EPB18132
SAC/XLPE/FGT/PVC
2
3
4
IEC
NetworkRail NR/L2/ELP/27408
BS EN 60228
BS 7655-1.3 and BS 7655-4.2
IEC 60502-1
6
Circular conductors schematic design
Rated Voltage
2
0,6/1kV
Outer sheath colour
BLACK
Conductor Identification
Brown, Black
Marking on the outer sheath
On the outer sheath by embossing on two primary
lines with the following information (example) :
Legend 1 (line 1):
CABELTE ELECTRIC CABLE 600/1000 V
NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR
Railway Catalogue number Property of Network Rail M.M.
Legend 2 (line 2):
CABELTE ELECTRIC CABLE 600/1000 V
NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR
Railway Catalogue number Property of Network Rail
DEP 2011-12-09
1 Conductor
Solid Aluminium Conductors (SAC), circular
( 35mm2) or shaped (> 35mm2), class 1,
according to BS EN 60228.
2 Insulation
XLPE type GP 8 according to BS 7655-1.3.
The two insulated conductors are stranded.
3 Identification tape
Polypropylene tape with a printed legend:
Property of Network Rail CABELTE YEAR,
applied over the stranded cores.
Thickness = 50m | Minimum width = 5mm.
4 Bedding (only in circular conductors design)
PVC.
5 Rodent protection
Fibreglass tape, helically applied with a minimum
overlap of 15%. Weaving design: plain weave 1/1
(272 tex). Nominal thickness of tape = 0,65mm.
6 Outer sheath
PVC type 9 according to BS 7655-4.2.
Page 1/3
PRODUCT SPECIFICATION
EPB18132
Technical Characteristics
Cable designation
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
0,6/1
2x16
2x25
2x35
2x50
2x70
2x95
2x120
Al Class 1
Al Class 1
Al Class 1
Al Class 1
Al Class 1
Al Class 1
Al Class 1
1,91
1,20
0,868
0,641
0,443
0,320
0,253
0,125
0,141
0,153
0,184
0,217
0,243
0,271
0,130
0,150
0,165
0,179
0,205
0,228
0,247
2,50+j2,29
1,59+j2,26
1,16+j2,24
0,87+j2,22
0,62+j2,19
0,46+j2,16
0,37+j2,14
Positive sequence impedance (/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770
Negative sequence impedance (/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770
Inductance (mH/km)
0,319
0,298
0,286
0,275
0,261
0,252
0,245
Reactance (/km)
0,100
0,0936
0,0898
0,0864
0,0820
0,0792
0,0770
1,96
1,23
0,890
0,660
0,457
0,332
0,264
XLPE GP8
XLPE GP8
XLPE GP8
XLPE GP8
XLPE GP8
XLPE GP8
XLPE GP8
2,0
2,0
2,0
2,0
2,0
2,0
2,0
BR-BK
BR-BK
BR-BK
BR-BK
BR-BK
BR-BK
BR-BK
Sheath material
PVC 9
PVC 9
PVC 9
PVC 9
PVC 9
PVC 9
PVC 9
2,4
2,4
2,6
2,7
2,9
3,0
3,2
Rodent protection
FGT
FGT
FGT
FGT
FGT
FGT
FGT
Yes
Yes
Yes
Yes
Yes
Yes
Yes
25
27
29
27
29
32
34
200
216
232
216
232
256
272
660
810
970
810
1010
1220
1450
4000
3000
3000
3000
2000
1500
1500
48
75
105
150
210
285
360
Impedance (cos
= 0,8) (/km)
Insulation material
Insulation nom. thickness (mm)
BR - Brown
BK - Black
FGT- Fibre Glass Tape
(1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100.m).
(2) These values may suffer slight changes.
DEP 2011-12-09
Page 2/3
PRODUCT SPECIFICATION
EPB18132
Technical Characteristics (cont.)
Cable designation
SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC
0,6/1
0,6/1
2x150
2x185
Al Class 1
Al Class 1
0,206
0,164
0,307
0,321
0,269
0,284
0,32+j2,12
0,26+j2,11
0,239
0,235
Reactance (/km)
0,0751
0,0738
0,217
0,175
XLPE GP8
XLPE GP8
2,0
2,0
BR-BK
BR-BK
Sheath material
PVC 9
PVC 9
3,4
3,6
Rodent protection
FGT
FGT
Yes
Yes
36
39
288
312
1680
1950
1400
1200
450
555
Impedance (cos
= 0,8) (/km)
Insulation material
Insulation nom. thickness (mm)
BR - Brown
BK - Black
FGT- Fibre Glass Tape
(1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100.m).
(2) These values may suffer slight changes.
DEP 2011-12-09