MOBITEL WELIKADA
Page 2 of
11
Equipment
CPC 100
5 kV Insulation Resistance
tester356
CMC
Digital multimeter
Brand
Omicron
Kyoritus
Omicron
Fluke
Serial No.
NJ644U
W0369405
EB892H
23030163
1.1Current transformer
1.1.1
Insulation Resistance test
Earth connection of the CT secondary star point should be removed
from the terminal block.
Insulation resistance test is done between primary-earth , primarysecondary (5 kV DC), secondary-earth & among secondary windings
(1 kV DC) for a period of 1 minute.
Table 2 : CT IR test
Test
primary- secondary
primary- earth
1S1-2S1
1S1-earth
2S1-earth
Insulation
Resistance(M)
Voltage( kV /min)
5/1
5/1
1/1
1/1
1/1
1.1.2
Winding Resistance test
A DC current of 1 A is injected to CT secondary terminals & the DC
voltage is measured using DC voltage input of CPC 100.
Initially the winding is provided with inductive energy & after
saturates the CT secondary winding, DC current is applied.
Winding resistance value is measured at room temperature &
the reference resistance is calculated at 75 C according to
following formula.
=
( ) (235 +
235 +
: IEC 60076-1
Winding Resistance at
25 C
( ) = , , (
Secondar
y current
( mA)
Rat
ed
rati
Measur
ed
ratio
Polarity
1.2Voltage Transformer
1.2.1
Insulation Resistance test
Remove earth connection from the VT primary & secondary star point.
And 5 kV DC voltage is applied between primary & earth terminals
for 1 minute , thus IR can be measured.
Similarly, Insulation resistance is measured between secondaryearth & among secondary cores. After conducting the IR test,
discharging must be done.
Table 5: VT IR test
Test
L1
L2
L3
primary Earth
primary sec
secondary
Earth
1a
a1
Voltage
( kV / min
)
5/1
5/1
1/1
1/1
L1
Core
1a 1n
Prima
ry
Volta
ge
Second
ary
Voltage
(V)
a1 n1
L2
1a 1n
a1 n1
L3
1a 1n
a1 n1
Rated
Ratio
11/3:
0.11/3
11/3:
0.11/3
11/3:
0.11/3
11/3:
0.11/3
11/3:
0.11/3
11/3:
0.11/3
Measur
ed
Ratio
Pha
se
(de
Polarit
y
( ) = , , ( )
Voltage( kV/min)
5/1
5/1
5/1
Insulation Resistance
Voltage (kV/min)
5/1
5/1
5/1
Insulation Resistance
(G)
Voltage (kV/min)
5/1
5/1
5/1
Insulation Resistance
(G)
Voltage (kV/min)
5/1
5/1
5/1
CB closed
Table 12 : Phase to Earth
Phase
L1
L2
L3
Phase
L1- L2
L2- L3
L3- L1
Insulation Resistance
(G)
Voltage (kV/min)
5/1
5/1
5/1
0.14
(IEC 60255-3)
(0.02
1)
L2
A)
L3
Trip
Time
Expect
ed
Deviati
on
In Remar
The insulation resistance test is measured between HV terminalsearth, HV LV terminals by applying 5 kV DC for 1 minute.
Also IR test is conducted between LV earth by applying 1 kV for 1 minute.
Table 15: Power transformer IR test
Test
Pri. Earth
Sec. Earth
Pri. Sec.
Insulation Resistance/
M
Test Voltage
(kV/min)
5/1
1/1
5/1
Phase 1V-1U
Phase 1W-1V
1
2
3
4
5
Phase 2W-N
2.3
Turns ratio test
A sinusoidal voltage of 500 V is applied to each HV terminal from 2 kV AC
output of the CPC 100.
The secondary induced voltage is measured from V1 AC input.
Tap
1
2
3
4
5
Nom.Rati
o
V Prim
Phase 1U
I Prim
I Phase
V Sec
V Phase
TTR
1U, 2u
2v
2w
1W
2.5
1V
Page 11 of
11
Ratio
Single phase 200 V AC is applied using CMC 356 between HV terminals & the
other HV
terminal voltages are measured.
Table 20: Magnetic Balance test
1U-1V
Applied/
200
Measured
X1
voltage
X2
1U-1W
X0
200
Y2
1V-1W
Y0
Y1
200
For the center limb, induced voltage is higher than the limb situated at the corner.
3.
Power Cable
3.1 Insulation Resistance test
The connections from either end of the power cable is removed.
A DC voltage of 5 kV is applied from the Insulation tester for a period of 1
minute, between each phase & copper screen.
Test voltage
5/1
( kV/min)
Test voltage (
kV/min)5/1
L2
L3
L1-L3
L2-L3
5/1
5/1
5/1
5/1