Beruflich Dokumente
Kultur Dokumente
EXPERIMENT NO. 3
Air Temperature Process Control (AT 922)
OBJECTIVES
1. To identify the important components of the air temperature control system and to
1. Walk around the experimental equipment, IDENTIFY and MARK the following major
components of the system in the P&I Diagram provided at the end the lab manual.
AR90
FS90
Flow switch (cut-off the heater power when very low air is detected)
KEYWORDS
TCY90
Air temperature system, PID controller, Dead time, FOPTD transfer function model
TE91
1.0 INTRODUCTION
TIT92
This model uses air to simulate a gas or vapor phase temperature process. The
TR91
Recorder
TIC90
thyristor to adjust the heat flow to the heater. The air flow rate is measured using a
TIC91
rotameter. A selective control technique is employed here that automatically select only a
TIC92
less heat demanding output to manipulate only final control element (the thyristor/heater).
FI90
VT
Process vent
HV90
Heater by-pass
1. The following steps constitute the start-up procedure. Go through these steps before
2. Switch the "PANEL, SCADA/DDC" selector switch at the front of the cubicle to
incoming process air from an external air supply system. The process air is connected to a
cubicle. All the panel instruments will lit up. (Make sure the heater is switched OFF at
air pressure regulator (AR90) and flows into the heater and then to the process vent, VT or
to another air process control training system. By varying the air flow rate at the discharge
manual valve downstream of the rotameter, FI90, the air flow load changes through the
heater can be implemented. The purpose of the the PID control is to maintain the air
temperature (TE91/TIT91) at the heater exit, at the operator setpoint without burning out
the heater.
this point)
3. If any annunciator gets activated, press the ACKNOWLEDGE button to silence the
buzzer.
4. Shut the manual valve MV90A and set air supply regulator AR90 to the pressure
indicated at the air regulator (45 psig).
5. Make sure the heater by-pass valve HV90 and manual valve MV90B are shut. Open the
vent valve VT fully to discharge air to the atmosphere.
Page 1
FAL90
9. The slope of the steepest tangent gives the Response Rate (RR).
is
activated
and
should
be
10. The process gain, Kp is equal to the maximum change in the air temperature ( PV)
ii) The pressure gauge PG90 reads as atmospheric pressure. If it reads more,
then check and open the vent valve VT.
transfer function.
iv) Check the temperature at recorder TR91 is not rising because the heater is
still OFF.
7. Manually open fully the inlet valve MV90A so that the air flow rate at flow meter FI90
reads about 45 Nm3/hr. (Do not alter the air pressure that was previously set at air
Y ( s ) K.e s
=
X (s) s + 1
K = process gain
8. Check the pressure gauge PG90 should reads slightly above atmospheric pressure.
= time constant
9. Now, press the RCD button on the recorder TR91 to start recording the temperature
response.
2. The process air supply and flow rate should remain as previously set in Section 3.3.
The following procedures are conducted for determining the process transfer function
3. Set a suitable setpoint, SV (i.e. range from 60C to 120C) at the temperature PID
parameters.
controller, TIC91, say 10C higher than the current setpoint SV. (TIC91 is still in
1. Make sure the air flow rate at variable area flow meter FI90 is 45 Nm3/hr. If it is not
read as 45
Nm3/hr,
2. Wait for the temperature response to be almost stable. (Red pen - TE91/TIT91 and
Green pen - TE92/TIT92 are almost steady)
3. Note the average air flow rate at the variable area flow meter FI90.
6. Transfer TIC91 to Auto (A) mode and make sure the heater is ON.
5. Switch ON the heater and mark on the recorder chart paper the instant the heater is
7. Observe patiently the temperature response of both the heater surface temperature
switched ON.
(TE90/TIC90, Green pen) and the heated air temperature (TE91/TIC91), Red pen).
Wait until the temperature response is steady at its setpoint value, SV.
7. Stop the recorder TR91 by pressing RCD button and take out the chart paper and
DO NOT FORGET TO MARK THE PID VALUES AND THE SET-POINT ON THE
Deadtime =
Page 2
Re cordchartspeed ( 500 mm hr )
1hr
8. Note that the heated air temperature (TE91/TIC91), Red pen) overshoots the setpoint,
SV even when the heater surface temperature (TE90/TIC90, Green pen) has started
decreasing.
9. Repeat the experiment with the following disturbances (using first (I) PID trial values):
i) Load disturbance
Switch the controller TIC91 to Manual (M) mode. Increase the control output,
MV at about 10% to 20%. Then, quickly switch the controller TIC91 to Auto
Switch the controller to Manual (M) mode. Step increase the temperature
current setpoint, SV (do not exceed 120C). Then, quickly switch the controller
10. Repeat Step (9) for the following PID trial values:
Page 3
Page 4