Addressable Input Module (AIM)

Addressable Contact Input Device

A UTC Fire & Security Company

Effective: January 2011


K-74-214

FEATURES

Monitors N.O. or N.C/ Unpowered Contacts


Full Digital Communications
Class B Initiating Device Circuit
Remote-led Output
Alarm Test from Control Unit Keypad
UL Listed #S3743
FM Approved #ODA9AY
CSFM #7300-1076:144

DESCRIPTION
The SmartOne Addressable Contact Input Device (AI)
is an intelligent field device with its own microprocessor,
memory and electronics necessary to interface N.O. or
N.C. unpowered contacts to the ARIESNET control
units. All of the electronics are contained in a high-impact
polymer case, creating a very small and durable device
for installation.
Two types of AI's are available: an AI/NC for interfacing
to normally-closed devices and an AI/NO for interfacing
to normally-open devices. The AI may be located up to
2,500 feet from the monitored device with #18 AWG wiring. An end-of-line-resistor is required for supervision of
the wiring to the device.

FIELD PROGRAMMING
System address, owner location message and reporting
type are programmable via the compatible control unit
configuration software program.
The System address is a 4-digit number that uniquely
identifies each device. The owner location message is a
40-character, alpha numeric message that describes the
location of the device. The reporting type is assigned to
the AI depending on the functionality of the device being
monitored.

SUPERVISION
The AI continuously monitors the integrity of the following:
Continuity of supervised wiring
Power/Communications circuit voltage
Internal power supply
Memory data
Faulty entering of data into AI memory

ALARM TEST
Any or all AIs can be tested by command from the compatible control unit. Results of the test may be printed out
at the system printer.

SPECIFICATIONS
Input Voltage:
16.5 - 27.5 VDC
Standby Current:
450 mA Max
Alarm Current:
450 mA Max
Operating Temperature:
-31 - 151oF (-35 -66oC) 0 - 95% RH
LED PULSE MODES
Normal:
9 second interval
Trouble:
LED is off
Alarm:
2 second interval
Acceptable Wire Size:
14, 16, 18 AWG
Installation:
The AI can be mounted in a North American 2-1/2-in.
(64 mm) deep, 1-gang box, or standard 4-in. square
box,1-1/2-in. (38 mm) deep with cover.

STATUS LED
A remote status LED may be connected to the AI.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular question, contact
KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-74-214 Rev. AB

2011 Kidde-Fenwal Inc.

Printed in USA.

A UTC Fire & Security Company


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com

Addressable Signal Module (ASM)


A UTC Fire & Security Company

Effective: January 2011


K-74-234

FEATURES

Full-digital communications
Addressable notification-appliance circuit (NAC)
Class Aor Class B wiring on NAC
Field-programmable for 24-VDC notification
appliances or 25 Vrms speakers
Supervises power for notification appliances
UL Listed and FM Approved #3005511
CSFM Approved

DESCRIPTION
The SmartOne Addressable Signal Module (ASM) is a
notification-appliance circuit that connects to the signaling line circuit of a compatible control unit. The ASM is an
intelligent field device that contains its own microprocessor, memory and the necessary electronics to provide
either 24 VDC for conventional notification-appliances or
25 Vrms for speakers.

MAXIMUM LINE RESISTANCES (#12 AWG WIRE)

PROGRAMMING
Each ASM can be configured to support speakers or
audible-visual notification appliances, and Class B or
Class A operation. The module can also be programmed
to support water flow, walk test, and drill modes. As with
any SmartOne device, addressing can be implemented
from the hand-held programmer (P/N 74-227) or the control panel keypad/menu. The Module can also be alarm
tested upon command from the control unit. Module
faults are individually reported to compatible control units
by module address, fault type, and fault-location message.

SUPERVISION
The module provides continuous internal supervision of:
Alarm contact position
Communications with the control unit
Internal power supply
Connections to external power supply for notificationappliances
Memory status module supervision prevents switching
audible or audio power into a shorted circuit.
A status LED is mounted on the unit.

SPECIFICATIONS
OUTPUT CIRCUIT CHARACTERISTICS

Output Current Rating:


2.0 A max. @ 30 VDC
20 W @ 70.7 Vrms or 20 W @ 25.0 Vrms

2011 Kidde-Fenwal Inc.

Printed in USA.

Resistance
(ohms)

Length
(ft.)

0.2

20.0

12.0K

0.5

8.0

5.0K

1.0

4.0

2.5K

1.5

2.7

1.6K

2.0

2.0

1.2K

Mounting
The unit can be mounted in a 4-inch x 4-inch electrical box.
Shipping Weight
10.5oz (298g)
Current Draw
500 uA in standby or alarm
Notification-Appliance Circuit Output
24 VDC, 2 A (max.), power limited, reverse polarity
supervised
Audio Circuit Output
25 V , 20 W (max.), non-power limited,
reverse polarity supervised
Power Supply Trouble Circuit End Of Line Resistor
4.7Kohms, 0.5 W
Operating Range
-31 F to 151 F, (-35 C to 66C)
0 to 95%, non-condensing

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular question, contact
KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-74-234 Rev. AB

Load
(amps)

rms

A UTC Fire & Security Company


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com

Addressable Output Module (AOM)


Addressable Relay Output Device

A UTC Fire & Security Company

Effective: January 2011


K-74-215

FEATURES

Full-Digital Communications
Addressable Control Point
Unpowered, SPDT Relay Contacts
Control-by-Event And/or By Time Operation
Status Indicator
Unique Internal Supervision
UL Listed and FM Approved
CSFM Approved

DESCRIPTION
The SmartOne Addressable Relay Output Device (AO)
is an addressable output module for control of auxiliary
equipment such as air handlers, door release and elevator recall.
The AO connects directly to a compatible control unit's
signaling line circuit (SLC) and contains a SPDT relay to
control auxiliary equipment. All of the electronics are contained in a small high-impact polymer case. This creates
a small and durable device for installation.

FIELD PROGRAMMING
The AO is field programmable with a unique four-digit
address and a 40-character owner location message.
The AO relay may be set or reset on command from the
control unit.
In addition to combinational-logic programming that utilizes system inputs (i.e., events) to activate this device,
the unit may be programmed for real-time clock operation. The real-time clock programming permits the AO to
be activated and deactivated by the time of day, calendar
date and day of the week.

SUPERVISION
The AO is continuously monitored for:
Internal power supply voltages
Faulty entering of data into AOs memory
Relay state equals command state
An internal set of relay contacts provides a feedback signal that confirms the activation of the addressable relay
output. If the relay fails to operate at the appropriate time,
the device transmits a trouble report for display by the
control unit.

SPECIFICATIONS
Input Voltage: 16.5 - 27.5 VDC
Standby Current: 400 A, Typical
Alarm Current: 400 A, Typical
Contact Ratings:
Resistive Contact Rating: 2 A @ 30 VDC
Inductive Rating (Motor Control):
1.0A @ 30 VDC, 0.6 PF.6A @ 120 VAC, 0.35 PF
Pilot Duty : 0.6A @ 30 VDC, 0.35 PF
Operating Environment:
-31F - 151oF (-35C - 66o C) at 0-95% RH
EMI Immunity: Meets UL 864
Dimensions:
2.3" x 1.8" x 0.8" nominal
Shipping Weight:
5.1 oz (145g)
LED Pulse Modes:
Normal: 9 second interval
Trouble: LED is off
Alarm: 2 second interval
Acceptable Wire Size: 14, 16, 18 AWG
Installation:
The AO can be mounted in a North American 1-1/2-in.
(64 mm) deep 1-gang box, or standard 4-in. square box
1-1/2-in. (38 mm) deep with a cover.

STATUS LED
A status LED is mounted on the unit.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the products suitability for a particular application. The product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular question, contact
KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-74-215 Rev. AB

2011 Kidde-Fenwal Inc.

Printed in USA.

A UTC Fire & Security Company


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com

Remote Releasing
Module (RRM)

TM

74.238 K

FEATURES

Up to 64 RRMs Per Signaling Line Circuit


Supports Both Gaseous and Pre-Action/Deluge
Sprinkler Systems
Triple R Protection Against Inadvertant
Extinguishing-System Activation
Versatile Mounting Configurations
5 Year Warranty
UL Listed, FM Approved

DESCRIPTION
The Remote Releasing Module (RRM) is a SmartOneTM field
device that provides the ability to remotely activate extinguishing-system control devices via the ARIES Control Panel
Signalling Line Circuit (SLC). The control units SLC supports
a maximum of 64 RRMs. Up to 16 RRMs can be configured
for simultaneous group activation with a maximum of 4 groups.
The RRM provides internal supervision of communication with
the ARIES Control Unit, connections to external power supply and memory status.
Release circuits are power-limited and supervised for short
circuit by using an In-line Releasing-Circuit Device
(P/N 06-220023-001). In the event of a ground fault, open,
short or a relay contact failure, the device will transmit a trouble
status to the ARIES Control Unit.

PROGRAMMING
As with any SmartOne device, addressing can be implemented
from the hand-held programmer (P/N 74-100013-001) or from
the ARIES Control Unit keypad menu. A 24VDC power supply is required for the RRM to program with a hand-held programmer.

STATUS LED
A status LED is mounted on the unit and indicates the modules
status.

Normal, Standby: flash at 9-second repetition rate


Output Active: On steady
Trouble: Off

INSTALLATION
The RRM can be mounted in the following:
P/N 70-600000-001 : Standard Mounting

North American 4-11/16 in. electrical box with a double


gang plaster ring (Rayco Model 841 or equivalent),
1/2 in. raised

4 in. square, 2-1/8 in. deep electrical box

P/N 70-600000-002 : In-Cabinet Mounting

Any UL-864 Listed enclosure with no other


electronics.

Terminal connections support wiring from #18 AWG to


#12 AWG. Wire sizes determine electrical box depth.
Once Installed and configured, the RRM requires little or no
maintenance.

ORDERING INFORMATION

SPECIFICATIONS
Item
SLC Wiring
Configuration

Activation

Description

Part Number

Remote Releasing Module


(With Standard Bracket and Front Cover Plate)

70-600000-001

Remote Releasing Module


(With In-Cabinet Bracket and Mounting Hardware)

70-600000-002

Inline Releasing-Circuit Device (One Required For Each


Release Circuit to be Supervised and Power Limited)

06-220023-001

Description
Class B, Style-4
Class A, Style-6
Class A, Style-7
Up to 64 RRMs per SLC (Activated
Consecutively)
Up to 4 Groups of 16 RRMs per group
(RRMs in a group activate simultaneously, groups
activate consecutively)

Releasing Circuit
2.4A Max. @ 24.0 VDC
Output Current
Operating Voltage 24 VDC Nominal
Trouble Circuit
Input

Power
Consumption

Environmental
Criteria

Construction
Shipping Weight

4.7K End of Line Resistor


"Open" contact = normal condition
From Power Supply:
Normal, Standby: 6.1 mA
Alarm: 45 mA
From SLC:
Normal, Standby: 410 A
Alarm: 410 A
Indoor/ Dry location use only
Operating Temperature range: 32F to 120F
(0C to 49C)
Humidity: 93% 2% RH at 90F 3F
(32C 2C)
High Impact Polymer Faceplate with a 16 gauge
Aluminum Bracket
10.5 oz (298 g)

The following power supplies are compatible with the Remote


Releasing Module.
Description

Manufacturer

Part Number

Multi-Zone Power Supply Assembly (used


with P/N: 77-297107-000 enclosure and
cables)

Kidde

77-297106-000

24 VDC, 1 A Auxiliary Power Ouput of


ARIES Control Unit, qty 2 (See Note 1)

Kidde

76-600000-001

24 VDC, 3A Power Supply, red enclosure

Altronix

AL 400ULX

24 VDC, 3A Power Supply, grey enclosure

Altronix

AL 400ULXR

24 VDC, 6A Power Supply, red enclosure

Altronix

AL 600ULX

24 VDC, 6A Power Supply, grey enclosure

Altronix

AL 600ULXR

24 VDC, 8A Power Supply, red enclosure

Altronix

AL 1024ULX

24 VDC, 8A Power Supply, grey enclosure

Altronix

AL 1024ULXR

Notes: 1. Both auxiliary circuits may be wired together to


obtain 2 A at 24 VDC.
2. Altronix power supplies may be ordered through
an authorized Altronix dealer. For a list of dealers,
visit www.altronix.com or call (888)-258-7669.

TM

Kidde Fire Systems


400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX (508) 881-8920
www.kiddefiresystems.com

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no responsibility for the product's suitability for a particular application. The product must be properly applied to
work correctly.
If you need more information on this product, or if you have a particular problem or question, contact
KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
Rev. AA

2006 Kidde-Fenwal, Inc.

Printed in U.S.A.