Measuring Transducers

Transducing electrical quantities Iskra MIS d.d.


Measuring Transducers

Features
AC, DC POWER SYSTEM MEASUREMENT
MICROPROCESSOR CONTROL
HOUSING FOR DIN RAIL MOUNTING IN
COMPLIANCE WITH EN 50022
PROGRAMMABLE VOLTAGE INPUT RANGE
PROGRAMMABLE CURRENT INPUT RANGE
PROGRAMMABLE ANALOGUE OUTPUT
SERIAL COMMUNICATION RS232/RS485 (OPTION)
UP TO THREE ELECTRICALLY ISOLATED ANALOGUE OUTPUTS
UNIVERSAL AUXILIARY POWER SUPPLY (OPTION)
ACCURACY CLASS 0.5 (FREQUENCY TRANSDUCER 0.2)
CURRENT INPUTS ELECTRICALLY ISOLATED FROM THE SYSTEM
OUTPUTS, SERIAL COMMUNICATION, AUXILIARY POWER SUPPLY, CURRENT
AND VOLTAGE INPUTS GALVANICALLY SEPARATED (SOME MODELS)

MISET Software / Features


Description
Digital technology, on which measuring transducers
are built, enables them, with corresponding software,
to adapt to different input and output quantities. Input
quantities, for energy measuring transducers, of phase
voltage can be set within the range from 50 to 500 V
and currents from 0.2 to 5 A. Values of analogue out puts can also be set within the range from 1 to 20 mA
for current and from 1 to 10 V for voltage. Input-output
characteristics can be created with five breaking
spots for unipolar and bipolar output signals. The accu racy class of measuring transducers is 0.5, except for
frequency, where accuracy class is 0.2.

- Configuring and setting software


- Full instrument setup capability
- Displays data in real time
- Windows compatible
- User friendly

The above stated versions of measuring transducers


can be provided with the RS232 or RS485 communica tion for connection to the network. The MODBUS com munication protocol is used with bit rate from 1,200 to
115,200 bit/s. A measuring transducer with three elec trically isolated bipolar analogue outputs (MI400) is
the most capable version. Outputs can be software
adapted to any measured quantity (voltage, current,
power, power factor, frequency) for a phase or for a
complete system value. The transducer is supplied
with a universal supply module within the range from
24 to 300 V DC or 40 to 276 V AC voltage.
Beside AC measuring transducers we produce also
DC programmable measuring transducers for conver sion of DC current and voltage, resistance and tem perature into appropirate DC current or voltage sig nals. Their analogue output signal is proportional to
the measured value and it is appropriate for regulation
of analogue and digital devices. Input quantities for
DC measuring transducers can vary from 50 mV to 300
V for voltage and from 1 mA to 1 A (up to 7.5 A as special version) for current. Output values are similar to
output values of AC measuring transducers. Accuracy
class for both (current and voltage) DC measuring
transducer is 0.5.

MISET Software / System requirements


MISET Software / Application
MISET software is created for configuring and setting
of all the instruments with serial communication port
(RS232 or RS485) connected in your power network.
Devices must be connected to the computer via
RS232 communication port (one device, or up to 32
devices connected in network via RS485/RS232 com munication converter).
With MISET software you can set any parameter of
your device, such as input values and transformer
ratios, type and value of output and its characteristic,
address, communication speed. It also displays measured values in numerical format and in table form.
PC software MISET is user friendly and involves help
function to simplify the work.

- Windows 95, 98, Millennium, 2000, XP, NT4.0


- 50 MB available disk space
- VGA monitor
- Min. 32 MB of RAM
- CD drive
- RS232 communication port

Measuring quantities
- AC voltage and current
- RMS AC voltage and current
- Active and reactive power
- Frequency
- Power factor
- Resistance
- DC voltage and current
- Temperature
- TAP position

Differences between measuring transducers


Our measuring transducers can be divided into two groups: MI400 multifunctional measuring transducer and all
the others.
MI400 is the most powerful multifunctional measuring transducer. It supervises simultaneously any 3 values of an
electrical system. It has the capability of measuring more than 50 different electrical quantities such as: TRMS
values of voltage, current, kW, kvar, kVA, PF, Hz, MD, THD etc in one instrument. All values are available via
communication port for monitoring on the PC. It can have up to three configurable analogue outputs, which are
programmable. Programmable are also CT and VT ratios.
All the other measuring transducers compose group MI4xx (4xx greater than 400). Each measuring transducer in
this group is tailored for measuring one electrical quantity. In the table below you can see which functionality is
covered by which instrument and instrument's input and output values.
Input quantity

TYPE

Programmable
transducer

Active power
transducer

Reactive power
transducer

Power factor
measuring

MI400

MI413

MI414

MI421

Class
Power supply
Measuring principle

0.5

1
With auxiliary power supply
Microprocessor control

INPUT
Measuring range

Input voltage
Nominal voltage
Input current
Nominal current
Nominal frequency
Consumption/Input
resistance
Overload capability
Power supply

-Pn...0...Pn
-Qn...0...Qn
-Sn...0...Sn
Cap. 0...1...0 Ind.
-180...0...+180
45...65 Hz
0...1.2 Un
0...1.2 In

-Pn...0...Pn
0...Pn

Voltage circuit: U2/3 M

-Qn...0...Qn
0...Qn

Un 0...50 - 500 V
Programmable range
In 0...0.5 - 5 A
Programmable range
50/60 Hz

Cap. 0...1...0 Ind.


-180...0...+180

Current circuit: 2 x 0.01

1.5 Un; 2 In
57, 100, 110, 230, 400, 500 V AC, 20%, 45...65 Hz 3 VA
Universal auxiliary power supply 24...300 V DC 40...276 V AC

OUTPUT
Range selection
Numbers of analogue
outputs
Current nominal values

Programmable range over communication, at placing order


0, 1, 2 and 3

1
-1 mA...0 (0.2)...1 mA
-5 mA...0 (1)...5 mA
-10 mA...0 (2)...10 mA
-20 mA...0 (4)...20 mA
-1 V...0... 1 V, -10 V... 0...10 V

Voltage nom. values


Harmonic analysis
Yes (Optional)
Maximum Demand
Yes
Communication
RS232 or RS485
RS232, RS485 (optional)
Residual ripple
< 1 % p.p.
on nominal current
Response time
< 300 ms
, 10 mA 1.5 k
,
Burden max. I output 5 mA 3 k
min. U output 20 mA 750 , 10 V 500
Ref. measuring range
0+50C
Working temperature
-10+55C
Storage temperature
-40...+70C
Climatic class
3 according to EN 60688
General technical data Protection system: IP 50, terminals IP20, according to EN 60529, 1989
Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)
Test voltage: 3.7 kV rms according to EN 61010-1: 1990
Characteristic curves
A, B, C, D
Dimensions
A = 100 mm, B = 75 mm, C = 104.5 mm

Input quantity

3 x AC Voltage

TYPE

MI436

Class
Power supply
Measuring principle

3 x AC Current

Frequency

MI438

MI420

0.5
With auxiliary power supply
Microprocessor control

0.2

0..6 A, 1 A, 5 A

40 to 70 Hz
3...500 V

INPUT
Measuring range
Input voltage
Nominal voltage

0..50 V to 0..500 V
500 V programmable,
57.74, 63.5, 100, 110,
230, 250, 400, 500 V
fixed configuration

Input current
Nominal current

6 A programmable
1 A, 5 A fixed
configuration

Nominal frequency
Consumption / Input
resistance
Overload capability
Power supply

45...55 Hz
48...52 Hz
45...65 Hz
55...65 Hz
< 0.5 VA

50/60 Hz

U2 / 3 M

I2 0.01

1.2 Un
2 In
Universal auxiliary power supply
24...300 V DC, 40...276 V AC, 40...70 Hz, < 3 VA

1.2 Un
57, 100, 110, 230, 400,
500 V AC, 20%,
Universal auxiliary
power supply 24...300 V
DC 40...276 V AC

OUTPUT
Range selection
Number of analogue
outputs
Current nominal values

Programmable range over communication, at placing order


3
0 (0.2)...1 mA
0 (1)...5 mA
10 mA fixed configuration
0 (4)...20 mA
4...20 mA fixed configuration
0...1 V to 0...10 V

Voltage nom. values


Harmonic analysis
Maximum Demand
Communication
Residual ripple on
nominal current
Response time
Burden max. Ioutput
min. Uoutput
Ref. measuring range
Working temperature
Storage temperature
Climatic class
General technical data

Characteristic curves
Dimensions

Yes (Optional)
Yes (thermal function)
RS232, RS485 (optional)
< 1% p.p.

5 mA, 20 mA
programmable
5 mA, 10 mA, 20 mA,
4...20 mA fixed
10 V programmable,
fixed
-

< 300 ms
, 10 mA 1.5 k
, 20 mA 750 , 10 V 500
5 mA 3 k
0+50C
-10+55C
-10+55C
-40 to +70 C
-40...+70C
3 according to EN 60688
3 according to EN 60688
Protection system: IP 50, terminals IP20, according to EN 60529, 1989
Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)
Test voltage: 3.7 kV rms according to EN 61010-1: 1990
A, B
A, B, D
A = 100 mm, B = 75 mm,
A = 44.8 mm, B = 75 mm,
C = 104.5 mm
C = 104.5 mm

Input quantity

TYPE
Class
Power supply
Measuring principle

AC - Voltage

AC - Current

RMS
AC - Voltage

RMS
AC - Current

MI406

MI408

MI416

MI418

0.5
Without auxiliary power supply
Rectifier method

With auxiliary power supply


Microprocessor control

INPUT
Measuring range
Input voltage

0.2...Un
Un 0...20 to 0...500 V

Nominal voltage

57.74, 63.5, 100,


110, 250, 500 V

0...In

Input current

In 0...1 A to 0...7.5 A

Nominal current
Nominal frequency
Consumption / Input
resistance
Overload capability
Power supply

0...1.2 Un
Un 0...50 V to 0...500 V
programmable range
57.74, 63.5, 100,
110, 230, 250, 400, 500 V

0...1.2 In

In 0..6 A
programmable range
In 1 A, 5 A fixed
configuration

1 A, 5 A
50/60 Hz
< 2 VA

< 2 VA

1.2 Un

2 In

< 0.5 VA

< 0.5 VA

1.2 Un
2 In
57, 100, 110, 230, 400, 500 V AC, 20 %,
45...65 Hz 3 VA
Universal auxiliary power supply
24...300 V DC, 40...276 V AC

Power supply from measuring circuit

OUTPUT
Range selection
Number of analogue outputs
Current nominal values

Voltage nom. values


Harmonic analysis
Maximum Demand
Communication
Residual ripple on
nominal current
Response time
Burden max. Ioutput
min. Uoutput
Ref. measuring range
Working temperature
Storage temperature
Climatic class
General technical data

Characteristic curves
Dimensions

At placing order

Programmable range over


communication, at placing order
1

0...5 mA
0...10 mA
0...20 mA

0 (0.2)...1 mA
0 (1)...5 mA
0 (2)...10 mA
0 (4)...20 mA
0...1 V, 0...10 V
Yes (Optional)

RS232, RS485 (optional)


< 1% p.p.

, 10 mA 1.5 k
,
5 mA 3 k
20 mA 750

< 300 ms

, 10 mA 1.5 k
,
5 mA 3 k
20 mA 750 , 10 V 500

0+50C
-10+55C
-40...+70C
3 according to EN 60688
Protection system: IP 50, terminals IP20, according to EN 60529, 1989
Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)
Test voltage: 3.7 kV rms according to EN 61010-1: 1990
A
A, B, D
A = 44.8 mm, B = 75 mm, C = 104.5 mm

Input quantity

TYPE

Temperature
Pt 100

Resistance

MI450

MI452

Class
Power supply
Measuring principle

Potenciometer &
TAP position

MI454

0.5
With auxiliary power supply
Microprocessor control

INPUT
Measuring range

Input value

Nominal value

Nominal frequency
Consumption / Input
resistance
Power supply

0..20 to 0..10 k
Un < 2.2 V

0...Rn
R0Rn...R0

to 0..500k

0..100
Un < 2.2 V

-200C+850C for Pt
-60C+250C for Ni
for
20 to 10 k
polinom programmable
0 to 100, 0 to 250,
-100 to 800C for Pt
0 to 100, 0 to 180,
-50 to 150C for Ni
fixed configuration

Rn 0..10 - 50 k

0..100 - 500 k
programmable

Rn 100 to 500 k
programmable

Rn 100, 1 k, 2 k, 5 k,
fixed
10 k, 20 k, 50 k
Rn 5 k, 10 k, 50 k, 100 k,
fixed
200 k, 500 k

Rn 100, 1 k, 2 k, 5 k, 10 k
20 k, 50 k, 100 k, 200 k,
0-linear
500 k
Rn 300, 1 k, 2 k, 5 k, 10 k,
20 k, 50 k, 100 k, 200 k,
10 steps
500 k
(both fixed configuartion)

< 0.5 VA
57, 100, 110, 230, 400, 500 V AC, 20 %,
Universal auxiliary power supply: 24...300 V DC,
40... 276 V AC

OUTPUT
Range selection
Number of analogue
outputs
Current nominal
values
Voltage nom. values
Harmonic analysis
Maximum Demand
Communication
Residual ripple on
nominal current
Response time
Burden max. Ioutput
min. Uoutput
Ref. measuring range
Working temperature
Storage temperature
Climatic class
General technical
data
Characteristic curves
Dimensions

Programmable range over communication, at placing order


1
-1...0 (0.2)...1 mA
-5...0 (1)...5 mA
-20...0 (4)...20 mA
-1...0...1 V, -10...0...10 V

0 (0.2)...1 mA
0 (1)...5 mA
0 (4)...20 mA
0...1 V, 0...10 V
RS232, RS485 (optional)
< 1 % p.p.
Programmable 0.5 s to 60 s

, 10 mA 1.5 k
, 20 mA 750 , 10 V 500
5 mA 3 k
0+50C
-10+55C
-40...+70C
2 according to EN 60688
Protection system: IP 50, terminals IP20, according to EN 60529, 1989
Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)
Test voltage: 3.7 kV rms according to EN 61010-1: 1990
A, B, C, D
A
A = 44.8 mm, B = 75 mm, C = 104.5 mm

Input quantity

DC Voltage

DC Current

RS232 to
RS485

TYPE

MI456

MI458

MI485

Class
Power supply
Measuring principle

0.5
With auxiliary power supply
Microprocessor control

INPUT
Measuring range
Input value

Nominal input

Nominal frequency
Consumption /
Input resistance
Overload capability
Power supply

0...Un
-Un0...Un
Un 0...50 mV 1 V
0..1 50 V
0..50 300 V
programmable
Un 50, 100, 500 mV,
1 V fixed
1.5, 2, 2.5, 4, 5, 6,
10, 15, 20, 25, 40,
50 V fixed
60, 100, 150,
200, 250, 400 V fixed

0...In
-In0...In
In 0...1 10 mA
0...10 100 mA
programmable

RS485
Bit rate to115200 bit/s
-

In 1, 1.5, 2, 2.5, 4, 5, 6,
10 mA fixed
In 15, 20, 25, 40, 50,
60, 100 mA fixed

DC
< 0.5 VA

< 0.5 VA

1.2 Un
2 In
57, 100, 110, 230, 400, 500 V AC, 20 %, 45...65 Hz 3 VA
Universal auxiliary power supply 24...300 V DC 40...276 V AC

OUTPUT
Range selection
Number of analogue
outputs
Current nominal
values
Voltage nom. values
Harmonic analysis
Maximum Demand
Communication

Programmable range over communication


at placing order
1
-1 mA...0 (0.2)...1 mA
-5 mA...0 (1)...5 mA
-20 mA...0 (4)...20 mA
-1V...0...1V, -10V...0...10V

RS232
Electrically isolated
Terminals or SUB D
connector
Indication
communication with
LED Diode

RS232, RS485 (optional)

Residual ripple on
< 1% p.p.
nominal current
Response time
Programmable 0.5s to 3s
Burden max. Ioutput
, 10 mA 1.5 k
, 20 mA 750 , 10 V 500
min. Uoutput
5 mA 3 k
Ref. measuring range
0+50C
Working temperature
-10+55C
Storage temperature
-40...+70C
Climatic class
3 according to EN 60688
General technical data Protection system: IP50, terminals IP20, according to EN 60529, 1989
Protection class: II, III cat. (300 Vrms), II cat. (500 Vrms)
Test voltage: 3.7 kV rms according to EN 61010-1: 1990
Characteristic curves
A, B, C, D
Dimensions
A = 44.8 mm, B = 75 mm, C = 104.5 mm
Note: Transducers according to EN 606881, EN 610101

Characteristic curves
a) linear characteristic

b) up to 5 break points

c) zoom absolute value

d) zoom

Case dimensions

Ordering info
Ordering informations for each transducer are available in technical leaflets.

Version 2, September 2004