ESR-1056*

Reissued December 1, 2004


This report is subject to re-examination in two years.

ICC Evaluation Service, Inc.

www.icc-es.org

Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543
Regional Office # 900 Montclair Road, Suite A, Birmingham, Alabama 35213 # (205) 599-9800
Regional Office # 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 # (708) 799-2305

DIVISION: 03CONCRETE
Section: 03151Concrete Anchoring

diameters, and with various lengths for multiple embedments


as noted in the tables in this report. Refer to Figure 1 for an
illustration of a typical screw anchor.

DIVISION: 04MASONRY
Section: 04081Masonry Anchorage

3.1.2 Normal-weight Concrete: Concrete shall be stoneaggregate normal-weight concrete having a minimum
compressive strength as noted in the tables in this report at
the time of anchor installation. Minimum concrete thickness
is 11/2 times the anchor embedment at the location of anchor
installation.

REPORT HOLDER:
SIMPSON STRONG-TIE COMPANY, INC.
4120 DUBLIN BOULEVARD, SUITE 400
DUBLIN, CALIFORNIA 94568
(925) 560-9000
www.simpsonanchors.com

3.1.3 Structural Sand-lightweight Concrete-fill Metaldeck Assembly:


3.1.3.1 Metal Deck: The metal deck shall be minimum No.
20 gage [0.035 inch (0.889 mm) base-metal thickness]
galvanized steel conforming to ASTM A 653/A 653M, with a
minimum yield strength of 38 ksi (261.8 MPa) and a minimum
ultimate strength of 45 ksi (310 MPa). Figure 2 illustrates
required metal-deck bottom-flute dimensions: a minimum of
41/2 inches (114 mm) wide, a maximum of 3 inches (76 mm)
deep, and with a minimum spacing of 12 inches (305 mm).
Metal decks having greater bottom flute widths and relative
spacings shall be permitted.

EVALUATION SUBJECT:
TITEN HD SCREW ANCHORS
1.0 EVALUATION SCOPE
Compliance with the following codes:
# 2000 International Building Code (IBC).

3.1.3.2 Concrete Fill: The structural sand-lightweight


concrete shall have a minimum 3,000 psi (20.7 MPa)
compressive strength at time of anchor installation.
Aggregates for structural sand-lightweight concrete shall
comply with Section 3.3 of ACI 318-95. Minimum concrete
thickness measured from the top flute is 31/4 inches (83 mm).
Refer to Figure 2.

# 2000 International Residential Code (IRC).


# 1997 Uniform Building Code (UBC).
Properties evaluated:
Structural
2.0 USES
The Titen HD screw anchor is for installation in predrilled
holes in normal-weight concrete, structural sand-lightweight
concrete on metal deck, and fully grouted concrete masonry
wall construction.
The Titen HD screw anchor is an alternative to cast-in-place
anchors described in IBC Section 1912 and UBC Section
1923.1. The anchors are permitted to be used in structures
regulated by the IRC, provided an engineered design is
submitted in accordance with IRC Section R301.1.2.
3.0 DESCRIPTION
3.1

Materials:

3.1.1 Titen HD Screw Anchor: The Titen HD screw anchor


is a carbon steel threaded anchor with a hex-washer head.
The screw anchor is manufactured from heat-treated steel
complying with SAE J403 Grade 10B21, and has either an
electrodeposited coating of zinc in accordance with ASTM B
633, Service Condition SC1, Type III; or a mechanically
deposited coating of zinc in accordance with ASTM B 695,
Class 65, Type I.
Titen HD screw anchors are available with nominally 3/8-,
/2-, 5/8-, and 3/4-inch (9.5, 12.7, 15.9 and 19.1 mm) shank

3.1.4 Grout-filled Concrete Masonry: When prism tests


are required, the compressive strength of masonry, fNm, at 28
days shall be a minimum of 1,500 psi (10.3 MPa). Fully
grouted masonry walls shall be constructed from the following
materials:
3.1.4.1 Concrete Masonry Units (CMUs): CMUs shall be
minimum Grade N, Type II, lightweight, medium-weight, or
normal-weight conforming to ASTM C 90 or UBC Standard
21-4. The minimum allowable nominal size of the CMU shall
be 8 inches (203 mm) wide by 8 inches (203 mm) high by 16
inches (406 mm) long (i.e., 8816).
3.1.4.2 Grout: Grout shall comply with IBC Section 2103.10,
IRC Section R609.1.1, or UBC Section 2103.4, as applicable.
Alternatively, the grout shall have a minimum compressive
strength when tested in accordance with ASTM C 1019-98a
equal to its specified strength, but not less than 2,000 psi
(13.8 MPa).
3.1.4.3 Mortar: Mortar shall comply with IBC Section
2103.7, IRC Section R607, or UBC Section 2103.3 and UBC
Standard 21-15, as applicable. The mortar shall have a
minimum compressive strength of 1,500 psi (10.3 MPa).
3.2

Design:

*Corrected October 2005


are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an
endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to any
finding or other matter in this report, or as to any product covered by the report.

Copyright 2005

Page 1 of 11

Page 2 of 11

ESR-1056

3.2.1 General: Anchors described in this report are


assigned allowable tension and shear loads for designs
based on allowable stress design (working stress design).
Use of the anchors to resist vibratory and moving loads, such
as those produced by reciprocating engines, cranes and
vehicles, is beyond the scope of this report.

assemblies subjected to combined shear and tension forces


shall be determined by the following equation:

3.2.2 Design of Anchors in Normal-weight Concrete:


Allowable tension and shear loads for installation in normalweight concrete are noted in Tables 3 through 6. Spacing and
edge distance requirements are noted in Tables 1 through 6.
Allowable load reduction factors noted in Table 2 are
applicable only to the allowable loads shown in Tables 3 and
4.

where:

For installations in normal-weight concrete, anchors are


recognized to resist dead-, live-, wind-, and earthquake-load
applications. Allowable loads may be increased by 331/3
percent when using the alternate basic load combinations in
accordance with Section 1605.3.2 of the IBC or Section
1612.3.2 of the UBC, for wind or earthquake loading
conditions. Alternatively, the load combinations in IBC Section
1605.3.2 may be multiplied by a factor of 0.75.

3.2.4 Design of Anchors Installed in Fully Grouted CMU


Masonry Walls: Allowable tension and shear loads for
anchors installed in the face of fully grouted CMU masonry
walls are noted in Table 8A for structures complying with the
IBC or IRC, and Table 8B for structures complying with the
UBC. The allowable tension and shear loads are for anchors
installed in the grouted cells, the center web of CMU units,
and horizontal mortared bed joints of fully grouted CMU
masonry wall construction. Allowable loads for anchors
installed in the vertical head joint or the end flanges of the
CMU units are outside the scope of this report. Edge and end
distances, and spacing requirements for anchors installed in
the face of fully grouted CMU masonry walls, as shown in
Figure 3, are noted in Tables 8A and 8B. Allowable load
reduction factors for anchors installed at reduced edge and
end distances, and reduced spacing, are noted in Tables 9
and 10.

Allowable loads for anchors installed in normal-weight


concrete subjected to combined shear and tension forces
shall be determined by the following equation:

Ps

Pt

5/3

V
+ s
Vt

5/3

# 1.0

where:
Ps =

Applied service tension load.

Pt =

Allowable service tension load.

Vs =

Applied service shear load.

Vt =

Allowable service shear load.

Ps Vs

+
# 1.0
Pt Vt

Ps =

Applied service tension load.

Pt =

Allowable service tension load.

Vs =

Applied service shear load.

Vt =

Allowable service shear load.

Allowable tension and shear loads for 1/2-inch and 5/8-inch


(12.7 mm and 15.9 mm) anchors installed in the top of fully
grouted concrete masonry walls (CMU grouted cores and
CMU webs), are noted in Table 11A for anchors installed in
structures complying with the IBC or IRC, and Table 11B for
anchors installed in structures complying with the UBC.

3.2.3 Design of Anchors Installed in the Top or Bottom


of Structural Sand-lightweight Concrete Filled Metal-deck
Assemblies: Allowable tension and shear loads, and spacing
and edge distance requirements, for anchors installed in the
top or bottom of structural sand-lightweight concrete filled
metal-deck assemblies are noted in Table 7. Refer to Figure
2 for required assembly details.

When using the alternate basic load combinations in IBC


Section 1605.3.2 or UBC Section 1612.3.2 that include wind
or earthquake loads, the allowable shear and tension loads
for anchors installed in the face and the top in fully grouted
CMU masonry walls may be increased by 331/3 percent.
Alternatively, the load combinations in IBC Section 1605.3.2
may be multiplied by a factor of 0.75.

Anchors installed in the top of structural sand-lightweight


concrete and metal-deck assemblies may resist wind or
earthquake loads. Allowable tension and shear loads may be
increased by 331/3 percent when using the alternate basic
load combinations in accordance with Section 1605.3.2 of the
IBC or Section 1612.3.2 of the UBC, for wind or earthquake
loading conditions. Alternatively, the load combinations in IBC
Section 1605.3.2 may be multiplied by a factor of 0.75.

Allowable loads for anchors installed in the face of fully


grouted CMU masonry walls subjected to combined shear
and tension forces shall be determined by the following
equation:

Anchors installed in the bottom of structural sandlightweight concrete and metal-deck assemblies may resist
wind or earthquake loads:

where:

Allowable tension loads for bottom deck installations may


be increased by 331/3 percent when using the alternate basic
load combinations in accordance with Section 1605.3.2 of the
IBC or Section 1612.3.2 of the UBC, for wind or earthquake
loading conditions. Alternatively, the load combinations in IBC
Section 1605.3.2 may be multiplied by a factor of 0.75.
Allowable shear loads for bottom deck installations shall not
be increased when using the alternate basic load
combinations in accordance with Section 1605.3.2 of the IBC
or Section 1612.3.2 of the UBC, for wind or earthquake
loading conditions.
Allowable loads for anchors installed into the top or bottom
of structural sand-lightweight concrete filled metal-deck

Ps Vs

+
# 1.0
Pt Vt

Ps =

Applied service tension load.

Pt =

Allowable service tension load.

Vs =

Applied service shear load.

Vt =

Allowable service shear load.

4.0 INSTALLATION
4.1

General:

Titen HD screw anchors shall be installed by drilling a pilot


hole into the substrate using a handheld electro-pneumatic
rotary hammer drill with a carbide-tipped drill bit conforming
to ANSI B212.15-1994. The pilot hole shall have the same
diameter as the nominal diameter of the anchor. The hole is
drilled to the specified embedment depth plus 1/2 inch (12.7
mm). Dust and debris in the hole shall be removed by using

Page 3 of 11

ESR-1056

oil-free compressed air. The Titen HD screw anchor shall be


installed into the hole to the required embedment using a
socket wrench or powered impact wrench.
4.1.1 Anchors Installed in Fully Grouted CMU Masonry
Walls: Anchors installed in the face of fully grouted CMU wall
construction shall be limited to the face shell of the CMU unit
(center web and grouted cores) and the horizontal mortared
bed joints, as indicated by the shaded areas in Figure 3.
Anchors installed in a T-joint, the mortared head joint, or the
end webs of a CMU unit, as indicated in the non-shaded
areas in Figure 3, are outside the scope of this report.
For anchors installed in the top of fully grouted concrete
masonry walls (CMU grouted cores and CMU webs), anchor
location shall comply with the minimum edge and end
distances noted in Tables 11A and 11B and shown in Figure
4. Anchors installed in the mortared head joint are outside the
scope of this report
4.2 Installation
Required):

with

Special

Inspection

(When

Continuous special inspection shall be provided when


required by the tables in this evaluation report. Special
inspection under the IBC and IRC shall conform to IBC
Section 1704; under the UBC, special inspection shall be in
accordance with UBC Section 1701.
For fasteners installed with special inspection, the following
items, as applicable, shall be inspected: fastener type and
dimensions; concrete type and concrete compressive
strength (for anchors installed in concrete); masonry unit type
and compliance with ASTM C 90; grout and mortar
compressive strengths, and (when required) masonry prism
compressive strength; drill bit size and compliance with ANSI
B212.15-1994; and fastener embedment, spacing, and edge
(and end) distances. The special inspector shall inspect and
verify that anchor installation complies with this evaluation
report and Simpson Strong-Tie Companys published
installation instructions.
5.0 CONDITIONS OF USE
The Titen HD Screw Anchors described in this report comply
with, or are suitable alternatives to what is specified in, the
codes listed in Section 1.0 of this report, subject to the
following conditions:
5.1

Anchors are identified and installed in accordance with


this report and the manufacturers published installation
instructions.

5.2

Anchors installed in normal-weight concrete to resist


dead, live, wind and earthquake load applications shall
be in accordance with Section 3.2.2.

5.3

Anchors installed into the top or bottom of structural


sand-lightweight concrete filled metal-deck assemblies
to resist dead, live, wind and earthquake load
applications shall be in accordance with Section 3.2.3.

5.4

Anchors installed in the face or the top of fully grouted


CMU masonry walls to resist dead, live, wind, and
earthquake load applications shall be in accordance
with Section 3.2.4.

5.5

Since an ICC-ES acceptance criteria for evaluating data


to determine the performance of anchors subjected to
fatigue or shock loading is unavailable at this time, the
use of these anchors under these conditions is beyond
the scope of this report.

5.6

Anchors are not permitted for use in conjunction with


fire-resistive construction. Exceptions would be:
Anchors resist wind or seismic loading only.

For other than wind or seismic loading, special


consideration is given to fire exposure conditions.
5.7

Since an ICC-ES acceptance criteria for evaluating the


performance of screw anchors in cracked concrete is
unavailable at this time, the use of anchors is limited to
installation in uncracked concrete. Cracking occurs
when ft > fr due to service loads or deformations.

5.8

Anchors are installed in substrates in holes predrilled


with carbide-tipped masonry drill bits complying with
ANSI B212.15-1994, and having the same diameter as
the nominal diameter of the anchor.

5.9

Calculations demonstrating that the applied loads are


less than the allowable loads described in this report,
shall be submitted to the building official. The
calculations shall be prepared by a registered design
professional where required by the statues of the
jurisdiction in which the project is to be constructed.

5.10 Special inspection, when required, shall be provided in


accordance with Section 4.2.
5.11 Anchors shall be limited to dry, interior use.
5.12 The Titen HD screw anchors are manufactured by
Simpson Strong-Tie Company at a facility in Brampton,
Ontario, Canada, under a quality control program with
inspections by CEL Consulting (AA-639).
6.0 EVIDENCE SUBMITTED
6.1

Data in accordance with the ICC-ES Acceptance


Criteria for Predrilled Fasteners (Screw Anchors) in
Concrete and Masonry (AC106), dated November 1,
2003, including the following optional tests:

6.1.1 Anchors installed in normal-weight concrete: Effects of


edge distance on tension and shear performance
(Test Series 4, 5, 6, 7, 13, 14, 15, and 16 of AC106);
effects of spacing on tension and shear performance
(Test Series 9 and 18 of AC106); oblique load tests
(Test Series 19 and 20 of AC106); and seismic
performance tests (Section 4.6 of AC106).
6.1.2 Anchors installed in the top and bottom of structural
sand-lightweight concrete and metal-deck assemblies:
Effects of edge distance on tension and shear
performance (Test Series 4 and 13 of AC106), and
seismic performance tests (Section 4.6 of AC106).
6.1.3 Anchors installed in the face of fully grouted CMU
masonry wall construction: Effects of edge distance on
tension and shear performance (Test Series 4, 5, 13,
and 14 of AC106), and seismic performance tests
(Section 4.6 of AC106).
6.1.4 Anchors installed in the top of fully grouted CMU
masonry wall construction with a minimum 13/4-inch
(44 mm) edge distance: Effects on tension and shear
performance (Test Series 4 and 13 of AC106), and
seismic performance tests (Section 4.6 of AC106).
6.2

A quality control manual.

7.0 IDENTIFICATION
Titen HD screw anchor packaging is marked with the
Simpson Strong-Tie Company name; product name (Titen
HD); anchor diameter and length; the name or logo of the
inspection agency (CEL Consulting); and the evaluation
report number (ESR-1056). In addition, the symbol and
anchor length (in inches) is stamped on the head of each
screw anchor.

Page 4 of 11

ESR-1056

FIGURE 1TYPICAL TITEN HD SCREW ANCHOR

TABLE 1SPACING AND EDGE DISTANCE REQUIREMENTS FOR TITEN HD SCREW ANCHORS
(Anchors Installed in Normal-weight Concrete)1,2
ANCHOR
DIAMETER
(inch)

MINIMUM
EMBEDMENT
DEPTH, hv
(inches)

EDGE DISTANCE
(inches)
Tension

Shear

Tension or Shear

Critical Edge
Distance, Ccr

Critical Edge
Distance, Ccr

Minimum Edge
Distance, Cmin

Critical Spacing,
Scr

Minimum
Spacing, Smin

41/2

13/4

11/2

13/4

71/2

13/4

10

21/2

13/4

12

23/4

/8

SPACING
(inches)

33/4

Tension or Shear

23/4
1

35/8

/2

5 /4
23/4
5

41/8

/8

5 /4
23/4
3

45/8

/4

5 /4
For SI: 1 inch = 25.4 mm.
1

The spacing and edge distance requirements in this table are applicable only to Tables 3 and 4.
The critical edge and spacing distances are for full anchor capacity, and the minimum edge and spacing distances are for reduced anchor
capacity. See Table 2 for applicable load reduction factors for anchors installed at distances less than the critical edge distance or less than critical
spacing.

TABLE 2LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS


(Anchors Installed in Normal-weight Concrete)1,2,3,4
ANCHOR
DIAMETER
(inch)

/8

MINIMUM
EMBEDMENT
DEPTH, hv
(inches)

23/4
33/4

EDGE DISTANCE (inches)


Tension or
Shear
Critical Edge
Distance, Ccr
1.0

23/4
1

/2

/8

/4

35/8

Minimum Edge Minimum Edge


Distance, Cmin Distance, Cmin
0.83

0.25

0.73

0.24

0.67

0.25

Tension or
Shear

Tension

Shear

Critical
Spacing, Scr

Minimum
Spacing, Smin

Minimum
Spacing, Smin

0.66

0.77

1.0

0.77

0.72

0.77

0.63

0.77

0.20

0.73

0.17

0.76

0.77

23/4

0.67

0.19

0.79

0.77

0.69

0.77

0.57

0.16

53/4

0.59

0.19

0.73

0.77

23/4

0.67

0.19

0.80

0.77

0.48

0.14

0.70

0.77

0.58

0.13

0.72

0.77

45/8

5 /4
For SI: 1 inch = 25.4 mm.

1.0

1.0

0.56

0.57

SPACING (inches)
Shear

53/4
41/8

1.0

Tension

1.0

1.0

1.0

The load reduction factors in this table are applicable only to the allowable loads shown in Tables 3 and 4.
Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied.
3
Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation.
4
Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linear
interpolation.
2

Page 5 of 11

ESR-1056
TABLE 3ALLOWABLE TENSION LOADS FOR TITEN HD SCREW ANCHORS
INSTALLED IN NORMAL-WEIGHT CONCRETE1,2,3,4 (pounds)

CRITICAL CRITICAL
MINIMUM
ANCHOR DRILL BIT
SPACING
EDGE
DIAMETER DIAMETER5 EMBEDMENT
DISTANCE (inches)
DEPTH
(inch)
(inches)
(inches)
(inches)
3

23/4

/8

/8

33/4

23/4
1

/2

/8

/4

Concrete Strength, fNc (psi)

2,000

3,000

4,000

2,000

3,000

1,075

1,315

1,550

540

660

4,000
775

1,770

2,115

2,455

885

1,060

1,230

1,400

1,645

580

700

825

2,270

2,685

930

1,135

1,345

53/4

2,570

3,240

3,910

1,285

1,620

1,955

23/4

1,155

1,400

1,645

580

700

825

2,185

2,630

3,070

1,095

1,315

1,535

53/4

3,240

3,955

4,670

1,620

1,980

2,335

23/4

1,170

1,410

1,645

585

705

825

2,585

3,470

4,355

1,295

1,735

2,180

3,440

4,055

4,670

1,720

2,030

2,335

45/8

/4

Concrete Strength, fNc (psi)

1,155

41/8

/8

INSTALLED WITHOUT SPECIAL


INSPECTION7

1,855

35/8

/2

INSTALLED WITH SPECIAL


INSPECTION6

10

12

53/4
For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.

1
Allowable loads are permitted to be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section
1605.3.2 of the IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section
1605.3.2 may be multiplied by a factor of 0.75.
2
Minimum concrete thickness is 1.5 times the anchor embedment.
3
Minimum edge distance and spacing shall comply with Table 1.
4
The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at the
time of anchor installation.
5
Anchor installation shall comply with Section 4.0 of this report.
6
These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report.
7
These tension loads are applicable when the anchors are installed without special inspection.

TABLE 4ALLOWABLE SHEAR LOADS FOR TITEN HD SCREW ANCHORS


INSTALLED IN NORMAL-WEIGHT CONCRETE1,2,3,4 (pounds)
ANCHOR
DIAMETER
(inch)
3

/8

DRILL BIT
DIAMETER5
(inch)
3

/8

MINIMUM
EMBEDMENT
DEPTH
(inches)
23/4
33/4

CRITICAL
EDGE
DISTANCE
(inches)

CRITICAL
SPACING
(inches)

41/2

23/4
1

/2

/2

/8

/8

/4

1,665

4,000
1,740

1,595

1,670

1,740

2,050

2,495

2,795

3,255

2,830

3,045

3,255

1,940

2,220

2,495

2,175

3,415

4,650

53/4

3,125

3,890

4,650

23/4

1,960

2,415

2,865

2,805

4,490

6,170

4,950

5,560

6,170

2 /4
5

3,000

1,585
1,605

/8

Concrete Strength, fNc (psi)


2,000

2,330

35/8
53/4

ALLOWABLE SHEAR LOAD6 (lbs)

41/8

45/8

53/4
For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.

71/2

10

12

1
Allowable loads are permitted to be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section
1605.3.2 of the IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section
1605.3.2 may be multiplied by a factor of 0.75.
2
Minimum concrete thickness is 1.5 times the anchor embedment.
3
Minimum edge distance and spacing shall comply with Table 1.
4
The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at the
time of anchor installation.
5
Anchor installation shall comply with Section 4.0 of this report.
6
Allowable shear loads are for installations with or without special inspection.

Page 6 of 11

ESR-1056

TABLE 5ALLOWABLE SHEAR LOADS (PARALLEL TO THE CONCRETE EDGE) FOR TITEN HD SCREW ANCHORS
INSTALLED IN fNc = 2,500 psi NORMAL-WEIGHT CONCRETE1,2,3,4 (pounds)
DRILL BIT
DIAMETER5
(inch)

ANCHOR
DIAMETER
(inch)

MINIMUM
EMBEDMENT
DEPTH
(inches)

ALLOWABLE
SHEAR LOAD
PARALLEL TO
THE CONCRETE
EDGE6
(pounds)

MINIMUM EDGE
DISTANCE
(inches)

MINIMUM END
DISTANCE
(inches)

CRITICAL
SPACING
(inches)

13/4

1,710

13/4

10

10

1,205

23/4
1

/2

1,165

31/2

/2

41/2
5

/8

1,950

23/4

/8

31/2
For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.

1,765

Allowable loads are permitted to be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section
1605.3.2 of the IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section
1605.3.2 may be multiplied by a factor of 0.75.
2
Minimum concrete thickness is 1.5 times the anchor embedment.
3
Minimum screw anchor edge and end distances, and critical spacing limitations, are applicable to the tabulated loads.
4
The tabulated loads are for anchors installed in normal-weight concrete having a minimum 2,500 psi compressive strength, fNc, at the time of
anchor installation.
5
The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.
6
Allowable shear loads are for installations with or without special inspection.

TABLE 6ALLOWABLE TENSION LOADS FOR TITEN HD SCREW ANCHORS


INSTALLED IN THE TOP SURFACE OF NORMAL-WEIGHT CONCRETE FOUNDATION STEM WALLS1,2,3,4,5 (pounds)
MINIMUM
ANCHOR LOCATION6
MINIMUM
ANCHOR DRILL BIT
ANCHOR
CONCRETE
DIAMETER DIAMETER
(inches)
EMBEDMENT FOUNDATION Critical
(inch)
(inch)
Critical
DEPTH,
STEM WALL
End
Edge
hv
THICKNESS Distance Distance
(inches)
(inches)

/2

/2

10

/2
/2
10
6
For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.
1

ALLOWABLE TENSION LOADS (pounds)


Concrete Compressive Strength, fNc
fNc = 2,500 psi

fNc = 4,500 psi

Installed
Installed
Installed
Installed
without
with Special
without
with
Special
Inspection7
Special
Special
Inspection8
Inspection7 Inspection8

13/4

3,855

1,930

5,075

2,540

13/4

43/8

3,570

1,785

4,760

2,380

Allowable loads may be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section 1605.3.2 of the
IBC or Section 1612.3.2 of the UBC, for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section 1605.3.2 may
be multiplied by a factor of 0.75.
2
Minimum concrete thickness is 12 inches.
3
Minimum screw anchor spacing is 15 inches.
4
The tabulated loads are for anchors installed in normal-weight concrete having a minimum compressive strength as shown in the table at the
time of anchor installation.
5
Anchor installation shall comply with Section 4.0 of this report.
6
Critical screw anchor edge and end distances are applicable to the tabulated loads.
7
These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report.
8
These tension loads are applicable when the anchors are installed without special inspection.

Page 7 of 11

ESR-1056
TABLE 7ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS
INSTALLED ON TOP OR BOTTOM OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE (f c = 3,000 psi)
AND METAL-DECK ASSEMBLIES1,2

ANCHOR
DIAMETER
(inch)

DRILL BIT
DIAMETER
(inch)

MINIMUM
EMBEDMENT
DEPTH
(inches)

ANCHOR LOCATION6 (inches)


Edge Distance
Minimum

Critical

Critical
Spacing

ALLOWABLE LOADS4 (lbs)


Shear7

Tension
Installed
with
Special
Inspection5

Installed
without
Special
Inspection6

ANCHORS INSTALLED IN THE TOP OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLIES
3

23/4

640

320

1,060

23/4

760

380

1,595

23/4

10

10

10

775

390

1,595

/8
/2
/8

/8
/2
/8

ANCHORS INSTALLED IN BOTTOM FLUTES OF STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLIES8
3

11/2 (9)

N/A

1,355

675

11/2 (9)

N/A

1,755

875

1,710

5
/8
/8
5
11/2 (9)
For SI: 1 inch = 25.4 mm, 1 lb = 4.45 N, 1 psi = 6.89 kPa.

N/A

10

2,235

1,115

2,675

/8
/2

/8
/2

1,025

The assembly shall consist of a metal deck and structural sand-lightweight concrete fill:
The deck shall be steel conforming to ASTM A 653/A 653M, with a minimum yield strength of 38,000 psi and minimum tensile strength of
45,000 psi, and shall have a minimum thickness of No. 20 gage [0.035 inch base-metal thickness (0.89 mm)]. Figure 2 illustrates required
metal-deck bottom-flute dimensions: a minimum of 41/2 inches (114 mm) wide, a maximum of 3 inches (76 mm) deep, and a minimum
spacing of 12 inches (305 mm). Metal decks having greater bottom flute widths and relative spacings shall be permitted.
The structural sand-lightweight concrete shall have a minimum concrete compressive strength, fNc, at the time of anchor installation of 3,000
psi, and shall have a minimum thickness of 31/4 inches measured from the top flute. Refer to Figure 2.
2
Anchor installation shall comply with Section 4.0 of this report.
3
Anchor edge distance and spacing shall comply with tabulated loads. N/A = Not applicable.
4
Use of anchors installed in the top or bottom of structural sand-lightweight concrete and metal-deck assemblies shall be permitted to resist wind
or earthquake tension and shear loads. Refer to Section 3.2.3 for design requirements for anchors installed in the top of the assembly, and for
anchors installed in the bottom of the assembly.
5
These tension loads are applicable only when the anchors are installed with special inspection as set forth in Section 4.2 of this report.
6
These reduced tension loads are applicable for anchors installed without special inspection.
7
Allowable shear loads are for installations with or without special inspection.
8
Allowable tension and shear loads are for anchors installed in the bottom flute of the steel deck, at a minimum edge distance of 11/2 inches from
the inclined edge of the bottom flute. Allowable shear loads act parallel or perpendicular to the deck flutes.
9
Minimum distance from an anchor to the end of a flute for bottom of deck installations shall comply with the following:
6 inches for 3/8-inch-diameter anchor.
8 inches for 1/2-inch-diameter anchor.
10 inches for 5/8-inch-diameter anchor.

FIGURE 2TITEN HD SCREW ANCHOR INSTALLED IN THE TOP AND BOTTOM OF A


STRUCTURAL SAND-LIGHTWEIGHT CONCRETE AND METAL-DECK ASSEMBLY

Page 8 of 11

ESR-1056

TABLE 8AIBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS INSTALLED IN THE
FACE OF FULLY GROUTED CMU MASONRY WALL CONSTRUCTION1
ANCHOR
DIA.2
(in.)

DRILL BIT
DIA.
(in.)

ANCHOR LOCATION4 (inches)

MIN.
EMBED.3
(in.)

Edge Distance

ANCHORS INSTALLED AT
DISTANCES $ CRITICAL EDGE
DISTANCE, ccrit, AND SPACING,
scrit5,6,7
(lbf)

Spacing

Critical, ccrit Minimum, cmin Critical, scrit

Tension

Shear

Minimum, smin

23/4

12

480

870

31/2

12

690

1,385

41/2

12

10

1,060

2,085

12

1,600

3,000

/8
/2
/8

/8
/2
/8

/4
/4
51/2
12
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.48 N
1

Anchors shall be installed a minimum of 11/4 inches from vertical head joints and T-joints. Refer to Figure 3 for permitted and prohibited anchor
installation locations.
2
The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.
3
Embedment depth is measured from the outside face of the masonry.
4
Critical and minimum edge distances, ccr and cmin, respectively, shall comply with this table. Refer to Figure 3. Critical and minimum spacing, scrit
and smin, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or shear
loads. Refer to Table 9 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge distances,
and to Table 10 for anchors installed between critical and minimum spacing.
5
Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight,
or normal-weight, closed-end, concrete masonry units (CMUs) conforming to ASTM C 90. Masonry shall be fully grouted with coarse grout having
a minimum compressive strength of 2,000 psi, and complying with IBC Section 2103.10 or IRC Section R609.1.1 as applicable. Mortar shall
comply with IBC Section 2103.7 or IRC Section R607, as applicable, and shall have a minimum specified compressive strength of 1,500 psi. The
specified compressive strength of masonry, fNm, at 28 days shall be a minimum of 1,500 psi.
6
Tabulated allowable loads are based on a safety factor of 5.0 and are based on special inspection being provided during anchor installation.
Special inspection requirements shall comply with Section 4.2 of this report.
7
Allowable loads may be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section 1605.3.2 of the
IBC for wind or earthquake loading conditions. Alternatively, the load combinations in IBC Section 1605.3.2 may be multiplied by a factor of 0.75.

FIGURE 3TITEN HD SCREW ANCHOR INSTALLED IN THE FACE OF GROUT-FILLED CMU


(CONCRETE MASONRY UNIT) WALL CONSTRUCTION (Refer to Tables 8, 9, and 10)

Page 9 of 11

ESR-1056

TABLE 8BALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS INSTALLED IN THE
FACE OF FULLY GROUTED CMU MASONRY WALL CONSTRUCTION1
ANCHOR
DIA.2
(in.)

DRILL
BIT DIA.
(in.)

ANCHOR LOCATION4 (inches)

MIN.
EMBED.3
(in.)

Edge Distance

ALLOWABLE LOADS BASED ON


ANCHORS INSTALLED AT DISTANCES
> CRITICAL EDGE DISTANCE, ccrit, AND
SPACING, scrit5,6,7
(lbf)

Spacing

Shear9

Tension

Critical, ccrit Minimum, cmin Critical, scrit Minimum, smin Installed with
Special
Inspection7

Installed
without
Special
Inspection8

23/4

12

600

300

31/2

12

860

430

1,730

41/2

12

10

1,325

665

2,605

3
/4
/4
51/2
12
4
For SI: 1 inch = 25.4 mm, 1 psi = 6.89 kPa, 1 lbf = 4.48 N.

12

2,000

1,000

3,750

/8
/2
/8

/8
/2
/8

1,085

Anchors shall be installed a minimum of 11/4 inches from vertical head joints and T-joints. Refer to Figure 3 for permitted and prohibited anchor
installation locations.
2
The drill bit diameter shall be equal to the nominal diameter of the anchor. Anchor installation shall comply with Section 4.0 of this report.
3
Embedment depth is measured from the outside face of the masonry.
4
Critical and minimum edge distances, ccr and cmin, respectively, shall comply with this table. Refer to Figure 3. Critical and minimum spacing, scrit
and smin, respectively, shall comply with this table. Critical and minimum edge and spacing distances are valid for anchors resisting tension or shear
loads. Refer to Table 9 for allowable tension and shear load reduction factors for anchors installed between critical and minimum edge distances,
and to Table 10 for anchors installed between critical and minimum spacing.
5
Tabulated loads are for anchors installed in fully grouted masonry wall construction, consisting of Grade N, Type II, lightweight, medium-weight,
or normal-weight, closed-end, concrete masonry units (CMUs) conforming to UBC Standard 21-4. Masonry shall be fully grouted with coarse grout
having a minimum compressive strength of 2,000 psi, and complying with UBC Section 2103.4. Mortar shall comply with UBC Section 2103.3
and UBC Standard 21-15, and shall have a minimum specified compressive strength of 1,500 psi. The specified compressive strength of masonry,
fNm, at 28 days shall be a minimum of 1,500 psi.
6
Allowable loads may be increased by 331/3 percent when using the alternate basic load combinations in accordance with Section 1612.3.2 of the
UBC for wind or earthquake loading conditions.
7
These allowable tension loads are based on a factor of safety of 4.0 and special inspection being provided during anchor installation. Special
inspection requirements shall comply with Section 4.2 of this report.
8
These reduced allowable tension loads are applicable for anchors installed without special inspection and are based on a factor of safety of 8.0.
9
These allowable shear loads are based on a factor of safety of 4.0 and anchor installation with or without special inspection.

Page 10 of 11

ESR-1056

TABLE 9LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS INSTALLED BETWEEN CRITICAL
AND MINIMUM EDGE DISTANCES (Anchors Installed in the Face of Grout-filled CMU Masonry Walls)1,2,3
MINIMUM
EMBEDMENT
DEPTH, hv
(inches)

ANCHOR
DIAMETER
(inch)

LOAD REDUCTION FACTORS FOR ANCHORS INSTALLED AT:


Critical Edge
Distance, Ccrit

Minimum Edge Distance, Cmin

Tension or Shear
Load

Tension Load

Shear Load Acting:


Towards
an Edge

Away from
an Edge

Parallel to
an Edge

23/4

1.0

1.0

0.58

0.89

0.77

31/2

1.0

1.0

0.38

0.79

0.48

41/2

1.0

0.83

0.30

0.58

0.46

51/2

1.0

0.66

0.21

0.38

0.44

/8
/2
/8

/4
For SI: 1 inch = 25.4 mm.
1

The load reduction factors in this table are applicable to the allowable loads shown in Tables 8A and 8B.
Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied.
3
Load reduction factors for anchors loaded in tension or shear with edge distances between critical and minimum are obtained by linear
interpolation.
2

TABLE 10LOAD REDUCTION FACTORS FOR TITEN HD SCREW ANCHORS INSTALLED BETWEEN CRITICAL AND MINIMUM
SPACING
(Anchors Installed in the Face of Grout-filled CMU Masonry Walls)1,2,3
MINIMUM
EMBEDMENT
DEPTH, hv
(inches)

ANCHOR
DIAMETER
(inch)

LOAD REDUCTION FACTORS FOR ANCHORS INSTALLED AT:


Critical Spacing, Scrit

Minimum Spacing, Smin

Tension or Shear Load

Tension Load

Shear Load

2 /4

1.0

0.87

0.62

31/2

1.0

0.69

0.62

41/2

1.0

0.59

0.62

51/2

1.0

0.50

0.62

/8
/2
/8

/4
For SI: 1 inch = 25.4 mm.
1

The load reduction factors in this table are applicable to the allowable loads shown in Tables 8A and 8B.
Reduction factors are cumulative. Multiple reduction factors for more than one spacing or edge distance are calculated separately and multiplied.
3
Load reduction factors for anchors loaded in tension or shear with spacing between critical and minimum are obtained by linear interpolation.
2

TABLE 11AIBC AND IRC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS
INSTALLED IN TOP OF GROUT-FILLED CMU MASONRY WALLS1
ANCHOR
DIA.
(inch)

/2

DRILL
BIT
DIA.
(inch)

/2

MIN.
EMBED.
(inches)

41/2

ANCHOR LOCATION2 (inches)


Minimum
Edge
Distance

Minimum
End
Distance

13/4

5
/8
/8
41/2
13/4
10
For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kPa.
1

Minimum
Spacing

IBC AND IRC ALLOWABLE LOADS3,4,5 (pounds)


Tension

Shear
Parallel
to Edge of
Masonry Wall

Perpendicular
to Edge of
Masonry Wall

570

585

160

10

570

675

160

The allowable tension and shear loads in Table 11A are applicable when anchors are installed in structures regulated by the IRC or IBC.
Minimum edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively. Refer
to Figure 4. Minimum spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside the scope
of this report.
3
The allowable loads in Table 11A are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to wind
and earthquake forces, the allowable loads may be increased as indicated in Section 3.2.4 of this report.
4
Loads for Grade N, Type II, lightweight, medium-weight, or normal-weight concrete masonry units (CMUs) conforming to ASTM C 90. Allowable
minimum nominal dimensions of the CMU shall be 8 inches wide by 8 inches high by 16 inches long (8"8"16"). Masonry wall construction shall
be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with IBC Section 2103.10 or IRC Section
R609.1.1, as applicable. Mortar shall comply with IBC Section 2103.7 or IRC Section R607.1, as applicable, and have a minimum compressive
strength of 1,500 psi. The specified compressive strength of masonry, fNm, at 28 days shall be a minimum of 1,500 psi.
5
Allowable tension and shear loads are based on a safety factor of 5.0, and are based on anchor installations with special inspection. Special
inspection shall be provided during anchor installation in accordance with Section 2107.2.1 of the IBC or Section R104.4 of the IRC, as applicable.
Refer to Section 4.2 of this report for special inspection requirements.
2

Page 11 of 11

ESR-1056
TABLE 11BUBC ALLOWABLE TENSION AND SHEAR LOADS FOR TITEN HD SCREW ANCHORS
INSTALLED IN TOP OF GROUT-FILLED CMU MASONRY WALLS1

ANCHOR
DIA.
(inch)

/2

DRILL
BIT
DIA.
(inch)

/2

MIN.
EMBED.
(inches)

41/2

ANCHOR LOCATION2 (inches)


Minimum
Edge
Distance

Minimum
End
Distance

13/4

5
/8
/8
41/2
13/4
10
For SI: 1 inch = 25.4 mm, 1 pound = 4.45 N, 1 psi = 6.89 kPa.
5

Minimum
Spacing

UBC ALLOWABLE LOADS3,4 (pounds)


Shear5

Tension
Installed
with
Special
Inspection6

Installed
without
Special
Inspection7

Parallel
to Edge of
Masonry

Perpendicular
to Edge of
Masonry

715

355

730

200

10

715

355

845

200

The allowable tension and shear loads in Table 11B are applicable for anchors installed in structures regulated by the UBC.
Minimum edge and end distances are measured from the anchor centerline to the edge and end of the CMU masonry wall, respectively. Refer
to Figure 4. Minimum spacing is measured from center-to-center of two anchors. Anchors installed in the mortared head joint are outside the scope
of this report.
3
The allowable loads in Table 11B are for anchors resisting dead, live, wind, and earthquake load applications. For short-term loading due to wind
and earthquake forces, the allowable loads may be increased as indicated in Section 3.2.4 of this report.
4
Loads for Grade N, Type II, lightweight, medium-weight, or normal-weight concrete masonry units (CMUs) conforming to UBC Standard 21-4.
Allowable minimum nominal dimensions of the CMU shall be 8 inches wide by 8 inches high by 16 inches long (8"8"16"). Masonry wall
construction shall be fully grouted with coarse grout having a minimum compressive strength of 2,000 psi, and complying with UBC Section 2103.4.
Mortar shall comply with UBC Section 2103.3 and UBC Standard 21-15, and have a minimum compressive strength of 1,500 psi. The specified
compressive strength of masonry, fNm, at 28 days shall be a minimum of 1,500 psi.
5
Allowable shear loads are based on a safety factor of 4.0. Special inspection for anchor installation is not required.
6
Allowable tension loads in the column entitled Installed with Special Inspection are based on a safety factor of 4.0. Special inspection shall be
provided during anchor installation, and shall comply with the requirements described in Section 4.2 of this report.
7
Allowable tension loads in the column entitled Installed without Special Inspection are based on a safety factor of 8.0. Special inspection for
anchor installation is not required for anchors assigned these reduced allowable tension loads.
2

FIGURE 4EDGE AND END DISTANCES FOR THE TITEN HD ANCHOR


INSTALLED IN THE TOP OF CMU MASONRY WALL CONSTRUCTION