Air System Sizing Summary for Electrical Substartion Elec.

Eq
Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

Air System Information


Air System Name ...... Electrical Substartion Elec. Eq
Equipment Class ........................................ PKG ROOF
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ................................................................. 538,2 m
Location .................................................... Muscat, Oman

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone L/s Sizing .................... Sum of space airflow rates


Space L/s Sizing ................ Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load .......................................................... 72,5
Sensible coil load ................................................... 68,4
Coil L/s at Jul 1600 ................................................ 5653
Max block L/s ........................................................ 5653
Sum of peak zone L/s ........................................... 5653
Sensible heat ratio ............................................... 0,943
m/kW ....................................................................... 7,4
W/m ..................................................................... 134,7
Water flow @ 5,6 K rise ......................................... N/A

kW
kW
L/s
L/s
L/s

Load occurs at ..................................................... Jul 1600


OA DB / WB ...................................................... 49,8 / 30,0
Entering DB / WB ............................................. 25,5 / 18,5
Leaving DB / WB .............................................. 15,4 / 14,8
Coil ADP ..................................................................... 14,3
Bypass Factor .......................................................... 0,100
Resulting RH ................................................................. 52
Design supply temp. ................................................... 14,4
Zone T-stat Check .................................................... 0 of 1
Max zone temperature deviation .................................. 0,0

C
C
C
C
%
C
OK
K

Central Heating Coil Sizing Data


Max coil load ............................................................ 7,0 kW
Coil L/s at Des Htg ................................................ 5653 L/s
Max coil L/s ........................................................... 5653 L/s
Water flow @ 11,1 K drop ...................................... N/A

Load occurs at ..................................................... Des Htg


W/m ........................................................................... 13,1
Ent. DB / Lvg DB .............................................. 20,8 / 21,9 C

Supply Fan Sizing Data


Actual max L/s ....................................................... 5653 L/s
Standard L/s .......................................................... 5643 L/s
Actual max L/(s-m) .............................................. 10,50 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0,00 BHP


Fan motor kW ............................................................. 0,00 kW
Fan static ......................................................................... 0 Pa
L/s/person ................................................................... 0,00 L/s/person

Design airflow L/s .................................................... 161 L/s


L/(s-m) ................................................................... 0,30 L/(s-m)

Hourly Analysis Program v4.90

Page 1 of 19

Zone Sizing Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

Air System Information


Air System Name ...... Electrical Substartion Elec. Eq
Equipment Class ........................................ PKG ROOF
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ................................................................. 538,2 m
Location .................................................... Muscat, Oman

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone L/s Sizing .................... Sum of space airflow rates


Space L/s Sizing ................ Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
64,3

Design
Minimum
Airflow
Airflow
(L/s)
(L/s)
5653
5653

Maximum
Heating
Time of
Load
Peak Load
(kW)
Jul 2100
4,2

Zone
Floor
Area
(m)
538,2

Zone
L/(s-m)
10,50

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name
Zone 1
6,6 kV SWITCHGEAR ROOM
HV SWITCHGEAR ROOM
LV SWITCHGEAR ROOM

Hourly Analysis Program v4.90

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1
1

9,9
4,6
49,8

Jul 2200
Aug 1800
Jul 2100

872
404
4377

0,8
0,6
2,8

137,9
68,5
331,8

6,32
5,90
13,19

Page 2 of 19

Ventilation Sizing Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 161 L/s

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
6,6 kV SWITCHGEAR ROOM
HV SWITCHGEAR ROOM
LV SWITCHGEAR ROOM
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.90

Mult.

Floor
Area
(m)

Maximum
Occupants

1
1
1

137,9
68,5
331,8

0,0
0,0
0,0

Maximum
Supply Air
(L/s)

Required
Outdoor Air
(L/s/person)

Required
Outdoor Air
(L/(s-m))

871,7
404,2
4377,3
5653,2

0,00
0,00
0,00

0,30
0,30
0,30

Required
Required
Outdoor Air Outdoor Air
(L/s) (% of supply)
0,0
0,0
0,0

0,0
0,0
0,0

Uncorrected
Outdoor Air
(L/s)
41,4
20,6
99,5
161,5

Page 3 of 19

Air System Design Load Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Central Heating Coil
>> Total Conditioning
Key:

Hourly Analysis Program v4.90

11/15/2015
05:43

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 49,8 C / 30,0 C
HEATING OA DB / WB 10,0 C / 5,8 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
270 m
3361
270 m
1348
538 m
5425
538 m
2499
0 m
0
0 m
0
0 m
0
0 m
0
19 m
803
19 m
363
538 m
0
538 m
0
0 m
0
0 m
0
0 m
0
0 m
0
5834 W
5834
0
0
0W
0
0
0
48715 W
48713
0
0
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
64135
0
4210
63536
0
4859
0%
0
0
0
0%
0
0
0
0%
0
0
0
5653 L/s
0
5653 L/s
0
161 L/s
4861
4112
161 L/s
2172
5653 L/s
0
5653 L/s
0
0
0
0%
0
0%
0
68397
4112
7031
68397
4123
0
0
7031
68397
4123
7031
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Latent
(W)
0
0
0
0
0
0
1
1
0
0

Page 4 of 19

Zone Design Load Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.90

11/15/2015
05:43

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 2100
HEATING DATA AT DES HTG
COOLING OA DB / WB 45,2 C / 29,1 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
270 m
3376
270 m
1348
538 m
5683
538 m
2499
0 m
0
0 m
0
0 m
0
0 m
0
19 m
708
19 m
363
538 m
0
538 m
0
0 m
0
0 m
0
0 m
0
0 m
0
5834 W
5834
0
0
0W
0
0
0
48715 W
48713
0
0
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
64314
0
4210

Latent
(W)
0
0
0
0
0

Page 5 of 19

Space Design Load Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

TABLE 1.1.A.

COMPONENT LOADS FOR SPACE '' 6,6 kV SWITCHGEAR ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 2200
HEATING DATA AT DES HTG
COOLING OA DB / WB 44,4 C / 28,9 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
SPACE LOADS
Details
(W)
(W)
Details
(W)
Window & Skylight Solar Loads
0 m
0
0 m
Wall Transmission
30 m
417
30 m
149
Roof Transmission
138 m
1457
138 m
640
Window Transmission
0 m
0
0 m
0
Skylight Transmission
0 m
0
0 m
0
Door Loads
0 m
0
0 m
0
Floor Transmission
138 m
0
138 m
0
Partitions
0 m
0
0 m
0
Ceiling
0 m
0
0 m
0
Overhead Lighting
1649 W
1649
0
0
Task Lighting
0W
0
0
0
Electric Equipment
6399 W
6398
0
0
People
0
0
0
0
0
Infiltration
0
0
0
Miscellaneous
0
0
0
Safety Factor
0% / 0%
0
0
0%
0
>> Total Zone Loads
9921
0
790

TABLE 1.1.B.

E EXPOSURE
WALL
H EXPOSURE
ROOF

Hourly Analysis Program v4.90

ENVELOPE LOADS FOR SPACE '' 6,6 kV SWITCHGEAR ROOM '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

Latent
(W)
0
0
0
0
0

HEATING
TRANS
(W)

30

0,450

417

149

138

0,418

1457

640

Page 6 of 19

Space Design Load Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

TABLE 1.2.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.2.B.

S EXPOSURE
WALL
DOOR
H EXPOSURE
ROOF

Hourly Analysis Program v4.90

11/15/2015
05:43

COMPONENT LOADS FOR SPACE '' HV SWITCHGEAR ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 48,3 C / 29,7 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
31 m
370
31 m
156
69 m
705
69 m
318
0 m
0
0 m
0
0 m
0
0 m
0
6 m
258
6 m
121
69 m
0
69 m
0
0 m
0
0 m
0
0 m
0
0 m
0
767 W
767
0
0
0W
0
0
0
2500 W
2500
0
0
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
4600
0
596

ENVELOPE LOADS FOR SPACE '' HV SWITCHGEAR ROOM '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

Latent
(W)
0
0
0
0
0

HEATING
TRANS
(W)

31
6

0,450
1,703

370
258

156
121

69

0,418

705

318

Page 7 of 19

Space Design Load Summary for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

TABLE 1.3.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.3.B.

N EXPOSURE
WALL
E EXPOSURE
WALL
W EXPOSURE
WALL
DOOR
H EXPOSURE
ROOF

Hourly Analysis Program v4.90

11/15/2015
05:43

COMPONENT LOADS FOR SPACE '' LV SWITCHGEAR ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 2100
HEATING DATA AT DES HTG
COOLING OA DB / WB 45,2 C / 29,1 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
208 m
2611
208 m
1042
332 m
3504
332 m
1541
0 m
0
0 m
0
0 m
0
0 m
0
13 m
472
13 m
242
332 m
0
332 m
0
0 m
0
0 m
0
0 m
0
0 m
0
3418 W
3417
0
0
0W
0
0
0
39816 W
39814
0
0
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
49818
0
2825

ENVELOPE LOADS FOR SPACE '' LV SWITCHGEAR ROOM '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

Latent
(W)
0
0
0
0
0

HEATING
TRANS
(W)

130

0,450

1541

651

30

0,450

412

148

49
13

0,450
1,703

658
472

242
242

332

0,418

3504

1541

Page 8 of 19

System Psychrometrics for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

July DESIGN COOLING DAY, 1600


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
49,8
25,5
15,4
15,4
15,4
15,4
24,8
24,8

Specific
Humidity
(kg/kg)
0,01888
0,01048
0,01023
0,01023
0,01023
0,01023
0,01023
0,01023

Airflow
(L/s)
161
5653
5653
5653
5653
5653
5653
5653

CO2 Level
(ppm)
400
736
736
736
736
736
746
746

Sensible
Heat
(W)
4861
68397
0
0
63536
0

Latent
Heat
(W)
4112
4123
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2942,3 W/(L/s)
Site Altitude = 14,9 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.90

Zone
Sensible
Load
(W)
64135

T-stat
Mode
Cooling

Zone
Cond
(W)
63536

Zone
Temp
(C)
24,8

Zone
Airflow
(L/s)
5653

CO2
Level
(ppm)
746

Terminal
Heating
Coil
(W)
0

Zone
Heating
Unit
(W)
0

Page 9 of 19

System Psychrometrics for Electrical Substartion Elec. Eq


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Central Heating Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
10,0
20,8
20,8
21,9
21,9
21,9
21,2
21,2

Specific
Humidity
(kg/kg)
0,00401
0,00401
0,00401
0,00401
0,00401
0,00401
0,00401
0,00401

Airflow
(L/s)
161
5653
5653
5653
5653
5653
5653
5653

CO2 Level
(ppm)
400
736
736
736
736
736
746
746

Sensible
Heat
(W)
-2172
0
7031
0
-4859
0

Latent
Heat
(W)
-1
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2942,3 W/(L/s)
Site Altitude = 14,9 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.90

Zone
Sensible
Load
(W)
-4210

T-stat
Mode
Deadband

Zone
Cond
(W)
-4859

Zone
Temp
(C)
21,2

Zone
Airflow
(L/s)
5653

CO2
Level
(ppm)
746

Terminal
Heating
Coil
(W)
0

Zone
Heating
Unit
(W)
0

Page 10 of 19

Air System Sizing Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

Air System Information


Air System Name ........... Electrical Substation Office
Equipment Class ......................................... SPLT AHU
Air System Type ...................................................... VAV

Number of zones ............................................................. 1


Floor Area ................................................................... 46,3 m
Location .................................................... Muscat, Oman

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone L/s Sizing ........................ Peak zone sensible load


Space L/s Sizing ................ Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load ............................................................ 5,6
Sensible coil load ..................................................... 4,8
Coil L/s at Aug 1700 ................................................ 310
Max block L/s at Aug 1800 ...................................... 318
Sum of peak zone L/s ............................................. 318
Sensible heat ratio ............................................... 0,862
m/kW ....................................................................... 8,3
W/m ..................................................................... 120,3
Water flow @ 5,6 K rise ......................................... N/A

kW
kW
L/s
L/s
L/s

Load occurs at ................................................... Aug 1700


OA DB / WB ...................................................... 49,2 / 29,9
Entering DB / WB ............................................. 26,0 / 17,9
Leaving DB / WB .............................................. 13,1 / 12,4
Coil ADP ..................................................................... 11,7
Bypass Factor .......................................................... 0,100
Resulting RH ................................................................. 46
Design supply temp. ................................................... 12,8
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0,0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s at Aug 1800 ..................................... 318 L/s
Standard L/s ............................................................ 317 L/s
Actual max L/(s-m) ................................................ 6,87 L/(s-m)

Fan motor BHP ........................................................... 0,00 BHP


Fan motor kW ............................................................. 0,00 kW
Fan static ......................................................................... 0 Pa

Return Fan Sizing Data


Actual max L/s at Aug 1800 ..................................... 318 L/s
Standard L/s ............................................................ 317 L/s
Actual max L/(s-m) ................................................ 6,87 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0,00 BHP


Fan motor kW ............................................................. 0,00 kW
Fan static ......................................................................... 0 Pa
L/s/person ................................................................... 4,26 L/s/person

Design airflow L/s ...................................................... 17 L/s


L/(s-m) ................................................................... 0,37 L/(s-m)

Hourly Analysis Program v4.90

Page 11 of 19

Zone Sizing Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

Air System Information


Air System Name ........... Electrical Substation Office
Equipment Class ......................................... SPLT AHU
Air System Type ...................................................... VAV

Number of zones ............................................................. 1


Floor Area ................................................................... 46,3 m
Location .................................................... Muscat, Oman

Sizing Calculation Information


Calculation Months ..................................... Jan to Dec
Sizing Data .................................................. Calculated

Zone L/s Sizing ........................ Peak zone sensible load


Space L/s Sizing ................ Individual peak space loads

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
4,3

Design
Minimum
Airflow
Airflow
(L/s)
(L/s)
318
17

Maximum
Heating
Time of
Load
Peak Load
(kW)
Aug 1800
0,6

Zone
Floor
Area
(m)
46,3

Zone
L/(s-m)
6,87

Zone Terminal Sizing Data

Zone Name
Zone 1

Reheat
Coil
Load
(kW)
0,8

Reheat
Coil
Water
L/s
@ 11,1 K
-

Zone
Htg
Coil
Load
(kW)
0,0

Zone
Htg
Water
L/s
@ 11,1 K
-

Mixing
Box Fan
Airflow
(L/s)
0

Space Loads and Airflows


Zone Name /
Space Name
Zone 1
OFFICE
PASSAGE

Hourly Analysis Program v4.90

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

1
1

2,9
1,4

Aug 1800
Aug 1800

214
104

0,2
0,4

23,4
22,9

9,13
4,56

Page 12 of 19

Ventilation Sizing Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ....................................................................... 17 L/s

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
OFFICE
PASSAGE
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.90

Mult.

Floor
Area
(m)

Maximum
Occupants

1
1

23,4
22,9

4,0
0,0

Maximum
Supply Air
(L/s)

Required
Outdoor Air
(L/s/person)

Required
Outdoor Air
(L/(s-m))

213,7
104,4
318,1

2,50
0,00

0,30
0,00

Required
Required
Outdoor Air Outdoor Air
(L/s) (% of supply)
0,0
0,0

0,0
0,0

Uncorrected
Outdoor Air
(L/s)
17,0
0,0
17,0

Page 13 of 19

Air System Design Load Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Terminal Reheat Coils
>> Total Conditioning
Key:

Hourly Analysis Program v4.90

11/15/2015
05:43

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1700
HEATING DATA AT DES HTG
COOLING OA DB / WB 49,2 C / 29,9 C
HEATING OA DB / WB 10,0 C / 5,8 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
52 m
667
52 m
258
46 m
470
46 m
215
0 m
0
0 m
0
0 m
0
0 m
0
6 m
264
6 m
121
36 m
0
36 m
0
0 m
0
0 m
0
0 m
0
0 m
0
568 W
489
0
0
0W
0
0
0
1498 W
1405
0
0
4
237
240
0
0
0
0
0
0
0
0
20% / 20%
707
48
0%
0
4239
288
595
4312
288
544
0%
0
0
0
0%
0
0
0
0%
0
0
0
310 L/s
0
17 L/s
0
17 L/s
489
483
1 L/s
12
310 L/s
0
17 L/s
0
0
0
0%
0
0%
0
4800
771
556
4800
771
0
0
556
4800
771
556
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Latent
(W)
0
0
0
0
0
0
0
0
0
0

Page 14 of 19

Zone Design Load Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

Zone 1

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

Hourly Analysis Program v4.90

11/15/2015
05:43

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 48,3 C / 29,7 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
52 m
669
52 m
258
46 m
476
46 m
215
0 m
0
0 m
0
0 m
0
0 m
0
6 m
258
6 m
121
36 m
0
36 m
0
0 m
0
0 m
0
0 m
0
0 m
0
568 W
494
0
0
0W
0
0
0
1498 W
1411
0
0
4
240
240
0
0
0
0
0
0
0
0
20% / 20%
710
48
0%
0
4259
288
595

Latent
(W)
0
0
0
0
0

Page 15 of 19

Space Design Load Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

TABLE 1.1.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

11/15/2015
05:43

COMPONENT LOADS FOR SPACE '' OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 48,3 C / 29,7 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
13 m
158
13 m
67
23 m
241
23 m
109
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
0 m
0
13 m
0
13 m
0
0 m
0
0 m
0
0 m
0
0 m
0
384 W
334
0
0
0W
0
0
0
1498 W
1411
0
0
4
240
240
0
0
0
0
0
0
0
0
20% / 20%
477
48
0%
0
2861
288
176

TABLE 1.1.B.

S EXPOSURE
WALL
H EXPOSURE
ROOF

Hourly Analysis Program v4.90

ENVELOPE LOADS FOR SPACE '' OFFICE '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

Latent
(W)
0
0
0
0
0

HEATING
TRANS
(W)

13

0,450

158

67

23

0,418

241

109

Page 16 of 19

Space Design Load Summary for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

TABLE 1.2.A.

SPACE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads

TABLE 1.2.B.

E EXPOSURE
WALL
S EXPOSURE
WALL
DOOR
H EXPOSURE
ROOF

Hourly Analysis Program v4.90

11/15/2015
05:43

COMPONENT LOADS FOR SPACE '' PASSAGE '' IN ZONE '' Zone 1 ''
DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1800
HEATING DATA AT DES HTG
COOLING OA DB / WB 48,3 C / 29,7 C
HEATING OA DB / WB 10,0 C / 5,8 C
OCCUPIED T-STAT 23,9 C
OCCUPIED T-STAT 21,1 C
Sensible
Latent
Sensible
Details
(W)
(W)
Details
(W)
0 m
0
0 m
38 m
511
38 m
191
23 m
236
23 m
106
0 m
0
0 m
0
0 m
0
0 m
0
6 m
258
6 m
121
23 m
0
23 m
0
0 m
0
0 m
0
0 m
0
0 m
0
184 W
160
0
0
0W
0
0
0
0W
0
0
0
0
0
0
0
0
0
0
0
0
0
0
20% / 20%
233
0
0%
0
1397
0
419

ENVELOPE LOADS FOR SPACE '' PASSAGE '' IN ZONE '' Zone 1 ''
COOLING
COOLING
Area
U-Value
Shade
TRANS
SOLAR
(m)
(W/(m-K))
Coeff.
(W)
(W)

Latent
(W)
0
0
0
0
0

HEATING
TRANS
(W)

31

0,450

427

156

7
6

0,450
1,703

84
258

35
121

23

0,418

236

106

Page 17 of 19

System Psychrometrics for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

August DESIGN COOLING DAY, 1700


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum
Return Fan

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
49,2
26,0
13,1
13,1
13,1
24,7
24,7
24,7

Specific
Humidity
(kg/kg)
0,01888
0,00951
0,00867
0,00867
0,00867
0,00898
0,00898
0,00898

Airflow
(L/s)
17
310
310
310
310
310
310
310

CO2 Level
(ppm)
400
1396
1396
1396
1396
1453
1453
1453

Sensible
Heat
(W)
489
4800
0
4312
0
0

Latent
Heat
(W)
483
771
288
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2942,3 W/(L/s)
Site Altitude = 14,9 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.90

Zone
Sensible
Load
(W)
4239

T-stat
Mode
Cooling

Zone
Cond
(W)
4312

Zone
Temp
(C)
24,7

Zone
Airflow
(L/s)
310

CO2
Level
(ppm)
1453

Terminal
Heating
Coil
(W)
0

Zone
Heating
Unit
(W)
0

Page 18 of 19

System Psychrometrics for Electrical Substation Office


Project Name: Electrical Substation
Prepared by: DISEPROSA

11/15/2015
05:43

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum
Return Fan

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(C)
10,0
19,9
19,9
19,9
20,0
20,5
20,5
20,5

Specific
Humidity
(kg/kg)
0,00401
0,00401
0,00401
0,00401
0,00401
0,00401
0,00401
0,00401

Airflow
(L/s)
1
17
17
17
17
17
17
17

CO2 Level
(ppm)
400
575
575
575
575
585
585
585

Sensible
Heat
(W)
-12
0
0
-544
0
0

Latent
Heat
(W)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2942,3 W/(L/s)
Site Altitude = 14,9 m

TABLE 2:

ZONE DATA

Zone Name
Zone 1

Hourly Analysis Program v4.90

Zone
Sensible
Load
(W)
-595

T-stat
Mode
Heating

Zone
Cond
(W)
-544

Zone
Temp
(C)
20,5

Zone
Airflow
(L/s)
17

CO2
Level
(ppm)
585

Terminal
Heating
Coil
(W)
556

Zone
Heating
Unit
(W)
0