SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

3.1 GENERAL

MC 3 T TRUNG TH & CC THIT B LIN QUAN

3.1 TNG QUT

This part of the Specification covers the design,

Phn ny cp r v thit k, nh sn xut, vn

fabrication, delivery, installation, testing and


commissioning of high tension switchgear and

chuyn, lp t, kim tra, v thm nh cc thit b


ng ct v chuyn mch cao th c cung cp

switchboards to be supplied and installed by the

v lp t bi nh thu.

Sub-Contractor.
this

Nh thu s ch rng c im k thut ny ca

Specification is based on sulphur hexafluoride

The

Sub-Contractor

my chuyn mch ny da trn my ct bng hp

(SF6) switchgear. The Sub-Contractor may offer


vacuum switchgear as an alternative provided

cht sulphur hexafluoride (SF6). Nh thu c th s


dng my ct chn khng thay th nhng phi

that the space requirements are complied with.

m bo khng gian yu cu. Trong trng hp

In this case, full technical specification of the


proposed switchgear shall be submitted by the

ny, nhng c im k thut ca my c thay


th s c xem xt bi Qun l K thut.

Sub-Contractor

to

shall

note

the

that

Engineer

for

consideration.
The H.V. switchgear shall be rated at min. 400

My ct cao th s c gi tr thp nht l 400 amp,

amp, 24 kV indoor single busbar, air-insulated,

24kV trn mt thanh ci, loi cch ly chn khng,

metal-clad SF6 or Vacuum type.

lp kim loi SF6 hay loi chn khng.

Type-test certificates of the circuit breaker and

Giy chng nhn kim nh ca CB v my ct s

switchboards shall be submitted with the Tender.


The results of all type tests shall be recorded in

c trnh cng vi gi thu. Tt c cc kim tra


s ghi nhn y cc thng s trong bin bn

type-test reports containing sufficient data to

kim tra xc nhn ng cc ch tiu. Ton b

prove

Specification.

nhng chi tit kim tra s c trnh ln Qun l K

Complete details of type tests shall be submitted


for inspection when requested by the Engineer

thut thm nh khi c yu cu trong qu trnh


m thu. Thng tin k thut v ti liu bng Anh

during tender assessment. Appropriate technical

ng phi trnh cng vi gi thu. Giy chng

information and literature in English language


must be submitted with the Tender. Type-test

nhn kim tra tt nht l c cp bi Hi ng


kim nh Association of Short-Circuit Testing

certificates shall be issued preferably by the

Authorities (ASTA). Giy chng nhn cp bi t

Association of Short-Circuit Testing Authorities

chc khc ch c chp nhn nu kim tra bi c

(ASTA). Test certificates issued by other


organisations will only be accepted if the testing

quan c thm quyn theo tiu chun tng ng


ASTA.

compliance

with

the

authority is established as being of equal


standing as ASTA.
3.2 THNG S NH MC

3.2 RATING
The ratings of the switchgear shall be as
follows:-

Nhng gi tr ca my ct s tun theo cc thng


s nh sau:

Rated voltage :

24 kV 3 Phase

in p nh mc :

24 kV 3 Phase

No. of poles :

Three

S cc :

Three

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/1

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

Rated frequency :

50 Hz

MC 3 T TRUNG TH & CC THIT B LIN QUAN

Tn s :

Rated impulse withstand voltage

50 Hz

in p xung kch chu c

to earth and between poles :

gia pha vi t :

125 kV

125 kV

Rated one minute power frequency withstand

in p tn s nh mc gia in p v ni t v

voltage to earth and between poles :

gia cc cc chu ng trong 1 pht :

50 kV

Rated current of circuit breaker :

400/630 A

Dng nh mc ca CB :

Rated current of busbar :

630 A

Dng nh mc ca thanh ci : 630 A

50 kV

400/630 A

Short circuit rating :

25 kA/ 3 sec.

Dng ngn mch nh mc :

25 kA / 3 sec.

Making capacity :

62.5 kA

Kh nng ng (nh) :

Breaking capacity :

25 kA R.M.S.

Kh nng ct ngn mch : 25 kA R.M.S.

62.5 kA

Both the short-circuit rating, making capacity and


breaking capacity, shall apply when the

C hai gi tr dng ngn mch, dung lng ng v


ct mch s c tnh khi CB ang v tr hot

circuit-breaker is being closed in the "SERVICE"

ng SERVICE v s lp t cc thanh ci ni

location and also with the equipment arranged


for busbar earthing and for circuit earthing.

t v mch ni t cng vy.

The panel shall be a dust and damp protected


enclosure to IP5X (BS EN 60529: 1992 -

T in phi c bo v chng bi v m t
theo IP5X (BS EN 60529: 1992 - Specification for

Specification for degrees of protection provided

degrees of protection provided by enclosures (IP

by enclosures (IP code)).

code)).
3.3 T CHUYN MCH TRUNG TH

3.3 SWITCHGEAR PANEL DESCRIPTION


The switchboard shall include the current
transformers, voltage transformers, indicator

T chuyn mch gm c bin dng , bin p, n


bo pha, ng h o dng, o p, kho lin ng v

lamps, ammeters, voltmeters, interlocks and

cc thit b bo v nh trong bn v v c m t

protection equipment as shown on the drawings

trong tiu chun k thut.

and described in the Specification.


3.4 ACCESSORIES

3.4 CC THIT B , PH TNG I KM

The Sub-Contractor shall supply and install the

Nh thu s cung cp v lp t ton b nhng

following

hng mc sau cng vi nhng thit b cn thit

items

complete

with

any

other

accessories necessary for the safe and proper

khc t in hot ng an ton v chnh xc.

operation of the switchboard:a) One set of H.V. test plugs for injection test

a) Mt b kim tra in p cao cho kim tra phun

through the six orifices of the circuit breaker.

thng qua su ci l ca CB.

b) One set of H.V. test plugs for primary


The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

b) Mt b kim tra cao p cho kim tra p ng


u tin s dng ting Anh khi c tranh chp
3/2

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

injection through the V.T. orifices.

MC 3 T TRUNG TH & CC THIT B LIN QUAN

s b thng qua nhng ng V.T.


c) Mt b kho mc vi mi 3 chic cho mi im

c) One set of padlocks each with three keys for

kho.

each padlocking point.


d) One key cabinet for padlocks and keys.

d) Mt t ng v cha kho.

e) Other necessary miscellaneous items such

e) Nhng thit b khc nh in tr, cu ch, b

as heaters, fuses and fuse links for tripping

ng ct cu ch,v.v

protection, terminal board tag blocks etc.


The Sub-Contractor shall supply and install any

Nh thu s cung cp v lp t nhng rle ph,

additional relays, contactors, wiring, fuses,

contactor, dy, cu ch, MCBs, u ni dy v.v

M.C.Bs, wiring termination etc. in the


switchboard supplied to ensure the proper and

c cung cp t in hot ng an ton v


chnh xc.

safe operation of the switchboard.


The switchboard shall be assembled to form a
complete flush fronted switchboard and readily

T in s c lp t thnh mt dy lin pha


trc v c khong trng hai u c th m

extensible at either end.

rng thm.

3.5 GENERAL CONSTRUCTION

3.5 CU TO CHUNG
T s c mt bung cch ly chng li bi v cn
trng c xp lng vo nhau. N c lm t tm

The switchboard shall consist of dust and


vermin-proof cubicles segregated into single tier
compartments. It shall be made from sheet steel

thp c dy ti thiu l 2mm. T phi thch hp

of 2mm minimum thickness. The switchboard

trong tt c cc iu kin bnh thng v khi c s

shall be suitable for all normal and fault


conditions and is to withstand repeatedly without

c v khng b bin dng, hay h hng, sc khi


ng ct CB.

distortion or failure, shocks caused by closing


and opening of the circuit breaker.
Each switchgear unit shall comprise two main

Mi my ct gm hai phn chnh, phn v c nh

portions, a fixed portion housing the busbars,

v thanh ci, bin dng, bin p, rle, n bo pha,

current transformers, voltage transformers,


relays, indicating lamps and instruments and a

v cc thit b khc; phn di ng bao gm b


chuyn mch vi my ct chn khng SF6.

moving portion comprising a carriage complete


with SF6/ vacuum circuit breaker.
A relay and instrument compartment shall be

Ngn ng dng c v rle c t pha trc t

located at the front of the switchgear unit and a

v ca c lp bn l m vo ni t dy v ni

hinged door shall be provided for access to the


internal wiring and terminals. Moulded gaskets of

dy bn trong. m ca c lm t vt liu khng


lo ho. Chiu cao ca t so vi mt sn khng

non-aging material shall be used to provide close

vt qu 1800mm. Tt c t in c chiu cao

sealing. The height of the instrument panel


above floor level shall not exceed 1800mm. All

ngang bng nhau. Cht ca np trn v sau c


thit k d dng thao tc trong tng t ring r

panels constituting a complete switchboard shall

m khng cn m nhng ni ang c in khc.

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/3

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

be equal height. Bolted-on rear and top covers


shall be designed to gain access to individual
circuits without exposing other circuits which
may be live.
All steel metalwork must be treated to prevent

Tt c tm kim loi phi c s l chng r st v

rusting and shall be complete with polyester


powder paint finish. The colour of the panel finish

c sn bng bt polyester. Mu sn s l mu
ca chnh hng. Cc thit b v rle s hon ton l

shall be manufacturers standard. Instruments

mu en. Thanh ci ni t s chy dc mi t

and relays shall be finished in black. A

ni t an ton cho tng phn.

continuous earth bar shall run along each board


for the efficient earthing of all sections.
3.6 SWITCHBOARD LAYOUT

3.6 S SP T T CAO P

The Sub-Contractor shall ensure that sufficient

Bn thu phi m bo khng gian mt trc

space shall be available for both front withdrawal

CB c ko ra d dng v mt sau t u ni

of circuit breakers and rear termination of power


cables.

cp.

A rubber insulating mat of 1m wide in


switchboard length and 3mm thick, complying

Theo BS921, mt tm thm cao su cch in c


chiu rng 1m s tri di theo mt trc t in v

with BS 921, shall be provided in front of the

c b dy 3mm.

switchboard panels.
3.7 BUSBARS AND CONNECTION

3.7 THANH CI V U NI

Busbars and connections of a cubicle shall be of


copper in accordance with BS 159: 1992 -

Thanh ci v s u ni trong mt t phi tun theo


BS 159: 1992 - Specification for high-voltage

Specification

and

busbars and busbar connections and BS 1977:

busbar connections and BS 1977: 1991 Specification for high conductivity copper tubes

1991 - Specification for high conductivity copper


tubes for electrical purposes t bit i vi gi tr

for electrical purposes in respect of current rating

dng in v cht liu u ni.

for

high-voltage

busbars

and material analysis.


Primary busbars shall be contained in a separate

Nhng thanh ci chnh s t trong mt ngn ring

compartment within the switchboard and access

bit trong t in v ch c th tip cn c qua

shall be possible only by means of bolted-on


sheet steel covers which shall be clearly marked

tm thp che bt bulong v c dn cnh bo


BUSBAR. Thanh ci v u ni s nhn thy c

"BUSBARS". Busbars and busbar connections

khi np che v ca m ra tip cn nhng phn

shall not be exposed when covers and doors are

cn li trong t. Thanh ci phi c th ko ra mt

open for access to the remainder of the


switchgear. Busbars shall be readily extensible.

cch d dng.

Each phase conductor of the primary busbars,


including all through joints and tapping

Mi pha ca thanh ci chnh, gm tt c nhng


im u ni t u n cui v b ni ly ngun

connections shall, in addition to being spaced at

s lm tng thm khong cch cho khong trng

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/4

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

such intervals as to give the necessary air

khng gian cn thit cho in p, c cch in

clearance for the voltage rating, be completely

hon ton hay c epoxy bo v thch hp. Khng

insulated or epoxy encapsulated in an approved

c s dng bng cch in.

manner. Taping will not be accepted.


Primary busbars, connections and their supports

Thanh ci chnh, s u ni v nhng thanh gi

shall be of an approved type and shall be


capable of carrying the short-time current

ca chng phi l loi c cho php s dng v


c kh nng chu c dng ngn mch nh mc

associated with their short-circuit ratings for a

trong thi gian ngn mch l 3 giy.

period of 3 seconds.
Where busbar supports use insulation of

Khi thanh gi thanh ci s dng cch in loi c

moulded or resin-bonded material, it shall have a

hay loi nha, chng phi c lp bn chng rt m

durable anti-hygroscopic surface finish with high


anti-tracking properties.

trn b mt.

The connections from busbars in individual units

Cc im ni t thanh ci trong cc b ring l s

shall have a continuous current rating of not less


than that of the equipment comprising the unit.

c dng nh mc lin tc khng nh hn cc thit


b bao gm.

At all points when connections or joints occur,


the busbars and connecting pieces shall be

Ti nhng im chuyn tip hay im ni, thanh ci

tinned or silver-plated and all bolts for joints shall

v nhng u ni s bng thic hay m bc v tt

be of high tensile steel. The resistance of any


length of conductor containing joints shall be no

c bulong phi l thp chu lc. in tr ca dy


dn c u ni khng c ln hn ci c chiu

greater than that of an equal length without a

di tng ng khng c u ni.

joint.
Primary busbars and connections shall be

Thanh ci chnh v u ni phi c nh du r

marked clearly and shall be placed for standard

rng v c t theo th t pha (R), Vng (Y),

phase sequence Red (R), Yellow (Y) and Blue


(B) counting from front to rear, top to bottom or

Xanh (B), tnh t trc ra sau, t trn xung , hay


t tri qua phi khi nhn t pha thit b ng ct c

left to right as viewed from the switching device

kh.

operating mechanism side.


3.8 CIRCUIT BREAKER

3.8 CU DAO T NG (CB)

Circuit breakers shall be 24 kV, 3 phase SF6


types with making capacity, short time current

CB l loi 24kV, 3 pha vi kh nng ng (nh) loi


SF6, gi tr dng in thi gian ngn, chc ning

rating, operating duty of the circuit breaker and

hot ng v hiu sut lm vic phi ph hp vi

the performance of all trip coils in compliance

BS 5311: 1988 - Specification for high-voltage

with BS 5311: 1988 - Specification for highvoltage alternating current circuit-breakers for a

alternating current circuit-breakers cho dung lng


ct l 25 kA rms.

breaking capacity of 25 kA rms.


The moving portion of each circuit-breaker unit

Phn ng ca CB gm mt CB 3 cc c c cu

shall consist of a three-pole circuit-breaker with

hot ng bng c kh, thit b ng ct chnh v

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/5

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

operating mechanism, primary and secondary

ph, cng tc ph, hin th v tr v dy iu khin,

disconnecting

tt c c gn trn mt khung thp chc chn.

devices,

auxiliary

switches,

position indicators and the necessary control

Khung thp v tt c phn kim loi ca phn ng

wiring all mounted on a substantial steel


framework. The framework and all metal parts of

t nhng phn mang in s tch ri vi phn c


in thng qua cc phn c nh. Ni t ca cc

the moving portion apart from current carrying

phn ng s c chp thun bi Qun l K

parts, shall be solidly earthed via the fixed


portion. The earthing of the moving portion shall

thut. C ngha rng s chp thun s c cung


cp cc CB c th thay th v c m bo trong

be to the approval of the Engineer. Mean of

v tr ng trong v tr c nh.

registration shall be provided so that circuit


breakers may be readily placed and secured in
the correct position in the fixed portion.
SF6 circuit breakers shall consist of a cylindrical
mild steel gas enclosure with six individual

SF6 CB gm c mt ng kh thp nh hnh tr gn


6 ng nha tng hp ring l. Trc ko ng ct

sealed epoxy resin bushings. The drive shaft to

cc tip im s i qua mt m kh xoay. Ap sut

the moving contacts shall pass through a rotating

bnh thng ca kh SF6 khng vot qu 4 bar. S

gas seal. The normal pressure of the SF6 gas


shall not exceed 4 bar. The leakage rate of SF6

r r ca kh SF6 s khng vt qu 1% trn 1


vng. CB SF6 c kh nng ct dng din nh mc

gas shall be less than 1% per annum. The SF6

ca n ti mt p sut kh. Mi pha s c nhng

circuit breaker shall be capable of interrupting its


rated normal current at atmospheric pressure.

tip im ng, c nh, nhng tip im khng c


h quang in.

Fixed and moving contacts, complete with arcing


contacts, shall be provided for each phase.
3.9 OPERATING MECHANISM

3.9 C CU C KH

The circuit breaker shall be provided with motor


charged spring, electrical closing, mechanical

CB c m t sc dng l xo, cun dy ng, phn


c kh ng bng tay, thit b ct bng in v bng

hand close, electrical shunt trip and mechanical

tay, cc cun ct bng tay v bng in. Mt b

hand trip facilities. A 4-digit operation counter


shall be provided to register the number of

m s ln hot ng vi 4 ch s.

operations.
The mechanism shall be trip-free type so that the
circuit-breaker shall be free to open during the

Phn c kh l loi t ct CB ct ngay lp tc


nu ng CB khi cun ct ang hot ng. CB phi

closing operation immediately its tripping device

c kh nng ng hon ton v gi li ti gi tr

operates. The circuit breaker shall be capable of


closing fully and latching against its rated making

dng nh mc ca n. CB cn c kh nng ng,


m chm bng tay thun li cho vic bo tr. CB

current. Facilities shall be provided for manual

cng s c mt s tin dng khc c thit k

slow closing and slow opening of the circuit

nhng khng s dng n khi CB a vo s dng

breaker for maintenance purposes. The circuit


breaker shall be so designed that these facilities

hay b tr ni t.

cannot be used when the circuit breaker is in the


service or earthing position.
The protective circuit shall be suitable for
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

Mch bo v s hot ng c t in p 30V DC


u tin s dng ting Anh khi c tranh chp
3/6

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

operation from a 30V D.C. battery supply.

MC 3 T TRUNG TH & CC THIT B LIN QUAN

cung cp t bnh ac quy.

The following coils shall operate continuously

Nhng cun dy sau s hot ng c lin tc ti

with their coils at an ambient temperature of


40oC, over a voltage range as follows:-

nhit 40 C, cp in p hot ng nh sau:

Spring charge motor:

85 - 110% of nominal
supply voltage

M t sc : 85 - 110% in p nh mc

85 - 110% of nominal

Cun dy ng : 85 - 110% in p nh mc

Closing solenoid:

supply voltage
Shunt trip release coil: 70 - 100% of nominal
supply voltage

Cun dy ct : 70 - 100% in p nh mc

Auxiliary switches shall be provided to interrupt


the closing supply or the tripping supply when the

Nhng tip im ph c s dng tng v tr


ring ca CB khi c ng hay m.

operation of closing and tripping respectively has


been completed.
All operating coils for use on the D.C. supply

Tt c cun dy hot ng phi s dng ngun DC

shall be connected so that failure of insulation to

trnh cun dy hot ng khi cch in i vi

earth does not cause the coil to become


energised.

t b h.

Tripping and closing circuits shall be provided


with fuse in each pole on each unit and shall be

Mch ng ct phi c cu ch bo v cho mi cc


v ring r vi nhau v vi nhng mch khc.

independent of each other and all other circuits.


Approved,
positively driven mechanically
operated indicating devices shall be provided to

Thit b hin th v tr lm vic ca CB c trang b


xc thc n ang m hay ng, kim tra,

indicate whether a circuit breaker is in the open

cch ly khi mch hay c ni t.

or closed service, isolated, test or earthed


positions.
3.10 ISOLATING DEVICES AND SHUTTERS

3.10 THIT B CCH IN V NHNG L CHN

When isolation is effected by withdrawal of the

Khi CB c ko cch ly ra khi mch, s c

circuit breaker, provision shall be made for

nhng hin th ch r tng trang thi v tr hot

positively locating the circuit breaker in the


service, isolated and earthing positions. Stops

ng ca CB, v tr cch ly v ni t. S c v tr
dng trnh CB khng b ko ra qu mc v mi

shall be provided to prevent over-travel and each

v tr s c hin th r rng. Mt nm xoay bng

position shall be clearly indicated. A mechanical

c kh s c s dng khi tng v tr ca CB c

selector mechanism shall be utilised such that


when a particular position is selected it is

chn, CB khng th t vo nhng v tr no


khc c.

impossible to locate the circuit-breaker in any


other position.
Isolating devices shall incorporate self-aligning
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

Thit b cch ly s lin kt vi nhng tip im t


u tin s dng ting Anh khi c tranh chp
3/7

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

contacts, the fixed contact of which shall be such

sp xp, tip im c nh, d dng kim tra

that

trong cng tc bo tr.

access

can

readily be obtained

for

maintenance purposes.
Metal shutters shall be provided to completely

L chn kim loi c trang b che chn nhng

shroud

the

tip im cch ly c nh vi thanh ci ca CB v

circuit-breaker busbar and feeder circuit. These


shutters shall be opened and closed

ca mch. Nhng l chn ny s ng, m t ng


khi di chuyn CB v ngn khng tip xc vi

fixed

isolating

contacts

of

automatically by the movement of the circuit

nhng tip im cch ly c nh khi CB c ko

breaker carriage and shall prevent access to the

ra. Nhng l chn cho nhng tip im cch ly c

fixed isolating contacts when the circuit breaker


is withdrawn. The shutters for the fixed isolating

nh c ni n thanh ci v s c c cu hot
ng c lp. Nhng l chn bo v thanh ci s

contacts connected to busbar and cables shall

c sn v ch trng BUSBAR. Nhng phn

have independent operating mechanisms.


Shutters for the busbars shall be painted red and

khc trong mch s c sn vng vi ch trng


CIRCUIT.

with white lettering BUSBAR. Those for the


circuits shall be painted yellow with white
lettering CIRCUIT.
To facilitate testing, a device shall be provided

d dng cho cng tc kim tra, s c mt thit b

for fixing, but not locking, shutters in an open


position. The device shall be arranged so as to

gi c nh, nhng khng phi l kho, nhng l


chn v tr m. Thit b s c sp xp bi b

be cancelled by the moving portion, to ensure

phn chuyn ng, m bo rng tnh nng t

that the automatic feature of the shutter is


restored.

ng ca nhng l chn c khi phc.

Self-aligning plug and socket isolating devices of

Trong thit k s c nhng plug v cm cch ly t

an approved design shall be provided for all


auxiliary circuits.

sp xp c lp t cho tt c cc mch ph.

3.11 NHNG B KHO

3.11 PADLOCKING FACILITIES


The

Sub-Contractor

shall

supply

sufficient

Thu ph s cung cp nhng b kho phc v cho

padlocking facilities for the following functions:a) To

lock

closed,

the

circuit

nhng chc nng sau:

breaker

compartment door.

a) ng kha, ca t cha CB.

b) To lock closed, each safety shutter in circuit


breaker compartment.

b) ng kho mi l chn an ton trong ngn


cha CB.

c) To lock closed, the V.T. safety shutters.


c) ng kho, nhng l chn an ton V.T
d) To disable the manual "TRIP" device when
the circuit breaker is in the "EARTH" position
and "CLOSED".

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

d) cch ly thit b hot ng "TRIP" bng tay


khi CB ang v tr "EARTH" v "CLOSED".

u tin s dng ting Anh khi c tranh chp


3/8

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

e) To

the

selector

circuit-breaker

lock

isolated

mechanism
and

on

MC 3 T TRUNG TH & CC THIT B LIN QUAN

e) kho nm vn c kh trn CB cch ly v v

service

tr lm vic.

positions.
3.12 INTERLOCKING FACILITIES

3.12 KHO LIN NG

Mechanical & electrical interlocking facilities shall


be provided to prevent the following operations:-

Kho lin ng c v in s c trang b ngn


nhng hot ng sau:

a) Withdrawal/ insertion of circuit breaker into

a)

S ko hay ci CB vo trong nhng tip im

the isolating contacts unless the circuit


breaker is in its open position

cch ly tr khi CB vo trong ng v tr m


ca n.

b) The closing of a circuit breaker unless it is in


its service, isolated, earthed or completely

b) ng CB tr khi n ang v tr hot ng,


cch ly, ni t hay hon ton c ko ra.

withdrawn position
c) Closing of a circuit breaker in service
position unless the auxiliary contacts are

c) ng CB vo v tr hot ng tr khi nhng tip


im ph c sn sng.

made
d) Insertion of a circuit breaker into service

d) a CB vo trong v tr hot ng khi nhng

position when its pole parts are not in their

cc ca n cha vo ng v tr.

proper positions
e) Closing of earthing switch when the circuit

e) ng tip im ni t khi CB v tr ng hay

breaker is in closed position or vice versa


f)

ngc li.

Closing of a circuit breaker unless its spring

f)

ng CB tr khi l xo sc .

is full charged
3.13 EARTHING AND EARTHING DEVICES

3.13 NI T V NHNG THIT B NI T

All metal parts other than those forming part of

Tt c nhng phn kim loi khng thuc v mch

an electrical circuit shall be connected in an


approved manner to a hard-drawn, high

in s c ni theo mt kiu cho php ko ra,


thanh ng c tnh dn in cao s chy di khng

conductivity copper earth busbar which shall run

ni gia v c bt bu long vo khung chnh ca

the full length and be bolted to the main frame of


the switchboard without joint. The earth busbar

t in. Thanh ni t phi c kh nng mang ti


vi dng in nh mc v trong sut thi gian c

shall be rated to carry currents equal in

dng ngn mch xy ra trn thit b. Kch thc

magnitude and duration to that associated with

nh nht l 50mm x 6.4mm.

the short circuit rating of the equipment.


Minimum size shall be 50mm x 6.4mm.
The design and construction of the equipment
shall be such that all metal parts, other than

Thit k v lp ni t s gm tt c nhng phn


kim loi, tr nhng phn mang in, hay nhng

current carrying parts, or withdrawal equipment

thit b di ng th s c ni t trc khi ng

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/9

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

are earthed before the primary connections are

MC 3 T TRUNG TH & CC THIT B LIN QUAN

mnh.

made.
Metal cases, supports and bases of all
instruments, relays or other associated

Thng kim loi, gi , v ca nhng dng c,


r le hay nhng thit b lin quan khc gn trn my

components mounted on the switchgear shall be

ct s c ni vi thanh ci t bng dy dn

connected to the earth busbar by conductors of


not less than 2.5 mm2 cross sectional area.

khng nh hn dy c tit din 2.5mm.

When components are provided for mounting

Khi nhng b phn cung cp c lp ring r, mi

separately, each shall be provided with an


earthing terminal not less than 35 mm2 cross

ci s c lp bng mt u ni t khng nh
hn 35mm.

sectional area.
Integral busbar earthing by means of the circuit

Ni t thanh ci bng CB s c trang b trn

breaker shall be provided on circuit breakers.

CB. Chng ch c th c ni t khi tt c CB,

Busbar earthing shall only be possible when all

ci m c th a thanh ci vo c m kho.

the circuit breakers which can feed the busbars


are locked open. With the circuit earthed,

Vi mch c ni t, nhng l chn bn trn


nhng tip im cch ly c nh chnh khng ni t

shutters over unearthed fixed main isolating

s b ng. Dng nhng cng tc ni t th

contacts shall be closed. Earthing facilities


employing earth switches are not acceptable.

khng c php.

Earthing switch with fault making capacity for


cable termination shall be provided. Earthing

Cng tc ni t c bo v cho u ni cp khi


ng mch s c cung cp. Cng tc ni t s

switch shall be designed for high speed

c thit k cho hat ng tc cao khng ph

operation independent of operator.

thuc vo ngi vn hnh.

Earthing devices shall have a short circuit rating

Thit b ni t s c mt gi tr dng ngn mch

equal to that of their associated circuit-breaker.

tng ng vi CB ca n.

Padlocking facilities shall be provided for the

Kho s c trang b ngn nga s ni t

purpose of preventing inadvertent earthing.

ngoi mun.

Labels shall be provided to show whether the


equipment is prepared for "SERVICE",

Nhng nhn thng bo s c cung cp ch


thit b sn sng cho "SERVICE", "BUSBAR

"BUSBAR EARTH" or "CIRCUIT EARTH". Such

EARTH" or "CIRCUIT EARTH". Nhng nhn thng

indication shall be visible from the front of the


equipment at all times.

bo s lun c nhn thy t mt trc ca thit


b.

3.14 TESTING FACILITIES

3.14 THIT B KIM TRA

All circuit breaker units shall be provided with

Tt c CB s c nhng thit b cho php kim tra

facilities to enable high tension tests to be

in cao p.

carried out.
Provision shall also be made for temporarily
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

Nhng mch ph cng s c lp t tm thi khi


u tin s dng ting Anh khi c tranh chp
3/10

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

completing the auxiliary circuits when the circuit

CB c cch ly v ko ra, cho php kim tra

breaker is isolated and withdrawn, to enable the

nhng chc nng lm vic ca CB.

functioning of the circuit breaker to be tested.


When current transformers and protective relays

Khi bin dng v r le bo v c lp, thc

are fitted, facilities shall be provided for primary

hin c, nhng cng c ny s c kim tra s

and secondary injection tests to be carried out.


These facilities shall be such that wires and

phu s cp v th cp. kim tra, nhng thit b


h tr nh dy dn, u ni cn thit khng cn

connections need not be disconnected for the

tho ra.

tests to be carried out.


3.15 MECHANICAL INDICATION

3.15 HIN TH C KH

Indication shall be provided to clearly indicate


whether a circuit breaker is in the open or

S hin th phi r rng bit trng thi CB ang


m, ng, hot ng, cch ly, kim tra hay ni t.

closed, service, isolated, test or earthed position.


Positively driven mechanical indicating devices
shall also be provided on all equipment to

Thit b hin th phn chuyn ng c kh s c


trang b trn tt c thit b ch nhng trng thi

indicate the following where applicable:-

sau:

Circuit breaker "OPEN" or "CLOSED"

CB "OPEN" or "CLOSED"

Circuit breaker
"SPRING FREE"

"SPRING

CHARGED"

or

3.16 AUXILIARY SWITCHES

CB "SPRING CHARGED" or "SPRING FREE"

3.16 CNG TC PH

Approved, positively driven in both directions,

Nhng cng tc ph, c php s dng, c kh

auxiliary switches shall be provided on all

nng thay i trng thi mt cch r rng c hai

circuit-breakers and isolators for indication,


control and interlocking.

hng, s trang b trn tt c CB v hp cch in


hin th, kim sot v kho ln nhau.

Auxiliary switches shall be strong, have a

Nhng cng tc ph phi chc chn, dt khot khi

positive wiping action when closing and shall be


mounted in an accessible position clear of

ng v s c lp trn v tr thun tin cho s


hot ng v mt c kh.

operating mechanisms.
Auxiliary switches shall be designed to make,

Nhng cng tc phu c thit k s dng cho

break and shall carry, without undue heating, the

ng ct dng din trong mch nhng khng gy

current of their associated circuit. Auxiliary

qu nhit. Nhng cng tc ph c dng in cho

switches shall be rated for 10A operational


current and shall be capable of breaking at least

php l 10A v th ct ti gi tr t nht l 2A-220V


DC vi thi gian ln hn 20 ms.

2A at 220V D.C. with a circuit time constant not


less than 20 ms.
Not less than eight spare auxiliary switches shall
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

Mi CB s c nhiu hn 8 cng tc ph d tr v 4
u tin s dng ting Anh khi c tranh chp
3/11

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

be provided with each circuit-breaker and not

ci cho mi mt b cch ly. Mi cng tc d phng

less than four with each isolator. Each spare

phi d dng i trng thi t thng m sang

contact

from

thng ng v ngc li. Tt c cng tc ph s

normally open to normally closed and vice versa.


All auxiliary switches shall be wired up (via

c ni (thng qua thit b ngt th cp nu khng


c thit b ko ra c) n trm ni dy trn mt

secondary

trc ca phn c nh c sp xp theo cng

shall

be readily changeable

disconnecting

devices

if

no

withdrawable equipment) to a terminal board on


the front of the fixed portion arranged in the

th t cho ring tng ci cng loi.

same sequence for each individual unit of the


same type.
3.17 ANTI-CONDENSATION HEATERS

3.17 IN TR SI

Anti-condensation heaters of an approved type


shall be provided inside each cubicle. They shall

in tr si chng ngng t cng chng loi s


c lp trong mi ngn t. Chng c kim sot

be thermostatically controlled, shrouded and

bng thermostat. Chng c che y v t sao

located so as not to cause injury to personnel or

cho trnh gy nguy him cho ngi v h hng

damage to equipment. The heaters shall be


switched
by
a
double-pole
miniature

thit b. Chng c cp ngun bi MCB 2 cc, vi


mt n hin th "cubicle heaters on" c lp ng

circuit-breaker, with a "cubicle heaters on"

trc t in. Ngun cp l 240V 50 Hz mt pha

indication lamp which shall be installed on the


front panel of the switchgear. The heaters shall

AC.

operate from a 240V 50 Hz single phase A.C.


supply.
3.18 INSULATORS

3.18 CCH IN

Minimum insulator lengths for enclosed


indoor-type circuit breakers shall be as follows:-

Chiu di cch in ti thiu cho loi CB trong nh


nh sau:

Rated voltage: 24 kV
in p nh mc: 24 kV
Minimum length of insulator in air

: 127mm
Khong cch cch in ti thiu

3.19 CURRENT TRANSFORMER

: 127mm

3.19 BIN DNG

Current transformers shall comply with BS 7626:


1993 - Specification for current transformers and

Bin dng s theo tiu chun BS 7626: 1993 Specification for current transformers v phi ph

shall be suitable for the operation of protective

hp bo v thit b, dng c, hay thit b o

gear, instruments and/ or metering equipment.

lng. Tiu chun thit k phi c Qun l K

The design characteristics shall be to the


Engineer's approval. The current transformers

thut ng . Cc bin dng cho mi t phi c gi


tr nh c ch trn bn v.

for each panel shall be of the rating as indicated


on the Sub-Contract Drawings.
The short time current rating of the primary
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

Gi tr dng in khng thng trc ca cun s


u tin s dng ting Anh khi c tranh chp
3/12

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

windings of the current transformers shall be not

cp phi ln hn CB bo v n. Cun th cp s

less than that of the associated circuit breaker.

phi ct mch trong vng 1 pht khi cun s cp

The secondary windings of each set of current

mang dng in nh mc.

transformers shall be capable of being open


circuited for one minute with the primary winding
carrying the rated current.
Current transformers shall be air-insulated and

Bin dng s cch in chn khng v c lp

shall be mounted in the fixed portion of the

trn phn c nh ca b chuyn mch mt cch

switchgear with a method of securing in position

m bo sao cho lc c kh tc ng ln bin dng

such that undue mechanical pressure cannot be


exerted on the transformer windings.

khng c qu mc.

CT characteristics, including magnetization


curves of each type of current transformer shall

c im ca CT, nh ng cong t ho ca mi
loi bin dng phi c xem xt v ng .

be submitted for approval.


All current transformers shall be installed with
the P1 terminals adjacent to the busbars. The

Tt c bin dng phi c lp t bng u ni P1


gn vi nhng thanh ci. Cc ca cun s v th

polarity of the primary and secondary windings of

cp ca mi ci phi c hin th mt cch r rng

each current transformer shall be clearly


indicated and labels shall be fitted in a readily

v nhn phi t v tr sao cho d dng c oc


t s, loi, cng sut ca mi ci.

accessible position to indicate the ratio, class


and duty of each transformer.
Current transformers for indication or metering

Bin dng hin th hay o lng s c cun s

shall have their secondary windings earthed at

cp ni t ti switchgear. Cun s cp ca bin

the switchgear. The secondary windings of


current transformers for protection shall be

dng bo v s c ni t vo ni cung cp cho


nhng r le. u ni r le s c ni bng u

earthed at the panel which accommodates the

ni c th m c.

associated relay. The relay connection shall be


made via a removable link.
3.20 BIN P

3.20 VOLTAGE TRANSFORMER


Voltage transformers shall be provided for the
operation

of

the

protective

gear,

Bin p c cung cp cho hot ng ca thit b

voltage

bo v, nhng dng c v trang thit b n p, bin

regulating equipment and instruments. Voltage


transformers shall comply with BS 7625: 1993 -

p phi ph hp vi tiu chun BS 7625: 1993 Specification for voltage transformers v s c

Specification for voltage transformers and shall

nhng gi tr sau:

be of the following rating:a) System Voltage: 22 kV 3 phase 50 Hz

a) in p h thng : 22 kV 3 phase 50 Hz

b) Highest Equipment Voltage: 24 kV

b) in p ln nht : 24 kV

c) Transformation Ratio: 22 kV/110 V

c) T s bin p

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

: 22 kV/110 V

u tin s dng ting Anh khi c tranh chp


3/13

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

d) Rated Output per Phase: 200 VA

d) in p ng ra mi pha : 200 VA

e) Accuracy: Class 0.5 for measurement

e) chnh xc : Class 0.5 cho o m

f)

f)

Voltage Factor: 1.2 continuously & 1.5 for 30

H s in p : 1.2 lin tc & 1.5 for 30 giy

sec
g) Insulation Level: 60 kV R.M.S.

g) Loi cch in : 60 kV R.M.S.

V.T.'s shall have two separate windings for

V.T. s c hai cun s v th cp cch ly v l loi

primary and secondary and shall be dry type with


epoxy encapsulation. They shall be housed in

kh c bc epoxy. Chng s ct trong khng kh


t nhin, hu nh c lm bng thp l, cch

naturally air-cooled totally enclosed sheet steel

in, v l loi co gin c.

enclosures and shall be of isolating and


retractable type.
The primary winding shall be connected through

Cun s cp s c ni qua cu ch c th thay

renewable fuses to BS 2692 - Fuses for voltages


exceeding 1000 V A.C. with current limiting

c theo BS 2692 - Fuses for voltages exceeding


1000 V A.C. c t tnh gii hn dng. Cun th

features. Secondary windings shall be connected

cp s c ni qua CB c dn nhn ch

through circuit breakers labeled to indicate their


function and phase colour, to the appropriate

chc nng ca chng v mu pha trong mch ca


chng.

circuits.
Primary fuses shall only be removed when the

Cu ch ca s cp ch c tho ra khi V.T hon

V.T. is entirely withdrawn out at the isolated

ton c ko ra khi v tr c cch ly

position.
Voltage transformers shall be capable of being

V.T phi c kh nng ni v tho c ra khi thit

connected and disconnected from the equipment

b trong khi ang ch vn hnh. B kho v tr

whilst in service. Facilities for padlocking in the


service position shall be provided. A set of safety

ang vn hnh s c trang b. Mt b l nhng l


chn bo v c chc nng kho c, cng s

shutters, capable of being padlocked, shall be

c trang b t ng che nhng tip im c

provided

fixed

nh khi V.T c cch ly. Nhng l chn s c t

contacts when the V.T. is isolated. Particulars of


shutters shall be identical to those for circuit

im ging nhau so vi nhng CB ca chng.


Nhng l chn s hot ng t ng bi b truyn

breakers.

ng c kch hot bng ng tc tho V.T.

to

automatically cover

The

shutters

shall

the

operate

automatically by positive drive activated by


movement of the V.T. assembly.
Loi cch in cho V.T v dy l loi F.

Class of insulation for components and windings


shall be Class F.
V.T. secondary windings shall be earthed at the

Cun th cp ca V.T. s c ni t ti b

switchgear through a link which can be removed


for insulation testing. The earthing of voltage

chuyn mch bng mt u ni c th tho ri


kim tra cch in. S ni t ca V.T s phi

transformers shall be approved by the Engineer.

c Qun l K thut ng .

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/14

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

Secondary circuits of voltage transformer shall

MC 3 T TRUNG TH & CC THIT B LIN QUAN

Mch nh th ca V.T khng c ni song song.

not be paralleled.
Connections to primary isolating contacts shall
have a thermal current rating of 200A and a

S u ni n nhng cng tc cch ly chnh s c


mt gi tr dng in sinh nhit l 200A v dung

short circuit capacity of the following:-

lng ngn mch nh sau:

Rated highest equipment voltage:

24 kV

in p nh mc ln nht ca thit b :

Rated short circuit breaking current: 25 kA

24 kV

Dng in ct ngn mch nh mc : 25 kA R.M.S.

R.M.S.
Type test on temperature rise shall be certified

Loi kim tra s gia tng nhit s c chng

by the manufacturer on tests undertaken in the


manufacturer's works.

nhn bi nh sn xut trong cng tc kim tra ca


nh sn xut.

3.21 CABLE BOX

3.21 HP NI CP

Cable boxes shall be suitable for terminating the

Hp ni cp phi thch hp ni cp trc tip ln

The

trn t my ct. Kch thc v s sp t trm ni

dimensions and terminal arrangements shall be


submitted for approval by the Engineer before

phi c Qun l K thut xem xt v chp thun


trc khi ch to.

cables

directly

into

the

switchgear.

manufacture is commenced.
All cable boxes shall be suitable for use with air

Tt c hp ni cp phi ph hp p ng c

insulated heat shrinkable elastometric PCP

khong cch khng gian, s gin n nhit, trm ni

cable termination and shall be designed to

dy bng cht nha n hi PCP v c thit k

exclude the entry of air, dust, or moisture. The


internal surfaces of cable boxes shall be cleaned

chng li khng kh, bi, hi m. B mt bn


trong ca hp ni dy phi sch, khng b r, bi sau

of all scale and rust after cleaning and priming

khi v sinh, sn lt v sn polyester.

and shall be finished with polyester powder paint.


The cable box shall be suitable for 3 core

Hp

XLPE/SWA/PVC cables. Where cable boxes are

XLPE/SWA/PVC. Nhng ch m hp ni cp s

provided for three-core cables, the sweating


sockets on the two outer phases shall be inclined

dng cp 3 rut, cm hn thic trn 2 pha ngoi


s c khuynh hng nghing vo trung tm

towards the central to minimise bending of the

gim thiu cong ca cp. Nhng ch c hn 1

cable cores. Where there is more than one core


per phase, the socket block shall be so designed

dy mi pha, b cm s c thit k sao cho


gim thiu cong ca cp.

ni

phi

thch

hp

vi

cp

rut

as to minimise bending of the cable cores.


All cable terminals shall be of adequate size to
ensure no over-heating takes place at rated

Tt c u ni cp phi c kch c tng thch


m bo khng b qu nhit khi mang ti vi dng

current. Neon indicators fed from potential

nh mc. n hin th neon c cung cp t b

divider on each phase of the cable termination


shall be provided in front of the panel to indicate

chia p trn mi pha ca u ni cp s c lp


pha trc ca t hin th cp ang c ngun

either cable are "live" or "dead".

hay mt.

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/15

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

The insulators and fittings shall be unaffected by

Vt cch in v khp ni phi khng b nh hng

atmospheric and climatic conditions, ozone,

bi iu kin khng kh, thi tit, kh ozone, axit,

acids, alkalis, dust deposits or rapid temperature

kim, ng bi hay s thay i nhit t ngt xy

changes likely to arise when operating in the site


conditions and shall be designed so as to

ra khi vn hnh trong iu kin v phi c


thit k sao cho d dng v sinh.

facilitate cleaning.
3.22 PROTECTION RELAYS

3.22 R LE BO V

The following shall be provided in a separate

Nhng thit b bo v sau s c lp t trong

compartment where specified:-

mt hp ring r nh:

a) Three single element induction disc type

a) Ba a cm ng n loi I.D.M.T.L. nhng r le

I.D.M.T.L. over-correct protection relays, c/w


high set instantaneous elements, with

bo v iu chnh chnh xc vi cc yu t tc
thi, vi dng chnh c t 50-200% trong 7

current setting of 50% to 200% in 7 equal

mc bng nhau v thi gian set t 0-3s v c

steps and time setting of 0-3s continuously

th iu chnh c n 10 ln dng in set.

adjustable at 10 times the current setting.


The time-current characteristics shall be the

c tnh thi gian- dng in s l 3/10 ph


hp vi BS 142 - Electrical protection relays.

3/10 category in accordance with BS 142 Electrical protection relays.


b) One single element induction disc type

b) Mt a cm ng n loi I.D.M.T.L. r le bo

I.D.M.T.L. earth fault relay with current


setting of 10% to 40% in 7 equal steps and

v chm t vi dng set t 10-40% trong 7


mc bng nhau v thi gian set t 0-1.3s c

time

th iu chnh n 10 ln gi tr dng in set.

setting

of

0-1.3s

continuously

adjustable at 10 times the current setting.


c) Incoming panel: Pilot wire Solkor RF/HOR 4

c) T ngun n: dy hin th loi Solkor RF/HOR

or equal.
d) Feeder

4 hay tng ng.


panel:

Temperature

trip

from

d) T ngun cp: bo v qu nhit t bin th,

transformers; differential current and inter-

lch dng, v inter-tripping n CB in p thp

tripping to L.V. circuit breaker.

(L.V. circuit breaker).

e) One single unit trip circuit supervision relay

e) Mt rle ct bo v, loi s gim st s ct

which shall supervise the trip circuit of the

mch ca CB v pht ra tn hiu chung bo v

circuit breaker and initiate audible alarm and


visual indication if the trip circuit fails. It shall

n hin th nu mch ct hng. N s kt ni


tt c cc s cung cp s c, thng hot

be connected across the trip supply, be

ng v lm tr trn in p ct di 40% gi

normally energised and delayed drop off if

tr thng. N s c in p hot ng l 30V

trip voltage falls below 40% of nominal


value. It shall be suitable for use at nominal

D.C v c nt nhn reset.

trip voltage of 30V D.C. and be hand reset.


All relays provided shall comply with BS 142 and

Tt c rle lp t phi tun theo quy nh BS 142

shall be of draw out case type and flush mounted

v l loi hp ko ra v c lp ngay vo mt

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/16

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

on the front panel of the switchgear. All terminals

trc ca t. Tt c u ni n rle phi c

to relays shall be suitably insulated and the

cch in ph hp v mch c lp cu ch thch

circuits shall be suitably fused, using H.R.C.

hp, s dng loi H.R.C.

fuses.
The relay contacts shall be of the double break

Nhng tip im ca rle phi l loi i. Chng c

type. The relay contacts shall have adequate


making and breaking capacity. Unless otherwise

dung lng ng v ct tng thch. Tr phi c


nhng yu cu v k thut khc, nhng tip im

specified, contacts shall be capable to make and

phi chu c cng sut 7500VA trong 0.5 giy vi

carry 7500 VA for 0.5 second with a maximum of

dng in ln nht 30A- 660V A.C hay D.C

30A and 660V.A.C. or D.C.


A red coloured latch shall be provided at the side

Mt ci cht nh du mu c lp bn cnh

of each relay which shall isolate the trip circuit


supply when the latch is moved from its fully

ca mi rle ci m s c lp ngun ct mch


khi cht c rt ra khi v tr kho ca n v trc

locked position and before the relay is drawn out.

khi rle c ko ra.

The Sub-Contractor shall supply and install the


alarm to be initiated by the auxiliary relay for

Nh thu s cung cp v lp t thit b bo ng


thng qua role ph bo v qu nhit cho bin th

transformer temperature protection and the trip

v role gim st mch ct.

circuit supervision relay.


The pilot wire protective system shall operate in

H thng bo v dy iu khin s vn hnh cng

conjunction with similar equipment at the remote


Power Grid end of the feeder via pilot cable. The

vi thit b tng t ti li ngun, im cui ca


ng dy thng qua cp iu khin. Nhng cp

pilot cables used by Power Grid will be either 5,

iu khin c s dng bi li ngun s l 5, 10,

copper conductor

hay 20 cp, loi dy ng bc polyethylene 1.5mm,

polyethylene insulated, copper tape screened,


polyethylene oversheathed armoured type.

ng c bc dy bng, bc st ph polyethylene.

10 or 20 pair, 1.5mm

3.23 PILOT AND CONTROL CABLES

3.23 CP DN V IU KHIN

All feeder panels shall be provided with

Tt c t ngun cung cp s c lp trm ni dy

termination for a twin core 1.5mm cable for

cho loi cp i 1.5mm ni dy dn t t ng

termination of pilot wires from Power Grid


switchgear.

ct li ngun.

Each transformer panel shall come with


sufficient number of control cable glands for

Mi t bin th phi lp s dy vi mc ch
bo ng, iu khin, ct mch.

alarm/ control/ tripping purposes.


The size of the cable gland for transformer and
feeder panel should be suitable for the overall

Kch thc ca ming m cp cho bin th v t


ngun cung cp phi ph hp bao trm ton b

diameter sizes of pilot/ control cable used. The

cp dn/ iu khin c s dng. ng knh

minimum size of alarm/ tripping control cable for


the
transformer
panel is 2.5mm2 in

nh nht ca cp iu khin bo ng/ ct mch


cho bin th l 2.5mm.

cross-sectional area.
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/17

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

Each panel shall be provided with a terminal

Mi t s c lp nhng trm ni dy. Nhng

block. Adequate terminals with spares and cable

im ni dy tng thch v nhng ming m dy

glands suitable for Power Grid control cable shall

ph hp cho cp iu khin ca li in s c

be provided.

trang b.

3.24 INDICATING INSTRUMENTS

3.24 THIT B HIN TH

All indicating instruments shall be to BS 89 -

Tt c nhng thit b hin th phi theo BS 89 -

Direct

Direct

acting

indicating

analogue

electrical

acting

indicating

analogue

electrical

measuring instruments and their accessories 1st

measuring instruments and their accessories mc

Grade moving iron spring controlled with


100mm, 240o scale dials and external zero

di chuyn th nht ca l xo c iu khin bng


100mm, 240o v chnh v khng bn ngoi. B

adjustment. Integrating meter shall be to BS

ng h s l loi BS 5685 - Electricity meters.

5685 - Electricity meters.


Each panel shall be equipped with neon potential

Mi t in s c trang b dn bo hin th

indicators to indicate whether each phase on the

tng pha trong t ang ang c in hay mt.

circuit side of the panel is "alive". The indicators


shall be energised from condenser bushings on

Nhng n bo s c cp ngun t b ng t li
trn t.

the panel.
a

Mi n hin th s c ni song song vi mt

normally-closed push-button switch in parallel.

Each

indicator

shall

be

wired

with

cng tc nhn thng ng. n s sng mi khi

The operation of this switch shall light up the


indicators.

nt nhn ny hot ng.

The indicators shall be mounted at the front of

n hin th s c lp mt trc ca t v s

the switch panel and shall be shielded from


extraneous light. The neon lamps shall be of

c che khi b chi nh sng t bn ngoi.


Nhng n neon phi ph hp cho s chiu

adequate dimensions to provide clear indication

sng r rng trong mi iu kin. Nhng u ni

under all conditions. The terminals at neon


indicators shall be adequately shielded with

ca n neon phi c che chn thch hp


trnh tip xc gin tip ca ngi ln phn c in.

positive means to prevent operating personnel


inadvertently coming into contact with the 'live'
terminals.
Laminated plastic sheet engraved labels of

Nhng tm nha plastic c khc nhn vi nhiu

ample size shall be provided for each of the units


on the switchboard. A means of fixing these

kch c khc nhau s c gn ln trn tng phn


ca t in cao p. Mt cch gn nhng ci

labels

by

nhn ny s c thc hin, khc vi cch dng

adhesives. The use of embossing tape for

cht kt dnh. Khng c php s dng dy bng

labeling is not acceptable.

khc ni lm nhn.

The Sub-Contractor shall, during the progress of

Trong sut qu trnh lp rp t in my ct, nh

manufacture of the switchboard, submit a


schedule of labels for approval by the Engineer

thu s phi a ra danh sch ca nhn Qun l


K thut xem xt trc khi chng c ng du.

shall

be

provided,

other

than

before engraving is carried out.


The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/18

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

Warning labels shall be affixed to the rear panels

Nhn cnh bo s dn ng sau t in v s c

and shall be coloured red with white lettering

nn , ch trng: "DANGER - LIVE BUSBAR

denoting "DANGER - LIVE BUSBAR INSIDE".

INSIDE".

In addition to automatic screening shutters and

Thm vo , t ng che nhng l chn v

barriers, warning labels shall also be provided for

hng ro, nhng bin cnh bo cng s c gn

all live parts such as test terminal blocks.

ln nhng phn c in nh nhng trm u dy.

A brief operation instruction of the switchboard

Mt bng thng tin v hot ng ca t in cng

together with a detailed schematic wiring

vi mt bn v dy dn, bng lit k cc bc lin

diagram listing out all the relevant switching


steps and interlocks for commissioning/

quan n vic ng ct, kho lin ng ca t


cho hoc khng cho mt phn hay ton b t cao

decommissioning of part or whole of the 22 kV

p 22kV vo hot ng cng s c gn trong

switchboard shall be provided by the


Sub-Contractor in a frame adjacent to the

khung v c cung cp bi nh thu.

switchboard.
All equipment shall be solidly earthed. The
earthing system shall comply with Singapore

Tt c cc thit b s c ni t mt cch chc


chn. H thng ni t phi tun theo tiu chun

Standard Code of Practice CP 5: 1988 - Wiring

Singapore CP 5: 1988 - Wiring of electrical

of electrical equipment of buildings, Singapore


Standard Codes of Practice CP: 16 - Earthing

equipment of buildings, Singapore Standard Codes


of Practice CP: 16 - Earthing and CP 17: 1991 - The

and CP 17: 1991 - The maintenance of electrical

maintenance of electrical switchgear for voltages up

switchgear for voltages up to and including 22


kV.

to and including 22 kV.

An earth bar shall be provided in the 22 kV

Mt thanh ni t s c lp trong phng my ct

switchroom.

22kV
3.26 NGUN D.C

3.26 D.C. SUPPLY


A 30V d.c. supply system shall be provided for

Mt ngun cung cp 30 V d.c s c cung cp

the opening and closing of the circuit breakers

ng, m ph cho CB v bo v trang thit b hay

operating auxiliary and protective equipment/

thit b bo v v.v nh thit k. H thng s gm

control devices, etc. as specified. The system


shall comprise a battery section and a charger

bnh c quy v b phn sc, mi b s c cha


trong mt ngn ring ca t in, vi dy iu

section

separate

khin, thit b bo v v nhng thit b h tr khc

compartments of a cubicle, c/w control wiring,


protective devices and other accessories as

nh yu cu, c cung cp bi mt nh sn xut


c ng k. Mt ngoi s c ph lp men gm

required, supplied by a single proprietary

hay cellulose hp vi t cao p.

each

housed

within

manufacturer. The cubicle shall be externally


finished in semi-gloss stoved enamel or cellulose
to match the switchboard.
The system shall also incorporate a double
wound step-down transformer of appropriate

H thng cng s lin kt vi mt bin p i gim


n mt gi tr thch hp cng nh lin kt vi cc

rating as well as the following components:-

thit b sau:

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/19

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

a) A.C. ON/ OFF switch

a)

MC 3 T TRUNG TH & CC THIT B LIN QUAN

Cng tc A.C. ON/OFF

b) D.C. voltmeter 0-50V

b) Vn k D.C 0-50V

c) D.C. charge ammeter of appropriate rating

c) Ampe k sc D.C. vi gi tr thch hp.

d) D.C. discharge ammeter of appropriate


rating

d) Ampe k x dng D.C vi gi tr thch hp.

e) "Float" pilot lamp (blue), "Boost" pilot lamp

e) "Float" n bo(xanh dng), "Boost" n bo

(green), "Mains on" pilot lamp (red).


f)

(xanh l), "Mains on" n bo().

"Charge Failure" pilot lamp (amber), "Low

f)

Voltage" pilot lamp (amber), "Earth Fault"


pilot lamp (amber).

"Charge Failure" n bo (vng), "Low Voltage"


n bo (vng), "Earth Fault" n bo (vng).

g) Audible alarm

g) Chung bo ng

h) Rectifier fuse of appropriate rating

h) Cu ch chnh lu c gi tr thch hp.

i)

Charge failure monitor, low volt monitor,


earth fault monitor

i)

B kim sot li sc, in p thp, li chm t.

j)

Boost/ Off/ Float selector switch

j)

Cng tc chuyn v tr Boost/Off/Float

k) Auto/ manual charge selector switch

k) Cng tc chuyn Auto/manual charge

l)

l)

Facilities for testing the batteries and pilot


lamps

Nhng thit b kim tra bnh c qui v n


bo.

m) Nhng im kim tra bo ng t xa. (dy tn


hiu t t n t tp trung cc d liu s c

m) Provisions of the remote alarm monitoring


points. (Signal wiring from the panel to the

lp t bi nh thu B.A.S):

field data gathering panel shall be done by


B.A.S. Sub-Contractor):i)

Battery High Voltage Alarm

i)

Bo ng Battery High Voltage

ii)

Battery Low Voltage Alarm

ii)

Bo ng Battery Low Voltage

iii) Mains Power Failure Alarm

ii)

Mt ngun Mains Power Failure

iv) Charging Failure Alarm

iv) Li ngun Sc

v) Earth Fault Alarm

v) Li chm t Earth Fault

n) Other components as required

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

n) Nhng thit b yu cu khc.

u tin s dng ting Anh khi c tranh chp


3/20

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

The voltage level on normal and boost charging

Mc sc bnh thng hay sc nhanh c th iu

shall be adjustable by means of clearly marked

chnh c bng cch chuyn b v tr c vch du

controls situated inside the cubicle.

c t bn trong t.

Essential requirements of the batteries and the

Nhng yu cu cn thit cho bnh v b sc nh

charger shall be as described below.

sau.

3.27 BATTERY

3.27 BNH C QUY

Batteries shall be of high performance nickel-

Bnh c tui th cao nh nickel-cadmium hay axit-

cadmium or sealed lead-acid type and shall be


capable of supplying the standby and intermittent

ch kh phi c kh nng cung cp d phng lin


tc cho ti nh d tnh m khng h hng trong

loads specified herein without deterioration under

nhng iu kin mi trng nht nh, vi mt b

the environmental condition specified, with a


constant voltage regulator connected to it as a

n p ni n n nh mt b sc ni. Mi ngn s
l hc nickel cadmium loi bn mng vi mt np

float charger. Cells shall be of the nickel

trn.

cadmium pocket plate type with a vent cap at the


top.
Cell containers shall be of moulded translucent

Nhng ngn cha phi l loi nha trong m c

plastic of high impact resistance and be able to


withstand continuously corrosion attack by

c bn cao v c kh nng chu c s n


mn bi cht in phn. Ngn cha bnh c qui

electrolyte. The battery compartment shall be

c thit k sao cho khi thc hin nhng cng

designed such that work performed on a battery


in service shall not require circuit interruption.

vic cn thit trn bnh m khng lm gin on


mch in.

Terminals and inter-cell connectors shall be of

im ni v cc u ni bn trong phi l loi vt

high conductivity corrosion-free material.


Interconnection of rows of cells shall be in

liu chng n mn v c tnh dn in cao. Nhng


mi ni bn trong mt ngn s c ti bi nhng

annealed copper bars of adequate cross section,

thanh ng vi mt tit din v cch in ph hp.

suitably insulated.
The battery shall have a nominal output of 30V.

Bnh in c in p ra thng l 30V. in p mt

The nominal cell voltage after rated discharge

ngn bnh thng sau khi s dng c gi tr khng

shall be not less than 1.1V.

t hn 1.1V.

On the failure of the mains supply, the battery

Khi ngun chnh b mt, bnh n phi c kh nng

shall be capable of supplying the connected load


for 5 hours. At the end of the 5-hour period, the

cung cp in trong vng 5 gi. Sau 5 gi, chng


phi cn kh nng cung cp ngun ng v ct

battery shall be capable of providing power to

cc CB 4 ln. Thi gian ng v ct s cch nhau

close and trip all the circuit breakers 4 times. The

khong 5 giy. Trong sut thi gian 5 gi cung cp

closing and tripping shall be made in an interval


of 5 seconds. During the 5-hour period and at

ngun lin tc hot ng ng ct cc thit b,


in p 2 u cc ca bnh s khng nh hn 27V.

the end of the above closing and tripping duties,


the terminal voltage of the battery shall be not
less than 27V.

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/21

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

3.28 CHARGER EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

3.28 CC THIT B SC

The battery charger shall be of constant voltage

B sc s l loi c hng s in p tri ni, thch

float type, suitable for use with the associated


batteries. The charger shall be operated at

hp s dng vi cc thit b h tr khc. B sc


hot ng vi ngun 400/230V A.C. v bao gm

400/230V A.C. and shall comprise transformer

mt bin th chnh lu vi dung lng thch hp

rectifiers of adequate capacity for the conversion


of A.C. to constant voltage D.C. for charging at

bin in p A.C sang D.C vi gi tr sc t do hay


sc tng in p nhanh cng nh cung cp cho ti

the float and boost values together with the

d phng. N phi c kh nng t bo v chng li

supply of the standing load specified. It shall be

qu ti v iu chnh trnh s lo ho ca b

self-protecting against continuous overload and


shall be suitable for re-adjustment to correct for

chnh lu v nhng phn khc.

aging of rectifiers and other parts.


The charger shall be of solid-state type with
protection

against

voltage

surges.

B sc l loi bn dn c bo v chng in p

The

nhiu. Cc thit b cng s c gi tr v c lp

components shall be so rated and mounted as to

sao cho m bo tt c iu kin hot ng,

ensure that under all operating conditions they


shall not require replacement during the life of

chng s khng phi b thay th trong sut tui th


ca thit b v yu cu khng hoc gim thiu s

the equipment and require no or minimum

cn chnh trc. Mch sc s c lp t sao cho

pre-commissioning adjustment. The charging


circuitry shall be so arranged that the failure of

s h hng ca tt c cc thit b s khng lm


bnh c quy b h do sc qu dng.

any component will not cause permanent


damage to the batteries by overcharging.
The charger shall be housed in a suitable

B sc s c t trong mt ngn bng thp vi

floor-mounted sheet-steel cubicle with lockable

sn lp thch hp, c bn l i c th kho c

double-hinged front doors, and anti-vermin


ventilation louvres.

lp ca trc, c khe l chn thng gi chng


cn trng.

The charger shall have a maximum current


rating sufficient to meet a battery charging

B sc phi c gi tr dng ln nht ph hp vi


dng sc trn ng h ampe, tng ng 7%

current in amperes, equal numerically to 7% of

dung lng bnh trong 10 gi. B sc s th hin

the battery capacity at the 10 hour rate. The

nhng bin i nh l vi in p ng ra so vi

charger on float charge performance shall be


such that with the output voltage set with rated

in p ng vo, tn s, v vi 50% ti, in p ng


ra s khng thay i qu 2% vi bt k s thay i

input voltage, frequency, and with 50% load, the

tn s, in p ng vo c quy nh trong c

output voltage shall not vary by more than +2%


with any combination of the input supply voltage

tnh k thut v s bin i dng ng ra t 0- 100%.


Vi gi tr tn s, in p ng vo, ng ra ca b

and frequency variations stipulated in the

sc s khng t hn gi tr ca n tnh bng watt

Specification and output current variation from

trong ton b khong in p ra.

zero to 100%. With rated input voltage and


frequency, the charger output shall not be less
than its rating in watts over the complete output
voltage range.
The charger shall have a taper characteristic
The English language version prevails
SECTION 3/VISTA VERDE SPECS/ ELECT

Trn b sc s c mt ming dp vi phn ui


u tin s dng ting Anh khi c tranh chp
3/22

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

booster charging facility, which shall be selected

gim dn th hin c trng ca b sc, ci

automatically or manually. In the event that the

chn ch sc t ng hay bng tay. Nu bnh

batteries are subjected to a heavy discharge,

in buc phi sc nhanh, nu cn thit chng s

automatic changeover from float to boost charge


(and vice-versa) operation shall occur as

i trng thi t sc chm sang nhanh ( v ngc


li) bng mt b chuyn i t ng phc hi

necessary to restore the batteries to the fully

bnh n trng thi y hon ton.

charged condition.
The charger shall maintain the batteries at a

B sc s duy tr bnh trng thi sc y da trn

normal fully charged state, based on the

nhng tiu chun sau:

following criteria:a) A constant voltage float-charge on the

a) Hng s in p sc tri ca bnh c quy s

batteries shall be arranged such that, at


below gassing level, the need for boost

c ci t di mc bay hi ca cht kh,


ch sc nhanh ca bnh th uc ci t

charging of the batteries is reduced to rare

gim n mc gia v s duy tr yu cu gim

intervals and maintenance requirements

n mc thp nht. Ch sc li nhanh ca

minimised. The float-charge rate shall give a


fast recharge to approximately 75% of the

bnh s c gi tr khong 75% dung lng ca


bnh trong vng 6 gi vi s hao ht cht in

batteries' capacity within six hours with

phn l thp nht.

minimum electrolytic loss.


b) Without heavy discharge, the float-charge

Khi bnh khng x nhanh, gi tr sc cng ch

rate shall also be such that battery


electrolyte, at the ambient temperature

nh l cht in phn ca bnh. nhit mi


trng xung quanh, khng cn thit sc y

specified, shall not require topping up at an

bnh t nht l mt ln trong khong mt nm.

interval less than once a year.


c) After a heavy discharge, the time to restore

c) Sau khi x nhanh, thi gian phc hi li y

the batteries to the fully charged condition

bnh s phi khng qu 8 gi. in p sc

shall be no more than 8 hours. The


booster-charge voltage shall be limited to a

nhanh s c gii hn ti gi tr ln nht m


khng lm gim tui th ca bnh.

maximum value which will not reduce the life


of the batteries.
occasional

d) Nu bnh in thnh thong c s dng chu k

discharge-charge cycling to condition the

np-x, nh sn xut s c thng bo

electrolyte, the manufacturer shall inform


and make provision for this in the charger.

lm sn nh yu cu cho b sc.

d) If

the

batteries

require

H.R.C. cartridge fuses shall be provided to

Cu ch v loi H.R.C. s c lp bo v v

protect and isolate individual control modules or


boards and outputs from the batteries and load.

cch ly board hay nhng mch iu khin v cho


dng ra t bnh n ti. Cu ch loi bt vt s

Screw-in fuse cartridges shall not be used in all

khng c s dng trong tt c mch L.V. v ph

L.V. and extra L.V. circuit.

L.V.

A suitable surge suppressor shall be installed in

Mt b kh nhiu thch hp s c lp trn c

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/23

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

MC 3 T TRUNG TH & CC THIT B LIN QUAN

both the input and output of the charger to

ng vo v ng ra ca b sc trnh gy h hng

prevent damage of the electronic components

cc thit b in t do bt k s nhiu t bn ngoi

due to any external surge.

no.

The charger shall also be provided with load

B sc cng s c lp b bo v qu p. Trn

over-voltage protection. On the output terminals

ng ra n ti, in p s c gii hn sau cho

to the load, the voltage shall be limited so as not


to exceed 12V D.C. with any combination of

khng vt qu 12VD.C bng bt k s lin kt


gia in p ng ra ca b sc v dng ti d

standing load current and charger output

phng.

voltage.
An approved charge fail relay shall be provided

Mt rle kim sot b sc thch hp s c lp

for the charger to detect failure of the D.C. output

t tm nhng li trn ng ra D.C ca b sc

of the float (low rate) charger.

(nh l kim sot im ra c gi tr thp).

A relay shall also be provided to detect fall of

Mt rle cng s c lp t kim sot gi tr

battery volts below the low-rate value. The alarm

in p thp ca bnh. Tn hiu bo li s pht ra

shall be delayed by between 30 to 60 seconds


and in the event of a failure in the delay circuit,

sau 30-60 giy, v khi trong mch bo li c s c


th tn hiu bo ng s pht ra tc thi. Tn hiu

an alarm shall be given instantaneously. The

bo ng s c mc ku nghe chi tai (in p tiu

alarm shall have a sharp threshold (the voltage


decay may be very slow, with high performance

hao s rt nh, so vi bnh c thi gian s dng


cao cho ti n) v tiu th lin tc khng qu 50

batteries on light. load) and take no more than

mA.

50 mA continuously.
Where the batteries are not earthed, means

Ni m bnh c quy khng c ni t, th s c

shall be provided to detect low insulation

lp b d tm in tr cch n thp cho tt c dy

resistance of all wiring connected to the battery


by means of a centre-tapped earth fault relay.

dn c ni n bnh bng mt rle chm t.

The earth fault relay shall operate when the


insulation of the wiring connected to either pole

Rle bo v chm t s tc ng khi cch in


ca dy dn ni n cc bnh in gim xung n

of the battery drops to 50,000. When one pole

50,000. Khi mt cc ca bnh tip xc trc tip

of the battery is directly connected to earth then

vi t th dng chm t ln hn 5mA s chy

no more than 5 mA earth fault current shall flow.


The continuous drain from the battery shall not

qua. Dng x lin tc t bnh c quy s khng c


vt qu 10 mA. Rle s cung cp n 3 tip im

exceed 10 mA. The relay shall provide three

c lp pht ra tn hiu bo ng.

independent contacts for alarms.


The control circuit of the charger shall be of the

Mch iu khin ca s l loi bn dn. Nu cn

solid-state type. Whenever it is necessary to step

thit gim in p cung cp cho cc thit b in

down the D.C. voltage for feeding electronic


components, an A.C./ D.C. converter shall be

t, mt b bin tn A.C/ D.C s c s dng. Nu


s dng nhng in tr mc ni tip, chng phi c

utilized. If any series resistors are used instead

gi tr tng thch.

for this purpose, they shall be adequately rated.

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/24

J. Roger Preston Vietnam Co., Ltd


SECTION 3 H.V SWITCHBOARD AND RELATED EQUIPMENT

3.29 DEHUMIDIFIER

MC 3 T TRUNG TH & CC THIT B LIN QUAN

3.29 B RT M

Dehumidifiers shall be self-contained units with

B rt m s l thit b t cha vi thng lm bng

laminated steel case.

thp tm.

They shall be equipped with automatic humidity

Chng s c trang b b kim sot m t

control, dial adjustable, and shall have automatic


drain trap.

ng, mt iu chnh c chia vnh, v c b x t


ng.

The operation of the humidifier shall not cause

Hot ng ca b rt m s khng lm tng nhit

any increase in the ambient temperature of the


room.

xung quanh ca phng.

The dehumidifier shall be capable of removing


16 litres or more of water per 24 hours from the

B rt m c kh nng rt c 16 lt nc trong
khng kh hay nhiu hn trong 24 gi v s dng

air and shall operate from 230V 50 Hz single

ngun cp 230V 50 Hz mt pha.

phase A.C. supply.


The Sub-Contractor shall be responsible for all

Nh thu s chu trch nhim v nhng ng ng

pipeworks and pumps, if necessary, to discharge

lm vic v bm, nu cn thit, x nc n l

the water to the nearest floor trap or drain as


directed by the Engineer.

thot sn hay ng ng x th s c hng


dn trc tip bi Qun l K thut.

The English language version prevails


SECTION 3/VISTA VERDE SPECS/ ELECT

u tin s dng ting Anh khi c tranh chp


3/25