Sie sind auf Seite 1von 34

VENTILATION AIR CONDITIONING HEATING

AIR HANDLING UNITS

TECHNICAL CATALOGUE

AIR HANDLING UNITS

CONTENTS

06.01-01

AHU - AIR HANDLING UNITS

06.01-02

DESCRIPTION ON TYPES OF SECTIONS

06.01-06

HORIZONTAL VERSION - AHU - H


Schemes, overall and joined dimensions

06.01-08

DOUBLE-DECK VERSION - AHU-DD


Schemes, overall and joined dimensions

10

06.01-10

UNIT SECTIONS
Schemes, overall and joined dimensions, weight

12

06.01-16

THERMAL CHARACTERISTICS

18

06.01-18

AERODYNAMIC CHARACTERISTICS

20

06.01-26

RECOMMENDATION FOR INSTALLATION

28

06.01-28

FUNCTIONAL SCHEMES FOR MANAGEMENT, CONTROL EQUIPMENT


AND AUTOMATION

30

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

www.tangra.bg

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-01

AHU AIR HANDLING UNITS

Model

Air handling units are modular built for indoor or outdoor installation. Intended to be build in general ventilation and airconditioning systems. Universal application: office buildings, stores, hotels and restaurants, swimming pools, industrial
buildings, etc. Depending of the air flow, they could be separated in nine standard sizes from 6000 m/h to 45000 m/h.

increased noise requirments

regular mode
industrial systems
Modifications depending on the installations of air handling units:
AHUH - horizontal version (air handling unit with mixing and intermediate coolant) (AHU 06 AHU 45H)
AHUDD - double deck version with heat exchanger air-air (AHU 06 AHU 24)

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

www.tangra.bg

06.01-02
AHUH / AHU-DD

AIR HANDLING UNITS

Description on types of sections


Construction
Insulation panels made of extruded polystyrene XPS type
with density 32 kg/m, thermal conductivity =0.039 W/m K
and combustibility class M1.
Upon request panels could be made of compressed mineral
wool with density 60-100 kg/m, thermal conductivity
=0.037 W/m K and combustibility class M0.
The panels are fixed with self-tapping screws or metric bolts.
Sides which should be opened for inspection and
maintenance are performed as doors, equipped with
knuckles and special locks. Revision covers could be fixed to
the supporting frame with reamers upon request.
Visual inspection is made through manhole incorporated in
the panel.
Sealing of the panels to the constructions is ensured by
strips of self-adhesive cellular rubber.

Supporting frame made of special aluminium profiles,


connected with aluminium corners. Construction sides
are closed with thermo and acoustic insulated panels. In
thus structure (UU universal section) are incorporated all
necessary elements for air treatment.
Side panels
Panels made of galvanized sheet steel with powder coating
at their external side (RAL7035) and heat and acoustic
insulated middle layer.
Two versions of side panels are possible:
Standard thickness of 25mm for model sizes from AHU 06
to AHU 20
Standard thickness of 50mm for model sizes from AHU 24
to AHU 45H
On request - for outdoor installation with thickness 50mm
(AHU06 AHU20)

Description on types of sections


U - Fan section
The section consists of centrifugal fan with forward or backward curved impeller. The type of fan is selected depending to the
specific requirements, according to the air flow and resistance of the installation:
BDB - Belt-driven double inlet centrifugal fan with backward curved impeller, standard version (section 03.07)
CBP - Belt-driven double inlet centrifugal fan with forward curved impeller (section 03.08) only for models AHU 06,
AHU 09, AHU 12
BPF - Direct-driven single inlet centrifugal fan with backward curved impeller.
The impellers made by Soler&Palau are statically and dynamically balanced.
Mounted to the frame on anti-vibration mounts, equipped with flexible connection. This avoids the transmission of vibration
to the casing.
Fans are driven by electrical motor, using belt drive or directly incorporated to the fan. The belts which are used are type B or
SPB. Belt pulleys are with fixing bush (hub). For easier belt tension motors are installed on a slider.
All motors are three phase 400V/50Hz, protection class IP54, class F insulation and working mode S1 (continuous). Ambient
temperature: - 30C +40C.
Maximum working temperature +60C and maximum altitude 1000m.

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-03

Description on types of sections


U - Thermal section
Include heating and/or cooling section (heat exchanger), drop separator and drain tray.
Types of sections (heat exchanger) that could be incorporated (section 02.05):
Two-rows (2R) basically used in heating mode.
Four-rows (4R) basically used in cooling mode.
Six-rows (6R) and eight-rows (8R) could be produced upon request.
Heat exchangers Water-air (heating and cooling) are tubular-plate type, made of copper pipes with strung on them aluminium
fins with step 2.3mm. Good contact between pipes and fins is achieved by mechanical distension. Incorporated in the section
by guides (rails), ensuring the sealing by air.
Drop eliminator is a cassette of profiled blades, designed to retain the condensation after the cooling section. Made of special
polymer profiles. Drain tray with connection, is mounted at the bottom of the cooling section.
Siphon must be ensured. He should be placed before condensation line is connected to the building installation.

AFU - Air filter section


Air filter section contains one or two consequently mounted air filters with different efficiency from lower to higher class from
G2 to F9, according BDS EN 779 (section 02.03).
For rough dust several air filter cassettes type AFC-V (class G3) or AFC-Z (class G4) are mounted together. The cassettes slide
into the section through glides (rails) and are fixed with profiles and bolt connection.
For fine purification filter wall made of several bad filters type AFC-B (class F6 F8). The cassettes are fixed to the filter wall
through reamers.
Air filter cassettes are disposable, they are consumables for the air handling units.
In more specific the section could be completed with other type air filters: reusable metal filters, carbon or absolute filters,
class H10 H13.

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

www.tangra.bg

06.01-04
AHUH / AHU-DD

AIR HANDLING UNITS

Description on types of sections


U - Mixing section
Build of one or two universal sections, horizontally or vertically adjoined.
Equipped with three dampers (PRJ multiple leaf damper, section 02.09):
Outlet (exhaust air)
Inlet (fresh air)
Mixing mounted between both streams
For smooth control is recommended damper with electric motor (actuator) and device for uniform signal control.

RU-REC / RU-ROT Recuperative (heat recovery) section


Recuperative heat exchanger Air-air incorporated in double deck construction:
RU-REC with plate heat exchanger type REC-AL, efficiency 50-61% (section 02.07).
RU-ROT with rotary regenerative heat exchanger type RRU, efficiency 67-80%.
Heat exchanger section RU-REC is equipped with by-pass damper type PRJ (section 02.09) at the fresh air stream and
drain tray at the exhaustion side. By-pass damper is used for defrosting of recuperator in winter and gave the possibility for
working in free cooling mode during transitional seasons. The heat exchanger transfer heat only, from the warm to the cold
air stream. Suitable for dehumidification of swimming pool installations.
Section RU-ROT is provided with rotary aluminium recuparator with motor and control panel. The recuperator transfer
heat and moisture between both streams. Suitable for air-conditioning installations at premises without large separation of
moisture.
Efficiency of heat exchangers depends on their type and specific parameters of the air. Calculated to each individual case.

REC-AL

www.tangra.bg

ROT

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-05

Description on types of sections


SAU - Sound attenuators section
Build in universal section baffles, placed parallel of the air stream. Baffles made of plates of fiber-glass, wrapped in glass
material to prevent atomization, protected by a safety metal grid and frame of galvanized steel sheet.
Standard version:
SA 10/10 baffles with thickness D=100 mm and distance between baffles S=100 mm effective from 500 to 4000 Hz
(middle range frequency). Section length L=1000mm
On customers request:
SA 10/6 baffles with thickness D=100 mm and distance between baffles S=60 mm effective in high range frequency.
SA 20/12 baffles with thickness D=200 mm and distance between baffles S=120 mm effective in low range frequency.
Different length of section and baffles: L=500, 1000, 1500 and 2000mm.
Sound attenuating section could be replaced by duct mounted sound attenuator type DSA (section 02.01).
InU / ExhU - Inlet / outlet sections
Sections similar to those described above, equipped with one or more control valves (PJR) with build-in single-stage filter for
inlet section or EK-N duct type electric heater.
Supporting frame
Made of aluminium corners and profiles of galvanized sheet steel with high 100mm. Mounted under each section of onestoreyed units. In double deck version for top row section supporting frame is not provided. To ease the transportation and
installation in the supporting frame are provided openings for lift up with mechanization.

Options and additional features


In air handling units could be incorporated also:
Fans with 2-speed motors
Fans with direct-drive motors and inverter
Heating section with working fluid steam
Steam humidifier
For outdoor installation:
Sections with increased insulation thickness (50mm) for outdoor installation (AHU 06- AHU20)
Additional roof covers to lead the rain water
Protection guard for direct discharge with net or NJR
Precast unit made of hot galvanized profile tube and adjustable in height
Steps (feet) for installation on surface with inclination up to 5%.
Management, control and automation:
Anti-frost protection of water sections
Torn belt signalization
Dirty filter signalization
Electric motor (actuator) for control valves (PJR, PJR-BP)
3-way valves with actuator for heating and cooling sections
Automatic defrost of recuperative heat exchanger (REC) and possibility of working in free cooling mode
Speed control of the rotary regenerative heat exchanger
Air temperature and/or humidity remote tracking
Electric board for control and automation

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

www.tangra.bg

06.01-06
AHUH / AHU-DD

AIR HANDLING UNITS

Horizontal version

AHU-H

Principle scheme

1.
2.
3.
4.

U - Fan section
U - Thermal section
AFU - Air filter section with two-stage cleaning
U - Mixing section

Overall and joined dimentions

Model

Air flow V
[m/h]

B
[mm]

H
[mm]

L1
[mm]

L2
[mm]

L3
[mm]

L4.1
[mm]

b=h
[mm]

c
[mm]

d
[mm]

e
[mm]

f
[mm]

AHU 06

30006500

1350

950

1300

800

1000

600

450

800

400

800

300

AHU 09

50009500

1600

1050

1400

800

1000

600

500

1000

500

900

400

AHU 12

680012500

1850

1150

1500

1000

1000

600

570

1200

500

1200

400

AHU 16

900016500

2100

1250

1500

1000

1000

700

640

1200

700

1300

500

AHU 20

1100021000

2360

1350

1700

1000

1000

800

720

1400

800

1400

600

AHU 24

1400025000

2360

1500

1800

1000

1200

800

800

1600

800

1600

600

AHU 30H

1700031000

2360

1700

1900

1200

1200

1000

900

1600

1000

2000

600

AHU 36H

2000037000

2360

1900

2100

1200

1200

1000

1000

1600

1200

2000

700

AHU 45H

2300048000

2360

2300

2400

1200

1200

1000

1300

1800

1200

2200

800

Note:
Special sizes and combinations on an individual project.
Size L1 depends on type and position of fan.
Size L2 is related to thermal section, consisting of COT+COX+ drop eliminator.
Size L3 is related to air filter section with two stages filter G3 and F8
For more information, please, see the corresponding sections in our catalogue.

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

AIR HANDLING UNITS

AHUH / AHU-DD

Horizontal version

06.01-07
AHU-H

Other possible combinations


1.
2.
3.
4.
5.
6.
7.
8.
9.

U - Fan section
TU - Thermal section with build in AFC air filter
InU - Inlet section with AFC-V air filter
CMU - Mixing section
UU - Universal section
SAU - Sound attenuating section
ExhU - Outlet unit with duct-type electric heater EK-N.
BU - Fan section independent box
NJZ - External grille

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

www.tangra.bg

06.01-08
AHUH / AHU-DD

AIR HANDLING UNITS

Double-deck version

AHU-DD

Principles schemes

1. BU - Fan section
2. TU - Thermal section
3. InU - Inlet section with AFC-V air
filter
4. RU-REC - Recuperative section with
plate heat exchanger
5. RU-ROT - Recuperative section with
rotary regenerative heat exchanger
6. InU - Inlet section with two stages of
cleaning

Overall and joined dimentions

Model

Air flow V
[m/h]

B
Hdd
H
H1
L1
L2
L3
L4.2
L4.3
b
h
c
d
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

AHU 06

30006500

1350 2000

AHU 09

50009500

AHU 12

1050 1300

800

2000

600

450

450

800

400

1600 2000 1050

950

1400

800

600

2000

600

500

500

1000

500

680012500

1850 2100

950

1500 1000

600

2000

600

570

570

1200

500

AHU 16

900016500

2100 2300 1250 1050 1500 1000

700

2000

600

640

640

1200

700

AHU 20

1100021000

2360 2500 1350

800

2000

600

720

720

1400

800

AHU 24
1400025000 2360 2850 1500 1350 1800 1000 800 2850 1000
Note:
Special sizes and combinations on an individual project.
Size L1 depends on type and position of fan.
Size L2 is related to thermal section, consisting of COT+COX+ drop eliminator.
Size L3 is related to air filter section with air filter AFC-V G3
For more information, please, see the corresponding sections in our catalogue.

800

800

1600

800

www.tangra.bg

950
1150

1150

1700 1000

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

10

AIR HANDLING UNITS

AHUH / AHU-DD

Double-deck version

06.01-09
AHU-DD

Other possible combination

1.
2.
3.
4.

U Fan section
B
TU - Thermal section
InU - Inlet section with AFC-V air filter
RU-REC - Recuperative section with plate
heat exchanger
5. RU-ROT - Recuperative section with rotary
regenerative heat exchanger
6. SAU - Sound attenuating section
7. ExhU - Outlet unit with bag filter AFC-B
8. UU - Universal section
9. ExhU - Outlet unit with duct-type electric
heater EK-N
10. NJZ - External grille

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

11

www.tangra.bg

06.01-10
AHUH / AHU-DD

AIR HANDLING UNITS

Unit sections
BU - Fan section
Possible schemes

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

12

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-11

Unit sections
BU - Fan section
BU aaa / bc d / ( V / H. )

example from p. 06.01-27 BU 16 / 32 R / (15500/700)

1. aaa Type and size of the fan



- fan type BDB (standard version)

fan type CBP

B fan type BPF
2. bc scheme depending on the type and position of the fan (p.06.01-10):

1c; 2c; 3c; 4c; 5c and 6c - position in section air handling unit (intermediate or ending)

b1 fan posotion 90

b2 fan posotion 270

b3 fan posotion 0
3. d air stream direction according to the service side:

R from left to right

L from right to left
4. V [m/h] air flow of the fan
5. H. [Pa] necessary external pressure of the fan

Overall and joined dimensions, weight

Model

Fan

BU 06

BDB 355C

BU 06A

CBP 12/9

BU 09

BDB 400C

BU 09A

CBP 15/11

BU 12

BDB 450C

BU 12A

CBP 18/18

BU 16

B
H
L1.1
L1.2
L1.3
b
h
e
f
k
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
450

175

135

300

3.0

270

310

340

190

290

300

4.0

245

500

500

180

150

450

4.0

331

370

400

190

280

450

4.0

304

570

570

180

155

550

5.5

416

560

480

180

230

550

5.5

385

1250

640

640

180

165

650

7.5

497

1800

1350

720

720

200

135

650

11.0

636

1800

1950

1450

800

800

220

135

600

15.0

781

1700

1900

2100

1550

900

900

220

190

550

15.0

910

2360

1900

2100

2250

1000

1000

265

180

18.5

1105

2360

2300

2250

2450

1130

1130

285

380

18.5

1335

2400

2600

1300

1300

285

220

22.0

1489

950

1300

1300

950

1600

1050

1300

1400

1050

1850

1150

1400

1500

1150

BDB 500C

2100

1250

1500

1600

BU 20

BDB 560C

2360

1350

1700

BU 24

BDB 630C

2360

1500

BU 30

BDB 710C

2360

BU 36

BDB 800T
BDB 900T
BDB 1000T

c
[mm]

450

1350

BU 45

N.
[kW]

Model

Fan

B
[mm]

H
[mm]

L1.4
[mm]

Nel.
[kW]

Weight
[mm]

Performance scheme

c
[mm]

d
[mm]

BU 06B

BPF 400

1350

950

950

3.0

187

61, 62, 63 and 64

800

400

BU 09B

BPF 450

1600

1050

950

4.0

231

61, 62, 63 and 64

1000

500

BU 12B

BPF 500

1850

1150

1050

5.5

287

61, 62, 63 and 64

1200

500

BU 16B

BPF 560

2100

1250

1150

7.5

371

61, 62, 63 and 64

1200

700

BU 20B

BPF 630

2360

1350

1350

11.0

472

61, 62, 63 and 64

1400

800

BU 24B

BPF 710

2360

1500

1500

15.0

606

61, 62, 63 and 64

1600

800

BU 30B

BPF 800

2360

1700

1700

15.0

686

61, 62, 63 and 64

1600

1000

BU 36B

BPF 900

2360

1900

1900

18.5

939

61, 62, 63 and 64

1600

1200

BU 45B

BPF 1000

2360

2300

2050

22.0

1074

61, 62, 63 and 64

1800

1200

Note:
Dimensions c/d of the inlet / outlet flange (PJR) are valid for all fan sections
TM total weight of fan section BU ** / 11(12) - R(L)
Nominal power of three phase motor Nel.
Aerodynamic and acoustic characteristics, see sections from 06.0118 up to 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

13

www.tangra.bg

06.01-12
AHUH / AHU-DD

AIR HANDLING UNITS

Unit sections
TU - Thermal section
Thermal heating section
with 2 or 4 rows water coil unit
TU OT *** / 2R - R(L) as standard
TU OT *** / 4R - R(L)
Thermal cooling section
with 2, 4, 6 or 8 rows water coil unit
with drop eliminator and drain tray
TU OX *** / 2R / - R(L)
TU OX *** / 4R / - R(L) as standard
TU OX *** / 6(8)R / - R(L) - upon request
Thermal section with heat exchangers:
heating unit: 2- or 4- rows,
cooling unit: 2-, 4-, 6- or 8-rows
with drop eliminator and drain tray
TU *** / 2R / 2R / K - R(L)
TU *** / 2R / 4R / K - R(L) as standard
TU *** / 4R / 4R / K - R(L)
TU *** / 4R / 6(8)R / K - R(L)
Thermal section with heat exchangers:
heating unit: 2- or 4-rows,
cooling unit: 2-, 4-, 6- or 8-rows
with drop eliminator and drain tray and air filter AFC-V (G3)
TU *** / 2R / 2R / K/ F - R(L)
TU *** / 2R / 4R / K / F - R(L) as standard
TU *** / 4R / 4R / K / F - R(L)
TU *** / 4R / 6(8)R / K / F - R(L)

Overall and joined dimensions, weight


Heat exchangers
B
H
L2.1
L2.2
L2.3
L2.4
[mm] [mm] [mm] [mm] [mm] [mm] COT (2R) / COX (4R)

2R

4R

weight [kg]
2R
4R
T

TU *** 06

1350

950

500

600

800

1100

1000/600 - *R

1"

1"

17

27

197

TU *** 09

1600 1050

500

600

1000 1300

1200/800 - *R

1"

2"

25

43

268

TU *** 12

1850

1150

500

600

1000 1300

1400/800 - *R

1"

2"

32

55

319

TU *** 16

2100

1250

500

600

1000 1300

1600/1000 - *R

2"

2"

45

74

384

TU *** 20

2360 1350

500

600

1000 1300

2000/1000 - *R

2"

3"

52

89

452

TU *** 24

2360 1500

600

800

1200 1500

2000/1200 - *R

2"

3"

65

106

561

TU *** 30

2360 1700

600

800

1200 1500

2000/1400 - *R

2"

4"

75

130

620

TU *** 36

2360 1900

600

800

1200 1500

2000/1600 - *R

2"

4"

83

144

668

TU *** 45

2360 2300

600

800

1200 1500

2000/2000 - *R

2"

4"

103

180

773

Model

Note:
R(L) - Air direction from the supply side of water coil unit
Weight of a single heat exchanger 2R or 4R
TM total weight of TU ** / 2R / 4R / K - R(L)
Technical characteristics, see p.06.01-16

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

14

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-13

Unit sections
AFU - Air filter section
Air filter section with single or double-stage
cleaning with filter cassettes type AFC-V G3 (G4)
and/or bag filters type AFC-B (F6 F8).
AFU *** / G4 / HxL - R(L)
AFU *** / G4+F8 / HxL - R(L)
Other types filter sections upon request

CMU - Mixing section

CMU *** / HxL - R(L)

Overall and joined dimensions, weight

Model

B
[mm]

H
[mm]

H1
[mm]

L3.1
[mm]

L3.2
[mm]

L4.1
[mm]

c1
[mm]

d1
[mm]

e
[mm]

f
[mm]

TM
[kg]

AFU 06

CMU 06

1350

950

1050

600

1000

600

500

400

800

300

152

AFU 09

CMU 09

1600

1050

950

600

1000

600

600

500

800

500

177

AFU 12

CMU 12

1850

1150

950

600

1000

600

800

500

1000

500

203

AFU 16

CMU 16

2100

1250

1050

600

1000

700

800

600

1200

600

229

AFU 20

CMU 20

2360

1350

1150

600

1000

700

1000

600

1400

600

258

AFU 24

CMU 24

2360

1500

1350

800

1200

850

1000

700

1600

700

327

AFU 30

CMU 30

2360

1700

800

1200

850

1100

700

1800

700

339

AFU 36

CMU 36

2360

1900

800

1200

950

1200

900

1800

800

358

AFU 45

CMU 45

2360

2300

800

1300

950

1400

1000

2220

800

395

Note:
PJR - multiple leaf damper and electric motor (actuator) in section 02.09
H1 in double deck version AHU-DD, see p. 06.01 - 08
T tentative weight of sections with length L=1000mm
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

15

www.tangra.bg

06.01-14
AHUH / AHU-DD

AIR HANDLING UNITS

Unit sections
RU-REU / RU-ROT Recuperative ((heat recovery)) section

RU-REC - Recuperative section with plate heat exchanger


REC-AL, drain tray and by-pass damper PJR-BP for fresh air
RU-REC ** - R(L) / L1(R1)

RU-ROT - Recuperative section with


rotary regenerative heat exchanger with motor
RU-ROT ** - R(L) / L1(R1)
Note:
Air stream direction from the inspection side:
fresh air:

R from left to right

L from right to left
exhausted air:

R1 from left to right

L1 from right to left

Overall and joined dimenstions, weight

Model

Air flow V
[m/h]

B
[mm]

Hdd
[mm]

RU-REC
h
L4.2
REC AL
[mm]
[mm]

RU-RO
NEL.
ROT
[W]

A0
[m2]

MT
[kg]

L4.3
[mm]

MT
[kg]

RU-** 06

6000

1350

2000

2200

1200/9

840

0.83

446

600

1250

90

212

RU-** 09

9000

1600

2000

2000

1200/9

1080

1.04

512

600

1500

90

281

RU-** 12

12000

1850

2100

2000

1200/9

1280

1.24

569

600

1750

180

341

RU-** 16

16000

2100

2300

2000

1200/9

1580

1.55

644

600

2000

180

412

RU-** 20

20000

2360

2500

2000

1200/9

1920

1.86

744

600

2250

180

556

RU-REC 24

24000

2360

2850

2850

1800/9

1920

2.79

1359

RU-ROT 24

24000

2600

2850

1200

2500

180

776

Note:
Heat exchanger must be protected with air filters at both streams
RU-REC 06 with incorporated air filter AFC-Z
Inlet section of plate heat exchanger 0 (m)
Drive motor of the rotary regenerative heat exchanger is single-phase with nominal power Nel.
MT - weight of the recuperative section
Efficiency of the recuperators, see p. 06.01-17

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

16

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-15

Unit sections
SAU - Sound attenuating section
SAU ** -10/10 - HxL - R(L) standard version
SAU ** -10/6 - HxL - R(L)
SAU ** -20/12 - HxL - R(L)

UU - Universal section
UU ** / HxL - R(L)

InU / ExhU - Inlet / outlet sections


Inlet section with one or two dampers (PJR)
InU *** / 1 - HxL - R(L)
InU *** / 2 - HxL - R(L)
Outlet section with one or two dampers (PJR)
ExhU *** / 1 - HxL - R(L)
ExhU *** / 2 - HxL - R(L)
Inlet section with air filter AFC-V G3 (G4) and one or two
dampers (PJR)
InU *** / 1(2) / F+(F) / HxL - R(L)

Overall and joined dimensions, weight


Model

B
[mm]

H
[mm]

H1
[mm]

L5
[mm]

L6
[mm]

L7.1
[mm]

L7.2
[mm]

MT
[kg]

SAU 06

InU/ ExhU 06

1350

950

1050

6002000

5002000

600

800

217

SAU 09

InU/ ExhU 09

1600

1050

950

6002000

5002000

600

800

278

SAU 12

InU/ ExhU 12

1850

1150

950

6002000

5002000

600

800

327

SAU 16

InU/ ExhU 16

2100

1250

1050

6002000

5002000

600

1000

379

SAU 20

InU/ ExhU 20

2360

1350

1250

6002000

5002000

600

1000

435

SAU 24

InU/ ExhU 24

2360

1500

1350

6002000

6002000

800

1000

518

SAU 30

InU/ ExhU 30

2360

1700

6002000

6002000

800

1200

547

SAU 36

InU/ ExhU 36

2360

1900

6002000

6002000

800

1200

592

SAU 45

InU/ ExhU 45

2360

2300

6002000

6002000

800

1200

682

Note:
For double deck version AHU-DD height of the section is H or H1
MT - weight of the sound attenuating section SAU ** -10/10 - BxHxL=1000mm
Dimensions of flange and dampers (PJR) have to be indicated in the order
For weight of universal, inlet or outlet sections, please use approximate weight per meter (see . 06.01-13)
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

17

www.tangra.bg

06.01-16
AHUH / AHU-DD

AIR HANDLING UNITS

Thermal characteristics / - counter-flow, atmospheric pressure - 710 mmHg


2-rows section

Heating mode

Cooling mode

1000/600 - 2R
6000
1200/800 - 2R
9000
1400/800 - 2R
12000
1600/1000 - 2R
16000
2000/1000 - 2R
20000
2000/1200 - 2R
24000
2000/1400 - 2R
30000
2000/1600 - 2R
36000
2000/2000 - 2R
45000
After recuperator
1000/600 - 2R
6000
1200/800 - 2R
9000
1400/800 - 2R
12000
1600/1000 - 2R
16000
2000/1000 - 2R
20000
2000/1200 - 2R
24000
2000/1400 - 2R
30000
2000/1600 - 2R
36000
2000/2000 - 2R
45000

air1 =-12, water1=80; water2 =60


Qheat
air2
Pair
Vwater
Pwater
[kW]
[]
[Pa]
[m3/h] [kPa]
71.6
23.2
33
3.1
4.8
108.1
23.4
29
4.6
4.1
146.3
24.0
42
6.3
6.7
204.6
25.7
36
8.8
8.8
257.4
26.0
36
11.1
12.0
312.2
26.4
36
13.4
7.6
384.9
25.8
40
16.5
12.3
448.7
24.8
44
19.3
13.1
569.7
25.3
43
24.5
18.0
air1 =+5, water1=80; water2 = 60
55.7
32.4
35
2.4
3.0
83.7
32.4
31
3.6
2.6
113.1
32.8
44
4.9
4.2
158.6
34.2
38
6.8
5.5
199.8
34.5
38
8.6
7.6
242.7
34.8
37
10.4
4.8
300.0
34.5
41
12.9
7.8
349.6
33.6
46
15.0
8.4
444.8
34.2
45
19.1
9.7

air1 =33, =40%, water1 =7,water2 =12


Qheat
air2
Pair
Vwater
Pwater
[kW]
[]
[Pa]
[m3/h] [kPa]
27.1
23.6
46
4.6
12.7
39.4
23.7
40
6.8
10.2
52.8
23.6
57
9.1
16.5
75.3
23.1
49
13.0
22.2
95.8
23.0
46
16.5
31.0
117.4
22.8
46
20.2
20.1
148.0
22.9
55
25.5
33.8
172.2
23.2
61
29.6
36.0
222.3
23.0
58
38.2
42.9
air1=30, =45%, water1 =7,water2=12
22.8
22.0
45
3.9
9.4
33.0
22.1
39
5.7
7.4
44.1
22.0
56
7.6
11.9
63.1
21.5
48
10.9
16.2
80.5
21.4
49
13.9
22.7
98.8
21.3
48
17.0
14.7
125.2
21.3
54
21.5
25.0
145.6
21.6
60
25.1
26.7
188.7
21.4
59
32.5
31.9

4-rows section

Heating mode

Cooling mode

air1 =-12, water1=80; water2 =60


Qheat
air2
Pair
Vwater
Pwater
[kW]
[]
[Pa]
[m3/h] [kPa]
112.9
43.5
69
4.9
4.5
170.9
44.0
61
7.3
2.6
229.6
44.4
88
9.9
3.3
317.6
46.5
75
13.6
3.0
399.3
46.9
75
17.2
3.7
481.0
47.1
74
20.7
4.1
589.4
45.9
82
25.3
4.8
692.1
44.7
92
29.7
5.7
869.1
45.0
90
37.4
6.9
air1 =+5, water1=80; water2 = 60
88.3
48.4
72
3.8
2.9
133.4
48.7
63
5.7
1.6
178.9
49.0
91
7.7
2.1
248.1
50.7
78
10.7
1.9
312.4
51.1
78
13.4
2.4
376.4
51.3
76
16.2
2.6
460.9
50.3
85
19.8
3.1
540.9
49.3
95
23.3
3.7
679.2
49.5
93
29.2
4.4

air1 =33, =40%, water1 =7,water2 =12


Qheat
air2
Pair
Vwater
Pwater
[kW]
[]
[Pa]
[m3/h] [kPa]
43.1
18.3
92
7.4
12.3
64.2
18.3
81
11.1
6.8
84.9
18.3
115
14.6
8.4
119.7
17.6
99
20.6
8.0
152.2
17.5
99
26.2
10.1
183.4
17.4
97
31.6
11.0
224.2
17.7
108
38.6
13.0
262.6
18.1
122
45.2
15.3
329.8
18.0
119
56.7
18.4
air1=30, =45%, water1 =7,water2=12
36.5
17.4
90
6.3
9.1
54.0
17.4
80
9.3
4.9
71.3
17.4
113
12.3
6.1
101.0
16.9
98
17.4
5.9
128.7
16.7
98
22.1
7.5
155.1
16.7
96
26.7
8.1
189.4
16.9
107
32.6
9.6
221.7
17.2
120
38.2
11.3
278.6
17.2
117
48.0
13.6

Model

Model

Vair
m/h

Vair
m/h

1000/600 - 4R
6000
1200/800 - 4R
9000
1400/800 - 4R
12000
1600/1000 - 4R
16000
2000/1000 - 4R
20000
2000/1200 - 4R
24000
2000/1400 - 4R
30000
2000/1600 - 4R
36000
2000/2000 - 4R
45000
After recuperator
1000/600 - 4R
6000
1200/800 - 4R
9000
1400/800 - 4R
12000
1600/1000 - 4R
16000
2000/1000 - 4R
20000
2000/1200 - 4R
24000
2000/1400 - 4R
30000
2000/1600 - 4R
36000
2000/2000 - 4R
45000

For some specific cases with different inlet parameters, please, contact us.
www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

18

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-17

Efficiency of RU-REC / RU-ROT


Initial conditions (parameters):
Amounts of fresh and exhausted air are equal VS=VE [m/h]
Atmospheric pressure - 710 mmHg 940 hPa
S1 (T.) = -12 - fresh air temperature
S = 80% - fresh air humidity
E1 (T.) = +22 - fresh air temperature
S = 30% - exhausted air humidity

Model

RU-REC

Model

RU-ROT

increased noise requirment

regular mode
industrial systems
Note :
E [%] - efficiency of fresh air
For more specific cases and accurate determination of all parameters, please, contact us or use online software REC 01 on
our website.

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

19

www.tangra.bg

06.01-18
AHUH / AHU-DD

AIR HANDLING UNITS

Aerodynamic characteristics of fan BDB *** C

BU **

BDB 355

BDB 400

BDB 450

BDB 500

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

20

AIR HANDLING UNITS

AHUH / AHU-DD

Aerodynamic characteristics of fan BDB *** C

06.01-19
BU **

BDB 560

BDB 630

BDB 710

Note :
For determination of sound level pressure on frequency
bands - page 06.01-24
For determination of the necessary motor power NEL. page 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

21

www.tangra.bg

06.01-20
AHUH / AHU-DD

AIR HANDLING UNITS

Aerodynamic characteristics of fan BDB *** T

BU **

BDB 800

BDB 900

BDB 1000

Note :
For determination of sound level pressure on frequency
bands - page 06.01-24
For determination of the necessary motor power NEL. page 06.01-25
www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

22

AIR HANDLING UNITS

AHUH / AHU-DD

Aerodynamic characteristics of fan CBP

06.01-21
BU ** A

CBP - 12/9

CBP - 15/11

CBP - 18/18

Note :
For determination of sound level pressure on frequency
bands - page 06.01-24
For determination of the necessary motor power NEL. page 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

23

www.tangra.bg

06.01-22
AHUH / AHU-DD

AIR HANDLING UNITS

Aerodynamic characteristics of fan BPF

www.tangra.bg

BU ** BD

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

24

AIR HANDLING UNITS

AHUH / AHU-DD

Aerodynamic characteristics of fan BPF

06.01-23
BU ** BD

Note :
For determination of sound level pressure on frequency
bands - page 06.01-24
For determination of the necessary motor power NEL. page 06.01-25
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

25

www.tangra.bg

06.01-24
AHUH / AHU-DD

AIR HANDLING UNITS

Aerodynamic characteristics of fan BPF

BU ** BD

Acoustic characteristics
For all types of fans sound pressure level could be defined by the formula:
Lw = Lw (A) + K , where:

Lw (A) read from the graphics of each fan for specific air flow and pressure (page. 06.0118 06.01-24)
[dB] factor of correction for sound pressure level on frequency bands

[dB] factor of correction for sound pressure level

Size of section

Fan

Frequency bands [Hz]


250
500
1000
0.7
-2.9
-5.8
-15
-9
-3.5
-15
-8
-4.7
-13
-5
-4.9

BU **
BU 06A
BU 09A
BU 12A

BDB ****
CBP 12/9
CBP 15/11
CBP 18/18

63
3.9
-30
-26
-24

125
5.8
-22
-18
-17

BU 06B
BU 09B
BU 12B

BPF 400
BPF 450
BPF 500

inlet

-6

-5

-3

-4

outlet

-3

-2

-1

BU 16B
BU 20B
BU 24B

BPF 560
BPF 630
BPF 710

inlet

-5

-2

outlet

-2

BU 30B
BU 36B
BU 45B

BPF 800
BPF 900
BPF 1000

inlet
outlet

www.tangra.bg

2000
-8.8
-5.5
-5.7
-7

4000
-14.5
-10
-8
-10

8000
-20.8
-18
-16
-20

-8

-11

-15

-20

-2

-4

-8

-11

-16

-1

-6

-8

-10

-16

-20

-4

-4

-4

-7

-12

-17

-3

-1

-2

-7

-7

-10

-18

-23

-4

-4

-5

-7

-14

-19

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

26

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-25

Example:

BDB 500

Air flow
Dynamic pressure
Fan speed
Efficiency
Air velocity
Total pressure
Absorbed power
Sound pressure level

The necessary motor power is determined by the formula:

Q=14760 m/h
Pd=62 Pa
N=1900 min-1
=78%
V=10.07 m/s
Pt=1515 Pa
W=8.0 kW
Lw(A)=90.3 dB(A)

Nel = K1 W
K2

, where:

K1 safety factor to overcome the starting torque


K2 efficiency (for V-belt transmissions K2=0.9)

Absorbed power W [kW]

< 0.5

0.5 2.0

2.0 5.0

5.0 10.0

> 10.0

Safety factor K1

1.5

1.3

1.2

1.15

1.1

8.0 = 10.22 kW -> 11.0 kW



N
l = 1.15
0.9
Sound pressure level [dB] on frequency bands [Hz]

Model

Fan

Lw(A)

BU **

BDB 500

90.3 dB

63

125

250

500

1000

2000

4000

8000

3.9

5.8

0.7

-2.9

-5.8

-8.8

-14.5

-20.8

94.2

96.1

91.0

87.4

84.5

81.5

75.8

69.5

Order designation - BU 16 / 33 R / (14760 / - ) (11,0kW)


BU 16 - fan section type with fan BDB 500C, N=11.0kW / 380V
33 performance scheme (see page 06.01-10); ending section; fan position 0
R air stream direction the inspection side from left to right
14760 m/h - air flow 15500/h and total pressure 1515 Pa
(11.0kW) - absorbed power different from the nominal
We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

27

www.tangra.bg

06.01-26
AHUH / AHU-DD

AIR HANDLING UNITS

Recommendation for installation


Air handling unit is mounted over a leveled building site (foundation or construction). The site should be sized for the
specific camera.
Sections are mounted one to another with sealing rubber between them. Connection between them is made with bolt
connection.
When connect the air handling unit to duct system, flexible connections should be used to prevent transmissions of noise
and vibration.
The supplying pipes for heating and cooling units should not prevent the unit maintenance. It is advisable to connect
them through flexible pipe-connections.
The indicated directions of inlet and outlet of water sections and counter-flow between water and air must be observed.
To prevention of freezing of water coil unit is recommended at the inlet section (fresh air) to mount multiple leaf damper
equipped with spring return actuator.
Must be ensured siphon, placed before condensation line is connected to the building installation.
To make a repair or maintenance of the unit, enough space in front of it must be ensured.
The size of doors and entry of the technical room should be considered with the overall dimensions of the installed sections when mounted, repaired or maintained.

Model
AHU 06
AHU 09
AHU 12
AHU 16
AHU 20
AHU 24
AHU 30H
AHU 36H
AHU 45H





B
[mm]

B1
[mm]

B2
[mm]

B3
[mm]

1350
1600
1850
2100
2360
2360
2360
2360
2360

800
800
900
900
900
900
900
900
900

1100
1100
1150
1250
1350
1500
1650
1850
2200

1650
1900
2150
2400
2700
2700
2700
2700
2700

Minimum free area to access


to the technical room
B4 [mm]

H2 [mm]

H3 [mm]

900
900
900
1000
1100
1200
1300
1500
1800

1900
1900
1900
1900
1900
1950
1950
1950
2250

1400
1650
1900
2150
2400
2650
-

B1 maintenance and cleaning of air filters


B2 repair and replacement of fan
B3 repair and replacement of heat exchangers: COT; COX; REC or ROT
B4 minimum width of the door of technical room
H2 height when fan, water section COT/COX or recuperator REC is repaired
H3 minimum height when rotary heat exchanger ROT is repaired
www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

28

AIR HANDLING UNITS

AHUH / AHU-DD

06.01-27

Order designation
AHU-DD 16 - Air handling unit, type 16
1. BU 16 / 32 R / (15500/700)

Fan section with BDB 500C,air flow 15500 m/h and external pressure 700Pa,
position 270, direction R from left to right; Nel. = 7.5kW/380V; ending section
according scheme 32;

2. BU 16B / 62 L / (15500/550)

Fan section with BPF 560, air flow 15500 m/h and external pressure 550Pa,
direction L from right to left; Nel. = 7.5kW/380V; ending section according
scheme 62 with outlet flange 1200/700

3. TU 16 / 2R / 4R / K R

Thermal section with 2-rows heating and 4-rows cooling heat exchanger, drop
eliminator and drain tray. Direction from the supply side R from left to tight

4. InU 16 / 1 / F / 10501000 - L

Inlet section with air filter and damper, height 1050mm and length 1000mm;
direction L from right to left; multiple leaf damper with manual control PJR
1200/700+M; bag filters AFC-B (F7) (specify when ordering)

5. InU 16 / 1 / F+F / 1050x1150 - R

Inlet section with two-stage cleaning and damper; height 1050mm and length
1115mmm, direction R from left to right, damper PJR 1200/700+A with spring
return actuator; air filter AFC-V (G4), bag filter AFC-B (F7). Type of filters and
actuator are specified when ordering

6. RU-REC 16 - R / L1

Recuperative section with plate heat exchanger type REC-Al, drain tray and bypass damper PJR-BP, direction of fresh air R from left to right and direction of
exhausted air L1 - from right to left

Note :
Fans total pressure, speed, absorbed power and belt drive are selected automatically.
Actuator type is specified when ordering.
Air filters types are specified when ordering.
When ordering should be additionally specified control elements and automation, as well as other options and possibilities
(see p . 06.01-5)
The scheme is viewed from the inspection side
Implementation of the order is proceed after co-ordination of scheme and technical parameters of the unit.

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

29

www.tangra.bg

06.01-28
AHUH / AHU-DD

AIR HANDLING UNITS

Functional schemes for management, control equipment and automation

AHU- H

Air handling unit with self-dependent exhaust fan

Premises

Exhaust air

Fresh air

Air handling unit with mixing section and pre-heating exchanger water-air

Premises

Exhaust air

Fresh air

Units
BS - supply fan
B - exhaust fan

COT1 pre-heating water exchanger


COT water heating section
COX water cooling section

Control equipment and automation elements:













DA1 - fresh air damper actuator


DA2 - exhausted air damper actuator
DA3 - air damper actuator - mixing section
DPS1 - differential pressure switch - rough filter for fresh
air
DPS2 - differential pressure switch - fine filter for fresh air
DPS3 - differential pressure switch - filter for exhaust air
DPSB1 - differential pressure switch - torn belt of the
supply fan
DPSB2 - differential pressure switch - torn belt of the
exhaust fan
FP/FP1 - frost protection of water heating sections COT
or COT1
TP1 - temperature probe managing VAH1
TP - temperature probe managing VAH or VAC
HP - humidity probe
www.tangra.bg

VAH1 - 3-way valve actuator for pre-heating exchanger


VAH - 3-way valve actuator - heating
VAC - 3-way valve actuator - cooling
FIS - frequency inverter control of the supply fan
FIE - frequency inverter control of the exhaust air
PZ - positioner - unified control signal
CP11 circulation pump - heating (pre-heating exchanger COT1)
CP1 circulation pump - heating
CP2 circulation pump - cooling

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

30

AIR HANDLING UNITS

AHUH / AHU-DD

Functional schemes for management, control equipment and automation

06.01-29
AHU-DD

Air handling unit with plate heat exchanger air-air

Premises

Fresh air

Exhaust air

Air handling unit with rotary regenerative heat exchanger air-air

Premises

Exhaust air

Fresh air

Units



BS - supply fan
B - exhaust fan

REC - plate heat exchanger


ROT - rotary regenerative heat exchanger
COT water heating section
COX water cooling section

Control equipment and automation elements:











TP - temperature probe managing VAH/VAC


TP1 - temperature probe managing DA3 (by-pass
damper REC-AL - free cooling)
VAH - 3-way valve actuator - heating
VAC - 3-way valve actuator - cooling
FIS - frequency inverter control of the supply fan
FIE - frequency inverter control of the exhaust fan
FIR - frequency inverter control of rotary regenerative
heat exchanger
CP1 circulation pump - heating
CP2 circulation pump - cooling

DA1 - fresh air damper actuator


DA2 - exhausted air damper actuator
DA3 - by-pass damper actuator
DPS1 - differential pressure switch - rough filter for fresh
air
DPS2 - differential pressure switch - fine filter for fresh air
DPS3 - differential pressure switch - air filter for exhausted air
DPSB1 - differential pressure switch - torn belt of the
supply fan
DPSB2 - differential pressure switch - torn belt of the
exhaust fan
DPSBP - pressure switch managing DA3 (defrosting RECAL - winter mode
FP - frost protection of water section COT

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

31

www.tangra.bg

www.tangra.bg

We reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

32

Ruse

Shumen
Vratsa

Gorna Oriahovitsa

Varna

Gabrovo

Sofia

Kazanlak

Sliven

Burgas

Pernik
Stara Zagora
Blagoevgrad

Plovdiv

Smolian
Petrich

Haskovo

Office of Tangra
Distributor of Tangra

Office Varna

Head office
174, Europa Blvd.
1331 Sofia, Bulgaria
www.tangra.bg
Tel.: (00359 2) 925 05 99; 925 06 10
Tel.: (00359 2) 927 58 13; 972 71 80
Fax: (00359 2) 925 05 57
e-mail: office@tangra.bg

West Industrial Range


behind printing house Varna - East
Tel.: (00359 52) 611 767
e-mail: varna@tangra.bg

Office Burgas

6, Transportna Str.
Tel.: (00359 56) 861 200
e-mail: bourgas@tangra.bg