Beruflich Dokumente
Kultur Dokumente
Tap
Changers
By Michael Krger, OMICRON Electronics Austria
138
PT&D
February/March 2003
www.powertrans.com.au
One important test is to measure the winding resistances including the resistances of all
connections and contacts. Another important test is the dynamic resistance measurement
to enable an analysis of the transient switching operation of the diverter switch.
If the switching process is interrupted (even if it is only a shorttime interruption), the ripple (= Imax - Imin) and the slope steepness
of the current change di/dt increase. Both quantities are measured
and displayed by the CPC. The values for all taps and particularly the
values for the three phases are compared. Major deviations from the
mean values indicate faulty switching. The measuring circuit used in
the CPC 100 is a glitch detector which is able to detect even shorttime failures as they occur during contact bouncing, for example.
The measuring current chosen should not be too high for this
measurement (< 1 A) since otherwise high magnetic energy
(= 1/2 LI2) is stored in the winding inductance. During an
interruption of the test current the magnetic energy is then
transformed into electric energy. In such cases an electric arc occurs
on the short-time opening contact. However, the interruption is
possibly too short for the electric arc to extinguish. Then the fault is
very difficult to detect from the outside.
TRANSFORMER RATIO MEASUREMENT
CPC 100 also enables the measurement of the transformer ratio
which can be recorded very simply per tap similar to the resistance
measurement. During the transformer ratio measurement the
amplitude and phase angle of the no-load current are also recorded.
This measurement enables a statement about the changes inside the
iron core of the particular leg. By comparing the excitation currents
of the individual phases, core burning and partial short-circuiting of
the core (e.g. caused by iron parts) which can also be a possible
reason for overheating, can be detected. Of course interturn short
circuits can also be detected this way.
LEAKAGE INDUCTANCE MEASUREMENT
The leakage inductance can also be measured. High fault currents
can cause a deformation of the windings possibly resulting in an
expansion of the leakage channel. A strong deformation of the coil
can increase the leakage inductance. Since CPC 100 also enables
impedance measurements using other frequencies than 50 Hz, this
measurement can also be carried out with relatively low currents in
the field. If required, the value for 50 Hz can be obtained by
interpolating the measurement results for adjacent frequencies. This
way the measurement result is not influenced by undesired
couplings from adjacent bus bars.
SUMMARY
With advancing age of transformers a regular check of the
operating condition becomes more and more important. The gas in
oil analysis is a proven and meaningful method of analysis. If
increased proportions of hydrocarbon gases are found in the oil, the
fault has to be localised as soon as possible. This way important
maintenance can be performed in time in order to avoid a sudden
total failure. The fault localisation can often be successfully
performed using relatively simple methods, such as resistance
measurements. Using the OMICRON CPC 100 the most important
transformer measurements can be performed quickly and efficiently.
Automatic test procedures enable simple operation and the test
report is created automatically.
February/March 2003 PT&D
139