PACKAGE

PPH Catalog
Packaged Air Conditioning units
with Hermetic Compressor
3.0-53.0 T.R. @ 50 Hz
3.5-59.0 T.R. @ 60 Hz

R22
www.petra-eng.com
50/60 Hz Imperial

Abcde abcde

abcdefg

Petra Products
Equipment Description

Series

Air-Cooled Water Chiller (Semi Hermetic Reciprocating Compressors)


Air-Cooled Water Chiller (Semi Hermetic Screw Compressor )
Residential Air-Cooled Water Chiller (Hermetic Reciprocating & Scroll Compressor )
Water Cooled Water Chiller (Semi Hermetic Reciprocating Compressors)
Water Cooled Water Chiller (Semi Hermetic Screw Compressor )
Residential Water Cooled Water Chiller (Hermetic Reciprocating & Scroll Compressor )
Hot & Cold Residential Water Chiller
Centrifugal Fans Air-Cooled Water Chiller (Semi Hermetic Reciprocating Compressors )
Centrifugal Fans Air-Cooled Water Chiller (Semi Hermetic Screw Compressors)
Centrifugal Fans Residential Air-Cooled Water Chiller (Hermetic Compressors)

APX
APS
RWC
WPX
WPS
WRWC
HRWC
CPX
CPS
CRWC

Equipment Description
Fan Coil Units
Low Static Pressure Fan Coil
Medium Static Pressure Fan Coil
High-Wall Plastic Fan Coil
Stack Type Fan Coil
Air Side Control Fan Coil
Free Standing Decorative Units
Air Handlers:
Comfort Maker
Air Handling Unit (Modular Type)

Series
RAC
DC
PWC
RSU
ASC
FSW
CM
PAH

Exhaust Fan
Package Units With Hermetic (Reciprocating & Scroll Compressor)
Package Units With Semi-Hermetic (Reciprocating Compressor)
Water Source Unit
Self-Contained Wall Mount Air Cooled Package
Split Units
Ducted Split Unit (Low, Medium & High Capacity -Hermetic Compressor)
Ducted Split Unit (High Capacity-Semi Hermetic Compressor)
Ducted Split Unit (Centrifugal Condenser Fans Hermetic Comp.)
Mini Split Wall Type
Mini Split Universal Type (Floor & Ceiling)
Cassette Type Unit
Free Standing Units
Close Control Split Unit (Computer Room)
Air Cooled refrigeration Unit
Air Cooled refrigeration Unit (Cold Stores)
Unit Cooler
Unit Freezer

PPH
PPS
PWSP
PWM

DSP
DSPS
PECU
C/HPW
C/HPU
PCU
FSX
PASC
RFU
RCU
UC
UF
* For special cases where standard designs do not fulfill the customers requirements,
custom-made designs can be made available.

Smart Fan
Full Duty

PEXT
PEXS

Heaters
Unit Heater
Electric Heater
Duct Heater
Others
Dry Coolers
Package Unit With Natural Gas Heater
Heat Pump Application For All Dx Units

Note:
EMC certification applies to 50 Hz specifications only.
UL & ETL Marks applies on US & Canada markets' products

UH
EH
DH

Index
Main
Introduction
1
Model Number Nomenclature
1
Main Description
1
Specifications
2
Standard Features
3
Optional Features
3
Microprocessor Controller
5
Selection Procedure
6
Series Data
General Data 50 Hz
8
General Data 60 Hz
10
Model Layout-standard construction12
Model Layout-optional construction 16
Performance Tables 50 Hz
22
Performance Tables 60 Hz
25
Evaporator Coil & Filter Pressure
Drop Charts
28
Petra Fan Series
29
Electrical Information
Data Tables 50 Hz
34
Data Tables 60 Hz
35
Wiring Diagrams
36
Refrigeration Schematic Diagram
38

Introduction
PPH units are single packaged units which are factory assembled, tested and shipped fully charge complete with
compressor, evaporator and condenser coils, fans and controls. These packages are designed for outdoor
installation, and they used for cooling only or cooling and heat pump application (optional).
PPH units are ideal for residential, commercial and industrial applications and are available in nominal range 3.0 to
53.0 tons @ 50Hz and 3.5 to 59.0 tons @ 60Hz.
Quality design and construction make PETRA's air-cooled package units with hermetic compressors the preferred
choice for applications utilizing DX cooling systems. PETRA's PPH series is designed for flexible capacity
applications and easy installation and maintenance.
Easy Installation
PPH units are compact in design, supplied in a complete package ready for operation, with no extra controls or
additional items for installation. The PPH units have a single power point entry with simple connections. All units
are designed to ensure maximum compliance with European standards CE-Mark and EMC through TUV.
Quick start-up is assured once installation is complete, as each PPH unit is manufactured in an ISO 9001 listed
facility to guarantee quality. In addition, all units are tested at the factory to provide reliable start up.
Note:
For more technical details, please refer to the nearest Sales Office or to PETRA Factory.

Nomenclature
P
P
H
60

Petra
Packaged Air Conditioner
Hermetic Compressors
Unit Size (Nominal Capacity MBH)

Main Description
Quiet Operation

Capacities to Fit Requirements

PPH series are basically constructed and engineered with


noise reduction as a main consideration with low noise fan
mounting, fiber glass insulation for the evaporator section
and compressors mounted on vibration isolators.

There is a large product range of packaged units, with


capacities ranging from 3.0 to 53.0 tons @ 50Hz and 3.5 to
59.0 tons @ 60Hz refrigeration tons at nominal conditions.

Low Cost Installation


Units are factory assembled, pre-charged, tasted and
provided with a single electrical connection point. On
arrival to the job site they are ready to be lifted to their
operating position through the lifting supports available on
the units.

Specifications
Casing

Belt Drive Evaporator Fan (for models PPH 85 and


above)

Heavy gauge galvanized steel casing with oven baked


polyester-epoxy electrostatic powder coating, designed for
outdoor installation. Fiber glass insulation for the evaporator
section only.

Models PPH85 and higher are provided with forward curved


centrifugal DWDI [Double Width Double Inlet] type that are
designed for maximum efficiency and uniform air
distribution. All fans are V-belt driven with variable pitch
pulley (for fan motors with 5.5 kW and less only). All fans
are statically and dynamically balanced to ensure quiet
operation and optimal performance.

Compressor
The compressor(s) used is hermetic refrigerant gas cooled,
with internal thermal protection . Starting is direct -on- line
with high efficiency and low sound levels, to match all other
Petra products' reliability and efficiency.
Models PPH 40 up to PPH 105 are with reciprocating type
compressors while models PPH 115 and higher are with
scroll compressors.

Evaporator Fan Motors (for models PPH 85 and


above)
Motors are of the totally enclosed induction type, with
fan/motor assembly placed on a floating base with a flexible
connection at the fan/casing interface. The base itself is
mounted on rubber in sheer vibration isolators to eliminate
noise and vibration transmission to buildings. All fans
motors are of the single- speed type, four pole and highly
efficient, induction type motors, totally enclosed air-over,
squirrel-cage type, internal thermal current protected, IP55
protection and with class "F" insulation.

Evaporator and Condenser Coils


The evaporator and condenser coils are designed to deliver
their respective duties at optimum performance at all design
conditions. Coils are manufactured from seamless copper
tubes mechanically- expanded into aluminum fins. All coils
are tested at 450 Psi, air pressure, under water to avoid
leakage. They also undergo dry chemical cleaning after
manufacturing for optimum system cleanness.

Filters
All Models are provided with 1.0 inch thick aluminum flat
filter (as standard features). Other filters are available upon
request.

Direct Driven, Condenser Propeller Fans


All condenser fans are of the propeller axial type, which are
directly mounted on the motor shaft. All fans are selected for
optimum efficiency and for maximum sound power
reduction. Fan blades are made for maximum corrosion
resistance, and are statically and dynamically balanced
before installation. PETRA also provides its "Patented
Design" for condenser fans mounting. This new design
offers low noise operation with high efficiency. All
condenser fans are equipped with wire guards.

Drain Pan
All units are provided with a drain pan having a drain
connection from one side. The drain pan is insulated on the
sides and underside to prevent condensation.

Insulation
All units are internally lined with 1.0 inch thick fiberglass
insulation for the coil and fan section (evaporator side only).

Condenser Fan Motor


All fans motors are of the six poles, induction type motors,
totally enclosed air-cooled, squirrel-cage type, internal
thermal current protected, IP55 protection, with class "F"
insulation.

Direct Drive Evaporator Fans


Models PPH40, PPH50 and PPH60 are provided with
forward curved centrifugal fans of the DWDI [Double Width
Double Inlet] Type that are designed for maximum
efficiency and uniform air distribution. The fans are
statically and dynamically balanced to ensure quiet
operation and optimal performance Fans are 3-speed and
driven by permanent split capacitor electric motors, with
internal thermal protection.

Standard Features
b- Through the external timer for Petra Mark III
controller.
5. Crank case heater for each compressor.
6. Control circuit breaker.
7. 220 volt as control voltage.
8. Microprocessor controller for model PPH 85 and above,
with the following main functions:
a- Compressor lead-lag operation to ensure longer
life for the compressors and equal running hours
between compressors.
b- External remote ON/OFF button for remote
operation of the unit using external ON/OFF
switch or connection to building management
system.
9. One power supply input.
10. High (manual reset) and low (automatic reset) pressure
safety switches (Capsule type; factory pre-set).
11. For models PPH 105 and above, voltage monitor
controller (phase failure relay) for monitoring the main
incoming power supply for the unit, which provides
protection from single phasing, under voltage, phasevoltage imbalance and phase- consequence.

A) Construction standard:
1. Easily accessible system components.
2. Ample space for easy access to power and control panels.
3. Heavy duty mounting chassis for the whole unit with
lifting lugs.
4. Rubber anti-vibration mounting for the compressors.
5. Weather proof, polyester-epoxy powder electrostatic paint
oven-baked finish for sheet metal and multi polyesterepoxy coating for base frame.
6. All units are shipped out from factory tested with safety
and control devices set against client requirement.
7. Variable pitch pulley for evaporator motor (for motors of
5.5 kW and less).
8. Single skin evaporator side with 1 inch thick fiberglass
insulation.
9. All suction lines are covered with rubber insulation, and
for further protection, the lines that extends in the
condenser side are wrapped-in cheese cloth and epoxy
painted with the same compressor color.

B) Electrical features:

C) Refrigeration features:

1. Control and power panels include the direct on line


starting contactors for the compressors and condenser
fans' motor.
2. Internal thermal motor protector for condenser and
evaporator fan motor.
3. Compressor electronic internal thermal protection.
4. Anti-recycling protection for compressors (time delay):
a- Through microprocessor for Petra Mark IV
controller.

1. Hermetic suction gas cooled compressor motor.


2. Filter drier (disposable type).
3. Charging ports.
4. Service valve on liquid line.
5. Thermostatic expansion valve.
6. Fully charged unit with Freon R-22.
7. Solenoid Valve.

Optional Features
14. Economizer option with fresh, return and exhaust air
dampers with actuators.
15. Gas Heater.

A) Construction options:
1. Plastic mesh around condenser section perimeter.
2. Mixing box with manually operated fresh and return air
dampers.
3. Roof top arrangement (bottom air supply and return unit).
4. Roof curb mounting.
5. Bag filter.
6. Anti corrosion protection for coils fins (for copper /
aluminum coils only).
7. Copper/copper coils.
8. Hot water coil (built inside unit)
9. Synthetic fiber media for flat filter.
10. 2.0" or 4.0" thick flat filter or V-type filter.
11. Double skin evaporator side.
12. Different evaporator side insulation material.
13. 2.0" thick insulation for evaporator side only.

If this option is installed, the unit has the ability to work


with free cooling or free heating mode allowing it to exploit
the external environmental condition as much as possible,
since it avoids turning on the heaters and the compressors.
This function can be achieved by controlling the
opening/closing of the external air damper. With reference to
the difference between the outdoor air temperature
(STD)/enthalpy and the indoor air temperature/(STD)
enthalpy.

B) Electrical options:

C) Refrigeration options:

1. Power circuit breaker for each motor.


2. Main power molded case circuit breaker for the whole
unit (can also be with external handle as an option).
3. Low ambient control.
The refrigeration systems in all units are inherently
designed to operate efficiently, without extra controls or
modifications. To permit the unit to operate in low
ambient conditions, head pressure control can be installed
either by:
- ON/OFF Condenser fans sequencing (for models
with 2 condenser fans).
- Varying the speed of the condenser fan motor
using speed controller.
4. Disconnect service switch, a unit mounted non-fused
disconnect service switch with an external handle to
isolate the unit from the power supply for servicing.
5. Ampere meter and voltmeter installed on the electric
control panel door.
6. Earth leakage relay for each compressor.
7. Earth leakage relay for the whole unit.
8. External overload relay for each motor.
9. Power factor correction capacitors.
10. Auto or manual provision for pump down operation of
each compressor stop.
11. Building automation system interface. Interfacing with
other building management system can be achieved by
an optional card, which can communicate with other
devices using the serial communication port.
12. Electric heater for heating purposes (built inside unit for
cooling units only).
13. Electric heater (built inside unit) to supplement unit
operation in case of heat pump mode operation.
14. Special microprocessor controller with additional
feature, such as:
a- Economizer operation and control with free cooling
function.
b- Display of additional function (condenser pressure,
ambient temperature, return temperature, defrost
control, low ambient control, buzzer alarm etc.).
c- Time schedule and zone control.
15. Motor actuator for fresh, return and exhaust air dampers.
16. Voltage monitor controller (phase failure relay) for
monitoring the main incoming power supply for the
unit, which provides protection from single-phasing,
under-voltage and over voltage, phase voltage
imbalance and phase nonsequence (for models PPH 40
up to PPH 85).
17. Variable Air Volume (VAV) control.
18. Winter start relay.
19. General alarm out put relay.
20. Auto-manual evaporator fan operation for airflow
balancing.

1. Heat pump package unit with 4-way reversing valve,


suction accumulator is a standard feature in heat pump
option.
2. Pressure gauges for each refrigeration circuit (high/low
pressure gauges).
3. Other refrigerant application (R-134a and R-407c).
4. Hot gas bypass (where it is necessary to avoid low suction
pressure and "compressor cycling").
5. Extra refrigerant accessories such as suction accumulators
(for cooling units only), refrigerant liquid receivers, oil
separators, etc.
6. Solenoid valve for heat pump mode.
7. Liquid line sight glass.

Microprocessor Controller (Main Controller)


PETRA's microprocessor controller is engineered to meet
the most demanding requirements of all control and data
monitoring applications. It could be activated to perform
different functions for cooling and heat pump applications.

Microprocessor controller is a standard feature on all models.


allowing service technicians to inspect and maintain such
devices in the conventional manner.
For external communication, RS-485 (Industrial
Communication Protocol) interface is provided (optional).
An optional special communication adapter could be
provided to communicate directly with RS-232 serial
interface to provide complete supervision for all functions,
setting (configuration) and alarm condition. A special
software can communicate with a remote control room
through modems for monitor and controlling the unit.

However, in order to render the microprocessor control and


peripherals easy to use by all skill levels of service teams,
only necessary functions for safety sequence of operation
and alarm function are activated as standard. In standard
execution, while using the microprocessor for packaged unit
control, it communicates with the standard conventional
control such as high pressure , low pressure etc, thus

Petra Mark III Controller

Optional Advanced Controller (Petra Mark IV)

The Standard Petra Controller (Petra Mark III) provides


the following features:
1- Ease of use with a large LED display of a highly
attractive user friendly interface.
2- Ability to control units in cooling and heat pump modes.
3- Temperature readings C or F.
4- Controls activation of three heaters (optional).
5- Remote (ON/OFF) system selection.
6- Controlling activation of humidification and
dehumidification system (optional).
7- Extended wall mounted display for remote control and
monitoring of the package unit up to 150 meters using a
bipolar cable. (optional)
8- Safety and control time delays:A-Time delay between two subsequent starts of the
same compressor.
B- Time delay between activation of 1st and 2nd
compressor.
C- Time delay between heaters activation and of
supply fan speed variation.
D- Time delay for supply fan in start-up and shut
down.

The Advanced Petra Controller provides the following


features, in addition to all the standard features mentioned in
the Petra Mark III controller. This controller has the
following extra functions:
1- L.C.D display (4 lines *20 characters).
2- Complete message display.
3- Automatic pump down at each compressor stop.
(optional)
4- External analogue signal for remote modification of the
set point which also can be used for power demand limit
for the unit. (optional)
5- Historical alarm option which can save the last 1600
alarms.
6- Ability to be connected to a serial printer directly without
using a P.C. (optional)
7- Optional graphical display.
8- Super heat controlling. (optional)
9- Discharge or/and suction pressure readings. (optional)
10- Full alarm management with alarm message and an
audible alarm. (optional)
11- Ability to be connected to a building management
system using an optional card. (optional)
12- Supervisory and maintaining function with hardware
and software provided by Petra. (optional)
13- User-friendly interface display.
14- Time schedule by using an additional clock board.
5

Selection Procedure
This example illustrates a step by step selection procedure to assist any user of this catalogue to select the appropriate
package unit to meet specific requirements.

Design Condition Requirements


Total cooling load
Sensible cooling load
Ambient Temperature
Evaporator entering air temperature (DB/WB)
Evaporator air flow
External static pressure
Altitude

Altitude (ft)

530 MBH
350 MBH
95 F
80 / 67 F
15,000 CFM
0.5 of Water
3000 Ft

Sea Level
1000
2000
3000
4000
5000
6000
7000
8000

Unit Size Selection

Capacity
Correction
Factor
1
0.995
0.99
0.985
0.98
0.973
0.967
0.96
0.95

Using the correction factor table to correct capacity for altitude, the required capacity will be:
Corrected Capacity = Required Capacity / Correction Factor
= 530 / 0.985
= 538.1 MBH
Corrected Sensible Capacity = Required Sensible Capacity / Correction Factor
= 350/ 0.985
= 355.3 MBH
From the cooling capacity tables (Performance Tables on page 24, model PPH530 is the closest selection to the required
capacity. So, from the table:
Total Capacity = 542.5 MBH
Sensible Capacity = 361.9 MBH
Evaporator Fan Selection
1. Determine Evaporator Coil Face Velocity
From the general data tables on page 9, find the evaporator coil area ft2 .
Coil face velocity

= Air flow rate [CFM]/Coil Area [Ft2]


= 15000/32
=468.75 fpm

Filter Face Velocity

=468.75 fpm

Now use the coil and filter charts on page 28, using face velocity of fpm to get the coil pressure drop and filter pressure drop
which are about 0.33 inch [H2O] and 0.125 inch [H2O] respectively.
Calculate total pressure drop
Total static pressure drop = External Static pressure drop+Evaporator Coil pressure drop+filter Pressure drop
= 0.5+ 0.33+0.125
= 0.955 Inch of [H2O]

Now from the general data table on page 9 find the evaporator fan model to be PETRA 9 unit, From the fan curves on pages
30 with air volume of (16000 cfm) find the following:A. Dynamic pressure drop [Velocity pressure] at 16000 cfm to be inch of [H2O]
B. Determine total fan pressure drop:
- Total Fan pressure drop

= Total static pressure drop + Dynamic pressure drop


= 0.955 + 0.48
= 1.435 inch of [H2O]

Now from the fan curve with 7500* cfm and 1.435 H2O we get the following:
1) Revolution / miniature impeller
2) Absorbed power

: 585 RPM
: 1.75 KW

*From the above data the following must be done to get the data for the double fans (this unit has 2 fans)
1) RPM should be multiplied by * 1.05, so
585 * 1.05 = 614 RPM (approximately)
2) The absorbed power should be multiplied by * 2.15, so
1.75 * 2.15 = 3.76 kW (approximately)
3) The motor kW can be obtained by adding power correction , (i.e 20%), so
3.76 * 1.20 = 4.512 kW
= 5.5 kW ( from the standard motors)
- Sound power level: from the general data tables on page 9, the sound pressure level at
10 ft=78.0 dB(A)
33 ft=72.0 dB(A)
*note:when the unit has two evaporator fans, the following should be done:
1) CFM should be divided by 2
2) RPM should be multiplied by * 1.05
3) The absorbed power should be multiplied by * 2.15

Model Layout - Optional Construction


With Bag Filter

16

Model Layout - Optional Construction


With Mixing Box

17

Model Layout - Optional Construction


With Mixing Box & V. Filter

18

Model Layout - Optional Construction


With Economizer & Return Fan

19

Model Layout - Optional Construction


Rooftop

20

Model Layout - Optional Construction


Rooftop With Gas Heater

21

Petra Fan Series

Total Pressure Drop [inch of water]

Petra 4

1.20
1.08
0.96
0.84
0.72
0.60
0.48
0.36
0.24
0.12
0

235 471 706 942 1177 1413 1648 1884 2119 2354 2590 2825

Air Flow Rate [CFM]

Note: This curve is for direct drive fan - 3 speed

29

Petra Fan Series


Petra 8

4.40
4.00
3.60
3.20
2.80

Total Pressure Drop [inch of water]

2.40
2.00

1.60

1.20

0.80

0.60

0.40
0.36
0.32
0.00
0.90

1.18

1.47

1.77

2.35

3.00 3.53 4.12 4.71 5.30 5.89

8.83

11.77

Air Flow Rate [CFM] * 1000

0.2

0.4

0.8

1.2 1.6 2.0

4.0

8.0

12.0 16.0 20.0

Fan Dynamic Head [inch of water] 10


31

Petra Fan Series


Petra 9

4.00
3.60
3.20

Total Pressure Drop [inch of water]

2.80
2.40
2.00

1.60

1.20

0.80

0.60

0.40
0.36
0.32
0.00
1.77

2.35

3.00

3.53 4.12 4.71 5.30 5.89

8.83

11.77

17.66

Air Flow Rate [CFM] * 1000

0.2

0.4

0.8

1.2

1.6 2.0

4.0

8.0

12.0 16.0 20.0

40.0

Fan Dynamic Head [inch of water] 10


32

Petra Fan Series


Petra 19

14.00
12.00

Total Pressure Drop [inch of water]

8.00

4.00

2.00
1.60
1.20

0.80

0.40
0.32
1.27

2.12

4.24

6.36

8.47 10.60

21.19

42.37

63.57

95.34

Air Flow Rate [CFM] * 1000


0.04

0.2

0.4

2.0

4.0

20.0

40.0

Fan Dynamic Head [inch of water] 10


33

Typical Wiring Diagrams

36

Typical Wiring Diagrams

37

Refrigeration Schematic Diagram

38

International Distribution Offices

United Arab Emirates


Abu Dhabi - Petra Air Conditioning Est.
Tel (9712) 6391308 Fax 6211027
Dubai - Saif Inter national Group
Tel (9714) 2958989 Fax 2958990
Lebanon - Petra Liban Ltd
Tel (9611) 663573 Fax 646209
West Bank - Petra International Export Co. Ltd.
Tel/Fax (9702) 2960701
Tunisia - Tunis Universal Petra
Tel/Fax (216) 71441960
Egypt - Ain Shams Company
Tel/Fax (202) 2754463/72
Saudi Arabia - Peninsular Distribution Company Ltd.
(An Abdul Latif Jameel Group Company)
Tel (9662) 6930000 Fax 6283923

Kuwait - Nouri Industrial Est.


Tel (965) 4333355 Fax 4344085
Qatar - Ajjaj Trading Co. (W.L.L.)
Tel (974) 4691546 Fax 4687258
California - USA
Air Treatment Corporation
Tel (909) 8697975 Fax 5985265
Pennsylvania, Maryland, Delaware
and Parts of New Jersey - USA
Peirce - Phelps, Inc.
Tel (215) 8795079 Fax (215) 8795141
North New Jersey and New York City - USA
DEBTRA A/C Sales
Tel (973) 4292828 Fax (973) 4294909
e-mail: debtraac@aol.com
Upstate New York and Vermont - USA
Advanced Comfort Systems
Tel (518) 8848444 Fax (518) 8848411

Pakistan - Genaire (PVT) Ltd.


Tel (9221) 4534161 Fax 4538162

Quality Management System ISO 9001;2000 and Environmental Management System ISO
14001;1996 Certification applies to Jordan Office only
Copyright 2002 By Petra Engineering Industries Co.
Design & Layout Copyright 2002 By Petra Engineering Industries Co.
ALL MODELS SIZES AND DIMENSIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

Offering You a Different Choice


Choice

ENGINEERING INDUSTRIES CO.

Headquarters
P.O.Box 141351 Amman, 11814 JORDAN
Factory Tel (962 6) 4051055 Fax 4051228
Marketing Tel (962 6) 5531508 Fax 5531513
Local Sales Tel (962 6) 4051425 Fax 4051248
International Sales Tel (962 6) 4051050 Fax 4051087
North/South America Sales Tel (962 6) 4051425
Fax (In the US) (888) 5226610 - (877) 4723010
LOCAL BRANCHES
Amman: Tel (962 6) 5531508 Fax 5531509
Mecca Street: Tel/Fax (9626) 5850553
Marj Alhamam: Tel (962 6) 5716151 Fax 5712008
Irbid : Tel/Fax (962 2) 7252406
Aqaba : Tel (962 3) 2019189 Fax 2019728
e-mail:petrasho@go.com.jo

www.petra-eng.com

PP/PPH-R22-50-60 Hz-Imp/2002/rev.0