TECHNICAL MANUAL

UCS CASSETTE

UCS MODEL

CONDIZIONAMENTO RISCALDAMENTO
A I R C O N D I T I O N I N G A N D H E AT I N G

INDEX

1.

GENERAL INFORMATION
1.1
1.2
1.3
1.4

2.
3.
4.

6
7

10
10
10
10
10
11
11
11

Description UCS

COANDA EFFECT
COMPONENTS
Structure
Heat exchangers
Fan deck
Electrical components and controls
Condensate pump
Air filter
Air outlet plenum
Air intake grill

ELECTRICAL ACCESSORIES
QEC10
QEC20
QEC30
Electric heater KREL
Thermostats and electronic regulators
IR Infrared control
OMNIBUS Regulation
WS Water sensor

12
12
12
12
12
13
14
14

HYDRAULIC ACCESSORIES
DTH3B2 or DTH2B2
DTJ3BM or DTJ2BM
DT Shut-off valve (ball valve)

15
15
16

TECHNICAL DATA
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8

8.

5
5
5
5

6.1
6.2
6.3

7.

UCS CASSETTE UNIT

5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8

pag.

2.1

4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

5.

Applications
Operation
Performances
Selection software

Nominal air volumes


Air volume of the air supply collar
into an adjacent room
Cooling capacities, 2 pipe system
Heating capacities, 2 pipe system
Cooling capacities, 4 pipe system
Heating capacities, 4 pipe system
Electrical data
Working operation limits

18
18
19
20
21
22
23
23

NOISE LEVELS
8.1
8.2

Sound power
Sound pressure in a closed environment

24
24

25

ENCLOSURE 1

ELECTRICAL CONNECTIONS

1. GENERAL INFORMATION
1.1 Applications
The EURAPO UCS Cassette units are designed for installation
on a false ceiling, suitable for heating and cooling applications.

For each model, thermal performances in heating and cooling


depend on the number of rows of the coil installed, which gives
the opportunity to make the air treatment suit every condition
required.
In cooling function, under the same operating conditions, the
more rows the heat exchanger has, the more it will dehumidify.

1.2 Operation
The effectiveness of these cassette units is due to the large surface area of the finned heat exchanger (coil) where the air
drawn from the room by the fan passes through.
The ambient air drawn through the central air intake grill is
blown into the circular heat exchanger, composed by copper
pipes and aluminium fins, and then it comes out from the 4
sides of the cassette unit. Thanks to the special combination of
air intake/air outlet grilles it is possible to obtain the pleasant
COANDA Effect.
In Heating operation, the hot water circulating in the finned coil
supplies heat to the air passing through the heat exchanger.
In Cooling operation, the chilled water circulating in the finned
coil removes heat from the air passing through the heat
exchanger. The air is also dehumidified and the condensed
water vapour collects itself on the condensate tray beneath the
heat exchanger. It is then evacuated by a condensate pump,
factory fitted and wired, to which proper water discharge pipes
must be connected.

1.4 Selection software


To facilitate choosing the correct size of a cassette unit for any
operating condition (including those differing from the standard ones), EURAPO offers a dedicated computer program,
either available on CD-ROM or it can be downloaded from the
EURAPO official web site, on request.

Installation and Operation instructions concerning the software for selection are given
on its Help on line.

1.3 Performances
The performance of a cassette unit can vary greatly with changes in the temperature and in the amount of water circulating
through the coil, as well as with changes in the temperature
and in the amount of air circulating through the coil.
The air volume is determined by selecting the proper fan speed
(MIN-MED-MAX), while the water flow rate is determined by the
specifications of the system and of the pump. Thermal performances of the unit can be optimised by controlling the inlet
flow rate of the water with proper regulating valves (ON/OFF or
modulating), which can be supplied as accessories.
The use of regulating valves is always recommended in
cooling operation.

2. UCS CASSETTE UNIT

LEGEND
1

Air suction grill

Filter

Air supply grilles

Air intake plenum/condensate tray

Heat exchanger

Fan wheel fixing screw

Fan wheel washer

Square washer

Fan wheel

10

Motor

11

Air supply collar

12

Fixing support

13

Capacitor

14

Terminal board

15

Autotransformer

16

Fixing screws for air supply grilles

17

Fixing screws for air intake plenum/cond. tray

18

Collar for ext. air intake

19

Non return valve pipe

20

Flow switch for cond. pump

21

Motor for cond. pump

22

Support for cond. pump

23

Condensing water discharge pipe

2.1 Description UCS


Horizontal unit with air outlet on 4 sides and central air intake,
suitable for installation on the false ceiling.
General features:
central air intake grill in heat resistant ABS, white colour;
4 sides air outlet plenum with manual flaps in order to adjust
the air flow;
unit equipped with condensate tray and condensate pump;

2 pipe systems: 2 or 3 row coils available; in all units an


electric heater (max. 1,5 kW) can be also installed;
4 pipe systems: the additional 1 row coil can be added to
units with a 2 or 3 row coil;
prearranged hole for fresh air intake (standard), diam.
100 mm;
prearranged holes for air supply into adjacent rooms
(standard), diam. 150 mm.

TWO PIPE SYSTEM


1 Water Inlet

3/4 F

2 Water Outlet

3/4 F

FOUR PIPE SYSTEM


1 Inlet cooling water

3/4 F

2 Outlet cooling water

3/4 F

3 Inlet heating water

1/2 F

4 Outlet heating water

1/2 F

3. COANDA EFFECT
The particular combination of the air intake and outlet grilles
permits to obtain a pleasant distribution of the air flow and
creates a good comfort in the room where the EURAPO UCS
cassette unit is installed.
This condition is granted by the phenomenon called COANDA
Effect: the air is blown towards the ceiling and not directly
downwards, it adheres to the ceiling (because of the depres-

sion created on the ceilings surface) and it attracts the air


coming from the room, by mixing with it.
The air throw is longer and the air falling velocity decreases, by
falling down as rain, with a milder temperature.
The COANDA effect guarantees an uniform air distribution and
it avoids a direct air flow against the people in the room.

4. COMPONENTS
4.1 Structure

4.3 Fan deck

The structure is made of 12/10 mm thick galvanised steel,


completely insulated inside with closed cell thermal insulation
material, 10 mm thick.
On three the of the four sides there is a prearranged hole having
diam. 150 mm for the connection to an air supply duct.
Furthermore there is a prearranged hole having diam. 100 mm
for the connection to an external air intake.
The relevant collars for an easy connection to the air duct are
always supplied as standard.

The fan deck, installed in central position, is composed by a


centrifugal fan and plastic impeller.
The electric motor is single phase with permanently connected
capacitor and thermal protection of the windings.
It is provided with six speeds (by using a transformer), three of
them are factory wired as standard, giving the nominal air
volumes.

The air plenum/condensate tray group is realised in heat resistant ABS material. The condensate tray has a water drainage
hole, which is normally close by a water-tight rubber cap.
The air plenum has special slots on the sides in order to permit
access to the external air: the fresh air coming through the slots
will perfectly mix with the internal air and pass through the heat
exchanger before blowing into the room.

4.4 Electrical components and controls


The electric panel (QEC00) consists of a galvanized metal box
which contains the terminal board for the electrical connections, the earth protection terminal, the autotransformer and
the capacitor.
The electric panel is located on the side of the units, at the
same side of the water connections.

Additionally there are four fixing supports which are part of the
main structure, that are supplied as standard in a separate kit.
The fixing supports can be installed on the proper holes on two
sides of the cassette unit, either on the upper side or on the
lower side.

Every unit is provided with an electric wiring diagram, always


showing all the controls and electric accessories connected to
the unit. The wiring diagram must be strictly respected in order
to obtain the requested working conditions of the unit.

4.2 Heat exchangers

4.5 Condensate pump

The finned heat exchangers are made of copper pipes and surface treated aluminium fins, bent for 360. The surface treatment on the fins permits to have a better condensing water
discharge from the fins themselves and a perfect air passage
through the heat exchanger, with reduced pressure drops and a
high dehumidification and efficiency of the coil.

The UCS EURAPO Cassette units are supplied with a built-in


condensate pump having a no-return valve on the outlet.
The pump has a water discharge head of 850 mm from the bottom side of the cassette unit. The pump is activated by a floating switch and a second switch is used for closing the cooling
valve in case of too high water level in the condensate tray, due
to some problems in the water evacuation system.

The hexagonal brass water connections have diameter G


female on the cooling coil and diameter G female on the
heating coil (4 pipe system). A particular internal fixing system
of the coils header will limit the problems of torsion and damages on the copper pipes.
Operating pressure: 8 bar, testing pressure: 30 bar;
Min/max water temperature: 5/85 C.
A drain valve is located beneath the coils headers in order to
completely discharge the water from the coil, when the unit
does not work for a long period of time.
The air bleed is done by loosening slightly the water inlet union
and supplying the water from the outlet connection.

10

Technical features:
max. water flow: 30 l/h
max. water discharge: 100 cm 15 l/h ( 10%)
power supply: 230V - 50/60 Hz
absorption: 0,06 A, 8,05 W (230V)
insulation: class B
ambient temperature: 0 to 45 C, 95% R.H.
alarm contact: exchange contact, 250~ - 4(1)A
sound level: lift 100 cm < 39 dB(A)

4.6 Air filter

4.7 Air outlet plenum

The air filter is composed by a metal frame on which a polypropylene fibre is fixed. It can be easily removed thanks to two
textile tongues fixed on its frame.
The filter is immediately accessible by removing the external air
intake grill.

The air outlet plenum is made by heat-resistant ABS plastic


material in white colour. It permits to distribute the air on the 4
sides of the unit.
On each side of the cassette unit there are white flaps which
can be totally closed on one or two (max.) sides of the unit, particularly used in case of an air discharge into an adjacent room.

4.8 Air intake grill


The air intake grill is realized in heat-resistant ABS plastic
material, white colour, with a very discreet design, covering the
air outlet flaps. This particular combination of air intake and air
outlet grilles permits to avoid to have direct air flow against the
people in the room.
A perfect internal insulation with closed-cell insulating material
guarantees not to have problems of water condensation on the
grilles.

The air intake grill is fixed by pressing the pins on the four
angles into the air supply plenum: this very easy operation of
fixing and removing the grill facilitates all installation and maintenance operations.
A black rope with hook permits to make the maintenance operations in total safe.

On request, the air intake/outlet grilles can be painted in every RAL colour, with delivery time and prices to be agreed.

11

5. ELECTRICAL ACCESSORIES
5.1 QEC10

5.4 Electric heater KREL

The galvanized metal electric panel includes, besides the standard terminal board (see QEC00), a double insulated transformer (230/24 Vac 10 VA) for the power supply to modulating valves. It is supplied as standard in combination to CER10 and
CER30 controllers.

Stainless steel 1,5 kW electric heater supplied with 2 safety


thermostats, one with automatic resetting and the other one
with manual resetting (in accordance with 73/23 CEE and EMC
89/336 CEE Directives) and a power relay card (QEC20).
When the Electric heater is installed, the cassette unit is internally insulated with heat resistant insulating material.

5.2 QEC20
The galvanized metal electric panel includes, besides the standard terminal board (see QEC00), a 230 Vac relay card for supporting the electric heater and/or for controlling the fan speeds
in master/slave solution.
It can be used in combination to the controllers CMR00,
CMR10, CER00, CER20.

5.3 QEC30
The galvanized metal electric panel includes, besides the standard terminal board (see QEC00), a 24 Vac relay card for controlling the fan speeds in master/slave solution, together with a
double insulated transformer (230/24 Vac 10 VA) for the power
supply to modulating valves and/or 24 Vac electronic cards.
It can be used in combination to the controllers CER11, CER31,
CER00 in 24V configuration and CER20 in 24 V configuration.

5.5 Thermostats and electronic regulators


The UCS Cassette can be controlled by one of the controllers
chosen among the wide range of EURAPO regulators.
In the below table there is a short description of the functions of
each controller and some of the possible combinations between
the mostly used accessories and controllers.

For more information, please refer to the EURAPO Technical Manual for Regulators.

12

FUNCTIONS-COMPATIBILITY TABLES FOR EURAPO REGULATORS


Functions

CSR00 CSR40 CMR00 CMR10 CER00 CER10 CER20 CER30

Ventilation mode (Thermostated-OFF-Continuous)


Manual speed selection

Manual and automatic speed selection


Manual S/W switch
S/W changeover with dead band or external (centralized)
Room thermostat

Limited or locked temperature setting range

De-stratification function
Economy/occupancy function
Window contact
Frost protection (with heating valve only)
Operating mode LED (Summer-Winter)
Dirty filter alarm LED

Compatibility

CSR00 CSR40 CMR00 CMR10 CER00 CER10 CER20 CER30

Only 2 pipe system

2 or 4 pipe system

ON/OFF 230V valves

Modulating 24V valves


Remote room thermostat TAD

NTC water sensor for S/W changeover (2 pipe system only)


Electric heater (in alternative to the heating valve)

5.6 IR Infrared control


If the UCS cassette unit cannot be wire-controlled, there is the
possibility to use the Infrared control: one dedicated electronic
card must be installed in the electric panel, the Infrared receiver
is located in the middle of the air intake grill and the remote
controller permits to manage the unit. The Infrared receiver has
a mode LED indicating the operating mode: GREEN for cooling, RED for heating, ORANGE for alarm.

13

5.7 OMNIBUS Regulation


The UCS cassette unit can be equipped with the new digital
control system OMNIBUS, for a complete individual or centralized (BMS System) managing of the water terminal unit.
For more information, please refer to the OMNIBUS Technical
Manual.

5.8 WS Water sensor


The NTC water sensor (3 meter long) is requested in 2 pipe
systems when the Cassette unit must work both in heating and
cooling mode and it is controlled by a microprocessor control.
The Summer/Winter changeover works with the following procedures:
WS combined with CER00, CER20, CER30
Summer: water temperature <17C = cooling on
water temperature >19 C = cooling off
Winter: water temperature >32 C = valve open
water temperature <30 C = valve close
water temperature >35 C = fan on
water temperature <33 C = fan off
WS combined with CER10
Summer: water temperature <11 C1K = cooling on
water temperature >14 C1K = cooling off
Winter: water temperature >40 C1k = heating on
water temperature <30 C1K = heating off
The water sensor is not suitable when 2 way valves are mounted on the unit (i.e. DTH2B2 or DTJ2BM).

14

6. HYDRAULIC ACCESSORIES
6.1 DTH3B2 or DTH2B2 ON/OFF valves, 3 way 4 port
(DTH3B2) or 2 way (DTH2B2) for 2 or 4 pipe systems, 230 V

6.2 DTJ3BM or DTJ2BM Modulating (24V) valves, 3 way 4


ports (DTJ3BM) or 2 way (DTJ2BM) for 2 or 4 pipe systems

The ON/OFF regulating valves, G M (for 2 pipe system) and G " M


for the heating coil (4 pipe system) 3 way with bypass or 2 way, are
provided with thermoelectric actuator and connection tubes. The
direct flow is closed by not supplying power to the actuator.
They are factory fitted and wired.

The modulating 0-10V valves, G M (for 2 pipe system) and


G " M for the heating coil (4 pipe system) 3 way with bypass
or 2 way, are provided with modulating actuator and connection tubes. The direct flow is closed by not giving signal to the
actuator.
They are factory fitted and wired.
The modulating valves are highly recommended in combination to the UCS cassette unit, for the high levels of
comfort that they can provide.

The full bore ball shut-off valves ending with G F connection are
supplied separate as a kit. In the same kit the auxiliary drain pan is
included.
These valves are available also with on/off 24V actuators: for more
information, please contact the EURAPO staff.

The full bore ball shut-off valves ending with G F connection


are supplied separate as a kit. In the same kit the auxiliary drain
pan is included.

Pressure drop diagram


For two valves having different Kvs value

Pressure drop [kPa]

kvs 1,63
kvs 2,5

Water flow [mc/h]

BODY VALVES TECHNICAL FEATURES


H3B2 H2B2

J3BM J2BM

H3A2 H2A2
(imp. 4 tubi)

J3AM J2AM
(imp. 4 tubi)

Nominal pressure

PN16 PN10

PN16

PN16 PN10

PN16

Water connection

" Gm

" Gm

" Gm

" Gm

Kv: water flow rate

2,5

2,5

1,6

1,6

15

ACTUATORS TECHNICAL FEATURES

H3B2 H2B2

Power supply
(V-ph-Hz)

Running time
(s)

230-1-50(60)

180

Control signal
(Vdc)

Protection
grade
IP 42

H3A2 H2A2
J3BM J2BM
J3AM J2AM

Controllers
compatibility
CMR00 CMR10
CER00 CER20 Omnibus

24-1-50(60)

010

IP 40

CER10/11 CER30/31
Omnibus

In order to choose the correct type of valve it is necessary to know the systems technical specifications; for this reason
the consultant should take full responsibility for the correct choice of the valve.

6.3 DT Shut-off valve (ball valve)


The full bore ball valve with T handle is part of the hydraulic kit.
It is designed to separate the unit from the piping system if
maintenance is required.

16

TWO PIPE SYSTEM


1 Water Inlet

1/2 F

2 Water Outlet

1/2 F

FOUR PIPE SYSTEM


1 Inlet cooling water

1/2 F

2 Outlet cooling water

1/2 F

3 Inlet heating water

1/2 F

4 Outlet heating water

1/2 F

17

7. TECHNICAL DATA
7.1 Nominal air volumes at Pa (m3/h)
Nominal values (m3/h)
Model
Fan speed

Fan speed 1
Fan speed 2
Fan speed 3
Fan speed 4
Fan speed 5
Fan speed 6

221-421

231-431

232-432

678
583
523
412
316
216

673
579
518
401
301
204

852
776
715
594
471
344

External static pressure [Pa]

7.2 Air volume of the air supply collar into an adjacent room

Air volume [mc/h]

Diagram for the indicative air volume of the air outlet collar
(diam. 150 mm), at the highest fan speed.

18

7.3 Cooling capacities, 2 pipe system


Room temperature: 27 C d.b. 48% R.H. Water temperature: 7/12 C

Size
Fan speed 1

Fan speed 2

Fan speed 3

Fan speed 4

Fan speed 5

Fan speed 6

Total water content

Total cooling capacity


Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop

kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
l

221

231

232

2,759
2,153
474
8,6
2,519*
1,941
443
7,3
2,355
1,800
405
6,5
2,024
1,520
348
4,9
1,697*
1,252
292
3,6
1,300*
0,938
223
2,2
1,2

4,301
3,151
739
12,0
3,864*
2,798
664
9,9
3,563
2,559
613
8,5
2,938*
2,074
505
6,0
2,345*
1,629
403
4,0
1,701
1,160
292
2,3
1,7

5,052*
3,781
869
16,0
4,745
3,522
816
14,3
4,486
3,304
771
12,9
3,936*
2,855
677
10,2
3,320
2,368
571
7,5
2,608*
1,824
448
4,9
1,7

* Standard fan speed

19

7.4 Heating capacities, 2 pipe system


Room temperature 20 C 50% R.H. Water temperature: 70/60 C

Size
Fan speed 1

Fan speed 2

Fan speed 3

Fan speed 4

Fan speed 5

Fan speed 6

Total water content

* Standard fan speed

20

Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop

kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
l

221

231

232

6.219
544
8.7
5.597*
489
7.2
5.247
459
6.4
4.402
385
4.6
3.588*
314
3.2
2.656*
232
1.9
1,2

9.061
792
10.7
8.008*
700
8.6
7.346
642
7.3
5.895*
515
4.9
4.567*
399
3.1
3.204
280
1.6
1,7

10.943*
957
15.0
10.162
888
13.2
9.516
832
11.7
8.179*
715
8.9
6.779
593
6.3
5.147*
450
3.9
1,7

7.5 Cooling capacities, 4 pipe system


Room temperature: 27 C d.b. 48% R.H. Water temperature: 7/12 C

Size
Fan speed 1

Fan speed 2

Fan speed 3

Fan speed 4

Fan speed 5

Fan speed 6

Total water content

Total cooling capacity


Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop

kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
kW
kW
l/h
kPa
l

421

431

432

2,529
2,062
435
16,6
2,328*
1,865
400
14,3
2,189
1,732
376
12,8
1,902
1,469
327
10,0
1,613*
1,217
277
7,4
1,253*
0,919
215
4,7
0,9

4,121
3,076
708
19,9
3,723*
2,738
640
16,6
3,445
2,508
592
14,4
2,863*
2,042
492
10,3
2,300*
1,609
395
7,0
1,682
1,152
289
4,0
1,4

4,796*
3,677
825
26,1
4,522
3,428
777
23,5
4,289
3,223
737
21,4
3,789*
2,793
651
17,1
3,220
2,325
554
12,8
2,550*
1,799
438
8,4
1,4

* Standard fan speed

21

7.6 Heating capacities, 4 pipe system (additional 1 row coil)


Room temperature: 20 C 50% R.H. Water temperature: 70/60 C

Size
Fan speed 1

Fan speed 2

Fan speed 3

Fan speed 4

Fan speed 5

Fan speed 6

Total water content

* Standard fan speed

22

Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop

kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
kW
l/h
kPa
l

421

431

432

2,864
250
11,9
2,628*
230
10,2
2,468
216
9,1
2,144
187
7,1
1,821*
159
5,3
1,425*
125
3,4
0,3

3,752
328
19,9
3,428*
300
16,9
3,203
280
15,0
2,728*
238
11,2
2,260*
198
8,0
1,728
151
4,9
0,3

4,311*
377
25,5
4,081
357
23,1
3,889
340
21,2
3,482*
304
17,4
3,020
264
13,5
2,470*
216
9,4
0,3

7.7 Electrical data


Power supply: 230-1-50 (V-ph-Hz)
Model
Nominal absorbed power

Nominal absorbed current

Fan speed 1
Fan speed 2
Fan speed 3
Fan speed 4
Fan speed 5
Fan speed 6
Fan speed 1
Fan speed 2
Fan speed 3
Fan speed 4
Fan speed 5
Fan speed 6

[W]
[W]
[W]
[W]
[W]
[W]
[A]
[A]
[A]
[A]
[A]
[A]

221-421

231-431

232-432

64
53*
46
34
24*
15*
0,310
0,250*
0,210
0,160
0,110*
0,070*

62
52*
46
34*
24*
15
0,310
0,240*
0,210
0,160*
0,110*
0,070

79*
65
56
42*
29
19*
0,350*
0,280
0,250
0,180*
0,130
0,080*

* Standard fan speed

Electrical data refer to standard UCS cassette units with clean filter and without external static pressure. A dirty filter or an
external air pressure drop will lower the absorbed power level.
The installation of electric accessories increase the absorbed power level.

7.8 Working operation limits


The UCS Cassette units can work correctly only if the following
operational limits are respected.

Max. operating pressure (water side): 800 kPa


Min. inlet cold water temperature: -5 C
Max. inlet cold water temperature: 20 C
Min. inlet hot water temperature: 35 C
Max. inlet hot water temperature: 85 C

For more detailed information, please use the EURAPO software


for selection.

23

8. NOISE LEVELS
8.1 Sound power
The acoustic emission characteristics of any noise source is
defined as its sound power (SWL). This typical measurement indicates the total radiated energy which does not vary
for a given noise source; that is, it does not depend on the
observer, location, distance or any other factor which is not
part of the source.
Following please find the values of the sound power level.

8.2 Sound pressure in a closed environment


The perceived noise radiated from a sound source is something
quite different: noise perception is indicated by its sound
pressure (SPL). Even though it is caused by the emission of a
sound energy, it greatly depends on the environment through
which the sound travels, on the distance from the source and on
all other circumstances that are not directly related to the primary noise source.

Sound power level

Besides the distance from the source, the most important factor
that influences the sound pressure (and, as a result, the perceived noise) in a closed environment is the amount of sound
energy reflected off surfaces that have a greater or lesser reflection capacity: it depends, therefore, on the re-transmission of
sound energy (power) acting upon reflecting surfaces.
Covering the walls with sound absorbing material (i.e., material
with a low sound reflecting capacity) is the most effective way to
reduce the noise level in a closed environment.
The following values indicate the sound pressure emitted by the
cassette unit, calculated at 1,5 meter distance and with a reverberation time of 0,3 seconds. By using the EURAPO software
for selection it is possible to calculate the new sound pressure
level obtained by changing the parameters: room volume,
distance from the noise source and reverberation time.
The reverberation time measures the sound characteristics of a
room: it increases as the room dimensions increase and decreases as the sound absorption capacity of the structure increases.

Sound pressure level in a closed environment


dB (A)

Model 221

Model 231

Model 232

Model 421

Model 431

Model 432

Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4
Fan speed 5 MED
Fan speed 6 MIN
Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4 MED
Fan speed 5 MIN
Fan speed 6
Fan speed 1 MAX
Fan speed 2
Fan speed 3
Fan speed 4 MED
Fan speed 5
Fan speed 6 MIN
Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4
Fan speed 5 MED
Fan speed 6 MIN
Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4 MED
Fan speed 5 MIN
Fan speed 6
Fan speed 1 MAX
Fan speed 2
Fan speed 3
Fan speed 4 MED
Fan speed 5
Fan speed 6 MIN

54
51
48
43
39
31
54
51
48
43
37
32
59
57
55
51
45
38
54
51
48
43
39
31
54
51
48
43
37
32
59
57
55
51
45
38

dB (A)
Model 221

Model 231

Model 232

Model 421

Model 431

Model 432

Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4
Fan speed 5 MED
Fan speed 6 MIN
Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4 MED
Fan speed 5 MIN
Fan speed 6
Fan speed 1 MAX
Fan speed 2
Fan speed 3
Fan speed 4 MED
Fan speed 5
Fan speed 6 MIN
Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4
Fan speed 5 MED
Fan speed 6 MIN
Fan speed 1
Fan speed 2 MAX
Fan speed 3
Fan speed 4 MED
Fan speed 5 MIN
Fan speed 6
Fan speed 1 MAX
Fan speed 2
Fan speed 3
Fan speed 4 MED
Fan speed 5
Fan speed 6 MIN

42
39
37
32
29
22
42
39
37
32
27
23
47
45
43
39
34
27
42
39
37
32
29
22
42
39
37
32
27
23
47
45
43
39
34
27

In order to select the UCS Cassette units with calculating conditions differing from the standard ones, please use the
EURAPO software for selection.

24

ENCLOSURE 1
ELECTRICAL CONNECTIONS

LEGEND
(for all the electric diagrams)
M

Fan motor

EV

Regulating valve: EVC for cooling; EVH for heating

MS

Terminal board for motor

RE

Electric heater

SV

Fan speed selector (OFF-1-2-3)

PR

Relay card

PE

Earth

TSRM

Safety thermostat with manual resetting

Neutral

TSRA

Safety thermostat with automatic resetting

Phase

Terminal board

TA

Room temperature thermostat: E = summer, I = winter

NOTE. If other configurations are required, different from the standard ones, please refer to the instruction manual of
every specific EURAPO regulator.

QEC00

25

QEC00 EV

QEC00 EVC EVH

26

QEC20 EV RE

QEC20 EVC EVH MASTER/SLAVE

27

Janna/Pn stampa digitale gfp.it 03.08

Via Malignani, 12 Z.I. Vallenoncello


33170 Pordenone Italy
Tel. ++39 0434 572552 Fax ++39 0434 28667
www.eurapo.it e-mail: info@eurapo.it

As programs and technologies are always improving, description, data and


drawings must be intended as merely indicative and can be modified
without any notice.