Beruflich Dokumente
Kultur Dokumente
AND
EARL F. RICHARDS
Transformer 1
Transformer 2
3-Phase
) Induction
Motor
SinglePhase
Load
(a)
VCA
XB
VA
AB
Q>..
INTRODUCTION
VCA
VBC
(b)
(c)
480
V~ ~r
An open-delta distribution system, which serves a singlephase load and 3-phase induction motor, was analyzed by
Anderson and Ruete [2] and by Bankus and Gerngross [3] in
papers written in 1954. Voltage unbalance on open-delta
systems was discussed in both papers. Anderson and Ruete
derived general equations which could be used to calculate
voltage unbalance. Bankus and Gerngross recommended transformer sizing that would result in a low voltage unbalance and
in maximum utilization of transformer kVA. In a later paper,
Bankus and Gerngross [41 compared the advantages and disadvantages of using either the open-delta leading or open-delta
lagging transformer connections.
Williams [10] analyzed the effects of voltage unbalance on
motor operation and concluded that the unbalanced voltages
cause increased motor losses and uneven heating. Gafford et al.
[7] attributed the rise in motor temperature under unbalanced
conditions to increased copper losses and unbalanced spatial
distribution of stator heating.
More recently, investigations have been made on the spatial
distribution within the motor of the heat resulting from
unbalanced voltages, and methods of derating motor loads to
prevent insulation failure have been proposed. The two
extremes for determining the amount of derating necessary are
presented in discussion by Lee [5, pp. 684-685] and the paper
by Berndt and Schmitz [5]. Lee assumed that the thermal
impedance between stator windings was negligible; therefore,
any additional heating caused by unbalanced voltages is evenly
distributed among all three windings. Therefore, Lee concluded to prevent insulation failure, the motor load should be
derated until the total losses in the stator windings do not
exceed the losses under rated conditions. On the other hand,
Berndt and Schmitz assumed that the thermal impedance
between windings was infinite. According to their theory, the
motor load should be derated until the maximum current in
any phase is equal to or less than rated current. Whereas Lee
presented an optimistic derating of the motor load, Berndt
and Schmitz were overly pessimistic. Later, Rao and Rao [81
presented two additional methods of motor derating by taking
into account winding and insulation details. Because the
methods of motor derating presented by Lee and Berndt and
Schmitz require a minimum knowledge of motor construction,
they were considered in this paper.
APPLICATIONS. SEPTEMBER/OCTOBER
Open-Delta
Transformer
Bank
Fig. 2.
Service
Lead
j (X
Induction
Motor
R +(1-s)
r
S
+x
Rr (a -1)
(2-s)
System Equations
LVbcJ
(Zl + 2ZL
LZL
ZC
2ZC)
Cable
R5
A.
Phase
Load
Fig. 3.
Fig. 4.
Single-
1976
(Zi
2ZC)
ZL _I[
Z, _
I2
(1)
For simplicity, (1) can be written
Vt
[Z] I +
V.
(2)
481
LVab
VPs= [Al Vt
(a)
a
a 21
aI
C
(b)
Fig. 5. Three-phase sequence models of an induction motor. (a)
Positive sequence model. (b) Negative sequence model.
+RS
+ Rr+/S +
j(Xs
+ Xr+)
I= (1 -a)I+ + (I -a2)f-
and
(3)
I3-
and
Z-=RS +
- s)
+
(2- S) (XS XrJ)
[a+
= z
Z+
IVab
Lab-
01P
o
L
z-
(5)
I2
I
_
[ZS] IS.
(6)
IVabI =-[I
Vah b
where
a-=1Zl200
a
a2
RVBC
(2 + 2ZL + Zl)
Iva
(2 + 2ZL + Zl)
(13)
or
VS=
(4)
(12)
1RiXm
X
(R i +4 jXm )
Rr
(11)
in which
Z
(10)
(9)
(8)
Z+
(1 -a)
(1 -a2)
(a
(a2
jjVbcj
a)
a2)
a2 IVab
a
a2)
(2 + 2ZL + ZI)
(14)
(7)
I-
1 JLVca
or
Ia=
[W] Is
+ It2
(15)
482
(16)
With a knowledge of the input voltages and circuit elements, (16) can be solved for the currents in the motor
sequence models. The line currents at the motor terminals can
then be calculated from (1 5). The sequence voltages at the
motor terminals -P. are determined by iniserting the values of
I into (5). The line to line terminal voltages are then calculated by rearranging (9) to obtain
Vt=
[AI-' Vs.
(17)
k152Rs
(18)
in which
is
total curretnt in Rs
(see Figs. 3 and 4)
and
R
kS=Tdesigned
israted 2RS
k
B. Motor Losses
The prediction of the spatial distribution of heat in an
induction motor is an extremely difficult problem. The wide
variety of induction motors make any general analysis difficult
by requiring intricate details of motor construction.
To keep the computer program in this study as general as
possible and to keep to a minimum the amount of knowledge
of motor construction required, the two methods of derating
presented by Lee [5. pp. 684-685] and Berndt and Schmitz
[5] were considered. Neither method can predict the exact
amount of derating necessary, but they do determine the
bounds which should be considered. These restrictions and
considerations, along with experience and engineering judgment, can then be employed to determine proper derating.
Unbalanced voltages cause an increase in rotor copper loss
[7], [9]. This loss can be calculated by adding the powers
dissipated in Rr+ and Rr,- for all three phases (see Figs. 3 and
4). In some cases, such as machines having deep bar or double
cage rotors, this loss can become significant in determining the
critical temperature [5], [7], [9]. Both derating methods
presented by Lee and Berndt and Schmitz assume that the
rotor copper loss has a neglgible effect on motor operation.
In many motors, the stator copper loss is the determining
factor for derating the motor load [51, [8]. The losses in R,
(the resistance of each of the stator windings) can be calculated from circuit theory (see Figs. 3 and 4). As a resuLlt of the
unbalanced line currents, these losses are not equal in each
winding. It is here that the two theories presented by Lee and
by Berndt and Schmitz differ. Lee assumed that the thermal
impedance between stator windings is negligible; therefore,
the temperatures of all three phases are equal and proportional
to the average of the powers dissipated in the stator windings.
On the other hand, Berndt and Schmitz assumed that the
thermal impedance is infinite and that overheating will result
in the phase dissipating the most power. Neither theory is
completely correct. The actual critical temperature lies
between the two estimates.
Past evidence has shown that for approximately each 10cC
rise in winding temperature, the insulation life is roughly
halved [1] . To estimate the effects of the unbalanced voltages
( 19)
(20)
VlkP2
kVA
483
and
z1k+1
READ DATA
=I
(22)
()
+3
r-12
2R
(-)
(23)
746 (hp) -P
-E/(aE/ls)
(25)
in which
aE[
-= 3IrI+2R
+ 3 Ir-
3
1
L+
(l-s)1
___
rL(2
~~(s
(21s)2J
l)
(26)
IZ 2400.
(24)
guess
sk+l = Sk
(16) _
desired.
In addition to knowing the impedance of the single-phase
load, (16) also requires that the slip of the induction motor be
specified. This is impractical because the programmer may not
always know the value of slip when the motor is operated at
other than the rated load or under unbalanced conditions. A
more reasonable quantity to specify is the output horsepower
of the motor. To achieve this, a second iteration loop is
included in the program. Equation (16) is originally solved by
using the value of slip the motor would have when operating
at nameplate speed. The power output of the motorP is then
determined by summing the power outputs of the motor
sequence models to give
P = 3 Ir+ 12R+
Perit-=
(27)
rated
hpd k+l
hpk -hP k
(Pcrit
(Pcrit
Prated)
hPrated)
(28)
in which
Prated
Rs(Israted)2
(29)
484
1976
230
En
4
0
r-
4D
.,1-
Ee
.d
5
C)
Computer
a)
Program
Laboratory Data
-4
0I
.4
Computer
Program
Laboratory
150
Data
Fig. 7.
rated
iS the
maginitude of the
Ccurrent in
Rs under- balanced
0.850
Single-Phase Load
KVA
in
I ig. 8.
1or
--Computer
f/-
Iig. 9.
Comnparison
Sinqle-Phase Load
of
Program
Laboratory Data
--
,,-
in
KVA
485
Voltage unbalance
Maximum stator heating (optimistic)
Estimated temperature (optimistic)
Maximum stator heating (pessimistic)
Estimated temperature (pessimistic)
2. Or
U4
U)
1. 5
I.
0.,
II.\
'-4
'0
.4-
0.
5-
a)
Fig. 10.
EXAMPLE OF AN APPLICATION OF
THE COMPUTER PROGRAM
A theoretical system was analyzed in a computer program
with the analysis presented in this paper. The system consisted
of a leading open-delta transformer bank serving a single-phase
load and 3-phase induction motor. Transformer ratings were
assumed to be 5 and 37.5 kVA, respectively. The single-phase
load was assumed to be 20 kVA at 0.9 power factor and
supplied by the larger of the two transformers. The 3-phase
induction motor was a 10 hp, 240 V, 4 pole, 60 Hz motor
having class B winding insulation. Motor constants were
assumed to be
REFERENCES
[1] P. L. Alger, The Nature of Induction Machines. New York:
Gordon and Breach, Science Publications, Inc., 1965.
[21 A. S. Anderson and R. C. Ruete, "Voltage unbalance in delta
secondaries serving single-phase and 3-phase loads," AIEE
Trans., vol. 73, pt. IIIA, August, 1954, pp. 928-932.
[31 H. M. Bankus and J. E. Gerngross, "Unbalanced loading and voltage unbalance on 3-phase distribution transformer banks," AIEE
Trans., vol. 73, pt. IIlA, April, 1954, pp. 367-376.
"Combined single-phase and 3-phase loading of open-delta
[41
transformer banks," AIEE Trans., vol. 76, pt. III, February,
1958, pp. 1337-1 343.
[5] M. M. Berndt and N. L. Schmitz, "Derating of polyphase induction motors operated with unbalanced line voltages," AIEE
Trans., vol. 78, pt. IIIA, February, 1963, pp. 680-685.
[6] E. Clarke, Circuit Analysis of A-C Power Systems, vol. 2. New
York: Wiley 1950.
[71 B. N. Gafford, W. C. Duesterhoeft, and C. C. Mosher, "Heating
of induction motors on unbalanced voltages," AIEE Trans.,
vol. 78, pt. IIlA, June, 1959, pp. 282-288.
[8] R. N. Rao and P. A. D. Rao, "Rerating factors of polyphase
induction motors under unbalanced line voltage conditions,"
IEEE Trans. Power App. Syst., vol. PAS-87, January, 1968,
pp. 240-248.
[9] S. C. Seematter and E. F. Richards, "Comptuer analysis of 3phase induction motor operation on an open-delta distribution
system," University of Missouri-Rolla Power Research Report,
PRC-7401-RS, April, 1974.
-,
Rs
Rr+
0. 1 53 ohm
per phase
Rr-= 0.507
Xn
Xs + Xr'
Xs + Xr-=
per phase.
1.7 percent
60 W
1240C
72 W
1 420C.
486
[10] J. E. WiUiams, "Operation of 3-phase induction motors on unbalanced voltages," AIEE Trans., vol. 73, April, 1954, pp. 125133.
1i
1i
\
NX'e
A-l"VI-
;.
I ._-,
.A
X, > F,-. i
;-Yb- 4S',.St/-'n-'
Nt
-1
'7V
D,i &
Abstract-The background of rising costs in the production, trans- f,well as transmission lines, distribution substations, distribution
mission, and distribution of electric power and energy is discussed and,lQ.lines, and everything else right up to and including the service
in particular, the significant increases in the cost of generation. It disof a consumer's home have increased in cost by a
cusses the adverse annual load pattern experienced by Buckeye Power,
Inc. and the electnc water heater control program of load managemenf
powe--i.not
cescrap