transducer signals in the 20 to +20
mA range from for example OLTC position, temperature or pressure transducers. The
module has six independent, galvanically separated channels.
718
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.13.2
Design
The Milliampere Input Module has six independent analog channels with separated
protection, filtering, reference, A/D-conversion and optical isolation for each input
making them galvanically isolated from each other and from the rest of the module.
For configuration of the input signals, refer to section "Signal matrix for mA inputs
SMMI".
The analog inputs measure DC current in the range of +/- 20 mA. The A/D converter
has a digital filter with selectable filter frequency. All inputs are calibrated separately
The filter parameters and the calibration factors are stored in a non-volatile memory on
the module.
The calibration circuitry monitors the module temperature and starts an automatical
calibration procedure if the temperature drift is outside the allowed range. The module
communicates, like the other I/O-modules on the serial CAN-bus.
719
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Protection
& filter
Protection
& filter
Volt-ref
DC/DC
Optoisolation
A/D Converter
Volt-ref
DC/DC
Optoisolation
A/D Converter
Volt-ref
DC/DC
Optoisolation
A/D Converter
Volt-ref
DC/DC
Optoisolation
A/D Converter
Protection
& filter
Volt-ref
DC/DC
Optoisolation
A/D Converter
Protection
& filter
Volt-ref
Memory
DC/DC
Microcontroller
Backplane connector
Protection
& filter
Optoisolation
A/D Converter
CAN
Process connector
Protection
& filter
99000504.vsd
IEC99000504 V1 EN
Figure 313:
17.2.13.3
Technical data
Table 468:
Quantity:
Rated value:
Nominal range:
Input resistance
Input range
5, 10, 20mA
0-5, 0-10, 0-20, 4-20mA
Power consumption
each mA-board
each mA input
2W
0.1 W
720
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.14
17.2.14.1
Introduction
The serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103,
DNP3 and LON communication. The module has two optical communication ports for
plastic/plastic, plastic/glass or glass/glass. One port is used for serial communication
(SPA, IEC 60870-5-103 and DNP3 port or dedicated IEC 60870-5-103 port depending
on ordered SLM module) and one port is dedicated for LON communication.
17.2.14.2
Design
The SLM is a PMC card and it is factory mounted as a mezzanine card on the NUM
module. Three variants of the SLM is available with different combinations of optical
fiber connectors, see figure 314. The plastic fiber connectors are of snap-in type and
the glass fiber connectors are of ST type.
IEC05000760 V1 EN
Figure 314:
LON port
721
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
IEC05000761 V1 EN
Figure 315:
Receiver, LON
Transmitter, LON
Observe that when the SLM connectors are viewed from the rear side
of the IED, contact 4 above is in the uppermost position and contact 1
in the lowest position.
17.2.14.3
Technical data
Table 469:
Quantity
Range or value
Optical connector
Fiber diameter
722
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Table 470:
Quantity
Range or value
Optical connector
diameter
17.2.15
17.2.15.1
Introduction
The Galvanic RS485 communication module (RS485) is used for DNP3.0
communication. The module has one RS485 communication port. The RS485 is a
balanced serial communication that can be used either in 2-wire or 4-wire connections.
A 2-wire connection uses the same signal for RX and TX and is a multidrop
communication with no dedicated Master or slave. This variant requires however a
control of the output. The 4-wire connection has separated signals for RX and TX
multidrop communication with a dedicated Master and the rest are slaves. No special
control signal is needed in this case.
17.2.15.2
Design
The RS485 is a PMC card and it is factory mounted as a mezzanine card on the NUM
module. The internal structure of the RS485 can be seen in figure 316:
PCI-con
PCIController
Local bus
to
wishbone
Status
Register
ID-chip
Control
Register
UART
RS485
tranceiver
Isolation
Rx
6-pole-connector
PCI-bus
Tx
Isolation
Isolation
Termination
Info
Register
Isolated
DC/DC
Soft
ground
2-pole
connector
PCI-con
Internal
bus
FPGA
32 MHz
IEC06000516 V1 EN
Figure 316:
723
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
The arrangement for the pins in the RS485 connector (figure 317) are presented in
table 471:
Table 471:
Pin
Name 2-wire
Name 4-wire
Description
RS485+
TX+
RS485
TX
Receive/transmit
Term
T-Term
N.A.
R-Term
N.A.
RX
Receive low
N.A.
RX+
Receive high
Angle
bracket
Screw
terminal
X3
Screw
terminal
X1
1
2
1
2
3
4
5
6
RS485
PWB
Backplane
IEC06000517 V1 EN
Figure 317:
RS485 connector
A second 2-pole screw connector is used for the connection of IO-ground. It can be
used in two combinations like:
724
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.15.3
Soft grounded: The IO is connected to the GND with an RC net parallel with a MOV
Technical data
Table 472:
Quantity
Range or value
Communication speed
240019200 bauds
External connectors
17.2.16
17.2.16.1
Introduction
The optical fast-ethernet module is used to connect an IED to the communication buses
(like the station bus) that use the IEC 61850-8-1 protocol (port A, B). The module has
one or two optical ports with ST connectors.
17.2.16.2
Functionality
The Optical Ethernet module (OEM) is used when communication systems according
to IEC6185081 have been implemented.
17.2.16.3
Design
The Optical Ethernet module (OEM) is a PMC card and mounted as a mezzanine card
on the ADM. The OEM is a 100base Fx module and available as a single channel or
double channel unit.
725
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
100Base-FX
Transmitter
EEPROM
ST fiber optic
connectors
Ethernet Controller
100Base-FX
Receiver
PCI - PCI Bridge
100Base-FX
Transmitter
ID chip
ST fiber optic
connectors
Ethernet Controller
100Base-FX
Receiver
EEPROM
IO - bus Connector
en04000472.vsd
IEC04000472 V1 EN
Figure 318:
ID chip
LED
Transmitter
IO bus
Receiver
Ethernet cont.
25MHz oscillator
LED
Transmitter
Ethernet cont.
25MHz oscillator
PCI bus
Receiver
PCI to PCI
bridge
en05000472.vsd
IEC05000472 V1 EN
Figure 319:
17.2.16.4
Technical data
Table 473:
Quantity
Rated value
Number of channels
1 or 2
Standard
Type of fiber
Wave length
1300 nm
Optical connector
Type ST
Communication speed
726
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.17
17.2.17.1
Introduction
The line data communication module (LDCM) is used for communication between the
IEDs situated at distances <68 miles or from the IED to optical to electrical converter
with G.703 interface located on a distances <1.9 miles away. The LDCM module sends
and rereceives data, to and from another LDCM module. The IEEE/ANSI standard
format is used.
The line data communication module is used for binary signal transfer. The module has
one optical port with ST connectors see figure 320.
Each module has one optical port, one for each remote end to which the IED
communicates.
Alternative cards for Short range (850 nm multi mode) are available.
Class 1 laser product. Take adequate measures to protect the eyes.
Never look into the laser beam.
17.2.17.2
Design
The LDCM is a PCMIP type II single width format module. The LDCM can be
mounted on:
the ADM
the NUM
727
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
ID
ST
16.000
MHz
32,768
MHz
IO-connector
ST
en07000087.vsd
IEC07000087 V1 EN
Figure 320:
The SR-LDCM layout. PCMIP type II single width format with two PCI
connectors and one I/O ST type connector
X1
2.5V
ADN
2841
MAX
3645
DS
3904
DS
3904
ID
FPGA
256 FBGA
PCI9054
TQ176
3
2
en06000393.vsd
IEC06000393 V1 EN
Figure 321:
17.2.17.3
Technical data
728
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Table 474:
Characteristic
Type of LDCM
Range or value
Short range (SR)
Type of fiber
Graded-index
multimode
62.5/125 m or
50/125 m
Singlemode 9/125
m
Singlemode 9/125 m
Wave length
850 nm
1310 nm
1550 nm
Optical budget
Graded-index multimode
62.5/125 mm,
13 dB (typical
distance about 2
mile *)
9 dB (typical
distance about 1
mile *)
22 dB (typical
distance 50 mile *)
Optical connector
Type ST
Type FC/PC
Type FC/PC
Protocol
C37.94
C37.94
implementation **)
Data transmission
Synchronous
Synchronous
Synchronous
2 Mb/s / 64 kbit/s
2 Mb/s / 64 kbit/s
2 Mb/s / 64 kbit/s
Clock source
Internal or
derived from
received signal
Internal or derived
from received signal
Graded-index multimode
50/125 mm
17.2.18
17.2.18.1
Introduction
This module includes a GPS receiver used for time synchronization. The GPS has one
SMA contact for connection to an antenna. It also includes an optical PPS STconnector output.
17.2.18.2
Design
The GTM is a PCMIP-format card and is placed only on one of the ADM slots. The
antenna input connector is shielded and directly attached to a grounded plate to
eliminate the risk of electromagnetic interference.
All communication between the GCM and the NUM is via the PCI-bus. PPS time data
is sent from the GCM to the rest of the time system to provide 1s accuracy at
729
Section 17
IED hardware
1MRK505208-UUS D
sampling level. An optical transmitter for PPS output is available for time
synchronization of another relay with an optical PPS input. The PPS output connector
is of ST-type for multimode fibre and could be used up to 1 km.
Controller
Selector
PCI
GPS- receiver
UART-core
PCI- core
FPGA
PCI
Antenna
connector
Receiver
memory
Stripline( 50 Ohms)
Wishbone bus
Registers
Optical
PPS
transmitter
TSU
IO
Transmitter
Driver
JTAG
connector
Configmemory
OSC
ID- chip
IEC09000980-1-en.vsd
IEC09000980 V1 EN
Figure 322:
17.2.18.3
Technical data
Table 475:
Function
Range or value
Accuracy
Receiver
1s relative UTC
<30 minutes
<15 minutes
<5 minutes
17.2.19
GPS antenna
17.2.19.1
Introduction
In order to receive GPS signals from the satellites orbiting the earth a GPS antenna
with applicable cable must be used.
730
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.2.19.2
Design
The antenna with a console for mounting on a horizontal or vertical flat surface or on
an antenna mast. See figure 323
2
3
xx04000155.vsd
IEC04000155 V2 EN
Figure 323:
where:
1
GPS antenna
TNC connector
Console, (2'6.7"x4'11')
Antenna cable
Use a 50 ohm coaxial cable with a male TNC connector in the antenna end and a male
SMA connector in the receiver end to connect the antenna to GTM. Choose cable type
and length so that the total attenuation is max. 26 dB at 1.6 GHz.
731
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Make sure that the antenna cable is not charged when connected to the
antenna or to the receiver. Short-circuit the end of the antenna cable
with some metal device, when first connected to the antenna. When the
antenna is connected to the cable, connect the cable to the receiver.
REx670 must be switched off when the antenna cable is connected.
17.2.19.3
Technical data
Table 476:
Function
Value
26 db @ 1.6 GHz
50 ohm
Lightning protection
Accuracy
+/-2s
17.2.20
17.2.20.1
Introduction
The IRIG-B time synchronizing module is used for accurate time synchronizing of the
IED from a station clock.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.
17.2.20.2
Design
The IRIG-B module have two inputs. One input is for the IRIG-B that can handle both
a pulse-width modulated signal (also called unmodulated) and an amplitude modulated
signal (also called sine wave modulated). The other is an optical input type ST for PPS
to synchronize the time between several protections.
732
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
STconnector
FPGA
PCI-con
32 MHz
OPTO_INPUT
PCI-bus
Registers
PCI-con
PCI-Controller
IRIGDecoder
ID-chip
Capture1
IRIG_INPUT
ZXING
Amplitude
modulator
Isolated
receiver
IO-con
Capture2
BNCconnector
4 mm barrier
Zero-cross
detector
MPPS
PPS
Isolated
DC/DC
5 to +- 12V
TSU
CMPPS
en06000303.vsd
IEC06000303 V1 EN
A1
Y2
C
C
ST
A1
DC//DC
Figure 324:
3
2
en06000304.vsd
IEC06000304 V1 EN
Figure 325:
IRIG-B PC-MIP board with top left ST connector for PPS 820 nm
multimode fibre optic signal input and lower left BNC connector for IRIGB signal input
733
Technical reference manual
Section 17
IED hardware
17.2.20.3
1MRK505208-UUS D
Technical data
Table 477:
IRIG-B
Quantity
Rated value
Electrical connector:
Electrical connector IRIG-B
BNC
Pulse-width modulated
5 Vpp
Amplitude modulated
low level
high level
1-3 Vpp
3 x low level, max 9 Vpp
Supported formats
Accuracy
Input impedance
100 k ohm
Optical connector:
Optical connector PPS and IRIG-B
Type ST
Type of fibre
Supported formats
Accuracy
+/- 2s
734
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.3
Dimensions
17.3.1
E
D
xx08000162.vsd
IEC08000162 V1 EN
Figure 326:
Case size
Tolerance
Flush mounting
Cut-out dimensions (inches)
A
+/0.04
B
+/0.04
6U, 1/2 x 19
8.27
10.01
0.160.39
0.49
6U, 3/4 x 19
12.69
10.01
0.160.39
0.49
6U, 1/1 x 19
17.11
10.01
0.160.39
0.49
E = 188.6 mm without rear protection cover, 229.6 mm with rear protection cover
735
Technical reference manual
Section 17
IED hardware
17.3.2
1MRK505208-UUS D
xx06000182.vsd
IEC06000182 V1 EN
Figure 327:
C
xx05000505.vsd
IEC05000505 V1 EN
Figure 328:
736
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Case size
(inches)
Tolerance
A
0.04
B
0.04
C
0.04
D
0.04
E
0.04
F
0.04
G
0.04
6U, 1/2 x 19
8.42
10.21
9.46
7.50
1.35
0.52
0.25 diam
6U, 3/4 x 19
12.85
10.21
13.89
7.50
1.35
0.52
0.25 diam
6U, 1/1 x 19
17.27
10.21
18.31
7.50
1.35
0.52
0.25 diam
17.3.3
A
B
E
en04000471.vsd
IEC04000471 V1 EN
Figure 329:
Wall mounting
6U, 1/2 x 19
10.50
10.52
10.74
15.36
9.57
6U, 3/4 x 19
15.92
14.94
10.74
15.36
9.57
6U, 1/1 x 19
20.31
19.33
10.74
15.36
9.57
737
Technical reference manual
Section 17
IED hardware
17.3.4
1MRK505208-UUS D
57 [2.24]
89 [3.5]
482.6 [19]
Dimension
mm [inches]
xx06000233.vsd
IEC06000233 V1 EN
Figure 330:
17.4
Mounting alternatives
17.4.1
Flush mounting
17.4.1.1
Overview
The flush mounting kit are utilized for case sizes:
1/2 x 19
3/4 x 19
1/1 x 19
1/4 x 19 (RHGS6 6U)
Only a single case can be mounted in each cut-out on the cubicle panel, for class IP54
protection.
Flush mounting cannot be used for side-by-side mounted IEDs when
IP54 class must be fulfilled. Only IP20 class can be obtained when
mounting two cases side-by-side in one (1) cut-out.
738
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.4.1.2
5
2
6
3
xx08000161.vsd
IEC08000161 V1 EN
Figure 331:
PosNo Description
Quantity Type
Sealing strip, used to obtain IP54 class. The sealing strip is factory
mounted between the case and front plate.
Fastener
Groove
2.9x9.5 mm
Panel
739
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.4.2
17.4.2.1
1b
xx08000160.vsd
IEC08000160 V1 EN
Figure 332:
Pos
Quantity
Type
1a, 1b
Screw
M4x6
740
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.4.3
Wall mounting
17.4.3.1
Overview
All case sizes, 1/2 x 19, 3/4 x 19,1/1 x 19, can be wall mounted. It is also possible
to mount the IED on a panel or in a cubicle.
When mounting the side plates, be sure to use screws that follows the
recommended dimensions. Using screws with other dimensions than
the original may damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for communication modules
with fiber connection; Serial SPA/IEC 60870-5-103, DNP3 and LON
communication module (SLM),Optical Ethernet module (OEM) and
Line data communication module (LDCM).
17.4.3.2
2
1
5
6
xx04000453.vs d
DOCUMENT127716-IMG2265 V1 EN
Figure 333:
741
Technical reference manual
Section 17
IED hardware
17.4.3.3
1MRK505208-UUS D
PosNo
Description
Quantity
Type
Bushing
Screw
M4x10
Screw
M6x12 or corresponding
Mounting bar
Screw
M5x8
Side plate
3.2"
(80 mm)
ANSI_en06000135.vsd
ANSI06000135 V1 EN
Figure 334:
PosNo
Description
Type
Screw
M4x10
Screw
M5x8
742
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.4.4
17.4.4.1
Overview
IED case sizes, 1/2 x 19 or 3/4 x 19 and RHGS cases, can be mounted side-by-side
up to a maximum size of 19. For side-by-side rack mounting, the side-by-side
mounting kit together with the 19 rack panel mounting kit must be used. The
mounting kit has to be ordered separately.
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws with
other dimensions than the original may damage the PCBs inside the IED.
17.4.4.2
xx04000456.vsd
IEC04000456 V1 EN
Figure 335:
PosNo
Description
Quantity
Type
Mounting plate
2, 3
Screw
16
M4x6
Mounting angle
743
Technical reference manual
Section 17
IED hardware
17.4.4.3
1MRK505208-UUS D
xx06000180.vsd
IEC06000180 V1 EN
Figure 336:
IED in the 670 series (1/2 x 19) mounted with a RHGS6 case
containing a test switch module equipped with only a test switch and a
RX2 terminal base
17.4.5
17.4.5.1
Overview
It is not recommended to flush mount side by side mounted cases if IP54 is required. If
your application demands side-by-side flush mounting, the side-by-side mounting
details kit and the 19 panel rack mounting kit must be used. The mounting kit has to
be ordered separately. The maximum size of the panel cut out is 19.
With side-by-side flush mounting installation, only IP class 20 is
obtained. To reach IP class 54, it is recommended to mount the IEDs
separately. For cut out dimensions of separately mounted IEDs, see
section "Flush mounting".
744
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
When mounting the plates and the angles on the IED, be sure to use
screws that follows the recommended dimensions. Using screws with
other dimensions than the original may damage the PCBs inside the IED.
17.4.5.2
3
4
xx06000181.vsd
IEC06000181 V1 EN
Figure 337:
PosNo
Description
Quantity
Type
Mounting plate
2, 3
Screw
16
M4x6
Mounting angle
745
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.5
Technical data
17.5.1
Enclosure
Table 478:
Case
Material
Steel sheet
Front plate
Surface treatment
Finish
Table 479:
Weight
Case size
17.5.2
Weight
6U, 1/2 x 19
22 lb
6U, 3/4 x 19
33 lb
6U, 1/1 x 19
40 lb
Connection system
Table 480:
Connector type
250 V AC, 20 A
4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
250 V AC, 20 A
4 mm2 (AWG12)
Table 481:
Connector type
Rated voltage
250 V AC
300 V AC
3 mm2 (AWG14)
746
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
17.5.3
Influencing factors
Table 482:
Parameter
Reference value
Nominal range
Influence
Ambient temperature,
operate value
+20 C
-10 C to +55 C
0.02% /C
Relative humidity
Operative range
10%-90%
0%-95%
10%-90%
Storage temperature
-40 C to +70 C
Table 483:
Dependence on
Reference value
max. 2%
Full wave rectified
15% of EL
0.01% /%
20% of EL
0.01% /%
24-60 V DC 20%
90-250 V DC 20%
Interruption
interval
050 ms
Table 484:
No restart
0 s
Correct behaviour
at power down
Restart time
<300 s
Dependence on
Influence
Frequency dependence,
operate value
fn 2.5 Hz for 50 Hz
fn 3.0 Hz for 60 Hz
1.0% / Hz
fn 2.5 Hz for 50 Hz
fn 3.0 Hz for60 Hz
2.0% / Hz
Harmonic frequency
dependence (20% content)
1.0%
Harmonic frequency
dependence for differential
protection (10% content)
6.0%
747
Technical reference manual
Section 17
IED hardware
17.5.4
1MRK505208-UUS D
Electromagnetic compatibility
Test
Reference standards
2.5 kV
IEC 60255-22-1
2.5 kV
2-4 kV
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.1
4 kV
IEC 60255-22-5
150-300 V
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
100 A/m
IEC 60255-22-3
35 V/m
26-1000 MHz
IEEE/ANSI C37.90.2
10 V, 0.15-80 MHz
IEC 60255-22-6
Radiated emission
30-1000 MHz
IEC 60255-25
Conducted emission
0.15-30 MHz
IEC 60255-25
Table 486:
1.4-2.7 GHz
Insulation
Test
Dielectric test
Insulation resistance
Reference standard
ANSI C37.90
748
Technical reference manual
Section 17
IED hardware
1MRK505208-UUS D
Table 487:
Environmental tests
Test
Reference standard
Cold test
IEC 60068-2-1
Storage test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-78
IEC 60068-2-30
Table 488:
CE compliance
Test
According to
Immunity
EN 50263
Emissivity
EN 50263
EN 50178
Table 489:
Mechanical tests
Test
Reference standards
Class II
IEC 60255-21-1
Class I
IEC 60255-21-1
Class II
IEC 60255-21-2
Class I
IEC 60255-21-2
Bump test
Class I
IEC 60255-21-2
Seismic test
Class II
IEC 60255-21-3
749
Technical reference manual
750
Section 18
Labels
1MRK505208-UUS D
Section 18
Labels
18.1
Labels on IED
Front view of IED
1
2
3
4
5
6
6
7
xx06000574.ep
IEC06000574 V1 EN
751
Technical reference manual
Section 18
Labels
1MRK505208-UUS D
Manufacturer
Transformer designations
IEC06000577-CUSTOMER-SPECIFIC V1 EN
IEC06000576-POS-NO V1 EN
752
Technical reference manual
Section 18
Labels
1MRK505208-UUS D
1
2
3
4
en06000573.ep
IEC06000573 V1 EN
Warning label
Caution label
IEC06000575 V1 EN
Warning label
753
Technical reference manual
754
Section 19
Connection diagrams
1MRK505208-UUS D
Section 19
Connection diagrams
This chapter includes diagrams of the IED with all slot, terminal block and optical
connector designations. It is a necessary guide when making electrical and optical
connections to the IED.
755
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-1-670-1.2-PG-ANSI V1 EN
756
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-2-670-1.2-PG-ANSI V1 EN
757
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-3-670-1.2-PG-ANSI V1 EN
758
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-4-670-1.2-PG-ANSI V1 EN
759
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-5-670-1.2-ANSI V1 EN
760
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-6-670-1.2-ANSI V1 EN
761
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-7-670-1.2-ANSI V1 EN
762
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-8-670-1.2-ANSI V1 EN
763
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-9-670-1.2-ANSI V1 EN
764
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-10-670-1.2-ANSI V1 EN
765
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-11-670-1.2-ANSI V1 EN
766
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-12-670-1.2-ANSI V1 EN
767
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-13-670-1.2-ANSI V1 EN
768
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-14-670-1.2-ANSI V1 EN
769
Technical reference manual
Section 19
Connection diagrams
1MRK505208-UUS D
1MRK002802-AB-15-670-1.2-ANSI V1 EN
770
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Section 20
20.1
Application
In order to assure time selectivity between different overcurrent protections at different
points in the network different time delays for the different protections are normally
used. The simplest way to do this is to use definite time-lag. In more sophisticated
applications current dependent time characteristics are used. Both alternatives are
shown in a simple application with three overcurrent protections operating in series.
IPickup
IPickup
IPickup
xx05000129_ansi.vsd
ANSI05000129 V1 EN
Figure 338:
771
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Stage 3
Time
Stage 2
Stage 1
Stage 2
Stage 1
Stage 1
Fault point
position
en05000130.vsd
IEC05000130 V1 EN
Figure 339:
Time
Fault point
position
en05000131.vsd
IEC05000131 V1 EN
Figure 340:
The inverse time characteristic makes it possible to minimize the fault clearance time
and still assure the selectivity between protections.
To assure selectivity between protections there must be a time margin between the
operation time of the protections. This required time margin is dependent of following
factors, in a simple case with two protections in series:
772
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A1
B1
51
51
Feeder
Time axis
t=0
t=t1
t=t2
t=t3
en05000132_ansi.vsd
ANSI05000132 V1 EN
Figure 341:
where:
t=0
t=t1
is Protection B1 trips
t=t2
is Breaker at B1 opens
t=t3
is Protection A1 resets
In the case protection B1 shall operate without any intentional delay (instantaneous).
When the fault occurs the protections pickup to detect the fault current. After the time
t1 the protection B1 send a trip signal to the circuit breaker. The protection A1 starts its
delay timer at the same time, with some deviation in time due to differences between
the two protections. There is a possibility that A1 will start before the trip is sent to the
B1 circuit breaker. At the time t2 the circuit breaker B1 has opened its primary contacts
and thus the fault current is interrupted. The breaker time (t2 - t1) can differ between
different faults. The maximum opening time can be given from manuals and test
protocols. Still at t2 the timer of protection A1 is active. At time t3 the protection A1 is
reset, that is the timer is stopped.
In most applications it is required that the times shall reset as fast as possible when the
current fed to the protection drops below the set current level, the reset time shall be
minimized. In some applications it is however beneficial to have some type of delayed
reset time of the overcurrent function. This can be the case in the following applications:
773
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
If there is a risk of intermittent faults. If the current IED, close to the faults, picks
up and resets there is a risk of unselective trip from other protections in the system.
Delayed resetting could give accelerated fault clearance in case of automatic
reclosing to a permanent fault.
Overcurrent protection functions are sometimes used as release criterion for other
protection functions. It can often be valuable to have a reset delay to assure the
release function.
20.2
Principle of operation
20.2.1
Mode of operation
The function can operate in a definite time-lag mode or in a current definite inverse
time mode. For the inverse time characteristic both ANSI and IEC based standard
curves are available. Also programmable curve types are supported via the component
inputs: p, A, B, C pr, tr, and cr.
Different characteristics for reset delay can also be chosen.
If current in any phase exceeds the set pickup current value (here internal signal
pickupValue), a timer, according to the selected operating mode, is started. The
component always uses the maximum of the three phase current values as the current
level used in timing calculations.
In case of definite time-lag mode the timer will run constantly until the time is reached
or until the current drops below the reset value (pickup value minus the hysteresis) and
the reset time has elapsed.
For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are chosen.
The general expression for inverse time curves is according to equation 84.
774
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A
t [s ] =
P
Pickupn
-C
+ B td
(Equation 84)
EQUATION1640 V1 EN
where:
p, A, B, C
Pickupn
td
For inverse time characteristics a time will be initiated when the current reaches the set
pickup level. From the general expression of the characteristic the following can be seen:
( top - B td ) Pickupn
-C
= A td
(Equation 85)
EQUATION1642 V1 EN
where:
top
The time elapsed to the moment of trip is reached when the integral fulfils according to
equation 86, in addition to the constant time delay:
t
Pickupn
0
- C dt A td
EQUATION1643 V1 EN
(Equation 86)
For the numerical protection the sum below must fulfil the equation for trip.
775
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
i ( j ) P
- C A td
Pickupn
j =1
Dt
(Equation 87)
EQUATION1644 V1 EN
where:
j=1
i
Pickupn
>1
EQUATION1646 V1 EN
Dt
is the number of the execution of the algorithm when the trip time
equation is fulfilled, that is, when a trip is given and
i (j)
For inverse time operation, the inverse time characteristic is selectable. Both the IEC
and ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure 342.
776
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Operate
time
tMin
Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN
Figure 342:
In order to fully comply with IEC curves definition setting parameter tMin shall be set
to the value which is equal to the operating time of the selected IEC inverse time curve
for measured current of twenty times the set current pickup value. Note that the
operating time value is dependent on the selected setting value for time multiplier k.
In addition to the ANSI and IEC standardized characteristics, there are also two
additional inverse curves available; the RI curve and the RD curve.
The RI inverse time curve emulates the characteristic of the electromechanical ASEA
relay RI. The curve is described by equation 89:
td
t [s ] =
0.339 - 0.235 Pickupn
i
(Equation 89)
EQUATION1647 V1 EN
where:
Pickupn is the set pickup current for step n
td
777
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
The RD inverse curve gives a logarithmic delay, as used in the Combiflex protection
RXIDG. The curve enables a high degree of selectivity required for sensitive residual
ground-fault current protection, with ability to detect high-resistive ground faults. The
curve is described by equation 90:
td Pickupn
[ ]
t s = 5.8 - 1.35 ln
(Equation 90)
EQUATION1648 V1 EN
where:
Pickupn is the set pickup current for step n,
td
If the curve type programmable is chosen, the user can make a tailor made inverse time
curve according to the general equation 91.
A
t [s ] =
P
Pickupn
-C
+ B td
EQUATION1640 V1 EN
(Equation 91)
Also the reset time of the delayed function can be controlled. There is the possibility to
choose between three different reset time-lags.
Instantaneous Reset
IEC Reset
ANSI Reset.
If instantaneous reset is chosen the timer will be reset directly when the current drops
below the set pickup current level minus the hysteresis.
If IEC reset is chosen the timer will be reset after a set constant time when the current
drops below the set pickup current level minus the hysteresis.
If ANSI reset time is chosen the reset time will be dependent of the current after fault
clearance (when the current drops below the pickup current level minus the hysteresis).
The timer will reset according to equation 92.
778
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
tr
td
t [s] =
i 2
-1
pickupn
(Equation 92)
ANSIEQUATION1197 V1 EN
where:
The set value tr is the reset time in case of zero current after fault clearance.
tr
td
t [s] =
i pr
- cr
pickupn
ANSIEQUATION1198 V1 EN
(Equation 93)
For RI and RD inverse time delay characteristics the possible delay time settings are
instantaneous and IEC constant time reset.
When inverse time overcurrent characteristic is selected, the operate
time of the stage will be the sum of the inverse time delay and the set
779
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
definite time delay. Thus, if only the inverse time delay is required, it is
of utmost importance to set the definite time delay for that stage to zero.
20.3
Inverse characteristics
Table 490:
Function
Range or value
Accuracy
ANSI/IEEE C37.112, 5%
+ 40 ms
Operating characteristic:
t =
A
P
( I - 1)
+ B td
EQUATION1651 V1 EN
Reset characteristic:
t =
(I
tr
2
td
-1
EQUATION1652 V1 EN
I = Imeasured/Iset
780
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Table 491:
Function
Range or value
Operating characteristic:
Accuracy
(0.000-60.000) s
A=0.14, P=0.02
A=13.5, P=1.0
IEC 60255-151, 5% + 40
ms
IEC Inverse
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
Programmable characteristic
Operate characteristic:
t =
A
P
td
( I - 1)
EQUATION1653 V1 EN
I = Imeasured/Iset
t =
A
P
(I - C )
+ B td
EQUATION1654 V1 EN
Reset characteristic:
t =
(I
TR
PR
- CR
td
EQUATION1655 V1 EN
I = Imeasured/Iset
781
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Table 492:
Function
Range or value
t =
0.339 -
0.236
Accuracy
IEC 60255-151, 5% + 40
ms
td
EQUATION1656 V1 EN
I = Imeasured/Iset
RD type logarithmic inverse characteristic
t = 5.8 - 1.35 In
td
I
EQUATION1657 V1 EN
I = Imeasured/Iset
782
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Table 493:
Function
Range or value
Type A curve:
t =
td = (0.05-1.10) in steps
of 0.01
Accuracy
5% +40 ms
td
V - VPickup
VPickup
EQUATION1661 V1 EN
V = Vmeasured
Type B curve:
t =
td = (0.05-1.10) in steps
of 0.01
td 480
V - VPickup
- 0.5
32
VPickup
2.0
- 0.035
EQUATION1662 V1 EN
Type C curve:
t =
td = (0.05-1.10) in steps
of 0.01
td 480
V - VPickup
- 0.5
32
VPickup
3.0
- 0.035
EQUATION1663 V1 EN
Programmable curve:
t =
td A
V - VPickup
B
VPickup
EQUATION1664 V1 EN
-C
+D
td = (0.05-1.10) in steps
of 0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001
783
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Table 494:
Function
Range or value
Type A curve:
t =
td = (0.05-1.10) in steps
of 0.01
Accuracy
5% +40 ms
td
VPickup - V
VPickup
EQUATION1658 V1 EN
V = Vmeasured
Type B curve:
t =
td = (0.05-1.10) in steps
of 0.01
td 480
VPickup - V
32
VPickup
- 0.5
2.0
+ 0.055
EQUATION1659 V1 EN
V = Vmeasured
Programmable curve:
t =
td A
VPickup - V
B
VPickup
EQUATION1660 V1 EN
V = Vmeasured
+D
P
-C
td = (0.05-1.10) in steps
of 0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001
784
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
Table 495:
Function
Range or value
Type A curve:
t =
td = (0.05-1.10) in steps
of 0.01
Accuracy
5% +40 ms
td
V - VPickup
VPickup
EQUATION1661 V1 EN
V = Vmeasured
Type B curve:
t =
td = (0.05-1.10) in steps
of 0.01
td 480
V - VPickup
- 0.5
32
VPickup
2.0
- 0.035
EQUATION1662 V1 EN
Type C curve:
t =
td = (0.05-1.10) in steps
of 0.01
td 480
V - VPickup
- 0.5
32
VPickup
3.0
- 0.035
EQUATION1663 V1 EN
Programmable curve:
t =
td A
V - VPickup
B
VPickup
EQUATION1664 V1 EN
-C
+D
td = (0.05-1.10) in steps
of 0.01
A = (0.005-200.000) in
steps of 0.001
B = (0.50-100.00) in
steps of 0.01
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001
785
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070750 V2 EN
Figure 343:
786
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070751 V2 EN
Figure 344:
787
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070752 V2 EN
Figure 345:
788
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070753 V2 EN
Figure 346:
789
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070817 V2 EN
Figure 347:
790
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070818 V2 EN
Figure 348:
791
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070819 V2 EN
Figure 349:
792
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070820 V2 EN
Figure 350:
793
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070821 V2 EN
Figure 351:
794
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070822 V2 EN
Figure 352:
795
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070823 V2 EN
Figure 353:
796
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070824 V2 EN
Figure 354:
797
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070825 V2 EN
Figure 355:
798
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070826 V2 EN
Figure 356:
799
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
A070827 V2 EN
Figure 357:
800
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN
Figure 358:
801
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN
Figure 359:
802
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN
Figure 360:
803
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN
Figure 361:
804
Technical reference manual
Section 20
Inverse time characteristics
1MRK505208-UUS D
GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN
Figure 362:
805
Technical reference manual
806
Section 21
Glossary
1MRK505208-UUS D
Section 21
Glossary
Alternating current
ACT
A/D converter
Analog-to-digital converter
ADBS
ADM
AI
Analog input
ANSI
AR
Autoreclosing
AngNegRes
Setting parameter/ZD/
ArgDirAngDir
Setting parameter/ZD/
ASCT
ASD
AWG
BBP
Busbar protection
BFP
BI
Binary input
BIM
BOM
BOS
BR
BS
British Standards
BSR
BST
C37.94
Section 21
Glossary
1MRK505208-UUS D
CAN
CB
Circuit breaker
CBM
CCITT
CCM
CCVT
Class C
CMPPS
CMT
CO cycle
Close-open cycle
Codirectional
COMTRADE
Contra-directional
CPU
CR
Carrier receive
CRC
CROB
CS
Carrier send
CT
Current transformer
CVT or CCVT
DAR
Delayed autoreclosing
DARPA
DBDL
DBLL
DC
Direct current
808
Technical reference manual
Section 21
Glossary
1MRK505208-UUS D
DFC
DFT
DHCP
DIP-switch
DI
Digital input
DLLB
DNP
DR
Disturbance recorder
DRAM
DRH
DSP
DTT
EHV network
EIA
EMC
Electromagnetic compatibility
EMF
(Electromotive force)
EMI
Electromagnetic interference
EnFP
EPA
ESD
Electrostatic discharge
FCB
FOX 20
FOX 512/515
Access multiplexer
FOX 6Plus
G.703
GCM
GDE
GI
Section 21
Glossary
1MRK505208-UUS D
GIS
Gas-insulated switchgear
GOOSE
GPS
GSAL
GTM
HDLC protocol
Human-machine interface
HSAR
HV
High-voltage
HVDC
IDBS
IEC
IEC 60044-6
IEC 60870-5-103
IEC 61850
IEC 6185081
IEEE
IEEE 802.12
IEEE P1386.1
IEEE 1686
IED
I-GIS
IOM
Instance
810
Technical reference manual
Section 21
Glossary
1MRK505208-UUS D
IP 20
IP 40
Ingression protection, according to IEC standard, level IP40Protected against solid foreign objects of 1mm diameter and
greater.
IP 54
IRF
IRIG-B:
ITU
LAN
LIB 520
LCD
LDCM
LDD
LED
Light-emitting diode
LNT
LON
MCB
MCM
MIM
Milli-ampere module
MPM
Section 21
Glossary
1MRK505208-UUS D
MVB
NCC
NUM
Numerical module
OCO cycle
Open-close-open cycle
OCP
Overcurrent protection
OEM
OLTC
OV
Over-voltage
Overreach
PCI
PCM
PCM600
PC-MIP
PMC
POR
Permissive overreach
POTT
Process bus
PSM
PST
PT ratio
PUTT
RASC
RCA
RFPP
RISC
RMS value
812
Technical reference manual
Section 21
Glossary
1MRK505208-UUS D
RS422
RS485
RTC
Real-time clock
RTU
SA
Substation Automation
SBO
Select-before-operate
SC
SCS
SCADA
SCT
SDU
SLM
SMA connector
SMT
SMS
SNTP
SPA
SRY
ST
Starpoint
SVC
TC
Trip coil
TCS
TCP
813
Technical reference manual
Section 21
Glossary
1MRK505208-UUS D
TCP/IP
TEF
TNC connector
Underreach
UTC
UV
Undervoltage
WEI
VT
Voltage transformer
X.21
814
Technical reference manual
Section 21
Glossary
1MRK505208-UUS D
3IO
3VO
815
Technical reference manual
816
817
ABB Inc.
1021 Main Campus Drive
Raleigh, NC 27606, USA
Phone
Toll Free: 1-800-HELP-365,
menu option #8
ABB Inc.
3450 Harvester Road
Burlington, ON L7N 3W5, Canada
Phone
Toll Free: 1-800-HELP-365,
menu option #8
Contact us