Sie sind auf Seite 1von 13

CIVIL WORKS FOR DATA CENTER

Sr. N0.

Item Description

Units

Qty.

Dismantling of existing office area and making it ready for Data


Centre floor containing furnitures, false ceiling, conduits,
lighting fixtures, windows, doors (in false ceiling) raceways etc
and pile them at one position indicated by customer.

Lot

POP Punning (8mm-12mm): Providing and fixing Average


8mm to 12mm thick POP Punning over cement plaster in line
& plumb finished smooth to receive paint.
Providing and laying 230mm thick brick wall with well burnt
good quality brick, in cement mortar 1:4. The bricks should be
fixed in Tounge and Groove arrangement to fix with earlier wall
and should have 6 inches wide plastering mesh (Metallic /
diamond shape PVC) beforeie providing with plaster from both
the sides of the wall. The plaster shall be applied from outside
wall whereever possible.
Providing & applying 10 to 12mm thk. Cement plaster in
cement & sand mortar 1:4 rough sand surface

Sqft

1100

Sft

168

Sft

759

Nos

Nos

Sqft

440

Sqft

440

Sft

100

Sqft

175

Nos

DOORS
Providing and fixing Single Leaf 2 hour Fire Rated Metallic
Door with frame and Vision Panel size 200mm x 300mm
(1200mm x 2200mm)
2 Providing and fixing Single leaf LAMINATED FLUSH DOOR (9
mm laminate) with Door Frame and fittings, Door closure of
Dorma make with 200 high Handle.(900 x2200)

FALSE CEILING
Providing and fixing Non perforated GI Metal ceiling system
0.4mm thk with Microlook Edge in true horizontal level
suspended on XL 15mm locking grid system and having format
as 600 x 600 mm supported at minimum 1200 mm inervals,
made of hot dip galvanized steel section powder coated as per
manufacturers specification.
FLOORING
The access floor system shall provide a minimum finished floor
height of 450 mm from the existing floor level. The system
shall provide for suitable pedestal and understructure design to
withstand various static loads and rolling loads. The entire
Access floor system shall be be made from steel and
cementatious infilled Access Floor system.UDL of 1350kg /
sq.mt to be maintained for the raised floor tiles.
Providing and Fixing 2mm thk Antistatic and antiskid Vinyl
flooring.
PARTITION
Providing & laying of 200mm thick light weight block (Aerocon)
in cement mortar 1:5 (1cement: 4 coarse sand) including
raking out the joints complete as directed & specified.
FURNITURE WORKS

Providing & fixing Modular table Linear type Size 1200mm X


600mm with laminate finish, also having metalic keyboard with
3 drawer pedestal. Also to have partition upto 1200mm height.

Providing Chairs- Medium Back with fabric on seat and back.


Basic Price Rs.7500/-

Nos

Providing and fixing Storage cabinets made out of comm Ply /


Particle board finished with laminate.

Sqft

40

Sqft

Nos

Sqft

1100

month

Nos
Sq Ft

2
40

sft.

646

1
2
3

5
7
8

1
TOTAL

MISCELLANEOUS
Providing & fixing - Floor Matts - 10mm thk as per requirement
Providing & fixing - Door Signages with vinyl cutting on acrylic
base.(size : 12"x3")
Providing and applying paint of approved make and pastel
shade to give an even shade over a primer coat as per
manufacturers recommendations after applying painting putty
to level and plumb and finishing with 2 coats of Plastic paint on
base coat of primer coat.
Housekeeping 2 person 1 industrial vaccum cleaner for 8
hours per day
Two Cup Tile Puller
Providing Step /ramp of 1200 mm Width and capable of
handling rack movement over the surface with matching
laimnation as raised floor with Vinyl Mat flooring and 3M
antiskid tape fixed horizontally at 1 feet distance each from
start to finish of the ramp . The structure should be of suitable
material and frame work of metallic nature if requested by
customer to handle heavey weight equipment
DISMANTLING AND REMOVAL
Demolishing and dismantling of existing partitions floors etc

SL.NO

BILL OF MATERIAL FOR ELECTRICAL WORKS


DESCRIPTION OF WORK

QUANTITY

UNIT

INTERNAL ELECTRICAL WORKS


Supply, receive, store, installation, testing & commissioning of the following as per
technical specifications & relevant drawings.
1.0
1.1
1.1.1

LT PANELS & FACTORY-BUILT MCB DISTRIBUTION BOARDS:


LT PANELS:
DATECENTER MAIN PANEL - As per the attached drawing
Supply, store, erection, testing and commissioning of 415v, 50HZ, LT Switchboard as per
Technical speifications and the Schematic drawings. All panel incomer breakers and bus
coupler breaker (wherever applicable) shall be provided with Potential free contacts for
BMS integration to communicate the status of ON, OFF and Trip of the breakers.
Supply , installation, testing & commissioning of LT panel. This will be floor mounted, free
standing, indoor duty, dust proof, vermin proof, front operated, electrical panel fabricated
as per specifications laid in this document and will be complete with the main and
auxiliary bus bars, interconnection, earth bus and will be powder coated finished with 70
micron. The PCC Panel shall be suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire
supply system. The Panel will be made as per detailed specifications.
Each MCCB shall have front operated handle, indication light for ON, phase barriers,
shrouding of bus.
Incomer: 160 A TPN Motorized breakers 2 nos with indication lamp, protection breaker,
Digital microprocessor based multifunction meter showing all power parameters like (A, V,
KVA, KW, KWH, KVAR, neutral current etc.). These breakers should have manual lock
provided with keys for locking in OFF position
Bus Coupler with lock: 160 A TPN motorized breaker with lock and key arrangement to
keep the breaker in off condition in normal operation. Bus-Coupler should be configured
with two input breakers to provide two-out-of three breakers ON condition.
Bus Bar : A set of TPN Aluminium bus bar rated for 250A (after considering all necessary
deratings) 3 phase 4wire, 50Hz.
Outgoing feeders: 80 A TPN MCB 04 nos (2 for UPS and 2 spare), 63 A 4 P MCB 02 nos,
32 A 4 P MCB 02 nos

1.1.2

40 kVA isolation transformer with K9 rating with enclosure and breaker at input with
busbars for input and out cable termination as per rating.

Nos

nos

1.1.16

1.2

1.2.1
A
1.2.2
A
1.3
A
B
C
2.1

A
B
2.2

Emergency Stop Button located remotely (near to the DC main door) to control the Two
Input supplies of Datacenter Main Panel and Two UPS sytems , wall mounted type with
suitable control wirings and accessories required. The Distance between the location of
Push button and the Datacenter main panel will be around 10 Meters and to UPS Room
is 25Mtrs..
FACTORY-BUILT MCB DISTRIBUTION BOARDS:
Supply, store, erection, testing and commissioning of MCB Distribution Boards of type IP43 Protection with Metal Door, wall-mounted (either surface or recessed type)as per
schematic drawings. The erection rates shall include fixing of DB on wall/Column
including supply of all fixing accessories, civil works etc., Space provision shall be made
for mounting ELCB in the incomer MCB. The rate shall be same for any combination of
outgoings (TP/SP).
HORIZONTAL TYPE. DOUBLE DOOR TPN DB :
6 Way TPN DB with seperator Incomer of approved make
SINGLE PHASE DB WITH DOUBLE DOOR :
8 Way DB of approved make
MCB, ELCB, ELMCB
Supply, store, erection, testing and commissioning of the following MCB,s, ELCB,s &
ELMCB,s
motor
6-32 AmpsofSP
MCBduty, C-curve charcterstics Din rail mounted to be fixed in the above
MCB Distribution Boards to suit any required combinations specified in the riser
6-32 Amps DP MCB
diagrams, With all the required accessories. C-curve has to be used for lighting and
6-32
MCB circuits and D-curve to be used for all UPS outgoing circuits.
utilityAmps
powerTPN
distribution
INDUSTRIAL TYPE SOCKETS AND PLUG TOPS
Supply, store, erection, testing and commissioning of factory made metal clad totally
enclosed with cast aluminium housing with industrial socket/interlocked combined rotary
switch and socket with scrapping earth connection and plug top. In case of interlocked
socket, the interlocking should ensure that the plug cannot be inserted or withdrawn while
the switch is in 'ON' position. (all switches & sockets shall be housed in painted MS
boxes). The erection rate shall include supply of angle iron frame work and fixing
accessories such as grip bolts/grouting/ welding to steel structures etc., All the MCBs
shall be of 'D' Curve specifications.
32A, 230V, 2P+E Plastic moulded industrial socket (female type), Overhead cable tray /
Raceways or surface mounted type. The pricing shall include to make the required
cutouts in the Raceways along with required accessories.
16A, 230V, 2P+E Plastic moulded industrial socket, Overhead cable tray / Raceways or
surface mounted type. The pricing shall include to make the required cutouts in the
Raceways along with required accessories.
MODULAR TYPE

Nos

Nos

Nos

14
8
6

Nos
Nos
Nos

20 Each
12 Each

A
B
3.0
3.1

A
C
D
E
F
4.0
4.1

A
B
C
D
5.0

Supply, erection, testing and commissioning of power points by providing following


switches/sockets mounted on suitable size metal coated boxes fixed flush/surface on to
the wall with all fixing and wiring accessories.
6/16 Amps, 5--pin (250 Volts) single phase universal socket with 16 Amps single pole
switch with indicating lamp.The pin configuration shall be round type. Plug tops are
excluded from the scope of supply.
3nos. 6 Amps, 5--pin (250 Volts) single phase universal socket with 16 Amps single pole
switch with indicating lamp.The pin configuration shall be round type. Plug tops are
excluded from the scope of supply.
SUB-MAINS/CIRCUIT MAINS/POWER WIRING
Supply and running of 1100 V grade FRLS PVC insulated Aluminum / Copper conductor
wires in 2mm thick FRLS PVC/ MS conduits as per specification titled "DISTRIBUTION
SYSTEM, CONDUITS, WIRING AND ACCESSORIES". The rate shall include all wiring &
conduit accessories as aplicable.
25 mm dia, FRLS PVC conduit with all accessories.
Supply and running of 3C 6 Sqmm FRLS PVC insulated multistrand copper conductor
wire in existing conduits/raceways.
Supply and running of 3C 4 Sqmm FRLS PVC insulated multistrand copper conductor
wire in existing conduits/raceways.
Supply and running of 3 C 2.5 Sqmm FRLS PVC insulated multistrand copper conductor
wire in existing conduits/raceways.
Supply & Running of 3 C 1.5 Sqmm multistrand copper conductor wire in existing
conduits.
POINT WIRING: FOR LIGHT FIXTRURES
POINT WIRING WITH FRLS PVC CONDUITS:
(False / Non False Ceiling Area)
Wiring with 2 x 2.5 Sqmm FRLS PVC insulated 1100V grade copper conductor wires and
1 x 1.5 Sqmm PVC insulated earth wire in 2mm thick, 25mm dia FRLS PVC conduits as
per specification titled "DISTRIBUTION SYSTEM, CONDUITS, WIRING &
ACCESSORIES". The rate shall include necessary accesories.
(SWITCHES & SOCKETS SHALL BE OF MODULAR TYPE)
Single light point controlled by 6 Amps switch (conduit / wires / switches)
Two light point controlled by 6 Amps switch (combined rate for two points)
Three light point controlled by 6 Amps switch (combined rate for three points)
Single light point controlled by 2 Nos. of 6 Amps switch (2 way switch) (conduit / wires /
switches)
LT CABLES WITH END TERMINATIONS

6 Each
3 Each

250

Mtr

100

Mtr

100

Mtr

50

Mtr

100

Mtr

2
4
2

No.
No.
No.

Rate Only

No.

A
B
C
5.1
A
B
C
5.3
A
B
5.1
A
B
C
6.0

6.1
6.3
6.4
6.6
7.0

3 1/2 core, 240 sq mm Aluminum Armoured cable for input to Data Centre electrical panel
from TISS electrical panel.
3 1/2 core, 120 sq mm Aluminum Armoured cable for input to Data Centre electrical panel
from TISS electrical panel.
3 1/2 C x 10 Sq mm (Lighting and BMS)
1.1kV, Copper Conductor, PVC Insulated, Unarmoured, flexible LT Cable
1C X 25 Sqmm
3 1/2 C x 16 Sq mm (PAC Input)
3C x 6 Sqmm
Supplying and providing the end terminations with copper lugs for all the above cables
with Double compression brass cable glands, taping, crimping, gland and armour
earthing, etc. complete as required.
3 1/2 core, 240 sq mm Aluminum Armoured cable for input to Data Centre electrical panel
from TISS electrical panel.
3 1/2 core, 120 sq mm Aluminum Armoured cable for input to Data Centre electrical panel
from TISS electrical panel.
1.1kV, Copper Conductor, PVC Insulated, Unarmoured, flexible LT Cable
1C X 25 Sqmm
3 1/2 C x 16 Sqmm
3C x 6 Sqmm
EARTHING
Supply & installation of the following with clamps, inspection chambers, excavation, refill
with soil, charcoal, salt, compound as per technical specifications & IS standards.
Complete. The cost shall include excavation, bacfilling, compaction, construction of
chambers & all required civil works.
25 x 6 mm GI Strip
25 x 6 mm Cu. Strip with Green sleeves
6 sq mm Green copper cable conductor
600x600x3.15mm Copper plate electrode earth station.The chamber size shall be 450 x
450 mm with C.I. Cover plate. The identification number shall be provided both inside
and outside.
SUPPLY & INSTALLATION OF INDOOR LIGHTING FIXTURES
Supply, Erection, Testing & Commissioning of the following light fixtures complete with
Energy Efficient Electronic Ballast, Control gear and all the other standard accessories
along with High effiecient "T5" or Equivalent Tubes / Lamps.

20

Mtr

300

Mtr

40

Mtr

200
60
40

Mtr
Mtr
Mtr

No.

No

16
32
16
8

No
No
No
No

120
100
75

Mtrs
Mtrs
Mtrs

Nos

NOTE
1.1
A
B
8.0
8.1

8.2

8.3

A
B
A

CFL Shall be with PF improvement condensor. Tubes shall be of colour 84 (cool


day light).
INDOOR LIGHT FIXTURES
2x28W Surface mounted/Suspended type lighting
luminiare suitable for28W T5
fluroscent Lamps with suitable reflector. Philips makeTMS 122/228 or Approved
equivalent. The cost shall includes the lamp and all required accessories.
2x36W Recess mounted, square type luminaire suitable for 2x36W CFL Lamps. Philips
make FBS 470/236 or approved equivalent. The cost shall includes the lamp and all requ
ired accessories.
MISCELLANEOUS
STEEL ITEMS
Supply,fabrication,erection & epoxy painting of steel items as required as per
specification complete, Generally steel items include cable tray, cable tray supporting
arrangements,MS Channels-(ISMC),Angles,Plates and any other steel items not covered
in other items of schedule of quantities. The cable trays shall be as per specification titled
"CABLE TRAYS" and shall be of ladder made of angles and flats / sheet steel folded
type . The rate shall also include painting with two coats of red oxide and primer and two
coats of synthetic enamel paint of approved shade.
LADDER TYPE CABLE TRAYS(GI TRAYS)
Supply & erection of the following sizes ladder type cable tray, Hot dip galvanized made
of 14 SWG GI sheet with two coats of red oxide primer and finished with good quality
paint with necessary supports. brackets,angle iron,suspension are measured separately
the heading "Steel Items".
PERFORATED TYPE CABLE TRAYS(GI TRAYS)/ WIREWAYS
Supply, erection, testing & commisioning of the following sizes prefabricated perforated
type cable tray made of 14 SWG GI sheet with two coats of red oxide primer and finished
with good quality paint with necessary supports, brackets,angle iron,suspension are
measured separately the heading "Steel Items".
300 (W) x 50 (H) x 2mm (T)
300 (W) x 100 (H) x 2mm (T)
WIREWAYS WITH COVERS
150 x 150 x 2mm Wire ways with covers suitable to mount 2 nos of 32A, 1Ph industrial
sockets at every 600mm intervals. The rate shall include for making the provision for
mounting the industrial sockets.

8 Each
3 Each

0.75

M.T.

50
50

Mtr
Mtr

20

Mtr

8.4

Supply & installation of following :


Rubber mats, first aid box, danger boards, shock treatment charts and other sundry items
(sizes/capacities to be got approved).
GRAND TOTAL

L/S

S.N.
A

2
3

Bill Of Material for Precision Air conditioning work


Description
Supply of PAC Indoor and Outdoor units
Supply,of micro processor based DX based Precision Air
conditioning unit FLOOR DISCHARGE, Top suction
indoor unit with Dehumidification feature. (1 working + 1
standby configuration) Precision Air conditioning units,
Units should have high sensible heat ratio of more than
90% . Dirty Filter alarm should be part of the system.Units
should be equipped with electronic expansion valve &
backward curved direct driven EC fans
Inside Conditions - 22+/- 1 Deg C & 50+/- 5 % RH and 40
Deg C ambient
Supply of 10 TR Capacity Floor Discharge Type
Precision AC Unit- with tandem compressor (with Heater,
Humidifier, Electronic Expansion Valve)
Model No.
TDAV 1021

Qty

Unit

Nos

Nos

40

RMT

30
30
15
2

RMT
RMT
RMT
Nos

Nos

300

sq ft

Nos

2
2

Nos
Nos

Lot

Supply of Low side items


Indoor Unit stands with height adjustable and suitable for
raised floor
Copper cabling interconnection between the outdoor and
5
indoor Units ( Power supply)
Hard Drawn Copper Piping between Indoor & Out Door
unit of Suitable Size including all fitting & accessories.
6
Copper Piping should be suitably supported at regular
intervals.
a
5/8" or equivalent
b
7/8" or equivalent
7
G.I Drain piping connection as required B class
8
M.S Mounting Frame for Outdoor units
Supply & Fixing of Powder coated AL Air grills 600 x 600
9
mm
10
Floor insulation with 9mm thick nitrile rubber insulation
Supply of R407 C refrigerant gas per unit as per length
11
mentioned above ( Pl provide cal for gas)
12
Installation & Commissioning
13 Active Tiles
AFPS (automatic flooor pressurisation system) with
sensors to sense underfloor air pressure and give
14 input to EC fans of PAC to modulate air delivery for
maintaining constant pressure below raised floor.
The price shall include cable also.
4

Bill of Material for UPS system


Sr No Description
APC Smart-UPS VT rack mounted 40kVA 400V w/5 batt mod.,
1 w/PDU & startup
2 NetShelter SX 42U 600mm Wide x 1070mm Deep Enclosure
3 NetShelter SX 42U 750mm Wide x 1070mm Deep Enclosure
Rack PDU,Basic, Zero U, 16A, 230V, (20) C13 & (4) C19; IEC
4 C20
5 Rack PDU, Basic, Zero U, 32A, 230V, (20)C13 & (4)C19
Cable Ladder 12" (30cm) Wide w/Ladder Attachment Kit
6 (AR8166ABLK)
7 Cable Trough, Open Bottom, 600mm
8 Cable Trough, 600mm
9 Cable Trough, 750mm
10 Data Cable Partition, NetShelter, 600mm Wide
11 Data Cable Partition, NetShelter, 600mm Wide, pass-through
12 Data Cable Partition, NetShelter, 750mm Wide
13 Data Cable Partition, NetShelter, 750mm Wide, pass-through
14 5X8 Scheduled Assembly of 1-3 Additional Racks
15 5X8 Scheduled Assembly Service for 1-5 Racks
16 shifting , loading and unloading of Exisiting UPS
17 Reinstallation of Existing 40KVA UPS
18 Reinstallation of Existing 6KVA UPS

Part #

UOM

SUVTR40KH5B5S
AR3100
AR3150

1
5
1.00

AP7552 / AP7551
AP7553

8
4

AR8165ABLK
AR8560
AR8561
AR8571
AR8162ABLK
AR8163ABLK
AR8172BLK
AR8173BLK
WASSEM5X8-3R-PX-10
WASSEM5X8-5R-PX-20
QWPRJ
QWPRJ
QWPRJ

1
2.00
5.00
1.00
7.00
7.00
1.00
1.00
1.00
1.00
1
1
1

BOQ Integrated Building Management Solution


Sl.No
A
1
2
3
4
5
6
7
8
B

1
2
3
4
C

1
2
3
4
5
6
7
8

Item description
UOM
Conventional Fire Alarm Systems
Supply and installation of Conventional 4 Zone Fire Alarm Panel , batteries
Nos.
etc. with 4 line auto dialer with recording message capacity .
Supply and installation of Conevntional photoelectric /Optical type smoke
Nos.
detectors with base.
Supply and installation of Manual call Points with base.
Nos.
Supply and installation of Conventional Electronic's Hooter cum Strobe
Nos.
Supply and installation of Response Indicator
Nos.
Fire Exit Signage boards with 3hrs battery backup
Nos.
Single side glow signage (100mm X 300mm)
Nos.
Supply and installation of 2 core 1.5Sq.mm Armoured FRLS cable.
Nos.
TOTAL
VESDA
Supply, Installing, Testing & Commissioning of the below as per
specifications:
Single zone Very early smoke detection panel (VLF 250)
Nos.
Power Supply Unit with Enclosure
Nos.
Aspiration Tubes, Capilary Tubes, Nozzles, accessories, etc.
Lot
25mm PVC Conduit
Mts.
TOTAL
FM-200 Gas Suppression System
FM-200 / HFC227 Gas Based Fire Suppression System - 42 Bar
System Only
80 Ltr.Seamless Cylinder CCOE Approved, complete with valve assembly.
Nos.
With Cylinder Strap.
HFC227 Gas (1,1,1,2,3,3,3 Hepta fluro propane) manufactured by GLCC
Nos.
or Dupont USA.
Electric Actuator
Nos.
Pneumatic Actuator
Nos.
Discharge Nozzles
Nos.
Master Cylinder Adapter Kit used to actuate the Slave Cylinder.
Nos.
Manual Actuator
Nos.
Flexible discharge Hose
Nos.

QTY

Makes

Ravel/Securico

System Sensor

4
2
5
1
1
150

System Sensor
Agni
STAR
STAR
STAR
Polycab/Technoflex

1
1
9
25

Xtralis
STAR
STAR
Precision/Ashoka

Kidde

50

Kidde

1
1
6
1
1
1

Kidde
Kidde
Kidde
Kidde
Kidde
Kidde

9
10
11
12
13
D

1
2
2
3
4
E
1
2
3
4
5

Cylinder Straps
Flexible Actuation Hose
Piping ASTM Grade A 106 Sch. 40 with fittings & supports
Manual Abort Station
Manual Release Station
TOTAL
Water leak detection system
Supply, Installing, Testing & Commissioning of the below as per
specifications:
2 Zone Water Leak detection Panel with LCDlLED display, power supply
and Water Leak detection Module resistant to oxidation and erosion having
a relay output for connection to the controller.
10mtrs. Water Leak Detection Sensing cable
15mtrs. Water Leak Detection Sensing cable
Sounder
Supply and surface laying of 2Cx 1.0
sq.mm Armoured Cable
TOTAL
Rodent Repellent System
Master Console capable of connecting to 12 Satellites complete with all
accessories as per specifications.
Satellite Units complete as per the specification
Rodent Cables
Bracket Stand
Supply & laying of 20mm PVC conduit
TOTAL

Nos.
Nos.
Nos.
Nos.
Nos.

2
1
1
1
1

Kidde
Kidde
STAR
Ravel
Ravel

Nos.

STAR

Nos.
Nos.
Nos.

1
1
1

STAR
STAR
STAR

Mtr

25

Polycab/Technoflex

Nos.

STAR

Nos.
RM
No.
No.

8
100
1
100

STAR
STAR
STAR
Polycab/Technoflex

SL No.

1
2
3
4
5
6
7
1
2
3
4
5
6

Description
Connectivity between Network rack & Server rack
at data center.
Cat 6A STP Patch cord, White, 2 Meter
10G, 24 Port Un loaded straight Jack Panel, 1U
Cat 6A AMP-TWIST 6S SL die-cast Jack without Dust
Cover
Cat 6A UTP Cable - Roll of 305 Mtrs, PVC
Cat 6A STP Patch cord, White, 2 Meter
Cat 6A STP Patch cord, White, 3Meter
2U Double sided Cable manager with Hinged door
system
Services
Laying of Cat 6A Cables
Termination of cables onto 24 port patch panels
Testing of cat 6A cables.
Integration of racks
Labelling & documentation of network ports
Project management charges

UOM

QTY

Nos
Nos

168
14

Nos

336

Nos
Nos
Nos

8
118
50

Nos

Mtrs
No's
No's
No's
Lot
Lot

2440
14
168
6
L/s
L/s