TEST REPORT
OF
MODEL EG3690 GRAVIMETRIC COAL FEEDERS
UPGRADATION WITH 196 NT CONTROLLER AND
VFD.
FOR NTPC RAMAGUNDAM STAGE-1 UNIT-1
Job No.- 1221/NTPC-STAGE-1
Date: 25/01/2014
1E
1F
Description
1E
1F
432
424
439
425
431
424
428
423
433
425
433
427
430
426
433
423
429
422
127.8
127.7
127.2
127.1
126.8
126.5
121.7
121.6
121.4
121.1
120.8
120.9
116.2
115.5
115.1
114.8
114.6
114.5
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
23.96
23.97
23.97
24.03
24.01
23.96
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
98 VAC 132
DC Voltage Measurements
Unregulated Voltage
Regulator U1
Regulator U2
1A
1B
1C
1D
1E
1F
9.88
9.88
9.82
9.76
9.80
9.75
5.12
5.18
5.10
5.19
5.16
5.16
10.22
10.25
10.01
10.10
10.24
10.26
4
-10.20
-10.16
-10.12
-10.16
-10.13
-10.14
14.83
14.86
14.89
14.90
14.87
15.07
-15.12
-15.06
-15.12
-15.07
-15.05
-14.97
a. With power applied, verify that only the display and the OFF LED is illuminated.
b. Press SELF TEST 04 keys. Verify that all displays and LEDs are illuminated for
a. Check the operation to properly actuate coal on belt level sensor. (LSFB)
Regulator U3
Regulator U4
Regulator U5
Measure the -10 volt supply at test point TP8 with reference to
digital ground, TP9. The voltage should be 10.00 to 10.25 V dc.
Measure the +15 volt supply at test point TP5 with reference to
digital ground, TP6. The voltage should be +14.25 to +15.75V dc.
Measure the -15 volt supply at test point TP4 with reference to
digital ground, TP6. The voltage should be 14.25 to -15.75 V dc.
five seconds.
2.3 Feeder Parameter Check
a. Check the set-up parameters by referring to the MICROPROCESSOR
CONTROLLER FEEDER DATA SHEET. To exit the set-up mode, press the OFF or
EXIT key.
2.5
Address
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Final Value
4.00 mt/h
4.00 t/h
1000.00
1000.00
881 kg/cum
881 kg/cum
0.00
0.00
2.00
2.00
40 Mt/h
28 mt/h
4 mt/h
10 mt/h
100 kg
100 kg
1.00
1.00
0.9144 m
112.700 cm
0.1720 cum
0.1730 cum
0.9144 m
112.713 cm
34 kg
31.100 kg
4000.00
4000.00
8000.00
8000.00
2.00
2.00
0.00
0.00
0.00
0.00
4.00
8.00
2.00
4.00
0.150
0.150
5.00
6.00
0.00
2.00
0.00
0.00
0.00
0.00
10 hz/mtph
10 hz/mtph
5.00
5.00
1430.00
1445.00
100.00
100
0.00
0.00
0.00
0.00
0.00
2.00
0.00
0.00
0.10 sec
0.10 sec
4.300 LBS/IN
4.300 LBS/IN
ParameterNumber
E 196
B 040
B 041
B 042
MOTOR NP FLA
B 043
MOTOR NP Hertz
B 044
MOTOR NP RPM
B 045
MOTOR NP POWER
MOTOR NP POWER
UNITS
MOTOR OL Hertz
MOTOR OL Factor
MOTOR POLES
TORQUE PERF MODE
SPEED
MODE/FEEDBACK
SELECT
MINIMUM SPEED
MAXIMUM SPEED
OVERSPEED LIMIT
SPEED REF A SEL
SPEED REF A Hi
SPEED REF A LO
TB MAN Ref Sel
ACCEL TIME-1
ACCEL TIME-2
DECEL TIME-1
DECEL TIME-1
PWM FREQUENCY
STOP MODE A
STOP MODE B
DIRECTION MODE
ANLG IN CONFIG
ANLG IN SQR ROOT
ANALOG IN 1 HI
ANALOG IN 1 LO
ANALOG IN 1 LOSS
ANALOG IN 2 HI
ANALOG IN 2 LO
ANALOG IN 2 LOSS
ANALOG OUT
CONFIG
ANALOG OUT
CONFIG
ANALOG OUT1 SEL
ANALOG OUT1 HI
ANALOG OUT1 LO
ANALOG OUT1
SCALE
DIGITAL IN1 SeL
DIGITAL In2 SeL
DIGITAL In3 Sel
DIGITAL OUT1
DIGITAL OUT2 SEL
B 046
B 047
B 048
B 049
B053
C 080
C 081
C 082
C 083
C 090
C 091
C 092
C 096
D 140
D 141
D 142
D 143
D 151
D 155
D 156
D 190
J 320
J 321
J 322
J 323
J 324
J 325
J 326
J 327
J 340
Parameter Name
J
J
J
J
341
342
343
344
J
J
J
J
J
J
354
361
362
363
380
384
Default
Setting
OPEN LOOP
ANALOG IN 2
ANALOG IN 1
RAMP
COAST
UNIPOLAR
VOLT
VOLT
DISABLED
VOLT
VOLT
DISABLED
XXXX XX00
XXXX XX00
0
10.00VOLT
0.00VOLTS
0
8
5
18
1
4
ADVANCED
INDUCTION
7.8
50
1445
5HP
0
55.0Hz
1
4
0
0
2.5Hz
50Hz
0.0Hz
1
50Hz
0.0Hz
2
3.0 SEC
10.0 SEC
3.0 SEC
10.0 SEC
4 KHZ
0
0
0
XXXX XX11
XXXX XX00
20.000mA
4.000mA
0
10
0
0
HORSEPOWER
SENSRLS VECT
OPEN LOOP
ANALOG IN 1
ANALOG IN 2
COAST
COAST
UNIPOLAR
SET INPUT LO
SET INPUT LO
XXXX XX01
OUTPUT FREQ
START
AUTO/MANUAL
FAULT
RUN
XXXX XX01
2
20.000mA
4.000mA
15.6
8
9
0
4
1
OUTPUT FREQ
RUN FORWARD
RUN REVERSE
NOT USED
RUN
FAULT
1E
1F
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
0.5
0.5
0.5
0.5
0.5
0.5
0.49
0.49
0.49
0.49
0.49
0.49
0.5
0.5
0.5
0.5
0.5
0.5
Description
Feeder No.
1C
1D
1A
1B
1265
1322
1218
10088
9855
10132
1E
1F
1320
1227
1268
10062
10050
10207
a. A1 Card 0% Input.
Press
Press
100%.
Press
c. A2 Card 0%
10
key to
or
203.3
202.5
201.6
200.8
203.0
200.2
1022.6
1017.4
1008.9
1007.2
1019.0
1003.8
197.4
199.2
199.5
196.7
199.2
994.1
986.3
key to store
d. A2 Card 100%
Press
100%. Press
or
e. A3 Card 0%
key, and
key to
press the
or
mA.
Press
199.5
f. A3 Card 100%
Press
100%. Press
990.9
Press the
mA.
Press
or
11
997.0
997.1
993.8
1E
1F
12
Feeder
Numb
er
1A
1B
1C
1D
1E
1F
CALCULATED
DENSITY =
VOLUMETRIC K4
J1
J2
J1
J2
ACTUAL
4886
4510
4930
4388
4978
4866
4920
4610
4835
4499
4812
4919
1951
2015
1992
2085
1961
1890
1986
2060
2045
2133
2091
1884
354.2
362.8
348.2
356.8
351.4
359.9
13
1A
SELF TEST
NUMBER
DESCRIPTION
Number Of Good Readings /
Deviation
0.24%
0.119%
0.213%
SPECIFICATION
Self Test #1
Tare Factor
3938922
3960622
3968950
% Error
0.03%
-0.24%
0.21%
0.25%
Self Test #2
Belt Travel
0.12305
0.12329
0.12319
% Error
-0.11%
0.04%
-0.08%
0.25%
Span Factor
0.223%
1.3861 e-05
0.027%
1.3929e-05
0.24%
1.4102 e-05
% Error
-0.06%
0.22 %
0.04%
0.25%
6.543 M
6.555 M
6.550 M
% Error
-0.19%
0.04%
-0.08%
0.25%
1B
SELF TEST
NUMBER
DESCRIPTION
Number Of Good Readings /
Deviation
0.172%
0.24%
0.151%
SPECIFICATION
Self Test #1
Tare Factor
4276620
4034566
3888119
% Error
-0.02%
0.12%
0.01%
0.25%
Self Test #2
Belt Travel
0.09747
0.12030
0.12028
-0.03%
0.15%
0.05%
0.25%
% Error
0.10%
0.13%
0.208%
Self Test #3
Span Factor
1.4245e-05
1.4794e-05
1.4045e-05
% Error
-0.21%
-0.10%
-0.00%
0.25%
5.298M
6.544 M
6.543 M
% Error
-0.03 %
0.23%
0.05%
0.25%
14
1C
SELF TEST
NUMBER
DESCRIPTION
Number Of Good Readings /
Deviation
0.162%
0.177%
0.177%
SPECIFICATION
Self Test #1
Tare Factor
2886179
3734748
3824656
% Error
0.04%
-0.25%
-0.10%
0.25%
Self Test #2
Belt Travel
0.12328
0.12329
0.12335
% Error
0.00%
-0.00%
0.00%
0.25%
0.209%
0.114%
0.244%
Self Test #3
Span Factor
1.3618e-05
1.3745e-05
1.3964e-05
% Error
-0.08%
-0.08%
-0.12%
0.25%
6.524 M
6.529M
6.533M
% Error
0.00%
-0.00%
0.15%
0.25%
1D
SELF TEST
NUMBER
DESCRIPTION
Number of Good Readings /
Deviation
0.18%
0.236%
0.227%
SPECIFICATION
Self Test #1
Tare Factor
3439631
4369921
4362967
% Error
-0.14%
0.14%
-0.16%
0.25%
Self Test #2
Belt Travel
0.12230
0.12230
0.1223
% Error
-0.17%
-0.13%
0.00%
0.25%
0.248%
0.224%
0.233%
Self Test #3
Span Factor
1.4191e-05
1.3861e-05
1.3846e-05
% Error
-0.02%
-0.07%
-0.11%
0.25%
6.560M
6.560M
6.565 M
% Error
-0.17 %
-0.13%
-0.08%
0.25%
15
1E
SELF TEST
NUMBER
TEST #2
TEST #3
TEST #4
SPECIFICATION
DESCRIPTION
0.123%
0.101%
0.149%
Self Test #1
Tare Factor
2627160
3647833
3672980
% Error
0.19 %
0.04%
-0.11%
0.25%
Self Test #2
Belt Travel
0.12397
0.12396
0.12391
% Error
0.03 %
0.00%
-0.05%
0.25%
0.174%
0.16%
0.159%
Self Test #3
Span Factor
1.1069e-05
1.3139e-05
1.2853e-05
% Error
0.03%
0.02%
-0.13%
0.25%
6.512 M
6.510 M
% Error
0.00%
-0.05%
0.25%
1F
SELF TEST
NUMBER
DESCRIPTION
Number of Good Readings /
Deviation
6.513 M
0.11%
0.218%
0.146%
0.224%
SPECIFICATION
Self Test #1
Tare Factor
4481226
4298198
4343221
% Error
0.12%
0.00%
-0.06%
0.25%
Self Test #2
Belt Travel
0.12177
0.12169
0.12186
% Error
-0.04%
-0.09%
0.08%
0.25%
Span Factor
0.245%
1.3054e-05
0.193%
1.3334e-05
0.224%
1.3440e-05
% Error
-0.02%
-0.03%
-0.2%
6.475 M
6.470 M
6.479 M
% Error
-0.04%
-0.01%
0.00%
0.25%
0.25%
Feeder Simulation Test in REMOTE Mode of Operation from DCS Demand Signal:
16
1A
Demand
Signal
T/Hr
mA
SELF TEST 06
Feed rate
Actual
SELF TEST 06
Motor
A3
Feed rate
Speed (RPM) Feed Rate O/P
Demand
From Display to DCS mA
Power Flex 70
Freq
Volts
Load
(AC)
38
(%)
3.66
0%
4.01
10.00
10.00
443
(Hz)
14.9
25%
8.02
10.00
10.00
443
14.9
95
3.66
50%
11.98
14.00
14.00
616
12
20.7
180
3.36
75%
16.03
21.00
21.00
927
16
31.5
267
3.40
100%
19.99
28.00
28.00
1239
20
41.3
350
3.41
1B
Demand
Signal
T/Hr
mA
SELF TEST 06
Feed rate
Actual
SELF TEST 06
Motor
A3
Feed rate
Speed (RPM) Feed Rate O/P
Demand
From Display to DCS mA
Power Flex 70
Freq
Volts
Load
(AC)
40
(%)
3.36
0%
4.00
10.00
10.00
465
(Hz)
15.7
25%
8.05
10.00
10.00
443
15.7
100
3.36
50%
12.03
14.00
14.00
651
12
21.7
185
3.35
75%
16.09
21.00
21.00
972
16
32.6
280
3.40
100%
20.84
28.00
28.00
1300
20
43.6
355
3.42
17
1C
Demand
Signal
T/Hr
mA
SELF TEST 06
Feed rate
Actual
SELF TEST 06
Motor
A3
Feed rate
Speed (RPM) Feed Rate O/P
Demand
From Display to DCS mA
Power Flex 70
Freq
Volts
Load
(AC)
35
(%)
3.66
0%
4.02
10.00
10.00
440
(Hz)
14.8
25%
8.04
10.00
10.00
440
14.8
93
3.66
50%
12.00
14.00
14.00
616
12
20.7
179
3.36
75%
16.09
21.00
21.00
925
16
31.5
267
3.40
100%
20.01
28.00
28.00
1234
20
41.4
349
3.41
1D
Demand
Signal
T/Hr
mA
SELF TEST 06
Feed rate
Actual
SELF TEST 06
Motor
A3
Feed rate
Speed (RPM) Feed Rate O/P
Demand
From Display to DCS mA
Power Flex 70
Freq
Volts
Load
(AC)
37
(%)
3.33
0%
4.02
10.00
10.00
439
(Hz)
14.8
25%
8.04
10.00
10.00
439
14.8
93
3.33
50%
12.00
14.00
14.00
626
12
21.7
180
3.35
75%
16.09
21.00
21.00
931
16
31.0
276
3.36
100%
20.01
28.00
28.00
1236
20
41.4
355
3.36
18
1E
Demand
Signal
T/Hr
mA
SELF TEST 06
Feed rate
Actual
SELF TEST 06
Motor
A3
Feed rate
Speed (RPM) Feed Rate O/P
Demand
From Display to DCS mA
Power Flex 70
Freq
Volts
Load
(AC)
37
(%)
3.26
0%
4.00
10.00
10.00
450
(Hz)
15.1
25%
8.02
10.00
10.00
450
15.1
96
3.26
50%
12.01
14.00
14.00
629
12
21.1
185
3.33
75%
16.02
21.00
21.00
945
16
31.7
278
3.34
100%
20.00
28.00
28.00
1264
20
42.3
360
3.45
1F
Demand
Signal
T/Hr
mA
SELF TEST 06
Feed rate
Actual
SELF TEST 06
Motor
A3
Feed rate
Speed (RPM) Feed Rate O/P
Demand
From Display to DCS mA
Power Flex 70
Freq
Volts
Load
(AC)
37
(%)
3.24
0%
4.10
10.00
10.00
448
(Hz)
15.0
25%
8.00
10.00
10.00
448
15.0
97
3.24
50%
11.98
14.00
14.00
631
12
21.0
184
3.29
75%
16.02
21.00
21.00
944
16
31.0
277
3.30
100%
20.03
28.00
28.00
1255
20
42.0
359
3.31
19